WorldWideScience

Sample records for treed xlpe cable

  1. Nonlinear Dielectric Response of Water Treed XLPE Cable Insulation

    Energy Technology Data Exchange (ETDEWEB)

    Hvidsten, Sverre

    1999-07-01

    Condition assessment of XLPE power cables is becoming increasingly important for the utilities, due to a large number of old cables in service with high probability of failure caused by water tree degradation. The commercial available techniques are generally based upon measurements of the dielectric response, either by time (polarisation/depolarisation current or return voltage) or frequency domain measurements. Recently it has been found that a high number of water trees in XLPE insulated cables causes the dielectric response to increase more than linearly with increasing test voltage. This nonlinear feature of water tree degraded XLPE insulation has been suggested to be of a great importance, both for diagnostic purposes, and for fundamental understanding of the water tree phenomenon itself. The main purpose of this thesis have been to study the nonlinear feature of the dielectric response measured on watertreed XLPE insulation. This has been performed by dielectric response measurements in both time and frequency domain, numerical calculations of losses of simplified water tree models, and fmally water content and water permeation measurements on single water trees. The dielectric response measurements were performed on service aged cable samples and laboratory aged Rogowski type objects. The main reason for performing laboratory ageing was to facilitate diagnostic testing as a function of ageing time of samples containing mainly vented water trees. A new method, based upon inserting NaC1 particles at the interface between the upper semiconductive screen and the insulation, was found to successfully enhance initiation and growth of vented water trees. AC breakdown strength testing show that it is the vented water trees that reduce the breakdown level of both the laboratory aged test objects and service aged cable samples. Vented water treeing was found to cause the dielectric response to become nonlinear at a relatively low voltage level. However, the measured

  2. Analysis of electrical tree propagation in XLPE power cable insulation

    International Nuclear Information System (INIS)

    Bao Minghui; Yin Xiaogen; He Junjia

    2011-01-01

    Electrical treeing is one of the major breakdown mechanisms for solid dielectrics subjected to high electrical stress. In this paper, the characteristics of electrical tree growth in XLPE samples have been investigated. XLPE samples are obtained from a commercial XLPE power cable, in which electrical trees have been grown from pin to plane in the frequency range of 4000-10,000 Hz, voltage range of 4-10 kV, and the distances between electrodes of 1 and 2 mm. Images of trees and their growing processes were taken by a CCD camera. The fractal dimensions of electric trees were obtained by using a simple box-counting technique. The results show that the tree growth rate and fractal dimension was bigger when the frequency or voltage was higher, or the distance between electrodes was smaller. Contrary to our expectation, it has been found that when the distance between electrodes changed from 1 to 2 mm, the required voltage of the similar electrical trees decreased only 1or 2 kV. In order to evaluate the difficulties of electrical tree propagation in different conditions, a simple energy threshold analysis method has been proposed. The threshold energy, which presents the minimum energy that a charge carrier in the well at the top of the tree should have to make the tree grow, has been computed considering the length of electrical tree, the fractal dimension, and the growth time. The computed results indicate that when one of the three parameters of voltage, frequency, and local electric field increase, the trends of energy threshold can be split into 3 regions.

  3. THE EFFICACY OF THE CABLES OF 6–110 KW WITH XLPE INSULATION. Part 2

    Directory of Open Access Journals (Sweden)

    M. A. Korotkevich

    2017-01-01

    Full Text Available The assessment of the suitability of cables of 6–110 kW with XLPE insulation in comparison with cables of the same voltage but possessing paper-oil insulation has been fulfilled on the basis of the method of multi-objective optimization that makes it possible to account not only the quantitative characteristics (of reduced costs, but also qualitative ones. As an indicator of the reliability of the cable line the maximum mean time to failure (the value inversely proportional to the parameter of succession of failures, which is an order more for cable lines with XLPE insulation than for cable lines with paper insulation, is adopted. A comprehensive assessment of the convenience of installation of cable lines revealed that the installation of cable with XLPE insulation features a 1.2–1.6 times easier installation as compared to three-wire (voltage 10 kW and 1.4 times easier installation as compared to single-core oil-filled cables (voltage of 110 kW. The efficacy of the cables 6–110 kW with XLPE insulation is proved on the basis on the method of multi-objective optimization, that took into account as the costs for the construction and operation of cable lines and the reliability of its operation, ease of its installation and other quality indicators. If the goals taken into account are considered as equally important, the polyethylene-insulated cables for a voltage of 10–110 kW is more efficient as compared to three-wire (voltage 10 kW and solid (110 kW cables with paper insulation. Herewith, the cost of the cable with XLPE insulation may exceed the cost of cable with paper insulation up to two times. If the most important aim is to provide the minimum reduced costs for the construction and operation of the cable line, the use of cables with XLPE insulation for voltage of 10 kW is most advisable in individual cases.

  4. Double Layered Sheath in Accurate HV XLPE Cable Modeling

    DEFF Research Database (Denmark)

    Gudmundsdottir, Unnur Stella; Silva, J. De; Bak, Claus Leth

    2010-01-01

    This paper discusses modelling of high voltage AC underground cables. For long cables, when crossbonding points are present, not only the coaxial mode of propagation is excited during transient phenomena, but also the intersheath mode. This causes inaccurate simulation results for high frequency...

  5. Investigations of Electrical Trees in the Inner Layer of XLPE Cable Insulation Using Computer-aided Image Recording Monitoring

    OpenAIRE

    Xie, Ansheng; Zheng, Xiaoquan; Li, Shengtao; Chen, George

    2010-01-01

    Using a computer-aided image recording monitoring system, extensive measurements have been performed in the inner layer of 66 kV cross-linked polyethylene (XLPE)cables. It has been found that there are three kinds of electrical trees in the samples,the branch-like tree, the bush-like tree and the mixed tree that is a mixture of the above two kinds. When the applied voltage frequency is less than or equal to 250 Hz, only the mixed tree appears in XLPE samples, when the frequency is greater tha...

  6. Study of Space Charge in SC Shield / XLPE Interface and Mid-Voltage Cable Perfomance

    Directory of Open Access Journals (Sweden)

    Idalberto Tamayo Ávila

    2013-01-01

    Full Text Available Se estudiaron tres cables experimentales de media tensión: C2, C3 y C4; con aislamiento de polietileno reticulado (XLPE denominados: Medio, Alto y Bajo en los test de perforación con tensiones sobre 150 kV. Los tres cables han sido medidos sistemáticamente mediante las técnicas del Pulso Electroacústico (PEA y de las Corrientes de Despolarización Estimuladas Térmicamente (TSDC usando un voltaje de polarización de 120 kV en muestras tal y como se reciben, tratadas térmicamente a 90 oC y 120 oC durante 672 horas. Las medidas de carga interna en el cable C4 son de un orden del doble que en los cables C2 y C3. El fenómeno de carga interfacial ha sido estudiado por espectroscopia infrarroja mediante la técnica de Reflectancia Total Atenuada (ATR y muestra que hay componentes que migran, se difunden y se trasportan desde la capa semiconductora externa hacia el aislamiento de polietileno reticulado durante el tratamiento térmico del cable. Las medidas por PEA usando un campo eléctrico de 120 KV/mm muestran la formación y propagación de paquetes de carga de espacio desde el semiconductor (SC hacia el aislamiento. Estos resultados son coherentes con las medidas mediante TSDC que muestran diferencias entre las áreas bajo la curva de corriente en función de la temperatura para los tres cables C2, C3 y C4 que es el resultado de la carga acumulada. Para resumir, la combinación de las mediciones PEA, TSDC y ATR son herramientas útiles para la comprensión de los procesos de relajación de carga de espacio y la eficiencia de los cables con aislamiento de XLPE.

  7. Analysis of Insulating Material of XLPE Cables considering Innovative Patterns of Partial Discharges

    Directory of Open Access Journals (Sweden)

    Fernando Figueroa Godoy

    2017-01-01

    Full Text Available This paper aims to analyze the quality of insulation in high voltage underground cables XLPE using a prototype which classifies the following usual types of patterns of partial discharge (PD: (1 internal PD, (2 superficial PD, (3 corona discharge in air, and (4 corona discharge in oil, in addition to considering two new PD patterns: (1 false contact and (2 floating ground. The tests and measurements to obtain the patterns and study cases of partial discharges were performed at the Testing Laboratory Equipment and Materials (LEPEM of the Federal Electricity Commission of Mexico (CFE using a measuring equipment LDIC and norm IEC60270. To classify the six patterns of partial discharges mentioned above a Probabilistic Neural Network Bayesian Modified (PNNBM method having the feature of using a large amount of data will be used and it is not saturated. In addition, PNN converges, always finding a solution in a short period of time with low computational cost. The insulation of two high voltage cables with different characteristics was analyzed. The test results allow us to conclude which wire has better insulation.

  8. Microstructural characterization of XLPE electrical insulation in power cables: determination of void size distributions using TEM

    International Nuclear Information System (INIS)

    Markey, L; Stevens, G C

    2003-01-01

    In an effort to progress in our understanding of the ageing mechanisms of high voltage cables submitted to electrical and thermal stresses, we present a quantitative study of voids, the defects which are considered to be partly responsible for cable failure. We propose a method based on large data sets of transmission electron microscopy (TEM) observations of replicated samples allowing for the determination of void concentration distribution as a function of void size in the mesoscopic to microscopic range at any point in the cable insulation. A theory is also developed to calculate the effect of etching on the apparent size of the voids observed. We present the first results of this sort ever obtained on two industrial cables, one of which was aged in an AC field. Results clearly indicate that a much larger concentration of voids occur near the inner semiconductor compared to the bulk of the insulation, independently of ageing. An effect of ageing can also be seen near the inner semiconductor, resulting in an increase in the total void internal surface area and a slight shift of the concentration curve towards larger voids, with the peak moving from about 40 nm to about 50 nm

  9. Electrical conduction of a XLPE nanocomposite

    Science.gov (United States)

    Park, Yong-Jun; Sim, Jae-Yong; Lim, Kee-Joe; Nam, Jin-Ho; Park, Wan-Gi

    2014-07-01

    The resistivity, breakdown strength, and formation of space charges are very important factors for insulation design of HVDC cable. It is known that a nano-sized metal-oxide inorganic filler reduces the formation of space charges in the polymer nanocomposite. Electrical conduction of cross-linked polyethylene(XLPE) nanocomposite insulating material is investigated in this paper. The conduction currents of two kinds of XLPE nanocomposites and XLPE without nano-filler were measured at temperature of 303 ~ 363 K under the applied electric fields of 10 ~ 50 kV/mm. The current of the nanocomposite specimen is smaller than that of XLPE specimen without nano-filler. The conduction mechanism may be explained in terms of Schottky emission and multi-core model.

  10. A time-resolved current method and TSC under vacuum conditions of SEM: Trapping and detrapping processes in thermal aged XLPE insulation cables

    Science.gov (United States)

    Boukezzi, L.; Rondot, S.; Jbara, O.; Boubakeur, A.

    2017-03-01

    Thermal aging of cross-linked polyethylene (XLPE) can cause serious concerns in the safety operation in high voltage system. To get a more detailed picture on the effect of thermal aging on the trapping and detrapping process of XLPE in the melting temperature range, Thermal Stimulated Current (TSC) have been implemented in a Scanning Electron Microscope (SEM) with a specific arrangement. The XLPE specimens are molded and aged at two temperatures (120 °C and 140 °C) situated close to the melting temperature of the material. The use of SEM allows us to measure both leakage and displacement currents induced in samples under electron irradiation. The first represents the conduction process of XLPE and the second gives information on the trapping of charges in the bulk of the material. TSC associated to the SEM leads to show spectra of XLPE discharge under thermal stimulation using both currents measured after electron irradiation. It was found that leakage current in the charging process may be related to the physical defects resulting in crystallinity variation under thermal aging. However the trapped charge can be affected by the carbonyl groups resulting from the thermo-oxidation degradation and the disorder in the material. It is evidenced from the TSC spectra of unaged XLPE that there is no detrapping charge under heat stimulation. Whereas the presence of peaks in the TSC spectra of thermally aged samples indicates that there is some amount of trapped charge released by heating. The detrapping behavior of aged XLPE is supported by the supposition of the existence of two trap levels: shallow traps and deep traps. Overall, physico-chemical reactions under thermal aging at high temperatures leads to the enhancement of shallow traps density and changes in range of traps depth. These changes induce degradation of electrical properties of XLPE.

  11. Condition based maintenance of a 20 kV-PE/XLPE-insulated cable network using the IRC-Analysis; Zustandsorientierte Instandhaltung eines polymerisolierten 20-kV-Kabelnetzes mit der IRC-Analyse. Moderne Diagnostik reduziert Stoerungsrate

    Energy Technology Data Exchange (ETDEWEB)

    Hoff, G.; Kranz, H.G. [BUGH Wuppertal (Germany). Labs. fuer Hochspannungstechnik; Beigert, M.; Petzold, F. [Seba Dynatronic Mess- und Ortungstechnik GmbH, Baunach (Germany); Kneissl, C. [Bereich Konzeption und Messtechnik, Lech Elektrizitaetswerke AG, Augsburg (Germany)

    2001-10-22

    For a preventive maintenance of a polymer insulated cable network a destruction free estimation of the status of the buried PE/XLPE-cables is needed. This contribution presents a condition based maintenance concept which is based on the IRC-Analysis. With this concept a major German utility was able to reduce the amount of failures in a part of the 20kV-cable network. The general tendency of increasing faults was broken. (orig.) [German] Die praeventive Instandhaltung in polymerisolierten Kabelnetzen setzt eine zerstoerungsfreie Zustandbestimmung von gelegten PE/VPE-isolierten Kabeln voraus. Die-Verfasser beschreiben ein zustandsorientiertes Wartungskonzept auf Basis der IRC-Analyse, mit dem es gelungen ist, in einem Teil des 20-kV-Kabelnetzes eines Energieversorgers die in der Vergangenheit stetig steigende Stoerungsrate drastisch zu reduzieren. (orig.)

  12. Development of a method of partial discharge detection in extra-high voltage cross-linked polyethylene insulated cable lines

    International Nuclear Information System (INIS)

    Katsuta, G.; Toya, A.; Muraoka, K.; Endoh, T.; Sekii, Y.; Ikeda, C.

    1992-01-01

    This paper reports that deterioration in the insulation performance of extra-high voltage XLPE cables is believed to be attributable to the deterioration caused by partial discharges. In the authors study, after using an XLPE cable to investigate the behavior of partial discharges under various adverse conditions, we succeeded in developing a highly sensitive new method of measuring partial discharge in XLPE cable lines. Partial discharges in a 275 kV XLPE cable live line has been measured using this newly developed method. As a result, a detection sensitivity of 1 pC has been achieved

  13. Aging Mechanisms and Nondestructive Aging Indicator of Filled Cross-linked Polyethylene (XLPE) Exposed to Simultaneous Thermal and Gamma Radiation

    Energy Technology Data Exchange (ETDEWEB)

    Liu, Shuaishuai; Fifield, Leonard S.; Bowler, Nicola

    2018-04-11

    Aging mechanisms and a nondestructive aging indicator of filled cross-linked polyethylene (XLPE) cable insulation material used in nuclear power plants (NPPs) are studied. Using various material characterization techniques, likely candidates and functions for the main additives in a commercial filled-XLPE insulation material have been identified. These include decabromodiphenyl ether and Sb2O3 as flame retardants, ZnS as white pigment and polymerized 1,2-dihydro-2,2,4-trimethylquinoline as antioxidant. Gas chromatography-mass spectrometry, differential scanning calorimetry, oxidation induction time and measurements of dielectric loss tangent are utilized to monitor property changes as a function of thermal and radiation exposure of the cable material. Small-molecular-weight hydrocarbons are evolve with gamma radiation aging at 90 °C. The level of antioxidant decreases with aging by volatilization and chemical reaction with free radicals. Thermal aging at 90 °C for 25 days or less causes no observable change to the cross-linked polymer structure. Gamma radiation causes damage to crystalline polymer regions and introduces defects. Dielectric loss tangent is shown to be an effective and reliable nondestructive indicator of the aging severity of the filled-XLPE insulation material.

  14. 77 FR 19525 - Specification for 15 kV and 25 kV Primary Underground Power Cable

    Science.gov (United States)

    2012-04-02

    ... resistant cables shall have strip tension of 0 through 18 pounds (0 through 8.16 kg). Comment: General Cable suggested changing the requirement of stripping tension for TR-XLPE cable to the industry standard of a maximum of 24 lb. Limiting the maximum stripping tension to 18 lb will cause quality cable to be rejected...

  15. Influence of water trees on breakdown voltage of polymeric cables insulations

    Energy Technology Data Exchange (ETDEWEB)

    Stancu, Cristina [INCDIE ICPE CA, Bucharest (Romania); Notingher, Petru V.; Plopeanu, Mihai Gabriel [Politehnica University of Bucharest, Bucharest (Romania)

    2011-07-01

    In a previous paper was shown that water trees development modifies considerably the electric field repartition, which increases significantly in the vicinity of treed areas. In order to find the water trees influence on the breakdown voltage, in the present paper, an experimental study on model cables insulated with low density polyethylene is done. In insulation samples, water trees with various dimensions and densities were developed. For the reduction of the test duration, an electric field with a higher frequency (3-5 kHz) was used. For breakdown voltage measurement an automatic setup was realized. For each value of the ageing time the dimensions and densities of water trees and breakdown voltage were measured and the dependency of the breakdown voltage with these quantities were analysed. The results show a significant reduction of the breakdown voltage of treed cables insulations compared to un-treed ones. Key words: polyethylene, water treeing, electric field, breakdown, power cables.

  16. Estimation of Medium Voltage Cable Parameters for PD Detection

    DEFF Research Database (Denmark)

    Villefrance, Rasmus; Holbøll, Joachim T.; Henriksen, Mogens

    1998-01-01

    Medium voltage cable characteristics have been determined with respect to the parameters having influence on the evaluation of results from PD-measurements on paper/oil and XLPE-cables. In particular, parameters essential for discharge quantification and location were measured. In order to relate...... and phase constants. A method to estimate this propagation constant, based on high frequency measurements, will be presented and will be applied to different cable types under different conditions. The influence of temperature and test voltage was investigated. The relevance of the results for cable...

  17. Stand structure and vegetation dynamics of a subalpine treed fen in Rocky Mountain National Park, Colorado

    Energy Technology Data Exchange (ETDEWEB)

    Johnson, J.B. [Colorado State Univ., Fort Collins, CO (United States). Dept. of Biology

    1997-06-01

    The tree population size structure and relationship between tree diameter and age were examined in a subalpine fen and surrounding Picea-Abies forest in northern Colorado. The fen grades from a sedge fen, through an ecotone, to a treed fen (i.e. fen colonized by trees). Tree growth rate varies across the vegetational gradient, with the sedge fen having the slowest growth, and the upland forest having the fastest growth. Differences in growth rate are related to the average size of peat hummocks, with areas containing tall hummocks exhibiting the highest tree growth rates. Size structures display the characteristic reverse-J distribution generally indicative of stable populations, but forest vegetation is expanding into the open regions of the fen, and within the treed fen an increase in Abies lasiocarpa is occurring. These changes are primarily attributed to a positive feedback situation wherein the fen`s surface is built up by peat accumulation. Distinct hummocks form first on the open fen but then coalesce to form raised peat islands in the treed fen. This new substrate provides habitat with a comparatively low water table and allows the growth of mesophytic forest vegetation. A pathway for this vegetational development is proposed. 40 refs., 2 figs.

  18. Cable aging management

    International Nuclear Information System (INIS)

    Anandkumaran, A.; Sedding, H.

    2012-01-01

    Worldwide, due to the age of the majority of nuclear generating stations significant attention is being paid to the condition of the major components, e.g., reactor, steam generator, turbine generator, transformer, etc., with respect to relicensing and life extension. However, there is recognition that cable systems are critical to the safe, reliable and economic operation of nuclear power plants. Consequently, there is great interest in ageing management of low and medium voltage cables in the nuclear environment. Successful implementation of such programs requires an understanding of how the materials associated with cables and their accessories behave under normal operating and accident conditions. However, there is also a great need to determine the actual condition of the materials and systems in order to make rational decisions on whether or not to replace cables to ensure long term assurance of reliable operation. This proposed contribution describes an approach to cable ageing management of low and medium voltage cables based on measurements of material and electrical properties obtained in the laboratory and in the field. The effectiveness of various chemical, mechanical and electrical test methods are discussed in the context of, • Cable configuration, i.e., low or medium voltage, shielded or unshielded • Material type, i.e., PVC, XLPE, EPR, etc., • Ageing stress, i.e., electrical, thermal, radiation, thermal plus radiation, etc. These factors are key to identifying the most appropriate test method (or methods) to enable understanding of the current condition of the cable. While electrical test methods, e.g., ac withstand testing, partial discharge and various dielectric loss measurement techniques have been found effective for medium voltage cables, they are of very limited use on low voltage cables that constitute the majority of cables in nuclear power plants. This limited effectiveness is due to the lack of a well defined ground plane that is a

  19. DC Electrical Ageing of XLPE under Hydrostatic Pressure

    Directory of Open Access Journals (Sweden)

    Fadila Benlizidia Lalam

    2017-01-01

    Full Text Available The experimental electrical ageing, of cross-linked polyethylene films 100 μm thick, was investigated under high hydrostatic pressure of 300 bar and at atmospheric pressure. The tests are conducted on direct current (dc for up to 1000 h ageing and at temperature of 70°C. The use of the Weibull statistic, with the estimation of confidence bounds at 90%, has shown that the hydrostatic pressure has a real effect on the lifetime. These lifetime data are qualitatively analyzed with the inverse power model. It was found that thermally activated process is able to describe the pressure effect on the electrical ageing of XLPE.

  20. Remaining life prediction of I and C cables for reliability assessment of NPP systems

    International Nuclear Information System (INIS)

    Santhosh, T.V.; Ghosh, A.K.; Fernandes, B.G.

    2012-01-01

    Highlights: ► A framework for time dependent reliability prediction of I and C cables for use in PSA of NPP has been developed using stress–strength interference theory. ► The proposed methodology has been illustrated with the accelerated thermal aging data on a typical XLPE cable. ► The behavior of insulation resistance when the degradation process is linear or exponential has also been modeled. ► The reliability index or probability of failure obtained from this approach can be used in system reliability evaluation to account for cable aging for PSA of NPP. - Abstract: Instrumentation and control (I and C) cables are one of the most important components in nuclear power plants (NPPs) because they provide power to safety-related equipment and also to transmit signals to and from various controllers to perform safety operations. I and C cables in NPP are subjected to a variety of aging and degradation stressors that can produce immediate degradation or aging-related mechanisms causing the degradation of cable components over time. Although, there exits several life estimation techniques, currently there is no any standard methodology or an approach toward estimating the time dependent reliability of I and C cables that can be directly used in probabilistic safety assessment (PSA) applications. Hence, the objective of this study is to develop an approach to estimate and confirm the continued acceptable margin in cable insulation life over time subjected to aging. This paper presents a framework based on the structural reliability theory to quantify the life time of I and C cable subjecting to thermal aging. Since cross-linked polyethylene (XLPE) cables are extensively being used in Indian NPPs, the remaining life time evaluations have been carried out for a typical XLPE cable. However, the methodology can be extended to other cables such as polyvinyl chloride (PVC), ethylene propylene rubber (EPR), etc.

  1. TREEDE, Point Fluxes and Currents Based on Track Rotation Estimator by Monte-Carlo Method

    International Nuclear Information System (INIS)

    Dubi, A.

    1985-01-01

    1 - Description of problem or function: TREEDE is a Monte Carlo transport code based on the Track Rotation estimator, used, in general, to calculate fluxes and currents at a point. This code served as a test code in the development of the concept of the Track Rotation estimator, and therefore analogue Monte Carlo is used (i.e. no importance biasing). 2 - Method of solution: The basic idea is to follow the particle's track in the medium and then to rotate it such that it passes through the detector point. That is, rotational symmetry considerations (even in non-spherically symmetric configurations) are applied to every history, so that a very large fraction of the track histories can be rotated and made to pass through the point of interest; in this manner the 1/r 2 singularity in the un-collided flux estimator (next event estimator) is avoided. TREEDE, being a test code, is used to estimate leakage or in-medium fluxes at given points in a 3-dimensional finite box, where the source is an isotropic point source at the centre of the z = 0 surface. However, many of the constraints of geometry and source can be easily removed. The medium is assumed homogeneous with isotropic scattering, and one energy group only is considered. 3 - Restrictions on the complexity of the problem: One energy group, a homogeneous medium, isotropic scattering

  2. Effect of D.C. testing water tree deteriorated cable and a preliminary evaluation of V.L.F. as alternate

    International Nuclear Information System (INIS)

    Eager, G.S. Jr.; Fryszczyn, B.; Katz, C.; ElBadaly, H.A.; Jean, A.R.

    1992-01-01

    This paper reports that according to the experience of some power utilities, the application of industry recommended high voltage d.c. field tests on 5-35 kV extruded dielectric cables, containing water trees, sometimes causes further deterioration of the insulation. Tests conducted on laboratory aged 15 kV ethylene propylene rubber (EP) and 15 and 28 kV crosslinked polyethylene (XLPE) insulated cables indicate that d.c. proof tests in accordance with AEIC specifications an IEEE test guides without flashover do not appear to cause further deterioration. Depending on the degree of cable aging and the level of test voltage, when flashovers take place, damage may be inflicted to XLPE cables. No damage was observed on aged EP cable, at the same test levels. Because of the aforementioned power utility experience, some users have requested an alternate field proof test. Tests conducted on new XLPE and EP cables indicate that damage to the insulation structure can be detected using VLF (0.1 Hz) voltage at approximately one-third the d.c. voltage level. Field tests conducted on severely tree deteriorated 15 kV polyethylene (PE) cable using AEIC recommended d.c. voltage level of about five times operating voltage level caused cable failure; VLF voltage levels up to two times operating voltage did not. VLF voltage appears to be a suitable alternate to d.c. voltage for field proof testing

  3. Space charge build-up in XLPE-cable with temperature gradient

    DEFF Research Database (Denmark)

    Holbøll, Joachim; Henriksen, Mogens; Hjerrild, Jesper

    2000-01-01

    and temperatures were applied in the 20 - 80°C range with gradients across the insulation of up to 15°C. In this paper, the observed charge phenomena in the bulk and at the interfaces are related to the external conditions, in particular to the temperature gradient. The measured space charge distributions...

  4. The Influence of Pre-conditioning on the Space Charge Formation in LDPE and XLPE

    DEFF Research Database (Denmark)

    Henriksen, Mogens; Holbøll, Joachim T.; Fleming, R.J.

    1996-01-01

    Planar LDPE and XLPE samples were conditioned by holding in short circuit for 48 hrs. at 40oC under rotary pump pressure, and space charge accumulation in these samples under DC fields of 20 kV/mm was then compared with the corresponding accumulation in unconditioned samples.The test results were...

  5. ASSESSMENT OF CABLE AGING USING CONDITION MONITORING TECHNIQUES

    International Nuclear Information System (INIS)

    GROVE, E.; LOFARO, R.; SOO, P.; VILLARAN, M.; HSU, F.

    2000-01-01

    Electric cables in nuclear power plants suffer degradation during service as a result of the thermal and radiation environments in which they are installed. Instrumentation and control cables are one type of cable that provide an important role in reactor safety. Should the polymeric cable insulation material become embrittled and cracked during service, or during a loss-of-coolant-accident (LOCA) and when steam and high radiation conditions are anticipated, failure could occur and prevent the cables from fulfilling their intended safety function(s). A research program is being conducted at Brookhaven National Laboratory to evaluate condition monitoring (CM) techniques for estimating the amount of cable degradation experienced during in-plant service. The objectives of this program are to assess the ability of the cables to perform under a simulated LOCA without losing their ability to function effectively, and to identify CM techniques which may be used to determine the effective lifetime of cables. The cable insulation materials tested include ethylene propylene rubber (EPR) and cross-linked polyethylene (XLPE). Accelerated aging (thermal and radiation) to the equivalent of 40 years of service was performed, followed by exposure to simulated LOCA conditions. The effectiveness of chemical, electrical, and mechanical condition monitoring techniques are being evaluated. Results indicate that several of these methods can detect changes in material parameters with increasing age. However, each has its limitations, and a combination of methods may provide an effective means for trending cable degradation in order to assess the remaining life of cables

  6. Categorical Inputs, Sensitivity Analysis, Optimization and Importance Tempering with tgp Version 2, an R Package for Treed Gaussian Process Models

    Directory of Open Access Journals (Sweden)

    Robert B. Gramacy

    2010-02-01

    Full Text Available This document describes the new features in version 2.x of the tgp package for R, implementing treed Gaussian process (GP models. The topics covered include methods for dealing with categorical inputs and excluding inputs from the tree or GP part of the model; fully Bayesian sensitivity analysis for inputs/covariates; sequential optimization of black-box functions; and a new Monte Carlo method for inference in multi-modal posterior distributions that combines simulated tempering and importance sampling. These additions extend the functionality of tgp across all models in the hierarchy: from Bayesian linear models, to classification and regression trees (CART, to treed Gaussian processes with jumps to the limiting linear model. It is assumed that the reader is familiar with the baseline functionality of the package, outlined in the first vignette (Gramacy 2007.

  7. Effect of moisture on the electrical performance of transition-joints for medium voltage paper-insulated cables; Elektrische Beeintraechtigung durch Feuchtigkeit an oelgetraenkten Isolierpapieren. Mittelspannungsuebergangsmuffen

    Energy Technology Data Exchange (ETDEWEB)

    Cardinaels, Jos [Nexans Network Solution, Erembodegem (Belgium). Produktentwicklung; Baesch, Manfred [Nexans Power Accessories Germany, Dortmund (Germany). Produkt- und Qualitaetsmanagement

    2009-06-15

    Paper-insulated cables are constructed with an impervious metallic outer jacket in order to protect them against ingress of moisture. On 'modern' transition-joints to XLPE-insulated cables, this metal barrier is interrupted, hence, a risk of moisture penetration exists. This text presents measurements of water-vapour permeability of used materials and discusses the results of ageing tests. (orig.)

  8. Treeing phenomenon of thermoplastic polyethylene blends for recyclable cable insulation materials

    Science.gov (United States)

    Li, Lunzhi; Zhang, Kai; Zhong, Lisheng; Gao, Jinghui; Xu, Man; Chen, Guanghui; Fu, Mingli

    2017-02-01

    Owing to its good recyclability and low processing energy consumption, non-crosslinked polyethylene blends (e.g. LLDPE-HDPE blends) are considered as one of potential environmental-friendly substitutions for crosslinked polyethylene (XLPE) as cable insulation material. Although extensive work has been performed for measuring the basic dielectric properties, there is a lack of the investigations on the aging properties for such a material system, which hinders the evaluation of reliability and lifetime of the material for cable insulation. In this paper, we study the electric aging phenomenon of 0.7LLDPE-0.3HDPE blending material by investigating the treeing behavior, and its comparison with XLPE and LLDPE. Treeing tests show that the 0.7LLDPE-0.3HDPE blends have lower probability for treeing as well as smaller treeing dimensions. Further thermal analysis and microstructure study results suggest that the blends exhibit larger proportion of thick lamellae and higher crystallinity with homogeneously-distributed amorphous region, which is responsible for good anti-treeing performance. Our finding provides the evidence that the 0.7LLDPE-0.3HDPE blends exhibits better electric-aging-retardance properties than XLPE, which may result in a potential application for cable insulation.

  9. Treeing phenomenon of thermoplastic polyethylene blends for recyclable cable insulation materials

    Directory of Open Access Journals (Sweden)

    Lunzhi Li

    2017-02-01

    Full Text Available Owing to its good recyclability and low processing energy consumption, non-crosslinked polyethylene blends (e.g. LLDPE-HDPE blends are considered as one of potential environmental-friendly substitutions for crosslinked polyethylene (XLPE as cable insulation material. Although extensive work has been performed for measuring the basic dielectric properties, there is a lack of the investigations on the aging properties for such a material system, which hinders the evaluation of reliability and lifetime of the material for cable insulation. In this paper, we study the electric aging phenomenon of 0.7LLDPE-0.3HDPE blending material by investigating the treeing behavior, and its comparison with XLPE and LLDPE. Treeing tests show that the 0.7LLDPE-0.3HDPE blends have lower probability for treeing as well as smaller treeing dimensions. Further thermal analysis and microstructure study results suggest that the blends exhibit larger proportion of thick lamellae and higher crystallinity with homogeneously-distributed amorphous region, which is responsible for good anti-treeing performance. Our finding provides the evidence that the 0.7LLDPE-0.3HDPE blends exhibits better electric-aging-retardance properties than XLPE, which may result in a potential application for cable insulation.

  10. tgp: An R Package for Bayesian Nonstationary, Semiparametric Nonlinear Regression and Design by Treed Gaussian Process Models

    Directory of Open Access Journals (Sweden)

    Robert B. Gramacy

    2007-06-01

    Full Text Available The tgp package for R is a tool for fully Bayesian nonstationary, semiparametric nonlinear regression and design by treed Gaussian processes with jumps to the limiting linear model. Special cases also implemented include Bayesian linear models, linear CART, stationary separable and isotropic Gaussian processes. In addition to inference and posterior prediction, the package supports the (sequential design of experiments under these models paired with several objective criteria. 1-d and 2-d plotting, with higher dimension projection and slice capabilities, and tree drawing functions (requiring maptree and combinat packages, are also provided for visualization of tgp objects.

  11. Charge Accumulation in LDPE and XLPE Conditioned at 80oC under Reduced Pressure

    DEFF Research Database (Denmark)

    Fleming, Robert J.; Henriksen, Mogens; Holbøll, Joachim T.

    1997-01-01

    The effects of thermal conditioning, under reduced pressure, on space accumulation in planar LDPE and XLPE samples under DC stress, have been investigated. The samples were conditioned prior to voltage application by being held at 80oC for 2-3 days in short circuit at rotary pump pressure. Some...... were then cooled to room temperature over a period of at least 6hr, still under rotary pump pressure and in short circuit, while others were cooled to room temperature in less than 1.5hr in the laboratory air. DC fields of 18kV/mm were then applied at room temperature, and space charge accumulation...

  12. Modelling of long High Voltage AC Cables in the Transmission System

    DEFF Research Database (Denmark)

    Gudmundsdottir, Unnur Stella

    : conductor-insulation (with or without SC layers)-conductor-insulation(-conductor-insulation), whereas a transmission line single core XLPE cable will normally have the configuration: conductor-SC layerinsulation-SC layer-conductor-SC layer-conductor-insulation. Furthermore the existing cable models use......, EMTDC/PSCAD is provided. A typical HV AC underground power cable is formed by 4 main layers, namely; Conductor-Insulation-Screen-Insulation. In addition to these main layers, the cable also has semiconductive screens, swelling tapes and metal foil. For high frequency modelling in EMT-based software......-SC layer-solid hollow conductor) is implemented in the model. These improvements result in a more correct series impedance and hence a more correct damping of the simulations. Even though the series impedance is more correct, it does still not include the proximity effect and high frequency oscillations...

  13. Online Location of Faults on AC Cables in Underground Transmission Systems

    DEFF Research Database (Denmark)

    Jensen, Christian Flytkjær

    under fault conditions well, but the accuracy of the calculated impedance is low for fault location purposes. The neural networks can therefore not be trained and no impedance-based fault location method can be used for crossbonded cables or hybrid lines. The use of travelling wave-based methods...... connection to verify the proposed method. Faults, at reduced a voltage are artificially applied in the cable system and the transient response is measured at two terminals at the cable’s ends. The measurements are time-synchronised and it is found that a very accurate estimation of the fault location can......A transmission grid is normally laid out as an almost pure overhead line (OHL) network. The introduction of transmission voltage level XLPE cables and the increasing interest in the environmental impact of OHL has resulted in an increasing interest in the use of underground cables on transmission...

  14. Tracking of Nuclear Cable Insulation Polymer Structural Changes using the Gel Fraction and Uptake Factor Method

    Energy Technology Data Exchange (ETDEWEB)

    Correa, Miguel; Huang, Qian; Fifield, Leonard S.

    2018-04-11

    Cross-linked polyethylene (XLPE) cable insulation samples were exposed to heat and gamma radiation at a series of temperatures, dose rates, and exposure times to evaluate the effects of these variables on material degradation. The samples were tested using the solvent incubation method to collect gel fraction and uptake factor data in order to assess the crosslinking and chain scission occurring in polymer samples with aging. Consistent with previous reports, gel fraction values were observed to increase and uptake factor values to decrease with radiation and thermal exposure. The trends seen were also more prominent as exposure time increased, suggesting this to be a viable method of tracking structural changes in the XLPE-insulated cable material over extended periods. For the conditions explored, the cable insulation material evaluated did not indicate signs of anomalous aging such as inverse temperature effect in which radiation-induced aging is more severe at lower temperature. Ongoing aging under identical radiation conditions and at lower temperature will further inform conclusions regarding the importance of inverse temperature effects for this material under these conditions.

  15. Cable handling

    International Nuclear Information System (INIS)

    1980-01-01

    In computerized axial tomography scanning, problems arise in exchanging electrical signals between fixed and rotating assemblies. A novel method of overcoming this problem is described in detail for both signal and high voltage cables. Apparatus using a sequence of drums and pulleys is used to maintain the interconnecting cables in a neat arrangement and free from mechanical strain. The apparatus is simple and relatively easy and inexpensive to assemble and maintain. (UK)

  16. Long-term aging and loss-of-coolant accident (LOCA) testing of electrical cables

    International Nuclear Information System (INIS)

    Nelson, C.F.; Gauthier, G.; Carlin, F.

    1996-10-01

    Experiments were performed to assess the aging degradation and loss-of-coolant accident (LOCA) behavior of electrical cables subjected to long-term aging exposures. Four different cable types were tested in both the U.S. and France: (1) U.S. 2 conductor with ethylene propylene rubber (EPR) insulation and a Hypalon jacket. (2) U.S. 3 conductor with cross-linked polyethylene (XLPE) insulation and a Hypalon jacket. (3) French 3 conductor with EPR insulation and a Hypalon jacket. (4) French coaxial with polyethylene (PE) insulation and a PE jacket. The data represent up to 5 years of simultaneous aging where the cables were exposed to identical aging radiation doses at either 40 degrees C or 70 degrees C; however, the dose rate used for the aging irradiation was varied over a wide range (2-100 Gy/hr). Aging was followed by exposure to simulated French LOCA conditions. Several mechanical, electrical, and physical-chemical condition monitoring techniques were used to investigate the degradation behavior of the cables. All the cables, except for the French PE cable, performed acceptably during the aging and LOCA simulations. In general, cable degradation at a given dose was highest for the lowest dose rate, and the amount of degradation decreased as the dose rate was increased

  17. Tailored sPP/Silica Nanocomposite for Ecofriendly Insulation of Extruded HVDC Cable

    Directory of Open Access Journals (Sweden)

    Bin Dang

    2015-01-01

    Full Text Available Cross-linked polyethylene (XLPE is a thermosetting material that cannot be recycled at the end of its lifetime. This study investigated the potential of syndiotactic polypropylene (sPP/silica as an ecofriendly extruded insulation system for HVDC cables. We investigated the morphology, Fourier transform infrared, and thermal, thermomechanical, and electrical behaviors of sPP modified with 0.5–3% nanosilica. We found that the silica/sPP nanocomposite without cross-linking offered a suitable mechanical modulus at room temperature and sufficient intensity at high temperatures, and adding nanosilica modified by a silane coupling agent to the sPP resulted in significant DC resistivity and space charge improvement. The optimal nanosilica content in the sPP was determined by balancing the mechanical and thermomechanical characteristics and the DC resistivity. The sPP/silica nanocomposite reported here shows great potential as a candidate insulation material for future ecofriendly extruded HVDC cables.

  18. Cable Stability

    Energy Technology Data Exchange (ETDEWEB)

    Bottura, L [European Organization for Nuclear Research, Geneva (Switzerland)

    2014-07-01

    Superconductor stability is at the core of the design of any successful cable and magnet application. This chapter reviews the initial understanding of the stability mechanism, and reviews matters of importance for stability such as the nature and magnitude of the perturbation spectrum and the cooling mechanisms. Various stability strategies are studied, providing criteria that depend on the desired design and operating conditions.

  19. New trends in design and fabrication of signal and power cables to increase nuclear safety

    International Nuclear Information System (INIS)

    Salmen, Florin; Florescu, Gheorghe; Ionescu, Aurel

    2007-01-01

    Based on NPP operating experiences in the past, it was found that the inadequate management of aging degradation caused shortening of the lifetime of equipment, which in turn, hindered plant life extension. Aging degradation of plant structures and components should be properly managed to ensure the designated safety function of plant systems during design life and extended life. From a safety perspective, aging management means maintaining the aging degradation level in major equipment and structures below the allowable limit and holding the capacity to sustain abnormal operating condition. Cable aging was not considered as a significant factor in relation to the nuclear power plant maintenance due to its long life which is almost the same as the plant design life. Attempts to extend the lifetime of NPP has become one of the major concern in the nuclear industry world wide. Consequently, life evaluation and lifetime management of cables to survive over 40 years has become major topic of discussion. In connection to this, accelerated aging must be studied in detail in order to simulate the natural aging in NPP. Test results for evaluating aging degradation after accelerated aging of polyethylene jacket will be described herein.There are hundred types of cables in NPPs. These cables can be classified as medium/low voltage cable, low power cable, instrument and control cable, panel connect line cable, special cable, security line cable, phone line cable and ground cable. Insulation and jacket material in electrical cables are fabricated of polymer materials combined with a number of additives and filler to provide the required mechanical, electrical and fire retardant proprieties. The most commonly used insulation materials are XLPE/EPR/EPDM and PVC. PVC has been widely used as an insulation material, particularly in old plants, but it is less used in modern plants. Neoprene/CSPE/PVC are commonly used material for nuclear cable jacket. The old types of cables

  20. CABLES MUSCULARES

    Directory of Open Access Journals (Sweden)

    Alejandro Gómez

    Full Text Available Los cables musculares o fibras de nitinol presentan una excelente alternativa a los actuadores convencionales, con una fuerza de actuación muy alta, equivalente a la de los actuadores hidráulicos, proporcionalmente a su peso, además de su acción silenciosa. Este material, inventado en 1963, aún no es muy conocido y de ahí que se haya realizado una recopilación de sus propiedades. Entre ellas, la temperatura de transición es la más importante, por ser la que activa la aleación. Muchos sistemas se han creado para alcanzar adecuadamente la temperatura de transición, y también se continúa en la investigación de métodos que ayuden a lograr un control preciso del movimiento de la aleación con memoria de forma (SMA.

  1. Universal Cable Brackets

    Science.gov (United States)

    Vanvalkenburgh, C.

    1985-01-01

    Concept allows routing easily changed. No custom hardware required in concept. Instead, standard brackets cut to length and installed at selected locations along cable route. If cable route is changed, brackets simply moved to new locations. Concept for "universal" cable brackets make it easy to route electrical cable around and through virtually any structure.

  2. Cable line engineering

    International Nuclear Information System (INIS)

    Jang, Hak Sin; Kim, Sin Yeong

    1998-02-01

    This book is about cable line engineering. It is comprised of nine chapters, which deals with summary of cable communication such as way, process of cable communication and optical communication, Line constant of transmission on primary constant, reflection and crosstalk, communication cable line of types like flat cable, coaxial cable and loaded cable, Install of communication line with types and facility of aerial line, construction method of communication line facility, Measurement of communication line, Carrier communication of summary, PCM communication with Introduction, regeneration relay system sampling and quantization and Electric communication service and general information network with mobile communication technique and satellite communication system.

  3. Superconducting ac cable

    Science.gov (United States)

    Schmidt, F.

    1980-11-01

    The components of a superconducting 110 kV ac cable for power ratings or = 2000 MVA were developed. The cable design is of the semiflexible type, with a rigid cryogenic envelope containing a flexible hollow coaxial cable core. The cable core consists of spirally wound Nb-A1 composite wires electrically insulated by high pressure polyethylene tape wrappings. A 35 m long single phase test cable with full load terminals rated at 110 kV and 10 kA was constructed and successfully tested. The results obtained prove the technical feasibility and capability of this cable design.

  4. Superconducting ac cable

    International Nuclear Information System (INIS)

    Schmidt, F.

    1980-01-01

    The components of a superconducting 110 kV ac cable for power ratings >= 2000 MVA have been developed. The cable design especially considered was of the semiflexible type, with a rigid cryogenic envelope and flexible hollow coaxial cable cores pulled into the former. The cable core consists of spirally wound Nb-Al composite wires and a HDPE-tape wrapped electrical insulation. A 35 m long single phase test cable with full load terminations for 110 kV and 10 kA was constructed and successfully tested. The results obtained prove the technical feasibility and capability of our cable design. (orig.) [de

  5. UAV Remote Sensing Can Reveal the Effects of Low-Impact Seismic Lines on Surface Morphology, Hydrology, and Methane (CH4) Release in a Boreal Treed Bog

    Science.gov (United States)

    Lovitt, J.; Rahman, M. M.; Saraswati, S.; McDermid, G. J.; Strack, M.; Xu, B.

    2018-03-01

    Peatlands are globally significant stores of soil carbon, where local methane (CH4) emissions are strongly linked to water table position and microtopography. Historically, these factors have been difficult to measure in the field, constraining our capacity to observe local patterns of variability. In this paper, we show how remote sensing surveys conducted from unmanned aerial vehicle (UAV) platforms can be used to map microtopography and depth to water over large areas with good accuracy, paving the way for spatially explicit estimates of CH4 emissions. This approach enabled us to observe—for the first time—the effects of low-impact seismic lines (LIS; petroleum exploration corridors) on surface morphology and CH4 emissions in a treed-bog ecosystem in northern Alberta, Canada. Through compaction, LIS lines were found to flatten the observed range in microtopographic elevation by 46 cm and decrease mean depth to water by 15.4 cm, compared to surrounding undisturbed conditions. These alterations are projected to increase CH4 emissions by 20-120% relative to undisturbed areas in our study area, which translates to a total rise of 0.011-0.027 kg CH4 day-1 per linear kilometer of LIS ( 2 m wide). The 16 km of LIS present at our 61 ha study site were predicted to boost CH4 emissions by 20-70 kg between May and September 2016.

  6. Energy cable engineering. Energiekabeltechnik

    Energy Technology Data Exchange (ETDEWEB)

    Luecking, H W

    1981-01-01

    This textbook intends to explain cable elements and common cable constructions according to VDE, and in a second part, to review the theoretical fundamentals and their consequences with a view to the construction of cables for higher voltages and powers. It will give the student a picture of the variety of problems and solutions which make cable engineering so interesting and show the practising engineer how to derive a theoretical system from their extensive everyday experience.

  7. Cable Supported Bridges

    DEFF Research Database (Denmark)

    Gimsing, Niels Jørgen

    Cable supported bridges in the form of suspension bridges and cable-stayed bridges are distinguished by their ability to overcome large spans.The book concentrates on the synthesis of cable supported bridges, covering both design and construction aspects. The analytical part covers simple methods...... to quantify the different structural configurations and allows a preliminary optimization of the main structure.Included are the most recent advances in structural design, corrosion protection of cables, aerodynamic safety, and erection procedures....

  8. Cable Television: Franchising Considerations.

    Science.gov (United States)

    Baer, Walter S.; And Others

    This volume is a comprehensive reference guide to cable television technology and issues of planning, franchising, and regulating a cable system. It is intended for local government officials and citizens concerned with the development of cable television systems in their communities, as well as for college and university classes in…

  9. Colleges and Cable Franchising.

    Science.gov (United States)

    Glenn, Neal D.

    After noting issues of audience appeal and financial and philosophical support for educational broadcasting, this paper urges community colleges to play an active role in the process of cable franchising. The paper first describes a cable franchise as a contract between a government unit and the cable television (CATV) company which specifies what…

  10. Cable strengthened arches

    NARCIS (Netherlands)

    Kamerling, M.W.

    2013-01-01

    The structural efficiency of arches, subjected to several variable loads, can be increased by strengthening these arches with cables. For these structures it can be necessary, especially in case the permanent load is small, to post-tension the cables to avoid any compression acting on the cables. A

  11. Effect of antioxidants on aging of nuclear plant cable insulation

    International Nuclear Information System (INIS)

    Reynolds, A.B.; Ray, J.W.; Wlodkowski, P.A.

    1991-01-01

    The effects of various antioxidants and antioxidant concentrations on the radiation and thermal stability of EPDM and XLPE polymers used for insulation of electric cable in nuclear power plants were measured. The objective was to determine if particular antioxidants could be identified as being especially effective for stabilization against radiation aging and combined thermal and radiation aging. Elongation to rupture was used as the measure of stability. Materials were irradiated to doses up to 2 MGy (200 Mrad) at a dose rate of 200 to 300 Gy/h in the Cobalt-60 Gamma Irradiation Facility at the University of Virginia. All of the antioxidants tested, which were known to provide excellent thermal stability, also provided good stability for radiation aging and combined thermal/radiation aging, although small differences between antioxidants were noted. No antioxidant or antioxidant combination was identified as being especially outstanding. Stabilization against radiation increased with increasing antioxidant concentration, but this trend was not observed for thermal aging. Damage from thermal and radiation aging was superposable. 9 refs., 16 figs., 12 tabs

  12. DC Cable for Railway

    Science.gov (United States)

    Tomita, Masaru

    The development of a superconducting cable for railways has commenced, assuming that a DC transmission cable will be used for electric trains. The cable has been fabricated based on the results of current testing of a superconducting wire, and various evaluation tests have been performed to determine the characteristics of the cable. A superconducting transmission cable having zero electrical resistance and suitable for railway use is expected to enhance regeneration efficiency, reduce power losses, achieve load leveling and integration of sub-stations, and reduce rail potential.

  13. Carbon dioxide flux and net primary production of a boreal treed bog: Responses to warming and water-table-lowering simulations of climate change

    Science.gov (United States)

    Munir, T. M.; Perkins, M.; Kaing, E.; Strack, M.

    2015-02-01

    Midlatitude treed bogs represent significant carbon (C) stocks and are highly sensitive to global climate change. In a dry continental treed bog, we compared three sites: control, recent (1-3 years; experimental) and older drained (10-13 years), with water levels at 38, 74 and 120 cm below the surface, respectively. At each site we measured carbon dioxide (CO2) fluxes and estimated tree root respiration (Rr; across hummock-hollow microtopography of the forest floor) and net primary production (NPP) of trees during the growing seasons (May to October) of 2011-2013. The CO2-C balance was calculated by adding the net CO2 exchange of the forest floor (NEff-Rr) to the NPP of the trees. From cooler and wetter 2011 to the driest and the warmest 2013, the control site was a CO2-C sink of 92, 70 and 76 g m-2, the experimental site was a CO2-C source of 14, 57 and 135 g m-2, and the drained site was a progressively smaller source of 26, 23 and 13 g CO2-C m-2. The short-term drainage at the experimental site resulted in small changes in vegetation coverage and large net CO2 emissions at the microforms. In contrast, the longer-term drainage and deeper water level at the drained site resulted in the replacement of mosses with vascular plants (shrubs) on the hummocks and lichen in the hollows leading to the highest CO2 uptake at the drained hummocks and significant losses in the hollows. The tree NPP (including above- and below-ground growth and litter fall) in 2011 and 2012 was significantly higher at the drained site (92 and 83 g C m-2) than at the experimental (58 and 55 g C m-2) and control (52 and 46 g C m-2) sites. We also quantified the impact of climatic warming at all water table treatments by equipping additional plots with open-top chambers (OTCs) that caused a passive warming on average of ~ 1 °C and differential air warming of ~ 6 °C at midday full sun over the study years. Warming significantly enhanced shrub growth and the CO2 sink function of the drained

  14. Cable aging tests

    International Nuclear Information System (INIS)

    Hubbard, G.

    1993-01-01

    This paper describes the results from aging, condition monitoring, and loss-of-coolant accident (LOCA) testing of class 1E electrical cables, per NUREG/CR-5772. This test was designed to test the performance of cables which had been aged with simultaneous radiation and thermal exposure. The tested cables included crosslinked polyolefin cables, ethylene propylene rubber cables, and miscellaneous cable types. Cables were exposed to 20, 40, and 60 years equivalent aging, and then exposed to LOCA tests at the end of their qualified life to determine the minimum insulation thickness needed for survival of the test. Failures were found in a large number of the tested cables. As a result the NRC has sent information notices to the industry regarding potential insulation problems. The results have raised the question of whether the artificial aging methods provide adequate testing methods. As a result of this testing the NRC is reviewing the artificial aging procedures, the adequacy of environmental qualification requirements for cable safety, and reexamining data from condition monitoring of installed cables

  15. Sizewell 'B' cable installation

    International Nuclear Information System (INIS)

    Gemmell, D.R.

    1992-01-01

    N G Bailey and Co. Ltd., UK were awarded the contract for the procurement, manufacture, works testing, works finishing, supply, delivery, off-loading, storage, installation, site finishing, preservation, setting to work and site testing of the following; the main cable installation throughout the Station including the addition of the Radioactive Waste Building, earthing and lightning protection installation, cable supporting steelwork and carriers and glanding and termination of cables. The cabling installation comprises power distribution, control and instrumentation cabling including all the associated cabling accessories, terminal boxes and similar components. The way that the contract was set-up, awarded and is now being carried out is described. Planning and industrial relations have been key features of the contract. (Author)

  16. Cable support arrangements

    International Nuclear Information System (INIS)

    Pendleton, E.; Murray, A.

    1983-01-01

    A cable support arrangement extending from a refuelling level floor of a nuclear reactor to the inner shield of a double rotatable shield comprises a linearly extensible cable support and disciplining boom, reaching from the floor to the main shield, and a circumferentially extensible cable support and disciplining means running from the end of the boom to a fixed end on the inner shield. (author)

  17. High voltage dc cables

    Energy Technology Data Exchange (ETDEWEB)

    Bjustrom, B

    1965-12-01

    How stress distribution in dc cables varies with temperature and stress level, influence of polarity reversals and space charges, and different types of overvoltage to which dc cable may be subjected are discussed. Design problems, especially as related to corrosion protection and to mechanical stress caused by wire armoring during manufacturing and laying, accessories and work done on test methods, and the possibility of designing 400 to 600 kV dc cables for transmitting 2000 to 4000 MW are described.

  18. Electrical power cable engineering

    CERN Document Server

    Thue, William A

    2011-01-01

    Fully updated, Electrical Power Cable Engineering, Third Edition again concentrates on the remarkably complex design, application, and preparation methods required to terminate and splice cables. This latest addition to the CRC Press Power Engineering series covers cutting-edge methods for design, manufacture, installation, operation, and maintenance of reliable power cable systems. It is based largely on feedback from experienced university lecturers who have taught courses on these very concepts.The book emphasizes methods to optimize vital design and installation of power cables used in the

  19. COPPER CABLE RECYCLING TECHNOLOGY

    International Nuclear Information System (INIS)

    Chelsea Hubbard

    2001-01-01

    The United States Department of Energy (DOE) continually seeks safer and more cost-effective technologies for use in deactivation and decommissioning (D and D) of nuclear facilities. The Deactivation and Decommissioning Focus Area (DDFA) of the DOE's Office of Science and Technology (OST) sponsors large-scale demonstration and deployment projects (LSDDPs). At these LSDDPs, developers and vendors of improved or innovative technologies showcase products that are potentially beneficial to the DOE's projects and to others in the D and D community. Benefits sought include decreased health and safety risks to personnel and the environment, increased productivity, and decreased costs of operation. The Idaho National Engineering and Environmental Laboratory (INEEL) generated a list of statements defining specific needs and problems where improved technology could be incorporated into ongoing D and D tasks. One such need is to reduce the volume of waste copper wire and cable generated by D and D. Deactivation and decommissioning activities of nuclear facilities generates hundreds of tons of contaminated copper cable, which are sent to radioactive waste disposal sites. The Copper Cable Recycling Technology separates the clean copper from contaminated insulation and dust materials in these cables. The recovered copper can then be reclaimed and, more importantly, landfill disposal volumes can be reduced. The existing baseline technology for disposing radioactively contaminated cables is to package the cables in wooden storage boxes and dispose of the cables in radioactive waste disposal sites. The Copper Cable Recycling Technology is applicable to facility decommissioning projects at many Department of Energy (DOE) nuclear facilities and commercial nuclear power plants undergoing decommissioning activities. The INEEL Copper Cable Recycling Technology Demonstration investigated the effectiveness and efficiency to recycle 13.5 tons of copper cable. To determine the effectiveness

  20. Cable Diagnostic Focused Initiative

    Energy Technology Data Exchange (ETDEWEB)

    Hartlein, R.A.; Hampton, R.N.

    2010-12-30

    This report summarizes an extensive effort made to understand how to effectively use the various diagnostic technologies to establish the condition of medium voltage underground cable circuits. These circuits make up an extensive portion of the electric delivery infrastructure in the United States. Much of this infrastructure is old and experiencing unacceptable failure rates. By deploying efficient diagnostic testing programs, electric utilities can replace or repair circuits that are about to fail, providing an optimal approach to improving electric system reliability. This is an intrinsically complex topic. Underground cable systems are not homogeneous. Cable circuits often contain multiple branches with different cable designs and a range of insulation materials. In addition, each insulation material ages differently as a function of time, temperature and operating environment. To complicate matters further, there are a wide variety of diagnostic technologies available for assessing the condition of cable circuits with a diversity of claims about the effectiveness of each approach. As a result, the benefits of deploying cable diagnostic testing programs have been difficult to establish, leading many utilities to avoid the their use altogether. This project was designed to help address these issues. The information provided is the result of a collaborative effort between Georgia Tech NEETRAC staff, Georgia Tech academic faculty, electric utility industry participants, as well as cable system diagnostic testing service providers and test equipment providers. Report topics include: •How cable systems age and fail, •The various technologies available for detecting potential failure sites, •The advantages and disadvantages of different diagnostic technologies, •Different approaches for utilities to employ cable system diagnostics. The primary deliverables of this project are this report, a Cable Diagnostic Handbook (a subset of this report) and an online

  1. Automated Cable Preparation for Robotized Stator Cable Winding

    Directory of Open Access Journals (Sweden)

    Erik Hultman

    2017-04-01

    Full Text Available A method for robotized cable winding of the Uppsala University Wave Energy Converter generator stator has previously been presented and validated. The purpose of this study is to present and validate further developments to the method: automated stand-alone equipment for the preparation of the winding cables. The cable preparation consists of three parts: feeding the cable from a drum, forming the cable end and cutting the cable. Forming and cutting the cable was previously done manually and only small cable drums could be handled. Therefore the robot cell needed to be stopped frequently. The new equipment was tested in an experimental robot stator cable winding setup. Through the experiments, the equipment was validated to be able to perform fully automated and robust cable preparation. Suggestions are also given on how to further develop the equipment with regards to performance, robustness and quality. Hence, this work represents another important step towards demonstrating completely automated robotized stator cable winding.

  2. Tailored sPP/Silica Nano composite for Eco friendly Insulation of Extruded HVDC Cable

    International Nuclear Information System (INIS)

    Dang, B.; He, J.; Hu, J.; Zhou, Y.

    2015-01-01

    Cross-linked polyethylene (XLPE) is a thermosetting material that cannot be recycled at the end of its lifetime. This study investigated the potential of syndiotactic polypropylene (sPP)/silica as an eco friendly extruded insulation system for HVDC cables. We investigated the morphology, Fourier transform infrared, and thermal, thermomechanical, and electrical behaviors of sPP modified with 0.5-3% nano silica. We found that the silica/sPP nano composite without cross-linking offered a suitable mechanical modulus at room temperature and sufficient intensity at high temperatures, and adding nano silica modified by a silane coupling agent to the sPP resulted in significant DC resistivity and space charge improvement. The optimal nano silica content in the sPP was determined by balancing the mechanical and thermomechanical characteristics and the DC resistivity. The sPP/silica nano composite reported here shows great potential as a candidate insulation material for future eco friendly extruded HVDC cables.

  3. Proposed superscreened cables and connectors

    International Nuclear Information System (INIS)

    Fowler, E.P.

    1975-11-01

    The paper summarises the present availability of superscreened cables and proposes the specification of a family of cables to meet the foreseeable needs of the nuclear power industry. The cable numbering system is described, special tests outlined and important details given for the chosen cables. Appropriate connectors are also discussed and listed with an outline of their required screening performance. (author)

  4. Costly cables; Lange Leitung

    Energy Technology Data Exchange (ETDEWEB)

    Hautmann, Daniel

    2012-08-15

    Connection of offshore wind turbines to the onshore power supply grid requires costly cables for HV DC power transmission. The technology is mature enough to enable low-loss power transmission, but construction times may last several years.

  5. Cable Aerodynamic Control

    DEFF Research Database (Denmark)

    Kleissl, Kenneth

    to a categorization of the different control technics together with an identification of two key mechanisms for reduction of the design drag force. During this project extensive experimental work examining the aerodynamics of the currently used cable surface modifications together with new innovative proposals have...... been conducted. The two current prevailing systems consisting of helically filleted cables and cables with a pattern-indented surface were directly compared under the same conditions and both applications were found with attractive properties. The pattern-indented surface maintained a low supercritical...... of reducing the intensity of the axial flow and disrupting the near wake flow structures. Similar studies during wet conditions with artificial simulation of light rain in the wind tunnel showed that the plain cable suffered from severe rain-wind induced vibrations. But despite the presence of both upper...

  6. Magnet cable manufacturing

    International Nuclear Information System (INIS)

    Royet, J.

    1985-07-01

    The superconducting magnets used in the construction of particle accelerators are mostly built from flat, multistrand cables with rectangular or keystoned cross sections. The superconducting strands are mostly circular but a design of a cable made of preflattened wires was proposed a few years ago under the name of Berkeley flat; such cable shows some interesting characteristics. Another design consists of a few smaller precabled wires (e.g. 6 around 1). This configuration allows smaller filaments and a better transposition of the current elements. The Superconducting Super Collider project involves the largest amount of superconducting cable ever envisaged for a single machine. Furthermore, the design calls for exceptional accuracy and improved characteristics of the cable. A part of the SSC research and development program is focused on these important questions. In this paper we emphasize the difference between the conventional cabling and wires with superconducting. A new concept for the tooling will be introduced as well as the necessary characteristics of a specialized cabler. 5 figs

  7. Instrumentation Cables Test Plan

    Energy Technology Data Exchange (ETDEWEB)

    Muna, Alice Baca [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States); LaFleur, Chris Bensdotter [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States)

    2016-10-01

    A fire at a nuclear power plant (NPP) has the potential to damage structures, systems, and components important to safety, if not promptly detected and suppressed. At Browns Ferry Nuclear Power Plant on March 22, 1975, a fire in the reactor building damaged electrical power and control systems. Damage to instrumentation cables impeded the function of both normal and standby reactor coolant systems, and degraded the operators’ plant monitoring capability. This event resulted in additional NRC involvement with utilities to ensure that NPPs are properly protected from fire as intended by the NRC principle design criteria (i.e., general design criteria 3, Fire Protection). Current guidance and methods for both deterministic and performance based approaches typically make conservative (bounding) assumptions regarding the fire-induced failure modes of instrumentation cables and those failure modes effects on component and system response. Numerous fire testing programs have been conducted in the past to evaluate the failure modes and effects of electrical cables exposed to severe thermal conditions. However, that testing has primarily focused on control circuits with only a limited number of tests performed on instrumentation circuits. In 2001, the Nuclear Energy Institute (NEI) and the Electric Power Research Institute (EPRI) conducted a series of cable fire tests designed to address specific aspects of the cable failure and circuit fault issues of concern1. The NRC was invited to observe and participate in that program. The NRC sponsored Sandia National Laboratories to support this participation, whom among other things, added a 4-20 mA instrumentation circuit and instrumentation cabling to six of the tests. Although limited, one insight drawn from those instrumentation circuits tests was that the failure characteristics appeared to depend on the cable insulation material. The results showed that for thermoset insulated cables, the instrument reading tended to drift

  8. Cable laying methods in a multi-cable elevator system

    Energy Technology Data Exchange (ETDEWEB)

    Dvornikov, V.I.; Makhinyan, V.V.

    1984-01-01

    Based on the solution of differential equations describing the stress and deformation state of cables during rolling on the drum, a conclusion is made concerning a rational method for hanging cables with a free-spinning end.

  9. DC Model Cable under Polarity Inversion and Thermal Gradient: Build-Up of Design-Related Space Charge

    Directory of Open Access Journals (Sweden)

    Nugroho Adi

    2017-07-01

    Full Text Available In the field of energy transport, High-Voltage DC (HVDC technologies are booming at present due to the more flexible power converter solutions along with needs to bring electrical energy from distributed production areas to consumption sites and to strengthen large-scale energy networks. These developments go with challenges in qualifying insulating materials embedded in those systems and in the design of insulations relying on stress distribution. Our purpose in this communication is to illustrate how far the field distribution in DC insulation systems can be anticipated based on conductivity data gathered as a function of temperature and electric field. Transient currents and conductivity estimates as a function of temperature and field were recorded on miniaturized HVDC power cables with construction of 1.5 mm thick crosslinked polyethylene (XLPE insulation. Outputs of the conductivity model are compared to measured field distributions using space charge measurements techniques. It is shown that some features of the field distribution on model cables put under thermal gradient can be anticipated based on conductivity data. However, space charge build-up can induce substantial electric field strengthening when materials are not well controlled.

  10. High Temperature Superconducting Underground Cable

    International Nuclear Information System (INIS)

    Farrell, Roger A.

    2010-01-01

    The purpose of this Project was to design, build, install and demonstrate the technical feasibility of an underground high temperature superconducting (HTS) power cable installed between two utility substations. In the first phase two HTS cables, 320 m and 30 m in length, were constructed using 1st generation BSCCO wire. The two 34.5 kV, 800 Arms, 48 MVA sections were connected together using a superconducting joint in an underground vault. In the second phase the 30 m BSCCO cable was replaced by one constructed with 2nd generation YBCO wire. 2nd generation wire is needed for commercialization because of inherent cost and performance benefits. Primary objectives of the Project were to build and operate an HTS cable system which demonstrates significant progress towards commercial progress and addresses real world utility concerns such as installation, maintenance, reliability and compatibility with the existing grid. Four key technical areas addressed were the HTS cable and terminations (where the cable connects to the grid), cryogenic refrigeration system, underground cable-to-cable joint (needed for replacement of cable sections) and cost-effective 2nd generation HTS wire. This was the worlds first installation and operation of an HTS cable underground, between two utility substations as well as the first to demonstrate a cable-to-cable joint, remote monitoring system and 2nd generation HTS.

  11. The Danish Superconducting Cable Project

    DEFF Research Database (Denmark)

    Tønnesen, Ole

    1997-01-01

    The design and construction of a superconducting cable is described. The cable has a room temperature dielectric design with the cryostat placed inside the electrical insulation.BSCCO 2223 superconducting tapes wound in helix form around a former are used as the cable conductor. Results from...

  12. Cable indenter aging monitor

    International Nuclear Information System (INIS)

    Shook, T.A.; Gardner, J.B.

    1988-07-01

    This project was undertaken to develop a hand-held, nondestructive test device to assess the aged condition of electrical cable by in situ measurement of mechanical properties of polymeric jackets and insulations. The device is an indenter similar to those used to make hardness measurements. Comparison of measurements made on installed cables with previous measurements serving as baseline aging/mechanical property data will determine the state of aging of the field cables. Such a device will be valuable in nuclear and fossil plant life extension programs. Preliminary laboratory tests on cables covered with ethylene propylene rubber (EPR) and chlorosulfated polyethylene (CSPE) point to the measurement of the rate of force increase resulting from constant rate deformation as having the best correlation with progressive thermal aging. This first phase of the work has demonstrated the technical feasibility of the method. A second phase will include the generation of additional groundwork data and the design of the portable indenter for in situ plant measurements

  13. Development of Inspection Robots for Bridge Cables

    Directory of Open Access Journals (Sweden)

    Hae-Bum Yun

    2013-01-01

    Full Text Available This paper presents the bridge cable inspection robot developed in Korea. Two types of the cable inspection robots were developed for cable-suspension bridges and cable-stayed bridge. The design of the robot system and performance of the NDT techniques associated with the cable inspection robot are discussed. A review on recent advances in emerging robot-based inspection technologies for bridge cables and current bridge cable inspection methods is also presented.

  14. Development of inspection robots for bridge cables.

    Science.gov (United States)

    Yun, Hae-Bum; Kim, Se-Hoon; Wu, Liuliu; Lee, Jong-Jae

    2013-01-01

    This paper presents the bridge cable inspection robot developed in Korea. Two types of the cable inspection robots were developed for cable-suspension bridges and cable-stayed bridge. The design of the robot system and performance of the NDT techniques associated with the cable inspection robot are discussed. A review on recent advances in emerging robot-based inspection technologies for bridge cables and current bridge cable inspection methods is also presented.

  15. Cable networks, services, and management

    CERN Document Server

    2015-01-01

    Cable Networks, Services, and Management is the first book to cover cable networks, services, and their management, in-depth, for network operators, engineers, researchers, and students. Thirteen experts in various fields have contributed their knowledge of network architectures and services, Operations, Administration, Maintenance, Provisioning, Troubleshooting (OAMPT) for residential and business services, cloud, Software Defined Networks (SDN), as well as virtualization concepts and their applications as part of the future directions of cable networks. The book begins by introducing architecture and services for Data Over Cable Service Interface Specification (DOCSIS) 3.0/ 3.1, Converged Cable Access Platform (CCAP), Content Distribution Networks (CDN, IP TV, and Packet Cable and Wi-Fi for Residential Services. Topics that are discussed in proceeding chapters include: operational systems and management architectures, service orders, provisioning, fault manageme t, performance management, billing systems a...

  16. 14 CFR 23.689 - Cable systems.

    Science.gov (United States)

    2010-01-01

    ... in cable tension throughout the range of travel under operating conditions and temperature variations... 14 Aeronautics and Space 1 2010-01-01 2010-01-01 false Cable systems. 23.689 Section 23.689... Systems § 23.689 Cable systems. (a) Each cable, cable fitting, turnbuckle, splice, and pulley used must...

  17. Dynamic testing of cable structures

    Directory of Open Access Journals (Sweden)

    Caetano Elsa

    2015-01-01

    Full Text Available The paper discusses the role of dynamic testing in the study of cable structures. In this context, the identification of cable force based on vibration measurements is discussed. Vibration and damping assessment are then introduced as the focus of dynamic monitoring systems, and particular aspects of the structural behaviour under environmental loads are analysed. Diverse application results are presented to support the discussion centred on cable-stayed bridges, roof structures, a guyed mast and a transmission line.

  18. Submerged Medium Voltage Cable Systems at Nuclear Power Plants. A Review of Research Efforts Relevant to Aging Mechanisms and Condition Monitoring

    Energy Technology Data Exchange (ETDEWEB)

    Brown, Jason [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States); Bernstein, Robert [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States); White, II, Gregory Von [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States); Glover, Steven F. [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States); Neely, Jason C. [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States); Pena, Gary [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States); Williamson, Kenneth Martin [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States); Zutavern, Fred J. [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States); Gelbard, Fred [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States)

    2015-03-01

    In a submerged environment, power cables may experience accelerated insulation degradation due to water - related aging mechanisms . Direct contact with water or moisture intrusion in the cable insulation s ystem has been identified in the literature as a significant aging stressor that can affect performance and lifetime of electric cables . Progressive reduction of the dielectric strength is commonly a result of water treeing which involves the development of permanent hydrophilic structures in the insulation coinciding with the absorption of water into the cable . Water treeing is a phenomenon in which dendritic microvoids are formed in electric cable insulation due to electrochemic al reactions , electromechanical forces , and diffusion of contaminants over time . These reactions are caused by the combined effect s of water presence and high electrical stress es in the material . Water tree growth follow s a tree - like branching pattern , i ncreasing in volume and length over time . Although these cables can be "dried out," water tree degradation , specifically the growth of hydrophilic regions, is believed to be permanent and typically worsens over time. Based on established research , water treeing or water induced damage can occur in a variety of electric cables including XLPE, TR - XLPE and other insulating materials, such as EPR and butyl rubber . Once water trees or water induced damage form, the dielectric strength of an insulation materia l will decrease gradually with time as the water trees grow in length, which could eventually result in failure of the insulating material . Under wet conditions or i n submerged environments , several environmental and operational parameters can influence w ater tree initiation and affect water tree growth . These parameters include voltage cycling, field frequency, temperature, ion concentration and chemistry, type of insula tion material , and the characteristics of its defects. In this effort, a review of academic

  19. Electromagnetic transients in power cables

    CERN Document Server

    da Silva, Filipe Faria

    2013-01-01

    From the more basic concepts to the most advanced ones where long and laborious simulation models are required, Electromagnetic Transients in Power Cables provides a thorough insight into the study of electromagnetic transients and underground power cables. Explanations and demonstrations of different electromagnetic transient phenomena are provided, from simple lumped-parameter circuits to complex cable-based high voltage networks, as well as instructions on how to model the cables.Supported throughout by illustrations, circuit diagrams and simulation results, each chapter contains exercises,

  20. Superconducting flat tape cable magnet

    Science.gov (United States)

    Takayasu, Makoto

    2015-08-11

    A method for winding a coil magnet with the stacked tape cables, and a coil so wound. The winding process is controlled and various shape coils can be wound by twisting about the longitudinal axis of the cable and bending following the easy bend direction during winding, so that sharp local bending can be obtained by adjusting the twist pitch. Stack-tape cable is twisted while being wound, instead of being twisted in a straight configuration and then wound. In certain embodiments, the straight length should be half of the cable twist-pitch or a multiple of it.

  1. Cable tray fire tests

    International Nuclear Information System (INIS)

    Klamerus, L.J.

    1978-01-01

    Funds were authorized by the Nuclear Regulatory Commission to provide data needed for confirmation of the suitability of current design standards and regulatory guides for fire protection and control in water reactor power plants. The activities of this program through August 1978 are summarized. A survey of industry to determine current design practices and a screening test to select two cable constructions which were used in small scale and full scale testing are described. Both small and full scale tests to assess the adequacy of fire retardant coatings and full scale tests on fire shields to determine their effectiveness are outlined

  2. Cable deterioration analysis method

    International Nuclear Information System (INIS)

    Sugiyama, Masahiko; Nitta, Makoto.

    1997-01-01

    At first, a hardness of a minute region and an elongation at break are measured relative to a plurality of reference samples having deterioration which is different stepwise, to obtain a relation between the hardness of the minute region and the elongation at break. They are obtained as information of correlation showing the degree of deterioration of cables. Then, samples are collected. The samples are collected from a PVC sheath. In this case, the samples to be used for the measurement are extremely small piece having the size of one side of about several hundred μm. Then, the hardness of the minute region of the samples is measured. The measured hardness of the minute region is corresponded to the previously obtained information of the correlation for deteriorations to judge the state of deterioration for the collected samples. With such procedures, the state of deterioration for electric wires and cables to be used in nuclear facilities such as power plants can easily be diagnosed substantially non destructively. (I.N.)

  3. Cable Television in Sedalia, Missouri.

    Science.gov (United States)

    Lamkin, Kathryn Janel

    A field study was conducted of the status of cable television in Sedalia, Missouri. Based on interviews of city council members and staff members of Cablevision, the Sedalia cable franchise holder, the following issues were investigated: (1) subscription rates; (2) franchise negotiations; (3) quality of existing services; and (4) possible…

  4. The optimum spanning catenary cable

    Science.gov (United States)

    Wang, C. Y.

    2015-03-01

    A heavy cable spans two points in space. There exists an optimum cable length such that the maximum tension is minimized. If the two end points are at the same level, the optimum length is 1.258 times the distance between the ends. The optimum lengths for end points of different heights are also found.

  5. Photonic-powered cable assembly

    Science.gov (United States)

    Sanderson, Stephen N.; Appel, Titus James; Wrye, IV, Walter C.

    2013-01-22

    A photonic-cable assembly includes a power source cable connector ("PSCC") coupled to a power receive cable connector ("PRCC") via a fiber cable. The PSCC electrically connects to a first electronic device and houses a photonic power source and an optical data transmitter. The fiber cable includes an optical transmit data path coupled to the optical data transmitter, an optical power path coupled to the photonic power source, and an optical feedback path coupled to provide feedback control to the photonic power source. The PRCC electrically connects to a second electronic device and houses an optical data receiver coupled to the optical transmit data path, a feedback controller coupled to the optical feedback path to control the photonic power source, and a photonic power converter coupled to the optical power path to convert photonic energy received over the optical power path to electrical energy to power components of the PRCC.

  6. Cable Bacteria in Freshwater Sediments

    DEFF Research Database (Denmark)

    Risgaard-Petersen, Nils; Kristiansen, Michael; Frederiksen, Rasmus

    2015-01-01

    In marine sediments cathodic oxygen reduction at the sediment surface can be coupled to anodic sulfide oxidation in deeper anoxic layers through electrical currents mediated by filamentous, multicellular bacteria of the Desulfobulbaceae family, the so-called cable bacteria. Until now, cable...... bacteria have only been reported from marine environments. In this study, we demonstrate that cable bacteria also occur in freshwater sediments. In a first step, homogenized sediment collected from the freshwater stream Giber Å, Denmark, was incubated in the laboratory. After 2 weeks, pH signatures...... marine cable bacteria, with the genus Desulfobulbus as the closest cultured lineage. The results of the present study indicate that electric currents mediated by cable bacteria could be important for the biogeochemistry in many more environments than anticipated thus far and suggest a common evolutionary...

  7. Length of a Hanging Cable

    Directory of Open Access Journals (Sweden)

    Eric Costello

    2011-01-01

    Full Text Available The shape of a cable hanging under its own weight and uniform horizontal tension between two power poles is a catenary. The catenary is a curve which has an equation defined by a hyperbolic cosine function and a scaling factor. The scaling factor for power cables hanging under their own weight is equal to the horizontal tension on the cable divided by the weight of the cable. Both of these values are unknown for this problem. Newton's method was used to approximate the scaling factor and the arc length function to determine the length of the cable. A script was written using the Python programming language in order to quickly perform several iterations of Newton's method to get a good approximation for the scaling factor.

  8. Investigating the burning characteristics of electric cables used in the nuclear power plant by way of 3-D transient FDS code

    Energy Technology Data Exchange (ETDEWEB)

    Ferng, Y.M., E-mail: ymferng@ess.nthu.edu.t [Department of Engineering and System Science, Institute of Nuclear Engineering and Science, National Tsing Hua University, 101, Sec. 2. Kuang-Fu Rd., Hsinchu 30013, Taiwan (China); Liu, C.H. [Department of Engineering and System Science, Institute of Nuclear Engineering and Science, National Tsing Hua University, 101, Sec. 2. Kuang-Fu Rd., Hsinchu 30013, Taiwan (China)

    2011-01-15

    Burning characteristics of electrical cables are one of the key parameters for the fire hazard assessment of nuclear power plants (NPPs) since the cables are the essential sources of fire in the plants. A three-dimensional (3-D) transient computational fluid dynamics (CFD) code{sub F}DS is adopted in this paper to simulate these characteristics related to the cable burning. Being one of the NRC licensing fire codes, the FDS includes the thermal-hydraulic equations, the turbulence model and the chemical combustion model, etc. In order to assess the CFD fire models used in this code, a burning test using the control cable with the outer jacket of polyvinylchloride (PVC) and the inner insulation of cross-linked polyethylene (XLPE) is conducted. The measured parameters associated with the burning characteristics include the heat release rate (HRR), O{sub 2} depletion, and CO and CO{sub 2} production, etc. Except the amount of O{sub 2} consumption, the predicted transient behaviors of other parameters can reproduce the measured data. Based on the chemical combustion model in the FDS code, this discrepancy may be essentially resulted from the default value of hydrogen fraction (H{sub frac}) contained in the soot since the soot yield for the burning of PVC material is high enough that the uncertainty in the H{sub frac} value has a prominent effect on the amount of O{sub 2} consumption. This explanation can be confirmed by a benchmark calculation for simulating a burning test with the polymethylmethacrylate (PMMA) fuel of low-soot yield. The present simulation works can provide the useful information for the plant staff or the researcher as they would perform the fire hazard analysis in the NPPs using the FDS code.

  9. 10BASE5 Ethernet Cable & Vampire Tap

    CERN Document Server

    1983-01-01

    10BASE5 Thick Ethernet Cable, 10Mbit/sec. In the 1980s and early 1990's, Ethernet became more popular and provided a much faster data transmission rate. This cable is one of the first ethernet cables from 1983, a thick, bulky affair. Computers were attached via "Vampire Taps" which were connectors screwed straight through the shielding of the cable.

  10. 14 CFR 27.1365 - Electric cables.

    Science.gov (United States)

    2010-01-01

    ... 14 Aeronautics and Space 1 2010-01-01 2010-01-01 false Electric cables. 27.1365 Section 27.1365... STANDARDS: NORMAL CATEGORY ROTORCRAFT Equipment Electrical Systems and Equipment § 27.1365 Electric cables. (a) Each electric connecting cable must be of adequate capacity. (b) Each cable that would overheat...

  11. 30 CFR 18.45 - Cable reels.

    Science.gov (United States)

    2010-07-01

    ... and locomotives shall maintain positive tension on the portable cable during reeling and unreeling. Such tension shall only be high enough to prevent a machine from running over its own cable(s). (e... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Cable reels. 18.45 Section 18.45 Mineral...

  12. 14 CFR 25.689 - Cable systems.

    Science.gov (United States)

    2010-01-01

    ... cable system must be designed so that there will be no hazardous change in cable tension throughout the... 14 Aeronautics and Space 1 2010-01-01 2010-01-01 false Cable systems. 25.689 Section 25.689... STANDARDS: TRANSPORT CATEGORY AIRPLANES Design and Construction Control Systems § 25.689 Cable systems. (a...

  13. Cables - a question of custom-design

    International Nuclear Information System (INIS)

    Doig, Tom

    1994-01-01

    Electrical equipment such as cabling can often be the limiting factor as far as machine operations in radioactive environments are concerned. Electronic and electrical equipment will degrade if exposed to ionising radiation, affecting equipment reliability, or causing complete failure. However, several companies provide custom-designed products directed specifically at the nuclear industry. One such company is Habia Cable which has built up its business in submarine cables, internal engine cables, and cables for high fire risk situations. It began supplying custom-designed cables to the nuclear industry in 1986, and has since then supplied cables throughout Europe from its plant in Sweden. (Author)

  14. Motility of electric cable bacteria

    DEFF Research Database (Denmark)

    Bjerg, Jesper Tataru; Damgaard, Lars Riis; Holm, Simon Agner

    2016-01-01

    Cable bacteria are filamentous bacteria that electrically couple sulfide oxidation and oxygen reduction at centimeter distances, and observations in sediment environments have suggested that they are motile. By time-lapse microscopy, we found that cable bacteria used gliding motility on surfaces...... with a highly variable speed of 0.50.3 ms1 (meanstandard deviation) and time between reversals of 155108 s. They frequently moved forward in loops, and formation of twisted loops revealed helical rotation of the filaments. Cable bacteria responded to chemical gradients in their environment, and around the oxic......-anoxic interface, they curled and piled up, with straight parts connecting back to the source of sulfide. Thus, it appears that motility serves the cable bacteria in establishing and keeping optimal connections between their distant electron donor and acceptors in a dynamic sediment environment....

  15. Cable SGEMP Code Validation Study

    Energy Technology Data Exchange (ETDEWEB)

    Ballard, William Parker [Sandia National Lab. (SNL-CA), Livermore, CA (United States). Center for CA Weapons Systems Engineering

    2013-05-01

    This report compared data taken on the Modular Bremsstrahlung Simulator using copper jacketed (cujac) cables with calculations using the RHSD-RA Cable SGEMP analysis tool. The tool relies on CEPXS/ONBFP to perform radiation transport in a series of 1D slices through the cable, and then uses a Green function technique to evaluate the expected current drive on the center conductor. The data were obtained in 2003 as part of a Cabana verification and validation experiment using 1-D geometries, but were not evaluated until now. The agreement between data and model is not adequate unless gaps between the dielectric and outer conductor (ground) are assumed, and these gaps are large compared with what is believed to be in the actual cable.

  16. Air flow around suspended cables

    Directory of Open Access Journals (Sweden)

    Gołębiowska Irena

    2017-01-01

    Full Text Available The impact of wind on construction structures is essential issue in design and operation. In particular, the wind can cause the dengerous vibrations of slender structures with low rigidity, eg. vibrations of cables of suspension and cable-stayed bridges or high voltage transmision lines, thus understanding of wind flow around such constructions is significant. In the paper the results of the analysis of wind flow around the cables for different Reynolds number is presented. The analysed flow meets the Navier-Stokes and continuity equations. The circle and elipse section of the cable is analysed. The discusion of vorticity, drag and lift coefficients and cases due to different angle of wind flow action is presented. The boundary layer and its infuence on total flow is analysed.

  17. Nuclear instrumentation cable end seal

    International Nuclear Information System (INIS)

    Cannon, C.P.; Brown, D.P.

    1979-01-01

    An improved coaxial end seal for hermetically sealed nuclear instrumentation cable exhibiting an improved breakdown pulse noise characteristic under high voltage, high temperature conditions is described. A tubular insulator body has metallized interior and exterior surface portions which are braze sealed to a center conductor and an outer conductive sheath. The end surface of the insulator body which is directed toward the coaxial cable to which it is sealed has a recessed surface portion within which the braze seal material terminates

  18. Comparison of Conductor-Temperature Calculations Based on Different Radial-Position-Temperature Detections for High-Voltage Power Cable

    Directory of Open Access Journals (Sweden)

    Lin Yang

    2018-01-01

    Full Text Available In this paper, the calculation of the conductor temperature is related to the temperature sensor position in high-voltage power cables and four thermal circuits—based on the temperatures of insulation shield, the center of waterproof compound, the aluminum sheath, and the jacket surface are established to calculate the conductor temperature. To examine the effectiveness of conductor temperature calculations, simulation models based on flow characteristics of the air gap between the waterproof compound and the aluminum are built up, and thermocouples are placed at the four radial positions in a 110 kV cross-linked polyethylene (XLPE insulated power cable to measure the temperatures of four positions. In measurements, six cases of current heating test under three laying environments, such as duct, water, and backfilled soil were carried out. Both errors of the conductor temperature calculation and the simulation based on the temperature of insulation shield were significantly smaller than others under all laying environments. It is the uncertainty of the thermal resistivity, together with the difference of the initial temperature of each radial position by the solar radiation, which led to the above results. The thermal capacitance of the air has little impact on errors. The thermal resistance of the air gap is the largest error source. Compromising the temperature-estimation accuracy and the insulation-damage risk, the waterproof compound is the recommended sensor position to improve the accuracy of conductor-temperature calculation. When the thermal resistances were calculated correctly, the aluminum sheath is also the recommended sensor position besides the waterproof compound.

  19. Static and Dynamic Characteristics of a Long-Span Cable-Stayed Bridge with CFRP Cables

    Directory of Open Access Journals (Sweden)

    Xu Xie

    2014-06-01

    Full Text Available In this study, the scope of CFRP cables in cable-stayed bridges is studied by establishing a numerical model of a 1400-m span of the same. The mechanical properties and characteristics of CFRP stay cables and of a cable-stayed bridge with CFRP cables are here subjected to comprehensive analysis. The anomalies in the damping properties of free vibration, nonlinear parametric vibration and wind fluctuating vibration between steel cables and CFRP cables are determined. The structural stiffness, wind resistance and traffic vibration of the cable-stayed bridge with CFRP cables are also analyzed. It was found that the static performances of a cable-stayed bridge with CFRP cables and steel cables are basically the same. The natural frequencies of CFRP cables do not coincide with the major natural frequencies of the cable-stayed bridge, so the likelihood of CFRP cable-bridge coupling vibration is minuscule. For CFRP cables, the response amplitudes of both parametric vibration and wind fluctuating vibration are smaller than those of steel cables. It can be concluded from the research that the use of CFRP cables does not change the dynamic characteristics of the vehicle-bridge coupling vibration. Therefore, they can be used in long-span cable-stayed bridges with an excellent mechanical performance.

  20. Static and Dynamic Characteristics of a Long-Span Cable-Stayed Bridge with CFRP Cables.

    Science.gov (United States)

    Xie, Xu; Li, Xiaozhang; Shen, Yonggang

    2014-06-23

    In this study, the scope of CFRP cables in cable-stayed bridges is studied by establishing a numerical model of a 1400-m span of the same. The mechanical properties and characteristics of CFRP stay cables and of a cable-stayed bridge with CFRP cables are here subjected to comprehensive analysis. The anomalies in the damping properties of free vibration, nonlinear parametric vibration and wind fluctuating vibration between steel cables and CFRP cables are determined. The structural stiffness, wind resistance and traffic vibration of the cable-stayed bridge with CFRP cables are also analyzed. It was found that the static performances of a cable-stayed bridge with CFRP cables and steel cables are basically the same. The natural frequencies of CFRP cables do not coincide with the major natural frequencies of the cable-stayed bridge, so the likelihood of CFRP cable-bridge coupling vibration is minuscule. For CFRP cables, the response amplitudes of both parametric vibration and wind fluctuating vibration are smaller than those of steel cables. It can be concluded from the research that the use of CFRP cables does not change the dynamic characteristics of the vehicle-bridge coupling vibration. Therefore, they can be used in long-span cable-stayed bridges with an excellent mechanical performance.

  1. The RHIC transfer line cable database

    International Nuclear Information System (INIS)

    Scholl, E.H.; Satogata, T.

    1995-01-01

    A cable database was created to facilitate and document installation of cables and wiring in the RHIC project, as well as to provide a data source to track possible wiring and signal problems. The eight tables of this relational database, currently implemented in Sybase, contain information ranging from cable routing to attenuation of individual wires. This database was created in a hierarchical scheme under the assumption that cables contain wires -- each instance of a cable has one to many wires associated with it. This scheme allows entry of information pertinent to individual wires while only requiring single entries for each cable. Relationships to other RHIC databases are also discussed

  2. Optical Measurement of Cable and String Vibration

    Directory of Open Access Journals (Sweden)

    Y. Achkire

    1998-01-01

    Full Text Available This paper describes a non contacting measurement technique for the transverse vibration of small cables and strings using an analog position sensing detector. On the one hand, the sensor is used to monitor the cable vibrations of a small scale mock-up of a cable structure in order to validate the nonlinear cable dynamics model. On the other hand, the optical sensor is used to evaluate the performance of an active tendon control algorithm with guaranteed stability properties. It is demonstrated experimentally, that a force feedback control law based on a collocated force sensor measuring the tension in the cable is feasible and provides active damping in the cable.

  3. Static and Dynamic Mechanical Properties of Long-Span Cable-Stayed Bridges Using CFRP Cables

    Directory of Open Access Journals (Sweden)

    Mei Kuihua

    2017-01-01

    Full Text Available The elastic modulus and deadweight of carbon fiber-reinforced polymer (CFRP cables are different from those of steel cables. Thus, the static and dynamic behaviors of cable-stayed bridges using CFRP cables are different from those of cable-stayed bridges using steel cables. The static and dynamic performances of the two kinds of bridges with a span of 1000 m were studied using the numerical method. The effects of geometric nonlinear factors on static performance of the two kinds of cable-stayed bridges were analyzed. The live load effects and temperature effects of the two cable-stayed bridges were also analyzed. The influences of design parameters, including different structural systems, the numbers of auxiliary piers, and the space arrangement types of cable, on the dynamic performance of the cable-stayed bridge using CFRP cables were also studied. Results demonstrate that sag effect of the CFRP cable is much smaller than that of steel cable. The temperature effects of CFRP cable-stayed bridge are less than those of steel cable-stayed bridge. The vertical bending natural vibration frequency of the CFRP cable-stayed bridge is generally lower than that of steel cable-stayed bridge, whereas the torsional natural vibration frequency of the former is higher than that of the latter.

  4. Umbilical Cable Recovery Load Analysis

    Institute of Scientific and Technical Information of China (English)

    YAN Shu-wang; JIA Zhao-lin; FENG Xiao-wei; LI Shi-tao

    2013-01-01

    Umbilical cable is a kind of integrated subsea cable widely used in the exploration and exploitation of oil and gas field.The severe ocean environment makes great challenges to umbilical maintenance and repair work.Damaged umbilical is usually recovered for the regular operation of the offshore production system.Analysis on cables in essence is a two-point boundary problem.The tension load at the mudline must be known first,and then the recovery load and recovery angle on the vessel can be solved by use of catenary equation.The recovery analysis also involves umbilicalsoil interaction and becomes more complicated.Calculation methods for recovery load of the exposed and buried umbilical are established and the relationship between the position of touch down point and the recovery load as well as the recovery angle and recovery load are analyzed.The analysis results provide a theoretical reference for offshore on-deck operation.

  5. Cable fire tests in France

    International Nuclear Information System (INIS)

    Kaercher, M.

    2000-01-01

    Modifications are being carried out in all French nuclear power plants to improve fire safety. These modifications are based on a three level defense in depth concept: fire preventing, fire containing and fire controlling. Fire containing requires many modifications such as protection of cable races and assessment of fire propagation which both need R and D development. On one hand, cable wraps made with mineral wool were tested in all configurations including effect of aging, overheating and fire and qualified for the use as protection from common failure modes. On the other hand, cables races in scale one were subject to gas burner or solvent pool fire to simulate ignition and fire propagation between trays and flash over situations. These tests have been performed under several typical lay out conditions. The results of the tests can be used as input data in computer modelling for validation of fire protection measures. (orig.) [de

  6. Online Cable Tester and Rerouter

    Science.gov (United States)

    Lewis, Mark; Medelius, Pedro

    2012-01-01

    Hardware and algorithms have been developed to transfer electrical power and data connectivity safely, efficiently, and automatically from an identified damaged/defective wire in a cable to an alternate wire path. The combination of online cable testing capabilities, along with intelligent signal rerouting algorithms, allows the user to overcome the inherent difficulty of maintaining system integrity and configuration control, while autonomously rerouting signals and functions without introducing new failure modes. The incorporation of this capability will increase the reliability of systems by ensuring system availability during operations.

  7. Data Base On Cables And Connectors

    Science.gov (United States)

    Bowen, Arlen R.; Oliver, John D.

    1995-01-01

    Report describes Connector Adapter Cable Information Data Base (CONNAID) computer program, managing data base containing necessary information concerning electrical connectors, breakout boxes, adapter cables, backshells, and pertinent torque specifications for engineering project.

  8. OTEC riser cable model and prototype testing

    Science.gov (United States)

    Kurt, J. P.; Schultz, J. A.; Roblee, L. H. S.

    1981-12-01

    Two different OTEC riser cables have been developed to span the distance between a floating OTEC power plant and the ocean floor. The major design concerns for a riser cable in the dynamic OTEC environment are fatigue, corrosion, and electrical/mechanical aging of the cable components. The basic properties of the cable materials were studied through tests on model cables and on samples of cable materials. Full-scale prototype cables were manufactured and were tested to measure their electrical and mechanical properties and performance. The full-scale testing was culminated by the electrical/mechanical fatigue test, which exposes full-scale cables to simultaneous tension, bending and electrical loads, all in a natural seawater environment.

  9. 30 CFR 7.407 - Test for flame resistance of electric cables and cable splices.

    Science.gov (United States)

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Test for flame resistance of electric cables... Electric Cables, Signaling Cables, and Cable Splice Kits § 7.407 Test for flame resistance of electric... material and 21/2 inches of conductor insulation. The type, amperage, voltage rating, and construction of...

  10. Trenchless Replacement of Buried Cable Lines

    Directory of Open Access Journals (Sweden)

    Hans-Joachim Bayer

    2007-01-01

    Full Text Available An enormous amount of underground electricity and telecommunication cables have been worn over the time with technical defects or need capacity increases. Thus, new lines need to be installed. In urban areas, even in smaller communities and in natural reserves, open trenching is difficult and often not permitted.In response, new patented methods of trenchless cable replacement using the HDD equipment have been developed by the TT Group. The new technology is called “Wash-over-cable-replacement” and applies specially designed drill heads, cutting around the old cable string in various configurations (completely closed, U-shape or S-shape embracing, depending to the coating type of the old cable. This special cable replacement drill head separates the cable from the surrounding adhesive soil or the sand bedding by creating a very small annular space around the cable thus enabling the pulling or dragging out of the old cable section between the start and the exit pit. After the old cable has been loosened from the surrounding soil by means of the wash over process and pulled out, the new cable can be smoothly pulled into the void using the drill rods and embedding the new cable in a rich bed of Bentonite.The wash-over drill heads are slim and have inner and outer nozzles for Bentonite and bits to handle roots, pebbles, gravel and the like. These drill heads perform very quickly (up to 3 meters per minute to effectively wash over existing cables without damaging the cable coating and prepare the ground for a fast new laying of a new cable in the existing line. Network owners also benefit from the fact that new geodetic or topographic surveys and documentations of the new cable are not necessary. Only the documents, remarks, technical codes and existing geodetic data need to be updated.The paper will outline the technological background and include several practical job examples.

  11. Active optical cable for intrasatellite communications

    Science.gov (United States)

    Blasco, J.; Cano, D.; Navasquillo, O.; Esteban, M. A.

    2017-11-01

    DAS Photonics and Airbus Defence and Space (Spain) have been working for more than six years in the concept of an Active Optical Cable (AOC) for copper cable substitution. The main advantages that AOC offers are significant mass and size saving, better flexibility and routing of the cable and immunity to EMI.

  12. Cable Television Report and Suggested Ordinance.

    Science.gov (United States)

    League of California Cities, Sacramento.

    Guidelines and suggested ordinances for cable television regulation by local governments are comprehensively discussed in this report. The emphasis is placed on franchising the cable operator. Seventeen legal aspects of franchising are reviewed, and an exemplary ordinance is presented. In addition, current statistics about cable franchising in…

  13. Remote Acquisition Amplifier For 50-Ohm Cable

    Science.gov (United States)

    Amador, Jose J.

    1995-01-01

    Buffer-amplifier unit designed to drive 50-Ohm cables up to 100 ft. (30 m) long, compensating for attenuation in cables and enabling remote operation of oscilloscopes. Variable resistor provides for adjustment of gain of amplifier, such that overall gain from input terminals of amplifier to output end of cable set to unity.

  14. 300 Area signal cable study

    International Nuclear Information System (INIS)

    Whattam, J.W.

    1994-01-01

    This report was prepared to discuss the alternatives available for removing the 300 Area overhead signal cable system. This system, installed in 1969, has been used for various monitoring and communication signaling needs throughout the 300 Area. Over the years this cabling system has deteriorated, has been continually reconfigured, and has been poorly documented to the point of nonreliability. The first step was to look at the systems utilizing the overhead signal cable that are still required for operation. Of the ten systems that once operated via the signal cable, only five are still required; the civil defense evacuation alarms, the public address (PA) system, the criticality alarms, the Pacific Northwest Laboratory Facilities Management Control System (FMCS), and the 384 annunciator panel. Of these five, the criticality alarms and the FMCS have been dealt with under other proposals. Therefore, this study focused on the alternatives available for the remaining three systems (evacuation alarms, PA system, and 384 panel) plus the accountability aid phones. Once the systems to be discussed were determined, then three alternatives for providing the signaling pathway were examined for each system: (1) re-wire using underground communication ducts, (2) use the Integrated Voice/Data Telecommunications System (IVDTS) already installed and operated by US West, and (3) use radio control. Each alternative was developed with an estimated cost, advantages, and disadvantages. Finally, a recommendation was provided for the best alternative for each system

  15. Arrangement for guiding transport cables

    International Nuclear Information System (INIS)

    1981-01-01

    This patent relates especially to x-ray equipment such as that used for computerized tomography, and in particular to an arrangement for guiding and supporting a plurality of power transmission cables and cooling hoses in a flexible manner. (U.K.)

  16. Selecting a Cable System Operator.

    Science.gov (United States)

    Cable Television Information Center, Washington, DC.

    Intended to assist franchising authorities with the process of selecting a cable television system operator from franchise applicants, this document provides a framework for analysis of individual applications. Section 1 deals with various methods which can be used to select an operator. The next section covers the application form, the vehicle a…

  17. Offshore Cable Installation - Lillgrund. Lillgrund Pilot Project

    Energy Technology Data Exchange (ETDEWEB)

    Unosson, Oscar [Vattenfall Vindkraft AB, Stockholm (Sweden)

    2009-01-15

    This report describes the installation method and the experiences gained during the installation of the submarine cables for the offshore wind farm at Lillgrund. The wind farm consists of 48 wind turbines and is expected to produce 0.33 TWh annually. Different aspects of the installation, such as techniques, co-operation between the installation teams, weather conditions and regulatory and environmental issues are described in this report. In addition, recommendations and guidelines are provided, which hopefully can be utilised in future offshore wind projects. The trenches, in which the submarine cables were laid, were excavated weeks before the cable laying. This installation technique proved to be successful for the laying of the inter array cables. The export cable, however, was laid into position with difficulty. The main reason why the laying of the export cable proved more challenging was due to practical difficulties connected with the barge entrusted with the cable laying, Nautilus Maxi. The barge ran aground a number of times and it had difficulties with the thrusters, which made it impossible to manoeuvre. When laying the inter array cables, the method specification was closely followed, and the laying of the cables was executed successfully. The knowledge and experience gained from the offshore cable installation in Lillgrund is essential when writing technical specifications for new wind plant projects. It is recommended to avoid offshore cable installation work in winter seasons. That will lower the chances of dealing with bad weather and, in turn, will reduce the risks

  18. Tubing and cable cutting tool

    Science.gov (United States)

    Mcsmith, D. D.; Richardson, J. I. (Inventor)

    1984-01-01

    A hand held hydraulic cutting tool was developed which is particularly useful in deactivating ejection seats in military aircraft rescue operations. The tool consists primarily of a hydraulic system composed of a fluid reservoir, a pumping piston, and an actuator piston. Mechanical cutting jaws are attached to the actuator piston rod. The hydraulic system is controlled by a pump handle. As the pump handle is operated the actuator piston rod is forced outward and thus the cutting jaws are forced together. The frame of the device is a flexible metal tubing which permits easy positioning of the tool cutting jaws in remote and normally inaccessible locations. Bifurcated cutting edges ensure removal of a section of the tubing or cable to thereby reduce the possibility of accidental reactivation of the tubing or cable being severed.

  19. Electromagnetic Transients in Power Cables

    DEFF Research Database (Denmark)

    Silva, Filipe Faria Da; Bak, Claus Leth

    . The chapter ends by proposing a systematic method that can be used when doing the insulation co-ordination study for a line, as well as the modelling requirements, both modelling depth and modelling detail of the equipment, for the study of the different types of transients followed by a step-by-step generic...... typically used for the screens of cables (both-ends bonding and cross-boding) and also presents methods that can be used to estimate the maximum current of a cable for different types of soils, i.e. thermal calculations. The end of the chapter introduces the shunt reactor, which is an important element...... detail of the equipment, for the study of the different types of transients followed by a step-by-step generic example....

  20. Comparison study of cable geometries and superconducting tape layouts for high-temperature superconductor cables

    Science.gov (United States)

    Ta, Wurui; Shao, Tianchong; Gao, Yuanwen

    2018-04-01

    High-temperature superconductor (HTS) rare-earth-barium-copper-oxide (REBCO) tapes are very promising for use in high-current cables. The cable geometry and the layout of the superconducting tapes are directly related to the performance of the HTS cable. In this paper, we use numerical methods to perform a comparison study of multiple-stage twisted stacked-tape cable (TSTC) conductors to find better cable structures that can both improve the critical current and minimize the alternating current (AC) losses of the cable. The sub-cable geometry is designed to have a stair-step shape. Three superconducting tape layouts are chosen and their transport performance and AC losses are evaluated. The magnetic field and current density profiles of the cables are obtained. The results show that arrangement of the superconducting tapes from the interior towards the exterior of the cable based on their critical current values in descending order can enhance the cable's transport capacity while significantly reducing the AC losses. These results imply that cable transport capacity improvements can be achieved by arranging the superconducting tapes in a manner consistent with the electromagnetic field distribution. Through comparison of the critical currents and AC losses of four types of HTS cables, we determine the best structural choice among these cables.

  1. An industrial cabling machine for the SSC

    International Nuclear Information System (INIS)

    Royet, J.; Armer, R.; Hannaford, R.; Scanlan, R.

    1989-02-01

    The SSC project will need the manufacturing of some 25,000 kilometers of keystoned flat cable. The technical specifications of the various cables to be produced are the result of five years of research and development work at LBL. An experimental cable machine was built and run in the laboratory; many improvements were implemented and tested. Semi-industrial production of the various cables was performed, and the resulting cables were used and tested in the one-meter model magnets and 17.5 meter dipole prototypes. From these experiments an industrial cabler specification was generated and used for an international RFQ. The winner of the contract is Dour Metal, a Belgium company that built the first industrial prototype which is now in a production line at New England Electric Wire Company. In this paper we describe the main characteristics of the machine and give the first industrial production results of superconducting keystoned cable for the SSC project. 4 refs

  2. Initial tension loss in cerclage cables.

    Science.gov (United States)

    Ménard, Jérémie; Émard, Maxime; Canet, Fanny; Brailovski, Vladimir; Petit, Yvan; Laflamme, George Y

    2013-10-01

    Cerclage cables, frequently used in the management of fractures and osteotomies, are associated with a high failure rate and significant loosening during surgery. This study compared the capacity to maintain tension of different types of orthopaedic cable systems. Multifilament Cobalt-Chrome (CoCr) cables with four different crimp/clamp devices (DePuy, Stryker, Zimmer and Smith&Nephew) and one non-metallic Nylon (Ny) cable from Kinamed were instrumented with a load cell to measure tension during insertion. Significant tension loss was observed with crimping for all cables (Ptensioner led to an additional unexpected tension loss (CoCr-DePuy: 18%, CoCr-Stryker: 29%, CoCr-Smith&Nephew: 33%, Ny: 46%, and CoCr-Zimmer: 52%). The simple CoCr (DePuy) cable system outperformed the more sophisticated locking devices due to its significantly better ability to prevent tension loss. Copyright © 2013 Elsevier Inc. All rights reserved.

  3. Fatigue of cable anchorage of large cable stayed bridge; Daikibo shachokyo cable teichaku kozo no hiro

    Energy Technology Data Exchange (ETDEWEB)

    Endo, T.; Matsumoto, T. [Honshu-Shikoku Bridge Authority, Tokyo (Japan); Tsukahara, H. [Yokogawa Bridge Corp., Tokyo (Japan); Miki, C. [Tokyo Institute of Technology, Tokyo (Japan)

    1995-10-21

    Design considerations such as design schemes, the assemblage and welding of steel plates, and safety for fatigue of welded connections have to be taken for the cable anchorages of the steel cable stayed bridges. In this study, two full scale models, which have different shape of box anchorages welded to the web of the main girder, were made to investigate fatigue characteristics as well as assemblage of plate and gelding details. Finite element analyses for both test models and actual bridges here carried out to compare stress distribution. It was confirmed that the assemblage and welding of both types of box anchorage were attainable kith required quality and accuracy. According to the fatigue test, fatigue cracks originated from the weldings of the bearing plate to which the load from cable socket applied directly were caused by out-of-plane bending of the bearing plate. It was proved that the slight modifications of the details around the bearing plate resulted in sufficient fatigue strength in both types of anchorage. 1 ref., 23 figs., 2 tabs.

  4. 47 CFR 76.802 - Disposition of cable home wiring.

    Science.gov (United States)

    2010-10-01

    ... 47 Telecommunication 4 2010-10-01 2010-10-01 false Disposition of cable home wiring. 76.802... MULTICHANNEL VIDEO AND CABLE TELEVISION SERVICE Cable Inside Wiring § 76.802 Disposition of cable home wiring. (a)(1) Upon voluntary termination of cable service by a subscriber in a single unit installation, a...

  5. Low Friction Cryostat for HTS Power Cable of Dutch Project

    NARCIS (Netherlands)

    Chevtchenko, O.; Zuijderduin, R.; Smit, J.; Willen, D.; Lentge, H.; Thidemann, C.; Traeholt, C.

    2012-01-01

    Particulars of 6 km long HTS AC power cable for Amsterdam project are: a cable has to fit in an annulus of 160 mm, with only two cooling stations at the cable ends [1]. Application of existing solutions for HTS cables would result in excessively high coolant pressure drop in the cable, possibly

  6. Field application of a cable NDT system for cable-stayed bridge using MFL sensors integrated

    Energy Technology Data Exchange (ETDEWEB)

    Kim, Ju Won; Choi, Jun Sung; Park, Seung Hee [Sungkyunkwan University, Seoul (Korea, Republic of); Lee, Eun Chan [Korea Maintance Co., Ltd., Seoul (Korea, Republic of)

    2014-02-15

    In this study, an automated cable non-destructive testing(NDT) system was developed to monitor the steel cables that are a core component of cable-stayed bridges. The magnetic flux leakage(MFL) method, which is suitable for ferromagnetic continuum structures and has been verified in previous studies, was applied to the cable inspection. A multi-channel MFL sensor head was fabricated using hall sensors and permanent magnets. A wheel-based cable climbing robot was fabricated to improve the accessibility to the cables, and operating software was developed to monitor the MFL-based NDT research and control the climbing robot. Remote data transmission and robot control were realized by applying wireless LAN communication. Finally, the developed element techniques were integrated into an MFL-based cable NDT system, and the field applicability of this system was verified through a field test at Seohae Bridge, which is a typical cable-stayed bridge currently in operation.

  7. Field application of a cable NDT system for cable-stayed bridge using MFL sensors integrated

    International Nuclear Information System (INIS)

    Kim, Ju Won; Choi, Jun Sung; Park, Seung Hee; Lee, Eun Chan

    2014-01-01

    In this study, an automated cable non-destructive testing(NDT) system was developed to monitor the steel cables that are a core component of cable-stayed bridges. The magnetic flux leakage(MFL) method, which is suitable for ferromagnetic continuum structures and has been verified in previous studies, was applied to the cable inspection. A multi-channel MFL sensor head was fabricated using hall sensors and permanent magnets. A wheel-based cable climbing robot was fabricated to improve the accessibility to the cables, and operating software was developed to monitor the MFL-based NDT research and control the climbing robot. Remote data transmission and robot control were realized by applying wireless LAN communication. Finally, the developed element techniques were integrated into an MFL-based cable NDT system, and the field applicability of this system was verified through a field test at Seohae Bridge, which is a typical cable-stayed bridge currently in operation.

  8. Power cables now and in the future

    Energy Technology Data Exchange (ETDEWEB)

    Wanser, G

    1976-01-01

    A survey is presented of the problems to be faced with the underground supply of electric power to large, urban areas and of the contributions that improvements in power cable technology will make to solving these problems. It is concluded that the increase in population densities and the rising demand for energy on the part of individual consumers bring up problems for electricity supply and thus have a direct influence on development trends in cable engineering. During the last few years the increasing capacities required in power transmission have led to the use of higher voltages and to the application of special methods of cooling for the oil-filled cable. When the technical and economic possibilities with present-day cable techniques have been exhausted, we must anticipate the introduction of new types of cable, i.e., gas-insulated cables and superconducting cables. The problems involved in power distribution are being solved successfully by resorting to larger conductor cross-sectional areas and by raising the voltage levels. The advantages of plastic cables are also being utilized on a wide scale. The requirement that there be freedom from partial discharges in plastic cables operating at medium and higher voltages is becoming increasingly more widely adopted as a new quality criterion in cable engineering. New materials from the polymer range are permitting the introduction of fittings which are easier to install and which reduce costs. Cable engineering has already, to a considerable extent, adapted itself to face future problems. Even so, there are still a large number of problems in cable engineering requiring research, development and operation.

  9. High-voltage polymeric insulated cables

    Energy Technology Data Exchange (ETDEWEB)

    Ross, A

    1987-01-01

    Reviews developments in high-voltage (here defined as 25 kV, 66 kV and 132 kV) polymeric insulated cables in the UK over the period 1979-1986, with particular reference to the experience of the Eastern Electricity Board. Outlines the background to the adoption of XPLE-insulated solid cable, and the design, testing, terminations, jointing and costs of 25 kV, 66 kV and 132 kV cables.

  10. Device for guiding various diameter size cable

    Energy Technology Data Exchange (ETDEWEB)

    Litvinov, I.M.; Klauzer, L.P.; Yeganov, L.I.; Zaripov, A.M.

    1982-01-30

    A design is submitted for a device to guide cable of various diameters. This device consists of a profiled multiple-pass roller, and clamps for uniting cut cable. This design is simplified by allowing both the rollers and their supports to rotate on the roller axis thus facilitating interaction with the clamps. The working surface of the supports is evolute while the outside surfaces have screw-channels for transfering the cable from one roller pass to the other.

  11. Vincennes University: Pioneer in Cable TV

    Science.gov (United States)

    Beckes, Isaac K.

    1972-01-01

    The development of cable educational television at Vincennes University (Indiana) is discussed in terms of the financing, securing of franchises, educational goals and plans for future expansion. (RN)

  12. How do you like them cables?

    CERN Multimedia

    Sergei Malyukov

    Cabling work is not for clautrophobic people! Cables are like the blood vessels and nervous system of ATLAS. With the help of all these cables, we can power ATLAS, control the detector and read out the data. Like the human blood vessels, they penetrate inside the ATLAS volume, reaching each of its elements. The ATLAS developers started to think about design of services, cables and pipes at the very first stages of the project. The cabling project has been developing most intensively during the last five years, passing through the projection and CAD design phases, then the installation of cable trays and finally the cables. The cable installation itself took two and a half years and was done by teams of technicians from several institutes from Russia, the Czech Republic and Poland. Here are some numbers to illustrate the scale of the ATLAS cabling system. More than 25000 optical fiber channels are used for reading the information from the sub-detectors and delivering the timing signals. The total numbe...

  13. Capacitor discharge process for welding braided cable

    Science.gov (United States)

    Wilson, Rick D.

    1995-01-01

    A capacitor discharge process for welding a braided cable formed from a plurality of individual cable strands to a solid metallic electrically conductive member comprises the steps of: (a) preparing the electrically conductive member for welding by bevelling one of its end portions while leaving an ignition projection extending outwardly from the apex of the bevel; (b) clamping the electrically conductive member in a cathode fixture; (c) connecting the electrically conductive member clamped in the cathode fixture to a capacitor bank capable of being charged to a preselected voltage value; (d) preparing the braided cable for welding by wrapping one of its end portions with a metallic sheet to form a retaining ring operable to maintain the individual strands of the braided cable in fixed position within the retaining ring; (e) clamping the braided cable and the retaining ring as a unit in an anode fixture so that the wrapped end portion of the braided cable faces the ignition projection of the electrically conductive member; and (f) moving the cathode fixture towards the anode fixture until the ignition projection of the electrically conductive member contacts the end portion of the braided cable thereby allowing the capacitor bank to discharge through the electrically conductive member and through the braided cable and causing the electrically conductive member to be welded to the braided cable via capacitor discharge action.

  14. Analytical and numerical construction of equivalent cables.

    Science.gov (United States)

    Lindsay, K A; Rosenberg, J R; Tucker, G

    2003-08-01

    The mathematical complexity experienced when applying cable theory to arbitrarily branched dendrites has lead to the development of a simple representation of any branched dendrite called the equivalent cable. The equivalent cable is an unbranched model of a dendrite and a one-to-one mapping of potentials and currents on the branched model to those on the unbranched model, and vice versa. The piecewise uniform cable, with a symmetrised tri-diagonal system matrix, is shown to represent the canonical form for an equivalent cable. Through a novel application of the Laplace transform it is demonstrated that an arbitrary branched model of a dendrite can be transformed to the canonical form of an equivalent cable. The characteristic properties of the equivalent cable are extracted from the matrix for the transformed branched model. The one-to-one mapping follows automatically from the construction of the equivalent cable. The equivalent cable is used to provide a new procedure for characterising the location of synaptic contacts on spinal interneurons.

  15. 30 CFR 77.601 - Trailing cables or portable cables; temporary splices.

    Science.gov (United States)

    2010-07-01

    ... LABOR COAL MINE SAFETY AND HEALTH MANDATORY SAFETY STANDARDS, SURFACE COAL MINES AND SURFACE WORK AREAS OF UNDERGROUND COAL MINES Trailing Cables § 77.601 Trailing cables or portable cables; temporary... or splices that heat or spark under load shall not be used. ...

  16. Switching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines

    DEFF Research Database (Denmark)

    da Silva, Filipe Miguel Faria; Bak, Claus Leth; Balle Holst, Per

    2011-01-01

    The disconnection of HV underground cables may, if unsuccessful, originate a restrike in the circuit breaker, leading to high overvoltages, and potentially damaging the cable and near equipment. Due to the cable high capacitance and low resistance the voltage damping is slow, resulting, half a cy...

  17. Danida1

    DEFF Research Database (Denmark)

    Henriksen, Mogens

    1996-01-01

    At the request of Danish Ministry of Foreign Affairs, Department TSA.4, electrical testing of possibly damaged cables has been evaluated. This matter concerns three different types of cable, which are10 km 30(36) kV XLPE armoured submarine power cable, 1-phase15 km 30(36) kV XLPE armoured...

  18. Danida3

    DEFF Research Database (Denmark)

    Henriksen, Mogens

    1996-01-01

    At the request of Danish Ministry of Foreign Affairs, Department TSA.4, electrical testing of possibly damaged cables has been evaluated. This matter concerns three different types of cable, which are,10 km 30(36) kV XLPE armoured submarine power cable, 1-phase15 km 30(36) kV XLPE armoured...

  19. Understanding losses in three core armoured submarine cables

    DEFF Research Database (Denmark)

    Silva, Filipe Miguel Faria da; Ebdrup, Thomas; Bak, Claus Leth

    2016-01-01

    . For practical an economical reasons the preferred choice of cable for both the array and the transmission cables are three-core armoured submarine cables. Therefore, it has becoming increasingly important to be able to calculate the ampacity of such cables accurately. At present time, the ampacity of three......-core armoured submarine cables is calculated according to IEC 60287-1-1 [1]. Various measurements conducted both by cable manufacturers and transmission system operators (TSO) have shown that using the cable rating method stated in IEC 60287-1-1 underestimates the cable ampacity [2]-[6]. Furthermore......, measurements conducted within the cable industry have shown that an armoured three core cable has higher losses than equal unarmoured three core cables. It is also suggested that the inaccuracy in the IEC armour’s loss factor (λ2) is the main responsible for the conservatism in the IEC cable rating method...

  20. Assessment of sodium conductor distribution cable

    Energy Technology Data Exchange (ETDEWEB)

    None

    1979-06-01

    The study assesses the barriers and incentives for using sodium conductor distribution cable. The assessment considers environmental, safety, energy conservation, electrical performance and economic factors. Along with all of these factors considered in the assessment, the sodium distribution cable system is compared to the present day alternative - an aluminum conductor system. (TFD)

  1. Cable Television: Citizen Participation After the Franchise.

    Science.gov (United States)

    Price, Monroe E.; Botein, Michael

    The Federal Communications Commission (FCC) has incorporated several allowances in its regulations pertaining to cable television. Some of these enable citizen groups and communities to intervene in the cable franchise after the final issuance in order to correct deficiencies in the franchising process and the administration of the franchise.…

  2. Cable Technology: A Challenge for Adult Educators.

    Science.gov (United States)

    Palchinsky, Jo

    The penetration of cable television throughout American communities makes it a potentially significant tool for improving the quality and accessibility of adult education. As cities begin to include in the cable franchise allotment monies for access by community members, adult educators need to become actively involved during the development of a…

  3. The Selling of Cable Television 1972.

    Science.gov (United States)

    National Cable Television Association, Inc., Washington, DC.

    The 1972 Cable Television Marketing Workshop reviewed in depth a wide variety of marketing and public relations techniques as they pertain to cable television. The workshop was attended by representatives of commercial television systems throughout the United States; it was intended to disseminate the sales and marketing experience of those…

  4. An ACLU Guide to Cable Television.

    Science.gov (United States)

    Powledge, Fred

    Proceeding from the hypothesis that cable television (CATV) is one of the most significant developments in modern America, this booklet examines the medium itself and then devotes special attention to the capacity of CATV to serve the First Amendment interest in diversity of expression. The opening section deals with the size and growth of cable,…

  5. Cable Television: The Process of Franchising.

    Science.gov (United States)

    Johnson, Leland L.; Botein, Michael

    In an effort to insure that cable television franchising procedures at the local level are based on a competitive and well-conceived selection process, this report discusses some of the most important steps of the franchising process. Not only does it show how the community should assess its needs and appraise the merits of the cable operator, but…

  6. Cables for nuclear power generating stations, (6)

    International Nuclear Information System (INIS)

    Kakuta, Tsunemi; Asakawa, Naoki; Yamamoto, Tomotaka; Watanabe, Mikio; Shingo, Yoshioki.

    1981-01-01

    New inorganic material insulated flexible triaxial cables have been developed for the purpose of applying around the primary circuit of fast breeder reactor (FBR). These cables were tested at high temperature and high #betta#-ray radiation environment, and they showed good electrical properties. Other noted results were that they showed good fire proof and flame resistant properties. (author)

  7. Cable Television and Educational Access: A Reconsideration.

    Science.gov (United States)

    Thornton, Lee R.; Greene, James C.

    1986-01-01

    Considers the possible impact of recent federal legislation on educational utilization of cable television. Stresses the importance of educators understanding the law's provisions and acting to initiate relationships with cable companies. Reviews public educational or governmental access provisions. Presents strategies for promoting reciprocity…

  8. Intermodal resonance of vibrating suspended cables

    NARCIS (Netherlands)

    Rienstra, S.W.

    2010-01-01

    The weakly nonlinear free vibrations of a single suspended cable, or a coupled system of suspended cables, may be classified as gravity modes (no tension variations to leading order) and elasto-gravity modes (tension and vertical displacement equally important). It was found earlier [12] that the

  9. A new multiconstraint method for determining the optimal cable stresses in cable-stayed bridges.

    Science.gov (United States)

    Asgari, B; Osman, S A; Adnan, A

    2014-01-01

    Cable-stayed bridges are one of the most popular types of long-span bridges. The structural behaviour of cable-stayed bridges is sensitive to the load distribution between the girder, pylons, and cables. The determination of pretensioning cable stresses is critical in the cable-stayed bridge design procedure. By finding the optimum stresses in cables, the load and moment distribution of the bridge can be improved. In recent years, different research works have studied iterative and modern methods to find optimum stresses of cables. However, most of the proposed methods have limitations in optimising the structural performance of cable-stayed bridges. This paper presents a multiconstraint optimisation method to specify the optimum cable forces in cable-stayed bridges. The proposed optimisation method produces less bending moments and stresses in the bridge members and requires shorter simulation time than other proposed methods. The results of comparative study show that the proposed method is more successful in restricting the deck and pylon displacements and providing uniform deck moment distribution than unit load method (ULM). The final design of cable-stayed bridges can be optimised considerably through proposed multiconstraint optimisation method.

  10. Nonlinear Analysis of Cable Vibration of a Multispan Cable-Stayed Bridge under Transverse Excitation

    Directory of Open Access Journals (Sweden)

    Kun Lin

    2014-01-01

    Full Text Available The nonlinear vibrations of cable in a multispan cable-stayed bridge subjected to transverse excitation are investigated. The MECS (multielements cable system model, where multielements per cable stay are used, is built up and used to analyze the model properties of the multispan cable-stayed bridges. Then, a simplified two-degrees-of-freedom (2-DOFs model, where the tower or the deck is reduced to a beam, is proposed to analyze the nonlinear dynamic behaviors of the beam and cable. The results of MECS model analysis show that the main tower in the multispan cable-stayed bridge is prone to the transverse vibration, and the local vibration of cables only has a little impact on the frequency values of the global modes. The results of simplified model analysis show that the energy can be transformed between the modes of the beam and cable when the nature frequencies of them are very close. On the other hand, with the transverse excitation changing, the cable can exhibit richer quasi-periodic or chaotic motions due to the nonlinear terms caused by the coupled mode between the beam and cable.

  11. A New Multiconstraint Method for Determining the Optimal Cable Stresses in Cable-Stayed Bridges

    Directory of Open Access Journals (Sweden)

    B. Asgari

    2014-01-01

    Full Text Available Cable-stayed bridges are one of the most popular types of long-span bridges. The structural behaviour of cable-stayed bridges is sensitive to the load distribution between the girder, pylons, and cables. The determination of pretensioning cable stresses is critical in the cable-stayed bridge design procedure. By finding the optimum stresses in cables, the load and moment distribution of the bridge can be improved. In recent years, different research works have studied iterative and modern methods to find optimum stresses of cables. However, most of the proposed methods have limitations in optimising the structural performance of cable-stayed bridges. This paper presents a multiconstraint optimisation method to specify the optimum cable forces in cable-stayed bridges. The proposed optimisation method produces less bending moments and stresses in the bridge members and requires shorter simulation time than other proposed methods. The results of comparative study show that the proposed method is more successful in restricting the deck and pylon displacements and providing uniform deck moment distribution than unit load method (ULM. The final design of cable-stayed bridges can be optimised considerably through proposed multiconstraint optimisation method.

  12. Nuclear power plant cable materials :

    Energy Technology Data Exchange (ETDEWEB)

    Celina, Mathias C.; Gillen, Kenneth T; Lindgren, Eric Richard

    2013-05-01

    A selective literature review was conducted to assess whether currently available accelerated aging and original qualification data could be used to establish operational margins for the continued use of cable insulation and jacketing materials in nuclear power plant environments. The materials are subject to chemical and physical degradation under extended radiationthermal- oxidative conditions. Of particular interest were the circumstances under which existing aging data could be used to predict whether aged materials should pass loss of coolant accident (LOCA) performance requirements. Original LOCA qualification testing usually involved accelerated aging simulations of the 40-year expected ambient aging conditions followed by a LOCA simulation. The accelerated aging simulations were conducted under rapid accelerated aging conditions that did not account for many of the known limitations in accelerated polymer aging and therefore did not correctly simulate actual aging conditions. These highly accelerated aging conditions resulted in insulation materials with mostly inert aging processes as well as jacket materials where oxidative damage dropped quickly away from the air-exposed outside jacket surface. Therefore, for most LOCA performance predictions, testing appears to have relied upon heterogeneous aging behavior with oxidation often limited to the exterior of the cable cross-section a situation which is not comparable with the nearly homogenous oxidative aging that will occur over decades under low dose rate and low temperature plant conditions. The historical aging conditions are therefore insufficient to determine with reasonable confidence the remaining operational margins for these materials. This does not necessarily imply that the existing 40-year-old materials would fail if LOCA conditions occurred, but rather that unambiguous statements about the current aging state and anticipated LOCA performance cannot be provided based on

  13. Parallel monostrand stay cable bending fatigue

    DEFF Research Database (Denmark)

    Winkler, Jan Pawel

    This dissertation investigates the bending fatigue response of high-strength steel monostrands and multistrand stay cables to cyclic transverse deformations. Increasing bridge stock numbers and a push for longer cable-supported span lengths have led to an increased number of reported incidents...... of damage and replacement of bridge stay cables due to wind and traffic-induced fatigue. The understanding of fatigue mechanisms in most steel structures is well established. However, in the case of cables composed of steel strands, many important aspects related with bending fatigue remain to be clarified...... associated with variable loading, and different testing procedures. As most of the contemporary stay cables are comprised of a number of individual highstrength steel monostrands, the research study started with an extensive experimental work on the fatigue response of a single monostrand to cyclic flexural...

  14. Development of radiation resistant PEEK insulation cable

    International Nuclear Information System (INIS)

    Mio, Keigo; Ogiwara, Norio; Hikichi, Yusuke; Furukori, Hisayoshi; Arai, Hideyuki; Nishizawa, Daiji; Nishidono, Toshiro

    2009-04-01

    Material characterization and development has been carried out for cable insulation suitable for use in the J-PARC 3-GeV RCS radiation environment. In spite of its high cost, PEEK (polyether-ether-ketone) has emerged as the leading candidate satisfying requirements of being non-halogen based, highly incombustible and with radiation resistant at least 10 MGy, along with the usual mechanical characteristics such as good elongation at break, which are needed in a cable insulation. Gamma-ray irradiation tests have been done in order to study radiation resistance of PEEK cable. Further, mechanical, electrical and fire retardant characteristics of a complete cable such as would be used at the J-PARC RCS were investigated. As a result, PEEK cables were shown to be not degraded by radiation up to at least 10 MGy, and thus could be expected to operate stably under the 3-GeV RCS radiation environment. (author)

  15. Behaviour of electrical cables under fire conditions

    International Nuclear Information System (INIS)

    Bertrand, R.; Chaussard, M.; Gonzalez, R.; Lacoue, J.; Mattei, J.M.; Such, J.M.

    2002-01-01

    A Fire Probabilistic Safety Assessment - called the Fire PSA - is being carried out by the French Institute of Radiological Protection and Nuclear Safety (IPSN) to be used in the framework of the safety assessment of operating 900 MWe PWRs. The aim of this study is to evaluate the core damage conditional probability which could result from a fire. A fire can induce unavailability of safety equipment, notably damaging electrical cables introducing a significant risk contributor. The purpose of this paper is to present the electrical cable fire tests carried out by IPSN to identify the failure modes and to determine the cable damage criteria. The impact of each kind of cable failure mode and the methodology used to estimate the conditional probability of a failure mode when cable damage occurred is also discussed. (orig.) [de

  16. Physical degradation assessment of generator station cables

    International Nuclear Information System (INIS)

    Stonkus, D.J.

    1988-01-01

    Preliminary studies of fossil-fired and nuclear generator station cables indicate that the low voltage PVC insulated cables are in relatively good condition. The insulation is flexible and in the case of nuclear cables can withstand a design basis event after nearly 15 years of service. Cables insulated with styrene butadiene rubber have been found embrittled and cables insulated with SBR should be closely inspected in any plant assurance program. Thermal analysis using oxidative induction technique shows promise to indicate cable insulation degradation. Long term reliability assurance and plant life extension studies are being actively pursued at Ontario Hydro. A major study is currently underway to extend the life of the oldest operating fossil-fuel station, the 8-unit, 2400 MW Lakeview TGS in operation since the 1960s. Plant life assurance programs have been initiated at the 2000 MW Lambton TGS in operation since 1969, and for the oldest operating nuclear plant, Pickering NGS A in operation since the early 1970s. As cables are considered one of the critical components in a generator station due to the extreme difficulty and cost of cable replacement, test programs have been initiated to evaluate the physical degradation of the cables and relate the results to electrical diagnostic tests and to chemical changes. The decommissioning of two small nuclear stations, the 20 MW Nuclear Power Demonstration (NPD) and the 200 MW Douglas Point NGS, which were placed in service in 1962 and 1967 respectively, will provide an opportunity to perform destructive electrical and physical evaluation on field aged cables

  17. Wind-induced cable vibrations and countermeasures of cables of PC cable-stayed bridge. PC syachokyo keburu no kaze ni yoru shindo to sono taisaku

    Energy Technology Data Exchange (ETDEWEB)

    Yoneda, M. (Kawada Industries Inc., Tokyo (Japan))

    1994-05-01

    In recent years, long span of cable-stayed bridges is remarkable. The wind-induced cable vibration called as line vibration and wake galloping was given as an important problem not only in the steel cable-stayed bridges but also in the PC cable-stayed bridges. The technical engineers in design of the cable-stayed bridges have many times to confront the problems on the vibration control of cables, it is considered that sufficient understand of the wind-induced vibration and countermeasures for cables of the PC cable-stayed bridges is necessary. Many reports on the countermeasure examples and trend of vibration control centred on cables of the cable-stayed bridges have been published. In this paper, the wind-induced vibration of cables in the cable-stayed bridges was reviewed, the examples of countermeasures of vibration control on cables in the PC cable-stayed bridges was mainly introduced. The remaining tasks and future prospects on vibration control of the PC cable-stayed bridges were described. 14 refs., 13 figs., 4 tabs.

  18. Simulation of the cabling process for Rutherford cables: An advanced finite element model

    Science.gov (United States)

    Cabanes, J.; Garlasche, M.; Bordini, B.; Dallocchio, A.

    2016-12-01

    In all existing large particle accelerators (Tevatron, HERA, RHIC, LHC) the main superconducting magnets are based on Rutherford cables, which are characterized by having: strands fully transposed with respect to the magnetic field, a significant compaction that assures a large engineering critical current density and a geometry that allows efficient winding of the coils. The Nb3Sn magnets developed in the framework of the HL-LHC project for improving the luminosity of the Large Hadron Collider (LHC) are also based on Rutherford cables. Due to the characteristics of Nb3Sn wires, the cabling process has become a crucial step in the magnet manufacturing. During cabling the wires experience large plastic deformations that strongly modify the geometrical dimensions of the sub-elements constituting the superconducting strand. These deformations are particularly severe on the cable edges and can result in a significant reduction of the cable critical current as well as of the Residual Resistivity Ratio (RRR) of the stabilizing copper. In order to understand the main parameters that rule the cabling process and their impact on the cable performance, CERN has developed a 3D Finite Element (FE) model based on the LS-Dyna® software that simulates the whole cabling process. In the paper the model is presented together with a comparison between experimental and numerical results for a copper cable produced at CERN.

  19. Non-cable vehicle guidance

    Energy Technology Data Exchange (ETDEWEB)

    Daugela, G.C.; Willott, A.M.; Chopiuk, R.G.; Thornton, S.E.

    1988-06-01

    The purpose is to determine the most promising driverless mine vehicle guidance systems that are not dependent on buried cables, and to plan their development. The project is presented in two phases: a preliminary study and literature review to determine whether suitable technologies exist to justify further work; and an in-depth assessment and selection of technologies for vehicle guidance. A large number of guidance elements are involved in a completely automated vehicle. The technologies that hold the best potential for development of guidance systems for mine vehicles are ultrasonics, radar, lasers, dead reckoning, and guidance algorithms. The best approach to adaptation of these technologies is on a step by step basis. Guidance modules that are complete in themselves and are designed to be integrated with other modules can provide short term benefits. Two modules are selected for development: the dragline operations monitor and automated machine control for optimized mining (AMCOM). 99 refs., 20 figs., 40 tabs.

  20. Self-healing cable for extreme environments

    Science.gov (United States)

    Huston, Dryver R. (Inventor); Tolmie, Bernard R. (Inventor)

    2009-01-01

    Self-healing cable apparatus and methods disclosed. The self-healing cable has a central core surrounded by an adaptive cover that can extend over the entire length of the self-healing cable or just one or more portions of the self-healing cable. The adaptive cover includes an axially and/or radially compressible-expandable (C/E) foam layer that maintains its properties over a wide range of environmental conditions. A tape layer surrounds the C/E layer and is applied so that it surrounds and axially and/or radially compresses the C/E layer. When the self-healing cable is subjected to a damaging force that causes a breach in the outer jacket and the tape layer, the corresponding localized axially and/or radially compressed portion of the C/E foam layer expands into the breach to form a corresponding localized self-healed region. The self-healing cable is manufacturable with present-day commercial self-healing cable manufacturing tools.

  1. Neutron detector with gamma compensated cable

    International Nuclear Information System (INIS)

    Warren, H.D.

    1975-01-01

    An illustrative embodiment of the invention describes a technique for essentially eliminating the radiation induced background currents that are generated in the cable that connects an ''in-core'' neutron detector to an electrical terminal that is outside of the reactor's radiation field. This undesirable radiation-induced cable current is suppressed through an appropriate selection of conductor and cable sheath materials and sizes that generally satisfy the equation: Z/sub l/sup n/d/sub l/ = Z/sub s/sup m/d/sub s/ where Z is the atomic number of the material; d is a characteristic of the size of the cable component; m and/n have values between 1 and 5 to express the electron emissivity of the cable component from photoelectric and Compton effects; l represents the conductor; and s represents the sheath. Thus, the radiation-generated electrons emitted from the conductor and the oppositely-directed electrons emitted from the inner surface of the cable sheath are mutually cancelled if this equation is satisfied. A typical cable that does meet this criterion at low temperatures has a centrally disposed Zircaloy-2 inner conductor of 0.011 inch diameter, an annular insulation of magnesium oxide powder compacted to 100 percent density, and an Inconel sheath with an outside diameter of 0.062 inch and 0.011 inch wall thickness. (auth)

  2. 46 CFR 111.60-5 - Cable installation.

    Science.gov (United States)

    2010-10-01

    ... REQUIREMENTS Wiring Materials and Methods § 111.60-5 Cable installation. (a) Each cable installation must meet... 46 Shipping 4 2010-10-01 2010-10-01 false Cable installation. 111.60-5 Section 111.60-5 Shipping... incorporated by reference; see 46 CFR 110.10-1), including clause 8. (b) Each cable installation made in...

  3. TMI cable tracer operation and maintenance manual for assembly 417910

    International Nuclear Information System (INIS)

    Sumstine, R.L.

    1983-11-01

    This manual provides technical information and instructions to operate and maintain the cable tracer designed for the Three Mile Island (TMI) Unit 2 Reactor Building. The TMI cable tracer was developed to allow TMI personnel to trace cables in cable trays that may be tested or sectioned for destructive examination

  4. Electrical cabling system associated at a nuclear reactor

    International Nuclear Information System (INIS)

    Dejeux, P.; Desfontaines, G.

    1988-01-01

    This cabling system for an electrical device in a nuclear reactor comprises at least a first cable issued of the device, a second cable comprising a first portion, a second portion and a third portion joining the second by a multiple quick fitting connector capable to connect at least ten second portions at ten other third portions of the second cable [fr

  5. Choice Of Computer Networking Cables And Their Effect On Data ...

    African Journals Online (AJOL)

    Computer networking is the order of the day in this Information and Communication Technology (ICT) age. Although a network can be through a wireless device most local connections are done using cables. There are three main computer-networking cables namely coaxial cable, unshielded twisted pair cable and the optic ...

  6. Non-linear stochastic response of a shallow cable

    DEFF Research Database (Denmark)

    Larsen, Jesper Winther; Nielsen, Søren R.K.

    2004-01-01

    The paper considers the stochastic response of geometrical non-linear shallow cables. Large rain-wind induced cable oscillations with non-linear interactions have been observed in many large cable stayed bridges during the last decades. The response of the cable is investigated for a reduced two...

  7. Wire in the Cable-Driven System of Surgical Robot

    Science.gov (United States)

    Wang, X. F.; Lv, N.; Mu, H. Z.; Xue, L. J.

    2017-07-01

    During the evolution of the surgical robot, cable plays an important role. It translates motion and force precisely from surgeon’s hand to the tool’s tips. In the paper, the vertical wires, the composition of cable, are mathematically modeled from a geometric point of view. The cable structure and tension are analyzed according to the characteristics of wire screw twist. The structural equations of the wires in different positions are derived for both non-bent cable and bent cable, respectively. The bending moment formula of bent cable is also obtained. This will help researchers find suitable cable and design more matched pulley.

  8. Condition Monitoring of Cables Task 3 Report: Condition Monitoring Techniques for Electric Cables

    Energy Technology Data Exchange (ETDEWEB)

    Villaran, M.; Lofaro, R.; na

    2009-11-30

    For more than 20 years the NRC has sponsored research studying electric cable aging degradation, condition monitoring, and environmental qualification testing practices for electric cables used in nuclear power plants. This report summarizes several of the most effective and commonly used condition monitoring techniques available to detect damage and measure the extent of degradation in electric cable insulation. The technical basis for each technique is summarized, along with its application, trendability of test data, ease of performing the technique, advantages and limitations, and the usefulness of the test results to characterize and assess the condition of electric cables.

  9. On the Minimum Cable Tensions for the Cable-Based Parallel Robots

    Directory of Open Access Journals (Sweden)

    Peng Liu

    2014-01-01

    Full Text Available This paper investigates the minimum cable tension distributions in the workspace for cable-based parallel robots to find out more information on the stability. First, the kinematic model of a cable-based parallel robot is derived based on the wrench matrix. Then, a noniterative polynomial-based optimization algorithm with the proper optimal objective function is presented based on the convex optimization theory, in which the minimum cable tension at any pose is determined. Additionally, three performance indices are proposed to show the distributions of the minimum cable tensions in a specified region of the workspace. An important thing is that the three performance indices can be used to evaluate the stability of the cable-based parallel robots. Furthermore, a new workspace, the Specified Minimum Cable Tension Workspace (SMCTW, is introduced, within which all the minimum tensions exceed a specified value, therefore meeting the specified stability requirement. Finally, a camera robot parallel driven by four cables for aerial panoramic photographing is selected to illustrate the distributions of the minimum cable tensions in the workspace and the relationship between the three performance indices and the stability.

  10. Parametrically excited oscillation of stay cable and its control in cable-stayed bridges.

    Science.gov (United States)

    Sun, Bing-nan; Wang, Zhi-gang; Ko, J M; Ni, Y Q

    2003-01-01

    This paper presents a nonlinear dynamic model for simulation and analysis of a kind of parametrically excited vibration of stay cable caused by support motion in cable-stayed bridges. The sag, inclination angle of the stay cable are considered in the model, based on which, the oscillation mechanism and dynamic response characteristics of this kind of vibration are analyzed through numerical calculation. It is noted that parametrically excited oscillation of a stay cable with certain sag, inclination angle and initial static tension force may occur in cable-stayed bridges due to deck vibration under the condition that the natural frequency of a cable approaches to about half of the first model frequency of the bridge deck system. A new vibration control system installed on the cable anchorage is proposed as a possible damping system to suppress the cable parametric oscillation. The numerical calculation results showed that with the use of this damping system, the cable oscillation due to the vibration of the deck and/or towers will be considerably reduced.

  11. Influence of Icing on Bridge Cable Aerodynamics

    DEFF Research Database (Denmark)

    Koss, Holger; Frej Henningsen, Jesper; Olsen, Idar

    2013-01-01

    In recent years the relevance of ice accretion for wind-induced vibration of structural bridge cables has been recognised and became a subject of research in bridge engineering. Full-scale monitoring and observation indicate that light precipitation at moderate low temperatures between zero and -5......°C may lead to large amplitude vibrations of bridge cables under wind action. For the prediction of aerodynamic instability quasi-steady models have been developed estimating the cable response magnitude based on structural properties and aerodynamic force coefficients for drag, lift and torsion...... forces of different bridge cables types. The experiments were conducted in a wind tunnel facility capable amongst others to simulate incloud icing conditions....

  12. 47 CFR 32.2422 - Underground cable.

    Science.gov (United States)

    2010-10-01

    ... FOR TELECOMMUNICATIONS COMPANIES Instructions for Balance Sheet Accounts § 32.2422 Underground cable... manholes and ducts in connection with construction work and the cost of permits and privileges for the...

  13. 47 CFR 32.2423 - Buried cable.

    Science.gov (United States)

    2010-10-01

    ... FOR TELECOMMUNICATIONS COMPANIES Instructions for Balance Sheet Accounts § 32.2423 Buried cable. (a... of cleaning manholes and ducts in connection with construction work and the cost of permits and...

  14. Chinese Market for Fibres and Cables

    Institute of Scientific and Technical Information of China (English)

    2003-01-01

    This article presents a summary of Chinese market of optical fibres and cables based on the development of the optical communications industry. Analysis shows that the market will keep growing for sometime in the future.

  15. Cable system transients theory, modeling and simulation

    CERN Document Server

    Ametani, Akihiro; Nagaoka, Naoto

    2015-01-01

    A systematic and comprehensive introduction to electromagnetic transient in cable systems, written by the internationally renowned pioneer in this field Presents a systematic and comprehensive introduction to electromagnetic transient in cable systems Written by the internationally renowned pioneer in the field Thorough coverage of the state of the art on the topic, presented in a well-organized, logical style, from fundamentals and practical applications A companion website is available

  16. Torsion instability of Dynamic Cables during Installation

    OpenAIRE

    Opgård, Marie Finstad

    2017-01-01

    The oil and gas industry today is a heavily regulated segment, and current standard hasestablished restrictions which yields a very limited weather window for offshore cable installations. This is due to experience with cable failure in harsh weather. A limiting factor in current practice is the design criterion for the minimum allowable radius of curvature in the touchdown point. In addition, current practice does not allow for occurrence of compression in the touch down zone...

  17. Ecology: Electrical Cable Bacteria Save Marine Life

    DEFF Research Database (Denmark)

    Nielsen, Lars Peter

    2016-01-01

    Animals at the bottom of the sea survive oxygen depletion surprisingly often, and a new study identifies cable bacteria in the sediment as the saviors. The bacterial electrical activity creates an iron 'carpet', trapping toxic hydrogen sulfide.......Animals at the bottom of the sea survive oxygen depletion surprisingly often, and a new study identifies cable bacteria in the sediment as the saviors. The bacterial electrical activity creates an iron 'carpet', trapping toxic hydrogen sulfide....

  18. A Cable-Shaped Lithium Sulfur Battery.

    Science.gov (United States)

    Fang, Xin; Weng, Wei; Ren, Jing; Peng, Huisheng

    2016-01-20

    A carbon nanostructured hybrid fiber is developed by integrating mesoporous carbon and graphene oxide into aligned carbon nanotubes. This hybrid fiber is used as a 1D cathode to fabricate a new cable-shaped lithium-sulfur battery. The fiber cathode exhibits a decent specific capacity and lifespan, which makes the cable-shaped lithium-sulfur battery rank far ahead of other fiber-shaped batteries. © 2015 WILEY-VCH Verlag GmbH & Co. KGaA, Weinheim.

  19. MVAC Submarine cable, impedance measurements and analysis

    DEFF Research Database (Denmark)

    Arentsen, Martin Trolle; Expethit, Adrian; Pedersen, Morten Virklund

    2017-01-01

    influence the losses. Secondly, cable parameters such as component impedances, positive-, zero-sequence impedances and losses are measured for varying currents and frequencies. Zero sequence is measured for two setups, one with armour grounded, and with armour open to match CIGREs formula assumption......-sequence impedance is found between the measurements and the CIGRÉ formulas. It is concluded that the formulas are not accurate for the specific cable under test....

  20. Polyethylene as a possible hvdc cable insulant

    Energy Technology Data Exchange (ETDEWEB)

    Hawley, W.G.; Body, R.S.; Mason, J.H.

    1966-10-01

    Many cable authorities have expressed the view that polyethylene would be attractive for this application. The dc conductivity of polyethylene is lower than that of impregnated paper, and varies less with temperature and stress. Polyethylene also has higher thermal conductivity and is resistant to moisture and electrochemical deterioration. Furthermore, processing polyethylene cables should ultimately involve lower capital and manufacturing costs. However, polyethylene has a lower limiting short circuit temperature unless it is cross linked.

  1. The analysis of cable forces based on natural frequency

    Science.gov (United States)

    Suangga, Made; Hidayat, Irpan; Juliastuti; Bontan, Darwin Julius

    2017-12-01

    A cable is a flexible structural member that is effective at resisting tensile forces. Cables are used in a variety of structures that employ their unique characteristics to create efficient design tension members. The condition of the cable forces in the cable supported structure is an important indication of judging whether the structure is in good condition. Several methods have been developed to measure on site cable forces. Vibration technique using correlation between natural frequency and cable forces is a simple method to determine in situ cable forces, however the method need accurate information on the boundary condition, cable mass, and cable length. The natural frequency of the cable is determined using FFT (Fast Fourier Transform) Technique to the acceleration record of the cable. Based on the natural frequency obtained, the cable forces then can be determine by analytical or by finite element program. This research is focus on the vibration techniques to determine the cable forces, to understand the physical parameter effect of the cable and also modelling techniques to the natural frequency and cable forces.

  2. Structural behavior of cable superconductors

    International Nuclear Information System (INIS)

    Becker, H.; Marston, P.

    1983-01-01

    The structural properties of cable superconductor coils, for particle accelerators such as the Tevatron and the CBA (Colliding Beam Accelerator), depend upon direction of loading. For compression perpendicular to the ''flat faces'' of the conductor, the coils exhibit nonlinear, inelastic and time dependent behavior. The same is true for ''inplane'' compression loading perpendicular to the conductor edges. In the lengthwise direction, the coils display tension and compression stress-strain curves typical of structural metals. The loading of primary concern is compression perpendicular to the conductor faces since deformations in that direction can have a major influence on magnetic field quality. However, the coil behavior under that condition is uncertain because of the nonlinear stress strain curve complicated by creep and relaxation at the stress levels induced by preloading and Lorentz forces. Furthermore, the stiffness of the loading fixture appears to influence the data as shown by results from tests run under different conditions at Berkeley, Brookhaven and MIT. The paper displays test data on stress-strain curves for all three loading directions. Results are presented for RT, 77 K and 4 K behavior. Data of various investigators are compared. The applicability of a relatively simple power law between stress and strain is depicted

  3. Environmental assessment of submarine power cables

    Energy Technology Data Exchange (ETDEWEB)

    Isus, Daniel; Martinez, Juan D. [Grupo General Cable Sistemas, S.A., 08560-Manlleu, Barcelona (Spain); Arteche, Amaya; Del Rio, Carmen; Madina, Virginia [Tecnalia Research and Innovation, 20009 San Sebastian (Spain)

    2011-03-15

    Extensive analyses conducted by the European Community revealed that offshore wind energy have relatively benign effects on the marine environment by comparison to other forms of electric power generation [1]. However, the materials employed in offshore wind power farms suffer major changes to be confined to the marine environment at extreme conditions: saline medium, hydrostatic pressure... which can produce an important corrosion effect. This phenomenon can affect on the one hand, to the material from the structural viewpoint and on the other hand, to the marine environment. In this sense, to better understand the environmental impacts of generating electricity from offshore wind energy, this study evaluated the life cycle assessment for some new designs of submarine power cables developed by General Cable. To achieve this goal, three approaches have been carried out: leaching tests, eco-toxicity tests and Life Cycle Assessment (LCA) methodologies. All of them are aimed to obtaining quantitative data for environmental assessment of selected submarine cables. LCA is a method used to assess environmental aspects and potential impacts of a product or activity. LCA does not include financial and social factors, which means that the results of an LCA cannot exclusively form the basis for assessment of a product's sustainability. Leaching tests results allowed to conclude that pH of seawater did not significantly changed by the presence of submarine three-core cables. Although, it was slightly higher in case of broken cable, pH values were nearly equals. Concerning to the heavy metals which could migrate to the aquatic medium, there were significant differences in both scenarios. The leaching of zinc is the major environmental concern during undersea operation of undamaged cables whereas the fully sectioned three-core cable produced the migration of significant quantities of copper and iron apart from the zinc migrated from the galvanized steel. Thus, the tar

  4. Environmental assessment of submarine power cables

    International Nuclear Information System (INIS)

    Isus, Daniel; Martinez, Juan D.; Arteche, Amaya; Del Rio, Carmen; Madina, Virginia

    2011-03-01

    Extensive analyses conducted by the European Community revealed that offshore wind energy have relatively benign effects on the marine environment by comparison to other forms of electric power generation [1]. However, the materials employed in offshore wind power farms suffer major changes to be confined to the marine environment at extreme conditions: saline medium, hydrostatic pressure... which can produce an important corrosion effect. This phenomenon can affect on the one hand, to the material from the structural viewpoint and on the other hand, to the marine environment. In this sense, to better understand the environmental impacts of generating electricity from offshore wind energy, this study evaluated the life cycle assessment for some new designs of submarine power cables developed by General Cable. To achieve this goal, three approaches have been carried out: leaching tests, eco-toxicity tests and Life Cycle Assessment (LCA) methodologies. All of them are aimed to obtaining quantitative data for environmental assessment of selected submarine cables. LCA is a method used to assess environmental aspects and potential impacts of a product or activity. LCA does not include financial and social factors, which means that the results of an LCA cannot exclusively form the basis for assessment of a product's sustainability. Leaching tests results allowed to conclude that pH of seawater did not significantly changed by the presence of submarine three-core cables. Although, it was slightly higher in case of broken cable, pH values were nearly equals. Concerning to the heavy metals which could migrate to the aquatic medium, there were significant differences in both scenarios. The leaching of zinc is the major environmental concern during undersea operation of undamaged cables whereas the fully sectioned three-core cable produced the migration of significant quantities of copper and iron apart from the zinc migrated from the galvanized steel. Thus, the tar

  5. Application study on the first cable-stayed bridge with CFRP cables in China

    Directory of Open Access Journals (Sweden)

    Kuihua Mei

    2015-08-01

    Full Text Available In order to push forward the development of CFRP cable-stayed bridge and accumulate experiences, the study on the application of the first cable-stayed bridge with CFRP cables in China was carried out. The design essentials of main components of the bridge were introduced and its integral performances, including static properties, dynamic properties and seismic response were analyzed using finite element method. A new bond-type anchorage was developed and the processes of fabricating and installing CFRP cables were elaborated. Based on the results of construction simulation, a tension scheme for bridge was propound. During constructing, the stresses and displacement of girder and pylon, as well as the forces and stresses of cables, were tested. The results indicate that all sections of the bridge could meet the requirements of the ultimate bearing capacity and normal service; the performance of the anchorage is good and the stresses in each cable system are similar; the tested values accord well with the calculated values. Further, creep deformation of the resin in anchorages under service load is not obvious. All these results demonstrate that the first application of CFRP cables in the cable-stayed bridge in China is successful.

  6. Ship nuclear power device of cable aging management

    International Nuclear Information System (INIS)

    Wei Hua; Chen Miao; Chen Tao

    2012-01-01

    Cable for marine nuclear power plant continuous delivery of electrical energy. Cable is mostly in the high temperature and strong radiation and harsh working environment, and can not be replaced in the lifetime This should be the cable aging management methods through research, maintenance and repair program to provide a scientific basis. Cable aging management approach for a number of different levels of cable management at different levels, relying on computers and other modern tools, the use of information management database software maintenance of the cable through the science of aging control. Cable Aging Management including the scope of cable aging management, classification management basis and used for different levels of management supervision and implementation of means testing approach. Application of the ship that has the operational management science, both planned maintenance to improve the science, but also improves the efficiency of aging management. This management method can be extended to nuclear power plants of cable aging management. (authors)

  7. Cable condition monitoring in a pressurized water reactor environment

    International Nuclear Information System (INIS)

    Al-Hussaini, T.J.

    1988-01-01

    Oconee Nuclear Station is the first nuclear plant designed, engineered and constructed by Duke Power Company. Even though the accelerated aging method was available to determine the life expectancy of the cable used in the reactor building, no natural aging data was available at that time. In order to be able to verify the condition of the reactor building cable over the life of the plant, an on-going cable monitoring plan was instituted. Various types of cable were selected to be monitored, and they were installed in cable life evaluation circuits in the reactor building. At five year intervals over the life of the plant, cable samples would be removed from these cable life evaluation circuits and tested to determine the effects of the reactor building environment on the integrity of the cable. A review of the cable life evaluation circuits and the results of the evaluation program to date is presented

  8. Characterization of fiber optic cables under large tensile loads

    International Nuclear Information System (INIS)

    Ogle, J.W.; Looney, L.D.; Peterson, R.T.

    1984-01-01

    Fiber optic cables designed for the Nevada Test Site (NTS) have to withstand an unusually harsh environment. Cables have been manufactured under a 6 year old DOE specification that has been slightly modified as the cable requirements are better understood. In order to better understand the cable properties a unique capability has been established at the NTS. Instrumentation has been developed to characterize the transmission properties of 1 km of fiber optic cable placed under a controlled tensile load up to 1500 lbs. The properties measured are cable tension, cable elongation, induced attenuation, attenuation vs. location, fiber strain, bandwidth, and ambient temperature. Preforming these measurements on cables from the two qualified NTS fiber optic cable manufacturers, Siecor and Andrew Corp., led to a new set of specifications

  9. Full-scale fire experiments on vertical horizontal cable trays

    International Nuclear Information System (INIS)

    Mangs, J.; Keski-Rahkonen, O.

    1997-10-01

    Two full-scale fire experiments on PVC cables used in nuclear power plants were carried out, one with cables in vertical position and one with cables in horizontal position. The vertical cable bundle, 3 m high, 300 mm wide and 30 mm thick, was attached to a steel cable ladder. The vertical bundle experiment was carried out in nearly free space with three walls near the cable ladder guiding air flow in order to stabilise flames. The horizontal cable experiment was carried out in a small room with five cable bundles attached to steel cable ladders. Three of the 2 m long cable bundles were located in an array, equally spaced above each other near one long side of the room and two correspondingly near the opposite long side. The vertical cable bundle was ignited with a small propane gas burner beneath the lower edge of the bundle. The horizontal cable bundles were ignited with a small propane burner beneath the lowest bundle in an array of three bundles. Rate of heat release by means of oxygen consumption calorimetry, mass change, CO 2 , CO and smoke production rate and gas, wall and cable surface temperatures were measured as a function of time, as well as time to sprinkler operation and failure of test voltage in cables. Additionally, the minimum rate of heat release needed to ignite the bundle was determined. This paper concentrates on describing and recording the experimental set-up and the data obtained. (orig.)

  10. Applying Diagnostics to Enhance Cable System Reliability (Cable Diagnostic Focused Initiative, Phase II)

    Energy Technology Data Exchange (ETDEWEB)

    Hartlein, Rick [Georgia Tech Research Corporation (GTRC), Atlanta, GA (United States). National Electric Energy Testing, Research and Applications Center (NEETRAC); Hampton, Nigel [Georgia Tech Research Corporation (GTRC), Atlanta, GA (United States). National Electric Energy Testing, Research and Applications Center (NEETRAC); Perkel, Josh [Georgia Tech Research Corporation (GTRC), Atlanta, GA (United States). National Electric Energy Testing, Research and Applications Center (NEETRAC); Hernandez, JC [Univ. de Los Andes, Merida (Venezuela); Elledge, Stacy [Georgia Tech Research Corporation (GTRC), Atlanta, GA (United States). National Electric Energy Testing, Research and Applications Center (NEETRAC); del Valle, Yamille [Georgia Tech Research Corporation (GTRC), Atlanta, GA (United States). National Electric Energy Testing, Research and Applications Center (NEETRAC); Grimaldo, Jose [Georgia Inst. of Technology, Atlanta, GA (United States). School of Electrical and Computer Engineering; Deku, Kodzo [Georgia Inst. of Technology, Atlanta, GA (United States). George W. Woodruff School of Mechanical Engineering

    2016-02-01

    The Cable Diagnostic Focused Initiative (CDFI) played a significant and powerful role in clarifying the concerns and understanding the benefits of performing diagnostic tests on underground power cable systems. This project focused on the medium and high voltage cable systems used in utility transmission and distribution (T&D) systems. While many of the analysis techniques and interpretations are applicable to diagnostics and cable systems outside of T&D, areas such as generating stations (nuclear, coal, wind, etc.) and other industrial environments were not the focus. Many large utilities in North America now deploy diagnostics or have changed their diagnostic testing approach as a result of this project. Previous to the CDFI, different diagnostic technology providers individually promoted their approach as the “the best” or “the only” means of detecting cable system defects.

  11. Young's moduli of cables for high field superconductive dipole magnet

    International Nuclear Information System (INIS)

    Yamada, Shunji; Shintomi, Takakazu.

    1983-01-01

    Superconductive dipole magnets for big accelerators are subjected to enormous electro-magnetic force, when they are operated with high field such as 10 Tesla. They should be constructed by means of superconductive cables, which have high Young's modulus, to obtain good performance. To develop such cables we measured the Young's moduli of cables for practical use of accelerator magnets. They are monolithic and compacted strand cables. We measured also Young's moduli of monolithic copper and brass cables for comparison. The obtained data showed the Young's moduli of 35 and 15 GPa for the monolithic and compacted strand cables, respectively. (author)

  12. CSNS control cable information management system based on web

    International Nuclear Information System (INIS)

    Lu Huihui; Wang Chunhong; Li Luofeng; Liu Zhengtong; Lei Bifeng

    2014-01-01

    This paper presents an approach to data modeling a great number of control devices and cables with complicated relations of CSNS (China Spallation Neutron Source). The CSNS accelerator control cable database was created using MySQL, and the control cable information management system based on Web was further built. During the development of the database, the design idea of IRMIS database was studied. and the actual situation of CSNS accelerator control cables was investigated. The control cable database model fitting the requirements was designed. This system is of great convenience to manage and maintain CSNS control devices and cables in the future. (authors)

  13. High voltage pulsed cable design: a practical example

    Energy Technology Data Exchange (ETDEWEB)

    Kewish, R.W. Jr.; Boicourt, G.P.

    1979-01-01

    The design of optimum high voltage pulse cable is difficult because very little emperical data are available on performance in pulsed applications. This paper follows the design and testing of one high voltage pulse cable, 40/100 trigger cable. The design was based on an unproven theory and the impressive outcome lends support to the theory. The theory is outlined and it is shown that there exists an inductance which gives a cable of minimum size for a given maximum stress. Test results on cable manufactured according to the design are presented and compared with the test results on the cable that 40/100 replaces.

  14. High voltage pulsed cable design: a practical example

    International Nuclear Information System (INIS)

    Kewish, R.W. Jr.; Boicourt, G.P.

    1979-01-01

    The design of optimum high voltage pulse cable is difficult because very little emperical data are available on performance in pulsed applications. This paper follows the design and testing of one high voltage pulse cable, 40/100 trigger cable. The design was based on an unproven theory and the impressive outcome lends support to the theory. The theory is outlined and it is shown that there exists an inductance which gives a cable of minimum size for a given maximum stress. Test results on cable manufactured according to the design are presented and compared with the test results on the cable that 40/100 replaces

  15. NEPO cable system aging management programs

    International Nuclear Information System (INIS)

    Toman, G.

    2002-01-01

    Full text: Cable polymer aging and condition monitoring is being studied in detail under the Nuclear Energy Plant Optimization Program (NEPO) that is co-sponsored by the U.S. Department of Energy and EPRI. Significant advances in modeling of polymer aging and condition monitoring have occurred and continue to be developed. The activities include: Analysis of the linearity of the Arrhenius model to room temperature; Development of a wear-out technique for determining remaining life of cable polymers; Determination of the aging fragility point for composite EPR/CSPE insulation with respect to LOCA function; Development of visual/tactile training aids for cable assessment; Development of a totally new nuclear magnetic resonance condition monitoring technique; Assessment of existing techniques with regard to repeatability, accuracy and ease of use. Through use of highly precise oxygen consumption experiments, the linearity of the Arrhenius model is being evaluated. In these experiments, polymer is placed in vials with a known amount of oxygen and aged at much lower temperatures than is possible with standard accelerated aging techniques. aging results are possible at room temperature. The technique is being applied to commonly used insulation and jacket polymers. The wear-out technique allows highly non-linear aging behavior to be made linear. The wearout point of a polymer is determined through high-rate aging and use of a condition monitoring technique to establish the end point. Then, micro-samples of cable that have been naturally aged are subjected to high rate aging to the same end point. The ratio of the remaining high rate aging period to the total high rate aging time provides a linear indication of the remaining service time. Initial screening of nuclear plant cable systems can use visual/tactile techniques to identify cable that has aged significantly. Training aids have been developed by developing sets of specimens with accelerated aging ranging from none

  16. Configuration of an inelastic flexible anchored cable

    Directory of Open Access Journals (Sweden)

    T. P. Dreyer

    1992-07-01

    Full Text Available Consider an inelastic, perfectly flexible cable with given external forces acting on the total length of the cable. The one end-point is fixed in the origin and the other end-point is anchored at a given point (a;b;c in space. The resulting configuration of the cable in space can be modelled by a system of non-linear differential equations. In this article it is shown that this continuous model of the cable can always be solved in terms of an integral. In the special case of a constant (i.e. independent of the position on the cable external force per unit length the solution is given explicitly in terms of three constants that describe the tension at the origin. These three constants are determined by the boundary values a, b and c at the other end-point, and must be calculated in general by a numerical procedure from the three resulting simultaneous non-linear equations. A few applications of this method are shown.

  17. Development of innovative superconducting DC power cable

    Energy Technology Data Exchange (ETDEWEB)

    Matsushita, Teruo; Kiuchi, Masaru [Dept. of Computer Science and Electronics Kyushu Institute of Technology, Iizuka (Japan)

    2017-09-15

    It is required to reduce the cost of superconducting cable to realize a superconducting DC power network that covers a wide area in order to utilize renewable energy. In this paper a new concept of innovative cable is introduced that can enhance the current-carrying capacity even though the same superconducting tape is used. Such a cable can be realized by designing an optimal winding structure in such a way that the angle between the tape and magnetic field becomes small. This idea was confirmed by preliminary experiments for a single layer model cable made of Bi-2223 tapes and REBCO coated conductors. Experiments of three and four layer cables of practical sizes were also done and it was found that the current-carrying capacity increased as theoretically predicted. If the critical current properties of commercial superconducting tapes are further improved in a parallel magnetic field, the enhancement will become pronounced and this technology will surely contribute to realization of superconducting DC power network.

  18. External heating of electrical cables and auto-ignition investigation

    Energy Technology Data Exchange (ETDEWEB)

    Courty, L., E-mail: leo.courty@univ-orleans.fr [Univ. Orleans, PRISME EA 4229, 63 Avenue de Lattre de Tassigny, 18020 Bourges (France); Garo, J.P. [Institut P’, UPR 3346 CNRS, ENSMA, Univ. Poitiers, 1 Av. Clément Ader, Téléport 2, BP 40109, 86961 Futuroscope Chasseneuil (France)

    2017-01-05

    Highlights: • Electrical cables pyrolysis and flammability have been studied. • Two different experimental setups were used to study cables mass loss and flammability. • A 1-D thermal model for cables mass loss and temperature is proposed. • Spontaneous and piloted ignitions have been investigated. - Abstract: Electric cables are now extensively used for both residential and industrial applications. During more than twenty years, multi-scale approaches have been developed to study fire behavior of such cables that represents a serious challenge. Cables are rather complicated materials because they consist of an insulated part and jacket of polymeric materials. These polymeric materials can have various chemical structures, thicknesses and additives and generally have a char-forming tendency when exposed to heat source. In this work, two test methods are used for the characterization of cable pyrolysis and flammability. The first one permits the investigation of cable pyrolysis. A description of the cable mass loss is obtained, coupling an Arrhenius expression with a 1D thermal model of cables heating. Numerical results are successfully compared with experimental data obtained for two types of cable commonly used in French nuclear power plants. The second one is devoted to ignition investigations (spontaneous or piloted) of these cables. All these basic observations, measurements and modelling efforts are of major interest for a more comprehensive fire resistance evaluation of electric cables.

  19. External heating of electrical cables and auto-ignition investigation

    International Nuclear Information System (INIS)

    Courty, L.; Garo, J.P.

    2017-01-01

    Highlights: • Electrical cables pyrolysis and flammability have been studied. • Two different experimental setups were used to study cables mass loss and flammability. • A 1-D thermal model for cables mass loss and temperature is proposed. • Spontaneous and piloted ignitions have been investigated. - Abstract: Electric cables are now extensively used for both residential and industrial applications. During more than twenty years, multi-scale approaches have been developed to study fire behavior of such cables that represents a serious challenge. Cables are rather complicated materials because they consist of an insulated part and jacket of polymeric materials. These polymeric materials can have various chemical structures, thicknesses and additives and generally have a char-forming tendency when exposed to heat source. In this work, two test methods are used for the characterization of cable pyrolysis and flammability. The first one permits the investigation of cable pyrolysis. A description of the cable mass loss is obtained, coupling an Arrhenius expression with a 1D thermal model of cables heating. Numerical results are successfully compared with experimental data obtained for two types of cable commonly used in French nuclear power plants. The second one is devoted to ignition investigations (spontaneous or piloted) of these cables. All these basic observations, measurements and modelling efforts are of major interest for a more comprehensive fire resistance evaluation of electric cables.

  20. Frequency Dependent Losses in Transmission Cable Conductors

    DEFF Research Database (Denmark)

    Olsen, Rasmus Schmidt; Holbøll, Joachim; Guðmundsdóttir, Unnur Stella

    2011-01-01

    , such as thermal conditions in and around the cable, as well as the heat generated in conductors, screens, armours etc., taking into account proximity and skin effects. The work performed and presented in this paper is concerned with an improved determination of the losses generated in the conductor, by means...... of better calculation of the AC resistance of transmission cable conductors, in particular regarding higher frequencies. In this way, also losses under harmonics can be covered. Furthermore, the model is suitable for modelling of transient attenuation in high voltage cables. The AC resistance is calculated...... based on the current density distribution in different conductor designs by means of the Finite Element Method (FEM). The obtained results and methods are compared to available standards (IEC publication 60287-1-1)....

  1. Distance and Cable Length Measurement System

    Science.gov (United States)

    Hernández, Sergio Elias; Acosta, Leopoldo; Toledo, Jonay

    2009-01-01

    A simple, economic and successful design for distance and cable length detection is presented. The measurement system is based on the continuous repetition of a pulse that endlessly travels along the distance to be detected. There is a pulse repeater at both ends of the distance or cable to be measured. The endless repetition of the pulse generates a frequency that varies almost inversely with the distance to be measured. The resolution and distance or cable length range could be adjusted by varying the repetition time delay introduced at both ends and the measurement time. With this design a distance can be measured with centimeter resolution using electronic system with microsecond resolution, simplifying classical time of flight designs which require electronics with picosecond resolution. This design was also applied to position measurement. PMID:22303169

  2. Vibration isolation of cable tray hangers

    International Nuclear Information System (INIS)

    Pearce, B.K.; Dixon, M.W.; Jackson, J.E.

    1984-01-01

    Analytical and experimental investigations have been performed to partially evaluate the feasibility of using much more flexible support systems than those presently used to support electrical and control cables in nuclear power plants. This approach, which entails introducing a flexible element between the support and the component being supported, could apply to many types of support systems, such as for piping, HVAC or even bridges. However, this paper addresses the specific case of cable tray hangers only. It was found that, for appropriate stiffness and damping characteristics, this concept could be used effectively to isolate cable trays from hanger motion caused by seismic excitation and to significantly reduce hanger loads while maintaining reasonable displacements. This was found to be true for all variations in system parameters investigated. Thus, the flexible hanger concept appears to offer much potential. However, additional study including full-scale testing and more detailed analysis must be completed before the concept can be validated for plant use

  3. Computer-Aided Engineering Of Cabling

    Science.gov (United States)

    Billitti, Joseph W.

    1989-01-01

    Program generates data sheets, drawings, and other information on electrical connections. DFACS program, centered around single data base, has built-in menus providing easy input of, and access to, data for all personnel involved in system, subsystem, and cabling. Enables parallel design of circuit-data sheets and drawings of harnesses. Also recombines raw information to generate automatically various project documents and drawings, including index of circuit-data sheets, list of electrical-interface circuits, lists of assemblies and equipment, cabling trees, and drawings of cabling electrical interfaces and harnesses. Purpose of program to provide engineering community with centralized data base for putting in, and gaining access to, functional definition of system as specified in terms of details of pin connections of end circuits of subsystems and instruments and data on harnessing. Primary objective to provide instantaneous single point of interchange of information, thus avoiding

  4. Radiation techology in cable making industry

    International Nuclear Information System (INIS)

    Kourim, P.; Vokal, A.

    1985-01-01

    Electron accelerators are used in radiation cross-linking of elastomer and thermoplastic layers of cable insulation and sheathing. Another application is cross-linking of insulation bands and moulded products to achieve thermal contractibility. Ionizing radiation is used for curing insulation lacquers on winding leads. In Czechoslovakia, problems of radiation curing of silicone rubber have been studied since 1973. Instrumentation has been installed including accelerators. The feasibility has also been studied of radiation cross-linking of insulation and semiconductor cable cores of hose-type trailing cables. Polyethylene mixes have been designed and prepared which are suitable for radiation cross-linking aimed at increasing thermal resistance above 100 degC. (M.D.)

  5. Power applications for superconducting cables in Denmark

    DEFF Research Database (Denmark)

    Tønnesen, Ole; Østergaard, Jacob; Olsen, S. Krüger

    1999-01-01

    In Denmark a growing concern for environmental protection has lead to wishes that the open country is kept free of overhead lines as far as possible. New lines under 100 kV and existing 60/50 kV lines should be established as underground cables. Superconducting cables represent an interesting...... in cases such as transmission of energy into cities and through areas of special interest. The planned large groups of windmills in Denmark generating up to 2000 MVA or more both on dry land and off-shore will be an obvious case for the application of superconducting AC or DC cables. These opportunities...... can be combined with other new technologies such as HVDC light transmission using isolated gate bipolar transistors (IGBTs). The network needed in a system with a substantial wind power generation has to be very strong in order to handle energy fluctuations. Such a network will be possible...

  6. Electrothermal Coordination in Cable Based Transmission Grids

    DEFF Research Database (Denmark)

    Olsen, Rasmus Schmidt; Holbøll, Joachim; Gudmundsdottir, Unnur Stella

    2013-01-01

    behavior of the components. The dynamic temperature calculations of power cables are suggested to be based on thermoelectric equivalents (TEEs). It is shown that the thermal behavior can be built into widely used load flow software, creating a strong ETC tool. ETC is, through two case scenarios, proven...... to be beneficial for both operator and system planner. It is shown how the thermal behavior can be monitored in real-time during normal dynamic load and during emergencies. In that way, ETC enables cables to be loaded above their normal rating, while maintaining high reliability of the system, which potentially...

  7. The Schmehausen cable net cooling tower

    International Nuclear Information System (INIS)

    Schlaich, J.; Mayr, G.; Weber, P.; Jasch, E.

    1976-01-01

    The prototype of a large cable net shell as a natural-draught cooling tower for the THTR-300 is presented. Results of wind tunnel tests and calculations are given, and the capacity is discussed. Design features of the main components are presented in illustrations and are described with regard to the construction process of the cooling tower. Finally, it is shown that the cable net cooling tower is a suitable construction for large dimensions and caving-in or seismic areas. (orig./HP) [de

  8. Relative stiffness of flat conductor cables

    Science.gov (United States)

    Hankins, J. D.

    1976-01-01

    The measurement of the bending moment required to obtain a given deflection in short lengths of flat conductor cable (FCC) is presented in this report. Experimental data were taken on 10 different samples of FCC and normalized to express all bending moments (relative stiffness factor) in terms of a cable 5.1 cm (2.0 in.) in width. Data are presented in tabular and graphical form for the covenience of designers who may be interested in finding torques exerted on critical components by short lengths of FCC.

  9. Modeling of Pressure Effects in HVDC Cables

    DEFF Research Database (Denmark)

    Szabo, Peter; Hassager, Ole; Strøbech, Esben

    1999-01-01

    A model is developed for the prediction of pressure effects in HVDC mass impregnatedcables as a result of temperature changes.To test the model assumptions, experiments were performed in cable like geometries.It is concluded that the model may predict the formation of gas cavities.......A model is developed for the prediction of pressure effects in HVDC mass impregnatedcables as a result of temperature changes.To test the model assumptions, experiments were performed in cable like geometries.It is concluded that the model may predict the formation of gas cavities....

  10. Analysis of Electrical Coupling Parameters in Superconducting Cables

    CERN Document Server

    Bottura, L; Rosso, C

    2003-01-01

    The analysis of current distribution and redistribution in superconducting cables requires the knowledge of the electric coupling among strands, and in particular the interstrand resistance and inductance values. In practice both parameters can have wide variations in cables commonly used such as Rutherford cables for accelerators or Cable-in-Conduits for fusion and SMES magnets. In this paper we describe a model of a multi-stage twisted cable with arbitrary geometry that can be used to study the range of interstrand resistances and inductances that is associated with variations of geometry. These variations can be due to cabling or compaction effects. To describe the variations from the nominal geometry we have adopted a cable model that resembles to the physical process of cabling and compaction. The inductance calculation part of the model is validated by comparison to semi-analytical results, showing excellent accuracy and execution speed.

  11. Manufacturing experience for the LHC inner triplet quadrupole cables

    CERN Document Server

    Scanlan, R M; Bossert, R; Kerby, J S; Ghosh, A K; Boivin, M; Roy, T

    2002-01-01

    The design for the U.S. LHC Inner Triplet Quadrupole magnet requires a 37 strand (inner layer) and a 46 strand (outer layer) cable. This represents the largest number of strands attempted to date for a production quantity of Rutherford-type cable. The cable parameters were optimized during the production of a series of short prototype magnets produced at FNAL. These optimization studies focused on critical current degradation, dimensional control, coil winding, and interstrand resistance. After the R&D phase was complete, the technology was transferred to NEEW and a new cabling machine was installed to produce these cables. At present, about 60 unit lengths, out of 90 required for the entire production series of magnets, have been completed for each type of cable. The manufacturing experience with these challenging cables will be reported. Finally, the implications for even larger cables, with more strands, will be discussed. (8 refs).

  12. Energy analysis of vehicle-to-cable barrier impacts.

    Science.gov (United States)

    2013-06-01

    An accident reconstruction technique was developed for estimating the energy absorbed during an impact with a cable barrier system as well as the initial impact velocity. The kinetic energy absorbed during a cable barrier system impact is comprised o...

  13. Device to take up slack in monorail cables

    Energy Technology Data Exchange (ETDEWEB)

    Szymanski, J

    1978-08-01

    This paper discusses the necessity to take up the slack of a monorail cable in an HBNPC mine in order to ensure good adhesion between the metal cable and the pulley. A new device has been tested with satisfactory results.

  14. Power plant cable condition monitoring and testing at Georgia Power

    International Nuclear Information System (INIS)

    Champion, T.C.

    1988-01-01

    Georgia Power's Research Center has been heavily involved in the evaluation of electrical insulating materials and cables since its inception more than 17 years ago. For the past ten years that expertise has been applied to cables used in generation plants. This paper discusses the results of two test programs. The first is a quality control inspection on 169 samples of new power generation cables. The second is a material degradation evaluation on four short cable samples removed from a coal fired plant during an equipment upgrade. The new material evaluation was performed to identify the cause of a high failure rate upon initial hi-pot testing of newly installed cables. The material degradation evaluation was performed to evaluate the need for replacement of existing cables during an equipment upgrade. Results of the evaluations have led to development of a detailed proposal for a program to evaluate cable degradation and remaining life for cables used in power generation facilities

  15. Configuration Synthesis for Fully Restrained 7-Cable-Driven Manipulators

    Directory of Open Access Journals (Sweden)

    Xiaoqiang Tang

    2012-10-01

    Full Text Available Cable distribution plays a vital role in Cable Driven Parallel Manipulators (CDPMs regarding tension and workspace quality, especially in fully restrained CDPMs. This paper focuses on three typical configurations of fully restrained CDPMs with 7 cables in order to introduce an approach for configuration synthesis. Firstly, the kinematic models of three types of CDPMs with 7 cables are set up. Then, in order to evaluate workspace quality, two new indices are proposed by using tensions along each cable, which are the All Cable Tension Distribution Index (ACTDI and Global Tension Distribution Index (GTDI. Next, the three types of CDPMs with 7 cables are analysed with the two indices. At the end, according to different performance requirements, the configurations of cable distribution are discussed and selected.

  16. Superscreened co-axial cables for the nuclear power industry

    International Nuclear Information System (INIS)

    1977-05-01

    This specification covers the requirements of superscreened cables. Part 1 covers general requirements and test methods. Part 2 covers data sheets setting out the electrical and mechanical requirements for each type of cable, together with engineering information. (U.K.)

  17. Fault Management of a Cold Dielectric HTS Power Transmission Cable

    International Nuclear Information System (INIS)

    Maguire, J; Allais, A; Yuan, J; Schmidt, F; Hamber, F; Welsh, Tom

    2006-01-01

    High temperature superconductor (HTS) power transmission cables offer significant advantages in power density over conventional copper-based cables. As with conventional cables, HTS cables must be safe and reliable when abnormal conditions, such as local and through faults, occur in the power grid. Due to the unique characteristics of HTS power cables, the fault management of an HTS cable is different from that of a conventional cable. Issues, such as nitrogen bubble formation within lapped dielectric material, need to be addressed. This paper reviews the efforts that have been performed to study the fault conditions of a cold dielectric HTS power cable. As a result of the efforts, a fault management scheme has been developed, which provides both local and through faults system protection. Details of the fault management scheme with examples are presented

  18. Composite carbon fiber cables; Des cables composites en fibres de carbone

    Energy Technology Data Exchange (ETDEWEB)

    Anon.

    2002-10-01

    In order to fulfill the requirements of offshore engineering, Freyssinet, a daughter company of the European Vinci group, has developed a series of high-performance carbon fiber cables. These composite materials have an excellent fatigue behaviour in a huge range of constraints. Moreover, their low weight allows the implementation of very long lengths of cables in marine environment with no loss in capacity. The specific weight of the current part of the cable is reduced by a factor of 4 with respect to an equivalent capacity armature made of steel. These materials were presented in June 2002 at the ultra deep engineering and technologies (UDET) exhibition of Brest (France). (J.S.)

  19. SSC 40 mm cable results and 50 mm design discussions

    International Nuclear Information System (INIS)

    Christopherson, D.; Capone, D.; Hannaford, R.; Remsbottom, R.; Delashmit, R.; Jayakumar, R.J.; Snitchler, G.; Scanlan, R.; Royet, J.

    1991-01-01

    This paper presents a summary of the cable produced for the 1990 40 mm Dipole Program. The cable design parameters for the 50 mm Dipole Program are discussed, as well as portions of the SSC specification draft. Considerations leading to the final cable configuration and the results of preliminary trials are included. The first iteration of a strand mapping program to automate cable strand maps is introduced

  20. SSC 40 mm cable results and 50 mm design discussions

    International Nuclear Information System (INIS)

    Christopherson, D.; Capone, D.; Hannaford, R.; Remsbottom, R.; Jayakumar, R.; Snitchler, G.; Scanlan, R.; Royet, J.

    1990-09-01

    A summary of the cable produced for the 1990 40 mm Dipole Program is presented. The cable design parameters for the 50 mm Dipole Program are discussed, as well as portions of the SSC specification draft. Considerations leading to the final cable configuration and the results of preliminary trials are included. The first iteration of a strand mapping program to automate cable strand maps is introduced. 7 refs., 2 figs., 1 tab

  1. 47 CFR 27.1202 - Cable/BRS cross-ownership.

    Science.gov (United States)

    2010-10-01

    ... portion of the franchise area actually served by the cable operator's cable system and the cable operator... franchise area actually served by the cable operator's cable system the cable operator will use the BRS... that no portion of the GSA of the BRS station is within the portion of the franchise area actually...

  2. Cable Television 1980: Status and Prospect for Higher Education.

    Science.gov (United States)

    Baus, F., Ed.

    Baseline information for the would-be cable television educational programer is provided by two papers, one an overview of the state of the cable television industry, and the other a report on a marketing study conducted to determine consumer attitudes toward cable TV as an educational medium. In "The Promise and Reality of Cable…

  3. 24 CFR 3285.704 - Telephone and cable TV.

    Science.gov (United States)

    2010-04-01

    ... 24 Housing and Urban Development 5 2010-04-01 2010-04-01 false Telephone and cable TV. 3285.704....704 Telephone and cable TV. Refer to § 3285.906 for considerations pertinent to installation of telephone and cable TV. ...

  4. 30 CFR 75.804 - Underground high-voltage cables.

    Science.gov (United States)

    2010-07-01

    ... AND HEALTH MANDATORY SAFETY STANDARDS-UNDERGROUND COAL MINES Underground High-Voltage Distribution § 75.804 Underground high-voltage cables. (a) Underground high-voltage cables used in resistance... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Underground high-voltage cables. 75.804 Section...

  5. 75 FR 61116 - Refunds Under the Cable Statutory License

    Science.gov (United States)

    2010-10-04

    ... Copyright Act, before it was amended to allow a cable system to calculate its royalty fees on a community-by... statutory license set forth in Section 111 are required to pay royalty fees to the Copyright Office... the methodology for a cable operator to calculate royalty fees. Cable operators now pay royalty fees...

  6. 47 CFR 76.111 - Cable sports blackout.

    Science.gov (United States)

    2010-10-01

    ... 47 Telecommunication 4 2010-10-01 2010-10-01 false Cable sports blackout. 76.111 Section 76.111... CABLE TELEVISION SERVICE Network Non-duplication Protection, Syndicated Exclusivity and Sports Blackout § 76.111 Cable sports blackout. (a) No community unit located in whole or in part within the specified...

  7. 46 CFR 111.60-6 - Fiber optic cable.

    Science.gov (United States)

    2010-10-01

    ... 46 Shipping 4 2010-10-01 2010-10-01 false Fiber optic cable. 111.60-6 Section 111.60-6 Shipping COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED) ELECTRICAL ENGINEERING ELECTRIC SYSTEMS-GENERAL REQUIREMENTS Wiring Materials and Methods § 111.60-6 Fiber optic cable. Each fiber optic cable must— (a) Be...

  8. 30 CFR 75.600 - Trailing cables; flame resistance.

    Science.gov (United States)

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Trailing cables; flame resistance. 75.600 Section 75.600 Mineral Resources MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR COAL MINE... cables; flame resistance. [Statutory Provisions] Trailing cables used in coal mines shall meet the...

  9. 30 CFR 75.600-1 - Approved cables; flame resistance.

    Science.gov (United States)

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Approved cables; flame resistance. 75.600-1 Section 75.600-1 Mineral Resources MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR COAL MINE... cables; flame resistance. Cables shall be accepted or approved by MSHA as flame resistant. [57 FR 61223...

  10. Working Paper for the Revision of San Francisco's Cable Franchise.

    Science.gov (United States)

    San Francisco Public Library, CA. Video Task Force.

    Ideas are presented for the revision of San Francisco's cable franchise. The recommendations in the report are based upon national research of library and urban use of cable communications and are designed to help the city's present and future cable franchises to comply with the regulations of the Federal Communications Commission by March 31,…

  11. A simulated-annealing-based approach for wind farm cabling

    NARCIS (Netherlands)

    Lehmann, S.; Rutter, I.; Wagner, D.; Wegner, F.

    2017-01-01

    We study the problem of computing a wind farm cabling with minimum costs allowing different cable types. Our model distinguishes different levels of granularity, where the highest level represents the cabling problem for the whole wind farm. Since even the most restricted of these problems is

  12. Cable Television: Technical Considerations in Franchising Major Market Systems.

    Science.gov (United States)

    Pilnick, Carl

    The 1972 Federal Communications Commission's (FCC) regulations on cable television were intended to assist the penetration of cable television into the large metropolitan regions of the United States. In these major market areas, the task for developing an appropriate franchise is complicated by the changing functional nature of the cable systems…

  13. 46 CFR 111.12-9 - Generator cables.

    Science.gov (United States)

    2010-10-01

    ... 46 Shipping 4 2010-10-01 2010-10-01 false Generator cables. 111.12-9 Section 111.12-9 Shipping... REQUIREMENTS Generator Construction and Circuits § 111.12-9 Generator cables. (a) The current-carrying capacity of generator cables must not be: (1) Less than 115 percent of the continuous generator rating; or (2...

  14. 7 CFR 1755.870 - RUS specification for terminating cables.

    Science.gov (United States)

    2010-01-01

    ... core wrap. (f) Shield. (1) An aluminum shield, plastic coated on one side, shall be applied... section establishes the requirements for terminating cables used to connect incoming outside plant cables... cylindrical core. (iii) The cable structure is completed by the application of a core wrap, a shield, and a...

  15. 30 CFR 75.817 - Cable handling and support systems.

    Science.gov (United States)

    2010-07-01

    ... High-Voltage Longwalls § 75.817 Cable handling and support systems. Longwall mining equipment must be provided with cable-handling and support systems that are constructed, installed and maintained to minimize... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Cable handling and support systems. 75.817...

  16. Environmental Impact of a Submarine Cable: Case Study of the Acoustic Thermometry of Ocean Climate (ATOC)/ Pioneer Seamount Cable

    Science.gov (United States)

    Kogan, I.; Paull, C. K.; Kuhnz, L.; von Thun, S.; Burton, E.; Greene, H. G.; Barry, J. P.

    2003-12-01

    To better understand the potential impacts of the presence of cables on the seabed, a topic of interest for which little data is published or publicly available, a study of the environmental impacts of the ATOC/Pioneer Seamount cable was conducted. The 95 km long, submarine, coaxial cable extends between Pioneer Seamount and the Pillar Point Air Force Station in Half Moon Bay, California. Approximately two thirds of the cable lies within the Monterey Bay National Marine Sanctuary. The cable is permitted to NOAA- Oceanic and Atmospheric Research for transmitting data from a hydrophone array on Pioneer Seamount to shore. The cable was installed unburied on the seafloor in 1995. The cable path crosses the continental shelf, descends to a maximum depth of 1,933 m, and climbs back upslope to 998 m depth near the crest of Pioneer Seamount. A total of 42 hours of video and 152 push cores were collected in 10 stations along cable and control transects using the ROVs Ventana and Tiburon equipped with cable-tracking tools. The condition of the cable, its effect on the seafloor, and distribution of benthic megafauna and infauna were determined. Video data indicated the nature of interaction between the cable and the seafloor. Rocky nearshore areas, where wave energies are greatest, showed the clearest evidence of impact. Here, evidence of abrasion included frayed and unraveling portions of the cable's armor and vertical grooves in the rock apparently cut by the cable. The greatest incision and armor damage occurred on ledges between spans in irregular rock outcrop areas. Unlike the nearshore rocky region, neither the rocks nor the cable appeared damaged along outcrops on Pioneer Seamount. Multiple loops of slack cable added during a 1997 cable repair operation were found lying flat on the seafloor. Several sharp kinks in the cable were seen at 240 m water depths in an area subjected to intense trawling activity. Most of the cable has become buried with time in sediment

  17. Broadband Wireline Provider Service: Cable Modem - DOCSIS 3.0; BBRI_cableDOCSIS12

    Data.gov (United States)

    University of Rhode Island Geospatial Extension Program — This dataset represents the availability of wireline broadband Internet access in Rhode Island via "Cable Modem - DOCSIS 3.0" technology. Broadband availability is...

  18. Broadband Wireline Provider Service: Cable Modem - Other; BBRI_cableOther12

    Data.gov (United States)

    University of Rhode Island Geospatial Extension Program — This dataset represents the availability of wireline broadband Internet access in Rhode Island via "Cable Modem - Other" technology. Broadband availability is...

  19. Aluminium cables in automotive applications : Prestudy of aluminium cable uses in Scania products&Failure analysis and evaluation

    OpenAIRE

    Man, Yu

    2016-01-01

    The increasing demand of light constructed vehicles as well as soaring price of copper metal owing to limited nature resources have been promoting the use of aluminium metal as an alternative conductor of automotive cables. This thesis work is to lay theoretical foundations for further research and development regarding the introduction of new automotive cables i.e. aluminium cables. Current application of automotive aluminium cables in automotive industry as well as failure analysis and eval...

  20. NRC Information Notice No. 92-01: Cable damage caused by inadequate cable installation procedures and controls

    International Nuclear Information System (INIS)

    Rossi, C.E.

    1993-01-01

    In June 1989, the Tennessee Valley Authority (TVA) removed the cables from a conduit in the reactor protection system of the Watts Bar Nuclear Plant, Unit 2, to inspect for damage. TVA selected this conduit in response to an employee's concern that a welding arc that struck the conduit in response to an employee's concern that a welding arc that struck the conduit during construction may have damaged cables in the conduit. When the cables were removed, TVA found significant damage in the insulation of some cables. This damage was not attributed to heat generated by the alleged welding arc. The damage was principally attributed to the pulling stresses exerted during the initial installation of the cables. Some of the cables had insulation removed down to the conductors. To assess the extent of cable damage and determine the scope of its investigation, TVA removed more cables from conduits that constituted the most difficult pulls (worst case) and found varying degrees of damage that it attributed to pulling stresses. To fill a conduit at Watts Bar, personnel used pull cords to pull more cables through the conduits over the top of existing cables. This practice is called ''pull-by.'' This practice can cause damage to the existing cables from the sawing action of the pull cords and the friction of cables as they are pulled over existing cables. TVA instituted programs to assess the adequacy of cable installation at all its nuclear facilities and take appropriate corrective actions. At Watts Bar, TVA replaced cables in conduits which exceeded a calculated threshold value of side wall bearing pressure (SWBP) and performed a high-potential (hi-pot) tests on a number of other cables in conduits with SWBP below the calculated threshold value

  1. Mineral insulated cables for post accident service

    International Nuclear Information System (INIS)

    McMillin, P.L.; Winkler, M.E.

    1986-01-01

    The regulatory requirement to measure the gamma radiation levels during accident conditions inside a reactor containment building is discussed. The development of a mineral-insulated cable and connector system to accurately transmit this measurement is described and a model of the response is developed

  2. AC loss in superconducting tapes and cables

    NARCIS (Netherlands)

    Oomen, M.P.

    2000-01-01

    The present study discusses the AC loss in high-temperature superconductors. Superconducting materials with a relatively high critical temperature were discovered in 1986. They are presently developed for use in large-scale power-engineering devices such as power-transmission cables, transformers

  3. History of cable-stayed bridges

    DEFF Research Database (Denmark)

    Gimsing, Niels Jørgen

    1999-01-01

    The principle of supporting a bridge deck by inclined tension members leading to towers on either side of the span has been known for centuries. However, the real development of cable-stayed bridges did not begin before the 1950s. Since then the free span has been increased from 183 m in the Strö...

  4. Improved cable insulation for superconducting magnets

    International Nuclear Information System (INIS)

    Anerella, M.; Ghosh, A.K.; Kelly, E.; Schmalzle, J.; Willen, E.; Fraivillig, J.; Ochsner, J.; Parish, D.J.

    1993-01-01

    Several years ago, Brookhaven joined with DuPont in a cooperative effort to develop improved cable insulation for SSC superconducting dipole magnets. The effort was supported by the SSC Central Design Group and later the SSC Laboratory. It was undertaken because turn-to-turn and midplane shorts were routinely being experienced during the assembly of magnets with coils made of the existing Kapton/fiberglass (K/FG) system of Kapton film overwrapped with epoxy-impregnated fiberglass tape. Dissection of failed magnets showed that insulation disruption and punch-through was occurring near the inner edges of turns close to the magnet midplane. Coil pressures of greater than 17 kpsi were sufficient to disrupt the insulation at local high spots where the cable had been strongly compacted in the keystoning operation during cable manufacture. In the joint development program, numerous combinations of polyimide films manufactured by DuPont with varying configurations and properties (including thickness) were subjected to tests at Brookhaven. Early tests were bench trials using wrapped cable samples. The most promising candidates were used in coils and many of these promising candidates were used in coils and many of these assembled and tested as magnets in both the SSC and RHIC magnet programs currently underway. The Kapton CI (CI) system that has been adopted represents a suitable compromise of numerous competing factors. It exhibits improved performance in the critical parameter of compressive punch-through resistance as well as other advantages over the K/FG system

  5. Cable Television for Librarians. Ordinances and Franchises

    Science.gov (United States)

    Drexel Library Quarterly, 1973

    1973-01-01

    A short lecture is presented on how librarians can incorporate their programing into that of existing and future cable television stations. The lecture was followed by a question/answer period. (Other conference materials are LI 503071-503076 and 503078 through 503084.) (SM)

  6. Improved cable insulation for superconducting magnets

    International Nuclear Information System (INIS)

    Anerella, M.; Ghosh, A.K.; Kelly, E.; Schmalzle, J.; Willen, E.; Fraivillig, J.; Ochsner, J.; Parish, D.J.

    1993-01-01

    Several years ago, Brookhaven joined with DuPont in a cooperative effort to develop improved cable insulation for SSC superconducting dipole magnets. The effort was supported by the SSC Central Design Group and later the SSC Laboratory. It was undertaken because turn-to-turn and midplane shorts were routinely being experienced during the assembly of magnets with coils made of the existing Kapton/Fiberglass (K/FG) system of Kapton film overwrapped with epoxy-impregnated fiberglass tape. Dissection of failed magnets showed that insulation disruption and punch-through was occurring near the inner edges of turns close to the magnet midplane. Coil pressures of greater than 17 kpsi were sufficient to disrupt the insulation at local high spots where wires in neighboring turns crossed one another and where the cable had been strongly compacted in the keystoning operation during cable manufacture. In the joint development program, numerous combinations of polyimide films manufactured by DuPont with varying configurations and properties (including thickness) were subjected to tests at Brookhaven. Early tests were bench trials using wrapped cable samples. The most promising candidates were used in coils and many of these assembled and tested as magnets in both the SSC and RHIC magnet programs currently underway. The Kapton CI (CI) system that has been adopted represents a suitable compromise of numerous competing factors. It exhibits improved performance in the critical parameter of compressive punch-through resistance as well as other advantages over the K/FG system

  7. Optimization of bridge cables with concave fillets

    DEFF Research Database (Denmark)

    Burlina, Celeste; Georgakis, Christos T.; Larsen, Søren V.

    In this paper the aerodynamic performance of new cable surfaces with concave fillet are examined and compared to plain, dimpled and helically filleted surfaces. To this end, an extensive wind-tunnel campaign was undertaken. Preliminary flow visualizations tests and static tests were performed to ...

  8. Cinema Futures: Cain, Abel or Cable?

    NARCIS (Netherlands)

    Elsaesser, Thomas; Hoffmann, Kay

    1998-01-01

    In the late 1960s, the cinema was pronounced dead. Television, like a Biblical Cain had slain his brother Abel. Some thirty years later, a remarkable reversal: rarely has the cinema been more popular. And yet, rarely has the cinema's future seemed more uncertain. Cinema Futures: Cain, Abel or Cable?

  9. Wide-band cable systems at SLAC

    International Nuclear Information System (INIS)

    Struven, W.

    1983-01-01

    SLAC's first cable TV system was installed in 1979 to remotely monitor a narrow pulse which was generated in the west end of the klystron gallery. When Stanford Linear Collider (SLC) experimental work started at the west end of the accelerator, the original 1979 cable was upgraded to a bidirectional system so that 2 MBaud point-to-point data and several video and 9600 baud channels could be transmitted. The implementation of the SLC requires a complete upgrading of the accelerator control system. The system is based on a distributed processing configuration using a PDP11/780 VAX in the Main Control Center (MCC) and Intel single-board computers in a multibus configuration along the accelerator. The high-speed data linking is supplied by a 1 MBaud Time Division Multiple Access (TDMA) Network. The same cable is used to provide video, low-speed data, voice and high-speed point-to-point data services. The transmission system will utilize a wideband midsplit cable facility to collect and distribute signals to all parts of the network

  10. Cable Design for FAIR SIS 300

    NARCIS (Netherlands)

    Kaugerts, J.; Moritz, G.; Wilson, M.N.; Ghosh, A.K.; den Ouden, A.

    GSI, Darmstadt is preparing to build FAIR (Facility for Antiproton and Ion Research) which include SIS 300, a 300T - m fast-ramping heavy ion synchrotron. Dipoles for this ring will be 2.9 m long, producing 6 T over a 100 mm coil aperture and ramped at 1 T/s. The cable for these dipoles must have

  11. Microminiature coaxial cable and methods manufacture

    Science.gov (United States)

    Bongianni, W.L.

    1986-04-08

    A coaxial cable is provided having a ribbon inner conductor surrounded by a dielectric and a circumferential conductor. The coaxial cable may be microminiature comprising a very thin ribbon strip conductor from between 5 to 15 [mu]m thick and from 150 to 200 [mu]m wide, having a surrounding foamed dielectric or parylene applied thereon by a vapor plasma process and an outer conductor of an adhering high conductivity metal vacuum deposited on the dielectric. Alternately the foam dielectric embodiment may have a contiguous parylene coating applied adjacent the inner conductor or the outer conductor or both. Also, the cable may be fabricated by forming a thin ribbon of strip conductive material into an inner conductor, applying thereabout a dielectric by spraying on a solution of polystyrene and polyethylene and then vacuum depositing and adhering high conductivity metal about the dielectric. The cable strength may be increased by adding glass microfilament fibers or glass microballoons to the solution of polystyrene and polyethylene. Further, the outer conductive layer may be applied by electroless deposition in an aqueous solution rather than by vacuum deposition. A thin coating of parylene is preferably applied to the outer conductor to prevent its oxidation and inhibit mechanical abrasion. 2 figs.

  12. Galloping instability to chaos of cables

    CERN Document Server

    Luo, Albert C J

    2017-01-01

    This book provides students and researchers with a systematic solution for fluid-induced structural vibrations, galloping instability and the chaos of cables. They will also gain a better understanding of stable and unstable periodic motions and chaos in fluid-induced structural vibrations. Further, the results presented here will help engineers effectively design and analyze fluid-induced vibrations.

  13. Bulk Electrical Cable Non-Destructive Examination Methods for Nuclear Power Plant Cable Aging Management Programs

    Energy Technology Data Exchange (ETDEWEB)

    Glass, Samuel W. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Jones, Anthony M. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Fifield, Leonard S. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Hartman, Trenton S. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States)

    2016-09-01

    This Pacific Northwest National Laboratory milestone report describes progress to date on the investigation of nondestructive test methods focusing particularly on bulk electrical test methods that provide key indicators of cable aging and damage. The work includes a review of relevant literature as well as hands-on experimental verification of inspection capabilities. As nuclear power plants consider applying for second, or subsequent, license renewal to extend their operating period from 60 years to 80 years, it is important to understand how the materials installed in plant systems and components will age during that time and develop aging management programs to assure continued safe operation under normal and design basis events (DBE). Normal component and system tests typically confirm the cables can perform their normal operational function. The focus of the cable test program, however, is directed toward the more demanding challenge of assuring the cable function under accident or DBE. The industry has adopted 50% elongation at break (EAB) relative to the un-aged cable condition as the acceptability standard. All tests are benchmarked against the cable EAB test. EAB, however, is a destructive test so the test programs must apply an array of other nondestructive examination (NDE) tests to assure or infer the overall set of cable’s system integrity. Assessment of cable integrity is further complicated in many cases by vendor’s use of dissimilar material for jacket and insulation. Frequently the jacket will degrade more rapidly than the underlying insulation. Although this can serve as an early alert to cable damage, direct test of the cable insulation without violating the protective jacket becomes problematic. This report addresses the range of bulk electrical NDE cable tests that are or could be practically implemented in a field-test situation with a particular focus on frequency domain reflectometry (FDR). The FDR test method offers numerous advantages

  14. A unique cabling designed to produce Rutherford-type superconducting cable for the SSC project

    International Nuclear Information System (INIS)

    Grisel, J.; Royet, J.M.; Scanlan, R.M.; Armer, R.

    1988-08-01

    Up to 25,000 Km of keystoned flat cable must be produced for the SSC project. Starting from a specification developed by Lawrence Berkeley Laboratory (LBL), a special cabling machine has been designed by Dour Metal. It has been designed to be able to run at a speed corresponding to a maximum production rate of 10 m/min. This cabling machine is the key part of the production line which consists of a precision Turkshead equipped with a variable power drive, a caterpillar, a dimensional control bench, a data acquisition system, and a take-up unit. The main features of the cabling unit to be described are a design with nearly equal path length between spool and assembling point for all the wires, and the possibility to run the machine with several over- or under-twisting ratios between cable and wires. These requirements led Dour Metal to the choice of an unconventional mechanical concept for a cabling machine. 4 refs., 2 figs

  15. Shape accuracy optimization for cable-rib tension deployable antenna structure with tensioned cables

    Science.gov (United States)

    Liu, Ruiwei; Guo, Hongwei; Liu, Rongqiang; Wang, Hongxiang; Tang, Dewei; Song, Xiaoke

    2017-11-01

    Shape accuracy is of substantial importance in deployable structures as the demand for large-scale deployable structures in various fields, especially in aerospace engineering, increases. The main purpose of this paper is to present a shape accuracy optimization method to find the optimal pretensions for the desired shape of cable-rib tension deployable antenna structure with tensioned cables. First, an analysis model of the deployable structure is established by using finite element method. In this model, geometrical nonlinearity is considered for the cable element and beam element. Flexible deformations of the deployable structure under the action of cable network and tensioned cables are subsequently analyzed separately. Moreover, the influence of pretension of tensioned cables on natural frequencies is studied. Based on the results, a genetic algorithm is used to find a set of reasonable pretension and thus minimize structural deformation under the first natural frequency constraint. Finally, numerical simulations are presented to analyze the deployable structure under two kinds of constraints. Results show that the shape accuracy and natural frequencies of deployable structure can be effectively improved by pretension optimization.

  16. 2nd International Conference on Cable-Driven Parallel Robots

    CERN Document Server

    Bruckmann, Tobias

    2015-01-01

    This volume presents the outcome of the second forum to cable-driven parallel robots, bringing the cable robot community together. It shows the new ideas of the active researchers developing cable-driven robots. The book presents the state of the art, including both summarizing contributions as well as latest research and future options. The book cover all topics which are essential for cable-driven robots: Classification Kinematics, Workspace and Singularity Analysis Statics and Dynamics Cable Modeling Control and Calibration Design Methodology Hardware Development Experimental Evaluation Prototypes, Application Reports and new Application concepts

  17. A preliminary bending fatigue spectrum for steel monostrand cables

    DEFF Research Database (Denmark)

    Winkler, Jan; Fischer, Gregor; Georgakis, Christos T.

    2011-01-01

    This paper presents the results of the experimental study on the bending fatigue resistance of high-strength steel monostrand cables. From the conducted fatigue tests in the high-stress, low-cycle region, a preliminary bending fatigue spectrum is derived for the estimation of monostrand cable...... service life expectancy. The presented preliminary bending fatigue spectrum of high-strength monostrands is currently unavailable in the published literature. The presented results provide relevant information on the bending mechanism and fatigue characteristics of monostrand steel cables in tension...... and flexure and show that localized cable bending has a pronounced influence on the fatigue resistance of cables under dynamic excitations....

  18. Energy losses of superconducting power transmission cables in the grid

    DEFF Research Database (Denmark)

    Østergaard, Jacob; Okholm, Jan; Lomholt, Karin

    2001-01-01

    One of the obvious motives for development of superconducting power transmission cables is reduction of transmission losses. Loss components in superconducting cables as well as in conventional cables have been examined. These losses are used for calculating the total energy losses of conventional...... as well as superconducting cables when they are placed in the electric power transmission network. It is concluded that high load connections are necessary to obtain energy saving by the use of HTSC cables. For selected high load connections, an energy saving of 40% is expected. It is shown...

  19. Superconducting power cables in Denmark - a case study

    DEFF Research Database (Denmark)

    Østergaard, Jacob

    1997-01-01

    A case study of a 450 MVA, 132 kV high temperature superconducting (HTS) power transmission cable has been carried out. In the study, a superconducting cable system is compared to a conventional cable system which is under construction for an actual transmission line in the Danish grid. The study...... that HTS cables will be less expensive for high power ratings, have lower losses for lines with a high load, and have a reduced reactive power production. The use of superconducting cables in Denmark accommodate plans by the Danish utility to make a substantial conversion of overhead lines to underground...

  20. Comparison of advanced high power underground cable designs

    International Nuclear Information System (INIS)

    Erb, J.; Heinz, W.; Hofmann, A.; Koefler, H.J.; Komarek, P.; Maurer, W.; Nahar, A.

    1975-09-01

    In this paper, advanced high power underground cable designs are compared in the light of available literature, of reports and information supplied by participating industries (AEG, BICC, CGE, Pirelli, Siemens), spontaneous contributions by EdF, France, BBC and Felten and Guilleaume Kabelwerke A.G., Germany, and Hitachi, Furukawa, Fujikura and Sumitomo, Japan, and earlier studies carried out at German public research centres. The study covers cables with forced cooling by oil or water, SF 6 -cables, polyethylene cables, cryoresistive and superconducting cables. (orig.) [de

  1. Behaviour at thermal ageing of power cable components through penetrations

    International Nuclear Information System (INIS)

    Puiu, D.; Gyongyosi, T.; Dinu, E.

    2009-01-01

    The materials for electric insulation and exterior jackets of the power cables are formulated organic compounds. The environmental service conditions will induce chemical and/or physical processes at molecular level of the material; these processes are the ageing mechanisms. The power cables passing through penetrations lead to an increase of the rate of thermal ageing mechanisms, resulting in irreversible degradation of mechanical and electric properties of the organic compounds and of the functional properties of the cable. The paper presents the results of the laboratory tests when the real environmental service conditions for penetration are simulated, the comparison with the results of the thermal computation of the power cables heating and the evaluation of the influence of temperature increase of the power cable components on the cable lifetime. For the particular case of a power cable with PVC insulation, we estimated a lifetime decrease about seven years as referred to lifetime of about 30 years for operation in air. (authors)

  2. submitter On Roebel Cable Geometry for Accelerator Magnet

    CERN Document Server

    Fleiter, J; Ballarino, A

    2016-01-01

    Roebel-type cables made of a ReBCO conductor are potential candidates for high-field accelerator magnets. The necessity to promote a large effective transverse section in a Roebel cable to avoid local overstress leading to degradation in electrical performance has been recently addressed. In this paper, a new geometry of meander tapes for a Roebel cable that enhances both the transverse effective section and the current margin at crossing segments is discussed. As Roebel cables are bent at the coil ends, the modulation of the bending radius of strands along the cable pitch leads to a shift of the strands with respect to each other. The shift magnitude is analytically investigated in this paper as a function of both cable features and coil geometry. Finally, the minimum transposition pitch of Roebel cables is determined on the basis of coil characteristics.

  3. Defying c-Abl signaling circuits through small allosteric compounds

    Directory of Open Access Journals (Sweden)

    Stefania eGonfloni

    2014-11-01

    Full Text Available Many extracellular and intracellular signals promote the c-Abl tyrosine kinase activity. c-Abl in turn triggers a multitude of changes either in protein phosphorylation or in gene expression in the cell. Yet, c-Abl takes part in diverse signaling routes because of several domains linked to its catalytic core. Complex conformational changes turn on and off its kinase activity. These changes affect surface features of the c-Abl kinase and likely its capability to bind actin and/or DNA. Two specific inhibitors (ATP-competitive or allosteric compounds regulate the c-Abl kinase through different mechanisms. NMR studies show that a c-Abl fragment (SH3-SH2-linker-SH1 adopts different conformational states upon binding to each inhibitor. This supports an unconventional use for allosteric compounds to unraveling physiological c-Abl signaling circuits.

  4. Optimal Cable Tension Distribution of the High-Speed Redundant Driven Camera Robots Considering Cable Sag and Inertia Effects

    Directory of Open Access Journals (Sweden)

    Yu Su

    2014-03-01

    Full Text Available Camera robots are high-speed redundantly cable-driven parallel manipulators that realize the aerial panoramic photographing. When long-span cables and high maneuverability are involved, the effects of cable sags and inertias on the dynamics must be carefully dealt with. This paper is devoted to the optimal cable tension distribution (OCTD for short of the camera robots. Firstly, each fast varying-length cable is discretized into some nodes for computing the cable inertias. Secondly, the dynamic equation integrated with the cable inertias is set up regarding the large-span cables as catenaries. Thirdly, an iterative optimization algorithm is introduced for the cable tension distribution by using the dynamic equation and sag-to-span ratios as constraint conditions. Finally, numerical examples are presented to demonstrate the effects of cable sags and inertias on determining tensions. The results justify the convergence and effectiveness of the algorithm. In addition, the results show that it is necessary to take the cable sags and inertias into consideration for the large-span manipulators.

  5. Long-term test of the 22.9kV HTS power cable system in LS Cable Ltd

    International Nuclear Information System (INIS)

    Jang, Hyun Man; Lee, Chang Young; Kim, Choon Dong; Kim, Do Hyung; Park, In Son; Ji, Bong Ki; Kim, Dong Wook; Cho, Jeonwook

    2006-01-01

    Since 2001, LS cable Ltd. has been developing the design, manufacturing and evaluation technologies for high temperature superconducting (HTS) power cable system as a member of DAPAS (Dream for Advanced Power system by Applied Superconductivity technology) program in Korea. The 30 m HTS cable system that is rated at 22.9 kV and 1.2 kA giving a rated capacity of 50 MVA had been developed and tested. The cable was designed as a cold dielectric type employing Bi-2223 HTS tapes and polypropylene (PP) laminated paper as the conductor and electrical insulation, respectively. The cable is cooled with sub-cooled liquid nitrogen at temperature from 75 to 77 K. The manufacturing and the installation of the cable system were completed in 2004. Long-term performance test of the cable system has been conducted for six months to verify its electric and mechanical properties in 2005

  6. Dynamical Analysis and Simulation Validation of Incompletely Restrained Cable-Suspended Swinging System Driven by Two Cables

    Directory of Open Access Journals (Sweden)

    Naige Wang

    2016-01-01

    Full Text Available The flexibility of the suspension multicables and driven length difference between two cables cause the translation and rotation of the platform in the incompletely restrained cable-suspended system driven by two cables (IRCSWs2, which are theoretically investigated in this paper. The suspension cables are spatially discretized using the assumed modes method (AMM and the equations of motion are derived from Lagrange equations of the first kind. Considering all the geometric matching conditions are approximately linear with external actuator, the differential algebraic equations (DAEs are transformed to a system of ordinary differential equations (ODEs. Using linear boundary conditions of the suspension cable, the current method can obtain not only the accurate longitudinal displacements of cable and posture of the platform, but also the tension between the platform and cables, and the current method is verified by ADAMS simulation.

  7. Development of polymer packaging for power cable

    Directory of Open Access Journals (Sweden)

    S. Sremac

    2014-10-01

    Full Text Available This paper discusses the issues of product design and the procedure of developing polymer packaging as one of the most important engineering tasks. For the purpose of packing power cables a polymer packaging has been designed in the form of drum. Packaging and many other consumer products are largely produced using polymeric materials due to many positive features. High Density Polyethylene is the type of polyethylene proposed for packaging purposes due to its low degree of branching and strong intermolecular forces. Transport and storage processes were automated based on the radio-frequency identification technology. The proposed system is flexible in terms of its possibility of accepting and processing different types of cables and other products.

  8. Loop Group Parakeet Virtual Cable Concept Demonstrator

    Science.gov (United States)

    Dowsett, T.; McNeill, T. C.; Reynolds, A. B.; Blair, W. D.

    2002-07-01

    The Parakeet Virtual Cable (PVC) concept demonstrator uses the Ethernet Local Area Network (LAN) laid for the Battle Command Support System (BCSS) to connect the Parakeet DVT(DA) (voice terminal) to the Parakeet multiplexer. This currently requires pairs of PVC interface units to be installed for each DVT(DA) . To reduce the cost of a PVC installation, the concept of a Loop Group Parakeet Virtual Cable (LGPVC) was proposed. This device was designed to replace the up to 30 PVC boxes and the multiplexer at the multiplexer side of a PVC installation. While the demonstrator is largely complete, testing has revealed an incomplete understanding of how to emulate the proprietary handshaking occurring between the circuit switch and the multiplexer. The LGPVC concept cannot yet be demonstrated.

  9. Optical fiber cable chemical stripping fixture

    Science.gov (United States)

    Kolasinski, John R. (Inventor); Coleman, Alexander M. (Inventor)

    1995-01-01

    An elongated fixture handle member is connected to a fixture body member with both members having interconnecting longitudinal central axial bores for the passage of an optical cable therethrough. The axial bore of the fixture body member, however, terminates in a shoulder stop for the outer end of a jacket of the optical cable covering both an optical fiber and a coating therefor, with an axial bore of reduced diameter continuing from the shoulder stop forward for a predetermined desired length to the outer end of the fixture body member. A subsequent insertion of the fixture body member including the above optical fiber elements into a chemical stripping solution results in a softening of the exposed external coating thereat which permits easy removal thereof from the optical fiber while leaving a desired length coated fiber intact within the fixture body member.

  10. Cabling in the Skyrme–Faddeev model

    International Nuclear Information System (INIS)

    Jennings, Paul

    2015-01-01

    The Skyrme–Faddeev model is a three-dimensional nonlinear field theory that has topological soliton solutions, called hopfions, which are novel string-like solutions taking the form of knots and links. Solutions found thus far take the form of torus knots and links of these, however torus knots form only a small family of known knots. It is an open question whether any non-torus knot hopfions exist. In this paper we present a construction of knotted fields with the form of cable knots to which an energy minimization scheme can be applied. We find the first known hopfions which do not have the form of torus knots, but instead take the form of cable and hyperbolic knots. (paper)

  11. Cryogenic cooling system for HTS cable

    Energy Technology Data Exchange (ETDEWEB)

    Yoshida, Shigeru [Taiyo Nippon Sanso, Tsukuba (Japan)

    2017-06-15

    Recently, Research and development activity of HTS (High Temperature Superconducting) power application is very progressive worldwide. Especially, HTS cable system and HTSFCL (HTS Fault current limiter) system are proceeding to practical stages. In such system and equipment, cryogenic cooling system, which makes HTS equipment cooled lower than critical temperature, is one of crucial components. In this article, cryogenic cooling system for HTS application, mainly cable, is reviewed. Cryogenic cooling system can be categorized into conduction cooling system and immersion cooling system. In practical HTS power application area, immersion cooling system with sub-cooled liquid nitrogen is preferred. The immersion cooling system is besides grouped into open cycle system and closed cycle system. Turbo-Brayton refrigerator is a key component for closed cycle system. Those two cooling systems are focused in this article. And, each design and component of the cooling system is explained.

  12. Organic dielectrics in high voltage cables

    Energy Technology Data Exchange (ETDEWEB)

    Vermeer, J

    1962-03-01

    It appears that the limit has been reached in the applicability of oil-impregnated paper as the dielectric for ehv cables, as with rising voltages the prevention of conductor losses becomes increasingly difficult, while the dielectric losses of the insulation, increasing as the square of the voltage, contribute to a greater extent to the temperature rise of the conductor. The power transmitting capacity of ehv cables reaches a maximum at 500 to 600 kV for these reasons. Apart from artificial cooling, a substantial improvement can be obtained only with the use of insulating materials with much lower dielectric losses; these can moreover be applied with a smaller wall thickness, but this means higher field strengths. Synthetic polymer materials meet these requirements but can be used successfully only in the form of lapped film tapes impregnated with suitable liquids. The electrical properties of these heterogeneous dielectrics, in particular, their impulse breakdown strengths are studied in detail.

  13. Southwire's High Temperature Superconducting Cable Development - Summary Report

    International Nuclear Information System (INIS)

    Sinha, Uday; Lindsay, David

    2005-01-01

    Final technical report on Southwire HTS cable development program. Southwire started an HTS cable development program beginning early 1995 with a Co-operative Research and Development Agreement (CRADA) with Oak Ridge National Laboratory. The development task was to study the properties of HTS tapes, and construct hand wound 1-m cables to study the winding characteristics of the tapes. Within a short time several 1-m long cables were constructed and tested. A goal was established to construct a 30-m long, three single-phase cables suitable to carry 1250-Aac at 12.4 kV and power Southwire's two main manufacturing plants, machinery division, and part of the corporate headquarters building. Southwire chose to construct a cold dielectric (CD) design cable that has the advantage of shielding magnetic fields and suitable for carrying larger amounts of current for future applications. The CD design however, required a dielectric material that would be suitable at liquid nitrogen temperature. After considerable testing, a polymer based tape called ''Cryoflex'' was developed by Southwire for use as a cold dielectric. Southwire developed a HTS cable making facility for the winding of HTS and dielectric tapes. At the same time Southwire and ORNL developed at Oak Ridge a dielectric testing laboratory and a 5-m cable test bed. The HTS cable requires special terminations that connect cables at 77 K and high pressures (design pressure of 150 psi) with outside power at ambient temperature and pressure. Two types of terminations called Vacuum (T-1) and Pressure termination (T-2) were developed. The vacuum termination needed very high vacuum (10 -5 bar) and cold ceramic bushings that were expensive and unreliable. The modified pressure termination eliminated vacuum, utilize industrial bushings, reduced cost, and increased reliability. Two 5-m cables were designed and constructed at Southwire with the same rating as needed for the 30-m cables. The 5-m cables were tested successfully

  14. Construction control of cable-stayed bridges

    OpenAIRE

    Lozano Galant, José Antonio

    2013-01-01

    Premi extraordinari doctorat curs 2012-2013, àmbit d’Enginyeria Civil This work presents a study of the simulation of cable-stayed bridges built on temporary supports focused on their response during construction and in service. To simulate the behavior during construction, a set of four different algorithms has been developed to deal with initial design (Backward Algorithm), updating the tensioning process when deviations on site are measured (Forward Algorithm), optimization processes (D...

  15. Electromagnetic compatibility design and cabling system rules

    International Nuclear Information System (INIS)

    Raimbourg, J.

    2009-01-01

    This report is devoted to establish EMC (Electromagnetic Compatibility) design and cabling system rules. It is intended for hardware designers in charge of designing electronic maps or integrating existing materials into a comprehensive system. It is a practical guide. The rules described in this document do not require enhanced knowledge of advanced mathematical or physical concepts. The key point is to understand phenomena with a pragmatic approach to highlight the design and protection rules. (author)

  16. Automated wireless monitoring system for cable tension using smart sensors

    Science.gov (United States)

    Sim, Sung-Han; Li, Jian; Jo, Hongki; Park, Jongwoong; Cho, Soojin; Spencer, Billie F.; Yun, Chung-Bang

    2013-04-01

    Cables are critical load carrying members of cable-stayed bridges; monitoring tension forces of the cables provides valuable information for SHM of the cable-stayed bridges. Monitoring systems for the cable tension can be efficiently realized using wireless smart sensors in conjunction with vibration-based cable tension estimation approaches. This study develops an automated cable tension monitoring system using MEMSIC's Imote2 smart sensors. An embedded data processing strategy is implemented on the Imote2-based wireless sensor network to calculate cable tensions using a vibration-based method, significantly reducing the wireless data transmission and associated power consumption. The autonomous operation of the monitoring system is achieved by AutoMonitor, a high-level coordinator application provided by the Illinois SHM Project Services Toolsuite. The monitoring system also features power harvesting enabled by solar panels attached to each sensor node and AutoMonitor for charging control. The proposed wireless system has been deployed on the Jindo Bridge, a cable-stayed bridge located in South Korea. Tension forces are autonomously monitored for 12 cables in the east, land side of the bridge, proving the validity and potential of the presented tension monitoring system for real-world applications.

  17. External heating of electrical cables and auto-ignition investigation.

    Science.gov (United States)

    Courty, L; Garo, J P

    2017-01-05

    Electric cables are now extensively used for both residential and industrial applications. During more than twenty years, multi-scale approaches have been developed to study fire behavior of such cables that represents a serious challenge. Cables are rather complicated materials because they consist of an insulated part and jacket of polymeric materials. These polymeric materials can have various chemical structures, thicknesses and additives and generally have a char-forming tendency when exposed to heat source. In this work, two test methods are used for the characterization of cable pyrolysis and flammability. The first one permits the investigation of cable pyrolysis. A description of the cable mass loss is obtained, coupling an Arrhenius expression with a 1D thermal model of cables heating. Numerical results are successfully compared with experimental data obtained for two types of cable commonly used in French nuclear power plants. The second one is devoted to ignition investigations (spontaneous or piloted) of these cables. All these basic observations, measurements and modelling efforts are of major interest for a more comprehensive fire resistance evaluation of electric cables. Copyright © 2016 Elsevier B.V. All rights reserved.

  18. Cabling for an SSC silicon tracking system

    International Nuclear Information System (INIS)

    Ziock, H.; Boissevain, J.; Cooke, B.; Miller, W.

    1990-01-01

    As part of the Superconducting Super Collider Laboratory (SSCL) funded silicon tracking subsystem R ampersand D program, we examine the problems associated with cabling such a system. Different options for the cabling plant are discussed. A silicon microstrip tracking detector for an SSC experiment is an extremely complex system. The system consists of approximately 10 7 detector channels, each of which requires a communication link with the outside world and connections to the detector bias voltage supply, to a DC power supply for the onboard electronics, and to an adjustable discrimination level. The large number of channels and the short time between beam interactions (16 nanoseconds) dictates the need for high speed and large bandwidth communication channels, and a power distribution system that can handle the high current draw of the electronics including the large AC component due to their switching. At the same time the constraints imposed by the physics measurements require that the cable plant have absolutely minimal mass and radiation length. 4 refs., 2 figs

  19. SQUG cable tray and conduit evaluation procedure

    International Nuclear Information System (INIS)

    Smith, P.D.; Eder, S.J.; Conoscente, J.P.

    1990-01-01

    Cable tray and conduit systems for electrical cables are a common feature and industrial facilities. They have an excellent performance history in past strong earthquake, even though they are rarely designed for earthquakes. Considerable data have been gathered on their performance in earthquakes and in shake table testing. The data have been used to develop a procedure for the verification of the seismic adequacy of cable tray and conduit systems in operating nuclear plants. The procedure is discussed in this paper. It will result in substantial savings, such as reduced engineering effort, fewer modifications of existing hardware, and simpler documentation, relative to alternate procedures like dynamic analysis of shake table testing. The procedure ensures safety-function in a unique manner since the methodology used to develop it (1) is based on a large body of historical data and (2) uses a relative approach of ensuring that nuclear plant systems will perform at least as well as systems that performed well in past earthquakes. (orig.)

  20. Commercialization of Medium Voltage HTS Triax TM Cable Systems

    Energy Technology Data Exchange (ETDEWEB)

    Knoll, David

    2012-12-31

    The original project scope that was established in 2007 aimed to install a 1,700 meter (1.1 mile) medium voltage HTS Triax{TM} cable system into the utility grid in New Orleans, LA. In 2010, however, the utility partner withdrew from the project, so the 1,700 meter cable installation was cancelled and the scope of work was reduced. The work then concentrated on the specific barriers to commercialization of HTS cable technology. The modified scope included long-length HTS cable design and testing, high voltage factory test development, optimized cooling system development, and HTS cable life-cycle analysis. In 2012, Southwire again analyzed the market for HTS cables and deemed the near term market acceptance to be low. The scope of work was further reduced to the completion of tasks already started and to testing of the existing HTS cable system in Columbus, OH. The work completed under the project included: • Long-length cable modeling and analysis • HTS wire evaluation and testing • Cable testing for AC losses • Optimized cooling system design • Life cycle testing of the HTS cable in Columbus, OH • Project management. The 200 meter long HTS Triax{TM} cable in Columbus, OH was incorporated into the project under the initial scope changes as a test bed for life cycle testing as well as the site for an optimized HTS cable cooling system. The Columbus cable utilizes the HTS TriaxTM design, so it provided an economical tool for these of the project tasks.

  1. Modeling Cable and Guide Channel Interaction in a High-Strength Cable-Driven Continuum Manipulator.

    Science.gov (United States)

    Moses, Matthew S; Murphy, Ryan J; Kutzer, Michael D M; Armand, Mehran

    2015-12-01

    This paper presents several mechanical models of a high-strength cable-driven dexterous manipulator designed for surgical procedures. A stiffness model is presented that distinguishes between contributions from the cables and the backbone. A physics-based model incorporating cable friction is developed and its predictions are compared with experimental data. The data show that under high tension and high curvature, the shape of the manipulator deviates significantly from a circular arc. However, simple parametric models can fit the shape with good accuracy. The motivating application for this study is to develop a model so that shape can be predicted using easily measured quantities such as tension, so that real-time navigation may be performed, especially in minimally-invasive surgical procedures, while reducing the need for hazardous imaging methods such as fluoroscopy.

  2. Rapid optimization of tension distribution for cable-driven parallel manipulators with redundant cables

    Science.gov (United States)

    Ouyang, Bo; Shang, Weiwei

    2016-03-01

    The solution of tension distributions is infinite for cable-driven parallel manipulators(CDPMs) with redundant cables. A rapid optimization method for determining the optimal tension distribution is presented. The new optimization method is primarily based on the geometry properties of a polyhedron and convex analysis. The computational efficiency of the optimization method is improved by the designed projection algorithm, and a fast algorithm is proposed to determine which two of the lines are intersected at the optimal point. Moreover, a method for avoiding the operating point on the lower tension limit is developed. Simulation experiments are implemented on a six degree-of-freedom(6-DOF) CDPM with eight cables, and the results indicate that the new method is one order of magnitude faster than the standard simplex method. The optimal distribution of tension distribution is thus rapidly established on real-time by the proposed method.

  3. Design, processing, and properties of Bi 2212\\/Ag Rutherford cables

    CERN Document Server

    Collings, E W; Scanlan, R M; Dietderich, D R; Motowidlo, L R; Sokolowski, R S; Aoki, Y; Hasegawa, T

    1999-01-01

    In a program intended to explore the use of high temperature superconducting (HTSC) cables in high field synchrotron dipole magnets model Bi:2212/Ag Rutherford cables were designed bearing in mind the needs for mechanical integrity, relatively high tensile strength, and low coupling losses. To satisfy these needs a core-type cable design was selected and a readily available heat-resistant core material acquired. Cables were wound for critical current- and AC loss measurement. Both winding-induced (mechanical) and core-induced (chemical) critical current degradation was examined. Interstrand coupling loss was measured calorimetrically on model cable samples with bare- and oxide-coated cores. From the results it was predicted that the losses of full-scale Bi:2212/Ag-wound LHC-type Rutherford cables would fall close to the acceptability range for the windings of high-field accelerator dipoles. (10 refs).

  4. Loss and Inductance Investigation in Superconducting Cable Conductors

    DEFF Research Database (Denmark)

    Olsen, Søren Krüger; Tønnesen, Ole; Træholt, Chresten

    1999-01-01

    An important parameter in the design and optimization of a superconducting cable conductor is the control of the current distribution among single tapes and layers. This distribution is to a large degree determined by inductances, since the resistances are low. The self and mutual inductances...... of transport current and current distribution.This presentation is based on a number of experiments performed on prototype superconducting cable conductors. The critical current (1uV/cm) of the conductor at 77K was 1590 A (cable #1) and 3240 A (cable #2) respectively.At an rms current of 2 kA (50 Hz) the AC......-loss was measured on cable #2 to 0.6W/mxphase. This is, to our knowledge, the lowest AC-loss (at 2kA and 77K) of a high temperature superconducting cable conductor reported so far....

  5. Dynamic characteristics of stay cables with inerter dampers

    Science.gov (United States)

    Shi, Xiang; Zhu, Songye

    2018-06-01

    This study systematically investigates the dynamic characteristics of a stay cable with an inerter damper installed close to one end of a cable. The interest in applying inerter dampers to stay cables is partially inspired by the superior damping performance of negative stiffness dampers in the same application. A comprehensive parametric study on two major parameters, namely, inertance and damping coefficients, are conducted using analytical and numerical approaches. An inerter damper can be optimized for one vibration mode of a stay cable by generating identical wave numbers in two adjacent modes. An optimal design approach is proposed for inerter dampers installed on stay cables. The corresponding optimal inertance and damping coefficients are summarized for different damper locations and interested modes. Inerter dampers can offer better damping performance than conventional viscous dampers for the target mode of a stay cable that requires optimization. However, additional damping ratios in other vibration modes through inerter damper are relatively limited.

  6. Guy cable design and damping for vertical axis wind turbines

    Science.gov (United States)

    Carne, T. G.

    1981-01-01

    Guy cables are frequently used to support vertical axis wind turbines since guying the turbine reduces some of the structural requirements on the tower. The guys must be designed to provide both the required strength and the required stiffness at the top of the turbine. The axial load which the guys apply to the tower, bearings, and foundations is an undesirable consequence of using guys to support the turbine. Limiting the axial load so that it does not significantly affect the cost of the turbine is an important objective of the cable design. The lateral vibrations of the cables is another feature of the cable design which needs to be considered. These aspects of the cable design are discussed, and a technique for damping cable vibrations was mathematically analyzed and demonstrated with experimental data.

  7. Frequency analysis of a tower-cable coupled system

    Energy Technology Data Exchange (ETDEWEB)

    Park, Moo Yeol [Young Sin Precision Engineering Ltd., Gyungju (Korea, Republic of); Kim, Seock Hyun; Park, In Su [Kangwon National University, Chuncheon (Korea, Republic of); Cui, Chengxun [Yanbian University, Yangji (China)

    2013-06-15

    This study considers the prediction of natural frequency to avoid resonance in a wind turbine tower- cable coupled system. An analytical model based on the Rayleigh-Ritz method is proposed to predict the resonance frequency of a wind turbine tower structure supported by four guy cables. To verify the validity of the analytical model, a small tower-cable model is manufactured and tested. The frequency and mode data of the tower model are obtained by modal testing and finite element analysis. The validity of the proposed method is verified through the comparison of the frequency analysis results. Finally, using a parametric study with the analytical model, we identified how the cable tension and cable angle affect the resonance frequency of the wind turbine tower structure. From the analysis results, the tension limit and optimal angle of the cable are identified.

  8. State of the art in power cable design, failure mechanisms and testing

    International Nuclear Information System (INIS)

    Orton, H.

    2005-01-01

    This presentation describes state of the art in power cable design, failure mechanisms and testing. It gives a history of cable usage and design of cables, describes different cable types, assessment of the condition of cables, aging and failures, testing and diagnostics

  9. 47 CFR 1.1155 - Schedule of regulatory fees and filing locations for cable television services.

    Science.gov (United States)

    2010-10-01

    ... locations for cable television services. 1.1155 Section 1.1155 Telecommunication FEDERAL COMMUNICATIONS... Schedule of regulatory fees and filing locations for cable television services. Fee amount Address 1. Cable Television Relay Service $315 FCC, Cable, P.O. Box 979084, St. Louis, MO 63197-9000 2. Cable TV System (per...

  10. An Acoustic Source Reactive to Tow Cable Strum

    Science.gov (United States)

    2012-09-21

    sound wave radiates from the head mass. Dkt . No. 101720 Application No. ?? REPLACEMENT SHEET? /3 DRAFT 1 CABLE CURVATURE INDUCING LONGITUDINAL...MOTION IDEALIZED TOW CABLE (NO TRANSVERSE VIBRATION) REALISTIC TOW CABLE (INCLUDES TRANSVERSE VIBRATION) DIRECTION OF TOW FIG. 1 (PRIOR ART) Dkt . No...DISPLACEMENT DISPLACEMENT LONGITUDINAL (PRIOR ART) DISPLACEMENT LONGITUDINAL Dkt . No. 101720 Application No. ?? REPLACEMENT SHEET? /3 DRAFT 10 A B B A

  11. Similarity Analysis of Cable Insulations by Chemical Test

    Energy Technology Data Exchange (ETDEWEB)

    Kim, Jong Seog [Central Research Institute of Korea Hydro and Nuclear Power Co., Daejeon (Korea, Republic of)

    2013-10-15

    As result of this experiment, it was found that FT-IR test for material composition, TGA test for aging trend are applicable for similarity analysis of cable materials. OIT is recommended as option if TGA doesn't show good trend. Qualification of new insulation by EQ report of old insulation should be based on higher activation energy of new insulation than that of old one in the consideration of conservatism. In old nuclear power plant, it is easy to find black cable which has no marking of cable information such as manufacturer, material name and voltage. If a type test is required for qualification of these cables, how could I select representative cable? How could I determine the similarity of these cables? If manufacturer has qualified a cable for nuclear power plant more than a decade ago and composition of cable material is changed with similar one, is it acceptable to use the old EQ report for recently manufactured cable? It is well known to use FT-IR method to determine the similarity of cable materials. Infrared ray is easy tool to compare compositions of each material. But, it is not proper to compare aging trend of these materials. Study for similarity analysis of cable insulation by chemical test is described herein. To study a similarity evaluation method for polymer materials, FT-IR, TGA and OIT tests were performed for two cable insulation(old and new) which were supplied from same manufacturer. FT-IR shows good result to compare material compositions while TGA and OIT show good result to compare aging character of materials.

  12. Method discussion of the performance evaluation on nuclear plant cable

    International Nuclear Information System (INIS)

    Lu Yongfang; Zhong Weixia; Sun Jiansheng; Liu Jingping

    2014-01-01

    A stock cable, which is same as the nuclear plant cable in service, was treated by thermal aging. After that, the mechanical property, the flame retardant property, the anti-oxidation were measured, and relationships between them due to the thermal aging were established. By those analysis, evaluating the in-service cable performance in nuclear plant and calculating its remaining life. Furthermore, the feasibility of this method was disscussed. (authors)

  13. Total Magnetic Field Signatures over Submarine HVDC Power Cables

    Science.gov (United States)

    Johnson, R. M.; Tchernychev, M.; Johnston, J. M.; Tryggestad, J.

    2013-12-01

    Mikhail Tchernychev, Geometrics, Inc. Ross Johnson, Geometrics, Inc. Jeff Johnston, Geometrics, Inc. High Voltage Direct Current (HVDC) technology is widely used to transmit electrical power over considerable distances using submarine cables. The most commonly known examples are the HVDC cable between Italy and Greece (160 km), Victoria-Tasmania (300 km), New Jersey - Long Island (82 km) and the Transbay cable (Pittsburg, California - San-Francisco). These cables are inspected periodically and their location and burial depth verified. This inspection applies to live and idle cables; in particular a survey company could be required to locate pieces of a dead cable for subsequent removal from the sea floor. Most HVDC cables produce a constant magnetic field; therefore one of the possible survey tools would be Marine Total Field Magnetometer. We present mathematical expressions of the expected magnetic fields and compare them with fields observed during actual surveys. We also compare these anomalies fields with magnetic fields produced by other long objects, such as submarine pipelines The data processing techniques are discussed. There include the use of Analytic Signal and direct modeling of Total Magnetic Field. The Analytic Signal analysis can be adapted using ground truth where available, but the total field allows better discrimination of the cable parameters, in particular to distinguish between live and idle cable. Use of a Transverse Gradiometer (TVG) allows for easy discrimination between cable and pipe line objects. Considerable magnetic gradient is present in the case of a pipeline whereas there is less gradient for the DC power cable. Thus the TVG is used to validate assumptions made during the data interpretation process. Data obtained during the TVG surveys suggest that the magnetic field of a live HVDC cable is described by an expression for two infinite long wires carrying current in opposite directions.

  14. Problems with conductors and dielectrics for cryogenic cables

    Energy Technology Data Exchange (ETDEWEB)

    Bogner, G; Penczynski, P [Siemens A.G., Erlangen (F.R. Germany). Abt. Reaktortechnik

    1976-06-01

    The most important problems which need to be solved if superconducting power cables are to be used on a large scale are connected with the superconducting cable materials and the dielectrics used for insulation. Research work on superconducting materials for ac and dc cables is briefly reviewed together with stabilization problems for these materials. Three types of insulation are considered - vacuum, subcooled or supercritical helium, and foil wound insulation. The merits and problems encountered in each case are discussed.

  15. Similarity Analysis of Cable Insulations by Chemical Test

    International Nuclear Information System (INIS)

    Kim, Jong Seog

    2013-01-01

    As result of this experiment, it was found that FT-IR test for material composition, TGA test for aging trend are applicable for similarity analysis of cable materials. OIT is recommended as option if TGA doesn't show good trend. Qualification of new insulation by EQ report of old insulation should be based on higher activation energy of new insulation than that of old one in the consideration of conservatism. In old nuclear power plant, it is easy to find black cable which has no marking of cable information such as manufacturer, material name and voltage. If a type test is required for qualification of these cables, how could I select representative cable? How could I determine the similarity of these cables? If manufacturer has qualified a cable for nuclear power plant more than a decade ago and composition of cable material is changed with similar one, is it acceptable to use the old EQ report for recently manufactured cable? It is well known to use FT-IR method to determine the similarity of cable materials. Infrared ray is easy tool to compare compositions of each material. But, it is not proper to compare aging trend of these materials. Study for similarity analysis of cable insulation by chemical test is described herein. To study a similarity evaluation method for polymer materials, FT-IR, TGA and OIT tests were performed for two cable insulation(old and new) which were supplied from same manufacturer. FT-IR shows good result to compare material compositions while TGA and OIT show good result to compare aging character of materials

  16. Development of halogen-free cables for nuclear power plants

    International Nuclear Information System (INIS)

    Yamamoto, Mitsuo; Ito, Kazumi; Yaji, Takeo; Yoshida, Shin; Sakurai, Takako; Matsushita, Shigetoshi.

    1990-01-01

    On the occasion where serious fire accidents were experienced in the past, the need for making flame-retardant wire and cable incombustible took place and has since been generalizing. Various sorts of flame-retardant cables have already been developed and been actually used. From the viewpoint of avoiding the interference with the evacuation and fire-fighting activity in case of fire or the secondary accidents such as corrosion of the distributing panel, etc., the demand for non-halogen flame-retardant cable has rapidly been increasing in recent years in some fields of general industries, because this specific cable would generate the least amount of toxic smoke or corrosive gas even when it should burn. Similar demand has been increasing also for the cable used for nuclear power plants. In this field, earnest desire has been made for the development of non-halogen flame-retardant cable having specific environmental resistance specially required at nuclear power plants in addition to the properties and capacities required in general industries. The authors have continued examinations on the anti-environmental properties of the materials for cable such as long heat resistance, radiation resistance, steam resistance and succeeded in completing various sorts of non-halogen flame-retardant cable for nuclear power plants. In this report, we will introduce various features of the cable we have developed this time as well as the long-term reliability of non-halogen flame-retardant materials. (author)

  17. Debris from cobalt-chrome cable may cause acetabular loosening.

    Science.gov (United States)

    Kelley, S S; Johnston, R C

    1992-12-01

    To address the issue of nonunion with trochanteric osteotomy, surgeons have experimented with various modes of fixation, wire and cable being the two most popular. From a group of 643 primary cemented total hip arthroplasties performed by a single surgeon via the trans-trochanteric approach, minimum four-year roentgenographic follow-up evaluations were performed on 322 hips (50%). The method of fixation was stainless steel monofilament wire in 162 cases and Co-Cr cable in 160. Trochanteric union rates were 75% (122 patients) for the wire group and 79% (126 patients) for the cable. Breakage rates of the entire trochanteric fixation construction (all three wires or cables) were 43% (68 patients) for the wire and 12% (20 patients) for the cable. Unraveled cable was seen in 56% of the hips (90 patients), and in 47% of these hips, there were no broken cables. Blinded roentgenographic analysis of the acetabulum, preformed independently, revealed that loosening of the acetabulum in the cable group was greater than in the wire group. Cables offer no significant benefit over wires and may have potential adverse effects. Generation of significant particulate debris was noted roentgenographically, and marked reaction/destruction was found at the time of revision surgery.

  18. Stationary operational behavior unsymmetrical superconducting three-phase cable

    Energy Technology Data Exchange (ETDEWEB)

    Iser, R.

    1974-01-01

    A superconducting cable with a coaxial conductor arrangement is electrically unsymmetrical. Voltage and current relationships are analyzed for such a cable where, as a result of reactance and capacitance matrices being unsymmetric, large voltage unsymmetry appears. This limits the practical length of this type of cable. It is shown that a significant gain in symmetry is attained by the use of two cables connected in parallel. The compensating current which then occurs involves no disadvantage. The circuit described permits overloads of up to 100 percent.

  19. Real Time Load Optimisation of Cable Based Transmission Grids

    DEFF Research Database (Denmark)

    Olsen, Rasmus Schmidt; Holbøll, Joachim; Guðmundsdottir, Unnur Stella

    2011-01-01

    Energinet.dk has launched an investigation of dynamic current ratings of cable based transmission grids, where both internal and external parameters are variables. The first topic was to investigate state of the art within calculating the current carrying capacity (ampacity or loadability......) of cables embedded in larger cable systems. Some recently published research has been concerned with dynamic loadability, but such researches are based on many assumptions. It is shown in the paper, that only limited research has been concerned with larger cable grids, and no remarkable work could been...

  20. Design guide for fire protection of grouped electrical cables

    International Nuclear Information System (INIS)

    Dungan, K.W.

    1991-05-01

    This paper develops design guidance for fire protection of grouped electrical cables using previous research and the concept of design objectives based on damage limits. A quantitative approach is taken to establishing performance-oriented design objectives and addressing fires exposing cables as well as cable fires. A one-page Design Calculation Checklist is developed and examples are shown. In addition, testing was done for placement of linear thermal detection on cable trays and recommendations are given. 32 refs., 10 figs., 8 tabs

  1. Strand critical current degradation in $Nb_{3}$ Sn Rutherford cables

    CERN Document Server

    Barzi, E; Higley, H C; Scanlan, R M; Yamada, R; Zlobin, A V

    2001-01-01

    Fermilab is developing 11 Tesla superconducting accelerator magnets based on Nb/sub 3/Sn superconductor. Multifilamentary Nb/sub 3/Sn strands produced using the modified jelly roll, internal tin, and powder-in-tube technologies were used for the development and test of the prototype cable. To optimize the cable geometry with respect to the critical current, short samples of Rutherford cable with packing factors in the 85 to 95% range were fabricated and studied. In this paper, the results of measurements of critical current, n-value and RRR made on the round virgin strands and on the strands extracted from the cable samples are presented. (5 refs).

  2. Development mineral insulated cables for nuclear instrumentation of reactors

    International Nuclear Information System (INIS)

    Calvo, W.A.P.; Hess Junior, A.; Brito Maciel, R. de

    1990-01-01

    In-core and out-of-core neutron detectors for reactor and safety control systems are usually connected by means of mineral insulated cables. The electrical signal, either a pulse or a current, is transmitted along the cable at high temperature, pressure and radiation and should not be influenced by electromagnetic interfereces from the environment. In this paper it is presented the result of the analysis of the mechanical and electrical properties of several types of mineral insulated cables and also the design, manufacture, sealing, cable ends and their applications to nuclear detectors of various types. (author) [pt

  3. Interstrand contact resistances of Bi-2212 Rutherford cables for SMES

    International Nuclear Information System (INIS)

    Kawagoe, A.; Kawabata, Y.; Sumiyoshi, F.; Nagaya, S.; Hirano, N.

    2006-01-01

    Interstrand contact resistances of Bi-2212 Rutherford cables for SMES coils were evaluated from a comparison between measured data and 2D-FEM analyses on interstrand coupling losses in these cables. The cables were composed of 30 non-twisted Bi-2212 strands with a diameter of 0.81 mm and a cable twist pitch of 90 mm. Three samples were measured; one of them had NiCr cores and the others had no cores. One of the latter two samples repeatedly experienced bending. The interstrand coupling losses were measured in liquid helium for the straight samples under transverse ac ripple magnetic fields superposed on dc bias magnetic fields. The transverse magnetic field was applied to the samples in directions both perpendicular and parallel to the flat face of the cable. The effect of the bending on the interstrand coupling losses could be neglected for the non-cored samples. The interstrand coupling losses of NiCr cored sample decreased by about 30% compared with the non-cored samples, in case the direction of the transverse magnetic fields applied to the cable is perpendicular to the flat face of the cable. Using these results and 2D-FEM analyses, taking into account that interstrand contact conditions vary from the center to the edge in the cross-section of cables, gave us the conclusion that the between side-by-side strands contact with metallurgical bond only in both edges of the cables

  4. Interstrand contact resistances of Bi-2212 Rutherford cables for SMES

    Science.gov (United States)

    Kawagoe, A.; Kawabata, Y.; Sumiyoshi, F.; Nagaya, S.; Hirano, N.

    2006-10-01

    Interstrand contact resistances of Bi-2212 Rutherford cables for SMES coils were evaluated from a comparison between measured data and 2D-FEM analyses on interstrand coupling losses in these cables. The cables were composed of 30 non-twisted Bi-2212 strands with a diameter of 0.81 mm and a cable twist pitch of 90 mm. Three samples were measured; one of them had NiCr cores and the others had no cores. One of the latter two samples repeatedly experienced bending. The interstrand coupling losses were measured in liquid helium for the straight samples under transverse ac ripple magnetic fields superposed on dc bias magnetic fields. The transverse magnetic field was applied to the samples in directions both perpendicular and parallel to the flat face of the cable. The effect of the bending on the interstrand coupling losses could be neglected for the non-cored samples. The interstrand coupling losses of NiCr cored sample decreased by about 30% compared with the non-cored samples, in case the direction of the transverse magnetic fields applied to the cable is perpendicular to the flat face of the cable. Using these results and 2D-FEM analyses, taking into account that interstrand contact conditions vary from the center to the edge in the cross-section of cables, gave us the conclusion that the between side-by-side strands contact with metallurgical bond only in both edges of the cables.

  5. Development of scaling rules for Rutherford type superconducting cables

    International Nuclear Information System (INIS)

    Royet, J.M.; Scanlan, R.M.

    1991-01-01

    During the R and D phase of the Superconducting Supercollider (SSC) program, LBL was responsible for establishing the parameters for cables used in SSC dipole and quadrupole magnets. In addition, LBL has collaborated with Fermi National Accelerator Laboratory on the design and fabrication of a new cable for use in the Low Beta Quadrupoles. As a result of the development work on these and other cables, we have arrived a set of scaling rules which provide guidelines for choosing the parameters for a wide range of superconducting cables. These parameters include strand size, strand number, keystone angle, percent compaction, cable pitch and compacted cable dimensions. In addition, we have defined the tolerance ranges for the key cable manufacturing parameters such as mandrel size and shape, strand tension, and Turkshead temperature control. In this paper, the authors present the results on cables ranging from 8 strands to 36 strands of 0.65mm wire and from 8 strands to 30 strands of 0.8mm wire. The authors use these results to demonstrate the application of the scaling rules for Rutherford-type cable

  6. Development of scaling rules for Rutherford type superconducting cables

    International Nuclear Information System (INIS)

    Royet, J.M.; Scanlan, R.M.

    1990-09-01

    During the R ampersand D phase of the Superconducting Supercollider (SSC) program, LBL was responsible for establishing the parameters for cables used in SSC dipole and quadrupole magnets. In addition, the design and fabrication of a new cable for use in the Low Beta Quadrupoles. As a result of the development work on these and other cables, we have arrived a set of scaling rules which provide guidelines for choosing the parameters for a wide range of superconducting cables. These parameters include strand size, strand number, keystone angle, percent compaction, cable pitch and compacted cable dimensions. In addition, we have defined the tolerance ranges for the key cable manufacturing parameters such as mandrel size and shape, stand tension, and Turkshead temperature control. In this paper, we present the results on cables ranging from 8 strands to 36 strands of 0.65mm wire and from 8 strands to 30 strands of 0.8mm wire. We use these results to demonstrate the application of the scaling rules for Rutherford-type cable

  7. Recent development of the Cu/Nb-Ti superconducting cables for SSC in Hitachi Cable, Ltd

    International Nuclear Information System (INIS)

    Sakai, S.; Iwaki, G.; Sawada, Y.; Moriai, H.; Ishigami, Y.

    1989-01-01

    In these few years, Cu/Nb-Ti superconducting cables for the dipole magnets of SSC projects have been developed in the industrial scale in Hitachi Cable, Ltd. The features of these developed conductors are as follows. (1) The diameter of Nb-Ti filaments is very small, 4-6 μm. (2) The critical current density (J c ) is very high, 2,850-3,050 A/mm 2 at 5 T on wires, 2750-2950 A/mm 2 at 5 T on cables in industrial scale. The champion J c of wires is 3,460 A/mm 2 at 5 T in the laboratory scale. (3) The RRR Residual Resistivity Ratio values of developed cables is very high, approximately 200, due to the newly developed high purity Oxygen Free Copper (OFC). (4) The conductors have been wound to the 1 m length dipole magnet in Hitachi Ltd., and it has generated 6.7 T in the central magnetic field at 6,595 A. The Cu/Cu-Mn/Nb-Ti composite wires which avoid the possibility of electrical coupling of the filaments have been produced in laboratory scale. The RRR of the copper stabilizer and J c properties have not degraded because of no metallurgical reactions between Cu and Mn, Nb-Ti and Mn. 7 refs., 9 figs., 4 tabs

  8. Method of exchanging cables of neutron monitoring instrumentation tube and folding device of the cable

    International Nuclear Information System (INIS)

    Sakamaki, Kazuo.

    1990-01-01

    In a BWR type reactor, a wide range monitor (WRNM) is used instead of a conventional neutron source range monitor (SRM) or an intermediate range monitor (IRM). The WRNM is always fixed to a predetermined position in a reactor core while containing a detection section in a dry tube, different from a conventional monitor. Accordingly, driving devices for the conventional detection section such as in SRM and IRM are not necessary but, when the reactor is operated for a long period of time, it is sometimes necessary to be replaced with new WRNM. According to the present invention, the cable of the detector placed in a neutron instrumentation tube is connected to a cable take-up drum in a take-up device passing through a cask. Then, the cable is taken-up by driving the take-up drum by a driving motor and the WRNM detection section attached to the top end of the cable is contained in the cask. With this constitution, replacing and processing operation for the detection section can be facilitated and operator's exposure dose can be reduced. (I.S.)

  9. Analytical model for cable tray fires

    International Nuclear Information System (INIS)

    Clarke, R.K.

    1975-09-01

    A model for cable tray fires based on buoyant plume theory is presented. Using the model in conjunction with empirical data on size of natural fires and burning rate of cellulosic materials, estimates are made of the heat flux as a function of vertical and horizontal distance from a tray fire. Both local fires and fires extending along a significant length of tray are considered. For the particular set of fire parameters assumed in the calculations, the current tray separation criteria of five feet vertical and three feet horizontal are found to be marginal for local fires and too small to prevent fire spread for extended tray fires. 8 references. (auth)

  10. Power laws from linear neuronal cable theory

    DEFF Research Database (Denmark)

    Pettersen, Klas H; Lindén, Henrik Anders; Tetzlaff, Tom

    2014-01-01

    suggested to be at the root of this phenomenon, we here demonstrate a possible origin of such power laws in the biophysical properties of single neurons described by the standard cable equation. Taking advantage of the analytical tractability of the so called ball and stick neuron model, we derive general...... are homogeneously distributed across the neural membranes and themselves exhibit pink ([Formula: see text]) noise distributions. While the PSD noise spectra at low frequencies may be dominated by synaptic noise, our findings suggest that the high-frequency power laws may originate in noise from intrinsic ion...

  11. Modelling and simulation of railway cable systems

    Energy Technology Data Exchange (ETDEWEB)

    Teichelmann, G.; Schaub, M.; Simeon, B. [Technische Univ. Muenchen, Garching (Germany). Zentrum Mathematik M2

    2005-12-15

    Mathematical models and numerical methods for the computation of both static equilibria and dynamic oscillations of railroad catenaries are derived and analyzed. These cable systems form a complex network of string and beam elements and lead to coupled partial differential equations in space and time where constraints and corresponding Lagrange multipliers express the interaction between carrier, contact wire, and pantograph head. For computing static equilibria, three different algorithms are presented and compared, while the dynamic case is treated by a finite element method in space, combined with stabilized time integration of the resulting differential algebraic system. Simulation examples based on reference data from industry illustrate the potential of such computational tools. (orig.)

  12. Two-way cable television project

    Science.gov (United States)

    Wilkens, H.; Guenther, P.; Kiel, F.; Kraus, F.; Mahnkopf, P.; Schnee, R.

    1982-02-01

    The market demand for a multiuser computer system with interactive services was studied. Mean system work load at peak use hours was estimated and the complexity of dialog with a central computer was determined. Man machine communication by broadband cable television transmission, using digital techniques, was assumed. The end to end system is described. It is user friendly, able to handle 10,000 subscribers, and provides color television display. The central computer system architecture with remote audiovisual terminals is depicted and software is explained. Signal transmission requirements are dealt with. International availability of the test system, including sample programs, is indicated.

  13. Fibre optic cable in the nuclear industry

    International Nuclear Information System (INIS)

    Roberts, Berwyn

    1987-01-01

    The uses of optical fibre cables to transmit light signals include medical applications and telecommunications. In the nuclear industry the applications include process control and monitoring, conventional datacoms, security fencing and sensors. Time division multiplexing is described and currently available fibre optic multipexers are listed and explained. Single and multimode fibres are mentioned. Fibre optics are also used in cryogenics, to monitor the integrity of the storage vessels for cryogenic liquids. The uses of fibre optics at Hartlepool, Heysham I and Torness are mentioned in particular. (UK)

  14. 77 FR 67290 - Basic Service Tier Encryption Compatibility Between Cable Systems and Consumer Electronics Equipment

    Science.gov (United States)

    2012-11-09

    ...-126] Basic Service Tier Encryption Compatibility Between Cable Systems and Consumer Electronics... between consumer electronics equipment (such as digital television sets) and newly encrypted cable service... Act''), Congress sought to make sure that consumer electronics equipment could receive cable...

  15. Continued development of a non-proprietary, high-tension, cable end terminal system.

    Science.gov (United States)

    2016-04-29

    A non-proprietary, cable guardrail system is currently under development for the Midwest States Pooled Fund Program. : A cable guardrail end terminal was necessary to accompany the cable guardrail system. The objective of this research : project was ...

  16. A PSO Driven Intelligent Model Updating and Parameter Identification Scheme for Cable-Damper System

    Directory of Open Access Journals (Sweden)

    Danhui Dan

    2015-01-01

    Full Text Available The precise measurement of the cable force is very important for monitoring and evaluating the operation status of cable structures such as cable-stayed bridges. The cable system should be installed with lateral dampers to reduce the vibration, which affects the precise measurement of the cable force and other cable parameters. This paper suggests a cable model updating calculation scheme driven by the particle swarm optimization (PSO algorithm. By establishing a finite element model considering the static geometric nonlinearity and stress-stiffening effect firstly, an automatically finite element method model updating powered by PSO algorithm is proposed, with the aims to identify the cable force and relevant parameters of cable-damper system precisely. Both numerical case studies and full-scale cable tests indicated that, after two rounds of updating process, the algorithm can accurately identify the cable force, moment of inertia, and damping coefficient of the cable-damper system.

  17. Copper Cable Recycling Technology. Innovative Technology Summary Report

    International Nuclear Information System (INIS)

    2001-01-01

    The United States Department of Energy (DOE) continually seeks safer and more cost-effective technologies for use in deactivation and decommissioning (D and D) of nuclear facilities. The Deactivation and Decommissioning Focus Area (DDFA) of the DOE's Office of Science and Technology (OST) sponsors large-scale demonstration and deployment projects (LSDDPs). At these LSDDPs, developers and vendors of improved or innovative technologies showcase products that are potentially beneficial to the DOE's projects and to others in the D and D community. Benefits sought include decreased health and safety risks to personnel and the environment, increased productivity, and decreased costs of operation. The Idaho National Engineering and Environmental Laboratory (INEEL) generated a list of statements defining specific needs and problems where improved technology could be incorporated into ongoing D and D tasks. One such need is to reduce the volume of waste copper wire and cable generated by D and D. Deactivation and decommissioning activities of nuclear facilities generates hundreds of tons of contaminated copper cable, which are sent to radioactive waste disposal sites. The Copper Cable Recycling Technology separates the clean copper from contaminated insulation and dust materials in these cables. The recovered copper can then be reclaimed and, more importantly, landfill disposal volumes can be reduced. The existing baseline technology for disposing radioactively contaminated cables is to package the cables in wooden storage boxes and dispose of the cables in radioactive waste disposal sites. The Copper Cable Recycling Technology is applicable to facility decommissioning projects at many Department of Energy (DOE) nuclear facilities and commercial nuclear power plants undergoing decommissioning activities. The INEEL Copper Cable Recycling Technology Demonstration investigated the effectiveness and efficiency to recycle 13.5 tons of copper cable. To determine the effectiveness

  18. Cook Strait cable leak investigation, March-June 1985

    International Nuclear Information System (INIS)

    Barry, B.J.; Fitzgerald, G.J.

    1985-09-01

    An investigation was made to locate a gas leak in an under-sea electric power cable. Krypton-85 was used as the tracer. Despite problems with the investigation there was strong evidence to suggest that the leak was in the joint between the land and sea portions of the cable. (auths)

  19. A Critical Look At South Dakota Cable TV Franchising.

    Science.gov (United States)

    Williamson, Rick P.

    An examination of the present status and future potential of cable television (CATV) in South Dakota is conducted. Chapter 1 offers a brief introduction to cable in the State and Chapter 2 discusses the value of CATV to South Dakota. The next Chapter presents a State plan for communications and the fourth deals with the subject of franchising. The…

  20. Lightning-resistant, low-inductance detonator cables

    Energy Technology Data Exchange (ETDEWEB)

    Druce, R.L.; Lee, R.S.; Moua, K.

    1994-04-01

    A lightning strike on a flat detonator cable in close proximity to a high explosive (HE) main charge poses a possible detonation hazard if the electrical explosion of the cable launches the dielectric cover coat of the cable at a high enough velocity to shock-initiate the HE. The detonator cable for the W87 system has been demonstrated to be incapable of initiating LX-17 main-charge explosive even for a 99 percentile negative lightning strike (1). The W87 cable is a relatively high inductance cable, unsuitable for use with low-inductance firesets. We have performed tests on a low-inductance cable designed for the W89 program, which show it to be marginal in its ability to withstand a lightning strike without the possibility of initiating a heated LX-17 main charge HE. A new cable design, proposed by R.E. Lee of LLNL has been tested and shown to be capable of withstanding a 99 percentile negative lightning strike without initiating LX-17 heated to 250{degree}C.

  1. Uses of Cable Television in Eight Midwestern Communities.

    Science.gov (United States)

    Gotsch, Constance M.

    This study of midwestern cable television systems was designed to accomplish three purposes: (1) compare recommended administration and franchise provisions with actual administration and franchise provisions to see how these policies relate to the future development of educational channels; (2) determine how educators and cable managers work…

  2. Measurements and modeling of EMC, applied to cabling and wiring

    NARCIS (Netherlands)

    Bargboer, G.

    2011-01-01

    A myriad of cables transport power and communication signals in larger buildings and installations. Cross talk between cables and connected equipment is a major concern. Regulations do exist, but often show to be insufficient to avoid undesirable coupling. The current thesis research addresses this

  3. 24 CFR 3285.906 - Telephone and cable TV.

    Science.gov (United States)

    2010-04-01

    ... URBAN DEVELOPMENT MODEL MANUFACTURED HOME INSTALLATION STANDARDS Optional Information for Manufacturer's Installation Instructions § 3285.906 Telephone and cable TV. It is recommended that the installation instructions explain that telephone and cable TV wiring should be installed in accordance with requirements of...

  4. Comparison of several innovative bridge cable surface modifications

    DEFF Research Database (Denmark)

    Kleissl, Kenneth; Georgakis, Christos T.

    Over the last two decades, several bridge cable manufacturers have introduced surface modifications on the high-density polyethylene (HDPE) sheathing that is installed for the protection of inner cable strands or wires. The modifications are based on research undertaken predominantly in Europe...

  5. Aerodynamic force coefficients of plain bridge cables in wet conditions

    DEFF Research Database (Denmark)

    Matteoni, Giulia; Georgakis, Christos T.

    In this paper, the aerodynamic forces and force coefficients from preliminary static wind tunnel tests on a plain cable in wet conditions are presented. The presented results are for several different relative cable wind-angles. A comparison is made with tests in dry conditions. In dry conditions...

  6. Chemical oxidation of cable insulating oil contaminated soil

    NARCIS (Netherlands)

    Jinlan Xu,; Pancras, T.; Grotenhuis, J.T.C.

    2011-01-01

    Leaking cable insulating oil is a common source of soil contamination of high-voltage underground electricity cables in many European countries. In situ remediation of these contaminations is very difficult, due to the nature of the contamination and the high concentrations present. Chemical

  7. Prevention of cable fires in nuclear power plants

    International Nuclear Information System (INIS)

    Murota, George; Yajima, Kazuo

    1979-01-01

    Nuclear power generation is indispensable to secure required electric power, therefore double or triple safety measures are necessary to prevent serious accidents absolutely. As for the countermeasures to cable fires, interest grew rapidly with the fire in Browns Ferry Power Station in USA in 1975 as the turning point, because multi-strand grouped cables caused to promote the spread of fire. In Japan, also the fire prevention measures for wires and cables were more strengthened, and the measures for preventing the spread of cable fires with the agent preventing the spread of fires have occupied the important position. When multi-strand cables are ignited by some cause, the fire spreads with very large combustion force along wirings to other rooms and installations, and electric systems are broken down. The harmful corrosive gas generated from the burning coating materials of cables diffuses very quickly. In nuclear power stations, the cables which are very hard to burn are adopted, fire prevention sections are established positively, the fire-resisting capability of fire prevention barriers is reviewed, and fire-resisting and smoke-preventing treatments are applied to the parts where cables penetrate walls, floors or ceilings. The paint and the sealing material which prevent the spread of fires are introduced. (Kako, I.)

  8. Optimized and practical electrical joints for CORC type HTS cables

    CERN Document Server

    Mulder, T; van der Laan, D C; Mentink, M G T; Dhallé, M; ten Kate, H H J

    2015-01-01

    Within CERN the development of REBCO-CORC (Conductor On Round Core) type cables is pursued in view of possible application in future detector and accelerator magnets. An important issue is the design and qualification of terminations for connecting CORC cables mutually or to bus-bars. A termination design is envisaged that combines a simple manufacturing process with a lowest possible joint terminal resistance in the few nΩ range at 4.2 K, first for a single CORC cable and subsequently for CORC based Cable-in-Conduit Conductors. The investigation concerns the effect of tapering the CORC cable within the joint to form a staircase like geometry, which allows current to pass more directly from the copper joint casing to the inner REBCO layers of the CORC cable. Simulations have shown a substantial decrease in joint resistance at operating current in the case both CORC cable and joint casing are tapered. The CORC cable and new joint were tested at CERN. In this paper, some details of the new joint design, fabric...

  9. Optimized and practical electrical joints for CORC type HTS cables

    International Nuclear Information System (INIS)

    Mulder, T; Dudarev, A; Mentink, M G T; Ten Kate, H H J; Van der Laan, D C; Dhallé, M

    2015-01-01

    Within CERN the development of REBCO-CORC (Conductor On Round Core) type cables is pursued in view of possible application in future detector and accelerator magnets. An important issue is the design and qualification of terminations for connecting CORC cables mutually or to bus-bars. A termination design is envisaged that combines a simple manufacturing process with a lowest possible joint terminal resistance in the few nΩ range at 4.2 K, first for a single CORC cable and subsequently for CORC based Cable-in-Conduit Conductors. The investigation concerns the effect of tapering the CORC cable within the joint to form a staircase like geometry, which allows current to pass more directly from the copper joint casing to the inner REBCO layers of the CORC cable. Simulations have shown a substantial decrease in joint resistance at operating current in the case both CORC cable and joint casing are tapered. The CORC cable and new joint were tested at CERN. In this paper, some details of the new joint design, fabrication process, and model are presented and the results are summarized. (paper)

  10. New, clean handling process introduced to improve cable quality

    Energy Technology Data Exchange (ETDEWEB)

    Hunt, C G

    1990-05-01

    The clean room system introduced by Canada Wire and Cable Limited in its Toronto plant for its cable manufacturing operation is described. While clean room technology is common in the food processing industry, optical and aerospace manufacturing processes, this is the first time it has been applied to wire and cable extrusion in North America. The purpose of the clean compound handling system is to prevent particle contamination in the shielding and cable insulation materials, as part of an effort to prevent premature underground electric cable failures. Two rooms are dedicated to handling different types of insulation compound, two are dedicated to receiving semi-conducting shielding material, and the fifth room functions as an air lock for the two insulation rooms. The atmosphere is highly regulated with programmable logic control. The air supply filters capture 99.97% of all particles 0.3 microns or larger. The system also maintains air temperature, relative humidity and static pressure. The life variability of cross-linked polyethylene primary distribution cable is dependant on five factors: material purity, extra clean compound handling, cable design, manufacturing process, and installation and operation practices. The clean room system is expected to result in cable that is more resistant to water treeing failures. 2 figs.

  11. Heat resistant wire and cable and heat shrinkable tubes

    Energy Technology Data Exchange (ETDEWEB)

    Ueno, Keiji [Sumitomo Electric Industries Ltd. (Japan)

    1994-12-31

    Radiation processes have been used in industrial fields (e.g. wire and cable, heat shrinkable tubes) for about 30 years. In Japan, 60 electron beam accelerators were used in R and D, 54 in wire and cable, 24 in tire rubber, 16 in paint curing, 14 in PE foam and 9 accelerators were used in heat shrinkable tubes in 1993. Many properties (e.g. solder resistance, thermal deformation, and solven resistance) of wire and cable are improved by using radiation processes, and many kinds of radiation crosslinked wire and cable are used in the consumer market (TV sets, VTR`s, audio disc players, etc.), automobiles (automobile wire harnesses, fusible link wires, sensor cables etc.), and the industrial market (computer cables, cables for keyboards, coaxial cables, etc.). Another important industrial application of E{beta} radiation process is heat shrinkable tubes. Heat shinkable tubes, heated by a hot gun, shrink 1/2 {approx} 1/3 of their inner diameters. Heat shrinkable tubes are used for covers of distributing line terminals, joint covers of telecommunication lines, protection of fuel pipe lines and so on. In this seminar, actual applications and characteristic properties of radiation crosslinked materials are presented.

  12. 47 CFR 15.118 - Cable ready consumer electronics equipment.

    Science.gov (United States)

    2010-10-01

    ... 47 Telecommunication 1 2010-10-01 2010-10-01 false Cable ready consumer electronics equipment. 15... Unintentional Radiators § 15.118 Cable ready consumer electronics equipment. (a) All consumer electronics TV... provisions of this section. Consumer electronics TV receiving equipment that includes features intended for...

  13. Cable systems for experimental facilities in JAERI TANDEM ACCELERATOR BUILDING

    International Nuclear Information System (INIS)

    Tukihashi, Yoshihiro; Yoshida, Tadashi; Takekoshi, Eiko

    1979-03-01

    Measuring cable systems for experimental facilities in JAERI TANDEM ACCELERATOR BUILDING were completed recently. Measures are taken to prevent penetration of noises into the measuring systems. The cable systems are described in detail, including power supplies and grounding for the measuring systems. (author)

  14. Proposed Ordinance for the Regulation of Cable Television. Working Draft.

    Science.gov (United States)

    Chicago City Council, IL.

    A model ordinance is proposed for the regulation of cable television in the city of Chicago. It defines the language of the ordinance, sets forth the method of granting franchises, and describes the terms of the franchises. The duties of a commission to regulate cable television are listed and the method of selecting commission members is…

  15. Evaluation of cable aging degradation based on plant operating condition

    International Nuclear Information System (INIS)

    Kim, Jong-Seog

    2005-01-01

    Extending the lifetime of nuclear power plant [(hereafter referred simply as ''NPP'')] is one of the most important concerns in the world nuclear industry. Cables are one of the long live items which have not been considered to be replaced during the design life of NPP. To extend the cable life beyond the design life, we need to prove that the design life is too conservative compared with the actual aging. Condition monitoring is one of the useful ways for evaluating the aging condition of cable. In order to simulate the natural aging in nuclear power plant, a study on accelerated aging needs to be conducted first. In this paper, evaluations of mechanical aging degradation for cable jacket were performed after accelerated aging under the continuous heating and intermittent heating. Contrary to general expectation, the intermittent heating to cable jacket showed low aging degradation, 50% break-elongation and 60% indenter modulus, compared with continuous heating. With the plant maintenance period of 1 month after every 12 or 18 months operation, we can easily deduce that the life time of cable jacket can be extended much longer than estimated through the general EQ (Environmental Qualification) test, which adopts continuous accelerated aging for determining cable life. Therefore, a systematic approach which considers the actual environment condition of nuclear power plant is required for determining the life of cables. (author)

  16. 7 CFR 1755.507 - Aerial cable services.

    Science.gov (United States)

    2010-01-01

    ... requirements: (1) Strand supported lashed construction shall be used. (2) Where practicable a 5/16 in. (8 mm...) Construction on poles shall comply with applicable construction drawings for regular line construction. Aerial... copper and fiber optic cables. (4) Where practicable, aerial cable shall pass under electrical guys...

  17. Education and Cable TV: A Guide to Franchising and Utilization.

    Science.gov (United States)

    Shafer, Jon

    Designed to provide the educator with some answers about cable television (CATV), this monograph and resource catalog provides a basic description of CATV, its educational uses, and the franchising provisions which relate to its educational uses. The transition of CATV from an association with broadcast television toward cable information systems…

  18. Distance Protection of Cross-Bonded Transmission Cable-Systems

    DEFF Research Database (Denmark)

    Bak, Claus Leth; F. Jensen, Christian

    2014-01-01

    In this paper the problems of protecting a cross-bonded cable system using distance protection are analysed. The combination of the desire to expand the high voltage transmission grid and the public's opinion towards new installations of overhead lines (OHL), more and more transmission cable syst...

  19. Long-term monitoring FBG-based cable load sensor

    Science.gov (United States)

    Zhang, Zhichun; Zhou, Zhi; Wang, Chuan; Ou, Jinping

    2006-03-01

    Stay cables are the main load-bearing components of stayed-cable bridges. The cables stress status is an important factor to the stayed-cable bridge structure safety evaluation. So it's very important not only to the bridge construction, but also to the long-term safety evaluation for the bridge structure in-service. The accurate measurement for cable load depends on an effective sensor, especially to meet the long time durability and measurement demand. FBG, for its great advantage of corrosion resistance, absolute measurement, high accuracy, electro-magnetic resistance, quasi-distribution sensing, absolute measurement and so on, is the most promising sensor, which can cater for the cable force monitoring. In this paper, a load sensor has been developed, which is made up of a bushing elastic supporting body, 4 FBGs uniformly-spaced attached outside of the bushing supporting body, and a temperature compensation FBG for other four FBGs, moreover a cover for protection of FBGs. Firstly, the sensor measuring principle is analyzed, and relationship equation of FBG wavelength shifts and extrinsic load has also been gotten. And then the sensor calibration experiments of a steel cable stretching test with the FBG load sensor and a reference electric pressure sensor is finished, and the results shows excellent linearity of extrinsic load and FBG wavelength shifts, and good repeatability, which indicates that such kind of FBG-based load sensor is suitable for load measurement, especially for long-term, real time monitoring of stay-cables.

  20. Shape modification of bridge cables for aerodynamic vibration control

    DEFF Research Database (Denmark)

    Kleissl, Kenneth; Georgakis, Christos

    2010-01-01

    In this paper, the viability of modifying cable shape and surface for the purpose of controlling wind-induced vibrations is examined. To this end, an extensive wind-tunnel test campaign was carried out on various cable sections in the critical Reynolds number region under both smooth and turbulen...

  1. On stiffening cables of a long reach manipulator

    International Nuclear Information System (INIS)

    Wang, S.L.; Santiago, P.

    1996-01-01

    A long reach manipulator will be used for waste remediation in large underground storage tanks. The manipulator's slenderness makes it flexible and difficult to control. A low-cost and effective method to enhance the manipulator's stiffness is proposed in this research by using suspension cables. These cables can also be used to accurately measure the position of the manipulator's wrist

  2. Advanced nuclear power plant design with minimized use of cables

    International Nuclear Information System (INIS)

    Anon.

    1984-01-01

    The objective of this report is to present a nuclear power plant design with a minimum utilization of cables. The report describes the types of software and hardware that will be needed to minimize hard-wired control and instrumentation circuits and to reduce the quantity of low voltage power cables while maintaining a high availability and reliability of the plant control systems

  3. Reducing Actuator Requirements in Continuum Robots Through Optimized Cable Routing.

    Science.gov (United States)

    Case, Jennifer C; White, Edward L; SunSpiral, Vytas; Kramer-Bottiglio, Rebecca

    2018-02-01

    Continuum manipulators offer many advantages compared to their rigid-linked counterparts, such as increased degrees of freedom and workspace volume. Inspired by biological systems, such as elephant trunks and octopus tentacles, many continuum manipulators are made of multiple segments that allow large-scale deformations to be distributed throughout the body. Most continuum manipulators currently control each segment individually. For example, a planar cable-driven system is typically controlled by a pair of cables for each segment, which implies two actuators per segment. In this article, we demonstrate how highly coupled crossing cable configurations can reduce both actuator count and actuator torque requirements in a planar continuum manipulator, while maintaining workspace reachability and manipulability. We achieve highly coupled actuation by allowing cables to cross through the manipulator to create new cable configurations. We further derive an analytical model to predict the underactuated manipulator workspace and experimentally verify the model accuracy with a physical system. We use this model to compare crossing cable configurations to the traditional cable configuration using workspace performance metrics. Our work here focuses on a simplified planar robot, both in simulation and in hardware, with the goal of extending this to spiraling-cable configurations on full 3D continuum robots in future work.

  4. Elasticity and mechanical advantage in cables and ropes

    International Nuclear Information System (INIS)

    O'Shea, M J

    2007-01-01

    The conditions under which one can gain mechanical advantage by pulling with a force F perpendicular to a cable (or rope) that is fixed at both ends are examined. While this is a commonly discussed example in introductory physics classes, its solution in terms of fundamental properties of the cable requires one to model the elasticity of the cable. This solution has several complex and interesting features, e.g. a large increase in the tension in the cable may occur upon application of F if (i) F lies in a certain range and (ii) the initial tension T 1 in the cable (before F is applied) satisfies T 1 < 0.0340 κ. Here, κ is the spring constant of a unit length of the cable. For steel cables and cables composed of other materials such as carbon nanorods where the elasticity is low, significant increases in tension are possible. Examples involving walking a tightrope and attempting to increase the tension in a rope hauling a load are considered. Two programs to solve the equations of this work are available in the electronic version of this journal

  5. Automation of Underground Cable Laying Equipment Using PLC and Hmi

    Science.gov (United States)

    Mal Kothari, Kesar; Samba, Vishweshwar; Tania, Kinza; Udayakumar, R., Dr; Karthikeyan, Ram, Dr

    2018-04-01

    Underground cable laying is an alternative for overhead cable laying of telecommunication and power transmission lines. It is becoming very popular in recent times because of some of its advantages over overhead cable laying. This type of cable laying is mostly practiced in developed countries because it is more expensive than overhead cable laying. Underground cable laying is more suitable when land is not available, and it also increases the aesthetics. This paper implements the automation on a manually operated cable pulling winch machine using programmable logic controller (PLC). Winch machines are useful in underground cable laying. The main aim of the project is to replace all the mechanical functions with electrical controls which are operated through a touch screen (HMI). The idea is that the machine should shift between parallel and series circuit automatically based on the pressure sensed instead of manually operating the solenoid valve. Traditional means of throttling the engine using lever and wire is replaced with a linear actuator. Sensors such as proximity, pressure and load sensor are used to provide the input to the system. The HMI used will display the speed, length and tension of the rope being winded. Ladder logic is used to program the PLC.

  6. Medium and high voltage power cables market in Europe

    International Nuclear Information System (INIS)

    Kupiec, M.

    1992-06-01

    This note gives an overview of the European market for medium and high voltage power cables. In this text, emphasis is placed on suppliers and important European clients; there is also a brief review of the different techniques for cable laying and utilization in Europe. This not has mainly been drafted from informations supplied by EUROPACABLE

  7. Heat resistant wire and cable and heat shrinkable tubes

    International Nuclear Information System (INIS)

    Keiji Ueno

    1994-01-01

    Radiation processes have been used in industrial fields (e.g. wire and cable, heat shrinkable tubes) for about 30 years. In Japan, 60 electron beam accelerators were used in R and D, 54 in wire and cable, 24 in tire rubber, 16 in paint curing, 14 in PE foam and 9 accelerators were used in heat shrinkable tubes in 1993. Many properties (e.g. solder resistance, thermal deformation, and solven resistance) of wire and cable are improved by using radiation processes, and many kinds of radiation crosslinked wire and cable are used in the consumer market (TV sets, VTR's, audio disc players, etc.), automobiles (automobile wire harnesses, fusible link wires, sensor cables etc.), and the industrial market (computer cables, cables for keyboards, coaxial cables, etc.). Another important industrial application of Eβ radiation process is heat shrinkable tubes. Heat shinkable tubes, heated by a hot gun, shrink 1/2 ∼ 1/3 of their inner diameters. Heat shrinkable tubes are used for covers of distributing line terminals, joint covers of telecommunication lines, protection of fuel pipe lines and so on. In this seminar, actual applications and characteristic properties of radiation crosslinked materials are presented

  8. Ground Loop Impedance of Long EHV Cable Lines

    DEFF Research Database (Denmark)

    Ohno, Teruo; Bak, Claus Leth; Sørensen, Thomas K.

    2012-01-01

    The distance protection scheme without communication is often applied to the backup protection of EHV cable lines. For a reliable operation of a ground distance relay, the ground loop impedance of EHV cable lines needs to have a linear relationship to the distance from the relay location...... to the fault location. The discontinuity of the ground loop impedance at cross-bonding points may have an ill effect on the reliable operation of the ground distance relay. However, the cause and parameters of the discontinuity and its effects on the ground distance relay protection have not been discussed...... in literature. Through the calculation of the ground loop impedance for cable lines, it has been found that, for long EHV cable lines, the reliable operation of the ground distance relay is possible with a typical relay setting. Effects of parameters, such as substation grounding, cable layouts...

  9. Development of low-smoke, flame-retarding cables

    International Nuclear Information System (INIS)

    Kato, H.; Kanemitsuya, K.; Furukawa, K.; Mio, K.

    1983-01-01

    A great deal of attention has been given to the potential fire hazard of combustion gases from organic materials. Although cable industries have developed flame-retarding organic materials for the insulation and jacketing of wires and cables, there was insufficient prevention of toxic gas formation during combustion. To cope with these problems associated with conventional PVC cables, the authors have directed to develop low-smoke, flame-retarding plasticized PVC formulations retaining the original mechanical, electrical and aging properties. A series of basic investigations on smoke suppression followed by an evaluation on practical cables could indicate some effective means to end these problems. This paper describes the results and discussion on smoke suppressing study of plasticized PVC as well as behavior and characteristics of the low-smoke, flame-retarding PVC wires and cables using these materials. (author)

  10. Overcurrent experiments on HTS tape and cable conductor

    DEFF Research Database (Denmark)

    Tønnesen, Ole; Jensen, Kim Høj; Træholt, Chresten

    2001-01-01

    their critical current. In this light, it is important to investigate the response of HTS tapes and cable conductors to overcurrents several times the critical current. A number of experiments have been performed on HTS tapes and cable conductors, with currents up to 20 times the critical current. During...... overcurrent experiments, the voltage, and the temperature were measured as functions of time in order to investigate the dynamic behavior of the HTS tape and cable conductor. After each experiment, damage to the superconductors was assessed by measuring the critical current. Preliminary results show...... that within seconds an HTS tape (critical current=17 A) heats above room temperature with an overcurrent larger than 140 A. Similar overcurrent experiments showed that a HTS cable conductor could sustain damage with overcurrents exceeding 10 times the critical current of the cable conductor....

  11. Cable tray ultimate strength test employing a large shaker table

    Energy Technology Data Exchange (ETDEWEB)

    Komatsu, K.; Myojin, K.; Imai, K. [The Kansai Electric Power Co., Osaka (Japan); Fuyama, H. [Mitsubishi Heavy Industries Ltd, Takasago (Japan); Kokubo, E. [Mitsubishi Heavy Industdries Ltd, Kobe (Japan)

    2004-07-01

    Ultimate behaviors of cable trays, used in nuclear plants, have not been well studied since cable trays are designed based on conservative design criteria. In this study, by employing a large shaker table, an ultimate strength test was conducted for cable trays used in nuclear power plants. This report describes the results of shaker table test. The following results were obtained. First, in an S{sub 2} earthquake, the damping ratio was so large - more than 30% due to the rubbing of cables - that a large response was not present and the strains in the support were within the elastic limits. Secondly, the support was strong enough to sustain the cable trays even when the strain in the support was 20 times larger than the elastic limit. (authors)

  12. Life-assessment technique for nuclear power plant cables

    International Nuclear Information System (INIS)

    Bartonicek, B.; Hnat, V.; Placek, V.

    1998-01-01

    The condition of polymer-based cable material can be best characterized by measuring elongation at break of its insulating materials. However, it is not often possible to take sufficiently large samples for measurement with the tensile testing machine. The problem has been conveniently solved by utilizing differential scanning calorimetry technique. From the tested cable, several microsamples are taken and the oxidation induction time (OIT) is determined. For each cable which is subject to the assessment of the lifetime, the correlation of OIT with elongation at break and the correlation of elongation at break with the cable service time has to be performed. A reliable assessment of the cable lifetime depends on accuracy of these correlations. Consequently, synergistic effects well known at this time - dose rate effects and effects resulting from the different sequence of applying radiation and elevated temperature must be taken into account

  13. Behaviour of French electrical cables under fire conditions

    Energy Technology Data Exchange (ETDEWEB)

    Bertrand, R.; Chaussard, M.; Gonzalez, R.; Lacoue, J.; Mattei, J.M.; Such, J.M

    2001-12-01

    A fire Probabilistic Safety Assessment - called fire PSA - is being carried out by the French Institute of Nuclear Safety and Protection (IPSN) to be used in the framework of the safety assessment of operating 900 MWe PWRs. The aim of this study is to evaluate the core damage conditional probability which could result from a fire. A fire can induce unavailability of safety equipment notably damaging electrical cables that are a significant risk contributor. The purpose of this communication is to present the electrical cable fire tests carried out by IPSN to identify the failure modes and to determine the cable damage criteria. Moreover, are indicated the impact of each kind of cable failure mode and the methodology used to estimate the conditional probability of a failure mode when cable damage occurred. (authors)

  14. MVAC Submarine cable, magnetic fields measurements and analysis

    DEFF Research Database (Denmark)

    Arentsen, Martin Trolle; Expethit, Adrian; Pedersen, Morten Virklund

    2017-01-01

    Standard 60287. Researchers believe that the wire armour of three phased submarine cables is the reason for the inaccurate calculations by the standard. Studies show that the magnetic behaviour of these cables are changed due to the wire armour. In order to investigate this hypothesis, this paper intends...... to supply the theoretical research with data from magnetic field measurements on a wire armoured 3-phase submarine cable, together with an investigation of the induced currents in the different cable components. The influence of the physical arrangement of the armour wires on the electric behaviour is also...... investigated, since several researchers believe that the twisting of the armour wires result in zero net induced voltage over one helix length. This is shown to be valid for the tested cable. Finally a replica of the armour has been built with just a single conductor in the centre. This setup was used...

  15. Development of environmental-friendly wire and cable

    International Nuclear Information System (INIS)

    Ueno, Keiji

    1996-01-01

    The electron beam technology has been used in many industrial fields as a method of conventional polymer modification or optimum processability. The main industrial fields of radiation crosslinking are wire and cable, heat shrinkable tubings, plastic foams, precuring of tires, floppy disk curing, foods packaging films, and so on. The radiation crosslinking of wire and cable was started in 1961 in Japan and 15 wire and cable companies are now using electron beam accelerators for production or R and D. The dominant characteristics of crosslinking of insulation materials are application at high temperature, good oil and chemical resistibility and high mechanical properties. These radiation crosslinking wire and cable are applied widely in electronics equipments and automobiles. Recently, electronics manufacturers have indicated deep concern over the effects on the environment. Wire and cable also are required to be applicable for environmental preservation. (J.P.N.)

  16. Sound cable crossing brings inexpensive electric power to Long Island

    International Nuclear Information System (INIS)

    Grzan, J.; Goyette, R.

    1992-01-01

    This paper reports that while many electric-utility customers in New York State benefit from inexpensive hydroelectric power from Canada and upstate New York, lack of sufficient transmission connections have prevented this electricity from reaching Long Island. However, a newly constructed underground/underwater link capable of carrying 700-MW now transmits low-cost electricity to the island, saving money for customers. The self-contained fluid-filled cable used for the underwater portion of the project is the largest underwater cable in the world. The use of high-pressure, fluid-filled pipe-type cable on the land portion represents the largest application of paper-polypropylene-paper (PPP) insulated cable in the United States. State-of-the-art technologies were implemented in the use of temperature monitoring and leak detection systems, SF 6 gas-insulated substation, and underwater cable laying and embedment techniques

  17. Losses in armoured three-phase submarine cables

    DEFF Research Database (Denmark)

    Ebdrup, Thomas; Silva, Filipe Miguel Faria da; Bak, Claus Leth

    2014-01-01

    The number of offshore wind farms will keep increasing in the future as a part of the shift towards a CO2 free energy production. The energy harvested from the wind farm must be brought to shore, which is often done by using a three-phase armoured submarine power cable. The use of an armour...... increases the losses in armoured cables compared to unarmoured cables. In this paper a thorough state of the art analysis is conducted on armour losses in three-phase armoured submarine power cables. The analysis shows that the IEC 60287-1-1 standard overestimates the armour losses which lead...... to the installation of cables with excessive phase conductor cross section. This paper also presents an example of the potential economic benefits of having a better knowledge of the losses introduced by the armour....

  18. Potential Impact of Submarine Power Cables on Crab Harvest

    Science.gov (United States)

    Bull, A. S.; Nishimoto, M.

    2016-02-01

    Offshore renewable energy installations convert wave or wind energy to electricity and transfer the power to shore through transmission cables laid on or buried beneath the seafloor. West coast commercial fishermen, who harvest the highly prized Dungeness crab (Metacarcinus magister) and the rock crab (Cancer spp.), are concerned that the interface of crabs and electromagnetic fields (EMF) from these cables will present an electrified fence on the seafloor that their target resource will not cross. Combined with the assistance of professional fishermen, submarine transmission cables that electrify island communities and offshore oil platforms in the eastern Pacific provide an opportunity to test the harvest of crab species across power transmission cables. In situ field techniques give commercial crab species a choice to decide if they will cross fully energized, EMF emitting, power transmission cables, in response to baited traps. Each independent trial is either one of two possible responses: the crab crosses the cable to enter a trap (1) or the crab does not cross the cable to enter a trap (0). Conditions vary among sample units by the following categorical, fixed factors (i.e., covariates) of cable structure (buried or unburied); direction of cable from crab position (west or east, north or south); time and season. A generalized linear model is fit to the data to determine whether any of these factors affect the probability of crabs crossing an energized cable to enter baited traps. Additionally, the experimental design, aside from the number of runs (set of sample trials) and the dates of the runs, is the same in the Santa Barbara Channel for rock crab and Puget Sound for Dungeness crab, and allows us to compare the capture rates of the two species in the two areas. We present preliminary results from field testing in 2015.

  19. Cable-to-post attachments for use in non-proprietary high-tension cable median barrier - phase II.

    Science.gov (United States)

    2016-03-24

    The objective of this study was to reevaluate and improve the existing cable-to-post attachment hardware that is utilized : in the non-proprietary cable barrier being developed at MwRSF. The study focused on redesigning the bolted, tabbed : bracket (...

  20. Aerodynamics of the cable of cable-stayed bridges; Shachokyo cable no kuriki shindo tokusei no rikai to soreni motozuku kuriki seishinho no teian

    Energy Technology Data Exchange (ETDEWEB)

    Matsumoto, M. [Kyoto University, Kyoto (Japan). Faculty of Engineering; Aoki, J.; Fuji, D. [West Japan Railway Company, Osaka (Japan); Kitayama, N. [Ishikawajima-Harima Heavy Industries Co. Ltd., Tokyo (Japan); Daito, Y. [Kyoto University, Kyoto (Japan)

    1996-07-21

    Wind tunnel tests were conducted assuming the aerodynamics of the cable of cable-stayed bridges especially in the case of strong wind with rain. Based on the results, an aerodynamic damping method was proposed. Factors of the rain vibration generation include the three-dimensional axial flow behind the cable, which is formed by the wind direction deviation angle, the upper side water flow on the cable surface formed by the rain, and the Karman vortex shedding, which are not uniform in the span direction. Newly proposed cable with elliptical plates showed an effective dumping performance. It restrains the formation of water flow due to its profile, and is effective for unstableness due to water flow formation. Distribution of the axial flow in the cable span direction was made clear. Three-dimensionality of the vortex shedding was greatly affected by this axial flow. Frequency of the Karman vortex shedding changed in the wide band by the axial flow. It was suggested that three-dimensionality of the flow field is enhanced by the rolling vibration, resulting in the unstableness of heaving vibration. 5 refs., 15 figs.

  1. Design of anti-theft/cable cut real time alert system for copper cable using microcontroller and GSM technology

    Science.gov (United States)

    Lim, E. K.; Norizan, M. N.; Mohamad, I. S.; Yasin, M. N. M.; Murad, S. A. Z.; Baharum, N. A.; Jamalullail, N.

    2017-09-01

    This paper presents the design of anti-theft/cable cut real time alert system using microcontroller and GSM technology. The detection part is using the electrical circuit wire connection in detecting the voltage drop of the cable inside the microcontroller digital input port. The GSM wireless modem is used to send the location of cable cut directly to the authority mobile phone. Microcontroller SK40C with Microchip PIC16F887 is used as a controller to control the wireless modem and also the detection device. The device is able to detect and display the location of the cable cut on the LCD display besides of and sending out the location of the cable break to the authority mobile phone wirelessly via SMS.

  2. Effect of Concrete Creep on the displacement of single tower single cable plane Extradosed Cable-stayed Bridge

    Science.gov (United States)

    Shi, Jing-xian; Ran, Zhi-hong

    2018-03-01

    Extradossed Cable-stayed Bridge is both cable-stayed Bridge and Continuous rigid frame bridge mechanics feature, Beam is the main force components, cable is supplement.This article combined with a single tower and single cable plane Extradossed cable-stayed bridge in Yunnan, use different creep calculation models and analysis deflection caused by creep effects. The results showing that deflection caused by creep effect is smaller than the same span continuous rigid frame bridge, the value is about 2cm. On the other hand the deflection is increasing with ambient humidity decreases, therefore in the dry environment the calculation model is relatively large in the pre-camber. In the choice of RC creep model is significant in the dry areas.

  3. Improved practical formulas for estimation of cable tension by vibration method; Shindoho ni yoru cable choryoku jitsuyo santeishiki no hosei

    Energy Technology Data Exchange (ETDEWEB)

    Zui, H. [Setsunan University, Osaka (Japan). Faculty of Engineering; Shinke, T. [Kobe Technical College, Kobe, Kobe (Japan); Hamazaki, Y. [Kobe Steel, Ltd., Kobe (Japan)

    1995-10-21

    The vibration method is usually utilized on the measurement of cable tension during construction of cable bridge such as Nielsen bridges or cable stayed bridges. Practical formula for the vibration method previously proposed by authors is often used where bending rigidity is taken into account. These formula, however, have a certain limit of application and do not yield good results when the cable is not slender or not enough mentioned. The practical formula is modified to improve the accuracy and new formulas are made. The new practical formulas are applicable to any cables, regardless of its length and tension in it. The accuracy is confirmed through comparison of the value obtained by practical formulas with measured values and calculated value by F.E.M. 2 refs., 4 figs., 1 tab.

  4. PCACE- PERSONAL COMPUTER AIDED CABLING ENGINEERING

    Science.gov (United States)

    Billitti, J. W.

    1994-01-01

    A computerized interactive harness engineering program has been developed to provide an inexpensive, interactive system which is designed for learning and using an engineering approach to interconnection systems. PCACE is basically a database system that stores information as files of individual connectors and handles wiring information in circuit groups stored as records. This directly emulates the typical manual engineering methods of data handling, thus making the user interface to the program very natural. Data files can be created, viewed, manipulated, or printed in real time. The printed ouput is in a form ready for use by fabrication and engineering personnel. PCACE also contains a wide variety of error-checking routines including connector contact checks during hardcopy generation. The user may edit existing harness data files or create new files. In creating a new file, the user is given the opportunity to insert all the connector and harness boiler plate data which would be part of a normal connector wiring diagram. This data includes the following: 1) connector reference designator, 2) connector part number, 3) backshell part number, 4) cable reference designator, 5) cable part number, 6) drawing revision, 7) relevant notes, 8) standard wire gauge, and 9) maximum circuit count. Any item except the maximum circuit count may be left blank, and any item may be changed at a later time. Once a file is created and organized, the user is directed to the main menu and has access to the file boiler plate, the circuit wiring records, and the wiring records index list. The organization of a file is such that record zero contains the connector/cable boiler plate, and all other records contain circuit wiring data. Each wiring record will handle a circuit with as many as nine wires in the interface. The record stores the circuit name and wire count and the following data for each wire: 1) wire identifier, 2) contact, 3) splice, 4) wire gauge if different from standard

  5. Vertical Cable Seismic Survey for Hydrothermal Deposit

    Science.gov (United States)

    Asakawa, E.; Murakami, F.; Sekino, Y.; Okamoto, T.; Ishikawa, K.; Tsukahara, H.; Shimura, T.

    2012-04-01

    The vertical cable seismic is one of the reflection seismic methods. It uses hydrophone arrays vertically moored from the seafloor to record acoustic waves generated by surface, deep-towed or ocean bottom sources. Analyzing the reflections from the sub-seabed, we could look into the subsurface structure. This type of survey is generally called VCS (Vertical Cable Seismic). Because VCS is an efficient high-resolution 3D seismic survey method for a spatially-bounded area, we proposed the method for the hydrothermal deposit survey tool development program that the Ministry of Education, Culture, Sports, Science and Technology (MEXT) started in 2009. We are now developing a VCS system, including not only data acquisition hardware but data processing and analysis technique. Our first experiment of VCS surveys has been carried out in Lake Biwa, JAPAN in November 2009 for a feasibility study. Prestack depth migration is applied to the 3D VCS data to obtain a high quality 3D depth volume. Based on the results from the feasibility study, we have developed two autonomous recording VCS systems. After we carried out a trial experiment in the actual ocean at a water depth of about 400m and we carried out the second VCS survey at Iheya Knoll with a deep-towed source. In this survey, we could establish the procedures for the deployment/recovery of the system and could examine the locations and the fluctuations of the vertical cables at a water depth of around 1000m. The acquired VCS data clearly shows the reflections from the sub-seafloor. Through the experiment, we could confirm that our VCS system works well even in the severe circumstances around the locations of seafloor hydrothermal deposits. We have, however, also confirmed that the uncertainty in the locations of the source and of the hydrophones could lower the quality of subsurface image. It is, therefore, strongly necessary to develop a total survey system that assures a accurate positioning and a deployment techniques

  6. Status of the segment interconnect, cable segment ancillary logic, and the cable segment hybrid driver projects

    International Nuclear Information System (INIS)

    Swoboda, C.; Barsotti, E.; Chappa, S.; Downing, R.; Goeransson, G.; Lensy, D.; Moore, G.; Rotolo, C.; Urish, J.

    1985-01-01

    The FASTBUS Segment Interconnect (SI) provides a communication path between two otherwise independent, asynchronous bus segments. In particular, the Segment Interconnect links a backplane crate segment to a cable segment. All standard FASTBUS address and data transactions can be passed through the SI or any number of SIs and segments in a path. Thus systems of arbitrary connection complexity can be formed, allowing simultaneous independent processing, yet still permitting devices associated with one segment to be accessed from others. The model S1 Segment Interconnect and the Cable Segment Ancillary Logic covered in this report comply with all the mandatory features stated in the FASTBUS specification document DOE/ER-0189. A block diagram of the SI is shown

  7. An Assembly Line Balancing Problem Automotive Cables

    Directory of Open Access Journals (Sweden)

    Triki Hager

    2015-02-01

    Full Text Available In this paper, an Assembly Line Balancing Problem (ALBP is presented in a real-world automotive cables manufacturer company. This company found it necessary to balance its line, since it needs to increase the production rate. In this ALBP, the number of stations is known and the objective is to minimize cycle time where both precedence and zoning constrains must be satisfied. This problem is formulated as a binary linear program (BLP. Since this problem is NP-hard, an innovative Genetic Algorithm (GA is implemented. The full factorial design is used to obtain the better combination GA parameters and a simple convergence experimental study is performed on the stopping criteria to reduce computational time. Comparison of the proposed GA results with CPLEX software shows that, in a reasonable time, the GA generates consistent solutions that are very close to their optimal ones. Therefore, the proposed GA approach is very effective and competitive.

  8. Hall probe magnetometer for SSC magnet cables

    International Nuclear Information System (INIS)

    Cross, R.W.; Goldfarb, R.B.

    1991-01-01

    The authors of this paper constructed a Hall probe magnetometer to measure the magnetization hysteresis loops of Superconducting Super Collider magnet cables. The instrument uses two Hall-effect field sensors to measure the applied field H and the magnetic induction B. Magnetization M is calculated from the difference of the two quantities. The Hall probes are centered coaxially in the bore of a superconducting solenoid with the B probe against the sample's broad surface. An alternative probe arrangement, in which M is measured directly, aligns the sample probe parallel to the field. The authors measured M as a function of H and field cycle rate both with and without a dc transport current. Flux creep as a function of current was measured from the dependence of ac loss on the cycling rate and from the decay of magnetization with time. Transport currents up to 20% of the critical current have minimal effect on magnetization and flux creep

  9. Temperature rise of cyclicly loaded power cables

    Energy Technology Data Exchange (ETDEWEB)

    Brakelmann, H

    1984-09-01

    A calculation method for the current ratings of cyclicly loaded power cables is introduced, taking into account optional shapes of the load cycle as well as the drying-out of the soil. The method is based on the Fourier-analysis of the loss cycle, representing an extension of the calculation method of VDE 0298. It is shown, that the ''VDE-method'' gives good results for the thermal resistances, if an ''utility load cycle'' in accordance with VDE 0298 is supposed. Only for cycles deviating essentially from the utility load cycle, the thermal resistances calculated by the ''VDE-method'' may be too great. In these cases the represented method is advantageous and can be processed by the aid of microcomputers.

  10. Local Distribution Fiber Optic Cable Communication System.

    Science.gov (United States)

    1981-03-20

    T 1 0 1 72 2304 T 1 0 0 36 1152 T 0 1 1 18 576 T 0 1 0 9 288 T 0 0 1 128 4096 S 1 1 0 64 2048 S 1 0 1 48 1536 S 1 0 0 32 1024 S 0 1 1 16 512 S 0 1 0a...channels. For 32 kb/s channels, the trunk transmission rates are 256, 288, 512, 576, 1024, 1152, 1536, 2048 , and 2304 kb/s. The DGM functions as...connectors will remain mated, even under transport conditions. In the MP shelter, power cables are drawn from the VDI /CAP nest. Extra flexible hook-up

  11. Design and Trajectory Analysis of Incompletely Restrained Cable-Suspension Swing System Driven by Two Cables

    Directory of Open Access Journals (Sweden)

    Naige Wang

    2015-12-01

    Full Text Available In order to simulate the swing conditions of a suspended platform of a construction shaft, marine ships, cars, etc., an incompletely restrained cable-suspension swing system driven by two cables (IRCSWs2 was designed and parameter trajectories of displacements, angles and tensions were systematically investigated. Firstly, the motion mechanism of the IRCSWs2 is described and the corresponding kinematic model is established. For further evaluating the analytical expressions, the ADAMS simulation model and the physical prototype experimental model were developed. The basic consistency and slight difference among the three models are illustrated by a comparison of different parameters. The approximately linear relationship between the driving displacements of two cables and the swing angles of the platform was obtained. Finally, the effects of various parameters on displacements, angles and tensions were analysed, and the results indicate that the translation of a suspended platform is slight during its swing and that the novel IRCSWs2 can be used to drive heavy loads using a relatively small driving force, which is useful for simulating swing environmental conditions long-term, in addition to being cost-effective.

  12. Solid-cryogen-stabilized, cable-in-conduit (CIC) superconducting cables

    Science.gov (United States)

    Voccio, J. P.; Michael, P. C.; Bromberg, L.; Hahn, S.

    2015-12-01

    This paper considers the use of a solid cryogen as a means to stabilize, both mechanically and thermally, magnesium diboride (MgB2) superconducting strands within a dual-channel cable-in-conduit (CIC) cable for use in AC applications, such as a generator stator winding. The cable consists of two separate channels; the outer channel contains the superconducting strands and is filled with a fluid (liquid or gas) that becomes solid at the device operating temperature. Several options for fluid will be presented, such as liquid nitrogen, hydrocarbons and other chlorofluorocarbons (CFCs) that have a range of melting temperatures and volumetric expansions (from solid at operating temperature to fixed volume at room temperature). Implications for quench protection and conductor stability, enhanced through direct contact with the solid cryogen, which has high heat capacity and thermal conductivity (compared with helium gas), will be presented. Depending on the cryogen, the conductor will be filled initially either with liquid at atmospheric conditions or a gas at high pressure (∼100 atm). After cooldown, the cryogen in the stranded-channel will be solid, essentially locking the strands in place, preventing strand motion and degradation due to mechanical deformation while providing enhanced thermal capacity for stability and protection. The effect of cryogen porosity is also considered. The relatively high heat capacity of solid cryogens at these lower temperatures (compared to gaseous helium) enhances the thermal stability of the winding. During operation, coolant flow through the open inner channel will minimize pressure drop.

  13. MR damping system on Dongting Lake cable-stayed bridge

    Science.gov (United States)

    Chen, Z. Q.; Wang, X. Y.; Ko, J. M.; Ni, Y. Q.; Spencer, Billie F., Jr.; Yang, G.

    2003-08-01

    The Dongting Lake Bridge is a cable-stayed bridge crossing the Dongting Lake where it meets the Yangtze River in southern central China. After this bridge was completed in 1999, its cables were observed to be sensitive to rain-wind-induced vibration, especially under adverse weather conditions of both rain and wind. To investigate the possibility of using MR damping systems to reduce cable vibration, a joint project between the Central South University of China and the Hong Kong Polytechnic University was conducted. Based on the promising research results, the bridge authority decided to install MR damping systems on the longest 156 stay cables. The installation started in July 2001 and finished in June 2002, making it the world's first application of MR dampers on cable-stayed bridge to suppress the rain-wind-induced cable vibration. As a visible and permanent aspect of bridge, the MR damping system must be aesthetically pleasing, reliable, durable, easy to maintain, as well as effective in vibration mitigation. Substantial work was done to meet these requirements. This paper describes the implementation of MR damping systems for cable vibration reduction.

  14. Thin film conductors for self-equalizing cables

    Science.gov (United States)

    Owen, G.; Trutna, W. R.; Orsley, T. J.; Lucia, F.; Daly, C. B.

    2017-10-01

    Self-equalizing cables using hollow conductors with wall thickness less than the skin depth were proposed in 1929. However, they do not appear ever to have been widely used, although the idea has resurfaced and been refined from time to time. In the early 2000's, self-equalizing conductors consisting of solid magnetic steel cores coated with silver were developed by W.L. Gore, and used in their 2.5 Gb/s "Eye-Opener" cables, although higher speed versions never appeared. We have revived the original 1929 idea, proposing to use glass as a solid insulating core. This technology can potentially work at frequencies of many 10's of GHz. Possible uses include short range GHz links such as USB and Thunderbolt, and intra-rack interconnections in data centers. Our feasibility experiments have validated the principle. Copper coated glass fibers can, in principle, be manufactured, but in these tests, the conductors were capillaries internally coated with silver as these are easily obtainable, relatively inexpensive and serve to test the concept. The performance of these experimental twin lead cables corresponds to calculations, confirming the general principle. By calculation, we have compared the performance of cables made from copper-on-insulator conductors to that of similar cables made with solid copper conductors, and verified that copper-on-insulator cables have significantly less frequency dependent loss. We have also made and tested cables with copper on PEEK conductors as surrogates for copper on glass fiber.

  15. Versatile cable handling mechanisms for remote operator control

    Energy Technology Data Exchange (ETDEWEB)

    Collie, A.A.; White, T.S.; Christopher, M.D.; Hewer, N.D. [Portech Ltd., Portsmouth (United Kingdom)

    1996-12-31

    This paper describes a system of cable management for keeping the umbilical cables of remote operating vehicles and manipulators tidy and contained without direct intervention by operators. Two distinct types of winding mechanism have been designed. One mechanism is a fixed reel type where the cable is wound onto the reel by a rotating bail arm. The other mechanism consists of a pair of curved belts held against each other between which cable is passed. The complete system includes tension measuring and slack loop take-up devices. The whole system is controlled by a servo system in conjunction with a PC based visual graphic environment which allows a variety of mechanisms to be built up into a system able to handle up to four umbilical cables simultaneously. The control system provides additional tension sensors and cable odometers connected to the control system so that the operator has immediate perception of all the cable parameters, and by defining rules, can set up a variety of alarm situations. (Author).

  16. Versatile cable handling mechanisms for remote operator control

    International Nuclear Information System (INIS)

    Collie, A.A.; White, T.S.; Christopher, M.D.; Hewer, N.D.

    1996-01-01

    This paper describes a system of cable management for keeping the umbilical cables of remote operating vehicles and manipulators tidy and contained without direct intervention by operators. Two distinct types of winding mechanism have been designed. One mechanism is a fixed reel type where the cable is wound onto the reel by a rotating bail arm. The other mechanism consists of a pair of curved belts held against each other between which cable is passed. The complete system includes tension measuring and slack loop take-up devices. The whole system is controlled by a servo system in conjunction with a PC based visual graphic environment which allows a variety of mechanisms to be built up into a system able to handle up to four umbilical cables simultaneously. The control system provides additional tension sensors and cable odometers connected to the control system so that the operator has immediate perception of all the cable parameters, and by defining rules, can set up a variety of alarm situations. (Author)

  17. Versatile cable handling mechanisms for remote operator control

    International Nuclear Information System (INIS)

    Collie, A.A.; White, T.S.; Christopher, M.D.; Hewer, N.D.

    1996-01-01

    This paper describes a system of cable management for keeping the umbilical cables of remote operating vehicles and manipulators tidy and contained without direct intervention by operators. Two distinct types of winding mechanism have been designed. One mechanism is a fixed reel type where the cable is wound onto the reel by a rotating bail arm. The other mechanism consists of a pair of curved belts held against each other, between which cable is passed. The complete system includes tension measuring and slack loop take-up devices. The whole system is controlled by a servo system in conjunction with a PC based visual graphic environment which allows a variety of mechanisms to be built up into a system able to handle up to four umbilical cables simultaneously. The control system provides additional tension sensors and cable odometers connected to the control system so that the operator has immediate perception of all the cable parameters, and by defining rules, can set up a variety of alarm situations. (UK)

  18. Longest cable-stayed bridge TATARA; Longest shachokyo Tatara Ohashi

    Energy Technology Data Exchange (ETDEWEB)

    Fujii, K. [Hiroshima University, Hiroshima (Japan). Faculty of Engineering

    1998-06-15

    The world`s longest cable-stayed bridge Tatara having a central span of 890 m had the both ends closed in August 1997, linking Namakuchi Island and Omishima Island. Final finishing work is continuing for opening of the West Seto Expressway in the spring of 1999. A cable-stayed bridge supports the bridge girders by perpendicular components of tensile force of cables stayed obliquely. On the other hand, there is a concern that the girders may have axial compression force generated due to horizontal components of the force from the cable tensile force, which can cause buckling of the girders. Therefore, in order to suspend the girders efficiently by increasing the perpendicular components of the cable force, and moreover to suppress the axial compression force on the girders, it is more advantageous to make bridge towers high, hence the towers of this bridge are highest among the bridges on the Shimanami Ocean Road. This bridge whose long girders are stayed with 21-stage multi cables presented a problem in designing the buckling in steel girders near the towers due to the horizontal components of the force generated by the bridge. Discussions were given, therefore, by using load withstanding force experiments using a whole bridge model of 1/50 scale, buckling experiments on full-size reinforcing plate models, and load withstanding force analysis using a tower model. A number of other technical discussions were repeated, by which the world`s longest cable-stayed bridge was completed. 9 figs., 1 tab.

  19. Improving greater trochanteric reattachment with a novel cable plate system.

    Science.gov (United States)

    Baril, Yannick; Bourgeois, Yan; Brailovski, Vladimir; Duke, Kajsa; Laflamme, G Yves; Petit, Yvan

    2013-03-01

    Cable-grip systems are commonly used for greater trochanteric reattachment because they have provided the best fixation performance to date, even though they have a rather high complication rate. A novel reattachment system is proposed with the aim of improving fixation stability. It consists of a Y-shaped fixation plate combined with locking screws and superelastic cables to reduce cable loosening and limit greater trochanter movement. The novel system is compared with a commercially available reattachment system in terms of greater trochanter movement and cable tensions under different greater trochanteric abductor application angles. A factorial design of experiments was used including four independent variables: plate system, cable type, abductor application angle, and femur model. The test procedure included 50 cycles of simultaneous application of an abductor force on the greater trochanter and a hip force on the femoral head. The novel plate reduces the movements of a greater trochanter fragment within a single loading cycle up to 26%. Permanent degradation of the fixation (accumulated movement based on 50-cycle testing) is reduced up to 46%. The use of superelastic cables reduces tension loosening up to 24%. However this last improvement did not result in a significant reduction of the grater trochanter movement. The novel plate and cables present advantages over the commercially available greater trochanter reattachment system. The plate reduces movements generated by the hip abductor. The superelastic cables reduce cable loosening during cycling. Both of these positive effects could decrease the risks related to grater trochanter non-union. Copyright © 2012 IPEM. Published by Elsevier Ltd. All rights reserved.

  20. Current distribution in Cable-In-Conduit Conductors

    International Nuclear Information System (INIS)

    Ferri, M.A.

    1994-05-01

    A numerical study of the current distribution in Cable-In-Conduit Conductors (CICC's) experiencing linearly ramping transport currents and transverse magnetic fields was conducted for both infinitely long, periodic cables and finite length cables terminated in low resistance joints. The goal of the study was to gain insight into the phenomenon known as Ramp Rate Limitation, an as yet unexplained correspondence between maximum attainable current and the ramp time taken to reach that current in CICC superconducting magnets. A discrete geometric model of a 27 strand multiply twisted CICC was developed to effectively represent the flux linkages, mutual inductances, and resistive contact points between the strands of an experimentally tested cable. The results of the numerical study showed that for fully periodic cables, the current imbalances due to ramping magnetic fields and ramping transport currents are negligible in the range of experimentally explored operating conditions. For finite length, joint terminated cables, however, significant imbalances can exist. Unfortunately, quantitative results are limited by a lack of knowledge of the transverse resistance between strands in the joints. Nonetheless, general results are presented showing the dependency of the imbalance on cable length, ramp time, and joint resistance for both ramping transverse magnet fields and ramping transport currents. At the conclusion of the study, it is suggested that calculated current imbalances in a finite length cable could cause certain strands to prematurely ''quench'' -- become non-superconducting --thus leading to an instability for the entire cable. This numerically predicted ''current imbalance instability'' is compared to the experimentally observed Ramp Rate Limitation for the 27 strand CICC sample

  1. Rotator cuff tendon connections with the rotator cable.

    Science.gov (United States)

    Rahu, Madis; Kolts, Ivo; Põldoja, Elle; Kask, Kristo

    2017-07-01

    The literature currently contains no descriptions of the rotator cuff tendons, which also describes in relation to the presence and characteristics of the rotator cable (anatomically known as the ligamentum semicirculare humeri). The aim of the current study was to elucidate the detailed anatomy of the rotator cuff tendons in association with the rotator cable. Anatomic dissection was performed on 21 fresh-frozen shoulder specimens with an average age of 68 years. The rotator cuff tendons were dissected from each other and from the glenohumeral joint capsule, and the superior glenohumeral, coracohumeral, coracoglenoidal and semicircular (rotator cable) ligaments were dissected. Dissection was performed layer by layer and from the bursal side to the joint. All ligaments and tendons were dissected in fine detail. The rotator cable was found in all specimens. It was tightly connected to the supraspinatus (SSP) tendon, which was partly covered by the infraspinatus (ISP) tendon. The posterior insertion area of the rotator cable was located in the region between the middle and inferior facets of the greater tubercle of the humerus insertion areas for the teres minor (TM), and ISP tendons were also present and fibres from the SSP extended through the rotator cable to those areas. The connection between the rotator cable and rotator cuff tendons is tight and confirms the suspension bridge theory for rotator cuff tears in most areas between the SSP tendons and rotator cable. In its posterior insertion area, the rotator cable is a connecting structure between the TM, ISP and SSP tendons. These findings might explain why some patients with relatively large rotator cuff tears can maintain seamless shoulder function.

  2. Aerodynamic instability of cables in transmission power lines; Inestabilidad aerodinamica en cables de lineas de transmision

    Energy Technology Data Exchange (ETDEWEB)

    Lopez Lopez, Alberto; Vilar Rojas, Jorge Ivan; Munoz Black, Celso J. [Instituto de Investigaciones Electricas, Cuernavaca (Mexico)

    1995-12-31

    One of the aerodynamic instabilities of transmission power lines cables is galloping, which consists in the appearance of important cable vibrations, mainly when the wind hits orthogonally the power line. In some cases the maximum amplitude that occurs reaches several meters, even when the wind velocities in a region are well below the value used for the mechanical design of the power lines. In general terms, galloping is associated with particular climatic conditions such as low temperatures and high humidities. In these conditions a coating of ice that adheres to the cable is formed, changing its transverse cross section, propitiating the galloping, although some authors have reported galloping without ice. These climatic conditions are presented mainly in the Northern part of our country and in the high regions of the mountain zones; nevertheless, the galloping phenomenon has been reported in few cases by Comision Federal de Electricidad (CFE). The possible expansion of the power lines in these regions of the country leads to prevent the measures needed to diminish the appearance of this phenomenon. In this paper mention is made in particular of the solution adopted to the galloping problem that has appeared in the transmission power line of Salamayuca to Reforma, Ciudad Juarez, Chihuahua (CFE,1991). [Espanol] Una de las inestabilidades aerodinamicas que se presentan en los cables de lineas de transmision es el galopeo, el cual consiste en la aparicion de vibraciones importantes de los cables, sobre todo cuando el flujo del viento incide ortogonalmente a la linea. En algunos casos las amplitudes maximas que se presentan llegan a ser de varios metros, aun cuando las velocidades del viento en una region esten muy por debajo del valor empleado para el diseno mecanico de las lineas. Generalmente, el galopeo se asocia con condiciones climaticas particulares como son las bajas temperaturas y altas humedades. En estas condiciones se forma una cubierta de hielo que se

  3. Aerodynamic instability of cables in transmission power lines; Inestabilidad aerodinamica en cables de lineas de transmision

    Energy Technology Data Exchange (ETDEWEB)

    Lopez Lopez, Alberto; Vilar Rojas, Jorge Ivan; Munoz Black, Celso J [Instituto de Investigaciones Electricas, Cuernavaca (Mexico)

    1996-12-31

    One of the aerodynamic instabilities of transmission power lines cables is galloping, which consists in the appearance of important cable vibrations, mainly when the wind hits orthogonally the power line. In some cases the maximum amplitude that occurs reaches several meters, even when the wind velocities in a region are well below the value used for the mechanical design of the power lines. In general terms, galloping is associated with particular climatic conditions such as low temperatures and high humidities. In these conditions a coating of ice that adheres to the cable is formed, changing its transverse cross section, propitiating the galloping, although some authors have reported galloping without ice. These climatic conditions are presented mainly in the Northern part of our country and in the high regions of the mountain zones; nevertheless, the galloping phenomenon has been reported in few cases by Comision Federal de Electricidad (CFE). The possible expansion of the power lines in these regions of the country leads to prevent the measures needed to diminish the appearance of this phenomenon. In this paper mention is made in particular of the solution adopted to the galloping problem that has appeared in the transmission power line of Salamayuca to Reforma, Ciudad Juarez, Chihuahua (CFE,1991). [Espanol] Una de las inestabilidades aerodinamicas que se presentan en los cables de lineas de transmision es el galopeo, el cual consiste en la aparicion de vibraciones importantes de los cables, sobre todo cuando el flujo del viento incide ortogonalmente a la linea. En algunos casos las amplitudes maximas que se presentan llegan a ser de varios metros, aun cuando las velocidades del viento en una region esten muy por debajo del valor empleado para el diseno mecanico de las lineas. Generalmente, el galopeo se asocia con condiciones climaticas particulares como son las bajas temperaturas y altas humedades. En estas condiciones se forma una cubierta de hielo que se

  4. Effects of Various Factors on the Viv-Induced Fatigue Damage In The Cable Of Submerged Floating Tunnel

    Directory of Open Access Journals (Sweden)

    Luoa Gang

    2015-12-01

    Full Text Available According to the modal superposition method, the vortex vibration procedure of submerged floating tunnel cable was compiled using Matlab, based on the calculated results, the fatigue damage was predicted. The effects of various factors, such as cable density, cable length, and pretension and velocity distribution on vortex induced fatigue damage in the cable were studied. The results show that velocity distribution has more effect on the cable fatigue damage than cable length, cable density and pre-tension. Secondly, cable length has also relatively effect on the cable damage fatigue, cable density and pretension has limited in a certain range.

  5. Experimental Investigation of Aerodynamic Instability of Iced Bridge Cable Sections

    DEFF Research Database (Denmark)

    Koss, Holger; Lund, Mia Schou Møller

    2013-01-01

    The accretion of ice on structural bridge cables changes the aerodynamic conditions of the surface and influences hence the acting wind load process. Full-scale monitoring indicates that light precipitation at moderate low temperatures between zero and -5°C may lead to large amplitude vibrations...... of bridge cables under wind action. This paper describes the experimental simulation of ice accretion on a real bridge cable sheet HDPE tube segment (diameter 160mm) and its effect on the aerodynamic load. Furthermore, aerodynamic instability will be estimated with quasi-steady theory using the determined...

  6. Cable fire risk of a nuclear power plant

    International Nuclear Information System (INIS)

    Aulamo, H.

    1998-02-01

    The aim of the study is to carry out a comprehensive review of cable fire risk issues of nuclear power plants (NPP) taking into account latest fire and risk assessment research results. A special emphasis is put on considering the fire risk analysis of cable rooms in the framework of TVO Olkiluoto NPP probabilistic safety assessment. The assumptions made in the analysis are assessed. The literature study section considers significant fire events at nuclear power plants, the most severe of which have nearly led to a reactor core damage (Browns Ferry, Greifswald, Armenia, Belojarsk, Narora). Cable fire research results are also examined

  7. Arc tracking energy balance for copper and aluminum aeronautic cables

    International Nuclear Information System (INIS)

    André, T; Valensi, F; Teulet, P; Cressault, Y; Zink, T; Caussé, R

    2017-01-01

    Arc tracking tests have been carried out between two voluntarily damaged aeronautic cables. Copper or aluminum conductors have been exposed to short circuits under alternating current. Various data have been recorded (arc voltage and current, radiated power and ablated mass), enabling to determine a power balance, in which every contribution is estimated. The total power is mainly transferred to the cables (between 50 and 65%, depending on the current and the cable type), and causes the melting and partial vaporization of the metallic core and insulating material, or is conducted or radiated. The other part is deposited into the arc column, being either radiated, convected or conducted. (paper)

  8. Effects of ice accretion on the aerodynamics of bridge cables

    DEFF Research Database (Denmark)

    Demartino, C.; Koss, Holger; Georgakis, Christos T.

    2015-01-01

    and stay cables. The aim of this paper is twofold; first, it was investigated the ice accretion process and the final shape of the ice accreted; then the aerodynamics of the ice accreted bridge cables was characterized, and related to the ice shape. Different climatic conditions, i.e. combinations...... of temperature, wind speed and yaw angle of accretion, were reproduced in a climatic wind tunnel, giving rise to different types of accretion. These were chosen such to generate the most common natural ice formations expected to produce bridge cable vibrations. A description of the geometric characteristics...

  9. Cable handling system for use in a nuclear reactor

    International Nuclear Information System (INIS)

    Crosgrove, R.O.; Larson, E.M.; Moody, E.

    1982-01-01

    A cable handling system for use in an installation such as a nuclear reactor is disclosed herein along with relevant portions of the reactor which, in a preferred embodiment, is a liquid metal fast breeder reactor. The cable handling system provides a specific way of interconnecting certain internal reactor components with certain external components, through an assembly of rotatable plugs. Moreover, this is done without having to disconnect these components from one another during rotation of the plugs and yet without interfering with other reactor components in the vicinity of the rotating plugs and cable handling system

  10. Superconducting Cable Development for Future High Energy Physics Detector Magnets

    Science.gov (United States)

    Horvath, I. L.

    1995-11-01

    Under the leadership of the Swiss Federal Institute of Technology (ETHZ) an international ad hoc collaboration for superconducting cables developed an aluminium stabilised superconducting cable for future detector magnets. With the financial support of the Swiss government, this R&D work was carried out for the European Organisation for Nuclear Research (CERN). In this report the manufacturing process is described and results of the quality control measurements are summarised. These tests showed that the industrial manufacturing of an aluminium stabilised superconducting cable is feasible.

  11. Conventional cable testing methods: strengths, weaknesses and possibilities

    International Nuclear Information System (INIS)

    Reynolds, P.H.

    1988-01-01

    The paper reviews the major conventional methods that can be used to test power plant cables. It assesses their usefulness in diagnosing the condition of the insulation of the cable and then proposes some possible directions for innovation. The methods examined are dc insulation resistance measurement, ac signal injection for continuous monitoring and fault location, and the ac measurement of capacitance and loss angle. Specific subjects considered are the effects of temperature, cable construction and installation, and the validity of insulation resistance or loss angle measurement. The innovative proposals refer to the use of automation in the measurement and of computer-based Expert Systems for the evaluation of the results

  12. Low Friction Cryostat for HTS Power Cable of Dutch Project

    DEFF Research Database (Denmark)

    Chevtchenko, Oleg; Zuijderduin, Roy; Smit, Johan

    2012-01-01

    affecting public acceptance of the project. In order to solve this problem, a model cryostat was developed consisting of alternating rigid and flexible sections and hydraulic tests were conducted using sub-cooled liquid nitrogen. In the 47 m-long cryostat, containing a full-size HTS cable model, measured....... A flexible dummy HTS cable was inserted into this cryostat and sub-cooled liquid nitrogen was circulated in the annulus between the dummy cable surface and the inner cryostat surface. In the paper details are presented of the cryostat, of the measurement setup, of the experiment and of the results....

  13. Cable Damage Detection System and Algorithms Using Time Domain Reflectometry

    Energy Technology Data Exchange (ETDEWEB)

    Clark, G A; Robbins, C L; Wade, K A; Souza, P R

    2009-03-24

    This report describes the hardware system and the set of algorithms we have developed for detecting damage in cables for the Advanced Development and Process Technologies (ADAPT) Program. This program is part of the W80 Life Extension Program (LEP). The system could be generalized for application to other systems in the future. Critical cables can undergo various types of damage (e.g. short circuits, open circuits, punctures, compression) that manifest as changes in the dielectric/impedance properties of the cables. For our specific problem, only one end of the cable is accessible, and no exemplars of actual damage are available. This work addresses the detection of dielectric/impedance anomalies in transient time domain reflectometry (TDR) measurements on the cables. The approach is to interrogate the cable using time domain reflectometry (TDR) techniques, in which a known pulse is inserted into the cable, and reflections from the cable are measured. The key operating principle is that any important cable damage will manifest itself as an electrical impedance discontinuity that can be measured in the TDR response signal. Machine learning classification algorithms are effectively eliminated from consideration, because only a small number of cables is available for testing; so a sufficient sample size is not attainable. Nonetheless, a key requirement is to achieve very high probability of detection and very low probability of false alarm. The approach is to compare TDR signals from possibly damaged cables to signals or an empirical model derived from reference cables that are known to be undamaged. This requires that the TDR signals are reasonably repeatable from test to test on the same cable, and from cable to cable. Empirical studies show that the repeatability issue is the 'long pole in the tent' for damage detection, because it is has been difficult to achieve reasonable repeatability. This one factor dominated the project. The two-step model

  14. Effects of simulated nuclear thermal pulses on fiber optic cables

    International Nuclear Information System (INIS)

    Baba, A.J.; Share, S.; Wasilik, J.H.

    1979-01-01

    The effects of pulsed thermal radiation on fiber optic cables with a variety of jackets (polyurethane, PVC, fluorocarbon) are presented. Exposure between 27 and 85 cal/cm 2 did not sever the optical fibers, but the radiation did cause disintegration of the jackets and the Kevlar strength members, which resulted in a significant reduction of the cable's ability to survive mechanical stress. Hardening techniques are discussed. The addition of low absorptance materials (white Teflon tape and aluminum foil) under clear or white Teflon jackets prevented some types of cables from being affected at fluences up to 110 cal/cm 2

  15. Impedance calculations for power cables to primary coolant pump motors

    International Nuclear Information System (INIS)

    Hegerhorst, K.B.

    1977-01-01

    The LOFT primary system motor generator sets are located in Room B-239 and are connected to the primary coolant pumps by means of a power cable. The calculated average impedance of this cable is 0.005323 ohms per unit resistance and 0.006025 ohms per unit reactance based on 369.6 kVA and 480 volts. The report was written to show the development of power cable parameters that are to be used in the SICLOPS (Simulation of LOFT Reactor Coolant Loop Pumping System) digital computer program as written in LTR 1142-16 and also used in the pump coastdowns for the FSAR Analysis

  16. Cable fire risk of a nuclear power plant; Ydinvoimalaitoksen kaapelipaloriski

    Energy Technology Data Exchange (ETDEWEB)

    Aulamo, H.

    1998-02-01

    The aim of the study is to carry out a comprehensive review of cable fire risk issues of nuclear power plants (NPP) taking into account latest fire and risk assessment research results. A special emphasis is put on considering the fire risk analysis of cable rooms in the framework of TVO Olkiluoto NPP probabilistic safety assessment. The assumptions made in the analysis are assessed. The literature study section considers significant fire events at nuclear power plants, the most severe of which have nearly led to a reactor core damage (Browns Ferry, Greifswald, Armenia, Belojarsk, Narora). Cable fire research results are also examined. 62 refs.

  17. 30 CFR 7.408 - Test for flame resistance of signaling cables.

    Science.gov (United States)

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Test for flame resistance of signaling cables..., Signaling Cables, and Cable Splice Kits § 7.408 Test for flame resistance of signaling cables. (a) Test... either and support and the center support. (6) After subjecting the test specimen to external flame for...

  18. Low AC Loss in a 3 kA HTS Cable of the Dutch Project

    DEFF Research Database (Denmark)

    Chevtchenko, Oleg; Zuijderduin, Roy; Smit, Johan

    2012-01-01

    Requirements for a 6km long high temperature superconducting (HTS) AC power cable of the Amsterdam project are: a cable has to fit in an annulus of 160mm, with two cooling stations at the cable ends only. Existing solutions for HTS cables would lead to excessively high coolant pressure drop in th...

  19. 30 CFR 77.600 - Trailing cables; short-circuit protection; disconnecting devices.

    Science.gov (United States)

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Trailing cables; short-circuit protection... AREAS OF UNDERGROUND COAL MINES Trailing Cables § 77.600 Trailing cables; short-circuit protection; disconnecting devices. Short-circuit protection for trailing cables shall be provided by an automatic circuit...

  20. 30 CFR 75.601 - Short circuit protection of trailing cables.

    Science.gov (United States)

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Short circuit protection of trailing cables. 75... MINE SAFETY AND HEALTH MANDATORY SAFETY STANDARDS-UNDERGROUND COAL MINES Trailing Cables § 75.601 Short circuit protection of trailing cables. [Statutory Provisions] Short circuit protection for trailing cables...

  1. 7 CFR 1755.902 - Minimum performance Specification for fiber optic cables.

    Science.gov (United States)

    2010-01-01

    ... installation provided by the end user, the manufacturer must provide a cable design with sag and tension tables... cables. 1755.902 Section 1755.902 Agriculture Regulations of the Department of Agriculture (Continued... optic cables. (a) Scope. This section is intended for cable manufacturers, Agency borrowers, and...

  2. Numerical analysis of the stability of HTS power cable under fault current considering the gaps in the cable

    International Nuclear Information System (INIS)

    Fang, J.; Li, H.F.; Zhu, J.H.; Zhou, Z.N.; Li, Y.X.; Shen, Z.; Dong, D.L.; Yu, T.; Li, Z.M.; Qiu, M.

    2013-01-01

    Highlights: •The equivalent circuit equations and the heat balance equations were established. •The current distributions of the HTS cable under fault current were obtained. •The temperature curves of conductor layers under fault current were obtained. •The effect of the gap liquid nitrogen on the thermal characteristics was studied. -- Abstract: During the operation of a high temperature superconducting power cable in a real grid, the power cable can be impacted inevitably by large fault current. The study on current distribution and thermal characteristics in the cable under fault current is the foundation to analyze its stability. To analyze the operation situation of 110 kV/3 kA class superconducting cable under the fault current of 25 kA rms for 3 s, the equivalent circuit equations and heat balance equations were established. The current distribution curves and the temperature distribution curves were obtained. The liquid nitrogen which exists in the gaps of HTS cable was taken into consideration, the influence of gap liquid nitrogen on the thermal characteristics was investigated. The analysis results can be used to estimate the security and stability of the superconducting cable

  3. Numerical analysis of the stability of HTS power cable under fault current considering the gaps in the cable

    Energy Technology Data Exchange (ETDEWEB)

    Fang, J., E-mail: fangseer@sina.com [School of Electrical Engineering, Beijing Jiaotong University, Beijing 100044 (China); Li, H.F. [School of Electrical Engineering, Beijing Jiaotong University, Beijing 100044 (China); Zhu, J.H.; Zhou, Z.N. [China Electric Power Research Institute, Beijing 100192 (China); Li, Y.X.; Shen, Z.; Dong, D.L.; Yu, T. [School of Electrical Engineering, Beijing Jiaotong University, Beijing 100044 (China); Li, Z.M.; Qiu, M. [China Electric Power Research Institute, Beijing 100192 (China)

    2013-11-15

    Highlights: •The equivalent circuit equations and the heat balance equations were established. •The current distributions of the HTS cable under fault current were obtained. •The temperature curves of conductor layers under fault current were obtained. •The effect of the gap liquid nitrogen on the thermal characteristics was studied. -- Abstract: During the operation of a high temperature superconducting power cable in a real grid, the power cable can be impacted inevitably by large fault current. The study on current distribution and thermal characteristics in the cable under fault current is the foundation to analyze its stability. To analyze the operation situation of 110 kV/3 kA class superconducting cable under the fault current of 25 kA{sub rms} for 3 s, the equivalent circuit equations and heat balance equations were established. The current distribution curves and the temperature distribution curves were obtained. The liquid nitrogen which exists in the gaps of HTS cable was taken into consideration, the influence of gap liquid nitrogen on the thermal characteristics was investigated. The analysis results can be used to estimate the security and stability of the superconducting cable.

  4. Impact of Cross-Tie Properties on the Modal Behavior of Cable Networks on Cable-Stayed Bridges.

    Science.gov (United States)

    Ahmad, Javaid; Cheng, Shaohong; Ghrib, Faouzi

    2015-01-01

    Dynamic behaviour of cable networks is highly dependent on the installation location, stiffness, and damping of cross-ties. Thus, these are the important design parameters for a cable network. While the effects of the former two on the network response have been investigated to some extent in the past, the impact of cross-tie damping has rarely been addressed. To comprehend our knowledge of mechanics associated with cable networks, in the current study, an analytical model of a cable network will be proposed by taking into account both cross-tie stiffness and damping. In addition, the damping property of main cables in the network will also be considered in the formulation. This would allow exploring not only the effectiveness of a cross-tie design on enhancing the in-plane stiffness of a constituted cable network, but also its energy dissipation capacity. The proposed analytical model will be applied to networks with different configurations. The influence of cross-tie stiffness and damping on the modal response of various types of networks will be investigated by using the corresponding undamped rigid cross-tie network as a reference base. Results will provide valuable information on the selection of cross-tie properties to achieve more effective cable vibration control.

  5. Simple Program to Investigate Hysteresis Damping Effect of Cross-Ties on Cables Vibration of Cable-Stayed Bridges

    Directory of Open Access Journals (Sweden)

    Panagis G. Papadopoulos

    2012-01-01

    Full Text Available A short computer program, fully documented, is presented, for the step-by-step dynamic analysis of isolated cables or couples of parallel cables of a cable-stayed bridge, connected to each other and possibly with the deck of the bridge, by very thin pretensioned wires (cross-ties and subjected to variation of their axial forces due to traffic or to successive pulses of a wind drag force. A simplified SDOF model, approximating the fundamental vibration mode, is adopted for every individual cable. The geometric nonlinearity of the cables is taken into account by their geometric stiffness, whereas the material nonlinearities of the cross-ties include compressive loosening, tensile yielding, and hysteresis stress-strain loops. Seven numerical experiments are performed. Based on them, it is observed that if two interconnected parallel cables have different dynamic characteristics, for example different lengths, thus different masses, weights, and geometric stiffnesses, too, or if one of them has a small additional mass, then a single pretensioned very thin wire, connecting them to each other and possibly with the deck of the bridge, proves effective in suppressing, by its hysteresis damping, the vibrations of the cables.

  6. Impact of Cross-Tie Properties on the Modal Behavior of Cable Networks on Cable-Stayed Bridges

    Directory of Open Access Journals (Sweden)

    Javaid Ahmad

    2015-01-01

    Full Text Available Dynamic behaviour of cable networks is highly dependent on the installation location, stiffness, and damping of cross-ties. Thus, these are the important design parameters for a cable network. While the effects of the former two on the network response have been investigated to some extent in the past, the impact of cross-tie damping has rarely been addressed. To comprehend our knowledge of mechanics associated with cable networks, in the current study, an analytical model of a cable network will be proposed by taking into account both cross-tie stiffness and damping. In addition, the damping property of main cables in the network will also be considered in the formulation. This would allow exploring not only the effectiveness of a cross-tie design on enhancing the in-plane stiffness of a constituted cable network, but also its energy dissipation capacity. The proposed analytical model will be applied to networks with different configurations. The influence of cross-tie stiffness and damping on the modal response of various types of networks will be investigated by using the corresponding undamped rigid cross-tie network as a reference base. Results will provide valuable information on the selection of cross-tie properties to achieve more effective cable vibration control.

  7. High power cable with internal water cooling 400 kV

    Science.gov (United States)

    Rasquin, W.; Harjes, B.

    1982-08-01

    Due to the concentration of electricity production in large power plants, the need of higher power transmissions, and the protection of environment, developement of a 400 kV water cooled cable in the power range of 1 to 5 GVA was undertaken. The fabrication and testing of equipment, engineering of cable components, fabrication of a test cable, development of cable terminal laboratory, testing of test cable, field testing of test cable, fabrication of industrial cable laboratory, testing of industrial cable, field testing of industrial cable, and system analysis for optimization were prepared. The field testing was impossible to realize. However, it is proved that a cable consisting of an internal stainless steel water cooled tube, covered by stranded copper profiles, insulated with heavy high quality paper, and protected by an aluminum cover can be produced, withstand tests accordingly to IEC/VDE recommendations, and is able to fulfill all exploitation conditions.

  8. Analysis of the Working Cable System of Single-span Circulating Ropeway

    Directory of Open Access Journals (Sweden)

    Qin Jian

    2017-01-01

    Full Text Available Based on the analysis of the mutual interaction between bearing cable and traction cable of single-span circulating ropeway, the calculation method is proposed for working cables of ropeway with arbitrary loads. The 5 sets nonlinear equations are set up for the working cables according to the equal spans and altitude differences of the bearing cable and the traction cable, the constant of the load running space and the bearing cable length, and the tension balance of bearing cable and traction cable beside load. The resolving method is proposed based on the Newton iterative method. The correctness and feasibility of the method are proved by the results of engineering test. From the solution, the tension and coordinate of working cables can be obtained accurately, which is meaningful for the design and analysis of the freight ropeway.

  9. Dynamic Analysis and Vibration Attenuation of Cable-Driven Parallel Manipulators for Large Workspace Applications

    Directory of Open Access Journals (Sweden)

    Jingli Du

    2013-01-01

    Full Text Available Cable-driven parallel manipulators are one of the best solutions to achieving large workspace since flexible cables can be easily stored on reels. However, due to the negligible flexural stiffness of cables, long cables will unavoidably vibrate during operation for large workspace applications. In this paper a finite element model for cable-driven parallel manipulators is proposed to mimic small amplitude vibration of cables around their desired position. Output feedback of the cable tension variation at the end of the end-effector is utilized to design the vibration attenuation controller which aims at attenuating the vibration of cables by slightly varying the cable length, thus decreasing its effect on the end-effector. When cable vibration is attenuated, motion controller could be designed for implementing precise large motion to track given trajectories. A numerical example is presented to demonstrate the dynamic model and the control algorithm.

  10. Development of Vertical Cable Seismic System (2)

    Science.gov (United States)

    Asakawa, E.; Murakami, F.; Tsukahara, H.; Ishikawa, K.

    2012-12-01

    The vertical cable seismic is one of the reflection seismic methods. It uses hydrophone arrays vertically moored from the seafloor to record acoustic waves generated by surface, deep-towed or ocean bottom sources. Analyzing the reflections from the sub-seabed, we could look into the subsurface structure. This type of survey is generally called VCS (Vertical Cable Seismic). Because VCS is an efficient high-resolution 3D seismic survey method for a spatially-bounded area, we proposed the method for the hydrothermal deposit survey tool development program that the Ministry of Education, Culture, Sports, Science and Technology (MEXT) started in 2009. We are now developing a VCS system, including not only data acquisition hardware but data processing and analysis technique. Our first experiment of VCS surveys has been carried out in Lake Biwa, JAPAN in November 2009 for a feasibility study. Prestack depth migration is applied to the 3D VCS data to obtain a high quality 3D depth volume. Based on the results from the feasibility study, we have developed two autonomous recording VCS systems. After we carried out a trial experiment in the actual ocean at a water depth of about 400m and we carried out the second VCS survey at Iheya Knoll with a deep-towed source. In this survey, we could establish the procedures for the deployment/recovery of the system and could examine the locations and the fluctuations of the vertical cables at a water depth of around 1000m. The acquired VCS data clearly shows the reflections from the sub-seafloor. Through the experiment, we could confirm that our VCS system works well even in the severe circumstances around the locations of seafloor hydrothermal deposits. We have carried out two field surveys in 2011. One is a 3D survey with a boomer for a high-resolution surface source and the other one for an actual field survey in the Izena Cauldron an active hydrothermal area in the Okinawa Trough. Through these surveys, we have confirmed that the

  11. ALOHA Cabled Observatory (ACO): Acoustic Doppler Current Profiler (ADCP): Velocity

    Data.gov (United States)

    National Oceanic and Atmospheric Administration, Department of Commerce — The University of Hawaii's ALOHA ("A Long-term Oligotrophic Habitat Assessment") Cabled Observatory (ACO) is located 100 km north of the island of Oahu, Hawaii (22...

  12. Dynamics of a deep-sea cable system

    International Nuclear Information System (INIS)

    Gulyaev, V.I.; Koshkin, V.L.; Serpak, I.O.

    1995-01-01

    We consider the problem of the dynamics of a deep-sea cable system consisting of branches of constant and variable length, interacting with an undercurrent which is variable in depth and direction. We construct a mathematical model for the motion of the element of the cable system. The cables are modeled as inextensible, flexible filaments of variable length. For numerical realization of the problem, we suggest special regularizing transformations of the variables, making it possible (without additional simplifications) to take into account all the characteristic features of the motion of the filaments and to avoid difficulties in the integration of the equations of motion connected with the variability of the length of the branches of the cable system. The proposed mathematical model and the technique for its numerical analysis is applicable for the investigation of the dynamics of a complex for mining minerals from the ocean floor

  13. Single cables for nuclear instrumentation : Experiences at TAPS

    International Nuclear Information System (INIS)

    Chalam, K.V.; Joshi, S.V.

    1977-01-01

    For fast response and good accuracy, cables of special type are required to be interposed between radiation detectors and preamplifiers/ monitors in a nuclear reactor. The essential characteristics which these signal cables must possess and the tests which they have to undergo are enumerated. Signal cables used in various individual neutron monitoring systems at the Tarapur Atomic Power Station are described in detail. The systems considered are : (1) source range monitoring systems, (2) intermediate range monitoring system, (3) power range monitoring systtem, (4) local power range monitoring system, (5) traversing in-core probe system and (6) area radiation monitoring system. Experience with signal cabling during power operation is given. (M.G.B.)

  14. Evaluation of radiation degradation of cable in nuclear power plant

    Energy Technology Data Exchange (ETDEWEB)

    Kim, K. Y.; Im, D. S.; Lim, I. S.; Lee, C.; Lee, K. Y.; Park, K. S. [Radiation Research Center for Innovative Technology, Seoul (Korea, Republic of)

    2007-11-15

    This project is aimed at lifetime prediction, evaluation of the cable integrity and contribution to the continuous operation in Gori no.1 by using calculating the activation energy before and after irradiation.

  15. Correlation of electrical reactor cable failure with materials degradation

    Energy Technology Data Exchange (ETDEWEB)

    Stuetzer, O.M.

    1986-03-01

    Complete circuit failure (shortout) of electrical cables typically used in nuclear power plant containments is investigated. Failure modes are correlated with the mechanical deterioration of the elastomeric cable materials. It is found that for normal reactor operation, electrical cables are reliable and safe over very long periods. During high temperature excursions, however, cables pulled across corners under high stress may short out due to conductor creep. Severe cracking will occur in short times during high temperatures (>150/sup 0/C) and in times of the order of years at elevated temperatures (100/sup 0/C to 140/sup 0/C). A theoretical treatment of stress distribution responsible for creep and for cracking by J.E. Reaugh of Science Applications, Inc. is contained in the Appendix. 29 refs., 32 figs.

  16. Probabilistic Modeling and Risk Assessment of Cable Icing

    DEFF Research Database (Denmark)

    Roldsgaard, Joan Hee

    This dissertation addresses the issues related to icing of structures with special emphasis on bridge cables. Cable supported bridges in cold climate suffers for ice accreting on the cables, this poses three different undesirable situations. Firstly the changed shape of the cable due to ice...... preliminary framework is modified for assessing the probability of occurrence of in-cloud and precipitation icing and its duration. Different probabilistic models are utilized for the representation of the meteorological variables and their appropriateness is evaluated both through goodness-of-fit tests...... are influencing the two icing mechanisms and their duration. The model is found to be more sensitive to changes in the discretization levels of the input variables. Thirdly the developed operational probabilistic framework for the assessment of the expected number of occurrences of ice/snow accretion on bridge...

  17. Optical fiber cabling technologies for flexible access network

    Science.gov (United States)

    Tanji, Hisashi

    2008-07-01

    Fiber-to-the-home (FTTH) outside plant infrastructure should be so designed and constructed as to flexibly deal with increasing subscribers and system evolution to be expected in the future, taking minimization of total cost (CAPEX and OPEX) into consideration. With this in mind, fiber access architectures are reviewed and key technologies on optical fiber and cable for supporting flexible access network are presented. Low loss over wide wavelength (low water peak) and bend-insensitive single mode fiber is a future proof solution. Enhanced separable ribbon facilitates mid-span access to individual fibers in a cable installed, improving fiber utilizing efficiency and flexibility of distribution design. It also contributes to an excellent low PMD characteristic which could be required for video RF overlay system or high capacity long reach metro-access convergence network in the future. Bend-insensitive fiber based cabling technique including field installable connector greatly improves fiber/cable handling in installation and maintenance work.

  18. Stability of superconducting cables for use in large magnet systems

    International Nuclear Information System (INIS)

    Tateishi, Hiroshi; Schmidt, C.

    1992-01-01

    The construction of large superconducting magnets requires the development of complicated conductor types, which can fulfill the specific requirements of different types of magnets. A rather hard boundary condition for large magnets is the presence of fast changing magnetic fields. In the Institute of Technical Physics of the Karlsruhe Nuclear Research Center, Germany, a superconducting cable was developed for use in poloidal field coils in Tokamak experiments. This 'POLO'-cable exhibits low losses in a magnetic ac-field and a high stability margin. In the present article the requirements on a superconducting cable are described, as well as the mechanisms of ac-losses and the calculation of the stability limit. Calculated values are compared with experimental data. Some unresolved problems concerning the stability of large magnets are discussed taking the example of the POLO-cable. (author)

  19. High Voltage AC underground cable systems for power transmission

    DEFF Research Database (Denmark)

    Bak, Claus Leth; Silva, Filipe Miguel Faria da

    2016-01-01

    researching electrical engineering topics related to using underground cables for power transmission at EHV level and including the 420 kV level. The research topics were laid down by ET/AAU and Energinet.dk in the DANPAC (DANish Power systems with AC Cables) research project. The main topics are discussed...... on the basis of 39 references published by ET/AAU and Energinet.dk. Part I of the paper explains the events that lead to the research project, reactive power compensation, modelling for transient studies, including field measurements and improvements to the existing models, and temporary overvoltages due...... to resonances. Part II covers transient phenomena, harmonics in cables, system modelling for different phenomena, main and backup protections in cable-based networks, online fault detection and future trends....

  20. High Voltage AC underground cable systems for power transmission

    DEFF Research Database (Denmark)

    Bak, Claus Leth; Silva, Filipe Miguel Faria da

    2016-01-01

    researching electrical engineering topics related to using underground cables for power transmission at EHV level and including the 420 kV level. The research topics were laid down by ET/AAU and Energinet.dk in the DANPAC (DANish Power systems with Ac Cables) research project. The main topics are discussed...... on the basis of 39 references published by ET/AAU and Energinet.dk. Part I of the paper explains the events that lead to the research project, reactive power compensation, modelling for transient studies, including field measurements and improvements to the existing models, and temporary overvoltages due...... to resonances. Part II covers transient phenomena, harmonics in cables, system modelling for different phenomena, main and backup protections in cable-based networks, online fault detection and future trends....

  1. 78 FR 1755 - Refunds Under the Cable Statutory License

    Science.gov (United States)

    2013-01-09

    ... signal to all of its subscribers. The Office and the cable industry have been aware of this issue for... (religious television programming); Canadian Claimants (Canadian television programming); and Music Claimants...

  2. Correlation of electrical reactor cable failure with materials degradation

    International Nuclear Information System (INIS)

    Stuetzer, O.M.

    1986-03-01

    Complete circuit failure (shortout) of electrical cables typically used in nuclear power plant containments is investigated. Failure modes are correlated with the mechanical deterioration of the elastomeric cable materials. It is found that for normal reactor operation, electrical cables are reliable and safe over very long periods. During high temperature excursions, however, cables pulled across corners under high stress may short out due to conductor creep. Severe cracking will occur in short times during high temperatures (>150 0 C) and in times of the order of years at elevated temperatures (100 0 C to 140 0 C). A theoretical treatment of stress distribution responsible for creep and for cracking by J.E. Reaugh of Science Applications, Inc. is contained in the Appendix. 29 refs., 32 figs

  3. Advanced refrigeration system for the Brookhaven superconducting cable project

    International Nuclear Information System (INIS)

    Jensen, J.E.

    1975-01-01

    A description is given of a basic supercritical refrigerator. The present status of the cable enclosure and the types of cooling schemes being considered are presented with some examples of laboratory results and computer analysis. (MOW)

  4. 47 CFR 76.956 - Cable operator response.

    Science.gov (United States)

    2010-10-01

    ... directed by the local franchising authority, a cable operator must file with the local franchise authority... failure to meet the minimum showing requirement. Any such motion for dismissal must state with...

  5. Crosslinking of wire and cable insulation using electron accelerators

    International Nuclear Information System (INIS)

    Feng Yongxiang; Ma Zueteh

    1992-01-01

    Radiation crosslinking of wire and cable insulation is a well-established technology that is widely used in industry. The advantages of radiation crosslinking over chemical crosslinking have helped maintain its steady growth. Since successful utilization of electron beam processing relies on the formulation of compounds used in insulation, the radiation crosslinking of various polymers is reviewed. The handling technology for crosslinking wire and cable insulation and the throughput capacity of electron beam processors are also discussed. More than 30% of the industrial electron accelerators in the world are used for the radiation crosslinking of wire and cable insulation. Prospects of increased use of electron accelerators for crosslinking of wire and cable insulation are very good. (orig.)

  6. Stability measurements on cored cables in normal and superfluid helium

    International Nuclear Information System (INIS)

    GHOSH, A.K.; SAMPSON, W.B.; KIM, S.W.; LEROY, D.; OBERLI, L.R.; WILSON, M.N.

    1998-01-01

    The relative stability of LHC type cables has been measured by the direct heating of one of the individual strands with a short duration current pulse. The minimum energy required to initiate a quench has been determined for a number of cables which have a central core to increase the effective inter-strand cross-over resistance. Experiments were performed in both normal helium at 4.4 K and superfluid at 1.9 K. Conductors in general are less stable at the lower temperature when measured at the same fraction of critical current. Results show that the cored-cables, even when partially filled with solder or with a porous-metal filler exhibit a relatively low stability at currents close to the critical current. It is speculated that the high inter-strand electrical and thermal resistance inherent in these cables may effect the stability at high currents

  7. Application of Superconducting Power Cables to DC Electric Railway Systems

    Science.gov (United States)

    Ohsaki, Hiroyuki; Lv, Zhen; Sekino, Masaki; Tomita, Masaru

    For novel design and efficient operation of next-generation DC electric railway systems, especially for their substantial energy saving, we have studied the feasibility of applying superconducting power cables to them. In this paper it is assumed that a superconducting power cable is applied to connect substations supplying electric power to trains. An analysis model line was described by an electric circuit, which was analyzed with MATLAB-Simulink. From the calculated voltages and currents of the circuit, the regenerative brake and the energy losses were estimated. In addition, assuming the heat loads of superconducting power cables and the cryogenic efficiency, the energy saving of the total system was evaluated. The results show that the introduction of superconducting power cables could achieve the improved use of regenerative brake, the loss reduction, the decreased number of substations, the reduced maintenance, etc.

  8. Applicability of cable theory to vascular conducted responses

    DEFF Research Database (Denmark)

    Hald, Bjørn Olav; Jensen, Lars Jørn; Sørensen, Preben Graae

    2012-01-01

    Conduction processes in the vasculature have traditionally been described using cable theory, i.e., locally induced signals decaying passively along the arteriolar wall. The decay is typically quantified using the steady-state length-constant, ¿, derived from cable theory. However......, the applicability of cable theory to blood vessels depends on assumptions that are not necessarily fulfilled in small arteries and arterioles. We have employed a morphologically and electrophysiologically detailed mathematical model of a rat mesenteric arteriole to investigate if the assumptions hold and whether...... ¿ adequately describes simulated conduction profiles. We find that several important cable theory assumptions are violated when applied to small blood vessels. However, the phenomenological use of a length-constant from a single exponential function is a good measure of conduction length. Hence, ¿ should...

  9. Dynamic properties of stay cables on the Penobscot Narrows bridge.

    Science.gov (United States)

    2014-09-01

    Cable-stayed bridges have been recognized as the most efficient and cost effective structural form for medium to long : span bridges over the past several decades. With their widespread use, cases of serviceability problems associated with : large am...

  10. Cable Television: Applied Anthropology in a New Town

    Science.gov (United States)

    Topper, Martin D.; Wilson, W. Leigh

    1976-01-01

    The anthropologist's role in using cable television as a tool of applied anthropology in a new town was examined. The project's purpose was to give a group of people a new usage for a communications medium. (Author/NQ)

  11. Emerging Subsea Networks: SMART Cable Systems for Science and Society

    Science.gov (United States)

    Howe, B. M.; Butler, R.; Joint Task Force, U.

    2016-02-01

    The subsea telecommunications cable industry is approaching a prospective new era: deploying SMART subsea cable systems (SMART = Science Monitoring And Reliable Telecommunication). The current global, commercial cable infrastructure consists of 1 Gm of cable, being refreshed now and expanding in the future. The SMART concept is to add a small external sensor package along the cable system at its optical repeaters to transmit important real-time environmental data via a dedicated wavelength or overhead channel in the transmission system, avoiding any impact on the commercial traffic. These small, reliable, existing sensors would precisely measure temperature, pressure and three-axis acceleration across the world's ocean floor over an extended period of time, being deployed using standard cable-laying procedures on new or refurbished cables, but not requiring maintenance through the 2-3 decade life of the cable systems. The game-changing factor is the urgent international need for ocean environmental data related to mitigating climate and sea-level change and improving tsunami and slope failure hazard warnings. Societal costs incurred by these are reaching billions of dollars and hundreds of thousands of deaths. Pressures for new and urgent public policies are evident from the 5th IPCC Assessment, USA-China agreement on limiting greenhouse gas emissions, clear evidence for rapid global warming, 21st Session of the Conference of the Parties to the UNFCCC (December 2015, Paris), and the scale of the costs of inaction. To support revised public policies and actions, decision-makers, industry leaders, and the public are seeking key scientific data, which will necessitate new sources of funding. Hence, the emergence of new SMART cable systems offered by the subsea telecommunications industry will provide new market opportunities, engage additional non-traditional users, and make profound societal contributions. The Joint Task Force (JTF) on SMART Subsea Cable Systems

  12. Development of Vertical Cable Seismic System

    Science.gov (United States)

    Asakawa, E.; Murakami, F.; Sekino, Y.; Okamoto, T.; Ishikawa, K.; Tsukahara, H.; Shimura, T.

    2011-12-01

    In 2009, Ministry of Education, Culture, Sports, Science and Technology(MEXT) started the survey system development for Hydrothermal deposit. We proposed the Vertical Cable Seismic (VCS), the reflection seismic survey with vertical cable above seabottom. VCS has the following advantages for hydrothermal deposit survey. (1) VCS is an efficient high-resolution 3D seismic survey in limited area. (2) It achieves high-resolution image because the sensors are closely located to the target. (3) It avoids the coupling problems between sensor and seabottom that cause serious damage of seismic data quality. (4) Because of autonomous recording system on sea floor, various types of marine source are applicable with VCS such as sea-surface source (GI gun etc.) , deep-towed or ocean bottom source. Our first experiment of 2D/3D VCS surveys has been carried out in Lake Biwa, JAPAN, in November 2009. The 2D VCS data processing follows the walk-away VSP, including wave field separation and depth migration. Seismic Interferometry technique is also applied. The results give much clearer image than the conventional surface seismic. Prestack depth migration is applied to 3D data to obtain good quality 3D depth volume. Seismic Interferometry technique is applied to obtain the high resolution image in the very shallow zone. Based on the feasibility study, we have developed the autonomous recording VCS system and carried out the trial experiment in actual ocean at the water depth of about 400m to establish the procedures of deployment/recovery and to examine the VC position or fluctuation at seabottom. The result shows that the VC position is estimated with sufficient accuracy and very little fluctuation is observed. Institute of Industrial Science, the University of Tokyo took the research cruise NT11-02 on JAMSTEC R/V Natsushima in February, 2011. In the cruise NT11-02, JGI carried out the second VCS survey using the autonomous VCS recording system with the deep towed source provided by

  13. USING CONDITION MONITORING TO PREDICT REMAINING LIFE OF ELECTRIC CABLES

    International Nuclear Information System (INIS)

    LOFARO, R.; SOO, P.; VILLARAN, M.; GROVE, E.

    2001-01-01

    Electric cables are passive components used extensively throughout nuclear power stations to perform numerous safety and non-safety functions. It is known that the polymers commonly used to insulate the conductors on these cables can degrade with time; the rate of degradation being dependent on the severity of the conditions in which the cables operate. Cables do not receive routine maintenance and, since it can be very costly, they are not replaced on a regular basis. Therefore, to ensure their continued functional performance, it would be beneficial if condition monitoring techniques could be used to estimate the remaining useful life of these components. A great deal of research has been performed on various condition monitoring techniques for use on electric cables. In a research program sponsored by the U.S. Nuclear Regulatory Commission, several promising techniques were evaluated and found to provide trendable information on the condition of low-voltage electric cables. These techniques may be useful for predicting remaining life if well defined limiting values for the aging properties being measured can be determined. However, each technique has advantages and limitations that must be addressed in order to use it effectively, and the necessary limiting values are not always easy to obtain. This paper discusses how condition monitoring measurements can be used to predict the remaining useful life of electric cables. The attributes of an appropriate condition monitoring technique are presented, and the process to be used in estimating the remaining useful life of a cable is discussed along with the difficulties that must be addressed

  14. Applicability of qualification testing of electric cable to life extension

    International Nuclear Information System (INIS)

    Reynolds, A.B.

    1988-01-01

    The methods for qualification testing of electric cable for nuclear power plants followed by U.S. cable manufacturers and endorsed by the U.S. Nuclear Regulatory Commission (NRC) involve irradiation aging at high dose rates at room temperature and accident aging in steam without the pressure of air. Testing is done sequentially. The research data which led to some concerns have been reviewed, and some conclusions regarding these concerns are suggested

  15. High temperature superconductor cable concepts for fusion magnets

    CERN Document Server

    AUTHOR|(CDS)2078397

    2013-01-01

    Three concepts of high temperature superconductor cables carrying kA currents (RACC, CORC and TSTC) are investigated, optimized and evaluated in the scope of their applicability as conductor in fusion magnets. The magnetic field and temperature dependence of the cables is measured; the thermal expansion and conductivity of structure, insulation and filling materials are investigated. High temperature superconductor winding packs for fusion magnets are calculated and compared with corresponding low temperature superconductor cases.

  16. Telecommunications: Issues in Providing Cable and Satellite Television Services

    Science.gov (United States)

    2002-10-01

    This report provides information on (1) whether the availability of cable modem Internet access service appears to be affecting the competitiveness of direct broadcast satellite (DBS) companies in the provision of video services, (2) whether cable prices and DBS penetration rates appear to be affected in areas where the DBS companies offer local broadcast channels, and (3) whether the two individual DBS companies are technologically capable of expanding local broadcast channel services into all 210 television markets in the United States.

  17. New selection rules for cable- and line protection

    Energy Technology Data Exchange (ETDEWEB)

    Kreuz, J

    1982-04-01

    In June 1981 new regulations were published on the protection and dimensioning of leads and cables: of DIN 57100/VDE 0100 the parts 430 and 523. They shall substitute the well-known Paragraph 41 'Dimensioning of leads and cables and their protection against high temperatures of VDE 0100/5.73. The work deals with the essential statements with application examples especially for the operation of low-voltage breakers and power switch-gear.

  18. Usage of Cable Bolts for Gateroad Maintenance in Soft Rocks

    Directory of Open Access Journals (Sweden)

    Iurii Khalymendyk

    2014-01-01

    Originality/value: 1. There are no regulations and state standards in regard to cable bolt installation parameters in the mines of Ukraine, consequently the usage of cable bolts for gateroad maintenance required preliminary testing under geological conditions at the Western Donbass mines with soft enclosing rocks. 2. Combining levelling with observations using extensometers allowed for the detection of the rock layers' uniform sagging zone in the roof of the gateroad.

  19. Structural health monitoring of bridge cables : An overview

    OpenAIRE

    DRISSI HABTI, Monssef; BETTI, Raimondo; YANEV, Bojidar

    2009-01-01

    Bridges are critical components of the civil infrastructure and are normally designed for a long life span. The life span of suspension bridges depends on the health of their cables, which, in turn, is a function of many factors. Therefore, continuous health monitoring (SHM) and regular condition assessment of cables is highly desirable. In this article, some SHM procedures based on direct, indirect non-destructive techniques NDT, and vibration theory are presented.

  20. The Thermal Regime Around Buried Submarine High-Voltage Cables

    Science.gov (United States)

    Emeana, C. J.; Dix, J.; Henstock, T.; Gernon, T.; Thompson, C.; Pilgrim, J.

    2015-12-01

    The expansion of offshore renewable energy infrastructure and the desire for "trans-continental shelf" power transmission, all require the use of submarine High Voltage (HV) cables. These cables have maximum operating surface temperatures of up to 70oC and are typically buried at depths of 1-2 m beneath the seabed, within the wide range of substrates found on the continental shelf. However, the thermal properties of near surface shelf sediments are poorly understood and this increases the uncertainty in determining the required cable current ratings, cable reliability and the potential effects on the sedimentary environments. We present temperature measurements from a 2D laboratory experiment, designed to represent a buried, submarine HV cable. We used a large (2.5 m-high) tank, filled with water-saturated ballotini and instrumented with 120 thermocouples, which measured the time-dependent 2D temperature distributions around the heat source. The experiments use a buried heat source to represent a series of realistic cable surface temperatures with the aim for identifying the thermal regimes generated within typical non-cohesive shelf sediments: coarse silt, fine sand and very coarse sand. The steady state heat flow regimes, and normalised and radial temperature distributions were assessed. Our results show that at temperatures up to 60°C above ambient, the thermal regimes are conductive for the coarse silt sediments and convective for the very coarse sand sediments even at 7°C above ambient. However, the heat flow pattern through the fine sand sediment shows a transition from conductive to convective heat flow at a temperature of approximately 20°C above ambient. These findings offer an important new understanding of the thermal regimes associated with submarine HV cables buried in different substrates and has huge impacts on cable ratings as the IEC 60287 standard only considers conductive heat flow as well as other potential near surface impacts.

  1. New quality assessment procedure for exchange area cable transmission parameters

    Science.gov (United States)

    Link, P. A.

    To best represent the customers' needs, a method of evaluating the transmission quality of exchange area cable must have representative requirements, a statistically powerful method of evaluating the conformance of cables to the requirements and a means of combining the results in a fashion that reflects the end use of the product. The method described herein utilizes a requirement structure containing nominal and maximum requirements to define a desirable distribution for each parameter.

  2. Device for stretching tapes or cables intended for manipulators

    International Nuclear Information System (INIS)

    Baudoin, J.-C.; Oger, Robert.

    1975-01-01

    The invention relates to a device for stretching tapes (or cables) intended for remote handling devices. Said equipment consists of a spring system continuously applying a constant tensile stress to said tapes (or cables) in view of taking up the slack in the latter. Said spring system is fastened to a supporting bar able to be rigidly connected to a member of the remote handling device [fr

  3. Device for stretching tapes or cables intended for manipulators

    Energy Technology Data Exchange (ETDEWEB)

    Baudoin, J C; Oger, R

    1975-03-06

    The invention relates to a device for stretching tapes (or cables) intended for remote handling devices. Said equipment consists of a spring system continuously applying a constant tensile stress to said tapes (or cables) in view of taking up the slack in the latter. Said spring system is fastened to a supporting bar able to be rigidly connected to a member of the remote handling device.

  4. Laplace Synthesis Validation through Measurements on Underground Transmission Cables

    OpenAIRE

    Uribe-Campos Felipe Alejandro

    2014-01-01

    Underground cable electrical parameters ZY as well as their modal propagation characteristics are highly frequency dependent which in certain cases turns its analysis difficult. To perform electromagnetic transient studies of cables the calculation of electrical parameters is essential to obtain the waves propagation solution through the multiconductor system. At the same time this requires to solve the inverse Laplace transform on a numerical form. Although the analytic Laplace transform has...

  5. Ageing of instrumentation and control cables in NPPs

    International Nuclear Information System (INIS)

    Santhosh; Ghosh, A.K.; Fernandes, B.G.

    2011-01-01

    Cables are vital components of instrumentation and control (I and C) systems in nuclear power plants (NPPs). The polymer materials used for insulation and jacket materials for electric cables are susceptible to ageing and degradation mechanisms caused by exposure to many of the stressors encountered in NPP service conditions. Ageing of components in NPP is an important concern since the degradation caused by ageing can impact the performance of susceptible equipment. This is of particular concern for safety-related equipment since the failure due to ageing can compromise the continued safe operation of the plant. The state-of-the art for incorporating cable ageing effects into probabilistic safety assessment (PSA) is still evolving and in the reliability assessment of NPP systems, the ageing effect of electrical cable is generally not considered and also, there is no standard method exists for incorporating such ageing effects into the system reliability. Therefore, identification and quantification of ageing of electrical cables is very much essential for an accurate prediction of system reliability for PSA applications. The objective of this study is to develop a methodology to assess the susceptibility of polymeric cable insulation to various ageing mechanisms; and the state of the insulation at any chosen time in order to evaluate the remaining life-time of operating cables in NPPs. This paper presents the state-of-the-art tools and techniques for insulation condition assessment, insulation life prediction methodologies, equipment qualification guidelines, and ageing management programs relating to I and C cables in NPPs. An approach to calculate the insulation resistance subjecting to different stressors has also been presented in this paper. (author)

  6. MIMO Terminal Performance Evaluation with a Novel Wireless Cable Method

    DEFF Research Database (Denmark)

    Fan, Wei; Kyösti, Pekka; Hentilä, Lassi

    2017-01-01

    chamber, which might be impractical and expensive. In this paper, a novel wireless cable method is proposed and experimentally validated. By recording the average power (i.e. reference signal received power (RSRP) in the LTE) per DUT antenna port and selecting optimal complex weights at the channel...... emulator output ports, a wireless cable connection can be achieved. The proposed method can be executed in a small RF shielded anechoic box, and offers low system cost, high measurement reliability and repeatability....

  7. Energy based optimization of viscous–friction dampers on cables

    International Nuclear Information System (INIS)

    Weber, F; Boston, C

    2010-01-01

    This investigation optimizes numerically a viscous–friction damper connected to a cable close to one cable anchor for fastest reduction of the total mechanical cable energy during a free vibration decay test. The optimization parameters are the viscous coefficient of the viscous part and the ratio between the friction force and displacement amplitude of the friction part of the transverse damper. Results demonstrate that an almost pure friction damper with negligibly small viscous damping generates fastest cable energy reduction over the entire decay. The ratio between the friction force and displacement amplitude of the optimal friction damper differs from that derived from the energy equivalent optimal viscous damper. The reason for this is that the nonlinearity of the friction damper causes energy spillover from the excited to higher modes of the order of 10%, i.e. cables with attached friction dampers vibrate at several frequencies. This explains why the energy equivalent approach does not yield the optimal friction damper. Analysis of the simulation data demonstrates that the optimally tuned friction damper dissipates the same energy per cycle as if each modal component of the cable were damped by its corresponding optimal linear viscous damper

  8. Precise timing signal transmission by a new optical fiber cable

    International Nuclear Information System (INIS)

    Tanaka, Shigeru; Murakami, Yasunori; Sato, Yoshihiro; Urakawa, Junji.

    1990-05-01

    For the precise timing signal transmission, a new optical fiber cable system was developed and installed between the 2.5GeV LINAC gun room and the TRISTAN control room. This fiber cable showed the reduced thermal transmission delay change less than 10psec/km in the temperature range from -20 to 30degC (average 0.04ppm/degC), which is 100 times smaller than that of any other existing coaxial cables and conventional optical fiber cables. The developed optical to electrical (O/E) and electrical to optical (E/O) converters also achieved the timing accuracy within 11psec over the temperature range from 10 to 35degC. The installed cable system in KEK eliminated the necessity of adjusting the phase drift of the TRISTAN Accumulation Ring (AR) RF signal (508MHz), which was required with the former coaxial cable due to the temperature change in a year. Measured full width of jitter over the installed 1600m fiber link was 18.8psec. (author)

  9. Leaky coaxial cable signal transmission for remote facilities

    Science.gov (United States)

    Smith, S. F.; Crutcher, R. I.

    To develop reliable communications methods to meet the rigorous requirements for nuclear hot cells and similar environments, including control of cranes, transporters, and advanced servomanipulators, the Consolidated Fuel Reprocessing Program (CFRP) at Oak Ridge National Laboratory (ORNL) has conducted extensive tests of numerous technologies to determine their applicability to remote operations. To alleviate the need for large bundles of cables that must accommodate crane/transporter motion relative to the boundaries of the cell, several transmission techniques are available, including slotted-line radio-frequency couplers, infrared beams, fiber-optic cables, free-space microwave, and inductively coupled leaky coaxial cable. This paper discusses the general characteristics, mode of operation, and proposed implementation of leaky coaxial cable technology in a waste-handling facility scheduled to be built in the near future at ORNL. In addition, specific system hardware based around the use of leaky coaxial cable is described in detail. Finally, data from a series of radiation exposure tests conducted by the CFRP on several samples of the basic leaky coaxial cable and associated connectors are presented.

  10. Development of non-halogen cables for nuclear power stations

    Energy Technology Data Exchange (ETDEWEB)

    Yagyu, Hideki; Yamamoto, Yasuaki; Onishi, Takao (Hitachi Cable, Ltd., Tokyo (Japan))

    1983-12-01

    The non-halogen fire-resistant cables for nuclear power stations which never generate halogen gas, have been developed. The cables comprise the insulator of EP rubber and the sheath of polyolefine containing non-halogen inorganic fire-retardant. The results of the environmental test and fire-resistance test are described. In the environmental test, the cables were subjected to the heating, gamma-irradiation and steam exposure successively, according to IEEE specification 323,383, and subsequently the change in the appearance, tensile strength and electrical performance of the cables was measured. In the fire-resistance test, the vertical tray fire test according to the IEEE specification 383 was adopted, and other tests including the vertical fire test on insulator cores, oxygen index, the generation of corrosive gas, copper mirror corrosion test, gas toxicity test and optical smoke density test were carried out. It became clear that the cables did not generate halogen gas on burning, and brought about reduced toxicity, corrosion and smoke, and that the safety against fire is greatly improved by using the cables.

  11. Progress on qualification testing methodology study of electric cables

    International Nuclear Information System (INIS)

    Yoshida, K.; Seguchi, T.; Okada, S.; Ito, M.; Kusama, Y.; Yagi, T.; Yoshikawa, M.

    1983-01-01

    Many instrumental, control and power cables are installed in nuclear power plants, and these cables contain a large amount of organic polymers as insulating and jacketing materials. They are exposed to radiation at high dose rate, steam at high temperature and chemical (or water) spray simultaneously when a LOCA occurs. Under such conditions, the polymers tend to lose their original properties. For reactor safety, the cables should be functional even if they are subjected to a loss-of-coolant accident (LOCA) at the end of their intended service life. In Japan, cable manufacturers qualify their cables according to the proposed test standard issued from IEEJ in 1982, but the standard still has many unsolved problems or uncertainties which have been dealt with tentatively through the manufacturer-user's agreement. The objectives of this research are to study the methodologies for qualification testing of electric wires and cables, and to provide the improved technical bases for modification of the standard. Research activities are divided into the Accident (LOCA) Testing Methodology and the Accelerated Aging Methodology

  12. Qualification of Fiber Optic Cables for Martian Extreme Temperature Environments

    Science.gov (United States)

    Ramesham, Rajeshuni; Lindensmith, Christian A.; Roberts, William T.; Rainen, Richard A.

    2011-01-01

    Means have been developed for enabling fiber optic cables of the Laser Induced Breakdown Spectrometer instrument to survive ground operations plus the nominal 670 Martian conditions that include Martian summer and winter seasons. The purpose of this development was to validate the use of the rover external fiber optic cabling of ChemCam for space applications under the extreme thermal environments to be encountered during the Mars Science Laboratory (MSL) mission. Flight-representative fiber optic cables were subjected to extreme temperature thermal cycling of the same diurnal depth (or delta T) as expected in flight, but for three times the expected number of in-flight thermal cycles. The survivability of fiber optic cables was tested for 600 cumulative thermal cycles from -130 to +15 C to cover the winter season, and another 1,410 cumulative cycles from -105 to +40 C to cover the summer season. This test satisfies the required 3 times the design margin that is a total of 2,010 thermal cycles (670 x 3). This development test included functional optical transmission tests during the course of the test. Transmission of the fiber optic cables was performed prior to and after 1,288 thermal cycles and 2,010 thermal cycles. No significant changes in transmission were observed on either of the two representative fiber cables subject through the 3X MSL mission life that is 2,010 thermal cycles.

  13. The Offshore Wind Farm Array Cable Layout Problem

    DEFF Research Database (Denmark)

    Bauer, Joanna; Lysgaard, Jens

    2014-01-01

    In an offshore wind farm (OWF), the turbines are connected to a transformer by cable routes that cannot cross each other. Finding the minimum cost array cable layout thus amounts to a vehicle routing problem with the additional constraints that the routes must be embedded in the plane. For this p......In an offshore wind farm (OWF), the turbines are connected to a transformer by cable routes that cannot cross each other. Finding the minimum cost array cable layout thus amounts to a vehicle routing problem with the additional constraints that the routes must be embedded in the plane....... For this problem, both exact and heuristic methods are of interest. We optimize cable layouts for real-world OWFs by a hop-indexed integer programming formulation, and develop a heuristic for computing layouts based on the Clarke and Wright savings heuristic for vehicle routing. Our heuristic computes layouts...... on average only 2% more expensive than the optimal layout. Finally, we present two problem extensions arising from real-world OWF cable layouts, and adapt the integer programming formulation to one of them. The thus obtained optimal layouts are up to 13% cheaper than the actually installed layouts....

  14. Trend analysis of cables failure events at nuclear power plants

    International Nuclear Information System (INIS)

    Fushimi, Yasuyuki

    2007-01-01

    In this study, 152 failure events related with cables at overseas nuclear power plants are selected from Nuclear Information Database, which is owned by The Institute of Nuclear Safety System, and these events are analyzed in view of occurrence, causal factor, and so on. And 15 failure events related with cables at domestic nuclear power plants are selected from Nuclear Information Archives, which is owned by JANTI, and these events are analyzed by the same manner. As a result of comparing both trends, it is revealed following; 1) A cable insulator failure rate is lower at domestic nuclear power plants than at foreign ones. It is thought that a deterioration diagnosis is performed broadly in Japan. 2) Many buried cables failure events have been occupied a significant portion of cables failure events during work activity at overseas plants, however none has been occurred at domestic plants. It is thought that sufficient survey is conducted before excavating activity in Japan. 3) A domestic age related cables failure rate in service is lower than the overseas one and domestic improper maintenance rate is higher than the overseas one. Maintenance worker' a skill improvement is expected in order to reduce improper maintenance. (author)

  15. Development of non-halogen cables for nuclear power stations

    International Nuclear Information System (INIS)

    Yagyu, Hideki; Yamamoto, Yasuaki; Onishi, Takao

    1983-01-01

    The non-halogen fire-resistant cables for nuclear power stations which never generate halogen gas, have been developed. The cables comprise the insulator of EP rubber and the sheath of polyolefine containing non-halogen inorganic fire-retardant. The results of the environmental test and fire-resistance test are described. In the environmental test, the cables were subjected to the heating, gamma-irradiation and steam exposure successively, according to IEEE specification 323,383, and subsequently the change in the appearance, tensile strength and electrical performance of the cables was measured. In the fire-resistance test, the vertical tray fire test according to the IEEE specification 383 was adopted, and other tests including the vertical fire test on insulator cores, oxygen index, the generation of corrosive gas, copper mirror corrosion test, gas toxicity test and optical smoke density test were carried out. It became clear that the cables did not generate halogen gas on burning, and brought about reduced toxicity, corrosion and smoke, and that the safety against fire is greatly improved by using the cables. (Yoshitake, I.)

  16. Applicability of cable theory to vascular conducted responses.

    Science.gov (United States)

    Hald, Bjørn Olav; Jensen, Lars Jørn; Sørensen, Preben Graae; Holstein-Rathlou, Niels-Henrik; Jacobsen, Jens Christian Brings

    2012-03-21

    Conduction processes in the vasculature have traditionally been described using cable theory, i.e., locally induced signals decaying passively along the arteriolar wall. The decay is typically quantified using the steady-state length-constant, λ, derived from cable theory. However, the applicability of cable theory to blood vessels depends on assumptions that are not necessarily fulfilled in small arteries and arterioles. We have employed a morphologically and electrophysiologically detailed mathematical model of a rat mesenteric arteriole to investigate if the assumptions hold and whether λ adequately describes simulated conduction profiles. We find that several important cable theory assumptions are violated when applied to small blood vessels. However, the phenomenological use of a length-constant from a single exponential function is a good measure of conduction length. Hence, λ should be interpreted as a descriptive measure and not in light of cable theory. Determination of λ using cable theory assumes steady-state conditions. In contrast, using the model it is possible to probe how conduction behaves before steady state is achieved. As ion channels have time-dependent activation and inactivation, the conduction profile changes considerably during this dynamic period with an initially longer spread of current. This may have implications in relation to explaining why different agonists have different conduction properties. Also, it illustrates the necessity of using and developing models that handle the nonlinearity of ion channels. Copyright © 2012 Biophysical Society. Published by Elsevier Inc. All rights reserved.

  17. Experimental characterization of shape memory alloy actuator cables

    Science.gov (United States)

    Biggs, Daniel B.; Shaw, John A.

    2016-04-01

    Wire rope (or cables) are a fundamental structural element in many engineering applications. Recently, there has been growing interest in stranding NiTi wires into cables to scale up the adaptive properties of NiTi tension elements and to make use of the desirable properties of wire rope. Exploratory experiments were performed to study the actuation behavior of two NiTi shape memory alloy cables and straight monofilament wire of the same material. The specimens were held under various dead loads ranging from 50 MPa to 400 MPa and thermally cycled 25 times from 140°C to 5°C at a rate of 12°C/min. Performance metrics of actuation stroke, residual strain, and work output were measured and compared between specimen types. The 7x7 cable exhibited similar actuation to the single straight wire, but with slightly longer stroke and marginally more shakedown, while maintaining equivalent specific work output. This leads to the conclusion that the 7x7 cable effectively scaled up the adaptive properties the straight wire. Under loads below 150 MPa, the 1x27 cable had up to double the actuation stroke and work output, but exhibited larger shakedown and poorer performance when loaded higher.

  18. Rapid cable tension estimation using dynamic and mechanical properties

    Science.gov (United States)

    Martínez-Castro, Rosana E.; Jang, Shinae; Christenson, Richard E.

    2016-04-01

    Main tension elements are critical to the overall stability of cable-supported bridges. A dependable and rapid determination of cable tension is desired to assess the state of a cable-supported bridge and evaluate its operability. A portable smart sensor setup is presented to reduce post-processing time and deployment complexity while reliably determining cable tension using dynamic characteristics extracted from spectral analysis. A self-recording accelerometer is coupled with a single-board microcomputer that communicates wirelessly with a remote host computer. The portable smart sensing device is designed such that additional algorithms, sensors and controlling devices for various monitoring applications can be installed and operated for additional structural assessment. The tension-estimating algorithms are based on taut string theory and expand to consider bending stiffness. The successful combination of cable properties allows the use of a cable's dynamic behavior to determine tension force. The tension-estimating algorithms are experimentally validated on a through-arch steel bridge subject to ambient vibration induced by passing traffic. The tension estimation is determined in well agreement with previously determined tension values for the structure.

  19. An enhanced fire hazard assessment model and validation experiments for vertical cable trays

    International Nuclear Information System (INIS)

    Li, Lu; Huang, Xianjia; Bi, Kun; Liu, Xiaoshuang

    2016-01-01

    Highlights: • An enhanced model was developed for vertical cable fire hazard assessment in NPP. • The validated experiments on vertical cable tray fires were conducted. • The capability of the model for cable tray with different cable spacing were tested. - Abstract: The model, referred to as FLASH-CAT (Flame Spread over Horizontal Cable Trays), was developed to estimate the heat release rate for vertical cable tray fire. The focus of this work is to investigate the application of an enhanced model to the single vertical cable tray fires with different cable spacing. The experiments on vertical cable tray fires with three typical cable spacing were conducted. The histories of mass loss rate and flame length were recorded during the cable fire. From the experimental results, it is found that the space between cable lines intensifies the cable combustion and accelerates the flame spread. The predictions by the enhanced model show good agreements with the experimental data. At the same time, it is shown that the enhanced model is capable of predicting the different behaviors of cable fires with different cable spacing by adjusting the flame spread speed only.

  20. An enhanced fire hazard assessment model and validation experiments for vertical cable trays

    Energy Technology Data Exchange (ETDEWEB)

    Li, Lu [Sate Key Laboratory of Fire Science, University of Science and Technology of China, Hefei 230027 (China); Huang, Xianjia, E-mail: huangxianjia@gziit.ac.cn [Joint Laboratory of Fire Safety in Nuclear Power Plants, Institute of Industry Technology Guangzhou & Chinese Academy of Sciences, Guangzhou 511458 (China); Bi, Kun; Liu, Xiaoshuang [China Nuclear Power Design Co., Ltd., Shenzhen 518045 (China)

    2016-05-15

    Highlights: • An enhanced model was developed for vertical cable fire hazard assessment in NPP. • The validated experiments on vertical cable tray fires were conducted. • The capability of the model for cable tray with different cable spacing were tested. - Abstract: The model, referred to as FLASH-CAT (Flame Spread over Horizontal Cable Trays), was developed to estimate the heat release rate for vertical cable tray fire. The focus of this work is to investigate the application of an enhanced model to the single vertical cable tray fires with different cable spacing. The experiments on vertical cable tray fires with three typical cable spacing were conducted. The histories of mass loss rate and flame length were recorded during the cable fire. From the experimental results, it is found that the space between cable lines intensifies the cable combustion and accelerates the flame spread. The predictions by the enhanced model show good agreements with the experimental data. At the same time, it is shown that the enhanced model is capable of predicting the different behaviors of cable fires with different cable spacing by adjusting the flame spread speed only.

  1. Analysis of Harmonic Vibration of Cable-Stayed Footbridge under the Influence of Changes of the Cables Tension

    Directory of Open Access Journals (Sweden)

    Pakos Wojciech

    2015-09-01

    Full Text Available The paper presents numerical analysis of harmonically excited vibration of a cable-stayed footbridge caused by a load function simulating crouching (squats while changing the static tension in chosen cables. The intentional synchronized motion (e.g., squats of a single person or group of persons on the footbridge with a frequency close to the natural frequency of the structure may lead to the resonant vibrations with large amplitudes. The appropriate tension changes in some cables cause detuning of resonance on account of stiffness changes of structures and hence detuning in the natural frequency that is close to the excitation frequency. The research was carried out on a 3D computer model of a real structure - a cable-stayed steel footbridge in Leśnica, a quarter of Wrocław, Poland, with the help of standard computer software based on FEM COSMOS/M System.

  2. Analysis of Harmonic Vibration of Cable-Stayed Footbridge under the Influence of Changes of the Cables Tension

    Science.gov (United States)

    Pakos, Wojciech

    2015-09-01

    The paper presents numerical analysis of harmonically excited vibration of a cable-stayed footbridge caused by a load function simulating crouching (squats) while changing the static tension in chosen cables. The intentional synchronized motion (e.g., squats) of a single person or group of persons on the footbridge with a frequency close to the natural frequency of the structure may lead to the resonant vibrations with large amplitudes. The appropriate tension changes in some cables cause detuning of resonance on account of stiffness changes of structures and hence detuning in the natural frequency that is close to the excitation frequency. The research was carried out on a 3D computer model of a real structure - a cable-stayed steel footbridge in Leśnica, a quarter of Wrocław, Poland, with the help of standard computer software based on FEM COSMOS/M System.

  3. High-temperature superconducting conductors and cables

    International Nuclear Information System (INIS)

    Peterson, D.E.; Maley, M.P.; Boulaevskii, L.; Willis, J.O.; Coulter, J.Y.; Ullmann, J.L.; Cho, Jin; Fleshler, S.

    1996-01-01

    This is the final report of a 3-year LDRD project at LANL. High-temperature superconductivity (HTS) promises more efficient and powerful electrical devices such as motors, generators, and power transmission cables; however this depends on developing HTS conductors that sustain high current densities J c in high magnetic fields at temperatures near liq. N2's bp. Our early work concentrated on Cu oxides but at present, long wire and tape conductors can be best made from BSCCO compounds with high J c at low temperatures, but which are degraded severely at temperatures of interest. This problem is associated with thermally activated motion of magnetic flux lines in BSCCO. Reducing these dc losses at higher temperatures will require a high density of microscopic defects that will pin flux lines and inhibit their motion. Recently it was shown that optimum defects can be produced by small tracks formed by passage of energetic heavy ions. Such defects result when Bi is bombarded with high energy protons. The longer range of protons in matter suggests the possibility of application to tape conductors. AC losses are a major limitation in many applications of superconductivity such as power transmission. The improved pinning of flux lines reduces ac losses, but optimization also involves other factors. Measuring and characterizing these losses with respect to material parameters and conductor design is essential to successful development of ac devices

  4. Automation of Electrical Cable Harnesses Testing

    Directory of Open Access Journals (Sweden)

    Zhuming Bi

    2017-12-01

    Full Text Available Traditional automated systems, such as industrial robots, are applied in well-structured environments, and many automated systems have a limited adaptability to deal with complexity and uncertainty; therefore, the applications of industrial robots in small- and medium-sized enterprises (SMEs are very limited. The majority of manual operations in SMEs are too complicated for automation. The rapidly developed information technologies (IT has brought new opportunities for the automation of manufacturing and assembly processes in the ill-structured environments. Note that an automation solution should be designed to meet the given requirements of the specified application, and it differs from one application to another. In this paper, we look into the feasibility of automated testing for electric cable harnesses, and our focus is on some of the generic strategies for the improvement of the adaptability of automation solutions. Especially, the concept of modularization is adopted in developing hardware and software to maximize system adaptability in testing a wide scope of products. A proposed system has been implemented, and the system performances have been evaluated by executing tests on actual products. The testing experiments have shown that the automated system outperformed manual operations greatly in terms of cost-saving, productivity and reliability. Due to the potential of increasing system adaptability and cost reduction, the presented work has its theoretical and practical significance for an extension for other automation solutions in SMEs.

  5. Sending more process data without additional cables

    International Nuclear Information System (INIS)

    Licht, H.; Roiha, R.; Rodych, M.

    1997-01-01

    The as-built data transmission capability in CANDU plants is fully employed. Long delays and high cost make it often not feasible to retrofit plant equipment with additional sensors and bring the data to the office. One of the reasons is the unavoidable addition of data transmission cables. This presentation describes the results of work performed in 1996/97 to network sensors using existing plant infrastructure. To provide an alternative solution, a general purpose data transmission system is being developed. It sends data over existing plant infrastructure such as power wiring and the telephone system. Its components are based on PC technology packaged in a 'black box', using special hardware and software to appear to the user as a very simple, low cost, device. Its drawback is its rather limited transmission speed. This design is in marked contrast to the complexity of present commercial data transmission systems. A point-to-point system has been demonstrated. A networked system is under development. (author)

  6. Light Water Reactor Sustainability Program: Evaluation of Localized Cable Test Methods for Nuclear Power Plant Cable Aging Management Programs

    Energy Technology Data Exchange (ETDEWEB)

    Glass, Samuel W. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Fifield, Leonard S. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Hartman, Trenton S. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States)

    2016-05-30

    This Pacific Northwest National Laboratory (PNNL) milestone report describes progress to date on the investigation of nondestructive test (NDE) methods focusing particularly on local measurements that provide key indicators of cable aging and damage. The work includes a review of relevant literature as well as hands-on experimental verification of inspection capabilities. As NPPs consider applying for second, or subsequent, license renewal (SLR) to extend their operating period from 60 years to 80 years, it important to understand how the materials installed in plant systems and components will age during that time and develop aging management programs (AMPs) to assure continued safe operation under normal and design basis events (DBE). Normal component and system tests typically confirm the cables can perform their normal operational function. The focus of the cable test program is directed toward the more demanding challenge of assuring the cable function under accident or DBE. Most utilities already have a program associated with their first life extension from 40 to 60 years. Regrettably, there is neither a clear guideline nor a single NDE that can assure cable function and integrity for all cables. Thankfully, however, practical implementation of a broad range of tests allows utilities to develop a practical program that assures cable function to a high degree. The industry has adopted 50% elongation at break (EAB) relative to the un-aged cable condition as the acceptability standard. All tests are benchmarked against the cable EAB test. EAB is a destructive test so the test programs must apply an array of other NDE tests to assure or infer the overall set of cable’s system integrity. These cable NDE programs vary in rigor and methodology. As the industry gains experience with the efficacy of these programs, it is expected that implementation practice will converge to a more common approach. This report addresses the range of local NDE cable tests that are

  7. Danida2

    DEFF Research Database (Denmark)

    Henriksen, Mogens

    1996-01-01

    At the request of Danish Ministry of Foreign Affairs, Department TSA.4, suggestions for electrical test procedures to determine possibly damaged of a 1-phase, 30 kV XLPE insulated armoured submarine power cable, has been further evaluated.......At the request of Danish Ministry of Foreign Affairs, Department TSA.4, suggestions for electrical test procedures to determine possibly damaged of a 1-phase, 30 kV XLPE insulated armoured submarine power cable, has been further evaluated....

  8. Detection of Local Temperature Change on HTS Cables via Time-Frequency Domain Reflectometry

    Science.gov (United States)

    Bang, Su Sik; Lee, Geon Seok; Kwon, Gu-Young; Lee, Yeong Ho; Ji, Gyeong Hwan; Sohn, Songho; Park, Kijun; Shin, Yong-June

    2017-07-01

    High temperature superconducting (HTS) cables are drawing attention as transmission and distribution cables in future grid, and related researches on HTS cables have been conducted actively. As HTS cables have come to the demonstration stage, failures of cooling systems inducing quench phenomenon of the HTS cables have become significant. Several diagnosis of the HTS cables have been developed but there are still some limitations of the experimental setup. In this paper, a non-destructive diagnostic technique for the detection of the local temperature change point is proposed. Also, a simulation model of HTS cables with a local temperature change point is suggested to verify the proposed diagnosis. The performance of the diagnosis is checked by comparative analysis between the proposed simulation results and experiment results of a real-world HTS cable. It is expected that the suggested simulation model and diagnosis will contribute to the commercialization of HTS cables in the power grid.

  9. Estimation of cables’ tension of cable-stayed footbridge using measured natural frequencies

    Directory of Open Access Journals (Sweden)

    Jakiel Przemysław

    2017-01-01

    Full Text Available This paper presents analysis of cables’ tension of steel cable-stayed footbridge using their field-test natural frequencies. A vibration method is usually used for the measured cable tension during the construction of cable systems stiffened with inclined cables. Practical formulas for the vibration method applied herein, mainly based on cable-sag and vertical angle effects (a survey measurement, have been verified on the one-tower steel cable-stayed bridge. The bridge is situated in Sieradz (Poland and it was the structure with the longest span concerning all the cable-stayed bridges in Poland until 1999. The obtained cable axial forces for estimated natural frequencies of low- and high-order modes are verified using FEM models. The final conclusions drawn on the basis of conducted studies can be useful for technical diagnosis, monitoring programs and repair works of similar class of cable-stayed bridges.

  10. Design, analysis and control of cable-suspended parallel robots and its applications

    CERN Document Server

    Zi, Bin

    2017-01-01

    This book provides an essential overview of the authors’ work in the field of cable-suspended parallel robots, focusing on innovative design, mechanics, control, development and applications. It presents and analyzes several typical mechanical architectures of cable-suspended parallel robots in practical applications, including the feed cable-suspended structure for super antennae, hybrid-driven-based cable-suspended parallel robots, and cooperative cable parallel manipulators for multiple mobile cranes. It also addresses the fundamental mechanics of cable-suspended parallel robots on the basis of their typical applications, including the kinematics, dynamics and trajectory tracking control of the feed cable-suspended structure for super antennae. In addition it proposes a novel hybrid-driven-based cable-suspended parallel robot that uses integrated mechanism design methods to improve the performance of traditional cable-suspended parallel robots. A comparative study on error and performance indices of hybr...

  11. Thin film conductors for self-equalizing cables

    Directory of Open Access Journals (Sweden)

    G. Owen

    2017-10-01

    Full Text Available Self-equalizing cables using hollow conductors with wall thickness less than the skin depth were proposed in 1929. However, they do not appear ever to have been widely used, although the idea has resurfaced and been refined from time to time. In the early 2000’s, self-equalizing conductors consisting of solid magnetic steel cores coated with silver were developed by W.L. Gore, and used in their 2.5 Gb/s “Eye-Opener” cables, although higher speed versions never appeared. We have revived the original 1929 idea, proposing to use glass as a solid insulating core. This technology can potentially work at frequencies of many 10’s of GHz. Possible uses include short range GHz links such as USB and Thunderbolt, and intra-rack interconnections in data centers. Our feasibility experiments have validated the principle. Copper coated glass fibers can, in principle, be manufactured, but in these tests, the conductors were capillaries internally coated with silver as these are easily obtainable, relatively inexpensive and serve to test the concept. The performance of these experimental twin lead cables corresponds to calculations, confirming the general principle. By calculation, we have compared the performance of cables made from copper-on-insulator conductors to that of similar cables made with solid copper conductors, and verified that copper-on-insulator cables have significantly less frequency dependent loss. We have also made and tested cables with copper on PEEK conductors as surrogates for copper on glass fiber.

  12. VPE single core medium voltage cables in EVU supply networks. [Polyethylene (VPE)

    Energy Technology Data Exchange (ETDEWEB)

    Reuter, E [Elektromark Kommunales Elektrizitaetswerk Mark A.G., Hagen (Germany, F.R.). Elektrotechnische Abt.

    1977-02-01

    This paper gives a brief outline of the different cable constructions and constructional parts of medium voltage cables (10 - 20 kV) in power supply networks. At medium voltage (particularly at 20 kV), single core cables are being used to an increasing extent, preferably for station supplies and for pole mounted cables. Polymerized polyethylene (VPE) is used as insulating material for this cable; according to present knowledge it is suitable for the insulation of power cables for all voltages up to 110 kV.

  13. Advanced superconducting power cable for MV urban power supply

    Energy Technology Data Exchange (ETDEWEB)

    Schmidt, Frank [Nexans Deutschland GmbH, Hannover (Germany); Merschel, Frank [RWE Deutschland AG, Essen (Germany); Noe, Mathias [Karlsruhe Institute of Technology, Karlsruhe (Germany)

    2015-07-01

    In recent years the technology of superconducting power cable systems has progressed such that the technical hurdles preparing for commercial applications have been mastered. Several field tests of large scale prototypes for the applications of superconducting cables as well as superconducting fault current limiters have been successfully accomplished and the technology of such systems is ready for commercialization. The presentation will give a detailed overview of the German AmpaCity project. An overview will be given on the development, manufacturing and installation of the 10 kV, 40 MVA HTS system consisting of a fault current limiter and of a 1 km cable in the city of Essen. Since it is the first time that a one kilometer HTS cable system is installed together with an HTS fault current limiter in a real grid application between two substations within a city center area, AmpaCity serves as a lighthouse project. In addition it is worldwide the longest installed HTS cable system so far. It is expected that relatively large technical advances will be made in the future of the comparatively new HTS technology, which in turn will bring associated cost reductions. For this reason, the AmpaCity pilot project in the downtown area of Essen in Germany will be an important step on the way to achieving more widespread application of HTS technology.

  14. Development of superior radiation resistant materials and cables. 2

    Energy Technology Data Exchange (ETDEWEB)

    Ikehara, Junichiro; Kanemitsuya, Kazuhiko; Ohara, Hideo; Araki, Syogo; Hamachi, Katsuhiko [Mitsubishi Cable Industries Ltd., Tokyo (Japan)

    1996-01-01

    Many nuclear power plants have been constructed in Japan and electric power generation is now highly dependent on this technology. Therefore, the needs for facilities that will enrich and reprocess nuclear fuel from nuclear power stations will be high. As there are areas with high levels of radiation, the cables which can be used in these environments are needed. We have developed a superior radiation-resistant cable which uses halogen flame-retardant materials. This radiation-resistant cable consists of Ethylene-propylene rubber (EPDM) insulation and Chlorosulfonated polyethylene (CSM) sheath can be safely used in areas with high levels of radiation. We developed this product to aid in disaster prevention. Non-halogen, flame-retardant EPDM is used for the insulation, and low-halogen, flame-retardant CSM and new non-halogen, flame-retardant materials are used for the sheath. These cables have superior flame-retardant properties and generate little smoke on corrosive gas. This products can hence reduce the danger of a secondary disaster in a fire. We expect that these cables will find application in areas with high levels of radiation. (author).

  15. Trial manufacture of flame retardant and radiation resistant cables

    Energy Technology Data Exchange (ETDEWEB)

    Oshima, Yunosuke; Hagiwara, Miyuki (Japan Atomic Energy Research Inst., Takasaki, Gunma. Takasaki Radiation Chemistry Research Establishment); Oda, Eisuke

    1983-04-01

    High radiation resistance as well as incombustibility is required for the wires and cables used for nuclear facilities such as nuclear power stations. In order to give such performance to general purpose insulation materials such as ethylene-propylene copolymerized rubber, acenaphthylene bromide condensation product was developed anew. Moreover, by the use of this agent, the new flame retardant and radiation resistant cables were manufactured for trial, which are not different from ordinary plastic rubber cables in the handling such as flexibility, and withstand the radiation nearly up to 1000 Mrad. The requirement for the agent giving flame retardant and radiation resistant properties is explained. The synthesis of acenaphthylene bromide and its condensation product and the effect of giving flame retardant and radiation resistant properties are described. The test resultd of the prevention of spread of flame, the endurance in LOCA-simulating environment, and radiation resistance for the cables manufactured for trial are reported. It was confirmed that the cables of this type are suitable to the use in which the maintenance of mechanical properties after radiation exposure is required.

  16. Electrostatic Analysis of Annular Holes Penetrated by Shorted-Cable

    Energy Technology Data Exchange (ETDEWEB)

    Choo, Jae Yul; Kim, Hyung Tae; Park, Hyun Shin; Cho, Young Sik [KINS, Daejeon (Korea, Republic of)

    2016-05-15

    The cabinet has an important role to protect the contained cables and digital modules for the safety function from the external electromagnetic (EM) source. Thus the immunity of an open cabinet against electromagnetic interference (EMI) numerically has been investigated using mode-matching method in. Another path for the external EM source to impinge on inner cables and digital modules is the bottom hole of the cabinet that is penetrated by various cables. Especially the EMI can detrimentally influence on the digital modules through annular space caused by sealing the bottom hole of the cabinet incompletely. Thus it is recently required that the electromagnetic interpretation in the annular hole is performed to remedy electromagnetic problems. Based on the mode-matching method, we solved the electrostatic boundary-value problem for holes penetrating shorted-cable at the bottom of a digital I and C cabinet. The Weber transform and the Hankel transform were applied to formulate the electrostatic potential. The capacitance and potential distribution generated near the penetrating shorted-cable were computed and compared with the result from the previous study.

  17. Dynamic tensile test of single PET textile cables

    Directory of Open Access Journals (Sweden)

    Pasco F.

    2012-08-01

    Full Text Available The tyres conception involves for certain applications, the use of textile cables as reinforcement. During its use, the tyre undergoes temperatures variations and dynamic loading rates. The consideration of these conditions during the numeric simulations requires the knowledge of the sensitivity of the mechanical behaviour to loading rate and temperature. In this paper, we developed an experimental methodology for testing textile cable up to high strain rate. The main difficulty of testing cables is the optimization of cable fixing on the machine. For that purpose, we adapted the solution of fixing by progressive binding already used in quasi-static, while taking into account constraints inherent to high strain tests. Firstly, the mass of grips was decreased in order to get force signal less sensitive to grips inertia. The method was developed on a high speed hydraulic machine equipped with a thermal enclosure. The investigated temperatures and strain rates range from room temperature to 373 ∘K (100 ∘C and from 0,01 to 100/s, respectively. In addition, the hydraulic machine was equipped with a high speed video camera. The obtained images were analysed by a tracking technique to measure the average strain in the cable (from 50 to 20000 f/s.

  18. Partial discharge testing of in-situ power cable accessories

    Energy Technology Data Exchange (ETDEWEB)

    Orban, H. E.

    2002-07-01

    An overview of commercially available diagnostic methods for in-situ power cable accessories is given and relevant field experiences with these diagnostics are described. The discussion includes both PILC and polymeric insulated cables. Two major types of degradation are most frequently involved in cable systems. One is an overall condition caused by chemical aging and /or water treeing. Diagnostics for this type of aging include dissipation factor (loss angle), harmonic analysis, return voltage, isothermal relaxation current, dielectric response, or dc leakage current. The second type of degradation is discrete or incremental; condition assessment utilizes dissipation factor measurements or partial discharge (PD) level measurements. The focus in this paper is on PD diagnostics, especially off-line methods such as the 60 Hz test, the combined AC and VLF diagnostic, and the oscillating wave test system test. Among on-line diagnostics, ultrasonic detection of partial discharge and measurement of partial discharge by installing direct, capacitive or inductive couplers near cable accessories, are described. Overall, partial discharge detection and location in cable accessories is considered inadequate, since interpretation of results is difficult due to the number of variables involved. 28 refs., 1 tab.

  19. Simultaneous Thermal and Gamma Radiation Aging of Electrical Cable Polymers

    Energy Technology Data Exchange (ETDEWEB)

    Fifield, Leonard S.

    2018-04-11

    The polymers used for insulation in nuclear power plant electrical cables are susceptible to aging during long term operation. Elevated temperature is the primary contributor to changes in polymer structure that result loss of mechanical and electrical properties, but gamma radiation is also a significant source of degradation for polymers used within relevant plant locations. Despite many years of polymer degradation research, the combined effects of simultaneous exposure to thermal and radiation stress are not well understood. As nuclear operators contemplate and prepare for extended operations beyond initial license periods, a predictive understanding of exposure-based cable material degradation is becoming an increasingly important input to safety, licensing, operations and economic decisions. We are focusing on carefully-controlled simultaneous thermal and gamma radiation accelerating aging and characterization of the most common nuclear cable polymers to understand the relative contributions of temperature, time, dose and dose rate to changes in cable polymer material structure and properties. Improved understanding of cable performance in long term operation will help support continued sustainable nuclear power generation.

  20. Development of cables for nuclear fuel processing facilities

    International Nuclear Information System (INIS)

    Kamimura, Seiji; Seki, Ikuo; Yamamoto, Yasuaki; Matsuyama, Shigeki; Endo, Shigeru; Yagi, Toshiaki; Kawakami, Waichiro.

    1988-01-01

    Accompanying the development of nuclear power stations, the expansion and repletion of the facilities for nuclear fuel cycle such as fuel reprocessing facilities and waste treatment facilities are requested. In these facilities, there is the environment which is exposed to very high level radiation, and in this case, the cables withstanding 10 MGy radiation dose are required. As the cables meeting such requirement, the new cables having excellent flexibility and radiation resistance were developed. In this paper, the points of material development and the characteristics of cables are reported. Considering the radiation resistance and others, ethylene propylene rubber was selected as the base polymer of the insulator, and polyethylene chlorosulfonate was selected as the sheath material. In order to give excellent radiation resistance, as the anti-rad, energy transfer type aromatic oil that absorbs and dissipates radiation energy and radical trap type anti-oxidant of amine group that catches and stabilizes the radicals generated in the polymer were added. The bromine group burning retarding agent having excellent radiation resistance was applied. In this way, the cables withstanding high radiation dose up to 10 MGy were able to be developed. (K.I.)

  1. Study of Nb3Sn cables for superconducting quadrupoles

    International Nuclear Information System (INIS)

    Otmani, R.

    1999-10-01

    In particle physics, the quest for higher energies may be satisfied by the use of niobium-tin superconducting magnets. Such magnets are made of Rutherford type cables which are wound from superconducting strands. The strands are made by the 'internal tin' method. The aim of this study is to determine the main parameters for the fabrication of a quadrupole. The two main requirements the cable must fulfill are high critical current and low losses. The main parameters were determined from different measurements and models. Thus, the key parameters for the current transport capacity are the number and the diameter of the filaments, the number of sub-elements, the surface of superconductor and the copper-to-non-copper ratio. For the hysteresis losses, the main parameters appear to be the effective filament diameter and the spacing of the filaments. For intra-strand losses, the main parameters appear to be the filaments' diameter, the filament spacing, the nature of the diffusion barrier and the Residual Resistivity Ratio (RRR) of the copper. The interstrand resistances for the cable are the key parameters for the losses. Thus, the nature of the strands coating or the presence of a stainless steel core can strongly diminish the cable losses. Finally, a design, for the strands and the cables for the fabrication of a quadrupole is proposed. (author)

  2. Seismic response of cable stayed bridges under multi support excitation

    Directory of Open Access Journals (Sweden)

    Mahmoud Reza ُُShiravand

    2017-07-01

    Full Text Available In this Study, the seismic response of cable stayed bridges have been evaluated under multi-support excitations. There are three sources that cause the earthquake wave characteristics change during its propagation path. Local site effect, loss of coherency and wave passage effect are three sources of spatial variation of seismic ground motions. In long span structures, such as cable supported bridges, this phenomenon is more evident and traditional analyzing (uniform excitation may not be valid and be conservative. Thus, it is necessary to investigate the response of cable stayed bridges under non-uniform excitations. For this purpose, the non-uniform time histories were artificially generated using Kriging method based on a set of known time history in the west support of bridge. Nonlinear time history analysis was performed and cables axial force, deck moment, pylons moment and finally drift ratio of bridge have been examined in order to investigate how non-uniform excitation change the seismic response of bridge compared with uniform excitations. Results show non-uniform excitation in some bridge components increase responses and decreases in the others. In non-uniform excitation, although total time history energy is lesser than uniform excitation, it can significantly change the distribution of the forces and makes differential displacement between cables supports and increase the possibility of failure.

  3. Development of superior radiation resistant materials and cables. 2

    International Nuclear Information System (INIS)

    Ikehara, Junichiro; Kanemitsuya, Kazuhiko; Ohara, Hideo; Araki, Syogo; Hamachi, Katsuhiko

    1996-01-01

    Many nuclear power plants have been constructed in Japan and electric power generation is now highly dependent on this technology. Therefore, the needs for facilities that will enrich and reprocess nuclear fuel from nuclear power stations will be high. As there are areas with high levels of radiation, the cables which can be used in these environments are needed. We have developed a superior radiation-resistant cable which uses halogen flame-retardant materials. This radiation-resistant cable consists of Ethylene-propylene rubber (EPDM) insulation and Chlorosulfonated polyethylene (CSM) sheath can be safely used in areas with high levels of radiation. We developed this product to aid in disaster prevention. Non-halogen, flame-retardant EPDM is used for the insulation, and low-halogen, flame-retardant CSM and new non-halogen, flame-retardant materials are used for the sheath. These cables have superior flame-retardant properties and generate little smoke on corrosive gas. This products can hence reduce the danger of a secondary disaster in a fire. We expect that these cables will find application in areas with high levels of radiation. (author)

  4. Development of no halogen incombustible cables for atomic energy

    International Nuclear Information System (INIS)

    Ishii, Nobumasa; Kimura, Hitoshi; Fujimura, Shun-ichi

    1990-01-01

    In upgrading light water reactor technology, it is important to improve the reliability of machinery and equipment, to make regular inspection efficient, to extend the period of continuous operation, to optimize operation cycle and to improve the maintainability of plant facilities. For the cables for nuclear power stations, high incombustibility is required, and at present halogen system incombustible materials are used. Recently the development of no halogen incombustible cables has been advanced, with which the generation of corrosive gas and smoke at the time of fires is slight. In this study, the application of such no halogen incombustible cables to nuclear power stations and the improvement of reliability of the cables were investigated. The cables to be developed are those for electric power, control and instrumentation in BWR plants and insulated electric wires. The required characteristics are incombustibility, no generation of smoke and corrosive gas at the time of fires, radiation resistance and steam resistance in LOCA. The selection of base polymers, metal hydrates and radiation protectors, the evaluation of radiation resistance and steam resistance, the examination of the corrosive and poisonous properties of generated gas and smoke generation and so on are reported. The development was successful. (K.I.)

  5. Method for analysis the complex grounding cables system

    International Nuclear Information System (INIS)

    Ackovski, R.; Acevski, N.

    2002-01-01

    A new iterative method for the analysis of the performances of the complex grounding systems (GS) in underground cable power networks with coated and/or uncoated metal sheathed cables is proposed in this paper. The analyzed grounding system consists of the grounding grid of a high voltage (HV) supplying transformer station (TS), middle voltage/low voltage (MV/LV) consumer TSs and arbitrary number of power cables, connecting them. The derived method takes into consideration the drops of voltage in the cable sheets and the mutual influence among all earthing electrodes, due to the resistive coupling through the soil. By means of the presented method it is possible to calculate the main grounding system performances, such as earth electrode potentials under short circuit fault to ground conditions, earth fault current distribution in the whole complex grounding system, step and touch voltages in the nearness of the earthing electrodes dissipating the fault current in the earth, impedances (resistances) to ground of all possible fault locations, apparent shield impedances to ground of all power cables, e.t.c. The proposed method is based on the admittance summation method [1] and is appropriately extended, so that it takes into account resistive coupling between the elements that the GS. (Author)

  6. Structured Cable for High-Current Coils of Tokamaks

    Science.gov (United States)

    Benson, Christopher; McIntyre, Peter; Sattarov, Akhdiyor; Mann, Thomas

    2011-10-01

    The 45 kA superconducting cable for the ITER central solenoid coil has yielded questionable results in two recent tests. In both cases the cable Tc increased after cycling only a fraction of the design life, indicating degradation due to fatigue and fracture among the superconducting strands. The Accelerator Research Lab at Texas A&M University is developing a design for a Nb3Sn structured cable suitable for such tokamak coils. The superconductor is configured in 6 sub-cables, and each subcable is supported within a channel of a central support structure within a high-strength armor sheath. The structured cable addresses two issues that are thought to compromise opposition at high current. The strands are supported without cross-overs (which produce stress concentration); and armor sheath and core structure bypass stress through the coil and among subcables so that the stress within each subcable is only what is produced directly upon it. Details of the design and plans for development will be presented.

  7. Kinematic and Dynamic Analysis of a Cable-Climbing Robot

    Directory of Open Access Journals (Sweden)

    Xu Fengyu

    2015-07-01

    Full Text Available To inspect broken cables or a cracked protective layer on cable-stayed bridges, a cable-climbing robot has been proposed and designed. In this paper, the complex 3D obstacles that may be encountered on cables are theoretically described, in order to investigate the obstacle-climbing capability of the cable-climbing robot. A climbing model is then proposed and used to design the robot. In the climbing model, two driven wheels are independently supported with a spring. Kinematics and dynamics models are further derived for the obstacle-climbing capabilities of the driving and driven wheels of the robot. In addition, the robot's obstacle-climbing tracks and its obstacle-climbing performance are simulated. Payload and obstacle-climbing experiments were conducted on the climbing robot in the laboratory. Based on the results of the simulation and the experiments, we obtained the variation of the driving torque in obstacle climbing. The contribution of this paper is intended to provide a basis for the precise motion control of the robot.

  8. Some considerations on special spacers with damping device for suppressing wake galloping in tandem cables of cable-stayed bridges; Heiretsu cable yo gensui kino tsuki supesa no gensui fuka tokusei ni kansuru 2,3 no kosatsu

    Energy Technology Data Exchange (ETDEWEB)

    Yoneda, M. [Kinki Univ., Higashi-Osaka, Osaka (Japan). Faculty of Science and Technology] Setouchi, H. [Kawada Industries Inc., Osaka (Japan)

    1998-03-20

    Cable vibration called wake galloping appears on cable-stayed bridges with parallel arranged cables and its suppression is an important problem. Various methods have been proposed for spacers with damping device for suppressing wake galloping in tandem cables of cable-stayed bridges. But, comparison of damping performances of various methods have not been discussed sufficiently. This paper deals with a type in which dampers are equipped on the midway of the tandem cables through the spacer jig and a type in which dampers are equipped on each surface of the tandem cables to generate shear deformation between them and circular spacer jig moiety and complex eigenvalue analyses are carried out on the two types with changing center spacing and diameters of the cables. The results clarify the relation between the structural damping characteristics and the cable spacing and the effect of torsional rigidity of the cables and also clarify of damping characteristics of the two types. 16 refs., 14 figs., 4 tabs.

  9. Development of Vertical Cable Seismic System (3)

    Science.gov (United States)

    Asakawa, E.; Murakami, F.; Tsukahara, H.; Mizohata, S.; Ishikawa, K.

    2013-12-01

    The VCS (Vertical Cable Seismic) is one of the reflection seismic methods. It uses hydrophone arrays vertically moored from the seafloor to record acoustic waves generated by surface, deep-towed or ocean bottom sources. Analyzing the reflections from the sub-seabed, we could look into the subsurface structure. Because VCS is an efficient high-resolution 3D seismic survey method for a spatially-bounded area, we proposed the method for the hydrothermal deposit survey tool development program that the Ministry of Education, Culture, Sports, Science and Technology (MEXT) started in 2009. We are now developing a VCS system, including not only data acquisition hardware but data processing and analysis technique. We carried out several VCS surveys combining with surface towed source, deep towed source and ocean bottom source. The water depths of the survey are from 100m up to 2100m. The target of the survey includes not only hydrothermal deposit but oil and gas exploration. Through these experiments, our VCS data acquisition system has been completed. But the data processing techniques are still on the way. One of the most critical issues is the positioning in the water. The uncertainty in the positions of the source and of the hydrophones in water degraded the quality of subsurface image. GPS navigation system are available on sea surface, but in case of deep-towed source or ocean bottom source, the accuracy of shot position with SSBL/USBL is not sufficient for the very high-resolution imaging. We have developed another approach to determine the positions in water using the travel time data from the source to VCS hydrophones. In the data acquisition stage, we estimate the position of VCS location with slant ranging method from the sea surface. The deep-towed source or ocean bottom source is estimated by SSBL/USBL. The water velocity profile is measured by XCTD. After the data acquisition, we pick the first break times of the VCS recorded data. The estimated positions of

  10. Vertical Cable Seismic Survey for SMS exploration

    Science.gov (United States)

    Asakawa, Eiichi; Murakami, Fumitoshi; Tsukahara, Hotoshi; Mizohata, Shigeharu

    2014-05-01

    The Vertical Cable Seismic (VCS) survey is one of the reflection seismic methods. It uses hydrophone arrays vertically moored from the seafloor to record acoustic waves generated by sea-surface, deep-towed or ocean bottom sources. Analyzing the reflections from the sub-seabed, we could look into the subsurface structure. Because the VCS is an efficient high-resolution 3D seismic survey method for a spatially-bounded area, we proposed it for the SMS survey tool development program that the Ministry of Education, Culture, Sports, Science and Technology (MEXT) started in 2009. We have been developing the VCS survey system, including not only data acquisition hardware but data processing and analysis technique. We carried out several VCS surveys combining with surface towed source, deep towed source and ocean bottom source. The water depths of these surveys are from 100m up to 2100 m. Through these experiments, our VCS data acquisition system has been also completed. But the data processing techniques are still on the way. One of the most critical issues is the positioning in the water. The uncertainty in the positions of the source and of the hydrophones in water degraded the quality of subsurface image. GPS navigation system is available on sea surface, but in case of deep-towed source or ocean bottom source, the accuracy of shot position with SSBL/USBL is not sufficient for the very high-resolution imaging. We have developed a new approach to determine the positions in water using the travel time data from the source to VCS hydrophones. In 2013, we have carried out the second VCS survey using the surface-towed high-voltage sparker and ocean bottom source in the Izena Cauldron, which is one of the most promising SMS areas around Japan. The positions of ocean bottom source estimated by this method are consistent with the VCS field records. The VCS data with the sparker have been processed with 3D PSTM. It gives the very high resolution 3D volume deeper than two

  11. Noise propagation issues in Belle II pixel detector power cable

    Science.gov (United States)

    Iglesias, M.; Arteche, F.; Echeverria, I.; Pradas, A.; Rivetta, C.; Moser, H.-G.; Kiesling, C.; Rummel, S.; Arcega, F. J.

    2018-04-01

    The vertex detector used in the upgrade of High-Energy physics experiment Belle II includes DEPFET pixel detector (PXD) technology. In this complex topology the power supply units and the front-end electronics are connected through a PXD power cable bundle which may propagate the output noise from the power supplies to the vertex area. This paper presents a study of the propagation of noise caused by power converters in the PXD cable bundle based on Multi-conductor Transmission Line (MTL) theory. The work exposes the effect of the complex cable topology and shield connections on the noise propagation, which has an impact on the requirements of the power supplies. This analysis is part of the electromagnetic compatibility based design focused on functional safety to define the shield connections and power supply specifications required to ensure the successful integration of the detector and, specifically, to achieve the designed performance of the front-end electronics.

  12. Fire safety requirements for electrical cables towards nuclear reactor safety

    International Nuclear Information System (INIS)

    Raju, M.R.

    2002-01-01

    Full text: Electrical power supply forms a very important part of any nuclear reactor. Power supplies have been categorized in to class I, II, III and IV from reliability point. The safety related equipment are provided with highly reliable power supply to achieve the safety of very high order. Vast network of cables in a nuclear reactor are grouped and segregated to ensure availability of power to at least one group under all anticipated occurrences. Since fire can result in failures leading to unavailability of power caused by common cause, both passive and active fire protection methods are adopted in addition to fire detection system. The paper describes the requirement for passive fire protection to electrical cables viz. fire barrier and fire breaks. The paper gives an account of the tests required to standardize the products. Fire safety implementation for cables in research reactors is described

  13. Sediment Biogeochemistry After the Entrance of Cable Bacteria

    DEFF Research Database (Denmark)

    Risgaard-Petersen, Nils

    fields which may strongly modify ionic transports. They form pH extremes, and accelerate the dissolution of iron sulfides, and carbonates in subsurface sediment. They further promote the formation of iron oxides and carbonates at the sediment surface and stimulate the removal of sulfides......, sulfide-rich coastal sediments, salt marshes seasonally hypoxic basins, subtidal coastal mud plains, as well as freshwater sediments and waterlogged soils. In this talk I will review our current knowledge on how cable bacteria influence the biogeochemistry of sediments. The cable bacteria form electric...... and the formation of sulfate[3] Field studies conducted in the marine environment indicate that some of these effects are expressed in a way that marine systems with active cable bacteria populations have elevated phosphorus-retention{Sulu-Gambari, 2016 #1501} and acts as strong buffers against adverse stage...

  14. Approximate Series Solutions for Nonlinear Free Vibration of Suspended Cables

    Directory of Open Access Journals (Sweden)

    Yaobing Zhao

    2014-01-01

    Full Text Available This paper presents approximate series solutions for nonlinear free vibration of suspended cables via the Lindstedt-Poincare method and homotopy analysis method, respectively. Firstly, taking into account the geometric nonlinearity of the suspended cable as well as the quasi-static assumption, a mathematical model is presented. Secondly, two analytical methods are introduced to obtain the approximate series solutions in the case of nonlinear free vibration. Moreover, small and large sag-to-span ratios and initial conditions are chosen to study the nonlinear dynamic responses by these two analytical methods. The numerical results indicate that frequency amplitude relationships obtained with different analytical approaches exhibit some quantitative and qualitative differences in the cases of motions, mode shapes, and particular sag-to-span ratios. Finally, a detailed comparison of the differences in the displacement fields and cable axial total tensions is made.

  15. Workshop on power plant cable condition monitoring: Proceedings

    International Nuclear Information System (INIS)

    Del Valle, L.

    1988-07-01

    A three-day workshop on cable condition monitoring was held in San Francisco on Fegruary 16--18, 1988. The workshop was cosponsored by the Nuclear Power, Electrical Systems, and Coal Combustion Systems Divisions of the Electric Power Research Institute. The primary objective of the workshop was to identify the state-of-the-art for cable condition monitoring. Twenty-five technical papers as well as EPRI research programs were presented at the technical sessions. Four working group sessions and one general session were held on each of two days. Each group session provided a forum for participants to exchange ideas and to discuss in more depth research for cable condition monitoring, existing and innovative testing technology, and utility and NRC needs for testing. Recommendations from the working groups were summarized and presented at the end of the workshop

  16. Experimental Investigations on Combustion Behaviors of Live PVC Cables

    Science.gov (United States)

    Wang, Liufang; Zhang, Jiaqing; Zhang, Bosi; Liu, Min; Fan, Minghao; Li, Qiang

    2018-03-01

    This paper investigated the combustion behaviors of live PVC cables with overload currents experimentally. The smoke coefficient of released smoke and the released gas concentration were examined. The results indicate that the combustion of live PVC cables can be divided into four stages, i.e., core exposed with a little smoke, obvious flame, maximum smoke and smoke depress. For most cases, using blue laser is better than using rad laser, since the extinction coefficient of the rad laser was larger than that of the blue laser. The response time of the detection of the released typical gases due to cable pyrolysis decreased and the peak values of the typical gases increased with the overload currents. In addition, the time to reach the peak value of gas concentration also decreased with the overload currents.

  17. Laplace Synthesis Validation through Measurements on Underground Transmission Cables

    Directory of Open Access Journals (Sweden)

    Uribe-Campos Felipe Alejandro

    2014-10-01

    Full Text Available Underground cable electrical parameters ZY as well as their modal propagation characteristics are highly frequency dependent which in certain cases turns its analysis difficult. To perform electromagnetic transient studies of cables the calculation of electrical parameters is essential to obtain the waves propagation solution through the multiconductor system. At the same time this requires to solve the inverse Laplace transform on a numerical form. Although the analytic Laplace transform has an indisputable accuracy, the application of its numerical version up-to-date has not been completely accepted. A complete methodology is developed in this work to guide analyst engineers or graduate students in the calculation of electromagnetic transients of underground cable systems. Finally, to help the validation of the numerical inverse Laplace transform a scaled prototype experiment is performed in the laboratory in which a transient step-response at the remote end of an energized conductor is measured.

  18. Nonlinear and hysteretic twisting effects in ocean cable laying

    International Nuclear Information System (INIS)

    Shashaty, A.J.

    1983-01-01

    Armored ocean cable unlays under the action of installation tensions and restraining moments applied by the ocean bottom and the ship's bow sheave. The process of elongation and twist is nonlinear and hysteretic. This process has often been assumed linear and reversible. The equations describing the moment which is developed in laying cable on the ocean bottom are worked out, without assuming linearity and reversibility. These equations are applied to some cases likely to arise. For a typical armored coaxial cable laid in 3700m (2,000 fathoms) depth without bottom tension, a steady-state laying-up moment of 134Nm (99 lbs. ft.) is developed. For the reversible case, no moment is developed. If the bottom tension is increased from zero to 33,375N (7500 lbs.) and then returned to zero, a peak moment of 198Nm (146 lbs. ft.) is developed

  19. Winding mandrel design for the wide cable SSC dipole

    International Nuclear Information System (INIS)

    Morgan, G.H.; Greene, A.; Jochen, G.; Morgillo, A.

    1990-01-01

    The 50 mm coil i.d. SSC dipole magnets use wider cables to give a greater operational margin between quench field and operating field. The cable used for the inner coil has 30 strands of the same size (0.808 mm) instead of 23 and the outer has 36 strands of the same size (0.648 mm) instead of 30 and the cable widths are increased in proportion. Although the coil inner diameter has been increased from 40 mm, the coil ends are noticeably harder to wind. This report describes the computational and experimental effort to design winding mandrels or center posts for the constant-perimeter ends. 1 ref., 2 figs., 2 tabs

  20. Dynamic model and workspace analysis of novel incompletely restrained cable-suspension swing system driven by two cables

    Directory of Open Access Journals (Sweden)

    Naige Wang

    2017-03-01

    Full Text Available The incompletely restrained cable-suspension swing system driven by two cables is introduced in this article. Based on wrench of forces theory and Lagrange’s equation of first kind, the static and dynamics models of incompletely restrained cable-suspension swing system driven by two cables are established, respectively. In order to obtain an intuitive understanding of the trajectory analysis, a dynamics model consisting of governing equation and geometric constraint conditions which is a set of the mixed differential-algebraic equation in mathematics is established. A typical feedback controller and an inverse model were set up to estimate the driving function. The effective workspace, which is used to guarantee an efficient swing process, mostly depends on the geometrical shape rather than the volume itself which was calculated by trajectory analysis. In order to estimate system features and ensure a limited range of tension in underconstrained spatial cable system, the probable location of unbalanced loading was evaluated by pointwise evaluation techniques during normal work.