WorldWideScience

Sample records for solar-assisted biomass-district heating

  1. Solar-assisted biomass-district heating: projects in Austria and operational data; Solarunterstuetzte Biomasse-Fernwaermeversorgung: Projekte in Oesterreich und Betriebsdaten

    Energy Technology Data Exchange (ETDEWEB)

    Faninger, G. [Institut fuer Interdisziplinaere Forschung und Fortbildung der Universitaeten Klagenfurt, Innsbruck und Wien (IFF), Klagenfurt (Austria)

    1998-12-31

    In recent years small-volume biomass district heating systems (district heat grids) have attracted increasing interest in Austria. By the end of 1997 some 359 biomass-district heating systems with an overall capacity of approximately 483 MW were in operation. If a biomass-district heating plant and a solar plant are combined the solar plant can supply most of the heat required outside the heating season. At present Austria runs 12 solar-assisted biomass-district heating grids with collector areas between 225 square metres and 1,250 square metres. In order to run these biomass-district heating systems in an economically and technically efficient way it is necessary to assure high quality in terms of planning, construction and operation. A list of criteria is set up on the basis of first operational data in order to evaluate energy efficiency and economic performance. These criteria should be applied in order to ensure that energy, environment and economy are equally considered in the planning and construction of solar-assisted biomass-district heating plants. They should also be helpful for the approval procedures of projects. (orig.) [Deutsch] Kleinraeumige Biomasse-Fernwaermeanlagen (Nahwaermenetze) fanden in den letzten Jahren zunehmendes Interesse in Oesterreich. So waren Ende 1997 insgesamt 359 Biomasse-Fernwaermeanlagen mit einer installierten Gesamtleistung von etwa 483 MW in Betrieb. Die Kombination einer Biomasse-Fernwaermeanlage mit einer Solaranlage bringt den Vorteil, dass die Waermebereitstellung ausserhalb der Heizsaison zu einem hohen Anteil ueber die Solaranlage vorgenommen werden kann. Derzeit werden in Oesterreich 12 solarunterstuetzte Biomasse-Nahwaermenetze mit Kollektorflaechen von 225 m{sup 2} bis 1.250 m{sup 2} betrieben. Um einen moeglichst effizienten und damit auch wirtschaftlichen Betrieb von solarunterstuetzten Biomasse-Fernwaermeanlagen zu gewaehrleisten, werden hohe Anforderungen an Planung, Ausfuehrung und Betrieb gestellt. Auf der

  2. Solar-assisted district heating systems - the SOLARIS pilot plant at Chemnitz - Status report; Solar unterstuetzte Nahwaermeversorgung - Pilotanlage SOLARIS Chemnitz Statusbericht `98

    Energy Technology Data Exchange (ETDEWEB)

    Urbaneck, T.; Schirmer, U. [Technische Univ. Chemnitz (Germany). Projektgruppe Solarthermie 2000

    1998-12-31

    The solar-assisted district heating in the Technology and Industrial Park SOLARIS is currently being built. The seasonal heat storage is a gravel-water tank with a volume of 8,000 cubic metre and has already been completed. The expectations have been met with respect to using a simple technology for the construction of seasonal storage and reducing costs. The initial operation is scheduled for summer 1998. Afterwards a two-year measuring programme will control and evaluate the function of the solar-assisted district heating system. (orig.) [Deutsch] Das solar unterstuetzte Nahwaermesystem im Chemnitzer Technologie- und Gewerbepark solaris befindet sich im Bau. Der saisonale Waermespeicher, ein 8000 m{sup 3} Kies-Wasser-Speicher ist fertiggestellt. Die Erwartungen in bezug auf eine einfache Technologie zum Bau von saisonalen Speichern und in bezug auf die Einhaltung des Kostenrahmens wurden erfuellt. Die Inbetriebnahme ist im Sommer 1998 geplant. Ein zweijaehriges Messprogramm soll nach Inbetriebnahme die Funktion des solar unterstuetzten Nahwaermesystems ueberwachen. (orig.)

  3. Solar heat storages in district heating networks

    Energy Technology Data Exchange (ETDEWEB)

    Ellehauge, K. (Ellehauge og Kildemoes, AArhus (DK)); Engberg Pedersen, T. (COWI A/S, Kgs. Lyngby (DK))

    2007-07-15

    This report gives information on the work carried out and the results obtained in Denmark on storages for large solar heating plants in district heating networks. Especially in Denmark the share of district heating has increased to a large percentage. In 1981 around 33% of all dwellings in DK were connected to a district heating network, while the percentage in 2006 was about 60% (in total 1.5 mio. dwellings). In the report storage types for short term storage and long term storages are described. Short term storages are done as steel tanks and is well established technology widely used in district heating networks. Long term storages are experimental and used in connection with solar heating. A number of solar heating plants have been established with either short term or long term storages showing economy competitive with normal energy sources. Since, in the majority of the Danish district heating networks the heat is produced in co-generation plants, i.e. plants producing both electricity and heat for the network, special attention has been put on the use of solar energy in combination with co-generation. Part of this report describes that in the liberalized electricity market central solar heating plants can also be advantageous in combination with co-generation plants. (au)

  4. Design of biomass district heating systems

    International Nuclear Information System (INIS)

    Vallios, Ioannis; Tsoutsos, Theocharis; Papadakis, George

    2009-01-01

    The biomass exploitation takes advantage of the agricultural, forest, and manure residues and in extent, urban and industrial wastes, which under controlled burning conditions, can generate heat and electricity, with limited environmental impacts. Biomass can - significantly - contribute in the energy supplying system, if the engineers will adopt the necessary design changes to the traditional systems and become more familiar with the design details of the biomass heating systems. The aim of this paper is to present a methodology of the design of biomass district heating systems taking into consideration the optimum design of building structure and urban settlement around the plant. The essential energy parameters are presented for the size calculations of a biomass burning-district heating system, as well as for the environmental (i.e. Greenhouse Gas Emissions) and economic evaluation (i.e. selectivity and viability of the relevant investment). Emphasis has been placed upon the technical parameters of the biomass system, the economic details of the boiler, the heating distribution network, the heat exchanger and the Greenhouse Gas Emissions

  5. Solar district heating and cooling: A review

    DEFF Research Database (Denmark)

    Perez-Mora, Nicolas; Bava, Federico; Andersen, Martin

    2018-01-01

    and decentralized solar district heating as well as block heating. For the different technologies, the paper describes commonly adopted control strategies, system configurations, types of installation, and integration. Real‐world examples are also given to provide a more detailed insight into how solar thermal...... technology can be integrated with district heating. Solar thermal technology combined with thermally driven chillers to provide cooling for cooling networks is also included in this paper. In order for a technology to spread successfully, not only technical but also economic issues need to be tackled. Hence......Both district heating and solar collector systems have been known and implemented for many years. However, the combination of the two, with solar collectors supplying heat to the district heating network, is relatively new, and no comprehensive review of scientific publications on this topic could...

  6. District heating and combined heat and power generation from biomass

    International Nuclear Information System (INIS)

    Veski, Rein

    1999-01-01

    An Altener programme seminar District Heating and Combined Heat and Power Generation from Biomass. Minitraining seminar and study tours and also Business forum, Exhibition and Short company presentations were held in Tallinn on March 21-23, 1999. The Seminar was organised by the VTT Energy, the Estonian Bioenergy Association and the Estonian Heat and Power Association in co-operation with the AFB-net. The Agricultural and Forestry Biomass Network (AFB-net) is part of the ALTENER programme. The Network aims at promoting and stimulating the implementation and commercial utilisation of energy from biomass and waste, through the initiation of business opportunities. This includes national and international co-operation and the exchange of the personnel. The Seminar was attended by consulting companies, scientists, municipal authorities and representatives of co-ordinating bodies engaged in renewable energy management as well as DH and CHP plant managers, equipment manufacturers and local energy planners from Finland, Estonia, Latvia, Lithuania, Sweden, Denmark, Belgium, Slovenia and Slovak Republic. At the Seminar minitraining issues were dealt with: the current situation and future trends in biomass DH in the Baltic Sea countries, and biomass DH and CHP in Eastern and Central Europe, planning and construction of biomass-based DH plants, biomass fuel procurement and handling technology, combustion technology, DH networks, financing of biomass projects and evaluating of projects, and case projects in Eastern and Central European countries. The following were presented: boilers with a capacity of 100 kW or more, stoker burners, wood and straw handling equipment, wood fuel harvesters, choppers, pelletisers, district heating pipelines and networks. (author)

  7. Heating technologies for limiting biomass consumption in 100% renewable energy systems

    DEFF Research Database (Denmark)

    Mathiesen, Brian Vad; Lund, Henrik; Connolly, David

    2011-01-01

    district heating enables the use of combined heat and power production (CPH) and other renewable resources than biomass such as large-scale solar thermal, large-heat pumps, geothermal heat, industrial surplus heat etc. which is important for reducing the biomass consumption. Where the energy density......The utilisation of biomass poses large challenges in renewable energy systems and buildings account for a substantial part of the energy supply also in 100% renewable energy systems. The analyses of heating technologies show that district heating systems are especially important in limiting...... the dependence on biomass resources and to create cost effective systems. District heating systems are especially important in renewable energy systems with large amounts of fluctuating renewable energy sources as it enables fuel efficient and lower cost energy systems with thermal heat storages. And also...

  8. Design and Performance Evaluation of a Solar Assisted Heat Pump Dryer Integrated with Biomass Furnace for Red Chilli

    Directory of Open Access Journals (Sweden)

    M. Yahya

    2016-01-01

    Full Text Available The performance of a solar assisted heat pump dryer integrated with biomass furnace has been designed and evaluated for drying red chillies, and drying kinetics of red chillies were evaluated. The red chillies were dried from 22 kg with moisture content of 4.26 db to moisture content of 0.08 db which needed 11 hours, with the average drying chamber temperature, drying chamber relative humidity, and an air mass flow rate of 70.5°C, 10.1%, and 0.124 kg/s, respectively, while the open sun drying needed 62 hours. Compared to open sun drying, this dryer yielded 82% saving in drying time. The drying rate, the specific moisture extraction rate, and thermal efficiency of the dryer were estimated in average to be about 1.57 kg/h, 0.14 kg/kWh, and 9.03%, respectively. Three mathematical models, the Newton, Henderson-Pabis, and Page models, were fitted to the experimental data on red chillies dried by solar assisted heat pump dryer integrated with biomass furnace and open sun drying. The performance of these models was evaluated by comparing the coefficient of determination (R2, mean bias error (MBE, and root mean-square error (RMSE. The Page model gave the best results for representing drying kinetics of red chillies.

  9. Flexibility of Large-Scale Solar Heating Plant with Heat Pump and Thermal Energy Storage

    DEFF Research Database (Denmark)

    Luc, Katarzyna Marta; Heller, Alfred; Rode, Carsten

    2017-01-01

    to decrease biomass use in a district heating system. The paper focuses on the renewable energy-based district heating system in Marstal, Denmark, with heat produced in central solar heating plant, wood pellet boiler, heat pump and bio-oil boiler. The plant has been the object of research and developments...

  10. Biomass universal district heating systems

    Science.gov (United States)

    Soltero, Victor Manuel; Rodríguez-Artacho, Salvador; Velázquez, Ramón; Chacartegui, Ricardo

    2017-11-01

    In mild climate regions Directive 27/2012 EU application for developing sustainable district heating networks in consolidated urban nucleus is a challenge. In Spain most of the municipalities above 5,000 inhabitants have a reliable natural gas network and individual heating systems at homes. In this work a new heating network paradigm is proposed, the biomass universal heating network in rural areas. This model involves all the economic, legal and technical aspects and interactions between the different agents of the systems: provider company, individual and collective end-users and local and regional administration. The continental region in Spain has 588 municipalities with a population above 1,500 inhabitants close to forest biomass with renewable use. In many of these cases the regulation identifies the ownership of the forest resources use. The universal heating networks are a great opportunity for energy saving of 2,000 GWh, avoiding 2.7 million tons of CO2 emissions and with a global annual savings for end users of 61.8 million of euros. The presented model is easily extrapolated to other small municipalities in Europe. The real application of the model is presented for three municipalities in different locations of Spain where Universal Heating Networks are under development. The analysis show the interest of the integrated model for the three cases with different structural agents and relationships between them. The use of sustainable forest resources, extracted and managed by local companies, strengths circular economy in the region with a potential global economic impact above 200 M€.

  11. Solar-assisted district heating systems: The Solarthermie 2000-programme; Solarunterstuetzte Nahwaermeversorgung: Programm Solarthermie-2000

    Energy Technology Data Exchange (ETDEWEB)

    Lottner, V. [Forschungszentrum Juelich GmbH (Germany). Projekttraeger Biologie, Energie, Umwelt (BEO)

    1998-12-31

    In Germany, utilisation of solar energy for thermal energy supply has a considerable technical and economic potential in terms of substitution of fossil fuels and reduction of CO{sub 2} emission. If appropriate technologies are used, solar-assisted district heat supply systems can be a cost-efficient concept for thermal utilisation of solar energy. The BMBF -programme `Solarthermie 2000` supports a number of pilot and demonstration plants in order to test and develop the most promising systems and storage facilities under real conditions. Long-term measuring programmes generate reliable data on thermal performance and cost of the plant concepts and create a solid basis for a technical and economic evaluation. (orig.) [Deutsch] Die Nutzung von Solarenergie fuer die Waermeversorgung bietet in Deutschland ein grosses technisches und wirtschaftliches Potential zur Substitution fossiler Energietraeger und Reduzierung der CO{sub 2} Emissionen in die Atmosphaere. Solarunterstuetzte Nahwaermesysteme stellen unter guenstigen technischen Bedingungen ein kostenguenstiges Konzept der thermischen Nutzung der Solarenergie dar. In dem BMBF-Programm Solarthermie-2000 werden Pilot- und Demonstrationsanlagen gefoerdert, so dass die aussichtsreichsten System- und Speicherkonzepte in der Praxis erprobt und gezielt weiterentwickelt werden koennen. Mit Langzeit-Messprogrammen werden belastbare Werte der thermischen Leistung und Kosten der Anlagenkonzepte ermittelt und eine zuverlaessige Grundlage fuer die technisch-wirtschaftliche Bewertung geschaffen. (orig.)

  12. Solar-assisted district heating systems, state-of-the-art and economic efficiency; Solarunterstuetzte Nahwaermeversorgung Stand der Technik und Wirtschaftlichkeit

    Energy Technology Data Exchange (ETDEWEB)

    Fisch, M.N. [Technische Univ. Braunschweig (Germany). Inst. fuer Gebaeude- und Solartechnik; Kuebler, R. [Steinbeis Transferzentrum Energie-, Gebaeude- und Solartechnik (STZ-IGS), Stuttgart (Germany)

    1998-12-31

    After the successful testing of smaller solar-assisted district heat supply projects in the first half of the Nineties in Germany (e.g. Ravensburg, Koengen, Neckarsulm, Schwaebisch-Gmuend), the first large-scale plants with long term heat storage started to operate in Hamburg and Friedrichshafen. Thus a target has been reached that had seemed to be an illusion for a long time - the utilisation of solar energy generated in the summer for building heating in wintertime. In Hamburg (collector area = 3,000 square metres) and Friedrichshafen (collector area = 5,600 square metres when finished) buried hot-water storage tanks with a volume of 4,500 cubic metres and 12,000 cubic metres were built; bore-hole heat storage is being tested in a third demonstration project in Neckarsulm. The first part of this plant (collector area = 2,700 square metres, storage capacity approximately 20,000 cubic metres) was put in operation in October 1997. A fourth solar-assisted district heating system with a gravel/water heat storage (volume approximately 8,000 cubic metres) is currently under construction in Chemnitz and supposed to be completed in the second half of 1998. (orig.) [Deutsch] Nach der erfolgreichen Erprobung von kleineren solarunterstuetzten Nahwaermeprojekten in der ersten Haelfte der neunziger Jahre in Deutschland (z.B. Ravensburg, Koengen, Neckarsulm, Schwaebisch-Gmuend) gingen Ende 1996 in Hamburg und Friedrichshafen die ersten solaren Grossanlagen mit Langzeit-Waermespeicher in Betrieb. Damit wurde ein Ziel erreicht, das ueber viele Jahre hinweg utopisch erschienen war - mit der Sonnenenergie aus dem Sommer im Winter die Gebaeude zu beheizen. Waehrend in Hamburg (Kollektorflaeche 3.000 m{sup 2}) und in Friedrichshafen (5.600 m{sup 2} im Endausbau) eingegrabene Heisswasser-Waermespeicher mit einem Volumen von 4.500 m{sup 3} bzw. 12.000 m{sup 3} realisiert wurden, wird in einem dritten Demonstrationsprojekt in Neckarsulm ein Erdsonden-Waermespeicher erprobt. Die erste

  13. Technoeconomic analysis of a biomass based district heating system

    International Nuclear Information System (INIS)

    Zhang, H.; Ugursal, V.I.; Fung, A.

    2005-01-01

    This paper discussed a proposed biomass-based district heating system to be built for the Pictou Landing First Nation Community in Nova Scotia. The community centre consists of 6 buildings and a connecting arcade. The methodology used to size and design heating, ventilating and air conditioning (HVAC) systems, as well as biomass district energy systems (DES) were discussed. Annual energy requirements and biomass fuel consumption predictions were presented, along with cost estimates. A comparative assessment of the system with that of a conventional oil fired system was also conducted. It was suggested that the design and analysis methodology could be used for any similar application. The buildings were modelled and simulated using the Hourly Analysis Program (HAP), a detailed 2-in-1 software program which can be used both for HVAC system sizing and building energy consumption estimation. A techno-economics analysis was conducted to justify the viability of the biomass combustion system. Heating load calculations were performed assuming that the thermostat was set constantly at 22 degrees C. Community centre space heating loads due to individual envelope components for 3 different scenarios were summarized, as the design architecture for the buildings was not yet finalized. It was suggested that efforts should be made to ensure air-tightness and insulation levels of the interior arcade glass wall. A hydronic distribution system with baseboard space heating units was selected, comprising of a woodchip boiler, hot water distribution system, convective heating units and control systems. The community has its own logging operation which will provide the wood fuel required by the proposed system. An outline of the annual allowable harvest covered by the Pictou Landing Forestry Management Plan was presented, with details of proposed wood-chippers for the creation of biomass. It was concluded that the woodchip combustion system is economically preferable to the

  14. Thermal performance of solar district heating plants in Denmark

    DEFF Research Database (Denmark)

    Furbo, Simon; Perers, Bengt; Bava, Federico

    2014-01-01

    The market for solar heating plants connected to district heating systems is expanding rapidly in Denmark. It is expected that by the end of 2014 the 10 largest solar heating plants in Europe will be located in Denmark. Measurements from 23 Danish solar heating plants, all based on flat plate solar...... collectors mounted on the ground, shows measured yearly thermal performances of the solar heating plants placed in the interval from 313 kWh/m² collector to 493 kWh/m² collector with averages for all plants of 411 kWh/m² collector for 2012 and 450 kWh/m² collector for 2013. Theoretical calculations show...... of the cost/performance ratio for solar collector fields, both with flat plate collectors and with concentrating tracking solar collectors. It is recommended to continue monitoring and analysis of all large solar heating plants to document the reliability of the solar heating plants. It is also recommended...

  15. Feasibility Study on Solar District Heating in China

    DEFF Research Database (Denmark)

    Huang, Junpeng; Fan, Jianhua; Furbo, Simon

    This paper analyzes the feasibility of developing solar district heating (SDH) in China from the perspective of incentive policy, selections of technical route, regional adaptability and economic feasibility for clean heating. Based on the analyzation, this proposes a road map for the development...

  16. Testing, development and demonstration of large scale solar district heating systems

    DEFF Research Database (Denmark)

    Furbo, Simon; Fan, Jianhua; Perers, Bengt

    2015-01-01

    In 2013-2014 the project “Testing, development and demonstration of large scale solar district heating systems” was carried out within the Sino-Danish Renewable Energy Development Programme, the so called RED programme jointly developed by the Chinese and Danish governments. In the project Danish...... know how on solar heating plants and solar heating test technology have been transferred from Denmark to China, large solar heating systems have been promoted in China, test capabilities on solar collectors and large scale solar heating systems have been improved in China and Danish-Chinese cooperation...

  17. Performance Analysis of Solar Assisted Fluidized Bed Dryer Integrated Biomass Furnace with and without Heat Pump for Drying of Paddy

    Directory of Open Access Journals (Sweden)

    M. Yahya

    2016-01-01

    Full Text Available The performances of a solar assisted fluidized bed dryer integrated biomass furnace (SA-FBDIBF and a solar assisted heat pump fluidized bed dryer integrated biomass furnace (SAHP-FBDIBF for drying of paddy have been evaluated, and also drying kinetics of paddy were determined. The SA-FBDIBF and the SAHP-FBDIBF were used to dry paddy from 11 kg with moisture content of 32.85% db to moisture content of 16.29% db (14% wb under an air mass flow rate of 0.1037 kg/s within 29.73 minutes and 22.95 minutes, with average temperatures and relative humidities of 80.3°C and 80.9°C and 12.28% and 8.14%, respectively. The average drying rate, specific energy consumption, and specific moisture extraction rate were 0.043 kg/minute and 0.050 kg/minute, 5.454 kWh/kg and 4.763 kWh/kg, and 0.204 kg/kWh and 0.241 kg/kWh for SA-FBDIBF and SAHP-FBDIBF, respectively. In SA-FBDIBF and SAHP-FBDIBF, the dryer thermal efficiencies were average values of 12.28% and 15.44%; in addition, the pickup efficiencies were 33.55% and 43.84% on average, whereas the average solar and biomass fractions were 10.9% and 10.6% and 36.6% and 30.4% for SA-FBDIBF and SAHP-FBDIBF, respectively. The drying of paddy occurred in the falling rate period. The experimental dimensionless moisture content data were fitted to three mathematical models. Page’s model was found best to describe the drying behaviour of paddy.

  18. The underground heat storage for solar-assisted district heating in Neckarsulm. First measuring results; Der Erdsonden-Waermespeicher fuer die solarunterstuetzte Nahwaermeversorgung in Neckarsulm. Erste Messergebnisse

    Energy Technology Data Exchange (ETDEWEB)

    Seiwald, H.; Hahne, E. [Stuttgart Univ. (Germany). Inst. fuer Thermodynamik und Waermetechnik

    1998-12-31

    A solar-assisted district heating system with seasonal underground heat storage is currently under construction in Neckarsulm (Baden-Wurttemberg). In the new residential area approximately 1,300 flats are going to be built during the next years. The overall energy demand (hot water and space heating) is supposed to be covered by 50% with solar energy. During the first phase the project will be subsidised in the frame of the BMBF programme `Solarthermie 2000, Teilprogramm III`. A solar plant consisting of 2,700 square metres of collectors, a buffer tank (100 cubic metre) and an underground heat storage with a volume of approx. 20,000 cubic metres will be constructed by the end of 1998. It will be the first plant in Germany where thermal energy generated of solar energy is stored at high temperatures (up to 80 C) directly in the earth and utilised without a heat pump. (orig.) [Deutsch] In Neckarsulm (Baden-Wuerttemberg) befindet sich derzeit eine solar unterstuetzte Nahwaermeversorgung mit saisonalem Endsonden-Waermespeicher im Aufbau. Im Neubaugebiet Amorbach werden in den naechsten Jahren rund 1300 Wohneinheiten entstehen, deren Gesamtwaermebedarf (Warmwasser und Raumheizung) zu rund 50% mit Sonnenenergie gedeckt werden soll. In der ersten Phase wird das Projekt im Rahmen des BMBF-Programms `Solarthermie 2000, Teilprogramm III` gefoerdert. Bis Ende 1998 wird eine Solaranlage bestehend aus 2.700 m{sup 2} Kollektoren, einem Pufferspeicher (100 m{sup 3}) und einem Endsonden-Waermespeicher mit einem Volumen von ca. 20.000 m{sup 3} erstellt. Damit wird in Deutschland erstmalig eine Anlage realisiert, bei der solar erzeugte Waerme auf hohem Temperaturniveau (bis zu 80 C) direkt im Erdreich gespeichert und ohne Waermepumpe genutzt werden soll. (orig.)

  19. Biomass fuels in district heating systems. Final report. Biobrensel i fjernvarmesystem. Sluttrapport

    Energy Technology Data Exchange (ETDEWEB)

    Otterstad, B.

    1987-02-01

    The report deals with an energy conservation project on district heating. The project gives a cost comparison between a biomass fuelled system for the local water heating/electric power supply and the development of hydroelectric power. The computer program ESENTRAL is used in the simulation. 3 drawings.

  20. White Pine Co. Public School System Biomass Conversion Heating Project

    Energy Technology Data Exchange (ETDEWEB)

    Paul Johnson

    2005-11-01

    The White Pine County School District and the Nevada Division of Forestry agreed to develop a pilot project for Nevada using wood chips to heat the David E. Norman Elementary School in Ely, Nevada. Consideration of the project was triggered by a ''Fuels for Schools'' grant that was brought to the attention of the School District. The biomass project that was part of a district-wide energy retrofit, called for the installation of a biomass heating system for the school, while the current fuel oil system remained as back-up. Woody biomass from forest fuel reduction programs will be the main source of fuel. The heating system as planned and completed consists of a biomass steam boiler, storage facility, and an area for unloading and handling equipment necessary to deliver and load fuel. This was the first project of it's kind in Nevada. The purpose of the DOE funded project was to accomplish the following goals: (1) Fuel Efficiency: Purchase and install a fuel efficient biomass heating system. (2) Demonstration Project: Demonstrate the project and gather data to assist with further research and development of biomass technology; and (3) Education: Educate the White Pine community and others about biomass and other non-fossil fuels.

  1. Limiting biomass consumption for heating in 100% renewable energy systems

    DEFF Research Database (Denmark)

    Mathiesen, Brian Vad; Lund, Henrik; Connolly, David

    2012-01-01

    -scale solar thermal, large heat pumps, geothermal heat, industrial surplus heat, and waste incineration. Where the energy density in the building stock is not high enough for DH to be economical, geothermal heat pumps can be recommended for individual heating systems, even though biomass consumption is higher......The utilisation of biomass poses large challenges in renewable energy systems while buildings account for a substantial part of the energy supply even in 100% renewable energy systems. In this paper the focus is on how the heating sector can reduce its consumption of biomass, thus leaving biomass...... for other sectors, but while still enabling a 100% renewable energy system. The analyses of heating technologies shows that district heating (DH) systems are important in limiting the dependence on biomass and create cost effective solutions. DH systems are especially important in renewable energy systems...

  2. Experimental study of a photovoltaic solar-assisted heat-pump/heat-pipe system

    International Nuclear Information System (INIS)

    Fu, H.D.; Pei, G.; Ji, J.; Long, H.; Zhang, T.; Chow, T.T.

    2012-01-01

    A practical design for a heat pump with heat-pipe photovoltaic/thermal (PV/T) collectors is presented. The hybrid system is called the photovoltaic solar-assisted heat-pump/heat-pipe (PV-SAHP/HP) system. To focus on both actual demand and energy savings, the PV-SAHP/HP system was designed to be capable of operating in three different modes, namely, the heat-pipe, solar-assisted heat pump, and air-source heat-pump modes. Based on solar radiation, the system operates in an optimal mode. A series of experiments were conducted in Hong Kong to study the performance of the system when operating in the heat-pipe and the solar-assisted heat-pump modes. Moreover, energy and exergy analyses were used to investigate the total PV/T performance of the system. - Highlights: ► A novel PV-SAHP/HP system with three different operating modes was proposed. ► Performance of the PV-SAHP/HP system was studied experimentally. ► A optimal operating mode of the PV-SAHP/HP system was suggested in this paper.

  3. Solar-assisted heat pump system for cost-effective space heating and cooling

    Energy Technology Data Exchange (ETDEWEB)

    Andrews, J W; Kush, E A; Metz, P D

    1978-03-01

    The use of heat pumps for the utilization of solar energy is studied. Two requirements for a cost-effective system are identified: (1) a special heat pump whose coefficient of performance continues to rise with source temperature over the entire range appropriate for solar assist, and (2) a low-cost collection and storage subsystem able to supply solar energy to the heat pump efficiently at low temperatures. Programs leading to the development of these components are discussed. A solar assisted heat pump system using these components is simulated via a computer, and the results of the simulation are used as the basis for a cost comparison of the proposed system with other solar and conventional systems.

  4. A cost-effective evaluation of biomass district heating in rural communities

    International Nuclear Information System (INIS)

    Hendricks, Aaron M.; Wagner, John E.; Volk, Timothy A.; Newman, David H.; Brown, Tristan R.

    2016-01-01

    Highlights: • Develop a cost-effective model using secondary data examining delivering heat through Biomass District Heating (BDH). • Eight of ten rural villages studied could cost-effectively deliver heat through BDH below the 2013 price of heating oil. • 80% of the annual cost of BDH was attributable to capital expenses. • Erratic fuel oil prices substantially impact future feasibility. • Village level feasibility is highly-influenced by the presence of large heat demanders. - Abstract: The economic feasibility of Biomass District Heating (BDH) networks in rural villages is largely unknown. A cost-effective evaluation tool is developed to examine the feasibility of BDH in rural communities using secondary data sources. The approach is unique in that it accounts for all the major capital expenses: energy center, distribution network, and energy transfer stations, as well as biomass procurement. BDH would deliver heat below #2 fuel oil in eight of the ten rural study villages examined, saving nearly $500,000 per year in heating expenses while demanding less than 5% of the forest residues sustainably available regionally. Capital costs comprised over 80% of total costs, illuminating the importance of reaching a sufficient heat density. Reducing capital costs by 1% lowers total cost by $93,000 per year. Extending capital payment period length five years or lowering interest rates has the next highest influence decreasing delivered heat price 0.49% and 0.35% for each 1% change, respectively. This highlights that specific building heat is a strong determinant of feasibility given the relative influence of high-demanding users on the overall village heat-density. Finally, we use a stochastic analysis projecting future #2 fuel oil prices, incorporating historical variability, to determine the probability of future BDH feasibility. Although future oil prices drop below the BDH feasibility threshold, the villages retain a 22–53% probability of feasibility after

  5. Annex to Solar heat storages in district heating networks. Comprehensive list of Danish literature and R and D projects

    Energy Technology Data Exchange (ETDEWEB)

    Ellehauge, K. (Ellehauge og Kildemoes, AArhus (DK)); Engberg Pedersen, T. (COWI A/S, Kgs. Lyngby (DK))

    2007-07-15

    This annex relates to the report 'Solar heat storages in district heating networks', which has been elaborated to inform about the Danish experiences and findings on the use of central solar heating plants in district heating networks, especially with the focus on the development of the storage part of the systems. The report has been funded as part of the IEE PREHEAT cooperation and by Energinet.dk, project no. 2006-2-6750. (au)

  6. Road map for district heating. The role of district heating in the energy system. Main report; Denmark; Roadmap for fjernvarmen. Fjernvarmens rolle i energisystemet. Hovedrapport

    Energy Technology Data Exchange (ETDEWEB)

    Hofmeister, M.; Aabye Moeller, A.; Eggert, A.; Bjerregaard, M. (Fjernvarmens Udviklingscenter, AArhus (Denmark)); Dyrelund, A. (Ramboell, Koebenhavn (Denmark)); OErsted Pedersen, H. (Ea Energianalyse, Koebenhavn (Denmark)); Lund, H. (Aalborg Univ., Aalborg (Denmark))

    2011-07-01

    In the recent years many studies of how Denmark can be fossil free by 2050 it is agreed that district heating will play a crucial role. District heating is an important factor of phasing out fossil fuels in an energy-and cost-effective way. But the future energy supply without fossil fuels poses new requirements for district heating. In the future, district heating shall provide energy for low-energy houses, have low distribution losses and use a variety of heat sources such as geothermal, solar, waste, surplus heat, CHP and various biomass con-version processes. In addition, it must all be done in an energy efficient way and in an active interaction with production of electricity and electricity consumption and, through integration of electricity from wind, solar and wave power. Low temperature, use of heat pumps and the interaction with electricity and biomass will be keywords. It is not only in Denmark we will need an active development of future technologies and systems. Large parts of Europe and many other parts of the world need the same development, and today Denmark has a significant export in the market - an export that has risen sharply, despite the recent economic recession. There is thus a double need to actively promote the development of future district heating technologies. We will partly need the technology development to realize the goal of a fossil free society and secondly because it is necessary to maintain and expand the export. This report contains a number of proposals for concrete actions - a roadmap for the development of district heating. The project is anchored at the District Energy Development Center that will work for an implementation of the concrete project ideas after the project completion. There is a need to increase the activity level for development of district heating. There is therefore a need to ensure financing of this development. We suggest that this can be done by creating an opportunity for a more sustained funding, for

  7. Road map for district heating. The role of district heating in the energy system. Summary report; Denmark; Roadmap for fjernvarmen. Fjernvarmens rolle i energisystemet. Resumerapport

    Energy Technology Data Exchange (ETDEWEB)

    Hofmeister, M.; Aabye Moeller, A.; Eggert, A.; Bjerregaard, M. (Fjernvarmens Udviklingscenter, AArhus (Denmark)); Dyrelund, A. (Ramboell, Koebenhavn (Denmark)); OErsted Pedersen, H. (Ea Energianalyse, Koebenhavn (Denmark)); Lund, H. (Aalborg Univ., Aalborg (Denmark))

    2011-07-01

    In the recent years many studies of how Denmark can be fossil free by 2050 it is agreed that district heating will play a crucial role. District heating is an important factor of phasing out fossil fuels in an energy-and cost-effective way. But the future energy supply without fossil fuels poses new requirements for district heating. In the future, district heating shall provide energy for low-energy houses, have low distribution losses and use a variety of heat sources such as geothermal, solar, waste, surplus heat, CHP and various biomass con-version processes. In addition, it must all be done in an energy efficient way and in an active interaction with production of electricity and electricity consumption and, through integration of electricity from wind, solar and wave power. Low temperature, use of heat pumps and the interaction with electricity and biomass will be keywords. It is not only in Denmark we will need an active development of future technologies and systems. Large parts of Europe and many other parts of the world need the same development, and today Denmark has a significant export in the market - an export that has risen sharply, despite the recent economic recession. There is thus a double need to actively promote the development of future district heating technologies. We will partly need the technology development to realize the goal of a fossil free society and secondly because it is necessary to maintain and expand the export. This report contains a number of proposals for concrete actions - a roadmap for the development of district heating. The project is anchored at the District Energy Development Center that will work for an implementation of the concrete project ideas after the project completion. There is a need to increase the activity level for development of district heating. There is therefore a need to ensure financing of this development. We suggest that this can be done by creating an opportunity for a more sustained funding, for

  8. Development of Solar Biomass Drying System

    Directory of Open Access Journals (Sweden)

    Atnaw Samson Mekbib

    2017-01-01

    Full Text Available The purpose of this paper focuses on the experimental pre-treatment of biomass in agricultural site using solar energy as power source and contribution of common use and efficiency solar dryer system for consumer. The main purpose of this design for solar cabinet dryer is to dry biomass via direct and indirect heating. Direct heating is the simplest method to dry biomass by exposing the biomass under direct sunlight. The solar cabinet dryer traps solar heat to increase the temperature of the drying chamber. The biomass absorbs the heat and transforms the moisture content within the biomass into water vapour and then leaves the chamber via the exhaust air outlet. This problem however can be solved by adopting indirect solar drying system. High and controllable temperatures can be achieved as a fan is used to move the air through the solar collector. This project has successfully created a solar cabinet dryer that combines both direct and indirect solar drying systems and functions to dry biomass as well as crops effectively and efficiently with minimal maintenance. Hence, it is indeed a substitution for conventional dryers which are affordable to local farmers.

  9. Solar-assisted district heating system - Scientific study. Solar-assisted district heating system with long-term thermal storage in Friedrichshafen-Wiggenhausen and Hamburg-Bramfeld.. Results of the first year of operation; Solar unterstuetzte Nahwaermeversorgung - Wissenschaftliches Begleitprogramm. Solare Nahwaermeversorgung mit Langzeitwaermespeicher in Friedrichshafen-Wiggenhausen und Hamburg-Bramfeld. Ergebnisse des ersten Betriebsjahres

    Energy Technology Data Exchange (ETDEWEB)

    Schulz, M.E.; Mahler, B.; Hahne, E. [Stuttgart Univ. (Germany). Inst. fuer Thermodynamik und Waermetechnik

    1998-12-31

    The first two pilot plants for solar district heating with seasonal thermal energy storage were put in operation in October 1996. Both projects were initiated by the Institute for Thermodynamics and Thermal Energy Technology (ITW) of the University of Stuttgart that also provided scientific support up to the present. This report presents the results of the first two years of operation of both plants. Both solar plants have been operated without any major problems. The solar energy yield in the first year of operation has only been reduced by the unsatisfactory operation of the heating grid. The most important step towards optimising the plants is the adjustment of the internal heating systems and thus the reduction of the heating temperatures which are currently too high. Based on subject pre-conditions the results projected for the first pilot plants for solar district heating and long-term thermal energy storage will be reached in the following years of operation. (orig.) [Deutsch] Im Oktober 1996 gingen die ersten beiden Pilotanlagen zur solaren Nahwaermeversorgung mit saisonaler Waermespeicherung in Betrieb. Beide Projekte wurden vom Institut fuer Thermodynamik und Waermetechnik (ITW), Universitaet Stuttgart initiiert und ueber die gesamte bisherige Laufzeit wissenschaftlich begleitet. Die Ergebnisse des ersten Betriebsjahres der beiden Anlagen sind in diesem Bericht zusammengestellt. In beiden Faellen funktionieren die Solaranlagen ohne grosse Probleme. Die solaren Ertraege wurden im ersten Betriebsjahr noch durch die unzureichende Betriebsweise der Heiznetze gemindert. Wichtigster Ansatzpunkt fuer eine Optimierung der Anlagen ist die Einregulierung der hausinternen Heizungssysteme und damit die Absenkung der derzeit noch zu hohen Heiznetztemperaturen. Unter dieser Voraussetzung werden die vorausgesagten Ergebnisse fuer die ersten Pilotanlagen zur solaren Nahwaerme mit Langzeit-Waermespeicher in den naechsten Betriebsjahren erreicht werden. (orig.)

  10. Combined use of solar heat and cogeneration - a perspective for district heating?; Kombinierter Einsatz von solarer Waerme und Kraft-Waerme-Kopplung - eine Perspektive fuer die Nahwaerme?

    Energy Technology Data Exchange (ETDEWEB)

    Entress, J. [Deutsches Zentrum fuer Luft- und Raumfahrt (DLR), Stuttgart (Germany). Abt. Systemanalyse und Technikbewertung; Steinborn, F. [Zentrum fuer Sonnenenergie- und Wasserstoff-Forschung Baden-Wuerttemberg (ZSW), Stuttgart (Germany). Fachgebiet Systemanalyse

    1998-02-01

    With Cogeneration of Heat and Power (CHP), climate-endangering CO{sub 2}-emissions can be reduced singificantly. The heat produced can be delivered at prices comparable to those of conventionally produced heat. With solar district heating, yet higher CO{sub 2}-savings are possible but at higher cost. Promising is a combination of CHP and solar district heating: The heat storage of the solar system can be used to level out heat demand, leading to smooth CHP operation, while heat generated by CHP can be used to substitute for low irradiation during the winter period. However, calculations together with simulation and optimization indicate that combining CHP and solar district heating is not the optimal solution in all cases. (orig.) [Deutsch] Der Einsatz von Blockheizkraftwerken (BHKW) kann zu einer deutlichen Reduzierung der klimagefaehrdenden CO{sub 2}-Emissionen beitragen. Dabei kann die ausgekoppelte Waerme etwa zum gleichen Preis wie konventionell erzeugte Waerme abgegeben werden. Hoehere CO{sub 2}-Einsparungen lassen sich hingegen mit solarer Nahwaerme erzielen, allerdings zu hoeheren Kosten. Eine Kombination dieser beiden Waermetechniken verspricht Vorteile: Einerseits kann der Waermespeicher des Solarsystems auch zum Ausgleich von Lastspitzen beim Betrieb des BHKW`s genutzt werden. Andererseits kann die waehrend der einstrahlungsarmen Wintermonate fehlende solare Waerme durch das BHKW erzeugt werden. Detaillierte Simulations- und Optimierungsrechnungen zeigen jedoch, dass eine Kombination dieser Waermetechniken nicht immer empfehlenswert ist. (orig.)

  11. Building Space Heating with a Solar-Assisted Heat Pump Using Roof-Integrated Solar Collectors

    Directory of Open Access Journals (Sweden)

    Zhiyong Yang

    2011-03-01

    Full Text Available A solar assisted heat pump (SAHP system was designed by using a roof-integrated solar collector as the evaporator, and then it was demonstrated to provide space heating for a villa in Tianjin, China. A building energy simulation tool was used to predict the space heating load and a three dimensional theoretical model was established to analyze the heat collection performance of the solar roof collector. A floor radiant heating unit was used to decrease the energy demand. The measurement results during the winter test period show that the system can provide a comfortable living space in winter, when the room temperature averaged 18.9 °C. The average COP of the heat pump system is 2.97 and with a maximum around 4.16.

  12. Biomass gasification in district heating systems - The effect of economic energy policies

    International Nuclear Information System (INIS)

    Wetterlund, Elisabeth; Soederstroem, Mats

    2010-01-01

    Biomass gasification is considered a key technology in reaching targets for renewable energy and CO 2 emissions reduction. This study evaluates policy instruments affecting the profitability of biomass gasification applications integrated in a Swedish district heating (DH) system for the medium-term future (around year 2025). Two polygeneration applications based on gasification technology are considered in this paper: (1) a biorefinery plant co-producing synthetic natural gas (SNG) and district heat; (2) a combined heat and power (CHP) plant using integrated gasification combined cycle technology. Using an optimisation model we identify the levels of policy support, here assumed to be in the form of tradable certificates, required to make biofuel production competitive to biomass based electricity generation under various energy market conditions. Similarly, the tradable green electricity certificate levels necessary to make gasification based electricity generation competitive to conventional steam cycle technology, are identified. The results show that in order for investment in the SNG biorefinery to be competitive to investment in electricity production in the DH system, biofuel certificates in the range of 24-42 EUR/MWh are needed. Electricity certificates are not a prerequisite for investment in gasification based CHP to be competitive to investment in conventional steam cycle CHP, given sufficiently high electricity prices. While the required biofuel policy support is relatively insensitive to variations in capital cost, the required electricity certificates show high sensitivity to variations in investment costs. It is concluded that the large capital commitment and strong dependency on policy instruments makes it necessary that DH suppliers believe in the long-sightedness of future support policies, in order for investments in large-scale biomass gasification in DH systems to be realised.

  13. Evaluation of Excess Heat Utilization in District Heating Systems by Implementing Levelized Cost of Excess Heat

    Directory of Open Access Journals (Sweden)

    Borna Doračić

    2018-03-01

    Full Text Available District heating plays a key role in achieving high primary energy savings and the reduction of the overall environmental impact of the energy sector. This was recently recognized by the European Commission, which emphasizes the importance of these systems, especially when integrated with renewable energy sources, like solar, biomass, geothermal, etc. On the other hand, high amounts of heat are currently being wasted in the industry sector, which causes low energy efficiency of these processes. This excess heat can be utilized and transported to the final customer by a distribution network. The main goal of this research was to calculate the potential for excess heat utilization in district heating systems by implementing the levelized cost of excess heat method. Additionally, this paper proves the economic and environmental benefits of switching from individual heating solutions to a district heating system. This was done by using the QGIS software. The variation of different relevant parameters was taken into account in the sensitivity analysis. Therefore, the final result was the determination of the maximum potential distance of the excess heat source from the demand, for different available heat supplies, costs of pipes, and excess heat prices.

  14. Performance analysis of a solar-assisted swimming pool heating system

    Energy Technology Data Exchange (ETDEWEB)

    Alkhamis, A I; Sherif, S A [Miami Univ., Coral Gables, FL (United States). Dept. of Mechanical Engineering

    1991-12-31

    This paper discusses feasibility studies for a solar-assisted heating system using a computer simulation program. The solar heating is accomplished by employing hot water generated by heat exchange with the solar collector working fluid. The performance of the system is analysed from both thermodynamic and economic standpoints and general conclusions are reached. 17 refs., 7 figs.

  15. Technoeconomic analysis of a biomass based district heating system. Paper no. IGEC-1-ID01

    International Nuclear Information System (INIS)

    Zhang, H.; Ugursal, V.I.; Fung, A.

    2005-01-01

    District energy systems (DES) that produce steam, hot water or chilled water at a central plant and then distribute that energy to buildings in the district for space heating, domestic hot water heating and air conditioning provide opportunities for increasing energy efficiency and reducing greenhouse gas (GHG) emissions. Use of biomass, such as wood, wood byproducts and wastes, fast-growing trees, agricultural crops and waste, in place of conventional fossil fuels to produce the thermal energy needed by a DES, presents further opportunities for reducing green house gas emissions as well as providing rural employment, and local solutions to rural and remote energy needs. In this paper, a technoeconomic analysis of a biomass based DES for a community center in Nova Scotia, Canada is presented. The methodology used to size and design the heating and ventilating system, as well as the biomass based DES is discussed. Annual energy requirement and biomass fuel consumption predictions are presented along with cost estimates. A comparative assessment of the economic feasibility of the system vis-a-vis a conventional oil fired system is conducted. While the results are specific to the particular application, the design and analysis methodology that is presented in the paper can be used for any similar application. (author)

  16. An analysis of solar assisted ground source heat pumps in cold climates

    International Nuclear Information System (INIS)

    Emmi, Giuseppe; Zarrella, Angelo; De Carli, Michele; Galgaro, Antonio

    2015-01-01

    Highlights: • The work focuses on solar assisted ground source heat pump in cold climates. • Multi-year simulations of SAGSHP, are carried out in six cold locations. • GSHP and SAGSHP are compared. • The effect of total borehole length on the heat pump energy efficiency is studied. • A dedicated control strategy is used to manage both solar and ground loops. - Abstract: Exploiting renewable energy sources for air-conditioning has been extensively investigated over recent years, and many countries have been working to promote the use of renewable energy to decrease energy consumption and CO_2 emissions. Electrical heat pumps currently represent the most promising technology to reduce fossil fuel usage. While ground source heat pumps, which use free heat sources, have been taking significant steps forward and despite the fact that their energy performance is better than that of air source heat pumps, their development has been limited by their high initial investment cost. An alternative solution is one that uses solar thermal collectors coupled with a ground source heat pump in a so-called solar assisted ground source heat pump. A ground source heat pump system, used to heat environments located in a cold climate, was investigated in this study. The solar assisted ground source heat pump extracted heat from the ground by means of borehole heat exchangers and it injected excess solar thermal energy into the ground. Building load profiles are usually heating dominated in cold climates, but when common ground source heat pump systems are used only for heating, their performance decreases due to an unbalanced ground load. Solar thermal collectors can help to ensure that systems installed in cold zones perform more efficiently. Computer simulations using a Transient System Simulation (TRNSYS) tool were carried out in six cold locations in order to investigate solar assisted ground source heat pumps. The effect of the borehole length on the energy efficiency of

  17. Thermo-economic optimization of a hybrid solar district heating plant with flat plate collectors and parabolic trough collectors in series

    DEFF Research Database (Denmark)

    Tian, Zhiyong; Perers, Bengt; Furbo, Simon

    2018-01-01

    heating network in this study. The results also show that parabolic trough collectors are economically feasible for district heating networks in Denmark. The generic and multivariable levelized cost of heat method can guide engineers and designers on the design, construction and control of large...... to optimize the hybrid solar district heating systems based on levelized cost of heat. It is found that the lowest net levelized cost of heat of hybrid solar heating plants could reach about 0.36 DKK/kWh. The system levelized cost of heat can be reduced by 5–9% by use of solar collectors in the district...

  18. Theoretical energy and exergy analyses of solar assisted heat pump space heating system

    Directory of Open Access Journals (Sweden)

    Atmaca Ibrahim

    2014-01-01

    Full Text Available Due to use of alternative energy sources and energy efficient operation, heat pumps come into prominence in recent years. Especially in solar-assisted heat pumps, sizing the required system is difficult and arduous task in order to provide optimum working conditions. Therefore, in this study solar assisted indirect expanded heat pump space heating system is simulated and the results of the simulation are compared with available experimental data in the literature in order to present reliability of the model. Solar radiation values in the selected region are estimated with the simulation. The case study is applied and simulation results are given for Antalya, Turkey. Collector type and storage tank capacity effects on the consumed power of the compressor, COP of the heat pump and the overall system are estimated with the simulation, depending on the radiation data, collector surface area and the heating capacity of the space. Exergy analysis is also performed with the simulation and irreversibility, improvement potentials and exergy efficiencies of the heat pump and system components are estimated.

  19. Validated TRNSYS Model for Solar Assisted Space Heating System

    International Nuclear Information System (INIS)

    Abdalla, Nedal

    2014-01-01

    The present study involves a validated TRNSYS model for solar assisted space heating system as applied to a residential building in Jordan using new detailed radiation models of the TRNSYS 17.1 and geometric building model Trnsys3d for the Google SketchUp 3D drawing program. The annual heating load for a building (Solar House) which is located at the Royal ScientiFIc Society (RS5) in Jordan is estimated under climatological conditions of Amman. The aim of this Paper is to compare measured thermal performance of the Solar House with that modeled using TRNSYS. The results showed that the annual measured space heating load for the building was 6,188 kWh while the heati.ng load for the modeled building was 6,391 kWh. Moreover, the measured solar fraction for the solar system was 50% while the modeled solar fraction was 55%. A comparison of modeled and measured data resulted in percentage mean absolute errors for solar energy for space heating, auxiliary heating and solar fraction of 13%, 7% and 10%, respectively. The validated model will be useful for long-term performance simulation under different weather and operating conditions.(author)

  20. Review on advanced of solar assisted chemical heat pump dryer for agriculture produce

    International Nuclear Information System (INIS)

    Fadhel, M.I.; Sopian, K.; Daud, W.R.W.; Alghoul, M.A.

    2011-01-01

    Over the past three decades there has been nearly exponential growth in drying R and D on a global scale. Improving of the drying operation to save energy, improve product quality as well as reduce environmental effect remained as the main objectives of any development of drying system. A solar assisted chemical heat pump dryer is a new solar drying system, which have contributed to better cost-effectiveness and better quality dried products as well as saving energy. A solar collector is adapted to provide thermal energy in a reactor so a chemical reaction can take place. This reduces the dependency of the drying technology on fossil energy for heating. In this paper a review on advanced of solar assisted chemical heat pump dryer is presented (the system model and the results from experimental studies on the system performance are discussed). The review of heat pump dryers and solar assisted heat pump dryer is presented. Description of chemical heat pump types and the overview of chemical heat pump dryer are discussed. The combination of chemical heat pump and solar technology gives extra efficiency in utilizing energy. (author)

  1. District heating as the infrastructure for competition among fuels and technologies

    DEFF Research Database (Denmark)

    Grohnheit, Poul Erik; Mortensen, Bent Ole Gram

    2016-01-01

    for increased energy efficiency. Additional technologies suitable for small-scale networks are heat pumps, solar panels and local biomass in the form of straw or biogas. For large-scale urban networks, incineration of urban waste and geothermal heat are key technologies. With heat storages district heating...... infrastructure can contribute significantly to balancing the intermittency of wind power. This paper is an update of the authors' article published in Energy Policy in 2003 focusing on the European directives focusing on competition in the electricity and gas network industries and promotion of renewables...... and cogeneration but limited support for the development and expansion of the district heating infrastructure. It was partly based on a contribution to the Shared Analysis Project for the European Commission Directorate-General for Energy, concerning the penetration of combined heat and power (CHP), energy saving...

  2. Numerical simulation of a heat pump assisted regenerative solar still with PCM heat storage for cold climates of Kazakhstan

    Directory of Open Access Journals (Sweden)

    Shakir Yessen

    2017-01-01

    Full Text Available A numerical model has been proposed in this work for predicting the energy performances of the heat pump assisted regenerative solar still with phase changing material heat storage under Kazakhstan climates. The numerical model is based on energy and mass balance. A new regenerative heat pump configuration with phase changing material heat storage is proposed to improve the performance. A comparison of results has been made between the conventional solar still and heat pump assisted regenerative solar still with phase changing material. The numerical simulation was performed for wide range of ambient temperatures between -30 and 30°C with wide range of solar intensities between 100 and 900 W/m2. The numerical simulation results showed that heat pump assisted regenerative solar still is more energy efficient and produce better yield when compared to the conventional simple solar still. The influences of solar intensity, ambient temperature, different phase changing materials, heat pump operating temperatures are discussed. The predicted values were found to be in good agreement with experimental results reported in literature.

  3. System performance and economic analysis of solar-assisted cooling/heating system

    KAUST Repository

    Huang, B.J.; Wu, J.H.; Yen, R.H.; Wang, J.H.; Hsu, H.Y.; Hsia, C.J.; Yen, C.W.; Chang, J.M.

    2011-01-01

    The long-term system simulation and economic analysis of solar-assisted cooling/heating system (SACH-2) was carried out in order to find an economical design. The solar heat driven ejector cooling system (ECS) is used to provide part of the cooling

  4. Large scale solar district heating. Evaluation, modelling and designing

    Energy Technology Data Exchange (ETDEWEB)

    Heller, A.

    2000-07-01

    The main objective of the research was to evaluate large-scale solar heating connected to district heating (CSDHP), to build up a simulation tool and to demonstrate the application of the tool for design studies and on a local energy planning case. The evaluation of the central solar heating technology is based on measurements on the case plant in Marstal, Denmark, and on published and unpublished data for other, mainly Danish, CSDHP plants. Evaluations on the thermal, economical and environmental performances are reported, based on the experiences from the last decade. The measurements from the Marstal case are analysed, experiences extracted and minor improvements to the plant design proposed. For the detailed designing and energy planning of CSDHPs, a computer simulation model is developed and validated on the measurements from the Marstal case. The final model is then generalised to a 'generic' model for CSDHPs in general. The meteorological reference data, Danish Reference Year, is applied to find the mean performance for the plant designs. To find the expectable variety of the thermal performance of such plants, a method is proposed where data from a year with poor solar irradiation and a year with strong solar irradiation are applied. Equipped with a simulation tool design studies are carried out spreading from parameter analysis over energy planning for a new settlement to a proposal for the combination of plane solar collectors with high performance solar collectors, exemplified by a trough solar collector. The methodology of utilising computer simulation proved to be a cheap and relevant tool in the design of future solar heating plants. The thesis also exposed the demand for developing computer models for the more advanced solar collector designs and especially for the control operation of CSHPs. In the final chapter the CSHP technology is put into perspective with respect to other possible technologies to find the relevance of the application

  5. An applied methodology for assessment of the sustainability of biomass district heating systems

    Science.gov (United States)

    Vallios, Ioannis; Tsoutsos, Theocharis; Papadakis, George

    2016-03-01

    In order to maximise the share of biomass in the energy supplying system, the designers should adopt the appropriate changes to the traditional systems and become more familiar with the design details of the biomass heating systems. The aim of this study is to present the development of methodology and its associated implementation in software that is useful for the design of biomass thermal conversion systems linked with district heating (DH) systems, taking into consideration the types of building structures and urban settlement layout around the plant. The methodology is based on a completely parametric logic, providing an impact assessment of variations in one or more technical and/or economic parameters and thus, facilitating a quick conclusion on the viability of this particular energy system. The essential energy parameters are presented and discussed for the design of biomass power and heat production system which are in connection with DH network, as well as for its environmental and economic evaluation (i.e. selectivity and viability of the relevant investment). Emphasis has been placed upon the technical parameters of biomass logistics, energy system's design, the economic details of the selected technology (integrated cogeneration combined cycle or direct combustion boiler), the DH network and peripheral equipment (thermal substations) and the greenhouse gas emissions. The purpose of this implementation is the assessment of the pertinent investment financial viability taking into account the available biomass feedstock, the economical and market conditions, and the capital/operating costs. As long as biomass resources (forest wood and cultivation products) are available and close to the settlement, disposal and transportation costs of biomass, remain low assuring the sustainability of such energy systems.

  6. Solar-assisted gas-energy water-heating feasibility for apartments

    Science.gov (United States)

    Davis, E. S.

    1975-01-01

    Studies of residential energy use, solar-energy technology for buildings, and the requirements for implementing technology in the housing industry led to a project to develop a solar water heater for apartments. A design study for a specific apartment was used to establish a solar water-heater cost model which is based on plumbing contractor bids and manufacturer estimates. The cost model was used to size the system to minimize the annualized cost of hot water. The annualized cost of solar-assisted gas-energy water heating is found to be less expensive than electric water heating but more expensive than gas water heating. The feasibility of a natural gas utility supplying the auxiliary fuel is evaluated. It is estimated that gas-utilizing companies will find it profitable to offer solar water heating as part of a total energy service option or on a lease basis when the price of new base-load supplies of natural gas reaches $2.50-$3.00 per million Btu.

  7. Solar Assisted Fast Pyrolysis: A Novel Approach of Renewable Energy Production

    Directory of Open Access Journals (Sweden)

    Mohammad U. H. Joardder

    2014-01-01

    Full Text Available Biofuel produced by fast pyrolysis from biomass is a promising candidate. The heart of the system is a reactor which is directly or indirectly heated to approximately 500°C by exhaust gases from a combustor that burns pyrolysis gas and some of the by-product char. In most of the cases, external biomass heater is used as heating source of the system while internal electrical heating is recently implemented as source of reactor heating. However, this heating system causes biomass or other conventional forms of fuel consumption to produce renewable energy and contributes to environmental pollution. In order to overcome these, the feasibility of incorporating solar energy with fast pyrolysis has been investigated. The main advantages of solar reactor heating include renewable source of energy, comparatively simpler devices, and no environmental pollution. A lab scale pyrolysis setup has been examined along with 1.2 m diameter parabolic reflector concentrator that provides hot exhaust gas up to 162°C. The study shows that about 32.4% carbon dioxide (CO2 emissions and almost one-third portion of fuel cost are reduced by incorporating solar heating system. Successful implementation of this proposed solar assisted pyrolysis would open a prospective window of renewable energy.

  8. Annual measured and simulated thermal performance analysis of a hybrid solar district heating plant with flat plate collectors and parabolic trough collectors in series

    DEFF Research Database (Denmark)

    Tian, Zhiyong; Perers, Bengt; Furbo, Simon

    2017-01-01

    Flat plate collectors have relatively low efficiency at the typical supply temperatures of district heating networks (70–95 °C). Parabolic trough collectors retain their high efficiency at these temperatures. To maximize the advantages of flat plate collectors and parabolic trough collectors in l...... for this type of hybrid solar district heating plants with flat plate collectors and parabolic trough collectors in the Nordic region, but also introduce a novel design concept of solar district heating plants to other high solar radiation areas....... in large solar heating plants for a district heating network, a hybrid solar collector field with 5960 m2 flat plate collectors and 4039 m2 parabolic trough collectors in series was constructed in Taars, Denmark. The design principle is that the flat plate collectors preheat the return water from...

  9. Solar Assisted Ground Source Heat Pump Performance in Nearly Zero Energy Building in Baltic Countries

    Science.gov (United States)

    Januševičius, Karolis; Streckienė, Giedrė

    2013-12-01

    In near zero energy buildings (NZEB) built in Baltic countries, heat production systems meet the challenge of large share domestic hot water demand and high required heating capacity. Due to passive solar design, cooling demand in residential buildings also needs an assessment and solution. Heat pump systems are a widespread solution to reduce energy use. A combination of heat pump and solar thermal collectors helps to meet standard requirements and increases the share of renewable energy use in total energy balance of country. The presented paper describes a simulation study of solar assisted heat pump systems carried out in TRNSYS. The purpose of this simulation was to investigate how the performance of a solar assisted heat pump combination varies in near zero energy building. Results of three systems were compared to autonomous (independent) systems simulated performance. Different solar assisted heat pump design solutions with serial and parallel solar thermal collector connections to the heat pump loop were modelled and a passive cooling possibility was assessed. Simulations were performed for three Baltic countries: Lithuania, Latvia and Estonia.

  10. The Forest Energy Chain in Tuscany: Economic Feasibility and Environmental Effects of Two Types of Biomass District Heating Plant

    Directory of Open Access Journals (Sweden)

    Claudio Fagarazzi

    2014-09-01

    Full Text Available The purpose of this study was to examine two biomass district heating plants operating in Tuscany, with a specific focus on the ex-post evaluation of their economic and financial feasibility and of their environmental benefits. The former biomass district heating plant supplies only public users (Comunità Montana della Lunigiana, CML: administrative body that coordinates the municipalities located in mountain areas, the latter supplies both public and private users (Municipality of San Romano in Garfagnana. Ex-post investment analysis was performed to check both the consistency of results with the forecasts made in the stage of the project design and on the factors, which may have reduced or jeopardized the estimated economic performance of the investment (ex-ante assessment. The results of the study point out appreciable results only in the case of biomass district heating plants involving private users and fuelled by biomasses sourced from third parties. In this case, the factors that most influence ex-post results include the conditions of the woody biomass local market (market prices, the policies of energy selling prices to private users and the temporal dynamics of private users’ connection. To ensure the consistency of ex-post economic outcome with the expected results it is thus important to: (i have good knowledge of the woody local market; (ii define energy selling prices that should be cheap for private users but consistent with energy production costs and (iii constrain private users beforehand to prevent errors in the plant design and in the preliminary estimate of return on investment. Moreover, the results obtained during the monitoring activities could help in providing information on the effectiveness of the supporting measures adopted and also to orient future choices of policy makers and particularly designers, to identify the most efficient configuration of district heating organization for improving energy and

  11. Design and System Analysis of Quad-Generation Plant Based on Biomass Gasification Integrated with District Heating

    DEFF Research Database (Denmark)

    Rudra, Souman

    alternative by upgrading existing district heating plant. It provides a generic modeling framework to design flexible energy system in near future. These frameworks address the three main issues arising in the planning and designing of energy system: a) socio impact at both planning and proses design level; b...... in this study. The overall aim of this work is to provide a complete assessment of the technical potential of biomass gasification for local heat and power supply in Denmark and replace of natural gas for the production. This study also finds and defines the future areas of research in the gasification......, it possible to lay a foundation for future gasification based power sector to produce flexible output such as electricity, heat, chemicals or bio-fuels by improving energy system of existing DHP(district heating plant) integrating gasification technology. The present study investigate energy system...

  12. Energetic and financial evaluation of solar assisted heat pump space heating systems

    International Nuclear Information System (INIS)

    Bellos, Evangelos; Tzivanidis, Christos; Moschos, Konstantinos; Antonopoulos, Kimon A.

    2016-01-01

    Highlights: • Four solar heating systems are presented in this work. • Various combinations between solar collectors and heat pumps are presented. • The systems are compared energetically and financially. • The use of PV and an air source heat pump is the best choice financially. • The use of PVT with a water source heat pump is the best solution energetically. - Abstract: Using solar energy for space heating purposes consists an alternative way for substituting fossil fuel and grid electricity consumption. In this study, four solar assisted heat pump heating systems are designed, simulated and evaluated energetically and financially in order to determine the most attractive solution. The use of PV collectors with air source heat pump is compared to the use of FPC, PVT and FPC with PV coupled with a water source heat pump. A sensitivity analysis for the electricity cost is conducted because of the great variety of this parameter over the last years. The final results proved that for electricity cost up to 0.23 €/kW h the use of PV coupled with an air source heat pump is the most sustainable solution financially, while for higher electricity prices the coupling of PVT with an water source heat pump is the best choice. For the present electricity price of 0.2 €/kW h, 20 m"2 of PV is able to drive the air source heat pump with a yearly solar coverage of 67% leading to the most sustainable solution. Taking into account energetic aspects, the use of PVT leads to extremely low grid electricity consumption, fact that makes this technology the most environmental friendly.

  13. Large-scale solar heat

    Energy Technology Data Exchange (ETDEWEB)

    Tolonen, J.; Konttinen, P.; Lund, P. [Helsinki Univ. of Technology, Otaniemi (Finland). Dept. of Engineering Physics and Mathematics

    1998-12-31

    In this project a large domestic solar heating system was built and a solar district heating system was modelled and simulated. Objectives were to improve the performance and reduce costs of a large-scale solar heating system. As a result of the project the benefit/cost ratio can be increased by 40 % through dimensioning and optimising the system at the designing stage. (orig.)

  14. SODHA. A data program for minimizing the cost function of a solar farm with storage connected to a district heating system

    Energy Technology Data Exchange (ETDEWEB)

    Haakansson, R; Rolandsson, S

    1982-05-03

    SODHA is a program for minimizing the investment needed for a solar plant supplying a district heating system. The plant consists of a solar farm, storage and a heat exchanger connected to a district heating network. By using SODHA it is possible to optimize solar collector area storage volume, insulation thickness and magnitude of heat exchanger. The calculation gives the best estimated configuration of the system, within given margins and specified regulation principles. The program can be used for an arbitrary period, e.g. one season (year). This work is financed by NE, the National Swedish Board for Energy Source Development.

  15. Distributed heat generation in a district heating system

    OpenAIRE

    Lennermo, Gunnar; Lauenberg, Patrick

    2016-01-01

    District heating (OH) systems need to be improved  regarding integration  of decentralised  heat generation. Micro production, prosumers and smart grids are terms becoming more and more common  in  connection  to  the  power  grid.  Concerning district  heating,  the  development  is slower, although improving. Today there are a number of such decentralised units for heat generation,  mainly  solar,  that have been partly evaluated.  Previous  studies  have shown  that there is a need to deve...

  16. Solar assisted conditioning of residences with floor heating and ceiling cooling: review and simulation results

    OpenAIRE

    Egrican, Nilufer; Korkmaz, Adnan

    2015-01-01

    Solar or solar assisted heating and cooling systems are becoming widespread to reduce CO2 emissions. Efficient radiant space heating and cooling systems can be used to decrease the energy bills and improve occupant thermal comfort in buildings. This study uses the TRNSYS program, for the modeling and simulation of solar assisted radiant heating and cooling of a building with the domestic hot water supply, to examine the effects of various parameters on energy consumption. Calculations are per...

  17. Status seminar `98: Solar-supported district heating with seasonal heat storage. Status report `98; Status-Seminar `98: Solarunterstuetzte Nahwaermeversorgung - Saisonale Waermespeicherung. Statusbericht `98

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1998-12-31

    This status report refers to the BMBF (Federal Ministry for Education, Science, Research and Technology) status seminar: Solar-assisted district heat supply - seasonal heat storage that took place in Neckarsulm on 19th and 20th May. 1998. The report contains the reference papers and the status reports of all projects supported under the Ministry`s SOLARTHERMIE programme that have already been finished or are still running. (orig.) [Deutsch] Der vorliegende Statusbericht wird anlaesslich des BMBF-Statusseminars: Solarunterstuetzte Nahwaermeversorgung - Saisonale Waermespeicherung am 19. und 20. Mai 1998 in Neckarsulm herausgegeben. Der Bericht enthaelt neben den Tagungsbeitraegen auch die Sachstandsberichte aller Projekte, die zu diesem Thema in den letzten Jahren von BMBF in dem Programm SOLARTHERMIE-2000 bereits abgeschlossen wurden oder z.Zt. gefoerdert werden. (orig.)

  18. Solar district heating system `Schillerstrasse` in Schwaebisch-Gmuend; Solare Nahwaerme ``Schillerstrasse`` in Schwaebisch Gmuend

    Energy Technology Data Exchange (ETDEWEB)

    Kuebler, R. [Steinbeis-Transferzentrum Energie-, Gebaeude- und Solartechnik, Stuttgart (Germany); Mangold, D. [Stuttgart Univ. (Germany). Inst. fuer Thermodynamik und Waermetechnik

    1998-12-31

    The construction project Schillerstrasse in Schwaebisch-Gmuend was planned and realised by the Siedlungswerk Stuttgart from 1993 until 1996. Like in earlier projects in Ravensburg and Koengen the Siedlungswerk wanted to use new technologies in the field of thermal insulation and heat supply at the construction of this new residential area in order to stay considerably below the former construction standards (WSVO 1982). One part of this energy concept is a large solar plant to support warm water supply. Good experience had been made with flat solar collectors at the three plants in Ravensburg and Koengen. In Schwaebisch-Gmuend vacuum pipe collectors were utilised for the first time. They were the only type of collectors which could be installed on the flat roofs without being visible from the ground. The solar-assisted district heating system was put in operation in May 1996. A new method that controls the system by measuring data acquisition enabled to measure and optimise the thermal performance of the plant. At the beginning of 1998 the plant was modified in order to improve the use of the solar plant. (orig.) [Deutsch] Das Bauvorhaben Schillerstrasse in Schwaebisch Gmuend wurde in den Jahren 1993-1996 vom Siedlungswerk Stuttgart geplant und gebaut. Aehnlich wie bei frueheren Projekten in Ravensburg und Koengen war es das Ziel des Siedlungswerks, in diesem Neubauvorhaben neue Wege beim Waermeschutz und bei der Waermeversorgung der Wohnanlage zu gehen, um den damaligen Baustandard (WSVO 1982) deutlich zu unterschreiten. Ein Element dieses Energiekonzepts ist eine grosse Solaranlage zur Unterstuetzung der Warmwasserbereitung. Nach guten Erfahrungen mit Flachkollektoren in den drei Anlagen in Ravensburg und Koengen wurden in Schwaebisch Gmuend zum ersten Mal Vakuum-Roehrenkollektoren eingesetzt. Fuer die Wahl der Vakuumroehren waren nicht zuletzt die stadtpolitischen Randbedingungen ausschlaggebend, die nur eine von unten nicht sichtbare Aufstellung auf dem

  19. Solar heating cooling. Preparation of possible participation in IEA, Solar Heating Cooling Task 25

    International Nuclear Information System (INIS)

    2001-03-01

    For the Danish solar heating industries it is interesting to discuss the domestic market possibilities and the export possibilities for solar heating cooling systems. The Danish solar heating sector also wants to participate in the international collaboration within IEA Solar Heating and Cooling Task 25 'Solar Assisted Air Conditioning of Buildings'. The Danish Energy Agency therefore has granted means for this project to discuss: The price of cooling for 3 different solar cooling methods (absorption cooling, desiccant cooling and ejector cooling); Market possibilities in Denmark and abroad; The advantages by Danish participation in IEA Task 25. The task has been solved through literature studies to establish status for the 3 technologies. It turned out that ejector cooling by low temperatures (85 deg. C from the solar collector) exists as pilot plants in relation to district heating, but is still not commercial accessible. Desiccant cooling, where the supplied heat has temperatures down to 55 deg. C is a well-developed technology. However only a handful of pilot plants with solar heating exists, and thus optimization relating to operation strategy and economy is on the experimental stage. Absorption cooling plants driven by solar heating are found in a large number in Japan and are also demonstrated in several other countries. The combination of absorption heating pump and solar heating is considered to be commercial accessible. Solar heating is interesting as heat source of to the extent that it can replace other sources of heat without the economy being depreciated. This can be the case in South Europe if: 1) oil or natural gas is used for heating; 2) a solar heating system already exists, e.g. for domestic water supply, and is installed so that the marginal costs by solar heating supply of the ventilation plant is reduced. All in all the above conditions mean that the market for solar heating for cooling is very limited in Europe, where almost everybody are

  20. Economic and environmental benefits of converting industrial processes to district heating

    International Nuclear Information System (INIS)

    Djuric Ilic, Danica; Trygg, Louise

    2014-01-01

    greenhouse gas emissions. The potential for the reduction of global greenhouse gas emissions is highly dependent on the alternative use of biomass and on the type of the marginal electricity producers. When the marginal effects from biomass use are not considered, the greenhouse gas emissions reduction is between 10 thousand tonnes of CO 2eq and 58 thousand tonnes of CO 2eq per year, depending on the county and the type of marginal electricity production plants. The highest reduction is achieved in Östergötland. However, considering that biomass is a limited resource, the increase of biomass use in the district heating systems may lead to a decrease of biomass use in other energy systems. If this assumption is included in the calculations, the conversion of the industrial processes to district heating still signify a potential for reduction of greenhouse gas emissions, but this potential is considerable lower

  1. Performance analysis of hybrid district heating system

    DEFF Research Database (Denmark)

    Mikulandric, Robert; Krajačić, Goran; Khavin, Gennadii

    2013-01-01

    District heating system could contribute to more efficient heat generation through cogeneration power plants or waste heat utilization facilities and to increase of renewable energy sources share in total energy consumption. In the most developed EU countries, renewable energy sources have been...... as problems related to transportation, storage and environmental impacts of biomass and waste utilisation. Implementation of heat storages in district heating systems could contribute to integration of intermittent energy sources. Hybridisation of heat production facility combines two or more different energy...... more extensively used in district heating systems either separately or as a supplement to traditional fossil fuels in order to achieve national energy policy objectives. However, they are still facing problems such as high intermittences, high energy production costs and low load factors as well...

  2. Optimisation models for decision support in the development of biomass-based industrial district-heating networks in Italy

    International Nuclear Information System (INIS)

    Chinese, Damiana; Meneghetti, Antonella

    2005-01-01

    A system optimisation approach is proposed to design biomass-based district-heating networks in the context of industrial districts, which are one of the main successful productive aspects of Italian industry. Two different perspectives are taken into account, that of utilities and of policy makers, leading to two optimisation models to be further integrated. A mixed integer linear-programming model is developed for a utility company's profit maximisation, while a linear-programming model aims at minimising the balance of greenhouse-gas emissions related to the proposed energy system and the avoided emissions due to the substitution of current fossil-fuel boilers with district-heating connections. To systematically compare their results, a sensitivity analysis is performed with respect to network size in order to identify how the optimal system configuration, in terms of selected boilers to be connected to a multiple energy-source network, may vary in the two cases and to detect possible optimal sizes. Then a factorial analysis is adopted to rank desirable client types under the two perspectives and identify proper marketing strategies. The proposed optimisation approach was applied to the design of a new district-heating network in the chair-manufacturing district of North-Eastern Italy. (Author)

  3. Large-scale solar heating

    Energy Technology Data Exchange (ETDEWEB)

    Tolonen, J.; Konttinen, P.; Lund, P. [Helsinki Univ. of Technology, Otaniemi (Finland). Advanced Energy Systems

    1998-10-01

    Solar heating market is growing in many European countries and annually installed collector area has exceeded one million square meters. There are dozens of collector manufacturers and hundreds of firms making solar heating installations in Europe. One tendency in solar heating is towards larger systems. These can be roof integrated, consisting of some tens or hundreds of square meters of collectors, or they can be larger centralized solar district heating plants consisting of a few thousand square meters of collectors. The increase of size can reduce the specific investments of solar heating systems, because e.g. the costs of some components (controllers, pumps, and pipes), planning and installation can be smaller in larger systems. The solar heat output can also be higher in large systems, because more advanced technique is economically viable

  4. Simulation of Hybrid Photovoltaic Solar Assisted Loop Heat Pipe/Heat Pump System

    Directory of Open Access Journals (Sweden)

    Nannan Dai

    2017-02-01

    Full Text Available A hybrid photovoltaic solar assisted loop heat pipe/heat pump (PV-SALHP/HP water heater system has been developed and numerically studied. The system is the combination of loop heat pipe (LHP mode and heat pump (HP mode, and the two modes can be run separately or compositely according to the weather conditions. The performances of independent heat pump (HP mode and hybrid loop heat pipe/heat pump (LHP/HP mode were simulated and compared. Simulation results showed that on typical sunny days in spring or autumn, using LHP/HP mode could save 40.6% power consumption than HP mode. In addition, the optimal switchover from LHP mode to HP mode was analyzed in different weather conditions for energy saving and the all-year round operating performances of the system were also simulated. The simulation results showed that hybrid LHP/HP mode should be utilized to save electricity on sunny days from March to November and the system can rely on LHP mode alone without any power consumption in July and August. When solar radiation and ambient temperature are low in winter, HP mode should be used

  5. Solar heating action plan; Solvarme handlingsplan

    Energy Technology Data Exchange (ETDEWEB)

    Nielsen, Jan Erik

    2011-10-15

    This solar action plan should be seen as a follow-up to the Danish Energy Agency's solar heating strategy from 2007, which showed great potential and opportunities for exploitation and use of solar heat in Denmark. In relation to the strategy from 2007, this action plan adjusted the distribution of solar heat from district heating plants and individual plants, but it is still the objective of this action plan to achieve the strategy's overall goal for 2030. With the implementation of the Action Plan in early 2012, it is estimated that in 2030 there will be about. 10 million m2 of solar collectors in operation, 8 million m2 for district heating and 2 million m2 for individual heating, equivalent to an installed capacity totaling 7 GW. The budget for actions in the Action Plan is about 80 million DKK annually over the next 5 years to initiate and ensure this development. (LN)

  6. Parametric sensitivity study for solar-assisted heat-pump systems

    Science.gov (United States)

    White, N. M.; Morehouse, J. H.

    1981-07-01

    The engineering and economic parameters affecting life-cycle costs for solar-assisted heat pump systems are investigted. The change in energy usage resulting from each engineering parameter varied was developed from computer simulations, and is compared with results from a stand-alone heat pump system. Three geographical locations are considered: Washington, DC, Fort Worth, TX, and Madison, WI. Results indicate that most engineering changes to the systems studied do not provide significant energy savings. The most promising parameters to ary are the solar collector parameters tau (-) and U/sub L/ the heat pump capacity at design point, and the minimum utilizable evaporator temperature. Costs associated with each change are estimated, and life-cycle costs computed for both engineering parameters and economic variations in interest rate, discount rate, tax credits, fuel unit costs and fuel inflation rates. Results indicate that none of the feasibile engineering changes for the system configuration studied will make these systems economically competitive with the stand-alone heat pump without a considerable tax credit.

  7. The strategic role of district heating in renewable energy use; Die strategische Bedeutung der Nahwaerme zur Nutzung erneuerbarer Energien

    Energy Technology Data Exchange (ETDEWEB)

    Nast, M. [Deutsches Zentrum fuer Luft- und Raumfahrt e.V. (DLR), Stuttgart (Germany). Abt. Systemanalyse und Technikbewertung; Boehnisch, H. [Zentrum fuer Sonnenenergie- und Wasserstoff-Forschung Baden-Wuerttemberg (ZSW), Stuttgart (Germany)

    1998-02-01

    District heating allows the utilization of biomass in low emission heating plants, the exploitation of solar energy and the seasonal storage of heat. If a sustainable energy supply system is to be created, district heating must not only be the system of choice for new housing districts but must also be retrofitted in existing settlements. The detailed analysis of a rural community shows that large segments of existing buildings can be connected to district heating systems even in regions with predominantly single dwellings and rural housing densities. The conditions necessary for establishing district heating systems are discussed. (orig.) [Deutsch] Nahwaermesysteme ermoeglichen, fossile und biogene Brennstoffe einzusetzen und lassen sich an saisonale Waermespeicher anschliessen. Zum Aufbau einer nachhaltigen Energieversorgung ist Nahwaerme nicht nur in Neubaugebieten notwendig sondern muss auch in den schon laenger genutzten Gebaeudebestand integriert werden. Das Beispiel einer umfassend analysierten Landgemeinde zeigt, dass ein grosser Teil des bestehenden Gebaeudebestandes an Waermenetze angeschlossen werden kann, selbst bei vorherrschender Bebauung mit Einfamilienhaeusern und laendlichen Gebaeudedichten. Die notwendigen Rahmenbedingungen fuer den Aufbau einer Nahwaermeversorgung werden erlaeutert. (orig.)

  8. A solar assisted heat-pump dryer and water heater

    International Nuclear Information System (INIS)

    Hawlader, M.N.A.; Chou, S.K.; Jahangeer, K.A.; Rahman, S.M.A.

    2006-01-01

    Growing concern about the depletion of conventional energy resources has provided impetus for considerable research and development in the area of alternative energy sources. A solar assisted heat pump dryer and water heater found to be one of the solutions while exploring for alternative energy sources. The heat pump system is used for drying and water heating applications with the major share of the energy derived from the sun and the ambient. The solar assisted heat pump dryer and water heater has been designed, fabricated and tested. The performance of the system has been investigated under the meteorological conditions of Singapore. The system consists of a variable speed reciprocating compressor, evaporator-collector, storage tank, air cooled condenser, auxiliary heater, blower, dryer, dehumidifier, and air collector. The drying medium used is air and the drying chamber is configured to carry out batch drying of good grains. A water tank connected in series with the air cooled condenser delivers hot water for domestic applications. The water tank also ensures complete condensation of the refrigerant vapour. A simulation program is developed using Fortran language to evaluate the performance of the system and the influence of different variables. The performance indices considered to evaluate the performance of the system are: Solar Fraction (SF), Coefficient of Performance (COP) and Specific Moisture Extraction Rate (SMER). A COP value of 7.5 for a compressor speed of 1800 rpm was observed. Maximum collector efficiencies of 0.86 and 0.81 have been found for evaporator-collector and air collector, respectively. A value of the SMER of 0.79 has been obtained for a load of 20 kg and a compressor speed of 1200 rpm

  9. Solar heating cooling. Preparation of possible participation in IEA, Solar Heating Cooling Task 25; Solvarmedrevet koeling. Forberedelse af evt. deltagelse i IEA, Solar Heating Cooling Task 25

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2001-03-01

    For the Danish solar heating industries it is interesting to discuss the domestic market possibilities and the export possibilities for solar heating cooling systems. The Danish solar heating sector also wants to participate in the international collaboration within IEA Solar Heating and Cooling Task 25 'Solar Assisted Air Conditioning of Buildings'. The Danish Energy Agency therefore has granted means for this project to discuss: The price of cooling for 3 different solar cooling methods (absorption cooling, desiccant cooling and ejector cooling); Market possibilities in Denmark and abroad; The advantages by Danish participation in IEA Task 25. The task has been solved through literature studies to establish status for the 3 technologies. It turned out that ejector cooling by low temperatures (85 deg. C from the solar collector) exists as pilot plants in relation to district heating, but is still not commercial accessible. Desiccant cooling, where the supplied heat has temperatures down to 55 deg. C is a well-developed technology. However only a handful of pilot plants with solar heating exists, and thus optimization relating to operation strategy and economy is on the experimental stage. Absorption cooling plants driven by solar heating are found in a large number in Japan and are also demonstrated in several other countries. The combination of absorption heating pump and solar heating is considered to be commercial accessible. Solar heating is interesting as heat source of to the exent that it can replace other sources of heat without the economy being depreciated. This can be the case in South Europe if: 1) oil or natural gas is used for heating; 2) a solar heating system already exists, e.g. for domestic water supply, and is installed so that the marginal costs by solar heating supply of the ventilation plant is reduced. All in all the above conditions mean that the market for solar heating for cooling is very limited in Europe, where almost

  10. Mapping of potential heat sources for heat pumps for district heating in Denmark

    International Nuclear Information System (INIS)

    Lund, Rasmus; Persson, Urban

    2016-01-01

    The ambitious policy in Denmark on having a 100% renewable energy supply in 2050 requires radical changes to the energy systems to avoid an extensive and unsustainable use of biomass resources. Currently, wind power is being expanded and the increasing supply of electricity is slowly pushing the CHP (combined heat and power) plants out of operation, reducing the energy efficiency of the DH (district heating) supply. Here, large heat pumps for district heating is a frequently mentioned solution as a flexible demand for electricity and an energy efficient heat producer. The idea is to make heat pump use a low temperature waste or ambient heat source, but it has so far been very unclear which heat sources are actually available for this purpose. In this study eight categories of heat sources are analysed for the case of Denmark and included in a detailed spatial analysis where the identified heat sources are put in relation to the district heating areas and the corresponding demands. The analysis shows that potential heat sources are present near almost all district heating areas and that sea water most likely will have to play a substantial role as a heat source in future energy systems in Denmark. - Highlights: • The availability of heat sources for heat pumps in Denmark are mapped and quantified. • A novel methodology for assessment of low temperature industrial excess heat is presented. • There are heat sources available for 99% of district heating networks in Denmark. • The concentration of heat sources is generally bigger around bigger cities than smaller. • Ambient temperature heat sources will be more needed in district heating of big cities.

  11. Development of hybrid solar-assisted cooling/heating system

    KAUST Repository

    Huang, B.J.; Wu, J.H.; Hsu, H.Y.; Wang, J.H.

    2010-01-01

    A solar-assisted ejector cooling/heating system (SACH) was developed in this study. The SACH combines a pump-less ejector cooling system (ECS) with an inverter-type heat pump (R22) and is able to provide a stable capacity for space cooling. The ECS is driven by solar heat and is used to cool the condenser of the R22 heat pump to increase its COP and reduce the energy consumption of the compressor by regulating the rotational speed of the compressor through a control system. In a complete SACH system test run at outdoor temperature 35 °C, indoor temperature 25 °C and compressor speed 20-80 Hz, and the ECS operating at generator temperature 90 °C and condensing temperature 37 °C, the corresponding condensing temperature of the heat pump in the SACH is 24.5-42 °C, cooling capacity 1.02-2.44 kW, input power 0.20-0.98 kW, and cooling COPc 5.11-2.50. This indicates that the use of ECS in SACH can effectively reduce the condensing temperature of the heat pump by 12.6-7.3 °C and reduce the power consumption by 81.2-34.5%. The SACH can also supply heat from the heat pump. At ambient temperature from 5 °C to 35 °C, the heating COPh is in the range 2.0-3.3. © 2010 Elsevier Ltd. All rights reserved.

  12. Development of hybrid solar-assisted cooling/heating system

    KAUST Repository

    Huang, B.J.

    2010-08-01

    A solar-assisted ejector cooling/heating system (SACH) was developed in this study. The SACH combines a pump-less ejector cooling system (ECS) with an inverter-type heat pump (R22) and is able to provide a stable capacity for space cooling. The ECS is driven by solar heat and is used to cool the condenser of the R22 heat pump to increase its COP and reduce the energy consumption of the compressor by regulating the rotational speed of the compressor through a control system. In a complete SACH system test run at outdoor temperature 35 °C, indoor temperature 25 °C and compressor speed 20-80 Hz, and the ECS operating at generator temperature 90 °C and condensing temperature 37 °C, the corresponding condensing temperature of the heat pump in the SACH is 24.5-42 °C, cooling capacity 1.02-2.44 kW, input power 0.20-0.98 kW, and cooling COPc 5.11-2.50. This indicates that the use of ECS in SACH can effectively reduce the condensing temperature of the heat pump by 12.6-7.3 °C and reduce the power consumption by 81.2-34.5%. The SACH can also supply heat from the heat pump. At ambient temperature from 5 °C to 35 °C, the heating COPh is in the range 2.0-3.3. © 2010 Elsevier Ltd. All rights reserved.

  13. Mushroom drying with solar assisted heat pump system

    International Nuclear Information System (INIS)

    Şevik, Seyfi; Aktaş, Mustafa; Doğan, Hikmet; Koçak, Saim

    2013-01-01

    Highlights: • Experimental investigation of a simple and cost effective solar assisted heat pump system. • Developing of a computer program for a drying system with different scenarios by using PLC. • Obtained less energy input with high coefficients of performance of system and more quality products. • Determination of mushroom drying properties such as moisture content, moisture ratio and drying ratio. - Abstract: In this study, a simple and cost effective solar assisted heat pump system (SAHP) with flat plate collectors and a water source heat pump has been proposed. Mushroom drying was examined experimentally in the drying system. Solar energy (SE) system and heat pump (HP) system can be used separately or together. A computer program has been developed for the system. Drying air temperature, relative humidity, weight of product values, etc. were monitored and controlled with different scenarios by using PLC. This system is cheap, good quality and sustainable and it is modeled for good quality product and increased efficiency. Thus, products could be dried with less energy input and more controlled conditions. Mushrooms were dried at 45 °C and 55 °C drying air temperature and 310 kg/h mass flow rate. Mushrooms were dried from initial moisture content 13.24 g water/g dry matter (dry basis) to final moisture content 0.07 g water/g dry matter (dry basis). Mushrooms were dried by using HP system, SE system and SAHP system respectively at 250–220 min, at 270–165 min and at 230–190 min. The coefficients of performance of system (COP) are calculated in a range from 2.1 to 3.1 with respect to the results of experiments. The energy utilization ratios (EURs) were found to vary between 0.42 and 0.66. Specific moisture extraction rate (SMER) values were found to vary between 0.26 and 0.92 kg/kW h

  14. Industrial Heat Pump for a High Temperature District Heating Application

    DEFF Research Database (Denmark)

    Poulsen, Claus Nørgaard

    by excess thermal energy from thermal solar panels. An industrial heat pump system using the natural refrigerant ammonia, is extracting the thermal energy from the storage when needed, and produce hot water at 85°C, for the district heating grid. The heat pump also acts as contributor to electricity grid...

  15. Thermodynamic evaluation of a novel solar-biomass hybrid power generation system

    International Nuclear Information System (INIS)

    Bai, Zhang; Liu, Qibin; Lei, Jing; Wang, Xiaohe; Sun, Jie; Jin, Hongguang

    2017-01-01

    Highlights: • A solar-biomass hybrid power system with zero carbon dioxide emission is proposed. • The internal mechanisms of the solar-biomass utilization are discussed. • The on-design and off-design properties of the system are numerically investigated. • The configurations of the proposed system are optimized. - Abstract: A solar-biomass hybrid power generation system, which integrates a solar thermal energy collection subsystem, a biomass steam boiler and a steam turbine power generation block, is developed for efficiently utilizing renewable energies. The solar thermal energy is concentrated by parabolic trough collectors and is used to heat the feed-water to the superheated steam of 371 °C, then the generated solar steam is further heated to a higher temperature level of 540 °C via a second-stage heating process in a biomass boiler, the system power generation capacity is about 50 MW. The hybrid process of the solar energy and biomass contributes to ameliorating the system thermodynamic performances and reducing of the exergy loss within the steam generation process. The off-design evaluation results indicate that the annual net solar-to-electric efficiency of the hybrid power system is improved to 18.13%, which is higher than that of the typical parabolic trough solar power system as 15.79%. The levelized cost of energy drops to 0.077 $/(kW h) from 0.192 $/(kW h). The annual biomass consumption rate is reduced by 22.53% in comparison with typical biomass power systems. The research findings provide a promising approach for the efficient utilization of the abundant renewable energies resources and the reduction of carbon dioxide emission.

  16. Influencing Swedish homeowners to adopt district heating system

    Energy Technology Data Exchange (ETDEWEB)

    Mahapatra, Krushna; Gustavsson, Leif [Ecotechnology, Mid Sweden University, Akademigatan 1, 831 25 Oestersund (Sweden)

    2009-02-15

    Improved energy efficiency and greenhouse gas mitigation could be achieved by replacing resistance heaters with district heating system. In 2005, only about 8% of the Swedish detached houses had district heating system. The expansion of such systems largely depends on homeowners' adoption decisions. And, to motivate homeowners to adopt district heating, it is essential to understand their decision-making process. In this context, in June 2005 we carried out a questionnaire survey of about 700 homeowners who lived in the city of Oestersund in houses with resistance heaters (baseline survey). About 84% of the respondents did not intend to install a new heating system. Since then these homeowners were influenced by (a) an investment subsidy by the Swedish government to replace resistance heaters with district heating, a brine/water-based heat pump, or a biomass-based heating system and (b) a marketing campaign by the municipality-owned district heating company. This paper analyses how these two measures influenced about 78% of the homeowners to adopt the district heating system. For this purpose we carried out a follow-up survey of the same homeowners in December 2006 (resurvey). Results showed that the investment subsidy and the marketing campaign created a need among the homeowners to adopt a new heating system. The marketing campaign was successful in motivating them to adopt the district heating system. The marketing strategy by the district heating company corresponds to the results obtained in the baseline survey. (author)

  17. Influencing Swedish homeowners to adopt district heating system

    International Nuclear Information System (INIS)

    Mahapatra, Krushna; Gustavsson, Leif

    2009-01-01

    Improved energy efficiency and greenhouse gas mitigation could be achieved by replacing resistance heaters with district heating system. In 2005, only about 8% of the Swedish detached houses had district heating system. The expansion of such systems largely depends on homeowners' adoption decisions. And, to motivate homeowners to adopt district heating, it is essential to understand their decision-making process. In this context, in June 2005 we carried out a questionnaire survey of about 700 homeowners who lived in the city of Ostersund in houses with resistance heaters (baseline survey). About 84% of the respondents did not intend to install a new heating system. Since then these homeowners were influenced by (a) an investment subsidy by the Swedish government to replace resistance heaters with district heating, a brine/water-based heat pump, or a biomass-based heating system and (b) a marketing campaign by the municipality-owned district heating company. This paper analyses how these two measures influenced about 78% of the homeowners to adopt the district heating system. For this purpose we carried out a follow-up survey of the same homeowners in December 2006 (resurvey). Results showed that the investment subsidy and the marketing campaign created a need among the homeowners to adopt a new heating system. The marketing campaign was successful in motivating them to adopt the district heating system. The marketing strategy by the district heating company corresponds to the results obtained in the baseline survey

  18. Influencing Swedish homeowners to adopt district heating system

    Energy Technology Data Exchange (ETDEWEB)

    Mahapatra, Krushna; Gustavsson, Leif [Ecotechnology, Mid Sweden University, Akademigatan 1, 831 25 Oestersund (Sweden)

    2009-02-15

    Improved energy efficiency and greenhouse gas mitigation could be achieved by replacing resistance heaters with district heating system. In 2005, only about 8% of the Swedish detached houses had district heating system. The expansion of such systems largely depends on homeowners' adoption decisions. And, to motivate homeowners to adopt district heating, it is essential to understand their decision-making process. In this context, in June 2005 we carried out a questionnaire survey of about 700 homeowners who lived in the city of Oestersund in houses with resistance heaters (baseline survey). About 84% of the respondents did not intend to install a new heating system. Since then these homeowners were influenced by (a) an investment subsidy by the Swedish government to replace resistance heaters with district heating, a brine/water-based heat pump, or a biomass-based heating system and (b) a marketing campaign by the municipality-owned district heating company. This paper analyses how these two measures influenced about 78% of the homeowners to adopt the district heating system. For this purpose we carried out a follow-up survey of the same homeowners in December 2006 (resurvey). Results showed that the investment subsidy and the marketing campaign created a need among the homeowners to adopt a new heating system. The marketing campaign was successful in motivating them to adopt the district heating system. The marketing strategy by the district heating company corresponds to the results obtained in the baseline survey. (author)

  19. Experimental analysis of a direct expansion solar assisted heat pump with integral storage tank for domestic water heating under zero solar radiation conditions

    International Nuclear Information System (INIS)

    Fernández-Seara, José; Piñeiro, Carolina; Alberto Dopazo, J.; Fernandes, F.; Sousa, Paulo X.B.

    2012-01-01

    Highlights: ► We analyze a direct expansion solar assisted heat pump under zero solar radiation. ► We determine the COP and equivalent seasonal performance factors (SPFe). ► We determine the main components’ performance under transient operating conditions. ► The Huang and Lee performance evaluation method provides a characteristic COP of 3.23. - Abstract: This paper deals with the experimental evaluation of the performance of a direct expansion solar assisted heat pump water heating (DX-SAHPWH) system working under zero solar radiation conditions at static heating operation mode of the storage tank. The DX-SAHPWH system includes two bare solar collectors as evaporator, a R134a rotary-type hermetic compressor, a thermostatic expansion valve and a helical coil condenser immersed in a 300 L water storage tank. The zero solar radiation and stable ambient air temperature working conditions were established by placing the solar collectors into a climate chamber. The analysis is based on experimental data taken from the DX-SAHPWH provided by the manufacturer and equipped with an appropriate data acquisition system. In the paper, the experimental facility, the data acquisition system and the experimental methodology are described. Performance parameters to evaluate the energy efficiency, such as COP and equivalent seasonal performance factors (SPFe) for the heating period, and the water thermal stratification in the storage tank are defined and obtained from the experimental data. Results from the experimental analysis under transient operating working conditions of the DX-SAHPWH system and its main components are shown and discussed. Lastly, the Huang and Lee DX-SAHPWH performance evaluation method was applied resulting in a characteristic COP of 3.23 for the DX-SAHPWH system evaluated under zero solar radiation condition.

  20. Efficient Solar-Thermal Energy Harvest Driven by Interfacial Plasmonic Heating-Assisted Evaporation.

    Science.gov (United States)

    Chang, Chao; Yang, Chao; Liu, Yanming; Tao, Peng; Song, Chengyi; Shang, Wen; Wu, Jianbo; Deng, Tao

    2016-09-07

    The plasmonic heating effect of noble nanoparticles has recently received tremendous attention for various important applications. Herein, we report the utilization of interfacial plasmonic heating-assisted evaporation for efficient and facile solar-thermal energy harvest. An airlaid paper-supported gold nanoparticle thin film was placed at the thermal energy conversion region within a sealed chamber to convert solar energy into thermal energy. The generated thermal energy instantly vaporizes the water underneath into hot vapors that quickly diffuse to the thermal energy release region of the chamber to condense into liquids and release the collected thermal energy. The condensed water automatically flows back to the thermal energy conversion region under the capillary force from the hydrophilic copper mesh. Such an approach simultaneously realizes efficient solar-to-thermal energy conversion and rapid transportation of converted thermal energy to target application terminals. Compared to conventional external photothermal conversion design, the solar-thermal harvesting device driven by the internal plasmonic heating effect has reduced the overall thermal resistance by more than 50% and has demonstrated more than 25% improvement of solar water heating efficiency.

  1. solar dryer with biomass backup heater for drying fruits

    African Journals Online (AJOL)

    SOLAR DRYER WITH BIOMASS BACKUP HEATER FOR DRYING FRUITS: DEVELOPMENT AND PERFORMANCE ANALYSIS. ... Journal of Science and Technology (Ghana) ... Most solar dryers rely on only solar energy as the heat source.

  2. Analysis and validation of a quasi-dynamic model for a solar collector field with flat plate collectors and parabolic trough collectors in series for district heating

    DEFF Research Database (Denmark)

    Tian, Zhiyong; Perers, Bengt; Furbo, Simon

    2018-01-01

    performance of the hybrid solar district heating plants is also presented. The measured and simulated results show that the integration of parabolic trough collectors in solar district heating plants can guarantee that the system produces hot water with relatively constant outlet temperature. The daily energy......A quasi-dynamic TRNSYS simulation model for a solar collector field with flat plate collectors and parabolic trough collectors in series was described and validated. A simplified method was implemented in TRNSYS in order to carry out long-term energy production analyses of the whole solar heating...... plant. The advantages of the model include faster computation with fewer resources, flexibility of different collector types in solar heating plant configuration and satisfactory accuracy in both dynamic and long-term analyses. In situ measurements were taken from a pilot solar heating plant with 5960 m...

  3. Solar-Biomass hybrid system for process heat supply in medium scale hotels in Sri Lanka

    OpenAIRE

    Abeywardana, Asela M.A.J.

    2016-01-01

    This study aimed at evaluating and demonstrating the feasibility of using Concentrated Solar Thermal technology combined with biomass energy technology as a hybrid renewable energy system to supply the process heat requirements in small scale industries in Sri Lanka. Particularly, the focus was to apply the concept to the expanding hotel industry, for covering the thermal energy demand of a medium scale hotel. Solar modules utilize the rooftop area of the building to a valuable application. L...

  4. Experimental study of a solar-assisted ground-coupled heat pump system with solar seasonal thermal storage in severe cold areas

    Energy Technology Data Exchange (ETDEWEB)

    Wang, Xiao; Zheng, Maoyu; Zhang, Wenyong; Zhang, Shu; Yang, Tao [School of Municipal and Environmental Engineering, Harbin Institute of Technology, NO 202 Haihe Road, Harbin, Hei Longjiang 150090 (China)

    2010-11-15

    This paper presents the experimental study of a solar-assisted ground-coupled heat pump system (SAGCHPS) with solar seasonal thermal storage installed in a detached house in Harbin. The solar seasonal thermal storage was conducted throughout the non-heating seasons. In summer, the soil was used as the heat sink to cool the building directly. In winter, the solar energy was used as a priority, and the building was heated by a ground-coupled heat pump (GCHP) and solar collectors alternately. The results show that the system can meet the heating-cooling energy needs of the building. In the heating mode, the heat directly supplied by solar collectors accounted for 49.7% of the total heating output, and the average coefficient of performance (COP) of the heat pump and the system were 4.29 and 6.55, respectively. In the cooling mode, the COP of the system reached 21.35, as the heat pump was not necessary to be started. After a year of operation, the heat extracted from the soil by the heat pump accounted for 75.5% of the heat stored by solar seasonal thermal storage. The excess heat raised the soil temperature to a higher level, which was favorable for increasing the COP of the heat pump. (author)

  5. Thermo-economic Optimization of Solar Assisted Heating and Cooling (SAHC System

    Directory of Open Access Journals (Sweden)

    A. Ghafoor

    2014-12-01

    Full Text Available The energy demand for cooling is continuously increasing due to growing thermal loads, changing architectural modes of building, and especially due to occupants indoor comfort requirements resulting higher electricity demand notably during peak load hours. This increasing electricity demand is resulting higher primary energy consumption and emission of green house gases (GHG due to electricity generation from fossil fuels. An exciting alternative to reduce the peak electricity consumption is the possible utilization of solar heat to run thermally driven cooling machines instead of vapor compression machines utilizing high amount of electricity. In order to widen the use of solar collectors, they should also be used to contribute for sanitary hot water production and space heating. Pakistan lying on solar belt has a huge potential to utilize solar thermal heat for heating and cooling requirement because cooling is dominant throughout the year and the enormous amount of radiation availability provides an opportunity to use it for solar thermal driven cooling systems. The sensitivity analysis of solar assisted heating and cooling system has been carried out under climatic conditions of Faisalabad (Pakistan and its economic feasibility has been calculated using maximization of NPV. Both storage size and collector area has been optimized using different economic boundary conditions. Results show that optimum area of collector lies between 0.26m2 to 0.36m2 of collector area per m2 of conditioned area for ieff values of 4.5% to 0.5%. The optimum area of collector increases by decreasing effective interest rate resulting higher solar fraction. The NPV was found to be negative for all ieff values which shows that some incentives/subsidies are needed to be provided to make the system cost beneficial. Results also show that solar fraction space heating varies between 87 and 100% during heating season and solar fraction cooling between 55 and 100% during

  6. District heating rehabilitation project. Viljandi - Estonia. Final report

    International Nuclear Information System (INIS)

    1998-04-01

    The main objective of the project has been to assist Viljandi Municipality with the rehabilitation of their district heating system, and thereby to support the positive development of the district heating system in Viljandi to a more energy efficient and rational system and to achieve a significantly decrease in the pollution from the production of heat energy in Viljandi. The project has also included technical assistance to Viljandi DH company, in order to make them capable of operation and maintaining of the new substations, and also training of the local operational staff for operation of the complete district heating system. Viljandi is a county and is centrally located in Estonia, which makes Viljandi very suitable as recipient for a demonstration project. One important objective was the projects significantly positive environmental impact in reduction of the generated emissions of CO 2 , NO x and SO 2 , as the project includes installation of more efficient energy systems and supply of heat from the 2 existing district heating plants (both are partly fired with wood chips) instead of heating by very old and worn-out coal fired boilers and inexpedient designed substations with the present operational conditions. (EG)

  7. District heating rehabilitation project. Viljandi - Estonia. Final report

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1998-04-01

    The main objective of the project has been to assist Viljandi Municipality with the rehabilitation of their district heating system, and thereby to support the positive development of the district heating system in Viljandi to a more energy efficient and rational system and to achieve a significantly decrease in the pollution from the production of heat energy in Viljandi. The project has also included technical assistance to Viljandi DH company, in order to make them capable of operation and maintaining of the new substations, and also training of the local operational staff for operation of the complete district heating system. Viljandi is a county and is centrally located in Estonia, which makes Viljandi very suitable as recipient for a demonstration project. One important objective was the projects significantly positive environmental impact in reduction of the generated emissions of CO{sub 2}, NO{sub x} and SO{sub 2}, as the project includes installation of more efficient energy systems and supply of heat from the 2 existing district heating plants (both are partly fired with wood chips) instead of heating by very old and worn-out coal fired boilers and inexpedient designed substations with the present operational conditions. (EG)

  8. Reduction of Energy Consumption and CO2 Emissions in Domestic Water Heating by Means of Direct Expansion Solar Assisted Heat Pump

    International Nuclear Information System (INIS)

    Baleta, J.; Curko, T.; Cutic, T.; Pasanec, J.; Soldo, V.

    2012-01-01

    Domestic water heating in households sector is usually performed by either fossil fuel fired or electric boilers. Both the combustion process of the former and large electricity consumption of the latter strongly influence overall greenhouse gas emissions. Moreover, very high specific heat of water requires large quantity of energy for water heating making a significant impact on the overall energy consumption in the households sector whose total consumption of 80,81 PJ equals to 19,6% of total primary energy supply in Croatia in 2010. Considering the mentioned impact on energy consumption and CO 2 emissions as well as goals set by European Commission (so called 20-20-20), new technologies based on renewable energy sources are more than welcome in the field of domestic water heating. Direct expansion solar assisted heat pump is presented in this paper. Its working principle is based on single-stage vapour-compression cycle. Representing a gradual step to commercial application with a water tank of 300 l, the developed mobile unit is designed as a test rig enabling all necessary measurements to evaluate potential of solar irradiation for domestic water heating on various locations. Besides the unit description, trial testing results are presented and analyzed as well as a basic comparison of CO 2 emissions between solar assisted heat pump and conventionally used water heating systems. Taking into account both the decentralized water heating and favourable climatic conditions (especially along the Croatian Adriatic coast) as well as rising fossil fuel prices, it is expected that solar assisted heat pumps will be commercialized in the near future.(author)

  9. Establishing biomass heating in the UK: phase 2

    International Nuclear Information System (INIS)

    2000-01-01

    The Biomass Heat Working Group, first set up in 1995, was taken on by British BioGen in 1996. Over the summer of 1996 British BioGen, supported by DTI, worked with the group to produce 'A Strategy to Develop the UK Market for Biomass Heating Installations'. In the spring of 1997 British BioGen agreed a two-year programme with ETSU (for the DTI) to 'Establish Biomass Heating in the UK'. The DTI's New and Renewable Energy Programme has supported this two-year programme which aims to bring together industry stakeholders and assist in the development of a significant biomass heat market in the UK. Overall we believe the project has been successful in its aim to increase the volume of biomass heating enquiries and enable greater use of the industry 'knowledge base'. Throughout the duration of the project a number of new biomass heating systems have been installed, including Shenstone Lodge School, Boughton Pumping Station and Elvendon Priory. In addition, an efficient system of information exchange has been established for customers and industry. British BioGen believe that the benefits of this system will be a crucial factor in achieving bioenergy industry targets of 2MWt for domestic heating, 2MWt for industrial and commercial heating and 2MWt for CHP by the end of 2001. The remainder of this summary offers highlights of the activities undertaken within the project, outlines the conclusions of the project and makes brief recommendations for further actions to assist the further deployment of biomass heating in the UK. (author)

  10. A novel solar-assisted heat pump driven by photovoltaic/thermal collectors: Dynamic simulation and thermoeconomic optimization

    International Nuclear Information System (INIS)

    Calise, Francesco; Dentice d'Accadia, Massimo; Figaj, Rafal Damian; Vanoli, Laura

    2016-01-01

    This paper presents a dynamic simulation model and a thermo-economic analysis of a novel polygeneration system based on a solar-assisted heat pump and an adsorption chiller, both driven by PVT (photovoltaic/thermal) collectors. The aim of this work is to design and dynamically simulate a novel ultra-high efficient solar heating and cooling system. The overall plant layout is designed to supply electricity, space heating and cooling and domestic hot water for a small residential building. The system combines solar cooling, solar-assisted heat pump and photovoltaic/thermal collector technologies in a novel solar polygeneration system. In fact, the polygeneration system is based on a PVT solar field, coupled with a water-to-water electric heat pump or to an adsorption chiller. PVT collectors simultaneously produce electricity and thermal energy. During the winter, hot water produced by PVT collectors primarily supplies the evaporator of the heat pump, whereas in summer, solar energy supplies an adsorption chiller providing the required space cooling. All year long, solar thermal energy in excess is converted into DHW (domestic hot water). The system model was developed in TRNSYS environment. 1-year dynamic simulations are performed for different case studies in various weather conditions. The results are analysed on different time bases presenting energetic, environmental and economic performance data. Finally, a sensitivity analysis and a thermoeconomic optimization were performed, in order to determine the set of system design/control parameters that minimize the simple pay-back period. The results showed a total energy efficiency of the PVT of 49%, a heat pump yearly coefficient of performance for heating mode above 4 and a coefficient of performance of the adsorption chiller of 0.55. Finally, it is also concluded that system performance is highly sensitive to the PVT field area. The system is profitable when a capital investment subsidy of 50% is considered

  11. Thermal performance analysis of a solar heating plant

    DEFF Research Database (Denmark)

    Fan, Jianhua; Huang, Junpeng; Andersen, Ola Lie

    was developed to calculate thermal performances of the plant. In the Trnsys model, three solar collector fields with a total solar collector area of 33,300 m2, a seasonal water pit heat storage of 75,000 m3, a simplified CO2 HP, a simplified ORC unit and a simplified wood chip boiler were included. The energy......Detailed measurements were carried out on a large scale solar heating plant located in southern Denmark in order to evaluate thermal performances of the plant. Based on the measurements, energy flows of the plant were evaluated. A modified Trnsys model of the Marstal solar heating plant...... consumption of the district heating net was modeled by volume flow rate and given forward and return temperatures of the district heating net. Weather data from a weather station at the site of the plant were used in the calculations. The Trnsys calculated yearly thermal performance of the solar heating plant...

  12. Establishing biomass heating in the UK: phase 2

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2000-07-01

    The Biomass Heat Working Group, first set up in 1995, was taken on by British BioGen in 1996. Over the summer of 1996 British BioGen, supported by DTI, worked with the group to produce 'A Strategy to Develop the UK Market for Biomass Heating Installations'. In the spring of 1997 British BioGen agreed a two-year programme with ETSU (for the DTI) to 'Establish Biomass Heating in the UK'. The DTI's New and Renewable Energy Programme has supported this two-year programme which aims to bring together industry stakeholders and assist in the development of a significant biomass heat market in the UK. Overall we believe the project has been successful in its aim to increase the volume of biomass heating enquiries and enable greater use of the industry 'knowledge base'. Throughout the duration of the project a number of new biomass heating systems have been installed, including Shenstone Lodge School, Boughton Pumping Station and Elvendon Priory. In addition, an efficient system of information exchange has been established for customers and industry. British BioGen believe that the benefits of this system will be a crucial factor in achieving bioenergy industry targets of 2MWt for domestic heating, 2MWt for industrial and commercial heating and 2MWt for CHP by the end of 2001. The remainder of this summary offers highlights of the activities undertaken within the project, outlines the conclusions of the project and makes brief recommendations for further actions to assist the further deployment of biomass heating in the UK. (author)

  13. Utilization of straw in district heating and CHP plants

    International Nuclear Information System (INIS)

    Nikolaisen, L.

    1993-01-01

    In Denmark 64 straw-fired district heating plants and 6 decentral CHP plants have been built since 1980 which are completely or partly straw-fired. The annual straw consumption in the district heating plants is 275,000 tons and in the decentral plants about 200,000 tons. The size of the district heating plants amounts to 0.5 MW - 10 MW and that of the CHP plants to 7 MW - 67 MW heat flow rate. Either whole bales or cut/scarified straw is used for firing. Hesston bales of about 450 kg control the market. The Centre of Biomass Technology is an activity supported 100 % by the Danish Energy Agency with the purpose of increasing the use of straw and wood in the energy supply (orig.)

  14. Cost and primary energy efficiency of small-scale district heating systems

    International Nuclear Information System (INIS)

    Truong, Nguyen Le; Gustavsson, Leif

    2014-01-01

    Highlights: • We analyzed minimum-cost options for small-scale DHSs under different contexts. • District heat production cost increases with reduced DHS scales. • Fewer technical options are suitable for small-scale DHSs. • Systems with combined technologies are less sensitive to changes in fuel prices. - Abstract: Efficient district heat production systems (DHSs) can contribute to achieving environmental targets and energy security for countries that have demands for space and water heating. The optimal options for a DHS vary with the environmental and social-political contexts and the scale of district heat production, which further depends on the size of the community served and the local climatic conditions. In this study, we design a small-scale, minimum-cost DHS that produces approximately 100 GWh heat per year and estimate the yearly production cost and primary energy use of this system. We consider conventional technologies, such as heat-only boilers, electric heat pumps and combined heat and power (CHP) units, as well as emerging technologies, such as biomass-based organic Rankine cycle (BORC) and solar water heating (SWH). We explore how different environmental and social-political situations influence the design of a minimum-cost DHS and consider both proven and potential technologies for small-scale applications. Our calculations are based on the real heat load duration curve for a town in southern Sweden. We find that the district heat production cost increases and that the potential for cogeneration decreases with smaller district heat production systems. Although the selection of technologies for a minimum-cost DHS depends on environmental and social-political contexts, fewer technical options are suitable for small-scale systems. Emerging technologies such as CHP-BORC and SWH improve the efficiency of primary energy use for heat production, but these technologies are more costly than conventional heat-only boilers. However, systems with

  15. German central solar heating plants with seasonal heat storage

    Energy Technology Data Exchange (ETDEWEB)

    Bauer, D.; Marx, R.; Nussbicker-Lux, J.; Ochs, F.; Heidemann, W. [Institute of Thermodynamics and Thermal Engineering (ITW), University of Stuttgart, Pfaffenwaldring 6, D-70550 Stuttgart (Germany); Mueller-Steinhagen, H. [Institute of Thermodynamics and Thermal Engineering (ITW), University of Stuttgart, Pfaffenwaldring 6, D-70550 Stuttgart (Germany); Institute of Technical Thermodynamics (ITT), German Aerospace Centre (DLR), Stuttgart (Germany)

    2010-04-15

    Central solar heating plants contribute to the reduction of CO{sub 2}-emissions and global warming. The combination of central solar heating plants with seasonal heat storage enables high solar fractions of 50% and more. Several pilot central solar heating plants with seasonal heat storage (CSHPSS) built in Germany since 1996 have proven the appropriate operation of these systems and confirmed the high solar fractions. Four different types of seasonal thermal energy stores have been developed, tested and monitored under realistic operation conditions: Hot-water thermal energy store (e.g. in Friedrichshafen), gravel-water thermal energy store (e.g. in Steinfurt-Borghorst), borehole thermal energy store (in Neckarsulm) and aquifer thermal energy store (in Rostock). In this paper, measured heat balances of several German CSHPSS are presented. The different types of thermal energy stores and the affiliated central solar heating plants and district heating systems are described. Their operational characteristics are compared using measured data gained from an extensive monitoring program. Thus long-term operational experiences such as the influence of net return temperatures are shown. (author)

  16. Low Temperature District Heating for Future Energy Systems

    DEFF Research Database (Denmark)

    Ford, Rufus; Pietruschka, Dirk; Sipilä, Kari

    participants being VTT Technical Research Centre of Finland (VTT), Technical University of Denmark (DTU), Norwegian University of Science and Technology (NTNU), Stuttgart Technology University of Applied Sciences (HFT) and SSE Enterprise in United Kingdom. The demonstration cases described in the report......This report titled “Case studies and demonstrations” is the subtask D report of the IEA DHC|CHP Annex TS1 project “Low Temperature District Heating for Future Energy Systems” carried out between 2013 and 2016. The project was led by Fraunhofer Institute for Building Physics (IBP) with the other...... include examples on low temperature district heating systems, solar heating in a district heating system, heat pump based heat supply and energy storages for both peak load management and for seasonal heat storage. Some demonstrations have been implemented while others are at planning phase...

  17. Solar dryer with thermal storage and biomass-backup heater

    Energy Technology Data Exchange (ETDEWEB)

    Madhlopa, A. [Department of Physics and Biochemical Sciences, Malawi Polytechnic, P/Bag 303, Blantyre 3 (Malawi); Ngwalo, G. [Department of Mechanical Engineering, Malawi Polytechnic, P/Bag 303, Blantyre 3 (Malawi)

    2007-04-15

    An indirect type natural convection solar dryer with integrated collector-storage solar and biomass-backup heaters has been designed, constructed and evaluated. The major components of the dryer are biomass burner (with a rectangular duct and flue gas chimney), collector-storage thermal mass and drying chamber (with a conventional solar chimney). The thermal mass was placed in the top part of the biomass burner enclosure. The dryer was fabricated using simple materials, tools and skills, and it was tested in three modes of operation (solar, biomass and solar-biomass) by drying twelve batches of fresh pineapple (Ananas comosus), with each batch weighing about 20 kg. Meteorological conditions were monitored during the dehydration process. Moisture and vitamin C contents were determined in both fresh and dried samples. Results show that the thermal mass was capable of storing part of the absorbed solar energy and heat from the burner. It was possible to dry a batch of pineapples using solar energy only on clear days. Drying proceeded successfully even under unfavorable weather conditions in the solar-biomass mode of operation. In this operational mode, the dryer reduced the moisture content of pineapple slices from about 669 to 11% (db) and yielded a nutritious dried product. The average values of the final-day moisture-pickup efficiency were 15%, 11% and 13% in the solar, biomass and solar-biomass modes of operation respectively. It appears that the solar dryer is suitable for preservation of pineapples and other fresh foods. Further improvements to the system design are suggested. (author)

  18. Integration of biomass into urban energy systems for heat and power. Part I: An MILP based spatial optimization methodology

    International Nuclear Information System (INIS)

    Pantaleo, Antonio M.; Giarola, Sara; Bauen, Ausilio; Shah, Nilay

    2014-01-01

    Highlights: • MILP tool for optimal sizing and location of heating and CHP plants to serve residential energy demand. • Trade-offs between local vs centralized heat generation, district heating vs natural gas distribution systems. • Assessment of multi-biomass supply chains and biomass to biofuel processing technologies. • Assessment of the key factors influencing the use of biomass and district heating in residential areas. - Abstract: The paper presents a mixed integer linear programming (MILP) approach to optimize multi-biomass and natural gas supply chain strategic design for heat and power generation in urban areas. The focus is on spatial and temporal allocation of biomass supply, storage, processing, transport and energy conversion (heat and CHP) to match the heat demand of residential end users. The main aim lies on the representation of the relationships between the biomass processing and biofuel energy conversion steps, and on the trade-offs between centralized district heating plants and local heat generation systems. After a description of state of the art and research trends in urban energy systems and bioenergy modelling, an application of the methodology to a generic case study is proposed. With the assumed techno-economic parameters, biomass based thermal energy generation results competitive with natural gas, while district heating network results the main option for urban areas with high thermal energy demand density. Potential further applications of this model are also described, together with main barriers for development of bioenergy routes for urban areas

  19. Integrated solar-assisted heat pumps for water heating coupled to gas burners; control criteria for dynamic operation

    International Nuclear Information System (INIS)

    Scarpa, F.; Tagliafico, L.A.; Tagliafico, G.

    2011-01-01

    A direct expansion integrated solar-assisted heat pump (ISAHP) is compared to a traditional flat plate solar panel for low temperature (45 deg. C) water heating applications. The (simulated) comparison is accomplished assuming both the devices are energy supplemented with an auxiliary standard gas burner, to provide the typical heat duty of a four-member family. Literature dynamical models of the systems involved have been used to calculate the main performance figures in a context of actual climatic conditions and typical stochastic user demand. The paper highlights new heat pump control concepts, needed when maximum energy savings are the main goal of the apparatus for given user demand. Simulations confirm the high collector efficiency of the ISAHP when its panel/evaporator works at temperature close to the ambient one. The device, with respect to a flat plate solar water heater, shows a doubled performance, so that it can do the same task just using an unglazed panel with roughly half of the surface.

  20. Energy dashboard for real-time evaluation of a heat pump assisted solar thermal system

    Science.gov (United States)

    Lotz, David Allen

    The emergence of net-zero energy buildings, buildings that generate at least as much energy as they consume, has lead to greater use of renewable energy sources such as solar thermal energy. One example is a heat pump assisted solar thermal system, which uses solar thermal collectors with an electrical heat pump backup to supply space heating and domestic hot water. The complexity of such a system can be somewhat problematic for monitoring and maintaining a high level of performance. Therefore, an energy dashboard was developed to provide comprehensive and user friendly performance metrics for a solar heat pump system. Once developed, the energy dashboard was tested over a two-week period in order to determine the functionality of the dashboard program as well as the performance of the heating system itself. The results showed the importance of a user friendly display and how each metric could be used to better maintain and evaluate an energy system. In particular, Energy Factor (EF), which is the ratio of output energy (collected energy) to input energy (consumed energy), was a key metric for summarizing the performance of the heating system. Furthermore, the average EF of the solar heat pump system was 2.29, indicating an efficiency significantly higher than traditional electrical heating systems.

  1. The solar-assisted district heating concept in Stuttgart-Burgholzhof; Das solarunterstuetzte Nahwaermekonzept Stuttgart-Burgholzhof

    Energy Technology Data Exchange (ETDEWEB)

    Grosshans, D. [Neckarwerke Stuttgart AG (Germany)

    1998-12-31

    The housing area Burgholzhof is located on a hill above the valley of Stuttgart in the city borough of Canstatt. The building area has a size of 13.4 hectare and will contain 1,360 flats with a total heated area of 86,000 square metres that can house 2,800 people. Heat will be supplied by a heating power station, a plant for thermal use of solar energy and a heat distribution system built by Neckarwerke Stuttgart (Stuttgart utility company). The Neckarwerke Stuttgart paid the construction costs of the plant for thermal utilisation of solar energy. They will not be included in the energy price charged to the consumer. (orig.) [Deutsch] Das Wohngebiet `Burgholzhof` liegt auf einer Anhoehe ueber dem Talkessel der Landeshauptstadt Stuttgart im Stadtteil Bad-Cannstatt. Die Bebauungsflaeche betraegt nach einer im Jahr 1997 durchgefuehrten Arrondierung 13,4 ha. Im Endausbau werden etwa 1360 Wohneinheiten mit einer beheizten Gesamtflaeche von etwa 86 000 m{sup 2} entstanden sein. Somit koennen etwa 2800 Buergerinnen und Buerger in diesem neuen Stadtteil wohnen. Zur Waermeversorgung wurde ein Heizwerk, eine Anlage zur thermischen Nutzung der Sonnenenergie und ein Waermeverteilsystem von den NWS erstellt. Die Kosten fuer den Bau der Anlage zur thermischen Nutzung der Sonnenenergie wurden von den NWS uebernommen. Sie sind somit kein Bestandteil des an die Nutzer zu verrechnenden Waermepreises. (orig.)

  2. Large Scale Solar Heating

    DEFF Research Database (Denmark)

    Heller, Alfred

    2001-01-01

    The main objective of the research was to evaluate large-scale solar heating connected to district heating (CSDHP), to build up a simulation tool and to demonstrate the application of the simulation tool for design studies and on a local energy planning case. The evaluation was mainly carried out...... model is designed and validated on the Marstal case. Applying the Danish Reference Year, a design tool is presented. The simulation tool is used for proposals for application of alternative designs, including high-performance solar collector types (trough solar collectors, vaccum pipe collectors......). Simulation programs are proposed as control supporting tool for daily operation and performance prediction of central solar heating plants. Finaly the CSHP technolgy is put into persepctive with respect to alternatives and a short discussion on the barries and breakthrough of the technology are given....

  3. Frosting characteristics and heating performance of a direct-expansion solar-assisted heat pump for space heating under frosting conditions

    International Nuclear Information System (INIS)

    Huang, Wenzhu; Ji, Jie; Xu, Ning; Li, Guiqiang

    2016-01-01

    Highlights: • Frosting and heating performance of DX-SAHP under frosting conditions is investigated. • The conditions when DX-SAHP frosts are studied. • The frosting process is observed during 360 min of operating. • The effect of ambient temperature, relative humidity and solar irradiation is analyzed. - Abstract: Direct expansion solar-assisted heat pump system (DX-SAHP) is promising in energy saving applications, but the performance of DX-SAHP under frosting conditions is rarely reported in the published literatures. In this paper, a DX-SAHP system with bare solar collectors for space heating is designed and experimentally investigated in the enthalpy difference lab with a solar simulator. The system is tested under a range of frosting conditions, with the ambient temperatures from 7 °C to −3 °C, the relative humidities of 50%, 70% and 90% and the solar irradiances of 0 W/m"2, 100 W/m"2, 200 W/m"2 and 300 W/m"2. The conditions when the DX-SAHP system frosts are studied. Results show that solar irradiance as low as 100 W/m"2 can totally prevent frosting when the ambient temperature is above −3 °C and the relative humidity is 70%. Besides, the frosting process is observed to be slower than that of fin-and-tube heat exchangers. The evaporator is not seriously frosted and the system performance is not significantly influenced after 360 min of continuous operating. Moreover the effects of ambient parameters, including the ambient temperature and the relative humidity, especially solar irradiation, on the system performance are studied and analyzed. Solar irradiation can effectively prevent or retard frosting, and also improve the heating performance of the DX-SAHP system. The DX-SAHP system is proved to be applicable under frosting conditions.

  4. Assessment of solar-assisted gas-fired heat pump systems

    Science.gov (United States)

    Lansing, F. L.

    1981-01-01

    As a possible application for the Goldstone Energy Project, the performance of a 10 ton heat pump unit using a hybrid solar gas energy source was evaluated in an effort to optimize the solar collector size. The heat pump system is designed to provide all the cooling and/or heating requirements of a selected office building. The system performance is to be augmented in the heating mode by utilizing the waste heat from the power cycle. A simplified system analysis is described to assess and compute interrrelationships of the engine, heat pump, and solar and building performance parameters, and to optimize the solar concentrator/building area ratio for a minimum total system cost. In addition, four alternative heating cooling systems, commonly used for building comfort, are described; their costs are compared, and are found to be less competitive with the gas solar heat pump system at the projected solar equipment costs.

  5. Fort Carson Building 1860 Biomass Heating Analysis Report

    Energy Technology Data Exchange (ETDEWEB)

    Hunsberger, Randolph [National Renewable Energy Lab. (NREL), Golden, CO (United States); Tomberlin, Gregg [National Renewable Energy Lab. (NREL), Golden, CO (United States); Gaul, Chris [National Renewable Energy Lab. (NREL), Golden, CO (United States)

    2015-09-01

    As part of the Army Net-Zero Energy Installation program, the Fort Carson Army Base requested that NREL evaluate the feasibility of adding a biomass boiler to the district heating system served by Building 1860. We have also developed an Excel-spreadsheet-based decision support tool--specific to the historic loads served by Building 1860--with which users can perform what-if analysis on gas costs, biomass costs, and other parameters. For economic reasons, we do not recommend adding a biomass system at this time.

  6. Experimental studies on a ground coupled heat pump with solar thermal collectors for space heating

    International Nuclear Information System (INIS)

    Xi, Chen; Hongxing, Yang; Lin, Lu; Jinggang, Wang; Wei, Liu

    2011-01-01

    This paper presents experimental studies on a solar-assisted ground coupled heat pump (SAGCHP) system for space heating. The system was installed at the Hebei Academy of Sciences in Shijiazhuang (lat. N38 o 03', long. E114 o 26'), China. Solar collectors are in series connection with the borehole array through plate heat exchangers. Four operation modes of the system were investigated throughout the coldest period in winter (Dec 5th to Dec 27th). The heat pump performance, borehole temperature distributions and solar colleting characteristics of the SAGCHP system are analyzed and compared when the system worked in continuous or intermittent modes with or without solar-assisted heating. The SAGCHP system is proved to perform space heating with high energy efficiency and satisfactory solar fraction, which is a promising substitute for the conventional heating systems. It is also recommended to use the collected solar thermal energy as an alternative source for the heat pump instead of recharging boreholes for heat storage because of the enormous heat capacity of the earth. -- Highlights: → We study four working modes of a solar-assisted ground coupled heat pump. → The heating performance is in direct relation with the borehole temperature. → Solar-assisted heating elevates borehole temperature and system performance. → The system shows higher efficiency over traditional heating systems in cold areas. → Solar heat is not suggested for high temperature seasonal storage.

  7. Biomass Supply Planning for Combined Heat and Power Plants using Stochastic Programming

    DEFF Research Database (Denmark)

    Guericke, Daniela; Blanco, Ignacio; Morales González, Juan Miguel

    method using stochastic optimization to support the biomass supply planning for combined heat and power plants. Our two-phase approach combines mid-term decisions about biomass supply contracts with the short-term decisions regarding the optimal market participation of the producer to ensure......During the last years, the consumption of biomass to produce power and heat has increased due to the new carbon neutral policies. Nowadays, many district heating systems operate their combined heat and power (CHP) plants using different types of biomass instead of fossil fuel, especially to produce......, and heat demand and electricity prices vary drastically during the planning period. Furthermore, the optimal operation of combined heat and power plants has to consider the existing synergies between the power and heating systems while always fulfilling the heat demand of the system. We propose a solution...

  8. District heating in Switzerland

    International Nuclear Information System (INIS)

    Herzog, F.

    1991-01-01

    District heating has been used in Switzerland for more than 50 years. Its share of the heat market is less than 3% today. An analysis of the use of district heating in various European countries shows that a high share of district heating in the heat market is always dependent on ideal conditions for its use. Market prospects and possible future developments in the use of district heating in Switzerland are described in this paper. The main Swiss producers and distributors of district heating are members of the Association of District Heating Producers and Distributors. This association supports the installation of district heating facilities where ecological, energetical and economic aspects indicate that district heating would be a good solution. (author) 2 tabs., 6 refs

  9. Solar-assisted heat pump – A sustainable system for low-temperature water heating applications

    International Nuclear Information System (INIS)

    Chaturvedi, S.K.; Gagrani, V.D.; Abdel-Salam, T.M.

    2014-01-01

    Highlights: • DX-SAHP water heaters systems are economical as well as energy conserving. • The economic analysis is performed using the life cycle cost (LCC) analysis. • LCC can be optimized with respect to the collector area at a specific temperature. • For high load temperature range a two stage heat pump system is more appropriate. - Abstract: Direct expansion solar assisted heat pump systems (DX-SAHP) have been widely used in many applications including water heating. In the DX-SAHP systems the solar collector and the heat pump evaporator are integrated into a single unit in order to transfer the solar energy to the refrigerant. The present work is aimed at studying the use of the DX-SAHP for low temperature water heating applications. The novel aspect of this paper involves a detailed long-term thermo-economic analysis of the energy conservation potential and economic viability of these systems. The thermal performance is simulated using a computer program that incorporates location dependent radiation, collector, economic, heat pump and load data. The economic analysis is performed using the life cycle cost (LCC) method. Results indicate that the DX-SAHP water heaters systems when compared to the conventional electrical water heaters are both economical as well as energy conserving. The analysis also reveals that the minimum value of the system life cycle cost is achieved at optimal values of the solar collector area as well as the compressor displacement capacity. Since the cost of SAHP system presents a barrier to mass scale commercialization, the results of the present study indicating that the SAHP life cycle cost can be minimized by optimizing the collector area would certainly be helpful in lowering, if not eliminating, the economic barrier to these systems. Also, at load temperatures higher than 70 °C, the performance of the single stage heat pump degrades to the extent that its cost and efficiency advantages over the electric only system are

  10. CMHC's district heating work may lead to solar power-towers

    Energy Technology Data Exchange (ETDEWEB)

    Peters, W

    1979-11-01

    A four-year study of district heating systems by the Canada Mortgage and Housing Corporation (CMHC) may combine with leadership recognition by the International Energy Agency to allow Canada to join the U.S. as the center for power-tower technology. The application of central receivers to district heating evolved from the district heating study as heliostat technology developed and the economics improved with scale. Based on the Barstow, Calif. prototype, a commercial version is envisioned for the mid-1980s to generate steam for power generation, heating, and cooling. A proponent suggests applying it to a multi-fuel system as a retrofit after the technology is perfected. Land availability and the need for direct sunlight present problems for this type of application in Canada, where much of the light is diffuse. A cautious view is taken by those who feel that cost will be prohibitive and who point out that the U.S. tests have yet to prove viability. (DCK)

  11. Projecting demand and supply of forest biomass for heating in Norway

    International Nuclear Information System (INIS)

    Tromborg, Erik; Havskjold, Monica; Lislebo, Ole; Rorstad, Per Kristian

    2011-01-01

    This paper assesses the increase in demand and supply for forest biomass for heating in Norway in 2020. By then there is a political aim to double the national production of bioenergy from the level in 2008. The competitiveness of woody biomass in central and district heating is analyzed in a model selecting the least-cost heating technology and scale in municipalities given a set of constraints and under different fuels price scenarios. The supply of forest biomass from roundwood is estimated based on data of forest inventories combined with elasticities regarding price and standing volumes. The supply of biomass from harvesting residues is estimated in an engineering approach based on data from the national forest inventories and roundwood harvest. The results show how the production of bioenergy is affected by changes in energy prices and support schemes for bioenergy. One conclusion from the analyses is that the government target of 14 TWh more bioenergy by 2020 is not likely to be met by current technologies and policy incentives. The contribution of the analysis is the detailed presentation of the heat market potentials and technology choices combined with supply functions for both roundwood and harvesting residues. - Highlights: → This paper accesses the demand and supply for forest biomass for heating in Norway in 2020. → Market share for wood in central and new district heating is analyzed in a cost-minimizing model. → The supply of forest biomass includes wood chips from import, roundwood and harvesting residues. → The production of bioenergy is affected by changes in energy prices and support schemes. → The government target for bioenergy is not met by current technologies and policy incentives.

  12. Life cycle assessment of fuels for district heating: A comparison of waste incineration, biomass- and natural gas combustion

    International Nuclear Information System (INIS)

    Eriksson, Ola; Finnveden, Goeran; Ekvall, Tomas; Bjoerklund, Anna

    2007-01-01

    The aim of this consequential life cycle assessment (LCA) is to compare district heating based on waste incineration with combustion of biomass or natural gas. The study comprises two options for energy recovery (combined heat and power (CHP) or heat only), two alternatives for external, marginal electricity generation (fossil lean or intense), and two alternatives for the alternative waste management (landfill disposal or material recovery). A secondary objective was to test a combination of dynamic energy system modelling and LCA by combining the concept of complex marginal electricity production in a static, environmental systems analysis. Furthermore, we wanted to increase the methodological knowledge about how waste can be environmentally compared to other fuels in district-heat production. The results indicate that combustion of biofuel in a CHP is environmentally favourable and robust with respect to the avoided type of electricity and waste management. Waste incineration is often (but not always) the preferable choice when incineration substitutes landfill disposal of waste. It is however, never the best choice (and often the worst) when incineration substitutes recycling. A natural gas fired CHP is an alternative of interest if marginal electricity has a high fossil content. However, if the marginal electricity is mainly based on non-fossil sources, natural gas is in general worse than biofuels

  13. Development of a direct expansion solar assisted heat pump for hot water supply

    International Nuclear Information System (INIS)

    Abdesselam Hamloui; Ong, K.S.; Than Cheok Fah; Masjuki Hassan

    2000-01-01

    Experimental investigations were conducted on the direct expansion solar assisted Heat Pump (DESAHP). Refrigerant R-22 was expanded in the solar collector which also acted as the evaporator in a conventional vapor compression refrigerating machine. The experiments were conducted under conditions of high and low solar radiation, with evaporator completely shaded from the sun, and at night. System thermal performance was determined by measuring refrigerant flow rate, temperature and pressure at numerous points in the system. The results showed that 227-l of water could be heated from 3O degree to 55 degree C in about 105 minutes. Higher water temperatures were obtained during hot sunny days. The coefficient of performance of heating, COP h , ranged from 11 to 4.7, depending upon operating conditions. The total saving of electric energy during hot sunny days was about 460 %. It means that for 1 kWh of electrical input to the system, we achieve 4.6 kWh. This percentage decreases as the evaporator temperature decreases and is a function of solar energy input. (Author)

  14. Monitoring of the energy performance of a district heating CHP plant based on biomass boiler and ORC generator

    International Nuclear Information System (INIS)

    Prando, Dario; Renzi, Massimiliano; Gasparella, Andrea; Baratieri, Marco

    2015-01-01

    More than seventy district heating (DH) plants based on biomass are operating in South Tyrol (Italy) and most of them supply heat to residential districts. Almost 20% of them are cogenerative systems, thus enabling primary energy savings with respect to the separate production of heat and power. However, the actual performance of these systems in real operation can considerably differ from the nominal one. The main objectives of this work are the assessment of the energy performance of a biomass boiler coupled with an Organic Rankine Cycle (i.e. ORC) generator under real operating conditions and the identification of its potential improvements. The fluxes of energy and mass of the plant have been measured onsite. This experimental evaluation has been supplemented with a thermodynamic model of the ORC generator, calibrated with the experimental data, which is capable to predict the system performance under different management strategies of the system. The results have highlighted that a decrease of the DH network temperature of 10 °C can improve the electric efficiency of the ORC generator of one percentage point. Moreover, a DH temperature reduction could decrease the main losses of the boiler, namely the exhaust latent thermal loss and the exhaust sensible thermal loss, which account for 9% and 16% of the boiler input power, respectively. The analysis of the plant has pointed out that the ORC pump, the flue gases extractor, the thermal oil pump and the condensation section fan are the main responsible of the electric self-consumption. Finally, the negative effect of the subsidisation on the performance of the plant has been discussed. - Highlights: • Energy performance of a biomass boiler coupled to an ORC turbine in real operation. • Potential improvements of a CHP plant connected to a DH network. • Performance prediction by means of a calibrated ORC thermodynamic model. • Influence of the DH temperature on the electric efficiency. • Impact of the

  15. Heat demand mapping and district heating grid expansion analysis: Case study of Velika Gorica

    Directory of Open Access Journals (Sweden)

    Dorotić Hrvoje

    2017-01-01

    Full Text Available Highly efficient cogeneration and district heating systems have a significant potential for primary energy savings and the reduction of greenhouse gas emissions through the utilization of a waste heat and renewable energy sources. These potentials are still highly underutilized in most European countries. They also play a key role in the planning of future energy systems due to their positive impact on the increase of integration of intermittent renewable energy sources, for example wind and solar in a combination with power to heat technologies. In order to ensure optimal levels of district heating penetration into an energy system, a comprehensive analysis is necessary to determine the actual demands and the potential energy supply. Economical analysis of the grid expansion by using the GIS based mapping methods hasn’t been demonstrated so far. This paper presents a heat demand mapping methodology and the use of its output for the district heating network expansion analysis. The result are showing that more than 59% of the heat demand could be covered by the district heating in the city of Velika Gorica, which is two times more than the present share. The most important reason of the district heating's unfulfilled potential is already existing natural gas infrastructure.

  16. Heat demand mapping and district heating grid expansion analysis: Case study of Velika Gorica

    Science.gov (United States)

    Dorotić, Hrvoje; Novosel, Tomislav; Duić, Neven; Pukšec, Tomislav

    2017-10-01

    Highly efficient cogeneration and district heating systems have a significant potential for primary energy savings and the reduction of greenhouse gas emissions through the utilization of a waste heat and renewable energy sources. These potentials are still highly underutilized in most European countries. They also play a key role in the planning of future energy systems due to their positive impact on the increase of integration of intermittent renewable energy sources, for example wind and solar in a combination with power to heat technologies. In order to ensure optimal levels of district heating penetration into an energy system, a comprehensive analysis is necessary to determine the actual demands and the potential energy supply. Economical analysis of the grid expansion by using the GIS based mapping methods hasn't been demonstrated so far. This paper presents a heat demand mapping methodology and the use of its output for the district heating network expansion analysis. The result are showing that more than 59% of the heat demand could be covered by the district heating in the city of Velika Gorica, which is two times more than the present share. The most important reason of the district heating's unfulfilled potential is already existing natural gas infrastructure.

  17. District heating rehabilitation project in Kaerdla on Hiiumaa, Estonia. Final report

    International Nuclear Information System (INIS)

    1998-03-01

    The main objective of the project has been to assist Kaerdla Municipality with the rehabilitation of their district heating system with Danish technology, and thereby support and make it possible for the Municipality of Kaerdla to develop the district heating sector in Kaerdla and thereby also to reduce emissions of harmful gases to the environment, as well as making a much more rational and energy efficient system. The project would further on demonstrate the use of pre-insulated pipes, which are fully sealed against penetration of water as well as demonstrate the use of compact units as substations including weather compensation control systems for regulation of heat and hot tap water supply for the district heating consumers. Besides the project gives significantly decreases in energy consumption's and in the pollution from the production of energy, the objective of the project was also to put great stress on providing technical assistance to Kaerdla DH company, in order to make them capable in operation and maintenance of the new district heating system, and also to train the local operational staff in operation of the complete district heating system. The project will have a high demonstration value towards other towns in Estonia with similar problems and configurations of their heating systems. (EG)

  18. District heating rehabilitation project in Kaerdla on Hiiumaa, Estonia. Final report

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1998-03-01

    The main objective of the project has been to assist Kaerdla Municipality with the rehabilitation of their district heating system with Danish technology, and thereby support and make it possible for the Municipality of Kaerdla to develop the district heating sector in Kaerdla and thereby also to reduce emissions of harmful gases to the environment, as well as making a much more rational and energy efficient system. The project would further on demonstrate the use of pre-insulated pipes, which are fully sealed against penetration of water as well as demonstrate the use of compact units as substations including weather compensation control systems for regulation of heat and hot tap water supply for the district heating consumers. Besides the project gives significantly decreases in energy consumption`s and in the pollution from the production of energy, the objective of the project was also to put great stress on providing technical assistance to Kaerdla DH company, in order to make them capable in operation and maintenance of the new district heating system, and also to train the local operational staff in operation of the complete district heating system. The project will have a high demonstration value towards other towns in Estonia with similar problems and configurations of their heating systems. (EG)

  19. Experimental Study of a Novel Direct-Expansion Variable Frequency Finned Solar/Air-Assisted Heat Pump Water Heater

    Directory of Open Access Journals (Sweden)

    Jing Qin

    2018-01-01

    Full Text Available A novel direct expansion variable frequency finned solar/air-assisted heat pump water heater was fabricated and tested in the enthalpy difference lab with a solar simulator. A solar/air source evaporator-collector with an automatic lifting glass cover plate was installed on the system. The system could be operated in three modes, namely, air, solar, and dual modes. The effects of the ambient temperature, solar irradiation, compressor frequency, and operating mode on the performance of this system were studied in this paper. The experimental results show that the ambient temperature, solar irradiation, and operating mode almost have no effect on the energy consumption of the compressor. When the ambient temperature and the solar irradiation were increased, the COP was found to increase with decreasing heating time. Also, when the compressor frequency was increased, an increase in the energy consumption of the compressor and the heat gain of the evaporator were noted with a decrease in the heating time.

  20. Power/heat production from biomass in Finland - Two modern Finnish examples

    International Nuclear Information System (INIS)

    Aeijaelae, M.

    1997-01-01

    According to this conference paper, Finland is a leading country in the utilization of biomass fuels for power and heat production. One reason is that peat and wood are the only indigenous fuels available in Finland. Other reasons are the strong forest industry and the widely adopted combined heat and power (CHP) production. CHP production is typical of process industry and municipal district heating. The most common boiler type in modern CHP plants is the fluidized bed type. District heating is the cheapest heating in municipalities with a few thousand inhabitants. Electric heating dominates in sparsely populated regions. CHP becomes attractive for populations of more than ten thousand. Two examples are described: (1) Rauhalahti Power Plant produces 140 MW of district heat, 65 MW of industrial steam and 87 MW of electricity. (2) Kuusamo Power Plant produces 6.1 MW electric energy and 17.6 MW district heat; its unique feature is the utilization of the bed mixing dryer for drying of the fuel prior to combustion, this dryer being the first of its kind in the world. 1 figure

  1. Optimization of solar assisted heat pump systems via a simple analytic approach

    Energy Technology Data Exchange (ETDEWEB)

    Andrews, J W

    1980-01-01

    An analytic method for calculating the optimum operating temperature of the collector/storage subsystem in a solar assisted heat pump is presented. A tradeoff exists between rising heat pump coefficient of performance and falling collector efficiency as this temperature is increased, resulting in an optimum temperature whose value increases with increasing efficiency of the auxiliary energy source. Electric resistance is shown to be a poor backup to such systems. A number of options for thermally coupling the system to the ground are analyzed and compared.

  2. Thermal performance analysis of a direct-expansion solar-assisted heat pump water heater

    International Nuclear Information System (INIS)

    Kong, X.Q.; Zhang, D.; Li, Y.; Yang, Q.M.

    2011-01-01

    A direct-expansion solar-assisted heat pump water heater (DX-SAHPWH) is described, which can supply hot water for domestic use during the whole year. The system mainly employs a bare flat-plate collector/evaporator with a surface area of 4.2 m 2 , an electrical rotary-type hermetic compressor, a hot water tank with the volume of 150 L and a thermostatic expansion valve. R-22 is used as working fluid in the system. A simulation model based on lumped and distributed parameter approach is developed to predict the thermal performance of the system. Given the structure parameters, meteorological parameters, time step and final water temperature, the numerical model can output operational parameters, such as heat capacity, system COP and collector efficiency. Comparisons between the simulation results and the experimental measurements show that the model is able to give satisfactory predictions. The effect of various parameters, including solar radiation, ambient temperature, wind speed and compressor speed, has been analyzed on the thermal performance of the system. -- Highlights: ► A direct-expansion solar-assisted heat pump water heater (DX-SAHPWH) is described. ► A simulation model based on lumped and distributed parameter approach is developed to predict the thermal performance of the system. ► The numerical model can output operational parameters, such as heat capacity, system COP and collector efficiency. ► Comparisons between the simulation results and the experimental measurements show that the model is able to give satisfactory predictions. ► The effect of various parameters has been analyzed on the thermal performance of the system.

  3. Development and validation of a detailed TRNSYS-Matlab model for large solar collector fields for district heating applications

    DEFF Research Database (Denmark)

    Bava, Federico; Furbo, Simon

    2017-01-01

    This study describes the development of a detailed TRNSYS-Matlab model to simulate the behavior of a large solar collector field for district heating application. The model includes and investigates aspects which are not always considered by simpler models, such as flow distribution...... programming and computing time. Thermal capacity was worth being considered only for the bulkier components, such as the longer distribution and transmission pipes. The actual control strategy, which regulates the flow rates in the solar heating plant, was accurately reproduced in the model, as proved...... in the different rows, effect of the flow regime on the collector efficiency, thermal capacity of the components and effect of shadows from row to row. The model was compared with measurements from a solar collector field and the impact of each aspect was evaluated. A good agreement between model and measurements...

  4. System performance and economic analysis of solar-assisted cooling/heating system

    KAUST Repository

    Huang, B.J.

    2011-11-01

    The long-term system simulation and economic analysis of solar-assisted cooling/heating system (SACH-2) was carried out in order to find an economical design. The solar heat driven ejector cooling system (ECS) is used to provide part of the cooling load to reduce the energy consumption of the air conditioner installed as the base-load cooler. A standard SACH-2 system for cooling load 3.5. kW (1. RT) and daily cooling time 10 h is used for case study. The cooling performance is assumed only in summer seasons from May to October. In winter season from November to April, only heat is supplied. Two installation locations (Taipei and Tainan) were examined.It was found from the cooling performance simulation that in order to save 50% energy of the air conditioner, the required solar collector area is 40m2 in Taipei and 31m2 in Tainan, for COPj=0.2. If the solar collector area is designed as 20m2, the solar ejector cooling system will supply about 17-26% cooling load in Taipei in summer season and about 21-27% cooling load in Tainan. Simulation for long-term performance including cooling in summer (May-October) and hot water supply in winter (November-April) was carried out to determine the monthly-average energy savings. The corresponding daily hot water supply (with 40°C temperature rise of water) for 20m2 solar collector area is 616-858L/day in Tainan and 304-533L/day in Taipei.The economic analysis shows that the payback time of SACH-2 decreases with increasing cooling capacity. The payback time is 4.8. years in Tainan and 6.2. years in Taipei when the cooling capacity >10. RT. If the ECS is treated as an additional device used as a protective equipment to avoid overheating of solar collectors and to convert the excess solar heat in summer into cooling to reduce the energy consumption of air conditioner, the payback time is less than 3 years for cooling capacity larger than 3. RT. © 2011 Elsevier Ltd.

  5. 太阳能辅助地源热泵供暖实验研究%Experimental study of a solar assisted ground source heat pump for heating

    Institute of Scientific and Technical Information of China (English)

    赵忠超; 丰威仙; 巩学梅; 米浩君; 成华; 云龙

    2014-01-01

    An experimental study is performed to determine the performance of the solar assisted ground source heat pump(SAGSHP)by using a solar-ground source heat pump hybrid system in the city of Ningbo. The result shows that comparing with the ground source heat pump(GSHP),when the ratio of solar energy to the whole en-ergy is 41. 9% ,the coefficient of performance( COP)of the heat pump and system can improve 15. 1% and 7. 7% respectively. Therefore,the solar assisted ground source heat pump has a significant performance advan-tage according to the experimental result.%选取宁波某公用建筑的太阳能-地源热泵复合系统为实验系统,对太阳能辅助地源热泵( solar assisted ground source heat pump,SAGSHP)供暖进行了实验研究.研究结果表明:与单一的地源热泵(ground source heat pump,GSHP)相比,当太阳能承担41.9%负荷时,热泵机组和整个系统的能效比(coefficient of performance,COP)分别提高了15.1%和7.7%, SAGSHP 供暖运行模式具有明显的性能优势.

  6. Woodfuel procurement strategies of district heating plants

    International Nuclear Information System (INIS)

    Roos, A.; Bohlin, F.; Hektor, B.; Hillring, B.

    2003-01-01

    Woodfuel use in the Swedish district heating sector increased significantly from 1985 to 1999. This study analysed strategies and considerations concerning woodfuel procurement in district heating plants. Priorities and concerns in the industry involved an increased woodfuel share, ambitions to create an environmental image, cost minimisation, awareness about the role of energy policies for fuel choice, improvement of woodfuel quality and the ambition to maintain a competitive woodfuel market with several suppliers. Factor analysis yielded five dimensions in the woodfuel procurement strategies among the district heating companies: (1) increased woodfuel use; (2) import; (3) spot market woodfuel purchases; (4) focus on refined woodfuels; and (5) using price only when deciding whether to use woodfuels or other fuels. Five clusters were defined along the three strategy dimensions (1)-(3). The clusters differed concerning size, experiences from the introduction of woodfuels, perceptions about woodfuels and strategies employed to date. This paper describes different strategies that the district heating companies apply on the woodfuel market. The conclusion is that policies should consider this diversity in procurement strategies, mitigate their negative side-effects and assist to make them cost-effective. (author)

  7. Air source absorption heat pump in district heating: Applicability analysis and improvement options

    International Nuclear Information System (INIS)

    Wu, Wei; Shi, Wenxing; Li, Xianting; Wang, Baolong

    2015-01-01

    Highlights: • Applicability of air source absorption heat pump (ASAHP) district heating is studied. • Return temperature and energy saving rate (ESR) in various conditions are optimized. • ASAHP is more suitable for shorter distance or lower temperature district heating. • Two options can reduce the primary return temperature and improve the applicability. • The maximum ESR is improved from 13.6% to 20.4–25.6% by compression-assisted ASAHP. - Abstract: The low-temperature district heating system based on the air source absorption heat pump (ASAHP) was assessed to have great energy saving potential. However, this system may require smaller temperature drop leading to higher pump consumption for long-distance distribution. Therefore, the applicability of ASAHP-based district heating system is analyzed for different primary return temperatures, pipeline distances, pipeline resistances, supplied water temperatures, application regions, and working fluids. The energy saving rate (ESR) under different conditions are calculated, considering both the ASAHP efficiency and the distribution consumption. Results show that ASAHP system is more suitable for short-distance district heating, while for longer-distance heating, lower supplied hot water temperature is preferred. In addition, the advantages of NH 3 /H 2 O are inferior to those of NH 3 /LiNO 3 , and the advantages for warmer regions and lower pipeline resistance are more obvious. The primary return temperatures are optimized to obtain maximum ESRs, after which the suitable distances under different acceptable ESRs are summarized. To improve the applicability of ASAHP, the integration of cascaded heat exchanger (CHX) and compression-assisted ASAHP (CASAHP) are proposed, which can reduce the primary return temperature. The integration of CHX can effectively improve the applicability of ASAHP under higher supplied water temperatures. As for the utilization of CASAHP, higher compression ratio (CR) is better in

  8. Potential Evaluation of Solar Heat Assisted Desiccant Hybrid Air Conditioning System

    Science.gov (United States)

    Tran, Thien Nha; Hamamoto, Yoshinori; Akisawa, Atsushi; Kashiwagi, Takao

    The solar thermal driven desiccant dehumidification-absorption cooling hybrid system has superior advantage in hot-humid climate regions. The reasonable air processing of desiccant hybrid air conditioning system and the utility of clean and free energy make the system environment friendly and energy efficient. The study investigates the performance of the desiccant dehumidification air conditioning systems with solar thermal assistant. The investigation is performed for three cases which are combinations of solar thermal and absorption cooling systems with different heat supply temperature levels. Two solar thermal systems are used in the study: the flat plate collector (FPC) and the vacuum tube with compound parabolic concentrator (CPC). The single-effect and high energy efficient double-, triple-effect LiBr-water absorption cooling cycles are considered for cooling systems. COP of desiccant hybrid air conditioning systems are determined. The evaluation of these systems is subsequently performed. The single effect absorption cooling cycle combined with the flat plate collector solar system is found to be the most energy efficient air conditioning system.

  9. Analysis of a Hybrid PV/Thermal Solar-Assisted Heat Pump System for Sports Center Water Heating Application

    Directory of Open Access Journals (Sweden)

    Y. Bai

    2012-01-01

    Full Text Available The application of solar energy provides an alternative way to replace the primary source of energy, especially for large-scale installations. Heat pump technology is also an effective means to reduce the consumption of fossil fuels. This paper presents a practical case study of combined hybrid PV/T solar assisted heat pump (SAHP system for sports center hot water production. The initial design procedure was first presented. The entire system was then modeled with the TRNSYS 16 computation environment and the energy performance was evaluated based on year round simulation results. The results show that the system COP can reach 4.1 under the subtropical climate of Hong Kong, and as compared to the conventional heating system, a high fractional factor of energy saving at 67% can be obtained. The energy performances of the same system under different climatic conditions, that include three other cities in France, were analyzed and compared. Economic implications were also considered in this study.

  10. Heat Pumps With Direct Expansion Solar Collectors

    Science.gov (United States)

    Ito, Sadasuke

    In this paper, the studies of heat pump systems using solar collectors as the evaporators, which have been done so far by reserchers, are reviwed. Usually, a solar collector without any cover is preferable to one with ac over because of the necessity of absorbing heat from the ambient air when the intensity of the solar energy on the collector is not enough. The performance of the collector depends on its area and the intensity of the convective heat transfer on the surface. Fins are fixed on the backside of the collector-surface or on the tube in which the refrigerant flows in order to increase the convective heat transfer. For the purpose of using a heat pump efficiently throughout year, a compressor with variable capacity is applied. The solar assisted heat pump can be used for air conditioning at night during the summer. Only a few groups of people have studied cooling by using solar assisted heat pump systems. In Japan, a kind of system for hot water supply has been produced commercially in a company and a kind of system for air conditioning has been installed in buildings commercially by another company.

  11. Impact of different national biomass policies on investment costs of biomass district heating plants. Final report

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2000-04-01

    The BIO-COST project - co-ordinated by E.V.A. - was funded by the European Commission's THERMIE Type B Programme. The objective of BIO-COST was to analyse the impact of national biomass policies on the investment costs of biomass district heating (DH) plants. The European comparison should help identifying measures to reduce investment costs for biomass DH plants and/or components down to a 'best practice' level. The investigation is based on the comparison of 20 biomass DH plants by country, with Denmark and Sweden having mainly high energy taxes as driver, while Austria and France rely mainly on subsidy systems. The results of BIO-COST show, that governmental policies can have a big impact especially on grid and buildings costs, effecting of course the overall costs of the plant enormously. Emission standards have their effects especially on the costs for technical equipment, however, this fact was not reflected in the BIO-COST data. The results do not show a clear advantage of either the energy tax approach or the subsidy approach: The French subsidy approach leads to fairly low cost levels compared to the Danish tax approach, while the Swedish tax approach seems to yield the lowest cost level. On the other hand the Austrian subsidy approach seems to intercrease investment costs. In principle both the tax as the subsidy approach can lead to the same effect: a project is calculated in such a way, that it just meets economic breakeven. This is typically the case when the project is not carried out by a private enterprise but by an operator aiming at enhanced public welfare (e.g. co-operative, municipality). In this case a subsidy model might yield more possibilities to encourage an economically efficient development, than a tax. Instead of giving subsidies as a fixed percentage of investments they could be adjusted to the actual needs of the project as proven by a standardised calculation. Of course this can create the incentive to expect higher

  12. Flexible use of electricity in heat-only district heating plants

    Directory of Open Access Journals (Sweden)

    Erik Trømborg

    2017-01-01

    Full Text Available European energy systems are in a period of significant transition, with the increasing shares of variable renewable energy (VRE and less flexible fossil-based generation units as predominant factors. The supply-side changes are expected to cause large short-term electricity price volatility. More frequent periods of low electricity prices may mean that electric use in flexible heating systems will become more profitable, and such flexible heating systems may, in turn, improve the integration of increasing shares of VRE. The objective of this study is to analyze the likely future of Nordic electricity price levels and variations and how the expected prices might affect the use of electricity and thermal storage in heat-only district heating plants. We apply the North European energy market model Balmorel to provide scenarios for future hourly electricity prices in years with normal, high, and low inflow levels to the hydro power system. The simulation tool energyPRO is subsequently applied to quantify how these electricity price scenarios affect the hourly use of thermal storage and individual boilers in heat-only district heating plants located in Norway. The two studied example plants use wood chips or heat pump as base load representing common technologies for district heating in Norway. The Balmorel results show that annual differences in inflow is still a decisive factor for Norwegian and Nordic electricity prices in year 2030 and that short-term (daily price variability is expected to increase. In the plant-level simulations, we find that tank storage, which is currently installed in only a few district heating plants in Norway, is a profitable flexibility option that will significantly reduce the use of fossil peak load in both biomass and heat-pump-based systems. Installation of an electric boiler in addition to tank storage is profitable in the heat pump system due to the limited capacity of the heat pump. Electricity will hence, to a

  13. Exploitation of humid air latent heat by means of solar assisted heat pumps operating below the dew point

    International Nuclear Information System (INIS)

    Scarpa, Federico; Tagliafico, Luca A.

    2016-01-01

    Highlights: • The opportunity of humid air latent heat exploitation by DX-SAHP is investigated. • A set of experimental tests confirms this opportunity and quantifies it as relevant. • A parametric analysis is performed, via simulation, to deepen the subject. • The energy gain is relevant during both night and daytime. - Abstract: Nowadays, the exploitation of environmental exergy resources for heating purposes (solar energy, convection heat transfer from ambient air, moist air humidity condensation) by means of properly designed heat pump systems is a possible opportunity. In particular, the use of direct expansion solar assisted heat pumps (DX-SAHP) is investigated in this study, when a bare external plate (the solar collector) is kept at temperatures lower than the dew point temperature of ambient air, so that condensation takes place on it. The potential of this technology is settled and an instrumented prototype of a small DX-SAHP system is used to verify the actual performance of the system, in terms of specific thermal energy delivered to the user, efficiency and regulation capabilities. Results clearly show that the contribution of the condensation is significant (20%–30% of the total harvested energy) overnight or in cloudy days with very low or no solar irradiation, and must be taken into account in a system model devoted to describe the DX-SAHP behavior. During daytime, the percentage gain decreases but is still consistent. By investigating along these lines, the heat due to condensation harvested by the collector is found to be a function of the dew-point temperature alone.

  14. Solar district heating and seasonal heat storage - state of the art; Solare Nahwaerme und Saisonale Waermespeicherung - Stand der Technik

    Energy Technology Data Exchange (ETDEWEB)

    Pfeil, M.; Hahne, E. [Zentrum fuer Sonnenenergie- und Wasserstoff-Forschung Baden-Wuerttemberg (ZSW), Stuttgart (Germany). Geschaeftsbereich Solarthermische Energietechnik; Lottner, V. [BEO Biologie, Energie Oekologie, Juelich (Germany); Schulz, M. [Stuttgart Univ. (Germany). Inst. fuer Thermodynamik und Waermetechnik

    1998-02-01

    Solar energy technology becomes more and more important for space and water heating of residential buildings. Compared to small systems for single-family houses, the specific investment cost of big solar plants is lower and a higher contribution of solar energy can be achieved. In central solar heating plants with seasonal storage (CSHPSS), more than 50% of the total heat demand of residential areas can be covered by solar energy. The first pilot plants for CSHPSS are operating in Germany since 1996. The first results of the accompanying monitoring program show good agreement between calculated and actual solar contribution. (orig.) [Deutsch] Die Nutzung solarer Niedertemperaturwaerme zur Brauchwassererwaermung und zur Beheizung von Wohngebaeuden erfaehrt in Deutschland ein immer groesseres Interesse. Solare Grossanlagen haben gegenueber solaren Kleinanlagen den Vorteil, dass mit geringeren Investitions- und Waermekosten groessere Anlagenertraege erzielt werden koennen. In Verbindung mit saisonaler Waermespeicherung erreichen solare Grossanlagen Deckungsanteile von 50% und darueber am Gesamtwaermebedarf von Wohnsiedlungen. Die ersten Pilotanlagen zur solaren Nahwaerme mit saisonalem Waermespeicher gingen 1996 in Betrieb und werden derzeit detailliert vermessen. Erste Ergebnisse zeigen, dass die vorausberechneten Werte fuer den Jahresenergieertrag erreicht werden koennen. (orig.)

  15. Techno-economic analysis of a local district heating plant under fuel flexibility and performance

    DEFF Research Database (Denmark)

    Rudra, Souman; Rosendahl, Lasse

    2017-01-01

    are calculated using the same procedure according to the use of various local renewable fuels known as “biogas option,” “solar option,” “heat pump option,” and “imported heat option.” A comparison has been made between the reference option and other options. The greatest reduction in heat cost is obtained from......, an investigation has been made to reduce the use of fossil fuels for district heating system and make use of the local renewable resources (biogas, solar, and heat pump) for district heating purposes. In this article, the techno-economic assessment is achieved through the development of a suite of models...... the biogas option by replacing a new engine, where 66 % of the current fuel is substituted with biogas....

  16. Performance of evaporator-collector and air collector in solar assisted heat pump dryer

    International Nuclear Information System (INIS)

    Hawlader, M.N.A.; Rahman, S.M.A.; Jahangeer, K.A.

    2008-01-01

    A solar assisted heat pump dryer has been designed, fabricated and tested. This paper presents the performance of the evaporator-collector and the air collector when operated under the same meteorological conditions. ASHRAE standard procedure for collector testing has been followed. The evaporator-collector of the heat pump is acting directly as the solar collector, and the temperature of the refrigerant at the inlet to the evaporator-collector always remained below the ambient temperature. Because of the rejection of sensible and latent heats of air at the dehumidifier, the temperature at the inlet to the air collector is lower than that of the ambient air. Hence, the thermal efficiency of the air collector also increases due to a reduction of losses from the collector. The efficiencies of the evaporator-collector and the air collector were found to vary between 0.8-0.86 and 0.7-0.75, respectively, when operated under the meteorological conditions of Singapore

  17. The technical use of solar energy

    International Nuclear Information System (INIS)

    Hahne, E.

    1993-01-01

    For all considerations on energy, information on energy-quantity and energy-value is necessary. Such information is presented for Germany as an example for an industrialized country. The application of solar heat for an Institute building is presented for a pilot project at the University Stuttgart. With unglazed solar collectors, a flooded pebble-bed store and a heat pump, about 60% of the Institute's heat demand can be supplied by solar energy. With the experience gained from this project, large district heating systems are designed for two different locations in Germany under differing conditions. For solar assisted house heating and domestic hot water, heat costs are obtained which are about twice the present heat cost in Germany. If solar energy assists domestic hot water production and house heating, costs can be achieved which are below present conventional heat cost. In addition, it will also reduce air pollution. (author). 9 figs., 6 tabs

  18. Renewable energy options in the Hradec Kralove and Pardubice districts, Eastern Bohemia

    International Nuclear Information System (INIS)

    Boye Olesen, G.; Beranovski, J.

    1993-06-01

    A detailed evaluation of a number of potential renewable energy sources in the districts of Hradec Kralove and Pardubice in Northern Bohemia ( Czech Republic). The possible uses of solar energy in relation to solar water heating and district heating were analyzed. The use of wind power by connecting wind turbines to the grid was not considered to be cost effective owing to low wind resources in this area (mean wind speed at 10m height is below 3 m/s). Possibilities for producing methane were investigated in relation to manures, sewage sludges and wet organic household and industrial wastes. Biomass fuel resources were examined from the point of view of straw, wood chips and biomass crops. Hydroelectric plants already exist and there are some resources of geothermal heat at a lower temperature. Estimates are given of renewable energy potentials dealt with, showing current available resources and potential resources if 50% of household wastes are sorted in organic and inorganic fractions, if 20% of sugar wastes is used for producing methane, if use of wood chips significantly increases and if waste water plants are contructed in Hradec Kralove and Novy Bydzov. These changes could take place before the year 2000. Animal manures, straw and wood resources cover 80% of renewable energy resources potential, excluding solar energy and biomass crops. The compiled data also gives information on estimated investment and running costs. (AB)

  19. Design of a Heat Pump Assisted Solar Thermal System

    OpenAIRE

    Krockenberger, Kyle G.; DeGrove, John M.; Hutzel, William J.; Foreman, J. Christopher

    2014-01-01

    This paper outlines the design of an active solar thermal loop system that will be integrated with an air source heat pump hot water heater to provide highly efficient heating of a water/propylene glycol mixture. This system design uses solar energy when available, but reverts to the heat pump at night or during cloudy weather. This new design will be used for hydronic heating in the Applied Energy Laboratory, a teaching laboratory at Purdue University, but it is more generally applicable for...

  20. VII international district heating conference

    International Nuclear Information System (INIS)

    1988-01-01

    The proceedings of the 7th International District Heating Conference contain the full texts of the 89 presented papers of which 11 fall under the INIS Subject Scope. The conference met in seven sessions and dealt with the following problem areas: design and optimization of systems of district heating, integration of the power system and the district heating systems, cooperation of nuclear and fossil burning sources in district heating systems, the use of specific nuclear power plants for heating purposes, questions of the control of systems of district heating, the development of components of heating networks, the reliability and design of heat supply pipes. (Z.M.)

  1. Study on the System Design of a Solar Assisted Ground Heat Pump System Using Dynamic Simulation

    Directory of Open Access Journals (Sweden)

    Min Gyung Yu

    2016-04-01

    Full Text Available Recently, the use of hybrid systems using multiple heat sources in buildings to ensure a stable energy supply and improve the system performance has gained attention. Among them, a heat pump system using both solar and ground heat was developed and various system configurations have been introduced. However, establishing a suitable design method for the solar-assisted ground heat pump (SAGHP system including a thermal storage tank is complicated and there are few quantitative studies on the detailed system configurations. Therefore, this study developed three SAGHP system design methods considering the design factors focused on the thermal storage tank. Using dynamic energy simulation code (TRNSYS 17, individual performance analysis models were developed and long-term quantitative analysis was carried out to suggest optimum design and operation methods. As a result, it was found that SYSTEM 2 which is a hybrid system with heat storage tank for only a solar system showed the highest average heat source temperature of 14.81 °C, which is about 11 °C higher than minimum temperature in SYSTEM 3. Furthermore, the best coefficient of performance (COP values of heat pump and system were 5.23 and 4.32 in SYSYEM 2, using high and stable solar heat from a thermal storage tank. Moreover, this paper considered five different geographical and climatic locations and the SAGHP system worked efficiently in having high solar radiation and cool climate zones and the system COP was 4.51 in the case of Winnipeg (Canada where the highest heating demand is required.

  2. Potential for solar space heating in Scotland

    Energy Technology Data Exchange (ETDEWEB)

    Macgregor, A W.K.

    1980-07-01

    This paper investigates the relative effectiveness of passive-type solar-assisted space heating systems at various latitudes within the British Isles. A comparison is made of the useful solar gain of the same system linked to the same house at four different locations. Month-by-month energy balances indicate that the annual useful solar contribution at the highest latitude (Lerwick, 60 deg N) is about 35% higher than at the lowest latitude (Kew, 53 deg N). The main reason for this difference is the higher heating loads in the north, particularly outside the winter months. The estimated available irradiation on south-facing vertical surfaces was almost the same at all four locations. Previous work in the UK indicates that, contrary to the conclusions in this paper, more southerly latitudes were the most favorable for solar space heating. The reasons for the disparity are discussed. It is recommended that research and development of passive solar-assisted space heating systems should be most vigorously pursued in the more northerly latitudes of the British Isles, where both the potential benefit and the need are greatest.

  3. Particulate emissions from biomass combustion in small district heating plants; Partikelemissioner fraan biobraensleeldade mindre fjaerrvaermecentraler

    Energy Technology Data Exchange (ETDEWEB)

    Persson, Henrik; Johansson, Linda; Tullin, Claes; Oesterberg, Stefan; Johansson, Mathias [Swedish National Testing and Research Inst., Boraas (Sweden); Leckner, Bo [Chalmers Univ. of Technology, Goeteborg (Sweden). Energy Conversion

    2001-12-01

    In recent years, negative health effects associated with increased levels of PM{sub 10} and PM{sub 2.5} (particles less then 10 and 2.5 {mu}m, respectively) in the ambient air have been highlighted. The development towards a sustainable society will lead to an increased use of biomass in Sweden. Conversion from oil to biomass can lead to increased local levels of particulate matter. In smaller district heating plants (up to a few MW), the dust reduction often is restricted to the use of cyclones/multicyclones having limited separation efficiency for submicron particles (particles less than 1 {mu}m). The emissions are often in the range 100 Mg/nm{sup 3} or higher but very few data regarding particle size distributions from district heating plants have been reported in the literature. In addition to the particle size, a number of other properties might be important for the health effects but the knowledge in this area is limited. It is therefore important to characterise the particles in detail regarding physical and chemical qualities. The objective with the present investigation is to measure and characterise the particulate emissions from two biomass based smaller district heating centrals for different fuel qualities (pellets, briquettes, forest residues and wood chips) and operating parameters such as load and excess air. In addition to analyses of dust and particulates, extensive measurements of the flue composition have been performed. Measurements were performed downstream the multicyclones. The dust emissions were found to be in the range 20 to 120 mg/MJ supplied fuel depending on operating condition and fuel quality. At normal operation, the dust emissions were about 35 to 40 mg/MJ supplied fuel. The particle size distributions were measured using an ELPI (Electric Low Pressure Impactor). The number size distributions were found to be dominated by submicron particles with maxima at diameters between 0. 1 and 0.3 gm. Additional measurements indicated that

  4. Biomass District Energy Trigeneration Systems: Emissions Reduction and Financial Impact

    International Nuclear Information System (INIS)

    Rentizelas, A.; Tolis, A.; Tatsiopoulos, I.

    2009-01-01

    Biomass cogeneration is widely used for district heating applications in central and northern Europe. Biomass trigeneration on the other hand, constitutes an innovative renewable energy application. In this work, an approved United Nations Framework Convention on Climate Change baseline methodology has been extended to allow the examination of biomass trigeneration applications. The methodology is applied to a case study in Greece to investigate various environmental and financial aspects of this type of applications. The results suggest that trigeneration may lead to significant emissions reduction compared to using fossil fuels or even biomass cogeneration and electricity generation. The emissions reduction achieved may be materialized into a considerable revenue stream for the project, if traded through a trading mechanism such as the European Union Greenhouse Gas Emission Trading Scheme. A sensitivity analysis has been performed to compensate for the high volatility of the emission allowances' value and the immaturity of the EU Trading Scheme, which prevent a reliable estimation of the related revenue. The work concludes that emission allowances trading may develop into one of the major revenue streams of biomass trigeneration projects, significantly increasing their financial yield and attractiveness. The impact on the yield is significant even for low future values of emission allowances and could become the main income revenue source of such projects, if emission allowances increase their value substantially. The application of trigeneration for district energy proves to lead to increased environmental and financial benefits compared to the cogeneration or electricity generation cases

  5. Industrial excess heat for district heating in Denmark

    International Nuclear Information System (INIS)

    Bühler, Fabian; Petrović, Stefan; Karlsson, Kenneth; Elmegaard, Brian

    2017-01-01

    Highlights: •Method for utilisation potential of industrial excess heat for district heating. •Industrial excess heat from thermal processes is quantified at single production units. •Linking of industrial excess heat sources and district heating demands done in GIS. •Excess heat recovery using direct heat transfer and heat pumps. •5.1% of the Danish district heating demand could be supplied by industrial excess heat. -- Abstract: Excess heat is available from various sources and its utilisation could reduce the primary energy use. The accessibility of this heat is however dependent amongst others on the source and sink temperature, amount and potential users in its vicinity. In this work a new method is developed which analyses excess heat sources from the industrial sector and how they could be used for district heating. This method first allocates excess heat to single production units by introducing and validating a new approach. Spatial analysis of the heat sources and consumers are then performed to evaluate the potential for using them for district heating. In this way the theoretical potential of using the excess heat for covering the heating demand of buildings is determined. Through the use of industry specific temperature profiles the heat usable directly or via heat pumps is further found. A sensitivity analysis investigates the impact of future energy efficiency measures in the industry, buildings and the district heating grid on the national potential. The results show that for the case study of Denmark, 1.36 TWh of district heat could be provided annually with industrial excess heat from thermal processes which equals 5.1% of the current demand. More than half of this heat was found to be usable directly, without the need for a heat pump.

  6. Optimization of a local district heating plant under fuel flexibility and performance

    DEFF Research Database (Denmark)

    Rudra, Souman; Rosendahl, Lasse; From, Niels

    2011-01-01

    are calculated for various local fuels in energyPRO. A comparison has been made between the reference model and the basis for individual solutions. The greatest reduction in heat price is obtained by replacing one engine with a new biogas where heat production is divided by 66% of biogas, 13% natural gas engines......, an investigation has been made to reduce the use of fossil fuels for district heating system and make use of the local renewable resources (Biogas, Solar and Geothermal) for district heating purpose. In this article, the techno-economic assessment is achieved through the development of a suite of models...

  7. Heat demand profiles of energy conservation measures in buildings and their impact on a district heating system

    International Nuclear Information System (INIS)

    Lundström, Lukas; Wallin, Fredrik

    2016-01-01

    Highlights: • Energy savings impact on an low CO 2 emitting district heating system. • Heat profiles of eight building energy conservation measures. • Exhaust air heat pump, heat recovery ventilation, electricity savings etc. • Heat load weather normalisation with segmented multivariable linear regression. - Abstract: This study highlights the forthcoming problem with diminishing environmental benefits from heat demand reducing energy conservation measures (ECM) of buildings within district heating systems (DHS), as the supply side is becoming “greener” and more primary energy efficient. In this study heat demand profiles and annual electricity-to-heat factors of ECMs in buildings are computed and their impact on system efficiency and greenhouse gas emissions of a Swedish biomass fuelled and combined heat and power utilising DHS are assessed. A weather normalising method for the DHS heat load is developed, combining segmented multivariable linear regressions with typical meteorological year weather data to enable the DHS model and the buildings model to work under the same weather conditions. Improving the buildings’ envelope insulation level and thereby levelling out the DHS heat load curve reduces greenhouse gas emissions and improves primary energy efficiency. Reducing household electricity use proves to be highly beneficial, partly because it increases heat demand, allowing for more cogeneration of electricity. However the other ECMs considered may cause increased greenhouse gas emissions, mainly because of their adverse impact on the cogeneration of electricity. If biomass fuels are considered as residuals, and thus assigned low primary energy factors, primary energy efficiency decreases when implementing ECMs that lower heat demand.

  8. District heating in Italy

    International Nuclear Information System (INIS)

    Sacchi, E.

    1998-01-01

    The legislative act establishing the electric monopoly virtually shut out the district heating associated with electricity cogeneration, while other laws, issued to counteract the effects of oil shocks, allowed municipal utilities to do so. Thus, district heating has experienced some development, though well below its possibilities. The article analyses the reasons for this lagging, reports district heating data and projects its forecasts against the Kyoto Protocol objectives [it

  9. Industrial excess heat for district heating in Denmark

    DEFF Research Database (Denmark)

    Bühler, Fabian; Petrovic, Stefan; Karlsson, Kenneth Bernard

    2017-01-01

    analyses excess heat sources from the industrial sector and how they could be used for district heating. This method first allocates excess heat to single production units by introducing and validating a new approach. Spatial analysis of the heat sources and consumers are then performed to evaluate...... the potential for using them for district heating. In this way the theoretical potential of using the excess heat for covering the heating demand of buildings is determined. Through the use of industry specific temperature profiles the heat usable directly or via heat pumps is further found. A sensitivity...... analysis investigates the impact of future energy efficiency measures in the industry, buildings and the district heating grid on the national potential. The results show that for the case study of Denmark, 1.36 TWh of district heat could be provided annually with industrial excess heat from thermal...

  10. Natural convection solar dryer with biomass back-up heater

    Energy Technology Data Exchange (ETDEWEB)

    Bena, B.; Fuller, R.J. [University of Melbourne (Australia). Faculty of Engineering

    2002-07-01

    A direct-type natural convection solar dryer and a simple biomass burner have been combined to demonstrate a drying technology suitable for small-scale processors of dried fruits and vegetables in non-electrified areas of developing countries. From a series of evaluation trials of the system, the capacity of the dryer was found to be 20-22kg of fresh pineapple arranged in a single layer of 0.01-m-thick slices. The overall drying efficiency of the unit was calculated to be {approx} 9%. During the same trial, the drying efficiency of the solar component alone was found to be 22%. Other trials estimated the efficiency of the burner in producing useful heat for drying to be 27%. Key features of the biomass burner were found to be the addition of thermal mass on the upper surface, an internal baffle plate to lengthen the exhaust gas exit path and a variable air inlet valve. Further modifications to further improve the performance of both the solar and biomass components of the dryer are suggested. (author)

  11. Preliminary business plan: Plzen district heating system upgrade

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1996-06-01

    The district heating system of the City of Plzen, Czech Republic, needs to have physical upgrades to replace aging equipment and to comply with upcoming environmental regulations. Also, its ownership and management are being changed as a result of privatization. As majority owner, the City has the primary goal of ensuring that the heating needs of its customers are met as reliably and cost-effectively as possible. This preliminary business plan is part of the detailed analysis (5 reports in all) done to assist the City in deciding the issues. Preparation included investigation of ownership, management, and technology alternatives; estimation of market value of assets and investment requirements; and forecasting of future cash flow. The district heating system consists of the Central Plzen cogeneration plant, two interconnected heating plants [one supplying both hot water and steam], three satellite heating plants, and cooperative agreements with three industrial facilities generating steam and hot water. Most of the plants are coal-fired, with some peaking units fired by fuel oil.

  12. Experimental validation of a theoretical model for a direct-expansion solar-assisted heat pump applied to heating

    International Nuclear Information System (INIS)

    Moreno-Rodriguez, A.; Garcia-Hernando, N.; González-Gil, A.; Izquierdo, M.

    2013-01-01

    This paper discusses the experimental validation of a theoretical model that determines the operating parameters of a DXSAHP (direct-expansion solar-assisted heat pump) applied to heating. For this application, the model took into account the variable condensing temperature, and it was developed from the following environmental variables: outdoor temperature, solar radiation and wind. The experimental data were obtained from a prototype installed at the University Carlos III, which is located south of Madrid. The prototype uses a solar collector with a total area of 5.6 m 2 , a compressor with a rated capacity of 1100 W, a thermostatic expansion valve and fan-coil units as indoor terminals. The monitoring results were analyzed for several typical days in the climatic zone where the machine was located to understand the equipment's seasonal behavior. The experimental coefficient of the performance varies between 1.9 and 2.7, and the equipment behavior in extreme outdoor conditions has also been known to determine the thermal demand that can be compensated for. - Highlights: • The study aims to present an experimental validation of a theoretical model. • The experimental COP can vary between 1.9 and 2.7 (max. condensation temperature 59 °C). • A “dragging term” relates condensation and evaporation temperature. • The operating parameters respond to the solar radiation. The COP may increase up to 25%

  13. Cogeneration: One way to use biomass efficiently

    International Nuclear Information System (INIS)

    Gustavsson, L.; Johansson, B.

    1993-01-01

    Cogeneration in district heating systems is the most energy-efficient way to convert biomass into heat and electricity with current or nearly commercial technologies. Methanol produced from biomass and used in vehicles instead of petrol or diesel could reduce carbon dioxide emissions nearly as much per unit of biomass as if the biomass were used to replace natural gas for cogeneration, but at some higher cost per unit of carbon dioxide reduction. The most energy-efficient way to use biomass for cogeneration appears to be combined cycle technology, and the world's first demonstration plant is now being built. Potentially, this technology can be used for electricity production in Swedish district heating systems to provide nearly 20% of current Swedish electricity production, while simultaneously reducing carbon dioxide emissions from the district heating systems by some 55%. The heat costs from cogeneration with biomass are higher than the heat costs from fossil fuel plants at current fuel prices. Biomass can only compete with fossil fuel if other advantages, for example a lower environmental impact are considered. (au) (35 refs.)

  14. A multicriteria approach to evaluate district heating system options

    Energy Technology Data Exchange (ETDEWEB)

    Ghafghazi, S.; Sowlati, T. [Department of Wood Science, University of British Columbia, 2931-2424 Main Mall, Vancouver, BC (Canada); Sokhansanj, S. [Department of Chemical and Biological Engineering, University of British Columbia, 2360 East Mall, Vancouver, BC (Canada); Environmental Sciences Division, Oak Ridge National Laboratory, Oak Ridge, TN 37831 (United States); Melin, S. [Department of Chemical and Biological Engineering, University of British Columbia, 2360 East Mall, Vancouver, BC (Canada); Delta Research Corporation, Delta, BC (Canada)

    2010-04-15

    District energy systems, in which renewable energy sources may be utilized, are centralized systems to provide energy to residential and commercial buildings. The aim of this paper is to evaluate and rank energy sources available for a case of district heating system in Vancouver, Canada, based on multiple criteria and the view points of different stakeholders, and to show how communication would affect the ranking of alternatives. The available energy sources are natural gas, biomass (wood pellets), sewer heat, and geothermal heat. The evaluation criteria include GHG emissions, particulate matter emissions, maturity of technology, traffic load, and local source. In order to rank the energy options the PROMETHEE method is used. In this paper, two different scenarios were developed to indicate how the communication between the stakeholders would affect their preferences about criteria weights and would change the ranking of alternatives. The result of this study shows that without communication the best energy source for the considered district energy system is different for different stakeholders. While, addressing concerns through efficient communication would result in a general consensus. In this case, wood pellet is the best energy alternative for all the stakeholders. (author)

  15. Impact of different improvement measures on the thermal performance of a solar collector field for district heating

    DEFF Research Database (Denmark)

    Bava, Federico; Furbo, Simon

    2018-01-01

    The paper describes the impact of different measures to improve the thermal performance of a solar heating plant for district heating applications. The impact of the different measures was evaluated through a validated TRNSYS-Matlab model. The model included details such as effect of the flow...... temperature of the collector field, control strategy based on weather forecast and use of different heat transfer fluids. The results showed that accurate input to the control strategy improved the yearly energy output of the plant by about 3%. If accurate input is not technically or economically feasible...... regime in the absorber pipes on the collector efficiency, flow distribution in the collector field, thermal capacity of the pipes and shadows from row to row. The improvement measures included variation of the operating temperatures, accurate input to the control strategy, feedback control on the outlet...

  16. Combined heat and power and solar energy; BHKW und solare Energie

    Energy Technology Data Exchange (ETDEWEB)

    Marchesi, M.; Schmidt, A.

    2006-07-01

    This illustrated article takes a look at a new apartment complex in Buelach, Switzerland, that meets the 'Minergie' low energy-consumption standard and also features solar-thermal heat generation. This solar installation provides heat for the provision of domestic hot water and, also, heat for the space-heating system of the building complex. The solar collectors cover an area of 153 m{sup 2}; their power is rated at 96 kW. Further elements of the building's technical services include a combined heat and power plant, a heat-pump and a gas-fired boiler. The article discusses ecological and social aspects of the design and construction of the building complex and briefly describes the installations, which also include a 'Minergie' fan-assisted balanced ventilation system.

  17. Procedures for selecting and buying district heating equipment. Sofia district heating. Final report

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1997-11-01

    The aim of this Final Report, prepared for the project `Procedures for Selecting and Buying DistRict Heating Equipment - Sofia District Heating Company`, is to establish an overview of the activities accomplished, the outputs delivered and the general experience gained as a result of the project. The main objective of the project is to enable Sofia District Heating Company to prepare specifications and tender documents, identify possible suppliers, evaluate offers, etc. in connection with purchase of district heating equipment. This objective has been reached by using rehabilitation of sub-stations as an example requested by Sofia DH. The project was originally planned to be finalized end of 1995, but due to the extensions of the scope of work, the project has been prolonged until end 1997. The following main activities were accomplished: Preparation of a detailed work plan; Collection of background information; Discussion and advice about technical specifications and tender documents for sub-station rehabilitation; Input to terms of reference for a master plan study; Input to technical specification for heat meters; Collection of ideas for topics and examples related to dissemination of information to consumers about matters related to district heating consumption. (EG)

  18. Introduction of renewable energy sources in the district heating system of Greece

    Directory of Open Access Journals (Sweden)

    Nikolaos Margaritis

    2016-06-01

    Full Text Available The district heating (DH system of Greece, mainly supported from lignite fired stations, is facing lately significant challenges. Stricter emission limits, decreased efficiency due to old age and increased costs are major challenges of the lignite sector and are expected to result in the decommissioning of several lignite-fired units in the coming years. As a result, managers of DH networks are currently investigating alternative scenarios for the substitution of thermal power that it is expected to be lost, through the integration of Renewable Energy Sources (RES into the system. In this paper, the DH systems of Kozani and Ptolemaida are examined regarding possible introduction of RES. The first study examines district heating of Kozani and alternative future options for covering a part of city’s thermal load whereas the second study refers to a biomass CHP plant (ORC technology, 1MWe, 5MWth to be powered from a biomass mixture (wood chips and straw.

  19. Exergoeconomic analysis of a solar assisted ground-source heat pump greenhouse heating system

    International Nuclear Information System (INIS)

    Ozgener, Onder; Hepbasli, Arif

    2005-01-01

    EXCEM analysis may prove useful to investigators in engineering and other disciplines due to the methodology are being based on the quantities exergy, cost, energy and mass. The main objective of the present study is to investigate between capital costs and thermodynamic losses for devices in solar assisted ground-source heat pump greenhouse heating system (SAGSHPGHS) with a 50 m vertical 32 mm nominal diameter U-bend ground heat exchanger. This system was designed and installed at the Solar Energy Institute, Ege University, Izmir, Turkey. Thermodynamic loss rate-to-capital cost ratios are used to show that, for components and the overall system, a systematic correlation appears to exist between capital cost and exergy loss (total or internal), but not between capital cost and energy loss or external exergy loss. This correlation may imply that devices in successful air conditioning are configured so as to achieve an overall optimal design, by appropriately balancing the thermodynamic (exergy-based) and economic characteristics of the overall system and its devices. The results may, (i) provide useful insights into the relations between thermodynamics and economics, both in general and for SAGSHPGHS (ii) help demonstrate the merits of second-law analysis. It is observed from the results that the maximum exergy destructions in the system particularly occur due to the electrical, mechanical and isentropic efficiencies and emphasize the need for paying close attention to the selection of this type of equipment, since components of inferior performance can considerably reduce the overall performance of the system. In conjunction with this, the total exergy losses values are obtained to be from 0.010 kW to 0.480 kW for the system. As expected, the largest energy and exergy losses occur in the greenhouse and compressor. The ratio of thermodynamic loss rate to capital cost values are obtained for a range from 0.035 to 1.125

  20. District heating in sequential energy supply

    International Nuclear Information System (INIS)

    Persson, Urban; Werner, Sven

    2012-01-01

    Highlights: ► European excess heat recovery and utilisation by district heat distribution. ► Heat recovery in district heating systems – a structural energy efficiency measure. ► Introduction of new theoretical concepts to express excess heat recovery. ► Fourfold potential for excess heat utilisation in EU27 compared to current levels. ► Large scale excess heat recovery – a collaborative challenge for future Europe. -- Abstract: Increased recovery of excess heat from thermal power generation and industrial processes has great potential to reduce primary energy demands in EU27. In this study, current excess heat utilisation levels by means of district heat distribution are assessed and expressed by concepts such as recovery efficiency, heat recovery rate, and heat utilisation rate. For two chosen excess heat activities, current average EU27 heat recovery levels are compared to currently best Member State practices, whereby future potentials of European excess heat recovery and utilisation are estimated. The principle of sequential energy supply is elaborated to capture the conceptual idea of excess heat recovery in district heating systems as a structural and organisational energy efficiency measure. The general conditions discussed concerning expansion of heat recovery into district heating systems include infrastructure investments in district heating networks, collaboration agreements, maintained value chains, policy support, world market energy prices, allocation of synergy benefits, and local initiatives. The main conclusion from this study is that a future fourfold increase of current EU27 excess heat utilisation by means of district heat distribution to residential and service sectors is conceived as plausible if applying best Member State practice. This estimation is higher than the threefold increase with respect to direct feasible distribution costs estimated by the same authors in a previous study. Hence, no direct barriers appear with

  1. 直膨式太阳能热泵系统仿真%Simulation of Direct Expansion Solar Assisted Heat Pump System

    Institute of Scientific and Technical Information of China (English)

    汪坤海; 闫金州; 邢琳; 关欣

    2017-01-01

    随着太阳能热利用和热泵技术的成熟及商品化,直膨式太阳能热泵技术将太阳能资源的清洁性、可再生性等特点和热泵系统的节能、高效的优点相结合,极具研究价值.但是目前直膨式太阳能热泵不能产品化推广的主要限制因素是系统设计不合理、运行不稳定、整体性能不佳等问题.现以直膨式太阳能热泵系统的优化和设计匹配为研究目标,同时,建立压缩机、集热器/蒸发器、热力膨胀阀、冷凝器及储热水箱的数学模型.从理论上分析集热器中集热面积、太阳能辐照度、环境温度、压缩机容积及冷凝温度等因素对直膨式太阳能热泵系统热工性能的影响,通过系统仿真及实验研究系统的整体热力性能,并在此基础上给出改善系统性能的建议.%With the use of solar thermal energy and the development and commercialization of heat pump technology, the direct - expansion solar - assisted heat pump which combines both the clean, renewable and other properties of solar energy resources with energy-saving and high efficient advantages of heat pump system, has great research values. But now major limiting factors of the direct-expansion solar- assisted heat pump cannot be promoted include the unreasonable system design, the unstable operation, the overall poor performance and other issues. The optimization and design matching of the direct-expansion solar-assisted heat pump system are researched; at the same time, a mathematical model of the heat collector/evaporator, compressor, thermostatic expansion valve, condenser and heat storage water tank is established. The area of heat, solar irradiance, ambient temperature, volume of compressor and condensation temperature and other factors on the effect of direct expansion solar-assisted heat pump system of the thermal performance are analyzed from the theory analysis; the overall thermal performance of the system is simulated and studied with

  2. Environmental performance of Miscanthus as a fuel alternative for district heat production

    DEFF Research Database (Denmark)

    Parajuli, Ranjan; Sperling, K.; Dalgaard, Tommy

    2015-01-01

    scenarios: (i) in Combined Heat and Power (CHP) plant and (ii) in a Boiler (producing heat only). Biomass conversion to heat is also compared with the conversion of natural gas (NG). The environmental impact categories considered for the assessment are: Global Warming Potential (GWP), Non-Renewable Energy......This study discusses about the environmental performance of Miscanthus conversion to district heat. Life Cycle Impact Assessment (LCIA) is used as a tool to assess the environmental impacts related to the biomass conversion to heat. Energy conversion of Miscanthus is compared in two combustion...... (NRE) use and Land use (LU). The current study revealed that for 1 MJ of heat production, Miscanthus fired in the CHP plant would lead to a GWP at −0.071 kg CO2-eq, an NRE use −0.767-MJ primary, and LU 0.09 m2-a (square metre-annual). For the same heat output, Miscanthus fired in the boiler would lead...

  3. Evaluation of hybrid solarbiomass dryer with no load

    Directory of Open Access Journals (Sweden)

    Yassen Tadahmun Ahmed

    2014-07-01

    Full Text Available Experimental study was carried out to investigate the performance of designed and fabricated hybrid solar-biomass dryer without load. The solar side was a natural convection mixed mode, while the biomass side was a hot air produced from a burner/gas to gas heat exchanger. The experiments have been conducted to test the dryer temperature, inlet and outlet relative humidity, outlet velocity, and biomass feeding rate. In the solar mode the maximum dryer temperature was 63°C. Behaviours of the velocity in the dryer was found to follow solar radiation available to the dryer. The velocity was in the range of 0.6 – 1.35 m/s through the 0.0176 m2 area of the outlet when the solar radiation was in the range of 150 – 880 W/m2. Two feeding rates of wood were used to investigate the dryer performance through the night. The results showed that at feeding rate 278 g/hr, the drying air mean temperature was 62 ºC. This temperature was more suitable than the measured drying air temperature at feeding rate 490 g/hr. Also the 62 °C drying environment is more stable and feasible for drying almost all types of products.

  4. Integration of biomass into urban energy systems for heat and power. Part II: Sensitivity assessment of main techno-economic factors

    International Nuclear Information System (INIS)

    Pantaleo, Antonio M.; Giarola, Sara; Bauen, Ausilio; Shah, Nilay

    2014-01-01

    Highlights: • Application of a MILP tool for optimal sizing and location of heating and CHP plants to serve residential energy demand. • Trade-offs between local vs centralized heat generation, district heating vs natural gas distribution systems. • Assessment of the key factors influencing the use of biomass and district heating in residential areas. - Abstract: The paper presents the application of a mixed integer linear programming (MILP) methodology to optimize multi-biomass and natural gas supply chain strategic design for heat and power generation in urban areas. The focus is on spatial and temporal allocation of biomass supply, storage, processing, transport and energy conversion (heat and CHP) to match the heat demand of residential end users. The main aim lies on the assessment of the trade-offs between centralized district heating plants and local heat generation systems, and on the decoupling of the biomass processing and biofuel energy conversion steps. After a brief description of the methodology, which is presented in detail in Part I of the research, an application to a generic urban area is proposed. Moreover, the influence of energy demand typologies (urban areas energy density, heat consumption patterns, buildings energy efficiency levels, baseline energy costs and available infrastructures) and specific constraints of urban areas (transport logistics, air emission levels, space availability) on the selection of optimal bioenergy pathways for heat and power is assessed, by means of sensitivity analysis. On the basis of these results, broad considerations about the key factors influencing the use of bioenergy into urban energy systems are proposed. Potential further applications of this model are also described, together with main barriers for development of bioenergy routes for urban areas

  5. District heating and energy efficiency in detached houses of differing size and construction

    Energy Technology Data Exchange (ETDEWEB)

    Joelsson, Anna; Gustavsson, Leif [Ecotechnology, Department of Engineering, Physics and Mathematics, Mid Sweden University, SE-831 25 Oestersund (Sweden)

    2009-02-15

    House envelope measures and conversion of heating systems can reduce primary energy use and CO{sub 2} emission in the existing Swedish building stock. We analysed how the size and construction of electrically heated detached houses affect the potential for such measures and the potential for cogenerated district heating. Our starting point was two typical houses built in the 1970s. We altered the floor plans to obtain 6 houses, with heated floor space ranging between 100 and 306 m{sup 2}. One of the houses was also analysed for three energy standards with differing heat loss rates. CO{sub 2} emission, primary energy use and heating cost were estimated after implementing house envelope measures, conversions to other heating systems and changes in the generation of district heat and electricity. The study accounted for primary energy, including energy chains from natural resources to useful heat in the houses. We showed that conversion to district heating based on biomass, together with house envelope measures, reduced the primary energy use by 88% and the CO{sub 2} emission by 96%, while reducing the annual societal cost by 7%. The choice of end-use heating system was decisive for the primary energy use, with district heating being the most efficient. Neither house size nor energy standard did significantly change the ranking of the heating systems, either from a primary energy or an economic viewpoint, but did affect the extent of the annual cost reduction after implementing the measures. (author)

  6. District heating and energy efficiency in detached houses of differing size and construction

    International Nuclear Information System (INIS)

    Joelsson, Anna; Gustavsson, Leif

    2009-01-01

    House envelope measures and conversion of heating systems can reduce primary energy use and CO 2 emission in the existing Swedish building stock. We analysed how the size and construction of electrically heated detached houses affect the potential for such measures and the potential for cogenerated district heating. Our starting point was two typical houses built in the 1970s. We altered the floor plans to obtain 6 houses, with heated floor space ranging between 100 and 306 m 2 . One of the houses was also analysed for three energy standards with differing heat loss rates. CO 2 emission, primary energy use and heating cost were estimated after implementing house envelope measures, conversions to other heating systems and changes in the generation of district heat and electricity. The study accounted for primary energy, including energy chains from natural resources to useful heat in the houses. We showed that conversion to district heating based on biomass, together with house envelope measures, reduced the primary energy use by 88% and the CO 2 emission by 96%, while reducing the annual societal cost by 7%. The choice of end-use heating system was decisive for the primary energy use, with district heating being the most efficient. Neither house size nor energy standard did significantly change the ranking of the heating systems, either from a primary energy or an economic viewpoint, but did affect the extent of the annual cost reduction after implementing the measures

  7. Biomass and Solar Technologies Lauded | News | NREL

    Science.gov (United States)

    4 » Biomass and Solar Technologies Lauded News Release: Biomass and Solar Technologies Lauded July security and reduce our reliance on foreign sources of oil." The Enzymatic Hydrolysis of Biomass Cellulose to Sugars technology is expected to allow a wide range of biomass resources to be used to produce

  8. Solar hot-water generation and heating - Kombi-Kompakt+

    International Nuclear Information System (INIS)

    Haller, M.; Vogelsanger, P.

    2005-01-01

    This final report for the Swiss Federal Office of Energy (SFOE) describes new testing facilities at the Institute for Solar Technology in Rapperswil, Switzerland, that allow the testing of solar systems the whole year through. The systems tested feature the combined generation of heat for hot water storage vessels and heat for space heating. The test method used, the Concise Cycle Test (CCT) is described. The results of tests made on a large number of systems demonstrate that it is especially important to have a test system that allows the solar market to be protected from unsatisfactory systems. Good co-operation with manufactures is noted. As the test method includes tests with secondary energy sources such as oil or gas, certain problems in this area were discovered and corrected. Further tests are to be made with systems using biomass as a secondary source of heat

  9. Solar heating for a village; Ein Dorf heizt solar

    Energy Technology Data Exchange (ETDEWEB)

    Roepcke, Ina

    2013-07-05

    In Buesingen (administrative district of Konstanz) a solar thermal system with 1091 sqm collector area is put into operation. Together with two wood chip boilers they supply more than 100 private and municipal buildings with regenerative heat. [German] In Buesingen im Landkreis Konstanz ist eine solarthermische Anlage mit 1091 qm Kollektorflaeche in Betrieb gegangen. Zusammen mit zwei Hackschnitzelkesseln versorgt sie ueber 100 private und kommunale Gebaeude mit regenerativer Waerme.

  10. Installation guidelines for Solar Heating System, single-family residence at New Castle, Pennsylvania

    Energy Technology Data Exchange (ETDEWEB)

    1980-01-01

    The Solar Heating System installer guidelines are provided for each subsystem and includes testing and filling the system. This single-family residential heating system is a solar-assisted, hydronic-to-warm-air system with solar-assisted domestic water heating. It is composed of the following major components: liquid cooled flat plate collectors; water storage tank; passive solar-fired domestic water preheater; electric hot water heater; heat pump with electric backup; solar hot water coil unit; tube-and-shell heat exchanger, three pumps, and associated pipes and valving in an energy transport module; control system; and air-cooled heat purge unit. Information is also provided on the operating procedures, controls, caution requirements, and routine and schedule maintenance. Information consists of written procedures, schematics, detail drawings, pictures and manufacturer's component data.

  11. Low Temperature District Heating for Future Energy Systems

    DEFF Research Database (Denmark)

    Schmidt, Dietrich; Kallert, Anna; Blesl, Markus

    2017-01-01

    of the building stock. Low temperature district heating (LTDH) can contribute significantly to a more efficient use of energy resources as well as better integration of renewable energy (e.g. geothermal or solar heat), and surplus heat (e.g. industrial waste heat) into the heating sector. LTDH offers prospects......The building sector is responsible for more than one third of the final energy consumption of societies and produces the largest amount of greenhouse gas emissions of all sectors. This is due to the utilisation of combustion processes of mainly fossil fuels to satisfy the heating demand...... for both the demand side (community building structure) and the supply side (network properties or energy sources). Especially in connection with buildings that demand only low temperatures for space heating. The utilisation of lower temperatures reduces losses in pipelines and can increase the overall...

  12. Urban district heating using nuclear heat - a survey

    International Nuclear Information System (INIS)

    Beresovski, T.; Oliker, I.

    1979-01-01

    The use of heat from nuclear power plants is of great interest in connection with projected future expansions of large urban district heating systems. Oil price escalation and air pollution from increased burning of fossil fuels are substantial incentivers for the adoption of nuclear heat and power plants. The cost of the hot water piping system from the nuclear plant to the city is a major factor in determining the feasibility of using nuclear heat. To achieve reasonable costs, the heat load should be at least 1500 MW(th), transport temperatures 125-200 0 C and distances preferably 50 km or less. Heat may be extracted from the turbines of conventional power reactors. Alternatively, some special-purpose smaller reactors are under development which are specially suited to production of heat with little or no power coproduct. Many countries are conducting studies of future expansions of district heating systems to use nuclear heat. Several countries are developing technology suitable for this application. Actual experience with the use of nuclear heat for district heating is currently being gained only in the USSR, however. While district heating appears to be a desirable technology at a time of increasing fossil-fuel costs, the use of nuclear heat will require siting of nuclear plants within transmission radius of cities. The institutional barries toward use of nuclear heating will have to be overcome before the energy conservation potential of this approach can be realized on a significant scale. (author)

  13. A new photovoltaic solar-assisted loop heat pipe/heat-pump system%新型光伏-太阳能环形热管/热泵复合系统

    Institute of Scientific and Technical Information of China (English)

    张龙灿; 裴刚; 张涛; 季杰

    2014-01-01

    The photovoltaic solar assisted loop heat pipe system/heat-pump (PV-SALHP/HP) is the combination of solar assisted loop heat pipe system (SALHP) and solar assisted heat pipe (SAHP). A photovoltaic/thermal (PVT) evaporator and condenser could be shared by two circling modes, and so is the working medium. The loop heat pipe mode will be utilized when solar radiation is strong and the temperature of working medium in PVT evaporator is higher than that in condenser. Correspondingly, the heat pump mode will be started when solar radiation is weak or the temperature difference of working medium in PVT evaporator and condenser cannot satisfy the condition of loop heat pipe mode. The loop heat pipe mode is passive and the heat pump mode is active, which means that the loop heat pipe mode does not consume work and the heat pump mode does. Therefore, the transformable mode of system could heavily reduce power consumption, raise the utilization ratio of solar energy, and promote energy saving. A PV-SAHP/LHP test rig is built. The instantaneous and daily performance of the loop heat pipe mode and heat pump mode is studied.%光伏-太阳能环形热管/热泵复合系统将太阳能环形热管循环模式和太阳能热泵循环模式有机结合,两者采用相同的工质,共用一个PVT蒸发器和冷凝器。当太阳辐照强度较强,工质在PVT蒸发器中的温度高于冷凝器中的温度时,可以利用环形热管模式制热;当太阳辐照强度较弱或工质在PVT蒸发器中与冷凝器中的温差无法满足环形热管模式运行时,可以利用热泵模式制热。两种模式既能够独立运行,又可以互相切换,确保热能的稳定供应,同时能够明显降低系统耗电量。搭建了光伏-太阳能环形热管/热泵复合系统实验平台,对复合系统在环形热管模式和热泵模式独立运行时的瞬时性能和全天性能进行了实验研究。

  14. Direct expansion solar assisted heat pumps – A clean steady state approach for overall performance analysis

    International Nuclear Information System (INIS)

    Tagliafico, Luca A.; Scarpa, Federico; Valsuani, Federico

    2014-01-01

    Traditional thermal solar panel technologies have limited efficiency and the required economic investments make them noncompetitive in the space heating market. The greatest limit to the diffusion of thermal solar systems is the characteristic temperatures they can reach: the strong connection between the user temperature and the collector temperature makes it possible to achieve high thermal (collector) efficiency only at low, often useless, user temperatures. By using solar collectors as thermal exchange units (evaporators) in a heat pump system (direct expansion solar assisted heat pump, DX-SAHP), the overall efficiency greatly increases with a significative cut of the associated investment in terms of pay-back time. In this study, an approach is proposed to the steady state analysis of DX-SAHP, which is based on the simplified inverse Carnot cycle and on the second law efficiency concept. This method, without the need of calculating the refrigerant fluid properties and the detailed processes occurring in the refrigeration device, allows us to link the main features of the plant to its relevant interactions with the surroundings. The very nature of the proposed method makes the relationship explicit and meaningful among all the involved variables. The paper, after the description of the method, presents an explanatory application of this technique by reviewing various aspects of the performance of a typical DX-SAHP in which the savings on primary energy consumption is regarded as the main feature of the plant and highlighted in a monthly averaged analysis. Results agree to those coming from a common standard steady state thermodynamic analysis. The application to a typical DX-SAHP system demonstrates that a mean saved primary energy of about 50% with respect to standard gas burner can be achieved for the same user needs. Such a result is almost independent from the type of flat plate solar panel used (double or single glazed, or even bare panels) as a result of

  15. Simulation of embedded heat exchangers of solar aided ground source heat pump system

    Institute of Scientific and Technical Information of China (English)

    王芳; 郑茂余; 邵俊鹏; 李忠建

    2008-01-01

    Aimed at unbalance of soil temperature field of ground source heat pump system, solar aided energy storage system was established. In solar assisted ground-source heat pump (SAGSHP) system with soil storage, solar energy collected in three seasons was stored in the soil by vertical U type soil exchangers. The heat abstracted by the ground-source heat pump and collected by the solar collector was employed to heating. Some of the soil heat exchangers were used to store solar energy in the soil so as to be used in next winter after this heating period; and the others were used to extract cooling energy directly in the soil by circulation pump for air conditioning in summer. After that solar energy began to be stored in the soil and ended before heating period. Three dimensional dynamic numerical simulations were built for soil and soil heat exchanger through finite element method. Simulation was done in different strata month by month. Variation and restoration of soil temperature were studied. Economy and reliability of long term SAGSHP system were revealed. It can be seen that soil temperature is about 3 ℃ higher than the original one after one year’s running. It is beneficial for the system to operate for long period.

  16. Future Services for District Heating Solutions in Residential Districts

    Directory of Open Access Journals (Sweden)

    Hannele Ahvenniemi

    2014-06-01

    Full Text Available The underlying assumption of this study is that in order to retain the competitiveness while reaching for the EU targets regarding low-energy construction, district heating companies need to develop new business and service models. How district heating companies could broaden their perspective and switch to a more service-oriented way of thinking is a key interest of our research. The used methods in our study are house builder interviews and a questionnaire. With the help of these methods we discussed the potential interest in heating related services acquiring a comprehensive understanding of the customer needs. The results indicate the importance of certain criteria when choosing the heating system in households: easiness, comfort and affordability seem to dominate the house builders’ preferences. Also environmental awareness seems to be for many an important factor when making a decision about the heating of the house. Altogether, based on the results of this study, we suggest that the prospects of district heating could benefit from highlighting certain aspects and strengths in the future. District heating companies need to increase flexibility, readiness to adopt new services, to invest in new marketing strategies and improving the communication skills.

  17. Investigation of thermodynamic performances for two solar-biomass hybrid combined cycle power generation systems

    International Nuclear Information System (INIS)

    Liu, Qibin; Bai, Zhang; Wang, Xiaohe; Lei, Jing; Jin, Hongguang

    2016-01-01

    Highlights: • Two solar-biomass hybrid combined cycle power generation systems are proposed. • The characters of the two proposed systems are compared. • The on-design and off-design properties of the system are numerically investigated. • The favorable performances of thermochemical hybrid routine are validated. - Abstract: Two solar-biomass hybrid combined cycle power generation systems are proposed in this work. The first system employs the thermochemical hybrid routine, in which the biomass gasification is driven by the concentrated solar energy, and the gasified syngas as a solar fuel is utilized in a combined cycle for generating power. The second system adopts the thermal integration concept, and the solar energy is directly used to heat the compressed air in the topping Brayton cycle. The thermodynamic performances of the developed systems are investigated under the on-design and off-design conditions. The advantages of the hybrid utilization technical mode are demonstrated. The solar energy can be converted and stored into the chemical fuel by the solar-biomass gasification, with the net solar-to-fuel efficiency of 61.23% and the net solar share of 19.01% under the specific gasification temperature of 1150 K. Meanwhile, the proposed system with the solar thermochemical routine shows more favorable behaviors, the annual system overall energy efficiency and the solar-to-electric efficiency reach to 29.36% and 18.49%, while the with thermal integration concept of 28.03% and 15.13%, respectively. The comparison work introduces a promising approach for the efficient utilization of the abundant solar and biomass resources in the western China, and realizes the mitigation of CO_2 emission.

  18. Integrated multiscale simulation of combined heat and power based district heating system

    International Nuclear Information System (INIS)

    Li, Peifeng; Nord, Natasa; Ertesvåg, Ivar Ståle; Ge, Zhihua; Yang, Zhiping; Yang, Yongping

    2015-01-01

    Highlights: • Simulation of power plant, district heating network and heat users in detail and integrated. • Coupled calculation and analysis of the heat and pressure losses of the district heating network. • District heating is not preferable for very low heat load due to relatively high heat loss. • Lower design supply temperatures of the district heating network give higher system efficiency. - Abstract: Many studies have been carried out separately on combined heat and power and district heating. However, little work has been done considering the heat source, the district heating network and the heat users simultaneously, especially when it comes to the heating system with large-scale combined heat and power plant. For the purpose of energy conservation, it is very important to know well the system performance of the integrated heating system from the very primary fuel input to the terminal heat users. This paper set up a model of 300 MW electric power rated air-cooled combined heat and power plant using Ebsilon software, which was validated according to the design data from the turbine manufacturer. Then, the model of heating network and heat users were developed based on the fundamental theories of fluid mechanics and heat transfer. Finally the combined heat and power based district heating system was obtained and the system performances within multiscale scope of the system were analyzed using the developed Ebsilon model. Topics with regard to the heat loss, the pressure drop, the pump power consumption and the supply temperatures of the district heating network were discussed. Besides, the operational issues of the integrated system were also researched. Several useful conclusions were drawn. It was found that a lower design primary supply temperature of the district heating network would give a higher seasonal energy efficiency of the integrated system throughout the whole heating season. Moreover, it was not always right to relate low design

  19. Performance Evaluation of a Lithium-Chloride Absorption Refrigeration and an Assessment of Its Suitability for Biomass Waste Heat

    Directory of Open Access Journals (Sweden)

    Sacha Oberweis

    2012-10-01

    Full Text Available This paper presents a computer model that will evaluate the performance of a thermo-chemical accumulator. The model is based on operational data such as temperatures and flow rates. The ultimate goal for this model is to estimate the coefficient of performance (COP of this unit when run on hot water from biomass combustion as the heat source. The outputs of the model are verified by comparing the simulation of the actual machine with published experimental data. The computed results for cooling COP are within 10% of the measured data. The simulations are all run for heat load temperatures varying between 80 °C and 110 °C. As expected, simulation results showed an increase in COP with increased heat source temperatures. The results demonstrate that the potential of combined solar and biomass combustion as a heat source for absorption cooling/heating in climates with low solar radiation can be coupled with biomass waste.

  20. District Heating Expansion Potential with Low-Temperature and End-Use Heat Savings

    DEFF Research Database (Denmark)

    Nielsen, Steffen; Grundahl, Lars

    2018-01-01

    District heating has the potential to play a key role in the transition towards a renewable energy system. However, the development towards reduced heat demands threatens the feasibility of district heating. Despite this challenge, opportunity exists in the form of fourth generation district...... heating, which operates at lower temperatures and enables better renewable integration. This article investigates this challenge by examining the district heating potential within three scenarios: The first is a reference scenario with current heat demand and temperatures, the second includes heat demand...... costs. The models are applied using an example case of The Northern Region of Denmark. The article concludes that the district heating potential is highest in the reference scenario. When heat savings are introduced, district heating expansions, in most cases, will not be feasible. Introducing low...

  1. Energy savings for solar heating systems; Solvarmeanlaegs energibesparelser

    Energy Technology Data Exchange (ETDEWEB)

    Furbo, S.; Fan, J.

    2011-01-15

    Energy savings for a number of new solar heating systems in one family houses have been determined by means of information on the energy consumption of the houses before and after installation of the solar heating systems. The investigated solar heating systems are marketed by Velux Danmark A/S, Sonnnenkraft Scandinavia A/S and Batec Solvarme A/S. Solar domestic hot water systems as well as solar combi systems are included in the investigations The houses have different auxiliary energy supply systems: Natural gas boilers, oil fired burners, electrical heating and district heating. Some of the houses have a second auxiliary energy supply system. The collector areas vary from 1.83 m{sup 2} to 9.28 m{sup 2}. Some of the solar heating systems are based on energy units with a new integrated natural gas boiler and a heat storage for the solar heating system. The existing energy systems in the houses are for most of the houses used as the auxiliary energy systems for the solar heating systems. The yearly energy savings for the houses where the only change is the installation of the solar heating system vary from 300 kWh per m{sup 2} solar collector to 1300 kWh per m{sup 2} solar collector. The average yearly energy savings is about 670 kWh per m{sup 2} solar collector for these solar heating systems. The energy savings per m{sup 2} solar collector are not influenced by the solar heating system type, the company marketing the system, the auxiliary energy supply system, the collector area, the collector tilt, the collector azimuth, the energy consumption of the house or the location of the house. The yearly energy savings for the houses with solar heating systems based on energy units including a new natural gas boiler vary from 790 kWh per m{sup 2} solar collector to 2090 kWh per m{sup 2} solar collector. The average yearly energy savings is about 1520 kWh per m{sup 2} solar collector for these solar heating systems. The energy savings per m{sup 2} solar collector for

  2. Geothermal direct-heat utilization assistance: Federal assistance program. Quarterly project progress report, October--December 1995

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1996-02-01

    The report summarizes geothermal technical assistance, R&D and technology transfer activities of the Geo-Heat Center at Oregon Institute of Technology for the first quarter of FY-96. It describes 90 contacts with parties during this period related to technical assistance with geothermal direct heat projects. Areas dealt with include geothermal heat pumps, space heating, greenhouses, aquaculture, equipment and resources. Research activities are summarized on low-temperature resource assessment, geothermal district heating system cost evaluation and silica waste utilization project. Outreach activities include the publication of a geothermal direct use Bulletin, dissemination of information, geothermal library, technical papers and seminars, development of a webpage, and progress monitor reports on geothermal resources and utilization.

  3. Preliminary study on solar-assisted tobacco curing in Thailand

    Energy Technology Data Exchange (ETDEWEB)

    Bamrungwong, S [Chiang Mai Univ.; Suchinda, B; Malila, D

    1982-04-01

    A solar heating system for assisting flue curing of Virginia tobacco leaf was studied. The equipment consisted of a brick and mortar tobacco curing barn of 3.6 m/sup 3/ volume. The solar air heater of 2.8 m/sup 2/ was a non-focus type, made from corrugated galvanized stel sheet coated with flat-black paint. The collector had a single glass cover on top and a 25 mm layer of styrofoam at the bottom. Electrical heating was utilized inside the bar to simulate the main heat source. The system under study had no thermal storage, therefore it was extremely difficult to regulate the temperature inside the barn precisely. Consequently, the solar assisting mode is not recommended during the yellowing stage of curing where very precise temperature control is required. Utilization of solar energy during other stages of curing showed a saving of the main conventional energy up to 33 to 15 percent. The average thermal efficiencies of the collector varied from 70 percent at high flow rate to 67 percent at low flow rate. 6 references.

  4. Solar assisted heat pumps: A possible wave of the future

    Science.gov (United States)

    Smetana, F. O.

    1976-01-01

    With the higher costs of electric power and the widespread interest to use solar energy to reduce the national dependence on fossil fuels, heat pumps are examined to determine their suitability for use with solar energy systems.

  5. Solarthermie 2000 - Partial programme 3: Solar district heat - solar campus Juelich, feasibility study of the seasonal heat storage; Solarthermie 2000, Teilprogramm 3: Solare Nahwaerme - Solar-Campus Juelich, Machbarkeitsuntersuchung des saisonalen Waermespeichers

    Energy Technology Data Exchange (ETDEWEB)

    Braxein, A. [Iwu - Ingenieurgesellschaft fuer Wasser und Umwelt mbH, Aachen (Germany); Spaete, F.; Repschlaeger, H. [Solar-Inst. Juelich (Germany); Friedel, J. [Stadtwerke Juelich (Germany)

    1998-12-31

    The heart of the solar-assisted district heating system for the solar campus Juelich is going to be a seasonal underground store with a capacity of 2,500 cubic metres, e.g. a rather small long-term storage. The aim of the project was to prove the technical and financial feasibility of the underground store by developing a building concept for the storage and to determine whether this concept was also suitable for larger storage facilities. The design of the floating lid and the suitability of various building materials were studied by means of a physical model. The resulting storage concept shows an underground storage pit whose shape is an inverted square pyramid base with a seal of double-layer PP-foil and a thermal insulation of pressure-resistant mineral wool in the upper part. The lid consists of 16 square walk-on floating containers with an edge length of 6.50 metres and a height of 1.0 metre each. Tests and calculations showed that the concept can be realised. The building costs for the small storage with a capacity of 2,500 cubic metres will amount to approx. DM 370 per cubic metre, costs for larger volumes of 25,000 cubic metres will amount to approx. DM 150 DM per cubic metre of water stored. (orig.) [Deutsch] Das Kernstueck der solargestuetzten Nahwaermeversorgung fuer den Solar-Campus Juelich soll ein 2500 m{sup 3} grosser, saisonaler Erdbeckenspeicher bilden, also ein relativ kleiner Langzeitspeicher. Ziel des Vorhabens war, die technische und finanzielle Machbarkeit des geplanten Erdbeckenspeichers durch ein baureifes Speicherkonzept nachzuweisen sowie die Uebertragbarkeit auf grosse saisonale Speicher gleicher Bauart zu untersuchen. Die konstruktive Ausbildung der schwimmenden Deckelkonstruktion sowie die Eignung verschiedener Baumaterialien wurden mit Hilfe eines physikalischen Modells untersucht. Das resultierende Speicherkonzept sieht einen Erdbeckenspeicher in Form eines umgedrehten, quadratischen Pyramidenstumpfes mit einer Abdichtung aus

  6. Fuzzy comprehensive evaluation of district heating systems

    International Nuclear Information System (INIS)

    Wei Bing; Wang Songling; Li Li

    2010-01-01

    Selecting the optimal type of district heating (DH) system is of great importance because different heating systems have different levels of efficiency, which will impact the system economics, environment and energy use. In this study, seven DH systems were analysed and evaluated by the fuzzy comprehensive evaluation method. The dimensionless number-goodness was introduced into the calculation, the economics, environment and energy technology factors were considered synthetically, and the final goodness values were obtained. The results show that if only one of the economics, environment or energy technology factors are considered, different heating systems have different goodness values. When all three factors were taken into account, the final ranking of goodness values was: combined heating and power>gas-fired boiler>water-source heat pump>coal-fired boiler>ground-source heat pump>solar-energy heat pump>oil-fired boiler. The combined heating and power system is the best choice from all seven systems; the gas-fired boiler system is the best of the three boiler systems for heating purpose; and the water-source heat pump is the best of the three heat pump systems for heating and cooling.

  7. Shortage of energy increases profitability of district heating

    International Nuclear Information System (INIS)

    2003-01-01

    Increased demand will cause the price of district heating to increase, but not to the level of the price of electricity. The cheapest heating alternative in Denmark, Norway and Sweden is district heating. In Norway, district heating is developed primarily for commercial buildings and housing cooperatives. Thirty per cent of all buildings under construction are prepared for district heating and the percentage will increase strongly in the coming time. The total net production of district heating in Norway in 2001 was 2000 GWh, which is only a small part of the total potential for district heating

  8. District heating in Flensburg

    Energy Technology Data Exchange (ETDEWEB)

    Prinz, W.

    1981-01-01

    The majority of our population, but also of our authorities, are still skeptical or even disapproving towards district heating. The reasons of this negative attitude are partly psychological - e.g. the individualism of the Swiss and their dislike for too centralised structures and ''forced connections'' - but also the existence of finished gas supply networks and the fear of considerable pre-investments and torn streets over years. The following article - held as a speech on the information meeting ''District heating and the possible contribution of nuclear energy'' organised by the Swiss Association for Atomic Energy in Bern shows a practical problem solving at the example of the district heating in Flensburg and deals with these questions.

  9. An economic optimization of evaporator and air collector area in a solar assisted heat pump drying system

    International Nuclear Information System (INIS)

    Rahman, S.M.A.; Saidur, R.; Hawlader, M.N.A.

    2013-01-01

    Highlights: • The optimum combination will provide around 89% of the total load. • The system has a savings during the life cycle with least payback period of 4.37 year. • The optimal system is insensitive to the variation in fuel inflation and discount rate. - Abstract: This paper presents an economic optimization of evaporator and air collector area of a solar assisted heat pump drying system. Economic viability of solar heating systems is usually made by comparing the cost flows recurring throughout the lifetime of the solar and conventional alternative systems. Therefore, identification of optimum variables by using a simulation program and an economic analysis based on payback period of the system are presented in this paper. FORTRAN language is used to run the simulation. Effect of load and different economic variables on payback period is also investigated. Economic analysis reveals that system has sufficient amount of savings during the life cycle with a minimum payback period of about 4 years

  10. The impact of lignocellulosic ethanol yields in polygeneration with district heating – A case study

    International Nuclear Information System (INIS)

    Starfelt, Fredrik; Daianova, Lilia; Yan, Jinyue; Thorin, Eva; Dotzauer, Erik

    2012-01-01

    Highlights: ► We model a system with ethanol, power and district heating production. ► Different ethanol yields are investigated from an overall system perspective. ► Yields of ethanol production have less importance for the profitability of the plant. -- Abstract: The development towards high energy efficiency and low environmental impact from human interactions has led to changes at many levels of society. As a result of the introduction of penalties on carbon dioxide emissions and other economic instruments, the energy industry is striving to improve energy efficiency and climate mitigation by switching from fossil fuels to renewable fuels. Biomass-based combined heat and power (CHP) plants connected to district heating networks have a need to find uses for the excess heat they produce in summer when the heat demand is low. On the other hand, the transport sector makes a substantial contribution to the increasing CO 2 emissions, which have to be reduced. One promising alternative to address these challenging issues is the integration of vehicle fuel production with biomass-based CHP plants. This paper presents the configuration and operating profits in terms of electricity, heat and ethanol fuel from cellulosic biomass. A case study of a commercial small scale CHP plant was conducted using simulation and modeling tools. The results clearly show that electricity production can be increased when CHP production is integrated with cellulosic ethanol production. The findings also show that the economic benefits of the energy system can be realized with near-term commercially available technology, and that the benefits do not rely solely on ethanol yields.

  11. Techno-economic evaluation of a ventilation system assisted with exhaust air heat recovery, electrical heater and solar energy

    OpenAIRE

    Özyoğurtçu, Gamze; Mobedi, Moghtada; Özerdem, Barış

    2014-01-01

    The energy consumed to condition fresh air is considerable, particularly for the buildings such as cinema, theatre or gymnasium saloons. The aim of the present study is to design a ventilation system assisted with exhaust air heat recovery unit, electrical heater and stored solar energy, then to make an economical analysis based on life cycle cost (LCC) to find out its payback period. The system is able to recover thermal energy of exhaust air, store solar energy during the sunlight period an...

  12. 加热原油的太阳能-污水源热泵系统的开发%Development on solar-assisted sewage source heat pump system for crude oil heating

    Institute of Scientific and Technical Information of China (English)

    钱剑峰; 王强

    2017-01-01

    In this paper, the situations of crude oil heating and oily water utilization were analyzed.The development situation of solar heat pump at home and abroad was introduced.It was put forward that the solar-assisted sewage source heat pump system could be used to reuse oily water for crude oil heating.The composition of the system and five kinds of operation mode were analyzed.The mathematical model was also established.It provided some references for the application of solar-assisted sewage source heat pump system.%分析了油田用热现状和含油污水利用现状,详述了太阳能热泵在国内外的发展现状.在此基础上,提出应用太阳能-污水源热泵系统回收含油污水余热来加热原油,进而分析了该系统的组成及五种运行模式,建立了系统的数学模型,为太阳能-污水源热泵系统的应用提供参考.

  13. A good year for district heating

    International Nuclear Information System (INIS)

    Bakken, Stein Arne

    2003-01-01

    In Norway, high prices on electric power have caused economic progress for the district heating companies. The price of district heating is determined by the prices of power and fuel oil. However, the government wants to remove the tax on electricity to the industry, which is the district heating companies' major group of customers, along with public buildings. This is likely to entail a great loss of income

  14. Microwave-assisted pyrolysis of biomass for liquid biofuels production

    DEFF Research Database (Denmark)

    Yin, Chungen

    2012-01-01

    Production of 2nd-generation biofuels from biomass residues and waste feedstock is gaining great concerns worldwide. Pyrolysis, a thermochemical conversion process involving rapid heating of feedstock under oxygen-absent condition to moderate temperature and rapid quenching of intermediate products......, is an attractive way for bio-oil production. Various efforts have been made to improve pyrolysis process towards higher yield and quality of liquid biofuels and better energy efficiency. Microwave-assisted pyrolysis is one of the promising attempts, mainly due to efficient heating of feedstock by ‘‘microwave...

  15. A review of large-scale solar heating systems in Europe

    International Nuclear Information System (INIS)

    Fisch, M.N.; Guigas, M.; Dalenback, J.O.

    1998-01-01

    Large-scale solar applications benefit from the effect of scale. Compared to small solar domestic hot water (DHW) systems for single-family houses, the solar heat cost can be cut at least in third. The most interesting projects for replacing fossil fuels and the reduction of CO 2 -emissions are solar systems with seasonal storage in combination with gas or biomass boilers. In the framework of the EU-APAS project Large-scale Solar Heating Systems, thirteen existing plants in six European countries have been evaluated. lie yearly solar gains of the systems are between 300 and 550 kWh per m 2 collector area. The investment cost of solar plants with short-term storage varies from 300 up to 600 ECU per m 2 . Systems with seasonal storage show investment costs twice as high. Results of studies concerning the market potential for solar heating plants, taking new collector concepts and industrial production into account, are presented. Site specific studies and predesign of large-scale solar heating plants in six European countries for housing developments show a 50% cost reduction compared to existing projects. The cost-benefit-ratio for the planned systems with long-term storage is between 0.7 and 1.5 ECU per kWh per year. (author)

  16. Increased combustion stability in modulating biomass boilers for district heating systems

    Energy Technology Data Exchange (ETDEWEB)

    Eriksson, Gunnar; Hermansson, Roger (eds.) [Lulea Univ. of Technology (Sweden)

    2002-09-01

    One of the problems in small district heating systems is the large load variation that must be handled by the system. If the boiler is designed to cover the needs during the coldest day in winter time in northern Europe it would have to run at loads as low as 10% of full load during summer time, when heat is needed only for tap water production. Load variations in small networks are quite fast and earlier investigations have shown that existing biomass boilers give rise to large amounts of harmful emissions at fast load variations and at low loads. The problem has been addressed in different ways: Three new boiler concepts have been realized and tested: A prototype of a 500 kW boiler with partitioned primary combustion chamber and supplied with a water heat store. A 10 kW bench scale combustor and a 500 kW prototype boiler based on pulsating combustion. Bench scale boilers to test the influence from applied sound on emissions and a 150 kW prototype boiler with a two-stage secondary vortex combustion chamber. Development of control and regulating equipment: Glow Guard, a control system using infra-red sensors to detect glowing char on the grate, has been constructed and tested. A fast prediction model that can be used in control systems has been developed. Simulation of the combustion process: Code to simulate pyrolysis/gasification of fuel on the grate has been developed. Combustion of the gas phase inside the combustion chamber has been simulated. The two models have been combined to describe the combustion process inside the primary chamber of a prototype boiler. A fast simulation code based on statistical methods that can predict the environmental performance of boilers has been developed. One of the boiler concepts matches the desired load span from 10 to 100% of full load with emissions far below the set limits for CO and THC and close to the set limits for NO{sub x}. The other boilers had a bit more narrow load range, one with very low emissions except for NO

  17. Impact assessment of biomass-based district heating systems in densely populated communities. Part II: Would the replacement of fossil fuels improve ambient air quality and human health?

    Science.gov (United States)

    Petrov, Olga; Bi, Xiaotao; Lau, Anthony

    2017-07-01

    To determine if replacing fossil fuel combustion with biomass gasification would impact air quality, we evaluated the impact of a small-scale biomass gasification plant (BRDF) at a university campus over 5 scenarios. The overall incremental contribution of fine particles (PM2.5) is found to be at least one order of magnitude lower than the provincial air quality objectives. The maximum PM2.5 emission from the natural gas fueled power house (PH) could adversely add to the already high background concentration levels. Nitrogen dioxide (NO2) emissions from the BRDF with no engineered pollution controls for NOx in place exceeded the provincial objective in all seasons except during summer. The impact score, IS, was the highest for NO2 (677 Disability Adjusted Life Years, DALY) when biomass entirely replaced fossil fuels, and the highest for PM2.5 (64 DALY) and CO (3 DALY) if all energy was produced by natural gas at PH. Complete replacement of fossil fuels by one biomass plant can result in almost 28% higher health impacts (708 DALY) compared to 513 DALY when both the current BRDF and the PH are operational mostly due to uncontrolled NO2 emissions. Observations from this study inform academic community, city planners, policy makers and technology developers on the impacts of community district heating systems and possible mitigation strategies: a) community energy demand could be met either by splitting emissions into more than one source at different locations and different fuel types or by a single source with the least-impact-based location selection criteria with biomass as a fuel; b) advanced high-efficiency pollution control devices are essential to lower emissions for emission sources located in a densely populated community; c) a spatial and temporal impact assessment should be performed in developing bioenergy-based district heating systems, in which the capital and operational costs should be balanced with not only the benefit to greenhouse gas emission

  18. Performance analysis on solar-water compound source heat pump for radiant floor heating system

    Institute of Scientific and Technical Information of China (English)

    曲世林; 马飞; 仇安兵

    2009-01-01

    A solar-water compound source heat pump for radiant floor heating (SWHP-RFH) experimental system was introduced and analyzed. The SWHP-RFH system mainly consists of 11.44 m2 vacuum tube solar collector,1 000 L water tank assisted 3 kW electrical heater,a water source heat pump,the radiant floor heating system with cross-linked polyethylene (PE-X) of diameter 20 mm,temperature controller and solar testing system. The SWHP-RFH system was tested from December to February during the heating season in Beijing,China under different operation situations. The test parameters include the outdoor air temperature,solar radiation intensity,indoor air temperature,radiation floor average surface temperature,average surface temperature of the building envelope,the inlet and outlet temperatures of solar collector,the temperature of water tank,the heat medium temperatures of heat pump condenser side and evaporator side,and the power consumption includes the water source heat pump system,the solar source heat pump system,the auxiliary heater and the radiant floor heating systems etc. The experimental results were used to calculate the collector efficiency,heat pump dynamic coefficient of performance (COP),total energy consumption and seasonal heating performance during the heating season. The results indicate that the performance of the compound source heat pump system is better than that of the air source heat pump system. Furthermore,some methods are suggested to improve the thermal performance of each component and the whole SWHP-RFH system.

  19. Diagnosis of district potential in terms of renewable energies. Report 1 - Present situation: Assessment of renewable energy production, Identification and quantification of territory's potentialities in terms of renewable energies

    International Nuclear Information System (INIS)

    2010-10-01

    After a presentation of the Gers district context (geography, administrative organisation, demography, housing, economy, expertise), the report presents the energy situation, an overview of the solar thermal sector (installations and installers), of the solar photovoltaic sector (existing and projected installations, installers), of hydroelectricity, of wood-energy (individual heating, industrial heating plants, planned installations), of wind energy, of biogas, and of geothermal energy (existing and planned installations). It proposes an assessment of these energies as a whole. Then, after an overview of the district situation with respect to national objectives and to other districts of the region, the study reports an identification and quantification of potentialities in terms of theoretical resources for different energy sources (solar, wind, hydraulic, wood, methanization, valorizable biomass, geothermal, and agri-fuels). Avoided CO 2 emissions are assessed

  20. Metamorphoses of cogeneration-based district heating in Romania: A case study

    International Nuclear Information System (INIS)

    Iacobescu, Flavius; Badescu, Viorel

    2011-01-01

    The paper presents the birth and evolution of the cogeneration-based district heating (DH) system in a medium size city in Romania (Targoviste). The evolution of the industrialization degree was the main factor which controlled the population growth and led to a continuous reconfiguration of the DH system. The DH system assisted by cogeneration emerged as a solution in a certain phase of the demographic development of the city. The political and social changes occurring in Romania after 1990 have had important negative consequences on the DH systems in small towns. In Targoviste the DH system survived but in 2001 the solution based on cogeneration became economically inefficient, due to the low technical quality of the existing equipment and the low gas prices, to the procedure of setting the DH tariffs and the service cost at consumer's level and to some bureaucratic problems. Energy policy measures taken at national and local levels in 2003 and 2005 led to the re-establishment of the cogeneration-based district heating in 2005. However, a different technical solution has been adopted. Details about the present (2009) cogeneration-based DH system in Targoviste are presented together with several technical and economical indicators. The main conclusion is that by a proper amendment of the technical solutions, cogeneration could be a viable solution for DH even in case of abrupt social and demographic changes, such as those occurring in Romania after 1990. - Research Highlights: →Birth and evolution of the cogeneration-based district heating system in a medium size city. →The industrialization degree is the main factor which controlled the reconfiguration of the district heating system. →Each stage of the evolution of district heating system has been a technological leap. →Cogeneration is a solution for district heating even in case of abrupt social changes.

  1. Central heating in Norway. A study of the market trends for the period 2008-2011; Vannbaaren varme i Norge. Et studium av markedsutviklingen i perioden 2008-2011

    Energy Technology Data Exchange (ETDEWEB)

    Haarberg, Karl Johan; Hansen, Eivind; Bjoerneng, Heidi; Vasvik, Truls

    2012-11-01

    Under floor heating distribution buildings gives the flexibility to accept multiple forms of renewable energy, whether from district heating, biomass, solar collectors or heat pumps. Central heating is therefore a joker for a flexible energy. This is why Prognosesenteret commissioned by Enova has conducted a survey on central heating systems aimed at plumbers over a 5-year period. (eb)

  2. District heating

    International Nuclear Information System (INIS)

    Hansen, L.

    1993-01-01

    The environmental risks and uncertainties of a high-energy future are disturbing and give rise to several reservations concerning the use of fossil fuels. A number of technologies will help to reduce atmospheric pollution. In Denmark special importance is attached to the following: Energy conservation. Efficient energy conversion. Renewable energy sources. District heating, combined production of heat and power. Many agree that district heating (DH), produced by the traditional heat-only plant, and combined heat and power (CHP) have enormous potential when considering thermal efficiency and lowered environmental impacts: The basic technology of each is proven, it would be relatively simple to satisfy a substantial part of the energy demand, and their high efficiencies mean reduced pollution including greenhouse gas emissions. This is especially important in high population density areas - the obviously preferred sites for such energy generation. Compared with individual heating DH can provide a community with an operationally efficient and most often also an economically competitive heat supply. This is particularly true under the circumstances where the DH system is supplied from CHP plants. Their use results in very substantial improvements in overall efficiency. Further environmental improvements arise from the reduced air pollution obtainable in reasonably large CHP plants equipped with flue gas cleaning to remove particles, sulphur dioxide, and nitrogen acids. As a consequence of these considerations, DH plays an important role in fulfilling the space and water heating demand in many countries. This is especially the case in Denmark where this technology is utilised to a very great extent. Indeed, DH is one of the reasons why Denmark has relatively good air quality in the cities. (au)

  3. Large scale solar district heating. Evaluation, modelling and designing - Appendices

    Energy Technology Data Exchange (ETDEWEB)

    Heller, A.

    2000-07-01

    The appendices present the following: A) Cad-drawing of the Marstal CSHP design. B) Key values - large-scale solar heating in Denmark. C) Monitoring - a system description. D) WMO-classification of pyranometers (solarimeters). E) The computer simulation model in TRNSYS. F) Selected papers from the author. (EHS)

  4. Device for district heating with utilization of waste heat from power plants

    International Nuclear Information System (INIS)

    Korek, J.

    1976-01-01

    In order to utilize the waste heat developing in power plants - especially in nuclear power plants - the author suggests to lead the waste heat of the coolers for oil (which the bearings are lubricated with), hydrogen (which serves for the stator rotor-cooling), and the stator cooling water to the circulating district heating water and to arrange these heat exchangers one behind another or parallel to each other in the water circuit of the district heating system. The oil cooler of the engine transformer is also connected with the circulation of the district heating water. The runback water of the district heating network could thus be heated from approx. 40 0 C up to 65 0 C. (UA) [de

  5. System impact of energy efficient building refurbishment within a district heated region

    International Nuclear Information System (INIS)

    Lidberg, T.; Olofsson, T.; Trygg, L.

    2016-01-01

    The energy efficiency of the European building stock needs to be increased in order to fulfill the climate goals of the European Union. To be able to evaluate the impact of energy efficient refurbishment in matters of greenhouse gas emissions, it is necessary to apply a system perspective where not only the building but also the surrounding energy system is taken into consideration. This study examines the impact that energy efficient refurbishment of multi-family buildings has on the district heating and the electricity production. It also investigates the impact on electricity utilization and emissions of greenhouse gases. The results from the simulation of four energy efficiency building refurbishment packages were used to evaluate the impact on the district heating system. The packages were chosen to show the difference between refurbishment actions that increase the use of electricity when lowering the heat demand, and actions that lower the heat demand without increasing the electricity use. The energy system cost optimization modeling tool MODEST (Model for Optimization of Dynamic Energy Systems with Time-Dependent Components and Boundary Conditions) was used. When comparing two refurbishment packages with the same annual district heating use, this study shows that a package including changes in the building envelope decreases the greenhouse gas emissions more than a package including ventilation measures. - Highlights: • Choice of building refurbishment measures leads to differences in system impact. • Building refurbishment in district heating systems reduces co-produced electricity. • Valuing biomass as a limited resource is crucial when assessing global GHG impact. • Building envelope measures decrease GHG (greenhouse gas) emissions more than ventilation measures.

  6. Federal technology alert. Parabolic-trough solar water heating

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1998-04-01

    Parabolic-trough solar water heating is a well-proven renewable energy technology with considerable potential for application at Federal facilities. For the US, parabolic-trough water-heating systems are most cost effective in the Southwest where direct solar radiation is high. Jails, hospitals, barracks, and other facilities that consistently use large volumes of hot water are particularly good candidates, as are facilities with central plants for district heating. As with any renewable energy or energy efficiency technology requiring significant initial capital investment, the primary condition that will make a parabolic-trough system economically viable is if it is replacing expensive conventional water heating. In combination with absorption cooling systems, parabolic-trough collectors can also be used for air-conditioning. Industrial Solar Technology (IST) of Golden, Colorado, is the sole current manufacturer of parabolic-trough solar water heating systems. IST has an Indefinite Delivery/Indefinite Quantity (IDIQ) contract with the Federal Energy Management Program (FEMP) of the US Department of Energy (DOE) to finance and install parabolic-trough solar water heating on an Energy Savings Performance Contract (ESPC) basis for any Federal facility that requests it and for which it proves viable. For an ESPC project, the facility does not pay for design, capital equipment, or installation. Instead, it pays only for guaranteed energy savings. Preparing and implementing delivery or task orders against the IDIQ is much simpler than the standard procurement process. This Federal Technology Alert (FTA) of the New Technology Demonstration Program is one of a series of guides to renewable energy and new energy-efficient technologies.

  7. An evaluation of solar energy for heating a highway maintenance headquarters building.

    Science.gov (United States)

    1985-01-01

    A highway maintenance area headquarters building having overall dimensions of 64 ft - 8 in by 42 ft - 0 in was equipped with an active solar heating system to assist in heating space and domestic hot water. The solar system was instrumented and its o...

  8. Biomass and Swedish energy policy

    International Nuclear Information System (INIS)

    Johansson, Bengt

    2001-01-01

    The use of biomass in Sweden has increased by 44% between 1990 and 1999. In 1999 it was 85 TWh, equivalent to 14% of the total Swedish energy supply. The existence of large forest industry and district heating systems has been an essential condition for this expansion. The tax reform in 1991 seems, however, to have been the most important factor responsible for the rapid bioenergy expansion. Through this reform, the taxation of fossil fuels in district heating systems increased by approximately 30-160%, depending on fuel, whereas bioenergy remained untaxed. Industry is exempted from the energy tax and pays reduced carbon tax. No tax is levied on fossil fuels used for electricity production. Investment grants have existed for biomass-based electricity production but these grants have not been large enough to make biomass-based electricity production economically competitive in a period of falling electricity prices. Despite this, the biomass-based electricity production has increased slightly between 1990 and 1999. A new taxation system aiming at a removal of the tax difference between the industry, district heating and electricity sectors has recently been analysed by the Swedish government. One risk with such a system is that it reduces the competitiveness for biomass in district heating systems as it seems unlikely that the taxes on fossil fuels in the industry and electricity sectors will increase to a level much higher than in other countries. A new system, based on green certificates, for supporting electricity from renewable energy sources has also been proposed by the government.

  9. 4th Generation District Heating (4GDH)

    DEFF Research Database (Denmark)

    Lund, Henrik; Werner, Sven; Wiltshire, Robin

    2014-01-01

    This paper defines the concept of 4th Generation District Heating (4GDH) including the relations to District Cooling and the concepts of smart energy and smart thermal grids. The motive is to identify the future challenges of reaching a future renewable non-fossil heat supply as part...... of the implementation of overall sustainable energy systems. The basic assumption is that district heating and cooling has an important role to play in future sustainable energy systems – including 100 percent renewable energy systems – but the present generation of district heating and cooling technologies will have...

  10. Solar assisted alkali pretreatment of garden biomass: Effects on lignocellulose degradation, enzymatic hydrolysis, crystallinity and ultra-structural changes in lignocellulose

    International Nuclear Information System (INIS)

    Gabhane, Jagdish; William, S.P.M. Prince; Vaidya, Atul N.; Das, Sera; Wate, Satish R.

    2015-01-01

    Highlights: • SAAP is an efficient and economic means of pretreatment. • SAAP was found to be efficient in lignin and hemicellulose removal. • SAAP enhanced the enzymatic hydrolysis. • FTIR, XRD and SEM provided vivid understanding about the mode of action of SAAP. • Mass balance closer of 98% for pretreated GB confirmed the reliability of SAAP. - Abstract: A comprehensive study was carried out to assess the effectiveness of solar assisted alkali pretreatment (SAAP) on garden biomass (GB). The pretreatment efficiency was assessed based on lignocellulose degradation, conversion of cellulose into reducing sugars, changes in the ultra-structure and functional groups of lignocellulose and impact on the crystallinity of cellulose, etc. SAAP was found to be efficient for the removal of lignin and hemicellulose that facilitated enzymatic hydrolysis of cellulose. FTIR and XRD studies provided details on the effectiveness of SAAP on lignocellulosic moiety and crystallinity of cellulose. Scanning electron microscopic analysis showed ultra-structural disturbances in the microfibrils of GB as a result of pretreatment. The mass balance closer of 97.87% after pretreatment confirmed the reliability of SAAP pretreatment. Based on the results, it is concluded that SAAP is not only an efficient means of pretreatment but also economical as it involved no energy expenditure for heat generation during pretreatment

  11. Development of an innovative polygeneration process in hybrid solar-biomass system for combined power, cooling and desalination

    International Nuclear Information System (INIS)

    Sahoo, U.; Kumar, R.; Pant, P.C.; Chaudhary, R.

    2017-01-01

    Highlights: • Heat utilization from solar and biomass resources are considered for hybridization. • Modeling of polygeneration process in hybrid solar-biomass power plant is considered. • Thermodynamic evaluation are performed to identify the effect of various parameters. • Primary Energy Saving of polygeneration process is determined. - Abstract: In the polygeneration process simultaneous production of power, vapor absorption refrigeration (VAR) cooling and multi-effect humidification and dehumidification (MEHD) desalination system from different heat sources in hybrid solar-biomass (HSB) system with higher energy efficiency take place. It is one of the solutions to fulfill energy requirements from renewable sources and also helps in the reduction of carbon dioxide emissions. The VAR cooling system operates using the extracted heat taken from turbine and condenser heat of the VAR cooling system is used in desalination system for production of drinking water as per demand requirement. Though the production of electricity decreases due to extraction of heat from turbine for VAR cooling and desalination, the complete system meets the energy requirements & increases the primary energy savings (PES). The thermodynamic evaluation and optimization of HSB system in polygeneration process for combined power, cooling and desalination is investigated to identify the effects of various operating parameters. Primary energy savings (PES) of polygeneration process in HSB system is achieved to 50.5%. The energy output is increased to 78.12% from this system as compared to simple power plant.

  12. Steps towards modern trends in district heating

    Directory of Open Access Journals (Sweden)

    Vasek Lubomir

    2017-01-01

    Full Text Available This paper focuses on new trends in district heating a cooling (DHC area and algorithms allowing incorporating new technologies and performing optimal control. Classical district heating usually means huge source (as heating plant and set of pipes which transfer heat energy through a medium, mostly water, across whole town and chilled water is returning back to the plant. Let’s imagine a modern city where buildings are consuming only a fraction of the energy contrary to what buildings required in the past. And especially during sunny or windy days, they have energy to spare. Around of such modern city is not only the one big heating plant, but perhaps solar and wind farms, waste incinerators, industrial companies with energy surpluses. Simply in this modern city are dozens, perhaps hundreds of small energy producers that share pipe network or at least part of it. In such a district energy system, production planning is more difficult. And not only production, modern houses with minimal heat loss and data connections also allow to plan consumption more effectively. The aim is to achieve the best solution evaluated by the objective function, usually determined by minimizing the production and distribution costs and providing meets the needs of energy consumers. The method presented in this paper is based on a simulation using the proposed holonic distributed model. This model also introduces the idea of general prosumers strategy, where all active elements within the modern DHC system are represented by prosumer objects. The prosumers are perceived as objects able to actively participate in the planning and realization of the production and consumption of energy. It is assumed that the general behaviour of the object in DHC is the same, no matter how they differ in size and design. Thus, all the objects are defined by two characteristics - the ability to produce and consume. The model based on this basic principle, of course, with the most

  13. Initiative for local district heating. New chances for municipal utilities. Boundary conditions for the heat market; Initiative Nahwaerme. Neue Chancen fuer Stadtwerke. Rahmenbedingungen fuer den Waermemarkt

    Energy Technology Data Exchange (ETDEWEB)

    Koenig, Michael [K.Group GmbH, Muenchen (Germany). Bereich Nachhaltige Energieversorgung und Stadtentwicklung

    2009-06-15

    In the regulated market, municipal utilities are forced to find new fields of activity. The heat market offers good chances. For example, local district heating grids can be established, independent power generation can be encouraged, and new services can be offered which may increase customer loyalty. The district heating initiative of the Baden-Wuerttemberg Minister of the Environment was launched early in 2009 with the intention to offer valuable assistance to the municipal utilities. (orig.)

  14. Solar heating - status and strategy. Research, development and demonstration; Solvarme - status og strategi. Forskning, udvikling og demonstration

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2007-05-15

    The Danish Energy Authority has prepared research and development strategies for a number of energy technologies, including solar heating. This report presents an inventory of solar heating and proposes a strategy for further development. The report has been prepared by a number of important stakeholders in the Danish solar heating area. The inventory part of the report includes most solar heating technologies, however, emphasis is on technologies which have had or are expected to become important for exploitation in Denmark. The strategy part of the report proposes prioritized areas in research, development and demonstration based on international trends and Danish strong and weak points, which are: 1) centralized solar heating supply, district heating, 2) individual solar heating supply in connection with development and construction of buildings, building integration, and finally 3) product development of solar collectors. (BA)

  15. Experimental Study of the Performance of Air Source Heat Pump Systems Assisted by Low-Temperature Solar-Heated Water

    Directory of Open Access Journals (Sweden)

    Jinshun Wu

    2013-01-01

    Full Text Available Due to the low temperatures, the heating efficiency of air source heat pump systems during the winter is very low. To address this problem, a low-temperature solar hot water system was added to a basic air source heat pump system. Several parameters were tested and analyzed. The heat collection efficiency of the solar collector was analyzed under low-temperature conditions. The factors that affect the performance of the heat pumps, such as the fluid temperature, pressure, and energy savings, were analyzed for cases where the solar energy auxiliary heat pump and the air source heat pump are used independently. The optimal heating temperature and the changes in the fluid temperature were determined. The influence of the compression ratio and the coefficient of performance (COP were investigated theoretically. The results revealed the parameters that are important to the performance of the system. Several measures for improving the COP of the heat pump units are provided for other applications and future research.

  16. Swedish district heating - owners, prices and profitability

    International Nuclear Information System (INIS)

    Andersson, Sofie; Werner, S.

    2001-01-01

    Owners, prices and profitability are examined in this report for 152 Swedish district heating companies during 1999. Only public information available has been used: Prices from a national annual consumer study, energy supplied, lengths of district heating pipes installed, and average prices for energy supplied. These companies are responsible for 96 % of all district heat supplied in Sweden. District heating systems owned by municipalities were responsible for 65 % of all district heat supply, while the share of power companies was 34 %. Other private owners accounted for 1 %. Only 12 % of the board members are women and more than 40 % of the companies have no woman in the board. The prices gathered by the annual consumer study are good estimates of the price level of district heating in Sweden. The average revenues are only 4,1 % lower than the effective average of prices gathered. Price of district heating decrease with size and market share. Use of combined heat and power plants decrease prices slightly. Lower prices with size can mainly be explained by lower energy supply costs. Calculated rates of return in relation to calculated replacement values increase slightly by size and are almost independent of age and market share. The purport of these conclusions is that the district heating companies share the cost reduction from size with their customers, while the whole benefit from high market shares is repaid to the customers. Calculated rates of return vary among the owner groups examined. Lower rates are accepted by municipalities, while power companies have higher rates at the average costs used. Total replacement costs for the 152 companies has been estimated to 89 billion Swedish crowns or 10 billion Euro. Only correlation analyses using one dimension have been used in this study. A higher degree of quality can be obtained by using multi-dimensional analyses

  17. Potential utilization of biomass in production of electricity, heat and transportation fuels including energy combines - Regional analyses and examples; Potentiell avsaettning av biomassa foer produktion av el, vaerme och drivmedel inklusive energikombinat - Regionala analyser och raekneexempel

    Energy Technology Data Exchange (ETDEWEB)

    Ericsson, Karin; Boerjesson, Paal

    2008-01-15

    The objective of this study is to analyse how the use of biomass may increase in the next 10-20 years in production of heat, electricity and transportation fuels in Sweden. In these analyses, the biomass is assumed to be used in a resource and cost efficient way. This means for example that the demand for heat determines the potential use of biomass in co-generation of heat and electricity and in energy combines, and that the markets for by-products determine the use of biomass in production of certain transportation fuels. The economic conditions are not analysed in this study. In the heat and electricity production sector, we make regional analyses of the potential use of biomass in production of small-scale heat, district heat, process heat in the forest industry and electricity produced in co-generation with heat in the district heating systems and forest industry. These analyses show that the use of biomass in heat and electricity production could increase from 87 TWh (the use in 2004/2005, excluding small-scale heat production with firewood) to between 113 TWh and 134 TWh, depending on the future expansion of the district heating systems. Geographically, the Stockholm province accounts for a large part of the potential increase owing to the great opportunities for increasing the use of biomass in production of district heat and CHP in this region. In the sector of transportation fuels we applied a partly different approach since we consider the market for biomass-based transportation fuels to be 'unconstrained' within the next 10-20 years. Factors that constrain the production of these fuels are instead the availability of biomass feedstock and the local conditions required for achieving effective production systems. Among the first generation biofuels this report focuses on RME and ethanol from cereals. We estimate that the domestic production of RME and ethanol could amount to up to 1.4 TWh/y and 0.7-3.8 TWh/y, respectively, where the higher figure

  18. A Feasibility Study on District Heating and Cooling Business Using Urban Waste Heat

    Energy Technology Data Exchange (ETDEWEB)

    Kim, Sang Joon; Choi, Byoung Youn; Lee, Kyoung Ho; Lee, Jae Bong [Korea Electric Power Research Institute, Taejon (Korea, Republic of); Yoo, Jae In; Yoon, Jae Ho; Oh, Myung Do; Park, Moon Su; Kang, Han Kee; Yoo, Kyeoung Hoon; Bak, Jong Heon; Kim, Sun Chang; Park, Heong Kee; Bae, Tae Sik [Korea Academy of Industrial Technology, Seoul (Korea, Republic of)

    1996-12-31

    Investigation of papers related to waste heat utilization using heat pump. Estimate of various kinds of urban waste heat in korea. Investigation and study on optimal control of district heating and cooling system. Prediction of energy saving and environmental benefits when the urban waste heat will be used as heat source and sink of heat pump for district heating and cooling. Estimation of economic feasibility on district heating and cooling project utilizing urban waste heat. (author). 51 refs., figs

  19. Boise geothermal district heating system

    Energy Technology Data Exchange (ETDEWEB)

    Hanson, P.J.

    1985-10-01

    This document describes the Boise geothermal district heating project from preliminary feasibility studies completed in 1979 to a fully operational system by 1983. The report includes information about the two local governments that participated in the project - the City of Boise, Idaho and the Boise Warm Springs Water District. It also discusses the federal funding sources; the financial studies; the feasibility studies conducted; the general system planning and design; design of detailed system components; the legal issues involved in production; geological analysis of the resource area; distribution and disposal; the program to market system services; and the methods of retrofitting buildings to use geothermal hot water for space heating. Technically this report describes the Boise City district heating system based on 170/sup 0/F water, a 4000 gpm production system, a 41,000 foot pipeline system, and system economies. Comparable data are also provided for the Boise Warm Springs Water District. 62 figs., 31 tabs.

  20. A renewable energy scenario for Aalborg Municipality based on low-temperature geothermal heat, wind power and biomass

    DEFF Research Database (Denmark)

    Østergaard, Poul Alberg; Mathiesen, Brian Vad; Möller, Bernd

    2010-01-01

    Aalborg Municipality, Denmark, wishes to investigate the possibilities of becoming independent of fossil fuels. This article describes a scenario for supplying Aalborg Municipality’s energy needs through a combination of low-temperature geothermal heat, wind power and biomass. Of particular focus...... in the scenario is how low-temperature geothermal heat may be utilised in district heating (DH) systems. The analyses show that it is possible to cover Aalborg Municipality’s energy needs through the use of locally available sources in combination with significant electricity savings, heat savings, reductions...... in industrial fuel use and savings and fuel-substitutions in the transport sector. With biomass resources being finite, the two marginal energy resources in Aalborg are geothermal heat and wind power. If geothermal heat is utilised more, wind power may be limited and vice versa. The system still relies...

  1. Experimental performance analysis on a direct-expansion solar-assisted heat pump water heater

    International Nuclear Information System (INIS)

    Li, Y.W.; Wang, R.Z.; Wu, J.Y.; Xu, Y.X.

    2007-01-01

    A direct expansion solar assisted heat pump water heater (DX-SAHPWH) experimental set-up is introduced and analyzed. This DX-SAHPWH system mainly consists of 4.20 m 2 direct expansion type collector/evaporator, R-22 rotary-type hermetic compressor with rated input power 0.75 kW, 150 L water tank with immersed 60 m serpentine copper coil and external balance type thermostatic expansion valve. The experimental research under typical spring climate in Shanghai showed that the COP of the DX-SAHPWH system can reach 6.61 when the average temperature of 150 L water is heated from 13.4 deg. C to 50.5 deg. C in 94 min with average ambient temperature 20.6 deg. C and average solar radiation intensity 955 W/m 2 . And the COP of the DX-SAHPWH system is 3.11 even if at a rainy night with average ambient temperature 17.1 deg. C. The seasonal average value of the COP and the collector efficiency was measured as 5.25 and 1.08, respectively. Through exergy analysis for each component of the DX-SAHPWH system, it can be calculated that the highest exergy loss occurs in the compressor, followed by collector/evaporator, condenser and expansion valve, respectively. Further more, some methods are suggested to improve the thermal performance of each component and the whole DX-SAHPWH system

  2. Heat pipes for ground heating and cooling

    Energy Technology Data Exchange (ETDEWEB)

    Vasiliev, L L

    1988-01-01

    Different versions of heat pipe ground heating and cooling devices are considered. Solar energy, biomass, ground stored energy, recovered heat of industrial enterprises and ambient cold air are used as energy and cold sources. Heat pipe utilization of air in winter makes it possible to design accumulators of cold and ensures deep freezing of ground in order to increase its mechanical strength when building roadways through the swamps and ponds in Siberia. Long-term underground heat storage systems are considered, in which the solar and biomass energy is accumulated and then transferred to heat dwellings and greenhouses, as well as to remove snow from roadways with the help of heat pipes and solar collectors.

  3. District heating from a community perspective : the Aboriginal experience

    Energy Technology Data Exchange (ETDEWEB)

    Wapachee, L. [Ouje-Bougoumou First Nation, Ouje-Bougoumou, PQ (Canada)

    2010-07-01

    This presentation discussed an alternative energy system that was incorporated into the planning and development of a new permanent village for the Ouje-Bougoumou Cree. The history of the Ouje-Bougoumou Cree people and its involvement with industry and governmental bodies were described at length. To provide for the long-term financial requirements of the community in a manner in harmony with Cree environmental philosophy, an appropriate alternative energy system was incorporated into the village architecture. Biomass district heating is an alternative energy system that uses a single source of energy to heat the community's houses and buildings. In this case, sawdust fuel is used to heat water, which is pumped through underground pipes to heat buildings before it cycles back to the plant for reheating. This system converts a waste product into usable energy, capturing and recycling energy while replacing conventional sources, such as oil, gas, or hydroelectricity, and creating local employment. Heat is the largest portion of the community's energy requirement. 11 figs., 1 tab.

  4. Thermodynamic performance analysis and optimization of a solar-assisted combined cooling, heating and power system

    International Nuclear Information System (INIS)

    Wang, Jiangjiang; Lu, Yanchao; Yang, Ying; Mao, Tianzhi

    2016-01-01

    This study aims to present a thermodynamic performance analysis and to optimize the configurations of a hybrid combined cooling, heating and power (CCHP) system incorporating solar energy and natural gas. A basic natural gas CCHP system containing a power generation unit, a heat recovery system, an absorption cooling system and a storage tank is integrated with solar photovoltaic (PV) panels and/or a heat collector. Based on thermodynamic modeling, the thermodynamic performance, including energy and exergy efficiencies, under variable work conditions, such as electric load factor, solar irradiance and installation ratio, of the solar PV panels and heat collector is investigated and analyzed. The results of the energy supply side analysis indicate that the integration of solar PV into the CCHP system more efficiently improves the exergy efficiency, whereas the integration of a solar heat collector improves the energy efficiency. To match the building loads, the optimization method combined with the operation strategy is employed to optimize the system configurations to maximize the integrated benefits of energy and economic costs. The optimization results of demand–supply matching demonstrate that the integration of a solar heat collector achieves a better integrated performance than the solar PV integration in the specific case study. - Highlights: • Design a CCHP system integrated with solar PV and heat collector. • Present the energy and exergy analyses under variable work conditions. • Propose an optimization method of CCHP system for demand-supply matching.

  5. Is Swedish district heating operating on an integrated market? – Differences in pricing, price convergence, and marketing strategy between public and private district heating companies

    International Nuclear Information System (INIS)

    Åberg, M.; Fälting, L.; Forssell, A.

    2016-01-01

    The deregulation of the Swedish electricity market in 1996 made it possible to operate municipal district heating commercially. Until that time district heating had been organized mainly as municipal utilities. After 1996 district heating is instead expected to function on a market. In competitive and integrated markets, prices are expected to be equal, or converging. To find out if district heating operates on an integrated market the differences in price levels, price convergence, price strategy, and business goals, among municipal, private and state owned district heating companies are investigated. Price statistics was used along with results from a questionnaire that was answered by representatives for 109 Swedish district heating companies. The results show that prices among district heating systems do not converge significantly and that variations in prices among municipal systems are larger than among private and state owned systems. Furthermore, despite the fact that district heating is supposed to be commercial, a vast majority of district heating companies apply cost-based pricing and not market pricing. The municipal companies give priority to political goals before financial goals. The conclusion is that a Swedish integrated market for heat has not yet evolved, and some district heating price-controlling mechanism is necessary. - Highlights: • Price statistics and owner type data were used along with results from a questionnaire. • Results show that prices among district heating systems do not converge. • Municipal district heating companies still apply cost-based pricing to a large extent. • District heating companies are not operating on an integrated market for heat. • Some price-controlling mechanism for district heating is necessary.

  6. A novel syngas-fired hybrid heating source for solar-thermal applications: Energy and exergy analysis

    International Nuclear Information System (INIS)

    Pramanik, Santanu; Ravikrishna, R.V.

    2016-01-01

    Highlights: • Biomass-derived syngas as a hybrid energy source for solar thermal power plants. • A novel combustor concept using rich-catalytic and MILD combustion technologies. • Hybrid energy source for a solar-driven supercritical CO 2 -based Brayton cycle. • Comprehensive energetic and exergetic analysis of the combined system. - Abstract: A hybrid heating source using biomass-derived syngas is proposed to enable continuous operation of standalone solar thermal power generation plants. A novel, two-stage, low temperature combustion system is proposed that has the potential to provide stable combustion of syngas with near-zero NO x emissions. The hybrid heating system consists of a downdraft gasifier, a two-stage combustion system, and other auxiliaries. When integrated with a solar cycle, the entire system can be referred to as the integrated gasification solar combined cycle (IGSCC). The supercritical CO 2 Brayton cycle (SCO 2 ) is selected for the solar cycle due to its high efficiency. The thermodynamic performance evaluation of the individual unit and the combined system has been conducted from both energy and exergy considerations. The effect of parameters such as gasification temperature, biomass moisture content, equivalence ratio, and pressure ratio is studied. The efficiency of the IGSCC exhibited a non-monotonic behavior. A maximum thermal efficiency of 36.5% was achieved at an overall equivalence ratio of 0.22 and pressure ratio of 2.75 when the gasifier was operating at T g = 1073 K with biomass containing 20% moisture. The efficiency increased to 40.8% when dry biomass was gasified at a temperature of 973 K. The exergy analysis revealed that the maximum exergy destruction occurred in the gasification system, followed by the combustion system, SCO 2 cycle, and regenerator. The exergy analysis also showed that 8.72% of the total exergy is lost in the exhaust; however, this can be utilized for drying of the biomass.

  7. Integration of biomass fast pyrolysis and precedent feedstock steam drying with a municipal combined heat and power plant

    International Nuclear Information System (INIS)

    Kohl, Thomas; Laukkanen, Timo P.; Järvinen, Mika P.

    2014-01-01

    Biomass fast pyrolysis (BFP) is a promising pre-treatment technology for converting biomass to transport fuel and in the future also for high-grade chemicals. BFP can be integrated with a municipal combined heat and power (CHP) plant. This paper shows the influence of BFP integration on a CHP plant's main parameters and its effect on the energetic and environmental performance of the connected district heating network. The work comprises full- and part-load operation of a CHP plant integrated with BFP and steam drying. It also evaluates different usage alternatives for the BFP products (char and oil). The results show that the integration is possible and strongly beneficial regarding energetic and environmental performance. Offering the possibility to provide lower district heating loads, the operation hours of the plant can be increased by up to 57%. The BFP products should be sold rather than applied for internal use as this increases the district heating network's primary energy efficiency the most. With this integration strategy future CHP plants can provide valuable products at high efficiency and also can help to mitigate global CO 2 emissions. - Highlights: • Part load simulation of a cogeneration plant integrated with biomas fast pyrolysis. • Analysis of energetic and environmental performance. • Assessment of different uses of the pyrolysis products

  8. Assessment of R290 as a possible alternative to R22 in direct expansion solar assisted heat pumps

    Directory of Open Access Journals (Sweden)

    Paradeshi Lokesh

    2017-01-01

    Full Text Available In this paper, the energy performance of a direct expansion solar assisted heat pump has been experimentally assessed with R290 as an alternative to R22 to meet the requirements of Kigali agreement. The experiments have been performed at Calicut climatic conditions (latitude of 11.15° N, longitude of 75.49° E during the winter climates of 2016. The performance parameters such as, compressor power consumption, condenser heating capacity, energy performance ratio, and solar energy input ratio were evaluated for energy performance comparison. The results showed that, R290 has 6.8% higher energy performance ratio when compared to R22, with 11% reduction in compressor power consumption. Moreover, R290 has negligible global warming impact and zero ozone depletion potential when compared to R22. The effect of wind speed, collector area, ambient temperature, and solar insolation on the system performance found to be with an average value of 0.85%, 12%, 2.5%, and 4.5% for the selected refrigerants, respectively.

  9. Co-sponsored second quarter progress review conference on district heating

    Energy Technology Data Exchange (ETDEWEB)

    None

    1980-01-01

    A summary of the progress review conference on district heating and cooling systems is presented. The agenda and lists of speakers and attendees are presented. A history of district heating and some present needs and future policies are given and an excerpt from the National District Heating Program Strategy (DOE, March 1980) is included. Following the presentation, District Heating and Cooling Systems Program, by Alan M. Rubin, a fact sheet on DOE's Integrated Community Energy Systems Program and information from an oral presentation, District Heating and Cooling Systems for Communities Through Power Plant Retrofit Distribution Network, are given. The Second Quarterly Oral Report to the US DOE on the District Heating and Cooling Project in Detroit; the executive summary of the Piqua, Ohio District Heating and Cooling Demonstration Project; the Second Quarterly Report of the Moorehead, Minnesota District Heating Project; and the report from the Moorehead, Minnesota mayor on the Hot Water District Heating Project are presented.

  10. Integration of space heating and hot water supply in low temperature district heating

    DEFF Research Database (Denmark)

    Elmegaard, Brian; Ommen, Torben Schmidt; Markussen, Michael

    2016-01-01

    District heating may supply many consumers efficiently, but the heat loss from the pipes to the ground is a challenge. The heat loss may be lowered by decreasing the network temperatures for which reason low temperature networks are proposed for future district heating. The heating demand...... of the consumers involves both domestic hot water and space heating. Space heating may be provided at low temperature in low energy buildings. Domestic hot water, however, needs sufficient temperatures to avoid growth of legionella. If the network temperature is below the demand temperature, supplementary heating...... is required by the consumer. We study conventional district heating at different temperatures and compare the energy and exergetic efficiency and annual heating cost to solutions that utilize electricity for supplementary heating of domestic hot water in low temperature district heating. This includes direct...

  11. Geothermal direct-heat utilization assistance. Quarterly progress report, April--June 1993

    Energy Technology Data Exchange (ETDEWEB)

    1993-08-01

    Progress is reported on the following R&D activities: evaluation of lineshaft turbine pump problems, geothermal district heating marketing strategy, and greenhouse peaking analysis. Other activities are reported on technical assistance, technology transfer, and the geothermal progress monitor.

  12. Upscaling a district heating system based on biogas cogeneration and heat pumps

    NARCIS (Netherlands)

    van Leeuwen, Richard Pieter; Fink, J.; Smit, Gerardus Johannes Maria; de Wit, Jan B.

    2015-01-01

    The energy supply of the Meppel district Nieuwveense landen is based on biogas cogeneration, district heating, and ground source heat pumps. A centrally located combined heat and power engine (CHP) converts biogas from the municipal wastewater treatment facility into electricity for heat pumps and

  13. Sustainability analysis. Development of various indicators of sustainability for technical environmental analysis and evaluation of local heat supply networks on the basis of regenerative energies in comparison to fossil energy sources

    International Nuclear Information System (INIS)

    Hehenberger-Risse, Diana

    2013-06-01

    The aim of this thesis is to define indicators to evaluate local heat supply systems based on renewable energy compared to fossil energy reference scenarios. With these indicators a assessment matrix was developed as a planning instrument for the realization of sustainable and energy-efficient local heat supply systems. Further inferences from single projects on regions can be done. In these thesis a method was developed to assess the sustainability of local heat supply systems with the focus on ecology under consideration of economically and social aspects. This method uses a set of indicators composed of Input-, Output-, Efficiency- and Balance indicators. To realize advancement in comparison to present situations, an environmental quality target to advance the environmental impacts of minimum 75% was defined. For the developing and application of the indicators different examples from projects and scenarios of combined heat production from Biomass, Biogas, Solar heat combined with near-surface geothermal storage; geothermal energy and fossil peakload supply were calculated. These scenarios were related to a basis fossil energy scenario. Overall, the two district heating projects Speichersdorf and Mitterteich were compared. In this case, the project Speichersdorf with different coverage areas and decrease heat densities was investigated. The lengths of electrical grid of two areas are 10,828 m and 6,027 m. Those were opposed to the biomass district-heating project Mitterteich with a grid length of 360 m and a higher heat density decrease. Furthermore, a scenario for heat supply was designed and calculated using geothermal plant operating in duplicate to provide heat to the large coverage area for the storage project village. The calculation of the various processes and scenarios was performed with the program GEMIS 4.8 based on the total heat generated (final energy) by the respective supply type. The study examined the main system components; boilers, solar heat

  14. Make the heat hotter. - marketing district heating to households in detached houses

    Energy Technology Data Exchange (ETDEWEB)

    Sernhed, Kerstin; Pyrko, Jurek

    2008-09-15

    For district heating (DH) companies, to expand in low heat density areas such as detached houses, it is essential to obtain a high rate of connections to the district-heating network in order to enhance the cost effectiveness. Marketing district heating to house owners is, however, a fairly different matter from selling it to customers in industrial, commercial, and multi-family buildings. Suitable market strategies need to be developed and the need for information about potential customers' preferences and attitudes are of great importance since the house-owners often constitute a heterogeneous group where different households have different requirements. This paper investigates a case of one Swedish district heating company's marketing activities and expansion strategies in a single family house area where the customers were offered conversion of their direct resistive electric heating (DEH) into district heating (DH). 88 out of 111 houses were converted in 2002. Four years later, interviews were carried out with 23 of the households in the area, both with those who had accept-ed the district heating offer and those who had not. The study shows that apart from the economic aspects, thermal comfort, aesthetics and practicalities also affected the buying decision. Since the different economic aspects of the offer were complex, it was very difficult for the households to make a strictly rational economical decision. Statistical analysis confirmed that variables such as age, type of household and energy use level could, to some extent, be related to the decision to convert from electric heating to district heating. Timing, low prices and the total solutions presented to the households were crucial factors in the success of the marketing strategy.

  15. New waste heat district heating system with combined heat and power based on absorption heat exchange cycle in China

    International Nuclear Information System (INIS)

    Sun Fangtian; Fu Lin; Zhang Shigang; Sun Jian

    2012-01-01

    A new waste heat district heating system with combined heat and power based on absorption heat exchange cycle (DHAC) was developed to increase the heating capacity of combined heat and power (CHP) through waste heat recovery, and enhance heat transmission capacity of the existing primary side district heating network through decreasing return water temperature by new type absorption heat exchanger (AHE). The DHAC system and a conventional district heating system based on CHP (CDH) were analyzed in terms of both thermodynamics and economics. Compared to CDH, the DHAC increased heating capacity by 31% and increased heat transmission capacity of the existing primary side district heating network by 75%. The results showed that the exergetic efficiency of DHAC was 10.41% higher and the product exergy monetary cost was 36.6¥/GJ less than a CHD. DHAC is an effective way to increase thermal utilization factor of CHP, and to reduce district heating cost. - Highlights: ► Absorption heat pumps are used to recover waste heat in CHP. ► Absorption heat exchanger can reduce exergy loss in the heat transfer process. ► New waste heat heating system (DHAC) can increase heating capacity of CHP by 31%. ► DHAC can enhance heat transmission capacity of the primary pipe network by 75%. ► DHAC system has the higher exergetic efficiency and the better economic benefit.

  16. Integration of Space Heating and Hot Water Supply in Low Temperature District Heating

    DEFF Research Database (Denmark)

    Elmegaard, Brian; Ommen, Torben Schmidt; Markussen, Michael

    2014-01-01

    pipes, where the water is at the highest temperature. The heat loss may be lowered by decreasing the temperatures in the network for which reason low temperature networks are proposed as a low loss solution for future district heating. However, the heating demand of the consumers involve both domestic......District heating makes it possible to provide heat for many consumers in an efficient manner. In particular, district heating based on combined heat and power production is highly efficient. One disadvantage of district heating is that there is a significant heat loss from the pipes...... to the surrounding ground. In larger networks involving both transmission and distribution systems, the heat loss is most significant from the distribution network. An estimate is that about 80-90 % of the heat loss occurs in the distribution system. In addition, the heat loss is naturally highest from the forward...

  17. Performance Analysis of a Hybrid District Heating System

    DEFF Research Database (Denmark)

    Mikulandric, Robert; Krajačić, Goran; Duic, Neven

    2015-01-01

    Hybridisation of district heating systems can contribute to more efficient heat generation through cogeneration power plants or through the share increase of renewable energy sources in total energy consumption while reducing negative aspects of particular energy source utilisation. In this work......, the performance of a hybrid district energy system for a small town in Croatia has been analysed. Mathematical model for process analysis and optimisation algorithm for optimal system configuration has been developed and described. The main goal of the system optimisation is to reduce heat production costs....... Several energy sources for heat production have been considered in 8 different simulation cases. Simulation results show that the heat production costs could be reduced with introduction of different energy systems into an existing district heating system. Renewable energy based district heating systems...

  18. Renewables for Heating and Cooling

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2007-07-01

    This timely report examines the technologies, current markets and relative costs for heat and cold production using biomass, geothermal and solar-assisted systems. It evaluates a range of national case studies and relevant policies. Should the successful and more cost-effective policies be implemented by other countries, then the relatively untapped economic potential of renewable energy heating and cooling systems could be better realised, resulting in potential doubling of the present market within the next few years.

  19. Primary energy consumption of the dwelling with solar hot water system and biomass boiler

    International Nuclear Information System (INIS)

    Berković-Šubić, Mihaela; Rauch, Martina; Dović, Damir; Andrassy, Mladen

    2014-01-01

    Highlights: • Methodology for determing delivered and primary energy is developed. • Conventional and solar hot water system are analyzed. • Influence of system components, heat losses and energy consumption is explored. • Savings when using solar system in delivered energy is 30% and in primary 75%. • Dwelling with higher Q H,nd has 60% shorter payback period. - Abstract: This paper presents a new methodology, based on the energy performance of buildings Directive related European norms. It is developed to overcome ambiguities and incompleteness of these standards in determining the delivered and primary energy. The available procedures from the present “Algorithm for determining the energy demands and efficiency of technical systems in buildings”, normally used for energy performance certification of buildings, also allow detailed analyzes of the influence of particular system components on the overall system energy efficiency. The calculation example is given for a Croatian reference dwelling, equipped with a solar hot water system, backed up with a biomass boiler for space heating and domestic hot water purposes as a part of the dwelling energy performance certification. Calculations were performed for two cases corresponding to different levels of the dwelling thermal insulation with an appropriate heating system capacity, in order to investigate the influence of the building heat losses on the system design and energy consumption. The results are compared against those obtained for the conventional system with a gas boiler in terms of the primary energy consumption as well as of investment and operating costs. These results indicate great reduction in both delivered and primary energy consumption when a solar system with biomass boiler is used instead of the conventional one. Higher savings are obtained in the case of the dwelling with higher energy need for space heating. Such dwellings also have a shorter payback period than the ones with

  20. District heating in Italy: Extent of use

    International Nuclear Information System (INIS)

    Sacchi, E.

    1992-01-01

    The Author surveys the trend that has been established over the last two decades in the use of district heating in Italy. Comparison with the European situation reveals that Italy is lagging behind. The reason for this the Author states is the Italian public's aversion to unknown risks involved in the utilization of innovative technologies associated with cogeneration/district heating (current preference is given to autonomous methane fuelled building space heating systems), and the current opinion of some misinformed public administrations that cogeneration/district heating plants are too costly. Citing the successful campaign by the natural gas industry to promote the public acceptance of methane as a safe, readily available and competitively priced energy source, he suggests that similar efforts be made to have the public also accept cogeneration (with methane fired gas turbines)/district heating as being safe and environmentally, as well as, economically beneficial

  1. Solar heating and cooling system installed at Leavenworth, Kansas

    Science.gov (United States)

    1980-01-01

    A solar heating and cooling is described which is designed to furnish 90 percent of the overall heating load, 70 percent of the cooling load and 100 percent of the domestic hot water load. The building has two floors with a total of 12,000 square feet gross area. The system has 120 flat-plate liquid solar panels with a net area of 2,200 square feet. Five 3 ton Arkla solar assisted absorption units provide the cooling, in conjunction with a 3,000 gallon chilled water storage tank. Two 3,000 gallon storage tanks are provided with one designated for summer use, whereas both tanks are utilized during winter.

  2. Thermodynamic performance analysis of a fuel cell trigeneration system integrated with solar-assisted methanol reforming

    International Nuclear Information System (INIS)

    Wang, Jiangjiang; Wu, Jing; Xu, Zilong; Li, Meng

    2017-01-01

    Highlights: • Propose a fuel cell trigeneration system integrated with solar-assisted methanol reforming. • Optimize the reaction parameters of methanol steam reforming. • Present the energy and exergy analysis under design and off-design work conditions. • Analyze the contributions of solar energy to the trigeneration system. - Abstract: A solar-assisted trigeneration system for producing electricity, cooling, and heating simultaneously is an alternative scheme to improve energy efficiency and boost renewable energy. This paper proposes a phosphoric acid fuel cell trigeneration system integrated with methanol and steam reforming assisted by solar thermal energy. The trigeneration system consists of a solar heat collection subsystem, methanol steam reforming subsystem, fuel cell power generation subsystem, and recovered heat utilization subsystem. Their respective thermodynamic models are constructed to simulate the system input/output characteristics, and energy and exergy efficiencies are employed to evaluate the system thermodynamic performances. The contribution of solar energy to the system is analyzed using solar energy/exergy share. Through the simulation and analysis of methanol and steam reforming reactions, the optimal reaction pressure, temperature, and methanol to water ratio are obtained to improve the flow rate and content of produced hydrogen. The thermodynamic simulations of the trigeneration system show that the system energy efficiencies at the summer and winter design work conditions are 73.7% and 51.7%, while its exergy efficiencies are 18.8% and 26.1%, respectively. When the solar radiation intensity is different from the design work condition, the total energy and exergy efficiencies in winter decrease approximately by 4.7% and 2.2%, respectively, due to the decrease in solar heat collection efficiency. This proposed novel trigeneration system complemented by solar heat energy and methanol chemical energy is favorable for improving the

  3. Environmental issues and competitiveness of district heating systems

    International Nuclear Information System (INIS)

    Kypreos, S.

    1991-01-01

    The advantages of district heating systems are evaluated in competition to individual heating for the Swiss markets. The preservation of the environmental quality on the national (clean air concept) and global scale (Toronto recommendation) is formulated as constraint of the energy system. The implications of these constraints for the economic competition of district heating is evaluated. The study estimates the evolution of energy demand in the heating markets and shortly describes the technical possibilities in satisfying demand by a set of conventional heating systems, systems using renewable energy sources, energy conservation measures and district heating systems based on conventional or nuclear energy sources. The main conclusion is that small capacity nuclear district heating systems, if acceptable, could enhance the flexibility of the Swiss energy system in respect to CO 2 control. (author) 3 figs., 4 tabs., 9 refs

  4. National energy policies: Obstructing the reduction of global CO2 emissions? An analysis of Swedish energy policies for the district heating sector

    International Nuclear Information System (INIS)

    Difs, Kristina

    2010-01-01

    The effect of national energy policies on a local Swedish district heating (DH) system has been studied, regarding the profitability of new investments and the potential for climate change mitigation. The DH system has been optimised regarding three investments: biomass-fuelled CHP (bio CHP), natural gas-fuelled combined cycle CHP (NGCC CHP) and biomass-fuelled heat-only boiler (bio HOB) in two scenarios (with or without national taxes and policy instruments). In both scenarios EU's tradable CO 2 emission permits are included. Results from the study show that when national policies are included, the most cost-effective investment option is the bio CHP technology. However, when national taxes and policy instruments are excluded, the DH system containing the NGCC CHP plant has 30% lower system cost than the bio CHP system. Regardless of the scenario and when coal condensing is considered as marginal electricity production, the NGCC CHP has the largest global CO 2 reduction potential, about 300 ktonne CO 2 . However, the CO 2 reduction potential is highly dependent on the marginal electricity production. Demonstrated here is that national policies such as tradable green certificates can, when applied to DH systems, contribute to investments that will not fully utilise the DH systems' potential for global CO 2 emissions reductions. - Research highlights: →Swedish energy policies are promoting biomass fuelled electricity generating technologies over efficient fossil fuel electricity generating technologies. →An efficient fossil fuel technology like the natural gas combine cycle CHP technology with high power-to-heat ratio has potential to reduce the global CO 2 emissions more than a biomass fuelled electricity generating technology. →Swedish energy policies such as tradable green certificates for renewable electricity can, when applied to district heating systems, contribute to investments that will not fully utilise the district heating systems potential for

  5. The situation of district heating, district cooling and energy supply in Hungary

    International Nuclear Information System (INIS)

    Sigmond, Gy.

    2009-01-01

    District heating represents with 650.000 heated dwellings approximately 15% of the Hungarian residential heating market. Since 1990 there is stagnation at the number of connected dwellings because erection of large settlements with prefab buildings has been stopped, and latter ones represent more than 75% of the dwelling heating market. During the same period, residential heat demand shrunk by 33%, because metering of hot water consumption resulted in changing consumer habits, and because of slowly but step by step refurbishment of buildings and heating systems. In Hungary district heating is present in all large and most of the medium size cities, in 92 cities together. Out of them, there is also a single village with a local district heating system, which heats more than 60% of cottages. The capacity os systems is spreading to a large extent. Approximately 36-36% of all heated dwellings are in Budapest and in 10 large cities in the country, while 148 of the total 202 systems have less than 10 MW capacities. In the fuel structure of district heating it is characteristic the overwhelming role of natural gas consumption, which has exceeded 80% already. Only a few numbers of heating power plants are fuelled by crown coal. The use of renewables is growing continuous, but, together with waste and waste energy, it amounts merely 8% of the total fuel use. Oil consumption is negligible. Currently the most promising DH-market is the service sector (public buildings and commercial consumers). DH-companies can sell their surplus supply capacities on the competitive market. Residential market can be preserved only with better legal conditions and with improving of demand side management. The industrial heat market can be gained when the erection of new power plants will be harmonized with industrial development in the frame of territorial planning. District cooling is just at the beginning in Hungary. Many new commercial and office buildings are erected with air conditioning

  6. Local business models for district heat production; Kaukolaemmoen paikalliset liiketoimintamallit

    Energy Technology Data Exchange (ETDEWEB)

    Hakala, L.; Pesola, A.; Vanhanen, J.

    2012-12-15

    Local district heating business, outside large urban centers, is a profitable business in Finland, which can be practiced with several different business models. In addition to the traditional, local district heating business, local district heat production can be also based on franchising business model, on integrated service model or on different types of cooperation models, either between a local district heat producer and industrial site providing surplus heat or between a local district heat producer and a larger district heating company. Locally available wood energy is currently utilized effectively in the traditional district heating business model, in which a local entrepreneur produces heat to consumers in the local area. The franchising model is a more advanced version of the traditional district heating entrepreneurship. In this model, franchisor funds part of the investments, as well as offers centralized maintenance and fuel supply, for example. In the integrated service model, the local district heat producer offers also energy efficiency services and other value-added services, which are based on either the local district heat suppliers or his partner's expertise. In the cooperation model with industrial site, the local district heating business is based on the utilization of the surplus heat from the industrial site. In some cases, profitable operating model approach may be a district heating company outsourcing operations of one or more heating plants to a local entrepreneur. It can be concluded that all business models for district heat production (traditional district heat business model, franchising, integrated service model, cooperative model) discussed in this report can be profitable in Finnish conditions, as well for the local heat producer as for the municipality - and, above all, they produce cost-competitive heat for the end-user. All the models were seen as viable and interesting and having possibilities for expansion Finland

  7. Biomass District Heat System for Interior Rural Alaska Villages

    Energy Technology Data Exchange (ETDEWEB)

    Wall, William A.; Parker, Charles R.

    2014-09-01

    Alaska Village Initiatives (AVI) from the outset of the project had a goal of developing an integrated village approach to biomass in Rural Alaskan villages. A successful biomass project had to be ecologically, socially/culturally and economically viable and sustainable. Although many agencies were supportive of biomass programs in villages none had the capacity to deal effectively with developing all of the tools necessary to build a complete integrated program. AVI had a sharp learning curve as well. By the end of the project with all the completed tasks, AVI developed the tools and understanding to connect all of the dots of an integrated village based program. These included initially developing a feasibility model that created the capacity to optimize a biomass system in a village. AVI intent was to develop all aspects or components of a fully integrated biomass program for a village. This meant understand the forest resource and developing a sustainable harvest system that included the “right sized” harvest equipment for the scale of the project. Developing a training program for harvesting and managing the forest for regeneration. Making sure the type, quality, and delivery system matched the needs of the type of boiler or boilers to be installed. AVI intended for each biomass program to be of the scale that would create jobs and a sustainable business.

  8. Waste heat of HTR power stations for district heating

    International Nuclear Information System (INIS)

    Bonnenberg, H.; Schlenker, H.V.

    1975-01-01

    The market situation, the applied techniques, and the transport, for district heating in combination with HTR plants are considered. Analysis of the heat market indicates a high demand for heat at temperatures between 100 and 150 0 C in household and industry. This market for district heating can be supplied by heat generated in HTR plants using two methods: (1) the combined heat and power generation in steam cycle plants by extracting steam from the turbine, and (2) the use of waste heat of a closed gas turbine cycle. The heat generation costs of (2) are negligible. The cost for transportation of heat over the average distance between existing plant sites and consumer regions (25 km) are between 10 and 20% of the total heat price, considering the high heat output of nuclear power stations. Comparing the price of heat gained by use of waste heat in HTR plants with that of conventional methods, considerable advantages are indicated for the combined heat and power generation in HTR plants. (author)

  9. Analysis of a feasible trigeneration system taking solar energy and biomass as co-feeds

    International Nuclear Information System (INIS)

    Zhang, Xiaofeng; Li, Hongqiang; Liu, Lifang; Zeng, Rong; Zhang, Guoqiang

    2016-01-01

    Highlights: • A feasible trigeneration system is proposed to generate power, heating and cooling. • The steam for biomass gasification process is provided by solar energy. • The thermodynamic properties of the proposed system are investigated. • Effects of ER and SBR on gasification process is presented. • The sensitivity of the economic performance of trigeneration system is evaluated. - Abstract: The trigeneration systems are widely used owing to high efficiency, low greenhouse gas emission and high reliability. Especially, those trigeneration systems taking renewable energy as primary input are paid more and more attention. This paper presents a feasible trigeneration system, which realizes biomass and solar energy integrating effective utilization according to energy cascade utilization and energy level upgrading of chemical reaction principle. In the proposed system, the solar energy with mid-and-low temperature converted to the chemical energy of bio-gas through gasification process, then the bio-gas will be taken as the fuel for internal combustion engine (ICE) to generate electricity. The jacket water as a byproduct generated from ICE is utilized in a liquid desiccant unit for providing desiccant capacity. The flue gas is transported into an absorption chiller and heat exchanger consequently, supplying chilled water and domestic hot water. The thermodynamic performance of the trigeneration system was investigated by the help of Aspen plus. The results indicate that the overall energy efficiency and the electrical efficiency of the proposed system in case study are 77.4% and 17.8%, respectively. The introduction of solar energy decreases the consumption of biomass, and the solar thermal energy input fraction is 8.6%. In addition, the primary energy saving ratio and annual total cost saving ratio compared with the separated generation system are 16.7% and 25.9%, respectively.

  10. Thermoeconomic optimization of a solar-assisted heat pump based on transient simulations and computer Design of Experiments

    International Nuclear Information System (INIS)

    Calise, Francesco; Dentice d’Accadia, Massimo; Figaj, Rafal Damian; Vanoli, Laura

    2016-01-01

    Highlights: • A polygeneration system for a residential house is presented. • Hybrid photovoltaic/thermal collectors are used, coupled with a solar-assisted heat pump. • An optimization has been performed. • The system is profitable even in the absence of incentives. • A simple pay-back period of about 5 year is achieved. - Abstract: In the paper, a model for the simulation and the optimization of a novel solar trigeneration system is presented. The plant simulation model is designed to supply electricity, space heating or cooling and domestic hot water for a small residential building. The system is based on a solar field equipped with flat-plate photovoltaic/thermal collectors, coupled with a water-to-water electric heat pump/chiller. The electrical energy produced by the hybrid collectors is entirely supplied to the building. During the winter, the thermal energy available from the solar field is used as a heat source for the evaporator of the heat pump and/or to produce domestic hot water. During the summer, the heat pump operates in cooling mode, coupled with a closed circuit cooling tower, providing space cooling for the building, and the hot water produced by the collectors is only used to produce domestic hot water. For such a system, a dynamic simulation model was developed in TRNSYS environment, paying special attention to the dynamic simulation of the building, too. The system was analyzed from an energy and economic point of view, considering different time bases. In order to minimize the pay-back period, an optimum set of the main design/control parameters was obtained by means of a sensitivity analysis. Simultaneously, a computer-based Design of Experiment procedure was implemented, aiming at calculating the optimal set of design parameters, using both energy and economic objective functions. The results showed that thermal and electrical efficiencies are above 40% and 10%, respectively. The coefficient of performance of the reversible heat

  11. Study of an innovative ejector heat pump-boosted district heating system

    International Nuclear Information System (INIS)

    Zhang, Bo; Wang, Yuanchao; Kang, Lisha; Lv, Jinsheng

    2013-01-01

    An Ejector heat pump-boosted District Heating (EDH) system is proposed to improve the heating capacity of existing district heating systems with Combined Heat and Power (CHP). In the EDH, two ejector heat pumps are installed: a primary heat pump (HP 1 ) at the heating station and a secondary heat pump (HP 2 ) at the heating substation. With the EDH, the low-grade waste heat from circulating cooling water in the CHP is recycled and the temperature difference between the water supply and the return of the primary heating network is increased. A thermodynamic model was provided. An experimental study was carried out for both HP 1 and HP 2 to verify the predicting performance. The results show that the COP of HP 1 can reach 1.5–1.9, and the return water temperature of the primary heating network could be decreased to 35 °C with HP 2 . A typical case study for the EDH was analyzed. -- Highlights: • An ejector heat pump-boosted district heating (EDH) is proposed. • The 1st ejector heat pump in EDH recycles heat from cooling water of the CHP. • The 2nd ejector heat pump in EDH boosts the thermal energy utilization of the primary heating network. • Modeling and experimental studies are presented

  12. District heating for Switzerland - Project development; Projektentwicklung Fernwaerme Schweiz - Abwaermenutzung aus (de)zentralen Quellen der Industrie und Umwelt (Schlussbericht Projektphase 1)

    Energy Technology Data Exchange (ETDEWEB)

    Oppermann, G. [Verband Fernwaerme Schweiz, Niederrohrdorf (Switzerland); Gutzwiller, S. [Eicher und Pauli AG, Planer fuer Energie- und Gebaeudetechnik, Liestal (Switzerland); Mueller, E. A. [EnergieSchweiz fuer Infrastrukturanlagen, Berne (Switzerland)

    2010-05-15

    This final report for 2010 for the Swiss Federal Office of Energy (SFOE) deals with the achievements of the first phase of a project concerning district heating systems in Switzerland. The Swiss District Heating Association (VFS) aims to initiate district heating projects using a four-phase project. Phase 1 involved the identification of potential projects: Locations for the use of waste heat, environmental heat, wood and biomass were identified. The further phases will involve possible investors, the development of concrete projects and, finally, their realisation. The report describes work to be done, the project organisation, presents basic data needed for the project phases, discusses regional planning aspects, reviews aids such as GPS data and 'excel' spread sheets and geographic aspects. Further topics addressed in the report include results achieved, the search for investors and external communication. The report is completed with recommendations and four appendices.

  13. Application of Predictive Control in District Heating Systems

    DEFF Research Database (Denmark)

    Palsson, Olafur Petur; Madsen, Henrik; Søgaard, Henning Tangen

    1993-01-01

    In district heating systems, and in particular if the heat production cakes place at a combined heat and power (CHP) plant, a reasonable control strategy is to keep the supply temperature from the district heating plant as low as possible. However, the control is subject to some restrictions, for...

  14. Current contributions on the technical thermodynamics, power engineering and district heating supply. Special publication; Aktuelle Beitraege zur technischen Thermodynamik, Energietechnik und Fernwaermeversorgung. Sonderveroeffentlichung

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2011-03-15

    Within the special publication under consideration, the German Heat and Power Association (Frankfurt (Main), Federal Republic of Germany) presents the following current contributions on the technical thermodynamics, power engineering and district heating supply: (1) Cellular metallic materials for innovative latent heat accumulator technologies (Jens Meinert); (2) Compressed air storage - technology, chances and problems (Rutger Kretschmer); (3) KWK electricity - Identification and evaluation (Matthias Krause); (4) Investigation of the storage ability of district heating grids and implementation into the optimized planning of heat generators (Sebastian Gross); (5) Autarcic thermal densification to the combined heat and power and cooling production? - A fundamental thermodynamic consideration (Torben Moeller); (6) Modelling of cogeneration power plants - Investigation of the transformation opportunity of existing district heating systems in LowEx grids (Martin Rhein); (7) Discrete building model for the dynamic thermohydraulic simulation of district heating (Dominik Haas); (8) Ventilation and degasification of solar power plants (Karin Ruehling); (9) Integral simulation of district heating with TRNSYS-TUD (Steffen Robbi); (10) Theoretical analyses of return temperatures in building heating networks (Andreas Meinzenbach); (11) Municipal energy efficiency as an important contribution to the reduction of greenhouse gas emissions (Matthias Mischke); (12) Investigation of the latent heat storage system PK 6 for use in air-conditioning installations (Sebastian Pinnau); (13) The role of the thermodynamics in the electromobility (Lars Schinke); (14) Flow and heat transfer in cooling channels with methane (Andre Schlott); (15) Numerical calculations of stoves fired with wooden logs (Ulf Senechal); (16) Supply of thermodynamic substance data for working fluids of power engineering (Hans-Joachim Kretzschmar); (17) Cyclic pipe-ground interaction in solar-thermal heat grids

  15. Solar Heating System with Building-Integrated Heat Storage

    DEFF Research Database (Denmark)

    Heller, Alfred

    1996-01-01

    Traditional solar heating systems cover between 5 and 10% of the heat demand fordomestic hot water and comfort heating. By applying storage capacity this share can beincreased much. The Danish producer of solar heating systems, Aidt-Miljø, markets such a system including storage of dry sand heated...... by PP-pipe heat exchanger. Heat demand is reduced due to direct solar heating, and due to storage. Heat demand is reduced due to direct solar heating, due to storage and due to lower heat losses through the ground. In theory, by running the system flow backwards through the sand storage, active heating...... can be achieved.The objective of the report is to present results from measured system evaluation andcalculations and to give guidelines for the design of such solar heating systems with building integrated sand storage. The report is aimed to non-technicians. In another report R-006 the main results...

  16. Nuclear power for district heating

    International Nuclear Information System (INIS)

    Lyon, R.B.; Sochaski, R.O.

    1975-09-01

    Current district heating trends are towards an increasing use of electricity. This report concerns the evaluation of an alternative means of energy supply - the direct use of thermal energy from CANDU nuclear stations. The energy would be transmitted via a hot fluid in a pipeline over distances of up to 40 km. Advantages of this approach include a high utilization of primary energy, with a consequent reduction in installed capacity, and load flattening due to inherent energy storage capacity and transport delays. Disadvantages include the low load factors for district heating, the high cost of the distribution systems and the necessity for large-scale operation for economic viability. This requirement for large-scale operation from the beginning could cause difficulty in the implementation of the first system. Various approaches have been analysed and costed for a specific application - the supply of energy to a district heating load centre in Toronto from the location of the Pickering reactor station about 40 km away. (author)

  17. Energy and exergy analysis of low temperature district heating network

    International Nuclear Information System (INIS)

    Li, Hongwei; Svendsen, Svend

    2012-01-01

    Low temperature district heating with reduced network supply and return temperature provides better match of the low quality building heating demand and the low quality heating supply from waste heat or renewable energy. In this paper, a hypothetical low temperature district heating network is designed to supply heating for 30 low energy detached residential houses. The network operational supply/return temperature is set as 55 °C/25 °C, which is in line with a pilot project carried out in Denmark. Two types of in-house substations are analyzed to supply the consumer domestic hot water demand. The space heating demand is supplied through floor heating in the bathroom and low temperature radiators in the rest of rooms. The network thermal and hydraulic conditions are simulated under steady state. A district heating network design and simulation code is developed to incorporate the network optimization procedure and the network simultaneous factor. Through the simulation, the overall system energy and exergy efficiencies are calculated and the exergy losses for the major district heating system components are identified. Based on the results, suggestions are given to further reduce the system energy/exergy losses and increase the quality match between the consumer heating demand and the district heating supply. -- Highlights: ► Exergy and energy analysis for low and medium temperature district heating systems. ► Different district heating network dimensioning methods are analyzed. ► Major exergy losses are identified in the district heating network and the in-house substations. ► Advantages to apply low temperature district heating are highlighted through exergy analysis. ► The influence of thermal by-pass on system exergy/energy performance is analyzed.

  18. State and development prospects of district heating in the FRG

    International Nuclear Information System (INIS)

    Buch, A.

    1975-12-01

    The study outlines the state of district heating, investigates the preconditions of its increased application and determines the thus obtainable saving in energy consumption. The heat consumption in homes, the energy use and the types of heating for room heating and hot water supply, the covering of the demand for district heating, design of a district heating supply, the regional planning and the production costs of district heating are individually considered. The results are shown clearly in tables, maps and and graphs. (HR/LH) [de

  19. Economic and environmental efficiency of district heating plants

    DEFF Research Database (Denmark)

    Agrell, Per J.; Bogetoft, Peter

    2005-01-01

    heat, have arbitrary valuation.This study concerns the most developed European district heating and cogeneration system, the Danish.By assessing environmental and economic ef¿ciency, the impact of governmental, market and managerial imperfections are estimated.The principal methodological base......District heating, the conversion of primary energy into distributed thermal energy and possible electric energy, is a challenge to regulate.In addition to the ever present asymmetric information in any suf¿ciently complex activity, some of the inputs for district heating, such as excess process...

  20. Heat planning for fossil-fuel-free district heating areas with extensive end-use heat savings: A case study of the Copenhagen district heating area in Denmark

    International Nuclear Information System (INIS)

    Harrestrup, M.; Svendsen, S.

    2014-01-01

    The Danish government plans to make the Danish energy system to be completely free of fossil fuels by 2050 and that by 2035 the energy supply for buildings and electricity should be entirely based on renewable energy sources. To become independent from fossil fuels, it is necessary to reduce the energy consumption of the existing building stock, increase energy efficiency, and convert the present heat supply from fossil fuels to renewable energy sources. District heating is a sustainable way of providing space heating and domestic hot water to buildings in densely populated areas. This paper is a theoretical investigation of the district heating system in the Copenhagen area, in which heat conservation is related to the heat supply in buildings from an economic perspective. Supplying the existing building stock from low-temperature energy resources, e.g. geothermal heat, might lead to oversized heating plants that are too expensive to build in comparison with the potential energy savings in buildings. Long-term strategies for the existing building stock must ensure that costs are minimized and that investments in energy savings and new heating capacity are optimized and carried out at the right time. - Highlights: • We investigate how much heating consumption needs to be reduced in a district heating area. • We examine fossil-fuel-free supply vs. energy conservations in the building stock. • It is slightly cost-beneficial to invest in energy renovation from today for a societal point of view. • It is economically beneficial for district heating companies to invest in energy renovations from today. • The cost per delivered heat unit is lower when energy renovations are carried out from today

  1. 15 Years of R&D in Central Solar Heating in Denmark

    DEFF Research Database (Denmark)

    Heller, Alfred

    2000-01-01

    Danish R&D activities during the last two decades in the field of Central Solar Heating Plants and Thermal Energy Storage Technologies are presented. The most relevant central solar heating plants (CSHPs), with and without seasonal storage, are examined and essential experiences highlighted....... The Saltum and Ry plants represent the type of CSHPs with preheating the return stream of a district heating net and no storage involved. The Marstal plant represents an alternative approach, connecting the CSHP to the delivery pipe for summer operation. Here the plant involves short-term storage...... and the application of variable flow that lead to novelties in the control strategy. The plant is described and experiences are analysed. The presented cases show that the technology, under special conditions, can be economically competitive with other heating technologies. Under normal conditions, public funding...

  2. Challenges in Smart Low-Temperature District Heating Development

    DEFF Research Database (Denmark)

    Li, Hongwei; Wang, Stephen Jia

    2014-01-01

    Previous research and development shows that low temperature district heating (LTDH) system is economic feasible for low energy buildings and buildings at sparse areas. Coupling with reduced network temperature and well-designed district heating (DH) networks, LTDH can reduce network heat loss by...

  3. Simulation of the thermal performance of a hybrid solar-assisted ground-source heat pump system in a school building

    Science.gov (United States)

    Androulakis, N. D.; Armen, K. G.; Bozis, D. A.; Papakostas, K. T.

    2018-04-01

    A hybrid solar-assisted ground-source heat pump (SAGSHP) system was designed, in the frame of an energy upgrade study, to serve as a heating system in a school building in Greece. The main scope of this study was to examine techniques to reduce the capacity of the heating equipment and to keep the primary energy consumption low. Simulations of the thermal performance of both the building and of five different heating system configurations were performed by using the TRNSYS software. The results are presented in this work and show that the hybrid SAGSHP system displays the lower primary energy consumption among the systems examined. A conventional ground-source heat pump system has the same primary energy consumption, while the heat pump's capacity is double and the ground heat exchanger 2.5 times longer. This work also highlights the contribution of simulation tools to the design of complex heating systems with renewable energy sources.

  4. The radiation safety assessment of the heating loop of district heating reactors

    International Nuclear Information System (INIS)

    Liu Yuanzhong

    1993-01-01

    The district heating reactors are used to supply heating to the houses in cities. The concerned problems are whether the radioactive materials reach the heated houses through heating loop, and whether the safety of the dwellers can be ensured. In order to prevent radioactive materials getting into the heated houses, the district heating reactors have three loops, namely, primary loop, intermediate loop, and heating loop. In the paper, the measures of preventing radioactive materials getting into the heating loop are presented, and the possible sources of the radioactivity in the water of the intermediate loop and the heating loop are given. The regulatory aim limit of radioactive concentration in the water of the intermediate loop is put forward, which is 18.5 Bq/l. Assuming that specific radioactivity of the water of contaminated intermediate loop is up to 18.5 Bq/l, the maximum concentration of radionuclides in water of the heating loop is calculated for the normal operation and the accident of district heating reactor. The results show that the maximum possible concentration is 5.7 x 10 -3 Bq/l. The radiation safety assessment of the heating loop is made out. The conclusions are that the district heating reactors do not bring any harmful impact to the dwellers, and the safety of the dwellers can be safeguarded completely

  5. Guidelines for District Heating Substations

    Energy Technology Data Exchange (ETDEWEB)

    2009-07-15

    The present guidelines contain a set of recommendations focusing on planning, installation, use and maintenance of district heating (DH) substations within district heating systems throughout Europe. The recommendations were developed in order to enable readers to develop well-functioning substations and an effective heat and domestic warm water delivery. These guidelines are intended to give the most effective overall solutions for various parts of the customer installation. The guidelines are not meant to specify the different components of the substation such as meters or heat exchangers. The guidelines deal with a wide variety of issues concerning both present systems of today and district heating systems of the future. Specific handling and maintenance recommendations are mainly focused on present modern systems but are also intended to cover the future situation as much as is feasible. For this reason, certain existing systems are not dealt with in these guidelines. For instance, these guidelines do not cover steam systems, systems with temperatures exceeding 110 deg C and pressure levels above 1.6 MPa. The guidelines include a chapter on the heat meter, as the meter and especially the meter installation is always installed simultaneously with the rest of the substation. These guidelines aim to provide best-practice and easy-to-handle recommendations for: - those who are responsible for relations between district heating utilities and customers; - those who own or maintain a building connected to the district heating network; - those who manufacture, plan, purchase, test and install substations. These guidelines do not deal with investment or cost aspects, but in general, Euroheat and Power recommends looking at the lifetime cost of all components of the substation, instead of investment costs alone. An example of this is provided in Chapter 7.8. The Guidelines were developed based on the most optimal operating principles of substations and meters

  6. Snow melting system with electric heating using photovoltaic power generation; Solar yusetsuko

    Energy Technology Data Exchange (ETDEWEB)

    Sasaki, M; Fujita, S; Kaga, T; Koyama, N [Hachinohe Institute of Technology, Aomori (Japan)

    1996-10-27

    This paper clarifies the solar characteristics in Hachinohe district, to investigate a possibility of the snow melting system with electric heating using solar energy. Power demand for snow melting, power generated by the photovoltaic (PV) array, area of PV array, and working conditions of the system, as to temperature, precipitation and snowfall, were investigated. The percentage of sunshine is 44% in Hachinohe district, which has more fortunate natural condition for utilizing solar radiation compared with that of 20% in Aomori prefecture. The intensity of solar radiation in winter from December to March is around 500 W/m{sup 2} in average, which is equivalent to the quantity of solar radiation, around 2 kWh/m{sup 2} a day. When assuming that snow on the road surface is frozen at the snowfall under the air temperature below -3{degree}C, the occurrence frequency is 50% during January and February in Hachinohe district, which means one frozen day for two days and is equivalent to the occurrence frequency of frozen days, 34% in average during winter. The electric application ratio is 0.34 at the maximum in winter. That is, days of 34% for one month are required for snow melting. 3 figs., 3 tabs.

  7. Large heat storage tank for load management nd implementation of ambient heat. District heating networks based on combined heat and power; Grosswaermespeicher zum Lastmanagement und zur Einbindung von Umweltenergie. Auf KWK basierende Fernwaermenetze

    Energy Technology Data Exchange (ETDEWEB)

    Gross, Sebastian; Rhein, Martin; Ruehling, Karin [Technische Universitaet Dresden (Germany). Inst. fuer Energietechnik

    2013-06-15

    The district heating based on combined heat and power is a transitional technology on the way to the supply of Germany with renewable energy. In the next years, this transitional technology can only be maintained and expanded when marketability is given. Therefore an appropriate combination has to be found from investment measures. Together with new aspects in the management strategy, these investment measures should significantly improve the marketability. The investment measures also aims to enable a primary energetic, appropriate combination of natural gas-based combined heat and power, renewable energy sources (solar thermal energy, ambient heat) and heat pump technology.

  8. Potentialities and type of integrating nuclear heating stations into district heating systems

    International Nuclear Information System (INIS)

    Munser, H.; Reetz, B.; Schmidt, G.

    1978-01-01

    Technical and economical potentialities of applying nuclear heating stations in district heating systems are discussed considering the conditions of the GDR. Special attention is paid to an optimum combination of nuclear heating stations with heat sources based on organic fuels. Optimum values of the contribution of nuclear heating stations to such combined systems and the economic power range of nuclear heating stations are estimated. Final considerations are concerned with the effect of siting and safety concepts of nuclear heating stations on the structure of the district heating system. (author)

  9. Spatiotemporal and economic analysis of industrial excess heat as a resource for district heating

    DEFF Research Database (Denmark)

    Bühler, Fabian; Petrović, Stefan; Holm, Fridolin Müller

    2018-01-01

    detailed analysis of the most suitable types of industries and the costs is required, allowing a targeted exploitation of this resource. This work extends the spatial and thermodynamic analysis, to account for the temporal match between industrial excess heat and district heating demands, as well...... as the costs for implementation and operation of the systems. This allows the determination of cost-effective district heating potentials, as well as the analysis of different industries and technological requirements. The results show that the temporal mismatch between excess heat and district heating demand...... and lack of demand, reduces the theoretical substitution potential by almost 30%. If heat storages are introduced, the total potential is reduced by only 10%. A majority of the excess heat can be utilised at socio-economic heating costs lower than the average Danish district heating price and the cost...

  10. Improving district heating in Kiev

    International Nuclear Information System (INIS)

    Salminen, P.

    2000-01-01

    The district heating modernisation project currently under way in Kiev, the capital of the Ukraine, is the largest project of its type financed by the World Bank. The budget for the five-year project is some USD 250 million of which USD 200 million is financed by the World Bank loan. The target of the project is to improve the city's district heating system, which is owned and operated by Kyivenergo. Consultancy services for the Project Implementation Unit are being provided by Electrowatt-Ekono and financed by the Finnish government

  11. Demonstration project in Volgograd on transfer of know-how from the district heating sector in Denmark to Russia. Final report

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1998-08-01

    A demonstration project on district heating know-how has been financed by the Danish Technical Assistance Programme administrated by the Danish Energy Agency. A demonstration project in Volgograd was approved, with a budget of only 200.000 DKK (180.000 Rbl). The administration of the project, from fact finding to the final report, has been very efficient in particular to other technical assistance programmes. Although the total budget is low only around 15% of the manpower has been used on administration. The transfer of specific technical experience can be summarized in the following: Installation of small decentralized heat exchanger units for preparation of hot water; Construction of low-cost decentralized heat exchanger installations for preparation of hot water; Installation of thermostatic valves; Installation of small substations for heating and hot water; Use of drain pumps for draining under constructions of district heating pipes to prevent outside corrosion; Design principles for construction and rehabilitation of concrete duct systems with internal and outside draining; Design principles for preinsulated pipes; Principles for monitoring the quality of supply in a local district heating network at the lowest costs by monitoring the critical differential pressure. (EG)

  12. Comparative analysis of heat pump and biomass boiler for small detached house heating

    Directory of Open Access Journals (Sweden)

    Olkowski Tomasz

    2017-01-01

    Full Text Available The purpose of the work is to answer the question - which of the two selected heat sources is more economically beneficial for small detached house: heat pump or biomass boiler fuelled with wood-pellets? The comparative analysis of these sources was carried out to discuss the issue. First, cost of both, equipment and operation of selected heat systems were analysed. Additionally, CO2 emission levels associated with these heat systems were determined. The comparative analysis of the costs of both considered heat systems showed that equipment cost of heat pump system is considerably bigger than the cost of biomass boiler system. The comparison of annual operation costs showed that heat pump operation cost is slightly lower than operation cost of biomass boiler. The analysis of above results shows that lower operation cost of heat pump in comparison with biomass boiler cost lets qualify heat pump as more economically justified only after 38 years of work. For both analysed devices, CO2 emission levels were determined. The considerations take into account the fact that heat pump consumes electricity. It is mostly generated through combustion of coal in Poland. The results show that in Poland biomass boiler can be described as not only more economically justified system but also as considerably more ecological.

  13. Comparative analysis of heat pump and biomass boiler for small detached house heating

    Science.gov (United States)

    Olkowski, Tomasz; Lipiński, Seweryn; Olędzka, Aneta

    2017-10-01

    The purpose of the work is to answer the question - which of the two selected heat sources is more economically beneficial for small detached house: heat pump or biomass boiler fuelled with wood-pellets? The comparative analysis of these sources was carried out to discuss the issue. First, cost of both, equipment and operation of selected heat systems were analysed. Additionally, CO2 emission levels associated with these heat systems were determined. The comparative analysis of the costs of both considered heat systems showed that equipment cost of heat pump system is considerably bigger than the cost of biomass boiler system. The comparison of annual operation costs showed that heat pump operation cost is slightly lower than operation cost of biomass boiler. The analysis of above results shows that lower operation cost of heat pump in comparison with biomass boiler cost lets qualify heat pump as more economically justified only after 38 years of work. For both analysed devices, CO2 emission levels were determined. The considerations take into account the fact that heat pump consumes electricity. It is mostly generated through combustion of coal in Poland. The results show that in Poland biomass boiler can be described as not only more economically justified system but also as considerably more ecological.

  14. District heating versus local heating - Social supportability

    International Nuclear Information System (INIS)

    Matei, Magdalena; Enescu, Diana; Varjoghie, Elena; Radu, Florin; Matei, Lucian

    2004-01-01

    District heating, DH, is an energy source which can provide a cost-effective, environmentally friendly source of heat and power for cities, but only in the case of well running systems, with reasonable technological losses. The benefits of DH system are well known: environmental friendly, energy security, economic and social advantages. DH already covers 60% of heating and hot water needs in transition economies. Today, 70 % of Russian, Latvian and Belarus homes use DH, and heating accounts for one-third of total Russian energy consumption. Yet a large number of DH systems in the region face serious financial, marketing or technical problems because of the policy framework. How can DH issues be best addressed in national and local policy? What can governments do to create the right conditions for the sustainable development of DH while improving service quality? What policies can help capture the economic, environmental and energy security benefits of co-generation and DH? To address these questions, the International Energy Agency (IEA) hosted in 2002 and 2004 conference focusing on the crucial importance of well-designed DH policies, for exchanging information on policy approaches. The conclusions of the conference have shown that 'DH systems can do much to save energy and boost energy security, but stronger policy measures are needed to encourage wise management and investment. With a stronger policy framework, DH systems in formerly socialist countries could save the equivalent of 80 billion cubic meters of natural gas a year through supply side efficiency improvements. This is greater than total annual natural gas consumption in Italy'. More efficient systems will also decrease costs, reducing household bills and making DH competitive on long-term. This paper presents the issues: -Theoretical benefits of the district heating and cooling systems; - Municipal heating in Romania; - Technical and economic problems of DH systems and social supportability; - How

  15. Innovative system for delivery of low temperature district heating

    OpenAIRE

    Ianakiev, A; Cui, JM; Garbett, S; Filer, A

    2017-01-01

    An innovative low temperature district heating (LTDH) local network is developed in Nottingham, supported by the REMOURBAN project, part of the H2020 Smart City and Community Lighthouse scheme. It was proposed that a branch emanating from the return pipe of the existing district heating system in Nottingham would be created to use low temperature heating for the first time on such scale in the UK. The development is aimed to extract unused heat from existing district heating system and to mak...

  16. Primary energy savings using heat storage for biomass heating systems

    Directory of Open Access Journals (Sweden)

    Mitrović Dejan M.

    2012-01-01

    Full Text Available District heating is an efficient way to provide heat to residential, tertiary and industrial users. The heat storage unit is an insulated water tank that absorbs surplus heat from the boiler. The stored heat in the heat storage unit makes it possible to heat even when the boiler is not working, thus increasing the heating efficiency. In order to save primary energy (fuel, the boiler operates on nominal load every time it is in operation (for the purpose of this research. The aim of this paper is to analyze the water temperature variation in the heat storage, depending on the heat load and the heat storage volume. Heat load is calculated for three reference days, with average daily temperatures from -5 to 5°C. The primary energy savings are also calculated for those days in the case of using heat storage in district heating.[Projekat Ministarstva nauke Republike Srbije, br. TR 33051: The concept of sustainable energy supply of settlements with energy efficient buildings

  17. District heating marketing. Strategies in the heating market. 2. ed.; Fernwaerme-Marketing. Strategien im Waermemarkt

    Energy Technology Data Exchange (ETDEWEB)

    Marschalleck, Helmut [MVV Energie AG, Mannheim (Germany); Arndt, Andreas [EnBW Vertriebs- und Servicegesellschaft, Karlsruhe (Germany); Behm, Norman [Stadtwerke Rostock AG (Germany)] [and others

    2012-07-01

    The assistance in the strategic and operational planning of an individual marketing strategy in the district heating market is the focus of the book under consideration. Starting from the definition of the actual situation (market analysis and marketing potential) and the strategic goal, a marketing concept and a marketing mix (product policy, pricing policy, distribution policy as well as communication policy) is established. Subsequently, the tools of the marketing controlling (incoming orders and turnover, marketing key performance indicators, reporting, marketing audit) are described.

  18. Development, validation and application of a fixed district heating model structure that requires small amounts of input data

    International Nuclear Information System (INIS)

    Aberg, Magnus; Widén, Joakim

    2013-01-01

    Highlights: • A fixed model structure for cost-optimisaton studies of DH systems is developed. • A method for approximating heat demands using outdoor temperature data is developed. • Six different Swedish district heating systems are modelled and studied. • The impact of heat demand change on heat and electricity production is examined. • Reduced heat demand leads to less use of fossil fuels and biomass in the modelled systems. - Abstract: Reducing the energy use of buildings is an important part in reaching the European energy efficiency targets. Consequently, local energy systems need to adapt to a lower demand for heating. A 90% of Swedish multi-family residential buildings use district heating (DH) produced in Sweden’s over 400 DH systems, which use different heat production technologies and fuels. DH system modelling results obtained until now are mostly for particular DH systems and cannot be easily generalised. Here, a fixed model structure (FMS) based on linear programming for cost-optimisaton studies of DH systems is developed requiring only general DH system information. A method for approximating heat demands based on local outdoor temperature data is also developed. A scenario is studied where the FMS is applied to six Swedish DH systems and heat demands are reduced due to energy efficiency improvements in buildings. The results show that the FMS is a useful tool for DH system optimisation studies and that building energy efficiency improvements lead to reduced use of fossil fuels and biomass in DH systems. Also, the share of CHP in the production mix is increased in five of the six DH systems when the heat demand is reduced

  19. Multi-annual planning of investments for heat production. 2009 - 2020 period

    International Nuclear Information System (INIS)

    2005-01-01

    A new Multi-annual Planning of Investments (PPI) for heat production in France has been realized in order to meet the conclusions of the Grenelle Environnement Forum for a better energy efficiency and a larger use of renewable energies. Based on quantitative data (the increase in heat production will reach more than 10 Mtoe by 2020), potential objectives have been assessed for the various heat production sources and techniques: wood, biomass (for buildings, district heating, industry and processes, cogeneration), deep and intermediary geothermal energy, individual heat pumps, individual and collective heat solar systems, biogas, etc. These objectives are said to be ambitious but reachable if every sources and techniques are thoroughly exploited

  20. Solar gasification of biomass: design and characterization of a molten salt gasification reactor

    Science.gov (United States)

    Hathaway, Brandon Jay

    The design and implementation of a prototype molten salt solar reactor for gasification of biomass is a significant milestone in the development of a solar gasification process. The reactor developed in this work allows for 3 kWth operation with an average aperture flux of 1530 suns at salt temperatures of 1200 K with pneumatic injection of ground or powdered dry biomass feedstocks directly into the salt melt. Laboratory scale experiments in an electrically heated reactor demonstrate the benefits of molten salt and the data was evaluated to determine the kinetics of pyrolysis and gasification of biomass or carbon in molten salt. In the presence of molten salt overall gas yields are increased by up to 22%; pyrolysis rates double due to improved heat transfer, while carbon gasification rates increase by an order of magnitude. Existing kinetic models for cellulose pyrolysis fit the data well, while carbon gasification in molten salt follows kinetics modeled with a 2/3 order shrinking-grain model with a pre-exponential factor of 1.5*106 min-1 and activation energy of 158 kJ/mol. A reactor concept is developed based around a concentric cylinder geometry with a cavity-style solar receiver immersed within a volume of molten carbonate salt. Concentrated radiation delivered to the cavity is absorbed in the cavity walls and transferred via convection to the salt volume. Feedstock is delivered into the molten salt volume where biomass gasification reactions will be carried out producing the desired product gas. The features of the cavity receiver/reactor concept are optimized based on modeling of the key physical processes. The cavity absorber geometry is optimized according to a parametric survey of radiative exchange using a Monte Carlo ray tracing model, resulting in a cavity design that achieves absorption efficiencies of 80%-90%. A parametric survey coupling the radiative exchange simulations to a CFD model of molten salt natural convection is used to size the annulus

  1. Solar Process Heat Basics | NREL

    Science.gov (United States)

    Process Heat Basics Solar Process Heat Basics Commercial and industrial buildings may use the same solar technologies-photovoltaics, passive heating, daylighting, and water heating-that are used for residential buildings. These nonresidential buildings can also use solar energy technologies that would be

  2. Model of a thermal energy storage device integrated into a solar assisted heat pump system for space heating

    International Nuclear Information System (INIS)

    Badescu, Viorel

    2003-01-01

    Details about modelling a sensible heat thermal energy storage (TES) device integrated into a space heating system are given. The two main operating modes are described. Solar air heaters provide thermal energy for driving a vapor compression heat pump. The TES unit ensures a more efficient usage of the collected solar energy. The TES operation is modeled by using two non-linear coupled partial differential equations for the temperature of the storage medium and heat transfer fluid, respectively. Preliminary results show that smaller TES units provide a higher heat flux to the heat pump vaporiser. This makes the small TES unit discharge more rapidly during time periods with higher thermal loads. The larger TES units provide heat during longer time periods, even if the heat flux they supply is generally smaller. The maximum heat flux is extracted from the TES unit during the morning. Both the heat pump COP and exergy efficiency decrease when the TES unit length increases. Also, the monthly thermal energy stored by the TES unit and the monthly energy necessary to drive the heat pump compressor are increased by increasing the TES unit length

  3. Kaliningrad regional district heating network 2004-2006. Final report

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2006-06-15

    This report concerns: Kaliningrad Regional District Heating Network project which was implemented from 2004 to 2006. The task of the project was to establish and operate an association for district heating companies in the region in order to transfer and distribute district heating know-how to the sector and through activities strengthen the sector. The long term aim was to contribute to establishment of an association to continue as a real association for the heat supply companies in the region. (au)

  4. Review of the technology for solar gasification of carbonaceous materials

    International Nuclear Information System (INIS)

    Epstein, M.; Spiewak, I.; Funken, K.H.; Ortner, J.

    1994-01-01

    Research has demonstrated the feasibility of solar assisted gasification of carbonaceous materials to form synthesis gas (syngas). The potential feedstocks range from natural gas, residual oil, biomass, and oil-shale to coal. The expected advantages of such processing are yields of syngas with calorific values above those of the carbonaceous feedstocks, syngas quality suited to production of hydrogen, methanol or bulk Fischer-Tropsch fuels, and the ability to process low-grade and waste materials with essentially no emissions to atmosphere other than small amounts of CO 2 . The review provides some background on solar receiver concepts to reach the high temperatures needed for syngas production, the basic chemistry involved, covers applicable experiments that have been reported with solar inputs and with conventional heating, heat transfer processes, process and energy balances, and cost analysis. Approximately 80 references are cited. The authors present their views on the most promising approaches to solar-assisted gasification, the technology development required, and the ultimate benefits of such development and commercialization

  5. Experimental and numerical study of latent heat thermal energy storage systems assisted by heat pipes for concentrated solar power application

    Science.gov (United States)

    Tiari, Saeed

    A desirable feature of concentrated solar power (CSP) with integrated thermal energy storage (TES) unit is to provide electricity in a dispatchable manner during cloud transient and non-daylight hours. Latent heat thermal energy storage (LHTES) offers many advantages such as higher energy storage density, wider range of operating temperature and nearly isothermal heat transfer relative to sensible heat thermal energy storage (SHTES), which is the current standard for trough and tower CSP systems. Despite the advantages mentioned above, LHTES systems performance is often limited by low thermal conductivity of commonly used, low cost phase change materials (PCMs). Research and development of passive heat transfer devices, such as heat pipes (HPs) to enhance the heat transfer in the PCM has received considerable attention. Due to its high effective thermal conductivity, heat pipe can transport large amounts of heat with relatively small temperature difference. The objective of this research is to study the charging and discharging processes of heat pipe-assisted LHTES systems using computational fluid dynamics (CFD) and experimental testing to develop a method for more efficient energy storage system design. The results revealed that the heat pipe network configurations and the quantities of heat pipes integrated in a thermal energy storage system have a profound effect on the thermal response of the system. The optimal placement of heat pipes in the system can significantly enhance the thermal performance. It was also found that the inclusion of natural convection heat transfer in the CFD simulation of the system is necessary to have a realistic prediction of a latent heat thermal storage system performance. In addition, the effects of geometrical features and quantity of fins attached to the HPs have been studied.

  6. Improving the performance of district heating systems by utilization of local heat boosters

    DEFF Research Database (Denmark)

    Falcone, A.; Dominkovic, D. F.; Pedersen, A. S.

    was to evaluate the possibilities to lower the forward temperature of the heat supply in order to reduce the heat losses of the system. Booster heat pumps are introduced to increase the water temperature close to the final users. A Matlab model was developed to simulate the state of the case study DH network...... was set to minimize the system heat losses. * Corresponding author 0303-1 1 This goal was achieved by lowering the forward temperature to 40°C and relying on the installed heat pumps to boost the water temperature to the admissible value needed for the domestic hot water preparation. Depending......District Heating (DH) plays an important role into the Danish energy green transition towards the future sustainable energy systems. The new, 4 th generation district heating network, the so called Low Temperature District Heating (LTDH), tends to lower the supply temperature of the heat down to 40...

  7. District heating and co-generation in Slovenia

    International Nuclear Information System (INIS)

    Hrovatin, Franc; Pecaric, Marko; Perovic, Olgica

    2000-01-01

    Recent development of district heating systems, gasification and co-generation processes in local communities in Slovenia as well as current status, potentials, possibilities and plans for further development in this sphere are presented. The current status presents energy production, distribution and use in district heating systems and in local gas distribution networks. An analysis of the energy and power generated and distributed in district power systems, made with regard to the size of the system, fuel used, type of consumers and the way of production, is given. Growth in different areas of local power systems in the period of last years is included. Potentials in the sphere of electrical energy and heat co-generation were assessed. Some possibilities and experience in heat energy storage are given and trends and plans for further development are introduced. (Authors)

  8. The use of biomass for energy in Sweden. Critical factors and lessons learned

    International Nuclear Information System (INIS)

    Johansson, Bengt; Boerjesson, Paal; Ericsson, Karin; Nilsson, Lars J.; Svenningsson, Per

    2002-08-01

    In this report the development of Swedish biomass use during recent decades is discussed. The relations between biomass supply, biomass demand and various policy initiatives are explored. The objectives are to discuss the most important factors affecting the biomass development and to establish which factors are specific for Swedish conditions and also to identify general factors that are relevant in assessing the possibility of expanding biomass use in different contexts. The focus is on the use of biomass for heat and electricity production. Biomass contributed 14% to the Swedish energy supply in 1999. The major fraction of Swedish biomass is used within the forest industry (63%) and in district heating systems (23%). The remaining fraction is used in small-scale boilers in one- and two family dwellings. Between 1990 and 1999 Swedish bioenergy use (including waste and peat) increased by 44%. During the same period there has been a fourfold increase in the district heating systems. By-products from forestry and the Swedish forest industry dominate the supply of biomass in Sweden, but the importation of biomass increased significantly during the 1990s. A number of factors of various kinds have interacted to bring about the increased use of biomass in Sweden during the past twenty years. These factors can be divided into three categories: structure, policies and actors. The existence of a major forest industry and well-developed district heating systems has enabled a rapid response to strong and standing policy commitments to biomass. The reformation of the taxation system, with the introduction of a high carbon tax on fossil fuels, has led to significantly improved competitiveness for biomass when used for heating purposes.

  9. Nuclear heat for industrial purposes and district heating

    International Nuclear Information System (INIS)

    1974-01-01

    Studies on the various possibilities for the application of heat from nuclear reactors in the form of district heat or process steam for industrial purposes had been made long before the present energy crisis. Although these studies have indicated technical feasibility and economical justification of such utilization, the availability of relatively cheap oil and difficulties in locating a nuclear heat source inside industrial areas did not stimulate much further development. Since the increase of oil prices, the interest in nuclear heat application is reawakened, and a number of new potential areas have been identified. It now seems generally recognized that the heat from nuclear reactors should play an important role in primary energy supply, not only for electricity production but also as direct heat. At present three broad areas of nuclear heat application are identified: Direct heat utilization in industrial processing requiring a temperature above 800 deg. C; Process steam utilization in various industries, requiring a temperature mainly in the range of 200-300 deg. C; Low temperature and waste heat utilization from nuclear power plants for desalination of sea water and district heating. Such classification is mainly related to the type and characteristics of the heat source or nuclear reactor which could be used for a particular application. Modified high temperature reactor types (HTR) are the candidates for direct heat application, while the LWR reactors can satisfy most of the demands for process steam. Production of waste heat is a characteristic of all thermal power plants, and its utilization is a major challenge in the field of power production

  10. Solar assisted heat pump on air collectors: A simulation tool

    Energy Technology Data Exchange (ETDEWEB)

    Karagiorgas, Michalis; Galatis, Kostas; Tsagouri, Manolis [Department of Mechanical Engineering Educators, ASPETE, N. Iraklio, GR 14121 (Greece); Tsoutsos, Theocharis [Environmental Engineering Dept., Technical University of Crete, Technical University Campus, GR 73100, Chania (Greece); Botzios-Valaskakis, Aristotelis [Centre for Renewable Energy Sources (CRES), 19th km Marathon Ave., GR 19001, Pikermi (Greece)

    2010-01-15

    The heating system of the bioclimatic building of the Greek National Centre for Renewable Energy Sources (CRES) comprises two heating plants: the first one includes an air source heat pump, Solar Air Collectors (SACs) and a heat distribution system (comprising a fan coil unit network); the second one is, mainly, a geothermal heat pump unit to cover the ground floor thermal needs. The SAC configuration as well as the fraction of the building heating load covered by the heating plant are assessed in two operation modes; the direct (hot air from the collectors is supplied directly to the heated space) and the indirect mode (warm air from the SAC or its mixture with ambient air is not supplied directly to the heated space but indirectly into the evaporator of the air source heat pump). The technique of the indirect mode of heating aims at maximizing the efficiency of the SAC, saving electrical power consumed by the compressor of the heat pump, and therefore, at optimizing the coefficient of performance (COP) of the heat pump due to the increased intake of ambient thermal energy by means of the SAC. Results are given for three research objectives: assessment of the heat pump efficiency whether in direct or indirect heating mode; Assessment of the overall heating plant efficiency on a daily or hourly basis; Assessment of the credibility of the suggested simulation model TSAGAIR by comparing its results with the TRNSYS ones. (author)

  11. Solar Pond devices: free energy or bioreactors for Artemia biomass production?

    Science.gov (United States)

    Gouveia, Luisa; Sousa, João; Marques, Ana; Tavares, Célia; Giestas, Margarida

    2009-08-01

    enterprise. Finally, the authors suggest a method of producing and collecting Artemia biomass, and of heating a fish larval tank, in an 'ideal' Solar Pond device, profiting from the low investment costs of using a decommissioned salt works.

  12. Comparison of two simulation methods for the technical feasibility of a district heating system using waste heat from a copper plant with thermal storage

    NARCIS (Netherlands)

    Xu, L.; Torrens Galdiz, J.I.; Hensen, J.L.M.

    Prior studies have noted that modelling and simulation approaches provide useful assistance in designing new generation district heating systems to deal with the increasing complexity of technologies. The available models and tools cover wide varieties in terms of technologies, model complexities,

  13. Toward 4th generation district heating

    DEFF Research Database (Denmark)

    Li, Hongwei; Svendsen, Svend; Dalla Rosa, Alessandro

    2014-01-01

    In many countries, district heating (DH) has a key role in the national strategic energy planning. However, tighter legislation on new and future buildings requires much less heating demand which subsequently causes relative high network heat loss. This will make current DH system uneconomical co...

  14. Passive solar heating

    Energy Technology Data Exchange (ETDEWEB)

    Wiberg, K

    1981-11-10

    The present work treats the possibilities for heating according to the passive solar heating method. Problems of 'spatial organization in an energy-saving society' are distinguished from among other social problems. The final delimination of the actual problems under investigation consists of the use of passive solar heating and especially the 'consequences of such solar heating exploitation upon the form and structures' of planning and construction. In the concluding chapter an applied example shows how this method can be used in designing an urban area and what are its limitations. The results indicate the possibilities and difficulties in attempting to transfer this ideal and general method into models and directives for form and structure from which examples of the actual possibilities in practical planning can be given.

  15. Fossil energy versus nuclear, wind, solar and agricultural biomass: Insights from an Italian national survey

    International Nuclear Information System (INIS)

    Cicia, Gianni; Cembalo, Luigi; Del Giudice, Teresa; Palladino, Andrea

    2012-01-01

    In Italy there has been considerable political debate around the new energy policy, which is specifically designed to contribute to climate change mitigation. While there is renewed interest in nuclear energy generation, there has been heated debate concerning wind farms that have rapidly expanded and are dramatically changing the landscape in many rural areas. Finally, interest has also increased in biomass as an energy source. However, in this case, a significant part of the population is worried about landscape change and primary crop reduction. In this study we report the results from a nation-wide survey (=504 households) in Italy undertaken during summer 2009. A Latent Class Choice Experiment was used to quantify household preferences over different energy sources. Our results show that Italian households can be split into three segments with homogeneous preferences. The first segment (35% of the population) shows strong preference for wind and solar energy and dislikes both biomass and nuclear. The second (33% of the population) shows moderate preference for solar and wind energy and, as with the first segment, dislikes both nuclear and biomass. The third (32% of the population) shows a strong preference for green energy (solar, wind and biomass) and is very much against nuclear energy. The three segments were also characterized in terms of household socio-economic characteristics. - Highlights: ► We quantify Italian household preferences over different energy sources. ► Results come from a nation-wide survey undertaken during summer 2009. ► Energy sources tested: fossil fuel, nuclear, wind, solar and agricultural biomass. ► A latent class choice experiment was used. ► Italians can be split into three segments with different energy source preferences.

  16. Numerical simulation of solar-assisted multi-effect distillation (SMED) desalination systems

    KAUST Repository

    Kim, Youngdeuk

    2013-01-01

    We present a simulation model for the transient behavior of solar-assisted seawater desalination plant that employs the evacuated-tube collectors in conjunction with a multieffect distillation plant of nominal water production capacity of 16m3/day. This configuration has been selected due to merits in terms of environment-friendliness and energy efficiency. The solar-assisted multi-effect distillation system comprises 849 m2 of evacuated-tube collectors, 280 m3 water storage tanks, auxiliary heater, and six effects and a condenser. The present analysis employs a baseline configuration, namely; (i) the local solar insolation input (Jeddah, Saudi Arabia), (ii) a coolant flow rate through the headers of collector based on ASHRAE standards, (iii) a heating water demand, and (iv) the augmentation of water temperature by auxiliary when the supply temperature from the solar tank drops below the set point. It is observed that the annual collector efficiency and solar fraction decrease from 57.3 to 54.8% and from 49.4 to 36.7%, respectively, with an increase in the heating water temperature from 80 to 90 °C. The overall water production rate and the performance ratio increase slightly from 0.18 to 0.21 kg/s and from 4.11 to 4.13, respectively. © 2013 Desalination Publications.

  17. Economic assessment of solar and conventional biomass gasification technologies: Financial and policy implications under feedstock and product gas price uncertainty

    International Nuclear Information System (INIS)

    Nickerson, Thomas A.; Hathaway, Brandon J.; Smith, Timothy M.; Davidson, Jane H.

    2015-01-01

    Four configurations of a novel solar-heated biomass gasification facility and one configuration of conventional biomass gasification are analyzed through financial and policy scenarios. The purpose of this study is to determine the potential financial position for varying configurations of a novel technology, as compared to the current state-of-the-art gasification technology. Through the use of project finance and policy scenario development, we assess the baseline breakeven syngas price (normalized against natural gas prices and based upon annual feedstock consumption), the sensitivity of major cost components for the novel facilities, and the implications of policy levers on the economic feasibility of the solar facilities. Findings show that certain solar configurations may compete with conventional facilities on a straightforward economic basis. However, with renewable energy policy levers in place the solar technologies become increasingly attractive options. - Highlights: • We model four solar and one conventional biomass gasification systems. • We assess economic feasibility of these systems with and without policy incentives. • Solar facilities compete with the conventional system in certain scenarios. • Feedstock costs are the largest contributor to system cost sensitivity. • Policy incentives create an economically favorable scenario for solar facilities

  18. Design of serially connected district heating heat pumps utilising a geothermal heat source

    DEFF Research Database (Denmark)

    Jensen, Jonas Kjær; Ommen, Torben Schmidt; Markussen, Wiebke Brix

    2017-01-01

    The design of two heat pumps (HP), connected in series, was investigated for operation in the district heating (DH) network of the Greater Copenhagen area, Denmark. The installation was dimensioned to supply 7.2 MW of heat at a temperature of 85 °C. The heat pumps utilise a geothermal heat source...

  19. The emissions from a space-heating biomass stove

    International Nuclear Information System (INIS)

    Koyuncu, T.; Pinar, Y.

    2007-01-01

    In this paper, the flue gas emissions of carbon monoxide (CO), nitrogen oxides (NO X ), sulphur dioxide (SO 2 ) and soot from an improved space-heating biomass stove and thermal efficiency of the stove have been investigated. Various biomass fuels such as firewood, wood shavings, hazelnut shell, walnut shell, peanut shell, seed shell of apricot (sweet and hot seed type), kernel removed corncob, wheat stalk litter (for cattle and sheep pen), cornhusk and maize stalk litter (for cattle pen) and charcoal were burned in the same space-heating biomass stove. Flue gas emissions were recorded during the combustion period at intervals of 5min. It was seen from the results that the flue gas emissions have different values depending on the characteristics of biomass fuels. Charcoal is the most appropriate biomass fuel for use in the space-heating biomass stoves because its combustion emits less smoke and the thermal efficiency of the stove is approximately 46%. (author)

  20. Sustainability analysis. Development of various indicators of sustainability for technical environmental analysis and evaluation of local heat supply networks on the basis of regenerative energies in comparison to fossil energy sources; Nachhaltigkeitsanalyse. Entwicklung verschiedener Nachhaltigkeitsindikatoren zur umwelttechnischen Analyse und Bewertung von Nahwaermeversorgungsnetzen auf Basis regenerativer Energien im Vergleich zu fossilen Energietraegern

    Energy Technology Data Exchange (ETDEWEB)

    Hehenberger-Risse, Diana

    2013-06-15

    The aim of this thesis is to define indicators to evaluate local heat supply systems based on renewable energy compared to fossil energy reference scenarios. With these indicators a assessment matrix was developed as a planning instrument for the realization of sustainable and energy-efficient local heat supply systems. Further inferences from single projects on regions can be done. In these thesis a method was developed to assess the sustainability of local heat supply systems with the focus on ecology under consideration of economically and social aspects. This method uses a set of indicators composed of Input-, Output-, Efficiency- and Balance indicators. To realize advancement in comparison to present situations, an environmental quality target to advance the environmental impacts of minimum 75% was defined. For the developing and application of the indicators different examples from projects and scenarios of combined heat production from Biomass, Biogas, Solar heat combined with near-surface geothermal storage; geothermal energy and fossil peakload supply were calculated. These scenarios were related to a basis fossil energy scenario. Overall, the two district heating projects Speichersdorf and Mitterteich were compared. In this case, the project Speichersdorf with different coverage areas and decrease heat densities was investigated. The lengths of electrical grid of two areas are 10,828 m and 6,027 m. Those were opposed to the biomass district-heating project Mitterteich with a grid length of 360 m and a higher heat density decrease. Furthermore, a scenario for heat supply was designed and calculated using geothermal plant operating in duplicate to provide heat to the large coverage area for the storage project village. The calculation of the various processes and scenarios was performed with the program GEMIS 4.8 based on the total heat generated (final energy) by the respective supply type. The study examined the main system components; boilers, solar heat

  1. Technical assessment of electric heat boosters in low-temperature district heating based on combined heat and power analysis

    DEFF Research Database (Denmark)

    Cai, Hanmin; You, Shi; Wang, Jiawei

    2018-01-01

    This paper provides a technical assessment of electric heat boosters (EHBs) in low-energy districts. The analysis is based on a hypothetical district with 23 terraced single-family houses supplied by both a lowtemperature district heating (LTDH) network and a low-voltage network (LVN). Two case...

  2. Solar heating and cooling.

    Science.gov (United States)

    Duffie, J A

    1976-01-01

    Solar energy is discussed as an energy resource that can be converted into useful energy forms to meet a variety of energy needs. The review briefly explains the nature of this energy resource, the kinds of applications that can be made useful, and the status of several systems to which it has been applied. More specifically, information on solar collectors, solar water heating, solar heating of buildings, solar cooling plus other applications, are included.

  3. District heating and heat storage using the solution heat of an ammonia/water system

    International Nuclear Information System (INIS)

    Taube, M.; Peier, W.; Mayor, J.C.

    1976-01-01

    The article describes a model for the optimum use of the heat energy generated in a nuclear power station for district heating and heat storage taking account of the electricity and heat demand varying with time. (HR/AK) [de

  4. North–South debate on district heating: Evidence from a household survey

    International Nuclear Information System (INIS)

    Guo, Jin; Huang, Ying; Wei, Chu

    2015-01-01

    There has been a long debate on whether South China should supply district heating for the residential sector, a system that is widely used in North China. The major concern is that it may further accelerate China's energy demand. Using a unique urban household level dataset, the China Residential Energy Consumption Survey (CRECS), we investigate residential energy consumption for heating and examine the energy intensity and energy cost of distributed heating in South China and district heating in North China during the 2012 heating season. Our results show that the total energy consumption for distributed heating system users in southern cities is significantly lower than for users of district heating systems in northern cities. However, when accounting for the heating area and heating season, the distributed heating households in the South consumed 32% more energy and paid 189% higher cost per unit area and per hour, but had lower comfort than district heating users in the North. These findings suggest promoting the district heating market in appropriate areas in South China. This not only can improve residential welfare, but also can indirectly reduce energy consumption and financial burdens. - Highlights: • The debate on whether Southern China apply district heating is present. • The household data in 2012 is used to compare the energy efficient and cost. • South resident use more energy and higher cost but less comfort than North. • Government should not prevent the district heating market.

  5. Improved district heating substation efficiency with a new control strategy

    International Nuclear Information System (INIS)

    Gustafsson, Jonas; Delsing, Jerker; Deventer, Jan van

    2010-01-01

    In this paper, we describe a new alternative control approach for indirectly connected district heating substations. Simulations results showed that the new approach results in an increased ΔT across the substation. Results were obtained for both ideal and non-ideal operation of the system, meaning that less water must be pumped through the district heating network, and a higher overall fuel efficiency can be obtained in the district heating power plants. When a higher fuel efficiency is achieved, the usage of primary fuel sources can be reduced. Improved efficiency also increases the effective heat transfer capacity of a district heating network, allowing more customers to be connected to an existing network without increasing the heating plant or network capacity. Also, if combined heat and power plants are used to produce the heat, the increased ΔT will result in a further improved overall fuel efficiency, as more electricity can be produced with colder cooling water. The idea behind the new control method is to consider the temperature of the water supplying the district heating substation with heat, often referred to as the primary supply temperature. This represents a logical next step, as currently, the only parameter generally taken into account or measured when controlling the temperature level of the radiator circuit is the local outdoor temperature. In this paper we show how the primary supply temperature together with thermodynamic knowledge of the building can be used to maximize the ΔT across the district heating substation.

  6. Investigation on Solar Heating System with Building-Integrated Heat Storage

    DEFF Research Database (Denmark)

    Heller, Alfred

    1996-01-01

    Traditional solar heating systems cover between 5 and 10% of the heat demand fordomestic hot water and comfort heating. By applying storage capacity this share can beincreased much. The Danish producer of solar heating systems, Aidt-Miljø, markets such a system including storage of dry sand heated...... by PP-pipe heat exchanger. Heat demand is reduced due to direct solar heating and due to storage. The storage affects the heat demand passively due to higher temperatures. Hence heat loss is reduced and passive heating is optioned. In theory, by running the system flow backwards, active heating can...... solar collector area of the system, was achieved. Active heating from the sand storage was not observed. The pay-back time for the system can be estimated to be similar to solar heated domestic hot water systems in general. A number of minor improvements on the system could be pointed out....

  7. Simulation of a solar assisted combined heat pump – Organic rankine cycle system

    International Nuclear Information System (INIS)

    Schimpf, Stefan; Span, Roland

    2015-01-01

    Highlights: • Addition of an ORC to a solar thermal and ground source heat pump system. • Reverse operation of the scroll compressor in ORC mode. • Annual simulations for application in a single-family house at three locations. • By introducing the ORC the net electricity demand is reduced by 1–9%. • Over the lifetime of the system savings can cover additional investments. - Abstract: A novel solar thermal and ground source heat pump system that harnesses the excess heat of the collectors during summer by an Organic Rankine Cycle (ORC) is simulated. For the ORC the heat pump process is reversed. In this case the scroll compressor of the heat pump runs as a scroll expander and the working fluid is condensed in the ground heat exchanger. Compared to a conventional solar thermal system the only additional investments for the combined system are a pump, valves and upgraded controls. The goal of the study is to simulate and optimize such a system. A brief overview of the applied models and the evolutionary algorithm for the optimization is given. A system with 12 m 2 of flat plate collectors installed in a single family house is simulated for the locations Ankara, Denver and Bochum. The ORC benefits add up to 20–140 kW h/a, which reduces the net electricity demand of the system by 1–9%. Overall 180–520 € are saved over a period of 20 years, which can be enough to cover the additional investments

  8. Market opening and third party access in district heating networks

    International Nuclear Information System (INIS)

    Soederholm, Patrik; Warell, Linda

    2011-01-01

    The purpose of this paper is to analyse the possible effects of introducing TPA in district heating networks by identifying and scrutinizing a number of possible scenarios for increased competition. The analysis builds on a theoretical discussion of economic efficiency in district heating operations, and the possible impacts on consumer prices of a market opening. An important conclusion is that regulated TPA may have small positive effects on competition, and at the same time it can have a negative impact on the possibility to run the integrated district heating operations in a cost-effective manner. This conclusion stems in part from the observation that most district heating networks are local in scope. Moreover, district heating operations are highly interdependent in, for instance, that the level of the return temperature of the water will affect the efficiency of combined heat and power plants. For these reasons, the introduction of the so-called single-buyer model or, perhaps even more preferable, an extended and more transparent producer market could represent more efficient market designs. Moreover, in networks with clear natural monopoly characteristics an ex ante price regulation must be considered. - Research Highlights: →The paper analyses the possible effects of TPA in district heating networks. → Four possible scenarios for increased competition are identified and scrutinized. → A conclusion is that regulated TPA have only small positive effects on competition. → District heating operations are highly interdependent and separation can be costly.

  9. District heating by the Bohunice nuclear power plant

    International Nuclear Information System (INIS)

    Metke, E.; Skvarka, P.

    1984-01-01

    Technical and economical aspects of district heating by the electricity generating nuclear plants in Czechoslovakia are discussed. As a first stage of the project, 240 MW thermal power will be supplied using bleeding lines steam from the B-2 nuclear power plant at Jaslovske Bohunice to heat up water at a central station to 130 grad C. The maximal thermal power that can be produced for district heating by WWER type reactors with regular condensation turbines is estimated to be: 465 MW for a WWER-440 reactor with two 220 MWe turbines and 950 MW for a WWER-1000 reactor with a Skoda made 1000 MWe turbine using a three-stage scheme to heat up water from 60 grad C to 150 grad C. The use of satelite heating turbines connected to the steam collector is expected to improve the efficiency. District heating needs will de taken into account for siting of the new power plants

  10. Opening of the markets increases the risks of district heating business

    International Nuclear Information System (INIS)

    Silvennoinen, A.

    2001-01-01

    Maintenance of the technical operation conditions of district heating is the main requirement of community to the district heating business. Infrastructure of district heating, including the heat generation and distribution plants, equipment and devices, requires relatively large investments. Total process from fuel purchase to heat delivery does not occur in a closed limited area, but it penetrates the total market area (heat distribution network) and even larger via fuel purchase and transport. E.g. the fuels are combustible and might explode. Oil-spills into the environment may have catastrophic effects. Large leakage of hot district heating water is both environmentally hazardous and forms also a health hazard, and they stop the delivery of district heat. Dominant position on the markets is also followed closely by the authorities. On the other hand competition with other heating forms require efficient operation. The author reviews in the article the basics of risk management, and especially in the district heating business. The risk management process is discussed in the risk analysis and determination of the significance of the risks, the effects of realization of the risks, planning of the measures to be taken to avoid risks, and preparations against the risks

  11. Theoretical and experimental analysis of a solar thermoelectric power generation device based on gravity-assisted heat pipes and solar irradiation

    International Nuclear Information System (INIS)

    Zhang, Zhe; Li, Wenbin; Kan, Jiangming; Xu, Daochun

    2016-01-01

    Highlights: • A technical solution to the power supply of wireless sensor networks is presented. • The low voltage produced by device is boosted from around 1 V to more than 4 V. • An output current and voltage of the device is acquired as 343 mA and 1057 mV. • The device provides output power 362.56 mW in no electricity conditions. • The economic value of device is demonstrated. - Abstract: Solar thermoelectric power generation has been widely used to solve the power supply limitation issue for low-power wireless sensors because of its light weight, high reliability, low cost, lack of noise, and environmental friendliness. A solar thermoelectric power generation system based on gravity-assisted heat pipes and solar radiation is devised in this paper, and its behavior is continuously measured in realistic outdoor circumstances. The effects of key parameters, including solar luminous flux, load resistance, a proportional coefficient, and a relative Seebeck coefficient, are analyzed. Related experimental results show that the device can output a voltage of 1057 mV and an electrical current of 343 mA, resulting in an output power of 362.56 mW. With a stable external energy conversion module under aluminous flux of 7.81 × 10"4 lx, the voltage converted from the nature solar radiation is boosted from 1057 mV to 4.40 V, which meets the rated operating voltage of low power consumption components, such as low-power wireless sensors and ZigBee modules. An economic analysis of the system shows that the solar thermoelectric power generation device is both economically and technically competitive when it is applied in a low-voltage wireless sensor network.

  12. Load Management in District Heating Operation

    OpenAIRE

    Li, Hongwei; Wang, Stephen Jia

    2015-01-01

    Smooth operation of district heating system will avoid installation of expensive peak heat boilers, improve plant partial load performance, increase the system redundancy for further network expansion and improve its resilience to ensuresecurity of supply during severe heating seasons. The peak heating load can be reduced through building demand side management. The building thermal mass can be used to shift the heating supply under the circumstance withoutjeopardizing the consumer thermal co...

  13. Experimental performance analysis and optimization of a direct expansion solar-assisted heat pump water heater

    International Nuclear Information System (INIS)

    Li, Y.W.; Wang, R.Z.; Wu, J.Y.; Xu, Y.X.

    2007-01-01

    In this study, a direct expansion solar-assisted heat pump water heater (DX-SAHPWH) with rated input power 750 W was tested and analyzed. Through experimental research in spring and thermodynamics analysis about the system performance, some suggestions for the system optimization are proposed. Then, a small-type DX-SAHPWH with rated input power 400 W was built, tested and analyzed. Through exergy analysis for each component of DX-SAHPWH (A) and (B), it can be seen that the highest exergy loss occurs in the compressor and collector/evaporator, followed by the condenser and expansion valve, respectively. Furthermore, some methods are suggested to improve the performance of each component, especially the collector/evaporator. A methodology for the design optimization of the collector/evaporator was introduced and applied. In order to maintain a proper matching between the heat pumping capacity of the compressor and the evaporative capacity of the collector/evaporator under widely varying ambient conditions, the electronic expansion valve and variable frequency compressor are suggested to be utilized for the DX-SAHPWH

  14. Biomass heating at East Surrey Hospital: technical evaluation

    Energy Technology Data Exchange (ETDEWEB)

    Landen, R; Rippengal, R

    2000-07-01

    This report provides the results of a detailed evaluation of the proposed biomass heating installation at East Surrey Hospital. It is intended to allow the Trust to make a decision on whether to proceed further with the scheme and, if so, on what basis. Specific areas assessed and reported on include: existing services provision for heating and cooling; technical aspects of the proposed biomass scheme; commercial aspects of the proposed biomass scheme. (author)

  15. Compact seasonal PCM heat storage for solar heating systems

    DEFF Research Database (Denmark)

    Dannemand, Mark

    Space heating of buildings and preparation of domestic hot water accounts for a large part of the society’s energy consumption. Solar radiation is an abundant and renewable energy source which can be harvested by solar collectors and used to cover heating demands in the built environment....... The seasonal availability of solar energy does however not match with the heating demands in buildings which typically are large in winter periods when limited solar energy is available. Heat can be stored over a few days in water stores but continuous heat losses limits the storage periods. The possibility...... of storing heat from summer where solar energy is widely available to winter periods where the heating demands are large, allows for implementing more renewable energy in our energy system. The phase change material (PCM) sodium acetate trihydrate (SAT) melts at 58 °C. The melting process requires...

  16. Korean district heating. Part 2: Investigation of the consumption pattern in a substation at Korea District Heating Corporation at the turn of the year 1994/95

    Energy Technology Data Exchange (ETDEWEB)

    Joensson, Mats; Olsson, Nils

    1996-05-01

    This thesis, which is the second part of two, analyses the consumption pattern and the conditions for district heating in the Republic of Korea at the turn of the year 1994-95. It is based on a study made in Seoul at Korea District Heating Corporation which is the largest district heating utility in Korea. District heating was introduced in the 80s because of the environmental advantages. In 1994 KDHC provided 340 000 households with district heating. KDHC receives most of its thermal energy from combined heat and power plants which use natural gas as fuel. One substation was chosen for the investigation and temperature, flow, and pressure were measured. A typical Korean substation has heat exchangers connected in parallel in only one step and the apartment complexes use floor heating for internal heating. The space heating load shows a linear relation to the outdoor temperature. The hot tap-water consumption shows a highly varying pattern with peak loads in the morning and evening. There were also an oscillating pattern for some of the temperatures and flows caused by poor regulation. DH suits very well to Korea with its climate and the overpopulated cities. KDHC:s expansion will help to make Korea one of the leading countries in modern district heating. 10 refs, 36 figs, 11 tabs

  17. Energy and exergy analysis of low temperature district heating network

    DEFF Research Database (Denmark)

    Li, Hongwei; Svendsen, Svend

    2012-01-01

    is designed to supply heating for 30 low energy detached residential houses. The network operational supply/return temperature is set as 55 °C/25 °C, which is in line with a pilot project carried out in Denmark. Two types of in-house substations are analyzed to supply the consumer domestic hot water demand...... energy/exergy losses and increase the quality match between the consumer heating demand and the district heating supply.......Low temperature district heating with reduced network supply and return temperature provides better match of the low quality building heating demand and the low quality heating supply from waste heat or renewable energy. In this paper, a hypothetical low temperature district heating network...

  18. Application of a temperature selective heat storage tank to a solar system. Part 3. Solar heat collecting system; Ondo sentaku chikunetsuso no solar system eno tekiyo. 3. Shunetsu hoshiki ni tsuite

    Energy Technology Data Exchange (ETDEWEB)

    Kamiya, Y [Kanto Gakuin University, Yokohama (Japan); Kanayama, K [Kitami Institute of Technology, Hokkaido (Japan)

    1996-10-27

    The tank system and tank-less system when the temperature selective heat storage tank is applied to a solar system were considered. In the tank system, the simulation shows that the annual supplementary heat consumption is reduced as the tank capacity becomes lower. The most suitable operating time set for determining the reference time is about five hours in winter and about nine hours in summer. The annual operating time is about 6.5 hours. In the tank-less system, the most suitable minimum flow rate per solar collector area of a heating medium in Tokyo and its districts is 10 L/hm{sup 2} for both three-step flow control and constant flow control. The tank-less system is slightly lower in annual supplementary heat consumption than the tank system. For the three-step flow control, a change in the annual supplementary heat consumption is lower than that in the minimum flow rate. For the constant flow control, however, the annual supplementary heat consumption rapidly increases when the flow rate more decreases than the optimum value. The number of pump start/stop counts for the three-step flow control is less than two times as high as for the constant flow control. 4 refs., 6 figs., 1 tab.

  19. Costs for district heating development. Status 2010; Kostnader for fjernvarmeutbygging. Status 2010

    Energy Technology Data Exchange (ETDEWEB)

    2010-12-15

    The report 'Costs of district heating development' presents the costs for district heating based on bioenergy primarily as base load. The report aims to be a tool for the heating developer to set up the investment budget and implement pilot projects. The project is funded by the Norwegian District Heating with support from Enova SF and implemented in close cooperation with the Norwegian district heating. (AG)

  20. Microwave assisted acid and alkali pretreatment of Miscanthus biomass for biorefineries

    Directory of Open Access Journals (Sweden)

    Zongyuan Zhu

    2015-10-01

    Full Text Available Miscanthus is a major bioenergy crop in Europe and a potential feedstock for second generation biofuels. Thermochemical pretreatment is a significant step in the process of converting lignocellulosic biomass into fermentable sugars. In this work, microwave energy was applied to facilitate NaOH and H2SO4 pretreatments of Miscanthus. This was carried out at 180 ℃ in a monomode microwave cavity at 300 W. Our results show that H2SO4 pretreatment contributes to the breakdown of hemicelluloses and cellulose, leading to a high glucose yield. The maximum sugar yield from available carbohydrates during pretreatment is 75.3% (0.2 M H2SO4 20 Min, and glucose yield is 46.7% under these conditions. NaOH and water pretreatments tend to break down only hemicellulose in preference to cellulose, contributing to high xylose yield. Compared to conventional heating NaOH/H2SO4 pretreatment, 12 times higher sugar yield was obtained by using microwave assisted pretreatment within half the time. NaOH pretreatments lead to a significantly enhanced digestibility of the residue, because the effective removal of lignin and hemicellulose makes cellulose fibres more accessible to cellulases. Morphological study of biomass shows that the tightly packed fibres in the Miscanthus were dismantled and exposed under NaOH condition. We studied sugar degradation under microwave assisted H2SO4 conditions. The results shows that 6-8% biomass was converted into levulinic acid (LA during pretreatment, showing the possibility of using microwave technology to produce LA from biomass. The outcome of this work shows great potential for using microwave in the thermo-chemical pretreatment for biomass and also selective production of LA from biomass.

  1. Solar heating and cooling of buildings

    Science.gov (United States)

    Bourke, R. D.; Davis, E. S.

    1975-01-01

    Solar energy has been used for space heating and water heating for many years. A less common application, although technically feasible, is solar cooling. This paper describes the techniques employed in the heating and cooling of buildings, and in water heating. The potential for solar energy to displace conventional energy sources is discussed. Water heating for new apartments appears to have some features which could make it a place to begin the resurgence of solar energy applications in the United States. A project to investigate apartment solar water heating, currently in the pilot plant construction phase, is described.

  2. Harnessing solar heat

    CERN Document Server

    Norton, Brian

    2013-01-01

    Systems engineered by man to harness solar heat in a controlled manner now include a diverse range of technologies each serving distinctive needs in particular climate contexts. This text covers the breadth of solar energy technologies for the conversion of solar energy to provide heat, either as the directly-used output or as an intermediary to other uses such as power generation or cooling. It is a wholly updated, extended and revised version of “Solar Energy Thermal Technology” first published in 1992. The text draws on the own author’s research and that of numerous colleagues and

  3. Port Graham Community Building Biomass Heating Design Project

    Energy Technology Data Exchange (ETDEWEB)

    Norman, Patrick [Port Graham Village Corporation, Anchorage, AK (United States); Sink, Charles [Chugachmiut, Anchorage, Alaska (United States)

    2015-04-30

    Native Village of Port Graham completed preconstruction activities to prepare for construction and operations of a cord wood biomass heating system to five or more community buildings in Port Graham, Alaska. Project Description Native Village of Port Graham (NVPG) completed preconstruction activities that pave the way towards reduced local energy costs through the construction and operations of a cord wood biomass heating system. NVPG plans include installation of a GARN WHS 3200 Boiler that uses cord wood as fuel source. Implementation of the 700,000 Btu per hour output biomass community building heat utility would heat 5-community buildings in Port Graham, Alaska. Heating system is estimated to displace 85% of the heating fuel oil or 5365 gallons of fuel on an annual basis with an estimated peak output of 600,000 Btu per hour. Estimated savings is $15,112.00 per year. The construction cost estimate made to install the new biomass boiler system is estimated $251,693.47 with an additional Boiler Building expansion cost estimated at $97,828.40. Total installed cost is estimated $349,521.87. The WHS 3200 Boiler would be placed inside a new structure at the old community Water Plant Building site that is controlled by NVPG. Design of the new biomass heat plant and hot water loop system was completed by Richmond Engineering, NVPG contractor for the project. A hot water heat loop system running off the boiler is designed to be placed underground on lands controlled by NVPG and stubbed to feed hot water to existing base board heating system in the following community buildings: 1. Anesia Anahonak Moonin Health and Dental Clinic 2. Native Village of Port Graham offices 3. Port Graham Public Safety Building/Fire Department 4. Port Graham Corporation Office Building which also houses the Port Graham Museum and Head Start Center 5. North Pacific Rim Housing Authority Workshop/Old Fire Hall Existing community buildings fuel oil heating systems are to be retro-fitted to

  4. Evaluation of the performance in the solar assisted heat pump system; Taiyonetsu riyo heat pump system no seino hyoka ni tsuite

    Energy Technology Data Exchange (ETDEWEB)

    Saito, Y [Osaka Institute of Technology, Osaka (Japan)

    1996-10-27

    Performance of a solar heating system with a hydrothermal source heat pump was evaluated and compared with that of a direct solar heating system. The sun-dependency rates ({Sigma}D and {Sigma}H)of the direct system and heat pump (HP)-provided system were expressed as a function of the rate ({alpha}) of the auxiliary heat against the collected heat and as a function of the performance coefficient and {alpha}, respectively. When the sun-dependency rates are compared, it is found that the HP-provided system is the more advantageous when {Sigma}H/{Sigma}D>1. The relationship between the {alpha}`s of the two systems was clarified and computation was performed to compare the sun-dependency rates on condition that the two are equal in the heat collecting area. Although the sun-dependence rate cannot be elevated to 100% in the HP-provided system, it achieves a sun-dependency rate higher than that of the direct system even when the heat collecting area is small. In cases where the building is economically limited, for instance, with respect to the area for solar collector installation, it is advantageous to employ the HP-provided system. 5 figs., 1 tab.

  5. Solar heating and hot water system installed at Southeast of Saline, Unified School District 306, Mentor, Kansas

    Science.gov (United States)

    1979-01-01

    The solar system, installed in a new building, was designed to provide 52 percent of the estimated annual space heating load and 84 percent of the estimated annual potable hot water requirement. The liquid flat plate collectors are ground-mounted and cover a total area of 5125 square feet. The system will provide supplemental heat for the school's closed-loop water-to-air heat pump system and domestic hot water. The storage medium is water inside steel tanks with a capacity of 11,828 gallons for space heating and 1,600 gallons for domestic hot water. The solar heating facility is described and drawings are presented of the completed system which was declared operational in September 1978, and has functioned successfully since.

  6. The Innovative Concept of Cold District Heating Networks: A Literature Review

    Directory of Open Access Journals (Sweden)

    Marco Pellegrini

    2018-01-01

    Full Text Available The development of sustainable and innovative solutions for the production and supply of energy at district level is nowadays one of the main technical challenges. In the past, district heating and cooling networks aimed to achieve greater energy efficiency through the centralization of the energy production process but with relevant losses related to heat transport. Moving towards a higher share of renewables and lower demand of primary energy requires redesign of the energy district networks. The novel concept of cold district heating networks aims to combine the advantages of a centralized energy distribution system with low heat losses in energy supply. This combined effect is achieved through the centralized supply of water at relatively low temperatures (in the range 10–25 °C, which is then heated up by decentralized heat pumps. Moreover, cold district heating networks are also very suitable for cooling delivery, since cold water supplying can be directly used for cooling purposes (i.e., free cooling or to feed decentralized chillers with very high energy efficiency ratio. This paper provides a preliminary literature review of existing cold district heating networks and then qualitatively analyses benefits and drawbacks in comparison with the alternatives currently used to produce heat and cold at district level, including the evaluation of major barriers to its further development.

  7. Nuclear district heating

    International Nuclear Information System (INIS)

    Ricateau, P.

    1976-01-01

    An economic study of nuclear district heating is concerned with: heat production, its transmission towards the area to be served and the distribution management towards the consumers. Foreign and French assessments show that the high cost of now existing techniques of hot water transport defines the competing limit distance between the site and township to be below some fifty kilometers for the most important townships (provided that the fuel price remain stationary). All studies converge towards the choice of a high transport temperature as soon as the distance is of some twenty kilometers. As for fossile energy saving, some new possibilities appear with process heat reactors; either PWR of about 1000MWth for large townships, or pool-type reactors of about 100MWth when a combination with an industrial steam supply occurs [fr

  8. Analysis of Competitiveness and Support Instruments for Heat and Electricity Production from Wood Biomass in Latvia

    Science.gov (United States)

    Klavs, G.; Kudrenickis, I.; Kundzina, A.

    2012-01-01

    Utilisation of renewable energy sources is one of the key factors in a search for efficient ways of reducing the emissions of greenhouse gases and improving the energy supply security. So far, the district heating supply in Latvia has been based on natural gas, with the wood fuel playing a minor role; the same is true for decentralised combined heat-power (CHP) production. The paper describes a method for evaluation of the economic feasibility of heat and electricity production from wood biomass under the competition between different fuel types and taking into account the electricity market. For the simulation, a cost estimation model is applied. The results demonstrate that wood biomass can successfully be utilised for competitive heat production by boiler houses, while for electricity production by CHP utilities it cannot compete on the market (even despite the low prices on wood biomass fuel) unless particular financial support instruments are applied. The authors evaluate the necessary support level and the impact of two main support instruments - the investment subsidies and the feed-in tariff - on the economic viability of wood-fuelled CHP plants, and show that the feed-in tariff could be considered as an instrument strongly affecting the competitiveness of such type CHP. Regarding the feed-in tariff determination, a compromise should be found between the economy-dictated requirement to develop CHP projects concerning capacities above 5 MWel - on the one hand, and the relatively small heat loads in many Latvian towns - on the other.

  9. Korean district heating. Part 1: A general report on Korean district heating 1994/1995; Fjaerrvaerme i Korea. Del 1: En allmaen redovisning av koreansk fjaerrvaerme aarsskiftet 1994/95

    Energy Technology Data Exchange (ETDEWEB)

    Joensson, Mats; Olsson, Nils

    1996-02-01

    This thesis describes the conditions for district heating in the Republic of Korea at the turn of the year 1994-95. It is based on a study made in Seoul at Korea District Heating Corporation, which is the largest district heating utility in Korea. The substations were particularly studied. District heating was introduced in Korea in the 80s because of the environmental advantages. KHDC was established in 1985 and in 1994 they provided 340 000 households with district heating. By the year of 2001 KDHC plans to supply 45% of the heating in Seoul with its 12 million inhabitants. KDHC receives most of its thermal energy from combined heat and power plants that use natural gas as fuel. In 1991 KDHC initiated a collaboration with Ekono of Finland to develop more advanced technology in Korea. Therefore the Finnish standard, which is similar to Swedish standard, has left it`s mark on the Korean district heating technology. Typical for the Korean substation is that the heat exchangers are connected in parallel in only one step. KDHC:s expansion will, within a couple of years, help to make Korea one of the leading countries in modern district heating. 9 refs, 3 figs, 2 tabs

  10. Research programme 'Active Solar Energy Use - Solar Heating and Heat Storage'. Activities and projects 2003

    International Nuclear Information System (INIS)

    Hadorn, J.-C.; Renaud, P.

    2003-01-01

    In this report by the research, development and demonstration (RD+D) programme coordinators the objectives, activities and main results in the area of solar heating and heat storage in Switzerland are presented for 2003. In a stagnating market environment the strategy of the Swiss Federal Office of Energy mainly consists in improving the quality and durability of solar collectors and materials, optimizing combisystems for space heating and domestic hot water preparation, searching for storage systems with a higher energy storage density than in the case of sensible heat storage in water, developing coloured solar collectors for more architectonic freedom, and finalizing a seasonal heat storage project for 100 dwellings to demonstrate the feasibility of solar fractions larger than 50% in apartment houses. Support was granted to the Swiss Testing Facility SPF in Rapperswil as in previous years; SPF was the first European testing institute to perform solar collector labeling according to the new rules of the 'Solar Keymark', introduced in cooperation with the European Committee for Standardization CEN. Several 2003 projects were conducted within the framework of the Solar Heating and Cooling Programme of the International Energy Agency IEA. Computerized simulation tools were improved. With the aim of jointly producing high-temperature heat and electric power a solar installation including a concentrating collector and a thermodynamic machine based on a Rankine cycle is still being developed. Seasonal underground heat storage was studied in detail by means of a validated computer simulation programme. Design guidelines were obtained for such a storage used in the summer time for cooling and in the winter time for space heating via a heat pump: depending on the ratio 'summer cooling / winter heating', cooling requires a cooling machine, or direct cooling without such a machine is possible. The report ends up with the list of all supported RD+D projects

  11. 北方地区应用太阳能辅助土壤源热泵效能分析%Efficiency Analysis of Utilizing Solar-assisted Ground Source Heat Pump in the Northern China

    Institute of Scientific and Technical Information of China (English)

    赵金秀

    2015-01-01

    针对北方寒冷地区气候特点,指出了太阳能辅助土壤源热泵系统相对于单独的土壤源热泵或单独的太阳能应用的技术特点。对北方寒冷地区某学校综合楼建筑进行了太阳能辅助土壤源热泵系统设计;并针对该建筑采用太阳能辅助土壤源热泵系统、采用单独的土壤源热泵系统或采用传统采暖空调系统,从三者经济效益、社会效益、环境效益等方面进行了比较,从而体现了太阳能辅助土壤源热泵系统相对于单独的土壤源热泵系统或传统采暖空调系统的高效、经济、节能、环保等优异性。%For the cold climate characteristics of the Northern China, the paper introduces the technical characteristics of solar-assisted ground source heat pump system relative to the separate ground source heat pump system or the separate solar energy application. For a complex building of a university in the cold northern area, the solar -assisted ground source heat pump system is designed, and economic benefits, social benefits, environmental benefits and other aspects about using the solar-assisted ground source heat pump system or using the ground source heat pump system alone or using the traditional air conditioning system are compared, thus reflects the excellent efficiency, cost-saving and energy -saving characteristics, and environmental protection about the solar assisted ground source heat pump system.

  12. 75 FR 6263 - Biomass Crop Assistance Program

    Science.gov (United States)

    2010-02-08

    ... guidelines followed for any harvesting, collecting, storing or transporting of such material from such... for the purposes of transport and delivery to eligible biomass conversion facilities. As specified in... or proposes to convert renewable biomass into heat, power, biobased products, advanced biodiesel, or...

  13. Reactor waste heat utilization and district heating reactors. Nuclear district heating in Sweden - Regional reject heat utilization schemes and small heat-only reactors

    International Nuclear Information System (INIS)

    Hannerz, K.; Larsson, Y.; Margen, P.

    1977-01-01

    A brief review is given of the current status of district heating in Sweden. In future, district heating schemes will become increasingly interesting as a means of utilizing heat from nuclear reactors. Present recommendations in Sweden are that large reactors should not be located closer than about 20 km from large population centres. Reject heat from such reactors is cheap at source. To minimize the cost of long distance hot water transmission large heat rates must be transmitted. Only areas with large populations can meet this requirement. The three areas of main interest are Malmoe/Lund/Helsingborg housing close to 0.5 million; Greater Stockholm housing 1 to 1.5 million and Greater Gothenburg housing about 0.5 million people. There is an active proposal that the Malmoe/Lund/Helsingborg region would be served by a third nuclear unit at Barsebaeck, located about 20 km from Malmoe/Lund and supplying 950 MW of base load heat. Preliminary proposals for Stockholm involve a 2000 MW heat supply; proposals for Gothenburg are more tentative. The paper describes progress on these proposals and their technology. It also outlines technology under development to increase the economic range of large scale heat transport and to make distribution economic even for low heat-density family housing estates. Regions apart from the few major urban areas mentioned above require the adoption of a different approach. To this end the development of a small, simple low-temperature reactor for heat-only production suitable for urban location has been started in Sweden in close contact with Finland. Some results of the work in progress are presented, with emphasis on the safety requirements. An outline is given in the paper as to how problems of regional heat planning and institutional and legislative issues are being approached

  14. Calculating the marginal costs of a district-heating utility

    International Nuclear Information System (INIS)

    Sjoedin, Joergen; Henning, Dag

    2004-01-01

    District heating plays an important role in the Swedish heat-market. At the same time, the price of district heating varies considerably among different district-heating utilities. A case study is performed here in which a Swedish utility is analysed using three different methods for calculating the marginal costs of heat supply: a manual spreadsheet method, an optimising linear-programming model, and a least-cost dispatch simulation model. Calculated marginal-costs, obtained with the three methods, turn out to be similar. The calculated marginal-costs are also compared to the actual heat tariff in use by the utility. Using prices based on marginal costs should be able to bring about an efficient resource-allocation. It is found that the fixed rate the utility uses today should be replaced by a time-of-use rate, which would give a more accurate signal for customers to change their heat consumptions. (Author)

  15. Simulation Models to Size and Retrofit District Heating Systems

    Directory of Open Access Journals (Sweden)

    Kevin Sartor

    2017-12-01

    Full Text Available District heating networks are considered as convenient systems to supply heat to consumers while reducing CO 2 emissions and increasing renewable energies use. However, to make them as profitable as possible, they have to be developed, operated and sized carefully. In order to cope with these objectives, simulation tools are required to analyze several configuration schemes and control methods. Indeed, the most common problems are heat losses, the electric pump consumption and the peak heat demand while ensuring the comfort of the users. In this contribution, a dynamic simulation model of all the components of the network is described. It is dedicated to assess some energetic, environmental and economic indicators. Finally, the methodology is used on an existing application test case namely the district heating network of the University of Liège to study the pump control and minimize the district heating network heat losses.

  16. Design of a solar-assisted drying system using the double-pass solar collector

    International Nuclear Information System (INIS)

    Sopian, K.; Daud, W.R.; Supranto; Othman, M.Y.; Yatim, B.

    2000-01-01

    A solar-assisted drying system that uses the double-pass solar collector with porous media in the second channel has been designed and constructed at the Solar Energy Research Park, Universiti Kebangsaan Malaysia. The drying system has a total of six double-pass solar collectors. Each collector has a length of 240 cm and a width of 120 cm. The upper channel depth is 3.5 cm and the lower channel depth is 10.5 cm. The lower channel is filled up with steel wool as the porous media. The solar collectors are arranged as 2 banks of 3 collectors each in series. Internal manifold are used to connect the collectors. An auxiliary heater source is installed to supply heat under unfavourable solar radiation conditions. An on/off controller is used to control the startup and shutdown of the auxiliary heater. An outlet temperature of 80-90 0 C can be achieved at a solar radiation range of 800-900 W/m 3 , ambient temperature of 29 degree C and flow rate of O.20 kg/s. (Author)

  17. Sensitivity of district heating system operation to heat demand reductions and electricity price variations: A Swedish example

    International Nuclear Information System (INIS)

    Åberg, M.; Widén, J.; Henning, D.

    2012-01-01

    In the future, district heating companies in Sweden must adapt to energy efficiency measures in buildings and variable fuel and electricity prices. Swedish district heating demands are expected to decrease by 1–2% per year and electricity price variations seem to be more unpredictable in the future. A cost-optimisation model of a Swedish local district heating system is constructed using the optimisation modelling tool MODEST. A scenario for heat demand changes due to increased energy efficiency in buildings, combined with the addition of new buildings, is studied along with a sensitivity analysis for electricity price variations. Despite fears that heat demand reductions will decrease co-generation of clean electricity and cause increased global emissions, the results show that anticipated heat demand changes do not increase the studied system's primary energy use or global CO 2 emissions. The results further indicate that the heat production plants and the fuels used within the system have crucial importance for the environmental impact of district heat use. Results also show that low seasonal variations in electricity price levels with relatively low winter prices promote the use of electric heat pumps. High winter prices on the other hand promote co-generation of heat and electricity in CHP plants. -- Highlights: ► A MODEST optimisation model of the Uppsala district heating system is built. ► The impact of heat demand change on heat and electricity production is examined. ► An electricity price level sensitivity analysis for district heating is performed. ► Heat demand changes do not increase the primary energy use or global CO 2 emissions. ► Low winter prices promote use of electric heat pumps for district heating production.

  18. Exergy and Energy Analysis of Low Temperature District Heating Network

    DEFF Research Database (Denmark)

    Li, Hongwei; Svendsen, Svend

    is in line with a pilot project that is carrying out in Denmark with network supply/return temperature at 55oC/25 oC. The consumer domestic hot water (DHW) demand is supplied with a special designed district heating (DH) storage tank. The space heating (SH) demand is supplied with a low temperature radiator......Low temperature district heating (LTDH) with reduced network supply and return temperature provides better match of the low quality building thermal demand and the low quality waste heat supply. In this paper, an exemplary LTDH network was designed for 30 low energy demand residential houses, which....... The network thermal and hydraulic conditions were simulated under steady state with an in-house district heating network design and simulation code. Through simulation, the overall system energetic and exergetic efficiencies were calculated and the exergy losses for the major district heating system...

  19. How low can the low heating load density district heating be? Environmental aspects on low heating load density district heating of the present generation compared to a domestic oil burner; Hur vaermegles kan den vaermeglesa fjaerrvaermen vara? Miljoeaspekter paa vaermegles fjaerrvaerme med dagens teknik jaemfoerd med villaoljepanna

    Energy Technology Data Exchange (ETDEWEB)

    Froeling, Morgan [Chalmers Univ. of Technology, Goeteborg (Sweden). Dept. of Chemical Environmental Science

    2005-07-01

    In Sweden we can see an increase of district heating networks in residential areas with low heat density. For the customer the economy is normally the most important argument when deciding to choose district heating. For many customers, however, arguments regarding environmental friendliness are important complimentary arguments. When district heating systems are built with decreased heat density, the environmental impacts from use of district heating will increase, depending on such as increased need of pipes and increased heat losses from the distribution system. The purpose of this study is to investigate if there is a limit, a lowest heat density when it is not any longer beneficial to build district heating when district heating replaces local oil furnace heating. Life cycle inventory data for district heating distribution systems in areas with low heat density has been compared with the use of oil furnaces. The environmental impacts are categorized into Global Warming Potential, Acidification Potential, Eutrofication Potential and Use of Finite Resources. To enhance the assessment three single point indicators have also been used: EcoIndicator99, EPS and ExternE. The economics of using district heating in areas with low heat density has not been regarded in this study. A model comparing the space heating of a single family home with an oil furnace or with district heating has been created. The home has an annual heat need of 20 MWh. The district heating distribution network is characterized by its linear heat density. The linear heat density is a rough description of a district heating network, and thus also the results from the model will be general. Still it can give us a general idea of the environmental limit for district heating in areas with low heat density. An assessment of all results indicate that with the type of technology used at present it is not environmentally beneficial to use district heating with lower linear heat density than 0,2 MWh/m. At

  20. Remote Sensing-Based Characterization of Settlement Structures for Assessing Local Potential of District Heat

    Directory of Open Access Journals (Sweden)

    Michael Nast

    2011-07-01

    Full Text Available In Europe, heating of houses and commercial areas is one of the major contributors to greenhouse gas emissions. When considering the drastic impact of an increasing emission of greenhouse gases as well as the finiteness of fossil resources, the usage of efficient and renewable energy generation technologies has to be increased. In this context, small-scale heating networks are an important technical component, which enable the efficient and sustainable usage of various heat generation technologies. This paper investigates how the potential of district heating for different settlement structures can be assessed. In particular, we analyze in which way remote sensing and GIS data can assist the planning of optimized heat allocation systems. In order to identify the best suited locations, a spatial model is defined to assess the potential for small district heating networks. Within the spatial model, the local heat demand and the economic costs of the necessary heat allocation infrastructure are compared. Therefore, a first and major step is the detailed characterization of the settlement structure by means of remote sensing data. The method is developed on the basis of a test area in the town of Oberhaching in the South of Germany. The results are validated through detailed in situ data sets and demonstrate that the model facilitates both the calculation of the required input parameters and an accurate assessment of the district heating potential. The described method can be transferred to other investigation areas with a larger spatial extent. The study underlines the range of applications for remote sensing-based analyses with respect to energy-related planning issues.

  1. The Regional Biomass-Energy Agency (ERBE): an opportunity for the biomass-energy development in Wallonia

    International Nuclear Information System (INIS)

    Lemaire, P.; Menu, J.F.; Belle, J.F. van; Schenkel, Y.

    1997-01-01

    In 1995, the European Commission (Directorate-General for Energy) and the Walloon government set up a biomass-energy agency (ERBE), to promote and build biomass-energy projects in Wallonia (Belgium). A survey of biomass-energy potential indicates that wood-energy seems to offer the best utilization opportunities. Forest and logging residues, sawmills' and joineries' off-cuts, pallets residues, etc. could be burnt in wood district heating units with a significant social benefit. Consequently, the ERBE Agency is trying to set up projects in this way in Austria (+/- 100 wood heating systems) or in Sweden. It serves to inform industries and municipalities about biomass-energy, to advise them in the building of biomass-energy projects, to identify their energy needs and their biomass resources, to carry out prefeasibility studies, to inform them about financing opportunities, and so on. (author)

  2. District heating from Forsmark

    International Nuclear Information System (INIS)

    1980-11-01

    The district heating system of Greater Stockholm must be based on other energy sources than oil. Two alternatives are assessed, namely heat from Forsmark or a coal fueled plant in the region of Stockholm. Forsmark 3 can produce both electricity and heat from the year 1988 on. The capacity can be increased by coal fueled blocks. For low electricity use, 115 TWh in the year 1990, the Forsmark alternative will be profitable. The alternative will be profitable. The alternative with a fossile fuelled plant will be profitable when planning for high consumption of electricity, 125 TWh. The Forsmark alternative means high investments and the introduction of new techniques. (G.B.)

  3. Expieriences On Low-Temperature District Heating In Lystrup – Denmark

    DEFF Research Database (Denmark)

    Thorsen, Jan Eric; Christiansen, Christian Holm; Brand, Marek

    2011-01-01

    by implementing Low-temperature district heating systems. Demonstration cases in EnergyFlexHouse and Boligforeningen Ringgården” EUDP 2011. A key challenge for optimum and competitive district heating (DH) system operation is reducing heat loss in networks. Today building regulations in most countries demand...

  4. Analysis of a Hybrid Solar-Assisted Trigeneration System

    Directory of Open Access Journals (Sweden)

    Elisa Marrasso

    2016-09-01

    Full Text Available A hybrid solar-assisted trigeneration system is analyzed in this paper. The system is composed of a 20 m2 solar field of evacuated tube collectors, a natural gas fired micro combined heat and power system delivering 12.5 kW of thermal power, an absorption heat pump (AHP with a nominal cooling power of 17.6 kW, two storage tanks (hot and cold and an electric auxiliary heater (AH. The plant satisfies the energy demand of an office building located in Naples (Southern Italy. The electric energy of the cogenerator is used to meet the load and auxiliaries electric demand; the interactions with the grid are considered in cases of excess or over requests. This hybrid solution is interesting for buildings located in cities or historical centers with limited usable roof surface to install a conventional solar heating and cooling (SHC system able to achieve high solar fraction (SF. The results of dynamic simulation show that a tilt angle of 30° maximizes the SF of the system on annual basis achieving about 53.5%. The influence on the performance of proposed system of the hot water storage tank (HST characteristics (volume, insulation is also studied. It is highlighted that the SF improves when better insulated and bigger HSTs are considered. A maximum SF of about 58.2% is obtained with a 2000 L storage, whereas the lower thermal losses take place with a better insulated 1000 L tank.

  5. Theoretical analysis and experimental study to solar assisted ground-source heat pump system%太阳能辅助系统的理论分析和实验研究

    Institute of Scientific and Technical Information of China (English)

    杨鹏; 刘自强; 侯静

    2011-01-01

    As a clean, renewable energy, the geothermal energy and solar energy are trend of develo- ping and using new energies in the future. This paper introduces solar assisted Ground Source Heat Pump system, combined with the advantage of t the geothermal energy and solar energy. Through theoretical analysis and experiment, the solar assisted Ground Source Heat Pump system is proved to be feasible and scientific.%地热能和太阳能作为清洁、可再生的能源,是未来开发和利用新能源的趋势,本文介绍了太阳能辅助地源热泵系统,是将二者结合,取长补短的一种热泵形式。通过理论分析和实验验证。证明了太阳能辅助地源热泵系统的可行性和科学性。

  6. Heat planning for fossil-fuel-free district heating areas with extensive end-use heat savings

    DEFF Research Database (Denmark)

    Harrestrup, Maria; Svendsen, S.

    2014-01-01

    is a theoretical investigation of the district heating system in the Copenhagen area, in which heat conservation is related to the heat supply in buildings from an economic perspective. Supplying the existing building stock from low-temperature energy resources, e.g. geothermal heat, might lead to oversized......The Danish government plans to make the Danish energy system to be completely free of fossil fuels by 2050 and that by 2035 the energy supply for buildings and electricity should be entirely based on renewable energy sources. To become independent from fossil fuels, it is necessary to reduce...... the energy consumption of the existing building stock, increase energy efficiency, and convert the present heat supply from fossil fuels to renewable energy sources. District heating is a sustainable way of providing space heating and domestic hot water to buildings in densely populated areas. This paper...

  7. Innovative system for delivery of low temperature district heating

    Directory of Open Access Journals (Sweden)

    Anton Ivanov Ianakiev

    2017-01-01

    Full Text Available An innovative Low Temperature District Heating (LTDH local network is developed in Nottingham, supported by REMOURBAN project, part of the H2020 Smart City and Community Lighthouse scheme. It was proposed that a branch emanating from the return pipe of the of the existing district heating system in Nottingham would be created to use low temperature heating for the first time in UK. The development is aimed to extract wasted (unused heat from existing district heating system and make it more efficient and profitable. Four maisonette blocks of 94 low-raised flats, at Nottingham demo site of the REMOURBAN project will be connected to this new LTDH system. The scheme will provide a primary supply of heat and hot water at approximately 50oC to 60oC. Innovated solutions have been put forward to overcome certain barriers, such as legionella related risks and peak loads during extreme heating seasons and occasional maintenance.

  8. Heat storage in forest biomass improves energy balance closure

    Science.gov (United States)

    Lindroth, A.; Mölder, M.; Lagergren, F.

    2010-01-01

    Temperature measurements in trunks and branches in a mature ca. 100 years-old mixed pine and spruce forest in central Sweden were used to estimate the heat storage in the tree biomass. The estimated heat flux in the sample trees and data on biomass distributions were used to scale up to stand level biomass heat fluxes. The rate of change of sensible and latent heat storage in the air layer below the level of the flux measurements was estimated from air temperature and humidity profile measurements and soil heat flux was estimated from heat flux plates and soil temperature measurements. The fluxes of sensible and latent heat from the forest were measured with an eddy covariance system in a tower. The analysis was made for a two-month period in summer of 1995. The tree biomass heat flux was the largest of the estimated storage components and varied between 40 and -35 W m-2 on summer days with nice weather. Averaged over two months the diurnal maximum of total heat storage was 45 W m-2 and the minimum was -35 W m-2. The soil heat flux and the sensible heat storage in air were out of phase with the biomass flux and they reached maximum values that were about 75% of the maximum of the tree biomass heat storage. The energy balance closure improved significantly when the total heat storage was added to the turbulent fluxes. The slope of a regression line with sum of fluxes and storage as independent and net radiation as dependent variable, increased from 0.86 to 0.95 for half-hourly data and the scatter was also reduced. The most significant finding was, however, that during nights with strongly stable conditions when the sensible heat flux dropped to nearly zero, the total storage matched the net radiation very well. Another interesting result was that the mean energy imbalance started to increase when the Richardson number became more negative than ca. -0.1. In fact, the largest energy deficit occurred at maximum instability. Our conclusion is that eddy covariance

  9. Optimising corrosion monitoring in district heating systems

    DEFF Research Database (Denmark)

    Hilbert, Lisbeth Rischel; Thorarinsdottir, R.I.; Andersen, A.

    2002-01-01

    A three-year project - financially supported by the Nordic Industrial Fund - on monitoring of corrosion in district heating systems has been initiated with participation of researchers and industrial partners in Denmark, Finland, Iceland, Norway and Sweden. The primary objective of the project...... is to improve the quality control in district heating systems by corrosion monitoring. In Danish systems electrochemical impedance spectroscopy (EIS), linear polarisation resistance (LPR), high-sensitive electrical resistance (ER) technology, crevice corrosion probes, as well as weight loss coupons...

  10. Heat Driven Cooling in District Energy Systems; Vaermedriven Kyla

    Energy Technology Data Exchange (ETDEWEB)

    Rydstrand, Magnus; Martin, Viktoria; Westermark, Mats [Royal Inst. of Technology, Stockholm (Sweden). Dept. of Chemical Engineering and Technology

    2004-07-01

    This report is reviewing different heat driven technologies for the production of cooling. It is shown that the supply of cooling gives the highest fuel utilization if heat from CHP production is used for the production of cooling instead of maximizing the electricity output in a condensing plant. High fuel utilization is reached since the direct production of cooling from heat is a thermodynamic shortcut as compared to the production of electricity as an intermediate product before cooling is produced. At direct production of cooling from heat it is possible to obtain 70 percent of the obtainable cooling of an ideal process. If electricity is produced from heat, 70 percent electricity could be obtained as compared to an ideal process. If this electricity would be used for the production of cooling 70 percent of the obtainable cooling in an ideal process would the result. The total production of cooling from heat with electricity as an intermediate product would therefore give 50 percent cooling as compared to an ideal process. Hence, heat driven cooling will give more cooling for a given fuel input. In the review of the different heat driven cooling options it was found that there are many alternatives suitable for different applications. Absorption cooling is suitable for water distributed cooling if the latent cooling load is low. Desiccant cooling is believed to have a large market in climates (applications) with high latent cooling loads. In the energy efficiency evaluation it is found that the highest fuel utilization is given for a central production of electricity using either district heating or district cooling as the energy carrier to supply cooling. In fact the potential of district heating as the energy carrier is thought to be the largest in large cities with humid climates. Further it is found that the chiller heat sink can contribute significantly to the cost in many applications, especially if water and/or electricity consumption are issues with

  11. Market Potential for Residential Biomass Heating Equipment: Stochastic and Econometric Assessments

    OpenAIRE

    Adee Athiyaman

    2015-01-01

    This paper provides estimates of market potential for biomass-residential-heating equipment in the US: that is, the greatest amount of biomass-residential-heating equipment that can be sold by the industry. The author's analysis is limited to biomass equipment used most to heat the housing unit. Assuming that households equipped with 10+ year old primary heating devices will replace rather than repair the devices he predicts that approximately 1.4 million units of residential home heating equ...

  12. Efficiency potential in the district heating sector. Final report

    International Nuclear Information System (INIS)

    Agrell, P.; Bogetoft, P.; Fristrup, P.; Munksgaard, J.; Pade, L.L.

    2003-10-01

    This report is the final documentation for the research project 'District heating prices in a liberalised energy market - benchmarking the production of combined heat and power'. The project compares activities for almost 300 companies, members of the Danish District Heating Society. The main aim of the analyses has been to uncover the saving potential by comparing each individual company to the most efficient companies in the sector. The variable costs have been studied, amounting to almost 7 billion Danish kroner a year, and the analyses found saving potential ranging from 5% to 60% dependent on the expectations to flexibility assigned to the individual companies. The data used are not available for the public as they exceed the Danish District Heating Society's annual statistics. (BA)

  13. Optimization of Serial Combined System of Ground-Coupled Heat Pump and Solar Collector

    Institute of Scientific and Technical Information of China (English)

    ZHAO Jun; CHEN Yan; LU Suzhen; CUI Junkui

    2009-01-01

    A mathematical optimization model was set up for a ground-solar combined system based on in-situ experimental results,in which the solar collector was combined serially with a ground-coupled heat pump(GCHP).The universal optimal equations were solved by the constrained variable metric method considering both the performance and economics.Then the model was applied to a specific case concerning an actual solar assisted GCHP system for space heating.The results indicated a system coefficient of performance(COP)of 3.9 for the optimal method under the seriaI heating mode,and 3.2 for the conventional one.In addition,the optimum solution also showed advantages in energy and cost saving.1eading to a 16.7%improvement in the heat pump performance at 17.2%less energy consumption and 11.8%lower annual cost,respectively.

  14. A cold end to the district heating year

    International Nuclear Information System (INIS)

    Talsi, M.

    2003-01-01

    According to preliminary data from the Finnish District Heating Association, a total of 29.5 TWh of district heat was sold in Finland in 2002. Low temperatures in October, November, and December boosted sales over the year as a whole to virtually normal levels, despite the exceptionally warm early part of the year. Sales were up some 4 % on 2001 and totalled EUR 1.09 billion

  15. Solar heating and cooling system installed at Leavenworth, Kansas. Final report

    Energy Technology Data Exchange (ETDEWEB)

    Perkins, R. M.

    1980-06-01

    The solar heating and cooling system installed at the headquarters of Citizens Mutual Savings Association in Leavenworth, Kansas, is described in detail. The project is part of the U.S. Department of Energy's solar demonstration program and became operational in March, 1979. The designer was TEC, Inc. Consulting Engineers, Kansas City, Missouri and contractor was Norris Brothers, Inc., Lawrence, Kansas. The solar system is expected to furnish 90 percent of the overall heating load, 70 percent of the cooling load and 100 percent of the domestic hot water load. The building has two floors with a total of 12,000 square feet gross area. The system has 120 flat-plate liquid solar panels with a net area of 2200 square feet. Five, 3-ton Arkla solar assisted absorption units provide the cooling, in conjunction with a 3000 gallon chilled water storage tank. Two, 3000 gallon storage tanks are provided with one designated for summer use, whereas both tanks are utilized during winter.

  16. Wood chip drying in connection with combined heat and power or solar energy in Finland

    Directory of Open Access Journals (Sweden)

    Rinne Samuli

    2014-01-01

    Full Text Available 20% of the Finnish district heating (DH power plant fuels are wood-based and the share is increasing. The wood fuel demand probably exceeds the potential supply in the future. The wood fuel drying with waste heat is one profitable opportunity to gain more wood fuel. If the drying energy can be produced with lower primary energy use than combusting the fuel directly, the drying potentially improves the system efficiency. In this study, the drying feasibility in the connection of a combined heat and power (CHP system, possibly with solar collectors, is calculated. The wood fuel heating can be increased profitably by 6%, using the heat from CHP for drying only when the marginal cost of the heat is low enough, i.e. the electricity price is high enough and there is free capacity after the DH demand. Although the drying is profitable, a larger heat storage can also increase the annual result similarly. The best investment choice depends on the plant properties. Here the optimal system enables 20% DH production cost savings. Solar heat may be profitable, when the solar heat has a 2–3% share of the annual heat demand. However, the dryer or larger storage tank are more profitable investments.

  17. Effect of Tube Diameter on The Design of Heat Exchanger in Solar Drying system

    Science.gov (United States)

    Husham Abdulmalek, Shaymaa; Khalaji Assadi, Morteza; Al-Kayiem, Hussain H.; Gitan, Ali Ahmed

    2018-03-01

    The drying of agriculture product consumes a huge fossil fuel rates that demand to find an alternative source of sustainable environmental friendly energy such as solar energy. This work presents the difference between using solar heat source and electrical heater in terms of design aspect. A circular-finned tube bank heat exchanger is considered against an electrical heater used as a heat generator to regenerate silica gel in solar assisted desiccant drying system. The impact of tube diameter on the heat transfer area was investigated for both the heat exchanger and the electrical heater. The fin performance was investigated by determining fin effectiveness and fin efficiency. A mathematical model was developed using MATLAB to describe the forced convection heat transfer between hot water supplied by evacuated solar collector with 70 °C and ambient air flow over heat exchanger finned tubes. The results revealed that the increasing of tube diameter augments the heat transfer area of both heat exchanger and electrical heater. The highest of fin efficiency was around 0.745 and the lowest was around 0.687 while the fin effectiveness was found to be around 0.998.

  18. Ground Source Geothermal District Heating and Cooling System

    Energy Technology Data Exchange (ETDEWEB)

    Lowe, James William [Ball State Univ., Muncie, IN (United States)

    2016-10-21

    Ball State University converted its campus from a coal-fired steam boiler district heating system to a ground source heat pump geothermal district system that produces simultaneously hot water for heating and chilled water for cooling. This system will include the installation of 3,600 four hundred feet deep vertical closed loop boreholes making it the largest ground source geothermal district system in the country. The boreholes will act as heat exchangers and transfer heat by virtue of the earth’s ability to maintain an average temperature of 55 degree Fahrenheit. With growing international concern for global warming and the need to reduce worldwide carbon dioxide loading of the atmosphere geothermal is poised to provide the means to help reduce carbon dioxide emissions. The shift from burning coal to utilizing ground source geothermal will increase electrical consumption but an overall decrease in energy use and reduction in carbon dioxide output will be achieved. This achievement is a result of coupling the ground source geothermal boreholes with large heat pump chiller technology. The system provides the thermodynamic means to move large amounts of energy with limited energy input. Ball State University: http://cms.bsu.edu/About/Geothermal.aspx

  19. Cogeneration and District Heating. Best Practices for Municipalities

    International Nuclear Information System (INIS)

    Nuorkivi, A.; Constantinescu, T.

    2005-01-01

    District heating (DH) and cogeneration of heat power (CHP) are well known technologies in the energy business and are often included in municipal policies as well. Some of the major benefits of DH and CHP are less known and the barriers faced by further development of DH and CHP are substantial. The main barriers are institutional. Municipalities can play a powerful role in facilitating local DH and CHP development in order to achieve the economic and environmental benefits of DH and CHP. This report is produced to assist municipalities in promoting efficient and environmental beneficial DH and CHP. The focus of the report is on the economies in transition, where the institutional barriers are acute. The report addresses the issues of organisational framework, price regulation and financing, energy demand, rehabilitation of DH systems and benchmarking of DH and CHP. The municipality may influence the DH development by a number of means. The most important means, discussed in the various chapters of the report, are: (1) City planning impacts on the heat load density. A high density is an important factor for the economics of DH and city planning may promote DH in areas with high density and individual heating modes in the areas with low density; (2) Managing the building stock owned by the municipality to join the DH system and paying for the heating services; (3) Setting strategic goals for the District Heating Enterprise (DHE), which they usually own, regarding the quality and the costs of heating. The DHE shall be given sufficient resources to work towards such goals; (4) Providing guarantees for financing DH rehabilitation and development. The DHE may not have access to commercial credits without municipal guarantees; and, (5) Supporting the DHE management by giving operational independence, supervising the management performance regularly and encouraging the co-operation with other DHEs and equipment manufacturers. Examples provided in the report of

  20. Conversion of individual natural gas to district heating

    DEFF Research Database (Denmark)

    Möller, Bernd; Lund, Henrik

    2010-01-01

    Replacing individual natural gas heating with district heating based to increasing shares of renewable energy sources may further reduce CO2-emissions in the Danish Building mass, while increasing flexibility of the energy system to accommodate significantly larger amounts of variable renewable...... energy production. The present paper describes a geographical study of the potential to expand district heating into areas supplied with natural gas. The study uses a highly detailed spatial database of the built environment, its current and potential future energy demand, its supply technologies and its...

  1. Energy source completion for geothermal district heating systems

    International Nuclear Information System (INIS)

    Popovski, Kiril

    2000-01-01

    Geothermal district heating systems differs from the others mainly in the part of energy source completion and its connection to the heat distribution systems rather known problem. Even rather known problematic in the countries where geothermal energy is in wide application, new appearances of mistakes are always present due to the fact that necessary literature is difficult to be found. Essentials of the geothermal well completion and connection of geothermal source to the district heating distribution system are summarized in the paper and several examples of geothermal projects in flow are presented. (Author)

  2. District Heating in Areas with Low Energy Houses

    DEFF Research Database (Denmark)

    Tol, Hakan Ibrahim

    -energy houses involved, together with the idea of utilizing booster pumps in the district heating network and (ii) use of network layouts of either a branched (tree-like) or a looped type. The methods developed were applied in a case study, the data of which was provided by the municipality of Roskilde...... in Denmark. The second case study was aimed at solving another regional energy planning scheme, one concerned with already existing houses, the heat requirements of which were currently being met by use of a natural gas grid or a conventional high-temperature district heating network. The idea considered......This PhD thesis presents a summary of a three-year PhD project involving three case studies, each pertaining to a typical regional Danish energy planning scheme with regard to the extensive use of low-energy district heating systems, operating at temperatures as low as 55°C for supply and 25°C...

  3. Geothermal direct-heat utilization assistance. Federal Assistance Program quarterly project progress report, April 1--June 30, 1998

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1998-07-01

    This report summarizes geothermal technical assistance, R and D and technology transfer activities of the Geo-Heat Center at Oregon Institute of Technology for the third quarter of FY98 (April--June, 1998). It describes 231 contacts with parties during this period related to technical assistance with geothermal direct heat projects. Areas dealt with included requests for general information including material for high school and university students, and material on geothermal heat pumps, resource and well data, spacing heating and cooling, greenhouses, aquaculture, equipment, district heating, resorts and spas, industrial applications, snow melting and electric power. Research activities include work on model construction specifications for line shaft submersible pumps and plate heat exchangers, and a comprehensive aquaculture developers package. A brochure on Geothermal Energy in Klamath County was developed for state and local tourism use. Outreach activities include the publication of the Quarterly Bulletin (Vol. 19, No. 2) with articles on research at the Geo-Heat Center, sustainability of geothermal resources, injection well drilling in Boise, ID and a greenhouse project in the Azores. Other outreach activities include dissemination of information mainly through mailings of publications, tours of local geothermal uses, geothermal library acquisitions and use, participation in workshops, short courses and technical meetings by the staff, and progress monitor reports on geothermal activities.

  4. Simulation analysis on dynamic performance of a combined solar/air dual source heat pump water heater

    International Nuclear Information System (INIS)

    Deng, Weishi; Yu, Jianlin

    2016-01-01

    Highlights: • A modified direct expansion solar-assisted heat pump water heater is investigated. • An additional air source evaporator is used in parallel way in the M-DX-SHPWH system. • The M-DX-SHPWH system displays a higher performance at the low solar radiation. • Effects of solar radiation and air temperature on the performance are discussed. - Abstract: This paper investigated a combined solar/air dual source heat pump water heater system for domestic water heating application. In the dual source system, an additional air source evaporator is introduced in parallel way based on a conventional direct expansion solar-assisted heat pump water heaters (DX-SHPWH) system, which can improve the performance of the DX-SHPWH system at a low solar radiation. In the present study, a dynamic mathematical model based on zoned lump parameter approach is developed to simulate the performance of the system (i.e. a modified DX-SHPWH (M-DX-SHPWH) system). Using the model, the performance of M-DX-SHPWH system is evaluated and then compared with that of the conventional DX-SHPWH system. The simulation results show the M-DX-SHPWH system has a better performance than that of the conventional DX-SHPWH system. At a low solar radiation of 100 W/m"2, the heating time of the M-DX-SHPWH decreases by 19.8% compared to the DX-SHPWH when water temperature reaches 55 °C. Meanwhile, the COP on average increases by 14.1%. In addition, the refrigerant mass flow rate distribution in the air source evaporator and the solar collector of the system, the allocation between the air source evaporator and the solar collector areas and effects of solar radiation and ambient air temperature on the system performance are discussed.

  5. Fundamentals of Solar Heating. Correspondence Course.

    Science.gov (United States)

    Sheet Metal and Air Conditioning Contractors National Association, Vienna, VA.

    This course is designed for the use of employees of the air conditioning industry, and offers supervised correspondence instruction about solar technology. The following aspects of applied solar technology are covered: solar heating and cooling, solar radiation, solar collectors, heat storage control devices and specialty items, sizing solar…

  6. Solar-powered Rankine heat pump for heating and cooling

    Science.gov (United States)

    Rousseau, J.

    1978-01-01

    The design, operation and performance of a familyy of solar heating and cooling systems are discussed. The systems feature a reversible heat pump operating with R-11 as the working fluid and using a motor-driven centrifugal compressor. In the cooling mode, solar energy provides the heat source for a Rankine power loop. The system is operational with heat source temperatures ranging from 155 to 220 F; the estimated coefficient of performance is 0.7. In the heating mode, the vapor-cycle heat pump processes solar energy collected at low temperatures (40 to 80 F). The speed of the compressor can be adjusted so that the heat pump capacity matches the load, allowing a seasonal coefficient of performance of about 8 to be attained.

  7. Heat extraction from turbines of Czechoslovak nuclear power plants for district heating

    International Nuclear Information System (INIS)

    Drahy, J.

    1985-01-01

    Two design are described of SKODA extraction turbines for Czechoslovak nuclear power plants with WWER-440 and WWER-1000 reactors. 220 MW steam turbines were originally designed as pure condensation turbines with uncontrolled steam extraction. Optimal ways are now being sought for their use for heating hot water for district heating. For district heating of the town of Trnava, the nuclear power plant at Jaslovske Bohunice will provide a two-step heating of water from 70 to 120 degC with a heat supply of 60 MW th from one turbine unit. The ratio of obtained heat power to lost electric power is 5.08. Investigations showed the possibility of extracting 85 MW th of heat from uncontrolled steam extraction, this at three-step water heating from 60 to 145 degC, the ratio of gained and lost power being 7.14. Information is presented on the SKODA 220 MW turbine with steam extraction for heat supply purposes and on the 1000 MW turbine with 893 MW th heat extraction. The specifications of both types are given. (Pu)

  8. Corrosion Fatigue in District Heating Water Tanks

    DEFF Research Database (Denmark)

    Maahn, Ernst Emanuel

    1996-01-01

    Three candidate materials for construction of buffer tanks for district heating water have been tested for corrosion fatigue properties in a district heating water environment. The investigation included Slow Strain Rate Testing of plain tensile specimens, crack initiation testing by corrosion...... fatigue of plain tensile specimens and crack growth rate determination for Compact Tensile Specimens under corrosion fatigue conditions. The three materials are equal with respect to stress corrosion sensibility and crack initiation. Crack growth rate is increased with a factor of 4-6 relative to an inert...

  9. Load Management in District Heating Operation

    DEFF Research Database (Denmark)

    Li, Hongwei; Wang, Stephen Jia

    2015-01-01

    Smooth operation of district heating system will avoid installation of expensive peak heat boilers, improve plant partial load performance, increase the system redundancy for further network expansion and improve its resilience to ensure security of supply during severe heating seasons. The peak...... heating load can be reduced through building demand side management. The building thermal mass can be used to shift the heating supply under the circumstance without jeopardizing the consumer thermal comfort. In this paper, the multi-agent framework is applied to a simplified building dynamic model...

  10. Solar Spots - Activities to Introduce Solar Energy into the K-8 Curricula.

    Science.gov (United States)

    Longe, Karen M.; McClelland, Michael J.

    Following an introduction to solar technology which reviews solar heating and cooling, passive solar systems (direct gain systems, thermal storage walls, sun spaces, roof ponds, and convection loops), active solar systems, solar electricity (photovoltaic and solar thermal conversion systems), wind energy, and biomass, activities to introduce solar…

  11. Fast microwave assisted pyrolysis of biomass using microwave absorbent.

    Science.gov (United States)

    Borges, Fernanda Cabral; Du, Zhenyi; Xie, Qinglong; Trierweiler, Jorge Otávio; Cheng, Yanling; Wan, Yiqin; Liu, Yuhuan; Zhu, Rongbi; Lin, Xiangyang; Chen, Paul; Ruan, Roger

    2014-03-01

    A novel concept of fast microwave assisted pyrolysis (fMAP) in the presence of microwave absorbents was presented and examined. Wood sawdust and corn stover were pyrolyzed by means of microwave heating and silicon carbide (SiC) as microwave absorbent. The bio-oil was characterized, and the effects of temperature, feedstock loading, particle sizes, and vacuum degree were analyzed. For wood sawdust, a temperature of 480°C, 50 grit SiC, with 2g/min of biomass feeding, were the optimal conditions, with a maximum bio-oil yield of 65 wt.%. For corn stover, temperatures ranging from 490°C to 560°C, biomass particle sizes from 0.9mm to 1.9mm, and vacuum degree lower than 100mmHg obtained a maximum bio-oil yield of 64 wt.%. This study shows that the use of microwave absorbents for fMAP is feasible and a promising technology to improve the practical values and commercial application outlook of microwave based pyrolysis. Copyright © 2014 Elsevier Ltd. All rights reserved.

  12. Emerging large-scale solar heating applications

    International Nuclear Information System (INIS)

    Wong, W.P.; McClung, J.L.

    2009-01-01

    Currently the market for solar heating applications in Canada is dominated by outdoor swimming pool heating, make-up air pre-heating and domestic water heating in homes, commercial and institutional buildings. All of these involve relatively small systems, except for a few air pre-heating systems on very large buildings. Together these applications make up well over 90% of the solar thermal collectors installed in Canada during 2007. These three applications, along with the recent re-emergence of large-scale concentrated solar thermal for generating electricity, also dominate the world markets. This paper examines some emerging markets for large scale solar heating applications, with a focus on the Canadian climate and market. (author)

  13. Emerging large-scale solar heating applications

    Energy Technology Data Exchange (ETDEWEB)

    Wong, W.P.; McClung, J.L. [Science Applications International Corporation (SAIC Canada), Ottawa, Ontario (Canada)

    2009-07-01

    Currently the market for solar heating applications in Canada is dominated by outdoor swimming pool heating, make-up air pre-heating and domestic water heating in homes, commercial and institutional buildings. All of these involve relatively small systems, except for a few air pre-heating systems on very large buildings. Together these applications make up well over 90% of the solar thermal collectors installed in Canada during 2007. These three applications, along with the recent re-emergence of large-scale concentrated solar thermal for generating electricity, also dominate the world markets. This paper examines some emerging markets for large scale solar heating applications, with a focus on the Canadian climate and market. (author)

  14. Thermodynamic analysis of solar assisted multi-functional trigeneration system

    Directory of Open Access Journals (Sweden)

    Önder KIZILKAN

    2016-02-01

    Full Text Available In this study, modelling and thermodynamic analysis of solar assisted trigeneration system was carried out. The required thermal energy for gas and vapor cycles were supplied from solar tower which is a new concept for gas cycle applications. Additionally, an absorption refrigeration cycle, vapor production process, drying process and water heating process were integrated to the system. Energy and exergy efficiencies of the trigeneration system were determined by the application of first and second law analyses. The results showed that the gas cycle efficiency was found to be 31%, vapor cycle efficiency was found to be 28% and coefficient of performance (COP values of the refrigeration system was found to be 0.77. Also the highest exergy destruction rate was found to be 4154 kW in solar tower.Keywords: Solar tower, Trigeneration, Gas cycle, Vapor cycle, Energy, Exergy

  15. The application of ground source heat pumps to a subdivision-wide district heating system

    International Nuclear Information System (INIS)

    Ciavaglia, L.

    2005-01-01

    Design guidelines for economic ground source heat pumps (GSHP) in district energy systems were presented. The broad economics of using central GSHP in a community district energy system were examined. Design parameters needed to utilize GSHP in district energy system were outlined. The sensitivity of energy prices and the costs of major capital were reviewed. District heating load duration curves were outlined. It was suggested that varying GSHP capacity from 0 to 100 per cent of load was advisable. In addition, capacity should be balanced with gas boiler technology. The amortizing of capital within energy costs was recommended. It was suggested that the best scenario was a minimum of 50 per cent ground energy. Details of pipings and heat exchanger costs were presented, along with costs for gas boilers and gas costs for the district energy system. Charts of current costing and reduction of piping capital were included. It was concluded that GSHP can be a viable component of a district energy system, as a GSHP based district energy system can provide more stable energy prices than conventional fossil fuel systems. It was suggested that sizing of GSHP at, or near, 40 per cent of peak demand provided optimal conditions with respect to energy cost and use of earth energy. tabs., figs

  16. District heating in Switzerland: Giving a survey and studying an example case

    Energy Technology Data Exchange (ETDEWEB)

    Kiss, M; Minder, R

    1981-05-01

    Today it is generally accepted that district-heating has essential adventages in areas which are suitable for it - as opposed to the heating mode which is most widely practiced in Switzerland, i.e. individual oil heating. These advantages shall only be pointed out briefly, here, by mentioning the following key words: economy, exploitation of fuel, safety of supply, and enviromental protection. Principally supporting the expansion of existing district-heating installations or the construction of new ones the authors give their view on the subject concerning the contribution to the total supply of heat which reasonably may be attributed to district-heating; they also give their opinion of the plans of a Swiss municipality as to its energy and district-heating supply.

  17. Energy supply and urban planning projects: Analysing tensions around district heating provision in a French eco-district

    International Nuclear Information System (INIS)

    Gabillet, Pauline

    2015-01-01

    Through the analysis of energy supply choices, this article explores the way in which energy priorities and their climate-related features are incorporated into urban public policy. These choices must take account of different factors, as is the case with district heating, which is justified as a vehicle of renewable energy while subject to pressure in eco-districts because its techno-economic balances are destabilised by falls in demand. Our study focuses particularly on the city of Metz (France), which has chosen district heating as the primary source for provision for the municipal area and for its first eco-district. We analyse the tensions within these choices, with particular attention to the way in which they are negotiated inside municipal departments and with the local energy operator. This enables us to explore the tensions in defining the scale that governs decisions and the linkages between energy-related and urban priorities. - Highlights: • Analyses of tensions in the choice of energy supplies for eco-districts. •District heating networks can be vehicles of renewable energy. • District heating networks are threatened by drops in energy consumption. • Energy supply issues oppose urban planning and energy policy in municipal departments. • Technical and financial adjustments can be made by the municipality to justify its energy choices

  18. An equivalent marginal cost-pricing model for the district heating market

    International Nuclear Information System (INIS)

    Zhang, Junli; Ge, Bin; Xu, Hongsheng

    2013-01-01

    District heating pricing is a core element in reforming the heating market. Existing district heating pricing methods, such as the cost-plus pricing method and the conventional marginal-cost pricing method, cannot simultaneously provide both high efficiency and sufficient investment cost return. To solve this problem, the paper presents a new pricing model, namely Equivalent Marginal Cost Pricing (EMCP) model, which is based on the EVE pricing theory and the unique characteristics of heat products and district heating. The EMCP model uses exergy as the measurement of heating product value and places products from different district heating regions into the same competition platform. In the proposed model, the return on investment cost is closely related to the quoted cost, and within the limitations of the Heating Capacity Cost Reference and the maximum compensated shadow capacity cost, both lower and higher price speculations of heat producers are restricted. Simulation results show that the model can guide heat producers to bid according to their production costs and to provide reasonable returns on investment, which contributes to stimulate the role of price leverage and to promote the optimal allocation of heat resources. - Highlights: • Presents a new district heating pricing model. • Provides both high market efficiency and sufficient investment cost return. • Provides a competition mechanism for various products from different DH regions. • Both of lower and higher price speculations are restricted in the new model

  19. Integration of large-scale heat pumps in the district heating systems of Greater Copenhagen

    DEFF Research Database (Denmark)

    Bach, Bjarne; Werling, Jesper; Ommen, Torben Schmidt

    2016-01-01

    This study analyses the technical and private economic aspects of integrating a large capacity of electric driven HP (heat pumps) in the Greater Copenhagen DH (district heating) system, which is an example of a state-of-the-art large district heating system with many consumers and suppliers....... The analysis was based on using the energy model Balmorel to determine the optimum dispatch of HPs in the system. The potential heat sources in Copenhagen for use in HPs were determined based on data related to temperatures, flows, and hydrography at different locations, while respecting technical constraints...

  20. Solar heating - a major source of renewable energy

    International Nuclear Information System (INIS)

    Bosselaar, L.

    2001-01-01

    Actions that can be taken to increase the uptake of technology for solar water heaters and solar buildings are discussed. An overview of existing technology covers solar water heating, solar buildings, space heating, solar cooling, solar drying, solar desalination. Solar water heating, solar buildings and solar crop drying are discussed individually under the sub-headings of (a) the technology; (b) the market; (c) potential; (d) economics and (e) market acceleration strategies. Other subjects discussed are market acceleration, main opportunities, R and D needs and conclusions. The IEA solar heating and solar cooling programme is described

  1. Solar-assisted low energy dwellings

    Energy Technology Data Exchange (ETDEWEB)

    Esbensen, T V

    1980-02-01

    The Zero Energy House Group was formed as a subproject of the CCMS Solar Energy Pilot Study in 1974 by seven participating countries experimenting with solar-assisted low-energy dwellings for temperate and northern European climatic conditions. A Zero Energy House is one in which solar energy is used to meet the reduced energy needs of buildings incorporating various thermal energy conservation features. This final report of the Zero Energy House Group includes brief descriptions of 13 major low-energy dwellings in the participating CCMS countries. An overall assessment of the state-of-the-art in solar-assisted low-energy dwellings is also included.

  2. Characterization of a solar photovoltaic/loop-heat-pipe heat pump water heating system

    International Nuclear Information System (INIS)

    Zhang, Xingxing; Zhao, Xudong; Xu, Jihuan; Yu, Xiaotong

    2013-01-01

    coefficient (COP PV/T ) was 8.7. Impact of the operational parameters (i.e. solar radiation, air temperature, air velocity, heat-pump’s evaporation temperature, glazing covers, and number of the absorbing heat pipes) to the performance of the system (in terms of efficiencies of the PV/LHP module and the system’s overall performance coefficient COP PV/T ) was investigated individually. The results indicated that lower solar radiation, lower air temperature, higher air velocity and smaller cover number led to enhanced electrical efficiency but reduced thermal efficiency of the module; whereas lower heat-pump’s evaporation temperature and larger number of heat absorbing pipes gave rise to both thermal and electrical efficiencies of the module. The research results would assist in developing a high efficient solar (space or hot water) heating system and thus contribute to realisation of the energy saving and associated carbon emission targets set for buildings globally.

  3. Solar heating systems for houses. A design handbook for solar combisystems

    International Nuclear Information System (INIS)

    Weiss, W.

    2003-11-01

    A handbook giving guidance on systems for providing combined solar space heating and solar water heating for houses has been produced by an international team. The guidance focuses on selection of the optimum combi-system for groups of single-family houses and multi-family houses. Standard classification and evaluation procedures are described. The book should be a valuable tool for building engineers, architects, solar manufacturers and installers of solar solar energy systems, and anyone interested in optimizing combined water and space heating solar systems

  4. Proposal for a district heat supply system

    International Nuclear Information System (INIS)

    Alefeld, G.

    1976-01-01

    A district heating scheme is proposed which makes it possible to use the waste heat from power stations for the supply of households and industry. The heat is stored by evaporation of ammonia salts or liquids with dissolved salts. Both substances are transported on existing rail- or waterways to heating stations near the consumers, and the heat recovered by reaction of the two components. Then the product of reaction is transported back to the power stations, and reactivated by heat again. Based on a cost estimation, it can be shown that the proposed heat transport with heat trains or ships, at distances up to 100 km, results in heat costs which are to-day already below that of heat from fuel oil. The investment required for the heat transport system is unusually low due to the use of transport ways which already exist. The district heating system is not only favourable in respect of the environment, but actually reduces its present strain, both at the consumer and at the power stations. The technical advantages of the suggested concept, especially the possibility of introducing it in stages, are discussed. The consequences for the national economy regarding the safety of supply and the trade balance, as well as for the public transport undertakings, are obvious, and therefore not included in the paper. (orig.) [de

  5. Effects of heat and electricity saving measures in district-heated multistory residential buildings

    International Nuclear Information System (INIS)

    Truong, Nguyen Le; Dodoo, Ambrose; Gustavsson, Leif

    2014-01-01

    Highlights: • We analyzed the potential for energy savings in district heated buildings. • Measures that reduce more peak load production give higher primary energy savings. • Efficient appliances increase heat demand but give net primary energy savings. • Efficient appliances give the largest net primary energy savings. - Abstract: The effects of heat and electricity saving measures in district-heated buildings can be complex because these depend not only on how energy is used on the demand side but also on how energy is provided from the supply side. In this study, we analyze the effects of heat and electricity saving measures in multistory concrete-framed and wood-framed versions of an existing district-heated building and examine the impacts of the reduced energy demand on different district heat (DH) production configurations. The energy saving measures considered are for domestic hot water reduction, building thermal envelope improvement, ventilation heat recovery (VHR), and household electricity savings. Our analysis is based on a measured heat load profile of an existing DH production system in Växjö, Sweden. Based on the measured heat load profile, we model three minimum-cost DH production system using plausible environmental and socio-political scenarios. Then, we investigate the primary energy implications of the energy saving measures applied to the two versions of the existing building, taking into account the changed DH demand, changed cogenerated electricity, and changed electricity use due to heat and electricity saving measures. Our results show that the difference between the final and primary energy savings of the concrete-framed and wood-framed versions of the case-study building is minor. The primary energy efficiency of the energy saving measures depends on the type of measure and on the composition of the DH production system. Of the various energy saving measures explored, electricity savings give the highest primary energy savings

  6. Technology Roadmaps: Solar Heating and Cooling

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2012-09-06

    The solar heating and cooling (SHC) roadmap outlines a pathway for solar energy to supply almost one sixth (18 EJ) of the world's total energy use for both heating and cooling by 2050. This would save some 800 megatonnes of carbon dioxide (CO2) emissions per year; more than the total CO2 emissions in Germany in 2009. While solar heating and cooling today makes a modest contribution to world energy demand, the roadmap envisages that if concerted action is taken by governments and industry, solar energy could annually produce more than 16% of total final energy use for low temperature heat and nearly 17% for cooling. Given that global energy demand for heat represents almost half of the world's final energy use -- more than the combined global demand for electricity and transport -- solar heat can make a significant contribution in both tackling climate change and strengthening energy security.

  7. Technology Roadmaps: Solar Heating and Cooling

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2012-07-01

    The solar heating and cooling (SHC) roadmap outlines a pathway for solar energy to supply almost one sixth (18 EJ) of the world’s total energy use for both heating and cooling by 2050. This would save some 800 megatonnes of carbon dioxide (CO2) emissions per year; more than the total CO2 emissions in Germany in 2009. While solar heating and cooling today makes a modest contribution to world energy demand, the roadmap envisages that if concerted action is taken by governments and industry, solar energy could annually produce more than 16% of total final energy use for low temperature heat and nearly 17% for cooling. Given that global energy demand for heat represents almost half of the world’s final energy use – more than the combined global demand for electricity and transport – solar heat can make a significant contribution in both tackling climate change and strengthening energy security.

  8. Heat transport analysis in a district heating and snow melting system in Sapporo and Ishikari, Hokkaido applying waste heat from GTHTR300

    International Nuclear Information System (INIS)

    Kasahara, Seiji; Kamiji, Yu; Terada, Atsuhiko; Yan Xing; Inagaki, Yoshiyuki; Murata, Tetsuya; Mori, Michitsugu

    2015-01-01

    A district heating and snow melting system utilizing waste heat from Gas Turbine High temperature Gas Reactor of 300 MW_e (GTHTR300), a heat-electricity cogeneration design of high temperature gas-cooled reactor, was analyzed. Application areas are set in Sapporo and Ishikari, the heavy snowfall cities in Northern Japan. The heat transport analyses are carried out by modeling the components in the system; pipelines of the secondary water loops between GTHTR300s and heat demand district and heat exchangers to transport the heat from the secondary water loops to the tertiary loops in the district. Double pipe for the secondary loops are advantageous for less heat loss and smaller excavation area. On the other hand, these pipes has disadvantage of more electricity consumption for pumping. Most of the heat demand in the month of maximum requirement can be supplied by 2 GTHTR300s and delivered by 9 secondary loops and around 5000 heat exchangers. Closer location of GTHTR300 site to the heat demand district is largely advantageous economically. Less decrease of the distance from 40 km to 20 km made the heat loss half and cost of the heat transfer system 22% smaller. (author)

  9. Wind power integration in Aalborg Municipality using compression heat pumps and geothermal absorption heat pumps

    DEFF Research Database (Denmark)

    Østergaard, Poul Alberg

    2013-01-01

    -temperature geothermal resources. The analyses have also demonstrated that the municipality will still rely heavily on surrounding areas for electric load balancing assistance. With a departure in a previously elaborated 100% renewable energy scenario, this article investigates how absorption heat pumps (AHP......Aalborg Municipality, Denmark is investigating ways of switching to 100% renewable energy supply over the next 40 years. Analyses so far have demonstrated a potential for such a transition through energy savings, district heating (DH) and the use of locally available biomass, wind power and low......) and compression heat pumps (HP) for the supply of DH impact the integration of wind power. Hourly scenario-analyses made using the EnergyPLAN model reveal a boiler production and electricity excess which is higher with AHPs than with HPs whereas condensing mode power generation is increased by the application...

  10. Parametric sensitivity analysis of a SOLRGT system with the indirect upgrading of low/mid-temperature solar heat

    International Nuclear Information System (INIS)

    Li, Yuan Yuan; Zhang, Na; Cai, Rui Xian

    2012-01-01

    Highlights: ► A solar-assisted methane chemically recuperated gas turbine cycle has been proposed. ► The parametric sensitivity analysis of a SOLRGT system has been carried out. ► The concept of indirect upgrading of solar heat proves to be feasible. -- Abstract: Development of novel solar–fossil fuel hybrid system is important for the efficient utilization of low temperature solar heat. A solar-assisted methane chemically recuperated gas turbine (SOLRGT) system was proposed by Zhang and co-worker, which integrated solar heat into a high efficiency power system. The low temperature solar heat is first converted into vapor latent heat provided for a reformer, and then indirectly upgraded to high-grade generated syngas chemical energy by the reformation reaction. In this paper, based on the above mentioned cycle, a parametric analysis is performed using ASPEN PLUS code to further evaluate the effect of key thermodynamics parameters on the SOLRGT performance. It can be shown that solar collector temperature, steam/air mass ratio, turbine inlet pressure, and turbine inlet temperature have significant effects on system efficiency, solar-to-electricity efficiency, fossil fuel saving ratio, specific CO 2 emission and so on. The solar collector temperature is varied between 140 and 240 °C and the maximum net solar-to-electricity efficiency and system efficiency for a given turbine inlet condition (turbine inlet temperature of 1308 °C and pressure ratio of 15) is 30.2% and 52.9%, respectively. The fossil fuel saving ratio can reach up to 21.8% and the reduction of specific CO 2 emission is also 21.8% compared to the reference system. The system performance is promising for an optimum pressure ratio at a given turbine inlet temperature.

  11. 太阳能热泵应用现状与性能分析%Application Situation and Performance Analysis of Solar-assisted Heat Pump(SAHP)

    Institute of Scientific and Technical Information of China (English)

    魏翠琴; 王丽萍; 贾少刚; 高志宏

    2017-01-01

    太阳能是清洁可再生能源,热泵是高效节能技术,两者有机结合应用既提高了太阳能集热器效率和热泵性能,又拓宽了应用范围,使其实用性大大增强.在介绍太阳能热泵系统的分类与工作原理基础上,概括了各类太阳能热泵的优缺点,总结了国内外该技术的应用和研究现状,着重分析了非直膨式太阳能热泵系统性能的影响因素——集热器安装朝向和角度、热泵的蒸发温度和冷凝温度是影响系统性能的主要因素.%Solar energy is clean and renewable, similarly heat pump has the features of high efficiency and excellent energy saving. The combination application of solar energy and heat pump could improve the efficiency of solar collectors and heat pump performance, meanwhile the application range and utility are greatly enhanced. The classification and working principle of Solar-assisted heat pump (SAHP) system is introduced in this paper, the advantages and disadvantages of SAHP were summarized, the domestic and overseas application of SAHP were summarized, the performance influence factors of indirect expansion SAHP were analyzed, the installed orientation and angle of tilt of Solar collector, heat pump evaporation temperature and condensation temperature are the main factors influencing the performance of the system.

  12. Smart energy systems and 4th generation district heating

    DEFF Research Database (Denmark)

    Lund, Henrik; Duic, Neven; Østergaard, Poul Alberg

    2016-01-01

    scientific understanding on how we can design and implement a suitable and least-cost transformation into a sustainable energy future. The concept of Smart Energy Systems emphasizes the importance of being coherent and cross-sectoral when the best solutions are to be found and how this also calls......This editorial gives an introduction to the important relationship between Smart Energy Systems and 4th Generation District Heating and presents a number of selected papers from the 1st International Conference on the topic. All of the papers elaborate on or otherwise contribute to the theoretical...... for the active inclusion of the heating and cooling sectors. The concept of 4th Generation District Heating emphasizes that district heating and cooling are both important elements but also technologies that have to be developed further into a 4th generation version to be able to fulfil their roles in future...

  13. Geothermal direct-heat utilization assistance. Quarterly project progress report, October--December 1997

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1997-01-01

    This report summarizes geothermal technical assistance, R and D and technology transfer activities of the Geo-Heat Center at Oregon Institute of Technology for the first quarter of FY-98 (October--December 1997). It describes 216 contacts with parties during this period related to technical assistance with geothermal direct heat projects. Areas dealt with include requests for general information including maps and material for high school debates, and material on geothermal heat pumps, resource and well data, space heating and cooling, greenhouses, aquaculture, equipment, district heating, resorts and spas, industrial applications, electric power and snow melting. Research activities include work on model construction specifications of lineshaft submersible pumps and plate heat exchangers, a comprehensive aquaculture developer package and revisions to the Geothermal Direct Use Engineering and Design Guidebook. Outreach activities include the publication of the Quarterly Bulletin (Vol. 18, No. 4) which was devoted entirely to geothermal activities in South Dakota, dissemination of information mainly through mailings of publications, tours of local geothermal uses, geothermal library acquisition and use, participation in workshops, short courses and technical meetings by the staff, and progress monitor reports on geothermal activities.

  14. Steady-state heat losses in pipes for low-energy district heating

    DEFF Research Database (Denmark)

    Dalla Rosa, Alessandro; Li, Hongwei; Svendsen, Svend

    2010-01-01

    The synergy between highly energy efficient buildings and low-energy district heating (DH) systems is a promising concept for the optimal integration of energy saving policies and energy supply systems based on renewable energy (RE). Distribution heat losses represent a key factor in the design o...

  15. Solar Air Heaters with Thermal Heat Storages

    OpenAIRE

    Saxena, Abhishek; Goel, Varun

    2013-01-01

    Solar energy can be converted into different forms of energy, either to thermal energy or to electrical energy. Solar energy is converted directly into electrical power by photovoltaic modules, while solar collector converts solar energy into thermal energy. Solar collector works by absorbing the direct solar radiation and converting it into thermal energy, which can be stored in the form of sensible heat or latent heat or a combination of sensible and latent heats. A theoretical study has be...

  16. Solar-assisted ground-source heat pump system design and case study%太阳能辅助地埋管地源热泵系统设计及实例分析

    Institute of Scientific and Technical Information of China (English)

    季永明; 端木琳; 李祥立

    2017-01-01

    Presents an improved method to determine the solar collector area of the solar-assisted ground-source heat pump system based on the heat balance method.For a commercial building in Dalian,proposes the design scheme of a solar-assisted ground-source heat pump system.Simulates the operating parameters of the system by TRNSYS,and the results show that,on the basis of ensuring the heating capacity of the building,the system guarantees the average temperature of the thermal storage soil which contains the ground heat exchanger periodic and consistent change,and the COP of the heat pump is improved significantly compared with that of the system without solar collectors in winter.%基于热平衡法提出了确定太阳能辅助地埋管地源热泵系统中太阳能集热器面积的方法.针对大连地区一公共建筑,提出了太阳能辅助地埋管地源热泵系统设计方案.采用TRNSYS软件对该系统运行参数进行了仿真模拟,结果显示,在保证建筑供热量的基础上,系统能长期保证热泵源侧换热器所在蓄热土壤平均温度呈周期性一致变化,且冬季热泵机组COP较无集热器工况显著提高.

  17. The market potential for solar heating plants in some European countries

    Energy Technology Data Exchange (ETDEWEB)

    Zinko, H; Bjaerklev, J.; Margen, P. [ZW Energiteknik AB, Nykoeping (Sweden)

    1996-03-01

    This study evaluates the market potential for solar collectors for residential heating in six European countries: Sweden, Denmark, Germany, Netherlands, Italy and Greece. The study is based on statistical information about the population, buildings, energy consumption and climatic conditions in the respective regions. The market potential was determined for systems supplying hot water and space heating in small houses and multi family houses, as well as for central block heating and district heating systems. Only systems with diurnal storage were taken into account. The technical potential was derived by analyzing the available roof areas, making allowance construction obstacles, unfavourable orientation, shadowing etc. Furthermore, commercial considerations, such as cost of competing energy sources, e.g. cogeneration and other low cost sources were considered. In accordance with our expectations, we assumed that the solar costs will decrease by 30 to 50% and that the market will increase by 30%/year during the next ten years, due to growing energy prices and by public financial support in an initial phase. It was found that there exists a commercial solar energy market in Greece for small systems and that the market could be nearly commercial in Italy. In the other countries the market must be stimulated by subsidies in order to take off. The total net potential for solar collectors in the six countries was found to about 100 Mm{sup 2} for small systems, and 60 Mm{sup 2} for large systems, corresponding to about 70 TWh/year. In a rough estimate we can say that the net solar collector market potential is about 1 m{sup 2}/inhabitant in north and central Europe, and 0.5m{sup 2} in south Europe. Although systems for seasonal storage were not included in our analysis, it is probable that these systems will increase the net market potential by a factor of 2-3. 9 refs

  18. The market potential for solar heating plants in some European countries

    International Nuclear Information System (INIS)

    Zinko, H.; Bjaerklev, J.; Margen, P.

    1996-03-01

    This study evaluates the market potential for solar collectors for residential heating in six European countries: Sweden, Denmark, Germany, Netherlands, Italy and Greece. The study is based on statistical information about the population, buildings, energy consumption and climatic conditions in the respective regions. The market potential was determined for systems supplying hot water and space heating in small houses and multi family houses, as well as for central block heating and district heating systems. Only systems with diurnal storage were taken into account. The technical potential was derived by analyzing the available roof areas, making allowance construction obstacles, unfavourable orientation, shadowing etc. Furthermore, commercial considerations, such as cost of competing energy sources, e.g. cogeneration and other low cost sources were considered. In accordance with our expectations, we assumed that the solar costs will decrease by 30 to 50% and that the market will increase by 30%/year during the next ten years, due to growing energy prices and by public financial support in an initial phase. It was found that there exists a commercial solar energy market in Greece for small systems and that the market could be nearly commercial in Italy. In the other countries the market must be stimulated by subsidies in order to take off. The total net potential for solar collectors in the six countries was found to about 100 Mm 2 for small systems, and 60 Mm 2 for large systems, corresponding to about 70 TWh/year. In a rough estimate we can say that the net solar collector market potential is about 1 m 2 /inhabitant in north and central Europe, and 0.5m 2 in south Europe. Although systems for seasonal storage were not included in our analysis, it is probable that these systems will increase the net market potential by a factor of 2-3. 9 refs

  19. Nuclear district heating. 1. Process heat reactors and transmission and distribution networks

    International Nuclear Information System (INIS)

    Caizergues, R.

    1979-01-01

    Three kinds of production station are considered: joint electricity and heat-producing stations, heat-producing stations with CAS reactors and heat-producing stations with Thermos reactors. The thermal energy supply possibilities of these stations, the cost price of this energy and the cost price per therm produced by the district heating source and conveyed to the user are studied [fr

  20. Solar heating pipe

    Energy Technology Data Exchange (ETDEWEB)

    Hinson-Rider, G.

    1977-10-04

    A fluid carrying pipe is described having an integral transparent portion formed into a longitudinally extending cylindrical lens that focuses solar heat rays to a focal axis within the volume of the pipe. The pipe on the side opposite the lens has a heat ray absorbent coating for absorbing heat from light rays that pass through the focal axis.

  1. Utilization of low-temperature heat sources for heat and power production

    DEFF Research Database (Denmark)

    Haglind, Fredrik; Elmegaard, Brian

    2014-01-01

    Low-temperature heat sources are available in many applications, ranging from waste heat from marine diesel engines, industries and refrigeration plants to biomass, geothermal and solar heat sources. There is a great potential for enhancing the utilization of these heat sources by novel...

  2. A nuclear reactor for district heating

    International Nuclear Information System (INIS)

    Bancroft, A.R.; Fenton, N.

    1989-07-01

    Global energy requirements are expected to double over the next 40 years. In the northern hemisphere, many countries consume in excess of 25 percent of their primary energy supply for building heating. Satisfying this need, within the constraints now being acknowledged for sustainable global development, provides an important opportunity for district heating. Fuel-use flexibility, energy and resource conservation, and reduced atmospheric pollution from acid gases and greenhouse gases, are important features offered by district heating systems. Among the major fuel options, only hydro-electricity and nuclear heat completely avoid emissions of combustion gases. To fill the need for an economical nuclear heat source, Atomic Energy of Canada Limited has designed a 10 MW plant that is suitable as a heat source within a network or as the main supply to large individual users. Producing hot water at temperatures below 100 degrees C, it incorporates a small pool-type reactor based on AECL's successful SLOWPOKE Research Reactor. A 2 MW prototype for the commercial unit is now being tested at the Whiteshell Nuclear Research Establishment in Manitoba. With capital costs of $7 million (Canadian), unit energy costs are projected to be $0.02/kWh for a 10 MW unit operating in a heating grid over a 30-year period. By keeping the reactor power low and the water temperature below 100 degrees C, much of the complexity of the large nuclear power plants can be avoided, thus allowing these small, safe nuclear heating systems to be economically viable

  3. Performance of low-temperature district heating for low-energy houses

    DEFF Research Database (Denmark)

    Brand, Marek; Dalla Rosa, Alessandro; Svendsen, Svend

    2010-01-01

    A Low Energy District Heating (LEDH) network supplying district heating water with temperature 50°C was built in Lærkehaven-Lystrup, Denmark, as a part of the ongoing “Energy Technology Development and Demonstration Programme” [EUDP, 2008] focused on “CO2-reduction in low energy buildings and com...

  4. Competition in the market for space heating. District heating as the infrastructure for competition among fuels and technologies

    International Nuclear Information System (INIS)

    Grohnheit, Poul Erik; Gram Mortensen, Bent Ole

    2003-01-01

    None of the EU directives on liberalisation of the electricity and gas markets are considering the district heating systems, although the district heating networks offer the possibility of competition between natural gas and a range of other fuels on the market for space heating. Cogeneration of electricity and heat for industrial processes or district heating is a technology option for increased energy efficiency and thus reduction of CO 2 emissions. In the mid-1990s less than 10% of the electricity generation in the European Union was combined production with significant variations among Member States. These variations are explained by different national legislation and relative power of institutions, rather than difference in industrial structure, climate or urban physical structure. The 'single energy carrier' directives have provisions that support the development of combined heat and power (CHP), but they do not support the development and expansion of the district heating infrastructure. The article is partly based on a contribution to the Shared Analysis Project for the European Commission DG Energy, concerning the penetration of CHP, energy saving, and renewables as instruments to meet the targets of the Kyoto Protocol within the liberalised European energy market. The quantitative and legal differences of the heat markets in selected Member States are described, and the consequences of the directives are discussed. Finally, we summarise the tasks for a European policy concerning the future regulation of district heating networks for CHP, emphasising the need for rules for a fair competition between natural gas and district heating networks

  5. Predicting the Heat Consumption in District Heating Systems using Meteorological Forecasts

    DEFF Research Database (Denmark)

    Nielsen, Henrik Aalborg, orlov 31.07.2008; Madsen, Henrik

    that meteorological forecasts are available on-line. Such a service has recently been introduced by the Danish Meteorological Institute. However, actual meteorological forecasts has not been available for the work described here. Assuming the climate to be known the mean absolute relative prediction error for 72 hour......Methods for on-line prediction of heat consumption in district heating systems hour by hour for horizons up to 72 hours are considered in this report. Data from the district heating system Vestegnens Kraftvarmeselskab I/S is used in the investigation. During the development it has been assumed......, this is somewhat contrary to practice. The work presented is a demonstration of the value of the so called gray box approach where theoretical knowledge about the system under consideration is combined with information from measurements performed on the system in order to obtain a mathematical description...

  6. LCA of domestic and centralized biomass combustion: The case of Lombardy (Italy)

    International Nuclear Information System (INIS)

    Caserini, S.; Livio, S.; Giugliano, M.; Grosso, M.; Rigamonti, L.

    2010-01-01

    This paper analyzes and compares the environmental impacts of biomass combustion in small appliances such as domestic open fireplaces and stoves, and in two types of centralized combined heat and power plants, feeding district heating networks. The analysis is carried out following a Life Cycle Assessment (LCA) approach. The expected savings of GHG (greenhouse gases) emissions due to the substitution of fossil fuels with biomass are quantified, as well as emissions of toxic pollutants and substances responsible for acidification and ozone formation. The LCA results show net savings of GHG emissions when using biomass instead of conventional fuels, varying from 0.08 to 1.08 t of CO 2 eq. per t of dry biomass in the different scenarios. Avoided GHG emissions thanks to biomass combustion in Lombardy are 1.32 Mt year -1 (1.5% of total regional GHG emissions). For the other impact categories, the use of biomass in district heating systems can again cause a consistent reduction of impacts, whereas biomass combustion in residential devices shows higher impacts than fossil fuels with a particular concern for PAH, VOC and particulate matter emissions. For example, in Lombardy, PM10 emissions from domestic devices are about 8100 t year -1 , corresponding to almost one third of the total particulate emissions in 2005. (author)

  7. Results of heating mode performance tests of a solar-assisted heat pump

    Science.gov (United States)

    Jones, C. B.; Smetana, F. O.

    1979-01-01

    The performance of a heat pump, utilizing 8.16 square meters of low-cost solar collectors as the evaporator in a Freon-114 refrigeration cycle, was determined under actual insolation conditions during the summer and fall of 1976. C.O.P.'s (coefficient of performance) greater than 3 were obtained with condensing temperatures around 78 C and evaporating temperatures around 27 C. Ambient temperatures were about 3 C above evaporating temperatures. Similar performance levels were obtained at other insolation and temperature conditions. Experience with the system has identified some component and system changes which should increase the obtainable C.O.P. to about 4.0. These are described along with the system's design rationale. The accumulated data are presented as an appendix.

  8. The Potential for Biomass District Energy Production in Port Graham, Alaska

    Energy Technology Data Exchange (ETDEWEB)

    Charles Sink, Chugachmiut; Keeryanne Leroux, EERC

    2008-05-08

    This project was a collaboration between The Energy & Environmental Research Center (EERC) and Chugachmiut – A Tribal organization Serving the Chugach Native People of Alaska and funded by the U.S. Department of Energy (DOE) Tribal Energy Program. It was conducted to determine the economic and technical feasibility for implementing a biomass energy system to service the Chugachmiut community of Port Graham, Alaska. The Port Graham tribe has been investigating opportunities to reduce energy costs and reliance on energy imports and support subsistence. The dramatic rise in the prices of petroleum fuels have been a hardship to the village of Port Graham, located on the Kenai Peninsula of Alaska. The Port Graham Village Council views the forest timber surrounding the village and the established salmon industry as potential resources for providing biomass energy power to the facilities in their community. Benefits of implementing a biomass fuel include reduced energy costs, energy independence, economic development, and environmental improvement. Fish oil–diesel blended fuel and indoor wood boilers are the most economical and technically viable options for biomass energy in the village of Port Graham. Sufficient regional biomass resources allow up to 50% in annual heating savings to the user, displacing up to 70% current diesel imports, with a simple payback of less than 3 years for an estimated capital investment under $300,000. Distributive energy options are also economically viable and would displace all imported diesel, albeit offering less savings potential and requiring greater capital. These include a large-scale wood combustion system to provide heat to the entire village, a wood gasification system for cogeneration of heat and power, and moderate outdoor wood furnaces providing heat to 3–4 homes or community buildings per furnace. Coordination of biomass procurement and delivery, ensuring resource reliability and technology acceptance, and arbitrating

  9. Design and safety aspects of nuclear district heating reactors

    International Nuclear Information System (INIS)

    Brogli, R.; Mathews, D.; Pelloni, S.

    1989-01-01

    Extensive studies on the rationale, the potential and the technology of nuclear district heating have been performed in Switzerland. Beside economics the safety aspects were of primary importance. Due to the high costs to transport heat the heating reactor tend to be small and therefore, minimally staffed and located close to population centers. Stringed safety rules are therefore applying. Gas cooled reactors are well suited as district heating reactors since they have due to their characteristics several inherent features, significant safety margins and a remarkable radioactivity retention potential. Some ways to mitigate the effects of water ingress and graphite corrosion are under investigation. (author). 5 refs, 3 figs

  10. Comparison of district heating expansion potential based on consumer-economy or socio-economy

    DEFF Research Database (Denmark)

    Grundahl, Lars; Nielsen, Steffen; Lund, Henrik

    2016-01-01

    Recent studies show that a high share of district heating is an important part of a future sustainable energy system or smart energy system with a high renewable energy penetration. These studies also show socio-economic benefits of expanding the district heating coverage. However, in order...... to implement such an expansion, district heating needs to be economically feasible for the heat consumers. This aspect is often not investigated and hence it is unknown if calculations based on consumer-economy, where tax payment is included, will yield the same potential of expansion. This study identifies...... the differences in the expansion potential of district heating calculated with a socio-economic and a consumer-economic approach, respectively, in a case study of Denmark. By also investigating the consumer-economy of expanding district heating, a deeper insight is obtained of possible locations for expanding...

  11. Vilnius district heating pilot project. Final report. Annex 1-14

    International Nuclear Information System (INIS)

    1995-03-01

    The present energy scenario model is based on the SYSTEM ROERNET energy planning module and includes the energy flows from the energy source to the consumer for space heating and domestic hot water. The energy sources are: District heating of City based on CHP or/and heat-only production. District heating of Naujoji Vilnia based on heat-only production. Local boilers using natural gas or heavy fuel oil. Stoves using kerosene, coke or wood. (Electricity panel might be included, but this has not been the case in the actual analyses). The calculations of the energy model results in estimation of: Annual heat production, especially simulation of the plant production for district heating system with the possibility of integrated pooled operation by giving an order of priority to each plant based on the efficiency of the plant. Annual fuel consumption and the fuel costs for the society. Annual electricity production and its value to the society. Annual operation and maintenance costs including costs connected with consumption of electricity for district heating purposes. The total annual investments due to the set of options applied in the scenario in question. Savings in plant investments if less production capacity is necessary in scenarios where the heat demand is decreasing. The flue gas emissions from the heat and CHP production in the Vilnius area are estimated by CO 2 , SO 3 , NO x and particulates. These emissions are not reduced by the possible savings of electricity production of a reference power-only plant outside Vilnius. (EG)

  12. District heating from coal cures Germany's oil phobia

    Energy Technology Data Exchange (ETDEWEB)

    Cooper, G.

    1982-04-30

    Germany's firm commitment to district heating, energy conservation and renewable energy was the most striking impression to emerge from this year's Hanover Fair. Despite the present low price of oil, industry and government are resolved to reduce the country's dependence on this fuel. Although oil now accounts for only 44 per cent of German's total energy consumption, compared with 55 per cent in 1972, price rises and economic stagnation mean that its value is now equivalent to some 20 per cent of the country's exports compared with just 6 per cent in 1972. Space and process heating are the biggest oil users. District heating schemes, heat pumps and waste-heat recovery are all being vigorously promoted to reduce the oil demand from these sectors. A recent study by the German Ministry of Research and Technology estimates that 25 per cent of all domestic heat could be delivered economically by district heating, some three times the present installed capacity.

  13. The turbulent cascade and proton heating in the solar wind during solar minimum

    International Nuclear Information System (INIS)

    Coburn, Jesse T.; Smith, Charles W.; Vasquez, Bernard J.; Stawarz, Joshua E.; Forman, Miriam A.

    2013-01-01

    Solar wind measurements at 1 AU during the recent solar minimum and previous studies of solar maximum provide an opportunity to study the effects of the changing solar cycle on in situ heating. Our interest is to compare the levels of activity associated with turbulence and proton heating. Large-scale shears in the flow caused by transient activity are a source that drives turbulence that heats the solar wind, but as the solar cycle progresses the dynamics that drive the turbulence and heat the medium are likely to change. The application of third-moment theory to Advanced Composition Explorer (ACE) data gives the turbulent energy cascade rate which is not seen to vary with the solar cycle. Likewise, an empirical heating rate shows no significan changes in proton heating over the cycle.

  14. European research school on large scale solar thermal – SHINE

    DEFF Research Database (Denmark)

    Bales, Chris; Forteza, Pau Joan Cortés; Furbo, Simon

    2014-01-01

    The Solar Heat Integration NEtwork (SHINE) is a European research school in which 13 PhD students in solar thermal technologies are funded by the EU Marie-Curie program. It has five PhD course modules as well as workshops and seminars dedicated to PhD students both within the project as well...... as outside of it. The SHINE research activities focus on large solar heating systems and new applications: on district heating, industrial processes and new storage systems. The scope of this paper is on systems for district heating for which there are five PhD students, three at universities and two...

  15. Yearly thermal performances of solar heating plants in Denmark – Measured and calculated

    DEFF Research Database (Denmark)

    Furbo, Simon; Dragsted, Janne; Perers, Bengt

    2018-01-01

    The thermal performance of solar collector fields depends mainly on the mean solar collector fluid temperature of the collector field and on the solar radiation. For Danish solar collector fields for district heating the measured yearly thermal performances per collector area varied in the period...... 2012–2016 between 313 kWh/m2 and 577 kWh/m2, with averages between 411 kWh/m2 and 463 kWh/m2. The percentage difference between the highest and lowest measured yearly thermal performance is about 84%. Calculated yearly thermal performances of typically designed large solar collector fields at six...... different locations in Denmark with measured weather data for the years 2002–2010 vary between 405 kWh/m2 collector and 566 kWh/m2 collector, if a mean solar collector fluid temperature of 60 °C is assumed. This corresponds to a percentage difference between the highest and lowest calculated yearly thermal...

  16. High temperature solar heating and cooling systems for different Mediterranean climates: Dynamic simulation and economic assessment

    International Nuclear Information System (INIS)

    Calise, Francesco

    2012-01-01

    The paper presents a dynamic model of an innovative solar heating and cooling system (SHC) based on the coupling of Parabolic Trough Collectors (PTC) with a double-stage LiBr-H 2 O absorption chiller; auxiliary energy for both heating and cooling is supplied by a biomass-fired heater. The system layout also includes a number of additional components such as: cooling tower, pumps, heat exchangers, etc. The consumption of non-renewable energy resources is only due to the small amount of electrical energy consumed by some auxiliary device. A case study is presented, in which the SHC provides space heating and cooling and domestic hot water for a small university hall, all year long. Both the SHC system and the building were dynamically simulated in TRNSYS. In order to evaluate the performance of the investigated system in various climatic conditions, the analyses were performed for seven Mediterranean cities in Italy, Spain, Egypt, France, Greece and Turkey. The analysis was also performed for a similar SHC in which the biomass heater was replaced by a gas-fired heater, in order to evaluate the influence of biomass to the overall system economic and energetic performance. In addition, a parametric analysis was performed in order to evaluate the sensitivity of the results, when varying some of the main design and operating parameters, such as: collector field area, tank volume and set-point temperatures. The results showed that the SHC system layout investigated can be competitive for the majority of the locations analysed, although the economic profitability is higher for the hottest climates. - Highlights: → In the high temperature SHC system the auxiliary heat is provided by biomass. → The energetic performance of the system is excellent during the summer. → In the winter the system suffers of the low beam radiation incident on the PTC. → The Simple Pay Back Period is encouraging, particularly in case of public funding. → An increase of the solar field

  17. From waste to raw material -- The route from biomass to wood ash for cadmium and other heavy metals

    NARCIS (Netherlands)

    Obernberger, I.; Narodoslawsky, M.

    1997-01-01

    Energetic utilization of biomass is considered an environmentally safe way of providing energy, especially for process heat and district - heating purposes. The main advantage of energy from biomass is the CO-neutrality of this energy-production process. However, this process produces a solid

  18. Performance investigation of a solar-assisted direct contact membrane distillation system

    KAUST Repository

    Kim, Youngdeuk

    2013-01-01

    This paper presents a solar-assisted direct contact membrane distillation (DCMD) system with novel energy recovery concepts for a continuous 24-h-a-day operation. A temperature modulating scheme is introduced to the solar-thermal system that supplies feed seawater to the DCMD modules. This scheme attenuates extreme temperature fluctuations of the feed water by storing the collected energy during solar-peak hours and reutilizing it throughout the day. Thus, the energy savings is realized yet the feed seawater temperature is maintained within the desired range. Additionally, the system employs heat recovery from the permeate and brine streams to the feed seawater. The simulations for such a system with a shell-and-tube type DCMD modules are carried out to examine the spatial property variations and the sensitivity of system performance (i.e., transmembrane pressure, permeate flux and performance ratio) to the operating conditions (inlet temperature and flow rate) and the fiber dimensions (fiber length and packing density). It is found that there are trade-offs between mean permeate flux and performance ratio with respect to permeate inlet temperature and flow rate and between total distillate production and performance ratio with respect to packing density. For the solar-assisted DCMD system having evacuated-tube collectors of 3360m2 with 160m3 seawater storage tanks and 50 DCMD modules, the annual solar fraction and the collector efficiency are found to be 77% and 53%, respectively, whilst the overall permeate production capacity is 31m3/day. The overall specific thermal energy consumption of the DCMD system with heat recovery is found to be 436kWh/m3 and it is about 43% lower as compared to the system without heat recovery. It is observed that the specific thermal energy consumption decreases significantly by 55% with increased collector area from 1983m2 to 3360m2 whereas the specific electrical energy consumption increases slightly by 16%. © 2012 Elsevier B.V.

  19. The TX-model - a quantitative heat loss analysis of district heating pipes by means of IR surface temperature measurements

    Energy Technology Data Exchange (ETDEWEB)

    Zinki, Heimo [ZW Energiteknik, Nykoeping (Sweden)

    1996-11-01

    The aim of this study was to investigate the possibility of analysing the temperature profile at the ground surface above buried district heating pipes in such a way that would enable the quantitative determination of heat loss from the pair of pipes. In practical applications, it is supposed that this temperature profile is generated by means of advanced IR-thermography. For this purpose, the principle of the TX - model has been developed, based on the fact that the heat losses from pipes buried in the ground have a temperature signature on the ground surface. Qualitative analysis of this temperature signature is very well known and in practical use for detecting leaks from pipes. These techniques primarily make use of relative changes of the temperature pattern along the pipe. In the quantitative heat loss analysis, however, it is presumed that the temperature profile across the pipes is related to the pipe heat loss per unit length. The basic idea is that the integral of the temperature profile perpendicular to the pipe, called TX, is a function of the heat loss, but is also affected by other parameters such as burial depth, heat diffusivity, wind, precipitation and so on. In order to analyse the parameters influencing the TX- factor, a simulation model for the energy balance at the ground surface has been developed. This model includes the heat flow from the pipe to the surface and the heat exchange at the surface with the environment due to convection, latent heat change, solar and long wave radiation. The simulation gives the surprising result that the TX factor is by and large unaffected during the course of a day even when the sun is shining, as long as other climate conditions are relatively stable (low wind, no rain, no shadows). The results from the simulations were verified at different sites in Denmark, Finland, Sweden and USA through a co-operative research program organised and partially financed by the IEA District Heating Programme, Task III, and

  20. Solar Heating Systems with Evacuated Tubular Solar Collector

    DEFF Research Database (Denmark)

    Qin, Lin; Furbo, Simon

    1998-01-01

    Recently different designed evacuated tubular solar collectors were introduced on the market by different Chinese companies. In the present study, investigations on the performance of four different Chinese evacuated tubular collectors and of solar heating systems using these collectors were...... carried out, employing both laboratory test and theoretical calculations. The collectors were tested in a small solar domestic hot water (SDHW) system in a laboratory test facility under realistic conditions. The yearly thermal performance of solar heating systems with these evacuated tubular collectors......, as well as with normal flat-plate collectors was calculated under Danish weather conditions. It is found that, for small SDHW systems with a combi tank design, an increase of 25% -55% net utilized solar energy can be achieved by using these evacuated tubular collectors instead of normal flat...

  1. Opportunities for District Heating Systems in Ukraine. Market survey. Final report

    Energy Technology Data Exchange (ETDEWEB)

    Brienen, M.

    2011-12-15

    The market survey should identify the existing and future opportunities for Dutch companies in the district heating sector in Ukraine, facilitate better understanding of the sector specifics by providing a complete picture on the whole district heating chain at specific cities mentioned and surrounding areas, and provide practical information on the best ways to enter this market segment by Dutch companies. The points of special interest are: (a) Analysis of main types of district heating chain in terms of the key stakeholders and their interest; Identification of the cases where the whole chain is under control (if any); Identification of the main directions of change within the existing set-up; (b) Analysis of the pricing model(s) and the procedures for setting up the prices for district heating; Identification of the main influencers on the decision making; (c) Identification of the main opportunities to use renewable energy for heating systems in Ukraine; and (d) Identification of the Dutch clusters with appropriate products, services and knowledge which can be used to achieve optimal results with district heating systems in Ukraine. Another important reason to execute this market survey is the 2g at-sign thereprogramme 'Ukraine-sustainable energy'. One of the consortia supported under the 2g at-sign there programme, is called NUSEP, Netherlands Ukrainian Sustainable Energy Platform. Under this platform 15-20 Dutch companies and institutes have joined forces. All of these companies and institutes are active in the field of(sustainable) energy. In short, the district heating sector in Ukraine offers many opportunities for Dutch companies. This survey will help Dutch companies to do business in Ukraine. The market research has been executed at both national level (where relevant concerns) and is specifically focused on the following cities and surrounding area: Kiev; Poltava; Kamyanets-Podilsky; Kovel; Lviv; Zhytomyr. Since the major developments in

  2. A Co-Powered Biomass and Concentrated Solar Power Rankine Cycle Concept for Small Size Combined Heat and Power Generation

    Directory of Open Access Journals (Sweden)

    Eileen Tortora

    2013-03-01

    Full Text Available The present work investigates the matching of an advanced small scale Combined Heat and Power (CHP Rankine cycle plant with end-user thermal and electric load. The power plant consists of a concentrated solar power field co-powered by a biomass furnace to produce steam in a Rankine cycle, with a CHP configuration. A hotel was selected as the end user due to its high thermal to electric consumption ratio. The power plant design and its operation were modelled and investigated by adopting transient simulations with an hourly distribution. The study of the load matching of the proposed renewable power technology and the final user has been carried out by comparing two different load tracking scenarios, i.e., the thermal and the electric demands. As a result, the power output follows fairly well the given load curves, supplying, on a selected winter day, about 50 GJ/d of thermal energy and the 6 GJ/d of electric energy, with reduced energy dumps when matching the load.

  3. Energy cascading in large district heating systems

    International Nuclear Information System (INIS)

    Mayer, F.W.

    1978-01-01

    District heat transfer is the most economical utilization of the waste heat of power plants. Optimum utilization and heat transfer over large distances are possible because of a new energy distribution system, the ''energy cascading system,'' in which heat is transferred to several consumer regions at different temperature ranges. It is made more profitable by the use of heat pumps. The optimum flow-line temperature is 368 0 K, and the optimum return-line temperature is 288 0 K, resulting in an approximately 50% reduction of electric power loss at the power plant

  4. Design of A District Heating System Including The Upgrading of Residual Industrial Waste Heat

    NARCIS (Netherlands)

    Falcao, P.W.; Mesbah, A.; Suherman, M.V.; Wennekes, S.

    2005-01-01

    This study was aimed to evaluate the feasibility of using a waste heat stream from DSM for a District Heating System. A conceptual design was carried out with emphasis on the unit for upgrading the residual waste heat. Having reviewed heat pump technology, mechanical heat pump was found to be the

  5. Low-temperature nuclear heat applications: Nuclear power plants for district heating

    International Nuclear Information System (INIS)

    1987-08-01

    The IAEA reflected the needs of its Member States for the exchange of information in the field of nuclear heat application already in the late 1970s. In the early 1980s, some Member States showed their interest in the use of heat from electricity producing nuclear power plants and in the development of nuclear heating plants. Accordingly, a technical committee meeting with a workshop was organized in 1983 to review the status of nuclear heat application which confirmed both the progress made in this field and the renewed interest of Member States in an active exchange of information about this subject. In 1985 an Advisory Group summarized the Potential of Low-Temperature Nuclear Heat Application; the relevant Technical Document reviewing the situation in the IAEA's Member States was issued in 1986 (IAEA-TECDOC-397). Programme plans were made for 1986-88 and the IAEA was asked to promote the exchange of information, with specific emphasis on the design criteria, operating experience, safety requirements and specifications for heat-only reactors, co-generation plants and power plants adapted for heat application. Because of a growing interest of the IAEA's Member States about nuclear heat employment in the district heating domaine, an Advisory Group meeting was organized by the IAEA on ''Low-Temperature Nuclear Heat Application: Nuclear Power Plants for District Heating'' in Prague, Czechoslovakia in June 1986. The information gained up to 1986 and discussed during this meeting is embodied in the present Technical Document. 22 figs, 11 tabs

  6. Energy from Waste and Biomass - ALTENER Conference held in Estonia

    International Nuclear Information System (INIS)

    Roos, Inge

    1999-01-01

    On November 9-10, 1998 ALTENER Conference Energy from Waste and Biomass took place in the hotel Pirita, Tallinn, Estonia. The Conference was organized by the Swedish National Energy Administration in co-operation with the FEMOPET Estonia and the South Jutland University Centre, Biomass Institute (Denmark). The main topics of the Conference were: collecting biogas from landfall, biogas from municipal sewage treatment, biogas from animal manure, waste heat, biomass from the pulp industry and the sawmill, biomass from forestry, biomass for local and district heating. More than 200 delegates from 14 countries participated in this event. A poster exhibition and two study tours to Paeaeskuela Landfill Plant and Jueri Boiler House were organised too. (author)

  7. Inter-cooler in solar-assisted refrigeration system: Theory and experimental verification

    Directory of Open Access Journals (Sweden)

    Zheng Hui-Fan

    2015-01-01

    Full Text Available An inter-cooler in the solar-assisted refrigeration system was investigated experimentally and theoretically, and the theoretical prediction was fairly in good agreement with the experimental data. The influence of pipe diameter, tooth depth, and spiral angle of inter-cooler on the performance of the refrigerant system was analyzed. It was concluded that heat transfer is influenced deeply by the structure parameters of inter-cooler, and the heat transfer capacity increases with tooth depth and spiral angle increasing, and decreases with tooth apex angle increasing.

  8. EFFICIENCY AND LIFETIME OF SOLAR COLLECTORS FOR SOLAR HEATING PLANTS

    DEFF Research Database (Denmark)

    The 12.5 m² flat plate solar collector HT, today marketed by Arcon Solvarme A/S, has been used in solar heating plants in Scandinavia since 1983. The collector is designed to operate in a temperature interval between 40°C and 90°C. The efficiency of the collector has been strongly improved since...... it was introduced on the market. The paper will present the increase of the efficiency of the collector due to technical improvements since 1983. Further, measurements from the spring of 2009 of the efficiency of two HT collectors, which have been in operation in the solar heating plant Ottrupgaard, Skørping......, Denmark since 1994 with a constant high flow rate and in the solar heating plant Marstal, Denmark since 1996 with a variable flow rate, will be presented. The efficiencies will be compared to the efficiencies of the collectors when they were first installed in the solar heating plants. The measurements...

  9. EFFICIENCY AND LIFETIME OF SOLAR COLLECTORS FOR SOLAR HEATING PLANTS

    DEFF Research Database (Denmark)

    Fan, Jianhua; Chen, Ziqian; Furbo, Simon

    2009-01-01

    The 12.5 m² flat plate solar collector HT, today marketed by Arcon Solvarme A/S, has been used in solar heating plants in Scandinavia since 1983. The collector is designed to operate in a temperature interval between 40°C and 90°C. The efficiency of the collector has been strongly improved since...... it was introduced on the market. The paper will present the increase of the efficiency of the collector due to technical improvements since 1983. Further, measurements from the spring of 2009 of the efficiency of two HT collectors, which have been in operation in the solar heating plant Ottrupgaard, Skørping......, Denmark since 1994 with a constant high flow rate and in the solar heating plant Marstal, Denmark since 1996 with a variable flow rate, will be presented. The efficiencies will be compared to the efficiencies of the collectors when they were first installed in the solar heating plants. The measurements...

  10. Parametric simulation and experimental analysis of earth air heat exchanger with solar air heating duct

    Directory of Open Access Journals (Sweden)

    Sanjeev Jakhar

    2016-06-01

    Full Text Available Earth air heat exchanger (EAHE systems are insufficient to meet the thermal comfort requirements in winter conditions. The low heating potential of such systems can be improved by integrating the system with solar air heating duct (SAHD. The aim of this paper is to present a model to estimate the heating potential for EAHE system with and without SAHD. The model is generated using TRNSYS 17 simulation tool and validated against experimental investigation on an experimental set-up in Ajmer, India. The experiment was done during the winter season, where the system was evaluated for different inlet flow velocities, length and depth of buried pipe. From the experimentation, it was observed that the depth of 3.7 m is sufficient for pipe burial and the 34 m length of pipe is sufficient to get optimum EAHE outlet temperature. It is also observed that increase in flow velocity results in drop in EAHE outlet temperature, while room temperature is found to increase for higher velocities (5 m/s. The COP of the system also increased up to 6.304 when assisted with solar air heating duct. The results obtained from the experiment data are in good agreement with simulated results within the variation of up to 7.9%.

  11. Dream aim reached: 1300 operational district heating supply connections

    Energy Technology Data Exchange (ETDEWEB)

    Handl, K H

    1988-11-01

    Only four years after the beginning of operation of the first consumer station at Klingnau on October 19, 1984, the Regional District Heating Supply in the Lower Aare Valley (Refuna) can already show 1295 operational district heating connections. There are almost 300 more than one year ago and about 20% more than originally foreseen during this short construction time. As in recent years, the number of consumers has significantly increased during a 'connection boom' in the first autumn weeks. The total heat supply power amounts to 51500 kilowatts. This is 70% of the power foreseen in the final stage. 3 figs., 1 tab.

  12. Greenhouse gas emissions of Dutch biomass. Quantification of greenhouse gases emission of Dutch biomass for electricity and heat

    International Nuclear Information System (INIS)

    Koop, K.; Yildiz, I.

    2010-09-01

    The greenhouse gas emissions of all available flows of the biomass chain have been established. This report has the following aims: (1) to establish the greenhouse gas emission of Dutch biomass available for generating electricity and heat; (2) to obtain insight in the opportunities and threats for using the potential of the biomass chains that have the highest potential to reduce greenhouse gas emissions. This report can be seen as a supplement to the report 'Availability of Dutch biomass for electricity and heat in 2020' (2009) [nl

  13. The study of the heat-engineering characteristics of a solar heat collector based on aluminum heat pipes

    International Nuclear Information System (INIS)

    Khairnasov, S.M.; Zaripov, V.K.; Passamakin, B.M. et al.

    2013-01-01

    This paper presents the results of studies into the heat-engineering characteristics of a flat heat solar collector based on aluminum heat pipes that is designed to be used in building facades. The principle of work and the structure of the solar collector are considered; the results of its comparison with a traditional flat solar collector are presented. The studies were performed at a heat carrier temperature range of +10 - +30 degree C and at a solar heat flow density of 400 - 1000 W/m 2 . The obtained experimental heat-engineering characteristics of the collector based on heat pipes show that they are at a level of traditional flow solar collectors; for example, its efficiency is 0.65 - 0.73. Meanwhile, the hydraulic resistance of the structure with heat pipes is by a factor of 2 - 2.4 smaller and ensures a high level of scalability, reliability, and maintainability, which is important when using it as an element of facade constructions of solar heat systems. (author)

  14. Energy policy strategies of the Baltic Sea Region for the post-Kyoto period - focusing on electricity and district heating generation

    Energy Technology Data Exchange (ETDEWEB)

    2012-05-15

    This study presents a comprehensive analysis of energy policy strategies for the Baltic Sea Region for the post-Kyoto period. To this aim, the study provides scenarios for the region in order to develop a both secure and climate-compatible energy system for the year 2020 and beyond. The long-term development of the energy systems in the Baltic Sea Region is analysed, i.e. in Denmark, Estonia, Finland, Germany, Latvia, Lithuania, Norway, Poland, Sweden, and the north western part of Russia. The study focuses on the electricity and district heating sectors. The Baltic Sea Region is comprised of countries with very different economies and characteristics. Hydropower is an important source of electricity generation in Norway, Sweden, Finland and Latvia. Biomass resources are significant throughout the region, deriving from both agricultural residues and large forested areas. Wind power already contributes considerably to electricity generation in countries such as Denmark and Germany, and is likely to play a much greater role in the region in the years to come, both onshore and offshore. In the longer term (2030 and beyond), solar power and geothermal energy could also provide notable contributions to the overall energy supply. The study shows that it is technically possible to reduce greenhouse gas emissions in the electricity and district heating sectors of the Baltic Sea Region by close to 100% using mainly renewable energy sources. The results indicate that this is a challenging, but manageable task. The associated costs are moderate and can be further decreased through regional cooperation. Once the various production technologies have the possibility to interact with district heating and flexible electricity consumption, and transmission connections are optimally utilised, it becomes realistic to integrate e.g. large volumes of wind power into the energy system as a whole. Furthermore, the hydro power reservoirs, particularly in Norway, play a key role in

  15. Space heating with ultra-low-temperature district heating - a case study of four single-family houses from the 1980s

    DEFF Research Database (Denmark)

    Østergaard, Dorte Skaarup; Svendsen, Svend

    2017-01-01

    . These benefits can be maximized if district heating temperatures are lowered as much as possible. In this paper we report on a project where 18 Danish single-family houses from the 1980s were supplied by ultra-low temperature district heating with a supply temperature as low as 45 degrees C for the main part...... of the year. The houses were heated by the existing hydraulic radiator systems, while domestic hot water was prepared by use of district heating and electric boosting. This paper evaluated the heating system temperatures that were necessary in order to maintain thermal comfort in four of the houses. First...... the four houses were modelled in the building simulation tool IDA ICE. The simulation models included the actual radiator sizes and the models were used to simulate the expected thermal comfort in the houses and resulting district heating return temperatures. Secondly measurements of the actual district...

  16. Effects of the distribution density of a biomass combined heat and power plant network on heat utilisation efficiency in village-town systems.

    Science.gov (United States)

    Zhang, Yifei; Kang, Jian

    2017-11-01

    The building of biomass combined heat and power (CHP) plants is an effective means of developing biomass energy because they can satisfy demands for winter heating and electricity consumption. The purpose of this study was to analyse the effect of the distribution density of a biomass CHP plant network on heat utilisation efficiency in a village-town system. The distribution density is determined based on the heat transmission threshold, and the heat utilisation efficiency is determined based on the heat demand distribution, heat output efficiency, and heat transmission loss. The objective of this study was to ascertain the optimal value for the heat transmission threshold using a multi-scheme comparison based on an analysis of these factors. To this end, a model of a biomass CHP plant network was built using geographic information system tools to simulate and generate three planning schemes with different heat transmission thresholds (6, 8, and 10 km) according to the heat demand distribution. The heat utilisation efficiencies of these planning schemes were then compared by calculating the gross power, heat output efficiency, and heat transmission loss of the biomass CHP plant for each scenario. This multi-scheme comparison yielded the following results: when the heat transmission threshold was low, the distribution density of the biomass CHP plant network was high and the biomass CHP plants tended to be relatively small. In contrast, when the heat transmission threshold was high, the distribution density of the network was low and the biomass CHP plants tended to be relatively large. When the heat transmission threshold was 8 km, the distribution density of the biomass CHP plant network was optimised for efficient heat utilisation. To promote the development of renewable energy sources, a planning scheme for a biomass CHP plant network that maximises heat utilisation efficiency can be obtained using the optimal heat transmission threshold and the nonlinearity

  17. Prospects for development of heat supply systems in high-rise districts

    Science.gov (United States)

    Zhila, Viktor; Solovyeva, Elena

    2018-03-01

    The article analyzes the main advantages and disadvantages of centralized and decentralized heat supply systems in high-rise districts. The main schemes of centralized heat supply systems are considered. They include centralized heat supply from boiler houses, centralized heat supply from autonomous heat sources, heat supply from roof boiler houses and door-to-door heating supply. For each of these variant, the gas distribution systems are considered and analyzed. These systems vary depending on the heat source location. For each of these systems, technical and economic indicators are taken into account, the analysis of which allows choosing the best option for districts where high-rise buildings predominate.

  18. Electricity eliminates rust from district heat pipes. The new deoxidation method works on radiators

    Energy Technology Data Exchange (ETDEWEB)

    Sonninen, R.; Leisio, C.

    1996-11-01

    Oxygen dissolving in district heating water through district heat pipes and pipe joints made of plastic corrodes many small and medium-size district heating systems, resulting in heat cuts in the buildings connected to these systems. IN some cases, corrosion products have even circulated back to district heating power plants, thus hampering heat generation in the worst of cases. People residing in blocks of flats where some radiator components are made of plastic also face a similar problem, though on a smaller scale. A small and efficient electrochemical deoxidation cell has now been invented to eliminate this nuisance, which occurs particularly in cold winter weather. (orig.)

  19. Dedicated low temperature nuclear district heating plants: Rationale and prospects

    International Nuclear Information System (INIS)

    Goetzmann, C.A.

    1997-01-01

    Space heating accounts for a substantial fraction of the end-energy consumption in a large number of industrialized countries. Accordingly, efforts have been under way since many years to utilize nuclear energy as a source for district heating. The paper describes the key technical and institutional issues affecting the implementation of such technology. It is argued that the basic case for nuclear district heating is sound but that its introduction merits and drawbacks strongly depend on local circumstances. (author). 4 figs, 1 tab

  20. Dedicated low temperature nuclear district heating plants: Rationale and prospects

    Energy Technology Data Exchange (ETDEWEB)

    Goetzmann, C A [Division of Nuclear Power, International Atomic Energy Agency, Vienna (Austria)

    1997-09-01

    Space heating accounts for a substantial fraction of the end-energy consumption in a large number of industrialized countries. Accordingly, efforts have been under way since many years to utilize nuclear energy as a source for district heating. The paper describes the key technical and institutional issues affecting the implementation of such technology. It is argued that the basic case for nuclear district heating is sound but that its introduction merits and drawbacks strongly depend on local circumstances. (author). 4 figs, 1 tab.

  1. Theoretical model and experimental validation of a direct-expansion solar assisted heat pump for domestic hot water applications

    International Nuclear Information System (INIS)

    Moreno-Rodríguez, A.; González-Gil, A.; Izquierdo, M.; Garcia-Hernando, N.

    2012-01-01

    This paper has shown the development of a theoretical model to determine the operating parameters and consumption of a domestic hot water (DHW) installation, which uses a direct-expansion solar assisted heat pump (DXSAHP) with refrigerant R-134a, a compressor with a rated capacity of 1.1 kW and collectors with a total area of 5.6 m 2 . The model results have been compared and validated the experimental results obtained with the equipment installed at the University Carlos III, South of Madrid. The analysis was conducted over the course of a year, and the results have been represented depending on the meteorological and process variables of several representative days. Taking into account the thermal losses of the installation and the dependency on the operating conditions, the acquired experimental coefficient of performance is between 1.7 and 2.9, while the DHW tank temperature over the course of the study is 51 °C. -- Highlights: ► The study aims to present a new theoretical model and an experimental validation. ► The experimental COP vary between 1.7 and 2.9 (max. condensation temperature 57 °C). ► The operating parameters respond to the solar radiation. The COP may increase up to 50%. ► The useful surface area varies between 50% and 85% of the total surface. ► The system stops if conditions exceed the maximum value of the absorbed heat.

  2. Heat savings in buildings in a 100% renewable heat and power system in Denmark with different shares of district heating

    DEFF Research Database (Denmark)

    Zvingilaite, Erika; Balyk, Olexandr

    2014-01-01

    levels of heat savings, which can be implemented by reducing heat transmission losses through building elements and by installing ventilation systems with heat recovery, in different future Danish heat and power system scenarios. Today almost 50% of heat demand in Denmark is covered by district heating......The paper examines implementation of heat saving measures in buildings in 2050, under the assumption that heat and power supply comes solely from renewable resources in Denmark.Balmorel – a linear optimisation model of heat and power sectors in Denmark is used for investigating economically viable....... A further expansion of district heating network in Denmark is assessed and penetration of heat savings is analysed in this context.If all heat saving measures, included in the model, are implemented, heat demand in Danish buildings in 2050 could be reduced by around 40%. Results show that it is cost...

  3. Economic and CO2 mitigation impacts of promoting biomass heating systems: An input-output study for Vorarlberg, Austria

    International Nuclear Information System (INIS)

    Madlener, Reinhard; Koller, Martin

    2007-01-01

    This paper reports on an empirical investigation about the economic and CO 2 mitigation impacts of bioenergy promotion in the Austrian federal province of Vorarlberg. We study domestic value-added, employment, and fiscal effects by means of a static input-output analysis. The bioenergy systems analysed comprise biomass district heating, pellet heating, and automated wood chip heating systems, as well as logwood stoves and boilers, ceramic stoves, and buffer storage systems. The results indicate that gross economic effects are significant, regarding both investment and operation of the systems, and that the negative economic effects caused by the displacement of conventional decentralised heating systems might be in the order of 20-40%. Finally, CO 2 mitigation effects are substantial, contributing already in 2004 around 35% of the 2010 CO 2 mitigation target of the Land Vorarlberg for all renewable energy sources

  4. Renewable energy sources for the world's poor: a review of current international development assistance programs

    Energy Technology Data Exchange (ETDEWEB)

    Ashworth, J. H.

    1979-10-01

    Foreign assistance funding of the creation, testing, and use of renewable energy sources concerning worldwide efforts to provide energy for Third World development is examined. Donor agencies and developing nations give serious attention to technologies that have been considered exotic and marginal: small-scale hydroelectric generation, solar water heating and distillation, biomass conversion to methane gas and alcohol, wind power, photovoltaic-powered small-scale irrigation, and village-level solar-powered absorption refrigeration. An initial effort to assist in the international coordination of donor activity and in the sharing of information generated by foreign-assistance projects that use renewable energy sources is reported. The report mainly provides information about specific development projects. It contains only a few of the projects that have been approved and funded by 1 June 1979. (MCW)

  5. Hybrid-renewable processes for biofuels production: concentrated solar pyrolysis of biomass residues

    Energy Technology Data Exchange (ETDEWEB)

    George, Anthe [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States); Geier, Manfred [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States); Dedrick, Daniel E. [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States)

    2014-10-01

    The viability of thermochemically-derived biofuels can be greatly enhanced by reducing the process parasitic energy loads. Integrating renewable power into biofuels production is one method by which these efficiency drains can be eliminated. There are a variety of such potentially viable "hybrid-renewable" approaches; one is to integrate concentrated solar power (CSP) to power biomass-to-liquid fuels (BTL) processes. Barriers to CSP integration into BTL processes are predominantly the lack of fundamental kinetic and mass transport data to enable appropriate systems analysis and reactor design. A novel design for the reactor has been created that can allow biomass particles to be suspended in a flow gas, and be irradiated with a simulated solar flux. Pyrolysis conditions were investigated and a comparison between solar and non-solar biomass pyrolysis was conducted in terms of product distributions and pyrolysis oil quality. A novel method was developed to analyse pyrolysis products, and investigate their stability.

  6. Solar heat-pipe wick modeling

    Energy Technology Data Exchange (ETDEWEB)

    Andraka, C.E.

    1999-07-01

    Stirling-cycle engines have been identified as a promising technology for the conversion of concentrated solar energy into usable electrical power. In previous experimental work, the author has demonstrated that a heat pipe receiver can significantly improve system performance over a directly-illuminated heater head. The design and operating conditions of a heat pipe receiver differ significantly from typical laboratory heat pipes. New wick structures have been developed to exploit the characteristics of the solar generation system. Typically, these wick structures allow vapor generation within the wick. Conventional heat pipe models do not handle this enhancement, yet it can more than double the performance of the wick. In this study, the author developed a steady-state model of a boiling-enhanced wick for a solar heat pipe receiver. The model is used for design-point calculations and is written in FORTRAN90. Some limited comparisons have been made with actual test data.

  7. MINERGIE modules: heat pump - heat pump/solar - wood - wood/solar; Minergie-Module Waermepumpe - Waermepumpe/Solar - Holz - Holz/Solar

    Energy Technology Data Exchange (ETDEWEB)

    Gallati, J. [Seecon GmbH, Lucerne (Switzerland); Portmann, M. [Buero Markus Portmann, Kriens (Switzerland); Zurfluh, B. [Zurfluh Lottenbach, Lucerne (Switzerland)

    2005-07-01

    This research report for the Swiss Federal Office of Energy (SFOE) presents the results of a project that examined the feasibility of setting up 'MINERGIE' low-energy-consumption module standards for the production of heat in small residential buildings. The aims of the standards and the basic idea behind the MINERGIE-modules are discussed. The concepts of the modules for heat pumps and wood-fired heating systems and their combination with solar installations are examined, as are their areas of application. The requirements placed on the modules are listed. System concepts, including simple schematics for typical installations, are presented for wood-log, wood-chippings and pellets-fired systems as well as for ground-loop and air-water heat pump systems as well as their solar-aided counterparts. The results of cost-benefit analyses are presented and questions regarding system guarantee and liability are examined.

  8. Analysis of energy development sustainability: The example of the lithuanian district heating sector

    International Nuclear Information System (INIS)

    Kveselis, Vaclovas; Dzenajavičienė, Eugenija Farida; Masaitis, Sigitas

    2017-01-01

    Today, sustainable energy development is one of key issues on European development agenda. The article describes one of sustainable energy development promoting tool - the eco-labelling scheme for district heating and cooling systems elaborated within the framework of Intelligent Energy for Europe program project “Ecoheat4cities” and partially funded by European Agency for Competitiveness and Innovation. The scheme is based on measured energy and environmental performance data of the district heating and cooling system and considers primary non-renewable energy usage together with the share of renewable energy and carbon dioxide emissions calculated using life-cycle analysis methodology. The “power bonus” approach is used for performance indicators of the heat generated in cogeneration installations. An analysis of a number of Lithuanian district heating companies using elaborated labelling criteria shows positive trends towards fulfilling Lithuania's energy policy goals. The labelling scheme gives opportunity for policy makers and urban planners to compare different heat supply options and decide upon exploiting district heating advantages and benefits for reaching EU energy and environment policy goals. - Highlights: • Overview of Lithuania's district heating sector was performed via main sustainability criteria. • Developing to greener and more efficient state was disclosed via analysis of three years activity results. • Green labelling may help district heating companies to maintain existing and attract new potential consumers.

  9. Biomass equipments. The wood-fueled heating plants; Materiels pour la biomasse. Les chaudieres bois

    Energy Technology Data Exchange (ETDEWEB)

    Chieze, B. [SA Compte R, 63 - Arlanc (France)

    1997-12-31

    This paper analyzes the consequences of the classification of biomass fuels in the French 2910 by-law on the classification of biomass-fueled combustion installations. Biomass fuels used in such installations must be only wood wastes without any treatment or coating. The design of biomass combustion systems must follow several specifications relative to the fueling system, the combustion chamber, the heat exchanger and the treatment of exhaust gases. Other technical solutions must be studied for other type of wood wastes in order to respect the environmental pollution laws. (J.S.)

  10. Techno-economic evaluation of a solar assisted combined heat pump – Organic Rankine Cycle system

    International Nuclear Information System (INIS)

    Schimpf, Stefan; Span, Roland

    2015-01-01

    Highlights: • Addition of an ORC to a solar thermal and ground source heat pump system. • Additional investments comprise only 400 € for a single-family house unit. • Recharging the ground during ORC has negligible impact on the COP of the HP. • Economics studied for application in Bochum, Denver and Ankara; only small benefits. • Use of isobutane instead of R134a would increase the profit of the ORC system. - Abstract: The economic feasibility of the addition of an ORC to a combined solar system coupled to a ground-source heat pump is discussed. The ORC prevents the stagnation of the solar loop and reverses the heat pump cycle. The working fluid is evaporated in the condenser of the heat pump, expanded in the scroll compressor, which becomes a scroll expander, and condensed in the brine heat exchanger. The only additional investments for the ORC system comprise a pump, valves and upgraded controls and are estimated to be 400 € for a single-family-house unit. Flat-plate collectors are the preferred collector type as the higher collector efficiency of evacuated tube collectors does not outweigh the higher costs. The thermal recharging of the ground during ORC has a negligible impact on the COP of the heat pump. However, the recharging leads to less deep boreholes compared to a conventional system. Because of the low investments for the ORC, even small reductions in borehole depth make a significant contribution to the economic feasibility of the system. The addition of the ORC overall generates a small profit of 155 € at Ankara and 74 € at Denver for a rocky soil and a thermally enhanced grout. On the contrary, the conventional solar combisystem coupled to a ground source heat pump was found to be economically unreasonable at all locations. The working fluid isobutane is interesting for future applications because of the lower global warming potential and the smaller saturation pressures compared to R134a. The latter allow for the installation of a

  11. A study of a small nuclear power plant system for district heating

    International Nuclear Information System (INIS)

    Imamura, Mitsuru; Sato, Kotaro; Narabayashi, Tadashi; Shimazu, Yoichiro; Tsuji, Masashi

    2008-01-01

    We have studied nuclear power plant for district heating. Already some towns and villages in Hokkaido have requested small reactor for district heating. Using existing technology allows us to shorten development period and to keep a lid on development cost. We decided to develop new reactor based on 'MUTSU' reactor technology. 'MUTSU' had already proved its safety. And 'MUTSU' reactor was boron free reactor. It allows plant system to become more compact and simple. And load following capability by core reactivity become bigger. It means to reduce control rod movement. It leads to dependability enhancement. We calculated burn-up calculation of erbium addition fuel. In the result the core life became about 10 years. In the district heating system, there are not only district heating but also snow melting with warm water. It uses steam condenser's heat, which are only discharged now. This small plant has passive safety system. It is natural cooling of containment vessel. In case of loss of coolant accident, decay heat can remove by natural convection air cooling after 6 hours. Decay heat within 6 hours can remove by evaporative heat transfer of pool on containment vessel. (author)

  12. Closed loop solar chemical heat pipe

    International Nuclear Information System (INIS)

    Levy, M.; Levitan, R.; Rosin, H.; Rubin, R.

    1991-01-01

    The system used for the closed loop operation of the solar chemical heat pipe comprises a reformer, heated by the solar furnace, a methanator and a storage assembly containing a compressor and storage cylinders. (authors). 7 figs

  13. Exploiting the Medium Term Biomass Energy Potentials in Austria. A Comparison of Costs and Macroeconomic Impact

    International Nuclear Information System (INIS)

    Steininger, K.W.; Voraberger, H.

    2003-01-01

    The transition to an implicitly solar-based energy system can make use of various specific biomass energy systems. This paper provides economic and environmental indicators for evaluating alternative options. The paper proceeds in three empirical steps. First, an expert survey supplies the primary biomass potentials available for non-food use in Austria and their respective costs. Second, an inquiry into investment, operating and financing costs of 30 different biomass energy use systems allows a standardized comparison among them and their relationship to fossil reference technologies. Third, a computable general equilibrium model of the Austrian economy is employed to quantify the impacts of fostering the use of distinct biomass energy technologies. The results allow us to distinguish between those technologies that tend to lead to an increase in both GDP and employment (e.g., combined heat and power production from sewage sludge biogas), to an increase only in employment, while GDP tends to diminish (e.g., district heating based on agricultural pellets) or to a decline in both (e.g., co-firing based on wood-chips, bark or industrial pellets). Individual technologies could account for up to one third of Austria's Kyoto obligation, while combinations of technologies, triggered by a combined CO2 tax and biomass energy subsidy for example, could almost fully lead to Austrian Kyoto-compliance

  14. Fault diagnosis methods for district heating substations

    Energy Technology Data Exchange (ETDEWEB)

    Pakanen, J.; Hyvaerinen, J.; Kuismin, J.; Ahonen, M. [VTT Building Technology, Espoo (Finland). Building Physics, Building Services and Fire Technology

    1996-12-31

    A district heating substation is a demanding process for fault diagnosis. The process is nonlinear, load conditions of the district heating network change unpredictably and standard instrumentation is designed only for control and local monitoring purposes, not for automated diagnosis. Extra instrumentation means additional cost, which is usually not acceptable to consumers. That is why all conventional methods are not applicable in this environment. The paper presents five different approaches to fault diagnosis. While developing the methods, various kinds of pragmatic aspects and robustness had to be considered in order to achieve practical solutions. The presented methods are: classification of faults using performance indexing, static and physical modelling of process equipment, energy balance of the process, interactive fault tree reasoning and statistical tests. The methods are applied to a control valve, a heat excharger, a mud separating device and the whole process. The developed methods are verified in practice using simulation, simulation or field tests. (orig.) (25 refs.)

  15. New CO{sub 2} neutral city area with integrated district heating system of the future in Hoeje Taastrup - Phase 1: Preparation of demonstration. Final report; Denmark; Ny CO{sub 2}-neutral bydel med fremtidens integrerede fjernvarmesystem i Hoeje Taastrup - Fase 1: Forberedelse af demonstration. Slutrapport

    Energy Technology Data Exchange (ETDEWEB)

    Kaarup Olsen, P.; Hummelshoej, R.M. (Cowi A/S (Denmark))

    2011-02-15

    The project has contributed considerably to developing and maturing many climate initiatives in Hoeje Taastrup municipality - including particularly having made an effort to develop and develop the plans for a CO{sub 2}-neutral quarter called 'Vision Gammelsa'. In this context, the project has involved relevant actors in the development of an energy concept for the quarter. The concept was later used as basis for an EU application to the CONCERTO programme, for which Hoeje Taastrup achieved final grant agreement in December 2009. In this way, the municipality obtained funding for a 6-year project 'ECO-Life' which will focus on energy measures in Hedehusene, Floeng and the Gammelsoe region. The project will be carried out in cooperation with a municipality in Lithuania (Birstonas) and Belgium (Kortrijk). In addition, the project supported the development of a climate plan and policy in the municipality. During the life of the project, the council has carried out a wide range of ambitious initiatives which to a great extent stems from the project and in particularly the cooperation that the project has brought along. Based on a preliminary draft proposal for the district, a number of energy concepts have been assessed that can make the district CO{sub 2}-neutral. Primary focus has been on the heat supply. It is recommended to establish a low-temperature heating network, since such a solution provides the best possibility of using surplus heat and renewable energy sources, and in the future, perhaps already in 15 years, district heating from VEKS will be CO{sub 2}-neutral. Three energy efficient and CO{sub 2} efficient district heating solutions have been investigated in more detail: 1) Local low-temperature district heating network with ground heat and solar heat. 2) Low-temperature district heating network based on return heat from the HTF/VEKS system. 3) Low-temperature district heating network with heat driven heat pumps and solar heat. All

  16. THERMOS, district central heating nuclear reactors

    International Nuclear Information System (INIS)

    Patarin, L.

    1981-02-01

    In order to expand the penetration of uranium in the national energy balance sheet, the C.E.A. has been studying nuclear reactors for several years now, that are capable of providing heat at favourable economic conditions. In this paper the THERMOS model is introduced. After showing the attraction of direct town heating by nuclear energy, the author describes the THERMOS project, defines the potential market, notably in France, and applies the lay-out study to the Grenoble Nuclear Study Centre site with district communal heating in mind. The economic aspects of the scheme are briefly mentioned [fr

  17. Small-scale automated biomass energy heating systems: a viable option for remote Canadian communities?

    Energy Technology Data Exchange (ETDEWEB)

    McCallum, B. [Canadian Forest Service, Ottawa, ON (Canada). Industry, Economics and Programs Branch

    1997-12-31

    The potential benefits of wood energy (forest biomass) for space heating in Canada`s remote communities was discussed. Diesel fuel and heating oil must be transported into these communities to produce electricity and to heat large public buildings. Below the treeline, roundwood is often used to heat private homes. The move toward environmentally sustainable development has focussed much attention on renewable energy technologies such as biomass energy, (i.e. any form of energy derived from plant or animal materials). Wood is the most readily available biomass fuel in remote communities. Woodchips and sawmill waste can be burned in automated biomass heating systems which provide a convenient way to use low-grade wood to heat large buildings or groups of buildings which would not be feasible to heat with roundwood. It was shown that one cord of spruce can produce 1.5 tonnes of woodchips to ultimately displace 300 litres of heating oil. A description of a small-commercial and small-industrial biomass system was presented. The benefits of biomass were described as: (1) direct savings compared to high-cost oil heat, (2) increased circulation of energy dollars inside the community, and (3) employment opportunities in harvesting, processing and operating biomass systems. A steady supply of good quality woodchips to the heating plant must be ensured. 1 ref., 3 figs.

  18. The future of the low temperature district heating reactor

    International Nuclear Information System (INIS)

    Lu Yingzhong; Wang Dazhong; Ma Changwen; Dong Duo; Tian Jiafu.

    1984-01-01

    In this paper, the role, development and situation of the low temperature district heating reactor (LTDHR) are briefly summarized. There are four types of LTDHR. They are PWR, reactor with boiling in the chimney, organic reactor and swimming pool reactor. The features of these reactors are introduced. The situation and role of the LTDHR in the future of the energy system are also discussed. The experiment on nuclear district heating with the swimming pool reactor in Qinghua Univ. is described briefly. (Author)

  19. District Heating at Power Failures - Final Report; Fjaerrvaerme vid Elavbrott - Slutrapport

    Energy Technology Data Exchange (ETDEWEB)

    Lauenburg, Patrick; Johansson, Per-Olof

    2008-11-15

    Our society is vulnerable to prolonged power cuts. In cold weather interrupted heating is one of the most serious threats. District heating is available at most locations in Sweden and if heat can be transferred to the connected buildings at a power failure, it is of great importance for securing energy supply. In this work it was found that there are good opportunities for upholding heat supply at a power failure through self-circulation in connected radiator system, which has previously been overlooked. Self Circulation occurs when there is a sufficiently large temperature difference between forward and return line in the radiator system. The control and circulation in radiator systems will fail, but if the district heating water can continue to pass through the heat exchangers of the radiator systems self-circulation can occur. A prerequisite for self-circulation in the individual buildings to work is therefore to district heating network can operate at a power failure. District heating supply must have back to maintain the production and distribution of district heating, which is not always the case. Our studies show that there is every reason to this. Moreover there are customers that have their own reserve aggregates, such as hospitals, which are dependent on the district heating network function. In an extensive power failure, it may be desirable to establish a smaller grid, separate from backbone, using local electricity generation. The establishment of such a network requires there is local production which can start to loose voltage networks and has necessary control equipment for the frequency approach. In Malmoe, it is now possible to establish a such a network with the help of local production units. A prerequisite is that there are consumption of heating. It is not unusual for power plants (which produce both electricity and heat) is dependent on the pipe system for cooling the production of electricity. One can from the results also argue that every

  20. Solar heating and employment in Canada

    Energy Technology Data Exchange (ETDEWEB)

    Victor, P A

    1978-01-01

    If solar heating technology is to be introduced into sections of Canada as a way to alleviate unemployment problems and stimulate the manufacturing sector, realistic expectations must be grounded in better estimates of solar energy's potential than were made by early nuclear power enthusiasts. A study by Middleton Associates identified a number of factors affecting employment. These include implementation rates, choice of technologies, industry size, government involvement, location, and the share of solar heating relative to other heating sources. An employment simulation model using available technologies as inputs suggests that solar heating is feasible on the basis of both energy source and employment strategy. Model results are favorable for direct and indirect employment, while displacement effects on employment in conventional fuel industries are minor. Direct employment is affected more by implementation rates than by variations in the amount of imported equipment.

  1. Performance of ultra low temperature district heating systems with utility plant and booster heat pumps

    DEFF Research Database (Denmark)

    Ommen, Torben Schmidt; Thorsen, Jan Eric; Markussen, Wiebke Brix

    2017-01-01

    The optimal integration of booster heat pumps in ultra low temperature district heating (ULTDH) was investigated and compared to the performance of low temperature district heating. Two possible heat production technologies for the DH networks were analysed, namely extraction combined heat...... temperature and the heat consumption profile. For reference conditions, the optimal return of ULTDH varies between 21 °C and 27 °C. When using a central HP to supply the DH system, the resulting coefficient of system performance (COSP) was in the range of 3.9 (-) to 4.7 (-) for equipment with realistic...... component efficiencies and effectiveness, when including the relevant parameters such as DH system pressure and heat losses. By using ULTDH with booster HPs, performance improvements of 12% for the reference calculations case were found, if the system was supplied by central HPs. Opposite results were found...

  2. Geothermal direct-heat utilization assistance. Quarterly project progress report, April--June 1993

    Energy Technology Data Exchange (ETDEWEB)

    Lienau, P.

    1993-06-01

    Technical assistance was provided to 60 requests from 19 states. R&D progress is reported on: evaluation of lineshaft turbine pump problems, geothermal district heating marketing strategy, and greenhouse peaking analysis. Two presentations and one tour were conducted, and three technical papers were prepared. The Geothermal Progress Monitor reported: USGS Forum on Mineral Resources, Renewable Energy Tax Credits Not Working as Congress Intended, Geothermal Industry Tells House Panel, Newberry Pilot Project, and Low-Temperature Geothermal Resources in Nevada.

  3. Energy recovery from waste incineration: Assessing the importance of district heating networks

    International Nuclear Information System (INIS)

    Fruergaard, T.; Christensen, T.H.; Astrup, T.

    2010-01-01

    Municipal solid waste incineration contributes with 20% of the heat supplied to the more than 400 district heating networks in Denmark. In evaluation of the environmental consequences of this heat production, the typical approach has been to assume that other (fossil) fuels could be saved on a 1:1 basis (e.g. 1 GJ of waste heat delivered substitutes for 1 GJ of coal-based heat). This paper investigates consequences of waste-based heat substitution in two specific Danish district heating networks and the energy-associated interactions between the plants connected to these networks. Despite almost equal electricity and heat efficiencies at the waste incinerators connected to the two district heating networks, the energy and CO 2 accounts showed significantly different results: waste incineration in one network caused a CO 2 saving of 48 kg CO 2 /GJ energy input while in the other network a load of 43 kg CO 2 /GJ. This was caused mainly by differences in operation mode and fuel types of the other heat producing plants attached to the networks. The paper clearly indicates that simple evaluations of waste-to-energy efficiencies at the incinerator are insufficient for assessing the consequences of heat substitution in district heating network systems. The paper also shows that using national averages for heat substitution will not provide a correct answer: local conditions need to be addressed thoroughly otherwise we may fail to assess correctly the heat recovery from waste incineration.

  4. Financial cost-benefit analysis of investment possibilities in district heating system on wood residues

    Directory of Open Access Journals (Sweden)

    Stošić Ivan

    2017-01-01

    Full Text Available The purpose of this research is to provide feasibility analysis of a long-term sustainable development concept for district heating based on wood residues. In this paper, the experimental study has been conducted starting from the data collected by field researches in municipality of Trstenik (town in Serbia with district heating system currently based on heavy fuel oil and lignite. Using the method of Financial Cost-Benefit Analysis, this study evaluates financial efficiency of investment in district heating plant based on wood residues and energy savings in district heating system. Findings show that such investment could be profitable from the financial point of view: Net Present Value of investment is positive, Financial Rate of Return is high (30.69%, and the pay-back period is relatively favourable (7 years. Moreover, the presented SWOT indicates that there are realistic prospects of implementation of district heating based on wood residues. However, this does not mean everything will go smoothly and easily, keeping in mind a number of challenges that each new concept of district heating contains immanently. Nevertheless, the results of this research could provide useful inputs for the decision makers when selecting appropriate models for improving performance of municipal district heating systems.

  5. Low Temperature District Heating Consumer Unit with Micro Heat Pump for Domestic Hot Water Preparation

    DEFF Research Database (Denmark)

    Zvingilaite, Erika; Ommen, Torben Schmidt; Elmegaard, Brian

    2012-01-01

    In this paper we present and analyse the feasibility of a district heating (DH) consumer unit with micro heat pump for domestic hot water (DHW) preparation in a low temperature (40 °C) DH network. We propose a micro booster heat pump of high efficiency (COP equal to 5,3) in a consumer DH unit...... in order to boost the temperature of the district heating water for heating the DHW. The paper presents the main designs of the suggested system and different alternative micro booster heat pump concepts. Energy efficiency and thermodynamic performance of these concepts are calculated and compared....... The results show that the proposed system has the highest efficiency. Furthermore, we compare thermodynamic and economic performance of the suggested heat pump-based concept with different solutions, using electric water heater. The micro booster heat pump system has the highest annualised investment (390 EUR...

  6. Solar energy

    Science.gov (United States)

    Rapp, D.

    1981-01-01

    The book opens with a review of the patterns of energy use and resources in the United States, and an exploration of the potential of solar energy to supply some of this energy in the future. This is followed by background material on solar geometry, solar intensities, flat plate collectors, and economics. Detailed attention is then given to a variety of solar units and systems, including domestic hot water systems, space heating systems, solar-assisted heat pumps, intermediate temperature collectors, space heating/cooling systems, concentrating collectors for high temperatures, storage systems, and solar total energy systems. Finally, rights to solar access are discussed.

  7. Residential solar-heating system

    Science.gov (United States)

    1978-01-01

    Complete residential solar-heating and hot-water system, when installed in highly-insulated energy-saver home, can supply large percentage of total energy demand for space heating and domestic hot water. System which uses water-heating energy storage can be scaled to meet requirements of building in which it is installed.

  8. Potential of HVAC and solar technologies for hospital retrofit to reduce heating energy consumption

    Science.gov (United States)

    Pop, Octavian G.; Abrudan, Ancuta C.; Adace, Dan S.; Pocola, Adrian G.; Balan, Mugur C.

    2018-02-01

    The study presents a combination of several energy efficient technologies together with their potential to reduce the energy consumption and to increase the comfort through the retrofit of a hospital building. The existing situation is characterized by an old and inefficient heating system, by the complete missing of any ventilation and by no cooling. The retrofit proposal includes thermal insulation and a distributed HVAC system consisting of several units that includes air to air heat exchangers and air to air heat pumps. A condensing boiler was also considered for heating. A solar thermal system for preparing domestic hot water and a solar photovoltaic system to assist the HVAC units are also proposed. Heat transfer principles are used for modelling the thermal response of the building to the environmental parameters and thermodynamic principles are used for modelling the behaviour of HVAC, solar thermal system and photovoltaic system. All the components of the heating loads were determined for one year period. The study reveals the capacity of the proposed systems to provide ventilation and thermal comfort with a global reduction of energy consumption of 71.6 %.

  9. Twin cities institutional issues study cogenerated hot water district heating

    Energy Technology Data Exchange (ETDEWEB)

    Sundberg, R. E.; Leas, R.; Kolb, J. O.

    1979-01-01

    Community district heating, utilizing hot water produced through electrical/thermal cogeneration, is seen as an integral part of Minnesota's Energy Policy and Conservation Plan. Several studies have been conducted which consider the technical and institutional issues affecting implementation of cogenerated district heating in the Minneapolis and St. Paul Metropolitan Area. The state of the technical art of cogenerated hot water district heating is assumed to be transferable from European experience. Institutional questions relating to such factors as the form of ownership, financing, operation, regulation, and product marketability cannot be transferred from the European experience, and have been the subject of an extensive investigation. The form and function of the Institutional Issues Study, and some of the preliminary conclusions and recommendations resulting from the study are discussed.

  10. A new district heating system in the city of Bolanzo

    DEFF Research Database (Denmark)

    Mazzocato, Alessandro; Li, Hongwei; Marchiori, S.

    2014-01-01

    In the context of the EU project “Sinfonia”, that aims to reduce Bolzano’s primary energy consumption up to 40%, SEL AG, an Italian energy company is planning to extend the existing district heating and cooling (DHC) network and explore strategies to improve efficiency, environmental, and economic...... performance. This research aims to assess the potential energy saving of temperature and peak heating load reduction in the Bolzano’s DHC network. Historical performance data from district heating (DH) users were collected and residential building were classified based on construction year and energy...

  11. Uncertainties in the daily operation of a district heating plant

    DEFF Research Database (Denmark)

    Sorknæs, Peter

    Studies have found that district heating (DH) systems should play an important role in future sustainable energy systems, but that DH has to adapt to lower heat demands. This means adapting to reduced operation hours for units essential for DHs integration in other parts of the energy system......, such as CHP. It will therefore likely be increasingly important to increase the value per operation hour. The value can be increased by offering balancing for the electricity system. This in turn increases the uncertainties in the daily operation planning of the DH system. In this paper the Danish DH plant...... Ringkøbing District Heating is used as a case to investigate what costs market uncertainties can incur on a DH plant. It is found that the market uncertainties in a 4 months simulated period increased Ringkøbing District Heatings costs by less than 1%. Several factors are however not included in this paper....

  12. Fiscal 1999 basic research on promotion of joint implementation. Comprehensive feasibility study on efficiency improvement project for heat generation facilities and heat supply networks for district heating at districts in Moscow region, the Russian Federation (2 model districts within the region)

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2000-03-01

    For the purpose of conserving energy and reducing greenhouse gas, a survey is conducted for district heating facilities of the Khimki district and Voskresensk district in Moscow and for their heat supply networks. Four boilers existing at the Khimki district are all to be replaced by natural gas turbine centralized cogeneration plants, and four boilers existing at the Voskresensk district are all to be replaced by natural gas turbine cogeneration facilities. These projects are designated as Case 1 and Case 2, different from each other in terms of power generation capability and heat supply scale. As for investment, a total of 267-million dollars will be necessary for Case 1, and 208-million dollars for Case 2. As for energy conservation, energy will be saved by approximately 2.8-million tons in total in terms of oil in Case 1, and approximately 2-million tons in terms of oil in Case 2. As for greenhouse gas reduction, there will be a reduction of approximately 6.8-million tons in terms of CO2 in Case 1, and a reduction of approximately 4.9-million tons in terms of CO2 in Case 2. (NEDO)

  13. Building an eco-effective district heating management system in a city

    Directory of Open Access Journals (Sweden)

    Gitelman Leonid

    2016-01-01

    Full Text Available The goal of making the urban environment safer amid increasing human impact adds to the importance of district heating management. The article outlines the results of a study into the problem of improving the urban environment by implementing two innovative solutions. Technological innovations imply the introduction of modern sustainable tools of reducing emissions in district heating networks, one of them being the combination of district heating and combined heat and power plants (a case study of Turin. Organizational innovations are built upon the management of demand for thermal energy that makes it possible to reduce investment in new construction and to optimize the architecture of heat load schedules for the purpose of alleviating energy and environmental pressure on the city. The authors propose formats and areas of demand side management for thermal energy and methods of offering economic incentives to program participants.

  14. Solar-Enhanced Air-Cooled Heat Exchangers for Geothermal Power Plants

    Directory of Open Access Journals (Sweden)

    Kamel Hooman

    2017-10-01

    Full Text Available This paper focuses on the optimization of a Solar-Enhanced Natural-Draft Dry-Cooling Tower (SENDDCT, originally designed by the Queensland Geothermal Energy Centre of Excellence (QGECE, as the air-cooled condenser of a geothermal power plant. The conventional method of heat transfer augmentation through fin-assisted area extension is compared with a metal foam-wrapped tube bundle. Both lead to heat-transfer enhancement, albeit at the expense of a higher pressure drop when compared to the bare tube bundle as our reference case. An optimal design is obtained through the use of a simplified analytical model and existing correlations by maximizing the heat transfer rate with a minimum pressure drop goal as the constraint. Sensitivity analysis was conducted to investigate the effect of sunroof diameter, as well as tube bundle layouts and tube spacing, on the overall performance of the system. Aiming to minimize the flow and thermal resistances for a SENDDCT, an optimum design is presented for an existing tower to be equipped with solar panels to afterheat the air leaving the heat exchanger bundles, which are arranged vertically around the tower skirt. Finally, correlations are proposed to predict the total pressure drop and heat transfer of the extended surfaces considered here.

  15. Study of an active wall solar heating system

    International Nuclear Information System (INIS)

    Kassem, Talal

    2006-01-01

    An active wall solar heating system was built and tested. In the same time a compatible computer program has been according to set the recommended dimensions for the solar collectors where (F-Chart) method used to set the ratio of monthly solar sharing average for the examined heating system. Some parameters, such as collectors' areas, its tilt angle and near earth reflecting were experimentally investigated, affecting the executed active solar heating system performance. The study explain the ability of using this system which is simple, Low coast and high performance in heating residential and public buildings and heating water with ratio of yearly solar sharing achieves the needed saving of using this system.(Author)

  16. Optimal Control of Solar Heating System

    KAUST Repository

    Huang, Bin-Juine

    2017-02-21

    Forced-circulation solar heating system has been widely used in process and domestic heating applications. Additional pumping power is required to circulate the water through the collectors to absorb the solar energy. The present study intends to develop a maximum-power point tracking control (MPPT) to obtain the minimum pumping power consumption at an optimal heat collection. The net heat energy gain Qnet (= Qs − Wp/ηe) was found to be the cost function for MPPT. The step-up-step-down controller was used in the feedback design of MPPT. The field test results show that the pumping power is 89 W at Qs = 13.7 kW and IT = 892 W/m2. A very high electrical COP of the solar heating system (Qs/Wp = 153.8) is obtained.

  17. Geothermal district heating system feasibility analysis, Thermopolis, Wyoming

    Energy Technology Data Exchange (ETDEWEB)

    Goering, S.W.; Garing, K.L.; Coury, G.; Mickley, M.C.

    1982-04-26

    The purpose of this study is to determine the technical and economic feasibility of constructing and operating a district heating system to serve the residential, commercial, and public sectors in Thermopolis. The project geothermal resource assessment, based on reviews of existing information and data, indicated that substantial hot water resources likely exist in the Rose Dome region 10 miles northeast of Thermopolis, and with quantities capable of supporting the proposed geothermal uses. Preliminary engineering designs were developed to serve the space heating and hot water heating demands for buildings in the Thermopolis-East Thermopolis town service area. The heating district design is based on indirect geothermal heat supply and includes production wells, transmission lines, heat exchanger units, and the closed loop distribution and collection system necessary to serve the individual customers. Three options are presented for disposal of the cooled waters-reinjection, river disposal, and agricultural reuse. The preliminary engineering effort indicates the proposed system is technically feasible. The design is sized to serve 1545 residences, 190 businesses, and 24 public buildings. The peak design meets a demand of 128.2 million Btu at production rates of 6400 gpm.

  18. District Heating Network Design and Configuration Optimization with Genetic Algorithm

    DEFF Research Database (Denmark)

    Li, Hongwei; Svendsen, Svend

    2013-01-01

    In this paper, the configuration of a district heating network which connects from the heating plant to the end users is optimized. Each end user in the network represents a building block. The connections between the heat generation plant and the end users are represented with mixed integer...... and the pipe friction and heat loss formulations are non-linear. In order to find the optimal district heating network configuration, genetic algorithm which handles the mixed integer nonlinear programming problem is chosen. The network configuration is represented with binary and integer encoding...... and it is optimized in terms of the net present cost. The optimization results indicates that the optimal DH network configuration is determined by multiple factors such as the consumer heating load, the distance between the heating plant to the consumer, the design criteria regarding the pressure and temperature...

  19. A transition perspective on alternatives to coal in Chinese district heating

    Directory of Open Access Journals (Sweden)

    Jingjing Zhang

    2015-06-01

    Full Text Available China accounts for half of the world’s annual coal consumption. Coal is the primary energy source for heating in urban areas, particularly in northern China. This causes significant challenges for urban air quality problems in China and greenhouse gases emissions. Urban district heating (DH systems penetration is very high in northern China. It supplies space heating to more than 80% of urban buildings in the area. Unlike the electricity and transportation sectors, the heating sector has received little attention from policy makers and researchers in China, DH systems are an enabling infrastructure which facilitates energy efficiency improvements and the use of renewable energy sources. This study explores the dynamics and possibility to expand alternative energy sources (natural gas, biomass, direct geothermal heat, ground-source heat pump, municipal waste heat, industrial waste heat for DH in China. We apply an analytical framework largely based on the multi-level perspective in socio-technical transitions theory, in which transitions are interpreted as the result of the functioning of niche, regime and landscape elements, and interactions between them. The study provides an integrated picture of the socio-technical structure and functioning of DH in China. The results show that an energy transition in Chinese DH systems has barely started. The system is characterised by stability of the coal-based DH regime, while a number of alternative niches are struggling to emerge. Among these, natural gas is the most successful example. However, at local level different niches present opportunities in terms of physical availability, economic viability and technical capacity to address changes in landscape pressures. A sustainable heat roadmap based on integrated energy planning and policy attention at the national level could be developed as one mechanism for instigating a much needed energy transition in DH in China.

  20. Corrosion Rate Monitoring in District Heating Systems

    DEFF Research Database (Denmark)

    Hilbert, Lisbeth Rischel; Nielsen, Lars Vendelbo; Andersen, A.

    2005-01-01

    be applicable, and if on-line monitoring could improve the quality control. Water quality monitoring was applied as well as corrosion rate monitoring with linear polarization resistance (LPR), electrochemical impedance spectroscopy (EIS), electrical resistance (ER) technique, mass loss and a crevice corrosion......Quality control in district heating systems to keep uniform corrosion rates low and localized corrosion minimal is based on water quality control. Side-stream units equipped with carbon steel probes for online monitoring were mounted in district heating plants to investigate which techniques would...... cell for localized corrosion risk estimation. Important variations in corrosion rate due to changes in make-up water quality were detected with the continuous monitoring provided by ER and crevice cell, while LPR gave unreliable corrosion rates. The acquisition time of two-three days for EIS...

  1. Performance test of solar-assisted ejector cooling system

    KAUST Repository

    Huang, Bin-Juine

    2014-03-01

    A solar-assisted ejector cooling/heating system (SACH-2k) is built and test result is reported. The solar-driven ejector cooling system (ECS) is connected in series with an inverter-type air conditioner (IAC). Several advanced technologies are developed in SACH-k2, including generator liquid level control in ECS, the ECS evaporator temperature control, and optimal control of fan power in cooling tower of ECS. From the field test results, the generator liquid level control performs quite well and keeps stable performance of ejector. The ECS evaporator temperature control also performs satisfactorily to keep ejector performance normally under low or fluctuating solar radiation. The fan power control system cooling tower performs stably and reduces the power consumption dramatically without affecting the ECS performance. The test results show that the overall system COPo including power consumptions of peripheral increases from 2.94-3.3 (IAC alone) to 4.06-4.5 (SACH-k2), about 33-43%. The highest COPo is 4.5. © 2013 Elsevier Ltd and IIR. All rights reserved.

  2. Modelling of heat transfer during torrefaction of large lignocellulosic biomass

    Science.gov (United States)

    Regmi, Bharat; Arku, Precious; Tasnim, Syeda Humaira; Mahmud, Shohel; Dutta, Animesh

    2018-07-01

    Preparation of feedstock is a major energy intensive process for the thermochemical conversion of biomass into fuel. By eliminating the need to grind biomass prior to the torrefaction process, there would be a potential gain in the energy requirements as the entire step would be eliminated. In regards to a commercialization of torrefaction technology, this study has examined heat transfer inside large cylindrical biomass both numerically and experimentally during torrefaction. A numerical axis-symmetrical 2-D model for heat transfer during torrefaction at 270°C for 1 h was created in COMSOL Multiphysics 5.1 considering heat generation evaluated from the experiment. The model analyzed the temperature distribution within the core and on the surface of biomass during torrefaction for various sizes. The model results showed similarities with experimental results. The effect of L/D ratio on temperature distribution within biomass was observed by varying length and diameter and compared with experiments in literature to find out an optimal range of cylindrical biomass size suitable for torrefaction. The research demonstrated that a cylindrical biomass sample of 50 mm length with L/D ratio of 2 can be torrefied with a core-surface temperature difference of less than 30 °C. The research also demonstrated that sample length has a negligible effect on core-surface temperature difference during torrefaction when the diameter is fixed at 25 mm. This information will help to design a torrefaction processing system and develop a value chain for biomass supply without using an energy-intensive grinding process.

  3. Modelling of heat transfer during torrefaction of large lignocellulosic biomass

    Science.gov (United States)

    Regmi, Bharat; Arku, Precious; Tasnim, Syeda Humaira; Mahmud, Shohel; Dutta, Animesh

    2018-02-01

    Preparation of feedstock is a major energy intensive process for the thermochemical conversion of biomass into fuel. By eliminating the need to grind biomass prior to the torrefaction process, there would be a potential gain in the energy requirements as the entire step would be eliminated. In regards to a commercialization of torrefaction technology, this study has examined heat transfer inside large cylindrical biomass both numerically and experimentally during torrefaction. A numerical axis-symmetrical 2-D model for heat transfer during torrefaction at 270°C for 1 h was created in COMSOL Multiphysics 5.1 considering heat generation evaluated from the experiment. The model analyzed the temperature distribution within the core and on the surface of biomass during torrefaction for various sizes. The model results showed similarities with experimental results. The effect of L/D ratio on temperature distribution within biomass was observed by varying length and diameter and compared with experiments in literature to find out an optimal range of cylindrical biomass size suitable for torrefaction. The research demonstrated that a cylindrical biomass sample of 50 mm length with L/D ratio of 2 can be torrefied with a core-surface temperature difference of less than 30 °C. The research also demonstrated that sample length has a negligible effect on core-surface temperature difference during torrefaction when the diameter is fixed at 25 mm. This information will help to design a torrefaction processing system and develop a value chain for biomass supply without using an energy-intensive grinding process.

  4. District heating systems for small scale development areas

    Energy Technology Data Exchange (ETDEWEB)

    McDougall, Rory e-mail: rory.mcdougall@online.no; Jensen, Bjoernulf

    2008-09-15

    Building projects are normally developed without considering integrated heating systems, especially where properties are for further sale. Due to focus on energy efficiency and environmental impact it is worth considering district heating systems, which include several energy carriers. The choice of energy carrier is assessed to optimize energy costs, account for environmental impact and obtain reliable heating supply, thus giving an energy flexible system for several buildings as opposed to individual heating systems in each building

  5. Efficient district heating in the future energy system. Final report; Effektiv fjernvarme i fremtidens energisystem. Slutrapport

    Energy Technology Data Exchange (ETDEWEB)

    2009-07-01

    The purpose of this project is to illustrate how district heating can develop its role in the future Danish energy system, for example by reducing energy losses and the dynamic use of common technologies such as cogeneration and heat storage, and less widespread technologies such as heat pumps, geothermal heating, and cooling. The aim is also to analyse how electricity and district heating can interact more effectively, and to point out how framework conditions are important for district heating's continued development and efficiency. In the project, a linear optimization model is developed and applied as to analyse the interaction between district heating supply on the one hand, and energy savings, CO{sub 2} targets, wind power and the international electricity market on the other hand. Furthermore, more close-case operational analyses of district heating systems have been made in Ringkoebing and the metropolitan area, based on data from the district heating companies. Finally, a wide range of challenges for district heating in the long term were discussed and analysed during meetings with the project's reference group, including the need for development and demonstration projects. (ln)

  6. Development of a Solar Assisted Drying System Using Double-Pass Solar Collector with Finned Absorber

    International Nuclear Information System (INIS)

    Azmi, M S M; Sopian, K; Ruslan, M H; Fudholi, A; Majid, Z A A; Yasin, J M; Othman, M Y

    2012-01-01

    The Solar Energy Research Group, Universiti Kebangsaan Malaysia, International Islamic University Malaysia and Yayasan FELDA has designed and constructed a solar assisted drying system at OPF FELDA Factory, Felda Bukit Sagu 2, Kuantan, Pahang. The drying system has a total of six double-pass solar collectors. Each collector has a length of 480 cm and a width of 120 cm. The first channel depth is 3.5 cm and the second channel depth is 7 cm. Longitudinal fins made of angle aluminium, 0.8 mm thickness were attached to the bottom surface of the absorber plate. The solar collectors are arranged as two banks of three collectors each in series. Internal manifold are used to connect the collectors. Air enters through the first channel and then through the second channel of the collector. An auxiliary heater source is installed to supply heat under unfavourable solar radiation condition. An on/off controller is used to control the startup and shutdown of the auxiliary heater. An outlet temperature of 70–75 °C can be achieved at solar radiation range of 800–900 W/m 2 and flow rate of 0.12 kg/s. The average thermal efficiency of a solar collector is approximately 37%.

  7. Development of a Solar Assisted Drying System Using Double-Pass Solar Collector with Finned Absorber

    Science.gov (United States)

    Azmi, M. S. M.; Othman, M. Y.; Sopian, K.; Ruslan, M. H.; Majid, Z. A. A.; Fudholi, A.; Yasin, J. M.

    2012-09-01

    The Solar Energy Research Group, Universiti Kebangsaan Malaysia, International Islamic University Malaysia and Yayasan FELDA has designed and constructed a solar assisted drying system at OPF FELDA Factory, Felda Bukit Sagu 2, Kuantan, Pahang. The drying system has a total of six double-pass solar collectors. Each collector has a length of 480 cm and a width of 120 cm. The first channel depth is 3.5 cm and the second channel depth is 7 cm. Longitudinal fins made of angle aluminium, 0.8 mm thickness were attached to the bottom surface of the absorber plate. The solar collectors are arranged as two banks of three collectors each in series. Internal manifold are used to connect the collectors. Air enters through the first channel and then through the second channel of the collector. An auxiliary heater source is installed to supply heat under unfavourable solar radiation condition. An on/off controller is used to control the startup and shutdown of the auxiliary heater. An outlet temperature of 70-75 °C can be achieved at solar radiation range of 800-900 W/m2 and flow rate of 0.12 kg/s. The average thermal efficiency of a solar collector is approximately 37%.

  8. A method of determining the thermal power demand of buildings connected to the district heating system with usage of heat accumulation

    Directory of Open Access Journals (Sweden)

    Turski Michał

    2017-01-01

    Full Text Available The paper presents a new method of determining the thermal power demand of buildings connected to the district heating system, which included the actual heat demand and the possibility of balancing the thermal power using the thermal storage capacity of district heating network and internal heat capacity of buildings. Moreover, the analysis of the effect of incidence of external air temperature and duration of episodes with the lowest outdoor temperatures on the thermal power demand of district heating system was conducted.

  9. Geothermal district heating applications in Turkey: a case study of Izmir-Balcova

    Energy Technology Data Exchange (ETDEWEB)

    Hepbasli, A. [Ege Univ., Dept. of Mechanical Engineering, Izmir (Turkey); Canakci, C. [Izmir-Balcova Geothermal Energy Inc., Izmir (Turkey)

    2003-05-01

    Turkey is located on the Mediterranean sector of the Alpine-Himalayan Tectonic Belt and is among the first seven countries in abundance of geothermal resources around the world. However, the share of its potential used is only about 2%. This means that considerable studies on geothermal energy could be conducted in order to increase the energy supply and to reduce atmospheric pollution in Turkey. The main objective in doing the present study is twofold, namely: (a) to overview the status and future aspects of geothermal district heating applications in Turkey and (b) to present the Izmir-Balcova geothermal district heating system, which is one example of the high temperature district heating applications in Turkey. The first geothermal heating application was applied in 1981 to the Izmir-Balcova thermal facilities, where the downhole heat exchanger was also used for the first time. Besides this, the first city based geothermal district heating system has been operated in Balikesir-Gonen since 1987. Recently, the total installed capacity has reached 820 MW{sub t} for direct use. An annual average growth of 23% of the residences connected to geothermal district heating systems has been achieved since 1983 in the country, representing a decrease of 5% in the last three years. Present applications have shown that in Turkey, geothermal energy is much cheaper than the other energy sources, like fossil fuels, and can make a significant contribution towards reducing the emission of greenhouse gases. (Author)

  10. District heating/cogeneration application studies for the Minneapolis-St Paul area. Executive summary; overall feasibility and economic viability for a district heating/new cogeneration system in Minneapolis-St. Paul

    Energy Technology Data Exchange (ETDEWEB)

    Margen, P.; Larsson, K.; Cronholm, L.A.; Marklund, J.E.

    1979-08-01

    A study was undertaken to determine the feasibility of introducing a large-scale, hot-water, district-heating system for the Minneapolis-St. Paul area. The analysis was based on modern European hot-water district-heating concepts in which cogeneration power plants supply the base-load thermal energy. Heat would be supplied from converted turbines of existing coal-fired power plants in Minneapolis and St. Paul. Toward the end of the 20-year development period, one or two new cogeneration units would be required. Thus, the district-heating system could use low-grade heat from either coal-fired or nuclear cogeneration power stations to replace the space-heating fuels currently used - natural gas and distillate oil. The following conclusions can be drawn: the concept is technically feasible, it has great value for fuel conservation, and with appropriate financing the system is economically viable.

  11. Competitive solar heating systems for residential buildings

    DEFF Research Database (Denmark)

    Furbo, Simon; Thür, Alexander; Fiedler, Frank

    2005-01-01

    The paper describes the ongoing research project “Competitive solar heating systems for residential buildings”. The aim of the project is to develop competitive solar combisystems which are attractive to buyers. The solar combisystems must be attractive compared to traditional energy systems, both....... In Denmark and Norway the focus is on solar heating/natural gas systems, and in Sweden and Latvia the focus is on solar heating/pellet systems. Additionally, Lund Institute of Technology and University of Oslo are studying solar collectors of various types being integrated into the roof and facade......, are the universities: Technical University of Denmark, Dalarna University, University of Oslo, Riga Technical University and Lund Institute of Technology, as well as the companies: Metro Therm A/S (Denmark), Velux A/S (Denmark), Solentek AB (Sweden) and SolarNor (Norway). The project consists of a number of Ph...

  12. Thermodynamic analysis and performance assessment of an integrated heat pump system for district heating applications

    International Nuclear Information System (INIS)

    Soltani, Reza; Dincer, Ibrahim; Rosen, Marc A.

    2015-01-01

    A Rankine cycle-driven heat pump system is modeled for district heating applications with superheated steam and hot water as products. Energy and exergy analyses are performed, followed by parametric studies to determine the effects of varying operating conditions and environmental parameters on the system performance. The district heating section is observed to be the most inefficient part of system, exhibiting a relative irreversibility of almost 65%, followed by the steam evaporator and the condenser, with relative irreversibilities of about 18% and 9%, respectively. The ambient temperature is observed to have a significant influence on the overall system exergy destruction. As the ambient temperature decreases, the system exergy efficiency increases. The electricity generated can increase the system exergy efficiency at the expense of a high refrigerant mass flow rate, mainly due to the fact that the available heat source is low quality waste heat. For instance, by adding 2 MW of excess electricity on top of the targeted 6 MW of product heat, the refrigerant mass flow rate increases from 12 kg/s (only heat) to 78 kg/s (heat and electricity), while the production of 8 MW of product heat (same total output, but in form of heat) requires a refrigerant mass flow rate of only 16 kg/s. - Highlights: • A new integrated heat pump system is developed for district heating applications. • An analysis and assessment study is undertaken through exergy analysis methodology. • A comparative efficiency evaluation is performed for practical applications. • A parametric study is conducted to investigate how varying operating conditions and state properties affect energy and exergy efficiencies.

  13. Energy of forest biomass in Croatia

    International Nuclear Information System (INIS)

    Cupin, N.; Krivak, B.; Dundovic, J.

    2005-01-01

    Forest biomass is organic substance raised in forest ecosystem, consisting of trees and bushes which are used for mechanical processing and thermal use. Croatia, with 44 percent of surface under forests, has the renewable energy potential in forest biomass that could cover as much as about 50 percent of the current heating consumption. The existence of an appropriate heating consume and district heating are a prerequisite for exploitation of the mentioned potential. At the same time, heating consumption enables the utilization of cogeneration plants and the paper gives examples of such possibilities in industry, community and special facilities (sport centres, hotels, hospitals etc.). Among them, the so called 'Croatian energy absurdum' is mentioned. The paper underlines the feasibility of exploitation of forest biomass at the national level and suggests that, in order to promote and accelerate the development of cogeneration plants, the HED expert group should be established. The task of the expert group would be to draft proposal for appropriate measures in this regard and submit it to the Government for consideration.(author)

  14. Optimal usage of low temperature heat sources to supply district heating by heat pumps

    DEFF Research Database (Denmark)

    Pieper, Henrik; Ommen, Torben Schmidt; Markussen, Wiebke Brix

    2017-01-01

    This paper presents a theoretical study on the optimal usage of different low temperature heat sources to supply district heating by heat pumps. The study is based on data for the Copenhagen region. The heat sources were prioritized based on the coefficient of performance calculated for each hour...... and the covered demand of each heat source as well as required peak unit capacity. The results showed that heat pumps using different heat sources yield better performance than a heat pump based on a single one. The performance was influenced by the composition of the different heat sources. It was found that 78......% groundwater, 22% seawater and 0% air resulted in highest COP of 3.33 for the given heat demand. Furthermore, the implementation of rule based short term storage made peak units redundant. The variation in base load capacity showed that heat pumps utilizing the analyzed heat sources could perform very...

  15. Biomass converted carbon quantum dots for all-weather solar cells

    International Nuclear Information System (INIS)

    Meng, Yuanyuan; Zhang, Yue; Sun, Weiyin; Wang, Min; He, Benlin; Chen, Haiyan; Tang, Qunwei

    2017-01-01

    Highlights: •CQDs are converted from soybean powders by a hydrothermal method. •The biomass converted CQDs are used for all-weather DSSCs. •The so-called all-weather DSSCs can generate electricity in the daytime and dark. •A dark efficiency as high as 7.97% is determined on the all-weather photovoltaics. •The launched solar cell extend our knowledge of advanced all-weather solar cells. -- Abstract: A great challenge for state-of-the-art photovoltaic devices is to realize electric power generation in all weathers. We constructively demonstrate here the conversion from biomass to carbon quantum dots for all-weather carbon quantum dot solar cells that can generate electricity in the daytime and in the dark. The combination of green-emitting long persistence phosphors with mesoscopic titanium dioxide realizes optical storage by composite photoanode under illumination and excitation to monochromatic green light in the dark. The optimized all-weather solar cell yields maximized dark power conversion efficiency as high as 7.97% along with persistent electricity output for several hours. This work begins a photovoltaic revolution to forward all-weather solar cells as future energy solutions.

  16. A heat pipe solar collector system for winter heating in Zhengzhou city, China

    Directory of Open Access Journals (Sweden)

    Zheng Hui-Fan

    2017-01-01

    Full Text Available A heat pipe solar collector system for winter heating is investigated both experimentally and theoretically. The hourly heat collecting capacity, water temperature and contribution rate of solar collector system based on Zhengzhou city typical sunshine are calculated. The study reveals that the heat collecting capacity and water temperature increases initially and then decreases, and the solar collector system can provide from 40% to 78% heating load for a 200 m2 villa with in Zhengzhou city from November to March.

  17. The analysis of thermal network of district heating system from investor point of view

    Science.gov (United States)

    Takács, Ján; Rácz, Lukáš

    2016-06-01

    The hydraulics of a thermal network of a district heating system is a very important issue, to which not enough attention is often paid. In this paper the authors want to point out some of the important aspects of the design and operation of thermal networks in district heating systems. The design boundary conditions of a heat distribution network and the requirements on active pressure - circulation pump - influencing the operation costs of the centralized district heating system as a whole, are analyzed in detail. The heat generators and the heat exchange stations are designed according to the design heat loads after thermal insulation, and modern boiler units are installed in the heating plant.

  18. High performance passive solar heating system with heat pipe energy transfer and latent heat storage

    NARCIS (Netherlands)

    Dijk, van H.A.L.; Galen, van E; Hensen, J.L.M.; Wit, de M.H.

    1983-01-01

    Preliminar results are reported from a current project on the development of a high performance passive solar heating system. Two special components are introduced: a. A heat pipe as a thermal diode tube for the efficient transfer of collected solar heat from the absorber plate to behind an

  19. High-power condensation turbine application to district heating

    International Nuclear Information System (INIS)

    Virchenko, M.A.; Arkad'ev, B.A.; Ioffe, V.Yu.

    1982-01-01

    In general outline the role of condensation turbines in NPP district heating is considered. The expediency of expansion of central heating loading of turbines of operating as well as newly designed condensation power plants on the basis of the WWER-1000-type reactors is shown. The principle heat flowsheet of the 1000 MW power turbine is given. An advantage in using turbines with uncontrolled steam bleeding is pointed out [ru

  20. LeBreton Flats district heating: Institutional issues

    Energy Technology Data Exchange (ETDEWEB)

    Gerow, L.B.; Bernstein, H.

    1981-12-01

    Despite the growing popularity in Europe of district heating as an alternative to conventional systems, a number of institutional barriers blocked the road to its successful implementation in Canada. These hurdles include questions of ownership, operation/administration, consumer accountability, financial arrangements, and general consumer acceptance of a new technology. In deciding on ownership, the major issues were legal. Provincial laws to be complied with included The Municipal Franchises Act, The Public Utilities Act, The Municipal Act and The Ontario Municipal Board Act. The operation and administration of the project were also beset with legal complications. The relevant laws were The Boilers and Pressure Vessels Act, and The Environmental Assessment Act. How to charge individual users (consumer accountability) raised a number of technical problems including metering and rate-setting for hot water distribution, and heat borrowing between units. The report recommends that groups planning to implement district heating are advised to allow plenty of lead time for obtaining approvals and franchising arrangements so as not to jeopardize construction schedules. 3 refs.