  1. The Evaluation Method of the Lightning Strike on Transmission Lines Aiming at Power Grid Reliability

    Science.gov (United States)

    Wen, Jianfeng; Wu, Jianwei; Huang, Liandong; Geng, Yinan; Yu, zhanqing

    2018-01-01

    Lightning protection of power system focuses on reducing the flashover rate, only distinguishing by the voltage level, without considering the functional differences between the transmission lines, and being lack of analysis the effect on the reliability of power grid. This will lead lightning protection design of general transmission lines is surplus but insufficient for key lines. In order to solve this problem, the analysis method of lightning striking on transmission lines for power grid reliability is given. Full wave process theory is used to analyze the lightning back striking; the leader propagation model is used to describe the process of shielding failure of transmission lines. The index of power grid reliability is introduced and the effect of transmission line fault on the reliability of power system is discussed in detail.

  2. Transmission grid security

    CERN Document Server

    Haarla, Liisa; Hirvonen, Ritva; Labeau, Pierre-Etienne

    2011-01-01

    In response to the growing importance of power system security and reliability, ""Transmission Grid Security"" proposes a systematic and probabilistic approach for transmission grid security analysis. The analysis presented uses probabilistic safety assessment (PSA) and takes into account the power system dynamics after severe faults. In the method shown in this book the power system states (stable, not stable, system breakdown, etc.) are connected with the substation reliability model. In this way it is possible to: estimate the system-wide consequences of grid faults; identify a chain of eve

  3. Incentives for an adequate, economic and reliable Swiss transmission grid. Final version

    International Nuclear Information System (INIS)

    Twomey, P.; Neuhoff, K.; Newbery, D.

    2006-11-01

    This comprehensive final report for the Swiss Federal Office of Energy (SFOE) discusses incentives necessary for the implementation of an adequate, economic and reliable Swiss electricity transmission grid. As Switzerland moves towards a more liberalised and competitive electricity market, an essential task of policy makers will be to ensure that incentives are in place for the construction, maintenance and operation of adequate, economic and reliable transmission infrastructure. As well as continuing to serve the domestic market, the location of Switzerland at the centre of Europe also means that policy should embrace opportunities in servicing the developing European Internal Market by providing transit and other services. Topics discussed include the economic evaluation of transmission investment proposals, regulated transmission investment, investments in transmission lines by power merchants, power auctions and congestion management as well as inter-TSO compensation mechanisms. European regulations and practice are discussed as are access questions and transmission charges. Developments in interconnection management and harmonisation are examined. The particular characteristics of the Swiss energy system, its prices and its legal frameworks are discussed. Cross-border trading and security of supply are also discussed

  4. Incentives for an adequate, economic and reliable Swiss transmission grid. Final version

    Energy Technology Data Exchange (ETDEWEB)

    Twomey, P.; Neuhoff, K.; Newbery, D.

    2006-11-15

    This comprehensive final report for the Swiss Federal Office of Energy (SFOE) discusses incentives necessary for the implementation of an adequate, economic and reliable Swiss electricity transmission grid. As Switzerland moves towards a more liberalised and competitive electricity market, an essential task of policy makers will be to ensure that incentives are in place for the construction, maintenance and operation of adequate, economic and reliable transmission infrastructure. As well as continuing to serve the domestic market, the location of Switzerland at the centre of Europe also means that policy should embrace opportunities in servicing the developing European Internal Market by providing transit and other services. Topics discussed include the economic evaluation of transmission investment proposals, regulated transmission investment, investments in transmission lines by power merchants, power auctions and congestion management as well as inter-TSO compensation mechanisms. European regulations and practice are discussed as are access questions and transmission charges. Developments in interconnection management and harmonisation are examined. The particular characteristics of the Swiss energy system, its prices and its legal frameworks are discussed. Cross-border trading and security of supply are also discussed

  5. Improving the north-American transmission grid: balancing out reliability and profitability

    International Nuclear Information System (INIS)

    Lewis, S.

    2004-01-01

    This paper gives an overview of the transmission assets owned by the Northeast Transmission National Grid in the USA. The national Grid is one of the largest transmission and distribution network in the New England/New York region. The focus of the National Grid is ownership, development, operation and maintenance of energy delivery networks (electricity and gas) under performance based regulation. The paper outlines the reasons why the investment in the USA. has lagged behind that in the U.K. Finally, the National Grid has created a number of tasks to be implemented based on the outages in the summer of 2003

  6. Maui Smart Grid Demonstration Project Managing Distribution System Resources for Improved Service Quality and Reliability, Transmission Congestion Relief, and Grid Support Functions

    Energy Technology Data Exchange (ETDEWEB)

    none,

    2014-09-30

    The Maui Smart Grid Project (MSGP) is under the leadership of the Hawaii Natural Energy Institute (HNEI) of the University of Hawaii at Manoa. The project team includes Maui Electric Company, Ltd. (MECO), Hawaiian Electric Company, Inc. (HECO), Sentech (a division of SRA International, Inc.), Silver Spring Networks (SSN), Alstom Grid, Maui Economic Development Board (MEDB), University of Hawaii-Maui College (UHMC), and the County of Maui. MSGP was supported by the U.S. Department of Energy (DOE) under Cooperative Agreement Number DE-FC26-08NT02871, with approximately 50% co-funding supplied by MECO. The project was designed to develop and demonstrate an integrated monitoring, communications, database, applications, and decision support solution that aggregates renewable energy (RE), other distributed generation (DG), energy storage, and demand response technologies in a distribution system to achieve both distribution and transmission-level benefits. The application of these new technologies and procedures will increase MECO’s visibility into system conditions, with the expected benefits of enabling more renewable energy resources to be integrated into the grid, improving service quality, increasing overall reliability of the power system, and ultimately reducing costs to both MECO and its customers.

  7. Transmission Integration | Grid Modernization | NREL

    Science.gov (United States)

    Transmission Integration Transmission Integration The goal of NREL's transmission integration integration issues and provide data, analysis, and models to enable the electric power system to more and finding solutions to address them to enable transmission grid integration. Capabilities Power

  8. National transmission grid study

    Energy Technology Data Exchange (ETDEWEB)

    Abraham, Spencer [USDOE Office of the Secretary of Energy, Washington, DC (United States)

    2003-05-31

    The National Energy Policy Plan directed the U.S. Department of Energy (DOE) to conduct a study to examine the benefits of establishing a national electricity transmission grid and to identify transmission bottlenecks and measures to address them. DOE began by conducting an independent analysis of U.S. electricity markets and identifying transmission system bottlenecks using DOE’s Policy Office Electricity Modeling System (POEMS). DOE’s analysis, presented in Section 2, confirms the central role of the nation’s transmission system in lowering costs to consumers through increased trade. More importantly, DOE’s analysis also confirms the results of previous studies, which show that transmission bottlenecks and related transmission system market practices are adding hundreds of millions of dollars to consumers’ electricity bills each year. A more detailed technical overview of the use of POEMS is provided in Appendix A. DOE led an extensive, open, public input process and heard a wide range of comments and recommendations that have all been considered.1 More than 150 participants registered for three public workshops held in Detroit, MI (September 24, 2001); Atlanta, GA (September 26, 2001); and Phoenix, AZ (September 28, 2001).

  9. Macedonian transmission grid capability and development

    International Nuclear Information System (INIS)

    Naumoski, K.; Achkoska, E.; Paunoski, A.

    2015-01-01

    The main task of the transmission grid is to guarantee evacuation of electricity from production facilities and, at the same time, supply the electricity to all customers, in a secure, reliable and qualitative manner. During the last years, transmission grid goes through the period of fast and important development, as a result of implementation of renewable and new technologies and creation of internal European electricity market. Due to these reasons, capacity of the existing grid needs to be upgraded either with optimization of existing infrastructure or constructing the new transmission projects. Among the various solutions for strengthening the grid, the one with the minimal investment expenses for construction is selected. While planning the national transmission grid, MEPSO planners apply multi-scenarios analyses, in order to handle all uncertainties, particularly in the forecasts on loads, production and exchange of electricity, location and size of the new power plants, hydrological conditions, integration of renewable sources and the evolution of the electricity market. Visions for development of European transmission grid are also considered. Special attention in the development plan is paid to modelling of power systems in the region of South-Eastern Europe and covering a wider area of the regional transmission grid with simulations of various market transactions. Macedonian transmission grid is developed to satisfy all requirements for electricity production/supply and transits, irrespective which scenario will be realized on long-term basis. Transmission development plan gives the road map for grid evolution from short-term and mid-term period towards long-term horizons (15-20 years ahead). While creating long-term visions, a big challenge in front of transmission planners is implementation of NPP. The paper gives overview of the planning process of Macedonian transmission grid,comprising: definition of scenarios,planning methodology and assessment of

  10. Reliability evaluation of smart distribution grids

    OpenAIRE

    Kazemi, Shahram

    2011-01-01

    The term "Smart Grid" generally refers to a power grid equipped with the advanced technologies dedicated for purposes such as reliability improvement, ease of control and management, integrating of distributed energy resources and electricity market operations. Improving the reliability of electric power delivered to the end users is one of the main targets of employing smart grid technologies. The smart grid investments targeted for reliability improvement can be directed toward the generati...

  11. Transmission reliability faces future challenges

    International Nuclear Information System (INIS)

    Beaty, W.

    1993-01-01

    The recently published Washington International Energy Group's 1993 Electric Utility Outlook states that nearly one-third (31 percent) of U.S. utility executives expect reliability to decrease in the near future. Electric power system stability is crucial to reliability. Stability analysis determines whether a system will stay intact under normal operating conditions, during minor disturbances such as load fluctuations, and during major disturbances when one or more parts of the system fails. All system elements contribute to reliability or the lack of it. However, this report centers on the transmission segment of the electric system. The North American Electric Reliability Council (NERC) says the transmission systems as planned will be adequate over the next 10 years. However, delays in building new lines and increasing demands for transmission services are serious concerns. Reliability concerns exist in the Mid-Continent Area Power Pool and the Mid-America Interconnected Network regions where transmission facilities have not been allowed to be constructed as planned. Portions of the transmission systems in other regions are loaded at or near their limits. NERC further states that utilities must be allowed to complete planned generation and transmission as scheduled. A reliable supply of electricity also depends on adhering to established operating criteria. Factors that could complicate operations include: More interchange schedules resulting from increased transmission services. Increased line loadings in portions of the transmission systems. Proliferation of non-utility generators

  12. Real Time Grid Reliability Management 2005

    Energy Technology Data Exchange (ETDEWEB)

    Eto, Joe; Eto, Joe; Lesieutre, Bernard; Lewis, Nancy Jo; Parashar, Manu

    2008-07-07

    The increased need to manage California?s electricity grid in real time is a result of the ongoing transition from a system operated by vertically-integrated utilities serving native loads to one operated by an independent system operator supporting competitive energy markets. During this transition period, the traditional approach to reliability management -- construction of new transmission lines -- has not been pursued due to unresolved issues related to the financing and recovery of transmission project costs. In the absence of investments in new transmission infrastructure, the best strategy for managing reliability is to equip system operators with better real-time information about actual operating margins so that they can better understand and manage the risk of operating closer to the edge. A companion strategy is to address known deficiencies in offline modeling tools that are needed to ground the use of improved real-time tools. This project: (1) developed and conducted first-ever demonstrations of two prototype real-time software tools for voltage security assessment and phasor monitoring; and (2) prepared a scoping study on improving load and generator response models. Additional funding through two separate subsequent work authorizations has already been provided to build upon the work initiated in this project.

  13. Contract networks for competition in transmission grids

    International Nuclear Information System (INIS)

    Hogan, W.W.

    1992-01-01

    Increased reliance on competition in energy markets requires pricing, access, and investment reform for the essential transmission grids. Due to the complexity of the network interactions, the usual analogies to economic concepts from other settings have little or no meaning in transmission grids. A contract network framework builds from first principles to define the conditions of an efficient market. 8 refs

  14. Power grid reliability and security

    Energy Technology Data Exchange (ETDEWEB)

    Bose, Anjan [Washington State Univ., Pullman, WA (United States); Venkatasubramanian, Vaithianathan [Washington State Univ., Pullman, WA (United States); Hauser, Carl [Washington State Univ., Pullman, WA (United States); Bakken, David [Washington State Univ., Pullman, WA (United States); Anderson, David [Washington State Univ., Pullman, WA (United States); Zhao, Chuanlin [Washington State Univ., Pullman, WA (United States); Liu, Dong [Washington State Univ., Pullman, WA (United States); Yang, Tao [Washington State Univ., Pullman, WA (United States); Meng, Ming [Washington State Univ., Pullman, WA (United States); Zhang, Lin [Washington State Univ., Pullman, WA (United States); Ning, Jiawei [Washington State Univ., Pullman, WA (United States); Tashman, Zaid [Washington State Univ., Pullman, WA (United States)

    2015-01-31

    This project has led to the development of a real-time simulation platform for electric power grids called Grid Simulator or GridSim for simulating the dynamic and information network interactions of large- scale power systems. The platform consists of physical models of power system components including synchronous generators, loads and control, which are simulated using a modified commercial power simulator namely Transient Stability Analysis Tool (TSAT) [1] together with data cleanup components, as well as an emulated substation level and wide-area power analysis components. The platform also includes realistic representations of communication network middleware that can emulate the real-time information flow back and forth between substations and control centers in wide-area power systems. The platform has been validated on a realistic 6000-bus model of the western American power system. The simulator GridSim developed in this project is the first of its kind in its ability to simulate real-time response of large-scale power grids, and serves as a cost effective real-time stability and control simulation platform for power industry.

  15. Smart Transmission Grids - Benefits and Risks

    Directory of Open Access Journals (Sweden)

    Velasco-Ramírez E.

    2013-01-01

    Full Text Available Nowadays the Power Systems are working near their stability limits, for this reason it is necessary and essential a transition to new transmission systems that ensure efficient delivery of electrical energy, with the objective to prevent “blackouts” that causesignificant losses in the economy of any country in the world. This paper analyzes important elements to consider having a healthy and efficient transition from a power grid vertically integrated into a smart transmission grid. A comparative analysis in the model, development, benefits and risks of the implementation of these systems, between two of the main marc of references of smart grids, the EU and the USA is presented.

  16. Reliability analysis in interdependent smart grid systems

    Science.gov (United States)

    Peng, Hao; Kan, Zhe; Zhao, Dandan; Han, Jianmin; Lu, Jianfeng; Hu, Zhaolong

    2018-06-01

    Complex network theory is a useful way to study many real complex systems. In this paper, a reliability analysis model based on complex network theory is introduced in interdependent smart grid systems. In this paper, we focus on understanding the structure of smart grid systems and studying the underlying network model, their interactions, and relationships and how cascading failures occur in the interdependent smart grid systems. We propose a practical model for interdependent smart grid systems using complex theory. Besides, based on percolation theory, we also study the effect of cascading failures effect and reveal detailed mathematical analysis of failure propagation in such systems. We analyze the reliability of our proposed model caused by random attacks or failures by calculating the size of giant functioning components in interdependent smart grid systems. Our simulation results also show that there exists a threshold for the proportion of faulty nodes, beyond which the smart grid systems collapse. Also we determine the critical values for different system parameters. In this way, the reliability analysis model based on complex network theory can be effectively utilized for anti-attack and protection purposes in interdependent smart grid systems.

  17. BC Transmission Corporation : working towards a smarter grid

    Energy Technology Data Exchange (ETDEWEB)

    Morison, K. [British Columbia Transmission Corp., Vancouver, BC (Canada)

    2009-07-01

    This presentation discussed smart grid initiatives implemented as part of the British Columbia Transmission Corporation's (BCTC) transmission technology roadmap. The BCTC system is comprised of 18,000 km of transmission lines with 292 stations and 2 system control centers. BCTC is now aiming to maximize transfer capability and plan transmission system expansions for electricity security and increased capacity. BCTC's smart grid program was also designed to address emerging concerns over sustainability and the environmental impacts of electricity generation. The smart grid program will reduce system congestion, enable the integration of renewable energy, and be used as part of a broader risk assessment strategy. The program includes the use of power electronics, advanced composites and nano-materials, and field work robotics. Advance control centre technologies and synchrophasors will be used to enable wide area control and security assessment. BCTC's other smart grid initiatives include the use of smart equipment monitoring and remote sensing technologies. It was concluded that information and grid-based technologies will increase the efficiency, reliability, and flexibility of the electricity delivery infrastructure. tabs., figs.

  18. Assessment of grid optimisation measures for the German transmission grid using open source grid data

    Science.gov (United States)

    Böing, F.; Murmann, A.; Pellinger, C.; Bruckmeier, A.; Kern, T.; Mongin, T.

    2018-02-01

    The expansion of capacities in the German transmission grid is a necessity for further integration of renewable energy sources into the electricity sector. In this paper, the grid optimisation measures ‘Overhead Line Monitoring’, ‘Power-to-Heat’ and ‘Demand Response in the Industry’ are evaluated and compared against conventional grid expansion for the year 2030. Initially, the methodical approach of the simulation model is presented and detailed descriptions of the grid model and the used grid data, which partly originates from open-source platforms, are provided. Further, this paper explains how ‘Curtailment’ and ‘Redispatch’ can be reduced by implementing grid optimisation measures and how the depreciation of economic costs can be determined considering construction costs. The developed simulations show that the conventional grid expansion is more efficient and implies more grid relieving effects than the evaluated grid optimisation measures.

  19. Distribution System Reliability Analysis for Smart Grid Applications

    Science.gov (United States)

    Aljohani, Tawfiq Masad

    Reliability of power systems is a key aspect in modern power system planning, design, and operation. The ascendance of the smart grid concept has provided high hopes of developing an intelligent network that is capable of being a self-healing grid, offering the ability to overcome the interruption problems that face the utility and cost it tens of millions in repair and loss. To address its reliability concerns, the power utilities and interested parties have spent extensive amount of time and effort to analyze and study the reliability of the generation and transmission sectors of the power grid. Only recently has attention shifted to be focused on improving the reliability of the distribution network, the connection joint between the power providers and the consumers where most of the electricity problems occur. In this work, we will examine the effect of the smart grid applications in improving the reliability of the power distribution networks. The test system used in conducting this thesis is the IEEE 34 node test feeder, released in 2003 by the Distribution System Analysis Subcommittee of the IEEE Power Engineering Society. The objective is to analyze the feeder for the optimal placement of the automatic switching devices and quantify their proper installation based on the performance of the distribution system. The measures will be the changes in the reliability system indices including SAIDI, SAIFI, and EUE. The goal is to design and simulate the effect of the installation of the Distributed Generators (DGs) on the utility's distribution system and measure the potential improvement of its reliability. The software used in this work is DISREL, which is intelligent power distribution software that is developed by General Reliability Co.

  20. Sensor Transmission Power Schedule for Smart Grids

    Science.gov (United States)

    Gao, C.; Huang, Y. H.; Li, J.; Liu, X. D.

    2017-11-01

    Smart grid has attracted much attention by the requirement of new generation renewable energy. Nowadays, the real-time state estimation, with the help of phasor measurement unit, plays an important role to keep smart grid stable and efficient. However, the limitation of the communication channel is not considered by related work. Considering the familiar limited on-board batteries wireless sensor in smart grid, transmission power schedule is designed in this paper, which minimizes energy consumption with proper EKF filtering performance requirement constrain. Based on the event-triggered estimation theory, the filtering algorithm is also provided to utilize the information contained in the power schedule. Finally, its feasibility and performance is demonstrated using the standard IEEE 39-bus system with phasor measurement units (PMUs).

  1. Column Grid Array Rework for High Reliability

    Science.gov (United States)

    Mehta, Atul C.; Bodie, Charles C.

    2008-01-01

    Due to requirements for reduced size and weight, use of grid array packages in space applications has become common place. To meet the requirement of high reliability and high number of I/Os, ceramic column grid array packages (CCGA) were selected for major electronic components used in next MARS Rover mission (specifically high density Field Programmable Gate Arrays). ABSTRACT The probability of removal and replacement of these devices on the actual flight printed wiring board assemblies is deemed to be very high because of last minute discoveries in final test which will dictate changes in the firmware. The questions and challenges presented to the manufacturing organizations engaged in the production of high reliability electronic assemblies are, Is the reliability of the PWBA adversely affected by rework (removal and replacement) of the CGA package? and How many times can we rework the same board without destroying a pad or degrading the lifetime of the assembly? To answer these questions, the most complex printed wiring board assembly used by the project was chosen to be used as the test vehicle, the PWB was modified to provide a daisy chain pattern, and a number of bare PWB s were acquired to this modified design. Non-functional 624 pin CGA packages with internal daisy chained matching the pattern on the PWB were procured. The combination of the modified PWB and the daisy chained packages enables continuity measurements of every soldered contact during subsequent testing and thermal cycling. Several test vehicles boards were assembled, reworked and then thermal cycled to assess the reliability of the solder joints and board material including pads and traces near the CGA. The details of rework process and results of thermal cycling are presented in this paper.

  2. Grid Transmission Expansion Planning Model Based on Grid Vulnerability

    Science.gov (United States)

    Tang, Quan; Wang, Xi; Li, Ting; Zhang, Quanming; Zhang, Hongli; Li, Huaqiang

    2018-03-01

    Based on grid vulnerability and uniformity theory, proposed global network structure and state vulnerability factor model used to measure different grid models. established a multi-objective power grid planning model which considering the global power network vulnerability, economy and grid security constraint. Using improved chaos crossover and mutation genetic algorithm to optimize the optimal plan. For the problem of multi-objective optimization, dimension is not uniform, the weight is not easy given. Using principal component analysis (PCA) method to comprehensive assessment of the population every generation, make the results more objective and credible assessment. the feasibility and effectiveness of the proposed model are validated by simulation results of Garver-6 bus system and Garver-18 bus.

  3. Reliability analysis of reinforced concrete grids with nonlinear material behavior

    Energy Technology Data Exchange (ETDEWEB)

    Neves, Rodrigo A [EESC-USP, Av. Trabalhador Sao Carlense, 400, 13566-590 Sao Carlos (Brazil); Chateauneuf, Alaa [LaMI-UBP and IFMA, Campus de Clermont-Fd, Les Cezeaux, BP 265, 63175 Aubiere cedex (France)]. E-mail: alaa.chateauneuf@ifma.fr; Venturini, Wilson S [EESC-USP, Av. Trabalhador Sao Carlense, 400, 13566-590 Sao Carlos (Brazil)]. E-mail: venturin@sc.usp.br; Lemaire, Maurice [LaMI-UBP and IFMA, Campus de Clermont-Fd, Les Cezeaux, BP 265, 63175 Aubiere cedex (France)

    2006-06-15

    Reinforced concrete grids are usually used to support large floor slabs. These grids are characterized by a great number of critical cross-sections, where the overall failure is usually sudden. However, nonlinear behavior of concrete leads to the redistribution of internal forces and accurate reliability assessment becomes mandatory. This paper presents a reliability study on reinforced concrete (RC) grids based on coupling Monte Carlo simulations with the response surface techniques. This approach allows us to analyze real RC grids with large number of failure components. The response surface is used to evaluate the structural safety by using first order reliability methods. The application to simple grids shows the interest of the proposed method and the role of moment redistribution in the reliability assessment.

  4. Reliability analysis of HVDC grid combined with power flow simulations

    Energy Technology Data Exchange (ETDEWEB)

    Yang, Yongtao; Langeland, Tore; Solvik, Johan [DNV AS, Hoevik (Norway); Stewart, Emma [DNV KEMA, Camino Ramon, CA (United States)

    2012-07-01

    Based on a DC grid power flow solver and the proposed GEIR, we carried out reliability analysis for a HVDC grid test system proposed by CIGRE working group B4-58, where the failure statistics are collected from literature survey. The proposed methodology is used to evaluate the impact of converter configuration on the overall reliability performance of the HVDC grid, where the symmetrical monopole configuration is compared with the bipole with metallic return wire configuration. The results quantify the improvement on reliability by using the later alternative. (orig.)

  5. Composite reliability evaluation for transmission network planning

    Directory of Open Access Journals (Sweden)

    Jiashen Teh

    2018-01-01

    Full Text Available As the penetration of wind power into the power system increases, the ability to assess the reliability impact of such interaction becomes more important. The composite reliability evaluations involving wind energy provide ample opportunities for assessing the benefits of different wind farm connection points. A connection to the weak area of the transmission network will require network reinforcement for absorbing the additional wind energy. Traditionally, the reinforcements are performed by constructing new transmission corridors. However, a new state-of-art technology such as the dynamic thermal rating (DTR system, provides new reinforcement strategy and this requires new reliability assessment method. This paper demonstrates a methodology for assessing the cost and the reliability of network reinforcement strategies by considering the DTR systems when large scale wind farms are connected to the existing power network. Sequential Monte Carlo simulations were performed and all DTRs and wind speed were simulated using the auto-regressive moving average (ARMA model. Various reinforcement strategies were assessed from their cost and reliability aspects. Practical industrial standards are used as guidelines when assessing costs. Due to this, the proposed methodology in this paper is able to determine the optimal reinforcement strategies when both the cost and reliability requirements are considered.

  6. Managing relationships between electric power industry restructuring and grid reliability

    International Nuclear Information System (INIS)

    Thomas, R.J.

    2005-01-01

    The electricity system is a critical infrastructure, and its continued and reliable functioning is essential to the nation's economy and well-being. However, the inter-dependency of electricity networks is not completely understood. The economic impact of outages was discussed in this white paper. It was suggested that moving to a restructured environment has degraded the reliability of the bulk system. New institutional arrangements and approaches to information management are needed. It was suggested that reliability practices caused the 2003 blackout, and not technical failures. Uncertainties in the restructured market were discussed, as well as incentives to maintain system adequacy. Examples of deregulation in other countries were presented. Organizational complexities were reviewed, including the Federal Energy Regulatory Commission's (FERC) requirements and the new layers of complexity that have been added to the decision-making process in the light of restructuring. Planning and connectivity issues were reviewed. The need for design standards in power grid control centres was discussed. Difficulties in collecting data from different control centres were considered. Issues concerning the lack of investment in research and development were discussed, with particular reference to the urgent need for coordinated research programs. The looming manpower crisis in the electric power industry was also discussed. Recommendations included ensuring that the transmission system can support a market structure; building a national reliability centre; solving the manpower crisis; and testing market designs before deploying them. It was concluded that good engineering design principles, including experimental economic testing, should be required of any new electricity market design before authorizing its use. 31 refs., 1 tab., 6 figs

  7. Reliability Oriented Design of a Grid-Connected Photovoltaic Microinverter

    DEFF Research Database (Denmark)

    Shen, Yanfeng; Wang, Huai; Blaabjerg, Frede

    2017-01-01

    High reliability performance of microinverters in Photovoltaic (PV) systems is a merit to match lifetime with PV panels, and to reduce the required maintenance efforts and costs. This digest applies a reliability oriented design method for a grid-connected PV microinverter to achieve specific...

  8. Evaluation of Reliability Parameters in Micro-grid

    Directory of Open Access Journals (Sweden)

    H. Hasanzadeh Fard

    2015-06-01

    Full Text Available Evaluation of the reliability parameters in micro-grids based on renewable energy sources is one of the main problems that are investigated in this paper. Renewable energy sources such as solar and wind energy, battery as an energy storage system and fuel cell as a backup system are used to provide power to the electrical loads of the micro-grid. Loads in the micro-grid consist of interruptible and uninterruptible loads. In addition to the reliability parameters, Forced Outage Rate of each component and also uncertainty of wind power, PV power and demand are considered for micro-grid. In this paper, the problem is formulated as a nonlinear integer minimization problem which minimizes the sum of the total capital, operational, maintenance and replacement cost of DERs. This paper proposes PSO for solving this minimization problem.

  9. High voltage direct current transmission converters, systems and DC grids

    CERN Document Server

    Jovcic, Dragan

    2015-01-01

    This comprehensive reference guides the reader through all HVDC technologies, including LCC (Line Commutated Converter), 2-level VSC and VSC HVDC based on modular multilevel converters (MMC) for an in-depth understanding of converters, system level design, operating principles and modeling. Written in a tutorial style, the book also describes the key principles of design, control, protection and operation of DC transmission grids, which will be substantially different from the practice with AC transmission grids. The first dedicated reference to the latest HVDC technologies and DC grid developments; this is an essential resource for graduate students and researchers as well as engineers and professionals working on the design, modeling and operation of DC grids and HVDC.

  10. Reliability analysis of grid connected small wind turbine power electronics

    International Nuclear Information System (INIS)

    Arifujjaman, Md.; Iqbal, M.T.; Quaicoe, J.E.

    2009-01-01

    Grid connection of small permanent magnet generator (PMG) based wind turbines requires a power conditioning system comprising a bridge rectifier, a dc-dc converter and a grid-tie inverter. This work presents a reliability analysis and an identification of the least reliable component of the power conditioning system of such grid connection arrangements. Reliability of the configuration is analyzed for the worst case scenario of maximum conversion losses at a particular wind speed. The analysis reveals that the reliability of the power conditioning system of such PMG based wind turbines is fairly low and it reduces to 84% of initial value within one year. The investigation is further enhanced by identifying the least reliable component within the power conditioning system and found that the inverter has the dominant effect on the system reliability, while the dc-dc converter has the least significant effect. The reliability analysis demonstrates that a permanent magnet generator based wind energy conversion system is not the best option from the point of view of power conditioning system reliability. The analysis also reveals that new research is required to determine a robust power electronics configuration for small wind turbine conversion systems.

  11. Impact of Considering 110 kV Grid Structures on the Congestion Management in the German Transmission Grid

    Science.gov (United States)

    Hoffrichter, André; Barrios, Hans; Massmann, Janek; Venkataramanachar, Bhavasagar; Schnettler, Armin

    2018-02-01

    The structural changes in the European energy system lead to an increase of renewable energy sources that are primarily connected to the distribution grid. Hence the stationary analysis of the transmission grid and the regionalization of generation capacities are strongly influenced by subordinate grid structures. To quantify the impact on the congestion management in the German transmission grid, a 110 kV grid model is derived using publicly available data delivered by Open Street Map and integrated into an existing model of the European transmission grid. Power flow and redispatch simulations are performed for three different regionalization methods and grid configurations. The results show a significant impact of the 110 kV system and prove an overestimation of power flows in the transmission grid when neglecting subordinate grids. Thus, the redispatch volume in Germany to dissolve bottlenecks in case of N-1 contingencies decreases by 38 % when considering the 110 kV grid.

  12. Integration of new nuclear power plants into transmission grids part I: Transmission system issues

    International Nuclear Information System (INIS)

    Abi-Samra, N.

    2008-01-01

    Integration of new nuclear plants into a transmission system is a two sided problem. On one side, adding the nuclear plant into an existing grid will change the attributes of that grid: e.g., loading of certain transmission lines will increase; voltages will be affected, etc. On the other side, the grid itself will affect the plant, and the plant needs to be designed to accommodate the specifics of the grid. Based on that, this paper is divided into two parts. Part I addresses the grid issues with the integration of the new plant, with emphasis on the electrical aspects of these issues. Part II of this paper, concentrates on the vulnerability of the plant from grid disturbances. Part II reintroduces a relatively new concept by this author called the Zone of Vulnerability (ZoV) for the new nuclear plants. (authors)

  13. 75 FR 14386 - Interpretation of Transmission Planning Reliability Standard

    Science.gov (United States)

    2010-03-25

    ...] Interpretation of Transmission Planning Reliability Standard March 18, 2010. AGENCY: Federal Energy Regulatory... transmission planning Reliability Standard TPL-002-0 provides that planning authorities and transmission... Reliability Standard TPL-002-0. In this order, the Commission proposes to reject NERC's proposed...

  14. Use of FACTS for enhanced flexibility and efficiency in power transmission and distribution grids

    Energy Technology Data Exchange (ETDEWEB)

    Grunbaum, Rolf; Wahlberg, Conny; Sannino, Ambra

    2010-09-15

    The paper shows how the use of FACTS increases flexibility in power transmission and distribution, improving capacity of transmission corridors to integrate renewable power production. Examples included are 69 kV directly connected SVCs for grid stabilization in conjunction with a high degree of wind power penetration; series compensation to evacuate power from the largest wind power installation in USA; SVC to increase the reliability and reduce congestion over a heavily loaded power corridor; thyristor controlled series compensation to increase the dynamic stability and power transmission capability of a power inter-connector. Finally, some applications of Dynamic energy storage are highlighted.

  15. Electrothermal Coordination in Cable Based Transmission Grids

    DEFF Research Database (Denmark)

    Olsen, Rasmus Schmidt; Holbøll, Joachim; Gudmundsdottir, Unnur Stella

    2013-01-01

    behavior of the components. The dynamic temperature calculations of power cables are suggested to be based on thermoelectric equivalents (TEEs). It is shown that the thermal behavior can be built into widely used load flow software, creating a strong ETC tool. ETC is, through two case scenarios, proven...... to be beneficial for both operator and system planner. It is shown how the thermal behavior can be monitored in real-time during normal dynamic load and during emergencies. In that way, ETC enables cables to be loaded above their normal rating, while maintaining high reliability of the system, which potentially...

  16. Relationship between competitive power markets and grid reliability : the PJM RTO experience

    Energy Technology Data Exchange (ETDEWEB)

    Harris, P.G. [PJM Interconnection LLC, Philadelphia, PA (United States)

    2005-07-01

    PJM is one of the largest grid operators in North America, serving 51 million people. This white paper examined the causes of the 2003 blackout in relation to grid management tools, operator training and system planning and analysis. The aim of the paper was to explain how competition and regional transmission offices (RTOs) are addressing these issues and doing more to help improve reliability and strengthen the grid. It was suggested that consumer savings can be achieved while enhancing, rather than diminishing the reliability and security of the electricity system. Changes in the electricity industry were reviewed. Issues concerning the lack of data to measure grid reliability were discussed. It was suggested that key influences on grid reliability are regional dispatch and scheduling practices, as well as RTO coordination and system operator training. Security constrained unit commitment was discussed, as well as various new technologies to improve reliability, including real-time contingency analysis and generation dispatch; real time voltage analysis; and visualization technology. Applications scales and scopes were discussed, as well as issues concerning RTO coordination. Issues concerning enhanced operator information through data transfer protocols were discussed, as well as the development of enhanced reliability tools through joint operating agreements. It was suggested that regional planning and large wholesale markets support regional reliability. It was concluded that regional RTO markets have evolved to produce economic efficiency and enhanced reliability in short-term and mid-term operations, and provide transparent regional information that will assist in providing data in the future, in order to address the long-term infrastructure investment concerns that exist on a national level.

  17. 76 FR 58101 - Electric Reliability Organization Interpretation of Transmission Operations Reliability Standard

    Science.gov (United States)

    2011-09-20

    ....C. Cir. 2009). \\4\\ Mandatory Reliability Standards for the Bulk-Power System, Order No. 693, FERC... for maintaining real and reactive power balance. \\14\\ Electric Reliability Organization Interpretation...; Order No. 753] Electric Reliability Organization Interpretation of Transmission Operations Reliability...

  18. Real Time Load Optimisation of Cable Based Transmission Grids

    DEFF Research Database (Denmark)

    Olsen, Rasmus Schmidt; Holbøll, Joachim; Guðmundsdottir, Unnur Stella

    2011-01-01

    Energinet.dk has launched an investigation of dynamic current ratings of cable based transmission grids, where both internal and external parameters are variables. The first topic was to investigate state of the art within calculating the current carrying capacity (ampacity or loadability......) of cables embedded in larger cable systems. Some recently published research has been concerned with dynamic loadability, but such researches are based on many assumptions. It is shown in the paper, that only limited research has been concerned with larger cable grids, and no remarkable work could been...

  19. Evaluation of Smart Grid Technologies Employed for System Reliability Improvement: Pacific Northwest Smart Grid Demonstration Experience

    Energy Technology Data Exchange (ETDEWEB)

    Agalgaonkar, Yashodhan P.; Hammerstrom, Donald J.

    2017-06-01

    The Pacific Northwest Smart Grid Demonstration (PNWSGD) was a smart grid technology performance evaluation project that included multiple U.S. states and cooperation from multiple electric utilities in the northwest region. One of the local objectives for the project was to achieve improved distribution system reliability. Toward this end, some PNWSGD utilities automated their distribution systems, including the application of fault detection, isolation, and restoration and advanced metering infrastructure. In light of this investment, a major challenge was to establish a correlation between implementation of these smart grid technologies and actual improvements of distribution system reliability. This paper proposes using Welch’s t-test to objectively determine and quantify whether distribution system reliability is improving over time. The proposed methodology is generic, and it can be implemented by any utility after calculation of the standard reliability indices. The effectiveness of the proposed hypothesis testing approach is demonstrated through comprehensive practical results. It is believed that wider adoption of the proposed approach can help utilities to evaluate a realistic long-term performance of smart grid technologies.

  20. Offshore grid transmission planning using approximated HVDC power flows

    Energy Technology Data Exchange (ETDEWEB)

    Torbaghan, Shahab Shariat; Rawn, Barry G.; Gibescu, Madeleine; Meijden, Mart van der [Delft Univ. of Technology (Netherlands). Dept. of Electrical Sustainable Energy

    2012-07-01

    In this paper we introduce an optimization framework which determines a socially optimum design of a HVDC offshore grid, under the assumption of a centralized network expansion planning scheme. This gives the optimum grid topology and interconnections capacity. In addition, the analytical solution to the optimization problem yields a market structure that expresses the relationship between the different regions' electricity prices and congestion charges associated with the interconnections. The optimization model sets the transmission capacities in a way that congestion shadow prices to be collected by the end of the economic lifetime of the project pay off the initial investment capital. We use this framework to study the impact of exercising different dispatching policies on the optimum design of the grid. The framework is applied to a multi-bus test system that functions under 8 different time periods. (orig.)

  1. Forward Capacity Markets: Maintaining Grid Reliability in Europe

    OpenAIRE

    Chaigneau, Matthieu

    2012-01-01

    The liberalization process of the electricity industry in many countries leads to new rules and new challenges for the grid management. System reliability is a major concern, mainly because of (a) the high level penetration of renewable energy sources and (b) the growing peak load and environmental regulations In most electricity markets, peak resources operate only during a short period, and at a high operating cost, jeopardizing their return on investment, while low-cost base resources make...

  2. Cost-effective solutions to maintaining smart grid reliability

    Science.gov (United States)

    Qin, Qiu

    As the aging power systems are increasingly working closer to the capacity and thermal limits, maintaining an sufficient reliability has been of great concern to the government agency, utility companies and users. This dissertation focuses on improving the reliability of transmission and distribution systems. Based on the wide area measurements, multiple model algorithms are developed to diagnose transmission line three-phase short to ground faults in the presence of protection misoperations. The multiple model algorithms utilize the electric network dynamics to provide prompt and reliable diagnosis outcomes. Computational complexity of the diagnosis algorithm is reduced by using a two-step heuristic. The multiple model algorithm is incorporated into a hybrid simulation framework, which consist of both continuous state simulation and discrete event simulation, to study the operation of transmission systems. With hybrid simulation, line switching strategy for enhancing the tolerance to protection misoperations is studied based on the concept of security index, which involves the faulted mode probability and stability coverage. Local measurements are used to track the generator state and faulty mode probabilities are calculated in the multiple model algorithms. FACTS devices are considered as controllers for the transmission system. The placement of FACTS devices into power systems is investigated with a criterion of maintaining a prescribed level of control reconfigurability. Control reconfigurability measures the small signal combined controllability and observability of a power system with an additional requirement on fault tolerance. For the distribution systems, a hierarchical framework, including a high level recloser allocation scheme and a low level recloser placement scheme, is presented. The impacts of recloser placement on the reliability indices is analyzed. Evaluation of reliability indices in the placement process is carried out via discrete event

  3. 78 FR 63036 - Transmission Planning Reliability Standards

    Science.gov (United States)

    2013-10-23

    ... Reliability Standards for the Bulk Power System, 130 FERC ] 61,200 (2010). \\8\\ Mandatory Reliability Standards... electric system operations across normal and contingency conditions. We also find that Reliability Standard... Reliability Standards for the Bulk Power System, 131 FERC ] 61,231 at P 21. Comments 24. NERC supports the...

  4. Reliability of the grid as function of power flow and configuration during maintenance

    International Nuclear Information System (INIS)

    Kovacs, Z.; Hlavac, P.; Janicek, F.

    2012-01-01

    The paper describes using of PSA (Probabilistic Safety Assessment) for analysis of the partial and total blackout of the grid for different power flows and configuration of the grid given by the preventive maintenance activities. The method uses event and fault tree analysis in combination with the dynamic stability analysis of the grid. The event trees model the grid response to the initiating event of the accident. The fault trees are used to model the reliability of the substation protection systems. Different end states of the event trees are simulated on the basis of dynamic stability analysis, as safe and emergency state, partial and total blackout. Minimal cut sets are generated, importance measures (Fussel-Vesely importance, risk increase factor and risk decrease factors) are calculated for the total and partial blackout. The most dominant initiating events and component failures are identified from the risk point of view. Using the PSA the model, of the transmission grid is being developed. The model can be implemented into the risk monitor software to analyze the risk for different configurations of the grid and to support the operation and the maintenance activities. (Authors)

  5. Reliability Engineering for ATLAS Petascale Data Processing on the Grid

    CERN Document Server

    Golubkov, D V; The ATLAS collaboration; Vaniachine, A V

    2012-01-01

    The ATLAS detector is in its third year of continuous LHC running taking data for physics analysis. A starting point for ATLAS physics analysis is reconstruction of the raw data. First-pass processing takes place shortly after data taking, followed later by reprocessing of the raw data with updated software and calibrations to improve the quality of the reconstructed data for physics analysis. Data reprocessing involves a significant commitment of computing resources and is conducted on the Grid. The reconstruction of one petabyte of ATLAS data with 1B collision events from the LHC takes about three million core-hours. Petascale data processing on the Grid involves millions of data processing jobs. At such scales, the reprocessing must handle a continuous stream of failures. Automatic job resubmission recovers transient failures at the cost of CPU time used by the failed jobs. Orchestrating ATLAS data processing applications to ensure efficient usage of tens of thousands of CPU-cores, reliability engineering ...

  6. 77 FR 26714 - Transmission Planning Reliability Standards

    Science.gov (United States)

    2012-05-07

    ... Reliability Standards for the Bulk-Power System, Order No. 693, FERC Stats. & Regs. ] 31,242, order on reh'g... Standards for the Bulk Power System, 130 FERC ] 61,200 (2010) (March 2010 Order). \\12\\ Mandatory Reliability... excluded from future planning assessments and its potential impact to bulk electric system reliability...

  7. Maximal network reliability for a stochastic power transmission network

    International Nuclear Information System (INIS)

    Lin, Yi-Kuei; Yeh, Cheng-Ta

    2011-01-01

    Many studies regarded a power transmission network as a binary-state network and constructed it with several arcs and vertices to evaluate network reliability. In practice, the power transmission network should be stochastic because each arc (transmission line) combined with several physical lines is multistate. Network reliability is the probability that the network can transmit d units of electric power from a power plant (source) to a high voltage substation at a specific area (sink). This study focuses on searching for the optimal transmission line assignment to the power transmission network such that network reliability is maximized. A genetic algorithm based method integrating the minimal paths and the Recursive Sum of Disjoint Products is developed to solve this assignment problem. A real power transmission network is adopted to demonstrate the computational efficiency of the proposed method while comparing with the random solution generation approach.

  8. 76 FR 23222 - Electric Reliability Organization Interpretation of Transmission Operations Reliability

    Science.gov (United States)

    2011-04-26

    ....3d 1342 (DC Cir. 2009). \\5\\ Mandatory Reliability Standards for the Bulk-Power System, Order No. 693... Reliability Standards for the Bulk-Power System. Action: FERC-725A. OMB Control No.: 1902-0244. Respondents...] Electric Reliability Organization Interpretation of Transmission Operations Reliability AGENCY: Federal...

  9. 78 FR 30804 - Transmission Planning Reliability Standards

    Science.gov (United States)

    2013-05-23

    ... shedding firm load versus planning to shed firm load, while still ensuring that the decision-making process... load loss. NERC states that it developed this information to ensure that an entity adequately... adverse reliability impacts. While consumers and local communities should be able to make decisions about...

  10. Transmission embedded cost allocation methodology with consideration of system reliability

    International Nuclear Information System (INIS)

    Hur, D.; Park, J.-K.; Yoo, C.-I.; Kim, B.H.

    2004-01-01

    In a vertically integrated utility industry, the cost of reliability, as a separate service, has not received much rigorous analysis. However, as a cornerstone of restructuring the industry, the transmission service pricing must change to be consistent with, and supportive of, competitive wholesale electricity markets. This paper focuses on the equitable allocation of transmission network embedded costs including the transmission reliability cost based on the contributions of each generator to branch flows under normal conditions as well as the line outage impact factor under a variety of load levels. A numerical example on a six-bus system is given to illustrate the applications of the proposed methodology. (author)

  11. Evaluating congestion management in the Dutch electricity transmission grid

    International Nuclear Information System (INIS)

    Blijswijk, Martti J. van; Vries, Laurens J. de

    2012-01-01

    Due to the increase in electricity generation capacity in the Netherlands and a new connection policy, transmission system operator (TSO) TenneT expects a significant increase in congestion in the Dutch transmission grid. To manage this, the Dutch government implemented redispatching, a method which is argued in the literature to potentially impose large congestion costs upon the TSO. A quantitative model of the Dutch electricity system was developed in order to evaluate this method. The outcomes were compared to the performance of three alternative congestion management methods. Regardless of the method, congestion costs were found to be substantially lower than in previous studies. Because combined-cycle gas turbines are the marginal generation technology in almost all cases, the costs of up and down regulation do not differ much. Consequently, the redispatching costs for the TSO are expected to be relatively low, and the opportunities for abuse of market power appear to be limited. While all the evaluated methods are effective and economically efficient, they have significantly different welfare effects. Market splitting creates significantly larger welfare effects than the different varieties of redispatching. - Highlights: ► Congestion management was recently introduced in the Netherlands. ► We quantitatively evaluate the effects of its application. ► We compare this to other congestion management methods. ► Given the specific situation that the marginal cost curve of production is flat, congestion costs are expected to be low.

  12. Bi-directional Multi Dimension CAP Transmission for Smart Grid Communication Services

    DEFF Research Database (Denmark)

    Zhang, Xu; Binti Othman, Maisara; Pang, Xiaodan

    2012-01-01

    We experimentally demonstrate bi-directional multi dimension carrierless amplitude and phase (CAP) transmission for smart grid communication services based on optical fiber networks. The proposed system is able to support multi-Gb/s transmission with high spectral efficiency.......We experimentally demonstrate bi-directional multi dimension carrierless amplitude and phase (CAP) transmission for smart grid communication services based on optical fiber networks. The proposed system is able to support multi-Gb/s transmission with high spectral efficiency....

  13. Safety awareness educational topics for the construction of power transmission systems with smart grid technologies

    Directory of Open Access Journals (Sweden)

    Bryan Hubbard

    2013-09-01

    Full Text Available Power transmission facilities in the U.S. are undergoing a transformation due to the increased use of distributed generation sources such as wind and solar power.  The current power grid system is also antiquated and in need of substantial retrofits to make it more efficient and reliable.  The new energy transmission system being designed and built to optimize power delivery is known as “Smart Grid”.  The increased activity in the construction of power transmission facilities and installation of new technologies into the current power system raises potential safety concerns.  Existing construction management curriculum may include general information about safety training, but does not typically include information about this specialized sector.  The objective of this study was to work with industry to identify key safety topics appropriate for inclusion in an introductory industrial construction course.  Results of interviews with industry identified numerous hazards that are not typically covered in typical construction curricula.  A joint undergraduate and graduate course in industrial construction was created to address these and additional concepts. A survey of the students was performed to determine the effectiveness of the course and also to determine their thoughts about the smart grid technologies and safety training. Information on electrical system hazards is presented along with results of the student surveys.

  14. An automated method for estimating reliability of grid systems using Bayesian networks

    International Nuclear Information System (INIS)

    Doguc, Ozge; Emmanuel Ramirez-Marquez, Jose

    2012-01-01

    Grid computing has become relevant due to its applications to large-scale resource sharing, wide-area information transfer, and multi-institutional collaborating. In general, in grid computing a service requests the use of a set of resources, available in a grid, to complete certain tasks. Although analysis tools and techniques for these types of systems have been studied, grid reliability analysis is generally computation-intensive to obtain due to the complexity of the system. Moreover, conventional reliability models have some common assumptions that cannot be applied to the grid systems. Therefore, new analytical methods are needed for effective and accurate assessment of grid reliability. This study presents a new method for estimating grid service reliability, which does not require prior knowledge about the grid system structure unlike the previous studies. Moreover, the proposed method does not rely on any assumptions about the link and node failure rates. This approach is based on a data-mining algorithm, the K2, to discover the grid system structure from raw historical system data, that allows to find minimum resource spanning trees (MRST) within the grid then, uses Bayesian networks (BN) to model the MRST and estimate grid service reliability.

  15. 76 FR 44323 - National Grid Transmission Services Corporation; Bangor Hydro Electric Company; Notice of...

    Science.gov (United States)

    2011-07-25

    ... DEPARTMENT OF ENERGY Federal Energy Regulatory Commission [Docket No. EL11-49-000] National Grid Transmission Services Corporation; Bangor Hydro Electric Company; Notice of Petition for Declaratory Order Take..., 18 CFR 385.207, National Grid Transmission Services Corporation and Bangor Hydro Electric Company...

  16. 77 FR 16435 - Transmission Relay Loadability Reliability Standard

    Science.gov (United States)

    2012-03-21

    ... conditions on all applicable transmission lines and transformers. I. Background A. Relay Protection Systems 2... and a power swing. If a power swing is detected, the protection system, ``blocks,'' or prevents the... to the reliability of the Bulk-Power System by requiring load-responsive phase protection relay...

  17. Integration of wind power in Germany's transmission grid by using HVDC links

    Energy Technology Data Exchange (ETDEWEB)

    Wasserrab, Andreas; Fleckenstein, Marco; Balzer, Gerd [Technische Univ. Darmstadt (Germany). Inst. of Electrical Power and Energy

    2012-07-01

    This paper deals with the challenges for the integration of wind power in Germany's transmission grid. Several options for the expansion of transmission grids are discussed. The consideration focuses on HVDC technologies, which are used for further analyses. The basis of the analysis is the transmission grid of a German transmission system operator, which is implemented in a simulation tool. The model consists of the 110-kV-, 220-kV- and the 380-kV-system. In different scenarios the integration of wind power is analysed by applying HVDC links to connect the northern part of the grid with the load centres in the South. The results of load flow calculations are discussed focusing on transmission line loading and voltage stability. The paper concludes with future prospects of HVDC applications in Germany. (orig.)

  18. Integrating generation and transmission networks reliability for unit commitment solution

    International Nuclear Information System (INIS)

    Jalilzadeh, S.; Shayeghi, H.; Hadadian, H.

    2009-01-01

    This paper presents a new method with integration of generation and transmission networks reliability for the solution of unit commitment (UC) problem. In fact, in order to have a more accurate assessment of system reserve requirement, in addition to unavailability of generation units, unavailability of transmission lines are also taken into account. In this way, evaluation of the required spinning reserve (SR) capacity is performed by applying reliability constraints based on loss of load probability and expected energy not supplied (EENS) indices. Calculation of the above parameters is accomplished by employing a novel procedure based on the linear programming which it also minimizes them to achieve optimum level of the SR capacity and consequently a cost-benefit reliability constrained UC schedule. In addition, a powerful solution technique called 'integer-coded genetic algorithm (ICGA)' is being used for the solution of the proposed method. Numerical results on the IEEE reliability test system show that the consideration of transmission network unavailability has an important influence on reliability indices of the UC schedules

  19. Reliability Equivalence to Symmetrical UHVDC Transmission Systems Considering Redundant Structure Configuration

    Directory of Open Access Journals (Sweden)

    Xing Jiang

    2018-03-01

    Full Text Available In recent years, the ultra-high voltage direct current (UHVDC transmission system has been developed rapidly for its significant long-distance, high-capacity and low-loss properties. Equipment failures and overall outages of the UHVDC system have increasingly vital influence on the power supply of the receiving end grid. To improve the reliability level of UHVDC systems, a quantitative selection and configuration approach of redundant structures is proposed in this paper, which is based on multi-state reliability equivalence. Specifically, considering the symmetry characteristic of an UHVDC system, a state space model is established as a monopole rather than a bipole, which effectively reduces the state space dimensions to be considered by deducing the reliability merging operator of two poles. Considering the standby effect of AC filters and the recovery effect of converter units, the number of available converter units and corresponding probability are expressed with in universal generating function (UGF form. Then, a sensitivity analysis is performed to quantify the impact of component reliability parameters on system reliability and determine the most specific devices that should be configured in the redundant structure. Finally, a cost-benefit analysis is utilized to help determine the optimal scheme of redundant devices. Case studies are conducted to demonstrate the effectiveness and accuracy of the proposed method. Based on the numerical results, configuring a set of redundant transformers is indicated to be of the greatest significance to improve the reliability level of UHVDC transmission systems.

  20. Reliability analysis for the smart grid : from cyber control and communication to physical manifestations of failure.

    Science.gov (United States)

    2010-01-01

    The Smart Grid is a cyber-physical system comprised of physical components, such as transmission lines and generators, and a : network of embedded systems deployed for their cyber control. Our objective is to qualitatively and quantitatively analyze ...

  1. Reliable Grid Condition Detection and Control of Single-Phase Distributed Power Generation Systems

    DEFF Research Database (Denmark)

    Ciobotaru, Mihai

    standards addressed to the grid-connected systems will harmonize the combination of the DPGS and the classical power plants. Consequently, the major tasks of this thesis were to develop new grid condition detection techniques and intelligent control in order to allow the DPGS not only to deliver power...... to the utility grid but also to sustain it. This thesis was divided into two main parts, namely "Grid Condition Detection" and "Control of Single-Phase DPGS". In the first part, the main focus was on reliable Phase Locked Loop (PLL) techniques for monitoring the grid voltage and on grid impedance estimation...... techniques. Additionally, a new technique for detecting the islanding mode has been developed and successfully tested. In the second part, the main reported research was concentrated around adaptive current controllers based on the information provided by the grid condition detection techniques. To guarantee...

  2. Transmission Technologies and Operational Characteristic Analysis of Hybrid UHV AC/DC Power Grids in China

    Science.gov (United States)

    Tian, Zhang; Yanfeng, Gong

    2017-05-01

    In order to solve the contradiction between demand and distribution range of primary energy resource, Ultra High Voltage (UHV) power grids should be developed rapidly to meet development of energy bases and accessing of large-scale renewable energy. This paper reviewed the latest research processes of AC/DC transmission technologies, summarized the characteristics of AC/DC power grids, concluded that China’s power grids certainly enter a new period of large -scale hybrid UHV AC/DC power grids and characteristics of “strong DC and weak AC” becomes increasingly pro minent; possible problems in operation of AC/DC power grids was discussed, and interaction or effect between AC/DC power grids was made an intensive study of; according to above problems in operation of power grids, preliminary scheme is summarized as fo llows: strengthening backbone structures, enhancing AC/DC transmission technologies, promoting protection measures of clean energ y accessing grids, and taking actions to solve stability problems of voltage and frequency etc. It’s valuable for making hybrid UHV AC/DC power grids adapt to operating mode of large power grids, thus guaranteeing security and stability of power system.

  3. Secure and Reliable IPTV Multimedia Transmission Using Forward Error Correction

    Directory of Open Access Journals (Sweden)

    Chi-Huang Shih

    2012-01-01

    Full Text Available With the wide deployment of Internet Protocol (IP infrastructure and rapid development of digital technologies, Internet Protocol Television (IPTV has emerged as one of the major multimedia access techniques. A general IPTV transmission system employs both encryption and forward error correction (FEC to provide the authorized subscriber with a high-quality perceptual experience. This two-layer processing, however, complicates the system design in terms of computational cost and management cost. In this paper, we propose a novel FEC scheme to ensure the secure and reliable transmission for IPTV multimedia content and services. The proposed secure FEC utilizes the characteristics of FEC including the FEC-encoded redundancies and the limitation of error correction capacity to protect the multimedia packets against the malicious attacks and data transmission errors/losses. Experimental results demonstrate that the proposed scheme obtains similar performance compared with the joint encryption and FEC scheme.

  4. Parametric study of variable renewable energy integration in Europe: Advantages and costs of transmission grid extensions

    International Nuclear Information System (INIS)

    Schaber, Katrin; Steinke, Florian; Mühlich, Pascal; Hamacher, Thomas

    2012-01-01

    Wind and solar energy will play an important role in the decarbonization of the European electricity generation. However, high shares of these variable renewable energies (VREs) challenge the power system considerably due to their temporal fluctuations and geographical dispersion. In this paper, we systematically analyze transmission grid extensions as an integration measure for VREs in Europe. We show the effects of grid extensions for fundamental properties of the power system as a function of the penetration and mix of wind and solar energy. Backup capacity requirements and overproduction are reduced with a powerful overlay transmission grid. We determine the costs of the grid extensions in dependence of the VRE penetration and mix and find that the grid integration costs remain below 25% of the VRE investment costs for all conceivable VRE configurations. Furthermore, robust design features of future power systems in terms of grid geometry and flexibility requirements for backup technologies are identified. We apply a spatially and temporally highly resolved techno-economic model of the European power system for our analysis. - Highlights: ► Quantification of the advantages and costs of a European overlay transmission grid. ► Grid integration costs for VREs in Europe remain below 6€/MWh. ► Application of a detailed power system model to a wide parameter space.

  5. A graphene oxide-carbon nanotube grid for high-resolution transmission electron microscopy of nanomaterials

    International Nuclear Information System (INIS)

    Zhang Lina; Zhang Haoxu; Zhou Ruifeng; Chen Zhuo; Li Qunqing; Fan Shoushan; Jiang Kaili; Ge Guanglu; Liu Renxiao

    2011-01-01

    A novel grid for use in transmission electron microscopy is developed. The supporting film of the grid is composed of thin graphene oxide films overlying a super-aligned carbon nanotube network. The composite film combines the advantages of graphene oxide and carbon nanotube networks and has the following properties: it is ultra-thin, it has a large flat and smooth effective supporting area with a homogeneous amorphous appearance, high stability, and good conductivity. The graphene oxide-carbon nanotube grid has a distinct advantage when characterizing the fine structure of a mass of nanomaterials over conventional amorphous carbon grids. Clear high-resolution transmission electron microscopy images of various nanomaterials are obtained easily using the new grids.

  6. Competitive power markets and grid reliability : keeping the promise

    International Nuclear Information System (INIS)

    Goulding, D.

    2005-01-01

    This white paper discussed various links between restructuring, competitive markets and reliability in the consolidation of electricity markets in Ontario. A historical approach was used, and the first section of the paper reviewed how reliability was managed in the pre-market period. The second section discussed the current reliability model and some of the general issues it has raised, as well as lessons learned. Structural reforms were reviewed. It was noted that currently dominant generators hold more market share than is compatible with ideas of workable competition. Issues concerning the mitigation of market power were discussed, with specific reference to the importance of public opinion. The need for mandatory standards and inclusive processes was emphasized, as well as the implementation of effective communication strategies and consumer education. A resource adequacy mechanism was recommended. The role of the Ontario Power Authority (OPA) was reviewed. Issues concerning consumer protection were examined. Future priorities included investment in infrastructure and reliability, as well as a realignment of markets. It was suggested that energy and reserve trading are critical for ensuring reliability in the market paradigm. Markets and inter-regional trading were discussed in terms of promoting reliability. Improvements in infrastructure were recommended, as well as a reduction in trade barriers. It was concluded that an over-arching, industry-wide commitment to investing in reliability is essential for managing the restructuring and reliability relationship in the years ahead. 15 refs

  7. Operation and control of a DC-grid offshore wind farm under DC transmission system faults

    DEFF Research Database (Denmark)

    Deng, Fujin; Chen, Zhe

    2013-01-01

    . Consequently, the protection and control strategies of dc systems need to be established. This paper studies a dc-grid offshore wind farm, where the wind power collection system and power transmission system adopt dc technology. In this paper, the redundancy of the HVDC transmission system under faults...... is studied, and a fault ridethrough strategy for the dc-grid offshore wind farm is proposed. The proposed strategy can effectively minimize the impacts of the power transmission system disturbance on the offshore wind farm, and on the ac grid. A dc-grid offshore wind farm example is simulated with PSCAD....../EMTDC, and the results validate the feasibility of the presented redundancy configuration and operation approach, and the fault ridethrough control strategy....

  8. Reliable multicast for the Grid: a case study in experimental computer science.

    Science.gov (United States)

    Nekovee, Maziar; Barcellos, Marinho P; Daw, Michael

    2005-08-15

    In its simplest form, multicast communication is the process of sending data packets from a source to multiple destinations in the same logical multicast group. IP multicast allows the efficient transport of data through wide-area networks, and its potentially great value for the Grid has been highlighted recently by a number of research groups. In this paper, we focus on the use of IP multicast in Grid applications, which require high-throughput reliable multicast. These include Grid-enabled computational steering and collaborative visualization applications, and wide-area distributed computing. We describe the results of our extensive evaluation studies of state-of-the-art reliable-multicast protocols, which were performed on the UK's high-speed academic networks. Based on these studies, we examine the ability of current reliable multicast technology to meet the Grid's requirements and discuss future directions.

  9. 76 FR 72203 - Voltage Coordination on High Voltage Grids; Notice of Reliability Workshop Agenda

    Science.gov (United States)

    2011-11-22

    ... DEPARTMENT OF ENERGY Federal Energy Regulatory Commission [Docket No. AD12-5-000] Voltage Coordination on High Voltage Grids; Notice of Reliability Workshop Agenda As announced in the Notice of Staff..., from 9 a.m. to 4:30 p.m. to explore the interaction between voltage control, reliability, and economic...

  10. Energy losses of superconducting power transmission cables in the grid

    DEFF Research Database (Denmark)

    Østergaard, Jacob; Okholm, Jan; Lomholt, Karin

    2001-01-01

    One of the obvious motives for development of superconducting power transmission cables is reduction of transmission losses. Loss components in superconducting cables as well as in conventional cables have been examined. These losses are used for calculating the total energy losses of conventional...... as well as superconducting cables when they are placed in the electric power transmission network. It is concluded that high load connections are necessary to obtain energy saving by the use of HTSC cables. For selected high load connections, an energy saving of 40% is expected. It is shown...

  11. Solar Energy Grid Integration Systems (SEGIS): adding functionality while maintaining reliability and economics

    Science.gov (United States)

    Bower, Ward

    2011-09-01

    An overview of the activities and progress made during the US DOE Solar Energy Grid Integration Systems (SEGIS) solicitation, while maintaining reliability and economics is provided. The SEGIS R&D opened pathways for interconnecting PV systems to intelligent utility grids and micro-grids of the future. In addition to new capabilities are "value added" features. The new hardware designs resulted in smaller, less material-intensive products that are being viewed by utilities as enabling dispatchable generation and not just unpredictable negative loads. The technical solutions enable "advanced integrated system" concepts and "smart grid" processes to move forward in a faster and focused manner. The advanced integrated inverters/controllers can now incorporate energy management functionality, intelligent electrical grid support features and a multiplicity of communication technologies. Portals for energy flow and two-way communications have been implemented. SEGIS hardware was developed for the utility grid of today, which was designed for one-way power flow, for intermediate grid scenarios, AND for the grid of tomorrow, which will seamlessly accommodate managed two-way power flows as required by large-scale deployment of solar and other distributed generation. The SEGIS hardware and control developed for today meets existing standards and codes AND provides for future connections to a "smart grid" mode that enables utility control and optimized performance.

  12. Grid connection of active stall wind farms using a VSC based DC transmission system

    DEFF Research Database (Denmark)

    Iov, F.; Sørensen, Poul Ejnar; Hansen, A.D.

    2005-01-01

    Currently, there is an increasing trend to connect large MW wind farms to the transmission system. Requirements that focus on the influence of the farms on the grid stability and power quality, and on the control capabilities of wind farms have already been established. The main trends of modern...... wind turbines/farms are clearly the variable speed operation and a grid connection through a power electronic interface, especially using doubly fed induction generators. Using power electronics the control capabilities of these wind turbines/farms are extended and thus the grid requirements...... are fulfilled. However, the traditional squirrel-cage generators based wind turbines/wind farms directly connected to the grid have less control capabilities. These wind turbines/farms cannot regulate their production and contribute to power system stability. A DC transmission system for connection...

  13. 78 FR 55249 - Transmission Relay Loadability Reliability Standard; Notice of Compliance Filing

    Science.gov (United States)

    2013-09-10

    ...; RM11-16-000] Transmission Relay Loadability Reliability Standard; Notice of Compliance Filing Take.... \\1\\ Transmission Relay Loadability Reliability Standard, Order No. 733, 130 FERC ] 61, 221 (2010..., Order No. 733-B, 136 FERC ] 61,185 (2011). \\2\\ Transmission Relay Loadability Reliability Standard, 138...

  14. DC Grid Control Concept for Expandable Multi-terminal HVDC Transmission Systems

    DEFF Research Database (Denmark)

    Irnawan, Roni; Silva, Filipe Miguel Faria da; Bak, Claus Leth

    2018-01-01

    In areas where there are already several HVDC links in operation or under construction, it is more likely that a DC grid emerges as a gradual process. Although the DC grid control concept has been widely discussed, the implementation in the expandable multi-terminal HVDC (MTDC) transmission systems...... still faces challenges. The existing converter control system needs to be adjusted when a point-to-point (PtP) link is operated into MTDC system, or when an additional converter is interconnected with an existing MTDC system, or even when a new DC grid control strategy is applied. In this paper, a new...... DC grid control concept is proposed that conserves and uses the existing converter control when an existing PtP link is extended into MTDC system or the existing MTDC system is expanded. An interface is proposed to decouple the DC grid secondary with converter control structures. By using...

  15. Joint interval reliability for Markov systems with an application in transmission line reliability

    International Nuclear Information System (INIS)

    Csenki, Attila

    2007-01-01

    We consider Markov reliability models whose finite state space is partitioned into the set of up states U and the set of down states D . Given a collection of k disjoint time intervals I l =[t l ,t l +x l ], l=1,...,k, the joint interval reliability is defined as the probability of the system being in U for all time instances in I 1 union ... union I k . A closed form expression is derived here for the joint interval reliability for this class of models. The result is applied to power transmission lines in a two-state fluctuating environment. We use the Linux versions of the free packages Maxima and Scilab in our implementation for symbolic and numerical work, respectively

  16. Joint interval reliability for Markov systems with an application in transmission line reliability

    Energy Technology Data Exchange (ETDEWEB)

    Csenki, Attila [School of Computing and Mathematics, University of Bradford, Bradford, West Yorkshire, BD7 1DP (United Kingdom)]. E-mail: a.csenki@bradford.ac.uk

    2007-06-15

    We consider Markov reliability models whose finite state space is partitioned into the set of up states {sub U} and the set of down states {sub D}. Given a collection of k disjoint time intervals I{sub l}=[t{sub l},t{sub l}+x{sub l}], l=1,...,k, the joint interval reliability is defined as the probability of the system being in {sub U} for all time instances in I{sub 1} union ... union I{sub k}. A closed form expression is derived here for the joint interval reliability for this class of models. The result is applied to power transmission lines in a two-state fluctuating environment. We use the Linux versions of the free packages Maxima and Scilab in our implementation for symbolic and numerical work, respectively.

  17. 78 FR 44557 - Revision to Transmission Vegetation Management Reliability Standard; Notice of Compliance Filing

    Science.gov (United States)

    2013-07-24

    ... Transmission Vegetation Management Reliability Standard; Notice of Compliance Filing Take notice that on July 12, 2013, the North American Electric Reliability Corporation (NERC), pursuant to Order No. 777 \\1... Reliability Standard FAC-003-2 to its Web site. \\1\\ Revisions to Reliability Standard for Transmission...

  18. Evaluating North American Electric Grid Reliability Using the Barabasi-Albert Network Model

    OpenAIRE

    Chassin, David P.; Posse, Christian

    2004-01-01

    The reliability of electric transmission systems is examined using a scale-free model of network structure and failure propagation. The topologies of the North American eastern and western electric networks are analyzed to estimate their reliability based on the Barabasi-Albert network model. A commonly used power system reliability index is computed using a simple failure propagation model. The results are compared to the values of power system reliability indices previously obtained using s...

  19. Deterrence and transmission as mechanisms ensuring reliability of gossip.

    Science.gov (United States)

    Giardini, Francesca

    2012-10-01

    Spreading information about the members of one's group is one of the most universal human behaviors. Thanks to gossip, individuals can acquire the information about their peers without sustaining the burden of costly interactions with cheaters, but they can also create and revise social bonds. Gossip has also several positive functions at the group level, promoting cohesion and norm compliance. However, gossip can be unreliable, and can be used to damage others' reputation or to circulate false information, thus becoming detrimental to people involved and useless for the group. In this work, we propose a theoretical model in which reliability of gossip depends on the joint functioning of two distinct mechanisms. Thanks to the first, i.e., deterrence, individuals tend to avoid informational cheating because they fear punishment and the disruption of social bonds. On the other hand, transmission provides humans with the opportunity of reducing the consequences of cheating through a manipulation of the source of gossip.

  20. Rate Adaptive Selective Segment Assignment for Reliable Wireless Video Transmission

    Directory of Open Access Journals (Sweden)

    Sajid Nazir

    2012-01-01

    Full Text Available A reliable video communication system is proposed based on data partitioning feature of H.264/AVC, used to create a layered stream, and LT codes for erasure protection. The proposed scheme termed rate adaptive selective segment assignment (RASSA is an adaptive low-complexity solution to varying channel conditions. The comparison of the results of the proposed scheme is also provided for slice-partitioned H.264/AVC data. Simulation results show competitiveness of the proposed scheme compared to optimized unequal and equal error protection solutions. The simulation results also demonstrate that a high visual quality video transmission can be maintained despite the adverse effect of varying channel conditions and the number of decoding failures can be reduced.

  1. Regional study on investment for transmission infrastructure in China based on the State Grid data

    Science.gov (United States)

    Wei, Wendong; Wu, Xudong; Wu, Xiaofang; Xi, Qiangmin; Ji, Xi; Li, Guoping

    2017-03-01

    Transmission infrastructure is an integral component of safeguarding the stability of electricity delivery. However, existing studies of transmission infrastructure mostly rely on a simple review of the network, while the analysis of investments remains rudimentary. This study conducted the first regionally focused analysis of investments in transmission infrastructure in China to help optimize its structure and reduce investment costs. Using State Grid data, the investment costs, under various voltages, for transmission lines and transformer substations are calculated. By analyzing the regional profile of cumulative investment in transmission infrastructure, we assess correlations between investment, population, and economic development across the regions. The recent development of ultra-high-voltage transmission networks will provide policy-makers new options for policy development.

  2. The Economics of Storage, Transmission and Drought: Integrating Variable Wind Power into Spatially Separated Electricity Grids

    NARCIS (Netherlands)

    Scora, H.; Sopinka, A.; Kooten, van G.C.

    2012-01-01

    To mitigate the high variability of wind and make it a more viable renewable energy source, observers recommend greater integration of spatially-separated electrical grids, with high transmission lines linking load centers, scattered wind farms and hydro storage sites. In this study, we examine the

  3. Transmission-grid requirements with scattered and fluctuating renewable electricity-sources

    DEFF Research Database (Denmark)

    Østergaard, Poul Alberg

    2003-01-01

    The article analysis the requirements of the transmission grids in a year 2020 situation with power balancing (matching production and consumption)as it is now on the few large power plants, and a year 2020 situation with geographically-scattered power balancing using e.g. CHP plants, heat pumps...

  4. Considerations on smart grid developments and impacts on transmission operation and planning

    NARCIS (Netherlands)

    Ribeiro, P.F.; Nguyen, P.H.; Kling, W.L.

    2012-01-01

    This paper discusses some historical and technical events, particularly in USA and Europe, over the last few years, that are aimed at modernizing the electric power grid. The paper also looks at possible impacts on transmission operation and planning as the system moves from a centralized to a

  5. Design of protective inductors for HVDC transmission line within DC grid offshore wind farms

    DEFF Research Database (Denmark)

    Deng, Fujin; Chen, Zhe

    2013-01-01

    in the HVDC link between the offshore station and the onshore station. The transient characteristics of the transmission system are analyzed in detail. The criteria of selecting protective inductors are proposed to effectively limit the short-circuit current and avoid the damage to the converters. A dc grid...

  6. Comprehensive evaluation of power grid projects' investment benefits under the reform of transmission and distribution price

    Science.gov (United States)

    Wang, Yongli; Wang, Gang; Zuo, Yi; Fan, Lisha; Ling, Yunpeng

    2017-03-01

    On March 15, 2015, the Central Office issued the "Opinions on Further Deepening the Reform of Electric Power System" (Zhong Fa No. 9). This policy marks the central government officially opened a new round of electricity reform. As a programmatic document under the new situation to comprehensively promote the reform of the power system, No. 9 document will be approved as a separate transmission and distribution of electricity prices, which is the first task of promoting the reform of the power system. Grid tariff reform is not only the transmission and distribution price of a separate approval, more of the grid company input-output relationship and many other aspects of deep-level adjustments. Under the background of the reform of the transmission and distribution price, the main factors affecting the input-output relationship, such as the main business, electricity pricing, and investment approval, financial accounting and so on, have changed significantly. The paper designed the comprehensive evaluation index system of power grid projects' investment benefits under the reform of transmission and distribution price to improve the investment efficiency of power grid projects after the power reform in China.

  7. Regulating Future Offshore Grids: Economic Impact Analysis on Wind Parks and Transmission System Operators

    DEFF Research Database (Denmark)

    Kitzing, Lena; Schröder, Sascha Thorsten

    the respective countries. This study focuses on how investors in wind parks and transmission systems are affected by the choice of regulatory regime in offshore grids with one to four countries connected. In order to capture the uncertainties related to the exposure to market prices as well as risks related...

  8. Cyber Risk Assessment of Transmission Lines in Smart Grids

    Directory of Open Access Journals (Sweden)

    Xuan Liu

    2015-12-01

    Full Text Available The increasing use of information technologies in power systems has increased the risk of power systems to cyber-attacks. In this paper, we assess the risk of transmission lines being overloaded due to cyber-based false data injection attacks. The cyber risk assessment is formulated as bilevel optimization problems that determine the maximum line flows under false data injection attacks. We propose efficient techniques to reduce the computation complexity of solving the bilevel problems. Specifically, primary and secondary filtering techniques are employed to identify the lines whose flows will never exceed their limits, which can significantly reduce computation burden. A special feasibility cut-based acceleration technique is introduced to further reduce the computation burden. The simulation results on the IEEE 30-bus, IEEE 118-bus, IEEE 300-bus and IEEE 2383-bus systems verify the proposed risk assessment model and the effectiveness of the proposed filtering and acceleration techniques.

  9. AC HTS Transmission Cable for Integration into the Future EHV Grid of the Netherlands

    Science.gov (United States)

    Zuijderduin, R.; Chevtchenko, O.; Smit, J. J.; Aanhaanen, G.; Melnik, I.; Geschiere, A.

    Due to increasing power demand, the electricity grid of the Netherlands is changing. The future grid must be capable to transmit all the connected power. Power generation will be more decentralized like for instance wind parks connected to the grid. Furthermore, future large scale production units are expected to be installed near coastal regions. This creates some potential grid issues, such as: large power amounts to be transmitted to consumers from west to east and grid stability. High temperature superconductors (HTS) can help solving these grid problems. Advantages to integrate HTS components at Extra High Voltage (EHV) and High Voltage (HV) levels are numerous: more power with less losses and less emissions, intrinsic fault current limiting capability, better control of power flow, reduced footprint, etc. Today's main obstacle is the relatively high price of HTS. Nevertheless, as the price goes down, initial market penetration for several HTS components is expected by year 2015 (e.g.: cables, fault current limiters). In this paper we present a design of intrinsically compensated EHV HTS cable for future grid integration. Discussed are the parameters of such cable providing an optimal power transmission in the future network.

  10. Application of essential facility doctrine to transmission grid; Sodenmo eno essential facility no hori no tekiyo

    Energy Technology Data Exchange (ETDEWEB)

    Maruyama, M. [Central Research Institute of Electric Power Industry, Tokyo (Japan)

    1997-06-01

    This paper arranges the essential facility doctrine in America and describes it according to each judgment example how the doctrine is applied on the access of electricity supply companies to transmission grids. By applying the result to the situation of Japan, the point at issue occurring in the range of the Anti-Monopoly Law was arranged and investigated when third parties (power generating manufacturers) access the transmission grids of electricity supply companies in the form of wholesale or self transmission in the electricity supply industry of Japan. In the judgment example of America, a transmission grid can be considered as essential facility. The refusal of essential facility application is judged to be illegal only when it aims at keeping and expanding the leading market share without a fair reason. The application of essential facility can be refused when the transmission line is insufficient in capacity, when no necessary technical conditions are satisfied during use, or when the cost generated during use cannot be collected. 18 refs., 7 figs., 2 tabs.

  11. Reliable Detection and Smart Deletion of Malassez Counting Chamber Grid in Microscopic White Light Images for Microbiological Applications.

    Science.gov (United States)

    Denimal, Emmanuel; Marin, Ambroise; Guyot, Stéphane; Journaux, Ludovic; Molin, Paul

    2015-08-01

    In biology, hemocytometers such as Malassez slides are widely used and are effective tools for counting cells manually. In a previous work, a robust algorithm was developed for grid extraction in Malassez slide images. This algorithm was evaluated on a set of 135 images and grids were accurately detected in most cases, but there remained failures for the most difficult images. In this work, we present an optimization of this algorithm that allows for 100% grid detection and a 25% improvement in grid positioning accuracy. These improvements make the algorithm fully reliable for grid detection. This optimization also allows complete erasing of the grid without altering the cells, which eases their segmentation.

  12. Identification of reliable gridded reference data for statistical downscaling methods in Alberta

    Science.gov (United States)

    Eum, H. I.; Gupta, A.

    2017-12-01

    Climate models provide essential information to assess impacts of climate change at regional and global scales. However, statistical downscaling methods have been applied to prepare climate model data for various applications such as hydrologic and ecologic modelling at a watershed scale. As the reliability and (spatial and temporal) resolution of statistically downscaled climate data mainly depend on a reference data, identifying the most reliable reference data is crucial for statistical downscaling. A growing number of gridded climate products are available for key climate variables which are main input data to regional modelling systems. However, inconsistencies in these climate products, for example, different combinations of climate variables, varying data domains and data lengths and data accuracy varying with physiographic characteristics of the landscape, have caused significant challenges in selecting the most suitable reference climate data for various environmental studies and modelling. Employing various observation-based daily gridded climate products available in public domain, i.e. thin plate spline regression products (ANUSPLIN and TPS), inverse distance method (Alberta Townships), and numerical climate model (North American Regional Reanalysis) and an optimum interpolation technique (Canadian Precipitation Analysis), this study evaluates the accuracy of the climate products at each grid point by comparing with the Adjusted and Homogenized Canadian Climate Data (AHCCD) observations for precipitation, minimum and maximum temperature over the province of Alberta. Based on the performance of climate products at AHCCD stations, we ranked the reliability of these publically available climate products corresponding to the elevations of stations discretized into several classes. According to the rank of climate products for each elevation class, we identified the most reliable climate products based on the elevation of target points. A web-based system

  13. Islanding the power grid on the transmission level: less connections for more security

    Science.gov (United States)

    Mureddu, Mario; Caldarelli, Guido; Damiano, Alfonso; Scala, Antonio; Meyer-Ortmanns, Hildegard

    2016-10-01

    Islanding is known as a management procedure of the power system that is implemented at the distribution level to preserve sensible loads from outages and to guarantee the continuity in electricity supply, when a high amount of distributed generation occurs. In this paper we study islanding on the level of the transmission grid and shall show that it is a suitable measure to enhance energy security and grid resilience. We consider the German and Italian transmission grids. We remove links either randomly to mimic random failure events, or according to a topological characteristic, their so-called betweenness centrality, to mimic an intentional attack and test whether the resulting fragments are self-sustainable. We test this option via the tool of optimized DC power flow equations. When transmission lines are removed according to their betweenness centrality, the resulting islands have a higher chance of being dynamically self-sustainable than for a random removal. Less connections may even increase the grid’s stability. These facts should be taken into account in the design of future power grids.

  14. Recovery Act-SmartGrid regional demonstration transmission and distribution (T&D) Infrastructure

    Energy Technology Data Exchange (ETDEWEB)

    Hedges, Edward T. [Kansas City Power & Light Company, Kansas City, MO (United States)

    2015-01-31

    This document represents the Final Technical Report for the Kansas City Power & Light Company (KCP&L) Green Impact Zone SmartGrid Demonstration Project (SGDP). The KCP&L project is partially funded by Department of Energy (DOE) Regional Smart Grid Demonstration Project cooperative agreement DE-OE0000221 in the Transmission and Distribution Infrastructure application area. This Final Technical Report summarizes the KCP&L SGDP as of April 30, 2015 and includes summaries of the project design, implementation, operations, and analysis performed as of that date.

  15. Comprehensive evaluation of power grid enterprises' credit rating under the reform of transmission and distribution price

    Science.gov (United States)

    Wang, Yongli; Wang, Gang; Zuo, Yi; Fan, Lisha; Wei, Jiaxiang

    2017-03-01

    On March 15, 2015, the central office issued the "Opinions on Further Deepening the Reform of Electric Power System" (in the 2015 No. 9). This policy marks the central government officially opened a new round of electricity reform. As a programmatic document under the new situation to comprehensively promote the reform of the power system, No. 9 document will be approved as a separate transmission and distribution of electricity prices, which is the first task of promoting the reform of the power system. Grid tariff reform is not only the transmission and distribution price of a separate approval, more of the grid company input-output relationship and many other aspects of deep-level adjustments. Under the background of the reform of the transmission and distribution price, the main factors affecting the input-output relationship, such as the main business, electricity pricing, and investment approval, financial accounting and so on, have changed significantly. The paper designed the comprehensive evaluation index system of power grid enterprises' credit rating under the reform of transmission and distribution price to reduce the impact of the reform on the company's international rating results and the ability to raise funds.

  16. Transmission cost allocation based on power flow tracing considering reliability benefit

    International Nuclear Information System (INIS)

    Leepreechanon, N.; Singharerg, S.; Padungwech, W.; Nakawiro, W.; Eua-Arporn, B.; David, A.K.

    2007-01-01

    Power transmission networks must be able to accommodate the continuously growing demand for reliable and economical electricity. This paper presented a method to allocate transmission use and reliability cost to both generators and end-consumers. Although transmission cost allocation methods change depending on the local context of the electric power industry, there is a common principle that transmission line capacity should be properly allocated to accommodate actual power delivery with an adequate reliability margin. The method proposed in this paper allocates transmission embedded cost to both generators and loads in an equitable manner, incorporating probability indices to allocate transmission reliability margin among users in both supply and demand sides. The application of the proposed method was illustrated using Bialek's tracing method on a multiple-circuit, six-bus transmission system. Probabilistic indices known as the transmission internal reliability margin (TIRM) and transmission external reliability margin (TERM) decomposed from the transmission reliability margin (TRM) were introduced, making true cost of using overall transmission facilities. 6 refs., 11 tabs., 5 figs

  17. Reliability of transmission networks : Impact of EHV underground cables & interaction of offshore-onshore networks

    NARCIS (Netherlands)

    Tuinema, B.W.

    2017-01-01

    For the future, several developments of the power system are expected. The transition towards a more sustainable energy supply puts new requirements on the design and operation of power systems, and the transmission network in particular. Offshore, a transmission grid will be implemented to collect

  18. A Data Transmission Algorithm Based on Dynamic Grid Division for Coal Goaf Temperature Monitoring

    Directory of Open Access Journals (Sweden)

    Qingsong Hu

    2014-01-01

    Full Text Available WSN (wireless sensor network is a perfect tool of temperature monitoring in coal goaf. Based on the three-zone theory of goaf, the GtmWSN model is proposed, and its dynamic features are analyzed. Accordingly, a data transmission scheme, named DTDGD, is worked out. Firstly, sink nodes conduct dynamic grid division on the GtmWSN according to virtual semicircle. Secondly, each node will confirm to which grid it belongs based on grid number. Finally, data will be delivered to sink nodes with greedy forward and hole avoidance. Simulation results and field data showed that the GtmWSN and DTDGD satisfied the lifetime need of goaf temperature monitoring.

  19. Adapting AC Lines to DC Grids for Large-Scale Renewable Power Transmission

    Directory of Open Access Journals (Sweden)

    D. Marene Larruskain

    2014-10-01

    Full Text Available All over the world, governments of different countries are nowadays promoting the use of clean energies in order to achieve sustainable energy systems. In this scenario, since the installed capacity is continuously increasing, renewable sources can play an important role. Notwithstanding that, some important problems may appear when connecting these sources to the grid, being the overload of distribution lines one of the most relevant. In fact, renewable generation is usually connected to the nearest AC grid, although this HV system may not have been designed considering distributed generation. In the particular case of large wind farms, the electrical grid has to transmit all the power generated by wind energy and, as a consequence, the AC system may get overloaded. It is therefore necessary to determine the impact of wind power transmission so that appropriate measures can be taken. Not only are these measures influenced by the amount of power transmitted, but also by the quality of the transmitted power, due to the output voltage fluctuation caused by the highly variable nature of wind. When designing a power grid, although AC systems are usually the most economical solution because of its highly proven technology, HVDC may arise in some cases (e.g. offshore wind farms as an interesting alternative, offering some added values such as lower losses and better controllability. This way, HVDC technology can solve most of the aforementioned problems and has a good potential for future use. Additionally, the fast development of power electronics based on new and powerful semiconductor devices allow the spread of innovative technologies, such as VSC-HVDC, which can be applied to create DC grids. This paper focuses on the main aspects involved in adapting the existing overhead AC lines to DC grids, with the objective of improving the transmission of distributed renewable energy to the centers of consumption.

  20. Reliability Oriented Design Tool For the New Generation of Grid Connected PV-Inverters

    DEFF Research Database (Denmark)

    Sintamarean, Nicolae Cristian; Blaabjerg, Frede; Wang, Huai

    2015-01-01

    is achieved and is further used as an input to the lifetime model. The proposed reliability-oriented design tool is used to study the impact of mission profile (MP) variation and device degradation (aging) in the PV inverter lifetime. The obtained results indicate that the MP of the field where the PV...... inverter is operating has an important impact (up to 70%) on the converter lifetime expectation, and it should be considered in the design stage to better optimize the converter design margin. In order to have correct lifetime estimation, it is crucial to consider also the device degradation feedback (in......This paper introduces a reliability-oriented design tool for a new generation of grid-connected photovoltaic (PV) inverters. The proposed design tool consists of a real field mission profile (RFMP) model (for two operating regions: USA and Denmark), a PV panel model, a grid-connected PV inverter...

  1. Assessment of transient stability of cable based transmission grids with reactive power compensation

    DEFF Research Database (Denmark)

    Foo, Yii; Dall, Laurids; Silva, Filipe Miguel Faria da

    2017-01-01

    Underground transmission cables are gaining popularity due to its applications near cities and aesthetic purpose. For example in Denmark, the transmission power grid is changing significantly as many conventional overhead lines (OHL) are replaced by cables and more is expected over the coming years...... through a series of sensitivity analysis with respect to the cables compensation degree. A separate case of disconnecting the SRs of the faulted line is also carried out. The tendencies are initially observed and explained for smaller systems, Single-Machine Infinite Bus (SMIB) and 9-bus system...

  2. Design Optimization of Transformerless Grid-Connected PV Inverters Including Reliability

    OpenAIRE

    Koutroulis, Eftichios; Blaabjerg, Frede

    2013-01-01

    This paper presents a new methodology for optimal design of transformerless photovoltaic (PV) inverters targeting a cost-effective deployment of grid-connected PV systems. The optimal switching frequency as well as the optimal values and types of the PV inverter components is calculated such that the PV inverter LCOE generated during the PV system lifetime period is minimized. The LCOE is also calculated considering the failure rates of the components, which affect the reliability performance...

  3. Resilience of electricity grids against transmission line overloads under wind power injection at different nodes.

    Science.gov (United States)

    Schiel, Christoph; Lind, Pedro G; Maass, Philipp

    2017-09-14

    A steadily increasing fraction of renewable energy sources for electricity production requires a better understanding of how stochastic power generation affects the stability of electricity grids. Here, we assess the resilience of an IEEE test grid against single transmission line overloads under wind power injection based on the dc power flow equations and a quasi-static grid response to wind fluctuations. Thereby we focus on the mutual influence of wind power generation at different nodes. We find that overload probabilities vary strongly between different pairs of nodes and become highly affected by spatial correlations of wind fluctuations. An unexpected behaviour is uncovered: for a large number of node pairs, increasing wind power injection at one node can increase the power threshold at the other node with respect to line overloads in the grid. We find that this seemingly paradoxical behaviour is related to the topological distance of the overloaded line from the shortest path connecting the wind nodes. In the considered test grid, it occurs for all node pairs, where the overloaded line belongs to the shortest path.

  4. Final Scientific/ Technical Report. Playas Grid Reliability and Distributed Energy Research

    Energy Technology Data Exchange (ETDEWEB)

    Romero, Van [New Mexico Institute Of Mining And Technology, Socorro, NM (United States); Weinkauf, Don [New Mexico Institute Of Mining And Technology, Socorro, NM (United States); Khan, Mushtaq [New Mexico Institute Of Mining And Technology, Socorro, NM (United States); Helgeson, Wes [New Mexico Institute Of Mining And Technology, Socorro, NM (United States); Weedeward, Kevin [New Mexico Institute Of Mining And Technology, Socorro, NM (United States); LeClerc, Corey [New Mexico Institute Of Mining And Technology, Socorro, NM (United States); Fuierer, Paul [New Mexico Institute Of Mining And Technology, Socorro, NM (United States)

    2012-06-30

    The future looks bright for solar and renewable energies in the United States. Recent studies claim that by 2050, solar power could supply a third of all electricity demand in the country’s western states. Technology advances, soft policy changes, and increased energy consciousness will all have to happen to achieve this goal. But the larger question is, what would it take to do more throughout the United States? The studies tie future solar and renewable growth in the United States to programs that aim to lower the soft costs of solar adoption, streamline utility interconnections, and increase technology advances through research and development. At the state and local levels, the most important steps are; Net metering: Net metering policies lets customers offset their electric bills with onsite solar and receive reliable and fair compensation for the excess electricity they provide to the grid. Not surprisingly, what utilities consider fair is not necessarily a rate that’s favorable to solar customers; Renewable portfolio standards (RPS): RPS policies require utilities to provide a certain amount of their power from renewable sources; some set specific targets for solar and other renewables. California’s aggressive RPS of 33% renewable energy by 2020 is not bankrupting the state, or its residents; Strong statewide interconnection policies: Solar projects can experience significant delays and hassles just to get connected to the grid. Streamlined feasibility and impact analysis are needed. Good interconnection policies are crucial to the success of solar or renewable energy development; Financing options: Financing is often the biggest obstacle to solar adoption. Those obstacles can be surmounted with policies that support creative financing options like third-party ownership (TPO) and property assessed clean energy (PACE). Attesting to the significance of TPO is the fact that in Arizona, it accounted for 86% of all residential photovoltaic (PV

  5. Fault-ride through behavior of MV-connected wind turbines and CHP-plants during transmission grid disturbances

    NARCIS (Netherlands)

    Karaliolios, P.; Coster, E.J.; Kling, W.L.; Myrzik, J.M.A.

    2009-01-01

    Apart from the positive technical consequences, the increasing penetration of Distributed Generation (DG) units connected to the distribution network brings new requirements in the protection strategy. Grid disturbances at the transmission level can cause the unwanted disconnection of large amount

  6. Smart transmission grids - benefits and risks; Redes de transmision inteligente. Beneficios y riesgos

    Energy Technology Data Exchange (ETDEWEB)

    Velasco-Ramirez, E.; Angeles-Camacho, C. [Universidad Nacional Autonoma de Mexico, Mexico, D.F. (Mexico)]. E-mails: TVelascoR@iingen.unam.mx; CAngelesC@ii.unam.mx; Garcia-Martinez, M. [Instituto Tecnologico de Toluca, Estado de Mexico (Mexico)]. E-mail: mgarciam@ittoluca.edu.mx

    2013-01-15

    Nowadays the Power Systems are working near their stability limits, for this reason it is necessary and essential a transition to new transmission systems that ensure efficient delivery of electrical energy, with the objective to prevent blackouts that cause significant losses in the economy of any country in the world. This paper analyzes important elements to consider having a healthy and efficient transition from a power grid vertically integrated into a smart transmission grid. A comparative analysis in the model, development, benefits and risks of the implementation of these systems, between two of the main marc of references of smart grids, the EU and the USA is presented. [Spanish] Actualmente los sistemas electricos operan cada vez mas cercanos a sus limites de estabilidad, es por ello que se hace necesaria y primordial la transicion hacia nuevos sistemas de transmision que garanticen la eficiente entrega de la energia electrica, evitando con ello cortes de energia que generan importantes perdidas en la economia de cualquier pais del mundo. En este documento se realiza un analisis de los elementos necesarios para una sana y eficiente transicion de una red de transmision electrica verticalmente, integrada hacia una red de transmision inteligente. Se presenta un analisis comparativo entre dos de los marcos de referencia mas importantes, el de la UE y el de EUA, en el modelo, desarrollo, beneficios y riesgos en la implementacion de estos sistemas.

  7. 77 FR 64920 - Revisions to Reliability Standard for Transmission Vegetation Management

    Science.gov (United States)

    2012-10-24

    ... reliability of the Bulk Electric System.'' NERC defines ``System Operating Limit'' as ``[t]he value (such as... values or gives reason to revisit the Reliability Standard. Accordingly, consistent with the activity...] Revisions to Reliability Standard for Transmission Vegetation Management AGENCY: Federal Energy Regulatory...

  8. 78 FR 22773 - Revisions to Reliability Standard for Transmission Vegetation Management; Correction

    Science.gov (United States)

    2013-04-17

    ...; Order No. 777] Revisions to Reliability Standard for Transmission Vegetation Management; Correction... modifying certain Reliability Standards. DATES: Effective on May 28, 2013. FOR FURTHER INFORMATION CONTACT... Requirement R2 of Reliability Standard FAC-003-2 within 45 days of the effective date of the Final Rule, while...

  9. 78 FR 21929 - Transmission Relay Loadability Reliability Standard; Notice of Compliance Filing

    Science.gov (United States)

    2013-04-12

    ... Relay Loadability Reliability Standard; Notice of Compliance Filing Take notice that on February 19... Relay Loadability Reliability Standard, Order No. 733, 130 FERC ] 61,221 (2010) (Order No. 733); order..., 136 FERC ] 61,185 (2011). \\2\\ Transmission Relay Loadability Reliability Standard, 138 FERC ] 61,197...

  10. 76 FR 23470 - Version One Regional Reliability Standard for Transmission Operations

    Science.gov (United States)

    2011-04-27

    ...; Order No. 752] Version One Regional Reliability Standard for Transmission Operations AGENCY: Federal... Power Act, the Federal Energy Regulatory Commission approves regional Reliability Standard TOP-007-WECC... purpose of this regional Reliability Standard is to ensure that actual flows and associated scheduled...

  11. Design optimization of transformerless grid-connected PV inverters including reliability

    DEFF Research Database (Denmark)

    Koutroulis, Eftichios; Blaabjerg, Frede

    2012-01-01

    Of the Electricity (LCOE) generated during the PV system lifetime period is minimized. The LCOE is calculated also considering the failure rates of the components, which affect the reliability performance and lifetime maintenance cost of the PV inverter. A design example is presented, demonstrating that compared...... to the non-optimized PV inverter structures, the PV inverters designed using the proposed optimization methodology exhibit lower total manufacturing and lifetime maintenance cost and inject more energy into the electric-grid and by that minimizing LCOE.......This paper presents a new methodology for optimal design of transformerless Photovoltaic (PV) inverters targeting a cost-effective deployment of grid-connected PV systems. The optimal values and types of the PV inverter components are calculated such that the PV inverter Levelized Cost...

  12. Design Optimization of Transformerless Grid-Connected PV Inverters Including Reliability

    DEFF Research Database (Denmark)

    Koutroulis, Eftichios; Blaabjerg, Frede

    2013-01-01

    such that the PV inverter LCOE generated during the PV system lifetime period is minimized. The LCOE is also calculated considering the failure rates of the components, which affect the reliability performance and lifetime maintenance cost of the PV inverter. A design example is presented, demonstrating...... that compared to the nonoptimized PV inverter structures, the PV inverters designed using the proposed optimization methodology exhibit lower total manufacturing and lifetime maintenance cost and inject more energy into the electric-grid and by that minimizing LCOE.......This paper presents a new methodology for optimal design of transformerless photovoltaic (PV) inverters targeting a cost-effective deployment of grid-connected PV systems. The optimal switching frequency as well as the optimal values and types of the PV inverter components is calculated...

  13. Reliability-Based Topology Optimization Using Stochastic Response Surface Method with Sparse Grid Design

    Directory of Open Access Journals (Sweden)

    Qinghai Zhao

    2015-01-01

    Full Text Available A mathematical framework is developed which integrates the reliability concept into topology optimization to solve reliability-based topology optimization (RBTO problems under uncertainty. Two typical methodologies have been presented and implemented, including the performance measure approach (PMA and the sequential optimization and reliability assessment (SORA. To enhance the computational efficiency of reliability analysis, stochastic response surface method (SRSM is applied to approximate the true limit state function with respect to the normalized random variables, combined with the reasonable design of experiments generated by sparse grid design, which was proven to be an effective and special discretization technique. The uncertainties such as material property and external loads are considered on three numerical examples: a cantilever beam, a loaded knee structure, and a heat conduction problem. Monte-Carlo simulations are also performed to verify the accuracy of the failure probabilities computed by the proposed approach. Based on the results, it is demonstrated that application of SRSM with SGD can produce an efficient reliability analysis in RBTO which enables a more reliable design than that obtained by DTO. It is also found that, under identical accuracy, SORA is superior to PMA in view of computational efficiency.

  14. Transcultural Adaptation of GRID Hamilton Rating Scale For Depression (GRID-HAMD) to Brazilian Portuguese and Evaluation of the Impact of Training Upon Inter-Rater Reliability.

    Science.gov (United States)

    Henrique-Araújo, Ricardo; Osório, Flávia L; Gonçalves Ribeiro, Mônica; Soares Monteiro, Ivandro; Williams, Janet B W; Kalali, Amir; Alexandre Crippa, José; Oliveira, Irismar Reis De

    2014-07-01

    GRID-HAMD is a semi-structured interview guide developed to overcome flaws in HAM-D, and has been incorporated into an increasing number of studies. Carry out the transcultural adaptation of GRID-HAMD into the Brazilian Portuguese language, evaluate the inter-rater reliability of this instrument and the training impact upon this measure, and verify the raters' opinions of said instrument. The transcultural adaptation was conducted by appropriate methodology. The measurement of inter-rater reliability was done by way of videos that were evaluated by 85 professionals before and after training for the use of this instrument. The intraclass correlation coefficient (ICC) remained between 0.76 and 0.90 for GRID-HAMD-21 and between 0.72 and 0.91 for GRID-HAMD-17. The training did not have an impact on the ICC, except for a few groups of participants with a lower level of experience. Most of the participants showed high acceptance of GRID-HAMD, when compared to other versions of HAM-D. The scale presented adequate inter-rater reliability even before training began. Training did not have an impact on this measure, except for a few groups with less experience. GRID-HAMD received favorable opinions from most of the participants.

  15. Drought and Heat Wave Impacts on Electricity Grid Reliability in Illinois

    Science.gov (United States)

    Stillwell, A. S.; Lubega, W. N.

    2016-12-01

    A large proportion of thermal power plants in the United States use cooling systems that discharge large volumes of heated water into rivers and cooling ponds. To minimize thermal pollution from these discharges, restrictions are placed on temperatures at the edge of defined mixing zones in the receiving waters. However, during extended hydrological droughts and heat waves, power plants are often granted thermal variances permitting them to exceed these temperature restrictions. These thermal variances are often deemed necessary for maintaining electricity reliability, particularly as heat waves cause increased electricity demand. Current practice, however, lacks tools for the development of grid-scale operational policies specifying generator output levels that ensure reliable electricity supply while minimizing thermal variances. Such policies must take into consideration characteristics of individual power plants, topology and characteristics of the electricity grid, and locations of power plants within the river basin. In this work, we develop a methodology for the development of these operational policies that captures necessary factors. We develop optimal rules for different hydrological and meteorological conditions, serving as rule curves for thermal power plants. The rules are conditioned on leading modes of the ambient hydrological and meteorological conditions at the different power plant locations, as the locations are geographically close and hydrologically connected. Heat dissipation in the rivers and cooling ponds is modeled using the equilibrium temperature concept. Optimal rules are determined through a Monte Carlo sampling optimization framework. The methodology is applied to a case study of eight power plants in Illinois that were granted thermal variances in the summer of 2012, with a representative electricity grid model used in place of the actual electricity grid.

  16. Multi-state time-varying reliability evaluation of smart grid with flexible demand resources utilizing Lz transform

    Science.gov (United States)

    Jia, Heping; Jin, Wende; Ding, Yi; Song, Yonghua; Yu, Dezhao

    2017-01-01

    With the expanding proportion of renewable energy generation and development of smart grid technologies, flexible demand resources (FDRs) have been utilized as an approach to accommodating renewable energies. However, multiple uncertainties of FDRs may influence reliable and secure operation of smart grid. Multi-state reliability models for a single FDR and aggregating FDRs have been proposed in this paper with regard to responsive abilities for FDRs and random failures for both FDR devices and information system. The proposed reliability evaluation technique is based on Lz transform method which can formulate time-varying reliability indices. A modified IEEE-RTS has been utilized as an illustration of the proposed technique.

  17. Can the BestGrid Process Improve Stakeholder Involvement in Electricity Transmission Projects?

    Directory of Open Access Journals (Sweden)

    Nadejda Komendantova

    2015-08-01

    Full Text Available The European Union has set ambitious targets for deployment of renewable energy sources to reach goals of climate change mitigation and energy security policies. However, the current state of electricity transmission infrastructure is a major bottleneck for further scaling up of renewable energy in the EU. Several thousands of kilometers of new lines have to be constructed and upgraded to accommodate growing volumes of intermittent renewable electricity. In many countries, construction of electricity transmission projects has been delayed for several years due to concerns of local stakeholders. The innovative BESTGRID approach, reported here, brings together transmission system operators (TSOs and non-governmental organizations (NGOs to discuss and understand the nature of stakeholder concerns. This paper has three objectives: (1 to understand stakeholder concerns about the deployment of electricity transmission grids in four pilot projects according to five guiding principles: need, transparency, engagement, environment, and impacts on human health as well as benefits; (2 to understand how these principles can be addressed to provide a basis for better decision-making outcomes; and (3 to evaluate the BESTGRID process based on feedback received from stakeholders and the level of participation achieved according to the ladder of Arnstein. This paper goes beyond a discussion of “measures to mitigate opposition” to understand how dialogue between TSOs and the public—represented mainly by NGOs and policy-makers—might lead to a better decision-making process and more sustainable electricity transmission infrastructure deployment.

  18. 76 FR 58424 - Transmission Relay Loadability Reliability Standard

    Science.gov (United States)

    2011-09-21

    ... distribution providers to set load-responsive phase protection relays according to specific criteria to ensure...-part R.1.10 allows transmission owners, generation owners and distribution providers to set transformer.... Thus, requiring that transformer fault protection relays are set to not expose the transformer to a...

  19. Transmission characteristics of a two dimensional antiscatter grid prototype for CBCT.

    Science.gov (United States)

    Altunbas, Cem; Kavanagh, Brian; Alexeev, Timur; Miften, Moyed

    2017-08-01

    High fraction of scattered radiation in cone-beam CT (CBCT) imaging degrades CT number accuracy and visualization of low contrast objects. To suppress scatter in CBCT projections, we developed a focused, two-dimensional antiscatter grid (2DASG) prototype. In this work, we report on the primary and scatter transmission characteristics of the 2DASG prototype aimed for linac mounted, offset detector geometry CBCT systems in radiation therapy, and compared its performance to a conventional one-dimensional ASG (1DASG). The 2DASG is an array of through-holes separated by 0.1 mm septa that was fabricated from tungsten using additive manufacturing techniques. Through-holes' focusing geometry was designed for offset detector CBCT in Varian TrueBeam system. Two types of ASGs were evaluated: (a) a conventional 1DASG with a grid ratio of 10, (b) the 2DASG prototype with a grid ratio of 8.2. To assess the scatter suppression performance of both ASGs, Scatter-to-primary ratio (SPR) and scatter transmission fraction (Ts) were measured using the beam stop method. Scatter and primary intensities were modulated by varying the phantom thickness between 10 and 40 cm. Additionally, the effect of air gap and bow tie (BT) filter on SPR and Ts were evaluated. Average primary transmission fraction (T P ) and pixel specific primary transmission were also measured for both ASGs. To assess the effect of transmission characteristics on projection image signal-to-noise ratio (SNR), SNR improvement factor was calculated. Improvement in contrast to noise ratio (CNR) was demonstrated using a low contrast object. In comparison to 1DASG, 2DASG reduced SPRs by a factor of 3 to 6 across the range of phantom setups investigated. Ts values for 1D and 2DASGs were in the range of 21 to 29%, and 5 to 14% respectively. 2DASG continued to provide lower SPR and Ts at increased air gap and with BT filter. Tp of 1D and 2DASGs were 70.6% and 84.7% respectively. Due to the septal shadow of the 2DASG, its pixel

  20. Reliability assessment of single-phase grid-connected PV microinverters considering mission profile and uncertainties

    DEFF Research Database (Denmark)

    Zare, Mohammad Hadi; Mohamadian, Mustafa; Wang, Huai

    2017-01-01

    Microinverters usually connect a PV panel to a Single-phase power grid. In such system, the input power is constant while the output power oscillates twice the line frequency. Thus, the input and output power differences should be stored in a storage component, which is typically an electrolytic ...... irritation of two different places on the micro inverter lifetime is studied....... capacitor. However, electrolytic capacitors are usually blamed for their short lifetime. Recently, some active power decoupling methods are introduced in the literature which can takes advantage of high reliable film capacitors. However, some extra switches and diodes are added to the microinverter which...... can influence the microinverter lifetime. This paper investigates the microinverter reliability according to mission profile where it is installed. To get more accurate results, uncertainties in both lifetime model and manufacturing process are considered. The effect of ambient temperature and solar...

  1. Design for Reliability of Power Electronics for Grid-Connected Photovoltaic Systems

    DEFF Research Database (Denmark)

    Yang, Yongheng; Sangwongwanich, Ariya; Blaabjerg, Frede

    2016-01-01

    Power electronics is the enabling technology for optimizing energy harvesting from renewable systems like Photovoltaic (PV) and wind power systems, and also for interfacing grid-friendly energy systems. Advancements in the power semiconductor technology (e.g., wide band-gap devices) have pushed...... the conversion efficiency of power electronics to above 98%, where however te reliability of power electronics is becoming of high concern. Therefore, it is important to design for reliable power electronic systems to lower the risks of many failures during operation; otherwise will increase the cost...... for maintenance and reputation, thus affecting the cost of PV energy. Today's PV power conversion applications require the power electronic systems with low failure rates during a service life of 20 years or even more. To achieve so, it is vital to know the main life-limiting factors of power electronic systems...

  2. 76 FR 58716 - Interpretation of Transmission Planning Reliability Standard

    Science.gov (United States)

    2011-09-22

    ..., Western Public Agencies Group, Western Montana Electric G&T Cooperative, Inc., Oregon Municipal Electric... Enforcement of Electric Reliability Standards, Order No. 672, FERC Stats. & Regs. ] 31,204, order on reh'g... FERC ] 61,062, order on reh'g & compliance, 117 FERC ] 61,126 (2006), aff'd sub nom. Alcoa, Inc. v...

  3. Coverage and Rate of Downlink Sequence Transmissions with Reliability Guarantees

    DEFF Research Database (Denmark)

    Park, Jihong; Popovski, Petar

    2017-01-01

    Real-time distributed control is a promising application of 5G in which communication links should satisfy certain reliability guarantees. In this letter, we derive closed-form maximum average rate when a device (e.g. industrial machine) downloads a sequence of n operational commands through cell...

  4. Automatic remote monitoring utilizing daily transmissions: transmission reliability and implantable cardioverter defibrillator battery longevity in the TRUST trial.

    Science.gov (United States)

    Varma, Niraj; Love, Charles J; Schweikert, Robert; Moll, Philip; Michalski, Justin; Epstein, Andrew E

    2018-04-01

    Benefits of automatic remote home monitoring (HM) among implantable cardioverter defibrillator (ICD) patients may require high transmission frequency. However, transmission reliability and effects on battery longevity remain uncertain. We hypothesized that HM would have high transmission success permitting punctual guideline based follow-up, and improve battery longevity. This was tested in the prospective randomized TRUST trial. Implantable cardioverter defibrillator patients were randomized post-implant 2:1 to HM (n = 908) (transmit daily) or to Conventional in-person monitoring [conventional management (CM), n = 431 (HM disabled)]. In both groups, five evaluations were scheduled every 3 months for 15 months. Home Monitoring technology performance was assessed by transmissions received vs. total possible, and number of scheduled HM checks failing because of missed transmissions. Battery longevity was compared in HM vs. CM at 15 months, and again in HM 3 years post-implant using continuously transmitted data. Transmission success per patient was 91% (median follow-up of 434 days). Overall, daily HM transmissions were received in 315 795 of a potential 363 450 days (87%). Only 55/3759 (1.46%) of unsuccessful scheduled evaluations in HM were attributed to transmission loss. Shock frequency and pacing percentage were similar in HM vs. CM. Fifteen month battery longevity was 12% greater in HM (93.2 ± 8.8% vs. 83.5 ± 6.0% CM, P battery longevity was 50.9 ± 9.1% (median 52%) at 36 months. Automatic remote HM demonstrated robust transmission reliability. Daily transmission load may be sustained without reducing battery longevity. Home Monitoring conserves battery longevity and tracks long term device performance. ClinicalTrials.gov; NCT00336284.

  5. Development of high speed and reliable data transmission system for industrial CT

    International Nuclear Information System (INIS)

    Gao Fuqiang; Dong Yanli; Liu Guohua

    2010-01-01

    In order to meet the requirements of large capacity,high speed and high reliability of data transmission for industrial CT, a data transmission system based on USB 2.0 was designed. In the process of data transmission, FPGA was the main controller, and USB 2.0 CY7C68013A worked in slave FIFO mode. The system sent the data got from data acquisition system to host computer for image reconstruction. The testing results show that the transmission rate can reach 33 MB/s and the precision is 100%. The system satisfies the requirements of data transmission for industrial CT. (authors)

  6. Obligations to transmission grid enlargement and cooperation of operators of transmission grids after the enactment of EnLAG and the Third regulation of single market for electricity 2009/72 EG from 13th July, 2009; Netzausbau- und Kooperationsverpflichtungen der Uebertragungsnetzbetreiber nach Inkrafttreten des EnLAG und der Dritten StromRL 2009/72 EG vom 13.7.2009

    Energy Technology Data Exchange (ETDEWEB)

    Saecker, Franz Juergen [Hogan und Hartson Raue LLP/LBD Beratungsgesellschaft mbH, Berlin (Germany)

    2009-10-15

    paragraph 11 EnWG (Energy Economy Law) in the version of the Electricity Grid Expansion Act (EnLAG) obliges the operators of transmission grids to an optimization of transmission grids. The obligation for optimization refers to the development of the existing grids and to an extended co-operation of the operators of transmission grids for the improvement of the transmission of the electricity. Under this aspect, the author of the contribution under consideration reports on: (a) Contents of the obligation for the optimization of transmission grids and the development of transmission grids; (b) Fulfilment of the obligation for co-operation in accordance with paragraph 12 sect. 1 and paragraph 22 sect. 2 sentence 4 EnWG by forming a virtual grid company for the transmission of electricity; (c) Model of a cooperation contract; (d) Formation of a 'Deutsches Netz AG' as an alternative concept.

  7. System Reliability Evaluation of Data Transmission in Commercial Banks with Multiple Branches

    Directory of Open Access Journals (Sweden)

    Yi-Kuei Lin

    2014-01-01

    Full Text Available The main purpose of this paper is to assess the system reliability of electronic transaction data transmissions made by commercial banks in terms of stochastic flow network. System reliability is defined as the probability of demand satisfaction and it can be used to measure quality of service. In this paper, we study the system reliability of data transmission from the headquarters of a commercial bank to its multiple branches. The network structure of the bank and the probability of successful data transmission are obtained through the collection of real data. The system reliability, calculated using the minimal path method and the recursive sum of disjoint products algorithm, provides banking managers with a view to comprehend the current state of the entire system. Besides, the system reliability can be used not only as a measurement of quality of service, but also an improvement reference of the system by adopting sensitivity analysis.

  8. The Role of Demand Resources In Regional Transmission Expansion Planning and Reliable Operations

    Energy Technology Data Exchange (ETDEWEB)

    Kirby, Brendan J [ORNL

    2006-07-01

    Investigating the role of demand resources in regional transmission planning has provided mixed results. On one hand there are only a few projects where demand response has been used as an explicit alternative to transmission enhancement. On the other hand there is a fair amount of demand response in the form of energy efficiency, peak reduction, emergency load shedding, and (recently) demand providing ancillary services. All of this demand response reduces the need for transmission enhancements. Demand response capability is typically (but not always) factored into transmission planning as a reduction in the load which must be served. In that sense demand response is utilized as an alternative to transmission expansion. Much more demand response is used (involuntarily) as load shedding under extreme conditions to prevent cascading blackouts. The amount of additional transmission and generation that would be required to provide the current level of reliability if load shedding were not available is difficult to imagine and would be impractical to build. In a very real sense demand response solutions are equitably treated in every region - when proposed, demand response projects are evaluated against existing reliability and economic criteria. The regional councils, RTOs, and ISOs identify needs. Others propose transmission, generation, or responsive load based solutions. Few demand response projects get included in transmission enhancement plans because few are proposed. But this is only part of the story. Several factors are responsible for the current very low use of demand response as a transmission enhancement alternative. First, while the generation, transmission, and load business sectors each deal with essentially the same amount of electric power, generation and transmission companies are explicitly in the electric power business but electricity is not the primary business focus of most loads. This changes the institutional focus of each sector. Second

  9. Grid-code of Croatian power system

    International Nuclear Information System (INIS)

    Toljan, I.; Mesic, M.; Kalea, M.; Koscak, Z.

    2003-01-01

    Grid Rules by the Croatian Electricity Utility deal with the control and usage of the Croatian power system's transmission and distribution grid. Furthermore, these rules include obligations and permissions of power grid users and owners, with the aim of a reliable electricity supply.(author)

  10. DRDT: distributed and reliable data transmission with cooperative nodes for lossy wireless sensor networks.

    Science.gov (United States)

    Seo, Jaewan; Kim, Moonseong; Hur, In; Choi, Wook; Choo, Hyunseung

    2010-01-01

    Recent studies have shown that in realistic wireless sensor network environments links are extremely unreliable. To recover from corrupted packets, most routing schemes with an assumption of ideal radio environments use a retransmission mechanism, which may cause unnecessary retransmissions. Therefore, guaranteeing energy-efficient reliable data transmission is a fundamental routing issue in wireless sensor networks. However, it is not encouraged to propose a new reliable routing scheme in the sense that every existing routing scheme cannot be replaced with the new one. This paper proposes a Distributed and Reliable Data Transmission (DRDT) scheme with a goal to efficiently guarantee reliable data transmission. In particular, this is based on a pluggable modular approach so that it can be extended to existing routing schemes. DRDT offers reliable data transmission using neighbor nodes, i.e., helper nodes. A helper node is selected among the neighbor nodes of the receiver node which overhear the data packet in a distributed manner. DRDT effectively reduces the number of retransmissions by delegating the retransmission task from the sender node to the helper node that has higher link quality to the receiver node when the data packet reception fails due to the low link quality between the sender and the receiver nodes. Comprehensive simulation results show that DRDT improves end-to-end transmission cost by up to about 45% and reduces its delay by about 40% compared to existing schemes.

  11. DRDT: Distributed and Reliable Data Transmission with Cooperative Nodes for LossyWireless Sensor Networks

    Directory of Open Access Journals (Sweden)

    Jaewan Seo

    2010-03-01

    Full Text Available Recent studies have shown that in realistic wireless sensor network environments links are extremely unreliable. To recover from corrupted packets, most routing schemes with an assumption of ideal radio environments use a retransmission mechanism, which may cause unnecessary retransmissions. Therefore, guaranteeing energy-efficient reliable data transmission is a fundamental routing issue in wireless sensor networks. However, it is not encouraged to propose a new reliable routing scheme in the sense that every existing routing scheme cannot be replaced with the new one. This paper proposes a Distributed and Reliable Data Transmission (DRDT scheme with a goal to efficiently guarantee reliable data transmission. In particular, this is based on a pluggable modular approach so that it can be extended to existing routing schemes. DRDT offers reliable data transmission using neighbor nodes, i.e., helper nodes. A helper node is selected among the neighbor nodes of the receiver node which overhear the data packet in a distributed manner. DRDT effectively reduces the number of retransmissions by delegating the retransmission task from the sender node to the helper node that has higher link quality to the receiver node when the data packet reception fails due to the low link quality between the sender and the receiver nodes. Comprehensive simulation results show that DRDT improves end-to-end transmission cost by up to about 45% and reduces its delay by about 40% compared to existing schemes.

  12. Critical Assessment of the Foundations of Power Transmission and Distribution Reliability Metrics and Standards.

    Science.gov (United States)

    Nateghi, Roshanak; Guikema, Seth D; Wu, Yue Grace; Bruss, C Bayan

    2016-01-01

    The U.S. federal government regulates the reliability of bulk power systems, while the reliability of power distribution systems is regulated at a state level. In this article, we review the history of regulating electric service reliability and study the existing reliability metrics, indices, and standards for power transmission and distribution networks. We assess the foundations of the reliability standards and metrics, discuss how they are applied to outages caused by large exogenous disturbances such as natural disasters, and investigate whether the standards adequately internalize the impacts of these events. Our reflections shed light on how existing standards conceptualize reliability, question the basis for treating large-scale hazard-induced outages differently from normal daily outages, and discuss whether this conceptualization maps well onto customer expectations. We show that the risk indices for transmission systems used in regulating power system reliability do not adequately capture the risks that transmission systems are prone to, particularly when it comes to low-probability high-impact events. We also point out several shortcomings associated with the way in which regulators require utilities to calculate and report distribution system reliability indices. We offer several recommendations for improving the conceptualization of reliability metrics and standards. We conclude that while the approaches taken in reliability standards have made considerable advances in enhancing the reliability of power systems and may be logical from a utility perspective during normal operation, existing standards do not provide a sufficient incentive structure for the utilities to adequately ensure high levels of reliability for end-users, particularly during large-scale events. © 2015 Society for Risk Analysis.

  13. Broadcasting for stability of the grid. EEG-feeding devices for reliable control; Broadcasting bringt Stabilitaet ins Netz. EEG-Einspeiseanlagen zuverlaessig steuern

    Energy Technology Data Exchange (ETDEWEB)

    Dunker, Ralf [Press-n-Relations II GmbH, Muenchen (Germany)

    2011-01-31

    In order to connect as many renewable power plants as possible to the public grid without overloading it, control is indispensable. Load management by radio control is an attractive option both for grid operators and power suppliers according to EEG. LW radio transmission permits spontaneous switching at reasonable cost. The Wemag grid has been using this system since 2005.

  14. Detectors on Edge Nodes against False Data Injection on Transmission Lines of Smart Grid

    Directory of Open Access Journals (Sweden)

    Peng Xun

    2018-06-01

    Full Text Available False data injection (FDI attack is a hot topic in large-scale Cyber-Physical Systems (CPSs, which can cause bad state estimation of controllers. In this paper, we focus on FDI detection on transmission lines of the smart grid. We propose a novel and effective detection framework to identify FDI attacks. Different from the previous methods, there are multi-tier detectors which utilize edge nodes such as the programmable logic controllers (PLCs instead of the central controller to detect attacks. The proposed framework can decrease the transmission time of data to reduce the latency of decisions because many sensory data need not be transmitted to the central controller for detection. We also develop a detection algorithm which utilizes classifiers based on machine learning to identify FDI. The training process is split from every edge node and is placed on the central node. The detectors are lightweight and are properly adopted in our detection framework. Our simulation experiments show that the proposed detection framework can provide better detection results than the existing detection approaches.

  15. WE-AB-207A-10: Transmission Characteristics of a Two Dimensional Antiscatter Grid Prototype for CBCT

    Energy Technology Data Exchange (ETDEWEB)

    Altunbas, C; Kavanagh, B; Miften, M [University of Colorado School of Medicine, Aurora, CO (United States)

    2016-06-15

    Purpose: Scattered radiation remains to be a major contributor to image quality degradation in CBCT. To address the scatter problem, a focused, 2D antiscatter grid (2DASG) prototype was designed, and fabricated using additive manufacturing processes. Its scatter and primary transmission properties were characterized using a linac mounted CBCT system. Methods: The prototype 2DASG was composed of rectangular grid holes separated by tungsten septa, and has a grid pitch of 2.91 mm, grid ratio of 8, and a septal thickness of 0.1 mm. Each grid hole was aligned or focused towards the x-ray source in half-fan (i.e. offset detector) geometry of the Varian TrueBeam CBCT system. Scatter and primary transmission experiments were performed by using acrylic blocks and the beam-stop method. Transmission properties of a radiographic ASG (1DASG) (grid ratio of 10) was also performed by using the identical setup. Results: At 30 cm phantom thickness, scatter to primary ratio (SPR) was 4.51 without any ASG device. SPR was reduced to 1.28 with 1DASG, and it was further reduced to 0.28 with 2DASG. Scatter transmission fraction (Ts) of 1DASG was 21%, and Ts was reduced to 5.8% with 2DASG. The average primary transmission fraction (Tp) of 1DASG was 70.6%, whereas Tp increased to 85.1% with 2DASG. Variation of Tp across 40 cm length (the long axis of flat panel detector) was 2.6%. Conclusion: When compared to conventional ASGs, the focused 2DASG can vastly improve scatter suppression and primary transmission performance. Due to precise alignment of 2DASG’s grid holes with respect to beam divergence, high degree of primary transmission through the 2DASG was maintained across the full length of the prototype. We strongly believe that robust scatter rejection and primary transmission characteristics of our 2DASG can translate into both improved quantitative accuracy and soft tissue resolution in linac mounted CBCT systems.

  16. AC HTS Transmission Cable for Integration into the Future EHV Grid of the Netherlands

    OpenAIRE

    Zuijderduin, R.; Chevtchenko, O.; Smit, J.J.; Aanhaanen, G.; Melnik, I.; Geschiere, A.

    2012-01-01

    Due to increasing power demand, the electricity grid of the Netherlands is changing. The future grid must be capable to transmit all the connected power. Power generation will be more decentralized like for instance wind parks connected to the grid. Furthermore, future large scale production units are expected to be installed near coastal regions. This creates some potential grid issues, such as: large power amounts to be transmitted to consumers from west to east and grid stability. High tem...

  17. Cross Layer Design for Optimizing Transmission Reliability, Energy Efficiency, and Lifetime in Body Sensor Networks.

    Science.gov (United States)

    Chen, Xi; Xu, Yixuan; Liu, Anfeng

    2017-04-19

    High transmission reliability, energy efficiency, and long lifetime are pivotal issues for wireless body area networks (WBANs. However, these performance metrics are not independent of each other, making it hard to obtain overall improvements through optimizing one single aspect. Therefore, a Cross Layer Design Optimal (CLDO) scheme is proposed to simultaneously optimize transmission reliability, energy efficiency, and lifetime of WBANs from several layers. Firstly, due to the fact that the transmission power of nodes directly influences the reliability of links, the optimized transmission power of different nodes is deduced, which is able to maximize energy efficiency in theory under the premise that requirements on delay and jitter are fulfilled. Secondly, a relay decision algorithm is proposed to choose optimized relay nodes. Using this algorithm, nodes will choose relay nodes that ensure a balance of network energy consumption, provided that all nodes transmit with optimized transmission power and the same packet size. Thirdly, the energy consumption of nodes is still unbalanced even with optimized transmission power because of their different locations in the topology of the network. In addition, packet size also has an impact on final performance metrics. Therefore, a synthesized cross layer method for optimization is proposed. With this method, the transmission power of nodes with more residual energy will be enhanced while suitable packet size is determined for different links in the network, leading to further improvements in the WBAN system. Both our comprehensive theoretical analysis and experimental results indicate that the performance of our proposed scheme is better than reported in previous studies. Relative to the relay selection and power control game (RSPCG) scheme, the CLDO scheme can enhance transmission reliability by more than 44.6% and prolong the lifetime by as much as 33.2%.

  18. A Design of a 345-kV Electric Power Transmission Line Interlinking Ramu and Rouna Grids in Papua New Guinea

    Directory of Open Access Journals (Sweden)

    Sakato Francis

    2017-01-01

    Full Text Available According to PNG Power Limited (PPL, Papua New Guinea’s peak power demand is expected to increase from 210 MW in 2012 to 347 MW in 2026. Under the current state of the power sector in Papua New Guinea (PNG, it is critical to implement measures to cope with the increasing power demand to promote investment, economic growth, and ultimately to achieve poverty reduction through economic growth. One of the solutions identified to improve the reliability of PNG power systems and thus to meet the demand is to interconnect the major grids in the country so that the loads could be shared among them. This project embarks in designing a 345-kV electric power transmission line to interlink the Ramu and Rouna power grids of Papua New Guinea. The design is done by analysing all the necessary aspects of the transmission lines with in-depth calculations performed using MATHCAD software. This design is the basis for extra-high voltage (EHV transmission network in anticipation for the power generation and demand growth in PNG.

  19. The Impact of Grid Unbalances on the Reliability of DC-link Capacitors in a Motor Drive

    DEFF Research Database (Denmark)

    Wang, Huai; Davari, Pooya; Kumar, Dinesh

    2017-01-01

    DC-link capacitor is one of the reliability-critical components in motor drive applications, which contributes to a considerable cost, size and failure. Its reliability performance depends on both inherent physical strength and external loading. The grid unbalances could alter the electro......-thermal stresses of key components in a motor drive. Therefore, this digest investigates the impact of grid voltage amplitude and phase unbalances on the lifetime of DC-link capacitors used in a standard three-phase motor drive. The theoretical stress models and experimental measurements of the capacitor voltages...... and ripple currents are presented. The relationship between the DC-link capacitor lifetime and the level of unbalances and loads are discussed based on a 7.5 kW motor drive system. The results serve as a guideline to size the DC-link capacitors to be robust enough at the presence of grid unbalance conditions....

  20. Comprehensive automation and monitoring of MV grids as the key element of improvement of energy supply reliability and continuity

    Directory of Open Access Journals (Sweden)

    Stanisław Kubacki

    2012-03-01

    Full Text Available The paper presents the issue of comprehensive automation and monitoring of medium voltage (MV grids as a key element of the Smart Grid concept. The existing condition of MV grid control and monitoring is discussed, and the concept of a solution which will provide the possibility of remote automatic grid reconfiguration and ensure full grid observability from the dispatching system level is introduced. Automation of MV grid switching is discussed in detail to isolate a faulty line section and supply electricity at the time of the failure to the largest possible number of recipients. An example of such automation controls’ operation is also presented. The paper’s second part presents the key role of the quick fault location function and the possibility of the MV grid’s remote reconfiguration for improving power supply reliability (SAIDI and SAIFI indices. It is also shown how an increase in the number of points fitted with faulted circuit indicators with the option of remote control of switches from the dispatch system in MV grids may affect reduction of SAIDI and SAIFI indices across ENERGA-OPERATOR SA divisions.

  1. Experimental evaluation of prefiltering for 56 Gbaud DP-QPSK signal transmission in 75 GHz WDM grid

    DEFF Research Database (Denmark)

    Borkowski, Robert; de Carvalho, Luis Henrique H.; Silva, Edson Porto da

    2014-01-01

    We investigate optical prefiltering for 56Gbaud (224Gbit/s) electrical time-division multiplexed (ETDM) dual polarization (DP) quaternary phase shift keying (QPSK) transmission. Different transmitter-side optical filter shapes are tested and their bandwidths are varied. Comparison of studied filter...... shapes shows an advantage of a pre-emphasis filter. Subsequently, we perform a fiber transmission of the 56Gbaud DP QPSK signal filtered with the 65GHz pre-emphasis filter to fit the 75GHz transmission grid. Bit error rate (BER) of the signal remains below forward error correction (FEC) limit after 300km...

  2. Studies of soft x-ray transmission through grid supported CH layers

    Science.gov (United States)

    Davis, J. S.; Keiter, P. A.; Klein, S. R.; Frank, Y.; Drake, R. P.; Shvarts, D.

    2017-10-01

    Recent experiments have shown that it may be possible to use laser-heated high-Z foils to drive new radiation transport (RadTran) experiments in gas fill tubes. These tubes must be pressurized above 1atm and the x-ray source needs to be physically separated from the gas. To achieve this, a grid-supported CH seal is implemented. The grid reduces the total surface area of the gas-seal interaction region lowering the thickness requirements for the CH layer. However, as mesh spacing is reduced, hole closure from wire ablation may reduce the x-ray flux. To optimize the seal design, experiments were performed measuring x-ray transmission through CH layers supported by meshes composed of copper, gold, or stainless steel and using hexagonal or square mesh geometries. The x-ray source was formed by heating a 0.5 μm thick planar gold foil with a 4 ns laser pulse at an intensity of 2 ×1014 W / cm 2. Emission data was collected using an x-ray framing camera and a Dante photodiode array. Experiments show that the CH layers can reach effective temperatures of nearly 100 eV but mesh design significantly affects performance, with a nearly 20 eV difference between the best and worst performing seal targets. This talk will discuss our findings and their impact on future RadTran experiments. This work is funded by the U.S. DOE, through the NNSA-DS and SC-OFES Joint Program in HED Laboratory Plasmas, Grant Number DE-NA0001840, the National LUFP, Grant Number DE-NA0000850, and through NNSA/OICF under Cooperatvie Agreement No. DE-FC52-08NA2830.

  3. Reliability assessment of wind farm-connected grids using Monte-Carlo testing

    Energy Technology Data Exchange (ETDEWEB)

    Belanger, Jean; Dufour, Christian [Opal-RT Technologies Inc., Montreal, QC (Canada); Paquin, Jean-Nicolas [BBA Inc., Mont-Saint-Hilaire, QC (Canada)

    2010-07-01

    The future of the power grid lies in large scale integration of distributed generation devices with the utility system, at either a medium- or low-voltage level. These new distribued generation technologies can offer benefits and opportunities to manufacturers and utilities in need of supplementary energy sources. However, a large increase in the number of distributed generation interconnections may potentially cause a number of technical concerns relating to the operation of the system in question. Because existing distribution networks were not originally designed to include complex distributed power-electronic systems, detailed testing of existing and future protection and control devices is necessary. The growing use of photovoltaic devices, wind turbines and other complex power electronic systems is changing the nature of distribution systems. The performance and stresses on wind farm and microgrid components will therefore depend on control and protection system reaction. In fact, this new generation of intelligent microgrids is becoming as complex as sophisticated high-voltage AC/DC transmission systems. This paper describes how the Monte Carlo simulation technique and parallel simulators can be used to evaluate worst-case stresses for different fault and operating conditions. (orig.)

  4. A reliable transmission protocol for ZigBee-based wireless patient monitoring.

    Science.gov (United States)

    Chen, Shyr-Kuen; Kao, Tsair; Chan, Chia-Tai; Huang, Chih-Ning; Chiang, Chih-Yen; Lai, Chin-Yu; Tung, Tse-Hua; Wang, Pi-Chung

    2012-01-01

    Patient monitoring systems are gaining their importance as the fast-growing global elderly population increases demands for caretaking. These systems use wireless technologies to transmit vital signs for medical evaluation. In a multihop ZigBee network, the existing systems usually use broadcast or multicast schemes to increase the reliability of signals transmission; however, both the schemes lead to significantly higher network traffic and end-to-end transmission delay. In this paper, we present a reliable transmission protocol based on anycast routing for wireless patient monitoring. Our scheme automatically selects the closest data receiver in an anycast group as a destination to reduce the transmission latency as well as the control overhead. The new protocol also shortens the latency of path recovery by initiating route recovery from the intermediate routers of the original path. On the basis of a reliable transmission scheme, we implement a ZigBee device for fall monitoring, which integrates fall detection, indoor positioning, and ECG monitoring. When the triaxial accelerometer of the device detects a fall, the current position of the patient is transmitted to an emergency center through a ZigBee network. In order to clarify the situation of the fallen patient, 4-s ECG signals are also transmitted. Our transmission scheme ensures the successful transmission of these critical messages. The experimental results show that our scheme is fast and reliable. We also demonstrate that our devices can seamlessly integrate with the next generation technology of wireless wide area network, worldwide interoperability for microwave access, to achieve real-time patient monitoring.

  5. A Markovian Approach Applied to Reliability Modeling of Bidirectional DC-DC Converters Used in PHEVs and Smart Grids

    Directory of Open Access Journals (Sweden)

    M. Khalilzadeh

    2016-12-01

    Full Text Available In this paper, a stochastic approach is proposed for reliability assessment of bidirectional DC-DC converters, including the fault-tolerant ones. This type of converters can be used in a smart DC grid, feeding DC loads such as home appliances and plug-in hybrid electric vehicles (PHEVs. The reliability of bidirectional DC-DC converters is of such an importance, due to the key role of the expected increasingly utilization of DC grids in modern Smart Grid. Markov processes are suggested for reliability modeling and consequently calculating the expected effective lifetime of bidirectional converters. A three-leg bidirectional interleaved converter using data of Toyota Prius 2012 hybrid electric vehicle is used as a case study. Besides, the influence of environment and ambient temperature on converter lifetime is studied. The impact of modeling the reliability of the converter and adding reliability constraints on the technical design procedure of the converter is also investigated. In order to investigate the effect of leg increase on the lifetime of the converter, single leg to five-leg interleave DC-DC converters are studied considering economical aspect and the results are extrapolated for six and seven-leg converters. The proposed method could be generalized so that the number of legs and input and output capacitors could be an arbitrary number.

  6. Reliability assessment platform for the power semiconductor devices - Study case on 3-phase grid-connected inverter application

    DEFF Research Database (Denmark)

    Vernica, Ionut; Ma, Ke; Blaabjerg, Frede

    2017-01-01

    provide valuable reliability information based on given mission profiles and system specification is first developed and its main concept is presented. In order to facilitate the test and access to the loading and lifetime information of the power devices, a novel mission profile based stress emulator...... experimental setup is proposed and designed. The link between the stress emulator setup and the reliability tool software is highlighted. Finally, the reliability assessment platform is demonstrated on a 3-phase grid-connected inverter application study case....

  7. 75 FR 4375 - Transmission Loading Relief Reliability Standard and Curtailment Priorities

    Science.gov (United States)

    2010-01-27

    ... the curtailment priorities set forth in the Commission's pro forma open access transmission tariff... prevent or manage potential or actual system operating limit or interconnection reliability operating...). \\2\\ A System Operating Limit or SOL is the value (such as MW, MVar, amperes, frequency or volts) that...

  8. AC HTS Transmission Cable for Integration into the Future EHV Grid of the Netherlands

    NARCIS (Netherlands)

    Zuijderduin, R.; Chevtchenko, O.; Smit, J.J.; Aanhaanen, G.; Melnik, I.; Geschiere, A.

    2012-01-01

    Due to increasing power demand, the electricity grid of the Netherlands is changing. The future grid must be capable to transmit all the connected power. Power generation will be more decentralized like for instance wind parks connected to the grid. Furthermore, future large scale production units

  9. Puget Sound Area Electric Reliability Plan : Appendix E, Transmission Reinforcement Analysis.

    Energy Technology Data Exchange (ETDEWEB)

    United States. Bonneville Power Administration.

    1992-04-01

    The purpose of this appendix to the draft environmental impact statement (EIS) report is to provide an update of the latest study work done on transmission system options for the Puget Sound Area Electric Reliability Plan. Also included in the attachments to the EIS are 2 reports analyzing the voltage stability of the Puget Sound transmission system and a review by Power Technologies, Inc. of the BPA voltage stability analysis and reactive options. Five transmission line options and several reactive options are presently being considered as possible solutions to the PSAFRP by the Transmission Team. The first two line options would be built on new rights-of way adjacent (as much as possible) to existing corridors. The reactive options would optimize the existing transmission system capability by adding new stations for series capacitors and/or switchgear. The other three line options are rebuilds or upgrades of existing cross mountain transmission lines. These options are listed below and include a preliminary assessment of the additional transmission system reinforcement required to integrate the new facilities into the existing transmission system. Plans were designed to provide at least 500 MVAR reactive margin.

  10. HTS Transmission Cable System for installation in the Long Island Power Grid

    Energy Technology Data Exchange (ETDEWEB)

    Schmidt, Frank [American Superconductor Corporation, Devens, MA (United States); Durand, Fabien [American Superconductor Corporation, Devens, MA (United States); Maguire, James [American Superconductor Corporation, Devens, MA (United States)

    2015-10-05

    Department of Energy (DOE) Award DE-FC26-07NT43240 was issued on October 1, 2007. Referred to as LIPA2, the principal objectives of the project were to develop key components required to deploy and demonstrate second-generation (2G) high temperature superconductor (HTS) cables in a 600 meter (2000 feet) underground segment of a 138kV three-phase transmission circuit of the Long Island Power Authority (LIPA) power grid. A previous effort under DOE Award DE-FC36-03GO13032 (referred to as LIPA1) resulted in installation (and subsequent successful operation) of first-generation (1G) HTS cables at the LIPA site. As with LIPA1, American Superconductor (AMSC) led the effort for LIPA2 and was responsible for overall management of the project and producing sufficient 2G wire to fabricate the required cable. Nexans' tasks included design/manufacture/installation of the cable, joint (splice), cable terminations and field repairable cryostat; while work by Air Liquide involved engineering and installation support for the refrigeration system modifications.

  11. A Cognitive Radio-Based Energy-Efficient System for Power Transmission Line Monitoring in Smart Grids

    Directory of Open Access Journals (Sweden)

    Saeed Ahmed

    2017-01-01

    Full Text Available The research in industry and academia on smart grids is predominantly focused on the regulation of generated power and management of its consumption. Because transmission of bulk-generated power to the consumer is immensely reliant on secure and efficient transmission grids, comprising huge electrical and mechanical assets spanning a vast geographic area, there is an impending need to focus on the transmission grids as well. Despite the challenges in wireless technologies for SGs, cognitive radio networks are considered promising for provisioning of communications services to SGs. In this paper, first, we present an IEEE 802.22 wireless regional area network cognitive radio-based network model for smart monitoring of transmission lines. Then, for a prolonged lifetime of battery finite monitoring network, we formulate the spectrum resource allocation problem as an energy efficiency maximization problem, which is a nonlinear integer programming problem. To solve this problem in an easier way, we propose an energy-efficient resource-assignment scheme based on the Hungarian method. Performance analysis shows that, compared to a pure opportunistic assignment scheme with a throughput maximization objective and compared to a random scheme, the proposed scheme results in an enhanced lifetime while consuming less battery energy without compromising throughput performance.

  12. An improved IEEE 802.11 protocol for reliable data transmission in power distribution fault diagnosis

    Energy Technology Data Exchange (ETDEWEB)

    Campoccia, F.; Di Silvestre, M.L.; Sanseverino, E.R.; Zizzo, G. [Palermo Univ., Palermo (Italy)

    2010-10-15

    In power systems, on-line transmission between local units and the central unit can be done by means of power line communications or wireless technology. During an electrical fault, the reliability of the distribution system depends on the security of the timely protective and restorative actions on the network. This paper focused on the WiFi system because of its economy and ease of installation. However, WiFi systems are typically managed by the IEEE 802.11 protocol, which is not reliable in terms of security in data communication. In WiFi networks, data is divided into packets and sent in succession to reduce errors within the radio channel. The IEEE 802.11 protocol has high probability for loss of packets or delay in their transmission. In order to ensure the reliability of data transmission times between two terminal units connected by WiFi stations, a new protocol was derived by modifying the IEEE 802.11. The improvements of the new protocol were highlighted and its capability for the diagnostic service was verified. The modified protocol eliminates the danger of collisions between packets and optimizes the transmission time for sending information. 6 refs., 7 tabs., 8 figs.

  13. Cross-border trading and transmission networks: a model for competition in natural gas and electricity grids

    International Nuclear Information System (INIS)

    Hogan, W.W.

    1992-01-01

    Cross border energy trading, for which transmission networks are a vital policy, is expanding. Within an environment of competition and open access, reform of transmission pricing, access and investment is needed. A theoretical framework for such reform is outlined. The design objectives advocated are to maintain a reliable service; to provide economic efficiency; to allow for long-term transmission contracts; to arrange compensation through a settlements system; to allow decomposition by region and company and to preserve administrative feasibility. A ''contract network'' model for transmission rights in a network is discussed. (UK)

  14. Reliability of Ceramic Column Grid Array Interconnect Packages Under Extreme Temperatures

    Science.gov (United States)

    Ramesham, Rajeshuni

    2011-01-01

    A paper describes advanced ceramic column grid array (CCGA) packaging interconnects technology test objects that were subjected to extreme temperature thermal cycles. CCGA interconnect electronic package printed wiring boards (PWBs) of polyimide were assembled, inspected nondestructively, and, subsequently, subjected to ex - treme-temperature thermal cycling to assess reliability for future deep-space, short- and long-term, extreme-temperature missions. The test hardware consisted of two CCGA717 packages with each package divided into four daisy-chained sections, for a total of eight daisy chains to be monitored. The package is 33 33 mm with a 27 27 array of 80%/20% Pb/Sn columns on a 1.27-mm pitch. The change in resistance of the daisy-chained CCGA interconnects was measured as a function of the increasing number of thermal cycles. Several catastrophic failures were observed after 137 extreme-temperature thermal cycles, as per electrical resistance measurements, and then the tests were continued through 1,058 thermal cycles to corroborate and understand the test results. X-ray and optical inspection have been made after thermal cycling. Optical inspections were also conducted on the CCGA vs. thermal cycles. The optical inspections were conclusive; the x-ray images were not. Process qualification and assembly is required to optimize the CCGA assembly, which is very clear from the x-rays. Six daisy chains were open out of seven daisy chains, as per experimental test data reported. The daisy chains are open during the cold cycle, and then recover during the hot cycle, though some of them also opened during the hot thermal cycle..

  15. Expected Range of Cooperation Between Transmission System Operators and Distribution System Operators After Implementation of ENTSO-E Grid Codes

    Directory of Open Access Journals (Sweden)

    Tomasz Pakulski

    2015-06-01

    Full Text Available The authors present the prospects of cooperation between transmission system operators (TSO and distribution system operators (DSO after entry into force ENTSO-E (European Network of Transmission System Operators for Electricity grid codes. New areas of DSO activities, associated with offering TSO aggregated services for national power system regulation based on the regulation resources connected to the distribution grid, and services on the distribution system level as part of the creation of local balancing areas (LBA are presented. The paper also presents the possibilities of providing ancillary services by different types of distributed generation sources in the distribution network. The LBA concept, which involves integrated management of local regulation resources including generation, demand, and energy storage is described. The options of the renewable energy sources (RES using for voltage and reactive power control in the distribution network with the use of wind farms (WF connected to the distribution system are characterized.

  16. The planning of transmission grids. Conditions of the energy policy turnaround; Die Planung der Uebertragungsnetze. Bedingung der Energiewende.

    Energy Technology Data Exchange (ETDEWEB)

    Witt, Siegfried de; Durinke, Peter; Kause, Harriet [DE WITT Rechtsanwaltsgesellschaft mbH, Berlin (Germany)

    2012-07-01

    The book reports on planning processes for the power transmission grid. The design and implementation of a high-voltage line of the transmission system consists of four stages (Part I): (a) National planning of requirements; (b) Planning procedures or federal sector planning; (c) Planning approval procedure; (d) Expropriation proceedings. Part II of this book describes the planning according to the Energy Economy Law (EnWG) and Electricity Grid Expansion Act (EnLAG). The Part III of the book under consideration describes the procedures to be taken out by the NABEG (Act for the Acceleration of Network Expansion) from the scope of paragraph 15 ROG (Regional Planning Act) and paragraph 43 EnWG.

  17. On a simulation study for reliable and secured smart grid communications

    Science.gov (United States)

    Mallapuram, Sriharsha; Moulema, Paul; Yu, Wei

    2015-05-01

    Demand response is one of key smart grid applications that aims to reduce power generation at peak hours and maintain a balance between supply and demand. With the support of communication networks, energy consumers can become active actors in the energy management process by adjusting or rescheduling their electricity usage during peak hours based on utilities pricing incentives. Nonetheless, the integration of communication networks expose the smart grid to cyber-attacks. In this paper, we developed a smart grid simulation test-bed and designed evaluation scenarios. By leveraging the capabilities of Matlab and ns-3 simulation tools, we conducted a simulation study to evaluate the impact of cyber-attacks on demand response application. Our data shows that cyber-attacks could seriously disrupt smart grid operations, thus confirming the need of secure and resilient communication networks for supporting smart grid operations.

  18. Wind Farm Grid Integration Using VSC Based HVDC Transmission - An Overview

    DEFF Research Database (Denmark)

    Chaudhary, Sanjay Kumar; Teodorescu, Remus; Rodriguez, Pedro

    2008-01-01

    The paper gives an overview of HVAC and HVDC connection of wind farm to the grid, with an emphasis on Voltage Source Converter (VSC)-based HVDC for large wind farms requiring long distance cable connection. Flexible control capabilities of a VSC-based HVDC system enables smooth integration of wind...... farm into the power grid network while meeting the Grid Code Requirements (GCR). Operation of a wind farm with VSC-based HVDC connection is described....

  19. SEA for strategic grid planning in South Africa: Enabling the efficient and effective roll out of strategic electricity transmission infrastructure

    CSIR Research Space (South Africa)

    Fischer, TD

    2016-05-01

    Full Text Available | Resilience and Sustainability 36th Annual Conference of the International Association for Impact Assessment 11 - 14 May 2016 | Nagoya Congress Center | Aichi-Nagoya | Japan | www.iaia.org SEA FOR STRATEGIC GRID PLANNING IN SOUTH AFRICA: Enabling... the efficient and effective roll out of strategic electricity transmission infrastructure Abstract ID: 409 Authors: Marshall Mabin(1) , Paul Lochner and Dee Fischer Council for Scientific and Industrial Research (CSIR), PO Box 320 Stellenbosch 7599 South...

  20. Probability of extreme interference levels computed from reliability approaches: application to transmission lines with uncertain parameters

    International Nuclear Information System (INIS)

    Larbi, M.; Besnier, P.; Pecqueux, B.

    2014-01-01

    This paper deals with the risk analysis of an EMC default using a statistical approach. It is based on reliability methods from probabilistic engineering mechanics. A computation of probability of failure (i.e. probability of exceeding a threshold) of an induced current by crosstalk is established by taking into account uncertainties on input parameters influencing levels of interference in the context of transmission lines. The study has allowed us to evaluate the probability of failure of the induced current by using reliability methods having a relative low computational cost compared to Monte Carlo simulation. (authors)

  1. Adaptable System Increasing the Transmission Speed and Reliability in Packet Network by Optimizing Delay

    Directory of Open Access Journals (Sweden)

    Zbynek Kocur

    2014-01-01

    Full Text Available There is a great diversity in the transmission technologies in current data networks. Individual technologies are in most cases incompatible at physical and partially also at the link layer of the reference ISO/OSI model. Network compatibility, as the ability to transmit data, is realizable through the third layer, which is able to guarantee the operation of the different devices across their technological differences. The proposed inverse packet multiplexer addresses increase of the speed and reliability of packet transmission to the third layer, and at the same time it increases the stability of the data communication by the regulation of the delay value during the transmission. This article presents implementation of a communication system and its verification in real conditions. The conclusion compares the strengths and weaknesses of the proposed control system.

  2. Enhancing the reliability of AC transmission networks by using a long distance HVDC-link

    Energy Technology Data Exchange (ETDEWEB)

    Fleckenstein, Marco; Balzer, Gerd; Wasserrab, Andreas; Neumann, Claus [Technische Univ. Darmstadt (Germany). Inst. of Electrical Power and Energy

    2012-07-01

    The absorption of energy from offshore wind farms is a difficult task for Transmission system operators (TSO) in Germany, even if no offshore wind farm is connected directly. The role of the TSOs in the north it is to transport this energy to the south of Germany. The transmission capacities of overhead lines are limited. With the expected rapid expansion of wind farms, this is no longer enough. Thus, the transmission system must be enhanced. One possibility is the installation of an HVDC link from north to south between two main substations in the 380 kV network. Based on a realistic case study, the impact of such a link on the reliability of the entire extra high voltage network is shown. (orig.)

  3. Exploring Relay Cooperation for Secure and Reliable Transmission in Two-HopWireless Networks

    Directory of Open Access Journals (Sweden)

    Yulong Shen

    2014-03-01

    Full Text Available This work considers the problem of secure and reliable information transmission via relay cooperation in two-hop relay wireless networks without the information of both eavesdropper channels and locations. While previous work on this problem mainly studied infinite networks and their asymptotic behavior and scaling law results, this papers focuses on a more practical network with finite number of system nodes and explores the corresponding exact result on the number of eavesdroppers one network can tolerate to ensure desired secrecy and reliability. We first study the scenario where path-loss is equal between all pairs of nodes and consider two transmission protocols there, one adopts an optimal but complex relay selection process with less load balance capacity while the other adopts a random but simple relay selection process with good load balance capacity. Theoretical analysis and numerical results are then provided to determine the maximum number of eavesdroppers one network can tolerate to ensure a desired performance in terms of the secrecy outage probability and transmission outage probability. We further extend our study to the more general scenario where path-loss between each pair of nodes also depends on the distance between them, for which a new transmission protocol with both preferable relay selection and good load balance as well as the corresponding theoretical analysis and numerical results are presented.

  4. The Annual Allowed Revenue growth of basic transmission grid face the expansion of transmission system; O crescimento da receita anual permitida da rede basica face a expansao do sistema de transmissao

    Energy Technology Data Exchange (ETDEWEB)

    Vieira, Isabela Sales; Camargo, Ivan Marques de Toledo [Universidade de Brasilia (UnB), DF (Brazil)

    2008-07-01

    Since the separation between the purchase and sale of electric energy and contracts for access and use of transmission systems, in 1999, when the first Annual Allowed Revenue of the transmission concessionaires was established, to the last Annual Revenue readjustment, in 2007, the revenue of the basic transmission grid more than quadruplicated. The growth of the Allowed Annual Revenue of the main transmission grid has raised questions about the excessive growth of the transmission system. However, despite the significant evolution of the basic transmission grid in the last years, it can be observed that since 2003 the growth curve of the Annual Allowed Revenue moved away from the transmission system growth curve. Between years 2000 and 2007, while the transmission system grew in average 4% per year, the average tax of growth of the Allowed Annual Revenue was superior 20% per year. Two facts contributed for this behavior - the great growth of IGP-M index, mainly between years 2002 and 2003, and the great difference between the Annual Allowed Revenue for the transmission installations existing in 1999 and the Maximum Annual Revenue for the new transmission installations, connected to the transmission grid since then. (author)

  5. Investigating the impact of unanticipated market and construction delays on the development of a meshed HVDC grid using dynamic transmission planning

    NARCIS (Netherlands)

    Shariat Torbaghan, S.; Gibescu, M.; Rawn, B.G.; Müller, H.; Roggenkamp, M.; vd Meijden, M.A.M.M.

    2015-01-01

    This study presents a market-based dynamic transmission planning framework for the construction of a meshed offshore voltage source converter-high voltage direct current (VSC-HVDC) grid. Such a grid is foreseen for integrating offshore wind and electricity trade functions among the North Sea

  6. Reliability and Energy Loss in Full-scale Wind Power Converter Considering Grid Codes and Wind Classes

    DEFF Research Database (Denmark)

    Zhou, Dao; Blaabjerg, Frede; Franke, Toke

    2014-01-01

    With the increasing penetration of the wind power, reliable operation and cost-effective wind energy production are of more and more importance. As one of the promising configurations, the cost on reliability and production losses of permanent-magnet synchronous generator based full-scale wind......, if the specific designed wind turbine system operates at different wind classes, it can be seen that higher wind class level results in lower lifetime of the power converter. In respect to the cost of the reactive power, either the OE or the UE reactive power increases the energy loss per year significantly...... power converter is studied considering the grid code with reactive power production as well as the annual wind profile. Regarding the reliability, it is found that either the Over-Excited (OE) or the Under-Excited (UE) reactive power injection threatens the lifespan under all wind classes. Meanwhile...

  7. Efficiency and reliability improvement in wind turbine converters by grid converter adaptive control

    DEFF Research Database (Denmark)

    Trintis, Ionut; Munk-Nielsen, Stig; Abrahamsen, Flemming

    2013-01-01

    This paper presents a control method that reduces the losses in wind turbine converters adaptively controlling the grid converter. The dc-link voltage adapts its reference based on the system state and therefore reduces the stored energy, and is therefore kept at the minimum necessary for the grid...... and generator side. Operating in this way, the electrical and thermal stress factors are decreased on the power electronic devices, increasing their lifetime. The simulation results using this method show efficiency increase and devices temperature cycles slightly decreased. Experimental results on a wind...... turbine power stack shows efficiency increase in the high power region....

  8. Contribution to calculating characteristics of power transmission of relevance to technical reliability

    Energy Technology Data Exchange (ETDEWEB)

    Voigt, B

    1982-02-19

    The possibilities are shown how input parameters are determined for reliability computations. This is done for the components of a transmission system and the evaluated failure statistics of an electric utility company. The following parameters of high interest to reliability engineering are treated: dependence of the failure frequency on the system's cable length, distribution of failure intervals of cables with different voltage levels, followerd by a study of influencing variables due to daily or seasonal fluctuations. Possibilities are pointed out of computing the system reliability on the basis of component parameters, and a method is presented that can be applied in the planning stage as well as during operation of energy transmission systems. Finally, the calculation of a real sub-net of a given energy supply is presented. The methodology of fault-tree analysis, implemented in several, different computer programs, is the input parameter of this section. This method is applied to determine minimum interface structures of a system, to simulating the TOP event in the fault tree and, in the method presented here, to determining the structural significance of components within a system.

  9. Optimized Reactive Power Flow of DFIG Power Converters for Better Reliability Performance Considering Grid Codes

    DEFF Research Database (Denmark)

    Zhou, Dao; Blaabjerg, Frede; Lau, Mogens

    2015-01-01

    . In order to fulfill the modern grid codes, over-excited reactive power injection will further reduce the lifetime of the rotor-side converter. In this paper, the additional stress of the power semiconductor due to the reactive power injection is firstly evaluated in terms of modulation index...

  10. Grid Integration Research | Wind | NREL

    Science.gov (United States)

    Grid Integration Research Grid Integration Research Researchers study grid integration of wind three wind turbines with transmission lines in the background. Capabilities NREL's grid integration electric power system operators to more efficiently manage wind grid system integration. A photo of

  11. A cost-efficient and reliable energy management of a micro-grid using intelligent demand-response program

    International Nuclear Information System (INIS)

    Safamehr, Hossein; Rahimi-Kian, Ashkan

    2015-01-01

    Providing a cost-efficient and reliable energy is one of the main issues in human societies of the 21st century. In response to this demand, new features of micro grid technology have provided huge potentials, specifically by the capability of having an interactive coordination between energy suppliers and consumers. Accordingly, this paper offers an improved model for achieving an optimal Demand Response programing. To solve the proposed multi-objective optimization problem, Artificial Bee Colony algorithm and quasi-static technique are utilized. The considered objectives in this paper are minimizing the overall cost of energy consumption and also improving the technical parameters of micro grid over a time horizon. This optimization is subject to several constraints such as satisfying the energy balance and the operating constraints of each energy supply sources. Manageable load or load as source is another enabling feature existing in smart energy networks, which is considered in this paper and its effect on cost reduction and reliability improvement is studied. Trying to examine the performance of the proposed Demand Response Programing in real conditions, the uncertainties are also analyzed by stochastic methods. The results show significant improvements which are obtained by applying just intelligent programming and management. - Highlights: • This paper presents a cost-efficient and reliable energy management of a micro-grid. • New models of battery and manageable loads are formulated. • Artificial Bee Colony algorithm is used to solve the optimization problem. • Quasi-static technique is used to simplify the solving procedure. • The uncertainties are also analyzed by stochastic methods.

  12. Analysis of different power grid segmentation and transmission schemes for power system security improvement

    International Nuclear Information System (INIS)

    Shami, U.T.; Chaudhary, M.S.

    2015-01-01

    This paper explores the power grid segmentation concept for power system stability improvement in detail. First, the firewall property of grid segmentation is investigated for a two area network. Then two HVDC technologies, LCC and VSC, are compared for the same network. A two area VSC-AC segmented network is then compared with two area VSC segmented network. Suitable segmentation topology and suitable number of VSC segmented areas are then investigated. Simulation results show that grid segmentation offers network stability during fault conditions and VSC is the most suitable choice for segmentation over LCC. Results further show that having large number of DC segmented areas and using the radial segmentation topology improves the stability of the overall system. All the simulations were carried out in PSS at the rate E software provided by SIEMENS discussed. Section IV discusses the test systems under study in this research. Section V compares and analyzes the simulation results. Section VI contains the conclusion. (author)

  13. Competitive electric power markets and grid reliability : something has changed during the past decade

    International Nuclear Information System (INIS)

    Fluckiger, K.

    2005-01-01

    This white paper reviewed some of the fundamental changes in the way in which electricity is provided to customers. Previously, electricity was delivered by integrated electric utilities that owned both generation and transmission and directly served their customers. Restructuring altered the rules that govern control, operation, ownership and regulation of the industry. The traditional integrated utility has been disaggregated. Wholesale electricity costs are no longer regulated and prices are now set by supply and demand in a market context. Generation investment decisions are based on future expectations of market performance. It was suggested that transmission should become a facilitator of the competitive market. Inter-ties are an essential part of a competitive market, as a means to import power when needed and to export surplus energy. The role of transmission in facilitating new generation by providing non-discriminatory and efficient transport to the market was discussed. It was noted that the lack of transmission investment is resulting in economic penalties, rising losses and constraints on more economic generators. Transmission congestion is counterproductive to the interests of customers. A move away from regional planning to a recognition of the wider interconnectedness of the system was recommended. The current practice of deferring necessary maintenance as a way to generate short-term profit was examined. It was noted that despite the need for new transmission infrastructure, investment in merchant alternating current projects has been slow to materialize. Other challenges to transmission included the uncertainty of regulatory processes and investment recovery as well as the unpredictability of flow patterns in the bulk power system. It was concluded that competitive generation markets will not work with an inadequate transmission infrastructure. Transmission enables new generation by ensuring non-discriminatory and efficient transport to market

  14. Improving ATLAS grid site reliability with functional tests using HammerCloud

    CERN Document Server

    Legger, F; The ATLAS collaboration

    2012-01-01

    With the exponential growth of LHC (Large Hadron Collider) data in 2011, and more coming in 2012, distributed computing has become the established way to analyse collider data. The ATLAS grid infrastructure includes almost 100 sites worldwide, ranging from large national computing centers to smaller university clusters. These facilities are used for data reconstruction and simulation, which are centrally managed by the ATLAS production system, and for distributed user analysis. To ensure the smooth operation of such a complex system, regular tests of all sites are necessary to validate the site capability of successfully executing user and production jobs. We report on the development, optimization and results of an automated functional testing suite using the HammerCloud framework. Functional tests are short light-weight applications covering typical user analysis and production schemes, which are periodically submitted to all ATLAS grid sites. Results from those tests are collected and used to evaluate site...

  15. Improving ATLAS grid site reliability with functional tests using HammerCloud

    CERN Document Server

    Legger, F; The ATLAS collaboration; Medrano Llamas, R; Sciacca, G; Van der Ster, D C

    2012-01-01

    With the exponential growth of LHC (Large Hadron Collider) data in 2011, and more coming in 2012, distributed computing has become the established way to analyse collider data. The ATLAS grid infrastructure includes more than 80 sites worldwide, ranging from large national computing centers to smaller university clusters. These facilities are used for data reconstruction and simulation, which are centrally managed by the ATLAS production system, and for distributed user analysis. To ensure the smooth operation of such a complex system, regular tests of all sites are necessary to validate the site capability of successfully executing user and production jobs. We report on the development, optimization and results of an automated functional testing suite using the HammerCloud framework. Functional tests are short light-weight applications covering typical user analysis and production schemes, which are periodically submitted to all ATLAS grid sites. Results from those tests are collected and used to evaluate si...

  16. Multi-Period Optimization for Voltage Control System in Transmission Grids

    DEFF Research Database (Denmark)

    Qin, Nan; Chen, Si; Liu, Chengxi

    2015-01-01

    Automatic Voltage Control (AVC) systems maintain the voltage in an acceptable range and minimize the power loss of the grid by coordinately regulating the controllable components. Switchable shunts and tap-able transformers are expected to be operated as few times as possible. This paper proposes...

  17. Scenario calculations for the 2012 grid development plan. Overdimensioned HVDC transmission lines; Szenarienrechnungen zum Netzentwicklungsplan (NEP) 2012. HGUe-Leitungen ueberdimensioniert

    Energy Technology Data Exchange (ETDEWEB)

    Oei, Pao-Yu; Sander, Aram; Hankel, Lisa; Laurisch, Lilian; Lorenz, Casimir [Technische Univ. Berlin (Germany); Schroeder, Andreas [Deutsches Institut fuer Wirtschaftsforschung, Berlin (Germany)

    2012-09-15

    The grid development plan presented in June 2012 by the German Federal Network Agency envisages a large number of new AC and DC transmission lines for Germany. The purpose of these transmission lines is to facilitate the point-to-point transport of electricity produced from renewable resources to load centres. The authors present a model-assisted analysis of the impact of these transmission lines on the structure of electricity production. They also investigate to what extent an increase in storage capacity and the steering of demand can serve as alternatives to grid expansion.

  18. Application of reliability based design concepts to transmission line structure foundations. Part 2

    International Nuclear Information System (INIS)

    DiGioia, A.M. Jr.; Rojas-Gonzalez, L.F.

    1991-01-01

    The application of reliability based design (RBD) methods to transmission line structure foundations has developed somewhat more slowly than that for the other structural components in line systems. In a previous paper, a procedure was proposed for the design of transmission line structures foundations using a probability based load and resistance factor design (LRFD) format. This procedure involved the determination of a foundation strength factor, φ F , which was used as a multiplier of the calculated nominal design strength to estimate the five percent exclusion limit strength required in the calculated nominal design strength to estimate the five percent exclusion limit strength required in the LRFD equation. Statistical analyses of results from full-scale load tests were used to obtain φ F values applicable to various nominal design strength equations and for drilled shafts subjected to uplift loads. These results clearly illustrated the significant economic benefits of conducting more detailed subsurface investigations for the design of transmission line structure foundations. A design example was also presented. In this paper the proposed procedure is extended to laterally load drilled shafts

  19. Simultaneous transmission of accurate time, stable frequency, data, and sensor system over one fiber with ITU 100 GHz grid

    Science.gov (United States)

    Horvath, Tomas; Munster, Petr; Vojtech, Josef; Velc, Radek; Oujezsky, Vaclav

    2018-01-01

    Optical fiber is the most used medium for current telecommunication networks. Besides data transmissions, special advanced applications like accurate time or stable frequency transmissions are more common, especially in research and education networks. On the other hand, new applications like distributed sensing are in ISP's interest because e.g. such sensing allows new service: protection of fiber infrastructure. Transmission of all applications in a single fiber can be very cost efficient but it is necessary to evaluate possible interaction before real application and deploying the service, especially if standard 100 GHz grid is considered. We performed laboratory measurement of simultaneous transmission of 100 G data based on DP-QPSK modulation format, accurate time, stable frequency and sensing system based on phase sensitive OTDR through two types of optical fibers, G.655 and G.653. These fibers are less common than G.652 fiber but thanks to their slightly higher nonlinear character, there are suitable for simulation of the worst case which can arise in a real network.

  20. The National Opportunity for Interoperability and its Benefits for a Reliable, Robust, and Future Grid Realized Through Buildings

    Energy Technology Data Exchange (ETDEWEB)

    Office of Energy Efficiency and Renewable Energy

    2016-02-01

    Today, increasing numbers of intermittent generation sources (e.g., wind and photovoltaic) and new mobile intermittent loads (e.g., electric vehicles) can significantly affect traditional utility business practices and operations. At the same time, a growing number of technologies and devices, from appliances to lighting systems, are being deployed at consumer premises that have more sophisticated controls and information that remain underused for anything beyond basic building equipment operations. The intersection of these two drivers is an untapped opportunity and underused resource that, if appropriately configured and realized in open standards, can provide significant energy efficiency and commensurate savings on utility bills, enhanced and lower cost reliability to utilities, and national economic benefits in the creation of new markets, sectors, and businesses being fueled by the seamless coordination of energy and information through device and technology interoperability. Or, as the Quadrennial Energy Review puts it, “A plethora of both consumer-level and grid-level devices are either in the market, under development, or at the conceptual stage. When tied together through the information technology that is increasingly being deployed on electric utilities’ distribution grids, they can be an important enabling part of the emerging grid of the future. However, what is missing is the ability for all of these devices to coordinate and communicate their operations with the grid, and among themselves, in a common language — an open standard.” In this paper, we define interoperability as the ability to exchange actionable information between two or more systems within a home or building, or across and within organizational boundaries. Interoperability relies on the shared meaning of the exchanged information, with agreed-upon expectations and consequences, for the response to the information exchange.

  1. Reliability consideration of low-power-grid-tied inverter for photovoltaic application

    OpenAIRE

    Liu, J.; Henze, N.

    2009-01-01

    In recent years PV modules have been improved evidently. An excellent reliability has been validated corresponding to Mean Time between Failure (MTBF) between 500 and 6000 years respectively in commercial utility power systems. Manufactures can provide performance guarantees for PV modules at least for 20 years. If an average inverter lifetime of 5 years is assumed, it is evident that the overall reliability of PV systems [PVSs] with integrated inverter is determined chiefly by the inverter i...

  2. Impact of Transport Layer Protocols on Reliable Information Access in Smart Grids

    DEFF Research Database (Denmark)

    Shahid, Kamal; Saeed, Aamir; Kristensen, Thomas le Fevre

    2017-01-01

    Time is critical for certain types of dynamic information (e.g. frequency control) in a smart grid scenario. The usefulness of such information depends upon the arrival within a specific frame of time, which in other case may not serve the purpose and effect controller’s performance....... The question is addressed by analyzing the performance of UDP and TCP over imperfect network conditions to show how the selection of transport layer protocol can dramatically affect controller’s performance. This analysis is based on a quality metric called mismatch probability that considers occurrence...

  3. Competitive energy consumption under transmission constraints in a multi-supplier power grid system

    Science.gov (United States)

    Popov, Ivan; Krylatov, Alexander; Zakharov, Victor; Ivanov, Dmitry

    2017-04-01

    Power grid architectures need to be revised in order to manage the increasing number of producers and, more generally, the decentralisation of energy production and distribution. In this work, we describe a multi-supplier multi-consumer congestion model of a power grid, where the costs of consumers depend on the congestion in nodes and arcs of the power supply network. The consumer goal is both to meet their energy demand and to minimise the costs. We show that the methods of non-atomic routing can be applied in this model in order to describe current distribution in the network. We formulate a consumer cost minimisation game for this setting, and discuss the challenges arising in equilibrium search for this game.

  4. The interplay between wind turbines and CPH plants and effects on transmission grid requirements

    DEFF Research Database (Denmark)

    Østergaard, Poul Alberg

    2003-01-01

    The article analyses power flows in the transmission system with scattered load balancing under various climatic conditions with uneven distributions of wind power and uneven temperature and thus CHP conditions in the country.......The article analyses power flows in the transmission system with scattered load balancing under various climatic conditions with uneven distributions of wind power and uneven temperature and thus CHP conditions in the country....

  5. Network Coding Protocols for Smart Grid Communications

    DEFF Research Database (Denmark)

    Prior, Rui; Roetter, Daniel Enrique Lucani; Phulpin, Yannick

    2014-01-01

    We propose a robust network coding protocol for enhancing the reliability and speed of data gathering in smart grids. At the heart of our protocol lies the idea of tunable sparse network coding, which adopts the transmission of sparsely coded packets at the beginning of the transmission process b...

  6. Improving ATLAS grid site reliability with functional tests using HammerCloud

    Science.gov (United States)

    Elmsheuser, Johannes; Legger, Federica; Medrano Llamas, Ramon; Sciacca, Gianfranco; van der Ster, Dan

    2012-12-01

    With the exponential growth of LHC (Large Hadron Collider) data in 2011, and more coming in 2012, distributed computing has become the established way to analyse collider data. The ATLAS grid infrastructure includes almost 100 sites worldwide, ranging from large national computing centers to smaller university clusters. These facilities are used for data reconstruction and simulation, which are centrally managed by the ATLAS production system, and for distributed user analysis. To ensure the smooth operation of such a complex system, regular tests of all sites are necessary to validate the site capability of successfully executing user and production jobs. We report on the development, optimization and results of an automated functional testing suite using the HammerCloud framework. Functional tests are short lightweight applications covering typical user analysis and production schemes, which are periodically submitted to all ATLAS grid sites. Results from those tests are collected and used to evaluate site performances. Sites that fail or are unable to run the tests are automatically excluded from the PanDA brokerage system, therefore avoiding user or production jobs to be sent to problematic sites.

  7. BECCS Market Launch Strategy Aiming to Help Ensure Reliable Grid Power at High Penetrations of IRE (Intermittent Renewable Electricity)

    Science.gov (United States)

    WIlliams, R. H.

    2017-12-01

    Despite its recognized importance for carbon (C)-mitigation, progress in advancing biomass energy with CO2 capture and sequestration (BECCS) has been slow. A BECCS market launch strategy based on technologies ready for commercial-scale demonstration is discussed—based on co-gasification of coal and biomass to make H2 with CCS. H2 so produced would be a key element of a H2 balancing capacity (H2-BC) strategy for ensuring reliable grid power at high IRE penetrations. High grid penetrations of IRE must be complemented by fast-ramping balancing (backup and/or storage) capacity (BC) to ensure reliable grid power. BC provided now by natural gas-fired gas turbine combined cycle and combustion turbine units would eventually have to be decarbonized to realize C-mitigation goals, via CCS or other means. Capital-intensive CCS energy systems require baseload operation to realize favourable economics, but at high IRE penetrations, BC plants must be operated at low capacity factors. A H2-BC strategy is a promising way to address this challenge. The elements of a H2-BC system are: (a) H2 production from carbonaceous feedstocks in baseload plants with CCS; (b) H2 consumption in fast-ramping BC units that operate at low capacity factors; (c) Buffer underground H2 storage to enable decoupling baseload H2 production from highly variable H2 consumption by BC units. The concept is likely to "work" because underground H2 storage is expected to be inexpensive. A H2 production analysis is presented for a negative GHG-emitting H2-BC system based on cogasification of corn stover and coal, with captured CO2 used for enhanced oil recovery. The technical readiness of each system component is discussed, and preliminary insights are offered as to the conditions under which the corresponding H2-BC system might compete with natural gas in providing backup for IRE on US electric grids. Public policy to help advance this strategy might be forthcoming, because 2 US Senate bills with broad

  8. Impacts of offshore grid developments in the North Sea region on market values by 2050: How will offshore wind farms and transmission lines pay?

    DEFF Research Database (Denmark)

    Traber, Thure; Koduvere, Hardi; Koivisto, Matti Juhani

    2017-01-01

    on the substantial differences in the expected economic exposure of wind power plants and transmission lines to the development of the electricity grid in the North Sea. Since details of the prospective energy system around the North Sea region shape these revenue expectations, we further develop and apply...... market values of wind farms on hub level due to impacts of different options for grid structures. The results aim to inform the discussion on possibilities for the allocation of grid expansion costs to the different connected countries including Belgium, Denmark, Germany, the Netherlands, Norway......Increasing the integration of renewable energy in Northern and Central Europe markets is greatly influenced by the development of electricity transmission grid infrastructure. On the background of the fast development of offshore wind energy and its connection to the onshore electricity systems...

  9. Method of Quantifying Size of Retinal Hemorrhages in Eyes with Branch Retinal Vein Occlusion Using 14-Square Grid: Interrater and Intrarater Reliability

    Directory of Open Access Journals (Sweden)

    Yuko Takashima

    2016-01-01

    Full Text Available Purpose. To describe a method of quantifying the size of the retinal hemorrhages in branch retinal vein occlusion (BRVO and to determine the interrater and intrarater reliabilities of these measurements. Methods. Thirty-five fundus photographs from 35 consecutive eyes with BRVO were studied. The fundus images were analyzed with Power-Point® software, and a grid of 14 squares was laid over the fundus image. Raters were asked to judge the percentage of each of the 14 squares that was covered by the hemorrhages, and the average of the 14 squares was taken to be the relative size of the retinal hemorrhage. Results. Interrater reliability between three raters was higher when a grid with 14 squares was used (intraclass correlation coefficient (ICC, 0.96 than that when a box with no grid was used (ICC, 0.78. Intrarater reliability, which was calculated by the retinal hemorrhage area measured on two different days, was also higher (ICC, 0.97 than that with no grid (ICC, 0.86. Interrater reliability for five fundus pictures with poor image quality was also good when a grid with 14 squares was used (ICC, 0.88. Conclusions. Although our method is subjective, excellent interrater and intrarater reliabilities indicate that this method can be adapted for clinical use.

  10. Operation reliability analysis of independent power plants of gas-transmission system distant production facilities

    Science.gov (United States)

    Piskunov, Maksim V.; Voytkov, Ivan S.; Vysokomornaya, Olga V.; Vysokomorny, Vladimir S.

    2015-01-01

    The new approach was developed to analyze the failure causes in operation of linear facilities independent power supply sources (mini-CHP-plants) of gas-transmission system in Eastern part of Russia. Triggering conditions of ceiling operation substance temperature at condenser output were determined with mathematical simulation use of unsteady heat and mass transfer processes in condenser of mini-CHP-plants. Under these conditions the failure probability in operation of independent power supply sources is increased. Influence of environmental factors (in particular, ambient temperature) as well as output electric capability values of power plant on mini-CHP-plant operation reliability was analyzed. Values of mean time to failure and power plant failure density during operation in different regions of Eastern Siberia and Far East of Russia were received with use of numerical simulation results of heat and mass transfer processes at operation substance condensation.

  11. Economic evaluation of reliability-centred maintenance (RCM): an electricity transmission industry perspective

    International Nuclear Information System (INIS)

    Bowler, D.J.; Primrose, P.L.; Leonard, R.

    1995-01-01

    Traditional approaches to appraising the introduction of reliability centred maintenance (RCM) are shown to exhibit severe limitations. In particular, the economic implications surrounding its adoption are repeatedly mis-stated, with the consequence that organisations may be investing in unprofitable RCM ventures. Previously quoted benefits are examined and, contrary to established opinion, it is shown that these 'generalised' statements, once redeemed, are able to be quantified. The paper then proceeds to describe a financial methodology, developed by NGC and UMIST, by which the introduction of RCM can be evaluated. Moreover, it shows that, by regarding RCM as an investment decision, rather than an 'act of faith', the economic viability of a potential application can be determined before vital resources are committed. Finally, it is demonstrated that when the methodology is applied within the context of the electricity transmission industry, the economic case underlying the adoption of RCM can be realistically appraised. (author)

  12. GOC-TX: A Reliable Ticket Synchronization Application for the Open Science Grid

    Science.gov (United States)

    Hayashi, Soichi; Gopu, Arvind; Quick, Robert

    2011-12-01

    One of the major operational issues faced by large multi-institutional collaborations is permitting its users and support staff to use their native ticket tracking environment while also exchanging these tickets with collaborators. After several failed attempts at email-parser based ticket exchanges, the OSG Operations Group has designed a comprehensive ticket synchronizing application. The GOC-TX application uses web-service interfaces offered by various commercial, open source and other homegrown ticketing systems, to synchronize tickets between two or more of these systems. GOC-TX operates independently from any ticketing system. It can be triggered by one ticketing system via email, active messaging, or a web-services call to check for current sync-status, pull applicable recent updates since prior synchronizations to the source ticket, and apply the updates to a destination ticket. The currently deployed production version of GOC-TX is able to synchronize tickets between the Numara Footprints ticketing system used by the OSG and the following systems: European Grid Initiative's system Global Grid User Support (GGUS) and the Request Tracker (RT) system used by Brookhaven. Additional interfaces to the BMC Remedy system used by Fermilab, and to other instances of RT used by other OSG partners, are expected to be completed in summer 2010. A fully configurable open source version is expected to be made available by early autumn 2010. This paper will cover the structure of the GOC-TX application, its evolution, and the problems encountered by OSG Operations group with ticket exchange within the OSG Collaboration.

  13. GOC-TX: A Reliable Ticket Synchronization Application for the Open Science Grid

    International Nuclear Information System (INIS)

    Hayashi, Soichi; Gopu, Arvind; Quick, Robert

    2011-01-01

    One of the major operational issues faced by large multi-institutional collaborations is permitting its users and support staff to use their native ticket tracking environment while also exchanging these tickets with collaborators. After several failed attempts at email-parser based ticket exchanges, the OSG Operations Group has designed a comprehensive ticket synchronizing application. The GOC-TX application uses web-service interfaces offered by various commercial, open source and other homegrown ticketing systems, to synchronize tickets between two or more of these systems. GOC-TX operates independently from any ticketing system. It can be triggered by one ticketing system via email, active messaging, or a web-services call to check for current sync-status, pull applicable recent updates since prior synchronizations to the source ticket, and apply the updates to a destination ticket. The currently deployed production version of GOC-TX is able to synchronize tickets between the Numara Footprints ticketing system used by the OSG and the following systems: European Grid Initiative's system Global Grid User Support (GGUS) and the Request Tracker (RT) system used by Brookhaven. Additional interfaces to the BMC Remedy system used by Fermilab, and to other instances of RT used by other OSG partners, are expected to be completed in summer 2010. A fully configurable open source version is expected to be made available by early autumn 2010. This paper will cover the structure of the GOC-TX application, its evolution, and the problems encountered by OSG Operations group with ticket exchange within the OSG Collaboration.

  14. Improving the Transmission System Reliability for the 154kV Radial Network Operation

    Energy Technology Data Exchange (ETDEWEB)

    Choo, Jin Boo; Yoo, Myeong Ho; Yoon, Young Beum; Kim, Tae Won [Korea Electric Power Research Institute, Taejon (Korea, Republic of); Lee, Gi Won; Chung, Beom Jin; Jung, Jung Won; Park, Kyu Hyun; Lee, Myung Hee; Kim, Hyun Jong; Kim, Chae Hee [KEYIN CO., (Korea, Republic of)

    1996-12-31

    Analyzing that 154kV radial network current ed operated, we developed Automatic Power Reconfiguration System(APRS) which restore blackout area. It consists of special data acquisition system(DAU) and central monitoring system for reason of protecting currently operating power system. In addition, it communicates using optical communication network for high speed data transmission and accuracy. An Accuracy of operation and stability of the developed system is tested using Real Time Digital Simulator in 3-bus equivalent model system. In An Outage case, our developed system can restore a blackout area in three second. An ability of the restoration of a blackout was verified by simulations. For the field test, the developed system was set up at SINCHON S/S, SESOMUN S/S, SINDANG S/S and MAJANG S/S governed by Seoul Power Transmission Center. If the system reliability is proved for a one year test in real power system, application of the system will be extended to the other substations.

  15. Coordinated parallel and series flexible AC transmission systems (FACTS) to support a power grid with a large amount of wind power

    Energy Technology Data Exchange (ETDEWEB)

    Mora-Cantallops, Marcal; Gomis-Bellmunt, Oriol; Sumper, Andreas; Rull-Duran, Joan [Univ. Politecnica de Catalunya, Barcelona (ES). Centre d' Innovacio Tecnologica en Convertidors Estatics i Accionaments (CITCEA-UPC)

    2009-07-01

    Wind power constitutes one of the more viable alternatives to conventional power generation technology. In the previous years, wind power penetration on electric grids has grown notably, and has brought several new issues related to its integration into power grids. Flexible AC Transmission Systems (FACTS) installed in the right place and controlled conveniently are able to mitigate and solve many of these issues. In the present work, a STATCOM and a SSSC are used coordinately to fully support an electric grid. Simulations include normal and fault operation. (orig.)

  16. Analysis of step-up transformer tap change on the quantities at the point of connection to transmission grid

    Directory of Open Access Journals (Sweden)

    Đorđević Dragan

    2017-01-01

    Full Text Available The analysis of a step-up transformer tap change on the quantities at the point of connection to the transmission grid is presented in this paper. The point of connection of generator TENT A6 has been analyzed, and a detailed model of this generator is available in software package DIgSILENT Power Factory. The comparison between the effect of a step-up transformer tap change on the quantities at the point of connection during automatic and manual operation of voltage regulator has been conducted. In order to conduct the analysis of the manual operation of the voltage regulator, the comparison between the different methods of modeling of these modes has been performed. Several generator operating points, selected in order to represent the need for tap change, have been analyzed. Also, previously mentioned analyses have been performed taking into account the voltage-reactive stiffness at the point of connection.

  17. Dynamic Reliability Analysis of Gear Transmission System of Wind Turbine in Consideration of Randomness of Loadings and Parameters

    Directory of Open Access Journals (Sweden)

    Lei Wang

    2014-01-01

    Full Text Available A dynamic model of gear transmission system of wind turbine is built with consideration of randomness of loads and parameters. The dynamic response of the system is obtained using the theory of random sampling and the Runge-Kutta method. According to rain flow counting principle, the dynamic meshing forces are converted into a series of luffing fatigue load spectra. The amplitude and frequency of the equivalent stress are obtained using equivalent method of Geber quadratic curve. Moreover, the dynamic reliability model of components and system is built according to the theory of probability of cumulative fatigue damage. The system reliability with the random variation of parameters is calculated and the influence of random parameters on dynamic reliability of components is analyzed. In the end, the results of the proposed method are compared with that of Monte Carlo method. This paper can be instrumental in the design of wind turbine gear transmission system with more advantageous dynamic reliability.

  18. Investigation on Transmission and Substation Facilities of Sichuan Power Grid in Wenchuan Earthquake

    Institute of Scientific and Technical Information of China (English)

    Yu Yongqing; Li Guangfan; Li Peng; Zhu Quanjun; Yuan Dalu; Wang Chengyu; Li Jinzhong; Huang Huang; Li Lixin; Zhang Xinghai; Liu Jingmin

    2009-01-01

    @@ On May 12,2008,an earthquake of Ms 8.0 hit the area around Wenchuan County,Sichuan Province,China.It has been one of the most destructive earthquakes since the founding of P.R.China in 1949.The quake caused not only tremendous loss of life and wealth,but also severe damage to transmission and substation facilities.After the disaster,an expert group from China Electric Power Research Institute (CEPRI)was sent for on-site investigation.This paper is a summary of the investigation,in which suggestions for electric equipment to resist earthquake disasters are also proponed.

  19. Transmission issues

    International Nuclear Information System (INIS)

    Bradford, J.; Wilson, L.; Thon, S.; Millar, N.

    2005-01-01

    This session on transmission issues focused on the role that transmission plays in electricity markets and the importance of getting the market structure right in terms of generation divestiture with buy back contracts, demand side responsive programs, transmission upgrades and long term contracts. The difficulties of distinguishing between market power and scarcity were examined along with some of the complications that ensue if transmission experiences congestion, as exemplified by the August 2003 blackout in eastern North America. The presentations described the best ways to handle transmission issues, and debated whether transmission should be deregulated or follow market forces. Issues of interconnections and reliability of connections were also debated along with the attempt to integrate renewables into the grid. Some presentations identified what new transmission must be built and what must be done to ensure that transmission gets built. The challenges and business opportunities for transmission in Alberta were discussed with reference to plans to invest in new infrastructure, where it is going outside of the province and how it works with other jurisdictions. Manitoba's Conawapa Hydro Project and its 2000 MW tie line to Ontario was also discussed. Some examples of non-optimal use of interconnections in Europe were also discussed in an effort to learn from these mistakes and avoid them in Canada. tabs., figs

  20. Evaluation of a proposal for reliable low-cost grid power with 100% wind, water, and solar.

    Science.gov (United States)

    Clack, Christopher T M; Qvist, Staffan A; Apt, Jay; Bazilian, Morgan; Brandt, Adam R; Caldeira, Ken; Davis, Steven J; Diakov, Victor; Handschy, Mark A; Hines, Paul D H; Jaramillo, Paulina; Kammen, Daniel M; Long, Jane C S; Morgan, M Granger; Reed, Adam; Sivaram, Varun; Sweeney, James; Tynan, George R; Victor, David G; Weyant, John P; Whitacre, Jay F

    2017-06-27

    A number of analyses, meta-analyses, and assessments, including those performed by the Intergovernmental Panel on Climate Change, the National Oceanic and Atmospheric Administration, the National Renewable Energy Laboratory, and the International Energy Agency, have concluded that deployment of a diverse portfolio of clean energy technologies makes a transition to a low-carbon-emission energy system both more feasible and less costly than other pathways. In contrast, Jacobson et al. [Jacobson MZ, Delucchi MA, Cameron MA, Frew BA (2015) Proc Natl Acad Sci USA 112(49):15060-15065] argue that it is feasible to provide "low-cost solutions to the grid reliability problem with 100% penetration of WWS [wind, water and solar power] across all energy sectors in the continental United States between 2050 and 2055", with only electricity and hydrogen as energy carriers. In this paper, we evaluate that study and find significant shortcomings in the analysis. In particular, we point out that this work used invalid modeling tools, contained modeling errors, and made implausible and inadequately supported assumptions. Policy makers should treat with caution any visions of a rapid, reliable, and low-cost transition to entire energy systems that relies almost exclusively on wind, solar, and hydroelectric power.

  1. A Smart Grid Framework for Optimally Integrating Supply-Side, Demand-Side and Transmission Line Management Systems

    Directory of Open Access Journals (Sweden)

    Chukwuka Monyei

    2018-04-01

    Full Text Available A coordinated centralized energy management system (ConCEMS is presented in this paper that seeks to integrate for optimal grid operation—the supply side energy management system (SSEMS, home energy management system (HEMS and transmission line management system (TLMS. ConCEMS in ensuring the optimal operation of an IEEE 30-bus electricity network harmonizes the individual objective function of SSEMS, HEMS and TLMS to evolve an optimal dispatch of participating demand response (DR loads that does not violate transmission line ampacity limits (TLMS constraint while minimizing consumer cost (HEMS constraint and supply side operations cost (SSEMS constraint. An externally constrained genetic algorithm (ExC-GA that is influenced by feedback from TLMS is also presented that intelligently varies the dispatch time of participating DR loads to meet the individual objective functions. Hypothetical day ahead dynamic pricing schemes (Price1, Price2 and Price3 have also been adopted alongside an existing time of use (Price0 pricing scheme for comparison and discussion while a dynamic thermal line rating (DTLR algorithm has also been incorporated to dynamically compute power limits based on real time associated data.

  2. Transmission pricing in privately-owned electricity grids: An illustration from the Argentine electricity pool

    International Nuclear Information System (INIS)

    Abdala, Manuel A.

    2008-01-01

    The Argentine electricity reform of 1992 offers an interesting example of decentralized transmission pricing arrangements within a competitive system. This paper is a shortened version of an original analysis made in 1994 of the regulation of the Argentine transmission system, with emphasis on investment cost allocation rules. To make up for the limitation of short-run marginal cost (SRMC) pricing, incentives on service quality were put in place, including penalties for lack of line availability. The mechanism for capacity expansion, based on ad-hoc rules for allocations of investment costs, had the potential to produce non-optimal investment outcomes, as such rules ignored beneficiaries on the demand side. For fine tuning of this system, I proposed an alternative rule based on traditional welfare analysis that broadens the universe of identified beneficiaries, and thus can be expected to produce a fairer outcome on investment cost allocation, reducing the potential risks of non-optimal investment. A brief postscript comments on the paper from the perspective of 2007. (author)

  3. Reliability of hybrid photovoltaic DC micro-grid systems for emergency shelters and other applications

    Science.gov (United States)

    Dhere, Neelkanth G.; Schleith, Susan

    2014-10-01

    Improvement of energy efficiency in the SunSmart Schools Emergency Shelters requires new methods for optimizing the energy consumption within the shelters. One major limitation in current systems is the requirement of converting direct current (DC) power generated from the PV array into alternating current (AC) power which is distributed throughout the shelters. Oftentimes, this AC power is then converted back to DC to run certain appliances throughout the shelters resulting in a significant waste of energy due to DC to AC and then again AC to DC conversion. This paper seeks to extract the maximum value out of PV systems by directly powering essential load components within the shelters that already run on DC power without the use of an inverter and above all to make the system reliable and durable. Furthermore, additional DC applications such as LED lighting, televisions, computers and fans operated with DC brushless motors will be installed as replacements to traditional devices in order to improve efficiency and reduce energy consumption. Cost of energy storage technologies continue to decline as new technologies scale up and new incentives are put in place. This will provide a cost effective way to stabilize the energy generation of a PV system as well as to provide continuous energy during night hours. It is planned to develop a pilot program of an integrated system that can provide uninterrupted DC power to essential base load appliances (heating, cooling, lighting, etc.) at the Florida Solar Energy Center (FSEC) command center for disaster management. PV arrays are proposed to be installed on energy efficient test houses at FSEC as well as at private homes having PV arrays where the owners volunteer to participate in the program. It is also planned to monitor the performance of the PV arrays and functioning of the appliances with the aim to improve their reliability and durability. After a successful demonstration of the hybrid DC microgrid based emergency

  4. Analysis on the Operation Strategy of the 220kV External Transmission Channel for the Nujiang Power Grid after the Installation of Series Compensation

    Science.gov (United States)

    Liu, Xiaoxin; Feng, Peilei; Jan, Lisheng; Dai, Xiaozhong; Cai, Pengcheng

    2018-01-01

    In recent years, Nujiang Prefecture vigorously develop hydropower, the grid structure in the northwest of Yunnan Province is not perfect, which leads to the research and construction of the power grid lags behind the development of the hydropower. In 2015, the company in view of the nu river hydropower dilemma decided to change outside the nu river to send out a passage with series compensation device in order to improve the transmission capacity, the company to the main problems related to the system plan, but not too much in the region distribution network and detailed study. Nujiang power grid has unique structure and properties of the nujiang power grid after respectively, a whole rack respectively into two parts, namely power delivery channels, load power supply, the whole grid occurred fundamental changes, the original strategy of power network is not applicable, especially noteworthy is the main failure after network of independent operation problem, how to avoid the local series, emergency problem is more urgent, very tolerance test area power grid, this paper aims at the analysis of existing data, simulation, provide a reference for respectively after the operation for the stable operation of the power grid.

  5. Protection devices in the transmission grids, German practice. Typical protection concepts in Germany's power transmission lines; Schutzsysteme im Uebertragungsnetz, deutsche Praxis. Typische Schutzkonzepte im deutschen Uebertragungsnetz

    Energy Technology Data Exchange (ETDEWEB)

    Herrmann, Hans-Joachim [Siemens AG, Nuernberg (Germany). Sektor Energy, Energy Automation; Ludwig, Andrea [50 Hertz Transmission GmbH, Berlin (Germany). Schutztechnik, Anlagenmanagement; Kuehn, Holger [Tennet TSO GmbH, Bayreuth (Germany). Schutztechnik, Assetmanagement/Umspannwerke; Oechsle, Fred [EnBW Regional AG, Stuttgart (Germany). Netzschutz, Netzservice - Projekte Strom

    2011-04-18

    The contribution presents typical protection concepts for power grids. Solutions for power plant feed-in, bus bar, transmission lines and coupling transformer are explained. General information is provided on triggering concepts, on the design of d.c. power supply, selection of current inverters, and other subjects.

  6. Reliability

    OpenAIRE

    Condon, David; Revelle, William

    2017-01-01

    Separating the signal in a test from the irrelevant noise is a challenge for all measurement. Low test reliability limits test validity, attenuates important relationships, and can lead to regression artifacts. Multiple approaches to the assessment and improvement of reliability are discussed. The advantages and disadvantages of several different approaches to reliability are considered. Practical advice on how to assess reliability using open source software is provided.

  7. Optimal Wind Energy Integration in Large-Scale Electric Grids

    Science.gov (United States)

    Albaijat, Mohammad H.

    The major concern in electric grid operation is operating under the most economical and reliable fashion to ensure affordability and continuity of electricity supply. This dissertation investigates the effects of such challenges, which affect electric grid reliability and economic operations. These challenges are: 1. Congestion of transmission lines, 2. Transmission lines expansion, 3. Large-scale wind energy integration, and 4. Phaser Measurement Units (PMUs) optimal placement for highest electric grid observability. Performing congestion analysis aids in evaluating the required increase of transmission line capacity in electric grids. However, it is necessary to evaluate expansion of transmission line capacity on methods to ensure optimal electric grid operation. Therefore, the expansion of transmission line capacity must enable grid operators to provide low-cost electricity while maintaining reliable operation of the electric grid. Because congestion affects the reliability of delivering power and increases its cost, the congestion analysis in electric grid networks is an important subject. Consequently, next-generation electric grids require novel methodologies for studying and managing congestion in electric grids. We suggest a novel method of long-term congestion management in large-scale electric grids. Owing to the complication and size of transmission line systems and the competitive nature of current grid operation, it is important for electric grid operators to determine how many transmission lines capacity to add. Traditional questions requiring answers are "Where" to add, "How much of transmission line capacity" to add, and "Which voltage level". Because of electric grid deregulation, transmission lines expansion is more complicated as it is now open to investors, whose main interest is to generate revenue, to build new transmission lines. Adding a new transmission capacity will help the system to relieve the transmission system congestion, create

  8. Practical Coupled Resonators in Domino Arrangements for Power Transmission and Distribution: Replacing Step-Down Power Transformers and Their Branches across the Power Grid

    Directory of Open Access Journals (Sweden)

    Athanasios G. Lazaropoulos

    2013-01-01

    /low-voltage (MV/LV, and HV/LV power transformers used across the world is investigated verifying their replacement potential with practical DCR configurations in all the cases examined. Fifth, based on a detailed collection of dimensions concerning power transformers and transmission line branches, it is first verified that practical DCR configurations cannot only substitute all step-down power transformers of the today's power grid but also replace entire transmission line branches too. Finally, it is obvious that there is a long journey ahead for WPT technology and its ultramodern DCR configurations to be affordably, widely, reliably, sustainably, and safely adopted in the human society. During these first steps of WPT development for power transmission and distribution, theoretical analyses and visions are necessary. The last cable problem, that is, the seamless power delivery as easily as information is now transmitted through the air, is one of the major technological challenges of the 21st century, and, thus, WPT technology will certainly play key role.

  9. Wireless communications networks for the smart grid

    CERN Document Server

    Ho, Quang-Dung; Rajalingham, Gowdemy; Le-Ngoc, Tho

    2014-01-01

    This brief presents a comprehensive review of the network architecture and communication technologies of the smart grid communication network (SGCN). It then studies the strengths, weaknesses and applications of two promising wireless mesh routing protocols that could be used to implement the SGCN. Packet transmission reliability, latency and robustness of these two protocols are evaluated and compared by simulations in various practical SGCN scenarios. Finally, technical challenges and open research opportunities of the SGCN are addressed. Wireless Communications Networks for Smart Grid provi

  10. 78 FR 73112 - Monitoring System Conditions-Transmission Operations Reliability Standards; Interconnection...

    Science.gov (United States)

    2013-12-05

    ...\\ \\8\\ Mandatory Reliability Standards for the Bulk-Power System, Order No. 693, 72 FR 16416 (Apr. 4... operators and reliability coordinators to ``plan and operate the interconnected Bulk Electric System in a... mandated in the currently- effective standards, thereby improving reliability of the bulk power system...

  11. Integrated Transmission and Distribution Control

    Energy Technology Data Exchange (ETDEWEB)

    Kalsi, Karanjit [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Fuller, Jason C. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Tuffner, Francis K. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Lian, Jianming [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Zhang, Wei [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Marinovici, Laurentiu D. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Fisher, Andrew R. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Chassin, Forrest S. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Hauer, Matthew L. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States)

    2013-01-01

    Distributed, generation, demand response, distributed storage, smart appliances, electric vehicles and renewable energy resources are expected to play a key part in the transformation of the American power system. Control, coordination and compensation of these smart grid assets are inherently interlinked. Advanced control strategies to warrant large-scale penetration of distributed smart grid assets do not currently exist. While many of the smart grid technologies proposed involve assets being deployed at the distribution level, most of the significant benefits accrue at the transmission level. The development of advanced smart grid simulation tools, such as GridLAB-D, has led to a dramatic improvement in the models of smart grid assets available for design and evaluation of smart grid technology. However, one of the main challenges to quantifying the benefits of smart grid assets at the transmission level is the lack of tools and framework for integrating transmission and distribution technologies into a single simulation environment. Furthermore, given the size and complexity of the distribution system, it is crucial to be able to represent the behavior of distributed smart grid assets using reduced-order controllable models and to analyze their impacts on the bulk power system in terms of stability and reliability.

  12. Ensuring the Reliable Operation of the Power Grid: State-Based and Distributed Approaches to Scheduling Energy and Contingency Reserves

    Science.gov (United States)

    Prada, Jose Fernando

    Keeping a contingency reserve in power systems is necessary to preserve the security of real-time operations. This work studies two different approaches to the optimal allocation of energy and reserves in the day-ahead generation scheduling process. Part I presents a stochastic security-constrained unit commitment model to co-optimize energy and the locational reserves required to respond to a set of uncertain generation contingencies, using a novel state-based formulation. The model is applied in an offer-based electricity market to allocate contingency reserves throughout the power grid, in order to comply with the N-1 security criterion under transmission congestion. The objective is to minimize expected dispatch and reserve costs, together with post contingency corrective redispatch costs, modeling the probability of generation failure and associated post contingency states. The characteristics of the scheduling problem are exploited to formulate a computationally efficient method, consistent with established operational practices. We simulated the distribution of locational contingency reserves on the IEEE RTS96 system and compared the results with the conventional deterministic method. We found that assigning locational spinning reserves can guarantee an N-1 secure dispatch accounting for transmission congestion at a reasonable extra cost. The simulations also showed little value of allocating downward reserves but sizable operating savings from co-optimizing locational nonspinning reserves. Overall, the results indicate the computational tractability of the proposed method. Part II presents a distributed generation scheduling model to optimally allocate energy and spinning reserves among competing generators in a day-ahead market. The model is based on the coordination between individual generators and a market entity. The proposed method uses forecasting, augmented pricing and locational signals to induce efficient commitment of generators based on firm

  13. Analyzing the topological, electrical and reliability characteristics of a power transmission system for identifying its critical elements

    International Nuclear Information System (INIS)

    Zio, E.; Golea, L.R.

    2012-01-01

    The subject of this paper is the analysis of an electrical transmission system with the objective of identifying its most critical elements with respect to failures and attacks. The methodological approach undertaken is based on graph-theoretical (topological) network analysis. Four different perspectives of analysis are considered within the formalism of weighed networks, adding to the purely topological analysis of the system, the reliability and electrical characteristics of its components. In each phase of the analysis: i) a graph-theoretical representation is offered to highlight the structure of the most important system connections according to the particular characteristics examined (topological, reliability, electrical or electrical-reliability), ii) the classical degree index of a network node is extended to account for the different characteristics considered. The application of these concepts of analysis to an electrical transmission system of literature confirms the importance of different perspectives of analysis on such a critical infrastructure. - Highlights: ► We analyze a power system from topological, reliability and electrical perspectives. ► We rank critical components within a vulnerability assessment framework. ► We compute an extended degree to rank critical energy paths. ► We compare several analytical approaches and provide a table for choosing among them. ► We suggest network changes to increase the reliability of highly loaded energy paths.

  14. Towards an optimal transmission system

    International Nuclear Information System (INIS)

    Calviou, M.

    2005-01-01

    This presentation provided background on National Grid USA and discussed transmission investment in the United States (US) and United Kingdom. It also discussed barriers to transmission investments and improvements, thoughts on solutions and a long-term vision. The presentation identified that transmission investment should follow from clear reliability rules designed to promote better operation and management; investment does not necessarily mean new rights-of-way; and transmission investment should target benefits to customers. It was stated that US transmission investment levels have decreased. A comparison between US and UK transmission investment was presented along with a chart of increasing US congestion costs. Barriers to investment in US transmission include vertical integration; misperception of transmission as a market product; federal and state jurisdiction issues; fragmentation in transmission ownership and operation; rate cap based plans that impact transmission; lack of clarity in cost allocation; and the site selection process. Possible solutions include policy and incentives, promoting independence and resolving structural issues. tabs., figs

  15. 75 FR 81157 - Version One Regional Reliability Standard for Transmission Operations

    Science.gov (United States)

    2010-12-27

    ... not exceed the path's system operating limits, when the transmission operator implements its real-time... return the actual power flow to within [system operating limits] such that at no time shall the power... return the transmission system to within [system operating limits] within a time certain, only a...

  16. Fault ride-through and grid support of permanent magnet synchronous generator-based wind farms with HVAC and VSC-HVDC transmission systems

    DEFF Research Database (Denmark)

    Liu, Hongzhi; Chen, Zhe

    2012-01-01

    This paper describes fault ride-through and grid support of offshore wind farms based on permanent magnet synchronous generator (PMSG) wind turbines connected to the onshore AC network through two alternative transmission systems: high voltage AC (HVAC) or high voltage DC (HVDC) based on voltage...... source converters (VSC). The proposed configurations of the PMSG-based offshore wind farm and VSC-based HVDC are given as well as their control strategies under both steady state and fault state. The PMSG-based offshore wind farm is integrated into a test power transmission system via either HVAC or VSC...

  17. Strategies and Decision Support Systems for Integrating Variable Energy Resources in Control Centers for Reliable Grid Operations

    Energy Technology Data Exchange (ETDEWEB)

    Jones, Lawrence E. [Alstom Grid Inc., Washington, DC (United States)

    2011-11-01

    This report provides findings from the field regarding the best ways in which to guide operational strategies, business processes and control room tools to support the integration of renewable energy into electrical grids.

  18. Strategies and Decision Support Systems for Integrating Variable Energy Resources in Control Centers for Reliable Grid Operations. Executive Summary

    Energy Technology Data Exchange (ETDEWEB)

    Jones, Lawrence E. [Alstom Grid, Inc., Washington, DC (United States)

    2011-11-01

    This is the executive summary for a report that provides findings from the field regarding the best ways in which to guide operational strategies, business processes and control room tools to support the integration of renewable energy into electrical grids.

  19. Power Line Communications for Smart Grid Applications

    Directory of Open Access Journals (Sweden)

    Lars Torsten Berger

    2013-01-01

    Full Text Available Power line communication, that is, using the electricity infrastructure for data transmission, is experiencing a renaissance in the context of Smart Grid. Smart Grid objectives include the integration of intermittent renewable energy sources into the electricity supply chain, securing reliable electricity delivery, and using the existing electrical infrastructure more efficiently. This paper surveys power line communications (PLCs in the context of Smart Grid. The specifications G3-PLC, PRIME, HomePlug Green PHY, and HomePlug AV2, and the standards IEEE 1901/1901.2 and ITU-T G.hn/G.hnem are discussed.

  20. 77 FR 25164 - Revision to Transmission Vegetation Management Reliability Standard; Notice Inviting Comments on...

    Science.gov (United States)

    2012-04-27

    ... mathematics and documentation of the technical justification behind the application of the Gallet equation and... application in NERC- approved Reliability Standard FAC-003-2 reasonable to address the minimum distance...

  1. Smart grids - French Expertise

    International Nuclear Information System (INIS)

    2015-11-01

    The adaptation of electrical systems is the focus of major work worldwide. Bringing electricity to new territories, modernizing existing electricity grids, implementing energy efficiency policies and deploying renewable energies, developing new uses for electricity, introducing electric vehicles - these are the challenges facing a multitude of regions and countries. Smart Grids are the result of the convergence of electrical systems technologies with information and communications technologies. They play a key role in addressing the above challenges. Smart Grid development is a major priority for both public and private-sector actors in France. The experience of French companies has grown with the current French electricity system, a system that already shows extensive levels of 'intelligence', efficiency and competitiveness. French expertise also leverages substantial competence in terms of 'systems engineering', and can provide a tailored response to meet all sorts of needs. French products and services span all the technical and commercial building blocks that make up the Smart Grid value chain. They address the following issues: Improving the use and valuation of renewable energies and decentralized means of production, by optimizing the balance between generation and consumption. Strengthening the intelligence of the transmission and distribution grids: developing 'Supergrid', digitizing substations in transmission networks, and automating the distribution grids are the focus of a great many projects designed to reinforce the 'self-healing' capacity of the grid. Improving the valuation of decentralized flexibilities: this involves, among others, deploying smart meters, reinforcing active energy efficiency measures, and boosting consumers' contribution to grid balancing, via practices such as demand response which implies the aggregation of flexibility among residential, business, and/or industrial sites. Addressing current technological challenges, in

  2. Reliable, Lightweight Transmissions For Off-Shore, Utility Scale Wind Turbines

    Energy Technology Data Exchange (ETDEWEB)

    Jean-Claude Ossyra

    2012-10-25

    The objective of this project was to reduce the technical risk for a hydrostatic transmission based drivetrain for high-power utility-size wind turbines. A theoretical study has been performed to validate the reduction of cost of energy (CoE) for the wind turbine, identify risk mitigation strategies for the drive system and critical components, namely the pump, shaft connection and hydrostatic transmission (HST) controls and address additional benefits such as reduced deployment costs, improved torque density and improved mean time between repairs (MTBR).

  3. Sensitivity analysis of smart grids reliability due to indirect cyber-power interdependencies under various DG technologies, DG penetrations, and operation times

    International Nuclear Information System (INIS)

    Hashemi-Dezaki, Hamed; Agah, Seyed Mohammad Mousavi; Askarian-Abyaneh, Hossein; Haeri-Khiavi, Homayoun

    2016-01-01

    Highlights: • A novel risk assessment method considering the ICPIs is proposed. • The protection and monitoring system as the ICPIs applications are studied. • The uncertainty of results is analyzed in addition to expected average results. • ICPIs impacts due to DG penetrations under various DG technologies are analyzed. • The well-being criteria have been provided in addition to reliability indices. - Abstract: The cyber failures such as failures in protection and monitoring systems will not stop the operation or change the behavior of the power system instantly but will adversely affect the performance of the power system against the potential failure. Such indirect cyber-power interdependencies (ICPIs) may either intensify the probability of future failures or postpone the repercussion to the present failure of the power elements. The much less effort has been devoted in literature to investigate the ICPIs impacts, particularly in stochastic simulating space. In this paper, a novel stochastic-based reliability evaluation method which considers the ICPIs impacts under various uncertain parameters is proposed. The consideration of uncertainty regarding the renewable distributed generation (DG) units, consumption patterns, power and cyber elements, and ICPIs is one of the most important contributions of the proposed method. Further, a novel stochastic-based state upgrading is introduced to concern the ICPIs of protection and monitoring systems. By using the proposed state upgrading methodology, it is possible to evaluate the reliability of smart grid based on ICPIs by using conventional reliability evaluation methods. The proposed risk assessment methodology is applied to an actual distribution grid. The several sensitivity studies are performed to gain insight into how the penetration level of DG units under various DG technology scenarios can affect the ICPIs impacts on the risk level of smart grid. The test results show that regardless of the DG

  4. Transmission Expansion Planning of Transnational Offshore Grids : A Techno-Economic and Legal Approach Case Study of the North Sea Offshore Grid

    NARCIS (Netherlands)

    Shariat Torbaghan, S.

    2016-01-01

    The new energy policy of the European Union (EU) with the core objectives of competitiveness, reliability and sustainability, has driven Europe into a transition towards a low carbon & sustainable electricity supply systems. Under the new policy, the European energy systems are pursing two major

  5. A Survey on Next-generation Power Grid Data Architecture

    Energy Technology Data Exchange (ETDEWEB)

    You, Shutang [University of Tennessee, Knoxville (UTK); Zhu, Dr. Lin [University of Tennessee (UT); Liu, Yong [ORNL; Liu, Yilu [ORNL; Shankar, Mallikarjun (Arjun) [ORNL; Robertson, Russell [Grid Protection Alliance; King Jr, Thomas J [ORNL

    2015-01-01

    The operation and control of power grids will increasingly rely on data. A high-speed, reliable, flexible and secure data architecture is the prerequisite of the next-generation power grid. This paper summarizes the challenges in collecting and utilizing power grid data, and then provides reference data architecture for future power grids. Based on the data architecture deployment, related research on data architecture is reviewed and summarized in several categories including data measurement/actuation, data transmission, data service layer, data utilization, as well as two cross-cutting issues, interoperability and cyber security. Research gaps and future work are also presented.

  6. An Energy-Efficient Link Layer Protocol for Reliable Transmission over Wireless Networks

    Directory of Open Access Journals (Sweden)

    Iqbal Adnan

    2009-01-01

    Full Text Available In multihop wireless networks, hop-by-hop reliability is generally achieved through positive acknowledgments at the MAC layer. However, positive acknowledgments introduce significant energy inefficiencies on battery-constrained devices. This inefficiency becomes particularly significant on high error rate channels. We propose to reduce the energy consumption during retransmissions using a novel protocol that localizes bit-errors at the MAC layer. The proposed protocol, referred to as Selective Retransmission using Virtual Fragmentation (SRVF, requires simple modifications to the positive-ACK-based reliability mechanism but provides substantial improvements in energy efficiency. The main premise of the protocol is to localize bit-errors by performing partial checksums on disjoint parts or virtual fragments of a packet. In case of error, only the corrupted virtual fragments are retransmitted. We develop stochastic models of the Simple Positive-ACK-based reliability, the previously-proposed Packet Length Optimization (PLO protocol, and the SRVF protocol operating over an arbitrary-order Markov wireless channel. Our analytical models show that SRVF provides significant theoretical improvements in energy efficiency over existing protocols. We then use bit-error traces collected over different real networks to empirically compare the proposed and existing protocols. These experimental results further substantiate that SRVF provides considerably better energy efficiency than Simple Positive-ACK and Packet Length Optimization protocols.

  7. Optimal stochastic scheduling of CHP-PEMFC, WT, PV units and hydrogen storage in reconfigurable micro grids considering reliability enhancement

    International Nuclear Information System (INIS)

    Bornapour, Mosayeb; Hooshmand, Rahmat-Allah; Khodabakhshian, Amin; Parastegari, Moein

    2017-01-01

    Highlights: • Stochastic model is proposed for coordinated scheduling of renewable energy sources. • The effect of combined heat and power is considered. • Uncertainties of wind speed, solar radiation and electricity market price are considered. • Profit maximization, emission and AENS minimization are considered as objective functions. • Modified firefly algorithm is employed to solve the problem. - Abstract: Nowadays the operation of renewable energy sources and combined heat and power (CHP) units is increased in micro grids; therefore, to reach optimal performance, optimal scheduling of these units is required. In this regard, in this paper a micro grid consisting of proton exchange membrane fuel cell-combined heat and power (PEMFC-CHP), wind turbines (WT) and photovoltaic (PV) units, is modeled to determine the optimal scheduling state of these units by considering uncertain behavior of renewable energy resources. For this purpose, a scenario-based method is used for modeling the uncertainties of electrical market price, the wind speed, and solar irradiance. It should be noted that the hydrogen storage strategy is also applied in this study for PEMFC-CHP units. Market profit, total emission production, and average energy not supplied (AENS) are the objective functions considered in this paper simultaneously. Consideration of the above-mentioned objective functions converts the proposed problem to a mixed integer nonlinear programming. To solve this problem, a multi-objective firefly algorithm is used. The uncertainties of parameters convert the mixed integer nonlinear programming problem to a stochastic mixed integer nonlinear programming problem. Moreover, optimal coordinated scheduling of renewable energy resources and thermal units in micro-grids improve the value of the objective functions. Simulation results obtained from a modified 33-bus distributed network as a micro grid illustrates the effectiveness of the proposed method.

  8. Development of reliability-based design and assessment standards for onshore gas transmission pipelines

    Energy Technology Data Exchange (ETDEWEB)

    Zhou, Joe; Rothwell, Brian [TransCanada PipeLines Ltd., Calgary, AB (Canada); Nessim, Maher; Zhou, Wenxing [C-FER Technologies, Edmonton, AB (Canada)

    2005-07-01

    Onshore pipelines have traditionally been designed with a deterministic stress based methodology. The changing operating environment has however imposed many challenges to the pipeline industry, including heightened public awareness of risk, more challenging natural hazards and increased economic competitiveness. To meet the societal expectation of pipeline safety and enhance the competitiveness of the pipeline industry, significant efforts have been spent for the development of reliability-based design and assessment (RBDA) methodology. This paper will briefly review the technology development in the RBDA area and the focus will be on the progresses in the past years in standard development within the American Society of Mechanical Engineers (ASME) and the Canadian Standard Association (CSA) organizations. (author)

  9. Consortium for Electric Reliability Technology Solutions Grid of the Future White Paper on Review of Recent Reliability Issues and Systems Events

    Energy Technology Data Exchange (ETDEWEB)

    Hauer, John F.; Dagle, Jeffery E.

    1999-12-01

    This report is one of six reports developed under the U.S. Department of Energy (DOE) program in Power System Integration and Reliability (PSIR). The objective of this report is to review, analyze, and evaluate critical reliability issues demonstrated by recent disturbance events in the North America power system. Eleven major disturbances are examined, most occurring in this decade. The strategic challenge is that the pattern of technical need has persisted for a long period of time. For more than a decade, anticipation of market deregulation has been a major disincentive to new investments in system capacity. It has also inspired reduced maintenance of existing assets. A massive infusion of better technology is emerging as the final option to continue reliable electrical services. If an investment in better technology will not be made in a timely manner, then North America should plan its adjustments to a very different level of electrical service. It is apparent that technical operations staff among the utilities can be very effective at marshaling their forces in the immediate aftermath of a system emergency, and that serious disturbances often lead to improved mechanisms for coordinated operation. It is not at all apparent that such efforts can be sustained through voluntary reliability organizations in which utility personnel external to those organizations do most of the technical work. The eastern interconnection shows several situations in which much of the technical support has migrated from the utilities to the Independent System Operator (ISO), and the ISO staffs or shares staff with the regional reliability council. This process may be a natural and very positive consequence of utility restructuring. If so, the process should be expedited in regions where it is less advanced.

  10. Smart grid in China

    DEFF Research Database (Denmark)

    Sommer, Simon; Ma, Zheng; Jørgensen, Bo Nørregaard

    2015-01-01

    China is planning to transform its traditional power grid in favour of a smart grid, since it allows a more economically efficient and a more environmentally friendly transmission and distribution of electricity. Thus, a nationwide smart grid is likely to save tremendous amounts of resources...

  11. An environmental sample chamber for reliable scanning transmission x-ray microscopy measurements under water vapor

    Energy Technology Data Exchange (ETDEWEB)

    Kelly, Stephen T.; Nigge, Pascal; Prakash, Shruti; Gilles, Mary K. [Chemical Sciences Division, Lawrence Berkeley National Laboratory, Berkeley, California 94720 (United States); Laskin, Alexander; Wang, Bingbing [William R. Wiley Environmental Molecular Sciences Laboratory, Pacific Northwest National Laboratory, Richland, Washington 99352 (United States); Tyliszczak, Tolek [Advanced Light Source, Lawrence Berkeley National Laboratory, Berkeley, California 94720 (United States); Leone, Stephen R. [Chemical Sciences Division, Lawrence Berkeley National Laboratory, Berkeley, California 94720 (United States); Department of Chemistry and Department of Physics, University of California, Berkeley, California 94720 (United States)

    2013-07-15

    We have designed, fabricated, and tested a compact gas-phase reactor for performing in situ soft x-ray scanning transmission x-ray microscopy (STXM) measurements. The reactor mounts directly to the existing sample holder used in the majority of STXM instruments around the world and installs with minimal instrument reconfiguration. The reactor accommodates many gas atmospheres, but was designed specifically to address the needs of measurements under water vapor. An on-board sensor measures the relative humidity and temperature inside the reactor, minimizing uncertainties associated with measuring these quantities outside the instrument. The reactor reduces x-ray absorption from the process gas by over 85% compared to analogous experiments with the entire STXM instrument filled with process gas. Reduced absorption by the process gas allows data collection at full instrumental resolution, minimizes radiation dose to the sample, and results in much more stable imaging conditions. The reactor is in use at the STXM instruments at beamlines 11.0.2 and 5.3.2.2 at the Advanced Light Source.

  12. Transmission line transformer for reliable and low-jitter triggering of a railgap switch.

    Science.gov (United States)

    Verma, Rishi; Mishra, Ekansh; Sagar, Karuna; Meena, Manraj; Shyam, Anurag

    2014-09-01

    The performance of railgap switch critically relies upon multichannel breakdown between the extended electrodes (rails) in order to ensure distributed current transfer along electrode length and to minimize the switch inductance. The initiation of several simultaneous arc channels along the switch length depends on the gap triggering technique and on the rate at which the electric field changes within the gap. This paper presents design, construction, and output characteristics of a coaxial cable based three-stage transmission line transformer (TLT) that is capable of initiating multichannel breakdown in a high voltage, low inductance railgap switch. In each stage three identical lengths of URM67 coaxial cables have been used in parallel and they have been wounded in separate cassettes to enhance the isolation of the output of transformer from the input. The cascaded output impedance of TLT is ~50 Ω. Along with multi-channel formation over the complete length of electrode rails, significant reduction in jitter (≤2 ns) and conduction delay (≤60 ns) has been observed by the realization of large amplitude (~80 kV), high dV/dt (~6 kV/ns) pulse produced by the indigenously developed TLT based trigger generator. The superior performance of TLT over conventional pulse transformer for railgap triggering application has been compared and demonstrated experimentally.

  13. Offshore wind power plants with VSC-HVDC transmission : Grid code compliance optimization and the effect on high voltage ac transmission system

    NARCIS (Netherlands)

    Ndreko, M.

    2017-01-01

    The development of large offshore wind power generation in the North Sea has been significantly accelerated in the last years. The large distance from shore in combination with the need for large transmission capacity has raised the interest for the voltage source converter high voltage direct

  14. Prospective single and multi-phase short-circuit current levels in the Dutch transmission, sub-transmission and distribution grids

    NARCIS (Netherlands)

    Janssen, A.L.J.; van Riet, M.J.M.; Smeets, R.P.P.; Kanters, J.; van den Akker, W.F.; Aanhaanen, G.L.P.

    2012-01-01

    As elsewhere in the world, also in the Netherlands utilities face an increase in the actual and future short-circuit current levels at all voltages. This development is provoked by the required increase in transmission capacity as well as the concentration of power generation capacity. Large

  15. Smart house-based optimal operation of thermal unit commitment for a smart grid considering transmission constraints

    Science.gov (United States)

    Howlader, Harun Or Rashid; Matayoshi, Hidehito; Noorzad, Ahmad Samim; Muarapaz, Cirio Celestino; Senjyu, Tomonobu

    2018-05-01

    This paper presents a smart house-based power system for thermal unit commitment programme. The proposed power system consists of smart houses, renewable energy plants and conventional thermal units. The transmission constraints are considered for the proposed system. The generated power of the large capacity renewable energy plant leads to the violated transmission constraints in the thermal unit commitment programme, therefore, the transmission constraint should be considered. This paper focuses on the optimal operation of the thermal units incorporated with controllable loads such as Electrical Vehicle and Heat Pump water heater of the smart houses. The proposed method is compared with the power flow in thermal units operation without controllable loads and the optimal operation without the transmission constraints. Simulation results show the validation of the proposed method.

  16. Integrating Variable Renewable Energy into the Grid: Key Issues, Greening the Grid (Spanish Version)

    Energy Technology Data Exchange (ETDEWEB)

    2016-04-01

    This is the Spanish version of 'Greening the Grid - Integrating Variable Renewable Energy into the Grid: Key Issues'. To foster sustainable, low-emission development, many countries are establishing ambitious renewable energy targets for their electricity supply. Because solar and wind tend to be more variable and uncertain than conventional sources, meeting these targets will involve changes to power system planning and operations. Grid integration is the practice of developing efficient ways to deliver variable renewable energy (VRE) to the grid. Good integration methods maximize the cost-effectiveness of incorporating VRE into the power system while maintaining or increasing system stability and reliability. When considering grid integration, policy makers, regulators, and system operators consider a variety of issues, which can be organized into four broad topics: New Renewable Energy Generation, New Transmission, Increased System Flexibility, and Planning for a High RE Future.

  17. Communication solutions for intelligent electricity grid; Kommunikationsloesungen fuer intelligente Stromnetze

    Energy Technology Data Exchange (ETDEWEB)

    Fielhauer, Jochen; Wieserner, Gerhard [Siemens AG, Nuernberg (Germany). Business Unit Sensors and Communication

    2013-06-01

    A central role in the construction of power transmission and power distribution systems are solutions that withstand even the harsh environmental conditions and meet performance-critical applications reliably and without interference. This also applies to all ethernet networks in the power generation and power distribution. Secure and robust communication solutions for smart grids which enable a cost-effective remote monitoring and control of smart grids are decisive.

  18. Evaluation of the reliability of electric power transmission systems; Evaluacion de confiabilidad de sistemas de transmision de energia electrica

    Energy Technology Data Exchange (ETDEWEB)

    Vega Ortiz, Miguel

    1989-07-01

    In this thesis it is attacked the problem of Reliability Evaluation of the Electrical Power Transmission Systems for aims of its integral planning. Once described the problem the indexes that measure the electric power systems reliability are presented. Later the methods to evaluate the transmission nets, such as the Contingencies Enumeration, the Monte Carlo, the one of Markov and the methods for complex systems such as the Minimum Interruptions, are described. This last one is widely developed for the advantages that its application presents in the planning of large and complex networks. The method of minimum interruptions consists of two big steps: To determine the minimum interruptions for the load points and to calculate the reliability indexes in base of the minimum interruptions. The conventional algorithms for the determination of minimum interruptions consider a problem for each load point in an independent form going through a determination of minimum tracks. In this type of algorithms the CPU time and the space in memory required grow exponentially for the case of large transmission systems, which represents a strong restriction for its application. In order to solve this problem a methodology was established in which the system is modeled by means of a grapho and the minimum interruptions are determined with an algorithm based on the construction of cycles in the dual grapho. With these interruptions the connectivity and the capacity of the network is evaluated, obtaining the reliability indexes for each bus and the system. These indexes are calculated with the equivalent representation for complex systems of series parallel connections defined by the minimum interruptions. One of the fundamental objectives in this study is to integrate the reliability to the planning process, with the concept of the expected value of the non-supplied energy and its penalty cost. In order to demonstrate the capacity, effectiveness and rapidity of the new implemented

  19. Cost on Reliability and Production Loss for Power Converters in the Doubly Fed Induction Generator to Support Modern Grid Codes

    DEFF Research Database (Denmark)

    Zhou, Dao; Blaabjerg, Frede; Lau, Mogens

    2016-01-01

    As wind farms are normally located in remote areas, many grid codes have been issued especially related to the reactive power support. Although the Doubly-Fed Induction Generator (DFIG) based power converter is able to control the active power and reactive power independently, the effects...... of providing reactive power on the lifetime of the power converter and the cost-of-energy of the whole system are seldom evaluated, even though it is an important topic. In this paper, the loss models of the DFIG system are established at various conditions of the reactive power injection. If the mission...... profile is taken into account, the lifespan of the power semiconductors as well as the cost of the reactive power can be calculated. It is concluded that an over-excited reactive power injection significantly reduces the power converter lifetime, only 1/4 of the case that there is no reactive power...

  20. Expanding the grid in Alberta

    Energy Technology Data Exchange (ETDEWEB)

    Horner, M. [AltaLink Management Ltd., Calgary, AB (Canada)

    2010-07-01

    This PowerPoint presentation discussed some of the changes and strategies that are currently being adopted by AltaLink to expand Alberta's electricity grid in relation to wind power development. The company is Alberta's largest transmission facility operator. Wind power currently accounts for approximately 5 percent of the province's generation mix. Applications for new wind farms will increase Alberta's 629 MW of wind power generation capacity to 5530 MW. Alberta's transmission regulation requires that 100 percent of in-merit generation can occur when transmission facilities are in service, and that 95 percent of in-merit generation can occur under abnormal operating conditions. A new transmission line is being constructed in the Pincher Creek and Lethbridge region as part of a southern Alberta transmission reinforcement project. The Alberta Electric System Operator (AESO) and Canadian Wind Energy Association (CanWEA) are working together to ensure that adequate resources are available while system reliability is maintained. The Ardenville wind farm is the first wind power project to be energized under the new connection model launched by the AESO. The connection model was developed to identify, connect, and construct new energy projects. The project will also identify connection routes with the lowest overall impact on the province. Alberta will also continue to implement technologies that ensure the development of a smart grid. tabs., figs.

  1. Reliability of offshore wind power production under extreme wind conditions. Deliverable D 9.5. Work Package 9: Electrical grid

    DEFF Research Database (Denmark)

    Cutululis, Nicolaos Antonio; Zeni, Lorenzo

    years, with each year simulated with five random seeds, leading to a total of 25 annual wind power time series for six large offshore wind farms, summing up to a little over 330 wind turbines. Two storm control strategies were used. The analysis involved several aspects inspired from reliability studies....... The aspects investigated are storm events occurrences and durations, storm control strategy impact on the capacity factor (lost production), the loss of production (power produced from wind drops below a certain threshold due to high wind speeds and storm controller) and finally, the wind power production......Reliability of offshore wind production under extreme wind conditions was investigated in this report. The wind power variability from existing and future large offshore wind farms in Western Denmark were simulated using the Correlated Wind model developed at Risø. The analysis was done for five...

  2. The often neglected yet crucial element in smart grid strategies

    Energy Technology Data Exchange (ETDEWEB)

    DiMarco, T. [Utility Industry Global Marketing Security, New York, NY (United States); Smith, W. [Intergraph Corp., Huntsville, AL (United States)

    2008-11-15

    Smart grids consist of automation technology that includes selfhealing networks, intelligent applications, and smart meters to improve load management. Electric utilities can benefit from making the transition from existing infrastructure to leading edge smart grid technology which offers better reliability and reduced maintenance costs. The smart grid improves the efficiency of electrical transmission and distribution, whether it involves carbon policies, grid modernization, renewable energy sources or smart end-use devices for the customer. Smart grids are expected to improve scheduling efficiency, dispatch management, transmission line surveillance and cyber security by enabling faster and better decisions from the control room. However, a smart grid control center is prone to human error. Operators must monitor data, locate work crews, analyze power system reports, and survey real-time transmission line data. They must choose optimal network configurations, whether it is to control voltage or to manage system restart following an outage. To do so, they need a system that will allow them to speed their analysis and take action. The true value of a smart grid is being able to see and control several critical applications in one unified system. A common operating picture improves overall situational awareness, reduces costs and increases efficiency in grid operations. The control center of the future will have 2D and 3D graphical visualization of complex real-time data to improve situational awareness, with multiple layers of information, including outages, distribution automation, geographic information systems, network analysis, and workforce management in a unified system. 1 fig.

  3. Overview of Recent Grid Codes for Wind Power Integration

    DEFF Research Database (Denmark)

    Altin, Müfit; Göksu, Ömer; Teodorescu, Remus

    2010-01-01

    As wind power penetration level increases, power system operators are challenged by the penetration impacts to maintain reliability and stability of power system. Therefore, grid codes are being published and continuously updated by transmission system operators of the countries. In this paper...

  4. Low-cost solution to the grid reliability problem with 100% penetration of intermittent wind, water, and solar for all purposes.

    Science.gov (United States)

    Jacobson, Mark Z; Delucchi, Mark A; Cameron, Mary A; Frew, Bethany A

    2015-12-08

    This study addresses the greatest concern facing the large-scale integration of wind, water, and solar (WWS) into a power grid: the high cost of avoiding load loss caused by WWS variability and uncertainty. It uses a new grid integration model and finds low-cost, no-load-loss, nonunique solutions to this problem on electrification of all US energy sectors (electricity, transportation, heating/cooling, and industry) while accounting for wind and solar time series data from a 3D global weather model that simulates extreme events and competition among wind turbines for available kinetic energy. Solutions are obtained by prioritizing storage for heat (in soil and water); cold (in ice and water); and electricity (in phase-change materials, pumped hydro, hydropower, and hydrogen), and using demand response. No natural gas, biofuels, nuclear power, or stationary batteries are needed. The resulting 2050-2055 US electricity social cost for a full system is much less than for fossil fuels. These results hold for many conditions, suggesting that low-cost, reliable 100% WWS systems should work many places worldwide.

  5. Strategies and Decision Support Systems for Integrating Variable Energy Resources in Control Centers for Reliable Grid Operations

    Energy Technology Data Exchange (ETDEWEB)

    Jones, Lawrence E.

    2012-01-05

    A variety of studies have recently evaluated the opportunities for the large-scale integration of wind energy into the US power system. These studies have included, but are not limited to, "20 Percent Wind Energy by 2030: Increasing Wind Energy's Contribution to US Electricity Supply", the "Western Wind and Solar Integration Study", and the "Eastern Wind Integration and Transmission Study." Each of these US based studies have evaluated a variety of activities that can be undertaken by utilities to help integrate wind energy.

  6. Examination of fault ride-through methods for off-shore wind farms connected to the grid through VSC-based HVDC transmission

    Energy Technology Data Exchange (ETDEWEB)

    Karaagac, U.; Mahseredjian, J.; Saad, H. [Ecole Polytechnique de Montreal, QC (Canada); Jensen, S.; Cai, L. [REpower Systems AG, Hamburg (Germany)

    2012-07-01

    The fault ride-through (FRT) performance of offshore wind farms (OWFs) is a challenging task when the OWF is connected to the onshore ac grid through a voltage source converter (VSC) based HVDC transmission system. The injected power from the OWF cannot be reduced by the offshore VSC during onshore ac faults and this causes a fast increase in the dc network voltage. Without any special FRT method, the dc network voltage may increase up to intolerable levels and cause operation of dc overvoltage protection. This paper compares various FRT methods based on fast reduction of power generation in OWFs. In addition, this paper proposes an improved FRT method based on controlled voltage drop for output power reduction in OWFs. The proposed improvement reduces mechanical stress on the wind turbine (WT) drive train, and electrical stress on the insulated gate bipolar transistors (IGBTs) of the HVDC and doubly-fed induction generator (DFIG) converters. Practical onshore ac fault scenarios are simulated for an OWF composed of DFIG type WTs and connected to a practical ac grid through a point-to-point modular multilevel converter (MMC) based HVDC system. (orig.)

  7. Providing all global energy with wind, water, and solar power, Part II: Reliability, system and transmission costs, and policies

    International Nuclear Information System (INIS)

    Delucchi, Mark A.; Jacobson, Mark Z.

    2011-01-01

    This is Part II of two papers evaluating the feasibility of providing all energy for all purposes (electric power, transportation, and heating/cooling), everywhere in the world, from wind, water, and the sun (WWS). In Part I, we described the prominent renewable energy plans that have been proposed and discussed the characteristics of WWS energy systems, the global demand for and availability of WWS energy, quantities and areas required for WWS infrastructure, and supplies of critical materials. Here, we discuss methods of addressing the variability of WWS energy to ensure that power supply reliably matches demand (including interconnecting geographically dispersed resources, using hydroelectricity, using demand-response management, storing electric power on site, over-sizing peak generation capacity and producing hydrogen with the excess, storing electric power in vehicle batteries, and forecasting weather to project energy supplies), the economics of WWS generation and transmission, the economics of WWS use in transportation, and policy measures needed to enhance the viability of a WWS system. We find that the cost of energy in a 100% WWS will be similar to the cost today. We conclude that barriers to a 100% conversion to WWS power worldwide are primarily social and political, not technological or even economic. - Research highlights: → We evaluate the feasibility of global energy supply from wind, water, and solar energy. → WWS energy can be supplied reliably and economically to all energy-use sectors. → The social cost of WWS energy generally is less than the cost of fossil-fuel energy. → Barriers to 100% WWS power worldwide are socio-political, not techno-economic.

  8. Survey of Transmission Cost Allocation Methodologies for Regional Transmission Organizations

    Energy Technology Data Exchange (ETDEWEB)

    Fink, S.; Porter, K.; Mudd, C.; Rogers, J.

    2011-02-01

    The report presents transmission cost allocation methodologies for reliability transmission projects, generation interconnection, and economic transmission projects for all Regional Transmission Organizations.

  9. CERTS: Consortium for Electric Reliability Technology Solutions - Research Highlights

    Energy Technology Data Exchange (ETDEWEB)

    Eto, Joseph

    2003-07-30

    Historically, the U.S. electric power industry was vertically integrated, and utilities were responsible for system planning, operations, and reliability management. As the nation moves to a competitive market structure, these functions have been disaggregated, and no single entity is responsible for reliability management. As a result, new tools, technologies, systems, and management processes are needed to manage the reliability of the electricity grid. However, a number of simultaneous trends prevent electricity market participants from pursuing development of these reliability tools: utilities are preoccupied with restructuring their businesses, research funding has declined, and the formation of Independent System Operators (ISOs) and Regional Transmission Organizations (RTOs) to operate the grid means that control of transmission assets is separate from ownership of these assets; at the same time, business uncertainty, and changing regulatory policies have created a climate in which needed investment for transmission infrastructure and tools for reliability management has dried up. To address the resulting emerging gaps in reliability R&D, CERTS has undertaken much-needed public interest research on reliability technologies for the electricity grid. CERTS' vision is to: (1) Transform the electricity grid into an intelligent network that can sense and respond automatically to changing flows of power and emerging problems; (2) Enhance reliability management through market mechanisms, including transparency of real-time information on the status of the grid; (3) Empower customers to manage their energy use and reliability needs in response to real-time market price signals; and (4) Seamlessly integrate distributed technologies--including those for generation, storage, controls, and communications--to support the reliability needs of both the grid and individual customers.

  10. Reliability Testing Beyond Qualification as a Key Component in Photovoltaic's Progress Toward Grid Parity: Preprint

    Energy Technology Data Exchange (ETDEWEB)

    Wohlgemuth, J. H.; Kurtz, S.

    2011-02-01

    This paper discusses why it is necessary for new lower cost PV modules to be tested using a reliability test sequence that goes beyond the Qualification test sequence now utilized for modules. Today most PV modules are warranted for 25 years, but the Qualification Test Sequence does not test for 25-year life. There is no accepted test protocol to validate a 25-year lifetime. This paper recommends the use of long term accelerated testing to compare now designs directly with older designs that have achieved long lifetimes in outdoor exposure. If the new designs do as well or better than the older ones, then it is likely that they will survive an equivalent length of time in the field.

  11. Improving the Reliability of Optimised Link State Routing in a Smart Grid Neighbour Area Network based Wireless Mesh Network Using Multiple Metrics

    Directory of Open Access Journals (Sweden)

    Yakubu Tsado

    2017-02-01

    Full Text Available Reliable communication is the backbone of advanced metering infrastructure (AMI. Within the AMI, the neighbourhood area network (NAN transports a multitude of traffic, each with unique requirements. In order to deliver an acceptable level of reliability and latency, the underlying network, such as the wireless mesh network(WMN, must provide or guarantee the quality-of-service (QoS level required by the respective application traffic. Existing WMN routing protocols, such as optimised link state routing (OLSR, typically utilise a single metric and do not consider the requirements of individual traffic; hence, packets are delivered on a best-effort basis. This paper presents a QoS-aware WMN routing technique that employs multiple metrics in OLSR optimal path selection for AMI applications. The problems arising from this approach are non deterministic polynomial time (NP-complete in nature, which were solved through the combined use of the analytical hierarchy process (AHP algorithm and pruning techniques. For smart meters transmitting Internet Protocol (IP packets of varying sizes at different intervals, the proposed technique considers the constraints of NAN and the applications’ traffic characteristics. The technique was developed by combining multiple OLSR path selection metrics with the AHP algorithminns-2. Compared with the conventional link metric in OLSR, the results show improvements of about 23% and 45% in latency and Packet Delivery Ratio (PDR, respectively, in a 25-node grid NAN.

  12. Cost- and reliability-oriented aggregation point association in long-term evolution and passive optical network hybrid access infrastructure for smart grid neighborhood area network

    Science.gov (United States)

    Cheng, Xiao; Feng, Lei; Zhou, Fanqin; Wei, Lei; Yu, Peng; Li, Wenjing

    2018-02-01

    With the rapid development of the smart grid, the data aggregation point (AP) in the neighborhood area network (NAN) is becoming increasingly important for forwarding the information between the home area network and wide area network. Due to limited budget, it is unable to use one-single access technology to meet the ongoing requirements on AP coverage. This paper first introduces the wired and wireless hybrid access network with the integration of long-term evolution (LTE) and passive optical network (PON) system for NAN, which allows a good trade-off among cost, flexibility, and reliability. Then, based on the already existing wireless LTE network, an AP association optimization model is proposed to make the PON serve as many APs as possible, considering both the economic efficiency and network reliability. Moreover, since the features of the constraints and variables of this NP-hard problem, a hybrid intelligent optimization algorithm is proposed, which is achieved by the mixture of the genetic, ant colony and dynamic greedy algorithm. By comparing with other published methods, simulation results verify the performance of the proposed method in improving the AP coverage and the performance of the proposed algorithm in terms of convergence.

  13. Smart grids fundamentals and technologies in electricity networks

    CERN Document Server

    Buchholz, Bernd M

    2014-01-01

    Efficient transmission and distribution of electricity is a fundamental requirement for sustainable development and prosperity. The world is facing great challenges regarding the reliable grid integration of renewable energy sources in the 21st century. The electric power systems of the future require fundamental innovations and enhancements to meet these challenges. The European Union's "Smart Grid" vision provides a first overview of the appropriate deep-paradigm changes in the transmission, distribution and supply of electricity.The book brings together common themes beginning with Smart Gr

  14. Electrical transmission

    Energy Technology Data Exchange (ETDEWEB)

    Sayers, D P

    1960-05-01

    After briefly tracing the history of electricity transmission, trends in high voltage transmission and experiments being conducted on 650 kV are discussed. 5000 miles of the U.K. grid are operated at 132 kV and 1000 at 275 kV, ultimately to provide a super grid at 380 kV. Problems are insulation, radio interference and the cost of underground lines (16 times that of overhead lines). Also considered are the economics of the grid as a means of transporting energy and as a means of spreading the peak load over the power stations in the most efficient manner. Finally, the question of amenities is discussed.

  15. Analysis to Inform CA Grid Integration Rules for PV: Final Report on Inverter Settings for Transmission and Distribution System Performance

    Energy Technology Data Exchange (ETDEWEB)

    Smith, Jeff [Electric Power Research Inst. (EPRI), Palo Alto, CA (United States); Rylander, Matthew [Electric Power Research Inst. (EPRI), Palo Alto, CA (United States); Boemer, Jens [Electric Power Research Inst. (EPRI), Palo Alto, CA (United States); Broderick, Robert Joseph [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States); Reno, Matthew J. [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States); Mather, Barry [National Renewable Energy Lab. (NREL), Golden, CO (United States)

    2016-09-01

    The fourth solicitation of the California Solar Initiative (CSI) Research, Development, Demonstration and Deployment (RD&D) Program established by the California Public Utilities Commission (CPUC) supported the Electric Power Research Institute (EPRI), National Renewable Energy Laboratory (NREL), and Sandia National Laboratories (SNL) with data provided from Pacific Gas and Electric (PG&E), Southern California Edison (SCE), and San Diego Gas and Electric (SDG&E) conducted research to determine optimal default settings for distributed energy resource advanced inverter controls. The inverter functions studied are aligned with those developed by the California Smart Inverter Working Group (SIWG) and those being considered by the IEEE 1547 Working Group. The advanced inverter controls examined to improve the distribution system response included power factor, volt-var, and volt-watt. The advanced inverter controls examined to improve the transmission system response included frequency and voltage ride-through as well as Dynamic Voltage Support. This CSI RD&D project accomplished the task of developing methods to derive distribution focused advanced inverter control settings, selecting a diverse set of feeders to evaluate the methods through detailed analysis, and evaluating the effectiveness of each method developed. Inverter settings focused on the transmission system performance were also evaluated and verified. Based on the findings of this work, the suggested advanced inverter settings and methods to determine settings can be used to improve the accommodation of distributed energy resources (PV specifically). The voltage impact from PV can be mitigated using power factor, volt-var, or volt-watt control, while the bulk system impact can be improved with frequency/voltage ride-through.

  16. Analysis of the public debate on health hazards due to high-voltage transmission lines. Recommendations for the radiation protection related communication with respect of grid extension

    International Nuclear Information System (INIS)

    Weber, Florian; Kuehne, Olaf; Jenal, Corinna; Sanio, Tina; Langer, Kerstin; Igel, Michael

    2016-01-01

    highlights the decisive role played by different social systems and their specific logics in any evaluative judgment. While industry and politics argue from the technological and economic need for new long-distance power lines, and urge this as the basis for their legitimacy, citizens' initiatives base their objections on emotional and aesthetic grounds, rejecting the change to their domestic and social environment as a looming threat, with all its negative connotations. Plans are regularly criticized for their impact on landscape, nature conservation, local economies, tourism, and health. Citizens' initiatives almost unanimously cite health risks and fears in connection with electro/magnetic fields, while the advocates of grid extension - the Federal Network Agency and transmission system operators - take a variety of approaches to this matter. The Federal Network Agency generally marginalizes health issues, and does so in specialist language, or in terms that demand in-depth study. On the other hand Amprion GmbH, as one of the operators, uses language that is readily accessible to laypeople, and its explanations leave less room for doubt than do those of the Federal Network Agency. Amprion argues that it can fulfill its task within the existing legislative framework. Nevertheless, health issues are not the company's main concern. TenneT TSO GmbH takes a more comprehensive approach, and its statements are more readily understandable, even though they also tend to use specialist language, citing scientific studies and generally softening risk. Sound scientific results are so far notably lacking, but improved communication of the known pros and cons of this technology is also urgently required. Another consistent factor is the problematic light in which previous grid extension plans and implementation processes are typically set, and the massive civic protests to which this has at various times given rise. Transmission system operators should have learnt by now

  17. Hawaii Electric System Reliability

    Energy Technology Data Exchange (ETDEWEB)

    Loose, Verne William [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States); Silva Monroy, Cesar Augusto [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States)

    2012-08-01

    This report addresses Hawaii electric system reliability issues; greater emphasis is placed on short-term reliability but resource adequacy is reviewed in reference to electric consumers’ views of reliability “worth” and the reserve capacity required to deliver that value. The report begins with a description of the Hawaii electric system to the extent permitted by publicly available data. Electrical engineering literature in the area of electric reliability is researched and briefly reviewed. North American Electric Reliability Corporation standards and measures for generation and transmission are reviewed and identified as to their appropriateness for various portions of the electric grid and for application in Hawaii. Analysis of frequency data supplied by the State of Hawaii Public Utilities Commission is presented together with comparison and contrast of performance of each of the systems for two years, 2010 and 2011. Literature tracing the development of reliability economics is reviewed and referenced. A method is explained for integrating system cost with outage cost to determine the optimal resource adequacy given customers’ views of the value contributed by reliable electric supply. The report concludes with findings and recommendations for reliability in the State of Hawaii.

  18. Hawaii electric system reliability.

    Energy Technology Data Exchange (ETDEWEB)

    Silva Monroy, Cesar Augusto; Loose, Verne William

    2012-09-01

    This report addresses Hawaii electric system reliability issues; greater emphasis is placed on short-term reliability but resource adequacy is reviewed in reference to electric consumers' views of reliability %E2%80%9Cworth%E2%80%9D and the reserve capacity required to deliver that value. The report begins with a description of the Hawaii electric system to the extent permitted by publicly available data. Electrical engineering literature in the area of electric reliability is researched and briefly reviewed. North American Electric Reliability Corporation standards and measures for generation and transmission are reviewed and identified as to their appropriateness for various portions of the electric grid and for application in Hawaii. Analysis of frequency data supplied by the State of Hawaii Public Utilities Commission is presented together with comparison and contrast of performance of each of the systems for two years, 2010 and 2011. Literature tracing the development of reliability economics is reviewed and referenced. A method is explained for integrating system cost with outage cost to determine the optimal resource adequacy given customers' views of the value contributed by reliable electric supply. The report concludes with findings and recommendations for reliability in the State of Hawaii.

  19. Grid Architecture 2

    Energy Technology Data Exchange (ETDEWEB)

    Taft, Jeffrey D. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States)

    2016-01-01

    The report describes work done on Grid Architecture under the auspices of the Department of Electricity Office of Electricity Delivery and Reliability in 2015. As described in the first Grid Architecture report, the primary purpose of this work is to provide stakeholder insight about grid issues so as to enable superior decision making on their part. Doing this requires the creation of various work products, including oft-times complex diagrams, analyses, and explanations. This report provides architectural insights into several important grid topics and also describes work done to advance the science of Grid Architecture as well.

  20. Wide-area situation awareness in electric power grid

    Science.gov (United States)

    Greitzer, Frank L.

    2010-04-01

    Two primary elements of the US energy policy are demand management and efficiency and renewable sources. Major objectives are clean energy transmission and integration, reliable energy transmission, and grid cyber security. Development of the Smart Grid seeks to achieve these goals by lowering energy costs for consumers, achieving energy independence and reducing greenhouse gas emissions. The Smart Grid is expected to enable real time wide-area situation awareness (SA) for operators. Requirements for wide-area SA have been identified among interoperability standards proposed by the Federal Energy Regulatory Commission and the National Institute of Standards and Technology to ensure smart-grid functionality. Wide-area SA and enhanced decision support and visualization tools are key elements in the transformation to the Smart Grid. This paper discusses human factors research to promote SA in the electric power grid and the Smart Grid. Topics that will be discussed include the role of human factors in meeting US energy policy goals, the impact and challenges for Smart Grid development, and cyber security challenges.

  1. Alternative approaches to transmission investment

    Energy Technology Data Exchange (ETDEWEB)

    Thon, S. [AltaLink Management Ltd., Calgary, AB (Canada)

    2004-07-01

    AltaLink is Canada's first stand-alone power transmission company, serving all major centres in Alberta and 85 per cent of Alberta's population. It has more than $1 billion in assets, 11,500 km of transmission lines and 300 substations. It was noted that there has not been any significant investment in power transmission in Alberta for the past 20 years, partly because transmission assets have a very long lifespan. The new role of the power grid is to ensure reliability, safety, efficiency, market effectiveness and supply diversity. The benefits and costs of AltaLink's 500 kV North-South upgrade project were outlined. It was noted that a healthy transmission system is the basis for economic growth throughout the province and for the development of Alberta's resource base. The transmission policy in Alberta endorses that all consumers pay postage stamp tariffs. It also promotes a proactive plan for transmission projects, the time to maximum rate (TMR) in limited cases only, a congestion-free grid under normal conditions, the financial commitment of generators, specific time limits on permitting processes, and regional interconnections to benefit all customers. tabs., figs.

  2. DanGrid. Report from working group 24. Roadmap for Smart Grid in Denmark with emphasis on the transmission companies' role; DanGrid. Delrapport. Arbejdsgruppe 24. Roadmap for Smart Grid i Danmark med saerlig vaegt pae netselskabernes rolle

    Energy Technology Data Exchange (ETDEWEB)

    Lomholt Finnemann, K. [DONG Energy, Virum (Denmark); Soerensen, Per [TRE-FOR, Kolding (Denmark); Larsen, Jim [EnergiMidt, Silkeborg (Denmark); Balasiu, A. [Siemens, Ballerup (Denmark); Holmberg Rasmussen, L. [Nordjysk Elhandel, Aalborg (Denmark); Moeller Joergensen, J. [Energinet.dk, Fredericia (Denmark); Norsk Jensen, A.; Nejsum, T.; Andersen, Kim [Dansk Energi, Frederiksberg (Denmark)

    2012-09-15

    The present report identifies a number of recommendations where specifically grid companies, but also authorities, customers and market players must initiate actions and activities to realize Smart Grid in Denmark by 2020. The report forms the basis for each network operator to implement Smart Grid, and is divided such that: 1 the management can create an overview of the steps to be taken in connection with the implementation, and 2. the technical department can develop a series of concrete actions to be implemented in the Smart Grid. The measures are divided into four groups: 1 - Establishment of business case and strategy: Efforts that support that each network operator prepares a business case and define a strategy for the creation of a Smart Grid. 2 - New technology in the grid: Measures relating to the importation of new technology in the grid, for example establishment of technology solutions for automating and monitoring the load on the network, and installing additional measurements at strategic points in the distribution network. 3 - Enabling customers' demand response: Initiatives that support that the grid company actively involves end users through price signals or by entering into agreements to regulate or move power consumption to a time of free capacity in the grid. 4 - Other activities: Measures which are horizontal and support that network companies develop a Smart Grid. New economic regulation of network companies is required to support the introduction of new technology in the grid, and at the same time crucial to enable customers' demand response. IT and data security must be established and customer engagement as active consumers of electricity should be strengthened. (LN)

  3. reliability reliability

    African Journals Online (AJOL)

    eobe

    Corresponding author, Tel: +234-703. RELIABILITY .... V , , given by the code of practice. However, checks must .... an optimization procedure over the failure domain F corresponding .... of Concrete Members based on Utility Theory,. Technical ...

  4. What is a smart grid?

    NARCIS (Netherlands)

    Kumar, A.

    2017-01-01

    The Indian Smart Grid Forum defines a smart grid as "a power system capable of two-way communication between all the entities of the network-generation, transmission, distribution and the consumers". Like most work on smart grids, this view is also mainly technical. This paper aims to progress the

  5. Renewable Energy Zone (REZ) Transmission Planning Process

    Energy Technology Data Exchange (ETDEWEB)

    Lee, Nathan [National Renewable Energy Laboratory (NREL), Golden, CO (United States)

    2018-03-08

    A REZ is a geographical area that enables the development of profitable, cost-effective, grid-connected renewable energy (RE). The REZ Transmission Planning Process is a proactive approach to plan, approve, and build transmission infrastructure connecting REZs to the power system which helps to increase the share of solar, wind and other RE resources in the power system while maintaining reliability and economics, and focuses on large-scale wind and solar resources that can be developed in sufficient quantities to warrant transmission system expansion and upgrades.

  6. Analysis and improvement of security of energy smart grids

    International Nuclear Information System (INIS)

    Halimi, Halim

    2014-01-01

    The Smart grid is the next generation power grid, which is a new self-healing, self-activating form of electricity network, and integrates power-flow control, increased quality of electricity, and energy reliability, energy efficiency and energy security using information and communication technologies. Communication networks play a critical role in smart grid, as the intelligence of smart grid is built based on information exchange across the power grid. Its two-way communication and electricity flow enable to monitor, predict and manage the energy usage. To upgrade an existing power grid into a smart grid, it requires an intelligent and secure communication infrastructure. Because of that, the main goal of this dissertation is to propose new architecture and implementation of algorithms for analysis and improvement of the security and reliability in smart grid. In power transmission segments of smart grid, wired communications are usually adopted to ensure robustness of the backbone power network. In contrast, for a power distribution grid, wireless communications provide many benefits such as low cost high speed links, easy setup of connections among different devices/appliances, and so on. Wireless communications are usually more vulnerable to security attacks than wired ones. Developing appropriate wireless communication architecture and its security measures is extremely important for a smart grid system. This research addresses physical layer security in a Wireless Smart Grid. Hence a defense Quorum- based algorithm is proposed to ensure physical security in wireless communication. The new security architecture for smart grid that supports privacy-preserving, data aggregation and access control is defined. This architecture consists of two parts. In the first part we propose to use an efficient and privacy-preserving aggregation scheme (EPPA), which aggregates real-time data of consumers by Local Gateway. During aggregation the privacy of consumers is

  7. Towards Integrating Distributed Energy Resources and Storage Devices in Smart Grid.

    Science.gov (United States)

    Xu, Guobin; Yu, Wei; Griffith, David; Golmie, Nada; Moulema, Paul

    2017-02-01

    Internet of Things (IoT) provides a generic infrastructure for different applications to integrate information communication techniques with physical components to achieve automatic data collection, transmission, exchange, and computation. The smart grid, as one of typical applications supported by IoT, denoted as a re-engineering and a modernization of the traditional power grid, aims to provide reliable, secure, and efficient energy transmission and distribution to consumers. How to effectively integrate distributed (renewable) energy resources and storage devices to satisfy the energy service requirements of users, while minimizing the power generation and transmission cost, remains a highly pressing challenge in the smart grid. To address this challenge and assess the effectiveness of integrating distributed energy resources and storage devices, in this paper we develop a theoretical framework to model and analyze three types of power grid systems: the power grid with only bulk energy generators, the power grid with distributed energy resources, and the power grid with both distributed energy resources and storage devices. Based on the metrics of the power cumulative cost and the service reliability to users, we formally model and analyze the impact of integrating distributed energy resources and storage devices in the power grid. We also use the concept of network calculus, which has been traditionally used for carrying out traffic engineering in computer networks, to derive the bounds of both power supply and user demand to achieve a high service reliability to users. Through an extensive performance evaluation, our data shows that integrating distributed energy resources conjointly with energy storage devices can reduce generation costs, smooth the curve of bulk power generation over time, reduce bulk power generation and power distribution losses, and provide a sustainable service reliability to users in the power grid.

  8. Reliability issues : a Canadian perspective

    International Nuclear Information System (INIS)

    Konow, H.

    2004-01-01

    A Canadian perspective of power reliability issues was presented. Reliability depends on adequacy of supply and a framework for standards. The challenges facing the electric power industry include new demand, plant replacement and exports. It is expected that demand will by 670 TWh by 2020, with 205 TWh coming from new plants. Canada will require an investment of $150 billion to meet this demand and the need is comparable in the United States. As trade grows, the challenge becomes a continental issue and investment in the bi-national transmission grid will be essential. The 5 point plan of the Canadian Electricity Association is to: (1) establish an investment climate to ensure future electricity supply, (2) move government and industry towards smart and effective regulation, (3) work to ensure a sustainable future for the next generation, (4) foster innovation and accelerate skills development, and (5) build on the strengths of an integrated North American system to maximize opportunity for Canadians. The CEA's 7 measures that enhance North American reliability were listed with emphasis on its support for a self-governing international organization for developing and enforcing mandatory reliability standards. CEA also supports the creation of a binational Electric Reliability Organization (ERO) to identify and solve reliability issues in the context of a bi-national grid. tabs., figs

  9. Interior point algorithm-based power flow optimisation of a combined AC and DC multi-terminal grid

    Directory of Open Access Journals (Sweden)

    Farhan Beg

    2015-01-01

    Full Text Available The high cost of power electronic equipment, lower reliability and poor power handling capacity of the semiconductor devices had stalled the deployment of systems based on DC (multi-terminal direct current system (MTDC networks. The introduction of voltage source converters (VSCs for transmission has renewed the interest in the development of large interconnected grids based on both alternate current (AC and DC transmission networks. Such a grid platform also realises the added advantage of integrating the renewable energy sources into the grid. Thus a grid based on DC MTDC network is a possible solution to improve energy security and check the increasing supply demand gap. An optimal power solution for combined AC and DC grids obtained by the solution of the interior point algorithm is proposed in this study. Multi-terminal HVDC grids lie at the heart of various suggested transmission capacity increases. A significant difference is observed when MTDC grids are solved for power flows in place of conventional AC grids. This study deals with the power flow problem of a combined MTDC and an AC grid. The AC side is modelled with the full power flow equations and the VSCs are modelled using a connecting line, two generators and an AC node. The VSC and the DC losses are also considered. The optimisation focuses on several different goals. Three different scenarios are presented in an arbitrary grid network with ten AC nodes and five converter stations.

  10. QoS Differential Scheduling in Cognitive-Radio-Based Smart Grid Networks: An Adaptive Dynamic Programming Approach.

    Science.gov (United States)

    Yu, Rong; Zhong, Weifeng; Xie, Shengli; Zhang, Yan; Zhang, Yun

    2016-02-01

    As the next-generation power grid, smart grid will be integrated with a variety of novel communication technologies to support the explosive data traffic and the diverse requirements of quality of service (QoS). Cognitive radio (CR), which has the favorable ability to improve the spectrum utilization, provides an efficient and reliable solution for smart grid communications networks. In this paper, we study the QoS differential scheduling problem in the CR-based smart grid communications networks. The scheduler is responsible for managing the spectrum resources and arranging the data transmissions of smart grid users (SGUs). To guarantee the differential QoS, the SGUs are assigned to have different priorities according to their roles and their current situations in the smart grid. Based on the QoS-aware priority policy, the scheduler adjusts the channels allocation to minimize the transmission delay of SGUs. The entire transmission scheduling problem is formulated as a semi-Markov decision process and solved by the methodology of adaptive dynamic programming. A heuristic dynamic programming (HDP) architecture is established for the scheduling problem. By the online network training, the HDP can learn from the activities of primary users and SGUs, and adjust the scheduling decision to achieve the purpose of transmission delay minimization. Simulation results illustrate that the proposed priority policy ensures the low transmission delay of high priority SGUs. In addition, the emergency data transmission delay is also reduced to a significantly low level, guaranteeing the differential QoS in smart grid.

  11. Boosting the adoption and the reliability of renewable energy sources: Mitigating the large-scale wind power intermittency through vehicle to grid technology

    International Nuclear Information System (INIS)

    Zhao, Yang; Noori, Mehdi; Tatari, Omer

    2017-01-01

    The integration of wind energy in the electricity sector and the adoption of electric vehicles in the transportation sector both have the potential to significantly reduce greenhouse gas emissions individually as well as in tandem with Vehicle-to-Grid technology. This study aims to evaluate the greenhouse gas emission savings of mitigating intermittency resulting from the introduction of wind power through Vehicle-to-Grid technologies, as well as the extent to which the marginal electricity consumption from charging an electric vehicle fleet may weaken this overall environmental benefit. To this end, the comparisons are conducted in seven independent system operator regions. The results indicate that, in most cases, the emission savings of a combination of wind power and Vehicle-to-Grid technology outweighs the additional emissions from marginal electricity generation for electric vehicles. In addition, the fluctuations in newly-integrated wind power could be balanced in the future using EVs and V2G technology, provided that a moderate portion of EV owners is willing to provide V2G services. On the other hand, such a combination is not favorable if the Vehicle-to-Grid service participation rate is less than 5% of all electric vehicle owners within a particular region. - Highlights: • The environmental benefit of vehicle to grid systems as grid stabilizer is analyzed. • Emission savings of vehicle to grid and impacts of electric vehicles are compared. • Seven independent system operator regions are studied. • Uncertainty and sensitivity analysis are performed through a Monte Carlo Simulation.

  12. Urban micro-grids

    International Nuclear Information System (INIS)

    Faure, Maeva; Salmon, Martin; El Fadili, Safae; Payen, Luc; Kerlero, Guillaume; Banner, Arnaud; Ehinger, Andreas; Illouz, Sebastien; Picot, Roland; Jolivet, Veronique; Michon Savarit, Jeanne; Strang, Karl Axel

    2017-02-01

    ENEA Consulting published the results of a study on urban micro-grids conducted in partnership with the Group ADP, the Group Caisse des Depots, ENEDIS, Omexom, Total and the Tuck Foundation. This study offers a vision of the definition of an urban micro-grid, the value brought by a micro-grid in different contexts based on real case studies, and the upcoming challenges that micro-grid stakeholders will face (regulation, business models, technology). The electric production and distribution system, as the backbone of an increasingly urbanized and energy dependent society, is urged to shift towards a more resilient, efficient and environment-friendly infrastructure. Decentralisation of electricity production into densely populated areas is a promising opportunity to achieve this transition. A micro-grid enhances local production through clustering electricity producers and consumers within a delimited electricity network; it has the ability to disconnect from the main grid for a limited period of time, offering an energy security service to its customers during grid outages for example. However: The islanding capability is an inherent feature of the micro-grid concept that leads to a significant premium on electricity cost, especially in a system highly reliant on intermittent electricity production. In this case, a smart grid, with local energy production and no islanding capability, can be customized to meet relevant sustainability and cost savings goals at lower costs For industrials, urban micro-grids can be economically profitable in presence of high share of reliable energy production and thermal energy demand micro-grids face strong regulatory challenges that should be overcome for further development Whether islanding is or is not implemented into the system, end-user demand for a greener, more local, cheaper and more reliable energy, as well as additional services to the grid, are strong drivers for local production and consumption. In some specific cases

  13. Communication technologies in smart grid

    Directory of Open Access Journals (Sweden)

    Miladinović Nikola

    2013-01-01

    Full Text Available The role of communication technologies in Smart Grid lies in integration of large number of devices into one telecommunication system. This paper provides an overview of the technologies currently in use in electric power grid, that are not necessarily in compliance with the Smart Grid concept. Considering that the Smart Grid is open to the flow of information in all directions, it is necessary to provide reliability, protection and security of information.

  14. Smart grid security

    Energy Technology Data Exchange (ETDEWEB)

    Cuellar, Jorge (ed.) [Siemens AG, Muenchen (Germany). Corporate Technology

    2013-11-01

    The engineering, deployment and security of the future smart grid will be an enormous project requiring the consensus of many stakeholders with different views on the security and privacy requirements, not to mention methods and solutions. The fragmentation of research agendas and proposed approaches or solutions for securing the future smart grid becomes apparent observing the results from different projects, standards, committees, etc, in different countries. The different approaches and views of the papers in this collection also witness this fragmentation. This book contains the following papers: 1. IT Security Architecture Approaches for Smart Metering and Smart Grid. 2. Smart Grid Information Exchange - Securing the Smart Grid from the Ground. 3. A Tool Set for the Evaluation of Security and Reliability in Smart Grids. 4. A Holistic View of Security and Privacy Issues in Smart Grids. 5. Hardware Security for Device Authentication in the Smart Grid. 6. Maintaining Privacy in Data Rich Demand Response Applications. 7. Data Protection in a Cloud-Enabled Smart Grid. 8. Formal Analysis of a Privacy-Preserving Billing Protocol. 9. Privacy in Smart Metering Ecosystems. 10. Energy rate at home Leveraging ZigBee to Enable Smart Grid in Residential Environment.

  15. Innovative protection and control systems for a reliable and secure operation of electrical transmission systems; Innovative Schutz- und Leitsysteme zur zuverlaessigen und sicheren elektrischen Energieuebertragung

    Energy Technology Data Exchange (ETDEWEB)

    Mueller, Sven C.; Kubis, Adreas; Rehtanz, Christian [Technische Univ. Dortmund (Germany). Inst. fuer Energiesysteme, Energieeffizienz und Energiewirtschaft (ie3); Brato, Sebastian; Goetze, Juergen [Technische Univ. Dortmund (Germany). Arbeitsgebiet Datentechnik

    2012-07-01

    The integration of European electricity markets as well as the increasing power feed-in by renewable energy sources pose new challenges to the operation of electrical transmission systems. Modern protection and control systems based on wide-area information can substantially contribute to a reliable and secure system operation even against the background of future demands. In this paper research advances regarding new applications for wide-area monitoring, protection and control as well as an integrated simulation for power and ICT systems are presented that have been developed in the course of DFG research unit FOR1511 at TU Dortmund. (orig.)

  16. A Reliable Data Transmission Model for IEEE 802.15.4e Enabled Wireless Sensor Network under WiFi Interference.

    Science.gov (United States)

    Sahoo, Prasan Kumar; Pattanaik, Sudhir Ranjan; Wu, Shih-Lin

    2017-06-07

    The IEEE 802.15.4e standard proposes Medium Access Control (MAC) to support collision-free wireless channel access mechanisms for industrial, commercial and healthcare applications. However, unnecessary wastage of energy and bandwidth consumption occur due to inefficient backoff management and collisions. In this paper, a new channel access mechanism is designed for the buffer constraint sensor devices to reduce the packet drop rate, energy consumption and collisions. In order to avoid collision due to the hidden terminal problem, a new frame structure is designed for the data transmission. A new superframe structure is proposed to mitigate the problems due to WiFi and ZigBee interference. A modified superframe structure with a new retransmission opportunity for failure devices is proposed to reduce the collisions and retransmission delay with high reliability. Performance evaluation and validation of our scheme indicate that the packet drop rate, throughput, reliability, energy consumption and average delay of the nodes can be improved significantly.

  17. Smart grid

    International Nuclear Information System (INIS)

    Choi, Dong Bae

    2001-11-01

    This book describes press smart grid from basics to recent trend. It is divided into ten chapters, which deals with smart grid as green revolution in energy with introduction, history, the fields, application and needed technique for smart grid, Trend of smart grid in foreign such as a model business of smart grid in foreign, policy for smart grid in U.S.A, Trend of smart grid in domestic with international standard of smart grid and strategy and rood map, smart power grid as infrastructure of smart business with EMS development, SAS, SCADA, DAS and PQMS, smart grid for smart consumer, smart renewable like Desertec project, convergence IT with network and PLC, application of an electric car, smart electro service for realtime of electrical pricing system, arrangement of smart grid.

  18. How reduction of theta rhythm by medial septum inactivation may covary with disruption of entorhinal grid cell responses due to reduced cholinergic transmission

    Directory of Open Access Journals (Sweden)

    Praveen K. Pilly

    2013-10-01

    Full Text Available Oscillations in the coordinated firing of brain neurons have been proposed to play important roles in perception, cognition, attention, learning, navigation, and sensory-motor control. The network theta rhythm has been associated with properties of spatial navigation, as has the firing of entorhinal grid cells and hippocampal place cells. Two recent studies reduced the theta rhythm by inactivating the medial septum (MS and demonstrated a correlated reduction in the characteristic hexagonal spatial firing patterns of grid cells. These results, along with properties of intrinsic membrane potential oscillations (MPOs in slice preparations of entorhinal cells, have been interpreted to support oscillatory interference models of grid cell firing. The current article shows that an alternative self-organizing map model of grid cells can explain these data about intrinsic and network oscillations without invoking oscillatory interference. In particular, the adverse effects of MS inactivation on grid cells can be understood in terms of how the concomitant reduction in cholinergic inputs may increase the conductances of leak potassium (K+ and slow and medium after-hyperpolarization (sAHP and mAHP channels. This alternative model can also explain data that are problematic for oscillatory interference models, including how knockout of the HCN1 gene in mice, which flattens the dorsoventral gradient in MPO frequency and resonance frequency, does not affect the development of the grid cell dorsoventral gradient of spatial scales, and how hexagonal grid firing fields in bats can occur even in the absence of theta band modulation. These results demonstrate how models of grid cell self-organization can provide new insights into the relationship between brain learning, oscillatory dynamics, and navigational behaviors.

  19. Smart grid technologies in local electric grids

    Science.gov (United States)

    Lezhniuk, Petro D.; Pijarski, Paweł; Buslavets, Olga A.

    2017-08-01

    The research is devoted to the creation of favorable conditions for the integration of renewable sources of energy into electric grids, which were designed to be supplied from centralized generation at large electric power stations. Development of distributed generation in electric grids influences the conditions of their operation - conflict of interests arises. The possibility of optimal functioning of electric grids and renewable sources of energy, when complex criterion of the optimality is balance reliability of electric energy in local electric system and minimum losses of electric energy in it. Multilevel automated system for power flows control in electric grids by means of change of distributed generation of power is developed. Optimization of power flows is performed by local systems of automatic control of small hydropower stations and, if possible, solar power plants.

  20. Increasing the reliability of power semiconductors using DAB-substrates; Steigerung der Zuverlaessigkeit von Leistungshalbleitern durch Verwendung von DAB-Substraten

    Energy Technology Data Exchange (ETDEWEB)

    Grieger, F.; Lindemann, A. [Magdeburg Univ. (Germany); Boettge, B.; Klengel, S.; Petzold, M. [Fraunhofer IWM, Halle an der Saale (Germany)

    2012-07-01

    Besides power electronic loads, power electronic sources for decentralised generation have established in the grid. In the smart grid, the use of power electronics will even increase because of the introduction of more HVDC transmission lines and the necessity to control power flows. This paper deals with direct aluminium bonded (DAB) substrates which can serve as carriers of power electronic components with further increased reliability as desirable for long-term usage in the smart grid. (orig.)

  1. A Fast and Reliable Broadcast Service for LTE-Advanced Exploiting Multihop Device-to-Device Transmissions

    Directory of Open Access Journals (Sweden)

    Giovanni Nardini

    2017-11-01

    Full Text Available Several applications, from the Internet of Things for smart cities to those for vehicular networks, need fast and reliable proximity-based broadcast communications, i.e., the ability to reach all peers in a geographical neighborhood around the originator of a message, as well as ubiquitous connectivity. In this paper, we point out the inherent limitations of the LTE (Long-Term Evolution cellular network, which make it difficult, if possible at all, to engineer such a service using traditional infrastructure-based communications. We argue, instead, that network-controlled device-to-device (D2D communications, relayed in a multihop fashion, can efficiently support this service. To substantiate the above claim, we design a proximity-based broadcast service which exploits multihop D2D. We discuss the relevant issues both at the UE (User Equipment, which has to run applications, and within the network (i.e., at the eNodeBs, where suitable resource allocation schemes have to be enforced. We evaluate the performance of a multihop D2D broadcasting using system-level simulations, and demonstrate that it is fast, reliable and economical from a resource consumption standpoint.

  2. Reliability risks during the transition to competitive electricity markets

    International Nuclear Information System (INIS)

    Hughes, J.P.

    2005-01-01

    The Electricity Consumers Resource Council (ELCON) is a U.S. association representing industrial consumers of electricity, and is a long-standing advocate of competition in the electric power industry. However, because a reliable grid is necessary to support competitive wholesale markets, ELCON believes that the transmission system is an essential facility that must remain regulated. The initiatives discussed in this white paper represent significant steps that the National Electric Reliability Council (NERC) and the industry have taken to improve reliability in a competitive and restructured electric industry. Strategic manoeuvres of incumbent utilities to maintain market share were evaluated, as well as discrimination against potential competitors. It was suggested that, occasionally, indecisive federal policies have been taken advantage of by utilities. The unintended consequences of state restructuring policies that allow utilities to over-earn their revenue requirements were reviewed. NERC reliability standards will remain unenforceable until a new Electricity Reliability Organization has been certified. Flawed market designs and inadequate market power mitigation, as well as the financial distress of merchant generators, pose considerable risks. It was suggested that these risks could trigger transmission loading relief incidents, local outages or widespread outages. In the absence of mandatory reliability standards with penalties, and complementary market rules for mitigating generation and transmission market power, economic incentives will encourage other forms of opportunistic behavior that may be the root cause of other outages. Public concern regarding these risks to grid reliability may result in lost public support for competitive electricity markets. Proposed solutions include the certification of a new Electric Reliability Organization to establish and enforce mandatory reliability standards, and granting the Federal Energy Regulatory Commission

  3. Did Geomagnetic Activity Challenge Electric Power Reliability During Solar Cycle 23? Evidence from the PJM Regional Transmission Organization in North America

    Science.gov (United States)

    Forbes, Kevin F.; Cyr, Chris St

    2012-01-01

    During solar cycle 22, a very intense geomagnetic storm on 13 March 1989 contributed to the collapse of the Hydro-Quebec power system in Canada. This event clearly demonstrated that geomagnetic storms have the potential to lead to blackouts. This paper addresses whether geomagnetic activity challenged power system reliability during solar cycle 23. Operations by PJM Interconnection, LLC (hereafter PJM), a regional transmission organization in North America, are examined over the period 1 April 2002 through 30 April 2004. During this time PJM coordinated the movement of wholesale electricity in all or parts of Delaware, Maryland, New Jersey, Ohio, Pennsylvania, Virginia, West Virginia, and the District of Columbia in the United States. We examine the relationship between a proxy of geomagnetically induced currents (GICs) and a metric of challenged reliability. In this study, GICs are proxied using magnetometer data from a geomagnetic observatory located just outside the PJM control area. The metric of challenged reliability is the incidence of out-of-economic-merit order dispatching due to adverse reactive power conditions. The statistical methods employed make it possible to disentangle the effects of GICs on power system operations from purely terrestrial factors. The results of the analysis indicate that geomagnetic activity can significantly increase the likelihood that the system operator will dispatch generating units based on system stability considerations rather than economic merit.

  4. Twelve Principles for Green Energy Storage in Grid Applications.

    Science.gov (United States)

    Arbabzadeh, Maryam; Johnson, Jeremiah X; Keoleian, Gregory A; Rasmussen, Paul G; Thompson, Levi T

    2016-01-19

    The introduction of energy storage technologies to the grid could enable greater integration of renewables, improve system resilience and reliability, and offer cost effective alternatives to transmission and distribution upgrades. The integration of energy storage systems into the electrical grid can lead to different environmental outcomes based on the grid application, the existing generation mix, and the demand. Given this complexity, a framework is needed to systematically inform design and technology selection about the environmental impacts that emerge when considering energy storage options to improve sustainability performance of the grid. To achieve this, 12 fundamental principles specific to the design and grid application of energy storage systems are developed to inform policy makers, designers, and operators. The principles are grouped into three categories: (1) system integration for grid applications, (2) the maintenance and operation of energy storage, and (3) the design of energy storage systems. We illustrate the application of each principle through examples published in the academic literature, illustrative calculations, and a case study with an off-grid application of vanadium redox flow batteries (VRFBs). In addition, trade-offs that can emerge between principles are highlighted.

  5. λ-Selection Strategy in C+L Band 1-Pbit/s (448 WDM/19-Core/128 Gbit/s/channel) Flex-Grid Space Division Multiplexed Transmission

    DEFF Research Database (Denmark)

    Asif, Rameez; Ye, Feihong; Morioka, Toshio

    2015-01-01

    In this paper, an inter-core crosstalk based wavelength selection scheme has been proposed for flex-grid superchannels in space division multiplexed transmission. The two λ-selection strategies are categorized as: (a) aligned wavelength super-channels (Aλ-SCs), where all super-channels are placed...... at same λ in all the cores and (b) interleaved wavelength super-channels (Iλ-SCs), where all super-channels are placed at different λ in all the neighboring cores. It is depicted that system performance is improved for DP-16QAM channels in 1-Pbit/s (448 WDM/19 Core/128 Gbit/s/channel) 60 km fiber link...

  6. Why transmission is still the critical link

    Energy Technology Data Exchange (ETDEWEB)

    Flynn, V. [ESBI Alberta Ltd., Calgary, AB (Canada)

    2002-07-01

    This paper describes the important role that transmission plays in the competitive electric power industry in North America and around the world. In the past several years the transmission sector has experienced a lack of investment, congestion on transmission networks, merchant transmission development, and the creation of Regional Transmission Organizations (RTOs). The transmission grid is central to the reliability of the entire electricity system. It also plays a vital role in promoting efficient markets in electricity. The author discusses the consequences of inadequate investment to this critical link within the power industry. He also discusses how much investment is needed, and the challenges and solutions to building an infrastructure. The integrated electric system and the electricity industry in Alberta is very different from those in the United Sates, but the issues facing the industry are the same. The challenge is the sharp increase in the number of system access requests by new generators combined with the difficulties in siting new transmission lines. There are 17,000 km of transmission lines in Alberta, at voltages ranging from 69 kV to 500 kV. There are also connections between neighbouring provinces. The transmission lines have a value of C$1.5 billion. Since there have been no major additions to the transmission grid since the mid-1980s, significant investments in the coming years will have a disproportionate impact on the cost of transmission. Two merchant transmission projects have been proposed. The first will enhance transfer of electricity between Alberta and Saskatchewan by 150 MW, and the second is proposed to be a 1,500 MW, 500 kV DC line from the Fort McMurray area to the Pacific Northwest. 5 figs.

  7. Multi-agent approach for power system in a smart grid protection context

    DEFF Research Database (Denmark)

    Abedini, Reza; Pinto, Tiago; Morais, Hugo

    2013-01-01

    electricity markets and in the other hand with increasing penetration of Distributed Generation (DG) because of environment issues and diminishing in fossil fuel reserves and its price growth, made microgrid more attractive. Micro grids are considers as partial of SmartGrid system to accommodate DGs as well......With increasing penetration of electricity application in society and the need of majority of appliance to electricity, high level of reliability becomes more essential; in one hand with deregulation of electricity market in production, transmission and distribution and emerge of competitive...... proposes a new approach for protection in a Microgrid environment as a part of SmartGrid: Multi-agent system to Protections Coordination (MAS-ProteC) which integrated in MASGriP (Multi-Agent Smart Grid Platform), providing protection services within network operation in SmartGrid in electricity market...

  8. Designing for Wide-Area Situation Awareness in Future Power Grid Operations

    Science.gov (United States)

    Tran, Fiona F.

    Power grid operation uncertainty and complexity continue to increase with the rise of electricity market deregulation, renewable generation, and interconnectedness between multiple jurisdictions. Human operators need appropriate wide-area visualizations to help them monitor system status to ensure reliable operation of the interconnected power grid. We observed transmission operations at a control centre, conducted critical incident interviews, and led focus group sessions with operators. The results informed a Work Domain Analysis of power grid operations, which in turn informed an Ecological Interface Design concept for wide-area monitoring. I validated design concepts through tabletop discussions and a usability evaluation with operators, earning a mean System Usability Scale score of 77 out of 90. The design concepts aim to support an operator's complete and accurate understanding of the power grid state, which operators increasingly require due to the critical nature of power grid infrastructure and growing sources of system uncertainty.

  9. The eGo grid model: An open source approach towards a model of German high and extra-high voltage power grids

    Science.gov (United States)

    Mueller, Ulf Philipp; Wienholt, Lukas; Kleinhans, David; Cussmann, Ilka; Bunke, Wolf-Dieter; Pleßmann, Guido; Wendiggensen, Jochen

    2018-02-01

    There are several power grid modelling approaches suitable for simulations in the field of power grid planning. The restrictive policies of grid operators, regulators and research institutes concerning their original data and models lead to an increased interest in open source approaches of grid models based on open data. By including all voltage levels between 60 kV (high voltage) and 380kV (extra high voltage), we dissolve the common distinction between transmission and distribution grid in energy system models and utilize a single, integrated model instead. An open data set for primarily Germany, which can be used for non-linear, linear and linear-optimal power flow methods, was developed. This data set consists of an electrically parameterised grid topology as well as allocated generation and demand characteristics for present and future scenarios at high spatial and temporal resolution. The usability of the grid model was demonstrated by the performance of exemplary power flow optimizations. Based on a marginal cost driven power plant dispatch, being subject to grid restrictions, congested power lines were identified. Continuous validation of the model is nescessary in order to reliably model storage and grid expansion in progressing research.

  10. Intelligent Control for a DC Micro-Grid System

    DEFF Research Database (Denmark)

    Martino, Michele; Quiñones, Yamshid Farhat; Raboni, Pietro

    2012-01-01

    This paper presents the dynamic response of a DC–micro-grid (DC-MG) controlled in master-slave mode. The benefits of the micro-grids (MGs) are the low cost in terms of power electronics converters and the high reliability and quality, even in case of loss connection to the transmission system. A ...... the units, especially in case of variable weather conditions with different DC loads. Thus the voltage level of the system and the power flow are shown, out of a detailed description of the power electronic interfaces featuring the distributed generators (DGs).......This paper presents the dynamic response of a DC–micro-grid (DC-MG) controlled in master-slave mode. The benefits of the micro-grids (MGs) are the low cost in terms of power electronics converters and the high reliability and quality, even in case of loss connection to the transmission system. A DC......-MG in fact can survive in standalone mode if properly managed. The considered system is made by a photovoltaic array (PV), a wind turbine (WT), a gas engine (GE) and an energy storage system (ESS). The DC-MG behavior is analyzed in different scenarios to demonstrate the efficacy of the control for all...

  11. Securing the smart grid information exchange

    Energy Technology Data Exchange (ETDEWEB)

    Fries, Steffen; Falk, Rainer [Siemens AG, Corporate Technology, Muenchen (Germany)

    2012-07-01

    The smart grid is based on information exchange between various stakeholders using open communication technologies, to control the physical electric grid through the information grid. Protection against cyber attacks is essential to ensure a reliable operation of the smart grid. This challenge is addressed by various regulatory, standardization, and research activities. After giving an overview of the security demand of a smart grid, existing and appearing standardization activities are described. (orig.)

  12. Smart Grid Research: Control Systems - IEEE Vision for Smart Grid Controls

    DEFF Research Database (Denmark)

    Aho, Jacob; Arnold, George; Buckspan, Andrew

    This document highlights the role of control systems in the evolution of the Smart Grid. It includes an overview of research investigations that are needed for renewable integration, reliability, self-healing, energy efficiency, and resilience to physical and cyber attacks. These investigations...... are encapsulated in several loci of control including: new methodologies for transmission, distribution, and renewable energy, and storage; new roles in emerging topics such as electricity markets, demand-response, microgrids, and virtual power plants; and new solutions for efficiency, heating and cooling...

  13. Regional Transmission Projects: Finding Solutions

    Energy Technology Data Exchange (ETDEWEB)

    The Keystone Center

    2005-06-15

    The Keystone Center convened and facilitated a year-long Dialogue on "Regional Transmission Projects: Finding Solutions" to develop recommendations that will help address the difficult and contentious issues related to expansions of regional electric transmission systems that are needed for reliable and economic transmission of power within and across regions. This effort brought together a cross-section of affected stakeholders and thought leaders to address the problem with the collective wisdom of their experience and interests. Transmission owners sat at the table with consumer advocates and environmental organizations. Representatives from regional transmission organizations exchanged ideas with state and federal regulators. Generation developers explored common interests with public power suppliers. Together, the Dialogue participants developed consensus solutions about how to begin unraveling some of the more intractable issues surrounding identification of need, allocation of costs, and reaching consensus on siting issues that can frustrate the development of regional transmission infrastructure. The recommendations fall into three broad categories: 1. Recommendations on appropriate institutional arrangements and processes for achieving regional consensus on the need for new or expanded transmission infrastructure 2. Recommendations on the process for siting of transmission lines 3. Recommendations on the tools needed to support regional planning, cost allocation, and siting efforts. List of Dialogue participants: List of Dialogue Participants: American Electric Power American Transmission Company American Wind Energy Association California ISO Calpine Corporation Cinergy Edison Electric Institute Environmental Defense Federal Energy Regulatory Commission Great River Energy International Transmission Company ISO-New England Iowa Public Utility Board Kanner & Associates Midwest ISO National Association of Regulatory Utility Commissioners National Association

  14. Transmission planning in a deregulated environment

    DEFF Research Database (Denmark)

    Xu, Zhao

    2006-01-01

    The worldwide trend for the deregulation of the electricity generation and transmission industries has led to dramatic changes in system operation and planning procedures. The optimum approach to transmission-expansion planning in a deregulated environment is an open problem especially when the r...... electricity market grid are performed. In addition, the proposed method is compared with a traditional planning method to further verify its effectiveness....... the responsibilities of the organisations carrying out the planning work need to be addressed. To date there is a consensus that the system operator and network manager perform the expansion planning work in a centralised way. However, with an increasing input from the electricity market, the objectives, constraints...... and approaches toward transmission planning should be carefully designed to ensure system reliability as well as meeting the market requirements. A market-oriented approach for transmission planning in a deregulated environment is proposed. Case studies using the IEEE 14-bus system and the Australian national...

  15. The Grid

    CERN Document Server

    Klotz, Wolf-Dieter

    2005-01-01

    Grid technology is widely emerging. Grid computing, most simply stated, is distributed computing taken to the next evolutionary level. The goal is to create the illusion of a simple, robust yet large and powerful self managing virtual computer out of a large collection of connected heterogeneous systems sharing various combinations of resources. This talk will give a short history how, out of lessons learned from the Internet, the vision of Grids was born. Then the extensible anatomy of a Grid architecture will be discussed. The talk will end by presenting a selection of major Grid projects in Europe and US and if time permits a short on-line demonstration.

  16. Hybrid AC-High Voltage DC Grid Stability and Controls

    Science.gov (United States)

    Yu, Jicheng

    The growth of energy demands in recent years has been increasing faster than the expansion of transmission facility construction. This tendency cooperating with the continuous investing on the renewable energy resources drives the research, development, and construction of HVDC projects to create a more reliable, affordable, and environmentally friendly power grid. Constructing the hybrid AC-HVDC grid is a significant move in the development of the HVDC techniques; the form of dc system is evolving from the point-to-point stand-alone dc links to the embedded HVDC system and the multi-terminal HVDC (MTDC) system. The MTDC is a solution for the renewable energy interconnections, and the MTDC grids can improve the power system reliability, flexibility in economic dispatches, and converter/cable utilizing efficiencies. The dissertation reviews the HVDC technologies, discusses the stability issues regarding the ac and HVDC connections, proposes a novel power oscillation control strategy to improve system stability, and develops a nonlinear voltage droop control strategy for the MTDC grid. To verify the effectiveness the proposed power oscillation control strategy, a long distance paralleled AC-HVDC transmission test system is employed. Based on the PSCAD/EMTDC platform simulation results, the proposed power oscillation control strategy can improve the system dynamic performance and attenuate the power oscillations effectively. To validate the nonlinear voltage droop control strategy, three droop controls schemes are designed according to the proposed nonlinear voltage droop control design procedures. These control schemes are tested in a hybrid AC-MTDC system. The hybrid AC-MTDC system, which is first proposed in this dissertation, consists of two ac grids, two wind farms and a five-terminal HVDC grid connecting them. Simulation studies are performed in the PSCAD/EMTDC platform. According to the simulation results, all the three design schemes have their unique salient

  17. How to Obtain a 100% Reliable Grid with Clean, Renewable Wind, Water, and Solar Providing 100% of all Raw Energy for All Purposes

    Science.gov (United States)

    Jacobson, M. Z.; Delucchi, M. A.; Cameron, M. A.; Frew, B. A.

    2016-12-01

    The greatest concern facing the large-scale integration of wind, water, and solar (WWS) into a power grid is the high cost of avoiding load loss caused by WWS variability and uncertainty. This talk discusses the recent development of a new grid integration model to address this issue. The model finds low-cost, no-load-loss, non-unique solutions to this problem upon electrification of all U.S. energy sectors (electricity, transportation, heating/cooling, and industry) while accounting for wind and solar time-series data from a 3-D global weather model that simulates extreme events and competition among wind turbines for available kinetic energy. Solutions are obtained by prioritizing storage for heat (in soil and water); cold (in ice and water); and electricity (in phase-change materials, pumped hydro, hydropower, and hydrogen); and using demand response. No natural gas, biofuels, or stationary batteries are needed. The resulting 2050-2055 U.S. electricity social cost for a full system is much less than for fossil fuels. These results hold for many conditions, suggesting that low-cost, stable 100% WWS systems should work many places worldwide. The paper this talk is based on was published in PNAS, 112, 15,060-15,065, 2015, doi:10.1073/pnas.1510028112.

  18. Smart Grids and Distributed Generation

    Directory of Open Access Journals (Sweden)

    Dorin BICĂ

    2018-06-01

    Full Text Available This paper describes the main characteristics of Smart Grids and distributed generation. Smart Grids can be defined as a modernization of the power system so it monitors, protects and automatically optimizes the operation of its interconnected elements (power plants, transmission and distribution system, industrial and residential loads. Distributed generation (DG refers to the production of electricity near the consumption place using renewable energy sources. A load flow analysis is performed for the IEEE14 system in which a DG source (a 5MW wind turbine is added that is on-grid or off-grid. The power losses are determined for these two cases.

  19. Transmission assets investment timing using net present value curves

    International Nuclear Information System (INIS)

    Garcia, Reinaldo C.; Contreras, Javier; Correia, Pedro F.; Munoz, Jose I.

    2010-01-01

    Improvement and expansion of the transmission grid is still an unresolved issue in the new competitive environment. In current electricity markets, transmission lines have become assets that need financial instruments for investors who wish to ensure steady long-term returns and to withstand short-term market volatility. The timing and the combination of new transmission investments is key to analyze their long-term effects. This paper presents the concept of net present value (NPV) curve to estimate the best investment time for the investor, where the curve is constructed by calculating the NPVs resulting from the investment in successive years. A specific contract model based on financial transmission rights (FTR) is used for the NPV evaluation of transmission assets, and the stochastic properties of all variables related to the investment market structure are considered. The model is applied to the IEEE 24-bus Reliability Test System (RTS) showing the approach capabilities as a decision-aid tool for transmission investors.

  20. Simulation model of the transmission grid for a large offshore windfarm, used in education and research st the Technical University of Denmark

    Energy Technology Data Exchange (ETDEWEB)

    Akhmatov, V.; Nielsen, A.H.

    2006-05-15

    A small test software-model for the transmission system containing a number of central power plants, consumption centres, local wind turbines and a large offshore windfarm has been implemented in the simulation tool Powerfactory (DigSilent). This model demonstrates the interaction between electricity-producing wind turbines and a realistic transmission system, for instance short-term voltage stability and ride-through capability of the wind turbines. The model has been developed by the Danish Transmission System Operator Energinet.dk for use by the Centre for Electric Technology (CET) at Technical University of Denmark. It has been applied in the education of electric power engineers and in research projects. An example of its use is presented. [Author].

  1. Power system reliability memento; Memento de la surete du systeme electrique

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2002-07-01

    The reliability memento of the French power system (national power transmission grid) is an educational document which purpose is to point out the role of each one as regards power system operating reliability. This memento was first published in 1999. Extensive changes have taken place since then. The new 2002 edition shows that system operating reliability is as an important subject as ever: 1 - foreword; 2 - system reliability: the basics; 3 - equipment measures taken in order to guarantee the reliability of the system; 4 - organisational and human measures taken to guarantee the reliability of the system; appendix 1 - system operation: basic concepts; appendix 2 - guiding principles governing the reliability of the power system; appendix 3 - international associations of transmission system operators; appendix 4 - description of major incidents.

  2. Current Grid operation and future role of the Grid

    Science.gov (United States)

    Smirnova, O.

    2012-12-01

    Grid-like technologies and approaches became an integral part of HEP experiments. Some other scientific communities also use similar technologies for data-intensive computations. The distinct feature of Grid computing is the ability to federate heterogeneous resources of different ownership into a seamless infrastructure, accessible via a single log-on. Like other infrastructures of similar nature, Grid functioning requires not only technologically sound basis, but also reliable operation procedures, monitoring and accounting. The two aspects, technological and operational, are closely related: weaker is the technology, more burden is on operations, and other way around. As of today, Grid technologies are still evolving: at CERN alone, every LHC experiment uses an own Grid-like system. This inevitably creates a heavy load on operations. Infrastructure maintenance, monitoring and incident response are done on several levels, from local system administrators to large international organisations, involving massive human effort worldwide. The necessity to commit substantial resources is one of the obstacles faced by smaller research communities when moving computing to the Grid. Moreover, most current Grid solutions were developed under significant influence of HEP use cases, and thus need additional effort to adapt them to other applications. Reluctance of many non-HEP researchers to use Grid negatively affects the outlook for national Grid organisations, which strive to provide multi-science services. We started from the situation where Grid organisations were fused with HEP laboratories and national HEP research programmes; we hope to move towards the world where Grid will ultimately reach the status of generic public computing and storage service provider and permanent national and international Grid infrastructures will be established. How far will we be able to advance along this path, depends on us. If no standardisation and convergence efforts will take place

  3. Current Grid operation and future role of the Grid

    International Nuclear Information System (INIS)

    Smirnova, O

    2012-01-01

    Grid-like technologies and approaches became an integral part of HEP experiments. Some other scientific communities also use similar technologies for data-intensive computations. The distinct feature of Grid computing is the ability to federate heterogeneous resources of different ownership into a seamless infrastructure, accessible via a single log-on. Like other infrastructures of similar nature, Grid functioning requires not only technologically sound basis, but also reliable operation procedures, monitoring and accounting. The two aspects, technological and operational, are closely related: weaker is the technology, more burden is on operations, and other way around. As of today, Grid technologies are still evolving: at CERN alone, every LHC experiment uses an own Grid-like system. This inevitably creates a heavy load on operations. Infrastructure maintenance, monitoring and incident response are done on several levels, from local system administrators to large international organisations, involving massive human effort worldwide. The necessity to commit substantial resources is one of the obstacles faced by smaller research communities when moving computing to the Grid. Moreover, most current Grid solutions were developed under significant influence of HEP use cases, and thus need additional effort to adapt them to other applications. Reluctance of many non-HEP researchers to use Grid negatively affects the outlook for national Grid organisations, which strive to provide multi-science services. We started from the situation where Grid organisations were fused with HEP laboratories and national HEP research programmes; we hope to move towards the world where Grid will ultimately reach the status of generic public computing and storage service provider and permanent national and international Grid infrastructures will be established. How far will we be able to advance along this path, depends on us. If no standardisation and convergence efforts will take place

  4. Power transformer reliability modelling

    NARCIS (Netherlands)

    Schijndel, van A.

    2010-01-01

    Problem description Electrical power grids serve to transport and distribute electrical power with high reliability and availability at acceptable costs and risks. These grids play a crucial though preferably invisible role in supplying sufficient power in a convenient form. Today’s society has

  5. Providing reliable energy in a time of constraints : a North American concern

    International Nuclear Information System (INIS)

    Egan, T.; Turk, E.

    2008-04-01

    The reliability of the North American electricity grid was discussed. Government initiatives designed to control carbon dioxide (CO 2 ) and other emissions in some regions of Canada may lead to electricity supply constraints in other regions. A lack of investment in transmission infrastructure has resulted in constraints within the North American transmission grid, and the growth of smaller projects is now raising concerns about transmission capacity. Labour supply shortages in the electricity industry are also creating concerns about the long-term security of the electricity market. Measures to address constraints must be considered in the current context of the North American electricity system. The extensive transmission interconnects and integration between the United States and Canada will provide a framework for greater trade and market opportunities between the 2 countries. Coordinated actions and increased integration will enable Canada and the United States to increase the reliability of electricity supply. However, both countries must work cooperatively to increase generation supply using both mature and emerging technologies. The cross-border transmission grid must be enhanced by increasing transmission capacity as well as by implementing new reliability rules, building new infrastructure, and ensuring infrastructure protection. Barriers to cross-border electricity trade must be identified and avoided. Demand-side and energy efficiency measures must also be implemented. It was concluded that both countries must focus on developing strategies for addressing the environmental concerns related to electricity production. 6 figs

  6. Non-Pilot Protection of the HVDC Grid

    Science.gov (United States)

    Badrkhani Ajaei, Firouz

    This thesis develops a non-pilot protection system for the next generation power transmission system, the High-Voltage Direct Current (HVDC) grid. The HVDC grid protection system is required to be (i) adequately fast to prevent damages and/or converter blocking and (ii) reliable to minimize the impacts of faults. This study is mainly focused on the Modular Multilevel Converter (MMC) -based HVDC grid since the MMC is considered as the building block of the future HVDC systems. The studies reported in this thesis include (i) developing an enhanced equivalent model of the MMC to enable accurate representation of its DC-side fault response, (ii) developing a realistic HVDC-AC test system that includes a five-terminal MMC-based HVDC grid embedded in a large interconnected AC network, (iii) investigating the transient response of the developed test system to AC-side and DC-side disturbances in order to determine the HVDC grid protection requirements, (iv) investigating the fault surge propagation in the HVDC grid to determine the impacts of the DC-side fault location on the measured signals at each relay location, (v) designing a protection algorithm that detects and locates DC-side faults reliably and sufficiently fast to prevent relay malfunction and unnecessary blocking of the converters, and (vi) performing hardware-in-the-loop tests on the designed relay to verify its potential to be implemented in hardware. The results of the off-line time domain transients studies in the PSCAD software platform and the real-time hardware-in-the-loop tests using an enhanced version of the RTDS platform indicate that the developed HVDC grid relay meets all technical requirements including speed, dependability, security, selectivity, and robustness. Moreover, the developed protection algorithm does not impose considerable computational burden on the hardware.

  7. Modeling and control of sustainable power systems. Towards smarter and greener electric grids

    Energy Technology Data Exchange (ETDEWEB)

    Lingfeng Wang (ed.) [Toledo Univ., OH (United States). Electrical Engineering and Computer Science Dept.

    2012-07-01

    The concept of the smart grid promises the world an efficient and intelligent approach of managing energy production, transportation, and consumption by incorporating intelligence, efficiency, and optimality into the power grid. Both energy providers and consumers can take advantage of the convenience, reliability, and energy savings achieved by real-time and intelligent energy management. To this end, the current power grid is experiencing drastic changes and upgrades. For instance, more significant green energy resources such as wind power and solar power are being integrated into the power grid, and higher energy storage capacity is being installed in order to mitigate the intermittency issues brought about by the variable energy resources. At the same time, novel power electronics technologies and operating strategies are being invented and adopted. For instance, Flexible AC transmission systems and phasor measurement units are two promising technologies for improving the power system reliability and power quality. Demand side management will enable the customers to manage the power loads in an active fashion. As a result, modeling and control of modern power grids pose great challenges due to the adoption of new smart grid technologies. In this book, chapters regarding representative applications of smart grid technologies written by world-renowned experts are included, which explain in detail various innovative modeling and control methods. (orig.)

  8. Reliability of techniques used in the diagnosis of canine visceral leishmaniasis by the national control program in Brazil: A survey in an area of recent transmission.

    Science.gov (United States)

    Belo, Vinícius Silva; Gregório, Eliana Aparecida; Teixeira-Neto, Rafael Gonçalves; da Rocha Lima, Ana Cristina Vianna Mariano; Pereira, Agnes Antônia Sampaio; Marcelino, Andreza Pain; Paz, Gustavo Fontes; da Silva, Eduardo Sérgio

    2017-10-01

    One of the key components of the Brazilian Program for the Control of Visceral Leishmaniasis (PCLV) is the euthanasia of Leishmania-infected canine reservoirs, the detection of which depends on a screening procedure involving a Dual Path Platform ® (DPP) immunoassay and a confirmatory enzyme-linked immunosorbent assay (ELISA). The aims of the present study were to evaluate the reliability of these techniques in a region of recent transmission of canine VL, to follow up the seroconversion 3-4 months after the initial diagnosis of DPP reactive but ELISA indeterminate or non-reactive dogs, and to identify the species of Leishmania in circulation in the area. Each animal was submitted to DPP under field conditions, performed by municipal health workers using peripheral blood (DPP-field), to DPP under laboratory conditions using serum (DPP-lab) and to ELISA using serum. The agreements between the tests were determined using McNemar's χ 2 test, Cohen's kappa coefficient (k) at the 95% confidence interval and prevalence-adjusted bias-adjusted kappa (PABAK). Of the 1130 dogs examined, 74.2% were non-reactive in all three tests applied. Based on the PCLV positive-infection criterion, seroprevalence was 8.9% (101/1130) with 83.2% (84/101) of infected animals showing reactivity in all three tests while 7.8% (8/101) were reactive in DPP-field and ELISA and 8.9% (9/101) in DPP-lab and ELISA. The proportions of disagreements were substantial in all comparisons. Inter-rater reliability between DPP-field and ELISA (k=0.55; PABAK=0.78) and DPP-lab and ELISA (k=0.59; PABAK=0.81) were considered moderate, while that between DPP-field and DPP-lab (k=0.61; PABAK=0.79) was classified as marginally good. The proportion of seroconversions in DPP reactive animals that were initially ELISA indeterminate was significantly higher than in those that were DPP reactive but initially ELISA non-reactive. Restriction fragment length polymorphism analysis revealed the presence of Leishmania

  9. Planning and designing smart grids: philosophical considerations

    NARCIS (Netherlands)

    Ribeiro, P.F.; Polinder, H.; Verkerk, M.J.

    2012-01-01

    The electric power grid is a crucial part of societal infrastructure and needs constant attention to maintain its performance and reliability. European grid project investments are currently valued at over 5 billion Euros and are estimated to reach 56 billion by 2020 [2]. Successful smart grid

  10. Transmission electron microscopy study for investigating high-temperature reliability of Ti10W90-based and Ta-based diffusion barriers up to 600 C

    International Nuclear Information System (INIS)

    Budhiman, Nando; Schuermann, Ulrich; Kienle, Lorenz; Jensen, Bjoern; Chemnitz, Steffen; Wagner, Bernhard

    2016-01-01

    Abstractauthoren Transmission electron microscopy (TEM) analysis, including energy dispersive X-ray (EDX) (elemental mapping, line, and point measurements) and energy filtered TEM (EFTEM) methods, is applied to investigate the high temperature reliability, especially material diffusion, of two types of diffusion barriers: titanium-tungsten-based (Ti 10 W 90 -based) and tantalum-based (Ta-based), with nickel (Ni) layer on top. Both barriers were deposited as a form of stacked layers on sili-con (Si) wafers using the physical vapor deposition (PVD) technique. TEM analysis is performed on both barriers before and after annealing (at 600 C for 24 h inside a vacuum chamber). No diffusion of material into the Si substrate as observed. Additionally, only diffusion between the Ni and adjoining Ti 10 W 90 layers, and between Ni and adjoining Ta layers in the Ti 10 W 90 -based and Ta-based barriers, respectively, are observed due to annealing. (copyright 2015 WILEY-VCH Verlag GmbH and Co. KGaA, Weinheim)

  11. Ice Cover Prediction of a Power Grid Transmission Line Based on Two-Stage Data Processing and Adaptive Support Vector Machine Optimized by Genetic Tabu Search

    OpenAIRE

    Xiaomin Xu; Dongxiao Niu; Lihui Zhang; Yongli Wang; Keke Wang

    2017-01-01

    With the increase in energy demand, extreme climates have gained increasing attention. Ice disasters on transmission lines can cause gap discharge and icing flashover electrical failures, which can lead to mechanical failure of the tower, conductor, and insulators, causing significant harm to people’s daily life and work. To address this challenge, an intelligent combinational model is proposed based on improved empirical mode decomposition and support vector machine for short-term forecastin...

  12. Grid Support in Large Scale PV Power Plants using Active Power Reserves

    DEFF Research Database (Denmark)

    Craciun, Bogdan-Ionut

    to validate the performance of the frequency support functions, a flexible grid model with IEEE 12 bus system characteristics has been developed and implemented in RTDS. A power hardware-in-the-loop (PHIL) system composed by 20 kW plant (2 x 10 kW inverters and PV linear simulator) and grid simulator (RTDS......Photovoltaic (PV) systems are in the 3rd place in the renewable energy market, after hydro and wind power. The increased penetration of PV within the electrical power system has led to stability issues of the entire grid in terms of its reliability, availability and security of the supply....... As a consequence, Large scale PV Power Plants (LPVPPs) operating in Maximum Power Point (MPP) are not supporting the electrical network, since several grid triggering events or the increased number of downward regulation procedures have forced European Network of Transmission System Operators for Electricity...

  13. The smart alternative : securing and strengthening our nation's vulnerable electric grid

    International Nuclear Information System (INIS)

    Nahigian, K.R.

    2008-01-01

    This article explained the concept of the next generation of electrical power grids known as the Smart Grid, which allows the possibility to either reallocate electricity during times of crisis or peak demand or prevent power disruptions through proactive diagnosis. The author examined the security, economic and environmental benefits of implementing the Smart Grid during a time of rising energy prices and desire for energy independence. The Smart Grid uses advanced communications and information technologies to create a modern transmission and distribution network that facilitates the integration of alternative energy sources such as wind and solar power, as well as energy-efficient technologies such as plug-in hybrid vehicles. The author emphasized that implementing the Smart Grid grid is also vital to strengthening America's resilience and security since a more robust energy infrastructure will ensure the reliable flow of electricity in the event of a crisis. In addition to promoting energy efficiency, the Smart Grid offers economic benefits, such as reducing the billions of dollars lost each year by American businesses on power outages. A Smart Grid could also open lucrative new markets for smart technologies. 2 figs

  14. Grid Integration Webinars | Energy Systems Integration Facility | NREL

    Science.gov (United States)

    Grid Integration Webinars Grid Integration Webinars Watch presentations from NREL analysts on various topics related to grid integration. Wind Curtailment and the Value of Transmission under a 2050 renewable curtailment under these high wind scenarios. Text Version Grid Integration Webinar: Exploring

  15. Superiority of the practical method to theory: Diagnose of service life of ropes in overhead transmission grids; Praktische Methode der Theorie ueberlegen: Diagnose der Lebensdauer von Freileitungsseilen

    Energy Technology Data Exchange (ETDEWEB)

    Brueckner, W.F.

    2005-02-07

    In designing overhead transmission lines, cable tension is of prior importance. High tension means shorter life unless vibration dampers are installed. On the other hand, higher tension will reduce the overall cost to an optimum level. The author presents experience and measured vibration sensitivities. (orig.) [German] Beim Entwurf von Freileitungen ist die Zugspannung der Seile von besonderer Bedeutung. Erhoehte Seilzugspannungen verringern die Lebensdauer der Seile, soweit die Schwingungsgefahr nicht durch geeignete Schwingungsdaempfer vermieden wird. Mit erhoehter Seilzugspannung verringern sich auch die Kosten der gesamten Freileitung bis zur optimalen Grenze, die von den Kosten je km fuer verschiedene Spannweiten zu bestimmen ist. Der Verfasser beschreibt Erfahrungen ueber die gemessene Schwingungsgefaehrdung der Seile. (orig.)

  16. Safety of the French power grid: audit and annual reporting; Surete du systeme electrique francais: audit et reporting annuel

    Energy Technology Data Exchange (ETDEWEB)

    Tesseron, J.M. [Reseau de Transport d' Electricite (RTE), 92 - Paris la Defense (France)

    2006-09-15

    Power system reliability is at the core of the responsibilities entrusted to RTE, the French transmission system operator. Considering the particularly important issue of reliability, RTE's management has set up an entity which reports to it directly on this subject. The two main activities of this entity involve drawing up the annual system reliability report and carrying out audits devoted to reliability. After going over the principles governing the control of system reliability in France, the document presents the experience acquired since 2000. The principles underlying the drafting of the annual reliability report and the method for scheduling and performing the reliability audits are first set out. The author then goes on to present how these principles are applied to two reliability audits, one carried out on voltage control and the other on the control of the clearance time of short-circuits affecting the 400 kV grid. (author)

  17. Grid Security

    CERN Multimedia

    CERN. Geneva

    2004-01-01

    The aim of Grid computing is to enable the easy and open sharing of resources between large and highly distributed communities of scientists and institutes across many independent administrative domains. Convincing site security officers and computer centre managers to allow this to happen in view of today's ever-increasing Internet security problems is a major challenge. Convincing users and application developers to take security seriously is equally difficult. This paper will describe the main Grid security issues, both in terms of technology and policy, that have been tackled over recent years in LCG and related Grid projects. Achievements to date will be described and opportunities for future improvements will be addressed.

  18. Smart Grid Integration Laboratory

    Energy Technology Data Exchange (ETDEWEB)

    Troxell, Wade [Colorado State Univ., Fort Collins, CO (United States)

    2011-12-22

    The initial federal funding for the Colorado State University Smart Grid Integration Laboratory is through a Congressionally Directed Project (CDP), DE-OE0000070 Smart Grid Integration Laboratory. The original program requested in three one-year increments for staff acquisition, curriculum development, and instrumentation all which will benefit the Laboratory. This report focuses on the initial phase of staff acquisition which was directed and administered by DOE NETL/ West Virginia under Project Officer Tom George. Using this CDP funding, we have developed the leadership and intellectual capacity for the SGIC. This was accomplished by investing (hiring) a core team of Smart Grid Systems engineering faculty focused on education, research, and innovation of a secure and smart grid infrastructure. The Smart Grid Integration Laboratory will be housed with the separately funded Integrid Laboratory as part of CSU's overall Smart Grid Integration Center (SGIC). The period of performance of this grant was 10/1/2009 to 9/30/2011 which included one no cost extension due to time delays in faculty hiring. The Smart Grid Integration Laboratory's focus is to build foundations to help graduate and undergraduates acquire systems engineering knowledge; conduct innovative research; and team externally with grid smart organizations. Using the results of the separately funded Smart Grid Workforce Education Workshop (May 2009) sponsored by the City of Fort Collins, Northern Colorado Clean Energy Cluster, Colorado State University Continuing Education, Spirae, and Siemens has been used to guide the hiring of faculty, program curriculum and education plan. This project develops faculty leaders with the intellectual capacity to inspire its students to become leaders that substantially contribute to the development and maintenance of Smart Grid infrastructure through topics such as: (1) Distributed energy systems modeling and control; (2) Energy and power conversion; (3

  19. Stochastic risk-averse coordinated scheduling of grid integrated energy storage units in transmission constrained wind-thermal systems within a conditional value-at-risk framework

    International Nuclear Information System (INIS)

    Hemmati, Reza; Saboori, Hedayat; Saboori, Saeid

    2016-01-01

    In recent decades, wind power resources have been integrated in the power systems increasingly. Besides confirmed benefits, utilization of large share of this volatile source in power generation portfolio has been faced system operators with new challenges in terms of uncertainty management. It is proved that energy storage systems are capable to handle projected uncertainty concerns. Risk-neutral methods have been proposed in the previous literature to schedule storage units considering wind resources uncertainty. Ignoring risk of the cost distributions with non-desirable properties may result in experiencing high costs in some unfavorable scenarios with high probability. In order to control the risk of the operator decisions, this paper proposes a new risk-constrained two-stage stochastic programming model to make optimal decisions on energy storage and thermal units in a transmission constrained hybrid wind-thermal power system. Risk-aversion procedure is explicitly formulated using the conditional value-at-risk measure, because of possessing distinguished features compared to the other risk measures. The proposed model is a mixed integer linear programming considering transmission network, thermal unit dynamics, and storage devices constraints. The simulations results demonstrate that taking the risk of the problem into account will affect scheduling decisions considerably depend on the level of the risk-aversion. - Highlights: • Risk of the operation decisions is handled by using risk-averse programming. • Conditional value-at-risk is used as risk measure. • Optimal risk level is obtained based on the cost/benefit analysis. • The proposed model is a two-stage stochastic mixed integer linear programming. • The unit commitment is integrated with ESSs and wind power penetration.

  20. Wind energy in offshore grids

    DEFF Research Database (Denmark)

    Schröder, Sascha Thorsten

    special characteristics of offshore grids. With an operational real options approach, it is furthermore illustrated how different support schemes and connections to additional countries affect the investment case of an offshore wind farm and the income of the transmission system operator. The investment...... and investment implications under different regulatory frameworks are a hitherto underrepresented research field. They are addressed by this thesis. Offshore grids between several countries combine the absorption of wind energy with international power trading. However, the inclusion into an offshore grid......This cumulative PhD thesis deals with wind integration in offshore grids from an economic point of view. It is composed of a generic part and eight papers. As the topic has mostly been analysed with a focus on topology and technical issues until now, market-operational questions in offshore grids...

  1. Grid Computing

    Indian Academy of Sciences (India)

    A computing grid interconnects resources such as high performancecomputers, scientific databases, and computercontrolledscientific instruments of cooperating organizationseach of which is autonomous. It precedes and is quitedifferent from cloud computing, which provides computingresources by vendors to customers ...

  2. Grid Computing

    Indian Academy of Sciences (India)

    IAS Admin

    emergence of supercomputers led to the use of computer simula- tion as an .... Scientific and engineering applications (e.g., Tera grid secure gate way). Collaborative ... Encryption, privacy, protection from malicious software. Physical Layer.

  3. Heterogeneous Wireless Networks for Smart Grid Distribution Systems: Advantages and Limitations.

    Science.gov (United States)

    Khalifa, Tarek; Abdrabou, Atef; Shaban, Khaled; Gaouda, A M

    2018-05-11

    Supporting a conventional power grid with advanced communication capabilities is a cornerstone to transferring it to a smart grid. A reliable communication infrastructure with a high throughput can lay the foundation towards the ultimate objective of a fully automated power grid with self-healing capabilities. In order to realize this objective, the communication infrastructure of a power distribution network needs to be extended to cover all substations including medium/low voltage ones. This shall enable information exchange among substations for a variety of system automation purposes with a low latency that suits time critical applications. This paper proposes the integration of two heterogeneous wireless technologies (such as WiFi and cellular 3G/4G) to provide reliable and fast communication among primary and secondary distribution substations. This integration allows the transmission of different data packets (not packet replicas) over two radio interfaces, making these interfaces act like a one data pipe. Thus, the paper investigates the applicability and effectiveness of employing heterogeneous wireless networks (HWNs) in achieving the desired reliability and timeliness requirements of future smart grids. We study the performance of HWNs in a realistic scenario under different data transfer loads and packet loss ratios. Our findings reveal that HWNs can be a viable data transfer option for smart grids.

  4. Heterogeneous Wireless Networks for Smart Grid Distribution Systems: Advantages and Limitations

    Directory of Open Access Journals (Sweden)

    Tarek Khalifa

    2018-05-01

    Full Text Available Supporting a conventional power grid with advanced communication capabilities is a cornerstone to transferring it to a smart grid. A reliable communication infrastructure with a high throughput can lay the foundation towards the ultimate objective of a fully automated power grid with self-healing capabilities. In order to realize this objective, the communication infrastructure of a power distribution network needs to be extended to cover all substations including medium/low voltage ones. This shall enable information exchange among substations for a variety of system automation purposes with a low latency that suits time critical applications. This paper proposes the integration of two heterogeneous wireless technologies (such as WiFi and cellular 3G/4G to provide reliable and fast communication among primary and secondary distribution substations. This integration allows the transmission of different data packets (not packet replicas over two radio interfaces, making these interfaces act like a one data pipe. Thus, the paper investigates the applicability and effectiveness of employing heterogeneous wireless networks (HWNs in achieving the desired reliability and timeliness requirements of future smart grids. We study the performance of HWNs in a realistic scenario under different data transfer loads and packet loss ratios. Our findings reveal that HWNs can be a viable data transfer option for smart grids.

  5. TD-LTE Wireless Private Network QoS Transmission Protection

    Science.gov (United States)

    Zhang, Jianming; Cheng, Chao; Wu, Zanhong

    With the commencement of construction of the smart grid, the demand power business for reliability and security continues to improve, the reliability transmission of power TD-LTE Wireless Private Network are more and more attention. For TD-LTE power private network, it can provide different QoS services according to the user's business type, to protect the reliable transmission of business. This article describes in detail the AF module of PCC in the EPC network, specifically introduces set up AF module station and QoS mechanisms in the EPS load, fully considers the business characteristics of the special power network, establishing a suitable architecture for mapping QoS parameters, ensuring the implementation of each QoS business. Through using radio bearer management, we can achieve the reliable transmission of each business on physical channel.

  6. Self-commutated high-voltage direct current transmission with DC circuit breakers. Backbone for the energy policy turnaround; Selbstgefuehrte Hochspannungs-Gleichstromuebertragung mit DC-Leistungsschalter. Rueckgrat fuer die Energiewende

    Energy Technology Data Exchange (ETDEWEB)

    Goerner, Raphael [ABB AG, Mannheim (Germany). Marketing und Vertrieb, Geschaeftsbereich Grid Systems

    2013-06-01

    The 'current war' between direct current and alternating current is extended by a new location. In the future, both technologies work together in order to provide a reliable power transmission in Germany and long-term in Europe. This is based on the self-guided high-voltage direct current transmission. In conjunction with direct current circuit breakers (DC circuit breaker) the power circuit breakers may help to make the transmission grids more flexible and to minimize losses.

  7. Resilient Grid Operational Strategies

    Energy Technology Data Exchange (ETDEWEB)

    Pasqualini, Donatella [Los Alamos National Lab. (LANL), Los Alamos, NM (United States)

    2017-03-01

    Extreme weather-related disturbances, such as hurricanes, are a leading cause of grid outages historically. Although physical asset hardening is perhaps the most common way to mitigate the impacts of severe weather, operational strategies may be deployed to limit the extent of societal and economic losses associated with weather-related physical damage.1 The purpose of this study is to examine bulk power-system operational strategies that can be deployed to mitigate the impact of severe weather disruptions caused by hurricanes, thereby increasing grid resilience to maintain continuity of critical infrastructure during extreme weather. To estimate the impacts of resilient grid operational strategies, Los Alamos National Laboratory (LANL) developed a framework for hurricane probabilistic risk analysis (PRA). The probabilistic nature of this framework allows us to estimate the probability distribution of likely impacts, as opposed to the worst-case impacts. The project scope does not include strategies that are not operations related, such as transmission system hardening (e.g., undergrounding, transmission tower reinforcement and substation flood protection) and solutions in the distribution network.

  8. Transient stability studies on industrial power systems interconnected to the transmission grid; Estudios de estabilidad transitoria en sistemas electricos industriales con generacion propia interconectaos con el sistema de transmision

    Energy Technology Data Exchange (ETDEWEB)

    Calderon Guizar, J.G. [Instituto de Investigaciones Electricas, Cuernavaca, Morelos (Mexico)]. E-mail: jgc@iie.org.mx

    2010-10-15

    Aiming to ensure continuity in the electrical supply to critical processes, the electrical systems of large industrial plants, i.e. gas, and petrochemical industries usually posses local generation. Should the local generation be enough to satisfy the demand of the plant, then the interconnection with the public grid is commonly used as an important support for emergency conditions. This paper is concerned with the dynamical performance of two interconnected industrial power systems tied to the transmission system. Simulation results indicate that the frequency performance of one of the industrial plants, after the transients caused by the loss of the tie with the transmission system have died out, is greatly improved if both industrial plants remain connected after the disturbance. [Spanish] La continuidad en el suministro de energia electrica a procesos criticos de grandes complejos industriales, tales como plantas petroquimicas, procesadoras de gas, etc., es un aspecto de fundamental importancia para garantizar una operacion adecuada de este tipo de complejos. Con el proposito de mejorar la confiabilidad en el suministro de energia a los procesos criticos, los sistemas electricos de estos complejos industriales, generalmente cuentan con generacion propia. Si la capacidad de generacion instalada en los sistemas industriales es suficiente para satisfacer el total de la carga del complejo, la interconexion con el sistema de transmision es utilizada principalmente como respaldo durante condiciones de emergencia. En este articulo se analiza el comportamiento dinamico de dos sistemas industriales con generacion propia, disenados para operar en forma aislada, interconectados entre si, a traves de un enlace de 115 kV y con el sistema de transmision. Los resultados obtenidos indican que el comportamiento de la frecuencia en estado estable en uno de los complejos, posterior a la perdida del enlace con el sistema de transmision, mejora de manera considerable cuando estos

  9. NSTAR Smart Grid Pilot

    Energy Technology Data Exchange (ETDEWEB)

    Rabari, Anil [NSTAR Electric, Manchester, NH (United States); Fadipe, Oloruntomi [NSTAR Electric, Manchester, NH (United States)

    2014-03-31

    NSTAR Electric & Gas Corporation (“the Company”, or “NSTAR”) developed and implemented a Smart Grid pilot program beginning in 2010 to demonstrate the viability of leveraging existing automated meter reading (“AMR”) deployments to provide much of the Smart Grid functionality of advanced metering infrastructure (“AMI”), but without the large capital investment that AMI rollouts typically entail. In particular, a central objective of the Smart Energy Pilot was to enable residential dynamic pricing (time-of-use “TOU” and critical peak rates and rebates) and two-way direct load control (“DLC”) by continually capturing AMR meter data transmissions and communicating through customer-sited broadband connections in conjunction with a standardsbased home area network (“HAN”). The pilot was supported by the U.S. Department of Energy’s (“DOE”) through the Smart Grid Demonstration program. NSTAR was very pleased to not only receive the funding support from DOE, but the guidance and support of the DOE throughout the pilot. NSTAR is also pleased to report to the DOE that it was able to execute and deliver a successful pilot on time and on budget. NSTAR looks for future opportunities to work with the DOE and others in future smart grid projects.

  10. A Grid Voltage Measurement Method for Wind Power Systems during Grid Fault Conditions

    OpenAIRE

    Yoo, Cheol-Hee; Chung, Il-Yop; Yoo, Hyun-Jae; Hong, Sung-Soo

    2014-01-01

    Grid codes in many countries require low-voltage ride-through (LVRT) capability to maintain power system stability and reliability during grid fault conditions. To meet the LVRT requirement, wind power systems must stay connected to the grid and also supply reactive currents to the grid to support the recovery from fault voltages. This paper presents a new fault detection method and inverter control scheme to improve the LVRT capability for full-scale permanent magnet synchronous generator (P...

  11. From the grid to the smart grid, topologically

    Science.gov (United States)

    Pagani, Giuliano Andrea; Aiello, Marco

    2016-05-01

    In its more visionary acceptation, the smart grid is a model of energy management in which the users are engaged in producing energy as well as consuming it, while having information systems fully aware of the energy demand-response of the network and of dynamically varying prices. A natural question is then: to make the smart grid a reality will the distribution grid have to be upgraded? We assume a positive answer to the question and we consider the lower layers of medium and low voltage to be the most affected by the change. In our previous work, we analyzed samples of the Dutch distribution grid (Pagani and Aiello, 2011) and we considered possible evolutions of these using synthetic topologies modeled after studies of complex systems in other technological domains (Pagani and Aiello, 2014). In this paper, we take an extra important step by defining a methodology for evolving any existing physical power grid to a good smart grid model, thus laying the foundations for a decision support system for utilities and governmental organizations. In doing so, we consider several possible evolution strategies and apply them to the Dutch distribution grid. We show how increasing connectivity is beneficial in realizing more efficient and reliable networks. Our proposal is topological in nature, enhanced with economic considerations of the costs of such evolutions in terms of cabling expenses and economic benefits of evolving the grid.

  12. Will British weather provide reliable electricity?

    International Nuclear Information System (INIS)

    Oswald, James; Raine, Mike; Ashraf-Ball, Hezlin

    2008-01-01

    There has been much academic debate on the ability of wind to provide a reliable electricity supply. The model presented here calculates the hourly power delivery of 25 GW of wind turbines distributed across Britain's grid, and assesses power delivery volatility and the implications for individual generators on the system. Met Office hourly wind speed data are used to determine power output and are calibrated using Ofgem's published wind output records. There are two main results. First, the model suggests that power swings of 70% within 12 h are to be expected in winter, and will require individual generators to go on or off line frequently, thereby reducing the utilisation and reliability of large centralised plants. These reductions will lead to increases in the cost of electricity and reductions in potential carbon savings. Secondly, it is shown that electricity demand in Britain can reach its annual peak with a simultaneous demise of wind power in Britain and neighbouring countries to very low levels. This significantly undermines the case for connecting the UK transmission grid to neighbouring grids. Recommendations are made for improving 'cost of wind' calculations. The authors are grateful for the sponsorship provided by The Renewable Energy Foundation

  13. Reliability in the utility computing era: Towards reliable Fog computing

    DEFF Research Database (Denmark)

    Madsen, Henrik; Burtschy, Bernard; Albeanu, G.

    2013-01-01

    This paper considers current paradigms in computing and outlines the most important aspects concerning their reliability. The Fog computing paradigm as a non-trivial extension of the Cloud is considered and the reliability of the networks of smart devices are discussed. Combining the reliability...... requirements of grid and cloud paradigms with the reliability requirements of networks of sensor and actuators it follows that designing a reliable Fog computing platform is feasible....

  14. Scheduling Network Traffic for Grid Purposes

    DEFF Research Database (Denmark)

    Gamst, Mette

    This thesis concerns scheduling of network traffic in grid context. Grid computing consists of a number of geographically distributed computers, which work together for solving large problems. The computers are connected through a network. When scheduling job execution in grid computing, data...... transmission has so far not been taken into account. This causes stability problems, because data transmission takes time and thus causes delays to the execution plan. This thesis proposes the integration of job scheduling and network routing. The scientific contribution is based on methods from operations...... research and consists of six papers. The first four considers data transmission in grid context. The last two solves the data transmission problem, where the number of paths per data connection is bounded from above. The thesis shows that it is possible to solve the integrated job scheduling and network...

  15. The paradox of transmission system value

    International Nuclear Information System (INIS)

    Haddad, S.Z.; Feldman, R.D.; Charnetzki, P.

    1995-01-01

    The central importance of utility strategic planning with respect to transmission systems has developed as a result of the passage of the Energy Policy Act and the rapid emergence of the era of open grid access. As a consequence, utilities have had to redefine transmission as being more than a cost center managed with reliability as the principal focus and regulated on a rate of return basis. Transmission must now be managed with a view to protection of customers, where possible, and to revenue maximization, both through pricing strategy and through operations. This shift has been compounded by the pressures being thrust upon utilities by regulators or being fomented by competitors to unbundle transmission and distribution from generation. This paper explores how the value of the transmission system can be viewed from the vantage points of different organizations (utilities, regulators, customers, independent generators, etc.). The paper addresses the uncertain and apparently paradoxical nature of transmission system value as it will be impacted by the possible alternative future structures of the electric power industry. Lastly, this paper suggests the strategic possibilities for utilities that this uncertainty presents

  16. Application of support vector machines in the evaluation of reliability generation and transmission systems; Aplicacao de maquinas de vetores suporte na avaliacao da confiabilidade de sistemas de geracao e transmissao

    Energy Technology Data Exchange (ETDEWEB)

    Dutra, Wellington Damascena; Resende, Leonidas Chaves de [Universidade Federal de Sao Joao Del-Rei (UFSJ), MG (Brazil); Manso, Luiz Antonio da Fonseca; Silva, Armando Martins Leite da [Universidade Federal de Itajuba (UNIFEI), MG (Brazil)

    2010-07-01

    This paper presents a methodology for assessing the reliability indices for composite generation and transmission systems based on Support Vector Machines (SVM). The importance of SVMs is its high generalization ability. The SVMs are used to classify data into two distinct classes. These can be named positive and negative. Thus, the basic idea is to classify the system states into success or failure. For this, a pre-classification of states is achieved by performing the proposed SVM-based neural network, where the sampled states during the beginning of the non-sequential Monte Carlo simulation (MCS) are considered as input data for training and validation sets. By adopting this procedure, a large number of states are classified by a simple evaluation of the network, providing significant reductions in computational costs. The proposed methodology is applied to the IEEE Reliability Test System and to the IEEE Modified Reliability Test System. (author)

  17. Creating a robust and integrated electrical transmission system

    International Nuclear Information System (INIS)

    McLain, S.

    2004-01-01

    The service territory for Puget Sound Energy (PSE) was presented in terms of electric power and gas transmission. Issues affecting the Puget Sound area include high growth and the west coast energy crisis which has had an adverse financial impact on the power industry. The transmission system is basically at capacity and has been impacted by imports and exports between the United States and Canada. Other issues include the separation between energy resources and transmission, modernizing the power grid, and challenges for independent power producers (IPPs). The Northwest Transmission Assessment Committee (NTAC), which was formed under the Northwest Power Pool, has the potential to bring interested parties to study constrained paths and to plan a single utility concept for the region. It is expected that new challenges such as financing and risk management will emerge once the technical solutions are identified and agreed upon. The issue of enforceable and mandatory reliability standards was also discussed. 1 fig

  18. Software-Based Challenges of Developing the Future Distribution Grid

    Energy Technology Data Exchange (ETDEWEB)

    Stewart, Emma; Kiliccote, Sila; McParland, Charles

    2014-06-01

    The software that the utility industry currently uses may be insufficient to analyze the distribution grid as it rapidly modernizes to include active resources such as distributed generation, switch and voltage control, automation, and increasingly complex loads. Although planners and operators have traditionally viewed the distribution grid as a passive load, utilities and consultants increasingly need enhanced analysis that incorporates active distribution grid loads in order to ensure grid reliability. Numerous commercial and open-source tools are available for analyzing distribution grid systems. These tools vary in complexity from providing basic load-flow and capacity analysis under steady-state conditions to time-series analysis and even geographical representations of dynamic and transient events. The need for each type of analysis is not well understood in the industry, nor are the reasons that distribution analysis requires different techniques and tools both from those now available and from those used for transmission analysis. In addition, there is limited understanding of basic capability of the tools and how they should be practically applied to the evolving distribution system. The study reviews the features and state of the art capability of current tools, including usability and visualization, basic analysis functionality, advanced analysis including inverters, and renewable generation and load modeling. We also discuss the need for each type of distribution grid system analysis. In addition to reviewing basic functionality current models, we discuss dynamics and transient simulation in detail and draw conclusions about existing software?s ability to address the needs of the future distribution grid as well as the barriers to modernization of the distribution grid that are posed by the current state of software and model development. Among our conclusions are that accuracy, data transfer, and data processing abilities are key to future

  19. Smart Control of Energy Distribution Grids over Heterogeneous Communication Networks

    DEFF Research Database (Denmark)

    Olsen, Rasmus Løvenstein; Iov, Florin; Hägerling, Christian

    2014-01-01

    The expected growth in distributed generation will significantly affect the operation and control of todays distribution grids. Being confronted with short time power variations of distributed generations, the assurance of a reliable service (grid stability, avoidance of energy losses) and the qu......The expected growth in distributed generation will significantly affect the operation and control of todays distribution grids. Being confronted with short time power variations of distributed generations, the assurance of a reliable service (grid stability, avoidance of energy losses...

  20. Comprehensive Solutions for Integration of Solar Resources into Grid Operations

    Energy Technology Data Exchange (ETDEWEB)

    Pennock, Kenneth [AWS Truepower, LLC, Albany, NY (United States); Makarov, Yuri V. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Rajagopal, Sankaran [Siemens Energy, Erlangen (Germany); Loutan, Clyde [California Independent System Operator; Etingov, Pavel V. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Miller, Laurie E. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Lu, Bo [Siemens Energy, Erlangen (Germany); Mansingh, Ashmin [Siemens Energy, Erlangen (Germany); Zack, John [MESO, Inc., Raleigh, NC (United States); Sherick, Robert [Southern California Edison, Rosemead, CA (United States); Romo, Abraham [Southern California Edison; Habibi-Ashrafi, Farrokh [Southern California Edison; Johnson, Raymond [Southern California Edison

    2016-01-14

    The need for proactive closed-loop integration of uncertainty information into system operations and probability-based controls is widely recognized, but rarely implemented in system operations. Proactive integration for this project means that the information concerning expected uncertainty ranges for net load and balancing requirements, including required balancing capacity, ramping and ramp duration characteristics, will be fed back into the generation commitment and dispatch algorithms to modify their performance so that potential shortages of these characteristics can be prevented. This basic, yet important, premise is the motivating factor for this project. The achieved project goal is to demonstrate the benefit of such a system. The project quantifies future uncertainties, predicts additional system balancing needs including the prediction intervals for capacity and ramping requirements of future dispatch intervals, evaluates the impacts of uncertainties on transmission including the risk of overloads and voltage problems, and explores opportunities for intra-hour generation adjustments helping to provide more flexibility for system operators. The resulting benefits culminate in more reliable grid operation in the face of increased system uncertainty and variability caused by solar power. The project identifies that solar power does not require special separate penetration level restrictions or penalization for its intermittency. Ultimately, the collective consideration of all sources of intermittency distributed over a wide area unified with the comprehensive evaluation of various elements of balancing process, i.e. capacity, ramping, and energy requirements, help system operators more robustly and effectively balance generation against load and interchange. This project showed that doing so can facilitate more solar and other renewable resources on the grid without compromising reliability and control performance. Efforts during the project included

  1. Autonomous Energy Grids: Preprint

    Energy Technology Data Exchange (ETDEWEB)

    Kroposki, Benjamin D [National Renewable Energy Laboratory (NREL), Golden, CO (United States); Dall-Anese, Emiliano [National Renewable Energy Laboratory (NREL), Golden, CO (United States); Bernstein, Andrey [National Renewable Energy Laboratory (NREL), Golden, CO (United States); Zhang, Yingchen [National Renewable Energy Laboratory (NREL), Golden, CO (United States); Hodge, Brian S [National Renewable Energy Laboratory (NREL), Golden, CO (United States)

    2017-10-04

    With much higher levels of distributed energy resources - variable generation, energy storage, and controllable loads just to mention a few - being deployed into power systems, the data deluge from pervasive metering of energy grids, and the shaping of multi-level ancillary-service markets, current frameworks to monitoring, controlling, and optimizing large-scale energy systems are becoming increasingly inadequate. This position paper outlines the concept of 'Autonomous Energy Grids' (AEGs) - systems that are supported by a scalable, reconfigurable, and self-organizing information and control infrastructure, can be extremely secure and resilient (self-healing), and self-optimize themselves in real-time for economic and reliable performance while systematically integrating energy in all forms. AEGs rely on scalable, self-configuring cellular building blocks that ensure that each 'cell' can self-optimize when isolated from a larger grid as well as partaking in the optimal operation of a larger grid when interconnected. To realize this vision, this paper describes the concepts and key research directions in the broad domains of optimization theory, control theory, big-data analytics, and complex system modeling that will be necessary to realize the AEG vision.

  2. Grid Code Requirements for Wind Power Integration

    DEFF Research Database (Denmark)

    Wu, Qiuwei

    2018-01-01

    This chapter reviews the grid code requirements for integration of wind power plants (WPPs). The grid codes reviewed are from the UK, Ireland, Germany, Denmark, Spain, Sweden, the USA, and Canada. Transmission system operators (TSOs) around the world have specified requirements for WPPs under...

  3. Smart Grid | Climate Neutral Research Campuses | NREL

    Science.gov (United States)

    power consumption of campus data centers. University of California at Los Angeles: Hosts the Wireless of the U.S. electric power grid through reinforced infrastructure, sophisticated electronic sensors transmission and distribution system to better coordinate energy delivery into the grid. Better coordinate

  4. Risk management and participation planning of electric vehicles in smart grids for demand response

    International Nuclear Information System (INIS)

    Nezamoddini, Nasim; Wang, Yong

    2016-01-01

    Demand response (DR) can serve as an effective tool to better balance the electricity demand and supply in the smart grid. It is defined as 'the changes in electricity usage by end-use customers from their normal consumption patterns' in response to pricing and incentive payments. This paper focuses on new opportunities for DR with electric vehicles (EVs). EVs are potential distributed energy resources that support both the grid-to-vehicle and vehicle-to-grid modes. Their participation in the time-based (e.g., time-of-use) and incentive-based (e.g., regulation services) DR programs helps improve the stability and reduce the potential risks to the grid. Smart scheduling of EV charging and discharging activities also supports high penetration of renewables with volatile energy generation. This paper proposes a novel stochastic model from the Independent System Operator's perspective for risk management and participation planning of EVs in the smart grid for DR. The risk factors considered in this paper involve those caused by uncertainties in renewables (wind and solar), load patterns, parking patterns, and transmission lines' reliability. The effectiveness of the model in response to various settings such as the area type (residential, commercial, and industrial), the EV penetration level, and the risk level has been investigated. - Highlights: • We identify new opportunities for demand response (DR) using electric vehicles (EVs). • We integrate EVs in both grid-to-vehicle and vehicle-to-grid modes in smart grids. • EV participation for both time- and incentive-based DR programs are modelled. • We consider uncertainties in renewables, load, parking, and transmission lines. • Model case studies are demonstrated in residential, commercial, and industrial areas.

  5. Power grids

    International Nuclear Information System (INIS)

    Viterbo, J.

    2012-01-01

    The implementation of renewable energies represents new challenges for electrical systems. The objective: making power grids smarter so they can handle intermittent production. The advent of smart grids will allow flexible operations like distributing energy in a multidirectional manner instead of just one way and it will make electrical systems capable of integrating actions by different users, consumers and producers in order to maintain efficient, sustainable, economical and secure power supplies. Practically speaking, they associate sensors, instrumentation and controls with information processing and communication systems in order to create massively automated networks. Smart grids require huge investments: for example more than 7 billion dollars have been invested in China and in the Usa in 2010 and France is ranked 9. worldwide with 265 million dollars invested. It is expected that smart grids will promote the development of new business models and a change in the value chain for energy. Decentralized production combined with the probable introduction of more or less flexible rates for sales or purchases and of new supplier-customer relationships will open the way to the creation of new businesses. (A.C.)

  6. Climate and Water Vulnerability of the US Electricity Grid Under High Penetrations of Renewable Energy

    Science.gov (United States)

    Macknick, J.; Miara, A.; O'Connell, M.; Vorosmarty, C. J.; Newmark, R. L.

    2017-12-01

    The US power sector is highly dependent upon water resources for reliable operations, primarily for thermoelectric cooling and hydropower technologies. Changes in the availability and temperature of water resources can limit electricity generation and cause outages at power plants, which substantially affect grid-level operational decisions. While the effects of water variability and climate changes on individual power plants are well documented, prior studies have not identified the significance of these impacts at the regional systems-level at which the grid operates, including whether there are risks for large-scale blackouts, brownouts, or increases in production costs. Adequately assessing electric grid system-level impacts requires detailed power sector modeling tools that can incorporate electric transmission infrastructure, capacity reserves, and other grid characteristics. Here, we present for the first time, a study of how climate and water variability affect operations of the power sector, considering different electricity sector configurations (low vs. high renewable) and environmental regulations. We use a case study of the US Eastern Interconnection, building off the Eastern Renewable Generation Integration Study (ERGIS) that explored operational challenges of high penetrations of renewable energy on the grid. We evaluate climate-water constraints on individual power plants, using the Thermoelectric Power and Thermal Pollution (TP2M) model coupled with the PLEXOS electricity production cost model, in the context of broader electricity grid operations. Using a five minute time step for future years, we analyze scenarios of 10% to 30% renewable energy penetration along with considerations of river temperature regulations to compare the cost, performance, and reliability tradeoffs of water-dependent thermoelectric generation and variable renewable energy technologies under climate stresses. This work provides novel insights into the resilience and

  7. THE MAIN DIRECTIONS OF IMPROVING THE EFFICIENCY OF PRODUCTION, TRANSMISSION AND DISTRIBUTION OF ELECTRICAL ENERGY

    Directory of Open Access Journals (Sweden)

    I. V. Zhezhelenko

    2018-01-01

    Full Text Available The main directions of increase of efficiency of production, transmission and distribution of electric energy have been formulated. The relation between the values of electricity losses during transmission via power grids of different countries and the level of the economies of these countries characterized by the value of gross domestic product at purchasing power parity per capita has been established. In the countries with a gross domestic product at purchasing power parity per capita less than 20 thousand US dollars electricity losses during its transmission via power grids are 1.5–2.5 times more than the ones transmitted via power grids of the industrialized countries where the specified purchasing power parity is in the range of 30.4–54.5 thousand US dollars. In the countries with more developed economies the technical culture of production, transmission and distribution of electricity is higher; the modern control systems of operation modes of electrical networks are used as well as of monitoring and accounting of electricity; also there are solvent and disciplined consumers in such countries as well as clear regulatory framework and tariff regulation system. However, the process of transmission and distribution of electricity is effective if not only low relative losses take place, but the normal (contractual requirements for carrying capacity, quality and reliability of electricity supply are provided. The possibility of analytical determination of the optimum value of reserve capacity of power plants providing the required level of reliability of the power system has been considered.

  8. The Emerging Interdependence of the Electric Power Grid & Information and Communication Technology

    Energy Technology Data Exchange (ETDEWEB)

    Taft, Jeffrey D. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Becker-Dippmann, Angela S. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States)

    2015-08-01

    This paper examines the implications of emerging interdependencies between the electric power grid and Information and Communication Technology (ICT). Over the past two decades, electricity and ICT infrastructure have become increasingly interdependent, driven by a combination of factors including advances in sensor, network and software technologies and progress in their deployment, the need to provide increasing levels of wide-area situational awareness regarding grid conditions, and the promise of enhanced operational efficiencies. Grid operators’ ability to utilize new and closer-to-real-time data generated by sensors throughout the system is providing early returns, particularly with respect to management of the transmission system for purposes of reliability, coordination, congestion management, and integration of variable electricity resources such as wind generation.

  9. North America grid segmentation case studies : technical feasibility and economics of implementation

    Energy Technology Data Exchange (ETDEWEB)

    Johnson, A.L. [Bonneville Power Administration, Portland, OR (United States); Clark, H.K.; El-Gasseir, M.M.; Epp, H.D.K.; Woodford, D.A. [DC Interconnect Inc., Vancouver, BC (Canada); Barthold, L.O.; Reppen, N.D.

    2009-07-01

    There continues to be unprecedented demand on power grids. The primary requirement is for a highly resilient grid that includes large transmission capacity reserves. There is increased demand for total transfer capability (TTC) to meet renewables policy targets and improved accommodation of complex market transactions. Some potential components include storage, FACTS controllers, dynamic ACE and other technologies. This presentation proposed segmentation as a different solution in order to meet the same demands more economically and greatly enhance reliability. The presentation described how segmentation works and discussed the benefits of a simple controller. Segmentation benefits in system planning and operation were also outlined. Other topics that were presented included renewable generation; grid security; cascading; adjustments that an operator might make; line converter and high voltage direct current (HVDC) converter options; HVDC line and converter configurations; and segmentation studies in North America. Economic analyses were also discussed. The presentation concluded with a potential application in northern Europe. 3 figs.

  10. Dynamic Line Rating Oncor Electric Delivery Smart Grid Program

    Energy Technology Data Exchange (ETDEWEB)

    Johnson, Justin; Smith, Cale; Young, Mike; Donohoo, Ken; Owen, Ross; Clark, Eddit; Espejo, Raul; Aivaliotis, Sandy; Stelmak, Ron; Mohr, Ron; Barba, Cristian; Gonzalez, Guillermo; Malkin, Stuart; Dimitrova, Vessela; Ragsdale, Gary; Mitchem, Sean; Jeirath, Nakul; Loomis, Joe; Trevino, Gerardo; Syracuse, Steve; Hurst, Neil; Mereness, Matt; Johnson, Chad; Bivens, Carrie

    2013-05-04

    Electric transmission lines are the lifeline of the electric utility industry, delivering its product from source to consumer. This critical infrastructure is often constrained such that there is inadequate capacity on existing transmission lines to efficiently deliver the power to meet demand in certain areas or to transport energy from high-generation areas to high-consumption regions. When this happens, the cost of the energy rises; more costly sources of power are used to meet the demand or the system operates less reliably. These economic impacts are known as congestion, and they can amount to substantial dollars for any time frame of reference: hour, day or year. There are several solutions to the transmission constraint problem, including: construction of new generation, construction of new transmission facilities, rebuilding and reconductoring of existing transmission assets, and Dynamic Line Rating (DLR). All of these options except DLR are capital intensive, have long lead times and often experience strong public and regulatory opposition. The Smart Grid Demonstration Program (SGDP) project co-funded by the Department of Energy (DOE) and Oncor Electric Delivery Company developed and deployed the most extensive and advanced DLR installation to demonstrate that DLR technology is capable of resolving many transmission capacity constraint problems with a system that is reliable, safe and very cost competitive. The SGDP DLR deployment is the first application of DLR technology to feed transmission line real-time dynamic ratings directly into the system operation’s State Estimator and load dispatch program, which optimizes the matching of generation with load demand on a security, reliability and economic basis. The integrated Dynamic Line Rating (iDLR)1 collects transmission line parameters at remote locations on the lines, calculates the real-time line rating based on the equivalent conductor temperature, ambient temperature and influence of wind and solar

  11. National Offshore Wind Energy Grid Interconnection Study

    Energy Technology Data Exchange (ETDEWEB)

    Daniel, John P. [ABB Inc; Liu, Shu [ABB Inc; Ibanez, Eduardo [National Renewable Energy Laboratory; Pennock, Ken [AWS Truepower; Reed, Greg [University of Pittsburgh; Hanes, Spencer [Duke Energy

    2014-07-30

    The National Offshore Wind Energy Grid Interconnection Study (NOWEGIS) considers the availability and potential impacts of interconnecting large amounts of offshore wind energy into the transmission system of the lower 48 contiguous United States. A total of 54GW of offshore wind was assumed to be the target for the analyses conducted. A variety of issues are considered including: the anticipated staging of offshore wind; the offshore wind resource availability; offshore wind energy power production profiles; offshore wind variability; present and potential technologies for collection and delivery of offshore wind energy to the onshore grid; potential impacts to existing utility systems most likely to receive large amounts of offshore wind; and regulatory influences on offshore wind development. The technologies considered the reliability of various high-voltage ac (HVAC) and high-voltage dc (HVDC) technology options and configurations. The utility system impacts of GW-scale integration of offshore wind are considered from an operational steady-state perspective and from a regional and national production cost perspective.

  12. Grid pulser

    International Nuclear Information System (INIS)

    Jansweijer, P.P.M.; Es, J.T. van.

    1990-01-01

    This report describes a fast pulse generator. This generator delivers a high-voltage pulse of at most 6000 V with a rise time being smaller than 50 nS. this results in a slew rate of more than 120.000 volts per μS. The pulse generator is used to control the grid of the injector of the electron accelerator MEA. The capacity of this grid is about 60 pF. In order to charge this capacity up to 6000 volts in 50 nS a current of 8 ampere is needed. The maximal pulse length is 50 μS with a repeat frequency of 500 Hz. During this 50 μS the stability of the pulse amplitude is better than 0.1%. (author). 20 figs

  13. The grid

    OpenAIRE

    Morrad, Annie; McArthur, Ian

    2018-01-01

    Project Anywhere Project title: The Grid   Artists: Annie Morrad: Artist/Senior Lecturer, University of Lincoln, School of Film and Media, Lincoln, UK   Dr Ian McArthur: Hybrid Practitioner/Senior Lecturer, UNSW Art & Design, UNSW Australia, Sydney, Australia   Annie Morrad is a London-based artist and musician and senior lecturer at the University of Lincoln, UK. Dr Ian McArthur is a Sydney-based hybrid practitione...

  14. Roadmap for the ARC Grid Middleware

    DEFF Research Database (Denmark)

    Kleist, Josva; Eerola, Paula; Ekelöf, Tord

    2006-01-01

    The Advanced Resource Connector (ARC) or the NorduGrid middleware is an open source software solution enabling production quality computational and data Grids, with special emphasis on scalability, stability, reliability and performance. Since its first release in May 2002, the middleware is depl...

  15. Performance of LTE for smart grid communications

    NARCIS (Netherlands)

    Karagiannis, Georgios; Pham, G.T.; Nguyen, A.D.; Heijenk, Geert; Haverkort, Boudewijn R.H.M.; Campfens, F.; Fischbach, K.; Krieger, U.R.

    The next generation power grid (the “Smart Grid‿) aims to minimize environmental impact, enhance markets, improve reliability and service, and reduce costs and improve efficiency of electricity distribution. One of the main protocol frameworks used in Smart Grids is IEC 61850. Together with the

  16. Reliability engineering

    International Nuclear Information System (INIS)

    Lee, Chi Woo; Kim, Sun Jin; Lee, Seung Woo; Jeong, Sang Yeong

    1993-08-01

    This book start what is reliability? such as origin of reliability problems, definition of reliability and reliability and use of reliability. It also deals with probability and calculation of reliability, reliability function and failure rate, probability distribution of reliability, assumption of MTBF, process of probability distribution, down time, maintainability and availability, break down maintenance and preventive maintenance design of reliability, design of reliability for prediction and statistics, reliability test, reliability data and design and management of reliability.

  17. Innovations in power systems reliability

    CERN Document Server

    Santora, Albert H; Vaccaro, Alfredo

    2011-01-01

    Electrical grids are among the world's most reliable systems, yet they still face a host of issues, from aging infrastructure to questions of resource distribution. Here is a comprehensive and systematic approach to tackling these contemporary challenges.

  18. Power grid operation risk management: V2G deployment for sustainable development

    Science.gov (United States)

    Haddadian, Ghazale J.

    The production, transmission, and delivery of cost--efficient energy to supply ever-increasing peak loads along with a quest for developing a low-carbon economy require significant evolutions in the power grid operations. Lower prices of vast natural gas resources in the United States, Fukushima nuclear disaster, higher and more intense energy consumptions in China and India, issues related to energy security, and recent Middle East conflicts, have urged decisions makers throughout the world to look into other means of generating electricity locally. As the world look to combat climate changes, a shift from carbon-based fuels to non-carbon based fuels is inevitable. However, the variability of distributed generation assets in the electricity grid has introduced major reliability challenges for power grid operators. While spearheading sustainable and reliable power grid operations, this dissertation develops a multi-stakeholder approach to power grid operation design; aiming to address economic, security, and environmental challenges of the constrained electricity generation. It investigates the role of Electric Vehicle (EV) fleets integration, as distributed and mobile storage assets to support high penetrations of renewable energy sources, in the power grid. The vehicle-to-grid (V2G) concept is considered to demonstrate the bidirectional role of EV fleets both as a provider and consumer of energy in securing a sustainable power grid operation. The proposed optimization modeling is the application of Mixed-Integer Linear Programing (MILP) to large-scale systems to solve the hourly security-constrained unit commitment (SCUC) -- an optimal scheduling concept in the economic operation of electric power systems. The Monte Carlo scenario-based approach is utilized to evaluate different scenarios concerning the uncertainties in the operation of power grid system. Further, in order to expedite the real-time solution of the proposed approach for large-scale power systems

  19. Safe Grid

    Science.gov (United States)

    Chow, Edward T.; Stewart, Helen; Korsmeyer, David (Technical Monitor)

    2003-01-01

    The biggest users of GRID technologies came from the science and technology communities. These consist of government, industry and academia (national and international). The NASA GRID is moving into a higher technology readiness level (TRL) today; and as a joint effort among these leaders within government, academia, and industry, the NASA GRID plans to extend availability to enable scientists and engineers across these geographical boundaries collaborate to solve important problems facing the world in the 21 st century. In order to enable NASA programs and missions to use IPG resources for program and mission design, the IPG capabilities needs to be accessible from inside the NASA center networks. However, because different NASA centers maintain different security domains, the GRID penetration across different firewalls is a concern for center security people. This is the reason why some IPG resources are been separated from the NASA center network. Also, because of the center network security and ITAR concerns, the NASA IPG resource owner may not have full control over who can access remotely from outside the NASA center. In order to obtain organizational approval for secured remote access, the IPG infrastructure needs to be adapted to work with the NASA business process. Improvements need to be made before the IPG can be used for NASA program and mission development. The Secured Advanced Federated Environment (SAFE) technology is designed to provide federated security across NASA center and NASA partner's security domains. Instead of one giant center firewall which can be difficult to modify for different GRID applications, the SAFE "micro security domain" provide large number of professionally managed "micro firewalls" that can allow NASA centers to accept remote IPG access without the worry of damaging other center resources. The SAFE policy-driven capability-based federated security mechanism can enable joint organizational and resource owner approved remote

  20. MATL : Canada's first merchant power transmission interconnection : experiences and future outlook

    International Nuclear Information System (INIS)

    Wilson, L.

    2006-01-01

    The current status of the Montana Alberta Tie Ltd. (MATL) merchant transmission project was outlined with reference to the business concept, the advantages of the project and market opportunities. Some of the challenges facing the project were discussed along with lessons learned and accomplishments thus far. MATL is preparing to construct a privately funded transmission line between Lethbridge, Alberta and Great Falls, Montana. The project represents the first direct power transmission inter-connection between Montana and Alberta. The 346 km, 230 kV AC transmission line with phase shifting transformer and 300 MW transfer capacity will be a synchronous interconnection and will improve the reliability of the entire electric systems in both Montana and Alberta. The benefits of the interconnected power system include increased reliability and stability of the existing power grids; better import/export capabilities; more competition and options in the marketplace; greater flexibility in scheduling generator maintenance; and, optimal allocation of generation resources. tabs., figs

  1. Nondestructive measurement of the grid ratio using a single image

    International Nuclear Information System (INIS)

    Pasciak, A. S.; Jones, A. Kyle

    2009-01-01

    The antiscatter grid is an essential part of modern radiographic systems. Since the introduction of the antiscatter grid, however, there have been few methods proposed for acceptance testing and verification of manufacturer-supplied grid specifications. The grid ratio (r) is an important parameter describing the antiscatter grid because it affects many other grid quality metrics, such as the contrast improvement ratio (K), primary transmission (T p ), and scatter transmission (T s ). Also, the grid ratio in large part determines the primary clinical use of the grid. To this end, the authors present a technique for the nondestructive measurement of the grid ratio of antiscatter grids. They derived an equation that can be used to calculate the grid ratio from a single off-focus flat field image by exploiting the relationship between grid cutoff and off-focus distance. The calculation can be performed by hand or with included analysis software. They calculated the grid ratios of several different grids throughout the institution, and afterward they destructively measured the grid ratio of a nominal r8 grid previously evaluated with the method. They also studied the sensitivity of the method to technical factors and choice of parameters. With one exception, the results for the grids found in the institution were in agreement with the manufacturer's specifications and international standards. The nondestructive evaluation of the r8 grid indicated a ratio of 7.3, while the destructive measurement indicated a ratio of 7.53±0.28. Repeated evaluations of the same grid yielded consistent results. The technique provides the medical physicist with a new tool for quantitative evaluation of the grid ratio, an important grid performance criterion. The method is robust and repeatable when appropriate choices of technical factors and other parameters are made.

  2. Smart Grid Control and Communication

    DEFF Research Database (Denmark)

    Ciontea, Catalin-Iosif; Pedersen, Rasmus; Kristensen, Thomas le Fevre

    2015-01-01

    to the reliability due to the stochastic behavior found in such networks. Therefore, key concepts are presented in this paper targeting the support of proper smart grid control in these network environments and its Real-Time Hardware-In-the Loop (HIL) verification. An overview on the required Information...

  3. Grid Synchronization for Distributed Generations

    DEFF Research Database (Denmark)

    Peyghami, Saeed; Mokhtari, Hossein; Blaabjerg, Frede

    2017-01-01

    Distributed generators (DGs) like photovoltaic arrays, wind turbines, and fuel cell modules, as well as distributed storage (DS) units introduce some advantages to the power systems and make it more reliable, flexible, and controllable in comparison with the conventional power systems. Grid inter...

  4. Grid interoperability: joining grid information systems

    International Nuclear Information System (INIS)

    Flechl, M; Field, L

    2008-01-01

    A grid is defined as being 'coordinated resource sharing and problem solving in dynamic, multi-institutional virtual organizations'. Over recent years a number of grid projects, many of which have a strong regional presence, have emerged to help coordinate institutions and enable grids. Today, we face a situation where a number of grid projects exist, most of which are using slightly different middleware. Grid interoperation is trying to bridge these differences and enable Virtual Organizations to access resources at the institutions independent of their grid project affiliation. Grid interoperation is usually a bilateral activity between two grid infrastructures. Recently within the Open Grid Forum, the Grid Interoperability Now (GIN) Community Group is trying to build upon these bilateral activities. The GIN group is a focal point where all the infrastructures can come together to share ideas and experiences on grid interoperation. It is hoped that each bilateral activity will bring us one step closer to the overall goal of a uniform grid landscape. A fundamental aspect of a grid is the information system, which is used to find available grid services. As different grids use different information systems, interoperation between these systems is crucial for grid interoperability. This paper describes the work carried out to overcome these differences between a number of grid projects and the experiences gained. It focuses on the different techniques used and highlights the important areas for future standardization

  5. Smart power grids 2011

    CERN Document Server

    Keyhani, Ali

    2012-01-01

    Electric power systems are experiencing significant changes at the worldwide scale in order to become cleaner, smarter, and more reliable. This edited book examines a wide range of topics related to these changes, which are primarily caused by the introduction of information technologies, renewable energy penetration, digitalized equipment, new operational strategies, and so forth. The emphasis will be put on the modeling and control of smart grid systems. This book addresses research topics such as high efficiency transforrmers, wind turbines and generators, fuel cells, or high speed turbines

  6. Dynamic Loadability of Cable Based Transmission Grids

    DEFF Research Database (Denmark)

    Olsen, Rasmus Schmidt

    D project was carried out at three main locations, the head quarters of Energinet.dk in Errits, DTU in Kgs. Lyngby and during a ve months external stay at Kinectrics in Toronto, Canada. At Energinet.dk I gained considerable knowledge about the practical considerations regarding design, installation...... be found in the appendix. This thesis is divided into 9 chapters, plus list of references, appendices, etc. References to literature are denoted in square brackets, e.g. [1], and equations are denoted in parenthesis, e.g. (1.2) where the 1 refers to the chapter number and the 2 refers to the specic...

  7. A Reduced Wind Power Grid Model for Research and Education

    DEFF Research Database (Denmark)

    Akhmatov, Vladislav; Lund, Torsten; Hansen, Anca Daniela

    2007-01-01

    A reduced grid model of a transmission system with a number of central power plants, consumption centers, local wind turbines and a large offshore wind farm is developed and implemented in the simulation tool PowerFactory (DIgSILENT). The reduced grid model is given by Energinet.dk, Transmission...

  8. Silicon carbide devices: more reliability for transmission and distribution systems; Dispositivos de SiC: mais confiabilidade para sistemas de transmissao e distribuicao

    Energy Technology Data Exchange (ETDEWEB)

    Basset, Roger; Ballad, John [Areva T and D Tecnology Centre (United Kingdom)

    2006-05-15

    The silicon carbide power semiconductors will represent an essential role in relation to electrical nets in the future. Counting with higher voltage levels, more rapid commutations and allowing higher temperatures then the current silicon semiconductors, they will result in power electronic equipment with lower dissipation and smaller amount of components, becoming more compacts and reliable.

  9. Impact of Converter Interfaced Generation and Load on Grid Performance

    Science.gov (United States)

    Ramasubramanian, Deepak

    Alternate sources of energy such as wind, solar photovoltaic and fuel cells are coupled to the power grid with the help of solid state converters. Continued deregulation of the power sector coupled with favorable government incentives has resulted in the rapid growth of renewable energy sources connected to the distribution system at a voltage level of 34.5kV or below. Of late, many utilities are also investing in these alternate sources of energy with the point of interconnection with the power grid being at the transmission level. These converter interfaced generation along with their associated control have the ability to provide the advantage of fast control of frequency, voltage, active, and reactive power. However, their ability to provide stability in a large system is yet to be investigated in detail. This is the primary objective of this research. In the future, along with an increase in the percentage of converter interfaced renewable energy sources connected to the transmission network, there exists a possibility of even connecting synchronous machines to the grid through converters. Thus, all sources of energy can be expected to be coupled to the grid through converters. The control and operation of such a grid will be unlike anything that has been encountered till now. In this dissertation, the operation and behavior of such a grid will be investigated. The first step in such an analysis will be to build an accurate and simple mathematical model to represent the corresponding components in commercial software. Once this bridge has been crossed, conventional machines will be replaced with their solid state interfaced counterparts in a phased manner. At each stage, attention will be devoted to the control of these sources and also on the stability performance of the large power system. This dissertation addresses various concerns regarding the control and operation of a futuristic power grid. In addition, this dissertation also aims to address the issue

  10. Secure and Time-Aware Communication of Wireless Sensors Monitoring Overhead Transmission Lines.

    Science.gov (United States)

    Mazur, Katarzyna; Wydra, Michal; Ksiezopolski, Bogdan

    2017-07-11

    Existing transmission power grids suffer from high maintenance costs and scalability issues along with a lack of effective and secure system monitoring. To address these problems, we propose to use Wireless Sensor Networks (WSNs) as a technology to achieve energy efficient, reliable, and low-cost remote monitoring of transmission grids. With WSNs, smart grid enables both utilities and customers to monitor, predict and manage energy usage effectively and react to possible power grid disturbances in a timely manner. However, the increased application of WSNs also introduces new security challenges, especially related to privacy, connectivity, and security management, repeatedly causing unpredicted expenditures. Monitoring the status of the power system, a large amount of sensors generates massive amount of sensitive data. In order to build an effective Wireless Sensor Network (WSN) for a smart grid, we focus on designing a methodology of efficient and secure delivery of the data measured on transmission lines. We perform a set of simulations, in which we examine different routing algorithms, security mechanisms and WSN deployments in order to select the parameters that will not affect the delivery time but fulfill their role and ensure security at the same time. Furthermore, we analyze the optimal placement of direct wireless links, aiming at minimizing time delays, balancing network performance and decreasing deployment costs.

  11. Smart Grid Technologies: Trends and Perspectives

    Directory of Open Access Journals (Sweden)

    Buran Anna

    2017-01-01

    Full Text Available The study explores the role of Smart Grid technologies, giving sustainable, reliable and safe energy. These technologies will provide an economic benefit to the government, the investors and the consumers. The paper overviews global trends and perspectives of using Smart Grid technologies in Russia and in other countries. The Smart Grid concept is especially important for Russia, because there are many power supply problems in the energy sector. This study is expected to be important for researchers and engineers studying Smart Grid technologies.

  12. Regression and kriging analysis for grid power factor estimation

    OpenAIRE

    Rajesh Guntaka; Harley R. Myler

    2014-01-01

    The measurement of power factor (PF) in electrical utility grids is a mainstay of load balancing and is also a critical element of transmission and distribution efficiency. The measurement of PF dates back to the earliest periods of electrical power distribution to public grids. In the wide-area distribution grid, measurement of current waveforms is trivial and may be accomplished at any point in the grid using a current tap transformer. However, voltage measurement requires reference to grou...

  13. Superconductors in the power grid materials and applications

    CERN Document Server

    2015-01-01

    Superconductors offer high throughput with low electric losses and have the potential to transform the electric power grid. Transmission networks incorporating cables of this type could, for example, deliver more power and enable substantial energy savings. Superconductors in the Power Grid: Materials and Applications provides an overview of superconductors and their applications in power grids. Sections address the design and engineering of cable systems and fault current limiters and other emerging applications for superconductors in the power grid, as well as case studies of industrial applications of superconductors in the power grid. Expert editor from highly respected US government-funded research centre Unique focus on superconductors in the power grid Comprehensive coverage

  14. Image and diagnosis quality of X-ray image transmission via cell phone camera: a project study evaluating quality and reliability.

    Directory of Open Access Journals (Sweden)

    Hans Goost

    Full Text Available INTRODUCTION: Developments in telemedicine have not produced any relevant benefits for orthopedics and trauma surgery to date. For the present project study, several parameters were examined during assessment of x-ray images, which had been photographed and transmitted via cell phone. MATERIALS AND METHODS: A total of 100 x-ray images of various body regions were photographed with a Nokia cell phone and transmitted via email or MMS. Next, the transmitted photographs were reviewed on a laptop computer by five medical specialists and assessed regarding quality and diagnosis. RESULTS: Due to their poor quality, the transmitted MMS images could not be evaluated and this path of transmission was therefore excluded. Mean size of transmitted x-ray email images was 394 kB (range: 265-590 kB, SD ± 59, average transmission time was 3.29 min ± 8 (CI 95%: 1.7-4.9. Applying a score from 1-10 (very poor - excellent, mean image quality was 5.8. In 83.2 ± 4% (mean value ± SD of cases (median 82; 80-89%, there was agreement between final diagnosis and assessment by the five medical experts who had received the images. However, there was a markedly low concurrence ratio in the thoracic area and in pediatric injuries. DISCUSSION: While the rate of accurate diagnosis and indication for surgery was high with a concurrence ratio of 83%, considerable differences existed between the assessed regions, with lowest values for thoracic images. Teleradiology is a cost-effective, rapid method which can be applied wherever wireless cell phone reception is available. In our opinion, this method is in principle suitable for clinical use, enabling the physician on duty to agree on appropriate measures with colleagues located elsewhere via x-ray image transmission on a cell phone.

  15. Alternatives to the grid : distributed generation

    Energy Technology Data Exchange (ETDEWEB)

    Kline, R.H. [Mercury Electric Co., Calgary, AB (Canada)

    2002-07-01

    This presentation outlines the benefits of distributed generation with reference to energy drivers, reliability, power quality, and the impact of open energy markets. Deregulation in Alberta's electric power industry has created options and imposed responsibilities on both industrial and commercial consumers. Customers have the option to self-generate a portion or all of their energy needs. The options are to buy energy from a power marketer, to buy energy from the Power Pool of Alberta, to develop one's own power, or to contract with an independent power producer. It is important to understand base load and peaking requirements in order to determine which option is best, where power quality and reliability will not be compromised. Small scale on-site power generation offers advantages such as reduced peak strain on the transmission grid, and reduced total energy costs. Regulatory changes are making it easier than ever to make the transition to distributed generation. The author briefly reviews the advantages of reciprocating engines and turbine-based generators. He notes that fuel cells, solar, and wind generators are not currently economically viable options. Mercury Electric's conventional turbine systems are illustrated as a potential viable option for self-generation. 2 figs.

  16. Conference on grid integration of renewable energies

    International Nuclear Information System (INIS)

    Fontaine, Pierre; Goeke, Berthold; Mignon, Herve; Brakelmann, Heinrich; Huebner, Gundula; Tanja Schmedes; Remy Garaude Verdier; Pierre-Guy Therond; Werner Diwald

    2012-01-01

    The French-German office for Renewable energies (OFAEnR) organised a conference on grid integration of renewable energies. In the framework of this French-German exchange of experience, about a hundred of participants exchanged views on the similarities and differences between the French and German approaches of renewable energies integration to grids. This document brings together the available presentations (slides) made during this event: 1 - Power grid development - Policy and challenges (Pierre Fontaine); 2 - Grid Development: German Strategy (Berthold Goeke); 3 - Power grids development: situational analysis (Herve Mignon); 4 - Traditional Power Lines, Partial Underground Cabling and HVDC lines: Costs, Benefits and Acceptance (Heinrich Brakelmann); 5 - Transmission Lines - Local Acceptance (Gundula Huebner); 6 - eTelligence- energy meets Intelligence: experience feedback from the grid operator EWe on smart grids and the integration of renewable energies (Tanja Schmedes); 7 - Nice Grid, The French Smart Grid Project within Grid4eU (Remy Garaude Verdier); 8 - Economical Analysis Of energy Storage For Renewable energy Farms - experience of EDF en on the basis of 3 call for tender issued by the French Government in 01/2010, 11/2010, and 09/2011: what conditions for a real deployment (Pierre-Guy Therond); 9 - Hydrogen as a renewable energies storage mean (Werner Diwald)

  17. Smart Grid Risk Management

    Science.gov (United States)

    Abad Lopez, Carlos Adrian

    Current electricity infrastructure is being stressed from several directions -- high demand, unreliable supply, extreme weather conditions, accidents, among others. Infrastructure planners have, traditionally, focused on only the cost of the system; today, resilience and sustainability are increasingly becoming more important. In this dissertation, we develop computational tools for efficiently managing electricity resources to help create a more reliable and sustainable electrical grid. The tools we present in this work will help electric utilities coordinate demand to allow the smooth and large scale integration of renewable sources of energy into traditional grids, as well as provide infrastructure planners and operators in developing countries a framework for making informed planning and control decisions in the presence of uncertainty. Demand-side management is considered as the most viable solution for maintaining grid stability as generation from intermittent renewable sources increases. Demand-side management, particularly demand response (DR) programs that attempt to alter the energy consumption of customers either by using price-based incentives or up-front power interruption contracts, is more cost-effective and sustainable in addressing short-term supply-demand imbalances when compared with the alternative that involves increasing fossil fuel-based fast spinning reserves. An essential step in compensating participating customers and benchmarking the effectiveness of DR programs is to be able to independently detect the load reduction from observed meter data. Electric utilities implementing automated DR programs through direct load control switches are also interested in detecting the reduction in demand to efficiently pinpoint non-functioning devices to reduce maintenance costs. We develop sparse optimization methods for detecting a small change in the demand for electricity of a customer in response to a price change or signal from the utility

  18. Multicriteria Parent Selection Using Cognitive Radio for RPL in Smart Grid Network

    Directory of Open Access Journals (Sweden)

    Adisorn Kheaksong

    2018-01-01

    Full Text Available To maintain reliability of advanced metering infrastructure network in smart grid, data sent from a smart meter must reach a data concentrator unit efficiently. Parent selecting mechanism in routing protocol for low-power and lossy (RPL is a key to maintain the reliability by balancing workload of meters in the network. In this paper, a parent selecting mechanism with three criteria including expected transmission count, residual energy, and expected transmission time is proposed to improve workload balancing and lifetime differences of all meters. A meter selects an immediate parent based on three factors. From simulation results, parents’ workload is better balanced and the lifetime of all meters in the network is depleted nearly at the same time. Moreover, a simulation with cognitive radio enabled meters, where data can be transmitted on a licensed channel opportunistically when the channel is not utilized, shows an improvement in the packet delivery ratio.

  19. Fuel Cell Backup Power System for Grid Service and Micro-Grid in Telecommunication Applications: Preprint

    Energy Technology Data Exchange (ETDEWEB)

    Ma, Zhiwen [National Renewable Energy Laboratory (NREL), Golden, CO (United States); Eichman, Joshua D [National Renewable Energy Laboratory (NREL), Golden, CO (United States); Kurtz, Jennifer M [National Renewable Energy Laboratory (NREL), Golden, CO (United States)

    2018-03-22

    This paper presents the feasibility and economics of using fuel cell backup power systems in telecommunication cell towers to provide grid services (e.g., ancillary services, demand response). The fuel cells are able to provide power for the cell tower during emergency conditions. This study evaluates the strategic integration of clean, efficient, and reliable fuel cell systems with the grid for improved economic benefits. The backup systems have potential as enhanced capability through information exchanges with the power grid to add value as grid services that depend on location and time. The economic analysis has been focused on the potential revenue for distributed telecommunications fuel cell backup units to provide value-added power supply. This paper shows case studies on current fuel cell backup power locations and regional grid service programs. The grid service benefits and system configurations for different operation modes provide opportunities for expanding backup fuel cell applications responsive to grid needs.

  20. Smart Grid Demonstration Project

    Energy Technology Data Exchange (ETDEWEB)

    Miller, Craig [National Rural Electric Cooperative Association, Arlington, VA (United States); Carroll, Paul [National Rural Electric Cooperative Association, Arlington, VA (United States); Bell, Abigail [National Rural Electric Cooperative Association, Arlington, VA (United States)

    2015-03-11

    The National Rural Electric Cooperative Association (NRECA) organized the NRECA-U.S. Department of Energy (DOE) Smart Grid Demonstration Project (DE-OE0000222) to install and study a broad range of advanced smart grid technologies in a demonstration that spanned 23 electric cooperatives in 12 states. More than 205,444 pieces of electronic equipment and more than 100,000 minor items (bracket, labels, mounting hardware, fiber optic cable, etc.) were installed to upgrade and enhance the efficiency, reliability, and resiliency of the power networks at the participating co-ops. The objective of this project was to build a path for other electric utilities, and particularly electrical cooperatives, to adopt emerging smart grid technology when it can improve utility operations, thus advancing the co-ops’ familiarity and comfort with such technology. Specifically, the project executed multiple subprojects employing a range of emerging smart grid technologies to test their cost-effectiveness and, where the technology demonstrated value, provided case studies that will enable other electric utilities—particularly electric cooperatives— to use these technologies. NRECA structured the project according to the following three areas: Demonstration of smart grid technology; Advancement of standards to enable the interoperability of components; and Improvement of grid cyber security. We termed these three areas Technology Deployment Study, Interoperability, and Cyber Security. Although the deployment of technology and studying the demonstration projects at coops accounted for the largest portion of the project budget by far, we see our accomplishments in each of the areas as critical to advancing the smart grid. All project deliverables have been published. Technology Deployment Study: The deliverable was a set of 11 single-topic technical reports in areas related to the listed technologies. Each of these reports has already been submitted to DOE, distributed to co-ops, and

  1. The MammoGrid Project Grids Architecture

    CERN Document Server

    McClatchey, Richard; Hauer, Tamas; Estrella, Florida; Saiz, Pablo; Rogulin, Dmitri; Buncic, Predrag; Clatchey, Richard Mc; Buncic, Predrag; Manset, David; Hauer, Tamas; Estrella, Florida; Saiz, Pablo; Rogulin, Dmitri

    2003-01-01

    The aim of the recently EU-funded MammoGrid project is, in the light of emerging Grid technology, to develop a European-wide database of mammograms that will be used to develop a set of important healthcare applications and investigate the potential of this Grid to support effective co-working between healthcare professionals throughout the EU. The MammoGrid consortium intends to use a Grid model to enable distributed computing that spans national borders. This Grid infrastructure will be used for deploying novel algorithms as software directly developed or enhanced within the project. Using the MammoGrid clinicians will be able to harness the use of massive amounts of medical image data to perform epidemiological studies, advanced image processing, radiographic education and ultimately, tele-diagnosis over communities of medical "virtual organisations". This is achieved through the use of Grid-compliant services [1] for managing (versions of) massively distributed files of mammograms, for handling the distri...

  2. Privacy-Preserving Meter Report Protocol of Isolated Smart Grid Devices

    Directory of Open Access Journals (Sweden)

    Zhiwei Wang

    2017-01-01

    Full Text Available Smart grid aims to improve the reliability, efficiency, and security of the traditional grid, which allows two-way transmission and efficiency-driven response. However, a main concern of this new technique is that the fine-grained metering data may leak the personal privacy information of the customers. Thus, the data aggregation mechanism for privacy protection is required for the meter report protocol in smart grid. In this paper, we propose an efficient privacy-preserving meter report protocol for the isolated smart grid devices. Our protocol consists of an encryption scheme with additively homomorphic property and a linearly homomorphic signature scheme, where the linearly homomorphic signature scheme is suitable for privacy-preserving data aggregation. We also provide security analysis of our protocol in the context of some typical attacks in smart grid. The implementation of our protocol on the Intel Edison platform shows that our protocol is efficient enough for the physical constrained devices, like smart meters.

  3. Development of a model for integrated simulation of the European transmission networks and electricity markets

    International Nuclear Information System (INIS)

    Rathke, Christian

    2013-01-01

    The liberalisation of electricity markets and the increase of renewable energy generation actually causes dramatic changes for the whole European power industry. The transmission system operators in particular have to meet the challenge to ensure a stable and reliable system operation in the future. Significant changes in power generation will require a substantial extension to current inadequate original transmission grids to handle increased wide area power flows. This is the only way to avoid overloading the grid and to reduce the herefrom resulting limitations for the Pan-European cross-border trade of electricity. This work describes in detail the development of a Pan-European integrated grid and an electricity market simulation tool. For this purpose an overview about the today's structure of the European electricity industry is given initially. Afterwards the configuration of the transmission grid, the used equipment and different methods for the load flow and short circuit calculation are explained. Furthermore models for the calculation of local loads and the power plant dispatch are presented in the following chapters. Following on from this a detailed model of the European electricity industry is developed and the main functions are described by means of some exemplary simulations. The simulation tool developed in this work enables the user to calculate realistic power plant schedules and the consequent resulting physical effects on the European transmission grid. It combines a time series based simulation of the electricity market with a detailed model of the transmission grid. The highly detailing of the model offers the feasibility to execute a complete AC load flow calculation using the Newton Raphson algorithm.Therefore it is possible to identify the active as well as the reactive power flows in the grid. The results of the power flow calculation are the basis for further investigations (e. g. the short circuit calculation) and to decide on

  4. Distribution Grid Integration of Photovoltaic Systems in Germany – Implications on Grid Planning and Grid Operation

    International Nuclear Information System (INIS)

    Stetz, Thomas

    2017-01-01

    Photovoltaic is the most dispersed renewable energy source in Germany, typically interconnected to low and medium voltage systems. In recent years, cost-intensive grid reinforcements had to be undertaken all across Germany’s distribution grids in order to increase their hosting capacity for these photovoltaic installations. This paper presents an overview on research results which show that photovoltaic itself can provide ancillary services to reduce its cost of interconnection. Especially the provision of reactive power turned out to be a technically effective and economically efficient method to increase a grid’s hosting capacity for photovoltaic capacity. Different reactive power control methods were investigated, revealing significant differences with regards to their grid operation implications. Business cases for residential-scale photovoltaic applications have shifted from feed-in-tariff based active power feed-in to self-consumption. However, increasing the photovoltaic self-consumption by additional battery-storage systems is still not economically reliable in Germany. (author)

  5. Electric transmission technology

    International Nuclear Information System (INIS)

    Shah, K.R.

    1990-01-01

    Electric transmission technology has matured and can transmit bulk power more reliably and economically than the technology 10 years ago.In 1882, Marcel Depres transmitted 15 kW electric power at 2 kV, using a constant direct current; present transmission voltages have risen to ± 600 kV direct current (DC) and 765 kV alternating current (AC), and it is now possible to transmit bulk electric power at voltages as high as ± 1000 kV DC and 1500 kV AC. Affordable computer systems are now available to optimize transmission reliably. New materials have reduced the bulk of insulation for lines and equipment. New conducting materials and configurations have reduced losses in transmission. Advances in line structures and conductor motion, understanding of flashover characteristics of insulators and air-gaps and electrical performance of lines have resulted in more compact urban transmission lines. (author). 15 refs., 7 tabs., 11 figs

  6. Wireless Sensor Network for Electric Transmission Line Monitoring

    Energy Technology Data Exchange (ETDEWEB)

    Alphenaar, Bruce

    2009-06-30

    Generally, federal agencies tasked to oversee power grid reliability are dependent on data from grid infrastructure owners and operators in order to obtain a basic level of situational awareness. Since there are many owners and operators involved in the day-to-day functioning of the power grid, the task of accessing, aggregating and analyzing grid information from these sources is not a trivial one. Seemingly basic tasks such as synchronizing data timestamps between many different data providers and sources can be difficult as evidenced during the post-event analysis of the August 2003 blackout. In this project we investigate the efficacy and cost effectiveness of deploying a network of wireless power line monitoring devices as a method of independently monitoring key parts of the power grid as a complement to the data which is currently available to federal agencies from grid system operators. Such a network is modeled on proprietary power line monitoring technologies and networks invented, developed and deployed by Genscape, a Louisville, Kentucky based real-time energy information provider. Genscape measures transmission line power flow using measurements of electromagnetic fields under overhead high voltage transmission power lines in the United States and Europe. Opportunities for optimization of the commercial power line monitoring technology were investigated in this project to enable lower power consumption, lower cost and improvements to measurement methodologies. These optimizations were performed in order to better enable the use of wireless transmission line monitors in large network deployments (perhaps covering several thousand power lines) for federal situational awareness needs. Power consumption and cost reduction were addressed by developing a power line monitor using a low power, low cost wireless telemetry platform known as the ''Mote''. Motes were first developed as smart sensor nodes in wireless mesh networking applications

  7. Demagnifying electron projection with grid masks

    International Nuclear Information System (INIS)

    Politycki, A.; Meyer, A.

    1978-01-01

    Tightly toleranced micro- and submicrostructures with smooth edges were realized by using transmission masks with an improved supporting grid (width of traverses 0.8 μm). Local edge shift due to the proximity effect is kept at a minimum. Supporting grids with stil narrower traverses (0.5 μm) were prepared by generating the grid pattern by electron beam writing. Masks of this kind allow projection at a demagnification ratio of 1:4, resulting in large image fields. (orig.) [de

  8. Impact of Investments in Generating Units and Transmission and Distribution Power Grids by 2025 on Voltage Stability and Branches Load in ENERGA SA Operational Territory – Main Findings of Research Project

    Directory of Open Access Journals (Sweden)

    Dominik Falkowski

    2013-03-01

    Full Text Available The article summarizes a research project which was conducted in order to ensure what will be the influence of future investments and changes in the Polish Power System on the stability and functionality of the ENERGA SA distribution grid system. Development of the ENERGA SA distribution grid system was also included. Only stable states were tested for various cases of system load and generation in power plants (the Nuclear Power Plant in Żarnowiec was taken into account and also in wind farms. The system was also tested in N-1 and N-2 states. The result of this study is an overall evaluation of the ENERGA SA distribution grid condition, as well as the identification of potential weak points inside this structure.

  9. Reliability Engineering

    International Nuclear Information System (INIS)

    Lee, Sang Yong

    1992-07-01

    This book is about reliability engineering, which describes definition and importance of reliability, development of reliability engineering, failure rate and failure probability density function about types of it, CFR and index distribution, IFR and normal distribution and Weibull distribution, maintainability and movability, reliability test and reliability assumption in index distribution type, normal distribution type and Weibull distribution type, reliability sampling test, reliability of system, design of reliability and functionality failure analysis by FTA.

  10. Wind and Solar on the Power Grid: Myths and Misperceptions, Greening the Grid (Spanish Version)

    Energy Technology Data Exchange (ETDEWEB)

    Authors: Denholm, Paul; Cochran, Jaquelin; Brancucci Martinez-Anido, Carlo

    2016-04-01

    This is the Spanish version of the 'Greening the Grid - Wind and Solar on the Power Grid: Myths and Misperceptions'. Wind and solar are inherently more variable and uncertain than the traditional dispatchable thermal and hydro generators that have historically provided a majority of grid-supplied electricity. The unique characteristics of variable renewable energy (VRE) resources have resulted in many misperceptions regarding their contribution to a low-cost and reliable power grid. Common areas of concern include: 1) The potential need for increased operating reserves, 2) The impact of variability and uncertainty on operating costs and pollutant emissions of thermal plants, and 3) The technical limits of VRE penetration rates to maintain grid stability and reliability. This fact sheet corrects misperceptions in these areas.

  11. Development of a High Performance Spacer Grid

    Energy Technology Data Exchange (ETDEWEB)

    Song, Kee Nam; Song, K. N.; Yoon, K. H. (and others)

    2007-03-15

    A spacer grid in a LWR fuel assembly is a key structural component to support fuel rods and to enhance the heat transfer from the fuel rod to the coolant. In this research, the main research items are the development of inherent and high performance spacer grid shapes, the establishment of mechanical/structural analysis and test technology, and the set-up of basic test facilities for the spacer grid. The main research areas and results are as follows. 1. 18 different spacer grid candidates have been invented and applied for domestic and US patents. Among the candidates 16 are chosen from the patent. 2. Two kinds of spacer grids are finally selected for the advanced LWR fuel after detailed performance tests on the candidates and commercial spacer grids from a mechanical/structural point of view. According to the test results the features of the selected spacer grids are better than those of the commercial spacer grids. 3. Four kinds of basic test facilities are set up and the relevant test technologies are established. 4. Mechanical/structural analysis models and technology for spacer grid performance are developed and the analysis results are compared with the test results to enhance the reliability of the models.

  12. HVDC grids for offshore and supergrid of the future

    CERN Document Server

    Gomis-Bellmunt, Oriol; Liang, Jun

    2016-01-01

    Presents the advantages, challenges, and technologies of High Voltage Direct Current (HVDC) Grids This book discusses HVDC grids based on multi-terminal voltage-source converters (VSC), which is suitable for the connection of offshore wind farms and a possible solution for a continent wide overlay grid. HVDC Grids: For Offshore and Supergrid of the Future begins by introducing and analyzing the motivations and energy policy drives for developing offshore grids and the European Supergrid. HVDC transmission technology and offshore equipment are described in the second part of the book. The third part of the book discusses how HVDC grids can be developed and integrated in the existing power system. The fourth part of the book focuses on HVDC grid integration, in studies, for different time domains of electric power systems. The book concludes by discussing developments of advanced control methods and control devices for enabling DC grids.

  13. Power Flow Simulations of a More Renewable California Grid Utilizing Wind and Solar Insolation Forecasting

    Science.gov (United States)

    Hart, E. K.; Jacobson, M. Z.; Dvorak, M. J.

    2008-12-01

    Time series power flow analyses of the California electricity grid are performed with extensive addition of intermittent renewable power. The study focuses on the effects of replacing non-renewable and imported (out-of-state) electricity with wind and solar power on the reliability of the transmission grid. Simulations are performed for specific days chosen throughout the year to capture seasonal fluctuations in load, wind, and insolation. Wind farm expansions and new wind farms are proposed based on regional wind resources and time-dependent wind power output is calculated using a meteorological model and the power curves of specific wind turbines. Solar power is incorporated both as centralized and distributed generation. Concentrating solar thermal plants are modeled using local insolation data and the efficiencies of pre-existing plants. Distributed generation from rooftop PV systems is included using regional insolation data, efficiencies of common PV systems, and census data. The additional power output of these technologies offsets power from large natural gas plants and is balanced for the purposes of load matching largely with hydroelectric power and by curtailment when necessary. A quantitative analysis of the effects of this significant shift in the electricity portfolio of the state of California on power availability and transmission line congestion, using a transmission load-flow model, is presented. A sensitivity analysis is also performed to determine the effects of forecasting errors in wind and insolation on load-matching and transmission line congestion.

  14. Smart Grid Status and Metrics Report Appendices

    Energy Technology Data Exchange (ETDEWEB)

    Balducci, Patrick J. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Antonopoulos, Chrissi A. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Clements, Samuel L. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Gorrissen, Willy J. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Kirkham, Harold [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Ruiz, Kathleen A. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Smith, David L. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Weimar, Mark R. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Gardner, Chris [APQC, Houston, TX (United States); Varney, Jeff [APQC, Houston, TX (United States)

    2014-07-01

    A smart grid uses digital power control and communication technology to improve the reliability, security, flexibility, and efficiency of the electric system, from large generation through the delivery systems to electricity consumers and a growing number of distributed generation and storage resources. To convey progress made in achieving the vision of a smart grid, this report uses a set of six characteristics derived from the National Energy Technology Laboratory Modern Grid Strategy. The Smart Grid Status and Metrics Report defines and examines 21 metrics that collectively provide insight into the grid’s capacity to embody these characteristics. This appendix presents papers covering each of the 21 metrics identified in Section 2.1 of the Smart Grid Status and Metrics Report. These metric papers were prepared in advance of the main body of the report and collectively form its informational backbone.

  15. Middleware for the next generation Grid infrastructure

    CERN Document Server

    Laure, E; Prelz, F; Beco, S; Fisher, S; Livny, M; Guy, L; Barroso, M; Buncic, P; Kunszt, Peter Z; Di Meglio, A; Aimar, A; Edlund, A; Groep, D; Pacini, F; Sgaravatto, M; Mulmo, O

    2005-01-01

    The aim of the EGEE (Enabling Grids for E-Science in Europe) project is to create a reliable and dependable European Grid infrastructure for e-Science. The objective of the EGEE Middleware Re-engineering and Integration Research Activity is to provide robust middleware components, deployable on several platforms and operating systems, corresponding to the core Grid services for resource access, data management, information collection, authentication & authorization, resource matchmaking and brokering, and monitoring and accounting. For achieving this objective, we developed an architecture and design of the next generation Grid middleware leveraging experiences and existing components essentially from AliEn, EDG, and VDT. The architecture follows the service breakdown developed by the LCG ARDA group. Our strategy is to do as little original development as possible but rather re-engineer and harden existing Grid services. The evolution of these middleware components towards a Service Oriented Architecture ...

  16. Smart Grids Cyber Security Issues and Challenges

    OpenAIRE

    Imen Aouini; Lamia Ben Azzouz

    2015-01-01

    The energy need is growing rapidly due to the population growth and the large new usage of power. Several works put considerable efforts to make the electricity grid more intelligent to reduce essentially energy consumption and provide efficiency and reliability of power systems. The Smart Grid is a complex architecture that covers critical devices and systems vulnerable to significant attacks. Hence, security is a crucial factor for the success and the wide deployment of...

  17. Grid Integration of Wind Farms

    Science.gov (United States)

    Giæver Tande, John Olav

    2003-07-01

    This article gives an overview of grid integration of wind farms with respect to impact on voltage quality and power system stability. The recommended procedure for assessing the impact of wind turbines on voltage quality in distribution grids is presented. The procedure uses the power quality characteristic data of wind turbines to determine the impact on slow voltage variations, flicker, voltage dips and harmonics. The detailed assessment allows for substantially more wind power in distribution grids compared with previously used rule-of-thumb guidelines. Power system stability is a concern in conjunction with large wind farms or very weak grids. Assessment requires the use of power system simulation tools, and wind farm models for inclusion in such tools are presently being developed. A fixed-speed wind turbine model is described. The model may be considered a good starting point for development of more advanced models, hereunder the concept of variable-speed wind turbines with a doubly fed induction generator is briefly explained. The use of dynamic wind farm models as part of power system simulation tools allows for detailed studies and development of innovative grid integration techniques. It is demonstrated that the use of reactive compensation may relax the short-term voltage stability limit and allow integration of significantly more wind power, and that application of automatic generation control technology may be an efficient means to circumvent thermal transmission capacity constraints. The continuous development of analysis tools and technology for cost-effective and secure grid integration is an important aid to ensure the increasing use of wind energy. A key factor for success, however, is the communication of results and gained experience, and in this regard it is hoped that this article may contribute.

  18. The cost of reliability

    International Nuclear Information System (INIS)

    Ilic, M.

    1998-01-01

    In this article the restructuring process under way in the US power industry is being revisited from the point of view of transmission system provision and reliability was rolled into the average cost of electricity to all, it is not so obvious how is this cost managed in the new industry. A new MIT approach to transmission pricing is here suggested as a possible solution [it

  19. Operational electricity transmission rates

    International Nuclear Information System (INIS)

    Roggen, M.

    1997-01-01

    In a liberalized electricity market both the consumers and the producers of electricity must pay for the use of the power transmission network. Thus, the net manager has unlimited options to realize efficiency improvements. A neutral and transparent management of the power grid is necessary to avoid disturbance of the market. KEMA Consulting translated abstract ideas and strategic advices to operational concepts in its report 'A framework for the determination of tariffs of the transport in the Dutch electricity sector'

  20. Simplified reactive power management strategy for complex power grids under stochastic operation and incomplete information

    DEFF Research Database (Denmark)

    Vlachogiannis, Ioannis (John)

    2009-01-01

    grids is a major issue for system operators. Under these circumstances an online reactive power management strategy with minimum risk concerning all uncertain and stochastic parameters is proposed. Therefore, new concepts such as reactive power-weighted node-to-node linking and reactive power control......In the current released energy market, the large-scale complex transmission networks and the distribution ones with dispersed energy sources and "intelligent" components operate under uncertainties, stochastic and prior incomplete information. A safe and reliable operation of such complex power...... capability are introduced. A distributed and interconnected stochastic learning automata system is implemented to manage, in a unified and unique way, the reactive power in complex power grids with stochastic reactive power demand and detect the vulnerable part. The proposed simplified strategy can also...

  1. Smart Grid Technologies in Europe: An Overview

    Directory of Open Access Journals (Sweden)

    Luca Ardito

    2013-01-01

    Full Text Available The old electricity network infrastructure has proven to be inadequate, with respect to modern challenges such as alternative energy sources, electricity demand and energy saving policies. Moreover, Information and Communication Technologies (ICT seem to have reached an adequate level of reliability and flexibility in order to support a new concept of electricity network — the smart grid. In this work, we will analyse the state-of-the-art of smart grids, in their technical, management, security, and optimization aspects. We will also provide a brief overview of the regulatory aspects involved in the development of a smart grid, mainly from the viewpoint of the European Union.

  2. European electricity grid. Status and perspective

    International Nuclear Information System (INIS)

    Maillard, Dominique

    2010-01-01

    There is no doubt about the need to expand and modernize the European electricity grid, especially in order to allow renewable energies to be fed stochastically into existing systems. As it is hardly possible at the present time and also in the near future to store electricity on a major scale and at adequate prices, electricity must be transmitted from the point of generation to the point of consumption directly and in real time. The development of grid systems, including cross-border transmission systems, is still behind expectations. This is not due to a shortage of projects or a lack of interest on the part of grid operators; the necessary political support is available as well, and investments at present are covered by the feed tariffs. The problem is the lack of acceptance. It is difficult to obtain new permits or commission new grids. This problem of the licensing authorities often results in considerable delays. Consequently, it is up to the grid operators to handle this situation and promote new, intelligent grid systems in an effort to achieve acceptance of a technical-scale infrastructure. This includes transparency in grid expansion, exchange with the public in order to reach mutual understanding and trust and also find compromises as well as the willingness to discuss various approaches to solutions (underground routing, upgrading of existing grid systems, smart systems, and intelligent designs) so as to optimize the use of the existing infrastructure. (orig.)

  3. Fiscal 1999 research result report on energy and environment technology demonstration research support project (International joint demonstration research project). Improvement of long-distant power transmission efficiency and reliability, and its environmental impact assessment; 1999 nendo chokyori soden hoshiki ni kansuru soden koritsu to soden shinraido no kojo oyobi kankyo eno eikyo hyoka seika hokokusho

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2000-03-01

    Japan-Russia international joint research was made on overhead ultrahigh-voltage DC power transmission lines for transmission loss reduction and reliability improvement, and an optimum international power supply cable system, considering energy saving and environment conservation. Using the European-Russian DC power transmission line of {+-}500kV and 4GW as a model, comparison was made between a model using Russian round strands and glass insulators and a model using Japanese low-loss wires and insulators. As for improvement of the reliability in cold districts, Russian design techniques for tower structure and ice loading were reasonable to counteract galloping oscillation and ice load. In evaluation and selection of optimum underground and marine cables, study was made on cable specifications using the Turkey-Russia power transmission route as a model. The environmental assessment result of these cables showed that XLPE cable under development is optimum. (NEDO)

  4. Smart Grid Privacy through Distributed Trust

    Science.gov (United States)

    Lipton, Benjamin

    Though the smart electrical grid promises many advantages in efficiency and reliability, the risks to consumer privacy have impeded its deployment. Researchers have proposed protecting privacy by aggregating user data before it reaches the utility, using techniques of homomorphic encryption to prevent exposure of unaggregated values. However, such schemes generally require users to trust in the correct operation of a single aggregation server. We propose two alternative systems based on secret sharing techniques that distribute this trust among multiple service providers, protecting user privacy against a misbehaving server. We also provide an extensive evaluation of the systems considered, comparing their robustness to privacy compromise, error handling, computational performance, and data transmission costs. We conclude that while all the systems should be computationally feasible on smart meters, the two methods based on secret sharing require much less computation while also providing better protection against corrupted aggregators. Building systems using these techniques could help defend the privacy of electricity customers, as well as customers of other utilities as they move to a more data-driven architecture.

  5. Grid connectivity issues and the importance of GCC. [GCC - Grid Code Compliance

    Energy Technology Data Exchange (ETDEWEB)

    Das, A.; Schwartz, M.-K. [GL Renewable Certification, Malleswaram, Bangalore (India)

    2012-07-01

    In India, the wind energy is concentrated in rural areas with a very high penetration. In these cases, the wind power has an increasing influence on the power quality on the grids. Another aspect is the influence of weak grids on the operation of wind turbines. Hence it becomes very much essential to introduce such a strong grid code which is particularly applicable to wind sector and suitable for Indian environmental grid conditions. This paper focuses on different international grid codes and their requirement with regard to the connection of wind farms to the electric power systems to mitigate the grid connectivity issues. The requirements include the ways to achieve voltage and frequency stability in the grid-tied wind power system. In this paper, comparative overview and analysis of the main grid connecting requirements will be conducted, comprising several national and regional codes from many countries where high wind penetration levels have been achieved or are expected in the future. The objective of these requirements is to provide wind farms with the control and regulation capabilities encountered in conventional power plants and are necessary for the safe, reliable and economic operation of the power system. This paper also provides a brief idea on the Grid Code Compliance (GCC) certification procedure implemented by the leading accredited certifying body like Germanischer Lloyd Renewables Certification (GL RC), who checks the conformity of the wind turbines as per region specific grid codes. (Author)

  6. Designing regulatory frameworks for merchant transmission investments by real options analysis

    International Nuclear Information System (INIS)

    Pringles, Rolando; Olsina, Fernando; Garcés, Francisco

    2014-01-01

    In deregulated electricity markets, the transmission network is a key infrastructure for enabling competition in the generation sector. A deficient expansion of the transmission grid prevents the realization of the benefits in terms of efficiency associated with market mechanisms. Consequently, it is essential to provide clear investment policies and economic signals to attract timely and efficient transmission investments in order to develop the system at minimum cost meeting the requirements of generators and consumers, while keeping adequate levels of service quality and reliability. This paper proposes a modern tool of economic evaluation based on real options analysis that provides the regulator the ability to assess various incentives that would lead transmission investors to make efficient decisions in highly uncertain environments. Real options properly values partially irreversible investment decisions, such as to defer, modify or abandon an investment project in response to the arrival of new information or as uncertainties are resolved. Decisions are evaluated from the point of view of a transmission investor trying to maximize its own profits in the time period set to recover the capital invested. The results allow the study of the behavior of transmission investors regarding their decision making when they have the possibility to manage the option to defer, under different regulatory schemes that encourage the expansion of the transmission system. - Highlights: • Regulatory frameworks for efficient and timely transmission expansions are designed. • Irreversibility and uncertainty of transmission investment is properly accounted for. • Response of network investors to regulatory incentives is quantitatively established

  7. SuperGrid or SmartGrid: Competing strategies for large-scale integration of intermittent renewables?

    International Nuclear Information System (INIS)

    Blarke, Morten B.; Jenkins, Bryan M.

    2013-01-01

    This paper defines and compares two strategies for integrating intermittent renewables: SuperGrid and SmartGrid. While conventional energy policy suggests that these strategies may be implemented alongside each other, the paper identifies significant technological and socio-economic conflicts of interest between the two. The article identifies differences between a domestic strategy for the integration of intermittent renewables, vis-à-vis the SmartGrid, and a cross-system strategy, vis-à-vis the SuperGrid. Policy makers and transmission system operators must understand the need for both strategies to evolve in parallel, but in different territories, or with strategic integration, avoiding for one strategy to undermine the feasibility of the other. A strategic zoning strategy is introduced from which attentive societies as well as the global community stand to benefit. The analysis includes a paradigmatic case study from West Denmark which supports the hypothesis that these strategies are mutually exclusive. The case study shows that increasing cross-system transmission capacity jeopardizes the feasibility of SmartGrid technology investments. A political effort is required for establishing dedicated SmartGrid innovation zones, while also redefining infrastructure to avoid the narrow focus on grids and cables. SmartGrid Investment Trusts could be supported from reallocation of planned transmission grid investments to provide for the equitable development of SmartGrid strategies. - Highlights: • Compares SuperGrid and SmartGrid strategies for integrating intermittent renewables. • Identifies technological and socio-economic conflicts of interest between the two. • Proposes a strategic zoning strategy allowing for both strategies to evolve. • Presents a paradigmatic case study showing that strategies are mutually exclusive. • Proposes dedicated SmartGrid innovation zones and SmartGrid investment trusts

  8. Opportunities and Benefits for Increasing Transmission Capacity between the US Eastern and Western Interconnections

    Science.gov (United States)

    Figueroa-Acevedo, Armando L.

    Historically, the primary justification for building wide-area transmission lines in the US and around the world has been based on reliability and economic criteria. Today, the influence of renewable portfolio standards (RPS), Environmental Protection Agency (EPA) regulations, transmission needs, load diversity, and grid flexibility requirements drives interest in high capacity wide-area transmission. By making use of an optimization model to perform long-term (15 years) co-optimized generation and transmission expansion planning, this work explored the benefits of increasing transmission capacity between the US Eastern and Western Interconnections under different policy and futures assumptions. The model assessed tradeoffs between investments in cross-interconnection HVDC transmission, AC transmission needs within each interconnection, generation investment costs, and operational costs, while satisfying different policy compliance constraints. Operational costs were broken down into the following market products: energy, up-/down regulation reserve, and contingency reserve. In addition, the system operating flexibility requirements were modeled as a function of net-load variability so that the flexibility of the non-wind/non-solar resources increases with increased wind and solar investment. In addition, planning reserve constraints are imposed under the condition that they be deliverable to the load. Thus, the model allows existing and candidate generation resources for both operating reserves and deliverable planning reserves to be shared throughout the interconnections, a feature which significantly drives identification of least-cost investments. This model is used with a 169-bus representation of the North American power grid to design four different high-capacity wide-area transmission infrastructures. Results from this analysis suggest that, under policy that imposes a high-renewable future, the benefits of high capacity transmission between the Eastern and

  9. Parallel grid population

    Science.gov (United States)

    Wald, Ingo; Ize, Santiago

    2015-07-28

    Parallel population of a grid with a plurality of objects using a plurality of processors. One example embodiment is a method for parallel population of a grid with a plurality of objects using a plurality of processors. The method includes a first act of dividing a grid into n distinct grid portions, where n is the number of processors available for populating the grid. The method also includes acts of dividing a plurality of objects into n distinct sets of objects, assigning a distinct set of objects to each processor such that each processor determines by which distinct grid portion(s) each object in its distinct set of objects is at least partially bounded, and assigning a distinct grid portion to each processor such that each processor populates its distinct grid portion with any objects that were previously determined to be at least partially bounded by its distinct grid portion.

  10. Transmission Line Series Compensation for Wind Energy Transmission

    International Nuclear Information System (INIS)

    Palanichamy, C; Wong, Y C

    2015-01-01

    Wind energy has demonstrated to be a clean, copious and absolutely renewable source of energy, and the large penetration of it into the power grid indicates that wind energy is considered an effective means of power generation, Transmission of wind energy from remote locations to load centers necessitates long transmission lines. Series compensation is a proven and economical transmission solution to address system power transfer strength, grid stability, and voltage profile issues of long transmission lines. In this paper, a programmable approach to determine the capacitive reactance of series capacitor and optimum location for its placement to achieve maximum power transfer gas been presented. The respective program with sample solutions has been provided for real-time applications. (paper)

  11. A Guidebook on Grid Interconnection and Islanded Operation of Mini-Grid Power Systems Up to 200 kW

    Energy Technology Data Exchange (ETDEWEB)

    Greacen, Chris [Lawrence Berkeley National Lab. (LBNL), Berkeley, CA (United States); Engel, Richard [Lawrence Berkeley National Lab. (LBNL), Berkeley, CA (United States); Quetchenbach, Thomas [Lawrence Berkeley National Lab. (LBNL), Berkeley, CA (United States)

    2013-04-01

    A Guidebook on Grid Interconnection and Islanded Operation of Mini-Grid Power Systems Up to 200 kW is intended to help meet the widespread need for guidance, standards, and procedures for interconnecting mini-grids with the central electric grid as rural electrification advances in developing countries, bringing these once separate power systems together. The guidebook aims to help owners and operators of renewable energy mini-grids understand the technical options available, safety and reliability issues, and engineering and administrative costs of different choices for grid interconnection. The guidebook is intentionally brief but includes a number of appendices that point the reader to additional resources for indepth information. Not included in the scope of the guidebook are policy concerns about “who pays for what,” how tariffs should be set, or other financial issues that are also paramount when “the little grid connects to the big grid.”

  12. National Offshore Wind Energy Grid Interconnection Study Executive Summary

    Energy Technology Data Exchange (ETDEWEB)

    Daniel, John P. [ABB, Inc., Cary, NC (United States); Liu, Shu [ABB, Inc., Cary, NC (United States); Ibanez, Eduardo [National Renewable Energy Lab. (NREL), Golden, CO (United States); Pennock, Ken [AWS Truepower, Albany, NY (United States); Reed, Gregory [Univ. of Pittsburgh, PA (United States); Hanes, Spencer [Duke Energy, Charlotte, NC (United States)

    2014-07-30

    The National Offshore Wind Energy Grid Interconnection Study (NOWEGIS) considers the availability and potential impacts of interconnecting large amounts of offshore wind energy into the transmission system of the lower 48 contiguous United States.

  13. Service-oriented advanced metering infrastructure for smart grids

    NARCIS (Netherlands)

    Chen, S.; Lukkien, J.J.; Zhang, L.

    2011-01-01

    Advanced Metering Infrastructure (AMI) enables smart grids to involve power consumers in the business process of power generation transmission, distribution and consumption. However, the participant of consumers challenges the current power systems with system integration and cooperation and

  14. Service-oriented advanced metering infrastructure for smart grids

    NARCIS (Netherlands)

    Chen, S.; Lukkien, J.J.; Zhang, L.

    2010-01-01

    Advanced Metering Infrastructure (AMI) enables smart grids to involve power consumers in the business process of power generation, transmission, distribution and consumption. However, the participant of consumers challenges the current power systems with system integration and cooperation and

  15. Yes and no to grid expansion.; Jein zum Netzausbau.

    Energy Technology Data Exchange (ETDEWEB)

    Huebner, Gundula; Pohl, Johannes [Halle-Wittenberg Univ. (Germany). Inst. fuer Psychologie

    2011-09-15

    The construction of new power plants using renewable energy sources necessitates expansion of power transmission grids. Everyone is in agreement about that, but there is disagreement about the details.

  16. National Offshore Wind Energy Grid Interconnection Study Full Report

    Energy Technology Data Exchange (ETDEWEB)

    Daniel, John P. [ABB, Inc., Cary, NC (United States); Liu, Shu [ABB, Inc., Cary, NC (United States); Ibanez, Eduardo [National Renewable Energy Lab. (NREL), Golden, CO (United States); Pennock, Ken [AWS Truepower, Albany, NY (United States); Reed, Gregory [Univ. of Pittsburgh, PA (United States); Hanes, Spencer [Duke Energy, Charlotte, NC (United States)

    2014-07-30

    The National Offshore Wind Energy Grid Interconnection Study (NOWEGIS) considers the availability and potential impacts of interconnecting large amounts of offshore wind energy into the transmission system of the lower 48 contiguous United States.

  17. Pacific Northwest Smart Grid Demonstration Project Technology Performance Report Volume 1: Technology Performance

    Energy Technology Data Exchange (ETDEWEB)

    Melton, Ron [Pacific Northwest National Lab. (PNNL), Richland, WA (United States)

    2015-06-01

    The Pacific Northwest Smart Grid Demonstration (PNWSGD), a $179 million project that was co-funded by the U.S. Department of Energy (DOE) in late 2009, was one of the largest and most comprehensive demonstrations of electricity grid modernization ever completed. The project was one of 16 regional smart grid demonstrations funded by the American Recovery and Reinvestment Act. It was the only demonstration that included multiple states and cooperation from multiple electric utilities, including rural electric co-ops, investor-owned, municipal, and other public utilities. No fewer than 55 unique instantiations of distinct smart grid systems were demonstrated at the projects’ sites. The local objectives for these systems included improved reliability, energy conservation, improved efficiency, and demand responsiveness. The demonstration developed and deployed an innovative transactive system, unique in the world, that coordinated many of the project’s distributed energy resources and demand-responsive components. With the transactive system, additional regional objectives were also addressed, including the mitigation of renewable energy intermittency and the flattening of system load. Using the transactive system, the project coordinated a regional response across the 11 utilities. This region-wide connection from the transmission system down to individual premises equipment was one of the major successes of the project. The project showed that this can be done and assets at the end points can respond dynamically on a wide scale. In principle, a transactive system of this type might eventually help coordinate electricity supply, transmission, distribution, and end uses by distributing mostly automated control responsibilities among the many distributed smart grid domain members and their smart devices.

  18. Smart Grid Communication Technologies in the Brazilian Electrical Sector

    OpenAIRE

    Kühne, Philipp; Hauer, Ines; Styczynski, Zbigniew A.; Fernandes, Rubipiara; Vale, Zita

    2013-01-01

    Intelligent electrical grids can be considered as the next generation of electrical energy transportation. The enormous potential leads to worldwide focus of research on the technology of smart grids. This paper aims to present a review of the Brazilian electricity sector in context with the integration of communication technologies for smart grids. The work gives an overview of the generation, transmission and distribution of electrical energy in the Brazil and a brief summary ...

  19. Replica consistency in a Data Grid

    International Nuclear Information System (INIS)

    Domenici, Andrea; Donno, Flavia; Pucciani, Gianni; Stockinger, Heinz; Stockinger, Kurt

    2004-01-01

    A Data Grid is a wide area computing infrastructure that employs Grid technologies to provide storage capacity and processing power to applications that handle very large quantities of data. Data Grids rely on data replication to achieve better performance and reliability by storing copies of data sets on different Grid nodes. When a data set can be modified by applications, the problem of maintaining consistency among existing copies arises. The consistency problem also concerns metadata, i.e., additional information about application data sets such as indices, directories, or catalogues. This kind of metadata is used both by the applications and by the Grid middleware to manage the data. For instance, the Replica Management Service (the Grid middleware component that controls data replication) uses catalogues to find the replicas of each data set. Such catalogues can also be replicated and their consistency is crucial to the correct operation of the Grid. Therefore, metadata consistency generally poses stricter requirements than data consistency. In this paper we report on the development of a Replica Consistency Service based on the middleware mainly developed by the European Data Grid Project. The paper summarises the main issues in the replica consistency problem, and lays out a high-level architectural design for a Replica Consistency Service. Finally, results from simulations of different consistency models are presented

  20. Wind energy in offshore grids

    Energy Technology Data Exchange (ETDEWEB)

    Schroeder, S.T.

    2013-01-15

    This cumulative PhD thesis deals with wind integration in offshore grids from an economic point of view. It is composed of a generic part and eight papers. As the topic has mostly been analysed with a focus on topology and technical issues until now, market-operational questions in offshore grids and investment implications under different regulatory frameworks are a hitherto underrepresented research field. They are addressed by this thesis. Offshore grids between several countries combine the absorption of wind energy with international power trading. However, the inclusion into an offshore grid affects the economics of an offshore wind park. It is shown that the spot market income is lower if an offshore wind farm is placed in an interconnector and subject to nodal pricing instead of having a national affiliation. Moreover, congestion in the interconnector can prevent the wind farm from correcting its wind forecast errors in a specific onshore balancing group. An analytical approach with a transmission system operator and a wind farm as stakeholders illustrates resulting incentives for strategic behaviour. Depending on the regulatory regime, they may be inclined to announce more or less generation than expected at the closure of the day-ahead spot market. This can lead to a suboptimal utilisation of the infrastructure and associated socio-economic losses. These and possibly undesired reallocative effects between the parties can be avoided if the regulatory regime is adjusted to reflect special characteristics of offshore grids. With an operational real options approach, it is furthermore illustrated how different support schemes and connections to additional countries affect the investment case of an offshore wind farm and the income of the transmission system operator. The investment framework has also been addressed with a policy study about possible combinations of support schemes and international cooperation mechanisms between countries to achieve their

  1. Smart grid security

    CERN Document Server

    Goel, Sanjay; Papakonstantinou, Vagelis; Kloza, Dariusz

    2015-01-01

    This book on smart grid security is meant for a broad audience from managers to technical experts. It highlights security challenges that are faced in the smart grid as we widely deploy it across the landscape. It starts with a brief overview of the smart grid and then discusses some of the reported attacks on the grid. It covers network threats, cyber physical threats, smart metering threats, as well as privacy issues in the smart grid. Along with the threats the book discusses the means to improve smart grid security and the standards that are emerging in the field. The second part of the b

  2. A plan for transmission access and pricing

    International Nuclear Information System (INIS)

    Oldak, M.

    1990-01-01

    The National Rural Electric Cooperative Association (NRECA) believes that while access to the interconnected transmission system (grid) is necessary to provide the most efficient and economical development and use of the bulk power supply system, the grid cannot be unconditionally opened. Additionally, access should be provided only under reasonable terms, conditions, and cost-based compensation, within a framework of joint planning and coordinated operations. NRECA describes here its transmission policy, a coordinated planning and utilization model (CPU)

  3. Digital Grid: Transforming the Electric Power Grid into an Innovation Engine for the United States

    OpenAIRE

    Chakrabortty, Aranya; Huang, Alex

    2017-01-01

    The electric power grid is one of the largest and most complex infrastructures ever built by mankind. Modern civilization depends on it for industry production, human mobility, and comfortable living. However, many critical technologies such as the 60 Hz transformers were developed at the beginning of the 20th century and have changed very little since then.1 The traditional unidirectional power from the generation to the customer through the transmission-distribution grid has also changed no...

  4. Communication, control and security challenges for the smart grid

    CERN Document Server

    Muyeen, SM

    2017-01-01

    The Smart Grid is a modern electricity grid allowing for distributed, renewable intermittent generation, partly owned by consumers. This requires advanced control and communication technologies in order to provide high quality power supply and secure generation, transmission and distribution. This book outlines these emerging technologies.

  5. Control of transformerless MMC-HVDC during asymmetric grid faults

    DEFF Research Database (Denmark)

    Timofejevs, Artjoms; Gamboa, Daniel; Liserre, Marco

    2013-01-01

    Modular multilevel converter (MMC) is the latest converter topology suitable for the transformerless applications in HVDC transmission. HVDC systems are required to remain connected during grid faults, provide grid support and completely decouple the healthy side from the faulty one. The MMC...

  6. Adaptive Data Collection Mechanisms for Smart Monitoring of Distribution Grids

    DEFF Research Database (Denmark)

    Kemal, Mohammed Seifu; Olsen, Rasmus Løvenstein

    2016-01-01

    Smart Grid systems not only transport electric energy but also information which will be active part of the electricity supply system. This has led to the introduction of intelligent components on all layers of the electrical grid in power generation, transmission, distribution and consumption...... in the loop test-bed with power and communication co-simulation for validation purposes....

  7. A transport layer protocol for the future high speed grid computing: SCTP versus fast tcp multihoming

    International Nuclear Information System (INIS)

    Arshad, M.J.; Mian, M.S.

    2010-01-01

    TCP (Transmission Control Protocol) is designed for reliable data transfer on the global Internet today. One of its strong points is its use of flow control algorithm that allows TCP to adjust its congestion window if network congestion is occurred. A number of studies and investigations have confirmed that traditional TCP is not suitable for each and every type of application, for example, bulk data transfer over high speed long distance networks. TCP sustained the time of low-capacity and short-delay networks, however, for numerous factors it cannot be capable to efficiently deal with today's growing technologies (such as wide area Grid computing and optical-fiber networks). This research work surveys the congestion control mechanism of transport protocols, and addresses the different issues involved for transferring the huge data over the future high speed Grid computing and optical-fiber networks. This work also presents the simulations to compare the performance of FAST TCP multihoming with SCTP (Stream Control Transmission Protocol) multihoming in high speed networks. These simulation results show that FAST TCP multihoming achieves bandwidth aggregation efficiently and outperforms SCTP multihoming under a similar network conditions. The survey and simulation results presented in this work reveal that multihoming support into FAST TCP does provide a lot of benefits like redundancy, load-sharing and policy-based routing, which largely improves the whole performance of a network and can meet the increasing demand of the future high-speed network infrastructures (such as in Grid computing). (author)

  8. BC Hydro's smart grid strategy within a global transformation

    Energy Technology Data Exchange (ETDEWEB)

    Zucker, R. [BC Hydro, Vancouver, BC (Canada). Smart Grid Development Program

    2009-07-01

    Electric utilities are now examining methods of ensuring adequate supply and energy security for the future. This presentation discussed BC Hydro's smart grid program within the context of other global automated metering initiatives. Over 60 per cent of the United States' gross domestic product (GDP) is derived from industries and services dependent on electricity. Power outages and interruptions cost the country an estimated $150 billion per year. A more efficient and reliable grid will provide $1.8 trillion in annual additive revenue by 2020. BC Hydro currently has over 1.8 million customers, and is comprised of 41 dam sites, 30 hydro facilities, and 9 thermal units. The utility has over 18,000 km of transmission lines and 56,000 km of distribution lines. The province's energy plan hopes to achieve energy self-sufficiency by 2016, and all new electric generation will be net zero greenhouse gas (GHG) or serve as an offset for GHG emissions. The BC Hydro smart meter program will help to support the utility's conservation program. The smart grid will include fundamental applications for metering, meter data management, distribution automation and management, and substation automation. The foundation of the smart meter system is comprised of IT and telecommunications infrastructure and a circuit topology. Reliability and power quality improvements of 40 per cent are anticipated, as well as significant improvements in energy efficiency and customer service. Smart grid applications are being designed for microgrids and plug-in vehicles. A voltage control system has been designed to allow the real time management of energy flows. It was concluded that smart grid programs will provide significant benefits to utility customers and communities in the province. tabs., figs.

  9. Cyber security issues, challenges and solutions for the emerging smart grid

    Energy Technology Data Exchange (ETDEWEB)

    Westlund, D. [N-Dimension Solutions Inc., Richmond Hill, ON (Canada)

    2007-07-01

    This paper explored the technology and business issues and challenges associated the smart grid's tolerance of physical and cyber security attacks and proposed a framework that provides practical solutions for the electric operator. The 7 characteristics of a smart grid were described. Notably, a smart grid is self healing; supports client equipment and usage behaviour; tolerates physical and cyber security attacks; delivers high-quality power to customers; supports various power generation technologies; supports competitive power markets; and, delivers capital asset optimization while minimizing operational costs. According to the North American Electric Reliability Council (NERC), power capacity will increase by 6 per cent in the United States and 9 per cent in Canada, while the demand for electricity is expected to rise by 19 and 13 per cent respectively. In addition, total transmission miles are projected to increase by less than 7 per cent in the U.S. and by only 3.5 per cent in Canada. A Smart Grid, with distributed monitoring and control, is therefore needed to meet the increased demand. However, the power and energy sectors are targets for cyber attackers. Cyber security in real-time grid operations is a complex matter. Cyber risks include unauthorized access to control systems; interception of control data; attack on system components; interception of monitoring data; intentional and unintentional human intervention; and, impairment to application software. The proposed solution framework is based on a roadmap developed by the United States Homeland Security organization, the United States Department of Energy, and the Canadian Energy Infrastructure Protection Division. NERC reliability standards and framework are also integrated into this framework. The technical aspects of the framework include: ease of use; defence-in-depth characteristics; extensive monitoring within electronic security perimeters; protection of legacy systems; auditing, logging

  10. A virtual laboratory for micro-grid information and communication infrastructures

    OpenAIRE

    Weimer, James; Xu, Yuzhe; Fischione, Carlo; Johansson, Karl Henrik; Ljungberg, Per; Donovan, Craig; Sutor, Ariane; Fahlén, Lennart E.

    2012-01-01

    Testing smart grid information and communication (ICT) infrastructures is imperative to ensure that they meet industry requirements and standards and do not compromise the grid reliability. Within the micro-grid, this requires identifying and testing ICT infrastructures for communication between distributed energy resources, building, substations, etc. To evaluate various ICT infrastructures for micro-grid deployment, this work introduces the Virtual Micro-Grid Laboratory (VMGL) and provides ...

  11. Economic perspectives of risk distribution system asset management : principles of risk valuation of grid investments

    OpenAIRE

    Rud, Linda

    2010-01-01

    A main challenge of the electricity grid company is to target the right level and choice of grid investment, maintenance and renewal. The nature of grid investments poses special challenges in determining the investment cash flow, partly because a main product of the grid investment often is to improve future performance, for example in terms of increased reliability. An essential aspect of valuing grid investments is to address the value of risk. The objective of this report is to apply the ...

  12. Wireless Infrastructure M2M Network For Distributed Power Grid Monitoring.

    Science.gov (United States)

    Gharavi, Hamid; Hu, Bin

    2017-01-01

    With the massive integration of distributed renewable energy sources (RESs) into the power system, the demand for timely and reliable network quality monitoring, control, and fault analysis is rapidly growing. Following the successful deployment of Phasor Measurement Units (PMUs) in transmission systems for power monitoring, a new opportunity to utilize PMU measurement data for power quality assessment in distribution grid systems is emerging. The main problem however, is that a distribution grid system does not normally have the support of an infrastructure network. Therefore, the main objective in this paper is to develop a Machine-to-Machine (M2M) communication network that can support wide ranging sensory data, including high rate synchrophasor data for real-time communication. In particular, we evaluate the suitability of the emerging IEEE 802.11ah standard by exploiting its important features, such as classifying the power grid sensory data into different categories according to their traffic characteristics. For performance evaluation we use our hardware in the loop grid communication network testbed to access the performance of the network.

  13. Modeling and Economic Analysis of Power Grid Operations in a Water Constrained System

    Science.gov (United States)

    Zhou, Z.; Xia, Y.; Veselka, T.; Yan, E.; Betrie, G.; Qiu, F.

    2016-12-01

    The power sector is the largest water user in the United States. Depending on the cooling technology employed at a facility, steam-electric power stations withdrawal and consume large amounts of water for each megawatt hour of electricity generated. The amounts are dependent on many factors, including ambient air and water temperatures, cooling technology, etc. Water demands from most economic sectors are typically highest during summertime. For most systems, this coincides with peak electricity demand and consequently a high demand for thermal power plant cooling water. Supplies however are sometimes limited due to seasonal precipitation fluctuations including sporadic droughts that lead to water scarcity. When this occurs there is an impact on both unit commitments and the real-time dispatch. In this work, we model the cooling efficiency of several different types of thermal power generation technologies as a function of power output level and daily temperature profiles. Unit specific relationships are then integrated in a power grid operational model that minimizes total grid production cost while reliably meeting hourly loads. Grid operation is subject to power plant physical constraints, transmission limitations, water availability and environmental constraints such as power plant water exit temperature limits. The model is applied to a standard IEEE-118 bus system under various water availability scenarios. Results show that water availability has a significant impact on power grid economics.

  14. Grid generation methods

    CERN Document Server

    Liseikin, Vladimir D

    2010-01-01

    This book is an introduction to structured and unstructured grid methods in scientific computing, addressing graduate students, scientists as well as practitioners. Basic local and integral grid quality measures are formulated and new approaches to mesh generation are reviewed. In addition to the content of the successful first edition, a more detailed and practice oriented description of monitor metrics in Beltrami and diffusion equations is given for generating adaptive numerical grids. Also, new techniques developed by the author are presented, in particular a technique based on the inverted form of Beltrami’s partial differential equations with respect to control metrics. This technique allows the generation of adaptive grids for a wide variety of computational physics problems, including grid clustering to given function values and gradients, grid alignment with given vector fields, and combinations thereof. Applications of geometric methods to the analysis of numerical grid behavior as well as grid ge...

  15. 77 FR 26686 - Transmission Planning Reliability Standards

    Science.gov (United States)

    2012-05-07

    ...' stakeholder process including, as discussed below, definition of the process and criteria or guidelines for... review in an open and transparent stakeholder process.'' \\13\\ NERC's proposed footnote `b' states: \\11... stakeholder process that includes addressing stakeholder comments. 7. NERC supplemented the filing on June 7...

  16. 76 FR 66229 - Transmission Planning Reliability Standards

    Science.gov (United States)

    2011-10-26

    ... that definition for review by regulators and other stakeholders, receive comments from regulators and stakeholders requesting a more narrow definition, and explain to the regulators and stakeholders why it is... Demand when ``subject to review in an open and transparent stakeholder process.'' \\16\\ NERC's proposed...

  17. North-east transmission networks : organization and operations

    International Nuclear Information System (INIS)

    Roberge, F.

    2003-01-01

    A review of Quebec's electric power industry was presented along with an outline of non-regulated activity and regulated activities in terms of power generation, transmission, distribution and customer service. Both the transmission and distribution components of Quebec's electric power industry are regulated by the Regie de l'energie. Transmission networks offer access to all wholesalers. Hydro-Quebec TransEnergie was created in 1997 as a functionally independent open access transmission provider with high reliability standards. TransEnergie can address seams issues with neighbouring networks. The three types of services offered in terms of tariffs were also discussed along with data regarding Hydro-Quebec assets, revenue and net income. Hydro-Quebec's relation with the New Brunswick, Ontario, New York and New England were presented along with the issue of congestion and congestion costs. Congestion was defined as an incapacity to deliver energy at low cost because of a limited grid capacity, which results in a need to use more expensive energy. Solutions to decrease congestion include: building new transmission lines; using specialized equipment at existing distribution points; constructing strategically placed power generating stations; reducing the power load; and, increasing network control. The factors that influence investments in transport were also discussed. 1 tab., 9 figs

  18. Models for the modern power grid

    Science.gov (United States)

    Nardelli, Pedro H. J.; Rubido, Nicolas; Wang, Chengwei; Baptista, Murilo S.; Pomalaza-Raez, Carlos; Cardieri, Paulo; Latva-aho, Matti

    2014-10-01

    This article reviews different kinds of models for the electric power grid that can be used to understand the modern power system, the smart grid. From the physical network to abstract energy markets, we identify in the literature different aspects that co-determine the spatio-temporal multilayer dynamics of power system. We start our review by showing how the generation, transmission and distribution characteristics of the traditional power grids are already subject to complex behaviour appearing as a result of the the interplay between dynamics of the nodes and topology, namely synchronisation and cascade effects. When dealing with smart grids, the system complexity increases even more: on top of the physical network of power lines and controllable sources of electricity, the modernisation brings information networks, renewable intermittent generation, market liberalisation, prosumers, among other aspects. In this case, we forecast a dynamical co-evolution of the smart grid and other kind of networked systems that cannot be understood isolated. This review compiles recent results that model electric power grids as complex systems, going beyond pure technological aspects. From this perspective, we then indicate possible ways to incorporate the diverse co-evolving systems into the smart grid model using, for example, network theory and multi-agent simulation.

  19. Chimera Grid Tools

    Science.gov (United States)

    Chan, William M.; Rogers, Stuart E.; Nash, Steven M.; Buning, Pieter G.; Meakin, Robert

    2005-01-01

    Chimera Grid Tools (CGT) is a software package for performing computational fluid dynamics (CFD) analysis utilizing the Chimera-overset-grid method. For modeling flows with viscosity about geometrically complex bodies in relative motion, the Chimera-overset-grid method is among the most computationally cost-effective methods for obtaining accurate aerodynamic results. CGT contains a large collection of tools for generating overset grids, preparing inputs for computer programs that solve equations of flow on the grids, and post-processing of flow-solution data. The tools in CGT include grid editing tools, surface-grid-generation tools, volume-grid-generation tools, utility scripts, configuration scripts, and tools for post-processing (including generation of animated images of flows and calculating forces and moments exerted on affected bodies). One of the tools, denoted OVERGRID, is a graphical user interface (GUI) that serves to visualize the grids and flow solutions and provides central access to many other tools. The GUI facilitates the generation of grids for a new flow-field configuration. Scripts that follow the grid generation process can then be constructed to mostly automate grid generation for similar configurations. CGT is designed for use in conjunction with a computer-aided-design program that provides the geometry description of the bodies, and a flow-solver program.

  20. Bayesian grid matching

    DEFF Research Database (Denmark)

    Hartelius, Karsten; Carstensen, Jens Michael

    2003-01-01

    A method for locating distorted grid structures in images is presented. The method is based on the theories of template matching and Bayesian image restoration. The grid is modeled as a deformable template. Prior knowledge of the grid is described through a Markov random field (MRF) model which r...

  1. The Particle Physics Data Grid. Final Report

    International Nuclear Information System (INIS)

    Livny, Miron

    2002-01-01

    The main objective of the Particle Physics Data Grid (PPDG) project has been to implement and evaluate distributed (Grid-enabled) data access and management technology for current and future particle and nuclear physics experiments. The specific goals of PPDG have been to design, implement, and deploy a Grid-based software infrastructure capable of supporting the data generation, processing and analysis needs common to the physics experiments represented by the participants, and to adapt experiment-specific software to operate in the Grid environment and to exploit this infrastructure. To accomplish these goals, the PPDG focused on the implementation and deployment of several critical services: reliable and efficient file replication service, high-speed data transfer services, multisite file caching and staging service, and reliable and recoverable job management services. The focus of the activity was the job management services and the interplay between these services and distributed data access in a Grid environment. Software was developed to study the interaction between HENP applications and distributed data storage fabric. One key conclusion was the need for a reliable and recoverable tool for managing large collections of interdependent jobs. An attached document provides an overview of the current status of the Directed Acyclic Graph Manager (DAGMan) with its main features and capabilities

  2. GStat 2.0: Grid Information System Status Monitoring

    OpenAIRE

    Field, L; Huang, J; Tsai, M

    2009-01-01

    Grid Information Systems are mission-critical components in today's production grid infrastructures. They enable users, applications and services to discover which services exist in the infrastructure and further information about the service structure and state. It is therefore important that the information system components themselves are functioning correctly and that the information content is reliable. Grid Status (GStat) is a tool that monitors the structural integrity of the EGEE info...

  3. TUX-INTERO: A Portal for secure interoperation of Grids

    OpenAIRE

    Shashi Bhanwar; Seema Bawa

    2010-01-01

    In this paper, we propose TUX-INTERO - a portlet-based Grid portal for integrating existing grid technologies under a common interface and providing reliable services to the users. We have developed a prototype of TUX-INTERO - a grid portal using portlet technology. The paper presents design and development of TUXINTERO. The requirements for the portal, its design and technology choices lead to the utilization of Globus Toolkit as middleware for connecting global resources, SUN N1 GE6 and Con...

  4. 76 FR 7187 - Priorities for Addressing Risks to the Reliability of the Bulk-Power System; Reliability...

    Science.gov (United States)

    2011-02-09

    ..., U.S. House of Representatives. 10:35 a.m. Introductions; Commissioner Cheryl LaFleur, Chair. 10:40 a... protecting against sophisticated and fast-moving threats? What role do you expect Smart Grid to play in the... grid reliability under Smart Grid applications? If not, how should NERC address these issues? c. Will...

  5. A Cloud Associated Smart Grid Admin Dashboard

    Directory of Open Access Journals (Sweden)

    P. Naveen

    2018-02-01

    Full Text Available Intelligent smart grid system undertakes electricity demand in a sustainable, reliable, economical and environmentally friendly manner. As smart grid involves, it has the liability of meeting the changing consumer needs on the day-to-day basis. Modern energy consumers like to vivaciously regulate their consumption patterns more competently and intelligently than current provided ways. To fulfill the consumers’ needs, smart meters and sensors make the grid infrastructure more efficient and resilient in energy data collection and management even with the ever-changing renewable power generation. Though cloud acts as an outlet for the energy consumers to retrieve energy data from the grid, the information systems available are technically constrained and not user-friendly. Hence, a simple technology enabled utility-consumer interactive information system in the form of a dashboard is presented to cater the electric consumer needs.

  6. Grids in Europe - a computing infrastructure for science

    International Nuclear Information System (INIS)

    Kranzlmueller, D.

    2008-01-01

    Grids provide sheer unlimited computing power and access to a variety of resources to todays scientists. Moving from a research topic of computer science to a commodity tool for science and research in general, grid infrastructures are built all around the world. This talk provides an overview of the developments of grids in Europe, the status of the so-called national grid initiatives as well as the efforts towards an integrated European grid infrastructure. The latter, summarized under the title of the European Grid Initiative (EGI), promises a permanent and reliable grid infrastructure and its services in a way similar to research networks today. The talk describes the status of these efforts, the plans for the setup of this pan-European e-Infrastructure, and the benefits for the application communities. (author)

  7. Comprehensive Smart Grid Planning in a Regulated Utility Environment

    Science.gov (United States)

    Turner, Matthew; Liao, Yuan; Du, Yan

    2015-06-01

    This paper presents the tools and exercises used during the Kentucky Smart Grid Roadmap Initiative in a collaborative electric grid planning process involving state regulators, public utilities, academic institutions, and private interest groups. The mandate of the initiative was to assess the existing condition of smart grid deployments in Kentucky, to enhance understanding of smart grid concepts by stakeholders, and to develop a roadmap for the deployment of smart grid technologies by the jurisdictional utilities of Kentucky. Through involvement of many important stakeholder groups, the resultant Smart Grid Deployment Roadmap proposes an aggressive yet achievable strategy and timetable designed to promote enhanced availability, security, efficiency, reliability, affordability, sustainability and safety of the electricity supply throughout the state while maintaining Kentucky's nationally competitive electricity rates. The models and methods developed for this exercise can be utilized as a systematic process for the planning of coordinated smart grid deployments.

  8. SMART FUEL CELL OPERATED RESIDENTIAL MICRO-GRID COMMUNITY

    Energy Technology Data Exchange (ETDEWEB)

    Dr. Mohammad S. Alam (PI/PD)

    2005-04-13

    To build on the work of year one by expanding the smart control algorithm developed to a micro-grid of ten houses; to perform a cost analysis; to evaluate alternate energy sources; to study system reliability; to develop the energy management algorithm, and to perform micro-grid software and hardware simulations.

  9. Macro Protections for Micro Grids

    DEFF Research Database (Denmark)

    Teimourzadeh, Saeed; Aminifar, Farrokh; Davarpanah, Mahdi

    2016-01-01

    economic and environmental benefits for the end customers, utilities, and society. Among those benefits we can include enhancement of reliability and resilience of power delivery systems as well as deferring new investment for bulky generation, transmission, and distribution expansions. Furthermore, DER......The need for cleaner and more efficient electrical power generation along with the limited budget for construction of bulkygeneration and transmission facilities have motivated power system utilities toward deployment of distributed energy resources (DERs). On-site generation by DERs offers various...

  10. Forecasting reliability of transformer populations

    NARCIS (Netherlands)

    Schijndel, van A.; Wetzer, J.; Wouters, P.A.A.F.

    2007-01-01

    The expected replacement wave in the current power grid faces asset managers with challenging questions. Setting up a replacement strategy and planning calls for a forecast of the long term component reliability. For transformers the future failure probability can be predicted based on the ongoing

  11. The Impact of the Topology on Cascading Failures in a Power Grid Model

    NARCIS (Netherlands)

    Koç, Y.; Warnier, M.; Mieghem, P. van; Kooij, R.E.; Brazier, F.M.T.

    2014-01-01

    Cascading failures are one of the main reasons for large scale blackouts in power transmission grids. Secure electrical power supply requires, together with careful operation, a robust design of the electrical power grid topology. Currently, the impact of the topology on grid robustness is mainly

  12. Renewable Energy Zones: Delivering Clean Power to Meet Demand, Greening the Grid

    Energy Technology Data Exchange (ETDEWEB)

    Hurlbut, David; Chernyakhovskiy, Ilya; Cochran, Jaquelin

    2016-05-01

    Greening the Grid provides technical assistance to energy system planners, regulators, and grid operators to overcome challenges associated with integrating variable renewable energy into the grid. This document describes the renewable energy zone concept that has emerged as a transmission planning tool to help scale up the penetration of solar, wind, and other resources on the power system.

  13. Mapping of grid faults and grid codes

    DEFF Research Database (Denmark)

    Iov, Florin; Hansen, A.D.; Sørensen, P.

    loads of wind turbines. The goal is also to clarify and define possible new directions in the certification process of power plant wind turbines, namely wind turbines, which participate actively in the stabilisation of power systems. Practical experience shows that there is a need...... challenges for the design of both the electrical system and the mechanical structure of wind turbines. An overview over the frequency of grid faults and the grid connection requirements in different relevant countries is done in this report. The most relevant study cases for the quantification of the loads......The present report is a part of the research project "Grid fault and design basis for wind turbine" supported by Energinet.dk through the grant PSO F&U 6319. The objective of this project is to investigate into the consequences of the new grid connection requirements for the fatigue and extreme...

  14. Mapping of grid faults and grid codes

    DEFF Research Database (Denmark)

    Iov, F.; Hansen, Anca Daniela; Sørensen, Poul Ejnar

    loads of wind turbines. The goal is also to clarify and define possible new directions in the certification process of power plant wind turbines, namely wind turbines, which participate actively in the stabilisation of power systems. Practical experience shows that there is a need...... challenges for the design of both the electrical system and the mechanical structure of wind turbines. An overview over the frequency of grid faults and the grid connection requirements in different relevant countries is done in this report. The most relevant study cases for the quantification of the loads......The present report is a part of the research project ''Grid fault and designbasis for wind turbine'' supported by Energinet.dk through the grant PSO F&U 6319. The objective of this project is to investigate into the consequences of the new grid connection requirements for the fatigue and extreme...

  15. Synchronization method for grid integrated battery storage systems during asymmetrical grid faults

    Directory of Open Access Journals (Sweden)

    Popadić Bane

    2017-01-01

    Full Text Available This paper aims at presenting a robust and reliable synchronization method for battery storage systems during asymmetrical grid faults. For this purpose, a Matlab/Simulink based model for testing of the power electronic interface between the grid and the battery storage systems has been developed. The synchronization method proposed in the paper is based on the proportional integral resonant controller with the delay signal cancellation. The validity of the synchronization method has been verified using the advanced laboratory station for the control of grid connected distributed energy sources. The proposed synchronization method has eliminated unfavourable components from the estimated grid angular frequency, leading to the more accurate and reliable tracking of the grid voltage vector positive sequence during both the normal operation and the operation during asymmetrical grid faults. [Project of the Serbian Ministry of Education, Science and Technological Development, Grant no. III 042004: Integrated and Interdisciplinary Research entitled: Smart Electricity Distribution Grids Based on Distribution Management System and Distributed Generation

  16. The advanced smart grid edge power driving sustainability

    CERN Document Server

    Carvallo, Andres

    2011-01-01

    Placing emphasis on practical ""how-to"" guidance, this cutting-edge resource provides you with a first-hand, insider's perspective on the advent and evolution of smart grids in the 21st century (smart grid 1.0). You gain a thorough understanding of the building blocks that comprise basic smart grids, including power plant, transmission substation, distribution, and meter automation. Moreover, this forward-looking volume explores the next step of this technology's evolution. It provides a detailed explanation of how an advanced smart grid incorporates demand response with smart appliances and

  17. Smart Grid Interoperability Maturity Model

    Energy Technology Data Exchange (ETDEWEB)

    Widergren, Steven E.; Levinson, Alex; Mater, J.; Drummond, R.

    2010-04-28

    The integration of automation associated with electricity resources (including transmission and distribution automation and demand-side resources operated by end-users) is key to supporting greater efficiencies and incorporating variable renewable resources and electric vehicles into the power system. The integration problems faced by this community are analogous to those faced in the health industry, emergency services, and other complex communities with many stakeholders. To highlight this issue and encourage communication and the development of a smart grid interoperability community, the GridWise Architecture Council (GWAC) created an Interoperability Context-Setting Framework. This "conceptual model" has been helpful to explain the importance of organizational alignment in addition to technical and informational interface specifications for "smart grid" devices and systems. As a next step to building a community sensitive to interoperability, the GWAC is investigating an interoperability maturity model (IMM) based on work done by others to address similar circumstances. The objective is to create a tool or set of tools that encourages a culture of interoperability in this emerging community. The tools would measure status and progress, analyze gaps, and prioritize efforts to improve the situation.

  18. A GridFTP transport driver for Globus XIO

    International Nuclear Information System (INIS)

    Kettimuthu, R.; Wantao, L.; Link, J.; Bresnahan, J.

    2008-01-01

    GridFTP is a high-performance, reliable data transfer protocol optimized for high-bandwidth wide-area networks. Based on the Internet FTP protocol, it defines extensions for high-performance operation and security. The Globus implementation of GridFTP provides a modular and extensible data transfer system architecture suitable for wide area and high-performance environments. GridFTP is the de facto standard in projects requiring secure, robust, high-speed bulk data transport. For example, the high energy physics community is basing its entire tiered data movement infrastructure for the Large Hadron Collider computing Grid on GridFTP; the Laser Interferometer Gravitational Wave Observatory routinely uses GridFTP to move 1 TB a day during production runs; and GridFTP is the recommended data transfer mechanism to maximize data transfer rates on the TeraGrid. Commonly used GridFTP clients include globus-url-copy, uberftp, and the Globus Reliable File Transfer service. In this paper, we present a Globus XIO based client to GridFTP that provides a simple Open/Close/Read/Write (OCRW) interface to the users. Such a client greatly eases the addition of GridFTP support to third-party programs, such as SRB and MPICH-G2. Further, this client provides an easier and familiar interface for applications to efficiently access remote files. We compare the performance of this client with that of globus-url-copy on multiple endpoints in the TeraGrid infrastructure. We perform both memory-to-memory and disk-to-disk transfers and show that the performance of this OCRW client is comparable to that of globus-url-copy. We also show that our GridFTP client significantly outperforms the GPFS WAN on the TeraGrid.

  19. A multi-objective framework for dynamic transmission expansion planning in competitive electricity market

    International Nuclear Information System (INIS)

    Foroud, Asghar Akbari; Abdoos, Ali Akbar; Keypour, Reza; Amirahmadi, Meisam

    2010-01-01

    Restructuring of power system has changed the traditional planning objectives and introduced challenges in the field of Transmission Expansion Planning (TEP). Due to these changes, new approaches and criteria are needed for transmission planning in deregulated environment. Therefore, in this paper, a dynamic expansion methodology is presented using a multi-objective optimization framework. Investment cost, congestion cost and reliability are considered in the optimization as three objectives. To overcome the difficulties in solving the non-convex and mixed integer nature of the optimization problems, a Non-Dominated Sorting Genetic Algorithm (NSGA II) approach is used followed by a fuzzy decision making analysis to obtain the final optimal solution. The planning methodology has been demonstrated on the IEEE 24-bus test system and north-east of Iran national 400 kV transmission grid to show the feasibility and capabilities of the proposed algorithm in electricity market environment. (author)

  20. Transmission tariffs - Principles, structure, aims and demands

    International Nuclear Information System (INIS)

    Groenli, Helle; Sand, Kjell

    1997-11-01

    The report deals with several optimization techniques for increasing the efficiency of electric grid operation in Norway. Methods and tools used for the determination of transmission costs are discussed such as partial transmission tariffs and Ramsey-pricing etc. 7 refs., 13 figs., 6 tabs

  1. SuperGrid or SmartGrid: Competing strategies for large-scale integration of intermittent renewables?

    DEFF Research Database (Denmark)

    Blarke, Morten; M. Jenkins, Bryan

    2013-01-01

    This paper defines and compares two strategies for integrating intermittent renewables: SuperGrid and SmartGrid. While conventional energy policy suggests that these strategies may be implemented alongside each other, the paper identifies significant technological and socio-economic conflicts...... of interest between the two. The article identifies differences between a domestic strategy for the integration of intermittent renewables, vis-à-vis the SmartGrid, and a cross-system strategy, vis-à-vis the SuperGrid. Policy makers and transmission system operators must understand the need for both...... a paradigmatic case study from West Denmark which supports the hypothesis that these strategies are mutually exclusive. The case study shows that increasing cross-system transmission capacity jeopardizes the feasibility of SmartGrid technology investments. A political effort is required for establishing...

  2. Alternative approaches to transmission investment

    Energy Technology Data Exchange (ETDEWEB)

    Welch, J.L. [International Transmission Co., Detroit, MI (United States)

    2004-07-01

    The International Transmission Company (ITC) is an independent power transmission company that owns, operates and maintains the high voltage transmission system in southeastern Michigan. The company's current focus is on investing in the transmission infrastructure to improve reliability, relieve congestion, improve access to generation and reduce energy costs for consumers. There is a need for investment in power transmission. Trends indicate that power transactions are on the rise while transmission investment is lagging because pricing protocols are inadequate and there is no regional tariff mechanism to allocate the benefits of new investment. The presentation reviewed the applicability of FTRs to transmission owners and the pitfalls of participant funding pricing. It also outlined the regional benefit allocation mechanism (RBAM) with an illustrative example. It was concluded that existing pricing policies must be improved to address the growing need for transmission investment. RBAM is needed to help investors recover costs from project beneficiaries. figs.

  3. Grid-Tied Photovoltaic Power System

    Science.gov (United States)

    Eichenberg, Dennis J.

    2011-01-01

    A grid-tied photovoltaic (PV) power system is connected directly to the utility distribution grid. Facility power can be obtained from the utility system as normal. The PV system is synchronized with the utility system to provide power for the facility, and excess power is provided to the utility. Operating costs of a PV power system are low compared to conventional power technologies. This method can displace the highest-cost electricity during times of peak demand in most climatic regions, and thus reduce grid loading. Net metering is often used, in which independent power producers such as PV power systems are connected to the utility grid via the customers main service panels and meters. When the PV power system is generating more power than required at that location, the excess power is provided to the utility grid. The customer pays the net of the power purchased when the on-site power demand is greater than the onsite power production, and the excess power is returned to the utility grid. Power generated by the PV system reduces utility demand, and the surplus power aids the community. Modern PV panels are readily available, reliable, efficient, and economical, with a life expectancy of at least 25 years. Modern electronics have been the enabling technology behind grid-tied power systems, making them safe, reliable, efficient, and economical with a life expectancy equal to the modern PV panels. The grid-tied PV power system was successfully designed and developed, and this served to validate the basic principles developed, and the theoretical work that was performed. Grid-tied PV power systems are reliable, maintenance- free, long-life power systems, and are of significant value to NASA and the community. Of particular value are the analytical tools and capabilities that have been successfully developed. Performance predictions can be made confidently for grid-tied PV systems of various scales. The work was done under the NASA Hybrid Power Management (HPM

  4. Smart Grid Development: Multinational Demo Project Analysis

    Directory of Open Access Journals (Sweden)

    Oleinikova I.

    2016-12-01

    Full Text Available This paper analyses demand side management (DSM projects and stakeholders’ experience with the aim to develop, promote and adapt smart grid tehnologies in Latvia. The research aims at identifying possible system service posibilites, including demand response (DR and determining the appropriate market design for such type of services to be implemented at the Baltic power system level, with the cooperation of distribution system operator (DSO and transmission system operator (TSO. This paper is prepared as an extract from the global smart grid best practices, smart solutions and business models.

  5. Smart Grid Development: Multinational Demo Project Analysis

    Science.gov (United States)

    Oleinikova, I.; Mutule, A.; Obushevs, A.; Antoskovs, N.

    2016-12-01

    This paper analyses demand side management (DSM) projects and stakeholders' experience with the aim to develop, promote and adapt smart grid tehnologies in Latvia. The research aims at identifying possible system service posibilites, including demand response (DR) and determining the appropriate market design for such type of services to be implemented at the Baltic power system level, with the cooperation of distribution system operator (DSO) and transmission system operator (TSO). This paper is prepared as an extract from the global smart grid best practices, smart solutions and business models.

  6. Initial results of local grid control using wind farms with grid support

    Energy Technology Data Exchange (ETDEWEB)

    Soerensen, Poul; Hansen, Anca D.; Iov, F.; Blaabjerg, F.

    2005-09-01

    This report describes initial results with simulation of local grid control using wind farms with grid support. The focus is on simulation of the behaviour of the wind farms when they are isolated from the main grid and establish a local grid together with a few other grid components. The isolated subsystems used in the work presented in this report do not intend to simulate a specific subsystem, but they are extremely simplified single bus bar systems using only a few more components than the wind farm. This approach has been applied to make it easier to understand the dynamics of the subsystem. The main observation is that the fast dynamics of the wind turbines seem to be able to contribute significantly to the grid control, which can be useful where the wind farm is isolated with a subsystem from the main grid with surplus of generation. Thus, the fast down regulation of the wind farm using automatic frequency control can keep the subsystem in operation and thereby improve the reliability of the grid. (LN)

  7. Neuroglial Transmission

    DEFF Research Database (Denmark)

    Gundersen, Vidar; Storm-Mathisen, Jon; Bergersen, Linda Hildegard

    2015-01-01

    as a signaling substance recently shown to act on specific lactate receptors in the brain. Complementing neurotransmission at a synapse, neuroglial transmission often implies diffusion of the transmitter over a longer distance and concurs with the concept of volume transmission. Transmission from glia modulates...... synaptic neurotransmission based on energetic and other local conditions in a volume of tissue surrounding the individual synapse. Neuroglial transmission appears to contribute significantly to brain functions such as memory, as well as to prevalent neuropathologies....

  8. Business Cases for Microgrids: Modeling Interactions of Technology Choice, Reliability, Cost, and Benefit

    Science.gov (United States)

    Hanna, Ryan

    Distributed energy resources (DERs), and increasingly microgrids, are becoming an integral part of modern distribution systems. Interest in microgrids--which are insular and autonomous power networks embedded within the bulk grid--stems largely from the vast array of flexibilities and benefits they can offer stakeholders. Managed well, they can improve grid reliability and resiliency, increase end-use energy efficiency by coupling electric and thermal loads, reduce transmission losses by generating power locally, and may reduce system-wide emissions, among many others. Whether these public benefits are realized, however, depends on whether private firms see a "business case", or private value, in investing. To this end, firms need models that evaluate costs, benefits, risks, and assumptions that underlie decisions to invest. The objectives of this dissertation are to assess the business case for microgrids that provide what industry analysts forecast as two primary drivers of market growth--that of providing energy services (similar to an electric utility) as well as reliability service to customers within. Prototypical first adopters are modeled--using an existing model to analyze energy services and a new model that couples that analysis with one of reliability--to explore interactions between technology choice, reliability, costs, and benefits. The new model has a bi-level hierarchy; it uses heuristic optimization to select and size DERs and analytical optimization to schedule them. It further embeds Monte Carlo simulation to evaluate reliability as well as regression models for customer damage functions to monetize reliability. It provides least-cost microgrid configurations for utility customers who seek to reduce interruption and operating costs. Lastly, the model is used to explore the impact of such adoption on system-wide greenhouse gas emissions in California. Results indicate that there are, at present, co-benefits for emissions reductions when customers

  9. Quality Assurance Framework for Mini-Grids

    Energy Technology Data Exchange (ETDEWEB)

    Baring-Gould, Ian [National Renewable Energy Lab. (NREL), Golden, CO (United States); Burman, Kari [National Renewable Energy Lab. (NREL), Golden, CO (United States); Singh, Mohit [National Renewable Energy Lab. (NREL), Golden, CO (United States); Esterly, Sean [National Renewable Energy Lab. (NREL), Golden, CO (United States); Mutiso, Rose [US Department of Energy, Washington, DC (United States); McGregor, Caroline [US Department of Energy, Washington, DC (United States)

    2016-11-01

    Providing clean and affordable energy services to the more than 1 billion people globally who lack access to electricity is a critical driver for poverty reduction, economic development, improved health, and social outcomes. More than 84% of populations without electricity are located in rural areas where traditional grid extension may not be cost-effective; therefore, distributed energy solutions such as mini-grids are critical. To address some of the root challenges of providing safe, quality, and financially viable mini-grid power systems to remote customers, the U.S. Department of Energy (DOE) teamed with the National Renewable Energy Laboratory (NREL) to develop a Quality Assurance Framework (QAF) for isolated mini-grids. The QAF for mini-grids aims to address some root challenges of providing safe, quality, and affordable power to remote customers via financially viable mini-grids through two key components: (1) Levels of service: Defines a standard set of tiers of end-user service and links them to technical parameters of power quality, power availability, and power reliability. These levels of service span the entire energy ladder, from basic energy service to high-quality, high-reliability, and high-availability service (often considered 'grid parity'); (2) Accountability and performance reporting framework: Provides a clear process of validating power delivery by providing trusted information to customers, funders, and/or regulators. The performance reporting protocol can also serve as a robust monitoring and evaluation tool for mini-grid operators and funding organizations. The QAF will provide a flexible alternative to rigid top-down standards for mini-grids in energy access contexts, outlining tiers of end-user service and linking them to relevant technical parameters. In addition, data generated through implementation of the QAF will provide the foundation for comparisons across projects, assessment of impacts, and greater confidence that

  10. Software reliability

    CERN Document Server

    Bendell, A

    1986-01-01

    Software Reliability reviews some fundamental issues of software reliability as well as the techniques, models, and metrics used to predict the reliability of software. Topics covered include fault avoidance, fault removal, and fault tolerance, along with statistical methods for the objective assessment of predictive accuracy. Development cost models and life-cycle cost models are also discussed. This book is divided into eight sections and begins with a chapter on adaptive modeling used to predict software reliability, followed by a discussion on failure rate in software reliability growth mo

  11. LHC computing grid

    International Nuclear Information System (INIS)

    Novaes, Sergio

    2011-01-01

    Full text: We give an overview of the grid computing initiatives in the Americas. High-Energy Physics has played a very important role in the development of grid computing in the world and in Latin America it has not been different. Lately, the grid concept has expanded its reach across all branches of e-Science, and we have witnessed the birth of the first nationwide infrastructures and its use in the private sector. (author)

  12. High density grids

    Energy Technology Data Exchange (ETDEWEB)

    Cohen, Aina E.; Baxter, Elizabeth L.

    2018-01-16

    An X-ray data collection grid device is provided that includes a magnetic base that is compatible with robotic sample mounting systems used at synchrotron beamlines, a grid element fixedly attached to the magnetic base, where the grid element includes at least one sealable sample window disposed through a planar synchrotron-compatible material, where the planar synchrotron-compatible material includes at least one automated X-ray positioning and fluid handling robot fiducial mark.

  13. Micro grids toward the smart grid

    International Nuclear Information System (INIS)

    Guerrero, J.

    2011-01-01

    Worldwide electrical grids are expecting to become smarter in the near future, with interest in Microgrids likely to grow. A microgrid can be defined as a part of the grid with elements of prime energy movers, power electronics converters, distributed energy storage systems and local loads, that can operate autonomously but also interacting with main grid. Thus, the ability of intelligent Microgrids to operate in island mode or connected to the grid will be a keypoint to cope with new functionalities and the integration of renewable energy resources. The functionalities expected for these small grids are: black start operation, frequency and voltage stability, active and reactive power flow control, active power filter capabilities, and storage energy management. In this presentation, a review of the main concepts related to flexible Microgrids will be introduced, with examples of real Microgrids. AC and DC Microgrids to integrate renewable and distributed energy resources will also be presented, as well as distributed energy storage systems, and standardization issues of these Microgrids. Finally, Microgrid hierarchical control will be analyzed looking at three different levels: i) a primary control based on the droop method, including an output impedance virtual loop; ii) a secondary control, which enables restoring any deviations produced by the primary control; and iii) a tertiary control to manage the power flow between the microgrid and the external electrical distribution system.

  14. Power management and frequency regulation for microgrid and smart grid: A real-time demand response approach

    Science.gov (United States)

    Pourmousavi Kani, Seyyed Ali

    Future power systems (known as smart grid) will experience a high penetration level of variable distributed energy resources to bring abundant, affordable, clean, efficient, and reliable electric power to all consumers. However, it might suffer from the uncertain and variable nature of these generations in terms of reliability and especially providing required balancing reserves. In the current power system structure, balancing reserves (provided by spinning and non-spinning power generation units) usually are provided by conventional fossil-fueled power plants. However, such power plants are not the favorite option for the smart grid because of their low efficiency, high amount of emissions, and expensive capital investments on transmission and distribution facilities, to name a few. Providing regulation services in the presence of variable distributed energy resources would be even more difficult for islanded microgrids. The impact and effectiveness of demand response are still not clear at the distribution and transmission levels. In other words, there is no solid research reported in the literature on the evaluation of the impact of DR on power system dynamic performance. In order to address these issues, a real-time demand response approach along with real-time power management (specifically for microgrids) is proposed in this research. The real-time demand response solution is utilized at the transmission (through load-frequency control model) and distribution level (both in the islanded and grid-tied modes) to provide effective and fast regulation services for the stable operation of the power system. Then, multiple real-time power management algorithms for grid-tied and islanded microgrids are proposed to economically and effectively operate microgrids. Extensive dynamic modeling of generation, storage, and load as well as different controller design are considered and developed throughout this research to provide appropriate models and simulation

  15. Note: Laser-cut molybdenum grids for a retarding field energy analyzer

    Science.gov (United States)

    Landheer, K.; Kobelev, A. A.; Smirnov, A. S.; Bosman, J.; Deelen, S.; Rossewij, M.; de Waal, A. C.; Poulios, I.; Benschop, A. F.; Schropp, R. E. I.; Rath, J. K.

    2017-06-01

    A retarding field energy analyzer (RFEA) with grids created by laser-cutting a honeycomb mesh in a 50 μm thick molybdenum foil is presented. The flat grids span an area of 1 cm2 and have high transmission (20 μm wide walls between 150 μm wide meshes). The molybdenum grids were tested in a 3-grid RFEA configuration with an analyzer depth of 0.87 mm.

  16. Integration of HTS Cables in the Future Grid of the Netherlands

    OpenAIRE

    Zuijderduin, R.; Chevchenko, O.; Smit, J.J.; Aanhaanen, G.; Melnik, I.; Geschiere, A.

    2012-01-01

    ue to increasing power demand, the electricity grid of the Netherlands is changing. The future transmission grid will obtain electrical power generated by decentralized renewable sources, together with large scale generation units located at the coastal region. In this way electrical power has to be distributed and transmitted over longer distances from generation to end user. Potential grid issues like: amount of distributed power, grid stability and electrical loss dissipation merit particu...

  17. Simulation For Synchronization Of A Micro-Grid With Three-Phase Systems

    Directory of Open Access Journals (Sweden)

    Mohammad Jafari Far

    2015-08-01

    Full Text Available Abstract today due to the high reliability of the micro-grids they have developed significantly. They have two states of operation the island state and connection to the main grid. Under certain circumstances the micro-grid is connected to or disconnected from the network. Synchronization of a micro-grid with the network must be done when its voltage is synchronized with the voltage in the main grid. Phase lock loops are responsible to identify the voltage phase of the micro-gird and the main grid and when these two voltages are in the same phase they connect the micro-grid to the main grid. In this research the connection of a micro-grid to the main grid in the two phases of synchronous and asynchronous voltage is simulated and investigated.

  18. Challenges facing production grids

    Energy Technology Data Exchange (ETDEWEB)

    Pordes, Ruth; /Fermilab

    2007-06-01

    Today's global communities of users expect quality of service from distributed Grid systems equivalent to that their local data centers. This must be coupled to ubiquitous access to the ensemble of processing and storage resources across multiple Grid infrastructures. We are still facing significant challenges in meeting these expectations, especially in the underlying security, a sustainable and successful economic model, and smoothing the boundaries between administrative and technical domains. Using the Open Science Grid as an example, I examine the status and challenges of Grids operating in production today.

  19. 76 FR 16277 - System Restoration Reliability Standards

    Science.gov (United States)

    2011-03-23

    ... electric system. Blackstart units are essential to restart generation and restore power to the grid in the... Standard EOP-007-0. \\2\\ Mandatory Reliability Standards for the Bulk-Power System, Order No. 693, 72 FR... = $5,894,624. Title: Mandatory Reliability Standards for the Bulk-Power System. Action: FERC 725A...

  20. Solar activity and economic fundamentals: Evidence from 12 geographically disparate power grids

    Science.gov (United States)

    Forbes, Kevin F.; St. Cyr, O. C.

    2008-10-01

    This study uses local (ground-based) magnetometer data as a proxy for geomagnetically induced currents (GICs) to address whether there is a space weather/electricity market relationship in 12 geographically disparate power grids: Eirgrid, the power grid that serves the Republic of Ireland; Scottish and Southern Electricity, the power grid that served northern Scotland until April 2005; Scottish Power, the power grid that served southern Scotland until April 2005; the power grid that serves the Czech Republic; E.ON Netz, the transmission system operator in central Germany; the power grid in England and Wales; the power grid in New Zealand; the power grid that serves the vast proportion of the population in Australia; ISO New England, the power grid that serves New England; PJM, a power grid that over the sample period served all or parts of Delaware, Maryland, New Jersey, Ohio, Pennsylvania, Virginia, West Virginia, and the District of Columbia; NYISO, the power grid that serves New York State; and the power grid in the Netherlands. This study tests the hypothesis that GIC levels (proxied by the time variation of local magnetic field measurements (dH/dt)) and electricity grid conditions are related using Pearson's chi-squared statistic. The metrics of power grid conditions include measures of electricity market imbalances, energy losses, congestion costs, and actions by system operators to restore grid stability. The results of the analysis indicate that real-time market conditions in these power grids are statistically related with the GIC proxy.

  1. Smart grid cyber security for Europe

    International Nuclear Information System (INIS)

    Pearson, Ivan L.G.

    2011-01-01

    In Europe, environmental and economic considerations are driving a revolution in power transmission and distribution. Specifically of interest to this paper, utility companies are increasingly using information and communication technology (ICT) to increase the efficiency and reliability of the grid, as well as to incorporate smaller-scale sources of intermittent wind and solar power into our electricity supply. This should have a positive effect on Europe's energy policy objectives. However, developments in the field of international security have made clear that increased reliance on ICT within the electricity sector will create new vulnerabilities that may undermine these gains. This paper argues that the European Union (EU) has the opportunity to mitigate these vulnerabilities by virtue of its strengthening regulatory position in the European market, and its record of promoting energy technology research. However, the organization will need to act now in recognizing that cyber security as an essential dimension of its energy policy. This paper recommends that the Commission acts now to appoint a coordinator to accelerate the adoption of sensitive institutional changes in this vein. It also suggests that the EU would benefit from cooperation with the United States-a country with strong cyber capabilities that would complement the European program. - Highlights: → Increased reliance on ICT has created new challenges in Europe's electricity sector.→ The European Union has the opportunity to mitigate these.→ The Union must acts now to prevent a potentially costly technological lock-in.→ It should designate a coordinator to drive through necessary legislative reforms.→ The United States would be a good international partner on the issue.

  2. Smart grid cyber security for Europe

    Energy Technology Data Exchange (ETDEWEB)

    Pearson, Ivan L.G., E-mail: ivan.pearson@ec.europa.eu [F03 - Energy Security Unit (ESU), European Commission, Joint Research Centre, Institute for Energy (Netherlands)

    2011-09-15

    In Europe, environmental and economic considerations are driving a revolution in power transmission and distribution. Specifically of interest to this paper, utility companies are increasingly using information and communication technology (ICT) to increase the efficiency and reliability of the grid, as well as to incorporate smaller-scale sources of intermittent wind and solar power into our electricity supply. This should have a positive effect on Europe's energy policy objectives. However, developments in the field of international security have made clear that increased reliance on ICT within the electricity sector will create new vulnerabilities that may undermine these gains. This paper argues that the European Union (EU) has the opportunity to mitigate these vulnerabilities by virtue of its strengthening regulatory position in the European market, and its record of promoting energy technology research. However, the organization will need to act now in recognizing that cyber security as an essential dimension of its energy policy. This paper recommends that the Commission acts now to appoint a coordinator to accelerate the adoption of sensitive institutional changes in this vein. It also suggests that the EU would benefit from cooperation with the United States-a country with strong cyber capabilities that would complement the European program. - Highlights: > Increased reliance on ICT has created new challenges in Europe's electricity sector.> The European Union has the opportunity to mitigate these.> The Union must acts now to prevent a potentially costly technological lock-in.> It should designate a coordinator to drive through necessary legislative reforms.> The United States would be a good international partner on the issue.

  3. A comprehensive WSN-based approach to efficiently manage a Smart Grid.

    Science.gov (United States)

    Martinez-Sandoval, Ruben; Garcia-Sanchez, Antonio-Javier; Garcia-Sanchez, Felipe; Garcia-Haro, Joan; Flynn, David

    2014-10-10

    The Smart Grid (SG) is conceived as the evolution of the current electrical grid representing a big leap in terms of efficiency, reliability and flexibility compared to today's electrical network. To achieve this goal, the Wireless Sensor Networks (WSNs) are considered by the scientific/engineering community to be one of the most suitable technologies to apply SG technology to due to their low-cost, collaborative and long-standing nature. However, the SG has posed significant challenges to utility operators-mainly very harsh radio propagation conditions and the lack of appropriate systems to empower WSN devices-making most of the commercial widespread solutions inadequate. In this context, and as a main contribution, we have designed a comprehensive ad-hoc WSN-based solution for the Smart Grid (SENSED-SG) that focuses on specific implementations of the MAC, the network and the application layers to attain maximum performance and to successfully deal with any arising hurdles. Our approach has been exhaustively evaluated by computer simulations and mathematical analysis, as well as validation within real test-beds deployed in controlled environments. In particular, these test-beds cover two of the main scenarios found in a SG; on one hand, an indoor electrical substation environment, implemented in a High Voltage AC/DC laboratory, and, on the other hand, an outdoor case, deployed in the Transmission and Distribution segment of a power grid. The results obtained show that SENSED-SG performs better and is more suitable for the Smart Grid than the popular ZigBee WSN approach.

  4. The North Seas Countries' Offshore Grid Initiative. Initial Findings. Final Report. Working Group 1 - Grid Configuration

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2012-11-15

    This report focuses on the tasks and results from Working Group 1 (WG1), grid configuration and integration, chaired jointly by representatives from Denmark and the Netherlands. The methodology, assumptions concerning generation portfolio, load situation, available technology and results are presented. This report presents the WG1 Offshore Grid Study that supports the North Seas Countries' Offshore Grid Initiative (NSCOGI) final report. The information contained in this report aims to evaluate the long-term development of an offshore grid structure in the North Seas by providing a view on how such a grid may possibly develop in the future, based on the assumptions made for this study. The report aims to compare and evaluate the possible advantages and disadvantages of the long term development of an optimised, integrated (or meshed) offshore grid in the North Seas by providing a view of how that possible grid might develop in the future against changes to the electricity energy requirements. To evaluate basic variants, different transmission design topologies (radial and meshed) were compared and analysed with respect to various aspects, such as cost/benefits, import and export levels and the systems' CO2 emissions.

  5. Human reliability

    International Nuclear Information System (INIS)

    Embrey, D.E.

    1987-01-01

    Concepts and techniques of human reliability have been developed and are used mostly in probabilistic risk assessment. For this, the major application of human reliability assessment has been to identify the human errors which have a significant effect on the overall safety of the system and to quantify the probability of their occurrence. Some of the major issues within human reliability studies are reviewed and it is shown how these are applied to the assessment of human failures in systems. This is done under the following headings; models of human performance used in human reliability assessment, the nature of human error, classification of errors in man-machine systems, practical aspects, human reliability modelling in complex situations, quantification and examination of human reliability, judgement based approaches, holistic techniques and decision analytic approaches. (UK)

  6. Reliability Calculations

    DEFF Research Database (Denmark)

    Petersen, Kurt Erling

    1986-01-01

    Risk and reliability analysis is increasingly being used in evaluations of plant safety and plant reliability. The analysis can be performed either during the design process or during the operation time, with the purpose to improve the safety or the reliability. Due to plant complexity and safety...... and availability requirements, sophisticated tools, which are flexible and efficient, are needed. Such tools have been developed in the last 20 years and they have to be continuously refined to meet the growing requirements. Two different areas of application were analysed. In structural reliability probabilistic...... approaches have been introduced in some cases for the calculation of the reliability of structures or components. A new computer program has been developed based upon numerical integration in several variables. In systems reliability Monte Carlo simulation programs are used especially in analysis of very...

  7. GridWise Standards Mapping Overview

    Energy Technology Data Exchange (ETDEWEB)

    Bosquet, Mia L.

    2004-04-01

    ''GridWise'' is a concept of how advanced communications, information and controls technology can transform the nation's energy system--across the spectrum of large scale, central generation to common consumer appliances and equipment--into a collaborative network, rich in the exchange of decision making information and an abundance of market-based opportunities (Widergren and Bosquet 2003) accompanying the electric transmission and distribution system fully into the information and telecommunication age. This report summarizes a broad review of standards efforts which are related to GridWise--those which could ultimately contribute significantly to advancements toward the GridWise vision, or those which represent today's current technological basis upon which this vision must build.

  8. Reliability Engineering Analysis of ATLAS Data Reprocessing Campaigns

    CERN Document Server

    Vaniachine, A; The ATLAS collaboration; Karpenko, D

    2013-01-01

    During three years of LHC data taking, the ATLAS collaboration completed three petascale data reprocessing campaigns on the Grid, with up to 2 PB of data being reprocessed every year. In reprocessing on the Grid, failures can occur for a variety of reasons, while Grid heterogeneity makes failures hard to diagnose and repair quickly. As a result, Big Data processing on the Grid must tolerate a continuous stream of failures, errors and faults. While ATLAS fault-tolerance mechanisms improve the reliability of Big Data processing in the Grid, their benefits come at costs and result in delays making the performance prediction difficult. Reliability Engineering provides a framework for fundamental understanding of the Big Data processing on the Grid, which is not a desirable enhancement but a necessary requirement. In ATLAS, cost monitoring and performance prediction became critical for the success of the reprocessing campaigns conducted in preparation for the major physics conferences. In addition, our Reliability...

  9. Reliability Engineering Analysis of ATLAS Data Reprocessing Campaigns

    CERN Document Server

    Vaniachine, A; The ATLAS collaboration; Karpenko, D

    2014-01-01

    During three years of LHC data taking, the ATLAS collaboration completed three petascale data reprocessing campaigns on the Grid, with up to 2 PB of data being reprocessed every year. In reprocessing on the Grid, failures can occur for a variety of reasons, while Grid heterogeneity makes failures hard to diagnose and repair quickly. As a result, Big Data processing on the Grid must tolerate a continuous stream of failures, errors and faults. While ATLAS fault-tolerance mechanisms improve the reliability of Big Data processing in the Grid, their benefits come at costs and result in delays making the performance prediction difficult. Reliability Engineering provides a framework for fundamental understanding of the Big Data processing on the Grid, which is not a desirable enhancement but a necessary requirement. In ATLAS, cost monitoring and performance prediction became critical for the success of the reprocessing campaigns conducted in preparation for the major physics conferences. In addition, our Reliability...

  10. GridOrbit public display

    DEFF Research Database (Denmark)

    Ramos, Juan David Hincapie; Tabard, Aurélien; Bardram, Jakob

    2010-01-01

    We introduce GridOrbit, a public awareness display that visualizes the activity of a community grid used in a biology laboratory. This community grid executes bioin-formatics algorithms and relies on users to donate CPU cycles to the grid. The goal of GridOrbit is to create a shared awareness about...

  11. Security for grids

    Energy Technology Data Exchange (ETDEWEB)

    Humphrey, Marty; Thompson, Mary R.; Jackson, Keith R.

    2005-08-14

    Securing a Grid environment presents a distinctive set of challenges. This paper groups the activities that need to be secured into four categories: naming and authentication; secure communication; trust, policy, and authorization; and enforcement of access control. It examines the current state of the art in securing these processes and introduces new technologies that promise to meet the security requirements of Grids more completely.

  12. The LHCb Grid Simulation

    CERN Multimedia

    Baranov, Alexander

    2016-01-01

    The LHCb Grid access if based on the LHCbDirac system. It provides access to data and computational resources to researchers with different geographical locations. The Grid has a hierarchical topology with multiple sites distributed over the world. The sites differ from each other by their number of CPUs, amount of disk storage and connection bandwidth. These parameters are essential for the Grid work. Moreover, job scheduling and data distribution strategy have a great impact on the grid performance. However, it is hard to choose an appropriate algorithm and strategies as they need a lot of time to be tested on the real grid. In this study, we describe the LHCb Grid simulator. The simulator reproduces the LHCb Grid structure with its sites and their number of CPUs, amount of disk storage and bandwidth connection. We demonstrate how well the simulator reproduces the grid work, show its advantages and limitations. We show how well the simulator reproduces job scheduling and network anomalies, consider methods ...

  13. The play grid

    DEFF Research Database (Denmark)

    Fogh, Rune; Johansen, Asger

    2013-01-01

    In this paper we propose The Play Grid, a model for systemizing different play types. The approach is psychological by nature and the actual Play Grid is based, therefore, on two pairs of fundamental and widely acknowledged distinguishing characteristics of the ego, namely: extraversion vs. intro...

  14. Planning in Smart Grids

    NARCIS (Netherlands)

    Bosman, M.G.C.

    2012-01-01

    The electricity supply chain is changing, due to increasing awareness for sustainability and an improved energy efficiency. The traditional infrastructure where demand is supplied by centralized generation is subject to a transition towards a Smart Grid. In this Smart Grid, sustainable generation

  15. Gridded Species Distribution, Version 1: Global Amphibians Presence Grids

    Data.gov (United States)

    National Aeronautics and Space Administration — The Global Amphibians Presence Grids of the Gridded Species Distribution, Version 1 is a reclassified version of the original grids of amphibian species distribution...

  16. From smart grid to micro grid. Energy active settlements of the future; Vom Smart Grid zum Micro Grid. Energieaktive Siedlungen der Zukunft

    Energy Technology Data Exchange (ETDEWEB)

    Brauner, G. [Technische Univ. Wien (Austria). Inst. fuer Energiesysteme und Elektrische Antriebe

    2012-07-01

    The path to a mainly sustainable energy supply is predetermined by European and national directives. It is to be expected that the sustainable energy supply is growing much faster than the infrastructure can follow. Bottlenecks in the transmission system in particular by the development of onshore and offshore wind energy are probable. Also the expansion of photovoltaics in the settlements demands from the distribution networks. The idea of smart grids to store the excess energy in the superimposed classical energy system is negatively impacted by new problems. The micro grid expands the decentralized technology by allowing for temporary autonomy and energy balance especially if central storage systems and transmission capacities can not be used due to temporary bottlenecks. Concepts of decentralized supply are interesting that offer a temporary opportunity for a restricted island operation with reduced load.

  17. Considerations on modelling grid-integrated PV

    CSIR Research Space (South Africa)

    Carter-Brown, Clinton G

    2017-08-01

    Full Text Available , transmission and sub- transmission)Customer voltages Must be between 90% and 110% 10 Peak load Grid A uto transform er F eeder Load 11 kV 132 kV OLTC 5% voltage drop 105% 5MW 100kW 5% boost 5% voltage drop 100% 100% 10% voltage drop 90% 105 100 90 90 92... 105 104.5 109 108 90 92.5 95 97.5 100 102.5 105 107.5 110 0 5 V o lt a g e ( % ) Distance (km) 12 Voltage profiles with no generation Low load 1% rise limit Peak load 15% drop limit 13 Peak load with generation Grid A uto transform er Feeder Load 11...

  18. Grid generation methods

    CERN Document Server

    Liseikin, Vladimir D

    2017-01-01

    This new edition provides a description of current developments relating to grid methods, grid codes, and their applications to actual problems. Grid generation methods are indispensable for the numerical solution of differential equations. Adaptive grid-mapping techniques, in particular, are the main focus and represent a promising tool to deal with systems with singularities. This 3rd edition includes three new chapters on numerical implementations (10), control of grid properties (11), and applications to mechanical, fluid, and plasma related problems (13). Also the other chapters have been updated including new topics, such as curvatures of discrete surfaces (3). Concise descriptions of hybrid mesh generation, drag and sweeping methods, parallel algorithms for mesh generation have been included too. This new edition addresses a broad range of readers: students, researchers, and practitioners in applied mathematics, mechanics, engineering, physics and other areas of applications.

  19. The GRID seminar

    CERN Multimedia

    CERN. Geneva HR-RFA

    2006-01-01

    The Grid infrastructure is a key part of the computing environment for the simulation, processing and analysis of the data of the LHC experiments. These experiments depend on the availability of a worldwide Grid infrastructure in several aspects of their computing model. The Grid middleware will hide much of the complexity of this environment to the user, organizing all the resources in a coherent virtual computer center. The general description of the elements of the Grid, their interconnections and their use by the experiments will be exposed in this talk. The computational and storage capability of the Grid is attracting other research communities beyond the high energy physics. Examples of these applications will be also exposed during the presentation.

  20. A Grid Voltage Measurement Method for Wind Power Systems during Grid Fault Conditions

    Directory of Open Access Journals (Sweden)

    Cheol-Hee Yoo

    2014-11-01

    Full Text Available Grid codes in many countries require low-voltage ride-through (LVRT capability to maintain power system stability and reliability during grid fault conditions. To meet the LVRT requirement, wind power systems must stay connected to the grid and also supply reactive currents to the grid to support the recovery from fault voltages. This paper presents a new fault detection method and inverter control scheme to improve the LVRT capability for full-scale permanent magnet synchronous generator (PMSG wind power systems. Fast fault detection can help the wind power systems maintain the DC-link voltage in a safe region. The proposed fault detection method is based on on-line adaptive parameter estimation. The performance of the proposed method is verified in comparison to the conventional voltage measurement method defined in the IEC 61400-21 standard.