WorldWideScience

Sample records for kv power systems

  1. Development of 66 kV/6.9 kV 2 MV A prototype HTS power transformer

    International Nuclear Information System (INIS)

    Bohno, T.; Tomioka, A.; Imaizumi, M.; Sanuki, Y.; Yamamoto, T.; Yasukawa, Y.; Ono, H.; Yagi, Y.; Iwadate, K.

    2005-01-01

    We have developed the technology of the producing a HTS magnet for the power transformer. Three subjects have been mainly studied, high voltage technologies, large current and low AC loss technologies and sub-cooling system technologies to establish the technology of 66 kV/6.9 kV 10 MV A class HTS power transformer. In order to verify the validity of elemental technologies, such as high voltage technologies, large current and low AC loss technologies and sub-cooling system technologies, single-phase 2 MV A class 66 kV/6.9 kV prototype HTS transformer was manufactured and tested. In the load loss (AC loss) measurement, it was obtained that the measured value of 633 W was almost corresponding to the calculated value of 576 W at the rated operation of 2 MV A. Moreover, the breakdown was not found all voltage withstand test. These test results indicate that elemental technologies were established for the development of 66 kV/6.9 kV 10 MV A class HTS power transformer

  2. Novel adaptive distance relay algorithm considering the operation of 154 kV SFCL in Korean power transmission system

    International Nuclear Information System (INIS)

    Lee, S.; Lee, J.; Song, S.; Yoon, J.; Lee, B.

    2015-01-01

    Highlights: • This paper presents an outline of the new project of the 154 kV SFCL in Korea. • And then we review some protection problems for the application of 154 kV SFCLs. • This paper proposes a new adaptive protection algorithm for 154 kV SFCLs. • The developed algorithm is tested in a simple distance relay system. - Abstract: In general, SFCLs can have a negative impact on the protective coordination in power transmission system because of the variable impedance of SFCLs. It is very important to solve the protection problems of the power system for the successful application of SFCLs to real power transmission system. This paper reviews some protection problems which can be caused by the application of 154 kV SFCLs to power transmission systems in South Korea. And then we propose an adaptive protection algorithm to solve the problems. The adaptive protection algorithm uses the real time information of the SFCL system operation.

  3. Performance of the 10-kV, 5-MA pulsed-power system for the FRX-C compression experiment

    International Nuclear Information System (INIS)

    Rej, D.J.; Waganaar, W.J.

    1991-01-01

    Performance data are presented for the 10-kV, 5-MA, 1.5-MJ pulsed-power system developed for the Los Alamos magnetic fusion facility FRX-C. This system energizes a low-inductance magnet for the high-power, compression heating of compact toroid plasmas. An ignitron-switched, 20-mF, 10-kV, 4-MA capacitor bank is discharged to produce the main compression field, while an inductively-isolated, 10-mF, 10-kV, 1-MA bank generates an initial magnetic field to accept the translated plasma. To date, the complete system has successfully operated for two years and approximately 2000 high-power discharges. Component performance during typical and fault-mode operation is reviewed. 5 refs., 5 figs

  4. FPGA based control system for -100 kV, 25 A Crowbarless DC power supply

    International Nuclear Information System (INIS)

    Upadhyay, R.; Tripathi, A.; Badapanda, M.K.; Lad, M.

    2015-01-01

    FPGA based digital control system has been developed for -100 kV, 25 A solid state modular crowbarless DC klystron bias power supply of 1 MW, 352.2 MHz RF test stand. The control system has capability to operate this power supply either in CW or pulse mode. Central controller, PSM controller and graphical user interface are key parts of this control system. Central controller monitors the status of various subsystems of this power supply like 11 kV step start unit, four numbers of main transformers each having 44 numbers of secondary windings and 176 numbers of switch power modules for deciding the number of power modules to be put ON and their duty cycles depending on the set output voltage and current. PSM controller sends appropriate control signal to the switch power modules through fibre optic lines and communicates it to the central controller. Linux based graphical user interface has been developed which enables the user to set the operating parameters along with their trip limits and displays the information of critical parameters of this power supply on a local touch screen panel. Provision for remote control and supervision is also provided through a separate PC connected to the main control system via Ethernet. The control system has capability to trip the power supply within 5 μsec in case any parameter exceeds its set limit. Suitable data logging feature is incorporated for offline fault analysis. The control system architecture along with its software protection interlocks are presented in this paper. The performance of the control system has been verified during operation of -100 kV, 25 A DC power supply with 1 MW, 352.2 MHz klystron amplifier. (author)

  5. 250 kV 6 mA compact Cockcroft-Walton high-voltage power supply

    Energy Technology Data Exchange (ETDEWEB)

    Ma, Zhan-Wen; Su, Xiao-Dong; Wei, Zhen; Huang, Zhi-Wu; Miao, Tian-You; Su, Tong-Ling [School of Nuclear Science and Technology, Lanzhou University, Lanzhou 730000 (China); Lu, Xiao-Long; Wang, Jun-Run; Yao, Ze-En, E-mail: zeyao@lzu.edu.cn [School of Nuclear Science and Technology, Lanzhou University, Lanzhou 730000 (China); Engineering Research Center for Neutron Application, Ministry of Education, Lanzhou University, Lanzhou 730000 (China)

    2016-08-15

    A compact power supply system for a compact neutron generator has been developed. A 4-stage symmetrical Cockcroft-Walton circuit is adopted to produce 250 kV direct current high-voltage. A 2-stage 280 kV isolation transformer system is used to drive the ion source power supply. For a compact structure, safety, and reliability during the operation, the Cockcroft-Walton circuit and the isolation transformer system are enclosed in an epoxy vessel containing the transformer oil whose size is about ∅350 mm × 766 mm. Test results indicate that the maximum output voltage of the power supply is 282 kV, and the stability of the output voltage is better than 0.63% when the high voltage power supply is operated at 250 kV, 6.9 mA with the input voltage varying ±10%.

  6. Long-pulse neutral beam power supply system for LBL 20 kV, 10 A sources

    International Nuclear Information System (INIS)

    Honey, V.J.; Baker, W.R.; Fitzgerald, M.L.

    1976-05-01

    A description is given of the power supplies and control system for the LBL 20 kV, 10 A, 10 sec long-pulse neutral beam source test facility, now in operation. Such sources are used in a number of existing and planned fusion power experiments

  7. Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) : Part 2: cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)

    CERN Document Server

    International Electrotechnical Commission. Geneva

    2005-01-01

    Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) : Part 2: cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)

  8. Development of a 400 kV 80 mA Cockcroft-Walton power supply and 12 kW isolation transformer systems for neutron generators

    Science.gov (United States)

    Lu, X.; Chen, S.; Zhang, Y.; Huang, Z.; Ma, Z.; Yao, Z.

    2017-06-01

    A 400 kV 80 mA Cockcroft-Walton power supply driven by 2.5 kHz frequency, and 12 kW isolation transformer systems are developed for an intense DD/DT neutron generator. The design, construction, and testing of the high voltage (HV) power supply and isolation transformer systems are detailed reported. The structure of step-up transformers can make the potential distribution uniform, and auxiliary coils of the isolation transformers can improve the power transmission efficiency significantly. The testing results show that the HV power supply can reach 400 kV, and the isolation transformer systems can withstand 400 kV voltages and its power transmission efficiency is about 98.1%.

  9. Design and performance of the 10-kV, 5-MA pulsed-power system for the FRX-C compression experiment

    International Nuclear Information System (INIS)

    Rej, D.J.; Barnes, G.A.; Gribble, R.J.; Hinckley, J.E.; Kreider, T.W.; Waganaar, W.J.

    1989-05-01

    The design and performance of the pulsed-power system for the FRX-C compact toroid compression heating experiment are reviewed. Two inductively-isolated, 10-kV capacitor banks (total energy = 1.5 MJ) are discharged through a common, low-inductance load. The 5-MA currents are switched and crowbarred with parallel arrays of size-D ignitrons. Power supplies are constructed in simple 25 and 50 kJ modules, each capable of supplying 100 kA at 10 kV. Non-negligible source inductance and the addition of high-power resistors maintain module isolation and protect the system during fault modes. 21 refs., 31 figs

  10. MFTF 230 kV pulsed power substation

    International Nuclear Information System (INIS)

    Wilson, J.H.

    1979-01-01

    The Mirror Fusion Test Facility (MFTF) currently under construction at the Lawrence Livermore Laboratory includes a Sustaining Neutral Beam Power Supply System (SNBPSS) consisting of 24 power-supply sets. The System will operate in long pulses (initially .5 seconds and eventually 30 seconds) at high power (200 MW), which will necessitate a large source of ac power. To meet this requirement, a new 230-kV substation is also being built at LLL. The constraints of cost, equipment protection, short operating lifetime (10 years), and reliability dictated a unique substation design. Its unusual features include provisions for fast fault detection and tripping, a capability for limiting ground fault current, low impedance, and economical design

  11. Diagnostics system for the 67 MJ, 50 kV pulsed power capacitor bank

    Energy Technology Data Exchange (ETDEWEB)

    Galakhov, I V; Gasheev, A S; Gruzin, I A; Gudov, S N; Murugov, V M; Osin, V A; Pankratov, V I; Pegoev, I N [All-Russian Scientific Research Inst. of Experimental Physics, Sarov (Russian Federation)

    1997-12-31

    The diagnostics system is designed for charging and discharging to the load of the large 67 MJ and 50 kV capacitor bank for the iodine laser pulse power of ISKRA-5 facility. Discharging diagnostics of the capacitor bank uses a technique to measure a sequence of times between representative discharge events for 665 discharge circuits of the bank. Benefits of the measurement techniques are discussed. (author). 3 figs., 3 refs.

  12. Diagnostics system for the 67 MJ, 50 kV pulsed power capacitor bank

    International Nuclear Information System (INIS)

    Galakhov, I.V.; Gasheev, A.S.; Gruzin, I.A.; Gudov, S.N.; Murugov, V.M.; Osin, V.A.; Pankratov, V.I.; Pegoev, I.N.

    1996-01-01

    The diagnostics system is designed for charging and discharging to the load of the large 67 MJ and 50 kV capacitor bank for the iodine laser pulse power of ISKRA-5 facility. Discharging diagnostics of the capacitor bank uses a technique to measure a sequence of times between representative discharge events for 665 discharge circuits of the bank. Benefits of the measurement techniques are discussed. (author). 3 figs., 3 refs

  13. Power System Reliability Assessment by Analysing Voltage Dips on the Blue Horizon Bay 22KV Overhead Line in the Nelson Mandela Bay Municipality

    Science.gov (United States)

    Lamour, B. G.; Harris, R. T.; Roberts, A. G.

    2010-06-01

    Power system reliability problems are very difficult to solve because the power systems are complex and geographically widely distributed and influenced by numerous unexpected events. It is therefore imperative to employ the most efficient optimization methods in solving the problems relating to reliability of the power system. This paper presents a reliability analysis and study of the power interruptions resulting from severe power outages in the Nelson Mandela Bay Municipality (NMBM), South Africa and includes an overview of the important factors influencing reliability, and methods to improve the reliability. The Blue Horizon Bay 22 kV overhead line, supplying a 6.6 kV residential sector has been selected. It has been established that 70% of the outages, recorded at the source, originate on this feeder.

  14. Compact 250-kV injector system for PIGMI

    International Nuclear Information System (INIS)

    Hamm, R.W.; Stevens, R.R. Jr.; Mueller, D.W.; Lederer, H.M.

    1978-01-01

    A 250-kV proton injector to be used in the development of a linac suitable for medical applications has been constructed. This injector utilizes a spherical Pierce geometry to produce a converging beam. A gas insulated accelerating column is cantilevered on a grounded vacuum system, with a separate high voltage equipment dome connected to a 300-kV Cockcroft-Walton power supply. The injector can be operated locally or remotely, with the remote control accomplished by a microprocessor system linked to a central control minicomputer. This injector has been designed as a low-cost compact system. The design details and the data obtained during initial operation are presented

  15. THE COMPARATIVE ANALYSIS OF ECONOMIC DISPATCH AND OPTIMAL POWER FLOW METHODS FOR 22-BUS 380-kV POWER SYSTEM IN TURKEY

    Directory of Open Access Journals (Sweden)

    Mehmet KURBAN

    2007-03-01

    Full Text Available In this paper, the economic dispatch and optimal power flow (OPF methods for the purpose of supplying the load demand with minimum cost is used for 22-bus 380-kV power system in Turkey which consists of 8 thermal plants operated by EUAS (Electricity Generation Co. Inc.and the results found are analyzed comparatively. The results of analysis are given in tables and figures. The analysis made is implemented by the software using MATLAB®. Furthermore, the software can be used for different power systems by using the graphical user interface (GUI. All data used in this study is taken from TEIAS (Transmission System Operator of Turkey and EUAS.

  16. Step-by-step application methodology in practical KEPCO 22.9kV bus-bar system

    International Nuclear Information System (INIS)

    Yoon, Jae-young; Lee, Seung-yeol

    2010-01-01

    With the increase of power demand and the progress of power industry deregulation, the transmission and distribution systems will have more complicated problems by the influence of curtailing investment and the NIMBY phenomena in overall power systems. [1-2] It is expected that the route length per MW demand of South Korea will decrease gradually from 0.6[C-km/MW] to 0.53[C-km/MW] in 2010.[3] This comes up to a real serious problem from system planning and operation viewpoints. HTS technologies related to power system have properties to solve these complex transmission and distribution constraints, especially for metropolitan area, in the future. As the HTS technology has developed, the HTS cable technology can be the most effective alternative to solve the future expected power network constraints. This paper describes the application methodology of developing 22.9kV HTS cable by CAST for practical distribution system. 22.9kV HTS cable under development with step-by-step application methodology can substitute the existing and planning conventional 154kV cable.[4-5] If this scheme is applied, part of downtown 154kV substation of metropolitan city such as Seoul can be changed into 22.9kV switching station. Additionally, it can give huge economic, environmental benefits to all of the concerned authorities.

  17. Reliability assessment of Port Harcourt 33/11kv Distribution System ...

    African Journals Online (AJOL)

    This makes reliability studies an important task besides all the other analyses required for assessing the system performance. The paper presents an analytical approach in the reliability assessment of the Port Harcourt 33/11kV power distribution system. The assessment was performed with the 2009 power outage data ...

  18. 100 kV solid-state switch for fusion heating systems

    International Nuclear Information System (INIS)

    Beaumont, B.; Bertrand, E.; Brugnetti, R.; Chatroux, D.; Kazarian, F.; Milly, R.; Prou, M.; Rigole, H.

    2005-01-01

    Power switching in RF heating systems is a delicate function as it is often linked to high power tube protection. In most RF systems, the end stage power tube is fed by a high voltage power supply (HVPS), which connection to the tube has to be interrupted in case of arc suspicion. The amount of energy that is allowable to be dissipated in the arc is in the range of 10-50 J, to limit the degradations observed on the tube structures. The protection function is usually performed by a crowbar. Furthermore, the HVPS is often shared by several power tubes, and the loss of all the power from the group of tubes is to be avoided to minimize the perturbation on the plasma experiment. A description of a 40 kV thyristor based crowbar and a 100 kV, 25 A MOSFET switch is given, as well as the contours of the existing components for high power switching applications. By combining small components, such as thyristors or MOSFET, in matrix, highly compact and reliable units have been built and implemented in Tore Supra RF systems

  19. The Reviewing of Distributed Power Sources Impact on Fallout’s Localization in 22 kV Network

    Directory of Open Access Journals (Sweden)

    Peter Bracinik

    2008-01-01

    Full Text Available The aim of this paper is to point out some facts that will occur by fault localization in 22 kV networks after the implementation of distributed power sources, especially wind power plants. This paper describes possible connection of these sources into power system in regard to their rated output. It also presents short theoretical background for short circuit calculation in 22 kV network. Then several examples explaining how the point of wind power plant connection can influence network’s operation during short-circuits and consequential fault’s localization are described in the second part of this paper

  20. Performance of a 100-kV, 78-kJ electric-gun system

    International Nuclear Information System (INIS)

    Chau, H.; Dittbenner, G.; Mikkelsen, K.; Weingart, R.; Froeschner, K.; Lee, R.

    1981-01-01

    A new electric gun system was constructed for use in high-pressure EOS studies. The system is powered by a 100 kV, 15.6 μF capacitor bank. At 100 kV charging voltage the system inductance is 23 nH. This system has driven 0.3 mm-thick Kapton projectiles to > 20 km/s and 0.3 mm Kapton/30 μm Ta projectiles to approx. 10 km/s. Projectile velocity is modeled phenomenlogically by an electrical Gurney model

  1. TS Seminar: Overview of Fermilab’s Power Distribution System

    CERN Multimedia

    CERN. Geneva

    2006-01-01

    A 27.5 km2 (6800 acre) site is powered by two 345 kV, two 34.5 kV, one 12.4 kV and five 7.2 kV lines. The talk gives an overview of Fermilab’s power distribution system with emphasis on accelerator power. The accelerator power distribution system provides 13.8 kV power to all accelerators and conventional loads. Design criteria, design features and operational experience are given.Organiser(s): F. Rodriguez-Mateos & Emmanuel Tsesmelis

  2. French 400 kV network

    Energy Technology Data Exchange (ETDEWEB)

    Pelissier, R

    1965-11-01

    A 400 kV transmission network has been constructed to carry hydroelectric power from the Alps and the Massif Central to Paris at peak hours and to carry power in the reverse direction in off-peak hours. A double circuit-ring at 400 kV encircling the Paris region is also nearing completion. Measures have to be taken to counter the very high short-circuit currents in such a network. A 730 kV network will eventually become necessary. The consequent multiplicity of transmission voltages will give rise to further problems. Collaboration with neighboring countries is envisaged. The problems of stability and synchronization posed by the new system are described and solutions suggested. The new circuit-breaking requirements are discussed, and details of tower design for 400 kV and 730 kV are given.

  3. High power cable with internal water cooling 400 kV

    Energy Technology Data Exchange (ETDEWEB)

    Rasquin, W; Harjes, B

    1982-08-01

    The project was planned for a duration of 4 years. Afterwards it has been extended over 6 years and finally stopped after 3 1/2 years. Therefore, of course results of field tests with an internally cooled 400 kV cable are not available. Nevertheless, this conductor cooled high power cable has been developed to such an extend, that this manufactured cable could withstand type tests according to IEC/VDE recommendations. Even by missing field tests it is obvious that a high power cable for 400 kV is available.

  4. 40-kV, 25-ms neutral-beam power supply for TMX

    International Nuclear Information System (INIS)

    Leavitt, G.A.

    1977-01-01

    Modifications are described to upgrade the neutral-beam power supply for the TMX from 40 kV, 10 ms to 40 kV, 25 ms. The redesign of the accel and suppressor power supplies to achieve separation of the high-voltage and control sections, operation of the arc pulse lines in series, operation of the arc pulse lines in a noisy environment with SCR trigger and crowbar, and modifications to the electrolytic storage banks are discussed

  5. Regulation System for the 18 kV/90 Mvar Compensators

    CERN Document Server

    Burdet, G

    2001-01-01

    Two 18 kV/90 Mvar static compensators are involved to stabilise the voltage, filter the harmonics and compensate the reactive power generated by the power converters used to supply the SPS accelerator magnets. The in-house hardware and software used by the regulation systems, difficult to maintain and upgrade, shall be renovated. Industrial solution based on PLC will be implemented. This paper describes the future system and its integration to the Electrical Network Supervisor.

  6. submitter Development of a 100 kW, 12.5 kV, 22 kHz and 30 kV insulated medium frequency transformer for compact and reliable medium voltage power conversion

    CERN Document Server

    Isler, Stephane; Aguglia, Davide; Bonnin, Xavier Abel

    2017-01-01

    This paper presents the critical design aspects addressed during the development of a 100 kW, 12.5 kV, 22 kHz, and 30 kV insulated medium frequency transformer used in a power converter. The transformers are used in a resonant multilevel converter topology producing HV DC voltage from a three phase 400 V AC industrial grid. The power converter is used to supply radio frequency systems in particle accelerators. Considerations about material selection, dielectric, magnetic and thermal design are discussed and experimental results on the full scale transformer and power converter are presented.

  7. Long-term test of the 22.9kV HTS power cable system in LS Cable Ltd

    International Nuclear Information System (INIS)

    Jang, Hyun Man; Lee, Chang Young; Kim, Choon Dong; Kim, Do Hyung; Park, In Son; Ji, Bong Ki; Kim, Dong Wook; Cho, Jeonwook

    2006-01-01

    Since 2001, LS cable Ltd. has been developing the design, manufacturing and evaluation technologies for high temperature superconducting (HTS) power cable system as a member of DAPAS (Dream for Advanced Power system by Applied Superconductivity technology) program in Korea. The 30 m HTS cable system that is rated at 22.9 kV and 1.2 kA giving a rated capacity of 50 MVA had been developed and tested. The cable was designed as a cold dielectric type employing Bi-2223 HTS tapes and polypropylene (PP) laminated paper as the conductor and electrical insulation, respectively. The cable is cooled with sub-cooled liquid nitrogen at temperature from 75 to 77 K. The manufacturing and the installation of the cable system were completed in 2004. Long-term performance test of the cable system has been conducted for six months to verify its electric and mechanical properties in 2005

  8. Study on Oscillations during Short Circuit of MW-Scale IGBT Power Modules by Means of a 6-kA/1.1-kV Nondestructive Testing System

    DEFF Research Database (Denmark)

    Wu, Rui; Diaz Reigosa, Paula; Iannuzzo, Francesco

    2015-01-01

    This paper uses a 6-kA/1.1-kV nondestructive testing system for the analysis of the short-circuit behavior of insulated-gate bipolar transistor (IGBT) power modules. A field-programmable gate array enables the definition of control signals to an accuracy of 10 ns. Multiple 1.7-kV/1-kA IGBT power...... modules displayed severe divergent oscillations, which were subsequently characterized. Experimental tests indicate that nonnegligible circuit stray inductance plays an important role in the divergent oscillations. In addition, the temperature dependence of the transconductance is proposed as an important...

  9. Internal services simulation control in 220/110kV power transformer station Mintia

    Science.gov (United States)

    Ciulica, D.; Rob, R.

    2018-01-01

    The main objectives in developing the electric transport and distribution networks infrastructure are satisfying the electric energy demand, ensuring the continuity of supply to customers, minimizing electricity losses in the transmission and distribution networks of public interest. This paper presents simulations in functioning of the internal services system 400/230 V ac in the 220/110 kV power transformer station Mintia. Using simulations in Visual Basic, the following premises are taken into consideration. All the ac consumers of the 220/110 kV power transformer station Mintia will be supplied by three 400/230 V transformers for internal services which can mutual reserve. In case of damaging at one transformer, the others are able to assume the entire consumption using automatic release of reserves. The simulation program studies three variants in which the continuity of supply to customers are ensured. As well, by simulations, all the functioning situations are analyzed in detail.

  10. On geomagnetically-induced currents in the Finnish 400 kV power system by an auroral electrojet current

    International Nuclear Information System (INIS)

    Pirjola, R.; Viljanen, A.

    1989-01-01

    The auroral electrojet current flowing in the ionosphere is modeled by a horizontal east-west line current of infinite length. The earth is described by a simple two-layer model. An expression for the earth-surface electric field, which is thus connected with a geomagnetic disturbance in and near the auroral zone, is given. This electric field is considered as external from the viewpoint of the Finnish 400 kV power system, and the resulting geomagnetically-induced currents (GICs) in the system are computed. In the north, i.e. near the electrojet, GICs may have values even in the order of hundreds of amperes. A comparison to GICs produced by an equivalent spatially-constant external electric field is demonstrated. Sometimes the location of the electrojet is further south. This possibility is studied by letting the line current have several different locations above the Finnish power grid

  11. Operational experience with -20 kV, 5 A DC power supply in Indus-2 RF system

    International Nuclear Information System (INIS)

    Tyagi, R.K.; Tripathi, A.; Upadhyay, R.; Badapanda, M.K.; Lad, M.

    2015-01-01

    An AC regulator based -20 kV, 5 A DC power supply is employed to bias 60 kW, 505.8 MHz klystron amplifier in Indus-2 RF system. A three terminal triggered spark gap based crowbar along with suitable limiting elements is incorporated at the output of the power supply for protection of sensitive klystron amplifier during load arcing conditions. Wire burn test is carried out on this power supply along with crowbar to ensure that the stored energy dumped into klystron during its arcing is less than 20 Joule. Various protection circuits like over voltage, over current, under voltage, phase failure, thermal overload and transformer oil over temperature protection have been incorporated in this power supply. Preventive maintenance of the power supply is carried out at regular intervals to ensure that it operates satisfactorily during actual operation.This includes checking the breakdown strength of transformer oil, drying of Silica gels in transformer breathers, checking of all electrical connections and cleaning of all high voltage components. The calibration of various meters, checking the setting of various protection-interlock cards and checking the healthiness of crowbar system are also done at regular intervals. During operation, crucial performance parameters of this power supply along with various interlock signals are continuously monitored. Suitable arrangement has been made to operate this supply either in local mode as well as in remote mode. This power supply is operating satisfactorily with klystron amplifier in Indus-2 RF system in round the clock mode for last 15 years and its operational experience are presented in this paper. (author)

  12. Design requirements document for the phase 1 privatization electrical power system

    Energy Technology Data Exchange (ETDEWEB)

    Singh, G.

    1997-10-31

    The electrical system for the Phase 1 privatization facilities will support the TWRS mission by providing the electrical power to the Phase 1 privatized facilities. This system will receive power from the Department of Energy-Richland Operations (RL) A4-8 230 kV transmission system powered from Bonneville Power Administration (BPA) Ashe and Midway 230 kV Substations. The existing RL 230 kV transmission line will be modified and looped 1021 into the new 230 kV substation bus. The new substation will be located in the vicinity of the privatized facilities, approximately 3.2 km (2 mi) south of the existing RL A4-8 230 kV transmission line. The substation will be capable of providing up to 40 MW of electrical power to support the Phase 1 privatization facilities and has space for accommodating future expansions. The substation will require at least two 230-13.8 kV transformers, 13.8 kV split bus switchgear, switchgear building, grounding transformers, instrument transformers, control and monitoring equipment, associated protection and isolation devices, lightning protection, yard lighting, cable and raceways, and infrastructure needed to provide desired availability and reliability. The power from the 13.8 kV switchgear located in the switchgear building will be delivered at the privatization facilities site boundaries. The 13.8 kV distribution system inside the privatization facilities site boundaries is the responsibility of the privatization contract.

  13. Design requirements document for the phase 1 privatization electrical power system

    International Nuclear Information System (INIS)

    Singh, G.

    1997-01-01

    The electrical system for the Phase 1 privatization facilities will support the TWRS mission by providing the electrical power to the Phase 1 privatized facilities. This system will receive power from the Department of Energy-Richland Operations (RL) A4-8 230 kV transmission system powered from Bonneville Power Administration (BPA) Ashe and Midway 230 kV Substations. The existing RL 230 kV transmission line will be modified and looped 1021 into the new 230 kV substation bus. The new substation will be located in the vicinity of the privatized facilities, approximately 3.2 km (2 mi) south of the existing RL A4-8 230 kV transmission line. The substation will be capable of providing up to 40 MW of electrical power to support the Phase 1 privatization facilities and has space for accommodating future expansions. The substation will require at least two 230-13.8 kV transformers, 13.8 kV split bus switchgear, switchgear building, grounding transformers, instrument transformers, control and monitoring equipment, associated protection and isolation devices, lightning protection, yard lighting, cable and raceways, and infrastructure needed to provide desired availability and reliability. The power from the 13.8 kV switchgear located in the switchgear building will be delivered at the privatization facilities site boundaries. The 13.8 kV distribution system inside the privatization facilities site boundaries is the responsibility of the privatization contract

  14. High power thyristors with 5 kV blocking voltage. Volume 1: Development of high-voltage-thyristors (4.5 kV) with good dynamic properties

    Science.gov (United States)

    Lock, K.; Patalong, H.; Platzoeder, K.

    1979-01-01

    Using neutron irradiated silicon with considerably lower spread in resistivity as compared to conventionally doped silicon it was possible to produce power thyristors with breakdown voltages between 3.5 kV and 5.5 kV. The thyristor pellets have a diameter of 50 mm. Maximum average on-state currents of 600 to 800 A can be reached with these elements. The dynamic properties of the thryistors could be improved to allow standard applications up to maximum repetitive voltages of 4.5 kV.

  15. Synchronization of 67 MJ, 50 kV pulsed power capacitor banks operation

    Energy Technology Data Exchange (ETDEWEB)

    Besuglov, V G; Galakhov, I V; Gasheev, A S; Grusin, I A; Gudov, S N; Kirillov, G A; Murugov, V M; Osin, V A; Petrakov, V N [All-Russian Scientific Research Inst. of Experimental Physics, Sarov (Russian Federation)

    1997-12-31

    A sync system for the 67 MJ, 50 kV pulse power capacitor bank of the ISKRA-5 facility`s iodine laser is described. This system is to provide synchronism (a jitter within 0.3 {mu}s) in firing of 665 spark gaps, 476 electric discharge pumping sources and 513 flash lamps. The sync system is designed as series-voltage pulse generators to be fired at specifically predetermined times. Also, the system ensures switching of spark gaps in a sequence as required by the experiment and reliable operation of the pumping sources. Procedures to maintain high interference immunity for the system are also addressed. (author). 2 tabs., 2 figs., 2 refs.

  16. High power cable with internal water cooling 400 kV

    Science.gov (United States)

    Rasquin, W.; Harjes, B.

    1982-08-01

    Due to the concentration of electricity production in large power plants, the need of higher power transmissions, and the protection of environment, developement of a 400 kV water cooled cable in the power range of 1 to 5 GVA was undertaken. The fabrication and testing of equipment, engineering of cable components, fabrication of a test cable, development of cable terminal laboratory, testing of test cable, field testing of test cable, fabrication of industrial cable laboratory, testing of industrial cable, field testing of industrial cable, and system analysis for optimization were prepared. The field testing was impossible to realize. However, it is proved that a cable consisting of an internal stainless steel water cooled tube, covered by stranded copper profiles, insulated with heavy high quality paper, and protected by an aluminum cover can be produced, withstand tests accordingly to IEC/VDE recommendations, and is able to fulfill all exploitation conditions.

  17. Development and use of 60 kV, and 150 kV floating deck modulators for high voltage protection of multi-megawatt ion beam accelerators

    International Nuclear Information System (INIS)

    Barber, G.C.; Ponte, N.S.; Schilling, G.

    1977-01-01

    Extraction currents of 60 A at 40 kV have been produced by utilizing a 60 kV floating deck modulator interfaced to a high voltage power supply. The modulator is operated in a series mode to repetitively pulse power to the ion beam accelerator. Current monitoring and other protective circuits provide interrupt commands to the series switch tube when faults occur. The constant current characteristics of the water cooled tetrode and the rapid response of the protective circuits effectively limit the fault energy to the ion source. Three of the 60 kV decks have been modified and stacked in a series configuration to supply 150 kV, 50 A pulses. This system supplies power for development of higher-energy multi-grid sources. In this system attention has been focused on forced voltage sharing of the three decks and on protective circuits for fault conditions. All control signal processing and conditioning is performed at ground level. Fiber optic links are used to interface with the high potential associated with the floating decks. A shunt modulator incorporated with this system provides regulation of the voltage to the ion source gradient grid. Future modulator development includes a system to deliver 100 A at 80 kV

  18. Measurements of crowbar performance of the 20 kV 130 A dc power supply of the TRIUMF RF system

    International Nuclear Information System (INIS)

    Mitra, A.K.

    1991-05-01

    The TRIUMF RF system operates at a fixed frequency of 23.06 MHz with a power capability of 1800 kW. The dc plate power for the four push-pull power amplifiers is provided by a single dc power supply at 20 kV, 130 A and the amplifiers are protected by a single ignitron crowbar circuit. In the case of voltage breakdown outside the tube, the triggering of the crowbar circuit relies on the voltage developed across a low resistance shunt in the return path of the common dc power supply. Frequent failure of the crowbar ignitrons following an external dc voltage breakdown led to the investigation of the crowbar performance. Current transformers have been installed in the common B + line to the power amplifiers and the anode circuit of the ignitron crowbar in order to measure amplitude, duration and time delay of various dc currents under fault conditions. Similar current transformers were installed in the individual anode circuits of the power amplifiers to provide protection to the complete system in case of an external dc voltage breakdown. The results of these measurements and recommended solutions for operations are reported. (Author) 3 refs., 4 figs

  19. Fault protection system in a 'regulated high voltage power supply (80 KV, 130A)' for neutral beam injector

    International Nuclear Information System (INIS)

    Patel, Paresh; Sumod, C.B.; Thakkar, Dipal

    2011-01-01

    Regulated High Voltage Power Supply (RHVPS) system has been developed at Institute for Plasma Research (IPR) for use with the Neutral Beam and RF applications. The highest ratings manufactured so far is 80 kV, 130 A. The system is developed in house and also being delivered at different research institutes for various applications. Since it is a multi megawatt output power system, and the loads have very low fault energy tolerant, fault protection system is mandatory. Protections are mandatory at each stage of conversion. Output fault protection is done in a variety of ways. Fast turn off at output is achieved and test results are discussed. Multi secondary transformers (5.6 MVA rating, with 40 outputs) are used in realising the power supply. These special transformers need protection even for over current at one secondary when the output fault current is not reflected to primaries to break the main circuit breaker. It becomes difficult to bifurcate fault in such situations. Special technique is applied to sense it. Electronic means are used for fast detection and tripping the system. This paper describes the basic RHVPS topology and test results along with presentation on the input and output fault protection systems. (author)

  20. Analysis of the 35 KV substation secondary system

    Science.gov (United States)

    Zhao, Yong; Jiang, Jianguo; Jiang, Chunlei; Ren, Shuang; Liu, Songbin

    2017-04-01

    This paper analyzes the status of the two system of some 35KV users' substation in Daqing oil field, the deficiencies of the two system of the existing 35KV substation are found out. And put forward the opinion of acceptance in the future work. I hope it can able to work in the future on the protection of professional help.

  1. Startup experience with the MFTF-B ECRH 100 kV dc power supply

    International Nuclear Information System (INIS)

    Bishop, S.R.; Goodman, R.A.; Wilson, J.H.

    1983-01-01

    One of the 24 Accel dc Power Supplies (ADCPS) originally intended for the Mirror Fusion Test Facility (MFTF-B) Neutral Beam Power Supply (NBPS) System has been converted to provide negative polarity output at 90 kV with a load current of 64 A dc. The load duty cycle is a pulse of 30-seconds duration with a pulse repetition period of five minutes. A new control system has been built which will serve as a prototype for the MFTF-B ADCPS controls, and a test setup was built which will be used to test the ADCPS. The Electron Cyclotron Resonance Heating (ECRH) dc Power Supply (DCPS) has been tested under both no-load and dummy-load conditions, under remote control, without notable problems. Test results indicate that the power supply should be reliable and safe to operate, and will meet the load duty requirements

  2. Startup experience with the MFTF-B ECRH 100 kV dc power supply

    International Nuclear Information System (INIS)

    Bishop, S.R.; Goodman, R.A.; Wilson, J.H.

    1983-01-01

    One of the 24 Accel DC Power Supplies (ADCPS) originally intended for the Mirror Fusion Test Facility (MFTF-B) Neutral Beam Power Supply (NBPS) System has been converted to provide negative polarity output at 90 kV with a load current of 64 A dc. The load duty cycle is a pulse of 30-seconds duration with a pulse repetition period of five minutes. A new control system has been built which will serve as a prototype for the MFTF-B ADCPS controls, and a test setup was built which will be used to test the ADCPS. The Electron Cyclotron Resonance Heating (ECRH) DC Power Supply (DCPS) has been tested under both no-load and dummy-load conditions, under remote control, without notable problems. Test results indicate that the power supply should be reliable and safe to operate, and will meet the load duty requirements

  3. A study on the insulation coordination of 765 kV system

    Energy Technology Data Exchange (ETDEWEB)

    Kim, Jeong Boo; Shim, Eung Bo [Korea Electric Power Corp. (KEPCO), Taejon (Korea, Republic of). Research Center; Lee, Yong Han; Youn, Jae Yeong; Hwang, Chi Woo; Jung, Dong Hak [Korea Electrotechnology Research Inst., Changwon (Korea, Republic of)

    1996-12-31

    Analysis of the power frequency temporary overvoltage. Analysis of switching surges - Fault imitation, closing and re closing, fault clearing. Analysis of lightning surges. Insulation design of 765 kV overhead transmission line. Insulation coordination of 765 kV gas insulated substation. Transient recovery voltage and high speed ground switch (author). 38 refs., 55 figs.

  4. Touch and step potential analysis at 23.9kV to 4.16kV & 13.8kV to 4.16kV distribution substations with pad-mounted transformers, floating grounds, and other exposed ungrounded metal bodies using WinIGS

    Science.gov (United States)

    Guzman, David G.

    An electrical substation is composed of various subsystems that allow for the effective and safe operation of the power grid. One of the subsystems integrating a conventional substation is defined as the ground grid system. This system allows for the effective operation of the power grid and all the electrical equipment connected to it by providing a ground potential reference, commonly known as the system ground. In addition, the ground grid system provides safety to the workers and the public transiting inside or living nearby a substation by reducing the step and touch potential (or voltage) levels present during a system fault. In today's utility industry practices there is an increasing trend for using pad-mounted electrical equipment for substation applications in an effort to construct new or upgrade existing electrical facilities inside limited property spaces. This thesis work presents an analysis for the effects of touch and step voltages at existing distribution substations where 23.9kV to 4.16kV & 13.8kV to 4.16kV pad-mounted transformers and other pad-mounted switchgear was installed to replace the traditional station class equipment. Moreover, this study will expose modeling techniques employed to define and determine the effects of floating grounds and other exposed metal bodies inside or surrounding these substations using WinIGS; this is in an effort to determine any risks of electric shock associated with this type of installations. The results presented in this work are intended to verify the requirements for the ground grid analysis and design for 4.16kV distribution substations with pad-mounted equipment in order to prevent dangerous step and touch voltage levels appearing at these sites during system faults; and ultimately prevent exposing individuals to the risk of an electric shock.

  5. Power supply system for KSTAR neutral beam injector

    Energy Technology Data Exchange (ETDEWEB)

    Cho, W., E-mail: franciscocho@nfri.re.kr; Bae, Y.S.; Han, W.S.; Jeong, J.H.; Kim, J.S.; Park, H.T.; Yang, H.L.; Oh, Y.K.; Kwak, J.G.

    2015-10-15

    Highlights: • The power supply system in KSTAR NBI consists of DC power supplies for ion source. • For operation NBI, DC High Voltage based on the low voltage transformer with chopper. • The surge absorber near the ion source limit the energy deposited to accelerator grid. - Abstract: The power supply system in KSTAR neutral beam injector consists of low voltage and high current DC power supplies for plasma generator of ion source and high voltage and high current DC power supply for accelerator grid system. The arc discharge is initiated by an arc power supply supplying the arc voltage between the chamber wall and 12 filaments which are heated by individual filament power supply. The negative output of arc power supply is common to each positive output of 12 filament power supplies. To interrupt the arc discharging for the fault condition of the arc current unbalance, DCCT current monitor is placed at the positive output cable of the filament power supply. The plasma grid (G1) power supply has the maximum capability of 120 kV/70 A which consists of low voltage regulator with IGBT-switched chopper array system for the voltage control in unit of 600 V and the high voltage rectified transformers to supply DC voltage of 20 kV, 30 kV, and 50 kV. The output voltage of the G1 power supply is also connected to the input of the voltage divider system which supplies the gradient voltage to the gradient grid (G2) in the range of 80–90% of G1 voltage by changing tap of winding resistors in unit of 1%. The charged G1 voltage is turned on and off by the high voltage switch (HVS) system consisting of MOSFET fast semiconductor switches which can immediately be opened less than 1 μs when the ion source grid breakdown occurs. The decelerating grid (G3) power supply is inverter system using capacitor-charge power supply to supply maximum −5 kV/5 A. The important component in power supply system is the surge absorber near the ion source to limit the arc energy deposited to

  6. Power supply system for KSTAR neutral beam injector

    International Nuclear Information System (INIS)

    Cho, W.; Bae, Y.S.; Han, W.S.; Jeong, J.H.; Kim, J.S.; Park, H.T.; Yang, H.L.; Oh, Y.K.; Kwak, J.G.

    2015-01-01

    Highlights: • The power supply system in KSTAR NBI consists of DC power supplies for ion source. • For operation NBI, DC High Voltage based on the low voltage transformer with chopper. • The surge absorber near the ion source limit the energy deposited to accelerator grid. - Abstract: The power supply system in KSTAR neutral beam injector consists of low voltage and high current DC power supplies for plasma generator of ion source and high voltage and high current DC power supply for accelerator grid system. The arc discharge is initiated by an arc power supply supplying the arc voltage between the chamber wall and 12 filaments which are heated by individual filament power supply. The negative output of arc power supply is common to each positive output of 12 filament power supplies. To interrupt the arc discharging for the fault condition of the arc current unbalance, DCCT current monitor is placed at the positive output cable of the filament power supply. The plasma grid (G1) power supply has the maximum capability of 120 kV/70 A which consists of low voltage regulator with IGBT-switched chopper array system for the voltage control in unit of 600 V and the high voltage rectified transformers to supply DC voltage of 20 kV, 30 kV, and 50 kV. The output voltage of the G1 power supply is also connected to the input of the voltage divider system which supplies the gradient voltage to the gradient grid (G2) in the range of 80–90% of G1 voltage by changing tap of winding resistors in unit of 1%. The charged G1 voltage is turned on and off by the high voltage switch (HVS) system consisting of MOSFET fast semiconductor switches which can immediately be opened less than 1 μs when the ion source grid breakdown occurs. The decelerating grid (G3) power supply is inverter system using capacitor-charge power supply to supply maximum −5 kV/5 A. The important component in power supply system is the surge absorber near the ion source to limit the arc energy deposited to

  7. Major trends in the development of electrical power systems

    Energy Technology Data Exchange (ETDEWEB)

    Syromyatnikov, I A

    1965-01-01

    The comparison is made between the USA and the USSR electrical systems and their growth. The author states that USSR is about 35 years behind in the construction of power transmission lines of 22 kV and above. Various graphs of economic developments are presented. It is stated that the work in the near future should be concentrated on 750 kV network and on combining the USSR electric power distribution into a single power system.

  8. Environmental Assessment for Central Power and Light Company`s proposed Military Highway-CFE tie 138/69-kV transmission line project Brownsville, Cameron County, Texas

    Energy Technology Data Exchange (ETDEWEB)

    1992-04-01

    Central Power and Light Company (CPL) intends to upgrade its existing transmission line ties with the Commision Federal de Electricidad (CFE) system in Mexico. CPL currently has a single 69-kilovolt (kV) transmission line in the Brownsville area which connects CPL`s system with the system of CFE. This existing line runs between the Brownsville Switching Station, located on Laredo Road in Brownsville, Cameron County, Texas, and an existing CFE 69-kV line at the Rusteberg Bend of the Rio Grande in Cameron County. Under current conditions of need, the existing 69-kV line does not possess sufficient capability to engage in appropriate power exchanges. Therefore, CPL is proposing to build a new line to link up with CFE. This proposed line would be a double-circuit line, which would (1) continue (on a slightly relocated route) the existing 69-kV tie from CPL`s Brownsville Switching Station to CFE`s facilities, and (2) add a 138-kV tie from the Military Highway Substation, located on Military Highway (US Highway 281), to CFE`s facilities. The proposed 138/69-kV line, which will be constructed and operated by CPL, will be built primarily on steel single-pole structures within an average 60-foot (ft) wide right-of-way (ROW). It will be approximately 6900--9200 ft (1.3--1.7 miles) in length, depending on the alternative route constructed.

  9. Performance of the TJ-II ECRH system with the new -80 kV 50 A high voltage power supply

    International Nuclear Information System (INIS)

    Fernandez, A.; de la Fuente, J.M.; Ganuza, D.; Kirpitchev, I.; Alonso, J.; Garcia, F.; Ascasibar, E.; del Rio, J.M.; Garcia, I.; Ros, A.; Alvarez, P.; Tolkachev, A.; Catalan, G.

    2009-01-01

    The ECRH system of the TJ-II stellarator consists of two triode - 53.2 GHz - gyrotrons, which can deliver a maximum power of 300 kW each, during 1 s. Both gyrotrons are fed by a common high voltage power supply (HVPS). During the last experimental campaigns the performance of the gyrotrons were limited by the HVPS, whose maximum output current was limited to 30 A and the ripple level of the output voltage was around 7%. In order to guarantee the reliability of the ECRH system and to improve its performance, a new HVPS has been developed and manufactured by the company JEMA and was commissioned at CIEMAT during 2007. The design is based on solid-state technology and high frequency commutation techniques. The new unit reaches -80 kV and 50 A during a maximum pulse length of 1 s. The complete design, testing and commissioning of the HVPS are presented, as well as the routine operation of the ECRH system during the TJ-II experimental campaign.

  10. Performance of the TJ-II ECRH system with the new -80 kV 50 A high voltage power supply

    Energy Technology Data Exchange (ETDEWEB)

    Fernandez, A. [Laboratorio Nacional de Fusion, EURATOM-CIEMAT Association, Avda. Complutense 22, 28040 Madrid (Spain)], E-mail: angela.curto@ciemat.es; de la Fuente, J.M.; Ganuza, D. [Grupo JEMA, Paseo del Circuito 10, 20160 Lasarte-Oria (Spain); Kirpitchev, I.; Alonso, J. [Laboratorio Nacional de Fusion, EURATOM-CIEMAT Association, Avda. Complutense 22, 28040 Madrid (Spain); Garcia, F. [Grupo JEMA, Paseo del Circuito 10, 20160 Lasarte-Oria (Spain); Ascasibar, E. [Laboratorio Nacional de Fusion, EURATOM-CIEMAT Association, Avda. Complutense 22, 28040 Madrid (Spain); del Rio, J.M.; Garcia, I. [Grupo JEMA, Paseo del Circuito 10, 20160 Lasarte-Oria (Spain); Ros, A.; Alvarez, P.; Tolkachev, A.; Catalan, G. [Laboratorio Nacional de Fusion, EURATOM-CIEMAT Association, Avda. Complutense 22, 28040 Madrid (Spain)

    2009-06-15

    The ECRH system of the TJ-II stellarator consists of two triode - 53.2 GHz - gyrotrons, which can deliver a maximum power of 300 kW each, during 1 s. Both gyrotrons are fed by a common high voltage power supply (HVPS). During the last experimental campaigns the performance of the gyrotrons were limited by the HVPS, whose maximum output current was limited to 30 A and the ripple level of the output voltage was around 7%. In order to guarantee the reliability of the ECRH system and to improve its performance, a new HVPS has been developed and manufactured by the company JEMA and was commissioned at CIEMAT during 2007. The design is based on solid-state technology and high frequency commutation techniques. The new unit reaches -80 kV and 50 A during a maximum pulse length of 1 s. The complete design, testing and commissioning of the HVPS are presented, as well as the routine operation of the ECRH system during the TJ-II experimental campaign.

  11. Experimental investigations of overvoltages in 6kV station service cable networks of thermal power plants

    Energy Technology Data Exchange (ETDEWEB)

    Vukelja, P.I.; Naumov, R.M.; Drobnjak, G.V.; Mrvic, J.D. [Nikola Tesla Inst., Belgrade (Yugoslavia)

    1996-12-31

    The paper presents the results of experimental investigations of overvoltages on 6kV isolated neutral station service cable networks of thermal power plants. The overvoltages were recorded with capacitive voltage measurement systems made at the Nikola Tesla Institute. Wideband capacitive voltage measurement systems recorded a flat response from below power frequencies to 10MHz. Investigations of overvoltages were performed for appearance and interruption of metal earth faults, intermittent earth faults, switching operation of HV motors switchgear, switching operation of transformers switchgear, and transfer of the network supply from one transformer to another. On the basis of these investigations, certain measures are proposed for limiting overvoltages and for the reliability of station service of thermal power plants.

  12. Integration of -70kV, 22A high voltage power supply with solid state crowbar and the LHCD system of SST-1

    International Nuclear Information System (INIS)

    Rajan Babu, N.; Virani, C.G.; Dalakoti, S.; Sharma, P.K.; Ambulkar, K.K.; Parmar, P.R.; Thakur, A.L.; Dhorajiya, Pragnesh

    2015-01-01

    LHCD system is a important system for the steady state operation of the SST-1 machine. Four numbers of klystrons of 3.7 GHz are used as a microwave source to produce 2 MW of microwave power. This power is launched into the machine to achieve the steady state operation of the SST-1 Machine. A -70kV, 22A high voltage power supply and a solid-state crowbar are procured and tested and validated for its performance separately. Both of the system are integrated and tested for its integrated performance for the safe and reliable test of the klystron tube. A 10J wire test is conducted for the optimum value of the series resistor. This test will validate the integrated performance of power supply, Crowbar and the interlocking circuit. This paper details the optimization of the ballast resistor from 150 ohms to 40 ohms and its successful integration with the klystron tube for its 500kW CW operation. Some operational experience is also shared

  13. Improving the Transmission System Reliability for the 154kV Radial Network Operation

    Energy Technology Data Exchange (ETDEWEB)

    Choo, Jin Boo; Yoo, Myeong Ho; Yoon, Young Beum; Kim, Tae Won [Korea Electric Power Research Institute, Taejon (Korea, Republic of); Lee, Gi Won; Chung, Beom Jin; Jung, Jung Won; Park, Kyu Hyun; Lee, Myung Hee; Kim, Hyun Jong; Kim, Chae Hee [KEYIN CO., (Korea, Republic of)

    1996-12-31

    Analyzing that 154kV radial network current ed operated, we developed Automatic Power Reconfiguration System(APRS) which restore blackout area. It consists of special data acquisition system(DAU) and central monitoring system for reason of protecting currently operating power system. In addition, it communicates using optical communication network for high speed data transmission and accuracy. An Accuracy of operation and stability of the developed system is tested using Real Time Digital Simulator in 3-bus equivalent model system. In An Outage case, our developed system can restore a blackout area in three second. An ability of the restoration of a blackout was verified by simulations. For the field test, the developed system was set up at SINCHON S/S, SESOMUN S/S, SINDANG S/S and MAJANG S/S governed by Seoul Power Transmission Center. If the system reliability is proved for a one year test in real power system, application of the system will be extended to the other substations.

  14. A 600kV 15mA Cockcroft-Walton high-voltage power supply with high stability and low-ripple voltage

    International Nuclear Information System (INIS)

    Su Tongling; Zhang Yimin; Chen Shangwen; Liu Yantong; Lv Huiyi; Liu Jiangtao

    2006-01-01

    A Cockcroft-Walton high-voltage power supply with high stability and low-ripple voltage has been developed. This power supply has been operated in a ns pulse neutron generator. The maximum non-load voltage is 600kV while the working voltage and load current are 550kV and 15mA, respectively. The tested results indicate that when the power supply is operated at 300kV, 6.7mA and the input voltage varies +/-10%, the long-term stability of the output voltage is S=(0.300-1.006)x10 -3 . The ripple voltage is δU P-P =6.2V at 300kV, 6.8-8.3mA and the ratio of δU P-P to the output voltage V H is δU P-P /V H =2.1x10 -5

  15. On the prohibition of automatic redundant power supply of 6 and 0.4 kV auxiliary sections at Leningrad NPP

    International Nuclear Information System (INIS)

    Mokeev, S.F.

    1987-01-01

    At Leningrad NPP the automatic switching on of the auxiliary power supply sources of 6 and 0.4 kV is prohibited to provide personnel safety and preserve destruction of electroequipment. With excess of current maximum value in the 6 kV section immediate detachment of all electric motors occurs. At that moment by the switchers detechment emergency signal it occurs immediate swithing on of auxiliary systems or emergency switching on of auxiliary supply of the main circulating pumps, that insreases abruptly operation reliability of plant technological department

  16. Reliability analysis of self-supply system of V-1 nuclear power plant

    International Nuclear Information System (INIS)

    Kuklik, B.

    The results are summarized of the fault tree analysis of the V-1 power plant self-consumption system. The 6 kV busbars providing power for the main circulating pumps, the steam generator feed pumps and other important components including the 0.4 kV busbars are of the highest importance for nuclear safety. A fault tree analysis was also made of the emergency core cooling system of the reactor. Dangerous faults are defined and fault trees are developed. A brief description is given of the calculation algorithm for a digital computer. Some results are discussed. The calculated reliability of the emergency core cooling system is 10 5 years, of the 6 kV busbars it is 6.6x10 4 years. In case of a permanent or a long-term outage of the 220 kV stand-bye power supply, the system reliability is reduced to 7x10 2 years. (Z.M.)

  17. Hybrid system power generation'wind-photovoltaic' connected to the ...

    African Journals Online (AJOL)

    Hybrid system power generation'wind-photovoltaic' connected to the ... from Hybrid System, power delivered to or from grid and phase voltage of the inverter leg. ... Renewable Energy, Electrical Network 220 kV, Hybrid System, Solar, MPPT.

  18. Voltage Analysis Improvement of 150 kV Transmission Subsystem Using Static Synchronous Compensator (STATCOM)

    Science.gov (United States)

    Akbar, P. A.; Hakim, D. L.; Sucita, T.

    2018-02-01

    In this research, testing improvements to the distribution voltage electricity at 150 kV transmission subsystem Bandung Selatan and New Ujungberung using Flexible AC Transmission System (FACTS) technology. One of them is by doing the control of active and reactive power through the power electronics equipment Static Synchronous Compensator (STATCOM). The subsystem is tested because it has a voltage profile are relatively less well when based on the IEEE / ANSI C.84.1 (142.5 - 157.5 kV). This study was conducted by analyzing the Newton-Raphson power flow on the simulator DigSilent Power Factory 15 to determine the profile of the voltage (V) on the system. Bus which has the lowest voltage to be a reference in the installation of STATCOM. From this research is known that the voltage on the conditions of the existing bus 28, as many as 21-23 still below standard buses (142.5 kV), after the installation is done using STATCOM, voltage on the buses improved by increasing the number of tracks that follow the standard / is in the range 142.5 kV -157.5 kV as many as 23-27 buses or 78.6% - 96%, with the optimum mounting on a bus Rancaekek STATCOM II with a capacity of 300 MVA.

  19. HVDC transmission preferred to 750 kV ac

    Energy Technology Data Exchange (ETDEWEB)

    1965-06-25

    It is unlikely that there will be a need in Britain for ac transmission voltages above 400 kV. But with the growing load density in the large conurbations with no possibility of local generation, high voltage dc transmission is likely to be most useful. It was concluded that by 1971 the 400 kV supergrid would be nation-wide and 6,200 circuit miles should be in service. With the expansion to accommodate the large new generating stations, the 400 kV supergrid would become an extremely high power distribution network rather than a transmission system. A higher voltage for transmission is outside the rational limit of speculation for a country the size of Britain.

  20. Conducted noise analysis and protection of 45 kJ/s, ±50 kV capacitor charging power supply when interfaced with repetitive Marx based pulse power system

    Science.gov (United States)

    Naresh, P.; Patel, Ankur; Sharma, Archana

    2015-09-01

    Pulse power systems with highly dynamic loads like klystron, backward wave oscillator (BWO), and magnetron generate highly dynamic noise. This noise leads to frequent failure of controlled switches in the inverter stage of charging power supply. Designing a reliable and compatible power supply for pulse power applications is always a tricky job when charging rate is in multiples of 10 kJ/s. A ±50 kV and 45 kJ/s capacitor charging power supply based on 4th order LCLC resonant topology has been developed for a 10 Hz repetitive Marx based system. Conditions for load independent constant current and zero current switching (ZCS) are derived mathematically. Noise generated at load end due to dynamic load is tackled effectively and reduction in magnitude noise voltage is achieved by providing shielding between primary and secondary of high voltage high frequency transformer and with LCLC low pass filter. Shielding scales down the ratio between coupling capacitance (Cc) and the collector-emitter capacitance of insulated gate bi-polar transistor switch, which in turn reduces the common mode noise voltage magnitude. The proposed 4th order LCLC resonant network acts as a low pass filter for differential mode noise in the reverse direction (from load to source). Power supply has been tested repeatedly with 5 Hz repetition rate with repetitive Marx based system connected with BWO load working fine without failure of single switch in the inverter stage.

  1. APPLICATION OF SSSC TO THE 330kV NIGERIAN ...

    African Journals Online (AJOL)

    HOD

    2,3 DEPARTMENT OF ELECTRONIC AND ELECTRICAL ENGR., FEDERAL POLYTECHNIC EDE, ... Longitudinal power systems of Nigerian 330 kV transmission network have steady-state ..... C tr ller ” Unpublish Master Thesis Submitted to.

  2. Implementation of Particle Swarm Optimization Method for Voltage Stability Analysis in 150 kV Sub System Grati – Paiton East Java

    Science.gov (United States)

    Kusumaningtyas, A. B.; Hidayat, M. N.; Ronilaya, F.

    2018-04-01

    Based on the data from State Electric Company on 15 January 2013, the undistributed power in the 150 kV sub system Grati-Paiton Region IV, that consist of 26 bus 150 kV and 2 bus generation 500 kV system, was recorded 3.286,00 MW. At the same time, the frequency of the system was down to 49 Hz. This lead to a deficit generation and unstable voltage condition in the system. Fast Voltage Stability Index (FVSI) method is used in this research to analyze the voltage stability of the buses. For buses with unstable voltage condition, reactive power will be injected through capacitor installation. The site where the capacitor will be installed is determined using the Fast Voltage Stability Index (FVSI) method while the size of the capacitor is determined using the Particle Swarm Optimization (PSO) method. The PSO method has been applied in some researches, such as to determine optimal placement and sizing in radial distribution network as well as in transmission network.. In this research, the PSO method is used to find the Qloss of an interconnection transmission system, which in turn, the value of the Qloss is used to determine the capacitance of the capacitor needed by the system.

  3. Design and development of a high-power, 500 kV pulsed line

    International Nuclear Information System (INIS)

    Nicolas, A.

    A study was made of very high voltage (500 kV) pulse production for 50 ns at half height. A coaxial line was coupled to a Marx generator for obtaining the pulses on an impedance-adapted electron diode. The maximum power obtained was 6.4 x 10 10 W with a current front in the diode of about 30 ns (80 ns pulse length at half height)

  4. Marys Lake 69/115-kV transmission line upgrade and substation expansion projects

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1996-05-01

    Western Area Power Administration (Western) and the Platte River Power Authority (Platte River) propose to upgrade portions of the existing electric transmission and substation system that serves the Town of Estes Park, Colorado. The existing transmission lines between the Estes Power Plant Switchyard and the Marys Lake Substation include a 115,000 volt (115-kV) line and 69,000 volt (69-kV) line. Approximately one mile is a double-circuit 115/69-kV line on steel lattice structures, and approximately two miles consists of separate single-circuit 115-kV and a 69-kV lines, constructed on wood H-Frame structures. Both lines were constructed in 1951 by the US Bureau of Reclamation. The existing transmission lines are on rights-of-way (ROW) that vary from 75 feet to 120 feet and are owned by Western. There are 48 landowners adjacent to the existing ROW. All of the houses were built adjacent to the existing ROW after the transmission lines were constructed. Upgrading the existing 69-kV transmission line between the Marys Lake Substation and the Estes Power Plant Switchyard to 115-kV and expanding the Marys Lake Substation was identified as the most effective way in which to improve electric service to Estes Park. The primary purpose and need of the proposed project is to improve the reliability of electric service to the Town of Estes Park. Lack of reliability has been a historical concern, and reliability will always be less than desired until physical improvements are made to the electrical facilities serving Estes Park.

  5. Marys Lake 69/115-kV transmission line upgrade and substation expansion projects

    International Nuclear Information System (INIS)

    1996-05-01

    Western Area Power Administration (Western) and the Platte River Power Authority (Platte River) propose to upgrade portions of the existing electric transmission and substation system that serves the Town of Estes Park, Colorado. The existing transmission lines between the Estes Power Plant Switchyard and the Marys Lake Substation include a 115,000 volt (115-kV) line and 69,000 volt (69-kV) line. Approximately one mile is a double-circuit 115/69-kV line on steel lattice structures, and approximately two miles consists of separate single-circuit 115-kV and a 69-kV lines, constructed on wood H-Frame structures. Both lines were constructed in 1951 by the US Bureau of Reclamation. The existing transmission lines are on rights-of-way (ROW) that vary from 75 feet to 120 feet and are owned by Western. There are 48 landowners adjacent to the existing ROW. All of the houses were built adjacent to the existing ROW after the transmission lines were constructed. Upgrading the existing 69-kV transmission line between the Marys Lake Substation and the Estes Power Plant Switchyard to 115-kV and expanding the Marys Lake Substation was identified as the most effective way in which to improve electric service to Estes Park. The primary purpose and need of the proposed project is to improve the reliability of electric service to the Town of Estes Park. Lack of reliability has been a historical concern, and reliability will always be less than desired until physical improvements are made to the electrical facilities serving Estes Park

  6. Major Refit for CERN's 400 kV Substation (Part of the new control and protection system for the 18 kV side)

    CERN Document Server

    2001-01-01

    The 400 kV substation on the Prévessin site brings in the electricity that powers CERN's accelerators and the majority of the Laboratory's installations. It was originally built in the 1970s for the SPS, and is one of only five privately owned 400 kV sub-stations in France. Three of the others belong to the national railway company, SNCF, supplying the Paris-Marseilles TGV line, the other is at the Cadarache research centre near mouth of the Rhone. After nearly thirty years of service, CERN's substation has just undergone a complete overhaul.

  7. Design and Control of a 13.2 kV/10 kVA Single-Phase Solid-State-Transformer with 1.7 kV SiC Devices

    Directory of Open Access Journals (Sweden)

    Jeong-Woo Lim

    2018-01-01

    Full Text Available This paper describes the power stage design, control, and performance evaluation of a 13.2 kV/10 kVA solid-state-transformer (SST for a power distribution system. The proposed SST consists of 10 modules where each individual module contains a unidirectional three-level power factor correction (PFC converter for the active-front-end (AFE stage and an LLC resonant converter for the isolated DC-DC stage. The operating principles of the converters are analyzed and the modulation and the control schemes for the entire module are described in detail. The DC-link voltage imbalance is also less than other SST topologies due to the low number of uncontrollable switching states. In order to simplify the control of the power stage, a modulation strategy for the AFE stage is proposed, and the modulation frequency of the LLC converter is also fixed. In addition, a compensation algorithm is suggested to eliminate the current measurement offset in the AFE stage. The proposed SST achieves the unity power factor at the input AC current regardless of the reactive or nonlinear load and a low voltage regulation at the AC output. In order to verify the effectiveness of the SST, the 13.2 kV/10 kV SST prototype is built and tested. Both the simulation and the experimental results under actual 13.2 kV line show the excellent performance of the proposed SST scheme.

  8. 130 kV 130 A High voltage switching mode power supply for neutral beam plasma heating: design issues

    International Nuclear Information System (INIS)

    Ganuza, D.; Del Rio, J.M.; Garcia, I.; Garcia, F.; Garcia de Madinabeitia, P.; Perez, A.; Zabaleta, J.R.

    2003-01-01

    The company JEMA has designed and manufactured two High Voltage Switching Mode Power Supplies (HVSMPS), rated at 130 kV dc and 130 A, each of which will feed the accelerator grids of two Positive Ion Neutral Injector (PINI) loads, to be installed at the Joint European Torus (EFDA-JET facility located at Culham, UK). The solution designed by JEMA includes two matching transformers which adapt the 36 kV of the JET AC power distribution network to the required 670 V at the secondary side. Additionally, such transformers provide a 30 deg.phase shift which is required by a 30000 A 12 pulse thyristor rectifier. The obtained and stabilised 650 V feed 120 IGBT invertors, which operate at 2778 Hz with modulated square waveform. Each invertor feeds a High Insulation High Frequency Transformer. The 120 transformers corresponding to one power supply are arranged in three oil filled tanks and provide the main insulation from the low voltage to the high voltage side. The square waveform obtained at the secondary of each transformer is rectified by means of a diode bridge. The connection in series of the 120 diode bridges provides the required 130 kV d.c. at the output. In order to protect the load, a redundant solid state crowbar has been designed. Such short circuiting device is composed of 26 Light Triggered Thyristors (LTTs), connected in series. Electrical simulations have been carried out in order to ensure that the system complies with the requirements of high accuracy and adequate protection of the load. The critical design of the High Voltage-High Frequency Transformers has also required electrostatic simulations of the electric field distribution

  9. PLTS Transformerless Tegangan 20 kV menggunakan Cascaded H-Bridge Multilevel Inverter

    Directory of Open Access Journals (Sweden)

    ANGGARA BRAJAMUSTHI

    2018-03-01

    Full Text Available ABSTRAK Aplikasi dari inverter multilevel pada sistem Pusat Listrik Tenaga Surya (PLTS dapat menghilangkan kebutuhan terhadap transformator, sehingga dapat mengurangi biaya investasi, mengurangi kompleksitas instalasi dan menghilangkan rugi-rugi daya transformator. Pada penelitian ini, sebuah inverter dengan topologi Cascaded H-Bridge Multilevel Inverter dirancang agar mampu mengubah tegangan rendah DC dari beberapa Photovoltaic (PV array menjadi tegangan fasa-fasa 20 kV AC. Perancangan menghasilkan sebuah inverter 3 fasa 27-level dimana setiap level masing-masing memiliki PV array, DC-DC boost converter, H-bridge inverter, dan keluaran 3 fasa terhubung dengan filter LCL. Setiap komponen dari inverter dan sistem tersebut kemudian dimodelkan pada MATLAB Simulink untuk mensimulasikan kinerja dari setiap komponen dan sistem pada Standard Test Condition (STC dari modul PV. Pada keadaan STC, daya 3 fasa maksimum yang dapat dihasilkan adalah 1,716 MW atau 68,54% dari daya DC maksimum sebesar 2,5 MWp. Sistem dapat menghasilkan tegangan fasa-fasa keluaran sebesar 20 kV dengan Total Harmonic Distortion (THD di bawah 5%. Kata kunci: Pusat Listrik Tenaga Surya (PLTS, photovoltaic, Cascaded H-Bridge Multilevel Inverter ABSTRACT The application of Multilevel Inverter in a Photovoltaic Solar Power Plant system could eliminate the needs of step-up transformer, which will reduce the system investment cost, simplify the system installation and also eliminate power losses of the transformer. In this paper, an inverter design was proposed with Cascaded H-Bridge Multilevel Inverter topology that is capable of converting low voltage DC power from several PV arrays into 20 kV AC power. The design resulted a 3 phase 27-level inverter where each level in the inverter has its own photovoltaic array, DC-DC boost converter, H-bridge inverter, and the 3 phase output is connected to LCL filter. Each component of the Inverter and the system were then modelled in MATLAB

  10. Load shedding and emergency load sequencing system at Sizewell B power station

    International Nuclear Information System (INIS)

    Bowcock, S.; Miller, D.

    1992-01-01

    Sizewell B Nuclear Power Station has a main electrical system that connects together the main turbo-generators, generating at 23.5kV, the 400kV grid and the auxiliary equipment required to operate the station. A separate essential electrical system fed from the main electrical system, supplies all the auxiliaries required to shut-down the nuclear reactor and maintain it in a safe shut-down condition. For safety reasons four similar independent essential electrical systems are provided, each headed by a 3.3kV switchboard and a stand-by 8MW diesel generator. Feeds from the 3.3kV switchboards in turn supply the essential 3.3kV drives and transformer fed 415V essential switchboards. The function of the Load Shedding and Emergency Load Sequencing (LSELS) System is to monitor the condition of the 3.3kV incoming supply from the main electrical system to each essential 3.3kV switchboard and initiate its replacement, with the supply from the associated diesel generator, if it is outside set parameters. In order to achieve this transfer the essential electrical system load must be reduced to a level which the diesel can accommodate as a standing load and then allow the sequenced reconnection of required loads so as not to overload the diesel. The LSELS equipment is categorised as Safety Category 1E and has a significant importance to the safe operation of the power station. Therefore the design of the system must be highly reliable and the purpose of this paper is to detail the design approach used to ensure that a high system reliability is achieved. (Author)

  11. Optimum voltage of auxiliary systems for thermal and nuclear power plants

    International Nuclear Information System (INIS)

    Tokumitsu, Iwao; Segawa, Motomichi

    1979-01-01

    In the power plants in Japan, their unit power output has been greatly enhanced since the introduction of new powerful thermal power plants from 1950's to 1960's. In both thermal and nuclear power plants, 1,000 MW machines have been already in operation. The increase of unit power output results in the increase of in-plant load capacity. Of these the voltage adopted for in-plant low voltage systems is now mainly 440 V at load terminals, and the voltage for in-plant high voltage systems has been changing to 6 kV level via 3 kV and 4 kV levels. As plant capacity increases, the load of low voltage systems significantly increases, and it is required to raise the voltage of 400 V level. By the way, the low voltage in AC is specified to be not higher than 600 V. This makes the change within the above range comparatively easy. Considering these conditions, it is recommended to change the voltage for low voltage systems to 575 V at power source terminals and 550 V at load terminals. Some merits in constructing power systems and in economy by raising the voltage were examined. Though demerits are also found, they are only about 15% of total merits. The most advantageous point in raising the voltage is to be capable of increasing the supplying range to low voltage system loads. (Wakatsuki, Y.)

  12. 600 kV modulator design for the SLAC Next Linear Collider Test Accelerator

    International Nuclear Information System (INIS)

    Harris, K.; de Lamare, J.; Nesterov, V.; Cassel, R.

    1992-07-01

    Preliminary design for the SLAC Next Linear Collider Test Accelerator (NLCTA) requires a pulse power source to produce a 600 kV, 600 A, 1.4 μs, 0.1% flat top pulse with rise and fall times of approximately 100 ns to power an X-Band klystron with a microperveance of 1.25 at ∼ 100 MW peak RF power. The design goals for the modulator, including those previously listed, are peak modulator pulse power of 340 MW operating at 120 Hz. A three-stage darlington pulse-forming network, which produces a >100 kV, 1.4 μs pulse, is coupled to the klystron load through a 6:1 pulse transformer. Careful consideration of the transformer leakage inductance, klystron capacitance, system layout, and component choice is necessary to produce the very fast rise and fall times at 600 kV operating continuously at 120 Hz

  13. Voltages and electric currents mensuration - class 15 kV - for systems electro-optical and magneto-optical; Medicao de tensoes e correntes - classe 15 kv - por sistemas eletro-opticos e magneto-opticos

    Energy Technology Data Exchange (ETDEWEB)

    Costa, Marcos Rodrigues

    1996-07-01

    The technical feasibility of the development of a novel system measuring of high voltage and current in 15 kV distribution lines was presented. The system is basically the combination of two other systems, one conventional and other electro-optical. The conventional subsystem is based on voltage dividers and magnetic rings while the electro-optical subsystem uses LEDs, resistors, optical-fibers and photodetectors. The system was completely tested in laboratory and its main characteristics are low price, easy of installation and flexibility. Two software for data acquisition by GPIB and A/D boards were also developed. The can provide reports on voltages, currents, power and phase-power. (author)

  14. TFTR neutral beam power system

    International Nuclear Information System (INIS)

    Deitz, A.; Murray, H.; Winje, R.

    1977-01-01

    The TFTR NB System will be composed of four beam lines, each containing three ion sources presently being developed for TFTR by the Lawrence Berkeley Laboratories (LBL). The Neutral Beam Power System (NBPS) will provide the necessary power required to operate these Ion Sources in both an experimental or operational mode as well as test mode. This paper describes the technical as well as the administrative/management aspects involved in the development and building of this system. The NBPS will combine the aspects of HV pulse (120 kV) and long pulse width (0.5 sec) together to produce a high power system that is unique in the Electrical Engineering field

  15. Quality control of a kV cone beam computed tomography imaging system

    International Nuclear Information System (INIS)

    Marguet, M.; Bodez, V.

    2009-01-01

    Purpose: This work presents the introduction of a quality assurance program for the On-Board Imager (O.B.I., Varian) kV cone beam computed tomography (kV C.B.C.T.) system, together with the results of 1 year monthly testing. Materials and methods: Firstly the geometric precision and stability of the equipment and of the associated software were evaluated using the Marker phantom. The coincidence of the accelerator isocenter and the imager isocenter was verified as well as the accuracy of the registration of kV cone beam computed tomography (kV C.B.C.T.) with reference CT images. Then, the kV C.B.C.T. image quality was evaluated using the Catphan 504 phantom and ArtiScan software (Aquilab) for both full-fan (F.F.) and half-fan (H.F.) imaging modes. Results: The kV C.B.C.T. isocenter and image registration with correction of the table position were found to be within a tolerance of 2.0 mm. Concerning the kV C.B.C.T. image quality, image noise and uniformity, the Hounsfield units (HU) stability and linearity, geometric distortion and high contrast resolution were all found to be within the manufacturer's recommendations for both F.F. and H.F. modes. However, the low contrast resolution for the HF mode did not meet the manufacturer's specifications. Conclusion: The quality assurance tests introduced have defined the initial system characteristics and their evolution during a period of 1 year, demonstrating the stability of the O.B.I.. (authors)

  16. Evidence of Gate Voltage Oscillations during Short Circuit of Commercial 1.7 kV/ 1 kA IGBT Power Modules

    DEFF Research Database (Denmark)

    Reigosa, Paula Diaz; Wu, Rui; Iannuzzo, Francesco

    2015-01-01

    This paper analyzes the evidence of critical gate voltage oscillations in 1.7 kV/1 kA Insulated-Gate Bipolar Transistor (IGBT) power modules under short circuit conditions. A 6 kA/1.1 kV Non-Destructive Test (NDT) set up for repeatable short circuit tests has been built with a 40 nH stray inducta...

  17. Design and development of power supplies for high power IOT based RF amplifier

    International Nuclear Information System (INIS)

    Kumar, Yashwant; Kumari, S.; Ghosh, M.K.; Bera, A.; Sadhukhan, A.; Pal, S.S.; Khare, V.K.; Tiwari, T.P.; Thakur, S.K.; Saha, S.

    2013-01-01

    Design, development, circuit topology, function of system components and key system specifications of different power supplies for biasing electrodes of Thales Inductive Output Tube (IOT) based high power RF amplifier are presented in this paper. A high voltage power supply (-30 kV, 3.2A dc) with fast (∼microsecond) crowbar protection circuit is designed, developed and commissioned at VECC for testing the complete setup. Other power supplies for biasing grid electrode (300V, 0.5A dc) and Ion Pump (3 kV, 0.1mA dc) of IOT are also designed, developed and tested with actual load. A HV Deck (60kV Isolation) is specially designed in house to place these power supplies which are floating at 30 kV. All these power supplies are powered by an Isolation Transformer (5 kVA, 60 kV isolation) designed and developed in VECC. (author)

  18. A field experiment on power line stabilization by SMES system

    International Nuclear Information System (INIS)

    Irie, F.; Takeo, M.; Sato, S.; Katahira, O.; Fukui, F.; Takamatsu, M.

    1992-01-01

    In this paper field experiments on stabilization of a hydro power plant by a SMES system are reported, where a generator having a rating of 60 kW at 3.3kV is connected to a 6.6kV power distribution line. The SMES system is composed of two 30kVA GTO convertors and a superconducting magnet system with an energy of 30kJ at 100A. Experiments of stabilization for the generator fluctuation caused by a sudden insertion of inductors in the line are successfully performed for some control modes. The value of the SMES system to compensate for a short period voltage dip is also confirmed

  19. Systems for protection and automation of distribution electric networks 22 kv

    International Nuclear Information System (INIS)

    Horak, M.

    2012-01-01

    This article deals with the new concept of fault location in overhead and cable 22 kV distribution systems, which are operated by ZSE Distribucia, a.s.. In the past the localisation of faults was a demanding and lengthy procedure, because the electric protection indicated only the affected output feeder. The exact fault point was then localised by manipulation in the field and by test switching in the power line where the fault took place. The current development of electric facilities and sharp fall in prices give use the possibility to broadly apply the simple digital metering devices equipped with the electric protection function. Once these devices are positioned densely along the individual power lines of the network, it is possible to localise the failure position quite exactly and electricity supply can be quickly restored. (Authors)

  20. Model for the ready definition and approximate comparison of alternative high voltage transmission systems. Phases II and III. Application to electric systems within the contiguous United States. [800 and 1200 kV; 400, 600, and 800 kV dc

    Energy Technology Data Exchange (ETDEWEB)

    1979-08-01

    Research on power delivery alternatives is reported. The first phase of this work was to develop a model of overhead transmission systems in the range of 362 to 1200 kV ac, and +-400 to +-800 kV dc. Such systems included transmission from generation to load and inter-connection of two large integrated systems, with and without the existence of an underlying lower voltage network in either case. This phase has been completed. The second and third phases involved application of the model to electric systems within selected regions of the US, and the entire US, respectively, dealing with real situations and including projected expansion to year 1987. The potential benefits and costs of using higher than existing transmission voltages were to be evaluated on this basis. Additionally, the most advantageous new voltage was to be determined taking into account direct and indirect benefits and costs. The results of the second and third phases are presented.

  1. Experiment and operation of a LHCD-35 kV/2.8 MW/1000 s high-voltage power supply on HT-7 tokamak

    International Nuclear Information System (INIS)

    Huang Yiyun

    2002-01-01

    A-35 kV/2.8 MW/1000s high-voltage power supply (HVPS) for HT-7 superconducting tokamak has been built successfully. The HVPS is scheduled to run on a 2.45 GHz/1 MW lower hybrid current drive (LHCD) system of HT-7 superconducting tokamak before the set-up of HT-7 superconducting tokamak in 2003. The HVPS has a series of advantages such as good steady and dynamic response, logical computer program controlling the HVPS without any fault, operational panel and experimental board for data acquisition, which both are grounded distinctively in a normative way to protect the main body of HVPS along with its attached equipment from dangers. Electric power cables and other control cables are disposed reasonably, to prevent signals from magnetic interference and ensure the precision of signal transfer. The author introduced the experiment and operation of a 35 kV/2.8 MW/1000 s HVPS for 2.45 GHz/1 MW LHCD system. The reliability and feasibility of the HVPS has been demonstrated in comparison with experimental results of original design and simulation data

  2. Major Refit for CERN's 400 kV Substation

    CERN Multimedia

    2001-01-01

    The 400 kV substation on the Prévessin site brings in the electricity that powers CERN's accelerators and the majority of the Laboratory's installations. It was originally built in the 1970s for the SPS, and is one of only five privately owned 400 kV sub-stations in France. Three of the others belong to the national railway company, SNCF, supplying the Paris-Marseilles TGV line, the other is at the Cadarache research centre near mouth of the Rhone. After nearly thirty years of service, CERN's substation has just undergone a complete overhaul. The new main 18 kV switchboard for the SPS pulsed network. The electricity supply for the original Prévessin substation was from the 400 kV EDF network, delivered through three 90 MW transformers at 18 kV to the SPS pulsed network, With the arrival of LEP, two 110 MW transformers were added to supply the new accelerator. Now, as CERN gears up for the LHC, additional pulsed power capacity is needed to supply the transfer lines carrying protons from...

  3. Evaluation of cooperation WPP and PV connected through the shared transformer to the network 22kV

    Directory of Open Access Journals (Sweden)

    Tomas Sumbera

    2012-01-01

    Full Text Available The article deals with evaluation the cooperation possibility of wind and solar power plants connected through the common transformator to the 22kV network. Cooperation evaluation is, based on measured data, for wind power plant about installed capacity 2MW and for solar power plant about installed capacity 1,1MWp. In the next part of this article there is the analysis of suitable localities for construction of „hybrid system (WPP+PV“ in the Czech Republic. The last part of the article deals with analysis of active power fluctuation of individuals electric sources compared with system WPP+PV and with evaluation the effects after system connection WPP+PV to the 22kV network.

  4. Auxiliary System Load Schemes in Large Thermal and Nuclear Power Plants

    International Nuclear Information System (INIS)

    Kuzle, I.; Bosnjak, D.; Pandzic, H.

    2010-01-01

    Uninterrupted auxiliary system power supply in large power plants is a key factor for normal operation, transient states, start-ups and shutdowns and particularly during fault conditions. Therefore, there are many challenges in designing the main electrical system as well as the auxiliary systems power supply. Depending upon the type of fuel used and the environmental control system required, a thermal power plant may consume as much as 10% of its total generation for auxiliary power, while a nuclear power plant may require only 4 - 6% auxiliaries. In general, the larger the power generating plant, the higher the voltage selected for the AC auxiliary electric system. Most stations in the 75 to 500 MW range utilize 4,2 kV as the base auxiliary system voltage. Large generating stations 500 - 1000 MW and more use voltage levels of 6,9 kV and more. Some single dedicated loads such as electric driven boiler feed pumps are supplied ba a 13,8 kV bus. While designing the auxiliary electric system, the following areas must be considered: motor starting requirements, voltage regulation requirements, short-circuit duty requirements, economic considerations, reliability and alternate sources. Auxiliary power supply can't be completely generalized and each situation should be studied on its own merits to determine the optimal solution. Naturally, nuclear power plants have more reliability requirements and safety design criteria. Main coolant-pump power supply and continuity of service to other vital loads deserve special attention. This paper presents an overview of some up-to-date power plant auxiliary load system concepts. The main types of auxiliary loads are described and the electric diagrams of the modern auxiliary system supply concepts are given. Various alternative sources of auxiliary electrical supply are considered, the advantages and disadvantages of these are compared and proposals are made for high voltage distribution systems around the thermal and nuclear plant

  5. Microprocessor supervised stability control system for the united power system of Middle Volga in fault conditions

    Energy Technology Data Exchange (ETDEWEB)

    Berdnikov, V I; Birgel, E R; Kovalev, V D; Kuznestov, A N

    1994-12-31

    The development of the 500 kV UPS of Middle Volga, the complication of its configuration and operating conditions particularly in connection with concentration of the generating power at Balakovo NPS have aggravated the problem of stability of the Middle Volga UPS when high power is transmitted along the 500 kV transient system. In this case the necessity for improving control actions` dosage accuracy has also appeared. This work discusses solution to the above mentioned issue. (author) 3 figs.

  6. Survey of magnetic fields near BPA 230-kV and 500-kV transmission lines

    International Nuclear Information System (INIS)

    Perrin, N.; Aggarwal, R.P.

    1991-01-01

    The purpose of this study was to characterize typical levels and variability of 60Hz magnetic fields at the centerline and edge of right-of-way of Bonneville Power Administration (BPA) 230-kV and 500-kV transmission lines. This was accomplished by taking magnetic field measurements at over 800 spans in Oregon and Washington. The spans were sampled using a stratified random sampling procedure with region (East vs. West), voltage (230-kV vs 500-kV), and circuit configuration as strata. There were five different circuit configuration groups for each region/voltage category requiring a total of 200 strata. Magnetic field measurements were taken at 13 locations under each span using an EMDEX-C as a survey meter. Additional information recorded for each span included conductor height (at 10 locations), right-of-way width, longitudinal and lateral slope, time of day, vegetation, terrain, weather conditions, temperature, wind speed, span length and presence of other lines in the corridor. 9 refs., 17 figs., 26 tabs

  7. Comparative assessment of 3.3kV/400A SiC MOSFET and Si IGBT power modules

    DEFF Research Database (Denmark)

    Ionita, Claudiu; Nawaz, Muhammad; Ilves, Kalle

    2017-01-01

    In this paper, a comparative evaluation between a commercial 3.3 kV/400 A Si-IGBT and a 3.3 kV/400 A SiC MOSFET power module in half-bridge configuration is presented. With a constant current of 250 A, a lower forward voltage (VDS) drop of 1.6 V is obtained for SiC MOSFET at 300 K compared to Si ...... the pulse duration was increased to 4 μs, where a short-circuit energy of 9.1 J was obtained. The cause of the failure is the thermal runaway leading to a drain-source short....

  8. Engineering of beam direct conversion for a 120-kV, 1-MW ion beam

    International Nuclear Information System (INIS)

    Barr, W.L.; Doggett, J.N.; Hamilton, G.W.; Kinney, J.D.; Moir, R.W.

    1977-01-01

    Practical systems for beam direct conversion are required to recover the energy from ion beams at high efficiency and at very high beam power densities in the environment of a high-power, neutral-injection system. Such an experiment is now in progress using a 120-kV beam with a maximum total current of 20 A. After neutralization, the H + component to be recovered will have a power of approximately 1MW. A system testing these concepts has been designed and tested at 15 kV, 2 kW in preparation for the full-power tests. The engineering problems involved in the full-power tests affect electron suppression, gas pumping, voltage holding, diagnostics, and measurement conditions. Planning for future experiments at higher power includes the use of cryopumping and electron suppression by a magnetic field rather than by an electrostatic field. Beam direct conversion for large fusion experiments and reactors will save millions of dollars in the cost of power supplies and electricity and will dispose of the charged beam under conditions that may mot be possible by other techniques

  9. Engineering of beam direct conversion for a 120-kV, 1-MW ion beam

    International Nuclear Information System (INIS)

    Barr, W.L.; Doggett, J.N.; Hamilton, G.W.; Kinney, J.D.; Moir, R.W.

    1977-01-01

    Practical systems for beam direct conversion are required to recover the energy from ion beams at high efficiency and at very high beam power densities in the environment of a high-power, neutral-injection system. Such an experiment is now in progress using a 120-kV beam with a maximum total current of 20 A. After neutralization, the H + component to be recovered will have a power of approximately 1 MW. A system testing these concepts has been designed and tested at 15 kV, 2 kW in preparation for the full-power tests. The engineering problems involved in the full-power tests affect electron suppression, gas pumping, voltage holding, diagnostics, and measurement conditions. Planning for future experiments at higher power includes the use of cryopumping and electron suppression by a magnetic field rather than by an electrostatic field. Beam direct conversion for large fusion experiments and reactors will save millions of dollars in the cost of power supplies and electricity and will dispose of the charged beam under conditions that may not be possible by other techniques

  10. 130 kV 130 A high voltage switching mode power supply for neutral beam injectors-Control issues and algorithms

    International Nuclear Information System (INIS)

    Ganuza, D.; Garcia, F.; Zulaika, M.; Perez, A.; Jones, T.T.C.

    2005-01-01

    The company JEMA has delivered to the Joint European Torus (JET facility in Culham) two high voltage switching mode power supplies (HVSMPS) each rated 130 kVdc and 130 A. One HVSMPS feeds the grids of two PINI loads. This paper describes the main control issues and the algorithms developed for the project. The most demanding requirements from the control point of view is an absolute accuracy of ±1300 V and the possibility of performing up to 255 re-applications of the high voltage during a 20 s pulse. Keeping the output voltage ripple to the specified tolerance has been a major achievement of the control system. Since the output stage is formed of several modules (120) connected in series, their stray capacitance to ground significantly influences the individual contribution of each single module to the global output voltage. Two complementary techniques have been used to balance the effects of the stray capacities. The fast re-applications requirement has a significant impact on the intermediate dc link. This section is composed of a capacity of 0.83 F, which feeds the 120 invertor modules. The dc link is fed by a 12 pulse SCR rectifier, whose matching transformers are connected to the 36 kV grid. Every re-application and every voltage shutdown supposes a quasi-instantaneous power step of 17 MW. Fast open loop algorithms have been implemented in order to keep the dc link voltage within acceptable margins. Moreover, the HVSMPS output characteristics have to be maintained during the rapid and important voltage fluctuations of the 36 kV mains (28-37 kV). The general control system is based on a Simatic S7 PLC, and a SCADA user interface. Up to 1000 signals are acquired. The control system has shown to be also a useful tool to allow for a rapid and accurate identification of faults and their origin

  11. Initial application of a geometric QA tool for integrated MV and kV imaging systems on three image guided radiotherapy systems.

    Science.gov (United States)

    Mao, Weihua; Speiser, Michael; Medin, Paul; Papiez, Lech; Solberg, Timothy; Xing, Lei

    2011-05-01

    Several linacs with integrated kilovoltage (kV) imaging have been developed for delivery of image guided radiation therapy (IGRT). High geometric accuracy and coincidence of kV imaging systems and megavoltage (MV) beam delivery are essential for successful image guidance. A geometric QA tool has been adapted for routine QA for evaluating and characterizing the geometric accuracy of kV and MV cone-beam imaging systems. The purpose of this work is to demonstrate the application of methodology to routine QA across three IGRT-dedicated linac platforms. It has been applied to a Varian Trilogy (Varian Medical Systems, Palo Alto, CA), an Elekta SynergyS (Elekta, Stockholm, Sweden), and a Brainlab Vero (Brainlab AG, Feldkirchen, Germany). Both the Trilogy and SynergyS linacs are equipped with a retractable kV x-ray tube and a flat panel detector. The Vero utilizes a rotating, rigid ring structure integrating a MV x-ray head mounted on orthogonal gimbals, an electronic portal imaging device (EPID), two kV x-ray tubes, and two fixed flat panel detectors. This dual kV imaging system provides orthogonal radiographs, CBCT images, and real-time fluoroscopic monitoring. Two QA phantoms were built to suit different field sizes. Projection images of a QA phantom were acquired using MV and kV imaging systems at a series of gantry angles. Software developed for this study was used to analyze the projection images and calculate nine geometric parameters for each projection. The Trilogy was characterized five times over one year, while the SynergyS was characterized four times and the Vero once. Over 6500 individual projections were acquired and analyzed. Quantitative geometric parameters of both MV and kV imaging systems, as well as the isocenter consistency of the imaging systems, were successfully evaluated. A geometric tool has been successfully implemented for calibration and QA of integrated kV and MV across a variety of radiotherapy platforms. X-ray source angle deviations up to

  12. Power supply system for negative ion source at IPR

    Science.gov (United States)

    Gahlaut, Agrajit; Sonara, Jashwant; Parmar, K. G.; Soni, Jignesh; Bandyopadhyay, M.; Singh, Mahendrajit; Bansal, Gourab; Pandya, Kaushal; Chakraborty, Arun

    2010-02-01

    The first step in the Indian program on negative ion beams is the setting up of Negative ion Experimental Assembly - RF based, where 100 kW of RF power shall be coupled to a plasma source producing plasma of density ~5 × 1012 cm-3, from which ~ 10 A of negative ion beam shall be produced and accelerated to 35 kV, through an electrostatic ion accelerator. The experimental system is modelled similar to the RF based negative ion source, BATMAN presently operating at IPP, Garching, Germany. The mechanical system for Negative Ion Source Assembly is close to the IPP source, remaining systems are designed and procured principally from indigenous sources, keeping the IPP configuration as a base line. High voltage (HV) and low voltage (LV) power supplies are two key constituents of the experimental setup. The HV power supplies for extraction and acceleration are rated for high voltage (~15 to 35kV), and high current (~ 15 to 35A). Other attributes are, fast rate of voltage rise (< 5ms), good regulation (< ±1%), low ripple (< ±2%), isolation (~50kV), low energy content (< 10J) and fast cut-off (< 100μs). The low voltage (LV) supplies required for biasing and providing heating power to the Cesium oven and the plasma grids; have attributes of low ripple, high stability, fast and precise regulation, programmability and remote operation. These power supplies are also equipped with over-voltage, over-current and current limit (CC Mode) protections. Fault diagnostics, to distinguish abnormal rise in currents (breakdown faults) with over-currents is enabled using fast response breakdown and over-current protection scheme. To restrict the fault energy deposited on the ion source, specially designed snubbers are implemented in each (extraction and acceleration) high voltage path to swap the surge energy. Moreover, the monitoring status and control signals from these power supplies are required to be electrically (~ 50kV) isolated from the system. The paper shall present the

  13. Power supply system for negative ion source at IPR

    International Nuclear Information System (INIS)

    Gahlaut, Agrajit; Sonara, Jashwant; Parmar, K G; Soni, Jignesh; Bandyopadhyay, M; Singh, Mahendrajit; Bansal, Gourab; Pandya, Kaushal; Chakraborty, Arun

    2010-01-01

    The first step in the Indian program on negative ion beams is the setting up of Negative ion Experimental Assembly - RF based, where 100 kW of RF power shall be coupled to a plasma source producing plasma of density ∼5 x 10 12 cm -3 , from which ∼ 10 A of negative ion beam shall be produced and accelerated to 35 kV, through an electrostatic ion accelerator. The experimental system is modelled similar to the RF based negative ion source, BATMAN presently operating at IPP, Garching, Germany. The mechanical system for Negative Ion Source Assembly is close to the IPP source, remaining systems are designed and procured principally from indigenous sources, keeping the IPP configuration as a base line. High voltage (HV) and low voltage (LV) power supplies are two key constituents of the experimental setup. The HV power supplies for extraction and acceleration are rated for high voltage (∼15 to 35kV), and high current (∼ 15 to 35A). Other attributes are, fast rate of voltage rise (< 5ms), good regulation (< ±1%), low ripple (< ±2%), isolation (∼50kV), low energy content (< 10J) and fast cut-off (< 100μs). The low voltage (LV) supplies required for biasing and providing heating power to the Cesium oven and the plasma grids; have attributes of low ripple, high stability, fast and precise regulation, programmability and remote operation. These power supplies are also equipped with over-voltage, over-current and current limit (CC Mode) protections. Fault diagnostics, to distinguish abnormal rise in currents (breakdown faults) with over-currents is enabled using fast response breakdown and over-current protection scheme. To restrict the fault energy deposited on the ion source, specially designed snubbers are implemented in each (extraction and acceleration) high voltage path to swap the surge energy. Moreover, the monitoring status and control signals from these power supplies are required to be electrically (∼ 50kV) isolated from the system. The paper shall

  14. Modeling and power system stability of VSC-HVDC systems for grid-connection of large offshore windfarms

    Energy Technology Data Exchange (ETDEWEB)

    Xue Yijing [Vestas China, Beijing (China); Akhmatov, Vladislav [Technical Univ. of Denmark, Lyngby (Denmark). Centre for Electric Technology

    2009-07-01

    Utilization of Voltage Source Converter (VSC) - High Voltage Direct Current (HVDC) systems for grid-connection of large offshore windfarms becomes relevant as installed power capacities as well as distances to the connection points of on-land transmission systems increase. At the same time, the grid code requirements of the Transmission System Operators (TSO), including ancillary system services and Low-Voltage Fault-Ride-Through (LVFRT) capability of large offshore windfarms, become more demanding. This paper presents a general-level model of and a LVFRT solution for a VSC-HVDC system for grid-connection of large offshore windfarms. The VSC-HVDC model is implemented using a general approach of independent control of active and reactive power in normal operations. The on-land VSC inverter, i.e. a grid-side inverter, provides voltage support to the transmission system and comprises a LVFRT solution in short-circuit faults. The presented model, LVFRT solution and impact on the system stability are investigated as a case study of a 1,000 MW offshore windfarm grid-connected through a VSC-HVDC system. The investigation is carried out on a model of the west Danish, with some elements of the north German, 400 kV, 220 kV and 150 kV transmission systems stage 2005-2006 using the DIgSILENT PowerFactory simulation program. In the investigation, a thermal power plant just south to the Danish border has been substituted by this 1,000 MW offshore windfarm utilizing the VSC-HVDC system. The investigation has shown that the substitution of a thermal power plant by a VSC-HVDC connected offshore windfarm should not have any negative impact on the short-term stability of the west Danish transmission system. The investigation should be repeated applying updated system model stages and offshore wind power commissioning schedules in the North and Baltic Seas. (orig.)

  15. TFTR neutral-beam power system

    International Nuclear Information System (INIS)

    Winje, R.A.

    1982-10-01

    The TFTR Neutral Beam Power System (NBPS) consists of the accelerator grid power supply and the auxiliary power supplies required to operate the TFTR 120-keV ion sources. The current configuration of the NBPS including the 11-MVA accelerator grid power supply and the Arc and Filament power supplies isolated for operation at accelerator grid voltages up to 120 kV, is described. The prototype NBPS has been assembled at the Princeton Plasma Physics Laboratory and has been operated. The results of the initial operation and the description and resolution of some of the technical problems encountered during the commissioning tests are presented

  16. On the use of programmable logical controllers (PLC) in the emergency control schemes for the 750 kV system

    Energy Technology Data Exchange (ETDEWEB)

    Lima, Roberto Campos de; Oliveira, Mario Cesar Santos de [FURNAS, Rio de Janeiro, RJ (Brazil)

    1994-12-31

    The energy produced at the Itaipu Power Plant for the Brazilian Interconnected System is transmitted through two different transmission system: -HVDC system, with two bipoles of +- 600 kV, 6300 MW which connect the substation of Foz do Iguacu in the State of Parana, to substation of Ibiuna in the State of Sao Paulo, transmitting the energy generated in 50 Hz units. This system was entirely commissioned on september of 1987. (author) 3 refs., 5 figs.

  17. EHV/HV Underground Cable Systems for Power Transmission

    DEFF Research Database (Denmark)

    Bak, Claus Leth

    of the transmission system must be re‐thought in order to accommodate the transmission needs for the future. New lines have to be constructed. Transmission lines are usually laid out as overhead lines, which are large structures, i.e. a 400 kV power pylon is 50 meters high. According to public opinion, such power...

  18. Rated power factor and excitation system of large turbine generator

    International Nuclear Information System (INIS)

    Tokumitsu, Iwao; Watanabe, Takashi; Banjou, Minoru.

    1979-01-01

    As for the rated power factor of turbine generators for thermal power stations, 90% has been adopted since around 1960. On the other hand, power transmission system has entered 500 kV age, and 1,000 kV transmission is expected in the near future. As for the supply of reactive power from thermal and nuclear turbine generators, the necessity of supplying leading reactive power has rather increased. Now, the operating power factor of thermal and nuclear generators becomes 96 to 100% actually. As for the excess stability of turbine generators owing to the strengthening of transmission system and the adoption of super-high voltage, the demand of strict conditions can be dealt with by the adoption of super-fast response excitation system of thyristor shunt winding self exciting type. The adoption of the turbine generators with 90 to 95% power factor and the adoption of the thyristor shunt winding self exciting system were examined and evaluated. The rated power factor of generators, excitation system and economy of adopting these systems are explained. When the power factor of generators is increased from 0.9 to 0.95, about 6% of saving can be obtained in the installation cost. When the thyristor shunt winding self excitation is adopted, it is about 10% more economical than AC excitation. (Kako, I.)

  19. Electronics system for the 150 kV negative ion test stand at BNL

    International Nuclear Information System (INIS)

    Larson, R.A.

    1977-01-01

    The 150 kV test stand at BNL is being used to investigate the extraction, acceleration and transport problems associated with the development of intense negative ion beams. The power supplies associated with these functions as well as the control and monitoring electronics are described

  20. Power systems for the Doublet III 2-MW ECH system

    International Nuclear Information System (INIS)

    Remsen, D.B. Jr.

    1981-10-01

    A system providing 5 second pulses at 60 GHz from ten 200 kW gyrotrons is being prepared for electron cyclotron heating experiments on Doublet III. The power supply for the gyrotron system is a power supply currently under construction by Universal Voltronics Corporation for the Doublet III neutral beam power supply, and is to have the option of reverse polarity (negative) to fill the needs of the system of ten gyrotons operating in parallel. The output of this power supply is 80 kV at 100A for 5 second pulses with good regulation. The output pulse rise and fall times and fault protection response time are all compatible with the gyrotron requirements

  1. Software for optimal selection of places for installation of balancing devices in 0,4 kV electric power systems loaded with electric motors

    Directory of Open Access Journals (Sweden)

    Romanova Victoria

    2017-01-01

    Full Text Available This publication considers the issues of development of the software program for designing of 0,4 kV power supply systems with motor-actuated load under voltage unsymmetry conditions (using the example of the Trans-Baikal Territory. Voltage unsymmetry is practically constant phenomenon in the electric power networks of different voltage types. Voltage unsymmetry effects significantly the electric power consumers, including the supply mains itself. It has especially negative impact on the electrical equipment operation process and its lifetime. The urgency of the problem is confirmed by multiple research on the same topic and by significant number of damages suffered by the electric power consumers staying in service (especially in the Trans-Baikal Territory and in the Far-East regions. Voltage unsymmetry causes economic loss and reduction of the electromagnetic interference value by the voltage unsymmetry coefficient in negative-phase sequence (K2U gives inevitable economic effect accordingly. However, the payback period for the activities aimed at reduction of electromagnetic interference, will vary from some months to several years. The more accurate value of the payback period may be obtained using the developed software program. The developed software design program is implemented by means of the programming language C# in Microsoft Visual Studio environment, using the built-in cross-platform database SQLite. The software program shall allow making quick and accurate calculation of the power losses, to determine the economic feasibility of provision special measures for removal of the voltage unsymmetry, for determination of optimal application and location of the balancing devices. The software implementation in power systems loaded with electric motors will improve reliability and efficiency of asynchronous motors. The software is of interest for developers of projects on power supply systems for regions with non-linear loads.

  2. The control system based on PXI technology for high voltage power supply

    International Nuclear Information System (INIS)

    Chen Dehong; Zhang Ming; Ma Shaoxiang; Xia Linglong; Zeng Zhen; Zhang Xueliang; Wang Chuliang; Yu Kexun

    2014-01-01

    A 100 kV/60 A high voltage power supply (HVPS) is being developed to carry some auxiliary heating research on J-TEXT and supply the auxiliary heating system. The power supply which consists of 144 switch modules is based on PSM technology. For the requirement of isolation, control and protection, a control system based on the PCI extensions for instrumentation (PXI) which meets up with the CODAC standards is designed with developed PSM technology for the high voltage power supply. The compact structure of hardware in the control system is presented too. And the control strategy which is based on shift phase pulse width modulation is discussed Some tests are performed on the control system to validate the control strategy, the experimental results show that the system has a good control performance and fast response, which meets the control requirement of 100 kV/60 A high voltage power supply. (authors)

  3. Interlaboratory comparison of measuring results of magnetic field near 400 kV overhead power line

    Directory of Open Access Journals (Sweden)

    Grbić Maja

    2012-01-01

    Full Text Available The paper presents a comparison of measured results of magnetic field near 400 kV overhead power lines obtained by three laboratories. This interlaboratory comparison was performed to ensure confidence in the quality of the test results. The measured results were analyzed with standard methods, using En number, based on which the evaluation of the laboratories was performed.

  4. The electrically silent Kv6.4 subunit confers hyperpolarized gating charge movement in Kv2.1/Kv6.4 heterotetrameric channels.

    Directory of Open Access Journals (Sweden)

    Elke Bocksteins

    Full Text Available The voltage-gated K(+ (Kv channel subunit Kv6.4 does not form functional homotetrameric channels but co-assembles with Kv2.1 to form functional Kv2.1/Kv6.4 heterotetrameric channels. Compared to Kv2.1 homotetramers, Kv6.4 exerts a ~40 mV hyperpolarizing shift in the voltage-dependence of Kv2.1/Kv6.4 channel inactivation, without a significant effect on activation gating. However, the underlying mechanism of this Kv6.4-induced modulation of Kv2.1 channel inactivation, and whether the Kv6.4 subunit participates in the voltage-dependent gating of heterotetrameric channels is not well understood. Here we report distinct gating charge movement of Kv2.1/Kv6.4 heterotetrameric channels, compared to Kv2.1 homotetramers, as revealed by gating current recordings from mammalian cells expressing these channels. The gating charge movement of Kv2.1/Kv6.4 heterotetrameric channels displayed an extra component around the physiological K(+ equilibrium potential, characterized by a second sigmoidal relationship of the voltage-dependence of gating charge movement. This distinct gating charge displacement reflects movement of the Kv6.4 voltage-sensing domain and has a voltage-dependency that matches the hyperpolarizing shift in Kv2.1/Kv6.4 channel inactivation. These results provide a mechanistic basis for the modulation of Kv2.1 channel inactivation gating kinetics by silent Kv6.4 subunits.

  5. Design and test of a 40-kV, 80-A, 10-msec, neutral-beam power supply series

    International Nuclear Information System (INIS)

    North, G.G.

    1977-01-01

    To meet neutral-beam source requirements, a combination series switch/regulator system has been developed that can provide up to 40-kV at 80A output for 10-ms from the continuously decaying voltage of a charged capacitor bank. The system uses 100% feedback control of a series hard tube regulator. This feedback regulator is able to maintain a 40-kV output level for 100% load variations while the source voltage for the capacitor bank is drained from an initial 55-kV down to as low as 43-kV during a 10-ms pulse. In addition to controlling the output voltage, the series regulator tube also serves the dual role of a disconnect or interrupt switch at the end of each pulse and during the frequent occurrence of a neutral-beam source fault. In the interrupt mode, complete disconnect is achieved in less than 2-μs after first observance of a fault condition; recovery times to normal operation of less than 10-μs after fault clearance can be attained if desired

  6. Commissioning and operation of 130 kV/130 A switched-mode HV power supplies with the upgraded JET neutral beam injectors

    International Nuclear Information System (INIS)

    Edwards, D.C.; Bigi, M.; Brown, D.P.D.; Ganuza, D.; Garcia, F.; Hudson, Z.; Jones, T.T.C.; Perez, A.

    2005-01-01

    The design features, on-site testing, commissioning and operation are described of two new 130 kV/130 A HV power supply units serving four upgraded 130 kV/60 A positive ion neutral injectors (PINIs) on JET. Both units were factory tested at full power and pulse length into dummy resistive load. Following on-site installation, the factory tests were repeated. The transition from dummy-load testing to PINI operation required full integration of the HVPS within the overall JET control system, and rigorous testing of the co-ordinated actions and protections of all PINI power supplies (filament and arc for plasma source and negative suppression grid). The implementation of these functions is described. Extensive use was made of parasitic integrated test pulses, where the other PINIs could be operated normally, with the HVPS energised under full remote control together with the corresponding PINI plasma sources, but with the HVPS connected to dummy load. The amount of NB operation time dedicated to commissioning was thereby minimised, yet gave a high degree of confidence of readiness for HV energisation of the PINI, and first beam operation followed less than 24 h from HV connection to the PINI. The routine operating experience and performance, including load protection characteristics of the new HVPS units are also described

  7. End user reliability assessment of 1.2-1.7 kV commercial SiC MOSFET power modules

    DEFF Research Database (Denmark)

    Ionita, Claudiu; Nawaz, Muhammad

    2017-01-01

    This paper is a first attempt to offer reliability evaluation of full SiC power modules where several dies are connected in parallel to increase power rating capability. Here, five different power modules with voltage rating from 1.2-1.7 kV and current rating from 120-800 A from three vendors hav......, which is connected in parallel with the MOSFET chip. For another module, there has also been recorded a failure of the gate oxide during H3TRB....

  8. Non-destructive test for VHTR fuel using 160kV X-ray system in Hotcell

    Energy Technology Data Exchange (ETDEWEB)

    Kim, Young Jun; Yoo, Boung Ok; Choo, Yong sun; Baik Sang youl; Kim, Hee Moon; Ahn, Sang Bok [KAERI, Daejeon (Korea, Republic of)

    2016-05-15

    The research for VHTR which is one of the next generation reactor has been actively carried out. As a part of the research for VHTR, an irradiation examination for the VHTR fuel was performed to confirm an in-pile behavior in HANARO. The non-destructive test for the irradiated fuel is very important to understand the in-pile behavior of the fuel. Especially, the X-ray system is useful to observe the fuel shape without destruction. A dimensional change and defect of the fuel can be confirmed thorough the Xray system. Also, using the 3-D software and CT technology, the fuel shape can be intuitionally observed. The 450kV and 160kV X-ray system were installed and operated in IMEF hotcell. The 160kV X-ray system relatively using a low voltage is suitable to a small scale sample. And high resolution images can be obtained. In this study, the non-destructive test for the unirradiated and irradiated VHTR fuel were performed using the 160kV X-ray system. Through these test, the possibility for the X-ray inspection of irradiated fuel was confirmed. The non-destructive test for the unirradiated and irradiated VHTR fuel were performed using the 160kV X-ray system. The clear images of the irradiated coated particle were produced without the radiation damage during the Xray inspection. The X-ray images of the VHTR fuel will be utilized as the in-pile performance validation data.

  9. Non-destructive test for VHTR fuel using 160kV X-ray system in Hotcell

    International Nuclear Information System (INIS)

    Kim, Young Jun; Yoo, Boung Ok; Choo, Yong sun; Baik Sang youl; Kim, Hee Moon; Ahn, Sang Bok

    2016-01-01

    The research for VHTR which is one of the next generation reactor has been actively carried out. As a part of the research for VHTR, an irradiation examination for the VHTR fuel was performed to confirm an in-pile behavior in HANARO. The non-destructive test for the irradiated fuel is very important to understand the in-pile behavior of the fuel. Especially, the X-ray system is useful to observe the fuel shape without destruction. A dimensional change and defect of the fuel can be confirmed thorough the Xray system. Also, using the 3-D software and CT technology, the fuel shape can be intuitionally observed. The 450kV and 160kV X-ray system were installed and operated in IMEF hotcell. The 160kV X-ray system relatively using a low voltage is suitable to a small scale sample. And high resolution images can be obtained. In this study, the non-destructive test for the unirradiated and irradiated VHTR fuel were performed using the 160kV X-ray system. Through these test, the possibility for the X-ray inspection of irradiated fuel was confirmed. The non-destructive test for the unirradiated and irradiated VHTR fuel were performed using the 160kV X-ray system. The clear images of the irradiated coated particle were produced without the radiation damage during the Xray inspection. The X-ray images of the VHTR fuel will be utilized as the in-pile performance validation data.

  10. CIAE 600 kV ns pulse neutron generator

    International Nuclear Information System (INIS)

    Shen Guanren; Guan Xialing; Chen Hongtao

    2001-01-01

    The overall composition of CIAE 600 kV ns Pulse Neutron Generator (CPNG) are introduced, and its characteristic, main technological performance and application were also given. CPNG consists of high voltage power supply with highest output voltage 600 kV, direct current 15 mA, stability and ripple ≤0.1%, 2214 mm x 1604 mm x 1504 mm stainless steel high voltage electrode, built in head equipment uniform field accelerating tube, ns pulsed installation, turbomolecular vacuum pump system and drift pipes at 0 degree and 45 degree. Its characteristics are: (1) high current beam; (2) high current beam ns pulsed installation made use of low energy for chopper and high energy for buncher; (3) compactly laid out and simple in structure

  11. A comparison of magnetic fields inside and outside high-voltage urban 110-kV power substations with the exposure recommendations of the Ukrainian regulatory authorities

    International Nuclear Information System (INIS)

    Okun, Oleksandr; Shevchenko, Sergey; Korpinen, Leena

    2013-01-01

    The aim of this study was to carry out theoretical investigations of power frequency magnetic fields (MFs), produced inside and outside the domain of urban 110-kV power substations and to establish a correspondence between the levels of the fields and the specified population limits as defined by Ukrainian regulations. The fields produced by high-voltage substations were studied based on the application of the numerical finite element methodology. The investigations have shown that magnetic flux density values calculated inside and outside the considered 110-kV power substations do not reach the exposure limits specified by the Ukrainian regulations (1750 μT) and by international guidelines (ICNIRP 2010). Inside the domain of the substation, the maximum value of MFs was found under the 10-kV bus-bars and it equalled 420 μT. (authors)

  12. The Effect of Phase-to-earth Faults on the Operating Conditions of a Separated 110 kV Grid Normally Operated with Effectively Earthed Neutral, and Temporarily Supplied from a Compensated 110 kV Grid

    Directory of Open Access Journals (Sweden)

    Wilhelm Rojewski

    2015-06-01

    Full Text Available The paper discusses the interoperability of the German compensated 110 kV grid and the Polish effectively earthed 110 kV grid. It is assumed that an area of one grid, separated from its power system, will be temporarily supplied from the other grid in its normal regime. Reference is made to the risks associated with phase-to-earth faults in grids so interconnected. Particular attention is paid to the working conditions of surge arresters and voltage transformers in the Polish 110 kV grid deprived of its neutral earthing when supplied from the German grid.

  13. Reconstruction of -35 kV/200 kW HVPS for test of klystron units in LHCD system

    International Nuclear Information System (INIS)

    Huang Yiyun

    2004-01-01

    The paper introduces the -35 kV/200 kW high voltage power supply (HVPS) which is specially used to test klystron units in LHCD system. The new klystrons must be tested under high voltage level before operation and the old klystrons which have worked for a longtime must be exercised by HVPS in lower hybrid current drive (LHCD) system. As the former HVPS has some shortages in engineering design and operation design, the HVPS has to be modified and rebuilt by adopting new method and technology to solve existing bottle-neck problems. (author)

  14. The electrical system of nuclear power plant

    International Nuclear Information System (INIS)

    Firman Silitonga; Gunarwan Prayitno

    2009-01-01

    In these system, electrical power system is supplied from two-offsite transmission system respective main transformer and house service transformer; and reserve transformer. The electrical load in these system consist of safety electrical system and non-safety electrical system, The safety electrical and non safety electrical systems consist of four 6,9 kV AC medium voltage bus and 480 V AC low voltage bus system. The DC power system consist of four safety 125 V DC power system and the two non-safety 125 DC power systems. The equipment in these electrical system is main turbine-generator; GTG safety; GTG alternate; uninterrupted power supply (UPS) and battery system. To protect electrical equipment and building to direct stroke and non direct stroke disturbances is installed netral grounding system and lightning protection and protection the personnel to touch-voltage is installed equipment grounding system and station grounding. The lightning arrester system is connected to station station grounding system. (author)

  15. Development of high power pumping system for capillary discharge EUV laser

    International Nuclear Information System (INIS)

    Sakai, Yusuke; Komatsu, Takanori; Watanabe, Masato; Okino, Akitoshi; Hotta, Eiki

    2008-01-01

    Development of high power pumping system for capillary discharge soft X-ray laser is reported. The pulsed power system consists of a 2.2 μF LC generator, a 2:54 step-up transformer and a 3 nF water capacitor. Taking advantage of high efficiency configuration, step-up ratio of water capacitor voltage to LC generator initial voltage is about 40 times. Consequently, obtained water capacitor voltage reaches about 450 kV when LC generator was charged to 12.5 kV. As a consequent, possibility of charging a water capacitor to 1 MV is demonstrated. With this extremely compact system, discharge current could be increased to nearly 100 kA through moderately long capillary, which leads to generation of high-density and high-temperature plasma column in order to realize EUV laser. (author)

  16. Modeling of Electric Field Around 100 MVA 150/20 KV Power Transformator Using Charge Simulation Method

    OpenAIRE

    Rachman, Noviadi Arief; Risdiyanto, Agus; Ramdan, Ade

    2013-01-01

    Charge Simulation Method is one of the field theory that can be used as an approach to calculate the electromagnetic distribution on the electrical conductor. This paper discussed electric field modeling around power transformator by using Matlab to find the safety distance. The safe distance threshold of the electric field to human health refers to WHO and SNI was 5 kV/m. The specification of the power transformator was three phases, 150/20 kV, and 100 MVA. The basic concept is to change the...

  17. FY 1998 Report on development of large-scale wind power generation systems. Part 2. Operational research on large-scale wind power generation systems; 1998 nendo ogata furyoku hatsuden system kaihatsu seika hokokusho. 2. Ogata furyoku hatsuden system no unten kenkyu

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1999-03-01

    The on-the-spot surveys are conducted and related information is collected for current status of wind power generators connected to power grid systems and simulation techniques therefor in the USA and European countries. In Denmark, the grid system to which wind power generators are connected is a 10kV radiation type system, by which these generators are connected to general consumers. Power quality is investigated by the programs developed by DEFU (Danske Elvarkers Forening Udredning). The German's Norderland Wind Park has the largest capacity in Europe with 35 units of 1.5MW generators. They are connected to a 110kV grind system via ISOREE to control disturbances to the commercial grid system. The USA, used to have the world largest wind power generation capacity, is now plays second fiddle to Germany whose capacity has now exceeded 2,000MW. The country is now seeing the second rush for construction of wind power generators, planning to have a new capacity of 570MW in 1998. Information is also collected from other countries or organizations, including the Netherlands, WREC, Italy and Spain. (NEDO)

  18. FY 1998 Report on development of large-scale wind power generation systems. Part 2. Operational research on large-scale wind power generation systems; 1998 nendo ogata furyoku hatsuden system kaihatsu seika hokokusho. 2. Ogata furyoku hatsuden system no unten kenkyu

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1999-03-01

    The on-the-spot surveys are conducted and related information is collected for current status of wind power generators connected to power grid systems and simulation techniques therefor in the USA and European countries. In Denmark, the grid system to which wind power generators are connected is a 10kV radiation type system, by which these generators are connected to general consumers. Power quality is investigated by the programs developed by DEFU (Danske Elvarkers Forening Udredning). The German's Norderland Wind Park has the largest capacity in Europe with 35 units of 1.5MW generators. They are connected to a 110kV grind system via ISOREE to control disturbances to the commercial grid system. The USA, used to have the world largest wind power generation capacity, is now plays second fiddle to Germany whose capacity has now exceeded 2,000MW. The country is now seeing the second rush for construction of wind power generators, planning to have a new capacity of 570MW in 1998. Information is also collected from other countries or organizations, including the Netherlands, WREC, Italy and Spain. (NEDO)

  19. Protection and switching system for the RFX power supply

    International Nuclear Information System (INIS)

    Browning, J.L.; Gray, J.W.; Mace, T.A.; Varley, G.L.

    1986-01-01

    The RFX toroidal field power supply comprises a large 4.8MJ (max) modular capacitor bank and four 14MW AC/DC converter flat-top power supply modules. The high fault level associated with the capacitor banks presents a problem in the design of the switching system, since mistiming could produce large currents in the flat-top supplies. The poloidal circuit consists of four groups of magnetising windings connected in series, each with its own flat-top convertor supply and opening switch transfer system. The flat-top converter supplies are needed when the transfer voltage has fallen from approximately 40kV to 1kV. Solutions to the problem of designing a fault-tolerant system which presents no danger to the flat-top converters are described in the paper. The adopted methods make use of hybrid ignitron/mechanical switches to give the required combination of switching speed and current carrying capacity, together with careful attention to the circuit layout of different switching elements. (author)

  20. Analysis of disturbances in the 15 kV traction power network by means of simulation calculations and tests; Analyse von Stoerungen im 15-kV-Bahnenergienetz durch Simulationsrechnungen und Versuche

    Energy Technology Data Exchange (ETDEWEB)

    Aeberhard, Martin; Basler, Egon [SBB AG, Zollikofen (Switzerland). Infrastruktur Energie

    2013-06-15

    Being one of the most important rail junctions of Switzerland, Olten is powered by a substation the 132 kV feeder of which features a number of structural weaknesses. Simulations were used to analyse the effects of electrical equipment failures in this substation on train operation, the nearby 15 kV overhead line system and the loads adjacent substations are subjected to. By considering all risks, a critical case of train operation with different load scenarios was investigated. The article includes a comparison between simulated and measured data and presents the conclusions that were drawn from the actions taken in respect of the future system design. (orig.)

  1. Life Cycle Assessment on a 765 kV Venezuelan Transmission System

    International Nuclear Information System (INIS)

    Wang, Wenlu; Tremouille, Gilles; Beroual, Abderrahmane; Bessede, Jean-Luc

    2011-03-01

    The demand to preserve the environment and form a sustainable development is greatly increasing in the recent decades all over the world, and this environmental concern is also merged in electrical power industry, resulting in many eco-design approaches in T and D industries. As a method of eco-design, Life Cycle Assessment (LCA) is a systematic tool that enables the assessment of the environmental impacts of a product or service throughout its entire life cycle, i.e. raw material production, manufacture, distribution, use and disposal including all intervening transportation steps necessary or caused by the product's existence. In T and D industries, LCA has been done for a lot of products individually, in order to see one product's environmental impacts and to seek for ways of improving its environmental performance. This eco-design for product approach is a rather well-developed trend, however, as only a single electrical product cannot provide the electrical power to users, electrical system consists of a huge number of components, in order to investigate system's environmental profile, the entire environmental profiles of different composing products has to be integrated systematically, that is to say, a system approach is needed. Under this philosophy, in this paper, an LCA using SimaPro (one kind of LCA software) is conducted on a whole Venezuelan 765 kV AC transmission system, which transmits 8000 MW hydro-electrical power through 760 km to this country's load centers, with total 7 substations, i.e. one sending end, 2 intermediate substations and 4 receiving ends. This LCA includes both transmission lines and substations, and then the environmental impacts of the whole transmission system are investigated. (authors)

  2. Draft Environmental Impact Statement: BPA/Puget Power Northwest Washington Transmission Project

    International Nuclear Information System (INIS)

    1993-11-01

    Bonneville Power Administration (BPS) and Puget Sound Power ampersand Light (Puget Power) propose to upgrade the existing high-voltage transmission system in the Whatcom and Skagit County area between the towns of Custer and Sedro Woolley, including within the city of Bellingham starting in 1995. The upgrades of the interconnected 230,000 volt (230-kV) and 115-kV systems are needed to increase the reliability of the local transmission system and to increase the import capacity on a nearby US-Canada 500-kV intertie by about 850 megawatts (MW). The increase in north-south transfer capability would be shared by BPA and Puget Power (about 425 MW each). Other actions would include replacement of an existing BPA 230-kV single-circuit, wood-pole H-frame transmission line with a lattice-steel double-circuit line; an existing Puget Power 115-kV single wood-pole transmission line rebuild, two short 115-kV Puget Power lines added at BPA's Bellingham Substation; and improvements made at existing BPA and Puget Power substations

  3. harmonic load modeling: a case study of 33 kv abuja steel mill feeder

    African Journals Online (AJOL)

    HOD

    An in-depth study of the harmonic orders inherent in a power system network is required ... This paper studied the harmonic orders of the 33 kV Abuja Steel Feeder .... models for various industrial and household electrical ..... Malaysia, 2013.

  4. Design and test of-80 kV snubber core assemblies for MFTF sustaining-neutral-beam power supplies

    International Nuclear Information System (INIS)

    Bishop, S.R.; Mayhall, D.J.; Wilson, J.H.; De Vore, K.R.; Ross, R.I.; Sears, R.G.

    1981-01-01

    Core snubbers, located near the neutral beam source ends of the Mirror Fusion Test Facility (MFTF) Sustaining Neutral Beam Power Supply System (SNBPSS) source cables, protect the neutral beam source extractor grid wires from overheating and sputtering during internal sparkdowns. The snubbers work by producing an induced counter-emf which limits the fault current and by absorbing the capacitive energy stored on the 80 kV source cables and power supplies. A computer program STACAL was used in snubber magnetic design to choose appropriate tape wound cores to provide 400 Ω resistance and 25 J energy absorption. The cores are mounted horizontally in a dielectric structure. The central source cable bundle passes through the snubber and terminates on three copper buses. Multilam receptacles on the buses connect to the source module jumper cables. Corona rings and shields limit electric field stresses to allow close clearances between snubbers

  5. Beam Extraction for 1-MV Electrostatic Accelerator at the 300 kV Test Stand

    Energy Technology Data Exchange (ETDEWEB)

    Park, Sae-Hoon; Kim, Yu-Seok [Dongguk University, Seoul (Korea, Republic of); Kwon, Hyeok-Jung; Cho, Yong-Sub [KOMAC, Gyeongju (Korea, Republic of)

    2015-05-15

    The Korea Multipurpose Accelerator Complex (KOMAC) has been developing a 300-kV test stand for a 1-MV electrostatic accelerator ion source. The ion source in the high-pressure vessel is required to have a high reliability. The test stand has been proposed and developed to confirm the stable operating conditions of the ion source. The ion source will be tested at the test stand to verify the long-time operating conditions. The test stand comprises a 300-kV high-voltage terminal, a battery for the ion-source power, a 60-Hz inverter, 200-MHz RF power, a 5-kV extraction power supply, a 300-kV accelerating tube, and a vacuum system. A beam extraction experiment for the test stand was performed, and the beam current was measured using a faraday cup in the chamber. A beam extraction results for the RF ion source will be presented. Beam extraction from the RF ion source of the test stand is verified by measuring the beam current with a faraday cup in the chamber. Thus far NI Labview, PLC and faraday cup have been used to measure the beam current. The OPC server is useful for monitoring the PLC values. The average beam current of (a), (b) and (c) shown in figure 2 are 110.241µA, 105.8597µA and 103.5278µA respectively.

  6. A Design of a 345-kV Electric Power Transmission Line Interlinking Ramu and Rouna Grids in Papua New Guinea

    Directory of Open Access Journals (Sweden)

    Sakato Francis

    2017-01-01

    Full Text Available According to PNG Power Limited (PPL, Papua New Guinea’s peak power demand is expected to increase from 210 MW in 2012 to 347 MW in 2026. Under the current state of the power sector in Papua New Guinea (PNG, it is critical to implement measures to cope with the increasing power demand to promote investment, economic growth, and ultimately to achieve poverty reduction through economic growth. One of the solutions identified to improve the reliability of PNG power systems and thus to meet the demand is to interconnect the major grids in the country so that the loads could be shared among them. This project embarks in designing a 345-kV electric power transmission line to interlink the Ramu and Rouna power grids of Papua New Guinea. The design is done by analysing all the necessary aspects of the transmission lines with in-depth calculations performed using MATHCAD software. This design is the basis for extra-high voltage (EHV transmission network in anticipation for the power generation and demand growth in PNG.

  7. Improvement the Capacity of Cockcroft-Walton High Voltage Source from 300 kV/20 mA to 500 kV/20 mA for Accelerating Voltage of Electron Beam Machine

    International Nuclear Information System (INIS)

    Suprapto; Djasiman

    2002-01-01

    The improvement capacity of Cockcroft-Walton high voltage source from 300 kV/20 mA to 500 kV/mA has been carrying out. To improve the capacity of high voltage source was done by means of increasing the stage number of voltage multiplier from 11 to 18 and its output voltage measuring resistance. Each stage of voltage multiplier consists of 2 capacitors and 2 circuits of high voltage diode. This voltage multiplier is constructed using main components of high voltage capacitor and high voltage diode each of 0.22 μF/50 kV and UF 5408 respectively. To avoid stray discharge and corona it was provided with high voltage electrode and corona ring. The test result indicated that the output voltage obtained from 16 stages was 350 kV according to operating condition of 25 MΩ resistive load and first stage voltage of 28.5 kV with oscillator frequency of 24 Hz. That condition requires anode voltage and current of 5.5 kV and 2.5 A respectively. The no load test for 16 stages indicates 400 kV of output voltage and 28.5 kV first stage voltage. Efficiency of high voltage source was 48 % at 6.75 kW of output power. The expected test of 500 kV with 18 stages of voltage multiplier can not be carried out because of some restrictive of loading system. From the test result can be predicted that the output voltage of 500 kV with 18 stages of voltage multiplier requires 31.2 kV of first stage voltage. Then the expected high voltage source of Cockcroft-Walton is capable as accelerating voltage source for Electron Beam Machine with energy of 500 kV. (author)

  8. Impact of Considering 110 kV Grid Structures on the Congestion Management in the German Transmission Grid

    Science.gov (United States)

    Hoffrichter, André; Barrios, Hans; Massmann, Janek; Venkataramanachar, Bhavasagar; Schnettler, Armin

    2018-02-01

    The structural changes in the European energy system lead to an increase of renewable energy sources that are primarily connected to the distribution grid. Hence the stationary analysis of the transmission grid and the regionalization of generation capacities are strongly influenced by subordinate grid structures. To quantify the impact on the congestion management in the German transmission grid, a 110 kV grid model is derived using publicly available data delivered by Open Street Map and integrated into an existing model of the European transmission grid. Power flow and redispatch simulations are performed for three different regionalization methods and grid configurations. The results show a significant impact of the 110 kV system and prove an overestimation of power flows in the transmission grid when neglecting subordinate grids. Thus, the redispatch volume in Germany to dissolve bottlenecks in case of N-1 contingencies decreases by 38 % when considering the 110 kV grid.

  9. Functional properties of human neuronal Kv11 channels

    DEFF Research Database (Denmark)

    Einarsen, Karoline; Calloe, Kirstine; Grunnet, Morten

    2009-01-01

    Kv11 potassium channels are important for regulation of the membrane potential. Kv11.2 and Kv11.3 are primarily found in the nervous system, where they most likely are involved in the regulation of neuronal excitability. Two isoforms of human Kv11.2 have been published so far. Here, we present...... current characteristics of the isoforms presented in this work may contribute to the regulation of neuronal excitability....

  10. Overvoltages transferred from a network of 220 kV to 15.65 kV level of the step-up transformer in HPP 'Bajina Bašta'

    Directory of Open Access Journals (Sweden)

    Vukelja Petar

    2011-01-01

    Full Text Available The paper presents the results of research in lightning surge waves and switching overvoltages transferred from a network of 220 kV to the 15.65 kV level of the step-up transformer in HPP 'Bajina Bašta'. Analysis of survey results lead to conclusion that transferred overvoltages can endanger 15.65 kV transformer windings and stator winding insulation. It was therefore suggested for the protection of the 15.65 kV isolation to install metal oxide surge arresters at a suitable place between the power generator bus bars and earthing.

  11. System impact assessment report 115 kV interconnection between Cornwall system and Hydro One : final report

    International Nuclear Information System (INIS)

    2005-01-01

    Cornwall Electric (CE) is the local distribution company that serves the City of Cornwall, Ontario. The utility can be supplied from either Hydro Quebec, New York ISO or the IESO. CE has proposed to connect Rosemount, McConnell and Courtaulds substations to the IESO-controlled grid in order to obtain access to the competitively priced electricity in Ontario. The load connected to the 2 substations peaks in winter at about 100 MW. The 2 substations will be connected in stages. Only 40 MW of load from the Rosemount substation will be connected initially, followed by up to 100 MW from the McConnell and Courtaulds substation at a later date. The connection will be made through a circuit that taps into the St. Lawrence transmission station in Ontario. A new circuit will also be built and strung on existing towers. This document described the requirements for under-frequency load shedding; voltage reduction facilities; power factor; on-line monitoring; and system protections. According to data provided by Hydro One, the circuit is adequately rated to accommodate connection of the load from the Rosemount and McConnell and Courtaulds substations with no thermal overloading concerns. Winter load conditions were also considered. However, the IESO noted a potential reliability concern in the event that the Cardinal Power generating station is out of service and only one of the transformers connecting St. Lawrence 230 kV bus to St. Lawrence 115 kV bus is in service. However, the power transfers rated at 250 MVA are within the continuous rating of one transformer. It was concluded that the connection of the new load does not have an impact on the short circuit current at the St. Lawrence transmission station. The continuous thermal rating of the circuit is considered to be adequate for the proposed 100 MW of load transfer and the rating of the new line is sufficient to supply the total load at McConnell and Courtaulds. The ratings of the new disconnect switches meet market

  12. Needs and Possibility of Involving Nuclear Power Plant in the Macedonian Power System

    International Nuclear Information System (INIS)

    Bosevski, T.; Causevski, A.

    1998-01-01

    The Macedonian Power System (MPS) used to be a part of the former Yugoslav Power System, and it was connected to the European system by 400 kV transmission lines. At the present time, the MPS works isolated from the UCPTE, only connected to the Yugoslav and Greek power systems. The connections with the Bulgarian and Albanian power systems are on a lower voltage level. The reliability and stability of the MPS needs to be improved. Macedonia is located in the central area of the Balkan, where the transmission systems from other Balkan countries are crossing. in the near future, the Macedonian Power System needs to be linked to the European system. To prepare for the energy demand at the beginning of the 21-st century, when the local coal reserves get exhausted, Macedonia needs to start with activities for substitution of the existing coal-fired thermal power plants with nuclear plants. This paper discusses the activities for global development solutions in the area of power generation. (author)

  13. Low voltage 80 KV to 125 KV electron processors

    International Nuclear Information System (INIS)

    Lauppi, U.V.

    1999-01-01

    The classic electron beam technology made use of accelerating energies in the voltage range of 300 to 800 kV. The first EB processors - built for the curing of coatings - operated at 300 kV. The products to be treated were thicker than a simple layer of coating with thicknesses up to 100g and more. It was only in the beginning of the 1970's that industrial EB processors with accelerating voltages below 300 kV appeared on the market. Our company developed the first commercial electron accelerator without a beam scanner. The new EB machine featured a linear cathode, emitting a shower or 'curtain' of electrons over the full width of the product. These units were much smaller than anv previous EB processors and dedicated to the curing of coatings and other thin layers. ESI's first EB units operated with accelerating voltages between 150 and 200 kV. In 1993 ESI announced the introduction of a new generation of Electrocure. EB processors operating at 120 kV, and in 1998, at the RadTech North America '98 Conference in Chicago, the introduction of an 80 kV electron beam processor under the designation Microbeam LV

  14. 3.5 MeV pulsed power system for LIA injector

    International Nuclear Information System (INIS)

    Li Jin; Dai Guangsen; Liu Xiaoping; Zhang Kaizhi; Li Xin; Li Yuan; Xia Liansheng; Xie Min; Zhang Linwen; Deng Jianjun; Ding Bonan

    2005-01-01

    A 3.5 MeV injector for linear induction accelerator has been built up at Institute of Fluid Physics, China Academy of Engineering Physics. The injector is based on the principle of inductive adder. It consists of 12 induction cells. Seven induction cells are on the cathode stem side, which are connected in series, and provide about 2 MV on the cathode of the diode. The other five are connected in series on the anode stem side and provide about 1.5 MV on the anode of the diode. A 3.5 MV pulsed power system to provide energy for the injector has been designed, which consists of two Marx generators, 12 water insulated Blumleins, and trigger system. Charge voltage of each water insulated Blumlein is 200 kV. A 300 kV/90 ns high voltage pulse is fed into one induction cell since load impedance is higher. The pulsed power system can generate an intense electron beam with 2-3 kA. (authors)

  15. IOT based RF power systems as an alternative to klystron amplifier in Indus-2 at the rate 505.812 MHz

    International Nuclear Information System (INIS)

    Deo, R.K.; Jain, M.K.; Kumar, Gautam; Lad, Mahendra; Badapanda, M.K.; Bagre, Sunil; Upadhyay, Rinki; Tripathi, Akhilesh; Rao, J.N.; Pandiyar, Mohan; Hannurkar, P.R.

    2013-01-01

    Due to non-availability of replacement Klystron tube in Indus-2, an IOT based high power RF amplifier system is realized. It is based on E2V make 80 kW IOTD2130 tube with its circuit assembly IMD2000ST. This amplifier system is easily available commercially due to its application in DTV broadcast. It has inherent advantages over klystron amplifier viz. high efficiency (η), less phase and amplitude sensitivity to HV ripple, higher linearity, compactness and less cooling requirement. This high power IOT amplifier is tested with its required control system, cooling system, electron gun auxiliary supplies, beam supply and focusing supply. The nominal beam voltage for this IOT is -36 kV however amplifier was tested successfully with indigenously developed -32 kV, crowbar less power supply. The optimum load impedance for IOT beam was calculated for this bias voltage ( 32kV). For the required load impedance, coupling coefficient (β) of output coupler to the O/P cavity was estimated and accordingly loop angle was adjusted. The amplifier has been tested up to 50 kW with amplifier efficiency 60% and gain 23 dB at - 32 kV beam voltage. (author)

  16. Synchronized Phasor Measurements of a Power System Event in Eastern Denmark

    DEFF Research Database (Denmark)

    Rasmussen, Joana; Jørgensen, Preben

    2003-01-01

    . The outage of the 400-kV tie-line weakened the Eastern Danish power system and excited power oscillations in the interconnected power systems. During this event prototype Phasor Measurements Units (PMU) gave the opportunity of realtime monitoring of positive sequence voltage and current phasors using...... satellite-based Global Positioning System (GPS). Comparisons between real-time recordings and results from dynamic simulations with PSS/E are presented. The main features from the simulation analysis are successfully verified by means of the corresponding synchronized phasor measurements....

  17. Synchronized Phasor Measurements of a Power System Event in Eastern Denmark

    DEFF Research Database (Denmark)

    Rasmussen, Joana; Jørgensen, Preben

    2006-01-01

    . The outage of the 400-kV tie-line weakened the Eastern Danish power system and excited power oscillations in the interconnected power systems. During this event prototype Phasor Measurements Units (PMU) gave the opportunity of realtime monitoring of positive sequence voltage and current phasors using...... satellite-based Global Positioning System (GPS). Comparisons between real-time recordings and results from dynamic simulations with PSS/E are presented. The main features from the simulation analysis are successfully verified by means of the corresponding synchronized phasor measurements....

  18. The influence of the 220 kv and 66 kv power electric systems and the subsystem of their servitude range in the 'chaco central' ecosystem in Paraguay; Relacion de tendido electrico de 220 kV y 66kV en el ecosistema del chaco central del Paraguay y el subsistema de su franja de servidumbre

    Energy Technology Data Exchange (ETDEWEB)

    Acosta E, Hugo Cesar [ANDE - Administracion Nacional de Electricidad, Assuncion (Paraguay)

    2001-07-01

    According to the report from DOP/EL, in a medium period of time it has been registered nine disconnections of the 66 kv power transmission line located in the Chaco zone occurred in the nocturnal period. Those disconnections affected negatively the milky processes of Colinas Menonitas, deteriorating more than 20,000 liters of milk for each cut of the electric energy service. DMA/IM has accomplished a investigation job together with DOM/FO and has found the main reasons for those disconnections, so based on them it has recommended possible solutions related to the problem.

  19. The short-circuit test results of 6.9 kV/2.3 kV 400 kVA-class YBCO model transformer

    International Nuclear Information System (INIS)

    Tomioka, A.; Otonari, T.; Ogata, T.; Iwakuma, M.; Okamoto, H.; Hayashi, H.; Iijima, Y.; Saito, T.; Gosho, Y.; Tanabe, K.; Izumi, T.; Shiohara, Y.

    2011-01-01

    The 6.9 kV/2.3 kV 400 kVA-class single-phase YBCO model transformer with the YBCO tape with copper tape was manufactured for short-circuit current test. Short-circuit test was performed and the short-circuit current of primary winding was 346 A which was about six times larger than the rated current. The I-V characteristics of the winding did not change before and after the test. The transformer withstood short-circuit current. We are planning to turn the result into a consideration of a 66 kV/6.9 kV-20 MVA-class three-phase superconducting transformer. We are developing an elemental technology for 66 kV/6.9 kV 20 MVA-class power transformer with YBCO conductors. The protection of short-circuit technology is one of the elemental technologies for HTS transformer. Since short-circuit current is much higher than critical current of YBCO tape, there is a possibility that superconducting characteristics may be damaged during short-circuit period. We made a conductor to compose the YBCO tape with copper tape. We manufactured 6.9 kV/2.3 kV 400 kVA-class YBCO model transformer using this conductor and performed short-circuit current test. The short-circuit current of primary winding was 346 A which was about six times larger than the rated current. The I-V characteristics of the winding did not change before and after the test. We may consider this conductor withstands short-circuit current.

  20. Submicrosecond linear pulse transformer for 800 kV voltage with modular low-inductance primary power supply

    Energy Technology Data Exchange (ETDEWEB)

    Bykov, Yu. A.; Krastelev, E. G., E-mail: ekrastelev@yandex.ru; Popov, G. V.; Sedin, A. A.; Feduschak, V. F. [Russian Academy of Sciences, Joint Institute for High Temperatures (Russian Federation)

    2016-12-15

    A pulsed power source with voltage amplitude up to 800 kV for fast charging (350–400 ns) of the forming line of a high-current nanosecond accelerator is developed. The source includes capacitive energy storage and a linear pulse transformer. The linear transformer consists of a set of 20 inductors with circular ferromagnetic cores surrounded by primary windings inside of which a common stock adder of voltage with film-glycerol insulation is placed. The primary energy storage consists of ten modules, each of which is a low-inductance assembly of two capacitors with a capacitance of 0.35 μF and one gas switch mounted in the same frame. The total energy stored in capacitors is 5.5 kJ at the operating voltage of 40 kV. According to test results, the parameters of the equivalent circuit of the source are the following: shock capacitance = 17.5 nF, inductance = 2 μH, resistance = 3.2 Ω.

  1. Design of EAST LHCD high power supply feedback control system based on PLC

    International Nuclear Information System (INIS)

    Hu Huaichuan; Shan Jiafang

    2009-01-01

    Design of EAST LHCD -35kV/5.6MW high power supply feedback control system based on PLC is described. Industrial computer and PLC are used to control high power supply in the system. PID arithmetic is adopted to achieve the feedback control of voltage of high power supply. Operating system is base on real-time operating system of QNX. Good controlling properties and reliable protective properties of the feedback control system are proved by the experiment results. (authors)

  2. Sustaining neutral beam power supply system for the Mirror Fusion Test Facility

    International Nuclear Information System (INIS)

    Eckard, R.D.; Van Ness, H.W.

    1979-01-01

    A fixed-price procurement contract for $24.9 million was awarded to Aydin Energy Division, Palo Alto, CA, for the design, manufacture, installation, and acceptance testing of the sustaining neutral beam power supply system (SNBPSS). This system is scheduled for completion in early 1981 and will provide the conditioned power for the 24 neutral beam source modules. Each of the 24 power supply sets will provide the accel potential of 80 kV at 88 A, the arc power, the filament power, and the suppressor power for its associated neutral beam source module

  3. Construction of a 500 kV aerial power line in East Java

    Energy Technology Data Exchange (ETDEWEB)

    Kaeufl, O; Paschen, R; Kummermehr, R

    1987-10-12

    The authors report on the technical preparations and the construction of a 500 kv, four-bundle power line with a pylon tonnage of approximately 10,000 t of steel and a route length of 251 km in Indonesia. Due to the difficult terrain conditions, the sensitive infrastructure and the extremely short construction period, this project was a special technological challenge. Initially, the authors explain the technical planning of Brown Boveri with emphasis on foundations and assembly. As part of this tailor-made concept new technological solutions were used. They were instrumental in the successful completion of the project in only 19 months by the end of 1986 to the complete satisfaction of the customer. The authors also comment on the pracitcal experiences gained during the construction.

  4. 735 kV air-blast circuit breakers for Hydro Quebec

    Energy Technology Data Exchange (ETDEWEB)

    Lindstrom, I

    1966-01-01

    In 1962 the Quebec Hydro-Electric Commission started the development of aproject for utilizing water power in Manicouagan and Outardes, two rivers some 350 miles northeast of the city of Montreal on the left bank of the St. Lawrence estuary. The project involved the transmission of power at 735 kV ac from Manicouagan and Outardes to the heavy and growing load centers of Quebec and Montreal. The total amount of energy to be transmitted in the final stage is about 6,000 MW. The project involved the need of considerable quantities of apparatus for 735 kV, such as transformers, reactors, lightning arrestors, circuit-breakers, and disconnectors. Since the supply of the major part of the 735 kV circuit-breakers, altogether 14 three-pole units, was awarded to ASEA in Sweden, a short presentation of these airblast circuit-breakers is presented.

  5. DC in urban areas distribution power systems and microgrids; Tasajaennite taajaman saehkoenjakelussa ja mikroverkoissa

    Energy Technology Data Exchange (ETDEWEB)

    Kylkisalo, T.; Alanen, R.

    2007-09-15

    This study deals with the utilization of DC distribution power systems and energy storages in urban areas. The properties and the components, that make the DC distribution power systems possible, are specifically examined from the perspective of the power system's control topology. The role of the energy storages as a part of the DC distribution power system and a tool of power quality control was also discussed. Using PSCAD/EMTDC simulation program two different concepts of the DC distribution power systems were simulated. Both low and medium voltage networks were designed as microgrids, which were capable operation without medium voltage feeder from the outside network as the entity of energy storages, auxiliary power source and loads. It emerged from the simulation that DC distribution power systems are capable to provide an uninterruptible delivery of current. In addition the effects on energy management of the DC distribution power systems, which include energy storages, were studied. Also a hierarchical principle was brought out, which could make an efficient interaction between electricity market and distributed power systems. Economical studies of the simplified 10 kV distribution system were done and the costs of AC and DC networks were compared. At 10 kV level AC system was found to be more economically efficient but DC network is more energy efficient because of remarkable smaller losses. Based on this study it can be said, that if the investment costs of the DC power systems can be reduced it could be a strong competitor to conventional AC power systems. (orig.)

  6. Estimation of expected short-circuit current levels in and circuit-breaker requirements for the 330 to 750 kV networks of the southern integrated power grid

    Energy Technology Data Exchange (ETDEWEB)

    Krivushkin, L.F.; Gorazeeva, T.F.

    1978-08-01

    Studies were made in order to project the operating levels in the Southern Integrated Power Grid to the year 2000. The short-circuit current levels and, the requirements which circuit breakers will have to meet are estimated. A gradual transition from 330 to 750 kV generation is foreseen, with 330 kV networks remaining only for a purely distribution service. The number of 330 kV line hookups and the number of circuit breakers at nodal points (stations and substations) will not change significantly, they will account for 40% of all circuit breakers installed in 25% of all nodal points. Short-circuit currents are expected to reach the 46 kA level in 750 kV networks and 63 kA (standing wave voltage 1.5 to 2.5 kV/microsecond) in 330 kV networks. These are the ratings of circuit breakers; of the 63 kA ones 150 will be needed by 1980--1990 and 400 by 1990--2000. It will also be eventually worthwhile to install circuit breakers with a 63 kA-750 kV rating.

  7. Neutral Beam Power System for TPX

    International Nuclear Information System (INIS)

    Ramakrishnan, S.; Bowen, O.N.; O'Conner, T.; Edwards, J.; Fromm, N.; Hatcher, R.; Newman, R.; Rossi, G.; Stevenson, T.; von Halle, A.

    1993-01-01

    The Tokamak Physics Experiment (TPX) will utilize to the maximum extent the existing Tokamak Fusion Test Reactor (TFTR) equipment and facilities. This is particularly true for the TFTR Neutral Beam (NB) system. Most of the NB hardware, plant facilities, auxiliary sub-systems, power systems, service infrastructure, and control systems can be used as is. The major changes in the NB hardware are driven by the new operating duty cycle. The TFTR Neutral Beam was designed for operation of the Sources for 2 seconds every 150 seconds. The TPX requires operation for 1000 seconds every 4500 seconds. During the Conceptual Design Phase of TPX every component of the TFTR NB Electrical Power System was analyzed to verify whether the equipment can meet the new operational requirements with our without modifications. The Power System converts 13.8 kV prime power to controlled pulsed power required at the NB sources. The major equipment involved are circuit breakers, auto and rectifier transformers surge suppression components, power tetrodes, HV Decks, and HVDC power transmission to sources. Thermal models were developed for the power transformers to simulate the new operational requirements. Heat runs were conducted for the power tetrodes to verify capability. Other components were analyzed to verify their thermal limitations. This paper describes the details of the evaluation and redesign of the electrical power system components to meet the TPX operational requirements

  8. Reactive power balance in a distribution network with wind farms and CHPS

    DEFF Research Database (Denmark)

    Lund, Torsten; Nielsen, John Eli; Hylle, Per

    2007-01-01

    In Denmark, a large part of the electricity is generated by wind turbines and combined heat and power plants. Most of them are connected to the distribution systems. In periods with high wind speeds, large flows of reactive power have been observed between the 150kV and the 60 kV systems. The tra......In Denmark, a large part of the electricity is generated by wind turbines and combined heat and power plants. Most of them are connected to the distribution systems. In periods with high wind speeds, large flows of reactive power have been observed between the 150kV and the 60 kV systems....... The transfer of reactive power reduces the capacity of the lines, causes thermal losses and can in some cases reduce the voltage stability margin of the system. To identify the origin of the problem, an actual distribution system with a high penetration of wind power and distributed generation has been...

  9. Simulation of interaction between wind farm and power system

    DEFF Research Database (Denmark)

    Sørensen, Poul Ejnar; Hansen, Anca Daniela; Janosi, L.

    2002-01-01

    A dynamic model of the wind farm Hagesholm has been implemented in the dedicated power system simulation program DIgSILENT. The wind farm con- sists of six 2MW NM2000/72 wind turbines from NEG-Micon. The model has been verified using simultaneous powerquality measurements on the 10 kV terminals...

  10. Beam Profile Measurement of 300 kV Ion Source Test Stand for 1 MV Electrostatic Accelerator

    International Nuclear Information System (INIS)

    Park, Sae-Hoon; Kim, Yu-Seok; Kim, Dae-Il; Kwon, Hyeok-Jung; Cho, Yong-Sub

    2015-01-01

    In this paper, RF ion source, test stand of the ion source and its test results are presented. Beam profile was measured at the downstream from the accelerating tube and at the beam dump by using BPM and wire scanner. The RF ion source of the test stand is verified by measuring the total beam current with a faraday cup in the chamber. The KOMAC (KOrea Multi-purpose Accelerator Complex) has been developing a 300 kV ion source test stand for a 1 MV electrostatic accelerator. An ion source and accelerating tube will be installed in a high pressure vessel. The ion source in a high pressure vessel requires high reliability. To confirm the stable operation of the ion source, a test stand was proposed and developed. The ion source will be tested at the test stand to verify its long-term operation conditions. The test stand consists of a 300 kV high voltage terminal, a battery for the ion source power, a 60 Hz inverter, a 200 MHz RF power, a 5 kV extraction power supply, a 300 kV accelerating tube, and a vacuum system. The beam profile monitor was installed at the downstream from the accelerating tube. Wire scanner and faraday-cup was installed at the end of the chamber

  11. Beam Profile Measurement of 300 kV Ion Source Test Stand for 1 MV Electrostatic Accelerator

    Energy Technology Data Exchange (ETDEWEB)

    Park, Sae-Hoon; Kim, Yu-Seok [Dongguk University, Gyeonju (Korea, Republic of); Kim, Dae-Il; Kwon, Hyeok-Jung; Cho, Yong-Sub [Korea Multipurpose Accelerator Complex, Gyeongju (Korea, Republic of)

    2015-10-15

    In this paper, RF ion source, test stand of the ion source and its test results are presented. Beam profile was measured at the downstream from the accelerating tube and at the beam dump by using BPM and wire scanner. The RF ion source of the test stand is verified by measuring the total beam current with a faraday cup in the chamber. The KOMAC (KOrea Multi-purpose Accelerator Complex) has been developing a 300 kV ion source test stand for a 1 MV electrostatic accelerator. An ion source and accelerating tube will be installed in a high pressure vessel. The ion source in a high pressure vessel requires high reliability. To confirm the stable operation of the ion source, a test stand was proposed and developed. The ion source will be tested at the test stand to verify its long-term operation conditions. The test stand consists of a 300 kV high voltage terminal, a battery for the ion source power, a 60 Hz inverter, a 200 MHz RF power, a 5 kV extraction power supply, a 300 kV accelerating tube, and a vacuum system. The beam profile monitor was installed at the downstream from the accelerating tube. Wire scanner and faraday-cup was installed at the end of the chamber.

  12. Effects of electromagnetic field of 33 and 275 kV influences on ...

    African Journals Online (AJOL)

    The effects of electromagnetic fields (EMF) from 33 and 275 kV high voltage transmission line on biochemical and antioxidant system changes in mustard leaf (Brassica chinensis) were investigated under field condition. Mustard leaves were exposed to EMF from power lines at distances of 0, 3, 6, 9, 10, 12, 15, 18, 20, 21, ...

  13. Loss Characteristics of 6.5 kV RC-IGBT Applied to a Traction Converter

    Directory of Open Access Journals (Sweden)

    Xianjin Huang

    2017-07-01

    Full Text Available 6.5 kV level IGBT (Insulated Gate Bipolar Transistor modules are widely applied in megawatt locomotive (MCUs traction converters, to achieve an upper 3.5 kV DC link, which is beneficial for decreasing power losses and increasing the power density. Reverse Conducting IGBT (RC-IGBT constructs the conventional IGBT function and freewheel diode function in a single chip, which has a greater flow ability in the same package volume. In the same cooling conditions, RC-IGBT allows for a higher operating temperature. In this paper, a mathematic model is developed, referring to the datasheets and measurement data, to study the 6.5 kV/1000 A RC-IGBT switching features. The relationship among the gate desaturated pulse, conducting losses, and recovery losses is discussed. Simulations and tests were carried out to consider the influence of total losses on the different amplitudes and durations of the desaturated pulse. The RC-IGBT traction converter system with gate pulse desaturated control is built, and the simulation and measurements show that the total losses of RC-IGBT with desaturated control decreased comparing to the RC-IGBT without desaturated control or conventional IGBT. Finally, a proportional small power platform is developed, and the test results prove the correction of the theory analysis.

  14. Do kV really make everything look grey? A comparative study of 600 kV computed tomography systems; Macht kV wirklich grau? Eine Vergleichsstudie zu 600 kV Computertomografiesystemen

    Energy Technology Data Exchange (ETDEWEB)

    Krumm, Michael; Sauerwein, Christoph; Haemmerle, Volker; Knupe, Gunnar [RayScan Technologies GmbH, Meersburg (Germany)

    2013-07-01

    In the automotive industry there is a manufacture of cast aluminium parts of considerable thickness. Growing importance is being attached to methods of nondestructive testing and full metrological characterisation of these parts. A major contribution to this end has been made by the latest generation of CT systems, whose 600 kV X-ray tubes and line detectors make for excellent image quality. The purpose of the present study was to make an objective assessment of the performance of these CT systems by examining the advantages and drawbacks of each. This included comparisons of various parameters such as tube voltage and exposure time as well as different tube and detector technologies and CT measurement methods.

  15. Crosstalk measurement on the D-III neutral beam power supplies

    International Nuclear Information System (INIS)

    Nerm, A.; Bowles, E.; Callis, R.W.; Colleraine, A.; Cowels, G.; Finizio, R.; Moore, D.; Tooker, J.F.; Varga, H.

    1983-01-01

    The Doublet III neutral beam plasma heating system comprises three beamlines with a total of six ion sources. Each of these ion sources is energized from a Neutral Beam Power System (NBPS) which is capable of delivering pulses at 80 kV and 100 A with pulse lengths up to 1 second in duration. A 138 kV San Diego Gas and Electric Company line is used as the prime power source for the NBPS. The 138 kV line is stepped down through an 84 MVA (pulse rating) 138 kV-12.47 kV transformer and an 8 MVA (pulse rating) 138 kV--480 V transformer. The 12.47 kV transformer feeds six NBPS high voltage circuits. The 480 V transformer supplies power to the filament, arc, and auxiliary power systems and control consoles in each NBPS. Each of the NBPS may block (controlled interruption of NBPS to protect the ion source) several times during a shot. Voltage variations due to such blocking by one or more systems have been measured on the 12.47 kV distribution bus as part of an effort to reduce system interaction. Interaction due to blocking during shots was found to be caused by noise picked up in low level circuits during ion source faults. High voltage DC fluctuations due to blocking do not cause interaction unless the voltage sags below the minimum required anode voltage for the pulse tetrodes in the Modular/Regulator, but interaction due to crowbar of the high voltage DC supply by a NBPS may result in a domino effect unless the remaining online systems are caused to block until the crowbarred system is cleared from the line (This feature is not presently implemented.). Voltage sag on the 480 V bus results from simultaneous operation of the ion sources. This sag, when it occurs, may lower the arc power input to the ion sources and cause reduced output power

  16. Research on data integration of Anshan 10 kV power distribution network system

    Energy Technology Data Exchange (ETDEWEB)

    Jiang, T.; Dang, N.; Liu, Y. [North China Electric Power Univ., Beijing (China); Wang, Z. [Anshan Electric Co. Ltd., Anshan City (China)

    2009-03-11

    Variations in data formats among electric power supervisory control systems are preventing the development of an integrated power distribution database. The use of standard XML protocols make web-based services platform and language independent, as they are based on open standards that allow software to communicate in a standardizing XML messaging system. This article discussed the use of web-based services as a safe interface for accessing distribution system databases. Web services technology was used to pass through the firewall of individual data servers while avoiding direct contact with the actual database and ensuring the security of the data server. A virtual machine technology was then applied in a testing environment to demonstrate the method. The test results confirmed that the method can be used to integrate data from various power systems. 8 refs., 5 figs.

  17. STUDY ON PERFORMANCE OF 21M 132kV TRANSMISSION TOWER WITH MEDIUM WIND INTENSITY

    OpenAIRE

    V. LAKSHMI; A. RAJAGOPALA RAO

    2012-01-01

    Electric Power is today playing an increasingly important role in the life of the community. In the electric power system the production and transmission of power are two predominant factors. For the purpose of transmission of electricity towers are the main medium with some wires at required distances and altitudes. The remotehydroelectric power plants have given rise to the need for extra high voltage. Prior to 1950, 150 kV electric transmission lines were considered and still higher voltag...

  18. Power-supply system for high-voltage electron guns with grid control

    International Nuclear Information System (INIS)

    Grigorev, Y.V.

    1985-01-01

    A power-supply system for electron guns with grid control is described which consists of a source of accelerating voltage between 20 and 180 kV with a current of 100 mA and a control circuit for an electron gun that contains a pulse generator having an output voltage of up to 5 kV for pulse durations of 2, 10, 50 and 90 microseconds. The output pulses of the generator are synchronized with a certain phase of the cathode heater current of the gun, and they can be repeated at a frequency between 100 and 0.4 Hz. The system is reliable and resistant to the overloads associated with breakdowns in the gun

  19. Charging system of ECRH high-voltage power supply and its control system

    International Nuclear Information System (INIS)

    Hu Guofu; Ding Tonghai; Liu Baohua; Jiang Shufang

    2003-01-01

    High-voltage power supply (HVPS) of Electron Cyclotron Resonance Heating (ECRH) for HT-7 and HT-7U is presently being constructed. The high voltage (100 kV) energy of HVPS is stored in the capacitor banks, and they can power one or two gyrotrons. All the operation of the charging system will be done by the control system, where the field signals are interfaced to programmable logic controller (PLC). The use of PLC not only simplifies the control system, but also enhances the reliability. The software written by using configuration software installed in the master computer allows for remote and multiple operator control, and the status and data information is also remotely available

  20. Analisis Pembebanan Ekonomis pada Jaringan 500 kV Jawa Bali Menggunakan Software PowerWorld

    Directory of Open Access Journals (Sweden)

    Badru Tamam Arozaq

    2012-09-01

    Full Text Available Pada jaringan 500 kV Jawa Bali, PT. PLN (Persero P3B menentukan kombinasi pembangkit yang akan beroperasi pada setiap level beban tertentu. Oleh karena itu, Economic Dispatch (ED atau pembagian pembebanan secara ekonomis dilakukan untuk menghasilkan pembebanan pembangkit yang optimal. Namun, hasil dari Economic Dispatch tersebut belum tentu dapat memenuhi batasan sistem seperti batasan pembakitan generator dan batasan saluran. Untuk itu, Optimal Power Flow (OPF perlu dilakukan dalam rangka pembagian pembebanan secara ekonomis, sekaligus memenuhi batasan-batasan sistem. Pada tugas akhir ini, perhitungan pembagian pembebanan pembangkit dilakukan dengan menggunakan software PowerWorld. Software ini memiliki keunggulan dalam teknik analisis, interaktif, dan disertai dengan grafik, sehingga mempermudah pembaca dalam memahami informasi yang diberikan. Dari hasil pengujian, terbukti bahwa pada keadaan normal ED dan OPF dalam penggunaan software PowerWorld, menghasilkan nilai yang sama yaitu sebesar 662.264,94 $/h. Tetapi pada saat terjadi pelanggaran batas saluran transmisi, hasil simulasi ED lebih murah yaitu sebesar 665.834,06 $/h sedangkan hasil OPF sebesar 863.630,50 $/h.

  1. Optimizing the switching time for 400 kV SF6 circuit breakers

    Science.gov (United States)

    Ciulica, D.

    2018-01-01

    This paper presents real-time voltage and current analysis for optimizing the wave switching point of the circuit breaker SF6. Circuit Breaker plays an important role in power systems. It provides protection for equipment in embedded stations in transport networks. SF6 Circuit Breaker is very important equipment in Power Systems, which is used for up to 400 kV due to its excellent performance. The controlled switching is used to eliminate transient modes and electrodynamic and dielectric charges in the network at manual switching of capacitor, shunt reactors and power transformers. These effects reduce the reliability and lifetime of the equipment installed on the network, or may lead to erroneous protection.

  2. Magnet power system for the Microwave Tokamak Experiment (MTX)

    International Nuclear Information System (INIS)

    Jackson, M.C.; Musslewhite, R.C.

    1987-01-01

    The system configuration, layout, and general philosophy for the MTX magnet power system is described. The vast majority of the magnet power equipment was quite successfully used on the ALCATOR-C experiment at the Massachusetts Institute of Technology. The AC power for the magnet system at MIT was obtained from a 225MVA alternator. The power for the system at LLNL is obtained directly from the local utility's 230 kV line. This installation, therefore, necessitates the addition of a great deal of equipment in ranges from new switchgear in the substation to using existing switchgear obtained from MIT as contractors for intershop electrical isolation as well as safety isolation for personnel entry into the experimental area. Additionally, some discussion is made of the unique layout of this facility and the tradeoffs made to accommodate them. 2 refs., 6 figs

  3. Development of a 300-kV Marx generator and its application to drive ...

    Indian Academy of Sciences (India)

    Accelerator and Pulse Power Division, Bhabha Atomic Research Centre, ... anode gap of 7·5 mm, an REB having beam voltage 160 kV and duration 150 ns ... lowest stage has a triggered SG which is closed by a 6 kV pulse obtained with the ...

  4. Inductive-pulsed power supplying system for a betatron electromagnet

    International Nuclear Information System (INIS)

    Otrubyannikov, Yu.A.; Safronov, A.S.

    1984-01-01

    Circuit of producing quasitriangular current pulses designed for the pulsed power supply system of betatron electromagnet is described. Introduction of additional winding into electromagnet provides circuit galvanic isolation, artificial commutation of basic circuit thyristors and inductive power input to the winding during thyristor commutation. The considered system is used for excitation of betatron electromagnet up to 18 MeV. Magnetic field energy equals 1100 Y. The maximal voltage in energy storage capacitor - 4.8 kV. Current amplitude in basic winding - 335 A. The number of loops in basic winding equals 80, in additional one - 32. Current pulse duration in electromagnet-3.8 ms. The system provides operation with controlled current pulse frequency from 0 up to 150 Hz. The maximal consumption power - 18 kW

  5. METHODICAL APPROACHES TO THE CHOICE OF THE NEW GENERATION OF HIGH-VOLTAGE POWER TRANSMISSION LINE 220 kV OPTIONS

    Directory of Open Access Journals (Sweden)

    POSTOLATI V.M.

    2010-08-01

    Full Text Available The Transmission Power Lines of new generation are described in the article (single- compact, double-circuit compact, double-circuit Controlled Self-compensating High Voltage Transmission Power Lines (CSHVL. Basic principles of creation, design elements and comparative characteristics of the transmission lines of the new generation are described, the advantages of its are showed. Methodical approaches to the choosing of a new generation of transmission lines and facilities management FACTS are formulated. Methodical approaches to the choice of options for transmission lines 220 kV and facilities management are shown.

  6. Electrical system design status of PEFP

    Energy Technology Data Exchange (ETDEWEB)

    Song, In Taek; Mun, Kyeong Jun; Kim, Jun Yeon [KAERI, Daejeon (Korea, Republic of)

    2012-10-15

    Proton Engineering Frontier Project (PEFP) has been developing a 100 MeV proton linear accelerator. Also, PEFP has been designing the Proton Accelerator Research Center in Gyeongju. In site, we installed GIS (Gas Insulated Switchgear) to receive 154kV electric power and 154kV/3.3kV transformer. For the energy saving scheme, we are now installing solar power system, automatic lighting control system and maximum control power system of PEFP. In this paper, we described electrical power system of PEFP.

  7. Test results of full-scale high temperature superconductors cable models destined for a 36 kV, 2 kA(rms) utility demonstration

    DEFF Research Database (Denmark)

    Daumling, M.; Rasmussen, C.N.; Hansen, F.

    2001-01-01

    Power cable systems using high temperature superconductors (HTS) are nearing technical feasibility. This presentation summarises the advancements and status of a project aimed at demonstrating a 36 kV, 2 kA(rms) AC cable system by installing a 30 m long full-scale functional model in a power...

  8. Development of the power system for accelerator

    International Nuclear Information System (INIS)

    Kwon, Hyeokjung; Kim, D. I.; Kim, H. S.; Park, B. S.; Seol, K. T.; Yun, S. P.; Song, Y. G.; Jang, J. H.; Cho, Y. S.

    2013-02-01

    The 100-MeV proton linac needs 4 modulators whose specification is as follows, -115kV, 55A, and 9%. The development of the modulators were successfully finished and installed at Gyeongju site of KAERI. One of them was used and successfully tested in the 20-MeV linac operation at Daejeon site. The klystron is used to supply the high power RF into the accelerating structure. There are 2 klystrons for 20-MeV part of the linac and 7 klystrons from 20-MeV to 100-MeV region. The maximum voltage is ?105kV, the peak power is 1.6 MW, and the duty is 9%. All of the 7 klystrons have been fabricated, tested and installed. The high power RF system includes circulators, dummy lodes, RF windows, and wave-guides. The development of the high power RF components was finished and they were installed at the Gyeongju site. The 11 sets of RCCS (resonant control cooling system) will be used to control the cooling water temperature inside the accelerating structure. The temperature range of the cooling water covers between 21 .deg. C and 33 .deg. C with the 0.1 .deg. C control. All RCCSs were installed in the klystron gallery. Purposes of the 20-MeV linac operation at Daejeon site of KAERI (2007∼2011) are to supply proton beams to user, to porve the accelerator performance, to test the developed components including LLRF, diagnostics, and control system, and to measure the proton beam properties. During the period, the total number of samples reaches to 1,603 and the average machine availability becomes 96.2%. The 20-MeV linac was disassembled, moved and installed at Gyeongju site after finishing the test operation

  9. Dynamic Performance of the ITER Reactive Power Compensation System

    International Nuclear Information System (INIS)

    Sheng Zhicai; Fu Peng; Xu Liuwei

    2011-01-01

    Dynamic performance of a reactive power compensation (RPC) system for the international thermonuclear experimental reactor (ITER) power supply is presented. Static var compensators (SVCs) are adopted to mitigate voltage fluctuation and reduce the reactive power down to a level acceptable for the French/European 400 kV grid. A voltage feedback and load power feedforward controller for SVC is proposed, with the feedforward loop intended to guarantee short response time and the feedback loop ensuring good dynamics and steady characteristics of SVC. A mean filter was chosen to measure the control signals to improve the dynamic response. The dynamic performance of the SVC is verified by simulations using PSCAD/EMTDC codes.

  10. Modification of 300kV RF Ion Source for 1-MV Electrostatic Accelerator at KOMAC

    Energy Technology Data Exchange (ETDEWEB)

    Kim, Dae-Il; Kwon, Hyeok-Jung; Park, Sae-Hoon; Cho, Yong-Sub [KOMAC, Gyeongju (Korea, Republic of)

    2015-05-15

    The specifications of the 1-MV electrostatic accelerator are shown as below. High voltage power supply is electron transformer rectifier (ELV) type which was developed in Nuclear Physics Institute (Novosibirsk) for industrial electron accelerators. And accelerator column consists of alumina and metal electrode rings were 0.5m-long brazed structure which can be installed horizontally. In case of ion source for 1-MV electrostatic accelerator, it is chosen a thonemann type rf ion source and 300-kV test-stand was made up to confirm the stable operating conditions. High voltage power supply is fabricated by domestic company, and its operation has been confirming at KOMAC site. Equally, the ion source of 300-kV test-stand should be modified to install into the high voltage power supply. In this paper, modification of ion source of 300-kV test-stand for 1-MV electrostatic accelerator is presented and its processes are considered. 300-kV RF ion source and power supply are testing for the 1-MV electrostatic accelerator and trying for combination between them. The 1-MV electrostatic accelerator will be fabricated with domestic companies and tested in the beam application research building at KOMAC.

  11. Modification of 300kV RF Ion Source for 1-MV Electrostatic Accelerator at KOMAC

    International Nuclear Information System (INIS)

    Kim, Dae-Il; Kwon, Hyeok-Jung; Park, Sae-Hoon; Cho, Yong-Sub

    2015-01-01

    The specifications of the 1-MV electrostatic accelerator are shown as below. High voltage power supply is electron transformer rectifier (ELV) type which was developed in Nuclear Physics Institute (Novosibirsk) for industrial electron accelerators. And accelerator column consists of alumina and metal electrode rings were 0.5m-long brazed structure which can be installed horizontally. In case of ion source for 1-MV electrostatic accelerator, it is chosen a thonemann type rf ion source and 300-kV test-stand was made up to confirm the stable operating conditions. High voltage power supply is fabricated by domestic company, and its operation has been confirming at KOMAC site. Equally, the ion source of 300-kV test-stand should be modified to install into the high voltage power supply. In this paper, modification of ion source of 300-kV test-stand for 1-MV electrostatic accelerator is presented and its processes are considered. 300-kV RF ion source and power supply are testing for the 1-MV electrostatic accelerator and trying for combination between them. The 1-MV electrostatic accelerator will be fabricated with domestic companies and tested in the beam application research building at KOMAC

  12. Circuit protection of ehv power systems from 150 to 765 kV

    Energy Technology Data Exchange (ETDEWEB)

    Geise, F; Jaeger, J

    1965-11-01

    Short tripping times required for all faults in ehv transmission systems are obtained by means of differential and comparative protection arrangements. It is essential that protection and communication systems be closely integrated and that special current transformers with linearized cores supply protective devices with correct measured values. By arranging filters between transformer and directional relay, it is possible to use capacitive voltage transformers for high speed protection. A description of power system with backup protection devices is presented.

  13. Aberration-corrected STEM/TEM imaging at 15 kV

    International Nuclear Information System (INIS)

    Sasaki, Takeo; Sawada, Hidetaka; Hosokawa, Fumio; Sato, Yuta; Suenaga, Kazu

    2014-01-01

    The performance of aberration-corrected (scanning) transmission electron microscopy (S/TEM) at an accelerating voltage of 15 kV was evaluated in a low-voltage microscope equipped with a cold-field emission gun and a higher-order aberration corrector. Aberrations up to the fifth order were corrected by the aberration measurement and auto-correction system using the diffractogram tableau method in TEM and Ronchigram analysis in STEM. TEM observation of nanometer-sized particles demonstrated that aberrations up to an angle of 50 mrad were compensated. A TEM image of Si[110] exhibited lattice fringes with a spacing of 0.192 nm, and the power spectrum of the image showed spots corresponding to distances of 0.111 nm. An annular dark-field STEM image of Si[110] showed lattice fringes of (111) and (22¯0) planes corresponding to lattice distances of 0.314 nm and 0.192 nm, respectively. At an accelerating voltage of 15 kV, the developed low-voltage microscope achieved atomic-resolution imaging with a small chromatic aberration and a large uniform phase. - Highlights: • Aberration-corrected STEM/TEM imaging at 15 kV demonstrated lattice fringes of Si[110] single crystal with a spacing of 0.192 nm. • To achieve this performance at a lower accelerating voltage, uniform phase area over 50 mrad is mandatory in Ronchigram and Diffractogram tableau. • This means a higher-order aberration of six-fold astigmatism should be compensated. • In addition, decreasing the effect of chromatic aberration plays an important role for improving the performance of linear scattering component at 15 kV TEM

  14. The short-circuit test results of 6.9 kV/2.3 kV 400 kVA-class YBCO model transformer with fault current limiting function

    International Nuclear Information System (INIS)

    Tomioka, A.; Bohno, T.; Kakami, S.; Isozaki, M.; Watanabe, K.; Toyama, K.; Sugiyama, S.; Konno, M.; Gosho, Y.; Okamoto, H.; Hayashi, H.; Tsutsumi, T.; Iwakuma, M.; Saito, T.; Tanabe, K.; Shiohara, Y.

    2013-01-01

    Highlights: ► We manufactured the 400 kV A-class YBCO model transformer with FCL function. ► Short-circuit test was performed by applying 6.9 kV on primary side. ► The short-circuit current was limited to 174 A for a prospective current of 559 A. ► It agreed with the design and we also confirmed the I c did not degrade. ► The results suggest the possibility to design YBCO transformers with FCL function. -- Abstract: We are developing an elemental technology for 66/6.9 kV 20 MVA-class superconducting power transformer with fault current limiting function. In order to obtain the characteristics of YBCO conductor when the AC over current supplied to the conductor, the model coils were manufactured with YBCO tapes and tested. Based on these results, we manufactured the 6.9 kV/2.3 kV 400 kVA-class YBCO model transformer with fault current limiting function and performed short-circuit test. At the 0.25 s after short-circuit, the short-circuit current of primary winding was limited to about 174 A for a prospective current of 559 A. It was consistent with the design. The I–V characteristics of the winding did not change before and after the test. We consider the model transformer to be able to withstand AC over-current with the function of current limiting. The results suggest the possibility to design YBCO superconducting transformers with fault current limiting function for practical power grid

  15. Upgrade of a 30 kV/10 mA anode power supply for triode type gyrotron

    Energy Technology Data Exchange (ETDEWEB)

    Siravo, Ugo, E-mail: ugo.siravo@epfl.ch; Alberti, Stefano; Dubray, Jérémie; Fasel, Damien; Hogge, Jean-Philippe; Marlétaz, Blaise; Marmillod, Philippe; Perez, Albert; Silva, Miguel

    2015-10-15

    Highlights: • Triode type gyrotron is fed by 3 power supplies: the main, an anode PS(APS) and a heater. • This paper presents the upgrade of 3APS, supplied in 1999, that never fulfilled the specs. • The new working principle is very efficient, easy to implement, for a minimal cost. • Upgraded APS provides extended modulation capabilities, no overshoot and lowerripple. • This upgrade will allow exploring new operation regimes for the 3 TCV X3 gyrotrons. - The RF power of a gyrotron with a triode type magnetron-injection-gun (MIG) can be directly controlled via the voltage applied between its anode and its cathode. Hence, the performance of this type of gyrotron relies directly on the possibilities offered by the power supply controlling the anode to cathode voltage. For a system of gyrotrons connected to the same main high-voltage power supply, with a triode MIG one has the additional advantage of independently controlling each individual gyrotron. This paper presents the modifications brought to the three existing 30 kV/10 mA anode power supplies connected to the 500 kW/118 GHz/2s X3 gyrotrons operated on the TCV Tokamak. The new working principle based on phase-shift modulation (PSM) is described in detail. Experimental results obtained on dummy load are compared to simulations performed during the design phase. With respect to the initial working principle, the modulation frequency capability has been increased by a factor 10 reaching more than 5 kHz, whereas the output voltage ripple as well as the overshoot/undershoot have been significantly reduced.

  16. 10kV SiC MOSFET split output power module

    DEFF Research Database (Denmark)

    Beczkowski, Szymon; Li, Helong; Uhrenfeldt, Christian

    2015-01-01

    The poor body diode performance of the first generation of 10kV SiC MOSFETs and the parasitic turn-on phenomenon limit the performance of SiC based converters. Both these problems can potentially be mitigated using a split output topology. In this paper we present a comparison between a classical...

  17. High Voltage AC underground cable systems for power transmission

    DEFF Research Database (Denmark)

    Bak, Claus Leth; Silva, Filipe Miguel Faria da

    2016-01-01

    researching electrical engineering topics related to using underground cables for power transmission at EHV level and including the 420 kV level. The research topics were laid down by ET/AAU and Energinet.dk in the DANPAC (DANish Power systems with AC Cables) research project. The main topics are discussed...... on the basis of 39 references published by ET/AAU and Energinet.dk. Part I of the paper explains the events that lead to the research project, reactive power compensation, modelling for transient studies, including field measurements and improvements to the existing models, and temporary overvoltages due...... to resonances. Part II covers transient phenomena, harmonics in cables, system modelling for different phenomena, main and backup protections in cable-based networks, online fault detection and future trends....

  18. High Voltage AC underground cable systems for power transmission

    DEFF Research Database (Denmark)

    Bak, Claus Leth; Silva, Filipe Miguel Faria da

    2016-01-01

    researching electrical engineering topics related to using underground cables for power transmission at EHV level and including the 420 kV level. The research topics were laid down by ET/AAU and Energinet.dk in the DANPAC (DANish Power systems with Ac Cables) research project. The main topics are discussed...... on the basis of 39 references published by ET/AAU and Energinet.dk. Part I of the paper explains the events that lead to the research project, reactive power compensation, modelling for transient studies, including field measurements and improvements to the existing models, and temporary overvoltages due...... to resonances. Part II covers transient phenomena, harmonics in cables, system modelling for different phenomena, main and backup protections in cable-based networks, online fault detection and future trends....

  19. Design characteristics of EU-APR1400 on-site power system

    International Nuclear Information System (INIS)

    Kim, D.H.; Kim, Y.S.; Kim, Y.S.

    2014-01-01

    In the global nuclear market, US and European design requirements have been largely used to develop the design of nuclear power plants(NPPs). The APR1400 design was developed on the basis of US regulatory guide and EPRI utility requirements document(URD). In order to enlarge the export market of APR1400, KHNP (Korea Hydro & Nuclear Power Co., Ltd) has developed the EU-APR1400 design which complies with the European nuclear design requirements. In this paper, the design characteristics of EU-APR1400 on-site power system developed according to the European design requirements of electrical power system are described. The European main design requirements of electrical power system involve 50 Hz rated frequency, 400/110 kV grid voltage, the application of the diversity and the redundancy, and so on. The EU-APR1400 on-site power system has been developed on the basis of these requirements. The representative designs include the redundancy, diversity, independence design, the emergency power supply design, the design for providing electrical power to the dedicated severe accident systems, and the design for European grid requirements. (author)

  20. Reliability improvement of potential transformer and secondary circuit of 6 kV 1E-class buses in Qinshan nuclear power plant

    International Nuclear Information System (INIS)

    Qian Houjun

    2014-01-01

    There are design defects in potential transformer (PT) and secondary circuit of 6 kV 1E-class buses in Qinshan Nuclear Power Plant Nuclear Island. During the operating period, there happened several serious operational events (loss of power) caused by PT resonance. The essay analyses the defects of original design, and put forward corresponding modification measures, which have been carried out by two steps between 2009 and 2010, and after the modification the same problems have not happened again. (author)

  1. Single-phase AutoReClosure ARC failure on 400 kV combinedcable/overhead line with permanently connected shunt reactor

    DEFF Research Database (Denmark)

    Bak, Claus Leth; Søgaard, Kim

    2008-01-01

    400 kV power system and initiated by Danish TSO Energinet.dk after having measured the voltage of the cable/overhead line after disconnection. A particular decaying dynamic phase voltage containing voltages higher than the voltage before disconnection appeared. A simulation model for the entire system...

  2. Automatización de la red de 34,5kV en la provincia de Villa Clara; Automation of 34,5 kV network in the province of Villa Clara

    Directory of Open Access Journals (Sweden)

    Obedi Álvarez Díaz

    2012-11-01

    Full Text Available En la actualidad la operación de la redes de 34.5kV de la provincia de Villa Clara se hace muy complejo debido a que los desconectivos existentes son operados manualmente por el personal y los tiempos de operación son extensos. El objetivo de la implementación de la automatización de las redes de 34.5kV en Villa Clara es operar dicha red de la forma más eficiente posible, donde se le suministre la energía eléctrica a los clientes con mínimos costos de operación, alto nivel de confiabilidad, disminución de la frecuencia de interrupciones y también de los tiempos. Se seleccionaron los lazos más importantes de la provincia, los cuales incluyen generación distribuida, realizándoles corridas de flujo de carga usando el software PowerSystem Explorer (PSX, obteniendo los lugares donde se deben colocar los recerradores. Estos se comunicarán entre sí, pudiendo ser configurables para distintas condiciones, además de poder operarlos a distancia.  At present the operation of the 34.5kV network of the province of Villa Clara is very complex because the existing disconnected are operated by staff and operating times are long. The objective of the implementation of the automation 34.5 kV networks in Villa Clara is operate as efficiently way as possible, where you supply the electricity to customers with minimal operating costs, high reliability, reduced the frequency of interruptions and the times. There have been selected the most important loops in the province, which include distributed generation, performing load flow runs using the Power System Explorer software(PSX, obtaining the locations should be placed reclosing. They shall communicate with each otherand can be configured for different conditions, in addition to being to operate them at a distance.

  3. Design and testing of 45 kV, 50 kHz pulse power supply for dielectric barrier discharges

    Science.gov (United States)

    Sharma, Surender Kumar; Shyam, Anurag

    2016-10-01

    The design, construction, and testing of high frequency, high voltage pulse power supply are reported. The purpose of the power supply is to generate dielectric barrier discharges for industrial applications. The power supply is compact and has the advantage of low cost, over current protection, and convenient control for voltage and frequency selection. The power supply can generate high voltage pulses of up to 45 kV at the repetitive frequency range of 1 kHz-50 kHz with 1.2 kW input power. The output current of the power supply is limited to 500 mA. The pulse rise time and fall time are less than 2 μs and the pulse width is 2 μs. The power supply is short circuit proof and can withstand variable plasma load conditions. The power supply mainly consists of a half bridge series resonant converter to charge an intermediate capacitor, which discharges through a step-up transformer at high frequency to generate high voltage pulses. Semiconductor switches and amorphous cores are used for power modulation at higher frequencies. The power supply is tested with quartz tube dielectric barrier discharge load and worked stably. The design details and the performance of the power supply on no load and dielectric barrier discharge load are presented.

  4. Equivalent model and power flow model for electric railway traction network

    Science.gov (United States)

    Wang, Feng

    2018-05-01

    An equivalent model of the Cable Traction Network (CTN) considering the distributed capacitance effect of the cable system is proposed. The model can be divided into 110kV side and 27.5kV side two kinds. The 110kV side equivalent model can be used to calculate the power supply capacity of the CTN. The 27.5kV side equivalent model can be used to solve the voltage of the catenary. Based on the equivalent simplified model of CTN, the power flow model of CTN which involves the reactive power compensation coefficient and the interaction of voltage and current, is derived.

  5. Simulation of interaction between wind farm and power system[Flicker

    Energy Technology Data Exchange (ETDEWEB)

    Soerensen, P.; Hansen, A.; Janosi, L.; Bech, J.; Bak-Jensen, B.

    2001-12-01

    A dynamic model of the wind farm Hagesholm has been implemented in the dedicated power system simulation program DIgSILENT. The wind farm consists of six 2MW NM2000/72 wind turbines from NEG-Micon. The model has been verified using simultaneous power quality measurements on the 10 kV terminals of a single wind turbine and power performance measurements on two wind turbines. The verification shows a generally good agreement between simulations and measurements, although the simulations at higher wind speeds seem to underestimate the power and voltage fluctuations. A way to improve the simulation at higher wind speeds is suggested. (au)

  6. Optimization of 200 kV electrostatic accelerator

    Directory of Open Access Journals (Sweden)

    M Nazmabadi

    2015-09-01

    Full Text Available Optimizations on 200 kV electrostatic accelerator have been done in order to increasing ion current on target, improving vacuum condition and reduction in x-rays emission, increasing stability of high voltage power supply and reaching much greater achievable voltage value. The accelerator tube has most important effect on beam tracing in the electrostatic accelerators. So precautions most be considered in designing and constructing of this part. In order to finding permissible tolerances in construction and assembling of 200 kV electrostatic accelerator column, first the effects of angle deviation of a part from accelerator axis on beam track in the accelerator tube was simulated with Simion 7.0 computer program. We found that in order to prevent beam lost, the tolerances of balancing and co-centering of each part should be smaller than 0.1 mm. Each part of accelerator tube constructed by tolerances lower than 0.05 mm. Ultrasonic cleaning method used in pre-assembling process of parts. Because of its excellences, in the new tube we used borosilicate glass instead of high density alumina as insulators between the metallic electrodes. After three days of working vacuum pumps the system reached to 8.0×10-7 and after months to 5.0×10-7 ultimate pressure values. Measurements showed that by these considerations the maximum of reachable ion current on target was 1.1 mA which increased 50% compared to old machine, while x-ray emission intensity was increased by 25%. Optimizations of high voltage power supply are now under studies and tests

  7. SMES based power modulator - status August 2001

    International Nuclear Information System (INIS)

    Juengst, K.P.; Gehring, R.; Kudymow, A.; Suess, E.

    2001-10-01

    Based on a superconducting magnetic energy storage (SMES) a long-pulse klystron modulator has been designed for use in the TESLA test facility (TTF) at DESY, Hamburg. A proto-type with an output power of 25 MW is under development at Forschungszentrum Karlsruhe in cooperation with the office of engineering lbK at Karlsruhe. Including a pulse transformer (1:13/11.5), the system will deliver pulses of 130 kV or 115 kV, 1.7 ms pulse length with a flat top of ± 0.5%, at a repetition rate up to 10 Hz. This new system's main features are a highly dynamic SMES (> 100 T/s), a high current power supply (rated 27 V/2.6 kA), a switched-mode high voltage power supply (rated 14 kV/45 A), a fast thyristor power switch for 2.6 kA approx. continuous current/ 2 ms break, an IGCT power switch rated 2.6 kA/14 kV, a protection switch unit and a system control unit. This demonstration system is to serve alternatively two klystrons of 5 MW RF output or one multibeam klystron of 10 MW RF output. A significant part of the components of the system has been built. A first set of the system components had been arranged to form a model of the modulator and 1 MW pulses were generated. The next large step in the area of the power electronic part is to increase the power of this test arrangement up to 10 MW. The SMES and its cryostat have undergone initial testing. The data acquisition and control system under development at DESY has been taken over and adjusted to our computer and experimental environment. (orig.)

  8. Soil scientific supervision of 220/38 kV cable circuits of the power station 'Eemscentrale' in the Dutch province Groningen: Part 2

    International Nuclear Information System (INIS)

    Langevoord, J.; Kraeima, A.F.

    1995-01-01

    Recently, five underground cable circuits were completed at the site of the EPON (an energy utility for the north-eastern part of the Netherlands) title power station, consisting of two 220 kV and two 380 kV connections with a total length of 24 km. In a previous article, attention is paid to theoretical aspects of heat transfer of cables for underground electricity transport, the research method of the soil scientific survey, and the results of the survey for the design of the cable connection, to be made by NKF (cable manufacturer) and for the final execution of the cable design. In this article attention will be paid to soil scientific marginal conditions and soil scientific supervision during the realization. 1 fig., 2 tabs., 2 refs

  9. Functional analysis of Kv1.2 and paddle chimera Kv channels in planar lipid bilayers

    Science.gov (United States)

    Tao, Xiao; MacKinnon, Roderick

    2010-01-01

    Summary Voltage-dependent K+ channels play key roles in shaping electrical signaling in both excitable as well as non-excitable cells. These channels open and close in response to the voltage changes across the cell membrane. Many studies have been carried out in order to understand the voltage sensing mechanism. Our laboratory recently determined the atomic structures of a mammalian voltage-dependent K+ channel Kv1.2 and a mutant of Kv1.2 named the ‘paddle-chimera’ channel, in which the voltage sensor paddle was transferred from Kv2.1 to Kv1.2. These two structures provide atomic descriptions of voltage-dependent channels with unprecedented clarity. Until now the functional integrity of these two channels biosynthesized in yeast cells have not been assessed. Here we report the electrophysiological and pharmacological properties of Kv1.2 and the paddle chimera channels in planar lipid bilayers. We demonstrate that Pichia yeast produce ‘normally functioning’ mammalian voltage-dependent K+ channels with qualitatively similar features to the Shaker K+ channel in the absence of the N-terminal inactivation gate, and that the paddle chimera mutant channel functions as well as Kv1.2. We find, however, that in several respects the Kv1.2 channel exhibits functional properties that are distinct from Kv1.2 channels reported in the literature. PMID:18638484

  10. Lawrence Berkeley laboratory neutral-beam engineering test facility power-supply system

    International Nuclear Information System (INIS)

    Lutz, I.C.; Arthur, C.A.; deVries, G.J.; Owren, H.M.

    1981-10-01

    The Lawrence Berkeley Laboratory is upgrading the neutral beam source test facility (NBSTF) into a neutral beam engineering test facility (NBETF) with increased capabilities for the development of neutral beam systems. The NBETF will have an accel power supply capable of 170 kV, 70 A, 30 sec pulse length, 10% duty cycle; and the auxiliary power supplies required for the sources. This paper describes the major components, their ratings and capabilities, and the flexibility designed to accomodate the needs of source development

  11. EFFECTS OF STEEL PLANTS WITH THREE-PHASE INDUCTION FURNACES ON POWER DISTRIBUTION QUALITY OF THE EXISTING 33 kV NETWORK IN NIGERIA

    Directory of Open Access Journals (Sweden)

    Saheed Lekan Gbadamosi

    2015-08-01

    Full Text Available This study aimed at evaluating and analyzing the voltage and current distortions on the introduction of a steel production plant in a typical 33 kV distribution system in Nigeria, with a view to assisting decisions made in the present system operation and planning effective service delivery in terms of quality. A three phase induction furnace was developed using MatLab Simulink software and the effects of steel plant loads on the quality of electric power system supply to electricity users on the same distribution network was analyzed in terms of total harmonic distortions of voltage and current. In order to evaluate voltage magnitude profile on the network, load flow computation and analyses were carried out on the 33 kV distribution network before and after the introduction of steel plant loads, using Successive Approximation Method. The results showed critical voltage magnitude profile below -5% of nominal voltage at the receiving end nodes. With the aid of the Matlab Simulink model, inadmissible voltage and current distortions of 15.47% and 10.35% were measured. Passive filter was proposed, designed and simulated, in order to mitigate these distortions caused by the steel production plant loads. By simulation, the installation of the designed passive filter gave a reduction of the distortions to permissible values. Further, for every 1 MW load increment when the steel plant is connected, network losses increased by 94%; however, for every of Mvar of filter capacity, loss reduction in the network is 5.1 MW.

  12. Mechanosensitive gating of Kv channels.

    Directory of Open Access Journals (Sweden)

    Catherine E Morris

    Full Text Available K-selective voltage-gated channels (Kv are multi-conformation bilayer-embedded proteins whose mechanosensitive (MS Popen(V implies that at least one conformational transition requires the restructuring of the channel-bilayer interface. Unlike Morris and colleagues, who attributed MS-Kv responses to a cooperative V-dependent closed-closed expansion↔compaction transition near the open state, Mackinnon and colleagues invoke expansion during a V-independent closed↔open transition. With increasing membrane tension, they suggest, the closed↔open equilibrium constant, L, can increase >100-fold, thereby taking steady-state Popen from 0→1; "exquisite sensitivity to small…mechanical perturbations", they state, makes a Kv "as much a mechanosensitive…as…a voltage-dependent channel". Devised to explain successive gK(V curves in excised patches where tension spontaneously increased until lysis, their L-based model falters in part because of an overlooked IK feature; with recovery from slow inactivation factored in, their g(V datasets are fully explained by the earlier model (a MS V-dependent closed-closed transition, invariant L≥4. An L-based MS-Kv predicts neither known Kv time courses nor the distinctive MS responses of Kv-ILT. It predicts Kv densities (hence gating charge per V-sensor several-fold different from established values. If opening depended on elevated tension (L-based model, standard gK(V operation would be compromised by animal cells' membrane flaccidity. A MS V-dependent transition is, by contrast, unproblematic on all counts. Since these issues bear directly on recent findings that mechanically-modulated Kv channels subtly tune pain-related excitability in peripheral mechanoreceptor neurons we undertook excitability modeling (evoked action potentials. Kvs with MS V-dependent closed-closed transitions produce nuanced mechanically-modulated excitability whereas an L-based MS-Kv yields extreme, possibly excessive

  13. Reliability assessment of distribution power systems including distributed generations

    International Nuclear Information System (INIS)

    Megdiche, M.

    2004-12-01

    Nowadays, power systems have reached a good level of reliability. Nevertheless, considering the modifications induced by the connections of small independent producers to distribution networks, there's a need to assess the reliability of these new systems. Distribution networks present several functional characteristics, highlighted by the qualitative study of the failures, as dispersed loads at several places, variable topology and some electrotechnical phenomena which must be taken into account to model the events that can occur. The adopted reliability calculations method is Monte Carlo simulations, the probabilistic method most powerful and most flexible to model complex operating of the distribution system. We devoted a first part on the case of a 20 kV feeder to which a cogeneration unit is connected. The method was applied to a software of stochastic Petri nets simulations. Then a second part related to the study of a low voltage power system supplied by dispersed generations. Here, the complexity of the events required to code the method in an environment of programming allowing the use of power system calculations (load flow, short-circuit, load shedding, management of units powers) in order to analyse the system state for each new event. (author)

  14. Research on Line Patrol Strategy of 110kV Transmission Line after Lightning Strike

    Directory of Open Access Journals (Sweden)

    Li Mingjun

    2016-01-01

    Full Text Available Lightning faults occupy in the majority of instantaneous fault and reclosing can usually be successful, so power supply can be restored without immediate patrol in many cases. Firstly, this paper introduces the lightning fault positioning and identifying method. Then test electrical performance of insulators after lightning strike from 110kV lines. Data shows that lightning strike has little effect on the electric performance of insulator. Finally, illustrating disposal process of the 110 kV transmission line after lightning fault, certifying that the power supply reliability be ensured without line patrol.

  15. An operational 150 kV microfocus rod anode X-ray system for nondestructive testing

    International Nuclear Information System (INIS)

    Fontijn, E.A.

    1978-01-01

    This paper describes an operational state of the art 150 kV microfocus rod anode X-ray system having ultra-high radiographic resolution capabilities. A cocal spot size of 0.050 mm is provided. Heretofore unattainable long rod anode lengths coupled with very small diameters are now possible using mini-magnetic lens technology. Over-all rod anode diameters as small as 9 mm with useful lengths of 1 m or more are possible, permitting panoramic inspections where previously only lower resolution radioisotope radiographic techniques were possible. Radiographic sensitivity of better than 1% has been reported with film-focal-distances on the order of 8 mm through 3 mm of steel. The system has been successfully applied to steam generator and heat exchanger tube-to-tubesheet weldments in both Europe and the USA. Other application areas include marine and aircraft jet engine inspection and numerous other applications where high reliability requirements indicate the use of a ultra-sensitive radiographic technique as is routinely demonstrated with the 150 kV Microfocus Rod Anode X-ray System. (orig.) [de

  16. Voltage and reactive power in the 380/220 kV power network of the new German Laender - state and prospects. Spannung und Blindleistung im 380/220-kV-Verbundnetz der neuen Bundeslaender - Stand und Ausblick

    Energy Technology Data Exchange (ETDEWEB)

    Behnke, M; Luettig, K; Radtke, H [Verbundnetz Elektroenergie AG, Berlin (Germany)

    1991-01-01

    With the preparation for restoring a German power network after nearly 40 years of separate development of the EES of the former DDR, the voltage/reactive power regulation must be examined and evaluated in the conditions of: - parting the connections to the present VES partners Poland and Czechoslovakia with the option of rectification - taking up parallel operation with the adjacent network undertakings of the old West German Laender (Preussen Elektra AG and Bayernwerke AG), ie: combined operation with DVG (superregional network of old West German Laender) and UCPTE (European electrical energy union). The aim is to configure this in the 380/220 kV network of the new German Laender, so that with a regionally compensated reactive power system, the voltage can be kept steady much better at times of heavy and light load, and the network losses can be reduced. (orig./GL).

  17. Development of a single-phase 30 m HTS power cable

    Science.gov (United States)

    Cho, Jeonwook; Bae, Joon-Han; Kim, Hae-Jong; Sim, Ki-Deok; Kim, Seokho; Jang, Hyun-Man; Lee, Chang-Young; Kim, Dong-Wook

    2006-05-01

    HTS power transmission cables appear to be the replacement and retrofitting of underground cables in urban areas and HTS power transmission cable offers a number of technical and economic merits compared to the normal conductor cable system. A 30 m long, single-phase 22.9 kV class HTS power transmission cable system has been developed by Korea Electrotechnology Research Institute (KERI), LS Cable Ltd., and Korea Institute of Machinery and Materials (KIMM), which is one of the 21st century frontier project in Korea since 2001. The HTS power cable has been developed, cooled down and tested to obtain realistic thermal and electrical data on HTS power cable system. The evaluation results clarified such good performance of HTS cable that DC critical current of the HTS cable was 3.6 kA and AC loss was 0.98 W/m at 1260 Arms and shield current was 1000 Arms. These results proved the basic properties for 22.9 kV HTS power cable. As a next step, we have been developing a 30 m, three-phase 22.9 kV, 50 MV A HTS power cable system and long term evaluation is in progress now.

  18. Faraday Rotator 5 kV Capacitor Bank

    International Nuclear Information System (INIS)

    Fetterman, C.C.

    1975-01-01

    A Faraday rotator 5 kV capacitor bank is a pulsed output power supply used to energize Faraday rotators for optical isolation in the ''LLL kJ Glass Laser System.'' Each supply contains either one, two or three parallel 240 μF storage capacitors depending on the size of the isolator used. Generally, the ''A*''(216 μH) isolator is energized with one capacitor, the ''A''(116 μH) isolator uses two capacitors and the ''B''(87 μH) isolator requires three capacitors. All models of isolators have been tested with four capacitors under maximum voltage and 25 feet of RG-217 cable with no hazardous effects. Except for the number of capacitors in each unit, the supplies are otherwise physically identical

  19. Outlook for use of 10 kV voltage in coal mines

    Energy Technology Data Exchange (ETDEWEB)

    Voloshchenko, N.I.; Nabokov, E.P.; Razumnyy, Yu.T.

    1983-01-01

    Based on technical-economic studies of the models of the plans for electricity supply, the economic expediency is shown of comprehensive implementation of measures for transition of high-voltage equipment of the mines to voltage of 10 kV with simultaneous improvement in the permissible power of short circuiting to 150 MV X A. Technical problems were examined which are associated with creation of explosion-safe electrical equipment, corresponding to the new technical requirements for the system of electricity supply of the coal mine.

  20. Safety procedures for the MFTF sustaining-neutral-beam power supply

    International Nuclear Information System (INIS)

    Wilson, J.H.

    1981-01-01

    The MFTF SNBPSS comprises a number of sources of potentially hazardous electrical energy in a small physical area. Power is handled at 80 kV dc, 80 A; 70 V dc, 4000 A; 25 V dc, 5500 A; 3 kV dc, 10 A; and 2 kV dc, 10 A. Power for these systems is furnished from two separate 480 V distribution systems and a 13.8 kV distribution system. A defense in depth approach is used; interlocks are provided in the hardware to make it difficult to gain access to an energized circuit, and the operating procedure includes precautions which would protect personnel even if no interlocks were working. The complexity of the system implies a complex operating procedure, and this potential complexity is controlled by presenting the procedure in a modular form using 37 separate checklists for specific operations. The checklists are presented in flowchart form, so contingencies can be handled at the lowest possible level without compromising safety

  1. Management of high current transients in the CWDD Injector 200 kV power system

    International Nuclear Information System (INIS)

    Carwardine, J.A.; Pile, G.; Zinneman, T.E.

    1993-01-01

    The injector for the Continuous Wave Deuterium Demonstrator is designed to deliver a high current CW negative deuterium ion beam at an energy of 200 keV to a Radio Frequency Quadrupole. The injector comprises a volume ion source, triode accelerator, high-power electron traps and low-energy beam transport with a single focusing solenoid. Some 75 Joules of energy are stored in stray capacitance around the high voltage system and discharged in a few microseconds following an injector breakdown. In order to limit damage to the accelerator grids, a magnetic snubber is incorporated to absorb most of the energy. Nevertheless, large current transients flow around the system as a result of an injector breakdown; these have frequently damaged power components and caused spurious behavior in many of the supporting systems. The analytical and practical approaches taken to minimize the effects of these transients are described. Injector breakdowns were simulated using an air spark gap and measurements made using standard EMC test techniques. The power circuit was modeled using an electrical simulation code; good agreement was reached between the model and measured results

  2. The subfamily-specific interaction between Kv2.1 and Kv6.4 subunits is determined by interactions between the N- and C-termini.

    Directory of Open Access Journals (Sweden)

    Elke Bocksteins

    Full Text Available The "silent" voltage-gated potassium (KvS channel subunit Kv6.4 does not form electrically functional homotetramers at the plasma membrane but assembles with Kv2.1 subunits, generating functional Kv2.1/Kv6.4 heterotetramers. The N-terminal T1 domain determines the subfamily-specific assembly of Kv1-4 subunits by preventing interactions between subunits that belong to different subfamilies. For Kv6.4, yeast-two-hybrid experiments showed an interaction of the Kv6.4 N-terminus with the Kv2.1 N-terminus, but unexpectedly also with the Kv3.1 N-terminus. We confirmed this interaction by Fluorescence Resonance Energy Transfer (FRET and co-immunoprecipitation (co-IP using N-terminal Kv3.1 and Kv6.4 fragments. However, full-length Kv3.1 and Kv6.4 subunits do not form heterotetramers at the plasma membrane. Therefore, additional interactions between the Kv6.4 and Kv2.1 subunits should be important in the Kv2.1/Kv6.4 subfamily-specificity. Using FRET and co-IP approaches with N- and C-terminal fragments we observed that the Kv6.4 C-terminus physically interacts with the Kv2.1 N-terminus but not with the Kv3.1 N-terminus. The N-terminal amino acid sequence CDD which is conserved between Kv2 and KvS subunits appeared to be a key determinant since charge reversals with arginine substitutions abolished the interaction between the N-terminus of Kv2.1 and the C-terminus of both Kv2.1 and Kv6.4. In addition, the Kv6.4(CKv3.1 chimera in which the C-terminus of Kv6.4 was replaced by the corresponding domain of Kv3.1, disrupted the assembly with Kv2.1. These results indicate that the subfamily-specific Kv2.1/Kv6.4 heterotetramerization is determined by interactions between Kv2.1 and Kv6.4 that involve both the N- and C-termini in which the conserved N-terminal CDD sequence plays a key role.

  3. Optimal power flow with optimal placement TCSC device on 500 kV Java-Bali electrical power system using genetic Algorithm-Taguchi method

    Science.gov (United States)

    Apribowo, Chico Hermanu Brillianto; Ibrahim, Muhammad Hamka; Wicaksono, F. X. Rian

    2018-02-01

    The growing burden of the load and the complexity of the power system has had an impact on the need for optimization of power system operation. Optimal power flow (OPF) with optimal location placement and rating of thyristor controlled series capacitor (TCSC) is an effective solution used to determine the economic cost of operating the plant and regulate the power flow in the power system. The purpose of this study is to minimize the total cost of generation by placing the location and the optimal rating of TCSC using genetic algorithm-design of experiment techniques (GA-DOE). Simulation on Java-Bali system 500 kV with the amount of TCSC used by 5 compensator, the proposed method can reduce the generation cost by 0.89% compared to OPF without using TCSC.

  4. RHIC BEAM ABORT KICKER POWER SUPPLY SYSTEM COMMISSIONING EXPERIENCE AND REMAINING ISSUES

    International Nuclear Information System (INIS)

    ZHANG, W.; AHRENS, L.A.; MI, J.; OERTER, B.; SANDERS, R.; SANDBERG, J.

    2001-01-01

    The RHIC Beam Abort Kicker Power Supply Systems commissioning experience and the remaining issues will be reported in this paper. The RHIC Blue Ring Beam Abort Kicker Power Supply System initial commissioning took place in June 1999. Its identical system in Yellow Ring was brought on line during Spring 2000. Each of the RHIC Beam Abort Kicker Power Supply Systems consists of five high voltage modulators and subsystems. These systems are critical devices for RHIC machine protection and environmental protection. They are required to be effective, reliable and operating with sufficient redundancy to safely abort the beam to its beam dump at the end of accumulation or at any time when they are commanded. To deflect 66 GeV ion beam to the beam absorbers, the RHIC Beam Abort Kicker Power Supply Systems were operated at 22 kV level. The RHIC 2000 commissioning run was very successful

  5. Negative-feedback control system of the high voltage power supply for ECRH

    International Nuclear Information System (INIS)

    Ding Tonghai; Liu Baohua; Jiang Shufang

    2001-01-01

    A kind of high accuracy negative high voltage power supply (HVPS) was introduced. The serial feedback was regulated according to the character of the high power tetrode and a new kind of integrator with preset value, which solved the key technological problem of the HVPS that the ECRH system required a voltage of -80 kV, a pulse width of 10 - 100 ms and a precision of 99.7%. The result using a PSPICE code simulation has shown that the method is practical

  6. Decision and Order in the matter of an application by Superior Wind Prince Power Inc. for an Order or Orders pursuant to section 92 of the Ontario Energy Board Act, 1998 granting leave to construct a 230 kV transmission line and associated facilities to connect a proposed 99 MW wind farm to the transmission system of Great Lakes Power Ltd. near Sault Ste Marie[In the matter of the Ontario Energy Board Act, 1998, S.O. 1998, c. 15, Schedule B

    Energy Technology Data Exchange (ETDEWEB)

    Kaiser, G.; Betts, B.; Vlahos, P.

    2005-07-28

    Superior Wind Prince Power Inc. plans to construct and operate a 99 MW wind generation facility near Sault Ste. Marie, Ontario. It has also filed an application with the Ontario Energy Board to construct transmission facilities to connect the wind farm to the transmission system of Great Lakes Power Ltd. This includes a substation with a 34.5/230 kV transformer, a high voltage breaker, and low voltage switchgear. It also includes an 11.2 km long, 230 kV transmission line and a switching station with a 230 kV breaker and related facilities. The entire project is scheduled for completion by March, 2006. The Board will proceed with the application by way of a written hearing. This document presents evidence of the applicant with reference to the request for proposals for 300 MW of Renewable Energy. The wind farm includes 66 wind turbine generators providing an output of 99 MW. Plans for a second phase would add 101 MW to the wind farm. Different high voltage and low voltage configurations have been examined on the basis of environmental and economic considerations and system reliability. The best configuration was a 34.5 kV underground collector system and a 230 kV above ground transmission line. Four alternative routes for the line were examined on the basis of environmental, technical and economic factors. This document also provided evidence of PUC Distribution Inc. and addressed issues regarding a system impact assessment, customer impact assessment, and environmental assessment. The Board questioned whether the project is needed, what impact it will have on transmission rates, and reliability of supply. It also examined if all land-use matters have been addressed. The Board approved the project subject to certain conditions regarding communications, monitoring and reporting requirements. 2 refs., 1 appendix.

  7. Increased power delivery from the DIII-D neutral beam injection system

    International Nuclear Information System (INIS)

    Colleraine, A.P.; Callis, R.W.; Hong, R.M.; Kellman, D.H.; Kim, J.; Langhorn, A.R.; Lee, R.; Phillips, J.C.; Wight, J.J.

    1989-12-01

    The neutral beam system installed on the DIII-D tokamak employs eight 80 kV Long Pulse Sources (LPS) mounted on four beamlines and was originally designed to deliver a nominal 12 MW of H degree power to a plasma for pulses of up to 5 sec duration. Lawrence Berkeley Laboratory designed the LPS for the US Fusion Program to fill the requirements of both the DIII-D and the TFTR machines. Essentially all source components are of a common design; the DIII-D version is therefore conservative in its rated parameters. Recently a neutron shield has been constructed around the torus hall allowing D degree injection to become routine. Because deuterium beams have a better neutralization efficiency, the nominal power delivery per source has been measured to be approximately 2 MW (for a total of 16 MW) without any modifications. However, by reoptimizing the voltage gradients in the source, the perveance can be increased without degrading the optics. A change of gradient grid voltage from 0.83 V accel to 0.79 V accel raises the perveance from 2.5 to 3.0 μPerv with a corresponding gain in beam power of about 20%. The arc power required also must be increased to the range of 100 to 120 kW but this is well within the design limits of the LPS. Further studies of our systems are now underway to assess the possibilities of raising V accel above 80 kV. An additional gain in power is possible by this technique. 6 refs., 6 figs

  8. Construction and 60 kV tests of the prototype pulser for the LHC injection kicker system

    CERN Document Server

    Barnes, M J; Carlier, E; Ducimetière, L; Schröder, G; Vossenberg, Eugène B

    1999-01-01

    The European Laboratory for Particle Physics (CERN) is constructing the Large Hadron Collider (LHC). Two counter-rotating proton beams will be injected into the LHC at an energy of 450 GeV by two kicker magnet systems, producing magnetic field pulses of approximately 900 ns rise time and 6.6 mu s flat top duration with a ripple of less than +or-0.5Both injection systems are composed of 4 travelling wave kicker magnets of 2.17 m length each, powered by pulse forming networks (PFNs). To achieve the high-required kick strength of 1.2 Tm, for a compact and cost efficient design, a characteristic impedance of 5 Ohms has been chosen. The design strategy for the magnets and generators has been defined after detailed analysis of existing systems. The electrical circuit has been optimised using the circuit analysis software PSpice. Most known parasitics have been modelled. A prototype PFN has been constructed at CERN and successfully tested at 60 kV. A calibration procedure has been developed and utilised for obtainin...

  9. Computer-aided analysis of power-electronic systems simulation of a high-voltage power converter

    International Nuclear Information System (INIS)

    Bordry, F.; Isch, H.W.; Proudlock, P.

    1987-01-01

    In the study of semiconductor devices, simulation methods play an important role in both the design of systems and the analysis of their operation. The authors describe a new and efficient computer-aided package program for general power-electronic systems. The main difficulty when taking into account non-linear elements, such as semiconductors, lies in determining the existence and the relations of the elementary sequences defined by the conduction or nonconduction of these components. The method does not require a priori knowledge of the state sequences of the semiconductor nor of the commutation instants, but only the circuit structure, its parameters and the commands to the controlled switches. The simulation program computes automatically both transient and steady-state waveforms for any circuit configuration. The simulation of a high-voltage power converter is presented, both for its steady-state and transient overload conditions. This 100 kV power converter (4 MW) will feed two klystrons in parallel

  10. Corona performance of a compact 230-kV line

    International Nuclear Information System (INIS)

    Chartier, V.L.; Blair, D.E.

    1994-01-01

    Permitting requirements and the acquisition of new rights-of-way for transmission facilities has in recent years become increasingly difficult for most utilities, including Puget Sound Power and Light Company. In order to maintain a high degree of reliability of service while being responsive to public concerns regarding the siting of high voltage (HV) transmission facilities, Puget Power has found it necessary to more heavily rely upon the use of compact lines in franchise corridors. Compaction does, however, precipitant increased levels of audible noise (AN) and radio and TV interference (RI and TVI) due to corona on the conductors and insulator assemblies. Puget Power relies upon the Bonneville Power Administration (BPA) Corona and Field Effects computer program to calculate AN and RI for new lines. Since there was some question of the program's ability to accurately represent quiet 230-kV compact designs, a joint project was undertaken with BPA to verify the program's algorithms. Long-term measurements made on an operating Puget Power 230-kV compact line confirmed the accuracy of BPA's AN model; however, the RI measurements were much lower than predicted by the BPA computer and other programs. This paper also describes how the BPA computer program can be used to calculate the voltage needed to expose insulator assemblies to the correct electric field in single test setups in HV laboratories

  11. Developments of compact pulsed-power system toward X-ray sources

    Directory of Open Access Journals (Sweden)

    Miyamoto Takuya

    2013-11-01

    Full Text Available In order to generate X-rays from X-pinch, the peak current and current-rising time required are estimated to be 100 kA and 100 ns, respectively. To obtain these parameters, we developed a pulsed-power system, which consists of a parallelized pulse-forming network (PFN. The 20 PFN modules of the system were driven at a charging voltage of 20 kV by a thin copper wire of load resistance. The results showed that the current and current-rising time are 18 kA and 107 ns, respectively. The wire/plasma temperature is 6.9 eV. The pulsed-power system is expected to generate X-rays from X-pinch by the proposed system. This can be achieved by raising the voltage and increasing the number of PFN modules.

  12. Improvement of the 400 kV linac electron source of AmPS

    International Nuclear Information System (INIS)

    Kroes, F.B.; Beuzekom, M.G. van; Dobbe, N.J.; Es, J.T. van; Jansweijer, P.P.M.; Kruijer, A.H.; Luigjes, G.; Sluijk, T.G.B.

    1992-01-01

    The installation of the 900 MeV Amsterdam Pulse Stretcher is nearly completed and its commissioning will start Spring 1992. The existing linac MEA will inject electrons in the AmPS ring. The linacs peak current will be increased from 20 to 80 mA. This requires modification of the 400 kV low emittance gun which now will deliver a peak current of maximum 400 mA instead of 100 mA at a pulse width of 2.1 μsec. The fourfold increase of the peakcurrent is obtained by doubling both the gun perveance (new gun part) and the pulsed extractor voltage. After chopping and pre-bunching more than 80 mA will be available for acceleration in MEA. To obtain optimum beam quality over this increased current range the hot deck electronics, operating at -400 kV, has been exchanged by a state of the art fast high voltage FET switching supply. The increased space charge forces in the beam require stronger electro-static focusing in the first electrostatic gap to define the beam diameter at the gun exit. This is accomplished with a 25 kV controlled power supply. A build in microprocessor, coupled to the local computer by optical fibers, is used to monitor and control the gun parameters. The 5kV gun extractor voltage pulse shape can be monitored by means of an analog fibre transducer with build in calibration. Finally, in order to improve the energy stability of the accelerated electrons a serial electron-tube stabilizer was added to the 400 kV DC power supply. A supply stability of 2. 10 -5 has been achieved. (author). 4 refs.; 6 figs

  13. Nanosecond pulsed power generator for a voltage amplitude up to 300 kV and a repetition rate up to 16 Hz for fine disintegration of quartz

    Energy Technology Data Exchange (ETDEWEB)

    Krastelev, E. G., E-mail: ekrastelev@yandex.ru; Sedin, A. A.; Tugushev, V. I. [Russian Academy of Sciences, Joint Institute for High Temperatures (Russian Federation)

    2015-12-15

    A generator of high-power high-voltage nanosecond pulses is intended for electrical discharge disintegration of mineral quartz and other nonconducting minerals. It includes a 320 kV Marx pulsed voltage generator, a high-voltage glycerin-insulated coaxial peaking capacitor, and an output gas spark switch followed by a load, an electric discharge disintegration chamber. The main parameters of the generator are as follows: a voltage pulse amplitude of up to 300 kV, an output impedance of ≈10 Ω, a discharge current amplitude of up to 25 kA for a half-period of 80–90 ns, and a pulse repetition rate of up to 16 Hz.

  14. Nanosecond pulsed power generator for a voltage amplitude up to 300 kV and a repetition rate up to 16 Hz for fine disintegration of quartz

    International Nuclear Information System (INIS)

    Krastelev, E. G.; Sedin, A. A.; Tugushev, V. I.

    2015-01-01

    A generator of high-power high-voltage nanosecond pulses is intended for electrical discharge disintegration of mineral quartz and other nonconducting minerals. It includes a 320 kV Marx pulsed voltage generator, a high-voltage glycerin-insulated coaxial peaking capacitor, and an output gas spark switch followed by a load, an electric discharge disintegration chamber. The main parameters of the generator are as follows: a voltage pulse amplitude of up to 300 kV, an output impedance of ≈10 Ω, a discharge current amplitude of up to 25 kA for a half-period of 80–90 ns, and a pulse repetition rate of up to 16 Hz

  15. Performance of the Crowbar of the LHC High Power RF System

    CERN Document Server

    Ravidà, G; Valuch, D

    2012-01-01

    The counter-rotating proton beams in the Large Hadron Collider (LHC) are captured and accelerated to their final energies by two identical 400 MHz Radio Frequency (RF) systems. The RF power source required for each beam comprises eight 300 kW klystrons. The output power of each klystron is fed via a circulator and a waveguide line to the input coupler of a single-cell superconducting (SC) cavity. Each unit of four klystrons is powered by a -100kV/40A AC/DC power converter. A fast protection system (crowbar) protects the four klystrons in each of these units. Although the LHC RF system has shown has very good performance, operational experience has shown that the five-gap double-ended thyratrons used in the crowbar system suffer, from time to time, from auto-firing, which result in beam dumps. This paper presents the recent results obtained with an alternative solution based on solid state thyristors. Comparative measurements with the thyratron are shown.

  16. Phase I Development of Neutral Beam Injector Solid-State Power System

    Science.gov (United States)

    Prager, James; Ziemba, Timothy; Miller, Kenneth E.; Slobodov, Ilia; Anderson, Seth

    2017-10-01

    Neutral beam injection (NBI) is an important tool for plasma heating, current drive and a diagnostic at fusion science experiments around the United States, including tokamaks, validation platform experiments, and privately funded fusion concepts. Currently, there are no vendors in the United States for NBI power systems. Eagle Harbor Technologies (EHT), Inc. is developing a new power system for NBI that takes advantage of the latest developments in solid-state switching. EHT has developed a resonant converter that can be scaled to the power levels required for NBI at small-scale validation platform experiments like the Lithium Tokamak Experiment. This power system can be used to modulate the NBI voltages over the course of a plasma shot, which can lead to improved control over the plasma. EHT will present initial modeling used to design this system as well as experimental data showing operation at 15 kV and 40 A for 10 ms into a test load. With support of DOE SBIR.

  17. Gate driver with high common mode rejection and self turn-on mitigation for a 10 kV SiC MOSFET enabled MV converter

    DEFF Research Database (Denmark)

    Dalal, Dipen Narendrabhai; Christensen, Nicklas; Jørgensen, Asger Bjørn

    2017-01-01

    Miller clamp circuit for a 10 kV half bridge SiC MOSFET power module. Designed power supply and the gate driver circuit are verified in a double pulse test setup and a continuous switching operation using the 10 kV half bridge silicon carbide MOSFET power module. An in-depth experimental verification...

  18. Pharmacological dissection of K(v)7.1 channels in systemic and pulmonary arteries

    DEFF Research Database (Denmark)

    Chadha, Preet S; Zunke, Friederike; Davis, Alison J

    2012-01-01

    The aim of this study was to characterize the functional impact of KCNQ1-encoded voltage-dependent potassium channels (K(v)7.1) in the vasculature.......The aim of this study was to characterize the functional impact of KCNQ1-encoded voltage-dependent potassium channels (K(v)7.1) in the vasculature....

  19. Decreased expression of Kv7 channels in Hirchsprung's disease.

    Science.gov (United States)

    O'Donnell, Anne-Marie; Coyle, David; Puri, Prem

    2017-07-01

    Voltage-dependent K + channels (Kv channels) participate in electrical rhythmicity and smooth muscle responses and are regulated by excitatory and inhibitory neurotransmitters. Kv channels also participate in the interstitial cell of Cajal (ICC) and smooth muscle cell (SMC) responses to neural inputs. The Kv family consists of 12 subfamilies, Kv1-Kv12, with five members of the Kv7 family identified to date: Kv7.1-Kv7.5. A recent study identified the potassium channel Kv7.5 as having a role in the excitability of ICC-IM in the mouse colon. We therefore designed this study to test the hypothesis that Kv7 channels are present in the normal human colon and are reduced in Hirschprung's disease (HSCR). HSCR tissue specimens were collected at the time of pull-through surgery (n=10), while normal control tissue specimens were obtained at the time of colostomy closure in patients with imperforate anus (n=10). Kv7.3-Kv7.5 immunohistochemistry was performed and visualized using confocal microscopy to assess their distribution. Western blot analysis was undertaken to determine Kv7.3-Kv7.5 protein quantification. Kv7.3 and Kv7.4-immunoreactivity was co-localized with neuron and ICC markers, while Kv7.5 was found to be expressed on both ICCs and SMCs. Western blot analysis revealed similar levels of Kv7.3 and Kv7.5 expression in the normal colon and HSCR colon, while Kv7.4 proteins were found to be markedly decreased in ganglionic specimens and decreased further in aganglionic specimens. A deficiency of Kv7.4 channels in the ganglionic and aganglionic bowel may place a role in colonic dysmotility in HSCR. Copyright © 2017 Elsevier Inc. All rights reserved.

  20. National Maglev initiative: California line electric utility power system requirements

    Science.gov (United States)

    Save, Phil

    1994-01-01

    The electrical utility power system requirements were determined for a Maglev line from San Diego to San Francisco and Sacramento with a maximum capacity of 12,000 passengers an hour in each direction at a speed of 300 miles per hour, or one train every 30 seconds in each direction. Basically the Maglev line requires one 50-MVA substation every 12.5 miles. The need for new power lines to serve these substations and their voltage levels are based not only on equipment loading criteria but also on limitations due to voltage flicker and harmonics created by the Maglev system. The resulting power system requirements and their costs depend mostly on the geographical area, urban or suburban with 'strong' power systems, or mountains and rural areas with 'weak' power systems. A reliability evaluation indicated that emergency power sources, such as a 10-MW battery at each substation, were not justified if sufficient redundancy is provided in the design of the substations and the power lines serving them. With a cost of $5.6 M per mile, the power system requirements, including the 12-kV DC cables and the inverters along the Maglev line, were found to be the second largest cost component of the Maglev system, after the cost of the guideway system ($9.1 M per mile), out of a total cost of $23 M per mile.

  1. Study of the Atucha I nuclear power plant's residual heat removal system unavailability through the fault tree analysis and common cause failures

    International Nuclear Information System (INIS)

    Terrado, C.A.

    1991-06-01

    The present essay offers a comprehensive research of the Atucha I nuclear power plant's residual heat removal system unavailability, including Fault Tree Analysis and Common Cause Failures (CCF) treatment. The study is developed within the Event Tree perspective that considers the loss of external electrical power of the initiating event. The event was constructed by the Safety Evaluations Division of the Ezeiza Atomic Center in Argentina. According to the Event Tree, the research includes system demand during plant operation with 132 KV and emergency generation (Diesel motor generators). The system unavailability assessment is approached in two different ways: a) Considering independent failures only. b) Taking into account the existence of Common Cause Events, and modeling dependent failures. The Fault Tree quantification is played using the AIEA PSAPACK Code. The assessment data base is compiled from plant specific records and generic data bases like TECDOC 478. After Fault Tree model logic development, some general procedures used in common cause failures treating are applied to pick up another set of solutions. The results of the study are: a) Four Fault Trees have been developed to model the abovementioned system: 132 KV and emergency generation, both including and excluding CCF. b) The following unavailability values were obtained: 132 KV independent failures only: 7 10 -4 . Emergency generation independent failures only: 1.53 10 -2 . 132 KV dependent and independent failures: 3.6 10 -3 . Emergency generation dependent and independent failures: 1.74 10 -2 . The major conclusions obtained from the precedent results are: a) When using 132 KV system configuration, minimal cut sets involving common cause failures represents 81%from total system unavailability. b) The dependent failures treatment is an important task to be considered in safety assessments in order to reach more realistic values. (Author) [es

  2. Modeling of Electric Field Around 100 MVA 150/20 kV Power Transformator using Charge Simulation Method

    Directory of Open Access Journals (Sweden)

    Noviadi Arief Rachman

    2013-07-01

    Full Text Available Charge Simulation Method is one of the field theory that can be used as an approach to calculate the electromagnetic distribution on the electrical conductor. This paper discussed electric field modeling around power transformator by using Matlab to find the safety distance. The safe distance threshold of the electric field to human health refers to WHO and SNI was 5 kV/m. The specification of the power transformator was three phases, 150/20 kV, and 100 MVA. The basic concept is to change the distribution charge on the conductor or dielectric polarization charge with a set of discrete fictitious charge. The value of discrete fictitious charge was equivalent to the potential value of the conductor, and became a reference to calculate the electric field around the surface contour of the selected power transformator. The measurement distance was 5 meter on each side of the transformator surface. The results showed that the magnitude of the electric field at the front side was 5541 V/m, exceeding the safety limits.

  3. Power system for tokamak fusion experiments. Motor generator with flywheel effect

    International Nuclear Information System (INIS)

    Miyachi, Kengo

    1997-01-01

    JT-60 requires an enormous electric power pulse about 1,300 MVA periodically for its plasma initiation, containment and heating. JT-60 could not receive all electric power from a commercial line for plasma experiment except about 160 MVA because the 275 kV commercial line has some limitations. Therefore JT-60 needs huge electric power sources. The power supply system of JT-60 has 3 motor generators (MG). The total capacity of MG is 1,115 MVA that consists of a toroidal MG (TMG), poloidal MG (PMG) and Heating power supply MG (HMG), and each MG has a huge flywheel effect. For example, TMG has a 4.02 GJ energy yield that consists of 6 disk flywheel. The total weight of flywheel of TMG is 650 ton. This report describes the structure, operating system, and maintenance history of 3 types of MG. (author)

  4. High power operation of the polyphase resonant converter modulator system for the spallation neutron source linear accelerator

    CERN Document Server

    Reass, W A; Baca, D M; Doss, J D; Gonzáles, J M; Gribble, R F; Trujillo, P G

    2003-01-01

    The spallation neutron source (SNS) is a new 1.4 MW average power beam, 1 GeV accelerator being built at Oak Ridge national laboratory. The accelerator requires 15 "long-pulse" converter-modulator stations each providing a maximum of 11 MW pulses with a 1.1 MW average power. Two variants of the converter-modulator are utilized, an 80 kV and a 140 kV design, the voltage dependant on the type of klystron load. The converter-modulator can be described as a resonant zero-voltage- switching polyphase boost inverter. As noted in Figure 1, each converter modulator derives its buss voltage from a standard 13.8 kV to 2100 Y (1.5 MVA) substation cast-core transformer. The substation also contains harmonic traps and filters to accommodate IEEE 519 and 141 regulations. Each substation is followed by an SCR preregulator to accommodate system voltage changes from no load to full load, in addition to providing a soft-start function. Energy storage and filtering is provided by special low inductance self-clearing metallized ...

  5. Analysis of three-phase power-supply systems using computer-aided design programs

    International Nuclear Information System (INIS)

    Oberst, E.F.

    1977-01-01

    A major concern of every designer of large, three-phase power-supply systems is the protection of system components from overvoltage transients. At present, three computer-aided circuit design programs are available in the Magnetic Fusion Energy (MFE) National Computer Center that can be used to analyze three-phase power systems: MINI SCEPTRE, SPICE I, and SPICE II. These programs have been used at Lawrence Livermore Laboratory (LLL) to analyze the operation of a 200-kV dc, 20-A acceleration power supply for the High Voltage Test Stand. Various overvoltage conditions are simulated and the effectiveness of system protective devices is observed. The simulated overvoltage conditions include such things as circuit breaker openings, pulsed loading, and commutation voltage surges in the rectifiers. These examples are used to illustrate the use of the computer-aided, circuit-design programs discussed in this paper

  6. β-Secretase BACE1 Promotes Surface Expression and Function of Kv3.4 at Hippocampal Mossy Fiber Synapses.

    Science.gov (United States)

    Hartmann, Stephanie; Zheng, Fang; Kyncl, Michele C; Karch, Sandra; Voelkl, Kerstin; Zott, Benedikt; D'Avanzo, Carla; Lomoio, Selene; Tesco, Giuseppina; Kim, Doo Y; Alzheimer, Christian; Huth, Tobias

    2018-04-04

    The β-secretase β-site APP-cleaving enzyme 1 (BACE1) is deemed a major culprit in Alzheimer's disease, but accumulating evidence indicates that there is more to the enzyme than driving the amyloidogenic processing of the amyloid precursor protein. For example, BACE1 has emerged as an important regulator of neuronal activity through proteolytic and, most unexpectedly, also through nonproteolytic interactions with several ion channels. Here, we identify and characterize the voltage-gated K + channel 3.4 (Kv3.4) as a new and functionally relevant interaction partner of BACE1. Kv3.4 gives rise to A-type current with fast activating and inactivating kinetics and serves to repolarize the presynaptic action potential. We found that BACE1 and Kv3.4 are highly enriched and remarkably colocalized in hippocampal mossy fibers (MFs). In BACE1 -/- mice of either sex, Kv3.4 surface expression was significantly reduced in the hippocampus and, in synaptic fractions thereof, Kv3.4 was specifically diminished, whereas protein levels of other presynaptic K + channels such as K Ca 1.1 and K Ca 2.3 remained unchanged. The apparent loss of presynaptic Kv3.4 affected the strength of excitatory transmission at the MF-CA3 synapse in hippocampal slices of BACE1 -/- mice when probed with the Kv3 channel blocker BDS-I. The effect of BACE1 on Kv3.4 expression and function should be bidirectional, as predicted from a heterologous expression system, in which BACE1 cotransfection produced a concomitant upregulation of Kv3.4 surface level and current based on a physical interaction between the two proteins. Our data show that, by targeting Kv3.4 to presynaptic sites, BACE1 endows the terminal with a powerful means to regulate the strength of transmitter release. SIGNIFICANCE STATEMENT The β-secretase β-site APP-cleaving enzyme 1 (BACE1) is infamous for its crucial role in the pathogenesis of Alzheimer's disease, but its physiological functions in the intact nervous system are only gradually

  7. Kv1 channels and neural processing in vestibular calyx afferents

    Directory of Open Access Journals (Sweden)

    Frances L Meredith

    2015-06-01

    Full Text Available Potassium-selective ion channels are important for accurate transmission of signals from auditory and vestibular sensory end organs to their targets in the central nervous system. During different gravity conditions, astronauts experience altered input signals from the peripheral vestibular system resulting in sensorimotor dysfunction. Adaptation to altered sensory input occurs, but it is not explicitly known whether this involves synaptic modifications within the vestibular epithelia. Future investigations of such potential plasticity require a better understanding of the electrophysiological mechanisms underlying the known heterogeneity of afferent discharge under normal conditions. This study advances this understanding by examining the role of the Kv1 potassium channel family in mediating action potentials in specialized vestibular afferent calyx endings in the gerbil crista and utricle. Pharmacological agents selective for different sub-types of Kv1 channels were tested on membrane responses in whole cell recordings in the crista. Kv1 channels sensitive to α-dendrotoxin and dendrotoxin-K were found to prevail in the central regions, whereas K+ channels sensitive to margatoxin, which blocks Kv1.3 and 1.6 channels, were more prominent in peripheral regions. Margatoxin-sensitive currents showed voltage-dependent inactivation. Dendrotoxin-sensitive currents showed no inactivation and dampened excitability in calyces in central neuroepithelial regions. The differential distribution of Kv1 potassium channels in vestibular afferents supports their importance in accurately relaying gravitational and head movement signals through specialized lines to the central nervous system. Pharmacological modulation of specific groups of K+ channels could help alleviate vestibular dysfunction on earth and in space.

  8. Kv1 channels and neural processing in vestibular calyx afferents.

    Science.gov (United States)

    Meredith, Frances L; Kirk, Matthew E; Rennie, Katherine J

    2015-01-01

    Potassium-selective ion channels are important for accurate transmission of signals from auditory and vestibular sensory end organs to their targets in the central nervous system. During different gravity conditions, astronauts experience altered input signals from the peripheral vestibular system resulting in sensorimotor dysfunction. Adaptation to altered sensory input occurs, but it is not explicitly known whether this involves synaptic modifications within the vestibular epithelia. Future investigations of such potential plasticity require a better understanding of the electrophysiological mechanisms underlying the known heterogeneity of afferent discharge under normal conditions. This study advances this understanding by examining the role of the Kv1 potassium channel family in mediating action potentials in specialized vestibular afferent calyx endings in the gerbil crista and utricle. Pharmacological agents selective for different sub-types of Kv1 channels were tested on membrane responses in whole cell recordings in the crista. Kv1 channels sensitive to α-dendrotoxin and dendrotoxin-K were found to prevail in the central regions, whereas K(+) channels sensitive to margatoxin, which blocks Kv1.3 and 1.6 channels, were more prominent in peripheral regions. Margatoxin-sensitive currents showed voltage-dependent inactivation. Dendrotoxin-sensitive currents showed no inactivation and dampened excitability in calyces in central neuroepithelial regions. The differential distribution of Kv1 potassium channels in vestibular afferents supports their importance in accurately relaying gravitational and head movement signals through specialized lines to the central nervous system. Pharmacological modulation of specific groups of K(+) channels could help alleviate vestibular dysfunction on earth and in space.

  9. The pan-Kv7 (KCNQ) Channel Opener Retigabine Inhibits Striatal Excitability by Direct Action on Striatal Neurons In Vivo

    DEFF Research Database (Denmark)

    Hansen, Henrik H; Weikop, Pia; Mikkelsen, Maria D

    2017-01-01

    Central Kv7 (KCNQ) channels are voltage-dependent potassium channels composed of different combinations of four Kv7 subunits, being differently expressed in the brain. Notably, striatal dopaminergic neurotransmission is strongly suppressed by systemic administration of the pan-Kv7 channel opener ...... by acute systemic haloperidol administration in the rat. The relative mRNA levels of Kv7 subunits in the rat striatum were found to be Kv7.2 = Kv7.3 = Kv7.5 > >Kv7.4. These data suggest that intrastriatal Kv7 channels play a direct role in regulating striatal excitability in vivo....

  10. Field Demonstration of a 24-kV Superconducting Cable at Detroit Edison

    International Nuclear Information System (INIS)

    Kelley, Nathan; Corsaro, Pietro

    2004-01-01

    Customer acceptance of high temperature superconducting (HTS) cable technology requires a substantial field demonstration illustrating both the system's technical capabilities and its suitability for installation and operation within the utility environment. In this project, the world's first underground installation of an HTS cable using existing ductwork, a 120 meter demonstration cable circuit was designed and installed between the 24 kV bus distribution bus and a 120 kV-24 kV transformer at Detroit Edison's Frisbie substation. The system incorporated cables, accessories, a refrigeration system, and control instrumentation. Although the system was never put in operation because of problems with leaks in the cryostat, the project significantly advanced the state-of-the-art in the design and implementation of Warm Dielectric cable systems in substation applications. Lessons learned in this project are already being incorporated in several ongoing demonstration projects

  11. New 30 kA power system at Fermilab and its use for measuring the effects of ripple current on the performance of superconducting high field magnets

    Energy Technology Data Exchange (ETDEWEB)

    Carcagno, R.; Feher, S.; Garvey, J.; Jaskierny, W.; Lamm, M.; Makulski, A.; Orris, D.F.; Pfeffer, H.; Tartaglia, M.; Tompkins, J.; Wolff, D.; /Fermilab

    2004-12-01

    A new 30 kA, 30 V dc Power System was designed, built, and commissioned at Fermilab for testing Superconducting High Field Magnets. This system has been successfully supporting operations at the Fermilab Magnet Test Facility since April 2002. It is based on six commercial 150 kW Power Energy Industries power supply modules and the following in-house modules: six 720 Hz filters, two 15 kA/1kV dc solid-state dump switch, and a 3 MJ/30 kA/1 kV dc dump resistor. Additional inhouse electronic components were designed and built to provide precise current regulation and distribution of current and current rate of change. An industrial-type Programmable Logic Controller system was used to provide equipment interlocks and monitoring. This paper summarizes studies on the influence of characteristics of this new power system--such as ripple current--on the performance of High Field Superconducting magnets.

  12. New 30 kA power system at Fermilab and its use for measuring the effects of ripple current on the performance of superconducting high field magnets

    International Nuclear Information System (INIS)

    Carcagno, R.; Feher, S.; Garvey, J.; Jaskierny, W.; Lamm, M.; Makulski, A.; Orris, D.F.; Pfeffer, H.; Tartaglia, M.; Tompkins, J.; Wolff, D.

    2004-01-01

    A new 30 kA, 30 V dc Power System was designed, built, and commissioned at Fermilab for testing Superconducting High Field Magnets. This system has been successfully supporting operations at the Fermilab Magnet Test Facility since April 2002. It is based on six commercial 150 kW Power Energy Industries power supply modules and the following in-house modules: six 720 Hz filters, two 15 kA/1kV dc solid-state dump switch, and a 3 MJ/30 kA/1 kV dc dump resistor. Additional in-house electronic components were designed and built to provide precise current regulation and distribution of current and current rate of change. An industrial-type Programmable Logic Controller system was used to provide equipment interlocks and monitoring. This paper summarizes studies on the influence of characteristics of this new power system--such as ripple current--on the performance of High Field Superconducting Magnets

  13. Design development and testing of high voltage power supply with crowbar protection for IOT based RF amplifier system in VECC

    Science.gov (United States)

    Thakur, S. K.; Kumar, Y.

    2018-05-01

    This paper described the detailed design, development and testing of high voltage power supply (‑30 kV, 3.2 A) and different power supplies for biasing electrodes of Inductive Output Tube (IOT) based high power Radio Frequency (RF) amplifier. This IOT based RF amplifier is further used for pursuing research and development activity in superconducting RF cavity project at Variable Energy Cyclotron Centre (VECC) Kolkata. The state-of-the-art technology of IOT-based high power RF amplifier is designed, developed, and tested at VECC which is the first of its kind in India. A high voltage power supply rated at negative polarity of 30 kV dc/3.2 A is required for biasing cathode of IOT with crowbar protection circuit. This power supply along with crowbar protection system is designed, developed and tested at VECC for testing the complete setup. The technical difficulties and challenges occured during the design of cathode power supply, its crowbar protection techniques along with other supported power supplies i.e. grid and ion pump power supplies are discussed in this paper.

  14. Parameter design and performance simulation of a 10 kV voltage compensation type active superconducting fault current limiter

    International Nuclear Information System (INIS)

    Chen, L.; Tang, Y.J.; Song, M.; Shi, J.; Ren, L.

    2013-01-01

    Highlights: •For a practical 10 kV system, the 10 kV active SFCL’s basic parameters are designed. •Under different fault conditions, the 10 kV active SFCL’s performances are simulated. •The designed 10 kV active SFCL’s engineering feasibility is discussed preliminarily. -- Abstract: Since the introduction of superconducting fault current limiter (SFCL) into electrical distribution system may be a good choice with economy and practicability, the parameter design and current-limiting characteristics of a 10 kV voltage compensation type active SFCL are studied in this paper. Firstly, the SFCL’s circuit structure and operation principle are presented. Then, taking a practical 10 kV distribution system as its application object, the SFCL’s basic parameters are designed to meet the system requirements. Further, using MATLAB, the detailed current-limiting performances of the 10 kV active SFCL are simulated under different fault conditions. The simulation results show that the active SFCL can deal well with the faults, and the parameter design’s suitability can be testified. At the end, in view of the engineering feasibility of the 10 kV active SFCL, some preliminary discussions are carried out

  15. LHC Power Distribution

    CERN Document Server

    Pedersen, J

    1999-01-01

    The power distribution for the LHC machine and its experiments will be realised making extensive use of the existing infrastructure for the LEP. The overall power requirement is approximately the same, about 125 MW. The load distribution will however change. The even points will loose in importance and the points 1 and 5 will, due to the installation of ATLAS and CMS, gain. A thorough reorganisation of the 18 kV distribution will thus be necessary. Due to the important cryogenic installations required for the LHC, the 3.3 kV distribution system, supplying mainly cryogenic compressors, will be extended with a number of new substations. The important number of new surface buildings, underground caverns and other underground structures all will receive general service installations: Lighting and power. The new injection tunnels will require complete installations: A.C. supplies for the power converters and for general service, and D.C. cabling for the magnets of the beam line. Special safe power installations ar...

  16. 250 kV aim for hvdc valves

    Energy Technology Data Exchange (ETDEWEB)

    1966-06-01

    Development now being carried out by ASEA is aimed at increasing the normal operating voltage for a mercury arc valve to 250 kV dc. The maximum direct voltage per valve group, with one valve in each arm of the bridge, is 125 kV for equipment already in operation in New Zealand, Japan, and Konti Scan. Valves for 130 kV and 133 kV operation are under construction for the Vancouver and the Pacific Intertie 1 links.

  17. Hvor fosser kvælstoffet hen?

    DEFF Research Database (Denmark)

    Larsen, Torben

    Der har i Ingeniøren inden i et par måneder kunne læses adskillelige ivrige indlæg om de danske fjordes evne til at fjerne kvælstof. Kvælstof fosser ud af fjordene? lød en af de første overskrifter. Få uger efter blev det stik modsatte synspunkt fremført under overskriften Fjordene holder på kvæl...

  18. Protection of control and monitoring equipment from electromagnetic noise in the 67 MJ, 50 kV capacitor bank

    Energy Technology Data Exchange (ETDEWEB)

    Galakhov, I V; Gasheev, A S; Grusin, I A; Gudov, S N; Kuz` michev, Yu P; Murugov, V M; Osin, V A; Pankratov, V I; Pegoev, I N [All-Russian Scientific Research Inst. of Experimental Physics, Sarov (Russian Federation)

    1997-12-31

    A discharge of the 67 MJ and 50 kV capacitor bank used as a pulsed power system for flashlamp pumping of ISKRA-5`s high-power iodine laser, involves control and diagnostic equipment being subjected to significant electromagnetic fields and electrical interference that will further develop through conductive circuits. The paper describes and validates design approaches to the grounding system, signal carriage and decoupling circuits that would result in lower interference both for the capacitor bank`s control and diagnostics systems. A summary is also given of the ten-years` practice in operating the control and diagnostics equipment during the facility experiments. (author). 1 tab., 3 refs.

  19. EVALUATING DEGREE OF ACTIVE POWER LOSSES REDUCTION IN THE ELECTRIC POWER LINES WITH REACTIVE POWER COMPENSATION

    Directory of Open Access Journals (Sweden)

    V. N. Radkevich

    2016-01-01

    Full Text Available The paper considers evaluation procedure for the degree of active power losses reduction in the power transmission lines under 1 kV and 6–10 kV of the systems of electric power supply of industrial enterprises with compensating installations mounted at the side of the customer. The capacitor installations conform to the applied voltage level and factor in dielectric losses in the capacitors. The voltage at the compensating device terminal changes from 0.95 to 1.05 of the capacitors nominal voltage. The study did not account for reactive power losses in the line, nor did it for its charge capacity, conditioned by relative shortness of the cable lines generally operating in the mains of industrial enterprises. For this reason, the quantities of reactive power being consumed and generated by the transmission line are negligible and do not significantly affect the reactive power flux. The researchers obtain functional relations that allow estimating the degree of power loss reduction in the transmission line factoring in its explicit initial data. They perform mathematical analysis of the obtained functional relations and study the function by means of derivatives. The function extremum points are found as well as the intervals of its increment and decrement. A graphical research of the obtained functional relation is performed. It is ascertained that reduction of the active power losses is contingent on the line and the capacitor-installation engineering factors, the electrical energy consumer reactive load value as well as the voltage applied to the capacitor installation. The functional relations presented in the article can be employed in scoping calculation necessary for decision making on the reactive power compensation in systems of the industrial facilities electric power supply. Their account will allow a more accurate estimate of technical and economic effect of the capacitor bank installation in the electrical mains under 1 kV and 6

  20. Advances in high voltage power switching with GTOs

    International Nuclear Information System (INIS)

    Podlesak, T.F.

    1990-01-01

    The control of high voltage at high power, particularly opening switches, has been difficult in the past. Using gate turnoff thyristors (GTOs) arranged in series enables large currents to be switched at high voltage. The authors report a high voltage opening switch has been successfully demonstrated. This switch uses GTOs in series and successfully operates at voltages higher than the rated voltage of the individual devices. It is believed that this is the first time this has been successfully demonstrated, in that GTOs have been operated in series before, but always in a manner as to not exceed the voltage capability of the individual devices. In short, the devices have not worked together, sharing the voltage, but one device has been operated using several backup devices. Of particular interest is how well the individual devices share the voltage applied to them. Equal voltage sharing between devices is absolutely essential, in order to not exceed the voltage rating of any of the devices in the series chain. This is accomplished at high (microsecond) switching speeds. Thus, the system is useful for high frequency applications as well as high power, making for a flexible circuit system element. This demonstration system is rated at 5 KV and uses 1 KV devices. A larger 24 KV system is under design and will use 4.5 KV devices. In order to design the 24 KV switch, the safe operating area of the large devices must be known thoroughly

  1. A robust and stable PLC based control system for 40kJ/25kV EMM system

    Energy Technology Data Exchange (ETDEWEB)

    Sharma, Vijay; Saroj, P.C.; Kulkarni, M.R.; Kumar, Satendra, E-mail: vijay9819420563@gmail.com [Accelerator and Pulse Power Division, Bhabha Atomic Research Centre, Mumbai (India)

    2014-07-01

    This paper describes the PLC based control system developed for a 40kJ/25kV Electro-magnetic machining (EMM) system. In EMM system large capacitor banks is charged with high voltage to store large energy and the banks is made to discharge into a coil within few milli-seconds using a triggered spark gaps. During discharge of the capacitor large surges and transients are generated in the system. The control system monitors/controls and interlocks all the units of the system for proper operation. The control system is the only subsystem which is electrically connected to all the low and high voltage subsystems. Care should be taken at the signal interfacing with the control system to protect the control system. (author)

  2. A robust and stable PLC based control system for 40kJ/25kV EMM system

    International Nuclear Information System (INIS)

    Sharma, Vijay; Saroj, P.C.; Kulkarni, M.R.; Kumar, Satendra

    2014-01-01

    This paper describes the PLC based control system developed for a 40kJ/25kV Electro-magnetic machining (EMM) system. In EMM system large capacitor banks is charged with high voltage to store large energy and the banks is made to discharge into a coil within few milli-seconds using a triggered spark gaps. During discharge of the capacitor large surges and transients are generated in the system. The control system monitors/controls and interlocks all the units of the system for proper operation. The control system is the only subsystem which is electrically connected to all the low and high voltage subsystems. Care should be taken at the signal interfacing with the control system to protect the control system. (author)

  3. Short-Circuit Degradation of 10-kV 10-A SiC MOSFET

    DEFF Research Database (Denmark)

    Eni, Emanuel-Petre; Beczkowski, Szymon; Munk-Nielsen, Stig

    2017-01-01

    The short-circuit behavior of power devices is highly relevant for converter design and fault protection. In this work, the degradation during short-circuit of a 10 kV 10 A 4H-SiC MOSFET is investigated at 6 kV DC-link voltage. The study aims to present the behavior of the device during short-circuit...... transients as it sustains increasing short-circuit pulses during its life-time. As the short-circuit pulse length increases, degradation of the device can be observed in periodically performed characterizations. The initial degradation seems to be associated with the channel region, and continuous stressing...

  4. Facing the challenges of distribution systems operation with high wind power penetration

    DEFF Research Database (Denmark)

    Das, Kaushik; Altin, Müfit; Hansen, Anca Daniela

    2017-01-01

    power flow in 60kV distribution networks through controlling the ability of wind power plants (WPPs) to generate or absorb reactive power. This paper aims to understand the characteristics of a distribution network with high penetration of distributed generation. A detailed analysis of the active...... and reactive power flows in a real distribution network under different wind and load conditions based on actual measurements is performed in order to understand the correlation between the consumption, wind power production, and the network losses. Conclusive remarks are presented, briefly expressing......This paper addresses the challenges associated with the operation of a distribution system with high penetration of wind power. The paper presents some preliminary investigations of an ongoing Danish research work, which has as main objective to reduce the network losses by optimizing the reactive...

  5. Recent developments in high average power driver technology

    International Nuclear Information System (INIS)

    Prestwich, K.R.; Buttram, M.T.; Rohwein, G.J.

    1979-01-01

    Inertial confinement fusion (ICF) reactors will require driver systems operating with tens to hundreds of megawatts of average power. The pulse power technology that will be required to build such drivers is in a primitive state of development. Recent developments in repetitive pulse power are discussed. A high-voltage transformer has been developed and operated at 3 MV in a single pulse experiment and is being tested at 1.5 MV, 5 kj and 10 pps. A low-loss, 1 MV, 10 kj, 10 pps Marx generator is being tested. Test results from gas-dynamic spark gaps that operate both in the 100 kV and 700 kV range are reported. A 250 kV, 1.5 kA/cm 2 , 30 ns electron beam diode has operated stably for 1.6 x 10 5 pulses

  6. Effects of haloperidol on Kv4.3 potassium channels.

    Science.gov (United States)

    Lee, Hong Joon; Sung, Ki-Wug; Hahn, Sang June

    2014-10-05

    Haloperidol is commonly used in clinical practice to treat acute and chronic psychosis, but it also has been associated with adverse cardiovascular events. We investigated the effects of haloperidol on Kv4.3 currents stably expressed in CHO cells using a whole-cell patch-clamp technique. Haloperidol did not significantly inhibit the peak amplitude of Kv4.3, but accelerated the decay rate of inactivation of Kv4.3 in a concentration-dependent manner. Thus, the effects of haloperidol on Kv4.3 were estimated from the integral of the Kv4.3 currents during the depolarization pulse. The Kv4.3 was decreased by haloperidol in a concentration-dependent manner with an IC50 value of 3.6 μM. Haloperidol accelerated the decay rate of Kv4.3 inactivation and activation kinetics in a concentration-dependent manner, thereby decreasing the time-to-peak. Haloperidol shifted the voltage dependence of the steady-state activation and inactivation of Kv4.3 in a hyperpolarizing direction. Haloperidol also caused an acceleration of the closed-state inactivation of Kv4.3. Haloperidol produced a use-dependent block of Kv4.3, which was accompanied by a slowing of recovery from the inactivation of Kv4.3. These results suggest that haloperidol blocks Kv4.3 by both interacting with the open state of Kv4.3 channels during depolarization and accelerating the closed-state inactivation at subthreshold membrane potentials. Copyright © 2014 Elsevier B.V. All rights reserved.

  7. A continuous acceleration tube of ions under 200 KV; Un tube d'acceleration continue d'ions sous 200 KV

    Energy Technology Data Exchange (ETDEWEB)

    Mongodin, G [Commissariat a l' Energie Atomique, Saclay (France). Centre d' Etudes Nucleaires

    1954-07-01

    The realization of an Van de Graaff accelerator required, for the preliminary studies, the construction of a small proton accelerator, functioning at 200 kV in order to resolve some parasitic effects inherent to the accelerators tubes. The aim of this report is to describe the different organs of the accelerator tube, to explain the operating system and to encode their characteristics. The report first presents the ion source and the beam buncher permitting to inject in the accelerator tube particles of about 9 kV and very batched in a thin beam of circular section. Then the study explain the tube characteristics considered like optic system. A method to obtain precise calculation of particle trajectories is exposed. Aberrations of the system were discussed and balance of the currents on all electrodes inside the tube for different regimes of working were provided. The influence of the residual pressure in the tube were explained. The report finally ends on a part of the fundamental problem of the straining occurring inside the tubes accelerators under high tension. (M.B.) [French] La realisation d n accelerateur du type Van de Graaff a necessite, entre autres etudes preliminaires, la construction d'un petit accelerateur de protons, fonctionnant sous 200 kV afin d'eclaircir certains effets parasites propres aux tubes accelerateurs. L'objet de ce rapport est de decrire les differents organes du tube accelerateur, d'en expliquer le fonctionnement et de chiffrer leurs caracteristiques. Le memoire presente d'abord la source d'ions et le canon permettant d'injecter dans le tube accelerateur des particules de 9 kV environ et bien groupees dans un faisceau fin de section circulaire. Puis il passe a l'etude du tube considere comme systeme optique. Une methode utilisee pour le calcul precis des trajectoires des particules y est exposee. Il aborde le probleme des aberrations de ce systeme et fournit par la suite le bilan des courants sur toutes les electrodes a l

  8. Normalized Noise Power Spectrum of Full Field Digital Mammography System

    International Nuclear Information System (INIS)

    Isa, Norriza Mohd; Wan Hassan, Wan Muhamad Saridan

    2010-01-01

    A method to measure noise power spectrum of a full field digital mammography system is presented. The effect of X-ray radiation dose, size and configuration of region of interest on normalized noise power spectrum (NNPS) was investigated. Flat field images were acquired using RQA-M2 beam quality technique (Mo/Mo anode-filter, 28 kV, 2 mm Al) with different clinical radiation doses. The images were cropped at about 4 cm from the edge of the breast wall and then divided into different size of non-overlapping or overlapping segments. NNPS was determined through detrending, 2-D fast Fourier transformation and normalization. Our measurement shows that high radiation dose gave lower NNPS at a specific beam quality.

  9. Wild Horse 69-kV transmission line environmental assessment

    International Nuclear Information System (INIS)

    1996-12-01

    Hill County Electric Cooperative Inc. (Hill County) proposes to construct and operate a 69-kV transmission line from its North Gildford Substation in Montana north to the Canadian border. A vicinity project area map is enclosed as a figure. TransCanada Power Corporation (TCP), a Canadian power-marketing company, will own and construct the connecting 69-kV line from the international border to Express Pipeline's pump station at Wild Horse, Alberta. This Environmental Assessment is prepared for the Department of Energy (DOE) as lead federal agency to comply with the requirements of the National Environmental Policy Act (NEPA), as part of DOE's review and approval process of the applications filed by Hill County for a DOE Presidential Permit and License to Export Electricity to a foreign country. The purpose of the proposed line is to supply electric energy to a crude oil pump station in Canada, owned by Express Pipeline Ltd. (Express). The pipeline would transport Canadian-produced oil from Hardisty, Alberta, Canada, to Caster, Wyoming. The Express Pipeline is scheduled to be constructed in 1996--97 and will supply crude oil to refineries in Wyoming and the midwest

  10. Wild Horse 69-kV transmission line environmental assessment

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1996-12-01

    Hill County Electric Cooperative Inc. (Hill County) proposes to construct and operate a 69-kV transmission line from its North Gildford Substation in Montana north to the Canadian border. A vicinity project area map is enclosed as a figure. TransCanada Power Corporation (TCP), a Canadian power-marketing company, will own and construct the connecting 69-kV line from the international border to Express Pipeline`s pump station at Wild Horse, Alberta. This Environmental Assessment is prepared for the Department of Energy (DOE) as lead federal agency to comply with the requirements of the National Environmental Policy Act (NEPA), as part of DOE`s review and approval process of the applications filed by Hill County for a DOE Presidential Permit and License to Export Electricity to a foreign country. The purpose of the proposed line is to supply electric energy to a crude oil pump station in Canada, owned by Express Pipeline Ltd. (Express). The pipeline would transport Canadian-produced oil from Hardisty, Alberta, Canada, to Caster, Wyoming. The Express Pipeline is scheduled to be constructed in 1996--97 and will supply crude oil to refineries in Wyoming and the midwest.

  11. Measurement ot the switching over-voltages at the disconnection of the high voltage shunt reactors in the Romanian power system

    Energy Technology Data Exchange (ETDEWEB)

    Stroica, Paul Constantin; Merfu, Ion; Stroica, Mihail; Merfu, Marius; Cojocaru, Florian; Stefan, Dinu; Cojocaru, Mihai

    2010-09-15

    The paper presents the measurements of the switching over-voltages made in the Romanian Power System, at the 400/220/110 kV Urechesti substation at the disconnection of a 400 kV, 100 MVAr shunt reactor type DFAL, Siemens, Germany, in 3 consecutive versions. The first one is for shunt reactor controlled by live-tank oil circuit breaker, the second one is for shunt reactor controlled by SF6 circuit breaker, and the third one is for shunt reactor controlled by SF6 circuit breaker and synchronize device.

  12. Study of a phase-to-ground fault on a 400 kV overhead transmission line

    Science.gov (United States)

    Iagăr, A.; Popa, G. N.; Diniş, C. M.

    2018-01-01

    Power utilities need to supply their consumers at high power quality level. Because the faults that occur on High-Voltage and Extra-High-Voltage transmission lines can cause serious damages in underlying transmission and distribution systems, it is important to examine each fault in detail. In this work we studied a phase-to-ground fault (on phase 1) of 400 kV overhead transmission line Mintia-Arad. Indactic® 650 fault analyzing system was used to record the history of the fault. Signals (analog and digital) recorded by Indactic® 650 were visualized and analyzed by Focus program. Summary of fault report allowed evaluation of behavior of control and protection equipment and determination of cause and location of the fault.

  13. Detailed design of a 13 kA 13 kV dc solid-state turn-off switch

    International Nuclear Information System (INIS)

    Praeg, W.F.

    1985-01-01

    An experimental facility for the study of electromagnetic effects in the First Wall-Blanket-shield (FWBS) systems of fusion reactors has been constructed at Argonne National Laboratory (ANL). In a test volume of 0.76 m 3 , a vertical, pulsed 5 kG dipole field (B -1 ) is perpendicular to a 10 kG solenoid field. Power supplies of 2.75 MW at 550 V dc and 5.5 MW at 550 V dc and a solid-state switch rated at 13 kA and 13 kV (169 MW) control the pulsed magnetic fields. The total stored energy in the coils is 2.6 MJ. This paper describes the design and construction features of the solid-state switching circuit which turns off a dc of 13 kA in approximately 82 μs and holds off voltages of < 13 kV

  14. Design study of an AC power supply system in JT-60SA

    International Nuclear Information System (INIS)

    Shimada, Katsuhiro; Baulaigue, Olivier; Cara, Philippe; Coletti, Alberto; Coletti, Roberto; Matsukawa, Makoto; Terakado, Tsunehisa; Yamauchi, Kunihito

    2011-01-01

    In the initial research phase of JT-60SA, which is the International Thermonuclear Experimental Reactor (ITER) satellite Tokamak with superconducting toroidal and poloidal magnetic field coils, the plasma heating operation of 30 MW-60 s or 20 MW-100 s is planned for 5.5 MA single null divertor plasmas. To achieve this operation, AC power source of the medium voltage of 18 kV and ∼7 GJ has to be provided in total to the poloidal field coil power supplies and additional heating devices such as neutral beam injection (NBI) and electron cyclotron radio frequency (ECRF). In this paper, the proposed AC power supply system in JT-60SA was estimated from the view point of available power, and harmonic currents based on the standard plasma operation scenario during the initial research phase. This AC power supply system consists of the reused JT-60 power supply facilities including motor generators with flywheel, AC breakers, harmonic filters, etc., to make it cost effective. In addition, the conceptual design of the upgraded AC power supply system for the ultimate heating power of 41 MW-100 s in the extended research phase is also described.

  15. Proposal to amend existing operating permit for the Ault-Craig 345-kV and Hayden-Archer 230-kV transmission lines, Routt, Jackson and Larimer Counties, Colorado

    International Nuclear Information System (INIS)

    1997-08-01

    The Western Area Power Administration, Rocky Mountain Region, is proposing to amend an existing US Forest Service operating permit for the Ault-Craig 345-kV and Hayden-Archer 230-kV transmission lines, which are located in Routt, jackson, and Larimer counties, Colorado. These transmission lines cross portions of the Roosevelt and Routt National Forests. The long-term use authorization Western is requesting from the Forest Service would be for the life of the Ault-Craig and Hayden-Archer transmission lines. This environmental assessment addresses those access road and right-of-way maintenance activities identified by Western that would be performed on Forest Service managed lands during the next approximately five years

  16. Proposal to amend existing operating permit for the Ault-Craig 345-kV and Hayden-Archer 230-kV transmission lines, Routt, Jackson and Larimer Counties, Colorado

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1997-08-01

    The Western Area Power Administration, Rocky Mountain Region, is proposing to amend an existing US Forest Service operating permit for the Ault-Craig 345-kV and Hayden-Archer 230-kV transmission lines, which are located in Routt, jackson, and Larimer counties, Colorado. These transmission lines cross portions of the Roosevelt and Routt National Forests. The long-term use authorization Western is requesting from the Forest Service would be for the life of the Ault-Craig and Hayden-Archer transmission lines. This environmental assessment addresses those access road and right-of-way maintenance activities identified by Western that would be performed on Forest Service managed lands during the next approximately five years.

  17. Development of highly repetitive pulse power system using amorphous metallic cores

    Energy Technology Data Exchange (ETDEWEB)

    Masugata, K; Yatsui, K [Nagaoka Univ. of Technology (Japan). Dept. of Electrical Engineering

    1997-12-31

    A new type of pulse power system has been developed to obtain an efficient highly repetitive pulse-power generation. The system is constructed of a double pulse circuit (1st stage), step-up transformer and Blumlein pulse forming line (BL) and can generate high power pulse of 600 kV, 24 kA, 60 ns. In the system, discharge gap switches are replaced by magnetic switches. In addition, instead of Marx generator, a step-up transformer is utilized to generate high voltage pulse. The system is tested under the double pulse mode where two 1st stage capacitors are connected in parallel and switched with a interval of T{sub d}. The minimum value of T{sub d} is limited by the recovery of 1st stage gap switches and at T{sub d} {>=} 500 {mu}s (equivalent rep-rate of 2 kHz), the system is operated with good reproducibility. To enhance the recovery, magnetic switch is utilized, which enables operation at T{sub d} {>=} 30 {mu}s (equivalent rep-rate of 33 kHz). (author). 7 figs., 7 refs.

  18. Improvement of the 400 kV linac electron source of AmPS

    International Nuclear Information System (INIS)

    Kroes, F.B.; Beuzekom, M.G. van; Dobbe, N.J.; Es, J.T. van; Jansweijer, P.P.M.; Kruijer, A.H.; Luigjes, G.; Sluijk, T.G.B.

    1992-01-01

    An existing linac (MEA) injects electrons into the Amsterdam Pulse Stretcher (AmPS) ring. The linac's peak current increases from 20 to 80 mA. This requires the modification of the 400 kV low emittance gun. The fourfold increase of the peak current is obtained by doubling both the gun perveance (new gun part) and the pulsed extractor voltage. To obtain optimum beam quality over this increased current range, the hot deck electronics has been exchanged by a fast high voltage FET switching supply. A built-in microprocessor, coupled to the local computer by optical fibers, is used to monitor and control the gun parameters. The 5 kV gun extractor voltage pulse shape can be monitored by means of an analog fibre transducer with build in calibration. Finally, in order to improve the energy stability of the accelerated electrons, a serial electron-tube stabilizer was added to the 400 kV DC power supply. (K.A.) 4 refs.; 6 figs

  19. Comparing Effects of TCR and TSC on MHO Distance Protection Setting in 400 kV Algerian Transmission Line

    Directory of Open Access Journals (Sweden)

    Mohamed ZELLAGUI

    2012-11-01

    Full Text Available This paper presents a study on the performances of distance relays setting in 400 kV in Eastern Algerian transmission networks at Sonelgaz Group (Algerian company of Electrical and Gas compensated by shunt Flexible AC Transmission System (FACTS. The facts are used for controlling transmission voltage, power flow, reactive power, and damping of power system oscillations in high power transfer levels. The effects of SVC devices i.e. Thyristor Controlled Reactor (TCR and the Thyristor Switched Capacitors (TSC insertion, on the total impedance of a transmission line protected by MHO distance relay are investigated. The modified setting zones protections for three forward zones (Z1, Z2 and Z3 have been calculated in order to improve the performances of distance relay protection and prevent circuit breaker nuisance tripping.

  20. Increase in the number of distributed power generation installations in electricity distribution grids - Simulation in a 16 kV medium-voltage network; Zunahme der dezentralen Energieerzeugungsanlagen in elektrischen Verteilnetzen: Simulationen im 16 kV Mittelspannungsnetz des AEW

    Energy Technology Data Exchange (ETDEWEB)

    Hoeckel, M.; Luechinger, P.

    2003-07-01

    This is the seventh part of a ten-part final report for the Swiss Federal Office of Energy (SFOE) on a project that looked into potential problems relating to the Swiss electricity distribution grid with respect to the increasing number of distributed power generation facilities being put into service. The identification of special conditions for the grid's operation and future development that take increasing decentralised power production into account are discussed. The results of the project activities encompass the analysis and evaluation of various problem areas associated with planning and management of the grid during normal operation and periods of malfunction, as well as required modifications to safety systems and grid configurations. This sixth appendix to the main report presents and discusses the results of simulations made on the basis of the real-life 16 kV medium-voltage distribution network operated by the Aargovian electricity utility AEW. This appendix describes the simulation methods used and the basic characteristics of medium-voltage networks and distributed generation facilities. Different types of load profiles, including domestic and industrial loads, are discussed. The results of the simulations are presented in graphical form and provide profiles of voltage and current, active and reactive power and further mains characteristics for varying load conditions. Also, daily profiles for situations with and without distributed generation are presented and short-circuit simulations and grid dynamics are discussed.

  1. Advanced electrical power system technology for the all electric aircraft

    Science.gov (United States)

    Finke, R. C.; Sundberg, G. R.

    1983-01-01

    The application of advanced electric power system technology to an all electric airplane results in an estimated reduction of the total takeoff gross weight of over 23,000 pounds for a large airplane. This will result in a 5 to 10 percent reduction in direct operating costs (DOC). Critical to this savings is the basic electrical power system component technology. These advanced electrical power components will provide a solid foundation for the materials, devices, circuits, and subsystems needed to satisfy the unique requirements of advanced all electric aircraft power systems. The program for the development of advanced electrical power component technology is described. The program is divided into five generic areas: semiconductor devices (transistors, thyristors, and diodes); conductors (materials and transmission lines); dielectrics; magnetic devices; and load management devices. Examples of progress in each of the five areas are discussed. Bipolar power transistors up to 1000 V at 100 A with a gain of 10 and a 0.5 microsec rise and fall time are presented. A class of semiconductor devices with a possibility of switching up to 100 kV is described. Solid state power controllers for load management at 120 to 1000 V and power levels to 25 kW were developed along with a 25 kW, 20 kHz transformer weighing only 3.2 kg. Previously announced in STAR as N83-24764

  2. Advanced electrical power system technology for the all electric aircraft

    Science.gov (United States)

    Finke, R. C.; Sundberg, G. R.

    1983-01-01

    The application of advanced electric power system technology to an all electric airplane results in an estimated reduction of the total takeoff gross weight of over 23,000 pounds for a large airplane. This will result in a 5 to 10 percent reduction in direct operating costs (DOC). Critical to this savings is the basic electrical power system component technology. These advanced electrical power components will provide a solid foundation for the materials, devices, circuits, and subsystems needed to satisfy the unique requirements of advanced all electric aircraft power systems. The program for the development of advanced electrical power component technology is described. The program is divided into five generic areas: semiconductor devices (transistors, thyristors, and diodes); conductors (materials and transmission lines); dielectrics; magnetic devices; and load management devices. Examples of progress in each of the five areas are discussed. Bipolar power transistors up to 1000 V at 100 A with a gain of 10 and a 0.5 microsec rise and fall time are presented. A class of semiconductor devices with a possibility of switching up to 100 kV is described. Solid state power controllers for load management at 120 to 1000 V and power levels to 25 kW were developed along with a 25 kW, 20 kHz transformer weighing only 3.2 kg.

  3. Combined kV and MV imaging for real-time tracking of implanted fiducial markers

    International Nuclear Information System (INIS)

    Wiersma, R. D.; Mao Weihua; Xing, L.

    2008-01-01

    In the presence of intrafraction organ motion, target localization uncertainty can greatly hamper the advantage of highly conformal dose techniques such as intensity modulated radiation therapy (IMRT). To minimize the adverse dosimetric effect caused by tumor motion, a real-time knowledge of the tumor position is required throughout the beam delivery process. The recent integration of onboard kV diagnostic imaging together with MV electronic portal imaging devices on linear accelerators can allow for real-time three-dimensional (3D) tumor position monitoring during a treatment delivery. The aim of this study is to demonstrate a near real-time 3D internal fiducial tracking system based on the combined use of kV and MV imaging. A commercially available radiotherapy system equipped with both kV and MV imaging systems was used in this work. A hardware video frame grabber was used to capture both kV and MV video streams simultaneously through independent video channels at 30 frames per second. The fiducial locations were extracted from the kV and MV images using a software tool. The geometric tracking capabilities of the system were evaluated using a pelvic phantom with embedded fiducials placed on a moveable stage. The maximum tracking speed of the kV/MV system is approximately 9 Hz, which is primarily limited by the frame rate of the MV imager. The geometric accuracy of the system is found to be on the order of less than 1 mm in all three spatial dimensions. The technique requires minimal hardware modification and is potentially useful for image-guided radiation therapy systems

  4. A capacitive level shifter for high voltage (2.5kV)

    DEFF Research Database (Denmark)

    Andersen, Thomas; Andersen, Michael A. E.; Thomsen, Ole Cornelius

    2012-01-01

    with focus on low power consumption as well as low capacitive load between the floating half-bridge node and ground (output capacitance). The operation of the level-shifter is tested and verified by measurements on a prototype half-bridge gate driver. Results conclude stabile operation at 2.44kV, 50k...

  5. 735 kV circuit breakers for ehv

    Energy Technology Data Exchange (ETDEWEB)

    1966-01-01

    French manufacturers have been studying the design of high and extra high voltage circuit breakers for several years. The two techniques they used were the low volume oil and the air pressure technique. These have permitted the development of a type gear capable of solving problems all over the world as they arose following the development of electrical energy transmission at extra high voltage as well as high short circuit power. Today, the air pressure solution is used in new constructions such as the 735 kV transmission network in Canada.

  6. Prototype tests on the ion source power supplies of the TEXTOR NI-system

    International Nuclear Information System (INIS)

    Goll, O.; Braunsberger, U.; Schwarz, U.

    1987-01-01

    The PINI ion source for the TEXTOR neutral injector is fed by a new modular transistorized power supply. All modules are located in a high voltage cage on 55 kV dc against ground. The normal operation of the injectors includes frequent grid breakdowns causing transient high voltage stresses on the ion source power supplies. These stresses must not disturb the safe operation of the power supplies. The paper describes the set up for extensive testing of a supply prototype module under the expected operating conditions. The main features of this test program are reviewed and the measures taken for a safe operation are discussed. As a result of the investigations, recommendations for the installation of the power supplies at the TEXTOR NI system are given

  7. Kv7 channels can function without constitutive calmodulin tethering.

    Directory of Open Access Journals (Sweden)

    Juan Camilo Gómez-Posada

    Full Text Available M-channels are voltage-gated potassium channels composed of Kv7.2-7.5 subunits that serve as important regulators of neuronal excitability. Calmodulin binding is required for Kv7 channel function and mutations in Kv7.2 that disrupt calmodulin binding cause Benign Familial Neonatal Convulsions (BFNC, a dominantly inherited human epilepsy. On the basis that Kv7.2 mutants deficient in calmodulin binding are not functional, calmodulin has been defined as an auxiliary subunit of Kv7 channels. However, we have identified a presumably phosphomimetic mutation S511D that permits calmodulin-independent function. Thus, our data reveal that constitutive tethering of calmodulin is not required for Kv7 channel function.

  8. Normalized noise power spectrum of full field digital mammography system

    International Nuclear Information System (INIS)

    Norriza Mohd Isa; Wan Muhamad Saridan Wan Hassan

    2009-01-01

    A method to measure noise power spectrum of a full field digital mammography system is presented. The effect of X-ray radiation dose, size and configuration of region of interest on normalized noise power spectrum (NNPS) was investigated. Flat field images were acquired using RQA-M2 beam quality technique (Mo/Mo anode-filter, 28 kV, 2 mm Al) with different clinical radiation doses. The images were cropped at about 4 cm from the edge of the breast wall and then divided into different size of non-overlapping or overlapping segments. NNPS was determined through detrending, 2-D fast Fourier transformation and normalization. Our measurement shows that high radiation dose gave lower NNPS at a specific beam quality. (Author)

  9. BPA/Puget Power Northwest Washington Transmission Project. Supplemental Draft Environmental Impact Statement

    International Nuclear Information System (INIS)

    1995-04-01

    Bonneville Power Administration and Puget Sound Power ampersand Light Company propose to upgrade the existing high-voltage transmission system in the Whatcom and Skagit County area between the towns of Custer and Sedro Woolley, including within the City of Bellingham, starting in 1995. The upgrades of the interconnected 230-kV and 115-kV systems are needed to increase the import capacity on a nearby U.S.-Canada 500-kV intertie by about 850 megawatts (MW). BPA and Puget Power would share the increase in north-south transfer capability. An existing BPA 230-kV single-circuit, wood-pole H-frame transmission line would be upgraded to a 230-kV lattice-steel double-circuit line. A Draft Environmental Impact Statement (DEIS) for the project was issued in November 1993. New 1994 studies showed that other improvements to Puget Power's system, and the addition of local generation has lessened local reliability problems. Also in 1994, BPA reevaluated all existing projects with this goal in mind. BPA and Puget determined that benefits would still result from this project, and that additional transfer capacity and improved system integrity warrant the expenditures. Given the changes in need, BPA decided to issue a Supplemental DEIS, and provide a second public review-and-comment period. The proposed action is designated Option 1. Impacts would be low to moderate and localized. Effects on soils and water resources in sensitive areas would be low to moderate; there would be little increase in magnetic fields, noise levels would approximate existing levels; and land use and property value impacts would be low. Threatened and endangered species would not be adversely affected, and all proposed Sections in wetlands would be covered by Nationwide Permit. Visual and socioeconomic impacts would be low to moderate. No cultural resources listed on the National Register of Historic Places would be affected

  10. Deletion of the Kv2.1 delayed rectifier potassium channel leads to neuronal and behavioral hyperexcitability

    Science.gov (United States)

    Speca, David J.; Ogata, Genki; Mandikian, Danielle; Bishop, Hannah I.; Wiler, Steve W.; Eum, Kenneth; Wenzel, H. Jürgen; Doisy, Emily T.; Matt, Lucas; Campi, Katharine L.; Golub, Mari S.; Nerbonne, Jeanne M.; Hell, Johannes W.; Trainor, Brian C.; Sack, Jon T.; Schwartzkroin, Philip A.; Trimmer, James S.

    2014-01-01

    The Kv2.1 delayed rectifier potassium channel exhibits high-level expression in both principal and inhibitory neurons throughout the central nervous system, including prominent expression in hippocampal neurons. Studies of in vitro preparations suggest that Kv2.1 is a key yet conditional regulator of intrinsic neuronal excitability, mediated by changes in Kv2.1 expression, localization and function via activity-dependent regulation of Kv2.1 phosphorylation. Here we identify neurological and behavioral deficits in mutant (Kv2.1−/−) mice lacking this channel. Kv2.1−/− mice have grossly normal characteristics. No impairment in vision or motor coordination was apparent, although Kv2.1−/− mice exhibit reduced body weight. The anatomic structure and expression of related Kv channels in the brains of Kv2.1−/− mice appears unchanged. Delayed rectifier potassium current is diminished in hippocampal neurons cultured from Kv2.1−/− animals. Field recordings from hippocampal slices of Kv2.1−/− mice reveal hyperexcitability in response to the convulsant bicuculline, and epileptiform activity in response to stimulation. In Kv2.1−/− mice, long-term potentiation at the Schaffer collateral – CA1 synapse is decreased. Kv2.1−/− mice are strikingly hyperactive, and exhibit defects in spatial learning, failing to improve performance in a Morris Water Maze task. Kv2.1−/− mice are hypersensitive to the effects of the convulsants flurothyl and pilocarpine, consistent with a role for Kv2.1 as a conditional suppressor of neuronal activity. Although not prone to spontaneous seizures, Kv2.1−/− mice exhibit accelerated seizure progression. Together, these findings suggest homeostatic suppression of elevated neuronal activity by Kv2.1 plays a central role in regulating neuronal network function. PMID:24494598

  11. PIC simulation of the vacuum power flow for a 5 terawatt, 5 MV, 1 MA pulsed power system

    Science.gov (United States)

    Liu, Laqun; Zou, Wenkang; Liu, Dagang; Guo, Fan; Wang, Huihui; Chen, Lin

    2018-03-01

    In this paper, a 5 Terawatt, 5 MV, 1 MA pulsed power system based on vacuum magnetic insulation is simulated by the particle-in-cell (PIC) simulation method. The system consists of 50 100-kV linear transformer drive (LTD) cavities in series, using magnetically insulated induction voltage adder (MIVA) technology for pulsed power addition and transmission. The pulsed power formation and the vacuum power flow are simulated when the system works in self-limited flow and load-limited flow. When the pulsed power system isn't connected to the load, the downstream magnetically insulated transmission line (MITL) works in the self-limited flow, the maximum of output current is 1.14 MA and the amplitude of voltage is 4.63 MV. The ratio of the electron current to the total current is 67.5%, when the output current reached the peak value. When the impedance of the load is 3.0 Ω, the downstream MITL works in the self-limited flow, the maximums of output current and the amplitude of voltage are 1.28 MA and 3.96 MV, and the ratio of the electron current to the total current is 11.7% when the output current reached the peak value. In addition, when the switches are triggered in synchronism with the passage of the pulse power flow, it effectively reduces the rise time of the pulse current.

  12. Retigabine, a Kv7.2/Kv7.3-Channel Opener, Attenuates Drug-Induced Seizures in Knock-In Mice Harboring Kcnq2 Mutations.

    Science.gov (United States)

    Ihara, Yukiko; Tomonoh, Yuko; Deshimaru, Masanobu; Zhang, Bo; Uchida, Taku; Ishii, Atsushi; Hirose, Shinichi

    2016-01-01

    The hetero-tetrameric voltage-gated potassium channel Kv7.2/Kv7.3, which is encoded by KCNQ2 and KCNQ3, plays an important role in limiting network excitability in the neonatal brain. Kv7.2/Kv7.3 dysfunction resulting from KCNQ2 mutations predominantly causes self-limited or benign epilepsy in neonates, but also causes early onset epileptic encephalopathy. Retigabine (RTG), a Kv7.2/ Kv7.3-channel opener, seems to be a rational antiepileptic drug for epilepsies caused by KCNQ2 mutations. We therefore evaluated the effects of RTG on seizures in two strains of knock-in mice harboring different Kcnq2 mutations, in comparison to the effects of phenobarbital (PB), which is the first-line antiepileptic drug for seizures in neonates. The subjects were heterozygous knock-in mice (Kcnq2Y284C/+ and Kcnq2A306T/+) bearing the Y284C or A306T Kcnq2 mutation, respectively, and their wild-type (WT) littermates, at 63-100 days of age. Seizures induced by intraperitoneal injection of kainic acid (KA, 12mg/kg) were recorded using a video-electroencephalography (EEG) monitoring system. Effects of RTG on KA-induced seizures of both strains of knock-in mice were assessed using seizure scores from a modified Racine's scale and compared with those of PB. The number and total duration of spike bursts on EEG and behaviors monitored by video recording were also used to evaluate the effects of RTG and PB. Both Kcnq2Y284C/+ and Kcnq2A306T/+ mice showed significantly more KA-induced seizures than WT mice. RTG significantly attenuated KA-induced seizure activities in both Kcnq2Y284C/+ and Kcnq2A306T/+ mice, and more markedly than PB. This is the first reported evidence of RTG ameliorating KA-induced seizures in knock-in mice bearing mutations of Kcnq2, with more marked effects than those observed with PB. RTG or other Kv7.2-channel openers may be considered as first-line antiepileptic treatments for epilepsies resulting from KCNQ2 mutations.

  13. High Voltage Distribution System (HVDS) as a better system compared to Low Voltage Distribution System (LVDS) applied at Medan city power network

    Science.gov (United States)

    Dinzi, R.; Hamonangan, TS; Fahmi, F.

    2018-02-01

    In the current distribution system, a large-capacity distribution transformer supplies loads to remote locations. The use of 220/380 V network is nowadays less common compared to 20 kV network. This results in losses due to the non-optimal distribution transformer, which neglected the load location, poor consumer profile, and large power losses along the carrier. This paper discusses how high voltage distribution systems (HVDS) can be a better system used in distribution networks than the currently used distribution system (Low Voltage Distribution System, LVDS). The proposed change of the system into the new configuration is done by replacing a large-capacity distribution transformer with some smaller-capacity distribution transformers and installed them in positions that closest to the load. The use of high voltage distribution systems will result in better voltage profiles and fewer power losses. From the non-technical side, the annual savings and payback periods on high voltage distribution systems will also be the advantage.

  14. The C-terminal HRET sequence of Kv1.3 regulates gating rather than targeting of Kv1.3 to the plasma membrane.

    Science.gov (United States)

    Voros, Orsolya; Szilagyi, Orsolya; Balajthy, András; Somodi, Sándor; Panyi, Gyorgy; Hajdu, Péter

    2018-04-12

    Kv1.3 channels are expressed in several cell types including immune cells, such as T lymphocytes. The targeting of Kv1.3 to the plasma membrane is essential for T cell clonal expansion and assumed to be guided by the C-terminus of the channel. Using two point mutants of Kv1.3 with remarkably different features compared to the wild-type Kv1.3 (A413V and H399K having fast inactivation kinetics and tetraethylammonium-insensitivity, respectively) we showed that both Kv1.3 channel variants target to the membrane when the C-terminus was truncated right after the conserved HRET sequence and produce currents identical to those with a full-length C-terminus. The truncation before the HRET sequence (NOHRET channels) resulted in reduced membrane-targeting but non-functional phenotypes. NOHRET channels did not display gating currents, and coexpression with wild-type Kv1.3 did not rescue the NOHRET-A413V phenotype, no heteromeric current was observed. Interestingly, mutants of wild-type Kv1.3 lacking HRET(E) (deletion) or substituted with five alanines for the HRET(E) motif expressed current indistinguishable from the wild-type. These results demonstrate that the C-terminal region of Kv1.3 immediately proximal to the S6 helix is required for the activation gating and conduction, whereas the presence of the distal region of the C-terminus is not exclusively required for trafficking of Kv1.3 to the plasma membrane.

  15. Development of anode high voltage power supply system for ECRH of HL-2A tokamak

    International Nuclear Information System (INIS)

    Chen Wenguang

    2009-01-01

    The anode high voltage power supply system consist of DC high-voltage power supply (HVPS) and pulse modulator. SCR is used to vary AC input voltage of the step-up transformer by controlling the trigger phase in the HVPS, and regulate the DC output voltage linearly at the potential of low-end via BJT, Dual closed-loop control technology is applied in the controller, and its maximum output is at 30kV and 130mA. Tetrode is the core component of the modulator. The circuit design is optimized by using the simulation software. Test and HL-2A discharge experimental results show that the power supply system is designed with some characteristics of output scale widely, low ripple and modulate quickly. (authors)

  16. System upgradation for surface mode negative ion beam extraction experiments in ROBIN

    International Nuclear Information System (INIS)

    Pandya, Kaushal; Bansal, Gourab; Soni, Jignesh

    2015-01-01

    ROBIN (Replica Of BATMAN source in India) is a replica of BATMAN source of IPP, Garching. Plasma production (inductively coupled, RF produced plasma), plasma diagnostic (langmuir probe, optical emission spectroscopy), negative ion beam extraction in volume mode with reduced extraction area of 2 cm 2 (4 apertures) using small bench top type power supply (10kV, 400mA), with increase extraction area of 73 cm 2 (146 apertures) and using actual power supplies (Extraction Power Supply System, EPSS (11kV, 35A), and Accelerator Power Supply System, APSS (35kV, 15A)) and beam diagnostic etc have been performed successfully in ROBIN. This paper will describe the details of the system upgradation for surface mode negative ion experiments and its performance in ROBIN

  17. TRUSSPOLE - Trussed Metallic Pole. Results of its application in 69 kV TL - simple circuit; Trusspole: poste metalico trelicado. Resultados da aplicacao em LT 69kV - circuito simples

    Energy Technology Data Exchange (ETDEWEB)

    Silva, Paulo Ricardo Ralo Liberato da; Mello, Reynaldo Castriota de; Ferreira, Sirio Jose; Cadete, Marcia Augusta de Moura [MJMS - Mendes Junior Montagens e Servicos Ltda., Santa Luzia, MG (Brazil); Souza, Mauro Dias de [EGEL - Engenharia e Construcoes Ltda. (Brazil); Dantas, Roberto Pires [PLT - Projetos de Linhas de Transmissao Ltda. (Brazil)

    1995-12-31

    This report describes the origin, the development and the results of the TRUSSPOLE(Trussed Metallic Post) application in electric power transmission systems. It concerns a spatial trussed structure with a single metallic basis, similar to the concrete or wood pole, able to associate the technical and economical advantages of the trussed structures and the tubular or solid thick poles. The results obtained in the project, in load experiments of a study initial prototype and in the construction of a 69 kV Cs transmission line, with a 53.2 Km extension, using this type of structural solution, are shown 5 refs., 4 figs., 3 tabs.

  18. Ingledow 500 kV substation : using mixed technology switchgear solutions for replacement

    Energy Technology Data Exchange (ETDEWEB)

    Wallner, C.; Glaubitz, P. [Siemens AG, Munich (Germany); Messinger, T. [British Columbia Transmission Corp., Vancouver, BC (Canada)

    2008-07-01

    The reliability of the 500 kV equipment at the Ingledow substation operated by BC Hydro Transmission System is of critical importance due to the energy interchange with the Bonneville Power Authority in the United States and the major role of the substation in serving the energy needs of British Columbia's densely populated Lower Mainland. Presently, the 500 kV switchyard includes 10 airblast circuit breakers and the associated current transformers which are all approaching their end of service-life. In response to environmental and safety concerns, the British Columbia Transmission Corporation adopted a policy whereby new oil-filled transformers are no longer acceptable, and the replacement of existing oil-filled transformers must be oil-free. The result is that the current transformers must be either bushing-type or sulphur-hexafluoride (SF6) type. The replacement strategies for the substation equipment consider economical, environmental and seismic issues. They have just as strong an influence on the decision process as the technical, operational and reliability aspects for the particular case or switchgear replacement in the transmission system. The Ingledow case demonstrates the advantages of using mixed technology switchgear, with its compact design flowing from gas insulated switchgear (GIS) for replacement of equipment in an outdoor switchyard. The advantages of the MTS in this case offer the possibility of future reconfiguration to improve the system reliability within the existing switchyard space. 3 refs., 5 figs.

  19. Skeletal muscle Kv7 (KCNQ) channels in myoblast differentiation and proliferation

    International Nuclear Information System (INIS)

    Roura-Ferrer, Meritxell; Sole, Laura; Martinez-Marmol, Ramon; Villalonga, Nuria; Felipe, Antonio

    2008-01-01

    Voltage-dependent K + channels (Kv) are involved in myocyte proliferation and differentiation by triggering changes in membrane potential and regulating cell volume. Since Kv7 channels may participate in these events, the purpose of this study was to investigate whether skeletal muscle Kv7.1 and Kv7.5 were involved during proliferation and myogenesis. Here we report that, while myotube formation did not regulate Kv7 channels, Kv7.5 was up-regulated during cell cycle progression. Although, Kv7.1 mRNA also increased during the G 1 -phase, pharmacological evidence mainly involves Kv7.5 in myoblast growth. Our results indicate that the cell cycle-dependent expression of Kv7.5 is involved in skeletal muscle cell proliferation

  20. Operating experience with the 50 MeV 10kA ATA power conditioning system

    International Nuclear Information System (INIS)

    Rogers, D.; Lee, F.D.; Newton, M.; Reginato, L.L.; Smith, M.E.

    1984-06-01

    The Advanced Test Accelerator (ATA) has been operational for over one year and has achieved full parameters in the power conditioning system. The pulsed power system has been previously described, however, during the past year of operation a considerable amount of statistical data has been accumulated on the 211 gas blown spark gaps that perform the main switching function in the ATA. These spark gaps were designed for 250kV, 40 kA and 70ns pulse. The parameter that made this spark gap somewhat unique was the requirement that it be able to provide a burst of ten pulses at one kilohertz with an average repetition rate of 5Hz. 2 references, 7 figures

  1. Short-Circuit Characterization of 10 kV 10A 4H-SiC MOSFET

    DEFF Research Database (Denmark)

    Eni, Emanuel-Petre; Beczkowski, Szymon; Munk-Nielsen, Stig

    2016-01-01

    The short-circuit capability of a power device is highly relevant for converter design and fault protection. In this paper a 10kV 10A 4H-SiC MOSFET is characterized and its short circuit withstand capability is studied and analyzed at 6 kV DC-link voltage. The test setup for this study is also...... introduced as its design, especially the inductance in the switching loop, can affect the experimental results. The study aims to present insights specific to the device which are different from that of silicon (Si) based devices. During the short-circuit operation, MOSFET saturation current, ID...

  2. The secret life of ion channels: Kv1.3 potassium channels and proliferation.

    Science.gov (United States)

    Pérez-García, M Teresa; Cidad, Pilar; López-López, José R

    2018-01-01

    Kv1.3 channels are involved in the switch to proliferation of normally quiescent cells, being implicated in the control of cell cycle in many different cell types and in many different ways. They modulate membrane potential controlling K + fluxes, sense changes in potential, and interact with many signaling molecules through their intracellular domains. From a mechanistic point of view, we can describe the role of Kv1.3 channels in proliferation with at least three different models. In the "membrane potential model," membrane hyperpolarization resulting from Kv1.3 activation provides the driving force for Ca 2+ influx required to activate Ca 2+ -dependent transcription. This model explains most of the data obtained from several cells from the immune system. In the "voltage sensor model," Kv1.3 channels serve mainly as sensors that transduce electrical signals into biochemical cascades, independently of their effect on membrane potential. Kv1.3-dependent proliferation of vascular smooth muscle cells (VSMCs) could fit this model. Finally, in the "channelosome balance model," the master switch determining proliferation may be related to the control of the Kv1.3 to Kv1.5 ratio, as described in glial cells and also in VSMCs. Since the three mechanisms cannot function independently, these models are obviously not exclusive. Nevertheless, they could be exploited differentially in different cells and tissues. This large functional flexibility of Kv1.3 channels surely gives a new perspective on their functions beyond their elementary role as ion channels, although a conclusive picture of the mechanisms involved in Kv1.3 signaling to proliferation is yet to be reached.

  3. TWRS privatization phase 1 electrical power system

    International Nuclear Information System (INIS)

    Singh, G.

    1997-01-01

    This document includes Conceptual Design Report (CDR) for a new 11 km (7 miles) 230 kV transmission line and a new 40 MVA substation (A6) which will be located east of Grout Facility in 200E Area tank farm. This substation will provide electrical power up to 20 MW each for two private contractor facilities for immobilization and disposal of low activity waste (LAW)

  4. Regulation of Kv1.4 potassium channels by PKC and AMPK kinases

    DEFF Research Database (Denmark)

    Andersen, Martin Nybo; Skibsbye, Lasse; Saljic, Arnela

    2018-01-01

    around the ubiquitin ligase Nedd4-2. In the present study we examined whether Kv1.4, constituting the cardiac Ito,s current, is subject to similar regulation. In the epithelial Madin-Darby Canine Kidney (MDCK) cell line, which constitutes a highly reproducible model system for addressing membrane...... targeting, we find, by confocal microscopy, that Kv1.4 cell surface expression is downregulated by activation of protein kinase C (PKC) and AMP-activated protein kinase (AMPK). In contrast, manipulating the activities of phosphatidylinositol-4,5-bisphosphate 3-kinase (PI3K) and serum and glucocorticoid......-regulated kinase 1 (SGK1) were without effect on channel localization. The PKC and AMPK-mediated downregulation of Kv1.4 membrane surface localization was confirmed by two-electrode voltage clamp in Xenopus laevis oocytes, where pharmacological activation of PKC and AMPK reduced Kv1.4 current levels. We further...

  5. Power Transmission from Large Offshore Wind Farms

    DEFF Research Database (Denmark)

    Pedersen, Jørgen Kaas

    1999-01-01

    The major part of the coming wind farms in Denmark will be placed offshore. If the location is near a grid with a high short circuit level the power can be transmitted as AC.If the wind farm is far away from the grid and the grid perhaps has a low short circuit level, the best solution...... for transmitting the power can be by DC. At the moment it is possible to build self-commutating DC/AC-inverters up to about 150 kV. This paper will show a concept to a solution for a wind farm and a transmission system based on synchronous generators or a powerformer® with a rated voltage of 50 kV. The AC power...... will be rectified and boosted to a fixed DC voltage (e.g. 100 kV). The speed of the generator will be variable, depending of the wind but also controlled with the duty-cycle of the booster. In that way all wind turbines can be connected to the same DC bus and the cable to the inverter station connected to the AC...

  6. SU-G-JeP3-06: Lower KV Image Dose Are Expected From a Limited-Angle Intra-Fractional Verification (LIVE) System for SBRT Treatments

    Energy Technology Data Exchange (ETDEWEB)

    Ding, G [Vanderbilt University Nashville, TN (United States); Yin, F; Ren, L [Duke University Medical Center, Durham, NC (United States)

    2016-06-15

    Purpose: In order to track the tumor movement for patient positioning verification during arc treatment delivery or in between 3D/IMRT beams for stereotactic body radiation therapy (SBRT), the limited-angle kV projections acquisition simultaneously during arc treatment delivery or in-between static treatment beams as the gantry moves to the next beam angle was proposed. The purpose of this study is to estimate additional imaging dose resulting from multiple tomosynthesis acquisitions in-between static treatment beams and to compare with that of a conventional kV-CBCT acquisition. Methods: kV imaging system integrated into Varian TrueBeam accelerators was modeled using EGSnrc Monte Carlo user code, BEAMnrc and DOSXYZnrc code was used in dose calculations. The simulated realistic kV beams from the Varian TrueBeam OBI 1.5 system were used to calculate dose to patient based on CT images. Organ doses were analyzed using DVHs. The imaging dose to patient resulting from realistic multiple tomosynthesis acquisitions with each 25–30 degree kV source rotation between 6 treatment beam gantry angles was studied. Results: For a typical lung SBRT treatment delivery much lower (20–50%) kV imaging doses from the sum of realistic six tomosynthesis acquisitions with each 25–30 degree x-ray source rotation between six treatment beam gantry angles were observed compared to that from a single CBCT image acquisition. Conclusion: This work indicates that the kV imaging in this proposed Limited-angle Intra-fractional Verification (LIVE) System for SBRT Treatments has a negligible imaging dose increase. It is worth to note that the MV imaging dose caused by MV projection acquisition in-between static beams in LIVE can be minimized by restricting the imaging to the target region and reducing the number of projections acquired. For arc treatments, MV imaging acquisition in LIVE does not add additional imaging dose as the MV images are acquired from treatment beams directly during the

  7. ON THE NEED TO INCREASE THE RELIABILITY OF LINEAR INSULATORS FOR DISTRIBUTION NETWORKS 10-20 KV

    Directory of Open Access Journals (Sweden)

    Yu. N. Shumilov

    2018-02-01

    Full Text Available Introduction. In Ukraine high voltage overhead distribution lines (OL of class 6 and 10 kV are the most extended. Their total length exceeds 280,000 km. More than 95% of the lines are made on line supports from reinforced concrete racks. On all poles of the overhead line, pin insulators are installed. According to the data of operation experience, up to 60-70% of single-phase earth (SPE faults due to «insulation» occurs on VL supports due to damage to line pin insulators, mainly during the thunderstorm period. Problem. Insufficient reliability of pin insulators leads to interruptions in power supply, accidents on the line, accidents in the area of reinforced concrete poles, where in the case of insulator damages, a long process of SPE occurs. Goal. The purpose of the work is to select the design and develop requirements for new linear insulators of 10-20 kV overhead lines that provide high resistance to lightning overvoltages with direct and inductive effects of lightning. Methodology. The research methodology consists in analyzing operational experience, calculating insulator parameters and laboratory tests. Results. Using statistical data on lightning parameters and data on mechanical loads on insulators, the main dimensions of line post insulators have been determined that will ensure their reliable operation under conditions of intense thunderstorm activity and extreme ice and wind loads. Conclusions. The main technical requirements for line post insulators for 10-20 kV distribution lines were formulated. On the 10 kV OL located in areas with increased thunderstorm activity it is recommended to use line post insulators instead of pin-type ones. On the OL-20 kV it is recommended to use only line post insulators. The use of high-lightning-resistant line post insulators on OL-10-20 kV will significantly increase the electrical safety and reliability of power supply to consumers. Increased by 2-3 times the cost of line post insulators in

  8. X irradiation of human epidermis in vitro. 2. Comparison of single 44 kV and 200 kV X irradiation

    Energy Technology Data Exchange (ETDEWEB)

    Wollina, U; Fueller, J; Burger, B; Hipler, C

    1989-01-01

    On the example of the reduction of epidermal adhesion of FITC wheat germ agglutinine (WGA) the direct membrane effect of a single X irradiation (44 kV and 220 kV) was analyzed in vitro. Human normal skin and psoriasis centres were compared. Normal skin showed no alteration of microscopically visible FITC-WGA adhesion on epidermal cells over the whole dose range. Foci of psoriasis responded to doses of /ge/ 5 Gy (44 and 220 kV) with a drastic reduction of epidermal lectin binding to lower and medium cell layers. Maximum efficacy was with 5 Gy (44 kV) or 10 Gy (220 kV). A dose elevation up to 20 Gy did not result in an increase of efficacy. Topographically the radiosensitive FITC-WGA adhesion could chiefly be seen in the dermal ridges. The findings support the impression of an increased radiosensitivity of the lesional psoriatic epidermis compared with normal skin. This is connected with an abnormal differentiation of keratinocytes in psoriasis. (author).

  9. Atlas Pulsed Power System: a Driver for Multi-Megagauss Fields

    International Nuclear Information System (INIS)

    Cochrane, J.C.; Bartsch, R.R.; Bennett, G.A.; Bowman, D.W.; Davis, H.A.; Ekdahl, C.A.; Gribble, R.F.; Kimerly, H.J.; Nielsen, K.E.; Parsons, W.M.; Paul, J.D.; Scudder, D.W.; Trainor, R.J.; Thompson, M.C.; Watt, R.G.

    1998-01-01

    Atlas is a pulsed power machine designed for hydrodynamic experiments for the Los Alamos High Energy Density Physics Experimental program. It is presently under construction and should be operational in late 2000. Atlas will store 23 MJ at an erected voltage of 240 kV. This will produce a current of 30 MA into a static load and as much as 32 MA into a dynamic load. The current pulse will have a rise time of approximately5micros and will produce a magnetic field driving the impactor liner of several hundred Tesla at the target radius of one to two centimeters. The collision can produce shock pressures of approximately15 megabars. Design of the pulsed power system will be presented along with data obtained from the Atlas prototype Marx module

  10. Considerations for transient stability, fault capacity and power flow study of offsite power system

    Energy Technology Data Exchange (ETDEWEB)

    Shin, M C; Kim, C W; Gwon, M H; Park, C W; Lee, K W; Kim, H M; Lee, G Y; Joe, P H [Sungkyunkwan Univ., Seoul (Korea, Republic of)

    1994-04-15

    By study of power flow calculation, fault capacity calculation and stability analysis according to connection of two units YGN 3 and 4 to KEPCO power system, we have conclusions as follows. As the result of power flow calculation, at peak load, the voltage change of each bus is very small when YGN 3 and 4 is connected with KEPCO power system. At base load, installation of phase modifing equipment is necessary in Seoul, Kyungki province where load is concentrated because bus voltage rises by increasing of charge capacity caused installation of underground cables. As the result of fault capacity calculation, fault capacity is increased because fault current increases when two units YGN 3 and 4 is connected with KEPCO power system. But it is enough to operate with presenting circuits breaker rated capacity. Transient stability studies have been conducted on the YK N/P generators 3 and 4 using a digital computer program. Three phase short faults have been simulated at the YK N/P 345[KV] bus with the resulting outage of transmission circuits. Several fault clearing times are applied: 6 cycles, 12 cycles, 15 cycles. The study results demonstrate that the transient stability of YK N/P is adequate to maintain stable for three phase short faults cleared within 12 cycles. The study results also demonstrate that the transient stability of YK N/P is stable for machine removals except 4-machine removal. In addition, the study shows that the transient stability analysis is implemented for the case of load.

  11. Normalized noise power spectrum of full field digital mammography detector system

    International Nuclear Information System (INIS)

    Norriza Mohd Isa; Wan Muhamad Saridan Wan Hassan

    2009-01-01

    Full text: A method to measure noise power spectrum of a full field digital mammography system is presented. The effect of X-ray radiation dose, size and configuration of region of interest on normalized noise power spectrum (NNPS) was investigated. Flat field images were acquired using RQA-M2 beam quality technique (Mo/Mo anode-filter, 28 kV, 2 mm Al) with different clinical radiation doses. The images were cropped at about 4 cm from the edge of the breast wall and then divided into different size of non-overlapping or overlapping segments. NNPS was determined through de trending, 2-D fast Fourier transformation and normalization. Our measurement shows that high radiation dose gave lower NNPS at a specific beam quality. (author)

  12. Design and development of 500 m long HTS cable system in the KEPCO power grid, Korea

    Science.gov (United States)

    Sohn, S. H.; Lim, J. H.; Yang, B. M.; Lee, S. K.; Jang, H. M.; Kim, Y. H.; Yang, H. S.; Kim, D. L.; Kim, H. R.; Yim, S. W.; Won, Y. J.; Hwang, S. D.

    2010-11-01

    In Korea, two long-term field demonstrations for high temperature superconducting (HTS) cable have been carried out for several years; Korea Electric Power Corporation (KEPCO) and LS Cable Ltd. (LSC) independently. Encouraged at the result of the projects performed in parallel, a new project targeting the real grid operation was launched in the fourth quarter of 2008 with the Korean government's financial support. KEPCO and LSC are jointly collaborating in the selection of substation, determination of cable specification, design of cryogenic system, and the scheme of protection coordination. A three phase 500 m long HTS cable at a distribution level voltage of 22.9 kV is to be built at 154/22.9 kV Icheon substation located in near Seoul. A hybrid cryogenic system reflecting the contingency plan is being designed including cryocoolers. The HTS cable system will be installed in the second quarter of 2010, being commissioned by the fall of 2010. This paper describes the objectives of the project and design issues of the cable and cryogenic system in detail.

  13. Contribution of kv7.4/kv7.5 heteromers to intrinsic and calcitonin gene-related Peptide-induced cerebral reactivity

    DEFF Research Database (Denmark)

    Chadha, Preet S; Jepps, Thomas A; Carr, Georgina

    2014-01-01

    Middle cerebral artery (MCA) diameter is regulated by inherent myogenic activity and the effect of potent vasodilators such as calcitonin gene-related peptide (CGRP). Previous studies showed that MCAs express KCNQ1, 4, and 5 potassium channel genes, and the expression products (Kv7 channels) part......) participate in the myogenic control of MCA diameter. The present study investigated the contribution of Kv7.4 and Kv7.5 isoforms to myogenic and CGRP regulation of MCA diameter and determined whether they were affected in hypertensive animals....

  14. Back-to-Back Energization of a 60kV Cable Network - Inrush Currents Phenomenon

    DEFF Research Database (Denmark)

    Faria da Silva, Filipe; Bak, Claus Leth; Hansen, M. Lind

    2010-01-01

    On November 2008 the Danish government decided that all Danish transmission lines with a rated voltage equal to and below 150kV must be put underground, in order to reduce the visual pollution caused by Overhead Lines. This decision will lead to a massive use of underground cables in the Danish...... Network, and force a change in the approach used until now when planning, analyzing and operating electrical power systems. One problem that might arise is the energization of cables in parallel, as this operation may originate high inrush currents, which represent a risk to the circuit breakers connected...

  15. Phasor measurement of wind power plant operation in Eastern Denmark

    DEFF Research Database (Denmark)

    Rasmussen, Joana; Nielsen, Arne Hejde

    2007-01-01

    Four Phasor Measurement Units (PMUs) record continuously voltage and current phasors in the 400 kV and 132 kV transmission system of Eastern Denmark. The abstract evaluates the unique concept for power system monitoring using PMUs. It focuses on utilization of synchronized phasor measurements from...... Nysted off-shore wind farm during a severe storm in 2005. The wind speeds during the event were so high, that Nysted offshore wind farm as well as a significant amount of on-land wind production in Denmark was disconnected from the grid. The PMU analysis illustrates that PMUs complement the traditional...... measurements from a traditional SCADA system. The case reveals the close relation between voltages, power flows and voltage phase angles over a wide area....

  16. Operational experience with reactive power control methods optimized for tokamak power supplies

    International Nuclear Information System (INIS)

    Sihler, C.; Huart, M.; Kaesemann, C.-P.; Streibl, B.

    2003-01-01

    The power and energy of the ASDEX Upgrade (AUG) tokamak are provided by two separate 10.5 kV, 110-85 Hz networks based on the flywheel generators EZ3-EZ4 in addition to the generator EZ2 dedicated to the toroidal field coil. The 10.5 kV networks supply the thyristor converters allowing fast control of the DC currents in the AUG poloidal field coils. Two methods for improving the load power factor in the present experimental campaign of AUG have been investigated, namely the control of the phase-to-neutral voltage in thyristor converters fitted with neutral thyristors, such as the new 145 MVA modular thyristor converter system (Group 6), and reactive power control achieved by means of static VAr compensators (SVC). The paper shows that reliable compensation up to 90 MVAr was regularly achieved and that electrical transients in SVC modules can be kept at an acceptable level. The paper will discuss the results from the reactive power reduction by SVC and neutral thyristor control and draw a comparative conclusion

  17. To minimized power outage by the application of 'RTV' (room temperature vulcanizing) silicon on high voltage porcelain insulators in Pakistan

    International Nuclear Information System (INIS)

    Hafiz Tehzeeb ul Hassan

    2003-01-01

    In Pakistan power network comprises of 500KV, 220KV, 132KV, 66KV and 33KV transmission lines and 11KV power distribution systems. Number of insulators are used in connected units in the shape of strings with transmission line as per insulation requirements with proper design according to the various kinds of pollution stresses. The transmission lines are passing from or near polluted areas and very dusty plains of Punjab and Sindh provinces. Practices are being used in these transmission lines for removal of accumulated contamination of insulators by periodic cleaning twice a year or de-energized transmission lines. Even then discontinuation of supply takes place in the polluted areas in foggy weather. Special technique of using water repellent (Room Temperature Vulcanizing) silicone coating/paint has been introduced on high voltage disc Insulators to minimize the outage in power net work in Pakistan. Especially in high pollution areas near chemical factories and near brick kilns etc comparison study of coated and uncoated disc Insulators have been carried out by ESDD (Equal Salt Deposit Density) measurement in salt fog chamber. (author)

  18. Mitochondrial ultrastructure and glucose signaling pathways attributed to the Kv1.3 ion channel

    Directory of Open Access Journals (Sweden)

    Christopher P. Kovach

    2016-05-01

    targeted disruption of the Kv1.3 channel in the olfactory bulb can modify TEE. Our study demonstrates that Kv1.3 regulates mitochondrial structure and alters glucose utilization; two important metabolic changes that could drive whole system changes in metabolism initiated at the olfactory bulb.

  19. The anticonvulsant retigabine suppresses neuronal Kv2-mediated currents

    DEFF Research Database (Denmark)

    Stas, Jeroen I; Bocksteins, Elke; Jensen, Camilla S

    2016-01-01

    Enhancement of neuronal M-currents, generated through KV7.2-KV7.5 channels, has gained much interest for its potential in developing treatments for hyperexcitability-related disorders such as epilepsy. Retigabine, a KV7 channel opener, has proven to be an effective anticonvulsant and has recently...

  20. Active and reactive power support of MV distribution systems using battery energy storage

    DEFF Research Database (Denmark)

    Wang, Jiawei; Hashemi Toghroljerdi, Seyedmostafa; You, Shi

    2017-01-01

    shaving and voltage support service from the perspective of Distribution System Operators (DSOs). An active power support algorithm is implemented and the effects of various load profiles as well as different Photovoltaic (PV) penetration scenarios on the operation of BESS and the optimal BESS converter......Adoption of Battery Energy Storage Systems (BESSs) for provision of grid services is increasing. This paper investigates the applications of BESS for the grid upgrade deferral and voltage support of Medium Voltage (MV) distribution systems. A BESS is modelled in Matlab/Simulink to perform peak load...... size for peak load shaving are investigated. The BESS annual lifetime degradation is also estimated using a rainflow counting algorithm. A reactive power support algorithm embedded with Q-U droop control is proposed in order to reduce the voltage drop in a part of 10 kV distribution network of Nordhavn...

  1. Switching Overvoltages in 60 kV reactor compensated cable grid due to resonance after disconnection

    DEFF Research Database (Denmark)

    Bak, Claus Leth; Baldursson, Haukur; Oumarou, Abdoul M.

    2008-01-01

    power could be directly connected to long cables. Switching both cable and reactor together will cause resonance to occur between the cable capacitance and the inductance of the cable during last end disconnection. Similar type of resonance condition is known to have caused switching overvoltages...... on the 400kV grid in Denmark. Therefore it is considered necessary to analyze further whether connecting a reactor directly to 60kV cable can cause switching overvoltages. A model in PSCAD was used to analyze which parameters can cause overvoltage. The switching resonance overvoltage was found to be caused...

  2. Final environmental assessment for a refinement of the power delivery component of the Southern Nevada Water Authority Treatment and Transmission Facility

    International Nuclear Information System (INIS)

    1998-07-01

    The Southern Nevada Water Authority (SNWA) is designing and constructing a system of regional water supply facilities to meet current and projected water demands and increase system reliability. The existing Southern Nevada Water system is being upgraded with a number of improvements to increase the capacity of the system. However, even the expanded system is expected to be unable to meet projected peak daily water demands by the year 1999. As a result, new facilities are being designed and constructed to operate in conjunction with the upgraded Southern Nevada Water system. These new facilities, known as the Southern Nevada Water Authority Treatment and Transmission Facility (SNWA-TTF), include four primary components: a new raw water intake; new transmission facilities including below ground pipelines, tunnels, and above ground pumping stations; a water treatment facility; and new power supply facilities. Because existing power supplies would not be adequate for the new water treatment facilities, new power facilities, consisting of two new 230 kV-69 kV substations and new 69 and 230 kV power lines, are being constructed. This environmental assessment is specifically on the new power facilities

  3. A charge-pump 60kV modulator for the ISOLDE target extraction voltage

    CERN Document Server

    Barlow, R A; Fowler, A; Gaudillet, H; Gharsa, T; Schipper, J

    2015-01-01

    The ISOLDE facility at CERN provides radioactive ion beams to a number of experimental stations. These ions are produced by a metal target, floating at 60 kV, which is impacted by a 1.4 GeV high intensity proton beam. The ions are then accelerated by a grounded extraction electrode to 60 keV, before transport to the experimental area. During proton beam impact extremely high ionisation of the volume around the target gives rise to significant leakage current which results in loss of charge on the effective target capacitance of approximately 6 nF. If short life-time isotopes are to be studied, the 60 kV must be re-established within a maximum of 10 ms. Recharging the target capacitance to 60 kV and to the required stability of better than 10-4 precludes a direct charging system and an alternative method of re-establishing the 60 kV is used. The present system [1], in operation since 1991, employs a resonant circuit which is triggered 35 µs prior to beam impact. This circuit transfers the charge on the effec...

  4. 14C SIRI samples at CNA: Measurements at 200 kV and 1000 kV

    International Nuclear Information System (INIS)

    Santos Arévalo, Francisco-Javier; Gómez Martínez, Isabel; Agulló García, Lidia

    2015-01-01

    The Sixth International Radiocarbon Intercomparison (SIRI) exercise has taken place during late 2013 and 2014. 13 samples were distributed for AMS (Accelerator Mass Spectrometry) and 5 for radiometric laboratories, including one sample exclusively for radiometric laboratories. Being the first opportunity for our laboratory to participate actively in an intercomparison exercise, we have prepared and measured the samples in the two existing AMS dedicated facilities at the Centro Nacional de Aceleradores (CNA): SARA (Spanish Accelerator for Radionuclide Analysis), a 1 MV multielemental AMS system from HVEE, and Micadas, a 200 kV radiocarbon dating system designed by ETH. Results are presented for the two systems, together with a description of both the sample preparation and measurement procedures.

  5. 14C SIRI samples at CNA: Measurements at 200 kV and 1000 kV

    Science.gov (United States)

    Santos Arévalo, Francisco-Javier; Gómez Martínez, Isabel; Agulló García, Lidia

    2015-10-01

    The Sixth International Radiocarbon Intercomparison (SIRI) exercise has taken place during late 2013 and 2014. 13 samples were distributed for AMS (Accelerator Mass Spectrometry) and 5 for radiometric laboratories, including one sample exclusively for radiometric laboratories. Being the first opportunity for our laboratory to participate actively in an intercomparison exercise, we have prepared and measured the samples in the two existing AMS dedicated facilities at the Centro Nacional de Aceleradores (CNA): SARA (Spanish Accelerator for Radionuclide Analysis), a 1 MV multielemental AMS system from HVEE, and Micadas, a 200 kV radiocarbon dating system designed by ETH. Results are presented for the two systems, together with a description of both the sample preparation and measurement procedures.

  6. A fast 30 kV 5 kHz repetition rate resonant capacitor charger

    NARCIS (Netherlands)

    Beckers, F.J.C.M.; Huiskamp, T.; van Heesch, E.J.M.; Pemen, A.J.M.

    2016-01-01

    A novel circuit topology of a fast 30 kV resonant capacitor charger is presented in this paper. The charger is designed for high repetition rate spark gap based pulsed power modulators. A spark gap can fire spontaneously (pre-firing) during charging of a capacitor bank due to poor dielectric

  7. Limitation of Electrical Power in January

    CERN Multimedia

    2006-01-01

    During maintenance work on CERN's 400 kV main electrical supply in Prevessin, the laboratory will be connected to the 130 kV Suisse network in Meyrin from 4 to 22 January. Due to the on-going LHC activities during this period, the power demand will be very close to the technical limitations of this source. The effort of every one to reduce the consumption of electrical energy during this period is vital to avoid powercuts caused by exceeding the maximum capacity of the system. Mario Batz TS/CV Gerard Cumer TS/EL

  8. Limitation of Electrical Power in January

    CERN Multimedia

    2007-01-01

    During maintenance work on CERN's 400 kV main electrical supply in Prevessin, the laboratory will be connected to the 130 kV Suisse network in Meyrin from 4 to 22 January. Due to the on-going LHC activities during this period, the power demand will be very close to the technical limitations of this source. The effort of every one to reduce the consumption of electrical energy during this period is vital to avoid powercuts caused by exceeding the maximum capacity of the system. Mario Batz TS/CV Gerard Cumer TS/EL

  9. Detailed design of a 13 kA 13 kV dc solid-state turn-off switch. [Revision

    International Nuclear Information System (INIS)

    Praeg, W.F.

    1985-01-01

    An experimental facility for the study of electromagnetic effects in the First Wall-Blanket-Shield (FWBS) systems of fusion reactors has been constructed at Argonne National Laboratory (ANL). In a test volume of 0.76 m 3 , a vertical, pulsed 5 kG dipole field (B dot less than or equal to 320 kGs -1 ) is perpendicular to a 10 kG solenoid field. Power supplies of 2.75 MW at 550 V dc and 5.5 MW at 550 V dc and a solid-state switch rated at 13 kA and 13 kV (169 MW) control the pulsed magnetic fields. The total stored energy in the coils is 2.6 MJ. This paper describes the design and construction features of the solid-state switching circuit which turns off a dc current of 13 kA in approximately 82 μs and holds off voltages of less than or equal to 13 kV. 14 figs

  10. Comparison of the quality of the chest film between digital radiography and conventional high kV radiography

    International Nuclear Information System (INIS)

    Zeng Qingsi; Cen Renli; Chen Ling; He Jianxun; Lin Hanfei

    2003-01-01

    Objective: To evaluate the quality and usefulness of direct digital radiography system in roentgenogram of chest in clinical practice. Methods: 1000 cases of chest roentgenograms with digital radiography and high kV conventional radiography were selected for analysis by 3 senior radiologists. Results: 1. With digital radiography system, the quality of chest film was assessed as grade A in 50.6%, grade B in 38.5%, grade C in 10.9%, and no waste film. 2. With conventional high kV radiography, the quality of chest film was assessed as grade A in 41.1%, grade B in 44.1%, grade C in 13.3%, and waste film in 1.5%. The direct digital radiography was statistically superior to the conventional high kV radiography. 3. The fine structure of the lungs could be revealed in 100.0% of chest roentgenogram with direct digital radiograph system, which was significantly higher than that acquired with the conventional high KV radiography (78.6%, P < 0.001). Conclusion: Direct digital radiography could provide the chest film with better quality than that with the conventional high kV radiography. The direct digital radiography system is easy to operate, fast in capturing imaging and could provide post-processing techniques, which will facilitate the accurate diagnosis of chest radiography

  11. Investigation on the Short-Circuit Behavior of an Aged IGBT Module Through a 6 kA/1.1 kV Non-Destructive Testing Equipment

    DEFF Research Database (Denmark)

    Wu, Rui; Smirnova, Liudmila; Iannuzzo, Francesco

    2014-01-01

    This paper describes the design and development of a 6 kA/1.1 kV non-destructive testing system, which aims for short circuit testing of high-power IGBT modules. An ultralow stray inductance of 37 nH is achieved in the implementation of the tester. An 100 MHz FPGA supervising unit enables 10 ns...

  12. Rugi Daya Dan Energi Akibat Korona Pada Saluran Udara Tegangan Ekstra Tinggi (SUTET 500 Kv

    Directory of Open Access Journals (Sweden)

    Muhamad Haddin

    2018-01-01

    Full Text Available The use of extra high voltage in electrical power transmission system causing corona. A visual corona phenomenon shown by the appearance of visible light radiation, hissing noise, ozone formation and power losses. The impact of corona affect the environment surrounding the overhead line transmission and power losses in the line. This research discusses power and energy losses due to corona by using quantitative method. Calculations performed by calculating relative air density values, disruptive critical voltages, power losses and corona energy. The research object was taken by extra high voltage  overhead line transmission 500kV Tanjung Jati B Power Plant to Ungaran Substation.The result show that corona power losses are 0.41-0.44 kW/mil (0.25-0.27kw/km per phase, with total 1.25-1.30kW/mil (0.78-0.81k/w/km. corona power losses 107.57-112.08 kW along of line. Average of corona energy losses obtained 2642.67 kWh. The percentage of corona power losses to electrical power supplied is between 0.005% to 0.011%.

  13. The State Power Corporation of China

    Institute of Scientific and Technical Information of China (English)

    2001-01-01

    @@General Description of SP The State Power Corporation of China (SP) was established on January 16, 1997 under the approval of the State Council. As the largest power corporation in China, with 160 billion Yuan of registered capital and 1.38 million staff, SP's business scope covers generation, transmission, distribution, engineering design, construction, project management, as well as trade and financing etc. The core business of SP is power network construction and operation. SP has 146,150 km transmission lines at the voltage of 220 kV and above, which accounts for 89.5% of that in China's mainland, among which there are 26,730 km and 8,680 km of 500 kV and 330 kV respectively.Power Sources Planning,

  14. Single-phase system in the voltage class of 15 kV at long distances; Alimentadores monofasicos em redes aereas na classe de 15 kV, para grandes distancias

    Energy Technology Data Exchange (ETDEWEB)

    Sant` Anna, Alzira M [UNESP, Botucatu, SP (Brazil). Faculdade de Ciencias Agronomicas; Simone, Gilio A [UNESP, Bauru, SP (Brazil). Dept. de Engenharia Eletrica

    1999-12-31

    There have always been three philosophies regarding the way how electrical power should be taken to the countrymen. One of them states that the feeding should be single-phase by two conductors, the tri-phase feeding philosophy and the one of the single-phase earth return. This work searched to asses the electrical behaviour of a single-phase by two conductors system, in the tension class of 15 kV, at long distance, as a way of making feasible the implantation of well structured single-phase circuits, that may cause the least disturbance in the tri-phase lines from which they derive. In order to reach the intended goals, simulations with a mathematical simulator of electric circuit were performed, working with the parameters of the lines, of the transformers and of the charges. A bi wired circuit of the distribution was assembled and taken to the same simulator, the one which provided the currents, the tension drop outs, at each point or part of the net. With these data it is possible to: verify the reduction of the torked in the motors axel; the reduction of the tension in the lamps; the behaviour of the net under variable conditions of charge. (author) 3 refs., 6 figs., 7 tabs.

  15. Analysis of Even Harmonics Generation in an Isolated Electric Power System

    Science.gov (United States)

    Kanao, Norikazu; Hayashi, Yasuhiro; Matsuki, Junya

    Harmonics bred from loads are mainly odd order because the current waveform has half-wave symmetry. Since the even harmonics are negligibly small, those are not generally measured in electric power systems. However, even harmonics were measured at a 500/275/154kV substation in Hokuriku Electric Power Company after removal of a transmission line fault. The even harmonics caused malfunctions of protective digital relays because the relays used 4th harmonics at the input filter as automatic supervisory signal. This paper describes the mechanism of generation of the even harmonics by comparing measured waveforms with ATP-EMTP simulation results. As a result of analysis, it is cleared that even harmonics are generated by three causes. The first cause is a magnetizing current of transformers due to flux deviation by DC component of a fault current. The second one is due to harmonic conversion of a synchronous machine which generates even harmonics when direct current component or even harmonic current flow into the machine. The third one is that increase of harmonic impedance due to an isolated power system produces harmonic voltages. The design of the input filter of protective digital relays should consider even harmonics generation in an isolated power system.

  16. Inactivation as a new regulatory mechanism for neuronal Kv7 channels

    DEFF Research Database (Denmark)

    Jensen, Henrik Sindal; Grunnet, Morten; Olesen, Søren-Peter

    2007-01-01

    neuronal channels and are important for controlling excitability. Kv7.1 channels have been considered the only Kv7 channels to undergo inactivation upon depolarization. However, here we demonstrate that inactivation is also an intrinsic property of Kv7.4 and Kv7.5 channels, which inactivate to a larger...

  17. Rapid internalization of the oncogenic K+ channel K(V10.1.

    Directory of Open Access Journals (Sweden)

    Tobias Kohl

    Full Text Available K(V10.1 is a mammalian brain voltage-gated potassium channel whose ectopic expression outside of the brain has been proven relevant for tumor biology. Promotion of cancer cell proliferation by K(V10.1 depends largely on ion flow, but some oncogenic properties remain in the absence of ion permeation. Additionally, K(V10.1 surface populations are small compared to large intracellular pools. Control of protein turnover within cells is key to both cellular plasticity and homeostasis, and therefore we set out to analyze how endocytic trafficking participates in controlling K(V10.1 intracellular distribution and life cycle. To follow plasma membrane K(V10.1 selectively, we generated a modified channel of displaying an extracellular affinity tag for surface labeling by α-bungarotoxin. This modification only minimally affected K(V10.1 electrophysiological properties. Using a combination of microscopy and biochemistry techniques, we show that K(V10.1 is constitutively internalized involving at least two distinct pathways of endocytosis and mainly sorted to lysosomes. This occurs at a relatively fast rate. Simultaneously, recycling seems to contribute to maintain basal K(V10.1 surface levels. Brief K(V10.1 surface half-life and rapid lysosomal targeting is a relevant factor to be taken into account for potential drug delivery and targeting strategies directed against K(V10.1 on tumor cells.

  18. Switched power workshop power supply working group

    International Nuclear Information System (INIS)

    Haseroth, H.; Hopkins, D.; Ikezi, H.; Kirbie, H.; Lincke, E.; Wilson, M.

    1988-01-01

    The power supply working group was assigned the problem of pulse charging the 3-MeV gun. The gun is a radial line structure that has two charging configurations: a single ring charged to 500 kV or nine rings charged from 100 to 200 kV. In either configuration, the pulsed source must rapidly charge the structure's ring(s) before breakdown can begin. The issues encountered in charging the structure can be divided into two categories. First, the charging system must be well matched to the gun structure. Proper impedance matching will avoid reflections and limit the fault current if the ring should spark. Second, several systems can achieve the wide range of charge voltages necessary. Some are better suited to high voltages, while others are better at low voltages. The following paragraphs will address the impedance matching issues are review three choices for pulse generators. A system for each type of source is described along with a very rough cost estimate. 1 ref., 4 figs., 2 tabs

  19. Switched power workshop: Power supply working group

    International Nuclear Information System (INIS)

    Haseroth, H.; Hopkins, D.; Ikezi, H.; Kirbie, H.C.; Lincke, E.; Wilson, M.

    1989-01-01

    The power supply working group was assigned the problem of pulse charging the 3-MeV gun. The gun is a radial line structure that has two charging configurations: a single ring charged to 500 kV or nine rings charged from 100 to 200 kV. In either configuration, the pulsed source must rapidly charge the structure's ring(s) before breakdown can begin. The issues encountered in charging the structure can be divided into two categories. First, the charging system must be well matched to the gun structure. Proper impedance matching will avoid reflections and limit the fault current if the ring should spark. Second, several systems can achieve the wide range of charge voltages necessary. Some are better suited to high voltages, while others are better at low voltages. The following paragraphs will address the impedance matching issues and review three choices for pulse generators. A system for each type of source is described along with a very rough cost estimate. 1 ref., 4 figs., 2 tabs

  20. Vacuum switchgear for power station auxiliary switchboards

    International Nuclear Information System (INIS)

    Coombs, P.E.

    1992-01-01

    Sizewell B is the first UK power station in which vacuum switchgear is used for the auxiliary switchboards. Previously the 3.3kV, 6.6kV or 11kV switchgear has used air-break circuit breakers and fused air-break contactors, known as motor starting devices or fused switching devices (FSD). The use of vacuum interrupters is therefore a new technology in this application, although it has been established in the UK distribution network and in industrial installations from the mid 1970s. Vacuum switchgear was already in use in the USA for power station auxiliary switchgear at the time that it was proposed for Sizewell B. The Sizewell B high voltage auxiliary switchgear comprises eight Unit and Station Auxiliary Switchboards at 3.3kV and 11kV, and four 3.3kV Essential Switchboards for the essential safety related circuits, making a total of 65 circuit breakers plus FSD panels. (Author)

  1. Short-circuit tests of 1650 and 96 MVA transformers for 1300 MW french nuclear power plants

    International Nuclear Information System (INIS)

    Mailhot, M.

    1989-01-01

    Power evacuation and feeding of the auxiliaries directly from the 400 kV grid are sensitive points governing the security of 1300 MW PWR Nuclear Power Plants of the French Program. These two different functions are provided by two specific types of transformers. - Banks of 3 single-phase 550 MVA - 400 kV/20 kV transformers. - Three-phase 96 MVA - 400 kV / 3 x 6.8 kV transformers. These passive elements must have a never failing reliability and assure a continuous service in spite of electric, thermal and mechanical stresses that may occur during the lifetime of the power plant. Dielectric and thermal tests carried out in the manufacturers test floors insure these stresses withstand capabilities of transformers. In France, high short-circuit power for the 400 kV network added to often low impedance voltages for transformers impose on them very high stresses during short-circuits. Calculation and experimentation on scale or partial models are not sufficient to insure short-circuit currents withstand capabilities of transformers. The margin of uncertainty dependent on obligatory extrapolations for this kind of complex systems [steel, magnetic sheets, copper, oil, paper and transformerboard] can be reduced in a significant way only by real scale tests on prototypes. These tests that need both high power and voltage cannot be performed in manufacturers test floors. So, in France they are carried out at the EDF Les Renardieres Laboratory. Following paper deals with SHELL TYPE TRANSFORMERS which, particularly thanks to their interleaved rectangular windings display a great resistance to short-circuit stresses

  2. Kv4 channels underlie the subthreshold-operating A-type K+-current in nociceptive dorsal root ganglion neurons

    Directory of Open Access Journals (Sweden)

    Thanawath R Na Phuket

    2009-07-01

    Full Text Available The dorsal root ganglion (DRG contains heterogeneous populations of sensory neurons including primary nociceptive neurons and C-fibers implicated in pain signaling.  Recent studies have demonstrated DRG hyperexcitability associated with downregulation of A-type K+ channels; however, the molecular correlate of the corresponding A-type K+ current (IA has remained hypothetical.  Kv4 channels may underlie the IA in DRG neurons.  We combined electrophysiology, molecular biology (whole-tissue and single-cell RT-PCR and immunohistochemistry to investigate the molecular basis of the IA in acutely dissociated DRG neurons from 7-8 day-old rats.  Whole-cell recordings demonstrate a robust tetraethylammonium-resistant (20 mM and 4-aminopyridine-sensitive (5 mM IA.  Matching Kv4 channel properties, activation and inactivation of this IA occur in the subthreshold range of membrane potentials and the rate of recovery from inactivation is rapid and voltage-dependent.  Among Kv4 transcripts, the DRG expresses significant levels of Kv4.1 and Kv4.3 mRNAs.  Also, single small-medium diameter DRG neurons (~30 mm exhibit correlated frequent expression of mRNAs encoding Kv4.1 and Nav1.8, a known nociceptor marker.  In contrast, the expressions of Kv1.4 and Kv4.2 mRNAs at the whole-tissue and single-cell levels are relatively low and infrequent.  Kv4 protein expression in nociceptive DRG neurons was confirmed by immunohistochemistry, which demonstrates colocalization of Kv4.3 and Nav1.8, and negligible expression of Kv4.2.  Furthermore, specific dominant-negative suppression and overexpression strategies confirmed the contribution of Kv4 channels to IA in DRG neurons.  Contrasting the expression patterns of Kv4 channels in the central and peripheral nervous systems, we discuss possible functional roles of these channels in primary sensory neurons.

  3. The acrylamide (S)-1 differentially affects Kv7 (KCNQ) potassium channels

    DEFF Research Database (Denmark)

    Bentzen, Bo Hjorth; Schmitt, Nicole; Calloe, Kirstine

    2006-01-01

    The family of Kv7 (KCNQ) potassium channels consists of five members. Kv7.2 and 3 are the primary molecular correlates of the M-current, but also Kv7.4 and Kv7.5 display M-current characteristics. M-channel modulators include blockers (e.g., linopirdine) for cognition enhancement and openers (e.g...

  4. Kv10.1 potassium channel: from the brain to the tumors.

    Science.gov (United States)

    Cázares-Ordoñez, V; Pardo, L A

    2017-10-01

    The KCNH1 gene encodes the Kv10.1 (Eag1) ion channel, a member of the EAG (ether-à-go-go) family of voltage-gated potassium channels. Recent studies have demonstrated that KCHN1 mutations are implicated in Temple-Baraitser and Zimmermann-Laband syndromes and other forms of developmental deficits that all present with mental retardation and epilepsy, suggesting that Kv10.1 might be important for cognitive development in humans. Although the Kv10.1 channel is mainly expressed in the mammalian brain, its ectopic expression occurs in 70% of human cancers. Cancer cells and tumors expressing Kv10.1 acquire selective advantages that favor cancer progression through molecular mechanisms that involve several cellular pathways, indicating that protein-protein interactions may be important for Kv10.1 influence in cell proliferation and tumorigenesis. Several studies on transcriptional and post-transcriptional regulation of Kv10.1 expression have shown interesting mechanistic insights about Kv10.1 role in oncogenesis, increasing the importance of identifying the cellular factors that regulate Kv10.1 expression in tumors.

  5. Investigation of 35-110 kV line and equipment exterior insulation and oil-filled power transformers under high-mountain conditions

    Energy Technology Data Exchange (ETDEWEB)

    Karapetyan, M.M.; Sanagyan, R.T.

    1980-01-01

    Flashover characteristics have been obtained for 35-110 kV external insulation at heights of up to 2000 m above sea level. The utilization of 35-110 kV equipment for heights of up to 2000 m above sea level is recommended. The dependence of the increase in flashover voltage in rain with increasing resistivity and the tendency toward an increase in the latter with increasing height above sea level are examined.

  6. In vitro measurement of CT density and estimation of stenosis related to coronary soft plaque at 100 kV and 120 kV on ECG-triggered scan

    Energy Technology Data Exchange (ETDEWEB)

    Horiguchi, Jun, E-mail: horiguch@hiroshima-u.ac.jp [Department of Clinical Radiology, Hiroshima University Hospital, 1-2-3, Kasumi-cho, Minami-ku, Hiroshima 734-8551 (Japan); Fujioka, Chikako, E-mail: fujioka@hiroshima-u.ac.jp [Department of Clinical Radiology, Hiroshima University Hospital, 1-2-3, Kasumi-cho, Minami-ku, Hiroshima 734-8551 (Japan); Kiguchi, Masao, E-mail: kiguchi@hiroshima-u.ac.jp [Department of Clinical Radiology, Hiroshima University Hospital, 1-2-3, Kasumi-cho, Minami-ku, Hiroshima 734-8551 (Japan); Yamamoto, Hideya, E-mail: hideyayama@hiroshima-u.ac.jp [Department of Cardiovascular Medicine, Hiroshima University Graduate School of Biomedical Sciences and Hiroshima University Hospital, 1-2-3, Kasumi-cho, Minami-ku, Hiroshima 734-8551 (Japan); Shen, Yun, E-mail: Yuna.Shen@ge.com [CT Lab of Great China, GE Healthcare, L12 and L15, Office Tower, Langham Place, 8 Argyle Street, Mongkok Kowloon (Hong Kong); Kihara, Yasuki, E-mail: ykihara@hiroshima-u.ac.jp [Department of Cardiovascular Medicine, Hiroshima University Graduate School of Biomedical Sciences and Hiroshima University Hospital, 1-2-3, Kasumi-cho, Minami-ku, Hiroshima 734-8551 (Japan)

    2011-02-15

    Purpose: The purpose of the study was to compare 100 kV and 120 kV prospective electrocardiograph (ECG)-triggered axial coronary 64-detector CT angiography (64-MDCTA) in soft plaque diagnosis. Materials and methods: Coronary artery models (n = 5) with artificial soft plaques (-32 HU to 53 HU at 120 kV) with three stenosis levels (25%, 50% and 75%) on a cardiac phantom (mimicking slim patient's environment) were scanned in heart rates of 55, 60 and 65 beats per minute (bpm). Four kinds of intracoronary enhancement (205 HU, 241 HU, 280 HU and 314 HU) were simulated. The soft plaque density and the measurement error of stenosis (in percentage), evaluated by two independent observers, were compared between 100 kV and 120 kV. The radiation dose was estimated. Results: Interobserver correlation of the measurement was excellent (density; r = 0.95 and stenosis measure; r = 0.97). Neither the density of soft plaque nor the measurement error of stenosis was different between 100 kV and 120 kV (p = 0.22 and 0.08). The estimated radiation doses were 2.0 mSv and 3.3 mSv (in 14 cm coverage) on 100 kV and 120 kV prospective ECG-triggered axial scans, respectively. Conclusion: The 100 kV prospective ECG-triggered coronary MDCTA has comparable performance to 120 kV coronary CTA in terms of soft plaque densitometry and measurement of stenosis, with a reduced effective dose of 2 mSv.

  7. JAERI 200 kV electron gun with an NEA-GaAs photocathode

    International Nuclear Information System (INIS)

    Nishitani, Tomohiro; Minehara, Eisuke J.; Hajima, Ryoichi; Nagai, Ryoji; Sawamura, Masaru; Nishimori, Nobuyuki; Kikuzawa, Nobuhiro; Yamauchi, Toshihiko

    2004-01-01

    The photocathode DC-gun with high average current, low beam emittance and long operational lifetime is considered to be indispensable for ERL-FEL. We have started the development program of a 200 keV electron gun with the NEA-GaAs photocathode for the first time in JAERI. In order to long an NEA surface lifetime, the JAERI 200 kV electron gun system consists of a 200 kV DC-gun chamber on extreme high vacuum condition and an NEA activation chamber with load-lock system. We report the goal of photocathode DC-gun R and D and the schedule of a developmental program. (author)

  8. Overvoltage protection of large power transformers

    DEFF Research Database (Denmark)

    Bak, Claus Leth; Wiechowski, Wojciech Tomasz; Einarsdottir, Kristin

    2006-01-01

    This paper demonstrates the results from a detailed study of the overvoltage protection of a particular 400/150 kV 400 MVA power transformer. The work presented here is based on real-life power system substation design and data and initiated by Danish TSO Energinet.dk as a consequence of a serious...... exceeded. It is clearly illustrated that the transient performance of the earth grid plays an important role in the overall overvoltage protection system design...

  9. {sup 14}C SIRI samples at CNA: Measurements at 200 kV and 1000 kV

    Energy Technology Data Exchange (ETDEWEB)

    Santos Arévalo, Francisco-Javier, E-mail: fj.santos@csic.es; Gómez Martínez, Isabel; Agulló García, Lidia

    2015-10-15

    The Sixth International Radiocarbon Intercomparison (SIRI) exercise has taken place during late 2013 and 2014. 13 samples were distributed for AMS (Accelerator Mass Spectrometry) and 5 for radiometric laboratories, including one sample exclusively for radiometric laboratories. Being the first opportunity for our laboratory to participate actively in an intercomparison exercise, we have prepared and measured the samples in the two existing AMS dedicated facilities at the Centro Nacional de Aceleradores (CNA): SARA (Spanish Accelerator for Radionuclide Analysis), a 1 MV multielemental AMS system from HVEE, and Micadas, a 200 kV radiocarbon dating system designed by ETH. Results are presented for the two systems, together with a description of both the sample preparation and measurement procedures.

  10. Rearrangement of potassium ions and Kv1.1/Kv1.2 potassium channels in regenerating axons following end-to-end neurorrhaphy: ionic images from TOF-SIMS.

    Science.gov (United States)

    Liu, Chiung-Hui; Chang, Hung-Ming; Wu, Tsung-Huan; Chen, Li-You; Yang, Yin-Shuo; Tseng, To-Jung; Liao, Wen-Chieh

    2017-10-01

    The voltage-gated potassium channels Kv1.1 and Kv1.2 that cluster at juxtaparanodal (JXP) regions are essential in the regulation of nerve excitability and play a critical role in axonal conduction. When demyelination occurs, Kv1.1/Kv1.2 activity increases, suppressing the membrane potential nearly to the equilibrium potential of K + , which results in an axonal conduction blockade. The recovery of K + -dependent communication signals and proper clustering of Kv1.1/Kv1.2 channels at JXP regions may directly reflect nerve regeneration following peripheral nerve injury. However, little is known about potassium channel expression and its relationship with the dynamic potassium ion distribution at the node of Ranvier during the regenerative process of peripheral nerve injury (PNI). In the present study, end-to-end neurorrhaphy (EEN) was performed using an in vivo model of PNI. The distribution of K + at regenerating axons following EEN was detected by time-of-flight secondary-ion mass spectrometry. The specific localization and expression of Kv1.1/Kv1.2 channels were examined by confocal microscopy and western blotting. Our data showed that the re-establishment of K + distribution and intensity was correlated with the functional recovery of compound muscle action potential morphology in EEN rats. Furthermore, the re-clustering of Kv1.1/1.2 channels 1 and 3 months after EEN at the nodal region of the regenerating nerve corresponded to changes in the K + distribution. This study provided direct evidence of K + distribution in regenerating axons for the first time. We proposed that the Kv1.1/Kv1.2 channels re-clustered at the JXP regions of regenerating axons are essential for modulating the proper patterns of K + distribution in axons for maintaining membrane potential stability after EEN.

  11. 75 FR 9573 - Minnkota Power Cooperative, Inc: Bemidji-Grand Rapids 230kV Transmission Project

    Science.gov (United States)

    2010-03-03

    ... Rapids 230kV Transmission Project AGENCY: Rural Utilities Service, USDA. ACTION: Notice of Availability... copy of the Draft EIS may be viewed online at the following Web sites: http://www.usda.gov/rus/water..., Longville, MN 56655; Walker Public Library, 207 4th St., Walker, MN 56484; Bovey Public Library--Village...

  12. Cryogenic System for a High-Temperature Superconducting Power Transmission Cable

    International Nuclear Information System (INIS)

    Demko, J.A.; Gouge, M.J.; Hughey, R.L.; Lue, J.W.; Martin, R.; Sinha, U.; Stovall, J.P.

    1999-01-01

    High-temperature superconducting (HTS) cable systems for power transmission are under development that will use pressurized liquid nitrogen to provide cooling of the cable and termination hardware. Southwire Company and Oak Ridge National Laboratory have been operating a prototype HTS cable system that contains many of the typical components needed for a commercial power transmission application. It is being used to conduct research in the development of components and systems for eventual commercial deployment. The cryogenic system was built by Air Products and Chemicals, Allentown, Pennsylvania, and can circulate up to 0.35 kg/s of liquid nitrogen at temperatures as low as 67 K at pressures of 1 to 10 bars. Sufficient cooling is provided for testing a 5-m-long HTS transmission cable system that includes the terminations required for room temperature electrical connections. Testing of the 5-m HTS transmission cable has been conducted at the design ac conditions of 1250 A and 7.5 kV line to ground. This paper contains a description of the essential features of the HTS cable cryogenic system and performance results obtained during operation of the system. The salient features of the operation that are important in large commercial HTS cable applications will be discussed

  13. A performance comparison of flat-panel imager-based MV and kV cone-beam CT

    International Nuclear Information System (INIS)

    Groh, B.A.; Siewerdsen, J.H.; Drake, D.G.; Wong, J.W.; Jaffray, D.A.

    2002-01-01

    The use of cone-beam computed tomography (CBCT) has been proposed for guiding the delivery of radiation therapy, and investigators have examined the use of both kilovoltage (kV) and megavoltage (MV) x-ray beams in the development of such CBCT systems. In this paper, the inherent contrast and signal-to-noise ratio (SNR) performance for a variety of existing and hypothetical detectors for CBCT are investigated analytically as a function of imaging dose and object size. Theoretical predictions are compared to the results of experimental investigations employing large-area flat-panel imagers (FPIs) at kV and MV energies. Measurements were performed on two different FPI-based CBCT systems: a bench-top prototype incorporating an FPI and kV x-ray source (100 kVp x rays), and a system incorporating an FPI mounted on the gantry of a medical linear accelerator (6 MV x rays). The SNR in volume reconstructions was measured as a function of dose and found to agree reasonably with theoretical predictions. These results confirm the theoretically predicted advantages of employing kV energy x rays in imaging soft-tissue structures found in the human body. While MV CBCT may provide a valuable means of correcting 3D setup errors and may offer an advantage in terms of simplicity of mechanical integration with a linear accelerator (e.g., implementation in place of a portal imager), kV CBCT offers significant performance advantages in terms of image contrast and SNR per unit dose for visualization of soft-tissue structures. The relatively poor SNR performance at MV energies is primarily a result of the low x-ray quantum efficiencies (∼a few percent or less) that are currently achieved with FPIs at high energies. Furthermore, kV CBCT with an FPI offers the potential of combined volumetric and radiographic/fluoroscopic imaging using the same device

  14. Custom power - the utility solution to distribution power quality

    Energy Technology Data Exchange (ETDEWEB)

    Woodley, N H [Westinghouse Electric Corp., Pittsburgh, PA (United States)

    1997-04-01

    The design of custom power products for electric power distribution system was discussed. Problems with power quality that result in loss of production to critical processes are costly and create a problem for the customer as well as the electric utility. Westinghouse has developed power quality improvement equipment for customers and utilities, using new technologies based on power electronics concepts. The Distribution Static Compensator (DSTATCOM) is a fast response, solid-state power controller that provides flexible voltage control for improving power quality at the point of connection to the utility`s 4.16 to 69 kV distribution feeder. STATCOM is a larger version of the DSTATCOM that can be used to solve voltage flicker problems caused by electric arc furnaces. Westinghouse has also developed a Dynamic Voltage Restorer (DVR) which protects a critical customer plant load from power system voltage disturbances. Solid-State Breakers (SSB) have also been developed which offer a solution to many of the distribution system problems that result in voltage sags, swells, and power outages. 6 refs., 8 figs.

  15. Bladder contractility is modulated by Kv7 channels in pig detrusor

    DEFF Research Database (Denmark)

    Svalø, Julie; Bille, Michala; Parameswaran Theepakaran, Neeraja

    2013-01-01

    Kv7 channels are involved in smooth muscle relaxation, and accordingly we believe that they constitute potential targets for the treatment of overactive bladder syndrome. We have therefore used myography to examine the function of Kv7 channels in detrusor, i.e. pig bladder, with a view...... relaxation, suggesting that Kv7.2 and/or Kv7.4 channels constitute the subtypes that are relevant to bladder contractility. The effects of retigabine and ML213 were attenuated by pre-incubation with 10µM XE991 (Kv7.1-7.5 channel blocker) (P...

  16. A study on stimulation of DC high voltage power of LCC series parallel resonant in projectile velocity measurement system

    Science.gov (United States)

    Lu, Dong-dong; Gu, Jin-liang; Luo, Hong-e.; Xia, Yan

    2017-10-01

    According to specific requirements of the X-ray machine system for measuring velocity of outfield projectile, a DC high voltage power supply system is designed for the high voltage or the smaller current. The system comprises: a series resonant circuit is selected as a full-bridge inverter circuit; a high-frequency zero-current soft switching of a high-voltage power supply is realized by PWM output by STM32; a nanocrystalline alloy transformer is chosen as a high-frequency booster transformer; and the related parameters of an LCC series-parallel resonant are determined according to the preset parameters of the transformer. The concrete method includes: a LCC series parallel resonant circuit and a voltage doubling circuit are stimulated by using MULTISM and MATLAB; selecting an optimal solution and an optimal parameter of all parts after stimulation analysis; and finally verifying the correctness of the parameter by stimulation of the whole system. Through stimulation analysis, the output voltage of the series-parallel resonant circuit gets to 10KV in 28s: then passing through the voltage doubling circuit, the output voltage gets to 120KV in one hour. According to the system, the wave range of the output voltage is so small as to provide the stable X-ray supply for the X-ray machine for measuring velocity of outfield projectile. It is fast in charging and high in efficiency.

  17. A continuous acceleration tube of ions under 200 KV

    International Nuclear Information System (INIS)

    Mongodin, G.

    1954-01-01

    The realization of an Van de Graaff accelerator required, for the preliminary studies, the construction of a small proton accelerator, functioning at 200 kV in order to resolve some parasitic effects inherent to the accelerators tubes. The aim of this report is to describe the different organs of the accelerator tube, to explain the operating system and to encode their characteristics. The report first presents the ion source and the beam buncher permitting to inject in the accelerator tube particles of about 9 kV and very batched in a thin beam of circular section. Then the study explain the tube characteristics considered like optic system. A method to obtain precise calculation of particle trajectories is exposed. Aberrations of the system were discussed and balance of the currents on all electrodes inside the tube for different regimes of working were provided. The influence of the residual pressure in the tube were explained. The report finally ends on a part of the fundamental problem of the straining occurring inside the tubes accelerators under high tension. (M.B.) [fr

  18. Preliminary study on development of 300 Kv compact focused gaseous ion beam system

    Energy Technology Data Exchange (ETDEWEB)

    Ohkubo, T.; Ishii, Y.; Kamiya, T. [Takasaki Advanced Radiation Research Institute, Japan Atomic Energy Agency (JAEA) 1233 Watanuki-machi, Takasaki, Gunma, 370-1292 (Japan); Miyake, Y. [Beam Seiko Instruments Inc., 2-10-1 Kamata, Ohta-ku, Tokyo, 144-0052 (Japan)

    2013-04-19

    A new 300 kV compact focused gaseous ion beam (gas-FIB) system with three-stage acceleration lens was constructed at JAEA. The preliminary experiments of formation of the focused gaseous ion beams were carried out to show the availability of the gas-FIB system as a writing tool for 3D proton lithography. As a result of the experiments, it was proved that the focal point was kept at the same position under changing the kinetic energy but with keeping the kinetic energy ratio constant, which was defined as the ratio of kinetic energy in object side to that in image side for the third acceleration lens. This characteristic of the gas-FIB is a good point to advance the 3D proton lithography changing penetration depth in a sample by varying the beam energy.

  19. Preliminary study on development of 300 Kv compact focused gaseous ion beam system

    International Nuclear Information System (INIS)

    Ohkubo, T.; Ishii, Y.; Kamiya, T.; Miyake, Y.

    2013-01-01

    A new 300 kV compact focused gaseous ion beam (gas-FIB) system with three-stage acceleration lens was constructed at JAEA. The preliminary experiments of formation of the focused gaseous ion beams were carried out to show the availability of the gas-FIB system as a writing tool for 3D proton lithography. As a result of the experiments, it was proved that the focal point was kept at the same position under changing the kinetic energy but with keeping the kinetic energy ratio constant, which was defined as the ratio of kinetic energy in object side to that in image side for the third acceleration lens. This characteristic of the gas-FIB is a good point to advance the 3D proton lithography changing penetration depth in a sample by varying the beam energy.

  20. Características de las fallas en alimentadores de 13,8 kV del sistema soterrado de La Habana;Characteristic of 13,8 kV feeders faults of the Havana underground system

    Directory of Open Access Journals (Sweden)

    Boris Alba - Valle

    2011-06-01

    Full Text Available El sistema soterrado de La Habana enfrenta problemas de continuas fallas en sus alimentadores de 13,8 kV. En este trabajo se determinan las características de estas averías, en el período comprendido entre los años 2007 y 2009, y se proponen algunas medidas objetivas con el fin de contribuir a su disminución. La investigación se basó fundamentalmente en el estudio de la base de datos de los alimentadores de 13,8 kV proporcionada por el departamento técnico de la Unidad Empresarial Básica (UEB Soterrada y en el uso de herramientas estadísticas digitales. Como resultado se pudo constatar que las fallas son más frecuentes en los alimentadores de la subestación de Tallapiedra producto de la humedad en cables y empalmes con aislamiento de PILC (papel impregnado en aceite y con cubierta de plomo, dispuestos por tierra muerta. Finalmente, las medidas propuestas tuvieron un impacto positivo en la disminución de estas fallas, en un período inferior a un año.The Havana underground system has problems of continuous faults in their 13,8 kV feeders. In this article the characteristics of these mishaps in the period of 2007 to 2009 are determined and purpose some objective measurements with the end of contributing to their decrease. The investigation was fundamentally based on the study of the 13,8 kV feeders database proportioned by the technical department of the Underground Basic Managerial Unit (UEB and the use of digital statistical tools. As a result, it was verified that the faults occur with more frequency in the Tallapiedra substation feeders, due to the humidity in cables and connections with PILC isolation (impregnated in oil and lead covered paper, prepared for undergrounding directly in the earth. Finally, the proposed measures had a positive impact in the decrease of these faults, in a period less than to a year.

  1. APR1400 Electrical Power System Conformance to SECY-91-078

    Energy Technology Data Exchange (ETDEWEB)

    Ha, Che-Wung; Kim, Yun-Ho [KHNP CRI, Daejeon (Korea, Republic of)

    2016-10-15

    In this paper, the APR1400 electric power system for NRC-DC was described. In addition, the conformance to SECY 91-078 was evaluated. Enclosure 1 of the SECY provides an overview of the issue and states that the staff concludes that feeding the safety buses from the offsite power sources through non-safety buses or from a common transformer winding with non-safety loads is not the most reliable configuration. Such an arrangement increases the difficulty in properly regulating voltage at the safety buses, subjects the safety loads to transients caused by the non-safety loads, and adds additional failure points between the offsite power sources and safety loads. Therefore, it is the staff’s position that at least one offsite circuit to each redundant safety division should be supplied directly from one of the offsite power sources with no intervening non-safety buses, in such a manner that the offsite source can power the safety buses upon a failure of any non-safety bus. The APR1400 does not have an intervening nonsafety bus in the current offsite to onsite electrical configuration; however, the design does include nonsafety and safety buses coming from the same secondary side 4.16 kV transformer winding. Nevertheless, the APR1400 has designed the electrical interface system between offsite and onsite power with enhanced reliability measures to ensure that the nonsafety system will not impact the safety loads. The design complies with GDC 17 and also conforms to SECY-91-078.

  2. Protection system for 11kV network using arc noise

    International Nuclear Information System (INIS)

    Burdi, M.K.; Memon, A.S.; Shaikh, S.A.

    2000-01-01

    Extensive research work is being done on protecting devices for 11KV network using arc noise and fault noise frequencies in relay to operate a circuit breaker; The relay works on the principle of detecting fault and extracting voltage signal output from the noise frequencies across filter. The voltage development without amplification, is enough to operate the circuit breaker. Sensitivity of the circuit breaker. In this paper design, operation and application of the relay are described. (author)

  3. Probabilistic determination of operating rules for 6.6 kV power supplies to 900 MW(e) pressurized-water units

    International Nuclear Information System (INIS)

    Blin, A.; Carnino, A.; Boursier, M.; Greppo, J.F.

    1975-01-01

    The 6.6 kV power supplies to the safety systems of the 900 MW PWR units being built by Electricite de France (EDF) are ensured by four redundant sources within or outside the site. Because of this redundancy, non-availability of one or more of the sources does not jeopardize the electricity supply - it merely means that the unit must be shut down deliberately for safety reasons at some time. The proposed method is a probabilistic approach which makes it possible to determine how long the unit can reasonably continue on power in such circumstances. The study described in the paper is based on operating results recorded by EDF for equipment similar to that envisaged for future nuclear power stations and in service in existing ones. The amount of information gathered and the method employed for gathering it permit a realistic assessment of the reliability parameters of the equipment (failure and repair rates). To allow for the fact that the equipment can be repaired, the method proper involves use of the Markov model, with which one can find, for each configuration of the system, the change over time of the probability P 0 of a simultaneous failure of all power sources. Use of this method requires prior conversion of the actual concept to an equivalent concept. The sensitivity of P 0 to the parameters is studied for each case, a reasonable uncertainty range being obtained for P 0 . Common mode failures for external or internal sources are introduced in parametric form so that the parameter value beyond which they can be neglected is determined. On the basis of the results of the study, the authors propose the adoption of a comparative criterion whereby any mode of operation in degraded conditions (one or more sources not available) is permitted provided that the corresponding value of P 0 is always lower than the maximum value attained by it in the reference situation (all sources available). Applying this criterion, one can determine with the help of graphs the

  4. Dimensional verification and location of the reactive static compensator in 220 kV; Verificacion del dimensionamiento y ubicacion del compensador estatico de reactivos en 220 kV

    Energy Technology Data Exchange (ETDEWEB)

    Fernandez Krekeler, Ubaldo [Administracion Nacional de Electricidad (ANDE), Asuncion (Paraguay)]. E-mail: ufernandez@ieee.org; Cardozo Sanchez, Freddy [Mirant Americas (United States)

    2001-07-01

    This work presents a determination verification of the compensation range and the location of reactive static compensator (RSC) in 220 kV. The verification is accomplished by analyses of the RSC effects in relation to the losses, loading and system voltage stability. The needed compensation range is investigated in full details, whereas that the required conversion level is directly related to this range. It is concluded that the RSC installation, foreseen for 2002, might be postponed for 2005/10 still without reinforcements in 500 kV. The Limpio substation seems to be the more suitable location in relation to the most analysed cases.

  5. Performance of the 10kV, 100-kA pulsed-power modules for the FRX-C magnetic compression experiment

    International Nuclear Information System (INIS)

    Rej, D.J.; Waganaar, W.J.

    1989-01-01

    In this paper, we present detailed performance data collected from over a year's operation of the 25 and 50-kJoule pulsed-power capacitor-bank modules developed for the Los Alamos magnetic fusion facility FRX-C. These modules supply the 5-MA magnet current needed for the compressional heating of compact toroid plasmoids. To date, 54 modules have been built and successfully tested at their full design rating: 100-kA peak output current at 10-kV charge, τ 1/4 = 60 μs (25-kJ module), or 110 μs (50-kJ module), crowbar L/R ≤ 1 ms. Modules are compact, cost about $5000 each, and though designed for 25 or 50 kJ, they can be easily modified for other pulsed-power applications. Energy is stored in 25-kJ capacitors. Start and crowbar switching is performed with a pair of water-cooled, size-D ignitrons. As an alternative to an ignitron, crowbar switching by solid-state rectifiers has been successfully demonstrated. Current is conducted between components and to the load by parallel-plate transmission lines and by a parallel array of commercially-available coaxial cable. 4 refs., 8 figs

  6. Harmonics in transmission power systems

    DEFF Research Database (Denmark)

    Wiechowski, Wojciech Tomasz

    . The comparison shows that results obtained used both types of the cores are the same, so it is concluded that both cores can be used for harmonic measurements. Low-inductance resistors are introduced in the secondary circuits, in series with the metering and protective relaying. On those resistors, the harmonic......Some time ago, Energinet.dk, the Transmission System Operator of the 150 kV and 400 kV transmission network in Denmark, had experienced operational malfunctions of some of the measuring and protection equipment. Also an overloading of a harmonic filter has been reported, and therefore, a need...... end only so the ground is not used as a return path. A way to reduce the capacitive coupling is to provide shielding. Harmonic currents are measured using the conventional inductive voltage transformers. Both protective and metering cores were compared if they could be used for harmonic measurements...

  7. Numerical simulation research of 300 kV, 5 electrodes negative ion beam system

    International Nuclear Information System (INIS)

    Wang Huisan; Jian Guangde

    2001-01-01

    According to the characteristic of high current negative ion beam extraction and acceleration system for negative ion-based neutral beam injector, a numerical simulation model and a calculation code of the negative ion beam system are established in order to assist the design of the system. The movement behavior of the negative ion beam and accompanying electron beam in joint effect of the electric and magnetic field of the system is calculated. The effect of relative parameters on the negative ion beam optics characteristic is investigated, such as beam density, negative ion initial temperature and stripping losses, final electrode aperture displacement. The electromagnetic configuration in the system is optimized. The initial optimized results for the 300 kV, 5 electrodes negative ion beam system show that the magnetic field of this system can deflect the electron beam to the extraction electrode as electron acceptor at lower energy and that assuming 20% stripping losses of the H - ion in extraction region and 21 mA ·cm -2 extracted H - beam density, the r.m.s. divergence angle of all output beam lets and divergence angle of 85% output beam lets are 0.327 deg. and 0.460 deg., respectively

  8. Chronic electroconvulsive stimulation but not chronic restraint stress modulates mRNA expression of voltage-dependent potassium channels Kv7.2 and Kv11.1 in the rat piriform cortex

    DEFF Research Database (Denmark)

    Hjæresen, Marie-Louise; Hageman, Ida; Wörtwein, Gitta

    2008-01-01

    The mechanisms by which stress and electroconvulsive therapy exert opposite effects on the course of major depression are not known. Potential candidates might include the voltage-dependent potassium channels. Potassium channels play an important role in maintaining the resting membrane potential...... and controlling neuronal excitability. To explore this hypothesis, we examined the effects of one or several electroconvulsive stimulations and chronic restraint stress (6 h/day for 21 days) on the expression of voltage-dependent potassium channel Kv7.2, Kv11.1, and Kv11.3 mRNA in the rat brain using in situ...... hybridization. Repeated, but not acute, electroconvulsive stimulation increased Kv7.2 and Kv11.1 mRNA levels in the piriform cortex. In contrast, restraint stress had no significant effect on mRNA expression of Kv7.2, Kv11.1, or Kv11.3 in any of the brain regions examined. Thus, it appears that the investigated...

  9. Using of explosive technologies for development of a compact current-limiting device for operation on 110 kV class systems

    Science.gov (United States)

    Shurupov, A. V.; Shurupov, M. A.; Kozlov, A. A.; Kotov, A. V.

    2016-11-01

    This paper considers the possibility of creating on new physical principles a highspeed current-limiting device (CLD) for the networks with voltage of 110 kV, namely, on the basis of the explosive switching elements. The device is designed to limit the steady short-circuit current to acceptable values for the time does not exceed 3 ms at electric power facilities. The paper presents an analysis of the electrical circuit of CLD. The main features of the scheme are: a new high-speed switching element with high regenerating voltage; fusible switching element that enables to limit the overvoltage after sudden breakage of network of the explosive switch; non-inductive resistor with a high heat capacity and a special reactor with operating time less than 1 s. We analyzed the work of the CLD with help of special software PSPICE, which is based on the equivalent circuit of single-phase short circuit to ground in 110 kV network. Analysis of the equivalent circuit operation CLD shows its efficiency and determines the CLD as a perspective direction of the current-limiting devices of new generation.

  10. Using of explosive technologies for development of a compact current-limiting device for operation on 110 kV class systems

    International Nuclear Information System (INIS)

    Shurupov, A V; Shurupov, M A; Kozlov, A A; Kotov, A V

    2016-01-01

    This paper considers the possibility of creating on new physical principles a highspeed current-limiting device (CLD) for the networks with voltage of 110 kV, namely, on the basis of the explosive switching elements. The device is designed to limit the steady short-circuit current to acceptable values for the time does not exceed 3 ms at electric power facilities. The paper presents an analysis of the electrical circuit of CLD. The main features of the scheme are: a new high-speed switching element with high regenerating voltage; fusible switching element that enables to limit the overvoltage after sudden breakage of network of the explosive switch; non-inductive resistor with a high heat capacity and a special reactor with operating time less than 1 s. We analyzed the work of the CLD with help of special software PSPICE, which is based on the equivalent circuit of single-phase short circuit to ground in 110 kV network. Analysis of the equivalent circuit operation CLD shows its efficiency and determines the CLD as a perspective direction of the current-limiting devices of new generation. (paper)

  11. Main unit electrical protection at Sizewell 'B' power station

    International Nuclear Information System (INIS)

    Fischer, A.; Keates, T.

    1992-01-01

    For any power station, reliable electrical protection of the main generating units (generators plus generator transformers) has important commercial implications. Spurious trips cause loss of generation and consequent loss of revenue, while failure to rapidly isolate a fault leads to unnecessary damage and again, loss of generation and revenue. While these conditions apply equally to Sizewell B there are additional factors to be taken into consideration. A spurious trip of a main generating unit may lead to a trip of the reactor with an associated challenge to the shutdown and core cooling plant. The generator transformers, besides exporting power from the generators to the 400 kV National Grid, also import power from the Grid to the 11 kV Main Electrical System, which in turn is the preferred source of supply to the Essential Electrical System. The Main Unit Protection is designed to clear generator faults leaving this off-site power route intact. Hence failure to operate correctly could affect the integrity of the Essential Electrical Supplies. (Author)

  12. Achievement report on developing superconductor power applied technologies in fiscal 1999 (1). Research and development of superconductor wire materials, research and development of superconductor power generators, research of total systems, research and development of freezing systems, and verification tests; 1999 nendo chodendo denryoku oyo gijutsu kaihatsu seika hokokusho. 1. Chodendo senzai no kenkyu kaihatsu / chodendo hatsudenki no kenkyu kaihatsu / total system no kenkyu / reito system no kenkyu kaihatsu / jissho shiken

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2000-03-01

    With an objective to achieve higher efficiency, higher density, and higher stability in power systems, research and development has been performed on superconductor power applied technologies. This paper summarizes the achievements thereof in fiscal 1999. In research and development of the superconductor wire materials, decrease in loss and increase in capacity of the conductors were progressed for the Nb{sub 3}Sn wire material, whereas its mechanical properties and stability were evaluated. In research and development of the superconductor generators, an ultra high speed responding generator was verified of its healthiness in a sudden short circuit test. A linkage test with an operating 77-kV system was performed, wherein verification was given that the superconductor generator can be operated stably against various disturbances. In research and development of the freezing systems, an improved system was structured, which achieved operation of 11,390 hours in a single system as a result of the high reliability of the oil-free structure. In the verification tests, the ultra high speed responding model generator was connect to the freezing system to give such tests as load test, onerous test, actuation test by using the M-G system, and 77-kV system linkage test. The functions, reliability, and durability of the system were verified, and different data were acquired. (NEDO)

  13. Development of 8 MW Power Supply Based on Pulse Step Modulation Technique for Auxiliary Heating System on HL-2A

    International Nuclear Information System (INIS)

    Xu Weidong; Xuan Weimin; Yao Lieying; Wang Yingqiao

    2012-01-01

    The high voltage power supply (HVPS) based on pulse step modulation (PSM) has already been developed for the auxiliary heating system on HL-2A. This power supply consists of many switch power supplies, and its output voltage can be obtained by modulating their delay time and pulse widths. The PSM topology and control principle are presented in this paper. The simple algorithms for the control system are explained clearly. The switch power supply (SPS) module has been built and the test results show it can meet the requirements of the auxiliary heating system. Now, 112 SPS modules and the whole system have already been developed. Its maximum output is about 72 kV/93 A. The protection time is less than 5 μs. The different outputs of this power supply are used for the electron cyclotron resonant heating (ECRH) system with different duty ratios. The experimental results of the entire system are presented. The results indicate that the whole system can meet the requirements of the auxiliary heating system on HL-2A.

  14. Solar PV-based rooftop power plant

    International Nuclear Information System (INIS)

    Ashok Kumar, B.; Kumar, Chaitanya; Patel, C.B.; Pattanaik, B.R.; Panda, P.K.; Kaul, S.K.; Mishra, H.

    2017-01-01

    Technical Services Division (TSD) is responsible for providing reliable power supply to various operating reactors, laboratories and facilities of BARC. The power supply to BARC is derived from TATA Power at 110 KV and 22 KV at an average HT tariff of Rs.8.49 per unit at present. Peak power demand of BARC in summer season goes up to 23 MW. TSD has implemented several energy conservation measures to reduce the energy consumption and as well taken initiatives to install solar PV based rooftop power plants to reduce the cost of energy consumption in BARC

  15. A study on DC hybrid three-phase fault current limiting interrupter for a power distribution system

    International Nuclear Information System (INIS)

    Shao, Hongtian; Satoh, Tomoyuki; Yamaguchi, Mitsugi; Fukui, Satoshi; Ogawa, Jun; Satoh, Takao; Ishikawa, Hiroyuki

    2005-01-01

    For the purpose of protecting electric power system, many researches and developments of fault current limiters are being performed. The authors studied a dc hybrid three-phase fault current limiting interrupter (FCLI) composed of a superconducting reactor and an S/N transition element, connected in series each other. The dc hybrid type fault current limiting interrupter can limit a fault current by means of the inductance of high temperature superconducting (HTS) coil together with the normal transition of HTS bulk material (HTSB). In the case of an accident, the normal transition of the bulk material can be accelerated by the magnetic field of the HTS coil. In this paper, the dc hybrid type fault current limiting interrupter for 5.5 km long 6.6 kV-600 A power distribution system is analyzed, and performances of fault current limitation and interruption are confirmed. Moreover, a reclosing operation is discussed for this power distribution system

  16. Development of a 33 kV, 20 A long pulse converter modulator for high average power klystron

    International Nuclear Information System (INIS)

    Reghu, T.; Mandloi, V.; Shrivastava, Purushottam

    2014-01-01

    Research, design, and development of high average power, long pulse modulators for the proposed Indian Spallation Neutron Source are underway at Raja Ramanna Centre for Advanced Technology. With this objective, a prototype of long pulse modulator capable of delivering 33 kV, 20 A at 5 Hz repetition rate has been designed and developed. Three Insulated Gate Bipolar Transistors (IGBT) based switching modules driving high frequency, high voltage transformers have been used to generate high voltage output. The IGBT based switching modules are shifted in phase by 120° with respect to each other. The switching frequency is 25 kHz. Pulses of 1.6 ms pulse width, 80 μs rise time, and 70 μs fall time have been achieved at the modulator output. A droop of ±0.6% is achieved using a simple segmented digital droop correction technique. The total fault energy transferred to the load during fault has been measured by conducting wire burn tests and is found to be within 3.5 J

  17. Development of a 33 kV, 20 A long pulse converter modulator for high average power klystron

    Science.gov (United States)

    Reghu, T.; Mandloi, V.; Shrivastava, Purushottam

    2014-05-01

    Research, design, and development of high average power, long pulse modulators for the proposed Indian Spallation Neutron Source are underway at Raja Ramanna Centre for Advanced Technology. With this objective, a prototype of long pulse modulator capable of delivering 33 kV, 20 A at 5 Hz repetition rate has been designed and developed. Three Insulated Gate Bipolar Transistors (IGBT) based switching modules driving high frequency, high voltage transformers have been used to generate high voltage output. The IGBT based switching modules are shifted in phase by 120° with respect to each other. The switching frequency is 25 kHz. Pulses of 1.6 ms pulse width, 80 μs rise time, and 70 μs fall time have been achieved at the modulator output. A droop of ±0.6% is achieved using a simple segmented digital droop correction technique. The total fault energy transferred to the load during fault has been measured by conducting wire burn tests and is found to be within 3.5 J.

  18. Development of a 33 kV, 20 A long pulse converter modulator for high average power klystron

    Energy Technology Data Exchange (ETDEWEB)

    Reghu, T.; Mandloi, V.; Shrivastava, Purushottam [Pulsed High Power Microwave Section, Raja Ramanna Centre for Advanced Technology, Indore 452013, M.P. (India)

    2014-05-15

    Research, design, and development of high average power, long pulse modulators for the proposed Indian Spallation Neutron Source are underway at Raja Ramanna Centre for Advanced Technology. With this objective, a prototype of long pulse modulator capable of delivering 33 kV, 20 A at 5 Hz repetition rate has been designed and developed. Three Insulated Gate Bipolar Transistors (IGBT) based switching modules driving high frequency, high voltage transformers have been used to generate high voltage output. The IGBT based switching modules are shifted in phase by 120° with respect to each other. The switching frequency is 25 kHz. Pulses of 1.6 ms pulse width, 80 μs rise time, and 70 μs fall time have been achieved at the modulator output. A droop of ±0.6% is achieved using a simple segmented digital droop correction technique. The total fault energy transferred to the load during fault has been measured by conducting wire burn tests and is found to be within 3.5 J.

  19. Development of compact rapid charging power supply for capacitive energy storage in pulsed power drivers.

    Science.gov (United States)

    Sharma, Surender Kumar; Shyam, Anurag

    2015-02-01

    High energy capacitor bank is used for primary electrical energy storage in pulsed power drivers. The capacitors used in these pulsed power drivers have low inductance, low internal resistance, and less dc life, so it has to be charged rapidly and immediately discharged into the load. A series resonant converter based 45 kV compact power supply is designed and developed for rapid charging of the capacitor bank with constant charging current up to 150 mA. It is short circuit proof, and zero current switching technique is used to commute the semiconductor switch. A high frequency resonant inverter switching at 10 kHz makes the overall size small and reduces the switching losses. The output current of the power supply is limited by constant on-time and variable frequency switching control technique. The power supply is tested by charging the 45 kV/1.67 μF and 15 kV/356 μF capacitor banks. It has charged the capacitor bank up to rated voltage with maximum charging current of 150 mA and the average charging rate of 3.4 kJ/s. The output current of the power supply is limited by reducing the switching frequency at 5 kHz, 3.3 kHz, and 1.7 kHz and tested with 45 kV/1.67 μF capacitor bank. The protection circuit is included in the power supply for over current, under voltage, and over temperature. The design details and the experimental testing results of the power supply for resonant current, output current, and voltage traces of the power supply with capacitive, resistive, and short circuited load are presented and discussed.

  20. The Trencin water power station

    International Nuclear Information System (INIS)

    2005-01-01

    This leaflet describes the Trencin water power station. The Trencin water power station was built seven years after the Dubnica nad Vahom water power station started its operation and was the last stage of the first and the oldest derived cascade of water power stations on the Vah River. After completing water power stations at Ladce (1936), Ilava (1946) and Dubnica nad Vahom (1949) and before constructing the Trencin water power station, the whole second derived cascade of water power stations including water power stations at Kostolna, Nove Mesto nad Vahom and Horna Streda was built as soon as possible mainly because the need to get compensation for discontinued electricity supplies as well as energetic coal from the Czech Republic. Hereby, experiences from the construction of previous grades were used, mainly as far as the dimensioning was concerned, as the fi rst installed power stations had, in comparison with the growing requirements on the electricity supplies, very low absorption capacity - only 150 m 3 .s -1 . Thus the Trencin power station (original name was the Skalka power station) was already dimensioned for the same absorption capacity as the cascade located downstream the river, that is 180 m 3 .s -1 . That was related also to growing demands on electricity supplies during the peaks in the daily electric system load diagram, and thus to the transfer from continuous operation of the water power station to semi-peak or even peak performance. According to the standards of power station classification, the Trencin water power station is a medium size, low pressure, channel power station with two units equipped by Kaplan turbines and synchronous hydro-alternators. The water power station installed capacity is 16.1 MW in total and its designed annual production of electrical energy for medium water year is 85,000 MWh, while the average annual production during the last 30 years is 86,252 MWh. Installed unit has a four-blade Kaplan turbine with the diameter

  1. The 150 kV cp microfocus X-ray unit

    NARCIS (Netherlands)

    Fontijn, L.A.

    1979-01-01

    Development of microfocus X-ray technique is defined. Advantages on other methods, principle of operation and the material comprising an intense electron source imaged on an X-ray target by means of a double magnetic lense system, are described. Resolution value at 150 kV is the imaging of a 0.1 mm

  2. The transient outward current in mice lacking the potassium channel gene Kv1.4

    Science.gov (United States)

    London, Barry; Wang, Dao W; Hill, Joseph A; Bennett, Paul B

    1998-01-01

    The transient outward current (Ito) plays a prominent role in the repolarization phase of the cardiac action potential. Several K+ channel genes, including Kv1.4, are expressed in the heart, produce rapidly inactivating currents when heterologously expressed, and may be the molecular basis of Ito.We engineered mice homozygous for a targeted disruption of the K+ channel gene Kv1.4 and compared Ito in wild-type (Kv1.4+/+), heterozygous (Kv1.4+/-) and homozygous ‘knockout’ (Kv1.4−/−) mice. Kv1.4 RNA was truncated in Kv1.4−/− mice and protein expression was absent.Adult myocytes isolated from Kv1.4+/+, Kv1.4+/− and Kv1.4−/− mice had large rapidly inactivating outward currents. The peak current densities at 60 mV (normalized by cellular capacitance, in pA pF−1; means ± s.e.m.) were 53.8 ± 5.3, 45.3 ± 2.2 and 44.4 ± 2.8 in cells from Kv1.4+/+, Kv1.4+/− and Kv1.4−/− mice, respectively (P mice.The voltage dependence and time course of inactivation were not changed by targeted disruption of Kv1.4. The mean best-fitting V½ (membrane potential at 50 % inactivation) values for myocytes from Kv1.4 +/+, Kv1.4+/− and Kv1.4−/− mice were -53.5 ± 3.7, -51.1 ± 2.6 and -54.2 ± 2.4 mV, respectively. The slope factors (k) were -10.1 ± 1.4, -8.8 ± 1.4 and -9.5 ± 1.2 mV, respectively. The fast time constants for development of inactivation at -30 mV were 27.8 ± 2.2, 26.2 ± 5.1 and 19.6 ± 2.1 ms in Kv1.4+/+, Kv1.4+/− and Kv1.4−/− myocytes, respectively. At +30 mV, they were 35.5 ± 2.6, 30.0 ± 2.1 and 28.7 ± 1.6 ms, respectively. The time constants for the rapid phase of recovery from inactivation at -80 mV were 32.5 ± 8.2, 23.3 ± 1.8 and 39.0 ± 3.7 ms, respectively.Nearly the entire inactivating component as well as more than 60 % of the steady-state outward current was eliminated by 1 mm 4-aminopyridine in Kv1.4+/+, Kv1.4+/− and Kv1.4−/− myocytes.Western blot analysis of heart membrane extracts showed no significant

  3. Differential expression of the Kv1 voltage-gated potassium channel family in the rat nephron.

    Science.gov (United States)

    Carrisoza-Gaytán, Rolando; Salvador, Carolina; Diaz-Bello, Beatriz; Escobar, Laura I

    2014-10-01

    Several potassium (K(+)) channels contribute to maintaining the resting membrane potential of renal epithelial cells. Apart from buffering the cell membrane potential and cell volume, K(+) channels allow sodium reabsorption in the proximal tubule (PT), K(+) recycling and K(+) reabsorption in the thick ascending limb (TAL) and K(+) secretion and K(+) reabsorption in the distal convoluted tubule (DCT), connecting tubule (CNT) and collecting duct. Previously, we identified Kv.1.1, Kv1.3 and Kv1.6 channels in collecting ducts of the rat inner medulla. We also detected intracellular Kv1.3 channel in the acid secretory intercalated cells, which is trafficked to the apical membrane in response to dietary K(+) to function as a secretory K(+) channel. In this work we sought to characterize the expression of all members of the Kv1 family in the rat nephron. mRNA and protein expression were detected for all Kv1 channels. Immunoblots identified differential expression of each Kv1 in the cortex, outer and inner medulla. Immunofluorescence labeling detected Kv1.5 in Bowman´s capsule and endothelial cells and Kv1.7 in podocytes, endothelial cells and macula densa in glomeruli; Kv1.4, Kv1.5 and Kv1.7 in PT; Kv1.2, Kv1.4 and Kv1.6 in TAL; Kv1.1, Kv1.4 and Kv1.6 in DCT and CNT and Kv1.3 in DCT, and all the Kv1 family in the cortical and medullary collecting ducts. Recently, some hereditary renal syndromes have been attributed to mutations in K(+) channels. Our results expand the repertoire of K(+) channels that contribute to K(+) homeostasis to include the Kv1 family.

  4. Proposed high voltage power supply for the ITER relevant lower hybrid current drive system

    International Nuclear Information System (INIS)

    Sharma, P.K.; Kazarian, F.; Garibaldi, P.; Gassman, T.; Artaud, J.F.; Bae, Y.S.; Belo, J.; Berger-By, G.; Bernard, J.M.; Cara, Ph.; Cardinali, A.; Castaldo, C.; Ceccuzzi, S.; Cesario, R.; Decker, J.; Delpech, L.; Ekedahl, A.; Garcia, J.; Goniche, M.; Guilhem, D.

    2011-01-01

    In the framework of the EFDA task HCD-08-03-01, the ITER lower hybrid current drive (LHCD) system design has been reviewed. The system aims to generate 24 MW of RF power at 5 GHz, of which 20 MW would be coupled to the plasmas. The present state of the art does not allow envisaging a unitary output of the klystrons exceeding 500 kW, so the project is based on 48 klystron units, leaving some margin when the transmission lines losses are taken into account. A high voltage power supply (HVPS), required to operate the klystrons, is proposed. A single HVPS would be used to feed and operate four klystrons in parallel configuration. Based on the above considerations, it is proposed to design and develop twelve HVPS, based on pulse step modulator (PSM) technology, each rated for 90 kV/90 A. This paper describes in details, the typical electrical requirements and the conceptual design of the proposed HVPS for the ITER LHCD system.

  5. Fault Analysis of ITER Coil Power Supply System

    International Nuclear Information System (INIS)

    Song, In Ho; Jun, Tao; Benfatto, Ivone

    2009-01-01

    The ITER magnet coils are all designed using superconductors with high current carrying capability. The Toroidal Field (TF) coils operate in a steadystate mode with a current of 68 kA and discharge the stored energy in case of quench with using 9 interleaved Fast Discharge Units (FDUs). The Central Solenoid (CS) coils and Poloidal Field (PF) coils operate in a pulse mode with currents of up to 45 kA and require fast variation of currents inducing more than 10 kV during normal operation on the coil terminals using Switching Network (SN) systems (CSs, PF1 and 6) and Booster and VS converters (PF2 to 5), which are series connected to Main converters. SN and FDU systems comprise high current DC circuit breakers and resistors for generating high voltage (SN) and to dissipate magnetic energy (FDUs). High transient voltages can arise due to the switching operation of SN and FD and the characteristics of resistors and stray components of DC distribution systems. Also, faults in power supply control such as shorts or grounding faults can produce higher voltages between terminals and between terminal and ground. Therefore, the design of the coil insulation, coil terminal regions, feeders, feed throughs, pipe breaks and instrumentation must take account of these high voltages during normal and abnormal conditions. Voltage insulation level can be defined and it is necessary to test the coils at higher voltages, to be sure of reliable performance during the lifetime of operation. This paper describes the fault analysis of the TF, CS and PF coil power supply systems, taking account of the stray parameter of the power supply and switching systems and inductively coupled superconducting coil models. Resistor grounding systems are included in the simulation model and all fault conditions such as converter hardware and software faults, switching system hardware and software faults, DC short circuits and single grounding faults are simulated. The occurrence of two successive faults

  6. AC transmission, with very high voltages and the 750 kV line

    Energy Technology Data Exchange (ETDEWEB)

    Bocker, H

    1964-01-01

    The economic case for adoption of extra-high voltages for transmitting electric power over distances of the order of 1000 km is discussed. Some special technical developments for solving the problems attached to such high voltages are briefly discussed, particularly in the fields of switching and transients suppression. The first 750-kV projects in Canada and Russia are mentioned. Equipment, e.g., bushings, transformers, etc., operating at such voltages are illustrated.

  7. THE METHOD OF SELECTION OF THE SETPOINT HIGH SPEED FEEDER SWITCH OF 3,3KV DC WITH MICROPROCESSOR-BASED PROTECTION SYSTEMS

    Directory of Open Access Journals (Sweden)

    P. Ye. Mykhalichenko

    2009-10-01

    Full Text Available In the article a new procedure of choice of minimum current jump for action of fast-acting switches of 3.3 kV DC traction substations intended for the use in the microprocessor protection system of feeders is described. This procedure is more perfect than existing one on the current increment and uses the results of mathematical simulation of the traction electric supply system.

  8. KV7 potassium channels

    DEFF Research Database (Denmark)

    Stott, Jennifer B; Jepps, Thomas Andrew; Greenwood, Iain A

    2014-01-01

    Potassium channels are key regulators of smooth muscle tone, with increases in activity resulting in hyperpolarisation of the cell membrane, which acts to oppose vasoconstriction. Several potassium channels exist within smooth muscle, but the KV7 family of voltage-gated potassium channels have been...

  9. 2KJ/S 1KV, 25HZ PRR capacitor charging power supply with twin phase shifted primary windings to achieve high charge transfer rate and stability

    International Nuclear Information System (INIS)

    Kelkar, Y.; Singh, Y.P.; Thakurta, A.C.

    2013-01-01

    The capacitor charging power supply (CCPS) was developed to charge bank of 150uF energy storage capacitor (15uf , 10 nos in parallel) upto 1kV in 35 ms exhibiting a peak charging power of 2 kJ/s at a repetition rate of 25 pps. A CCPS observes a large change in load variations at the output. Initially the capacitor will act as a short circuit so the topology must be such that it should withstand short circuit condition repetitively. The High Voltage capacitor charging power supply consist of two identical full bridge resonant converters feeding to two primary windings of a transformer with rectified secondary connected to capacitor load. Topology selection is based on the fact that the series resonant converter with switching frequency f s , below 50% of the resonant frequency f r (f s ≤ 0.5 f r ) act as a current source. (author)

  10. Development on power distribution technologies of four electric power companies in Japan. The Kansai Electric Power Co. , Inc

    Energy Technology Data Exchange (ETDEWEB)

    1989-07-01

    Since dependency upon electric power has been rising yearly with the development of industry and the progress of information-oriented society, various kinds of technical development are needed to supply electricity. Furthermore, amenity of people's living has been highly intended, and life style has varied. Consequently, customers' needs for energy including related services have varied remarkably, and each customer has selected energy more subjectively from the wide range of viewpoint such as reliability, handiness, cleanliness, safety, and economic efficiency. In such situation, the power distribution section of Kansai Electric Power settled four themes for major technical development and has been promoting them. Four themes are as follows; to develop a total automation system for power distribution, to promote 20kV/400V-class power distribution, to develop techniques to form facilities harmonizing with local amenity, and to make business management efficient with the advanced NC system. 3 figs., 4 tabs.

  11. Non-Destructive Investigation on Short Circuit Capability of Wind-Turbine-Scale IGBT Power Modules

    DEFF Research Database (Denmark)

    Wu, Rui; Iannuzzo, Francesco; Wang, Huai

    2014-01-01

    This paper presents a comprehensive investigation on the short circuit capability of wind-turbine-scale IGBT power modules by means of a 6 kA/1.1 kV non-destructive testing system. A Field Programmable Gate Array (FPGA) supervising unit is adpoted to achieve an accurate time control for short...... circuit test, which enables to define the driving signals with an accuracy of 10 ns. Thanks to the capability and the effectiveness of the constructed setup, oscillations appearing during short circuits of the new-generation 1.7 kV/1 kA IGBT power modules have been evidenced and characterized under...

  12. ANALISIS PENGARUH REKONFIGURASI GROUNDING KABEL POWER 20 kV TERHADAP ERROR RATIO CURRENT TRANSFORMERS PELANGGAN TEGANGAN MENENGAH DI HOTEL GOLDEN TULIP SEMINYAK

    Directory of Open Access Journals (Sweden)

    Kadek Amerta Yasa

    2017-10-01

    Full Text Available Hotel Golden Tulip Seminyak  merupakan pelanggan listrik tegangan menengah yang sangat potensial. Pada penelitian di hotel ini,  kami menemukan bahwa error ratio trafo arus sebelum rekonfigurasi grounding berkisar – 67% dan rugi-rugi daya sebesar - 214.809,00 W pada persentase beban 20%.  Error ratio memengaruhi arus yang terbaca di sisi sekunder trafo dan juga memengaruhi rugi daya.  Upaya yang dilakukan untuk mengurangi nilai error ratio dan rugi daya tersebut yaitu dengan melakukan rekonfigurasi grounding yaitu dengan memindahkan posisi tap grounding kabel power 20 kV masuk kembali melalui sisi primer trafo arus.  Nilai error ratio setelah rekonfigurasi grounding diperoleh berkisar – 0,05% dan  rugi-rugi daya - 20,18 W pada persentase beban 20%.

  13. Strategies for Power/Energy Saving in Distribution Networks

    Directory of Open Access Journals (Sweden)

    GRIGORAS, G.

    2010-05-01

    Full Text Available The power/energy losses reduction in distribution systems is an important issue during planning and operation, with important technical and economical implications. Thus, the energy losses minimization implies not only the technical improvement of the network, through its renewal with the introduction of the technological innovations in the equipment and circuit components as well as the optimal planning of the design and development of the network, but also requires the use of the methods and software tools to facilitate the operation process. The paper presents a strategy for power/energy saving which replacement of the 6 kV voltage level with 20 kV voltage level in correlation with the extent of using efficient transformers. In this line, different urban distribution networks were analyzed using fuzzy techniques.

  14. Regulation of KV channel voltage-dependent activation by transmembrane β subunits

    Directory of Open Access Journals (Sweden)

    Xiaohui eSun

    2012-04-01

    Full Text Available Voltage-activated K+ (KV channels are important for shaping action potentials and maintaining resting membrane potential in excitable cells. KV channels contain a central pore-gate domain (PGD surrounded by four voltage-sensing domains (VSD. The VSDs will change conformation in response to alterations of the membrane potential thereby inducing the opening of the PGD. Many KV channels are heteromeric protein complexes containing auxiliary β subunits. These β subunits modulate channel expression and activity to increase functional diversity and render tissue specific phenotypes. This review focuses on the KV β subunits that contain transmembrane (TM segments including the KCNE family and the β subunits of large conductance, Ca2+- and voltage-activated K+ (BK channels. These TM β subunits affect the voltage-dependent activation of KV α subunits. Experimental and computational studies have described the structural location of these β subunits in the channel complexes and the biophysical effects on VSD activation, PGD opening and VSD-PGD coupling. These results reveal some common characteristics and mechanistic insights into KV channel modulation by TM β subunits.

  15. An accurate method for computer-generating tungsten anode x-ray spectra from 30 to 140 kV.

    Science.gov (United States)

    Boone, J M; Seibert, J A

    1997-11-01

    A tungsten anode spectral model using interpolating polynomials (TASMIP) was used to compute x-ray spectra at 1 keV intervals over the range from 30 kV to 140 kV. The TASMIP is not semi-empirical and uses no physical assumptions regarding x-ray production, but rather interpolates measured constant potential x-ray spectra published by Fewell et al. [Handbook of Computed Tomography X-ray Spectra (U.S. Government Printing Office, Washington, D.C., 1981)]. X-ray output measurements (mR/mAs measured at 1 m) were made on a calibrated constant potential generator in our laboratory from 50 kV to 124 kV, and with 0-5 mm added aluminum filtration. The Fewell spectra were slightly modified (numerically hardened) and normalized based on the attenuation and output characteristics of a constant potential generator and metal-insert x-ray tube in our laboratory. Then, using the modified Fewell spectra of different kVs, the photon fluence phi at each 1 keV energy bin (E) over energies from 10 keV to 140 keV was characterized using polynomial functions of the form phi (E) = a0[E] + a1[E] kV + a2[E] kV2 + ... + a(n)[E] kVn. A total of 131 polynomial functions were used to calculate accurate x-ray spectra, each function requiring between two and four terms. The resulting TASMIP algorithm produced x-ray spectra that match both the quality and quantity characteristics of the x-ray system in our laboratory. For photon fluences above 10% of the peak fluence in the spectrum, the average percent difference (and standard deviation) between the modified Fewell spectra and the TASMIP photon fluence was -1.43% (3.8%) for the 50 kV spectrum, -0.89% (1.37%) for the 70 kV spectrum, and for the 80, 90, 100, 110, 120, 130 and 140 kV spectra, the mean differences between spectra were all less than 0.20% and the standard deviations were less than approximately 1.1%. The model was also extended to include the effects of generator-induced kV ripple. Finally, the x-ray photon fluence in the units of

  16. Molecular and functional characterization of Kv7 K+ channel in murine gastrointestinal smooth muscles

    DEFF Research Database (Denmark)

    Jepps, Thomas Andrew; Greenwood, Iain A; Moffatt, James D

    2009-01-01

    that K(v)7.x especially K(v)7.4 and K(v)7.5 are expressed in different regions of the murine gastrointestinal tract and blockers of K(v)7 channels augment inherent contractile activity. Drugs that selectively block K(v)7.4/7.5 might be promising therapeutics for the treatment of motility disorders...

  17. Metal artifact correction for x-ray computed tomography using kV and selective MV imaging

    International Nuclear Information System (INIS)

    Wu, Meng; Keil, Andreas; Constantin, Dragos; Star-Lack, Josh; Zhu, Lei; Fahrig, Rebecca

    2014-01-01

    Purpose: The overall goal of this work is to improve the computed tomography (CT) image quality for patients with metal implants or fillings by completing the missing kilovoltage (kV) projection data with selectively acquired megavoltage (MV) data that do not suffer from photon starvation. When both of these imaging systems, which are available on current radiotherapy devices, are used, metal streak artifacts are avoided, and the soft-tissue contrast is restored, even for regions in which the kV data cannot contribute any information. Methods: Three image-reconstruction methods, including two filtered back-projection (FBP)-based analytic methods and one iterative method, for combining kV and MV projection data from the two on-board imaging systems of a radiotherapy device are presented in this work. The analytic reconstruction methods modify the MV data based on the information in the projection or image domains and then patch the data onto the kV projections for a FBP reconstruction. In the iterative reconstruction, the authors used dual-energy (DE) penalized weighted least-squares (PWLS) methods to simultaneously combine the kV/MV data and perform the reconstruction. Results: The authors compared kV/MV reconstructions to kV-only reconstructions using a dental phantom with fillings and a hip-implant numerical phantom. Simulation results indicated that dual-energy sinogram patch FBP and the modified dual-energy PWLS method can successfully suppress metal streak artifacts and restore information lost due to photon starvation in the kV projections. The root-mean-square errors of soft-tissue patterns obtained using combined kV/MV data are 10–15 Hounsfield units smaller than those of the kV-only images, and the structural similarity index measure also indicates a 5%–10% improvement in the image quality. The added dose from the MV scan is much less than the dose from the kV scan if a high efficiency MV detector is assumed. Conclusions: The authors have shown that it

  18. Metal artifact correction for x-ray computed tomography using kV and selective MV imaging

    Energy Technology Data Exchange (ETDEWEB)

    Wu, Meng, E-mail: mengwu@stanford.edu [Department of Electrical Engineering, Stanford University, Stanford, California 94305 (United States); Keil, Andreas [microDimensions GmbH, Munich 81379 (Germany); Constantin, Dragos; Star-Lack, Josh [Varian Medical Systems, Inc., Palo Alto, California 94304 (United States); Zhu, Lei [Nuclear and Radiological Engineering and Medical Physics Programs, The George W. Woodruff School of Mechanical Engineering, Georgia Institute of Technology, Atlanta, Georgia 30332 (United States); Fahrig, Rebecca [Department of Radiology, Stanford University, Stanford, California 94305 (United States)

    2014-12-15

    Purpose: The overall goal of this work is to improve the computed tomography (CT) image quality for patients with metal implants or fillings by completing the missing kilovoltage (kV) projection data with selectively acquired megavoltage (MV) data that do not suffer from photon starvation. When both of these imaging systems, which are available on current radiotherapy devices, are used, metal streak artifacts are avoided, and the soft-tissue contrast is restored, even for regions in which the kV data cannot contribute any information. Methods: Three image-reconstruction methods, including two filtered back-projection (FBP)-based analytic methods and one iterative method, for combining kV and MV projection data from the two on-board imaging systems of a radiotherapy device are presented in this work. The analytic reconstruction methods modify the MV data based on the information in the projection or image domains and then patch the data onto the kV projections for a FBP reconstruction. In the iterative reconstruction, the authors used dual-energy (DE) penalized weighted least-squares (PWLS) methods to simultaneously combine the kV/MV data and perform the reconstruction. Results: The authors compared kV/MV reconstructions to kV-only reconstructions using a dental phantom with fillings and a hip-implant numerical phantom. Simulation results indicated that dual-energy sinogram patch FBP and the modified dual-energy PWLS method can successfully suppress metal streak artifacts and restore information lost due to photon starvation in the kV projections. The root-mean-square errors of soft-tissue patterns obtained using combined kV/MV data are 10–15 Hounsfield units smaller than those of the kV-only images, and the structural similarity index measure also indicates a 5%–10% improvement in the image quality. The added dose from the MV scan is much less than the dose from the kV scan if a high efficiency MV detector is assumed. Conclusions: The authors have shown that it

  19. Metal artifact correction for x-ray computed tomography using kV and selective MV imaging.

    Science.gov (United States)

    Wu, Meng; Keil, Andreas; Constantin, Dragos; Star-Lack, Josh; Zhu, Lei; Fahrig, Rebecca

    2014-12-01

    The overall goal of this work is to improve the computed tomography (CT) image quality for patients with metal implants or fillings by completing the missing kilovoltage (kV) projection data with selectively acquired megavoltage (MV) data that do not suffer from photon starvation. When both of these imaging systems, which are available on current radiotherapy devices, are used, metal streak artifacts are avoided, and the soft-tissue contrast is restored, even for regions in which the kV data cannot contribute any information. Three image-reconstruction methods, including two filtered back-projection (FBP)-based analytic methods and one iterative method, for combining kV and MV projection data from the two on-board imaging systems of a radiotherapy device are presented in this work. The analytic reconstruction methods modify the MV data based on the information in the projection or image domains and then patch the data onto the kV projections for a FBP reconstruction. In the iterative reconstruction, the authors used dual-energy (DE) penalized weighted least-squares (PWLS) methods to simultaneously combine the kV/MV data and perform the reconstruction. The authors compared kV/MV reconstructions to kV-only reconstructions using a dental phantom with fillings and a hip-implant numerical phantom. Simulation results indicated that dual-energy sinogram patch FBP and the modified dual-energy PWLS method can successfully suppress metal streak artifacts and restore information lost due to photon starvation in the kV projections. The root-mean-square errors of soft-tissue patterns obtained using combined kV/MV data are 10-15 Hounsfield units smaller than those of the kV-only images, and the structural similarity index measure also indicates a 5%-10% improvement in the image quality. The added dose from the MV scan is much less than the dose from the kV scan if a high efficiency MV detector is assumed. The authors have shown that it is possible to improve the image quality of

  20. Improvement of ionizer and power supply of 860 A sputtering negative ion source

    International Nuclear Information System (INIS)

    An Kun; Yu Lingda; Wu Bingbing; Wang Guangfu

    2014-01-01

    A transmission surface type ionizer was developed with a φ2.5 mm stainless steel sheath core heating cable, and the ion source power supply was also improved. A continuous adjustable DC switching power supply was employed instead of the original AC power supply as the ionizer power supply, and a 0 - -20 kV DC power supply at the ground potential as the power of the immersion lens replaced the original 10 kV DC power supply suspended in -20 kV. The variation of the beam intensity of H"- in the front Faraday cup of the GIC4117 2 × 1.7 MV tandetron with the ionizer heating current was also shown. (authors)

  1. Power Outage - 16 October

    CERN Multimedia

    2014-01-01

    At 19:03 last night, a fire in an 18kV circuit breaker in building 212 led to a blackout on the Meyrin site. The CERN fire brigade rapidly brought the fire under control and power was restored by 22:25. Many CERN systems were affected and have been brought back in to service overnight, this work will continue through the day.

  2. Design study of the vertical field power supply for JT-60

    International Nuclear Information System (INIS)

    Yabuno, Kohei; Tani, Keiji; Shimada, Ryuichi; Kishimoto, Hiroshi; Yoshida, Hidetoshi

    1977-09-01

    The results of a basic design study of the vertical field power supply for JT-60 (JAERI large tokamak) are described. The objective of the study is to evaluate several types of power supply circuits for fast excitation and control of the vertical field. A design requirement is to produce a rapidly increasing vertical field within accuracy of +-5% around the proper field strength required to center the plasma in the vacuum vessel. The plasma current is assumed to increase at the rate of about 100 MA/sec. To meet the requirement, a maximum voltage of 15 kV is necessary in the current build-up time, while generally relatively low voltage is necessary after the current flattop is reached. A hybrid power supply which consists of a dc power source (a thyristor converter) and an inductive energy storage system is proposed. The maximum voltage of the dc power source is determined as 4 kV from the voltage required in the current flattop time. This is sufficient also in the current build-up time if the dc power source is used together with the inductive energy storage system. (auth.)

  3. The importance of immunohistochemical analyses in evaluating the phenotype of Kv channel knockout mice.

    Science.gov (United States)

    Menegola, Milena; Clark, Eliana; Trimmer, James S

    2012-06-01

    To gain insights into the phenotype of voltage-gated potassium (Kv)1.1 and Kv4.2 knockout mice, we used immunohistochemistry to analyze the expression of component principal or α subunits and auxiliary subunits of neuronal Kv channels in knockout mouse brains. Genetic ablation of the Kv1.1 α subunit did not result in compensatory changes in the expression levels or subcellular distribution of related ion channel subunits in hippocampal medial perforant path and mossy fiber nerve terminals, where high levels of Kv1.1 are normally expressed. Genetic ablation of the Kv4.2 α subunit did not result in altered neuronal cytoarchitecture of the hippocampus. Although Kv4.2 knockout mice did not exhibit compensatory changes in the expression levels or subcellular distribution of the related Kv4.3 α subunit, we found dramatic decreases in the cellular and subcellular expression of specific Kv channel interacting proteins (KChIPs) that reflected their degree of association and colocalization with Kv4.2 in wild-type mouse and rat brains. These studies highlight the insights that can be gained by performing detailed immunohistochemical analyses of Kv channel knockout mouse brains. Wiley Periodicals, Inc. © 2012 International League Against Epilepsy.

  4. SU-F-J-16: Planar KV Imaging Dose Reduction Study

    Energy Technology Data Exchange (ETDEWEB)

    Gershkevitsh, E; Zolotuhhin, D [North Estonia Medical Centre, Tallinn (Estonia)

    2016-06-15

    Purpose: IGRT has become an indispensable tool in modern radiotherapy with kV imaging used in many departments due to superior image quality and lower dose when compared to MV imaging. Many departments use manufacturer supplied protocols for imaging which are not always optimised between image quality and radiation dose (ALARA). Methods: Whole body phantom PBU-50 (Kyoto Kagaku ltd., Japan) for imaging in radiology has been imaged on Varian iX accelerator (Varian Medical Systems, USA) with OBI 1.5 system. Manufacturer’s default protocols were adapted by modifying kV and mAs values when imaging different anatomical regions of the phantom (head, thorax, abdomen, pelvis, extremities). Images with different settings were independently reviewed by two persons and their suitability for IGRT set-up correction protocols were evaluated. The suitable images with the lowest mAs were then selected. The entrance surface dose (ESD) for manufacturer’s default protocols and modified protocols were measured with RTI Black Piranha (RTI Group, Sweden) and compared. Image quality was also measured with kVQC phantom (Standard Imaging, USA) for different protocols. The modified protocols have been applied for clinical work. Results: For most cases optimized protocols reduced the ESD on average by a factor of 3(range 0.9–8.5). Further reduction in ESD has been observed by applying bow-tie filter designed for CBCT. The largest reduction in dose (12.2 times) was observed for Thorax lateral protocol. The dose was slightly increased (by 10%) for large pelvis AP protocol. Conclusion: Manufacturer’s default IGRT protocols could be optimised to reduce the ESD to the patient without losing the necessary image quality for patient set-up correction. For patient set-up with planar kV imaging the bony anatomy is mostly used and optimization should focus on this aspect. Therefore, the current approach with anthropomorphic phantom is more advantageous in optimization over standard kV quality

  5. Design for a FET based 1 MHz, 10 kV pulse generator

    International Nuclear Information System (INIS)

    Barnes, M.J.; Wait, G.D.

    1995-08-01

    A pulse generator consisting of a coaxial cable and a high voltage modulator, incorporating two stacks of Field-Effect Transistor (FET) switches operating in ''push-pull'' mode, has been designed and built. The modulator generates a continuous, unipolar, pulse train at a fundamental frequency of 1 MHz and a magnitude of 10 kV. The rise and fall times of the pulses are less than 39 ns. The two stacks each utilize 14 FETS, which are individually rated at 1 kV. The design incorporates a low-loss coaxial cable on which pulses are stored. Extensive PSpice simulations have been carried out to evaluate various design options. Subsequent measurements on the prototype pulse generator confirm the PSpice predictions. This system is applicable for the kicker system at TRIUMF

  6. Improvement of the dynamic response of the ITER Reactive Power Compensation system

    International Nuclear Information System (INIS)

    Finotti, Claudio; Gaio, Elena; Song, Inho; Tao, Jun; Benfatto, Ivone

    2015-01-01

    Highlights: • The slow response reasons of the classic ITER Reactive Power Compensation (RPC) control are explained. • The dynamic behaviors of the ac/dc converter and of the RPC are characterized. • New control concept to speed up the RPC response is developed. • Good performance of the new RPC control is verified even during fast transient conditions. - Abstract: The ITER ac/dc conversion system can absorb a total active and reactive power up to 500 MW and 950 Mvar, respectively. The Reactive Power Compensation (RPC) system is rated for a nominal power of 750 Mvar necessary to comply with the allowable reactive power limit value from the grid of 200 Mvar. This system is currently under construction and is based on Static Var Compensation technology with Thyristor Controlled Reactor (TCR) and Tuned Filters. The RPC has to minimize the demand of reactive power from the grid; its control is based on a feed-forward method, where the corrective input is the measurement of the reactive power consumption of the ac/dc converters, derived from the 50 Hz component of the Fast Fourier Transform (FFT) of the three-phase voltages and currents. The delay introduced by the FFT calculation and the slow response of the TCR could make the response speed of the RPC not sufficient to face fast variations of the reactive power demand and therefore in this paper a new controller of the RPC able to overcome this shortcoming is proposed and evaluated. It is based on the calculation of the predicted consumption of the reactive power by using the voltage reference signals coming from the Plasma Control System and the measurements of the dc current of the ac/dc converters and of the 66 kV busbar voltage, and on the speed up of the RPC control by introducing a lead–lag transfer function.

  7. Improvement of the dynamic response of the ITER Reactive Power Compensation system

    Energy Technology Data Exchange (ETDEWEB)

    Finotti, Claudio, E-mail: claudio.finotti@igi.cnr.it [Consorzio RFX (CNR, ENEA, INFN, Università di Padova, Acciaierie Venete SpA), Corso Stati Uniti 4, 35127 Padova (Italy); Gaio, Elena [Consorzio RFX (CNR, ENEA, INFN, Università di Padova, Acciaierie Venete SpA), Corso Stati Uniti 4, 35127 Padova (Italy); Song, Inho; Tao, Jun; Benfatto, Ivone [ITER Organization, Route de Vinon-sur-Verdon, CS 90 046, 13067 St. Paul Lez Durance Cedex (France)

    2015-10-15

    Highlights: • The slow response reasons of the classic ITER Reactive Power Compensation (RPC) control are explained. • The dynamic behaviors of the ac/dc converter and of the RPC are characterized. • New control concept to speed up the RPC response is developed. • Good performance of the new RPC control is verified even during fast transient conditions. - Abstract: The ITER ac/dc conversion system can absorb a total active and reactive power up to 500 MW and 950 Mvar, respectively. The Reactive Power Compensation (RPC) system is rated for a nominal power of 750 Mvar necessary to comply with the allowable reactive power limit value from the grid of 200 Mvar. This system is currently under construction and is based on Static Var Compensation technology with Thyristor Controlled Reactor (TCR) and Tuned Filters. The RPC has to minimize the demand of reactive power from the grid; its control is based on a feed-forward method, where the corrective input is the measurement of the reactive power consumption of the ac/dc converters, derived from the 50 Hz component of the Fast Fourier Transform (FFT) of the three-phase voltages and currents. The delay introduced by the FFT calculation and the slow response of the TCR could make the response speed of the RPC not sufficient to face fast variations of the reactive power demand and therefore in this paper a new controller of the RPC able to overcome this shortcoming is proposed and evaluated. It is based on the calculation of the predicted consumption of the reactive power by using the voltage reference signals coming from the Plasma Control System and the measurements of the dc current of the ac/dc converters and of the 66 kV busbar voltage, and on the speed up of the RPC control by introducing a lead–lag transfer function.

  8. Study and field verification of the effects of removing closing resistors from 500 kV circuit breakers

    International Nuclear Information System (INIS)

    Selin, D.A.; Agrawal, B.L.; Farmer, R.G.; Demcko, J.A.

    1992-01-01

    Closing resistors in EHV circuit breakers are frequently used to reduce switching transients on lines thus preventing flashovers during line energization. Maintenance and failures of such closing resistors can be costly and reduce transmission system reliability. For these reasons, APS conducted an investigation into the technical feasibility of operating its 500 kV without closing resistors. This paper describes study results of removing closing resistors from 500 kV breakers in a system which employs older technology silicon carbide type surge arresters. The paper also describes results of field tests of the expected flashover rates calculated in the study. These field tests involve repeatedly energizing a 258 mile 500 kV line using a breaker in which the closing resistors are disabled. Transient overvoltages captured during the tests are compared with predicted overvoltages. The study concludes that closing resistors may be removed from the subject system without unacceptable consequences

  9. Power transformers - Part 11: Dry-type transformers

    CERN Document Server

    International Electrotechnical Commission. Geneva

    2004-01-01

    Applies to dry-type power transformers (including auto-transformers) having values of highest voltage for equipment up to and including 36 kV and at least one winding operating at greater than 1,1 kV. Applies to all construction technologies.

  10. Space structures, power, and power conditioning; Proceedings of the Meeting, Los Angeles, CA, Jan. 11-13, 1988

    International Nuclear Information System (INIS)

    Askew, R.F.

    1988-01-01

    Various papers on space structures, power, and power conditioning are presented. Among the topics discussed are: heterogeneous gas core reaction for space nuclear power, pulsed gas core reactor for burst power, fundamental considerations of gas core reactor systems, oscillating thermionic conversion for high-density space power, thermoelectromagnetic pumps for space nuclear power systems, lightweight electrochemical converter for space power applications, ballistic acceleration by superheated hydrogen, laser-induced current switching in gaseous discharge, electron-beam-controlled semiconductor switches, laser-controlled semiconductor closing and opening switch. Also addressed are: semiconductor-metal eutectic composites for high-power switching, optical probes for the characterization of surface breakdown, 40 kV/20 kA pseudospark switch for laser applications, insulation direction for high-power space systems, state space simulation of spacecraft power systems, structural vibration of space power station systems, minimum-time control of large space structures, novel fusion reaction for space power and propulsion, repetition rate system evaluations, cryogenic silicon photoconductive switches for high-power lasers, multilevel diamondlike carbon capacitor structure, surface breakdown of prestressed insulators, C-Mo and C-Zr alloys for space power systems, magnetic insulation for the space environment

  11. 75 FR 75170 - Minnkota Power Cooperative, Inc.: Bemidji to Grand Rapids 230 kV Transmission Line Project

    Science.gov (United States)

    2010-12-02

    ... availability of Record of Decision. SUMMARY: The Rural Utilities Service, hereinafter referred to as RUS and/or the Agency, has issued a Record of Decision (ROD) for the Environmental Impact Statement (EIS) for the... financing to construct the 230 kilovolt (kV) transmission line between the Wilton Substation near Bemidji...

  12. Power converters for ITER

    CERN Document Server

    Benfatto, I

    2006-01-01

    The International Thermonuclear Experimental Reactor (ITER) is a thermonuclear fusion experiment designed to provide long deuterium– tritium burning plasma operation. After a short description of ITER objectives, the main design parameters and the construction schedule, the paper describes the electrical characteristics of the French 400 kV grid at Cadarache: the European site proposed for ITER. Moreover, the paper describes the main requirements and features of the power converters designed for the ITER coil and additional heating power supplies, characterized by a total installed power of about 1.8 GVA, modular design with basic units up to 90 MVA continuous duty, dc currents up to 68 kA, and voltages from 1 kV to 1 MV dc.

  13. The 12th 735-kV transmission line project: Hydro-Quebec network

    International Nuclear Information System (INIS)

    1992-01-01

    Hydro-Quebec is proposing to construct a 735-kV transmission line from the Chissibi station near the LG3 hydroelectric power plant to the Jacques-Cartier station near Quebec City. The width of the right-of-way will generally be 90 m and it is intended to install the line in two stages. The Chissibi-Chibougamau section should enter service in 1993 and the Chibougamau-Cartier section in 1994. The cost of the line is estimated at $1.21 billion, of which $900 million is for line construction and $310 million for station equipment. Prospective corridors for the line route have been selected, portions of which enable twinning with Hydro-Quebec's existing 9th 735-kV line. A series of hearings on the environmental and other impacts of the power line project was held by the Bureau d'audiences publiques sur l'environnement and results are summarized along with the views of the Bureau. The summary describes the justification for the project, the choice of the transmission line route, the evaluation of the impacts of the project on the natural and human environments, health effects due to magnetic fields, and effects on the economic development of northern Quebec. Recommendations are given for mitigating the impacts of the project. 13 refs., 8 figs., 2 tabs

  14. High voltage system design for the IUCF 300 KV electron cooling system

    International Nuclear Information System (INIS)

    Bertuccio, T.; Brown, B.; Donica, G.; Ellison, T.; Friesel, D.L.

    1985-01-01

    A summary of the electron beam high voltage system design for the IUCF Cooler now under construction, is presented. There are extremely stringent regulation requirements (about 10ppm) on the main high voltage power supply (-300 kVDC, 15 mA), and less stringent requirements on the gun anode power supply, in order to achieve the regulation needed to store beams in the IUCF Cooler with very low momentum spreads (Δp/p approx. = 2 x 10 -5 ). An overview of the main high voltage power supply (HVPS) specifications and design, as well as provisions and plans to improve the regulation are discussed. The electron collection system, modeled after the FNAL collector which was able to collect between 99.9% and 99.99% of the electron beam, is discussed along with the requirements of the associated power supplies. The designs of the high voltage acceleration structures and high voltage platform are discussed, as well as practical design considerations based upon experience with the Fermilab 120 keV electron cooling system

  15. High reliability low jitter 80 kV pulse generator

    International Nuclear Information System (INIS)

    Savage, Mark Edward; Stoltzfus, Brian Scott

    2009-01-01

    Switching can be considered to be the essence of pulsed power. Time accurate switch/trigger systems with low inductance are useful in many applications. This article describes a unique switch geometry coupled with a low-inductance capacitive energy store. The system provides a fast-rising high voltage pulse into a low impedance load. It can be challenging to generate high voltage (more than 50 kilovolts) into impedances less than 10 (Omega), from a low voltage control signal with a fast rise time and high temporal accuracy. The required power amplification is large, and is usually accomplished with multiple stages. The multiple stages can adversely affect the temporal accuracy and the reliability of the system. In the present application, a highly reliable and low jitter trigger generator was required for the Z pulsed-power facility [M. E. Savage, L. F. Bennett, D. E. Bliss, W. T. Clark, R. S. Coats,J. M. Elizondo, K. R. LeChien, H. C. Harjes, J. M. Lehr, J. E. Maenchen, D. H. McDaniel, M. F. Pasik, T. D. Pointon, A. C. Owen, D. B. Seidel, D. L. Smith, B. S. Stoltzfus, K.W. Struve, W.A. Stygar, L.K. Warne, and J. R. Woodworth, 2007 IEEE Pulsed Power Conference, Albuquerque, NM (IEEE, Piscataway, NJ, 2007), p. 979]. The large investment in each Z experiment demands low prefire probability and low jitter simultaneously. The system described here is based on a 100 kV DC-charged high-pressure spark gap, triggered with an ultraviolet laser. The system uses a single optical path for simultaneously triggering two parallel switches, allowing lower inductance and electrode erosion with a simple optical system. Performance of the system includes 6 ns output rise time into 5.6 (Omega), 550 ps one-sigma jitter measured from the 5 V trigger to the high voltage output, and misfire probability less than 10 -4 . The design of the system and some key measurements will be shown in the paper. We will discuss the design goals related to high reliability and low jitter. While

  16. Superconducting power cables in Denmark - a case study

    DEFF Research Database (Denmark)

    Østergaard, Jacob

    1997-01-01

    A case study of a 450 MVA, 132 kV high temperature superconducting (HTS) power transmission cable has been carried out. In the study, a superconducting cable system is compared to a conventional cable system which is under construction for an actual transmission line in the Danish grid. The study...... that HTS cables will be less expensive for high power ratings, have lower losses for lines with a high load, and have a reduced reactive power production. The use of superconducting cables in Denmark accommodate plans by the Danish utility to make a substantial conversion of overhead lines to underground...

  17. SNS EXTRACTION KICKER POWER SUPPLY PROTOTYPE TEST

    International Nuclear Information System (INIS)

    MI, J.L.; SANDBERG, J.; SANDERS, R.; SOUKAS, A.; ZHANG, W.

    2000-01-01

    The SNS (Spallation Neutron Source) accumulator ring Extraction System consists of a Fast kicker and a Lambertson Septum magnet. The proposed design will use 14 kicker magnets powered by an Extraction Kicker Power Supply System. They will eject the high power beam from the SNS accumulator ring into RTBT (Ring to Target Beam Tunnel) through a Lambertson Septum magnet. This paper describes some test results of the SNS Extraction Kicker power supply prototype. The high repetition rate of 60 pulse per second operation is the challenging part of the design. In the prototype testing, a 3 kA damp current of 700ns pulse-width, 200 nS rise time and 60 Hz repetition rate at 32 kV PFN operation voltage has been demonstrated. An Extraction kicker power supply system design diagram is depicted

  18. A Study on the construction of 22.9 kV distribution test line of KEPCO

    Energy Technology Data Exchange (ETDEWEB)

    Yang, Hi Kyun; Choi, Hung Sik; Hwang, Si Dole; Jung, Young Ho [Korea Electric Power Corp. (KEPCO), Taejon (Korea, Republic of). Research Center; Kim, Dong Hwan; Choi, Chang Huk [Korea Power Engineering Company and Architecture Engineers (Korea, Republic of)

    1995-12-31

    In order to enhance the reliability of power supply and the quality of electricity, a study on the construction of 22.9 kV distribution test line was performed. The main objective of this study was to establish a construction plan and a basic design to perform the construction and the detailed design of the test line effectively. (author). 21 refs., 45 figs.

  19. A novel synthetic test system for thyristor level in the converter valve of HVDC power transmission

    Directory of Open Access Journals (Sweden)

    Liu Longchen

    2016-01-01

    Full Text Available The converter valve is the core equipment in the HVDC power transmission system, a+-nd its performance has a direct effect on the reliability, stability and efficiency of the whole power system. As the basic unit of HVDC converter valve, the thyristor level needs to be test routinely in order to grasp the state of the converter valve equipment. Therefore, it is urgent to develop a novel synthetic test system for the thyristor level with thyristor control unit (TCU. However, currently there is no specific test scheme for the thyristor level of HVDC converter valve. In this paper, the synthetic test principle, content and methods for the thyristor level with TCU are presented based on the analysis of the thyristor reverse recovery characteristic and the IEC technology standard. And a transient high-voltage pulse is applied to the thyristor level during its reverse recovery period in order to test the characteristics of thyristor level. Then, the synthetic test system for the thyristor level is applied to the converter valve test of ±800 kV HVDC power transmission project, and the practical test result verifies the reasonability and validity of the proposed synthetic test system.

  20. Electric power transmission for a Hanford Nuclear Energy Center (HNEC)

    International Nuclear Information System (INIS)

    1975-09-01

    The major issues examined in the comparison of the DIST and HNEC transmission concepts are: (1) type of transmission to be employed and an assessment of its technical feasibility, (2) availability of rights-of-way, (3) economics, (4) environmental impact, and (5) overall reliability of the transmission system. The type of transmission selected for bulk power transfer from an HNEC for the time period studied is overhead AC, 500 kV double or single circuit, a voltage currently used in the PNW system. This type of system can accommodate growth up to at least 23,000 MW of thermal capacity at an HNEC. Significant additional transmountain capacity needs would require 1100 kV transmission, which should be technologically proved by the end of the 1970s. (auth)

  1. Expression and function of K(V)2-containing channels in human urinary bladder smooth muscle.

    Science.gov (United States)

    Hristov, Kiril L; Chen, Muyan; Afeli, Serge A Y; Cheng, Qiuping; Rovner, Eric S; Petkov, Georgi V

    2012-06-01

    The functional role of the voltage-gated K(+) (K(V)) channels in human detrusor smooth muscle (DSM) is largely unexplored. Here, we provide molecular, electrophysiological, and functional evidence for the expression of K(V)2.1, K(V)2.2, and the electrically silent K(V)9.3 subunits in human DSM. Stromatoxin-1 (ScTx1), a selective inhibitor of K(V)2.1, K(V)2.2, and K(V)4.2 homotetrameric channels and of K(V)2.1/9.3 heterotetrameric channels, was used to examine the role of these channels in human DSM function. Human DSM tissues were obtained during open bladder surgeries from patients without a history of overactive bladder. Freshly isolated human DSM cells were studied using RT-PCR, immunocytochemistry, live-cell Ca(2+) imaging, and the perforated whole cell patch-clamp technique. Isometric DSM tension recordings of human DSM isolated strips were conducted using tissue baths. RT-PCR experiments showed mRNA expression of K(V)2.1, K(V)2.2, and K(V)9.3 (but not K(V)4.2) channel subunits in human isolated DSM cells. K(V)2.1 and K(V)2.2 protein expression was confirmed by Western blot analysis and immunocytochemistry. Perforated whole cell patch-clamp experiments revealed that ScTx1 (100 nM) inhibited the amplitude of the voltage step-induced K(V) current in freshly isolated human DSM cells. ScTx1 (100 nM) significantly increased the intracellular Ca(2+) level in DSM cells. In human DSM isolated strips, ScTx1 (100 nM) increased the spontaneous phasic contraction amplitude and muscle force, and enhanced the amplitude of the electrical field stimulation-induced contractions within the range of 3.5-30 Hz stimulation frequencies. These findings reveal that ScTx1-sensitive K(V)2-containing channels are key regulators of human DSM excitability and contractility and may represent new targets for pharmacological or genetic intervention for bladder dysfunction.

  2. 110 kV NETWORK TECHNICAL LOSSES ASSESSMENT. REAL DISTRIBUTION SYSTEM CASE STUDY

    Directory of Open Access Journals (Sweden)

    BARBULESCU C.

    2015-06-01

    Full Text Available The paper is focusing on evaluating the technical losses within a real distribution network. The study was conducted for a distribution system operator within the Romanian Power System. The analysed area is represented by a real part of the Romanian Power System. It is modelled in a computer aided power system analysis tool. Several power system operating conditions are analysed. Power system optimization measures are provided having as a goal to reduce the technical losses' value. Values obtained based on the field measurement are compared to the ones provided by computer simulations. These conclusions are very useful for the distribution network operator.

  3. Modeling and Simulation of Transient Fault Response at Lillgrund Wind Farm when Subjected to Faults in the Connecting 130 kV Grid

    Energy Technology Data Exchange (ETDEWEB)

    Eliasson, Anders; Isabegovic, Emir

    2009-07-01

    The purpose of this thesis was to investigate what type of faults in the connecting grid should be dimensioning for future wind farms. An investigation of over and under voltages at the main transformer and the turbines inside Lillgrund wind farm was the main goal. The results will be used in the planning stage of future wind farms when performing insulation coordination and determining the protection settings. A model of the Lillgrund wind farm and a part of the connecting 130 kV grid were built in PSCAD/EMTDC. The farm consists of 48 Siemens SWT-2.3-93 2.3 MW wind turbines with full power converters. The turbines were modeled as controllable current sources providing a constant active power output up to the current limit of 1.4 pu. The transmission lines and cables were modeled as frequency dependent (phase) models. The load flows and bus voltages were verified towards a PSS/E model and the transient response was verified towards measuring data from two faults, a line to line fault in the vicinity of Barsebaeck (BBK) and a single line-to-ground fault close to Bunkeflo (BFO) substation. For the simulation, three phase to ground, single line to ground and line to line faults were applied at different locations in the connecting grid and the phase to ground voltages at different buses in the connecting grid and at turbines were studied. These faults were applied for different configurations of the farm. For single line to ground faults, the highest over voltage on a turbine was 1.22 pu (32.87 kV) due to clearing of a fault at BFO (the PCC). For line to line faults, the highest over voltage on a turbine was 1.59 pu (42.83 kV) at the beginning of a fault at KGE one bus away from BFO. Both these cases were when all radials were connected and the turbines ran at full power. The highest over voltage observed at Lillgrund was 1.65 pu (44.45 kV). This over voltage was caused by a three phase to ground fault applied at KGE and occurred at the beginning of the fault and when

  4. Evaluation of “direct input” effectiveness for industrial enterprises power supply

    Directory of Open Access Journals (Sweden)

    Malinina Tatyana

    2017-01-01

    Full Text Available The cost of energy has increased significantly for the industrial enterprises over the recent years, due to an increase in the electricity tariffs and the changes in the rules of the electricity market. Tariffs for electricity sold to consumers, differentiated according to various parameters, one of which is the voltage range. The higher the voltage range, the lower the tariffs, and thus, the consumer pays less for the supplied energy. Currently only for big consumers made energy supply “direct input” through the construction of an overhead line (OL with a nominal voltage of 110 kV or 220 kV. However, it is advisable to consider the issue of power supply efficiency of big and medium-sized industrial enterprises based on the “direct input”. The questions of voltage level study based on empirical formulas are considered in the article, expressing the dependence of the voltage from the transmission distance and the amount of transmitted power. It was proven that these formulas give a large spread, so intermediate voltage classes 35 kV and 110 kV, which compared with the traditional option of power supply on the basis of the cable line 10 kV, have been selected. Based on the technical and economic calculations it has been proved the value of the transmit power and length of the line at which the power supply of industrial enterprise on the basis of “ direct input” with a nominal voltage of 110 kV becomes effective.

  5. Interconnected High-Voltage Pulsed-Power Converters System Design for H− Ion Sources

    CERN Document Server

    Aguglia, D

    2014-01-01

    This paper presents the design and experimental validations of a system of three new high-voltage (HV) pulsedpower converters for the H− sources. The system requires three pulsed voltages (50, 40, and 25 kV to ground) at 2-Hz repetition rate, for 700 μs of usable flat-top. The solution presents ripplefree output voltages and minimal stored energy to protect the ion source from the consequences of arc events. Experimental results on the final full-scale prototype are presented. In case of short-circuit events, the maximal energy delivered to the source is in the Joule range. HV flat-top stability of 1% is experimentally achieved with a simple Proportional-Integral- Derivative regulation and preliminary tuned H− source (e.g., radio frequency control, gas injection, and so forth). The system is running since more than a year with no power converter failures and damage to the source.

  6. The development of a 200 kV monochromated field emission electron source

    Energy Technology Data Exchange (ETDEWEB)

    Mukai, Masaki, E-mail: mmukai@jeol.co.jp [JEOL Ltd., 3-1-2 Musashino, Akishima, Tokyo 196-8558 (Japan); Kim, Judy S. [University of Oxford, Department of Materials, Parks Road, Oxford, OX1 3PH (United Kingdom); Omoto, Kazuya; Sawada, Hidetaka; Kimura, Atsushi; Ikeda, Akihiro; Zhou, Jun; Kaneyama, Toshikatsu [JEOL Ltd., 3-1-2 Musashino, Akishima, Tokyo 196-8558 (Japan); Young, Neil P.; Warner, Jamie H.; Nellist, Peter D.; Kirkland, Angus I. [University of Oxford, Department of Materials, Parks Road, Oxford, OX1 3PH (United Kingdom)

    2014-05-01

    We report the development of a monochromator for an intermediate-voltage aberration-corrected electron microscope suitable for operation in both STEM and TEM imaging modes. The monochromator consists of two Wien filters with a variable energy selecting slit located between them and is located prior to the accelerator. The second filter cancels the energy dispersion produced by the first filter and after energy selection forms a round monochromated, achromatic probe at the specimen plane. The ultimate achievable energy resolution has been measured as 36 meV at 200 kV and 26 meV at 80 kV. High-resolution Annular Dark Field STEM images recorded using a monochromated probe resolve Si–Si spacings of 135.8 pm using energy spreads of 218 meV at 200 kV and 217 meV at 80 kV respectively. In TEM mode an improvement in non-linear spatial resolution to 64 pm due to the reduction in the effects of partial temporal coherence has been demonstrated using broad beam illumination with an energy spread of 134 meV at 200 kV. - Highlights: • Monochromator for 200 kV aberration corrected TEM and STEM was developed. • Monochromator produces monochromated and achromatic probe at specimen plane. • Ultimate energy resolution was measured to be 36 meV at 200 kV and 26 meV at 80 kV. • Atomic resolution STEM images were recorded using monochromated electron probe. • Improvements of TEM resolution were confirmed using monochromated illumination.

  7. The development of a 200 kV monochromated field emission electron source

    International Nuclear Information System (INIS)

    Mukai, Masaki; Kim, Judy S.; Omoto, Kazuya; Sawada, Hidetaka; Kimura, Atsushi; Ikeda, Akihiro; Zhou, Jun; Kaneyama, Toshikatsu; Young, Neil P.; Warner, Jamie H.; Nellist, Peter D.; Kirkland, Angus I.

    2014-01-01

    We report the development of a monochromator for an intermediate-voltage aberration-corrected electron microscope suitable for operation in both STEM and TEM imaging modes. The monochromator consists of two Wien filters with a variable energy selecting slit located between them and is located prior to the accelerator. The second filter cancels the energy dispersion produced by the first filter and after energy selection forms a round monochromated, achromatic probe at the specimen plane. The ultimate achievable energy resolution has been measured as 36 meV at 200 kV and 26 meV at 80 kV. High-resolution Annular Dark Field STEM images recorded using a monochromated probe resolve Si–Si spacings of 135.8 pm using energy spreads of 218 meV at 200 kV and 217 meV at 80 kV respectively. In TEM mode an improvement in non-linear spatial resolution to 64 pm due to the reduction in the effects of partial temporal coherence has been demonstrated using broad beam illumination with an energy spread of 134 meV at 200 kV. - Highlights: • Monochromator for 200 kV aberration corrected TEM and STEM was developed. • Monochromator produces monochromated and achromatic probe at specimen plane. • Ultimate energy resolution was measured to be 36 meV at 200 kV and 26 meV at 80 kV. • Atomic resolution STEM images were recorded using monochromated electron probe. • Improvements of TEM resolution were confirmed using monochromated illumination

  8. Modeling-independent elucidation of inactivation pathways in recombinant and native A-type Kv channels

    Science.gov (United States)

    Fineberg, Jeffrey D.; Ritter, David M.

    2012-01-01

    A-type voltage-gated K+ (Kv) channels self-regulate their activity by inactivating directly from the open state (open-state inactivation [OSI]) or by inactivating before they open (closed-state inactivation [CSI]). To determine the inactivation pathways, it is often necessary to apply several pulse protocols, pore blockers, single-channel recording, and kinetic modeling. However, intrinsic hurdles may preclude the standardized application of these methods. Here, we implemented a simple method inspired by earlier studies of Na+ channels to analyze macroscopic inactivation and conclusively deduce the pathways of inactivation of recombinant and native A-type Kv channels. We investigated two distinct A-type Kv channels expressed heterologously (Kv3.4 and Kv4.2 with accessory subunits) and their native counterparts in dorsal root ganglion and cerebellar granule neurons. This approach applies two conventional pulse protocols to examine inactivation induced by (a) a simple step (single-pulse inactivation) and (b) a conditioning step (double-pulse inactivation). Consistent with OSI, the rate of Kv3.4 inactivation (i.e., the negative first derivative of double-pulse inactivation) precisely superimposes on the profile of the Kv3.4 current evoked by a single pulse because the channels must open to inactivate. In contrast, the rate of Kv4.2 inactivation is asynchronous, already changing at earlier times relative to the profile of the Kv4.2 current evoked by a single pulse. Thus, Kv4.2 inactivation occurs uncoupled from channel opening, indicating CSI. Furthermore, the inactivation time constant versus voltage relation of Kv3.4 decreases monotonically with depolarization and levels off, whereas that of Kv4.2 exhibits a J-shape profile. We also manipulated the inactivation phenotype by changing the subunit composition and show how CSI and CSI combined with OSI might affect spiking properties in a full computational model of the hippocampal CA1 neuron. This work unambiguously

  9. Soil scientific survey of 220/38 kV cable circuits of the power station 'Eemscentrale' in the Dutch province Groningen; Theoretical backgrounds, research method and results

    International Nuclear Information System (INIS)

    Langevoord, J.; Van Loon, L.J.M.

    1995-01-01

    Recently, five underground cable circuits were completed at the site of the EPON (an energy utility for the north-eastern part of the Netherlands) title power station, consisting of two 220 kV and two 380 kV connections with a total length of 24 km. Soil scientific in situ investigations and laboratory tests were carried out in advance to collect data, on the basis of which thermal resistivity and critical thermal conditions could be calculated. It was demonstrated by the calculated results that no de-hydrated zones occurred around the cable for design criteria conditions. Optimal cable bed conditions could be achieved, using some of the sand excavated from the trench. In this article, attention will be paid to theoretical aspects of heat transfer of cables for underground electricity transport, the research method of the soil scientific survey, and the results of the survey for the design of the cable connection, to be made by NKF (cable manufacturer) and for the final execution of the cable design. In the second article, to be published in a next issue of this magazine, attention will be paid to soil scientific marginal conditions and soil scientific supervision during the realization. 9 figs., 6 tabs., 9 refs

  10. Section 1: Alberta Power Limited

    International Nuclear Information System (INIS)

    Kothari, R.; Quinn, D.

    1991-01-01

    A study was carried out to produce a compendium of electric and magnetic field levels that exist in Canada and to characterize and classify the sources of electric and magnetic fields. Alberta Power's contribution to this project was mainly to measure electric and magnetic fields produced by transmission lines in their service area in Alberta. Ten 240 kV transmission lines, ten 144 kV transmission lines, one 72 kV transmission line, two 25 kV distribution lines, two substations, and one residence were monitored for 60 Hz electric and magnetic field levels. For the 240 kV transmission lines, the electric field ranged from 0.4 kV/m to 1.9 kV/m and the magnetic field from 2.5 milligauss to 27 milligauss at the edge of the right-of-way. For 144 kV lines, the electric and magnetic fields ranged from 0.24-1.00 kV/m and 2.25-12.00 milligauss, respectively, at the edge of the right-of-way. 5 tabs

  11. Future 400 kV Algerian network and radio electric disturbances in dry weather and under rain

    Directory of Open Access Journals (Sweden)

    Brahami M.

    2007-01-01

    Full Text Available The development of the electrical power networks to very high voltage (V.H.V reveals problems involved in the high electric fields; it is essential to consider it in the design of installations in order to avoid or to mitigate some problematic or dangerous effects. Among the most important harmful effects, we can note the "radio interference disturbances". The principal aim of this paper is the use of a simulation programme using an analytical method based on the theory of propagation modes, made by one of the authors, for determination and calculation of the exact profile of disturbance field of actual high voltage lines (220 kV and in project (400 kV in dry weather and under rain. Specific software called "effect corona" was developed for this purpose.

  12. KCNE1 constrains the voltage sensor of Kv7.1 K+ channels.

    Directory of Open Access Journals (Sweden)

    Liora Shamgar

    Full Text Available Kv7 potassium channels whose mutations cause cardiovascular and neurological disorders are members of the superfamily of voltage-gated K(+ channels, comprising a central pore enclosed by four voltage-sensing domains (VSDs and sharing a homologous S4 sensor sequence. The Kv7.1 pore-forming subunit can interact with various KCNE auxiliary subunits to form K(+ channels with very different gating behaviors. In an attempt to characterize the nature of the promiscuous gating of Kv7.1 channels, we performed a tryptophan-scanning mutagenesis of the S4 sensor and analyzed the mutation-induced perturbations in gating free energy. Perturbing the gating energetics of Kv7.1 bias most of the mutant channels towards the closed state, while fewer mutations stabilize the open state or the inactivated state. In the absence of auxiliary subunits, mutations of specific S4 residues mimic the gating phenotypes produced by co-assembly of Kv7.1 with either KCNE1 or KCNE3. Many S4 perturbations compromise the ability of KCNE1 to properly regulate Kv7.1 channel gating. The tryptophan-induced packing perturbations and cysteine engineering studies in S4 suggest that KCNE1 lodges at the inter-VSD S4-S1 interface between two adjacent subunits, a strategic location to exert its striking action on Kv7.1 gating functions.

  13. Sidney-North Yuma 230-kV Transmission Line Project, Colorado and Nebraska

    Energy Technology Data Exchange (ETDEWEB)

    1991-06-01

    This report describes the need for a 230-kV overhead transmission line to supply power from Sidney, Nebraska to eastern Colorado. The alternative scenario compared to construction of the line is No Action. Rejected alternatives include underground lines and different routing paths, with a possible extension to the Sterling area. Both scenarios are evaluated for environmental effects, cost, and consequences for the eastern Colorado region. The proposed route is determined to be the environmentally preferred choice. 120 refs., 6 figs., 13 tabs. (MHB)

  14. Identification of a functional interaction between Kv4.3 channels and c-Src tyrosine kinase.

    Science.gov (United States)

    Gomes, Pedro; Saito, Tomoaki; Del Corsso, Cris; Alioua, Abderrahmane; Eghbali, Mansoureh; Toro, Ligia; Stefani, Enrico

    2008-10-01

    Voltage-gated K(+) (Kv) channels are key determinants of cardiac and neuronal excitability. A substantial body of evidence has accumulated in support of a role for Src family tyrosine kinases in the regulation of Kv channels. In this study, we examined the possibility that c-Src tyrosine kinase participates in the modulation of the transient voltage-dependent K(+) channel Kv4.3. Supporting a mechanistic link between Kv4.3 and c-Src, confocal microscopy analysis of HEK293 cells stably transfected with Kv4.3 showed high degree of co-localization of the two proteins at the plasma membrane. Our results further demonstrate an association between Kv4.3 and c-Src by co-immunoprecipitation and GST pull-down assays, this interaction being mediated by the SH2 and SH3 domains of c-Src. Furthermore, we show that Kv4.3 is tyrosine phosphorylated under basal conditions. The functional relevance of the observed interaction between Kv4.3 and c-Src was established in patch-clamp experiments, where application of the Src inhibitor PP2 caused a decrease in Kv4.3 peak current amplitude, but not the inactive structural analogue PP3. Conversely, intracellular application of recombinant c-Src kinase or the protein tyrosine phosphatase inhibitor bpV(phen) increased Kv4.3 peak current amplitude. In conclusion, our findings provide evidence that c-Src-induced Kv4.3 channel activation involves their association in a macromolecular complex and suggest a role for c-Src-Kv4.3 pathway in regulating cardiac and neuronal excitability.

  15. Flatiron-Erie 115kV transmission line project, Larimer, Weld and Boulder Counties, Colorado

    International Nuclear Information System (INIS)

    1993-05-01

    Western Area Power Administration (Western) proposes to uprate its existing 115-kV Flatiron-Erie transmission line. The line is located in Larimer, Weld and Boulder Counties, Colorado, and passes through the City of Longmont. The line connects Flatiron Substation and several of the substations supplying Longmont. It is a single circuit 115-kV line, 31.5 miles long, and was built in 1950-51 on a 75-foot wide right-of-way (ROW) using wood H-frame structures. Western proposes to build 27 new structures along the line, to replace or modify 45 of the existing structures and to remote 11 of them. Many of these additions and changes would involve structures that are approximately 5 to 15 feet taller than the existing ones. The existing conductors and ground wires would remain in place. The purpose of these actions would be to allow the power carrying capability of the line to be increased and to replace deteriorating/structural members. Western would be the sole participant in the proposed project. This report gives an analysis of the study area environment and the development of alternative routes. An assessment is presented of the impacts of the primary alternative routes. The environmental consequences of this project are addressed

  16. MicroRNA-301a mediated regulation of Kv4.2 in diabetes: identification of key modulators.

    Directory of Open Access Journals (Sweden)

    Siva K Panguluri

    Full Text Available Diabetes is a metabolic disorder that ultimately results in major pathophysiological complications in the cardiovascular system. Diabetics are predisposed to higher incidences of sudden cardiac deaths (SCD. Several studies have associated diabetes as a major underlying risk for heart diseases and its complications. The diabetic heart undergoes remodeling to cope up with the underlying changes, however ultimately fails. In the present study we investigated the changes associated with a key ion channel and transcriptional factors in a diabetic heart model. In the mouse db/db model, we identified key transcriptional regulators and mediators that play important roles in the regulation of ion channel expression. Voltage-gated potassium channel (Kv4.2 is modulated in diabetes and is down regulated. We hypothesized that Kv4.2 expression is altered by potassium channel interacting protein-2 (KChIP2 which is regulated upstream by NFkB and miR-301a. We utilized qRT-PCR analysis and identified the genes that are affected in diabetes in a regional specific manner in the heart. At protein level we identified and validated differential expression of Kv4.2 and KChIP2 along with NFkB in both ventricles of diabetic hearts. In addition, we identified up-regulation of miR-301a in diabetic ventricles. We utilized loss and gain of function approaches to identify and validate the role of miR-301a in regulating Kv4.2. Based on in vivo and in vitro studies we conclude that miR-301a may be a central regulator for the expression of Kv4.2 in diabetes. This miR-301 mediated regulation of Kv4.2 is independent of NFkB and Irx5 and modulates Kv4.2 by direct binding on Kv4.2 3'untranslated region (3'-UTR. Therefore targeting miR-301a may offer new potential for developing therapeutic approaches.

  17. Electron cyclotron heating/current-drive system using high power tubes for QUEST spherical tokamak

    Science.gov (United States)

    Onchi, Takumi; Idei, H.; Hasegawa, M.; Nagata, T.; Kuroda, K.; Hanada, K.; Kariya, T.; Kubo, S.; Tsujimura, T. I.; Kobayashi, S.; Quest Team

    2017-10-01

    Electron cyclotron heating (ECH) is the primary method to ramp up plasma current non-inductively in QUEST spherical tokamak. A 28 GHz gyrotron is employed for short pulses, where the radio frequency (RF) power is about 300 kW. Current ramp-up efficiency of 0.5 A/W has been obtained with focused beam of the second harmonic X-mode. A quasi-optical polarizer unit has been newly installed to avoid arcing events. For steady-state tokamak operation, 8.56 GHz klystron with power of 200 kW is used as the CW-RF source. The high voltage power supply (54 kV/13 A) for the klystron has been built recently, and initial bench test of the CW-ECH system is starting. The array of insulated-gate bipolar transistor works to quickly cut off the input power for protecting the klystron. This work is supported by JSPS KAKENHI (15H04231), NIFS Collaboration Research program (NIFS13KUTR085, NIFS17KUTR128), and through MEXT funding for young scientists associated with active promotion of national university reforms.

  18. High-power semiconductor RSD-based switch

    Energy Technology Data Exchange (ETDEWEB)

    Bezuglov, V G; Galakhov, I V; Grusin, I A [All-Russian Scientific Research Inst. of Experimental Physics, Sarov (Russian Federation); and others

    1997-12-31

    The operating principle and test results of a high-power semiconductor RSD-based switch with the following operating parameters is described: operating voltage 25 kV, peak operating current 200 kA, maximum transferred charge 70 C. The switch is intended for use by high-power capacitor banks of state-of-the-art research facilities. The switch was evaluated for applicability in commercial pulsed systems. The possibility of increasing the peak operating current to 500 kA is demonstrated. (author). 4 figs., 2 refs.

  19. Cusp Guns for Helical-Waveguide Gyro-TWTs of a High-Gain High-Power W-Band Amplifier Cascade

    Science.gov (United States)

    Manuilov, V. N.; Samsonov, S. V.; Mishakin, S. V.; Klimov, A. V.; Leshcheva, K. A.

    2018-02-01

    The evaluation, design, and simulations of two different electron guns generating the beams for W-band second cyclotron harmonic gyro-TWTs forming a high-gain powerful amplifier cascade are presented. The optimum configurations of the systems creating nearly axis-encircling electron beams having velocity pitch-factor up to 1.5, voltage/current of 40 kV/0.5 A, and 100 kV/13 A with acceptable velocity spreads have been found and are presented.

  20. Kv7.1 surface expression is regulated by epithelial cell polarization

    DEFF Research Database (Denmark)

    Andersen, Martin N; Olesen, Søren-Peter; Rasmussen, Hanne Borger

    2011-01-01

    The potassium channel K(V)7.1 is expressed in the heart where it contributes to the repolarization of the cardiac action potential. In addition, K(V)7.1 is expressed in epithelial tissues where it plays a role in salt and water transport. Mutations in the kcnq1 gene can lead to long QT syndrome...... and deafness, and several mutations have been described as trafficking mutations. To learn more about the basic mechanisms that regulate K(V)7.1 surface expression, we have investigated the trafficking of K(V)7.1 during the polarization process of the epithelial cell line Madin-Darby Canine Kidney (MDCK) using...... is regulated by signaling mechanisms involved in epithelial cell polarization in particular signaling cascades involving protein kinase C and PI3K....

  1. Needs for Constructing and Possibilities of Nuclear Power Plants Interconnection to the Croatian Electricity Grid

    International Nuclear Information System (INIS)

    Zeljko, M.; Bajs, D.

    1998-01-01

    Due to development of electric power system and considering an increase of electrical energy consumption, needs for larger units in new power plants are obvious. Connection of large nuclear power plants to the grid, depending on their power and location, usually requires significant investments in transmission network development and construction. Considering the capacity of the 400 kV transmission network in Croatia, this problem is evident. This paper deals with the possibilities of nuclear power plants construction, as one possible option in electric power system development, and their interconnection to the electricity grid. (author)

  2. A 120kV IGBT modulator for driving a Pierce electron gun

    International Nuclear Information System (INIS)

    Earley, Lawrence M.; Brown, Richard W.; Carlson, Randolph L.; Ferguson, Patrick; Haynes, William B.; Kirbie, Hugh C.; Russell, Steven J.; Sigler, Floyd E.; Smirnova, Evgenya I.; Wheat, Robert M. Jr.

    2004-01-01

    An IGBT modulator has been developed to drive a 120 kV, 23 A Pierce electron gun. The modulator is capable of producing pulses up to 10 μs in width at repetition rates up to 10Hz with no active reset. The pulse rise time on the electron gun will be approximately 2 μs and the remaining 8 μs of flattop is tuned to have a ripple of less than 1 percent rms. The modulator technology was developed from a previous 50 kV prototype. The modulator consists of six boards, each with one EUPEC IGBT that drives a single common step-up transformer wound on METGLAS 2605SC cores. The six transformer cores share a common bi-filar output secondary winding. The modulator uses a fiber optic trigger system and has a high voltage cable output with an epoxy receptacle on the oil end and a ceramic receptacle on the vacuum end. The 120 kV electron gun was manufactured by MDS Co. and will be used to generate sheet electron beams from the standard pencil beam produced by the Pierce electron gun.

  3. Blockade of the voltage-gated potassium channel Kv1.3 inhibits immune responses in vivo.

    Science.gov (United States)

    Koo, G C; Blake, J T; Talento, A; Nguyen, M; Lin, S; Sirotina, A; Shah, K; Mulvany, K; Hora, D; Cunningham, P; Wunderler, D L; McManus, O B; Slaughter, R; Bugianesi, R; Felix, J; Garcia, M; Williamson, J; Kaczorowski, G; Sigal, N H; Springer, M S; Feeney, W

    1997-06-01

    The voltage activated K+ channel (Kv1.3) has recently been identified as the molecule that sets the resting membrane potential of peripheral human T lymphoid cells. In vitro studies indicate that blockage of Kv1.3 inhibits T cell activation, suggesting that Kv1.3 may be a target for immunosuppression. However, despite the in vitro evidence, there has been no in vivo demonstration that blockade of Kv1.3 will attenuate an immune response. The difficulty is due to species differences, as the channel does not set the membrane potential in rodent peripheral T cells. In this study, we show that the channel is present on peripheral T cells of miniswine. Using the peptidyl Kv1.3 inhibitor, margatoxin, we demonstrate that Kv1.3 also regulates the resting membrane potential, and that blockade of Kv1.3 inhibits, in vivo, both a delayed-type hypersensitivity reaction and an Ab response to an allogeneic challenge. In addition, prolonged Kv1.3 blockade causes reduced thymic cellularity and inhibits the thymic development of T cell subsets. These results provide in vivo evidence that Kv1.3 is a novel target for immunomodulation.

  4. Pulsed Power Generators For Two-section Lia Relativistic Magnetron Driver

    CERN Document Server

    Agafonov, A V; Pevchev, V P

    2004-01-01

    Two prototypes of pulsed power generators for a two-sectional LIA - specialized driver of a relativistic magnetron were constructed and tested. The driver for the double-sided powering of a relativistic magnetron consists of two identical sets of induction modules (two sections of LIA) with inner electrodes - vacuum adders connected to both sides of a coaxial magnetron. It provides the symmetric power flowing in a magnetron and a possibility of localising of the electron flow in magnetron interaction region. The first generator designed for a small-scale laboratory installation provides the output pulses of 100 ns in duration with voltage amplitude of 50 kV at repetition rate of 1 pps. The construction of the generator is based on the application of experimental capacitor banks designed as a pulse forming line with the next parameters: charging voltage - 80 kV, impedance - 1,7 Ohm, pulse duration - 80 ns at a matched load. The second generator was designed for 1 MV integrated LIA - magnetron system. It cons...

  5. PKC and AMPK regulation of Kv1.5 potassium channels

    DEFF Research Database (Denmark)

    Andersen, Martin Nybo; Skibsbye, Lasse; Tang, Chuyi

    2015-01-01

    The voltage-gated Kv1.5 potassium channel, conducting the ultra-rapid rectifier K(+) current (IKur), is regulated through several pathways. Here we investigate if Kv1.5 surface expression is controlled by the 2 kinases PKC and AMPK, using Xenopus oocytes, MDCK cells and atrial derived HL-1 cells....

  6. Wireless system for location of permanent faults by short circuit current monitoring in electric power distribution network; Sistema wireless para localizacao de faltas permanentes atraves da monitoracao da corrente de curto-circuito em redes de distribuicao de energia eletrica

    Energy Technology Data Exchange (ETDEWEB)

    Machado, A.G.; Correa, A.C.; Machado, R.N. das M.; Ferreira, A.M.D.; Pinto, J.A.C. [Instituto Federal de Educacao, Ciencia e Tecnologia do Para (IFPA), Belem, PA (Brazil)], E-mail: alcidesmachado000@yahoo.com.br; Barra Junior, W. [Universidade Federal do Para (UFPA), Belem, PA (Brazil). Inst. de Tecnologia. Faculdade de Engenharia Eletrica], E-mail: walbarra@ufpa.br

    2009-07-01

    This paper presents the development of an automatic system for permanent short-circuits location in medium voltage (13.8 kV) electric power system distribution feeders, by indirect monitoring of the line current. When a permanent failure occurs, the developed system uses mobile telephony (GSM) text messages (SMS) to inform the power company operation center where the failure most likely took place. With this information in real time, the power company operation center may provide the network restoration in a faster and efficient way. (author)

  7. Day-Ahead Congestion Management in Distribution Systems through Household Demand Response and Distribution Congestion Prices

    DEFF Research Database (Denmark)

    Liu, Weijia; Wu, Qiuwei; Wen, Fushuan

    2014-01-01

    into balancing power might challenge the operation of electric distribution systems and cause congestions. This paper presents a distribution congestion price (DCP) based market mechanism to alleviate possible distribution system congestions. By employing the loca- tional marginal pricing (LMP) model...... is proposed. Finally, a practical Danish 60kV/10.5kV distribution system is employed as the test case to verify the proposed method for mitigating congestion....

  8. Integration of wind power in Germany's transmission grid by using HVDC links

    Energy Technology Data Exchange (ETDEWEB)

    Wasserrab, Andreas; Fleckenstein, Marco; Balzer, Gerd [Technische Univ. Darmstadt (Germany). Inst. of Electrical Power and Energy

    2012-07-01

    This paper deals with the challenges for the integration of wind power in Germany's transmission grid. Several options for the expansion of transmission grids are discussed. The consideration focuses on HVDC technologies, which are used for further analyses. The basis of the analysis is the transmission grid of a German transmission system operator, which is implemented in a simulation tool. The model consists of the 110-kV-, 220-kV- and the 380-kV-system. In different scenarios the integration of wind power is analysed by applying HVDC links to connect the northern part of the grid with the load centres in the South. The results of load flow calculations are discussed focusing on transmission line loading and voltage stability. The paper concludes with future prospects of HVDC applications in Germany. (orig.)

  9. SU-E-I-23: A General KV Constrained Optimization of CNR for CT Abdominal Imaging

    International Nuclear Information System (INIS)

    Weir, V; Zhang, J

    2015-01-01

    Purpose: While Tube current modulation has been well accepted for CT dose reduction, kV adjusting in clinical settings is still at its early stage. This is mainly due to the limited kV options of most current CT scanners. kV adjusting can potentially reduce radiation dose and optimize image quality. This study is to optimize CT abdomen imaging acquisition based on the assumption of a continuous kV, with the goal to provide the best contrast to noise ratio (CNR). Methods: For a given dose (CTDIvol) level, the CNRs at different kV and pitches were measured with an ACR GAMMEX phantom. The phantom was scanned in a Siemens Sensation 64 scanner and a GE VCT 64 scanner. A constrained mathematical optimization was used to find the kV which led to the highest CNR for the anatomy and pitch setting. Parametric equations were obtained from polynomial fitting of plots of kVs vs CNRs. A suitable constraint region for optimization was chosen. Subsequent optimization yielded a peak CNR at a particular kV for different collimations and pitch setting. Results: The constrained mathematical optimization approach yields kV of 114.83 and 113.46, with CNRs of 1.27 and 1.11 at the pitch of 1.2 and 1.4, respectively, for the Siemens Sensation 64 scanner with the collimation of 32 x 0.625mm. An optimized kV of 134.25 and 1.51 CNR is obtained for a GE VCT 64 slice scanner with a collimation of 32 x 0.625mm and a pitch of 0.969. At 0.516 pitch and 32 x 0.625 mm an optimized kV of 133.75 and a CNR of 1.14 was found for the GE VCT 64 slice scanner. Conclusion: CNR in CT image acquisition can be further optimized with a continuous kV option instead of current discrete or fixed kV settings. A continuous kV option is a key for individualized CT protocols

  10. SU-E-I-23: A General KV Constrained Optimization of CNR for CT Abdominal Imaging

    Energy Technology Data Exchange (ETDEWEB)

    Weir, V; Zhang, J [University of Kentucky, Lexington, KY (United States)

    2015-06-15

    Purpose: While Tube current modulation has been well accepted for CT dose reduction, kV adjusting in clinical settings is still at its early stage. This is mainly due to the limited kV options of most current CT scanners. kV adjusting can potentially reduce radiation dose and optimize image quality. This study is to optimize CT abdomen imaging acquisition based on the assumption of a continuous kV, with the goal to provide the best contrast to noise ratio (CNR). Methods: For a given dose (CTDIvol) level, the CNRs at different kV and pitches were measured with an ACR GAMMEX phantom. The phantom was scanned in a Siemens Sensation 64 scanner and a GE VCT 64 scanner. A constrained mathematical optimization was used to find the kV which led to the highest CNR for the anatomy and pitch setting. Parametric equations were obtained from polynomial fitting of plots of kVs vs CNRs. A suitable constraint region for optimization was chosen. Subsequent optimization yielded a peak CNR at a particular kV for different collimations and pitch setting. Results: The constrained mathematical optimization approach yields kV of 114.83 and 113.46, with CNRs of 1.27 and 1.11 at the pitch of 1.2 and 1.4, respectively, for the Siemens Sensation 64 scanner with the collimation of 32 x 0.625mm. An optimized kV of 134.25 and 1.51 CNR is obtained for a GE VCT 64 slice scanner with a collimation of 32 x 0.625mm and a pitch of 0.969. At 0.516 pitch and 32 x 0.625 mm an optimized kV of 133.75 and a CNR of 1.14 was found for the GE VCT 64 slice scanner. Conclusion: CNR in CT image acquisition can be further optimized with a continuous kV option instead of current discrete or fixed kV settings. A continuous kV option is a key for individualized CT protocols.

  11. Design of full digital 50 kV electronic gun high voltage power supply

    International Nuclear Information System (INIS)

    Ge Lei; Shang Lei

    2014-01-01

    The design of full digital electronic gun high voltage power supply based on DSP was introduced in this paper. This power supply has innovations of full digital feedback circuit and PID closed-loop control mode. The application of high frequency resonant converter circuit reduces the size of the resonant element and transformer. The current-coupling distributed high voltage transformer and rectifier circuit were employed in this power supply. By this way, the power supply efficiency is improved and the number of distributed parameters is reduced, and the rectifier circuit could work under the oil-free environment. This power supply has been used in electronic grid-control high voltage system of the irradiation accelerator. (authors)

  12. Development of Highly Selective Kv1.3-Blocking Peptides Based on the Sea Anemone Peptide ShK

    Directory of Open Access Journals (Sweden)

    Michael W. Pennington

    2015-01-01

    Full Text Available ShK, from the sea anemone Stichodactyla helianthus, is a 35-residue disulfide-rich peptide that blocks the voltage-gated potassium channel Kv1.3 at ca. 10 pM and the related channel Kv1.1 at ca. 16 pM. We developed an analog of this peptide, ShK-186, which is currently in Phase 1b-2a clinical trials for the treatment of autoimmune diseases such as multiple sclerosis and rheumatoid arthritis. While ShK-186 displays a >100-fold improvement in selectivity for Kv1.3 over Kv1.1 compared with ShK, there is considerable interest in developing peptides with an even greater selectivity ratio. In this report, we describe several variants of ShK that incorporate p-phophono-phenylalanine at the N-terminus coupled with internal substitutions at Gln16 and Met21. In addition, we also explored the combinatorial effects of these internal substitutions with an alanine extension at the C-terminus. Their selectivity was determined by patch-clamp electrophysiology on Kv1.3 and Kv1.1 channels stably expressed in mouse fibroblasts. The peptides with an alanine extension blocked Kv1.3 at low pM concentrations and exhibited up to 2250-fold selectivity for Kv1.3 over Kv1.1. Analogs that incorporates p-phosphono-phenylalanine at the N-terminus blocked Kv1.3 with IC50s in the low pM range and did not affect Kv1.1 at concentrations up to 100 nM, displaying a selectivity enhancement of >10,000-fold for Kv1.3 over Kv1.1. Other potentially important Kv channels such as Kv1.4 and Kv1.6 were only partially blocked at 100 nM concentrations of each of the ShK analogs.

  13. Initial operation of a high-power quasi-optical gyrotron

    International Nuclear Information System (INIS)

    Fliflet, A.W.; Hargreaves, T.A.; Manheimer, W.M.; Fischer, R.P.; Barsanti, M.L.

    1990-01-01

    Results from the initial operating of a high-power quasi-optical gyrotron based on the 90-kV 50-A Varian VUW-8144 electron gun are reported. The output power and efficiency have been measured for a resonator mirror separation of 19.4 cm with a magnetic field of 4.95 T, corresponding to resonator output coupling of 1.9%, and for a resonator mirror separation of 21.4 cm with a magnetic field of 4.7 T, corresponding to a resonator output coupling of 3.1%. Operation was multimoded with 3--6 modes excited in the range of 125--130 GHz for the 4.95-T magnetic field. A peak efficiency of 15% at an output power of 161 kW was obtained for a gun voltage of 93 kV and a current of 12 A. A peak-output power of 364 kW at an efficiency of 10% was obtained at a voltage of 95.6 kV and 37.5 A

  14. Development of microcontroller based remote control system for HV power supply of ECR ion source for ADSS project

    International Nuclear Information System (INIS)

    Srivastava, S.; Misra, A.; Thakur, S.K.; Pandey, H.K.; Pandit, V.S.

    2009-01-01

    In this paper we will describe the design and development of the microcontroller based interface card used to control and monitor the operation of High Voltage Power supply 120kV/50mA (HVPS). This power supply is deployed for the extraction of proton beam from the microwave ion source in the ADSS project. (author)

  15. A comparison of kV and MV imaging in head and neck image guided radiotherapy

    Energy Technology Data Exchange (ETDEWEB)

    Devereux, B. [Radiation Oncology Queensland, 280 North St, Toowoomba 4350 (Australia)], E-mail: beth.devereux@roq.net.au; Frantzis, J.; Sisson, T.; Jones, M.; Martin, J.; Middleton, M. [Radiation Oncology Queensland, 280 North St, Toowoomba 4350 (Australia)

    2010-02-15

    Purpose: To compare and assess kV and MV imaging modalities and their role in image guided radiotherapy (IGRT) for head and neck cancer patients. Method: Twelve patients receiving radical radiotherapy to the head and neck were analysed in this study. Six patients undertook MV daily online intervention and a further six patients undertook kV daily online intervention. Pre-intervention field placement data were collected from three separate observers' image match analysis for each patient. The radiotherapy collective involved in the daily online image match analysis formed the fourth observer in the study. The primary end point was to establish the difference in inter- and intra-observer variance between kV and MV imaging modalities. Results: The range of the standard deviations of systematic set-up error for MV imaging calculated was 1.47-2.33 mm (MV) and 1.61-1.64 mm (kV) for the right-left (RL), 2.10-2.17 mm (MV) and 1.53-1.84 mm (kV) for the cranio-caudal (CC) and 1.43-1.63 mm (MV) and 1.02-1.11 mm (kV) for the anterior-posterior (AP). The mean inter-observer variance was 0.21 mm (MV) and 0.41 mm (kV) for the RL, 0.53 mm (MV) and 0.55 mm (kV) for the CC and 0.23 mm (MV) and 0.16 mm (kV) for the AP direction. Intra-observer mean variance was in the order of 0.60 mm (MV) and 0.16 mm (kV) for the RL, 1.41 mm (MV) and 0.05 mm (kV) for the CC and 1.41 mm (MV) and 0.08 mm (kV) for the AP. Discussion: The data in this study suggest both inter- and intra-observer consistency across kV and MV imaging modalities were comparable. However, it is felt that the improved clarity and quality of kV imaging allows all observers to analyse images in a consistent manner, identifying and acting on potential field placement moves. Conclusion: The introduction of kV imaging has maintained the high levels of inter- and intra-observer consistency achieved with MV imaging. This in turn further enables positive verification outcomes and supports the implementation of potential

  16. System Protection Schemes in Eastern Denmark

    DEFF Research Database (Denmark)

    Rasmussen, Joana

    outages in the southern part of the 132-kV system introduce further stress in the power system, eventually leading to a voltage collapse. The local System Protection Scheme against voltage collapse is designed as a response-based scheme, which is dependent on local indication of reactive and active power...... effective measures, because they are associated with large reactive power losses in the transmission system. Ordered reduction of wind generation is considered an effective measure to maintain voltage stability in the system. Reactive power in the system is released due to tripping of a significant amount...... system. In that way, the power system capability could be extended beyond normal limits....

  17. Development of modular scalable pulsed power systems for high power magnetized plasma experiments

    Science.gov (United States)

    Bean, I. A.; Weber, T. E.; Adams, C. S.; Henderson, B. R.; Klim, A. J.

    2017-10-01

    New pulsed power switches and trigger drivers are being developed in order to explore higher energy regimes in the Magnetic Shock Experiment (MSX) at Los Alamos National Laboratory. To achieve the required plasma velocities, high-power (approx. 100 kV, 100s of kA), high charge transfer (approx. 1 C), low-jitter (few ns) gas switches are needed. A study has been conducted on the effects of various electrode geometries and materials, dielectric media, and triggering strategies; resulting in the design of a low-inductance annular field-distortion switch, optimized for use with dry air at 90 psig, and triggered by a low-jitter, rapid rise-time solid-state Linear Transformer Driver. The switch geometry and electrical characteristics are designed to be compatible with Syllac style capacitors, and are intended to be deployed in modular configurations. The scalable nature of this approach will enable the rapid design and implementation of a wide variety of high-power magnetized plasma experiments. This work is supported by the U.S. Department of Energy, National Nuclear Security Administration. Approved for unlimited release, LA-UR-17-2578.

  18. Method of selecting optimum cross arm lengths for a 750 kV transmission line

    Energy Technology Data Exchange (ETDEWEB)

    Aleksandrov, G N; Olorokov, V P

    1965-01-01

    A method is presented, based on both technical and economic considerations, for selecting cross arm lengths for intermediate poles of power transmission lines according to the effects of internal overvoltage, methods from probability theory and mathematical statistics employed. The problem of optimum pole size is considered in terms of the effect of internal overvoltages for a prescribed maximum level of 2.1 PU currently used in the USSR for the design of 750 kV lines.

  19. Fundamental role for the KCNE4 ancillary subunit in Kv7.4 regulation of arterial tone

    DEFF Research Database (Denmark)

    Jepps, Thomas A; Carr, Georgina; Lundegaard, Pia R

    2015-01-01

    tone by Kv7 channels. In HEK cells expressing Kv7.4, co-expression of KCNE4 increased the membrane expression of Kv7.4 and significantly altered Kv7.4 current properties. Quantitative PCR analysis of different rat arteries found that the KCNE4 isoform predominated and proximity ligation experiments...... leads to reduced Kv7.4 membrane abundance, a depolarized membrane potential and an augmented response to vasoconstrictors. KCNE4 is a key regulator of the function and expression of Kv7.4 in vascular smooth muscle. ABSTRACT: The KCNE ancillary subunits (KCNE1-5) significantly alter the expression...... to reduced Kv7.4 membrane abundance, a depolarized membrane potential and an augmented response to vasoconstrictors. The present study is the first to demonstrate an integral role of KCNE4 in regulating the function and expression of Kv7.4 in vascular smooth muscle....

  20. TECHNICAL AND ECONOMIC EVALUATION OF OPTIMAL VOLTAGE LEVEL FOR THE POWER SUPPLY OF DEEP MINE OPERATING HORIZONS

    OpenAIRE

    Shkrabets, F. P.; Ostapchuk, O. V.; Kozhevnikov, A. V.; Akulov, A. V.

    2015-01-01

    The most perspective option for possible deep mine power supply is the one with the deep input of 35 kV voltage by installing of underground 35kV/6 kV substation. This option is caused by the expected level of electrical loads, provided by mine development, the power consumers’ deep layout (considering the distance from the source to the shaft on the surface and from the shaft to the underground substation chamber) and primary and the most responsible power consumers (blind shaft lifting devi...

  1. Downregulation of Kv7.4 channel activity in primary and secondary hypertension

    DEFF Research Database (Denmark)

    Jepps, Thomas Andrew; Chadha, Preet S; Davis, Alison J

    2011-01-01

    Voltage-gated potassium (K(+)) channels encoded by KCNQ genes (Kv7 channels) have been identified in various rodent and human blood vessels as key regulators of vascular tone; however, nothing is known about the functional impact of these channels in vascular disease. We ascertained the effect of...... structurally different activators of Kv7.2 through Kv7.5 channels (BMS-204352, S-1, and retigabine) on blood vessels from normotensive and hypertensive animals.......Voltage-gated potassium (K(+)) channels encoded by KCNQ genes (Kv7 channels) have been identified in various rodent and human blood vessels as key regulators of vascular tone; however, nothing is known about the functional impact of these channels in vascular disease. We ascertained the effect of 3...

  2. Three-Phase Short-Circuit Current Calculation of Power Systems with High Penetration of VSC-Based Renewable Energy

    Directory of Open Access Journals (Sweden)

    Niancheng Zhou

    2018-03-01

    Full Text Available Short-circuit current level of power grid will be increased with high penetration of VSC-based renewable energy, and a strong coupling between transient fault process and control strategy will change the fault features. The full current expression of VSC-based renewable energy was obtained according to transient characteristics of short-circuit current. Furtherly, by analyzing the closed-loop transfer function model of controller and current source characteristics presented in steady state during a fault, equivalent circuits of VSC-based renewable energy of fault transient state and steady state were proposed, respectively. Then the correctness of the theory was verified by experimental tests. In addition, for power grid with VSC-based renewable energy, superposition theorem was used to calculate AC component and DC component of short-circuit current, respectively, then the peak value of short-circuit current was evaluated effectively. The calculated results could be used for grid planning and design, short-circuit current management as well as adjustment of relay protection. Based on comparing calculation and simulation results of 6-node 500 kV Huainan power grid and 35-node 220 kV Huaisu power grid, the effectiveness of the proposed method was verified.

  3. Immunomodulatory effects of diclofenac in leukocytes through the targeting of Kv1.3 voltage-dependent potassium channels.

    Science.gov (United States)

    Villalonga, Núria; David, Miren; Bielańska, Joanna; González, Teresa; Parra, David; Soler, Concepció; Comes, Núria; Valenzuela, Carmen; Felipe, Antonio

    2010-09-15

    Kv1.3 plays a crucial role in the activation and proliferation of T-lymphocytes and macrophages. While Kv1.3 is responsible for the voltage-dependent potassium current in T-cells, in macrophages this K(+) current is generated by the association of Kv1.3 and Kv1.5. Patients with autoimmune diseases show a high number of effector memory T cells that are characterized by a high expression of Kv1.3 and Kv1.3 antagonists ameliorate autoimmune disorders in vivo. Diclofenac is a non-steroidal anti-inflammatory drug (NSAID) used in patients who suffer from painful autoimmune diseases such as rheumatoid arthritis. In this study, we show that diclofenac impairs immune response via a mechanism that involves Kv1.3. While diclofenac inhibited Kv1.3 expression in activated macrophages and T-lymphocytes, Kv1.5 remained unaffected. Diclofenac also decreased iNOS levels in Raw 264.7 cells, impairing their activation in response to lipopolysaccharide (LPS). LPS-induced macrophage migration and IL-2 production in stimulated Jurkat T-cells were also blocked by pharmacological doses of diclofenac. These effects were mimicked by Margatoxin, a specific Kv1.3 inhibitor, and Charybdotoxin, which blocks both Kv1.3 and Ca(2+)-activated K(+) channels (K(Ca)3.1). Because Kv1.3 is a very good target for autoimmune therapies, the effects of diclofenac on Kv1.3 are of high pharmacological relevance. Copyright 2010 Elsevier Inc. All rights reserved.

  4. Silencing of Kv4.1 potassium channels inhibits cell proliferation of tumorigenic human mammary epithelial cells

    International Nuclear Information System (INIS)

    Jang, Soo Hwa; Choi, Changsun; Hong, Seong-Geun; Yarishkin, Oleg V.; Bae, Young Min; Kim, Jae Gon; O'Grady, Scott M.; Yoon, Kyong-Ah; Kang, Kyung-Sun; Ryu, Pan Dong; Lee, So Yeong

    2009-01-01

    Potassium channel activity has been shown to facilitate cell proliferation in cancer cells. In the present study, the role of Kv4.1 channels in immortal and tumorigenic human mammary epithelial cells was investigated. Kv4.1 protein expression was positively correlated with tumorigenicity. Moreover, transfection with siRNAs targeting Kv4.1 mRNA suppressed proliferation of tumorigenic mammary epithelial cells. Experiments using mRNA isolated from human breast cancer tissues revealed that the level of Kv4.1 mRNA expression varied depending on the stage of the tumor. Kv4.1 protein expression increased during stages T2 and T3 compared to normal tissue. These results demonstrated that Kv4.1 plays a role in proliferation of tumorigenic human mammary epithelial cells. In addition, elevated Kv4.1 expression may be useful as a diagnostic marker for staging mammary tumors and selective blockers of Kv4.1 may serve to suppress tumor cell proliferation.

  5. Use of TCSR with Split Windings for Shortening the Spar Cycle Time in 500 kV Lines

    Energy Technology Data Exchange (ETDEWEB)

    Matinyan, A. M., E-mail: al-drm@mail.ru; Peshkov, M. V.; Karpov, V. N.; Alekseev, N. A. [JSC “R& D Center at Federal Grid Company of Unified Power System,” (Russian Federation)

    2017-01-15

    The arc-fault recharge phenomenon in single-phase automatic reclosure (SPAR) of a line is examined. Abrief description is given of the design of a 500 kV thyristor controlled shunt reactor (TCSR) with split valve-side windings. This type of TCSR is shown to effectively quench a single-phase arc fault in a power transmission line and shortens the SPAR cycle time.

  6. A truncated Kv1.1 protein in the brain of the megencephaly mouse: expression and interaction

    Directory of Open Access Journals (Sweden)

    Århem Peter

    2005-11-01

    Full Text Available Abstract Background The megencephaly mouse, mceph/mceph, is epileptic and displays a dramatically increased brain volume and neuronal count. The responsible mutation was recently revealed to be an eleven base pair deletion, leading to a frame shift, in the gene encoding the potassium channel Kv1.1. The predicted MCEPH protein is truncated at amino acid 230 out of 495. Truncated proteins are usually not expressed since nonsense mRNAs are most often degraded. However, high Kv1.1 mRNA levels in mceph/mceph brain indicated that it escaped this control mechanism. Therefore, we hypothesized that the truncated Kv1.1 would be expressed and dysregulate other Kv1 subunits in the mceph/mceph mice. Results We found that the MCEPH protein is expressed in the brain of mceph/mceph mice. MCEPH was found to lack mature (Golgi glycosylation, but to be core glycosylated and trapped in the endoplasmic reticulum (ER. Interactions between MCEPH and other Kv1 subunits were studied in cell culture, Xenopus oocytes and the brain. MCEPH can form tetramers with Kv1.1 in cell culture and has a dominant negative effect on Kv1.2 and Kv1.3 currents in oocytes. However, it does not retain Kv1.2 in the ER of neurons. Conclusion The megencephaly mice express a truncated Kv1.1 in the brain, and constitute a unique tool to study Kv1.1 trafficking relevant for understanding epilepsy, ataxia and pathologic brain overgrowth.

  7. Voltage profile program for the Kennedy Space Center electric power distribution system

    Science.gov (United States)

    1976-01-01

    The Kennedy Space Center voltage profile program computes voltages at all busses greater than 1 Kv in the network under various conditions of load. The computation is based upon power flow principles and utilizes a Newton-Raphson iterative load flow algorithm. Power flow conditions throughout the network are also provided. The computer program is designed for both steady state and transient operation. In the steady state mode, automatic tap changing of primary distribution transformers is incorporated. Under transient conditions, such as motor starts etc., it is assumed that tap changing is not accomplished so that transformer secondary voltage is allowed to sag.

  8. Novel Kv7.1-phosphatidylinositol 4,5-bisphosphate interaction sites uncovered by charge neutralization scanning

    DEFF Research Database (Denmark)

    Eckey, Karina; Wrobel, Eva; Strutz-Seebohm, Nathalie

    2014-01-01

    Kv7.1 to Kv7.5 α-subunits belong to the family of voltage-gated potassium channels (Kv). Assembled with the β-subunit KCNE1, Kv7.1 conducts the slowly activating potassium current IKs, which is one of the major currents underlying repolarization of the cardiac action potential. A known regulator...... of corresponding long QT syndrome mutants suggested impaired PIP2 regulation as the cause for channel dysfunction. To clarify the underlying structural mechanism of PIP2 binding, molecular dynamics simulations of Kv7.1/KCNE1 complexes containing two PIP2 molecules in each subunit at specific sites were performed...

  9. From pan-reactive KV7 channel opener to subtype selective opener/inhibitor by addition of a methyl group.

    Directory of Open Access Journals (Sweden)

    Sigrid Marie Blom

    Full Text Available The voltage-gated potassium channels of the KV7 family (KV7.1-5 play important roles in controlling neuronal excitability and are therefore attractive targets for treatment of CNS disorders linked to hyperexcitability. One of the main challenges in developing KV7 channel active drugs has been to identify compounds capable of discriminating between the neuronally expressed subtypes (KV7.2-5, aiding the identification of the subunit composition of KV7 currents in various tissues, and possessing better therapeutic potential for particular indications. By taking advantage of the structure-activity relationship of acrylamide KV7 channel openers and the effects of these compounds on mutant KV7 channels, we have designed and synthesized a novel KV7 channel modulator with a unique profile. The compound, named SMB-1, is an inhibitor of KV7.2 and an activator of KV7.4. SMB-1 inhibits KV7.2 by reducing the current amplitude and increasing the time constant for the slow component of the activation kinetics. The activation of KV7.4 is seen as an increase in the current amplitude and a slowing of the deactivation kinetics. Experiments studying mutant channels with a compromised binding site for the KV7.2-5 opener retigabine indicate that SMB-1 binds within the same pocket as retigabine for both inhibition of KV7.2 and activation of KV7.4. SMB-1 may serve as a valuable tool for KV7 channel research and may be used as a template for further design of better subtype selective KV7 channel modulators. A compound with this profile could hold novel therapeutic potential such as the treatment of both positive and cognitive symptoms in schizophrenia.

  10. Proposal for the Award of a Contract for the Supply of 18kV Power Transformers Rated 464 kVA to 2 MVA

    CERN Document Server

    2002-01-01

    This document concerns the award of a contract for the supply of thirty-five 18 kV cast-resin rectifier power transformers rated 464 kVA to 2 MVA and 26 protective enclosures. Following a market survey (MS-2920/SL/LHC) carried out among 56 firms in sixteen Member States, a call for tenders (IT-3007/SL/LHC) was sent on 12 August 2002 to eight firms in five Member States. By the closing date, CERN had received three tenders from three firms in three Member States. The Finance Committee is invited to agree to the negotiation of a contract with TRASFOR (CH), the lowest bidder, for the supply of 35 power transformers rated 464 kVA to 2 MVA and 26 protective enclosures for a total amount of 1 398 500 Swiss francs, not subject to revision, with an option for three additional transformers and protective enclosures, for an additional amount of 107 650 Swiss francs, subject to revision for inflation from 1 January 2005, bringing the total amount to 1 506 150 Swiss francs subject to revision for inflation from 1 January...

  11. Protection and measurement systems for 500 keV DC industrial accelerator

    International Nuclear Information System (INIS)

    Rajan, R.N.; Saroj, P.C.; Nanu, K.; Sharma, D.K.; Bakhtsingh, R.I.; Pandey, M.K.; Aggarwal, Ritu; Nagesh, K.V.; Sethi, R.C.

    2003-01-01

    A 500 keV, 20 ma electron beam accelerator has been developed and commissioned for industrial processing application at BRIT, Vashi. The 500 kV supply system consists of a 10 kV/2a DC power supply, 15 kW/10 kHz oscillator, 60 kV/10 kHz step-up transformer, and a 10 stage balanced Cockcroft-Walton multiplier. Since this is a high voltage system, and is prone to generate high electrical surges in the event of fault, adequate protection measures have to be incorporated to prevent catastrophic failure to the components of the supply system and also for measurement and control devices. Two level safety protection schemes have been incorporated in this system. This paper describes about various safety measures incorporated in the system and a few system specific measurement schemes

  12. A new slip stacking RF system for a twofold power upgrade of Fermilab's Accelerator Complex

    Energy Technology Data Exchange (ETDEWEB)

    Madrak, Robyn [Fermi National Accelerator Lab. (FNAL), Batavia, IL (United States)

    2014-05-15

    Fermilab's Accelerator Complex has been recently upgraded, in order to increase the 120 GeV proton beam power on target from about 400 kW to over 700 kW for NOvA and other future intensity frontier experiments. One of the key ingredients of the upgrade is the offloading of some Main Injector synchrotron operations - beam injection and RF manipulation called ''slip stacking'' - to the 8GeV Recycler Ring, which had until recently been used only for low-intensity antiproton storage and cooling. This required construction of two new 53 MHz RF systems for the slip-stacking manipulations. The cavities operate simultaneously at Vpeak ≲150 kV, but at slightly different frequencies (Δf=1260 Hz). Their installation was completed in September 2013. This article describes the novel solutions used in the design of the new cavities, their tuning system, and the associated high power RF system. First results showing effective operation of the RF system, beam capture and successful slip-stacking in the Recycler Ring are presented.

  13. Design and development of power supplies at VECC for accelerators

    International Nuclear Information System (INIS)

    Thakur, S.K.

    2013-01-01

    Several power supplies have been designed and developed in-house incorporating various topologies to match the load requirements. Most of the power supplies have been being utilised in K-130 and K-500 cyclotrons operation successfully from last several years. Amongst other types, Switching Mode PS (SMPS), Phase Controlled Rectifier (PCR), Linear mode power supply are mostly in use, irrespective of their own merits and demerits. Switching mode power supply (SMPS) is most common topology for various applications ranging from high current to high voltage applications. Due to low stored energy and faster response, the SMPS incorporating Pulse Switch Modulation (PSM) configuration is most suitable for high voltage DC power supply at larger power compared to its counterparts, makes possible to operate the power system without crowbar. For an IOT cathode power supply, a 200kW at - 40kV High voltage power supply is under development incorporating SMPS and PSM technique. Earlier, High Voltage power supply was made by using Tetrode Tube in linear mode for RF amplifier for K-130 Cyclotron. Later, in K-500 Cyclotron, a High Voltage power supply was developed incorporating PCR topology rated at 20kV, 20 Amp for Anodes for 3 nos. of RF amplifiers. These HV power supply is equipped with ultra-fast acting Crowbar Protection System developed in VECC which is for the protection of costly RF Tubes against the internal arc. Design and development of SMPS based Bipolar Power Supply with 4-Quadrant operation rated at ± 27 V, ± 300 Amp with current stability around 100 ppm for Super-conducting Magnets along with quench protection and energy dumping scheme. (author)

  14. Superconducting toroidal field coil power supply and protection system for NET

    International Nuclear Information System (INIS)

    Hicks, J.B.

    1986-01-01

    A power supply and quench protection system is proposed in which alternate coils are connected in series to produce two separate circuits, each with 8 coils. Both circuits are provided with power supplies comprising rectifier transformers and thyristor equipped Graetz bridges, which are operated at maximum forward voltage (125 V) to charge the coils to 24 kA, 17.75 GJ in ≅ 2 hours and are fully inverted for scheduled discharges. Pulsed firing of the thyristors allows the same power supplies to be used to maintain the currents against resistive losses, without increasing the reactive power consumption or harmonic current generation. Rapid discharges are initiated by opening d.c. circuit breakers to introduce discharge resistors between the coils of each circuit. The maximum possible value of peak voltage-to-ground is then limited to 2.25 times the discharge voltage applied to each coil. A 5 kV discharge voltage allows the coils to be discharged with a time constant of 18.5 s, which is sufficiently rapid to limit the quench ''hot spot'' temperature to 68 K. The coil connections impose sufficient symmetry on the coil current distribution to ensure that no out-of-plane forces are produced on the coils. Even if one circuit breaker fails to interrupt, the variation of coil currents is sufficiently small that the resulting symmetric variation of radial centring forces is acceptable

  15. DESIGN AND CONSTRUCTION OF A 12 kV DC POWER SUPPLY 175

    African Journals Online (AJOL)

    DR. AMINU

    voltage multiplying rectifier. It is suitable as a power supply for the nitrogen laser. .... (Hilborn, 1976), Raman spectroscopy (Kunabenchi, et al. 1982), and laser isotope ... laser consists of a channel that contains nitrogen gas, a switching system.

  16. T Cell Subset and Stimulation Strength-Dependent Modulation of T Cell Activation by Kv1.3 Blockers.

    Directory of Open Access Journals (Sweden)

    Wai-Ping Fung-Leung

    Full Text Available Kv1.3 is a voltage-gated potassium channel expressed on T cells that plays an important role in T cell activation. Previous studies have shown that blocking Kv1.3 channels in human T cells during activation results in reduced calcium entry, cytokine production, and proliferation. The aim of the present study was to further explore the effects of Kv1.3 blockers on the response of different human T cell subsets under various stimulation conditions. Our studies show that, unlike the immune suppressor cyclosporine A, the inhibitory effect of Kv1.3 blockers was partial and stimulation strength dependent, with reduced inhibitory efficacy on T cells under strengthened anti-CD3/CD28 stimulations. T cell responses to allergens including house dust mites and ragweed were partially reduced by Kv1.3 blockers. The effect of Kv1.3 inhibition was dependent on T cell subsets, with stronger effects on CCR7- effector memory compared to CCR7+ central memory CD4 T cells. Calcium entry studies also revealed a population of CD4 T cells resistant to Kv1.3 blockade. Activation of CD4 T cells was accompanied with an increase in Kv1.3 currents but Kv1.3 transcripts were found to be reduced, suggesting a posttranscriptional mechanism in the regulation of Kv1.3 activities. In summary, Kv1.3 blockers inhibit T cell activation in a manner that is highly dependent on the T cell identity and stimulation strength, These findings suggest that Kv1.3 blockers inhibit T cells in a unique, conditional manner, further refining our understanding of the therapeutic potential of Kv1.3 blockers.

  17. Ground-fault protection of insulated high-voltage power networks in mines

    Energy Technology Data Exchange (ETDEWEB)

    Pudelko, H

    1976-09-01

    Safety of power networks is discussed in underground black coal mines in Poland. Safety in mines with a long service life was compared with safety in mines constructed since 1950. Power networks and systems protecting against electric ground-faults in the 2 mine groups are comparatively evaluated. Systems for protection against electric ground-faults in mine high-voltage networks with an insulated star point of the transformer are characterized. Fluctuations of resistance of electrical insulation under conditions of changing load are analyzed. The results of analyses are given in 14 diagrams. Recommendations for design of systems protecting against electric ground-faults in 6 kV mine power systems are made. 7 references.

  18. ANALYSIS OF ENERGY EFFICIENCY OF OPERATING MODES OF ELECTRICAL SYSTEMS WITH THE TRACTION LOADS

    Directory of Open Access Journals (Sweden)

    V. E. Bondarenko

    2017-03-01

    Full Text Available Innovative scenarios of reliable energy supply of transportation process aimed at reducing the specific energy consumption and increase energy efficiency of the systems of electric traction. The paper suggests innovative energy saving directions in traction networks of railways and new circuit solutions accessing traction substations in energy systems networks, ensure energy security of the transportation process. To ensure the energy security of rail transport special schemes were developed to propose the concept of external power traction substations, which would increase the number of connections to the networks of 220 – 330 kV, as well as the creation of transport and energy corridors, development of its own supply of electric networks of 110 kV substations and mobile RP-110 kV of next generation. Therefore, the investment program of the structures owned by the Ukrainian Railways (Ukrzaliznytsia need to be synchronized in their technological characteristics, as well as the criteria of reliability and quality of power supply with the same external energy investment programs. It is found that without any load on left or right supplying arm one of two less loaded phases of traction transformer begins generating specific modes in the supplying three-phase line. Thus, modes of mobile substation cause leakage in one of the phases of the supply line of traction transformers of active-capacitive current, and as a result generating energy in the main power line of 154 kV, which is fixed and calculated by electricity meters. For these three phase mode supply network is necessary to use 1st algorithm, i.e. taking into account the amount of electricity as the energy in all phases. For effective application of reactive power compensation devices in the AC traction power supply systems it is proposed to develop regulatory documentation on necessity of application and the order of choice of parameters and placement of compensation systems taking into

  19. SU-G-JeP4-13: Continuous Intra-Fractional Monitoring of the Prostate Using Dynamic KV Collimation and Tube Current Modulation

    Energy Technology Data Exchange (ETDEWEB)

    Parsons, D [Dalhousie Unviersity, Halifax, Nova Scotia (Canada); Robar, J [Dalhousie Unviersity, Halifax, Nova Scotia (Canada); Nova Scotia Health Authority, Halifax, NS (Canada)

    2016-06-15

    Purpose: The focus of this work is to improve the available kV image quality for continuous intra-fraction monitoring of the prostate. This is investigated using a novel blade collimation system enabling modulated volume-of-interest (VOI) imaging of prostate fiducial markers. Methods: A four-blade dynamic kV collimator was used to track a VOI during gantry rotation. Planar image quality was investigated as a function of collimator dimension, while maintaining the same dose to isocenter, for a 22.2 cm diameter cylindrical water phantom with a 9 mm diameter bone insert. A sample prostate anatomy was defined in the planning system, including three fiducial markers within the CTV. The VOI margin around each marker was set to be 2σ of the population covariance matrix characterizing prostate motion. DRRs were used to calculate the kV attenuation for each VOI as a function of angle. The optimal marker and tube current were determined using kV attenuation. Monte Carlo simulations were used to calculate the imaging dose to the phantom and MV scatter dose to the imaging panel. Results: Preliminary measurements show an increase in CNR by a factor of 1.3 with the VOI method, when decreasing from an 6×6 to 2×2 cm{sup 2} field. Attenuation calculations show a change in kV fluence at the detector by a factor of 21.6 with fiducial optimization; resultant tube current modulation increases maximum dose by a factor of 1.4 compared to no modulation. MV scatter contribution to the kV detector changes by approximately a factor of two over a complete gantry rotation. Conclusion: The dynamic collimation system allows single fiducial marker tracking at a very low dose, with reduction of scatter and improvement of image quality, compared to imaging the entire prostate. The approach is compatible with tube current modulation, which enables consistent image quality throughout the range of gantry rotation. This project was funded by Varian Medical Systems.

  20. Nuclear power in long term energy strategies in Macedonia

    International Nuclear Information System (INIS)

    Volkanovski, A.

    2001-01-01

    The Macedonian Power System (MPS) used to be a part of the former Yugoslav Power System, and it was connected to the European system by 400 kV transmission lines. at the present time, the MPS works isolated from the UCPTE, only connected to the Yugoslav and Greek power systems. The connections with the Bulgarian and Albanian power systems are on a lower voltage level. The reliability and stability of the MPS needs to be improved. Macedonia is located in the central area of the Balkan, where the transmission lines from other Balkan countries are crossing. In the near future, the Macedonian Power System needs to be linked to the European system. To prepare for the energy demand at the beginning of the 21-st century, when the local coal reserves get exhausted, Macedonia needs to start with activities for substitution of the existing coal-fired thermal power plants with nuclear plants. This paper discusses the activities for global development solutions in the area of power generation. (author)

  1. Some problems relating to the transmission of electrical power at very high voltage

    Energy Technology Data Exchange (ETDEWEB)

    Goldstein, A

    1965-01-01

    Some of the technical and economic factors which influence the choice of a transmission system, particularly a very high voltage one, are discussed. The stability of transmission overvoltages at mains frequency and their control by means of compensating reactances is described. Overvoltages due to circuit-breaker operation and those of atmospheric origin, and appropriate protective devices, the behaviour of equipment at 750 kV, and problems of testing are included. Finally, the 735 kV network now being installed to carry 5300 MW of hydroelectric power 650 km from the Manicouagan River to Quebec and Montreal is described.

  2. Fiscal 1998 research report on the total electric power loss reduction project for Myanmer; 1998 nendo Myanmer koku denryoku soshitsu sogo teigen project chosa hokokusho

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1999-03-01

    As a part of Japanese clean development mechanism, study was made on reduction of greenhouse effect gas emission from thermal power plants by reduction of power transmission and distribution losses of power systems in Myanmer. Study was made on technical power transmission and distribution losses for the national grid transmission system, 33kV sub- transmission system of Thaketa substation in Yangong city, and 6.6kV and 400V distribution systems of Latha and Lanmadaw townships in the downtown area of Yangong. Countermeasures for power loss reduction were considered on the basis of the study result. The loss reduction project plan includes a construction cost of 5,134,000US$, loss reduction of 7,726kW, and loss reduction of 33,213,000kWh. The project feasibility and profitability were evaluated by comparison between a financial internal rate of return (FIRR) and an opportunity cost assuming that a discount rate is the opportunity cost. As a result, FIRR was 17.36% and the discount rate was 8.89% in Myanmer. (NEDO)

  3. KCNE4 is an inhibitory subunit to Kv1.1 and Kv1.3 potassium channels

    DEFF Research Database (Denmark)

    Grunnet, Morten; Rasmussen, Hannne B; Hay-Schmidt, Anders

    2003-01-01

    is detected in the heart and in five different parts of the brain. Having the broad distribution of Kv1 channels in mind, the demonstrated inhibitory property of KCNE4-subunits could locally and/or transiently have a dramatic influence on cellular excitability and on setting resting membrane potentials....

  4. HTS Transmission Cable System for installation in the Long Island Power Grid

    Energy Technology Data Exchange (ETDEWEB)

    Schmidt, Frank [American Superconductor Corporation, Devens, MA (United States); Durand, Fabien [American Superconductor Corporation, Devens, MA (United States); Maguire, James [American Superconductor Corporation, Devens, MA (United States)

    2015-10-05

    Department of Energy (DOE) Award DE-FC26-07NT43240 was issued on October 1, 2007. Referred to as LIPA2, the principal objectives of the project were to develop key components required to deploy and demonstrate second-generation (2G) high temperature superconductor (HTS) cables in a 600 meter (2000 feet) underground segment of a 138kV three-phase transmission circuit of the Long Island Power Authority (LIPA) power grid. A previous effort under DOE Award DE-FC36-03GO13032 (referred to as LIPA1) resulted in installation (and subsequent successful operation) of first-generation (1G) HTS cables at the LIPA site. As with LIPA1, American Superconductor (AMSC) led the effort for LIPA2 and was responsible for overall management of the project and producing sufficient 2G wire to fabricate the required cable. Nexans' tasks included design/manufacture/installation of the cable, joint (splice), cable terminations and field repairable cryostat; while work by Air Liquide involved engineering and installation support for the refrigeration system modifications.

  5. Selectivity of power system protections at power swings in power system

    Directory of Open Access Journals (Sweden)

    Jan Machowski

    2012-12-01

    Full Text Available The paper discusses out-of-step protection systems such as: generator pole slip protections, out of step tripping protections, distance protections of step-up transformer, distance protections of transmission lines and transformers, power swing blocking, and special out-of-step protection. It is shown that all these protections make up a protection system, to which a setting concept uniform for the entire power system has to be applied. If a power system is inappropriately equipped with these protections, or their settings are inappropriate, they may operate unselectively, thus contributing to the development of power system blackouts. In the paper the concepts for a real power system are given for the two stages: target stage fully compliant with selectivity criteria, and transitional stage between the current and target stages.

  6. Space Weather Effects on Current and Future Electric Power Systems

    Science.gov (United States)

    Munoz, D.; Dutta, O.; Tandoi, C.; Brandauer, W.; Mohamed, A.; Damas, M. C.

    2016-12-01

    This work addresses the effects of Geomagnetic Disturbances (GMDs) on the present bulk power system as well as the future smart grid, and discusses the mitigation of these geomagnetic impacts, so as to reduce the vulnerabilities of the electric power network to large space weather events. Solar storm characterized by electromagnetic radiation generates geo-electric fields that result in the flow of Geomagnetically Induced Currents (GICs) through the transmission lines, followed by transformers and the ground. As the ground conductivity and the power network topology significantly vary with the region, it becomes imperative to estimate of the magnitude of GICs for different places. In this paper, the magnitude of GIC has been calculated for New York State (NYS) with the help of extensive modelling of the whole NYS electricity transmission network using real data. Although GIC affects only high voltage levels, e.g. above 300 kV, the presence of coastline in NYS makes the low voltage transmission lines also susceptible to GIC. Besides this, the encroachment of technologies pertaining to smart grid implementation, such as Phasor Measurement Units (PMUs), Microgrids, Flexible AC Transmission System (FACTS), and Information and Communication Technology (ICT) have been analyzed for GMD impacts. Inaccurate PMU results due to scintillation of GPS signals that are affected by electromagnetic interference of solar storm, presence of renewable energy resources in coastal areas that are more vulnerable to GMD, the ability of FACTS devices to either block or pave new path for GICs and so on, shed some light on impacts of GMD on smart grid technologies.

  7. Effects of the small molecule HERG activator NS1643 on Kv11.3 channels.

    Directory of Open Access Journals (Sweden)

    Arne Bilet

    Full Text Available NS1643 is one of the small molecule HERG (Kv11.1 channel activators and has also been found to increase erg2 (Kv11.2 currents. We now investigated whether NS1643 is also able to act as an activator of Kv11.3 (erg3 channels expressed in CHO cells. Activation of rat Kv11.3 current occurred in a dose-dependent manner and maximal current increasing effects were obtained with 10 µM NS1643. At this concentration, steady-state outward current increased by about 80% and the current increase was associated with a significant shift in the voltage dependence of activation to more negative potentials by about 15 mV. In addition, activation kinetics were accelerated, whereas deactivation was slowed. There was no significant effect on the kinetics of inactivation and recovery from inactivation. The strong current-activating agonistic effect of NS1643 did not result from a shift in the voltage dependence of Kv11.3 channel inactivation and was independent from external Na(+ or Ca(2+. At the higher concentration of 20 µM, NS1643 induced clearly less current increase. The left shift in the voltage dependence of activation reversed and the voltage sensitivity of activation dramatically decreased along with a slowing of Kv11.3 channel activation. These data show that, in comparison to other Kv11 family members, NS1643 exerts distinct effects on Kv11.3 channels with especially pronounced partial antagonistic effects at higher concentration.

  8. Probabilistic management of power distribution systems; Probabilistisch netbeheer

    Energy Technology Data Exchange (ETDEWEB)

    Roggen, M. (ed.)

    2005-07-01

    Managers of electricity networks must be able to answer the question how their investments contribute to minimizing the consequences of power failures. A probabilistic approach weighs risks based on which the most efficient method to prevent failures can be chosen. Use is made of a network calculation program (PowerFactory) and a simulation model and an Excel interface to carry out stochastic calculations. [Dutch] Sinds begin dit jaar geldt dat aan de voorwaarde van het n-1 principe voor netten met een spanningsniveau lager dan 220 kV niet langer in alle gevallen hoeft te worden voldaan. Bijvoorbeeld als de kosten van een investering niet opwegen tegen de maatschappelijke belangen. Dat geeft netbeheerders de ruimte om andere criteria aan te leggen voor ontwerp en onderhoud. Netbeheerders kunnen veel baat hebben bij een probabilistische benadering die alle risico's vooraf inzichtelijk en daarmee beheersbaar maakt. KEMA koppelde PowerFactory aan een probabilistisch simulatiemodel, in combinatie met een Excel-interface, waarmee allerhande variabelen kunnen worden ingevoerd om stochastische berekeningen mee uit te voeren.

  9. MicroRNA-Mediated Downregulation of the Potassium Channel Kv4.2 Contributes to Seizure Onset

    Directory of Open Access Journals (Sweden)

    Christina Gross

    2016-09-01

    Full Text Available Seizures are bursts of excessive synchronized neuronal activity, suggesting that mechanisms controlling brain excitability are compromised. The voltage-gated potassium channel Kv4.2, a major mediator of hyperpolarizing A-type currents in the brain, is a crucial regulator of neuronal excitability. Kv4.2 expression levels are reduced following seizures and in epilepsy, but the underlying mechanisms remain unclear. Here, we report that Kv4.2 mRNA is recruited to the RNA-induced silencing complex shortly after status epilepticus in mice and after kainic acid treatment of hippocampal neurons, coincident with reduction of Kv4.2 protein. We show that the microRNA miR-324-5p inhibits Kv4.2 protein expression and that antagonizing miR-324-5p is neuroprotective and seizure suppressive. MiR-324-5p inhibition also blocks kainic-acid-induced reduction of Kv4.2 protein in vitro and in vivo and delays kainic-acid-induced seizure onset in wild-type but not in Kcnd2 knockout mice. These results reveal an important role for miR-324-5p-mediated silencing of Kv4.2 in seizure onset.

  10. SIMULATION OF THE TRANSITIONAL REGIME OF THE MOLDOVAN POWER UNDER STATIC STABILITY

    Directory of Open Access Journals (Sweden)

    Postolaty V.M.

    2013-04-01

    Full Text Available The paper presents the outcome of the Moldovan power system static stability modeling and analysis, considering the operation in parallel with the Ukrainian power system and the established operation regimes. The analysis includes verification of the reserve of static stability and definition of the static stability limits for a given operation mode, and the determination of the power system stability domain of the controlled system nodes. Parameters used for the analysis are the active power flows via controlled sections and the voltage levels at the controlled system nodes. Two options of Moldovan power system scheme are considered: a single-circuit transit Dniester HPP - Balti - Straseni – Chisinau 330kV and a double-circuit transit. Studies have shown that the implementation of the double-circuit transit would lead to better static stability parameters and lower power system losses. The analysis has been carried out based on the power system stability.

  11. Controlled Compact High Voltage Power Lines

    Directory of Open Access Journals (Sweden)

    Postolati V.

    2016-04-01

    Full Text Available Nowadays modern overhead transmission lines (OHL constructions having several significant differences from conventional ones are being used in power grids more and more widely. Implementation of compact overhead lines equipped with FACTS devices, including phase angle regulator settings (compact controlled OHL, appears to be one of the most effective ways of power grid development. Compact controlled AC HV OHL represent a new generation of power transmission lines embodying recent advanced achievements in design solutions, including towers and insulation, together with interconnection schemes and control systems. Results of comprehensive research and development in relation to 110–500kV compact controlled power transmission lines together with theoretical basis, substantiation, and methodological approaches to their practical application are presented in the present paper.

  12. Pharmacological Targeting Of Neuronal Kv7.2/3 Channels: A Focus On Chemotypes And Receptor Sites.

    Science.gov (United States)

    Miceli, Francesco; Soldovieri, Maria Virginia; Ambrosino, Paolo; Manocchio, Laura; Medoro, Alessandro; Mosca, Ilaria; Taglialatela, Maurizio

    2017-10-12

    The Kv7 (KCNQ) subfamily of voltage-gated potassium channels consists of 5 members (Kv7.1-5) each showing a characteristic tissue distribution and physiological roles. Given their functional heterogeneity, Kv7 channels represent important pharmacological targets for development of new drugs for neuronal, cardiac and metabolic diseases. In the present manuscript, we focus on describing the pharmacological relevance and the potential therapeutic applications of drugs acting on neuronally-expressed Kv7.2/3 channels, placing particular emphasis on the different modulator chemotypes, and highlighting their pharmacodynamic and, whenever possible, pharmacokinetic peculiarities. The present work is based on an in-depth search of the currently available scientific literature, and on our own experience and knowledge in the field of neuronal Kv7 channel pharmacology. Space limitations impeded to describe the full pharmacological potential of Kv7 channels; thus, we have chosen to focus on neuronal channels composed of Kv7.2 and Kv7.3 subunits, and to mainly concentrate on their involvement in epilepsy. An astonishing heterogeneity in the molecular scaffolds exploitable to develop Kv7.2/3 modulators is evident, with important structural/functional peculiarities of distinct compound classes. In the present work we have attempted to show the current status and growing potential of the Kv7 pharmacology field. We anticipate a bright future for the field, and we express our hopes that the efforts herein reviewed will result in an improved treatment of hyperexcitability (or any other) diseases. Copyright© Bentham Science Publishers; For any queries, please email at epub@benthamscience.org.

  13. A Novel Nanosecond Pulsed Power Unit for the Formation of ·OH in Water

    Science.gov (United States)

    Li, Shengli; Hu, Sheng; Zhang, Han

    2012-04-01

    A novel nanosecond pulsed power unit was developed for plasma treatment of wastewater, based on the theory of magnetic pulse compression and semiconductor opening switch (SOS). The peak value, rise time and pulse duration of the output voltage were observed to be -51 kV, 60 ns and 120 ns, respectively. The concentrations of ·OH generated by the novel nanosecond pulsed plasma power were determined using the method of high-performance liquid chromatography (HPLC). The results showed that the concentrations of ·OH increased with the increase in peak voltage, and the generation rates of ·OH were 4.1 × 10-10 mol/s, 5.7 × 10-10 mol/s, and 7.7 × 10-10 mol/s at 30 kV, 35 kV, and 40 kV, respectively. The efficiency of OH generation was found to be independent of the input parameters for applied power, with an average value of 3.23×10-12 mol/J obtained.

  14. A Novel Nanosecond Pulsed Power Unit for the Formation of ·OH in Water

    International Nuclear Information System (INIS)

    Li Shengli; Hu Sheng; Zhang Han

    2012-01-01

    A novel nanosecond pulsed power unit was developed for plasma treatment of wastewater, based on the theory of magnetic pulse compression and semiconductor opening switch (SOS). The peak value, rise time and pulse duration of the output voltage were observed to be -51 kV, 60 ns and 120 ns, respectively. The concentrations of ·OH generated by the novel nanosecond pulsed plasma power were determined using the method of high-performance liquid chromatography (HPLC). The results showed that the concentrations of ·OH increased with the increase in peak voltage, and the generation rates of ·OH were 4.1 × 10 -10 mol/s, 5.7 × 10 -10 mol/s, and 7.7 × 10 -10 mol/s at 30 kV, 35 kV, and 40 kV, respectively. The efficiency of OH generation was found to be independent of the input parameters for applied power, with an average value of 3.23×10 -12 mol/J obtained. (plasma technology)

  15. A 70 kV solid-state high voltage pulse generator based on saturable pulse transformer.

    Science.gov (United States)

    Fan, Xuliang; Liu, Jinliang

    2014-02-01

    High voltage pulse generators are widely applied in many fields. In recent years, solid-state and operating at repetitive mode are the most important developing trends of high voltage pulse generators. A solid-state high voltage pulse generator based on saturable pulse transformer is proposed in this paper. The proposed generator is consisted of three parts. They are charging system, triggering system, and the major loop. Saturable pulse transformer is the key component of the whole generator, which acts as a step-up transformer and main switch during working process of this generator. The circuit and working principles of the proposed pulse generator are introduced first in this paper, and the saturable pulse transformer used in this generator is introduced in detail. Circuit of the major loop is simulated to verify the design of the system. Demonstration experiments are carried out, and the results show that when the primary energy storage capacitor is charged to a high voltage, such as 2.5 kV, a voltage with amplitude of 86 kV can be achieved on the secondary winding. The magnetic core of saturable pulse transformer is saturated deeply and the saturable inductance of the secondary windings is very small. The switch function of the saturable pulse transformer can be realized ideally. Therefore, a 71 kV output voltage pulse is formed on the load. Moreover, the magnetic core of the saturable pulse transformer can be reset automatically.

  16. CEBAF 200 kV Inverted Electron Gun

    International Nuclear Information System (INIS)

    Grames, J.M.; Adderley, P.A.; Clark, J.; Hansknecht, J.; Poelker, M.; Stutzman, M.L.; Suleiman, R.; Surles-Law, K.E.L.

    2011-01-01

    Two DC high voltage GaAs photoguns have been built at Jefferson Lab based on a compact inverted insulator design. One photogun provides the polarized electron beam at CEBAF and operates at 130 kV bias voltage. The other gun is used for high average current lifetime studies at a dedicated test facility and has been operated at bias voltage up to 225 kV. The advantages of higher DC voltage for CEBAF include reduced space-charge emittance growth and the potential for prolonged photocathode lifetime. However, a consequence of operating at higher voltages is the increased likelihood of field emission or breakdown, both of which are unacceptable. Highlights of the R and D studies leading toward a production 200keV GaAs photogun for CEBAF will be presented.

  17. Evaluation of the Harmonic Impedance of Frydlant (Line 53 Power Network

    Directory of Open Access Journals (Sweden)

    Shehab Abdulwadood Ali

    2013-01-01

    Full Text Available The harmonic impedance of the power system is an important quantity, which describes the behaviour of the power system with the existence of different frequencies beside the fundamental. The harmonic study belongs to the most difficult part of the electrical measurements and calculations even by using computer software. The main problem accompanying the calculating methods is to obtain the exact data of the electrical network parameters or to know the exact operational status of the system. In this paper the harmonic impedance of Frydlant (line 53, 22~kV in Czech Republic power network was calculated by using a very specialized software and suitable for solving such calculations called "NetCalc. version 3.0" [1].

  18. First 735 kV transmission, Manicouagan, Montreal

    Energy Technology Data Exchange (ETDEWEB)

    Cahill, L

    1964-11-01

    The 735 kV transmission network of Hydro Quebec is described giving reasons for choice of voltage, stability factors level of insulation, disposition of conductors, insulators, equipment used and state of readiness of the project.

  19. Solid state modulator for klystron power supply XFEL TDS INJ

    Science.gov (United States)

    Zavadtsev, A. A.; Zavadtsev, D. A.; Zybin, D. A.; Churanov, D. V.; Shemarykin, P. V.

    2016-09-01

    The transverse deflecting system XFEL TDS INJ for European X-ray Free Electron Laser includes power supply for the CPI VKS-8262HS klystron. It has been designed for pulse high-voltage, cathode heating, solenoid and klystron ion pump. The klystron power supply includes solid state modulator, pulse transformer, controlled power supply for cathode heating and commercial power supplies for solenoid and ion pump. Main parameters of the modulator are 110 kV of peak voltage, 72 A peak current, and pulse length up to 6 μs. The klystron power supply has been developed, designed, manufactured, tuned, tested and installed in the XFEL building. All designed parameters are satisfied.

  20. Development of high power klystron. 3. Development of klystron No.2

    International Nuclear Information System (INIS)

    Hirano, K.; Wang, Y.L.; Sato, I.

    2000-08-01

    A high power klystron has been developed as the RF source of the high power CW electron linac (10 MeV, 100 mA, 1.249135 GHz). CW power of 1.2 MW and efficiencies over 65% at a beam voltage 85 kV were the design goal. We developed a long pill-box type beryllia window (long pill-box window) withstood the RF power of 1.7 MW (CW) and replaced the standard pill-box window of the prototype klystron with long pill-box window. The high power RF test was carried out with the converted klystron. This klystron has achieved CW RF power of 885 kW and efficiency of 47% at beam voltage of 85 kV. This paper describes key points of the designs to achieve the RF power over 1.2 MW and results of the high power RF test of the second klystron, which has been optimized by simulation codes to improve better efficiency. The second klystron has achieved the maximum efficiency of 56.5% with CW output power of 782 kW at a beam voltage of 80 kV and a cathode current of 20.4 A in present. The third klystron will be manufactured to reflect results of this test. (author)

  1. Specific Kv1.3 blockade modulates key cholesterol-metabolism-associated molecules in human macrophages exposed to ox-LDL.

    Science.gov (United States)

    Yang, Yong; Wang, Yan-Fu; Yang, Xiao-Fang; Wang, Zhao-Hui; Lian, Yi-Tian; Yang, Ying; Li, Xiao-Wei; Gao, Xiang; Chen, Jian; Shu, Yan-Wen; Cheng, Long-Xian; Liao, Yu-Hua; Liu, Kun

    2013-01-01

    Cholesterol-metabolism-associated molecules, including scavenger receptor class A (SR-A), lectin-like oxidized low-density lipoprotein receptor-1 (LOX-1), CD36, ACAT1, ABCA1, ABCG1, and scavenger receptor class B type I, can modulate cholesterol metabolism in the transformation from macrophages to foam cells. Voltage-gated potassium channel Kv1.3 has increasingly been demonstrated to play an important role in the modulation of macrophage function. Here, we investigate the role of Kv1.3 in modulating cholesterol-metabolism-associated molecules in human acute monocytic leukemia cell-derived macrophages (THP-1 macrophages) and human monocyte-derived macrophages exposed to oxidized LDL (ox-LDL). Human Kv1.3 and Kv1.5 channels (hKv1.3 and hKv1.5) are expressed in macrophages and form a heteromultimeric channel. The hKv1.3-E314 antibody that we had generated as a specific hKv1.3 blocker inhibited outward delayed rectifier potassium currents, whereas the hKv1.5-E313 antibody that we had generated as a specific hKv1.5 blocker failed. Accordingly, the hKv1.3-E314 antibody reduced percentage of cholesterol ester and enhanced apoA-I-mediated cholesterol efflux in THP-1 macrophages and human monocyte-derived macrophages exposed to ox-LDL. The hKv1.3-E314 antibody downregulated SR-A, LOX-1, and ACAT1 expression and upregulated ABCA1 expression in THP-1 macrophages and human monocyte-derived macrophages. Our results reveal that specific Kv1.3 blockade represents a novel strategy modulating cholesterol metabolism in macrophages, which benefits the treatment of atherosclerotic lesions.

  2. Recombinant expression of margatoxin and agitoxin-2 in Pichia pastoris: an efficient method for production of KV1.3 channel blockers.

    Directory of Open Access Journals (Sweden)

    Raveendra Anangi

    Full Text Available The K(v1.3 voltage-gated potassium channel regulates membrane potential and calcium signaling in human effector memory T cells that are key mediators of autoimmune diseases such as multiple sclerosis, type 1 diabetes, and rheumatoid arthritis. Thus, subtype-specific K(v1.3 blockers have potential for treatment of autoimmune diseases. Several K(v1.3 channel blockers have been characterized from scorpion venom, all of which have an α/β scaffold stabilized by 3-4 intramolecular disulfide bridges. Chemical synthesis is commonly used for producing these disulfide-rich peptides but this approach is time consuming and not cost effective for production of mutants, fusion proteins, fluorescently tagged toxins, or isotopically labelled peptides for NMR studies. Recombinant production of K(v1.3 blockers in the cytoplasm of E. coli generally necessitates oxidative refolding of the peptides in order to form their native disulfide architecture. An alternative approach that avoids the need for refolding is expression of peptides in the periplasm of E. coli but this often produces low yields. Thus, we developed an efficient Pichia pastoris expression system for production of K(v1.3 blockers using margatoxin (MgTx and agitoxin-2 (AgTx2 as prototypic examples. The Pichia system enabled these toxins to be obtained in high yield (12-18 mg/L. NMR experiments revealed that the recombinant toxins adopt their native fold without the need for refolding, and electrophysiological recordings demonstrated that they are almost equipotent with the native toxins in blocking K(V1.3 (IC(50 values of 201±39 pM and 97 ± 3 pM for recombinant AgTx2 and MgTx, respectively. Furthermore, both recombinant toxins inhibited T-lymphocyte proliferation. A MgTx mutant in which the key pharmacophore residue K28 was mutated to alanine was ineffective at blocking K(V1.3 and it failed to inhibit T-lymphocyte proliferation. Thus, the approach described here provides an efficient method of

  3. Concept design of the high voltage transmission system for the collider tunnel

    International Nuclear Information System (INIS)

    Norman, L.S.

    1992-03-01

    In order to provide electrical service to the Superconducting Super Collider Laboratory (SSCL) 54-mile-circumference collider of 125 MVA at 69 kV or 155 MVA at 138 kV of distributed power, it must be demonstrated that the concept design for a high-voltage transmission system can meet the distribution requirements of the collider electrical system with its cryogenic system's large motor loads and its pulsed power technical systems. It is a practical design, safe for operating personnel and cost-effective. The normal high-voltage transmission techniques of overhead and underground around the 54-mile collider tunnel could not be applied because of technical and physical constraints, or was environmentally unacceptable. The approach taken to solve these problems is the installation of 69-kV or 138-kV exposed solid dielectric transmission cable inside the collider tunnel with the superconducting magnets, cryogenic piping, electrical medium, and low-voltage distribution systems, and electronic/instrumentation wiring systems. This mixed-use approach has never been attempted in a collider tunnel. Research into all aspects of the engineering and installation problems and consultation with transmission cable manufacturers, electrical utilities, and European entities with similar installations -- such as the Channel Tunnel -- demonstrate that the concept design is feasible and practical. This paper presents a history of the evolution of the concept design. Design studies are underway to determine the system configuration and voltages. Included in this report are tunnel transmission cable system considerations and evaluation of solid dielectric high-voltage cable design

  4. Concept design of the high-voltage transmission system for the collider tunnel

    International Nuclear Information System (INIS)

    Norman, L.S.

    1992-01-01

    In order to provide electrical service to the Superconducting Super Collider Laboratory (SSCL) 54-mile-circumference collider of 125 MVA at 69 kV or 155 MVA at 138 kV of distributed power, it must be demonstrated that the concept design for a high-voltage transmission system can meet the distribution requirements of the collider electrical system with its cryogenic system's large motor loads and its pulsed power technical systems. It is a practical design, safe for operating personnel and cost-effective. The normal high-voltage transmission techniques of overhead and underground around the 54-mile collider tunnel could not be applied because of technical and physical constraints, or was environmentally unacceptable. The approach taken to solve these problems is the installation of 69-kV or 138-kV exposed solid dielectric transmission cable inside the collider tunnel with the superconducting magnets, cryogenic piping, electrical medium, and low-voltage distribution systems, and electronic/instrumentation wiring systems. This mixed-use approach has never been attempted in a collider tunnel. Research into all aspects of the engineering and installation problems and consultation with transmission cable manufacturers, electrical utilities, and European entities with similar installations-such as the Channel Tunnel-demonstrate that the concept design is feasible and practical. This paper presents a history of the evolution of the concept design. Design studies are underway to determine the system configuration and voltages. Included in this report are tunnel transmission cable system considerations and evaluation of solid dielectric high-voltage cable design

  5. Modellering og måling af metan-emission fra kvæg

    DEFF Research Database (Denmark)

    Storm, I; Hellwing, Anne Louise Frydendahl; Nielsen, N I

    2011-01-01

    Udvikling af og kendskab til de metoder, der bruges til måling af kvægs metan-emission udgør en vigtig del af forskningen indenfor området. I dette indlæg præsenteres de mest anvendte metoder til måling og estimation af kvægs metan-emission, herunder modeller, in vitro inkubation, kammer-metoder,......-metoder, SF6-metoden og CO2-metoden. De enkelte metoder beskrives og fordele, ulemper og anvendelsesområder sammenlignes. Dette er vigtig baggrundsinformation for forståelse og fortolkning af øvrige forskningsresultater og for at kunne planlægge fremtidige projekter.......Udvikling af og kendskab til de metoder, der bruges til måling af kvægs metan-emission udgør en vigtig del af forskningen indenfor området. I dette indlæg præsenteres de mest anvendte metoder til måling og estimation af kvægs metan-emission, herunder modeller, in vitro inkubation, kammer...

  6. Autonomous power networks based power system

    International Nuclear Information System (INIS)

    Jokic, A.; Van den Bosch, P.P.J.

    2006-01-01

    This paper presented the concept of autonomous networks to cope with this increased complexity in power systems while enhancing market-based operation. The operation of future power systems will be more challenging and demanding than present systems because of increased uncertainties, less inertia in the system, replacement of centralized coordinating activities by decentralized parties and the reliance on dynamic markets for both power balancing and system reliability. An autonomous network includes the aggregation of networked producers and consumers in a relatively small area with respect to the overall system. The operation of an autonomous network is coordinated and controlled with one central unit acting as an interface between internal producers/consumers and the rest of the power system. In this study, the power balance problem and system reliability through provision of ancillary services was formulated as an optimization problem for the overall autonomous networks based power system. This paper described the simulation of an optimal autonomous network dispatching in day ahead markets, based on predicted spot prices for real power, and two ancillary services. It was concluded that large changes occur in a power systems structure and operation, most of them adding to the uncertainty and complexity of the system. The introduced concept of an autonomous power network-based power system was shown to be a realistic and consistent approach to formulate and operate a market-based dispatch of both power and ancillary services. 9 refs., 4 figs

  7. Molecular Expression and Pharmacological Evidence for a Functional Role of Kv7 Channel Subtypes in Guinea Pig Urinary Bladder Smooth Muscle

    Science.gov (United States)

    Afeli, Serge A. Y.; Malysz, John; Petkov, Georgi V.

    2013-01-01

    Voltage-gated Kv7 (KCNQ) channels are emerging as essential regulators of smooth muscle excitability and contractility. However, their physiological role in detrusor smooth muscle (DSM) remains to be elucidated. Here, we explored the molecular expression and function of Kv7 channel subtypes in guinea pig DSM by RT-PCR, qRT-PCR, immunohistochemistry, electrophysiology, and isometric tension recordings. In whole DSM tissue, mRNAs for all Kv7 channel subtypes were detected in a rank order: Kv7.1~Kv7.2Kv7.3~Kv7.5Kv7.4. In contrast, freshly-isolated DSM cells showed mRNA expression of: Kv7.1~Kv7.2Kv7.5Kv7.3~Kv7.4. Immunohistochemical confocal microscopy analyses of DSM, conducted by using co-labeling of Kv7 channel subtype-specific antibodies and α-smooth muscle actin, detected protein expression for all Kv7 channel subtypes, except for the Kv7.4, in DSM cells. L-364373 (R-L3), a Kv7.1 channel activator, and retigabine, a Kv7.2-7.5 channel activator, inhibited spontaneous phasic contractions and the 10-Hz electrical field stimulation (EFS)-induced contractions of DSM isolated strips. Linopiridine and XE991, two pan-Kv7 (effective at Kv7.1-Kv7.5 subtypes) channel inhibitors, had opposite effects increasing DSM spontaneous phasic and 10 Hz EFS-induced contractions. EFS-induced DSM contractions generated by a wide range of stimulation frequencies were decreased by L-364373 (10 µM) or retigabine (10 µM), and increased by XE991 (10 µM). Retigabine (10 µM) induced hyperpolarization and inhibited spontaneous action potentials in freshly-isolated DSM cells. In summary, Kv7 channel subtypes are expressed at mRNA and protein levels in guinea pig DSM cells. Their pharmacological modulation can control DSM contractility and excitability; therefore, Kv7 channel subtypes provide potential novel therapeutic targets for urinary bladder dysfunction. PMID:24073284

  8. Operating characteristics and modeling of the LLNL 100-kV electric gun

    International Nuclear Information System (INIS)

    Osher, J.E.; Barnes, G.; Chau, H.H.; Lee, R.S.; Lee, C.; Speer, R.; Weingart, R.C.

    1989-01-01

    In the electric gun, the explosion of an electrically heated metal foil and the accompanying magnetic forces drive a thin flyer plate up a short barrel. Flyer velocities of up to 18 km/s make the gun useful for hypervelocity impact studies. The authors briefly review the technological evolution of the exploding-metal circuit elements that power the gun, describe the 100-kV electric gun designed at Lawrence Livermore National Laboratory (LLNL) in some detail, and present the general principles of electric gun operation. They compare the experimental performance of the LLNL gun with a simple model and with predictions of a magnetohydrodynamics code

  9. Power system stabilizer control for wind power to enhance power system stability

    OpenAIRE

    Domínguez García, José Luís; Gomis Bellmunt, Oriol; Bianchi, Fernando Daniel; Sumper, Andreas

    2011-01-01

    The paper presents a small signal stability analysis for power systems with wind farm interaction. Power systems have damping oscillation modes that can be excited by disturbance or fault in the grid. The power converters of the wind farms can be used to reduce these oscillations and make the system more stable. These ideas are explored to design a power system stabilized (PSS) for a network with conventional generators and a wind farm in order to increase the damping of the oscillation...

  10. IHEP S-band 45 MW pulse power klystron development

    International Nuclear Information System (INIS)

    Dong Dong; Zhou Zusheng; Zhang Liang; Li Gangying; Tian Shuangmin

    2006-01-01

    S-band 45 MW pulse power klystron has been developed in the Institute of High Energy Physics (IHEP) for the Beijing Electron Positron Collider (BEPC) upgrade projects (BEPC-II). This new klystron has 5 cavities in its RF-beam interaction and single RF output window, and the RF output power is 45 MW at 310 kV, the gain is 50 dB, the efficiency 40%. The manufacturing, training and testing of a prototype klystron has been finished in IHEP and RF power 45 MW at 300 kV has been reached. The testing results show that all the parameters of the 45 MW klystron reach the design goal. (authors)

  11. Aspects related to the interaction of Angra I with the Furnas system

    International Nuclear Information System (INIS)

    Silva, Lourenca Francisca da

    1982-10-01

    This work studies the following aspects related to the interaction of the Angra I power plant with the Furnas electric network: reliability of alternative sources, 500 kV and 138 kV systems and emergency diesel generators; operation capacity of Angra I and performance of Angra I and the future power plants Angra II and III. In the first part, after the Furnas network and the main systems of the Angra I power plant (specially the electrical system) have been analysed, the reliability for each source was computed separately and then the results lumped together. The reliability computation for the 500 kV system was done employing the computer code CST-ELETROSUL (reliability or transmission system) and for the remaining computations the fault tree theory was used, resulting in a number that represents the approximate value of the alternative sources, referring to the assumed considerations. In the second part, some limitations in the operation capacity of Angra I were verified, suggesting that the power plant should operate in base-load for safety reasons. In order to determine the factors that define the performance of a Nuclear Power Plant, FDIS, FCON, FINP and FIP, the works already accomplished by Centrais Eletricas Brasileiras S/A - ELETROBRAS were taken as a basis and were implemented with more recent data about operation of the nuclear power plant PWR. The computer code SPSS (Statistical Package for the Social Sciences) was utilized for obtaining the factors concerning to power plant with the capacity of Angra I, II and III. From the obtained valves and with the static generation capacity theory, were composed the load permanency curves from the unity 1 and for the three unities lumped together in the CNAA site. (author)

  12. The power industry of the Magadan oblast: part of the Leninist GOELRO (State Commission for the Electrification of Russia) plan

    Energy Technology Data Exchange (ETDEWEB)

    Pozdnyak, I.G.; Anishchenko, Ye.B.

    1981-01-01

    A brief history is given of the development of the Magadan oblast's power industry, which is inseparably connected with development of the very rich raw material resources and fast development of the mining industry. In 1985 completion of construction of the Kolyma GES is planned; with the end of its construction will begin preparatory work one Ust'-Srednekansk GES: the second GES of the Kalyma falls. Work has begun since 1981 to expand the third phase of the Magadan heat and electric power plant. In 1982 completion of installation of power equipment at the Arkagalinsk State regional power plant is planned. In the 11th five-year plan construction of the system of 220 kV power lines will be finished, and 110 and 35 kV power distribution lines will be built. A special place belongs to construction of the Lankovskaya thermal power plant, which will aid in creating a stable fuel-energy base with a positive future. Chukotka power will be further developed. By 1990, 18 more state farms should be connected to the state power system. Completing the power basis in the Magadan oblast will enable an acceleration in its development, and a rise in the material and cultural standard of living of the people of the Far Northeast.

  13. 35-kV GaAs subnanosecond photoconductive switches

    Science.gov (United States)

    Pocha, Michael D.; Druce, Robert L.

    1990-12-01

    High-voltage, fast-pulse generation using GaAs photoconductive switches is investigated. It is possible to to generate 35-kV pulses with risetimes as short as 135 ps using 5-mm gap switches, and electric field hold-off of greater than 100 kV/cm is achieved. An approximately 500-ps FWHM on/off electrical pulse is generated with an amplitude of approximately 3 kV using neutron-irradiated GaAs having short carrier lifetimes. Experimental results are described, and fabrication of switches and the diagnostics used to measure these fast signals are discussed. Experience with the nonlinear lock-on and avalanche modes of operation observed in GaAs is also described.

  14. Comparison between IEEE and CIGRE Thermal Behaviour Standards and Measured Temperature on a 132-kV Overhead Power Line

    Directory of Open Access Journals (Sweden)

    Alberto Arroyo

    2015-12-01

    Full Text Available This paper presents the steady and dynamic thermal balances of an overhead power line proposed by CIGRE (Technical Brochure 601, 2014 and IEEE (Std.738, 2012 standards. The estimated temperatures calculated by the standards are compared with the averaged conductor temperature obtained every 8 min during a year. The conductor is a LA 280 Hawk type, used in a 132-kV overhead line. The steady and dynamic state comparison shows that the number of cases with deviations to conductor temperatures higher than 5 ∘ C decreases from around 20% to 15% when the dynamic analysis is used. As some of the most critical variables are magnitude and direction of the wind speed, ambient temperature and solar radiation, their influence on the conductor temperature is studied. Both standards give similar results with slight differences due to the different way to calculate the solar radiation and convection. Considering the wind, both standards provide better results for the estimated conductor temperature as the wind speed increases and the angle with the line is closer to 90 ∘ . In addition, if the theoretical radiation is replaced by that measured with the pyranometer, the number of samples with deviations higher than 5 ∘ C is reduced from around 15% to 5%.

  15. Development of 6.6 kV/600 A superconducting fault current limiter using coated conductors

    Energy Technology Data Exchange (ETDEWEB)

    Yazawa, T., E-mail: takashi.yazawa@toshiba.co.j [Toshiba Corporation, Power Systems Company (Japan); Koyanagi, K.; Takahashi, M.; Toba, K.; Takigami, H.; Urata, M. [Toshiba Corporation, Power Systems Company (Japan); Iijima, Y.; Saitoh, T. [Fujikura Ltd. (Japan); Amemiya, N. [Superconductivity Research Laboratory, ISTEC (Japan); Shiohara, Y. [Department of Electrical Engineering, Kyoto University (Japan); Ito, T. [Tokyo Gas Co., Ltd. (Japan)

    2009-10-15

    As one of the programs in the Ministry of Economy, Trade and Industry (METI) project regarding R and D on superconducting coated conductor, three-phase superconducting fault current limiter (SFCL) for 6.6 kV application was developed and successfully tested. The developed SFCL was mainly comprised three-phase set of current limiting coils installed in a sub-cooled nitrogen cryostat with a GM cryocooler, circuit breakers and a sequence circuit. The whole system was installed in a cubicle. Two tapes of coated conductor were wound in parallel in each coil to obtain the rated current of 72 A rms. After developing the whole SFCL system, short circuit experiments were implemented with a short circuit generator. In a three-line ground fault test, the SFCL successfully restricted the prospected short circuit current over 1.6 kA to about 800 A by the applied voltage of 6.6 kV. The SFCL was installed in a user field and connected with a gas engine generator, followed by a consecutive operation. In this program, 600 A class FCL coil, with which four coated conductor tapes were wound, was also developed. The coil showed sufficiently low AC loss at the rated current. With these results, the program attained the planned target of the fundamentals for the 6.6 kV/600 A SFCL.

  16. Stockholm Power Tech. Power systems

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1995-11-01

    The proceedings from this symposium is presented in six volumes: Invited speakers` sessions; Power systems; Power electronics; High-voltage technology; Electrical machines and drives; and Information and control systems. This report covers the power systems volume. Separate abstracts have been prepared for 141 of the 145 papers in this volume

  17. Stockholm Power Tech. Power systems

    International Nuclear Information System (INIS)

    1995-01-01

    The proceedings from this symposium is presented in six volumes: Invited speakers' sessions; Power systems; Power electronics; High-voltage technology; Electrical machines and drives; and Information and control systems. This report covers the power systems volume. Separate abstracts have been prepared for 141 of the 145 papers in this volume

  18. Choice of 735 kV transmission economics and system performance

    Energy Technology Data Exchange (ETDEWEB)

    McGillis, D T

    1966-01-01

    The present Hydro Quebec load is 8,000 MW and is expected to be 16,000 MW by the late 1970's and 26,000 MW by the middle of the 1980's. This load is concentrated in the area along the St. Lawrence River between Quebec City and Montreal where most of Quebec's six million people live. Fortunately there is in the Province of Quebec enough hydroelectric potential to meet the increase in load that is expected to develop over the next 15 to 20 years. These new sources are, however, at least 500 miles away from the Montreal-Quebec load area. Though this consideration had some bearing on the planning of the Hydro-Quebec ehv network, the choice of 735 kV transmission for the Manicouagan-Outardes project was based principally on economic studies of alternative transmission facilities for this specific project.

  19. Pulsed Power Supply Based on Magnetic Energy Storage for Non-Destructive High Field Magnets

    Science.gov (United States)

    Aubert, G.; Defoug, S.; Joss, W.; Sala, P.; Dubois, M.; Kuchinsk, V.

    2004-11-01

    The first test results of a recently built pulsed power supply based on magnetic energy storage will be described. The system consists of the 16 kV shock alternator with a short-circuit power of 3600 MVA of the VOLTA Testing Center of the Schneider Electric SA company, a step-down transformer with a ratio of 1/24, a three-phase diode bridge designed for a current rising exponentially to 120 kA, and a big, 10 ton, heavy, 10 mH aluminum storage coil. The system is designed to store 72 MJ, normal operation will be at 50 MJ, and will work with voltages up to 20 kV. A transfer of 20% of the stored energy into the high field coil should be possible. Special making switches and interrupters have been developed to switch the high currents in a very short time. For safety and redundancy two independent monitoring systems control the energy transfer. A sequencing control system operates the switches on the ac side and protective switches on the dc side, a specially developed real-time control-monitoring system checks several currents and voltages and commands the dc circuit breakers and making switches.

  20. Protein kinase A stimulates Kv7.1 surface expression by regulating Nedd4-2-dependent endocytic trafficking

    DEFF Research Database (Denmark)

    Andersen, Martin Nybo; Hefting, Louise Leth; Steffensen, Annette Buur

    2015-01-01

    The potassium channel Kv7.1 plays critical physiological roles in both heart and epithelial tissues. In heart, Kv7.1 and the accessory subunit KCNE1 forms the IKs current, which is enhanced by PKA mediated phosphorylation. The observed current increase requires both phosphorylation of Kv7.......1 and the presence of KCNE1. However, PKA also stimulates Kv7.1 currents in epithelial tissues, such as colon, where the channel does not co-assemble with KCNE1. Here, we demonstrate that PKA activity significantly impacts the subcellular localization of Kv7.1 in Madin Darby Canine Kidney cells. While PKA inhibition...... reduced the fraction of channels at the cell surface, PKA activation increased it. We show that PKA inhibition lead to intracellular accumulation of Kv7.1 in late endosomes/lysosomes. By mass spectroscopy we identified eight phosphorylated residues on Kv7.1, however, none appeared to play a role...