  1. Load calculations of radiant cooling systems for sizing the plant

    DEFF Research Database (Denmark)

    Bourdakis, Eleftherios; Kazanci, Ongun Berk; Olesen, Bjarne W.

    2015-01-01

    The aim of this study was, by using a building simulation software, to prove that a radiant cooling system should not be sized based on the maximum cooling load but at a lower value. For that reason six radiant cooling models were simulated with two control principles using 100%, 70% and 50% of t...

  2. Load calculations of radiant cooling systems for sizing the plant

    DEFF Research Database (Denmark)

    Bourdakis, Eleftherios; Kazanci, Ongun Berk; Olesen, Bjarne W.

    2015-01-01

    The aim of this study was, by using a building simulation software, to prove that a radiant cooling system should not be sized based on the maximum cooling load but at a lower value. For that reason six radiant cooling models were simulated with two control principles using 100%, 70% and 50...

  3. Analysis of the evaporative towers cooling system of a coal-fired power plant

    Directory of Open Access Journals (Sweden)

    Laković Mirjana S.

    2012-01-01

    Full Text Available The paper presents a theoretical analysis of the cooling system of a 110 MW coal-fired power plant located in central Serbia, where eight evaporative towers cool down the plant. An updated research on the evaporative tower cooling system has been carried out to show the theoretical analysis of the tower heat and mass balance, taking into account the sensible and latent heat exchanged during the processes which occur inside these towers. Power plants which are using wet cooling towers for cooling condenser cooling water have higher design temperature of cooling water, thus the designed condensing pressure is higher compared to plants with a once-through cooling system. Daily and seasonal changes further deteriorate energy efficiency of these plants, so it can be concluded that these plants have up to 5% less efficiency compared to systems with once-through cooling. The whole analysis permitted to evaluate the optimal conditions, as far as the operation of the towers is concerned, and to suggest an improvement of the plant. Since plant energy efficiency improvement has become a quite common issue today, the evaluation of the cooling system operation was conducted under the hypothesis of an increase in the plant overall energy efficiency due to low cost improvement in cooling tower system.

  4. Marginal costs of water savings from cooling system retrofits: a case study for Texas power plants

    Science.gov (United States)

    Loew, Aviva; Jaramillo, Paulina; Zhai, Haibo

    2016-10-01

    The water demands of power plant cooling systems may strain water supply and make power generation vulnerable to water scarcity. Cooling systems range in their rates of water use, capital investment, and annual costs. Using Texas as a case study, we examined the cost of retrofitting existing coal and natural gas combined-cycle (NGCC) power plants with alternative cooling systems, either wet recirculating towers or air-cooled condensers for dry cooling. We applied a power plant assessment tool to model existing power plants in terms of their key plant attributes and site-specific meteorological conditions and then estimated operation characteristics of retrofitted plants and retrofit costs. We determined the anticipated annual reductions in water withdrawals and the cost-per-gallon of water saved by retrofits in both deterministic and probabilistic forms. The results demonstrate that replacing once-through cooling at coal-fired power plants with wet recirculating towers has the lowest cost per reduced water withdrawals, on average. The average marginal cost of water withdrawal savings for dry-cooling retrofits at coal-fired plants is approximately 0.68 cents per gallon, while the marginal recirculating retrofit cost is 0.008 cents per gallon. For NGCC plants, the average marginal costs of water withdrawal savings for dry-cooling and recirculating towers are 1.78 and 0.037 cents per gallon, respectively.

  5. Performance analysis of a combined cycle gas turbine power plant by using various inlet air cooling systems

    Energy Technology Data Exchange (ETDEWEB)

    Rahim, Murad A. [Department of Mechanical Engineering, Gazi University (Turkey)], e-mail: mrahim@gazi.edu.tr

    2011-07-01

    In recent years, the use of gas turbines in combined cycle power plants has increased. Turbine inlet air cooling appears to be the best solution for maximizing both production and efficiency, particularly in a hot climate. The aim of this study is to determine the impact of different air cooling systems on the gas turbine's performance and carbon dioxide emissions. Computer simulations were carried out, using the THERMOFLEX program, on fogging, evaporative cooling, adsorption cooling, and electrical chiller cooling systems as well as on a base case without cooling system. Results showed that inlet air cooling systems are effective in increasing the efficiency of gas turbine power plants. In addition it was found that absorption chillers are the best system for increasing power generation but that economic and source analyses should be conducted before installing a cooling system. This paper demonstrated that inlet air cooling systems have the ability to increase net power generation of gas turbine power plants.

  6. Web-based distributed System for TOF Experiment Cooling Plant Monitoring

    CERN Document Server

    Blanc, D

    2001-01-01

    This paper discusses the monitoring and control system for an automated cooling process. The plant is located in an experiment environment and with some distance between the principal components of the system namely the cooling station of the lead target temperature measurements and the TOF experiment control room. TOF experiment operators interact from a SCADA supervisory station through the TCP-IP Ethernet communication channel with the cooling plant. The main issue concerns the degree of automation given to the plant and the SCADA station to greatly ease the TOF control room operation. Another important issue is the real need for TOF physicists and vacuum technicians to access specific operational information in their respective process systems. In this way the availability of the Wizcon® Web-based SCADA applications, which reside on standard Windows NT Web servers, deliver real-time access and historical data to the different applications. The various authorised users can interact with their own applicat...

  7. The effects of age on nuclear power plant containment cooling systems

    Energy Technology Data Exchange (ETDEWEB)

    Lofaro, R.; Subudhi, M.; Travis, R.; DiBiasio, A.; Azarm, A. [Brookhaven National Lab., Upton, NY (United States); Davis, J. [Science Applications International Corp., New York, NY (United States)

    1994-04-01

    A study was performed to assess the effects of aging on the performance and availability of containment cooling systems in US commercial nuclear power plants. This study is part of the Nuclear Plant Aging Research (NPAR) program sponsored by the US Nuclear Regulatory Commission. The objectives of this program are to provide an understanding of the aging process and how it affects plant safety so that it can be properly managed. This is one of a number of studies performed under the NPAR program which provide a technical basis for the identification and evaluation of degradation caused by age. The effects of age were characterized for the containment cooling system by reviewing and analyzing failure data from national databases, as well as plant-specific data. The predominant failure causes and aging mechanisms were identified, along with the components that failed most frequently. Current inspection, surveillance, and monitoring practices were also examined. A containment cooling system unavailability analysis was performed to examine the potential effects of aging by increasing failure rates for selected components. A commonly found containment spray system design and a commonly found fan cooler system design were modeled. Parametric failure rates for those components in each system that could be subject to aging were accounted for in the model to simulate the time-dependent effects of aging degradation, assuming no provisions are made to properly manage it. System unavailability as a function of increasing component failure rates was then calculated.

  8. Legionnaires' Disease Bacterium in power-plant cooling systems: Phase 1. Final report

    Energy Technology Data Exchange (ETDEWEB)

    Christensen, S.W.; Solomon, J.A.; Gough, S.B.; Tyndall, R.L.; Fliermans, C.B.

    1983-06-01

    A survey was undertaken of the distribution, density, viability, and infectivity of Legionnaires' Disease Bacteria (Legionella) in power plant cooling systems. Water samples were collected during each of the four seasons at various locations within each of nine power plants and from ambient waters at each site. Measurements of a number of physical and chemical characteristics were made, and Legionella profiles (density, viability, and infectivity for guinea pigs) were obtained. Legionella were detected in nearly all samples. Water from closed-cycle cooling systems frequently had lower densities of Legionella than the ambient water. Nonetheless, infectious Legionella, as defined by their isolation from inoculated guinea pigs, were significantly more likely to be found in samples from the plant-exposed water of closed-cycle plants than in samples from once-through plants or in ambient samples. A new species (L. oakridgensis) was initially isolated from two of the sites, and it has since been found to have a widespread distribution. Two other organisms found to cause illness in guinea pigs may also be new species. Phase II of the project involves investigating possible cause/effect relationships between physicochemical variables and Legionella. This work may contribute toward eventual control techniques for this pathogen.

  9. Legionnaires' disease bacteria in power plant cooling systems: Phase 2

    Energy Technology Data Exchange (ETDEWEB)

    Tyndall, R.L.; Christensen, S.W.; Solomon, J.A.

    1985-04-01

    Legionnaires' Disease Bacteria (Legionella) are a normal component of the aquatic community. The study investigated various environmental factors that affect Legionella profiles in power plant cooling waters. The results indicate that each of the four factors investigated (incubation temperature, water quality, the presence and type of associated biota, and the nature of the indigenous Legionella population) is important in determining the Legionella profile of these waters. Simple predictive relationships were not found. At incubation temperatures of 32/sup 0/ and 37/sup 0/C, waters from a power plant where infectious Legionella were not observed stimulated the growth of stock Legionella cultures more than did waters from plants where infectious Legionella were prevalent. This observation is consistent with Phase I results, which showed that densities of Legionella were frequently reduced in closed-cycle cooling systems despite the often higher infectivity of Legionella in closed-cycle waters. In contrast, water from power plants where infectious Legionella were prevalent supported the growth of indigenous Legionella pneumophila at 42/sup 0/C, while water from a power plant where infectious Legionella were absent did not support growth of indigenous Legionella. Some Legionella are able to withstand a water temperature of 85/sup 0/C for several hours, thus proving more tolerant than was previously realized. Finally, the observation that water from two power plants where infectious Legionella were prevalent usually supported the growth of Group A Legionella at 45/sup 0/C indicates the presence, of soluble Legionella growth promoters in these waters. This test system could allow for future identification and control of these growth promoters and, hence, of Legionella. 25 refs., 23 figs., 10 tabs.

  10. Mandate a Man to Fish?: Technological advance in cooling systems at U.S. thermal electric plants

    Science.gov (United States)

    Peredo-Alvarez, Victor M.; Bellas, Allen S.; Trainor-Guitton, Whitney J.; Lange, Ian

    2016-02-01

    Steam-based electrical generating plants use large quantities of water for cooling. The potential environmental impacts of water cooling systems have resulted in their inclusion in the Clean Water Act's (CWA) Sections 316(a), related to thermal discharges and 316(b), related to cooling water intake. The CWA mandates a technological standard for water cooling systems. This analysis examines how the performance-adjusted rates of thermal emissions and water withdrawals for cooling units have changed over their vintage and how these rates of change were impacted by imposition of the CWA. Results show that the rate of progress increased for cooling systems installed after the CWA whilethere was no progress previous to it.

  11. Performance of introducing outdoor cold air for cooling a plant production system with artificial light

    Directory of Open Access Journals (Sweden)

    Jun eWang

    2016-03-01

    Full Text Available The commercial use of a plant production system with artificial light (PPAL is limited by its high initial construction and operation costs. The electric-energy consumed by heat pumps, applied mainly for cooling, accounts for 15-35% of the total electric-energy used in a PPAL. To reduce the electric-energy consumption, an air exchanger with low capacity (180 W was used for cooling by introducing outdoor cold air. In this experiment, the indoor air temperature in two PPALs (floor area: 6.2 m2 each was maintained at 25ºC and 20ºC during light and dark periods, respectively, for lettuce production. In one PPAL (PPALe, an air exchanger (air flow rate: 250 m3 h-1 was used along with a heat pump (cooling capacity: 3.2 kW to maintain the indoor air temperature at the set-point. The other PPAL (PPALc with only a heat pump (cooling capacity: 3.2 kW was used for reference. Effects of introducing outdoor cold air on energy use efficiency, coefficient of performance (COP, electric-energy consumption for cooling and growth of lettuce were investigated. The results show that: when the air temperature difference between indoor and outdoor ranged from 20.2°C to 30.0°C: 1 the average energy use efficiency of the air exchanger was 2.8 and 3.4 times greater than the COP of the heat pumps in the PPALe and PPALc, respectively; 2 hourly electric-energy consumption in the PPALe reduced by 15.8-73.7% compared with that in the PPALc; 3 daily supply of CO2 in the PPALe reduced from 0.15 kg to 0.04 kg compared with that in the PPALc; 4 no significant difference in lettuce growth was observed in both PPALs. The results indicate that using air exchanger to introduce outdoor cold air should be considered as an effective way to reduce electric-energy consumption for cooling with little effects on plant growth in a PPAL.

  12. Comparative analysis of cooling systems for energy equipment of combined heat and power plants and nuclear power plants

    Science.gov (United States)

    Reutov, B. F.; Lazarev, M. V.; Ermakova, S. V.; Zisman, S. L.; Kaplanovich, L. S.; Svetushkov, V. V.

    2016-07-01

    In the 20th century, the thermal power engineering in this country was oriented toward oncethrough cooling systems. More than 50% of the CHPP and NPP capacities with once-through cooling systems put into operation before the 1990s were large-scale water consumers but with minimum irretrievable water consumption. In 1995, the Water Code of the Russian Federation was adopted in which restrictions on application of once-through cooling systems for newly designed combined heat and power plants (CHPPs) were introduced for the first time. A ban on application of once-through systems was imposed by the current Water Code of the Russian Federation (Federal law no. 74-FZ, Art. 60 Cl. 4) not only for new CHPPs but also for those to be modified. Clause 4 of Article 60 of the Water Code of the Russian Federation contravenes law no. 7-FZ "On Protection of the Environment" that has priority significance, since the water environment is only part of the natural environment and those articles of the Water Code of the Russian Federation that are related directly to electric power engineering, viz., Articles 46 and 62. In recent decades, the search for means to increase revenue charges and the economic pressure on the thermal power industry caused introduction by law of charges for use of water by cooling systems irrespective of the latter's impact on the water quality of the source, the environment, the economic efficiency of the power production, and the living conditions of the people. The long-range annual increase in the water use charges forces the power generating companies to switch transfer once-through service water supply installations to recirculating water supply systems and once-through-recirculating systems with multiple reuse of warm water, which drastically reduces the technical, economic, and ecological characteristic of the power plant operation and also results in increasing power rates for the population. This work comprehensively substantiates the demands of

  13. Global Freshwater Thermal Pollution from Steam-Electric Power Plants with Once-Through Cooling Systems

    Science.gov (United States)

    Raptis, C. E.; van Vliet, M. T. H.; Pfister, S.

    2015-12-01

    Thermoelectric power generation requires large amounts of cooling water. In facilities employing once-through cooling systems the heat removed in the power cycle is rejected directly into a water body. Several studies have focused on the impacts of power-related thermal emissions in Europe and the U.S., in terms of river temperature increase and the capacity for power production, especially in the light of legislative measures designed to protect freshwater bodies from excessive temperature. In this work we present a comprehensive, global analysis of current freshwater thermal pollution by thermoelectric facilities. The Platts World Electric Power Plant (WEPP) database was the principal data source. Data gaps in the principal parameters of the steam-electric power cycle were filled in by regression relationships developed in this work. Some 2400 steam-electric units using once-through freshwater cooling systems, amounting to 19% of the global installed capacity of thermoelectric units, were identified and georeferenced, and a global view of thermal emission rates was achieved by systematically solving the Rankine cycle on a power generating unit level. The rejected heat rates are linearly proportional to the steam flow rate, which in turn is directly proportional to the power produced. By applying the appropriate capacity factors, the rejected heat rate can be estimated for each unit or agglomeration of units at the desired temporal resolution. We coupled mean annual emission rates with the global gridded hydrological-river temperature model VIC-RBM to obtain a first view of river temperature increases resulting from power generation. The results show that in many cases, even on a mean annual emission rate basis and a relatively large spatial resolution of 0.5 x 0.5 degrees, the local limits for temperature increase are often exceeded, especially in the U.S. and Europe.

  14. District heating and cooling systems for communities through power plant retrofit and distribution network. Final report. Volume I. Text

    Energy Technology Data Exchange (ETDEWEB)

    None

    1979-09-15

    An analysis was performed investigating the potential of retrofitting Detroit Edison's Conners Creek power plant to supply district heating and cooling to an area surrounding the plant and within the City of Detroit. A detailed analysis was made of the types and ages of the buildings in the service area as a basis for establishing loads. The analysis of the power plant established possible modifications to the turbines to serve the load in the area. Based upon the service area data and plant retrofit schemes, a distribution system was developed incrementally over a 20-y period. An economic analysis of the system was performed to provide cash flows and payback periods for a variety of energy costs, system costs, and escalation rates to determine the economic viability of the system analyzed. The legal and regulatory requirements required of the district heating and cooling system owner in Michigan were also analyzed to determine what conditions must be met to own and operate the system.

  15. A very cool cooling system

    CERN Multimedia

    Antonella Del Rosso

    2015-01-01

    The NA62 Gigatracker is a jewel of technology: its sensor, which delivers the time of the crossing particles with a precision of less than 200 picoseconds (better than similar LHC detectors), has a cooling system that might become the precursor to a completely new detector technique.   The 115 metre long vacuum tank of the NA62 experiment. The NA62 Gigatracker (GTK) is composed of a set of three innovative silicon pixel detectors, whose job is to measure the arrival time and the position of the incoming beam particles. Installed in the heart of the NA62 detector, the silicon sensors are cooled down (to about -20 degrees Celsius) by a microfluidic silicon device. “The cooling system is needed to remove the heat produced by the readout chips the silicon sensor is bonded to,” explains Alessandro Mapelli, microsystems engineer working in the Physics department. “For the NA62 Gigatracker we have designed a cooling plate on top of which both the silicon sensor and the...

  16. Exergetic Analysis of a Novel Solar Cooling System for Combined Cycle Power Plants

    Directory of Open Access Journals (Sweden)

    Francesco Calise

    2016-09-01

    Full Text Available This paper presents a detailed exergetic analysis of a novel high-temperature Solar Assisted Combined Cycle (SACC power plant. The system includes a solar field consisting of innovative high-temperature flat plate evacuated solar thermal collectors, a double stage LiBr-H2O absorption chiller, pumps, heat exchangers, storage tanks, mixers, diverters, controllers and a simple single-pressure Combined Cycle (CC power plant. Here, a high temperature solar cooling system is coupled with a conventional combined cycle, in order to pre-cool gas turbine inlet air in order to enhance system efficiency and electrical capacity. In this paper, the system is analyzed from an exergetic point of view, on the basis of an energy-economic model presented in a recent work, where the obtained main results show that SACC exhibits a higher electrical production and efficiency with respect to the conventional CC. The system performance is evaluated by a dynamic simulation, where detailed simulation models are implemented for all the components included in the system. In addition, for all the components and for the system as whole, energy and exergy balances are implemented in order to calculate the magnitude of the irreversibilities within the system. In fact, exergy analysis is used in order to assess: exergy destructions and exergetic efficiencies. Such parameters are used in order to evaluate the magnitude of the irreversibilities in the system and to identify the sources of such irreversibilities. Exergetic efficiencies and exergy destructions are dynamically calculated for the 1-year operation of the system. Similarly, exergetic results are also integrated on weekly and yearly bases in order to evaluate the corresponding irreversibilities. The results showed that the components of the Joule cycle (combustor, turbine and compressor are the major sources of irreversibilities. System overall exergetic efficiency was around 48%. Average weekly solar collector

  17. Study on chemical control indicators for circulating cooling systems water chemistry at power plants

    OpenAIRE

    Кишневский, Виктор Афанасьевич; Чиченин, Вадим Валентинович

    2014-01-01

    An analysis of applied stability indices, used for water chemistry control of circulating cooling systems at TPP and NPP is given in the paper.The spectrum of controlled indicators of circulating and make-up water during long-term operation of various water chemistries on scale models of circulating cooling systems at TPP and NPP is investigated.The results of chemical control of water chemistry with dosing mineral acid to make-up water and acrylic water chemistry without dosing mineral acid ...

  18. Data center cooling system

    Energy Technology Data Exchange (ETDEWEB)

    Chainer, Timothy J; Dang, Hien P; Parida, Pritish R; Schultz, Mark D; Sharma, Arun

    2015-03-17

    A data center cooling system may include heat transfer equipment to cool a liquid coolant without vapor compression refrigeration, and the liquid coolant is used on a liquid cooled information technology equipment rack housed in the data center. The system may also include a controller-apparatus to regulate the liquid coolant flow to the liquid cooled information technology equipment rack through a range of liquid coolant flow values based upon information technology equipment temperature thresholds.

  19. A Techno-Economic Assessment of Hybrid Cooling Systems for Coal- and Natural-Gas-Fired Power Plants with and without Carbon Capture and Storage.

    Science.gov (United States)

    Zhai, Haibo; Rubin, Edward S

    2016-04-05

    Advanced cooling systems can be deployed to enhance the resilience of thermoelectric power generation systems. This study developed and applied a new power plant modeling option for a hybrid cooling system at coal- or natural-gas-fired power plants with and without amine-based carbon capture and storage (CCS) systems. The results of the plant-level analyses show that the performance and cost of hybrid cooling systems are affected by a range of environmental, technical, and economic parameters. In general, when hot periods last the entire summer, the wet unit of a hybrid cooling system needs to share about 30% of the total plant cooling load in order to minimize the overall system cost. CCS deployment can lead to a significant increase in the water use of hybrid cooling systems, depending on the level of CO2 capture. Compared to wet cooling systems, widespread applications of hybrid cooling systems can substantially reduce water use in the electric power sector with only a moderate increase in the plant-level cost of electricity generation.

  20. Reuse of Treated Internal or External Wastewaters in the Cooling Systems of Coal-Based Thermoelectric Power Plants

    Energy Technology Data Exchange (ETDEWEB)

    Radisav Vidic; David Dzombak; Ming-Kai Hsieh; Heng Li; Shih-Hsiang Chien; Yinghua Feng; Indranil Chowdhury; Jason Monnell

    2009-06-30

    This study evaluated the feasibility of using three impaired waters - secondary treated municipal wastewater, passively treated abandoned mine drainage (AMD), and effluent from ash sedimentation ponds at power plants - for use as makeup water in recirculating cooling water systems at thermoelectric power plants. The evaluation included assessment of water availability based on proximity and relevant regulations as well as feasibility of managing cooling water quality with traditional chemical management schemes. Options for chemical treatment to prevent corrosion, scaling, and biofouling were identified through review of current practices, and were tested at bench and pilot-scale. Secondary treated wastewater is the most widely available impaired water that can serve as a reliable source of cooling water makeup. There are no federal regulations specifically related to impaired water reuse but a number of states have introduced regulations with primary focus on water aerosol 'drift' emitted from cooling towers, which has the potential to contain elevated concentrations of chemicals and microorganisms and may pose health risk to the public. It was determined that corrosion, scaling, and biofouling can be controlled adequately in cooling systems using secondary treated municipal wastewater at 4-6 cycles of concentration. The high concentration of dissolved solids in treated AMD rendered difficulties in scaling inhibition and requires more comprehensive pretreatment and scaling controls. Addition of appropriate chemicals can adequately control corrosion, scaling and biological growth in ash transport water, which typically has the best water quality among the three waters evaluated in this study. The high TDS in the blowdown from pilot-scale testing units with both passively treated mine drainage and secondary treated municipal wastewater and the high sulfate concentration in the mine drainage blowdown water were identified as the main challenges for blowdown

  1. Radiant Floor Cooling Systems

    DEFF Research Database (Denmark)

    Olesen, Bjarne W.

    2008-01-01

    In many countries, hydronic radiant floor systems are widely used for heating all types of buildings such as residential, churches, gymnasiums, hospitals, hangars, storage buildings, industrial buildings, and smaller offices. However, few systems are used for cooling.This article describes a floor...... cooling system that includes such considerations as thermal comfort of the occupants, which design parameters will influence the cooling capacity and how the system should be controlled. Examples of applications are presented....

  2. Construction of a cooling water inlet system with settling basin of Derna power plant station (Libya)

    Energy Technology Data Exchange (ETDEWEB)

    Glissmann, R.; Heimburg, A.M. von; Sinner, H.

    1985-03-01

    Construction of a cooling water intake system with settling basin. The extension of the power station at Derna, in Libya, necessitated the construction of a new cooling water intake system including screening facilities and a settling basin. Construction based on extensive prefabrication (precast concrete) was chosen. The precast reinforced units, ranging up to about 4000 t in weight, were towed on barges to the site of erection. At Derna these units were temporarily stored on the sea bed for several months, during which they were exposed to winter storms and rough sea. The major precast portion of the settling basin was constructed direct on the barge. On arrival at the site, the barge was sunk, allowing the precast unit, which was designed with sufficient buoyancy, to be floated off. The open unprotected coast required special arrangements for the protection of personnel, structures and equipment.

  3. IMPROVEMENT OF SYSTEMS OF TECHNICAL WATER SUPPLY WITH COOLING TOWERS FOR HEAT POWER PLANTS TECHNICAL AND ECONOMIC INDICATORS PERFECTION. Part 2

    Directory of Open Access Journals (Sweden)

    Yu. A. Zenovich-Leshkevich-Olpinskiy

    2016-01-01

    Full Text Available The method of calculation of economic efficiency that can be universal and is suitable for feasibility study of modernization of irrigation and water distribution system of cooling towers has been developed. The method takes into account the effect of lower pressure exhaust steam in the condenser by lowering the temperature of the cooling water outlet of a cooling tower that aims at improvement of technical and economic indicators of heat power plants. The practical results of the modernization of irrigation and water distribution system of a cooling tower are presented. As a result, the application of new irrigation and water distribution systems of cooling towers will make it possible to increase the cooling efficiency by more than 4 оС and, therefore, to obtain the fuel savings by improving the vacuum in the turbine condensers. In addition, the available capacity of CHP in the summer period is increased. The results of the work, the experience of modernization of irrigation and water distribution systems of the Gomel CHP-2 cooling towers system, as well as the and methods of calculating of its efficiency can be disseminated for upgrading similar facilities at the power plants of the Belarusian energy system. Some measures are prosed to improve recycling systems, cooling towers and their structures; such measures might significantly improve the reliability and efficiency of technical water supply systems of heat power plants.

  4. A LOPA application to the hydrogen cooling system of the main electric generator of a nuclear power plant

    Energy Technology Data Exchange (ETDEWEB)

    Vasconcelos, Flavia M.; Frutuoso e Melo, Paulo Fernando Ferreira [Universidade Federal do Rio de Janeiro (UFRJ), RJ (Brazil)]. E-mails: flaviamvasconcelos@gmail.com; frutuoso@con.ufrj.br; Saldanha, P.L. [Comissao Nacional de Energia Nuclear (CNEN), Rio de Janeiro, RJ (Brazil). Coordenacao de Reatores]. E-mail: saldanha@cnen.gov.br

    2008-07-01

    The Layer of Protection Analysis (LOPA) is a powerful analytical tool for assessing the adequacy of protection layers used to mitigate risks in a process plant. LOPA applies semi-quantitative measures to evaluate the frequency of potential incidents and the probability of failure of protection layers. This paper presents an application of the Layer of Protection Analysis technique to a nuclear power plant in order to evaluate the cooling system of an electric generator, so as to identify scenarios that might lead to a plant shutdown. Next, the frequencies of occurrence of these events and the probability of failure on demand of the independent protection layers are determined. Here a difficulty is related to the lack of failure and initiating event data. The consequences identified are listed as impact events and are classified as to their severity level. The initiating causes are listed for each impact event and the likelihood is estimated for each initiating cause. Independent Protection Layers (ILPs) are listed. The mitigated event likelihood is studied and additional ILPs can be evaluated and added to reduce the risk. As a conclusion, LOPA demonstrated that the hydrogen inner-cooling electric generator system is in compliance with the risk scenarios adopted for this study. Some suggestions were made in order to automate some manual actions to increase the system reliability. (author)

  5. Influence of thermal flow field of cooling tower on recirculation ratio of a direct air-cooled system for a power plant

    Institute of Scientific and Technical Information of China (English)

    Zhao Wanli; Liu Peiqing

    2008-01-01

    In order to get thermal flow field of direct air-cooled system,the hot water was supplied to the model of direct air-cooled condenser(ACC).The particle image velocimetery(PIV)experiments were carried out to get thermal flow field of a ACC under different conditions in low velocity wind tunnel,at the same time,the recirculation ratio at cooling tower was measured,so the relationship between flow field characteristics and recirculation ratio of cooling tower can be discussed.From the results we can see that the flow field configuration around cooling tower has great effects on average recirculation ratio under cooling tower.The eddy formed around cooling tower is a key reason that recireulation pro-duces.The eddy intensity relates to velocity magnitude and direction angle,and the configuration of eddy lies on the ge-ometry size of cooling tower.So changing the flow field configuration around cooling tower reasonably can decrease recir-culation ratio under cooling tower,and heat dispel effect of ACC can also be improved.

  6. Natural Circulation in Water Cooled Nuclear Power Plants Phenomena, models, and methodology for system reliability assessments

    Energy Technology Data Exchange (ETDEWEB)

    Jose Reyes

    2005-02-14

    In recent years it has been recognized that the application of passive safety systems (i.e., those whose operation takes advantage of natural forces such as convection and gravity), can contribute to simplification and potentially to improved economics of new nuclear power plant designs. In 1991 the IAEA Conference on ''The Safety of Nuclear Power: Strategy for the Future'' noted that for new plants the use of passive safety features is a desirable method of achieving simplification and increasing the reliability of the performance of essential safety functions, and should be used wherever appropriate''.

  7. Hydronic rooftop cooling systems

    Science.gov (United States)

    Bourne, Richard C.; Lee, Brian Eric; Berman, Mark J.

    2008-01-29

    A roof top cooling unit has an evaporative cooling section that includes at least one evaporative module that pre-cools ventilation air and water; a condenser; a water reservoir and pump that captures and re-circulates water within the evaporative modules; a fan that exhausts air from the building and the evaporative modules and systems that refill and drain the water reservoir. The cooling unit also has a refrigerant section that includes a compressor, an expansion device, evaporator and condenser heat exchangers, and connecting refrigerant piping. Supply air components include a blower, an air filter, a cooling and/or heating coil to condition air for supply to the building, and optional dampers that, in designs that supply less than 100% outdoor air to the building, control the mixture of return and ventilation air.

  8. Intelligent control of a cryogenic cooling plant based on blackboard system architecture.

    Science.gov (United States)

    Linkens, D A; Abbod, M F; Browne, A; Cade, N

    2000-01-01

    Intelligent system techniques have been rapidly assimilating into process control engineering, with many applications reported in the last decade. Intelligent control is bringing a new perspective as well as new challenges to process control. In this paper, a software architecture for a Blackboard for Integrated Intelligent Control Systems (BIICS) is described. The system is designed to simultaneously support multiple heterogeneous intelligent methodologies, such as neural networks. expert systems, fuzzy logic, neural networks and genetic algorithms. It will be shown how such methodologies can be readily assimilated into the software architecture. The BIICS system represents a multi-purpose platform for design and simulation of intelligent control paradigms for different kinds of processes. Currently the system utilizes intelligent control techniques (neuro-fuzzy and genetic optimization) for controlling a cryogenic plant used for superconductor testing at temperatures below 100 K.

  9. The ITER neutral beam test facility: designs of the general infrastructure, cryo-system and cooling plant

    Energy Technology Data Exchange (ETDEWEB)

    Cordier, J.J.; Hemsworth, R.; Chantant, M.; Gravil, B.; Henry, D.; Sabathier, F.; Doceul, L.; Thomas, E.; Van Houtte, D. [Association Euratom-CEA Cadarache (DSM/DRFC), 13 - Saint-Paul-lez-Durance (France). Dept. de Recherches sur la Fusion Controlee; Zaccaria, P.; Antoni, V.; Dal Bello, S.; Masiello, A.; Marcuzzi, D. [Consorzio RFX Association Euratom-ENEA, Padova (Italy); Antipenkov, A.; Dremel, M.; Day, C. [Institut fur Technische Physik, FZK, Karlsruhe (Germany); Mondino, P.L. [Max-Planck-Institut fuer Plasmaphysik, EFDA CSU, Garching (Germany)

    2004-07-01

    The CEA Association is involved, in close collaboration with ENEA, FZK, IPP and UKEA European Associations, in the first ITER neutral beam injector and the ITER neutral beam test facility design (NBTF). A total power of about 50 MW will have to be removed in steady state on the neutral beam test facility (NBTF). The main purpose of this task is to make progress with the detailed design of the first ITER NB injector and to start the conceptual design of the ITER NBTF. The general infrastructure layout of a generic site for the NBTF, includes the test facility itself equipped of a dedicated beamline vessel and integration studies of associated auxiliaries as cooling plant, cryo-plant and fore-pumping system. The general infrastructure and auxiliaries layout of the NBTF are described. (authors)

  10. Superconductor rotor cooling system

    Science.gov (United States)

    Gamble, Bruce B.; Sidi-Yekhlef, Ahmed; Schwall, Robert E.; Driscoll, David I.; Shoykhet, Boris A.

    2002-01-01

    A system for cooling a superconductor device includes a cryocooler located in a stationary reference frame and a closed circulation system external to the cryocooler. The closed circulation system interfaces the stationary reference frame with a rotating reference frame in which the superconductor device is located. A method of cooling a superconductor device includes locating a cryocooler in a stationary reference frame, and transferring heat from a superconductor device located in a rotating reference frame to the cryocooler through a closed circulation system external to the cryocooler. The closed circulation system interfaces the stationary reference frame with the rotating reference frame.

  11. Alternative Room Cooling System

    Directory of Open Access Journals (Sweden)

    Md. Fazle Rabbi

    2015-06-01

    Full Text Available The rapidly growing population results in an increasing demand for much more residential and commercial buildings, which leads to vertical growth of the buildings and needs proper ventilation of those buildings. Natural air ventilation system is not sufficient for conventional building structures. Hence fans and air-conditioners are must to meet the requirement of proper ventilation as well as space conditioning. Globally building sector consumes largest energy in heating, cooling, ventilation and space conditioning. This load can be minimized by the application of solar chimney and modification in building structure for heating, cooling, ventilation and space conditioning. Passive solar cooling is a subject of interest to provide cooling by using the sun, a powerful energy source. This is done for ensuring human comfort in hot climates. ASHRAE (American Society of Heating, Refrigerating and Air Conditioning Engineers defines Comfort as ‘that state of mind which expresses satisfaction with the thermal environment.’ The present paper describes the development of a solar passive cooling system, which can provide thermal cooling throughout the summer season in hot and humid climates. The constructed passive system works on natural convection mode of air. Such system reduces the inside temperature of up to 5°C from the atmospheric temperature. Temperature can further be reduced by the judicious use of night ventilation.

  12. Foulant characteristics comparison in recycling cooling water system makeup by municipal reclaimed water and surface water in power plant.

    Science.gov (United States)

    Ping, Xu; Jing, Wang; Yajun, Zhang; Jie, Wang; Shuai, Si

    2015-01-01

    Due to water shortage, municipal reclaimed water rather than surface water was replenished into recycling cooling water system in power plants in some cities in China. In order to understand the effects of the measure on carbon steel corrosion, characteristics of two kinds of foulant produced in different systems were studied in the paper. Differences between municipal reclaimed water and surface water were analyzed firstly. Then, the weight and the morphology of two kinds of foulant were compared. Moreover, other characteristics including the total number of bacteria, sulfate reducing bacteria, iron bacteria, extracellular polymeric substance (EPS), protein (PN), and polysaccharide (PS) in foulant were analyzed. Based on results, it could be concluded that microbial and corrosive risk would be increased when the system replenished by municipal reclaimed water instead of surface water.

  13. Monitoring Cray Cooling Systems

    Energy Technology Data Exchange (ETDEWEB)

    Maxwell, Don E [ORNL; Ezell, Matthew A [ORNL; Becklehimer, Jeff [Cray, Inc.; Donovan, Matthew J [ORNL; Layton, Christopher C [ORNL

    2014-01-01

    While sites generally have systems in place to monitor the health of Cray computers themselves, often the cooling systems are ignored until a computer failure requires investigation into the source of the failure. The Liebert XDP units used to cool the Cray XE/XK models as well as the Cray proprietary cooling system used for the Cray XC30 models provide data useful for health monitoring. Unfortunately, this valuable information is often available only to custom solutions not accessible by a center-wide monitoring system or is simply ignored entirely. In this paper, methods and tools used to harvest the monitoring data available are discussed, and the implementation needed to integrate the data into a center-wide monitoring system at the Oak Ridge National Laboratory is provided.

  14. Waveguide cooling system

    Science.gov (United States)

    Chen, B. C. J.; Hartop, R. W.

    1981-04-01

    An improved system is described for cooling high power waveguides by the use of cooling ducts extending along the waveguide, which minimizes hot spots at the flanges where waveguide sections are connected together. The cooling duct extends along substantially the full length of the waveguide section, and each flange at the end of the section has a through hole with an inner end connected to the duct and an opposite end that can be aligned with a flange hole in another waveguide section. Earth flange is formed with a drainage groove in its face, between the through hole and the waveguide conduit to prevent leakage of cooling fluid into the waveguide. The ducts have narrowed sections immediately adjacent to the flanges to provide room for the installation of fasteners closely around the waveguide channel.

  15. Optimal Design of Cogeneration Systems in Industrial Plants Combined with District Heating/Cooling and Underground Thermal Energy Storage

    Directory of Open Access Journals (Sweden)

    Vincenzo Dovì

    2011-12-01

    Full Text Available Combined heat and power (CHP systems in both power stations and large plants are becoming one of the most important tools for reducing energy requirements and consequently the overall carbon footprint of fundamental industrial activities. While power stations employ topping cycles where the heat rejected from the cycle is supplied to domestic and industrial consumers, the plants that produce surplus heat can utilise bottoming cycles to generate electrical power. Traditionally the waste heat available at high temperatures was used to generate electrical power, whereas energy at lower temperatures was either released to the environment or used for commercial or domestic heating. However the introduction of new engines, such as the ones using the organic Rankine cycle, capable of employing condensing temperatures very close to the ambient temperature, has made the generation of electrical power at low temperatures also convenient. On the other hand, district heating is becoming more and more significant since it has been extended to include cooling in the warm months and underground storage of thermal energy to cope with variable demand. These developments imply that electric power generation and district heating/cooling may become alternative and not complementary solutions for waste energy of industrial plants. Therefore the overall energy management requires the introduction of an optimisation algorithm to select the best strategy. In this paper we propose an algorithm for the minimisation of a suitable cost function, for any given variable heat demand from commercial and domestic users, with respect to all independent variables, i.e., temperatures and flowrates of warm fluid streams leaving the plants and volume and nature of underground storage. The results of the preliminary process integration analysis based on pinch technology are used in this algorithm to provide bounds on the values of temperatures.

  16. Wet and dry cooling systems optimization applied to a modern waste-to-energy cogeneration heat and power plant

    Energy Technology Data Exchange (ETDEWEB)

    Barigozzi, G.; Perdichizzi, A.; Ravelli, S. [Department of Industrial Engineering, Bergamo University (Italy)

    2011-04-15

    In Brescia, Italy, heat is delivered to 70% of 200.000 city inhabitants by means of a district heating system, mainly supplied by a waste to energy plant, utilizing the non recyclable fraction of municipal and industrial solid waste (800,000 tons/year, otherwise landfilled), thus saving annually over 150,000 tons of oil equivalent and over 400,000 tons of CO{sub 2} emissions. This study shows how the performance of the waste-to-energy cogeneration plant can be improved by optimising the condensation system, with particular focus on the combination of wet and dry cooling systems. The analysis has been carried out using two subsequent steps: in the first one a schematic model of the steam cycle was accomplished in order to acquire a knowledge base about the variables that would be most influential on the performance. In the second step the electric power output for different operating conditions was predicted and optimized in a homemade program. In more details, a thermodynamic analysis of the steam cycle, according to the design operating condition, was performed by means of a commercial code (Thermoflex {sup copyright}) dedicated to power plant modelling. Then the off-design behaviour was investigated by varying not only the ambient conditions but also several parameters connected to the heat rejection rate, like the heat required from district heating and the auxiliaries load. Each of these parameters has been addressed and considered in determining the overall performance of the thermal cycle. After that, a complete prediction of the cycle behaviour was performed by simultaneously varying different operating conditions. Finally, a Matlab {sup copyright} computer code was developed in order to optimize the net electric power as a function of the way in which the condensation is operated. The result is an optimum set of variables allowing the wet and dry cooling system to be regulated in such a way that the maximum power is achieved. The best strategy consists in

  17. Safety assessment for electricity generation failure accident of gas cooled nuclear power plant using system dynamics (SD) method

    Energy Technology Data Exchange (ETDEWEB)

    Woo, Tae Ho [Seoul National Univ. (Korea, Republic of). Dept. of Nuclear Engineering

    2013-04-15

    The power production failure happens in the loss of coolant of the nuclear power plants (NPPs). The air ingress is a serious accident in gas cooled NPPs. The quantification of the study performed by the system dynamics (SD) method which is processed by the feedback algorithms. The Vensim software package is used for the simulation, which is performed by the Monte-Carlo method. Two kinds of considerations as the economic and safety properties are important in NPPs. The result shows the stability of the operation when the power can be decided. The maximum value of risk is the 11.77 in 43rd and the minimum value is 0.0 in several years. So, the success of the circulation of coolant is simulated by the dynamical values. (orig.)

  18. District heating and cooling systems for communities through power plant retrofit and distribution network, City of Piqua, Ohio

    Energy Technology Data Exchange (ETDEWEB)

    None

    1979-09-18

    The goal of the Piqua, Ohio District Heating and Cooling Demonstration Project is to demonstrate the feasibility and efficiency of using cogenerated thermal energy from the City's Municipal Power Plant to provide residential, commercial and industrial space heating and cooling and satisfy other community energy needs as appropriate. Progress in four tasks within this project is reported. These tasks include: development of team work plan resource allocation; identification of thermal energy source market; analysis of energy market; and planning of power plant retrofits. (LCL)

  19. ATLAS - Liquid Cooling Systems

    CERN Multimedia

    Bonneau, P.

    1998-01-01

    Photo 1 - Cooling Unit - Side View Photo 2 - Cooling Unit - Detail Manifolds Photo 3 - Cooling Unit - Rear View Photo 4 - Cooling Unit - Detail Pump, Heater and Exchanger Photo 5 - Cooling Unit - Detail Pump and Fridge Photo 6 - Cooling Unit - Front View

  20. Cooling Floor AC Systems

    Science.gov (United States)

    Jun, Lu; Hao, Ding; Hong, Zhang; Ce, Gao Dian

    The present HVAC equipments for the residential buildings in the Hot-summer-and-Cold-winter climate region are still at a high energy consuming level. So that the high efficiency HVAC system is an urgently need for achieving the preset government energy saving goal. With its advantage of highly sanitary, highly comfortable and uniform of temperature field, the hot-water resource floor radiation heating system has been widely accepted. This paper has put forward a new way in air-conditioning, which combines the fresh-air supply unit and such floor radiation system for the dehumidification and cooling in summer or heating in winter. By analyze its advantages and limitations, we found that this so called Cooling/ Heating Floor AC System can improve the IAQ of residential building while keep high efficiency quality. We also recommend a methodology for the HVAC system designing, which will ensure the reduction of energy cost of users.

  1. IMPROVEMENT OF SYSTEMS OF TECHNICAL WATER SUPPLY WITH COOLING TOWERS FOR STEAM POWER PLANTS TECHNICAL AND ECONOMIC INDICATORS PERFECTION. Part 1

    Directory of Open Access Journals (Sweden)

    Yu. A. Zenovich-Leshkevich-Olpinskiy

    2016-01-01

    Full Text Available In order to reduce the temperature of cooling water and increase the efficiency of use of power resources the main directions of modernization of systems of technical water supply with cooling towers at steam power plants are presented. The problems of operation of irrigation systems and water distribution systems of cooling towers are reviewed. The design of heat and mass transfer devices, their shortcomings and the impact on the cooling ability of the cooling tower are also under analysis. The use of droplet heat and mass transfer device based on the lattice polypropylene virtually eliminates the shortcomings of the film and droplet-film heat and mass transfer devices of the cooling tower, increasing lifetime, and improving the reliability and efficiency of the operation of the main equipment of thermal power plants. The design of the water distribution devices of cooling towers is also considered. It is noted that the most effective are water-spattering low-pressure nozzles made of polypropylene that provides uniform dispersion of water and are of a high reliability and durability.

  2. Combined thermal storage pond and dry cooling tower waste heat rejection system for solar-thermal steam-electric power plants. Final report

    Energy Technology Data Exchange (ETDEWEB)

    Guyer, E.C.; Bourne, J.G.; Brownell, D.L.; Rose, R.M.

    1979-02-28

    The thermal performance and economics of the combined thermal storage pond and dry cooling tower waste heat rejection system concept for solar-thermal steam-electric plants have been evaluated. Based on the computer simulation of the operation of southwest-sited solar-thermal plants, it has been determined that the combined pond-tower concept has significant cost and performance advantages over conventional dry cooling systems. Use of a thermal storage pond as a component of the dry cooling system allows a significant reduction in the required dry cooling heat exchange capacity and the associated parasitic power consumption. Importantly, it has been concluded that the combined pond-tower dry cooling system concept can be employed to economically maintain steam condensing temperatures at levels normally achieved with conventional evaporative cooling systems. An evaluation of alternative thermal storage pond design concepts has revealed that a stratified vertical-flow cut-and-fill reservoir with conventional membrane lining and covering would yield the best overall system performance at the least cost.

  3. District heating and cooling systems for communities through power plant retrofit distribution network. Final report, September 1, 1978-May 31, 1979

    Energy Technology Data Exchange (ETDEWEB)

    None

    1979-10-01

    This volume presents information on the institutional factors, i.e., legal and regulatory aspects, a preliminary economic analysis, and a proposal for future studies on retrofitting existing thermal power plants so that they can supply heat for district heating and cooling systems for communities. (LCL)

  4. District heating and cooling systems for communities through power-plant retrofit and distribution network. Volume 2. Tasks 1-3. Final report. [Downtown Toledo steam system

    Energy Technology Data Exchange (ETDEWEB)

    Watt, J.R.; Sommerfield, G.A.

    1979-08-01

    Each of the tasks is described separately: Task 1 - Demonstration Team; Task 2 - Identify Thermal Energy Source(s) and Potential Service Area(s); and Task 3 - Energy Market Analysis. The purpose of the project is to establish and implement measures in the downtown Toledo steam system for conserving scarce fuel supplies through cogeneration, by retrofit of existing base- or intermediate-loaded electric-generating plants to provide for central heating and cooling systems, with the ultimate purpose of applying the results to other communities. For Task 1, Toledo Edison Company has organized a Demonstration Team (Battelle Columbus Laboratories; Stone and Webster; Ohio Dept. of Energy; Public Utilities Commission of Ohio; Toledo Metropolitan Area Council of Governments; and Toledo Edison) that it hopes has the expertise to evaluate the technical, legal, economic, and marketing issues related to the utilization of by-product heat from power generation to supply district heating and cooling services. Task 2 gives a complete technical description of the candidate plant(s), its thermodynamic cycle, role in load dispatch, ownership, and location. It is concluded that the Toledo steam distribution system can be the starting point for developing a new district-heating system to serve an expanding market. Battelle is a member of the team employed as a subcontractor to complete the energy market analysis. The work is summarized in Task 3. (MCW)

  5. Hybrid radiator cooling system

    Science.gov (United States)

    France, David M.; Smith, David S.; Yu, Wenhua; Routbort, Jules L.

    2016-03-15

    A method and hybrid radiator-cooling apparatus for implementing enhanced radiator-cooling are provided. The hybrid radiator-cooling apparatus includes an air-side finned surface for air cooling; an elongated vertically extending surface extending outwardly from the air-side finned surface on a downstream air-side of the hybrid radiator; and a water supply for selectively providing evaporative cooling with water flow by gravity on the elongated vertically extending surface.

  6. Model development and validation of a solar cooling plant

    Energy Technology Data Exchange (ETDEWEB)

    Zambrano, Darine; Garcia-Gabin, Winston [Escuela de Ingenieria Electrica, Facultad de Ingenieria, Universidad de Los Andes, La Hechicera, Merida 5101 (Venezuela); Bordons, Carlos; Camacho, Eduardo F. [Departamento de Ingenieria de Sistemas y Automatica, Escuela Superior de Ingenieros, Universidad de Sevilla, Camino de Los Descubrimientos s/n, Sevilla 41092 (Spain)

    2008-03-15

    This paper describes the dynamic model of a solar cooling plant that has been built for demonstration purposes using market-available technology and has been successfully operational since 2001. The plant uses hot water coming from a field of solar flat collectors which feed a single-effect absorption chiller of 35 kW nominal cooling capacity. The work includes model development based on first principles and model validation with a set of experiments carried out on the real plant. The simulation model has been done in a modular way, and can be adapted to other solar cooling-plants since the main modules (solar field, absorption machine, accumulators and auxiliary heater) can be easily replaced. This simulator is a powerful tool for solar cooling systems both during the design phase, when it can be used for component selection, and also for the development and testing of control strategies. (author)

  7. Steam-Electric Power-Plant-Cooling Handbook

    Energy Technology Data Exchange (ETDEWEB)

    Sonnichsen, J.C.; Carlson, H.A.; Charles, P.D.; Jacobson, L.D.; Tadlock, L.A.

    1982-02-01

    The Steam-Electric Power Plant Cooling Handbook provides summary data on steam-electric power plant capacity, generation and number of plants for each cooling means, by Electric Regions, Water Resource Regions and National Electric Reliability Council Areas. Water consumption by once-through cooling, cooling ponds and wet evaporative towers is discussed and a methodology for computation of water consumption is provided for a typical steam-electric plant which uses a wet evaporative tower or cooling pond for cooling.

  8. Coexistence of Legionella pneumophila Bacteria and Free-Living Amoebae in Lakes Serving as a Cooling System of a Power Plant.

    Science.gov (United States)

    Zbikowska, Elżbieta; Kletkiewicz, Hanna; Walczak, Maciej; Burkowska, Aleksandra

    2014-01-01

    The study was aimed at determining whether potentially pathogenic free-living amoebae (FLA) and Legionella pneumophila can be found in lakes serving as a natural cooling system of a power plant. Water samples were collected from five lakes forming the cooling system of the power plants Pątnów and Konin (Poland). The numbers of investigated organisms were determined with the use of a very sensitive molecular method-fluorescence in situ hybridization (FISH). The result of the present study shows that thermally altered aquatic environments provide perfect conditions for the growth of L. pneumophila and amoebae. The bacteria were identified in the biofilm throughout the entire research period and in the subsurface water layer in July and August. Hartmanella sp. and/or Naegleria fowleri were identified in the biofilm throughout the entire research period.

  9. Hybrid Cooling for Geothermal Power Plants: Final ARRA Project Report

    Energy Technology Data Exchange (ETDEWEB)

    Bharathan, D.

    2013-06-01

    Many binary-cycle geothermal plants use air as the heat rejection medium. Usually this is accomplished by using an air-cooled condenser (ACC) system to condense the vapor of the working fluid in the cycle. Many air-cooled plants suffer a loss of production capacity of up to 50% during times of high ambient temperatures. Use of limited amounts of water to supplement the performance of ACCs is investigated. Deluge cooling is found to be one of the least-cost options. Limiting the use of water in such an application to less than one thousand operating hours per year can boost plant output during critical high-demand periods while minimizing water use in binary-cycle geothermal power plants.

  10. Process integration: Cooling water systems design

    CSIR Research Space (South Africa)

    Gololo, KV

    2010-10-01

    Full Text Available This paper presents a technique for grassroot design of cooling water system for wastewater minimization which incorporates the performances of the cooling towers involved. The study focuses mainly on cooling systems consisting of multiple cooling...

  11. Radiative cooling for thermophotovoltaic systems

    Science.gov (United States)

    Zhou, Zhiguang; Sun, Xingshu; Bermel, Peter

    2016-09-01

    Radiative cooling has recently garnered a great deal of attention for its potential as an alternative method for photovoltaic thermal management. Here, we will consider the limits of radiative cooling for thermal management of electronics broadly, as well as a specific application to thermal power generation. We show that radiative cooling power can increase rapidly with temperature, and is particularly beneficial in systems lacking standard convective cooling. This finding indicates that systems previously operating at elevated temperatures (e.g., 80°C) can be passively cooled close to ambient under appropriate conditions with a reasonable cooling area. To examine these general principles for a previously unexplored application, we consider the problem of thermophotovoltaic (TPV) conversion of heat to electricity via thermal radiation illuminating a photovoltaic diode. Since TPV systems generally operate in vacuum, convective cooling is sharply limited, but radiative cooling can be implemented with proper choice of materials and structures. In this work, realistic simulations of system performance are performed using the rigorous coupled wave analysis (RCWA) techniques to capture thermal emitter radiation, PV diode absorption, and radiative cooling. We subsequently optimize the structural geometry within realistic design constraints to find the best configurations to minimize operating temperature. It is found that low-iron soda-lime glass can potentially cool the PV diode by a substantial amount, even to below ambient temperatures. The cooling effect can be further improved by adding 2D-periodic photonic crystal structures. We find that the improvement of efficiency can be as much as an 18% relative increase, relative to the non-radiatively cooled baseline, as well as a potentially significant improvement in PV diode lifetime.

  12. 46 CFR 153.432 - Cooling systems.

    Science.gov (United States)

    2010-10-01

    ... 46 Shipping 5 2010-10-01 2010-10-01 false Cooling systems. 153.432 Section 153.432 Shipping COAST... Control Systems § 153.432 Cooling systems. (a) Each cargo cooling system must have an equivalent standby... cooling system. (b) Each tankship that has a cargo tank with a required cooling system must have a manual...

  13. Cooling water systems design using process integration

    CSIR Research Space (South Africa)

    Gololo, KV

    2010-09-01

    Full Text Available Cooling water systems are generally designed with a set of heat exchangers arranged in parallel. This arrangement results in higher cooling water flowrate and low cooling water return temperature thus reducing cooling tower efficiency. Previous...

  14. Temperature initiated passive cooling system

    Science.gov (United States)

    Forsberg, Charles W.

    1994-01-01

    A passive cooling system for cooling an enclosure only when the enclosure temperature exceeds a maximum standby temperature comprises a passive heat transfer loop containing heat transfer fluid having a particular thermodynamic critical point temperature just above the maximum standby temperature. An upper portion of the heat transfer loop is insulated to prevent two phase operation below the maximum standby temperature.

  15. Industry Application ECCS / LOCA Integrated Cladding/Emergency Core Cooling System Performance: Demonstration of LOTUS-Baseline Coupled Analysis of the South Texas Plant Model

    Energy Technology Data Exchange (ETDEWEB)

    Zhang, Hongbin [Idaho National Lab. (INL), Idaho Falls, ID (United States); Szilard, Ronaldo [Idaho National Lab. (INL), Idaho Falls, ID (United States); Epiney, Aaron [Idaho National Lab. (INL), Idaho Falls, ID (United States); Parisi, Carlo [Idaho National Lab. (INL), Idaho Falls, ID (United States); Vaghetto, Rodolfo [Texas A & M Univ., College Station, TX (United States); Vanni, Alessandro [Texas A & M Univ., College Station, TX (United States); Neptune, Kaleb [Texas A & M Univ., College Station, TX (United States)

    2017-06-01

    Under the auspices of the DOE LWRS Program RISMC Industry Application ECCS/LOCA, INL has engaged staff from both South Texas Project (STP) and the Texas A&M University (TAMU) to produce a generic pressurized water reactor (PWR) model including reactor core, clad/fuel design and systems thermal hydraulics based on the South Texas Project (STP) nuclear power plant, a 4-Loop Westinghouse PWR. A RISMC toolkit, named LOCA Toolkit for the U.S. (LOTUS), has been developed for use in this generic PWR plant model to assess safety margins for the proposed NRC 10 CFR 50.46c rule, Emergency Core Cooling System (ECCS) performance during LOCA. This demonstration includes coupled analysis of core design, fuel design, thermalhydraulics and systems analysis, using advanced risk analysis tools and methods to investigate a wide range of results. Within this context, a multi-physics best estimate plus uncertainty (MPBEPU) methodology framework is proposed.

  16. Turbine Blade Cooling System Optimization

    OpenAIRE

    GIRARDEAU, Julian; PAILHES, Jérôme; SEBASTIAN, Patrick; PARDO, Frédéric; Nadeau, Jean-Pierre

    2013-01-01

    The authors wish to thank turbine designers from TURBOMECA SAFRAN Group.; International audience; Designing high performance cooling systems suitable for preserving the service lifetime of nozzle guide vanes of turboshaft engines leads to significant aerodynamic losses. These losses jeopardize the performance of the whole engine. In the same time, a low efficiency cooling system may affect the costs of maintenance repair and overhaul of the engine as component life decreases. Consequently, de...

  17. Cryogenic cooling system for HTS cable

    Energy Technology Data Exchange (ETDEWEB)

    Yoshida, Shigeru [Taiyo Nippon Sanso, Tsukuba (Japan)

    2017-06-15

    Recently, Research and development activity of HTS (High Temperature Superconducting) power application is very progressive worldwide. Especially, HTS cable system and HTSFCL (HTS Fault current limiter) system are proceeding to practical stages. In such system and equipment, cryogenic cooling system, which makes HTS equipment cooled lower than critical temperature, is one of crucial components. In this article, cryogenic cooling system for HTS application, mainly cable, is reviewed. Cryogenic cooling system can be categorized into conduction cooling system and immersion cooling system. In practical HTS power application area, immersion cooling system with sub-cooled liquid nitrogen is preferred. The immersion cooling system is besides grouped into open cycle system and closed cycle system. Turbo-Brayton refrigerator is a key component for closed cycle system. Those two cooling systems are focused in this article. And, each design and component of the cooling system is explained.

  18. A Process for Evaluating Adverse Environmental Impacts by Cooling-Water System Entrainment at a California Power Plant

    Directory of Open Access Journals (Sweden)

    C.P. Ehrler

    2002-01-01

    Full Text Available A study to determine the effects of entrainment by the Diablo Canyon Power Plant (DCPP was conducted between 1996 and 1999 as required under Section 316(b of the Clean Water Act. The goal of this study was to present the U.S. Environmental Protection Agency (EPA and Central Coast Regional Water Quality Control Board (CCRWQCB with results that could be used to determine if any adverse environmental impacts (AEIs were caused by the operation of the plant’s cooling-water intake structure (CWIS. To this end we chose, under guidance of the CCRWQCB and their entrainment technical working group, a unique approach combining three different models for estimating power plant effects: fecundity hindcasting (FH, adult equivalent loss (AEL, and the empirical transport model (ETM. Comparisons of the results from these three approaches provided us a relative measure of confidence in our estimates of effects. A total of 14 target larval fish taxa were assessed as part of the DCPP 316(b. Example results are presented here for the kelp, gopher, and black-and-yellow (KGB rockfish complex and clinid kelpfish. Estimates of larval entrainment losses for KGB rockfish were in close agreement (FH is approximately equals to 550 adult females per year, AEL is approximately equals to 1,000 adults [male and female] per year, and ETM = larval mortality as high as 5% which could be interpreted as ca. 2,600 1 kg adult fish. The similar results from the three models provided confidence in the estimated effects for this group. Due to lack of life history information needed to parameterize the FH and AEL models, effects on clinid kelpfish could only be assessed using the ETM model. Results from this model plus ancillary information about local populations of adult kelpfish suggest that the CWIS might be causing an AEI in the vicinity of DCPP.

  19. Proposal of cooling plant, for SPIDER and MITICA experiments

    Energy Technology Data Exchange (ETDEWEB)

    Fellin, F., E-mail: francesco.fellin@igi.cnr.it [Consorzio RFX, Associazione EURATOM-ENEA sulla Fusione, Corso Stati Uniti 4, I-35127 Padova (Italy); Marcuzzi, D.; Zaccaria, P. [Consorzio RFX, Associazione EURATOM-ENEA sulla Fusione, Corso Stati Uniti 4, I-35127 Padova (Italy); Agarici, G. [Fusion for Energy, ITER Department, Heating and CD, Josep Pla, 2 Torres Diagonal Litoral B3 E- 08019, Barcelona (Spain)

    2011-10-15

    This paper presents a proposal of Cooling Plant for two new Neutral Beam experiments called MITICA and SPIDER to be realized in Padova (Italy). A large amount of Power (up to 70 MW) has to be removed from in-vessel components and auxiliary systems belonging to these two experiments. Different experimental scenarios (pulse duration ranging from few seconds up to 3600 s), requirements for operating temperature, coolant quality and voltage holding are taken into account in this conceptual design proposal. To reduce the radiological risks due to possible presence of activated corrosion products (ACP) in some water cooled components suitable design choices have been analysed. This work was carried out by considering carefully a lot of different aspects like operability, standardization of components, maintenance and repair, optimization of the installed power and the overall costs of the plant. Experiment components with similar requirements are grouped in the same primary circuits where fine temperature regulation, water quality monitoring and calorimetric measurements are the main characteristics. Each primary circuit (PC) is connected to secondary circuits which allow thermal dissipation and, in some cases, also component preheating. Secondary circuits are connected to two large basins the water of which is cooled down by active cooling rejection system such as cooling towers and air coolers. In this way the requirement for impulsive heat dissipation is fulfilled by the water basins allowing to install a less powerful active rejection system and so reducing the total costs. A large effort was done to guarantee good plant integration with the Experiment Main Hall (in which MITICA and SPIDER are located) and other technical supplies, buildings and areas. Other special requirements for stand-alone systems like Draining and Drying System, Pressure Test System and Chemical Control System are also part of this work.

  20. Helium-cooling in fusion power plants

    Energy Technology Data Exchange (ETDEWEB)

    Wong, C.P.C.; Baxi, C.B.; Hamilton, C.J.; Schleicher, R.W.; Streckert, H.

    1994-11-01

    This paper reviews different helium-cooled first wall and blanket designs; and compares the selection of structural materials. The authors found that the solid breeder, SiC-composite material option generates the lowest amount of induced radioactivity and afterheat and has the highest temperature capability. When combined with the direct cycle gas turbine system, it has the potential to be the most economical fusion system and can compete with advanced fission reactors. When compared to martensitic steel and V-alloy, SiC-composite is the least developed of these three structural materials, a focused development effort will be needed. Fundamental research has begun in addressing the issues of optimized composite materials, irradiation effects, leak tightness and low activation braze materials. Development of helium-cooled high heat flux components and further development of the direct cycle gas turbine system will also be needed.

  1. Solar-powered cooling system

    Energy Technology Data Exchange (ETDEWEB)

    Farmer, Joseph C

    2013-12-24

    A solar-powered adsorption-desorption refrigeration and air conditioning system uses nanostructural materials made of high specific surface area adsorption aerogel as the adsorptive media. Refrigerant molecules are adsorbed on the high surface area of the nanostructural material. A circulation system circulates refrigerant from the nanostructural material to a cooling unit.

  2. Compressor bleed cooling fluid feed system

    Science.gov (United States)

    Donahoo, Eric E; Ross, Christopher W

    2014-11-25

    A compressor bleed cooling fluid feed system for a turbine engine for directing cooling fluids from a compressor to a turbine airfoil cooling system to supply cooling fluids to one or more airfoils of a rotor assembly is disclosed. The compressor bleed cooling fluid feed system may enable cooling fluids to be exhausted from a compressor exhaust plenum through a downstream compressor bleed collection chamber and into the turbine airfoil cooling system. As such, the suction created in the compressor exhaust plenum mitigates boundary layer growth along the inner surface while providing flow of cooling fluids to the turbine airfoils.

  3. Strandby Harbour on solar cooling. Demonstration of 8.000 m{sup 2} solar collectors combined with flue gas cooling with a absorption cooling system; Combined heat and power plant (CHP); Strandby havn paa solkoeling. Demonstration af 8.000 m{sup 2} solfangere kombineret med roeggaskoeling med absorptionskoeleanlaeg

    Energy Technology Data Exchange (ETDEWEB)

    Soerensen, Flemming (Strandby Varmevaerk, Strandby (Denmark)); Soerensen, Per Alex (PlanEnergi, Skoerping (Denmark)); Ulbjerg, F. (Ramboell, Odense (Denmark)); Sloth, H. (Houe and Olsen, Thisted (Denmark))

    2010-04-15

    The aim of the project was to demonstrate 1) high solar heating ratio (18% annually) at a decentralized natural gas combined heat and power plant; 2) increased efficiency (5% of the heat consumption) in a natural gas CHP by using an extra flue gas cooler and an absorption heat pump; 3) a double tank system where a new tank during winter is used for cooling/ heat storage for the absorption heat pump and during summer for solar heat storage in serial operation with the old tank. The concept of combining solar power, absorption cooling and natural gas-fired small-scale CHP in Strandby met expectations and could be replicated in other CHP plants. However, it is important to note that if major construction modifications in the flue gas condensation system in the boiler or engine are required, the operating hours must not be reduced significantly in the amortisation period for the conversion. (ln)

  4. Performance Evaluation of the Concept of Hybrid Heat Pipe as Passive In-core Cooling Systems for Advanced Nuclear Power Plant

    Energy Technology Data Exchange (ETDEWEB)

    Jeong, Yeong Shin; Kim, Kyung Mo; Kim, In Guk; Bang, In Cheol [UNIST, Ulsan (Korea, Republic of)

    2015-05-15

    As an arising issue for inherent safety of nuclear power plant, the concept of hybrid heat pipe as passive in-core cooling systems was introduced. Hybrid heat pipe has unique features that it is inserted in core directly to remove decay heat from nuclear fuel without any changes of structures of existing facilities of nuclear power plant, substituting conventional control rod. Hybrid heat pipe consists of metal cladding, working fluid, wick structure, and neutron absorber. Same with working principle of the heat pipe, heat is transported by phase change of working fluid inside metal cask. Figure 1 shows the systematic design of the hybrid heat pipe cooling system. In this study, the concept of a hybrid heat pipe was introduced as a Passive IN-core Cooling Systems (PINCs) and demonstrated for internal design features of heat pipe containing neutron absorber. Using a commercial CFD code, single hybrid heat pipe model was analyzed to evaluate thermal performance in designated operating condition. Also, 1-dimensional reactor transient analysis was done by calculating temperature change of the coolant inside reactor pressure vessel using MATLAB. As a passive decay heat removal device, hybrid heat pipe was suggested with a concept of combination of heat pipe and control rod. Hybrid heat pipe has distinct feature that it can be a unique solution to cool the reactor when depressurization process is impossible so that refueling water cannot be injected into RPV by conventional ECCS. It contains neutron absorber material inside heat pipe, so it can stop the reactor and at the same time, remove decay heat in core. For evaluating the concept of hybrid heat pipe, its thermal performance was analyzed using CFD and one-dimensional transient analysis. From single hybrid heat pipe simulation, the hybrid heat pipe can transport heat from the core inside to outside about 18.20 kW, and total thermal resistance of hybrid heat pipe is 0.015 .deg. C/W. Due to unique features of long heat

  5. Cooling system for electronic components

    Energy Technology Data Exchange (ETDEWEB)

    Anderl, William James; Colgan, Evan George; Gerken, James Dorance; Marroquin, Christopher Michael; Tian, Shurong

    2016-05-17

    Embodiments of the present invention provide for non interruptive fluid cooling of an electronic enclosure. One or more electronic component packages may be removable from a circuit card having a fluid flow system. When installed, the electronic component packages are coincident to and in a thermal relationship with the fluid flow system. If a particular electronic component package becomes non-functional, it may be removed from the electronic enclosure without affecting either the fluid flow system or other neighboring electronic component packages.

  6. Cooling system for electronic components

    Energy Technology Data Exchange (ETDEWEB)

    Anderl, William James; Colgan, Evan George; Gerken, James Dorance; Marroquin, Christopher Michael; Tian, Shurong

    2015-12-15

    Embodiments of the present invention provide for non interruptive fluid cooling of an electronic enclosure. One or more electronic component packages may be removable from a circuit card having a fluid flow system. When installed, the electronic component packages are coincident to and in a thermal relationship with the fluid flow system. If a particular electronic component package becomes non-functional, it may be removed from the electronic enclosure without affecting either the fluid flow system or other neighboring electronic component packages.

  7. System for cooling a cabinet

    DEFF Research Database (Denmark)

    2015-01-01

    The present disclosure relates to a cooling system comprising an active magnetic regenerator having a cold side and a hot side, a hot side heat exchanger connected to the hot side of the magnetic regenerator, one or more cold side heat exchangers, and a cold store reservoir comprising a volume...

  8. Solar Cooling System Using Solar-Driven Hybrid Chiller

    OpenAIRE

    Hirai, Akira

    2012-01-01

    We developed an appropriate Absorption chiller to "Solar cooling system" in 2010. In addition, we added the improvement to the machine. "Solar cooling system" can be easily constructed with the machine. and, we constructed the demonstration plant, and verified the utility

  9. District heating and cooling systems for communities through power plant retrofit and distribution network, city of Piqua, Ohio

    Energy Technology Data Exchange (ETDEWEB)

    None

    1979-01-01

    The feasibility analysis and evaluation of the Piqua, Ohio District Heating and Cooling Demonstration program is being conducted by the Piqua Municipal Power Co., the Piqua Law Dept., the Public Works Dept., a firm of economic analysts, and the Georgia Tech Engineering Dept. This volume contains information on the organization and composition of the demonstration team; characterization of the Piqua community; and the technical, environmental, institutional; financial, and economic assessments of the project. (LCL)

  10. RAMI analysis for DEMO HCPB blanket concept cooling system

    Energy Technology Data Exchange (ETDEWEB)

    Dongiovanni, Danilo N., E-mail: danilo.dongiovanni@enea.it [ENEA, Unità Tecnica Fusione, ENEA C. R. Frascati (Italy); Pinna, Tonio [ENEA, Unità Tecnica Fusione, ENEA C. R. Frascati (Italy); Carloni, Dario [KIT, Institute of Neutron Physics and Reactor Technology (INR) – KIT (Germany)

    2015-10-15

    Highlights: • RAMI (reliability, availability, maintainability and inspectability) preliminary assessment for HCPB blanket concept cooling system. • Reliability block diagram (RBD) modeling and analysis for HCPB primary heat transfer system (PHTS), coolant purification system (CPS), pressure control system (PCS), and secondary cooling system. • Sensitivity analysis on system availability performance. • Failure models and repair models estimated on the base of data from the ENEA fusion component failure rate database (FCFRDB). - Abstract: A preliminary RAMI (reliability, availability, maintainability and inspectability) assessment for the HCPB (helium cooled pebble bed) blanket cooling system based on currently available design for DEMO fusion power plant is presented. The following sub-systems were considered in the analysis: blanket modules, primary cooling loop including pipework and steam generators lines, pressure control system (PCS), coolant purification system (CPS) and secondary cooling system. For PCS and CPS systems an extrapolation from ITER Test Blanket Module corresponding systems was used as reference design in the analysis. Helium cooled pebble bed (HCPB) system reliability block diagrams (RBD) models were implemented taking into account: system reliability-wise configuration, operating schedule currently foreseen for DEMO, maintenance schedule and plant evolution schedule as well as failure and corrective maintenance models. A simulation of plant activity was then performed on implemented RBDs to estimate plant availability performance on a mission time of 30 calendar years. The resulting availability performance was finally compared to availability goals previously proposed for DEMO plant by a panel of experts. The study suggests that inherent availability goals proposed for DEMO PHTS system and Tokamak auxiliaries are potentially achievable for the primary loop of the HCPB concept cooling system, but not for the secondary loop. A

  11. Use of Treated Municipal Wastewater as Power Plant Cooling System Makeup Water: Tertiary Treatment versus Expanded Chemical Regimen for Recirculating Water Quality Management

    Energy Technology Data Exchange (ETDEWEB)

    David Dzombak; Radisav Vidic; Amy Landis

    2012-06-30

    Treated municipal wastewater is a common, widely available alternative source of cooling water for thermoelectric power plants across the U.S. However, the biodegradable organic matter, ammonia-nitrogen, carbonate and phosphates in the treated wastewater pose challenges with respect to enhanced biofouling, corrosion, and scaling, respectively. The overall objective of this study was to evaluate the benefits and life cycle costs of implementing tertiary treatment of secondary treated municipal wastewater prior to use in recirculating cooling systems. The study comprised bench- and pilot-scale experimental studies with three different tertiary treated municipal wastewaters, and life cycle costing and environmental analyses of various tertiary treatment schemes. Sustainability factors and metrics for reuse of treated wastewater in power plant cooling systems were also evaluated. The three tertiary treated wastewaters studied were: secondary treated municipal wastewater subjected to acid addition for pH control (MWW_pH); secondary treated municipal wastewater subjected to nitrification and sand filtration (MWW_NF); and secondary treated municipal wastewater subjected nitrification, sand filtration, and GAC adsorption (MWW_NFG). Tertiary treatment was determined to be essential to achieve appropriate corrosion, scaling, and biofouling control for use of secondary treated municipal wastewater in power plant cooling systems. The ability to control scaling, in particular, was found to be significantly enhanced with tertiary treated wastewater compared to secondary treated wastewater. MWW_pH treated water (adjustment to pH 7.8) was effective in reducing scale formation, but increased corrosion and the amount of biocide required to achieve appropriate biofouling control. Corrosion could be adequately controlled with tolytriazole addition (4-5 ppm TTA), however, which was the case for all of the tertiary treated waters. For MWW_NF treated water, the removal of ammonia by

  12. Use of Treated Municipal Wastewater as Power Plant Cooling System Makeup Water: Tertiary Treatment versus Expanded Chemical Regimen for Recirculating Water Quality Management

    Energy Technology Data Exchange (ETDEWEB)

    David Dzombak; Radisav Vidic; Amy Landis

    2012-06-30

    Treated municipal wastewater is a common, widely available alternative source of cooling water for thermoelectric power plants across the U.S. However, the biodegradable organic matter, ammonia-nitrogen, carbonate and phosphates in the treated wastewater pose challenges with respect to enhanced biofouling, corrosion, and scaling, respectively. The overall objective of this study was to evaluate the benefits and life cycle costs of implementing tertiary treatment of secondary treated municipal wastewater prior to use in recirculating cooling systems. The study comprised bench- and pilot-scale experimental studies with three different tertiary treated municipal wastewaters, and life cycle costing and environmental analyses of various tertiary treatment schemes. Sustainability factors and metrics for reuse of treated wastewater in power plant cooling systems were also evaluated. The three tertiary treated wastewaters studied were: secondary treated municipal wastewater subjected to acid addition for pH control (MWW_pH); secondary treated municipal wastewater subjected to nitrification and sand filtration (MWW_NF); and secondary treated municipal wastewater subjected nitrification, sand filtration, and GAC adsorption (MWW_NFG). Tertiary treatment was determined to be essential to achieve appropriate corrosion, scaling, and biofouling control for use of secondary treated municipal wastewater in power plant cooling systems. The ability to control scaling, in particular, was found to be significantly enhanced with tertiary treated wastewater compared to secondary treated wastewater. MWW_pH treated water (adjustment to pH 7.8) was effective in reducing scale formation, but increased corrosion and the amount of biocide required to achieve appropriate biofouling control. Corrosion could be adequately controlled with tolytriazole addition (4-5 ppm TTA), however, which was the case for all of the tertiary treated waters. For MWW_NF treated water, the removal of ammonia by

  13. Information technology equipment cooling system

    Science.gov (United States)

    Schultz, Mark D.

    2014-06-10

    According to one embodiment, a system for removing heat from a rack of information technology equipment may include a sidecar indoor air to liquid heat exchanger that cools warm air generated by the rack of information technology equipment. The system may also include a liquid to liquid heat exchanger and an outdoor heat exchanger. The system may further include configurable pathways to connect and control fluid flow through the sidecar heat exchanger, the liquid to liquid heat exchanger, the rack of information technology equipment, and the outdoor heat exchanger based upon ambient temperature and/or ambient humidity to remove heat from the rack of information technology equipment.

  14. District heating and cooling systems for communities through power plant retrofit and distribution networks. Phase 1: identificaion and assessment. Final report

    Energy Technology Data Exchange (ETDEWEB)

    1979-09-01

    Appendix A, Utility Plant Characteristics, contains information describing the characteristics of seven utility plants that were considered during the final site selection process. The plants are: Valley Electric Generating Plant, downtown Milwaukee; Manitowoc Electric Generating Plant, downtown Manitowoc; Blount Street Electric Generating Plant, downtown Madison; Pulliam Electric Generating Plant, downtown Green Bay; Edgewater Electric Generating Plant, downtown Sheboygan; Rock River Electric Generating Plant, near Janesville and Beloit; and Black Hawk Electric Generating Plant, downtown Beloit. Additional appendices are: Future Loads; hvac Inventory; Load Calculations; Factors to Induce Potential Users; Turbine Retrofit/Distribution System Data; and Detailed Economic Analysis Results/Data.

  15. Startup of Pumping Units in Process Water Supplies with Cooling Towers at Thermal and Nuclear Power Plants

    Energy Technology Data Exchange (ETDEWEB)

    Berlin, V. V., E-mail: vberlin@rinet.ru; Murav’ev, O. A., E-mail: muraviov1954@mail.ru; Golubev, A. V., E-mail: electronik@inbox.ru [National Research University “Moscow State University of Civil Engineering,” (Russian Federation)

    2017-03-15

    Aspects of the startup of pumping units in the cooling and process water supply systems for thermal and nuclear power plants with cooling towers, the startup stages, and the limits imposed on the extreme parameters during transients are discussed.

  16. District heating and cooling system for communities through power plant retrofit and distribution network. Final report, Phase I

    Energy Technology Data Exchange (ETDEWEB)

    1979-06-01

    The technical and economic feasibility of retrofitting thermal power plants in Minnesota to accommodate both heat and power generation for district heating was examined and is discussed. Three communities were identified as viable sites for co-generation district heating. (LCL)

  17. Use of Cooling Thermal Storage as a Heat Sink for Steam Power Plant

    Science.gov (United States)

    Hegazy, Ahmed Sabry

    In the present paper, a system is proposed for improving the performance of steam power plant with air-cooled condenser during peak loads. In this system, the power plant comprises two steam turbines, and the air-cooled condenser is replaced by two condensers. The first one is air-cooled (dry) and used for condensing the exhaust steam of the first turbine, while the second is water-cooled and serves to condense the steam outlet of the second turbine. The warm cooling water exiting the wet condenser is pumped to a cooling storage container, where it is cooled and re-circulated to the wet condenser. Cooling is produced by a refrigeration machine driven by the extra electric power generated by the two turbines during the time of the off-peak-loads (low electricity rates). Simple energy analyses have been developed to predict the energy characteristics of this system. The results of this paper showed that the proposed system leads to improving the plant power output at peak-loads. About 6, 16, 24 and 33% increase in generated plant power can be achieved at peak-loads (high electricity rates) when the ambient temperature is 20, 30, 40 and 50°C respectively, and the whole steam exiting both turbines is cooled in a wet condenser to a design temperature of 20°C. The results showed also that choice of the capacity of each turbine is essentially affected by the quality of the refrigeration machine and ambient temperature.

  18. Turbine airfoil with ambient cooling system

    Science.gov (United States)

    Campbell, Jr, Christian X.; Marra, John J.; Marsh, Jan H.

    2016-06-07

    A turbine airfoil usable in a turbine engine and having at least one ambient air cooling system is disclosed. At least a portion of the cooling system may include one or more cooling channels configured to receive ambient air at about atmospheric pressure. The ambient air cooling system may have a tip static pressure to ambient pressure ratio of at least 0.5, and in at least one embodiment, may include a tip static pressure to ambient pressure ratio of between about 0.5 and about 3.0. The cooling system may also be configured such that an under root slot chamber in the root is large to minimize supply air velocity. One or more cooling channels of the ambient air cooling system may terminate at an outlet at the tip such that the outlet is aligned with inner surfaces forming the at least one cooling channel in the airfoil to facilitate high mass flow.

  19. District heating and cooling systems for communities through power plant retrofit distribution network. Volume 3. Final report, September 1, 1978-May 31, 1979

    Energy Technology Data Exchange (ETDEWEB)

    None

    1979-10-01

    This final report of Phase I of the study presents Task 4, Technical Review and Assessment. The most-promising district-heating concept identified in the Phase I study for the Public Service Electric and Gas Company, Newark, New Jersey, is a hot-water system in which steam is extracted from an existing turbine and used to drive a new, small backpressure turbine-generator. The backpressure turbine provides heat for district heating and simultaneously provides additional electric-generating capacity to partially offset the capacity lost due to the steam extraction. This approach is the most-economical way to retrofit the stations studied for district heating while minimizing electric-capacity loss. Nine fossil-fuel-fired stations within the PSE and G system were evaluated for possibly supplying heat for district heating and cooling in cogeneration operations, but only three were selected to supply the district-heating steam. They are Essex, Hudson, and Bergen. Plant retrofit, thermal distribution schemes, consumer-conversion scheme, and consumer-metering system are discussed. Extensive technical information is provided in 16 appendices, additional tables, figures, and drawings. (MCW)

  20. Large scale solar cooling plants in America, Asia and Europe

    Energy Technology Data Exchange (ETDEWEB)

    Holter, Christian; Olsacher, Nicole [S.O.L.I.D. GmbH, Graz (Austria)

    2010-07-01

    Large scale solar cooling plants with an area between 120 - 1600 m{sup 2} are representative examples to illustrate S.O.L.I.D.'s experiences. The selected three reference solar cooling plants are located on three different continents: America, Asia and Europe. Every region has different framework conditions and its unforeseen challenges but professional experience and innovative ideas form the basis that each plant is operating well and satisfying the customer's demand. This verifies that solar cooling already is a proven technology. (orig.)

  1. CLASSIFICATION OF SYSTEMS FOR PASSIVE AFTERHEAT REMOVAL FROM REACTOR CONTAINMENT OF NUCLEAR POWER PLANT WITH WATER-COOLED POWER REACTOR

    Directory of Open Access Journals (Sweden)

    N. Khaled

    2014-01-01

    Full Text Available A classification on systems for passive afterheat removal from reactor containment has been developed in the paper.  The classification permits to make a detailed analysis of various concepts pertaining to systems for passive afterheat removal from reactor containment of new generation. The paper considers main classification features of the given systems.

  2. Optimal Cooling Load Sharing Strategies for Different Types of Absorption Chillers in Trigeneration Plants

    Directory of Open Access Journals (Sweden)

    Benedetto Conte

    2016-07-01

    Full Text Available Trigeneration plants can use different types of chillers in the same plant, typically single effect and double effect absorption chillers, vapour compression chillers and also cooling storage systems. The highly variable cooling demand of the buildings connected to a district heating and cooling (DHC network has to be distributed among these chillers to achieve lower operating costs and higher energy efficiencies. This problem is difficult to solve due to the different partial load behaviour of each chiller and the different chiller combinations that can cover a certain cooling demand using an appropriate sizing of the cooling storage. The objective of this paper is to optimize the daily plant operation of an existing trigeneration plant based on cogeneration engines and to study the optimal cooling load sharing between different types of absorption chillers using a mixed integer linear programming (MILP model. Real data from a trigeneration plant connected to a DHC close to Barcelona (Spain is used for the development of this model. The cooling load distribution among the different units is heavily influenced by the price of the electricity sold to the grid which rules the duration of the operation time of the engines. The main parameter to compare load distribution configurations is the primary energy saving indicator. Cooling load distribution among the different chillers changes also with the load of the whole plant because the chiller performance changes with load.

  3. Selective analysis of power plant operation on the Hudson River with emphasis on the Bowline Point Generating Station. Volume 2. [Multiple impact of power plant once-through cooling systems on fish populations

    Energy Technology Data Exchange (ETDEWEB)

    Barnthouse, L. W.; Cannon, J. B.; Christensen, S. G.

    1977-07-01

    Because of the location of the Bowline, Roseton, and Indian Point power generating facilities in the low-salinity zone of the Hudson estuary, operation of these plants with the present once-through cooling systems will adversely influence the fish populations that use the area for spawning and initial periods of growth and development. Recruitment rates and standing crops of several fish species may be lowered in response to the increased mortality caused by entrainment of nonscreenable eggs and larvae and by impingement of screenable young of the year. Entrainment and impingement data are particularly relevant for assessing which fish species have the greatest potential for being adversely affected by operation of Bowline, Roseton, and Indian Point with once-through cooling. These data from each of these three plants suggest that the six species that merit the greatest consideration are striped bass, white perch, tomcod, alewife, blueback herring, and bay anchovy. Two points of view are available for assessing the relative importance of the fish species in the Hudson River. From the fisheries point of view, the only two species of major importance are striped bass and shad. From the fish-community and ecosystem point of view, the dominant species, as determined by seasonal and regional standing crops (in numbers and biomass per hectare), are the six species most commonly entrained and impinged, namely, striped bass, white perch, tomcod, alewife, blueback herring, and anchovy.

  4. The Role of Absorption Cooling for Reaching Sustainable Energy Systems

    Energy Technology Data Exchange (ETDEWEB)

    Lindmark, Susanne

    2005-07-01

    This thesis focuses on the role and potential of absorption cooling in future energy systems. Two types of energy systems are investigated: a district energy system based on waste incineration and a distributed energy system with natural gas as fuel. In both cases, low temperature waste heat is used as driving energy for the absorption cooling. The main focus is to evaluate the absorption technology in an environmental perspective, in terms of reduced CO{sub 2} emissions. Economic evaluations are also performed. The reduced electricity when using absorption cooling instead of compression cooling is quantified and expressed as an increased net electrical yield. The results show that absorption cooling is an environmentally friendly way to produce cooling as it reduces the use of electrically driven cooling in the energy system and therefore also reduces global CO{sub 2} emissions. In the small-scale trigeneration system the electricity use is lowered with 84 % as compared to cooling production with compression chillers only. The CO{sub 2} emissions can be lowered to 45 CO{sub 2}/MWh{sub c} by using recoverable waste heat as driving heat for absorption chillers. However, the most cost effective cooling solution in a district energy system is a combination between absorption and compression cooling technologies according to the study. Absorption chillers have the potential to be suitable bottoming cycles for power production in distributed systems. Net electrical yields over 55 % may be reached in some cases with gas motors and absorption chillers. This small-scale system for cogeneration of power and cooling shows electrical efficiencies comparable to large-scale power plants and may contribute to reducing peak electricity demand associated with the cooling demand.

  5. Solar-powered cooling system

    Energy Technology Data Exchange (ETDEWEB)

    Farmer, Joseph C.

    2015-07-28

    A solar-powered adsorption-desorption refrigeration and air conditioning system that uses nanostructural materials such as aerogels, zeolites, and sol gels as the adsorptive media. Refrigerant molecules are adsorbed on the high surface area of the nanostructural material while the material is at a relatively low temperature, perhaps at night. During daylight hours, when the nanostructural materials is heated by the sun, the refrigerant are thermally desorbed from the surface of the aerogel, thereby creating a pressurized gas phase in the vessel that contains the aerogel. This solar-driven pressurization forces the heated gaseous refrigerant through a condenser, followed by an expansion valve. In the condenser, heat is removed from the refrigerant, first by circulating air or water. Eventually, the cooled gaseous refrigerant expands isenthalpically through a throttle valve into an evaporator, in a fashion similar to that in more conventional vapor recompression systems.

  6. High temperature cooling system and method

    Science.gov (United States)

    Loewen, Eric P.

    2006-12-12

    A method for cooling a heat source, a method for preventing chemical interaction between a vessel and a cooling composition therein, and a cooling system. The method for cooling employs a containment vessel with an oxidizable interior wall. The interior wall is oxidized to form an oxide barrier layer thereon, the cooling composition is monitored for excess oxidizing agent, and a reducing agent is provided to eliminate excess oxidation. The method for preventing chemical interaction between a vessel and a cooling composition involves introducing a sufficient quantity of a reactant which is reactive with the vessel in order to produce a barrier layer therein that is non-reactive with the cooling composition. The cooling system includes a containment vessel with oxidizing agent and reducing agent delivery conveyances and a monitor of oxidation and reduction states so that proper maintenance of a vessel wall oxidation layer occurs.

  7. Evaluation of geothermal cooling systems for Arizona

    Energy Technology Data Exchange (ETDEWEB)

    White, D.H.; Goldstone, L.A.

    1982-08-01

    Arizona consumes nearly 50 percent more electricity during the peak summer season of May through part of October, due to the high cooling load met by electrical-driven air conditioning units. This study evaluates two geothermal-driven cooling systems that consume less electricity, namely, absorption cooling and heat pumps. Adsorption cooling requires a geothermal resource above 105{sup 0}C (220{sup 0}F) in order to operate at a reasonable efficiency and capacity. Geothermal resources at these temperatures or above are believed existing in the Phoenix and Tucson areas, but at such depths that geothermal-driven absorption systems have high capital investments. Such capital investments are uneconomical when paid out over only five months of operation each year, but become economical when cascaded with other geothermal uses. There may be other regions of the state, where geothermal resources exist at 105{sup 0}C (220{sup 0}F) or higher at much less depth, such as the Casa Grande/Coolidge or Hyder areas, which might be attractive locations for future plants of the high-technology industries. Geothermal assisted heat pumps have been shown in this study to be economical for nearly all areas of Arizona. They are more economical and reliable than air-to-air heat pumps. Such systems in Arizona depend upon a low-temperature geothermal resource in the narrow range of 15.5 to 26.6{sup 0}C (60 to 80{sup 0}F), and are widely available in Arizona. The state has over 3000 known (existing) thermal wells, out of a total of about 30,000 irrigation wells.

  8. Plants for passive cooling. A preliminary investigation of the use of plants for passive cooling in temperate humid climates

    Energy Technology Data Exchange (ETDEWEB)

    Spirn, A W; Santos, A N; Johnson, D A; Harder, L B; Rios, M W

    1981-04-01

    The potential of vegetation for cooling small, detached residential and commercial structures in temperate, humid climates is discussed. The results of the research are documented, a critical review of the literature is given, and a brief review of energy transfer processes is presented. A checklist of design objectives for passive cooling, a demonstration of design applications, and a palette of selected plant species suitable for passive cooling are included.

  9. Two years of operation of a large solar cooling plant

    Energy Technology Data Exchange (ETDEWEB)

    Lazzarin, R.M.; Romagnoni, P. (Padua Univ. (Italy)); Casasola, L. (CERIT, Pordenone (Italy))

    1993-05-01

    A solar plant was installed with a surface area of 440 m[sup 2] of evacuated-tube collectors, a reflecting surface of the same area and an absorption refrigeration system for air-conditioning the CERIT building of Pordenone. A 43 m[sup 3] heat-storage unit, at temperatures of 80-90[sup o]C, and a 150 m[sup 3] cold-storage unit were also installed. These components form the largest solar cooling plant in Europe. After two years of operation, it is possible to evaluate the project as a whole, and to appreciate the contribution of the flat solar reflector and the working of the absorption unit. (Author)

  10. Naegleria fowleri in cooling waters of power plants

    Energy Technology Data Exchange (ETDEWEB)

    Cerva, L.; Kasprzak, W.; Mazur, T.

    1982-01-01

    Six strains of nonvirulent and three strains of virulent variants of Naegleria fowleri amoebae were isolated from the examined cooling water samples from 9 power plants. The virulent variants were obtained solely from effluents discharged from power plants with a closed-circuit cooling N. fowleri was not detected outside the reach of the thermal pollution. A disinfection of out-flowing cooling water seems to be an unnecessary investment in our climate. Warm discharge water should under no conditions be used directly for sports and recreational purposes.

  11. Justifying plans to improve performance of an existing cooling system

    Energy Technology Data Exchange (ETDEWEB)

    Burns, J. [Stone & Webster Engineering Corp., Boston, MA (United States); Godard, D.; Randall, R. [Niagara-Mohawk Power Company, Syracuse, NY (United States); Cooper, J. [Cooper & Associates, P.A., Tampa, FL (United States)

    1996-08-01

    This paper discusses the kinds of quantitative justification needed to convince today`s cost-conscious, informed utility management that proposed improvements to the cooling system are feasible and will be of strong economic benefit to the station. It summarizes the evaluations developed during the review of circulating water system improvement candidates that accompanied the recent 4.5% power uprate of an existing large station with a closed cycle cooling system which utilizes a natural draft cooling tower. Presented in the paper are the capital costs and turbine performance improvements related to: air blanketing reduction by baffle plate additions to the condenser air coolers; minimizing costs of waterbox/bundle cleaning programs; cooling system performance monitoring enhancements; the prudency of tube staking after uprate; the benefits of a circulating water flow increase; better cooling tower hot water distribution; adding a layer of fill to the cooling tower; and finally the value of a helper tower. Considered too in this paper are the performance test surveys of both the condenser and cooling tower that identified the cause and/or performance deficiencies. The general principles to be discussed will be applicable to all sizes and types of power plant cooling systems. The paper however, will focus on the 1994-1995 case study of a 675,000 GPM closed cooling system with a 537 ft. counterflow natural draft cooling tower and a 670,000 sq. ft. six bundle single pass condenser which serves the six flow low pressure (LP) turbine of an 1100 MW nuclear plant. One example of the outcome of the program was an approximate 20% increase in condenser cleanliness from 55% to 75%. 9 refs., 7 figs.

  12. Review and assessment of engineering economic studies of dry cooled electrical generating plants

    Energy Technology Data Exchange (ETDEWEB)

    Fryer, B.C.

    1976-03-01

    The major U.S. studies conducted between 1970 and 1975 on the economics of dry cooled electrical generating plants are reviewed. This review was undertaken to collect, compare, and summarize the approaches, assumptions, and results of several major studies on dry cooling engineering economics, and to evaluate the computer codes associated with these economic studies. From this review it was concluded that adequate detailed evaluation of state-of-the-art dry cooling systems has not been conducted and that comprehensive computer programs capable of such evaluations are not publicly available. Therefore, it is recommended that: a method for determining power production costs of dry cooled plants should be developed which reflects the actual way a utility would interface a dry cooled plant with a utility system to minimize power production costs; a comprehensive detailed evaluation of metal finned tube state-of-the-art dry cooling systems should be conducted to determine if, and where, the costs of dry cooling can be reduced; and advanced dry cooling concepts should be evaluated for potential savings in power production costs. (LCL)

  13. A combined capillary cooling system for cooling fuel cells

    Energy Technology Data Exchange (ETDEWEB)

    Silva, Ana Paula; Pelizza, Pablo Rodrigo; Galante, Renan Manozzo; Bazzo, Edson [Universidade Federal de Santa Catarina (LabCET/UFSC), Florianopolis, SC (Brazil). Dept. de Engenharia Mecanica. Lab. de Combustao e Engenharia de Sistemas Termicos], Emails: ana@labcet.ufsc.br, pablo@labcet.ufsc.br, renan@labcet.ufsc.br, ebazzo@emc.ufsc.br

    2010-07-01

    The operation temperature control has an important influence over the PEMFC (Proton Exchange Membrane Fuel Cell) performance. A two-phase heat transfer system is proposed as an alternative for cooling and thermal control of PEMFC. The proposed system consists of a CPL (Capillary Pumped Loop) connected to a set of constant conductance heat pipes. In this work ceramic wick and stainless mesh wicks have been used as capillary structure of the CPL and heat pipes, respectively. Acetone has been used as the working fluid for CPL and deionized water for the heat pipes. Experimental results of three 1/4 inch stainless steel outlet diameter heats pipes and one CPL have been carried out and presented in this paper. Further experiments are planned coupling the proposed cooling system to a module which simulates the fuel cell. (author)

  14. Floor cooling and air-cooling, the effects on thermal comfort or different cooling systems

    Energy Technology Data Exchange (ETDEWEB)

    Sijpheer, N.C.; Bakker, E.J.; Ligthart, F.A.T.M.; Opstelten, I.J. [ECN Energie in de Gebouwde Omgeving en Netten, Petten (Netherlands)

    2007-09-15

    One of the research areas of the Energy research Centre of the Netherlands (ECN) concerns the built environment. Several facilities to conduct research activities are at ECN's disposal. One of these facilities, are five research dwellings located on the premises of ECN. Measured data from these facilities together with weather data and computer models are used to evaluate innovative energy concepts and components in energy systems. Experiments with different cooling systems in ECN's research dwellings are executed to evaluate their effective influence on both energy use and thermal comfort. Influence of inhabitants' behaviour is taken into account in these experiments. The thermal comfort is indicated by the Predicted Mean Vote (PMV) as defined by P.O. Fanger. For this paper, the results of measurements with a floor cooling and air cooling system are assessed. Effects on the PMV measured during experiments with the two different cooling systems will be presented.

  15. Advances in Solar Heating and Cooling Systems

    Science.gov (United States)

    Ward, Dan S.

    1976-01-01

    Reports on technological advancements in the fields of solar collectors, thermal storage systems, and solar heating and cooling systems. Diagrams aid in the understanding of the thermodynamics of the systems. (CP)

  16. Conceptual design of advanced central receiver power systems sodium-cooled receiver concept. Volume 4. Commercial and pilot plant cost data. Final report

    Energy Technology Data Exchange (ETDEWEB)

    1979-03-01

    This volume of the advanced central receiver final report presents the cost data using the cost breakdown structure identified in the preliminary specification. Cost summaries are presented in the following sections for the 100-MWe and 281-MWe commercial plant and a 10-MWe pilot plant. Cost substantiation data for this volume are presented in the appendices. Other cost summary data include Nth plant data for the 100-MWe and 281-MWe commercial plants, and a summary for the alternative concept air-rock storage system. The main description of the plant costing technique occurs as part of Section II for the 100-MWe baseline concept.

  17. Conceptual design of advanced central receiver power systems sodium-cooled receiver concept. Volume 4. Commercial and pilot plant cost data. Final report

    Energy Technology Data Exchange (ETDEWEB)

    1979-03-01

    This volume of the advanced central receiver final report presents the cost data using the cost breakdown structure identified in the preliminary specification. Cost summaries are presented in the following sections for the 100-MWe and 281-MWe commercial plant and a 10-MWe pilot plant. Cost substantiation data for this volume are presented in the appendices. Other cost summary data include Nth plant data for the 100-MWe and 281-MWe commercial plants, and a summary for the alternative concept air-rock storage system. The main description of the plant costing technique occurs as part of Section II for the 100-MWe baseline concept.

  18. Hot gas path component cooling system

    Science.gov (United States)

    Lacy, Benjamin Paul; Bunker, Ronald Scott; Itzel, Gary Michael

    2014-02-18

    A cooling system for a hot gas path component is disclosed. The cooling system may include a component layer and a cover layer. The component layer may include a first inner surface and a second outer surface. The second outer surface may define a plurality of channels. The component layer may further define a plurality of passages extending generally between the first inner surface and the second outer surface. Each of the plurality of channels may be fluidly connected to at least one of the plurality of passages. The cover layer may be situated adjacent the second outer surface of the component layer. The plurality of passages may be configured to flow a cooling medium to the plurality of channels and provide impingement cooling to the cover layer. The plurality of channels may be configured to flow cooling medium therethrough, cooling the cover layer.

  19. Geographic, technologic, and economic analysis of using reclaimed water for thermoelectric power plant cooling.

    Science.gov (United States)

    Stillwell, Ashlynn S; Webber, Michael E

    2014-04-15

    Use of reclaimed water-municipal wastewater treatment plant effluent-in nonpotable applications can be a sustainable and efficient water management strategy. One such nonpotable application is at thermoelectric power plants since these facilities require cooling, often using large volumes of freshwater. To evaluate the geographic, technologic, and economic feasibility of using reclaimed water to cool thermoelectric power plants, we developed a spatially resolved model of existing power plants. Our model integrates data on power plant and municipal wastewater treatment plant operations into a combined geographic information systems and optimization approach to evaluate the feasibility of cooling system retrofits. We applied this broadly applicable methodology to 125 power plants in Texas as a test case. Results show that sufficient reclaimed water resources exist within 25 miles of 92 power plants (representing 61% of capacity and 50% of generation in our sample), with most of these facilities meeting both short-term and long-term water conservation cost goals. This retrofit analysis indicates that reclaimed water could be a suitable cooling water source for thermoelectric power plants, thereby mitigating some of the freshwater impacts of electricity generation.

  20. Scale formation in deluged dry cooling systems

    Energy Technology Data Exchange (ETDEWEB)

    Pratt, D.R.

    1976-05-01

    Deluging of air-cooled heat exchangers with water during warm periods holds the promise of increasing heat rejection capability and reducing the cost of dry cooling. One of the principal uncertainties in the use of the deluge concept is the tendency toward deposition of solids from the delugate. Small amounts of calcium carbonate scale may significantly reduce the cooling efficiency of a deluged system by reducing the heat transfer coefficient and interfering with delugate flow. Thus the question of delugate water quality is of major importance in evaluating scale formation and its effect on heat transfer in the deluged dry cooling system. The paper discusses, in relation to the deluged dry cooling system, the importance of scale prevention, the theory of scale formation and application of this theory to the deluged system, the problems of delugate evaporation, and delugate treatment required to prevent scaling.

  1. Cooling the intact loop of primary heat transport system using Shutdown Cooling System in case of LOCA events

    Directory of Open Access Journals (Sweden)

    Icleanu Diana Laura

    2015-01-01

    Full Text Available The purpose of this paper is to model the operation of the Shutdown Cooling System (SDCS for CANDU 6 nuclear power plants in case of LOCA accidents, using Flowmaster calculation code, by delimiting models and setting calculation assumptions, input data for hydraulic analysis and input data for calculating thermal performance check for heat exchangers that are part of this system.

  2. Capital cost: gas cooled fast reactor plant

    Energy Technology Data Exchange (ETDEWEB)

    1977-09-01

    The results of an investment cost study for a 900 MW(e) GCFR central station power plant are presented. The capital cost estimate arrived at is based on 1976 prices and a conceptual design only, not a mature reactor design.

  3. COOLING WATER ISSUES AND OPPORTUNITIES AT U.S. NUCLEAR POWER PLANTS

    Energy Technology Data Exchange (ETDEWEB)

    Gary Vine

    2010-12-01

    This report has been prepared for the Department of Energy, Office of Nuclear Energy (DOE-NE), for the purpose of providing a status report on the challenges and opportunities facing the U.S. commercial nuclear energy industry in the area of plant cooling water supply. The report was prompted in part by recent Second Circuit and Supreme Court decisions regarding cooling water system designs at existing thermo-electric power generating facilities in the U.S. (primarily fossil and nuclear plants). At issue in the courts have been Environmental Protection Agency regulations that define what constitutes “Best Technology Available” for intake structures that withdraw cooling water that is used to transfer and reject heat from the plant’s steam turbine via cooling water systems, while minimizing environmental impacts on aquatic life in nearby water bodies used to supply that cooling water. The report was also prompted by a growing recognition that cooling water availability and societal use conflicts are emerging as strategic energy and environmental issues, and that research and development (R&D) solutions to emerging water shortage issues are needed. In particular, cooling water availability is an important consideration in siting decisions for new nuclear power plants, and is an under-acknowledged issue in evaluating the pros and cons of retrofitting cooling towers at existing nuclear plants. Because of the significant ongoing research on water issues already being performed by industry, the national laboratories and other entities, this report relies heavily on ongoing work. In particular, this report has relied on collaboration with the Electric Power Research Institute (EPRI), including its recent work in the area of EPA regulations governing intake structures in thermoelectric cooling water systems.

  4. Test of different measures for the prevention of scaling in the cooling system of Grohnde nuclear power plant; Test verschiedener Massnahmen zur Verhuetung von Kalkablagerungen im Kuehlsystem des Kernkraftwerks Grohnde

    Energy Technology Data Exchange (ETDEWEB)

    Czolkoss, W. [Taprogge GmbH, Wetter (Germany); Jacobi, G.; Schueler, A. [Gemeinschaftskernkraftwerk Grohnde GmbH, Emmerthal (Germany); Fichte, W. [Allianz-Zentrum fuer Technik GmbH (AZT), Ismaning (Germany)

    2002-07-01

    In the cooling system of the Grohnde Nuclear Power Plant, heavy calcium carbonate precipitations have occurred in the turbine condenser and in the cooling tower since 1994. Those precipitations cause performance losses and high cleaning costs. Reasons for the intensified precipitation are apparently the biologically upgraded water quality of the river Weser, as well as specific operational conditions of the cooling system (partial recirculation of cooling water). It was noticed that the formation of calcium carbonate deposits occurred within a limited period of less than two weeks in May. The calcium precipitation was that strong during this time that it could not be stopped despite the immediate application of corundum cleaning balls in the tube cleaning system. (orig.) [German] Im Kuehlsystem des Kernkraftwerks Grohnde kommt es seit 1994 zu starken Kalkausfaellungen im Turbinenkondensator und im Kuehlturm, die Leistungsverluste und hohe Reinigungskosten verursachen. Das Auftreten der Kalkabscheidungen haengt offensichtlich mit der oekologisch verbesserten Wasserqualitaet der Weser und spezifischen Betriebsbedingungen des Kuehlsystems zusammen. Die Auswertung der Betriebsmessdaten des Kuehlwassers zeigt, dass eine der Ursachen der zeitlich begrenzten, extremen Kalkabscheidung im Kuehlsystem offenbar das Wachstum von Mikroorganismen in der Weser ist, aus der das Kuehlsystem gespeist wird. (orig.)

  5. Heat Driven Cooling in District Energy Systems; Vaermedriven Kyla

    Energy Technology Data Exchange (ETDEWEB)

    Rydstrand, Magnus; Martin, Viktoria; Westermark, Mats [Royal Inst. of Technology, Stockholm (Sweden). Dept. of Chemical Engineering and Technology

    2004-07-01

    high costs. However heat sinks are unavoidable from a system perspective and there are potential cost savings since a low-pressure steam turbines will not be required if heat driven cooling is implemented. The fuel utilization for some technologies (not necessarily the best technology) was evaluated in two different scenarios: 1) with electricity production from coal; and 2) with electricity production from natural gas. It is shown in the scenarios that the heat driven cooling technologies give lower fuel consumption as compared producing electricity as an intermediate product before cooling is produced. Further it should be noted that electricity is produced, not consumed, if heat is used directly for the production of cooling. We claim that cost effective solutions for district heat driven chillers and/or combined production of electricity and district cooling can be found in all climates with high enough density of heating and cooling demands. It was found that district heat driven chillers can be very energy efficient in warm and humid climates since desiccant systems are an effective way of handling latent cooling loads. In dry climates, with low latent loads, water distributed cooling has a large potential and absorption cooling will give high fuel utilization seen from a system perspective. In climates where water shortage is a problem it is possible that the temperature lift of the conventional absorption chiller has to be increased in order to be able to use dry cooling towers. The temperature lift can be increased by changing the chiller design or by using a different working pair. Heat driven cooling can be integrated into an energy system in different ways. In USA and Japan, district heating is not well developed. Instead small, distributed combined heat and power (CHP) plants with high exhaust temperatures are widespread. Cooling is often produced, in these regions, through absorption cooling (using heat from CHP) or compression chillers depending on

  6. The Evaporative Cooling System for the ATLAS Inner Detector

    CERN Document Server

    Aitree, D; Anderssen, E C; Akhnazarov, V; Apsimon, R J; Barclay, P; Batchelor, L E; Bates, R L; Battistin, M; Bendotti, J; Berry, S; Bitadze, A; Bizzel, J P; Bonneau, P; Bosteels, Michel; Butterworth, J M; Butterworth, S; Carter, A A; Carter, J R; Catinaccio, A; Corbaz, F; Danielsson, H O; Danilevich, E; Dixon, N; Dixon, S D; Doherty, F; Dorholt, O; Doubrava, M; Egorov, I; Egorov, K; Einsweiler, K; Falou, A C; Feraudet, P; Ferrari, P; Fowler, K; Fraser, J T; French, R S; Galuska, M; Gannaway, F; Gariano, G; Gibson, M D; Gilchriese, M G D; Giugni, D; Godlewski, J; Gousakov, I; Górski, B; Hallewell, G D; Hartman, N; Hawkings, R J; Haywood, S J; Hessey, N P; Infante, S; Jackson, J N; Jones, T J; Kaplon, J; Katunin, S; Lindsay, S; Luisa, L; Massol, N; McEwan, F; McMahon, S J; Menot, C; Mistry, J; Morris, J; Muskett, D M; Nagai, K; Nichols, A; Nicholson, R; Nickerson, R B; Nielsen, S L; Nordahl, P E; Olcese, M; Parodi, M; Pérez-Gómez, F; Pernegger, H; Perrin, E; Rossi, L P; Rovani, A; Ruscino, E; Sandaker, H; Smith, A; Sopko, V; Stapnes, S; Stodulski, M; Tarrant, J; Thadome, J; Tovey, D; Turala, M; Tyndel, M; Vacek, V; van der Kraaij, E; Viehhauser, G H A; Vigeolas, E; Wells, P S; Wenig, S; Werneke, P

    2008-01-01

    This paper describes the evaporative system used to cool the silicon detector structures of the inner detector sub-detectors of the ATLAS experiment at the CERN Large Hadron Collider. The motivation for an evaporative system, its design and construction are discussed. In detail the particular requirements of the ATLAS inner detector, technical choices and the qualification and manufacture of final components are addressed. Finally results of initial operational tests are reported. Although the entire system described, the paper focuses on the on-detector aspects. Details of the evaporative cooling plant will be discussed elsewhere.

  7. The ATLAS IBL CO2 Cooling System

    CERN Document Server

    Verlaat, Bartholomeus; The ATLAS collaboration

    2016-01-01

    The Atlas Pixel detector has been equipped with an extra B-layer in the space obtained by a reduced beam pipe. This new pixel detector called the ATLAS Insertable B-Layer (IBL) is installed in 2014 and is operational in the current ATLAS data taking. The IBL detector is cooled with evaporative CO2 and is the first of its kind in ATLAS. The ATLAS IBL CO2 cooling system is designed for lower temperature operation (<-35⁰C) than the previous developed CO2 cooling systems in High Energy Physics experiments. The cold temperatures are required to protect the pixel sensors for the high expected radiation dose up to 550 fb^-1 integrated luminosity. This paper describes the design, development, construction and commissioning of the IBL CO2 cooling system. It describes the challenges overcome and the important lessons learned for the development of future systems which are now under design for the Phase-II upgrade detectors.

  8. Effectiveness-weighted control method for a cooling system

    Energy Technology Data Exchange (ETDEWEB)

    Campbell, Levi A.; Chu, Richard C.; David, Milnes P.; Ellsworth Jr., Michael J.; Iyengar, Madhusudan K.; Schmidt, Roger R.; Simons, Robert E.

    2015-12-15

    Energy efficient control of cooling system cooling of an electronic system is provided based, in part, on weighted cooling effectiveness of the components. The control includes automatically determining speed control settings for multiple adjustable cooling components of the cooling system. The automatically determining is based, at least in part, on weighted cooling effectiveness of the components of the cooling system, and the determining operates to limit power consumption of at least the cooling system, while ensuring that a target temperature associated with at least one of the cooling system or the electronic system is within a desired range by provisioning, based on the weighted cooling effectiveness, a desired target temperature change among the multiple adjustable cooling components of the cooling system. The provisioning includes provisioning applied power to the multiple adjustable cooling components via, at least in part, the determined control settings.

  9. Effectiveness-weighted control of cooling system components

    Energy Technology Data Exchange (ETDEWEB)

    Campbell, Levi A.; Chu, Richard C.; David, Milnes P.; Ellsworth Jr., Michael J.; Iyengar, Madhusudan K.; Schmidt, Roger R.; Simmons, Robert E.

    2015-12-22

    Energy efficient control of cooling system cooling of an electronic system is provided based, in part, on weighted cooling effectiveness of the components. The control includes automatically determining speed control settings for multiple adjustable cooling components of the cooling system. The automatically determining is based, at least in part, on weighted cooling effectiveness of the components of the cooling system, and the determining operates to limit power consumption of at least the cooling system, while ensuring that a target temperature associated with at least one of the cooling system or the electronic system is within a desired range by provisioning, based on the weighted cooling effectiveness, a desired target temperature change among the multiple adjustable cooling components of the cooling system. The provisioning includes provisioning applied power to the multiple adjustable cooling components via, at least in part, the determined control settings.

  10. Pathogenic amoebae in power-plant cooling lakes. Final report

    Energy Technology Data Exchange (ETDEWEB)

    Tyndall, R.L.; Willaert, E.; Stevens, A.R.

    1981-06-01

    Cooling waters and associated algae and sediments from four northern and four southern/western electric power plants were tested for the presence of pathogenic amoebae. Unheated control waters and algae/sediments from four northern and five southern/western sites were also tested. When comparing results from the test versus control sites, a significantly higher proportion (P less than or equal to 0.05) of the samples from the test sites were positive for thermophilic amoeba, thermophilic Naegleria and pathogenic Naegleria. The difference in number of samples positive for thermophilic Naegleria between heated and unheated waters, however, was attributable predominantly to the northern waters and algae/sediments. While two of four northern test sites yielded pathogenic Naegleria, seven of the eight isolates were obtained from one site. Seasonality effects relative to the isolation of the pathogen were also noted at this site. One pathogen was isolated from a southwestern test site. Pathogens were not isolated from any control sites. Some of the pathogenic isolates were analyzed serologically and classified as pathogenic Naegleria fowleri. Salinity, pH, conductivity, and bacteriological profiles did not obviously correlate with the presence or absence of pathogenic Naegleria. While thermal addition was significantly associated with the presence of thermophilic Naegleria (P less than or equal to 0.05), the data implicate other as yet undefined parameters associated with the presence of the pathogenic thermophile. Until further delineation of these parameters is effected, generalizations cannot be made concerning the effect of thermal impact on the growth of pathogenic amoeba in a particular cooling system.

  11. Cooling system with automated seasonal freeze protection

    Energy Technology Data Exchange (ETDEWEB)

    Campbell, Levi A.; Chu, Richard C.; David, Milnes P.; Ellsworth, Jr., Michael J.; Iyengar, Madhusudan K.; Simons, Robert E.; Singh, Prabjit; Zhang, Jing

    2016-05-24

    An automated multi-fluid cooling system and method are provided for cooling an electronic component(s). The cooling system includes a coolant loop, a coolant tank, multiple valves, and a controller. The coolant loop is at least partially exposed to outdoor ambient air temperature(s) during normal operation, and the coolant tank includes first and second reservoirs containing first and second fluids, respectively. The first fluid freezes at a lower temperature than the second, the second fluid has superior cooling properties compared with the first, and the two fluids are soluble. The multiple valves are controllable to selectively couple the first or second fluid into the coolant in the coolant loop, wherein the coolant includes at least the second fluid. The controller automatically controls the valves to vary first fluid concentration level in the coolant loop based on historical, current, or anticipated outdoor air ambient temperature(s) for a time of year.

  12. Controlled cooling of an electronic system for reduced energy consumption

    Science.gov (United States)

    David, Milnes P.; Iyengar, Madhusudan K.; Schmidt, Roger R.

    2016-08-09

    Energy efficient control of a cooling system cooling an electronic system is provided. The control includes automatically determining at least one adjusted control setting for at least one adjustable cooling component of a cooling system cooling the electronic system. The automatically determining is based, at least in part, on power being consumed by the cooling system and temperature of a heat sink to which heat extracted by the cooling system is rejected. The automatically determining operates to reduce power consumption of the cooling system and/or the electronic system while ensuring that at least one targeted temperature associated with the cooling system or the electronic system is within a desired range. The automatically determining may be based, at least in part, on one or more experimentally obtained models relating the targeted temperature and power consumption of the one or more adjustable cooling components of the cooling system.

  13. Preoperational test report, recirculation condenser cooling systems

    Energy Technology Data Exchange (ETDEWEB)

    Clifton, F.T.

    1997-11-04

    This represents a preoperational test report for Recirculation Condenser Systems, Project W-030. Project W-030 provides a ventilation upgrade for the four Aging Waste Facility tanks. The four system provide condenser cooling water for vapor space cooling of tanks AY1O1, AY102, AZ1O1, AZ102. Each system consists of a valved piping loop, a pair of redundant recirculation pumps, a closed-loop evaporative cooling tower, and supporting instrumentation; equipment is located outside the farm on concrete slabs. Piping is routed to the each ventilation condenser inside the farm via below-grade concrete trenches. The tests verify correct system operation and correct indications displayed by the central Monitor and Control System.

  14. Preoperational test report, recirculation condenser cooling systems

    Energy Technology Data Exchange (ETDEWEB)

    Clifton, F.T.

    1997-11-04

    This represents a preoperational test report for Recirculation Condenser Systems, Project W-030. Project W-030 provides a ventilation upgrade for the four Aging Waste Facility tanks. The four system provide condenser cooling water for vapor space cooling of tanks AY1O1, AY102, AZ1O1, AZ102. Each system consists of a valved piping loop, a pair of redundant recirculation pumps, a closed-loop evaporative cooling tower, and supporting instrumentation; equipment is located outside the farm on concrete slabs. Piping is routed to the each ventilation condenser inside the farm via below-grade concrete trenches. The tests verify correct system operation and correct indications displayed by the central Monitor and Control System.

  15. Prototype solar heating and cooling systems

    Energy Technology Data Exchange (ETDEWEB)

    1978-03-01

    A collection of quarterly reports from the AiResearch Manufacturing Company covering the period July 12, 1976, through December 31, 1977, is presented. AiResearch Manufacturing Company is developing eight prototype solar heating and cooling systems. This effort calls for the development, manufacture, test, system installation, maintenance, problem resolution, and performance evaluation. The systems are 3, 25 and 75-ton size units.

  16. Cavity Cooling for Ensemble Spin Systems

    Science.gov (United States)

    Cory, David

    2015-03-01

    Recently there has been a surge of interest in exploring thermodynamics in quantum systems where dissipative effects can be exploited to perform useful work. One such example is quantum state engineering where a quantum state of high purity may be prepared by dissipative coupling through a cold thermal bath. This has been used to great effect in many quantum systems where cavity cooling has been used to cool mechanical modes to their quantum ground state through coupling to the resolved sidebands of a high-Q resonator. In this talk we explore how these techniques may be applied to an ensemble spin system. This is an attractive process as it potentially allows for parallel remove of entropy from a large number of quantum systems, enabling an ensemble to achieve a polarization greater than thermal equilibrium, and potentially on a time scale much shorter than thermal relaxation processes. This is achieved by the coupled angular momentum subspaces of the ensemble behaving as larger effective spins, overcoming the weak individual coupling of individual spins to a microwave resonator. Cavity cooling is shown to cool each of these subspaces to their respective ground state, however an additional algorithmic step or dissipative process is required to couple between these subspaces and enable cooling to the full ground state of the joint system.

  17. Implications of Transitioning from De Facto to Engineered Water Reuse for Power Plant Cooling.

    Science.gov (United States)

    Barker, Zachary A; Stillwell, Ashlynn S

    2016-05-17

    Thermoelectric power plants demand large quantities of cooling water, and can use alternative sources like treated wastewater (reclaimed water); however, such alternatives generate many uncertainties. De facto water reuse, or the incidental presence of wastewater effluent in a water source, is common at power plants, representing baseline conditions. In many cases, power plants would retrofit open-loop systems to cooling towers to use reclaimed water. To evaluate the feasibility of reclaimed water use, we compared hydrologic and economic conditions at power plants under three scenarios: quantified de facto reuse, de facto reuse with cooling tower retrofits, and modeled engineered reuse conditions. We created a genetic algorithm to estimate costs and model optimal conditions. To assess power plant performance, we evaluated reliability metrics for thermal variances and generation capacity loss as a function of water temperature. Applying our analysis to the greater Chicago area, we observed high de facto reuse for some power plants and substantial costs for retrofitting to use reclaimed water. Conversely, the gains in reliability and performance through engineered reuse with cooling towers outweighed the energy investment in reclaimed water pumping. Our analysis yields quantitative results of reclaimed water feasibility and can inform sustainable management of water and energy.

  18. The ATLAS IBL CO2 cooling system

    Science.gov (United States)

    Verlaat, B.; Ostrega, M.; Zwalinski, L.; Bortolin, C.; Vogt, S.; Godlewski, J.; Crespo-Lopez, O.; Van Overbeek, M.; Blaszcyk, T.

    2017-02-01

    The ATLAS Pixel detector has been equipped with an extra pixel layer in the space obtained by a smaller radius beam pipe. This new pixel layer called the Insertable B-Layer (IBL) was installed in 2014 and is operational in the current ATLAS data taking. The IBL detector is cooled with evaporative CO2 and is the first of its kind in ATLAS. The ATLAS IBL CO2 cooling system is designed for lower temperature operation (systems in High Energy Physics experiments. The cold temperatures are required to protect the pixel sensors for the expected high radiation dose received at an integrated luminosity of 550 fb1. This paper describes the design, development, construction and commissioning of the IBL CO2 cooling system. It describes the challenges overcome and the important lessons learned for the development of future systems which are now under design for the Phase-II upgrade detectors.

  19. Use of reclaimed water for power plant cooling.

    Energy Technology Data Exchange (ETDEWEB)

    Veil, J. A.; Environmental Science Division

    2007-10-16

    Freshwater demands are steadily increasing throughout the United States. As its population increases, more water is needed for domestic use (drinking, cooking, cleaning, etc.) and to supply power and food. In arid parts of the country, existing freshwater supplies are not able to meet the increasing demands for water. New water users are often forced to look to alternative sources of water to meet their needs. Over the past few years, utilities in many locations, including parts of the country not traditionally water-poor (e.g., Georgia, Maryland, Massachusetts, New York, and North Carolina) have needed to reevaluate the availability of water to meet their cooling needs. This trend will only become more extreme with time. Other trends are likely to increase pressure on freshwater supplies, too. For example, as populations increase, they will require more food. This in turn will likely increase demands for water by the agricultural sector. Another example is the recent increased interest in producing biofuels. Additional water will be required to grow more crops to serve as the raw materials for biofuels and to process the raw materials into biofuels. This report provides information about an opportunity to reuse an abundant water source -- treated municipal wastewater, also known as 'reclaimed water' -- for cooling and process water in electric generating facilities. The report was funded by the U.S. Department of Energy's (DOE's) National Energy Technology Laboratory (NETL) Innovations for Existing Plants research program (Feeley 2005). This program initiated an energy-water research effort in 2003 that includes the availability and use of 'nontraditional sources' of water for use at power plants. This report represents a unique reference for information on the use of reclaimed water for power plant cooling. In particular, the database of reclaimed water user facilities described in Chapter 2 is the first comprehensive national effort

  20. MULTIFUNCTIONAL SOLAR SYSTEMS FOR HEATING AND COOLING

    Directory of Open Access Journals (Sweden)

    Doroshenko A.V.

    2010-12-01

    Full Text Available The basic circuits of multifunctional solar systems of air drainage, heating (hot water supply and heating, cooling and air conditioning are developed on the basis of open absorption cycle with a direct absorbent regeneration. Basic decisions for new generation of gas-liquid solar collectors are developed. Heat-mass-transfer apparatus included in evaporative cooling system, are based on film interaction of flows of gas and liquid and in them, for the creation of nozzle, multi-channel structures from polymeric materials and porous ceramics are used. Preliminary analysis of multifunctional systems possibilities is implemented.

  1. 78 FR 35330 - Initial Test Programs for Water-Cooled Nuclear Power Plants

    Science.gov (United States)

    2013-06-12

    ... COMMISSION Initial Test Programs for Water-Cooled Nuclear Power Plants AGENCY: Nuclear Regulatory Commission... revision to Regulatory Guide (RG), 1.68, ``Initial Test Programs for Water-Cooled Nuclear Power Plants... Initial Test Programs (ITPs) for light water cooled nuclear power plants. ADDRESSES: Please refer...

  2. Work Breakdown Structure and Plant/Equipment Designation System Numbering Scheme for the High Temperature Gas- Cooled Reactor (HTGR) Component Test Capability (CTC)

    Energy Technology Data Exchange (ETDEWEB)

    Jeffrey D Bryan

    2009-09-01

    This white paper investigates the potential integration of the CTC work breakdown structure numbering scheme with a plant/equipment numbering system (PNS), or alternatively referred to in industry as a reference designation system (RDS). Ideally, the goal of such integration would be a single, common referencing system for the life cycle of the CTC that supports all the various processes (e.g., information, execution, and control) that necessitate plant and equipment numbers be assigned. This white paper focuses on discovering the full scope of Idaho National Laboratory (INL) processes to which this goal might be applied as well as the factors likely to affect decisions about implementation. Later, a procedure for assigning these numbers will be developed using this white paper as a starting point and that reflects the resolved scope and outcome of associated decisions.

  3. Performance testing of engineered corium cooling systems

    Energy Technology Data Exchange (ETDEWEB)

    Lomperski, S., E-mail: lomperski@anl.gov [Argonne National Laboratory, 9700 S. Cass Avenue, Argonne, IL 60439-4840 (United States); Farmer, M.T. [Argonne National Laboratory, 9700 S. Cass Avenue, Argonne, IL 60439-4840 (United States)

    2012-02-15

    Highlights: Black-Right-Pointing-Pointer Experiments tested two engineered corium cooling systems. Black-Right-Pointing-Pointer The systems passively inject water into corium from below. Black-Right-Pointing-Pointer These systems cool corium much faster than top flooding. - Abstract: The coolability of ex-vessel core debris continues to be an issue of concern in the realm of light water reactor safety. Extensive research into corium/concrete interaction phenomena has been unable to establish the certainty of melt quench and stabilization within the containment boundary for all credible cases of cooling restricted to top flooding. As a result, there has been continuing interest in engineered systems that can augment cooling. This paper describes the testing of two passive cooling concepts that inject water into corium from below via nozzles embedded within the basemat: one with porous concrete nozzles and the other with a type of composite nozzle. The latter supplements water injection with noncondensable gas to stabilize flow and suppress vapor explosions. Each test involved a 136 kg melt composed of 56/23/14 wt% UO{sub 2}/ZrO{sub 2}/siliceous concrete at an initial depth of 30 cm. The setup with the porous concrete nozzles successfully injected water into the melt at heads as low as 2.3 m. The composite nozzle test was partially successful, with three nozzles delivering coolant while a fourth was damaged by the melt and failed to inject water. The melts cooled twice as fast as similar ones tested in a top flooding configuration. These experiments confirmed earlier work at Forschungszentrum Karlsruhe and elsewhere indicating that cooling via bottom water injection is a particularly effective method for quenching ex-vessel corium melts.

  4. Energy penalty analysis of possible cooling water intake structurerequirements on existing coal-fired power plants.

    Energy Technology Data Exchange (ETDEWEB)

    Veil, J. A.; Littleton, D. J.; Gross, R. W.; Smith, D. N.; Parsons, E.L., Jr.; Shelton, W. W.; Feeley, T. J.; McGurl, G. V.

    2006-11-27

    Section 316(b) of the Clean Water Act requires that cooling water intake structures must reflect the best technology available for minimizing adverse environmental impact. Many existing power plants in the United States utilize once-through cooling systems to condense steam. Once-through systems withdraw large volumes (often hundreds of millions of gallons per day) of water from surface water bodies. As the water is withdrawn, fish and other aquatic organisms can be trapped against the screens or other parts of the intake structure (impingement) or if small enough, can pass through the intake structure and be transported through the cooling system to the condenser (entrainment). Both of these processes can injure or kill the organisms. EPA adopted 316(b) regulations for new facilities (Phase I) on December 18, 2001. Under the final rule, most new facilities could be expected to install recirculating cooling systems, primarily wet cooling towers. The EPA Administrator signed proposed 316(b) regulations for existing facilities (Phase II) on February 28, 2002. The lead option in this proposal would allow most existing facilities to achieve compliance without requiring them to convert once-through cooling systems to recirculating systems. However, one of the alternate options being proposed would require recirculating cooling in selected plants. EPA is considering various options to determine best technology available. Among the options under consideration are wet-cooling towers and dry-cooling towers. Both types of towers are considered to be part of recirculating cooling systems, in which the cooling water is continuously recycled from the condenser, where it absorbs heat by cooling and condensing steam, to the tower, where it rejects heat to the atmosphere before returning to the condenser. Some water is lost to evaporation (wet tower only) and other water is removed from the recirculating system as a blow down stream to control the building up of suspended and

  5. Radiant Heating and Cooling Systems. Part two

    DEFF Research Database (Denmark)

    Kim, Kwan Woo; Olesen, Bjarne W.

    2015-01-01

    Control of the heating and cooling system needs to be able to maintain the indoor temperatures within the comfort range under the varying internal loads and external climates. To maintain a stable thermal environment, the control system needs to maintain the balance between the heat gain...

  6. Engine room cooling system using jet pump

    Energy Technology Data Exchange (ETDEWEB)

    Lim, J.W.; Lee, S.H. [Daewoo Heavy Industries Ltd. (Korea)

    2000-04-01

    Construction machinery includes an engine enclosure separated from a cooling system enclosure by a wall to reduce noise and advance cooling system performance. For this structure, however, the axial fan cannot be of benefit to the engine room, and so the temperature rise in the engine room makes several bad conditions. This paper proposes that hot air in engine room is evacuated by secondary pipe using jet pump. This paper demonstrates the structure and the effect of jet pump and useful guideline on design of area, length, and shape of secondary pipe to maximize the effect of jet pump. (author). 4 refs., 7 figs., 5 tabs.

  7. The ATLAS IBL CO2 Cooling System

    CERN Document Server

    Verlaat, Bartholomeus; The ATLAS collaboration

    2016-01-01

    The ATLAS Pixel detector has been equipped with an extra B-layer in the space obtained by a reduced beam pipe. This new pixel detector called the ATLAS Insertable B-Layer (IBL) is installed in 2014 and is operational in the current ATLAS data taking. The IBL detector is cooled with evaporative CO2 and is the first of its kind in ATLAS. The ATLAS IBL CO2 cooling system is designed for lower temperature operation (<-35⁰C) than the previous developed CO2 cooling systems in High Energy Physics experiments. The cold temperatures are required to protect the pixel sensors for the high expected radiation dose up to 550 fb^-1 integrated luminosity.

  8. Gemini helium closed cycle cooling system

    Science.gov (United States)

    Lazo, Manuel; Galvez, Ramon; Rogers, Rolando; Solis, Hernan; Tapia, Eduardo; Maltes, Diego; Collins, Paul; White, John; Cavedoni, Chas; Yamasaki, Chris; Sheehan, Michael P.; Walls, Brian

    2008-07-01

    The Gemini Observatory presents the Helium Closed Cycle Cooling System that provides cooling capacity at cryogenic temperatures for instruments and detectors. It is implemented by running three independent helium closed cycle cooling circuits with several banks of compressors in parallel to continuously supply high purity helium gas to cryocoolers located about 100-120 meters apart. This poster describes how the system has been implemented, the required helium pressures and gas flow to reach cryogenic temperature, the performance it has achieved, the helium compressors and cryocoolers in use and the level of vibration the cryocoolers produce in the telescope environment. The poster also describes the new technology for cryocoolers that Gemini is considering in the development of new instruments.

  9. Operational cost minimization in cooling water systems

    Directory of Open Access Journals (Sweden)

    Castro M.M.

    2000-01-01

    Full Text Available In this work, an optimization model that considers thermal and hydraulic interactions is developed for a cooling water system. It is a closed loop consisting of a cooling tower unit, circulation pump, blower and heat exchanger-pipe network. Aside from process disturbances, climatic fluctuations are considered. Model constraints include relations concerning tower performance, air flowrate requirement, make-up flowrate, circulating pump performance, heat load in each cooler, pressure drop constraints and climatic conditions. The objective function is operating cost minimization. Optimization variables are air flowrate, forced water withdrawal upstream the tower, and valve adjustment in each branch. It is found that the most significant operating cost is related to electricity. However, for cooled water temperatures lower than a specific target, there must be a forced withdrawal of circulating water and further makeup to enhance the cooling tower capacity. Additionally, the system is optimized along the months. The results corroborate the fact that the most important variable on cooling tower performance is not the air temperature itself, but its humidity.

  10. Analysis of pumping systems to large flows of cooling water in power plants; Analisis de sistemas de bombeo para grandes flujos de agua de enfriamiento en centrales termoelectricas

    Energy Technology Data Exchange (ETDEWEB)

    Sanchez Sanchez, Ramon; Herrera Velarde, Jose Ramon; Gonzalez Sanchez, Angel [Instituto de Investigaciones Electricas, Cuernavaca, Morelos (Mexico)]. E-mail: rsanchez@iie.org.mx; jrhv@iie.org.mx; ags@iie.org.mx

    2010-11-15

    Accurate measurement of large water flows remains being a challenge in the problems of implementation of circulating water systems of power plants and other applications. This paper, presents a methodology for the analysis in pumping systems with high rates of water in power plants, as well as their practical application and results in pipelines water flow of a thermoelectrical power plant of 350 MW. In this power plant, the water flow per pipeline for a half of condenser oscillates around 7 m{sup 3}/s (14 m{sup 3}/s per power generating unit). In this analysis, we present the techniques used to measure large flows of water with high accurately, as well as the computational model for water circulating system using PIPE FLO and the results of practical application techniques. [Spanish] La medicion precisa de grandes flujos de agua, sigue siendo un reto en los problemas de aplicacion de sistemas de agua de circulacion de centrales termoelectricas, entre otras aplicaciones. En este articulo, se presenta una metodologia para el analisis de sistemas de bombeo con grandes flujos de agua en centrales termoelectricas, asi como, su aplicacion practica y los resultados obtenidos en los ductos de agua de circulacion de una central generadora con unidades de 350 MW. En esta central, los flujos por caja de agua oscilan alrededor de los 7 m{sup 3}/s (14 m{sup 3}/s por unidad generadora). En el analisis, se presentan las tecnicas utilizadas para medir con precision grandes flujos de agua (tubo de Pitot), asi como, el modelado del sistema de agua de circulacion por medio de un paquete computacional (PIPE FLO) y resultados obtenidos de la aplicacion de dichas tecnicas.

  11. District heating and cooling systems for communities through power plant retrofit distribution network. Final report, September 1, 1978-May 31, 1979

    Energy Technology Data Exchange (ETDEWEB)

    None

    1979-10-01

    This Final Report (Volume 2) of Phase 1 of District Heating for Communities Through Power Plant Retrofit Distribution Network contains 3 tasks: (1) Demonstration Team; (2) Identify Thermal Energy Sources and Potential Service Areas; and (3) Energy Market Analysis. Task 2 consists of estimating the thermal load within 5 and 10 miles of Public Service Electric and Gas Company steam power plants, Newark, New Jersey; estimating the costs of supplying thermal services to thermal loads of varying densities; a best case economic analysis of district heating for single-family homes; and some general comments on district-heating system design and development. Task 3 established the potential market for district heating that exists within a 5-mile radius of the selected generating stations; a sample of the questionnaire sent to the customers are shown. (MCW)

  12. Description and cost analysis of a deluge dry/wet cooling system.

    Energy Technology Data Exchange (ETDEWEB)

    Wiles, L.E.; Bamberger, J.A.; Braun, D.J.; Braun, D.J.; Faletti, D.W.; Willingham, C.E.

    1978-06-01

    The use of combined dry/wet cooling systems for large base-load power plants offers the potential for significant water savings as compared to evaporatively cooled power plants and significant cost savings in comparison to dry cooled power plants. The results of a detailed engineering and cost study of one type of dry/wet cooling system are described. In the ''deluge'' dry/wet cooling method, a finned-tube heat exchanger is designed to operate in the dry mode up to a given ambient temperature. To avoid the degradation of performance for higher ambient temperatures, water (the delugeate) is distributed over a portion of the heat exchanger surface to enhance the cooling process by evaporation. The deluge system used in this study is termed the HOETERV system. The HOETERV deluge system uses a horizontal-tube, vertical-plate-finned heat exchanger. The delugeate is distributed at the top of the heat exchanger and is allowed to fall by gravity in a thin film on the face of the plate fin. Ammonia is used as the indirect heat transfer medium between the turbine exhaust steam and the ambient air. Steam is condensed by boiling ammonia in a condenser/reboiler. The ammonia is condensed in the heat exchanger by inducing airflow over the plate fins. Various design parameters of the cooling system have been studied to evaluate their impact on the optimum cooling system design and the power-plant/utility-system interface. Annual water availability was the most significant design parameter. Others included site meteorology, heat exchanger configuration and air flow, number and size of towers, fan system design, and turbine operation. It was concluded from this study that the HOETERV deluge system of dry/wet cooling, using ammonia as an intermediate heat transfer medium, offers the potential for significant cost savings compared with all-dry cooling, while achieving substantially reduced water consumption as compared to an evaporatively cooled power plant. (LCL)

  13. Pressure shock analyses in a power plant cooling system and a hydraulic stowing system in a potassium mine; Druckstossanalysen am Beispiel eines Kraftwerkskuehlsystems und einer Spuelversatzanlage im Kalibergbau

    Energy Technology Data Exchange (ETDEWEB)

    Lange, H. [Babcock Borsig Power Service GmbH, Oberhausen (Germany)

    2000-07-01

    Pressure shocks in pipeline systems are caused by acceleration or delaying of fluid flow. They depend on the acceleration or delay rate, the medium density, and the local sound velocity with which the pressure waves propagate. Pressure shocks cause dynamic external loads which may cause damage to pipes, connections or supports and should therefore precalculated already in the planning stage in order to prevent damage. The contribution shows how precalculation of the flow data in a complex, meshed pipeline system will help to optimize the sytem and to maintain its integrity in case of pressure shocks. [German] Druckstoesse in Leitungssystemen werden erzeugt, wenn ein Fluid beschleunigt oder abgebremst (verzoegert wird). Die Groesse dieser Druckstoesse haengt von der Verzoegerung (Beschleunigung) deren Mediumsdichte sowie von der oertlichen Schallgeschwindigkeit ab mit der sich diese Druckwellen fortpflanzen. Druckstoesse bewirken nicht nur eine kurzzeitige Druckaenderung im System, sondern erzeugen dynamische aeussere Lasten, die erhebliche Groessen annehmen und fuer diverse Schaeden an Leitungen, Anschluessen oder Unterstuetzungen verantwortlich sein koennen. Daher ist die Berechnung im voraus wuenschenswert und notwendig, um schon in der Planung entsprechende konstruktive Massnahmen einfliessen zu lassen, damit keine Ueberbeanspruchung des Systems eintreten kann. In den vorliegenden Analysen wird gezeigt, dass fuer ein komplexes, vermaschtes Rohrleitungssystem mit Rueckschlagklappen und Pumpen bei Pumpenausfall durch Vorausberechnungen der Stroemungsdaten, wie Massenstroeme, Stroemungsgeschwindigkeiten, Druecke usw., fuer verschiedene Lastfaelle eine Systemoptimierung durchgefuehrt werden kann. Ausserdem wird gezeigt, dass durch geeignete Massnahmen bei einer Spuelversatzanlage der Druckstoss so abgemindert werden kann, dass die Integritaet des Systems gewaehrleistet wird. (orig.)

  14. for an Internal Cooling Air System

    Directory of Open Access Journals (Sweden)

    Tadaharu Kishibe

    2000-01-01

    Full Text Available The swirling flow field in an internal cooling air system in which the fluid passes through an inducer, a hollow turbine shaft, and a cavity between two disks (referred to as a wheel space is solved using computational fluid dynamics and the pressure fluctuations on the hollow shaft wall surface are measured.

  15. Turbine airfoil with laterally extending snubber having internal cooling system

    Science.gov (United States)

    Scribner, Carmen Andrew; Messmann, Stephen John; Marsh, Jan H.

    2016-09-06

    A turbine airfoil usable in a turbine engine and having at least one snubber with a snubber cooling system positioned therein and in communication with an airfoil cooling system is disclosed. The snubber may extend from the outer housing of the airfoil toward an adjacent turbine airfoil positioned within a row of airfoils. The snubber cooling system may include an inner cooling channel separated from an outer cooling channel by an inner wall. The inner wall may include a plurality of impingement cooling orifices that direct impingement fluid against an outer wall defining the outer cooling channel. In one embodiment, the cooling fluids may be exhausted from the snubber, and in another embodiment, the cooling fluids may be returned to the airfoil cooling system. Flow guides may be positioned in the outer cooling channel, which may reduce cross-flow by the impingement orifices, thereby increasing effectiveness.

  16. Investigation of the Use of Absorption Cooling Cycles to Reduce the Amount of Cooling Water Needed for Power Plants.

    Energy Technology Data Exchange (ETDEWEB)

    Middleton, Bobby D. [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States)

    2016-11-01

    This report outlines a preliminary study on the feasibility of using absorption cooling technology to cool thermoelectric power plants. Water availability is becoming more important in the production of energy throughout the world, especially in thermoelectric power generation. Currently, thermoelectric power generation accounts for about 48% of all water withdrawals in the United States. Rising population, increasing e lectricity use per capita, and decreasing water reserves threaten the availability of water for use in cooling power plants. To this end, Sandia National Laboratories has begun an initiative to find ways to increase the water use efficiency of power plants . In 2016, the New Mexico Small Business Association funded a project whereby Sandia would complete a preliminary assessment of the viability of utilizing absorption cooling technologies to aid in cooling thermoelectric power plants, thereby decreasing the amount of water required to generate electricity. This project was proposed by Thales Energy, a small business located in Albuquerque, NM. Due to time and money constraints, only a preliminary analysis was performed. The results indicate that the use of a bsorption cooling technologies is scientifically feasible and that, with more engineering analysis, may be economically feasible for some power plants, dependent upon local environmental conditions and the price currently being paid for cooling water by th e plant.

  17. On synthesis and optimization of cooling water systems with multiple cooling towers

    CSIR Research Space (South Africa)

    Gololo, KV

    2011-01-01

    Full Text Available research on cooling water systems has focused mainly on heat exchanger network thus excluding the interaction between heat exchanger network and the cooling towers. This paper presents a technique for grassroot design of cooling water system for wastewater...

  18. Preliminary Study of Solar Chimney Assisted Cooling System for SMART

    Energy Technology Data Exchange (ETDEWEB)

    Lee, Byung Il; Park, Seong Jun; Lee, Young Hyeon; Park, Hyo Chan; Park, Youn Won [BEES Inc., KAIST, Daejeon (Korea, Republic of)

    2016-05-15

    In this paper, the possibility of application for a complete passive final heat removal system using a solar chimney power plant for SMART NPP was estimated. Additionally the size of the cooling system was approximately calculated under the some assumptions. In order to estimate the applicability of SCPP as a complete passive secondary cooling system for SMART, we try to calculate the size of heat exchanger and simulate SCPP performance. As a result, it was found that SCPP could be coupled with SMART and some of waste heat could be recovered into electricity without any change in SCPP size. The related all parameters satisfying the constraint of the final heat removal system for SMART were calculated. Using the constraint of the amount of heat to be removed from SMART, two kinds of SCPP performances were analyzed; one for a stand alone SCPP in Fig 8(a) and second for SCPP with SMART in Fig 8(b)

  19. Overview of issues affecting the demand for dry and wet/dry cooling for thermal power plants

    Energy Technology Data Exchange (ETDEWEB)

    Hendrickson, P.L.

    1978-09-01

    The Dry Cooling Enhancement Program was initiated to: develop economic and performance models for cost optimization of total heat rejection systems using dry and dry/wet cooling; analyze and disseminate operating experience on existing dry-cooled plant performance; and demonstrate certain features of existing technology equipment to provide confidence for specification by utilities. The ultimate objective was to promote water conservation through industry use of dry cooling by developing and demonstrating the reliability of lower-cost systems. The economic, legal, and water availability factors that will contribute to future selection of dry and wet/dry cooling and thus influence the projected market for these types of cooling systems in the next 20 years are considered.

  20. Cooling Efficiency of Laminar Cooling System for Plate Mill

    Institute of Scientific and Technical Information of China (English)

    ZHANG Dian-hua; WANG Bing-xing; ZHOU Na; YU Ming; WANG Jun

    2008-01-01

    Heat transfer was researched from a perspective of the industry application.On the basis of the first law of thermodynamics,the cooling efficiency was deduced from the change of enthalpy inside hot plate.The relationship between the cooling efficiency and its influencing parameters was regressed from plenty of data collected from the worksite and discussed in detail.The temperature profiles resulting from the online model and the model modified by regressed formulas were presented and compared.The results indicated that the control accuracy of the modified model was increased obviously.

  1. Cooling system having dual suction port compressor

    Energy Technology Data Exchange (ETDEWEB)

    Wu, Guolian

    2017-08-29

    A cooling system for appliances, air conditioners, and other spaces includes a compressor, and a condenser that receives refrigerant from the compressor. The system also includes an evaporator that receives refrigerant from the condenser. Refrigerant received from the condenser flows through an upstream portion of the evaporator. A first portion of the refrigerant flows to the compressor without passing through a downstream portion of the evaporator, and a second portion of the refrigerant from the upstream portion of the condenser flows through the downstream portion of the evaporator after passing through the upstream portion of the evaporator. The second portion of the refrigerant flows to the compressor after passing through the downstream portion of the evaporator. The refrigeration system may be configured to cool an appliance such as a refrigerator and/or freezer, or it may be utilized in air conditioners for buildings, motor vehicles, or other such spaces.

  2. Cogen-absorption plants for refrigeration purposes and turbine air inlet cooling

    Energy Technology Data Exchange (ETDEWEB)

    Langreck, Juergen [Colibri bv (Netherlands)

    2000-04-01

    Most cogeneration systems produce power and heat but with absorption refrigeration plants (ARP) the products are power and 'cold'. An ARP driven by heat from a turbine exhaust can provide the cooling for the inlet air with very low consumption of electricity, consequently there is a significant increase in power output from the cogeneration unit. Two different ARP systems are currently available but the author describes only the ammonia-water system, which can achieve temperatures down to -60 degrees C. The article discusses the principle behind ARP, the capital cost and returns on investment, how the cogeneration plant is linked to the ARP, ARP for turbine inlet air cooling, and the potential applications of cogeneration-ARP.

  3. A study on cooling efficiency using 1-d analysis code suitable for cooling system of thermoforming

    Energy Technology Data Exchange (ETDEWEB)

    Li, Zhen Zhe; Heo, Kwang Su; Xuan, Dong Ji; Seol, Seoung Yun [Chonnam National University, Gwangju (Korea, Republic of)

    2009-03-15

    Thermoforming is one of the most versatile and economical processes available for polymer products, but cycle time and production cost must be continuously reduced in order to improve the competitive power of products. In this study, water spray cooling was simulated to apply to a cooling system instead of compressed air cooling in order to shorten the cycle time and reduce the cost of compressed air used in the cooling process. At first, cooling time using compressed air was predicted in order to check the state of mass production. In the following step, the ratio of removed energy by air cooling or water spray cooling among the total removed energy was found by using 1-D analysis code of the cooling system under the condition of checking the possibility of conversion from 2-D to 1-D problem. The analysis results using water spray cooling show that cycle time can be reduced because of high cooling efficiency of water spray, and cost of production caused by using compressed air can be reduced by decreasing the amount of the used compressed air. The 1-D analysis code can be widely used in the design of a thermoforming cooling system, and parameters of the thermoforming process can be modified based on the recommended data suitable for a cooling system of thermoforming

  4. 中水在炼油循环冷却水系统中的应用%The Application of Water Reused into Circulating Cooling Water System in Oil Refining Plant

    Institute of Scientific and Technical Information of China (English)

    高建权; 刘丽娜; 王炜; 魏志朝

    2011-01-01

    The characteristics and effects of recycled water reusing as circulating cooling water for oil refining plants were analyzed.The results of corrosion and scale inhibitor experiment indicated that the water treatment agents for recycled water can inhibit the corrosion and scale completely.After eight months' system optimization and industrial application,the circulating cooling system was still in good working order with five ratio cyele of concentration or more.%分析了中水作为炼油循环冷却水系统补水的特点及对循环水系统的影响。缓蚀和阻垢实验结果表明,中水回用水处理剂完全可以有效控制系统的腐蚀和结垢。经过8个月的不断优化和工业运行,系统在浓缩倍数为5以上的情况下,运行状况良好。

  5. 核电循环冷却水一氯胺反应动力学规律%Research on kinetic of monochloramine in circulating cooling water system of nuclear power plant

    Institute of Scientific and Technical Information of China (English)

    赫俊国; 刘剑; 王胜龙; JosephDELAAT; FlorenceBERNE; 崔崇威

    2011-01-01

    Desinfection of cooling water system of nuclear plant is the research focus for nuclear power sys- tems. With the circulating cooling water module from Dampierre nuclear plant in France, we study the kinetic of consumption of monoehloramine as a desinfeet and determine that the consumption of monochloramine with raw water is the first-order kinetic reaction, and the rate constant is 0. 002 min - 1. The analysis of consumption of monochloramine with Fe3 + added in shows that, the Fe3+ has no significant effect on the consumption of monochloramine. The results can provide technical support and guidance for the design and management of nu- clear power plants in China.%核电站循环冷却水系统的消毒是核电水系统的研究重点.以法国丹皮尔核电站冷却塔模型为研究对象,进行一氯胺消毒剂的消耗动力学研究,确定以天然原水为循环水介质的一氯胺消耗动力学符合一级反应的动力学模型,其反应速率常数为0.002min^-1;以人工模拟投加Fe^3+进行一氯胺消耗分析表明,Fe^3+对一氯胺的消耗无显著影响.

  6. Simulation on Cooling System of Automotive Waste Heat Thermoelectric Generator

    Directory of Open Access Journals (Sweden)

    Xiaohong Yuan

    2013-06-01

    Full Text Available The cooling system of automobile waste heat Thermoelectric Generator (TEG is researched in the study. Integrated model of cooling system and vehicle is built based on GT-Cool, analysis of the different cooling ways shows that when using independent cooling system, the ratio between power consumption and output is high and system performance is poor; By using integrated cooling system, the expectation of keep constant engine warm up time and synchronous change of water temperature between different tanks is realized after water tanks are improved.

  7. Progress of the Water Cooling System for CYCIAE-100

    Institute of Scientific and Technical Information of China (English)

    LI; Zhen-guo; WU; Long-cheng; LIU; Geng-guo

    2013-01-01

    The water cooling system for CYCIAE-100 has achieved a significant progress in 2013,its progress can be summarized as follows:1)The deionized water production equipment and the main circulating water cooling unit are installed and tested.2)The circulating water cooling unit for high power target and circulating water cooling unit for vacuum helium compressor are installed and tested.

  8. Low pressure cooling seal system for a gas turbine engine

    Science.gov (United States)

    Marra, John J

    2014-04-01

    A low pressure cooling system for a turbine engine for directing cooling fluids at low pressure, such as at ambient pressure, through at least one cooling fluid supply channel and into a cooling fluid mixing chamber positioned immediately downstream from a row of turbine blades extending radially outward from a rotor assembly to prevent ingestion of hot gases into internal aspects of the rotor assembly. The low pressure cooling system may also include at least one bleed channel that may extend through the rotor assembly and exhaust cooling fluids into the cooling fluid mixing chamber to seal a gap between rotational turbine blades and a downstream, stationary turbine component. Use of ambient pressure cooling fluids by the low pressure cooling system results in tremendous efficiencies by eliminating the need for pressurized cooling fluids for sealing this gap.

  9. Controlled cooling of an electronic system based on projected conditions

    Science.gov (United States)

    David, Milnes P.; Iyengar, Madhusudan K.; Schmidt, Roger R.

    2016-05-17

    Energy efficient control of a cooling system cooling an electronic system is provided based, in part, on projected conditions. The control includes automatically determining an adjusted control setting(s) for an adjustable cooling component(s) of the cooling system. The automatically determining is based, at least in part, on projected power consumed by the electronic system at a future time and projected temperature at the future time of a heat sink to which heat extracted is rejected. The automatically determining operates to reduce power consumption of the cooling system and/or the electronic system while ensuring that at least one targeted temperature associated with the cooling system or the electronic system is within a desired range. The automatically determining may be based, at least in part, on an experimentally obtained model(s) relating the targeted temperature and power consumption of the adjustable cooling component(s) of the cooling system.

  10. Controlled cooling of an electronic system based on projected conditions

    Energy Technology Data Exchange (ETDEWEB)

    David, Milnes P.; Iyengar, Madhusudan K.; Schmidt, Roger R.

    2015-08-18

    Energy efficient control of a cooling system cooling an electronic system is provided based, in part, on projected conditions. The control includes automatically determining an adjusted control setting(s) for an adjustable cooling component(s) of the cooling system. The automatically determining is based, at least in part, on projected power consumed by the electronic system at a future time and projected temperature at the future time of a heat sink to which heat extracted is rejected. The automatically determining operates to reduce power consumption of the cooling system and/or the electronic system while ensuring that at least one targeted temperature associated with the cooling system or the electronic system is within a desired range. The automatically determining may be based, at least in part, on an experimentally obtained model(s) relating the targeted temperature and power consumption of the adjustable cooling component(s) of the cooling system.

  11. Ice Thermal Storage Systems for LWR Supplemental Cooling and Peak Power Shifting

    Energy Technology Data Exchange (ETDEWEB)

    Haihua Zhao; Hongbin Zhang; Phil Sharpe; Blaise Hamanaka; Wei Yan; WoonSeong Jeong

    2010-06-01

    Availability of enough cooling water has been one of the major issues for the nuclear power plant site selection. Cooling water issues have frequently disrupted the normal operation at some nuclear power plants during heat waves and long draught. The issues become more severe due to the new round of nuclear power expansion and global warming. During hot summer days, cooling water leaving a power plant may become too hot to threaten aquatic life so that environmental regulations may force the plant to reduce power output or even temporarily to be shutdown. For new nuclear power plants to be built at areas without enough cooling water, dry cooling can be used to remove waste heat directly into the atmosphere. However, dry cooling will result in much lower thermal efficiency when the weather is hot. One potential solution for the above mentioned issues is to use ice thermal storage systems (ITS) that reduce cooling water requirements and boost the plant’s thermal efficiency in hot hours. ITS uses cheap off-peak electricity to make ice and uses those ice for supplemental cooling during peak demand time. ITS is suitable for supplemental cooling storage due to its very high energy storage density. ITS also provides a way to shift large amount of electricity from off peak time to peak time. Some gas turbine plants already use ITS to increase thermal efficiency during peak hours in summer. ITSs have also been widely used for building cooling to save energy cost. Among three cooling methods for LWR applications: once-through, wet cooling tower, and dry cooling tower, once-through cooling plants near a large water body like an ocean or a large lake and wet cooling plants can maintain the designed turbine backpressure (or condensation temperature) during 99% of the time; therefore, adding ITS to those plants will not generate large benefits. For once-through cooling plants near a limited water body like a river or a small lake, adding ITS can bring significant economic

  12. Open cycle cooling systems using solar energy

    Energy Technology Data Exchange (ETDEWEB)

    Lazzarin, R.; Sovrano, M.

    Open cycle cooling systems are particularly suitable for utilizing solar energy. In all these systems the adsorption and absorption phenomena are very important, hence they are described separately. The cycles used are essentially two: the Baum-Kakabaev cycle using liquid absorbers and the dehumidification/humidification cycle where also adsorbent substances can be utilized. Solar energy is used in the regeneration process of dehumidifying substances. Reactivation modes can be various: suitability of one mode or the other can depend on the climate of the site where the system is installed.

  13. Radiant Heating and Cooling Systems. Part one

    DEFF Research Database (Denmark)

    Kim, Kwan Woo; Olesen, Bjarne W.

    2015-01-01

    The use of radiant heating systems has several thousand years of history.1,2 The early stage of radiant system application was for heating purposes, where hot air from flue gas (cooking, fires) was circulated under floors or in walls. After the introduction of plastic piping water-based radiant...... heating and cooling with pipes embedded in room surfaces (floor, wall, and ceiling), the application increased significantly worldwide. Earlier application of radiant heating systems was mainly for residential buildings because of its comfort and free use of floor space without any obstruction from...

  14. Conceptual design of advanced central receiver power systems sodium-cooled receiver concept. Volume 2, Book 1. Commercial plant conceptual design. Final report

    Energy Technology Data Exchange (ETDEWEB)

    1979-03-01

    The conceptual design of the 100-MW solar tower focus commercial power plant is described in detail. Sodium is pumped up to the top of a tall tower where the receiver is located. The sodium is heated in the receiver and then flows down the tower, through a pressure reducing device, and thence into a large, hot storage tank which is located at ground level and whose size is made to meet a specific thermal energy storage capacity requirement. From this tank, the sodium is pumped by a separate pump, through a system of sodium-to-water steam generators. The steam generator system consists of a separate superheater and reheater operating in parallel and an evaporator unit operating in series with the other two units. The sodium flowing from the evaporator unit is piped to a cold storage tank. From the cold storage tank, sodium is then pumped up to the tip of the tower to complete the cycle. The steam generated in the steam generators is fed to a conventional off-the-shelf, high-efficiency turbine. The steam loop operates in a conventional rankine cycle with the steam generators serving the same purpose as a conventional boiler and water being fed to the evaporator with conventional feedwater pumps. The pressure reducing device (a standard drag valve, for example) serves to mitigate the pressure caused by the static head of sodium and thus allows the large tanks to operate at ambient pressure conditions. (WHK)

  15. Optimal Environmental Performance of Water-cooled Chiller System with All Variable Speed Configurations

    Science.gov (United States)

    Yu, Fu Wing; Chan, Kwok Tai

    This study investigates how the environmental performance of water-cooled chiller systems can be optimized by applying load-based speed control to all the system components. New chiller and cooling tower models were developed using a transient systems simulation program called TRNSYS 15 in order to assess the electricity and water consumption of a chiller plant operating for a building cooling load profile. The chiller model was calibrated using manufacturer's performance data and used to analyze the coefficient of performance when the design and control of chiller components are changed. The NTU-effectiveness approach was used for the cooling tower model to consider the heat transfer effectiveness at various air-to-water flow ratios and to identify the makeup water rate. Applying load-based speed control to the cooling tower fans and pumps could save an annual plant operating cost by around 15% relative to an equivalent system with constant speed configurations.

  16. Computational Fluid Dynamics Analysis of Very High Temperature Gas-Cooled Reactor Cavity Cooling System

    Energy Technology Data Exchange (ETDEWEB)

    Frisani, Angelo; Hassan, Yassin A; Ugaz, Victor M

    2010-11-02

    The design of passive heat removal systems is one of the main concerns for the modular very high temperature gas-cooled reactors (VHTR) vessel cavity. The reactor cavity cooling system (RCCS) is a key heat removal system during normal and off-normal conditions. The design and validation of the RCCS is necessary to demonstrate that VHTRs can survive to the postulated accidents. The computational fluid dynamics (CFD) STAR-CCM+/V3.06.006 code was used for three-dimensional system modeling and analysis of the RCCS. A CFD model was developed to analyze heat exchange in the RCCS. The model incorporates a 180-deg section resembling the VHTR RCCS experimentally reproduced in a laboratory-scale test facility at Texas A&M University. All the key features of the experimental facility were taken into account during the numerical simulations. The objective of the present work was to benchmark CFD tools against experimental data addressing the behavior of the RCCS following accident conditions. Two cooling fluids (i.e., water and air) were considered to test the capability of maintaining the RCCS concrete walls' temperature below design limits. Different temperature profiles at the reactor pressure vessel (RPV) wall obtained from the experimental facility were used as boundary conditions in the numerical analyses to simulate VHTR transient evolution during accident scenarios. Mesh convergence was achieved with an intensive parametric study of the two different cooling configurations and selected boundary conditions. To test the effect of turbulence modeling on the RCCS heat exchange, predictions using several different turbulence models and near-wall treatments were evaluated and compared. The comparison among the different turbulence models analyzed showed satisfactory agreement for the temperature distribution inside the RCCS cavity medium and at the standpipes walls. For such a complicated geometry and flow conditions, the tested turbulence models demonstrated that the

  17. Utilization of municipal wastewater for cooling in thermoelectric power plants

    Energy Technology Data Exchange (ETDEWEB)

    Safari, Iman [Illinois Inst. of Technology, Chicago, IL (United States); Walker, Michael E. [Illinois Inst. of Technology, Chicago, IL (United States); Hsieh, Ming-Kai [Carnegie Mellon Univ., Pittsburgh, PA (United States); Dzombak, David A. [Carnegie Mellon Univ., Pittsburgh, PA (United States); Liu, Wenshi [Univ. of Pittsburgh, PA (United States); Vidic, Radisav D. [Univ. of Pittsburgh, PA (United States); Miller, David C. [National Energy Technology Lab. (NETL), Morgantown, WV (United States); Abbasian, Javad [Illinois Inst. of Technology, Chicago, IL (United States)

    2013-09-01

    A process simulation model has been developed using Aspen Plus® with the OLI (OLI System, Inc.) water chemistry model to predict water quality in the recirculating cooling loop utilizing secondary- and tertiary-treated municipal wastewater as the source of makeup water. Simulation results were compared with pilot-scale experimental data on makeup water alkalinity, loop pH, and ammonia evaporation. The effects of various parameters including makeup water quality, salt formation, NH3 and CO2 evaporation mass transfer coefficients, heat load, and operating temperatures were investigated. The results indicate that, although the simulation model can capture the general trends in the loop pH, experimental data on the rates of salt precipitation in the system are needed for more accurate prediction of the loop pH. It was also found that stripping of ammonia and carbon dioxide in the cooling tower can influence the cooling loop pH significantly. The effects of the NH3 mass transfer coefficient on cooling loop pH appear to be more significant at lower values (e.g., kNH3 < 4×10-3 m/s) when the makeup water alkalinity is low (e.g., <90 mg/L as CaCO3). The effect of the CO2 mass transfer coefficient was found to be significant only at lower alkalinity values (e.g., kCO2<4×10-6 m/s).

  18. France uses the sun to cool its wine: the Banyuls winery solar cooling system

    Energy Technology Data Exchange (ETDEWEB)

    Anon.

    2003-12-01

    The engineering consultancy Tecsol was asked to design a cooling system for a winery that would limit the variations in temperature during the year. Tecsol proposed a solar system. The total investment cost amounted to nearly two million French Francs (300,000 euros), almost double the cost of a conventional air-conditioning system. However, because the solar system reduced the conventional energy needs of the warehouse by about 40%, the French Agency for Environment and Energy Management (ADEME) provided a 37% subsidy for its rational use of energy. The 'Solarclim' solar installation has three functions: it produces hot water via 693 vacuum tube collectors with a useful surface of 130 m{sup 2}. The collectors are fixed to the roof of the wine cellar, which has an angle of 15 deg. Heat from the collectors is transferred to a 1000-litre hot water storage tank; it produces chilled water using a lithium bromide absorption plant with a nominal cooling capacity of 52 kW. This is housed in the technical premises on the lowest level and is used in conjunction with a 180 kW open-circuit cooling tower on the north facade; and the third function combines air-conditioning and, when necessary, space heating. The installation has been operating for 12 years with no particular problems. The equipment is environmentally friendly. The solar heat source avoids CO{sub 2} emissions, the absorption machine does not use CFCs or HCFCs, and the system is totally silent. (UK)

  19. The Selection of Cooling Systems of Giant Hydro-Generators

    Institute of Scientific and Technical Information of China (English)

    2010-01-01

    The selection of cooling system for hydro-generator in Ertan Hydropower Station is reviewed in this paper. The new viewpoint on air-cooled system of hydraulic generator of recent years is analyzed and described. That is, "Full air-cooled system is always preferred to inner

  20. District heating and cooling systems for communities through power plant retrofit distribution network. Phase 2. Final report, 1 March 1980-31 January 1984. Volume VII. Appendix C

    Energy Technology Data Exchange (ETDEWEB)

    1984-01-31

    This volume contains: Hudson No. 2 Limited Retrofit Cost Estimates provided by Stone and Webster Engineering Corp. (SWEC); backup data and basis of estimate for SWEC Heater Plant and Gas Turbine Plant (Kearny No. 12) cost estimates; and Appendices - Analysis of Relevant Tax Laws.

  1. Design and Transient Analysis of Passive Safety Cooling Systems for Advanced Nuclear Reactors

    OpenAIRE

    Galvez, Cristhian

    2011-01-01

    The Pebble Bed Advanced High Temperature Reactor (PB-AHTR) is a pebble fueled, liquid salt cooled, high temperature nuclear reactor design that can be used for electricity generation or other applications requiring the availability of heat at elevated temperatures. A stage in the design evolution of this plant requires the analysis of the plant during a variety of potential transients to understand the primary and safety cooling system response. This study focuses on the performance of the pa...

  2. Numerical Study on Flow and Heat Transfer Characteristics of Finned Tube Bundles for Air-cooled Heat Exchangers of Indirect Dry Cooling Systems in Power Plants%电站间冷系统空冷散热器翅片管束流动传热性能的数值研究

    Institute of Scientific and Technical Information of China (English)

    杨立军; 贾思宁; 卜永东; 杜小泽; 杨勇平

    2012-01-01

    空冷散热器为电站间接空冷系统的主要设备,研究空冷散热器翅片管束的流动传热特性,对于电站间冷系统的优化设计与高效运行具有重要意义.对间接空冷系统空冷散热器常用翅片管束流动传热性能进行了数值模拟研究,通过计算获得了空冷散热器冷却空气流动阻力和平均对流换热系数随迎面风速的变化规律,拟合得到了摩擦因子与努赛尔特数随雷诺数的变化关系.利用对流换热的综合性能评价标准(performance evaluation criteria,PEC),即Nu/f1/3,对6种翅片管束的流动传热性能进行了比较.结果表明,随迎面风速增加,空气对流换热增强,压降增加,翅片管的对流换热系数随之升高,摩擦因子降低,但是换热系数的增加幅度小于压降的增加幅度.Forgo型翅片管束综合流动传热性能优于椭圆型管束.本文研究结果为电站间冷系统空冷散热器的选型和优化设计提供了一定的理论依据.%Air-cooled heat exchanger is one of the main components of the indirect dry cooling system in a power plant. It is of benefit to the optimal design and operation of indirect dry cooling system to clarify the flow and heat transfer characteristics of air-cooled finned tube heat exchangers. The thermo-flow performances of the commonly used finned tube bundles in air-cooled heat exchangers were investigated by a numerical simulation. The variations of the flow resistance and average convection heat transfer coefficient of cooling air through the finned tube heat exchanger with the windward velocity were presented. The correlating equations of the friction factor versus Reynolds number, and the Nusselt number versus Reynolds number were fitted. On the basis of the performance evaluation criteria for convection heat transfer, the expression of Nu/f1/3 was applied to the thermo-flow performances prediction for six finned tube bundles. The results show that as the windward velocity increases

  3. 生活垃圾焚烧发电厂冷却系统节能分析%Energy-saving Analysis of Cooling System in Domestic Waste Incineration Plants

    Institute of Scientific and Technical Information of China (English)

    王颖; 刘云杰; 蒋金明

    2013-01-01

    The energy-saving design points of turbine cycle cooling tower in waste incineration plants were summarized.Combining with domestic waste incineration plants,its application in engineering design was introduced.%归纳了垃圾焚烧发电厂机力通风冷却塔的供电节能设计要点,结合生活垃圾焚烧发电厂,介绍其在工程设计中的应用.

  4. Recent trends in solar thermal sorption cooling system technology

    Directory of Open Access Journals (Sweden)

    Khaled M Bataineh

    2015-05-01

    Full Text Available Solar thermal cooling is the best alternative solution to overcome the problems associated with using nonrenewable resources. There are several thermal cooling methods developed differing from each other according to the thermodynamic cycle and type of refrigerant used. Recent developments in absorption and adsorption solar cooling systems are presented. Summarized thermodynamic modeling for both absorption and adsorption solar cooling systems is given. Brief thermal analysis among the types of solar collectors is presented. System efficiencies and optimization analysis are presented. The influences of geometrical, system configurations, and physical parameters on the performance of solar thermal sorption cooling system are investigated. The basis for the design of absorption and adsorption solar cooling systems is provided. Several case studies in different climatic conditions are presented. Economic feasibility for both systems is discussed. Comparison between the absorption and adsorption solar cooling system is summarized.

  5. Biofouling evaluation in the seawater cooling circuit of an operating coastal power plant

    Energy Technology Data Exchange (ETDEWEB)

    Murthy, P.S.; Veeramani, P.; Ershath, M.I.M.; Venugopalan, V.P. [BARC Facilities, Water and Steam Chemistry Div., Kalpakkam, Tamil Nadu (India)

    2010-07-01

    Chlorination is the most commonly used method of biofouling control in cooling water systems of coastal power stations. In the present study, we report results of extensive sampling in different sections of the cooling water system of an operating power station undertaken during three consecutive maintenance shutdowns. The power plant employed continuous low level chlorination (0.2 ± 0.1 mg L{sup -1} TRO) with twice-a-week booster dosing (0.4 ± 0.1 mg L-1 TRO for 8 hours). In addition, the process seawater heat exchangers received supplementary dosing of bromide treatment (0.2 ± 0.1 mg L{sup -1} TRO for 1 hour in every 8 h shift). Biofouling samples were collected from the cooling water conduits, heat exchanger water boxes, pipelines, heated discharge conduits and outfall section during the annual maintenance shutdown of the plant in the years 2007, 2008 and 2009. Simultaneous monitoring of biofouling on test coupons in coastal waters enabled direct comparison of fouling situation on test panels and that in the cooling system. The data showed significant reduction in biofouling inside the cooling circuit as compared to the coastal waters. However, significant amount of fouling was still evident at several places, indicating inadequacy of the biocide treatment regime. The maximum load of 31.3 kg m{sup 2} y{sup -1} was observed in the conduits leading to the process seawater heat exchangers (PSW-HX) and the minimum of 1.3 kg m{sup 2} y{sup -1} was observed in the outfall section. Fouling loads of 12.2 - 14.7 kg m{sup 2} y{sup -1} were observed in the concrete conduits feeding the main condensers. Bromide treatment ahead of the PSW-HX could marginally reduce the fouling load in the downstream section of the dosing point; the HX inlets still showed good biofouling. Species diversity across the cooling water system showed the pre-condenser section to be dominated by green mussels (Perna viridis), pearl oysters (Pinctada sp.) and edible oysters (Crassostrea sp

  6. mathematical model for direct evaporative space cooling systems

    African Journals Online (AJOL)

    eobe

    MATHEMATICAL MODEL FOR DIRECT EVAPORATIVE SPACE COOLING. SYSTEMS ... Water is the working fluid in evaporative cooling thus it is ..... co o lin g efficien cy (%. ) Time (hrs) predicted experimental. 0. 10. 20. 30. 40. 50. 60. 70. 80.

  7. Electromechanically cooled germanium radiation detector system

    Science.gov (United States)

    Lavietes, Anthony D.; Joseph Mauger, G.; Anderson, Eric H.

    1999-02-01

    We have successfully developed and fielded an electromechanically cooled germanium radiation detector (EMC-HPGe) at Lawrence Livermore National Laboratory (LLNL). This detector system was designed to provide optimum energy resolution, long lifetime, and extremely reliable operation for unattended and portable applications. For most analytical applications, high purity germanium (HPGe) detectors are the standard detectors of choice, providing an unsurpassed combination of high energy resolution performance and exceptional detection efficiency. Logistical difficulties associated with providing the required liquid nitrogen (LN) for cooling is the primary reason that these systems are found mainly in laboratories. The EMC-HPGe detector system described in this paper successfully provides HPGe detector performance in a portable instrument that allows for isotopic analysis in the field. It incorporates a unique active vibration control system that allows the use of a Sunpower Stirling cycle cryocooler unit without significant spectral degradation from microphonics. All standard isotopic analysis codes, including MGA and MGA++ [1], GAMANL [2], GRPANL [3]and MGAU [4], typically used with HPGe detectors can be used with this system with excellent results. Several national and international Safeguards organisations including the International Atomic Energy Agency (IAEA) and U.S. Department of Energy (DOE) have expressed interest in this system. The detector was combined with custom software and demonstrated as a rapid Field Radiometric Identification System (FRIS) for the U.S. Customs Service [5]. The European Communities' Safeguards Directorate (EURATOM) is field-testing the first Safeguards prototype in their applications. The EMC-HPGe detector system design, recent applications, and results will be highlighted.

  8. Model Predictive Control for the Operation of Building Cooling Systems

    Energy Technology Data Exchange (ETDEWEB)

    Ma, Yudong; Borrelli, Francesco; Hencey, Brandon; Coffey, Brian; Bengea, Sorin; Haves, Philip

    2010-06-29

    A model-based predictive control (MPC) is designed for optimal thermal energy storage in building cooling systems. We focus on buildings equipped with a water tank used for actively storing cold water produced by a series of chillers. Typically the chillers are operated at night to recharge the storage tank in order to meet the building demands on the following day. In this paper, we build on our previous work, improve the building load model, and present experimental results. The experiments show that MPC can achieve reduction in the central plant electricity cost and improvement of its efficiency.

  9. User's manual for the BNW-II optimization code for dry/wet-cooled power plants

    Energy Technology Data Exchange (ETDEWEB)

    Braun, D.J.; Bamberger, J.A.; Braun, D.J.; Faletti, D.W.; Wiles, L.E.

    1978-05-01

    The User's Manual describes how to operate BNW-II, a computer code developed by the Pacific Northwest Laboratory (PNL) as a part of its activities under the Department of Energy (DOE) Dry Cooling Enhancement Program. The computer program offers a comprehensive method of evaluating the cost savings potential of dry/wet-cooled heat rejection systems. Going beyond simple ''figure-of-merit'' cooling tower optimization, this method includes such items as the cost of annual replacement capacity, and the optimum split between plant scale-up and replacement capacity, as well as the purchase and operating costs of all major heat rejection components. Hence the BNW-II code is a useful tool for determining potential cost savings of new dry/wet surfaces, new piping, or other components as part of an optimized system for a dry/wet-cooled plant.

  10. USE of mine pool water for power plant cooling.

    Energy Technology Data Exchange (ETDEWEB)

    Veil, J. A.; Kupar, J. M .; Puder, M. G.

    2006-11-27

    Water and energy production issues intersect in numerous ways. Water is produced along with oil and gas, water runs off of or accumulates in coal mines, and water is needed to operate steam electric power plants and hydropower generating facilities. However, water and energy are often not in the proper balance. For example, even if water is available in sufficient quantities, it may not have the physical and chemical characteristics suitable for energy or other uses. This report provides preliminary information about an opportunity to reuse an overabundant water source--ground water accumulated in underground coal mines--for cooling and process water in electric generating facilities. The report was funded by the U.S. Department of Energy's (DOE's) National Energy Technology Laboratory (NETL), which has implemented a water/energy research program (Feeley and Ramezan 2003). Among the topics studied under that program is the availability and use of ''non-traditional sources'' of water for use at power plants. This report supports NETL's water/energy research program.

  11. Plant Phenotype Characterization System

    Energy Technology Data Exchange (ETDEWEB)

    Daniel W McDonald; Ronald B Michaels

    2005-09-09

    This report is the final scientific report for the DOE Inventions and Innovations Project: Plant Phenotype Characterization System, DE-FG36-04GO14334. The period of performance was September 30, 2004 through July 15, 2005. The project objective is to demonstrate the viability of a new scientific instrument concept for the study of plant root systems. The root systems of plants are thought to be important in plant yield and thus important to DOE goals in renewable energy sources. The scientific study and understanding of plant root systems is hampered by the difficulty in observing root activity and the inadequacy of existing root study instrumentation options. We have demonstrated a high throughput, non-invasive, high resolution technique for visualizing plant root systems in-situ. Our approach is based upon low-energy x-ray radiography and the use of containers and substrates (artificial soil) which are virtually transparent to x-rays. The system allows us to germinate and grow plant specimens in our containers and substrates and to generate x-ray images of the developing root system over time. The same plant can be imaged at different times in its development. The system can be used for root studies in plant physiology, plant morphology, plant breeding, plant functional genomics and plant genotype screening.

  12. Experimental study on a transpiration cooling thermal protection system

    Institute of Scientific and Technical Information of China (English)

    2010-01-01

    Transpiration cooling thermal protection systems (TPS) are investigated for potential applications in hypersonic and re-entry vehicles,which are subjected to the severe aerodynamic heating environment. In this paper a transpiration cooling thermal protection system was designed and manufactured,and an experiment platform with radiant heating at the bottom as heat source was developed. The cooling capacity of the transpiration cooling TPS was experimentally investigated. By combining transpiration cooling method with traditional TPS,the heat load capability of the TPS can be improved. The structure temperature with active cooling applied was much lower than that without active cooling applied under the same heat load as well as the heat load increased with active cooling than the one without active cooling for the same structure temperature. The experimental results showed that at 5800 s,the temperature of inner structure was 100°C with active cooling applied compared to 500°C without active cooling applied,then the temperature increased and reached to 360°C at 8300 s. Heat load of this transpiration cooling TPS can be increased by over 70% as compared to the passion one and the cooling capability of the transpiration TPS was about 1700 kJ/kg. The results can provide fundamental data for developing the transpiration cooling TPS.

  13. District heating system cools new hotel; Fernwaerme aus KVA kuehlt neues Ibis-Hotel

    Energy Technology Data Exchange (ETDEWEB)

    Schmid, W.

    2009-07-01

    This article takes a look at how an absorption cooling system provides cooling for a new hotel in Basel, Switzerland. The driving energy for the absorption cooling system is provided by the local district heating system. Cheap, summertime heat is provided by the local utility IWB from the city's waste incineration plant to drive the system. Details are presented on the installation and figures are given on cooling power and energy prices. The energy-relevant construction details of the new hotel are examined and the air-conditioning installations are described. The special planning competence involved is commented on. The control of the absorption refrigeration system is looked at in detail and the particular finesse involved in its operation is commented on. The quiet, roof-mounted cooling units are also described and a schematic diagram of the installation is presented.

  14. Temperature conditioning in ornamental plant production with a prototype device: root zone cooling in protected environments

    Directory of Open Access Journals (Sweden)

    Gianluca Burchi

    2013-09-01

    Full Text Available One of the greatest growing costs in greenhouse floriculture is for energy. To reduce energy costs for thermal conditioning was projected an innovative root zone cooling system characterized by two coaxial pipes with hydraulic countercurrent flows. This new system was compared with a traditional system with hydraulic flows cocurrent. The plants were equipped with coolers for obtaining flowering in the summer period by a culture of Alstroemeria spp and were measured energy consumption in each root zone cooling system. The tests also focused on a particular change, made during the tests of previous years, which allows the coaxial system in turning his operation from countercurrent flows to cocurrent flows. The results obtained show that the root zone coaxial cooling system allows to obtain, in comparison to the traditional type, a better temperature uniformity of the root zone ground, both when it is used with countercurrent flows both when it is used with cocurrent flow. The system also allows a slight overall reduction in energy consumption.

  15. Hybrid Cooling Systems for Low-Temperature Geothermal Power Production

    Energy Technology Data Exchange (ETDEWEB)

    Ashwood, A.; Bharathan, D.

    2011-03-01

    This paper describes the identification and evaluation of methods by which the net power output of an air-cooled geothermal power plant can be enhanced during hot ambient conditions with a minimal amount of water use.

  16. Economics of heat pump systems for simultaneous heating and cooling

    Energy Technology Data Exchange (ETDEWEB)

    Ghosh, S.; Devotta, S.; Patwardhan, V.S.

    1987-01-01

    Heat pumps can be incorporated advantageously into processes which require simultaneously both cooling and heating. The economics of heat pumps in India for simultaneous heat and cooling is assessed with respect to process, design and economic parameters. For the typical conditions of various parameters in India, a heat pump system for simultaneous heating and cooling is very attractive.

  17. CoolPack – Simulation tools for refrigeration systems

    DEFF Research Database (Denmark)

    Jakobsen, Arne; Rasmussen, Bjarne D.; Andersen, Simon Engedal

    1999-01-01

    CoolPack is a collection of programs used for energy analysis and optimisation of refrigeration systems. CoolPack is developed at the Department of Energy Engineering at the Technical University of Denmark. The Danish Energy Agency finances the project. CoolPack is freeware and can be downloaded...

  18. Optimal scheduling of biocide dosing for seawater-cooled power and desalination plants

    KAUST Repository

    Mahfouz, Abdullah Bin

    2011-02-13

    Thermal desalination systems are typically integrated with power plants to exploit the excess heat resulting from the power-generation units. Using seawater in cooling the power plant and the desalination system is a common practice in many parts of the world where there is a shortage of freshwater. Biofouling is one of the major problems associated with the usage of seawater in cooling systems. Because of the dynamic variation in the power and water demands as well as the changes in the characteristics of seawater and the process, there is a need to develop an optimal policy for scheduling biocide usage and cleaning maintenance of the heat exchangers. The objective of this article is to introduce a systematic procedure for the optimization of scheduling the dosing of biocide and dechlorination chemicals as well as cleaning maintenance for a power production/thermal desalination plant. A multi-period optimization formulation is developed and solved to determine: the optimal levels of dosing and dechlorination chemicals; the timing of maintenance to clean the heat-exchange surfaces; and the dynamic dependence of the biofilm growth on the applied doses, the seawater-biocide chemistry, the process conditions, and seawater characteristics for each time period. The technical, economic, and environmental considerations of the system are accounted for. A case study is solved to elucidate the applicability of the developed optimization approach. © 2011 Springer-Verlag.

  19. Capillary Action may Cool Systems and Precisely balance Chemical Reactions

    Science.gov (United States)

    Kriske, Richard

    2011-10-01

    It is well known that it takes no work for Water to rise in a Capillary tube against the force of Gravity. There is a precise balance in this system that resembles Robert Millikan's ``Oil Drop'' experiment, where mass was balanced against the electrostatic force. If at the top of the capillary tube there is evaporation, one can see that the system is cooled as another water molecule has room to move up the column. Furthermore, if the evaporation process can be controlled one photon at a time, a precise balance is created between a photon, and the height/mass of the column. If other molecules are place in the column, they can be moved up and down the column, in a chromatograph way, in a fairly precise manner, by controlling evaporation and molecular weight. If in addition to all of this, the interface of the solution against the walls of the column have Fermi levels, it can be seen as a very precise Electrochemical Device. In the situation of nanotubes, as opposed to trees and plants, these properties can be used to create measure environmental properties and to Balance Chemical Reactions. Forests, and Plants may cool themselves and their environment using this process, and using this process coupled with more energetic photons through photosynthesis.

  20. 核电厂辅助冷却水系统水锤计算与防护%Water Hammer Calculation and Prevention of Auxiliary Cooling Water System in Nuclear Power Plant

    Institute of Scientific and Technical Information of China (English)

    王学华; 熊兴才; 薛海青

    2014-01-01

    对核电厂常规岛辅助冷却水系统由板式换热器改为管壳式换热器并取消升压泵的方案特点进行了定性分析,指出了系统方案改进后的辅助冷却水系统正常停运时会产生水锤现象。通过对辅助冷却水系统建模定量计算了循环水泵停泵工况时的水锤最大压力,提出了通过调整阀门关闭时间消除水锤现象的防护方案并进行了计算验证。%ABSTRACT:This paper,first of all,qualitatively analyzes the characteristic of the auxiliary cooling water system of the conventional island of the nuclear power plant which uses the tube heater instead of the plate heater,pointing out that water hammer phenomena may be caused in the improved system. The maximum pressure of the water hammer when the circulating water pump is shut down is simulated and calculated. Finally the paper proposes the water hammer prevention solution of regulating the valve closing time and certifies the scheme by calculation.

  1. Remote Measurement of Heat Flux from Power Plant Cooling Lakes

    Energy Technology Data Exchange (ETDEWEB)

    Garrett, Alfred J.; Kurzeja, Robert J.; Villa-Aleman, Eliel; Bollinger, James S.; Pendergast, Malcolm M.

    2013-06-01

    Laboratory experiments have demonstrated a correlation between the rate of heat loss q" from an experimental fluid to the air above and the standard deviation σ of the thermal variability in images of the fluid surface. These experimental results imply that q" can be derived directly from thermal imagery by computing σ. This paper analyses thermal imagery collected over two power plant cooling lakes to determine if the same relationship exists. Turbulent boundary layer theory predicts a linear relationship between q" and σ when both forced (wind driven) and free (buoyancy driven) convection are present. Datasets derived from ground- and helicopter-based imagery collections had correlation coefficients between σ and q" of 0.45 and 0.76, respectively. Values of q" computed from a function of σ and friction velocity u* derived from turbulent boundary layer theory had higher correlations with measured values of q" (0.84 and 0.89). Finally, this research may be applicable to the problem of calculating losses of heat from the ocean to the atmosphere during high-latitude cold-air outbreaks because it does not require the information typically needed to compute sensible, evaporative, and thermal radiation energy losses to the atmosphere.

  2. Progress of the stochastic cooling system of the Collector Ring

    CERN Document Server

    Dimopoulou, C; Bohm, R; Dolinskyy, O; Franzke, B; Hettrich, R; Maier, W; Menges, R; Nolden, F; Peschke, C; Petri, P; Steck, M; Thorndahl, L

    2013-01-01

    An overview of the recent achievements and ongoing developments for the stochastic cooling system of the Collector Ring is given. In focus are the hardware developments as well as the progress in predicting the system performance. The system operates in the frequency band 1-2 GHz, it has to provide fast 3D cooling of antiproton, rare isotope and stable heavy ion beams. The main challenges are (i) the cooling of antiprotons by means of cryogenic movable pick-up electrodes and (ii) the fast two-stage cooling (pre-cooling by the Palmer method, followed by the notch filter method) of the hot rare isotope beams (RIBs). Recently, a novel code for simulating the cooling process in the time domain has been developed at CERN. First results for the momentum cooling for heavy ions in the CR will be shown in comparison with results obtained in the frequency domain with the Fokker-Planck approach.

  3. Plant Systems Biology (editorial)

    Science.gov (United States)

    In June 2003, Plant Physiology published an Arabidopsis special issue devoted to plant systems biology. The intention of Natasha Raikhel and Gloria Coruzzi, the two editors of this first-of-its-kind issue, was ‘‘to help nucleate this new effort within the plant community’’ as they considered that ‘‘...

  4. The Selection of Cooling systems of Giant Hydro-Generators

    Institute of Scientific and Technical Information of China (English)

    Li Dingzhong

    2010-01-01

    @@ The selection of cooling system for hydro-generator in Ertan Hydropower Station is reviewed in this pap(ar) The new viewpoint on air-cooled system of hydraul(is)generator of recent years is analyzed and described. That is, "Full air-cooled system is always preferred to inner water cooling system in hydro-generator." Moreov() the decision process and corresponding actions of aircooled system design for hydro-generator in Longtan Hydropower Station, Xiaowan Hydropower Station and Laxiwa Hydropower Station are introduced.

  5. Desiccant Cooling System for Thermal Comfort: A Review

    Directory of Open Access Journals (Sweden)

    HEMANT PARMAR,

    2011-05-01

    Full Text Available Desiccant cooling system (DCS is alternate suitable option against conventional cooling system in humid climates. A typical system combines a dehumidifier that uses dry desiccant wheel, with direct or indirect evaporative systems and a sensible cooling system. DCS is the environmental protection technique for cooling purpose of the building. This system reduces the CFC level in the environment because it restricts the use of conventional refrigerant. In this paper, all the working principles and expected research areashave been discussed. Through detailed literature survey it has been observed that a desiccant cooling system may be a suitable option for thermal comfort in the climate where the humidity is higher. Thedesiccant cooling system (DCS has proven their feasibility and cost saving in the field of air conditioning. This review provides a brief overview on the development of desiccant cooling system in different fields. Finally, concluding remarks regarding further development of desiccant cooling for thermal comfort are also provided. This technology is economically feasible and optimizes with low cost. This review is useful for making opportunities to further research in different areas of desiccant cooling system.

  6. Nutrient solution cooling and its effect on temperature of leaf lettuce in hydroponic system.

    Science.gov (United States)

    Nam, S W; Kim, M K; Son, J E

    1996-12-01

    The heat transfer characteristics of a hydroponic system were experimentally verified after theoretical establishment and the effect of nutrient solution cooling on the plant temperature was investigated. About 96 percent of the total heat flow transferred from culture bed to nutrient solution was the conductive heat through planting board and partitioning materials. The average and maximum temperatures of the leaf lettuce decreased 0.6 and 1.5 degrees C., respectively, with cooling of nutrient solution by 6 degrees C. A numerical model for prediction of cooling load of nutrient solution in a hydroponic greenhouse was developed, and the results from the simulation model showed a good agreement with those from experiments. A mechanical cooling system using the counter flow type with double pipes was developed for cooling the nutrient solution. Also the heat transfer characteristics of the system were analyzed experimentally and theoretically, and compared with the other existing cooling systems of nutrient solution. The cooling capacities of three different systems, which used polyethylene tube in solution tank, stainless tube in solution tank, and the counter flow type with double pipes, were comparatively evaluated.

  7. GOTHIC Simulation of Passive Containment Cooling System

    Energy Technology Data Exchange (ETDEWEB)

    Ha, Huiun; Kim, Hangon [Korea Hydro and Nuclear Power Co. Ltd., Daejeon (Korea, Republic of)

    2013-05-15

    The performance of this system depends on the condensation of steam moving downward inside externally cooled vertical tubes. AES-2006: During a DBA, heat is removed by internally cooled vertical tubes, which are located in containment. We are currently developing the conceptual design of Innovative PWR, which is will be equipped with various passive safety features, including PCCS. We have plan to use internal heat exchanger (HX) type PCCS with concrete containment. In this case, the elevation of HXs is important to ensure the heat removal during accidents. In general, steam is lighter than air mixture in containment. So, steam may be collected at the upper side of containment. It means that higher elevation of HXs, larger heat removal efficiency of those. So, the aim of the present paper is to give preliminary study on variation of heat removal performance according to elevation of HXs. With reference to the design specification of the current reactors including APR+, we had determined conceptual design of PCCS. Using it, we developed a GOTHIC model of the APR1400 containment was adopted PCCS. This calculation model is described herein and representative results of calculation are presented. APR 1400 GOTHIC model was developed for PCCS performance calculation and sensitivity test according to installation elevation of PCCXs. Calculation results confirm that PCCS is working properly. It is found that the difference due to the installation elevation of PCCXs is insignificant at this preliminary analysis, however, further studies should be performed to confirm final performance of PCCS according to the installation elevation. These insights are important for developing the PCCS of Innovative PWR.

  8. Solar space heating and cooling by selective use of the components of a desiccant cooling system

    Science.gov (United States)

    Abbud, Ihsan Aladdin

    The economic advantages of by-passing various components of a desiccant cooling system under conditions not requiring their use are estimated by evaluating the annual costs of heating and cooling a commercial building in three representative U.S. cities. Life-cycle costs of systems employing solar heat for space heating and desiccant regeneration are compared with those using electric heat. The costs of purchasing and operating heating and desiccant cooling systems, with and without solar heat supply, are compared with those employing conventional heating and vapor compression cooling. The conditions under which commercial buildings can be cooled with desiccant systems at costs competitive with conventional systems are identified. A commercially available vapor compression air conditioner is used as a standard of comparison for energy consumption and room comfort. Heating and cooling requirements of the building are determined by use of the BLAST computer model in a simulation of long term system operation. Performance of the desiccant cooling system and life cycle savings obtained by its use are determined by simulation employing the TRNSYS computer model. TRNSYS compatible subroutines are developed to simulate operation of the desiccant equipment, the building, and the controllers that operate and monitor the system components. The results are presented in tabular and graphical form. This study shows that in the widely different climates represented in Los Angeles, New York, and Miami, by-passing various components in the desiccant cooling system when they are not needed is economically advantageous. Operation cost of the complete system decreased by 47.3% in Los Angeles, by 30.9% in New York City, and by 23.9% in Miami by not operating the desiccant wheel and other elements. The ventilation desiccant cooling system has major economic advantage over conventional systems under conditions of moderate humidity, as in Los Angeles and New York City. In Miami, however

  9. Electric drive systems including smoothing capacitor cooling devices and systems

    Energy Technology Data Exchange (ETDEWEB)

    Dede, Ercan Mehmet; Zhou, Feng

    2017-02-28

    An electric drive system includes a smoothing capacitor including at least one terminal, a bus bar electrically coupled to the at least one terminal, a thermoelectric device including a first side and a second side positioned opposite the first side, where the first side is thermally coupled to at least one of the at least one terminal and the bus bar, and a cooling element thermally coupled to the second side of the thermoelectric device, where the cooling element dissipates heat from the thermoelectric device.

  10. Review of Dry Cooling Technologies in Power Plants%电站空冷技术

    Institute of Scientific and Technical Information of China (English)

    卜永东; 杨立军; 杜小泽; 杨勇平

    2013-01-01

    An increasing focus on water conservation combined with continuing concern on the environmental effects of both once-through and evaporative cooling has resulted in increasing popularity of dry cooling technology.Finned tube heat exchanger is one of the main equipments for either direct or indirect dry cooling system.The flow and heat transfer characteristics of the finned tube bundles in various geometric forms are the key issues to the thermo-hydraulic performances of dry cooling system.The forced convection heat transfer is commonly taken to realize the heat rejection from the exhaust steam of turbine to the cooling air for the present direct dry cooling system,so the aerodynamic behavior of the axial flow fan and the cluster effect due to the array of tens of axial flow fans will impose conspicuous impacts on the performance of direct dry cooling system.For the indirect dry cooling system,the ambient air is driven to flow through the air-cooled heat exchanger by means of the buoyancy force due to the air density difference between the outside and inside of the natural draught dry-cooling tower,removing the heat rejection from the circulating water.The thermo-hydraulic performances of indirect dry cooling system are mainly dependent upon the structure of dry-cooling tower,and the air-cooled heat exchanger layout of either horizontal location at the inlet cross section of the tower or vertical arrangement around the circumference at the base of the tower.The ambient air is employed directly or indirectly as the cooling medium of the exhaust steam,so the ambient condition becomes one of the key issues for the performance of dry cooling system in power plants.In this work,the state-of-the-art in dry cooling technologies of power plants will be reviewed and assessed,and the future development trends and application is forecasted.%随着对水资源日益匮乏,以及对直流和蒸发冷却方式引起的环境问题的持续关注,电站空冷技术获得了快速

  11. District heating and cooling systems for communities through power plant retrofit distribution network, Phase 2. Final report, 1 March 1980-31 January 1984. Volume II

    Energy Technology Data Exchange (ETDEWEB)

    1984-01-31

    This volume begins with an Introduction summarizing the history, methodology and scope of the study, the project team members and the private and public groups consulted in the course of the study. The Load and Service Area Assessment follows, including: a compilation and analysis of existing statistical thermal load data from census data, industrial directories, PSE and G records and other sources; an analysis of responses to a detailed, 4-page thermal load questionnaire; data on public buildings and fuel and energy use provided by the New Jersey Dept. of Energy; and results of other customer surveys conducted by PSE and G. A discussion of institutional questions follows. The general topic of rates is then discussed, including a draft hypothetical Tariff for Thermal Services. Financial considerations are discussed including a report identifying alternative ownership/financing options for district heating systems and the tax implications of these options. Four of these options were then selected by PSE and G and a financial (cash-flow) analysis done (by the PSE and G System Planning Dept.) in comparison with a conventional heating alternative. Year-by-year cost of heat ($/10/sup 6/ Btu) was calculated and tabulated, and the various options compared.

  12. Cooling factor for magnetic refrigeration systems

    Directory of Open Access Journals (Sweden)

    Mohammadreza Ghahremani

    2014-12-01

    Full Text Available The adiabatic temperature change (ΔTad during the magnetization process of polycrystalline gadolinium and Ni51Mn33.4In15.6 Heusler alloy is directly measured near the Curie temperature. The cooling factor (CF is introduced as the area under the curve of adiabatic temperature change versus ambient temperature. The CF provides more representative measure of cooling performance in the operational temperature range. Selecting different temperature abscissas qualitatively changes the interpretation of the cooling performance of a magnetocaloric material. In particular, plotting ΔTad versus initial temperature gives a measurably different CF compared to that given by plotting ΔTad versus average temperature.

  13. District heating and cooling systems for communities through power plant retrofit and distribution network. Volume 3. Tasks 4-6. Final report

    Energy Technology Data Exchange (ETDEWEB)

    Watt, J.R.; Sommerfield, G.A.

    1979-08-01

    Stone and Webster Engineering Corporation is a member of the Demonstration Team to review and assess the technical aspects of cogeneration for district heating. Task 4 details the most practical retrofit schemes. Of the cogeneration schemes studied, a back-pressure turbine is considered the best source of steam for district heating. Battelle Columbus Laboratories is a member of the Demonstration Team employed to investigate several institutional issues affecting the success of district heating. The Toledo Edison legal staff reviewed the legal aspects of mandate to serve, easement and franchise requirements, and corporate charter requirements. The principal findings of both the Battelle investigations and the legal research are summarized in Task 5. A complete discussion of each issue is included in the two sections labeled Legal Issues and Institutional Issues. In Task 6, Battelle Columbus Laboratories completed a preliminary economic analysis, incorporating accurate input parameters applicable to utility ownership of the proposed district-heating system. The methodology used is summarized, the assumptions are listed, and the results are briefly reviewed.

  14. ANALYSIS OF A HIGH TEMPERATURE GAS-COOLED REACTOR POWERED HIGH TEMPERATURE ELECTROLYSIS HYDROGEN PLANT

    Energy Technology Data Exchange (ETDEWEB)

    M. G. McKellar; E. A. Harvego; A. M. Gandrik

    2010-11-01

    An updated reference design for a commercial-scale high-temperature electrolysis (HTE) plant for hydrogen production has been developed. The HTE plant is powered by a high-temperature gas-cooled reactor (HTGR) whose configuration and operating conditions are based on the latest design parameters planned for the Next Generation Nuclear Plant (NGNP). The current HTGR reference design specifies a reactor power of 600 MWt, with a primary system pressure of 7.0 MPa, and reactor inlet and outlet fluid temperatures of 322°C and 750°C, respectively. The reactor heat is used to produce heat and electric power to the HTE plant. A Rankine steam cycle with a power conversion efficiency of 44.4% was used to provide the electric power. The electrolysis unit used to produce hydrogen includes 1.1 million cells with a per-cell active area of 225 cm2. The reference hydrogen production plant operates at a system pressure of 5.0 MPa, and utilizes a steam-sweep system to remove the excess oxygen that is evolved on the anode (oxygen) side of the electrolyzer. The overall system thermal-to-hydrogen production efficiency (based on the higher heating value of the produced hydrogen) is 42.8% at a hydrogen production rate of 1.85 kg/s (66 million SCFD) and an oxygen production rate of 14.6 kg/s (33 million SCFD). An economic analysis of this plant was performed with realistic financial and cost estimating The results of the economic analysis demonstrated that the HTE hydrogen production plant driven by a high-temperature helium-cooled nuclear power plant can deliver hydrogen at a competitive cost. A cost of $3.03/kg of hydrogen was calculated assuming an internal rate of return of 10% and a debt to equity ratio of 80%/20% for a reactor cost of $2000/kWt and $2.41/kg of hydrogen for a reactor cost of $1400/kWt.

  15. Computational Fluid Dynamics Analysis of an Evaporative Cooling System

    Directory of Open Access Journals (Sweden)

    Kapilan N.

    2016-11-01

    Full Text Available The use of chlorofluorocarbon based refrigerants in the air-conditioning system increases the global warming and causes the climate change. The climate change is expected to present a number of challenges for the built environment and an evaporative cooling system is one of the simplest and environmentally friendly cooling system. The evaporative cooling system is most widely used in summer and in rural and urban areas of India for human comfort. In evaporative cooling system, the addition of water into air reduces the temperature of the air as the energy needed to evaporate the water is taken from the air. Computational fluid dynamics is a numerical analysis and was used to analyse the evaporative cooling system. The CFD results are matches with the experimental results.

  16. Corrosion inhibitors for intermediate cooling systems

    Energy Technology Data Exchange (ETDEWEB)

    Falk, I.; Suhr, L.

    1985-04-01

    The selected inhibitors were tested for heat and radiation stability and corrosion protection on the bench scale. Based on the results from these tests two of the products were selected, Bycoguard 81 and Bycoguard MP4S for continuing corrosion tests in an autoclave loop at 90 degrees C and 120 degrees C. Oxygen saturated deionized water with an addition of 1 ppm chloride was recirculated in the loop. Samples of copper and carbon steel were exposed to the water in the autoclave for periods up to 10 weeks. The purpose of this project was to find a substitute for hydrazine and chromates. Besides good corrosion protection qualities the toxic and environmental effect of the inhibitors should be minimal. The investigation has shown that the copper inhibitor BTA (benzotriazole) loses its corrosion protection qualities at a water temperature of 120 degrees C. The protection effects at 90 degrees C were satisfactory for both of the materials. The corrosion rates measured were 0.01 mm/y or less for the copper and carbon steel samples. The environment in the autoclave during the testing was more corrosive than is to be found in intermediate cooling systems. Due to the low corrosion rates measured the two inhibitors are to be recommended as alternatives to hydrazine and chromates.

  17. Venus Surface Power and Cooling System Design

    Science.gov (United States)

    Landis, Geoffrey A.; Mellott, Kenneth D.

    2004-01-01

    A radioisotope power and cooling system is designed to provide electrical power for the a probe operating on the surface of Venus. Most foreseeable electronics devices and sensors simply cannot operate at the 450 C ambient surface temperature of Venus. Because the mission duration is substantially long and the use of thermal mass to maintain an operable temperature range is likely impractical, some type of active refrigeration may be required to keep certain components at a temperature below ambient. The fundamental cooling requirements are comprised of the cold sink temperature, the hot sink temperature, and the amount of heat to be removed. In this instance, it is anticipated that electronics would have a nominal operating temperature of 300 C. Due to the highly thermal convective nature of the high-density atmosphere, the hot sink temperature was assumed to be 50 C, which provided a 500 C temperature of the cooler's heat rejecter to the ambient atmosphere. The majority of the heat load on the cooler is from the high temperature ambient surface environment on Venus. Assuming 5 cm radial thickness of ceramic blanket insulation, the ambient heat load was estimated at approximately 77 watts. With an estimated quantity of 10 watts of heat generation from electronics and sensors, and to accommodate some level of uncertainty, the total heat load requirement was rounded up to an even 100 watts. For the radioisotope Stirling power converter configuration designed, the Sage model predicts a thermodynamic power output capacity of 478.1 watts, which slightly exceeds the required 469.1 watts. The hot sink temperature is 1200 C, and the cold sink temperature is 500 C. The required heat input is 1740 watts. This gives a thermodynamic efficiency of 27.48 %. The maximum theoretically obtainable efficiency is 47.52 %. It is estimated that the mechanical efficiency of the power converter design is on the order of 85 %, based on experimental measurements taken from 500 watt power

  18. Treatment of waste water from recirculating cooling system in LNG plant using electrodialysis technology%电渗析技术处理 LN G 工厂循环冷却系统排污水研究

    Institute of Scientific and Technical Information of China (English)

    王丹; 童富良; 王滟; 杨晓娇

    2014-01-01

    waste water from recirculating cooling system in Hubei LNG plant amounts up to 1 200 m3 per day .Direct discharge would not only cause the waste of water resource ,but also bring large impact to the operation of the downstream sewage treatment plants .In order to pro‐mote the recycling rate ,a “multi‐stage continuous electrodialysis desalination system” was de‐signed to treat the waste water for reusing .According to the design calculation ,the flow veloci‐ty ,the overall desalination rate ,the conductivity of the treated water were set at 5 .0 cm/s ,75%~80% ,and 300~350 μs/cm respectively in 50 m3/h electrodialysis system .The debugging re‐sults showed that the optimum operating voltage was 110 V ,the most suitable flow rate was 50 m3/h ,and the treated water from the electrodialysis system could meet all the design require‐ments .The process can reduce the fresh water consumption and waste water discharge by 300 000 tons per year respectively ,and bring direct economic benefit of about RMB 600 000 yuan each year .%湖北L N G工厂循环冷却水系统每日排污量高达1200 m3,直接排放不仅造成水资源的浪费,同时对下游污水处理厂的运行产生较大冲击。为提高该部分废水的重复利用率,设计采用“多级连续式电渗析除盐系统”对其进行脱盐处理后回用于循环水系统。经计算,50 m3/h的电渗析装置设计流速采用 V =5.0 cm/s ,设计总脱盐率ε=75%~80%,产水电导率300~350μs/cm。装置建成后调试结果表明,最佳操作电压为110 V ,最适宜进水流量为50 m3/h ,产水各项指标满足预期设计要求。每年可减少新鲜水消耗和废水排放各30×104 t ,产生直接经济效益约60万元。

  19. Performance of materials in the component cooling water systems of pressurized water reactors

    Energy Technology Data Exchange (ETDEWEB)

    Lee, B.S.

    1993-06-01

    The component cooling water (CCW) system provides cooling water to several important loads throughout the plant under all operating conditions. An aging assessment CCW systems in pressurized water reactors (PWRs) was conducted as part of Nuclear Plant Aging Research Program (NPAR) instituted by the US Nuclear Regulatory Commission. This paper presents some of the results on the performances of materials in respect of their application in CCW Systems. All the CCW system failures reported to the Nuclear Plant Reliability Data System (NPRDS) from January 1988 to June 1990 were reviewed; it is concluded that three of the main contributors to CCW system failures are valves, pumps, and heat exchangers. This study identified the modes and causes of failure for these components; most of the causes for the aging-related failures could be related to the performance of materials. Also, in this paper the materials used for these components are reviewed, and there aging mechanisms under CCW system conditions are discussed.

  20. The role of absorption cooling for reaching sustainable energy systems

    OpenAIRE

    Lindmark, Susanne

    2005-01-01

    The energy consumption is continuous to increase around the world and with that follows the demand for sustainable solutions for future energy systems. With growing energy consumption from fossil based fuels the threat of global warming through release of CO2 to the atmosphere increases. The demand for cooling is also growing which would result in an increased consumption of electricity if the cooling demand was to be fulfilled by electrically driven cooling technology. A more sustainable sol...

  1. Cooling systems for ultra-high temperature turbines.

    Science.gov (United States)

    Yoshida, T

    2001-05-01

    This paper describes an introduction of research and development activities on steam cooling in gas turbines at elevated temperature of 1500 C and 1700 C level, partially including those on water cooling. Descriptions of a new cooling system that employs heat pipes are also made. From the view point of heat transfer, its promising applicability is shown with experimental data and engine performance numerical evaluation.

  2. Study of reactor plant disturbed cooling condition modes caused by the VVER reactor secondary circuit

    Directory of Open Access Journals (Sweden)

    V.I. Belozerov

    2016-12-01

    Based on the RELAP-5, TRAC, and TRACE software codes, reactor plant cooling condition malfunction modes caused by the VVER-1000 secondary circuit were simulated and investigated. Experimental data on the mode with the turbine-generator stop valve closing are presented. The obtained dependences made it possible to determine the maximum values of pressure and temperature in the circulation circuit as well as estimate the Minimum Critical Heat Flux Ratio (MCHFR. It has been found that, if any of the initial events occurs, safety systems are activated according to the set points; transient processes are stabilized in time; and the Critical Heat Flux (CHF limit is provided. Therefore, in the event of emergency associated with the considered modes, the reactor plant safety will be ensured.

  3. Improved Performance of an Air Cooled Condenser (ACC) Using SPX Wind Guide Technology at Coal-Based Thermoelectric Power Plants

    Energy Technology Data Exchange (ETDEWEB)

    Ken Mortensen

    2010-12-31

    This project added a new airflow enhancement technology to an existing ACC cooling process at a selected coal power plant. Airflow parameters and efficiency improvement for the main plant cooling process using the applied technology were determined and compared with the capabilities of existing systems. The project required significant planning and pre-test execution in order to reach the required Air Cooled Condenser system configuration for evaluation. A host Power Plant ACC system had to be identified, agreement finalized, and addition of the SPX ACC Wind Guide Technology completed on that site. Design of the modification, along with procurement, fabrication, instrumentation, and installation of the new airflow enhancement technology were executed. Baseline and post-modification cooling system data was collected and evaluated. The improvement of ACC thermal performance after SPX wind guide installation was clear. Testing of the improvement indicates there is a 5% improvement in heat transfer coefficient in high wind conditions and 1% improvement at low wind speed. The benefit increased with increasing wind speed. This project was completed on schedule and within budget.

  4. PERFORMANCE EVALUATION OF CEILING RADIANT COOLING SYSTEM IN COMPOSITE CLIMATE

    Energy Technology Data Exchange (ETDEWEB)

    Sharma, Anuj [Malaviya National Institute of Technology (MNIT), Jaipur, India; Mathur, Jyotirmay [Malaviya National Institute of Technology (MNIT), Jaipur, India; Bhandari, Mahabir S [ORNL

    2015-01-01

    Radiant cooling systems are proving to be an energy efficient solution due to higher thermal capacity of cooling fluid especially for the buildings that require individual zone controls and where the latent loads are moderate. The Conventional air conditioners work at very low temperature i.e.5-8 c (refrigerant evaporator inlet) while the radiant cooling systems, also referred as high temperature cooling system, work at high temperatures i.e. 14-18 c. The radiant cooling systems can maintain lower MRT (Mean Radiant Temperature) as ceiling panels maintain uniform temperature gradient inside room and provide higher human comfort. The radiant cooling systems are relatively new systems and their operation and energy savings potential are not quantified for a large number of buildings and operational parameters. Moreover, there are only limited numbers of whole building simulation studies have been carried out for these systems to have a full confidence in the capability of modelling tools to simulate these systems and predict the impact of various operating parameters. Theoretically, savings achieve due to higher temperature set point of chilled water, which reduces chiller-running time. However, conventional air conditioner runs continuously to maintain requisite temperature. In this paper, experimental study for performance evaluation of radiant cooling system carried out on system installed at Malaviya National Institute of Technology Jaipur. This paper quantifies the energy savings opportunities and effective temperature by radiant cooling system at different chilled water flow rates and temperature range. The data collected/ analysed through experimental study will used for calibration and validation of system model of building prepared in building performance simulation software. This validated model used for exploring optimized combinations of key parameters for composite climate. These optimized combinations will used in formulation of radiant cooling system

  5. Study of the circulation theory of the cooling system in vertical evaporative cooling generator

    Institute of Scientific and Technical Information of China (English)

    YU; Shunzhou; CAI; Jing; GUO; Chaohong

    2006-01-01

    The article briefly states the current development of evaporative cooling generator and its advantages comparing with generators of traditional cooling. Vertical evaporative cooling generator, which adopts Close-Loop-Self-Cycle with no-pump and free convection boil in the hollow stator bar, is one of the great developments in generator design. This article emphasizes the importance of cooling system in generator; expatiates the circulation theory in two aspects, energy and flow; and analyzes the essential reason,motivity and stability of Close-Loop-Self-Cycle. The article points out that the motivity of the circulation is the heat absorbed by coolant. After absorbing heat the coolant will have the ability of doing work because of the phase change. In another words, it is the buoyancy causing by density difference leads to the Close-Loop-Self-Cycle. This conclusion is validated by experimental data.

  6. Measures against the adverse impact of natural wind on air-cooled condensers in power plant

    Institute of Scientific and Technical Information of China (English)

    2010-01-01

    The natural wind plays disadvantageous roles in the operation of air-cooled steam condensers in power plant.It is of use to take various measures against the adverse effect of wind for the performance improvement of air-cooled condensers.Based on representative 2×600 MW direct air-cooled power plant,three ways that can arrange and optimize the flow field of cooling air thus enhance the heat transfer of air-cooled condensers were proposed.The physical and mathematical models of air-cooled condensers with various flow leading measures were presented and the flow and temperature fields of cooling air were obtained by CFD simulation.The back pressures of turbine were calculated for different measures on the basis of the heat transfer model of air-cooled condensers.The results show that the performance of air-cooled condensers is improved thus the back pressure of turbine is lowered to some extent by taking measures against the adverse impact of natural wind.

  7. Prototype solar heating and combined heating cooling systems

    Science.gov (United States)

    1978-01-01

    The design and development of eight prototype solar heating and combined heating and cooling systems is discussed. The program management and systems engineering are reported, and operational test sites are identified.

  8. User's manual for the BNW-I optimization code for dry-cooled power plants. Volume I

    Energy Technology Data Exchange (ETDEWEB)

    Braun, D.J.; Daniel, D.J.; De Mier, W.V.; Faletti, D.W.; Wiles, L.E.

    1977-01-01

    This User's Manual provides information on the use and operation of three versions of BNW-I, a computer code developed by Battelle, Pacific Northwest Laboratory (PNL) as a part of its activities under the ERDA Dry Cooling Tower Program. These three versions of BNW-I were used as reported elsewhere to obtain comparative incremental costs of electrical power production by two advanced concepts (one using plastic heat exchangers and one using ammonia as an intermediate heat transfer fluid) and a state-of-the-art system. The computer program offers a comprehensive method of evaluating the cost savings potential of dry-cooled heat rejection systems and components for power plants. This method goes beyond simple ''figure-of-merit'' optimization of the cooling tower and includes such items as the cost of replacement capacity needed on an annual basis and the optimum split between plant scale-up and replacement capacity, as well as the purchase and operating costs of all major heat rejection components. Hence, the BNW-I code is a useful tool for determining potential cost savings of new heat transfer surfaces, new piping or other components as part of an optimized system for a dry-cooled power plant.

  9. Evaluation of two cooling systems under a firefighter coverall

    NARCIS (Netherlands)

    Teunissen, L.P.J.; Wang, L.C.; Chou, S.N.; Huang, C.; Jou, G.T.; Daanen, H.A.M.

    2014-01-01

    Firemen often suffer from heat strain. This study investigated two chest cooling systems for use under a firefighting suit. In nine male subjects, a vest with water soaked cooling pads and a vest with water perfused tubes were compared to a control condition. Subjects performed 30 min walking and 10

  10. Application of Hastelloy X in Gas-Cooled Reactor Systems

    DEFF Research Database (Denmark)

    Brinkman, C. R.; Rittenhouse, P. L.; Corwin, W.R.

    1976-01-01

    Hastelloy X, an Ni--Cr--Fe--Mo alloy, may be an important structural alloy for components of gas-cooled reactor systems. Expected applications of this alloy in the High-Temperature Gas-Cooled Reactor (HTGR) are discussed, and the development of interim mechanical properties and supporting data...

  11. Development of a cooling system for superconducting wind turbine generator

    Science.gov (United States)

    Furuse, Mitsuho; Fuchino, Shuichiro; Okano, Makoto; Natori, Naotake; Yamasaki, Hirofumi

    2016-12-01

    This paper deals with the cooling system for high-Tc superconducting (HTS) generators for large capacity wind turbines. We have proposed a cooling system with a heat exchanger and circulation pumps to cool HTS field windings designed for 10 MW-class superconducting generators. In the cooling system, the refrigerants in the stationary and rotational systems are completely separated; heat between the two systems exchanges using a rotational-stationary heat exchanger. The refrigerant in rotational system is circulated by highly reliable pumps. We designed the rotational-stationary heat exchanger based on a conventional shell-and tube type heat exchanger. We also demonstrated that heat exchange in cryogenic temperature is possible with a commercially available heat exchanger. We devised a novel and highly reliable cryogenic helium circulation pump with magnetic reciprocating rotation system and verified its underlying principle with a small-scale model.

  12. Engineering and cost comparison of three different all-dry cooling systems

    Energy Technology Data Exchange (ETDEWEB)

    Fryer, B.C.; Braun, D.J.; Braun, D.J.; Faletti, D.W.; Wiles, L.E.

    1976-09-01

    Results of a detailed engineering and cost study of three different all-dry cooling systems to assess the potential for reducing the cost of all-dry cooling for steam electric power plants are described. The three types of cooling systems considered were: state-of-the-art (SOA) dry cooling system; with a conventional surface condenser, and water used to condense the steam is passed through an induced mechanical draft, metal finned tube cooling tower; an advanced dry cooling system (PLASTIC) utilizing heat exchangers made of bare plastic tubes in the cooling tower; and an advanced dry cooling system utilizing ammonia as the coolant (NH/sub 3/). The NH/sub 3/ system differs from the SOA system in that ammonia is substituted for water as the intermediate fluid. Steam from the turbine is condensed by boiling ammonia in a condenser/reboiler; the ammonia vapor is condensed in an induced draft, metal finned tube heat exchanger and returned to the condenser/reboiler. The major conclusions drawn from this study are that: SOA systems offered by vendors are so near optimum in terms of heat exchanger unit geometry and configuration that there is little, if any, cost advantage to be gained by further study of SOA systems using wrap-on or extruded finned tubes other than in the selection of tube materials, materials compatibility, water quality control, or fin manufacturing methods; significant savings (34 percent) in incremental power production costs appear to be obtainable using NH/sub 3/ systems; and considerable savings (22 percent) can also be obtained with PLASTIC systems.

  13. Low temperature heating and high temperature cooling embedded water based surface heating and cooling systems

    CERN Document Server

    Babiak, Jan; Petras, Dusan

    2009-01-01

    This Guidebook describes the systems that use water as heat-carrier and when the heat exchange within the conditioned space is more than 50% radiant. Embedded systems insulated from the main building structure (floor, wall and ceiling) are used in all types of buildings and work with heat carriers at low temperatures for heating and relatively high temperature for cooling.

  14. Mathematic modeling on flexible cooling system in hot strip mill

    Institute of Scientific and Technical Information of China (English)

    彭良贵; 刘相华; 赵宪明; 吴迪

    2014-01-01

    A novel cooling system combining ultra fast cooling rigs with laminar cooling devices was investigated. Based on the different cooling mechanisms, a serial of mathematic models were established to describe the relationship between water flow and spraying pressure and the relationship between water spraying heat flux and layout of nozzles installed on the top and bottom cooling headers. Model parameters were validated by measured data. Heat transfer models including air convection model, heat radiation model and water cooling capacity model were detailedly introduced. In addition, effects on cooling capacity by water temperature and different valve patterns were also presented. Finally, the comparison results from UFC used or not have been provided with respect to temperature evolution and mechanical properties of Q235B steel grade with thickness of 7.8 mm. Since online application of the sophisticated CTC process control system based on these models, run-out table cooling control system has been running stably and reliably to produce resource-saving, low-cost steels with smaller grain size.

  15. Control of Non-linear Marine Cooling System

    DEFF Research Database (Denmark)

    Hansen, Michael; Stoustrup, Jakob; Bendtsen, Jan Dimon

    2011-01-01

    We consider the problem of designing control laws for a marine cooling system used for cooling the main engine and auxiliary components aboard several classes of container vessels. We focus on achieving simple set point control for the system and do not consider compensation of the non......-linearities, closed circuit flow dynamics or transport delays that are present in the system. Control laws are therefore designed using classical control theory and the performance of the design is illustrated through two simulation examples....

  16. Oxygen Handling and Cooling Options in High Temperature Electrolysis Plants

    Energy Technology Data Exchange (ETDEWEB)

    Manohar S. Sohal; J. Stephen Herring

    2008-07-01

    Idaho National Laboratory is working on a project to generate hydrogen by high temperature electrolysis (HTE). In such an HTE system, safety precautions need to be taken to handle high temperature oxygen at ~830°C. This report is aimed at addressing oxygen handling in a HTE plant.. Though oxygen itself is not flammable, most engineering material, including many gases and liquids, will burn in the presence of oxygen under some favorable physicochemical conditions. At present, an absolute set of rules does not exist that can cover all aspects of oxygen system design, material selection, and operating practices to avoid subtle hazards related to oxygen. Because most materials, including metals, will burn in an oxygen-enriched environment, hazards are always present when using oxygen. Most materials will ignite in an oxygen-enriched environment at a temperature lower than that in air, and once ignited, combustion rates are greater in the oxygen-enriched environment. Even many metals, if ignited, burn violently in an oxygen-enriched environment. However, these hazards do not preclude the operations and systems involving oxygen. Oxygen can be safely handled and used if all the materials in a system are not flammable in the end-use environment or if ignition sources are identified and controlled. In fact, the incidence of oxygen system fires is reported to be low with a probability of about one in a million. This report is a practical guideline and tutorial for the safe operation and handling of gaseous oxygen in high temperature electrolysis system. The intent is to provide safe, practical guidance that permits the accomplishment of experimental operations at INL, while being restrictive enough to prevent personnel endangerment and to provide reasonable facility protection. Adequate guidelines are provided to govern various aspects of oxygen handling associated with high temperature electrolysis system to generate hydrogen. The intent here is to present acceptable

  17. Safe corrosion inhibitor for treating cooling water on heat power engineering plants

    Science.gov (United States)

    Nikolaeva, L. A.; Khasanova, D. I.; Mukhutdinova, E. R.; Safin, D. Kh.; Sharifullin, I. G.

    2017-08-01

    Heat power engineering (HPE) consumes significant volumes of water. There are, therefore, problems associated with corrosion, biological fouling, salt deposits, and sludge formation on functional surfaces of heat power equipment. One of the effective ways to solve these problems is the use of inhibitory protection. The development of new Russian import-substituting environmentally friendly inhibitors is very relevant. This work describes experimental results on the OPC-800 inhibitor (TU 2415-092-00206 457-2013), which was produced at Karpov Chemical Plant and designed to remove mineral deposits, scale, and biological fouling from the surfaces of water-rotation node systems on HPE objects. This reagent is successfully used as an effective corrosion inhibitor in the water recycling systems of Tatarstan petrochemical enterprises. To save fresh make-up water, the circulating system is operated in a no-blow mode, which is characterized by high evaporation and salt content coefficients. It was experimentally found that corrosion rate upon treatment of recycled water with the OPC-800 inhibitor is 0.08-0.10 mm/year. HPE mainly uses inhibitors based on oxyethylidene diphosphonic (OEDPA) and nitrilotrimethylphosphonic (NTMPA) acids. The comparative characteristic of inhibition efficiency for OPC-800 and OEDF-Zn-U2 is given. The results obtained indicate that OPC-800 can be used as an inhibitor for treatment of cooling water in HPE plants. In this case, it is necessary to take into account the features of water rotation of a thermal power plant.

  18. Preoperational test report, primary ventilation condenser cooling system

    Energy Technology Data Exchange (ETDEWEB)

    Clifton, F.T.

    1997-10-29

    This represents the preoperational test report for the Primary Ventilation Condenser Cooling System, Project W-030. Project W-030 provides a ventilation upgrade for the four Aging Waste Facility tanks. The system uses a closed chilled water piping loop to provide offgas effluent cooling for tanks AY101, AY102, AZ1O1, AZ102; the offgas is cooled from a nominal 100 F to 40 F. Resulting condensation removes tritiated vapor from the exhaust stack stream. The piping system includes a package outdoor air-cooled water chiller with parallel redundant circulating pumps; the condenser coil is located inside a shielded ventilation equipment cell. The tests verify correct system operation and correct indications displayed by the central Monitor and Control System.

  19. Cavity cooling of an ensemble spin system.

    Science.gov (United States)

    Wood, Christopher J; Borneman, Troy W; Cory, David G

    2014-02-07

    We describe how sideband cooling techniques may be applied to large spin ensembles in magnetic resonance. Using the Tavis-Cummings model in the presence of a Rabi drive, we solve a Markovian master equation describing the joint spin-cavity dynamics to derive cooling rates as a function of ensemble size. Our calculations indicate that the coupled angular momentum subspaces of a spin ensemble containing roughly 10(11) electron spins may be polarized in a time many orders of magnitude shorter than the typical thermal relaxation time. The described techniques should permit efficient removal of entropy for spin-based quantum information processors and fast polarization of spin samples. The proposed application of a standard technique in quantum optics to magnetic resonance also serves to reinforce the connection between the two fields, which has recently begun to be explored in further detail due to the development of hybrid designs for manufacturing noise-resilient quantum devices.

  20. Tube failures due to cooling process problem and foreign materials in power plants

    Energy Technology Data Exchange (ETDEWEB)

    Ahmad, J. [Kapar Energy Ventures Sdn Bhd, Jalan Tok Muda, Kapar 42200 (Malaysia); Purbolaksono, J., E-mail: judha@uniten.edu.m [Department of Mechanical Engineering, Universiti Tenaga Nasional, Km 7 Jalan Kajang-Puchong, Kajang 43009, Selangor (Malaysia); Beng, L.C. [Kapar Energy Ventures Sdn Bhd, Jalan Tok Muda, Kapar 42200 (Malaysia)

    2010-07-15

    Cooling process which uses water for heat transfer is an essential factor in coal-fired and nuclear plants. Loss of cooling upset can force the plants to shut down. In particular, this paper reports visual inspections and metallurgical examinations on the failed SA210-A1 right-hand side (RHS) water wall tube of a coal-fired plant. The water wall tube showed the abnormal outer surface colour and has failed with wide-open ductile rupture and thin edges indicating typical signs of short-term overheating. Metallurgical examinations confirmed the failed tube experiencing higher temperature operation. Water flow starvation due to restriction inside the upstream tube is identified as the main root cause of failure. The findings are important to take failure mitigation actions in the future operation. Discussion on the typical problems related to the cooling process in nuclear power plants is also presented.

  1. Microscale Waste Heat Driven Cooling System

    Science.gov (United States)

    2012-05-02

    to the Inter-Agency Power Group Mechanical Working Group Meeting 2012 about the ammonia-water absorption chiller technology demonstrator developed by...Development and Engineering Center is provided. 15. SUBJECT TERMS absorption ; heat actuated cooling 16. SECURITY CLASSIFICATION OF: 17. LIMITATION OF...for a Sustainable Future Sustainable Products for a Sustainable Future Acknowledgments US Army - CERDEC Smaller Lighter Co-Generation & Absorption

  2. Study of Natural Convection Passive Cooling System for Nuclear Reactors

    Science.gov (United States)

    Abdillah, Habibi; Saputra, Geby; Novitrian; Permana, Sidik

    2017-07-01

    Fukushima nuclear reactor accident occurred due to the reactor cooling pumps and followed by all emergencies cooling systems could not work. Therefore, the system which has a passive safety system that rely on natural laws such as natural convection passive cooling system. In natural convection, the cooling material can flow due to the different density of the material due to the temperature difference. To analyze such investigation, a simple apparatus was set up and explains the study of natural convection in a vertical closed-loop system. It was set up that, in the closed loop, there is a heater at the bottom which is representing heat source system from the reactor core and cooler at the top which is showing the cooling system performance in room temperature to make a temperature difference for convection process. The study aims to find some loop configurations and some natural convection performances that can produce an optimum flow of cooling process. The study was done and focused on experimental approach and simulation. The obtained results are showing and analyzing in temperature profile data and the speed of coolant flow at some point on the closed-loop system.

  3. Evaluation of Active Cooling Systems for Non-Residential Buildings

    Directory of Open Access Journals (Sweden)

    M.A. Othuman Mydin

    2014-05-01

    Full Text Available Cooling systems are an essential element in many facets of modern society including cars, computers and buildings. Cooling systems are usually divided into two types: passive and active. Passive cooling transfers heat without using any additional energy while active cooling is a type of heat transfer that uses powered devices such as fans or pumps. This paper will focus on one particular type of passive cooling: air-conditioning systems. An air-conditioning system is defined as controlled air movement, temperature, humidity and cleanliness of a building area. Air conditioning consists of cooling and heating. Therefore, the air-conditioning system should be able to add and remove heat from the area. An air-conditioning system is defined as a control or treatment of air in a confined space. The process that occurs is the air-conditioning system absorbs heat and dust while, at the same time, cleaning the air breathed into a closed space. The purpose of air-conditioning is to maintain a comfortable atmosphere for human life and to meet user requirements. In this paper, air-conditioning systems for non-residential buildings will be presented and discussed.

  4. Active cooling system for Tokamak in-vessel operation manipulator

    Energy Technology Data Exchange (ETDEWEB)

    Yuan, Jianjun, E-mail: yuanjj@sjtu.edu.cn; Chen, Tan; Li, Fashe; Zhang, Weijun; Du, Liang

    2015-10-15

    Highlights: • We summarized most of the challenges of fusion devices to robot systems. • Propose an active cooling system to protect all of the necessary components. • Trial design test and theoretical analysis were conducted. • Overall implementation of the active cooling system was demonstrated. - Abstract: In-vessel operation/inspection is an indispensable task for Tokamak experimental reactor, for a robot/manipulator is more capable in doing this than human being with more precise motion and less risk of damaging the ambient equipment. Considering the demanding conditions of Tokamak, the manipulator should be adaptable to rapid response in the extreme conditions such as high temperature, vacuum and so on. In this paper, we propose an active cooling system embedded into such manipulator. Cameras, motors, gearboxes, sensors, and other mechanical/electrical components could then be designed under ordinary conditions. The cooling system cannot only be a thermal shield since the components are also heat sources in dynamics. We carry out a trial test to verify our proposal, and analyze the active cooling system theoretically, which gives a direction on the optimization by varying design parameters, components and distribution. And based on thermal sensors monitoring and water flow adjusting a closed-loop feedback control of temperature is added to the system. With the preliminary results, we believe that the proposal gives a way to robust and inexpensive design in extreme environment. Further work will concentrate on overall implementation and evaluation of this cooling system with the whole inspection manipulator.

  5. Preliminary design package for prototype solar heating and cooling systems

    Science.gov (United States)

    1978-01-01

    A summary is given of the preliminary analysis and design activity on solar heating and cooling systems. The analysis was made without site specific data other than weather; therefore, the results indicate performance expected under these special conditions. Major items include a market analysis, design approaches, trade studies and other special data required to evaluate the preliminary analysis and design. The program calls for the development and delivery of eight prototype solar heating and cooling systems for installation and operational test. Two heating and six heating and cooling units will be delivered for Single Family Residences, Multiple-family Residences and commercial applications.

  6. Costs and cost algorithms for dry cooling tower systems

    Energy Technology Data Exchange (ETDEWEB)

    Ard, P.A.; Henager, C.H.; Pratt, D.R.; Wiles, L.E.

    1976-09-01

    Costs were obtained and cast models prepared for the major components beyond the turbine exhaust flange of a dry cooling system using either water or ammonia as the intermediate heat exchange fluid. (LCL)

  7. Technical analysis of a river basin-based model of advanced power plant cooling technologies for mitigating water management challenges

    Energy Technology Data Exchange (ETDEWEB)

    Stillwell, Ashlynn S [Department of Civil, Architectural, and Environmental Engineering, University of Texas at Austin, 1 University Station C1786, Austin, TX 78712 (United States); Clayton, Mary E; Webber, Michael E, E-mail: ashlynn.stillwell@mail.utexas.edu, E-mail: mclayton34@mail.utexas.edu, E-mail: webber@mail.utexas.edu [Department of Mechanical Engineering, University of Texas at Austin, 1 University Station C2200, Austin, TX 78712 (United States)

    2011-07-15

    Thermoelectric power plants require large volumes of water for cooling, which can introduce drought vulnerability and compete with other water needs. Alternative cooling technologies, such as cooling towers and hybrid wet-dry or dry cooling, present opportunities to reduce water diversions. This case study uses a custom, geographically resolved river basin-based model for eleven river basins in the state of Texas (the Brazos and San Jacinto-Brazos, Colorado and Colorado-Brazos, Cypress, Neches, Nueces, Red, Sabine, San Jacinto, and Trinity River basins), focusing on the Brazos River basin, to analyze water availability during drought. We utilized two existing water availability models for our analysis: (1) the full execution of water rights-a scenario where each water rights holder diverts the full permitted volume with zero return flow, and (2) current conditions-a scenario reflecting actual diversions with associated return flows. Our model results show that switching the cooling technologies at power plants in the eleven analyzed river basins to less water-intensive alternative designs can potentially reduce annual water diversions by 247-703 million m{sup 3}-enough water for 1.3-3.6 million people annually. We consider these results in a geographic context using geographic information system tools and then analyze volume reliability, which is a policymaker's metric that indicates the percentage of total demand actually supplied over a given period. This geographic and volume reliability analysis serves as a measure of drought susceptibility in response to changes in thermoelectric cooling technologies. While these water diversion savings do not alleviate all reliability concerns, the additional streamflow from the use of dry cooling alleviates drought concerns for some municipal water rights holders and might also be sufficient to uphold instream flow requirements for important bays and estuaries on the Texas Gulf coast.

  8. Control of mineral scale deposition in cooling systems using secondary-treated municipal wastewater.

    Science.gov (United States)

    Li, Heng; Hsieh, Ming-Kai; Chien, Shih-Hsiang; Monnell, Jason D; Dzombak, David A; Vidic, Radisav D

    2011-01-01

    Secondary-treated municipal wastewater (MWW) is a promising alternative to freshwater as power plant cooling system makeup water, especially in arid regions. A prominent challenge for the successful use of MWW for cooling is potentially severe mineral deposition (scaling) on pipe surfaces. In this study, theoretical, laboratory, and field work was conducted to evaluate the mineral deposition potential of MWW and its deposition control strategies under conditions relevant to power plant cooling systems. Polymaleic acid (PMA) was found to effectively reduce scale formation when the makeup water was concentrated four times in a recirculating cooling system. It was the most effective deposition inhibitor of those studied when applied at 10 mg/L dosing level in a synthetic MWW. However, the deposition inhibition by PMA was compromised by free chlorine added for biogrowth control. Ammonia present in the wastewater suppressed the reaction of the free chlorine with PMA through the formation of chloramines. Monochloramine, an alternative to free chlorine, was found to be less reactive with PMA than free chlorine. In pilot tests, scaling control was more challenging due to the occurrence of biofouling even with effective control of suspended bacteria. Phosphorous-based corrosion inhibitors are not appropriate due to their significant loss through precipitation reactions with calcium. Chemical equilibrium modeling helped with interpretation of mineral precipitation behavior but must be used with caution for recirculating cooling systems, especially with use of MWW, where kinetic limitations and complex water chemistries often prevail. Copyright © 2010 Elsevier Ltd. All rights reserved.

  9. User's guide for the BNW-III optimization code for modular dry/wet-cooled power plants

    Energy Technology Data Exchange (ETDEWEB)

    Braun, D.J.; Faletti, D.W.

    1984-09-01

    This user's guide describes BNW-III, a computer code developed by the Pacific Northwest Laboratory (PNL) as part of the Dry Cooling Enhancement Program sponsored by the US Department of Energy (DOE). The BNW-III code models a modular dry/wet cooling system for a nuclear or fossil fuel power plant. The purpose of this guide is to give the code user a brief description of what the BNW-III code is and how to use it. It describes the cooling system being modeled and the various models used. A detailed description of code input and code output is also included. The BNW-III code was developed to analyze a specific cooling system layout. However, there is a large degree of freedom in the type of cooling modules that can be selected and in the performance of those modules. The costs of the modules are input to the code, giving the user a great deal of flexibility.

  10. Adsorption Cooling System Using Metal-Impregnated Zeolite-4A

    Directory of Open Access Journals (Sweden)

    Somsuk Trisupakitti

    2016-01-01

    Full Text Available The adsorption cooling systems have been developed to replace vapor compression due to their benefits of being environmentally friendly and energy saving. We prepared zeolite-4A and experimental cooling performance test of zeolite-water adsorption system. The adsorption cooling test-rig includes adsorber, evaporator, and condenser which perform in vacuum atmosphere. The maximum and minimum water adsorption capacity of different zeolites and COP were used to assess the performance of the adsorption cooling system. We found that loading zeolite-4A with higher levels of silver and copper increased COP. The Cu6%/zeolite-4A had the highest COP at 0.56 while COP of zeolite-4A alone was 0.38. Calculating the acceleration rate of zeolite-4A when adding 6% of copper would accelerate the COP at 46%.

  11. Liquid cooling system for the vibro-tactile threshold device.

    Science.gov (United States)

    Parsons, Erin M; Redd, Christian; Gandhi, Minu S; Tuckett, Robert P; Bamberg, Stacy J Morris

    2011-01-01

    Vibrotactile threshold testing has been used to investigate activation of human somatosensory pathways. A portable vibrotactile threshold testing device called the Vibrotactile Threshold Evaluator for the Workplace (VTEW) was designed for screening of carpal tunnel syndrome in the workplace, and initially contained a small fan for cooling. During subject testing, the device is operated intermittently, which causes the linear actuator to warm the tactile probe. The probe causes discomfort for some subjects. During testing, the probe heated to 42 °C within 90 seconds of continuous operation. A liquid cooling system was implemented to dissipate heat from the probe. The liquid cooling system maintains a steady state temperature of 36 °C for continuous actuation of the probe. The liquid cooling system is capable of maintaining a safe operating temperature, without adding erroneous vibrations to the device. However, the cooling system deters the portability of the device. Further research will investigate how to make the liquid cooling system portable and implements vibrotactile threshold testing in the workplace to quickly evaluate whether or not a person has early symptoms of carpal tunnel syndrome.

  12. Simulation of an active cooling system for photovoltaic modules

    Science.gov (United States)

    Abdelhakim, Lotfi

    2016-06-01

    Photovoltaic cells are devices that convert solar radiation directly into electricity. However, solar radiation increases the photovoltaic cells temperature [1] [2]. The temperature has an influence on the degradation of the cell efficiency and the lifetime of a PV cell. This work reports on a water cooling technique for photovoltaic panel, whereby the cooling system was placed at the front surface of the cells to dissipate excess heat away and to block unwanted radiation. By using water as a cooling medium for the photovoltaic solar cells, the overheating of closed panel is greatly reduced without prejudicing luminosity. The water also acts as a filter to remove a portion of solar spectrum in the infrared band but allows transmission of the visible spectrum most useful for the PV operation. To improve the cooling system efficiency and electrical efficiency, uniform flow rate among the cooling system is required to ensure uniform distribution of the operating temperature of the PV cells. The aims of this study are to develop a 3D thermal model to simulate the cooling and heat transfer in Photovoltaic panel and to recommend a cooling technique for the PV panel. The velocity, pressure and temperature distribution of the three-dimensional flow across the cooling block were determined using the commercial package, Fluent. The second objective of this work is to study the influence of the geometrical dimensions of the panel, water mass flow rate and water inlet temperature on the flow distribution and the solar panel temperature. The results obtained by the model are compared with experimental results from testing the prototype of the cooling device.

  13. Simulation of an active cooling system for photovoltaic modules

    Energy Technology Data Exchange (ETDEWEB)

    Abdelhakim, Lotfi [Széchenyi István University of Applied Sciences, Department of Mathematics, P.O.Box 701, H-9007 Győr (Hungary)

    2016-06-08

    Photovoltaic cells are devices that convert solar radiation directly into electricity. However, solar radiation increases the photovoltaic cells temperature [1] [2]. The temperature has an influence on the degradation of the cell efficiency and the lifetime of a PV cell. This work reports on a water cooling technique for photovoltaic panel, whereby the cooling system was placed at the front surface of the cells to dissipate excess heat away and to block unwanted radiation. By using water as a cooling medium for the photovoltaic solar cells, the overheating of closed panel is greatly reduced without prejudicing luminosity. The water also acts as a filter to remove a portion of solar spectrum in the infrared band but allows transmission of the visible spectrum most useful for the PV operation. To improve the cooling system efficiency and electrical efficiency, uniform flow rate among the cooling system is required to ensure uniform distribution of the operating temperature of the PV cells. The aims of this study are to develop a 3D thermal model to simulate the cooling and heat transfer in Photovoltaic panel and to recommend a cooling technique for the PV panel. The velocity, pressure and temperature distribution of the three-dimensional flow across the cooling block were determined using the commercial package, Fluent. The second objective of this work is to study the influence of the geometrical dimensions of the panel, water mass flow rate and water inlet temperature on the flow distribution and the solar panel temperature. The results obtained by the model are compared with experimental results from testing the prototype of the cooling device.

  14. Solar heating and cooling system design and development

    Science.gov (United States)

    1979-01-01

    The design and development of marketable solar heating and cooling systems for single family and commercial applications is described. The delivery, installation, and monitoring of the prototype systems are discussed. Seven operational test sites are discussed in terms of system performance. Problems encountered with equipment and installation were usually due to lack of skills required for solar system installation.

  15. Active noise canceling system for mechanically cooled germanium radiation detectors

    Science.gov (United States)

    Nelson, Karl Einar; Burks, Morgan T

    2014-04-22

    A microphonics noise cancellation system and method for improving the energy resolution for mechanically cooled high-purity Germanium (HPGe) detector systems. A classical adaptive noise canceling digital processing system using an adaptive predictor is used in an MCA to attenuate the microphonics noise source making the system more deployable.

  16. The ITER neutral beam test facility: Designs of the general infrastructure, cryosystem and cooling plant

    Energy Technology Data Exchange (ETDEWEB)

    Cordier, J.J. [Association EURATOM-CEA, DSM, Departement Recherche Fusion Controlee, CEA/Cadarache, bat 506, F-13108 Saint Paul Lez Durance Cedex (France)]. E-mail: jean-jacques.cordier@cea.fr; Hemsworth, R. [Association EURATOM-CEA, DSM, Departement Recherche Fusion Controlee, CEA/Cadarache, bat 506, F-13108 Saint Paul Lez Durance Cedex (France); Chantant, M. [Association EURATOM-CEA, DSM, Departement Recherche Fusion Controlee, CEA/Cadarache, bat 506, F-13108 Saint Paul Lez Durance Cedex (France); Gravil, B. [Association EURATOM-CEA, DSM, Departement Recherche Fusion Controlee, CEA/Cadarache, bat 506, F-13108 Saint Paul Lez Durance Cedex (France); Henry, D. [Association EURATOM-CEA, DSM, Departement Recherche Fusion Controlee, CEA/Cadarache, bat 506, F-13108 Saint Paul Lez Durance Cedex (France); Sabathier, F. [Association EURATOM-CEA, DSM, Departement Recherche Fusion Controlee, CEA/Cadarache, bat 506, F-13108 Saint Paul Lez Durance Cedex (France); Doceul, L. [Association EURATOM-CEA, DSM, Departement Recherche Fusion Controlee, CEA/Cadarache, bat 506, F-13108 Saint Paul Lez Durance Cedex (France); Thomas, E. [Association EURATOM-CEA, DSM, Departement Recherche Fusion Controlee, CEA/Cadarache, bat 506, F-13108 Saint Paul Lez Durance Cedex (France); Houtte, D. van [Association EURATOM-CEA, DSM, Departement Recherche Fusion Controlee, CEA/Cadarache, bat 506, F-13108 Saint Paul Lez Durance Cedex (France); Zaccaria, P. [CONSORZIO RFX Association EURATOM-ENEA, Corso Stati Uniti 4, I-35127 Padova (Italy); Antoni, V. [CONSORZIO RFX Association EURATOM-ENEA, Corso Stati Uniti 4, I-35127 Padova (Italy); Bello, S. Dal; Marcuzzi, D. [CONSORZIO RFX Association EURATOM-ENEA, Corso Stati Uniti 4, I-35127 Padova (Italy); Antipenkov, A.; Day, C.; Dremel, M. [FZK, Institut fuer Technische Physik, Karlsruhe 76021 (Germany); Mondino, P.L. [EFDA CSU, Max-Planck-Institut fuer Plasma Physik Boltzmannstr. 2, D-85748 Garching (Germany)

    2005-11-15

    The CEA Association is involved, in close collaboration with ENEA, FZK, IPP and UKAEA European Associations, in the first ITER neutral beam (NB) injector and the ITER neutral beam test facility design (EFDA task ref. TW3-THHN-IITF1). A total power of about 50 MW will have to be removed in steady state on the neutral beam test facility (NBTF). The main purpose of this task is to make progress with the detailed design of the first ITER NB injector and to start the conceptual design of the ITER NBTF. The general infrastructure layout of a generic site for the NBTF includes the test facility itself equipped with a dedicated beamline vessel [P.L. Zaccaria, et al., Maintenance schemes for the ITER neutral beam test facility, this conference] and integration studies of associated auxiliaries such as cooling plant, cryoplant and forepumping system.

  17. Integrated numerical methods for hypersonic aircraft cooling systems analysis

    Science.gov (United States)

    Petley, Dennis H.; Jones, Stuart C.; Dziedzic, William M.

    1992-01-01

    Numerical methods have been developed for the analysis of hypersonic aircraft cooling systems. A general purpose finite difference thermal analysis code is used to determine areas which must be cooled. Complex cooling networks of series and parallel flow can be analyzed using a finite difference computer program. Both internal fluid flow and heat transfer are analyzed, because increased heat flow causes a decrease in the flow of the coolant. The steady state solution is a successive point iterative method. The transient analysis uses implicit forward-backward differencing. Several examples of the use of the program in studies of hypersonic aircraft and rockets are provided.

  18. Progress of the Water Cooling System for CYCIAE-100

    Institute of Scientific and Technical Information of China (English)

    LI; Zhen-guo; WU; Long-cheng; LIU; Geng-guo

    2012-01-01

    <正>According to the general construction schedule of the BRIF project, the water cooling system for CYCIAE-100 has achieved a significant progress in 2012, its progress can be summarized as follows. 1) Inside wiring of 7 water distribution cabinets were completed. 2) Manufacturer selection of circulating water cooling unit and deionized water production equipment was decided after market survey and bidding process. The contracts were formally signed in February. The deionized water production equipment was ready in May and the circulating water cooling

  19. Cooling and shielding systems for infrared detectors - requirements and limits.

    Science.gov (United States)

    Wiecek, B

    2005-01-01

    This paper presents three main cooling systems used for infrared detectors. At first thermoelectric devices are discussed. They allow cooling down the detector with low efficiency and not to the very low temperature. They do not generate any vibrations and therefore are suitable for thermal detectors, where the microphone effect can decrease their performance. Photon detectors need to be cooled down even to 77K or better. The only way to have such deep cooling is to use the cooler based on thermodynamic cycle such as Stirling one. With the high efficiency one can easily obtain cryogenic temperature for a detector. The electromagnetic noise and vibration generation are the main disadvantages of using such devices. Joule-Thomson effect during gas expansion is 3rdcooling system discussed in the paper. It is highly effective process, used for gas liquefaction too. The working gas is being removed during cooling into the atmosphere, so the need of continuous supplying with compressed one, what makes this system very difficult for remote applications. In the paper, simple calculations are presented to illustrate the advantages and disadvantages of the different cooling systems.

  20. Studies and Design of the ECAL (CMS) Cooling System

    CERN Document Server

    Gasser, D

    2000-01-01

    The Electromagnetic CALorimeter (ECAL) sub-detector for the CMS experiment has to achieve very tight requirements in terms of temperature stability. The CV group is now involved in the design of a cooling system for ECAL. The status and the content of the work which has been done will be explained. The theoretical studies which helped to understand the ECAL thermal behaviour and the efficiency of the hydraulic network in charge of the cooling will first be briefly presented. Moreover, it will be shown how these studies helped to improve the cooling design inside ECAL. A proposal for an external cooling system of ECAL will be presented as well. Finally, experimental thermal tests, which are planned for April 2000 on a prototype corresponding to a part of ECAL, will be described. These tests aim to check the technical solutions which can be applied in the context of the real ECAL detector.

  1. Effect of input power on cooling property of a thermoacoustic cooling system with diameter-expanded prime movers

    Science.gov (United States)

    Ueno, So; Sakamoto, Shin-ichi; Orino, Yuichiro; Wada, Takahiro; Inui, Yoshitaka; Watanabe, Yoshiaki

    2016-07-01

    We studied a thermoacoustic cooling system driven at low temperatures to make practical use of the system. Aiming to reduce the driving temperature of the thermoacoustic system, we developed a loop-tube-type thermoacoustic system with diameter-expanded two-stage prime movers, i.e., a heat-to-sound transducer. The system drove at 67 °C. Additionally, we developed a prototype for a thermoacoustic cooling system with a diameter-expanded two-stage prime mover. In the experiment, the cooling point temperature was decreased by 4.4 °C from room temperature, i.e., 20 °C. To improve the cooling performance of the prototype thermoacoustic cooling system, we experimentally investigated the effect of increasing the input power on the cooling performance.

  2. Desiccant dehumidification and cooling systems assessment and analysis

    Energy Technology Data Exchange (ETDEWEB)

    Collier, R.K. Jr. [Collier Engineering, Reno, NV (United States)

    1997-09-01

    The objective of this report is to provide a preliminary analysis of the principles, sensitivities, and potential for national energy savings of desiccant cooling and dehumidification systems. The report is divided into four sections. Section I deals with the maximum theoretical performance of ideal desiccant cooling systems. Section II looks at the performance effects of non-ideal behavior of system components. Section III examines the effects of outdoor air properties on desiccant cooling system performance. Section IV analyzes the applicability of desiccant cooling systems to reduce primary energy requirements for providing space conditioning in buildings. A basic desiccation process performs no useful work (cooling). That is, a desiccant material drying air is close to an isenthalpic process. Latent energy is merely converted to sensible energy. Only when heat exchange is applied to the desiccated air is any cooling accomplished. This characteristic is generic to all desiccant cycles and critical to understanding their operation. The analyses of Section I show that desiccant cooling cycles can theoretically achieve extremely high thermal CoP`s (>2). The general conclusion from Section II is that ventilation air processing is the most viable application for the solid desiccant equipment analyzed. The results from the seasonal simulations performed in Section III indicate that, generally, the seasonal performance of the desiccant system does not change significantly from that predicted for outdoor conditions. Results from Section IV show that all of the candidate desiccant systems can save energy relative to standard vapor-compression systems. The largest energy savings are achieved by the enthalpy exchange devise.

  3. Use of a temperature-initiated passive cooling system (TIPACS) for the modular high-temperature gas-cooled reactor cavity cooling system (RCCS)

    Energy Technology Data Exchange (ETDEWEB)

    Forsberg, C.W.; Conklin, J.; Reich, W.J.

    1994-04-01

    A new type of passive cooling system has been invented (Forsberg 1993): the Temperature-Initiated Passive Cooling System (TIPACS). The characteristics of the TIPACS potentially match requirements for an improved reactor-cavity-cooling system (RCCS) for the modular high-temperature gas-cooled reactor (MHTGR). This report is an initial evaluation of the TIPACS for the MHTGR with a Rankines (steam) power conversion cycle. Limited evaluations were made of applying the TIPACS to MHTGRs with reactor pressure vessel temperatures up to 450 C. These temperatures may occur in designs of Brayton cycle (gas turbine) and process heat MHTGRs. The report is structured as follows. Section 2 describes the containment cooling issues associated with the MHTGR and the requirements for such a cooling system. Section 3 describes TIPACS in nonmathematical terms. Section 4 describes TIPACS`s heat-removal capabilities. Section 5 analyzes the operation of the temperature-control mechanism that determines under what conditions the TIPACS rejects heat to the environment. Section 6 addresses other design and operational issues. Section 7 identifies uncertainties, and Section 8 provides conclusions. The appendixes provide the detailed data and models used in the analysis.

  4. Modeling and energy simulation of the variable refrigerant flow air conditioning system with water-cooled condenser under cooling conditions

    Energy Technology Data Exchange (ETDEWEB)

    Li, Yueming; Wu, Jingyi [Shanghai Jiao Tong University, Institute of Refrigeration and Cryogenics (China); Shiochi, Sumio [Daikin Industries Ltd. (Japan)

    2009-09-15

    As a new system, variable refrigerant flow system with water-cooled condenser (water-cooled VRF) can offer several interesting characteristics for potential users. However, at present, its dynamic simulation simultaneously in association with building and other equipments is not yet included in the energy simulation programs. Based on the EnergyPlus's codes, and using manufacturer's performance parameters and data, the special simulation module for water-cooled VRF is developed and embedded in the software of EnergyPlus. After modeling and testing the new module, on the basis of a typical office building in Shanghai with water-cooled VRF system, the monthly and seasonal cooling energy consumption and the breakdown of the total power consumption are analyzed. The simulation results show that, during the whole cooling period, the fan-coil plus fresh air (FPFA) system consumes about 20% more power than the water-cooled VRF system does. The power comparison between the water-cooled VRF system and the air-cooled VRF system is performed too. All of these can provide designers some ideas to analyze the energy features of this new system and then to determine a better scheme of the air conditioning system. (author)

  5. The Straw Cooling System in the ATLAS TRT

    CERN Document Server

    Godlewski, J

    2002-01-01

    This technical note deals with the straw cooling system for the TRT End-caps in the ATLAS detector. The combination of a high gas flow requirement and small gas volumes yield unfavourable properties in terms of control stability. Early experiments on a prototype of the final cooling system, showed that pressure losses in the gas distribution lines must be decreased to fulfil the pressure control requirements. One part of this note is devoted to a cfd analysis of a critical component, an elbow duct, in the gas distribution line. To enable analyses of the overall cooling system dynamics, generic simulation components were created and applied in a simulation of the prototype cooling system. The simulation was verified by an equivalent experiment on the prototype cooling system. The manifolds that distribute and collect the gas in the group-of-wheels are dealt with in the last chapter where results from a fluid mechanical model implemented in Matlab are compared to values obtained by experiments

  6. Simulations and economic analyses of desiccant cooling systems

    Energy Technology Data Exchange (ETDEWEB)

    Shelpuk, B. C.; Hooker, D. W.; Jorgensen, G. J.; Bingham, C. E.

    1979-06-01

    The progress to date in the development and analysis of computer simulations of solar-powered desiccant cooling using an axial-flow disc-type dehumidifier wheel, solar-powered space heating, and electrically driven, standard vapor-compression air-conditioning systems for residential use is documented. Computer simulations for both solar and conventional heating and cooling systems were performed for 12-month heating and cooling seasons. Annual thermal performance and the resulting life cycle costs for both types of systems were analyzed and compared. The heating/cooling season simulations were run for five U.S. cities representing a wide range of climatic conditions and insolation. With the informaion resulting from these simulations, the optimum air-conditioning system was chosen to maximize the conservation of fossil fuels and minimize operating costs. Because of the increasing use of residential air conditioning employing electrically driven vapor-compression coolers, the five locations were studied to determine if it would be beneficial (in terms of both economics and fossil fuel displacement) to displace fossil-fuel-powered vapor-compression coolers and natural gas space heaters with solar-powered heating and desiccant cooling systems.

  7. The convection cooling system of the Yakutsk permafrost seed repository

    Institute of Scientific and Technical Information of China (English)

    Vladimir N.Panin; Georgii P.Kuzmin

    2014-01-01

    Temperature is critical to maintaining seed viability under long term storage conditions. It has been common practice to use refrigeration systems to maintain required storage temperatures. A seed repository constructed in permafrost in Ya kutsk, Russia is the first seed storage facility that relies solely on natural cold. This paper describes the design and per formance of the cooling system of the repository. An innovative aspect of the cooling system is that it utilizes the patterns of temperature wave propagation in permafrost. Predicted and measured ground temperatures for the first year of operation are presented and analyzed. Results indicate that convection air cooling systems can be used to control the temperature regime in underground facilities in permafrost.

  8. Utilization of municipal wastewater for cooling in thermoelectric power plants: Evaluation of the combined cost of makeup water treatment and increased condenser fouling

    Energy Technology Data Exchange (ETDEWEB)

    Walker, Michael E. [Illinois Inst. of Technology, Chicago, IL (United States). Dept. of Chemical and Biological Engineering; Theregowda, Ranjani B. [Carnegie Mellon Univ., Pittsburgh, PA (United States). Dept of Civil and Mechanical Engineering; Safari, Iman [Illinois Inst. of Technology, Chicago, IL (United States). Dept. of Chemical and Biological Engineering; Abbasian, Javad [Illinois Inst. of Technology, Chicago, IL (United States). Dept. of Chemical and Biological Engineering; Arastoopour, Hamid [Illinois Inst. of Technology, Chicago, IL (United States). Dept. of Chemical and Biological Engineering; Dzombak, David A. [Carnegie Mellon Univ., Pittsburgh, PA (United States). Dept of Civil and Mechanical Engineering; Hsieh, Ming-Kai [Tamkang Univ., Taipei (Taiwan). Waer Resources Management and Policy Research Center; Miller, David C. [National Energy Technology Lab. (NETL), Morgantown, WV (United States)

    2013-10-01

    A methodology is presented to calculate the total combined cost (TCC) of water sourcing, water treatment and condenser fouling in the recirculating cooling systems of thermoelectric power plants. The methodology is employed to evaluate the economic viability of using treated municipal wastewater (MWW) to replace the use of freshwater as makeup water to power plant cooling systems. Cost analyses are presented for a reference power plant and five different tertiary treatment scenarios to reduce the scaling tendencies of MWW. Results indicate that a 550 MW sub-critical coal fired power plant with a makeup water requirement of 29.3 ML/day has a TCC of $3.0 - 3.2 million/yr associated with the use of treated MWW for cooling. (All costs USD 2009). This translates to a freshwater conservation cost of $0.29/kL, which is considerably lower than that of dry air cooling technology, $1.5/kL, as well as the 2020 conservation cost target set by the U.S. Department of Energy, $0.74/kL. Results also show that if the available price of freshwater exceeds that of secondary-treated MWW by more than $0.13-0.14/kL, it can be economically advantageous to purchase secondary MWW and treat it for utilization in the recirculating cooling system of a thermoelectric power plant.

  9. Interim Report: Air-Cooled Condensers for Next Generation Geothermal Power Plants Improved Binary Cycle Performance

    Energy Technology Data Exchange (ETDEWEB)

    Daniel S. Wendt; Greg L. Mines

    2010-09-01

    As geothermal resources that are more expensive to develop are utilized for power generation, there will be increased incentive to use more efficient power plants. This is expected to be the case with Enhanced Geothermal System (EGS) resources. These resources will likely require wells drilled to depths greater than encountered with hydrothermal resources, and will have the added costs for stimulation to create the subsurface reservoir. It is postulated that plants generating power from these resources will likely utilize the binary cycle technology where heat is rejected sensibly to the ambient. The consumptive use of a portion of the produced geothermal fluid for evaporative heat rejection in the conventional flash-steam conversion cycle is likely to preclude its use with EGS resources. This will be especially true in those areas where there is a high demand for finite supplies of water. Though they have no consumptive use of water, using air-cooling systems for heat rejection has disadvantages. These systems have higher capital costs, reduced power output (heat is rejected at the higher dry-bulb temperature), increased parasitics (fan power), and greater variability in power generation on both a diurnal and annual basis (larger variation in the dry-bulb temperature). This is an interim report for the task ‘Air-Cooled Condensers in Next- Generation Conversion Systems’. The work performed was specifically aimed at a plant that uses commercially available binary cycle technologies with an EGS resource. Concepts were evaluated that have the potential to increase performance, lower cost, or mitigate the adverse effects of off-design operation. The impact on both cost and performance were determined for the concepts considered, and the scenarios identified where a particular concept is best suited. Most, but not all, of the concepts evaluated are associated with the rejection of heat. This report specifically addresses three of the concepts evaluated: the use of

  10. Study on Heat Recovery Technology of Closed Cooling Water System for Nuclear Power Plants%核电厂闭式冷却水系统余热回收技术研究

    Institute of Scientific and Technical Information of China (English)

    石建中; 侯平利; 胡友情; 王世勇

    2011-01-01

    提出了一种能回收闭式冷却水系统余热的节能减排技术方案,可在凝结水温度不大于34℃的条件下利用凝结水来代替海水吸收闭式冷却水系统中的余热.文中给出了红沿河核电厂1000MW级机组的应用分析实例.结果表明,通过回收闭式冷却水系统余热可增加机组出力约1.5 MW,减少温排水海洋污染约2.1×107t/a,产生经济效益约3.58×106元/a.%A new technology of energy saving and emission reducing which can recover the heat of closed cooling water was proposed. The condensate is used to absorb the heat from the closed cooling water when the condensate temperature is not greater than 34*10, instead of sea water. An application case for Hongyanhe 1000 MW class nuclear power plant is given to show that with this method, the unit output would be increased about 1.5 MW, the warm water emission would be reduced about 2.1xlO71 /a and the economic benefit would be increased about 3.58xlO6 RMB each year.

  11. Tool for economic and environmental analysis of hybrid plants for district cooling and district heating - 'District cooling 2.0'. Final report and user guide; Vaerktoej til oekonomisk og miljoemaessig analyse af hybridanlaeg til fjernkoeling og fjernvarme. Fjernkoel 2.0. Slutrapport og brugermanual

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2013-03-15

    The purpose of the tool is to help bring district cooling solutions into consideration by facilitating rapid technical / economic and environmental analysis of district cooling solutions - also with heat pump operation. The tool is a screening tool intended for specific cases with actual data from reality. The tool can analyze the simultaneous production of heat and cooling, and use of storage can make district cooling even more profitable. It is also possible to analyze the importance of flexible electricity and heating prices and see how they can be utilized, including the calculation of the probable prices on heating and cooling, and investments. The tool can make calculations on the following plant types: - Systems with only cooling without cold storage; - Systems with only cooling with cold storage; - Systems with cooling and heating controlled by cooling - with heat storage; - Systems with heating and cooling controlled by heating - with heating and cooling storage; - Systems with cooling and heating with optimized management - with heat storage. The tool can also be used to make general assessments, for example, to analyze the importance of flexible electricity and heating prices of typical district cooling systems, and for that matter, heat pump systems. (LN)

  12. Cooling system optimization analysis for hot forming processes

    Science.gov (United States)

    Ghoo, Bonyoung; Umezu, Yasuyoshi; Watanabe, Yuko

    2013-12-01

    Hot forming technology was developed to produce automotive panels having ultra-high tensile stress over 1500MPa. The elevated temperature corresponds with decreased flow stress and increased ductility. Furthermore, hot forming products have almost zero springback amounts. This advanced forming technology accelerates the needs for numerical simulations coupling with thermal-mechanical formulations. In the present study, 3-dimensional finite element analyses for hot forming processes are conducted using JSTAMP/NV and LS-DYNA considering cooling system. Special attention is paid to the optimization of cooling system using thermo-mechanical finite element analysis through the influence of various cooling parameters. The presented work shows an adequate cooling system functions and microstructural phase transformation material model together with a proper set of numerical parameters can give both efficient and accurate design insight in hot forming manufacturing process. JSTAMP/NV and LS-DYNA can become a robust combination set for complex hot forming analysis which needs thermo-mechanical and microstructural material modeling and various process modeling. The use of the new JSTAMP/NV function for multishot manufacturing process is shown good capabilities in cooling system evaluation. And the use of the advanced LS-DYNA microstructural phase transformation model is shown good evaluation results in martensite amount and Vickers hardness after quenching.

  13. 间接空气冷凝扩展表面换热器结构优化%Power Plant Cooling System Type Slotted Aluminum Fin Surface Heat Transfer and Flow Resistance Characteristics of Numerical Study

    Institute of Scientific and Technical Information of China (English)

    安恩科; 张浏骏; 冯祥

    2014-01-01

    Because of low cost , easy molding Aluminum finned tube is widely applied in the indirect air -cooling condenser , the relationship between the heat transfer coefficient and resistance on air speed to aluminum finned tube heat exchanger design and operation is very important.Using computational fluid dynamics ( CFD) method, the heat resistance performance on three structures of aluminum fin heat exchangers are studied by numerical simulation , the calculation results show that , for the same diameter , the heat transfer coefficient of single bridge and the double bridge structure is basically the same , but the double bridge resistance increased; for single or double bridge struc-ture, Large diameter has the large heat transfer coefficient , at the same time resistance increases more; when the fin thinning , the heat transfer coefficient is basically unchanged , but the resistance is obviously reduced.The re-search results has an important reference value on the economic operation of the air cooled condenser and air cooling power plant.%铝翅片管由于成本低、易于成型在间接空冷冷凝器上有广泛应用,其传热系数和阻力与空气速度之间的关系对铝翅片管换热器设计和运行很重要。应用计算流体力学(CFD)方法,对三种结构铝翅片换热器的换热及阻力性能进行了数值模拟,计算结果表明,对于相同的管径,单桥与双桥结构的传热系数基本相同,而双桥的阻力有所增大;对于单桥或双桥结构来说,大管结构的传热系数增大,同时阻力增大较多;当翅片减薄时,传热系数基本不变,而阻力有明显的减小。研究结果对提高空冷凝汽器乃至空冷电厂的运行经济性都具有重要的参考价值。

  14. Thermotunneling Based Cooling Systems for High Efficiency Buildings

    Energy Technology Data Exchange (ETDEWEB)

    Aimi, Marco; Arik, Mehmet; Bray, James; Gorczyca, Thomas; Michael, Darryl; Weaver, Stan

    2007-09-30

    GE Global Research's overall objective was to develop a novel thermotunneling-cooling device. The end use for these devices is the replacement of vapor cycle compression (VCC) units in residential and commercial cooling and refrigeration systems. Thermotunneling devices offer many advantages over vapor cycle compression cooling units. These include quiet, reliable, non-moving parts operation without refrigerant gases. Additionally theoretical calculations suggest that the efficiency of thermotunneling devices can be 1.5-2x that of VCC units. Given these attributes it can be seen that thermotunneling devices have the potential for dramatic energy savings and are environmentally friendly. A thermotunneling device consists of two low work function electrodes separated by a sub 10 nanometer-sized gap. Cooling by thermotunneling refers to the transport of hot electrons across the gap, from the object to be cooled (cathode) to the heat rejection electrode (anode), by an applied potential. GE Global Research's goal was to model, design, fabricate devices and demonstrate cooling base on the thermotunneling technology.

  15. A data acquisition system for water heating and cooling experiments

    Science.gov (United States)

    Perea Martins, J. E. M.

    2017-01-01

    This work presents a simple analogue waterproof temperature probe design and its electronic interfacing with a computer to compose a data acquisition system for water temperature measurement. It also demonstrates the system usage through an experiment to verify the water heating period with an electric heater and another to verify the Newton’s law of cooling

  16. Design and Control of Hydronic Radiant Cooling Systems

    Science.gov (United States)

    Feng, Jingjuan

    Improving energy efficiency in the Heating Ventilation and Air conditioning (HVAC) systems in buildings is critical to achieve the energy reduction in the building sector, which consumes 41% of all primary energy produced in the United States, and was responsible for nearly half of U.S. CO2 emissions. Based on a report by the New Building Institute (NBI), when HVAC systems are used, about half of the zero net energy (ZNE) buildings report using a radiant cooling/heating system, often in conjunction with ground source heat pumps. Radiant systems differ from air systems in the main heat transfer mechanism used to remove heat from a space, and in their control characteristics when responding to changes in control signals and room thermal conditions. This dissertation investigates three related design and control topics: cooling load calculations, cooling capacity estimation, and control for the heavyweight radiant systems. These three issues are fundamental to the development of accurate design/modeling tools, relevant performance testing methods, and ultimately the realization of the potential energy benefits of radiant systems. Cooling load calculations are a crucial step in designing any HVAC system. In the current standards, cooling load is defined and calculated independent of HVAC system type. In this dissertation, I present research evidence that sensible zone cooling loads for radiant systems are different from cooling loads for traditional air systems. Energy simulations, in EnergyPlus, and laboratory experiments were conducted to investigate the heat transfer dynamics in spaces conditioned by radiant and air systems. The results show that the magnitude of the cooling load difference between the two systems ranges from 7-85%, and radiant systems remove heat faster than air systems. For the experimental tested conditions, 75-82% of total heat gain was removed by radiant system during the period when the heater (simulating the heat gain) was on, while for air

  17. The development of a solar residential heating and cooling system

    Science.gov (United States)

    1975-01-01

    The MSFC solar heating and cooling facility was assembled to demonstrate the engineering feasibility of utilizing solar energy for heating and cooling buildings, to provide an engineering evaluation of the total system and the key subsystems, and to investigate areas of possible improvement in design and efficiency. The basic solar heating and cooling system utilizes a flat plate solar energy collector, a large water tank for thermal energy storage, heat exchangers for space heating, and an absorption cycle air conditioner for space cooling. A complete description of all systems is given. Development activities for this test system included assembly, checkout, operation, modification, and data analysis, all of which are discussed. Selected data analyses for the first 15 weeks of testing are included, findings associated with energy storage and the energy storage system are outlined, and conclusions resulting from test findings are provided. An evaluation of the data for summer operation indicates that the current system is capable of supplying an average of 50 percent of the thermal energy required to drive the air conditioner. Preliminary evaluation of data collected for operation in the heating mode during the winter indicates that nearly 100 percent of the thermal energy required for heating can be supplied by the system.

  18. Storing carbon dioxide in saline formations : analyzing extracted water treatment and use for power plant cooling.

    Energy Technology Data Exchange (ETDEWEB)

    Dwyer, Brian P.; Heath, Jason E.; Borns, David James; Dewers, Thomas A.; Kobos, Peter Holmes; Roach, Jesse D.; McNemar, Andrea; Krumhansl, James Lee; Klise, Geoffrey T.

    2010-10-01

    In an effort to address the potential to scale up of carbon dioxide (CO{sub 2}) capture and sequestration in the United States saline formations, an assessment model is being developed using a national database and modeling tool. This tool builds upon the existing NatCarb database as well as supplemental geological information to address scale up potential for carbon dioxide storage within these formations. The focus of the assessment model is to specifically address the question, 'Where are opportunities to couple CO{sub 2} storage and extracted water use for existing and expanding power plants, and what are the economic impacts of these systems relative to traditional power systems?' Initial findings indicate that approximately less than 20% of all the existing complete saline formation well data points meet the working criteria for combined CO{sub 2} storage and extracted water treatment systems. The initial results of the analysis indicate that less than 20% of all the existing complete saline formation well data may meet the working depth, salinity and formation intersecting criteria. These results were taken from examining updated NatCarb data. This finding, while just an initial result, suggests that the combined use of saline formations for CO{sub 2} storage and extracted water use may be limited by the selection criteria chosen. A second preliminary finding of the analysis suggests that some of the necessary data required for this analysis is not present in all of the NatCarb records. This type of analysis represents the beginning of the larger, in depth study for all existing coal and natural gas power plants and saline formations in the U.S. for the purpose of potential CO{sub 2} storage and water reuse for supplemental cooling. Additionally, this allows for potential policy insight when understanding the difficult nature of combined potential institutional (regulatory) and physical (engineered geological sequestration and extracted water

  19. Wind turbine generators having wind assisted cooling systems and cooling methods

    Science.gov (United States)

    Bagepalli, Bharat [Niskayuna, NY; Barnes, Gary R [Delanson, NY; Gadre, Aniruddha D [Rexford, NY; Jansen, Patrick L [Scotia, NY; Bouchard, Jr., Charles G.; Jarczynski, Emil D [Scotia, NY; Garg, Jivtesh [Cambridge, MA

    2008-09-23

    A wind generator includes: a nacelle; a hub carried by the nacelle and including at least a pair of wind turbine blades; and an electricity producing generator including a stator and a rotor carried by the nacelle. The rotor is connected to the hub and rotatable in response to wind acting on the blades to rotate the rotor relative to the stator to generate electricity. A cooling system is carried by the nacelle and includes at least one ambient air inlet port opening through a surface of the nacelle downstream of the hub and blades, and a duct for flowing air from the inlet port in a generally upstream direction toward the hub and in cooling relation to the stator.

  20. Desiccant Dewpoint Cooling System Independent of External Water Sources

    DEFF Research Database (Denmark)

    Bellemo, Lorenzo; Elmegaard, Brian; Markussen, Wiebke B.

    2015-01-01

    This paper presents a patent pending technical solution aiming to make desiccant cooling systems independent of external water sources, hence solving problems of water availability, cost and treatment that can decrease the system attractiveness. The solution consists in condensing water from the ...... to the desiccant dew-point system without water recovery, the required regeneration temperature increases and the system thermal efficiency decreases.......This paper presents a patent pending technical solution aiming to make desiccant cooling systems independent of external water sources, hence solving problems of water availability, cost and treatment that can decrease the system attractiveness. The solution consists in condensing water from...... the air that regenerates the desiccant dehumidifier, and using it for running the evaporative coolers in the system. A closed regeneration circuit is used for maximizing the amount of condensed water. This solution is applied to a system with a desiccant wheel dehumidifier and a dew point cooler, termed...

  1. Systems Evaluation at the Cool Energy House

    Energy Technology Data Exchange (ETDEWEB)

    J. Williamson and S. Puttagunta

    2013-09-01

    Steven Winter Associates, Inc. (SWA) monitored several advanced mechanical systems within a 2012 deep energy retrofitted home in the small Orlando suburb of Windermere, FL. This report provides performance results of one of the home's heat pump water heaters (HPWH) and the whole-house dehumidifier (WHD) over a six month period. In addition to assessing the energy performance of these systems, this study sought to quantify potential comfort improvements over traditional systems. This information is applicable to researchers, designers, plumbers, and HVAC contractors. Though builders and homeowners can find useful information within this report, the corresponding case studies are a likely better reference for this audience.

  2. Systems Evaluation at the Cool Energy House

    Energy Technology Data Exchange (ETDEWEB)

    Williamson, J. [Steven Winter Associates, Inc., Norwalk, CT (United States); Puttagunta, S. [Steven Winter Associates, Inc., Norwalk, CT (United States)

    2013-09-01

    Steven Winter Associates, Inc. (SWA) monitored several advanced mechanical systems within a 2012 deep energy retrofitted home in the small Orlando suburb of Windermere, FL. This report provides performance results of one of the home's heat pump water heaters (HPWH) and the whole-house dehumidifier (WHD) over a six month period. In addition to assessing the energy performance of these systems,this study sought to quantify potential comfort improvements over traditional systems. This information is applicable to researchers, designers, plumbers, and HVAC contractors. Though builders and homeowners can find useful information within this report, the corresponding case studies are a likely better reference for this audience.

  3. Liquid Cooling System for CPU by Electroconjugate Fluid

    Directory of Open Access Journals (Sweden)

    Yasuo Sakurai

    2014-06-01

    Full Text Available The dissipated power of CPU for personal computer has been increased because the performance of personal computer becomes higher. Therefore, a liquid cooling system has been employed in some personal computers in order to improve their cooling performance. Electroconjugate fluid (ECF is one of the functional fluids. ECF has a remarkable property that a strong jet flow is generated between electrodes when a high voltage is applied to ECF through the electrodes. By using this strong jet flow, an ECF-pump with simple structure, no sliding portion, no noise, and no vibration seems to be able to be developed. And then, by the use of the ECF-pump, a new liquid cooling system by ECF seems to be realized. In this study, to realize this system, an ECF-pump is proposed and fabricated to investigate the basic characteristics of the ECF-pump experimentally. Next, by utilizing the ECF-pump, a model of a liquid cooling system by ECF is manufactured and some experiments are carried out to investigate the performance of this system. As a result, by using this system, the temperature of heat source of 50 W is kept at 60°C or less. In general, CPU is usually used at this temperature or less.

  4. Efficient energy storage in liquid desiccant cooling systems

    Energy Technology Data Exchange (ETDEWEB)

    Hublitz, Astrid

    2008-07-18

    Liquid Desiccant Cooling Systems (LDCS) are open loop sorption systems for air conditioning that use a liquid desiccant such as a concentrated salt solution to dehumidify the outside air and cool it by evaporative cooling. Thermochemical energy storage in the concentrated liquid desiccant can bridge power mismatches between demand and supply. Low-flow LDCS provide high energy storage capacities but are not a state-of-the-art technology yet. The key challenge remains the uniform distribution of the liquid desiccant on the heat and mass transfer surfaces. The present research analyzes the factors of influence on the energy storage capacity by simulation of the heat and mass transfer processes and specifies performance goals for the distribution of the process media. Consequently, a distribution device for the liquid desiccant is developed that reliably meets the performance goals. (orig.)

  5. Desiccant aging and its effect on desiccant cooling system performance

    Energy Technology Data Exchange (ETDEWEB)

    Belding, W.A. [Innovative Research Enterprises, Danville, CA (United States); Delmas, M.P.F.; Holeman, W.D. [LaRoche Industries Inc., Baton Rouge, LA (United States)

    1996-05-01

    Desiccants used for the purpose of space conditioning or enthalpy transfer can be subjected to hundreds of thousands of adsorption/regeneration cycles over their useful life. Studying the loss of a desiccant`s equilibrium water adsorption capacity after exposure to thermal cycling is a common method for quantifying desiccant aging. Since isotherm shape and desiccant capacity can be related to overall cooling-system performance, system cooling capacity and coefficients of performance over time can be predicted. Adsorption isotherms for several different desiccants have been determined after subjecting the materials to varying numbers of thermal cycles in a specially designed test unit capable of adsorption/desorption cycling every 10 min. Aging curves for a new Type 1M desiccant developed specifically for desiccant cooling applications by LaRoche Industries Inc. are compared to other commonly used desiccants. (author)

  6. Experimental study on solar desiccant cooling system. 2nd Report; Taiyonetsu kudo desiccant cooling system no jikkenteki kento. 2

    Energy Technology Data Exchange (ETDEWEB)

    Tanaka, H.; Funato, H. [Fukuoka Institute of Technology, Fukuoka (Japan); Kuma, T. [Seibu Giken Co. Ltd., Fukuoka (Japan)

    1996-10-27

    Study has been made about a desiccant cleaning system using solar heated water for regenerating the dehumidifier. A dehumidifier and evaporation coolers are combined to attain a synergistic effect in dehumidifying and cooling the air in the house. The simultaneous control of humidity and temperature, however, is quite difficult. Under the circumstances, an evaporation cooler was removed from the outdoor air intake side, to leave a humidifier alone for the control of humidity only. In addition, the length of the dehumidifier was reduced into half for saving fan driving power and for downscaling the model. With only one evaporation cooler in operation that is installed at the exhaust side, the cooling effect is diminished by half. For dealing with the situation, ultrasonic atomization is performed at the exhaust side evaporation cooler for the improvement of the air cooling effect for the next sensible heat exchanger (intake side). The return air is heated by the solar heater water (approximately 60{degree}C hot), regenerates the dehumidifier, and then exhausted. The atomization process elevates the cooling effect, and the resultant cooling effect was as high as that expected from a 2-cooler setup. The dehumidification effect, however, lowers a little. Exclusion of the atomization process will enhance the dehumidification effect, but will reduce the cooling effect as well. 3 refs., 8 figs., 3 tabs.

  7. PARAMETERS OF WATER CIRCULATION NETWORK FOR A DISTRICT HEATING AND COOLING SYSTEM

    Institute of Scientific and Technical Information of China (English)

    2000-01-01

    In a district heating and cooling system, i.e. Beijing combined heating cooling and power (CHCP) system studied here, high temperature water generated by two cogeneration plants circulates through a network between the plants and heat substations. At heat substations, supply water of high temperature from the network drives absorption chillers for air-conditioning in summer and meets space heating demands in winter or domestic hot water demands by heat exchangers in the whole year. The parameters, i.e. supply/return water temperature in the network, has a great impact on primary energy consumption (PEC) of the absorption chillers, circulation pumps and domestic hot water (DHW), which is studied in this paper.

  8. Development of hybrid solar-assisted cooling/heating system

    KAUST Repository

    Huang, B.J.

    2010-08-01

    A solar-assisted ejector cooling/heating system (SACH) was developed in this study. The SACH combines a pump-less ejector cooling system (ECS) with an inverter-type heat pump (R22) and is able to provide a stable capacity for space cooling. The ECS is driven by solar heat and is used to cool the condenser of the R22 heat pump to increase its COP and reduce the energy consumption of the compressor by regulating the rotational speed of the compressor through a control system. In a complete SACH system test run at outdoor temperature 35 °C, indoor temperature 25 °C and compressor speed 20-80 Hz, and the ECS operating at generator temperature 90 °C and condensing temperature 37 °C, the corresponding condensing temperature of the heat pump in the SACH is 24.5-42 °C, cooling capacity 1.02-2.44 kW, input power 0.20-0.98 kW, and cooling COPc 5.11-2.50. This indicates that the use of ECS in SACH can effectively reduce the condensing temperature of the heat pump by 12.6-7.3 °C and reduce the power consumption by 81.2-34.5%. The SACH can also supply heat from the heat pump. At ambient temperature from 5 °C to 35 °C, the heating COPh is in the range 2.0-3.3. © 2010 Elsevier Ltd. All rights reserved.

  9. Cooling water shortage causes nuclear power plant standstill; Hitzefrei fuer Atomstrom

    Energy Technology Data Exchange (ETDEWEB)

    Loenker, O.

    2003-09-01

    The cooling water shortage during the high 'Michaela' induced operators of nuclear and coal power plants to run their plants at lower power. In future heat waves, decentralisation and shutdown of inefficient large-scale power plants may be the only solution. (orig.) [German] Niedrige Pegelstaende, erwaermte Fluesse: Weil das Kuehlwasser knapp wurde, zwang Hoch 'Michaela' die Betreiber von Atom- und Kohle-Kraftwerken zum Drosseln ihrer Anlagen. Gegen kuenftige Hitzewellen hilft nur die Dezentralisierung der Energiewirtschaft und die Abkehr von ineffizienten Grosskraftwerken. (orig.)

  10. Energy and Exergy Performances of Air-Based vs. Water-Based Heating and Cooling Systems: A Case Study of a Single-Family House

    DEFF Research Database (Denmark)

    Kazanci, Ongun Berk; Shukuya, Masanori; Olesen, Bjarne W.

    2016-01-01

    -based systems, an air heating and cooling system, and a radiant floor heating and cooling system were chosen, respectively. A single-family house was used as a case study assuming that different space heating and cooling systems were used to condition the indoor space of this house. In addition to the thermal...... energy and exergy inputs to the system, energy and exergy inputs to the auxiliary components were also studied. Both heating and cooling cases were considered and three climatic zones were studied; Copenhagen (Denmark), Yokohama (Japan), and Ankara (Turkey). The analysis showed that the water......-based radiant heating and cooling system performed better than the air-based system both in terms of energy and exergy input to the heating/cooling plant. The relative benefits of the water-based system over the air-based system vary depending on the climatic zone. The air-based system also requires higher...

  11. Reliability and safety of the K Reactor cooling system: Part 2, Engineering analysis of hydraulic and mechanical aspects

    Energy Technology Data Exchange (ETDEWEB)

    Shoemaker, R.H.

    1960-04-04

    Subsequent to the recent formulation and adoption of safety criteria for reactor cooling systems, there appeared the need for an independent evaluation of the safety and reliability of the K-Reactor cooling system in terms of these criteria. The primary, secondary and last-ditch cooling systems of this reactor involve a strong inter-dependence between electrical and hydraulic components of the water plant. Because of the complexity of inter-relationships between these components, the analysis was divided into two parallel studies which were accomplished during the simmer of 1959. F. D. Robbins has presented his analysis of the electrical power and control system in HW-61887. This report deals with an engineering analysis of the hydraulic and mechanical aspects of the reliability and safety of the K-Reactor Cooling System. The system, as described in this report, is that which existed during the simmer of 1959, prior to modification under Project CG-775 (now Project CG-883).

  12. Prototype solar heating and cooling systems

    Science.gov (United States)

    1979-01-01

    A combination of monthly progress reports are presented. It contains a summary of activities and progress made from November 1, 1978, to February 28, 1979. The effort calls for the development, manufacture, test, system installation, maintenance, problem resolution, and performance evaluation.

  13. Cool gas micropropulsion system for cubesats

    NARCIS (Netherlands)

    Breukelen, E. van; Sanders, B.H.; Schuurbiers, C.A.H.

    2009-01-01

    CubeSats are becoming more mature and many capabilities previously associated with microsatellites and bigger platforms are coming to the CubeSat. Moreover, they are becoming available as commercial off the shelf systems with standardized interfaces. TNO Defence and Security of the Netherlands is in

  14. Cool gas micropropulsion system for cubesats

    NARCIS (Netherlands)

    Breukelen, E. van; Sanders, B.H.; Schuurbiers, C.A.H.

    2009-01-01

    CubeSats are becoming more mature and many capabilities previously associated with microsatellites and bigger platforms are coming to the CubeSat. Moreover, they are becoming available as commercial off the shelf systems with standardized interfaces. TNO Defence and Security of the Netherlands is in

  15. 中水回用对石化循环冷却水系统的危害及对策%The Harm and Countermeasure of Recycled Water Reused into Circulating Cooling Water System in Petrochemical Plant

    Institute of Scientific and Technical Information of China (English)

    王炜; 魏志朝

    2011-01-01

    The source,category and disposing process of waste water in oil refining industry were stated.The characteristics of recycled water and influencing factors as make-up water into circulating cooling water system were analyzed,and the processes of reducing%阐述了炼化污水的主要来源、分类和处理过程的差别。分析了中水的主要特点及作为循环冷却水系统补水的危害和主要影响因素。概括了优化循环水系统操作管理以降低中水对系统危害的方法。

  16. Soft-Sensing Method of Water Temperature Measurement for Controlled Cooling System

    Institute of Scientific and Technical Information of China (English)

    CAI Xiao-hui; ZHANG Dian-hua; WANG Guo-dong; LIU Xiang-hua; FAN Lei

    2003-01-01

    Aiming at the water temperature measuring problem for controlled cooling system of rolling plant, a new water temperature measuring method based on soft-sensing method with a water temperature model of on-line self correction parameter was built. A water temperature compensation factor model was also built to improve coiling temperature control precision. It was proved that the model meets production requirements. The soft-sensing technique has extensive applications in the field of metal forming.

  17. 脉冲磁场对电厂循环冷却水中异养菌的灭活%Inactivation of heterotrophic bacteria in circulation cooling water system of power plant by pulsed magnetic field

    Institute of Scientific and Technical Information of China (English)

    武红梅; 刘智安; 薛金英; 刘洋; 周斐博; 王玮

    2012-01-01

    为了控制微生物繁殖对电厂循环冷却水系统造成的危害,研究了脉冲电源发生器与线圈绕组相连产生的脉冲磁场对循环水中异养菌的灭活影响,并对灭活关键因素进行了分析。实验结果表明,脉冲磁场对电厂循环冷却水中的异养菌有灭活作用;灭活率对频率和输出电压有选择性,并且随着作用时间和温度的升高而升高;在扫频范围100~1000 Hz、输出电压3 V、单次作用时间为15 s,温度45℃时,异养菌灭活率达到78.8%。%In order to control the harm caused by microbial growth in circulation cooling water systems,the inactivation of heterotrophic bacteria was investigated with the pulsed magnetic fields generated by DC-pulse generator combining with coil windings.Analyses for key factors of sterilization were carried out.The experimental results revealed that the pulsed magnetic fields have effects on inactivation of heterotrophic bacteria in the circulation cooling water system.The inactivation rates take selectivity for the frequency and output voltage.The inactivation rates increase with the increasing of temperature and time duration for each pulse.When the sweep frequency of pulsed magnetic field ranges from 10 to 1 000 Hz,the output voltage is 3 V,and the time duration for each pulse is 15 s,the inactivation rate is 78.8%.

  18. BETTER DUCT SYSTEMS FOR HOME HEATING AND COOLING.

    Energy Technology Data Exchange (ETDEWEB)

    ANDREWS,J.

    2001-01-01

    This is a series of six guides intended to provide a working knowledge of residential heating and cooling duct systems, an understanding of the major issues concerning efficiency, comfort, health, and safety, and practical tips on installation and repair of duct systems. These guides are intended for use by contractors, system designers, advanced technicians, and other HVAC professionals. The first two guides are also intended to be accessible to the general reader.

  19. Development of cooling and cleaning systems for enhanced gas ...

    African Journals Online (AJOL)

    Development of cooling and cleaning systems for enhanced gas quality for 3.7 ... The pollutants generated from gasification include particulate matter, tars, ... Air and gas flow rates were measured to be 18.8 m3/h and 20.12 kg/h respectively.

  20. Energy conservation in cooling systems. Blowers; Energiebesparing in koelsystemen. Ventilatoren

    Energy Technology Data Exchange (ETDEWEB)

    Huijgens, G.

    2009-03-15

    On the role of blowers with regard to the options to save energy with cooling systems. In particular attention is paid to so-called Electronically Commutated (EC) Motors. [Dutch] Over de rol van ventilatoren in de mogelijkheden om energie te besparen met koelsystemen. In het bijzonder wordt aandacht besteed aan de zogenaamde Electronically Commutated (EC) Motors.

  1. Thermohydraulic safety issues for liquid metal cooled systems

    Energy Technology Data Exchange (ETDEWEB)

    Gerbeth, Gunter; Stefani, Frank [Helmholtz-Zentrum Dresden-Rossendorf (HZDR) e.V., Dresden (Germany). Inst. of Fluid Dynamics; Eckert, Sven

    2016-05-15

    In this paper recent developments of various techniques for single-phase and two-phase flow measurements with relevance to liquid metal cooled systems will be presented. Further, the status of the DRESDYN platform for large-scale experiments with liquid sodium is sketched.

  2. Development of cooling and cleaning systems for enhanced gas ...

    African Journals Online (AJOL)

    DR OKE

    The temperature of the gas after developed cooling and cleaning system ... conventional energy sources with renewable energy sources used in hybrid mode .... dry filters 1 and 2) and for air flow across orifice plate. ... Technologies Pvt. Ltd., ... allow the gas to pass through various porous media collecting the particulates of.

  3. Performance test of solar-assisted ejector cooling system

    KAUST Repository

    Huang, Bin-Juine

    2014-03-01

    A solar-assisted ejector cooling/heating system (SACH-2k) is built and test result is reported. The solar-driven ejector cooling system (ECS) is connected in series with an inverter-type air conditioner (IAC). Several advanced technologies are developed in SACH-k2, including generator liquid level control in ECS, the ECS evaporator temperature control, and optimal control of fan power in cooling tower of ECS. From the field test results, the generator liquid level control performs quite well and keeps stable performance of ejector. The ECS evaporator temperature control also performs satisfactorily to keep ejector performance normally under low or fluctuating solar radiation. The fan power control system cooling tower performs stably and reduces the power consumption dramatically without affecting the ECS performance. The test results show that the overall system COPo including power consumptions of peripheral increases from 2.94-3.3 (IAC alone) to 4.06-4.5 (SACH-k2), about 33-43%. The highest COPo is 4.5. © 2013 Elsevier Ltd and IIR. All rights reserved.

  4. Solar heating and cooling system installed at Leavenworth, Kansas

    Science.gov (United States)

    1980-01-01

    A solar heating and cooling is described which is designed to furnish 90 percent of the overall heating load, 70 percent of the cooling load and 100 percent of the domestic hot water load. The building has two floors with a total of 12,000 square feet gross area. The system has 120 flat-plate liquid solar panels with a net area of 2,200 square feet. Five 3 ton Arkla solar assisted absorption units provide the cooling, in conjunction with a 3,000 gallon chilled water storage tank. Two 3,000 gallon storage tanks are provided with one designated for summer use, whereas both tanks are utilized during winter.

  5. Performance evaluation of an active solar cooling system utilizing low cost plastic collectors and an evaporatively-cooled absorption chiller

    Science.gov (United States)

    Lof, G. O.; Westhoff, M. A.; Karaki, S.

    1984-02-01

    During the summer of 1982, air conditioning in Solar House 3 at Colorado State University was provided by an evaporatively-cooled absorption chiller. The single-effect lithium bromide chiller is an experimental three-ton unit from which heat is rejected by direct evaporative cooling of the condenser and absorber walls, thereby eliminating the need for a separate cooling tower. Domestic hot water was also provided by use of a double-walled heat exchanger and 80-gal hot water tank. A schematic of the system is given. Objectives of the project were: (1) evaluation of system performance over the course of one cooling season in Fort Collins, Colorado; (2) optimization of system operation and control; (3) development of a TRNSYS compatible model of the chiller; and (4) determination of cooling system performance in several U.S. climates by use of the model.

  6. System design package for a solar heating and cooling system installed at Akron, Ohio

    Science.gov (United States)

    1979-01-01

    Information used to evaluate the design of a solar heating, cooling, and domestic hot water system is given. A conventional heat pump provides summer cooling items as the design data brochure, system performance specification, system hazard analysis, spare parts list, and detailed design drawings. A solar system is installed in a single-family dwelling at Akron, Ohio, and at Duffield, Virginia.

  7. Experimental Studies of NGNP Reactor Cavity Cooling System With Water

    Energy Technology Data Exchange (ETDEWEB)

    Corradini, Michael; Anderson, Mark; Hassan, Yassin; Tokuhiro, Akira

    2013-01-16

    This project will investigate the flow behavior that can occur in the reactor cavity cooling system (RCCS) with water coolant under the passive cooling-mode of operation. The team will conduct separate-effects tests and develop associated scaling analyses, and provide system-level phenomenological and computational models that describe key flow phenomena during RCCS operation, from forced to natural circulation, single-phase flow and two-phase flow and flashing. The project consists of the following tasks: Task 1. Conduct separate-effects, single-phase flow experiments and develop scaling analyses for comparison to system-level computational modeling for the RCCS standpipe design. A transition from forced to natural convection cooling occurs in the standpipe under accident conditions. These tests will measure global flow behavior and local flow velocities, as well as develop instrumentation for use in larger scale tests, thereby providing proper flow distribution among standpipes for decay heat removal. Task 2. Conduct separate-effects experiments for the RCCS standpipe design as two-phase flashing occurs and flow develops. As natural circulation cooling continues without an ultimate heat sink, water within the system will heat to temperatures approaching saturation , at which point two-phase flashing and flow will begin. The focus is to develop a phenomenological model from these tests that will describe the flashing and flow stability phenomena. In addition, one could determine the efficiency of phase separation in the RCCS storage tank as the two-phase flashing phenomena ensues and the storage tank vents the steam produced. Task 3. Develop a system-level computational model that will describe the overall RCCS behavior as it transitions from forced flow to natural circulation and eventual two-phase flow in the passive cooling-mode of operation. This modeling can then be used to test the phenomenological models developed as a function of scale.

  8. Performance of Upgraded Cooling System for Lhd Helical Coils

    Science.gov (United States)

    Hamaguchi, S.; Imagawa, S.; Obana, T.; Yanagi, N.; Moriuchi, S.; Sekiguchi, H.; Oba, K.; Mito, T.; Motojima, O.; Okamura, T.; Semba, T.; Yoshinaga, S.; Wakisaka, H.

    2008-03-01

    Helical coils of the Large Helical Device (LHD) are large scale superconducting magnets for heliotron plasma experiments. The helical coils had been cooled by saturated helium at 4.4 K, 120 kPa until 2005. An upgrade of the cooling system was carried out in 2006 in order to improve the cryogenic stability of the helical coils and then it has been possible to supply the coils with subcooled helium at 3.2 K, 120 kPa. A designed mass flow of the supplied subcooled helium is 50 g/s. The subcooled helium is generated at a heat exchanger in a saturated helium bath. A series of two centrifugal cold compressors with gas foil bearing is utilized to lower the helium pressure in the bath. The supplied helium temperature is regulated by rotational speed of the cold compressors and power of a heater in the bath. The mass flow of the supplied helium is also controlled manually by a supply valve and its surplus is evaporated by ten heaters at the outlet above the coils. In the present study, the performance of the cooling system has been investigated and a stable operating method has also developed. As the result, it was confirmed that the performance of the upgraded cooling system satisfies the requirements.

  9. Benchmark ultra-cool dwarfs in widely separated binary systems

    Directory of Open Access Journals (Sweden)

    Jones H.R.A.

    2011-07-01

    Full Text Available Ultra-cool dwarfs as wide companions to subgiants, giants, white dwarfs and main sequence stars can be very good benchmark objects, for which we can infer physical properties with minimal reference to theoretical models, through association with the primary stars. We have searched for benchmark ultra-cool dwarfs in widely separated binary systems using SDSS, UKIDSS, and 2MASS. We then estimate spectral types using SDSS spectroscopy and multi-band colors, place constraints on distance, and perform proper motions calculations for all candidates which have sufficient epoch baseline coverage. Analysis of the proper motion and distance constraints show that eight of our ultra-cool dwarfs are members of widely separated binary systems. Another L3.5 dwarf, SDSS 0832, is shown to be a companion to the bright K3 giant η Cancri. Such primaries can provide age and metallicity constraints for any companion objects, yielding excellent benchmark objects. This is the first wide ultra-cool dwarf + giant binary system identified.

  10. Comparison of Air Cooled and Evaporatively Cooled Refrigerartion Systems – A Review Paper

    Directory of Open Access Journals (Sweden)

    V. V. Birangane

    2014-06-01

    Full Text Available The air cooled condensers are widely used as they are less costly and give satisfactory performance. But their performance is greatly affected by the temperature of cooling media which is ambient air. To deal this problem we can use water cooled condenser. But their cost and maintenance limit their use. The performance improvement of Air cooled condensers can be achieved by using evaporative cooling. This method may prove quiet effective and less costly. There are researchers working on the above issue. Few of them have successfully implemented the research in practice. The paper deals with a few papers using the evaporative cooling. The applications include domestic as well as industrial.

  11. CFD Model Development and validation for High Temperature Gas Cooled Reactor Cavity Cooling System (RCCS) Applications

    Energy Technology Data Exchange (ETDEWEB)

    Hassan, Yassin [Univ. of Wisconsin, Madison, WI (United Texas A & M Univ., College Station, TX (United States); Corradini, Michael; Tokuhiro, Akira; Wei, Thomas Y.C.

    2014-07-14

    The Reactor Cavity Cooling Systems (RCCS) is a passive safety system that will be incorporated in the VTHR design. The system was designed to remove the heat from the reactor cavity and maintain the temperature of structures and concrete walls under desired limits during normal operation (steady-state) and accident scenarios. A small scale (1:23) water-cooled experimental facility was scaled, designed, and constructed in order to study the complex thermohydraulic phenomena taking place in the RCCS during steady-state and transient conditions. The facility represents a portion of the reactor vessel with nine stainless steel coolant risers and utilizes water as coolant. The facility was equipped with instrumentation to measure temperatures and flow rates and a general verification was completed during the shakedown. A model of the experimental facility was prepared using RELAP5-3D and simulations were performed to validate the scaling procedure. The experimental data produced during the steady-state run were compared with the simulation results obtained using RELAP5-3D. The overall behavior of the facility met the expectations. The facility capabilities were confirmed to be very promising in performing additional experimental tests, including flow visualization, and produce data for code validation.

  12. Impact of plant shoot architecture on leaf cooling: a coupled heat and mass transfer model.

    Science.gov (United States)

    Bridge, L J; Franklin, K A; Homer, M E

    2013-08-01

    Plants display a range of striking architectural adaptations when grown at elevated temperatures. In the model plant Arabidopsis thaliana, these include elongation of petioles, and increased petiole and leaf angles from the soil surface. The potential physiological significance of these architectural changes remains speculative. We address this issue computationally by formulating a mathematical model and performing numerical simulations, testing the hypothesis that elongated and elevated plant configurations may reflect a leaf-cooling strategy. This sets in place a new basic model of plant water use and interaction with the surrounding air, which couples heat and mass transfer within a plant to water vapour diffusion in the air, using a transpiration term that depends on saturation, temperature and vapour concentration. A two-dimensional, multi-petiole shoot geometry is considered, with added leaf-blade shape detail. Our simulations show that increased petiole length and angle generally result in enhanced transpiration rates and reduced leaf temperatures in well-watered conditions. Furthermore, our computations also reveal plant configurations for which elongation may result in decreased transpiration rate owing to decreased leaf liquid saturation. We offer further qualitative and quantitative insights into the role of architectural parameters as key determinants of leaf-cooling capacity.

  13. Utilization of process energy from supermarket refrigeration systems. Coupling of cooling and heating; Prozessenergienutzung von Supermarktkaelteanlagen. Kaelte-Waerme-Kopplung

    Energy Technology Data Exchange (ETDEWEB)

    Wirsching, Alexander [TEKO Gesellschaft fuer Kaeltetechnik mbH, Altenstadt (Germany). Technologie und Kommunikation

    2010-03-15

    The efficiency is defined as the relation between utility and expenditure. Thus, it is obvious for the specialist of refrigeration to tackle with the expenditure (energy consumption) since the utilization conventionally is defined as the produced/need cooling performance of a refrigeration plant. If refrigeration plants are regarded according to their function (withdrawal of heat from a refrigeration chamber and delivery to the environment), the heating system is the producer of the requirement for cooling in 'the winter' (heating season). Thus, the refrigeration plant perhaps already has a marvellous efficiency, and the separate heating system too - however in interaction. The broad view moves into the focus. The possible approaches and effects are described in the contribution under consideration using the example of a Discount supermarket with a sales area of 800 square meters and a requirement of cooling of more than 30 kW.

  14. Method and system for powering and cooling semiconductor lasers

    Science.gov (United States)

    Telford, Steven J; Ladran, Anthony S

    2014-02-25

    A semiconductor laser system includes a diode laser tile. The diode laser tile includes a mounting fixture having a first side and a second side opposing the first side and an array of semiconductor laser pumps coupled to the first side of the mounting fixture. The semiconductor laser system also includes an electrical pulse generator thermally coupled to the diode bar and a cooling member thermally coupled to the diode bar and the electrical pulse generator.

  15. Correcting Aberrations in Complex Magnet Systems for Muon Cooling Channels

    Energy Technology Data Exchange (ETDEWEB)

    J.A. Maloney, B. Erdelyi, A. Afanaciev, R.P. Johnson, Y.S. Derbenev, V.S. Morozov

    2011-03-01

    Designing and simulating complex magnet systems needed for cooling channels in both neutrino factories and muon colliders requires innovative techniques to correct for both chromatic and spherical aberrations. Optimizing complex systems, such as helical magnets for example, is also difficult but essential. By using COSY INFINITY, a differential algebra based code, the transfer and aberration maps can be examined to discover what critical terms have the greatest influence on these aberrations.

  16. CARMENES ultra-stable cooling system: very promising results

    Science.gov (United States)

    Mirabet, E.; Carvas, P.; Lizon, J.-L.; Becerril, S.; Rodríguez, E.; Abril, M.; Cárdenas, M. C.; Morales, R.; Pérez, D.; Sánchez Carrasco, M. A.; Amado, P. J.; Seifert, W.; Quirrenbach, A.; Caballero, J. A.; Ribas, I.; Reiners, A.; Dreizler, S.

    2014-07-01

    CARMENES is a high resolution spectrograph to detect planets through the variation of radial velocity, destined for the Calar Alto Observatory in Almeria, Spain. The optical bench has a working temperature of 140K with a 24 hours stability of ±0,1K; goal ±0,01K. It is enclosed with a radiation shield actively cooled with thermalized nitrogen gas that flows through strategically positioned heat exchangers to remove its radiative load. The cooling system has an external preparation unit (N2GPU), which provides the nitrogen gas through actively vaporizing liquid nitrogen with heating resistances and a three stage circuit flow, each one controlled by an independent PID. Since CARMENES is still in the construction phase, a dedicated test facility has been built in order to simulate the instrument and correctly establish the N2GPU parameters. Furthermore, the test facility allows a wide range of configurations set-ups, which enables a full characterization of the N2GPU and the cooling system. The N2GPU has been designed to offer a wide temperature range of thermally stabilized nitrogen gas flow, which apart from CARMENES could also be used to provide ultra-high thermal stability in other cryogenic instruments. The present paper shows the testing of the cooling performance, the hardware used and the very promising results obtained.

  17. Mineral scaling mitigation in cooling systems using tertiary-treated municipal wastewater.

    Science.gov (United States)

    Liu, Wenshi; Chien, Shih-Hsiang; Dzombak, David A; Vidic, Radisav D

    2012-09-15

    Treated municipal wastewater (MWW) is recognized as a significant potential source of cooling water for power generation. One of the key challenges for the successful use of the effluent from wastewater treatment facilities for cooling is the potential for significant mineral scaling when the raw water is concentrated as much as 4-6 times in recirculating cooling systems. Previous bench- and pilot-scale tests have shown that commonly used phosphorus- and polymer- based scaling inhibitors are ineffective when secondary-treated municipal wastewater (MWW) is used as make-up. In this study, two types of tertiary-treated municipal wastewaters, namely secondary-treated MWW with pH adjustment (MWW_pH) and secondary-treated MWW subjected to nitrification and sand filtration (MWW_NF) were evaluated as the sole source of make-up water for recirculating cooling systems. Both laboratory studies and pilot-scale tests revealed that adjusting the pH to 7.8 could reduce the mineral scaling rate by more than 80% without causing any significant corrosion problems. In contrast to MWW, where calcium carbonate was the dominant scaling mineral, the main component of mineral scale in MWW_pH was calcium phosphate. Both static and dynamic bench-scale tests indicated that scaling would not be a significant concern when MWW_NF is used as the make-up water in recirculating cooling systems operated at 4-6 cycles of concentration (CoC). Extended pilot-scale studies confirmed that MWW_NF is suitable makeup water for power plant cooling systems and that no anti-scaling chemicals would be required. Copyright © 2012 Elsevier Ltd. All rights reserved.

  18. Passive low energy cooling of buildings

    CERN Document Server

    Givoni, Baruch

    1994-01-01

    A practical sourcebook for building designers, providing comprehensive discussion of the impact of basic architectural choices on cooling efficiency, including the layout and orientation of the structure, window size and shading, exterior color, and even the use of plantings around the site. All major varieties of passive cooling systems are presented, with extensive analysis of performance in different types of buildings and in different climates: ventilation; radiant cooling; evaporative cooling; soil cooling; and cooling of outdoor spaces.

  19. Ten questions about radiant heating and cooling systems

    DEFF Research Database (Denmark)

    Rhee, Kyu-Nam; Olesen, Bjarne W.; Kim, Kwang Woo

    2017-01-01

    Radiant heating and cooling (RHC) systems are being increasingly applied not only in residential but also in non-residential buildings such as commercial buildings, education facilities, and even large scale buildings such as airport terminals. Furthermore, with the combined ventilation system used...... studies on RHC systems in terms of comfort, heat transfer analysis, energy simulation, control strategy, system configurations and so on. Many studies have demonstrated that the RHC system is a good solution to improve indoor environmental quality while reducing building energy consumption for heating...

  20. Analysis of advanced solar hybrid desiccant cooling systems for buildings

    Energy Technology Data Exchange (ETDEWEB)

    Schlepp, D.; Schultz, K.

    1984-10-01

    This report describes an assessment of the energy savings possible from developing hybrid desiccant/vapor-compression air conditioning systems. Recent advances in dehumidifier design for solar desiccant cooling systems have resulted in a dehumidifier with a low pressure drop and high efficiency in heat and mass transfer. A recent study on hybrid desiccant/vapor compression systems showed a 30%-80% savings in resource energy when compared with the best conventional systems with vapor compression. A system consisting of a dehumidifier with vapor compression subsystems in series was found to be the simplest and best overall performer.

  1. Naegleria fowleri in cooling circuits of industrial and power plants in North Moravia

    Energy Technology Data Exchange (ETDEWEB)

    Cerva, L.; Simanov, L.

    1983-01-01

    Both nonvirulent (15 strains) and virulent (1 strain) variants of Naegleria fowleri were isolated from the cooling circuits in seven of ten examined plants in North Moravia. No amoebae were found in waters with a high salinity (electric conductivity more than 614 microseconds) and with a low content of phosphates and oxygen. Other results of the physical, chemical and bacteriological examinations showed no direct bearing on the occurrence of N. fowleri.

  2. Operational aspects of the VELO cooling system of LHCb

    CERN Document Server

    Jans, E

    2014-01-01

    The VELO is a silicon strip detector that is positioned around the interaction region of LHCb. It is placed inside a secondary vacuum with respect to that of the LHC. The cooling system of the VELO is based on the bi-phase accumulator controlled method, using CO$_2$ as coolant. The main objective is the removal of the heat produced by the front-end electronics. Moreover, the leakage currents of the sensors are strongly reduced and thermal runaway is prevented. Since the sensors have been irradiated in Run 1 they should always be cooled to below $^-$5 $^{\\rm{o}}$C. The operational principle and main characteristics of the system are described, as well as the warning and safety systems that guarantee the safe operation of the detector. The few problems that have been encountered during the four years of continuous operation are discussed together with the solutions that have been implemented.

  3. Feedback linearization based control of a variable air volume air conditioning system for cooling applications.

    Science.gov (United States)

    Thosar, Archana; Patra, Amit; Bhattacharyya, Souvik

    2008-07-01

    Design of a nonlinear control system for a Variable Air Volume Air Conditioning (VAVAC) plant through feedback linearization is presented in this article. VAVAC systems attempt to reduce building energy consumption while maintaining the primary role of air conditioning. The temperature of the space is maintained at a constant level by establishing a balance between the cooling load generated in the space and the air supply delivered to meet the load. The dynamic model of a VAVAC plant is derived and formulated as a MIMO bilinear system. Feedback linearization is applied for decoupling and linearization of the nonlinear model. Simulation results for a laboratory scale plant are presented to demonstrate the potential of keeping comfort and maintaining energy optimal performance by this methodology. Results obtained with a conventional PI controller and a feedback linearizing controller are compared and the superiority of the proposed approach is clearly established.

  4. Experimental validation of the simulation module of the water-cooled variable refrigerant flow system under cooling operation

    Energy Technology Data Exchange (ETDEWEB)

    Li, Yue Ming; Wu, Jing Yi [Institute of Refrigeration and Cryogenics, Shanghai Jiao Tong University, Shanghai (China); Shiochi, Sumio [Daikin Industries, Ltd., 1304 Kanaoka-cho, Kita-ku, Sakai, Osaka 591-8511 (Japan)

    2010-05-15

    On the basis of EnergyPlus's codes, the catalogue and performance parameters from some related companies, a special simulation module for variable refrigerant flow system with a water-cooled condenser (water-cooled VRF) was developed and embedded in the software of EnergyPlus, the building energy simulation program. To evaluate the energy performance of the system and the accuracy of the simulation module, the measurement of the water-cooled VRF is built in Dalian, China. After simulation and comparison, some conclusions can be drawn. The mean of the absolute value of the daily error in the 9 days is 11.3% for cooling capacity while the one for compressor power is 15.7%. At the same time, the accuracy of the power simulation strongly depends on the accuracy of the cooling capacity simulation. (author)

  5. Development of Personalized Radiant Cooling System for an Office Room

    Energy Technology Data Exchange (ETDEWEB)

    Khare, Vaibhav [Malaviya National Institute of Technology (MNIT), Jaipur, India; Sharma, Anuj [Malaviya National Institute of Technology (MNIT), Jaipur, India; Mathur, Jyotirmay [Malaviya National Institute of Technology (MNIT), Jaipur, India; Bhandari, Mahabir S [ORNL

    2015-01-01

    The building industry nowadays is facing two major challenges increased concern for energy reduction and growing need for thermal comfort. These challenges have led many researchers to develop Radiant Cooling Systems that show a large potential for energy savings. This study aims to develop a personalized cooling system using the principle of radiant cooling integrated with conventional all-air system to achieve better thermal environment at the workspace. Personalized conditioning aims to create a microclimatic zone around a single workspace. In this way, the energy is deployed only where it is actually needed, and the individual s needs for thermal comfort are fulfilled. To study the effect of air temperature along with air temperature distribution for workspace, air temperature near the vicinity of the occupant has been obtained as a result of Computational Fluid Dynamics (CFD) simulation using FLUENT. The analysis showed that personalized radiant system improves thermal environment near the workspace and allows all-air systems to work at higher thermostat temperature without compromising the thermal comfort, which in turn reduces its energy consumption.

  6. Implementation of gas district cooling and cogeneration systems in Malaysia; Mise en oeuvre de systemes de gas district cooling et de cogeneration en Malaisie

    Energy Technology Data Exchange (ETDEWEB)

    Haron, S. [Gas District Cooling, M, Sdn Bhd (Malaysia)

    2000-07-01

    With its energy demand in the early 1990's growing at a high rate due to the country's strong economic growth, Malaysia studied various options to improve the efficiency of its energy use. Since its natural gas reserves are almost four times that of its crude oil reserves, efforts were therefore centered on seeking ways to boost the use of natural gas to mitigate the growing domestic energy need. PETRONAS, the national oil company, subsequently studied and chose the District Cooling System using natural gas as the primary source of fuel. The Kuala Lumpur City Center development, which houses the PETRONAS Twin Towers, was subsequently chosen as the first project to use the Gas District Cooling (GDC) System. To acquire the technology and implement this project, PETRONAS created a new subsidiary, Gas District Cooling (Malaysia) Sendirian Berhad (GDC(M)). In the process of improving the plant's efficiency, GDC(M) discovered that the GDC system's efficiency and project economics would be significantly enhanced if its is coupled to a Cogeneration system. Having proven the success of the GDC/Cogeneration system, GDC(M) embarked on a campaign to aggressively promote and seek new opportunities to implement the system, both in Malaysia-and abroad. Apart from enhancing efficiency of energy use, and providing better project economics, the GDC/Cogeneration system also is environment friendly. Today, the GDC/Cogeneration systems is the system of choice for several important developments in Malaysia, which also includes the country's prestigious projects such as the Kuala Lumpur International Airport and the New Federal Government Administrative Center in Putrajaya. (author)

  7. Solar cooling system performance, Frenchman's Reef Hotel, Virgin Islands

    Science.gov (United States)

    Harber, H.

    1981-01-01

    The operational and thermal performance of a variety of solar systems are described. The Solar Cooling System was installed in a hotel at St. Thomas, U. S. Virgin Islands. The system consists of the evacuated glass tube collectors, two 2500 gallon tanks, pumps, computerized controller, a large solar optimized industrial sized lithium bromide absorption chiller, and associated plumbing. Solar heated water is pumped through the system to the designed public areas such as lobby, lounges, restaurant and hallways. Auxiliary heat is provided by steam and a heat exchanger to supplement the solar heat.

  8. A recirculating cooling system for improved topical cardiac hypothermia.

    Science.gov (United States)

    Rosenfeldt, F L; Fambiatos, A; Pastoriza-Pinol, J; Stirling, G R

    1981-10-01

    A simple system is described that recirculates cooling fluid for topical cardiac hypothermia. This disposable system can produce a flow of 1,500 ml/min at 2 degrees to 4 degrees C. The recirculating cooler produced significantly lower myocardial temperatures than a conventional fluid-discard system in 22 patients having coronary operation. This system has been used as part of the technique of hypothermic cardioplegia in more than 600 patients. During various cardiac procedures, septal temperatures were maintained well below 20 degrees C for 60 minutes or more without the need to reinfuse the cardioplegic solution.

  9. A dynamic model of an innovative high-temperature solar heating and cooling system

    Directory of Open Access Journals (Sweden)

    Buonomano Annamaria

    2016-01-01

    Full Text Available In this paper a new simulation model of a novel solar heating and cooling system based on innovative high temperature flat plate evacuated solar thermal collector is presented. The system configuration includes: flat-plate evacuated solar collectors, a double-stage LiBr-H2O absorption chiller, gas-fired auxiliary heater, a closed loop cooling tower, pumps, heat exchangers, storage tanks, valves, mixers and controllers. The novelty of this study lies in the utilization of flat-plate stationary solar collectors, manufactured by TVP Solar, rather than concentrating ones (typically adopted for driving double-stage absorption chillers. Such devices show ultra-high thermal efficiencies, even at very high (about 200°C operating temperatures, thanks to the high vacuum insulation. Aim of the paper is to analyse the energy and economic feasibility of such novel technology, by including it in a prototypal solar heating and cooling system. For this purpose, the solar heating and cooling system design and performance were analysed by means of a purposely developed dynamic simulation model, implemented in TRNSYS. A suitable case study is also presented. Here, the simulated plant is conceived for the space heating and cooling and the domestic hot water production of a small building, whose energy needs are fulfilled through a real installation (settled also for experimental purposes built up close to Naples (South Italy. Simulation results show that the investigated system is able to reach high thermal efficiencies and very good energy performance. Finally, the economic analysis shows results comparable to those achieved through similar renewable energy systems.

  10. Method and system for providing cooling for turbine components

    Energy Technology Data Exchange (ETDEWEB)

    Morgan, Victor John; Lacy, Benjamin Paul

    2016-08-16

    A system for providing cooling for a turbine component that includes an outer surface exposed to combustion gases is provided. A component base includes at least one fluid supply passage coupleable to a source of cooling fluid. At least one feed passage communicates with the at least one fluid supply passage. At least one delivery channel communicates with the at least one feed passage. At least one cover layer covers the at least one feed passage and the at least one delivery channel, defining at least in part the component outer surface. At least one discharge passage extends to the outer surface. A diffuser section is defined in at least one of the at least one delivery channel and the at least one discharge passage, such that a fluid channeled through the system is diffused prior to discharge adjacent the outer surface.

  11. How to measure thermal effects of personal cooling systems : Human, thermal manikin and human simulator study

    NARCIS (Netherlands)

    Bogerd, N.; Psikuta, A.; Daanen, H.A.M.; Rossi, R.M.

    2010-01-01

    Thermal effects, such as cooling power and thermophysiological responses initiated upon application of a personal cooling system, can be assessed with (i) humans, (ii) a thermal manikin and (iii) a thermophysiological human simulator. In order to compare these methods, a cooling shirt (mild cooling)

  12. Cooling System Design for PEM Fuel Cell Powered Air Vehicles

    Science.gov (United States)

    2010-06-18

    radiator #7. The fan blades and shroud were formed using stereo lithography; the fan motor was a brushless DC motor with motor controller. These...Naval Research Laboratory Washington, DC 20375-5320 NRL/MR/6110--10-9253 Cooling System Design for PEM Fuel Cell Powered Air Vehicles June 18, 2010...Stroman, Michael W. Schuette,* and Gregory S. Page† Naval Research Laboratory 4555 Overlook Avenue, SW Washington, DC 20375-5342 NRL/MR/6110--10-9253

  13. Cathode Stalk Cooling System for the MK 1 Quarterwave Gun

    Science.gov (United States)

    2012-06-01

    of electrons can occur for strong fields, a π≥ . In this case, the electrons are shifted from the proper phase for gain to one for absorption ...better representing the pressure rise and decrease. The cooling system was then tested with a water chiller , which was easier to establish basic... chiller was set up in the evening, with the stalk temperatures at a room temperature of 293 K, and left on overnight to ensure a steady temperature

  14. Evaluation of battery packs for liquid microclimate cooling systems

    Science.gov (United States)

    Teal, Walter B., Jr.; Avellini, Barbara A.

    1995-05-01

    The Navy clothing and Textile Research Facility conducted a literature and industry survey to determine the best commercially available battery technology for use with liquid microclimate cooling systems (MCS), and a laboratory evaluation of a battery pack utilizing that technology. Nickel/cadmium batteries were determined to be the best battery technology commercially available at the present time. However, several other battery technologies are nearing commercialization and may be available in the near future.

  15. Biotic and physico-chemical conditions in a cooling reservoir of a coal-fired power plant

    Data.gov (United States)

    US Fish and Wildlife Service, Department of the Interior — Cholla Lake is a cooling reservoir for the coal fired Cholla electrical generating plant. The lake provides recreational fishing and water contact recreation. The...

  16. Solar heating and cooling system installed at Columbus, Ohio

    Science.gov (United States)

    1980-01-01

    The Solar Energy System was installed as a part of a new construction of a college building. The building will house classrooms and laboratories, administrative offices and three lecture halls. The Solar Energy System consists of 4,096 square feet (128 panels) Owens/Illinois Evacuated Glass Tube Collector Subsystem, and a 5,000 gallon steel tank below ground storage system. Hot water is circulated between the collectors and storage tank, passing through a water/lithium bromide absorption chiller to cool the building.

  17. Preliminary evaluation of wet/dry cooling concepts for power plants

    Energy Technology Data Exchange (ETDEWEB)

    Loscutoff, W.V.

    1976-01-01

    A large number of possible combinations of air and water flow arrangements and sequences are analyzed in the study presented. First, the heat transfer effectiveness of each was established, based on the assumption of constant size of the dry and wet subsystems. Next, the water consumption required to augment a constant-sized dry subsystem for maintaining cooling capability at a dry bulb temperature in excess of the design conditions for the dry system alone was determined. Results are presented which point to a number of significant conclusions relative to the preferred arrangement of the dry and wet subsystems in dry/wet heat rejection systems. The conclusions are based on the assumption that the wet cooling is used only to augment the dry cooling capability and that minimum consumption of water is a primary consideration.

  18. Heat exchange and hydraulic resistance of compact laser mirror cooling systems

    Science.gov (United States)

    Shanin, Yu. I.; Shanin, O. I.

    2013-07-01

    The hydraulic resistance of cooling systems for laser mirrors and the heat exchange in them have been investigated experimentally. The data obtained have been generalized for several cooling systems with different porous elements.

  19. Environmental Problems Associated With Decommissioning The Chernobyl Nuclear Power Plant Cooling Pond

    Energy Technology Data Exchange (ETDEWEB)

    Farfan, E. B.; Jannik, G. T.; Marra, J. C.; Oskolkov, B. Ya.; Bondarkov, M. D.; Gaschak, S. P.; Maksymenko, A. M.; Maksymenko, V. M.; Martynenko, V. I.

    2009-11-09

    Decommissioning of nuclear power plants and other nuclear fuel cycle facilities has been an imperative issue lately. There exist significant experience and generally accepted recommendations on remediation of lands with residual radioactive contamination; however, there are hardly any such recommendations on remediation of cooling ponds that, in most cases, are fairly large water reservoirs. The literature only describes remediation of minor reservoirs containing radioactive silt (a complete closure followed by preservation) or small water reservoirs resulting in reestablishing natural water flows. Problems associated with remediation of river reservoirs resulting in flooding of vast agricultural areas also have been described. In addition, the severity of environmental and economic problems related to the remedial activities is shown to exceed any potential benefits of these activities. One of the large, highly contaminated water reservoirs that require either remediation or closure is Karachay Lake near the MAYAK Production Association in the Chelyabinsk Region of Russia where liquid radioactive waste had been deep well injected for a long period of time. Backfilling of Karachay Lake is currently in progress. It should be noted that secondary environmental problems associated with its closure are considered to be of less importance since sustaining Karachay Lake would have presented a much higher radiological risk. Another well-known highly contaminated water reservoir is the Chernobyl Nuclear Power Plant (ChNPP) Cooling Pond, decommissioning of which is planned for the near future. This study summarizes the environmental problems associated with the ChNPP Cooling Pond decommissioning.

  20. ENVIRONMENTAL PROBLEMS ASSOCIATED WITH DECOMMISSIONING THE CHERNOBYL NUCLEAR POWER PLANT COOLING POND

    Energy Technology Data Exchange (ETDEWEB)

    Farfan, E.

    2009-09-30

    Decommissioning of nuclear power plants and other nuclear fuel cycle facilities has been an imperative issue lately. There exist significant experience and generally accepted recommendations on remediation of lands with residual radioactive contamination; however, there are hardly any such recommendations on remediation of cooling ponds that, in most cases, are fairly large water reservoirs. The literature only describes remediation of minor reservoirs containing radioactive silt (a complete closure followed by preservation) or small water reservoirs resulting in reestablishing natural water flows. Problems associated with remediation of river reservoirs resulting in flooding of vast agricultural areas also have been described. In addition, the severity of environmental and economic problems related to the remedial activities is shown to exceed any potential benefits of these activities. One of the large, highly contaminated water reservoirs that require either remediation or closure is Karachay Lake near the MAYAK Production Association in the Chelyabinsk Region of Russia where liquid radioactive waste had been deep well injected for a long period of time. Backfilling of Karachay Lake is currently in progress. It should be noted that secondary environmental problems associated with its closure are considered to be of less importance since sustaining Karachay Lake would have presented a much higher radiological risk. Another well-known highly contaminated water reservoir is the Chernobyl Nuclear Power Plant (ChNPP) Cooling Pond, decommissioning of which is planned for the near future. This study summarizes the environmental problems associated with the ChNPP Cooling Pond decommissioning.

  1. Development of Innovative Heating and Cooling Systems Using Renewable Energy Sources for Non-Residential Buildings

    Directory of Open Access Journals (Sweden)

    Cinzia Buratti

    2013-10-01

    Full Text Available Industrial and commercial areas are synonymous with high energy consumption, both for heating/cooling and electric power requirements, which are in general associated to a massive use of fossil fuels producing consequent greenhouse gas emissions. Two pilot systems, co-funded by the Italian Ministry for the Environment, have been created to upgrade the heating/cooling systems of two existing buildings on the largest industrial estate in Umbria, Italy. The upgrade was specifically designed to improve the system efficiency and to cover the overall energy which needs with renewable energy resources. In both cases a solar photovoltaic plant provides the required electric power. The first system features a geothermal heat pump with an innovative layout: a heat-storage water tank, buried just below ground level, allows a significant reduction of the geothermal unit size, hence requiring fewer and/or shorter boreholes (up to 60%–70%. In the other system a biomass boiler is coupled with an absorption chiller machine, controlling the indoor air temperature in both summer and winter. In this case, lower electricity consumption, if compared to an electric compression chiller, is obtained. The first results of the monitoring of summer cooling are presented and an evaluation of the performance of the two pilot systems is given.

  2. D0 Silicon Upgrad: D0 Silicon Cooling System

    Energy Technology Data Exchange (ETDEWEB)

    Squires, B.; /Fermilab

    1998-07-14

    The cooling system design is not complete. This paper lays out the general design and some of the design calculations that have been performed up to this date. Further refinement will be performed. This is especially true in the piping layout, piping insulation and detector manifold areas. The silicon detector is cooled by means of a coolant in the beryllium channels that also act as the primary supporting device for the silicon ladders and wedges. The coolant is water with ethylene glycol added as a freezing point depressant. The glycol concentration in the coolant is 30% by weight resulting in a freezing point of approximately -15 C. If the water/glycol is not sufficient for maintaining the desired detector temperature the concentration of the water/glycol may be changed or an alternative coolant may be used.

  3. NGNP: High Temperature Gas-Cooled Reactor Key Definitions, Plant Capabilities, and Assumptions

    Energy Technology Data Exchange (ETDEWEB)

    Phillip Mills

    2012-02-01

    This document is intended to provide a Next Generation Nuclear Plant (NGNP) Project tool in which to collect and identify key definitions, plant capabilities, and inputs and assumptions to be used in ongoing efforts related to the licensing and deployment of a high temperature gas-cooled reactor (HTGR). These definitions, capabilities, and assumptions are extracted from a number of sources, including NGNP Project documents such as licensing related white papers [References 1-11] and previously issued requirement documents [References 13-15]. Also included is information agreed upon by the NGNP Regulatory Affairs group's Licensing Working Group and Configuration Council. The NGNP Project approach to licensing an HTGR plant via a combined license (COL) is defined within the referenced white papers and reference [12], and is not duplicated here.

  4. District cooling pipes. Pipes and components in district cooling systems. Technical recommendations

    Energy Technology Data Exchange (ETDEWEB)

    2009-07-15

    Euroheat and Power (EHP) draws up technical recommendations for pipes and components in district heating and district cooling systems. Through references to these requirements, the quality of products and systems is ensured and procurement and installation are facilitated. The recommendations are based on experiences, standards, development and research results. These recommendations cover only the type of pipes and materials listed in the table of content. Material such as reinforced plastic AP, glass fibre, reinforced plastic GAP or nodular iron can be used but they are not in the scope of this recommendation. These recommendations are meant for DC systems using treated water with quality values comparable to DH water. As these requirements include different materials and solutions, the customer should make active selections when procuring a system. Full column wide text in these technical recommendations includes requirements, while indented text is informative. The tables presented in this set of recommendations are based on Swedish experience. The Task Force Transport and Distribution at Euroheat and Power has drawn up these technical recommendations

  5. New Type Regulating Valve Applied in Cooling System of Blast Furnace

    Institute of Scientific and Technical Information of China (English)

    HE Sheng-ping; ZOU De-yu; XU Gang; LU De-chang

    2004-01-01

    A new type regulating valve with the cooling mode of constant temperature difference water supply, temperature difference self-operated regulating valve, was introduced into blast furnace cooling system to overcome shortcomings of the cooling mode of constant flow rate water supply. The results show that the temperature difference between inlet and outlet water of cooling wall can be decreased greatly and steadily, and the water supply for blast furnace cooling can be reduced considerably.

  6. Numerical modeling for the retrofit of the hydraulic cooling subsystems in operating power plant

    Science.gov (United States)

    AlSaqoor, S.; Alahmer, A.; Al Quran, F.; Andruszkiewicz, A.; Kubas, K.; Regucki, P.; Wędrychowicz, W.

    2017-08-01

    This paper presents the possibility of using the numerical methods to analyze the work of hydraulic systems on the example of a cooling system of a power boiler auxiliary devices. The variety of conditions at which hydraulic system that operated in specific engineering subsystems requires an individualized approach to the model solutions that have been developed for these systems modernizing. A mathematical model of a series-parallel propagation for the cooling water was derived and iterative methods were used to solve the system of nonlinear equations. The results of numerical calculations made it possible to analyze different variants of a modernization of the studied system and to indicate its critical elements. An economic analysis of different options allows an investor to choose an optimal variant of a reconstruction of the installation.

  7. Structural engineering developments in power plant cooling tower construction. 100 years of natural draught cooling towers - from tower cooler to cooling tower. Bautechnische Entwicklungen im Kraftwerkskuehlturmbau. 100 Jahre Naturzugkuehltuerme - vom Kaminkuehler zum Kuehlkamin

    Energy Technology Data Exchange (ETDEWEB)

    Damjakob, H.; Depe, T.; Vrangos, V. (Balcke-Duerr AG, Ratingen (Germany))

    1992-06-01

    Almost exactly 100 years ago, tower-type structures were first used for the production of artificial ventilation for cooling purposes. The shell of these so-called tower coolers, today known as 'natural draught cooling towers', was, from the outset, the subject of multiple structural engineering develepments in respect of design, material, construction and statistical calculation. These developments have been stimulated especially by the spasmodic increase in dimensions in the application of power plant cooling towers and, more recently, in connection with ecological requirements. (orig.).

  8. Environmental Problems Associated with Decommissioning of Chernobyl Power Plant Cooling Pond

    Science.gov (United States)

    Foley, T. Q.; Oskolkov, B. Y.; Bondarkov, M. D.; Gashchak, S. P.; Maksymenko, A. M.; Maksymenko, V. M.; Martynenko, V. I.; Jannik, G. T.; Farfan, E. B.; Marra, J. C.

    2009-12-01

    Decommissioning of nuclear power plants and other nuclear fuel cycle facilities associated with residual radioactive contamination is a fairly pressing issue. Significant problems may result from decommissioning of cooling ponds. The Chernobyl Nuclear Power Plant (ChNPP) Cooling Pond is one of the largest self-contained bodies of water in the Chernobyl Region and Ukrainian Polesye with a water surface area of 22.9 km2. The major hydrological feature of the ChNPP Cooling Pond is that its water level is 6-7 m higher than the water level in the Pripyat River and water losses due to seepage and evaporation are replenished by pumping water from the Pripyat River. In 1986, the accident at the ChNPP #4 Reactor Unit significantly contaminated the ChNPP Cooling Pond. According to the 2001 data, the total radionuclide inventory in the ChNPP Cooling Pond bottom deposits was as follows: 16.28 ± 2.59 TBq for 137Cs; 2.4 ± 0.48 TBq for 90Sr, and 0.00518 ± 0.00148 TBq for 239+240Pu. Since ChNPP is being decommissioned, the ChNPP Cooling Pond of such a large size will no longer be needed and cost effective to maintain. However, shutdown of the water feed to the Pond would expose the contaminated bottom deposits and change the hydrological features of the area, destabilizing the radiological and environmental situation in the entire region in 2007 - 2008, in order to assess potential consequences of draining the ChNPP Cooling Pond, the authors conducted preliminary radio-ecological studies of its shoreline ecosystems. The radioactive contamination of the ChNPP Cooling Pond shoreline is fairly variable and ranges from 75 to 7,500 kBq/m2. Three areas with different contamination levels were selected to sample soils, vegetation, small mammals, birds, amphibians, and reptilians in order to measure their 137Cs and 90Sr content. Using the ERICA software, their dose exposures were estimated. For the 2008 conditions, the estimated dose rates were found to be as follows: amphibians - 11

  9. POOL WATER TREATMENT AND COOLING SYSTEM DESCRIPTION DOCUMENT

    Energy Technology Data Exchange (ETDEWEB)

    V. King

    2000-06-19

    The Pool Water Treatment and Cooling System is located in the Waste Handling Building (WHB), and is comprised of various process subsystems designed to support waste handling operations. This system maintains the pool water temperature within an acceptable range, maintains water quality standards that support remote underwater operations and prevent corrosion, detects leakage from the pool liner, provides the capability to remove debris from the pool, controls the pool water level, and helps limit radiological exposure to personnel. The pool structure and liner, pool lighting, and the fuel staging racks in the pool are not within the scope of the Pool Water Treatment and Cooling System. Pool water temperature control is accomplished by circulating the pool water through heat exchangers. Adequate circulation and mixing of the pool water is provided to prevent localized thermal hotspots in the pool. Treatment of the pool water is accomplished by a water treatment system that circulates the pool water through filters, and ion exchange units. These water treatment units remove radioactive and non-radioactive particulate and dissolved solids from the water, thereby providing the water clarity needed to conduct waste handling operations. The system also controls pool water chemistry to prevent advanced corrosion of the pool liner, pool components, and fuel assemblies. Removal of radioactivity from the pool water contributes to the project ALARA (as low as is reasonably achievable) goals. A leak detection system is provided to detect and alarm leaks through the pool liner. The pool level control system monitors the water level to ensure that the minimum water level required for adequate radiological shielding is maintained. Through interface with a demineralized water system, adequate makeup is provided to compensate for loss of water inventory through evaporation and waste handling operations. Interface with the Site Radiological Monitoring System provides continuous

  10. Simulation Analysis of the Four Configurations of Solar Desiccant Cooling System Using Evaporative Cooling in Tropical Weather in Malaysia

    Directory of Open Access Journals (Sweden)

    M. M. S. Dezfouli

    2014-01-01

    Full Text Available A high demand for air conditioning systems exists in hot and humid regions because of the warm climate during the year. The high energy consumption of conventional air conditioning system is the reason for our investigation of the solar desiccant cooling system as an energy-efficient cooling system. Four model configurations were considered to determine the best configuration of a solar desiccant cooling system: one-stage ventilation, one-stage recirculation, two-stage ventilation, and two-stage recirculation. These models were stimulated for 8,760 hr of operation under hot and humid weather in Malaysia. Several parameters (i.e., coefficient of performance or COP, room temperature and humidity ratio, and the solar fraction of each system were evaluated by detecting the temperature and humidity ratio of the different points of each configuration by TRNSYS simulation. The latent and sensible loads of the test room were 0.875 kW and 2.625 kW, respectively. By investigating the simulation results of the four systems, the ventilation modes were found to be higher than the recirculation modes in the one- and two-stage solar desiccant cooling systems. The isothermal dehumidification COP of the two-stage ventilation was higher than that of the two-stage recirculation. Hence, the two-stage ventilation mode desiccant cooling system in a hot and humid area has higher efficiency than the other configurations.

  11. 77 FR 36014 - Initial Test Program of Emergency Core Cooling Systems for Boiling-Water Reactors

    Science.gov (United States)

    2012-06-15

    ... COMMISSION Initial Test Program of Emergency Core Cooling Systems for Boiling-Water Reactors AGENCY: Nuclear...-1277, ``Initial Test Program of Emergency Core Cooling Systems for Boiling- Water Reactors.'' This... testing features of emergency core cooling systems (ECCSs) for boiling-water reactors (BWRs). DATES...

  12. System Study: Reactor Core Isolation Cooling 1998–2012

    Energy Technology Data Exchange (ETDEWEB)

    T. E. Wierman

    2013-10-01

    This report presents an unreliability evaluation of the reactor core isolation cooling (RCIC) system at 31 U.S. commercial boiling water reactors. Demand, run hours, and failure data from fiscal year 1998 through 2012 for selected components were obtained from the Equipment Performance and Information Exchange (EPIX). The unreliability results are trended for the most recent 10 year period while yearly estimates for system unreliability are provided for the entire active period. No statistically significant increasing trend was identified in the HPCI results. Statistically significant decreasing trends were identified for RCIC start-only and 8-hour trends.

  13. System Study: Reactor Core Isolation Cooling 1998-2014

    Energy Technology Data Exchange (ETDEWEB)

    Schroeder, John Alton [Idaho National Lab. (INL), Idaho Falls, ID (United States). Risk Assessment and Management Services Dept.

    2015-12-01

    This report presents an unreliability evaluation of the reactor core isolation cooling (RCIC) system at 31 U.S. commercial boiling water reactors. Demand, run hours, and failure data from fiscal year 1998 through 2014 for selected components were obtained from the Institute of Nuclear Power Operations (INPO) Consolidated Events Database (ICES). The unreliability results are trended for the most recent 10 year period, while yearly estimates for system unreliability are provided for the entire active period. No statistically significant trends were identified in the RCIC results.

  14. Passive-solar directional-radiating cooling system

    Energy Technology Data Exchange (ETDEWEB)

    Hull, John R. (Hinsdale, IL); Schertz, William W. (Batavia, IL)

    1986-01-01

    A radiative cooling system for use with an ice-making system having a radiating surface aimed at the sky for radiating energy at one or more wavelength bands for which the atmosphere is transparent and a cover thermally isolated from the radiating surface and transparent at least to the selected wavelength or wavelengths, the thermal isolation reducing the formation of condensation on the radiating surface and/or cover and permitting the radiation to continue when the radiating surface is below the dewpoint of the atmosphere, and a housing supporting the radiating surface, cover and heat transfer means to an ice storage reservoir.

  15. System Study: Reactor Core Isolation Cooling 1998–2013

    Energy Technology Data Exchange (ETDEWEB)

    Schroeder, John Alton [Idaho National Lab. (INL), Idaho Falls, ID (United States). Risk Assessment and Management Services Dept.

    2015-01-31

    This report presents an unreliability evaluation of the reactor core isolation cooling (RCIC) system at 31 U.S. commercial boiling water reactors. Demand, run hours, and failure data from fiscal year 1998 through 2013 for selected components were obtained from the Institute of Nuclear Power Operations (INPO) Consolidated Events Database (ICES). The unreliability results are trended for the most recent 10-year period, while yearly estimates for system unreliability are provided for the entire active period. No statistically significant trends were identified in the RCIC results.

  16. Expanding the potential for saline formations : modeling carbon dioxide storage, water extraction and treatment for power plant cooling.

    Energy Technology Data Exchange (ETDEWEB)

    2011-04-01

    The National Water, Energy and Carbon Sequestration simulation model (WECSsim) is being developed to address the question, 'Where in the current and future U.S. fossil fuel based electricity generation fleet are there opportunities to couple CO{sub 2} storage and extracted water use, and what are the economic and water demand-related impacts of these systems compared to traditional power systems?' The WECSsim collaborative team initially applied this framework to a test case region in the San Juan Basin, New Mexico. Recently, the model has been expanded to incorporate the lower 48 states of the U.S. Significant effort has been spent characterizing locations throughout the U.S. where CO{sub 2} might be stored in saline formations including substantial data collection and analysis efforts to supplement the incomplete brine data offered in the NatCarb database. WECSsim calculates costs associated with CO{sub 2} capture and storage (CCS) for the power plant to saline formation combinations including parasitic energy costs of CO{sub 2} capture, CO{sub 2} pipelines, water treatment options, and the net benefit of water treatment for power plant cooling. Currently, the model can identify the least-cost deep saline formation CO{sub 2} storage option for any current or proposed coal or natural gas-fired power plant in the lower 48 states. Initial results suggest that additional, cumulative water withdrawals resulting from national scale CCS may range from 676 million gallons per day (MGD) to 30,155 MGD depending on the makeup power and cooling technologies being utilized. These demands represent 0.20% to 8.7% of the U.S. total fresh water withdrawals in the year 2000, respectively. These regional and ultimately nation-wide, bottom-up scenarios coupling power plants and saline formations throughout the U.S. can be used to support state or national energy development plans and strategies.

  17. Model based predictive control of a high temperature gas cooled power plant coupled to a hydrogen production facility

    Science.gov (United States)

    Rhoads, Lloyd A.

    This thesis builds upon recent studies focusing on modeling, operation, and control of high temperature gas cooled reactors. A computer model was developed, based on mass, energy, and momentum balances of control volumes throughout the plant. Several simulations of the plant behavior were conducted and their results were compared with those from the literature. Proportional control was combined with optimal control to form a time varying, adjustable gain predictive controller which adjusts the proportional gains during transients. The controller was designed to utilize control rod motions and bypass control valves to maintain desired plant conditions. An optimization scheme was introduced to efficiently solve the optimization problem formulated as part of the predictive controller operation. Several additional transients were run to examine the full plant controller performance. Multiple predictive controllers were designed and their performance was compared with a proportional controller throughout each transient. The predictive controller results confirmed the importance of proper selection of the optimal controller parameters, in particular the controller time step size and the horizon time. The well-designed proportional controllers clearly demonstrated improvements in plant performance during short time scale transients, namely a loss of secondary heat transfer transient and a step change in desired power transient. Results from long time scale transients demonstrated the capabilities of the proposed bypass control system to control electrical power production without the need for storage vessels.

  18. A gas-cooled reactor surface power system

    Science.gov (United States)

    Lipinski, Ronald J.; Wright, Steven A.; Lenard, Roger X.; Harms, Gary A.

    1999-01-01

    A human outpost on Mars requires plentiful power to assure survival of the astronauts. Anywhere from 50 to 500 kW of electric power (kWe) will be needed, depending on the number of astronauts, level of scientific activity, and life-cycle closure desired. This paper describes a 250-kWe power system based on a gas-cooled nuclear reactor with a recuperated closed Brayton cycle conversion system. The design draws upon the extensive data and engineering experience developed under the various high-temperature gas cooled reactor programs and under the SP-100 program. The reactor core is similar in power and size to the research reactors found on numerous university campuses. The fuel is uranium nitride clad in Nb1%Zr, which has been extensively tested under the SP-100 program. The fuel rods are arranged in a hexagonal array within a BeO block. The BeO softens the spectrum, allowing better use of the fuel and stabilizing the geometry against deformation during impact or other loadings. The system has a negative temperature feedback coefficient so that the power level will automatically follow a variable load without the need for continuous adjustment of control elements. Waste heat is removed by an air-cooled heat exchanger using cold Martian air. The amount of radioactivity in the reactor at launch is very small (less than a Curie, and about equal to a truckload of uranium ore). The system will need to be engineered so that criticality can not occur for any launch accident. This system is also adaptable for electric propulsion or life-support during transit to and from Mars.

  19. Study on metal accumulation in aquatic plants of Cuciurgan cooling reservoir

    Directory of Open Access Journals (Sweden)

    Zubcov Elena

    2014-07-01

    Full Text Available The biomass of plants from the Cuciurgan cooling reservoir of the Moldovan Thermal Power Plant is dependent on the reservoir thermofication and bore considerable modifications. The contents of many metals in aquatic plants were highly correlated with their contents in water: r=0,87-0,91. The dynamics of trace element accumulation depends on seasonal factors. From the beginning of spring to the end of summer and beginning of autumn, the concentrations of trace elements increased by large increments, while with the decrease in temperature below 10°C, an opposite effect was observed. After plant death, a significant part of accumulated trace elements are released into the water, in the most cases this being associated with organic compounds. More than one half of the amount of trace elements is deposited with the decaying plants in the bottom sediments. Therefore, difficulties may arise, while identifying the role of aquatic plants in biogenic migration of metals in aquatic ecosystems and water purification processes.

  20. System performance and economic analysis of solar-assisted cooling/heating system

    KAUST Repository

    Huang, B.J.

    2011-11-01

    The long-term system simulation and economic analysis of solar-assisted cooling/heating system (SACH-2) was carried out in order to find an economical design. The solar heat driven ejector cooling system (ECS) is used to provide part of the cooling load to reduce the energy consumption of the air conditioner installed as the base-load cooler. A standard SACH-2 system for cooling load 3.5. kW (1. RT) and daily cooling time 10 h is used for case study. The cooling performance is assumed only in summer seasons from May to October. In winter season from November to April, only heat is supplied. Two installation locations (Taipei and Tainan) were examined.It was found from the cooling performance simulation that in order to save 50% energy of the air conditioner, the required solar collector area is 40m2 in Taipei and 31m2 in Tainan, for COPj=0.2. If the solar collector area is designed as 20m2, the solar ejector cooling system will supply about 17-26% cooling load in Taipei in summer season and about 21-27% cooling load in Tainan. Simulation for long-term performance including cooling in summer (May-October) and hot water supply in winter (November-April) was carried out to determine the monthly-average energy savings. The corresponding daily hot water supply (with 40°C temperature rise of water) for 20m2 solar collector area is 616-858L/day in Tainan and 304-533L/day in Taipei.The economic analysis shows that the payback time of SACH-2 decreases with increasing cooling capacity. The payback time is 4.8. years in Tainan and 6.2. years in Taipei when the cooling capacity >10. RT. If the ECS is treated as an additional device used as a protective equipment to avoid overheating of solar collectors and to convert the excess solar heat in summer into cooling to reduce the energy consumption of air conditioner, the payback time is less than 3 years for cooling capacity larger than 3. RT. © 2011 Elsevier Ltd.

  1. Pilot-scale cooling tower to evaluate corrosion, scaling, and biofouling control strategies for cooling system makeup water.

    Science.gov (United States)

    Chien, S H; Hsieh, M K; Li, H; Monnell, J; Dzombak, D; Vidic, R

    2012-02-01

    Pilot-scale cooling towers can be used to evaluate corrosion, scaling, and biofouling control strategies when using particular cooling system makeup water and particular operating conditions. To study the potential for using a number of different impaired waters as makeup water, a pilot-scale system capable of generating 27,000 kJ∕h heat load and maintaining recirculating water flow with a Reynolds number of 1.92 × 10(4) was designed to study these critical processes under conditions that are similar to full-scale systems. The pilot-scale cooling tower was equipped with an automatic makeup water control system, automatic blowdown control system, semi-automatic biocide feeding system, and corrosion, scaling, and biofouling monitoring systems. Observed operational data revealed that the major operating parameters, including temperature change (6.6 °C), cycles of concentration (N = 4.6), water flow velocity (0.66 m∕s), and air mass velocity (3660 kg∕h m(2)), were controlled quite well for an extended period of time (up to 2 months). Overall, the performance of the pilot-scale cooling towers using treated municipal wastewater was shown to be suitable to study critical processes (corrosion, scaling, biofouling) and evaluate cooling water management strategies for makeup waters of complex quality.

  2. Presence of pathogenic amoebae in power plant cooling waters. Final report, October 15, 1977-September 30, 1979. [Naegleria fowleri

    Energy Technology Data Exchange (ETDEWEB)

    Tyndall, R.L.; Willaert, E.; Stevens, A.R.

    1981-03-01

    Cooling-water-associated algae and sediments from five northern and five southern or western electric power plants were tested for the presence of pathogenic amoebae. In addition, water algae and sediments from five northern and five southern/western sites not associated with power plants were tested. There was a significant correlation at northern power plants between the presence of thermophilic, pathogenic amoebae in cooling waters and thermal additions. Presence of the pathogenic did not correlate with salinity, pH, conductivity, or a variety of various chemical components of the cooling waters. Selected pathogenic isolates were tested serologically and were classified as Naegleria fowleri. Although thermal additions were shown to be contributing factor in predisposing cooling waters to the growth of pathogenic amoebae, the data suggest the involvement of other currently undefined parameters associated with the presence of the pathogenic amoebae. 35 refs., 21 tabs.

  3. Development of a water-mist cooling system: A 12,500 Kcal/h air-cooled chiller

    Directory of Open Access Journals (Sweden)

    Chung-Neng Huang

    2015-11-01

    Full Text Available Global warming and energy exhaustion problems are becoming a severe problems, of which energy conservation and carbon reduction are the most critical. Between 40% and 48% of the total electricity used in a building is consumed by air conditioning systems. The development of a supersonic water-misting cooling system with a fuzzy control system is proposed to optimize existing condenser noise, space, and energy consumption, as well as to address problems with cooling capacity resulting from improper control between compressors and condensers. An experimental platform was established for conducting tests, observing cooling efficiencies, and calculating power saving statuses. Comparing the observed cooling efficiency, a temperature difference of 5.4 °C was determined before and after the application; this is significant regarding efficiency. The method produces no pollution or water accumulation. When compared with fixed frequency air-cooled water chillers, an exceptional energy saving of 25% was observed. The newly developed supersonic mist-cooled chiller is an excellent solution to increasing water and electricity fees.

  4. User's manual for the BNW-I optimization code for dry-cooled power plants. Volume III. [PLCIRI

    Energy Technology Data Exchange (ETDEWEB)

    Braun, D.J.; Daniel, D.J.; De Mier, W.V.; Faletti, D.W.; Wiles, L.E.

    1977-01-01

    This appendix to User's Manual for the BNW-1 Optimization Code for Dry-Cooled Power Plants provides a listing of the BNW-I optimization code for determining, for a particular size power plant, the optimum dry cooling tower design using a plastic tube cooling surface and circular tower arrangement of the tube bundles. (LCL)

  5. Wind power plant system services

    DEFF Research Database (Denmark)

    Basit, Abdul; Altin, Müfit

    Traditionally, conventional power plants have the task to support the power system, by supplying power balancing services. These services are required by the power system operators in order to secure a safe and reliable operation of the power system. However, as in the future the wind power...... is going more and more to replace conventional power plants, the sources of conventional reserve available to the system will be reduced and fewer conventional plants will be available on-line to share the regulation burden. The reliable operation of highly wind power integrated power system might...... then beat risk unless the wind power plants (WPPs) are able to support and participate in power balancing services. The objective of this PhD project is to develop and analyse control strategies which can increase the WPPs capability to provide system services, such as active power balancing control...

  6. Isolation of Naegleria fowleri from the cooling pond of an electric power plant in France

    Energy Technology Data Exchange (ETDEWEB)

    Dive, D.G.; Leclerc, H.; De Jonckheere, J.; Delattre, J.M.

    Eleven strains of Naegleria have been isolated from 126 samples of the cooling pond of an electric power plant near Metz, France. Three strains showed specific characters of N. fowleri (pathogenicity for mice after intranasal instillation, immunofluorescence with anti N. fowleri serum and non-agglutination with ConA up to 1 mg/ml. Some particular characteristics were noted; the cysts showed a high number of pores and the pathogenicity was is lower using Swiss mice than using NMRI mice. The need for a standardization of methods for isolation and characterization are discussed as well as the occurrence of N. fowleri at the site.

  7. Wetland Water Cooling Partnership: The Use of Constructed Wetlands to Enhance Thermoelectric Power Plant Cooling and Mitigate the Demand of Surface Water Use

    Energy Technology Data Exchange (ETDEWEB)

    Apfelbaum, Steven; Duvall, Kenneth; Nelson, Theresa; Mensing, Douglas; Bengtson, Harlan; Eppich, John; Penhallegon, Clayton; Thompson, Ry

    2013-09-30

    Through the Phase I study segment of contract #DE-NT0006644 with the U.S. Department of Energy’s National Energy Technology Laboratory, Applied Ecological Services, Inc. and Sterling Energy Services, LLC (the AES/SES Team) explored the use of constructed wetlands to help address stresses on surface water and groundwater resources from thermoelectric power plant cooling and makeup water requirements. The project objectives were crafted to explore and develop implementable water conservation and cooling strategies using constructed wetlands (not existing, naturally occurring wetlands), with the goal of determining if this strategy has the potential to reduce surface water and groundwater withdrawals of thermoelectric power plants throughout the country. Our team’s exploratory work has documented what appears to be a significant and practical potential for augmenting power plant cooling water resources for makeup supply at many, but not all, thermoelectric power plant sites. The intent is to help alleviate stress on existing surface water and groundwater resources through harvesting, storing, polishing and beneficially re-using critical water resources. Through literature review, development of conceptual created wetland plans, and STELLA-based modeling, the AES/SES team has developed heat and water balances for conventional thermoelectric power plants to evaluate wetland size requirements, water use, and comparative cooling technology costs. The ecological literature on organism tolerances to heated waters was used to understand the range of ecological outcomes achievable in created wetlands. This study suggests that wetlands and water harvesting can provide a practical and cost-effective strategy to augment cooling waters for thermoelectric power plants in many geographic settings of the United States, particularly east of the 100th meridian, and in coastal and riverine locations. The study concluded that constructed wetlands can have significant positive

  8. System design package for the solar heating and cooling central data processing system

    Science.gov (United States)

    1978-01-01

    The central data processing system provides the resources required to assess the performance of solar heating and cooling systems installed at remote sites. These sites consist of residential, commercial, government, and educational types of buildings, and the solar heating and cooling systems can be hot-water, space heating, cooling, and combinations of these. The instrumentation data associated with these systems will vary according to the application and must be collected, processed, and presented in a form which supports continuity of performance evaluation across all applications. Overall software system requirements were established for use in the central integration facility which transforms raw data collected at remote sites into performance evaluation information for assessing the performance of solar heating and cooling systems.

  9. Solar-Cooled Hotel in the Virgin Islands

    Science.gov (United States)

    Harber, H.

    1982-01-01

    Performance of solar cooling system is described in 21-page report. System provides cooling for public areas including ball rooms, restaurant, lounge, lobby and shops. Chilled water from solar-cooling system is also used to cool hot water from hotel's desalinization plant.

  10. Solar-Cooled Hotel in the Virgin Islands

    Science.gov (United States)

    Harber, H.

    1982-01-01

    Performance of solar cooling system is described in 21-page report. System provides cooling for public areas including ball rooms, restaurant, lounge, lobby and shops. Chilled water from solar-cooling system is also used to cool hot water from hotel's desalinization plant.

  11. Parameter analysis for feasibility evaluation of shallow groundwater cooling of power plants

    Science.gov (United States)

    Dirix, Katrijn; Harcouët-Menou, Virginie; Van Bael, Johan; Laenen, Ben

    2017-04-01

    This paper presents the first results of a finite difference-based numerical model, aiming to evaluate the potential of a new cooling concept that is based on the use of closed loop groundwater cooling integrated in a binary cycle. The new concept includes the seasonal combination of air cooling and shallow groundwater cooling and is part of the H2020 MATChING project. The proposed cooling system under investigation will be compared with dry type cooler condenser (e.g. air cooled condenser systems) and aims to reduce overall water withdrawal without compromising the energy efficiency of the system. The pilot site for this evaluation is the geothermal Balmatt site in Mol-Dessel, Belgium. When operating at its full potential, this site could produce up to 27 MW of heat. To (partly) cool this heat, water from the permeable Miocene 'Diest formation' could be used in a closed loop, i.e. without consuming water. This aquifer is located at a depth of 35 to 151 m bgl, consists of glauconitic coarse sands and has an average permeability of 10 m/day. The water has a temperature of ca. 12°C. In the design under evaluation, this water will be heated up to a maximum of 22°C after passing through the condenser. During summer months, the water will be injected directly back into the aquifer, while in winter, additional cooling will be realised using an air cooler before injecting the water (at ca. 6 °C). By adding this extra cooling step, the lifetime of the system will increase significantly. To cool the large amount of rejected heat, over 2000 m3/h of water needs to be extracted from the aquifer, requiring the installation of several doublet systems. The feasibility of such an installation depends on several interdependent factors, such as temperature, pressure, well distance, distance between the doublets, permeability and natural flow conditions. Since no exact values of most of these factors are available, a large uncertainty exists for feasibility predictions. To assess

  12. Sensitivity of energy and exergy performances of heating and cooling systems to auxiliary components

    DEFF Research Database (Denmark)

    Kazanci, Ongun Berk; Shukuya, Masanori; Olesen, Bjarne W.

    2017-01-01

    should be used in design and analysis of the whole heating and cooling systems, in addition to the energy analysis. In this study, water-based (floor heating and cooling, and radiator heating) and air-based (air heating and cooling) heating and cooling systems were compared in terms of their energy use...... and exergy consumption for auxiliary components (pumps and fans). The effects of the auxiliary components on whole system energy and exergy performance were identified. Water-based heating systems required 68% lower auxiliary exergy input than the warm-air heating system with heat recovery, and floor cooling...

  13. Summary of Field Measurement on UF6 Cylinders Using Electro-Mechanically Cooled Systems

    Energy Technology Data Exchange (ETDEWEB)

    McGinnis, Brent R [ORNL; Smith, Steven E [ORNL; Solodov, Alexander A [ORNL; Whitaker, J Michael [ORNL; Morgan, James B [ORNL; MayerII, Richard L. [USEC, Inc.; Montgomery, J. Brent [U.S. Enrichment Corporation Paducah Gaseous Diffusion Plant

    2009-01-01

    Measurement of the enrichment of solid state UF6 stored within large metal cylinders is a task commonly performed by plant operators and inspectors. The measurement technologies typically used range from low-resolution, high-efficiency sodium iodide detectors to high-resolution, moderate-efficiency high-purity germanium (HPGe) detectors. The technology used and methods deployed are dependent upon the material being measured, environmental conditions, time constraints, and measurement-precision requirements. Operators and inspectors typically use specially designed, HPGe detectors that are cooled with liquid nitrogen in situations where high-resolution measurements are required. However, the requirement for periodically refilling the system with liquid nitrogen makes remote usage cumbersome and slow. The task of cooling the detector reduces the available time for the inspector to perform other safeguards activities while on site. If the inspector has to reduce the count time for each selected cylinder to ensure that all preselected cylinders are measured during the inspection, the resulting measurement uncertainties may be increased, making it more difficult to detect and verify potential discrepancies in the operator's declarations. However, recent advances in electromechanically cooled HPGe detectors may provide the inspector with an improved verification tool by eliminating the need for liquid nitrogen. This report provides a summary of test results for field measurements performed using electromechanically cooled HPGe detectors on depleted, natural, and low-enriched uranium cylinders. The results of the study provide valuable information to inspectors and operators regarding the capabilities and limitations of electromechanically cooled systems based on true field-measurement conditions.

  14. Model Based Control of Single-Phase Marine Cooling Systems

    DEFF Research Database (Denmark)

    Hansen, Michael

    2014-01-01

    ”, it is shown that the part of the proposed model relating to the thermodynamics is dynamically accurate and with relatively small steady state deviations. The same is shown for a linear version of the part of the model governing the hydraulics of the cooling system. On the subject of control, the main focus...... in this work is on the development of a nonlinear robust control design. The design is based on principles from feedback. linearization to compensate for nonlinearities as well as transport delays by including a delay estimate in the feedback law. To deal with the uncertainties that emerged from the feedback...

  15. System and method for cooling a superconducting rotary machine

    Science.gov (United States)

    Ackermann, Robert Adolf; Laskaris, Evangelos Trifon; Huang, Xianrui; Bray, James William

    2011-08-09

    A system for cooling a superconducting rotary machine includes a plurality of sealed siphon tubes disposed in balanced locations around a rotor adjacent to a superconducting coil. Each of the sealed siphon tubes includes a tubular body and a heat transfer medium disposed in the tubular body that undergoes a phase change during operation of the machine to extract heat from the superconducting coil. A siphon heat exchanger is thermally coupled to the siphon tubes for extracting heat from the siphon tubes during operation of the machine.

  16. Thermal design of lithium bromide-water solution vapor absorption cooling system for indirect evaporative cooling for IT pod

    Science.gov (United States)

    Sawant, Digvijay Ramkrishna

    Nowadays with increase use of internet, mobile there is increase in heat which ultimately increases the efficient cooling system of server room or IT POD. Use of traditional ways of cooling system has ultimately increased CO2 emission and depletion of CFC's are serious environmental issues which led scientific people to improve cooling techniques and eliminate use of CFC's. To reduce dependency on fossil fuels and 4environmental friendly system needed to be design. For being utilizing low grade energy source such as solar collector and reducing dependency on fossil fuel vapour absorption cooling system has shown a great driving force in today's refrigeration systems. This LiBr-water aabsorption cooling consists of five heat exchanger namely: Evaporator, Absorber, Solution Heat Exchanger, Generator, Condenser. The thermal design was done for a load of 23 kW and the procedure was described in the thesis. There are 120 servers in the IT POD emitting 196 W of heat each on full load and some of the heat was generated by the computer placed inside the IT POD. A detailed procedure has been discussed. A excel spreadsheet was to prepared with varying tube sizes to see the effect on flows and ultimately overall heat transfer coefficient.

  17. Measures for noise pollution abatement in existing cooling tower systems; Massnahmen zur Geraeuschminderung an bestehenden Kuehlturmanlagen

    Energy Technology Data Exchange (ETDEWEB)

    Niessen, R. [Sulzer-Escher Wyss GmbH, Lindau (Germany)

    1998-09-01

    The operator`s order discussed by the paper was for planning and performance of backfitting measures for noise pollution abatement in an existing cooling tower system equipped with sound attenuation devices. Although the existing plant was operating in compliance with the legal noise emission limits, residents of neighbouring dwellings had been complaining about noise pollution. (orig./CB) [Deutsch] Die Aufgabe, eine nachtraegliche Massnahme zur Laermminderung an einer bestehenden, mit Schalldaempfern ausgeruesteten Anlage zu planen und durchzufuehren, wurde vom Betreiber einer Rueckkuehlanlage gestellt. Der vom Gesetzgeber definierte Grenzwert fuer den Nachtbetrieb wurde mit der bestehenden Anlage zwar erreicht, doch die Anwohner fuehlten eine Belaestigung durch den Anlagenbetrieb. (orig./GL)

  18. Cooling Tower Optimization A Simple Way to Generate Green Megawatts and to Increase the Efficiency of a Power Plant

    Energy Technology Data Exchange (ETDEWEB)

    Strohmer, F.

    2014-07-01

    The profitability of nuclear power plants is worldwide challenged by low electricity prices. One hand low cost shale gas is offering a low price electricity production , other hand additional taxes on fuel are reducing the operating income of nuclear power stations. The optimization of cooling towers can help to increase the efficiency and profit of a nuclear power plant. (Author)

  19. Automatic heating and cooling system in a gas purge microsyringe extraction.

    Science.gov (United States)

    Piao, Xiangfan; Bi, Jinhu; Yang, Cui; Wang, Xiaoping; Wang, Juan; Li, Donghao

    2011-10-30

    The gas purge microsyringe extraction (GP-MSE) technique offers quantitative and simultaneous extraction, and rapid gas chromatographic-mass spectrometric determination of volatile and semivolatile chemicals is possible. To simplify the application, a new automatic temperature control system was developed here. Stable heating and cooling over a wide range of temperatures were achieved using a micro-heater and thermoelectric cooler under varying gas flow conditions. Temperatures could be accurately controlled in the range 20-350°C (heating) and 20 to -4°C (cooling). Temperature effects on the extraction performance of the GP-MSE were experimentally investigated by comparing the recoveries of polycyclic aromatic hydrocarbons (PAHs) under various experimental conditions. A sample treatment was completed within 3 min, which is much less than the time required for chromatographic analysis. The recovery of chemicals determined ranged from 81 to 96%. High reproducibility data (RSD ≤ 5%) were obtained for direct extraction of various analytes in spiked complex plant and biological samples. The data show that the heating and cooling system has potential applications in GP-MSE system for the direct determination of various kinds of volatile and semivolatile chemicals from complex matrices without any, or only minor, sample pretreatment.

  20. Cooled electronic system with liquid-cooled cold plate and thermal spreader coupled to electronic component

    Energy Technology Data Exchange (ETDEWEB)

    Chainer, Timothy J.; Graybill, David P.; Iyengar, Madhusudan K.; Kamath, Vinod; Kochuparambil, Bejoy J.; Schmidt, Roger R.; Steinke, Mark E.

    2016-04-05

    Apparatus and method are provided for facilitating cooling of an electronic component. The apparatus includes a liquid-cooled cold plate and a thermal spreader associated with the cold plate. The cold plate includes multiple coolant-carrying channel sections extending within the cold plate, and a thermal conduction surface with a larger surface area than a surface area of the component to be cooled. The thermal spreader includes one or more heat pipes including multiple heat pipe sections. One or more heat pipe sections are partially aligned to a first region of the cold plate, that is, where aligned to the surface to be cooled, and partially aligned to a second region of the cold plate, which is outside the first region. The one or more heat pipes facilitate distribution of heat from the electronic component to coolant-carrying channel sections of the cold plate located in the second region of the cold plate.

  1. Cooled electronic system with liquid-cooled cold plate and thermal spreader coupled to electronic component

    Energy Technology Data Exchange (ETDEWEB)

    Chainer, Timothy J.; Graybill, David P.; Iyengar, Madhusudan K.; Kamath, Vinod; Kochuparambil, Bejoy J.; Schmidt, Roger R.; Steinke, Mark E.

    2016-08-09

    Apparatus and method are provided for facilitating cooling of an electronic component. The apparatus includes a liquid-cooled cold plate and a thermal spreader associated with the cold plate. The cold plate includes multiple coolant-carrying channel sections extending within the cold plate, and a thermal conduction surface with a larger surface area than a surface area of the component to be cooled. The thermal spreader includes one or more heat pipes including multiple heat pipe sections. One or more heat pipe sections are partially aligned to a first region of the cold plate, that is, where aligned to the surface to be cooled, and partially aligned to a second region of the cold plate, which is outside the first region. The one or more heat pipes facilitate distribution of heat from the electronic component to coolant-carrying channel sections of the cold plate located in the second region of the cold plate.

  2. Thermodynamic Analysis of a Power Plant Integrated with Fogging Inlet Cooling and a Biomass Gasification

    Directory of Open Access Journals (Sweden)

    Hassan Athari

    2015-01-01

    Full Text Available Biomass energy and especially biofuels produced by biomass gasification are clean and renewable options for power plants. Also, on hot days the performance of gas turbines decreases substantially, a problem that can be mitigated by fog cooling. In the present paper, a biomass-integrated fogging steam injected gas turbine cycle is analyzed with energy and exergy methods. It is observed that (1 increasing the compressor pressure ratio raises the air flow rate in the plant but reduces the biomass flow rate; (2 increasing the gas turbine inlet temperature decreases the air and biomass flow rates; (3 increasing the compressor pressure ratio raises the energy and exergy efficiencies, especially at lower pressure ratios; (4 increasing the gas turbine inlet temperature raises both efficiencies; and (5 overspray increases the energy efficiency and net cycle power slightly. The gas turbine exhibits the highest exergy efficiency of the cycle components and the combustor the lowest. A comparison of the cycle with similar cycles fired by natural gas and differently configured cycles fueled by biomass shows that the cycle with natural gas firing has an energy efficiency 18 percentage points above the biomass fired cycle, and that steam injection increases the energy efficiency about five percentage points relative to the cycle without steam injection. Also, the influence of steam injection on energy efficiency is more significant than fog cooling.

  3. Reliability and Maintainability Data for Liquid Metal Cooling Systems

    Energy Technology Data Exchange (ETDEWEB)

    Cadwallader, Lee Charles [Idaho National Laboratory

    2015-05-01

    One of the coolants of interest for future fusion breeding blankets is lead-lithium. As a liquid metal it offers the advantages of high temperature operation for good station efficiency, low pressure, and moderate flow rate. This coolant is also under examination for use in test blanket modules to be used in the ITER international project. To perform reliability, availability, maintainability and inspectability (RAMI) assessment as well as probabilistic safety assessment (PSA) of lead-lithium cooling systems, component failure rate data are needed to quantify the system models. RAMI assessment also requires repair time data and inspection time data. This paper presents a new survey of the data sets that are available at present to support RAMI and PSA quantification. Recommendations are given for the best data values to use when quantifying system models.

  4. Evaporative Cooling and Dehumidification Garment for Portable Life Support Systems

    Science.gov (United States)

    Izenson, Michael; Chen, Weibo; Bue, Grant

    2013-01-01

    This paper describes the design and development of an innovative thermal and humidity control system for future space suits. The system comprises an evaporation cooling and dehumidification garment (ECDG) and a lithium chloride absorber radiator (LCAR). The ECDG absorbs heat and water vapor from inside the suit pressure garment, while the LCAR rejects heat to space without venting water vapor. The ECDG is built from thin, flexible patches with coversheets made of non-porous, water-permeable membranes that -enclose arrays of vapor flow passages. Water vapor from inside the spacesuit diffuses across the water permeable membranes, enters the vapor flow channels, and then flows to the LCAR, thus dehumidifying the internal volume of the space suit pressure garment. Additional water evaporation inside the ECDG provides cooling for sensible heat loads. -The heat released from condensation and absorption in the LCAR is rejected to the environment by thermal radiation. We have assembled lightweight and flexible ECDG pouches from prototypical materials and measured their performance in a series of separate effects tests under well-controlled, prototypical conditions. Sweating hot plate tests at typical space suit pressures show that ECDG pouches can absorb over 60 W/ft of latent heat and 20 W/ft of sensible heat from the pressure garment environment. These results are in good agreement with the predictions of our analysis models.

  5. Application of Hastelloy X in gas-cooled reactor systems

    Energy Technology Data Exchange (ETDEWEB)

    Brinkman, C.R.; Rittenhouse, P.L.; Corwin, W.R.; Strizak, J.P.; Lystrup, A.; DiStefano, J.R.

    1976-10-01

    Hastelloy X, an Ni--Cr--Fe--Mo alloy, may be an important structural alloy for components of gas-cooled reactor systems. Expected applications of this alloy in the High-Temperature Gas-Cooled Reactor (HTGR) are discussed, and the development of interim mechanical properties and supporting data are reported. Properties of concern include tensile, creep, creep-rupture, fatigue, creep-fatigue interaction, subcritical crack growth, thermal stability, and the influence of helium environments with controlled amounts of impurities on these properties. In order to develop these properties in helium environments that are expected to be prototypic of HTGR operating conditions, it was necessary to construct special environmental test systems. Details of construction and operating parameters are described. Interim results from tests designed to determine the above properties are presented. To date a fairly extensive amount of information has been generated on this material at Oak Ridge National Laboratory and elsewhere concerning behavior in air, which is reviewed. However, only limited data are available from tests conducted in helium. Comparisons of the fatigue and subcritical growth behavior in air between Hastelloy X and a number of other structural alloys are given.

  6. An experimental comparison between a novel and a conventional cooling system for the blown film process

    Science.gov (United States)

    Janas, M.; Andretzky, M.; Neubert, B.; Kracht, F.; Wortberg, J.

    2016-03-01

    The blown film extrusion is a significant manufacturing process of plastic films. Compared to other extrusion processes, the productivity is limited by the cooling of the extrudate. A conventional cooling system for the blown film application provides the cooling air tangentially, homogeneous over the whole circumference of the bubble, using a single or dual lip cooling ring. In prior works, major effects could be identified that are responsible for a bad heat transfer. Besides the formation of a boundary sublayer on the film surface due to the fast flowing cooling air, there is the interaction between the cooling jet and the ambient air. In order to intensify the cooling of a tubular film, a new cooling approach was developed, called Multi-Jet. This system guides the air vertically on the film surface, using several slit nozzles over the whole tube formation zone. Hence, the jets penetrate the sublayer. To avoid the interaction with the ambient air, the bubble expansion zone is surrounded by a housing. By means of a numeric investigation, the novel cooling approach and the efficiency of the cooling system could be proved. Thereby, a four times higher local heat transfer coefficient is achieved compared to a conventional cooling device. In this paper, the Multi-Jet cooling system is experimentally tested for several different process conditions. To identify a worth considering cooling configuration of the novel cooling system for the experiment, a simulation tool presets the optimal process parameters. The comparison between the results of the new and a conventional system shows that the novel cooling method is able to gain the same frost line height using a 40% lower cooling air volume flow. Due to the housing of the tube formation zone, a heat recovery can be achieved.

  7. Desalting a process cooling water using nanofiltration

    NARCIS (Netherlands)

    Radier, R.G.J.; van Oers, C.W.; Steenbergen, A.; Wessling, Matthias

    2001-01-01

    The cooling water system of a chemical plant of Akzo Nobel is a partly open system. The site is located at the North Sea. The air in contact with the cooling water contains seawater droplets dissolving and increasing the chloride concentration. The cooling water contains chromate to protect the inst

  8. Using waste heat for cooling with compact resorption plants; Kompakte Resorptionsanlagen zum Kuehlen mit Abwaerme

    Energy Technology Data Exchange (ETDEWEB)

    Weimer, Thomas [Makatec GmbH, Bondorf (Germany); Helle, Kirsten [Institut fuer Energie- und Umwelttechnik (IUTA) e.V. Energy Conversion and Energy Storage, Duisburg (Germany)

    2012-03-15

    Cooling technologies gain an increasing importance in the industrialized world. Ammonia based absorption chillers can be employed for air conditioning and refrigeration, using waste heat as driving force. With using the resorption technology for ammonia based absorption chillers gas cleaning is needless. Resorption systems consist of two solvent cycles exchanging refrigerant, both with absorber, desorber and solvent heat exchanger. Plate heat exchangers or new membrane contactors used as desorber and absorber lead to compact resorption chillers. (orig.)

  9. Use of Produced Water in Recirculated Cooling Systems at Power Generating Facilities

    Energy Technology Data Exchange (ETDEWEB)

    C. McGowin; M. DiFilippo; L. Weintraub

    2006-06-30

    Tree ring studies indicate that, for the greater part of the last three decades, New Mexico has been relatively 'wet' compared to the long-term historical norm. However, during the last several years, New Mexico has experienced a severe drought. Some researchers are predicting a return of very dry weather over the next 30 to 40 years. Concern over the drought has spurred interest in evaluating the use of otherwise unusable saline waters to supplement current fresh water supplies for power plant operation and cooling and other uses. The U.S. Department of Energy's National Energy Technology Laboratory sponsored three related assessments of water supplies in the San Juan Basin area of the four-corner intersection of Utah, Colorado, Arizona, and New Mexico. These were (1) an assessment of using water produced with oil and gas as a supplemental supply for the San Juan Generating Station (SJGS); (2) a field evaluation of the wet-surface air cooling (WSAC) system at SJGS; and (3) the development of a ZeroNet systems analysis module and an application of the Watershed Risk Management Framework (WARMF) to evaluate a range of water shortage management plans. The study of the possible use of produced water at SJGS showed that produce water must be treated to justify its use in any reasonable quantity at SJGS. The study identified produced water volume and quality, the infrastructure needed to deliver it to SJGS, treatment requirements, and delivery and treatment economics. A number of produced water treatment alternatives that use off-the-shelf technology were evaluated along with the equipment needed for water treatment at SJGS. Wet surface air-cooling (WSAC) technology was tested at the San Juan Generating Station (SJGS) to determine its capacity to cool power plant circulating water using degraded water. WSAC is a commercial cooling technology and has been used for many years to cool and/or condense process fluids. The purpose of the pilot test was to

  10. Dechlorination Technology Manual. Final report. [Utility cooling water discharge systems

    Energy Technology Data Exchange (ETDEWEB)

    Aschoff, A.F.; Chiesa, R.J.; Jacobs, M.H.; Lee, Y.H.; Mehta, S.C.; Meko, A.C.; Musil, R.R.; Sopocy, D.M.; Wilson, J.A.

    1984-11-01

    On November 19, 1982, the United States Environmental Protection Agency (EPA) promulgated regulations severely restricting chlorination practices as they relate to utility cooling water discharge systems. EPRI authorized the preparation of a manual on dechlorination technology to assist utilities in evaluating the various alternatives available to them to meet these new requirements. The Dechlorination Technology Manual emphasizes the engineering aspects involved in the selection and design of dechlorination systems. However, background information is included concerning chemistry, regulatory requirements, environmental considerations and aquatic impacts. There is also a brief discussion of the various alternatives to dechlorination. Case studies are given to acquaint the user with the use of the manual for the design of chlorination facilities given various site-related characteristics, such as salt versus fresh waters. Numerous graphs and tables are presented to facilitate the selection and design process. 207 references, 66 figures, 60 tables.

  11. Thermoelectric generator cooling system and method of control

    Science.gov (United States)

    Prior, Gregory P; Meisner, Gregory P; Glassford, Daniel B

    2012-10-16

    An apparatus is provided that includes a thermoelectric generator and an exhaust gas system operatively connected to the thermoelectric generator to heat a portion of the thermoelectric generator with exhaust gas flow through the thermoelectric generator. A coolant system is operatively connected to the thermoelectric generator to cool another portion of the thermoelectric generator with coolant flow through the thermoelectric generator. At least one valve is controllable to cause the coolant flow through the thermoelectric generator in a direction that opposes a direction of the exhaust gas flow under a first set of operating conditions and to cause the coolant flow through the thermoelectric generator in the direction of exhaust gas flow under a second set of operating conditions.

  12. Installation and Commissioning of the Resonant Frequency Control Cooling System

    Energy Technology Data Exchange (ETDEWEB)

    Kwon, Hyeokjung; Seol, Kyungtae; Kim, Hansung; Jang, Jiho; Cho, Yongsub [Korea Atomic Energy Research Institute, Daejeon (Korea, Republic of)

    2013-05-15

    Total 11 sets of Resonant Frequency Control Cooling System (RCCS) are used to control the resonance frequency of the 100-MeV DTL. The specifications of the RCCS are summarized. The RCCS should cover the temperature from 21 .deg. C to 33 .deg. C, heat load from magnet power only to full RF power in addition to the magnet power. The stability of the temperature control is less than 0.1 .deg. C. The control input variable comes from the resonance frequency error from the low level RF (LLRF) system. All RCCSs were installed and tested. In this paper, the installation and initial test results of the RCCS are presented. The standalone test of the RCCS for 100-MeV DTL was carried out. The results showed that the chiller temperature fluctuated above the specification mainly because the chiller controller was not properly tuned, but the RCCS with two independent control valves could be operated to give the required stability.

  13. Increasing the Efficiency of a Thermoelectric Generator Using an Evaporative Cooling System

    Science.gov (United States)

    Boonyasri, M.; Jamradloedluk, J.; Lertsatitthanakorn, C.; Therdyothin, A.; Soponronnarit, S.

    2016-11-01

    A system for reducing heat from the cold side of a thermoelectric (TE) power generator, based on the principle of evaporative cooling, is presented. An evaporative cooling system could increase the conversion efficiency of a TE generator. To this end, two sets of TE generators were constructed. Both TE generators were composed of five TE power modules. The cold and hot sides of the TE modules were fixed to rectangular fin heat sinks. The hot side heat sinks were inserted in a hot gas duct. The cold side of one set was cooled by the cooling air from a counter flow evaporative cooling system, whereas the other set was cooled by the parallel flow evaporative cooling system. The counter flow pattern had better performance than the parallel flow pattern. A comparison between the TE generator with and without an evaporative cooling system was made. Experimental results show that the power output increased by using the evaporative cooling system. This can significantly increase the TE conversion efficiency. The evaporative cooling system increased the power output of the TE generator from 22.9 W of ambient air flowing through the heat sinks to 28.6 W at the hot gas temperature of 350°C (an increase of about 24.8%). The present study shows the promising potential of using TE generators with evaporative cooling for waste heat recovery.

  14. Optimization and Model of Laminar Cooling Control System for Hot Strip Mills

    Institute of Scientific and Technical Information of China (English)

    XIE Hai-bo; LIU Xiang-hua; WANG Guo-dong; ZHANG Zhong-ping

    2006-01-01

    The structure of laminar cooling control system for hot rolling was introduced and the control mode, cooling strategy, segment tracking and model recalculation were analyzed. The parameters of air/water cooling models were optimized by regressing the data gathering in situ, and satisfactory effect was obtained. The coiling temperature can be controlled within ±15 ℃.

  15. Optimal design of passive containment cooling system for innovative PWR

    Directory of Open Access Journals (Sweden)

    Huiun Ha

    2017-08-01

    Full Text Available Using the Generation of Thermal-Hydraulic Information for Containments (GOTHIC code, thermal-hydraulic phenomena that occur inside the containment have been investigated, along with the preliminary design of the passive containment cooling system (PCCS of an innovative pressurized water reactor (PWR. A GOTHIC containment model was constructed with reference to the design data of the Advanced Power Reactor 1400, and report related PCCS. The effects of the design parameters were evaluated for passive containment cooling tank (PCCT geometry, PCCS heat exchanger (PCCX location, and surface area. The analyzed results, obtained using the single PCCT, showed that repressurization and reheating phenomena had occurred. To resolve these problems, a coupled PCCT concept was suggested and was found to continually decrease the containment pressure and temperature without repressurization and reheating. If the installation level of the PCCX is higher than that of the PCCT, it may affect the PCCS performance. Additionally, it was confirmed that various means of increasing the external surface area of the PCCX, such as fins, could help improve the energy removal performance of the PCCS. To improve the PCCS design and investigate its performance, further studies are needed.

  16. Chemical treatment of slime in industrial cooling water systems

    Energy Technology Data Exchange (ETDEWEB)

    Sato, Noriyuki

    1987-07-01

    Chemical suppression test was made for slime produced in pipes of the industrial water cooling systems. The 3 month chemical slime treatment test in 1984 proved to be effective, and the test has been carried out since July, 1985. The objective was to suppress the generation of slime by decreasing the number of general bacteria by slime treatment agent (fungicide of chloride group). The number of bacteria in the supplied water was compared for the time and day of the week when samples were collected. It was found that there was no regular rule in the variation of the number of bacteria, with measured result of 30-10/sup 6/ variation range. From the variation in the number of bacteria and the sticking conditions of slime on the test board, it became clear that suppression was possible by drastically decreasing the bacteria number in cooling water in the early stage of chemical supply, followed by resupply of treatment agent in a week when the bacteria would be restored to its original amount by supplied water. However, the method is to suppress the slime generation, and is unable to stop the generation completely. (9 figs, 3 tabs)

  17. High perveance electron gun for the electron cooling system

    CERN Document Server

    Korotaev, Yu V; Petrov, A; Sidorin, A; Smirnov, A; Syresin, E M; Titkova, I

    2000-01-01

    The cooling time in the electron cooling system is inversely proportional to the beam current. To obtain high current of the electron beam the control electrode of the gun is provided with a positive potential and an electrostatic trap for secondary electrons appears inside the electron gun. This leads to a decrease in the gun perveance. To avoid this problem, the adiabatic high perveance electron gun with the clearing control electrode is designed in JINR (J. Bosser, Y. Korotaev, I. Meshkov, E. Syresin et al., Nucl. Instr. and Meth. A 391 (1996) 103. Yu. Korotaev, I. Meshkov, A. Sidorin, A. Smirnov, E. Syresin, The generation of electron beams with perveance of 3-6 mu A/V sup 3 sup / sup 2 , Proceedings of SCHEF'99). The clearing control electrode has a transverse electric field, which clears secondary electrons. Computer simulations of the potential map were made with RELAX3D computer code (C.J. Kost, F.W. Jones, RELAX3D User's Guide and References Manual).

  18. Water and Climate Impacts on Power System Operations: The Importance of Cooling Systems and Demand Response Measures

    Energy Technology Data Exchange (ETDEWEB)

    Macknick, Jordan [National Renewable Energy Lab. (NREL), Golden, CO (United States); Zhou, Ella [National Renewable Energy Lab. (NREL), Golden, CO (United States); O' Connell, Matthew [National Renewable Energy Lab. (NREL), Golden, CO (United States); Brinkman, Gregory [National Renewable Energy Lab. (NREL), Golden, CO (United States); Miara, Ariel [City College of New York, NY (United States); Ibanez, Eduardo [GE Energy Connections, Atlanta, GA (United States); Hummon, Marissa [Tendril, Denver, CO (United States)

    2016-12-01

    The U.S. electricity sector is highly dependent upon water resources; changes in water temperatures and water availability can affect operational costs and the reliability of power systems. Despite the importance of water for power system operations, the effects of changes in water characteristics on multiple generators in a system are generally not modeled. Moreover, demand response measures, which can change the magnitude and timing of loads and can have beneficial impacts on power system operations, have not yet been evaluated in the context of water-related power vulnerabilities. This effort provides a first comprehensive vulnerability and cost analysis of water-related impacts on a modeled power system and the potential for demand response measures to address vulnerability and cost concerns. This study uniquely combines outputs and inputs of a water and power plant system model, production cost, model, and relative capacity value model to look at variations in cooling systems, policy-related thermal curtailments, and demand response measures to characterize costs and vulnerability for a test system. Twenty-five scenarios over the course of one year are considered: a baseline scenario as well as a suite of scenarios to evaluate six cooling system combinations, the inclusion or exclusion of policy-related thermal curtailments, and the inclusion or exclusion of demand response measures. A water and power plant system model is utilized to identify changes in power plant efficiencies resulting from ambient conditions, a production cost model operating at an hourly scale is used to calculate generation technology dispatch and costs, and a relative capacity value model is used to evaluate expected loss of carrying capacity for the test system.

  19. Theoretical analysis of the performance of different cooling strategies with the concept of cool exergy

    DEFF Research Database (Denmark)

    Kazanci, Ongun Berk; Shukuya, Masanori; Olesen, Bjarne W.

    2016-01-01

    The whole chains of exergy flows for different cooling systems were compared. The effects of cooling demand (internal vs. external solar shading), space cooling method (floor cooling vs. air cooling with ventilation system), and the availability of a nearby natural heat sink (intake air for the v......The whole chains of exergy flows for different cooling systems were compared. The effects of cooling demand (internal vs. external solar shading), space cooling method (floor cooling vs. air cooling with ventilation system), and the availability of a nearby natural heat sink (intake air......-water, etc.) and indoor terminal units, only with a minimized demand. The water-based floor cooling system performed better than the air-based cooling system; when an air-to-water heat pump was used as the cooling source, the required exergy input was 28% smaller for the floor cooling system. The auxiliary...... exergy input of air-based systems was significantly larger than the water-based systems. The use of available cool exergy in the crawl-space resulted in 54% and 29% smaller exergy input to the power plant for the air-based and water-based cooling systems, respectively. For floor cooling, the exergy input...

  20. Economic viability of incorporating multi-effect distillation with district cooling systems in the United Arab Emirates

    OpenAIRE

    Hughes, BR; Chaudhry, HN; Rezazadeh, F

    2013-01-01

    The United Arab Emirates (UAE) has one of the most advanced and developed desalination systems in the world, mainly located along the shore. The aim of this study is to analyze the economic feasibility of incorporating the two most prominent types of desalination systems within the existing district cooling plants in the UAE by utilizing waste heat recovery. Mathematical models are established to compare reverse osmosis (RO) with multi-effect distillation (MED) technology coupled with distric...

  1. Planning of a Quadgeneration power plant for Jammerbugt energy system

    DEFF Research Database (Denmark)

    Rudra, Souman; Hoffmann, Jessica; Rosendahl, Lasse

    2011-01-01

    Quadgeneration is the simultaneous production of power, heat and cooling and different fuels from flexible feedstocks such as biomass, waste, refinery residue etc. In order to accommodate more renewable energy into the energy system, it is extremely necessary to develop new flexible power plants...... heating energy technology into a Quadgeneration energy system at Jammerbugt municipality in the north of Denmark in a creative and innovative manner that can reduce CO2 emission and fuel limitations, whilst not compromising security of delivering heat and power to the local resident. So, it is essential...... of some equipments in the Quadgeneration power plant. This paper presents two models for the investment planning of a Quadgeneration energy system in Jammerbugt municipality, and uses these models for different case studies addressing the system for production of heat, cooling, liquid fuels...

  2. Army Gas-Cooled Reactor Systems Program. ML-1 analytical design report. Volume II. Systems analysis: heat transfer and fluid flow

    Energy Technology Data Exchange (ETDEWEB)

    None

    1961-01-01

    The analysis preceding and supporting the design of the cooling system of the ML-1, a mobile, low-power, nuclear power plant, is described in sufficient detail for an engineer to follow the development of the design. Test results and similar data are used to support the calculations whenever possible.

  3. System design package for the solar heating and cooling central data processing system

    Energy Technology Data Exchange (ETDEWEB)

    1978-03-01

    This system design package for the Central Data Processing System consists of the Software Performance Specification, Hardware Performance Specification, Software Verification Plan, CDPS Development Program, Qualification and Acceptance Test Procedures, Qualification Test and Analysis Report, and Qualification and Acceptance Test Review. The Central Data Processing System, located at IBM's Federal System Division facility in Huntsville, Alabama, provides the resources required to assess the performance of solar heating and cooling systems installed at remote sites. These sites consist of residential, commercial, government, and educational types of buildings, and the solar heating and cooling systems can be hot-water, space heating, cooling, and combinations of these. The instrumentation data associated with these systems will vary according to the application and must be collected, processed, and presented in a form which supports continuity of performance evaluation across all applications.

  4. Influence of cooling medium on rat hemostatic system

    Directory of Open Access Journals (Sweden)

    N. A. Lycheva

    2017-01-01

    Full Text Available The purpose of the article is to study the effect of air and water-immersion cooling media on the hemostatic system in the pre-active period of cold trauma.Material and methods. The study was performed on 43 laboratory Wistar rats. Single air hypothermia was modeled by placing animals in individual cells into a cooling chamber at a temperature –25 °С. The animals were in the chamber until the rectal temperature reached 30 °C, which corresponded to a moderate degree of hypothermia in rats. Water immersion hypothermia was modeled by placing animals in individual cells into water with a temperature 5 °C and air 7 °C. The criterion for cessation of exposure was a rectal temperature of 27–30 °C, which also corresponded to a moderate degree of hypothermia. We assessed the state of vascularplatelet and plasma hemostasis, as well as the physiological state of anticoagulant and fibrinolytic systems. The study was performed by using routine techniques and an integral method - thromboelastography.Results. It was established that during water immersion cooling, experimental animals developed thrombocytosis and activated their aggregation function. Laboratory indicators characterizing the initial stages of plasma hemostasis, and external and internal ways of activation did not change at this intensity of hypothermic exposure. At the same time, at the final stage of coagulation, pronounced thrombinemia was recorded, which was confirmed by a significant increase in the concentration of soluble fibrin-monomer complexes and a decrease in the time of their self-assembly. In addition, inhibition of fibrinolytic activity of plasma associated with a decrease in the concentration of antithrombin III was observed. In this case, single air hypothermia, accompanied by the rise in a rectal temperature up to 30 ° C, also caused significant changes in the hemostatic system. Vascular-platelet hemostasis responded to a significant decrease in aggregation activity

  5. Effect of façade systems on the performance of cooling ceilings: In situ measurements

    Directory of Open Access Journals (Sweden)

    Katharina Eder

    2015-03-01

    Full Text Available This article presents an innovative façade system designed to increase the thermal comfort inside an office room and to enhance the cooling capacity of the suspended cooling ceiling. A series of measurements is conducted in an existing office building with different façade systems (i.e., a combination of glazing and shading. An innovative façade system is developed based on this intensive set of measurements. The new system enhances the thermal comfort and cooling capacity of the suspended cooling ceiling. The main usage of the new system is the refurbishment and improvement of existing façade systems.

  6. Simulation and experimental investigation of solar absorption cooling system in Reunion Island

    Energy Technology Data Exchange (ETDEWEB)

    Praene, Jean Philippe; Marc, Olivier; Lucas, Franck; Miranville, Frederic [Physique et Ingenierie Mathematique appliquees a l' Energie et a l' Environnement Laboratory (PIMENT), Universite de la Reunion, Departement Sciences du Batiment et de l' Environnement, 117 Rue du General Ailleret, 97430 Tampon (France)

    2011-03-15

    With the development of technologies and the fast increase of our population we will need to adjust the conventional electrical source to meet the continuous increasing demand. Since the energy cost as well as the environmental awareness is growing fast, technologies using renewable energies appear as an interesting alternative. The aim of this research is to present a solar-driven 30 kW LiBr/H{sub 2}O single-effect absorption cooling system which has been designed and installed at Institut Universitaire Technologique of Saint Pierre. The first part of this article deals with the simulation of the solar thermal plant. A pilot plant has been setup as part of RAFSOL which is a research program managed by the national research agency (ANR). (author)

  7. Photometric Study of the Possible Cool Quadruple System PY Virginis

    Science.gov (United States)

    Zhu, L. Y.; Qian, S. B.; Liu, N. P.; Liu, L.; Jiang, L. Q.

    2013-02-01

    Complete CCD photometric light curves in BV(RI)c bands obtained in 2012 for the short-period close binary system PY Virginis are presented. A new photometric analysis with the Wilson—Van Hamme code shows that PY Vir is an A-type marginal contact binary system. The absolute parameters of PY Vir are derived using spectroscopic and photometric solutions. Combining new determined times of minimum light with others published in the literature, the O - C diagram of the binary star is investigated. A periodic variation, with a period of 5.22(±0.05) years and an amplitude of 0.0075(±0.0004) days, was discovered. Since the spectrum of a third component has been detected by Rucinski et al., we consider this cyclic period oscillation to be the result of the light-time effect due to the presence of a third body. This third component may also be a binary itself. Therefore, PY Vir should be a quadruple system composed of two cool-type binary systems. This system is a good astrophysical laboratory to study the formation and evolution of close binaries and multiple systems.

  8. Effect of Mixed Corrosion Inhibitors in Cooling Water System

    Directory of Open Access Journals (Sweden)

    Dina Raheem

    2011-01-01

    Full Text Available The effect of mixed corrosion inhibitors in cooling system was evaluated by using carbon steel specimens and weight loss analysis. The carbon steel specimens immersed in mixture of sodium phosphate (Na2 HPO4 used as corrosion inhibitor and sodium glocunate (C6 H11 NaO7 as a scale dispersant at different concentrations (20,40, 60, 80 ppm and at different temperature (25,50,75 and 100ºC for (1-5 days. The corrosion inhibitors efficiency was calculated by using uninhibited and inhibited water to give 98.1%. The result of these investigations indicate that the corrosion rate decreases with the increase the corrosion inhibitors concentration at 80 ppm and at 100ºC for 5 days, (i.e, corrosion rate= 0.014gmd.

  9. RF System for the MICE Demonstration of Ionisation Cooling

    Energy Technology Data Exchange (ETDEWEB)

    Ronald, K.; et al.

    2017-04-01

    Muon accelerators offer an attractive option for a range of future particle physics experiments. They can enable high energy (TeV+) high energy lepton colliders whilst mitigating the difficulty of synchrotron losses, and can provide intense beams of neutrinos for fundamental physics experiments investigating the physics of flavor. The method of production of muon beams results in high beam emittance which must be reduced for efficient acceleration. Conventional emittance control schemes take too long, given the very short (2.2 microsecond) rest lifetime of the muon. Ionisation cooling offers a much faster approach to reducing particle emittance, and the international MICE collaboration aims to demonstrate this technique for the first time. This paper will present the MICE RF system and its role in the context of the overall experiment.

  10. R&D on The Cooling Systems Using Natural Refrigerants

    Science.gov (United States)

    Yanagi, Hideharu

    The use of waste heat of low temperatures is an important problem from the environmental considerations. Notice that adsorption cycles have a distinct advantage over other systems of their ability to produce cooling by using low waste heat as 60 to 80°C and also being absolutely benign for the environment. However the present available adsorption chillers are still heavier and larger in size. Hence their compactness and cost reduction as well as higher efficiency are urgent tasks for wider use. This review discusses recent development on adsorption heat pumps as well as forthcoming applications. The sources are mainly papers and discussions at the IEA Annex 24 Workshop in Turin, Italy (1999), FOA6 (Fundamental of Adsorption) Conference in Presquile de Giens, France (1998) and ISHPC (International Sorption Heat Pump Conference) in Munich, Germany (1999).

  11. Numerical Study of the Effect of a Power Plant Cooling Water Discharge in the Montevideo Bay

    Directory of Open Access Journals (Sweden)

    Mónica Fossati

    2011-01-01

    Full Text Available The numerical simulation of the water temperature in the Río de la Plata River and Montevideo's Bay was done using the numerical model of finite elements RMA-10 in its 2D vertical integrated mode. Parameters involved in the formulations of thermal exchange with the atmosphere were adjusted using measurements of water temperature in several locations of the water body. After calibrating the model, it was used to represent the operation of a power plant located in Montevideo's Bay. This central takes water from the bay in order to cool its generators and also discharges high-temperature water into the bay. The correct representation of temperatures at the water intake and discharge of the plant reflects that the model is able to represent the operation of the central. Several analysis were made to study the thermal plume, the effects of the water discharge on the water intake of the power plant, and the effect on environmental variables of the study area like currents.

  12. CFD Analysis of the Primary Cooling System for the Small Modular Natural Circulation Lead Cooled Fast Reactor SNRLFR-100

    OpenAIRE

    Pengcheng Zhao; Kangli Shi; Shuzhou Li; Jingchao Feng; Hongli Chen

    2016-01-01

    Small modular reactor (SMR) has drawn wide attention in the past decades, and Lead cooled fast reactor (LFR) is one of the most promising advanced reactors which are able to meet the safety economic goals of Gen-IV nuclear energy systems. A small modular natural circulation lead cooled fast reactor-100 MWth (SNRLFR-100) is being developed by University of Science and Technology of China (USTC). In the present work, a 3D CFD model, primary heat exchanger model, fuel pin model, and point kineti...

  13. Ground Source Geothermal District Heating and Cooling System

    Energy Technology Data Exchange (ETDEWEB)

    Lowe, James William [Ball State Univ., Muncie, IN (United States)

    2016-10-21

    Ball State University converted its campus from a coal-fired steam boiler district heating system to a ground source heat pump geothermal district system that produces simultaneously hot water for heating and chilled water for cooling. This system will include the installation of 3,600 four hundred feet deep vertical closed loop boreholes making it the largest ground source geothermal district system in the country. The boreholes will act as heat exchangers and transfer heat by virtue of the earth’s ability to maintain an average temperature of 55 degree Fahrenheit. With growing international concern for global warming and the need to reduce worldwide carbon dioxide loading of the atmosphere geothermal is poised to provide the means to help reduce carbon dioxide emissions. The shift from burning coal to utilizing ground source geothermal will increase electrical consumption but an overall decrease in energy use and reduction in carbon dioxide output will be achieved. This achievement is a result of coupling the ground source geothermal boreholes with large heat pump chiller technology. The system provides the thermodynamic means to move large amounts of energy with limited energy input. Ball State University: http://cms.bsu.edu/About/Geothermal.aspx

  14. Optimization of a solar cooling system with interior energy storage

    Energy Technology Data Exchange (ETDEWEB)

    Sanjuan, C.; Soutullo, S.; Heras, M.R. [Department of Energy, Energy Efficiency in Buildings Unit, CIEMAT, Madrid E-28040 (Spain)

    2010-07-15

    This paper focuses on the optimization of the performance of a solar absorption cooling system composed by four units with interior energy storage. A full dynamic simulation model that includes the solar collector field, the absorption heat pump system and the building load calculation has been developed. It has been applied to optimize the coupling of a system based on this new technology of solar powered absorption heat pump, to a bioclimatic building recently constructed in the Plataforma Solar de Almeria (PSA) in Spain. The absorption heat pump system considered is composed by four heat pumps that store energy in the form of crystallized salts so that no external storage capacity is required. Each heat pump is composed of two separate barrels that can charge (store energy from the solar field) and discharge (deliver heat or cold to the building) independently. Different configurations of the four units have been analysed taking into account the storage possibilities of the system and its capacity to respond to the building loads. It has been shown how strong the influence of the control strategies in the overall performance is, and the importance of using hourly simulations models when looking for highly efficient buildings. (author)

  15. Cryogenic cooling with cryocooler on a rotating system.

    Science.gov (United States)

    Oguri, S; Choi, J; Kawai, M; Tajima, O

    2013-05-01

    We developed a system that continuously maintains a cryocooler for long periods on a rotating table. A cryostat that holds the cryocooler is set on the table. A compressor is located on the ground and supplies high-purity (>99.999%) and high-pressure (1.7 MPa) helium gas and electricity to the cryocooler. The operation of the cryocooler and other instruments requires the development of interface components between the ground and rotating table. A combination of access holes at the center of the table and two rotary joints allows simultaneous circulation of electricity and helium gas. The developed system provides two innovative functions under the rotating condition, cooling from room temperature and the maintenance of a cold condition for long periods. We have confirmed these abilities as well as temperature stability under a condition of continuous rotation at 20 rpm. The developed system can be applied in various fields, e.g., in tests of Lorentz invariance, searches for axion, radio astronomy, and cosmology, and application of radar systems. In particular, there is a plan to use this system for a radio telescope observing cosmic microwave background radiation.

  16. Cryogenic cooling with cryocooler on a rotating system

    Science.gov (United States)

    Oguri, S.; Choi, J.; Kawai, M.; Tajima, O.

    2013-05-01

    We developed a system that continuously maintains a cryocooler for long periods on a rotating table. A cryostat that holds the cryocooler is set on the table. A compressor is located on the ground and supplies high-purity (>99.999%) and high-pressure (1.7 MPa) helium gas and electricity to the cryocooler. The operation of the cryocooler and other instruments requires the development of interface components between the ground and rotating table. A combination of access holes at the center of the table and two rotary joints allows simultaneous circulation of electricity and helium gas. The developed system provides two innovative functions under the rotating condition, cooling from room temperature and the maintenance of a cold condition for long periods. We have confirmed these abilities as well as temperature stability under a condition of continuous rotation at 20 rpm. The developed system can be applied in various fields, e.g., in tests of Lorentz invariance, searches for axion, radio astronomy, and cosmology, and application of radar systems. In particular, there is a plan to use this system for a radio telescope observing cosmic microwave background radiation.

  17. Experimental study and modeling of cooling ceiling systems using steady-state analysis

    Energy Technology Data Exchange (ETDEWEB)

    Fonseca Diaz, Nestor [Thermodynamic Laboratory, University of Liege Belgium, Campus du Sart Tilman, Bat: B49 - P33, B-4000 Liege (Belgium); Universidad Tecnologica de Pereira, Facultad de Ingenieria Mecuanica, AA. 97 Pereira (Colombia); Lebrun, Jean [Thermodynamic Laboratory, University of Liege Belgium, Campus du Sart Tilman, Bat: B49 - P33, B-4000 Liege (Belgium); Andre, Philippe [Departement Sciences et Gestion de l' Environnement, University of Liege Belgium, 185, Avenue de Longwy, B-6700 Arlon (Belgium)

    2010-06-15

    This article presents the results of an experimental study performed to develop a computational model of cooling ceiling systems. The model considers the cooling ceiling as a fin. Only the dry regime is considered. From ceiling and room dimensions, material description of the cooling ceiling and measurement of supply water mass flow rate and air and water temperatures, the model calculates the cooling ceiling capacity, ceiling surface average temperature and water exhaust temperature. Fin efficiency, mixed convection close to the cooling ceiling (generated by the ventilation system) and panel perforations influence are studied. The theoretical approach gives to the user an appropriate tool for preliminary calculation, design and diagnosis in commissioning processes in order to determine the main operating conditions of the system in cooling mode. A series of experimental results got on four types of cooling ceilings are used in order to validate the model. (author)

  18. Stochastic Cooling

    Energy Technology Data Exchange (ETDEWEB)

    Blaskiewicz, M.

    2011-01-01

    Stochastic Cooling was invented by Simon van der Meer and was demonstrated at the CERN ISR and ICE (Initial Cooling Experiment). Operational systems were developed at Fermilab and CERN. A complete theory of cooling of unbunched beams was developed, and was applied at CERN and Fermilab. Several new and existing rings employ coasting beam cooling. Bunched beam cooling was demonstrated in ICE and has been observed in several rings designed for coasting beam cooling. High energy bunched beams have proven more difficult. Signal suppression was achieved in the Tevatron, though operational cooling was not pursued at Fermilab. Longitudinal cooling was achieved in the RHIC collider. More recently a vertical cooling system in RHIC cooled both transverse dimensions via betatron coupling.

  19. Overview of Cooling Water System for the KSTAR 1{sup st} Plasma Experiment

    Energy Technology Data Exchange (ETDEWEB)

    Kim, Y. J.; Kim, S. T.; Im, D. S.; Joung, N. Y.; Kim, Y. S. [National Fusion Research Institute, Daejeon (Korea, Republic of)

    2009-05-15

    The KSTAR cooling water system (CWS) consists of a primary cooling water system (PCWS), a secondary cooling water system (SCWS), and a de-mineralizing and de-ionized water system (DIWS). The PCWS cooling loops have been made for the poloidal field (PF) and toroidal field (TF) magnet power supplies (MPS), vacuum vessel (VV), electron cyclotron heating (ECH), ion cyclotron heating (ICRH), vacuum pumps, diagnostics, helium facility, etc. The CWS had been done individual commissioning of each system to confirm the design specifications by the end of 2006 and had gradually begun operation for the KSTAR ancillary devices by March 2008.

  20. Consideration of sub-cooled LN2 circulation system for HTS power machines

    Science.gov (United States)

    Yoshida, Shigeru; Hirai, Hirokazu; Nara, N.; Nagasaka, T.; Hirokawa, M.; Okamoto, H.; Hayashi, H.; Shiohara, Y.

    2012-06-01

    We consider a sub-cooled liquid nitrogen (LN) circulation system for HTS power equipment. The planned circulation system consists of a sub-cool heat exchanger (subcooler) and a circulation pump. The sub-cooler will be connected to a neon turbo- Brayton cycle refrigerator with a cooling power of 2 kW at 65 K. Sub-cooled LN will be delivered into the sub-cooler by the pump and cooled within it. Sub-cooled LN is adequate fluid for cooling HTS power equipment, because its dielectric strength is high and it supports a large critical current. However, a possibility of LN solidification in the sub-cooler is a considerable issue. The refrigerator will produce cold neon gas of about 60 K, which is lower than the nitrogen freezing temperature of 63 K. Therefore, we designed two-stage heat exchangers which are based on a plate-fin type and a tube-intube type. Process simulations of those heat exchangers indicate that sub-cooled LN is not frozen in either sub-cooler. The plate-fin type sub-cooler is consequently adopted for its reliability and compactness. Furthermore, we found that a cooling system with a Brayton refrigerator has the same total cooling efficiency as a cooling system with a Stirling refrigerator.

  1. Energy gain from cooling circuits in underground plants. Energiegewinnung aus Kuehlkreislaeufen in Tiefbergbauanlagen

    Energy Technology Data Exchange (ETDEWEB)

    Hoelter, H.; Igelbuescher, H.; Gresch, H.; Dewert, H.; Kneissl, H.; Nasser, G.

    1988-03-03

    The energetic use of the heat contents of pit water is a well-known method. To further develop this idea, the invention proposes to use the heat that is generated when cooling the air in the heat exchangers. This is done in such a way that the pit heat is cooled decentrally by means of heat exchangers. The coolant is transported through the liquid up to the proximity of the shaft and is exchanged there again in order to convert the carrier medium into gaseous form so as to make it available with its own buoyancy for several days for operating a liquid turbine by a a re-exchange of the liquid for a generation of the energy of fall. As a result, considerable energy conservation is achieved by re-exchanging the exchanged heat being generated in the underground cooling system in an underground circuit again and by transporting it to the surface through a vapourized carrier medium without additional energy requirements.

  2. 大容量机组空冷支架结构抗震设计方法研究%STUDY OF THE SEISMIC DESIGN METHOD OF AIR COOLED CONDENSER SUPPORT STRUCTURE SYSTEM IN HIGH-CAPACITY THERMAL POWER PLANT

    Institute of Scientific and Technical Information of China (English)

    刘林; 白国良; 薛群虎; 代慧娟

    2014-01-01

    大容量机组空冷支架结构属质量和刚度沿竖向分布不均匀的竖向混合结构,结构的扭转效应明显,地震作用复杂。大直径钢筋混凝土薄壁管柱为结构的主要抗侧力构件和耗能构件,结构抗震防线过于单一。强烈地震作用下,混凝土管柱底部及柱顶钢桁架连接部位为抗震设计的关键部位。目前,对大容量机组空冷支架结构抗震设计缺乏系统研究,国家相关规范对这方面内容很少涉及。为了确保空冷支架结构的安全,在模型抗震性能试验和大直径薄壁管柱承载力试验的基础上,提出了大容量机组空冷支架结构抗震设计方法和抗震构造措施。%Support structure of air cooled condenser is a typical vertical hybrid structure whose stiffness and mass are non-uniform at vertical direction; torsion effect of the structure is obvious , earthquake response of the structure is complex.Research results show that the large-diameter and thin-walled reinforced concrete pipe columns are main lateral force resisting members in the structure , the damage of the structure is mainly concentrated on the bottom of the columns, structure’s earthquake resistance fortification is simplex .For lacking of systematic study on the seismic design method of this kind of structure , and little of its design cortents is involved in the national standards .In order to guarantee the safety of the support structure and equipment under earthquake action , based on the seismic behavior test of model structure and bearing capacity test of large-diameter and thin-walled reinforced concrete pipe columns , seismic design method and seismic measure are put forward to design support structure of air cooled condenser .

  3. Application of Heat Pump in Cooling Water System of HIRFL

    Institute of Scientific and Technical Information of China (English)

    2001-01-01

    Accelerator generates a lot of heat when it is working.It must be cooled by the circulating cooling water.Generally the heat was released to atimosphere by the cooling water tower.Because the heat energy is very huge(about 2M watts for HIRFL),it is big waste and the machine can’t be cooled to appropriate temperature when ambient temperature is high in summer.In order to solve the problems,the heat pump has been used

  4. Open absorption system for cooling and air conditioning using membrane contactors. 2006 annual report

    Energy Technology Data Exchange (ETDEWEB)

    Conde-Petit, M. [M. Conde Engineering, Zuerich (Switzerland); Weber, R. [Materials Science and Technology (EMPA), Abteilung Bautechnologien, Duebendorf (Switzerland)

    2006-11-15

    This illustrated annual report for 2006 for the Swiss Federal Office of Energy (SFOE) reports on work being done on the development of an open absorption system for cooling and air-conditioning. The report reviews the construction of a first prototype and the manufacture of its components. The conceptual design of this new type of air handling unit (AHU), operating with a liquid desiccant, is discussed. The AHU is to be autonomous and the system will not require additional mechanical refrigeration. It is to be thermally driven at temperatures below 80 {sup o}C. Waste heat sources, solar collectors, district heating plants and co-generation systems are targeted as providers of thermal energy at this temperature level. Work carried out is reported on, including that on two-stream membrane contactors.

  5. The performance of a temperature cascaded cogeneration system producing steam, cooling and dehumidification

    KAUST Repository

    Myat, Aung

    2013-02-01

    This paper discusses the performance of a temperature-cascaded cogeneration plant (TCCP), equipped with an efficient waste heat recovery system. The TCCP, also called a cogeneration system, produces four types of useful energy-namely, (i) electricity, (ii) steam, (iii) cooling and (iv) dehumidification-by utilizing single fuel source. The TCCP comprises a Capstone C-30 micro-turbine that generates nominal capacity of 26 kW of electricity, a compact and efficient waste heat recovery system and a host of waste-heat-activated devices, namely (i) a steam generator, (ii) an absorption chiller, (iii) an adsorption chiller and (iv) a multi-bed desiccant dehumidifier. The performance analysis was conducted under different operation conditions such as different exhaust gas temperatures. It was observed that energy utilization factor could be as high as 70% while fuel energy saving ratio was found to be 28%. © 2013 Desalination Publications.

  6. Chapter 15. Plant pathology and managing wildland plant disease systems

    Science.gov (United States)

    David L. Nelson

    2004-01-01

    Obtaining specific, reliable knowledge on plant diseases is essential in wildland shrub resource management. However, plant disease is one of the most neglected areas of wildland resources experimental research. This section is a discussion of plant pathology and how to use it in managing plant disease systems.

  7. Development of Natural Gas Fired Combined Cycle Plant for Tri-Generation of Power, Cooling and Clean Water Using Waste Heat Recovery: Techno-Economic Analysis

    Directory of Open Access Journals (Sweden)

    Gowtham Mohan

    2014-10-01

    Full Text Available Tri-generation is one of the most efficient ways for maximizing the utilization of available energy. Utilization of waste heat (flue gases liberated by the Al-Hamra gas turbine power plant is analyzed in this research work for simultaneous production of: (a electricity by combining steam rankine cycle using heat recovery steam generator (HRSG; (b clean water by air gap membrane distillation (AGMD plant; and (c cooling by single stage vapor absorption chiller (VAC. The flue gases liberated from the gas turbine power cycle is the prime source of energy for the tri-generation system. The heat recovered from condenser of steam cycle and excess heat available at the flue gases are utilized to drive cooling and desalination cycles which are optimized based on the cooling energy demands of the villas. Economic and environmental benefits of the tri-generation system in terms of cost savings and reduction in carbon emissions were analyzed. Energy efficiency of about 82%–85% is achieved by the tri-generation system compared to 50%–52% for combined cycles. Normalized carbon dioxide emission per MW·h is reduced by 51.5% by implementation of waste heat recovery tri-generation system. The tri-generation system has a payback period of 1.38 years with cumulative net present value of $66 million over the project life time.

  8. Design considerations and experimental observations for the TAMU air-cooled reactor cavity cooling system for the VHTR

    Science.gov (United States)

    Sulaiman, S. A.; Dominguez-Ontiveros, E. E.; Alhashimi, T.; Budd, J. L.; Matos, M. D.; Hassan, Y. A.

    2015-04-01

    The Reactor Cavity Cooling System (RCCS) is a promising passive decay heat removal system for the Very High Temperature Reactor (VHTR) to ensure reliability of the transfer of the core residual and decay heat to the environment under all off-normal circumstances. A small scale experimental test facility was constructed at Texas A&M University (TAMU) to study pertinent multifaceted thermal hydraulic phenomena in the air-cooled reactor cavity cooling system (RCCS) design based on the General Atomics (GA) concept for the Modular High Temperature Gas-Cooled Reactor (MHTGR). The TAMU Air-Cooled Experimental Test Facility is ⅛ scale from the proposed GA-MHTGR design. Groundwork for experimental investigations focusing into the complex turbulence mixing flow behavior inside the upper plenum is currently underway. The following paper illustrates some of the chief design considerations used in construction of the experimental test facility, complete with an outline of the planned instrumentation and data acquisition methods. Computational Fluid Dynamics (CFD) simulations were carried out to furnish some insights on the overall behavior of the air flow in the system. CFD simulations assisted the placement of the flow measurement sensors location. Preliminary experimental observations of experiments at 120oC inlet temperature suggested the presence of flow reversal for cases involving single active riser at both 5 m/s and 2.25 m/s, respectively and four active risers at 2.25 m/s. Flow reversal may lead to thermal stratification inside the upper plenum by means of steady state temperature measurements. A Particle Image Velocimetry (PIV) experiment was carried out to furnish some insight on flow patterns and directions.

  9. Design considerations and experimental observations for the TAMU air-cooled reactor cavity cooling system for the VHTR

    Energy Technology Data Exchange (ETDEWEB)

    Sulaiman, S. A., E-mail: shamsulamri@tamu.edu; Dominguez-Ontiveros, E. E., E-mail: elvisdom@tamu.edu; Alhashimi, T., E-mail: jbudd123@tamu.edu; Budd, J. L., E-mail: dubaiboy@tamu.edu; Matos, M. D., E-mail: mailgoeshere@gmail.com; Hassan, Y. A., E-mail: yhasssan@tamu.edu [Department of Nuclear Engineering, Texas A and M University, College Station, TX, 77843-3133 (United States)

    2015-04-29

    The Reactor Cavity Cooling System (RCCS) is a promising passive decay heat removal system for the Very High Temperature Reactor (VHTR) to ensure reliability of the transfer of the core residual and decay heat to the environment under all off-normal circumstances. A small scale experimental test facility was constructed at Texas A and M University (TAMU) to study pertinent multifaceted thermal hydraulic phenomena in the air-cooled reactor cavity cooling system (RCCS) design based on the General Atomics (GA) concept for the Modular High Temperature Gas-Cooled Reactor (MHTGR). The TAMU Air-Cooled Experimental Test Facility is ⅛ scale from the proposed GA-MHTGR design. Groundwork for experimental investigations focusing into the complex turbulence mixing flow behavior inside the upper plenum is currently underway. The following paper illustrates some of the chief design considerations used in construction of the experimental test facility, complete with an outline of the planned instrumentation and data acquisition methods. Computational Fluid Dynamics (CFD) simulations were carried out to furnish some insights on the overall behavior of the air flow in the system. CFD simulations assisted the placement of the flow measurement sensors location. Preliminary experimental observations of experiments at 120oC inlet temperature suggested the presence of flow reversal for cases involving single active riser at both 5 m/s and 2.25 m/s, respectively and four active risers at 2.25 m/s. Flow reversal may lead to thermal stratification inside the upper plenum by means of steady state temperature measurements. A Particle Image Velocimetry (PIV) experiment was carried out to furnish some insight on flow patterns and directions.

  10. Conceptual design of advanced central receiver power systems sodium-cooled receiver concept. Volume 2, Book 2. Appendices. Final report

    Energy Technology Data Exchange (ETDEWEB)

    1979-03-01

    The appendices include: (A) design data sheets and P and I drawing for 100-MWe commercial plant design, for all-sodium storage concept; (B) design data sheets and P and I drawing for 100-MWe commercial plant design, for air-rock bed storage concept; (C) electric power generating water-steam system P and I drawing and equipment list, 100-MWe commercial plant design; (D) design data sheets and P and I drawing for 281-MWe commercial plant design; (E) steam generator system conceptual design; (F) heat losses from solar receiver surface; (G) heat transfer and pressure drop for rock bed thermal storage; (H) a comparison of alternative ways of recovering the hydraulic head from the advanced solar receiver tower; (I) central receiver tower study; (J) a comparison of mechanical and electromagnetic sodium pumps; (K) pipe routing study of sodium downcomer; and (L) sodium-cooled advanced central receiver system simulation model. (WHK)

  11. Cooling system having reduced mass pin fins for components in a gas turbine engine

    Science.gov (United States)

    Lee, Ching-Pang; Jiang, Nan; Marra, John J

    2014-03-11

    A cooling system having one or more pin fins with reduced mass for a gas turbine engine is disclosed. The cooling system may include one or more first surfaces defining at least a portion of the cooling system. The pin fin may extend from the surface defining the cooling system and may have a noncircular cross-section taken generally parallel to the surface and at least part of an outer surface of the cross-section forms at least a quartercircle. A downstream side of the pin fin may have a cavity to reduce mass, thereby creating a more efficient turbine airfoil.

  12. Influence of Chlorination and Choice of Materials on Fouling in Cooling Water System under Brackish Seawater Conditions

    Directory of Open Access Journals (Sweden)

    Pauliina Rajala

    2016-06-01

    Full Text Available Cooling systems remove heat from components and industrial equipment. Water cooling, employing natural waters, is typically used for cooling large industrial facilities, such as power plants, factories or refineries. Due to moderate temperatures, cooling water cycles are susceptible to biofouling, inorganic fouling and scaling, which may reduce heat transfer and enhance corrosion. Hypochlorite treatment or antifouling coatings are used to prevent biological fouling in these systems. In this research, we examine biofouling and materials’ degradation in a brackish seawater environment using a range of test materials, both uncoated and coated. The fouling and corrosion resistance of titanium alloy (Ti-6Al-4V, super austenitic stainless steel (254SMO and epoxy-coated carbon steel (Intershield Inerta160 were studied in the absence and presence of hypochlorite. Our results demonstrate that biological fouling is intensive in cooling systems using brackish seawater in sub-arctic areas. The microfouling comprised a vast diversity of bacteria, archaea, fungi, algae and protozoa. Chlorination was effective against biological fouling: up to a 10–1000-fold decrease in bacterial and archaeal numbers was detected. Chlorination also changed the diversity of the biofilm-forming community. Nevertheless, our results also suggest that chlorination enhances cracking of the epoxy coating.

  13. Economic analysis of wind-powered refrigeration cooling/water-heating systems in food processing. Final report

    Energy Technology Data Exchange (ETDEWEB)

    Garling, W.S.; Harper, M.R.; Merchant-Geuder, L.; Welch, M.

    1980-03-01

    Potential applications of wind energy include not only large central turbines that can be utilized by utilities, but also dispersed systems for farms and other applications. The US Departments of Energy (DOE) and Agriculture (USDA) currently are establishing the feasibility of wind energy use in applications where the energy can be used as available, or stored in a simple form. These applications include production of hot water for rural sanitation, heating and cooling of rural structures and products, drying agricultural products, and irrigation. This study, funded by USDA, analyzed the economic feasibility of wind power in refrigeration cooling and water heating systems in food processing plants. Types of plants included were meat and poultry, dairy, fruit and vegetable, and aquaculture.

  14. Fast cooling for a system of stochastic oscillators

    Energy Technology Data Exchange (ETDEWEB)

    Chen, Yongxin, E-mail: chen2468@umn.edu; Georgiou, Tryphon T., E-mail: tryphon@umn.edu [Department of Electrical and Computer Engineering, University of Minnesota, 200 Union Street S.E., Minneapolis, Minnesota 55455 (United States); Pavon, Michele, E-mail: pavon@math.unipd.it [Dipartimento di Matematica, Università di Padova, Via Trieste 63, 35121 Padova (Italy)

    2015-11-15

    We study feedback control of coupled nonlinear stochastic oscillators in a force field. We first consider the problem of asymptotically driving the system to a desired steady state corresponding to reduced thermal noise. Among the feedback controls achieving the desired asymptotic transfer, we find that the most efficient one from an energy point of view is characterized by time-reversibility. We also extend the theory of Schrödinger bridges to this model, thereby steering the system in finite time and with minimum effort to a target steady-state distribution. The system can then be maintained in this state through the optimal steady-state feedback control. The solution, in the finite-horizon case, involves a space-time harmonic function φ, and −logφ plays the role of an artificial, time-varying potential in which the desired evolution occurs. This framework appears extremely general and flexible and can be viewed as a considerable generalization of existing active control strategies such as macromolecular cooling. In the case of a quadratic potential, the results assume a form particularly attractive from the algorithmic viewpoint as the optimal control can be computed via deterministic matricial differential equations. An example involving inertial particles illustrates both transient and steady state optimal feedback control.

  15. Cryogenic cooling with cryocooler on a rotating system

    CERN Document Server

    Oguri, Shugo; Kawai, Masanori; Tajima, Osamu

    2013-01-01

    We developed a system that continuously maintains a cryocooler for long periods on a rotating table. A cryostat that holds the cryocooler is set on the table. A compressor is located on the ground and supplies high-purity (> 99.999%) and high-pressure (1.7 MPa) helium gas and electricity to the cryocooler. The operation of the cryocooler and other instruments requires the development of interface components between the ground and rotating table. A combination of access holes at the center of the table and two rotary joints allows simultaneous circulation of electricity and helium gas. The developed system provides two innovative functions under the rotating condition; cooling from room temperature and the maintenance of a cold condition for long periods. We have confirmed these abilities as well as temperature stability under a condition of continuous rotation at 20 revolutions per minute. The developed system can be applied in various fields; e.g., in tests of Lorentz invariance, searches for axion, radio as...

  16. Fast cooling for a system of stochastic oscillators

    Science.gov (United States)

    Chen, Yongxin; Georgiou, Tryphon T.; Pavon, Michele

    2015-11-01

    We study feedback control of coupled nonlinear stochastic oscillators in a force field. We first consider the problem of asymptotically driving the system to a desired steady state corresponding to reduced thermal noise. Among the feedback controls achieving the desired asymptotic transfer, we find that the most efficient one from an energy point of view is characterized by time-reversibility. We also extend the theory of Schrödinger bridges to this model, thereby steering the system in finite time and with minimum effort to a target steady-state distribution. The system can then be maintained in this state through the optimal steady-state feedback control. The solution, in the finite-horizon case, involves a space-time harmonic function φ, and -logφ plays the role of an artificial, time-varying potential in which the desired evolution occurs. This framework appears extremely general and flexible and can be viewed as a considerable generalization of existing active control strategies such as macromolecular cooling. In the case of a quadratic potential, the results assume a form particularly attractive from the algorithmic viewpoint as the optimal control can be computed via deterministic matricial differential equations. An example involving inertial particles illustrates both transient and steady state optimal feedback control.

  17. A passive decay-heat removal system for an ABWR based on air cooling

    Energy Technology Data Exchange (ETDEWEB)

    Mochizuki, Hiroyasu, E-mail: mochizki@u-fukui.ac.jp [Research Institute of Nuclear Engineering, University of Fukui, 1-2-4 Kanawa-cho, Tsuruga, Fukui 914-0055 (Japan); Yano, Takahiro [School of Engineering, University of Fukui, 1-2-4 Kanawa-cho, Tsuruga, Fukui 914-0055 (Japan)

    2017-01-15

    Highlights: • A passive decay heat removal system for an ABWR is discussed using combined system of the reactor and an air cooler. • Effect of number of pass of the finned heat transfer tubes on heat removal is investigated. • The decay heat can be removed by air coolers with natural convection. • Two types of air cooler are evaluated, i.e., steam condensing and water cooling types. • Measures how to improve the heat removal rate and to make compact air cooler are discussed. - Abstract: This paper describes the capability of an air cooling system (ACS) operated under natural convection conditions to remove decay heat from the core of an Advanced Boiling Water Reactor (ABWR). The motivation of the present research is the Fukushima Severe Accident (SA). The plant suffered damages due to the tsunami and entered a state of Station Blackout (SBO) during which seawater cooling was not available. To prevent this kind of situation, we proposed a passive decay heat removal system (DHRS) in the previous study. The plant behavior during the SBO was calculated using the system code NETFLOW++ assuming an ABWR with the ACS. However, decay heat removal under an air natural convection was difficult. In the present study, a countermeasure to increase heat removal rate is proposed and plant transients with the ACS are calculated under natural convection conditions. The key issue is decreasing pressure drop over the tube banks in order to increase air flow rate. The results of the calculations indicate that the decay heat can be removed by the air natural convection after safety relief valves are actuated many times during a day. Duct height and heat transfer tube arrangement of the AC are discussed in order to design a compact and efficient AC for the natural convection mode. As a result, a 4-pass heat transfer tubes with 2-row staggered arrangement is the candidate of the AC for the DHRS under the air natural convection conditions. The heat removal rate is re-evaluated as

  18. ESM Calculations for Hydroponic Plant and Fungi Growth Chambers, Biosolids Dewatering Plant System, and Tilapia Growth System--EAC Presentation 2004

    OpenAIRE

    Aydogan, Selen; Blau, Gary; Pekny, Joseph; Reklaitis, Gintaras

    2004-01-01

    In this work, preliminary Equivalent System Mass (ESM) estimations of the Hydroponic Plant and Fungi Growth Chambers, Biosolids Dewatering Plant and Tilapia Growth Systems are presented. ESM may be used to evaluate a system or technology based on its mass, volume, power, cooling and manpower requirements. This ESM analysis focuses on a hypothetical device, instead of the anticipated technology that is system flight proven in mission operations. We have examined the Evolved Mars Base mission, ...

  19. Air cooled turbine component having an internal filtration system

    Science.gov (United States)

    Beeck, Alexander R [Orlando, FL

    2012-05-15

    A centrifugal particle separator is provided for removing particles such as microscopic dirt or dust particles from the compressed cooling air prior to reaching and cooling the turbine blades or turbine vanes of a turbine engine. The centrifugal particle separator structure has a substantially cylindrical body with an inlet arranged on a periphery of the substantially cylindrical body. Cooling air enters centrifugal particle separator through the separator inlet port having a linear velocity. When the cooling air impinges the substantially cylindrical body, the linear velocity is transformed into a rotational velocity, separating microscopic particles from the cooling air. Microscopic dust particles exit the centrifugal particle separator through a conical outlet and returned to a working medium.

  20. Evaluating two different evaporative cooling management systems for dairy cows in a hot, dry climate.

    Science.gov (United States)

    Ryan, D P; Boland, M P; Kopel, E; Armstrong, D; Munyakazi, L; Godke, R A; Ingraham, R H

    1992-04-01

    Milk production, rectal temperature, live weight gain, reproductive performance, and weather data were obtained on 150 Holstein cows managed under two cooling systems on a large dairy farm in Saudi Arabia during the summer months. Cows were paired at the onset of the trial according to days postpartum, lactation number, and current milk production. Females were then allocated either to a system that forced air, precooled by evaporative cooling, over the cows or to a system that alternately showered a fine mist onto the surface of the cows and then forced air at ambient temperature over them. The cows receiving evaporative cooling and those with spray and fan cooling were on sand and on slatted concrete floor, respectively, during the periods of cooling. The onset of estrus was observed during the night when the cows preferred the unshaded corral. For the 120-d trial period, 84% (62 of 75) of the cows receiving evaporative cooling and 60% (44 of 75) of the cows receiving spray and fan cooling became pregnant. In the evaporative cooling system, the pregnancy rate per insemination was 35.2% (179 inseminations) versus 23.2% (194 inseminations) for spray and fan cooling. The mean postpartum interval to pregnancy was 117.6 d for the evaporative cooling cows and 146.7 d for spray and fan cooling cows. The evaporative cooling system, with its open shades and sand bedding, enhanced reproductive performance and milk production compared with that of cows cooled with a spray and fan system with slatted flooring in this hot climate.

  1. Conceptual design of a passive moderator cooling system for a pressure tube type natural circulation boiling water cooled reactor

    Energy Technology Data Exchange (ETDEWEB)

    Kumar, Mukesh [Reactor Engineering Division, Bhabha Atomic Research Centre, Trombay, Mumbai 400 085 (India); Pal, Eshita, E-mail: eshi.pal@gmail.com [Homi Bhabha National Institute, Anushaktinagar, Mumbai 400 094 (India); Nayak, Arun K.; Vijayan, Pallipattu K. [Reactor Engineering Division, Bhabha Atomic Research Centre, Trombay, Mumbai 400 085 (India)

    2015-09-15

    Highlights: • Passive moderator cooling system is designed to cool moderator passively during SBO. • PMCS is a system of two natural circulation loops, coupled via a heat exchanger. • RELAP5 analyses show that PMCS maintains moderator within safe limits for 7 days. - Abstract: The recent Fukushima accident has raised strong concern and apprehensions about the safety of reactors in case of a prolonged Station Black Out (SBO) continuing for several days. In view of this, a detailed study was performed simulating this condition in Advanced Heavy Water Reactor. In this study, a novel concept of moderator cooling by passive means has been introduced in the reactor design. The Passive Moderator Cooling System (PMCS) consists of a shell and tube heat exchanger designed to remove 2 MW heat from the moderator inside Calandria. The heat exchanger is located at a suitable elevation from the Calandria of the reactor, such that the hot moderator rises due to buoyancy into the heat exchanger and upon cooling from shell side water returns to Calandria forming a natural circulation loop. The shell side of the heat exchanger is also a natural circulation loop connected to an overhead large water reservoir, namely the GDWP. The objective of the PMCS is to remove the heat from the moderator in case of an SBO and maintaining its temperature below the permissible safe limit (100 °C) for at least 7 days. The paper first describes the concept of the PMCS. The concept has been assessed considering a prolonged SBO for at least 7 days, through an integrated analysis performed using the code RELAP5/MOD3.2 considering all the major components of the reactor. The analysis shows that the PMCS is able to maintain the moderator temperature below boiling conditions for 7 days.

  2. Development and analysis of a new integrated power and cooling plant using LiBr–H2O mixture

    Indian Academy of Sciences (India)

    R Shankar; T Srinivas

    2014-12-01

    Cooling needs are increasing rapidly at hot climatic countries with increased global warming. The existed vapour compression refrigeration (VCR) system demands electricity for its operation which is more expensive. The concept of a newly proposed cooling cogeneration cycle has been developed by clubbing the power and cooling processes. It consists of characteristics of Rankine cycle and vapour absorption refrigeration (VAR) system and can be developed at hot climatic conditions with LiBr–water mixture as a working fluid. The results show that increase in heat source temperature is boosting power with a drop in cooling. The resulted cooling is seven times more than the power generation. The separator temperature has been recommended from 140 to 150°C to maximize the total output.

  3. Thermal modeling in an engine cooling system to control coolant flow for fuel consumption improvement

    Science.gov (United States)

    Park, Sangki; Woo, Seungchul; Kim, Minho; Lee, Kihyung

    2016-09-01

    The design and evaluation of engine cooling and lubrication systems is generally based on real vehicle tests. Our goal here was to establish an engine heat balance model based on mathematical and interpretive analysis of each element of a passenger diesel engine cooling system using a 1-D numerical model. The purpose of this model is to determine ways of optimizing the cooling and lubrication components of an engine and then to apply these methods to actual cooling and lubrication systems of engines that will be developed in the future. Our model was operated under the New European Driving Cycle (NEDC) mode conditions, which represent the fuel economy evaluation mode in Europe. The flow rate of the cooling system was controlled using a control valve. Our results showed that the fuel efficiency was improved by as much as 1.23 %, cooling loss by 1.35 %, and friction loss by 2.21 % throughout NEDC modes by modification of control conditions.

  4. Analysis of a New Dissipation System for a Solar Cooling Installation

    Directory of Open Access Journals (Sweden)

    Carlos Monné Bailo

    2010-01-01

    Full Text Available This paper describes a solar absorption cooling installation located at the University of Zaragoza (Spain. The installation is based on the performance of an absorption chiller. The solar cooling system consists of 37,5 m2 of flat plate collector, a 4.5 kW, single-effect LiBr-H2O absorption chiller, and a dry cooling tower. The installation provides cooling to a gymnasium belonging to the sports center of the university. To carry out the installation analysis, the system was continuously monitored. In 2007, 2008 and 2009, several studies have been performed in order to analyze the full system operation. The measured data showed the strong influence of the cooling water temperature and the generator driving temperature on the COP. Due to the experimental evidence of the influence of the cooling water temperature, a new heat rejection system based on a geothermal heat sink has been installed and studied.

  5. A Model to Predict Total Chlorine Residue in the Cooling Seawater of a Power Plant Using Iodine Colorimetric Method

    Directory of Open Access Journals (Sweden)

    Pei-Jie Meng

    2008-04-01

    Full Text Available A model experiment monitoring the fate of total residue oxidant (TRO in water at a constant temperature and salinity indicated that it decayed exponentially with time, and with TRO decaying faster in seawater than in distilled water. The reduction of TRO by temperature (°K was found to fit a curvilinear relationship in distilled water (r2 = 0.997 and a linear relationship in seawater (r2 = 0.996. Based on the decay rate, flow rate, and the length of cooling water flowing through at a given temperature, the TRO level in the cooling water of a power plant could be estimated using the equation developed in this study. This predictive model would provide a benchmark for power plant operators to adjust the addition of chlorine to levels necessary to control bio-fouling of cooling water intake pipelines, but without irritating ambient marine organisms.

  6. A Model to Predict Total Chlorine Residue in the Cooling Seawater of a Power Plant Using Iodine Colorimetric Method

    Science.gov (United States)

    Wang, Jih-Terng; Chen, Ming-Hui; Lee, Hung-Jen; Chang, Wen-Been; Chen, Chung-Chi; Pai, Su-Cheng; Meng, Pei-Jie

    2008-01-01

    A model experiment monitoring the fate of total residue oxidant (TRO) in water at a constant temperature and salinity indicated that it decayed exponentially with time, and with TRO decaying faster in seawater than in distilled water. The reduction of TRO by temperature (°K) was found to fit a curvilinear relationship in distilled water (r2 = 0.997) and a linear relationship in seawater (r2 = 0.996). Based on the decay rate, flow rate, and the length of cooling water flowing through at a given temperature, the TRO level in the cooling water of a power plant could be estimated using the equation developed in this study. This predictive model would provide a benchmark for power plant operators to adjust the addition of chlorine to levels necessary to control bio-fouling of cooling water intake pipelines, but without irritating ambient marine organisms. PMID:19325768

  7. COOLING FAN AND SYSTEM PERFORMANCE AND EFFICIENCY IMPROVEMENTS

    Energy Technology Data Exchange (ETDEWEB)

    Ronald Dupree

    2005-07-31

    Upcoming emissions regulations (Tiers 3, 4a and 4b) are imposing significantly higher heat loads on the cooling system than lesser regulated machines. This work was a suite of tasks aimed at reducing the parasitic losses of the cooling system, or improving the design process through six distinct tasks: 1. Develop an axial fan that will provide more airflow, with less input power and less noise. The initial plan was to use Genetic Algorithms to do an automated fan design, incorporating forward sweep for low noise. First and second generation concepts could not meet either performance or sound goals. An experienced turbomachinery designer, using a specialized CFD analysis program has taken over the design and has been able to demonstrate a 5% flow improvement (vs 10% goal) and 10% efficiency improvement (vs 10% goal) using blade twist only. 2. Fan shroud developments, using an 'aeroshroud' concept developed at Michigan State University. Performance testing at Michigan State University showed the design is capable of meeting the goal of a 10% increase in flow, but over a very narrow operating range of fan performance. The goal of 10% increase in fan efficiency was not met. Fan noise was reduced from 0 to 2dB, vs. a goal of 5dB at constant airflow. The narrow range of fan operating conditions affected by the aeroshroud makes this concept unattractive for further development at this time 3. Improved axial fan system modeling is needed to accommodate the numbers of cooling systems to be redesigned to meet lower emissions requirements. A CFD fan system modeling guide has been completed and transferred to design engineers. Current, uncontrolled modeling practices produce flow estimates in some cases within 5% of measured values, and in some cases within 25% of measured values. The techniques in the modeling guide reduced variability to the goal of + 5% for the case under study. 4. Demonstrate the performance and design versatility of a high performance fan. A

  8. COOLING FAN AND SYSTEM PERFORMANCE AND EFFICIENCY IMPROVEMENTS

    Energy Technology Data Exchange (ETDEWEB)

    Ronald Dupree

    2005-07-31

    Upcoming emissions regulations (Tiers 3, 4a and 4b) are imposing significantly higher heat loads on the cooling system than lesser regulated machines. This work was a suite of tasks aimed at reducing the parasitic losses of the cooling system, or improving the design process through six distinct tasks: 1. Develop an axial fan that will provide more airflow, with less input power and less noise. The initial plan was to use Genetic Algorithms to do an automated fan design, incorporating forward sweep for low noise. First and second generation concepts could not meet either performance or sound goals. An experienced turbomachinery designer, using a specialized CFD analysis program has taken over the design and has been able to demonstrate a 5% flow improvement (vs 10% goal) and 10% efficiency improvement (vs 10% goal) using blade twist only. 2. Fan shroud developments, using an 'aeroshroud' concept developed at Michigan State University. Performance testing at Michigan State University showed the design is capable of meeting the goal of a 10% increase in flow, but over a very narrow operating range of fan performance. The goal of 10% increase in fan efficiency was not met. Fan noise was reduced from 0 to 2dB, vs. a goal of 5dB at constant airflow. The narrow range of fan operating conditions affected by the aeroshroud makes this concept unattractive for further development at this time 3. Improved axial fan system modeling is needed to accommodate the numbers of cooling systems to be redesigned to meet lower emissions requirements. A CFD fan system modeling guide has been completed and transferred to design engineers. Current, uncontrolled modeling practices produce flow estimates in some cases within 5% of measured values, and in some cases within 25% of measured values. The techniques in the modeling guide reduced variability to the goal of + 5% for the case under study. 4. Demonstrate the performance and design versatility of a high performance fan. A

  9. System and method for regulating EGR cooling using a rankine cycle

    Energy Technology Data Exchange (ETDEWEB)

    Ernst, Timothy C.; Morris, Dave

    2015-12-22

    This disclosure relates to a waste heat recovery (WHR) system and method for regulating exhaust gas recirculation (EGR) cooling, and more particularly, to a Rankine cycle WHR system and method, including a recuperator bypass arrangement to regulate EGR exhaust gas cooling for engine efficiency improvement and thermal management. This disclosure describes other unique bypass arrangements for increased flexibility in the ability to regulate EGR exhaust gas cooling.

  10. Micro-Stirling Active Cooling Module (MS/ACM) for DoD Electronics Systems

    Science.gov (United States)

    2012-03-01

    Micro- Stirling Active Cooling Module (MS/ACM) for DoD Electronics Systems Douglas S. Beck Beck Engineering, Inc. 1490 Lumsden Road, Port Orchard...refrigerator. We are developing for DARPA a cm-scale Micro- Stirling Active Cooling Module (MS/ACM) micro- refrigerator to benefit the DoD systems. Under...a DARPA contract, we are designing, building, and demonstrating a breadboard MS/ACM. Keywords: Stirling ; cooler; active cooling module; micro

  11. System and method for regulating EGR cooling using a Rankine cycle

    Energy Technology Data Exchange (ETDEWEB)

    Ernst, Timothy C.; Morris, Dave

    2017-08-29

    This disclosure relates to a waste heat recovery (WHR) system and method for regulating exhaust gas recirculation (EGR) cooling, and more particularly, to a Rankine cycle WHR system and method, including a recuperator bypass arrangement to regulate EGR exhaust gas cooling for engine efficiency improvement and thermal management. This disclosure describes other unique bypass arrangements for increased flexibility in the ability to regulate EGR exhaust gas cooling.

  12. Design for micro-combined cooling, heating and power systems stirling engines and renewable power systems

    CERN Document Server

    2015-01-01

    ‘Design for Micro-Combined Cooling, Heating & Power Systems’ provides a manual for the technical and structural design of systems for supplying decentralised energy in residential buildings. It presents the micro-combined cooling, heating & power systems Stirling engines & renewable energy sources (mCCHP-SE-RES) systems in an accessible manner both for the public at large, and for professionals who conceive, design or commercialise such systems or their components.  The high performance levels of these systems are demonstrated within the final chapter by the results of an experiment in which a house is equipped with a mCCHP-SE-RES system. The reader is also familiarized with the conceptual, technical and legal aspects of modern domestic energy systems; the components that constitute these systems; and advanced algorithms for achieving the structural and technical design of such systems. In residential buildings, satisfying demands of durable development has gradually evolved from necessity to...

  13. Non-Cooled Power System for Venus Lander

    Science.gov (United States)

    Salazar, Denise; Landis, Geoffrey A.; Colozza, Anthony J.

    2014-01-01

    The Planetary Science Decadal Survey of 2013-2022 stated that the exploration of Venus is of significant interest. Studying the seismic activity of the planet is of particular importance because the findings can be compared to the seismic activity of Earth. Further, the geological and atmospheric properties of Venus will shed light into the past and future of Earth. This paper presents a radioisotope power system (RPS) design for a small low-power Venus lander. The feasibility of the new power system is then compared to that of primary batteries. A requirement for the power source system is to avoid moving parts in order to not interfere with the primary objective of the mission - to collect data about the seismic activity of Venus using a seismometer. The target mission duration of the lander is 117 days, a significant leap from Venera 13, the longest-lived lander on the surface of Venus, which survived for 2 hours. One major assumption for this mission design is that the power source system will not provide cooling to the other components of the lander. This assumption is based on high-temperature electronics technology that will enable the electronics and components of the lander to operate at Venus surface temperature. For the proposed RPS, a customized General Purpose Heat Source Radioisotope Thermoelectric Generator (GPHSRTG) is designed and analyzed. The GPHS-RTG is chosen primarily because it has no moving parts and it is capable of operating for long duration missions on the order of years. This power system is modeled as a spherical structure for a fundamental thermal analysis. The total mass and electrical output of the system are calculated to be 24 kilograms and 26 Watts, respectively. An alternative design for a battery-based power system uses Sodium Sulfur batteries. To deliver a similar electrical output for 117 days, the battery mass is calculated to be 234 kilograms. Reducing mission duration or power required will reduce the required battery mass

  14. Alert Systems for production Plants

    DEFF Research Database (Denmark)

    Nielsen, Thomas Dyhre; Jensen, Finn Verner

    2005-01-01

    We present a new methodology for detecting faults and abnormal behavior in production plants. The methodology stems from a joint project with a Danish energy consortium. During the course of the project we encountered several problems that we believe are common for projects of this type. Most...... system operation, i.e., it does not rely on information about the possible faults. We illustrate the proposed method using real-world data from a coal driven power plant as well as simulated data from an oil production facility....

  15. Thermo Active Building Systems – Using Building Mass To Heat and Cool

    DEFF Research Database (Denmark)

    Olesen, Bjarne W.

    2014-01-01

    Using the thermal storage capacity of the concrete slabs between each floor in multistory buildings to heat or cool is a trend that began in the early 1990s in Switzerland.1,2 Pipes carrying water for heating and cooling are embedded in the center of the concrete slab. In central Europe (Germany......, Austria, Netherlands, etc.), this type of system has been installed in a significant number of new office buildings since the late 1990s. The trend is spreading to other parts of the world (the rest of Europe, North America and Asia). Thermo active building systems (TABS) are primarily used for cooling...... multistory buildings. By activating the building mass, there is a direct heating-cooling effect. Also, because of the thermal mass, the peak load will be reduced and some of the cooling load will be transferred beyond the time of occupancy. Because these systems for cooling operate at water temperatures...

  16. Heat exchanger. [rocket combustion chambers and cooling systems

    Science.gov (United States)

    Sokolowski, D. E. (Inventor)

    1978-01-01

    A heat exchanger, as exemplified by a rocket combustion chamber, is constructed by stacking thin metal rings having microsized openings therein at selective locations to form cooling passages defined by an inner wall, an outer wall and fins. Suitable manifolds are provided at each end of the rocket chamber. In addition to the cooling channel openings, coolant feed openings may be formed in each of rings. The coolant feed openings may be nested or positioned within generally U-shaped cooling channel openings. Compression on the stacked rings may be maintained by welds or the like or by bolts extending through the stacked rings.

  17. Impact of drought on U.S. steam electric power plant cooling water intakes and related water resource management issues.

    Energy Technology Data Exchange (ETDEWEB)

    Kimmell, T. A.; Veil, J. A.; Environmental Science Division

    2009-04-03

    This report was funded by the U.S. Department of Energy's (DOE's) National Energy Technology Laboratory (NETL) Existing Plants Research Program, which has an energy-water research effort that focuses on water use at power plants. This study complements their overall research effort by evaluating water availability at power plants under drought conditions. While there are a number of competing demands on water uses, particularly during drought conditions, this report focuses solely on impacts to the U.S. steam electric power plant fleet. Included are both fossil-fuel and nuclear power plants. One plant examined also uses biomass as a fuel. The purpose of this project is to estimate the impact on generation capacity of a drop in water level at U.S. steam electric power plants due to climatic or other conditions. While, as indicated above, the temperature of the water can impact decisions to halt or curtail power plant operations, this report specifically examines impacts as a result of a drop in water levels below power plant submerged cooling water intakes. Impacts due to the combined effects of excessive temperatures of the returned cooling water and elevated temperatures of receiving waters (due to high ambient temperatures associated with drought) may be examined in a subsequent study. For this study, the sources of cooling water used by the U.S. steam electric power plant fleet were examined. This effort entailed development of a database of power plants and cooling water intake locations and depths for those plants that use surface water as a source of cooling water. Development of the database and its general characteristics are described in Chapter 2 of this report. Examination of the database gives an indication of how low water levels can drop before cooling water intakes cease to function. Water level drops are evaluated against a number of different power plant characteristics, such as the nature of the water source (river vs. lake or reservoir

  18. 核电循环泵轴承冷却风扇结构及其流场分析%Structure and Flow Field Analysis of Bearing Cooling Fans of the Circulating Cooling Water Pump in a Nuclear Power Plant

    Institute of Scientific and Technical Information of China (English)

    吴明哲; 王晓冬; 孙德臣

    2016-01-01

    The circulating cooling water pump in a nuclear power plant operates in a high temperature environment,and the pump bearing receives a large amount of heat load,so the work reliability is of great importance.To reduce the bearing’s working temperature and ensure its safe operation,a cooling device should be installed in the pump system.The structure of the bearing’s axial flow cooling fan in the pump was proposed,and the optimum design method of the bearing’s axial flow cooling fan in the pump was established.For the fan blades,the optimized calculation using BFGS algorithm was proceeded.A simulation verification of the system was proposed by using FLUENT,whose results showed that the design method is suitable for the bearing’s axial flow cooling fan design in circulating cooling water pumps in a nuclear power plant.%核电站冷却水循环泵在高温环境下工作,泵轴承受到很大的热负载,其工作可靠性至关重要。为降低轴承工作温度、保证轴承安全工作,在泵轴系统上设置了冷却装置。提出了泵轴承冷却用轴流式风扇的结构,建立了风扇结构的 BFGS 优化计算方法,采用计算流体力学软件 FLUENT 对风扇流场进行了数值分析。数值模拟结果表明,基于 BFGS 设计方法得到的冷却风扇性能有较好的设计计算精度,能够满足核电站冷却水循环泵轴承冷却的要求,该计算方法方便可行。

  19. Vibration test on KMRR reactor structure and primary cooling system piping

    Energy Technology Data Exchange (ETDEWEB)

    Chung, Seung Hoh; Kim, Tae Ryong; Park, Jin Hoh; Park, Jin Suk; Ryoo, Jung Soo [Korea Atomic Energy Research Institute, Taejon (Korea, Republic of)

    1994-10-01

    Most equipments, piping systems and reactor structures in nuclear power plants are subjected to flow induced vibration due to high temperature and high pressure coolant flowing inside or outside of the equipments, systems and structures. Because the flow induced vibration sometimes causes significant damage to reactor structures and piping systems, it is important and necessary to evaluate the vibration effect on them and to prove their structural integrity. Korea Multipurpose Research Reactor (KMRR) being constructed by KAERI is 30 MWt pool type research reactor. Since its main structures and piping systems were designed and manufactured in accordance with the standards and guidelines for commercial nuclear power plant, it was decided to evaluate their vibratory response in accordance with the standards and guidelines for commercial NPP. The objective of this vibration test is the assessment of vibration levels of KMRR reactor structure and primary cooling piping system for their structural integrity under the steady-state or transient operating condition. 38 figs, 14 tabs, 2 refs. (Author).

  20. Analysis of two troubles of air pre-cooling system of small-sized air separation plant%两起小型空分设备空气预冷系统故障分析

    Institute of Scientific and Technical Information of China (English)

    李小兴; 梁莺娥

    2012-01-01

    在3200 m3/h空分设备运行过程中,发生了常温水流量偏大导致常温水泵和低温水泵同时跳车、冷冻水温度调节旋钮脱落导致冷冻水温度太低的两起故障。介绍故障发生时的现象、故障原因以及故障发生时的应急操作。%During operation of 3200 m3/h air separation plant,slightly high flowrate of normal temperature water results in simultaneous trip of both the normal temperature water pump and the low-temperature water pump,and the dropping of the chilled water temperature adjustment knob results in too low chilled water temperature.The phenomena at occurring of the two troubles are described,and their causes and emergency operation are described.

  1. Monitoring Systems for Hydropower Plants

    Directory of Open Access Journals (Sweden)

    Damaschin Pepa

    2015-07-01

    Full Text Available One of the most important issue in hydro power industry is to determine the necessary degree of automation in order to improve the operation security. Depending upon the complexity of the system (the power plant equipment the automation specialist will build a philosophy of control following some general principals of security and operation. Helped by the modern digital equipment, today is relative easy to design a complete monitoring and supervising system including all the subparts of a hydro aggregate. A series of sensors and transducers specific for each auxiliary installation of the turbine and generator will be provided, together with a PLC or an industrial PC that will run an application software for implementing the security and control algorithms. The purpose of this paper is to offer a general view of these issues, providing a view of designing an automation & control and security system for hydro power plants of small, medium and big power.

  2. Better Duct Systems for Home Heating and Cooling; Building Technologies Program (Brochure)

    Energy Technology Data Exchange (ETDEWEB)

    None

    2004-11-01

    Duct systems used in forced-air space-conditioning systems are a vital element in home energy efficiency. How well a system works makes a big difference in the cost and the effectiveness of heating and cooling a home.

  3. System Design and Installation for RS600 Programmable Control System for Solar Heating and Cooling

    Energy Technology Data Exchange (ETDEWEB)

    None

    1978-01-01

    This document contains the installation, operation and maintenance manual, the system design drawings, installation drawings and the system design data brochure. It provides detailed information necessary for the building/ purchase and installation of the RS600 Programmable Control System for solar heating, combined heating and cooling and/ or hot water systems. Included are such item as general specifications, user configuration and options, displays, theory of operation, trouble-shooting procedures, parts lists, drawings, diagrams, wiring lists and warranty assistance.

  4. Thermal Analysis of a Solar Powered Absorption Cooling System with Fully Mixed Thermal Storage at Startup

    Directory of Open Access Journals (Sweden)

    Camelia Stanciu

    2017-01-01

    Full Text Available A simple effect one stage ammonia-water absorption cooling system fueled by solar energy is analyzed. The considered system is composed by a parabolic trough collector concentrating solar energy into a tubular receiver for heating water. This is stored in a fully mixed thermal storage tank and used in the vapor generator of the absorption cooling system. Time dependent cooling load is considered for the air conditioning of a residential two-storey house. A parametric study is performed to analyze the operation stability of the cooling system with respect to solar collector and storage tank dimensions. The results emphasized that there is a specific storage tank dimension associated to a specific solar collector dimension that could ensure the longest continuous startup operation of the cooling system when constant mass flow rates inside the system are assumed.

  5. Improved cooling design for high power waveguide system

    Science.gov (United States)

    Chen, W. C. J.; Hartop, R.

    1981-06-01

    Testing of X band high power components in a traveling wave resonator indicates that this improved cooling design reduces temperature in the waveguide and flange. The waveguide power handling capability and power transmission reliability is increased substantially.

  6. RF system concepts for a muon cooling experiment

    Energy Technology Data Exchange (ETDEWEB)

    Turner, W.C.; Corlett, J.N.; Li, D. [Lawrence Berkeley National Lab., CA (United States); Moretti, A. [Fermi National Accelerator Lab., Batavia, IL (United States); Kirk, H.G.; Palmer, R.B.; Zhao, Y. [Brookhaven National Lab., Upton, NY (United States)

    1998-06-01

    The feasibility of muon colliders for high energy physics experiments has been under intensive study for the past few years and recent activity has focused on defining an R and D program that would answer the critical issues. An especially critical issue is developing practical means of cooling the phase space of the muons once they have been produced and captured in a solenoidal magnetic transport channel. Concepts for the rf accelerating cavities of a muon cooling experiment are discussed.

  7. TRACG-CFD analysis of ESBWR reactor water cleanup shutdown cooling system mixing coefficient

    Energy Technology Data Exchange (ETDEWEB)

    Gallardo, J. [UNAM, Facultad de Ingenieria, Ciudad Universitaria, 04510 Ciudad de Mexico (Mexico); Marquino, W.; Mistreanu, A.; Yang, J., E-mail: euqrop@hotmail.com [General Electric Hitachi Nuclear Energy, Wilmington, 28401 North Carolina (United States)

    2015-09-15

    The ESBWR is a 1520 nominal [M We] Generation III+ natural circulation boiling water reactor designed to high levels of safety utilizing features that have been successfully used before in operating BWRs, as well as standard features common to A BWR. In September of 2014, the US NRC has certified the ESBWR design for use in the USA. The RWCU/Sdc is an auxiliary system for the ESBWR nuclear island. Basic functions it performs include purifying the reactor coolant during normal operation and shutdown and providing shutdown cooling and cooldown to cold shutdown conditions. The performance of the RWCU system during shutdown cooling is directly related to the temperature of the water removed through the outlets, which is coupled with the vessel and F W temperatures through a thermal mixing coefficient. The complex three-dimensional (3-D) geometry of the BWR downcomer and lower plenum has a great impact on the flow mixing. Only a fine mesh technique like CFD can predict the 3-D temperature distribution in the RPV during shutdown and provide the RWCU/Sdc system inlet temperature. Plant shutdown is an unsteady event by nature and was modeled as a succession of CFD steady-state simulations. It is required to establish the mixing coefficient (which is a function of the heat balance and the core flow) during the operation of the RWCU system in the multiple shutdown cooling modes, and therefore a range of core flows needs to be estimated using quasi steady states obtained with TRACG. The lower end of that range is obtained from a system with minimal power decay heat and core flow; while the higher end corresponds to the power at the beginning of RWCU/Sdc operation when the cooldown is transferred to the RWCU/Sdc after the initial depressurization via the turbine bypass valves. Because the ESBWR RWCU/Sdc return and suction designs provide good mixing, the uniform mixing energy balance was found to be an adequate alternative for deriving the mixing coefficient. The CFD mass flow

  8. Corrosion control when using secondary treated municipal wastewater as alternative makeup water for cooling tower systems.

    Science.gov (United States)

    Hsieh, Ming-Kai; Li, Heng; Chien, Shih-Hsiang; Monnell, Jason D; Chowdhury, Indranil; Dzombak, David A; Vidic, Radisav D

    2010-12-01

    Secondary treated municipal wastewater is a promising alternative to fresh water as power plant cooling water system makeup water, especially in arid regions. Laboratory and field testing was conducted in this study to evaluate the corrosiveness of secondary treated municipal wastewater for various metals and metal alloys in cooling systems. Different corrosion control strategies were evaluated based on varied chemical treatment. Orthophosphate, which is abundant in secondary treated municipal wastewater, contributed to more than 80% precipitative removal of phosphorous-based corrosion inhibitors. Tolyltriazole worked effectively to reduce corrosion of copper (greater than 95% inhibition effectiveness). The corrosion rate of mild steel in the presence of free chlorine 1 mg/L (as Cl2) was approximately 50% higher than in the presence of monochloramine 1 mg/L (as Cl2), indicating that monochloramine is a less corrosive biocide than free chlorine. The scaling layers observed on the metal alloys contributed to corrosion inhibition, which could be seen by comparing the mild steel 21-day average corrosion rate with the last 5-day average corrosion rate, the latter being approximately 50% lower than the former.

  9. Performance Evaluation of a Software Engineering Tool for Automated Design of Cooling Systems in Injection Moulding

    DEFF Research Database (Denmark)

    Jauregui-Becker, Juan M.; Tosello, Guido; van Houten, Fred J.A.M.

    2013-01-01

    This paper presents a software tool for automating the design of cooling systems for injection moulding and a validation of its performance. Cooling system designs were automatically generated by the proposed software tool and by applying a best practice tool engineering design approach. The two...

  10. Heat management of a cooling system based on the heat pipe for LED lighting fixtures

    Directory of Open Access Journals (Sweden)

    Rassamakin A. B.

    2013-10-01

    Full Text Available The authors have investigated a LED lamp cooling system that operates on a heat pipe basis. The paper describes the experimental stand, methods and results of the tests carried out for the different positions of the lamp at energy consumption of 196 W. It is shown that the considered cooling system ensures proper temperature of LEDs.

  11. 40 CFR 749.68 - Hexavalent chromium-based water treatment chemicals in cooling systems.

    Science.gov (United States)

    2010-07-01

    ... 40 Protection of Environment 30 2010-07-01 2010-07-01 false Hexavalent chromium-based water treatment chemicals in cooling systems. 749.68 Section 749.68 Protection of Environment ENVIRONMENTAL PROTECTION AGENCY (CONTINUED) TOXIC SUBSTANCES CONTROL ACT WATER TREATMENT CHEMICALS Air Conditioning and Cooling Systems § 749.68 Hexavalent...

  12. Cooling the largest events hall in the Benelux with an ATES system

    Energy Technology Data Exchange (ETDEWEB)

    Bakema, G. [IF Technology bv, Arnheim (Netherlands); Hengel, P.P.M. van den [BV Technical Management, Amersfoort (Netherlands)

    1994-12-31

    The cold storage to cool the new `De Prins van Oranje` hall of the Royal Netherlands Industries Fair in Utrecht, was started up early 1994. This system, with a cooling capacity of 2600 kW is the largest cold storage in an aquifer in the Netherlands. In the winter of 1994, this system stored 160 MWh cold energy. (orig.)

  13. Optimization Tool for Direct Water Cooling System of High Power IGBT Modules

    DEFF Research Database (Denmark)

    Bahman, Amir Sajjad; Blaabjerg, Frede

    2016-01-01

    important issue for thermal design engineers. This paper aims to present a user friendly optimization tool for direct water cooling system of a high power module which enables the cooling system designer to identify the optimized solution depending on customer load profiles and available pump power. CFD...

  14. Closed-cycle gas flow system for cooling of high Tc d.c. SQUID magnetometers

    NARCIS (Netherlands)

    Bosch, van den P.J.; Holland, H.J.; Brake, ter H.J.M.; Rogalla, H.

    1995-01-01

    A high Tc.d.c SQUID based magnetometer for magnetocardiography is currently under development at the University of Twente. Since such a magnetometer should be simple to use, the cooling of the system can be realized most practically by means of a cryocooler. A closed-cycle gas flow cooling system in

  15. Solar Heating and Cooling of Residential Buildings: Sizing, Installation and Operation of Systems.

    Science.gov (United States)

    Colorado State Univ., Ft. Collins. Solar Energy Applications Lab.

    This training course and a companion course titled "Design of Systems for Solar Heating and Cooling of Residential Buildings," are designed to train home designers and builders in the fundamentals of solar hydronic and air systems for space heating and cooling and domestic hot water heating for residential buildings. Each course, organized in 22…

  16. Model-based fault detection for generator cooling system in wind turbines using SCADA data

    DEFF Research Database (Denmark)

    Borchersen, Anders Bech; Kinnaert, Michel

    2016-01-01

    In this work, an early fault detection system for the generator cooling of wind turbines is presented and tested. It relies on a hybrid model of the cooling system. The parameters of the generator model are estimated by an extended Kalman filter. The estimated parameters are then processed by an ...

  17. An Experimental and Analytical Study of a Radiative Cooling System with Unglazed Flat Plate Collectors

    DEFF Research Database (Denmark)

    Hosseinzadeh, Elham; Taherian, Hessam

    2012-01-01

    On an average about 40% of world energy is used in residential buildings and the largest energy consumption is allocated to the cooling and air-conditioning systems. So every attempt to economize energy consumption is very valuable. In this research a nocturnal radiative cooling system with flat...... as a guideline to derive the governing equations of a night sky radiator. Then, a cooling loop, including a storage tank, pump, connecting pipes, and a radiator has been studied experimentally. The water is circulated through the unglazed flat-plate radiator having 4 m2 of collector area at night to be cooled...

  18. Constraining the role of early land plants in Palaeozoic weathering and global cooling.

    Science.gov (United States)

    Quirk, Joe; Leake, Jonathan R; Johnson, David A; Taylor, Lyla L; Saccone, Loredana; Beerling, David J

    2015-08-22

    How the colonization of terrestrial environments by early land plants over 400 Ma influenced rock weathering, the biogeochemical cycling of carbon and phosphorus, and climate in the Palaeozoic is uncertain. Here we show experimentally that mineral weathering by liverworts—an extant lineage of early land plants—partnering arbuscular mycorrhizal (AM) fungi, like those in 410 Ma-old early land plant fossils, amplified calcium weathering from basalt grains threefold to sevenfold, relative to plant-free controls. Phosphate weathering by mycorrhizal liverworts was amplified 9-13-fold over plant-free controls, compared with fivefold to sevenfold amplification by liverworts lacking fungal symbionts. Etching and trenching of phyllosilicate minerals increased with AM fungal network size and atmospheric CO2 concentration. Integration of grain-scale weathering rates over the depths of liverwort rhizoids and mycelia (0.1 m), or tree roots and mycelia (0.75 m), indicate early land plants with shallow anchorage systems were probably at least 10-fold less effective at enhancing the total weathering flux than later-evolving trees. This work challenges the suggestion that early land plants significantly enhanced total weathering and land-to-ocean fluxes of calcium and phosphorus, which have been proposed as a trigger for transient dramatic atmospheric CO2 sequestration and glaciations in the Ordovician. © 2015 The Authors.

  19. CFD Analysis of the Primary Cooling System for the Small Modular Natural Circulation Lead Cooled Fast Reactor SNRLFR-100

    Directory of Open Access Journals (Sweden)

    Pengcheng Zhao

    2016-01-01

    Full Text Available Small modular reactor (SMR has drawn wide attention in the past decades, and Lead cooled fast reactor (LFR is one of the most promising advanced reactors which are able to meet the safety economic goals of Gen-IV nuclear energy systems. A small modular natural circulation lead cooled fast reactor-100 MWth (SNRLFR-100 is being developed by University of Science and Technology of China (USTC. In the present work, a 3D CFD model, primary heat exchanger model, fuel pin model, and point kinetic model were established based on some reasonable simplifications and assumptions, the steady-state natural circulation characteristics of SNCLFR-100 primary cooling system were discussed and illustrated, and some reasonable suggestions were proposed for the reactor’s thermal-hydraulic and structural design. Moreover, in order to have a first evaluation of the system behavior in accident conditions, an unprotected loss of heat sink (ULOHS transient simulation at beginning of the reactor cycle (BOC has been analyzed and discussed based on the steady-state simulation results. The key temperatures of the reactor core are all under the safety limits at transient state; the reactor has excellent thermal-hydraulic performance.

  20. Passive residual energy utilization system in thermal cycles on water-cooled power reactors

    Energy Technology Data Exchange (ETDEWEB)

    Placco, Guilherme M.; Guimaraes, Lamartine N.F., E-mail: placco@ieav.cta.br, E-mail: guimarae@ieav.cta.br [Instituto de Estudos Avancados (IEAV/DCTA) Sao Jose dos Campos, SP (Brazil); Santos, Rubens S. dos, E-mail: rsantos@ien.gov.br [Instituto de Engenharia Nuclear (IEN/CNEN -RJ), Rio de Janeiro, RJ (Brazil)

    2013-07-01

    This work presents a concept of a residual energy utilization in nuclear plants thermal cycles. After taking notice of the causes of the Fukushima nuclear plant accident, an idea arose to adapt a passive thermal circuit as part of the ECCS (Emergency Core Cooling System). One of the research topics of IEAv (Institute for Advanced Studies), as part of the heat conversion of a space nuclear power system is a passive multi fluid turbine. One of the main characteristics of this device is its passive capability of staying inert and be brought to power at moments notice. During the first experiments and testing of this passive device, it became clear that any small amount of gas flow would generate power. Given that in the first stages of the Fukushima accident and even during the whole event there was plenty availability of steam flow that would be the proper condition to make the proposed system to work. This system starts in case of failure of the ECCS, including loss of site power, loss of diesel generators and loss of the battery power. This system does not requires electricity to run and will work with bleed steam. It will generate enough power to supply the plant safety system avoiding overheating of the reactor core produced by the decay heat. This passive system uses a modified Tesla type turbine. With the tests conducted until now, it is possible to ensure that the operation of this new turbine in a thermal cycle is very satisfactory and it performs as expected. (author)

  1. Assessment of the reduced ore cooling process at the Ernesto Che Guevara Plant

    Directory of Open Access Journals (Sweden)

    Ever Góngora-Leyva

    2012-10-01

    Full Text Available The analysis of the investigations related to evaluations on the process of reduced ore cooling in rotating horizontal cylinders on an industrial scale indicated that there are only water temperature measurements on one end of pit and showed no experiments where the variables of water and ore flowrates were evaluated nor the relation with the temperature of the ore at the cooler outlet. Based on this precedent, six thermocouples were installed to calculate the cooling water temperature in three locations on both sides of the pit connected to the data input system in place in the enterprise. The design of the experiment was developed from analyzing a population of data from a 6/month period. The results showed that the variable of greater impact on the ore temperature at the cot oler outlet is the water flowrate. For lower water flowrates (15m3/h heat transfer by water evaporation to the air is predominant and for higher water flowrates (25m3/h heat transfer by convection is predominant. Also, it was possible to know that the cooler heat output reaches the highest values (86% with the lowest ore and water flowrates (15m3/h and 29t/h, respectively.

  2. Integrating fuel cell power systems into building physical plants

    Energy Technology Data Exchange (ETDEWEB)

    Carson, J. [KCI Technologies, Inc., Hunt Valley, MD (United States)

    1996-12-31

    This paper discusses the integration of fuel cell power plants and absorption chillers to cogenerate chilled water or hot water/steam for all weather air conditioning as one possible approach to building system applications. Absorption chillers utilize thermal energy in an absorption based cycle to chill water. It is feasible to use waste heat from fuel cells to provide hydronic heating and cooling. Performance regimes will vary as a function of the supply and quality of waste heat. Respective performance characteristics of fuel cells, absorption chillers and air conditioning systems will define relationships between thermal and electrical load capacities for the combined systems. Specifically, this paper develops thermodynamic relationships between bulk electrical power and cooling/heating capacities for combined fuel cell and absorption chiller system in building applications.

  3. Performance Assessment of a Desiccant Cooling System in a CHP Application with an IC Engine

    Energy Technology Data Exchange (ETDEWEB)

    Jalalzadeh-Azar, A. A.; Slayzak, S.; Judkoff, R.; Schaffhauser, T.; DeBlasio, R.

    2005-04-01

    Performance of a desiccant cooling system was evaluated in the context of combined heat and power (CHP). The baseline system incorporated a desiccant dehumidifier, a heat exchanger, an indirect evaporative cooler, and a direct evaporative cooler. The desiccant unit was regenerated through heat recovery from a gas-fired reciprocating internal combustion engine. The system offered sufficient sensible and latent cooling capacities for a wide range of climatic conditions, while allowing influx of outside air in excess of what is typically required for commercial buildings. Energy and water efficiencies of the desiccant cooling system were also evaluated and compared with those of a conventional system. The results of parametric assessments revealed the importance of using a heat exchanger for concurrent desiccant post cooling and regeneration air preheating. These functions resulted in enhancement of both the cooling performance and the thermal efficiency, which are essential for fuel utilization improvement. Two approaches for mixing of the return air and outside air were examined, and their impact on the system cooling performance and thermal efficiency was demonstrated. The scope of the parametric analyses also encompassed the impact of improving the indirect evaporative cooling effectiveness on the overall cooling system performance.

  4. The impact of monochloramine on the diversity and dynamics of Legionella pneumophila subpopulations in a nuclear power plant cooling circuit.

    Science.gov (United States)

    Jakubek, Delphine; Le Brun, Matthieu; Leblon, Gerard; DuBow, Michael; Binet, Marie

    2013-08-01

    Members of the pathogenic Legionella genus encounter suitable growth conditions in nuclear power plant cooling circuits. To limit its proliferation and ensure that levels remain below regulatory thresholds, chemical treatment with monochloramine can be used in continuous or sequential conditions. The aim of this study was to determine the impact of monochloramine on L. pneumophila subpopulations in the cooling circuits of a nuclear power plant. The chosen procedure involved monitoring the diversity and dynamics of L. pneumophila subpopulations every month over the course of a year in a nuclear power plant cooling circuit, which was treated for 2 months during the period under study. This study confirmed the effectiveness of monochloramine to limit L. pneumophila concentrations in cooling circuits. The culturable L. pneumophila community was strongly affected by the injection of monochloramine. Several subpopulations persisted during treatment at low concentrations (below the detection limit of standard methods), suggesting that the susceptibility of L. pneumophila is strain dependent. Although the composition of the subpopulations was not similar, the resilience of the community structure was observed. Indeed, the community eventually returned to its initial structure and presented a similar pattern of richness, diversity and uniformity to that seen before treatment.

  5. Autonomous systems for plant protection

    DEFF Research Database (Denmark)

    Griepentrog, Hans W.; Ruckelshausen, Arno; Jørgensen, Rasmus Nyholm

    2010-01-01

    Advances in automation are demanded by the market mainly as a response to high labor costs. Robotic outdoor systems are ready to allow not only economically viable operations but also increased efficiency in agriculture, horticulture and forestry. The aim of this chapter is to give examples of au...... and safe behaviors. In general the potential of saving e.g. of herbicides are huge when high precision targeting based on individual weed plant detections is used....

  6. Comparison of solar panel cooling system by using dc brushless fan and dc water

    Science.gov (United States)

    Irwan, Y. M.; Leow, W. Z.; Irwanto, M.; M, Fareq; Hassan, S. I. S.; Safwati, I.; Amelia, A. R.

    2015-06-01

    The purpose of this article is to discuss comparison of solar panel cooling system by using DC brushless fan and DC water pump. Solar photovoltaic (PV) power generation is an interesting technique to reduce non-renewable energy consumption and as a renewable energy. The temperature of PV modules increases when it absorbs solar radiation, causing a decrease in efficiency. A solar cooling system is design, construct and experimentally researched within this work. To make an effort to cool the PV module, Direct Current (DC) brushless fan and DC water pump with inlet/outlet manifold are designed for constant air movement and water flow circulation at the back side and front side of PV module representatively. Temperature sensors were installed on the PV module to detect temperature of PV. PIC microcontroller was used to control the DC brushless fan and water pump for switch ON or OFF depend on the temperature of PV module automatically. The performance with and without cooling system are shown in this experiment. The PV module with DC water pump cooling system increase 3.52%, 36.27%, 38.98%in term of output voltage, output current, output power respectively. It decrease 6.36 °C compare than to PV module without DC water pump cooling system. While DC brushless fan cooling system increase 3.47%, 29.55%, 32.23%in term of output voltage, output current, and output power respectively. It decrease 6.1 °C compare than to PV module without DC brushless fan cooling system. The efficiency of PV module with cooling system was increasing compared to PV module without cooling system; this is because the ambient temperature dropped significantly. The higher efficiency of PV cell, the payback period of the system can be shorted and the lifespan of PV module can also be longer.

  7. Thermal behaviour analysis on ITER component cooling water system loop 2B

    Energy Technology Data Exchange (ETDEWEB)

    Guo, Bin, E-mail: guobin@ipp.ac.cn [Institute of Plasma Physics, Chinese Academy of Sciences, Hefei 230031 (China); Fu, Peng [Institute of Plasma Physics, Chinese Academy of Sciences, Hefei 230031 (China); Dell’Orco, Giovanni; Liliana, Teodoros; Tao, Jun [ITER Organization, CS 90 046, 13067 St Paul Lez Durance Cedex (France); Yang, Lei [Institute of Plasma Physics, Chinese Academy of Sciences, Hefei 230031 (China)

    2015-11-15

    Highlights: • Thermal hydraulic analysis model has been developed to perform thermal analysis on the component cooling water system loop 2B. • The cooling water temperature profile at client inlet and outlet during one cycle of the most demanding plasma operation scenario was obtained. • Operation behaviour of the main heat exchanger for CCWS-2B has been depicted. - Abstract: ITER cooling water system is composed by several cooling loops, the primary heat transfer loops that form the Tokamak Cooling Water System (TCWS), the secondary heat transfer loops that form the Component Cooling Water System (CCWS) and the Chilled Water System (CHWS) and a tertiary heat transfer loop which is the Heat Rejection System (HRS). The CCWS is further divided into CCWS-1, CCWS-2A, CCWS-2B, CCWS-2C, CCWS-2D depending on the water chemistry needs of clients and wetted area material. The component cooling water system loop 2B (CCWS-2B) has the function to remove heat load from coil power supply component, Neutral Beam Injectors (NBIs) system component and diagnostic system which are located in different buildings. As the total number of the client connections for the loop is a few hundreds, simplified thermal hydraulic analysis model has been developed to perform thermal analysis on the component cooling water system loop 2B. The curve of the cooling water temperature at client inlet and outlet during one cycle of the most demanding plasma operation scenario was obtained and the cooling water flow rate can meet the thermal removal requirement of client was also confirmed from this analysis. In addition, operation behaviour of the main heat exchanger for CCWS-2B in this thermal analysis was depicted for main heat exchanger selection purposes. This study has been carried out with the AFT Fathom code.

  8. Cooling water system thermal performance analysis using the COCO computer code

    Energy Technology Data Exchange (ETDEWEB)

    Hom, J.; Jakub, R.M.; Durkosh, D.E. [Westinghouse Electric Corp., Pittsburgh, PA (United States). Energy Systems Business Unit

    1996-10-01

    Westinghouse Energy Systems Business Unit (ESBU) has worked with electric utility personnel to analyze the thermal performance of essential cooling water systems at nuclear generating stations. The primary goal of these analyses has been to demonstrate the operability of the cooling water systems during postulated limiting post-accident operation. In previous cooling water system thermal analyses, peak containment operating conditions were generally used as input assuming steady-state conditions. This approach is conservative as it does not take into account the improvement in containment conditions and cooling water system temperatures over time. This approach can, also, lead to an inconsistent set of assumptions between the two distinct analyses which may result in overly conservative calculated system operating conditions. These conditions inevitably impose unnecessary restrictions on cooling water system operation. Over the last few years, Westinghouse ESBU has coupled both the containment integrity and the cooling water system thermal calculations into an integrated analysis. This allows the use of a consistent set of input parameters and assumptions in the calculation of limiting cooling water system operating conditions. This approach has been successfully used to increase system operating margins. This paper provides an overview of this coupled thermal analysis along with examples of where increased operating margins can be applied.

  9. Two-Pipe Chilled Beam System for Both Cooling and Heating of Office Buildings

    DEFF Research Database (Denmark)

    Afshari, Alireza; Gordnorouzi, Rouzbeh; Hultmark, Göran;

    2013-01-01

    advantage of renewable energy. The results showed that the energy consumption was 3% less in the 2-pipe chilled beam system in comparison with the conventional 4-pipe system when moving cooled and heated water through the building, transferring the energy to where it is needed. Using free cooling (taking...... consumption and hence energy savings in the 2-pipe chilled beam system in comparison with the 4-pipe system. The 2-pipe chilled beam system used high temperature cooling and low temperature heating with a water temperature of 20°C to 23°C, available for free most of the year. The system can thus take......Simulations were performed to compare a conventional 4-pipe chilled beam system and a 2-pipe chilled beam system. The objective was to establish requirements, possibilities and limitations for a well-functioning 2-pipe chilled beam system for both cooling and heating of office buildings...

  10. Thermal ecology of Naegleria fowleri from a power plant cooling reservoir.

    Science.gov (United States)

    Huizinga, H W; McLaughlin, G L

    1990-07-01

    The pathogenic, free-living amoeba Naegleria fowleri is the causative agent of human primary amebic meningoencephalitis. N. fowleri has been isolated from thermally elevated aquatic environments worldwide, but temperature factors associated with occurrence of the amoeba remain undefined. In this study, a newly created cooling reservoir (Clinton Lake, Illinois) was surveyed for Naegleria spp. before and after thermal additions from a nuclear power plant. Water and sediment samples were collected from heated and unheated arms of the reservoir and analyzed for the presence of thermophilic Naegleria spp. and pathogenic N. fowleri. Amoebae were identified by morphology, in vitro cultivation, temperature tolerance, mouse pathogenicity assay, and DNA restriction fragment length analysis. N. fowleri was isolated from the thermally elevated arm but not from the ambient-temperature arm of the reservoir. The probability of isolating thermophilic Naegleria and pathogenic N. fowleri increased significantly with temperature. Repetitive DNA restriction fragment profiles of the N. fowleri Clinton Lake isolates and a known N. fowleri strain of human origin were homogeneous.

  11. Thermal ecology of Naegleria fowleri from a power plant cooling reservoir

    Energy Technology Data Exchange (ETDEWEB)

    Huizinga, H.W. (Illinois State Univ., Normal (USA)); McLaughlin, G.L. (Univ. of Illinois, Urbana (USA))

    1990-07-01

    The pathogenic, free-living amoeba Naegleria fowleri is the causative agent of human primary amebic meningoencephalitis. N. fowleri has been isolated from thermally elevated aquatic environments worldwide, but temperature factors associated with occurrence of the amoeba remain undefined. In this study, a newly created cooling reservoir (Clinton Lake, Illinois) was surveyed for Naegleria spp. before and after thermal additions from a nuclear power plant. Water and sediment samples were collected from heated and unheated arms of the reservoir and analyzed for the presence of thermophilic Naegleria spp. and pathogenic N. fowleri. Amoebae were identified by morphology, in vitro cultivation, temperature tolerance, mouse pathogenicity assay, and DNA restriction fragment length analysis. N. fowleri was isolated from the thermally elevated arm but not from the ambient-temperature arm of the reservoir. The probability of isolating thermophilic Naegleria and pathogenic N. fowleri increased significantly with temperature. Repetitive DNA restriction fragment profiles of the N. fowleri Clinton Lake isolates and a known N. fowleri strain of human origin were homogeneous.

  12. Performance analysis on utilization of sky radiation cooling energy for space cooling. Part 2; Hosha reikyaku riyo reibo system ni kansuru kenkyu. 2

    Energy Technology Data Exchange (ETDEWEB)

    Marushima, S.; Saito, T. [Tohoku University, Sendai (Japan)

    1996-10-27

    Studies have been made about a heat accumulation tank type cooling system making use of radiation cooling that is a kind of natural energy. The daily operating cycle of the cooling system is described below. A heat pump air conditioner performs cooling during the daytime and the exhaust heat is stored in a latent heat accumulation tank; the heat is then used for the bath and tapwater in the evening; at night radiation cooling is utilized to remove the heat remnant in the tank for the solidification of the phase change material (PCM); the solidified PCM serves as the cold heat source for the heat pump air conditioner to perform cooling. The new system decelerates urban area warming because it emits the cooler-generated waste heat not into the atmosphere but into space taking advantage of radiation cooling. Again, the cooler-generated waste heat may be utilized for energy saving and power levelling. For the examination of nighttime radiation cooling characteristics, CaCl2-5H2O and Na2HPO4-12H2O were tested as the PCM. Water was used as the heating medium. In the case of a PCM high in latent heat capacity, some work has to be done for insuring sufficient heat exchange for it by, for instance, rendering the flow rate low. The coefficient of performance of the system discussed here is three times higher than that of the air-cooled type heat pump system. 8 refs., 5 figs., 4 tabs.

  13. LED Systems Target Plant Growth

    Science.gov (United States)

    2010-01-01

    To help develop technologies for growing edible biomass (food crops) in space, Kennedy Space Center partnered with Orbital Technologies Corporation (ORBITEC), of Madison, Wisconsin, through the Small Business Innovation Research (SBIR) program. One result of this research was the High Efficiency Lighting with Integrated Adaptive Control (HELIAC) system, components of which have been incorporated into a variety of agricultural greenhouse and consumer aquarium lighting features. The new lighting systems can be adapted to a specific plant species during a specific growth stage, allowing maximum efficiency in light absorption by all available photosynthetic tissues.

  14. Sub-cooled liquid nitrogen cryogenic system with neon turbo-refrigerator for HTS power equipment

    Science.gov (United States)

    Yoshida, S.; Hirai, H.; Nara, N.; Ozaki, S.; Hirokawa, M.; Eguchi, T.; Hayashi, H.; Iwakuma, M.; Shiohara, Y.

    2014-01-01

    We developed a prototype sub-cooled liquid nitrogen (LN) circulation system for HTS power equipment. The system consists of a neon turbo-Brayton refrigerator with a LN sub-cooler and LN circulation pump unit. The neon refrigerator has more than 2 kW cooling power at 65 K. The LN sub-cooler is a plate-fin type heat exchanger and is installed in a refrigerator cold box. In order to carry out the system performance tests, a dummy cryostat having an electric heater was set instead of a HTS power equipment. Sub-cooled LN is delivered into the sub-cooler by the LN circulation pump and cooled within it. After the sub-cooler, sub-cooled LN goes out from the cold box to the dummy cryostat, and comes back to the pump unit. The system can control an outlet sub-cooled LN temperature by adjusting refrigerator cooling power. The refrigerator cooling power is automatically controlled by the turbo-compressor rotational speed. In the performance tests, we increased an electric heater power from 200 W to 1300 W abruptly. We confirmed the temperature fluctuation was about ±1 K. We show the cryogenic system details and performance test results in this paper.

  15. The final cool down

    CERN Multimedia

    Thursday 29th May, the cool-down of the final sector (sector 4-5) of LHC has begun, one week after the start of the cool-down of sector 1-2. It will take five weeks for the sectors to be cooled from room temperature to 5 K and a further two weeks to complete the cool down to 1.9 K and the commissioning of cryogenic instrumentation, as well as to fine tune the cryogenic plants and the cooling loops of cryostats.Nearly a year and half has passed since sector 7-8 was cooled for the first time in January 2007. For Laurent Tavian, AT/CRG Group Leader, reaching the final phase of the cool down is an important milestone, confirming the basic design of the cryogenic system and the ability to operate complete sectors. “All the sectors have to operate at the same time otherwise we cannot inject the beam into the machine. The stability and reliability of the cryogenic system and its utilities are now very important. That will be the new challenge for the coming months,” he explains. The status of the cool down of ...

  16. Cooling system in a rotary piston internal combustion engine. Kuehlsystem einer Rotationskolbenbrennkraftmaschine

    Energy Technology Data Exchange (ETDEWEB)

    Eiermann, D.; Nuber, R.

    1991-05-23

    Cooling system of a trochoid-type rotary piston internal combustion engine with a liquid-cooled casing. First the coolant is conducted isochronically and in parallel through cooling chambers of the jacket and a side part of the casing from where it is transported by a cooling pump through the cooling chambers of the other side part, on past a thermostat and into a cooler positioned on this other side part. The cooler consists of a parallel connected pipe bundle whose finned pipes follow the radial outer contours of the casing of the machine. From the cooler the coolant is conducted back into the cooling chambers of the first side part and the jacket. A blower fitted on the eccentric shaft of the internal combustion engine inside the cooler takes in fresh air axially and discharges it radially through the finned pipes.

  17. A Novel Pre-cooling System for a Cryogenic Pulsating Heat Pipe

    Science.gov (United States)

    Xu, Dong; Liu, Huiming; Gong, Linghui; Xu, Xiangdong; Li, Laifeng

    To reduce the influence of the pipe material on the measurement of effective thermal conductivity, the pipe of a cryogenic pulsating heat pipe is generally made of stainless steel. Because of the low thermal conductivity of stainless steel, the pre-cooling of the evaporator in cryogenic pulsating heat pipe using helium as working fluid at 4.2 K is a problem. We designed a mechanical-thermal switch between the cryocooler and the evaporator, which was on during the pre-cooling process and off during the test process. By using the pre-cooling system, the cool down time of the cryogenic pulsating heat pipe was reduced significantly.

  18. Development of an Anti-Vibration Controller for Magnetic Bearing Cooling Systems Project

    Data.gov (United States)

    National Aeronautics and Space Administration — This proposal outlines a program to develop a vibration-free reverse-Brayton cycle cooling system using specially-tuned magnetic bearings. Such a system is critical...

  19. Characterization of selected application of biomass energy technologies and a solar district heating and cooling system

    Energy Technology Data Exchange (ETDEWEB)

    D' Alessio, Dr., Gregory J.; Blaunstein, Robert P.

    1980-09-01

    The following systems are discussed: energy self-sufficient farms, wood gasification, energy from high-yield silviculture farms, and solar district heating and cooling. System descriptions and environmental data are included for each one. (MHR)

  20. Demonstration of a Passive Thermal Management System for Cooling Electronics in Extreme Environments Project

    Data.gov (United States)

    National Aeronautics and Space Administration — Extended operation of exploratory systems on the surface of planets like Venus, means that techniques to cool system electronics to essentially room temperature...

  1. Chitosan Effects on Plant Systems

    Directory of Open Access Journals (Sweden)

    Massimo Malerba

    2016-06-01

    Full Text Available Chitosan (CHT is a natural, safe, and cheap product of chitin deacetylation, widely used by several industries because of its interesting features. The availability of industrial quantities of CHT in the late 1980s enabled it to be tested in agriculture. CHT has been proven to stimulate plant growth, to protect the safety of edible products, and to induce abiotic and biotic stress tolerance in various horticultural commodities. The stimulating effect of different enzyme activities to detoxify reactive oxygen species suggests the involvement of hydrogen peroxide and nitric oxide in CHT signaling. CHT could also interact with chromatin and directly affect gene expression. Recent innovative uses of CHT include synthesis of CHT nanoparticles as a valuable delivery system for fertilizers, herbicides, pesticides, and micronutrients for crop growth promotion by a balanced and sustained nutrition. In addition, CHT nanoparticles can safely deliver genetic material for plant transformation. This review presents an overview on the status of the use of CHT in plant systems. Attention was given to the research that suggested the use of CHT for sustainable crop productivity.

  2. Chitosan Effects on Plant Systems

    Science.gov (United States)

    Malerba, Massimo; Cerana, Raffaella

    2016-01-01

    Chitosan (CHT) is a natural, safe, and cheap product of chitin deacetylation, widely used by several industries because of its interesting features. The availability of industrial quantities of CHT in the late 1980s enabled it to be tested in agriculture. CHT has been proven to stimulate plant growth, to protect the safety of edible products, and to induce abiotic and biotic stress tolerance in various horticultural commodities. The stimulating effect of different enzyme activities to detoxify reactive oxygen species suggests the involvement of hydrogen peroxide and nitric oxide in CHT signaling. CHT could also interact with chromatin and directly affect gene expression. Recent innovative uses of CHT include synthesis of CHT nanoparticles as a valuable delivery system for fertilizers, herbicides, pesticides, and micronutrients for crop growth promotion by a balanced and sustained nutrition. In addition, CHT nanoparticles can safely deliver genetic material for plant transformation. This review presents an overview on the status of the use of CHT in plant systems. Attention was given to the research that suggested the use of CHT for sustainable crop productivity. PMID:27347928

  3. Hydro-Potential Utilization of Cooling Water on the Hydro-Electric Power Plant Dalešice

    OpenAIRE

    Hudec, Martin; Haluza, Miloslav; Kubálek, Jiří

    2009-01-01

    Engineering solution of a surplus pressure head in a system of reversible machine unit's cooling water. Current technologies supplemented with Francis turbine or more precisely a centrifugal volute-type pump in turbine mode. It contains the layout for the basic extent of several various high-speeds with regard to maximum coverage of working conditions. Minimization of construction works on the structure of the cooling water inlet. Furthermore it includes an assignment of the annual power prod...

  4. Mathematical and experimental investigations on dispersion and recirculation of plumes from dry cooling towers at Wyodak Power Plant in Wyoming

    Energy Technology Data Exchange (ETDEWEB)

    Onishi, Y.; Trent, D.S.

    1976-02-01

    The study presented was conducted (1) to develop a two-dimensional mathematical simulation model for determination of plume dispersion and recirculation from an existing code; (2) to investigate experimentally and mathematically the recirculation and temperature distributions of plumes from two dry cooling towers at the Wyodak Plant in Wyoming; and (3) to elucidate the effects of wind velocity, temperature of heated effluent, adjacent cooling towers and local topography on plume dispersion and recirculation. The mathematical model is based on solution of the steady flow momentum and energy equations using the stream function-vorticity technique. Experiments were conducted in a 10-foot-wide hydraulic flume, using water as a model flow. The study shows that plume recirculation and dispersion are strongly influenced by local topography and nearby structures such as adjacent cooling towers and buildings, as well as by the ambient wind velocity and effluent exit temperature.

  5. Experimental investigation of cooling performance of a novel HVAC system combining natural ventilation with diffuse ceiling inlet and TABS

    DEFF Research Database (Denmark)

    Yu, Tao; Heiselberg, Per Kvols; Lei, Bo;

    2015-01-01

    Highlights •An experimental investigation of cooling performance of a combined HVAC system is carried out. •Cooling performance of TABS with and without the influence of diffuse ceiling is analyzed. •Radiant and convective heat transfer coefficients of TABS cooling are studied. •Cooling components...

  6. Corrosion of metals and alloys - Corrosion and fouling in industrial cooling water systems - Part 1: Guidelines for conducting pilot-scale evaluation of corrosion and fouling control additives for open recirculating cooling water systems

    CERN Document Server

    International Organization for Standardization. Geneva

    2006-01-01

    Corrosion of metals and alloys - Corrosion and fouling in industrial cooling water systems - Part 1: Guidelines for conducting pilot-scale evaluation of corrosion and fouling control additives for open recirculating cooling water systems

  7. Field evaluation of performance of radiant heating/cooling ceiling panel system

    DEFF Research Database (Denmark)

    Li, Rongling; Yoshidomi, Togo; Ooka, Ryozo;

    2015-01-01

    heating/coolingceiling panel system is used. However, no standard exists for the in situ performance evaluation of radiantheating/cooling ceiling systems; furthermore, no published database is available for comparison. Thus,this study aims to not only clarify the system performance but also to share our...... experience and our resultsfor them to serve as a reference for other similar projects. Here, the system performance in relation toits heating/cooling capacity and thermal comfort has been evaluated. The heat transfer coefficient fromwater to room was 3.7 W/(m2K) and 4.8 W/(m2K) for heating and cooling cases...

  8. Cooling Performance Characteristics on Mobile Air-Conditioning System for Hybrid Electric Vehicles

    OpenAIRE

    Ho-Seong Lee; Moo-Yeon Lee

    2013-01-01

    This study investigates the cooling performance characteristics of the mobile air-conditioning system using R744 (CO2) for the hybrid electric vehicle as an alternative to both the R-134a and the conventional air-conditioning system. The developed air-conditioning system is operated with an electric driven compressor in the battery driving mode and a belt driven compressor in the engine driving mode. The cooling performance characteristics of the developed system have been analyzed by experim...

  9. Ground-Coupled Heating-Cooling Systems in Urban Areas: How Sustainable Are They?

    Science.gov (United States)

    Younger, Paul L.

    2008-01-01

    Ground-coupled heating-cooling systems (GCHCSs) exchange heat between the built environment and the subsurface using pipework buried in trenches or boreholes. If heat pumps in GCHCSs are powered by "green electricity," they offer genuine carbon-free heating-cooling; for this reason, there has been a surge in the technology in recent years.…

  10. Fan and Pad Evaporative Cooling System for Greenhouses: Evaluation of a Numerical and Analytical Model

    NARCIS (Netherlands)

    Sapounas, A.; Nikita-Martzopoulou, Ch.; Bartzanas, T.; Kittas, C.

    2008-01-01

    An experimental greenhouse equipped with fan and pad evaporative cooling is analysed using two different models. The first one consists of a numerical simulation approach applying a commercial CFD code. The main aspects of evaporative cooling systems, in terms of heat and mass transfer and both the

  11. Solar heating and cooling of residential buildings: sizing, installation and operation of systems. 1980 edition

    Energy Technology Data Exchange (ETDEWEB)

    None

    1980-09-01

    This manual was prepared as a text for a training course on solar heating and cooling of residential buildings. The course and text are directed toward sizing, installation, operation, and maintenance of solar systems for space heating and hot water supply, and solar cooling is treated only briefly. (MHR)

  12. Greenhouse with an Integrated NIR Filter and a Solar Cooling System

    NARCIS (Netherlands)

    Sonneveld, P.J.; Swinkels, G.L.A.M.; Kempkes, F.L.K.; Campen, J.B.; Bot, G.P.A.

    2006-01-01

    The scope of this paper is a new greenhouse design that incorporates both a filter for rejecting near infrared radiation (NIR) and a solar cooling system. Cooled greenhouses are an important issue for the combination of high global radiation and high outdoor temperatures. As a first measure, this

  13. Performance test of the cryogenic cooling system for the superconducting fault current limiter

    Science.gov (United States)

    Hong, Yong-Ju; In, Sehwan; Yeom, Han-Kil; Kim, Heesun; Kim, Hye-Rim

    2015-12-01

    A Superconducting Fault Current Limiter is an electric power device which limits the fault current immediately in a power grid. The SFCL must be cooled to below the critical temperature of high temperature superconductor modules. In general, they are submerged in sub-cooled liquid nitrogen for their stable thermal characteristics. To cool and maintain the target temperature and pressure of the sub-cooled liquid nitrogen, the cryogenic cooling system should be designed well with a cryocooler and coolant circulation devices. The pressure of the cryostat for the SFCL should be pressurized to suppress the generation of nitrogen bubbles in quench mode of the SFCL. In this study, we tested the performance of the cooling system for the prototype 154 kV SFCL, which consist of a Stirling cryocooler, a subcooling cryostat, a pressure builder and a main cryostat for the SFCL module, to verify the design of the cooling system and the electric performance of the SFCL. The normal operation condition of the main cryostat is 71 K and 500 kPa. This paper presents tests results of the overall cooling system.

  14. Construction and test of a cryocooler-cooled low-Tc SQUID gradiometer system

    NARCIS (Netherlands)

    Rijpma, A.P.; Krooshoop, H.J.G.; Lefevere, M.W.; Leeuwen, van E.P.; Holland, H.J.; Haken, ten B.; Brake, ter H.J.M.

    2008-01-01

    A cryocooler-cooled low-Tc SQUID gradiometer system was designed and constructed. It is based on a 4 K GM-cooler that is positioned several meters from the measuring head containing the SQUID sensors. The cooling power is transported by means of a circulating helium flow. Thus, there are three main

  15. Improvements on cool gas generators and their application in space propulsion systems

    NARCIS (Netherlands)

    Sanders, H.M.; Schuurbiers, C.A.H.; Vandeberg, R.J.

    2014-01-01

    Cool Gas Generators are an innovative means to store gas which can be used in propulsion and pressurization systems but also for inflatable structures and terrestrial applications. In Cool Gas Generators, the gas is stored chemically, without pressure or leakage and with a long life time without mai

  16. Applicability of a desiccant dew-point cooling system independent of external water sources

    DEFF Research Database (Denmark)

    Bellemo, Lorenzo; Elmegaard, Brian; Kærn, Martin Ryhl

    2015-01-01

    The applicability of a technical solution for making desiccant cooling systems independent of external water sources is investigated. Water is produced by condensing the desorbed water vapour in a closed regeneration circuit. Desorbed water recovery is applied to a desiccant dew-point cooling...

  17. Greenhouse with an Integrated NIR Filter and a Solar Cooling System

    NARCIS (Netherlands)

    Sonneveld, P.J.; Swinkels, G.L.A.M.; Kempkes, F.L.K.; Campen, J.B.; Bot, G.P.A.

    2006-01-01

    The scope of this paper is a new greenhouse design that incorporates both a filter for rejecting near infrared radiation (NIR) and a solar cooling system. Cooled greenhouses are an important issue for the combination of high global radiation and high outdoor temperatures. As a first measure, this st

  18. Ground-Coupled Heating-Cooling Systems in Urban Areas: How Sustainable Are They?

    Science.gov (United States)

    Younger, Paul L.

    2008-01-01

    Ground-coupled heating-cooling systems (GCHCSs) exchange heat between the built environment and the subsurface using pipework buried in trenches or boreholes. If heat pumps in GCHCSs are powered by "green electricity," they offer genuine carbon-free heating-cooling; for this reason, there has been a surge in the technology in recent…

  19. Cooling Systems Design in Hot Stamping Tools by a Thermal-Fluid-Mechanical Coupled Approach

    Directory of Open Access Journals (Sweden)

    Tao Lin

    2014-06-01

    Full Text Available Hot stamping tools with cooling systems are the key facilities for hot stamping process of Ultrahigh strength steels (UHSS in automotive industry. Hot stamping tools have significant influence on the final microstructure and properties of the hot stamped parts. In serials production, the tools should be rapidly cooled by cooling water. Hence, design of hot stamping tools with cooling systems is important not only for workpieces of good quality but also for the tools with good cooling performance and long life. In this paper, a new multifield simulation method was proposed for the design of hot stamping tools with cooling system. The deformation of the tools was also analyzed by this method. Based on MpCCI (Mesh-based parallel Code Coupling Interface, thermal-fluid simulation and thermal-fluid-mechanical coupled simulation were performed. Subsequently, the geometrical parameters of the cooling system are investigated for the design. The results show that, both the distance between the ducts and the distance between the ducts and the tools loaded contour have significant influence on the quenching effect. And better quenching effect can be achieved with the shorter distance from the tool surface and with smaller distance between ducts. It is also shown that, thermal expansion is the main reason for deformation of the hot forming tools, which causes the distortion of the cooling ducts, and the stress concentration at corner of the ducts.

  20. Cooling Performance Characteristics on Mobile Air-Conditioning System for Hybrid Electric Vehicles

    Directory of Open Access Journals (Sweden)

    Ho-Seong Lee

    2013-01-01

    Full Text Available This study investigates the cooling performance characteristics of the mobile air-conditioning system using R744 (CO2 for the hybrid electric vehicle as an alternative to both the R-134a and the conventional air-conditioning system. The developed air-conditioning system is operated with an electric driven compressor in the battery driving mode and a belt driven compressor in the engine driving mode. The cooling performance characteristics of the developed system have been analyzed by experiments under various operating conditions of inlet air temperature, air flow rates for the gas cooler side and evaporator side, and electric compressor revolution respectively. As a result, cooling performances of the tested air-conditioning system for the EDC driving mode (electricity driven compressor were better than those for the BDC driving mode (belt driven compressor. The cooling capacity and cooling COP of the tested air-conditioning system for both driving modes were over 5.0 kW and 2.0, respectively. The observed cooling performance of the tested air-conditioning system may be sufficient for the cabin cooling of hybrid electric vehicles.