WorldWideScience

Sample records for short-circuit current isc

  1. Worst Asymmetrical Short-Circuit Current

    DEFF Research Database (Denmark)

    Arana Aristi, Iván; Holmstrøm, O; Grastrup, L

    2010-01-01

    In a typical power plant, the production scenario and the short-circuit time were found for the worst asymmetrical short-circuit current. Then, a sensitivity analysis on the missing generator values was realized in order to minimize the uncertainty of the results. Afterward the worst asymmetrical...

  2. Thyristor based short circuit current injection in isolated grids

    OpenAIRE

    Hoff, Bjarte; Sharma, Pawan; Østrem, Trond

    2017-01-01

    This paper proposes a thyristor based short circuit current injector for providing short circuit current in isolated and weak grids, where sufficient fault current to trigger circuit breakers may not be available. This will allow the use of conventional miniature circuit breakers, which requires high fault current for instantaneous tripping. The method has been validated through experiments.

  3. Electrical short circuit and current overload tests on aircraft wiring

    Science.gov (United States)

    Cahill, Patricia

    1995-01-01

    The findings of electrical short circuit and current overload tests performed on commercial aircraft wiring are presented. A series of bench-scale tests were conducted to evaluate circuit breaker response to overcurrent and to determine if the wire showed any visible signs of thermal degradation due to overcurrent. Three types of wire used in commercial aircraft were evaluated: MIL-W-22759/34 (150 C rated), MIL-W-81381/12 (200 C rated), and BMS 1360 (260 C rated). A second series of tests evaluated circuit breaker response to short circuits and ticking faults. These tests were also meant to determine if the three test wires behaved differently under these conditions and if a short circuit or ticking fault could start a fire. It is concluded that circuit breakers provided reliable overcurrent protection. Circuit breakers may not protect wire from ticking faults but can protect wire from direct shorts. These tests indicated that the appearance of a wire subjected to a current that totally degrades the insulation looks identical to a wire subjected to a fire; however the 'fire exposed' conductor was more brittle than the conductor degraded by overcurrent. Preliminary testing indicates that direct short circuits are not likely to start a fire. Preliminary testing indicated that direct short circuits do not erode insulation and conductor to the extent that ticking faults did. Circuit breakers may not safeguard against the ignition of flammable materials by ticking faults. The flammability of materials near ticking faults is far more important than the rating of the wire insulation material.

  4. cAMP Stimulates Transepithelial Short-Circuit Current and Fluid Transport Across Porcine Ciliary Epithelium.

    Science.gov (United States)

    Cheng, Angela King-Wah; Civan, Mortimer M; To, Chi-Ho; Do, Chi-Wai

    2016-12-01

    To investigate the effects of cAMP on transepithelial electrical parameters and fluid transport across porcine ciliary epithelium. Transepithelial electrical parameters were determined by mounting freshly isolated porcine ciliary epithelium in a modified Ussing chamber. Similarly, fluid movement across intact ciliary body was measured with a custom-made fluid flow chamber. Addition of 1, 10, and 100 μM 8-Br-cAMP (cAMP) to the aqueous side (nonpigmented ciliary epithelium, NPE) induced a sustained increase in short-circuit current (Isc). Addition of niflumic acid (NFA) to the aqueous surface effectively blocked the cAMP-induced Isc stimulation. The administration of cAMP to the stromal side (pigmented ciliary epithelium, PE) triggered a significant stimulation of Isc only at 100 μM. No additive effect was observed with bilateral application of cAMP. Likewise, forskolin caused a significant stimulation of Isc when applied to the aqueous side. Concomitantly, cAMP and forskolin increased fluid transport across porcine ciliary epithelium, and this stimulation was effectively inhibited by aqueous NFA. Depleting Cl- in the bathing solution abolished the baseline Isc and inhibited the subsequent stimulation by cAMP. Pretreatment with protein kinase A (PKA) blockers (H89/KT5720) significantly inhibited the cAMP- and forskolin-induced Isc responses. Our results suggest that cAMP triggers a sustained stimulation of Cl- and fluid transport across porcine ciliary epithelium; Cl- channels in the NPE cells are potentially a cellular site for this PKA-sensitive cAMP-mediated response.

  5. Effect of cAMP on short-circuit current in isolated human ciliary body.

    Science.gov (United States)

    Wu, Ren-yi; Ma, Ning; Hu, Qian-qian

    2013-07-01

    Cyclic adenosine monophosphate (cAMP) could activate chloride channels in bovine ciliary body and trigger an increase in the ionic current (short-circuit current, Isc) across the ciliary processes in pigs. The purpose of this study was to investigate how cAMP modulates Isc in isolated human ciliary processes and the possible involvement of chloride transport across the tissue in cAMP-induced Isc change. In an Ussing-type chamber system, the Isc changes induced by the cAMP analogue 8-bromo-cAMP and an adenylyl cyclase activator forskolin in isolated human ciliary processes were assessed. The involvement of Cl(-) component in the bath solution was investigated. The effect of Cl(-) channel (10 µmol/L niflumic acid and 1 mmol/L 4,4'-diisothiocyanostilbene-2,2'-disulfonic acid (DIDS)), K(+) channel (10 mmol/L tetraethylammonium chloride (TEA)), or Na(+) channel blockers (1 mmol/L amiloride) on 8-bromo-cAMP-induced Isc change was also studied. Dose-dependently, 8-bromo-cAMP (10 nmol/L-30 µmol/L) or forskolin (10 nmol/L-3 µmol/L) increased Isc across the ciliary processes with an increase in negative potential difference on the non-pigmented epithelium (NPE) side of the tissue. Isc increase induced by 8-bromo-cAMP was more pronounced when the drug was applied on the NPE side than on the pigmented epithelium side. When the tissue was bathed in low Cl(-) solutions, the Isc increase was significantly inhibited. Finally, niflumic acid and DIDS, but not TEA or amiloride, significantly prevented the Isc increase induced by 8-bromo-cAMP. cAMP stimulates stroma-to-aqueous anionic transport in isolated human ciliary processes. Chloride is likely to be among the ions, the transportation of which across the tissue is triggered by cAMP, suggesting the potential role of cAMP in the process of aqueous humor formation in human eyes.

  6. Effect of notch depth of modified current collector on internal-short-circuit mitigation for lithium-ion battery

    Science.gov (United States)

    Wang, Meng; Noelle, Daniel J.; Shi, Yang; Le, Anh V.; Qiao, Yu

    2018-01-01

    Formation of internal short circuit (ISC) may result in catastrophic thermal runaway of lithium-ion battery (LIB). Among LIB cell components, direct contact between cathode and anode current collectors is most critical to the ISC behavior, yet is still relatively uninvestigated. In the current study, we analyze the effect of heterogeneity of current collector on the temperature increase of LIB cells subjected to mechanical abuse. The cathode current collector is modified by surface notches, so that it becomes effectively brittle and the ISC site can be isolated. Results from impact tests on LIB cells with modified current collectors suggest that their temperature increase can be negligible. The critical parameters include the failure strain and the failure work of modified current collector, both of which are related to the notch depth.

  7. The effect of acute hypoxia on short-circuit current and epithelial resistivity in biopsies from human colon.

    Science.gov (United States)

    Carra, Graciela E; Ibáñez, Jorge E; Saraví, Fernando D

    2013-09-01

    In isolated colonic mucosa, decreases in short-circuit current (ISC) and transepithelial resistivity (RTE) occur when hypoxia is either induced at both sides or only at the serosal side of the epithelium. We assessed in human colon biopsies the sensitivity to serosal-only hypoxia and mucosal-only hypoxia and whether Na, K-ATPase blockade with ouabain interacts with hypoxia. Biopsy material from patients undergoing colonoscopy was mounted in an Ussing chamber for small samples (1-mm2 window). In a series of experiments we assessed viability and the electrical response to the mucolytic, dithiothreitol (1 mmol/l). In a second series, we explored the effect of hypoxia without and with ouabain. In a third series, we evaluated the response to a cycle of hypoxia and reoxygenation induced at the serosal or mucosal side while keeping the oxygenation of the opposite side. 1st series: Dithiothreitol significantly decreased the unstirred layer and ISC but increased RTE. 2nd series: Both hypoxia and ouabain decreased ISC, but ouabain increased RTE and this effect on RTE prevailed even during hypoxia. 3rd series: Mucosal hypoxia caused lesser decreases of ISC and RTE than serosal hypoxia; in the former, but not in the latter, recovery was complete upon reoxygenation. In mucolytic concentration, dithiothreitol modifies ISC and RTE. Oxygen supply from the serosal side is more important to sustain ISC and RTE in biopsy samples. The different effect of hypoxia and Na, K-ATPase blockade on RTE suggests that their depressing effect on ISC involves different mechanisms.

  8. Laser induced non-monotonic degradation in short-circuit current of triple-junction solar cells

    Science.gov (United States)

    Dou, Peng-Cheng; Feng, Guo-Bin; Zhang, Jian-Min; Song, Ming-Ying; Zhang, Zhen; Li, Yun-Peng; Shi, Yu-Bin

    2018-06-01

    In order to study the continuous wave (CW) laser radiation effects and mechanism of GaInP/GaAs/Ge triple-junction solar cells (TJSCs), 1-on-1 mode irradiation experiments were carried out. It was found that the post-irradiation short circuit current (ISC) of the TJSCs initially decreased and then increased with increasing of irradiation laser power intensity. To explain this phenomenon, a theoretical model had been established and then verified by post-damage tests and equivalent circuit simulations. Conclusion was drawn that laser induced alterations in the surface reflection and shunt resistance were the main causes for the observed non-monotonic decrease in the ISC of the TJSCs.

  9. Approximative calculation of transient short-circuit currents in power-systems

    Energy Technology Data Exchange (ETDEWEB)

    Heuck, K; Rosenberger, R; Dettmann, K D; Kegel, R

    1986-08-01

    The paper shows that it is approximatively possible to calculate the transient short-circuit currents for symmetrical and asymmetrical faults in power-systems. For that purpose a simple equivalent network is found. Its error of approximation is small. For the important maximum short-circuit current limits of error are pointed out compared to VDE 0102.

  10. 30 CFR 75.601-3 - Short circuit protection; dual element fuses; current ratings; maximum values.

    Science.gov (United States)

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Short circuit protection; dual element fuses... Trailing Cables § 75.601-3 Short circuit protection; dual element fuses; current ratings; maximum values. Dual element fuses having adequate current-interrupting capacity shall meet the requirements for short...

  11. Solar Cell Short Circuit Current Errors and Uncertainties During High Altitude Calibrations

    Science.gov (United States)

    Snyder, David D.

    2012-01-01

    High altitude balloon based facilities can make solar cell calibration measurements above 99.5% of the atmosphere to use for adjusting laboratory solar simulators. While close to on-orbit illumination, the small attenuation to the spectra may result in under measurements of solar cell parameters. Variations of stratospheric weather, may produce flight-to-flight measurement variations. To support the NSCAP effort, this work quantifies some of the effects on solar cell short circuit current (Isc) measurements on triple junction sub-cells. This work looks at several types of high altitude methods, direct high altitude meas urements near 120 kft, and lower stratospheric Langley plots from aircraft. It also looks at Langley extrapolation from altitudes above most of the ozone, for potential small balloon payloads. A convolution of the sub-cell spectral response with the standard solar spectrum modified by several absorption processes is used to determine the relative change from AMO, lscllsc(AMO). Rayleigh scattering, molecular scatterin g from uniformly mixed gases, Ozone, and water vapor, are included in this analysis. A range of atmosph eric pressures are examined, from 0. 05 to 0.25 Atm to cover the range of atmospheric altitudes where solar cell calibrations a reperformed. Generally these errors and uncertainties are less than 0.2%

  12. Effects of tetrodotoxin and ion replacements on the short-circuit current induced by Escherichiacoli heat stable enterotoxin across small intestine of the gerbil (Gerbillus cheesmani

    Directory of Open Access Journals (Sweden)

    Fawzia Yaqoub Al-Balool

    2004-03-01

    Full Text Available The effects of mucosally added Escherichia coli heat stable enterotoxin (STa 30 ng ml-1 on the basal short-circuit current (Isc in µA cm-2 across stripped and unstripped sheets of jejuna and ilea taken from fed, starved (4 days, water ad lib and undernourished (50% control food intake for 21 days gerbil (Gerbillus cheesmani were investigated. The effect of neurotoxin tetrodotoxin (TTX 10 µM and the effects of replacing chloride by gluconate or the effects of removing bicarbonate from bathing buffers on the maximum increase in Isc induced by STa were also investigated. The maximum increase in Isc which resulted from the addition of STa were significantly higher in jejuna and ilea taken from starved and undernourished gerbils when compared with the fed control both using stripped and unstripped sheets. In the two regions of the small intestine taken from fed and starved animals TTX reduced the maximum increase in Isc induced by STa across unstripped sheets only. Moreover in jejuna and ilea taken from undernourished gerbils TTX reduced significantly the maximum increase in Isc induced by STa across stripped and unstripped sheets. Replacing chloride by gluconate decreased the maximum increase in Isc induced by STa across jejuna and ilea taken from undernourished gerbils only. Removing bicarbonates from bathing buffer decreased the maximum increase in Isc across the jejuna and ilea taken from starved and undernourished gerbils.

  13. Bumetanide increases Cl--dependent short-circuit current in late distal colon: Evidence for the presence of active electrogenic Cl- absorption.

    Science.gov (United States)

    Tang, Lieqi; Fang, Xiefan; Winesett, Steven P; Cheng, Catherine Y; Binder, Henry J; Rivkees, Scott A; Cheng, Sam X

    2017-01-01

    Mammalian colonic epithelia consist of cells that are capable of both absorbing and secreting Cl-. The present studies employing Ussing chamber technique identified two opposing short-circuit current (Isc) responses to basolateral bumetanide in rat distal colon. Apart from the transepithelial Cl--secretory Isc in early distal colon that was inhibited by bumetanide, bumetanide also stimulated Isc in late distal colon that had not previously been identified. Since bumetanide inhibits basolateral Na+-K+-2Cl- cotransporter (NKCC) in crypt cells and basolateral K+-Cl- cotransporter (KCC) in surface epithelium, we proposed this stimulatory Isc could represent a KCC-mediated Cl- absorptive current. In support of this hypothesis, ion substitution experiments established Cl- dependency of this absorptive Isc and transport inhibitor studies demonstrated the involvement of an apical Cl- conductance. Current distribution and RNA sequencing analyses revealed that this Cl- absorptive Isc is closely associated with epithelial Na+ channel (ENaC) but is not dependent on ENaC activity. Thus, inhibition of ENaC by 10 μM amiloride or benzamil neither altered the direction nor its activity. Physiological studies suggested that this Cl- absorptive Isc senses dietary Cl- content; thus when dietary Cl- was low, Cl- absorptive Isc was up-regulated. In contrast, when dietary Cl- was increased, Cl- absorptive Isc was down-regulated. We conclude that an active Cl- extrusion mechanism exists in ENaC-expressing late distal colon and likely operates in parallel with ENaC to facilitate NaCl absorption.

  14. Short-Circuit Current Analysis for DFIG Wind Farm Considering the Action of a Crowbar

    Directory of Open Access Journals (Sweden)

    Yan Hong Yuan

    2018-02-01

    Full Text Available With the increasing capacity of wind farms integrated into the power grid, the short-circuit current analysis for wind farms becomes more and more important. Since the wind turbine is usually integrated into the power grid via power electronic devices, the “crowbar” is installed in the wind turbine to protect the power electronic devices and to improve the fault ride through capability. The impact of the crowbar has to be considered during the short-circuit current analysis for the wind farm. In order to fully analyze the short-circuit current characteristics of a wind farm, the short-circuit currents for a doubly-fed induction generator (DFIG wind turbine under symmetrical and asymmetrical faults considering the crowbar action characteristic are derived firstly. Then the action situation of the crowbar of a DFIG wind turbine is studied and the action area curve is obtained. Taking the crowbar action, or not, as the grouping criterion, wind turbines in the wind farm are divided into two groups, and the wind farm is aggregated into two equivalent wind turbines. Using the equivalent model, the short-circuit current of a wind farm can be calculated accurately. Finally, simulations are performed in MATLAB/Simulink which is the commercial math software produced by the MathWorks company in Natick, Massachusetts, the United States to verify the proposed short-circuit current calculation method for the DFIG wind farm.

  15. Modelling the short-circuit current of polymer bulk heterojunction solar cells

    International Nuclear Information System (INIS)

    Geens, Wim; Martens, Tom; Poortmans, Jef; Aernouts, Tom; Manca, Jean; Lutsen, Laurence; Heremans, Paul; Borghs, Staf; Mertens, Robert; Vanderzande, Dirk

    2004-01-01

    An analytical model has been developed to estimate the short-circuit current density of conjugated polymer/fullerene bulk heterojunction solar cells. The model takes into account the solvent-dependent molecular morphology of the donor/acceptor blend, which was revealed by transmission electron microscopy. Field-effect transistors based on single and composite organic layers were fabricated to determine values for the charge carrier mobilities of such films. These values served as input parameters of the model. It is shown that the difference in short-circuit current density that was measured between toluene-cast and chlorobenzene-cast conjugated polymer/fullerene photovoltaic cells (Appl. Phys. Lett. 78 (2001) 841) could be very well simulated with the model. Moreover, the calculations illustrate how increasing the hole and electron mobilities in the photoactive blend can improve the overall short-circuit current density of the solar cell

  16. Short-Circuit Current Analysis for DFIG Wind Farm Considering the Action of a Crowbar

    OpenAIRE

    Yan Hong Yuan; Feng Wu

    2018-01-01

    With the increasing capacity of wind farms integrated into the power grid, the short-circuit current analysis for wind farms becomes more and more important. Since the wind turbine is usually integrated into the power grid via power electronic devices, the “crowbar” is installed in the wind turbine to protect the power electronic devices and to improve the fault ride through capability. The impact of the crowbar has to be considered during the short-circuit current analysis for the wind farm....

  17. Defects influence on short circuit current density in p-i-n silicon solar cell

    International Nuclear Information System (INIS)

    Wagah F Mohamad; Alhan M Mustafa

    2006-01-01

    The admittance analysis method has been used to calculate the collection efficiency and the short circuit current density in a-Si:H p-i-n solar cell, as a function of the thickness of i-layer. Its is evident that the results of the short circuit current can be used to determine the optimal thickness of the i-layer of a cell, and it will be more accurate in comparison with the previous studies using a constant generation rate or an empirical exponential function for the generation of charge carriers throughout the i-layer

  18. Verification of the short-circuit current making capability of high-voltage switching devices

    NARCIS (Netherlands)

    Smeets, R.P.P.; Linden, van der W.A.

    2001-01-01

    Switching-in of short-circuit current leads to pre-arcing in the switching device. Pre-arcing affects the ability of switchgear to close and latch. In three-phase systems, making is associated with transient voltage phenomena that may have a significant impact on the duration of the pre-arcing

  19. The influence of gamma irradiation on short-circuit current in CuGaSe2

    International Nuclear Information System (INIS)

    Gasimoglu, I.; Mamedova, I.A.; Bagirov, A.G.

    2005-01-01

    Full text : The influence of gamma irradiation on a short-circuit current at 77 K was investigated. The appeared strip with a maximum at 1,61 ///// after irradiation in spectral dependence connected with p-type radiating defects [ru

  20. Influence of wavelength on transient short-circuit current in polycrystalline silicon solar cells

    International Nuclear Information System (INIS)

    Ba, B.; Kane, M.

    1993-10-01

    The influence of the wavelength of a monochromatic illumination on transient short-circuit current in an n/p polycrystalline silicon part solar cell junction is investigated. A wavelength dependence in the initial part of the current decay is observed in the case of cells with moderate grain boundary effects. This influence is attenuated in polycrystalline cells with strong grain boundary activity. (author). 10 refs, 6 figs

  1. Measurements of impedances for determinating the minimum short-circuit current in main systems 500 V of underground mining establishments

    Energy Technology Data Exchange (ETDEWEB)

    Rittinghaus, D

    1981-09-01

    The complex short-circuit impedances of energized low-voltage main systems were measured with a double-bridge in underground mining operation. The magnitude of the short-circuit currents depends on these impedances. Customary calculations of such currents depend on empirical approximations. To verify the accuracy of these approximations, the measured impedances of 61 nodes in three different main systems were compared with the results of the calculations. The comparison made between the short-circuit currents determined by measurable quantities and the values calculated according to VDE 0118 shows that the stipulated coefficients for calculating the minimum short-circuit currents lie very far on the safe side. An amendment for calculating the short-circuit in accordance with VDE 0118 is therefore suggested.

  2. Increased short circuit current in an azafullerene-based organic solar cell.

    Science.gov (United States)

    Cambarau, Werther; Fritze, Urs F; Viterisi, Aurélien; Palomares, Emilio; von Delius, Max

    2015-01-21

    We report the synthesis of a solution-processable, dodecyloxyphenyl-substituted azafullerene monoadduct (DPC59N) and its application as electron acceptor in bulk heterojunction organic solar cells (BHJ-OSCs). Due to its relatively strong absorption of visible light, DPC59N outperforms PC60BM in respect to short circuit current (JSC) and external quantum efficiency (EQE) in blends with donor P3HT.

  3. Several problems of algorithmization in integrated computation programs on third generation computers for short circuit currents in complex power networks

    Energy Technology Data Exchange (ETDEWEB)

    Krylov, V.A.; Pisarenko, V.P.

    1982-01-01

    Methods of modeling complex power networks with short circuits in the networks are described. The methods are implemented in integrated computation programs for short circuit currents and equivalents in electrical networks with a large number of branch points (up to 1000) on a computer with a limited on line memory capacity (M equals 4030 for the computer).

  4. Spatially resolved determination of the short-circuit current density of silicon solar cells via lock-in thermography

    International Nuclear Information System (INIS)

    Fertig, Fabian; Greulich, Johannes; Rein, Stefan

    2014-01-01

    We present a spatially resolved method to determine the short-circuit current density of crystalline silicon solar cells by means of lock-in thermography. The method utilizes the property of crystalline silicon solar cells that the short-circuit current does not differ significantly from the illuminated current under moderate reverse bias. Since lock-in thermography images locally dissipated power density, this information is exploited to extract values of spatially resolved current density under short-circuit conditions. In order to obtain an accurate result, one or two illuminated lock-in thermography images and one dark lock-in thermography image need to be recorded. The method can be simplified in a way that only one image is required to generate a meaningful short-circuit current density map. The proposed method is theoretically motivated, and experimentally validated for monochromatic illumination in comparison to the reference method of light-beam induced current.

  5. Development of processing procedures for advanced silicon solar cells. [antireflection coatings and short circuit currents

    Science.gov (United States)

    Scott-Monck, J. A.; Stella, P. M.; Avery, J. E.

    1975-01-01

    Ten ohm-cm silicon solar cells, 0.2 mm thick, were produced with short circuit current efficiencies up to thirteen percent and using a combination of recent technical advances. The cells were fabricated in conventional and wraparound contact configurations. Improvement in cell collection efficiency from both the short and long wavelengths region of the solar spectrum was obtained by coupling a shallow junction and an optically transparent antireflection coating with back surface field technology. Both boron diffusion and aluminum alloying techniques were evaluated for forming back surface field cells. The latter method is less complicated and is compatible with wraparound cell processing.

  6. The effect of different solar simulators on the measurement of short-circuit current temperature coefficients

    Science.gov (United States)

    Curtis, H. B.; Hart, R. E., Jr.

    1982-01-01

    Gallium arsenide solar cells are considered for several high temperature missions in space. Both near-Sun and concentrator missions could involve cell temperatures on the order of 200 C. Performance measurements of cells at elevated temperatures are usually made using simulated sunlight and a matched reference cell. Due to the change in bandgap with increasing temperature at portions of the spectrum where considerable simulated irradiance is present, there are significant differences in measured short circuit current at elevated temperatures among different simulators. To illustrate this, both experimental and theoretical data are presented for gallium arsenide cells.

  7. Variations in the electrical short-circuit current decay for recombination lifetime and velocity measurements

    Science.gov (United States)

    Jung, Tae-Won; Lindholm, Fredrik A.; Neugroschel, Arnost

    1987-01-01

    An improved measurement system for electrical short-circuit current decay is presented that extends applicability of the method to silicon solar cells having an effective lifetime as low as 1 microsec. The system uses metal/oxide/semiconductor transistors as voltage-controlled switches. Advances in theory developed here increase precision and sensitivity in the determination of the minority-carrier recombination lifetime and recombination velocity. A variation of the method, which exploits measurements made on related back-surface field and back-ohmic contact devices, further improves precision and sensitivity. The improvements are illustrated by application to 15 different silicon solar cells.

  8. Methods for stable recording of short-circuit current in a Na+-transporting epithelium.

    Science.gov (United States)

    Gondzik, Veronika; Awayda, Mouhamed S

    2011-07-01

    Epithelial Na(+) transport as measured by a variety of techniques, including the short-circuit current technique, has been described to exhibit a "rundown" phenomenon. This phenomenon manifests as time-dependent decrease of current and resistance and precludes the ability to carry out prolonged experiments aimed at examining the regulation of this transport. We developed methods for prolonged stable recordings of epithelial Na(+) transport using modifications of the short-circuit current technique and commercial Ussing-type chambers. We utilize the polarized MDCK cell line expressing the epithelial Na(+) channel (ENaC) to describe these methods. Briefly, existing commercial chambers were modified to allow continuous flow of Ringer solution and precise control of such flow. Chamber manifolds and associated plumbing were modified to allow precise temperature clamp preventing temperature oscillations. Recording electrodes were modified to eliminate the use of KCl and prevent membrane depolarization from KCl leakage. Solutions utilized standard bicarbonate-based buffers, but all gasses were prehydrated to clamp buffer osmolarity. We demonstrate that these modifications result in measurements of current and resistance that are stable for at least 2 h. We further demonstrate that drifts in osmolarity similar to those obtained before prior to our modifications can lead to a decrease of current and resistance similar to those attributed to rundown.

  9. Maximizing the short circuit current of organic solar cells by partial decoupling of electrical and optical properties

    Science.gov (United States)

    Qarony, Wayesh; Hossain, Mohammad I.; Jovanov, Vladislav; Knipp, Dietmar; Tsang, Yuen Hong

    2018-03-01

    The partial decoupling of electronic and optical properties of organic solar cells allows for realizing solar cells with increased short circuit current and energy conversion efficiency. The proposed device consists of an organic solar cell conformally prepared on the surface of an array of single and double textured pyramids. The device geometry allows for increasing the optical thickness of the organic solar cell, while the electrical thickness is equal to the nominal thickness of the solar cell. By increasing the optical thickness of the solar cell, the short circuit current is distinctly increased. The quantum efficiency and short circuit current are determined using finite-difference time-domain simulations of the 3D solar cell structure. The influence of different solar cell designs on the quantum efficiency and short circuit current is discussed and optimal device dimensions are proposed.

  10. Adrenomedullin increases the short-circuit current in the mouse seminal vesicle: actions on chloride secretion.

    Science.gov (United States)

    Liao, S B; Cheung, K H; O, W S; Tang, Fai

    2014-08-01

    Adrenomedullin (ADM) may regulate seminal vesicle fluid secretion, and this may affect sperm quality. In this study, we investigated the effect of ADM on chloride secretion in the mouse seminal vesicle. The presence of ADM in mouse seminal vesicle was confirmed using immunostaining, and the molecular species was determined using gel filtration chromatography coupled with enzyme-linked assay for ADM. The effects of ADM on chloride secretion were studied by short-circuit current technique in a whole-mount preparation of mouse seminal vesicle in an Ussing chamber. The effects of specific ADM and calcitonin gene-related peptide (CGRP) receptor antagonists were investigated. Whether the ADM effect depended on the cAMP- and/or calcium-activated chloride channel was also studied using specific chloride channel blockers. The results showed that ADM was present in seminal vesicle epithelial cells. The major molecular species was precursor in the mouse seminal vesicle. ADM increased short-circuit current through the calcium-activated chloride channel in mouse seminal vesicle, and CGRP receptor was involved. We conclude that ADM may regulate chloride and fluid secretion from the seminal vesicle, which may affect the composition of the seminal plasma bathing the sperm and, hence, fertility. © 2014 by the Society for the Study of Reproduction, Inc.

  11. Three-Phase Short-Circuit Current Calculation of Power Systems with High Penetration of VSC-Based Renewable Energy

    Directory of Open Access Journals (Sweden)

    Niancheng Zhou

    2018-03-01

    Full Text Available Short-circuit current level of power grid will be increased with high penetration of VSC-based renewable energy, and a strong coupling between transient fault process and control strategy will change the fault features. The full current expression of VSC-based renewable energy was obtained according to transient characteristics of short-circuit current. Furtherly, by analyzing the closed-loop transfer function model of controller and current source characteristics presented in steady state during a fault, equivalent circuits of VSC-based renewable energy of fault transient state and steady state were proposed, respectively. Then the correctness of the theory was verified by experimental tests. In addition, for power grid with VSC-based renewable energy, superposition theorem was used to calculate AC component and DC component of short-circuit current, respectively, then the peak value of short-circuit current was evaluated effectively. The calculated results could be used for grid planning and design, short-circuit current management as well as adjustment of relay protection. Based on comparing calculation and simulation results of 6-node 500 kV Huainan power grid and 35-node 220 kV Huaisu power grid, the effectiveness of the proposed method was verified.

  12. THE RATE OF CURRENT CHANGE DURING A SHORT CIRCUIT IN THE POWER CIRCUITS OF THE ELECTRIC ROLLING STOCK WITH REGARD TO EDDY CURRENTS

    Directory of Open Access Journals (Sweden)

    L. V. Dubinets

    2010-04-01

    Full Text Available In the article the issue of influence of vortical currents on rate of change of short circuit current is considered, a mathematical model for the calculation of short circuit currents in the traction mode in the power circuits of DC electric rolling stock is presented, and the research results are given.

  13. An alternative explanation for the occurrence of short circuit current increases in the small intestine following challenge by bacterial enterotoxins.

    Science.gov (United States)

    Lucas, M L

    2013-10-01

    Secretory diarrhoeal disease due to enterotoxins is thought to arise from the enhancement to pathologically high rates of normally occurring chloride ion and therefore fluid secretion from enterocytes. In support of this concept, many enterotoxins increase intestinal short-circuit current, regarded now as faithfully reflecting the increased chloride ion secretion. Contradicting this assumption, STa reduces absorption but does not cause secretion in vivo although short-circuit current is increased in vitro. There is therefore a mismatch between an assumed enterocyte mediated secretory event that should but does not cause net fluid secretion and an undoubtedly increased short-circuit current. It is proposed here that short-circuit current increases are not themselves secretory events but result from interrupted fluid absorption. A noteworthy feature of compounds that inhibit the increase in short-circuit current is that the majority are vasoactive, neuroactive or both. In general, vasodilator substances increase current. An alternative hypothesis for the origin of short-circuit current increases is that these result from reflex induction of electrogenic fluid absorption. This reflex enhances a compensatory response that is also present at a cellular level. An intestinal reflex is therefore proposed by which decreases in interstitial and intravascular volume or pressure within the intestine initiate an electrogenic fluid absorption mechanism that compensates for the loss of electrically neutral fluid absorption. This hypothesis would explain the apparently complex pharmacology of short-circuit current increases since many depressor substances have receptors in common with enterocytes and enteric nerves. The proposed alternative view of the origin of short-circuit current increases assumes that these do not represent chloride secretion from the enterocytes. This view may therefore aid the successful development of anti-diarrhoeal drugs to overcome a major cause of

  14. Short-circuit current improvement in thin cells with a gridded back contact

    Science.gov (United States)

    Giuliano, M.; Wohlgemuth, J.

    1980-01-01

    The use of gridded back contact on thin silicon solar cells 50 micrometers was investigated. An unexpected increase in short circuit current of almost 10 percent was experienced for 2 cm x 2 cm cells. Control cells with the standard continuous contact metallization were fabricated at the same time as the gridded back cells with all processes identical up to the formation of the back contact. The gridded back contact pattern was delineated by evaporation of Ti-Pd over a photo-resist mask applied to the back of the wafer; the Ti-Pd film on the controls was applied in the standard fashion in a continuous layer over the back of the cell. The Ti-Pd contacts were similarly applied to the front of the wafer, and the grid pattern on both sides of the cell was electroplated with 8-10 micrometers of silver.

  15. Short circuit current changes in electron irradiated GaAlAs/GaAs solar cells

    Science.gov (United States)

    Walker, G. H.; Conway, E. J.

    1978-01-01

    Heteroface p-GaAlAs/p-GaAs/n-GaAs solar cells with junction depths of 0.8, 1.5, and 4 microns were irradiated with 1 MeV electrons. The short-circuit current for the 4 micron junction depth cells is significantly reduced by the electron irradiation. Reduction of the junction depth to 1.5 microns improves the electron radiation resistance of the cells while further reduction of the junction depth to 0.8 microns improves the stability of the cells even more. Primary degradation is in the blue region of the spectrum. Considerable recovery of lost response is obtained by annealing the cells at 200 C. Computer modeling shows that the degradation is caused primarily by a reduction in the minority carrier diffusion length in the p-GaAs.

  16. The Effect of Current-Limiting Reactors on the Tripping of Short Circuits in High-Voltage Electrical Equipment

    International Nuclear Information System (INIS)

    Volkov, M. S.; Gusev, Yu. P.; Monakov, Yu. V.; Cho, Gvan Chun

    2016-01-01

    The insertion of current-limiting reactors into electrical equipment operating at a voltage of 110 and 220 kV produces a change in the parameters of the transient recovery voltages at the contacts of the circuit breakers for disconnecting short circuits, which could be the reason for the increase in the duration of the short circuit, damage to the electrical equipment and losses in the power system. The results of mathematical modeling of the transients, caused by tripping of the short circuit in a reactive electric power transmission line are presented, and data are given on the negative effect of a current-limiting resistor on the rate of increase and peak value of the transient recovery voltages. Methods of ensuring the standard requirements imposed on the parameters of the transient recovery voltages when using current-limiting reactors in the high-voltage electrical equipment of power plants and substations are proposed and analyzed

  17. The short-circuit current of the ileum, but not the colon, is altered in the streptozotocin diabetic rat.

    Science.gov (United States)

    Forrest, Abigail; Makwana, Rajesh; Parsons, Mike

    2006-02-01

    Ion transport in control and streptozotocin-diabetic rat colon and ileum was studied using the Ussing chamber technique. No differences were observed between control and diabetic colonic mucosal short-circuit current under either basal or carbachol (100 nmol/L-1 micromol/L)-stimulated or prostaglandin E2 (100 nmol/L-1 micromol/L)-stimulated conditions. Similarly to colonic tissues, no differences in the short circuit current in either carbachol-stimulated or prostaglandin E2-stimulated tissues were observed between control and diabetic ileal mucosa. The basal diabetic ileal short circuit current (99.58 +/- 22.67 microA) was significantly greater than that of control ileal tissues (29.67 +/- 4.45 microA). This difference was abolished by the sodium-glucose-cotransporter inhibitor, phloridzin (50 micromol/L) (118.00 +/- 28.09 microA vs. 25.60 +/- 4.59 microA) and was also prevented by the replacement of glucose with mannitol in the buffer bathing the apical side of the tissue (control: 17.05 +/- 5.85 microA vs. 17.90 +/- 3.10 microA). Acetazolamide (450 micromol/L; a carbonic anhydrase inhibitor), amiloride, and bumetanide (100 micromol/L each; Na+-channel blockers), piroxicam (50 micromol/L; a COX1 cyclooxygenase inhibitor), and ouabain (1 mmol/L; a K+ transport inhibitor) had no effect on the basal short circuit current of either control or diabetic ileal tissues. This indicated that the alteration in the basal short circuit current of diabetic ileal tissues was due to a change in cellular glucose transport, whereas the evoked changes in short circuit current were unaffected by the diabetic state.

  18. Technical Study on Improvement of Endurance Capability of Limit Short-circuit Current of Charge Control SMART Meter

    Science.gov (United States)

    Li, W. W.; Du, Z. Z.; Yuan, R. m.; Xiong, D. Z.; Shi, E. W.; Lu, G. N.; Dai, Z. Y.; Chen, X. Q.; Jiang, Z. Y.; Lv, Y. G.

    2017-10-01

    Smart meter represents the development direction of energy-saving smart grid in the future. The load switch, one of the core parts of smart meter, should be of high reliability, safety and endurance capability of limit short-circuit current. For this reason, this paper discusses the quick simulation of relationship between attraction and counterforce of load switch without iteration, establishes dual response surface model of attraction and counterforce and optimizes the design scheme of load switch for charge control smart meter, thus increasing electromagnetic attraction and spring counterforce. In this way, this paper puts forward a method to improve the withstand capacity of limit short-circuit current.

  19. Optical effects of shadow masks on short circuit current of organic photovoltaic devices.

    Science.gov (United States)

    Lin, Chi-Feng; Lin, Bing-Hong; Liu, Shun-Wei; Hsu, Wei-Feng; Zhang, Mi; Chiu, Tien-Lung; Wei, Mau-Kuo; Lee, Jiun-Haw

    2012-03-21

    In this paper, we have employed different shadow masks attached on top of organic photovoltaic (OPV) devices to study the optical effects of the former on the short circuit current (J(SC)). To rule out possible lateral electrical conduction and simplify the optical effects inside the device, a small-molecular heterojunction OPV device with a clear donor/acceptor interface was employed with a hole extraction layer exhibiting high resistance intentionally. Careful calibration with a shadow mask was employed. By attaching two layers of opaque masks in combination with a suitable holder design to shield the light from the edges and backside, the value of J(SC) approached that of the dark current, even under 1-sun radiation. With different illumination areas, we found that the photons illuminating the non-active region of the device contributed to 40% of the J(SC) by optical effect within the width of about 1 mm around the active region. When illuminating the non-active area with 12 mm to the active area, a 5.6 times improvement in the J(SC) was observed when the incident angle was 75°. With the introduction of a microstructured film onto the OPV device and an increase in the reflection from the non-active region, a 15% enhancement of the J(SC) compared to the control device was achieved.

  20. Short-circuit current density imaging of crystalline silicon solar cells via lock-in thermography: Robustness and simplifications

    International Nuclear Information System (INIS)

    Fertig, Fabian; Greulich, Johannes; Rein, Stefan

    2014-01-01

    Spatially resolved determination of solar cell parameters is beneficial for loss analysis and optimization of conversion efficiency. One key parameter that has been challenging to access by an imaging technique on solar cell level is short-circuit current density. This work discusses the robustness of a recently suggested approach to determine short-circuit current density spatially resolved based on a series of lock-in thermography images and options for a simplified image acquisition procedure. For an accurate result, one or two emissivity-corrected illuminated lock-in thermography images and one dark lock-in thermography image have to be recorded. The dark lock-in thermography image can be omitted if local shunts are negligible. Furthermore, it is shown that omitting the correction of lock-in thermography images for local emissivity variations only leads to minor distortions for standard silicon solar cells. Hence, adequate acquisition of one image only is sufficient to generate a meaningful map of short-circuit current density. Beyond that, this work illustrates the underlying physics of the recently proposed method and demonstrates its robustness concerning varying excitation conditions and locally increased series resistance. Experimentally gained short-circuit current density images are validated for monochromatic illumination in comparison to the reference method of light-beam induced current

  1. Mode of the short circuit in the direct current electric traction network with different feed charts of fyder area

    Directory of Open Access Journals (Sweden)

    P. Mihalichenko

    2012-12-01

    Full Text Available In the article the results of mathematical design of the system of electric traction of direct current are represented in the mode of short circuit and different feed charts of fyder area: two-sided; one-sided. Comparison of transitional electric sizes which characterize electromagnetic processes during these malfunctions is analysed and executed.

  2. High short-circuit current density CdTe solar cells using all-electrodeposited semiconductors

    Energy Technology Data Exchange (ETDEWEB)

    Echendu, O.K., E-mail: oechendu@yahoo.com; Fauzi, F.; Weerasinghe, A.R.; Dharmadasa, I.M.

    2014-04-01

    CdS/CdTe and ZnS/CdTe n–n heterojunction solar cells have been fabricated using all-electrodeposited semiconductors. The best devices show remarkable high short-circuit current densities of 38.5 mAcm{sup −2} and 47.8 mAcm{sup −2}, open-circuit voltages of 630 mV and 646 mV and conversion efficiencies of 8.0% and 12.0% respectively. The major strength of these device structures lies in the combination of n–n heterojunction with a large Schottky barrier at the n-CdTe/metal back contact which provides the required band bending for the separation of photo-generated charge carriers. This is in addition to the use of a high quality n-type CdTe absorber layer with high electron mobility. The potential barrier heights estimated for these devices from the current–voltage characteristics exceed 1.09 eV and 1.13 eV for CdS/CdTe and ZnS/CdTe cells respectively. The diode rectification factors of both devices are in excess of four orders of magnitude with reverse saturation current densities of 1.0 × 10{sup −7} Acm{sup −2} and 4.0 × 10{sup −7} Acm{sup −2} respectively. These all-electrodeposited solar cell device structures are currently being studied and developed as an alternative to the well-known p–n junction structures which utilise chemical bath-deposited CdS. The preliminary material growth, device fabrication and assessment results are presented in this paper. - Highlights: • Two-electrode deposition. • High J{sub sc} Schottky barrier solar cells. • CdCl{sub 2} + CdF{sub 2} treatment.

  3. Vasotocin- and mesotocin-induced increases in short-circuit current across tree frog skin.

    Science.gov (United States)

    Takada, Makoto; Fujimaki-Aoba, Kayo; Hokari, Shigeru

    2011-02-01

    In adult amphibian skin, Na(+) crosses from outside to inside. This Na(+) transport can be measured as the amiloride-blockable short-circuit current (SCC) across the skin. We investigated the effects of arginine vasotocin (AVT) and mesotocin (MT), and those of antagonists of the vasopressin and oxytocin receptors, on the SCC across Hyla japonica skin. (1) Both AVT (100 pmol/L or more) and MT (1 nmol/L or more) increased the SCC. (2) The AVT- and MT-induced increases in SCC recovered with time (downregulation). (3) These AVT/MT-induced effects were blocked by application of OPC-31260 (vasopressin V(2)-receptor antagonist). (4) The OPC-31260 concentration needed to block the AVT-induced response was lower upon post-application (after application of agonist) than upon pre-application (before application of agonist), suggesting the number of receptors may have decreased after AVT application. (5) Upon repeated application of AVT (100 pmol/L), the induced SCC increase did not differ significantly between the 1st and 2nd applications. (6) The time to reach the half-maximum value of the AVT-induced or MT-induced increase in SCC was not significantly different between washout and post-application of OPC-31260, suggesting that post-application of OPC-31260 cleared AVT and MT from their receptors. The effects of AVT, MT, and their antagonists in H. japonica, which is adapted to a terrestrial habitat, are compared with our previously published data on Rana catesbeiana (=Lithobates catesbeianus), which is adapted to a semiaquatic habitat.

  4. Extra-high short-circuit current for bifacial solar cells in sunny and dark-light conditions.

    Science.gov (United States)

    Duan, Jialong; Duan, Yanyan; Zhao, Yuanyuan; He, Benlin; Tang, Qunwei

    2017-09-05

    We present here a symmetrically structured bifacial solar cell tailored by two fluorescent photoanodes and a platinum/titanium/platinum counter electrode, yielding extra-high short-circuit current densities as high as 28.59 mA cm -2 and 119.9 μA cm -2 in simulated sunlight irradiation (100 mW cm -2 , AM1.5) and dark-light conditions, respectively.

  5. The dependence of the short circuit current with γ-radiation in CuGaSe2

    International Nuclear Information System (INIS)

    Gasimoglu, I.; Mamedova, I.A.; Bagirov, A.G.

    2005-01-01

    Full text: The A I B III C IV semiconducting compounds are of interest for semiconducting devising. In particular the presence of the birefringence makes the compounds as a perspective materials for using in nonlinear optical transformers. Besides, the complex generation-recombination processes in these compounds are due to the local states in the band gap, which is also due to the complex chemical structure of these compounds. In this report the results of the influence of γ-radiation on the short circuit current in CuGaSe 2 are presented. The Co 6 0 with the quantum energy of 1.25 MeV was a source of radiation. The resistance was 10 2 kΩ at 300 K. The In-Ga eutectic was used as a contact. The measurements have been carried out at 77 K. The electrometer B7-30 was used for the short circuit current measurements, sensitivity of which is 10 -15 A. The intensity of γ-rays was 20 R/s, durability of radiation was 15 min. The spectrometer SPM-2 was used as a source of radiation of monoxrmator light. The spectral dependence of short circuit current of non radiated CuGaSe 2 crystal has a maximum at λ=700 nm (0.77 eV) with the half width of 0.26 eV. The maximum of short circuit current is in good agreement with the value 1.8 eV at 300 K. That is why one can assume that observed peak in J sc ∼∼f(λ) dependence with the maximum at 1.77 eV is due to electronic transitions from the valence band to conduction band. After radiation of CuGaSe 2 crystal new maximum is observed in the spectral dependence of short circuit current at λ=770 nm (1.61 eV) at 77 K. Splitting between the peaks is 0.13 eV. The appearance of the second peak maybe is due to the formation of radiation defects of acceptor type, which are located for 0.13 eV above than the top of valence band. The peak at 1.59 eV, which is due the donor-acceptor recombination, is observed in photoluminescence spectra. It is assumed that, Se vacancy forms the donor levels, Cu vacancy -acceptor levels

  6. Adrenomedullin increased the short-circuit current in the pig oviduct through chloride channels via the CGRP receptor: mediation by cAMP and calcium ions but not by nitric oxide.

    Science.gov (United States)

    Liao, S B; Cheung, K H; Cheung, M P L; To, Y T; O, W S; Tang, F

    2013-10-01

    The oviduct serves as a site for the fertilization of the ovum and the transport of the conceptus down to the uterus for implantation. In this study, we investigated the presence of adrenomedullin (ADM) and its receptor component proteins in the pig oviduct. The effect of ADM on oviductal secretion, the specific receptor, and the mechanisms involved were also investigated. The presence of ADM and its receptor component proteins in the pig oviduct were confirmed using immunostaining. Short-circuit current (I(sc)) technique was employed to study chloride ion secretion in the oviductal epithelium. ADM increased I(sc) through cAMP- and calcium-activated chloride channels, and this effect could be inhibited by the CGRP receptor antagonist, hCGRP8-37. In contrast, the nitric oxide synthase inhibitor, L-NG-nitroarginine methyl ester (L-NAME), could not block the effect of ADM on I(sc). In summary, ADM may increase oviductal fluid secretion via chloride secretion independent of the nitric oxide pathway for the transport of sperm and the conceptus.

  7. Enhancement of short-circuit current density in polymer bulk heterojunction solar cells comprising plasmonic silver nanowires

    Energy Technology Data Exchange (ETDEWEB)

    Yang, Yuzhao; Lin, Xiaofeng; Ou, Jiemei; Chen, Xudong, E-mail: cescxd@mail.sysu.edu.cn, E-mail: stszx@mail.sysu.edu.cn, E-mail: chenyj69@mail.sysu.edu.cn [Key Laboratory for Polymeric Composite and Functional Materials of Ministry of Education of China, Sun Yat-sen University, Guangzhou 510275 (China); Qing, Jian; Zhong, Zhenfeng; Zhou, Xiang, E-mail: cescxd@mail.sysu.edu.cn, E-mail: stszx@mail.sysu.edu.cn, E-mail: chenyj69@mail.sysu.edu.cn; Chen, Yujie, E-mail: cescxd@mail.sysu.edu.cn, E-mail: stszx@mail.sysu.edu.cn, E-mail: chenyj69@mail.sysu.edu.cn [State Key Laboratory of Optoelectronic Materials and Technologies, School of Physics and Engineering, Sun Yat-sen University, Guangzhou 510275 (China); Hu, Chenglong [Key Laboratory of Optoelectronic Chemical Materials and Devices of Ministry of Education, Jianghan University, Wuhan 430056 (China)

    2014-03-24

    We demonstrate that the influence of plasmonic effects based on silver nanowires (Ag NWs) on the characteristics of polymer solar cells (PSCs). The solution-processed Ag NWs are situated at the interface of anode buffer layer and active layer, which could enhance the performance especially the photocurrent of PSCs by scattering, localized surface plasmon resonance, and surface plasmon polaritons. Plasmonic effects are confirmed by the enhancement of extinction spectra, external quantum efficiency, and steady state photoluminescence. Consequently, the short-circuit current density (J{sub sc}) and power conversion efficiency enhance about 24% and 18%, respectively, under AM1.5 illumination when Ag NWs plasmonic nanostructure incorporated into PSCs.

  8. Small-bandgap polymer solar cells with unprecedented short-circuit current density and high fill factor.

    Science.gov (United States)

    Choi, Hyosung; Ko, Seo-Jin; Kim, Taehyo; Morin, Pierre-Olivier; Walker, Bright; Lee, Byoung Hoon; Leclerc, Mario; Kim, Jin Young; Heeger, Alan J

    2015-06-03

    Small-bandgap polymer solar cells (PSCs) with a thick bulk heterojunction film of 340 nm exhibit high power conversion efficiencies of 9.40% resulting from high short-circuit current density (JSC ) of 20.07 mA cm(-2) and fill factor of 0.70. This remarkable efficiency is attributed to maximized light absorption by the thick active layer and minimized recombination by the optimized lateral and vertical morphology through the processing additive. © 2015 WILEY-VCH Verlag GmbH & Co. KGaA, Weinheim.

  9. Short-circuit logic

    NARCIS (Netherlands)

    Bergstra, J.A.; Ponse, A.

    2010-01-01

    Short-circuit evaluation denotes the semantics of propositional connectives in which the second argument is only evaluated if the first argument does not suffice to determine the value of the expression. In programming, short-circuit evaluation is widely used. A short-circuit logic is a variant of

  10. Optimization of the short-circuit current in an InP nanowire array solar cell through opto-electronic modeling.

    Science.gov (United States)

    Chen, Yang; Kivisaari, Pyry; Pistol, Mats-Erik; Anttu, Nicklas

    2016-09-23

    InP nanowire arrays with axial p-i-n junctions are promising devices for next-generation photovoltaics, with a demonstrated efficiency of 13.8%. However, the short-circuit current in such arrays does not match their absorption performance. Here, through combined optical and electrical modeling, we study how the absorption of photons and separation of the resulting photogenerated electron-hole pairs define and limit the short-circuit current in the nanowires. We identify how photogenerated minority carriers in the top n segment (i.e. holes) diffuse to the ohmic top contact where they recombine without contributing to the short-circuit current. In our modeling, such contact recombination can lead to a 60% drop in the short-circuit current. To hinder such hole diffusion, we include a gradient doping profile in the n segment to create a front surface barrier. This approach leads to a modest 5% increase in the short-circuit current, limited by Auger recombination with increased doping. A more efficient approach is to switch the n segment to a material with a higher band gap, like GaP. Then, a much smaller number of holes is photogenerated in the n segment, strongly limiting the amount that can diffuse and disappear into the top contact. For a 500 nm long top segment, the GaP approach leads to a 50% higher short-circuit current than with an InP top segment. Such a long top segment could facilitate the fabrication and contacting of nanowire array solar cells. Such design schemes for managing minority carriers could open the door to higher performance in single- and multi-junction nanowire-based solar cells.

  11. Current distribution in LV networks during 1-phase MV short-circuit

    NARCIS (Netherlands)

    Waes, van J.B.M.; Provoost, F.; Merwe, van der J.; Cobben, J.F.G.; Deursen, van A.P.J.; van Riet, M.J.M.; Laan, van der P.C.T.

    2000-01-01

    This paper describes the consequences of a fault in a medium voltage network on the grounding systems at the LV-side. To study the current distribution and to verify the models, we deliberately introduced one phase to ground faults in the 10 kV floating MV network. The selected site was the end of a

  12. [Shunt and short circuit].

    Science.gov (United States)

    Rangel-Abundis, Alberto

    2006-01-01

    Shunt and short circuit are antonyms. In French, the term shunt has been adopted to denote the alternative pathway of blood flow. However, in French, as well as in Spanish, the word short circuit (court-circuit and cortocircuito) is synonymous with shunt, giving rise to a linguistic and scientific inconsistency. Scientific because shunt and short circuit made reference to a phenomenon that occurs in the field of the physics. Because shunt and short circuit are antonyms, it is necessary to clarify that shunt is an alternative pathway of flow from a net of high resistance to a net of low resistance, maintaining the stream. Short circuit is the interruption of the flow, because a high resistance impeaches the flood. This concept is applied to electrical and cardiovascular physiology, as well as to the metabolic pathways.

  13. Simultaneous improvement in short circuit current, open circuit voltage, and fill factor of polymer solar cells through ternary strategy.

    Science.gov (United States)

    An, Qiaoshi; Zhang, Fujun; Li, Lingliang; Wang, Jian; Sun, Qianqian; Zhang, Jian; Tang, Weihua; Deng, Zhenbo

    2015-02-18

    We present a smart strategy to simultaneously increase the short circuit current (Jsc), the open circuit voltage (Voc), and the fill factor (FF) of polymer solar cells (PSCs). A two-dimensional conjugated small molecule photovoltaic material (SMPV1), as the second electron donor, was doped into the blend system of poly(3-hexylthiophene) (P3HT) and [6,6]-phenyl-C71-butyric acid methyl (PC71BM) to form ternary PSCs. The ternary PSCs with 5 wt % SMPV1 doping ratio in donors achieve 4.06% champion power conversion efficiency (PCE), corresponding to about 21.2% enhancement compared with the 3.35% PCE of P3HT:PC71BM-based PSCs. The underlying mechanism on performance improvement of ternary PSCs can be summarized as (i) harvesting more photons in the longer wavelength region to increase Jsc; (ii) obtaining the lower mixed highest occupied molecular orbital (HOMO) energy level by incorporating SMPV1 to increase Voc; (iii) forming the better charge carrier transport channels through the cascade energy level structure and optimizing phase separation of donor/acceptor materials to increase Jsc and FF.

  14. Small-Molecule Solar Cells with Simultaneously Enhanced Short-Circuit Current and Fill Factor to Achieve 11% Efficiency.

    Science.gov (United States)

    Nian, Li; Gao, Ke; Jiang, Yufeng; Rong, Qikun; Hu, Xiaowen; Yuan, Dong; Liu, Feng; Peng, Xiaobin; Russell, Thomas P; Zhou, Guofu

    2017-08-01

    High-efficiency small-molecule-based organic photovoltaics (SM-OPVs) using two electron donors (p-DTS(FBTTh 2 ) 2 and ZnP) with distinctively different absorption and structural features are reported. Such a combination works well and synergically improves device short-circuit current density (J sc ) to 17.99 mA cm -2 and fill factor (FF) to 77.19%, yielding a milestone efficiency of 11%. To the best of our knowledge, this is the highest power conversion efficiency reported for SM-OPVs to date and the first time to combine high J sc over 17 mA cm -2 and high FF over 77% into one SM-OPV. The strategy of using multicomponent materials, with a selecting role of balancing varied electronic and structural necessities can be an important route to further developing higher performance devices. This development is important, which broadens the dimension and versatility of existing materials without much chemistry input. © 2017 WILEY-VCH Verlag GmbH & Co. KGaA, Weinheim.

  15. Radial direct bandgap p-i-n GaNP microwire solar cells with enhanced short circuit current

    Energy Technology Data Exchange (ETDEWEB)

    Sukrittanon, Supanee [Graduate Program of Materials Science and Engineering, University of California, San Diego, La Jolla, California 92037 (United States); Liu, Ren; Pan, Janet L. [Department of Electrical and Computer Engineering, University of California, San Diego, La Jolla, California 92037 (United States); Breeden, Michael C. [Department of Nanoengineering, University of California, San Diego, La Jolla, California 92037 (United States); Jungjohann, K. L. [Center for Integrated Nanotechnologies, Sandia National Laboratories, Albuquerque, New Mexico 87185 (United States); Tu, Charles W., E-mail: ctu@ece.ucsd.edu, E-mail: sdayeh@ece.ucsd.edu; Dayeh, Shadi A., E-mail: ctu@ece.ucsd.edu, E-mail: sdayeh@ece.ucsd.edu [Graduate Program of Materials Science and Engineering, University of California, San Diego, La Jolla, California 92037 (United States); Department of Electrical and Computer Engineering, University of California, San Diego, La Jolla, California 92037 (United States)

    2016-08-07

    We report the demonstration of dilute nitride heterostructure core/shell microwire solar cells utilizing the combination of top-down reactive-ion etching to create the cores (GaP) and molecular beam epitaxy to create the shells (GaNP). Systematic studies of cell performance over a series of microwire lengths, array periods, and microwire sidewall morphologies examined by transmission electron microscopy were conducted to shed light on performance-limiting factors and to optimize the cell efficiency. We show by microscopy and correlated external quantum efficiency characterization that the open circuit voltage is degraded primarily due to the presence of defects at the GaP/GaNP interface and in the GaNP shells, and is not limited by surface recombination. Compared to thin film solar cells in the same growth run, the microwire solar cells exhibit greater short circuit current but poorer open circuit voltage due to greater light absorption and number of defects in the microwire structure, respectively. The comprehensive understanding presented in this work suggests that performance benefits of dilute nitride microwire solar cells can be achieved by further tuning of the epitaxial quality of the underlying materials.

  16. Controlled Conjugated Backbone Twisting for an Increased Open-Circuit Voltage while Having a High Short-Circuit Current in Poly(hexylthiophene) Derivatives

    KAUST Repository

    Ko, Sangwon; Hoke, Eric T.; Pandey, Laxman; Hong, Sanghyun; Mondal, Rajib; Risko, Chad; Yi, Yuanping; Noriega, Rodrigo; McGehee, Michael D.; Bré das, Jean-Luc; Salleo, Alberto; Bao, Zhenan

    2012-01-01

    and charge-transfer state energy of the polymer:fullerene BHJ solar cells increased substantially with the degree of twist induced within the conjugated backbone-due to an increase in the polymer ionization potential-while the short-circuit current decreased

  17. Prospective single and multi-phase short-circuit current levels in the Dutch transmission, sub-transmission and distribution grids

    NARCIS (Netherlands)

    Janssen, A.L.J.; van Riet, M.J.M.; Smeets, R.P.P.; Kanters, J.; van den Akker, W.F.; Aanhaanen, G.L.P.

    2012-01-01

    As elsewhere in the world, also in the Netherlands utilities face an increase in the actual and future short-circuit current levels at all voltages. This development is provoked by the required increase in transmission capacity as well as the concentration of power generation capacity. Large

  18. The factors influencing nonlinear characteristics of the short-circuit current in dye-sensitized solar cells investigated by a numerical model.

    Science.gov (United States)

    Shi, Yushuai; Dong, Xiandui

    2013-06-24

    A numerical model for interpretation of the light-intensity-dependent nonlinear characteristics of the short-circuit current in dye-sensitized solar cells is suggested. The model is based on the continuity equation and includes the influences of the nongeminate recombination between electrons and electron acceptors in the electrolyte and the geminate recombination between electrons and oxidized dye molecules. The influences of the order and rate constant of the nongeminate recombination reaction, the light-absorption coefficient of the dye, the film thickness, the rate constant of geminate recombination, and the regeneration rate constant on the nonlinear characteristics of the short-circuit current are simulated and analyzed. It is proposed that superlinear and sublinear characteristics of the short-circuit current should be attributed to low electron-collection efficiency and low dye-regeneration efficiency, respectively. These results allow a deep understanding of the origin of the nonlinear characteristics of the short-circuit current in solar cells. Copyright © 2013 WILEY-VCH Verlag GmbH & Co. KGaA, Weinheim.

  19. Increased short circuit current in organic photovoltaic using high-surface area electrode based on ZnO nanowires decorated with CdTe quantum dots.

    Science.gov (United States)

    Aga, R S; Gunther, D; Ueda, A; Pan, Z; Collins, W E; Mu, R; Singer, K D

    2009-11-18

    A photosensitized high-surface area transparent electrode has been employed to increase the short circuit current of a photovoltaic device with a blend of poly(3-hexylthiophene) (P3HT) and (6,6)-phenyl C61 butyric acid methyl ester (PCBM) as the active layer. This is achieved by directly growing ZnO nanowires on indium tin oxide (ITO) film via a physical vapor method. The nanowire surface is then decorated with CdTe quantum dots by pulsed electron-beam deposition (PED). The nanowires alone provided a 20-fold increase in the short circuit current under visible light illumination. This was further increased by a factor of approximately 1.5 by the photosensitization effect of CdTe, which has an optical absorption of up to 820 nm.

  20. Analysis of the impact of connecting a larger number of small hydroelectric power plants to the short-circuit currents values and relay protection system of distribution network

    Directory of Open Access Journals (Sweden)

    Sučević Nikola

    2017-01-01

    Full Text Available In this paper the influence of a large number of small hydro power plants on the short-circuit currents is analysed, as well as the operation of the relay protection system within the real distribution network in Serbia. The necessary modification of the existing protection functions, as well as the implementation of the new proposed protection functions, are presented and discussed. Network modeling and analysis are performed using the program tool DIgSILENT PowerFactory.

  1. Controlled Conjugated Backbone Twisting for an Increased Open-Circuit Voltage while Having a High Short-Circuit Current in Poly(hexylthiophene) Derivatives

    KAUST Repository

    Ko, Sangwon

    2012-03-21

    Conjugated polymers with nearly planar backbones have been the most commonly investigated materials for organic-based electronic devices. More twisted polymer backbones have been shown to achieve larger open-circuit voltages in solar cells, though with decreased short-circuit current densities. We systematically impose twists within a family of poly(hexylthiophene)s and examine their influence on the performance of polymer:fullerene bulk heterojunction (BHJ) solar cells. A simple chemical modification concerning the number and placement of alkyl side chains along the conjugated backbone is used to control the degree of backbone twisting. Density functional theory calculations were carried out on a series of oligothiophene structures to provide insights on how the sterically induced twisting influences the geometric, electronic, and optical properties. Grazing incidence X-ray scattering measurements were performed to investigate how the thin-film packing structure was affected. The open-circuit voltage and charge-transfer state energy of the polymer:fullerene BHJ solar cells increased substantially with the degree of twist induced within the conjugated backbone-due to an increase in the polymer ionization potential-while the short-circuit current decreased as a result of a larger optical gap and lower hole mobility. A controlled, moderate degree of twist along the poly(3,4-dihexyl-2,2′:5′,2′′- terthiophene) (PDHTT) conjugated backbone led to a 19% enhancement in the open-circuit voltage (0.735 V) vs poly(3-hexylthiophene)-based devices, while similar short-circuit current densities, fill factors, and hole-carrier mobilities were maintained. These factors resulted in a power conversion efficiency of 4.2% for a PDHTT:[6,6]-phenyl-C 71-butyric acid methyl ester (PC 71BM) blend solar cell without thermal annealing. This simple approach reveals a molecular design avenue to increase open-circuit voltage while retaining the short-circuit current. © 2012 American

  2. Controlled conjugated backbone twisting for an increased open-circuit voltage while having a high short-circuit current in poly(hexylthiophene) derivatives.

    Science.gov (United States)

    Ko, Sangwon; Hoke, Eric T; Pandey, Laxman; Hong, Sanghyun; Mondal, Rajib; Risko, Chad; Yi, Yuanping; Noriega, Rodrigo; McGehee, Michael D; Brédas, Jean-Luc; Salleo, Alberto; Bao, Zhenan

    2012-03-21

    Conjugated polymers with nearly planar backbones have been the most commonly investigated materials for organic-based electronic devices. More twisted polymer backbones have been shown to achieve larger open-circuit voltages in solar cells, though with decreased short-circuit current densities. We systematically impose twists within a family of poly(hexylthiophene)s and examine their influence on the performance of polymer:fullerene bulk heterojunction (BHJ) solar cells. A simple chemical modification concerning the number and placement of alkyl side chains along the conjugated backbone is used to control the degree of backbone twisting. Density functional theory calculations were carried out on a series of oligothiophene structures to provide insights on how the sterically induced twisting influences the geometric, electronic, and optical properties. Grazing incidence X-ray scattering measurements were performed to investigate how the thin-film packing structure was affected. The open-circuit voltage and charge-transfer state energy of the polymer:fullerene BHJ solar cells increased substantially with the degree of twist induced within the conjugated backbone--due to an increase in the polymer ionization potential--while the short-circuit current decreased as a result of a larger optical gap and lower hole mobility. A controlled, moderate degree of twist along the poly(3,4-dihexyl-2,2':5',2''-terthiophene) (PDHTT) conjugated backbone led to a 19% enhancement in the open-circuit voltage (0.735 V) vs poly(3-hexylthiophene)-based devices, while similar short-circuit current densities, fill factors, and hole-carrier mobilities were maintained. These factors resulted in a power conversion efficiency of 4.2% for a PDHTT:[6,6]-phenyl-C(71)-butyric acid methyl ester (PC(71)BM) blend solar cell without thermal annealing. This simple approach reveals a molecular design avenue to increase open-circuit voltage while retaining the short-circuit current.

  3. Hybrid solar cells with outstanding short-circuit currents based on a room temperature soft-chemical strategy: the case of P3HT:Ag2S.

    Science.gov (United States)

    Lei, Yan; Jia, Huimin; He, Weiwei; Zhang, Yange; Mi, Liwei; Hou, Hongwei; Zhu, Guangshan; Zheng, Zhi

    2012-10-24

    P3HT:Ag(2)S hybrid solar cells with broad absorption from the UV to NIR band were directly fabricated on ITO glass by using a room temperature, low energy consumption, and low-cost soft-chemical strategy. The resulting Ag(2)S nanosheet arrays facilitate the construction of a perfect percolation structure with organic P3HT to form ordered bulk heterojunctions (BHJ); without interface modification, the assembled P3HT:Ag(2)S device exhibits outstanding short-circuit current densities (J(sc)) around 20 mA cm(-2). At the current stage, the optimized device exhibited a power conversion efficiency of 2.04%.

  4. A study on the short-circuit test by fault angle control and the recovery characteristics of the fault current limiter using coated conductor

    International Nuclear Information System (INIS)

    Park, D.K.; Kim, Y.J.; Ahn, M.C.; Yang, S.E.; Seok, B.-Y.; Ko, T.K.

    2007-01-01

    Superconducting fault current limiters (SFCLs) have been developed in many countries, and they are expected to be used in the recent electric power systems, because of their great efficiency for operating these power system stably. It is necessary for resistive FCLs to generate resistance immediately and to have a fast recovery characteristic after the fault clearance, because of re-closing operation. Short-circuit tests are performed to obtained current limiting operational and recovery characteristics of the FCL by a fault controller using a power switching device. The power switching device consists of anti-parallel connected thyristors. The fault occurs at the desired angle by controlling the firing angle of thyristors. Resistive SFCLs have different current limiting characteristics with respect to the fault angle in the first swing during the fault. This study deals with the short-circuit characteristic of FCL coils using two different YBCO coated conductors (CCs), 344 and 344s, by controlling the fault angle and experimental studies on the recovery characteristic by a small current flowing through the SFCL after the fault clearance. Tests are performed at various voltages applied to the SFCL in a saturated liquid nitrogen cooling system

  5. Grating-coupled surface plasmon enhanced short-circuit current in organic thin-film photovoltaic cells.

    Science.gov (United States)

    Baba, Akira; Aoki, Nobutaka; Shinbo, Kazunari; Kato, Keizo; Kaneko, Futao

    2011-06-01

    In this study, we demonstrate the fabrication of grating-coupled surface plasmon resonance (SPR) enhanced organic thin-film photovoltaic cells and their improved photocurrent properties. The cell consists of a grating substrate/silver/P3HT:PCBM/PEDOT:PSS structure. Blu-ray disk recordable substrates are used as the diffraction grating substrates on which silver films are deposited by vacuum evaporation. P3HT:PCBM films are spin-coated on silver/grating substrates. Low conductivity PEDOT:PSS/PDADMAC layer-by-layer ultrathin films deposited on P3HT:PCBM films act as the hole transport layer, whereas high conductivity PEDOT:PSS films deposited by spin-coating act as the anode. SPR excitations are observed in the fabricated cells upon irradiation with white light. Up to a 2-fold increase in the short-circuit photocurrent is observed when the surface plasmon (SP) is excited on the silver gratings as compared to that without SP excitation. The finite-difference time-domain simulation indicates that the electric field in the P3HT:PCBM layer can be increased using the grating-coupled SP technique. © 2011 American Chemical Society

  6. Adrenomedullin increases the short-circuit current in the rat prostate: Receptors, chloride channels, the effects of cAMP and calcium ions and implications on fluid secretion.

    Science.gov (United States)

    Liao, S B; Cheung, K H; Cheung, M P L; Wong, P F; O, W S; Tang, F

    2014-05-01

    In this study, we have investigated the effects of adrenomedullin on chloride and fluid secretion in the rat prostate. The presence of adrenomedullin (ADM) in rat prostate was confirmed using immunostaining, and the molecular species was determined using gel filtration chromatography coupled with an enzyme-linked assay for ADM. The effects of ADM on fluid secretion were studied by short-circuit current technique in a whole mount preparation of the prostate in an Ussing chamber. The results indicated that the ADM level was higher in the ventral than the dorso-lateral prostate and the major molecular species was the active peptide. ADM increased the short-circuit current through both the cAMP- and calcium-activated chloride channels in the ventral lobe, but only through the calcium-activated channels in the dorso-lateral lobe. These stimulatory effects were blocked by the calcitonin gene-related peptide (CGRP) receptor antagonist, hCGRP8-37. We conclude that ADM may regulate prostatic fluid secretion through the chloride channels, which may affect the composition of the seminal plasma bathing the spermatozoa and hence fertility. © 2014 American Society of Andrology and European Academy of Andrology.

  7. Design and flight performance evaluation of the Mariners 6, 7, and 9 short-circuit current, open-circuit voltage transducers

    Science.gov (United States)

    Patterson, R. E.

    1973-01-01

    The purpose of the short-circuit voltage transducer is to provide engineering data to aid the evaluation of array performance during flight. The design, fabrication, calibration, and in-flight performance of the transducers onboard the Mariner 6, 7 and 9 spacecrafts are described. No significant differences were observed in the in-flight electrical performance of the three transducers. The transducers did experience significant losses due to coverslides or adhesive darkening, increased surface reflection, or spectral shifts within coverslide assembly. Mariner 6, 7 and 9 transducers showed non-cell current degradations of 3-1/2%, 3%, and 4%, respectively at Mars encounter and 6%, 3%, and 4-12%, respectively at end of mission. Mariner 9 solar Array Test 2 showed 3-12% current degradation while the transducer showed 4-12% degradation.

  8. Improvement of Short-Circuit Current Density in Dye-Sensitized Solar Cells Using Sputtered Nanocolumnar TiO2 Compact Layer

    Directory of Open Access Journals (Sweden)

    Lung-Chien Chen

    2010-01-01

    Full Text Available The effect of a nanocolumnar TiO2 compact layer in dye-sensitized solar cells (DSSCs was examined. Such a compact layer was sputtered on a glass substrate with an indium tin oxide (ITO film using TiO2 powder as the raw material, with a thickness of ~100 nm. The compact layer improved the short-circuit current density and the efficiency of conversion of solar energy to electricity by the DSSC by 53.37% and 59.34%, yielding values of 27.33 mA/cm2 and 9.21%, respectively. The performance was attributed to the effective electron pathways in the TiO2 compact layer, which reduced the back reaction by preventing direct contact between the redox electrolyte and the conductive substrate.

  9. Effect of dislocations on the open-circuit voltage, short-circuit current and efficiency of heteroepitaxial indium phosphide solar cells

    Science.gov (United States)

    Jain, Raj K.; Flood, Dennis J.

    1990-01-01

    Excellent radiation resistance of indium phosphide solar cells makes them a promising candidate for space power applications, but the present high cost of starting substrates may inhibit their large scale use. Thin film indium phosphide cells grown on Si or GaAs substrates have exhibited low efficiencies, because of the generation and propagation of large number of dislocations. Dislocation densities were calculated and its influence on the open circuit voltage, short circuit current, and efficiency of heteroepitaxial indium phosphide cells was studied using the PC-1D. Dislocations act as predominant recombination centers and are required to be controlled by proper transition layers and improved growth techniques. It is shown that heteroepitaxial grown cells could achieve efficiencies in excess of 18 percent AMO by controlling the number of dislocations. The effect of emitter thickness and surface recombination velocity on the cell performance parameters vs. dislocation density is also studied.

  10. Short-circuit impedance measurement

    DEFF Research Database (Denmark)

    Pedersen, Knud Ole Helgesen; Nielsen, Arne Hejde; Poulsen, Niels Kjølstad

    2003-01-01

    Methods for estimating the short-circuit impedance in the power grid are investigated for various voltage levels and situations. The short-circuit impedance is measured, preferably from naturally occurring load changes in the grid, and it is shown that such a measurement system faces different...

  11. Cell short circuit, preshort signature

    Science.gov (United States)

    Lurie, C.

    1980-01-01

    Short-circuit events observed in ground test simulations of DSCS-3 battery in-orbit operations are analyzed. Voltage signatures appearing in the data preceding the short-circuit event are evaluated. The ground test simulation is briefly described along with performance during reconditioning discharges. Results suggest that a characteristic signature develops prior to a shorting event.

  12. Estimating the short-circuit impedance

    DEFF Research Database (Denmark)

    Nielsen, Arne Hejde; Pedersen, Knud Ole Helgesen; Poulsen, Niels Kjølstad

    1997-01-01

    A method for establishing a complex value of the short-circuit impedance from naturally occurring variations in voltage and current is discussed. It is the symmetrical three phase impedance at the fundamental grid frequency there is looked for. The positive sequence components in voltage...... and current are derived each period, and the short-circuit impedance is estimated from variations in these components created by load changes in the grid. Due to the noisy and dynamic grid with high harmonic distortion it is necessary to threat the calculated values statistical. This is done recursively...... through a RLS-algorithm. The algorithms have been tested and implemented on a PC at a 132 kV substation supplying a rolling mill. Knowing the short-circuit impedance gives the rolling mill an opportunity to adjust the arc furnace operation to keep flicker below a certain level. Therefore, the PC performs...

  13. SITE WIDE SHORT CIRCUIT STUDY ASSESSMENT

    International Nuclear Information System (INIS)

    CARRATT, R.T.

    2004-01-01

    The Department of Energy requested that Fluor Hanford develop a plan to update the electrical distribution studies for FH managed facilities. Toward this end, an assessment of FH's nuclear facilities was performed to determine whether a current short circuit study of the facility electrical distribution system exists, and the status of such study. This report presents the methodology and results of that assessment. The assessment identified 29 relevant facilities. Of these, a short circuit study could not be identified for 15 facilities. A short circuit study was found to exist for fourteen facilities, however, of these 14, four were not released into a controlled document system, and two were not performed for the entire electrical distribution system. It is recommended that for four of the facilities no further action is required based upon the limited nature of the existing electrical system, or as in the case of PFP, the status of the existing short circuit study was determined adequate. For the majority of the facilities without a short circuit study, it is recommended that one is performed, and released into a controlled document system. Two facilities require further evaluation due to missing or conflicting documentation. For the remainder of the facilities, the recommendations are to review and revise as appropriate the existing study, and release into a controlled document system. A summation of the recommendations is presented

  14. Textbook Error: Short Circuiting on Electrochemical Cell

    Science.gov (United States)

    Bonicamp, Judith M.; Clark, Roy W.

    2007-01-01

    Short circuiting an electrochemical cell is an unreported but persistent error in the electrochemistry textbooks. It is suggested that diagrams depicting a cell delivering usable current to a load be postponed, the theory of open-circuit galvanic cells is explained, the voltages from the tables of standard reduction potentials is calculated and…

  15. An Icepak-PSpice Co-Simulation Method to Study the Impact of Bond Wires Fatigue on the Current and Temperature Distribution of IGBT Modules under Short-Circuit

    DEFF Research Database (Denmark)

    Wu, Rui; Iannuzzo, Francesco; Wang, Huai

    2014-01-01

    Bond wires fatigue is one of the dominant failure mechanisms of IGBT modules. Prior-art research mainly focuses on its impact on the end-of-life failure, while its effect on the short-circuit capability of IGBT modules is still an open issue. This paper proposes a new electro-thermal simulation...... approach enabling analyze the impact of the bond wires fatigue on the current and temperature distribution on IGBT chip surface under short-circuit. It is based on an Icepack-PSpice co-simulation by taking the advantage of both a finite element thermal model and an advanced PSpice-based multi-cell IGBT...

  16. Detecting short circuits during assembly

    Science.gov (United States)

    Deboo, G. J.

    1980-01-01

    Detector circuit identifies shorts between bus bars of electronic equipment being wired. Detector sounds alarm and indicates which planes are shorted. Power and ground bus bars are scanned continuously until short circuit occurs.

  17. The short-circuit test results of 6.9 kV/2.3 kV 400 kVA-class YBCO model transformer with fault current limiting function

    International Nuclear Information System (INIS)

    Tomioka, A.; Bohno, T.; Kakami, S.; Isozaki, M.; Watanabe, K.; Toyama, K.; Sugiyama, S.; Konno, M.; Gosho, Y.; Okamoto, H.; Hayashi, H.; Tsutsumi, T.; Iwakuma, M.; Saito, T.; Tanabe, K.; Shiohara, Y.

    2013-01-01

    Highlights: ► We manufactured the 400 kV A-class YBCO model transformer with FCL function. ► Short-circuit test was performed by applying 6.9 kV on primary side. ► The short-circuit current was limited to 174 A for a prospective current of 559 A. ► It agreed with the design and we also confirmed the I c did not degrade. ► The results suggest the possibility to design YBCO transformers with FCL function. -- Abstract: We are developing an elemental technology for 66/6.9 kV 20 MVA-class superconducting power transformer with fault current limiting function. In order to obtain the characteristics of YBCO conductor when the AC over current supplied to the conductor, the model coils were manufactured with YBCO tapes and tested. Based on these results, we manufactured the 6.9 kV/2.3 kV 400 kVA-class YBCO model transformer with fault current limiting function and performed short-circuit test. At the 0.25 s after short-circuit, the short-circuit current of primary winding was limited to about 174 A for a prospective current of 559 A. It was consistent with the design. The I–V characteristics of the winding did not change before and after the test. We consider the model transformer to be able to withstand AC over-current with the function of current limiting. The results suggest the possibility to design YBCO superconducting transformers with fault current limiting function for practical power grid

  18. Calculations of the displacement damage and short-circuit current degradation in proton irradiated (AlGa)As-GaAs solar cells

    Science.gov (United States)

    Yeh, C. S.; Li, S. S.; Loo, R. Y.

    1987-01-01

    A theoretical model for computing the displacement damage defect density and the short-circuit current (I sub sc) degradation in proton-irradiated (AlGa)As-GaAs p-n junction solar cells is presented. Assumptions were made with justification that the radiation induced displacement defects form an effective recombination center which controls the electron and hole lifetimes in the junction space charge region and in the n-GaAs active layer of the irradiated GaAs p-n junction cells. The degradation of I sub sc in the (AlGa)As layer was found to be negligible compared to the total degradation. In order to determine the I sub sc degradation, the displacement defect density, path length, range, reduced energy after penetrating a distance x, and the average number of displacements formed by one proton scattering event were first calculated. The I sub sc degradation was calculated by using the electron capture cross section in the p-diffused layer and the hole capture cross section in the n-base layer as well as the wavelength dependent absorption coefficients. Excellent agreement was found between the researchers calculated values and the measured I sub sc in the proton irradiated GaAs solar cells for proton energies of 100 KeV to 10 MeV and fluences from 10 to the 10th power p/square cm to 10 to the 12th power p/square cm.

  19. The short circuit current improvement in P3HT:PCBM based polymer solar cell by introducing PSBTBT as additional electron donor.

    Science.gov (United States)

    Sun, Lu; Shen, Liang; Mengd, Fanxu; Xu, Peng; Guo, Wenbin; Ruan, Shengping

    2014-05-01

    Here we demonstrate the influence of electron-donating polymer addition on the performance of poly(3-hexylthiophene) (P3HT):1 -(3-methoxycarbonyl)-propyl-1-phenyl-(6,6) C61 (PCBM) solar cells. Poly[(4,42-bis(2-ethylhexyl) dithieno [3,2-b:22,32-d] silole)-2,6-diylalt-(2,1,3-benzothiadiazole)-4,7-diyl] (PSBTBT) was chosen as the electron-donating polymer to improve the short circuit current (J(sc)) due to its distinct absorption in the near-IR range and similar HOMO level with that of P3HT. In the study, we found that J(sc) was improved for ternary blend (P3HT:PSBTBT:PCBM) solar cells. The dependence of device performance was investigated. J(sc) got decreased with increasing the ratio of PSBTBT. Result showed that J(sc) of ternary blend solar cells was improved greatly after thermal annealing at 150 degrees C, close to that of the binary blend (PSBTBT:PCBM) solar cells.

  20. Effects of arginine vasotocin and mesotocin on the activation and development of amiloride-blockable short-circuit current across larval, adult, and cultured larval bullfrog skins.

    Science.gov (United States)

    Takada, Makoto; Fujimaki-Aoba, Kayo; Hokari, Shigeru

    2010-03-01

    Amphibian skin has osmoregulatory functions, with Na(+) crossing from outside to inside. Na(+) transport can be measured as the short-circuit current (SCC). We investigated the short-term and long-term effects of arginine vasotocin (AVT) and mesotocin (MT) (which modulate Na(+) transport) on the activation and development of an amiloride-blockable SCC (adult-type feature) in larval, adult, and corticoid-cultured larval bullfrog skins. We found: (1) AVT-receptor (AVT-R) and MT-receptor (MT-R) mRNAs could be detected in both larval and adult skins, (2) in the short term (within 60 min), the larval SCC (amiloride-stimulated SCC) was increased by AVT, forskolin, and MT, suggesting that AVT and MT did not activate the inactive ENaC (epithelial sodium channel) protein thought to be expressed in larval skin, (3) in the short term (within 90 min), AVT, forskolin, and MT stimulated the adult SCC (amiloride-blockable SCC), (4) AVT and MT increased both the larval and adult SCC via receptors insensitive to OPC-21268 (an antagonist of the V(1)-type receptor), OPC-31260 (an antagonist of the V(2)-type receptor), and ([d(CH(2))(5),Tyr(Me)(2),Thr(4),Orn(8),des-Gly-NH (2) (9) ]VT) (an antagonist of the oxytocin receptor), (5) culturing EDTA-treated larval skin with corticoids supplemented with AVT (1 microM) or MT (1 microM) for 2 weeks (long-term effects of AVT and MT) did not alter the corticoid-induced development of an amiloride-blockable SCC (adult-type feature). AVT and MT thus have the potential to stimulate SCC though channels that are already expressed, but they may not influence the development of the amiloride-blockable SCC (an adult-type feature) in larval skin.

  1. On Demand Internal Short Circuit Device Enables Verification of Safer, Higher Performing Battery Designs

    Energy Technology Data Exchange (ETDEWEB)

    Darcy, Eric; Keyser, Matthew

    2017-05-15

    The Internal Short Circuit (ISC) device enables critical battery safety verification. With the aluminum interstitial heat sink between the cells, normal trigger cells cannot be driven into thermal runaway without excessive temperature bias of adjacent cells. With an implantable, on-demand ISC device, thermal runaway tests show that the conductive heat sinks protected adjacent cells from propagation. High heat dissipation and structural support of Al heat sinks show high promise for safer, higher performing batteries.

  2. Short-circuit experiments on a high Tc-superconducting cable conductor

    DEFF Research Database (Denmark)

    Tønnesen, Ole; Jensen, E.H.; Traholt, C.

    2002-01-01

    A high temperature superconductor (HTS) cable conductor (CC) with a critical current of 2.1 kA was tested over a range of short-circuit currents up to 20 kA. The duration of the short-circuit currents is 1 s. Between each short-circuit test the critical current of the HTS CC was measured in order...

  3. 30 CFR 75.518-2 - Incandescent lamps, overload and short circuit protection.

    Science.gov (United States)

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Incandescent lamps, overload and short circuit...-General § 75.518-2 Incandescent lamps, overload and short circuit protection. Incandescent lamps installed... or direct current feeder circuits, need not be provided with separate short circuit or overload...

  4. Three-phase short circuit calculation method based on pre-computed surface for doubly fed induction generator

    Science.gov (United States)

    Ma, J.; Liu, Q.

    2018-02-01

    This paper presents an improved short circuit calculation method, based on pre-computed surface to determine the short circuit current of a distribution system with multiple doubly fed induction generators (DFIGs). The short circuit current, injected into power grid by DFIG, is determined by low voltage ride through (LVRT) control and protection under grid fault. However, the existing methods are difficult to calculate the short circuit current of DFIG in engineering practice due to its complexity. A short circuit calculation method, based on pre-computed surface, was proposed by developing the surface of short circuit current changing with the calculating impedance and the open circuit voltage. And the short circuit currents were derived by taking into account the rotor excitation and crowbar activation time. Finally, the pre-computed surfaces of short circuit current at different time were established, and the procedure of DFIG short circuit calculation considering its LVRT was designed. The correctness of proposed method was verified by simulation.

  5. Capacitive short circuit detection in transformer core laminations

    International Nuclear Information System (INIS)

    Schulz, Carl A.; Duchesne, Stephane; Roger, Daniel; Vincent, Jean-Noel

    2008-01-01

    A capacitive measurement procedure is proposed that serves to detect burr-induced short circuits in transformer core laminations. The tests are conducted on stacks of transformer steel sheets as used for transformer core production and yield a short-circuit probability indicative of the additional eddy current losses to be expected. Applied during the assembly of transformer cores, the measurements can help to decide whether the burr treatment process is working efficiently or has to be readjusted

  6. Improved Short-Circuit Protection for Power Cells in Series

    Science.gov (United States)

    Davies, Francis

    2008-01-01

    A scheme for protection against short circuits has been devised for series strings of lithium electrochemical cells that contain built-in short-circuit protection devices, which go into a high-resistance, current-limiting state when heated by excessive current. If cells are simply connected in a long series string to obtain a high voltage and a short circuit occurs, whichever short-circuit protection device trips first is exposed to nearly the full string voltage, which, typically, is large enough to damage the device. Depending on the specific cell design, the damage can defeat the protective function, cause a dangerous internal short circuit in the affected cell, and/or cascade to other cells. In the present scheme, reverse diodes rated at a suitably high current are connected across short series sub-strings, the lengths of which are chosen so that when a short-circuit protection device is tripped, the voltage across it does not exceed its rated voltage. This scheme preserves the resetting properties of the protective devices. It provides for bypassing of cells that fail open and limits cell reversal, though not as well as does the more-expensive scheme of connecting a diode across every cell.

  7. Investigation on the Short Circuit Safe Operation Area of SiC MOSFET Power Modules

    DEFF Research Database (Denmark)

    Reigosa, Paula Diaz; Luo, Haoze; Iannuzzo, Francesco

    2016-01-01

    This paper gives a better insight of the short circuit capability of state-of-the-art SiC MOSFET power modules rated at 1.2 kV by highlighting the physical limits under different operating conditions. Two different failure mechanisms have been identified, both reducing the short-circuit capability...... of SiC power modules in respect to discrete SiC devices. Based on such failure mechanisms, two short circuit criteria (i.e., short circuit current-based criterion and gate voltage-based criterion) are proposed in order to ensure their robustness under short-circuit conditions. A Safe Operation Area (SOA...

  8. A Short-Circuit Safe Operation Area Identification Criterion for SiC MOSFET Power Modules

    DEFF Research Database (Denmark)

    Reigosa, Paula Diaz; Iannuzzo, Francesco; Luo, Haoze

    2017-01-01

    This paper proposes a new method for the investigation of the short-circuit safe operation area (SCSOA) of state-of-the-art SiC MOSFET power modules rated at 1.2 kV based on the variations in SiC MOSFET electrical parameters (e.g., short-circuit current and gate–source voltage). According...... to the experimental results, two different failure mechanisms have been identified, both reducing the short-circuit capability of SiC power modules with respect to discrete SiC devices. Based on such failure mechanisms, two short-circuit safety criteria have been formulated: 1) the short-circuit...

  9. Wireless system for location of permanent faults by short circuit current monitoring in electric power distribution network; Sistema wireless para localizacao de faltas permanentes atraves da monitoracao da corrente de curto-circuito em redes de distribuicao de energia eletrica

    Energy Technology Data Exchange (ETDEWEB)

    Machado, A.G.; Correa, A.C.; Machado, R.N. das M.; Ferreira, A.M.D.; Pinto, J.A.C. [Instituto Federal de Educacao, Ciencia e Tecnologia do Para (IFPA), Belem, PA (Brazil)], E-mail: alcidesmachado000@yahoo.com.br; Barra Junior, W. [Universidade Federal do Para (UFPA), Belem, PA (Brazil). Inst. de Tecnologia. Faculdade de Engenharia Eletrica], E-mail: walbarra@ufpa.br

    2009-07-01

    This paper presents the development of an automatic system for permanent short-circuits location in medium voltage (13.8 kV) electric power system distribution feeders, by indirect monitoring of the line current. When a permanent failure occurs, the developed system uses mobile telephony (GSM) text messages (SMS) to inform the power company operation center where the failure most likely took place. With this information in real time, the power company operation center may provide the network restoration in a faster and efficient way. (author)

  10. Relationships between body mass index and short-circuit current in human duodenal and colonic mucosal biopsies. Osbak PS, Bindslev N, Hansen MB. Acta Physiol (Oxf). 2011 Jan;201(1):47-53

    DEFF Research Database (Denmark)

    Osbak, Philip Samuel; Bindslev, Niels; Berner-Hansen, Mark

    2011-01-01

    Aim: Retrospectively, to investigate the relationship between body mass index (BMI) and basal electrogenic transport as measured by short-circuit current (SCC) in human duodenal and colonic mucosal biopsies. Methods: The study included biopsies from mucosa of normal appearance in the sigmoid colon...... and >25 kg m)2). Statistical significance was assessed by the unpaired t-test or Wilcoxon rank-sum test. Correlation coefficients were calculated by Pearson product moment correlation. Results: In colonic biopsies, basal SCC (mean standard deviation) was significantly higher in 59 biopsies from 30...

  11. Shapeable short circuit resistant capacitor

    Science.gov (United States)

    Taylor, Ralph S.; Myers, John D.; Baney, William J.

    2015-10-06

    A ceramic short circuit resistant capacitor that is bendable and/or shapeable to provide a multiple layer capacitor that is extremely compact and amenable to desirable geometries. The capacitor that exhibits a benign failure mode in which a multitude of discrete failure events result in a gradual loss of capacitance. Each event is a localized event in which localized heating causes an adjacent portion of one or both of the electrodes to vaporize, physically cleaning away electrode material from the failure site. A first metal electrode, a second metal electrode, and a ceramic dielectric layer between the electrodes are thin enough to be formed in a serpentine-arrangement with gaps between the first electrode and the second electrode that allow venting of vaporized electrode material in the event of a benign failure.

  12. Development of a safety case for the use of current limiting devices to manage short circuit currents on electrical distribution networks. Final report

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2004-07-01

    The original objective of this study was to review the safety issues associated with the use of current limiting devices and to write a risk assessment in accordance with good practice. But, when legislative procedures became apparent, the scope was changed to include involvement with the HSE, the DTI and Ofgem. It turned out that it would have been very difficult to write a safety case that would satisfy all of the agencies, or a risk assessment that would cover all applications. The scope of the study was therefore changed to focus on how the existing barriers should be tackled and the implications of the existing legislation. The approach to the study is described; it included reviews of background information and literature, questionnaires to manufacturers, a review of the reliability and hazards of the devices, and a review of UK safety legislation. The Final Report describes all this and includes discussion on the consequences of failure of fault current limiting devices, control measures which could be used to minimise risk, and recommendations for a way forward.

  13. Short- circuit tests of circuit breakers

    OpenAIRE

    Chorovský, P.

    2015-01-01

    This paper deals with short-circuit tests of low voltage electrical devices. In the first part of this paper, there are described basic types of short- circuit tests and their principles. Direct and indirect (synthetic) tests with more details are described in the second part. Each test and principles are explained separately. Oscilogram is obtained from short-circuit tests of circuit breakers at laboratory. The aim of this research work is to propose a test circuit for performing indirect test.

  14. High performance of PbSe/PbS core/shell quantum dot heterojunction solar cells: short circuit current enhancement without the loss of open circuit voltage by shell thickness control.

    Science.gov (United States)

    Choi, Hyekyoung; Song, Jung Hoon; Jang, Jihoon; Mai, Xuan Dung; Kim, Sungwoo; Jeong, Sohee

    2015-11-07

    We fabricated heterojunction solar cells with PbSe/PbS core shell quantum dots and studied the precisely controlled PbS shell thickness dependency in terms of optical properties, electronic structure, and solar cell performances. When the PbS shell thickness increases, the short circuit current density (JSC) increases from 6.4 to 11.8 mA cm(-2) and the fill factor (FF) enhances from 30 to 49% while the open circuit voltage (VOC) remains unchanged at 0.46 V even with the decreased effective band gap. We found that the Fermi level and the valence band maximum level remain unchanged in both the PbSe core and PbSe/PbS core/shell with a less than 1 nm thick PbS shell as probed via ultraviolet photoelectron spectroscopy (UPS). The PbS shell reduces their surface trap density as confirmed by relative quantum yield measurements. Consequently, PbS shell formation on the PbSe core mitigates the trade-off relationship between the open circuit voltage and the short circuit current density. Finally, under the optimized conditions, the PbSe core with a 0.9 nm thick shell yielded a power conversion efficiency of 6.5% under AM 1.5.

  15. Estimation of expected short-circuit current levels in and circuit-breaker requirements for the 330 to 750 kV networks of the southern integrated power grid

    Energy Technology Data Exchange (ETDEWEB)

    Krivushkin, L.F.; Gorazeeva, T.F.

    1978-08-01

    Studies were made in order to project the operating levels in the Southern Integrated Power Grid to the year 2000. The short-circuit current levels and, the requirements which circuit breakers will have to meet are estimated. A gradual transition from 330 to 750 kV generation is foreseen, with 330 kV networks remaining only for a purely distribution service. The number of 330 kV line hookups and the number of circuit breakers at nodal points (stations and substations) will not change significantly, they will account for 40% of all circuit breakers installed in 25% of all nodal points. Short-circuit currents are expected to reach the 46 kA level in 750 kV networks and 63 kA (standing wave voltage 1.5 to 2.5 kV/microsecond) in 330 kV networks. These are the ratings of circuit breakers; of the 63 kA ones 150 will be needed by 1980--1990 and 400 by 1990--2000. It will also be eventually worthwhile to install circuit breakers with a 63 kA-750 kV rating.

  16. The Short Circuit Model of Reading.

    Science.gov (United States)

    Lueers, Nancy M.

    The name "short circuit" has been given to this model because, in many ways, it adequately describes what happens bioelectrically in the brain. The "short-circuiting" factors include linguistic, sociocultural, attitudinal and motivational, neurological, perceptual, and cognitive factors. Research is reviewed on ways in which each one affects any…

  17. A multilayer electro-thermal model of pouch battery during normal discharge and internal short circuit process

    International Nuclear Information System (INIS)

    Chen, Mingbiao; Bai, Fanfei; Song, Wenji; Lv, Jie; Lin, Shili

    2017-01-01

    Highlights: • 2D network equivalent circuit considers the interplay of cell units. • The temperature non-uniformity Φ of multilayer model is bigger than that of lumped model. • The temperature non-uniformity is quantified and the reason of non-uniformity is analyzed. • Increasing the thermal conductivity of the separator can effectively relieve the heat spot effect of ISC. - Abstract: As the electrical and thermal characteristic will affect the batteries’ safety, performance, calendar life and capacity fading, an electro-thermal coupled model for pouch battery LiFePO_4/C is developed in normal discharge and internal short circuit process. The battery is discretized into many cell elements which are united as a 2D network equivalent circuit. The electro-thermal model is solved with finite difference method. Non-uniformity of current distribution and temperature distribution is simulated and the result is validated with experiment data at various discharge rates. Comparison of the lumped model and the multilayer structure model shows that the temperature non-uniformity Φ of multilayer model is bigger than that of lumped model and shows more precise. The temperature non-uniformity is quantified and the reason of non-uniformity is analyzed. The electro-thermal model can also be used to guide the safety design of battery. The temperature of the ISC element near tabs is the highest because the equivalent resistance of the external circuit (not including the ISC element) is the smallest when the resistance of cell units is small. It is found that increasing the thermal conductivity of integrated layer can effectively relieve the heat spot effect of ISC.

  18. A Comprehensive Investigation on the Short Circuit Performance of MW-level IGBT Power Modules

    DEFF Research Database (Denmark)

    Wu, Rui; Reigosa, Paula Diaz; Iannuzzo, Francesco

    2015-01-01

    This paper investigates the short circuit performance of commercial 1.7 kV / 1 kA IGBT power modules by means of a 6 kA Non-Destructive-Tester. A mismatched current distribution among the parallel chips has been observed, which can reduce the short circuit capability of the IGBT power module unde...... short circuit conditions. Further Spice simulations reveal that the stray parameters inside the module play an important role in contributing to such a phenomenon....

  19. Short circuit in deep brain stimulation.

    Science.gov (United States)

    Samura, Kazuhiro; Miyagi, Yasushi; Okamoto, Tsuyoshi; Hayami, Takehito; Kishimoto, Junji; Katano, Mitsuo; Kamikaseda, Kazufumi

    2012-11-01

    The authors undertook this study to investigate the incidence, cause, and clinical influence of short circuits in patients treated with deep brain stimulation (DBS). After the incidental identification of a short circuit during routine follow-up, the authors initiated a policy at their institution of routinely evaluating both therapeutic impedance and system impendence at every outpatient DBS follow-up visit, irrespective of the presence of symptoms suggesting possible system malfunction. This study represents a report of their findings after 1 year of this policy. Implanted DBS leads exhibiting short circuits were identified in 7 patients (8.9% of the patients seen for outpatient follow-up examinations during the 12-month study period). The mean duration from DBS lead implantation to the discovery of the short circuit was 64.7 months. The symptoms revealing short circuits included the wearing off of therapeutic effect, apraxia of eyelid opening, or dysarthria in 6 patients with Parkinson disease (PD), and dystonia deterioration in 1 patient with generalized dystonia. All DBS leads with short circuits had been anchored to the cranium using titanium miniplates. Altering electrode settings resulted in clinical improvement in the 2 PD cases in which patients had specific symptoms of short circuits (2.5%) but not in the other 4 cases. The patient with dystonia underwent repositioning and replacement of a lead because the previous lead was located too anteriorly, but did not experience symptom improvement. In contrast to the sudden loss of clinical efficacy of DBS caused by an open circuit, short circuits may arise due to a gradual decrease in impedance, causing the insidious development of neurological symptoms via limited or extended potential fields as well as shortened battery longevity. The incidence of short circuits in DBS may be higher than previously thought, especially in cases in which DBS leads are anchored with miniplates. The circuit impedance of DBS

  20. Quantifying and Reducing Curve-Fitting Uncertainty in Isc

    Energy Technology Data Exchange (ETDEWEB)

    Campanelli, Mark; Duck, Benjamin; Emery, Keith

    2015-06-14

    Current-voltage (I-V) curve measurements of photovoltaic (PV) devices are used to determine performance parameters and to establish traceable calibration chains. Measurement standards specify localized curve fitting methods, e.g., straight-line interpolation/extrapolation of the I-V curve points near short-circuit current, Isc. By considering such fits as statistical linear regressions, uncertainties in the performance parameters are readily quantified. However, the legitimacy of such a computed uncertainty requires that the model be a valid (local) representation of the I-V curve and that the noise be sufficiently well characterized. Using more data points often has the advantage of lowering the uncertainty. However, more data points can make the uncertainty in the fit arbitrarily small, and this fit uncertainty misses the dominant residual uncertainty due to so-called model discrepancy. Using objective Bayesian linear regression for straight-line fits for Isc, we investigate an evidence-based method to automatically choose data windows of I-V points with reduced model discrepancy. We also investigate noise effects. Uncertainties, aligned with the Guide to the Expression of Uncertainty in Measurement (GUM), are quantified throughout.

  1. Quantifying and Reducing Curve-Fitting Uncertainty in Isc: Preprint

    Energy Technology Data Exchange (ETDEWEB)

    Campanelli, Mark; Duck, Benjamin; Emery, Keith

    2015-09-28

    Current-voltage (I-V) curve measurements of photovoltaic (PV) devices are used to determine performance parameters and to establish traceable calibration chains. Measurement standards specify localized curve fitting methods, e.g., straight-line interpolation/extrapolation of the I-V curve points near short-circuit current, Isc. By considering such fits as statistical linear regressions, uncertainties in the performance parameters are readily quantified. However, the legitimacy of such a computed uncertainty requires that the model be a valid (local) representation of the I-V curve and that the noise be sufficiently well characterized. Using more data points often has the advantage of lowering the uncertainty. However, more data points can make the uncertainty in the fit arbitrarily small, and this fit uncertainty misses the dominant residual uncertainty due to so-called model discrepancy. Using objective Bayesian linear regression for straight-line fits for Isc, we investigate an evidence-based method to automatically choose data windows of I-V points with reduced model discrepancy. We also investigate noise effects. Uncertainties, aligned with the Guide to the Expression of Uncertainty in Measurement (GUM), are quantified throughout.

  2. Research Tool to Evaluate the Safety Response of Lithium Batteries to an Internal Short Circuit

    Energy Technology Data Exchange (ETDEWEB)

    Keyser, Matthew; Darcy, Eric; Pesaran, Ahmad

    2016-06-19

    Li-ion cells provide the highest specific energy and energy density rechargeable battery with the longest life. Many safety incidents that take place in the field originate due to an internal short that was not detectable or predictable at the point of manufacture. NREL's internal short circuit (ISC) device is capable of simulating shorts and produces consistent and reproducible results. The cell behaves normally until the ISC device is activated wherein a latent defect (i.e., built into the cell during manufacturing) gradually moves into position to create an internal short while the battery is in use, providing relevant data to verify abuse models. The ISC device is an effective tool for studying the safety features of parts of Li-ion batteries.

  3. The short-circuit concept used in field equivalence principles

    DEFF Research Database (Denmark)

    Appel-Hansen, Jørgen

    1990-01-01

    In field equivalence principles, electric and magnetic surface currents are specified and considered as impressed currents. Often the currents are placed on perfect conductors. It is shown that these currents can be treated through two approaches. The first approach is decomposition of the total...... field into partial fields caused by the individual impressed currents. When this approach is used, it is shown that, on a perfect electric (magnetic) conductor, impressed electric (magnetic) surface currents are short-circuited. The second approach is to note that, since Maxwell's equations...... and the boundary conditions are satisfied, none of the impressed currents is short-circuited and no currents are induced on the perfect conductors. Since all currents and field quantities are considered at the same time, this approach is referred to as the total-field approach. The partial-field approach leads...

  4. Discrimination Between Inrush and Short Circuit Currents in Differential Protection of Power Transformer Based on Correlation Method Using the Wavelet Transform

    OpenAIRE

    M. Rasoulpoor; M. Banejad; A. Ahmadyfard

    2011-01-01

    This paper presents a novel technique for transformer differential protection to prevent incorrect operation due to inrush current. The proposed method in this paper is based on time-frequency transform known as the Wavelet transform. The discrete Wavelet transform is used for analysis the differential current signals in time and frequency domains. The investigation on the energy distribution of the signal on the discrete Wavelet transform components shows the difference distribution between ...

  5. Utilization of symmetrical components in a communication-assisted protection scheme for radial MV feeders with variable or reduced short-circuit currents

    DEFF Research Database (Denmark)

    Ciontea, Catalin-Iosif; Bak, Claus Leth; Blaabjerg, Frede

    2017-01-01

    because the fault current is significantly lower in the islanded mode compared to the grid-connected mode and consequently a single set of settings for the OC relays is not sufficient. This paper propose a communication-assisted protection scheme that is able to operate correctly in a radial Medium...... over positive-sequence current, while the relays placed downstream the fault detect a zero magnitude for their corresponding ratios. Protection relays calculate the magnitude of the proposed ratio and then exchange the obtained value with the adjacent upstream relays using communication. Therefore......, each relay would have access to its own ratio and to the ratio provided by the adjacent relay. Finally, the relay with the highest calculated magnitude of the ratio of zero-sequence to positive-sequence current will trip, thus clearing the fault. The new protection scheme is implemented in a test...

  6. LS1 Report: short-circuit tests

    CERN Multimedia

    Katarina Anthony

    2014-01-01

    As the LS1 draws to an end, teams move from installation projects to a phase of intense testing. Among these are the so-called 'short-circuit tests'. Currently under way at Point 7, these tests verify the cables, the interlocks, the energy extraction systems, the power converters that provide current to the superconducting magnets and the cooling system.   Thermal camera images taken during tests at point 4 (IP4). Before putting beam into the LHC, all of the machine's hardware components need to be put to the test. Out of these, the most complicated are the superconducting circuits, which have a myriad of different failure modes with interlock and control systems. While these will be tested at cold - during powering tests to be done in August - work can still be done beforehand. "While the circuits in the magnets themselves cannot be tested at warm, what we can do is verify the power converter and the circuits right up to the place the cables go into the magn...

  7. Achieving 12.8% Efficiency by Simultaneously Improving Open-Circuit Voltage and Short-Circuit Current Density in Tandem Organic Solar Cells.

    Science.gov (United States)

    Qin, Yunpeng; Chen, Yu; Cui, Yong; Zhang, Shaoqing; Yao, Huifeng; Huang, Jiang; Li, Wanning; Zheng, Zhong; Hou, Jianhui

    2017-06-01

    Tandem organic solar cells (TOSCs), which integrate multiple organic photovoltaic layers with complementary absorption in series, have been proved to be a strong contender in organic photovoltaic depending on their advantages in harvesting a greater part of the solar spectrum and more efficient photon utilization than traditional single-junction organic solar cells. However, simultaneously improving open circuit voltage (V oc ) and short current density (J sc ) is a still particularly tricky issue for highly efficient TOSCs. In this work, by employing the low-bandgap nonfullerene acceptor, IEICO, into the rear cell to extend absorption, and meanwhile introducing PBDD4T-2F into the front cell for improving V oc , an impressive efficiency of 12.8% has been achieved in well-designed TOSC. This result is also one of the highest efficiencies reported in state-of-the-art organic solar cells. © 2017 WILEY-VCH Verlag GmbH & Co. KGaA, Weinheim.

  8. The ISC Seismic Event Bibliography

    Science.gov (United States)

    Di Giacomo, Domenico; Storchak, Dmitry

    2015-04-01

    The International Seismological Centre (ISC) is a not-for-profit organization operating in the UK for the last 50 years and producing the ISC Bulletin - the definitive worldwide summary of seismic events, both natural and anthropogenic - starting from the beginning of 20th century. Often researchers need to gather information related to specific seismic events for various reasons. To facilitate such task, in 2012 we set up a new database linking earthquakes and other seismic events in the ISC Bulletin to bibliographic records of scientific articles (mostly peer-reviewed journals) that describe those events. Such association allows users of the ISC Event Bibliography (www.isc.ac.uk/event_bibliography/index.php) to run searches for publications via a map-based web interface and, optionally, selecting scientific publications related to either specific events or events in the area of interest. Some of the greatest earthquakes were described in several hundreds of articles published over a period of few years. The journals included in our database are not limited to seismology but bring together a variety of fields in geosciences (e.g., engineering seismology, geodesy and remote sensing, tectonophysics, monitoring research, tsunami, geology, geochemistry, hydrogeology, atmospheric sciences, etc.) making this service useful in multidisciplinary studies. Usually papers dealing with large data set are not included (e.g., papers describing a seismic catalogue). Currently the ISC Event Bibliography includes over 17,000 individual publications from about 500 titles related to over 14,000 events that occurred in last 100+ years. The bibliographic records in the Event Bibliography start in the 1950s, and it is updated as new publications become available.

  9. Apical P2XR contribute to [Ca2+]i signaling and Isc in mouse renal MCD.

    Science.gov (United States)

    Li, Liuzhe; Lynch, I Jeanette; Zheng, Wencui; Cash, Melanie N; Teng, Xueling; Wingo, Charles S; Verlander, Jill W; Xia, Shen-Ling

    2007-08-03

    We examined P2X receptor expression and distribution in the mouse collecting duct (CD) and their functional role in Ca(2+) signaling. Both P2X(1) and P2X(4) were detected by RT-PCR and Western blot. Immunohistochemistry demonstrated apical P2X(1) and P2X(4) immunoreactivity in principal cells in the outer medullary CD (OMCD) and inner medullary CD (IMCD). Luminal ATP induced an increase in Ca(2+) signaling in native medullary CD (MCD) as measured by fluorescence imaging. ATP also induced an increase in Ca(2+) signaling in MCD cells grown in primary culture but not in the presence of P2XR antagonist PPNDS. Short circuit current (I(sc)) measurement with mouse IMCD cells showed that P2XR agonist BzATP induced a larger I(sc) than did P2YR agonist UTP in the apical membrane. Our data reveal for the first time that P2X(1) and P2X(4) are cell-specific with prominent immunoreactivity in the apical area of MCD cells. The finding that P2XR blockade inhibits ATP-induced Ca(2+) signaling suggests that activation of P2XR is a key step in Ca(2+)-dependent purinergic signaling. The result that activation of P2XR produces large I(sc) indicates the necessity of P2XR in renal CD ion transport.

  10. Automatic location of short circuit faults

    Energy Technology Data Exchange (ETDEWEB)

    Lehtonen, M. [VTT Energy, Espoo (Finland); Hakola, T.; Antila, E. [ABB Power Oy, Helsinki (Finland); Seppaenen, M. [North-Carelian Power Company (Finland)

    1996-12-31

    In this presentation, the automatic location of short circuit faults on medium voltage distribution lines, based on the integration of computer systems of medium voltage distribution network automation is discussed. First the distribution data management systems and their interface with the substation telecontrol, or SCADA systems, is studied. Then the integration of substation telecontrol system and computerised relay protection is discussed. Finally, the implementation of the fault location system is presented and the practical experience with the system is discussed

  11. Automatic location of short circuit faults

    Energy Technology Data Exchange (ETDEWEB)

    Lehtonen, M [VTT Energy, Espoo (Finland); Hakola, T; Antila, E [ABB Power Oy (Finland); Seppaenen, M [North-Carelian Power Company (Finland)

    1998-08-01

    In this chapter, the automatic location of short circuit faults on medium voltage distribution lines, based on the integration of computer systems of medium voltage distribution network automation is discussed. First the distribution data management systems and their interface with the substation telecontrol, or SCADA systems, is studied. Then the integration of substation telecontrol system and computerized relay protection is discussed. Finally, the implementation of the fault location system is presented and the practical experience with the system is discussed

  12. Automatic location of short circuit faults

    Energy Technology Data Exchange (ETDEWEB)

    Lehtonen, M [VTT Energy, Espoo (Finland); Hakola, T; Antila, E [ABB Power Oy, Helsinki (Finland); Seppaenen, M [North-Carelian Power Company (Finland)

    1997-12-31

    In this presentation, the automatic location of short circuit faults on medium voltage distribution lines, based on the integration of computer systems of medium voltage distribution network automation is discussed. First the distribution data management systems and their interface with the substation telecontrol, or SCADA systems, is studied. Then the integration of substation telecontrol system and computerised relay protection is discussed. Finally, the implementation of the fault location system is presented and the practical experience with the system is discussed

  13. Synchronous Condenser Allocation for Improving System Short Circuit Ratio

    DEFF Research Database (Denmark)

    Jia, Jundi; Yang, Guangya; Nielsen, Arne Hejde

    2018-01-01

    With converter-based renewable energy sources increasingly integrated into power systems and conventional power plants gradually phased out, future power systems will experience reduced short circuit strength. The deployment of synchronous condensers can serve as a potential solution. This paper...... presents an optimal synchronous condenser allocation method for improving system short circuit ratio at converter point of common coupling using a modified short circuit analysis approach. The total cost of installing new synchronous condensers is minimized while the system short circuit ratios...

  14. 30 CFR 56.12065 - Short circuit and lightning protection.

    Science.gov (United States)

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Short circuit and lightning protection. 56... Electricity § 56.12065 Short circuit and lightning protection. Powerlines, including trolley wires, and telephone circuits shall be protected against short circuits and lightning. ...

  15. 30 CFR 57.12065 - Short circuit and lightning protection.

    Science.gov (United States)

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Short circuit and lightning protection. 57... MINES Electricity Surface Only § 57.12065 Short circuit and lightning protection. Powerlines, including trolley wires, and telephone circuits shall be protected against short circuits and lightning. ...

  16. Short-circuited coil in a solenoid circuit of a pulse magnetic field

    International Nuclear Information System (INIS)

    Kivshik, A.F.; Dubrovin, V.Yu.

    1976-01-01

    A short-circuited coil at the end of a long pulse solenoid attenuates the dissipation field by 3-5 times. A plug-configuration field is set up in the middle portion of the pulse solenoid incorporating the short-circuited coils. Shunting of the coils with the induction current by resistor Rsub(shunt) provides for the adjustment of the plug ratio γ

  17. Analysis of High Power IGBT Short Circuit Failures

    Energy Technology Data Exchange (ETDEWEB)

    Pappas, G.

    2005-02-11

    The Next Linear Collider (NLC) accelerator proposal at SLAC requires a highly efficient and reliable, low cost, pulsed-power modulator to drive the klystrons. A solid-state induction modulator has been developed at SLAC to power the klystrons; this modulator uses commercial high voltage and high current Insulated Gate Bipolar Transistor (IGBT) modules. Testing of these IGBT modules under pulsed conditions was very successful; however, the IGBTs failed when tests were performed into a low inductance short circuit. The internal electrical connections of a commercial IGBT module have been analyzed to extract self and mutual partial inductances for the main current paths as well as for the gate structure. The IGBT module, together with the partial inductances, has been modeled using PSpice. Predictions for electrical paths that carry the highest current correlate with the sites of failed die under short circuit tests. A similar analysis has been carried out for a SLAC proposal for an IGBT module layout. This paper discusses the mathematical model of the IGBT module geometry and presents simulation results.

  18. Transfer of sulfur from IscS to IscU during Fe/S cluster assembly.

    Science.gov (United States)

    Urbina, H D; Silberg, J J; Hoff, K G; Vickery, L E

    2001-11-30

    The cysteine desulfurase enzymes NifS and IscS provide sulfur for the biosynthesis of Fe/S proteins. NifU and IscU have been proposed to serve as template or scaffold proteins in the initial Fe/S cluster assembly events, but the mechanism of sulfur transfer from NifS or IscS to NifU or IscU has not been elucidated. We have employed [(35)S]cysteine radiotracer studies to monitor sulfur transfer between IscS and IscU from Escherichia coli and have used direct binding measurements to investigate interactions between the proteins. IscS catalyzed transfer of (35)S from [(35)S]cysteine to IscU in the absence of additional thiol reagents, suggesting that transfer can occur directly and without involvement of an intermediate carrier. Surface plasmon resonance studies and isothermal titration calorimetry measurements further revealed that IscU binds to IscS with high affinity (K(d) approximately 2 microm) in support of a direct transfer mechanism. Transfer was inhibited by treatment of IscU with iodoacetamide, and (35)S was released by reducing reagents, suggesting that transfer of persulfide sulfur occurs to cysteinyl groups of IscU. A deletion mutant of IscS lacking C-terminal residues 376-413 (IscSDelta376-413) displayed cysteine desulfurase activity similar to the full-length protein but exhibited lower binding affinity for IscU, decreased ability to transfer (35)S to IscU, and reduced activity in assays of Fe/S cluster assembly on IscU. The findings with IscSDelta376-413 provide additional support for a mechanism of sulfur transfer involving a direct interaction between IscS and IscU and suggest that the C-terminal region of IscS may be important for binding IscU.

  19. Mineral processing by short circuits in protoplanetary disks

    DEFF Research Database (Denmark)

    Mcnally, C.P.; Hubbard, A.; Mac Low, M.-M.

    2013-01-01

    Meteoritic chondrules were formed in the early solar system by brief heating of silicate dust to melting temperatures. Some highly refractory grains (Type B calcium-aluminum-rich inclusions, CAIs) also show signs of transient heating. A similar process may occur in other protoplanetary disks......, as evidenced by observations of spectra characteristic of crystalline silicates. One possible environment for this process is the turbulent magnetohydrodynamic flow thought to drive accretion in these disks. Such flows generally form thin current sheets, which are sites of magnetic reconnection, and dissipate...... the magnetic fields amplified by a disk dynamo. We suggest that it is possible to heat precursor grains for chondrules and other high-temperature minerals in current sheets that have been concentrated by our recently described short-circuit instability. We extend our work on this process by including...

  20. Performance of Llampuedken with short circuit and plasma loads

    International Nuclear Information System (INIS)

    Chuaqui, Hernan; Mitchell, Ian H.; Aliaga-Rossel, Raul; Favre, Mario; Wyndham, Edmund S.

    2002-01-01

    Llampuedken is a pulsed power generator designed to deliver a 1 MA, 250 ns risetime current pulse into a dense plasma load. The main novel feature of this generator is the two auxiliary transmission lines which transmit the energy not absorbed by the load, reflect it at the open end of the line and deliver it to the load when the energy from the main lines is decreasing. With the auxiliary lines an increase of 30% on the current as well as a decrease of the voltage at the load is obtained. To date Llampuedken has been operated up to the 400 kA level, into both short circuit and plasma loads. Details of actual performance of the pulse power generator are presented and compared with simulations

  1. Short circuit analysis of distribution system with integration of DG

    DEFF Research Database (Denmark)

    Su, Chi; Liu, Zhou; Chen, Zhe

    2014-01-01

    and as a result bring challenges to the network protection system. This problem has been frequently discussed in the literature, but mostly considering only the balanced fault situation. This paper presents an investigation on the influence of full converter based wind turbine (WT) integration on fault currents......Integration of distributed generation (DG) such as wind turbines into distribution system is increasing all around the world, because of the flexible and environmentally friendly characteristics. However, DG integration may change the pattern of the fault currents in the distribution system...... during both balanced and unbalanced faults. Major factors such as external grid short circuit power capacity, WT integration location, connection type of WT integration transformer are taken into account. In turn, the challenges brought to the protection system in the distribution network are presented...

  2. Short Circuit Tests First Step of LHC Hardware Commissioning Completion

    CERN Document Server

    Barbero-Soto, E; Bordry, Frederick; Casas Lino, M P; Coelingh, G J; Cumer, G; Dahlerup-Petersen, K; Guillaume, J C; Inigo-Golfin, J; Montabonnet, V; Nisbet, D; Pojer, M; Principe, R; Rodríguez-Mateos, F; Saban, R; Schmidt, R; Thiesen, H; Vergara-Fernández, A; Zerlauth, M; Castaneda Serra, A; Romera Ramirez, I

    2008-01-01

    For the two counter rotating beams in the Large Hadron Collider (LHC) about 8000 magnets (main dipole and quadrupole magnets, corrector magnets, separation dipoles, matching section quadrupoles etc.) are powered in about 1500 superconducting electrical circuits. The magnets are powered by power converters that have been designed for the LHC with a current between 60 and 13000A. Between October 2005 and September 2007 the so-called Short Circuit Tests were carried-out in 15 underground zones where the power converters of the superconducting circuits are placed. The tests aimed to qualify the normal conducting equipments of the circuits such as power converters and normal conducting high current cables. The correct operation of interlock and energy extraction systems was validated. The infrastructure systems including AC distribution, water and air cooling and the control systems was also commissioned. In this paper the results of the two year test campaign are summarized with particular attention to problems e...

  3. Official (ISC)2 guide to the CISSP CBK

    CERN Document Server

    Hernandez, Steven

    2012-01-01

    Recognized as one of the best tools available for the information security professional and especially for candidates studying for the (ISC)2 CISSP examination, the Official (ISC)2(R) Guide to the CISSP(R) CBK(R), Third Edition has been updated and revised to reflect the latest developments in this ever-changing field. Endorsed by the (ISC)2, this book provides unrivaled preparation for the certification exam that is both up to date and authoritative. Compiled and reviewed by CISSPs and (ISC)2 members, the text provides an exhaustive review of the 10 current domains of the CBK.

  4. Short-Circuit Modeling of a Wind Power Plant: Preprint

    Energy Technology Data Exchange (ETDEWEB)

    Muljadi, E.; Gevorgian, V.

    2011-03-01

    This paper investigates the short-circuit behavior of a WPP for different types of wind turbines. The short-circuit behavior will be presented. Both the simplified models and detailed models are used in the simulations and both symmetrical faults and unsymmetrical faults are discussed.

  5. TCAD analysis of short-circuit oscillations in IGBTs

    DEFF Research Database (Denmark)

    Reigosa, Paula Diaz; Iannuzzo, Francesco; Rahimo, Munaf

    2017-01-01

    Insulated-Gate Bipolar Transistors (IGBTs) exhibit a gate-voltage oscillation phenomenon during short-circuit, which can result in a gate-oxide breakdown. The oscillations have been investigated through device simulations and experimental investigations of a 3.3-kV IGBT. It has been found...... during short circuit....

  6. Influence of an inner short-circuit on the behaviour of the superconducting magnet

    International Nuclear Information System (INIS)

    Zizek, F.

    1984-01-01

    On exciting one of the superconducting quadrupole magnets, voltage pulses were observed on the winding outlets. Over a certain current level the pulses disappeared and a quench of the magnet was registered. A subsequent analysis proved that phenomenon was caused by short-circuiting of the turns inside one of the quadrupole coils. The voltage pulses were caused by repeated quenches of the short-circuited part of the winding. The above effect did not appear until a certain rate of rise of the current was attained

  7. Influence of an inner short-circuit on the behaviour of the superconducting magnet

    Energy Technology Data Exchange (ETDEWEB)

    Zizek, F. (Skoda k.p., Plzen (Czechoslovakia))

    1984-01-01

    On exciting one of the superconducting quadrupole magnets, voltage pulses were observed on the winding outlets. Over a certain current level the pulses disappeared and a quench of the magnet was registered. A subsequent analysis proved that phenomenon was caused by short-circuiting of the turns inside one of the quadrupole coils. The voltage pulses were caused by repeated quenches of the short-circuited part of the winding. The above effect did not appear until a certain rate of rise of the current was attained.

  8. MINERAL PROCESSING BY SHORT CIRCUITS IN PROTOPLANETARY DISKS

    Energy Technology Data Exchange (ETDEWEB)

    McNally, Colin P. [Niels Bohr International Academy, Niels Bohr Institute, DK-2100 Copenhagen (Denmark); Hubbard, Alexander; Mac Low, Mordecai-Mark [Department of Astrophysics, American Museum of Natural History, New York, NY 10024-5192 (United States); Ebel, Denton S. [Department of Earth and Planetary Sciences, American Museum of Natural History, New York, NY 10024-5192 (United States); D' Alessio, Paola, E-mail: cmcnally@nbi.dk, E-mail: ahubbard@amnh.org, E-mail: mordecai@amnh.org, E-mail: debel@amnh.org, E-mail: p.dalessio@crya.unam.mx [Centro de Radioastronomia y Astrofisica, Universidad Nacional Autonoma de Mexico, 58089 Morelia, MICH (Mexico)

    2013-04-10

    Meteoritic chondrules were formed in the early solar system by brief heating of silicate dust to melting temperatures. Some highly refractory grains (Type B calcium-aluminum-rich inclusions, CAIs) also show signs of transient heating. A similar process may occur in other protoplanetary disks, as evidenced by observations of spectra characteristic of crystalline silicates. One possible environment for this process is the turbulent magnetohydrodynamic flow thought to drive accretion in these disks. Such flows generally form thin current sheets, which are sites of magnetic reconnection, and dissipate the magnetic fields amplified by a disk dynamo. We suggest that it is possible to heat precursor grains for chondrules and other high-temperature minerals in current sheets that have been concentrated by our recently described short-circuit instability. We extend our work on this process by including the effects of radiative cooling, taking into account the temperature dependence of the opacity; and by examining current sheet geometry in three-dimensional, global models of magnetorotational instability. We find that temperatures above 1600 K can be reached for favorable parameters that match the ideal global models. This mechanism could provide an efficient means of tapping the gravitational potential energy of the protoplanetary disk to heat grains strongly enough to form high-temperature minerals. The volume-filling nature of turbulent magnetic reconnection is compatible with constraints from chondrule-matrix complementarity, chondrule-chondrule complementarity, the occurrence of igneous rims, and compound chondrules. The same short-circuit mechanism may perform other high-temperature mineral processing in protoplanetary disks such as the production of crystalline silicates and CAIs.

  9. On-Demand Cell Internal Short Circuit Device

    Science.gov (United States)

    Darcy, Eric; Keyser, Matthew

    2014-01-01

    A device implantable in Li-ion cells that can generate a hard internal short circuit on-demand by exposing the cell to 60?C has been demonstrated to be valuable for expanding our understanding of cell responses. The device provides a negligible impact to cell performance and enables the instigation of the 4 general categories of cell internal shorts to determine relative severity and cell design susceptibility. Tests with a 18650 cell design indicates that the anode active material short to the aluminum cathode current collector tends to be more catastrophic than the 3 other types of internal shorts. Advanced safety features (such as shutdown separators) to prevent or mitigate the severity of cell internal shorts can be verified with this device. The hard short success rate achieved to date in 18650 cells is about 80%, which is sufficient for using these cells in battery assemblies for field-failure-relevant, cell-cell thermal runaway propagation verification tests

  10. Short Circuits of a 10 MW High Temperature Superconducting Wind Turbine Generator

    DEFF Research Database (Denmark)

    Song, Xiaowei (Andy); Liu, Dong; Polinder, Henk

    2016-01-01

    Direct drive high temperature superconducting (HTS) wind turbine generators have been proposed to tackle challenges for ever increasing wind turbine ratings. Due to smaller reactances in HTS generators, higher fault currents and larger transient torques could occur if sudden short circuits happen...... at generator terminals. In this paper, a finite element model that couples magnetic fields and the generator’s equivalent circuits is developed to simulate short circuit faults. Afterwards, the model is used to study the transient performance of a 10 MW HTS wind turbine generator under four different short...... that the short circuits pose great challenges to the generator, and careful consideration should be given to protect the generator. The results presented in this paper would be beneficial to the design, operation and protection of an HTS wind turbine generator....

  11. Short Circuits of a 10-MW High-Temperature Superconducting Wind Turbine Generator

    DEFF Research Database (Denmark)

    Song, Xiaowei (Andy); Liu, Dong; Polinder, Henk

    2017-01-01

    Direct Drive high-temperature superconducting (HTS) wind turbine generators have been proposed to tackle challenges for ever increasing wind turbine ratings. Due to smaller reactances in HTS generators, higher fault currents and larger transient torques could occur if sudden short circuits take...... place at generator terminals. In this paper, a finite element model that couples magnetic fields and the generator's equivalent circuits is developed to simulate short-circuit faults. Afterward, the model is used to study the transient performance of a 10-MW HTS wind turbine generator under four...... show that the short circuits pose great challenges to the generator, and careful consideration should be given to protect the generator. The findings presented in this paper would be beneficial to the design, operation and protection of an HTS wind turbine generator....

  12. In-situ short-circuit protection system and method for high-energy electrochemical cells

    Science.gov (United States)

    Gauthier, Michel; Domroese, Michael K.; Hoffman, Joseph A.; Lindeman, David D.; Noel, Joseph-Robert-Gaetan; Radewald, Vern E.; Rouillard, Jean; Rouillard, Roger; Shiota, Toshimi; Trice, Jennifer L.

    2003-04-15

    An in-situ thermal management system for an energy storage device. The energy storage device includes a plurality of energy storage cells each being coupled in parallel to common positive and negative connections. Each of the energy storage cells, in accordance with the cell's technology, dimensions, and thermal/electrical properties, is configured to have a ratio of energy content-to-contact surface area such that thermal energy produced by a short-circuit in a particular cell is conducted to a cell adjacent the particular cell so as to prevent the temperature of the particular cell from exceeding a breakdown temperature. In one embodiment, a fuse is coupled in series with each of a number of energy storage cells. The fuses are activated by a current spike capacitively produced by a cell upon occurrence of a short-circuit in the cell, thereby electrically isolating the short-circuited cell from the common positive and negative connections.

  13. In-situ short circuit protection system and method for high-energy electrochemical cells

    Science.gov (United States)

    Gauthier, Michel; Domroese, Michael K.; Hoffman, Joseph A.; Lindeman, David D.; Noel, Joseph-Robert-Gaetan; Radewald, Vern E.; Rouillard, Jean; Rouillard, Roger; Shiota, Toshimi; Trice, Jennifer L.

    2000-01-01

    An in-situ thermal management system for an energy storage device. The energy storage device includes a plurality of energy storage cells each being coupled in parallel to common positive and negative connections. Each of the energy storage cells, in accordance with the cell's technology, dimensions, and thermal/electrical properties, is configured to have a ratio of energy content-to-contact surface area such that thermal energy produced by a short-circuit in a particular cell is conducted to a cell adjacent the particular cell so as to prevent the temperature of the particular cell from exceeding a breakdown temperature. In one embodiment, a fuse is coupled in series with each of a number of energy storage cells. The fuses are activated by a current spike capacitively produced by a cell upon occurrence of a short-circuit in the cell, thereby electrically isolating the short-circuited cell from the common positive and negative connections.

  14. Short-Circuit Characterization of 10 kV 10A 4H-SiC MOSFET

    DEFF Research Database (Denmark)

    Eni, Emanuel-Petre; Beczkowski, Szymon; Munk-Nielsen, Stig

    2016-01-01

    The short-circuit capability of a power device is highly relevant for converter design and fault protection. In this paper a 10kV 10A 4H-SiC MOSFET is characterized and its short circuit withstand capability is studied and analyzed at 6 kV DC-link voltage. The test setup for this study is also...... introduced as its design, especially the inductance in the switching loop, can affect the experimental results. The study aims to present insights specific to the device which are different from that of silicon (Si) based devices. During the short-circuit operation, MOSFET saturation current, ID...

  15. Forces and stresses in cryoturbogenerator rotor in presence of short circuit

    International Nuclear Information System (INIS)

    Kovarskii, M.E.; Rubinraut, A.M.; Tsyrlin, A.L.

    1981-01-01

    A method is presented for determining the electrodynamic forces, mechanical stresses, and strains in the shells of a cryogenic-turbogenerator cryostat in the presence of an abrupt short circuit. The physical pattern of occurrence of forces in a cryostat shell is considered for capacitive, inductive, and active armature-current cases. It is shown that in addition to the radial component, there is a tangential component of the electrodynamic forces, with the interaction of the two components governing the strength in the presence of short circuits. Results are reported for mechanical-strength calculations, based on the proposed method, for a 200 kw cryogenic turbogenerator

  16. Short Circuits of a 10 MW High Temperature Superconducting Wind Turbine Generator

    NARCIS (Netherlands)

    Song, X.; Polinder, H.; Liu, D.; Mijatovic, Nenad; Holbøll, Joachim; Jensen, Bogi Bech

    Direct drive high temperature superconducting (HTS) wind turbine generators have been proposed to tackle challenges for ever increasing wind turbine ratings. Due to smaller reactances in HTS generators, higher fault currents and larger transient torques could occur if sudden short circuits happen at

  17. Electro-thermal modeling of high power IGBT module short-circuits with experimental validation

    DEFF Research Database (Denmark)

    Wu, Rui; Iannuzzo, Francesco; Wang, Huai

    2015-01-01

    A novel Insulated Gate Bipolar Transistor (IGBT) electro-thermal modeling approach involving PSpice and ANSYS/Icepak with both high accuracy and simulation speed has been presented to study short-circuit of a 1.7 kV/1 kA commercial IGBT module. The approach successfully predicts the current...

  18. Short circuit protection for a power distribution system

    Science.gov (United States)

    Owen, J. R., III

    1969-01-01

    Sensing circuit detects when the output from a matrix is present and when it should be present. The circuit provides short circuit protection for a power distribution system where the selection of the driven load is accomplished by digital logic.

  19. Integrated Power Flow and Short Circuit Calculation Method for Distribution Network with Inverter Based Distributed Generation

    Directory of Open Access Journals (Sweden)

    Shan Yang

    2016-01-01

    Full Text Available Power flow calculation and short circuit calculation are the basis of theoretical research for distribution network with inverter based distributed generation. The similarity of equivalent model for inverter based distributed generation during normal and fault conditions of distribution network and the differences between power flow and short circuit calculation are analyzed in this paper. Then an integrated power flow and short circuit calculation method for distribution network with inverter based distributed generation is proposed. The proposed method let the inverter based distributed generation be equivalent to Iθ bus, which makes it suitable to calculate the power flow of distribution network with a current limited inverter based distributed generation. And the low voltage ride through capability of inverter based distributed generation can be considered as well in this paper. Finally, some tests of power flow and short circuit current calculation are performed on a 33-bus distribution network. The calculated results from the proposed method in this paper are contrasted with those by the traditional method and the simulation method, whose results have verified the effectiveness of the integrated method suggested in this paper.

  20. The short-circuit test results of 6.9 kV/2.3 kV 400 kVA-class YBCO model transformer

    International Nuclear Information System (INIS)

    Tomioka, A.; Otonari, T.; Ogata, T.; Iwakuma, M.; Okamoto, H.; Hayashi, H.; Iijima, Y.; Saito, T.; Gosho, Y.; Tanabe, K.; Izumi, T.; Shiohara, Y.

    2011-01-01

    The 6.9 kV/2.3 kV 400 kVA-class single-phase YBCO model transformer with the YBCO tape with copper tape was manufactured for short-circuit current test. Short-circuit test was performed and the short-circuit current of primary winding was 346 A which was about six times larger than the rated current. The I-V characteristics of the winding did not change before and after the test. The transformer withstood short-circuit current. We are planning to turn the result into a consideration of a 66 kV/6.9 kV-20 MVA-class three-phase superconducting transformer. We are developing an elemental technology for 66 kV/6.9 kV 20 MVA-class power transformer with YBCO conductors. The protection of short-circuit technology is one of the elemental technologies for HTS transformer. Since short-circuit current is much higher than critical current of YBCO tape, there is a possibility that superconducting characteristics may be damaged during short-circuit period. We made a conductor to compose the YBCO tape with copper tape. We manufactured 6.9 kV/2.3 kV 400 kVA-class YBCO model transformer using this conductor and performed short-circuit current test. The short-circuit current of primary winding was 346 A which was about six times larger than the rated current. The I-V characteristics of the winding did not change before and after the test. We may consider this conductor withstands short-circuit current.

  1. Short-circuit protection of LLC resonant converter using voltages across resonant tank elements

    Directory of Open Access Journals (Sweden)

    Denys Igorovych Zaikin

    2015-06-01

    Full Text Available This paper describes two methods for the short-circuit protection of the LLC resonant converter. One of them uses the voltage across the capacitor and the other uses the voltage across the inductor of the resonant tank. These voltages can be processed (integrated or differentiated to recover the resonant tank current. The two circuits illustrated in the described methods make it possible to develop a robust LLC converter design and to avoid using lossy current measurement elements, such as a shunt resistor or current transformer. The methods also allow measuring resonant tank current without breaking high-current paths and connecting the measuring circuit in parallel with the inductor or capacitor of the resonant tank. Practical implementations of these indirect current measurements have been experimentally tested for the short-circuit protection of the 1600 W LLC converter.

  2. Extending the ISC-GEM Global Earthquake Instrumental Catalogue

    Science.gov (United States)

    Di Giacomo, Domenico; Engdhal, Bob; Storchak, Dmitry; Villaseñor, Antonio; Harris, James

    2015-04-01

    After a 27-month project funded by the GEM Foundation (www.globalquakemodel.org), in January 2013 we released the ISC-GEM Global Instrumental Earthquake Catalogue (1900 2009) (www.isc.ac.uk/iscgem/index.php) as a special product to use for seismic hazard studies. The new catalogue was necessary as improved seismic hazard studies necessitate that earthquake catalogues are homogeneous (to the largest extent possible) over time in their fundamental parameters, such as location and magnitude. Due to time and resource limitation, the ISC-GEM catalogue (1900-2009) included earthquakes selected according to the following time-variable cut-off magnitudes: Ms=7.5 for earthquakes occurring before 1918; Ms=6.25 between 1918 and 1963; and Ms=5.5 from 1964 onwards. Because of the importance of having a reliable seismic input for seismic hazard studies, funding from GEM and two commercial companies in the US and UK allowed us to start working on the extension of the ISC-GEM catalogue both for earthquakes that occurred beyond 2009 and for earthquakes listed in the International Seismological Summary (ISS) which fell below the cut-off magnitude of 6.25. This extension is part of a four-year program that aims at including in the ISC-GEM catalogue large global earthquakes that occurred before the beginning of the ISC Bulletin in 1964. In this contribution we present the updated ISC GEM catalogue, which will include over 1000 more earthquakes that occurred in 2010 2011 and several hundreds more between 1950 and 1959. The catalogue extension between 1935 and 1949 is currently underway. The extension of the ISC-GEM catalogue will also be helpful for regional cross border seismic hazard studies as the ISC-GEM catalogue should be used as basis for cross-checking the consistency in location and magnitude of those earthquakes listed both in the ISC GEM global catalogue and regional catalogues.

  3. Apparatus including a plurality of spaced transformers for locating short circuits in cables

    Science.gov (United States)

    Cason, R. L.; Mcstay, J. J. (Inventor)

    1978-01-01

    A cable fault locator is described for sensing faults such as short circuits in power cables. The apparatus includes a plurality of current transformers strategically located along a cable. Trigger circuits are connected to each of the current transformers for placing a resistor in series with a resistive element responsive to an abnormally high current flowing through that portion of the cable. By measuring the voltage drop across the resistive element, the location of the fault can be determined.

  4. Simulation and experimental study on lithium ion battery short circuit

    International Nuclear Information System (INIS)

    Zhao, Rui; Liu, Jie; Gu, Junjie

    2016-01-01

    Highlights: • Both external and internal short circuit tests were performed on Li-ion batteries. • An electrochemical–thermal model with an additional nail site heat source is presented. • The model can accurately simulate the temperature variations of non-venting batteries. • The model is reliable in predicting the occurrence and start time of thermal runaway. • A hydrogel cooling system proves its strength in preventing battery thermal runaway. - Abstract: Safety is the first priority in lithium ion (Li-ion) battery applications. A large portion of electrical and thermal hazards caused by Li-ion battery is associated with short circuit. In this paper, both external and internal short circuit tests are conducted. Li-ion batteries and battery packs of different capacities are used. The results indicate that external short circuit is worse for smaller size batteries due to their higher internal resistances, and this type of short can be well managed by assembling fuses. In internal short circuit tests, higher chance of failure is found on larger capacity batteries. A modified electrochemical–thermal model is proposed, which incorporates an additional heat source from nail site and proves to be successful in depicting temperature changes in batteries. Specifically, the model is able to estimate the occurrence and approximate start time of thermal runaway. Furthermore, the effectiveness of a hydrogel based thermal management system in suppressing thermal abuse and preventing thermal runaway propagation is verified through the external and internal short tests on batteries and battery packs.

  5. Asymmetrical short circuits in medium-voltage networks with grounded neutral through resistance

    Energy Technology Data Exchange (ETDEWEB)

    Tanasescu, M.; Maries, H.

    1981-01-01

    This article introduces the concepts of ''damage to ground'' and ''current to ground indicator'', which characterize the efficiency of the operating mode of the neutral. The values of these two indicators are assigned by directive (eletric power plan design instruction PE109/1980) and must be provided when selecting the parameters of compensating devices installed in the neutral. Possible aymmetrical short circuits in medium-voltage networks with neutral ground are examined. Formulas are derived for determining the short-circuiting currents and undamaged phase voltages in order to determine the damage to ground indicator and ground current indicator; an example of a calculation is given.

  6. A Short-Circuit Method for Networks.

    Science.gov (United States)

    Ong, P. P.

    1983-01-01

    Describes a method of network analysis that allows avoidance of Kirchoff's Laws (providing the network is symmetrical) by reduction to simple series/parallel resistances. The method can be extended to symmetrical alternating current, capacitance or inductance if corresponding theorems are used. Symmetric cubic network serves as an example. (JM)

  7. Load Flow and Short Circuit Analysis of the Class III Power System of HANARO

    Energy Technology Data Exchange (ETDEWEB)

    Kim, H. K.; Jung, H. S

    2005-12-15

    The planning, design, and operation of electric power system require engineering studies to assist in the evaluation of the system performance, reliability, safety and economics. The Class III power of HANARO supplies power for not only HANARO but also RIPF and IMEF. The starting current of most ac motors is five to ten times normal full load current. The loads of the Class III power are connected in consecutive orders at an interval for 10 seconds to avoid excessive voltage drop. This technical report deals with the load flow study and motor starting study for the Class III power of HANARO using ETAP(Electrical Transient Analyzer Program) to verify the capacity of the diesel generator. Short-circuit studies are done to determine the magnitude of the prospective currents flowing throughout the power system at various time intervals after a fault occurs. Short-circuit studies can be performed at the planning stage in order to help finalize the system layout, determine voltage levels, and size cables, transformers, and conductors. From this study, we verify the short circuit current capacity of air circuit breaker(ACB) and automatic transfer switch(ATS) of the Class III power.

  8. Prevention of short circuits in solution-processed OLED devices

    NARCIS (Netherlands)

    Jolt Oostra, A.; Blom, P.W.M.; Michels, J.J.

    2014-01-01

    Pinholes in the emitting layer of an organic light emitting diode (OLED), e.g. induced by particle contamination or processing flaws, lead to direct contact between the hole-injection layer (HIL) and the cathode. The resulting short circuits give rise to catastrophic device failure. We demonstrate

  9. Packaging Solutions for Mitigating IGBT Short-Circuit Instabilities

    DEFF Research Database (Denmark)

    Reigosa, Paula Diaz; Iannuzzo, Francesco; Blaabjerg, Frede

    2017-01-01

    In this paper, the gate voltage oscillations occurring under short-circuit conditions in Insulated-Gate Bipolar Transistors are investigated, together with their dependency with respect to stray inductance variations. By using AnSYS Q3D Extractor, electromagnetic simulations are conducted to extr...

  10. Full Digital Short Circuit Protection for Advanced IGBTs

    OpenAIRE

    谷村, 拓哉; 湯浅, 一史; 大村, 一郎

    2011-01-01

    A full digital short circuit protection method for advanced IGBTs has been proposed and experimentally demonstrated for the first time. The method employs combination of digital circuit, the gate charge sense instead of the conventional sense IGBT and analog circuit configuration. Digital protection scheme has significant advantages in thevprotection speed and flexibility.

  11. A Computer Program for Short Circuit Analysis of Electric Power ...

    African Journals Online (AJOL)

    The Short Circuit Analysis Program (SCAP) is to be used to assess the composite effects of unbalanced and balanced faults on the overall reliability of electric power system. The program uses the symmetrical components method to compute all phase and sequence quantities for any bus or branch of a given power network ...

  12. Control of internal and external short circuits in lithium batteries using a composite thermal switch

    Science.gov (United States)

    Mcdonald, Robert C.; Pickett, Jerome; Goebel, Franz

    1991-01-01

    A composite material has been developed, consisting of a blend of metal and fluorocarbon particles, which behaves as an electronic conductor at room temperature and which abruptly becomes an insulator at a predetermined temperature. This switching behavior results from the difference in thermal expansion coefficients between the conductive and non-conductive portions of the composite. This material was applied as a thin film between the carbon cathode in Li/SOCl2 cells, and the metallic cathode current collector. Using test articles incorporating this feature it was shown that lithium cells externally heated or internally heated during a short circuit lost rate capability and the ability to overheat well below the melting point of lithium (180 C). Thus, during an internal or external cell short circuit, the potential for thermal runaway involving reactions of molten lithium is avoided.

  13. Unstable behaviour of normally-off GaN E-HEMT under short-circuit

    Science.gov (United States)

    Martínez, P. J.; Maset, E.; Sanchis-Kilders, E.; Esteve, V.; Jordán, J.; Bta Ejea, J.; Ferreres, A.

    2018-04-01

    The short-circuit capability of power switching devices plays an important role in fault detection and the protection of power circuits. In this work, an experimental study on the short-circuit (SC) capability of commercial 600 V Gallium Nitride enhancement-mode high-electron-mobility transistors (E-HEMT) is presented. A different failure mechanism has been identified for commercial p-doped GaN gate (p-GaN) HEMT and metal-insulator-semiconductor (MIS) HEMT. In addition to the well known thermal breakdown, a premature breakdown is shown on both GaN HEMTs, triggered by hot electron trapping at the surface, which demonstrates that current commercial GaN HEMTs has requirements for improving their SC ruggedness.

  14. Experimental study on short-circuit characteristics of the new protection circuit of insulated gate bipolar transistor

    International Nuclear Information System (INIS)

    Ji, In-Hwan; Choi, Young-Hwan; Ha, Min-Woo; Han, Min-Koo; Choi, Yearn-Ik

    2006-01-01

    A new protection circuit employing the collector to emitter voltage (V CE ) sensing scheme for short-circuit withstanding capability of the insulated gate bipolar transistor (IGBT) is proposed and verified by experimental results. Because the current path between the gate and collector can be successfully eliminated in the proposed protection circuit, the power consumption can be reduced and the gate input impedance can be increased. Previous study is limited to dc characteristics. However, experimental results show that the proposed protection circuit successfully reduces the over-current of main IGBT by 80.4% under the short-circuit condition

  15. Fine-Tuning the Energy Levels of a Nonfullerene Small-Molecule Acceptor to Achieve a High Short-Circuit Current and a Power Conversion Efficiency over 12% in Organic Solar Cells.

    Science.gov (United States)

    Kan, Bin; Zhang, Jiangbin; Liu, Feng; Wan, Xiangjian; Li, Chenxi; Ke, Xin; Wang, Yunchuang; Feng, Huanran; Zhang, Yamin; Long, Guankui; Friend, Richard H; Bakulin, Artem A; Chen, Yongsheng

    2018-01-01

    Organic solar cell optimization requires careful balancing of current-voltage output of the materials system. Here, such optimization using ultrafast spectroscopy as a tool to optimize the material bandgap without altering ultrafast photophysics is reported. A new acceptor-donor-acceptor (A-D-A)-type small-molecule acceptor NCBDT is designed by modification of the D and A units of NFBDT. Compared to NFBDT, NCBDT exhibits upshifted highest occupied molecular orbital (HOMO) energy level mainly due to the additional octyl on the D unit and downshifted lowest unoccupied molecular orbital (LUMO) energy level due to the fluorination of A units. NCBDT has a low optical bandgap of 1.45 eV which extends the absorption range toward near-IR region, down to ≈860 nm. However, the 60 meV lowered LUMO level of NCBDT hardly changes the V oc level, and the elevation of the NCBDT HOMO does not have a substantial influence on the photophysics of the materials. Thus, for both NCBDT- and NFBDT-based systems, an unusually slow (≈400 ps) but ultimately efficient charge generation mediated by interfacial charge-pair states is observed, followed by effective charge extraction. As a result, the PBDB-T:NCBDT devices demonstrate an impressive power conversion efficiency over 12%-among the best for solution-processed organic solar cells. © 2017 WILEY-VCH Verlag GmbH & Co. KGaA, Weinheim.

  16. Investigation on a short circuit of large-area OLED lighting panels

    International Nuclear Information System (INIS)

    Park, J W; Kim, T W; Park, J B

    2013-01-01

    A short circuit often arises from large-area organic light-emitting device (OLED) lighting panels due to particles (i.e. dust, organic or metal debris) or the spike-like surface of the indium–tin–oxide (ITO) anode. On the emergence of a short circuit, an instant current crowding occurs, thereby reducing substantially the resistance of the panels and causing a failure of a dimming control. In this paper, we investigate the effect of the surface morphology of ITO on the resistance and dimmability of the panels. We have demonstrated that the peak-to-valley roughness of ITO should be much less than 20 nm or the resistance of the panels should be much higher than 1 MΩ in order to avoid an unwanted short-circuit phenomenon and thus achieve the high-yield fabrication of OLED lighting panels. It is also addressed that much care is taken to ensure a dimming control of OLED lighting panels with a larger active area because the resistance of those panels varies depending more sensitively on the surface roughness of ITO. (paper)

  17. Utilisation of symmetrical components in a communication-based protection for loop MV feeders with variable short-circuit power

    DEFF Research Database (Denmark)

    Ciontea, Catalin-Iosif; Bak, Claus Leth; Blaabjerg, Frede

    2018-01-01

    -circuit power is presented. It relies on utilisation of symmetrical components of the short-circuit currents and on communication between the protection relays. The proposed method addresses the Single Phase to Ground (SPG) faults occurring in directly grounded distribution networks, with focus on closed......Variability of the available short-circuit power also implies variation of the fault level, which can potentially cause several protection problems in the electric networks. In this paper, a novel protection method that is insensitive to the fault level changes caused by variable short......-loop Medium Voltage (MV) feeders. Case studies are presented, which demonstrate that the proposed protection scheme is capable of effectively detecting the SPG faults in closed-loop feeders with variable short-circuit power....

  18. Representative-Sandwich Model for Mechanical-Crush and Short-Circuit Simulation of Lithium-ion Batteries

    Energy Technology Data Exchange (ETDEWEB)

    Zhang, Chao; Santhanagopalan, Shriram; Sprague, Michael A.; Pesaran, Ahmad A.

    2015-07-28

    Lithium-ion batteries are currently the state-of-the-art power sources for a variety of applications, from consumer electronic devices to electric-drive vehicles (EDVs). Being an energized component, failure of the battery is an essential concern, which can result in rupture, smoke, fire, or venting. The failure of Lithium-ion batteries can be due to a number of external abusive conditions (impact/crush, overcharge, thermal ramp, etc.) or internal conditions (internal short circuits, excessive heating due to resistance build-up, etc.), of which the mechanical-abuse-induced short circuit is a very practical problem. In order to better understand the behavior of Lithium-ion batteries under mechanical abuse, a coupled modeling methodology encompassing the mechanical, thermal and electrical response has been developed for predicting short circuit under external crush.

  19. Transient analysis of the output short-circuit fault of high power and high voltage DC power supply

    International Nuclear Information System (INIS)

    Yang Zhigang; Zhang Jian; Huang Yiyun; Hao Xu; Sun Haozhang; Guo Fei

    2014-01-01

    The transient conditions of output short-circuit fault of high voltage DC power supply was introduced, and the energy of power supply injecting into klystron during the protection process of three-electrode gas switch were analyzed and calculated in detail when klystron load happening electrode arc faults. The results of calculation and simulation are consistent with the results of the experiment. When the output short-circuit fault of high voltage power supply occurs, switch can be shut off in the microsecond, and the short circuit current can be controlled in 200 A. It has verified the rapidity and reliability of the three-electrode gas switch protection, and it has engineering application value. (authors)

  20. [Electric short-circuit incident observed with "Upsher" laryngoscopes].

    Science.gov (United States)

    Tritsch, L; Vailly, B

    2006-01-01

    We observed an electrical short-circuit between a fasten screw of the printed circuit and the handle of an Upsher universal laryngoscope (serial number UQ1). The isolating Silicone layer was broken above the screw. This isolation defect was found all over our Upsher laryngoscopes of the UQ1 series. No doubt that if accumulators were used instead of batteries, emitted heat would be in largest amount and perhaps dangerous.

  1. Electromechanical stress in transformers caused by three-phase short-circuits; Estresse eletromecanico em transformadores causado por curtos-circuitos trifasicos

    Energy Technology Data Exchange (ETDEWEB)

    Rosentino, A.J.J. Pereira; Delaiba, A.C.; Saraiva, E.; Oliveira, J.C. de; Lynce, M. [Universidade Federal de Uberlandia (UFU), MG (Brazil). Fac. de Engenharia Eletrica], Emails: arnaldoufu@gmail.com, delaiba@ufu.br, elise.saraiva@yahoo.com.br, jcoliveira@ufu.br, lynce@ufu.br; Bronzeado, H. de S. [Companhia Hidro Eletrica do Sao Francisco (CHESF), Recife, PE (Brazil)], Emails: herivelto.bronzeado@gmail.com, hebron@chesf.gov.br

    2009-07-01

    One of the reasons for internal failures of transformers is the weakness of the isolation of its conductors/coils due to vibrations caused by electromechanics forces produced by the high short-circuit currents. In this context, this paper presents a methodology to estimate the electromechanical stress in transformers caused by three-phase short circuits. Details of the characteristics of radial and axial forces that can occur in concentric windings of transformers, focusing mainly on the axial are presented. It is presented the preliminary description of techniques for diagnosis and monitoring of transformers in the face of mechanical stress caused by short circuit. This study considers the transformers core involved.

  2. Transient analysis of unbalanced short circuits of the ERDA-NASA 100 kW wind turbine alternator

    Science.gov (United States)

    Hwang, H. H.; Gilbert, L. J.

    1976-01-01

    Unbalanced short-circuit faults on the alternator of the ERDA-NASA Mod-O100-kW experimental wind turbine are studied. For each case, complete solutions for armature, field, and damper-circuit currents; short-circuit torque; and open-phase voltage are derived directly by a mathematical analysis. Formulated results are tabulated. For the Mod-O wind turbine alternator, numerical calculations are given, and results are presented by graphs. Comparisons for significant points among the more important cases are summarized. For these cases the transients are found to be potentially severe. The effect of the alternator neutral-to-ground impedance is evaluated.

  3. Compact electro-thermal modeling of a SiC MOSFET power module under short-circuit conditions

    DEFF Research Database (Denmark)

    Ceccarelli, Lorenzo; Reigosa, Paula Diaz; Bahman, Amir Sajjad

    2017-01-01

    A novel physics-based, electro-thermal model which is capable of estimating accurately the short-circuit behavior and thermal instabilities of silicon carbide MOSFET multi-chip power modules is proposed in this paper. The model has been implemented in PSpice and describes the internal structure.......2 kV breakdown voltage and about 300 A rated current. The short-circuit behavior of the module is investigated experimentally through a non-destructive test setup and the model is validated. The estimation of overcurrent and temperature distribution among the chips can provide useful information...

  4. Detection Method for Soft Internal Short Circuit in Lithium-Ion Battery Pack by Extracting Open Circuit Voltage of Faulted Cell

    Directory of Open Access Journals (Sweden)

    Minhwan Seo

    2018-06-01

    Full Text Available Early detection of internal short circuit which is main cause of thermal runaway in a lithium-ion battery is necessary to ensure battery safety for users. As a promising fault index, internal short circuit resistance can directly represent degree of the fault because it describes self-discharge phenomenon caused by the internal short circuit clearly. However, when voltages of individual cells in a lithium-ion battery pack are not provided, the effect of internal short circuit in the battery pack is not readily observed in whole terminal voltage of the pack, leading to difficulty in estimating accurate internal short circuit resistance. In this paper, estimating the resistance with the whole terminal voltages and the load currents of the pack, a detection method for the soft internal short circuit in the pack is proposed. Open circuit voltage of a faulted cell in the pack is extracted to reflect the self-discharge phenomenon obviously; this process yields accurate estimates of the resistance. The proposed method is verified with various soft short conditions in both simulations and experiments. The error of estimated resistance does not exceed 31.2% in the experiment, thereby enabling the battery management system to detect the internal short circuit early.

  5. Short circuit experiment on an FCL coil wound with YBCO tape with a high-resistance stabilizing layer

    Energy Technology Data Exchange (ETDEWEB)

    Yazawa, T; Iijima, Y; Saito, T [Toshiba Corporation, Fujikura Ltd (Japan); Amemiya, N [Toshiba Corporation, Yokohama National University (Japan); Shiohara, Y [Toshiba Corporation, ISTEC SRL (Japan); Koyanagi, K; Ono, M; Urata, M, E-mail: takashi.yazawa@toshiba.co.jp

    2008-02-15

    One of the programs in the Ministry of Economy, Trade and Industry regarding R and D for developing YBCO conductors is to evaluate the suitability of the conductors in several applications. This paper focuses on one of the expected power applications, namely, a fault current limiter (FCL). YBCO tape conductors with ion beam assisted deposition (IBAD) substrates are used in this work. In order to increase the resistivity of the conductor, which is preferable for FCL applications, the thickness of a protective layer made of silver was decreased as much as possible. After obtaining the required current limiting performance in short sample experiments, a model coil was developed aiming at 6.6 kV-class FCLs. Short circuit experiments were conducted with a short-circuit generator. The coil successfully suppressed a short-circuit current of over 1.4 kA to about 500 A under an applied voltage of 3.8 kV, which is the nominal phase-to-ground voltage. The coil also suppressed a short-circuit current of 17 kA down to 700 A. The experimental results are as expected and show promise toward FCL applications.

  6. Other origins for the fluorescence modulation of single dye molecules in open-circuit and short-circuit devices.

    Science.gov (United States)

    Teguh, Jefri S; Kurniawan, Michael; Wu, Xiangyang; Sum, Tze Chien; Yeow, Edwin K L

    2013-01-07

    Fluorescence intensity modulation of single Atto647N dye molecules in a short-circuit device and a defective device, caused by damaging an open-circuit device, is due to a variation in the excitation light focus as a result of the formation of an alternating electric current.

  7. Short circuit experiment on an FCL coil wound with YBCO tape with a high-resistance stabilizing layer

    International Nuclear Information System (INIS)

    Yazawa, T; Iijima, Y; Saito, T; Amemiya, N; Shiohara, Y; Koyanagi, K; Ono, M; Urata, M

    2008-01-01

    One of the programs in the Ministry of Economy, Trade and Industry regarding R and D for developing YBCO conductors is to evaluate the suitability of the conductors in several applications. This paper focuses on one of the expected power applications, namely, a fault current limiter (FCL). YBCO tape conductors with ion beam assisted deposition (IBAD) substrates are used in this work. In order to increase the resistivity of the conductor, which is preferable for FCL applications, the thickness of a protective layer made of silver was decreased as much as possible. After obtaining the required current limiting performance in short sample experiments, a model coil was developed aiming at 6.6 kV-class FCLs. Short circuit experiments were conducted with a short-circuit generator. The coil successfully suppressed a short-circuit current of over 1.4 kA to about 500 A under an applied voltage of 3.8 kV, which is the nominal phase-to-ground voltage. The coil also suppressed a short-circuit current of 17 kA down to 700 A. The experimental results are as expected and show promise toward FCL applications

  8. 30 CFR 77.600 - Trailing cables; short-circuit protection; disconnecting devices.

    Science.gov (United States)

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Trailing cables; short-circuit protection... AREAS OF UNDERGROUND COAL MINES Trailing Cables § 77.600 Trailing cables; short-circuit protection; disconnecting devices. Short-circuit protection for trailing cables shall be provided by an automatic circuit...

  9. 30 CFR 75.601 - Short circuit protection of trailing cables.

    Science.gov (United States)

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Short circuit protection of trailing cables. 75... MINE SAFETY AND HEALTH MANDATORY SAFETY STANDARDS-UNDERGROUND COAL MINES Trailing Cables § 75.601 Short circuit protection of trailing cables. [Statutory Provisions] Short circuit protection for trailing cables...

  10. 30 CFR 75.601-1 - Short circuit protection; ratings and settings of circuit breakers.

    Science.gov (United States)

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Short circuit protection; ratings and settings... Trailing Cables § 75.601-1 Short circuit protection; ratings and settings of circuit breakers. Circuit breakers providing short circuit protection for trailing cables shall be set so as not to exceed the...

  11. 30 CFR 75.601-2 - Short circuit protection; use of fuses; approval by the Secretary.

    Science.gov (United States)

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Short circuit protection; use of fuses... Trailing Cables § 75.601-2 Short circuit protection; use of fuses; approval by the Secretary. Fuses shall not be employed to provide short circuit protection for trailing cables unless specifically approved...

  12. 30 CFR 75.518 - Electric equipment and circuits; overload and short circuit protection.

    Science.gov (United States)

    2010-07-01

    ... short circuit protection. 75.518 Section 75.518 Mineral Resources MINE SAFETY AND HEALTH ADMINISTRATION... Equipment-General § 75.518 Electric equipment and circuits; overload and short circuit protection... installed so as to protect all electric equipment and circuits against short circuit and overloads. Three...

  13. Device for testing continuity and/or short circuits in a cable

    Science.gov (United States)

    Hayhurst, Arthur R. (Inventor)

    1995-01-01

    A device for testing current paths is attachable to a conductor. The device automatically checks the current paths of the conductor for continuity of a center conductor, continuity of a shield and a short circuit between the shield and the center conductor. The device includes a pair of connectors and a circuit to provide for testing of the conductive paths of the cable. The pair of connectors electrically connects the conductive paths of a cable to be tested with the circuit paths of the circuit. The circuit paths in the circuit include indicators to simultaneously indicate the results of the testing.

  14. Round busbar concept for 30 nH, 1.7 kV, 10 kA IGBT non-destructive short-circuit tester

    DEFF Research Database (Denmark)

    Smirnova, Liudmila; Pyrhönen, Juha; Iannuzzo, Francesco

    2014-01-01

    Design of a Non-Destructive Test (NDT) set-up for short-circuit tests of 1.7 kV, 1 kA IGBT modules is discussed in this paper. The test set-up allows achieving short-circuit current up to 10 kA. The important objective during the design of the test set-up is to minimize the parasitic inductance...

  15. Closed Form Solution of Synchronous Machine Short Circuit Transients

    Directory of Open Access Journals (Sweden)

    Gibson H.M. Sianipar

    2010-05-01

    Full Text Available This paper presents the closed form solution of the synchronous machine transients undergoing short circuit. That analytic formulation has been derived based on linearity and balanced conditions of the fault. Even though restrictive, the proposed method will serve somehow or other as a new resource for EMTP productivity. Indisputably superior, the closed-form formulation has some features inimitable by discretization such as continuity, accuracy and absolute numerical stability. Moreover, it enables us to calculate states at one specific instant independent of previous states or a snapshot, which any discretization methods cannot do.

  16. A Simple Short Circuit Analysis for Power Networks

    Directory of Open Access Journals (Sweden)

    Koşalay İlhan

    2016-01-01

    Full Text Available This study investigates the transient behavior of short circuits in power circuits. The circuit consists of two part; input part and load part. These two parts are connected with a circuit breaker switch. The circuit works in two modes; first mode is when the switch is open and second mode is when the switch is closed. This study analyses the circuit when the switch is closed. The analysis is done with different types of closing angle. The analysis is done by forming state equations and those equations are solved numerically by using Matlab. The analysis and conclusion is performed by observing the behaviors of the graphs.

  17. Improving the Short-Circuit Reliability in IGBTs

    DEFF Research Database (Denmark)

    Reigosa, Paula Diaz; Iannuzzo, Francesco; Rahimo, Munaf

    2018-01-01

    takes place during the IGBT short-circuit, whose time-varying element is the Miller capacitance, which is involved in the amplification mechanism. This hypothesis has been validated through simulations and its mitigation is possible by increasing the electric field at the emitter of the IGBT......In this paper, the oscillation mechanism limiting the ruggedness of IGBTs is investigated through both circuit and device analysis. The work presented here is based on a time-domain approach for two different IGBT cell structures (i.e., trench-gate and planar), illustrating the 2-D effects during...

  18. Capacitive effects in IGBTs limiting their reliability under short circuit

    DEFF Research Database (Denmark)

    Reigosa, Paula Diaz; Iannuzzo, Francesco; Rahimo, Munaf

    2017-01-01

    The short-circuit oscillation mechanism in IGBTs is investigated in this paper by the aid of semiconductor device simulation tools. A 3.3-kV IGBT cell has been used for the simulations demonstrating that a single IGBT cell is able to oscillate together with the external circuit parasitic elements....... The work presented here through both circuit and device analysis, confirms that the oscillations can be understood with focus on the device capacitive effects coming from the interaction between carrier concentration and the electric field. The paper also shows the 2-D effects during one oscillation cycle...

  19. Short-circuit testing of monofilar Bi-2212 coils connected in series and in parallel

    International Nuclear Information System (INIS)

    Polasek, A; Dias, R; Serra, E T; Filho, O O; Niedu, D

    2010-01-01

    Superconducting Fault Current Limiters (SCFCL's) are one of the most promising technologies for fault current limitation. In the present work, resistive SCFCL components based on Bi-2212 monofilar coils are subjected to short-circuit testing. These SCFCL components can be easily connected in series and/or in parallel by using joints and clamps. This allows a considerable flexibility to developing larger SCFCL devices, since the configuration and size of the whole device can be easily adapted to the operational conditions. The single components presented critical current (Ic) values of 240-260 A, at 77 K. Short-circuits during 40-120 ms were applied. A single component can withstand a voltage drop of 126-252 V (0.3-0.6 V/cm). Components connected in series withstand higher voltage levels, whereas parallel connection allows higher rated currents during normal operation, but the limited current is also higher. Prospective currents as high as 10-40 kA (peak value) were limited to 3-9 kA (peak value) in the first half cycle.

  20. Short-Circuit Degradation of 10-kV 10-A SiC MOSFET

    DEFF Research Database (Denmark)

    Eni, Emanuel-Petre; Beczkowski, Szymon; Munk-Nielsen, Stig

    2017-01-01

    The short-circuit behavior of power devices is highly relevant for converter design and fault protection. In this work, the degradation during short-circuit of a 10 kV 10 A 4H-SiC MOSFET is investigated at 6 kV DC-link voltage. The study aims to present the behavior of the device during short-circuit...... transients as it sustains increasing short-circuit pulses during its life-time. As the short-circuit pulse length increases, degradation of the device can be observed in periodically performed characterizations. The initial degradation seems to be associated with the channel region, and continuous stressing...

  1. A Nanostructured Composites Thermal Switch Controls Internal and External Short Circuit in Lithium Ion Batteries

    Science.gov (United States)

    McDonald, Robert C.; VanBlarcom, Shelly L.; Kwasnik, Katherine E.

    2013-01-01

    A document discusses a thin layer of composite material, made from nano scale particles of nickel and Teflon, placed within a battery cell as a layer within the anode and/or the cathode. There it conducts electrons at room temperature, then switches to an insulator at an elevated temperature to prevent thermal runaway caused by internal short circuits. The material layer controls excess currents from metal-to-metal or metal-to-carbon shorts that might result from cell crush or a manufacturing defect

  2. Errors in short circuit measurements due to spectral mismatch between sunlight and solar simulators

    Science.gov (United States)

    Curtis, H. B.

    1976-01-01

    Errors in short circuit current measurement were calculated for a variety of spectral mismatch conditions. The differences in spectral irradiance between terrestrial sunlight and three types of solar simulator were studied, as well as the differences in spectral response between three types of reference solar cells and various test cells. The simulators considered were a short arc xenon lamp AMO sunlight simulator, an ordinary quartz halogen lamp, and an ELH-type quartz halogen lamp. Three types of solar cells studied were a silicon cell, a cadmium sulfide cell and a gallium arsenide cell.

  3. Various mechanisms and clinical phenotypes in electrical short circuits of high-voltage devices: report of four cases and review of the literature.

    Science.gov (United States)

    Tsurugi, Takuo; Matsui, Shogo; Nakajima, Hiroshi; Nishii, Nobuhiro; Honda, Toshihiro; Kaneko, Yoshiaki

    2015-06-01

    An electrical short circuit is a rare complication in a high-voltage implantable cardioverter-defibrillator (ICD). However, the inability of an ICD to deliver appropriate shock therapy can be life-threatening. During the last 2 years, four cases of serious complications related to an electrical short circuit have been reported in Japan. A spark due to an electrical short circuit resulted in the failure of an ICD shock to terminate ventricular tachycardia and total damage to the ICD generator in three of four cases. Two of the four patients died from an electrical short circuit between the right ventricle and superior vena cava (SVC) leads. The others had audible sounds from the ICD generator site and were diagnosed with a lead-to-can abrasion, which was manifested by the arc mark on the surface of the can. It is still difficult to predict the occurrence of an electrical short circuit in current ICD systems. To reduce the probability of an electrical short circuit, we suggest the following: (i) avoid lead stress at ICD implantation, (ii) select a single-coil lead instead of a dual-coil lead, or (iii) use a unique algorithm which automatically disconnect can or SVC lead from shock deliver circuit when excessive current was detected. Published on behalf of the European Society of Cardiology. All rights reserved. © The Author 2015. For permissions please email: journals.permissions@oup.com.

  4. Tin Whisker Electrical Short Circuit Characteristics. Part 2

    Science.gov (United States)

    Courey, Karim J.; Asfour, Shihab S.; Onar, Arzu; Bayliss, Jon A.; Ludwig, Lawrence L.; Wright, Maria C.

    2009-01-01

    Existing risk simulations make the assumption that when a free tin whisker has bridged two adjacent exposed electrical conductors, the result is an electrical short circuit. This conservative assumption is made because shorting is a random event that has an unknown probability associated with it. Note however that due to contact resistance electrical shorts may not occur at lower voltage levels. In our first article we developed an empirical probability model for tin whisker shorting. In this paper, we develop a more comprehensive empirical model using a refined experiment with a larger sample size, in which we studied the effect of varying voltage on the breakdown of the contact resistance which leads to a short circuit. From the resulting data we estimated the probability distribution of an electrical short, as a function of voltage. In addition, the unexpected polycrystalline structure seen in the focused ion beam (FIB) cross section in the first experiment was confirmed in this experiment using transmission electron microscopy (TEM). The FIB was also used to cross section two card guides to facilitate the measurement of the grain size of each card guide's tin plating to determine its finish.

  5. Spectral analysis to detection of short circuit fault of solar photovoltaic modules in strings

    International Nuclear Information System (INIS)

    Sevilla-Camacho, P.Y.; Robles-Ocampo, J.B.; Zuñiga-Reyes, Marco A.

    2017-01-01

    This research work presents a method to detect the number of short circuit faulted solar photovoltaic modules in strings of a photovoltaic system by taking into account speed, safety, and non-use of sensors and specialized and expensive equipment. The method consists on apply the spectral analysis and statistical techniques to the alternating current output voltage of a string and detect the number of failed modules through the changes in the amplitude of the component frequency of 12 kHz. For that, the analyzed string is disconnected of the array; and a small pulsed voltage signal of frequency of 12 kHz introduces him under dark condition and controlled temperature. Previous to the analysis, the signal is analogic filtered in order to reduce the direct current signal component. The spectral analysis technique used is the Fast Fourier Transform. The obtained experimental results were validated through simulation of the alternating current equivalent circuit of a solar cell. In all experimental and simulated test, the method allowed to identify correctly the number of photovoltaic modules with short circuit in the analyzed string. (author)

  6. Consequences and mitigation of saltwater intrusion induced by short-circuiting during aquifer storage and recovery in a coastal subsurface

    Science.gov (United States)

    Gerardus Zuurbier, Koen; Stuyfzand, Pieter Jan

    2017-02-01

    Coastal aquifers and the deeper subsurface are increasingly exploited. The accompanying perforation of the subsurface for those purposes has increased the risk of short-circuiting of originally separated aquifers. This study shows how this short-circuiting negatively impacts the freshwater recovery efficiency (RE) during aquifer storage and recovery (ASR) in coastal aquifers. ASR was applied in a shallow saltwater aquifer overlying a deeper, confined saltwater aquifer, which was targeted for seasonal aquifer thermal energy storage (ATES). Although both aquifers were considered properly separated (i.e., a continuous clay layer prevented rapid groundwater flow between both aquifers), intrusion of deeper saltwater into the shallower aquifer quickly terminated the freshwater recovery. The presumable pathway was a nearby ATES borehole. This finding was supported by field measurements, hydrochemical analyses, and variable-density solute transport modeling (SEAWAT version 4; Langevin et al., 2007). The potentially rapid short-circuiting during storage and recovery can reduce the RE of ASR to null. When limited mixing with ambient groundwater is allowed, a linear RE decrease by short-circuiting with increasing distance from the ASR well within the radius of the injected ASR bubble was observed. Interception of deep short-circuiting water can mitigate the observed RE decrease, although complete compensation of the RE decrease will generally be unattainable. Brackish water upconing from the underlying aquitard towards the shallow recovery wells of the ASR system with multiple partially penetrating wells (MPPW-ASR) was observed. This leakage may lead to a lower recovery efficiency than based on current ASR performance estimations.

  7. An Investigation of the Electrical Short Circuit Characteristics of Tin Whiskers

    Science.gov (United States)

    Courey, Karim J.

    2008-01-01

    Existing risk simulations make the assumption that when a free tin whisker has bridged two adjacent exposed electrical conductors, the result is an electrical short circuit. This conservative assumption is made because shorting is a random event that has a currently unknown probability associated with it. Due to contact resistance electrical shorts may not occur at lower voltage levels. In this experiment, we study the effect of varying voltage on the breakdown of the contact resistance which leads to a short circuit. From this data we can estimate the probability of an electrical short, as a function of voltage, given that a free tin whisker has bridged two adjacent exposed electrical conductors. Also, three tin whiskers grown from the same Space Shuttle Orbiter card guide used in the aforementioned experiment were cross-sectioned and studied using a focused ion beam (FIB). The rare polycrystalline structure seen in the FIB cross section was confirmed using transmission electron microscopy (TEM). The FIB was also used to cross section two card guides to facilitate the measurement of the grain size to determine that the tin plating on the card guides had a bright finish.

  8. Integrated Power Flow and Short Circuit Calculation Method for Distribution Network with Inverter Based Distributed Generation

    OpenAIRE

    Yang, Shan; Tong, Xiangqian

    2016-01-01

    Power flow calculation and short circuit calculation are the basis of theoretical research for distribution network with inverter based distributed generation. The similarity of equivalent model for inverter based distributed generation during normal and fault conditions of distribution network and the differences between power flow and short circuit calculation are analyzed in this paper. Then an integrated power flow and short circuit calculation method for distribution network with inverte...

  9. Double-layer rotor magnetic shield performance analysis in high temperature superconducting synchronous generators under short circuit fault conditions

    Science.gov (United States)

    Hekmati, Arsalan; Aliahmadi, Mehdi

    2016-12-01

    High temperature superconducting, HTS, synchronous machines benefit from a rotor magnetic shield in order to protect superconducting coils against asynchronous magnetic fields. This magnetic shield, however, suffers from exerted Lorentz forces generated in light of induced eddy currents during transient conditions, e.g. stator windings short-circuit fault. In addition, to the exerted electromagnetic forces, eddy current losses and the associated effects on the cryogenic system are the other consequences of shielding HTS coils. This study aims at investigating the Rotor Magnetic Shield, RMS, performance in HTS synchronous generators under stator winding short-circuit fault conditions. The induced eddy currents in different circumferential positions of the rotor magnetic shield along with associated Joule heating losses would be studied using 2-D time-stepping Finite Element Analysis, FEA. The investigation of Lorentz forces exerted on the magnetic shield during transient conditions has also been performed in this paper. The obtained results show that double line-to-ground fault is of the most importance among different types of short-circuit faults. It was revealed that when it comes to the design of the rotor magnetic shields, in addition to the eddy current distribution and the associated ohmic losses, two phase-to-ground fault should be taken into account since the produced electromagnetic forces in the time of fault conditions are more severe during double line-to-ground fault.

  10. ISC-EHB: Reconstruction of a robust earthquake dataset

    Science.gov (United States)

    Weston, J.; Engdahl, E. R.; Harris, J.; Di Giacomo, D.; Storchak, D. A.

    2018-04-01

    The EHB Bulletin of hypocentres and associated travel-time residuals was originally developed with procedures described by Engdahl, Van der Hilst and Buland (1998) and currently ends in 2008. It is a widely used seismological dataset, which is now expanded and reconstructed, partly by exploiting updated procedures at the International Seismological Centre (ISC), to produce the ISC-EHB. The reconstruction begins in the modern period (2000-2013) to which new and more rigorous procedures for event selection, data preparation, processing, and relocation are applied. The selection criteria minimise the location bias produced by unmodelled 3D Earth structure, resulting in events that are relatively well located in any given region. Depths of the selected events are significantly improved by a more comprehensive review of near station and secondary phase travel-time residuals based on ISC data, especially for the depth phases pP, pwP and sP, as well as by a rigorous review of the event depths in subduction zone cross sections. The resulting cross sections and associated maps are shown to provide details of seismicity in subduction zones in much greater detail than previously achievable. The new ISC-EHB dataset will be especially useful for global seismicity studies and high-frequency regional and global tomographic inversions.

  11. Study on Turn-to-turn Short Circuit On一line Monitoring System for Dry一type Ai r一core Reactor

    Directory of Open Access Journals (Sweden)

    GAO Zi-wei

    2017-04-01

    Full Text Available The change of current value caused by turn-to-turn short circuit of dry-type air-core reactor is so little that failure detection is difficult to be carried out. In order to solve this problem,a new on-line monitoring system based on impedance variation of turn-to-turn short circuit is proposed. The numerical method is applied to analyze the variation of equivalent resistance and equivalent reactance when dry-type air-core reactor winding short circuit happens in different places,and the monitoring method based on harmonic analysis method and quasi- synchronization sampling method is analyzed by theory. The hardware system,which takes single-chip microcomputer as the core of data processing and logic control,completes data acquisition of voltage signal and current signal of the reactor. In the respect of software design,the impedance variation will be uploaded to the PC after it has been calculated by using the above monitoring method,and then monitoring of turn-to-turn short circuit fault will be realized. Finally,the design of on-line monitoring system is studied by testing. The research result shows that,the equivalent resistance increases and the equivalent reactance decreases when turn-to-turn short circuit occurs,and the variation of equivalent resistance is more obvious than equivalent reactance. The experiment results prove that this monitoring method is true and the on-line monitoring system is feasible.

  12. An Empirical Model for Estimating the Probability of Electrical Short Circuits from Tin Whiskers-Part I

    Science.gov (United States)

    Courey, Karim; Wright, Clara; Asfour, Shihab; Bayliss, Jon; Ludwig, Larry

    2008-01-01

    Existing risk simulations make the assumption that when a free tin whisker has bridged two adjacent exposed electrical conductors, the result is an electrical short circuit. This conservative assumption is made because shorting is a random event that has a currently unknown probability associated with it. Due to contact resistance, electrical shorts may not occur at lower voltage levels. In this experiment, we study the effect of varying voltage on the breakdown of the contact resistance which leads to a short circuit. From this data, we can estimate the probability of an electrical short, as a function of voltage, given that a free tin whisker has bridged two adjacent exposed electrical conductors. In addition, three tin whiskers grown from the same Space Shuttle Orbiter card guide used in the aforementioned experiment were cross sectioned and studied using a focused ion beam (FIB).

  13. Thirteen years test experience with short-circuit withstand capability of large power transformers

    NARCIS (Netherlands)

    Smeets, R.P.P.; Paske, te L.H.; Leufkens, P.P.; Fogelberg, T.

    2009-01-01

    The ability to withstand a short circuit is recognised more and more as an essential characteristic of power transformers. IEC and IEEE Standards, as well as other national standards specify short-circuit testing and how to check the withstand capability. Unfortunately, however, there is extensive

  14. Built-in unit with short-circuit insulation for hermetic cable ducts

    International Nuclear Information System (INIS)

    Tschacher, B.; Gurr, W.; Kusserow, J.; Katzmarek, W.

    1984-01-01

    The invention concerns a built-in unit with short-circuit insulation for hermetic cable ducts, especially for containments of nuclear power reactors. The short-circuit insulation is achieved by an insulation plate made from radiation-resistant insulating materials of high mechanical strength

  15. Fourteen years of test experience with short-circuit withstand capability of large power transformers

    NARCIS (Netherlands)

    Smeets, R.P.P.; Paske, te L.H.

    2010-01-01

    Experience is reported of short-circuit testing of large power transformers during the past 14 years by KEMA in the Netherlands. In total, 119 transformers > 25 MVA participated in the survey. KEMA shows that at initial access to standard IEC short-circuit tests, 28% failed initially in a wide range

  16. Robustness of MW-Level IGBT modules against gate oscillations under short circuit events

    DEFF Research Database (Denmark)

    Reigosa, Paula Diaz; Wu, Rui; Iannuzzo, Francesco

    2015-01-01

    The susceptibility of MW-level IGBT power modules to critical gate voltage oscillations during short circuit events has been evidenced experimentally. This paper proposes a sensitivity analysis method to better understand the oscillating behavior dependence on different operating conditions (i...... the oscillation phenomenon, as well as to further improve the device performance during short circuit....

  17. 30 CFR 77.506 - Electric equipment and circuits; overload and short-circuit protection.

    Science.gov (United States)

    2010-07-01

    ... short-circuit protection. 77.506 Section 77.506 Mineral Resources MINE SAFETY AND HEALTH ADMINISTRATION... circuits; overload and short-circuit protection. Automatic circuit-breaking devices or fuses of the correct type and capacity shall be installed so as to protect all electric equipment and circuits against short...

  18. On-line diagnosis of inter-turn short circuit fault for DC brushed motor.

    Science.gov (United States)

    Zhang, Jiayuan; Zhan, Wei; Ehsani, Mehrdad

    2018-06-01

    Extensive research effort has been made in fault diagnosis of motors and related components such as winding and ball bearing. In this paper, a new concept of inter-turn short circuit fault for DC brushed motors is proposed to include the short circuit ratio and short circuit resistance. A first-principle model is derived for motors with inter-turn short circuit fault. A statistical model based on Hidden Markov Model is developed for fault diagnosis purpose. This new method not only allows detection of motor winding short circuit fault, it can also provide estimation of the fault severity, as indicated by estimation of the short circuit ratio and the short circuit resistance. The estimated fault severity can be used for making appropriate decisions in response to the fault condition. The feasibility of the proposed methodology is studied for inter-turn short circuit of DC brushed motors using simulation in MATLAB/Simulink environment. In addition, it is shown that the proposed methodology is reliable with the presence of small random noise in the system parameters and measurement. Copyright © 2018 ISA. Published by Elsevier Ltd. All rights reserved.

  19. Sixteen years of test experiences with short-circuit withstand capability of large power transformers

    NARCIS (Netherlands)

    Smeets, R.P.P.; Paske, te L.H.

    2012-01-01

    Experience is reported of short-circuit testing of large power transformers during the past 16 years by KEMA in the Netherlands. In total, 174 transformers > 25 MVA participated in the survey. KEMA shows that at initial access to standard IEC short-circuit tests, 24% failed initially in a wide range

  20. Cage-rotor induction motor inter-turn short circuit fault detection with and without saturation effect by MEC model.

    Science.gov (United States)

    Naderi, Peyman

    2016-09-01

    The inter-turn short fault for the Cage-Rotor-Induction-Machine (CRIM) is studied in this paper and its local saturation is taken into account. However, in order to observe the exact behavior of machine, the Magnetic-Equivalent-Circuit (MEC) and nonlinear B-H curve are proposed to provide an insight into the machine model and saturation effect respectively. The electrical machines are generally operated near to their saturation zone due to some design necessities. Hence, when the machine is exposed to a fault such as short circuit or eccentricities, it is operated within its saturation zone and thus, time and space harmonics are integrated and as a result, current and torque harmonics are generated which the phenomenon cannot be explored when saturation is dismissed. Nonetheless, inter-turn short circuit may lead to local saturation and this occurrence is studied in this paper using MEC model. In order to achieve the mentioned objectives, two and also four-pole machines are modeled as two samples and the machines performances are analyzed in healthy and faulty cases with and without saturation effect. A novel strategy is proposed to precisely detect inter-turn short circuit fault according to the stator׳s lines current signatures and the accuracy of the proposed method is verified by experimental results. Copyright © 2016 ISA. Published by Elsevier Ltd. All rights reserved.

  1. THE RELIABILITY OF DETERMINING THE SHORT CIRCUIT ZONE OF THE LINES OF 6–35 kV

    Directory of Open Access Journals (Sweden)

    F. А. Romaniuk

    2018-01-01

    Full Text Available A method of increasing the reliability of determining the zone of short-circuit at the current step protection of the lines of 6–35 kV with unilateral power, aimed at improvement of their technical perfection, is presented in the paper. Having taken the relative simpleness of the current protection into account the authors consider the unilateral remote method of accounting the parameters of the emergency mode and the type of fault to be the most suitable for the implementation of the algorithm of its functioning as compared with the existing methods of fault location. The major factors affecting the accuracy of determining the short circuit zone based on the remote method are noted. With the use of the method of computational experiment the influence of the load currents and contact resistances of various levels on the magnitude and character of changes of errors of determination of the calculated distance of the point of fault from the protection installation location taking into account the errors of measuring transformers. It is demonstrated that in many cases of arc short circuit in a loaded line in order to define the zone of short-circuit with fair accuracy correction of the estimated distance to the fault as calculated by the parameters of the damaged loop (loops is required. According to the results of numerical experiments corrective expressions on the basis of two relative asymmetry currents determined by the current values of the differences of the phase currents of the line for detecting a type of a short circuit have been obtained. The assessment of the efficiency of the proposed method has been performed. It is shown that the application of the proposed correction method makes it possible to increase the accuracy of fault zone detection. The dynamic properties of the proposed method applied to different modes of the line functioning have been studied. It is determined that in the worst case the definition of the fault zone for a

  2. On the short circuit resilience of organic solar cells: prediction and validation.

    Science.gov (United States)

    Oostra, A Jolt; Smits, Edsger C P; de Leeuw, Dago M; Blom, Paul W M; Michels, Jasper J

    2015-09-07

    The operational characteristics of organic solar cells manufactured with large area processing methods suffers from the occurrence of short-circuits due to defects in the photoactive thin film stack. In this work we study the effect of a shunt resistance on an organic solar cell and demonstrate that device performance is not affected negatively as long as the shunt resistance is higher than approximately 1000 Ohm. By studying charge transport across PSS-lithium fluoride/aluminum (LiF/Al) shunting junctions we show that this prerequisite is already met by applying a sufficiently thick (>1.5 nm) LiF layer. We demonstrate that this remarkable shunt-resilience stems from the formation of a significant charge transport barrier at the PSS-LiF/Al interface. We validate our predictions by fabricating devices with deliberately severed photoactive layers and find an excellent agreement between the calculated and experimental current-voltage characteristics.

  3. Short-circuit tests of 1650 and 96 MVA transformers for 1300 MW french nuclear power plants

    International Nuclear Information System (INIS)

    Mailhot, M.

    1989-01-01

    Power evacuation and feeding of the auxiliaries directly from the 400 kV grid are sensitive points governing the security of 1300 MW PWR Nuclear Power Plants of the French Program. These two different functions are provided by two specific types of transformers. - Banks of 3 single-phase 550 MVA - 400 kV/20 kV transformers. - Three-phase 96 MVA - 400 kV / 3 x 6.8 kV transformers. These passive elements must have a never failing reliability and assure a continuous service in spite of electric, thermal and mechanical stresses that may occur during the lifetime of the power plant. Dielectric and thermal tests carried out in the manufacturers test floors insure these stresses withstand capabilities of transformers. In France, high short-circuit power for the 400 kV network added to often low impedance voltages for transformers impose on them very high stresses during short-circuits. Calculation and experimentation on scale or partial models are not sufficient to insure short-circuit currents withstand capabilities of transformers. The margin of uncertainty dependent on obligatory extrapolations for this kind of complex systems [steel, magnetic sheets, copper, oil, paper and transformerboard] can be reduced in a significant way only by real scale tests on prototypes. These tests that need both high power and voltage cannot be performed in manufacturers test floors. So, in France they are carried out at the EDF Les Renardieres Laboratory. Following paper deals with SHELL TYPE TRANSFORMERS which, particularly thanks to their interleaved rectangular windings display a great resistance to short-circuit stresses

  4. The principle of elaboration of the relay protection against short circuits between the closely placed phases of high voltage electrical line

    Directory of Open Access Journals (Sweden)

    Kiorsak M.

    2015-12-01

    Full Text Available The article is devoted to the elaboration of the principle of relay protection against short circuits between the closely placed phases of higher voltage electrical line with self-compensation, based on the six phase’s symmetrical components. It is shown that the unsymmetrical short circuits between the closely placed phases are characterized by appearance of zero and tertiary sequences of symmetrical components. This fact can be used to choose them for relay protection. The electrical basic circuits and formulas for calculation of the passive parameters of zero and tertiary filters of currents (voltages are done. It is presented the structural-functional basic circuit scheme for relay protection against short circuits between the closely placed phases of higher voltage electrical line with self-compensation.

  5. Evaporating short-circuits in the ATLAS liquid argon barrel presampler 006

    CERN Document Server

    Belhorma, B; Lund-Jensen, B; Rydström, S; Yamouni, M

    2005-01-01

    A technique to eliminate or limit the implications of short-circuits in the ATLAS barrel presampler is described. A high voltage capacitor with a large capacity is charged at different high voltages and discharged through the short-circuit which allows either to disintegrate the dust being the origin of the short-circuit, or to burn away a thin etched copper strip which acts as a fuse on the corresponding presampler anode. This effect is possible even in the presence of a resistive HV cable (10 to 30 ohms) in series which dampens the pulse.

  6. Direct observation of short-circuit diffusion during the formation of a single cupric oxide nanowire

    International Nuclear Information System (INIS)

    Cheng, C-L; Ma, Y-R; Chou, M H; Huang, C Y; Yeh, V; Wu, S Y

    2007-01-01

    Short-circuit diffusion was observed in a single CuO nanowire synthesized using a thermal oxidation method. The confocal Raman spectra of a single CuO nanowire permit direct observation of the nature of an individual CuO nanowire. The parameter order obtained from the inverse Raman B g 2 peak linewidth results in the length dependence of the linewidth and a short-circuit diffusion length of 3.3 μm. The observed structural information is also consistent with the energy dispersive x-ray spectroscopic mapping. The results confirm that the growth of CuO nanowires occurs through the short-circuit diffusion mechanism

  7. Non-Destructive Investigation on Short Circuit Capability of Wind-Turbine-Scale IGBT Power Modules

    DEFF Research Database (Denmark)

    Wu, Rui; Iannuzzo, Francesco; Wang, Huai

    2014-01-01

    This paper presents a comprehensive investigation on the short circuit capability of wind-turbine-scale IGBT power modules by means of a 6 kA/1.1 kV non-destructive testing system. A Field Programmable Gate Array (FPGA) supervising unit is adpoted to achieve an accurate time control for short...... circuit test, which enables to define the driving signals with an accuracy of 10 ns. Thanks to the capability and the effectiveness of the constructed setup, oscillations appearing during short circuits of the new-generation 1.7 kV/1 kA IGBT power modules have been evidenced and characterized under...

  8. Rebuild of the Bulletin of the International Seismological Centre (ISC), part 1: 1964-1979

    Science.gov (United States)

    Storchak, Dmitry A.; Harris, James; Brown, Lonn; Lieser, Kathrin; Shumba, Blessing; Verney, Rebecca; Di Giacomo, Domenico; Korger, Edith I. M.

    2017-12-01

    The data from the Bulletin of the International Seismological Centre (ISC) have always been and still remain in demand for a wide range of studies in Geosciences. The unique features of the Bulletin include long-term coverage (1904-present), the most comprehensive set of included seismic data from the majority of permanent seismic networks at any given time in the history of instrumental recording (currently 150) and homogeneity of the data and their representation. In order to preserve this homogeneity, the ISC has followed its own standard seismic event processing procedures that have not substantially changed until the early 2000s. Several considerable and necessary advancements in the ISC data collection and seismic event location procedures have created a need to rebuild the data for preceding years in line with the new procedures. Thus was set up a project to rebuild the ISC Bulletin for the period from the beginning of the ISC data till the end of data year 2010. The project is known as the Rebuild of the ISC Bulletin. From data month of January 2011, the ISC data have already been processed with the fully tested and established new procedures and do not require an alteration. It was inconceivable even to think about such a project for many tens of years, but great advances in computer power and increased support by the ISC Member-Institutions and Sponsors have given us a chance to perform this project. Having obtained a lot of experience on the way, we believe that within a few years the entire period of the ISC data will be reprocessed and extended for the entire period of instrumental seismological recordings from 1904 till present. The purpose of this article is to describe the work on reprocessing the ISC Bulletin data under the Rebuild project. We also announce the release of the rebuilt ISC Bulletin for the period 1964-1979 with all seismic events reprocessed and relocated in line with the modern ISC procedures, 68,000 new events, 255 new stations

  9. 30 CFR 77.506-1 - Electric equipment and circuits; overload and short circuit protection; minimum requirements.

    Science.gov (United States)

    2010-07-01

    ... short circuit protection; minimum requirements. 77.506-1 Section 77.506-1 Mineral Resources MINE SAFETY...-1 Electric equipment and circuits; overload and short circuit protection; minimum requirements. Devices providing either short circuit protection or protection against overload shall conform to the...

  10. 30 CFR 75.518-1 - Electric equipment and circuits; overload and short circuit protection; minimum requirements.

    Science.gov (United States)

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Electric equipment and circuits; overload and short circuit protection; minimum requirements. 75.518-1 Section 75.518-1 Mineral Resources MINE SAFETY... short circuit protection; minimum requirements. A device to provide either short circuit protection or...

  11. Updating default depths in the ISC bulletin

    Science.gov (United States)

    Bolton, Maiclaire K.; Storchak, Dmitry A.; Harris, James

    2006-09-01

    The International Seismological Centre (ISC) publishes the definitive global bulletin of earthquake locations. In the ISC bulletin, we aim to obtain a free depth, but often this is not possible. Subsequently, the first option is to obtain a depth derived from depth phases. If depth phases are not available, we then use the reported depth from a reputable local agency. Finally, as a last resort, we set a default depth. In the past, common depths of 10, 33, or multiples of 50 km have been assigned. Assigning a more meaningful default depth, specific to a seismic region will increase the consistency of earthquake locations within the ISC bulletin and allow the ISC to publish better positions and magnitude estimates. It will also improve the association of reported secondary arrivals to corresponding seismic events. We aim to produce a global set of default depths, based on a typical depth for each area, from well-constrained events in the ISC bulletin or where depth could be constrained using a consistent set of depth phase arrivals provided by a number of different reporters. In certain areas, we must resort to using other assumptions. For these cases, we use a global crustal model (Crust2.0) to set default depths to half the thickness of the crust.

  12. PSPICE simulation of bipolar pulse converter based on short-circuited coaxial transmission line

    International Nuclear Information System (INIS)

    Shi Lei; Fan Yajun

    2010-01-01

    The operating principle of the bipolar pulse converter based on short-circuited coaxial transmission line type is given. The output bipolar pulses are simulated by using PSPICE program on condition of different electric length and different impedance of the short-circuited coaxial transmission line. The bipolar pulses are generated by using unipolar pulse with pulse width of 2 ns in experiment, the experimental result fit well with the simulation result. (authors)

  13. Modeling of Short-Circuit-Related Thermal Stress in Aged IGBT Modules

    DEFF Research Database (Denmark)

    Bahman, Amir Sajjad; Iannuzzo, Francesco; Uhrenfeldt, Christian

    2017-01-01

    In this paper, the thermal stress on bond wires of aged IGBT modules under short-circuit conditions has been studied with respect to different solder delamination levels. To ensure repeatable test conditions, ad-hoc DBC (direct bond copper) samples with delaminated solder layers have been purposely...... in the surface temperature distribution, which confirms the hypothesis that short-circuit events produce significantly uneven stresses on bond wires....

  14. Prediction of Short-Circuit-Related Thermal Stress in Aged IGBT Modules

    DEFF Research Database (Denmark)

    Bahman, Amir Sajjad; Iannuzzo, Francesco; Uhrenfeldt, Christian

    2016-01-01

    In this paper, the thermal stress on bond wires of aged IGBT modules under short-circuit conditions has been studied with respect to different solder delamination levels. To ensure repeatable test conditions, ad-hoc DBC (direct bond copper) samples with delaminated solder layers have been purposely...... in the surface temperature distribution which confirms the hypothesis that short-circuit events produce significantly uneven stresses on bond wires....

  15. Minimum short-circuit ratios for grid interconnection of wind farms with induction generators

    Energy Technology Data Exchange (ETDEWEB)

    Reginatto, Romeu; Rocha, Carlos [Western Parana State University (UNIOESTE), Foz do Iguacu, PR (Brazil). Center for Engineering and Exact Sciences], Emails: romeu@unioeste.br, croberto@unioeste.br

    2009-07-01

    This paper concerns the problem of determining the minimum value for the short-circuit ratio which is adequate for the interconnection of a given wind farms to a given grid point. First, a set of 3 criteria is defined in order to characterize the quality/safety of the interconnection: acceptable terminal voltage variations, a minimum active power margin, and an acceptable range for the internal voltage angle. Then, the minimum short circuit ratio requirement is determined for 6 different induction generator based wind turbines, both fixed-speed (with and without reactive power compensation) and variable-speed (with the following control policies: reactive power, power factor, and terminal voltage regulation). The minimum short-circuit ratio is determined and shown in graphical results for the 6 wind turbines considered, for X/R in the range 0-15, also analyzing the effect of more/less stringent tolerances for the interconnection criteria. It is observed that the tighter the tolerances the larger the minimum short-circuit ratio required. For the same tolerances in the interconnection criteria, a comparison of the minimum short circuit ratio required for the interconnection of both squirrel-cage and doubly-fed induction generators is presented, showing that the last requires much smaller values for the short-circuit ratio. (author)

  16. The Simulation Computer Based Learning (SCBL) for Short Circuit Multi Machine Power System Analysis

    Science.gov (United States)

    Rahmaniar; Putri, Maharani

    2018-03-01

    Strengthening Competitiveness of human resources become the reply of college as a conductor of high fomal education. Electrical Engineering Program UNPAB (Prodi TE UNPAB) as one of the department of electrical engineering that manages the field of electrical engineering expertise has a very important part in preparing human resources (HR), Which is required by where graduates are produced by DE UNPAB, Is expected to be able to compete globally, especially related to the implementation of Asean Economic Community (AEC) which requires the active participation of graduates with competence and quality of human resource competitiveness. Preparation of HR formation Competitive is done with the various strategies contained in the Seven (7) Higher Education Standard, one part of which is the implementation of teaching and learning process in Electrical system analysis with short circuit analysis (SCA) This course is a course The core of which is the basis for the competencies of other subjects in the advanced semester at Development of Computer Based Learning model (CBL) is done in the learning of interference analysis of multi-machine short circuit which includes: (a) Short-circuit One phase, (B) Two-phase Short Circuit Disruption, (c) Ground Short Circuit Disruption, (d) Short Circuit Disruption One Ground Floor Development of CBL learning model for Electrical System Analysis course provides space for students to be more active In learning in solving complex (complicated) problems, so it is thrilling Ilkan flexibility of student learning how to actively solve the problem of short-circuit analysis and to form the active participation of students in learning (Student Center Learning, in the course of electrical power system analysis.

  17. Method of repair of short circuits for in-situ leaching

    International Nuclear Information System (INIS)

    Baughman, D.R.; Bergeson, J.R.

    1984-01-01

    In an acidic in-situ leaching system, a short circuit passage through a subterranean formation between a fracture associated with an injection well and a fracture associated with a production well can be plugged by introducing a non-acidic liquid for displacing acidic leach liquid from the short circuit passage, introducing into the injection well a basic composition including a sealing material that gels under acidic conditions, and introducing sufficient liquid into the injection well to displace at least a portion of the basic composition containing sealing material from the injection well into the short circuit passage. Liquid flow between the injection well and the production well is then discontinued for a sufficient time for residual acid in the subterranean formation surrounding the short circuit passage to contact the sealing material and cause gelation of the sealing material in the short circuit passage. The introduction of acidic leach liquid to the formation can then continue. The sealing material may be a polymer or a water soluble silicate

  18. Experimental investigation of internal short circuits in lithium-ion batteries

    Science.gov (United States)

    Poramapojana, Poowanart

    With outstanding performance of Lithium-ion batteries, they have been widely used in many applications. For hybrid electric vehicles and electric vehicles, customer concerns of battery safety have been raised as a number of car accidents were reported. To evaluate safety performance of these batteries, a nail penetration test is used to simulate and induce internal short circuits instantaneously. Efforts to explain failure mechanisms of the penetration using electrochemical-thermal coupled models have been proposed. However, there is no experimental validation because researchers lack of a diagnostic tool to acquire important cell characteristics at a shorting location, such as shorting current and temperature. In this present work, diagnostic nails have been developed to acquire nail center temperatures and shorting current flow through the nails during nail penetration tests. Two types of cylindrical wall structures are used to construct the nails: a double-layered stainless steel wall and a composite cylindrical wall. An inner hollow cylinder functions as a sensor holder where two wires and one thermocouple are installed. To study experimental reproducibility and repeatability of experimental results, two nail penetration tests are conducted using two diagnostic nails with the double-layered wall. Experimental data shows that the shorting resistance at the initial stage is a critical parameter to obtain repeatable results. The average shorting current for both tests is approximately 40 C-rate. The fluctuation of the shorting current is due to random sparks and fire caused loose contacts between the nail and the cell components. Moreover, comparative experimental results between the two wall structures reveal that the wall structure does not affect the cell characteristics and Ohmic heat generation of the nail. The wall structure effects to current measurements inside the nail. With the composite wall, the actual current redistribution into the inner wall is

  19. Limitation of short-circuit power due to distributed generation

    NARCIS (Netherlands)

    Morren, J.; Reckers, T.J.M.; Berende, M.J.C.; Slootweg, J.G.

    2012-01-01

    Introduction of DG units in the network will result in increasing fault current levels. In this contribution several solutions are described to limit the fault currents in the network, in order to avoid overloading and destruction of components in the networks. The main focus of the paper is on the

  20. Approximate entropy—a new statistic to quantify arc and welding process stability in short-circuiting gas metal arc welding

    International Nuclear Information System (INIS)

    Cao Biao; Xiang Yuanpeng; Lü Xiaoqing; Zeng Min; Huang Shisheng

    2008-01-01

    Based on the phase state reconstruction of welding current in short-circuiting gas metal arc welding using carbon dioxide as shielding gas, the approximate entropy of welding current as well as its standard deviation has been calculated and analysed to investigate their relation with the stability of electric arc and welding process. The extensive experimental and calculated results show that the approximate entropy of welding current is significantly and positively correlated with arc and welding process stability, whereas its standard deviation is correlated with them negatively. A larger approximate entropy and a smaller standard deviation imply a more stable arc and welding process, and vice versa. As a result, the approximate entropy of welding current promises well in assessing and quantifying the stability of electric arc and welding process in short-circuiting gas metal arc welding

  1. Fault Detection and Location of IGBT Short-Circuit Failure in Modular Multilevel Converters

    Directory of Open Access Journals (Sweden)

    Bin Jiang

    2018-06-01

    Full Text Available A single fault detection and location for Modular Multilevel Converter (MMC is of great significance, as numbers of sub-modules (SMs in MMC are connected in series. In this paper, a novel fault detection and location method is proposed for MMC in terms of the Insulated Gate Bipolar Translator (IGBT short-circuit failure in SM. The characteristics of IGBT short-circuit failures are analyzed, based on which a Differential Comparison Low-Voltage Detection Method (DCLVDM is proposed to detect the short-circuit fault. Lastly, the faulty IGBT is located based on the capacitor voltage of the faulty SM by Continuous Wavelet Transform (CWT. Simulations have been done in the simulation software PSCAD/EMTDC and the results confirm the validity and reliability of the proposed method.

  2. Data on the natural ventilation performance of windcatcher with anti-short-circuit device (ASCD).

    Science.gov (United States)

    Nejat, Payam; Calautit, John Kaiser; Majid, Muhd Zaimi Abd; Hughes, Ben Richard; Jomehzadeh, Fatemeh

    2016-12-01

    This article presents the datasets which were the results of the study explained in the research paper 'Anti-short-circuit device: a new solution for short-circuiting in windcatcher and improvement of natural ventilation performance' (P. Nejat, J.K. Calautit, M.Z. Abd. Majid, B.R. Hughes, F. Jomehzadeh, 2016) [1] which introduces a new technique to reduce or prevent short-circuiting in a two-sided windcatcher and also lowers the indoor CO2 concentration and improve the ventilation distribution. Here, we provide details of the numerical modeling set-up and data collection method to facilitate reproducibility. The datasets includes indoor airflow, ventilation rates and CO2 concentration data at several points in the flow field. The CAD geometry of the windcatcher models are also included.

  3. Allocation of synchronous condensers for restoration of system short-circuit power

    DEFF Research Database (Denmark)

    Marrazi, Emanuel; Yang, Guangya; Weinreich-Jensen, Peter

    2017-01-01

    Modern power systems, employing an increasing number of converter-based renewable energy sources (RES) and decreasing the usage of conventional power plants, are leading to lower levels of short-circuit power and rotational inertia. A solution to this is the employment of synchronous condensers...... in the grid, in order to provide sufficient short-circuit power. This results in the increase of the short-circuit ratio (SCR) at transmission system bus-bars serving as points of interconnection (POI) to renewable generation. Evaluation of the required capacity and grid-location of the synchronous condensers......, isinherently a mixed integer non-linear optimization problem, which could not be done on manual basis considering each type of machine and all bus-bars. This study therefore proposes a method of optimal allocation of synchronous condensers in a hypothetic future scenario of a transmission system fed...

  4. Allocation of synchronous condensers for restoration of system short-circuit power

    DEFF Research Database (Denmark)

    Marrazi, Emanuel; Yang, Guangya; Weinreich-Jensen, Peter

    2017-01-01

    Modern power systems, employing an increasing number of converter-based renewable energy sources (RES) and decreasing the usage of conventional power plants, are leading to lower levels of short-circuit power and rotational inertia. A solution to this is the employment of synchronous condensers...... in the grid, in order to provide sufficient short-circuit power. This results in the increase of the short-circuit ratio (SCR) at transmission system bus-bars serving as points of interconnection (POI) to renewable generation. Evaluation of the required capacity and grid-location of the synchronous condensers...... by renewable generation. Total cost of synchronous condenser installations in the system is minimized and the SCRs at the POIs of central renewable power plants are strengthened. The method has potential for application on larger grids, aiding grid-integration of RES....

  5. Clearance of short circuited ion optics electrodes by capacitive discharge. [in ion thrusters

    Science.gov (United States)

    Poeschel, R. L.

    1976-01-01

    The ion optics electrodes of low specific impulse (3000 sec) mercury electron bombardment ion thrusters are vulnerable to short circuits by virtue of their relatively small interelectrode spacing (0.5 mm). Metallic flakes from backsputtered deposits are the most probable cause of such 'shorts' and 'typical' flakes have been simulated here using refractory wire that has a representative, but controllable, cross section. Shorting wires can be removed by capacitive discharge without significant damage to the electrodes. This paper describes an evaluation of 'short' removal versus electrode damage for several combinations of capacitor voltage, stored energy, and short circuit conditions.

  6. Voltage Recovery of Grid-Connected Wind Turbines with DFIG After a Short-Circuit Fault

    DEFF Research Database (Denmark)

    Sun, Tao; Chen, Zhe; Blaabjerg, Frede

    2004-01-01

    The fast development of wind power generation brings new requirements for wind turbine integration to the network. After clearance of an external short-circuit fault, the voltage at the wind turbine terminal should be re-established with minimized power losses. This paper concentrates on voltage......-establish the wind turbine terminal voltage after the clearance of an external short-circuit fault, and the restore the normal operation of the variable speed wind turbine with DFIG, which has been demonstrated by simulation results....

  7. Knock-downs of mitochondrial iron-sulfur cluster assembly proteins IscS and IscU down-regulate the active mitochondrion of procyclic Trypanosoma brucei

    Czech Academy of Sciences Publication Activity Database

    Šmíd, O.; Horáková, Eva; Vilímová, V.; Hrdý, I.; Cammack, R.; Horváth, A.; Lukeš, Julius; Tachezy, J.

    2006-01-01

    Roč. 281, č. 39 (2006), s. 28679-28686 ISSN 0021-9258 R&D Projects: GA ČR GA204/04/0435; GA AV ČR IAA5022302 Institutional research plan: CEZ:AV0Z60220518 Keywords : IscS * IscU * FeS Subject RIV: EB - Genetics ; Molecular Biology Impact factor: 5.808, year: 2006

  8. Short circuit signatures from different wind turbine generator types

    DEFF Research Database (Denmark)

    Martinez, Jorge; Kjær, Philip C.; Rodriguez, Pedro

    2011-01-01

    Modern wind power plants are required and designed to ride through faults in the network, subjected to the fault clearance and following grid code demands. Beside voltage support during faults, the wind turbine fault current contribution is important to establish the correct settings for the relay...... of the protections. The following wind turbine generator during faults have been studied: (i) induction generator, (ii) induction generator with variable rotor resistance (iii) converter-fed rotor (often referred to as DFIG) and (iv) full scale converter. To make a clear comparison and performance analysis during...... faults, and the consequent effects on substation protections, the aforementioned configurations have been simulated using PSCAD/EMTDC, with the same power plant configuration, electrical grid and generator data. Additionally, a comparison of these wind turbine technologies with a conventional power plant...

  9. Minimization of the Electromagnetic Torque Ripple Caused by the Coils Inter-Turn Short Circuit Fault in Dual-Redundancy Permanent Magnet Synchronous Motors

    Directory of Open Access Journals (Sweden)

    Yiguang Chen

    2017-11-01

    Full Text Available With the development of electric vehicles and More-Electric/All-Electric aircraft, high reliability is required in motor servo systems. The redundancy technique is one of the most effective methods to improve the reliability of motor servo systems. In this paper, the structure of dual-redundancy permanent magnet synchronous motor (DRPMSM with weak thermal coupling and no electromagnetic coupling is analyzed and the mathematical model of this motor is established. However, there is little research on how to suppress the torque ripple caused by short-circuited coils in the DRPMSM. The main contribution of this paper is to present the advantages of DRPMSM and to find a way to suppress the torque ripple caused by the short circuit fault in DRPMSM. In order to improve operation quality and enhance the reliability of DRPMSM after a short circuit occurs, the torque ripple caused by the coils inter-turn short circuit fault in DRPMSM is analyzed in detail. Then, a control method for suppressing the electromagnetic torque ripple of a short-circuited coil is proposed for the first time by using an improved adaptive proportional resonant (PR controller and a proportional integral (PI controller in parallel. PR control is a method of controlling alternating components without steady-state error, and it can be used to suppress torque ripple. DRPMSM adopts speed and current double closed-loop control strategies. An improved adaptive PR controller and a PI controller are employed in parallel for the speed loop, while traditional PI control is adopted in current loop. From the simulation and experimental results, the torque ripple is reduced from 45.4 to 5.6% when the torque ripple suppression strategy proposed in this paper is adopted, in the case that the speed is 600 r/min. The torque ripple suppression strategy based on the PR controller can quickly and effectively suppress the torque ripple caused by the short-circuited coils, which makes the motor speed

  10. Development of internal/external short circuit protection for lithium D cells

    Science.gov (United States)

    Mcdonald, Robert C.; Bragg, Bobby J.

    1992-01-01

    A brief discussion of short circuit protection for lithium D cells is given in viewgraph format. The following topics are presented: (1) historical need; (2) program objectives; (3) composite thermal switch (CTS) development; (4) laboratory cells with CTS; and (5) the incorporation of CTS into lithium D cells.

  11. Network model and short circuit program for the Kennedy Space Center electric power distribution system

    Science.gov (United States)

    1976-01-01

    Assumptions made and techniques used in modeling the power network to the 480 volt level are discussed. Basic computational techniques used in the short circuit program are described along with a flow diagram of the program and operational procedures. Procedures for incorporating network changes are included in this user's manual.

  12. Estimating the Probability of Electrical Short Circuits from Tin Whiskers. Part 2

    Science.gov (United States)

    Courey, Karim J.; Asfour, Shihab S.; Onar, Arzu; Bayliss, Jon A.; Ludwig, Larry L.; Wright, Maria C.

    2010-01-01

    To comply with lead-free legislation, many manufacturers have converted from tin-lead to pure tin finishes of electronic components. However, pure tin finishes have a greater propensity to grow tin whiskers than tin-lead finishes. Since tin whiskers present an electrical short circuit hazard in electronic components, simulations have been developed to quantify the risk of said short circuits occurring. Existing risk simulations make the assumption that when a free tin whisker has bridged two adjacent exposed electrical conductors, the result is an electrical short circuit. This conservative assumption is made because shorting is a random event that had an unknown probability associated with it. Note however that due to contact resistance electrical shorts may not occur at lower voltage levels. In our first article we developed an empirical probability model for tin whisker shorting. In this paper, we develop a more comprehensive empirical model using a refined experiment with a larger sample size, in which we studied the effect of varying voltage on the breakdown of the contact resistance which leads to a short circuit. From the resulting data we estimated the probability distribution of an electrical short, as a function of voltage. In addition, the unexpected polycrystalline structure seen in the focused ion beam (FIB) cross section in the first experiment was confirmed in this experiment using transmission electron microscopy (TEM). The FIB was also used to cross section two card guides to facilitate the measurement of the grain size of each card guide's tin plating to determine its finish .

  13. Short-Circuit Robustness Assessment in Power Electronic Modules for Megawatt Applications

    DEFF Research Database (Denmark)

    Iannuzzo, Francesco

    2016-01-01

    In this paper, threats and opportunities in testing of megawatt power electronic modules under short circuit are presented and discussed, together with the introduction of some basic principles of non-destructive testing, a key technique to allow post-failure analysis. The non-destructive testing...

  14. L2 Reading Ability: Further Insight into the Short-Circuit Hypothesis.

    Science.gov (United States)

    Taillefer, Gail F.

    1996-01-01

    Discusses the notion of a language proficiency threshold that short circuits the transfer of reading ability from the native language (L1) to a second language (L2). This study, in which cognitive complexity of tasks and students' L2 proficiency levels vary, focuses on university students in France reading preprofessional English texts. (39…

  15. Results of experimental research of the modes of short circuit in a traction network

    Directory of Open Access Journals (Sweden)

    P.Ye. Mykhalichenko

    2012-08-01

    Full Text Available In the article the results, namely oscillograms of the transitional feeder electric values obtained by the experimental tests of the short circuit modes in case of setting off different types of substation fast-acting switches are presented. The experiments were conducted on the operating electrified track sections of the Prydniprovs’ka Railway.

  16. EQUATIONS OF ELECTRIC MOTOR POWER SUPPLY UNIT DISSYMMETRY UNDER PHASE SHORT-CIRCUIT FAULT

    Directory of Open Access Journals (Sweden)

    V.Y. Tchaban

    2013-04-01

    Full Text Available In the paper, a formula is introduced for calculating electric motor supply unit voltage under feeding by a common transformer in the condition of a phase short-circuit in one of the motors. The formula is used in every time step of electromechanical state equations integration.

  17. Interaction of ultrashort laser pulses and silicon solar cells under short circuit conditions

    Energy Technology Data Exchange (ETDEWEB)

    Mundus, M., E-mail: markus.mundus@ise.fraunhofer.de; Giesecke, J. A.; Fischer, P.; Hohl-Ebinger, J.; Warta, W. [Fraunhofer Institute for Solar Energy Systems (ISE), Heidenhofstraße 2, 79110 Freiburg (Germany)

    2015-02-28

    Ultrashort pulse lasers are promising tools for numerous measurement purposes. Among other benefits their high peak powers allow for efficient generation of wavelengths in broad spectral ranges and at spectral powers that are orders of magnitude higher than in conventional light sources. Very recently this has been exploited for the establishment of sophisticated measurement facilities for electrical characterization of photovoltaic (PV) devices. As the high peak powers of ultrashort pulses promote nonlinear optical effects they might also give rise to nonlinear interactions with the devices under test that possibly manipulate the measurement outcome. In this paper, we present a comprehensive theoretical and experimental study of the nonlinearities affecting short circuit current (I{sub SC}) measurements of silicon (Si) solar cells. We derive a set of coupled differential equations describing the radiation-device interaction and discuss the nonlinearities incorporated in those. By a semi-analytical approach introducing a quasi-steady-state approximation and integrating a Green's function we solve the system of equations and obtain simulated I{sub SC} values. We validate the theoretical model by I{sub SC} ratios obtained from a double ring resonator setup capable for reproducible generation of various ultrashort pulse trains. Finally, we apply the model to conduct the most prominent comparison of I{sub SC} generated by ultrashort pulses versus continuous illumination. We conclude by the important finding that the nonlinearities induced by ultrashort pulses are negligible for the most common I{sub SC} measurements. However, we also find that more specialized measurements (e.g., of concentrating PV or Si-multijunction devices as well as highly localized electrical characterizations) will be biased by two-photon-absorption distorting the I{sub SC} measurement.

  18. Rapid battery depletion and loss of therapy due to a short circuit in bipolar DBS for essential tremor.

    Science.gov (United States)

    Allert, Niels; Barbe, Michael Thomas; Timmermann, Lars; Coenen, Volker Arnd

    2017-05-01

    Technical dysfunctions have been reported reducing efficacy of deep brain stimulation (DBS). Here, we report on an essential-tremor patient in whom a short circuit in bipolar DBS resulted not only in unilateral loss of therapy but also in high current flow and thereby rapid decline of the impulse-generator battery voltage from 2.83 V a week before the event to 2.54 V, indicating the need for an impulse-generator replacement. Immediate re-programming restored therapeutic efficacy. Moreover, the reduction in current flow allowed the battery voltage to recover without immediate surgical intervention to 2.81 V a week later.

  19. Inverted Fuel Cell: Room-Temperature Hydrogen Separation from an Exhaust Gas by Using a Commercial Short-Circuited PEM Fuel Cell without Applying any Electrical Voltage.

    Science.gov (United States)

    Friebe, Sebastian; Geppert, Benjamin; Caro, Jürgen

    2015-06-26

    A short-circuited PEM fuel cell with a Nafion membrane has been evaluated in the room-temperature separation of hydrogen from exhaust gas streams. The separated hydrogen can be recovered or consumed in an in situ olefin hydrogenation when the fuel cell is operated as catalytic membrane reactor. Without applying an outer electrical voltage, there is a continuous hydrogen flux from the higher to the lower hydrogen partial pressure side through the Nafion membrane. On the feed side of the Nafion membrane, hydrogen is catalytically split into protons and electrons by the Pt/C electrocatalyst. The protons diffuse through the Nafion membrane, the electrons follow the short-circuit between the two brass current collectors. On the cathode side, protons and electrons recombine, and hydrogen is released. © 2015 WILEY-VCH Verlag GmbH & Co. KGaA, Weinheim.

  20. The effect of recombination under short-circuit conditions on the determination of charge transport properties in nanostructured photoelectrodes.

    Science.gov (United States)

    Villanueva-Cab, J; Anta, J A; Oskam, G

    2016-01-28

    We report on the commonly unaccounted for process of recombination under short-circuit conditions in nanostructured photoelectrodes with special attention to the charge collection efficiency. It is observed that when recombination under short circuit conditions is significant, small perturbation methods overestimate the charge-collection efficiency, which is related to the inaccurate determination of the electron diffusion coefficient and diffusion length.

  1. Approaching Repetitive Short Circuit Tests on MW-Scale Power Modules by means of an Automatic Testing Setup

    DEFF Research Database (Denmark)

    Reigosa, Paula Diaz; Wang, Huai; Iannuzzo, Francesco

    2016-01-01

    An automatic testing system to perform repetitive short-circuit tests on megawatt-scale IGBT power modules is pre-sented and described in this paper, pointing out the advantages and features of such testing approach. The developed system is based on a non-destructive short-circuit tester, which has...

  2. Functional Complementation Studies Reveal Different Interaction Partners of Escherichia coli IscS and Human NFS1.

    Science.gov (United States)

    Bühning, Martin; Friemel, Martin; Leimkühler, Silke

    2017-08-29

    The trafficking and delivery of sulfur to cofactors and nucleosides is a highly regulated and conserved process among all organisms. All sulfur transfer pathways generally have an l-cysteine desulfurase as an initial sulfur-mobilizing enzyme in common, which serves as a sulfur donor for the biosynthesis of sulfur-containing biomolecules like iron-sulfur (Fe-S) clusters, thiamine, biotin, lipoic acid, the molybdenum cofactor (Moco), and thiolated nucleosides in tRNA. The human l-cysteine desulfurase NFS1 and the Escherichia coli homologue IscS share a level of amino acid sequence identity of ∼60%. While E. coli IscS has a versatile role in the cell and was shown to have numerous interaction partners, NFS1 is mainly localized in mitochondria with a crucial role in the biosynthesis of Fe-S clusters. Additionally, NFS1 is also located in smaller amounts in the cytosol with a role in Moco biosynthesis and mcm 5 s 2 U34 thio modifications of nucleosides in tRNA. NFS1 and IscS were conclusively shown to have different interaction partners in their respective organisms. Here, we used functional complementation studies of an E. coli iscS deletion strain with human NFS1 to dissect their conserved roles in the transfer of sulfur to a specific target protein. Our results show that human NFS1 and E. coli IscS share conserved binding sites for proteins involved in Fe-S cluster assembly like IscU, but not with proteins for tRNA thio modifications or Moco biosynthesis. In addition, we show that human NFS1 was almost fully able to complement the role of IscS in Moco biosynthesis when its specific interaction partner protein MOCS3 from humans was also present.

  3. Comparison of short-circuit characteristics of trench gate and planar gate U-shaped channel SOI-LIGBTs

    Science.gov (United States)

    Zhang, Long; Zhu, Jing; Sun, Weifeng; Zhao, Minna; Huang, Xuequan; Chen, Jiajun; Shi, Longxing; Chen, Jian; Ding, Desheng

    2017-09-01

    Comparison of short-circuit (SC) characteristics of 500 V rated trench gate U-shaped channel (TGU) SOI-LIGBT and planar gate U-shaped channel (PGU) SOI-LIGBT is made for the first time in this paper. The on-state carrier profile of the TGU structure is reshaped by the dual trenches (a gate trench G1 and a hole barrier trench G2), which leads to a different conduction behavior from that of the PGU structure. The TGU structure exhibits a higher latchup immunity but a severer self-heating effect. At current density (JC) 640 A/cm2. Comparison of layouts and fabrication processes are also made between the two types of devices.

  4. Model-based evaluation of the short-circuited tripolar cuff configuration.

    Science.gov (United States)

    Andreasen, Lotte N S; Struijk, Johannes J

    2006-05-01

    Recordings of neural information for use as feedback in functional electrical stimulation are often contaminated with interfering signals from muscles and from stimulus pulses. The cuff electrode used for the neural recording can be optimized to improve the S/I ratio. In this work, we evaluate a model of both the nerve signal and the interfering signals recorded by a cuff, and subsequently use this model to study the signal to interference ratio of different cuff designs and to evaluate a recently introduced short-circuited tripolar cuff configuration. The results of the model showed good agreement with results from measurements in rabbits and confirmed the superior performance of the short-circuited tripolar configuration as compared with the traditionally used tripolar configuration.

  5. NREL/NASA Internal Short-Circuit Instigator in Lithium Ion Cells

    Energy Technology Data Exchange (ETDEWEB)

    Keyser, Matthew; Long, Dirk; Pesaran, Ahmad; Darcy, Eric; Shoesmith, Mark; McCarthy, Ben

    2015-10-11

    Lithium-ion cells provide the highest specific energy (>280 Wh/kg) and energy density (>600 Wh/L) rechargeable battery building block to date with the longest life. Electrode/electrolyte thermal instability and flammability of the electrolyte of Li-ion cells make them prone to catastrophic thermal runaway under some rare internal short circuit conditions. Despite extensive QC/QA, standardized industry safety testing, and over 18 years of manufacturing experience, major recalls have taken place and incidents still occur. Many safety incidents that take place in the field originate due to an internal short that was not detectable or predictable at the point of manufacture. The Internal Short-Circuit Instigator can be used to study types of separators, non-flammable electrolytes, electrolyte additives, fusible tabs, propagation studies, and gas generation within a cell.

  6. Short Circuit Ratio analysis of multi-infeed HVDC system with a VSC-HVDC link

    DEFF Research Database (Denmark)

    Liu, Yan; Chen, Zhe

    2011-01-01

    As an important indicator of system stability, Short Circuit Ratio (SCR) is commonly used in power system analysis. For systems include HVDC link connection, the Effective SCR (ESCR) is mostly applied to indicate the strength of HVDC infeed bus. The contribution of VSC-HVDC link to multi......-infeed HVDC system stability has been analyzed a lot but the study on ESCR of this kind of system is still insufficient. This paper presents a calculation method for ESCR of the hybrid multi infeed HVDC system based on a simple two-infeed HVDC system model. The equivalent circuit of this system under short...... circuit situation is firstly obtained based on the model. Then its Thevenin equivalent circuit is derived and system ESCR can be calculated. At last, simulation study verified that the calculated ESCR value under different cases can indicate the change of system stability....

  7. A new tessera into the interactome of the isc operon:A novel interaction between HscB and IscS

    Directory of Open Access Journals (Sweden)

    Annalisa Pastore

    2016-09-01

    Full Text Available Iron sulfur clusters are essential universal prosthetic groups which can be formed inorganically but, in biology, are bound to proteins and produced enzymatically. Most of the components of the machine that produces the clusters are conserved throughout evolution. In bacteria, they are encoded in the isc operon. Previous reports provide information on the role of specific components but a clear picture of how the whole machine works is still missing. We have carried out a study of the effects of the co-chaperone HscB from the model system E. coli. We document a previously undetected weak interaction between the chaperone HscB and the desulfurase IscS, one of the two main players of the machine. The binding site involves a region of HscB in the longer stem of the approximately L-shaped molecules, whereas the interacting surface of IscS overlaps with the surface previously involved in binding other proteins, such as ferredoxin and frataxin. Our findings provide an entirely new perspective to our comprehension of the role of HscB and propose this protein as a component of the IscS complex.

  8. An Empirical Model for Estimating the Probability of Electrical Short Circuits from Tin Whiskers. Part 2

    Science.gov (United States)

    Courey, Karim; Wright, Clara; Asfour, Shihab; Onar, Arzu; Bayliss, Jon; Ludwig, Larry

    2009-01-01

    In this experiment, an empirical model to quantify the probability of occurrence of an electrical short circuit from tin whiskers as a function of voltage was developed. This empirical model can be used to improve existing risk simulation models. FIB and TEM images of a tin whisker confirm the rare polycrystalline structure on one of the three whiskers studied. FIB cross-section of the card guides verified that the tin finish was bright tin.

  9. An Investigation of Short Circuits in All-solution Processed and All-organic Solar Cells

    OpenAIRE

    Johansson, Jim

    2015-01-01

    Organic solar cells have shown great promise of becoming a cheaper alternative to inorganic solar cells. Additionally, they can also be made semitransparent. To avoid using expensive indium tin oxide electrodes in organic solar cells the electrodes can be made from conductive polymer, poly(3,4-ethylenedioxythiophene):polystyrene sulfonate (PEDOT:PSS). However, these so-called PEDOT-PEDOT solar cells are prone to short-circuiting. The work behind this thesis thus aimed to find the cause of the...

  10. Modeling and Fault Diagnosis of Interturn Short Circuit for Five-Phase Permanent Magnet Synchronous Motor

    Directory of Open Access Journals (Sweden)

    Jian-wei Yang

    2015-01-01

    Full Text Available Taking advantage of the high reliability, multiphase permanent magnet synchronous motors (PMSMs, such as five-phase PMSM and six-phase PMSM, are widely used in fault-tolerant control applications. And one of the important fault-tolerant control problems is fault diagnosis. In most existing literatures, the fault diagnosis problem focuses on the three-phase PMSM. In this paper, compared to the most existing fault diagnosis approaches, a fault diagnosis method for Interturn short circuit (ITSC fault of five-phase PMSM based on the trust region algorithm is presented. This paper has two contributions. (1 Analyzing the physical parameters of the motor, such as resistances and inductances, a novel mathematic model for ITSC fault of five-phase PMSM is established. (2 Introducing an object function related to the Interturn short circuit ratio, the fault parameters identification problem is reformulated as the extreme seeking problem. A trust region algorithm based parameter estimation method is proposed for tracking the actual Interturn short circuit ratio. The simulation and experimental results have validated the effectiveness of the proposed parameter estimation method.

  11. Conditions of the existence of 'short circuit' effect for plasma in a conducting cylinder

    International Nuclear Information System (INIS)

    Zhilinskij, A.P.; Kuteev, B.V.

    1975-01-01

    It has been experimentally established that in a cylindrical container with conducting side and end walls, the phenomenon of short circuit (the Symon effect) is not always realized. The short circuiting of plane end and of side surfaces causes an acceleration of a plasma decay only during the initial stage in a comparatively short time. Characteristic lifetimes during the late stage remain unchanged in this case. In conditions of a stable plasma they correspond to classical values of the plasma decay constant at the ambipolar diffusion of charged particles along and across force lines of a magnetic field. A fundamental change in the nature of the diffusion and a decrease of the plasma lifetime almost by two orders are realized in an instrument in which an end conducting wall for plasma in created with a short cylinder at the end of a solenoid in a sharply nonuniform magnetic field. The data obtained testify to the fact that the short circuit effect takes place in conditions when on boundaries of plasma the possibility of simultaneous flowing of unipolar electron flows along and of ion flows across a magnetic field is assured. The results of the experiments are compared with a theory

  12. The InSAR Scientific Computing Environment (ISCE): A Python Framework for Earth Science

    Science.gov (United States)

    Rosen, P. A.; Gurrola, E. M.; Agram, P. S.; Sacco, G. F.; Lavalle, M.

    2015-12-01

    The InSAR Scientific Computing Environment (ISCE, funded by NASA ESTO) provides a modern computing framework for geodetic image processing of InSAR data from a diverse array of radar satellites and aircraft. ISCE is both a modular, flexible, and extensible framework for building software components and applications as well as a toolbox of applications for processing raw or focused InSAR and Polarimetric InSAR data. The ISCE framework contains object-oriented Python components layered to construct Python InSAR components that manage legacy Fortran/C InSAR programs. Components are independently configurable in a layered manner to provide maximum control. Polymorphism is used to define a workflow in terms of abstract facilities for each processing step that are realized by specific components at run-time. This enables a single workflow to work on either raw or focused data from all sensors. ISCE can serve as the core of a production center to process Level-0 radar data to Level-3 products, but is amenable to interactive processing approaches that allow scientists to experiment with data to explore new ways of doing science with InSAR data. The NASA-ISRO SAR (NISAR) Mission will deliver data of unprecedented quantity and quality, making possible global-scale studies in climate research, natural hazards, and Earth's ecosystems. ISCE is planned as the foundational element in processing NISAR data, enabling a new class of analyses that take greater advantage of the long time and large spatial scales of these new data. NISAR will be but one mission in a constellation of radar satellites in the future delivering such data. ISCE currently supports all publicly available strip map mode space-borne SAR data since ERS and is expected to include support for upcoming missions. ISCE has been incorporated into two prototype cloud-based systems that have demonstrated its elasticity in addressing larger data processing problems in a "production" context and its ability to be

  13. Cysteine desulfurase IscS2 plays a role in oxygen resistance in Clostridium difficile.

    Science.gov (United States)

    Giordano, Nicole; Hastie, Jessica L; Smith, Ashley D; Foss, Elissa D; Gutierrez-Munoz, Daniela F; Carlson, Paul E

    2018-06-04

    Clostridium difficile is an anaerobic, spore-forming bacterium capable of colonizing the gastrointestinal tract of humans following disruption of the normal microbiota, typically from antibiotic therapy for an unrelated infection. With approximately 500,000 confirmed infections leading to 29,000 deaths per year in the United States, C. difficile infection (CDI) is an urgent public health threat. We previously determined C. difficile survives in up to 3% oxygen. Low levels of oxygen are present in the intestinal tract with the higher concentrations being associated with the epithelial cell surface. Additionally, antibiotic treatment, the greatest risk factor for CDI, increases intestinal oxygen concentration. Therefore, we hypothesized that the C. difficile genome encodes mechanisms for survival during oxidative stress. Previous data have shown that cysteine desulfurases involved in iron-sulfur cluster assembly are involved in protecting bacteria from oxidative stress. In this study, deletion of a putative cysteine desulfurase ( Cd 630_12790/IscS2) involved in the iron sulfur cluster (Isc) system caused a severe growth defect in the presence of 2% oxygen. Additionally, this mutant delayed colonization in a conventional mouse model of CDI, and failed to colonize in a germ-free model, which has higher intestinal oxygen levels. These data imply an undefined role for this cysteine desulfurase in protecting C. difficile from low levels of oxygen in the gut. This is a work of the U.S. Government and is not subject to copyright protection in the United States. Foreign copyrights may apply.

  14. Correction: The effect of recombination under short-circuit conditions on the determination of charge transport properties in nanostructured photoelectrodes.

    Science.gov (United States)

    Villanueva-Cab, J; Anta, J A; Oskam, G

    2016-05-28

    Correction for 'The effect of recombination under short-circuit conditions on the determination of charge transport properties in nanostructured photoelectrodes' by J. Villanueva-Cab et al., Phys. Chem. Chem. Phys., 2016, 18, 2303-2308.

  15. Reducing the Risk of Damage to Power Transformers of 110 kV and Above Accompanying Internal Short Circuits

    Energy Technology Data Exchange (ETDEWEB)

    L’vova, M. M. [JSC “R& D Center at Federal Grid Company of the Unified Power System” (Russian Federation); L’vov, S. Yu. [Presselektro LLC (Russian Federation); Komarov, V. B. [IPCE RAS (Russian Federation); Lyut’ko, E. O. [JSC “R& D Center at Federal Grid Company of the Unified Power System” (Russian Federation); Vdoviko, V. P. [EMA Ltd. (Russian Federation); Demchenko, V. V. [JSC “Boguchanskaya HPP” (Russian Federation); Belyaev, S. G. [PKF Konif Ltd. (Russian Federation); Savel’ev, V. A. [Ivanovo State Power University (Russian Federation); L’vov, M. Yu., E-mail: timashova@nte-power.ru; L’vov, Yu. N. [JSC “R& D Center at Federal Grid Company of the Unified Power System” (Russian Federation)

    2015-03-15

    Methods of increasing the operating reliability of power transformers, autotransformers and shunting reactors in order to reduce the risk of damage, which accompany internal short circuits and equipment fires and explosions, are considered.

  16. A survey of SiC power MOSFETs short-circuit robustness and failure mode analysis

    DEFF Research Database (Denmark)

    Ceccarelli, L.; Reigosa, P. D.; Iannuzzo, F.

    2017-01-01

    The aim of this paper is to provide an extensive overview about the state-of-art commercially available SiC power MOSFET, focusing on their short-circuit ruggedness. A detailed literature investigation has been carried out, in order to collect and understand the latest research contribution within...... this topic and create a survey of the present scenario of SiC MOSFETs reliability evaluation and failure mode analysis, pointing out the evolution and improvements as well as the future challenges in this promising device technology....

  17. Short circuit detection in the winding and operation of superconducting magnets

    International Nuclear Information System (INIS)

    Walstrom, P.L.

    1982-01-01

    Three categories of shorts will be discussed: (1) shorts to the metallic bobbin or other structural elements, (2) shorts between turns caused by instrumentation wires that are deliberately connected to a turn at the end (e.g., voltage taps) and that short out to another turn but are not completely severed in the process, and (3) short circuits between turns caused by direct contact due to insulation failure by chips of metal bridging turns and by instrumentation wires that bridge turns but are severed in the process of shorting

  18. Experimental Study on Short Circuit Phenomena in Air Switch of Distribution Line due to Sparkover between Different Poles on Which One Surge Arrester of the Three Ones is Omitted

    Science.gov (United States)

    Sato, Tomoyuki; Uemura, Satoshi; Asakawa, Akira; Yokoyama, Shigeru; Honda, Hideki; Horikoshi, Kazuhiro

    In this study, we experimentally examined the possibility of the internal short circuit of an air switch due to the sparkover between different poles under the condition that no surge arrester exists in neighboring poles and one of three surge arresters is omitted at the pole with an air switch. Experiments at Shiobara Testing Yard and Akagi Testing Center of CRIEPI clarified the following. Fault current may flow via the grounding point of a pole with an air switch and that of the next pole on a different phase from grounded phase of the pole with an air switch. If the low-voltage wire, overhead ground wire or communication wire forms a short circuit between them, ultimately the air switch may burn out. Moreover Fault current continues even if the length of the short-circuit between different poles is increased. Although the increase of the short-circuit length results in the increase of wire impedance, the amount of increase is still small compared with source impedance.

  19. Transient stability of DFIG wind turbines at an external short-circuit fault

    DEFF Research Database (Denmark)

    Sun, Tao; Chen, Zhe; Blaabjerg, Frede

    2005-01-01

    The fast development of wind power generation brings new requirements for wind turbine integration into the network. After clearance of an external short-circuit fault, gridconnected wind turbines should restore their normal operation without power loss caused by disconnections. This article...... are described in detail. The transient process of grid-connected wind turbines with DFIGs at an external shortcircuit fault is analysed, and in critical post-fault situations a measure is proposed for the voltage recovery of DFIG wind turbines after fault clearance. Simulation results demonstrate...... that in uncritical post-fault situations the control schemes are able to restore the wind turbine's normal operation without disconnections.lt is also proved that the proposed measure is effective in re-establishing the voltage at the wind turbine terminal in critical post-fault situations....

  20. Avoiding short circuits from zinc metal dendrites in anode by backside-plating configuration

    Science.gov (United States)

    Higashi, Shougo; Lee, Seok Woo; Lee, Jang Soo; Takechi, Kensuke; Cui, Yi

    2016-01-01

    Portable power sources and grid-scale storage both require batteries combining high energy density and low cost. Zinc metal battery systems are attractive due to the low cost of zinc and its high charge-storage capacity. However, under repeated plating and stripping, zinc metal anodes undergo a well-known problem, zinc dendrite formation, causing internal shorting. Here we show a backside-plating configuration that enables long-term cycling of zinc metal batteries without shorting. We demonstrate 800 stable cycles of nickel–zinc batteries with good power rate (20 mA cm−2, 20 C rate for our anodes). Such a backside-plating method can be applied to not only zinc metal systems but also other metal-based electrodes suffering from internal short circuits. PMID:27263471

  1. Growth Mechanism Studies of ZnO Nanowires: Experimental Observations and Short-Circuit Diffusion Analysis.

    Science.gov (United States)

    Shih, Po-Hsun; Wu, Sheng Yun

    2017-07-21

    Plenty of studies have been performed to probe the diverse properties of ZnO nanowires, but only a few have focused on the physical properties of a single nanowire since analyzing the growth mechanism along a single nanowire is difficult. In this study, a single ZnO nanowire was synthesized using a Ti-assisted chemical vapor deposition (CVD) method to avoid the appearance of catalytic contamination. Two-dimensional energy dispersive spectroscopy (EDS) mapping with a diffusion model was used to obtain the diffusion length and the activation energy ratio. The ratio value is close to 0.3, revealing that the growth of ZnO nanowires was attributed to the short-circuit diffusion.

  2. Enhanced charging kinetics of porous electrodes: surface conduction as a short-circuit mechanism.

    Science.gov (United States)

    Mirzadeh, Mohammad; Gibou, Frederic; Squires, Todd M

    2014-08-29

    We use direct numerical simulations of the Poisson-Nernst-Planck equations to study the charging kinetics of porous electrodes and to evaluate the predictive capabilities of effective circuit models, both linear and nonlinear. The classic transmission line theory of de Levie holds for general electrode morphologies, but only at low applied potentials. Charging dynamics are slowed appreciably at high potentials, yet not as significantly as predicted by the nonlinear transmission line model of Biesheuvel and Bazant. We identify surface conduction as a mechanism which can effectively "short circuit" the high-resistance electrolyte in the bulk of the pores, thus accelerating the charging dynamics and boosting power densities. Notably, the boost in power density holds only for electrode morphologies with continuous conducting surfaces in the charging direction.

  3. Effect of Short-Circuit Pathways on Water Quality in Selected Confined Aquifers (Invited)

    Science.gov (United States)

    McMahon, P. B.

    2010-12-01

    Confined aquifers in the United States generally contain fewer anthropogenic contaminants than unconfined aquifers because confined aquifers often contain water recharged prior to substantial human development and redox conditions are more reducing, which favors degradation of common contaminants like nitrate and chlorinated solvents. Groundwater in a confined part of the High Plains aquifer near York, Nebraska had an adjusted radiocarbon age of about 2,000 years, and groundwater in a confined part of the Floridan aquifer near Tampa, Florida had apparent ages greater than 60 years on the basis of tritium measurements. Yet compounds introduced more recently into the environment (anthropogenic nitrate and volatile organic compounds) were detected in selected public-supply wells completed in both aquifers. Depth-dependent measurements of flow and chemistry in the pumping supply wells, groundwater age dating, numerical modeling of groundwater flow, and other monitoring data indicated that the confined aquifers sampled by the supply wells were connected to contaminated unconfined aquifers by short-circuit pathways. In the High Plains aquifer, the primary pathways appeared to be inactive irrigation wells screened in both the unconfined and confined aquifers. In the Floridan aquifer, the primary pathways were karst sinkholes and conduits. Heavy pumping in both confined systems exacerbated the problem by reducing the potentiometric surface and increasing groundwater velocities, thus enhancing downward gradients and reducing reaction times for processes like denitrification. From a broader perspective, several confined aquifers in the U.S. have experienced large declines in their potentiometric surfaces because of groundwater pumping and this could increase the potential for contamination in those aquifers, particularly where short-circuit pathways connect them to shallower, contaminated sources of water, such as was observed in York and Tampa.

  4. Implications of electronic short circuiting in plasma sprayed solid oxide fuel cells on electrode performance evaluation by electrochemical impedance spectroscopy

    Energy Technology Data Exchange (ETDEWEB)

    White, B.D. [Department of Mechanical Engineering, The University of British Columbia, 2054-6250 Applied Sciences Lane, Vancouver, British Columbia (Canada); Kesler, O. [Department of Mechanical and Industrial Engineering, University of Toronto, 5 King' s College Road, Toronto, Ontario (Canada)

    2008-02-15

    Electronic short circuiting of the electrolyte in a solid oxide fuel cell (SOFC) arising from flaws in the plasma spray fabrication process has been found to have a significant effect on the perceived performance of the electrodes, as evaluated by electrochemical impedance spectroscopy (EIS). The presence of a short circuit has been found to lead to the underestimation of the electrode polarization resistance (R{sub p}) and hence an overestimation of electrode performance. The effect is particularly noticeable when electrolyte resistance is relatively high, for example during low to intermediate temperature operation, leading to an obvious deviation from the expected Arrhenius-type temperature dependence of R{sub p}. A method is developed for determining the real electrode performance from measurements of various cell properties, and strategies for eliminating the occurrence of short circuiting in plasma sprayed cells are identified. (author)

  5. Implications of electronic short circuiting in plasma sprayed solid oxide fuel cells on electrode performance evaluation by electrochemical impedance spectroscopy

    Science.gov (United States)

    White, B. D.; Kesler, O.

    Electronic short circuiting of the electrolyte in a solid oxide fuel cell (SOFC) arising from flaws in the plasma spray fabrication process has been found to have a significant effect on the perceived performance of the electrodes, as evaluated by electrochemical impedance spectroscopy (EIS). The presence of a short circuit has been found to lead to the underestimation of the electrode polarization resistance (R p) and hence an overestimation of electrode performance. The effect is particularly noticeable when electrolyte resistance is relatively high, for example during low to intermediate temperature operation, leading to an obvious deviation from the expected Arrhenius-type temperature dependence of R p. A method is developed for determining the real electrode performance from measurements of various cell properties, and strategies for eliminating the occurrence of short circuiting in plasma sprayed cells are identified.

  6. Effects of Armature Winding Segmentation with Multiple Converters on the Short Circuit Torque of 10-MW Superconducting Wind Turbine Generators

    DEFF Research Database (Denmark)

    Liu, Dong; Polinder, Henk; Abrahamsen, Asger Bech

    2017-01-01

    Superconducting synchronous generators (SCSGs) are drawing more attention in large direct-drive wind turbine applications. Despite low weight and compactness, the short circuit torque of an SCSG may be too high for wind turbine constructions due to a large magnetic air gap of an SCSG. This paper...... aims at assessing the effects of armature winding segmentation on reducing the short circuit torque of 10-MW SCSGs. A concept of armature winding segmentation with multiple power electronic converters is presented. Four SCSG designs using different topologies are examined. Results show that armature...... winding segmentation effectively reduce the short circuit torque in all the four SCSG designs when one segment is shorted at the terminal....

  7. Increasing emitter efficiency in 3.3-kV enhanced trench IGBTs for higher short-circuit capability

    DEFF Research Database (Denmark)

    Reigosa, Paula Diaz; Iannuzzo, Francesco; Rahimo, Munaf

    2018-01-01

    In this paper, a 3.3-kV Enhanced Trench IGBT has been designed with a high emitter efficiency, for improving its short-circuit robustness. The carrier distribution profile has been shaped in a way that it is possible to increase the electric field at the surface of the IGBT, and thereby, counteract...... the Kirk Effect onset. This design approach is beneficial for mitigating high-frequency oscillations, typically observed in IGBTs under short-circuit conditions. The effectiveness of the proposed design rule is validated by means of mixed-mode device simulations. Then, two IGBTs have been fabricated...... with different emitter efficiencies and tested under short circuit, validating that the high-frequency oscillations can be mitigated, with higher emitter efficiency IGBT designs....

  8. Transient Analysis of Grid-Connected Wind Turbines with DFIG After an External Short-Circuit Fault

    DEFF Research Database (Denmark)

    Sun, Tao; Chen, Zhe; Blaabjerg, Frede

    2004-01-01

    The fast development of wind power generation brings new requirements for wind turbine integration to the network. After the clearance of an external short-circuit fault, the grid-connected wind turbine should restore its normal operation with minimized power losses. This paper concentrates...... on transient analysis of variable speed wind turbines with doubly fed induction generator (DFIG) after an external short-circuit fault. A simulation model of a MW-level variable speed wind turbine with DFIG developed in PSCAD/EMTDC is presented, and the control and protection schemes are described in detail....... After the clearance of an external short-circuit fault the control schemes manage to restore the wind turbine?s normal operation, and their performances are demonstrated by simulation results both during the fault and after the clearance of the fault....

  9. Influence of Metal Transfer Stability and Shielding Gas Composition on CO and CO2 Emissions during Short-circuiting MIG/MAG Welding

    Directory of Open Access Journals (Sweden)

    Valter Alves de Meneses

    Full Text Available Abstract: Several studies have demonstrated the influence of parameters and shielding gas on metal transfer stability or on the generation of fumes in MIG/MAG welding, but little or nothing has been discussed regarding the emission of toxic and asphyxiating gases, particularly as it pertains to parameterization of the process. The purpose of this study was to analyze and evaluate the effect of manufacturing aspects of welding processes (short-circuit metal transfer stability and shielding gas composition on the gas emission levels during MIG/MAG welding (occupational health and environmental aspects. Using mixtures of Argon with CO2 and O2 and maintaining the same average current and the same weld bead volume, short-circuit welding was performed with carbon steel welding wire in open (welder’s breathing zone and confined environments. The welding voltage was adjusted to gradually vary the transfer stability. It was found that the richer the composition of the shielding gas is in CO2, the more CO and CO2 are generated by the arc. However, unlike fume emission, voltage and transfer stability had no effect on the generation of these gases. It was also found that despite the large quantity of CO and CO2 emitted by the arc, especially when using pure CO2 shielding gas, there was no high level residual concentration of CO and CO2 in or near the worker’s breathing zone, even in confined work cells.

  10. Short-Circuit Fault Detection and Classification Using Empirical Wavelet Transform and Local Energy for Electric Transmission Line.

    Science.gov (United States)

    Huang, Nantian; Qi, Jiajin; Li, Fuqing; Yang, Dongfeng; Cai, Guowei; Huang, Guilin; Zheng, Jian; Li, Zhenxin

    2017-09-16

    In order to improve the classification accuracy of recognizing short-circuit faults in electric transmission lines, a novel detection and diagnosis method based on empirical wavelet transform (EWT) and local energy (LE) is proposed. First, EWT is used to deal with the original short-circuit fault signals from photoelectric voltage transformers, before the amplitude modulated-frequency modulated (AM-FM) mode with a compactly supported Fourier spectrum is extracted. Subsequently, the fault occurrence time is detected according to the modulus maxima of intrinsic mode function (IMF₂) from three-phase voltage signals processed by EWT. After this process, the feature vectors are constructed by calculating the LE of the fundamental frequency based on the three-phase voltage signals of one period after the fault occurred. Finally, the classifier based on support vector machine (SVM) which was constructed with the LE feature vectors is used to classify 10 types of short-circuit fault signals. Compared with complementary ensemble empirical mode decomposition with adaptive noise (CEEMDAN) and improved CEEMDAN methods, the new method using EWT has a better ability to present the frequency in time. The difference in the characteristics of the energy distribution in the time domain between different types of short-circuit faults can be presented by the feature vectors of LE. Together, simulation and real signals experiment demonstrate the validity and effectiveness of the new approach.

  11. Microscale failure mechanisms leading to internal short circuit in Li-ion batteries under complex loading scenarios

    NARCIS (Netherlands)

    Sahraei, E.; Bosco, E.; Dixon, B.; Lai, B.

    2016-01-01

    One of the least understood mechanisms of Li-ion batteries is the development of internal short circuits under mechanical loads. In this study, a micro mechanical model is developed and subjected to various loading scenarios to understand the sequence of failure in the multi-layer, multi-material

  12. Developing an Empirical Model for Estimating the Probability of Electrical Short Circuits from Tin Whiskers. Part 2

    Science.gov (United States)

    Courey, Karim J.; Asfour, Shihab S.; Onar, Arzu; Bayliss, Jon A.; Ludwig, Larry L.; Wright, Maria C.

    2009-01-01

    To comply with lead-free legislation, many manufacturers have converted from tin-lead to pure tin finishes of electronic components. However, pure tin finishes have a greater propensity to grow tin whiskers than tin-lead finishes. Since tin whiskers present an electrical short circuit hazard in electronic components, simulations have been developed to quantify the risk of said short circuits occurring. Existing risk simulations make the assumption that when a free tin whisker has bridged two adjacent exposed electrical conductors, the result is an electrical short circuit. This conservative assumption is made because shorting is a random event that had an unknown probability associated with it. Note however that due to contact resistance electrical shorts may not occur at lower voltage levels. In our first article we developed an empirical probability model for tin whisker shorting. In this paper, we develop a more comprehensive empirical model using a refined experiment with a larger sample size, in which we studied the effect of varying voltage on the breakdown of the contact resistance which leads to a short circuit. From the resulting data we estimated the probability distribution of an electrical short, as a function of voltage. In addition, the unexpected polycrystalline structure seen in the focused ion beam (FIB) cross section in the first experiment was confirmed in this experiment using transmission electron microscopy (TEM). The FIB was also used to cross section two card guides to facilitate the measurement of the grain size of each card guide's tin plating to determine its finish.

  13. Fast and Accurate Icepak-PSpice Co-Simulation of IGBTs under Short-Circuit with an Advanced PSpice Model

    DEFF Research Database (Denmark)

    Wu, Rui; Iannuzzo, Francesco; Wang, Huai

    2014-01-01

    A basic problem in the IGBT short-circuit failure mechanism study is to obtain realistic temperature distribution inside the chip, which demands accurate electrical simulation to obtain power loss distribution as well as detailed IGBT geometry and material information. This paper describes an unp...

  14. Failure Analysis of Short-Circuited Lithium-Ion Battery with Nickel-Manganese-Cobalt/Graphite Electrode.

    Science.gov (United States)

    Lee, Seung-Mi; Kim, Jea-Yeon; Byeon, Jai-Won

    2018-09-01

    Accidental failures and explosions of lithium-ion batteries have been reported in recent years. To determine the root causes and mechanisms of these failures from the perspective of material degradation, failure analysis was conducted for an intentionally shorted lithium-ion battery. The battery was subjected to electrical overcharging and mechanical pressing to simulate internal short-circuiting. After in situ measurement of the temperature increase during the short-circuiting of the electrodes, the disassembled battery components (i.e., the anode, cathode, and separator) were analyzed by scanning electron microscopy and energy-dispersive X-ray spectroscopy. Regardless of the simulated short-circuit method (mechanical or electrical), damage was observed in the shorted batteries. Numerous small cracks and chemical reaction products were observed on the electrode surface, along with pore shielding on the separator. The event of short-circuiting increased the surface temperature of the battery to approximately 90 °C, which prompted the deterioration and decomposition of the electrolyte, thus affecting the overall battery performance; this was attributed to the decomposition of the lithium salt at 60 °C. The gas generation due to the breakdown of the electrolyte causes pressure accumulation inside the cell; therefore, the electrolyte leaks.

  15. EQUATIONS OF ELECTRIC MOTOR POWER SUPPLY UNIT DISSYMMETRY UNDER PHASE-TO-PHASE SHORT-CIRCUIT FAULT

    Directory of Open Access Journals (Sweden)

    V.Y. Tchaban

    2013-10-01

    Full Text Available In the paper, a formula is introduced to calculate electric motor supply unit voltage under feeding by a common transformer in the condition of a phase-to-phase short-circuit. The formula is used in every time step of electromechanical state equations integration.

  16. An iterative approach for symmetrical and asymmetrical Short-circuit calculations with converter-based connected renewable energy sources

    DEFF Research Database (Denmark)

    Göksu, Ömer; Teodorescu, Remus; Bak-Jensen, Birgitte

    2012-01-01

    As more renewable energy sources, especially more wind turbines are installed in the power system, analysis of the power system with the renewable energy sources becomes more important. Short-circuit calculation is a well known fault analysis method which is widely used for early stage analysis...

  17. Official (ISC)2 guide to the CISSP exam

    CERN Document Server

    Hansche, Susan; Hare, Chris

    2003-01-01

    Candidates for the CISSP exam can now go directly to the source for study materials that are indispensable in achieving certification. The Official (ISC)2 Guide to the CISSP Exam is derived from the actual CBK review course created and administered by the non-profit security consortium (ISC)2. In addition to being an invaluable study guide, this book is detailed enough to serve as an authoritative information security resource. Both of the guide's co-authors are CISSPs, and the entire text has been reviewed and approved by Hal Tipton, Co-Founder and Past President of ISSA and Co-Founder of (I

  18. Official (ISC)2 guide to the CISSP CBK

    CERN Document Server

    Gordon, Adam

    2015-01-01

    As a result of a rigorous, methodical process that (ISC)² follows to routinely update its credential exams, it has announced that enhancements will be made to both the Certified Information Systems Security Professional (CISSP) credential, beginning April 15, 2015. (ISC)² conducts this process on a regular basis to ensure that the examinations and subsequent training and continuing professional education requirements encompass the topic areas relevant to the roles and responsibilities of today's practicing information security professionals.Refreshed technical content has been added to the off

  19. Detection of Internal Short Circuit in Lithium Ion Battery Using Model-Based Switching Model Method

    Directory of Open Access Journals (Sweden)

    Minhwan Seo

    2017-01-01

    Full Text Available Early detection of an internal short circuit (ISCr in a Li-ion battery can prevent it from undergoing thermal runaway, and thereby ensure battery safety. In this paper, a model-based switching model method (SMM is proposed to detect the ISCr in the Li-ion battery. The SMM updates the model of the Li-ion battery with ISCr to improve the accuracy of ISCr resistance R I S C f estimates. The open circuit voltage (OCV and the state of charge (SOC are estimated by applying the equivalent circuit model, and by using the recursive least squares algorithm and the relation between OCV and SOC. As a fault index, the R I S C f is estimated from the estimated OCVs and SOCs to detect the ISCr, and used to update the model; this process yields accurate estimates of OCV and R I S C f . Then the next R I S C f is estimated and used to update the model iteratively. Simulation data from a MATLAB/Simulink model and experimental data verify that this algorithm shows high accuracy of R I S C f estimates to detect the ISCr, thereby helping the battery management system to fulfill early detection of the ISCr.

  20. Investigation of Permanent Magnet Demagnetization in Synchronous Machines during Multiple Short-Circuit Fault Conditions

    Directory of Open Access Journals (Sweden)

    Stefan Sjökvist

    2017-10-01

    Full Text Available Faults in electrical machines can vary in severity and affect different parts of the machine. This study focuses on various kinds of short-circuits on the terminal side of a generic 20 kW surface mounted permanent magnet synchronous generator and how successive faults affect the performance of the machine. The study was conducted with the commercially available finite element method software COMSOL Multiphysics ® , and two time-dependent models for demagnetization of permanent magnets were compared, one using only internal models and the other using a proprietary external function. The study is simulation based and the two models were compared to a previously experimentally verified stationary model. Results showed that the power output decreased by more than 30% after five successive faults. In addition, the no-load voltage had become unsymmetrical, which was explained by the uneven demagnetization of the permanent magnets. The permanent magnet with the lowest reduction in average remanence was decreased by 0.8%, while the highest average reduction was 23.8% in another permanent magnet. The internal simulation model was about four times faster than the external model, but slightly overestimated the demagnetization.

  1. Investigation and Classification of Short-Circuit Failure Modes Based on Three-Dimensional Safe Operating Area for High-Power IGBT Modules

    DEFF Research Database (Denmark)

    Chen, Yuxiang; Li, Wuhua; Iannuzzo, Francesco

    2018-01-01

    is implemented to motivate advanced contributions in future dependence research of device short-circuit failure modes on temperature. Consequently, a comprehensive and thoughtful review of where the development of short-circuit failure mode research works of IGBT stands and is heading is provided....

  2. Role of IscX in Iron-Sulfur Cluster Biogenesis in Escherichia coli

    Energy Technology Data Exchange (ETDEWEB)

    Kim, Jin Hae; Bothe, Jameson R.; Frederick, Ronnie O.; Holder, Johneisa C.; Markley, John L. [UW

    2014-08-20

    The Escherichia coli isc operon encodes key proteins involved in the biosynthesis of iron–sulfur (Fe–S) clusters. Whereas extensive studies of most ISC proteins have revealed their functional properties, the role of IscX (also dubbed YfhJ), a small acidic protein encoded by the last gene in the operon, has remained in question. Previous studies showed that IscX binds iron ions and interacts with the cysteine desulfurase (IscS) and the scaffold protein for cluster assembly (IscU), and it has been proposed that IscX functions either as an iron supplier or a regulator of Fe–S cluster biogenesis. We have used a combination of NMR spectroscopy, small-angle X-ray scattering (SAXS), chemical cross-linking, and enzymatic assays to enlarge our understanding of the interactions of IscX with iron ions, IscU, and IscS. We used chemical shift perturbation to identify the binding interfaces of IscX and IscU in their complex. NMR studies showed that Fe2+ from added ferrous ammonium sulfate binds IscX much more avidly than does Fe3+ from added ferric ammonium citrate and that Fe2+ strengthens the interaction between IscX and IscU. We found that the addition of IscX to the IscU–IscS binary complex led to the formation of a ternary complex with reduced cysteine desulfurase activity, and we determined a low-resolution model for that complex from a combination of NMR and SAXS data. We postulate that the inhibition of cysteine desulfurase activity by IscX serves to reduce unproductive conversion of cysteine to alanine. By incorporating these new findings with results from prior studies, we propose a detailed mechanism for Fe–S cluster assembly in which IscX serves both as a donor of Fe2+ and as a regulator of cysteine desulfurase activity.

  3. What Industry Is Saying About the Battery ISC Device (Text Version) |

    Science.gov (United States)

    version of the video What Industry Is Saying About the Battery ISC Device. Bring Up NREL Logo with Music Transportation Research | NREL What Industry Is Saying About the Battery ISC Device (Text Version) What Industry Is Saying About the Battery ISC Device (Text Version) The following is the text

  4. Official (ISC)2 guide to the ISSMP CBK

    CERN Document Server

    Tipton, Harold F

    2007-01-01

    As the recognized leader in the field of information security education and certification, the (ISC)2(R) promotes the development of information security professionals around the world. The Certified Information Systems Security Professional-Information Systems Security Management Professional (CISSP-ISSMP(R)) examination assesses individuals' understanding of security management practices. Obtaining certification validates your ability to create and implement effective information security management programs that meet the security needs of today's organizations. Preparing professionals for c

  5. Evidence of Gate Voltage Oscillations during Short Circuit of Commercial 1.7 kV/ 1 kA IGBT Power Modules

    DEFF Research Database (Denmark)

    Reigosa, Paula Diaz; Wu, Rui; Iannuzzo, Francesco

    2015-01-01

    This paper analyzes the evidence of critical gate voltage oscillations in 1.7 kV/1 kA Insulated-Gate Bipolar Transistor (IGBT) power modules under short circuit conditions. A 6 kA/1.1 kV Non-Destructive Test (NDT) set up for repeatable short circuit tests has been built with a 40 nH stray inducta...

  6. A geometric approach for fault detection and isolation of stator short circuit failure in a single asynchronous machine

    KAUST Repository

    Khelouat, Samir

    2012-06-01

    This paper deals with the problem of detection and isolation of stator short-circuit failure in a single asynchronous machine using a geometric approach. After recalling the basis of the geometric approach for fault detection and isolation in nonlinear systems, we will study some structural properties which are fault detectability and isolation fault filter existence. We will then design filters for residual generation. We will consider two approaches: a two-filters structure and a single filter structure, both aiming at generating residuals which are sensitive to one fault and insensitive to the other faults. Some numerical tests will be presented to illustrate the efficiency of the method.

  7. Matlab/Simulink Implementation of Wave-based Models for Microstrip Structures utilizing Short-circuited and Opened Stubs

    Directory of Open Access Journals (Sweden)

    Biljana P. Stošić

    2011-12-01

    Full Text Available This paper describes modeling and analyzing procedures for microstrip filters based on use of one-dimensional wave digital approach. Different filter structures are observed. One filter is based on quarter-wave length short-circuited stubs and connecting transmission lines. The other one is based on cross-junction opened stubs. Frequency responses are obtained by direct analysis of the block-based networks formed in Simulink toolbox of MATLAB environment. This wave-based method allows an accurate and efficient analysis of different microwave structures.

  8. Fast-responding short circuit protection system with self-reset for use in circuit supplied by DC power

    Science.gov (United States)

    Burns, Bradley M. (Inventor); Blalock, Norman N. (Inventor)

    2011-01-01

    A short circuit protection system includes an inductor, a switch, a voltage sensing circuit, and a controller. The switch and inductor are electrically coupled to be in series with one another. A voltage sensing circuit is coupled across the switch and the inductor. A controller, coupled to the voltage sensing circuit and the switch, opens the switch when a voltage at the output terminal of the inductor transitions from above a threshold voltage to below the threshold voltage. The controller closes the switch when the voltage at the output terminal of the inductor transitions from below the threshold voltage to above the threshold voltage.

  9. Spectroscopic and functional characterization of iron-sulfur cluster-bound forms of Azotobacter vinelandii (Nif)IscA.

    Science.gov (United States)

    Mapolelo, Daphne T; Zhang, Bo; Naik, Sunil G; Huynh, Boi Hanh; Johnson, Michael K

    2012-10-16

    The mechanism of [4Fe-4S] cluster assembly on A-type Fe-S cluster assembly proteins, in general, and the specific role of (Nif)IscA in the maturation of nitrogen fixation proteins are currently unknown. To address these questions, in vitro spectroscopic studies (UV-visible absorption/CD, resonance Raman and Mössbauer) have been used to investigate the mechanism of [4Fe-4S] cluster assembly on Azotobacter vinelandii(Nif)IscA, and the ability of (Nif)IscA to accept clusters from NifU and to donate clusters to the apo form of the nitrogenase Fe-protein. The results show that (Nif)IscA can rapidly and reversibly cycle between forms containing one [2Fe-2S](2+) and one [4Fe-4S](2+) cluster per homodimer via DTT-induced two-electron reductive coupling of two [2Fe-2S](2+) clusters and O(2)-induced [4Fe-4S](2+) oxidative cleavage. This unique type of cluster interconversion in response to cellular redox status and oxygen levels is likely to be important for the specific role of A-type proteins in the maturation of [4Fe-4S] cluster-containing proteins under aerobic growth or oxidative stress conditions. Only the [4Fe-4S](2+)-(Nif)IscA was competent for rapid activation of apo-nitrogenase Fe protein under anaerobic conditions. Apo-(Nif)IscA was shown to accept clusters from [4Fe-4S] cluster-bound NifU via rapid intact cluster transfer, indicating a potential role as a cluster carrier for delivery of clusters assembled on NifU. Overall the results support the proposal that A-type proteins can function as carrier proteins for clusters assembled on U-type proteins and suggest that they are likely to supply [2Fe-2S] clusters rather than [4Fe-4S] for the maturation of [4Fe-4S] cluster-containing proteins under aerobic or oxidative stress growth conditions.

  10. Official (ISC)2 guide to the CISSP CBK

    CERN Document Server

    Hernandez, CISSP, Steven

    2009-01-01

    With each new advance in connectivity and convenience comes a new wave of threats to privacy and security capable of destroying a company's reputation, violating a consumer's privacy, compromising intellectual property, and in some cases endangering personal safety. This is why it is essential for information security professionals to stay up to date with the latest advances in technology and the new security threats they create. Recognized as one of the best tools available for the information security professional and especially for candidates studying for the (ISC)2 CISSP examination, the O

  11. Official (ISC)2 guide to the CSSLP CBK

    CERN Document Server

    Paul, Mano

    2013-01-01

    The text allows readers to learn about software security from a renowned security practitioner who is the appointed software assurance advisor for (ISC)2. Complete with numerous illustrations, it makes complex security concepts easy to understand and implement. In addition to being a valuable resource for those studying for the CSSLP examination, this book is also an indispensable software security reference for those already part of the certified elite. A robust and comprehensive appendix makes this book a time-saving resource for anyone involved in secure software development.

  12. The Inertial Stellar Compass (ISC): A Multifunction, Low Power, Attitude Determination Technology Breakthrough

    Science.gov (United States)

    Bauer, Frank H. (Technical Monitor); Dennehy, Neil; Gambino, Joel; Maynard, Andrew; Brady, T.; Buckley, S.; Zinchuk, J.

    2003-01-01

    The Inertial Stellar Compass (ISC) is a miniature, low power, stellar inertial attitude determination system with an accuracy of better than 0.1 degree (1 sigma) in three axes. The ISC consumes only 3.5 Watts of power and is contained in a 2.5 kg package. With its embedded on-board processor, the ISC provides attitude quaternion information and has Lost-in-Space (LIS) initialization capability. The attitude accuracy and LIS capability are provided by combining a wide field of view Active Pixel Sensor (APS) star camera and Micro- ElectroMechanical System (MEMS) inertial sensor information in an integrated sensor system. The performance and small form factor make the ISC a useful sensor for a wide range of missions. In particular, the ISC represents an enabling, fully integrated, micro-satellite attitude determination system. Other applications include using the ISC as a single sensor solution for attitude determination on medium performance spacecraft and as a bolt on independent safe-hold sensor or coarse acquisition sensor for many other spacecraft. NASA's New Millennium Program (NMP) has selected the ISC technology for a Space Technology 6 (ST6) flight validation experiment scheduled for 2004. NMP missions, such a s ST6, are intended to validate advanced technologies that have not flown in space in order to reduce the risk associated with their infusion into future NASA missions. This paper describes the design, operation, and performance of the ISC and outlines the technology validation plan. A number of mission applications for the ISC technology are highlighted, both for the baseline ST6 ISC configuration and more ambitious applications where ISC hardware and software modifications would be required. These applications demonstrate the wide range of Space and Earth Science missions that would benefit from infusion of the ISC technology.

  13. Effect of short circuited DC link capacitor of an AC–DC–AC inverter on the performance of induction motor

    Directory of Open Access Journals (Sweden)

    Hadeed Ahmed Sher

    2016-07-01

    Full Text Available Induction motors are widely used in industrial power plants due to their robustness, reliability and high performance under variable operating conditions in the electrical power system. Modern industrial progress is dependent on these ruggedly constructed induction motors. Almost every sophisticated process of the industry is based on induction motors. Most of these motors are controlled by means of inverters that change the line frequency. The change in parameters of inverter makes it possible to control the motor according to the design requirements. The reliability of inverter based motor control is an important issue for industrial applications and therefore, it becomes very vital for design engineers to have comprehensive analysis of the inverter fed induction machine. This paper investigates one of the faults that may occur on the DC link of an inverter fed induction motor. The effect of the capacitor short circuit is presented in this paper. It also deals with the effects of short circuited capacitor on freewheeling diode. DC link capacitors are well designed and even the probability of capacitor failure is high, it is always a rare case if they puncture, however this analysis will add to the reliability of the induction machine under variable operating condition.

  14. Detection of inter-turn short-circuit at start-up of induction machine based on torque analysis

    Directory of Open Access Journals (Sweden)

    Pietrowski Wojciech

    2017-12-01

    Full Text Available Recently, interest in new diagnostics methods in a field of induction machines was observed. Research presented in the paper shows the diagnostics of induction machine based on torque pulsation, under inter-turn short-circuit, during start-up of a machine. In the paper three numerical techniques were used: finite element analysis, signal analysis and artificial neural networks (ANN. The elaborated numerical model of faulty machine consists of field, circuit and motion equations. Voltage excited supply allowed to determine the torque waveform during start-up. The inter-turn short-circuit was treated as a galvanic connection between two points of the stator winding. The waveforms were calculated for different amounts of shorted-turns from 0 to 55. Due to the non-stationary waveforms a wavelet packet decomposition was used to perform an analysis of the torque. The obtained results of analysis were used as input vector for ANN. The response of the neural network was the number of shorted-turns in the stator winding. Special attention was paid to compare response of general regression neural network (GRNN and multi-layer perceptron neural network (MLP. Based on the results of the research, the efficiency of the developed algorithm can be inferred.

  15. Robust Diagnosis Method Based on Parameter Estimation for an Interturn Short-Circuit Fault in Multipole PMSM under High-Speed Operation.

    Science.gov (United States)

    Lee, Jewon; Moon, Seokbae; Jeong, Hyeyun; Kim, Sang Woo

    2015-11-20

    This paper proposes a diagnosis method for a multipole permanent magnet synchronous motor (PMSM) under an interturn short circuit fault. Previous works in this area have suffered from the uncertainties of the PMSM parameters, which can lead to misdiagnosis. The proposed method estimates the q-axis inductance (Lq) of the faulty PMSM to solve this problem. The proposed method also estimates the faulty phase and the value of G, which serves as an index of the severity of the fault. The q-axis current is used to estimate the faulty phase, the values of G and Lq. For this reason, two open-loop observers and an optimization method based on a particle-swarm are implemented. The q-axis current of a healthy PMSM is estimated by the open-loop observer with the parameters of a healthy PMSM. The Lq estimation significantly compensates for the estimation errors in high-speed operation. The experimental results demonstrate that the proposed method can estimate the faulty phase, G, and Lq besides exhibiting robustness against parameter uncertainties.

  16. Extra high speed modified Lundell alternator parameters and open/short-circuit characteristics from global 3D-FE magnetic field solutions

    Science.gov (United States)

    Wang, R.; Demerdash, N. A.

    1992-06-01

    The combined magnetic vector potential - magnetic scalar potential method of computation of 3D magnetic fields by finite elements, introduced in a companion paper, is used for global 3D field analysis and machine performance computations under open-circuit and short-circuit conditions for an example 14.3 kVA modified Lundell alternator, whose magnetic field is of intrinsic 3D nature. The computed voltages and currents under these machine test conditions were verified and found to be in very good agreement with corresponding test data. Results of use of this modelling and computation method in the study of a design alteration example, in which the stator stack length of the example alternator is stretched in order to increase voltage and volt-ampere rating, are given here. These results demonstrate the inadequacy of conventional 2D-based design concepts and the imperative of use of this type of 3D magnetic field modelling in the design and investigation of such machines.

  17. Extra high speed modified Lundell alternator parameters and open/short-circuit characteristics from global 3D-FE magnetic field solutions

    Science.gov (United States)

    Wang, R.; Demerdash, N. A.

    1992-01-01

    The combined magnetic vector potential - magnetic scalar potential method of computation of 3D magnetic fields by finite elements, introduced in a companion paper, is used for global 3D field analysis and machine performance computations under open-circuit and short-circuit conditions for an example 14.3 kVA modified Lundell alternator, whose magnetic field is of intrinsic 3D nature. The computed voltages and currents under these machine test conditions were verified and found to be in very good agreement with corresponding test data. Results of use of this modelling and computation method in the study of a design alteration example, in which the stator stack length of the example alternator is stretched in order to increase voltage and volt-ampere rating, are given here. These results demonstrate the inadequacy of conventional 2D-based design concepts and the imperative of use of this type of 3D magnetic field modelling in the design and investigation of such machines.

  18. Diagnosis of Short-Circuit Fault in Large-Scale Permanent-Magnet Wind Power Generator Based on CMAC

    Directory of Open Access Journals (Sweden)

    Chin-Tsung Hsieh

    2013-01-01

    Full Text Available This study proposes a method based on the cerebellar model arithmetic controller (CMAC for fault diagnosis of large-scale permanent-magnet wind power generators and compares the results with Error Back Propagation (EBP. The diagnosis is based on the short-circuit faults in permanent-magnet wind power generators, magnetic field change, and temperature change. Since CMAC is characterized by inductive ability, associative ability, quick response, and similar input signals exciting similar memories, it has an excellent effect as an intelligent fault diagnosis implement. The experimental results suggest that faults can be diagnosed effectively after only training CMAC 10 times. In comparison to training 151 times for EBP, CMAC is better than EBP in terms of training speed.

  19. Model-based fault diagnosis approach on external short circuit of lithium-ion battery used in electric vehicles

    International Nuclear Information System (INIS)

    Chen, Zeyu; Xiong, Rui; Tian, Jinpeng; Shang, Xiong; Lu, Jiahuan

    2016-01-01

    Highlights: • The characteristics of ESC fault of lithium-ion battery are investigated experimentally. • The proposed method to simulate the electrical behavior of ESC fault is viable. • Ten parameters in the presented fault model were optimized using a DPSO algorithm. • A two-layer model-based fault diagnosis approach for battery ESC is proposed. • The effective and robustness of the proposed algorithm has been evaluated. - Abstract: This study investigates the external short circuit (ESC) fault characteristics of lithium-ion battery experimentally. An experiment platform is established and the ESC tests are implemented on ten 18650-type lithium cells considering different state-of-charges (SOCs). Based on the experiment results, several efforts have been made. (1) The ESC process can be divided into two periods and the electrical and thermal behaviors within these two periods are analyzed. (2) A modified first-order RC model is employed to simulate the electrical behavior of the lithium cell in the ESC fault process. The model parameters are re-identified by a dynamic-neighborhood particle swarm optimization algorithm. (3) A two-layer model-based ESC fault diagnosis algorithm is proposed. The first layer conducts preliminary fault detection and the second layer gives a precise model-based diagnosis. Four new cells are short-circuited to evaluate the proposed algorithm. It shows that the ESC fault can be diagnosed within 5 s, the error between the model and measured data is less than 0.36 V. The effectiveness of the fault diagnosis algorithm is not sensitive to the precision of battery SOC. The proposed algorithm can still make the correct diagnosis even if there is 10% error in SOC estimation.

  20. Correlation between photoconductivity in nanocrystalline titania and short circuit current transients in MEH-PPV/titania solar cells

    International Nuclear Information System (INIS)

    Xie, Z B; Henry, B M; Kirov, K R; Barkhouse, D A R; Burlakov, V M; Smith, H E; Grovenor, C R M; Assender, H E; Briggs, G A D; Kano, M; Tsukahara, Y

    2007-01-01

    We report the first experimental observation of a direct relationship between electron transport in different nanocrystalline TiO 2 thin films and the photovoltaic performance of TiO 2 /MEH-PPV composite solar cells made using these same TiO 2 films. We show that the transient behaviour in the composite solar cells under illumination can be explained by the transient photoconductivity performance of the TiO 2 layer

  1. Functionalized carbon nanotube doping of P3HT:PCBM photovoltaic devices for enhancing short circuit current and efficiency

    Directory of Open Access Journals (Sweden)

    Rohit Bhatia

    2017-03-01

    Full Text Available We have successfully functionalized multiwalled carbon nanotubes (MWCNTs using nitrene approach employing the two aryl azides as a precursor for nitrene generation. The dispersion of functionalized MWCNTs has been enhanced in various organic solvents. These functionalized MWCNTs have been successfully doped in various concentrations in the bulk heterojunction (BHJ organic photovoltaic (OPV cells with a poly (3-hexyl thiophene (P3HT and [6,6]-phenyl-C61-butyric acid methyl ester (PCBM photoactive blended layer. The incorporation of MWCNTs with aryl functional groups, in active the layer, results in enhanced performance with respect to a reference cell. The maximum power conversion efficiency of 1.86% is achieved with adduct I while in the case of adduct II it gets double to 2.0% in comparison with a reference cell. This improvement in the device performance is attributed to enhanced exciton dissociation and improved charge transport properties due to the formation of a nanotube percolation network in the photoactive composite layer.

  2. Modelling the temperature induced degradation kinetics of the short circuit current in organic bulk heterojunction solar cells

    NARCIS (Netherlands)

    Conings, B.S.T.; Bertho, S.; Vandewal, K.; Senes, A.; D'Haen, J.; Manca, J.V.; Janssen, R.A.J.

    2010-01-01

    In organic bulk heterojunction solar cells, the nanoscale morphology of interpenetrating donor-acceptor materials and the resulting photovoltaic parameters alter as a consequence of prolonged operation at temperatures above the glass transition temperature. Thermal annealing induces clustering of

  3. Mutual influences of rated currents, short circuit levels, fault durations and integrated protective schemes for industrial distribution MV switchgears

    Energy Technology Data Exchange (ETDEWEB)

    Gaidano, G. (FIAT Engineering, Torino, Italy); Lionetto, P.F.; Pelizza, C.; Tommazzolli, F.

    1979-01-01

    This paper deals with the problem of integrated and coordinated design of distribution systems, as regards the definition of system structure and parameters together with protection criteria and schemes. Advantages in system operation, dynamic response, heavier loads with reduced machinery rating margins and overall cost reduction, can be achieved. It must be noted that MV switchgears installed in industrial main distribution substations are the vital nodes of the distribution system. Very large amounts of power (up to 100 MW and more) are conveyed through MV busbars, coming from Utility and from in-plant generators and outgoing to subdistribution substations, to step-down transformers and to main concentrated loads (big drivers, furnaces etc.). Criteria and methods already studied and applied to public distribution are examined to assess service continuity and economics by means of the reduction of thermal stresses, minimization of disturbances and improvement of system stability. The life of network components depends on sizing, on fault energy levels and on probability of fault occurrence. Constructional measures and protection schemes, which reduce probability and duration of faults, are the most important tools to improve overall reliability. The introduction of advanced techniques, mainly based on computer application, not only allows drastic reduction of fault duration, but also permits the system to operate, under any possible contingency, in the optimal conditions, as the computer provides adaptive control. This mode of system management makes it possible to size network components with reference to the true magnitude of system quantities, avoiding expensive oversizing connected to the unflexibility of conventional protection and control schemes.

  4. A method of increasing the sensitivity of protection from single-phase short-circuits to ground in the 6 – 10 kV network

    International Nuclear Information System (INIS)

    Manilov, A. M.; Mel’nik, D. A.

    2012-01-01

    A method of increasing the sensitivity of protection from single-phase short-circuits to ground by acting on the signal with brief dummy grounding of the neutral is described. After determining the damage, the neutral is again grounded through a high resistance and an arc-quenching reactor. An increase in the protection sensitivity is thereby obtained, the damage detection time is shortened, and the probability of the single-phase short-circuit to ground converting into double and multipoint earth faults is reduced.

  5. On the short-circuit and avalanche ruggedness reliability assessment of SiC MOSFET modules

    DEFF Research Database (Denmark)

    Ionita, Claudiu; Nawaz, Muhammad; Ilves, Kalle

    2017-01-01

    to failure, a gate-source voltage drop has been recorded, which is associated with a high G-S leakage current. The main failure mechanism, however, is the thermal runaway which leads the devices into avalanche breakdown mode. During the UIS tests, multiple samples from the three vendors of the power modules...

  6. The Short Circuit Hypothesis of ESL Reading--Or when Language Competence Interferes with Reading Performance.

    Science.gov (United States)

    Clarke, Mark A.

    1980-01-01

    Examines a sampling of current ESL reading instruction practices, addressing the concern that the lack of a generally accepted theory of L2 reading constitutes a major obstacle to teaching and testing ESL reading skills. Summarizes the results of two studies and discusses their implications for ESL teachers. (MES)

  7. Application of Copper Cladding Aluminum Composites in UHV Portable Earthing and Short-circuiting Wires

    Directory of Open Access Journals (Sweden)

    Zhu Jianjun

    2018-01-01

    Full Text Available Aiming at the heavy weight and inconvenience when carrying and installing copper earthing wires on the UHV transmission lines, in this paper, we present the use of copper clad aluminum(CCA composite materials as a lightweight method for UHV earthing wire conductor. Theoretical calculations and tests of the fusing current in a short time for copper and CCA material are conducted. The results show that the theoretical value of the earthing wire conductor's fusing current corresponds with the test value on condition of the conductor cross section greater than 4mm2 as well as fusing time less than 1.5s. The CCA-10 earthing wires get 36.2% weight reduction compared with copper wires.

  8. Internal Short-Circuiting Phenomena In An Open-Cycle MHD Generator

    Energy Technology Data Exchange (ETDEWEB)

    Sasaki, Y.; Ishibashi, E. [Hitachi Research Laboratory, Hitachi-shi, Ibaraki-ken (Japan); Kasahara, T.; Kazawa, Y. [Hitachi Works, Hitachi Ltd., Hitachi-shi, Ibaraki-ken (Japan)

    1968-11-15

    The influence of internal electrical leakage due to circulating currents flowing through velocity boundary layers and due to metallic elements in insulating walls (peg walls) is experimentally investigated. For this purpose a combustion-driven MHD generator is utilized. The active part of the generator test section is 60 cm in length with a constant cross-section of 3 x 12 cm{sup 2}. At typical operating conditions about 70 g/s of diesel light oil is burned with oxygen-enriched air, resulting in a thermal input of 3 MW, a fluid velocity of 500 to 700 m/s and a gas temperature of 2700 to 2900 Degree-Sign K at the channel inlet. KOH is used as the seed material. The magnetic field can be raised up to 1.95 Teslas. In the range of lower magnetic fields (B < 0.8T) it is shown that an observed open-circuit voltage agrees well with the theoretical value OBh which is defined in a one-dimensional MHD model. In other words, the circulating currents scarcely affect the open-circuit voltage. The theoretical basis for this fact is obtained by the use of a simple model. Experimental results obtained in several runs using three sets of insulating walls show that thermal boundary layers at water-cooled metals are more conductive than expected and that the open- circuit voltage decreases because of leakage currents flowing through metal pegs, when the internal resistance of the generator is relatively large. Also, it is shown that an alumina coating is effective in reducing the leakage currents. (author)

  9. Dendrite short-circuit and fuse effect on Li/polymer/Li cells

    International Nuclear Information System (INIS)

    Rosso, Michel; Brissot, Claire; Teyssot, Anna; Dolle, Mickael; Sannier, Lucas; Tarascon, Jean-Marie; Bouchet, Renaud; Lascaud, Stephane

    2006-01-01

    We report on experimental and theoretical studies of dendritic growth in Li/polymer/Li symmetric cells. Potential evolution with time, impedance and in situ microscopy experiments enable to characterise the onset and evolution of dendrites. In particular we observe that dendrites may burn when a high enough current goes through them, a thermo-fusible effect predicted in a previous paper and confirmed by SEM experiments. We present a calculation that gives a quantitative description of this effect: our results enable to understand a series of experimental data published in the literature concerning impedance variations observed while cycling lithium-polymer cells

  10. Fast Calculation Model and Theoretical Analysis of Rotor Unbalanced Magnetic Pull for Inter-Turn Short Circuit of Field Windings of Non-Salient Pole Generators

    Directory of Open Access Journals (Sweden)

    Guangtao Zhang

    2017-05-01

    Full Text Available Inter-turn short circuit of field windings (ISCFW may cause the field current of a generator to increase, output reactive power to decrease, and unit vibration to intensify, seriously affecting its safe and stable operation. Full integration of mechanical and electrical characteristics can improve the sensitivity of online monitoring, and detect the early embryonic period fault of small turns. This paper studies the calculations and variations of unbalanced magnetic pull (UMP, of which the excitation source of rotor vibration is the basis and key to online fault monitoring. In grid load operation, ISCFW are first calculated with the multi-loop method, so as to obtain the numerical solutions of the stator and the rotor currents during the fault. Next, the air-gap magnetic field of the ISCFW is analyzed according to the actual composition modes of the motor loops in the fault, so as to obtain the analytic expressions of the air-gap magnetic motive force (MMF and magnetic density. The UMP of the rotor is obtained by solving the integral of the Maxwell stress. The correctness of the electric quantity calculation is verified by the ISCFW experiment, conducted in a one pair-pole non-salient pole model machine. On this basis, comparing the simulation analysis with the calculation results of the model in this paper not only verifies the accuracy of the electromagnetic force calculation, but also proves that the latter has the advantages of a short time consumption and high efficiency. Finally, the influencing factors and variation law of UMP are analyzed by means of an analytic model. This develops a base for the online monitoring of ISCFW with the integration of mechanical and electrical information.

  11. Modelling Li-ion cell thermal runaway triggered by an internal short circuit device using an efficiency factor and Arrhenius formulations

    DEFF Research Database (Denmark)

    Coman, Paul Tiberiu; Darcy, Eric; Veje, Christian

    2017-01-01

    This paper presents a novel model for analyzing the thermal runaway in Li-ion battery cells with an internal short circuit device implanted in the cell. The model is constructed using Arrhenius formulations for representing the self-heating chemical reactions and the State of Charge. The model...

  12. Short-circuit ruggedness assessment of a 1.2 kV/180 A SiC MOSFET power module

    DEFF Research Database (Denmark)

    Ionita, Claudiu; Nawaz, Muhammad; Ilves, Kalle

    2017-01-01

    is typically encountered in applications for devices of these ratings. Five modules were failed in total, with a critical short-circuit energy, Ecr ranging from 7.3 J to 9.7 J. The failure mechanism is generally the thermal runaway. Prior to failure, a decrease in VGS can be observed which is an indication...

  13. Sub-module Short Circuit Fault Diagnosis in Modular Multilevel Converter Based on Wavelet Transform and Adaptive Neuro Fuzzy Inference System

    DEFF Research Database (Denmark)

    Liu, Hui; Loh, Poh Chiang; Blaabjerg, Frede

    2015-01-01

    for continuous operation and post-fault maintenance. In this article, a fault diagnosis technique is proposed for the short circuit fault in a modular multi-level converter sub-module using the wavelet transform and adaptive neuro fuzzy inference system. The fault features are extracted from output phase voltage...

  14. Effects of an electromagnetic shield and armature teeth on the short-circuit performance of a direct drive superconducting generator for 10 MW wind turbines

    DEFF Research Database (Denmark)

    Liu, Dong; Polinder, Henk; Abrahamsen, Asger Bech

    2015-01-01

    reactance. An electromagnetic (EM) shield between the rotor and the stator as well as iron or non-magnetic composite (NMC) armature teeth affects the sub-transient reactance of a superconducting machine so that they play a role in the short-circuit performance of a superconducting wind generator. This paper...

  15. MATHEMATICAL MODELING OF TRANSIENT EMERGENCY ELECTROMAGNETIC PROCESSES IN THE SYSTEM OF THE ELECTROMAGNETIC TRACTION DC. 2. SHORT CIRCUIT WITH ELECTRIC ROLLING STOCK

    Directory of Open Access Journals (Sweden)

    P. E. Mihalichenko

    2010-04-01

    Full Text Available The article deals with the description of mathematical model of the system of traction electric power supply with load in the short circuit condition as well as the calculation results of this emergency process. The transition values as well as the character of their change, which can be used for detection of emergency processes, have been determined.

  16. Room Temperature Magnetic Field Measurements as a Tool to Localize Inter-turns Electrical Short Circuits in the LHC Main Dipole coils

    CERN Document Server

    Bellesia, B; Todesco, E

    2006-01-01

    In this report the method for the localization of the electric shorts circuits in the main LHC dipoles using the magnetic measurements at room temperature is presented. The steps of the method are discussed, and two cases are studied in detail. A complete statistics of the 12 cases analyzed up to now is given.

  17. On-Line Detection of Coil Inter-Turn Short Circuit Faults in Dual-Redundancy Permanent Magnet Synchronous Motors

    Directory of Open Access Journals (Sweden)

    Yiguang Chen

    2018-03-01

    Full Text Available In the aerospace and military fields, with high reliability requirements, the dual-redundancy permanent magnet synchronous motor (DRPMSM with weak thermal coupling and no electromagnetic coupling is needed. A common fault in the DRPMSM is the inter-turn short circuit fault (ISCF. However, research on how to diagnose ISCF and the set of faulty windings in the DRPMSM is lacking. In this paper, the structure of the DRPMSM is analyzed and mathematical models of the motor under normal and faulty conditions are established. Then an on-line ISCF detection scheme, which depends on the running modes of the DRPMSM and the average values for the difference of the d-axis voltages between two sets of windings in the latest 20 sampling periods, is proposed. The main contributions of this paper are to analyze the calculation for the inductance of each part of the stator windings and propose the on-line diagnosis method of the ISCF under various operating conditions. The simulation and experimental results show that the proposed method can quickly and effectively diagnose ISCF and determine the set of faulty windings of the DRPMSM.

  18. KNOWLEDGE TRANSFER AND LEARNING: PROBLEMS OF KNOWLEDGE TRANSFER ASSOCIATED WITH TRYING TO SHORT-CIRCUIT THE LEARNING CYCLE

    Directory of Open Access Journals (Sweden)

    Sue Newell

    2006-11-01

    Full Text Available Knowledge is considered to be a key organizational resource in the 21st century and the knowledge management ‘movement’ has alerted organizations to the fact that they should more strategically exploit their knowledge assets. Companies are thus lured by the suggestion that they can gain competitive advantage by the more astute management of their knowledge base and in particular, by the transfer of knowledge across individuals, groups and organizational units, using IT to accomplish this. In this paper, we reflect on this common view of knowledge transfer. More specifically, we question an implication of this view - essentially the possibility of short-circuiting the learning cycle, so that individuals do not have to rely on their personal or shared experiences to identify better practices, but can learn from the codified lessons of others in IT systems. More importantly, we consider the characteristics of knowledge – that knowledge is distributed, ambiguous and disruptive – that makes its transfer highly problematic. Drawing on case research, we relate this to the learning cycle (Kolb 1984 and thereby identify barriers to knowledge transfer. We conclude by considering ways of overcoming these barriers by emphasizing the importance of social systems alongside technical systems.

  19. Theoretical and experimental analysis of a linear accelerator endowed with single feed coupler with movable short-circuit

    International Nuclear Information System (INIS)

    Forno, Massimo Dal; Craievich, Paolo; Penco, Giuseppe; Vescovo, Roberto

    2013-01-01

    The front-end injection systems of the FERMI@Elettra linac produce high brightness electron beams that define the performance of the Free Electron Laser. The photoinjector mainly consists of the radiofrequency (rf) gun and of two S-band rf structures which accelerate the beam. Accelerating structures endowed with a single feed coupler cause deflection and degradation of the electron beam properties, due to the asymmetry of the electromagnetic field. In this paper, a new type of single feed structure with movable short-circuit is proposed. It has the advantage of having only one waveguide input, but we propose a novel design where the dipolar component is reduced. Moreover, the racetrack geometry allows to reduce the quadrupolar component. This paper presents the microwave design and the analysis of the particle motion inside the linac. A prototype has been machined at the Elettra facility to verify the new coupler design and the rf field has been measured by adopting the bead-pull method. The results are here presented, showing good agreement with the expectations

  20. Mechanism of the entire overdischarge process and overdischarge-induced internal short circuit in lithium-ion batteries.

    Science.gov (United States)

    Guo, Rui; Lu, Languang; Ouyang, Minggao; Feng, Xuning

    2016-07-22

    Lithium-ion batteries connected in series are prone to be overdischarged. Overdischarge results in various side effects, such as capacity degradation and internal short circuit (ISCr). However, most of previous research on the overdischarge of a cell was terminated when the cell voltage dropped to 0 V, leaving the further impacts of overdischarge unclear. This paper investigates the entire overdischarge process of large-format lithium-ion batteries by discharging the cell to -100% state of charge (SOC). A significant voltage platform is observed at approximately -12% SOC, and ISCr is detected after the cell is overdischarged when passing the platform. The scanning electron microscopy (SEM) and X-ray diffraction (XRD) results indicate that the overdischarge-induced ISCr is caused by Cu deposition on electrodes, suggesting possible Cu collector dissolution at the voltage platform near -12% SOC. A prognostic/mechanistic model considering ISCr is used to evaluate the resistance of ISCr (RISCr), the value of which decreases sharply at the beginning of ISCr formation. Inducing the ISCr by overdischarge is effective and well controlled without any mechanical deformation or the use of a foreign substance.

  1. Eco-friendly preparation of large-sized graphene via short-circuit discharge of lithium primary battery.

    Science.gov (United States)

    Kang, Shaohong; Yu, Tao; Liu, Tingting; Guan, Shiyou

    2018-02-15

    We proposed a large-sized graphene preparation method by short-circuit discharge of the lithium-graphite primary battery for the first time. LiC x is obtained through lithium ions intercalation into graphite cathode in the above primary battery. Graphene was acquired by chemical reaction between LiC x and stripper agents with dispersion under sonication conditions. The gained graphene is characterized by Raman spectrum, X-ray diffraction (XRD), transmission electron microscopy (TEM), X-ray photoelectron spectroscopy (XPS), Atomic force microscope (AFM) and Scanning electron microscopy (SEM). The results indicate that the as-prepared graphene has a large size and few defects, and it is monolayer or less than three layers. The quality of graphene is significant improved compared to the reported electrochemical methods. The yield of graphene can reach 8.76% when the ratio of the H 2 O and NMP is 3:7. This method provides a potential solution for the recycling of waste lithium ion batteries. Copyright © 2017 Elsevier Inc. All rights reserved.

  2. Theoretical and experimental analysis of a linear accelerator endowed with single feed coupler with movable short-circuit.

    Science.gov (United States)

    Dal Forno, Massimo; Craievich, Paolo; Penco, Giuseppe; Vescovo, Roberto

    2013-11-01

    The front-end injection systems of the FERMI@Elettra linac produce high brightness electron beams that define the performance of the Free Electron Laser. The photoinjector mainly consists of the radiofrequency (rf) gun and of two S-band rf structures which accelerate the beam. Accelerating structures endowed with a single feed coupler cause deflection and degradation of the electron beam properties, due to the asymmetry of the electromagnetic field. In this paper, a new type of single feed structure with movable short-circuit is proposed. It has the advantage of having only one waveguide input, but we propose a novel design where the dipolar component is reduced. Moreover, the racetrack geometry allows to reduce the quadrupolar component. This paper presents the microwave design and the analysis of the particle motion inside the linac. A prototype has been machined at the Elettra facility to verify the new coupler design and the rf field has been measured by adopting the bead-pull method. The results are here presented, showing good agreement with the expectations.

  3. Impact of hydroelectric installations on the morphology's short-circuited reaches of the Durance and the Verdon Rivers

    International Nuclear Information System (INIS)

    Lefort, Philippe; Chapuis, Margot

    2012-01-01

    Attenuation of flood peaks by the reservoirs of Serre Poncon and along the Verdon River, and diversions of the Durance River's flow in the industrial canal significantly modify the flow regime in the short-circuited beds. Upstream inflow of gravel materials is decreased, bed-load transport is significantly reduced, channels' mobility is atrophied, or becomes even nonexistent. The vegetation impact leads then to an obstruction of the braided channel, the rare occurrence of high flows is not able to prevent. Clearing the bed has been and stays an efficient response to the vegetation encroachment, and a necessary condition to maintain the discharge capacity during high flow, the originality and the diversity of the natural landforms. The loss of mobility is also due to bed-load transport's interruption through dams, but even more to the past gravel extractions and to weirs that sustain low flow: bed-load transport restoration through dams, sedimentary recharge of the bed with gravels coming from lateral terraces and increasing of high flows intensity will lead to a minimal required mobility. (authors)

  4. Short-Circuit Fault Tolerant Control of a Wind Turbine Driven Induction Generator Based on Sliding Mode Observers

    Directory of Open Access Journals (Sweden)

    Takwa Sellami

    2017-10-01

    Full Text Available The installed energy production capacity of wind turbines is growing intensely on a global scale, making the reliability of wind turbine subsystems of greater significance. However, many faults like Inter-Turn Short-Circuit (ITSC may affect the turbine generator and quickly lead to a decline in supplied power quality. In this framework, this paper proposes a Sliding Mode Observer (SMO-based Fault Tolerant Control (FTC scheme for Induction Generator (IG-based variable-speed grid-connected wind turbines. First, the dynamic models of the wind turbine subsystems were developed. The control schemes were elaborated based on the Maximum Power Point Tracking (MPPT method and Indirect Rotor Flux Oriented Control (IRFOC method. The grid control was also established by regulating the active and reactive powers. The performance of the wind turbine system and the stability of injected power to the grid were hence analyzed under both healthy and faulty conditions. The robust developed SMO-based Fault Detection and Isolation (FDI scheme was proved to be fast and efficient for ITSC detection and localization.Afterwards, SMO were involved in scheming the FTC technique. Accordingly, simulation results assert the efficacy of the proposed ITSC FTC method for variable-speed wind turbines with faulty IG in protecting the subsystems from damage and ensuring continuous connection of the wind turbine to the grid during ITSC faults, hence maintaining power quality.

  5. The CTBTO Link to the database of the International Seismological Centre (ISC)

    Science.gov (United States)

    Bondar, I.; Storchak, D. A.; Dando, B.; Harris, J.; Di Giacomo, D.

    2011-12-01

    The CTBTO Link to the database of the International Seismological Centre (ISC) is a project to provide access to seismological data sets maintained by the ISC using specially designed interactive tools. The Link is open to National Data Centres and to the CTBTO. By means of graphical interfaces and database queries tailored to the needs of the monitoring community, the users are given access to a multitude of products. These include the ISC and ISS bulletins, covering the seismicity of the Earth since 1904; nuclear and chemical explosions; the EHB bulletin; the IASPEI Reference Event list (ground truth database); and the IDC Reviewed Event Bulletin. The searches are divided into three main categories: The Area Based Search (a spatio-temporal search based on the ISC Bulletin), the REB search (a spatio-temporal search based on specific events in the REB) and the IMS Station Based Search (a search for historical patterns in the reports of seismic stations close to a particular IMS seismic station). The outputs are HTML based web-pages with a simplified version of the ISC Bulletin showing the most relevant parameters with access to ISC, GT, EHB and REB Bulletins in IMS1.0 format for single or multiple events. The CTBTO Link offers a tool to view REB events in context within the historical seismicity, look at observations reported by non-IMS networks, and investigate station histories and residual patterns for stations registered in the International Seismographic Station Registry.

  6. The Akt inhibitor ISC-4 synergizes with cetuximab in 5-FU-resistant colon cancer.

    Directory of Open Access Journals (Sweden)

    Joshua E Allen

    Full Text Available Phenylbutyl isoselenocyanate (ISC-4 is an Akt inhibitor with demonstrated preclinical efficacy against melanoma and colon cancer. In this study, we sought to improve the clinical utility of ISC-4 by identifying a synergistic combination with FDA-approved anti-cancer therapies, a relevant and appropriate disease setting for testing, and biomarkers of response. We tested the activity of ISC-4 and 19 FDA-approved anticancer agents, alone or in combination, against the SW480 and RKO human colon cancer cell lines. A synergistic interaction with cetuximab was identified and validated in a panel of additional colon cancer cell lines, as well as the kinetics of synergy. ISC-4 in combination with cetuximab synergistically reduced the viability of human colon cancer cells with wild-type but not mutant KRAS genes. Further analysis revealed that the combination therapy cooperatively decreased cell cycle progression, increased caspase-dependent apoptosis, and decreased phospho-Akt in responsive tumor cells. The synergism between ISC-4 and cetuximab was retained independently of acquired resistance to 5-FU in human colon cancer cells. The combination demonstrated synergistic anti-tumor effects in vivo without toxicity and in the face of resistance to 5-FU. These results suggest that combining ISC-4 and cetuximab should be explored in patients with 5-FU-resistant colon cancer harboring wild-type KRAS.

  7. The Comparison of the Inquiry Behavior of ISCS and Non-ISCS Science Students as Measured by the Tab Science Test

    Science.gov (United States)

    Stallings, Everett S.; Snyder, William R.

    1977-01-01

    Studies of a group of seventh-grade students who were tested for inquiry skills using the TAB Science Test showed no significant differences between those students who had studied the Intermediate Science Curriculum Study (ISCS) and those who studied another curriculum. (MLH)

  8. Radiotherapy supporting system based on the image database using IS&C magneto-optical disk

    Science.gov (United States)

    Ando, Yutaka; Tsukamoto, Nobuhiro; Kunieda, Etsuo; Kubo, Atsushi

    1994-05-01

    Since radiation oncologists make the treatment plan by prior experience, information about previous cases is helpful in planning the radiation treatment. We have developed an supporting system for the radiation therapy. The case-based reasoning method was implemented in order to search old treatments and images of past cases. This system evaluates similarities between the current case and all stored cases (case base). The portal images of the similar cases can be retrieved for reference images, as well as treatment records which show examples of the radiation treatment. By this system radiotherapists can easily make suitable plans of the radiation therapy. This system is useful to prevent inaccurate plannings due to preconceptions and/or lack of knowledge. Images were stored into magneto-optical disks and the demographic data is recorded to the hard disk which is equipped in the personal computer. Images can be displayed quickly on the radiotherapist's demands. The radiation oncologist can refer past cases which are recorded in the case base and decide the radiation treatment of the current case. The file and data format of magneto-optical disk is the IS&C format. This format provides the interchangeability and reproducibility of the medical information which includes images and other demographic data.

  9. Feasibility study of superconducting power cables for DC electric railway feeding systems in view of thermal condition at short circuit accident

    Science.gov (United States)

    Kumagai, Daisuke; Ohsaki, Hiroyuki; Tomita, Masaru

    2016-12-01

    A superconducting power cable has merits of a high power transmission capacity, transmission losses reduction, a compactness, etc., therefore, we have been studying the feasibility of applying superconducting power cables to DC electric railway feeding systems. However, a superconducting power cable is required to be cooled down and kept at a very low temperature, so it is important to reveal its thermal and cooling characteristics. In this study, electric circuit analysis models of the system and thermal analysis models of superconducting cables were constructed and the system behaviors were simulated. We analyzed the heat generation by a short circuit accident and transient temperature distribution of the cable to estimate the value of temperature rise and the time required from the accident. From these results, we discussed a feasibility of superconducting cables for DC electric railway feeding systems. The results showed that the short circuit accident had little impact on the thermal condition of a superconducting cable in the installed system.

  10. Internal short circuit and accelerated rate calorimetry tests of lithium-ion cells: Considerations for methane-air intrinsic safety and explosion proof/flameproof protection methods.

    Science.gov (United States)

    Dubaniewicz, Thomas H; DuCarme, Joseph P

    2016-09-01

    Researchers with the National Institute for Occupational Safety and Health (NIOSH) studied the potential for lithium-ion cell thermal runaway from an internal short circuit in equipment for use in underground coal mines. In this third phase of the study, researchers compared plastic wedge crush-induced internal short circuit tests of selected lithium-ion cells within methane (CH 4 )-air mixtures with accelerated rate calorimetry tests of similar cells. Plastic wedge crush test results with metal oxide lithium-ion cells extracted from intrinsically safe evaluated equipment were mixed, with one cell model igniting the chamber atmosphere while another cell model did not. The two cells models exhibited different internal short circuit behaviors. A lithium iron phosphate (LiFePO 4 ) cell model was tolerant to crush-induced internal short circuits within CH 4 -air, tested under manufacturer recommended charging conditions. Accelerating rate calorimetry tests with similar cells within a nitrogen purged 353-mL chamber produced ignitions that exceeded explosion proof and flameproof enclosure minimum internal pressure design criteria. Ignition pressures within a 20-L chamber with 6.5% CH 4 -air were relatively low, with much larger head space volume and less adiabatic test conditions. The literature indicates that sizeable lithium thionyl chloride (LiSOCl 2 ) primary (non rechargeable) cell ignitions can be especially violent and toxic. Because ignition of an explosive atmosphere is expected within explosion proof or flameproof enclosures, there is a need to consider the potential for an internal explosive atmosphere ignition in combination with a lithium or lithium-ion battery thermal runaway process, and the resulting effects on the enclosure.

  11. Intelligence and High Intensity Drug Trafficking Areas (HIDTA's): A Critical Evaluation of the HIDTA Investigative Support Center (ISC)

    National Research Council Canada - National Science Library

    Gutierrez, Michael

    2004-01-01

    ...) Investigative Support Center (ISC). Prior to 9/11, the national intelligence apparatus was littered with flaws, including lack of information sharing, interagency conflict, and autonomous operations...

  12. Water quality, hydrology, and the effects of changes in phosphorus loading to Pike Lake, Washington County, Wisconsin, with special emphasis on inlet-to-outlet short-circuiting

    Science.gov (United States)

    Rose, William J.; Robertson, Dale M.; Mergener, Elizabeth A.

    2004-01-01

    Pike Lake is a 459-acre, mesotrophic to eutrophic dimictic lake in southeastern Wisconsin. Because of concern over degrading water quality in the lake associated with further development in its watershed, a study was conducted by the U.S. Geological Survey from 1998 to 2000 to describe the water quality and hydrology of the lake, quantify sources of phosphorus including the effects of short-circuiting of inflows, and determine how changes in phosphorus loading should affect the water quality of the lake. Measuring all significant water and phosphorus sources and estimating lesser sources was the method used to construct detailed water and phosphorus budgets. The Rubicon River, ungaged near-lake surface inflow, precipitation, and ground water provide 55, 20, 17, and 7 percent of the total inflow, respectively. Water leaves the lake through the Rubicon River outlet (87 percent) or by evaporation (13 percent). Total input of phosphorus to the lake was about 3,500 pounds in 1999 and 2,400 pounds in 2000. About 80 percent of the phosphorus was from the Rubicon River, about half of which came from the watershed and half from a waste-water treatment plant in Slinger, Wisconsin. Inlet-to-outlet short-circuiting of phosphorus is facilitated by a meandering segment of the Rubicon River channel through a marsh at the north end of the lake. It is estimated that 77 percent of phosphorus from the Rubicon River in monitoring year 1999 and 65 percent in monitoring year 2000 was short-circuited to the outlet without entering the main body of the lake.

  13. Fault clearance in medium-voltage networks using remote-monitored short-circuit alarms; Stoerungsbeseitigung im MS-Netz mit fernueberwachten Kurzschlussmeldern

    Energy Technology Data Exchange (ETDEWEB)

    Beran, B. [Reginalzentrum Neckar-Franken der EnBW Regional AG, Oehringen (Germany). Bereich Netzfuehrung; Deiss, R. [RBS Genius GmbH, Stuttgart (Germany). Bereich Korrosionsschutz und Gaslecksuche; Stibbe, T. [Phoenix Contact GmbH und Co KG, Blomberg (Lippe) (Germany). Vertrieb Deutschland

    2006-04-15

    In March 2005, a pilot project on remote monitoring of short-circuit alarms using GSM was started. In cooperation with RBS Genius GmbH (100 percent subsidiary of EnBW Regional AG) who already use a similar technology for controlling cathodic corrosion protection systems, and the EnBW-Regionalzentrum Neckar-Franken, the functionalities were specified. After only five months of development and assembly time, the first 15 units were installed in exposed and difficult-to-access sites. All sites were located along very long power lines in which localisation of the defect would be very time-consuming. (orig.)

  14. A Flexible Power Control Method of VSC-HVDC Link for the Enhancement of Effective Short-Circuit Ratio in a Hybrid Multi-Infeed HVDC System

    DEFF Research Database (Denmark)

    Liu, Yan; Chen, Zhe

    2013-01-01

    . To evaluate the contribution of the VSC-HVDC link on the voltage stability of HMIDC system, this paper proposes an effective short circuit ratio (ESCR) calculation method. Through the calculation, the voltage support capability of the VSC-HVDC link can be quantitatively represented by the ESCR. Furthermore......, based on the calculation results, a flexible power control strategy for the VSC-HVDC link is developed to provide maximum reactive power support under grid faults. The theoretical analysis of the HMIDC system is based on the Danish transmission grid, evaluated through PSCAD simulations under different...

  15. NREL Multiphysics Modeling Tools and ISC Device for Designing Safer Li-Ion Batteries

    Energy Technology Data Exchange (ETDEWEB)

    Pesaran, Ahmad A.; Yang, Chuanbo

    2016-03-24

    The National Renewable Energy Laboratory has developed a portfolio of multiphysics modeling tools to aid battery designers better understand the response of lithium ion batteries to abusive conditions. We will discuss this portfolio, which includes coupled electrical, thermal, chemical, electrochemical, and mechanical modeling. These models can simulate the response of a cell to overheating, overcharge, mechanical deformation, nail penetration, and internal short circuit. Cell-to-cell thermal propagation modeling will be discussed.

  16. IRRIGATION SCHEDULING CALCULATOR (ISC TO IMPROVE WATER MANAGEMENT ON FIELD LEVEL IN EGYPT

    Directory of Open Access Journals (Sweden)

    Samiha Abou El-Fetouh Hamed Ouda

    2017-10-01

    Full Text Available The developed model is MS excel sheet called “Irrigation Scheduling Calculator, ISC”. The model requires to input daily weather data to calculate daily evapotranspiration using Penman-Monteith equation. The model calculates water depletion from the root zone to determine when to irrigate and how much water should be applied. The charge from irrigation pump is used to calculate how many hours should the farmer run the pump to deliver the needed amount of water. ISC model was used to developed irrigation schedule for wheat and maize planted in El-Gharbia governorate. The developed schedules were compared to the actual schedules for both crops. Furthermore, CropSyst model was calibrated for both crops and run using the developed schedules by ISC model. The simulation results indicated that the calculated irrigation amount by ISC model for wheat was lower than actual schedule by 6.0 mm. Furthermore, the simulated wheat productivity by CropSyst was higher than measured grain and biological by 2%. Similarly, the calculated applied irrigation amount by ISC model for maize was lower than actual schedule by 79.0 mm and the productivity was not changed.

  17. Feasibility Study of the PS Injection for 2 GeV LIU Beams with an Upgraded KFA-45 Injection Kicker System Operating in Short Circuit Mode

    CERN Document Server

    Kramer, Thomas; Borburgh, Jan; Ducimetière, Laurent; Feliciano, Luis; Ferrero Colomo, Alvaro; Goddard, Brennan; Sermeus, Luc

    2016-01-01

    Under the scope of the LIU project the CERN PS Booster to PS beam transfer will be modified to match the requirements for the future 2 GeV beams. This paper describes the evaluation of the proposed upgrade of the PS injection kicker. Different schemes of an injection for LIU beams into the PS have been outlined in the past already under the aspect of individual transfer kicker rise and fall time performances. Homogeneous rise and fall time requirements in the whole PSB to PS transfer chain have been established which allowed to consider an upgrade option of the present injection kicker system operated in short circuit mode. The challenging pulse quality constraints require an improvement of the flat top and post pulse ripples. Both operation modes, terminated and short circuit mode are analysed and analogue circuit simulations for the present and upgraded system are outlined. Recent measurements on the installed kickers are presented and analysed together with the simulation data. First measurements verifying...

  18. Evolution of short circuit levels in the National Electric System, years 2007 to 2011; Evolucion de los niveles de cortocircuito del Sistema Electrico Nacional, anos 2007 al 2011

    Energy Technology Data Exchange (ETDEWEB)

    Quintana Castaneda, J; Reyes Escobedo, G [Instituto de Investigaciones Electricas (Mexico)]. E-mails: jqc@iie.org.mx; gustavo.reyes@iie.org.mx; Ibarra Romo, F.G. [Comision Federal de Electricidad (Mexico)]. E-mail: federico.ibarra@cfe.gob.mx

    2013-03-15

    The present document shows an analysis of 2011 short-circuit levels on the different nodes (substations) that integrate the National Electric System. This analysis presents the figures of short-circuit levels on past years, stating on 2007, with the purpose of detecting the variation on each one of these nodes and identify the cases that because it's high levels are considered as critical nodes of the transmission system. At the end of the analysis some recommendations to minimize the potential risks are given on those substations classified as critical nodes. [Spanish] En este documento se expone un analisis de los niveles de cortocircuito que se presentaron en el 2011 en los distintos nodos (subestaciones) que conforman la red del Sistema Electrico Nacional (SEN). Este analisis muestra las cifras de los niveles de cortocircuito que se han presentado desde el ano 2007, a fin de estudiar el comportamiento y evolucion que han tenido los nodos de la red electrica, identificando aquellos puntos que por sus altos niveles de cortocircuito se consideran como nodos criticos. En la parte final del analisis se dan algunas recomendaciones para disminuir los riesgos que se pudieran presentar en aquellas subestaciones clasificadas como nodos criticos.

  19. Detecting the single line to ground short circuit fault in the submarine’s power system using the artificial neural network

    Directory of Open Access Journals (Sweden)

    Behniafar Ali

    2013-01-01

    Full Text Available The electric marine instruments are newly inserted in the trade and industry, for which the existence of an equipped and reliable power system is necessitated. One of the features of such a power system is that it cannot have an earth system causing the protection relays not to be able to detect the single line to ground short circuit fault. While on the other hand, the occurrence of another similar fault at the same time can lead to the double line fault and thereby the tripping of relays and shortening of vital loads. This in turn endangers the personals' security and causes the loss of military plans. From the above considerations, it is inferred that detecting the single line to ground fault in the marine instruments is of a special importance. In this way, this paper intends to detect the single line to ground fault in the power systems of the marine instruments using the wavelet transform and Multi-Layer Perceptron (MLP neural network. In the numerical analysis, several different types of short circuit faults are simulated on several marine power systems and the proposed approach is applied to detect the single line to ground fault. The results are of a high quality and preciseness and perfectly demonstrate the effectiveness of the proposed approach.

  20. Advanced Near Net Shape Technology (ANNST) - Integrally Stiffened Cylinder (ISC)

    Data.gov (United States)

    National Aeronautics and Space Administration — Machined/welded construction of launch vehicle cryotanks is expensive, heavy, and risky. The current state of the art manufacturing of launch vehicles contributes to...

  1. The Molecular Bases of the Dual Regulation of Bacterial Iron Sulfur Cluster Biogenesis by CyaY and IscX

    Directory of Open Access Journals (Sweden)

    Salvatore Adinolfi

    2018-02-01

    Full Text Available IscX (or YfhJ is a protein of unknown function which takes part in the iron-sulfur cluster assembly machinery, a highly specialized and essential metabolic pathway. IscX binds to iron with low affinity and interacts with IscS, the desulfurase central to cluster assembly. Previous studies have suggested a competition between IscX and CyaY, the bacterial ortholog of frataxin, for the same binding surface of IscS. This competition could suggest a link between the two proteins with a functional significance. Using a hybrid approach based on nuclear magnetic resonance, small angle scattering and biochemical methods, we show here that IscX is a modulator of the inhibitory properties of CyaY: by competing for the same site on IscS, the presence of IscX rescues the rates of enzymatic cluster formation which are inhibited by CyaY. The effect is stronger at low iron concentrations, whereas it becomes negligible at high iron concentrations. These results strongly suggest the mechanism of the dual regulation of iron sulfur cluster assembly under the control of iron as the effector.

  2. Development of a prototype solid state fault current limiting and interrupting device for low voltage distribution networks.

    OpenAIRE

    Ahmed, M.; Putrus, G. A.; Ran, L.; Penlington, R.

    2006-01-01

    This paper describes the development of a solid-state Fault Current Limiting and Interrupting Device (FCLID) suitable for low voltage distribution networks. The main components of the FCLID are a bidirectional semiconductor switch that can disrupt the short-circuit current, and a voltage clamping element that helps in controlling the current and absorbing the inductive energy stored in the network during current interruption. Using a hysteresis type control algorithm, the short-circuit curren...

  3. Successful field implementation of novel cementing solution for ISC wells : case histories

    Energy Technology Data Exchange (ETDEWEB)

    Meher, R.K.; Suyan, K.M.; Dasgupta, D. [Society of Petroleum Engineers, Dubai (United Arab Emirates)]|[Oil and Natural Gas Corp. Ltd., Tel Bhavan, Dehradun (India); Deodhar, S.; Sharma, V.; Jain, V.K. [Oil and Natural Gas Corp. Ltd., Tel Bhavan, Dehradun (India)

    2008-10-15

    Cementation of in-situ combustion (ISC) wells is challenging since wells are frequently associated with weak and unconsolidated formation. However, cement rise up to surface is desired to prevent casing failure. Moreover, the cement sheath is also required to withstand extreme stresses due to high temperature cycling experienced during in-situ combustion process. In response to the problem of inadequate placement time and flash setting, Portland cement-silica blends were used for cementation of ISC wells in India instead of alumina cement blends. However, the use of the cement-silica blends has resulted in insufficient cement rise because of losses during cementation. The cured cement failed to contain the strength and permeability in course of ISC process causing charge of sub-surface shallower layers. This paper discussed the development and implementation of a non-alumina based thermally stable lightweight lead slurry and a ductile high temperature resistance tail slurry for mitigating these problems. The paper provided details of the study as well as four successful case histories. The cementing practice for ISC wells around the world was first described and illustrated. Next, the paper outlined the formulation of thermally stable tail slurry through laboratory studies. Slurry parameters of the tail slurry were presented, including slurry weight; thickening time; fluid loss; free fluid; and rheology. The paper also reviewed a study of compressive strength and permeability of thermal slurry; slurry parameters of the lightweight lead slurry; and study of compressive strength and permeability of lightweight thermal slurry. 8 refs., 4 tabs., 12 figs.

  4. Size optimization for complex permeability measurement of magnetic thin films using a short-circuited microstrip line up to 30 GHz

    Science.gov (United States)

    Takeda, Shigeru; Naoe, Masayuki

    2018-03-01

    High-frequency permeability spectra of magnetic films were measured over a wideband frequency range of 0.1-30 GHz using a shielded and short-circuited microstrip line jig. In this measurement, spurious resonances had to be suppressed up to the highest frequency. To suppress these resonances, characteristic impedance of the microstrip line should approach 50 Ω at the junction between connector and microstrip line. The main factors dominating these resonances were structures of the jig and the sample. The dimensions were optimized in various experiments, and results demonstrated that the frequency could be raised to at least 20 GHz. For the transverse electromagnetic mode to transmit stably along the microstrip line, the preferred sample was rectangular, with the shorter side parallel to the line and the longer side perpendicular to it, and characteristic impedance strongly depended on the signal line width of the jig. However, too small a jig and sample led to a lower S/N ratio.

  5. Spectroscopic and functional characterization of iron-bound forms of Azotobacter vinelandii (Nif)IscA.

    Science.gov (United States)

    Mapolelo, Daphne T; Zhang, Bo; Naik, Sunil G; Huynh, Boi Hanh; Johnson, Michael K

    2012-10-16

    The ability of Azotobacter vinelandii(Nif)IscA to bind Fe has been investigated to assess the role of Fe-bound forms in NIF-specific Fe-S cluster biogenesis. (Nif)IscA is shown to bind one Fe(III) or one Fe(II) per homodimer and the spectroscopic and redox properties of both the Fe(III)- and Fe(II)-bound forms have been characterized using the UV-visible absorption, circular dichroism, and variable-temperature magnetic circular dichroism, electron paramagnetic resonance, Mössbauer and resonance Raman spectroscopies. The results reveal a rhombic intermediate-spin (S = 3/2) Fe(III) center (E/D = 0.33, D = 3.5 ± 1.5 cm(-1)) that is most likely 5-coordinate with two or three cysteinate ligands and a rhombic high spin (S = 2) Fe(II) center (E/D = 0.28, D = 7.6 cm(-1)) with properties similar to reduced rubredoxins or rubredoxin variants with three cysteinate and one or two oxygenic ligands. Iron-bound (Nif)IscA undergoes reversible redox cycling between the Fe(III)/Fe(II) forms with a midpoint potential of +36 ± 15 mV at pH 7.8 (versus NHE). l-Cysteine is effective in mediating release of free Fe(II) from both the Fe(II)- and Fe(III)-bound forms of (Nif)IscA. Fe(III)-bound (Nif)IscA was also shown to be a competent iron source for in vitro NifS-mediated [2Fe-2S] cluster assembly on the N-terminal domain of NifU, but the reaction occurs via cysteine-mediated release of free Fe(II) rather than direct iron transfer. The proposed roles of A-type proteins in storing Fe under aerobic growth conditions and serving as iron donors for cluster assembly on U-type scaffold proteins or maturation of biological [4Fe-4S] centers are discussed in light of these results.

  6. A Review on Grid-connected Converter Control for Short Circuit Power Provision under Grid Unbalanced Faults

    DEFF Research Database (Denmark)

    Jia, Jundi; Yang, Guangya; Nielsen, Arne Hejde

    2017-01-01

    behave significantly different from the traditional alternators under grid faults. In order to evaluate the potential impact of future converter-based power systems on protective relays, it is necessary to consider diverse current control strategies of voltage source converters (VSC) under unbalanced...

  7. Controlled short-circuiting MIG-MAG welding process and procedures applied to the root pass in pipeline construction; Processo de soldagem MIG/MAG em curto-circuito controlado e procedimentos aplicados ao passe de raiz na construcao de linhas dutoviarias

    Energy Technology Data Exchange (ETDEWEB)

    Silva, Regis H.G. e; Gohr Junior, Raul; Weck, Leonardo W.A. [Santa Catarina Univ., Florianopolis, SC (Brazil). Dept. de Engenharia Mecanica. Lab. de Soldagem e Mecatronica (LABSOLDA)

    2005-07-01

    The work deals with the study and development of the Controlled Short-Circuiting MIG/MAG Welding Process (CCC) and procedures for the root pass on pipes, in pipelines construction. The developed process (CCC) consists in an semi-automatic slag free operation, yielding higher productivity than the Coated Electrode and TIG processes, with satisfactory properties on the root weld. The significant influence of the welding over the time schedule and construction cost makes the development of this technology attractive, in order to become available at low cost, enhancing the companies' competitiveness in the globalized oil sector. The developed system, a MIG/MAG variant, features the advantages of short-circuiting metal transfer and avoids its inconveniences (mainly with high CO{sub 2} content gases), enabling its use on pipes root welding. This is possible through current waveform control, providing process and weld pool stability. Procedures for the root pass were determined for each of the welding positions reached in thick walled pipes welding, with the CCC. Also, the low welder training time was notable. (author)

  8. Interaction of the iron–sulfur cluster assembly protein IscU with the Hsc66/Hsc20 molecular chaperone system of Escherichia coli

    Science.gov (United States)

    Hoff, Kevin G.; Silberg, Jonathan J.; Vickery, Larry E.

    2000-01-01

    The iscU gene in bacteria is located in a gene cluster encoding proteins implicated in iron–sulfur cluster assembly and an hsc70-type (heat shock cognate) molecular chaperone system, iscSUA-hscBA. To investigate possible interactions between these systems, we have overproduced and purified the IscU protein from Escherichia coli and have studied its interactions with the hscA and hscB gene products Hsc66 and Hsc20. IscU and its iron–sulfur complex (IscU–Fe/S) stimulated the basal steady-state ATPase activity of Hsc66 weakly in the absence of Hsc20 but, in the presence of Hsc20, increased the ATPase activity up to 480-fold. Hsc20 also decreased the apparent Km for IscU stimulation of Hsc66 ATPase activity, and surface plasmon resonance studies revealed that Hsc20 enhances binding of IscU to Hsc66. Surface plasmon resonance and isothermal titration calorimetry further showed that IscU and Hsc20 form a complex, and Hsc20 may thereby aid in the targeting of IscU to Hsc66. These results establish a direct and specific role for the Hsc66/Hsc20 chaperone system in functioning with isc gene components for the assembly of iron–sulfur cluster proteins. PMID:10869428

  9. An application of residual current protective device at electrical installation

    International Nuclear Information System (INIS)

    Firman Silitonga

    2008-01-01

    In an electrical installation, a protection for overload and short circuit are always to be installed. In addition to the installation, it is necessary to be installed a protection device for residual current because both the short circuit and the overload device protection will not work for the residual current. The quantity of the residual current must be defined first at any electrical installation to define an appropriate residual current protection so that not every residual current will break the circuit down. This paper will explain a method how to install a residual protection device for 3500 VA or more at TN and TT of earthing system. (author)

  10. Investigation on the Short-Circuit Behavior of an Aged IGBT Module Through a 6 kA/1.1 kV Non-Destructive Testing Equipment

    DEFF Research Database (Denmark)

    Wu, Rui; Smirnova, Liudmila; Iannuzzo, Francesco

    2014-01-01

    This paper describes the design and development of a 6 kA/1.1 kV non-destructive testing system, which aims for short circuit testing of high-power IGBT modules. An ultralow stray inductance of 37 nH is achieved in the implementation of the tester. An 100 MHz FPGA supervising unit enables 10 ns...

  11. Open- and Short-Circuit Fault Identification for a Boost dc/dc Converter in PV MPPT Systems

    Directory of Open Access Journals (Sweden)

    Diego R. Espinoza Trejo

    2018-03-01

    Full Text Available This paper proposes a fault identification system for short and open-circuit switch faults (SOCSF for a dc/dc converter acting as a Maximum Power Point Tracker (MPPT in Photovoltaic (PV systems. A closed-loop operation is assumed for the boost dc/dc converter. A linearizing control plus a Proportional-Derivative (PD controller is suggested for PV voltage regulation at the maximum power point (MPP. In this study, the SOCSF are modeled by using an additive fault representation and the fault identification (FI system is synthesized departing from a Luenberger observer. Hence, an FI signal is obtained, which is insensitive to irradiance and load current changes, but affected by the SOCSF. For FI purposes, only the sensors used in the control system are needed. Finally, an experimental evaluation is presented by using a solar array simulator dc power supply and a boost dc/dc converter of 175 W in order to validate the ideas this study exposes.

  12. Asymmetrical squaraines for high-performance small-molecule organic solar cells with a short circuit current of over 12 mA cm(-2).

    Science.gov (United States)

    Chen, Yao; Zhu, Youqin; Yang, Daobin; Luo, Qian; Yang, Lin; Huang, Yan; Zhao, Suling; Lu, Zhiyun

    2015-04-11

    An asymmetrical squaraine dye (Py-3) with its two electron-donating aryl groups directly linked to the electron-withdrawing squaric acid core possesses an ideal bandgap of 1.33 eV, together with an intense and broad absorption band in the range 550-950 nm. Hence, the resulting solution-processed solar cells display an impressive Jsc of 12.03 mA cm(-2) and a PCE of 4.35%.

  13. A fast fault protection based on direction of bus-side capacitor discharge current for a high-surety power supply

    DEFF Research Database (Denmark)

    Li, Haijin; Chen, Min; Yang, Boping

    2017-01-01

    A short-circuit fault protection strategy based on the direction of bus-side capacitor discharge current for a high-surety power supply, known as Super Uninterruptable Power Supply (Super UPS), is studied in this paper. It consists of multiple energy sources and storage components. All energy...... strategy is necessary to keep the uninterruptable power for the critical load. In this paper, the characteristics of the short-circuit fault are analyzed first. Then, a fast short-circuit fault locating and isolating strategy based on the direction of the discharge current of the busside capacitors...

  14. Controlled expression of nif and isc iron-sulfur protein maturation components reveals target specificity and limited functional replacement between the two systems.

    Science.gov (United States)

    Dos Santos, Patricia C; Johnson, Deborah C; Ragle, Brook E; Unciuleac, Mihaela-Carmen; Dean, Dennis R

    2007-04-01

    The nitrogen-fixing organism Azotobacter vinelandii contains at least two systems that catalyze formation of [Fe-S] clusters. One of these systems is encoded by nif genes, whose products supply [Fe-S] clusters required for maturation of nitrogenase. The other system is encoded by isc genes, whose products are required for maturation of [Fe-S] proteins that participate in general metabolic processes. The two systems are similar in that they include an enzyme for the mobilization of sulfur (NifS or IscS) and an assembly scaffold (NifU or IscU) upon which [Fe-S] clusters are formed. Normal cellular levels of the Nif system, which supplies [Fe-S] clusters for the maturation of nitrogenase, cannot also supply [Fe-S] clusters for the maturation of other cellular [Fe-S] proteins. Conversely, when produced at the normal physiological levels, the Isc system cannot supply [Fe-S] clusters for the maturation of nitrogenase. In the present work we found that such target specificity for IscU can be overcome by elevated production of NifU. We also found that NifU, when expressed at normal levels, is able to partially replace the function of IscU if cells are cultured under low-oxygen-availability conditions. In contrast to the situation with IscU, we could not establish conditions in which the function of IscS could be replaced by NifS. We also found that elevated expression of the Isc components, as a result of deletion of the regulatory iscR gene, improved the capacity for nitrogen-fixing growth of strains deficient in either NifU or NifS.

  15. Effect of the depth base along the vertical on the electrical parameters of a vertical parallel silicon solar cell in open and short circuit

    Directory of Open Access Journals (Sweden)

    Gokhan Sahin

    2018-03-01

    Full Text Available This article presented a modeling study of effect of the depth base initiating on vertical parallel silicon solar cell’s photovoltaic conversion efficiency. After the resolution of the continuity equation of excess minority carriers, we calculated the electrical parameters such as the photocurrent density, the photovoltage, series resistance and shunt resistances, diffusion capacitance, electric power, fill factor and the photovoltaic conversion efficiency. We determined the maximum electric power, the operating point of the solar cell and photovoltaic conversion efficiency according to the depth z in the base. We showed that the photocurrent density decreases with the depth z. The photovoltage decreased when the depth base increases. Series and shunt resistances were deduced from electrical model and were influenced and the applied the depth base. The capacity decreased with the depth z of the base. We had studied the influence of the variation of the depth z on the electrical parameters in the base. Keywords: Depth base, Conversion efficiency, Electrical parameters, Open circuit, Short circuit

  16. Back-reactions, short-circuits, leaks and other energy wasteful reactions in biological electron transfer: redox tuning to survive life in O(2).

    Science.gov (United States)

    Rutherford, A William; Osyczka, Artur; Rappaport, Fabrice

    2012-03-09

    The energy-converting redox enzymes perform productive reactions efficiently despite the involvement of high energy intermediates in their catalytic cycles. This is achieved by kinetic control: with forward reactions being faster than competing, energy-wasteful reactions. This requires appropriate cofactor spacing, driving forces and reorganizational energies. These features evolved in ancestral enzymes in a low O(2) environment. When O(2) appeared, energy-converting enzymes had to deal with its troublesome chemistry. Various protective mechanisms duly evolved that are not directly related to the enzymes' principal redox roles. These protective mechanisms involve fine-tuning of reduction potentials, switching of pathways and the use of short circuits, back-reactions and side-paths, all of which compromise efficiency. This energetic loss is worth it since it minimises damage from reactive derivatives of O(2) and thus gives the organism a better chance of survival. We examine photosynthetic reaction centres, bc(1) and b(6)f complexes from this view point. In particular, the evolution of the heterodimeric PSI from its homodimeric ancestors is explained as providing a protective back-reaction pathway. This "sacrifice-of-efficiency-for-protection" concept should be generally applicable to bioenergetic enzymes in aerobic environments. Copyright © 2012 Federation of European Biochemical Societies. All rights reserved.

  17. Asbestos as 'toxic short-circuit' optic-fibre for UV within the cell-net: — Likely roles and hazards for secret UV and IR metabolism

    International Nuclear Information System (INIS)

    Traill, Robert R

    2011-01-01

    The most toxic asbestos fibres have widths 250nm-10nm, and this toxicity is 'physical', which could mean either mechanical or optical: Tangling with chromosomes is a mechanical hazard occasionally reported, and fibres 100nm wide — or chrysotile (white asbestos) is >150nm. In both cases, UV A /UV B -transmission would then predominate. (Chrysotile 150nm might be benign — escaping both mechanical and optical!). But what would generate such UV, and why would its transmission be toxic? Thar and Kühl (J.Theor.Biol.:2004) explain that the long mitochondria on microtubules may be able to act as UV-lasers, (and many observers since Gurwitsch 1923 have reported ultraweak UV emissions escaping from all types of living bio-tissue). That all suggests some universal secret role for UV, apparently related to mitosis. Insertion of fibre 'short-circuits' could then cause upsets in mitosis-control, and hence DNA irregularities. Such UV-control could parallel similar lower-powered Infra-Red control-systems (as considered elsewhere for coaxial myelin; or as portrayed by G.Albrecht-Buehler's online animations etc.); and the traditional short mitochondria seem better suited for this IR task.

  18. Stator Vibration Characteristic Identification of Turbogenerator among Single and Composite Faults Composed of Static Air-Gap Eccentricity and Rotor Interturn Short Circuit

    Directory of Open Access Journals (Sweden)

    Yu-Ling He

    2016-01-01

    Full Text Available This paper investigates the radial stator vibration characteristics of turbogenerator under the static air-gap eccentricity (SAGE fault, the rotor interturn short circuit (RISC fault, and the composite faults (CFs composed of SAGE and RISC, respectively. Firstly, the impact of the faulty types on the magnetic flux density (MFD is analyzed, based on which the detailed expressions of the magnetic pull per unit area (MPPUA on the stator under different performing conditions are deduced. Then, numerical FEM simulations based on Ansoft and an experimental study are carried out, taking the SDF-9 type fault simulating generator as the study object. It is shown that SAGE will increase the stator vibration at 2f (f is the electrical frequency which already exists even in normal condition, while RISC and CF will bring in stator vibrations at f, 2f, 3f, and 4f at the same time. The vibration amplitudes under CF are larger than those under RISC. As SAGE increases, the vibration amplitudes of each harmonic component under CF will all be increased, while the development of RISC will decrease the 2nd harmonic vibration but meanwhile increase the 4th harmonic vibration. The achievements of this paper are beneficial for fault identification and condition monitoring of the turbogenerator.

  19. Characterization of the voltage control systems and speed of a synchronous machine of high power for short circuit testing; Caracterizacion de los sistemas de control de voltaje y velocidad de una maquina sincrona de alta potencia para pruebas de corto circuito

    Energy Technology Data Exchange (ETDEWEB)

    Segura Ozuna, Victor Octavio; Hernandez Rodriguez, Isaura Victoria; Alcaide Godinez, Indira Xochiquetzal; Garduno Ramirez, Raul; Montero Cervantes, Julio Cesar [Instituto de Investigaciones Electricas, Cuernavaca, Morelos (Mexico); Ruiz Rodriguez, Genaro; Martinez Torres; Ricardo [CFE-LAPEM, Irapuato, Guanajuato (Mexico)

    2012-07-01

    This paper introduces a characterization of the behavior of the speed and voltage control systems of a special purpose synchronous machine (GCC) based on measuring and monitoring physical signals, and recording of the sampled waveforms. Basically, the GCC supplies the energy to perform high-power short-circuits tests to certify electrical equipment and components, as required by the Comision Federal de Electricidad (CFE) in Mexico. The GCC operates alternately as motor and generator. With the GCC operating as motor, speed control during startup, acceleration, re-acceleration and braking is carried out by a static frequency converter (SFC). Complementary, the voltage controller manipulates excitation power to control terminal voltage when the GCC operates as generator and regulates excitation current when the GCC operates as motor. Compared to conventional voltage regulation systems, which must go off in case of short-circuit, the GCC voltage regulator must keep controlling field excitation to maintain the required line current and terminal voltage during short-circuit tests. Monitoring of physical signals was carried out with a portable data acquisition system based on SCXI and PXI digital platforms. A total of 78 signals were monitored with a 6 kHz sampling rate that was enough to obtain detailed signal waveforms. Data captured was processed and plotted for analysis. The signal graphs show the current real behavior of both, the voltage control system and the speed control system, and constitute a precise characterization of their behavior. [Spanish] Este documento presenta una caracterizacion del comportamiento de los sistemas de control de velocidad y voltaje de una maquina sincrona de proposito especial (GCC) basada en la medicion y monitoreo de senales fisicas, asi como en el registro de las formas de onda muestreadas. Basicamente, la GCC suministra la energia para efectuar pruebas de corto circuito de alta potencia para certificar equipo y componentes

  20. Chinese mitten crab (Eriocheir sinensis) iron-sulphur cluster assembly protein 2 (EsIscA2) is differentially regulated after immune and oxidative stress challenges.

    Science.gov (United States)

    Zhang, Peng; Liu, Yu; Wang, Min; Dong, Miren; Liu, Zhaoqun; Jia, Zhihao; Wang, Weilin; Zhang, Anguo; Wang, Lingling; Song, Linsheng

    2018-07-01

    Iron-sulphur clusters (ISCs), one of the oldest and most versatile cofactors of proteins, are involved in catalysis reactions, electron transport reactions, regulation processes as well as sensing of ambient conditions. Iron-sulphur cluster assembly protein (IscA) is a scaffold protein member of ISC formation system, which plays a significant role in the assembly and maturation process of ISC proteins. In the present study, the cDNA sequence of iron-sulphur cluster assembly protein 2 (designated as EsIscA2) was cloned from Eriocheir sinensis. The open reading frame (ORF) of EsIscA2 was of 507 bp, encoding a peptide of 168 amino acids with a typically conserved Fe-S domain. A tetrameric form was predicated by the SWISS-MODEL prediction algorithm, and three conserved cysteine residues (Cys-93, Cys-158, Cys-160) from each IscA monomer were predicted to form a 'cysteine pocket'. The deduced amino acid sequence of EsIscA2 shared over 50% similarity with that of other IscAs. EsIscA2 was clustered with IscA2 proteins from invertebrates and vertebrates, indicating that the protein was highly conservative in the evolution. rEsIscA2 exhibited a high iron binding affinity in the concentration ranging from 2 to 200 μM. EsIscA2 transcripts were detected in all the tested tissues including gonad, hemocytes, gill, muscle, heart, hepatopancreas and eyestalk, and EsIscA2 protein was detected in the mitochondria of hemocytes. The highest mRNA expression level of EsIscA2 was detected in muscle and hepatopancreas, which was about 34.66-fold (p < 0.05) and 27.07-fold (p < 0.05) of that in hemocytes, respectively. After Aeromonas hydrophila and lipopolysaccharide (LPS) stimulations, the mRNA expression of EsIscA2 in hemocytes was down-regulated and reached the lowest level at 24 h (0.31-fold, p < 0.05) and 48 h (0.29-fold, p < 0.05) compared to control group, respectively. And the expression of EsIscA2 mRNA in hepatopancreas was repressed from 6 h to 48 h post

  1. Um critério para determinar a regulagem da tensão em soldagem MIG/MAG por curto-circuito A criterion to determine voltage setting in short-circuit GMAW

    Directory of Open Access Journals (Sweden)

    Gabriel Maradei Carneiro de Rezende

    2011-06-01

    Full Text Available Este trabalho apresenta um estudo exploratório sobre um critério denominado "Critério Laprosolda para Estabilidade de Transferência em MIG/MAG com curto-circuito", o qual tem por finalidade uma análise quantitativa da regularidade da transferência metálica para regulagem de parâmetros para soldagem MIG/MAG por curto circuito convencional. Inicialmente é apresentado o embasamento para elaboração deste critério. A avaliação da confiabilidade do mesmo foi feita por meio de soldagens e comparações dos resultados com o rendimento de deposição e com as características geométricas do cordão de solda. Para isto, chapas de teste com 3,18 mm de espessura e abertura de raiz de 1 mm entre elas foram soldadas, dentro dos mesmos parâmetros de corrente e velocidade de alimentação, usando arame AWS ER70S-6 de 1,2 mm de diâmetro protegido pela mistura Argônio 85% - Dióxido de Carbono 15%. Para atender a relação proposta, varreu-se a regulagem de tensões de soldagem desde valores muito baixos até muito altos para o que se esperava para esta condição de soldagem. Os resultados confirmam a efetividade do "Índice de Regularidade" como meio de avaliar regulagens de soldagem MIG/MAG visando minimizar respingos e otimizar o acabamento do cordão.This paper presents an exploratory study on a criterion called "Criterion for Stability Laprosolda Transfer in MIG / MAG with short circuit", which aims at a quantitative analysis of the regularity of metal transfer for setting parameters for MIG / MAG conventional in short circuit. Initially it is stated the foundation for development of this criterion. The evaluation of that was made by welding and comparisons of results with the efficiency of deposition and the geometric characteristics of the weld bead. For this, the test plates with 3.18 mm thick and 1 mm gap between them was welded in the same range of current and feeding speed, using wire AWS ER70S-6 1.2 mm of diameter protected by the

  2. New Circuits or Short Circuits?

    Science.gov (United States)

    McLaughlin, Frank

    1967-01-01

    Schools must refuse to contribute to this age of "information overload" and, through an interdisciplinary approach, assist students to become receptive to humane feelings and to understand the complexities of a culture. To these ends, educators must "re-program" the entire educational system by relinquishing their attachment to their own…

  3. Hsc66 substrate specificity is directed toward a discrete region of the iron-sulfur cluster template protein IscU.

    Science.gov (United States)

    Hoff, Kevin G; Ta, Dennis T; Tapley, Tim L; Silberg, Jonathan J; Vickery, Larry E

    2002-07-26

    Hsc66 and Hsc20 comprise a specialized chaperone system important for the assembly of iron-sulfur clusters in Escherchia coli. Only a single substrate, the Fe/S template protein IscU, has been identified for the Hsc66/Hsc20 system, but the mechanism by which Hsc66 selectively binds IscU is unknown. We have investigated Hsc66 substrate specificity using phage display and a peptide array of IscU. Screening of a heptameric peptide phage display library revealed that Hsc66 prefers peptides with a centrally located Pro-Pro motif. Using a cellulose-bound peptide array of IscU we determined that Hsc66 interacts specifically with a region (residues 99-103, LPPVK) that is invariant among all IscU family members. A synthetic peptide (ELPPVKIHC) corresponding to IscU residues 98-106 behaves in a similar manner to native IscU, stimulating the ATPase activity of Hsc66 with similar affinity as IscU, preventing Hsc66 suppression of bovine rhodanese aggregation, and interacting with the peptide-binding domain of Hsc66. Unlike native IscU, however, the synthetic peptide is not bound by Hsc20 and does not synergistically stimulate Hsc66 ATPase activity with Hsc20. Our results indicate that Hsc66 and Hsc20 recognize distinct regions of IscU and further suggest that Hsc66 will not bind LPPVK motifs with high affinity in vivo unless they are in the context of native IscU and can be directed to Hsc66 by Hsc20.

  4. Superconducting dc fault current limiter

    International Nuclear Information System (INIS)

    Cointe, Y.

    2007-12-01

    Within the framework of the electric power market liberalization, DC networks have many interests compared to alternative ones, but their protections need to use new systems. Superconducting fault current limiters enable by an overstepping of the critical current to limit the fault current to a preset value, lower than the theoretical short-circuit current. For these applications, coated conductors offer excellent opportunities. We worked on the implementation of these materials and built a test bench. We carried out limiting experiments to estimate the quench homogeneity at various short-circuit parameters. An important point is the temperature measurement by deposited sensors on the ribbon, results are in good correlation with the theoretical models. Improved quench behaviours for temperatures close to the critical temperature have been confirmed. Our results enable to better understand the limitation mechanisms of coated conductors. (author)

  5. Effect of Short-Circuit Faults in the Back-to-Back Power Electronic Converter and Rotor Terminals on the Operational Behavior of the Doubly-Fed Induction Generator Wind Energy Conversion System

    Directory of Open Access Journals (Sweden)

    Dimitrios G. Giaourakis

    2015-02-01

    Full Text Available This paper deals with the operational behavior of the Doubly-Fed Induction Generator Wind Energy Conversion System under power electronic converter and rotor terminals faulty conditions. More specifically, the effect of the short-circuit fault both in one IGBT of the back-to-back power electronic converter and in rotor phases on the overall system behavior has been investigated via simulation using a system of 2 MW. Finally, the consequences of these faults have been evaluated.

  6. ISC origin times for announced and presumed underground nuclear explosions at several test sites

    International Nuclear Information System (INIS)

    Rodean, H.C.

    1979-01-01

    Announced data for US and French underground nuclear explosions indicate that nearly all detonations have occurred within one or two tenths of a second after the minute. This report contains ISC origin-time data for announced explosions at two US test sites and one French test site, and includes similar data for presumed underground nuclear explosions at five Soviet sites. Origin-time distributions for these sites are analyzed for those events that appeared to be detonated very close to the minute. Particular attention is given to the origin times for the principal US and Soviet test sites in Nevada and Eastern Kazakhstan. The mean origin times for events at the several test sites range from 0.4 s to 2.8 s before the minute, with the earlier mean times associated with the Soviet sites and the later times with the US and French sites. These times indicate lower seismic velocities beneath the US and French sites, and higher velocities beneath the sites in the USSR 9 figures, 8 tables

  7. Study on Oscillations during Short Circuit of MW-Scale IGBT Power Modules by Means of a 6-kA/1.1-kV Nondestructive Testing System

    DEFF Research Database (Denmark)

    Wu, Rui; Diaz Reigosa, Paula; Iannuzzo, Francesco

    2015-01-01

    This paper uses a 6-kA/1.1-kV nondestructive testing system for the analysis of the short-circuit behavior of insulated-gate bipolar transistor (IGBT) power modules. A field-programmable gate array enables the definition of control signals to an accuracy of 10 ns. Multiple 1.7-kV/1-kA IGBT power...... modules displayed severe divergent oscillations, which were subsequently characterized. Experimental tests indicate that nonnegligible circuit stray inductance plays an important role in the divergent oscillations. In addition, the temperature dependence of the transconductance is proposed as an important...

  8. Regulation of the HscA ATPase reaction cycle by the co-chaperone HscB and the iron-sulfur cluster assembly protein IscU.

    Science.gov (United States)

    Silberg, Jonathan J; Tapley, Tim L; Hoff, Kevin G; Vickery, Larry E

    2004-12-24

    The ATPase activity of HscA, a specialized hsp70 molecular chaperone from Escherichia coli, is regulated by the iron-sulfur cluster assembly protein IscU and the J-type co-chaperone HscB. IscU behaves as a substrate for HscA, and HscB enhances the binding of IscU to HscA. To better understand the mechanism by which HscB and IscU regulate HscA, we examined binding of HscB to the different conformational states of HscA and the effects of HscB and IscU on the kinetics of the individual steps of the HscA ATPase reaction cycle. Affinity sensor studies revealed that whereas IscU binds both ADP (R-state) and ATP (T-state) HscA complexes, HscB interacts only with an ATP-bound state. Studies of ATPase activity under single-turnover and rapid mixing conditions showed that both IscU and HscB interact with the low peptide affinity T-state of HscA (HscA++.ATP) and that both modestly accelerate (3-10-fold) the rate-determining steps in the HscA reaction cycle, k(hyd) and k(T-->R). When present together, IscU and HscB synergistically stimulate both k(hyd) (approximately = 500-fold) and k(T-->R) (approximately = 60-fold), leading to enhanced formation of the HscA.ADP-IscU complex (substrate capture). Following ADP/ATP exchange, IscU also stimulates k(R-->T) (approximately = 50-fold) and thereby accelerates the rate at which the low peptide affinity HscA++.ATP T-state is regenerated. Because HscA nucleotide exchange is fast, the overall rate of the chaperone cycle in vivo will be determined by the availability of the IscU-HscB substrate-co-chaperone complex.

  9. Current enhancement in crystalline silicon photovoltaic by low-cost nickel silicide back contact

    KAUST Repository

    Bahabry, R. R.; Gumus, A.; Kutbee, A. T.; Wehbe, N.; Ahmed, S. M.; Ghoneim, M. T.; Lee, K. -T.; Rogers, J. A.; Hussain, M. M.

    2016-01-01

    We report short circuit current (Jsc) enhancement in crystalline silicon (C-Si) photovoltaic (PV) using low-cost Ohmic contact engineering by integration of Nickel mono-silicide (NiSi) for back contact metallization as an alternative to the status quo of using expensive screen printed silver (Ag). We show 2.6 mA/cm2 enhancement in the short circuit current (Jsc) and 1.2 % increment in the efficiency by improving the current collection due to the low specific contact resistance of the NiSi on the heavily Boron (B) doped Silicon (Si) interface.

  10. Current enhancement in crystalline silicon photovoltaic by low-cost nickel silicide back contact

    KAUST Repository

    Bahabry, R. R.

    2016-11-30

    We report short circuit current (Jsc) enhancement in crystalline silicon (C-Si) photovoltaic (PV) using low-cost Ohmic contact engineering by integration of Nickel mono-silicide (NiSi) for back contact metallization as an alternative to the status quo of using expensive screen printed silver (Ag). We show 2.6 mA/cm2 enhancement in the short circuit current (Jsc) and 1.2 % increment in the efficiency by improving the current collection due to the low specific contact resistance of the NiSi on the heavily Boron (B) doped Silicon (Si) interface.

  11. Shaft MisalignmentDetectionusing Stator Current Monitoring

    OpenAIRE

    Alok Kumar Verma, Somnath Sarangi and M.H. Kolekar

    2013-01-01

    This paper inspects the misaligned of shaft by usingdiagnostic medium such as current and vibration.Misalignments in machines can cause decrease inefficiency and in the long-run it may cause failurebecause of unnecessary vibration, stress on motor,bearings and short-circuiting in stator and rotorwindings.In this study, authors investigate the onsetof instability on a shaft mounted on journal bearings.Shaft displacement and stator current samples duringmachine run up under misaligned condition...

  12. The transfer function method for the evaluation of short-circuit tests and on-site diagnostics of power transformers; Die Uebertragungsfunktion als Methode zur Beurteilung der Stosskurzschlusspruefung und Vor-Ort-Isolationsdiagnose

    Energy Technology Data Exchange (ETDEWEB)

    Christian, J.; Feser, K. [Stuttgart Univ. (Germany). Inst. fuer Energieuebertragung und Hochspannungstechnik; Leibfried, T. [Siemens AG, Nuernberg (Germany). Geschaeftsgebiet Leistungstransformatoren; Jaeggi, F. [Aare-Tessin AG fuer Elektrizitaet, Olten (Switzerland)

    1999-03-22

    A short circuit test according to IEC 76-5 was performed on a 125 MVA, 245 kV/53 kV power transformer from the Siemens factory in Nuremberg at the Kema high power laboratory (Arnhem, Netherlands) in March 1997. Thereby, the transfer function method was examined as an additional method for evaluating the short-circuit test. The visual inspection of the transformer after returning to the Nuremberg factory carried out by engineers from Atel and Siemens and representatives of Kema showed no changes of the core and coil assembly. At the Flumenthal substation a second transformer of the same type was installed. Before commissioning, the transfer functions of both transformers have been measured. These measurements provide essential information concerning the comparability of measurements from different transformers and are the basis for measurements to be carried out in the future. (orig.) [Deutsch] Im Maerz 1997 wurde ein 125-MVA-Leistungstranformator aus dem Siemens Transformatorenwerk Nuernberg im Hochleistungslabor der Kema, Arnheim einer Stosskurzschlusspruefung unterzogen. Dabei wurde die Analyse der Uebertragungsfunktion des Transformators als zusaetzliche Methode zur Beurteilung der Stosskurzschlusspruefung untersucht. Der Aktivteil wurde danach im Herstellerwerk begutachtet. Dabei ergaben sich keine Beanstandungen. Im Umspannwerk Flumenthal wurde ein zweiter baugleicher Transformator installiert. Vor der Inbetriebnahme wurden zusaetzliche Vergleichsmessungen an den zwei baugleichen Transformatoren durchgefuehrt. (orig.)

  13. Overcoming Short-Circuit in Lead-Free CH3NH3SnI3 Perovskite Solar Cells via Kinetically Controlled Gas-Solid Reaction Film Fabrication Process.

    Science.gov (United States)

    Yokoyama, Takamichi; Cao, Duyen H; Stoumpos, Constantinos C; Song, Tze-Bin; Sato, Yoshiharu; Aramaki, Shinji; Kanatzidis, Mercouri G

    2016-03-03

    The development of Sn-based perovskite solar cells has been challenging because devices often show short-circuit behavior due to poor morphologies and undesired electrical properties of the thin films. A low-temperature vapor-assisted solution process (LT-VASP) has been employed as a novel kinetically controlled gas-solid reaction film fabrication method to prepare lead-free CH3NH3SnI3 thin films. We show that the solid SnI2 substrate temperature is the key parameter in achieving perovskite films with high surface coverage and excellent uniformity. The resulting high-quality CH3NH3SnI3 films allow the successful fabrication of solar cells with drastically improved reproducibility, reaching an efficiency of 1.86%. Furthermore, our Kelvin probe studies show the VASP films have a doping level lower than that of films prepared from the conventional one-step method, effectively lowering the film conductivity. Above all, with (LT)-VASP, the short-circuit behavior often obtained from the conventional one-step-fabricated Sn-based perovskite devices has been overcome. This study facilitates the path to more successful Sn-perovskite photovoltaic research.

  14. Comportamiento del tiempo de duración, la frecuencia de los cortocircuitos y la conductividad eléctrica durante el reencendido del arco en la soldadura SMAW (AC con electrodos E6013 Behavior of short-circuit frequency and duration time and electrical conductivity on arc turn- on during SMAW (AC with E6013 electrodes

    Directory of Open Access Journals (Sweden)

    Alejandro García Rodríguez

    2009-03-01

    Full Text Available El presente trabajo tiene como objetivo la evaluación del comportamiento del tiempo de duración, la frecuencia de los cortocircuitos y la conductividad durante el reencendido del arco en el proceso de soldadura SMAW (Shielded Metal Arc Welding, con corriente alterna y electrodos E6013. El análisis estadístico no-paramétrico garantiza un procesamiento robusto de los datos, atenuando la influencia de valores atípicos y errores derivados del empleo de aproximaciones a distribuciones continuas conocidas. La mediana y la mediana de la desviación absoluta (MAD, respecto a la mediana de los datos, constituyen los estimadores de localización y dispersión utilizados, respectivamente. El electrodo, en el régimen de 160 A, presenta una mayor estabilidad, en el aporte metálico, dada por el menor valor del MAD promedio del período de cortocircuito (39,36 ms y de la duración del cortocircuito (1,43 ms, reafirmada con la presencia de una mayor conductividad eléctrica durante el reencendido (1766,17x10-3 S·s-1.The objective of this work is the valuation of the behavior of short-circuits frequency and duration time and electrical conductivity on arc reigniting in SMAW (Shielded Metal Arc Welding process with alternate current and E6013 electrodes. The non parametric statistic analysis realize a robust data processing, minimizing the outliers influence and mistakes derivates about employ of approximations to well know continues distributions. The median and the median absolute deviation (MAD respect to median of the data are the localization and dispersion estimators used, respectively. The electrode at 160 A present a better stability on metal transference supported on the most little value of MAD for the period of transference (39,36 ms, and the MAD of the short-circuit duration (1,43 ms, according with the presence of a major electric conductivity during the arc reigniting (1766,17x10-3 S·s-1.

  15. Intrinsic Radiation Source Generation with the ISC Package: Data Comparisons and Benchmarking

    International Nuclear Information System (INIS)

    Solomon, Clell J. Jr.

    2012-01-01

    The characterization of radioactive emissions from unstable isotopes (intrinsic radiation) is necessary for shielding and radiological-dose calculations from radioactive materials. While most radiation transport codes, e.g., MCNP [X-5 Monte Carlo Team, 2003], provide the capability to input user prescribed source definitions, such as radioactive emissions, they do not provide the capability to calculate the correct radioactive-source definition given the material compositions. Special modifications to MCNP have been developed in the past to allow the user to specify an intrinsic source, but these modification have not been implemented into the primary source base [Estes et al., 1988]. To facilitate the description of the intrinsic radiation source from a material with a specific composition, the Intrinsic Source Constructor library (LIBISC) and MCNP Intrinsic Source Constructor (MISC) utility have been written. The combination of LIBISC and MISC will be herein referred to as the ISC package. LIBISC is a statically linkable C++ library that provides the necessary functionality to construct the intrinsic-radiation source generated by a material. Furthermore, LIBISC provides the ability use different particle-emission databases, radioactive-decay databases, and natural-abundance databases allowing the user flexibility in the specification of the source, if one database is preferred over others. LIBISC also provides functionality for aging materials and producing a thick-target bremsstrahlung photon source approximation from the electron emissions. The MISC utility links to LIBISC and facilitates the description of intrinsic-radiation sources into a format directly usable with the MCNP transport code. Through a series of input keywords and arguments the MISC user can specify the material, age the material if desired, and produce a source description of the radioactive emissions from the material in an MCNP readable format. Further details of using the MISC utility can

  16. 7th International Seminar on Climate System and Climate Change(ISCS) through the Eyes of a Trainee

    Institute of Scientific and Technical Information of China (English)

    Karen K.Y.Shum

    2010-01-01

    @@ At the invitation of Dr.Dahe Qin,the president of ISCS and the Co-Chair of IPCC WGI,the Hong Kong Observatory has been obliged to participate and benefit from the International Seminar in Beijing,China on 19-30 July 2010.Seminar topics included atmospheric chemistry and climate effects of aerosol biogeochemical cycles,cryosphere and its role in the climate system and climate change,climate models and its application in climate change research,climate change adaptation and mitigation.Data is a common ground for these multi-disciplinary studies around the globe.

  17. Building and implementing a security certification and accreditation program official (ISC)2 guide to the CAPCM CBK

    CERN Document Server

    Howard, Patrick D

    2004-01-01

    Building and Implementing a Security Certification and Accreditation Program: Official (ISC)2 Guide to the CAP CBK demonstrates the practicality and effectiveness of certification and accreditation (C&A) as a risk management methodology for IT systems in both public and private organizations. It provides security professionals with an overview of C&A components, enabling them to document the status of the security controls of their IT systems, and learn how to secure systems via standard, repeatable processes.  This book consists of four main sections. It begins with a description of what it

  18. Double functions of porous TiO2 electrodes on CH3NH3PbI3 perovskite solar cells: Enhancement of perovskite crystal transformation and prohibition of short circuiting

    Directory of Open Access Journals (Sweden)

    Govindhasamy Murugadoss

    2014-08-01

    Full Text Available In order to analyze the crystal transformation from hexagonal PbI2 to CH3NH3PbI3 by the sequential (two-step deposition process, perovskite CH3NH3PbI3 layers were deposited on flat and/or porous TiO2 layers. Although the narrower pores using small nanoparticles prohibited the effective transformation, the porous-TiO2 matrix was able to help the crystal transformation of PbI2 to CH3NH3PbI3 by sequential two-step deposition. The resulting PbI2 crystals in porous TiO2 electrodes did not deteriorate the photovoltaic effects. Moreover, it is confirmed that the porous TiO2 electrode had served the function of prohibiting short circuits between working and counter electrodes in perovskite solar cells.

  19. Software Project Management Plan for the Integrated Systems Code (ISC) of New Production Reactor -- Modular High Temperature Gas Reactor

    International Nuclear Information System (INIS)

    Taylor, D.

    1990-11-01

    The United States Department of Energy (DOE) has selected the Modular High Temperature Gas-Cooled Reactor (MHTGR) as one of the concepts for the New Production Reactor (NPR). DOE has also established several Technical Working Groups (TWG's) at the national laboratories to provide independent design confirmation of the NPR-MHTGR design. One of those TWG's is concerned with Thermal Fluid Flow (TFF) and analysis methods to provide independent design confirmation of the NPR-MHTGR. Analysis methods are also needed for operational safety evaluations, performance monitoring, sensitivity studies, and operator training. The TFF Program Plan includes, as one of its principal tasks, the development of a computer program (called the Integrated Systems Code, or ISC). This program will provide the needed long-term analysis capabilities for the MHTGR and its subsystems. This document presents the project management plan for development of the ISC. It includes the associated quality assurance tasks, and the schedule and resource requirements to complete these activities. The document conforms to the format of ANSI/IEEE Std. 1058.1-1987. 2 figs

  20. Highly Conformal Ni Micromesh as a Current Collecting Front Electrode for Reduced Cost Si Solar Cell

    DEFF Research Database (Denmark)

    Gupta, Nikita; Rao, K. D. M.; Gupta, Ritu

    2017-01-01

    deposition of Ni wire network on corrugated solar cell, a short circuit current of 33.28 mA/cm2 was obtained in comparison to 20.53 mA/cm2 without the network electrode. On comparing the efficiency with the conventional cells with screen printed electrodes, a 20% increment in efficiency has been observed...

  1. Fault current contribution from VSC-based wind turbines to the grid

    DEFF Research Database (Denmark)

    Valentini, Massimo; Akhmatov, Vladislav; Iov, Florin

    2008-01-01

    current injections during the fault. In this paper an equivalent VSC-based wind turbine model for short-circuit calculations at steady-state conditions is developed and presented. The model is implemented in DigSILENT PowerFactory using the DPL-Programming Language. The developed wind turbine model...

  2. Current limiters

    Energy Technology Data Exchange (ETDEWEB)

    Loescher, D.H. [Sandia National Labs., Albuquerque, NM (United States). Systems Surety Assessment Dept.; Noren, K. [Univ. of Idaho, Moscow, ID (United States). Dept. of Electrical Engineering

    1996-09-01

    The current that flows between the electrical test equipment and the nuclear explosive must be limited to safe levels during electrical tests conducted on nuclear explosives at the DOE Pantex facility. The safest way to limit the current is to use batteries that can provide only acceptably low current into a short circuit; unfortunately this is not always possible. When it is not possible, current limiters, along with other design features, are used to limit the current. Three types of current limiters, the fuse blower, the resistor limiter, and the MOSFET-pass-transistor limiters, are used extensively in Pantex test equipment. Detailed failure mode and effects analyses were conducted on these limiters. Two other types of limiters were also analyzed. It was found that there is no best type of limiter that should be used in all applications. The fuse blower has advantages when many circuits must be monitored, a low insertion voltage drop is important, and size and weight must be kept low. However, this limiter has many failure modes that can lead to the loss of over current protection. The resistor limiter is simple and inexpensive, but is normally usable only on circuits for which the nominal current is less than a few tens of milliamperes. The MOSFET limiter can be used on high current circuits, but it has a number of single point failure modes that can lead to a loss of protective action. Because bad component placement or poor wire routing can defeat any limiter, placement and routing must be designed carefully and documented thoroughly.

  3. CONCEPTS OF IMPROVING CURRENT PROTECTION OF POWER-GRID LINES

    Directory of Open Access Journals (Sweden)

    F. A. Romaniuk

    2015-01-01

    Full Text Available The  6–35  kV  power-grid  current  protection  serves  to  protect  the  transmission  lines against phase-to-phase short-circuits. The major disadvantage of it lies in the relatively large time delays of the last stages especially in the main sections of the grid owing to the stepped relay characteristics as well as a large number of the steps. A full-fledged protection of the 6–35 kV lines against inter-phase short circuits can be provided by the two-stage current protection: the first stage being the current cutoff without any time delay and the second stage – the maximum current protection where the time delay is linear contingent on the distance between the protection placement and the fault-point location. The article introduces the rating formulae for the time delays of the second-stage and their exemplary graphic presentation. The authors offer a variant for solving the problem with computation of the second-stage time delays in those instances where several feeders diverge from the bus bars of the substation located in the end of the protected line.Improving current protections for the 6–35 kV transmission lines with one-end power supply against interphase short-circuits can be based on the collective application of the following principles: accounting for the type and location of the short-circuit which provides for the high-performance cutoff zone instantaneous expansion and its independence on the mode of failure and the grid operation mode. It also allows increase of the last stage sensitiveness towards asymmetrical short-circuits; detection of the short-circuit location only on the results of fault currents measurement which simplifies the protection implementation; realization of the last (second protection stage with linear-dependent time delay which ensures potentiality of its operation speed increase.

  4. Correlation between Self-Citation and Impact Factor in Iranian English Medical Journals in WoS and ISC: A Comparative Approach.

    Science.gov (United States)

    Ghazi Mirsaeid, Seyed Javad; Motamedi, Nadia; Ramezan Ghorbani, Nahid

    2015-09-01

    In this study, the impact of self-citation (Journal and Author) on impact factor of Iranian English Medical journals in two international citation databases, Web of Science (WoS) and Islamic world science citation center (ISC), were compared by citation analysis. Twelve journals in WoS and 26 journals in ISC databases indexed between the years (2006-2009) were selected and compared. For comparison of self-citation rate in two databases, we used Wilcoxon and Mann-whitney tests. We used Pearson test for correlation of self-citation and IF in WoS, and the Spearman's correlation coefficient for the ISC database. Covariance analysis was used for comparison of two correlation tests. P. value was 0.05 in all of tests. There was no significant difference between self-citation rates in two databases (P>0.05). Findings also showed no significant difference between the correlation of Journal self-citation and impact factor in two databases (P=0.526) however, there was significant difference between the author's self-citation and impact factor in these databases (Pcitation in the Impact Factor of WoS was higher than the ISC.

  5. Involvement of the Cra global regulatory protein in the expression of the iscRSUA operon, revealed during studies of tricarballylate catabolism in Salmonella enterica.

    Science.gov (United States)

    Lewis, Jeffrey A; Boyd, Jeffrey M; Downs, Diana M; Escalante-Semerena, Jorge C

    2009-04-01

    In Salmonella enterica, tricarballylate (Tcb) catabolism requires function of TcuB, a membrane-bound protein that contains [4Fe-4S] clusters and heme. TcuB transfers electrons from reduced flavin adenine dinucleotide in the Tcb dehydrogenase (TcuA) to electron acceptors in the membrane. We recently showed that functions needed to assemble [Fe-S] clusters (i.e., the iscRSUA-hscBA-fdx operon) compensate for the lack of ApbC during growth of an apbC strain on Tcb. ApbC had been linked to [Fe-S] cluster metabolism, and we showed that an apbC strain had decreased TcuB activity. Here we report findings that expand our understanding of the regulation of expression of the iscRSUA genes in Salmonella enterica. We investigated why low levels of glucose or other saccharides restored growth of an apbC strain on Tcb. Here we report the following findings. (i) A Cra. (iv) Putative Cra binding sites are present in the regulatory region of the iscRSUA operon. (v) Cra protein binds to all three sites in the iscRSUA promoter region in a concentration-dependent fashion. To our knowledge, this is the first report of the involvement of Cra in [Fe-S] cluster assembly.

  6. Resistive Fault Current Limiter Prototypes: Mechanical and Electrical Analyses

    International Nuclear Information System (INIS)

    Martini, L; Arcos, I; Bocchi, M; Brambilla, R; Dalessandro, R; Frigerio, A; Rossi, V

    2006-01-01

    The problem of excessive short-circuit currents has become an important issue for power systems operators and there are clear indications for a growing interest in superconducting fault current limiter devices for MV and HV grids. In this work, we report on both simulation and electrical testing on single-phase SFCL prototypes developed in the framework of an Italian RTD project to be completed with a 3-phase SFCL unit by the end of 2005

  7. Advantages of the synthetic technique for the conduction of short circuit tests to breakers; Ventajas de la tecnica sintetica para realizar pruebas de corto circuito a interruptores

    Energy Technology Data Exchange (ETDEWEB)

    Sibilski, Henry [Instituto Electrotecnico de Varsovia, Varsovia (Poland); Ochoa Vivanco, Ruben [Instituto de Investigaciones Electricas, Cuernavaca (Mexico)

    1987-12-31

    In this article the operational principle of the synthetic test is described; specifically of the current injection circuit in parallel. Its utilization in the research and development of new breaker models and its wide possibilities regarding its testing characteristics is outlined. Likewise the different tests that can be performed by means of the synthetic technique are described. Finally the importance of the synthetic tests is outlined for the development of own technology in the area of interruption equipment and emphasis is made that in industrialized countries this technique is of common practice. [Espanol] En este articulo se describe el principio de operacion de la prueba sintetica; especificamente del circuito de inyeccion de corriente en paralelo. Se destaca su utilizacion en la investigacion y desarrollo de nuevos modelos de interruptores y sus amplias posibilidades en cuanto a caracteristicas de prueba. Asimismo, se describen las diferentes pruebas que pueden realizarse mediante la tecnica sintetica. Por ultimo, se destaca la importancia de las pruebas sinteticas para el desarrollo de tecnologia propia en el area de equipos de interrupcion, y se hace notar que en paises desarrollados, esta tecnica es practica comun.

  8. Membrane-proximal TRAIL species are incapable of inducing short circuit apoptosis signaling: Implications for drug development and basic cytokine biology.

    Science.gov (United States)

    Tatzel, Katharina; Kuroki, Lindsay; Dmitriev, Igor; Kashentseva, Elena; Curiel, David T; Goedegebuure, S Peter; Powell, Matthew A; Mutch, David G; Hawkins, William G; Spitzer, Dirk

    2016-03-03

    TRAIL continues to garner substantial interest as a recombinant cancer therapeutic while the native cytokine itself serves important tumor surveillance functions when expressed in membrane-anchored form on activated immune effector cells. We have recently developed the genetically stabilized TRAIL platform TR3 in efforts to improve the limitations associated with currently available drug variants. While in the process of characterizing mesothelin-targeted TR3 variants using a single chain antibody (scFv) delivery format (SS-TR3), we discovered that the membrane-tethered cytokine had a substantially increased activity profile compared to non-targeted TR3. However, cell death proceeded exclusively via a bystander mechanism and protected the mesothelin-positive targets from apoptosis rather than leading to their elimination. Incorporation of a spacer-into the mesothelin surface antigen or the cancer drug itself-converted SS-TR3 into a cis-acting phenotype. Further experiments with membrane-anchored TR3 variants and the native cytokine confirmed our hypothesis that membrane-proximal TRAIL species lack the capacity to physically engage their cognate receptors coexpressed on the same cell membrane. Our findings not only provide an explanation for the "peaceful" coexistence of ligand and receptor of a representative member of the TNF superfamily but give us vital clues for the design of activity-enhanced TR3-based cancer therapeutics.

  9. Advantages of the synthetic technique for the conduction of short circuit tests to breakers; Ventajas de la tecnica sintetica para realizar pruebas de corto circuito a interruptores

    Energy Technology Data Exchange (ETDEWEB)

    Sibilski, Henry [Instituto Electrotecnico de Varsovia, Varsovia (Poland); Ochoa Vivanco, Ruben [Instituto de Investigaciones Electricas, Cuernavaca (Mexico)

    1986-12-31

    In this article the operational principle of the synthetic test is described; specifically of the current injection circuit in parallel. Its utilization in the research and development of new breaker models and its wide possibilities regarding its testing characteristics is outlined. Likewise the different tests that can be performed by means of the synthetic technique are described. Finally the importance of the synthetic tests is outlined for the development of own technology in the area of interruption equipment and emphasis is made that in industrialized countries this technique is of common practice. [Espanol] En este articulo se describe el principio de operacion de la prueba sintetica; especificamente del circuito de inyeccion de corriente en paralelo. Se destaca su utilizacion en la investigacion y desarrollo de nuevos modelos de interruptores y sus amplias posibilidades en cuanto a caracteristicas de prueba. Asimismo, se describen las diferentes pruebas que pueden realizarse mediante la tecnica sintetica. Por ultimo, se destaca la importancia de las pruebas sinteticas para el desarrollo de tecnologia propia en el area de equipos de interrupcion, y se hace notar que en paises desarrollados, esta tecnica es practica comun.

  10. pH-induced conformational change of IscU at low pH correlates with protonation/deprotonation of two conserved histidine residues.

    Science.gov (United States)

    Dai, Ziqi; Kim, Jin Hae; Tonelli, Marco; Ali, Ibrahim K; Markley, John L

    2014-08-19

    IscU, the scaffold protein for the major iron-sulfur cluster biosynthesis pathway in microorganisms and mitochondria (ISC pathway), plays important roles in the formation of [2Fe-2S] and [4Fe-4S] clusters and their delivery to acceptor apo-proteins. Our laboratory has shown that IscU populates two distinct, functionally relevant conformational states, a more structured state (S) and a more dynamic state (D), that differ by cis/trans isomerizations about two peptidyl-prolyl peptide bonds [Kim, J. H., Tonelli, M., and Markley, J. L. (2012) Proc. Natl. Acad. Sci. U.S.A., 109, 454-459. Dai Z., Tonelli, M., and Markley, J. L. (2012) Biochemistry, 51, 9595-9602. Cai, K., Frederick, R. O., Kim, J. H., Reinen, N. M., Tonelli, M., and Markley, J. L. (2013) J. Biol. Chem., 288, 28755-28770]. Here, we report our findings on the pH dependence of the D ⇄ S equilibrium for Escherichia coli IscU in which the D-state is stabilized at low and high pH values. We show that the lower limb of the pH dependence curve results from differences in the pKa values of two conserved histidine residues (His10 and His105) in the two states. The net proton affinity of His10 is about 50 times higher and that of His105 is 13 times higher in the D-state than in the S-state. The origin of the high limb of the D ⇄ S pH dependence remains to be determined. These results show that changes in proton inventory need to be taken into account in the steps in iron-sulfur cluster assembly and transfer that involve transitions of IscU between its S- and D-states.

  11. Cadmium uptake capacity of an indigenous cyanobacterial strain, Nostoc entophytum ISC32: new insight into metal uptake in microgravity-simulating conditions.

    Science.gov (United States)

    Alidoust, Leila; Soltani, Neda; Modiri, Sima; Haghighi, Omid; Azarivand, Aisan; Khajeh, Khosro; Shahbani Zahiri, Hossein; Vali, Hojatollah; Akbari Noghabi, Kambiz

    2016-02-01

    Among nine cyanobacterial strains isolated from oil-contaminated regions in southern Iran, an isolate with maximum cadmium uptake capacity was selected and identified on the basis of analysis of morphological criteria and 16S rRNA gene sequence similarity as Nostoc entophytum (with 99% similarity). The isolate was tentatively designated N. entophytum ISC32. The phylogenetic affiliation of the isolates was determined on the basis of their 16S rRNA gene sequence. The maximum amount of Cd(II) adsorbed by strain ISC32 was 302.91 mg g(-1) from an initial exposure to a solution with a Cd(II) concentration of 150 mg l(-1). The cadmium uptake by metabolically active cells of cyanobacterial strain N. entophytum ISC32, retained in a clinostat for 6 days to simulate microgravity conditions, was examined and compared with that of ground control samples. N. entophytum ISC32 under the influence of microgravity was able to take up cadmium at amounts up to 29% higher than those of controls. The activity of antioxidant enzymes including catalase and peroxidase was increased in strain ISC32 exposed to microgravity conditions in a clinostat for 6 days, as catalase activity of the cells was more than three times higher than that of controls. The activity of the peroxidase enzyme increased by 36% compared with that of the controls. Membrane lipid peroxidation was also increased in the cells retained under microgravity conditions, up to 2.89-fold higher than in non-treated cells. Images obtained using scanning electron microscopy showed that cyanobacterial cells form continuous filaments which are drawn at certain levels, while the cells placed in a clinostat appeared as round-shaped, accumulated together and distorted to some extent.

  12. The Effect of UV-Irradiation (under Short-Circuit Condition) on Dye-Sensitized Solar Cells Sensitized with a Ru-Complex Dye Functionalized with a (diphenylamino)Styryl-Thio phen Group

    International Nuclear Information System (INIS)

    Nonomura, K.; Xu, Y.; Marinado, T.; Hagberg, D.P.; Sun, L.; Boschloo, G.; Hagfeldt, A.; Rong Zhang, R.; Boschloo, G.; Hagfeldt, A.

    2009-01-01

    A new ruthenium complex, cis-di(thiocyanato)(2,2'-bipyridine-4,4'-dicarboxylic acid)(4,4'-bis (2-(5-(2-(4-diphenylaminophenyl)ethenyl) -thiophen-2-yl)ethenyl)-2,2'-bipyridine)ruthenium(II) (named E322) has been synthesized for use in dye-sensitized solar cells (DSCs). Higher extinction coefficient and a broader absorption compared to the standard Ru-dye, N719, were aimed. DSCs were fabricated with E322, and the efficiency was 0.12% initially. (4.06% for N719, as reference). The efficiency was enhanced to 1.83% by exposing the cell under simulated sunlight containing UV-irradiation at short-circuit condition. The reasons of this enhancement are (1) enhanceing electron injection from sensitizer to TiO 2 following a shift toward positive potentials of the conduction band of TiO 2 by the adsorption of protons or cations from the sensitizer, or from the redox electrolyte and (2) improving the regeneration reaction of the oxidized dye by the redox electrolyte by the dissolution of aggregated dye from the surface of TiO 2 following the treatment.

  13. The short circuit instability in protoplanetary disks

    DEFF Research Database (Denmark)

    Hubbard, A.; McNally, C.P.; Mac Low, M.M.

    2013-01-01

    We introduce a magneto-hydrodynamic instability which occurs, among other locations, in the inner, hot regions of protoplanetary disks, and which alters the way in which resistive dissipation of magnetic energy into heat proceeds. This instability can be likened to both an electrical short circui...

  14. Don't "Short Circuit" STEM Instruction

    Science.gov (United States)

    Bruxvoort, Crystal; Jadrich, James

    2016-01-01

    Science students should undertake engineering design projects and carry out scientific investigations, as recommended by the "Next Generation Science Standards" (NGSS Lead States 2013). However, studies show that students misconstrue the goals of science and engineering and are uncertain about their respective practices (Gilbert and Wade…

  15. Simon short circuit effect in ECRIS

    NARCIS (Netherlands)

    Drentje, AG; Wolters, U; Nadzeyka, A; Meyer, D; Wiesemann, K

    The plasma confinement within an electron cyclotron resonance ion source significantly influences the charge state distribution and hence the performance of the source. The different axial and radial diffusion processes govern the confinement time. In many experiments it has been shown that

  16. Current redistribution in cables made of insulated, soldered, or oxidized strands

    International Nuclear Information System (INIS)

    Turck, B.

    1979-07-01

    Current redistributions are compared in cables made of insulated strands, soldered, or oxidized strands and insulated strands with periodic joints. After discussing the different current redistributions in the cases of a rapidly changing current and a dc current, several particular situations are investigated: what happens if a strand is broken, or if a local normal zone appears that does not affect all the strands equally, the detection of this normal zone, and the influence of short circuits between strands

  17. An Improved Current Controller to ensure the robust performance of grid-connected converters under weak grid conditions

    DEFF Research Database (Denmark)

    Khazraj, Hesam; Silva, Filipe Miguel Faria da; Bak, Claus Leth

    2016-01-01

    Voltage Source Converters (VSCs) operating in very weak grids with low Short Circuit Ratio (SCR) are known to meet stability challenges. This article investigates instability of a grid connected current-controlled converter under weak grid conditions, which is often attributed to the dynamic...

  18. Balancing High Open Circuit Voltage over 1.0 V and High Short Circuit Current in Benzodithiophene-Based Polymer Solar Cells with Low Energy Loss: A Synergistic Effect of Fluorination and Alkylthiolation

    DEFF Research Database (Denmark)

    Du, Zhengkun; Bao, Xichang; Li, Yonghai

    2018-01-01

    Based on the most recently significant progress within the last one year in organic photovoltaic research from either alkylthiolation or fluorination on benzo[1,2-b: 4,5-b'] dithiophene moiety for high efficiency polymer solar cells (PSCs), two novel simultaneously fluorinated and alkylthiolated ...

  19. Global regulator IscR positively contributes to antimonite resistance and oxidation in Comamonas testosteroni S44

    DEFF Research Database (Denmark)

    Liu, Hongliang; Zhuang, Weiping; Zhang, Shengzhe

    2015-01-01

    Antimonial compounds can be found as a toxic contaminant in the environment. Knowledge on mechanisms of microbial Sb oxidation and its role in microbial tolerance are limited. Previously, we found that Comamonas testosteroni S44 was resistant to multiple heavy metals and was able to oxidize the t...... and Sb(III) oxidation via Fe-S cluster biogenesis and oxidative stress protection. Bacterial Sb(III) oxidation is a detoxification reaction.......Antimonial compounds can be found as a toxic contaminant in the environment. Knowledge on mechanisms of microbial Sb oxidation and its role in microbial tolerance are limited. Previously, we found that Comamonas testosteroni S44 was resistant to multiple heavy metals and was able to oxidize...... the toxic antimonite [Sb(III)] to the much less toxic antimonate [Sb(V)]. In this study, transposon mutagenesis was performed in C. testosteroni S44 to isolate genes responsible for Sb(III) resistance and oxidation. An insertion mutation into iscR, which regulates genes involved in the biosynthesis of Fe...

  20. Superconducting fault current limiter using high-resistive YBCO tapes

    Energy Technology Data Exchange (ETDEWEB)

    Yazawa, T. [Power and Industrial System R and D Center, Toshiba Corporation, 2-4 Suehiro, Tsurumi, Yokohama 230-0045 (Japan)], E-mail: takashi.yazawa@toshiba.co.jp; Koyanagi, K.; Takahashi, M.; Ono, M.; Toba, K.; Takigami, H.; Urata, M. [Power and Industrial System R and D Center, Toshiba Corporation, 2-4 Suehiro, Tsurumi, Yokohama 230-0045 (Japan); Iijima, Y.; Saito, T. [Fujikura Ltd., 1-5-1 Kiba, Koto, Tokyo 135-0042 (Japan); Ameniya, N. [Yokohama National University, 79-1 Tokiwadai, Hodogaya, Yokohama 240-8501 (Japan); Shiohara, Y. [Superconductivity Research Laboratory, ISTEC, 1-10-13 Shinonome, Koto, Tokyo 135-0062 (Japan)

    2008-09-15

    One of the programs in the Ministry of Economy and Trade and Industry (METI) project regarding R and D on YBCO conductor is to evaluate the applicability of the developed conductor toward several applications. This paper focuses on a fault current limiter (FCL) as one of the expected power applications. YBCO tape conductors with ion beam assisted deposition (IBAD) substrate are used in this work. In order to obtain high resistance of the conductor, which is preferable to an FCL, the thickness of the protecting layer made of silver was decreased as possible. Then high-resistive metal stabilizing layer is attached on the silver layer to improve stability. Obtaining the relevant current limiting performance on short sample experiments, model coils were developed to aim the 6.6 kV-class FCL. Short circuit experiments were implemented with a short circuit generator. The coil successfully restricted the short circuit current over 17 kA to about 700 A by the applied voltage of 3.8 kV, which is nominal phase-to-ground voltage. The experimental results show good agreement with computer analyses and show promising toward the application.

  1. A Regulatory Circuit Composed of a Transcription Factor, IscR, and a Regulatory RNA, RyhB, Controls Fe-S Cluster Delivery

    Directory of Open Access Journals (Sweden)

    Pierre Mandin

    2016-09-01

    Full Text Available Fe-S clusters are cofactors conserved through all domains of life. Once assembled by dedicated ISC and/or SUF scaffolds, Fe-S clusters are conveyed to their apo-targets via A-type carrier proteins (ATCs. Escherichia coli possesses four such ATCs. ErpA is the only ATC essential under aerobiosis. Recent studies reported a possible regulation of the erpA mRNA by the small RNA (sRNA RyhB, which controls the expression of many genes under iron starvation. Surprisingly, erpA has not been identified in recent transcriptomic analysis of the iron starvation response, thus bringing into question the actual physiological significance of the putative regulation of erpA by RyhB. Using an sRNA library, we show that among 26 sRNAs, only RyhB represses the expression of an erpA-lacZ translational fusion. We further demonstrate that this repression occurs during iron starvation. Using mutational analysis, we show that RyhB base pairs to the erpA mRNA, inducing its disappearance. In addition, IscR, the master regulator of Fe-S homeostasis, represses expression of erpA at the transcriptional level when iron is abundant, but depleting iron from the medium alleviates this repression. The conjunction of transcriptional derepression by IscR and posttranscriptional repression by RyhB under Fe-limiting conditions is best described as an incoherent regulatory circuit. This double regulation allows full expression of erpA at iron concentrations for which Fe-S biogenesis switches from the ISC to the SUF system. We further provide evidence that this regulatory circuit coordinates ATC usage to iron availability.

  2. ISC1-dependent metabolic adaptation reveals an indispensable role for mitochondria in induction of nuclear genes during the diauxic shift in Saccharomyces cerevisiae.

    Science.gov (United States)

    Kitagaki, Hiroshi; Cowart, L Ashley; Matmati, Nabil; Montefusco, David; Gandy, Jason; de Avalos, Silvia Vaena; Novgorodov, Sergei A; Zheng, Jim; Obeid, Lina M; Hannun, Yusuf A

    2009-04-17

    Growth of Saccharomyces cerevisiae following glucose depletion (the diauxic shift) depends on a profound metabolic adaptation accompanied by a global reprogramming of gene expression. In this study, we provide evidence for a heretofore unsuspected role for Isc1p in mediating this reprogramming. Initial studies revealed that yeast cells deleted in ISC1, the gene encoding inositol sphingolipid phospholipase C, which resides in mitochondria in the post-diauxic phase, showed defective aerobic respiration in the post-diauxic phase but retained normal intrinsic mitochondrial functions, including intact mitochondrial DNA, normal oxygen consumption, and normal mitochondrial polarization. Microarray analysis revealed that the Deltaisc1 strain failed to up-regulate genes required for nonfermentable carbon source metabolism during the diauxic shift, thus suggesting a mechanism for the defective supply of respiratory substrates into mitochondria in the post-diauxic phase. This defect in regulating nuclear gene induction in response to a defect in a mitochondrial enzyme raised the possibility that mitochondria may initiate diauxic shift-associated regulation of nucleus-encoded genes. This was established by demonstrating that in respiratory-deficient petite cells these genes failed to be up-regulated across the diauxic shift in a manner similar to the Deltaisc1 strain. Isc1p- and mitochondrial function-dependent genes significantly overlapped with Adr1p-, Snf1p-, and Cat8p-dependent genes, suggesting some functional link among these factors. However, the retrograde response was not activated in Deltaisc1, suggesting that the response of Deltaisc1 cannot be simply attributed to mitochondrial dysfunction. These results suggest a novel role for Isc1p in allowing the reprogramming of gene expression during the transition from anaerobic to aerobic metabolism.

  3. Analysis on current limiting characteristics of a transformer type SFCL with two triggering current levels

    International Nuclear Information System (INIS)

    Lim, Sung-Hun; Ko, Seckcheol; Han, Tae-Hee

    2013-01-01

    Highlights: ► We suggested the transformer type SFCL with two triggering current levels. ► The short-circuit tests for the suggested SFCL was executed. ► The fault angle as the fault conditions to verify its operation was selected. ► The usefulness of the suggested SFCL was confirmed through the short-circuit test. -- Abstract: In this paper, the transformer type superconducting fault current limiter (SFCL) with two triggering current levels was suggested and its current limiting characteristics were analyzed. The structure of the suggested transformer type SFCL with two triggering current levels largely consists of two parts. One is the transformer with two magnetically coupled coils, which correspond to the primary winding and the secondary one connected with one high-T C superconducting (HTSC) element. The other is third coil, or, another secondary winding with one HTSC element, which is wound on the same iron core together with two coils. This suggested transformer type SFCL can limit the fault current by generating its limiting impedance with two different amplitudes, which are dependent on the initial amplitude of the fault current in case of the fault occurrence. To confirm the usefulness of the proposed SFCL, the current limiting tests of the SFCL according to the fault angle, one of the effective fault conditions to affect the amplitude of the initial fault current, were carried out and its effective limiting operations were discussed

  4. A Regulatory Circuit Composed of a Transcription Factor, IscR, and a Regulatory RNA, RyhB, Controls Fe-S Cluster Delivery.

    Science.gov (United States)

    Mandin, Pierre; Chareyre, Sylvia; Barras, Frédéric

    2016-09-20

    Fe-S clusters are cofactors conserved through all domains of life. Once assembled by dedicated ISC and/or SUF scaffolds, Fe-S clusters are conveyed to their apo-targets via A-type carrier proteins (ATCs). Escherichia coli possesses four such ATCs. ErpA is the only ATC essential under aerobiosis. Recent studies reported a possible regulation of the erpA mRNA by the small RNA (sRNA) RyhB, which controls the expression of many genes under iron starvation. Surprisingly, erpA has not been identified in recent transcriptomic analysis of the iron starvation response, thus bringing into question the actual physiological significance of the putative regulation of erpA by RyhB. Using an sRNA library, we show that among 26 sRNAs, only RyhB represses the expression of an erpA-lacZ translational fusion. We further demonstrate that this repression occurs during iron starvation. Using mutational analysis, we show that RyhB base pairs to the erpA mRNA, inducing its disappearance. In addition, IscR, the master regulator of Fe-S homeostasis, represses expression of erpA at the transcriptional level when iron is abundant, but depleting iron from the medium alleviates this repression. The conjunction of transcriptional derepression by IscR and posttranscriptional repression by RyhB under Fe-limiting conditions is best described as an incoherent regulatory circuit. This double regulation allows full expression of erpA at iron concentrations for which Fe-S biogenesis switches from the ISC to the SUF system. We further provide evidence that this regulatory circuit coordinates ATC usage to iron availability. Regulatory small RNAs (sRNAs) have emerged as major actors in the control of gene expression in the last few decades. Relatively little is known about how these regulators interact with classical transcription factors to coordinate genetic responses. We show here how an sRNA, RyhB, and a transcription factor, IscR, regulate expression of an essential gene, erpA, in the bacterium E

  5. Estudo de alguns parâmetros básicos da soldagem GMAW com transferência por curto-circuito Evaluation of basic parameters of short-circuit GMA welding

    Directory of Open Access Journals (Sweden)

    Paulo J. Modenesi

    2011-03-01

    these limitations of GMA welding, the authors of the present work have been working on the development of a mathematical model to simulate the variation of operational and electrical parameters during welding. This paper aims to evaluate methodologies to determine two key variables of this model (the electrode electrical resistivity and the sum of the voltage drops in the arc anode and cathode regionsin short-circuit welding. Experimental trials were performed in a mechanized jig by depositing bead-onplate welds on low-carbon steel bars. Methodologies to evaluate those variables were developed based in proposals from the literature. Experimental details of these methodologies are analyzed and their results are compared to results from the literature. These procedures are evaluated, compared with data from the literature and new procedures are proposed to estimate those parameters and the contact resistance between the contact tip and the electrode. Results suggest values between 6 and 9 Ω for this last parameter.

  6. Definition of the electric requirements for the equipment associated to the limiter reactor on a 550 kV line occurring from manoeuvres under short circuits; Definicao dos requisitos eletricos dos equipamentos associados ao reator limitador em 550 kV, em decorrencia de manobras sob curtos-circuitos

    Energy Technology Data Exchange (ETDEWEB)

    Machado Junior, Camilo; Furuoka, Nita; Rose, Eber Havila [ELETRONORTE, Brasilia, DF (Brazil)]. E-mail: eber@eln.gov.br; Violin, Airton; Martinez, Manuel Luis Barreira [Escola Federal de Engenharia de Itajuba (EFEI), MG (Brazil). Inst. de Engenharia Eletrica. Lab. de Alta Tensao; Saraiva, Carlos Alberto Moura [Consorcio THEMAG-ENGEVIX, Sao Paulo, SP (Brazil)

    2001-07-01

    This paper presents the ascertaining based on the TRT study results performed to the definition of the new circuit breakers characteristics for the second stage of the Tucurui hydroelectric power plant, placed at the northern Brazil and with final configuration of two power houses and two air isolated substations, amounting 9 GVA. To reduce the short-circuit level to satisfactory values series reactors were used among the 550 kV substations. The result of the studies associated to the circuit breaker specifications are presented.

  7. MODELACIÓN DE LA DISPERSIÓN DE ANHÍDRIDO SULFUROSO EN LA COMUNA DE LA COMUNA DE PUCHUNCAVÍ UTILIZANDO EL PROGRAMA ISC3 MODELING OF THE SULFUR DIOXIDE DISPERSION IN THE PUCHUNCAVI CITY USING THE PROGRAM ISC3

    Directory of Open Access Journals (Sweden)

    Pamela Lazo

    2006-12-01

    Full Text Available El presente trabajo evalúa el modelo de dispersión atmosférica ISC3 en la comuna de Puchuncaví, modelando las emisiones de SO 2 provenientes del Complejo Industrial Las Ventanas en las cinco estaciones que conforman la red de calidad del aire de este complejo. Se modelan concentraciones horarias y promedio de 24 horas para los años 2003 y 2004, minimizando los errores sistemáticos mediante la aplicación del filtro Kalman. Se evalúa el desempeño del modelo mediante una serie de herramientas estadísticas. Se realiza un análisis de sensibilidad de la variación en la tasa de emisión de SO 2 , velocidad y dirección del viento, observando que el modelo es sensible a estos factores y siendo una de las causas de los errores obtenidos en cuatro de las cinco estaciones de calidad del aire del complejo industrial. Se concluye que el modelo ISC3 predice con menor error en la dirección del viento predominante en frecuencia, entregando un mejor ajuste para velocidades de viento elevadas en direcciones de viento menores en frecuencia. Se observa que el filtro de Kalman mejora el desempeño del modelo ISC3 entregando resultados con menor error en las cinco estaciones de calidad del aire.The present work evaluates the atmospheric dispersion model ISC3 in Puchuncaví, Chile, modelling the emissions of SO 2 coming from the five stations that make up the air quality network in the industrial complex of Ventanas. 24 hour average concentrations for the years 2003 and 2004 were modelled, systematic errors being diminished by using a Kalman filter. The performance of the model is evaluated using a series of statistic tools. An analysis of the sensitivity of the SO 2 rate of emission, speed and wind direction variation is made, noting that the model is sensible to these factors, being this one of the causes of the errors found in four of the five stations that measured the quality of the air. It is concluded that the Kalman filter improves model ISC3

  8. Effects of current stress and thermal storage on polymeric heterojunction P3HT:PCBM solar cell

    DEFF Research Database (Denmark)

    Rizzo, Antonio; Cester, Andrea; Torto, Lorenzo

    2016-01-01

    We subjected P3HT:PCBM solar cells to electrical constant current stress and thermal storage. We employed the impedance spectroscopy technique combined to conventional DC measurements for device characterization during all stresses. We identified and separated different contributions affecting...... the open circuit voltage and short circuit current. Several mechanisms are behind these changes during the stresses; in particular, we underlined the exciton recombination rate and the variation of the built-in voltage....

  9. STUDI ANALISIS KOORDINASI OVER CURRENT RELAY (OCR) DAN GROUND FAULT RELAY (GFR) PADA RECLOSER DI SALURAN PENYULANG PENEBEL

    OpenAIRE

    I Dewa Gde Agung Budhi Udiana; I G Dyana Arjana; Tjok Gede Indra Partha

    2017-01-01

    Short circuit causing over current problem and can might causing interference of the equipment performance such as distribution transformers also causing widespread disruption occurred. In resolving such interference is required as protection system on the distribution system. Seeing all above is needed coordination between the supporting component of the protection system which is consisted of Over Current Relay (OCR) and Ground Fault Relay (GFR). The research was conducted at PT. PLN (Perse...

  10. Analysis on fault current limiting and recovery characteristics of a flux-lock type SFCL with an isolated transformer

    International Nuclear Information System (INIS)

    Ko, Seckcheol; Lim, Sung-Hun; Han, Tae-Hee

    2013-01-01

    Highlights: ► Countermeasure to reduce the power burden of HTSC element consisting of the flux-lock type SFCL was studied. ► The power burden of HTSC element could be decreased by using the isolated transformer. ► The SFCL designed with the additive polarity winding could be confirmed to cause less power burden of the HTSC element. -- Abstract: The flux-lock type superconducting fault current limiter (SFCL) can quickly limit the fault current shortly after the short circuit occurs and recover the superconducting state after the fault removes. However, the superconducting element comprising the flux-lock type SFCL can be destructed when the high fault current passes through the SFCL. Therefore, the countermeasure to control the fault current and protect the superconducting element is required. In this paper, the flux-lock type SFCL with an isolated transformer, which consists of two parallel connected coils on an iron core and the isolated transformer connected in series with one of two coils, was proposed and the short-circuit experimental device to analyze the fault current limiting and the recovery characteristics of the flux-lock type SFCL with the isolated transformer were constructed. Through the short-circuit tests, the flux-lock type SFCL with the isolated transformer was confirmed to perform more effective fault current limiting and recovery operation compared to the flux-lock type SFCL without the isolated transformer from the viewpoint of the quench occurrence and the recovery time of the SFCL

  11. Soft X-ray beam induced current technique

    Energy Technology Data Exchange (ETDEWEB)

    Watts, B; Ade, H [Department of Physics, North Carolina State University, Raleigh, NC 27695 (United States); Queen, D; Hellman, F [Department of Physics, University of California, Berkeley, CA 94720 (United States); Kilcoyne, A L D; Tyliszczak, T, E-mail: benjamin.watts@gmail.co [Advanced Light Source, Lawrence Berkeley Nat. Lab., Berkeley, CA 94720 (United States)

    2009-09-01

    Direct mapping of the charge transport efficiency of polymer solar cell devices using a soft X-ray beam induced current (SoXBIC) method is described. By fabricating a polymer solar cell on an x-ray transparent substrate, we demonstrate the ability to map polymer composition and nanoscale structure within an operating solar cell device and to simultaneously measure the local charge transport efficiency via the short-circuit current. A simple model is calculated and compared to experimental SoXBIC data of a PFB:F8BT bulk-heterojunction device in order to gain greater insight into the device operation and physics.

  12. Development of 6.6 kV/600 A superconducting fault current limiter using coated conductors

    Energy Technology Data Exchange (ETDEWEB)

    Yazawa, T., E-mail: takashi.yazawa@toshiba.co.j [Toshiba Corporation, Power Systems Company (Japan); Koyanagi, K.; Takahashi, M.; Toba, K.; Takigami, H.; Urata, M. [Toshiba Corporation, Power Systems Company (Japan); Iijima, Y.; Saitoh, T. [Fujikura Ltd. (Japan); Amemiya, N. [Superconductivity Research Laboratory, ISTEC (Japan); Shiohara, Y. [Department of Electrical Engineering, Kyoto University (Japan); Ito, T. [Tokyo Gas Co., Ltd. (Japan)

    2009-10-15

    As one of the programs in the Ministry of Economy, Trade and Industry (METI) project regarding R and D on superconducting coated conductor, three-phase superconducting fault current limiter (SFCL) for 6.6 kV application was developed and successfully tested. The developed SFCL was mainly comprised three-phase set of current limiting coils installed in a sub-cooled nitrogen cryostat with a GM cryocooler, circuit breakers and a sequence circuit. The whole system was installed in a cubicle. Two tapes of coated conductor were wound in parallel in each coil to obtain the rated current of 72 A rms. After developing the whole SFCL system, short circuit experiments were implemented with a short circuit generator. In a three-line ground fault test, the SFCL successfully restricted the prospected short circuit current over 1.6 kA to about 800 A by the applied voltage of 6.6 kV. The SFCL was installed in a user field and connected with a gas engine generator, followed by a consecutive operation. In this program, 600 A class FCL coil, with which four coated conductor tapes were wound, was also developed. The coil showed sufficiently low AC loss at the rated current. With these results, the program attained the planned target of the fundamentals for the 6.6 kV/600 A SFCL.

  13. ISC High Performance 2016 International Workshops, ExaComm, E-MuCoCoS, HPC-IODC, IXPUG, IWOPH, P^3MA, VHPC, WOPSSS

    CERN Document Server

    Mohr, Bernd; Kunkel, Julian M

    2016-01-01

    This book constitutes revised selected papers from 7 workshops that were held in conjunction with the ISC High Performance 2016 conference in Frankfurt, Germany, in June 2016. The 45 papers presented in this volume were carefully reviewed and selected for inclusion in this book. They stem from the following workshops: Workshop on Exascale Multi/Many Core Computing Systems, E-MuCoCoS; Second International Workshop on Communication Architectures at Extreme Scale, ExaComm; HPC I/O in the Data Center Workshop, HPC-IODC; International Workshop on OpenPOWER for HPC, IWOPH; Workshop on the Application Performance on Intel Xeon Phi – Being Prepared for KNL and Beyond, IXPUG; Workshop on Performance and Scalability of Storage Systems, WOPSSS; and International Workshop on Performance Portable Programming Models for Accelerators, P3MA.

  14. ISC High Performance 2017 International Workshops, DRBSD, ExaComm, HCPM, HPC-IODC, IWOPH, IXPUG, P^3MA, VHPC, Visualization at Scale, WOPSSS

    CERN Document Server

    Yokota, Rio; Taufer, Michela; Shalf, John

    2017-01-01

    This book constitutes revised selected papers from 10 workshops that were held as the ISC High Performance 2017 conference in Frankfurt, Germany, in June 2017. The 59 papers presented in this volume were carefully reviewed and selected for inclusion in this book. They stem from the following workshops: Workshop on Virtualization in High-Performance Cloud Computing (VHPC) Visualization at Scale: Deployment Case Studies and Experience Reports International Workshop on Performance Portable Programming Models for Accelerators (P^3MA) OpenPOWER for HPC (IWOPH) International Workshop on Data Reduction for Big Scientific Data (DRBSD) International Workshop on Communication Architectures for HPC, Big Data, Deep Learning and Clouds at Extreme Scale Workshop on HPC Computing in a Post Moore's Law World (HCPM) HPC I/O in the Data Center ( HPC-IODC) Workshop on Performance and Scalability of Storage Systems (WOPSSS) IXPUG: Experiences on Intel Knights Landing at the One Year Mark International Workshop on Communicati...

  15. Harmonic current control for LCL-filtered VSCs connected to ultra-weak grids

    DEFF Research Database (Denmark)

    Wang, Xiongfei; Yang, Dongsheng; Blaabjerg, Frede

    2017-01-01

    This paper addresses the harmonic current control for LCL-filtered Voltage-Source Converters (VSCs) connected to ultra-weak (high-impedance) grids. It is shown that the harmonic current controllers tend to be unstable as the Short-Circuit Ratio (SCR) of the system reduces. An active stabilizing...... control scheme is thus proposed by feeding back the filter capacitor voltage and the converter-side current. The method not only stabilizes the harmonic current control with a wide range of SCR values, but also mitigates harmonic distortions in the grid-side current of the VSC. The stabilizing mechanism...

  16. Symmetrical and Unsymmetrical Fault Currents of a Wind Power Plant: Preprint

    Energy Technology Data Exchange (ETDEWEB)

    Gevorgian, V.; Singh, M.; Muljadi, E.

    2011-12-01

    This paper investigates the short-circuit behavior of a wind power plant for different types of wind turbines. Both symmetrical faults and unsymmetrical faults are investigated. The size of wind power plants (WPPs) keeps getting bigger and bigger. The number of wind plants in the U.S. has increased very rapidly in the past 10 years. It is projected that in the U.S., the total wind power generation will reach 330 GW by 2030. As the importance of WPPs increases, planning engi-neers must perform impact studies used to evaluate short-circuit current (SCC) contribution of the plant into the transmission network under different fault conditions. This information is needed to size the circuit breakers, to establish the proper sys-tem protection, and to choose the transient suppressor in the circuits within the WPP. This task can be challenging to protec-tion engineers due to the topology differences between different types of wind turbine generators (WTGs) and the conventional generating units. This paper investigates the short-circuit behavior of a WPP for different types of wind turbines. Both symmetrical faults and unsymmetrical faults are investigated. Three different soft-ware packages are utilized to develop this paper. Time domain simulations and steady-state calculations are used to perform the analysis.

  17. Determination of over current protection thresholds for class D audio amplifiers

    DEFF Research Database (Denmark)

    Nyboe, Flemming; Risbo, L; Andreani, Pietro

    2005-01-01

    Monolithic class-D audio amplifiers typically feature built-in over current protection circuitry that shuts down the amplifier in case of a short circuit on the output speaker terminals. To minimize cost, the threshold at which the device shuts down must be set just above the maximum current...... that can flow in the loudspeaker during normal operation. The current required is determined by the complex loudspeaker impedance and properties of the music signals played. This work presents a statistical analysis of peak output currents when playing music on typical loudspeakers for home entertainment....

  18. Superconductive AC current limiter

    International Nuclear Information System (INIS)

    Bekhaled, M.

    1987-01-01

    This patent describes an AC current limiter for a power transport line including a power supply circuit and feeding a load circuit via an overload circuit-breaker member. The limiter comprises a transformer having a primary winding connected in series between the power supply circuit and the load circuit and at least one secondary winding of superconductor material contained in a cryogenic enclosure and short-circuited on itself. The leakage reactance of the transformer as seen from the primary winding is low, and the resistance of the at least one secondary winding when in the non-superconducting state and as seen from the primary is much greater than the nominal impedance of the transformer. The improvement whereby the at least one secondary winding of the transformer comprises an active winding in association with a set of auxiliary windings. The set of auxiliary windings is constituted by an even number of series-connected auxiliary windings wound in opposite directions, with the total number of turns in one direction being equal to the total number of turns in the opposite direction, and with the thermal capacity of the secondary winding as a whole being sufficiently high to limit the expansion thereof to a value which remains small during the time it takes the circuit-breaking member to operate

  19. Fullerene solubility-current density relationship in polymer solar cells

    International Nuclear Information System (INIS)

    Renz, Joachim A.; Gobsch, Gerhard; Hoppe, Harald; Troshin, Pavel A.; Razumov, V.F.

    2008-01-01

    During the last decade polymer solar cells have undergone a steady increase in overall device efficiency. To date, essential efficiency improvements of polymer-fullerene solar cells require the development of new materials. Whilst most research efforts aim at an improved or spectrally extended absorption of the donor polymer, not so much attention has been paid to the fullerene properties themselves. We have investigated a number of structurally related fullerenes, in order to study the relationship between chemical structure and resulting polymer-fullerene bulk heterojunction photovoltaic properties. Our study reveals a clear connection between the fullerene solubility as material property on one hand and the solar cells short circuit photocurrent on the other hand. The tendency of the less soluble fullerene derivates to aggregate was accounted for smaller current densities in the respective solar cells. Once a minimum solubility of approx. 25 mg/ml in chlorobenzene was overcome by the fullerene derivative, the short circuit current density reached a plateau, of about 8-10 mA/cm 2 . Thus the solubility of the fullerene derivative directly influences the blend morphology and displays an important parameter for efficient polymer-fullerene bulk heterojunction solar cell operation. (copyright 2008 WILEY-VCH Verlag GmbH and Co. KGaA, Weinheim) (Abstract Copyright [2008], Wiley Periodicals, Inc.)

  20. Nobiletin Stimulates Chloride Secretion in Human Bronchial Epithelia via a cAMP/PKA-Dependent Pathway

    Directory of Open Access Journals (Sweden)

    Yuan Hao

    2015-08-01

    Full Text Available Background/Aims: Nobiletin, a citrus flavonoid isolated from tangerines, alters ion transport functions in intestinal epithelia, and has antagonistic effects on eosinophilic airway inflammation of asthmatic rats. The present study examined the effects of nobiletin on basal short-circuit current (ISC in a human bronchial epithelial cell line (16HBE14o-, and characterized the signal transduction pathways that allowed nobiletin to regulate electrolyte transport. Methods: The ISC measurement technique was used for transepithelial electrical measurements. Intracellular calcium ([Ca2+]i and cAMP were also quantified. Results: Nobiletin stimulated a concentration-dependent increase in ISC, which was due to Cl- secretion. The increase in ISC was inhibited by a cystic fibrosis transmembrane conductance regulator inhibitor (CFTRinh-172, but not by 4,4'-diisothiocyano-stilbene-2,2'-disulphonic acid (DIDS, Chromanol 293B, clotrimazole, or TRAM-34. Nobiletin-stimulated ISC was also sensitive to a protein kinase A (PKA inhibitor, H89, and an adenylate cyclase inhibitor, MDL-12330A. Nobiletin could not stimulate any increase in ISC in a cystic fibrosis (CF cell line, CFBE41o-, which lacked a functional CFTR. Nobiletin stimulated a real-time increase in cAMP, but not [Ca2+]i. Conclusion: Nobiletin stimulated transepithelial Cl- secretion across human bronchial epithelia. The mechanisms involved activation of adenylate cyclase- and cAMP/PKA-dependent pathways, leading to activation of apical CFTR Cl- channels.

  1. Current transformer model with hysteresis for improving the protection response in electrical transmission systems

    Science.gov (United States)

    Matussek, Robert; Dzienis, Cezary; Blumschein, Jörg; Schulte, Horst

    2014-12-01

    In this paper, a generic enhanced protection current transformer (CT) model with saturation effects and transient behavior is presented. The model is used for the purpose of analysis and design of power system protection algorithms. Three major classes of protection CT have been modeled which all take into account the nonlinear inductance with remanence effects. The transient short-circuit currents in power systems are simulated under CT saturation condition. The response of a common power system protection algorithm with respect to robustness to nominal parameter variations and sensitivity against maloperation is demonstrated by simulation studies.

  2. Current transformer model with hysteresis for improving the protection response in electrical transmission systems

    International Nuclear Information System (INIS)

    Matussek, Robert; Dzienis, Cezary; Blumschein, Jörg; Schulte, Horst

    2014-01-01

    In this paper, a generic enhanced protection current transformer (CT) model with saturation effects and transient behavior is presented. The model is used for the purpose of analysis and design of power system protection algorithms. Three major classes of protection CT have been modeled which all take into account the nonlinear inductance with remanence effects. The transient short-circuit currents in power systems are simulated under CT saturation condition. The response of a common power system protection algorithm with respect to robustness to nominal parameter variations and sensitivity against maloperation is demonstrated by simulation studies

  3. Detection of mechanical failures in induction motors by current spectrum analysis

    Energy Technology Data Exchange (ETDEWEB)

    Sokansky, K; Novak, P; Bilos, J; Labaj, J [Technical University Ostrava, Moraviasilesian Power Stations s.h.c. (Czech Republic)

    1998-12-31

    From the diagnostic point of view, an electric machine can be understood as an electromechanical system. It means that any manifestations of mechanical failures do not have to show themselves only in mechanical quantities, i.e. vibration in our case. Mechanical failures can also manifest themselves in electrical quantities, namely in electric current in our case. This statement is valid inversely too, which means that faults occurring in electric circuits can be measured through mechanical quantities. This presentation deals with measuring the current spectra of induction motors with short circuited armatures that are drives used in the industries most. (orig.) 3 refs.

  4. Detection of mechanical failures in induction motors by current spectrum analysis

    Energy Technology Data Exchange (ETDEWEB)

    Sokansky, K.; Novak, P.; Bilos, J.; Labaj, J. [Technical University Ostrava, Moraviasilesian Power Stations s.h.c. (Czech Republic)

    1997-12-31

    From the diagnostic point of view, an electric machine can be understood as an electromechanical system. It means that any manifestations of mechanical failures do not have to show themselves only in mechanical quantities, i.e. vibration in our case. Mechanical failures can also manifest themselves in electrical quantities, namely in electric current in our case. This statement is valid inversely too, which means that faults occurring in electric circuits can be measured through mechanical quantities. This presentation deals with measuring the current spectra of induction motors with short circuited armatures that are drives used in the industries most. (orig.) 3 refs.

  5. Identification and utilization of inter-species conserved (ISC probesets on Affymetrix human GeneChip® platforms for the optimization of the assessment of expression patterns in non human primate (NHP samples

    Directory of Open Access Journals (Sweden)

    Arnold Alma

    2004-10-01

    Full Text Available Abstract Background While researchers have utilized versions of the Affymetrix human GeneChip® for the assessment of expression patterns in non human primate (NHP samples, there has been no comprehensive sequence analysis study undertaken to demonstrate that the probe sequences designed to detect human transcripts are reliably hybridizing with their orthologs in NHP. By aligning probe sequences with expressed sequence tags (ESTs in NHP, inter-species conserved (ISC probesets, which have two or more probes complementary to ESTs in NHP, were identified on human GeneChip® platforms. The utility of human GeneChips® for the assessment of NHP expression patterns can be effectively evaluated by analyzing the hybridization behaviour of ISC probesets. Appropriate normalization methods were identified that further improve the reliability of human GeneChips® for interspecies (human vs NHP comparisons. Results ISC probesets in each of the seven Affymetrix GeneChip® platforms (U133Plus2.0, U133A, U133B, U95Av2, U95B, Focus and HuGeneFL were identified for both monkey and chimpanzee. Expression data was generated from peripheral blood mononuclear cells (PBMCs of 12 human and 8 monkey (Indian origin Rhesus macaque samples using the Focus GeneChip®. Analysis of both qualitative detection calls and quantitative signal intensities showed that intra-species reproducibility (human vs. human or monkey vs. monkey was much higher than interspecies reproducibility (human vs. monkey. ISC probesets exhibited higher interspecies reproducibility than the overall expressed probesets. Importantly, appropriate normalization methods could be leveraged to greatly improve interspecies correlations. The correlation coefficients between human (average of 12 samples and monkey (average of 8 Rhesus macaque samples are 0.725, 0.821 and 0.893 for MAS5.0 (Microarray Suite version 5.0, dChip and RMA (Robust Multi-chip Average normalization method, respectively. Conclusion It is

  6. Internal Short Circuits in Lithium-Ion Cells for PHEVs

    Energy Technology Data Exchange (ETDEWEB)

    Sriramulu, Suresh [Tiax LLC, Lexington, MA (United States); Stringfellow, Richard [Tiax LLC, Lexington, MA (United States)

    2013-05-25

    Development of Plug-in Hybrid Electric Vehicles (PHEVs) has recently become a high national priority because of their potential to enable significantly reduced petroleum consumption by the domestic transportation sector in the relatively near term. Lithium-ion (Li-ion) batteries are a critical enabling technology for PHEVs. Among battery technologies with suitable operating characteristics for use in vehicles, Li-ion batteries offer the best combination of energy, power, life and cost. Consequently, worldwide, leading corporations and government agencies are supporting the development of Li-ion batteries for PHEVs, as well as the full spectrum of vehicular applications ranging from mild hybrid to all-electric. In this project, using a combination of well-defined experiments, custom designed cells and simulations, we have improved the understanding of the process by which a Li-ion cell that develops an internal short progresses to thermal runaway. Using a validated model for thermal runaway, we have explored the influence of environmental factors and cell design on the propensity for thermal runaway in full-sized PHEV cells. We have also gained important perspectives about internal short development and progression; specifically that initial internal shorts may be augmented by secondary shorts related to separator melting. Even though the nature of these shorts is very stochastic, we have shown the critical and insufficiently appreciated role of heat transfer in influencing whether a developing internal short results in a thermal runaway. This work should lead to enhanced perspectives on separator design, the role of active materials and especially cathode materials with respect to safety and the design of automotive cooling systems to enhance battery safety in PHEVs.

  7. Short-Circuiting the Bureaucracy: Policy Origins in Education.

    Science.gov (United States)

    Graham, Hugh Davis

    The Great Society's secret task forces created by Lyndon Johnson, particularly in the case-study area of federal education policy, show the use and misuse of the task force device. Modern use of it began with John F. Kennedy. Although he used the task force device effectively sometimes, he did not use it effectively in his educational programs in…

  8. Short-circuiting magma differentiation from basalt straight to rhyolite?

    Science.gov (United States)

    Ruprecht, P.; Winslow, H.

    2017-12-01

    Silicic magmas are the product of varying degrees of crystal fractionation and crustal assimilation/melting. Both processes lead to differentiation that is step-wise rather than continuous for example during melt separation from a crystal mush (Dufek and Bachmann, 2010). However, differentiation is rarely efficient enough to evolve directly from a basaltic to a rhyolitic magma. At Volcán Puyehue-Cordón Caulle, Chile, the magma series is dominated by crystal fractionation where mixing trends between primitive and felsic end members in the bulk rock compositions are almost absent (e.g. P, FeO, TiO2 vs. SiO2). How effective fraction is in this magmatic system is not well-known. The 2011-12 eruption at Cordón Caulle provides new constraints that rhyolitic melts may be derived directly from a basaltic mush. Minor, but ubiquitous mafic, crystal-rich enclaves co-erupted with the predominantly rhyolitic near-aphyric magma. These enclaves are among the most primitive compositions erupted at Puyehue-Cordón Caulle and geochemically resemble closely basaltic magmas that are >10 ka old (Singer et al. 2008) and that have been identified as a parental tholeiitic mantle-derived magma (Schmidt and Jagoutz, 2017) for the Southern Andean Volcanic Zone. The vesiculated nature, the presence of a microlite-rich groundmass, and a lack of a Eu anomaly in these encalves suggest that they represent recharge magma/mush rather than sub-solidus cumulates and therefore have potentially a direct petrogenetic link to the erupted rhyolites. Our results indicate that under some conditions crystal fractionation can be very effective and the presence of rhyolitic magmas does not require an extensive polybaric plumbing system. Instead, primitive mantle-derived magmas source directly evolved magmas. In the case, of the magma system beneath Puyehue-Cordón Caulle, which had three historic rhyolitic eruptions (1921-22, 1960, 2011-12) these results raise the question whether rhyolite magma extraction has been efficient for multiple eruptions? References: Dufek & Bachmann (2010) Geology 38, 687-690; Schmidt & Jagoutz (2017) G-cubed, doi: 10.1002/2016GC006699; Singer et al. (2008) GSA Bulletin 120, 599-618.

  9. Proposed budget cuts threaten to short-circuit Grid network

    CERN Multimedia

    Butler, D

    2001-01-01

    Changes to the budget for the European sixth Framework programme may jeapardize the Grid project. The EU Parliament have asked to cut the budget for infrastructure to 500 million euros from 900 and of this 150 million will probably be allocated to Ge the pan-European research network (1 page).

  10. Method and device for current driven electric energy conversion

    DEFF Research Database (Denmark)

    2012-01-01

    Device comprising an electric power converter circuit for converting electric energy. The converter circuit comprises a switch arrangement with two or more controllable electric switches connected in a switching configuration and controlled so as to provide a current drive of electric energy from...... configurations such as half bridge buck, full bridge buck, half bridge boost, or full bridge boost. A current driven conversion is advantageous for high efficient energy conversion from current sources such as solar cells or where a voltage source is connected through long cables, e.g. powerline cables for long...... an associated electric source connected to a set of input terminals. This is obtained by the two or more electric swiches being connected and controlled to short-circuit the input terminals during a part of a switching period. Further, a low pass filter with a capacitor and an inductor are provided to low pass...

  11. Study on current limiting characteristics of SFCL with two trigger current levels

    International Nuclear Information System (INIS)

    Lim, S.H.

    2010-01-01

    In this paper, the superconducting fault current limiter (SFCL) with two trigger current levels was suggested and its effectiveness through the analysis on the current limiting characteristics was described. The proposed SFCL, which consists of the triggering and the limiting components, can limit the fault current by generating the limiting impedance through two steps according to the amplitude of the initial fault current. In case that the fault happens, the lower initial fault current causes the only superconducting element of the triggering component to be quenched. On the other hand, the higher initial fault current makes both the superconducting elements comprising the triggering and the limiting components of the SFCL to be quenched, which contributes to the higher impedance of the SFCL. Therefore, the effective fault current limiting operation of the SFCL can be performed by generating the SFCL's impedance in proportion to the amplitude of the initial fault current. To confirm the current limiting operation of the proposed SFCL, the short-circuit tests of the SFCL according to the fault angle were carried out and its effective fault current limiting operations could be discussed.

  12. Neurophysiological mechanisms of bradykinin-evoked mucosal chloride secretion in guinea pig small intestine.

    Science.gov (United States)

    Qu, Mei-Hua; Ji, Wan-Sheng; Zhao, Ting-Kun; Fang, Chun-Yan; Mao, Shu-Mei; Gao, Zhi-Qin

    2016-02-15

    To investigate the mechanism for bradykinin (BK) to stimulate intestinal secretomotor neurons and intestinal chloride secretion. Muscle-stripped guinea pig ileal preparations were mounted in Ussing flux chambers for the recording of short-circuit current (Isc). Basal Isc and Isc stimulated by BK when preincubated with the BK receptors antagonist and other chemicals were recorded using the Ussing chamber system. Prostaglandin E2 (PGE2) production in the intestine was determined by enzyme immunologic assay (EIA). Application of BK or B2 receptor (B2R) agonist significantly increased the baseline Isc compared to the control. B2R antagonist, tetrodotoxin and scopolamine (blockade of muscarinic receptors) significantly suppressed the increase in Isc evoked by BK. The BK-evoked Isc was suppressed by cyclooxygenase (COX)-1 or COX-2 specific inhibitor as well as nonselective COX inhibitors. Preincubation of submucosa/mucosa preparations with BK for 10 min significantly increased PGE2 production and this was abolished by the COX-1 and COX-2 inhibitors. The BK-evoked Isc was suppressed by nonselective EP receptors and EP4 receptor antagonists, but selective EP1 receptor antagonist did not have a significant effect on the BK-evoked Isc. Inhibitors of PLC, PKC, calmodulin or CaMKII failed to suppress BK-induced PGE2 production. The results suggest that BK stimulates neurogenic chloride secretion in the guinea pig ileum by activating B2R, through COX increasing PGE2 production. The post-receptor transduction cascade includes activation of PLC, PKC, CaMK, IP3 and MAPK.

  13. A No-Arc DC Circuit Breaker Based on Zero-Current Interruption

    Science.gov (United States)

    Xiang, Xuewei; Chai, Jianyun; Sun, Xudong

    2017-05-01

    A dc system has no natural current zero-crossing point, so a dc arc is more difficult to extinguish than an ac arc. In order to effectively solve the problem of the dc arc, this paper proposes a dc circuit breaker (DCCB) capable of implementing a no-arc interruption. The proposed DCCB includes a main branch consisting of a mechanical switch, a diode and a current-limiting inductor, a semi-period resonance circuit consisting of a diode, an inductor and a capacitor, and a buffer branch consisting of a capacitor, a thyristor and a resistor. The mechanical switch is opened in a zero-current state, and the overvoltage caused by the counter electromotive force of the inductor does not exist. Meanwhile, the capacitor has a buffering effect on the voltage. The rising of the voltage of the mechanical switch is slower than the rising of the insulating strength of a contact gap of the mechanical switch, resulting in the contact gap not able to be broken down. Thus, the arc cannot be generated. The simulation results show that the proposed DCCB does not generate the arc in the interruption process, the rise rate of the short circuit current can be effectively limited, and the short circuit fault point can be rapidly isolated from the dc power supply.

  14. Influencia de la generación distribuida en los niveles de cortocircuito y en las protecciones eléctricas en subestaciones de 110 / 34,5 kV; The effects caused due to the introduction of Distribution Generation in the short-circuit levels and the protecti

    Directory of Open Access Journals (Sweden)

    Marta Bravo de las Casas

    2011-02-01

    Full Text Available En este trabajo se muestran algunos resultados de los efectos provocados por la introducción de la GD enlas redes cubanas en lo que respecta a los niveles de cortocircuito y los ajustes de las protecciones en cincosubestaciones de 110 / 34,5 kV ubicadas en las provincias de Villa Clara, Cienfuegos y Sancti Spíritus. Seobtuvieron conclusiones importantes con respecto a las necesidades de funciones de protección y criteriosde ajuste de las protecciones. Además, con respecto a la necesidad de tener en las subestaciones relésdigitales modernos con el fin de que puedan responder correctamente y en el menor tiempo posible a losdiferentes escenarios de operación que tendrá el sistema en las nuevas condiciones y así corresponder a lasexigencias que impone la GD a los esquemas de protección. In this article, results are shown of the effects caused due to the introduction of Distribution Generation(DG in the Cuban Networks with respect to short-circuit levels and the protection settings of five 110/34.5kV substations located in the provinces of Villa Clara, Cienfuegos y Sancti Spíritus. Important conclusionshave been obtained with respect to the necessities of the protection functions and their settings criteria.Besides, with respect to the necessity of having modern digital relays in order to respond correctly and inthe least possible time to the different stages of operation that the system may have in the new conditionsof operation and in this manner corresponds to the demands that the DG imply in protection systems. 

  15. Modulation of electrogenic transport processes in the porcine proximal colon by enteric neurotransmitters.

    Science.gov (United States)

    Pfannkuche, H; Mauksch, A; Gäbel, G

    2012-06-01

    The aim of our study was to evaluate the involvement of essential pro- and antisecretory neurotransmitters in regulation of secretion in porcine proximal colon. Choline acetyltransferase (ChAT), nitric oxide synthase (NOS), vasoactive intestinal peptide (VIP), substance P (SP), somatostatin (SOM) and neuropeptide Y (NPY) were located immunohistochemically in the epithelium and subepithelial layer. Modulation of epithelial secretion was studied in Ussing chambers. Application of carbachol (CA), sodium nitroprussid (SNP), VIP and SP but not of NPY or SOM resulted in a chloride dependent increase in short circuit current (I(sc) ). I(sc) increase induced by CA, VIP or SNP was not altered by preincubation with tetrodotoxin or indomethacin. In contrast, SP-induced I(sc) increase was diminished by preincubation with tetrodotoxin, indomethacin, L-nitro-arginin-methyl-ester, and atropine but not hexamethonium. Simultaneous application of CA and VIP, or CA and SNP increased the I(sc) stronger as expected. Applying SP/CA led to a smaller increase in I(sc) as calculated. It is concluded that mainly prosecretory neurotransmitters are involved in regulation of colonic secretion. Cross-potentiations of acetylcholine and nitric oxide and acetylcholine and VIP suggest activation of different intracellular cascades. Similar intracellular pathways may be stimulated by acetylcholine and SP, thus preventing an additive effect of the transmitters. © 2011 Blackwell Verlag GmbH.

  16. Ground Return Current Behaviour in High Voltage Alternating Current Insulated Cables

    Directory of Open Access Journals (Sweden)

    Roberto Benato

    2014-12-01

    Full Text Available The knowledge of ground return current in fault occurrence plays a key role in the dimensioning of the earthing grid of substations and of cable sealing end compounds, in the computation of rise of earth potential at substation sites and in electromagnetic interference (EMI on neighbouring parallel metallic conductors (pipes, handrails, etc.. Moreover, the ground return current evaluation is also important in steady-state regime since this stray current can be responsible for EMI and also for alternating current (AC corrosion. In fault situations and under some assumptions, the ground return current value at a substation site can be computed by means of k-factors. The paper shows that these simplified and approximated approaches have a lot of limitations and only multiconductor analysis can show the ground return current behaviour along the cable (not only the two end values both in steady-state regime and in short circuit occurrence (e.g., phase-to-ground and phase-to-phase-to-ground. Multiconductor cell analysis (MCA considers the cable system in its real asymmetry without simplified and approximated hypotheses. The sensitivity of ground return current on circuit parameters (cross-bonding box resistances, substation earthing resistances, soil resistivity is presented in the paper.

  17. Regulation of ion transport via apical purinergic receptors in intact rabbit airway epithelium

    DEFF Research Database (Denmark)

    Poulsen, Asser Nyander; Klausen, Thomas Levin; Pedersen, Peter Steen

    2005-01-01

    and unidirectional Cl- fluxes decreased significantly. The results suggest that nucleotides released to the airway surface liquid exert an autocrine regulation of epithelial NaCl absorption mainly by inhibiting the amiloride-sensitive epithelial Na+ channel (ENaC) and paracellular anion conductance via a P2Y......We investigated purinergic receptors involved in ion transport regulation in the intact rabbit nasal airway epithelium. Stimulation of apical membrane P2Y receptors with ATP or UTP (200 microM) induced transient increases in short-circuit current (Isc) of 13 and 6% followed by sustained inhibitions...

  18. Optimizations of large area quasi-solid-state dye-sensitized solar cells

    DEFF Research Database (Denmark)

    Biancardo, M.; West, K.; Krebs, Frederik C

    2006-01-01

    In this paper, we address optimizations of dye sensitized solar cells (DSSCs) through the combination of important issues like semi-transparency, quasi-solid-state constructions and low-cost realization of serially connected modules. DSSCs with a transparency of 50% in the visible region, moderate...... encouraging results. A short circuit current (I-sc) of 4.45 mA cm(-2) with an open circuit voltage (V-oc) of 0.5 V were recorded in standard solar cells sensitized by cis-bis(thiocyano) ruthenium(II)-bis-2, 2'-bipyridine-4, 4'-dicarboxylate. Up-scaling tests demonstrate the easy realization of a 625 cm(2...

  19. Quality Evaluation for Microcrystalline Silicon Thin-Film Solar Cells by Single-Layer Absorption

    Directory of Open Access Journals (Sweden)

    Sheng-Hui Chen

    2012-01-01

    Full Text Available The absorption coefficient at 1.4 eV is divided by the value at 0.9 eV to obtain the factor used to judge the quality of μc-Si:H. PV device performance can be predicted by multiplying Voc with Isc when using this layer as an intrinsic layer. The results show a good relationship between the quality factor and the product of open-circuit voltage and short-circuit current. However, the final efficiency is influenced by the identities of the interface in the multilayer structure.

  20. Influence of stabilizer thickness on over-current test of YBCO-coated conductors

    International Nuclear Information System (INIS)

    Kwon, N Y; Kim, H S; Kim, K L; Lee, H G; Yim, S W; Kim, H-R; Hyun, O-B; Kim, H M

    2009-01-01

    The increased use of distributed power generation has led to increasingly high fault current levels. A superconducting fault current limiter (SFCL) is a potential solution to prevent the problem of short-circuit currents. YBCO-coated conductors (CCs) are one of the most promising superconducting materials for SFCLs. Most YBCO CCs have stabilizers, which play a significant role in limiting the fault current in the SFCL. Therefore, the selection of the appropriate material and the thickness of the stabilizer of the CC used for the SFCL may affect its quench/recovery characteristics. In this paper, the quench/recovery characteristics of YBCO CC tapes having stabilizers with various thicknesses were investigated. The quench/recovery test results showed that, as the thickness of the stabilizer decreased, both the final approach temperature and the recovery time decreased.

  1. Regulation of electrolyte transport with IL-1β in rabbit distal colon

    Directory of Open Access Journals (Sweden)

    F. R. Homaidan

    1995-01-01

    Full Text Available Interletrkin-1β levels are elevated in inflammatory bowel disease. In this study the mechanism by which interleukin-1β affects electrolyte transport in the rabbit distal colon, was investigated. Interleukin-1β caused a delayed increase in short-circuit current (Isc which was attributed to protein synthesis since the effect was inhibited by cycloheximide. The interleukin-1β induced increase in Isc was not affected by amiloride treatment but was completely inhibited by bumetanide or in chloride-free buffer and by indomethacin. Prostaglandin E2 levels increased in tissue treated with interleukin-1β, but this increase was reversed by cycloheximide. These data suggest that interleukin-1β causes its effect via a yet to be identified second messenger, by increasing chloride secretion through a prostaglandin E2 mediated mechanism.

  2. Nitric oxide inhibition of NaCl secretion in the opercular epithelium of seawater-acclimated killifish, Fundulus heteroclitus

    DEFF Research Database (Denmark)

    Gerber, Lucie; Jensen, Frank B; Madsen, Steffen S

    2016-01-01

    to explore the mechanism(s) triggering NO action. A modified Biotin-switch technique was used to investigate S-nitrosation of proteins. Stimulation of endogenous NO production via the nitric oxide synthase (NOS) substrate L-arginine (2.0 mmol l-1), and addition of exogenous NO via the NO donor SNAP (10-6 mol...... l-1 to 10-4 mol l-1), decreased the epithelial short-circuit current (Isc). Inhibition of endogenous NO production by the NOS inhibitor L-NAME (10-4 mol l-1) increased Isc and revealed a tonic control of ion transport by NO in unstimulated opercular epithelia. The NO scavenger PTIO (10-5 mol l-1...

  3. Research of grounding capacitive current of neutral non-grounding auxiliary system in nuclear power plants

    International Nuclear Information System (INIS)

    Yang Shan; Liu Li; Huang Xiaojing

    2014-01-01

    In the domestic and abroad standards, the grounding capacitive current limitation in the non-grounding electric auxiliary system is less than 10 A. Limiting capacitive current in the standard aims to speed up the arc extinguishing to reduce the duration of arc over-voltage, but not to prevent the arc producing, The arc over-voltage harm is related to the multiple, frequency and duration of the over-voltage. When the insulation vulnerabilities appear in the equipment, the arc over-voltage may result in insulation vulnerabilities of the electrical equipment breakdown, which leads to multiple, short-circuit accidents. The cable connector, accessory and electromotor winding are all insulation vulnerabilities. Setting the arc suppression coil which can counteract the grounding capacitive current makes the arc vanish quickly. Using the casting bus which remarkably reduces the ground capacitance of the electric transmission line makes the equipment safer. (authors)

  4. Flux-lock type of superconducting fault current limiters: A comprehensive review

    Science.gov (United States)

    Badakhshan, M.; Mousavi G., S. M.

    2018-04-01

    Power systems must be developed and extended to supply the continuous enhancement of demands for electrical energy. This development of systems in addition to the integration of distributed generation (DG) units to the power systems results higher capacity of system. Hence, short circuit current of network is confronted with persistent increasing. Since exploration of high temperature superconducting (HTS) materials, superconducting fault current limiters (SFCLs) have attracted a lot of attention all over the world. There are different types of SFCLs. Flux-lock type of SFCL because of its characteristics in fault current limitation is an important category of SFCLs. This paper aims to present a comprehensive review of research activities and applications of Flux-lock type of SFCLs in power systems.

  5. Measuring ac losses in superconducting cables using a resonant circuit:Resonant current experiment (RESCUE)

    DEFF Research Database (Denmark)

    Däumling, Manfred; Olsen, Søren Krüger; Rasmussen, Carsten

    1998-01-01

    be recorded using, for example, a digital oscilloscope. The amplitude decay of the periodic voltage or current accurately reflects the power loss in the system. It consists of two components-an ohmic purely exponential one (from leads, contacts, etc.), and a nonexponential component originating from......A simple way to obtain true ac losses with a resonant circuit containing a superconductor, using the decay of the circuit current, is described. For the measurement a capacitor is short circuited with a superconducting cable. Energy in the circuit is provided by either charging up the capacitors...... with a certain voltage, or letting a de flow in the superconductor. When the oscillations are started-either by opening a switch in case a de is flowing or by closing a switch to connect the charged capacitors with the superconductor-the current (via a Rogowski coil) or the voltage on the capacitor can...

  6. Imposed currents in galvanic cells

    International Nuclear Information System (INIS)

    Biesheuvel, P.M.; Soestbergen, M. van; Bazant, M.Z.

    2009-01-01

    We analyze the steady-state behavior of a general mathematical model for reversible galvanic cells, such as redox flow cells, reversible solid oxide fuel cells, and rechargeable batteries. We consider not only operation in the galvanic discharging mode, spontaneously generating a positive current against an external load, but also operation in two modes which require a net input of electrical energy: (i) the electrolytic charging mode, where a negative current is imposed to generate a voltage exceeding the open-circuit voltage, and (ii) the 'super-galvanic' discharging mode, where a positive current exceeding the short-circuit current is imposed to generate a negative voltage. Analysis of the various (dis-)charging modes of galvanic cells is important to predict the efficiency of electrical to chemical energy conversion and to provide sensitive tests for experimental validation of fuel cell models. In the model, we consider effects of diffuse charge on electrochemical charge-transfer rates by combining a generalized Frumkin-Butler-Volmer equation for reaction kinetics across the compact Stern layer with the full Poisson-Nernst-Planck transport theory, without assuming local electroneutrality. Since this approach is rare in the literature, we provide a brief historical review. To illustrate the general theory, we present results for a monovalent binary electrolyte, consisting of cations, which react at the electrodes, and non-reactive anions, which are either fixed in space (as in a solid electrolyte) or are mobile (as in a liquid electrolyte). The full model is solved numerically and compared to analytical results in the limit of thin diffuse layers, relative to the membrane thickness. The spatial profiles of the ion concentrations and electrostatic potential reveal a complex dependence on the kinetic parameters and the imposed current, in which the diffuse charge at each electrode and the total membrane charge can have either sign, contrary perhaps to intuition

  7. Aplicabilidade do índice de risco do sistema NNIS na predição da incidência de infecção do sítio cirúrgico (ISC em um hospital universitário no sul do Brasil

    Directory of Open Access Journals (Sweden)

    Freitas P. F.

    2000-01-01

    Full Text Available OBJETIVO: Investigar a aplicabilidade da metodologia do sistema NNIS em um hospital universitário brasileiro, por meio da avaliação do modelo preditivo de ISC que deu origem ao índice de medida de risco intrínseco. CASUÍSTICA E MÉTODO: Foi conduzida uma revisão retrospectiva dos prontuários de 9.322 pacientes submetidos a procedimento cirúrgico no período de janeiro de 1993 a dezembro de 1998. Os dados foram coletados utilizando a opção detalhada do componente de vigilância do paciente cirúrgico do sistema NNIS. Foi calculada a incidência de ISC de acordo com as diferentes categorias individuais dos componentes do índice de risco NNIS (Classe de Ferida, escore ASA e duração da cirurgia. A força da associação entre cada um destes fatores e a ocorrência de ISC foi medida pelo coeficiente Gamma de Goodman-Kruskal (G. RESULTADOS: O escore ASA mostrou-se o melhor preditor de ISC entre os componentes individuais do índice de risco (G=0.49. O índice composto mostrou ser um melhor preditor de ISC do que classe de ferida e teve um poder preditivo semelhante ao do ASA (G=0.50. CONCLUSÕES: O grau de associação entre o índice NNIS e a ocorrência de ISC encontrada no presente estudo está em consonância com os resultados relatados por outros autores e mostrou-se adequado para a avaliação do risco de infecção cirúrgica em nossos pacientes. Amostras utilizando diferentes hospitais com características semelhantes são necessárias para avaliar o risco associado com procedimentos cirúrgicos específicos.

  8. Research trend in thermally stimulated current method for development of materials and devices in Japan

    Science.gov (United States)

    Iwamoto, Mitsumasa; Taguchi, Dai

    2018-03-01

    Thermally stimulated current (TSC) measurement is widely used in a variety of research fields, i.e., physics, electronics, electrical engineering, chemistry, ceramics, and biology. TSC is short-circuit current that flows owing to the displacement of charges in samples during heating. TSC measurement is very simple, but TSC curves give very important information on charge behaviors. In the 1970s, TSC measurement contributed greatly to the development of electrical insulation engineering, semiconductor device technology, and so forth. Accordingly, the TSC experimental technique and its analytical method advanced. Over the past decades, many new molecules and advanced functional materials have been discovered and developed. Along with this, TSC measurement has attracted much attention in industries and academic laboratories as a way of characterizing newly discovered materials and devices. In this review, we report the latest research trend in the TSC method for the development of materials and devices in Japan.

  9. Subcell Light Current-Voltage Characterization of Irradiated Multijunction Solar Cell

    Directory of Open Access Journals (Sweden)

    Walker Don

    2017-01-01

    Full Text Available The degradation of individual subcell J-V parameters, such as short circuit current, open circuit voltage, fill factor, and power of a GaInP/GaInAs/Ge triple junction solar cell by 1 MeV electrons were derived utilizing the spectral reciprocity relation between electroluminescence and external quantum efficiency. After exposure to a fluence of 1 × 1015 1 MeV electrons, it was observed that up to 67% of the voltage loss is from the middle, GaInAs subcell. Also, the dark saturation current of the Ge and GaInAs subcells increased but a simultaneous decrease in ideality factor caused a reduction of the open circuit voltage. The reduced ideality factor further indicates a change in the primary recombination mechanism.

  10. Optimal Placement and Sizing of Fault Current Limiters in Distributed Generation Systems Using a Hybrid Genetic Algorithm

    Directory of Open Access Journals (Sweden)

    N. Bayati

    2017-02-01

    Full Text Available Distributed Generation (DG connection in a power system tends to increase the short circuit level in the entire system which, in turn, could eliminate the protection coordination between the existing relays. Fault Current Limiters (FCLs are often used to reduce the short-circuit level of the network to a desirable level, provided that they are dully placed and appropriately sized. In this paper, a method is proposed for optimal placement of FCLs and optimal determination of their impedance values by which the relay operation time, the number and size of the FCL are minimized while maintaining the relay coordination before and after DG connection. The proposed method adopts the removal of low-impact FCLs and uses a hybrid Genetic Algorithm (GA optimization scheme to determine the optimal placement of FCLs and the values of their impedances. The suitability of the proposed method is demonstrated by examining the results of relay coordination in a typical DG network before and after DG connection.

  11. Different modes of electrogenic Na+ absorption in the coprodeum of the chicken embryo: role of extracellular Ca2+.

    Science.gov (United States)

    Heinz, M; Krattenmacher, R; Hoffmann, B; Clauss, W

    1991-01-01

    Transepithelial electrogenic Na+ transport (INa) was investigated in the coprodeum of 20-days-old chicken embryos in Ussing chambers. Short circuit current (Isc) and transepithelial resistance (Rt) were 14.7 +/- 4.8 microA.cm-2 (n = 12) and 0.53 +/- 0.09 k omega.cm-2 (n = 12), respectively. INa was calculated from changes in Isc by substitution of mucosal Na+ by (N-methyl-D-glucamine) (NMDG). Isc inversed during Na+ removal, and INa was found to be 27.8 +/- 4.7 microA.cm-2 (n = 12). Amiloride (100 mumol.l-1) inhibited only about 60% of INa. Analysis of Isc fluctuations revealed a Lorentzian component in the power density spectrum with a corner frequency of about 57 Hz. This component was not correlated to INa, and its origin is still unclear. Removal of mucosal Ca2+ increased INa about 2.5-fold due to an increase of the amiloride-insensitive component of INa in additionally investigated adult tissues. The results clearly show that this is due to a non-selective cation channel with an "apparent" order of selectivity Cs+ greater than Na+ = K+ greater than Rb+ greater than Li+. The Ca2+ concentration required to block 50% of the Isc was about 18 mumol.l-1. The IscCa could also be suppressed by other divalent cations such as Mg2+ and Ba2+. Additionally, an INa-linked Lorentzian component occurred which dominated the control spectrum with a significantly higher corner frequency (about 88 Hz). The results indicate that Na+ absorption in the coprodeum of the chicken embryo is more complex than in adult hens.(ABSTRACT TRUNCATED AT 250 WORDS)

  12. Using of explosive technologies for development of a compact current-limiting device for operation on 110 kV class systems

    Science.gov (United States)

    Shurupov, A. V.; Shurupov, M. A.; Kozlov, A. A.; Kotov, A. V.

    2016-11-01

    This paper considers the possibility of creating on new physical principles a highspeed current-limiting device (CLD) for the networks with voltage of 110 kV, namely, on the basis of the explosive switching elements. The device is designed to limit the steady short-circuit current to acceptable values for the time does not exceed 3 ms at electric power facilities. The paper presents an analysis of the electrical circuit of CLD. The main features of the scheme are: a new high-speed switching element with high regenerating voltage; fusible switching element that enables to limit the overvoltage after sudden breakage of network of the explosive switch; non-inductive resistor with a high heat capacity and a special reactor with operating time less than 1 s. We analyzed the work of the CLD with help of special software PSPICE, which is based on the equivalent circuit of single-phase short circuit to ground in 110 kV network. Analysis of the equivalent circuit operation CLD shows its efficiency and determines the CLD as a perspective direction of the current-limiting devices of new generation.

  13. Using of explosive technologies for development of a compact current-limiting device for operation on 110 kV class systems

    International Nuclear Information System (INIS)

    Shurupov, A V; Shurupov, M A; Kozlov, A A; Kotov, A V

    2016-01-01

    This paper considers the possibility of creating on new physical principles a highspeed current-limiting device (CLD) for the networks with voltage of 110 kV, namely, on the basis of the explosive switching elements. The device is designed to limit the steady short-circuit current to acceptable values for the time does not exceed 3 ms at electric power facilities. The paper presents an analysis of the electrical circuit of CLD. The main features of the scheme are: a new high-speed switching element with high regenerating voltage; fusible switching element that enables to limit the overvoltage after sudden breakage of network of the explosive switch; non-inductive resistor with a high heat capacity and a special reactor with operating time less than 1 s. We analyzed the work of the CLD with help of special software PSPICE, which is based on the equivalent circuit of single-phase short circuit to ground in 110 kV network. Analysis of the equivalent circuit operation CLD shows its efficiency and determines the CLD as a perspective direction of the current-limiting devices of new generation. (paper)

  14. Market potential of superconductor current limiters; Marktpotential von supraleitenden Strombegrenzern

    Energy Technology Data Exchange (ETDEWEB)

    Lakner, M.; Braun, D. [ABB Schweiz AG, Corporate Research, Baden-Daettwil (Switzerland); Schnyder, G.; Mauchle, P. [Schnyder Ingenieure AG, Huenenberg (Switzerland)

    2003-07-01

    This final report for the Swiss Federal Office of Energy describes the two concepts - 'resistive' and 'inductive' - used for Superconducting Fault Current Limiters (SCFCL) that utilise the transition from zero to finite resistance to limit short-circuit currents. The main advantages of SCFCL are compared to other current-limiting technologies: They can limit any type of prospective fault current, operate fail-safe, be self-triggered and self-restoring. Their main disadvantage - the cooling effort necessary - is also discussed. The application possibilities of SCFCL were investigated by simulating the impact on utility and industrial grids. Applications of SCFCL such as the coupling of medium-voltage grids and their use in series with a circuit-breaker on the secondary side of a substation transformer are discussed. It is also shown that, by using fault current limiters, considerable cost savings can be made, especially in connection with new installations or the extension of existing plants.

  15. Generalized space vector control for current source inverters and rectifiers

    Directory of Open Access Journals (Sweden)

    Roseline J. Anitha

    2016-06-01

    Full Text Available Current source inverters (CSI is one of the widely used converter topology in medium voltage drive applications due to its simplicity, motor friendly waveforms and reliable short circuit protection. The current source inverters are usually fed by controlled current source rectifiers (CSR with a large inductor to provide a constant supply current. A generalized control applicable for both CSI and CSR and their extension namely current source multilevel inverters (CSMLI are dealt in this paper. As space vector pulse width modulation (SVPWM features the advantages of flexible control, faster dynamic response, better DC utilization and easy digital implementation it is considered for this work. This paper generalizes SVPWM that could be applied for CSI, CSR and CSMLI. The intense computation involved in framing a generalized space vector control are discussed in detail. The algorithm includes determination of band, region, subregions and vectors. The algorithm is validated by simulation using MATLAB /SIMULINK for CSR 5, 7, 13 level CSMLI and for CSR fed CSI.

  16. Phenomenological description of depoling current in Pb0.99Nb0.02(Zr0.95Ti0.05)0.98O3 ferroelectric ceramics under shock wave compression: Relaxation model

    Science.gov (United States)

    Jiang, Dongdong; Du, Jinmei; Gu, Yan; Feng, Yujun

    2012-05-01

    By assuming a relaxation process for depolarization associated with the ferroelectric (FE) to antiferroelectric (AFE) phase transition in Pb0.99Nb0.02(Zr0.95Ti0.05)0.98O3 ferroelectric ceramics under shock wave compression, we build a new model for the depoling current, which is different from both the traditional constant current source (CCS) model and the phase transition kinetics (PTK) model. The characteristic relaxation time and new-equilibrated polarization are dependent on both the shock pressure and electric field. After incorporating a Maxwell s equation, the relaxation model developed applies to all the depoling currents under short-circuit condition and high-impedance condition. Influences of shock pressure, load resistance, dielectric property, and electrical conductivity on the depoling current are also discussed. The relaxation model gives a good description about the suppressing effect of the self-generated electric field on the FE-to-AFE phase transition at low shock pressures, which cannot be described by the traditional models. After incorporating a time- and electric-field-dependent repolarization, this model predicts that the high-impedance current eventually becomes higher than the short-circuit current, which is consistent with the experimental results in the literature. Finally, we make the comparison between our relaxation model and the traditional CCS model and PTK model.

  17. Fault Current Characteristics of the DFIG under Asymmetrical Fault Conditions

    Directory of Open Access Journals (Sweden)

    Fan Xiao

    2015-09-01

    Full Text Available During non-severe fault conditions, crowbar protection is not activated and the rotor windings of a doubly-fed induction generator (DFIG are excited by the AC/DC/AC converter. Meanwhile, under asymmetrical fault conditions, the electrical variables oscillate at twice the grid frequency in synchronous dq frame. In the engineering practice, notch filters are usually used to extract the positive and negative sequence components. In these cases, the dynamic response of a rotor-side converter (RSC and the notch filters have a large influence on the fault current characteristics of the DFIG. In this paper, the influence of the notch filters on the proportional integral (PI parameters is discussed and the simplified calculation models of the rotor current are established. Then, the dynamic performance of the stator flux linkage under asymmetrical fault conditions is also analyzed. Based on this, the fault characteristics of the stator current under asymmetrical fault conditions are studied and the corresponding analytical expressions of the stator fault current are obtained. Finally, digital simulation results validate the analytical results. The research results are helpful to meet the requirements of a practical short-circuit calculation and the construction of a relaying protection system for the power grid with penetration of DFIGs.

  18. High power tests of beryllium oxide windows to the lower hybrid current drive launcher in JET

    International Nuclear Information System (INIS)

    Ekedahl, A.; Brandon, M.; Finburg, P.

    1999-01-01

    The vacuum windows to the 3.70 GHz Lower Hybrid Current Drive (LHCD) system in JET were originally designed to withstand 350 kW for 20 s with VSWR ≤ 1.8. High power RF tests of the windows have been carried out in the LHCD test facility at JET. All windows that were tested could operate at 500 kW for 10 s in a matched load. Two windows passed an endurance test at 250 kW for 20 s with the windows terminated in a short circuit. One window also passed this endurance test without active cooling. The results show that this type of window can be used in a new advanced launcher, as proposed for ITER, in which the output power from each klystron (P ≤ 500 kW) will be transmitted through one waveguide and one vacuum window. (author)

  19. Elucidating the interplay between dark current coupling and open circuit voltage in organic photovoltaics

    KAUST Repository

    Erwin, Patrick

    2011-01-01

    A short series of alkyl substituted perylenediimides (PDIs) with varying steric bulk are used to demonstrate the relationship between molecular structure, materials properties, and performance characteristics in organic photovoltaics. Devices were made with the structure indium tin oxide/copper phthalocyanine (200 Å)/PDI (200 Å)/bathocuproine (100 Å)/aluminum (1000 Å). We found that PDIs with larger substituents produced higher open circuit voltages (VOC\\'s) despite the donor acceptor interface gap (Δ EDA) remaining unchanged. Additionally, series resistance was increased simultaneously with VOC the effect of reducing short circuit current, making the addition of steric bulk a tradeoff that needs to be balanced to optimize power conversion efficiency. © 2011 American Institute of Physics.

  20. Current state and trends of access to sanitation in Ethiopia and the need to revise indicators to monitor progress in the Post-2015 era.

    Science.gov (United States)

    Beyene, Abebe; Hailu, Tamene; Faris, Kebede; Kloos, Helmut

    2015-05-02

    Investigating the current level and trends of access and identifying the underlying challenges to sanitation system development will be useful in determining directions developing countries are heading as they plan to promote sustainable development goals (post 2015 agenda). This research investigates the status and trends of access to improved sanitation coverage (ISC) in relation to the MDG target in Ethiopia with the aim of identifying prevailing constraints and suggesting the way forward in the post-MDG era. We examined data from a nationwide inventory conducted in accordance with the sanitation ladder at the national level and from a household survey in randomly selected urban slums in Addis Ababa. The inventory data were analyzed and interpreted using the conceptual model of the sanitation ladder. We used administrative reports and survey results to plot the time trend of the ISC. The data from the nationwide inventory of sanitation facilities, which are presented along the sanitation ladder reveal that more than half of the Ethiopian population (52.1%) still used unimproved sanitation facilities in 2014. The majority (35.6%) practiced open defecation, implying that the country is far from the MDG target for access to improved sanitation (56%). Most people in urban slums (88.6%) used unimproved sanitation facilities, indicating that the urban poor did not receive adequate sanitation services. Trend analysis shows that access to ISC has increased, but Central Statistical Authority (CSA) data reveal a decline. This discrepancy is due to differences in data collection methods and tools. Dry pit latrines are the most widely used toilet facilities in Ethiopia, accounting for about 97.5% of the ISC. The sanitation coverage is far from the MDG target and the majority of the population, mainly the urban poor, are living in a polluted environment, exposed to water and sanitation-related diseases. The sanitation coverage estimates might be even lower if proper

  1. STUDI ANALISIS KOORDINASI OVER CURRENT RELAY (OCR DAN GROUND FAULT RELAY (GFR PADA RECLOSER DI SALURAN PENYULANG PENEBEL

    Directory of Open Access Journals (Sweden)

    I Dewa Gde Agung Budhi Udiana

    2017-08-01

    Full Text Available Short circuit causing over current problem and can might causing interference of the equipment performance such as distribution transformers also causing widespread disruption occurred. In resolving such interference is required as protection system on the distribution system. Seeing all above is needed coordination between the supporting component of the protection system which is consisted of Over Current Relay (OCR and Ground Fault Relay (GFR. The research was conducted at PT. PLN (Persero South Bali Area Network, INDONESIA on recloser in the feeder line of Penebel. OCR setting between the Relay feeder of Penebel, Recloser Celagi, Recloser Bakisan, and Recloser Benana still less selective, with time value coordination between average security was still less than 0,2 second. Then OCR setting and GFR relay feeder of Penebel, Recloser Celagi, Recloser Bakisan, and Recloser Benana was recommended for re-setting in order to minimize disruption and electric power distribution system to be reliable.

  2. Fault ride-through enhancement of fixed speed wind turbine using bridge-type fault current limiter

    Directory of Open Access Journals (Sweden)

    Mostafa I. Marei

    2016-05-01

    Full Text Available The interaction between wind energy turbines and the grid results in two main problems, increasing the short-circuit level and reducing the Fault Ride-Through (FRT capability during faults. The objective of this paper is to solve these problems, for fixed speed Wind Energy Systems (WECS, utilizing the bridge-type Fault Current Limiter (FCL with a discharging resistor. A simple cascaded control system is proposed for the FCL to regulate the terminal voltage of the generator and limit the current. The system is simulated on PSCAD/EMTDC software to evaluate the dynamic performance of the proposed WECS compensated by FCL. The simulation results show the potentials of the FCL as a simple and effective method for solving grid interconnection problems of WECS.

  3. Neural influences on human intestinal epithelium in vitro.

    Science.gov (United States)

    Krueger, Dagmar; Michel, Klaus; Zeller, Florian; Demir, Ihsan E; Ceyhan, Güralp O; Slotta-Huspenina, Julia; Schemann, Michael

    2016-01-15

    We present the first systematic and, up to now, most comprehensive evaluation of the basic features of epithelial functions, such as basal and nerve-evoked secretion, as well as tissue resistance, in over 2200 surgical specimens of human small and large intestine. We found no evidence for impaired nerve-evoked epithelial secretion or tissue resistance with age or disease pathologies (stomach, pancreas or colon cancer, polyps, diverticulitis, stoma reversal). This indicates the validity of future studies on epithelial secretion or resistance that are based on data from a variety of surgical specimens. ACh mainly mediated nerve-evoked and basal secretion in the small intestine, whereas vasoactive intestinal peptide and nitric oxide were the primary pro-secretory transmitters in the large intestine. The results of the present study revealed novel insights into regional differences in nerve-mediated secretion in the human intestine and comprise the basis by which to more specifically target impaired epithelial functions in the diseased gut. Knowledge on basic features of epithelial functions in the human intestine is scarce. We used Ussing chamber techniques to record basal tissue resistance (R-basal) and short circuit currents (ISC; secretion) under basal conditions (ISC-basal) and after electrical field stimulation (ISC-EFS) of nerves in 2221 resectates from 435 patients. ISC-EFS was TTX-sensitive and of comparable magnitude in the small and large intestine. ISC-EFS or R-basal were not influenced by the patients' age, sex or disease pathologies (cancer, polyps, diverticulitis). Ion substitution, bumetanide or adenylate cyclase inhibition studies suggested that ISC-EFS depended on epithelial cAMP-driven chloride and bicarbonate secretion but not on amiloride-sensitive sodium absorption. Although atropine-sensitive cholinergic components prevailed for ISC-EFS of the duodenum, jejunum and ileum, PG97-269-sensitive [vasoactive intestinal peptide (VIP) receptor 1

  4. NH4+ secretion in the avian colon. An actively regulated barrier to ammonium permeation of the colon mucosa

    DEFF Research Database (Denmark)

    Holtug, K.; Laverty, G.; Arnason, S.S.

    2009-01-01

    Experiments were designed to characterize an active, electrogenic transport of NH(4)(+) ions across the colonic epithelium of the domestic fowl (Gallus gallus). Colonic segments were isolated and stripped of underlying muscle. The mucosal epithelia were mounted in Ussing chambers and voltage......-clamped to measure the short-circuit currents (I(SC)) associated with transport. Bilateral addition of NH(4)(+) caused a dose-dependent outward current (negative I(SC)), with a Km of 34+/-8 mM and a maximal current response of 311+/-47 microA cm(-2) (12+/-2 microEq cm(-2) h(-1)). A similar effect was seen...... with unilateral addition of NH(4)(+) to the serosal (s) side, but not with mucosal (m) addition. Pre-treatment with 10(-4) M amiloride exposed a net outward (negative) I(SC), and serosal NH(4)(+) addition further increased this outward current with a Km of 53+/-24 mM. Decreasing the bath pH from 7.3 to 6.0 did...

  5. A micro-power LDO with piecewise voltage foldback current limit protection

    International Nuclear Information System (INIS)

    Wei Hailong; Liu Youbao; Guo Zhongjie; Liao Xue

    2012-01-01

    To achieve a constant current limit, low power consumption and high driving capability, a micro-power LDO with a piecewise voltage-foldback current-limit circuit is presented. The current-limit threshold is dynamically adjusted to achieve a maximum driving capability and lower quiescent current of only 300 nA. To increase the loop stability of the proposed LDO, a high impedance transconductance buffer under a micro quiescent current is designed for splitting the pole that exists at the gate of the pass transistor to the dominant pole, and a zero is designed for the purpose of the second pole phase compensation. The proposed LDO is fabricated in a BiCMOS process. The measurement results show that the short-circuit current of the LDO is 190 mA, the constant limit current under a high drop-out voltage is 440 mA, and the maximum load current under a low drop-out voltage is up to 800 mA. In addition, the quiescent current of the LDO is only 7 μA, the load regulation is about 0.56% on full scale, the line regulation is about 0.012%/V, the PSRR at 120 Hz is 58 dB and the drop-out voltage is only 70 mV when the load current is 250 mA. (semiconductor integrated circuits)

  6. State of the art of superconducting fault current limiters and their application to the electric power system

    International Nuclear Information System (INIS)

    Morandi, Antonio

    2013-01-01

    Highlights: ► The state of the art of superconducting fault current limiters is reviewed. ► An innovative concept of FCL is discussed and the potential of MgB 2 is outlined. ► The use of FCL to allow more interconnection of MV bus-bar is discussed. ► The use of FCL to increase the immunity from voltage dips is discussed. ► The use of FCL to integrate more distributed generation is pointed out. -- Abstract: Modern electric power systems are becoming more and more complex in order to meet new needs. Nowadays a high power quality is mandatory and there is the need to integrate increasing amounts of on-site generation. All this translates in more sophisticated electric network with intrinsically high short circuit rate. This network is vulnerable in case of fault and special protection apparatus and procedures needs to be developed in order to avoid costly or even irreversible damage. A superconducting fault current limiter (SFCL) is a device with a negligible impedance in normal operating conditions that reliably switches to a high impedance state in case of extra-current. Such a device is able to increase the short circuit power of an electric network and to contemporarily eliminate the hazard during the fault. It can be regarded as a key component for future electric power systems. In this paper the state of the art of superconducting fault current limiters mature for applications is briefly resumed and the potential impact of this device on the paradigm of design and operation of power systems is analyzed. In particular the use of the FCL as a mean to allow more interconnection of MV bus-bars as well an increased immunity with respect to the voltage disturbances induced by critical customer is discussed. The possibility to integrate more distributed generation in the distribution grid is also considered

  7. Design Aspects and Test of an Inductive Fault Current Limiter

    Directory of Open Access Journals (Sweden)

    Arsénio Pedro

    2014-05-01

    Full Text Available Magnetic shielding inductive fault current limiters with high temperature superconducting tapes are considered as emerging devices that provide technology for the advent of modern power grids. The development of such limiters requires magnetic iron cores and leads to several design challenges regarding the constitutive parts of the limiter, namely the primary and secondary windings. Preliminary tests in a laboratory scale prototype have been carried out considering an assembly designed for simplicity in which the optimization of the magnetic coupling between the primary and secondary was not the main focus. This work addresses the design configuration of an inductive current limiter prototype regarding the assembly of the primary and secondary windings in the core. The prototype is based on a closed magnetic core wound by a primary, built from a normal electric conductor, and a short-circuited secondary, built from first generation superconducting tape. Four different design configurations are considered. Through experimental tests, the performance of such prototype is discussed and compared, in terms of normal and fault operation regimes. The results show that all the configurations assure effective magnetic shielding at normal operation regime, however, at fault operation regime, there are differences among configurations.

  8. Estimated Historical and Current Nitrogen Balances for Illinois

    Directory of Open Access Journals (Sweden)

    Mark B. David

    2001-01-01

    Full Text Available The Midwest has large riverine exports of nitrogen (N, with the largest flux per unit area to the Mississippi River system coming from Iowa and Illinois. We used historic and current data to estimate N inputs, outputs, and transformations for Illinois where human activity (principally agriculture and associated landscape drainage have had a dominant impact. Presently, ~800,000 Mg of N is added each year as fertilizer and another 420,000 Mg is biologically fixed, primarily by soybean (Glycine max L. Merr.. These annual inputs are greater than exports in grain, which results in surplus N throughout the landscape. Rivers within the state export approximately 50% of this surplus N, mostly as nitrate, and the remainder appears to be denitrified or temporarily incorporated into the soil organic matter pool. The magnitude of N losses for 1880, 1910, 1950, and 1990 are compared. Initial cultivation of the prairies released large quantities of N (~500,000 Mg N year�1, and resulted in riverine N transport during the late 19th century that appears to have been on the same order of magnitude as contemporary N losses. Riverine flux was estimated to have been at a minimum in about 1950, due to diminished net mineralization and low fertilizer inputs. Residual fertilizer N from corn (Zea mays L., biological N fixed by soybean, short-circuiting of soil water through artificial drainage, and decreased cropping-system diversity appear to be the primary sources for current N export.

  9. Mechanism on radiation degradation of Si space solar cells

    International Nuclear Information System (INIS)

    Yamaguchi, Masafumi; Taylor, S.J.; Hisamatsu, Tadashi; Matsuda, Sumio

    1998-01-01

    Radiation testing of Si n + -p-p + structure space solar cells has revealed an anomalous increase in short-circuit current Isc, followed by an abrupt decrease and cell failure, induced by high fluence electron and proton irradiations. A model to explain these phenomena by expressing the change in carrier concentration p of the base region is proposed in addition to the well-known model where Isc is decreased by minority-carrier lifetime reduction with irradiation. Change in carrier concentration causes broadening the depletion layer to contribute increase in the generated photocurrent and increase in recombination-generation current in the depletion layer, and increase in the resistivity of the base layer to result in the abrupt decrease of Isc and failure of the solar cell. Type conversion from p-type to n-type in base layer has been confirmed by EBIC (electron-beam induced current) and spectral response measurements. Moreover, origins of radiation-induced defects in heavily irradiated Si and generation of deep donor defects have also been examined by using DLTS (deep level transient spectroscopy) analysis. (author)

  10. The effects of hypoxia on active ionic transport processes in the gill epithelium of hyperregulating crab, Carcinus maneas.

    Science.gov (United States)

    Lucu, Čedomil; Ziegler, Andreas

    2017-09-01

    Effects of hypoxia on the osmorespiratory functions of the posterior gills of the shore crab Carcinus maenas acclimated to 12ppt seawater (DSW) were studied. Short-circuit current (Isc) across the hemilamella (one epithelium layer supported by cuticle) was substantially reduced under exposure to 1.6, 2.0, or 2.5mg O 2 /L hypoxic saline (both sides of epithelium) and fully recovered after reoxygenation. Isc was reduced equally in the epithelium exposed to 1.6mg O 2 /L on both sides and when the apical side was oxygenated and the basolateral side solely exposed to hypoxia. Under 1.6mg O 2 /L, at the level of maximum inhibition of Isc, conductance was decreased from 40.0mScm -2 to 34.7mScm -2 and fully recovered after reoxygenation. Isc inhibition under hypoxia and reduced 86 Rb + (K + ) fluxes across apically located K + channels were caused preferentially by reversible inhibition of basolaterally located and ouabain sensitive Na + ,K + -ATPase mediated electrogenic transport. Reversible inhibition of Isc is discussed as decline in active transport energy supply down regulating metabolic processes and saving energy during oxygen deprivation. In response to a 4day exposure of Carcinus to 2.0mg O 2 /L, hemolymph Na + and Cl - concentration decreased, i.e. hyperosmoregulation was weakened. Variations of the oxygen concentration level and exposure time to hypoxia lead to an increase of the surface of mitochondria per epithelium area and might in part compensate for the decrease in oxygen availability under hypoxic conditions. Copyright © 2017 Elsevier Inc. All rights reserved.

  11. Modulation of ion transport across rat distal colon by cysteine

    Directory of Open Access Journals (Sweden)

    Martin eDiener

    2012-03-01

    Full Text Available The aim of this study was to identify the actions of stimulation of endogenous production of H2S by cysteine, the substrate for the two H2S-producing enzymes, cystathionin-beta-synthase and cystathionin-gamma-lyase, on ion transport across rat distal colon. Changes in short-circuit current (Isc induced by cysteine were measured in Ussing chambers. Free cysteine caused a concentration-dependent, transient fall in Isc, which was sensitive to amino-oxyacetate and beta-cyano-L-alanine, i.e. inhibitors of H2S-producing enzymes. In contrast, Na cysteinate evoked a biphasic change in Isc, i.e. an initial fall followed by a secondary increase, which was also reduced by these enzyme inhibitors. All responses were dependent on the presence of Cl- and inhibited by bumetanide, suggesting that free cysteine induces an inhibition of transcellular Cl- secretion, whereas Na cysteinate – after a transient inhibitory phase – activates anion secretion. The assumed reason for this discrepancy is a fall in the cytosolic pH induced by free cysteine, but not by Na cysteinate, as observed in isolated colonic crypts loaded with the pH-sensitive dye, BCECF. Intracellular acidification is known to inhibit epithelial K+ channels. Indeed, after preinhibition of basolateral K+ channels with tetrapentylammonium or Ba2+, the negative Isc induced by free cysteine was reduced significantly. In consequence, stimulation of endogenous H2S production by Na cysteinate causes, after a short inhibitory response, a delayed activation of anion secretion, which is missing in the case of free cysteine, probably due to the cytosolic acidification. In contrast, diallyl trisulfide, which is intracellularly converted to H2S, only evoked a monophasic increase in Isc without the initial fall observed with Na cysteinate. Consequently, time course and amount of produced H2S seem to strongly influence the functional response of the colonic epithelium evoked by this gasotransmitter.

  12. A superconducting direct-current limiter with a power of up to 8 MVA

    Science.gov (United States)

    Fisher, L. M.; Alferov, D. F.; Akhmetgareev, M. R.; Budovskii, A. I.; Evsin, D. V.; Voloshin, I. F.; Kalinov, A. V.

    2016-12-01

    A resistive switching superconducting fault current limiter (SFCL) for DC networks with a nominal voltage of 3.5 kV and a nominal current of 2 kA was developed, produced, and tested. The SFCL has two main units—an assembly of superconducting modules and a high-speed vacuum circuit breaker. The assembly of superconducting modules consists of nine (3 × 3) parallel-series connected modules. Each module contains four parallel-connected 2G high-temperature superconducting (HTS) tapes. The results of SFCL tests in the short-circuit emulation mode with a maximum current rise rate of 1300 A/ms are presented. The SFCL is capable of limiting the current at a level of 7 kA and break it 8 ms after the current-limiting mode begins. The average temperature of HTS tapes during the current-limiting mode increases to 210 K. After the current is interrupted, the superconductivity recovery time does not exceed 1 s.

  13. A superconducting direct-current limiter with a power of up to 8 MVA

    Energy Technology Data Exchange (ETDEWEB)

    Fisher, L. M.; Alferov, D. F., E-mail: DFAlferov@niitfa.ru; Akhmetgareev, M. R.; Budovskii, A. I.; Evsin, D. V.; Voloshin, I. F.; Kalinov, A. V. [National Technical Physics and Automation Research Institute (Russian Federation)

    2016-12-15

    A resistive switching superconducting fault current limiter (SFCL) for DC networks with a nominal voltage of 3.5 kV and a nominal current of 2 kA was developed, produced, and tested. The SFCL has two main units—an assembly of superconducting modules and a high-speed vacuum circuit breaker. The assembly of superconducting modules consists of nine (3 × 3) parallel–series connected modules. Each module contains four parallel-connected 2G high-temperature superconducting (HTS) tapes. The results of SFCL tests in the short-circuit emulation mode with a maximum current rise rate of 1300 A/ms are presented. The SFCL is capable of limiting the current at a level of 7 kA and break it 8 ms after the current-limiting mode begins. The average temperature of HTS tapes during the current-limiting mode increases to 210 K. After the current is interrupted, the superconductivity recovery time does not exceed 1 s.

  14. Research on resistance characteristics of YBCO tape under short-time DC large current impact

    Science.gov (United States)

    Zhang, Zhifeng; Yang, Jiabin; Qiu, Qingquan; Zhang, Guomin; Lin, Liangzhen

    2017-06-01

    Research of the resistance characteristics of YBCO tape under short-time DC large current impact is the foundation of the developing DC superconducting fault current limiter (SFCL) for voltage source converter-based high voltage direct current system (VSC-HVDC), which is one of the valid approaches to solve the problems of renewable energy integration. SFCL can limit DC short-circuit and enhance the interrupting capabilities of DC circuit breakers. In this paper, under short-time DC large current impacts, the resistance features of naked tape of YBCO tape are studied to find the resistance - temperature change rule and the maximum impact current. The influence of insulation for the resistance - temperature characteristics of YBCO tape is studied by comparison tests with naked tape and insulating tape in 77 K. The influence of operating temperature on the tape is also studied under subcooled liquid nitrogen condition. For the current impact security of YBCO tape, the critical current degradation and top temperature are analyzed and worked as judgment standards. The testing results is helpful for in developing SFCL in VSC-HVDC.

  15. FCL: A solution to fault current problems in DC networks

    International Nuclear Information System (INIS)

    Cointe, Y; Tixador, P; Villard, C

    2008-01-01

    Within the context of the electric power market liberalization, DC networks have many interests compared to AC ones. New energy landscapes open the way of a diversified production. Innovative interconnection diagrams, in particular using DC buses, are under development. In this case it is not possible to defer the fault current interruption in the AC side. DC fault current cutting remains a difficult problem. FCLs (Fault Current Limiters) enable to limit the current to a preset value, lower than the theoretical short-circuit current. For this application Coated Conductors (CC) offer an excellent opportunity. Due to these promising characteristics we build a test bench and work on the implementation of these materials. The test bench is composed by 10 power amplifiers, to reach 4 kVA in many configurations of current and voltage. We carried out limiting experiments on DyBaCuO CC from EHTS, samples are about five centimeters long and many potential measuring points are pasted on the shunt to estimate the quench homogeneity. Thermal phenomena in FCLs are essential, numerical models are important to calculate the maximum temperatures. To validate these models we measure the CC temperature by depositing thermal sensors (Cu resistance) above the shunt layer and the substrate. An electrical insulation with a low thermal resistivity between the CC and the sensors is necessary. We use a thin layer of Parylene because of its good mechanical and electrical insulation properties at low temperature. The better quench behaviour of CC for temperatures close to the critical temperature has been confirmed. The measurements are in good agreement with simulations, this validates the thermal models

  16. Electrophysiological response of chicken's jejunal epithelium to increasing levels of T-2 toxin.

    Science.gov (United States)

    Yunus, Agha Waqar; Kröger, Susan; Tichy, Alexander; Zentek, Jürgen; Böhm, Josef

    2013-02-01

    The present investigations were conducted to test the effects of T-2 toxin on electrophysiological variables of jejunal epithelium of chicken. Jejunal segments of broilers were monitored in Ussing chambers in the presence of T-2 toxin at the levels of 0 (negative control), 0 (methanol/vehicle control), 0.1, 1, 5, and 10 μg/ml of buffer. T-2 toxin did not affect basal values of short circuit current (I(sc)), transmural potential difference, or tissue conductivity in the jejunal epithelium. T-2 toxin also did not statistically affect glucose-induced electrophysiological variables during the first 3 min of glucose induction. Compared to the vehicle control, the ouabain-sensitive I(sc) was negatively affected (P = 0.008) only under 5 μg of T-2 toxin/ml. Increasing levels of T-2 toxin negatively affected the ouabain-sensitive I(sc) in a cubic (P = 0.007) fashion. These data indicate that acute exposure to moderate levels of T-2 toxin may progressively impair the cation gradient across the jejunal epithelium.

  17. Electrophysiological evidence for an ATP-gated ion channel in the principal cells of the frog skin epithelium

    DEFF Research Database (Denmark)

    Brodin, Birger; Nielsen, Robert

    2000-01-01

    P2X receptor, Na+ absorption, Short circuit current, Cell potential, Microelectrodes, Frog skin, Cytosolic Ca2+......P2X receptor, Na+ absorption, Short circuit current, Cell potential, Microelectrodes, Frog skin, Cytosolic Ca2+...

  18. Axonal and glial currents activated during the post-tetanic hyperpolarization in non-myelinated nerve.

    Science.gov (United States)

    Robert, A; Jirounek, P

    1998-07-01

    Changes in membrane potential and potassium concentration in the extracellular space ([K+]e) of rabbit vagus nerve were measured simultaneously during electrical activity and during the period of recovery using a modified sucrose-gap method and potassium-sensitive microelectrodes. After stimulation for 15 s at 15 Hz the main activity-induced increase in [K+]e reached 16.9 mM. This increase in [K+]e was paralleled by a depolarization of the preparation. The period of activity was followed by a post-tetanic hyperpolarization (PTH) lasting tens of seconds, generated by the axonal electrogenic Na+-K+ pump and to a lesser extent by the pump of the surrounding Schwann cells. The amplitude of the PTH dramatically increased in experiments in which inward currents were blocked by removal of Cl– or after application of Cs+ or Ba2+, indicating that under normal conditions the current generated by the Na+-K+ pump is strongly short-circuited. A pharmacological and kinetic study showed that these currents are: (1) the hyperpolarization-activated current I h, and (2) the inwardly rectifying I KIR current. The results show that the latter originates from Schwann cells. Our data indicate that in non-myelinated nerves there is a subtle association of inward ionic channels which (1) helps the cell to maintain an optimal membrane potential after a period of activity, and (2) contributes to the removal of excess K+ from the extracellular space.

  19. Experiment study on an inductive superconducting fault current limiter using no-insulation coils

    Science.gov (United States)

    Qiu, D.; Li, Z. Y.; Gu, F.; Huang, Z.; Zhao, A.; Hu, D.; Wei, B. G.; Huang, H.; Hong, Z.; Ryu, K.; Jin, Z.

    2018-03-01

    No-insulation (NI) coil made of 2 G high temperature superconducting (HTS) tapes has been widely used in DC magnet due to its excellent performance of engineering current density, thermal stability and mechanical strength. However, there are few AC power device using NI coil at present. In this paper, the NI coil is firstly applied into inductive superconducting fault current limiter (iSFCL). A two-winding structure air-core iSFCL prototype was fabricated, composed of a primary copper winding and a secondary no-insulation winding using 2 G HTS coated conductors. Firstly, in order to testify the feasibility to use NI coil as the secondary winding, the impedance variation of the prototype at different currents and different cycles was tested. The result shows that the impedance increases rapidly with the current rises. Then the iSFCL prototype was tested in a 40 V rms/ 3.3 kA peak short circuit experiment platform, both of the fault current limiting and recovery property of the iSFCL are discussed.

  20. Weak currents

    International Nuclear Information System (INIS)

    Leite Lopes, J.

    1976-01-01

    A survey of the fundamental ideas on weak currents such as CVC and PCAC and a presentation of the Cabibbo current and the neutral weak currents according to the Salam-Weinberg model and the Glashow-Iliopoulos-Miami model are given [fr

  1. Spin current

    CERN Document Server

    Valenzuela, Sergio O; Saitoh, Eiji; Kimura, Takashi

    2012-01-01

    In a new branch of physics and technology called spin-electronics or spintronics, the flow of electrical charge (usual current) as well as the flow of electron spin, the so-called 'spin current', are manipulated and controlled together. This book provides an introduction and guide to the new physics and application of spin current.

  2. The adenosine A2B receptor is involved in anion secretion in human pancreatic duct Capan-1 epithelial cells

    DEFF Research Database (Denmark)

    Hayashi, M.; Inagaki, A.; Novak, Ivana

    2016-01-01

    Adenosine modulates a wide variety of biological processes via adenosine receptors. In the exocrine pancreas, adenosine regulates transepithelial anion secretion in duct cells and is considered to play a role in acini-to-duct signaling. To identify the functional adenosine receptors and Cl......− channels important for anion secretion, we herein performed experiments on Capan-1, a human pancreatic duct cell line, using open-circuit Ussing chamber and gramicidin-perforated patch-clamp techniques. The luminal addition of adenosine increased the negative transepithelial potential difference (Vte......) in Capan-1 monolayers with a half-maximal effective concentration value of approximately 10 μM, which corresponded to the value obtained on whole-cell Cl− currents in Capan-1 single cells. The effects of adenosine on Vte, an equivalent short-circuit current (Isc), and whole-cell Cl− currents were inhibited...

  3. An analytical-numerical approach for parameter determination of a five-parameter single-diode model of photovoltaic cells and modules

    Science.gov (United States)

    Hejri, Mohammad; Mokhtari, Hossein; Azizian, Mohammad Reza; Söder, Lennart

    2016-04-01

    Parameter extraction of the five-parameter single-diode model of solar cells and modules from experimental data is a challenging problem. These parameters are evaluated from a set of nonlinear equations that cannot be solved analytically. On the other hand, a numerical solution of such equations needs a suitable initial guess to converge to a solution. This paper presents a new set of approximate analytical solutions for the parameters of a five-parameter single-diode model of photovoltaic (PV) cells and modules. The proposed solutions provide a good initial point which guarantees numerical analysis convergence. The proposed technique needs only a few data from the PV current-voltage characteristics, i.e. open circuit voltage Voc, short circuit current Isc and maximum power point current and voltage Im; Vm making it a fast and low cost parameter determination technique. The accuracy of the presented theoretical I-V curves is verified by experimental data.

  4. Development of a digital solar simulator based on full-bridge converter

    Science.gov (United States)

    Liu, Chen; Feng, Jian; Liu, Zhilong; Tong, Weichao; Ji, Yibo

    2014-02-01

    With the development of solar photovoltaic, distribution schemes utilized in power grid had been commonly application, and photovoltaic (PV) inverter is an essential equipment in grid. In this paper, a digital solar simulator based on full-bridge structure is presented. The output characteristic curve of system is electrically similar to silicon solar cells, which can greatly simplify research methods of PV inverter, improve the efficiency of research and development. The proposed simulator consists on a main control board based on TM320F28335, phase-shifted zero-voltage-switching (ZVS) DC-DC full-bridge converter and voltage and current sampling circuit, that allows emulating the voltage-current curve with the open-circuit voltage (Voc) of 900V and the short-circuit current (Isc) of 18A .When the system connected to a PV inverter, the inverter can quickly track from the open-circuit to the maximum power point and keep stability.

  5. Structural, electrical, and photoelectric properties of p-NiO/n-CdTe heterojunctions

    Science.gov (United States)

    Parkhomenko, Hryhorii; Solovan, Mykhaylo; Brus, Viktor; Maystruk, Eduard; Maryanchuk, Pavlo

    2018-01-01

    p-NiO/n-CdTe-photosensitive heterojunctions were prepared by the deposition of nickel oxide thin films onto n-type single-crystal CdTe substrates by DC reactive magnetron sputtering. The analysis of capacitance-voltage (C-V) characteristics, measured at different frequencies of the small amplitude AC signal and corrected by the effect of the series resistance, provided evidence of the presence of electrically charged interface states, which significantly affect the measured capacitance. The dominant current transport mechanisms in the heterojunctions were determined at forward and reverse biases. Using "light" I-V characteristics, we determined the open-circuit voltage Voc=0.42 V, the short-circuit current Isc=57.5 μA/cm2, and the fill factor FF=0.24 under white light illumination with the intensity of 80 mW.

  6. Hypotonicity induced K+ and anion conductive pathways activation in eel intestinal epithelium

    DEFF Research Database (Denmark)

    Lionetto, M G; Giordano, M E; De Nuccio, F

    2005-01-01

    , the activation of 'emergency' systems of rapid cell volume regulation is fundamental in their physiology. The aim of the present work was to study the physiological response to hypotonic stress in a salt-transporting epithelium, the intestine of the euryhaline teleost Anguilla anguilla. Eel intestinal epithelium......, when symmetrically bathed with Ringer solution, develops a net Cl- current giving rise to a negative transepithelial potential at the basolateral side of the epithelium. The eel intestinal epithelium responded to a hypotonic challenge with a biphasic decrease in the transepithelial voltage (V......(te)) and the short circuit current (I(sc)). This electrophysiological response correlated with a regulatory volume decrease (RVD) response, recorded by morphometrical measurement of the epithelium height. Changes in the transepithelial resistance were also observed following the hypotonicity exposure...

  7. Silicon nanowire array architecture for heterojunction electronics

    International Nuclear Information System (INIS)

    Solovan, M. M.; Brus, V. V.; Mostovyi, A. I.; Maryanchuk, P. D.; Orletskyi, I. G.; Kovaliuk, T. T.; Abashin, S. L.

    2017-01-01

    Photosensitive nanostructured heterojunctions n-TiN/p-Si were fabricated by means of titanium nitride thin films deposition (n-type conductivity) by the DC reactive magnetron sputtering onto nano structured single crystal substrates of p-type Si (100). The temperature dependencies of the height of the potential barrier and series resistance of the n-TiN/p-Si heterojunctions were investigated. The dominant current transport mechanisms through the heterojunctions under investigation were determined at forward and reverse bias. The heterojunctions under investigation generate open-circuit voltage V_o_c = 0.8 V, short-circuit current I_s_c = 3.72 mA/cm"2 and fill factor FF = 0.5 under illumination of 100 mW/cm"2.

  8. Effect of solution concentration on MEH-PPV thin films

    Science.gov (United States)

    Affendi, I. H. H.; Sarah, M. S. P.; Alrokayan, Salman A. H.; Khan, Haseeb A.; Rusop, M.

    2018-05-01

    MEH-PPV thin films were prepared with a mixture of THF (tetrahydrofuran) solution deposited by spin coating method. The surface topology of MEH-PPV thin film were characterize by atomic force microscopy (AFM) and optical properties of absorption spectra were characterized by using Ultraviolet-visible-near-infrared (UV-Vis-NIR). The MEH-PPV concentration variation affects the surface and optical properties of the thin film where 0.5 mg/ml MEH-PPV concentration have a good surface topology provided the same film also gives the highest absorption coefficient were then deposited to a TiO2 thin film forming composite layer. The composite layer then shows low current flow of short circuit current of Isc = -5.313E-7 A.

  9. Study of a Betavoltaic Battery Using Electroplated Nickel-63 on Nickel Foil as a Power Source

    Directory of Open Access Journals (Sweden)

    Young Rang Uhm

    2016-06-01

    Full Text Available A betavoltaic battery was prepared using radioactive 63Ni attached to a three-dimensional single trenched P–N absorber. The optimum thickness of a 63Ni layer was determined to be approximately 2 μm, considering the minimum self-shielding effect of beta particles. Electroplating of radioactive 63Ni on a nickel (Ni foil was carried out at a current density of 20 mA/cm2. The difference of the short-circuit currents (Isc between the pre- and postdeposition of 63Ni (16.65 MBq on the P–N junction was 5.03 nA, as obtained from the I–V characteristics. An improved design with a sandwich structure was provided for enhancing performance.

  10. Lithium-Ion Battery Safety Study Using Multi-Physics Internal Short-Circuit Model (Presentation)

    Energy Technology Data Exchange (ETDEWEB)

    Kim, G-.H.; Smith, K.; Pesaran, A.

    2009-06-01

    This presentation outlines NREL's multi-physics simulation study to characterize an internal short by linking and integrating electrochemical cell, electro-thermal, and abuse reaction kinetics models.

  11. Short circuit : how brain connectivity and disconnectivity relate to brain function

    OpenAIRE

    Langen, Carolyn

    2018-01-01

    markdownabstractThe brain is like a super computer: it is a collection of interconnected computational units which work together to enable both basic functions, such as regulation of breathing, as well as higher functions, such as cognition, thought and emotion. The computational units, or regions, are located in the grey matter (i.e. the cortical surface and in the subcortex), whereas the connections between them, or tracts, are found in the white matter. The development and maintenance of b...

  12. Control of Internal and External Short Circuits in Lithium Ion and Lithium Batteries, Phase I

    Data.gov (United States)

    National Aeronautics and Space Administration — NASA has identified needs for compact high-energy-density primary and secondary batteries. Lithium and Lithium Ion cells, respectively, are meeting these needs for...

  13. Short circuit behavior of distribution grids with a large share of distributied generation units

    NARCIS (Netherlands)

    Coster, E.J.; Karaliolios, P.; Xyngi, I.; Slootweg, J.G.; Popov, M.; Kling, W.L.; Sluis, van der L.

    2011-01-01

    increasing rapidly. Most of these units are connected to the distribution grid. With the increasing penetration level the impact of these units on for instance power flows, fault levels and protective systems cannot be neglected anymore. To allow an increasing penetration level of DG without causing

  14. Short Circuits or Superconductors? Effects of Group Composition on High-Achieving Students' Science Assessment Performance.

    Science.gov (United States)

    Webb, Noreen M.; Nemer, Kariane Mari; Zuniga, Stephen

    2002-01-01

    Studied the effects of group ability composition (homogeneous versus heterogeneous) on group processes and outcomes for high-ability students completing science assessments. Results for 83 high ability students show the quality of group functioning serves as the strongest predictor of high-ability students' performance and explained much of the…

  15. Proton exchange membrane fuel cell operation and degradation in short-circuit.

    OpenAIRE

    Silva , R.E.; Harel , F.; Jemei , S.; Gouriveau , Rafael; Hissel , Daniel; Boulon , L.; Agbossou , K.

    2013-01-01

    International audience; Hybridization of proton exchange membrane fuel cells (PEMFC) and ultra capacitors (UC) are considered as an alternative way to implement high autonomy, high dynamic, and reversible energy sources. PEMFC allow high efficiency and high autonomy, however their dynamic response is limited and this source does not allow recovering energy. UC appears to be a complementary source to fuel cell systems (FCS) due to their high power density, fast dynamics, and reversibility. A d...

  16. Determination of short circuit stresses in an air core reactor using ...

    African Journals Online (AJOL)

    DR OKE

    developed has crossed the boundary condition limit of 70 MPa whereas the ... The method can be used to identify the inter layer forces ... Power transformer design using magnetic circuit theory and finite element analysis – A Comparison.

  17. Transient short-circuit behaviour of distributed energy sources and their influence on protection coordination conference

    NARCIS (Netherlands)

    Geldtmeijer, D.A.M.; Provoost, F.; Myrzik, J.M.A.; Kling, W.L.

    2006-01-01

    This paper presents the results obtained by research on the influence of distributed generation (DG) on protection in the distribution network. Generation connected to the grid is subject to protection regulations. Applying the present regulations to distributed generation results in unnecessary

  18. Light-current-induced acceleration of degradation of methylammonium lead iodide perovskite solar cells

    Science.gov (United States)

    Xiang, Yuren; Zhang, Fan; He, Junjie; Lian, Jiarong; Zeng, Pengju; Song, Jun; Qu, Junle

    2018-04-01

    The photo-conversion efficiency of perovskite solar cells (PSCs) has been improved considerably in recent years, but the poor stability of PSCs still prevents their commercialization. In this report, we use the rate of the integrated short-circuit current change (Drate) to investigate the performance degradation kinetics and identify the degradation of PSCs that is accelerated by the light current. The value of Drate increases by an order of magnitude from about 0.02 to 0.35 mA cm-2·min-1 after light-IV testing. The accelerated degradation progress is proven to be dominated by the hydration process and the migration of the iodine ions of the light current. The migration of the iodine ions enhances the hydration process through a chain reaction, enabling the formation of fast diffusion channels for both H2O and O2, which induce the rapid decomposition of the perovskite film and increase the density of the trap state. The X-ray photoelectron spectroscopy measurement data also indicate that the super oxygen may be formed due to the PCBM damage caused by the migration iodine ions. An understanding of the degradation acceleration mechanism would provide an insight into the effect of ion migration on the stability of PSCs.

  19. Spin current

    CERN Document Server

    Valenzuela, Sergio O; Saitoh, Eiji; Kimura, Takashi

    2017-01-01

    Since the discovery of the giant magnetoresistance effect in magnetic multilayers in 1988, a new branch of physics and technology, called spin-electronics or spintronics, has emerged, where the flow of electrical charge as well as the flow of electron spin, the so-called “spin current,” are manipulated and controlled together. The physics of magnetism and the application of spin current have progressed in tandem with the nanofabrication technology of magnets and the engineering of interfaces and thin films. This book aims to provide an introduction and guide to the new physics and applications of spin current, with an emphasis on the interaction between spin and charge currents in magnetic nanostructures.

  20. Technique and Calculation Results of Currents and Voltages in the Circuits of the Measuring Element of the Protection Device of the Transmission Line Based on the Control of Transient Processes

    Science.gov (United States)

    Lachugin, V. F.; Kulikov, A. L.; Platonov, P. S.; Vucolov, V. Yu.

    2017-12-01

    The specifics of generation of the signals of current and voltage in the circuits of a directional element of wave relay protection during short circuit (SC) in overhead power transmission lines are considered. The computing method of transient processes in the protection circuits, including frequency filters, that attenuate the parameters of currents and voltages of the mode taking into account the higher harmonic components and probable deviations of the frequency of transmission line from the rated value is presented. It is revealed that it is advisable to implement the measuring circuits of the directional elements of wave relay protection with the three-section filter attenuating the frequencies from 45 to 55 Hz and the low pass filter with cutoff frequency that does not exceed 1 kHz.