WorldWideScience

Sample records for fire protection improvements

  1. Improvement of fire protection measures for nuclear power plants

    International Nuclear Information System (INIS)

    2012-01-01

    Improvements of fire protection measures for nuclear power plants were performed as following items: Development of fire hazard analysis method. Application of developed Fire Dynamic tool to actual plants, With regard to fire tests for the fire data acquisition, cable fire test and oil fire test were performed. Implementation of fire hazard analysis code and simulation were performed as following items: Fire analysis codes FDS, SYLVIA, CFAST were implemented in order to analyze the fire progression phenomena, Trial simulation of fire hazard as Metal-Clad Switch Gear Fire of ONAGAWA NPP in Tohoku earthquake (HEAF accident). (author)

  2. Improvement of fire protection measures for nuclear power plants

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2013-08-15

    Improvements of fire protection measures for nuclear power plants were performed as following items: Development of fire hazard analysis method. Application of developed Fire Dynamic Tool to actual plants (FDT{sup S}), With regard to fire tests for the fire data acquisition, cable fire test and High Energy Arcing Faults (HEAF) fire test were performed. Implementation of fire hazard analysis code and simulation were performed as following items: Fire analysis codes FDS, SYLVIA, and CFAST were implemented in order to analyze the fire progression phenomena. Trial simulation of HEAF accident of Onagawa NPP in Tohoku earthquake. (author)

  3. Fire protection

    International Nuclear Information System (INIS)

    Janetzky, E.

    1980-01-01

    Safety and fire prevention measurements have to be treated like the activities developing, planning, construction and erection. Therefore it is necessary that these measurements have to be integrated into the activities mentioned above at an early stage in order to guarantee their effectiveness. With regard to fire accidents the statistics of the insurance companies concerned show that the damage caused increased in the last years mainly due to high concentration of material. Organization of fire prevention and fire fighting, reasons of fire break out, characteristics and behaviour of fire, smoke and fire detection, smoke and heat venting, fire extinguishers (portable and stationary), construction material in presence of fire, respiratory protection etc. will be discussed. (orig./RW)

  4. Loft fire protection

    International Nuclear Information System (INIS)

    White, E.R.; Jensen, J.D.

    1980-01-01

    Quantified criteria that was developed and applied to provide in-depth fire protection for the Loss of Fluid Test (LOFT) Facility are presented. The presentation describes the evolution process that elevated the facility's fire protection from minimal to that required for a highly protected risk or improved risk. Explored are some infrequently used fire protection measures that are poorly understood outside the fire protection profession

  5. The improvement of the fire protections system for nuclear cycle facilities. Formulation of a fire protection guideline for nuclear fuel cycle facilities

    International Nuclear Information System (INIS)

    2012-04-01

    The private side Fire Protection Guideline was investigated with respect to the fire having taken place at the nuclear reactor site followed by the Chuetsu-Oki earthquake in Niigata Prefecture in 2007. To improve the fire protection system especially applicable to MOX fuel fabrication facilities, JNES (Japan Nuclear Energy Safety Organization) investigated private guidelines adopted in Japanese Light Water cooled Reactors, the standardized guidelines used in Nuclear Facilities in other countries including USA, and the standards in the chemical plants. The content of the guideline concerns the prevention of the fire breakout, the prevention of fire extension, the reduction of the fire effects, as well as the facility-characteristic protection countermeasures and the fire effect evaluations. (S. Ohno)

  6. Fire Protection Program Manual

    Energy Technology Data Exchange (ETDEWEB)

    Sharry, J A

    2012-05-18

    This manual documents the Lawrence Livermore National Laboratory (LLNL) Fire Protection Program. Department of Energy (DOE) Orders 420.1B, Facility Safety, requires LLNL to have a comprehensive and effective fire protection program that protects LLNL personnel and property, the public and the environment. The manual provides LLNL and its facilities with general information and guidance for meeting DOE 420.1B requirements. The recommended readers for this manual are: fire protection officers, fire protection engineers, fire fighters, facility managers, directorage assurance managers, facility coordinators, and ES and H team members.

  7. Aircraft Fire Protection Laboratory

    Data.gov (United States)

    Federal Laboratory Consortium — The Navy Aircraft Protection Laboratory provides complete test support for all Navy air vehicle fire protection systems.The facility allows for the simulation of a...

  8. Improvement of flame resistance of non-flame retardant cables by applying fire protection measures

    International Nuclear Information System (INIS)

    Takemura, Yujiro; Segoshi, Yoshinori; Jinno, Susumu; Mii, Kazuki

    2017-01-01

    The new regulatory requirements, which were put in force after the Fukushima Daiichi accident, impose the use of flame retardant cables on the plant components having safety functions for the purpose of fire protection. However, some Japanese nuclear power plants built in the early days use non-flame retardant cables that do not pass the demonstration test to check for the flame resistance. To cope with the new regulatory requirements, a fire protection measure for non-flame retardant cables was introduced to assure flame resistance of non-flame retardant cables equivalent to or higher than that of flame retardant cables. To illustrate the fire protection measure, both non-flame retardant cables and its cable tray are covered with fire protection sheet fabricated from incombustible material to form an assembly. Considering the demonstration test results, it can be concluded that flame resistance performance of non-flame retardant cables equivalent to or higher than that of flame retardant cables can be assured by forming the assembly even if an external fire outside the assembly and internal cable fire inside the assembly are assumed. This paper introduces the design of the assembly consisting of a bundle of cables and a cable tray and summarizes the results of demonstration tests. (author)

  9. Sodium fire protection

    International Nuclear Information System (INIS)

    Raju, C.; Kale, R.D.

    1979-01-01

    Results of experiments carried out with sodium fires to develop extinguishment techniques are presented. Characteristics, ignition temperature, heat evolution and other aspects of sodium fires are described. Out of the powders tested for extinguishment of 10 Kg sodium fires, sodium bi-carbonate based dry chemical powder has been found to be the best extinguisher followed by large sized vermiculite and then calcium carbonate powders distributed by spray nozzles. Powders, however, do not extinguish large fires effectively due to sodium-concrete reaction. To control large scale fires in a LMFBR, collection trays with protective cover have been found to cause oxygen starvation better than flooding with inert gas. This system has an added advantage in that there is no damage to the sodium facilities as has been in the case of powders which often contain chlorine compounds and cause stress corrosion cracking. (M.G.B.)

  10. FIRE PROTECTION SYSTEMS AND TECHNOLOGIES

    Directory of Open Access Journals (Sweden)

    Aristov Denis Ivanovich

    2016-03-01

    Full Text Available The All-Russian Congress “Fire Stop Moscow” was de-voted to the analysis of the four segments of the industry of fire protection systems and technologies: the design of fire protec-tion systems, the latest developments and technologies of active and passive fire protection of buildings, the state and the devel-opment of the legal framework, the practice of fire protection of buildings and structures. The forum brought together the repre-sentatives of the industry of fire protection systems, scientists, leading experts, specialists in fire protection and representatives of construction companies from different regions of Russia. In parallel with the Congress Industrial Exhibition of fire protection systems, materials and technology was held, where manufacturers presented their products. The urgency of the “Fire Stop Moscow” Congress in 2015 organized by the Congress Bureau ODF Events lies primarily in the fact that it considered the full range of issues related to the fire protection of building and construction projects; studied the state of the regulatory framework for fire safety and efficiency of public services, research centers, private companies and busi-nesses in the area of fire safety. The main practical significance of the event which was widely covered in the media space, was the opportunity to share the views and information between management, science, and practice of business on implementing fire protection systems in the conditions of modern economic relations and market realities. : congress, fire protection, systems, technologies, fire protection systems, exhibition

  11. Fire protection for clean rooms

    International Nuclear Information System (INIS)

    Kirson, D.

    1990-01-01

    The fire protection engineer often must decide what size fire can be tolerated before automatic fire suppression systems actuate. Is it a wastepaper basket fire, a bushel basket fire...? In the case of state-of-the-art clean rooms, the answer clearly is not even an incipient fire. Minor fires in clean rooms can cause major losses. This paper discusses what a clean room is and gives a brief overview of the unique fire protection challenges encountered. The two major causes of fire related to clean rooms in the semiconductor industry are flammable/pyrophoric gas fires in plastic ducts and polypropylene wet bench fires. This paper concentrates on plastic ductwork in clean rooms, sprinkler protection in ductwork, and protection for wet benches

  12. Fire protection measures

    International Nuclear Information System (INIS)

    Bittner

    1997-01-01

    The presentation could only show a very brief overview of the analysis results of a wide study of the existing fire protection situation at Mochovce. As far not already done the next steps will be the selection of the final suppliers of the different measures, the detailed design and the implementation of the measures. As part of the further assistance in fire protection EUCOM will perform compliance checks of the DD and implementation and assist EMO for raising problems. Especially during the implementation of the measures the belonging quality checks have a high priority. Assuming that the implementation of measures will be in accordance with with the study results and the relevant basic design requirements it can be stated that safety level concerning fire protection will be in accordance with international requirement like IAEA 50 SG D2. The next step of our work will be the delta analysis for 2 unit and the relevant basic design as far as there are differences to unit 1. (author)

  13. The economics of fire protection

    CERN Document Server

    Ramachandran, Ganapathy

    2003-01-01

    This important new book, the first of its kind in the fire safety field, discusses the economic problems faced by decision-makers in the areas of fire safety and fire precautions. The author considers the theoretical aspects of cost-benefit analysis and other relevant economic problems with practical applications to fire protection systems. Clear examples are included to illustrate these techniques in action. The work covers: * the performance and effectiveness of passive fire protection measures such as structural fire resistance and means of escape facilities, and active systems such as sprinklers and detectors * the importance of educating for better understanding and implementation of fire prevention through publicity campaigns and fire brigade operations * cost-benefit analysis of fire protection measures and their combinations, taking into account trade-offs between these measures. The book is essential reading for consultants and academics in construction management, economics and fire safety, as well ...

  14. National Fire Protection Association

    Science.gov (United States)

    ... closed NFPA Journal® NFPA Journal® Update (newsletter) Fire Technology ... die from American home fires, and another 13,000 are injured each year. This is the story of fire that the statistics won't show ...

  15. Forest fire occurrence and silvicultural-economic prerequisites for protection improvement in forest regions of Krasnoyarsk Krai

    Directory of Open Access Journals (Sweden)

    V. V. Furyaev

    2017-10-01

    Full Text Available The territory of the Krasnoyarsk Krai is substantially diverse in terms of climatic, silvicultural and economic conditions owing to its sufficient spread from the North to the South. These differences were to some extent taken into account when the forest fund of the Krasnoyarsk Krai was divided into seven forest regions: forest tundra of Central Siberia, highland taiga of Central Siberia, plain taiga of West Siberia, Angara region, subtaiga forest steppe of Central Siberia, Altai-Sayanskiy highland, Altai-Sayanskiy highland forest steppe. The regions show different levels of fire occurrence and different fire effects that require different levels of protection from forest fires. Optimization of the protection is based on activities that combine prevention and timely detection of fires depending on development of forest regions and intensity of forest management. The main focus of the paper is on possibility or inadvisability of prescribed fires, fire-use fires (fires that started naturally but were then managed for their beneficial effects and the system of activities increasing fire resistance of the most valuable forests. It is justified that taking into account the effects of forest fires, selective protection of forests is expedient in forest-tundra Middle Siberia and highland taiga of Middle Siberia regions. The whole area of plain taiga of West Siberia region should be subject to protection but with various levels of intensity in different parts of it. The forest fund of Angara, subtaiga forest steppe of Middle Siberia, Altai-Sayanskiy highland, Altai-Sayanskiy highland forest steppe regions should be protected on the whole area. Application of prescribed fires is relevant in the subzone of South taiga, in the forest steppe zone as well as in the submontane and lowland taiga belts. Fire-use fires are admissible on limited areas in the subzones of Middle and North taiga.

  16. Passive fire protection role and evolutions

    Energy Technology Data Exchange (ETDEWEB)

    Cerosky, Tristan [NUVIA (France); Perdrix, Johan [NUVIA Protection (France)

    2015-12-15

    Major incidents associated with nuclear power plants often invoke a re-examination of key safety barriers. Fire hazard, in particular, is a key concern for safe operation of nuclear power plants given its propensity to damage safety systems which could ultimately lead to radioactive release into the atmosphere. In the recent past, events such as the Fukushima disaster have led to an industry-wide push to improve nuclear safety arrangements. As part of these measures, upgrading of fire safety systems has received significant attention. In addition to the inherent intricacies associated with such a complex undertaking, factors such as frequent changes in the national and European fire regulations also require due attention while formulating a fire protection strategy. This paper will highlight some salient aspects underpinning an effective fire protection strategy. This will involve: A) A comprehensive introduction to the different aspects of fire safety (namely prevention, containment and mitigation) supported by a review of the development of the RCC-I from 1993 to 1997 editions and the ETC-F (AFCEN codes used by EDF in France). B) Development of the fire risk analysis methodology and the different functions of passive fire protection within this method involving confinement and protection of safety-related equipment. C) A review of the benefits of an effective passive fire protection strategy, alongside other arrangements (such as active fire protection) to a nuclear operator in term of safety and cost savings. It is expected that the paper will provide nuclear operators useful guidelines for strengthening existing fire protection systems.

  17. Standpipe systems for fire protection

    CERN Document Server

    Isman, Kenneth E

    2017-01-01

    This important new manual goes beyond the published NFPA standards on installation of standpipe systems to include the rules in the International Building Code, municipal fire codes, the National Fire Code of Canada, and information on inspection, testing, and maintenance of standpipe systems. Also covered are the interactions between standpipe and sprinkler systems, since these important fire protection systems are so frequently installed together. Illustrated with design examples and practical applications to reinforce the learning experience, this is the go-to reference for engineers, architects, design technicians, building inspectors, fire inspectors, and anyone that inspects, tests or maintains fire protection systems. Fire marshals and plan review authorities that have the responsibility for reviewing and accepting plans and hydraulic calculations for standpipe systems are also an important audience, as are firefighters who actually use standpipe systems. As a member of the committees responsible for s...

  18. Fire protection for launch facilities using machine vision fire detection

    Science.gov (United States)

    Schwartz, Douglas B.

    1993-02-01

    Fire protection of critical space assets, including launch and fueling facilities and manned flight hardware, demands automatic sensors for continuous monitoring, and in certain high-threat areas, fast-reacting automatic suppression systems. Perhaps the most essential characteristic for these fire detection and suppression systems is high reliability; in other words, fire detectors should alarm only on actual fires and not be falsely activated by extraneous sources. Existing types of fire detectors have been greatly improved in the past decade; however, fundamental limitations of their method of operation leaves open a significant possibility of false alarms and restricts their usefulness. At the Civil Engineering Laboratory at Tyndall Air Force Base in Florida, a new type of fire detector is under development which 'sees' a fire visually, like a human being, and makes a reliable decision based on known visual characteristics of flames. Hardware prototypes of the Machine Vision (MV) Fire Detection System have undergone live fire tests and demonstrated extremely high accuracy in discriminating actual fires from false alarm sources. In fact, this technology promises to virtually eliminate false activations. This detector could be used to monitor fueling facilities, launch towers, clean rooms, and other high-value and high-risk areas. Applications can extend to space station and in-flight shuttle operations as well; fiber optics and remote camera heads enable the system to see around obstructed areas and crew compartments. The capability of the technology to distinguish fires means that fire detection can be provided even during maintenance operations, such as welding.

  19. 49 CFR 193.2801 - Fire protection.

    Science.gov (United States)

    2010-10-01

    ... 49 Transportation 3 2010-10-01 2010-10-01 false Fire protection. 193.2801 Section 193.2801...: FEDERAL SAFETY STANDARDS Fire Protection § 193.2801 Fire protection. Each operator must provide and maintain fire protection at LNG plants according to sections 9.1 through 9.7 and section 9.9 of NFPA 59A...

  20. Fire Protection Informational Exchange

    Science.gov (United States)

    2016-07-01

    durable and launderable. A summary of contractor lead efforts to achieve these goals was presented. 3.19 US Naval Air Systems Command The NAVAIR fire... contractors spoke next concerning their companies’ technologies for fuel fire mitigation. Randy Fontinakes from Meggitt summarized his company’s products...decomprHalon FUS~ ht Surgeon’a Manual, USN: 0 Mdentlry, rapid d.eC)mpt"tMion • moct.rate .ctfvtty, rapkl decomprualon c: 0 Ill 5 1000 +- ph~lo4oglcal

  1. Report on task I: fire protection system study

    International Nuclear Information System (INIS)

    Bernard, E.A.; Cano, G.L.

    1977-02-01

    This study (1) evaluates, on a comparative basis, the national and international regulatory and insurance standards that serve as guidance for fire protection within the nuclear power industry; (2) analyzes the recommendations contained in the major reports on the Browns Ferry Fire; (3) proposes quantitative safety goals and evaluation methods for Nuclear Power Plant Fire Protection Systems (NPPFPS); (4) identifies potential improvements that may be incorporated into NPPFPS; and (5) recommends a plan of action for continuation of the fire protections systems study

  2. Fire protection in nuclear power plants

    International Nuclear Information System (INIS)

    1979-01-01

    The Safety Guide gives design and some operational guidance for protection from fire and fire-related explosions in nuclear power plants (NPP). It confines itself to fire protection of items important to safety, leaving the aspects of fire protection not related to safety in NPP to be decided upon the basis of the national practices and regulations

  3. 29 CFR 1926.150 - Fire protection.

    Science.gov (United States)

    2010-07-01

    ... 29 Labor 8 2010-07-01 2010-07-01 false Fire protection. 1926.150 Section 1926.150 Labor... (CONTINUED) SAFETY AND HEALTH REGULATIONS FOR CONSTRUCTION Fire Protection and Prevention § 1926.150 Fire protection. (a) General requirements. (1) The employer shall be responsible for the development of a fire...

  4. Fire protection maintenance at Browns Ferry Nuclear Plant

    International Nuclear Information System (INIS)

    Kern, J.R.

    1989-01-01

    This paper describes two approaches to staffing and organizing a fire protection maintenance group. Both have been used at Browns Ferry Nuclear Plant. One takes traditional craft functions and relocates them from the plant maintenance department to the fire protection section. The other expands the role to include response to fire, medical, and hazardous material emergencies. Both approaches remove the fire protection supervisor from a purely staff role, and involve him/her in direct-line management functions. This results in improved technical direction to the craftsmen, improved quality of the work performed, and improved craft morale. It also assures the fire protection supervisor of much more detailed knowledge of the overall status of the fire protection systems

  5. The French fire protection concept. Vulnerability analysis

    International Nuclear Information System (INIS)

    Kaercher, M.

    1998-01-01

    The French fire protection concept is based on a principle of three levels of defence in depth: fire prevention, fire containing and fire controlling. Fire prevention is based on arrangements which prevent the fire from starting or which make difficult for the fire to start. Fire containing is based on design measures so that the fire will have no impact on the safety of the installation. For fire controlling, equipment nad personnel are on duty in order to detect, to fight and to gain control over the fire as early as possible. The French fire protection concept gives priority to fire containing based on passive structural measures. All buildings containing safety equipment are divided into fire compartments (or fire areas) and fire cells (or fire zones). Basically, a compartment houses safety equipment belonging to one division (or train) so that the other division is always available to reach the plant safe shut down or to mitigate an accident. Because there is a large number of fire compartments and fire cells, deviations from the general principle can be observed. To this reason the RCC-I (Design and Construction Rules applicable for fire protection) requires to implement an assessment of the principle of division. This assessment is called vulnerability analysis. The vulnerability analysis is usually performed at the end of the project, before erection. It is also possible to perform a vulnerability analysis in an operating nuclear power plant in the scope of a fire safety upgrading programme. In the vulnerability analysis, the functional failure of all the equipment (except for those protected by a qualified fire barrier, designed or able to withstand the fire consequences) within the fire compartment or cell, where the fire breaks out, is postulated. The potential consequences for the plant safety are analysed

  6. 14 CFR 33.17 - Fire protection.

    Science.gov (United States)

    2010-01-01

    ... 14 Aeronautics and Space 1 2010-01-01 2010-01-01 false Fire protection. 33.17 Section 33.17... STANDARDS: AIRCRAFT ENGINES Design and Construction; General § 33.17 Fire protection. (a) The design and... protection unless damage by fire will not cause leakage or spillage of a hazardous quantity of flammable...

  7. 30 CFR 77.306 - Fire protection.

    Science.gov (United States)

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Fire protection. 77.306 Section 77.306 Mineral Resources MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR COAL MINE SAFETY AND HEALTH MANDATORY....306 Fire protection. Based on the need for fire protection measures in connection with the particular...

  8. 46 CFR 176.810 - Fire protection.

    Science.gov (United States)

    2010-10-01

    ... 46 Shipping 7 2010-10-01 2010-10-01 false Fire protection. 176.810 Section 176.810 Shipping COAST...) INSPECTION AND CERTIFICATION Material Inspections § 176.810 Fire protection. (a) At each initial and... and have the vessel ready for inspection of its fire protection equipment, including the following: (1...

  9. Fire protection and fire fighting in nuclear installations

    International Nuclear Information System (INIS)

    1989-01-01

    Fires are a threat to all technical installations. While fire protection has long been a well established conventional discipline, its application to nuclear facilities requires special considerations. Nevertheless, for a long time fire engineering has been somewhat neglected in the design and operation of nuclear installations. In the nuclear industry, the Browns Ferry fire in 1975 brought about an essential change in the attention paid to fire problems. Designers and plant operators, as well as insurance companies and regulators, increased their efforts to develop concepts and methods for reducing fire risks, not only to protect the capital investment in nuclear plants but also to consider the potential secondary effects which could lead to nuclear accidents. Although the number of fires in nuclear installations is still relatively large, their overall importance to the safety of nuclear power plants was not considered to be very high. Only more recently have probabilistic analyses changed this picture. The results may well have to be taken into account more carefully. Various aspects of fire fighting and fire protection were discussed during the Symposium, the first of its kind to be organized by the IAEA. It was convened in co-operation with several organizations working in the nuclear or fire protection fields. The intention was to gather experts from nuclear engineering areas and the conventional fire protection field at one meeting with a view to enhancing the exchange of information and experience and to presenting current knowledge on the various disciplines involved. The presentations at the meeting were subdivided into eight sessions: standards and licensing (6 papers); national fire safety practices (7 papers); fire safety by design (11 papers); fire fighting (2 papers); computer fire modeling (7 papers); fire safety in fuel center facilities (7 papers); fire testing of materials (3 papers); fire risk assessment (5 papers). A separate abstract was

  10. Safety study of fire protection for nuclear fuel cycle facility

    International Nuclear Information System (INIS)

    2013-01-01

    Insufficiencies in the fire protection system of the nuclear reactor facilities were pointed out when the fire occurred due to the Niigata prefecture-Chuetsu-oki Earthquake in July, 2007. This prompted the revision of the fire protection safety examination guideline for nuclear reactors as well as commercial guidelines. The commercial guidelines have been endorsed by the regulatory body. Now commercial fire protection standards for nuclear facilities such as the design guideline and the management guideline for protecting fire in the Light Water Reactors (LWRs) are available, however, those to apply to the nuclear fuel cycle facilities such as mixed oxide fuel fabrication facility (MFFF) have not been established. For the improvement of fire protection system of the nuclear fuel cycle facilities, the development of a standard for the fire protection, corresponding to the commercial standard for LWRs were required. Thus, Japan Nuclear Energy Safety Organization (JNES) formulated a fire protection guidelines for nuclear fuel cycle facilities as a standard relevant to the fire protection of the nuclear fuel cycle facilities considering functions specific to the nuclear fuel cycle facilities. In formulating the guidelines, investigation has been conduced on the commercial guidelines for nuclear reactors in Japan and the standards relevant to the fire protection of nuclear facilities in USA and other countries as well as non-nuclear industrial fire protection standards. The guideline consists of two parts; Equipments and Management, as the commercial guidances of the nuclear reactor. In addition, the acquisition of fire evaluation data for a components (an electric cabinet, cable, oil etc.) targeted for spread of fire and the evaluation model of fire source were continued for the fire hazard analysis (FHA). (author)

  11. Rx fire laws: tools to protect fire: the `ecological imperative?

    Science.gov (United States)

    Dale Wade; Steven Miller; Johnny Stowe; James Brenner

    2006-01-01

    The South is the birthplace of statutes and ordinances that both advocate and protect the cultural heritage of woods burning, which has been practiced in this region uninterrupted for more than 10,000 years. We present a brief overview of fire use in the South and discuss why most southern states recognized early on that periodic fire was necessary to sustain fire...

  12. 49 CFR 193.2611 - Fire protection.

    Science.gov (United States)

    2010-10-01

    ... 49 Transportation 3 2010-10-01 2010-10-01 false Fire protection. 193.2611 Section 193.2611 Transportation Other Regulations Relating to Transportation (Continued) PIPELINE AND HAZARDOUS MATERIALS SAFETY...: FEDERAL SAFETY STANDARDS Maintenance § 193.2611 Fire protection. (a) Maintenance activities on fire...

  13. Improving disaster risk reduction capacity of District Civil Protection Units in managing veld fires: A case of Mangwe District in Matabeleland South Province, Zimbabwe

    Directory of Open Access Journals (Sweden)

    Ernest Dube

    2015-05-01

    Full Text Available This article analysed disaster risk reduction capacity of District Civil Protection Units (DCPUs in managing veld fires in Mangwe District of Matabeleland South Province, Zimbabwe. Veld fires have resulted in unnecessary material, environmental and economic losses. Communities’ livelihoods and property have been destroyed, and the natural environment depleted. The research sought to improve disaster risk reduction capacity of DCPUs in managing veld fires, through new intervention strategies and a new model. The objectives of the study were to investigate the main causes of veld fires; to analyse their impacts; to examine the effectiveness of the current intervention strategies; and to identify challenges in implementing these interventions. Furthermore, the study sought to recommend new possible intervention strategies. This mainly qualitative study employed self-administered questionnaires, interviews and focus-group discussions. Questionnaires were used to investigate members of the DCPU’s ideas, views and experiences, interviews solicited perceptions of community leaders and their subjects, whilst focus-group discussions assisted with information from members of the District Civil Protection Planning Committee. Veld fires in the district are mainly caused by human activities, and they are prevalent during the months of September and October. They affect livelihoods and the natural environment the most. This study found that DCPUs are not prepared to manage veld fires and therefore recommended new strategies and adoption of the community-based disaster risk reduction model. The new strategies include involving community leaders and members of the communities in DCPUs; regular training and workshops to members of DCPUs on veld fire management; creation of fire protection associations; regular campaigns and rehearsal of emergency drills by the DCPU personnel; the introduction of competitions and incentives in veld fire management; vigorous

  14. DOE Standard: Fire protection design criteria

    International Nuclear Information System (INIS)

    1999-07-01

    The development of this Standard reflects the fact that national consensus standards and other design criteria do not comprehensively or, in some cases, adequately address fire protection issues at DOE facilities. This Standard provides supplemental fire protection guidance applicable to the design and construction of DOE facilities and site features (such as water distribution systems) that are also provided for fire protection. It is intended to be used in conjunction with the applicable building code, National Fire Protection Association (NFPA) Codes and Standards, and any other applicable DOE construction criteria. This Standard replaces certain mandatory fire protection requirements that were formerly in DOE 5480.7A, ''Fire Protection'', and DOE 6430.1A, ''General Design Criteria''. It also contains the fire protection guidelines from two (now canceled) draft standards: ''Glove Box Fire Protection'' and ''Filter Plenum Fire Protection''. (Note: This Standard does not supersede the requirements of DOE 5480.7A and DOE 6430.1A where these DOE Orders are currently applicable under existing contracts.) This Standard, along with the criteria delineated in Section 3, constitutes the basic criteria for satisfying DOE fire and life safety objectives for the design and construction or renovation of DOE facilities

  15. Aging assessment for active fire protection systems

    International Nuclear Information System (INIS)

    Ross, S.B.; Nowlen, S.P.; Tanaka, T.

    1995-06-01

    This study assessed the impact of aging on the performance and reliability of active fire protection systems including both fixed fire suppression and fixed fire detection systems. The experience base shows that most nuclear power plants have an aggressive maintenance and testing program and are finding degraded fire protection system components before a failure occurs. Also, from the data reviewed it is clear that the risk impact of fire protection system aging is low. However, it is assumed that a more aggressive maintenance and testing program involving preventive diagnostics may reduce the risk impact even further

  16. Fire protection at nuclear power plants

    International Nuclear Information System (INIS)

    1999-11-01

    The guide presents specific requirements for the design and implementation of fire protection arrangements at nuclear power plants and for the documents relating to the fire protection that are to be submitted to STUK (Finnish Radiation and Nuclear Safety Authority). Inspections of the fire protection arrangements to be conducted by STUK during the construction and operation of the power plants are also described in this guide. The guide can also be followed at other nuclear facilities

  17. Fire prevention and protection for trackless equipment

    Energy Technology Data Exchange (ETDEWEB)

    Burger, A.J.

    1988-10-01

    With the increased use of trackless diesel and electrical equipment underground, the fire danger associated with this equipment has increased. The need for adequate fire prevention and protection on all aspects of trackless mechanised mining must be taken into consideration. This paper describes briefly the causes of fires on trackless equipment and the precautions taken to reduce the risk of ignition. 1 tab.

  18. SFPE handbook of fire protection engineering

    CERN Document Server

    Gottuk, Daniel; Jr, John; Harada, Kazunori; Kuligowski, Erica; Puchovsky, Milosh; Torero, Jose´; Jr, John; WIECZOREK, CHRISTOPHER

    2016-01-01

    Revised and significantly expanded, the fifth edition of this classic work offers both new and substantially updated information. As the definitive reference on fire protection engineering, this book provides thorough treatment of the current best practices in fire protection engineering and performance-based fire safety. Over 130 eminent fire engineers and researchers contributed chapters to the book, representing universities and professional organizations around the world. It remains the indispensible source for reliable coverage of fire safety engineering fundamentals, fire dynamics, hazard calculations, fire risk analysis, modeling and more. With seventeen new chapters and over 1,800 figures, the this new edition contains: • Step-by-step equations that explain engineering calculations • Comprehensive revision of the coverage of human behavior in fire, including several new chapters on egress system design, occupant evacuation scenarios, combustion toxicity and data for human behavior analysis • Rev...

  19. Fire protection guidelines for nuclear power plants

    International Nuclear Information System (INIS)

    1976-06-01

    Guidelines acceptable to the NRC staff for implementing in the development of a fire protection program for nuclear power plants. The purpose of the fire protection program is to ensure the capability to shut down the reactor and maintain it in a safe shutdown condition and to minimize radioactive releases to the environment in the event of a fire. If designs or methods different from the guidelines presented herein are used, they must provide fire protection comparable to that recommended in the guidelines. Suitable bases and justification should be provided for alternative approaches to establish acceptable implementaion of General Design Criterion 3

  20. 10 CFR 36.27 - Fire protection.

    Science.gov (United States)

    2010-01-01

    ... 10 Energy 1 2010-01-01 2010-01-01 false Fire protection. 36.27 Section 36.27 Energy NUCLEAR REGULATORY COMMISSION LICENSES AND RADIATION SAFETY REQUIREMENTS FOR IRRADIATORS Design and Performance Requirements for Irradiators § 36.27 Fire protection. (a) The radiation room at a panoramic irradiator must...

  1. 46 CFR 169.311 - Fire protection.

    Science.gov (United States)

    2010-10-01

    ... 46 Shipping 7 2010-10-01 2010-10-01 false Fire protection. 169.311 Section 169.311 Shipping COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED) NAUTICAL SCHOOLS SAILING SCHOOL VESSELS Construction and Arrangement Hull Structure § 169.311 Fire protection. (a) The general construction of the vessel...

  2. PG BN 1600 sodium fire protection system

    International Nuclear Information System (INIS)

    Bar, J.; Urbancik, L.

    1978-12-01

    A design was developed of a fire protection system for steam generator of a 1600 MW sodium cooled fast reactor (BN-1600). Chemical reactions are described of liquid sodium with atmospheric components and solid materials coming into contact with sodium in its release from the steam generator, and in safeguarding protection against sodium fires. The requirements for the purity of nitrogen as an atmosphere inert to liquid sodium are given. Characteristics and basic parameters are shown of level and spray fires, elementary terms are explained concerning the properties of aerosols formed during fires, the methods and means of release signalling and fire alarm are described as are fire precautions using fire-fighting equipment, modifying the support tank and the cell bottom and building sewage pits. The design of the system comprises an alarm system for liquid sodium using point and line electric contact sensors and flame photometer based aerosol sensors as well as a fire-fighting system based on the system of channelling liquid sodium into emergency discharge tanks filled with an inert gas, a set of fire extinguishers and other fire fighting material, and measures for the elimination of sodium fire consequences. (J.B.)

  3. Fire protection for telecommunications central offices

    International Nuclear Information System (INIS)

    McKenna, L.A. Jr.

    1990-01-01

    The provision of continuous, uninterrupted telecommunications service is vital to modern life. In order to provide uninterrupted service to customers, a service continuity program has been in place with AT and T for many years. This program integrates many different protection strategies and plans, each designed to mitigate one of the many threats to service continuity. The fire protection program implemented within AT and T is a part of this service continuity program. In the design of this program, a number of unusual problems had to be addressed due to the service continuity requirements. Typical solutions to fire protection problems (ignition prevention, detection, and suppression) which are embodied in building and fire prevention codes are inadequate to provide service continuity. This presentation outlines the basic arrangement of a telecommunications central office, the specific fire protection problems encountered, the fire protection philosophy developed through the use of a systems approach, and the implementation of the fire protection program. Special emphasis is placed on the strategies employed in lieu of more traditional fire protection schemes and the stimuli for selecting them

  4. Solution of Fire Protection in Historic Buildings

    Science.gov (United States)

    Iringová, Agnes; Idunk, Róbert

    2016-12-01

    The paper introduces optimization of the functional use of renovated spaces in historic buildings in terms of fire risk. It brings assessment of fire protection in the folk house Habánsky Dvor, situated in the village of Veľké Leváre, whose function was changed into the museum. It goes into static analysis of existing load-bearing structures and assessment of their fire resistance according to Eurocodes.

  5. Fire protection in power plants

    International Nuclear Information System (INIS)

    Penot, J.

    1986-01-01

    Graphex-CK 23 is a unique sodium fire extinction product. Minimum amounts of powder are required for very fast action. The sodium can be put to use again, when the fire has been extinguished. It can be applied in other industrial branches and with other metals, e.g. sodium/potassium circuits or lithium coolant in power plants. [de

  6. Fire protection concept for power stations

    International Nuclear Information System (INIS)

    Zitzmann, H.

    The author shows how a systematic approach permits the design of a fire-protected power station. The special conditions of an individual power station are here treated as marginal conditions. The article describes how the concept is realized in the completed power station, taking account of the information provided by fire statistics. (orig.) [de

  7. Fire Resistance Tests of Various Fire Protective Coatings

    Directory of Open Access Journals (Sweden)

    Mindaugas GRIGONIS

    2011-03-01

    Full Text Available Tests were carried out on more than 14 different samples of fire protective coatings in order to investigate a relation between the thickness of the intumescent fire protection coating and the time of exposure to heat. A number of coatings of different chemical composition enabled to determine the fire resistance behaviour patterns. During test the one-side and volumetric methods were employed in observance of the standard temperature-time curves. For one-side method, the coating was applied on one side and all edges of the specimen, whereas for volumetric test the specimens were completely covered with fire protective coating. It is shown that a layer of coating protects the specimen's surface from heat exposure for a certain period of time until full oxidation of the coating occurs. The efficiency of fire protective coatings also depends on thickness of the charred layer of the side exposed to heat.http://dx.doi.org/10.5755/j01.ms.17.1.257

  8. Quality assurance through fire protection documentation

    Energy Technology Data Exchange (ETDEWEB)

    Spitzer, Franz [KAEFER Industrie GmbH, Kirchheim (Germany); Winter, Harald [Harald Winter Software, Unterschleissheim (Germany)

    2010-07-01

    Legal and organisational requirements regarding fire protection have become more and more stringent. In doing so owners must take account of public law and insurance law. A specialised fire protection management system - FiProMan - can assist in meeting these requirements quickly and efficiently by ensuring quality, carrying out subsequent installation work, repair work and making maintenance planable. In addition, the legal requirements of continuance are met. (orig.)

  9. Stochastic representation of fire behavior in a wildland fire protection planning model for California.

    Science.gov (United States)

    J. Keith Gilless; Jeremy S. Fried

    1998-01-01

    A fire behavior module was developed for the California Fire Economics Simulator version 2 (CFES2), a stochastic simulation model of initial attack on wildland fire used by the California Department of Forestry and Fire Protection. Fire rate of spread (ROS) and fire dispatch level (FDL) for simulated fires "occurring" on the same day are determined by making...

  10. The importance of verifiable fire protection design

    Energy Technology Data Exchange (ETDEWEB)

    Medonos, Sava [Petrellus Ltd. (United Kingdom)]. E-mail: smm@petrellus.co.uk; Geddes, Paul [Global Solutions UK Ltd. (United Kingdom)]. E-mail: paul@globalsolutionsuk.com

    2004-07-01

    Simplistic methods based on the Hp/A ratio between the heated surface area and volume or a 2-dimensional analysis may be sufficient for the determination of fire protection coatings for simple components. For the optimization of fire protection of pressure systems and load bearing structures, however, they have proved to be inadequate, as they do not represent the response taking place. This often leads to over-protection or inadequate fire resistance. In the past 10 years there have been claims in petrochemical industry of 'methods' for fire protection 'optimization' based on a walk-down through a topside or plant, or a heat-up calculation of a few cross sections with no regard to stress. These methods are wrong. In the best case these 'methods of optimization' lead to high unnecessary costs and in the worst case in an explosion of a vessel, structural collapse, domino effects and cataclysmic fire throughout the plant. The operator or design contractor should always require a Method Statement including a proof of verification to obtain the adequate quality of fire protection. (author)

  11. Integrated approach to fire safety at the Krsko nuclear power plant - fire protection action plan

    International Nuclear Information System (INIS)

    Lambright, J.A.; Cerjak, J.; Spiler, J.; Ioannidi, J.

    1998-01-01

    Nuclear Power Plant Krsko (NPP Krsko) is a Westinghouse design, single-unit, 1882 Megawatt thermal (MWt), two-loop, pressurized water nuclear power plant. The fire protection program at NPP Krsko has been reviewed and reports issued recommending changes and modifications to the program, plant systems and structures. Three reports were issued, the NPP Krsko Fire Hazard Analysis (Safe Shout down Separation Analysis Report), the ICISA Analysis of Core Damage Frequency Due to Fire at the NPP Krsko and IPEEE (Individual Plant External Event Examination) related to fire risk. The Fire Hazard Analysis Report utilizes a compliance - based deterministic approach to identification of fire area hazards. This report focuses on strict compliance from the perspective of US Nuclear Regulatory Commission (USNRC), standards, guidelines and acceptance criteria and does not consider variations to comply with the intent of the regulations. The probabilistic analysis methide used in the ICISA and IPEEE report utilizes a risk based nad intent based approach in determining critical at-risk fire areas. NPP Krsko has already completed the following suggestions/recommendations from the above and OSART reports in order to comply with Appendix R: Installation of smoke detectors in the Control Room; Installation of Emergency Lighting in some plant areas and of Remote Shout down panels; Extension of Sound Power Communication System; Installation of Fire Annunciator Panel at the On-site Fire Brigade Station; Installation of Smoke Detection System in the (a) Main Control Room Panels, (b) Essential Service Water Building. (c) Component Cooling Building pump area, chiller area and HVAC area, (d) Auxiliary Building Safety pump rooms, (e) Fuel Handling room, (f) Intermediate Building AFFW area and compressor room, and (g) Tadwaste building; inclusion of Auxiliary operators in the Fire Brigade; training of Fire Brigade Members in Plant Operation (9 week course); Development of Fire Door Inspection and

  12. Remote sensing evaluation of fire hazard : Towards operational tools for improving the security of citizens and protecting the environment

    NARCIS (Netherlands)

    Maffei, C.; Gambardella, C.; Menenti, M.

    2015-01-01

    Forest fires are a threat for both the environment and the security of citizens. This is particularly relevant in the Mediterranean, where the population density is high, and long dry summers drive vegetation into fireprone conditions. Policy makers underline the key role of prevention over damage

  13. Analysis of fire protection in nuclear power plants

    International Nuclear Information System (INIS)

    Hosser, D.; Schneider, U.

    1982-01-01

    Regulations and test specifications for fire prevention in nuclear power plants are presented as well as the fire protection measures in a newly constructed nuclear power plant. Although the emphasis is placed differently, all rules are based on the following single measures: Fire prevention, fire detection, fire fighting, fire checking, attack, flight, and rescue, organisational measures. (orig./GL) [de

  14. Improvement of fire fighting means for NPPs

    International Nuclear Information System (INIS)

    Viktorov, V.V.

    1993-01-01

    The problems dealing with testing of flame dampers for NPP ventilation systems are considered. The characteristics of the Darmatt fire-resistant material developed for protection of cable lines and equipment against fire effects are given

  15. Fire protection countermeasures for containment ventilation systems

    International Nuclear Information System (INIS)

    Alvares, N.J.; Beason, D.G.; Bergman, W.; Ford, H.W.; Lipska, A.E.

    1980-01-01

    The goal of this project is to find countermeasures to protect HEPA filters in exit ventilation ducts from the heat and smoke generated by fire. Several methods for partially mitigating the smoke exposure to the HEPA filters were identified through testing and analysis. These independently involve controlling the fuel, controlling the fire, and intercepting the smoke aerosol prior to its sorption on the HEPA filter. Exit duct treatment of aerosols is not unusual in industrial applications and involves the use of scrubbers, prefilters, and inertial impaction, depending on the size, distribution, and concentration of the subject aerosol. However, when these unmodified techniques were applied to smoke aerosols from fires on materials, common to experimental laboratories of LLNL, it was found they offered minimal protection to the HEPA filters. Ultimately, a continuous, movable, high-efficiency prefilter using modified commercial equipment was designed. This technique is capable of protecting HEPA filters over the total duration of the test fires. The reason for success involved the modificaton of the prefiltration media. Commercially available filter media has a particle sorption efficiency that is inversely proportional to media strength. To achieve properties of both efficiency and strength, we laminated rolling filter media with the desired properties. It is not true that the use of rolling prefilters solely to protect HEPA filters from fire-generated smoke aerosols is cost effective in every type of containment system, especially if standard fire-protection systems are available in the space. But in areas of high fire risk, where the potential fuel load is large and ignition sources are plentiful, the complication of a rolling prefilter in exit ventilation ducts to protect HEPA filters from smoke aerosols is definitely justified

  16. Training of fire protection personnel in nuclear power plants

    International Nuclear Information System (INIS)

    Blaser, W.

    1980-01-01

    Training of fire protection personnel in nuclear power plants is divided up in three categories: training of fire protection commissioners which is mostly carried out externally; training of fire fighting personnel in the form of basic and repeated training usually by the fire protection commissioner; training of other employers with regard to behaviour in case of fire and during work involving a fire hazard. (orig.) [de

  17. Reliability Based Optimization of Fire Protection

    DEFF Research Database (Denmark)

    Thoft-Christensen, Palle

    fire protection (PFP) of firewalls and structural members. The paper is partly based on research performed within the EU supported research project B/E-4359 "Optimized Fire Safety of Offshore Structures" and partly on research supported by the Danish Technical Research Council (see Thoft-Christensen [1......]). Special emphasis is put on the optimization software developed within the project.......It is well known that fire is one of the major risks of serious damage or total loss of several types of structures such as nuclear installations, buildings, offshore platforms/topsides etc. This paper presents a methodology and software for reliability based optimization of the layout of passive...

  18. Fire protection in ventilation systems and in case of fire operating ventilation systems

    International Nuclear Information System (INIS)

    Zitzelsberger, J.

    1983-01-01

    The fire risks in ventilation systems are discussed. It follows a survey of regulations on fire prevention and fire protection in ventilation systems and smoke and heat exhaust systems applicable to nuclear installations in the Federal Republic of Germany. Fire protection concepts for normal systems and for systems operating also in case of fire will be given. Several structural elements for fire protection in those systems will be illustrated with regard to recent research findings

  19. Development of a risk informed fire protection program

    Energy Technology Data Exchange (ETDEWEB)

    Ribeiro, J.; McDevitt, B.; Sawyer, O.; Volk, M.A.; Drennan, J.; Sweely, C.

    2015-07-01

    Over the past decade, one of the largest challenges for the Nuclear Power Plant (NPP) Operator in the United States has been the implementation of risk-informed, performance-based (RI-PB) fire protection strategies into their fire protection program. Regardless of whether a utility decides to fully transition their licensing basis from deterministic to risk based, or if they simply complete a fire probabilistic risk assessment (FPRA) in order to augment their current program, it is clear that risk-informed, performance based fire protection strategies and the associated challenges are the growing trend in the United States and are here to stay. The experience of the nuclear industry in the United States with the implementation of RI-PB fire protection strategies can provide a great deal of insight for plants and utilities that follow, either by choice or necessity, a similar path. The similarities in the design of the United States and Spanish nuclear plants make these insights even more significant contributions to the strategy and planning for the Spanish fleet. The experience in United States will provide guidance to avoid similar missteps and better plan for the challenges of the transition process. As the Spanish fleet develops risk-informed and deterministic strategies to improve fire safety, an understanding of the challenges and lessons learned from the United States experience will save time and money. (Author)

  20. Fire protection countermeasures for containment ventilation systems

    International Nuclear Information System (INIS)

    Alvares, N.; Beason, D.; Bergman, V.; Creighton, J.; Ford, H.; Lipska, A.

    1980-01-01

    The goal of this project is to find countermeasures to protect High Efficiency Particulate Air (HEPA) filters, in exit ventilation ducts, from the heat and smoke generated by fire. Initially, methods were developed to cool fire-heated air by fine water spray upstream of the filters. It was recognized that smoke aerosol exposure to HEPA filters could also cause disruption of the containment system. Through testing and analysis, several methods to partially mitigate the smoke exposure to the HEPA filters were identified. A continuous, movable, high-efficiency prefilter using modified commercial equipment was designed. The technique is capable of protecting HEPA filters over the total time duration of the test fires. The reason for success involved the modification of the prefiltration media. Commercially available filter media has particle sorption efficiency that is inversely proportional to media strength. To achieve properties of both efficiency and strength, rolling filter media were laminated with the desired properties. The approach was Edisonian, but truncation in short order to a combination of prefilters was effective. The application of this technique was qualified, since it is of use only to protect HEPA filters from fire-generated smoke aerosols. It is not believed that this technique is cost effective in the total spectrum of containment systems, especially if standard fire protection systems are available in the space. But in areas of high-fire risk, where the potential fuel load is large and ignition sources are plentiful, the complication of a rolling prefilter in exit ventilation ducts to protect HEPA filters from smoke aerosols is definitely justified

  1. Fire protection in the nuclear power plant

    International Nuclear Information System (INIS)

    Takuma, Masao

    1977-01-01

    According to the publication by US NRC, 32 fires have occurred in the nuclear power stations in operation, but most of them were small fire, and did not affect the safety of the nuclear power stations. The largest fire was that which occurred in the Browns Ferry Nuclear Power Station of TVA, USA, in March, 1976. It did not jeopardize the safety of the reactor facilities, and the leak of radioactive substance did not occur at all. But the investigation was made extensively by the joint committee of both houses, the government and others, and the deficiency in the countermeasures to fire was found, and it was clarified that some revision would by required on the standard applied heretofore. It was the valuable experience for improving further the safety of nuclear power stations. The fire occurred by the ignition of the polyurethane for sealing cable penetrations due to candle flame for testing. About 1600 cables were burned. When fire breaks out in a nuclear power station, it is necessary to stop and cool the reactor without fail, and to prevent the leak of radioactive substances definitely. In case of the fire in Browns Ferry, these requirements were fulfilled satisfactorily. The countermeasures on the basis of the experience in Browns Ferry and the design of the counterplan to fire in nuclear power stations are explained. (Kako, I.)

  2. Safety study of fire protection for nuclear fuel cycle facility

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2013-08-15

    Based on the investigation of fire protection standards for domestic and foreign nuclear facilities, the fire protection guideline for nuclear fuel cycle facility has been completed. In 2012, trial operation is started by private company using the guideline. In addition, the acquisition of fire evaluation data for a components (electric cable) targeted for spread of fire and the evaluation model of fire source were continued for the fire hazard analysis (FHA). (author)

  3. Safety study of fire protection for nuclear fuel cycle facility

    International Nuclear Information System (INIS)

    2013-01-01

    Based on the investigation of fire protection standards for domestic and foreign nuclear facilities, the fire protection guideline for nuclear fuel cycle facility has been completed. In 2012, trial operation is started by private company using the guideline. In addition, the acquisition of fire evaluation data for a components (electric cable) targeted for spread of fire and the evaluation model of fire source were continued for the fire hazard analysis (FHA). (author)

  4. WASTE HANDLING BUILDING FIRE PROTECTION SYSTEM DESCRIPTION DOCUMENT

    Energy Technology Data Exchange (ETDEWEB)

    J. D. Bigbee

    2000-06-21

    The Waste Handling Building Fire Protection System provides the capability to detect, control, and extinguish fires and/or mitigate explosions throughout the Waste Handling Building (WHB). Fire protection includes appropriate water-based and non-water-based suppression, as appropriate, and includes the distribution and delivery systems for the fire suppression agents. The Waste Handling Building Fire Protection System includes fire or explosion detection panel(s) controlling various detectors, system actuation, annunciators, equipment controls, and signal outputs. The system interfaces with the Waste Handling Building System for mounting of fire protection equipment and components, location of fire suppression equipment, suppression agent runoff, and locating fire rated barriers. The system interfaces with the Waste Handling Building System for adequate drainage and removal capabilities of liquid runoff resulting from fire protection discharges. The system interfaces with the Waste Handling Building Electrical Distribution System for power to operate, and with the Site Fire Protection System for fire protection water supply to automatic sprinklers, standpipes, and hose stations. The system interfaces with the Site Fire Protection System for fire signal transmission outside the WHB as needed to respond to a fire emergency, and with the Waste Handling Building Ventilation System to detect smoke and fire in specific areas, to protect building high-efficiency particulate air (HEPA) filters, and to control portions of the Waste Handling Building Ventilation System for smoke management and manual override capability. The system interfaces with the Monitored Geologic Repository (MGR) Operations Monitoring and Control System for annunciation, and condition status.

  5. WASTE HANDLING BUILDING FIRE PROTECTION SYSTEM DESCRIPTION DOCUMENT

    International Nuclear Information System (INIS)

    J. D. Bigbee

    2000-01-01

    The Waste Handling Building Fire Protection System provides the capability to detect, control, and extinguish fires and/or mitigate explosions throughout the Waste Handling Building (WHB). Fire protection includes appropriate water-based and non-water-based suppression, as appropriate, and includes the distribution and delivery systems for the fire suppression agents. The Waste Handling Building Fire Protection System includes fire or explosion detection panel(s) controlling various detectors, system actuation, annunciators, equipment controls, and signal outputs. The system interfaces with the Waste Handling Building System for mounting of fire protection equipment and components, location of fire suppression equipment, suppression agent runoff, and locating fire rated barriers. The system interfaces with the Waste Handling Building System for adequate drainage and removal capabilities of liquid runoff resulting from fire protection discharges. The system interfaces with the Waste Handling Building Electrical Distribution System for power to operate, and with the Site Fire Protection System for fire protection water supply to automatic sprinklers, standpipes, and hose stations. The system interfaces with the Site Fire Protection System for fire signal transmission outside the WHB as needed to respond to a fire emergency, and with the Waste Handling Building Ventilation System to detect smoke and fire in specific areas, to protect building high-efficiency particulate air (HEPA) filters, and to control portions of the Waste Handling Building Ventilation System for smoke management and manual override capability. The system interfaces with the Monitored Geologic Repository (MGR) Operations Monitoring and Control System for annunciation, and condition status

  6. Upgrading of fire protection arrangements at Magnox power stations in the United Kingdom

    International Nuclear Information System (INIS)

    Zhu, L.H.

    1998-01-01

    The methodology used in conducting fire hazard assessments at Magnox Reactor power stations operated by Magnox Electric plc is described. The assessments use a deterministic approach. This includes the identification of essential plant and the associated supporting systems required for the safe trip, shutdown and post-trip cooling of the reactor, assessment of the location of the essential plant and the vulnerability of these plant in the presence of a fire, assessment of essential functions against the effects of a fire and identification of improvements to the fire protection arrangements. Practical aspects of fire protection engineering on operating power stations are discussed and examples of improvements in protection described. (author)

  7. Fire protection in nuclear power plants

    International Nuclear Information System (INIS)

    1992-01-01

    The Code on Design (Safety Series 50-C-D (Rev. 1)) within the NUSS (Nuclear Safety Standards) programme of the IAEA points out the necessity of measures for protecting plant items which are important to safety against fires of internal and external origin. Experience of the past two decades in the operation of nuclear power plants and modern analysis techniques confirm that fire may be a real threat to nuclear safety and should receive adequate attention from the beginning of the design process throughout the life of the plant. Within the framework of the NUSS programme, a Safety Guide on fire protection had therefore been developed to enlarge on the general requirements given in the Code. Since its first publication in 1979, there has been considerable development in protection technology and analysis methods and after the Chernobyl accident it was decided to revise the existing Guide. The present Safety Guide is intended to advise designers, safety assessors and regulators on the concept of fire protection in the design of nuclear power plants and on recommended ways of implementing the concept in some detail in practice. Figs, 1 tab

  8. DOE Fire Protection Handbook, Volume I

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1996-08-01

    The Department of Energy (DOE) Fire Protection Program is delineated in a number of source documents including; the Code of Federal Regulations (CFR), DOE Policy Statements and Orders, DOE and national consensus standards (such as those promulgated by the National Fire Protection Association), and supplementary guidance, This Handbook is intended to bring together in one location as much of this material as possible to facilitate understanding and ease of use. The applicability of any of these directives to individual Maintenance and Operating Contractors or to given facilities and operations is governed by existing contracts. Questions regarding applicability should be directed to the DOE Authority Having Jurisdiction for fire safety. The information provided within includes copies of those DOE directives that are directly applicable to the implementation of a comprehensive fire protection program. They are delineated in the Table of Contents. The items marked with an asterisk (*) are included on the disks in WordPerfect 5.1 format, with the filename noted below. The items marked with double asterisks are provided as hard copies as well as on the disk. For those using MAC disks, the files are in Wordperfect 2.1 for MAC.

  9. Seismic design criteria of fire protection systems for DOE facilities

    International Nuclear Information System (INIS)

    Hardy, G.; Cushing, R.; Driesen, G.

    1991-01-01

    Fire protection systems are critical to the safety of personnel and to the protection of inventory during any kind of emergency situation that involves a fire. The importance of these fire protection systems is hightened for DOE facilities which often house nuclear, chemical or scientific processes. Current research into the topic of open-quotes fires following earthquakesclose quotes has demonstrated that the risks of a fire starting as a result of a major earthquake can be significant. Thus, fire protection systems need to be designed to withstand the anticipated seismic event for the site in question

  10. 29 CFR Appendix A to Subpart L of... - Fire Protection

    Science.gov (United States)

    2010-07-01

    ... dioxide, or dry chemical. Combustible metal (Class D hazards) fires pose a different type of fire problem... control this type of fire. Therefore, certain metals have specific dry powder extinguishing agents which... use on certain metal fires provide the best protection; however, there are also some “universal” type...

  11. 46 CFR 194.15-7 - Fire protection.

    Science.gov (United States)

    2010-10-01

    ... 46 Shipping 7 2010-10-01 2010-10-01 false Fire protection. 194.15-7 Section 194.15-7 Shipping COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED) OCEANOGRAPHIC RESEARCH VESSELS HANDLING, USE... § 194.15-7 Fire protection. (a) If a fixed or semiportable fire-fighting system is installed, it shall...

  12. Basing of a complex design measures for protection against fire

    International Nuclear Information System (INIS)

    Kryuger, V.

    1983-01-01

    Fire impact on NPP radiation safety is analyzed. The general industry requirements to the protection system against fire are shown to be insufficient for NPPs. A complex of protection measures against fire is suggested that should be taken into account in the NPP designs [ru

  13. Particular features of fire protection in nuclear power plants

    International Nuclear Information System (INIS)

    Krueger, W.

    1985-01-01

    The particular features of fire protection in nuclear power plants that are connected with the need to ensure nuclear and radiation safety even during an emergency are outlined followed by the recommendation to lay them down in special fire protection standards. These, in conjunction with comprehensive fire hazard analyses, could serve to work out complex concepts for the fire protection of individual nuclear power plants. Such concepts would be very useful for review and assessment of the fire protection design during the licensing process and for later inspections. (author)

  14. Applications of Living Fire PRA models to Fire Protection Significance Determination Process in Taiwan

    International Nuclear Information System (INIS)

    De-Cheng, Chen; Chung-Kung, Lo; Tsu-Jen, Lin; Ching-Hui, Wu; Lin, James C.

    2004-01-01

    The living fire probabilistic risk assessment (PRA) models for all three operating nuclear power plants (NPPs) in Taiwan had been established in December 2000. In that study, a scenario-based PRA approach was adopted to systematically evaluate the fire and smoke hazards and associated risks. Using these fire PRA models developed, a risk-informed application project had also been completed in December 2002 for the evaluation of cable-tray fire-barrier wrapping exemption. This paper presents a new application of the fire PRA models to fire protection issues using the fire protection significance determination process (FP SDP). The fire protection issues studied may involve the selection of appropriate compensatory measures during the period when an automatic fire detection or suppression system in a safety-related fire zone becomes inoperable. The compensatory measure can either be a 24-hour fire watch or an hourly fire patrol. The living fire PRA models were used to estimate the increase in risk associated with the fire protection issue in terms of changes in core damage frequency (CDF) and large early release frequency (LERF). In compliance with SDP at-power and the acceptance guidelines specified in RG 1.174, the fire protection issues in question can be grouped into four categories; red, yellow, white and green, in accordance with the guidelines developed for FD SDP. A 24-hour fire watch is suggested only required for the yellow condition, while an hourly fire patrol may be adopted for the white condition. More limiting requirement is suggested for the red condition, but no special consideration is needed for the green condition. For the calculation of risk measures, risk impacts from any additional fire scenarios that may have been introduced, as well as more severe initiating events and fire damages that may accompany the fire protection issue should be considered carefully. Examples are presented in this paper to illustrate the evaluation process. (authors)

  15. Regulatory point of view on defense in depth approach to fire protection in nuclear power plant

    Energy Technology Data Exchange (ETDEWEB)

    Rinta-Filppula, Samu; Lehto, Matti; Vaelikangas, Pekka [Radiation and Nuclear Safety Authority STUK, Helsinki (Finland)

    2015-12-15

    The defense-in-depth (DiD) principle is a relatively new approach to fire protection design, even though DiD has been used in nuclear power plant (NPP) safety evaluation and design for decades (IAEA 75-INSAG-3, Rev. 1/INSAG-12). It is the main design criterion in fire protection in the latest edition of Finnish Radiation and Nuclear Safety Authority (STUK) issued guide YVL B.8 for the fire protection in nuclear facilities. The DiD approach to fire protection consists of four levels of defense: preventing the ignition of fires, detecting and extinguishing of ignited fires, preventing fire growth and spreading, confining the fire so that safety functions can be performed irrespective of the effects of the fire. The design of fire protection should take all these levels into account so that fire protection is well balanced and not dependent on a single fire protection factor or level of DiD. Despite being central to the design of fire protection, corresponding evaluations of DiD are done according to more or less unambiguous methods. The main goal of this study is to start the development of such, as much as possible, unambiguous systematic and logical method. First issue then is to build a picture of how fire safety features are executed on different levels of DiD and what is the corresponding safety importance to NPP. The Loviisa NPP was studied as an example case due to a long history of fire safety improvements since commissioning in 1977. The improvements are sorted qualitatively by their means of fire safety impact and level of DiD approach to fire protection and general plant DiD. The correspondence between the two DiD principles is an interesting issue which is discussed in this paper. Finally, Fire PRA is used to determine the safety importance of the improvements. The method proposed for the evaluation of DiD approach to fire protection is a combined ignition root cause analysis - event tree of fire scenario - consequential failure modes and effects analysis

  16. Chemical Solutions of Fire Protection Problems

    Directory of Open Access Journals (Sweden)

    Vakhitova, L.M.

    2015-11-01

    Full Text Available The modern approaches to the creation of fire protective coatings by modifying intumescent systems by nanomaterials with study of the chemical reaction mechanisms under the high temperatures influence were considered. A systematic study of the interactions of components of polyphosphate type intumescent blend were carried out, a well-defined correlations between the directions of chemical processes and fire retardant properties of intumescent coatings were found. Efficient ways to simultaneous increase of fireprotective efficiency and performance characteristics of intumescent coatings (operatin life, resistance to environmental factors and bioсontamination were proposed. The results of fundamental research allowed to develop new formulations of flame retardant compositions, whose properties have been confirmed by tests in accordance with existing standardized methods, these results were introduced into production.

  17. Safety design guides for fire protection for CANDU 9

    International Nuclear Information System (INIS)

    Lee, Duk Su; Chang, Woo Hyun; Lee, Nam Young; A. C. D. Wright

    1996-03-01

    This safety design guide establishes design requirements to ensure the radiological risk to the public due to fire is acceptable and operating personnel are adequately protected from the hazards of fires. This safety design guide also specifies the safety criteria for fire protection to be applied to mitigate fires and recommends the fire protection program to be established to initiate, coordinate and document the design activities associated with fire protection. The requirements for fire protection outlined in this safety design guide shall be satisfied in the design stage and the change status of the regulatory requirements, code and standards should be traced and incorporated into this safety design guide accordingly. 1 fig., (Author) .new

  18. Incineration process fire and explosion protection

    International Nuclear Information System (INIS)

    Ziegler, D.L.

    1975-01-01

    Two incinerators will be installed in the plutonium recovery facility under construction at the Rocky Flats Plant. The fire and explosion protection features designed into the incineration facility are discussed as well as the nuclear safety and radioactive material containment features. Even though the incinerator system will be tied into an emergency power generation system, a potential hazard is associated with a 60-second delay in obtaining emergency power from a gas turbine driven generator. This hazard is eliminated by the use of steam jet ejectors to provide normal gas flow through the incinerator system during the 60 s power interruption. (U.S.)

  19. National and international standards and recommendations on fire protection and fire safety assessment

    International Nuclear Information System (INIS)

    Berg, H.P.

    2007-01-01

    Experience feedback from events in nuclear facilities worldwide has shown that fire can represent a safety significant hazard. Thus, the primary objectives of fire protection programmes are to minimize both the probability of occurrence and the consequences of a fire. The regulator body expects that the licensees justify their arrangements for identifying how fires can occur and spread, assess the vulnerability of plant equipment and structures, determine how the safe operation of a plant is affected, and introduce measures to prevent a fire hazard from developing and propagating as well as to mitigate its effects in case the fire cannot be prevented. For that purpose usually a comprehensive regulatory framework for fire protection has been elaborated, based on national industrial regulations, nuclear specific regulations as well as international recommendations or requirements. Examples of such national and international standards and recommendations on fire protection and fire safety assessment as well as ongoing activities in this field are described. (orig.)

  20. Development of a Smart Residential Fire Protection System

    Directory of Open Access Journals (Sweden)

    Juhwan Oh

    2013-01-01

    Full Text Available Embedded system is applied for the development of smart residential fire detection and extinguishing system. Wireless communication capability is integrated into various fire sensors and alarm devices. The system activates the fire alarm to warn occupants, executes emergency and rescue calls to remote residents and fire-fighting facility in an intelligent way. The effective location of extra-sprinklers within the space of interest for the fire extinguishing system is also investigated. Actual fire test suggests that the developed wireless system for the smart residential fire protection system is reliable in terms of sensors and their communication linkage.

  1. Intelligent buildings, automatic fire alarm and fire-protection control system

    International Nuclear Information System (INIS)

    Tian Deyuan

    1999-01-01

    The author describes in brief the intelligent buildings, and the automatic fire alarm and fire-protection control system. On the basis of the four-bus, three-bus and two-bus, a new transfer technique was developed

  2. Fire fighting at Chernobyl and fire protection at UK nuclear power stations

    International Nuclear Information System (INIS)

    Bindon, F.J.L.

    1987-01-01

    The fire fighting measures undertaken by the fire crews at the Chernobyl reactor accident are described. This information highlights the need to develop engineering equipment which will give a far greater degree of personnel protection to fire crews and others in radiological accidents. The British position on fire protection at nuclear power stations is outlined. The general levels of radiation exposure which would be used as a guide to persons in the vicinity of a radiation accident are also given. (UK)

  3. EFFICIENCY OF FIRE-FIGHTING PROTECTION OBJECTS IN PROVISION OF FIRE SAFETY AT INDUSTRIAL ENTERPRISES

    OpenAIRE

    A. V. Zhovna

    2008-01-01

    The paper gives an analysis of economic results pertaining to organization of a system for fire-fighting protection of industrial enterprises in theRepublicofBelarus. Statistical data on operational conditions of technical means of fire-fighting protection, particularly, automatic systems for detection and extinguishing of fires, systems of internal fire-fighting water-supply.  Requirements and provisions  of normative and technical documents are thoroughly studied. Observance of these docume...

  4. 46 CFR 194.20-7 - Fire protection.

    Science.gov (United States)

    2010-10-01

    ... 46 Shipping 7 2010-10-01 2010-10-01 false Fire protection. 194.20-7 Section 194.20-7 Shipping COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED) OCEANOGRAPHIC RESEARCH VESSELS HANDLING, USE... Fire protection. (a) Each chemical storeroom shall be protected by a fixed automatic carbon dioxide...

  5. 46 CFR 153.460 - Fire protection systems.

    Science.gov (United States)

    2010-10-01

    ... 46 Shipping 5 2010-10-01 2010-10-01 false Fire protection systems. 153.460 Section 153.460... Requirements for Flammable Or Combustible Cargoes § 153.460 Fire protection systems. Each self-propelled ship... protection system listed beside the cargo in Table 1 and described in the footnotes to Table 1. (b) The...

  6. Modern tools to evaluate and optimize fire protection systems

    International Nuclear Information System (INIS)

    Alvares, N.J.; Hasegawa, H.K.

    1980-01-01

    Modern techniques, such as fault tree analysis, can be used to obtain engineering descriptions of specific fire protection systems. The analysis allows establishment of an optimum level of fire protection, and evaluates the level of protection provided by various systems. A prime example: the application to fusion energy experiments

  7. Fire protection at the Mochovce nuclear power plant

    International Nuclear Information System (INIS)

    Molnarova, Zuzana; Zeman, Peter

    2009-01-01

    A succinct account is given of current situation in fire prevention at the Mochovce NPP and of past fire events. The fact is stressed that no fire ever occurred at any technological facility of the plant since the startup of the reactor units. Steps required to improve fire safety at a nuclear power plant are highlighted. (orig.)

  8. General fire protection guidelines for egyptian nuclear facilities. Vol. 4

    Energy Technology Data Exchange (ETDEWEB)

    Radhad, S; Hussien, A Z; Hammad, F H [National Center for Nuclear Safety and Radiation Control, Atomic Energy Authority, Cairo (Egypt)

    1996-03-01

    The purpose of this paper is to establish the regulatory requirements of that will provide and ensure fire protection of egyptian nuclear facilities. Those facilities that use, handle and store low and/or medium radioactive substances are included. Two or more classes of occupancy are considered to occur in the same building or structure. Fir protection measures and systems were reviewed for three of the egyptian Nuclear facilities. These are egypt first nuclear reactor (ETRR-1) building and systems, hot laboratories buildings and facilities, and the building including the AECL type Is-6500 industrial cobalt-60 gamma irradiator {sup E}gypt`s mega gamma I{sup .} The study includes the outlines of the various aspects of fire protection with a view to define the relevant highlights and scope of egyptian guideline for nuclear installations. The study considers fire protection aspects including the following items: 1- Site selection. 2- General facility design. 3- Fire alarm, detection and suppression systems. (4- Protection for specific areas/control room, cable spreading room, computer room) 5- Fire emergency response planning. 6- Fire water supply. 7- Emergency lighting and communication. 8- Rescue and escape routes. 9- Explosion protection. 10-Manual fire fighting. 11- Security consideration in the interest of fire protection. 12- quality assurance programme. Therefore, first of all the design stage, then during the construction stage, and later during the operation stage, measures must be taken to forestall the risks associated with the outbreak of fire and to ensure that consequences of fire accidents remain limited.

  9. General fire protection guidelines for egyptian nuclear facilities. Vol. 4

    International Nuclear Information System (INIS)

    Radhad, S.; Hussien, A.Z.; Hammad, F.H.

    1996-01-01

    The purpose of this paper is to establish the regulatory requirements of that will provide and ensure fire protection of egyptian nuclear facilities. Those facilities that use, handle and store low and/or medium radioactive substances are included. Two or more classes of occupancy are considered to occur in the same building or structure. Fir protection measures and systems were reviewed for three of the egyptian Nuclear facilities. These are egypt first nuclear reactor (ETRR-1) building and systems, hot laboratories buildings and facilities, and the building including the AECL type Is-6500 industrial cobalt-60 gamma irradiator E gypt's mega gamma I . The study includes the outlines of the various aspects of fire protection with a view to define the relevant highlights and scope of egyptian guideline for nuclear installations. The study considers fire protection aspects including the following items: 1- Site selection. 2- General facility design. 3- Fire alarm, detection and suppression systems. 4- Protection for specific areas/control room, cable spreading room, computer room) 5- Fire emergency response planning. 6- Fire water supply. 7- Emergency lighting and communication. 8- Rescue and escape routes. 9- Explosion protection. 10-Manual fire fighting. 11- Security consideration in the interest of fire protection. 12- quality assurance programme. Therefore, first of all the design stage, then during the construction stage, and later during the operation stage, measures must be taken to forestall the risks associated with the outbreak of fire and to ensure that consequences of fire accidents remain limited

  10. Factors Controlling Vegetation Fires in Protected and Non-Protected Areas of Myanmar

    Science.gov (United States)

    Biswas, Sumalika; Vadrevu, Krishna Prasad; Lwin, Zin Mar; Lasko, Kristofer; Justice, Christopher O.

    2015-01-01

    Fire is an important disturbance agent in Myanmar impacting several ecosystems. In this study, we quantify the factors impacting vegetation fires in protected and non-protected areas of Myanmar. Satellite datasets in conjunction with biophysical and anthropogenic factors were used in a spatial framework to map the causative factors of fires. Specifically, we used the frequency ratio method to assess the contribution of each causative factor to overall fire susceptibility at a 1km scale. Results suggested the mean fire density in non-protected areas was two times higher than the protected areas. Fire-land cover partition analysis suggested dominant fire occurrences in the savannas (protected areas) and woody savannas (non-protected areas). The five major fire causative factors in protected areas in descending order include population density, land cover, tree cover percent, travel time from nearest city and temperature. In contrast, the causative factors in non-protected areas were population density, tree cover percent, travel time from nearest city, temperature and elevation. The fire susceptibility analysis showed distinct spatial patterns with central Myanmar as a hot spot of vegetation fires. Results from propensity score matching suggested that forests within protected areas have 11% less fires than non-protected areas. Overall, our results identify important causative factors of fire useful to address broad scale fire risk concerns at a landscape scale in Myanmar. PMID:25909632

  11. Factors controlling vegetation fires in protected and non-protected areas of myanmar.

    Directory of Open Access Journals (Sweden)

    Sumalika Biswas

    Full Text Available Fire is an important disturbance agent in Myanmar impacting several ecosystems. In this study, we quantify the factors impacting vegetation fires in protected and non-protected areas of Myanmar. Satellite datasets in conjunction with biophysical and anthropogenic factors were used in a spatial framework to map the causative factors of fires. Specifically, we used the frequency ratio method to assess the contribution of each causative factor to overall fire susceptibility at a 1km scale. Results suggested the mean fire density in non-protected areas was two times higher than the protected areas. Fire-land cover partition analysis suggested dominant fire occurrences in the savannas (protected areas and woody savannas (non-protected areas. The five major fire causative factors in protected areas in descending order include population density, land cover, tree cover percent, travel time from nearest city and temperature. In contrast, the causative factors in non-protected areas were population density, tree cover percent, travel time from nearest city, temperature and elevation. The fire susceptibility analysis showed distinct spatial patterns with central Myanmar as a hot spot of vegetation fires. Results from propensity score matching suggested that forests within protected areas have 11% less fires than non-protected areas. Overall, our results identify important causative factors of fire useful to address broad scale fire risk concerns at a landscape scale in Myanmar.

  12. Factors controlling vegetation fires in protected and non-protected areas of myanmar.

    Science.gov (United States)

    Biswas, Sumalika; Vadrevu, Krishna Prasad; Lwin, Zin Mar; Lasko, Kristofer; Justice, Christopher O

    2015-01-01

    Fire is an important disturbance agent in Myanmar impacting several ecosystems. In this study, we quantify the factors impacting vegetation fires in protected and non-protected areas of Myanmar. Satellite datasets in conjunction with biophysical and anthropogenic factors were used in a spatial framework to map the causative factors of fires. Specifically, we used the frequency ratio method to assess the contribution of each causative factor to overall fire susceptibility at a 1km scale. Results suggested the mean fire density in non-protected areas was two times higher than the protected areas. Fire-land cover partition analysis suggested dominant fire occurrences in the savannas (protected areas) and woody savannas (non-protected areas). The five major fire causative factors in protected areas in descending order include population density, land cover, tree cover percent, travel time from nearest city and temperature. In contrast, the causative factors in non-protected areas were population density, tree cover percent, travel time from nearest city, temperature and elevation. The fire susceptibility analysis showed distinct spatial patterns with central Myanmar as a hot spot of vegetation fires. Results from propensity score matching suggested that forests within protected areas have 11% less fires than non-protected areas. Overall, our results identify important causative factors of fire useful to address broad scale fire risk concerns at a landscape scale in Myanmar.

  13. Cernavoda nuclear power plant: Modifications in the fire protection measures of the CANDU 6 standard design

    International Nuclear Information System (INIS)

    Covalschi, V.

    1998-01-01

    Having as purpose the improvement of fire safety at the Cernavoda NPP - both in the prevention and the protection aspects in the case of fire - we implemented some modifications in the CANDU 6 standard design. These improvements are inspired, mainly, from two sources: the world-wide achievements in the field of fire protection techniques, introduced in nuclear power plants since the middle of 70's, when the CANDU 6 design was completed; the national practice and experience in fire protection, usually applied in industrial objectives (conventional power plants, in particular). The absence of any incident may be considered as a proof of the efficiency of the implemented fire preventing and protection measures. (author)

  14. Fires: what plant locations should we really protect

    International Nuclear Information System (INIS)

    Berry, D.L.

    1980-01-01

    A fire protection analysis technique was developed from earlier work involving the protection of nuclear power plants against acts of sabotage. Characteristics unique to fire phenomena were used to modify the sabotage analysis methodology. These characteristics include the effects of fuel loads, ventilation rates, heat loss areas, barrier ratings, and plant locations. The new fire analysis technique was applied to an example nuclear power plant having 85 different plant areas. It was found that some safety and nonsafety areas were both highly vulnerable to fire spread and important to overall safety, while other areas were found to be of marginal importance to fire safety

  15. Planning for fire control and protection of personnel

    International Nuclear Information System (INIS)

    Rule, A.V.

    1989-01-01

    Because nuclear installations are designed and built to high standards with segregation and fire barriers included, the risk from fires is not high. However, small fires can become large and nuclear sites present additional hazards to fire fighters because of radiation release and from metal fires (magnesium alloys and sodium) which require special techniques of firefighting. All sites have their own fire fighting force which would tackle a fire initially and these should train and work in close cooperation with the Local Authority fire service. The main points raised concern radiation protection for the fire fighters including the issuing of emergency dosemeters and potassium iodate tablets, decontamination of personnel, vehicles and equipment, communications, and the need for standardisation of plans at all installations throughout the country. (U.K.)

  16. Perspective methods of fire and explosion protection of 'Ukrytie' object

    International Nuclear Information System (INIS)

    Zakhmatov, V.D.; Potikha, V.M.; Shkarabura, N.G.

    1999-01-01

    There are 5 atomic power stations in Ukraine-Chernobyl, Zaporozhe, Rivne, Khmelnytsk, Yuzhnoukrainsk. Fire statistics on them: 1993 - 5 fires, 1994 - 2, 1995 - 2, 1996 - 3, 1997-98 no fires. The most valuable unique experience, accumulated in Ukraine, -is extinguishing of different fires, arising in the radioactive zone. There were the following kinds of fires: burning roof of the 4-th bloc; forest fires; fires in cable tunnels; spilled oil in wrecked constructions and buildings. Professional impulse fire-extinguisher is one of the most perspective developments. These fire-extinguishers have high power, range and scale of action. They are universal: able to solve different tasks in extinguishing, to decontaminate, for group and individual light and heat protection, for preventing explosions of dust and gas of up to 50 m 3 volume and in the open space

  17. CFES--California Fire Economics Simulator: A Computerized System for Wildland Fire Protection Planning

    Science.gov (United States)

    Jeremy S. Fried; J. Keith Gilless; Robert E. Martin

    1987-01-01

    The University of California's Department of Forestry and Resource Management, under contract with the California Department of Forestry and Fire Protection, has developed and released the first version of the California Fire Economics Simulator (CFES). The current release is adapted from the Initial Action Assessment component of the USFS's National Fire...

  18. Fire protection in nuclear power plants

    International Nuclear Information System (INIS)

    Wright, H.A.

    1981-01-01

    This lecture describes briefly the chronological order of events which may arise for a very serious emergency situation in a nuclear power plant for which preparations should be made even though the situation has an extremely low probability of happening. The planning and preparedness required are expected to cope with a whole spectrum of emergency situations, from minor accidents to serious plant failures which also lead to releases of significant quantities of radioactive material beyond the site boundary. Fire protection aspects will be briefly covered, and some guidance will be provided on exercises to ensure the plans are feasible and the appropriate personnel and facilities are in a satisfactory state of preparedness. (orig./RW)

  19. Fire protection guidelines for nuclear power plants, June 1976

    International Nuclear Information System (INIS)

    Anon.

    1977-01-01

    Guidelines acceptable to the NRC staff for implementing in the development of a fire protection program for nuclear power plants. The purpose of the fire protection program is to ensure the capability to shut down the reactor and maintain it in a safe shutdown condition and to minimize radioactive releases to the environment in the event of a fire. If designs or methods different from the guidelines presented herein are used, they must provide fire protection comparable to that recommended in the guidelines. Suitable bases and justification should be provided for alternative approaches to establish acceptable implementation of General Design Criterion 3

  20. 14 CFR 25.854 - Lavatory fire protection.

    Science.gov (United States)

    2010-01-01

    ... AIRWORTHINESS STANDARDS: TRANSPORT CATEGORY AIRPLANES Design and Construction Fire Protection § 25.854 Lavatory fire protection. For airplanes with a passenger capacity of 20 or more: (a) Each lavatory must be... disposal receptacle for towels, paper, or waste, located within the lavatory. The extinguisher must be...

  1. 24 Command Fire Improvement Action Program Plan

    International Nuclear Information System (INIS)

    GRIFFIN, G.B.

    2000-01-01

    Fluor Hanford (FH) is responsible for providing support to the Department of Energy Richland Operations Office (RL) in the implementation of the Hanford Emergency Preparedness (EP) program. During fiscal year 2000, a number of program improvements were identified from various sources including a major range fire (24 Command Fire). Evaluations of the emergency preparedness program have confirmed that it currently meets all requirements and that performance of personnel involved is good, however the desire to effect continuous improvement resulted in the development of this improvement program plan. This program plan defines the activities that will be performed in order to achieve the desired performance improvements

  2. Course in fire protection training for nuclear power plant personnel

    International Nuclear Information System (INIS)

    Walker, K.L.; Bates, E.F.; Randall, J.D.

    1979-01-01

    Proposed Regulatory Guide 1.120, entitled ''Fire Protection Guidelines for Nuclear Power Plants,'' provides detailed requirements for the overall fire protection programs at nuclear power plant sites in the United States. An essential element in such a program in the training of plant fire brigade personnel is the use of proper firefighting techniques and equipment. The Texas A and M University Nuclear Science Center (NSC) in conjunction with the Fire Protection Training Division of the Texas Engineering Extension Service has developed a one-week course to meet this training need. The program emphasizes hands-on exercises. The course is designed for up to 18 students with all protective clothing provided. Fire instructors are certified by the State of Texas, and registered nuclear engineers and certified health physicists supervise the radiological safety exercises. The first course was conducted during the week of January 8--12, 1979

  3. Technological Improvements for Digital Fire Control Systems

    Science.gov (United States)

    2017-09-30

    Final Technical Status Report For DOTC-12-01-INIT061 Technological Improvements for Digital Fire Control Systems Reporting Period: 30 Sep...accuracy and responsiveness to call for fire. These prototypes shall be more cost effective, sustainable , use a higher percentage of alternative...of the quad charts and provide DOTC with sufficient initiative information, the Quarterly Report must be supplemented with data described below

  4. EFFICIENCY OF FIRE-FIGHTING PROTECTION OBJECTS IN PROVISION OF FIRE SAFETY AT INDUSTRIAL ENTERPRISES

    Directory of Open Access Journals (Sweden)

    A. V. Zhovna

    2008-01-01

    Full Text Available The paper gives an analysis of economic results pertaining to organization of a system for fire-fighting protection of industrial enterprises in theRepublicofBelarus. Statistical data on operational conditions of technical means of fire-fighting protection, particularly, automatic systems for detection and extinguishing of fires, systems of internal fire-fighting water-supply.  Requirements and provisions  of normative and technical documents are thoroughly studied. Observance of these documents is to ensure the required level of  fire safety. On the basis of the obtained results concerning  economic analysis of efficiency optimization directions are defined for selection of technical means of fire-fighting protection at objects of industrial purpose.

  5. FIRE

    International Nuclear Information System (INIS)

    Brtis, J.S.; Hausheer, T.G.

    1990-01-01

    FIRE, a microcomputer based program to assist engineers in reviewing and documenting the fire protection impact of design changes has been developed. Acting as an electronic consultant, FIRE is designed to work with an experienced nuclear system engineer, who may not have any detailed fire protection expertise. FIRE helps the engineer to decide if a modification might adversely affect the fire protection design of the station. Since its first development, FIRE has been customized to reflect the fire protection philosophy of the Commonwealth Edison Company. That program is in early production use. This paper discusses the FIRE program in light of its being a useful application of expert system technologies in the power industry

  6. Nuclear power plant fire protection: fire detection (subsystems study Task 2)

    International Nuclear Information System (INIS)

    Berry, D.L.

    1977-12-01

    This report examines the adequacy of fire detection in the context of nuclear power plant safety. Topics considered are: (1) establishing area detection requirements, (2) selecting specific detector types, (3) locating and spacing detectors, and (4) performing installation tests and maintenance. Based on a thorough review of fire detection codes and standards and fire detection literature, the report concludes that current design and regulatory guidelines alone are insufficient to ensure satisfactory fire detection system performance. To assure adequate fire detection, this report recommends the use of in-place testing of detectors under conditions expected to occur normally in areas being protected

  7. Still a hot issue. US fire protection 20 years on

    International Nuclear Information System (INIS)

    Hathaway, L.R.

    1995-01-01

    Current fire protection concerns in the US nuclear industry are reviewed. Twenty years ago, a fire at the Brown's Ferry nuclear plant triggered a vigorous programme of regulation by the US Nuclear Regulatory Commission (NRC) and a still active response by power plant operators in seeking protection measures to meet the NRC criteria. The largest fire protection issue facing the industry concerns Thermo-Lag, a product formed from resins, subliming materials and fibreglass. This fire resistant wrap was installed in about 75 plants to provide a barrier between safety related cable systems. The Brown's Ferry fire has re-emphasised the importance of the separation criteria between redundant safety systems. Since 1989, however, there have been doubts about the adequacy of Thermo-Lag barriers and a major testing and analysis project addressing the problem is currently being sponsored by six utilities. Other regulatory- related issues facing the industry are the recently proposed defence-in-depth fire protection methodology, and for the future, fire protection strategies to cover shutdown, turbine generators and penetration seals through fire barriers. (UK)

  8. Fire protection in Angra-2 nuclear power plant. The use of fire protection collars on plastic piping systems

    International Nuclear Information System (INIS)

    Oliveira Segabinaze, R. de

    1994-01-01

    The object of this paper is to briefly the use of fire protection collars on plastic piping systems passing through wall and floor penetration. The fire protection collars consist of a stainless steel housing, in which the leading edges of two pivoting plates are in constant pressure contact with the pipe. In case of fire these plates react on the softened pipe with a guillotine action, thereby stopping the flow; within the housing a foam material expands to fill the space when subject to the heat of the fire. The piping project has to be modified to permit the fixing of the collars to walls and floor penetrations. (author). 2 refs, 9 figs

  9. Review of fire protection in the nuclear facilities of the Atomic Energy Commission, 1947--1975

    International Nuclear Information System (INIS)

    Maybee, W.W.

    1979-01-01

    In the 28 years in which it grew from a temporary wartime bomb development program to a federal agency with over $30 billion worth of facilities housing much of the nation's advanced research efforts, the Atomic Energy Commission set many records for safety. Among the best was a cumulative fire loss ratio of 12 cents per $100 of value. A 1969 fire--one of four in its history that exceeded $1 million in loss--incurred damages totaling $26 million and prompted major additions to its fire protection programs. The added programs, encompassing additional fire protection engineers, new protection systems, independent inspection programs, and new performance-based goals, resulted in an order-of-magnitude improvement. The cumulative fire loss ratio after 1969 was 0.06 cents per $100 of value, a record few industries have ever achieved

  10. Safety guide on fire protection in nuclear power plants

    International Nuclear Information System (INIS)

    1976-01-01

    The purpose of the Safety Guide is to give specific design and operational guidance for protection from fire and explosion in nuclear power plants, based on the general guidance given in the relevant sections of the 'Safety Code of Practice - Design' and the 'Safety Code of Practice - Operation' of the International Atomic Energy Agency. The guide will confine itself to fire protection of safety systems and items important to safety, leaving the non-safety matters of fire protection in nuclear power plants to be decided upon the basis of the various available national and international practices and regulations. (HP) [de

  11. Cold Vacuum Drying facility fire protection system design description

    International Nuclear Information System (INIS)

    PITKOFF, C.C.

    1999-01-01

    This document describes the Cold Vacuum Drying Facility (CVDF) fire protection system (FPS). The FPS provides fire detection, suppression, and loss limitation for the CVDF structure, personnel, and in-process spent nuclear fuel. The system provides, along with supporting interfacing systems, detection, alarm, and activation instrumentation and controls, distributive piping system, isolation valves, and materials and controls to limit combustibles and the associated fire loadings

  12. The principles of protection against fires in nuclear facilities

    International Nuclear Information System (INIS)

    Dupuy, Ph.; Gupta, O.

    2000-01-01

    Because of the presence of fissile or radioactive materials in nuclear facilities, their protection against fires is different from that of classical industrial installations. 3 priorities have been defined, in importance order: 1) maintaining nuclear safety in order to protect public and environment, 2) protection of workers, and 3) limiting the damages on the installation. The prevention of fires is based on 4 rules: 1) limiting as much as possible the quantity of inflammable materials and imposing a strict control of any use of igniting source, 2) assuring a permanent monitoring of the installation by means of reliable devices able to detect any fire starting, 3) designing the sectorization of the installation in order to keep fire in delimited zones and prevent its extension, and 4) enhancing the efficiency of the fire brigade intervention. (A.C.)

  13. Internal fire protection analysis for the United Kingdom EPR design

    Energy Technology Data Exchange (ETDEWEB)

    Laid, Abdallah [Nuclear New Build Generation Company Ltd. (NNB GenCo), Barnwood (United Kingdom). EDF Energy Plc.; Cesbron, Mickael [Service Etudes et Project Thermiques et Nucleaires (SEPTEN), Lyon (France). EDF-SA

    2015-12-15

    In the deterministic design basis analysis of the United Kingdom (UK) EPR based nuclear power plants all postulated initiating events are grouped into two different types, internal faults and internal/external hazards. ''Internal Fires'' is one of the internal hazards analysed at the design stage of the UK EPR. In effect, the main safety objective for fire protection is to ensure that all the required safety functions are performed in the event of an internal fire. To achieve this safety objective, provisions for protection against fire risks are taken to: (i) limit the spread of a fire, protect the safety functions of the facility; (ii) limit the propagation of smoke and dispersion of toxic, radioactive, inflammable, corrosive or explosive materials, and (iii) ensure the achievement of a safe shutdown state, personnel evacuation and all other necessary emergency actions. This paper presents the UK EPR approach on how the above provisions are applied. Such provisions involve implementing means of fire prevention, surveillance, firefighting and limiting fire consequences, appropriate to the risks inherent to the facility. Overall, the design of the UK EPR fire protection systems is based on three types of measures: prevention, containment and control.

  14. Reserves protect against deforestation fires in the Amazon.

    Directory of Open Access Journals (Sweden)

    J Marion Adeney

    Full Text Available BACKGROUND: Reserves are the principal means to conserve forests and biodiversity, but the question of whether reserves work is still debated. In the Amazon, fires are closely linked to deforestation, and thus can be used as a proxy for reserve effectiveness in protecting forest cover. We ask whether reserves in the Brazilian Amazon provide effective protection against deforestation and consequently fires, whether that protection is because of their location or their legal status, and whether some reserve types are more effective than others. METHODOLOGY/PRINCIPAL FINDINGS: Previous work has shown that most Amazonian fires occur close to roads and are more frequent in El Niño years. We quantified these relationships for reserves and unprotected areas by examining satellite-detected hot pixels regressed against road distance across the entire Brazilian Amazon and for a decade with 2 El Niño-related droughts. Deforestation fires, as measured by hot pixels, declined exponentially with increasing distance from roads in all areas. Fewer deforestation fires occurred within protected areas than outside and the difference between protected and unprotected areas was greatest near roads. Thus, reserves were especially effective at preventing these fires where they are known to be most likely to burn; but they did not provide absolute protection. Even within reserves, at a given distance from roads, there were more deforestation fires in regions with high human impact than in those with low impact. The effect of El Niño on deforestation fires was greatest outside of reserves and near roads. Indigenous reserves, limited-use reserves, and fully protected reserves all had fewer fires than outside areas and did not appear to differ in their effectiveness. CONCLUSIONS/SIGNIFICANCE: Taking time, regional factors, and climate into account, our results show that reserves are an effective tool for curbing destructive burning in the Amazon.

  15. Reserves Protect against Deforestation Fires in the Amazon

    Science.gov (United States)

    Adeney, J. Marion; Christensen, Norman L.; Pimm, Stuart L.

    2009-01-01

    Background Reserves are the principal means to conserve forests and biodiversity, but the question of whether reserves work is still debated. In the Amazon, fires are closely linked to deforestation, and thus can be used as a proxy for reserve effectiveness in protecting forest cover. We ask whether reserves in the Brazilian Amazon provide effective protection against deforestation and consequently fires, whether that protection is because of their location or their legal status, and whether some reserve types are more effective than others. Methodology/Principal Findings Previous work has shown that most Amazonian fires occur close to roads and are more frequent in El Niño years. We quantified these relationships for reserves and unprotected areas by examining satellite-detected hot pixels regressed against road distance across the entire Brazilian Amazon and for a decade with 2 El Niño-related droughts. Deforestation fires, as measured by hot pixels, declined exponentially with increasing distance from roads in all areas. Fewer deforestation fires occurred within protected areas than outside and the difference between protected and unprotected areas was greatest near roads. Thus, reserves were especially effective at preventing these fires where they are known to be most likely to burn; but they did not provide absolute protection. Even within reserves, at a given distance from roads, there were more deforestation fires in regions with high human impact than in those with low impact. The effect of El Niño on deforestation fires was greatest outside of reserves and near roads. Indigenous reserves, limited-use reserves, and fully protected reserves all had fewer fires than outside areas and did not appear to differ in their effectiveness. Conclusions/Significance Taking time, regional factors, and climate into account, our results show that reserves are an effective tool for curbing destructive burning in the Amazon. PMID:19352423

  16. Wildland Fire Research: Water Supply and Ecosystem Protection

    Science.gov (United States)

    Research is critical to better understand how fires affect water quality and supply and the overall health of an ecosystem. This information can be used to protect the safety of drinking water and assess the vulnerability of water supplies.

  17. Cold Vacuum Drying (CVD) Facility, Diesel Generator Fire Protection

    International Nuclear Information System (INIS)

    SINGH, G.

    2000-01-01

    This Acceptance Test Procedure (ATP) has been prepared to demonstrate that the Fire Protection and Detection System installed by Project W-441 (Cold Vacuum Drying Facility and Diesel Generator Building) functions as required by project specifications

  18. Cold Vacuum Drying (CVD) Facility, Diesel Generator Fire Protection

    CERN Document Server

    Singh, G

    2000-01-01

    This Acceptance Test Procedure (ATP) has been prepared to demonstrate that the Fire Protection and Detection System installed by Project W-441 (Cold Vacuum Drying Facility and Diesel Generator Building) functions as required by project specifications.

  19. Nuclear Power Plant Fire Protection Research Program

    International Nuclear Information System (INIS)

    Datta, A.

    1985-07-01

    The goal is to develop test data and analytical capabilities to support the evaluation of: (1) the contribution of fires to the risk from nuclear power plants; (2) the effects of fires on control room equipment and operations; and (3) the effects of actuation of fire suppression systems on safety equipment. A range of fire sources will be characterized with respect to their energy and mass evolution, including smoke, corrosion products, and electrically conductive products of combustion. An analytical method for determining the environment resulting from fire will be developed. This method will account for the source characteristics, the suppression action following detection of the fire, and certain parameters specific to the plant enclosure in which the fire originates, such as the geometry of the enclosure and the ventilation rate. The developing local environment in the vicinity of safety-related equipment will be expressed in terms of temperatures, temperature rise rates, heat fluxes, and moisture and certain species content. The response of certain safe shutdown equipment and components to the environmental conditions will be studied. The objective will be to determine the limits of environmental conditions that a component may be exposed to without impairment of its ability to function

  20. 78 FR 55765 - Compensatory and Alternative Regulatory Measures for Nuclear Power Plant Fire Protection (CARMEN...

    Science.gov (United States)

    2013-09-11

    ... Nuclear Power Plant Fire Protection (CARMEN-FIRE) AGENCY: Nuclear Regulatory Commission. ACTION: Draft..., ``Compensatory and Alternative Regulatory Measures for Nuclear Power Plant Fire Protection (CARMEN-FIRE).'' In... caused by impaired fire protection features at nuclear power plants. The report documents the history of...

  1. 78 FR 45573 - Compensatory and Alternative Regulatory Measures for Nuclear Power Plant Fire Protection (CARMEN...

    Science.gov (United States)

    2013-07-29

    ... Nuclear Power Plant Fire Protection (CARMEN-FIRE) AGENCY: Nuclear Regulatory Commission. ACTION: Notice of... Nuclear Power Plant Fire Protection (CARMEN-FIRE), Draft Report for Comment.'' DATES: Comments on this... caused by impaired fire protection features at nuclear power plants. The report documents the history of...

  2. Fire protection of safe shutdown capability at commercial nuclear power plants

    International Nuclear Information System (INIS)

    Sullivan, K.

    1993-01-01

    The comprehensive industrial safety standards and codes that exist today have evolved from lessons learned through past experience, research results, and improvements in technological capabilities. The current requirements for fire safety features of commercial nuclear power stations operated in the U.S. are a notable example of this practice. Although fire protection has always been an important design requirement, from the aftermath of a serious fire that occurred in 1975 at the Browns Ferry plant, it was learned that the life safety and property protection concerns of the major fire insurance underwriters may not sufficiently encompass nuclear safety issues, particularly with regard to the potential for fire damage to result in the common mode failure of redundant trains of systems, and composites important to the safe shutdown of the reactor. Following its investigations into the Browns Ferry fire, the Nuclear Regulatory Commission (NRC) promulgated guidance documents, which ultimately developed into mandatory regulations, necessary to assure the implementation of a fire protection program that would address nuclear safety concerns. The new criteria that evolved, contain prescriptive design features, as well as personnel and administrative requirements the Commission determined to be necessary to provide a defense-in-depth level of protection against the hazards of fire and its associated effects on safety related equipment. These criteria are primarily contained in Appendix R of Title 10 to the Code of Federal Regulations (10 CFR 50)

  3. Diesel generator fire protection: getting the balance right

    International Nuclear Information System (INIS)

    Enzmann, Hans; Swiss Reinsurance Co., Zurich)

    1986-01-01

    A wide range of different approaches to the fire protection of diesel generators can be found in nuclear power plants around the world. In some cases there is too little protection. In others there is far too much, such that fire prevention has been overemphasised at the expense of diesel generator operability and overall nuclear safety. A risk assessment check list developed in Switzerland could help to achieve the right balance. (author)

  4. Influence of safeguards and fire protection on criticality safety

    International Nuclear Information System (INIS)

    Six, D.E.

    1980-01-01

    There are several positive influences of safeguards and fire protection on criticality safety. Experts in each discipline must be aware of regulations and requirements of the others and work together to ensure a fault-tree design. EG and G Idaho, Inc., routinely uses an Occupancy-Use Readiness Manual to consider all aspects of criticality safety, fire protection, and safeguards. The use of the analytical tree is described

  5. Fire protection in nuclear power plants. Pt. 3. Fire protection for mechanical and electrotechnical equipment and components

    International Nuclear Information System (INIS)

    1994-01-01

    The KTA rule applies to LWRs and defines requirements to be met for fire protection of equipment and installations of the safety system, and all safety-relevant systems, and of those operating systems that under the effect of fire, may cause improper functioning of safety system components. (orig./HP) [de

  6. Fire protection of nuclear power plant cable ducts

    International Nuclear Information System (INIS)

    Kandrac, J.; Lukac, L.

    1987-01-01

    Fire protection of cable ducts in the Bohunice and Dukovany V-2 nuclear power plants is of a fourtier type. The first level consists in preventive measures incorporated in the power plant design and layout. The second level consists in early detection and a quick repressive action provided by an electric fire alarm system and a stationary spray system, respectively. Fire partitions and glands represent the third level while special spray, paint and lining materials represent the fourth level of the protection. Briefly discussed are the results of an analysis of the stationary spray system and the effects reducing the efficiency of a fire-fighting action using this system. The analysis showed the need of putting off cable duct fires using mobile facilities in case the stationary spray system cannot cope any longer. (Z.M.). 3 figs., 2 refs

  7. New probabilistic decision-making tools for fire protection systems

    International Nuclear Information System (INIS)

    Ksobiech, C.; Mowrer, F.

    1991-01-01

    The FIVE methodology provides guidance to utilities in performing an examination of potential plant severe accidents caused by fire initiated events. FIVE is oriented toward uncovering limiting plant design or operating characteristics (vulnerabilities) that make certain fire-initiated events more likely than others. It provides a combination of deterministic and probabilistic techniques for examining a power plant's fire probability and protection characteristics. It includes a two phase progressive screening method and a third phase consisting of a plant walkdown/verification process. The FIVE methodology centers on providing assurance of the availability of at least one train of the safe shutdown systems. FIVE has been developed for implementation by plant personnel who are most experienced with their plant's operations, fire hazards and fire protection features. The methodology provides these plant personnel with guidelines to quickly screen the plant down to the most significant locations where vulnerabilities may exist and then identify options to reduce the vulnerabilities

  8. Intumescent paint as fire protection coating

    Directory of Open Access Journals (Sweden)

    R. B. R.S. OLIVEIRA

    Full Text Available Abstract This paper is a compendium on intumescent paint and its main features regarding chemical composition, thermophysical properties and performance as a fire-retardant material. Some of the main technical publications and lines of research on the subject are presented herein. The purpose of this paper is to show the current stage of the technical research being conducted on the topic and enable a better understanding of this fire-retardant material.

  9. Fire protection system operating experience review for fusion applications

    International Nuclear Information System (INIS)

    Cadwallader, L.C.

    1995-12-01

    This report presents a review of fire protection system operating experiences from particle accelerator, fusion experiment, and other applications. Safety relevant operating experiences and accident information are discussed. Quantitative order-of-magnitude estimates of fire protection system component failure rates and fire accident initiating event frequencies are presented for use in risk assessment, reliability, and availability studies. Safety concerns with these systems are discussed, including spurious operation. This information should be useful to fusion system designers and safety analysts, such as the team working on the Engineering Design Activities for the International Thermonuclear Experimental Reactor

  10. Fire protection system operating experience review for fusion applications

    Energy Technology Data Exchange (ETDEWEB)

    Cadwallader, L.C.

    1995-12-01

    This report presents a review of fire protection system operating experiences from particle accelerator, fusion experiment, and other applications. Safety relevant operating experiences and accident information are discussed. Quantitative order-of-magnitude estimates of fire protection system component failure rates and fire accident initiating event frequencies are presented for use in risk assessment, reliability, and availability studies. Safety concerns with these systems are discussed, including spurious operation. This information should be useful to fusion system designers and safety analysts, such as the team working on the Engineering Design Activities for the International Thermonuclear Experimental Reactor.

  11. Literature study regarding fire protection in nuclear power plants. Part I: Fire rated separations

    International Nuclear Information System (INIS)

    Isaksson, S.

    1995-06-01

    This literature study has been made on behalf of the Swedish Nuclear Power Inspectorate. The aim is to describe different aspects of fire protection in nuclear power plants. Conventional building codes can not give guidance on where to make fire rated separations in order to separate redundant trains of safety systems. The separation must originate in functional demands from the authorities on what functions are essential during and after a fire, and under what circumstances these functions shall be retained, i.e. the number of independent faults and initiating events. As a basic demand it is suggested to rate the strength of separations according to conventional building code, based on fire load. The whole separating construction shall have the same fire rating, including the ventilation system. Deviations from the basic demand can de done in case it can be proven that it is possible to compensate some or all of the fire rating with other measures. There is a general lack of statistical information regarding the reliability of fire separating constructions such as walls, fire doors, penetration seals and fire dampers. The amount of cables penetrating a seal is in many cases much higher in real installations than what has been tested for type approval. It would therefore be valuable to perform a furnace test with a more representative amount of cables passing through a penetration seal. Tests have shown that the 20 foot horizontal separation distance stipulated by NRC is not a guarantee against fire damage. Spatial separations based on general requirements shall not be allowed, but considered from case to case based on actual circumstances. For fire protection by isolation or coatings, it is of great importance to choose the method of protection carefully, to be compatible with the material it shall be applied on, and the environment and types of fire that may occur. 48 refs, 2 figs, 5 tabs

  12. Fire protection at hot laboratories: Prevention, surveillance and fire-fighting

    International Nuclear Information System (INIS)

    Chappellier, A.M.

    1976-01-01

    After pointing out that fire in a hot laboratory can be an important factor contributing to a radioactivity accident, the author briefly recalls the items to be taken into account in a fire hazard analysis. He then describes various important aspects of prevention, detection and fire-fighting which - at the French Commissariat a l'Energie Atomique - are governed by already defined rules or by guidelines which are sufficiently advanced to give a clear idea of the final conclusions to be drawn therefrom. From the point of view protection, the concept of fire sector has been evolved, at hot laboratories, becomes the fire and contamination sector, so as to ensure under all circumstances the containment of any radioactive materials dispersed in the premises on fire. Regarding fire detection, a study should be made on the constraints specific to the facility and liable to affect detector operation. These include ventilation, radiations, neutral or corrosive atmosphere, etc. As regards fire-fighting, two particular aspects are dealt with, namely the question of using water in case of fire and action to be taken concerning ventilation. A practical example - the protection of a ventilation system - is described. In conclusion the paper refers to the need for a thorough analysis specific to each hot laboratory, and to the importance of preparing an operational plan so as to avoid any dangerous improvisations in case of an accident. (author)

  13. Study to develop improved fire resistant aircraft passenger seat materials

    Science.gov (United States)

    Duskin, F. E.; Schutter, K. J.; Sieth, H. H.; Trabold, E. L.

    1980-01-01

    The Phase 3 study of the NASA 'Improved Fire Resistant Aircraft Seat Materials' involved fire tests of improved materials in multilayered combinations representative of cushion configurations. Tests were conducted to determine their thermal, smoke, and fire resistance characteristics. Additionally, a 'Design Guideline' for Fire Resistant Passenger Seats was written outlining general seat design considerations. Finally, a three-abreast 'Tourist Class' passenger seat assembly fabricated from the most advanced fire-resistant materials was delivered.

  14. The radiation protection units of the Austrian fire brigades

    International Nuclear Information System (INIS)

    Aspek, W.; Schoenhacker, S.

    2009-01-01

    Since the 1960s, Austrian fire brigades have been involved in radiation protection. With the preparations for the NPP Zwentendorf and the building of the research reactor in Seibersdorf, the first radiation protection units of the fire brigade were founded. 45 years later: The NPP Zwentendorf never saw its start-up, the use of nuclear energy for the production of electricity is prohibited by a constitutional law, and the research reactor is being decommissioned. What's left are the radiation protection units of the fire brigades. The contribution gives an overview of similarities and differences of the radiation protection units in the nine federal states of Austria, with a special focus on equipment, training and organisation. Nation-wide guidelines and regulations for the tactics of first responders at radiological emergencies are presented and a couple of incidents will be analysed. (orig.)

  15. Fire protection of safe shutdown capability at commercial nuclear power plants

    International Nuclear Information System (INIS)

    Sullivan, K.

    1993-01-01

    The comprehensive industrial safety standards and codes that exist today have evolved from lessons learned through past experience, research results, and improvements in technological capabilities. The current requirements for fire safety features of commercial nuclear power stations operated in the US are a notable example of this practice. Although fire protection has always been an important design requirement, from the aftermath of a serious fire that occurred in 1975 at the Browns Ferry plant, it was learned that the life safety and property protection concerns of the major fire insurance underwriters may not sufficiently encompass nuclear safety issues, particularly with regard to the potential for fire damage to result in the common mode failure of redundant trains of systems, and components important to the safe shutdown of the reactor. Following its investigations into the Browns Ferry fire, the Nuclear Regulatory Commission (NRC) promulgated guidance documents, which ultimately developed into mandatory regulations, necessary to assure the implementation of a fire protection program that would address nuclear safety concerns. The new criteria that evolved, contain prescriptive design features, as well as personnel and administrative requirements the Commission determined to be necessary to provide a defense-in-depth level of protection against the hazards of fire and its associated effects on safety related equipment. These criteria are primarily contained in Appendix R of Title 10 to the Code of Federal Regulations (10 CFR 50). Since 1983, various members of the Department of Nuclear Energy (DNE) at Brookhaven National Laboratory (BNL) have provided technical assistance to the Nuclear Regulatory Commission (NRC) in support of its evaluations of fire protection features implemented at commercial nuclear power stations operated in the US. This paper presents a discussion of the insights gained by the author during his active participation in this area

  16. Design guide for fire protection of grouped electrical cables

    International Nuclear Information System (INIS)

    Dungan, K.W.

    1991-05-01

    This paper develops design guidance for fire protection of grouped electrical cables using previous research and the concept of design objectives based on damage limits. A quantitative approach is taken to establishing performance-oriented design objectives and addressing fires exposing cables as well as cable fires. A one-page Design Calculation Checklist is developed and examples are shown. In addition, testing was done for placement of linear thermal detection on cable trays and recommendations are given. 32 refs., 10 figs., 8 tabs

  17. Challenges to fire protection measures at Hamaoka Nuclear Power Station

    International Nuclear Information System (INIS)

    Narama, Takeshi

    2015-01-01

    New regulatory standards for fire protection at nuclear power plants have been established by the Nuclear Regulation Authority. This paper introduces the measures taken by the Hamaoka Nuclear Power Station for the following four items, which were especially big changes. (1) To install a combination of sensors of different types or instruments with equivalent functions so as to be able to emit unique signals to inform a fire in the early stage. (2) To conduct 'UL vertical burn test' as the demonstration test for self-extinguishing performance as the condition for flame-retardant cable. (3) To install automatic fire-extinguishers or fixed fire-extinguishing devices of manual type at the spots where fire-fighting is difficult due to the filling of smoke in a fire or the effect of radiation. (4) To separate the system for purpose of ensuring safety function to attain the high-temperature shutdown and cold-temperature shutdown of a reactor whatever fire may happen at the nuclear facilities. The examples of the installation of fire-extinguishers as the measures for the above Item (3) are as follows; (A) as for the devices containing oil, a foam-extinguishing agent is released against each target device from the nozzle, and (B) for large vertical pump motors indoors and relatively small pump motors, IA type automatic foam extinguishing systems are installed. (A.O.)

  18. The usage of phase change materials in fire fighter protective clothing: its effect on thermal protection

    Science.gov (United States)

    Zhao, Mengmeng

    2017-12-01

    The thermal protective performance of the fire fighter protective clothing is of vital importance for fire fighters. In the study fabrics treated by phase change materials (PCMs) were applied in the multi-layered fabrics of the fire fighter protective clothing ensemble. The PCM fabrics were placed at the different layers of the clothing and their thermal protective performance were measured by a TPP tester. Results show that with the application of the PCM fabrics the thermal protection of the multi-layered fabrics was greatly increased. The time to reach a second degree burn was largely reduced. The location of the PCM fabrics at the different layers did not affect much on the thermal protective performance. The higher amount of the PCM adds on, the higher thermal protection was brought. The fabrics with PCMs of a higher melting temperature could contribute to higher thermal protection.

  19. Fire-protection research for energy technology: Fy 80 year end report

    Science.gov (United States)

    Hasegawa, H. K.; Alvares, N. J.; Lipska, A. E.; Ford, H.; Priante, S.; Beason, D. G.

    1981-05-01

    This continuing research program was initiated in order to advance fire protection strategies for Fusion Energy Experiments (FEE). The program expanded to encompass other forms of energy research. Accomplishments for fiscal year 1980 were: finalization of the fault-free analysis of the Shiva fire management system; development of a second-generation, fire-growth analysis using an alternate model and new LLNL combustion dynamics data; improvements of techniques for chemical smoke aerosol analysis; development and test of a simple method to assess the corrosive potential of smoke aerosols; development of an initial aerosol dilution system; completion of primary small-scale tests for measurements of the dynamics of cable fires; finalization of primary survey format for non-LLNL energy technology facilities; and studies of fire dynamics and aerosol production from electrical insulation and computer tape cassettes.

  20. Fire-protection research for energy technology: FY 80 year-end report

    International Nuclear Information System (INIS)

    Hasegawa, H.K.; Alvares, N.J.; Lipska, A.E.; Ford, H.; Priante, S.; Beason, D.G.

    1981-01-01

    This continuing research program was initiated in 1977 in order to advance fire protection strategies for Fusion Energy Experiments (FEE). The program has since been expanded to encompass other forms of energy research. Accomplishments for fiscal year 1980 were: finalization of the fault-tree analysis of the Shiva fire management system; development of a second-generation, fire-growth analysis using an alternate moel and new LLNL combustion dynamics data; improvements of techniques for chemical smoke aerosol analysis; development and test of a simple method to assess the corrosive potential of smoke aerosols; development of an initial aerosol dilution system; completion of primary small-scale tests for measurements of the dynamics of cable fires; finalization of primary survey format for non-LLNL energy technology facilities; and studies of fire dynamics and aerosol production from electrical insulation and computer tape cassettes

  1. Design guides for cell atmosphere controls, utilities and fire protection

    International Nuclear Information System (INIS)

    Hill, A.J. Jr.; Peishel, F.L.; Slattery, E.F.

    1981-01-01

    Facilities for handling radioactive and toxic materials must be designed not only for efficient operation, but also for protection of the operating personnel and the public. The ventilation system is of primary importance in maintaining containment of any airborne radioactivity. The type, number, and location of in-cell services must be adequate for planned operations, but also must allow flexibility to accommodate expansion in the scope of operations or changes in programs. Fire protection systems and operational controls are mandatory to maintain containment of radioactivity in the event of an operating error or process accident that may result in a fire

  2. Monitoring of fire incidences in vegetation types and Protected ...

    Indian Academy of Sciences (India)

    two types of sensor data, i.e., AWiFS and MODIS, have found fires in 281 (out of 614) Protected Areas of India. .... 56 m resolution prepared as part of national car- bon project has ...... and its deficiency in India were pointed out as back- ground.

  3. Fire Propagation Performance of Intumescent Fire Protective Coatings Using Eggshells as a Novel Biofiller

    Directory of Open Access Journals (Sweden)

    M. C. Yew

    2014-01-01

    Full Text Available This paper aims to synthesize and characterize an effective intumescent fire protective coating that incorporates eggshell powder as a novel biofiller. The performances of thermal stability, char formation, fire propagation, water resistance, and adhesion strength of coatings have been evaluated. A few intumescent flame-retardant coatings based on these three ecofriendly fire retardant additives ammonium polyphosphate phase II, pentaerythritol and melamine mixed together with flame-retardant fillers, and acrylic binder have been prepared and designed for steel. The fire performance of the coatings has conducted employing BS 476: Part 6-Fire propagation test. The foam structures of the intumescent coatings have been observed using field emission scanning electron microscopy. On exposure, the coated specimens’ B, C, and D had been certified to be Class 0 due to the fact that their fire propagation indexes were less than 12. Incorporation of ecofriendly eggshell, biofiller into formulation D led to excellent performance in fire stopping (index value, (I=4.3 and antioxidation of intumescent coating. The coating is also found to be quite effective in water repellency, uniform foam structure, and adhesion strength.

  4. Fire protection program evaluation of Argonne National Laboratory, West for the Department of Energy

    International Nuclear Information System (INIS)

    1984-01-01

    A fire protection engineering survey was conducted of the Argonne National Laboratory, West Facility, near Idaho Falls, Idaho. This facility includes EBR-II, TREAT, ZPPR, and HFEF. The facility meets the improved risk criteria as set forth in DOE Order 5480.1, Chapter VII. Some recommendations are given

  5. Rules for preventing chemical risks: fire protection

    International Nuclear Information System (INIS)

    1985-02-01

    The Fundamental Safety Rules applicable to certain types of nuclear installation are intended to clarify the conditions of which observance, for the type of installation concerned and for the subject that they deal with, is considered as equivalent to compliance with regulatory French technical practice. These Rules should facilitate safety analysises and the clear understanding between persons interested in matters related to nuclear safety. They in no way reduce the operator's liability and pose no obstacle to statutory provisions in force. For any installation to which a Fundamental Safety Rule applies according to the foregoing paragraph, the operator may be relieved from application of the Rule if he shows proof that the safety objectives set by the Rule are attained by other means that he proposes within the framework of statutory procedures. Furthermore, the Central Service for the Safety of Nuclear Installations reserves the right at all times to alter any Fundamental Safety Rule, as required, should it deem, this necessary, while specifying the applicability conditions. The present rule defines the dispositions to take in account for avoid fire hazards in nuclear facilities (Power reactors and accelerators are excluded) [fr

  6. Fire protection: no fire without smoke. CCTV breakthrough in fire detection

    International Nuclear Information System (INIS)

    Anon.

    1997-01-01

    A new CCTV-based fire detection system uses advanced software to detect and locate smoke and vapour from a fire before it becomes visible to the human eye, but is intelligent enough to avoid false alarms due to steam, moving machinery or operating staff in the monitored area. The starting point for the development effort was video motion detection software as used in the security industry. (author)

  7. Dampers, fluidics and the failsafe fallacy [fire protection

    International Nuclear Information System (INIS)

    Dann, M.; Hodgson, T.

    1989-01-01

    The fire protection practices adopted at nuclear power stations generally follow the well established principles used throughout industry. Unfortunately, there is one particular area - the interaction with heating, ventilation and air conditioning (HVAC) services - where nuclear power stations pose a seemingly insoluble conflict: that between the need to contain and the need to ventilate. Now, however, solid state fire dampers using power fluidics may promise a solution. One of the key characteristics of a fluidic device is that it is 'solid state', i.e. it has no moving parts. Because of this, its inherent reliability is orders of magnitude greater than a mechanical device. (U.K.)

  8. Strategy and system of fire protection at Guangdong Daya Bay Nuclear Power Plant

    International Nuclear Information System (INIS)

    Zhou Weihong

    1999-12-01

    The fire protection is an important safety issue of nuclear power utilities. The author depicts the strategy and management system of fire protection implemented successfully at Guangdong Daya Bay Nuclear Power Plant of China

  9. 41 CFR 102-80.135 - Who is a qualified fire protection engineer?

    Science.gov (United States)

    2010-07-01

    ... protection engineer? 102-80.135 Section 102-80.135 Public Contracts and Property Management Federal Property... qualified fire protection engineer? A qualified fire protection engineer is defined as an individual with a thorough knowledge and understanding of the principles of physics and chemistry governing fire growth...

  10. 14 CFR 25.865 - Fire protection of flight controls, engine mounts, and other flight structure.

    Science.gov (United States)

    2010-01-01

    ... 14 Aeronautics and Space 1 2010-01-01 2010-01-01 false Fire protection of flight controls, engine... Design and Construction Fire Protection § 25.865 Fire protection of flight controls, engine mounts, and other flight structure. Essential flight controls, engine mounts, and other flight structures located in...

  11. Fire Source Accessibility of Water Mist Fire Suppression Improvement through Flow Method Control

    Energy Technology Data Exchange (ETDEWEB)

    Jung, Jun Ho; Kim, Hyeong Taek; Kim, Yun Jung; Park, Mun Hee [KHNP CRI, Daejeon (Korea, Republic of)

    2013-10-15

    Recently, nuclear power plants set CO{sub 2} fire suppression system. However it is hard to establish and to maintain and it also has difficulties performing function test. Therefore, it needs to develop a new fire suppression system to replace the existing CO{sub 2} fire suppression systems in nuclear power plant. In fact, already, there exist alternatives - gas fire suppression system or clean fire extinguishing agent, but it is hard to apply because it requires a highly complicated plan. However, water mist fire suppression system which has both water system and gas system uses small amount of water and droplet, so it is excellent at oxygen displacement and more suitable for nuclear power plant because it can avoid second damage caused by fire fighting water. This paper explains about enclosure effect of water mist fire suppression. And it suggests a study direction about water mist fire source approach improvement and enclosure effect improvement, using flow method control of ventilation system. Water mist fire suppression can be influenced by various variable. And flow and direction of ventilation system are important variable. Expectations of the plan for more fire source ventilation system is as in the following. It enhances enclosure effects of water mists, so it improves extinguish performance. Also the same effect as a inert gas injection causes can be achieved. Lastly, it is considered that combustible accessibility of water mists will increase because of descending air currents.

  12. Installation and operation of the Plantwide Fire Protection Systems and related Domestic Water Supply Systems

    International Nuclear Information System (INIS)

    1991-12-01

    A safe work environment is needed to support the Savannah River Site (SRS) mission of producing special nuclear material. This Environmental Assessment (EA) assesses the potential environmental impact(s) of adding to and upgrading the Plantwide Fire Protection System and selected related portions of the Domestic Water Supply System at SRS, Aiken, South Carolina. The following objectives are expected to be met by this action: Prevent undue threat to public health and welfare from fire at SRS; prevent undue hazard to employees at SRS from fire; prevent unacceptable delay to vital DOE programs as a result of fire at SRS; keep fire related property damage at SRS to a manageable level;, and provide an upgraded supply of domestic water for the Reactor Areas. The Reactor Areas' domestic water supplies do not meet current demand capacity due to the age and condition of the 30-year old iron piping. In addition, the water quality for these supplies is not consistent with current SCDHEC requirements. Therefore, DOE proposes to upgrade this Domestic Water Supply System to meet current demand and quality levels, as well as the needs of fire protection system improvement

  13. The correspondence concerning fire protection regulation for operating reactors (separation flame test of unpurified cables)

    International Nuclear Information System (INIS)

    Hasegawa, Takayasu; Miyakoshi, Hirohisa; Goto, Masami

    2013-01-01

    Nuclear power plants are taking fire protection measures taking into account past findings about the effects of fire by the demonstration test in order to maintain the safety of nuclear power plant in the event of a fire. The objective of the demonstration test described in this paper is to obtain advanced knowledge about over current fire of unqualified cable to be applied to fire protection measures. (author)

  14. Probabilistic evaluation of fire protection features found in nuclear power plants

    International Nuclear Information System (INIS)

    Azarm, M.A.; Boccio, J.L.; Ruger, C.

    1985-01-01

    This paper describes a method which can be used to evaluate, on a relative basis, the NRC Fire Protection (FP) guidelines as found in Section 9.5.1 (Fire Protection) of the Standard Review Plan (SRP). The approach, a hybrid of existing physical models for fire propagation determinations and probabilistic models for fire-mitigation system reliability, can potentially be used as an adjunct to the present fire safety review process

  15. Remotely-sensed active fire data for protected area management: eight-year patterns in the Manas National Park, India.

    Science.gov (United States)

    Takahata, Chihiro; Amin, Rajan; Sarma, Pranjit; Banerjee, Gitanjali; Oliver, William; Fa, John E

    2010-02-01

    The Terai-Duar savanna and grasslands, which once extended along most of the Himalayan foothills, now only remain in a number of protected areas. Within these localities, grassland burning is a major issue, but data on frequency and distribution of fires are limited. Here, we analysed the incidence of active fires, which only occur during the dry season (Nov.-Mar.), within a significant area of Terai grasslands: the Manas National Park (MNP), India. We obtained locations of 781 fires during the 2000-2008 dry seasons, from the Fire Information for Resource Management System (FIRMS) that delivers global MODIS hotspot/fire locations using remote sensing and GIS technologies. Annual number of fires rose significantly from around 20 at the start of the study period to over 90 after 2002, with most (85%) detected between December and January. Over half of the fires occurred in tall grasslands, but fire density was highest in wetland and riverine vegetation, dry at the time. Most burning took place near rivers, roads and the park boundary, suggesting anthropogenic origins. A kernel density map of all recorded fires indicated three heavily burnt areas in the MNP, all within the tall grasslands. Our study demonstrates, despite some technical caveats linked to fire detection technology, which is improving, that remote fire data can be a practical tool in understanding fire concentration and burning temporal patterns in highly vulnerable habitats, useful in guiding management.

  16. Inspection of fire protection measures and fire fighting capability at nuclear power plants. A publication within the NUSS programme

    International Nuclear Information System (INIS)

    1994-01-01

    The present publication has been developed with the help of experts from regulatory, operating and engineering organizations, all with practical experience in the field of fire protection of nuclear power plants. The publication outlines practices for inspecting the fire protection measures at nuclear power plants in accordance with Safety Series No.50-SG-D2(Rev.1), Fire Protection in Nuclear Power Plants, and includes a comprehensive fire safety inspection checklist of the specific elements to be addressed when evaluating the adequacy and effectiveness of the fire protection measures and manual fire fighting capability available at operating nuclear power plants. The publication will be useful not only to regulators and safety assessors but also to operators and designers. The book addresses a specialized topic and it is recommended that it be used in conjunction with Safety Guide No.50-SG-D2(Rev.1)

  17. Fire protection assessment in a WANO peer review

    International Nuclear Information System (INIS)

    Vella, R.

    1998-01-01

    The peer review programme is becoming the key programme of WANO. The reviews are conducted to assess the performance of plant personnel, the conditions of systems and equipment, the quality of programmes and procedures, and the effectiveness of plant management. The review team consists of highly qualified staff from other WANO members throughout the world who have extensive practical experience in the area the review. At the request of Paris Centre Members, the fire protection area has been added to the scope of WANO peer reviews. Relevant performance objectives and criteria have been developed to cover this area, these are written guidances upon which review of plant performance can be based. They are supported by criteria, more narrow in scope, to help further define what attributes of the fire protection management area contribute to the achievement of the associated performance objective. (author)

  18. EDV supported dynamic fire protection concept adaptation during dismantling of nuclear facilities

    International Nuclear Information System (INIS)

    Mummert, Maxi; Traichel, Anke; Dilger, Matthias

    2013-01-01

    Fire protection concepts are supposed to be a decision guide for the definition of measures and priorities in fire fighting and fire prevention. In case of reactor dismantling a fire protection concept for the actual status is required. Following the fuel removal from the reactor the protection goals are reduced to the safe confinement of radioactive materials and the restriction of radiation exposure. A dynamic fire protection concept was developed to allow the compliance with the required protection measures with respect to the protection targets. The implementation of the dynamic fire protection concept simplifies the planning of the dismantling steps and to adjust the fire protection measured in the frame of changes in the plant.

  19. Corrosion protection pays off for coal-fired power plants

    Energy Technology Data Exchange (ETDEWEB)

    Hansen, T.

    2006-11-15

    Zinc has long been used to hot-dip galvanise steel to deliver protection in harsh environments. Powder River Basin or eastern coal-fired plants benefit from using galvanized steel for conveyors, vibratory feeders, coal hoppers, chutes, etc. because maintenance costs are essentially eliminated. When life cycle costs for this process are compared to an alternative three-coal paint system for corrosion protection, the latter costs 5-10 times more than hot-dip galvanizing. An AEP Power Plant in San Juan, Puerto Rico and the McDuffie Coal Terminal in Mobile, AL, USA have both used hot-dip galvanized steel. 1 fig., 1 tab.

  20. Updates of the fire protection system of the Juzbado Nuclear Fuel Fabrication Plant; Actualizaciones del Sistema de Proteccion Contra Incendios de la Fabrica de Combustible Nuclear de Juzbado

    Energy Technology Data Exchange (ETDEWEB)

    Dorado, P.; Palomo, J. J.; Romano, A.

    2015-07-01

    The Juzbado Nuclear Fuel Fabrication Plant fire protection system is one of the most important safety system of the plant. Every year, a large part of the annual investment is employed to improve this system, to update its technology, in order to improve detection and extinction capability to minimize fire risk. Over the last few years, several improvement projects have been carried out that focused on fire detection technology update and on optimization of local detectors integration with a centralized control system, as well as on an advanced public address system, which used clear and unambiguous messages improving personnel response to a plant evacuation. Planned projects and those, which are currently under development, focus on improving passive fire protection means as well as fire protection of key emergency response equipment s such as emergency diesel generators and fire extinguishing bombs. (Author)

  1. An evaluation of risk methods for prioritizing fire protection features: a procedure for fire barrier penetration seals

    International Nuclear Information System (INIS)

    Dey, M.K.

    2004-01-01

    This paper generally evaluates risk methods available for prioritizing fire protection features. Risk methods involving both the use of qualitative insights, and quantitative results from a fire probabilistic risk analysis are reviewed. The applicability of these methods to develop a prioritized list of fire barrier penetration seals in a plant based on risk significance is presented as a procedure to illustrate the benefits of the methods. The paper concludes that current fire risk assessment methods can be confidently used to prioritize plant fire protection features, specifically fire barrier penetration seals. Simple prioritization schemes, using qualitative assessments and insights from fire PRA methodology may be implemented without the need for quantitative results. More elaborate prioritization schemes that allow further refinements to the categorization process may be implemented using the quantitative results of the screening processes in good fire PRAs. The use of the quantitative results from good fire PRAs provide several benefits for risk prioritization of fire protection features at plants, mainly from the plant systems analyses conducted for a fire PRA

  2. 'Passive fire protection in nuclear power plants' - German technologies of the company svt Brandschutz in future as well in Korean NPPs? -

    International Nuclear Information System (INIS)

    Bremer, Joerg; Kim, Duill; Wendt, Ruediger

    2002-01-01

    Fires in NPPs are unfortunately not avoidable and to consider during the planning and operation period of the plants. The multitude of combustible materials which are used especially cables, oils and other building materials describe a potential source of danger. In Germany recently a new planning guideline for the fire protection field in NPPs has been adopted: the nuclear guideline KTA 1401. This document certainly is one of the most progressive guidelines for the fire protection field and has united · structural engineering elements of fire protection · electrotechnical and machine components · as well as questions of fire alarm and organisation measures. Passive and active fire protection measures are explained and layed down in their complexity within this document. Our group of companies has realised quit a lot of fire protection projects in Europe during the last years, especially within retrofitting measures for NPPs in Germany, Switzerland, Russia, the Ukraine and Lithuania, the Czech and Slovak Republic as well as within decommissioning projects of NPPs. We have carried out international fire protection projects of the EBRD, London, and within the framework of TACIS projects of the European Commission, i. a. linked with the working out of fire protection analyses for NPPs realised in close co-operation with the Germanischer Lloyd, Hamburg. We especially have wide experiences in improving the fire protection of cable installations where a 100% separation of the different safety systems is not any longer possible

  3. Passive fire protection in high density village (case study, Bustaman Semarang)

    Science.gov (United States)

    Sukawi, Sukawi; Wahyu Firmandhani, Satriya; Hardiman, Gagoek

    2017-12-01

    Fire hazard is the disaster that always has an unpredictable process of coming. When it comes, its level scope and the magnitude of the effects cannot be predicted. Dense settlements especially in big cities, among others Bustaman Kampong Semarang never escape from physical problems such as flooding and wildfire. If both are compared in dense settlements scope, so that, wild fire is the most potentially catastrophic. It is necessary to do a research on passive fire protection in a village of high density city such as Bustaman. Qualitative research was conducted using descriptive method to conduct observations and interviews in the Bustaman. Bustaman as a high density village, with narrow roads and dense rows of houses. The terraced buildings are also encountered, and found many buildings use combustible material. That environmental conditions can facilitate the propagation of flames in case of fire. To improve the established Bustaman's environment, in terms of the application of passive fire protection systems, it is recommended to utilize the road as the dividing buildings. Need to build the separation wall fireproof in every each series in several units of too long buildings and attempted open space procurement that separates rows of buildings that are too long, and also the replacement of combustible material with a material that is more incombustible.

  4. Fire protection at the Fast Flux Test Facility (a sodium cooled test reactor)

    International Nuclear Information System (INIS)

    Bell, J.R.

    1980-01-01

    For purposes of this presentation, fire protection at the FFTF is subdivided into two catagories; protection for non-sodium areas and protection for areas containing sodium. Fire protection systems and philosophies for non-sodium areas at the FFTF are very similar to those used at conventional power plants being constructed throughout the country. They follow, essentially, the NRC rules and guidelines and ANSI 59.4 Generic Requirements for Light Water Nuclear Power Plant Fire Protection. The FFTF with its support facilities have their own water system comprised of a looped 8'' and 10'' underground distribution system, three 1500 GPM fire pumps and three ground level storage tanks totaling 736,000 gallons with 420,000 reserved for fire protection. Fire hydrants are enclosed with hose houses outfitted for use by the Emergency Response Team (ERT). Fire prevention systems for sodium areas of the FFTF are also described

  5. Potentials and limitations of remote fire monitoring in protected areas.

    Science.gov (United States)

    Dos Santos, João Flávio Costa; Romeiro, Joyce Machado Nunes; de Assis, José Batuíra; Torres, Fillipe Tamiozzo Pereira; Gleriani, José Marinaldo

    2018-03-01

    Protected areas (PAs) play an important role in maintaining the biodiversity and ecological processes of the site. One of the greatest challenges for the PA management in several biomes in the world is wildfires. The objective of this work was to evaluate the potentialities and limitations of the use of data obtained by orbital remote sensing in the monitoring fire occurrence in PAs. Fire Occurrence Records (FORs) were analyzed in Serra do Brigadeiro State Park, Minas Gerais, Brazil, from 2007 to 2015, using photo interpreted data from TM, ETM + and OLI sensors of the Landsat series and the Hot Spot Database (HSD) from the Brazilian Institute of Space Research - INPE. It was also observed the time of permanence of the scar left by fire on the landscape, through the multitemporal analysis of the behavior of NDVI (Normalized Difference Vegetation Index) and NBR (Normalized Burn Ratio) indexes, before and after the occurrence. The greatest limitation found for the orbital remote monitoring was the presence of clouds in the passage of the sensor in dates close to the occurrence of the fires. The burned area identified by photo interpretation was 54.9% less than the area contained in the FOR. Although the HSD reported fire occurrences in the buffer zone (up to 10km from the Park), no FORs were found at a distance greater than 1100m from the boundaries of the PA. As the main potential of remote sensing, the possibility of identifying burned areas throughout the park and surroundings is highlighted, with low costs and greater accuracy. Copyright © 2017 Elsevier B.V. All rights reserved.

  6. Regional scales of fire danger rating in the forest: improved technique

    Directory of Open Access Journals (Sweden)

    A. V. Volokitina

    2017-04-01

    Full Text Available Wildland fires distribute unevenly in time and over area under the influence of weather and other factors. It is unfeasible to air patrol the whole forest area daily during a fire season as well as to keep all fire suppression forces constantly alert. Daily work and preparedness of forest fire protection services is regulated by the level of fire danger according to weather conditions (Nesterov’s index. PV-1 index, fire hazard class (Melekhov’s scale, regional scales (earlier called local scales. Unfortunately, there is still no unified comparable technique of making regional scales. As a result, it is difficult to maneuver forest fire protection resources, since the techniques currently used are not approved and not tested for their performance. They give fire danger rating incomparable even for neighboring regions. The paper analyzes the state-of-the-art in Russia and abroad. It is stated the irony is that with factors of fire danger measured quantitatively, the fire danger itself as a function has no quantitative expression. Thus, selection of an absolute criteria is of high importance for improvement of daily fire danger rating. On the example of the Chunsky forest ranger station (Krasnoyarsk Krai, an improved technique is suggested of making comparable local scales of forest fire danger rating based on an absolute criterion of fire danger rating – a probable density of active fires per million ha. A method and an algorithm are described of automatized local scales of fire danger that should facilitate effective creation of similar scales for any forest ranger station or aviation regional office using a database on forest fires and weather conditions. The information system of distant monitoring by Federal Forestry Agency of Russia is analyzed for its application in making local scales. To supplement the existing weather station net it is suggested that automatic compact weather stations or, if the latter is not possible, simple

  7. Fire protection programme during construction of the Chashma nuclear power plant

    International Nuclear Information System (INIS)

    Mian Umer, M.

    1998-01-01

    A clear view is given of several measures that have been taken with regard to fire prevention, protection and fire fighting during all phases of the construction, installation and commissioning of the Chasma nuclear power plant to protect personnel and equipment so that any delays in plant operation as a result of fire incident can be avoided. These measures include the precautions taken, the provisions made for fire extinguishers and hydrants, and the setting up of a fire brigade. An overview is also given of the fire incidents that have occurred. (author)

  8. Constructive fire protection of steel corrugated beams of buildings and other structures

    Directory of Open Access Journals (Sweden)

    Ilyin Nikolay

    2017-01-01

    Full Text Available The research introduces a methodology of establishing indicators of fire safety of a building in relation to a guaranteed duration of steel fire-proof corrugated beams resistance in conditions of standard fire tests. Indicators of fire safety are also established in the assessment of design limits of steel fire-proof corrugated beams during design process, construction or maintenance of the building as well as in reducing economic costs when testing steel structures for fire resisting property. The suggested methodology introduces the system of actions aimed to design constructive fire protection of steel corrugated beams of buildings. Technological effect is achieved by conducting firing tests of steel construction by non-destructive methods; the evaluation of fire resistance of fire-proof elements of corrugated beams (corrugated web, upper and lower shelves is identified by the least fire-proof element of a welded I-beam. In this methodology fire resistance duration of the constituent elements of a welded I-beam with account of its fire protection ability is described with an analytic function taken as variables. These variables are intensity strength of stresses and the degree of fire protection of a compound element.

  9. Literature study regarding fire protection in nuclear power plants. Part 2: Fire detection and -extinguishing systems

    International Nuclear Information System (INIS)

    Isaksson, S.

    1996-01-01

    This literature study has been made on behalf of the Swedish Nuclear Power Inspectorate. The aim is to describe different aspects of fire protection in nuclear power plants. Detection and extinguishing systems in Swedish nuclear power plants have only to a limited extent been designed after functional demands, such as a maximum acceptable damage or a maximum time to detect a fire. The availability of detection systems is difficult to assess, partly because of lack of statistics. The user interface is very important in complex systems as nuclear plants. An extinguishing system designed according to the insurance companies' regulations will only fulfill the basic demands. It should be noted that normal sprinkler design does not aim for extinguishing fires, the objective is to control fire until manual extinguishment is possible. There is a great amount of statistics on wet and dry pipe sprinkler systems, while statistics are more scarce for deluge systems. The statistics on the reliability of gaseous extinguishing systems have been found very scarce. A drawback of these systems is that they are normally designed for one shot only. There are both traditional and more recent extinguishing systems that can replace halons. From now on there will be a greater need for a thorough examination of the properties needed for the individual application and a quantification of the acceptable damage. There are several indications on the importance of a high quality maintenance program as well as carefully developed routines for testing and surveillance to ensure the reliability of detection and extinguishing systems. 78 refs, 8 figs, 10 tabs

  10. An assessment of the fire protection requirements throughout a NPP life related to current IAEA regulations and American, Canadian and UE regulations

    International Nuclear Information System (INIS)

    Branzeu, N.; Necula, D.; Badea, M.; Teodorescu, D.; Peteu, M.

    2006-01-01

    Statistics on fires has surprisingly shown that the frequency of fires in a nuclear power plant are as high as in the conventional industrial units. The analyses on fires occurred in a NPP need to consider both their well-known severe damages and the nuclear consequences. In 1975 a severe fire occurred in BROWNS FERRY NPP due to the ignition of the polyurethane foam used in the electric cable penetration sealings. The fire propagated to the cable channels and damaged over 1600 cables. The fire event revealed important shortcomings in the fire protection design and procedures. The fire represented a crucial event that changed fundamentally the fire protection regulation in the United States nuclear industry. The fire protection programs, standards and guides currently applied, have been developed on basis of this fire analysis and gained conclusions/experience. The purpose of the article is to be a short presentation of the fire protection requirements for all NPP life stages (i.e. design, construction, commissioning, operation and decommissioning), including the most recent issues of the standards, codes, guides and regulations in US, Canada, IAEA and some European countries. Such documentation represented the main technical support in establishing the national fire protection standard design regarding all the stages of a CANDU-6 NPP life, all the types of operational NPPs, particularly for Cernavoda NPP Unit 1 and Unit 2 (now in an advanced stage of construction). In order to satisfy the requirements provided by this documentation, as practically as possible, a list of analyses and fire protection improvement measures for Cernavoda NPP is presented. (authors)

  11. 30 CFR 77.1916 - Welding, cutting, and soldering; fire protection.

    Science.gov (United States)

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Welding, cutting, and soldering; fire... OF UNDERGROUND COAL MINES Slope and Shaft Sinking § 77.1916 Welding, cutting, and soldering; fire protection. (a) One portable fire extinguisher shall be provided where welding, cutting, or soldering with...

  12. 77 FR 74381 - Protection of Stratospheric Ozone: Listing of Substitutes for Ozone Depleting Substances-Fire...

    Science.gov (United States)

    2012-12-14

    ... Protection of Stratospheric Ozone: Listing of Substitutes for Ozone Depleting Substances--Fire Suppression... a companion proposed rule issuing listings for three fire suppressants under EPA's Significant New... companion proposed rule issuing listings for three fire suppressants under EPA's Significant New...

  13. Optimization of fire protection measures and quality controls in nuclear power plants

    International Nuclear Information System (INIS)

    Brenig, H.; Holtschmidt, H.; Liemersdorf, H.; Suetterlin, L.; Dobbernack, R.; Hahn, C.; Hosser, D.; Kordina, K.; Schneider, U.; Sprey, W.; Wesche, H.

    1985-09-01

    This study presents theoretical and experimental investigations on the evaluation of fire hazards and the optimization of fire protection measures in German nuclear power plants. Differences between the method presented here and the US ''Fire Hazard Analysis'' result from the inclusion of the stringent redundancy concept of German nuclear power plants and the emphasis placed on passive structural fire protection measures. The method includes a time-dependent quantification of fire-specific event sequences. Fire occurrence frequencies and the reliabilities of active fire protection measures were derived from German experiences and literature abroad. The reliability data of passive fire protection measures were obtained by an evaluation of experiments and probabilistic analyses. For the calculation of fire sequences fundamental experiments were taken into consideration. For the quantification of the time-dependent event trees a methodology was applied which permits an evaluation of the influence of the individual measures. The consequences of fire were investigated for ten fire events identified as decisive, and the fire sequence paths important in terms of safety were quantified. Their annual frequencies are within a range of 10 -3 to 8.10 -6 . (orig./HP) [de

  14. RCC-F: Design and construction rules for PWR fire protection systems

    International Nuclear Information System (INIS)

    2013-01-01

    The RCC-F code defines the rules for designing, building and installing the fire protection systems used to manage the nuclear hazards inherent in the outbreak of a fire inside the facility and thereby control the fundamental nuclear functions. The code provides fire protection recommendations in terms of: the industrial risk (loss of assets and/or operation), personnel safety, the environment. The code is divided into five main sections: generalities, design safety principles, fire protection design bases, construction provisions, rules for installing the fire protection components and equipment. The RCC-F code is available as an ETC-F version specifically for EPR projects (European pressurized reactor). Contents of the 2013 edition of the ETC-F code: Volume A - Generalities: Structure of ETC-F general points, documentation (in progress), chapter (provision) quality assurance; Volume B - Design safety principles: design nuclear safety principles; Volume C - Fire protection design bases: fire protection design bases; Volume D - Construction provisions: construction provisions; Volume E - Installation rules for fire protection: rules for installing the fire protection, components and equipment

  15. Cold Vacuum Dryer (CVD) Facility Fire Protection System Design Description (SYS 24)

    Energy Technology Data Exchange (ETDEWEB)

    SINGH, G.

    2000-10-17

    This system design description (SDD) addresses the Cold Vacuum Drying (CVD) Facility fire protection system (FPS). The primary features of the FPS for the CVD are a fire alarm and detection system, automatic sprinklers, and fire hydrants. The FPS also includes fire extinguishers located throughout the facility and fire hydrants to assist in manual firefighting efforts. In addition, a fire barrier separates the operations support (administrative) area from the process bays and process bay support areas. Administrative controls to limit combustible materials have been established and are a part of the overall fire protection program. The FPS is augmented by assistance from the Hanford Fire Department (HED) and by interface systems including service water, electrical power, drains, instrumentation and controls. This SDD, when used in conjunction with the other elements of the definitive design package, provides a complete picture of the FPS for the CVD Facility.

  16. Fire protection for nuclear power plants. Part 1. Fundamental approaches. Version 6/99

    International Nuclear Information System (INIS)

    1999-06-01

    The KTA nuclear safety code sets out the fundamental approaches and principles for the prevention of fires in nuclear power plants, addressing aspects such as initiation, spreading, and effects of a fire: (a) Fire load and ignition sources, (b) structural and plant engineering conditions, (c) ways and means relating to fire call and fire fighting. Relevant technical and organisational measures are defined. Scope and quality of fire prevention measures to be taken, as well the relevant in-service inspection activities are determined according to the protective goals pursued in each case. (orig./CB) [de

  17. Study on aging management of fire protection system in nuclear power plant

    International Nuclear Information System (INIS)

    Fang Huasong; Du Yu; Li Jianwen; Shi Haining; Tu Fengsheng

    2010-01-01

    Fire prevention, fire fighting and fire automatic alarms are three aspects which be included in fire protection system in nuclear power plants. The fire protection system can protect personnel, equipment etc in the fire, so their performance will have a direct influence on the safe operation in nuclear power plants. The disabled accidents caused by aging have happened continuously with the extension of time in the fire protection system, which is the major security risk during the running time in nuclear power plants. In view of the importance of fire protection system and the severity of aging problems, the aging are highly valued by the plant operators and related organizations. Though the feedback of operating experience in nuclear power plant, the impact of the fire-fighting equipment aging on system performance and reliability be assessed, the aging sensitive equipment be selected to carry out the aging analysis and to guide the management and maintenance to guarantee the healthy operation in life time of fire protection system in nuclear power plant. (authors)

  18. Development of a Smart Residential Fire Protection System

    OpenAIRE

    Juhwan Oh; Zhongwei Jiang; Henry Panganiban

    2013-01-01

    Embedded system is applied for the development of smart residential fire detection and extinguishing system. Wireless communication capability is integrated into various fire sensors and alarm devices. The system activates the fire alarm to warn occupants, executes emergency and rescue calls to remote residents and fire-fighting facility in an intelligent way. The effective location of extra-sprinklers within the space of interest for the fire extinguishing system is also investigated. Actual...

  19. The principles for creation of fire-prevention forest belts with barriers of deciduous species for protection from crown fires

    Directory of Open Access Journals (Sweden)

    S. N. Sannikov

    2017-10-01

    Full Text Available The article discuss one of the priority security problems in Russia, which is elaboration of the strategic system of the forest and society safeguards from catastrophic forest crown fires in connection with rapid climate warming. It is postulated, that a most effective and reliable barrier for the dispersal of the intensive crown fire in a coniferous forest massive can be a sufficiently wide strip of deciduous tree species – «deciduous forest barrier», which has phytomass capable of absorbing crown fire energy and transforming them to surface fire, which may be extinguished by technical means. The actuality of the natural study of the transition parameters from the crown fire to surface fire has been noted, depending on climate, fire intensity and the deciduous barrier structure. The results of the quantitative natural investigation of the consequences of catastrophic crown fires of 2004 in the island pine forests of forest-steppe zone in Kurgan Oblast, which passed through the belt of 50–70 year-old birch stands of middle density, has been cited and formalized mathematically. It has been shown, that 150 m width of deciduous forest barrier is necessary as a minimum for the reliable transition of the high intensive front crown fire to surface fire in the forest-steppe conditions of the Western Siberia, but this width reduces with a decreasing heating effect. It has been proposed to create the complex fire-prevention forest belts of different construction for the protection of forests, industrial objects and settlements. Besides a basic deciduous barrier, their structure should include technologically necessary buffer zones and zones for the localization and extinguishing surface fire, which stop a crown fire. It has been recommended to use natural regeneration of deciduous tree species, as a most effective and non-deficient method for the creation of deciduous forest barriers in the predominant forest types, except the lichen pine forests

  20. Effective fire protection for turbines ensures high operational availability; Wirksamer Brandschutz fuer Turbinen stellt hohe Verfuegbarkeit sicher

    Energy Technology Data Exchange (ETDEWEB)

    Knop, Arnd [Minimax GmbH und Co. KG, Bad Oldesloe (Germany). Div. Energy

    2013-10-01

    Designing fire protection in power plants is extremely complex and related to different requirements from operators, insurers, and experts. High- and low-pressure water mist systems are increasingly used in turbine fire protection, as they have ideal properties for this type of application. There are multifaceted fire risks in the areas adjacent to a turbine. Therefore, an overall view of all protected areas is indispensable for effective and reliable fire protection. The paper provides a detailed look at the entire spectrum of possible fire protection technologies for turbines and their adjacent areas, describes functionalities and itemises the benefits of individual fire protection measures. (orig.)

  1. Technical methods for a risk-informed, performance-based fire protection program at nuclear power plants

    International Nuclear Information System (INIS)

    Dey, M.K.

    1998-01-01

    This paper presents a technical review and examination of technical methods that are available for developing a risk-informed, performance-based fire protection program at a nuclear plant. The technical methods include ''engineering tools'' for examining the fire dynamics of fire protection problems, reliability techniques for establishing an optimal fire protection surveillance program, fire computer codes for analyzing important fire protection safety parameters, and risk-informed approaches that can range from drawing qualitative insights from risk information to quantifying the risk impact of alternative fire protection approaches. Based on this technical review and examination, it is concluded that methods for modeling fires, and reliability and fire PRA analyses are currently available to support the initial implementation of simple risk-informed, performance-based approaches in fire protection programs. (author)

  2. Technical methods for a risk-informed, performance-based fire protection program at nuclear power plants

    International Nuclear Information System (INIS)

    Dey, M.K.

    2000-01-01

    This paper presents a technical review and examination of technical methods that are available for developing a risk-informed, performance-based fire protection program at a nuclear plant. The technical methods include 'engineering tools' for examining the fire dynamics of fire protection problems, reliability techniques for establishing an optimal fire protection surveillance program, fire computer codes for analyzing important fire protection safety parameters, and risk-informed approaches that can range from drawing qualitative insights from risk information to quantifying the risk impact of alternative fire protection approaches. Based on this technical review and examination, it is concluded that methods for modeling fires, and reliability and fire probabilistic risk analyses (PRA) are currently available to support the initial implementation of simple risk-informed, performance-based approaches in fire protection programs. (orig.) [de

  3. Laboratory investigation of fire protection coatings for creosote-treated timber railroad bridges

    Science.gov (United States)

    Carol A. Clausen; Robert H. White; James P. Wacker; Stan T. Lebow; Mark A. Dietenberger; Samuel L. Zelinka; Nicole M. Stark

    2014-01-01

    As the incidence of timber railroad bridge fires increases, so has the need to develop protective measures to reduce the risk from accidental ignitions primarily caused by hot metal objects. Of the six barrier treatments evaluated in the laboratory for their ability to protect timbers from fires sourced with ignition from hot metal objects only one intumescent coating...

  4. 77 FR 58170 - Proposed Renewal of Existing Information Collection; Fire Protection (Underground Coal Mines)

    Science.gov (United States)

    2012-09-19

    ... Renewal of Existing Information Collection; Fire Protection (Underground Coal Mines) AGENCY: Mine Safety... INFORMATION: I. Background Fire protection standards for underground coal mines are based on section 311(a) of the Federal Mine Safety and Health Act of 1977 (Mine Act). 30 CFR 75.1100 requires that each coal mine...

  5. Improving composition of protective coatings for steel casting

    International Nuclear Information System (INIS)

    Kuz'kina, N.N.; Pegov, V.G.; Bogatenkov, V.F.; Shub, L.G.; Raspopova, N.A.

    1983-01-01

    A radically new fuel-free slag-forming mixture used as protective coating for steel casting is introduced. The lack of combustible powders precludes explosion and fire Lazard in mixture preparation. Usage of the new mixture in stainless steel casting of Kh18N10T type permitted to improve the ingot surface quality and reduce spoilage from 1.16 to 0.66%

  6. 10 CFR Appendix R to Part 50 - Fire Protection Program for Nuclear Power Facilities Operating Prior to January 1, 1979

    Science.gov (United States)

    2010-01-01

    ... service-water/fire-water uses the minimum volume for fire uses shall be ensured by means of dedicated... knowledge of his or her role in the fire fighting strategy for the area assumed to contain the fire... LICENSING OF PRODUCTION AND UTILIZATION FACILITIES Pt. 50, App. R Appendix R to Part 50—Fire Protection...

  7. Dual protection of wood surface treated with melamine-modified urea-formaldehyde resin mixed with ammonium polyphosphate against both fire and decay

    Science.gov (United States)

    Xing-xia Ma; Grant T. Kirker; Ming-liang Jiang; Yu-zhang Wu

    2016-01-01

    Surface coatings of melamine-modified urea-formaldehyde resins (MUFs) containing ammonium polyphosphate (APP) have been shown to significantly improve the fire retardancy of wood by prolonging the ignition time and reducing the heat release rate, total heat released, and mass loss rate. Dual protection of wood against both decay and fire has been proposed for remedial...

  8. Fire protection program fiscal year 1995 site support program plan, Hanford Fire Department

    International Nuclear Information System (INIS)

    Good, D.E.

    1994-09-01

    The mission of the Hanford Fire Department (HFD) is to support the safe and timely cleanup of the Hanford site by providing fire suppression, fire prevention, emergency rescue, emergency medical service, and hazardous materials response; and to be capable of dealing with and terminating emergency situations which could threaten the operations, employees, or interest of the US Department of Energy operated Hanford Site. This includes response to surrounding fire departments/districts under a mutual aid agreement and contractual fire fighting, hazardous materials, and ambulance support to Washington Public Power Supply System (Supply System). The fire department also provides site fire marshal overview authority, fire system testing and maintenance, self-contained breathing apparatus maintenance, building tours and inspections, ignitable and reactive waste site inspections, prefire planning, and employee fire prevention education. This report describes the specific responsibilities and programs that the HFD must support and the estimated cost of this support for FY1995

  9. Fire Protection Program fiscal year 1996, site support program plan Hanford Fire Department. Revision 2

    International Nuclear Information System (INIS)

    Good, D.E.

    1995-09-01

    The mission of the Hanford Fire Department (HFD) is to support the safe and timely cleanup of the Hanford site by providing fire suppression, fire prevention, emergency rescue, emergency medical service, and hazardous materials response; and to be capable of dealing with and terminating emergency situations which could threaten the operations, employees, or interest of the US Department of Energy operated Hanford Site. This includes response to surrounding fire departments/districts under a mutual aid agreement and contractual fire fighting, hazardous materials, and ambulance support to Washington Public Power Supply System (Supply System). The fire department also provides site fire marshal overview authority, fire system testing and maintenance, self-contained breathing apparatus maintenance, building tours and inspections, ignitable and reactive waste site inspections, prefire planning, and employee fire prevention education. This report gives a program overview, technical program baselines, and cost and schedule baseline

  10. 33 CFR 149.419 - Can the water supply for the helicopter deck fire protection system be part of a fire water system?

    Science.gov (United States)

    2010-07-01

    ... 33 Navigation and Navigable Waters 2 2010-07-01 2010-07-01 false Can the water supply for the... § 149.419 Can the water supply for the helicopter deck fire protection system be part of a fire water system? (a) The water supply for the helicopter deck fire protection system required under § 149.420 or...

  11. LMFBR plant design features for sodium spill and fire protection

    International Nuclear Information System (INIS)

    Palm, R.E.

    1982-01-01

    Design features have been developed for an LMFBR plant to protect the concrete structures from potential liquid spills and fires and prevent sodium-concrete reactions. The inclusion of these features in the plant design reduces the severity of design basis accident conditions imposed on containment and other critical plant structures. Steel liners are provided in cells containing radioactive sodium systems, and catch pans are located in non-radioactive sodium system cells. The design requirements and descriptions of each of these protective features are presented. The loading conditions, analytical approach and numerical results are also included. Design of concrete cell structures that are subject to high temperature effects from sodium spills is discussed. The structural design considers the influence of high temperature on design properties of concrete and carbon steel materials based on results of a comprehensive test program. The development of these design features and high temperature design considerations for the Clinch River Breeder Reactor Plant (CRBRP) are presented in this paper

  12. Fire resistance of wood members with directly applied protection

    Science.gov (United States)

    Robert H. White

    2009-01-01

    Fire-resistive wood construction is achieved either by having the structural elements be part of fire-rated assemblies or by using elements of sufficient size that the elements themselves have the required fire-resistance ratings. For exposed structural wood elements, the ratings in the United States are calculated using either the T.T. Lie method or the National...

  13. Passive fire building protection system evaluation (case study: millennium ict centre)

    Science.gov (United States)

    Rahman, Vinky; Stephanie

    2018-03-01

    Passive fire protection system is a system that refers to the building design, both regarding of architecture and structure. This system usually consists of structural protection that protects the structure of the building and prevents the spread of fire and facilitate the evacuation process in case of fire. Millennium ICT Center is the largest electronic shopping center in Medan, Indonesia. As a public building that accommodates the crowd, this building needs a fire protection system by the standards. Therefore, the purpose of this study is to evaluate passive fire protection system of Millennium ICT Center building. The study was conducted to describe the facts of the building as well as direct observation to the research location. The collected data is then processed using the AHP (Analytical Hierarchy Process) method in its weighting process to obtain the reliability value of passive fire protection fire system. The results showed that there are some components of passive fire protection system in the building, but some are still unqualified. The first section in your paper

  14. Appraisal of Passive and Active Fire Protection Systems in Student’s Accommodation

    Directory of Open Access Journals (Sweden)

    Ismail I.

    2014-03-01

    Full Text Available Fire protection systems are very important systems that must be included in buildings. They have a great significance in reducing or preventing the occurrences of fire. This paper presents an assessment of fire protection systems in student’s accommodation. Student accommodation is a particular type of building that provides shelter for students at University. In addition, it is also supposed to be an attractive environment, conducive to learning, and importantly, safe for occupation. The fire safety of occupants in a building, must be in accordance with the requirements of the building’s code. Therefore, the design of the building must comply with the Uniform Building By-Law (UBBL 1984 of Malaysia, and provide all of the required safety features. This paper describes the findings from investigations of passive and active fire protection systems installed in buildings, based on fire safety requirements, UBBL (1984.

  15. Performance of a Protected Wireless Sensor Network in a Fire. Analysis of Fire Spread and Data Transmission

    Science.gov (United States)

    Antoine-Santoni, Thierry; Santucci, Jean-François; de Gentili, Emmanuelle; Silvani, Xavier; Morandini, Frederic

    2009-01-01

    The paper deals with a Wireless Sensor Network (WSN) as a reliable solution for capturing the kinematics of a fire front spreading over a fuel bed. To provide reliable information in fire studies and support fire fighting strategies, a Wireless Sensor Network must be able to perform three sequential actions: 1) sensing thermal data in the open as the gas temperature; 2) detecting a fire i.e., the spatial position of a flame; 3) tracking the fire spread during its spatial and temporal evolution. One of the great challenges in performing fire front tracking with a WSN is to avoid the destruction of motes by the fire. This paper therefore shows the performance of Wireless Sensor Network when the motes are protected with a thermal insulation dedicated to track a fire spreading across vegetative fuels on a field scale. The resulting experimental WSN is then used in series of wildfire experiments performed in the open in vegetation areas ranging in size from 50 to 1,000 m2. PMID:22454563

  16. An Implementing Strategy for Improving Wildland Fire Environmental Literacy

    Science.gov (United States)

    McCalla, M. R.; Andrus, D.; Barnett, K.

    2007-12-01

    ). The OFCM model for promoting wildland fire environmental literacy, the model's component parts, as well as an implementing strategy to execute the model will be presented. That is, the presentation will lay out the framework and methodology which the OFCM used to systematically define the wildland fire weather and climate education and outreach needs through interdepartmental collaboration within the OFCM coordinating infrastructure. A key element of the methodology is to improve the overall understanding and use of wildland fire forecast and warning climate and weather products and to exploit current and emerging technologies to improve the dissemination of customer-tailored forecast and warning information and products to stakeholders and users. Thus, the framework and methodology define the method used to determine the target public, private, and academic sector audiences. The methodology also identifies the means for determining the optimal channels, formats, and content for informing end users in time for effective action to be taken.

  17. Fire protection and safety in working with sodium. Pt. 2

    International Nuclear Information System (INIS)

    Foerster, K.; Kremer, K.H.; Wolf, J.

    1978-01-01

    The use of sodium as a heat transfer medium in nuclear plant and the associated development of sodium technology caused the requirement for adapting fire and safety precautions to new conditions of dealing with this liquid. The comparison in the first part of this article of the properties of sodium with those of petrol clarified the different fire characteristics of sodium compared to many other combustible materials and the effects of fires which differ from conventional fires. Based on this, measures for fire precautions and for safety of personnel are introduced. (orig.) [de

  18. Nuclear power plant fire protection: philosophy and analysis

    International Nuclear Information System (INIS)

    Berry, D.L.

    1980-05-01

    This report combines a fire severity analysis technique with a fault tree methodology for assessing the importance to nuclear power plant safety of certain combinations of components and systems. Characteristics unique to fire, such as propagation induced by the failure of barriers, have been incorporated into the methodology. By applying the resulting fire analysis technique to actual conditions found in a representative nuclear power plant, it is found that some safety and nonsafety areas are both highly vulnerable to fire spread and impotant to overall safety, while other areas prove to be of marginal importance. Suggestions are made for further experimental and analytical work to supplement the fire analysis method

  19. Fire protection devices in the controlled region of GKN nuclear power station

    International Nuclear Information System (INIS)

    Bernhardt, S.; Grauf, E.

    1976-01-01

    In the GKN nuclear power station ('Neckar reactor'), an 805 MW PWR reactor whose start-up is scheduled for the near future, fire protection measures have been realized that go far beyond those realized in other German nuclear power stations until now. One of the main reasons is that the authorities have been sensibilized by a fire in the refuelling cavity during construction and by the Browns Ferry fire and are therefore extremely thorough in their examination. Further subsections have been added to the fire prevention sections in order to provide better quenching devices for potential fire sites. (orig./AK) [de

  20. Fire protection equipment in the area of control of the Neckar Community Nuclear Power Station

    International Nuclear Information System (INIS)

    Bernhardt, S.; Grauf, E.

    1976-01-01

    In the Neckar Community Nuclear Power Station - an 805 MW pressurised water reactor shortly to reach the stage of nuclear operation - fire protection measures have been realised to an extent hitherto uncommon in German nuclear power plants. The reason is to be sought from the authorities who have become more sensitive because of a fire in a reactor vessel during the construction stage and the fire at Browns Ferry and have consequently become extremely expert. Apart from the fire regulations hitherto normal further subregulations have been created in order to be able to make better provision of extinguishing devices against fire hazards. (orig.) [de

  1. Numerical case studies of vertical wall fire protection using water spray

    Directory of Open Access Journals (Sweden)

    L.M. Zhao

    2014-11-01

    Full Text Available Studies of vertical wall fire protection are evaluated with numerical method. Typical fire cases such as heated dry wall and upward flame spread have been validated. Results predicted by simulations are found to agree with experiment results. The combustion behavior and flame development of vertical polymethylmethacrylate slabs with different water flow rates are explored and discussed. Water spray is found to be capable of strengthening the fire resistance of combustible even under high heat flux radiation. Provided result and data are expected to provide reference for fire protection methods design and development of modern buildings.

  2. Deformation and Heat Transfer on Three Sides Protected Beams under Fire Accident

    Science.gov (United States)

    Imran, M.; Liew, M. S.; Garcia, E. M.; Nasif, M. S.; Yassin, A. Y. M.; Niazi, U. M.

    2018-04-01

    Fire accidents are common in oil and gas industry. The application of passive fire protection (PFP) is a costly solution. The PFP is applied only on critical structural members to optimise project cost. In some cases, beams cannot be protected from the top flange in order to accommodate for the placement of pipe supports and grating. It is important to understand the thermal and mechanical response of beam under such condition. This paper discusses the response of steel beam under ISO 834 fire protected, unprotected and three sides protected beams. The model validated against an experimental study. The experimental study has shown good agreement with FE model. The study revealed that the beams protected from three sides heat-up faster compare to fully protected beam showing different temperature gradient. However, the affects load carrying capacity are insignificant under ISO 834 fire.

  3. Studying the Post-Fire Response of Vegetation in California Protected Areas with NDVI-based Pheno-Metrics

    Science.gov (United States)

    Jia, S.; Gillespie, T. W.

    2016-12-01

    Post-fire response from vegetation is determined by the intensity and timing of fires as well as the nature of local biomes. Though the field-based studies focusing on selected study sites helped to understand the mechanisms of post-fire response, there is a need to extend the analysis to a broader spatial extent with the assistance of remotely sensed imagery of fires and vegetation. Pheno-metrics, a series of variables on the growing cycle extracted from basic satellite measurements of vegetation coverage, translate the basic remote sensing measurements such as NDVI to the language of phenology and fire ecology in a quantitative form. In this study, we analyzed the rate of biomass removal after ignition and the speed of post-fire recovery in California protected areas from 2000 to 2014 with USGS MTBS fire data and USGS eMODIS pheno-metrics. NDVI drop caused by fire showed the aboveground biomass of evergreen forest was removed much slower than shrubland because of higher moisture level and greater density of fuel. In addition, the above two major land cover types experienced a greatly weakened immediate post-fire growing season, featuring a later start and peak of season, a shorter length of season, and a lower start and peak of NDVI. Such weakening was highly correlated with burn severity, and also influenced by the season of fire and the land cover type, according to our modeling between the anomalies of pheno-metrics and the difference of normalized burn ratio (dNBR). The influence generally decayed over time, but can remain high within the first 5 years after fire, mostly because of the introduction of exotic species when the native species were missing. Local-specific variables are necessary to better address the variance within the same fire and improve the outcomes of models. This study can help ecologists in validating the theories of post-fire vegetation response mechanisms and assist local fire managers in post-fire vegetation recovery.

  4. Development of fire protection standards for the EPR project

    International Nuclear Information System (INIS)

    Frank, H.J.; Kaercher, M.; Wittmann, R.

    2000-01-01

    In 1989 Framatome and Siemens decided by setting up their joint subsidiary NPI (Nuclear Power International) to co-operate in designing a new European Pressurised Water Reactor, the EPR. French and German utilities decided to participate in this project. In parallel to the co-operation on supplier's and utility's side, the French and German safety authorities and safety experts wanted to work closely together in order to harmonise and further develop the outstanding safety standards in France and Germany. An organisation has been set up to elaborate common codes related to the EPR design, at the level of the French design and construction rules (RCC) of the German KTA safety standards and DIN standards for nuclear technology, the so-called EPR technical codes (ETC). In this context the decision was made to develop a new fire protection code, the ETC-F, which should be harmonised between France and Germany. The article gives an insight in the developing process of the ETC-F and an outlook on existing and perhaps further national activities. (orig.) [de

  5. Fire-Protection Research for Energy-Technology Projects: FY 1981 year-end report

    International Nuclear Information System (INIS)

    Hasegawa, H.K.; Alvares, N.J.; Lipska-Quinn, A.E.; Beason, D.G.; Foote, K.L.; Priante, S.J.

    1982-01-01

    This report summarizes research conducted in fiscal year 1981 for the DOE-supported project, Fire Protection Research for Energy Technology Projects. Initiated in 1977, this ongoing research program was conceived to advance fire protection strategies for Energy Technology Projects to keep abreast of the unique fire problems that are developing with the complexity of energy technology research. We are developing an analytical methodology through detailed study of fusion energy experiments at Lawrence Livermore National Laboratory (LLNL). Employing these facilities as models for methodology development, we are simultaneously advancing three major task areas: (1) determination of unique fire hazards of current fusion energy facilities; (2) evaluation of the ability of accepted fire management measures to meet and negate hazards; and (3) performance of unique research into problem areas we have identified to provide input into analytical fire-growth and damage-assessment models

  6. Fire-Protection Research for Energy-Technology Projects: FY 1981 year-end report

    Energy Technology Data Exchange (ETDEWEB)

    Hasegawa, H.K.; Alvares, N.J.; Lipska-Quinn, A.E.; Beason, D.G.; Foote, K.L.; Priante, S.J.

    1982-07-20

    This report summarizes research conducted in fiscal year 1981 for the DOE-supported project, Fire Protection Research for Energy Technology Projects. Initiated in 1977, this ongoing research program was conceived to advance fire protection strategies for Energy Technology Projects to keep abreast of the unique fire problems that are developing with the complexity of energy technology research. We are developing an analytical methodology through detailed study of fusion energy experiments at Lawrence Livermore National Laboratory (LLNL). Employing these facilities as models for methodology development, we are simultaneously advancing three major task areas: (1) determination of unique fire hazards of current fusion energy facilities; (2) evaluation of the ability of accepted fire management measures to meet and negate hazards; and (3) performance of unique research into problem areas we have identified to provide input into analytical fire-growth and damage-assessment models.

  7. Fire protection research for DOE facilities: FY 83 year-end report

    International Nuclear Information System (INIS)

    Hasegawa, H.K.; Alvares, N.J.; Lipska-Quinn, A.E.; Beason, D.G.; Foote, K.L.; Priante, S.J.; Stagge, K.

    1984-01-01

    We summarize our research in FY 83 for the DOE-sponsored project, Fire Protection Research for DOE Facilities. This research program was initiated in 1977 to advance fire-protection strategies of energy technology facilities in order to keep abreast of the unique fire problems that develop along with energy technology research. Since 1977, the program has broadened its original scope, as reflected in previous year-end reports. We are developing an analytical methodology through detailed study of fusion energy experiments at Lawrence Livermore National Laboratory (LLNL). Using these experiments as models for methodology development, we are currently advancing three major task areas: (1) the identification of fire hazards unique to fusion energy facilities, (2) the evaluation of accepted fire-management measures to meet the negate hazards, and (3) the performance of unique research into problem areas we have identified to provide input into analytical fire-growth and damage-assessment models

  8. Fire-protection research for DOE facilities: FY 82 year-end report

    International Nuclear Information System (INIS)

    Hasegawa, H.K.; Alvares, N.J.; Lipska-Quinn, A.E.; Beason, D.G.; Priante, S.J.; Foote, K.L.

    1983-01-01

    We summarize our research in FY 82 for the DOE-sponsored project, Fire Protection Research for DOE Facilities. This research program was initiated in 1977 to advance fire-protection strategies for energy technology facilities to keep abreast of the unique fire problems that develop along with energy technology research. Since 1977, the program has broadened its original scope, as reflected in previous year-end reports. We are developing an analytical methodology through detailed study of fusion energy experiments at Lawrence Livermore National Laboratory (LLNL). Using these experiments as models for methodology development, we are concurrently advancing three major task areas: (1) the identification of fire hazards unique to current fusion energy facilities; (2) the evaluation of accepted fire-management measures to meet and negate hazards; and (3) the performance of unique research into problem areas we have identified to provide input into analytical fire-growth and damage-assessment models

  9. Industrial safety and fire protection during the construction phase

    International Nuclear Information System (INIS)

    Zimmer, K.

    1977-01-01

    The questions and problems of industrial safety and fire prevention have to be treated like the activities planning, developing, assembly, etc. This statement is illustrated by statistics of the fire insurance companies, from which it can be seen that the number of fire accidents has decreased but that the damage caused has greatly increased. The sooner the fire prevention and industrial safety measures are integrated in the planning phase, the better for the total costs. Preventive measures that possibly have to be introduced at a later stage are not only generally much more expensive but are also seldom as effective. (orig./HK) [de

  10. Advances in safety countermeasures at the Tomari NPP of Hokkaido Electric Power on the basis of Fukushima Daiichi NPP accident. Fire protection and other advances

    International Nuclear Information System (INIS)

    Shibata, Taku; Dasai, Katsumi

    2014-01-01

    Fire protections for the nuclear power plants have been based on the fire laws and the conventional guide. After Fukushima Daiichi NPP accident, many safety countermeasures - also about Fire Protection - have been discussed in the Japanese authorities. This paper shows our present activities in the Tomari NPP about the fire protections from the view points of Fire Prevention, Fire Detection/Suppression Systems and Fire Protection, and other advances. (author)

  11. Summary of fire protection programs of the United States Department of Energy

    International Nuclear Information System (INIS)

    1991-10-01

    This edition of the Annual Summary of DOE Fire Protection Programs continues the series started in 1972. Since May 1950, an annual report has been required from each field organization. The content has varied through the years and most of the accident data reporting requirements have been superseded by the Computerized Accident/Incident Reporting System administered by EG ampersand G, Idaho. However, this report is the sole source of information relating to fire protection programs, and to the actions of the field offices and to headquarters that are of general fire protection interest

  12. Ceramic fiber blanket wrap for fire protection of cable trays and conduits

    International Nuclear Information System (INIS)

    Chaille, C.E.; Reiman, R.J.

    1980-01-01

    In some areas of nuclear power plants, cables of redundant electrical systems, which are necessary for the safe shutdown of the reactor, are in close proximity. If a fire should occur in one of these areas, both electrical systems could be destroyed before the fire is extinguished and control of the reactor may be lost. A ceramic fiber blanket was evaluated as a fire protective wrap around cable trays and conduits. 2 refs

  13. 14 CFR 121.308 - Lavatory fire protection.

    Science.gov (United States)

    2010-01-01

    ... operate a passenger-carrying airplane unless each lavatory in the airplane is equipped with a smoke...-carrying airplane unless each lavatory in the airplane is equipped with a built-in fire extinguisher for each disposal receptacle for towels, paper, or waste located within the lavatory. The built-in fire...

  14. 14 CFR 23.865 - Fire protection of flight controls, engine mounts, and other flight structure.

    Science.gov (United States)

    2010-01-01

    ... 14 Aeronautics and Space 1 2010-01-01 2010-01-01 false Fire protection of flight controls, engine... controls, engine mounts, and other flight structure. Flight controls, engine mounts, and other flight... they are capable of withstanding the effects of a fire. Engine vibration isolators must incorporate...

  15. Risk reduction in road and rail LPG transportation by passive fire protection

    NARCIS (Netherlands)

    Paltrinieri, N.; Landucci, G.; Molag, M.; Bonvicini, S.; Spadoni, G.; Cozzani, V.

    2009-01-01

    The potential reduction of risk in LPG (Liquefied Petroleum Gas) road transport due to the adoption of passive fire protections was investigated. Experimental data available for small scale vessels fully engulfed by a fire were extended to real scale road and rail tankers through a finite elements

  16. Recommendations for ionization chamber smoke detectors for commercial and industrial fire protection systems (1988)

    International Nuclear Information System (INIS)

    1989-01-01

    Ionization chamber smoke detectors (ICSDs) utilising a radioactive substance as the source of ionization are used to detect the presence of smoke and hence give early warning of a fire. These recommendations are intended to ensure that the use of ICSDs incorporating radium-226 and americium-241 in commercial/industrial fire protection systems does not give rise to any unnecessary radiation exposure

  17. 76 FR 70413 - National Fire Protection Association (NFPA): Request for Comments on NFPA's Codes and Standards

    Science.gov (United States)

    2011-11-14

    ... Private Fire Protection. P NFPA 36 Standard for Solvent Extraction Plants P NFPA 52 Vehicular Gaseous Fuel Systems Code P NFPA 67 Guideline on Explosion Protection for Gaseous N Mixtures in Pipe Systems. NFPA 68 Standard on Explosion Protection by Deflagration P Venting. NFPA 70B Recommended Practice for Electrical...

  18. Protection against fire and high temperature by using porous media and water

    International Nuclear Information System (INIS)

    Yano, T.; Ochi, M.; Snya, S.

    1991-01-01

    In this paper the protection method against the fire and high temperature under the disaster environments is developed and examined by utilizing the transpiration cooling to maintain the objectives at the room temperature. A room model installed by thermal protection panel for security heaven to which the people are able to escape from the fire in safety. The cooling structure is mainly composed of porous media which is made by thin ceramic paper, and the reinforced ceramic paper. The experimental verification of the room and cable models shows that the thermal protection by transpiration of water have good ability to keep inside at the room temperature even if in the violent fire. It is also clarified that the thermal protection technology by transpiration is expective to defend the room, building, cable, safety equipment, information system and etc., from the fire

  19. Modeling the protection afforded by burrows, cavities, and roosts during wildland surface fires

    Science.gov (United States)

    Anthony Bova; Matthew Dickinson

    2009-01-01

    Wildland surface fires produce many toxic and irritating compounds, such as formaldehyde and acrolein, and harmful gases such as carbon monoxide. Several factors influence the degree of protection offered by animal shelters against combustion products and heat.

  20. Upgrading and efficiency improvement in coal-fired power plants

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2013-08-01

    Improving the efficiencies of the large number of older coal-fired power plants operating around the world would give major savings in CO2 emissions together with significant other benefits. This report begins with a summary of the ways efficiency can become degraded and of the means available to combat the decrease in performance. These include improvements to operating and maintenance practices and more major techniques that are available, including boiler and turbine retrofits. There is also an update on fuel drying developments as a route to higher efficiency in plants firing high moisture lignites. The largest chapter of the report contains a number of descriptions of case study improvement projects, to illustrate measures that have been applied, benefits that have been achieved and identify best practices, which are summarised. Major national and international upgrading programmes are described.

  1. 14 CFR 23.1359 - Electrical system fire protection.

    Science.gov (United States)

    2010-01-01

    ... procedures must be fire-resistant. (c) Insulation on electrical wire and electrical cable must be self... this part, or other approved equivalent methods. The average burn length must not exceed 3 inches (76...

  2. Water Supply Systems For Aircraft Fire And Rescue Protection

    Science.gov (United States)

    1995-01-01

    This Advisory Circular (AC) provides guidance for the selection : of a water source and standards for the design of a distribution system to : support aircraft rescue and fire fighting (ARFF) service operations on : airports.

  3. Protection against fire hazards in French nuclear power plants

    International Nuclear Information System (INIS)

    Chapus, J.

    2000-01-01

    The prevention of fire in French nuclear power plants has followed the evolution of safety regulations. Today fire hazards are no longer considered as classical industrial risks but as specific risks that deserve to be studied thoroughly and in a more formalized form. In the beginning of the eighties EDF was committed to the redaction of a technical referential against fire gathering all the directives applicable to the N4-type plant (1450 MW). In 1994 this technical referential was reconsidered and enlarged in order to involve 900 MW and 1300 MW units. In each nuclear power plant a PAI (plan against fire) has been elaborated so that the installation can be progressively upgraded according to the last standard defined by the technical referential. (A.C.)

  4. Action taken by the french safety authorities for fire protection and fire fighting in basic nuclear plants

    International Nuclear Information System (INIS)

    Savornin, J.; Gibault, M.; Berger, R.; Kaluzny, Y.; Wallard, H.E.; Winter, D.

    1989-03-01

    The safety goal for nuclear installations is to prevent the dispersal of radioactive substances, both in the work area and outside the buildings into the environment. It is therefore at the design stage, then during construction and subsequent operation that it is necessary to take preventive measures against the outbreak of fire, and to take precautions to ensure that the consequences will always be limited. The paper describes the arrangements made by the French safety authorities to provide protection against fire in both nuclear plants and nuclear fuel cycle installations at all these stages

  5. Fire protection research for energy technology projects; FY 79 year-end report

    International Nuclear Information System (INIS)

    Hasegawa, H.K.; Alvares, N.J.; Lipska, A.E.; Ford, H.; Beason, D.G.

    1981-01-01

    This report describes work performed in fiscal year 1979, on a DOE funded study entitled Fire Protection Research for Energy Technology Projects. The primary goal of this program is to ensure that fire protection measures for Fusion Energy Experiments (FEE) evolve concurrently with the complexity of FEE. Ultimately, it is planned that the detailed study of fusion experiments will provide an analytical methodology which can be applied to the full range of energy technology projects. We attempt to achieve this objective by coordinately advancing 3 (three) major task areas; (a) determine the fire hazards of current FEE facilities (b) assess the ability of accepted fire management strategies to meet and negate the hazard, (c) perform unique research into problem areas we have identified to provide input into analytical fire growth and damage assessment models

  6. Fires in refugee and displaced persons settlements: The current situation and opportunities to improve fire prevention and control.

    Science.gov (United States)

    Kazerooni, Yasaman; Gyedu, Adam; Burnham, Gilbert; Nwomeh, Benedict; Charles, Anthony; Mishra, Brijesh; Kuah, Solomon S; Kushner, Adam L; Stewart, Barclay T

    2016-08-01

    We aimed to describe the burden of fires in displaced persons settlements and identify interventions/innovations that might address gaps in current humanitarian guidelines. We performed a systematic review of: (i) academic and non-academic literature databases; and (ii) guidelines from leading humanitarian agencies/initiatives regarding fire prevention/control. Of the 1521 records retrieved, 131 reports described settlement fires in 31 hosting countries since 1990. These incidents resulted in 487 deaths, 790 burn injuries, displacement of 382,486 individuals and destruction of 50,509 shelters. There was a 25-fold increase in the rate of settlement fires from 1990 to 2015 (0.002-0.051 per 100,000 refugees, respectively). Only 4 of the 15 leading humanitarian agencies provided recommendations about fire prevention/control strategies. Potentially useful interventions/innovations included safer stoves (e.g. solar cookers) and fire retardant shelter materials. The large and increasing number of fires in displaced persons settlements highlights the need to redress gaps in humanitarian fire prevention/control guidelines. The way forward includes: (i) developing consensus among aid agencies regarding fire prevention/control strategies; (ii) evaluating the impact of interventions/innovations on the burden of fires; and (iii) engaging agencies in a broader discussion about protecting camp residents from armed groups. Copyright © 2015 Elsevier Ltd and ISBI. All rights reserved.

  7. Design criteria document, Fire Protection Task, K Basin Essential Systems Recovery, Project W-405

    International Nuclear Information System (INIS)

    Johnson, B.H.

    1994-01-01

    The K Basin were constructed in the early 1950's with a 20 year design life. The K Basins are currently in their third design life and are serving as a near term storage facility for irradiated N Reactor fuel until an interim fuel storage solution can be implemented. In April 1994, Project W-405, K Basin Essential Systems Recovery, was established to address (among other things) the immediate fire protection needs of the 100K Area. A Fire Barrier Evaluation was performed for the wall between the active and inactive areas of the 105KE and 105KW buildings. This evaluation concludes that the wall is capable of being upgraded to provide an equivalent level of fire resistance as a qualified barrier having a fire resistance rating of 2 hours. The Fire Protection Task is one of four separate Tasks included within the scope of Project W405, K Basin Essential systems Recovery. The other three Tasks are the Water Distribution System Task, the Electrical System Task, and the Maintenance Shop/Support Facility Task. The purpose of Project W-405's Fire Protection Task is to correct Life Safety Code (NFPA 101) non-compliances and to provide fire protection features in Buildings 105KE, 105KW and 190KE that are essential for assuring the safe operation and storage of spent nuclear fuel at the 100K Area Facilities' Irradiated Fuel Storage Basins (K Basins)

  8. Management impacts on fire occurrence: A comparison of fire regimes of African and South American tropical savannas in different protected areas.

    Science.gov (United States)

    Alvarado, Swanni T; Silva, Thiago Sanna Freire; Archibald, Sally

    2018-07-15

    Humans can alter fire dynamics in grassland systems by changing fire frequency, fire seasonality and fuel conditions. These changes have effects on vegetation structure and recovery, species composition, and ecosystem function. Understanding how human management can affect fire regimes is vital to detect potential changes in the resilience of plant communities, and to predict vegetation responses to human interventions. We evaluated the fire regimes of two recently protected areas in Madagascar (Ibity and Itremo NPA) and one in Brazil (Serra do Cipó NP) before and after livestock exclusion and fire suppression policies. We compare the pre- and post-management fire history in these areas and analyze differences in terms of total annual burned area, density of ignitions, burn scar size distribution, fire return period and seasonal fire distribution. More than 90% of total park areas were burned at least once during the studied period, for all parks. We observed a significant reduction in the number of ignitions for Ibity NPA and Serra do Cipó NP after livestock exclusion and active fire suppression, but no significant change in total burned area for each protected area. We also observed a seasonal shift in burning, with fires happening later in the fire season (October-November) after management intervention. However, the protected areas in Madagascar had shorter fire return intervals (3.23 and 1.82 years) than those in Brazil (7.91 years). Our results demonstrate that fire exclusion is unattainable, and probably unwarranted in tropical grassland conservation areas, but show how human intervention in fire and vegetation patterns can alter various aspects of the fire regimes. This information can help with formulating realistic and effective fire management policies in these valuable conservation areas. Copyright © 2018 Elsevier Ltd. All rights reserved.

  9. Defence-in-depth strategy of fire protection and its relevance after final shutdown (by the example of Germany)

    Energy Technology Data Exchange (ETDEWEB)

    Beesen, Michael; Ernst, Benjamin; Fischer, Guenter [TUeV SUeD Industrie Service GmbH (Germany)

    2015-12-15

    Nuclear power plants (NPP) are protected against internal and external fires by a fire protection defence-in-depth concept including the following precautionary measures: operational, structural and equipment related fire protection measures as well as manual fire fighting. The fire protection measures are designed in consideration of fires to be expected (from fire loads permanently and temporarily present together with potential ignition sources) in order to prevent a violation of both the protection goals of public law and the nuclear protection goals / radiological safety objectives in case of internal and external fires. The aspect ''What is the future significance of the fire protection defence-in-depth concept?'' needs to be considered with regard to the situation following the final shutdown. From our point of view as a TSO (technical safety organization) both the non-nuclear protection goals (e.g. prevent occurrence of a fire; ensure escape and rescue of humans) as well as the nuclear ones have to be ensured after final shutdown of a nuclear plant. The protection goals of public law will almost completely remain after the plant has stopped commercial operation while the nuclear safety objectives will be stepwise reduced in consideration of the decommissioning status until the end of the nuclear supervision. Nevertheless, the fire protection concept must clearly specify those fire protection measures that are necessary to ensure the plants' safety. The situation on site regularly needs to be under examination to check if the fire protection concept covers all conditions to be considered and if the existing fire protection measures are sufficient or if an adaption is necessary.

  10. Current trends towards a new regulation and evolution of fire protection systems technologies in nuclear power plants

    International Nuclear Information System (INIS)

    Rodriguez Sanjuan, G.

    1996-01-01

    For some time now, the field of Fire Protection in Nuclear Power Plants has, with its own peculiarities in an otherwise general process, been the centre of some controversy caused by tendencies to reduce regulatory inflexibility by transforming what was originally a prescriptive, pro grammatical and deterministic regulatory system into a system based on risk assessment and operating experience. Such tendencies include: Cost Beneficial Licensing Actions (CBLA) Use of the Probabilistic Safety Analysis (PSA) as a tool for evaluating the impact of postulated fires in nuclear safety Improvement of communications between the regulatory body and the industry These trends have coincided with the arduous process of requalifying passive fire-resistant protection materials, such as Thermo lag and others, which are used to separate redundant Safe Shutdown trains with fire-resistance ranges of one (1) hour or three (3) hours, in compliance with some of the alternatives that Appendix R to 10 CFR 50 offers. The process has involved a lot of effort and financial cost in requalification and in employing compensatory measures until operability of the fire-resistant materials is reestablished. A new test methodology has been created for these barriers (GL 86-10, Supplement 1) and new materials have become available and are currently undergoing qualification. (Author)

  11. Fire protection requirements of the insurance industry and their impact on nuclear power plant design and construction

    International Nuclear Information System (INIS)

    Deitchman, J.V.; King, W.T. Jr.; Nashman, T.A.

    1976-01-01

    The insurance industry, with its wealth of knowledge and experience in the fire protection area and with preservation of its funds at stake, has always been heavily involved in the fire protection programs of nuclear power plants. Since it was concerned with property preservation in addition to nuclear safety, the insurance industry placed more detailed emphasis on fire protection requirements than did the nuclear regulatory bodies. Since the Browns Ferry fire, however, the insurance industry, the Nuclear Regulatory Commission, the Advisory Committee on Reactor Safeguards and the utilities themselves have re-examined their approaches to fire protection. A more coordinated approach seems to have emerged, which is based largely upon insurance industry specifications and guidelines. The paper briefly summarizes the fire protection requirements of the insurance industry as they apply to nuclear power plants. Some of the ways these requirements affect project planning, plant design, and construction timing are reviewed, as well as some of the more controversial fire protection areas

  12. Project 93L-EWL-097, fire alarm system improvements, 300 Area

    International Nuclear Information System (INIS)

    Scott, M.V.

    1995-01-01

    This document contains the Acceptance Test Procedure (ATP) which will demonstrate that the modifications to the Fire Protection systems in the 338 Building function as intended. The ATP will test the fire alarm control panel, flow alarm pressure switch, post indicator valve tamper switch, heat detectors, flow switches, and fire alarm signaling devices

  13. Efficacy of water spray protection against propane and butane jet fires impinging on LPG storage tanks

    Energy Technology Data Exchange (ETDEWEB)

    Shirvill, L.C. [Shell Global Solutions (UK), Chester (United Kingdom)

    2004-03-01

    Liquefied petroleum gas (LPG) storage tanks are often provided with water sprays to protect them in the event of a fire. This protection has been shown to be effective in a hydrocarbon pool fire but uncertainties remained regarding the degree of protection afforded in a jet fire resulting from a liquid or two-phase release of LPG. Two projects, sponsored by the Health and Safety Executive, have been undertaken to study, at full scale, the performance of a water spray system on an empty 13 tonne LPG vessel under conditions of jet fire impingement from nearby releases of liquid propane and butane. The results showed that a typical water deluge system found on an LPG storage vessel cannot be relied upon to maintain a water film over the whole vessel surface in an impinging propane or butane jet fire scenario. The deluge affects the fire itself, reducing the luminosity and smoke, resulting in a lower rate of wall temperature rise at the dry patches, when compared with the undeluged case. The results of these studies will be used by the HSE in assessing the risk of accidental fires on LPG installations leading to boiling liquid expanding vapour explosion (BLEVE) incidents. (Author)

  14. Methods and criteria for evaluation of nuclear reactor fire protection alternatives and modifications

    International Nuclear Information System (INIS)

    Levinson, S.H.

    1982-01-01

    The objective of this work is to develop a methodology for the evaluation of a fire protection system in a nuclear power plant and demonstrate the feasibility of encoding this method in a computer program. A Monte Carlo simulation has been developed; it is divided into the four phases of a fire scenario: ignition, detection, suppression and propagation. The ignition model consists of probabilistically determining at what location within the zone a fire will occur. The detection model is divided into two components. THe first is the automatic detection model, which calculates the fire's physical symptoms and compares them against the threshold values of the detectors specified for the zone to determine a time-to-detection. The second part is the human detection model; this evaluates the time required for a human to observe and report a fire. If detection is successful, the suppression mode determines if the fire is effectively extinguished, and if so, the time required to do so. This model is also divided into an automatic and human component. The propagation model is embedded in a deterministic, control-volume computer code which calculates the fire scenario history. A computer program, FIRES, is described which supports the developed models. FIRES is an interactive graphics package providing a simple means of establishing the many input parameters. In addition to allowing parameter values to be easily set or modified, the graphics provides a convenient display mode for the results of a simulation

  15. Fire ants protect mealybugs against their natural enemies by utilizing the leaf shelters constructed by the leaf roller Sylepta derogata.

    Directory of Open Access Journals (Sweden)

    Aiming Zhou

    Full Text Available The importance of mutualism is receiving more attention in community ecology. In this study, the fire ant Solenopsis invicta was found to take advantage of the shelters constructed by the leaf roller Sylepta derogata to protect mealybugs (Phenacoccus solenopsis against their natural enemies. This protective effect of fire ant tending on the survival of mealybugs in shelters was observed when enemies and leaf rollers were simultaneously present. Specifically, fire ants moved the mealybugs inside the shelters produced by S. derogata on enemy-infested plants. Compared with that in plants without ants, the survival of mealybugs in shelters in the presence of natural enemies in plants with ants markedly improved. Both the protection of ants and the shelters provided by leaf rollers did not affect the survival of mealybugs in the absence of enemies in plants. Ants and leaf rollers significantly improved the survival of mealybugs in predator-infested plants, whereas no such improvement was observed in parasitoid-infested ones.

  16. Unified Facilities Criteria (UFC) Design: Fire Protection Engineering for Facilities

    Science.gov (United States)

    2003-08-20

    following provisions: • Ceiling sprinkler design area must be increased by 10 percent. ESFR sprinklers must increase the required number to be...Control System ESFR Early Suppression Fast-Response Sprinklers ETL Engineering Technical Letters FAAA Fire Administration Authorization Act FM

  17. 30 CFR 77.1100 - Fire protection; training and organization.

    Science.gov (United States)

    2010-07-01

    ....1100 Section 77.1100 Mineral Resources MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR COAL MINE SAFETY AND HEALTH MANDATORY SAFETY STANDARDS, SURFACE COAL MINES AND SURFACE WORK AREAS OF... facilities and equipment shall be provided commensurate with the potential fire hazards at each structure...

  18. 14 CFR 125.175 - Protection of other airplane components against fire.

    Science.gov (United States)

    2010-01-01

    ... 14 Aeronautics and Space 3 2010-01-01 2010-01-01 false Protection of other airplane components... CERTIFICATION AND OPERATIONS: AIRPLANES HAVING A SEATING CAPACITY OF 20 OR MORE PASSENGERS OR A MAXIMUM PAYLOAD... Requirements § 125.175 Protection of other airplane components against fire. (a) Except as provided in...

  19. 14 CFR 121.277 - Protection of other airplane components against fire.

    Science.gov (United States)

    2010-01-01

    ... 14 Aeronautics and Space 3 2010-01-01 2010-01-01 false Protection of other airplane components....277 Protection of other airplane components against fire. (a) Except as provided in paragraph (b) of this section, all airplane surfaces aft of the nacelles in the area of one nacelle diameter on both...

  20. A conceptual framework for formulating a focused and cost-effective fire protection program based on analyses of risk and the dynamics of fire effects

    International Nuclear Information System (INIS)

    Dey, M.K.

    1999-01-01

    This paper proposes a conceptual framework for developing a fire protection program at nuclear power plants based on probabilistic risk analysis (PRA) of fire hazards, and modeling the dynamics of fire effects. The process for categorizing nuclear power plant fire areas based on risk is described, followed by a discussion of fire safety design methods that can be used for different areas of the plant, depending on the degree of threat to plant safety from the fire hazard. This alternative framework has the potential to make programs more cost-effective, and comprehensive, since it will allow a more systematic and broader examination of fire risk, and provide a means to distinguish between high and low risk fire contributors. (orig.)

  1. Improved fire retardancy of thermoset composites modified with carbon nanofibers

    International Nuclear Information System (INIS)

    Zhao Zhongfu; Gou Jan

    2009-01-01

    Multifunctional thermoset composites were made from polyester resin, glass fiber mats and carbon nanofiber sheets (CNS). Their flaming behavior was investigated with cone calorimeter under well-controlled combustion conditions. The heat release rate was lowered by pre-planting carbon nanofiber sheets on the sample surface with the total fiber content of only 0.38 wt.%. Electron microscopy showed that carbon nanofiber sheet was partly burned and charred materials were formed on the combusting surface. Both the nanofibers and charred materials acted as an excellent insulator and/or mass transport barrier, improving the fire retardancy of the composite. This behavior agrees well with the general mechanism of fire retardancy in various nanoparticle-thermoplastic composites.

  2. Connective Heating Improvement for Emergency Fire Shelters (CHIEFS): Composition and Performance of Fire Shelter Concepts at Close-Out

    Science.gov (United States)

    Fody, Joshua M.; Daryabeigi, Kamran; Bruce, Walter E., III; Wells, John M.; Wusk, Mary E.; Calomino, Anthony M.; Miller, Steve D.

    2018-01-01

    Summary of highlights of the Convective Heating Improvement for Emergency Fire Shelters (CHIEFS) taskunder NASA. CHIEFS was tasked with providing the US Forest Service with an emergency fire shelter forimproved resistance to flame contact. Emphasis is on the final shelter designs at task close-out (end of FY17).

  3. Sevoflurane improves gaseous exchange and exerts protective ...

    African Journals Online (AJOL)

    Sevoflurane improves gaseous exchange and exerts protective effects in ... Lung water content and cell count were estimated by standard protocols. ... It reversed LPS-induced oxidative stress, as demonstrated by increase in total antioxidant ...

  4. New fire diurnal cycle characterizations to improve fire radiative energy assessments made from MODIS observations

    NARCIS (Netherlands)

    Andela, N.; Kaiser, J.; van der Werf, G.R.

    2015-01-01

    Accurate near real time fire emissions estimates are required for air quality forecasts. To date, most approaches are based on satellite-derived estimates of fire radiative power (FRP), which can be converted to fire radiative energy (FRE) which is directly related to fire emissions. Uncertainties

  5. A new approach to the Danish guidelines for fire protection of combustible insulation

    Directory of Open Access Journals (Sweden)

    Dragsted Anders

    2013-11-01

    Full Text Available The tendency to use thicker layers of insulation and a wider use of combustible insulation materials is identified to pose a potential risk to fire safety of buildings. A new approach to the current Danish prescriptive code on fire protection of combustible insulation is proposed as a way to meet the concern. The new approach uses the fire properties of the insulation material itself to point out the necessary protective measures. This is contrary to the most European countries were only a reaction to fire class of the façade construction as a whole is required. The basic principle is presented but more research is needed to complete the new approach.

  6. Evaluation of Generic Issue 57: Effects of fire protection system actuation on safety-related equipment

    International Nuclear Information System (INIS)

    Lambright, J.; Bohn, M.; Lynch, J.; Ross, S.; Brosseau, D.

    1992-12-01

    Nuclear power plants have experienced actuations of fire protection systems (FPSs) under conditions for which these systems were not intended to actuate and also have experienced advertent actuations with the presence of a fire. These actuations have often damaged safety-related equipment. A review of the impact of past occurrences of both types of such events and their impact on plant safety systems, an analysis of the risk impacts of such events on nuclear power plant safety, and a cost-benefit analysis of potential corrective measures have been performed. Thirteen different scenarios leading to actuation of fire protection systems due to a variety of causes were identified. These scenarios ranged from inadvertent actuation caused by human error to hardware failure, and include seismic root causes and seismic/fire interactions. A quantification of these thirteen root causes, where applicable, was performed on generically applicable scenarios. This document, Volume 4, contains appendices E and F of this report

  7. Forum for fire protection and safety in power plants[Norway

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2005-07-01

    The conference contains 16 presentations on topics in the fields of fire protection and safety in plants in Western Norway, reorganization and reconstruction of power systems and plants in Norway, various aspects of risk and vulnerability analysis, technological aspects of plant management and construction and problems and risks with particularly transformers. Some views on challenges of the fire departments and the new Norwegian regulations for electrical power supply systems are included. One presentation deals with challenges for Icelandic power production plants.

  8. Factors influencing improved attendance in the UK fire service.

    Science.gov (United States)

    Litchfield, I; Hinckley, P

    2016-12-01

    Sickness absence rates in the UK continue to exceed those in much of the developed world, with an annual cost to employers of £29 billion. Rates of sickness absence in the public sector are higher than those in the private sector, with the exception of the fire service where they are consistently lower. To understand the influences that increase attendance among operational firefighters. A series of semi-structured interviews undertaken with operational staff to explore their attitudes to sickness absence. Review and analysis of participant responses identified a number of key themes, namely employee well-being, including physical fitness and mental health; employee engagement with the fire service as manifested by culture, experience, nature of the job and leadership; organizational factors including the staffing model and relationship with occupational health services and policy, which describes both refinements to and implementation of targeted policies. Previously observed factors such as improved fitness and the distinct firefighter culture play a role, yet other factors emerged that could explain the differences. These include the greater work-life balance offered by their shift patterns, the terms and conditions of employment and perhaps most importantly the evolution of precisely targeted policies that understand the unique nature of the operational fire service. © The Author 2016. Published by Oxford University Press on behalf of the Society of Occupational Medicine.

  9. Toward improving our application and understanding of crown fire behavior

    Science.gov (United States)

    Martin E. Alexander; Miguel G. Cruz; Nicole M. Vaillant

    2014-01-01

    The suggestion has been made that most wildland fire operations personnel base their expectations of how a fire will behave largely on experience and, to a lesser extent, on guides to predicting fire behavior (Burrows 1984). Experienced judgment is certainly needed in any assessment of wildland fire potential but it does have its limitations. The same can be said for...

  10. Neural networks improve performance of coal-fired boilers

    Energy Technology Data Exchange (ETDEWEB)

    Radl, B.J. [Pegasus Technologies Ltd., Painesville, OH (United States)

    1999-03-01

    Work sponsored by the US Department of Energy through its NICE{sup 3} programme, and co-funded by industry partners First Energy Corp. (host organisation and co-funder) and Pegasus Technologies (inventor, developer and supplier), has resulted in the development of online, real-time neural networks which help coal-fired utility boilers to dynamically adjust combustion setpoints. The payoff is a system which helps reduce NOx emissions up to 60%, while improving heat rate up to 2% overall. The system has avoided or postponed large capacity expenditures while meeting environmental compliance requirements. 3 figs., 1 tab.

  11. Cable fire tests in France

    International Nuclear Information System (INIS)

    Kaercher, M.

    2000-01-01

    Modifications are being carried out in all French nuclear power plants to improve fire safety. These modifications are based on a three level defense in depth concept: fire preventing, fire containing and fire controlling. Fire containing requires many modifications such as protection of cable races and assessment of fire propagation which both need R and D development. On one hand, cable wraps made with mineral wool were tested in all configurations including effect of aging, overheating and fire and qualified for the use as protection from common failure modes. On the other hand, cables races in scale one were subject to gas burner or solvent pool fire to simulate ignition and fire propagation between trays and flash over situations. These tests have been performed under several typical lay out conditions. The results of the tests can be used as input data in computer modelling for validation of fire protection measures. (orig.) [de

  12. Integrated system of occupational safety and health and fire protection of the fire rescue brigades members.

    Science.gov (United States)

    Božović, Marijola; Živković, Snežana; Mihajlović, Emina

    2018-06-01

    The objective of the conducted research is the identification and determination of requirements of members of fire rescue brigades during operations in the conditions of high risk in order to minimize the possibilities for injury incidence during the intervention. The research is focused on examination, determination and identification of factors affecting the increasing number of occupational injuries of members of fire rescue brigades during interventions. Hypothetical framework of the research problem consists of general hypothesis and six special hypotheses. Results suggest that almost all respondents believe that their skills and abilities are applicable in the intervention phase, but less than a half believe that their skills are applicable in prevention phase. Two-thirds of respondents stated that in their organization they have support for further education and upgrading while a half of respondents stated that they need education concerning identification, assessment and management of risks that can lead to emergency situations.

  13. Examination of alternatives to upgrade fire safety in operating NPPs

    International Nuclear Information System (INIS)

    Park, J. H.; Jung, I. S.

    2003-01-01

    For the Kori unit 2,3,4, Younggwang 1,2 and Ulchin 1,2 fire protection vulnerabilities and further improvement items are investigated. The most major problem is that those plants do not have plant-specific Fire Hazard Analysis Report. To improve fire safety of those plants, their own Fire Hazard Analysis should be proceed at first. Then, according to results of Fire Hazard Analysis, fire protection improvement program should be implemented. For the assurance of long term fire safety, result of Fire Hazard Analysis should be incorporated in the FSAR and periodically reviewed the impact of design change to fire safety

  14. FIRE PROTECTION OF TIMBER STRUCTURES STRENGTHENED WITH FRP MATERIALS

    Directory of Open Access Journals (Sweden)

    Radek Zigler

    2015-12-01

    Full Text Available Modern, progressive methods of structures’ strengthening based on the use of composite materials composed of high strength fibers (carbon, glass, aramid or basalt and matrices based on epoxy resins brings, among many indisputable advantages (low weight, high effectiveness, easy application etc. also some disadvantages. One of the major disadvantages is a low fire resistance of these materials due to the low glass transition temperature Tg of the resin used. Based on an extensive research of strengthening of historic structures with FRP materials [1], the article outlines possible approaches to this problem, especially while strengthening timber load- bearing structures of historic buildings.

  15. Fire Protection of Weapon Storage and Water Mist Redundancy Philosophies

    Science.gov (United States)

    2012-11-01

    criteria me system ged system ozzles dummy tor d, insulated titute of Swe stems pedo pipe Date 2012 den Refere -03-31 P90 nce 0038-04...test wit tion test wit ution test wi t system, 10 st system, 5 m, 5 bar, 50 , 10 bar, 50 ummy, free- edo dummy pedo dummy pedo dummy ummy, dren...systems usi lower volum pedo dumm temperature discharge d ion. h Institute ynamics dström Date 2012 den ater mist/wa ests indicate fire

  16. Improved core protection calculator system algorithm

    International Nuclear Information System (INIS)

    Yoon, Tae Young; Park, Young Ho; In, Wang Kee; Bae, Jong Sik; Baeg, Seung Yeob

    2009-01-01

    Core Protection Calculator System (CPCS) is a digitized core protection system which provides core protection functions based on two reactor core operation parameters, Departure from Nucleate Boiling Ratio (DNBR) and Local Power Density (LPD). It generates a reactor trip signal when the core condition exceeds the DNBR or LPD design limit. It consists of four independent channels which adapted a two out of four trip logic. CPCS algorithm improvement for the newly designed core protection calculator system, RCOPS (Reactor COre Protection System), is described in this paper. New features include the improvement of DNBR algorithm for thermal margin, the addition of pre trip alarm generation for auxiliary trip function, VOPT (Variable Over Power Trip) prevention during RPCS (Reactor Power Cutback System) actuation and the improvement of CEA (Control Element Assembly) signal checking algorithm. To verify the improved CPCS algorithm, CPCS algorithm verification tests, 'Module Test' and 'Unit Test', would be performed on RCOPS single channel facility. It is expected that the improved CPCS algorithm will increase DNBR margin and enhance the plant availability by reducing unnecessary reactor trips

  17. Improved Mask Protected DES using RSA Algorithm

    Directory of Open Access Journals (Sweden)

    Asha Latha S.

    2016-01-01

    Full Text Available The data encryption standard is a pioneering and farsighted standard which helped to set a new paradigm for encryption standards. But now DES is considered to be insecure for some application. Asymmetric mask protected DES is an advanced encryption method for effectively protecting the advanced DES. There are still probabilities to improve its security. This paper propose a method, which introduce a RSA key generation scheme in mask protected DES instead of plain key, which result in enhancement in the security of present asymmetric mask protected DES. We further propose a Vedic mathematical method of RSA implementation which reduce the complexity of computation in RSA block thereby resulting in reduced delay (four timesthat improves the performance of overall system. The software implementation was performed using Xilinx 13.2 and Model-Sim was used for the simulation environment.

  18. WILDLAND FIRE MANAGEMENT: Improved Planning Will Help Agencies Better Identify Fire-Fighting Preparedness Needs

    National Research Council Canada - National Science Library

    Hill, Barry

    2002-01-01

    Each year, wildland fires on federal lands burn millions of acres of forests, grasslands, and desert, and federal land management agencies expend hundreds of millions of dollars to fight these fires...

  19. International guidelines for fire protection at nuclear installations including nuclear fuel plants, nuclear fuel stores, teaching reactors, research establishments

    International Nuclear Information System (INIS)

    The guidelines are recommended to designers, constructors, operators and insurers of nuclear fuel plants and other facilities using significant quantities of radioactive materials including research and teaching reactor installations where the reactors generally operate at less than approximately 10 MW(th). Recommendations for elementary precautions against fire risk at nuclear installations are followed by appendices on more specific topics. These cover: fire protection management and organization; precautions against loss during construction alterations and maintenance; basic fire protection for nuclear fuel plants; storage and nuclear fuel; and basic fire protection for research and training establishments. There are numerous illustrations of facilities referred to in the text. (U.K.)

  20. Literature study regarding fire protection in nuclear power plants. Part I: Fire rated separations; Litteraturstudie angaaende brandskydd i kaernkraftverk. Del I: Brandteknisk separation

    Energy Technology Data Exchange (ETDEWEB)

    Isaksson, S [Swedish Testing and Research Inst., Boraas (Sweden)

    1995-06-01

    This literature study has been made on behalf of the Swedish Nuclear Power Inspectorate. The aim is to describe different aspects of fire protection in nuclear power plants. Conventional building codes can not give guidance on where to make fire rated separations in order to separate redundant trains of safety systems. The separation must originate in functional demands from the authorities on what functions are essential during and after a fire, and under what circumstances these functions shall be retained, i.e. the number of independent faults and initiating events. As a basic demand it is suggested to rate the strength of separations according to conventional building code, based on fire load. The whole separating construction shall have the same fire rating, including the ventilation system. Deviations from the basic demand can de done in case it can be proven that it is possible to compensate some or all of the fire rating with other measures. There is a general lack of statistical information regarding the reliability of fire separating constructions such as walls, fire doors, penetration seals and fire dampers. The amount of cables penetrating a seal is in many cases much higher in real installations than what has been tested for type approval. It would therefore be valuable to perform a furnace test with a more representative amount of cables passing through a penetration seal. Tests have shown that the 20 foot horizontal separation distance stipulated by NRC is not a guarantee against fire damage. Spatial separations based on general requirements shall not be allowed, but considered from case to case based on actual circumstances. For fire protection by isolation or coatings, it is of great importance to choose the method of protection carefully, to be compatible with the material it shall be applied on, and the environment and types of fire that may occur. 48 refs, 2 figs, 5 tabs.

  1. Fire protection in laboratories and factories. Guide for nuclear operator

    International Nuclear Information System (INIS)

    Savornin, J.; Hebrard, L.; Michard, J.; Muller, G.; Vasseur, C.

    1987-12-01

    Putting in place a nuclear industry is possible only if is taken into account the systematic risks connecting with the manipulation of radioactive matters. The measures taken are essentially the putting in place of static or dynamic barriers confinement. Therefore in case of fire their efficiencies can be reduced. The basic safety rule no. I-4.a serie U defines the objectives but do not give all the means to arrive. The present guide has for objective to propose the means which allow to satisfy these objectives. It permits to define the importance of precautions to take in terms of possible consequences. This document is not a rule. It has for objective to give advices [fr

  2. Review of national and international demands on fire protection in nuclear power plants and their application in the Swedish nuclear industry

    International Nuclear Information System (INIS)

    Fredholm, Lotta

    2010-02-01

    regarding fire safety at nuclear power plants that have been studied are regulation from USA, Finland, Great Britain, Canada, Germany and the international organisations IAEA and WENRA. The conclusion of this study is that the differences between the regulations mostly are differences in detailed fire safety design. Some differences can not easily be explained by national. Differences and the resulting effect on the overall fire safety is very difficult to evaluate. Regarding how to improve the Swedish regulations regarding fire safety at nuclear power plants there are different possibilities. One is to complement the regulations with acceptable solutions on how to design the fire protection. If this shall be done IAEAs Safety Guides seem to be the easiest of the more detailed fire requirements to adopt to Swedish conditions. Another way of improving the regulation is to give more guidance on how to proof that the rules are fulfilled. In this case the Canadian guidelines may be a good source of ideas and information

  3. 5 CFR 551.541 - Employees engaged in fire protection activities or law enforcement activities.

    Science.gov (United States)

    2010-01-01

    ... activities or law enforcement activities. 551.541 Section 551.541 Administrative Personnel OFFICE OF... activities or law enforcement activities. (a) An employee engaged in fire protection activities or law enforcement activities (as described in §§ 551.215 and 551.216, respectively) who receives compensation for...

  4. 48 CFR 2052.235-71 - Safety, health, and fire protection.

    Science.gov (United States)

    2010-10-01

    ... extension of time or for compensation or damages by reason of, or in connection with, this type of work... performance of the work under this contract to protect the health and safety of its employees and of members... hazards to life and property. The contractor shall comply with all applicable health, safety, and fire...

  5. 29 CFR 1915.507 - Land-side fire protection systems.

    Science.gov (United States)

    2010-07-01

    ... standard for employee safety or employee protection from fire hazards in land-side facilities, including... remains hazardous to employee safety or health, or provide safeguards to prevent employees from entering... hazardous to employee safety or health; and (6) Select, install, inspect, maintain, and test all automatic...

  6. Protection against internal fires and explosions in the design of nuclear power plants. Safety guide

    International Nuclear Information System (INIS)

    2004-01-01

    Experience of the past two decades in the operation of nuclear power plants and modern analysis techniques confirm that fire may be a real threat to nuclear safety and should receive adequate attention from the beginning of the design process throughout the life of the plant. Within the framework of the NUSS programme, a Safety Guide on fire protection had therefore been developed to enlarge on the general requirements given in the Code. Since its first publication in 1979, there has been considerable development in protection technology and analysis methods and after the Chernobyl accident it was decided to revise the existing Guide. This Safety Guide supplements the requirements established in Safety of Nuclear Power Plants: Design. It supersedes Safety Series No. 50-SG-D2 (Rev. 1), Fire Protection in Nuclear Power Plants: A Safety Guide, issued in 1992.The present Safety Guide is intended to advise designers, safety assessors and regulators on the concept of fire protection in the design of nuclear power plants and on recommended ways of implementing the concept in some detail in practice

  7. Improving global fire carbon emissions estimates by combining moderate resolution burned area and active fire observations

    Science.gov (United States)

    Randerson, J. T.; Chen, Y.; Giglio, L.; Rogers, B. M.; van der Werf, G.

    2011-12-01

    In several important biomes, including croplands and tropical forests, many small fires exist that have sizes that are well below the detection limit for the current generation of burned area products derived from moderate resolution spectroradiometers. These fires likely have important effects on greenhouse gas and aerosol emissions and regional air quality. Here we developed an approach for combining 1km thermal anomalies (active fires; MOD14A2) and 500m burned area observations (MCD64A1) to estimate the prevalence of these fires and their likely contribution to burned area and carbon emissions. We first estimated active fires within and outside of 500m burn scars in 0.5 degree grid cells during 2001-2010 for which MCD64A1 burned area observations were available. For these two sets of active fires we then examined mean fire radiative power (FRP) and changes in enhanced vegetation index (EVI) derived from 16-day intervals immediately before and after each active fire observation. To estimate the burned area associated with sub-500m fires, we first applied burned area to active fire ratios derived solely from within burned area perimeters to active fires outside of burn perimeters. In a second step, we further modified our sub-500m burned area estimates using EVI changes from active fires outside and within of burned areas (after subtracting EVI changes derived from control regions). We found that in northern and southern Africa savanna regions and in Central and South America dry forest regions, the number of active fires outside of MCD64A1 burned areas increased considerably towards the end of the fire season. EVI changes for active fires outside of burn perimeters were, on average, considerably smaller than EVI changes associated with active fires inside burn scars, providing evidence for burn scars that were substantially smaller than the 25 ha area of a single 500m pixel. FRP estimates also were lower for active fires outside of burn perimeters. In our

  8. 33 CFR 127.1507 - Water systems for fire protection.

    Science.gov (United States)

    2010-07-01

    ... (CONTINUED) WATERFRONT FACILITIES WATERFRONT FACILITIES HANDLING LIQUEFIED NATURAL GAS AND LIQUEFIED HAZARDOUS GAS Waterfront Facilities Handling Liquefied Hazardous Gas Firefighting Equipment § 127.1507 Water... means for distributing and applying the water to protect personnel; to cool storage tanks, equipment...

  9. Reliability data of fire protection equipment and features in German nuclear power plants

    International Nuclear Information System (INIS)

    Roewekamp, M.; Riekert, T.; Sehrbrock, W.

    1997-01-01

    In order to perform probabilistic fire safety analyses, a comprehensive data base is needed including physical characteristics of fire compartments and their inventory, fire occurrence frequencies, technical reliability data for all fire-related equipment, human actions and human error probabilities, etc. In order to provide updated and realistic reliability data, the operational behaviour of different fire protection features in two German nuclear power plants was analysed in the framework of the study presented here. The analyses are based on the examination of reported results of the regular inspection and maintenance programs for nuclear power plants. Besides a plant specific assessment of the reliability data a generic assessment for an application as input data for fault tree analyses in the framework of probabilistic risk studies for other German plants was carried out. The analyses of failures and unavailabilities gave the impression that most of them are single failures without relevance for the plant safety. The data gained from NPPs were compared to reliability data of the German insurance companies for the same protection features installed in non-nuclear installations and to older nuclear specific reliability data. This comparison showed up a higher reliability. (orig.) [de

  10. Active and passive fire protection system in academic building KH. Mas Mansur, Islamic University of Indonesia

    Directory of Open Access Journals (Sweden)

    Suryoputro M. Ragil

    2018-01-01

    Full Text Available According to the theory of fire triangle, the existence of combustible materials, heat, and oxygen can cause fire disaster. KH. Mas Mansur building, Islamic University of Indonesia has a fire protection, but rarely to be checked regularly and the number of equipment is less standard as well as the lack of an evacuation route map to facilitate the evacuation process. Inside the building also does not provide safety signs such as the evacuation directions, exit, and warning in case of fire. Therefore, researchers analysed the infrastructure of prevention and control in the building KH. Mas Mansur. Researchers used the method of observation, interviews, and checklist to know the condition directly, and compare with the standard regulations. Results concordance rate of existing infrastructure is 67% fire extinguisher, hydrant box 56%, 71% alarms, sprinkler 0%, 40% detectors, emergency doors 71%, 50% emergency stairs, assembly point 0% and directions 0%. The current results were below the standard of at least 80%. As for recommendations, researchers create a new evacuation map then put the existing infrastructure according to standard regulations, and it had consulted with the specialist of Occupational Safety and Health in the field of fire.

  11. Towards Improved Airborne Fire Detection Systems Using Beetle Inspired Infrared Detection and Fire Searching Strategies

    Directory of Open Access Journals (Sweden)

    Herbert Bousack

    2015-06-01

    Full Text Available Every year forest fires cause severe financial losses in many countries of the world. Additionally, lives of humans as well as of countless animals are often lost. Due to global warming, the problem of wildfires is getting out of control; hence, the burning of thousands of hectares is obviously increasing. Most important, therefore, is the early detection of an emerging fire before its intensity becomes too high. More than ever, a need for early warning systems capable of detecting small fires from distances as large as possible exists. A look to nature shows that pyrophilous “fire beetles” of the genus Melanophila can be regarded as natural airborne fire detection systems because their larvae can only develop in the wood of fire-killed trees. There is evidence that Melanophila beetles can detect large fires from distances of more than 100 km by visual and infrared cues. In a biomimetic approach, a concept has been developed to use the surveying strategy of the “fire beetles” for the reliable detection of a smoke plume of a fire from large distances by means of a basal infrared emission zone. Future infrared sensors necessary for this ability are also inspired by the natural infrared receptors of Melanophila beetles.

  12. Significance analysis of the regional differences on icing time of water onto fire protective clothing

    Science.gov (United States)

    Zhao, L. Z.; Jing, L. S.; Zhang, X. Z.; Xia, J. J.; Chen, Y.; Chen, T.; Hu, C.; Bao, Z. M.; Fu, X. C.; Wang, R. J.; Wang, Y.; Wang, Y. J.

    2017-09-01

    The object of this work was to determine the icing temperature in icing experiment. Firstly, a questionnaire investigation was carried out on 38 fire detachments in different regions. These Statistical percentage results were divided into northern east group and northern west group. Secondly, a significance analysis between these two results was made using Mann-Whitney U test. Then the icing temperature was determined in different regions. Thirdly, the icing experiment was made in the environment of -20°C in Daxing’an Mountain. The anti-icing effect of new fire protective clothing was verified in this icing.

  13. An effective and practical fire-protection system. [for aircraft fuel storage and transport

    Science.gov (United States)

    Mansfield, J. A.; Riccitiello, S. R.; Fewell, L. L.

    1975-01-01

    A high-performance sandwich-type fire protection system comprising a steel outer sheath and insulation combined in various configurations is described. An inherent advantage of the sheath system over coatings is that it eliminates problems of weatherability, materials strength, adhesion, and chemical attack. An experimental comparison between the protection performance of state-of-the-art coatings and the sheath system is presented, with emphasis on the protection of certain types of steel tanks for fuel storage and transport. Sheath systems are thought to be more expensive than coatings in initial implementation, although they are less expensive per year for sufficiently long applications.

  14. Fire Risk Assessment in Germany

    International Nuclear Information System (INIS)

    Berg, H. P.

    2000-01-01

    Quantitative fire risk assessment can serve as an additional tool to assess the safety level of a nuclear power plant (NPP) and to set priorities for fire protection improvement measures. The recommended approach to be applied within periodic safety reviews of NPPs in Germany starts with a screening process providing critical fire zones in which a fully developed fire has the potential to both cause an initiating event and impair the function of at least one component or system critical to safety. The second step is to perform a quantitative analysis using a standard event tree has been developed with elements for fire initiation, ventilation of the room, fire detection, fire suppression, and fire propagation. In a final step, the fire induced frequency of initiating events, the main contributors and the calculated hazard state frequency for the fire event are determined. Results of the first quantitative fire risk studies performed in Germany are reported. (author)

  15. A parametric study on the use of passive fire protection in FPSO topside module

    Directory of Open Access Journals (Sweden)

    Martin Friebe

    2014-12-01

    Full Text Available Fire is a continuous threat to FPSO topside modules as large amounts of oil and gas are passing through the modules. As a conventional measure to mitigate structural failure under fire, passive fire protection (PFP coatings are widely used on main structural members. However, an excessive use of PFP coatings can cause considerable cost for material purchase, installation, inspection and maintenance. Long installation time can be a risk since the work should be done nearly at the last fabrication stage. Thus, the minimal use of PFP can be beneficial to the reduction of construction cost and the avoidance of schedule delay. This paper presents a few case studies on how different applications of PFP have influence on collapse time of a FPSO module structure. A series of heat analysis and thermal elasto-plastic FE analysis are performed for different PFP coatings and the resultant collapse time and the amount of PFP coatings are compared with each other.

  16. Regulatory analysis for the resolution of generic issue 57: Effects of Fire Protection System Actuation on Safety-Related Equipment

    International Nuclear Information System (INIS)

    Woods, H.W.

    1993-10-01

    Actuation of Fire Protection Systems (FPS) in Nuclear Power Plants have resulted in adverse interactions with equipment important to safety. Precursor operational experience has shown that 37% of all FPS actuations damaged some equipment, and 20% of all FPS actuations have resulted in a plant transient and reactor trip. On an average 0.17 FPS actuations per reactor year have been experienced in nuclear power plants in this country. This report presents the regulatory analysis for GI-57, ''Effects of Fire Protection System Actuation on Safety-Related Equipment''. The risk reduction estimates, cost/benefit analyses, and other insights gained during this effort have shown that implementation of the recommendations contained in this report can significantly reduce risk, and that these improvements can be warranted in accordance with the backfit rule, 10 CFR 50.109(a)(3). However, plant specific analyses are required in order to identify such improvements. Generic analyses can not serve to identify improvements that could be warranted for individual, specific plants. Plant specific analyses of the type needed for this purpose are underway as part of the Individual Plant Examination of External Events (IPEEE) program

  17. Fire protection concepts for Timber-Glass Composite façades

    Directory of Open Access Journals (Sweden)

    Schleicher Andreas

    2016-01-01

    The main objectives can be summarized as follows: Growth and densification in urban areas require the development of intelligent and resource-efficient building systems for “Smart Cities” of the future. By using timber-glass composites (TGC the primary energy demand of buildings can be reduced substantially. This research project examines the feasibility of applications of this new technology in multi-story and high-rise buildings. Critical aspects concerning fire protection such as flammability of timber elements, fire spread and failure of façade elements with bracing capacity will be analyzed. Different strategies will be developed in case studies and validated by structural analysis. Large scale mock ups of TGC façade elements will be checked on their suitability in fire tests. The findings of this research will lead to innovative fire safety concepts for building systems with TGC façades. Compliance with the high safety standards for multi-story buildings in urban areas like Vienna is one of the main objectives of this work. The adaptation of these fire safety concepts to the national standards of the neighboring countries will be continued subsequently. The gained knowledge should lead to further cooperation with companies for serial productions with TGC technology.

  18. Planning for risk-informed/performance-based fire protection at nuclear power plants. Final report

    International Nuclear Information System (INIS)

    Najafi, B.; Parkinson, W.J.; Lee, J.A.

    1997-12-01

    This document presents a framework for discussing issues and building consensus towards use of fire modeling and risk technology in nuclear power plant fire protection program implementation. The plan describes a three-phase approach: development of core technologies, implementation of methods, and finally, case studies and pilot applications to verify viability of such methods. The core technologies are defined as fire modeling, fire and system tests, use of operational data, and system and risk techniques. The implementation phase addresses the programmatic issues involved in implementing a risk-informed/performance-based approach in an integrated approach with risk/performance measures. The programmatic elements include: (1) a relationship with fire codes and standards development as defined by the ongoing effort of NFPA for development of performance-based standards; (2) the ability for NRC to undertake inspection and enforcement; and (3) the benefit to utilities in terms of cost versus safety. The case studies are intended to demonstrate applicability of single issue resolution while pilot applications are intended to check the applicability of the integrated program as a whole

  19. Mine shaft fire and smoke protection systems - an update on hardware development and in-mine testing

    International Nuclear Information System (INIS)

    Johnson, G.A.

    1982-01-01

    In 1976, The Bureau of Mines developed a prototype system to sense and extinguish fires in shafts and shaft stations in underground metal and nonmetal mines. Subsequent work modified this technology to include fueling areas, spontaneous combustion zones and coal mines. This paper updates IC-8783 ''In-mine Fire Tests of Mine Shaft Fire and Smoke Protection Systems'', which was published in 1978 and summarized the design and in-mine, actual fire testing of the first prototype mine shaft fire and smoke protection system. This paper also updates related work from IC-8775 ''Spontaneous Oxidation and Combustion of Sulfide Ores in Underground Mines, (also published in 1978) and IC-8808 ''In-mine Evaluation of Underground Fire and Smoke Detectors'', (published in early 1979)

  20. Fire protection upgrading of four Russian 440/230 VVER units

    International Nuclear Information System (INIS)

    Corsini, G.; Yelfimov, S.

    1995-01-01

    The main goal of TACIS 3.6 a project funded by the Commission of the European Communities (CEC), was the front-end engineering for upgrading the Fire Protection System (FPS) of the safety-related equipment of Novovoronezh, Units 3 and 4, and Kola, Units 1 and 2, VVER 440/230 nuclear power plants. As a first step, all the safety-related equipment had to be identified, evaluation criteria had to be established and the existing FPS reviewed against the criteria. In the second step, the selection of the upgrading measures, depending on feasibility and cost estimate, has been accomplished, room by room. The third step, carried out on schedule and completed end July 95, has been essentially the preparation of the Technical Specifications for procurement of the needed equipment including remaining detail engineering. The Russian sub-contactor Atom Energo Project (AEP), who have been the designers of these older NPP s, have done the work with the Italian Ansaldo as the consultants of their Russian colleagues. Practical aspects of the engineering work are discussed and examples of improvements selected for retrofitting described. (author)

  1. Improving Nocturnal Fire Detection with the VIIRS Day-Night Band

    Science.gov (United States)

    Polivka, Thomas N.; Wang, Jun; Ellison, Luke T.; Hyer, Edward J.; Ichoku, Charles M.

    2016-01-01

    Building on existing techniques for satellite remote sensing of fires, this paper takes advantage of the day-night band (DNB) aboard the Visible Infrared Imaging Radiometer Suite (VIIRS) to develop the Firelight Detection Algorithm (FILDA), which characterizes fire pixels based on both visible-light and infrared (IR) signatures at night. By adjusting fire pixel selection criteria to include visible-light signatures, FILDA allows for significantly improved detection of pixels with smaller and/or cooler subpixel hotspots than the operational Interface Data Processing System (IDPS) algorithm. VIIRS scenes with near-coincident Advanced Spaceborne Thermal Emission and Reflection (ASTER) overpasses are examined after applying the operational VIIRS fire product algorithm and including a modified "candidate fire pixel selection" approach from FILDA that lowers the 4-µm brightness temperature (BT) threshold but includes a minimum DNB radiance. FILDA is shown to be effective in detecting gas flares and characterizing fire lines during large forest fires (such as the Rim Fire in California and High Park fire in Colorado). Compared with the operational VIIRS fire algorithm for the study period, FILDA shows a large increase (up to 90%) in the number of detected fire pixels that can be verified with the finer resolution ASTER data (90 m). Part (30%) of this increase is likely due to a combined use of DNB and lower 4-µm BT thresholds for fire detection in FILDA. Although further studies are needed, quantitative use of the DNB to improve fire detection could lead to reduced response times to wildfires and better estimate of fire characteristics (smoldering and flaming) at night.

  2. Fire protection system management in nuclear facilities: strengthening factor of integrated management system - a case study

    International Nuclear Information System (INIS)

    Santos, Joao Regis dos

    2005-01-01

    The present study investigated and analyzed the importance of a system of integrated safety manage, environment and health in a nuclear installation, having as perspective, the fire protection manage. The inquiry was made using a qualitative research involving a case study, where the considered environment was the Reconversion and UO 2 Plant of the Industrias Nucleares do Brasil (INB), located in Resende, Rio de Janeiro and the studied population, the managers and the staff directly involved with the aspects related to the safety of the industrial complex of the related company. The motivation for the research was the search of a bigger interaction of the questions related to the safety, environment and health in the nuclear industry having, as axle of the investigation, the fire protection. As a result, it was observed that in a nuclear installation, although dealing with diversified safety processes, integration is possible and necessary, since there are more reasons for integration than otherwise. (author)

  3. Protection of High Ceiling Nuclear Facilities Using Photoelectric Sensors and Infrared Fire Detectors

    International Nuclear Information System (INIS)

    Wadoud, A.A.; El Eissawi, H.M.; Saleh, A.A.

    2017-01-01

    A variety of different security systems and components are commercially available and widely used. Before implementing a security system, it is important to understand the characteristics and requirements of the facility area to be protected. Technology and manufacturers of security devices are rapidly changing. It is necessary to use optimal security equipment suitable for the surrounding environment of the facility to be protected. Several security sensors can be used to protect the nuclear facilities, such as passive infrared detectors and glass breakage sensors, vibration detectors, and microwave sensors. This work introduces technical specifications, operation and method of installation for these detectors in nuclear facilities. Also a comparative study of different security sensors or equipment is provided. The photoelectric detectors and infrared fire beam smoke detectors are reliable, suitable and advanced security equipment. They can be used in special cases because of their advantages, this includes their long ranges and accuracy in performance. This paper presents a new concept for adapting the use infrared optical fire beam smoke detector as intrusion detection equipment in high ceiling buildings or towering height facilities. This is in addition to their main function, namely fire detection.The paper also provides a study for their types and installation method. Focus is made on the installation and operation method for two advanced security systems, and wireless control circuit for the overall system operation

  4. Findings From Fire Inspections

    Data.gov (United States)

    Nuclear Regulatory Commission — The purpose of this study data is to provide a metric with which to assess the effectiveness of improvements to the U.S. NRC's fire protection regulations in support...

  5. Tunnel fire dynamics

    CERN Document Server

    Ingason, Haukur; Lönnermark, Anders

    2015-01-01

    This book covers a wide range of issues in fire safety engineering in tunnels, describes the phenomena related to tunnel fire dynamics, presents state-of-the-art research, and gives detailed solutions to these major issues. Examples for calculations are provided. The aim is to significantly improve the understanding of fire safety engineering in tunnels. Chapters on fuel and ventilation control, combustion products, gas temperatures, heat fluxes, smoke stratification, visibility, tenability, design fire curves, heat release, fire suppression and detection, CFD modeling, and scaling techniques all equip readers to create their own fire safety plans for tunnels. This book should be purchased by any engineer or public official with responsibility for tunnels. It would also be of interest to many fire protection engineers as an application of evolving technical principles of fire safety.

  6. Proposal for the award of a blanket purchase contract for the design, supply, installation and maintenance of automatic fire-detection, fire-protection and voice-alarm systems for the Super Proton Synchrotron

    CERN Document Server

    2017-01-01

    Proposal for the award of a blanket purchase contract for the design, supply, installation and maintenance of automatic fire-detection, fire-protection and voice-alarm systems for the Super Proton Synchrotron

  7. Linking management effectiveness indicators to observed effects of protected areas on fire occurrence in the Amazon rainforest.

    Science.gov (United States)

    Nolte, Christoph; Agrawal, Arun

    2013-02-01

    Management-effectiveness scores are used widely by donors and implementers of conservation projects to prioritize, track, and evaluate investments in protected areas. However, there is little evidence that these scores actually reflect the capacity of protected areas to deliver conservation outcomes. We examined the relation between indicators of management effectiveness in protected areas and the effectiveness of protected areas in reducing fire occurrence in the Amazon rainforest. We used data collected with the Management Effectiveness Tracking Tool (METT) scorecard, adopted by some of the world's largest conservation organizations to track management characteristics believed to be crucial for protected-area effectiveness. We used the occurrence of forest fires from 2000 through 2010 as a measure of the effect of protected areas on undesired land-cover change in the Amazon basin. We used matching to compare the estimated effect of protected areas with low versus high METT scores on fire occurrence. We also estimated effects of individual protected areas on fire occurrence and explored the relation between these effects and METT scores. The relations between METT scores and effects of protected areas on fire occurrence were weak. Protected areas with higher METT scores in 2005 did not seem to have performed better than protected areas with lower METT scores at reducing fire occurrence over the last 10 years. Further research into the relations between management-effectiveness indicators and conservation outcomes in protected areas seems necessary, and our results show that the careful application of matching methods can be a suitable method for that purpose. ©2012 Society for Conservation Biology.

  8. Probabilistic assessment of fire hazard: a contribution of power industry to the development of fire protection engineering

    International Nuclear Information System (INIS)

    Kandrac, J.; Skvarka, P.

    1990-01-01

    Draft methodology was developed for assessment of fire hazard in nuclear power plants. Named DIMEHORP, the methodology is based on fire hazard analyses and on the analyses of the possible ways of fire propagation and of the power plant systems. The former includes determining the spaces of the power plant in which a fire can arise. Fire propagation analysis deals with the probability that within a given section the fire will propagate and cause damage to the equipment before it is localized. The mathematical model used is based on probability theory in conjunction with expert estimates. The methodology was applied to the assessment of the effect of fire in the cable rooms of the Dukovany nuclear power plant on the safety and reliability of its operation. (Z.M.). 3 tabs., 6 refs

  9. Oriented clay nanopaper from biobased components--mechanisms for superior fire protection properties.

    Science.gov (United States)

    Carosio, F; Kochumalayil, J; Cuttica, F; Camino, G; Berglund, L

    2015-03-18

    The toxicity of the most efficient fire retardant additives is a major problem for polymeric materials. Cellulose nanofiber (CNF)/clay nanocomposites, with unique brick-and-mortar structure and prepared by simple filtration, are characterized from the morphological point of view by scanning electron microscopy and X-ray diffraction. These nanocomposites have superior fire protection properties to other clay nanocomposites and fiber composites. The corresponding mechanisms are evaluated in terms of flammability (reaction to a flame) and cone calorimetry (exposure to heat flux). These two tests provide a wide spectrum characterization of fire protection properties in CNF/montmorrilonite (MTM) materials. The morphology of the collected residues after flammability testing is investigated. In addition, thermal and thermo-oxidative stability are evaluated by thermogravimetric analyses performed in inert (nitrogen) and oxidative (air) atmospheres. Physical and chemical mechanisms are identified and related to the unique nanostructure and its low thermal conductivity, high gas barrier properties and CNF/MTM interactions for char formation.

  10. Effects of alpha-zirconium phosphate on thermal degradation and flame retardancy of transparent intumescent fire protective coating

    Energy Technology Data Exchange (ETDEWEB)

    Xing, Weiyi [State Key Laboratory of Fire Science, University of Science and Technology of China, 96 Jinzai Road, Hefei, Anhui 230026 (China); Zhang, Ping [State Key Laboratory Cultivation Base for Nonmetal Composites and Functional Materials, Southwest University of Science and Technology, 59 Qinglong Road, Mianyang 621010 (China); Song, Lei; Wang, Xin [State Key Laboratory of Fire Science, University of Science and Technology of China, 96 Jinzai Road, Hefei, Anhui 230026 (China); Hu, Yuan, E-mail: yuanhu@ustc.edu.cn [State Key Laboratory of Fire Science, University of Science and Technology of China, 96 Jinzai Road, Hefei, Anhui 230026 (China)

    2014-01-01

    Graphical abstract: - Highlights: • A transparent intumescent fire protective coating was obtained by UV-cured technology. • OZrP could enhance the thermal stability and anti-oxidation of the coating. • OZrP could reduce the combustion properties of the coatings. - Abstract: Organophilic alpha-zirconium phosphate (OZrP) was used to improve the thermal and fire retardant behaviors of the phenyl di(acryloyloxyethyl)phosphate (PDHA)-triglycidyl isocyanurate acrylate (TGICA)-2-phenoxyethyl acrylate (PHEA) (PDHA-TGICA-PHEA) coating. The morphology of nanocomposite coating was characterized by X-ray diffraction (XRD) and transmission electron microscopy (TEM). The effect of OZrP on the flame retardancy, thermal stability, fireproofing time and char formation of the coatings was investigated by microscale combustion calorimeter (MCC), thermogravimetric analysis (TGA), X-ray photoelectron spectroscopy (XPS), laser Raman spectroscopy (LRS) and scanning electric microscope (SEM). The results showed that by adding OZrP, the peak heat release rate and total heat of combustion were significantly reduced. The highest improvement was achieved with 0.5 wt% OZrP. XPS analysis indicated that the performance of anti-oxidation of the coating was improved with the addition of OZrP, and SEM images showed that a good synergistic effect was obtained through a ceramic-like layer produced by OZrP covered on the surface of char.

  11. Effects of alpha-zirconium phosphate on thermal degradation and flame retardancy of transparent intumescent fire protective coating

    International Nuclear Information System (INIS)

    Xing, Weiyi; Zhang, Ping; Song, Lei; Wang, Xin; Hu, Yuan

    2014-01-01

    Graphical abstract: - Highlights: • A transparent intumescent fire protective coating was obtained by UV-cured technology. • OZrP could enhance the thermal stability and anti-oxidation of the coating. • OZrP could reduce the combustion properties of the coatings. - Abstract: Organophilic alpha-zirconium phosphate (OZrP) was used to improve the thermal and fire retardant behaviors of the phenyl di(acryloyloxyethyl)phosphate (PDHA)-triglycidyl isocyanurate acrylate (TGICA)-2-phenoxyethyl acrylate (PHEA) (PDHA-TGICA-PHEA) coating. The morphology of nanocomposite coating was characterized by X-ray diffraction (XRD) and transmission electron microscopy (TEM). The effect of OZrP on the flame retardancy, thermal stability, fireproofing time and char formation of the coatings was investigated by microscale combustion calorimeter (MCC), thermogravimetric analysis (TGA), X-ray photoelectron spectroscopy (XPS), laser Raman spectroscopy (LRS) and scanning electric microscope (SEM). The results showed that by adding OZrP, the peak heat release rate and total heat of combustion were significantly reduced. The highest improvement was achieved with 0.5 wt% OZrP. XPS analysis indicated that the performance of anti-oxidation of the coating was improved with the addition of OZrP, and SEM images showed that a good synergistic effect was obtained through a ceramic-like layer produced by OZrP covered on the surface of char

  12. Computer code structure for evaluation of fire protection measures and fighting capability at nuclear plants

    International Nuclear Information System (INIS)

    Anton, V.

    1997-01-01

    In this work a computer code structure for Fire Protection Measures (FPM) and Fire Fighting Capability (FFC) at Nuclear Power Plants (NPP) is presented. It allows to evaluate the category (satisfactory (s), needs for further evaluation (n), unsatisfactory (u)) to which belongs the given NPP for a self-control in view of an IAEA inspection. This possibility of a self assessment resulted from IAEA documents. Our approach is based on international experience gained in this field and stated in IAEA recommendations. As an illustration we used the FORTRAN programming language statement to make clear the structure of the computer code for the problem taken into account. This computer programme can be conceived so that some literal message in English and Romanian languages be displayed beside the percentage assessments. (author)

  13. GIS Fuzzy Expert System for the assessment of ecosystems vulnerability to fire in managing Mediterranean natural protected areas.

    Science.gov (United States)

    Semeraro, Teodoro; Mastroleo, Giovanni; Aretano, Roberta; Facchinetti, Gisella; Zurlini, Giovanni; Petrosillo, Irene

    2016-03-01

    A significant threat to the natural and cultural heritage of Mediterranean natural protected areas (NPAs) is related to uncontrolled fires that can cause potential damages related to the loss or a reduction of ecosystems. The assessment and mapping of the vulnerability to fire can be useful to reduce landscape damages and to establish priority areas where it is necessary to plan measures to reduce the fire vulnerability. To this aim, a methodology based on an interactive computer-based system has been proposed in order to support NPA's management authority for the identification of vulnerable hotspots to fire through the selection of suitable indicators that allow discriminating different levels of sensitivity (e.g. Habitat relevance, Fragmentation, Fire behavior, Ecosystem Services, Vegetation recovery after fire) and stresses (agriculture, tourism, urbanization). In particular, a multi-criteria analysis based on Fuzzy Expert System (FES) integrated in a GIS environment has been developed in order to identify and map potential "hotspots" of fire vulnerability, where fire protection measures can be undertaken in advance. In order to test the effectiveness of this approach, this approach has been applied to the NPA of Torre Guaceto (Apulia Region, southern Italy). The most fire vulnerable areas are the patch of century-old forest characterized by high sensitivity and stress, and the wetlands and century-old olive groves due to their high sensitivity. The GIS fuzzy expert system provides evidence of its potential usefulness for the effective management of natural protected areas and can help conservation managers to plan and intervene in order to mitigate the fire vulnerability in accordance with conservation goals. Copyright © 2015 Elsevier Ltd. All rights reserved.

  14. Plasma-aided surface technology for modification of materials referred to fire protection

    International Nuclear Information System (INIS)

    Dineff, P.; Gospodinova, D.; Kostova, L.; Vladkova, T.; Chen, E.

    2008-01-01

    There has been considerable interest in dielectric barrier air discharge at atmospheric pressure and room temperature over the past decade due to the increased number of industrial applications. New plasma-aided capillary impregnation technology for flame spreading stop and fire protection of porous materials was developed. Research, based on thermogravimetric analysis (TGA), differential thermal analysis (DTA), and differential scanning calorimetry (DSC), proves that plasma-chemical surface pre-treatment exert material change on chemical interaction between phosphorus containing flame retardant and wood matrix (Pinus sylvestris, Bulgaria; Pseudotsuga, Canada)

  15. Clinch River breeder reactor sodium fire protection system design and development

    International Nuclear Information System (INIS)

    Foster, K.W.; Boasso, C.J.; Kaushal, N.N.

    1984-01-01

    To assure the protection of the public and plant equipment, improbable accidents were hypothesized to form the basis for the design of safety systems. One such accident is the postulated failure of the Intermediate Heat Transfer System (IHTS) piping within the Steam Generator Building (SGB), resulting in a large-scale sodium fire. This paper discusses the design and development of plant features to reduce the consequences of the accident to acceptable levels. Additional design solutions were made to mitigate the sodium spray contribution to the accident scenario. Sodium spill tests demonstrated that large sodium leaks can be safely controlled in a sodium-cooled nuclear power plant

  16. Radiative and conductive heat transfer in a nongrey semitransparent medium. Application to fire protection curtains

    Energy Technology Data Exchange (ETDEWEB)

    Berour, Nacer; Lacroix, David E-mail: david.lacroix@lemta.uhp-nancy.fr; Boulet, Pascal; Jeandel, Gerard

    2004-06-01

    This paper deals with heat transfer in nongrey media which scatter, absorb and emit radiation. Considering a two dimensional geometry, radiative and conductive phenomena through the medium have been taken into account. The radiative part of the problem was solved using the discrete ordinate method with classical S{sub n} quadratures. The absorption and scattering coefficients involved in the radiative transfer equation (RTE) were obtained from the Mie theory. Conduction inside the medium was linked to the RTE through the energy conservation. Validation of the model has been achieved with several simulation of water spray curtains used as fire protection walls.

  17. Ways to Improve Russian Coal-Fired Power Plants

    International Nuclear Information System (INIS)

    Tumanovskii, A. G.; Olkhovsky, G. G.

    2015-01-01

    Coal is an important fuel for the electric power industry of Russia, especially in Ural and the eastern part of the country. It is fired in boilers of large (200 – 800 MW) condensing power units and in many cogeneration power plants with units rated at 50 – 180 MW. Many coal-fired power plants have been operated for more than 40 – 50 years. Though serviceable, their equipment is obsolete and does not comply with the current efficiency, environmental, staffing, and availability standards. It is urgent to retrofit and upgrade such power plants using advanced equipment, engineering and business ideas. Russian power-plant engineering companies have designed such advanced power units and their equipment such as boilers, turbines, auxiliaries, process and environmental control systems similar to those produced by the world’s leading manufacturers. Their performance and ways of implementation are discussed

  18. Ways to Improve Russian Coal-Fired Power Plants

    Energy Technology Data Exchange (ETDEWEB)

    Tumanovskii, A. G., E-mail: vti@vti.ru; Olkhovsky, G. G. [JSC “All-Russia Thermal Engineering Institute,” (Russian Federation)

    2015-07-15

    Coal is an important fuel for the electric power industry of Russia, especially in Ural and the eastern part of the country. It is fired in boilers of large (200 – 800 MW) condensing power units and in many cogeneration power plants with units rated at 50 – 180 MW. Many coal-fired power plants have been operated for more than 40 – 50 years. Though serviceable, their equipment is obsolete and does not comply with the current efficiency, environmental, staffing, and availability standards. It is urgent to retrofit and upgrade such power plants using advanced equipment, engineering and business ideas. Russian power-plant engineering companies have designed such advanced power units and their equipment such as boilers, turbines, auxiliaries, process and environmental control systems similar to those produced by the world’s leading manufacturers. Their performance and ways of implementation are discussed.

  19. Harvest facility protects and improves fishery

    International Nuclear Information System (INIS)

    Hampton, T.; Daley, W.

    1991-01-01

    This paper reports that by constructing a trap and transfer/harvest facility to control anadromous fish migration, the trout fishery on the Boardman River was protected and the salmon fishery was improved. The James P. Price Fish Trap and Transfer/Harvest Facility at Traverse City, Michigan, was constructed by the Traverse City Light and Power Department because of a licensing condition during the redevelopment of the Boardman and Sabin hydroelectric plants. The facility was constructed along with a fish ladder at the Union Street Dam to control the anadromous fish migration in lieu of constructing fish ladders at the Union Street, Sabin and Boardman Dams. The Michigan Department of Natural Resources (MDNR) and the U.S. Fish and Wildlife Service required that the fish ladders be constructed before the hydroelectric plants could be reactivated. The MDNR was also planning to introduce salmon into the Boardman River as far up as the reservoir of the Boardman Dam, which is the third dam from the mouth of the river

  20. Standard on fire protection for self-propelled and mobile surface mining equipment. 2001 ed.

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2001-07-01

    Safeguard life and property against fire and related hazards in mines with the latest requirements in NFPA 121. This 2001 edition covers fire detection, suppression, ignition sources, fire risk assessment and maintenance of mining equipment systems. 4 apps.

  1. Protective clothing[Occupational safety of personnel in the event of a sodium fire

    Energy Technology Data Exchange (ETDEWEB)

    Malet, J C; Regnier, J [DSN/SESTR, Centre de Cadarache, Saint-Paul-lez-Durance (France)

    1979-03-01

    The present operational and intervention suits are described. Research work is currently in progress to improve the performance of the existing suits and to develop more resistant protective clothing. (author)

  2. Corrosion and protection in reinforced concrete : Pulse cathodic protection: an improved cost-effective alternative

    NARCIS (Netherlands)

    Koleva, D.A.

    2007-01-01

    Corrosion and protection in reinforced concrete. Pulse cathodic protection: an improved cost-effective alternative. The aim of the research project was to study the possibilities for establishing a new or improved electrochemical method for corrosion prevention/protection for reinforced concrete.

  3. Effects of weathering on performance of intumescent coatings for structure fire protection in the wildland-urban interface

    Science.gov (United States)

    Bahrani, Babak

    The objective of this study was to investigate the effects of weathering on the performance of intumescent fire-retardant coatings on wooden products. The weathering effects included primary (solar irradiation, moisture, and temperature) and secondary (environmental contaminants) parameters at various time intervals. Wildland urban interface (WUI) fires have been an increasing threat to lives and properties. Existing solutions to mitigate the damages caused by WUI fires include protecting the structures from ignition and minimizing the fire spread from one structure to another. These solutions can be divided into two general categories: active fire protection systems and passive fire protection systems. Passive systems are either using pre-applied wetting agents (water, gel, or foam) or adding an extra layer (composite wraps or coatings). Fire-retardant coating treatment methods can be divided into impregnated (penetrant) and intumescent categories. Intumescent coatings are easy to apply, economical, and have a better appearance in comparison to other passive fire protection methods, and are the main focus of this study. There have been limited studies conducted on the application of intumescent coatings on wooden structures and their performance after long-term weathering exposure. The main concerns of weathering effects are: 1) the reduction of ignition resistance of the coating layer after weathering; and 2) the fire properties of coatings after weathering since coatings might contribute as a combustible fuel and assist the fire growth after ignition. Three intumescent coatings were selected and exposed to natural weathering conditions in three different time intervals. Two types of tests were performed on the specimens: a combustibility test consisted of a bench-scale performance evaluation using a Cone Calorimeter, and a thermal decomposition test using Simultaneous Differential Scanning Calorimetry (DSC) and Thermogravimetric Analysis (TGA) method (also known

  4. Sevoflurane improves gaseous exchange and exerts protective ...

    African Journals Online (AJOL)

    mice, and exerted protective effects against acute LPS-induced lung injury. ... This is an Open Access article that uses a funding model which does not charge readers .... field microscope [20]. ... by Tukey's test were used for statistical analysis.

  5. Fire and Smoke Model Evaluation Experiment: Coordination of a study to improve smoke modeling for fire operations within the United States

    Science.gov (United States)

    French, N. H. F.; Ottmar, R. D.; Brown, T. J.; Larkin, N. K.

    2017-12-01

    The Fire and Smoke Model Evaluation Experiment (FASMEE) is an integrative research effort to identify and collect critical measurements to improve operational wildland fire and smoke prediction systems. FASMEE has two active phases and one suggested phase. Phase 1 is the analysis and planning process to assess the current state of fire-plume-smoke modeling and to determine the critical measurements required to evaluate and improve these operational fire and smoke models. As the major deliverable for Phase 1, a study plan has been completed that describes the measurement needs, field campaigns, and command, safety and air space de-confliction plans necessary to complete the FASMEE project. Phase 2 is a set of field campaigns to collect data during 2019-2022. Future Improvements would be a set of analyses and model improvements based on the data collected within Phase 2 that is dependent on identifying future funding sources. In this presentation, we will review the FASMEE Study Plan and detailed measurements and conditions expected for the four to five proposed research burns. The recommended measurements during Phase 2 span the four interrelated disciplines of FASMEE: fuels and consumption, fire behavior and energy, plume dynamics and meteorology, and smoke emissions, chemistry, and transport. Fuel type, condition, and consumption during wildland fire relates to several fire impacts including radiative heating, which provides the energy that drives fire dynamics. Local-scale meteorology is an important factor which relates to atmospheric chemistry, dispersion, and transport. Plume dynamics provide the connection between fire behavior and far-field smoke dispersion, because it determines the vertical distribution of the emissions. Guided by the data needs and science questions generated during Phase 1, three wildland fire campaigns were selected. These included the western wildfire campaign (rapid deployment aimed at western wildfires supporting NOAA, NASA, and NSF

  6. Evaluation Of Fire Safety And Protection At PUSPATI TRIGA Reactor (RTP)

    International Nuclear Information System (INIS)

    Ahmad Nabil Ab Rahim; Alfred Sanggau Ligam; Nurhayati Ramli; Mohd Fazli Zakaria; Naim Syauqi Hamzah; Phongsakorn Prak; Mohammad Suhaimi Kassim; Zarina Masood

    2014-01-01

    Fire hazard is one of many risks that can affect the safety operation of PUSPATI TRIGA Reactor. Reactor building in Malaysian Nuclear Agency was built in 1980s and the fire system has been introduced since then. The evaluation of the fire safety system at this time is important to ensure the efficiency of fire prevention, fighting and mitigation task that probably occurs. This evaluation involves with the fire fighting system and equipment, integrity of the system from the perspective of management and equipment, fire fighting procedure and fire fighting response team. (author)

  7. Coal fly ash-containing sprayed mortar for passive fire protection of steel sections

    Directory of Open Access Journals (Sweden)

    Vilches, L. F.

    2005-09-01

    Full Text Available The present article addresses the possible use of coal fly ash as the chief component of sprayed mortars to fireproof steel structures. A pilot wet-mix gunning rig was specifically designed and built to spray different pastes on to sheet steel and sections with different surface/volume ratios. After gunning, the specimens were placed in a furnace and subjected to standard fire resistance testing. Product fire resistance was calculated from the test results. The mortar used in this study, with a high fly ash content, was found to have acceptable mechanical properties as well as afire resistance potential comparable to those of commercial passive fire protection products.

    En este artículo se estudia el posible uso de las cenizas volantes procedentes de la combustión del carbón como constituyente principal de morteros que pueden ser proyectados sobre estructuras metálicas, para protegerlas contra el fuego. Con objeto de estudiar el proceso de proyección, se ha construido una planta piloto de gunitado por vía húmeda. La pasta se ha proyectado sobre placas metálicas y perfiles metálicos con diferentes relaciones superficie/volumen. Tras el gunitado, las probetas proyectadas se colocan en un horno y se someten a un programa de calentamiento según la norma de resistencia al fuego. A partir de los datos obtenidos se ha podido realizar una estimación de la resistencia al fuego del producto. Los resultados muestran que el material proyectado usado en este estudio, que contiene una alta proporción de cenizas volantes, tiene unas propiedades mecánicas aceptables y unas características potenciales de resistencia al fuego comparables a las de otros productos comerciales utilizados en la protección pasiva contra el fuego.

  8. The improvement for fire retardant and radiation resistance characteristics of chloroprene rubber

    Energy Technology Data Exchange (ETDEWEB)

    Kim, K. Y.; Lee, C.; Kim, P. J.; Kim, J. H

    2004-04-01

    In the report, in order to improve the fire retardancy better Chloroprene Rubber (CR) after adding each fixed amount of inorganic metallic hydroxide, and then compared and assessed fire retardancy with electrical properties and mechanical properties we intended to choose the most excellent additives. Also according to Co{sup 60} {gamma}-ray irradiation, we compared electrical, echanical and fire retardant characteristics to analyse to have the additives of inorganic filler effect on CR's antirad characteristic. In result, CR containing inorganic additive, advanced considerably fire retardant characteristics, but seems to be tended to declined electrical and mechanical characteristics on the whole. In syntherically comparison, the specimen viewed the most excellent characteristics is CR containing Magnesium hydroxide. As to Co{sup 60} {gamma}-ray irradiated Chloroprene rubber containing inorganic additives, fire retardant characteristic are improved, but electrical and mechanical properties are deteriorated as a function of radiation dose. Comparing before irradiation and after irradiation, the best inorganic filler into CR consider Magnesium hydroxide. In this report, in case of adding 30 phr of inorganic filler to CR we observed fire retardancy and radiation resistance characteristics change in according to the kinds of additives, but the research for choosing the optimum amount of additives is considered to progress from now on as adjusting the amount of additives presented excellent characteristics.

  9. Adsorber fires

    International Nuclear Information System (INIS)

    Holmes, W.

    1987-01-01

    The following conclusions are offered with respect to activated charcoal filter systems in nuclear power plants: (1) The use of activated charcoal in nuclear facilities presents a potential for deep-seated fires. (2) The defense-in-depth approach to nuclear fire safety requires that if an ignition should occur, fires must be detected quickly and subsequently suppressed. (3) Deep-seated fires in charcoal beds are difficult to extinguish. (4) Automatic water sprays can be used to extinguish fires rapidly and reliably when properly introduced into the burning medium. The second part of the conclusions offered are more like challenges: (1) The problem associated with inadvertent actuations of fire protection systems is not a major one, and it can be reduced further by proper design review, installation, testing, and maintenance. Eliminating automatic fire extinguishing systems for the protection of charcoal adsorbers is not justified. (2) Removal of automatic fire protection systems due to fear of inadvertent fire protection system operation is a case of treating the effect rather than the cause. On the other hand, properly maintaining automatic fire protection systems will preserve the risk of fire loss at acceptable levels while at the same time reducing the risk of damage presented by inadvertent operation of fire protection systems

  10. A novel method to design water spray cooling system to protect floating roof atmospheric storage tanks against fires

    Directory of Open Access Journals (Sweden)

    Iraj Alimohammadi

    2015-01-01

    Full Text Available Hydrocarbon bulk storage tank fires are not very common, but their protection is essential due to severe consequences of such fires. Water spray cooling system is one of the most effective ways to reduce damages to a tank from a fire. Many codes and standards set requirements and recommendations to maximize the efficiency of water spray cooling systems, but these are widely different and still various interpretations and methods are employed to design such systems. This article provides a brief introduction to some possible design methods of cooling systems for protection of storage tanks against external non-contacting fires and introduces a new method namely “Linear Density Method” and compares the results from this method to the “Average Method” which is currently in common practice. The average Method determines the flow rate for each spray nozzle by dividing the total water demand by the number of spray nozzles while the Linear Density Method determines the nozzle flow rate based on the actual flow over the surface to be protected. The configuration of the system includes a one million barrel crude oil floating roof tank to be protected and which is placed one half tank diameter from a similar adjacent tank with a full surface fire. Thermal radiation and hydraulics are modeled using DNV PHAST Version 6.53 and Sunrise PIPENET Version 1.5.0.2722 software respectively. Spray nozzles used in design are manufactured by Angus Fire and PNR Nozzles companies. Schedule 40 carbon steel pipe is used for piping. The results show that the cooling system using the Linear Density Method consumes 3.55% more water than the design using the average method assuming a uniform application rate of 4.1 liters per minute. Despite higher water consumption the design based on Linear Density Method alleviates the problems associated with the Average Method and provides better protection.

  11. Mean composite fire severity metrics computed with Google Earth Engine offer improved accuracy and expanded mapping potential

    Science.gov (United States)

    Parks, Sean; Holsinger, Lisa M.; Voss, Morgan; Loehman, Rachel A.; Robinson, Nathaniel P.

    2018-01-01

    Landsat-based fire severity datasets are an invaluable resource for monitoring and research purposes. These gridded fire severity datasets are generally produced with pre-and post-fire imagery to estimate the degree of fire-induced ecological change. Here, we introduce methods to produce three Landsat-based fire severity metrics using the Google Earth Engine (GEE) platform: the delta normalized burn ratio (dNBR), the relativized delta normalized burn ratio (RdNBR), and the relativized burn ratio (RBR). Our methods do not rely on time-consuming a priori scene selection and instead use a mean compositing approach in which all valid pixels (e.g. cloud-free) over a pre-specified date range (pre- and post-fire) are stacked and the mean value for each pixel over each stack is used to produce the resulting fire severity datasets. This approach demonstrates that fire severity datasets can be produced with relative ease and speed compared the standard approach in which one pre-fire and post-fire scene are judiciously identified and used to produce fire severity datasets. We also validate the GEE-derived fire severity metrics using field-based fire severity plots for 18 fires in the western US. These validations are compared to Landsat-based fire severity datasets produced using only one pre- and post-fire scene, which has been the standard approach in producing such datasets since their inception. Results indicate that the GEE-derived fire severity datasets show improved validation statistics compared to parallel versions in which only one pre-fire and post-fire scene are used. We provide code and a sample geospatial fire history layer to produce dNBR, RdNBR, and RBR for the 18 fires we evaluated. Although our approach requires that a geospatial fire history layer (i.e. fire perimeters) be produced independently and prior to applying our methods, we suggest our GEE methodology can reasonably be implemented on hundreds to thousands of fires, thereby increasing opportunities

  12. Improved transformer protection using probabilistic neural network ...

    African Journals Online (AJOL)

    user

    secure and dependable protection for power transformers. Owing to its superior learning and generalization capabilities Artificial. Neural Network (ANN) can considerably enhance the scope of WI method. ANN approach is faster, robust and easier to implement than the conventional waveform approach. The use of neural ...

  13. Improved transformer protection using probabilistic neural network ...

    African Journals Online (AJOL)

    This article presents a novel technique to distinguish between magnetizing inrush current and internal fault current of power transformer. An algorithm has been developed around the theme of the conventional differential protection method in which parallel combination of Probabilistic Neural Network (PNN) and Power ...

  14. PART I: Bioventing Pilot Test Work Plan for Fire Protection Training Area Site FY-03, Charleston AFB, South Carolina. PART II: Draft Interim Pilot Test Results Report for Fire Protection Training Area Site FT-03, Charleston AFB, South Carolina

    National Research Council Canada - National Science Library

    1993-01-01

    This site-specific work plan presents the scope of a bioventing pilot test for in situ treatment of fuel contaminated soils at the Fire Protection Training Area designated as Site FT-O3, Charleston Air Force Base (AFB), South Carolina...

  15. Review of national and international demands on fire protection in nuclear power plants and their application in the Swedish nuclear industry; Oeversikt av nationell och internationell kravbild avseende brandskydd paa kaernkraftverk och hur dessa tillaempas i svensk kaernkraftindustri

    Energy Technology Data Exchange (ETDEWEB)

    Fredholm, Lotta (Tyrens AB, Malmoe (Sweden))

    2010-02-15

    regarding fire safety at nuclear power plants that have been studied are regulation from USA, Finland, Great Britain, Canada, Germany and the international organisations IAEA and WENRA. The conclusion of this study is that the differences between the regulations mostly are differences in detailed fire safety design. Some differences can not easily be explained by national. Differences and the resulting effect on the overall fire safety is very difficult to evaluate. Regarding how to improve the Swedish regulations regarding fire safety at nuclear power plants there are different possibilities. One is to complement the regulations with acceptable solutions on how to design the fire protection. If this shall be done IAEAs Safety Guides seem to be the easiest of the more detailed fire requirements to adopt to Swedish conditions. Another way of improving the regulation is to give more guidance on how to proof that the rules are fulfilled. In this case the Canadian guidelines may be a good source of ideas and information

  16. Application of improved AHP method to radiation protection optimization

    International Nuclear Information System (INIS)

    Wang Chuan; Zhang Jianguo; Yu Lei

    2014-01-01

    Aimed at the deficiency of traditional AHP method, a hierarchy model for optimum project selection of radiation protection was established with the improved AHP method. The result of comparison between the improved AHP method and the traditional AHP method shows that the improved AHP method can reduce personal judgment subjectivity, and its calculation process is compact and reasonable. The improved AHP method can provide scientific basis for radiation protection optimization. (authors)

  17. 29 CFR 553.213 - Public agency employees engaged in both fire protection and law enforcement activities.

    Science.gov (United States)

    2010-07-01

    ... regardless of how the employee's time is divided between the two activities. However, all time spent in... spends the majority of work time during the work period. ... 29 Labor 3 2010-07-01 2010-07-01 false Public agency employees engaged in both fire protection and...

  18. The Nuclear Safety Council's Instruction IS-30 on program requirements of fire protection at nuclear power plants; La instruccion IS-30 del consejo de Seguridad Nuclear sobre requisitos del programa de proteccion contraincendios en centrales nucleares

    Energy Technology Data Exchange (ETDEWEB)

    Peco, J.

    2015-07-01

    The Nuclear Safety Councils Instrumentation IS-30 is the standard that establishes the fire protection program requirements for the Spanish nuclear power plants with operating license in order to satisfy the two fire protection objectives, which are the adoption of the defense-in-depth principle for fire protection and, by fire area confinement, to ensure that one train of components needed to achieve and maintain the safe shutdown conditions is free of fire damage, and that radioactive liberation is minimized. (Author)

  19. State-of-the-art review of sodium fire analysis and current notions for improvements

    International Nuclear Information System (INIS)

    Tasi, S.S.

    1978-01-01

    Sodium releases from postulated pipe ruptures, as well as failures of sodium handling equipment in liquid metal fast breeder reactors, may lead to substantial pressure-temperature transients in the sodium system cells, as well as in the reactor containment building. Sodium fire analyses are currently performed with analytical tools, such as the SPRAY, SOMIX, SPOOL-FIRE and SOFIRE-II codes. A review and evaluation of the state-of-the-art in sodium fire analysis is presented, and suggestions for further improvements are made. This work is based, in part, on studies made at Brookhaven National Laboratory during the past several years in the areas of model development and improvement associated with the accident analyses of LMFBRs

  20. 29 CFR Appendix C to Subpart L of... - Fire Protection References For Further Information

    Science.gov (United States)

    2010-07-01

    ..., Batterymarch Park, Quincy, MA 02269 . 3. Fire Fighter Professional Qualifications, NFPA 1001; National Fire... of Equipment for the Removal of Smoke and Grease-Laden Vapor from Commercial Cooking Equipment, NFPA...

  1. 309 Building fire protection analysis and justification for deactivation of sprinkler system. Revision 1

    International Nuclear Information System (INIS)

    Conner, R.P.

    1997-01-01

    Provide a 'graded approach' fire evaluation in preparation for turnover to Environmental Restoration Contractor for D and D. Scope includes revising 309 Building book value and evaluating fire hazards, radiological and toxicological releases, and life safety issues

  2. Development of Human Factors Engineering Requirements for Fire Fighting Protective Equipment

    National Research Council Canada - National Science Library

    Hopmeier, Michael; Christen, Hank T; Malone, Michael V

    2005-01-01

    This report is the result of an effort to develop an understanding of fire fighter needs through an assessment of relevant research and fire fighter-related literature, forums, conferences, and symposia...

  3. Rapid-fire improvement with short-cycle kaizen.

    Science.gov (United States)

    Heard, E

    1999-05-01

    Continuous improvement is an attractive idea, but it is typically more myth than reality. SCK is no myth. It delivers dramatic improvements in traditional measures quickly. SCK accomplishes this via kaizens: rapid, repeated, time-compressed changes for the better in bite-sized chunks of the business.

  4. 76 FR 70414 - National Fire Protection Association (NFPA) Proposes To Revise Codes and Standards

    Science.gov (United States)

    2011-11-14

    ... Commercial Cooking Operations. NFPA 99--2012 Health Care Facilities Code 6/22/2012 NFPA 99B--2010 Standard... Explosion Investigations..... 1/4/2012 NFPA 1005--2007 Standard for Professional Qualifications for 1/4/2012 Marine Fire Fighting for Land-Based Fire Fighters. NFPA 1021--2009 Standard for Fire Officer Professional...

  5. Mathematical Foundation Based Inter-Connectivity modelling of Thermal Image processing technique for Fire Protection

    Directory of Open Access Journals (Sweden)

    Sayantan Nath

    2015-09-01

    Full Text Available In this paper, integration between multiple functions of image processing and its statistical parameters for intelligent alarming series based fire detection system is presented. The proper inter-connectivity mapping between processing elements of imagery based on classification factor for temperature monitoring and multilevel intelligent alarm sequence is introduced by abstractive canonical approach. The flow of image processing components between core implementation of intelligent alarming system with temperature wise area segmentation as well as boundary detection technique is not yet fully explored in the present era of thermal imaging. In the light of analytical perspective of convolutive functionalism in thermal imaging, the abstract algebra based inter-mapping model between event-calculus supported DAGSVM classification for step-by-step generation of alarm series with gradual monitoring technique and segmentation of regions with its affected boundaries in thermographic image of coal with respect to temperature distinctions is discussed. The connectedness of the multifunctional operations of image processing based compatible fire protection system with proper monitoring sequence is presently investigated here. The mathematical models representing the relation between the temperature affected areas and its boundary in the obtained thermal image defined in partial derivative fashion is the core contribution of this study. The thermal image of coal sample is obtained in real-life scenario by self-assembled thermographic camera in this study. The amalgamation between area segmentation, boundary detection and alarm series are described in abstract algebra. The principal objective of this paper is to understand the dependency pattern and the principles of working of image processing components and structure an inter-connected modelling technique also for those components with the help of mathematical foundation.

  6. Preliminary report on fire protection research program (July 6, 1977 test)

    International Nuclear Information System (INIS)

    Klamerus, L.J.

    1977-10-01

    This preliminary report describes a fire test performed at Sandia Laboratories on an array of cable trays filled with fire retardant (IEEE 383 qualified) electrical cable. The cable trays were arranged in an open-space horizontal configuration with the separation distances of Regulatory Guide 1.75 between those trays representing redundant safety divisions. Propane burners were used to produce a fully developed cable fire in one tray which then was allowed to interact with other trays. From this test it appears that it is possible for a fire to propagate across the vertical separation distance between safety divisions, if a fully developed cable fire is the initiating event

  7. 32 CFR 644.554 - Insurance against loss or damages to buildings and improvements by fire or acts of God.

    Science.gov (United States)

    2010-07-01

    ... 32 National Defense 4 2010-07-01 2010-07-01 true Insurance against loss or damages to buildings and improvements by fire or acts of God. 644.554 Section 644.554 National Defense Department of... Procedure § 644.554 Insurance against loss or damages to buildings and improvements by fire or acts of God...

  8. Safety test of an improved multihundred watt FSA: launch abort, solid propellant fire

    International Nuclear Information System (INIS)

    Seabourn, C.M.

    1978-07-01

    This safety test consisted of exposing a simulant-fueled Improved Multihundred Watt Fuel Sphere Assembly, containing a Pt-3008 sphere holding the fuel simulant, to a single proximity fire of UTP-3001 solid rocket propellant for 10.5 min. The graphite outside shell sustained only minor abrasion damage. It was covered on one side with a heavy deposit of alumina from the fire mixed with silica from the test bed. The Pt-3008 shell had small amounts of carbon, alumina, and silica deposited on its surface but sustained no other damage. The PT-3008 sphere was not breached, and therefore the fuel sphere assembly would not release fuel in a solid-propellant fire of a launch abort. 12 figures

  9. Improved Methods for Fire Risk Assessment in Low-Income and Informal Settlements

    Directory of Open Access Journals (Sweden)

    John Twigg

    2017-02-01

    Full Text Available Fires cause over 300,000 deaths annually worldwide and leave millions more with permanent injuries: some 95% of these deaths are in low- and middle-income countries. Burn injury risk is strongly associated with low-income and informal (or slum settlements, which are growing rapidly in an urbanising world. Fire policy and mitigation strategies in poorer countries are constrained by inadequate data on incidence, impacts, and causes, which is mainly due to a lack of capacity and resources for data collection, analysis, and modelling. As a first step towards overcoming such challenges, this project reviewed the literature on the subject to assess the potential of a range of methods and tools for identifying, assessing, and addressing fire risk in low-income and informal settlements; the process was supported by an expert workshop at University College London in May 2016. We suggest that community-based risk and vulnerability assessment methods, which are widely used in disaster risk reduction, could be adapted to urban fire risk assessment, and could be enhanced by advances in crowdsourcing and citizen science for geospatial data creation and collection. To assist urban planners, emergency managers, and community organisations who are working in resource-constrained settings to identify and assess relevant fire risk factors, we also suggest an improved analytical framework based on the Haddon Matrix.

  10. Improved Methods for Fire Risk Assessment in Low-Income and Informal Settlements.

    Science.gov (United States)

    Twigg, John; Christie, Nicola; Haworth, James; Osuteye, Emmanuel; Skarlatidou, Artemis

    2017-02-01

    Fires cause over 300,000 deaths annually worldwide and leave millions more with permanent injuries: some 95% of these deaths are in low- and middle-income countries. Burn injury risk is strongly associated with low-income and informal (or slum) settlements, which are growing rapidly in an urbanising world. Fire policy and mitigation strategies in poorer countries are constrained by inadequate data on incidence, impacts, and causes, which is mainly due to a lack of capacity and resources for data collection, analysis, and modelling. As a first step towards overcoming such challenges, this project reviewed the literature on the subject to assess the potential of a range of methods and tools for identifying, assessing, and addressing fire risk in low-income and informal settlements; the process was supported by an expert workshop at University College London in May 2016. We suggest that community-based risk and vulnerability assessment methods, which are widely used in disaster risk reduction, could be adapted to urban fire risk assessment, and could be enhanced by advances in crowdsourcing and citizen science for geospatial data creation and collection. To assist urban planners, emergency managers, and community organisations who are working in resource-constrained settings to identify and assess relevant fire risk factors, we also suggest an improved analytical framework based on the Haddon Matrix.

  11. Survival Mediterranean Style: Lifestyle Changes to Improve the Health of the US Fire Service.

    Science.gov (United States)

    Korre, Maria; Sotos-Prieto, Mercedes; Kales, Stefanos N

    2017-01-01

    Cardiovascular disease (CVD) causes almost half of all on-duty deaths in US firefighters and is an important and costly cause of morbidity. In addition, cancer is a growing health concern in this population. Obesity and obesity-associated, cardiometabolic risk clustering are major, modifiable risk factors for fire service CVD and cancer risk. The Mediterranean diet (MedDiet) is proven effective in primary and secondary CVD prevention. It is also associated with a decreased risk of cancer and other chronic diseases. Moreover, it can be adapted into successful workplace interventions. Emerging data from our group regarding the US Fire Service show that greater compliance with the MedDiet is associated with improved CVD risk profiles and less weight gain among career firefighters. Moreover, the fact that career firefighters take a considerable number of meals communally on the job also represents an excellent opportunity for a workplace Mediterranean Diet Nutritional Intervention (MDNI). The devastating effects of obesity, CVD, and cancer on the US fire service are recognized, but currently few effective preventive programs exist. The consistently positive health benefits from following a MedDiet and promising preliminary data in the fire service justify translational research to determine the most effective means of delivering MDNIs to US firefighters. Therefore, a high priority should be assigned to efforts, which can help further disseminate and implement our program of novel behavior change strategies, "Survival Mediterranean Style," throughout the US fire service and eventually to other occupations.

  12. Survival Mediterranean Style: Lifestyle Changes to Improve the Health of the US Fire Service

    Directory of Open Access Journals (Sweden)

    Maria Korre

    2017-12-01

    Full Text Available Cardiovascular disease (CVD causes almost half of all on-duty deaths in US firefighters and is an important and costly cause of morbidity. In addition, cancer is a growing health concern in this population. Obesity and obesity-associated, cardiometabolic risk clustering are major, modifiable risk factors for fire service CVD and cancer risk. The Mediterranean diet (MedDiet is proven effective in primary and secondary CVD prevention. It is also associated with a decreased risk of cancer and other chronic diseases. Moreover, it can be adapted into successful workplace interventions. Emerging data from our group regarding the US Fire Service show that greater compliance with the MedDiet is associated with improved CVD risk profiles and less weight gain among career firefighters. Moreover, the fact that career firefighters take a considerable number of meals communally on the job also represents an excellent opportunity for a workplace Mediterranean Diet Nutritional Intervention (MDNI. The devastating effects of obesity, CVD, and cancer on the US fire service are recognized, but currently few effective preventive programs exist. The consistently positive health benefits from following a MedDiet and promising preliminary data in the fire service justify translational research to determine the most effective means of delivering MDNIs to US firefighters. Therefore, a high priority should be assigned to efforts, which can help further disseminate and implement our program of novel behavior change strategies, “Survival Mediterranean Style,” throughout the US fire service and eventually to other occupations.

  13. Fire safety improvement of para-aramid fiber in thermoplastic polyurethane elastomer

    International Nuclear Information System (INIS)

    Chen, Xilei; Wang, Wenduo; Li, Shaoxiang; Jiao, Chuanmei

    2017-01-01

    Highlights: • Fire safety of para-aramid fiber on TPU has been investigated. • Para-aramid fiber has excellent flame retardant abilities and smoke suppression properties on TPU. • A new technique to improve the fire safety polymer is provided in this article. - Abstract: This article mainly studied fire safety effects of para-aramid fiber (AF) in thermoplastic polyurethane (TPU). The TPU/AF composites were prepared by molten blending method, and then the fire safety effects of all TPU composites were tested using cone calorimeter test (CCT), microscale combustion colorimeter test (MCC), smoke density test (SDT), and thermogravimetric/fourier transform infrared spectroscopy (TG-IR). The CCT test showed that AF could improve the fire safety of TPU. Remarkably, the peak value of heat release rate (pHRR) and the peak value of smoke production rate (pSPR) for the sample with 1.0 wt% content of AF were decreased by 52.0% and 40.5% compared with pure TPU, respectively. The MCC test showed that the HRR value of AF-2 decreased by 27.6% compared with pure TPU. TG test showed that AF promoted the char formation in the degradation process of TPU; as a result the residual carbon was increased. The TG-IR test revealed that AF had increased the thermal stability of TPU at the beginning and reduced the release of CO_2 with the decomposition going on. Through the analysis of the results of this experiment, it will make a great influence on the study of the para-aramid fiber in the aspect of fire safety of polymer.

  14. Fire safety improvement of para-aramid fiber in thermoplastic polyurethane elastomer

    Energy Technology Data Exchange (ETDEWEB)

    Chen, Xilei; Wang, Wenduo; Li, Shaoxiang; Jiao, Chuanmei, E-mail: jiaochm@qust.edu.cn

    2017-02-15

    Highlights: • Fire safety of para-aramid fiber on TPU has been investigated. • Para-aramid fiber has excellent flame retardant abilities and smoke suppression properties on TPU. • A new technique to improve the fire safety polymer is provided in this article. - Abstract: This article mainly studied fire safety effects of para-aramid fiber (AF) in thermoplastic polyurethane (TPU). The TPU/AF composites were prepared by molten blending method, and then the fire safety effects of all TPU composites were tested using cone calorimeter test (CCT), microscale combustion colorimeter test (MCC), smoke density test (SDT), and thermogravimetric/fourier transform infrared spectroscopy (TG-IR). The CCT test showed that AF could improve the fire safety of TPU. Remarkably, the peak value of heat release rate (pHRR) and the peak value of smoke production rate (pSPR) for the sample with 1.0 wt% content of AF were decreased by 52.0% and 40.5% compared with pure TPU, respectively. The MCC test showed that the HRR value of AF-2 decreased by 27.6% compared with pure TPU. TG test showed that AF promoted the char formation in the degradation process of TPU; as a result the residual carbon was increased. The TG-IR test revealed that AF had increased the thermal stability of TPU at the beginning and reduced the release of CO{sub 2} with the decomposition going on. Through the analysis of the results of this experiment, it will make a great influence on the study of the para-aramid fiber in the aspect of fire safety of polymer.

  15. Use of social networks to improve radiation protection

    International Nuclear Information System (INIS)

    Medina Gironzini, E.

    2013-01-01

    The development of information and communication technologies has improved relations between the specialists in radiation protection worldwide. Takes advantage of these media to exchange experiences on issues of common interest and technical concerns are resolved in very short times. (Author)

  16. Thermal Spray Coatings for High-Temperature Corrosion Protection in Biomass Co-Fired Boilers

    Science.gov (United States)

    Oksa, M.; Metsäjoki, J.; Kärki, J.

    2015-01-01

    There are over 1000 biomass boilers and about 500 plants using waste as fuel in Europe, and the numbers are increasing. Many of them encounter serious problems with high-temperature corrosion due to detrimental elements such as chlorides, alkali metals, and heavy metals. By HVOF spraying, it is possible to produce very dense and well-adhered coatings, which can be applied for corrosion protection of heat exchanger surfaces in biomass and waste-to-energy power plant boilers. Four HVOF coatings and one arc sprayed coating were exposed to actual biomass co-fired boiler conditions in superheater area with a probe measurement installation for 5900 h at 550 and 750 °C. The coating materials were Ni-Cr, IN625, Fe-Cr-W-Nb-Mo, and Ni-Cr-Ti. CJS and DJ Hybrid spray guns were used for HVOF spraying to compare the corrosion resistance of Ni-Cr coating structures. Reference materials were ferritic steel T92 and nickel super alloy A263. The circulating fluidized bed boiler burnt a mixture of wood, peat and coal. The coatings showed excellent corrosion resistance at 550 °C compared to the ferritic steel. At higher temperature, NiCr sprayed with CJS had the best corrosion resistance. IN625 was consumed almost completely during the exposure at 750 °C.

  17. Interim guidelines for protecting fire-fighting personnel from multiple hazards at nuclear plant sites

    International Nuclear Information System (INIS)

    Klein, A.R.; Bloom, C.W.

    1989-07-01

    This report provides interim guidelines for reducing the impact to fire fighting and other supporting emergency response personnel from the multiple hazards of radiation, heat stress, and trauma when fighting a fire in a United States commercial nuclear power plant. Interim guidelines are provided for fire brigade composition, training, equipment, procedures, strategies, heat stress and trauma. In addition, task definitions are provided to evaluate and further enhance the interim guidelines over the long term. 19 refs

  18. [Protecting Safety During Dust Fires and Dust Explosions - The Example of the Formosa Fun Coast Water Park Accident].

    Science.gov (United States)

    Hsieh, Ming-Hong; Wu, Jia-Wun; Li, Ya-Cing; Tang, Jia-Suei; Hsieh, Chun-Chien

    2016-02-01

    This paper will explore the fire and explosion characteristics of cornstarch powder as well as strategies for protecting the safety of people who are involved a dust fire or dust explosion. We discuss the 5 elements of dust explosions and conduct tests to analyze the fire and explosion characteristics of differently colored powders (yellow, golden yellow, pink, purple, orange and green). The results show that, while all of the tested powders were difficult to ignite, low moisture content was associated with significantly greater risks of ignition and flame spread. We found the auto-ignition temperature (AIT) of air-borne cornstarch powder to be between 385°C and 405°C, with yellow-colored cornstarch powder showing the highest AIT and pink-colored cornstarch powder showing the lowest AIT. The volume resistivity of all powder samples was approximately 108 Ω.m, indicating that they were nonconductive. Lighters and cigarettes are effective ignition sources, as their lit temperatures are higher than the AIT of cornstarch powder. In order to better protect the safety of individuals at venues where cornstarch powder is released, explosion control measures such as explosion containment facilities, vents, and explosion suppression and isolation devices should be installed. Furthermore, employees that work at these venues should be better trained in explosion prevention and control measures. We hope this article is a reminder to the public to recognize the fire and explosion characteristics of flammable powders as well as the preventive and control measures for dust explosions.

  19. Modeling the Pyrolysis and Combustion Behaviors of Non-Charring and Intumescent-Protected Polymers Using “FiresCone”

    Directory of Open Access Journals (Sweden)

    Long Shi

    2015-10-01

    Full Text Available A mathematical model, named FiresCone, was developed to simulate the pyrolysis and combustion processes of different types of combustible materials, which also took into account both gas and solid phases. In the present study, some non-charring and intumescent-protected polymer samples were investigated regarding their combustion behaviors in response to pre-determined external heat fluxes. The modeling results were validated against the experimental outcomes obtained from a cone calorimeter. The predicted mass loss rates of the samples were found to fit reasonably well with the experimental data collected under various levels of external irradiation. Both the experimental and modeling results showed that the peak mass loss rate of the non-charring polymer material occurred near the end of burning, whereas for the intumescent-protected polymer it happed shortly after the start of the experiment. “FiresCone” is expected to act as a practical tool for the investigation of fire behavior of combustible materials. It is also expected to model fire scenarios under complicated conditions.

  20. Improving fire season definition by optimized temporal modelling of daily human-caused ignitions.

    Science.gov (United States)

    Costafreda-Aumedes, S; Vega-Garcia, C; Comas, C

    2018-07-01

    Wildfire suppression management is usually based on fast control of all ignitions, especially in highly populated countries with pervasive values-at-risk. To minimize values-at-risk loss by improving response time of suppression resources it is necessary to anticipate ignitions, which are mainly caused by people. Previous studies have found that human-ignition patterns change spatially and temporally depending on socio-economic activities, hence, the deployment of suppression resources along the year should consider these patterns. However, full suppression capacity is operational only within legally established fire seasons, driven by past events and budgets, which limits response capacity and increases damages out of them. The aim of this study was to assess the temporal definition of fire seasons from the perspective of human-ignition patterns for the case study of Spain, where people cause over 95% of fires. Humans engage in activities that use fire as a tool in certain periods within a year, and in locations linked to specific spatial factors. Geographic variables (population, infrastructures, physiography and land uses) were used as explanatory variables for human-ignition patterns. The changing influence of these geographic variables on occurrence along the year was analysed with day-by-day logistic regression models. Daily models were built for all the municipal units in the two climatic regions in Spain (Atlantic and Mediterranean Spain) from 2002 to 2014, and similar models were grouped within continuous periods, designated as ignition-based seasons. We found three ignition-based seasons in the Mediterranean region and five in the Atlantic zones, not coincidental with calendar seasons, but with a high degree of agreement with current legally designated operational fire seasons. Our results suggest that an additional late-winter-early-spring fire season in the Mediterranean area and the extension of this same season in the Atlantic zone should be re

  1. Risk reduction in road and rail LPG transportation bij passive fire protection

    NARCIS (Netherlands)

    Molag e.a., M. (Menso)

    2009-01-01

    The potential reduction of risk in LPG (Liquified Petroleum Gas) road transport due to the adoption of passive fire protectionswas investigated. Experimental data available for small scale vessels fully engulfed by a fire were extended to real scale road and rail tankers through a finite elements

  2. Technologies for Protection and Resistance Enhancement of Critical Infrastructures againstExtreme Fire

    Science.gov (United States)

    2014-05-01

    involving hydrocarbon fires, such as gasoline or crude oil carried in a tanker truck/train, or any other fuel fire of equivalent intensity. Examples of...and impact of weather exposure on the insulation, as well as possible health risk by inhalation (mainly concern for interior application), application

  3. United States Department of Energy's reactor core protection evaluation methodology for fires at RBMK and VVER nuclear power plants. Revision 1

    International Nuclear Information System (INIS)

    1997-06-01

    This document provides operators of Soviet-designed RBMK (graphite moderated light water boiling water reactor) and VVER (pressurized light water reactor) nuclear power plants with a systematic Methodology to qualitatively evaluate plant response to fires and to identify remedies to protect the reactor core from fire-initiated damage

  4. Aircraft Instrument, Fire Protection, Warning, Communication, Navigation and Cabin Atmosphere Control System (Course Outline), Aviation Mechanics 3 (Air Frame): 9067.04.

    Science.gov (United States)

    Dade County Public Schools, Miami, FL.

    This document presents an outline for a 135-hour course designed to familiarize the student with manipulative skills and theoretical knowledge concerning aircraft instrument systems like major flight and engine instruments; fire protection and fire fighting systems; warning systems and navigation systems; aircraft cabin control systems, such as…

  5. An improved algorithm for small and cool fire detection using MODIS data: A preliminary study in the southeastern United States

    Science.gov (United States)

    Wanting Wang; John J. Qu; Xianjun Hao; Yongqiang Liu; William T. Sommers

    2006-01-01

    Traditional fire detection algorithms mainly rely on hot spot detection using thermal infrared (TIR) channels with fixed or contextual thresholds. Three solar reflectance channels (0.65 μm, 0.86 μm, and 2.1 μm) were recently adopted into the MODIS version 4 contextual algorithm to improve the active fire detection. In the southeastern United...

  6. Alternative approach for fire suppression of class A, B and C fires in gloveboxes

    Energy Technology Data Exchange (ETDEWEB)

    Rosenberger, Mark S [Los Alamos National Laboratory; Tsiagkouris, James A [Los Alamos National Laboratory

    2011-02-10

    Department of Energy (DOE) Orders and National Fire Protection Association (NFPA) Codes and Standards require fire suppression in gloveboxes. Several potential solutions have been and are currently being considered at Los Alamos National Laboratory (LANL). The objective is to provide reliable, minimally invasive, and seismically robust fire suppression capable of extinguishing Class A, B, and C fires; achieve compliance with DOE and NFPA requirements; and provide value-added improvements to fire safety in gloveboxes. This report provides a brief summary of current approaches and also documents the successful fire tests conducted to prove that one approach, specifically Fire Foe{trademark} tubes, is capable of achieving the requirement to provide reliable fire protection in gloveboxes in a cost-effective manner.

  7. Potential effects of the fire protection system sprays at Browns Ferry on fission product transport

    International Nuclear Information System (INIS)

    Niemczyk, S.J.

    1983-01-01

    The fire protection system (FPS) sprays within any nuclear plant are not intended to mitigate radioactive releases to the environment resulting from severe core-damage accidents. However, it has been shown here that during certain postulated severe accident scenarios at the Browns Ferry Nuclear Plant, the functioning of FPS sprays could have a significant impact on the radioactive releases. Thus the effects of those sprays need to be taken into account for realistic estimation of source terms for some accident scenarios. The effects would include direct ones such as cooling of the reactor building atmosphere and scrubbing of radioactivity from it, as well as indirect effects such as an altered likelihood of hydrogen burning and flooding of various safety-related pumps in the reactor building basement. Thus some of the impacts of the sprays would be beneficial with respect to mitigating releases to the environment but some others might not be. The effects of the FPS would be very scenario dependent with a wide range of potential effects often existing for a given accident sequence. Any generalization of the specific results presented here for Browns Ferry to other nuclear plants must be done cautiously, as it appears from a preliminary investigation that the relevant physical and operational characteristics of FPS spray systems differ widely among even otherwise apparently similar plants. Likewise the standby gas treatment systems, which substantially impact the effects of the FPS, differ significantly among plants. More work for both Mark I plants and other plants, BWRs and PWRs alike, is indicated so the potential effects of FPS spray systems during severe accidents can be at least ball-parked for more realistic accident analyses

  8. Monitoring of cloudiness in the function of the forests fire protection

    Directory of Open Access Journals (Sweden)

    Živanović Stanimir

    2016-01-01

    Full Text Available Fires in forests are seasonal in nature, conditioned by the moisture content of the fuel material. The emergence of these fires in Serbia is becoming more common and depending on the intensity and duration, fires have a major impact on the state of vegetation. The aim of this study was to determine the correlation between dynamics of cloudiness occurrence and forest fires. To study the correlation of these elements, Pearson correlation coefficients were used. The analysis is based on the meteorological data obtained from meteorological station Negotin for the period from 1991 to 2010. Among the tested influences, the degree of cloudiness showed positive correlative interdependence with the dynamics of fire occurrence in nature. The annual number of fires correlates positively with the average number of clear days (p = 0.25. Also, it was found that the annual number of fires with medium intensity, correlated negatively with the average number of cloudy days (p= -0.26, but not statistically significant (p> 0.05.

  9. Iron aluminide weld overlay coatings for boiler tube protection in coal-fired low NOx boilers

    Energy Technology Data Exchange (ETDEWEB)

    Banovic, S.W.; DuPont, J.N.; Marder, A.R. [Lehigh Univ., Bethlehem, PA (United States). Energy Research Center

    1997-12-01

    Iron aluminide weld overlay coatings are currently being considered for enhanced sulfidation resistance in coal-fired low NO{sub x} boilers. The use of these materials is currently limited due to hydrogen cracking susceptibility, which generally increases with an increase in aluminum concentration of the deposit. The overall objective of this program is to attain an optimum aluminum content with good weldability and improved sulfidation resistance with respect to conventional materials presently in use. Research has been initiated using Gas Tungsten Arc Welding (GTAW) in order to achieve this end. Under different sets of GTAW parameters (wire feed speed, current), both single and multiple pass overlays were produced. Characterization of all weldments was conducted using light optical microscopy, scanning electron microscopy, and electron probe microanalysis. Resultant deposits exhibited a wide range of aluminum contents (5--43 wt%). It was found that the GTAW overlays with aluminum contents above {approximately}10 wt% resulted in cracked coatings. Preliminary corrosion experiments of 5 to 10 wt% Al cast alloys in relatively simple H{sub 2}/H{sub 2}S gas mixtures exhibited corrosion rates lower than 304 stainless steel.

  10. Geostationary Sensor Based Forest Fire Detection and Monitoring: An Improved Version of the SFIDE Algorithm

    Directory of Open Access Journals (Sweden)

    Valeria Di Biase

    2018-05-01

    Full Text Available The paper aims to present the results obtained in the development of a system allowing for the detection and monitoring of forest fires and the continuous comparison of their intensity when several events occur simultaneously—a common occurrence in European Mediterranean countries during the summer season. The system, called SFIDE (Satellite FIre DEtection, exploits a geostationary satellite sensor (SEVIRI, Spinning Enhanced Visible and InfraRed Imager, on board of MSG, Meteosat Second Generation, satellite series. The algorithm was developed several years ago in the framework of a project (SIGRI funded by the Italian Space Agency (ASI. This algorithm has been completely reviewed in order to enhance its efficiency by reducing false alarms rate preserving a high sensitivity. Due to the very low spatial resolution of SEVIRI images (4 × 4 km2 at Mediterranean latitude the sensitivity of the algorithm should be very high to detect even small fires. The improvement of the algorithm has been obtained by: introducing the sun elevation angle in the computation of the preliminary thresholds to identify potential thermal anomalies (hot spots, introducing a contextual analysis in the detection of clouds and in the detection of night-time fires. The results of the algorithm have been validated in the Sardinia region by using ground true data provided by the regional Corpo Forestale e di Vigilanza Ambientale (CFVA. A significant reduction of the commission error (less than 10% has been obtained with respect to the previous version of the algorithm and also with respect to fire-detection algorithms based on low earth orbit satellites.

  11. Detection and Characterization of Low Temperature Peat Fires during the 2015 Fire Catastrophe in Indonesia Using a New High-Sensitivity Fire Monitoring Satellite Sensor (FireBird)

    Science.gov (United States)

    Atwood, Elizabeth C.; Englhart, Sandra; Lorenz, Eckehard; Halle, Winfried; Wiedemann, Werner; Siegert, Florian

    2016-01-01

    Vast and disastrous fires occurred on Borneo during the 2015 dry season, pushing Indonesia into the top five carbon emitting countries. The region was affected by a very strong El Niño-Southern Oscillation (ENSO) climate phenomenon, on par with the last severe event in 1997/98. Fire dynamics in Central Kalimantan were investigated using an innovative sensor offering higher sensitivity to a wider range of fire intensities at a finer spatial resolution (160 m) than heretofore available. The sensor is onboard the TET-1 satellite, part of the German Aerospace Center (DLR) FireBird mission. TET-1 images (acquired every 2–3 days) from the middle infrared were used to detect fires continuously burning for almost three weeks in the protected peatlands of Sebangau National Park as well as surrounding areas with active logging and oil palm concessions. TET-1 detection capabilities were compared with MODIS active fire detection and Landsat burned area algorithms. Fire dynamics, including fire front propagation speed and area burned, were investigated. We show that TET-1 has improved detection capabilities over MODIS in monitoring low-intensity peatland fire fronts through thick smoke and haze. Analysis of fire dynamics revealed that the largest burned areas resulted from fire front lines started from multiple locations, and the highest propagation speeds were in excess of 500 m/day (all over peat > 2m deep). Fires were found to occur most often in concessions that contained drainage infrastructure but were not cleared prior to the fire season. Benefits of implementing this sensor system to improve current fire management techniques are discussed. Near real-time fire detection together with enhanced fire behavior monitoring capabilities would not only improve firefighting efforts, but also benefit analysis of fire impact on tropical peatlands, greenhouse gas emission estimations as well as mitigation measures to reduce severe fire events in the future. PMID:27486664

  12. Detection and Characterization of Low Temperature Peat Fires during the 2015 Fire Catastrophe in Indonesia Using a New High-Sensitivity Fire Monitoring Satellite Sensor (FireBird).

    Science.gov (United States)

    Atwood, Elizabeth C; Englhart, Sandra; Lorenz, Eckehard; Halle, Winfried; Wiedemann, Werner; Siegert, Florian

    2016-01-01

    Vast and disastrous fires occurred on Borneo during the 2015 dry season, pushing Indonesia into the top five carbon emitting countries. The region was affected by a very strong El Niño-Southern Oscillation (ENSO) climate phenomenon, on par with the last severe event in 1997/98. Fire dynamics in Central Kalimantan were investigated using an innovative sensor offering higher sensitivity to a wider range of fire intensities at a finer spatial resolution (160 m) than heretofore available. The sensor is onboard the TET-1 satellite, part of the German Aerospace Center (DLR) FireBird mission. TET-1 images (acquired every 2-3 days) from the middle infrared were used to detect fires continuously burning for almost three weeks in the protected peatlands of Sebangau National Park as well as surrounding areas with active logging and oil palm concessions. TET-1 detection capabilities were compared with MODIS active fire detection and Landsat burned area algorithms. Fire dynamics, including fire front propagation speed and area burned, were investigated. We show that TET-1 has improved detection capabilities over MODIS in monitoring low-intensity peatland fire fronts through thick smoke and haze. Analysis of fire dynamics revealed that the largest burned areas resulted from fire front lines started from multiple locations, and the highest propagation speeds were in excess of 500 m/day (all over peat > 2m deep). Fires were found to occur most often in concessions that contained drainage infrastructure but were not cleared prior to the fire season. Benefits of implementing this sensor system to improve current fire management techniques are discussed. Near real-time fire detection together with enhanced fire behavior monitoring capabilities would not only improve firefighting efforts, but also benefit analysis of fire impact on tropical peatlands, greenhouse gas emission estimations as well as mitigation measures to reduce severe fire events in the future.

  13. 46 CFR 28.330 - Galley hood and other fire protection equipment.

    Science.gov (United States)

    2010-10-01

    ... Stage of Construction on or After or Which Undergo a Major Conversion Completed on or After September 15... pre-engineered dry or wet chemical fire extinguishing system meeting the applicable sections of NFPA...

  14. Aircraft Carrier Flight and Hangar Deck Fire Protection: History and Current Status

    National Research Council Canada - National Science Library

    Darwin, Robert L; Bowman, Howard L; Hunstad, Mary; Leach, William B; Williams, Frederick W

    2005-01-01

    .... Next, a review of firefighting systems, including the firefighting agents currently in use, as well as the current tactics for fighting fires on the flight deck and the hangar deck, is provided...

  15. Fire and lightning: what are the risks and how to be protected?

    International Nuclear Information System (INIS)

    Rigal, F.

    2011-01-01

    This article reviews the risks of fire and lightning on photovoltaic panels installed on roofs. It appears that the risk of lighting must be taken into account since the direct impact of lightning on photovoltaic panels can be disastrous. The installation of lightning rods or lightning protector is recommended. Concerning fire risks, technical failures or the presence of electric arcs can put fire on solar panels but their occurrence is very low (only about 20 cases reported in Europe for the last 10 years). Tests have shown that standard photovoltaic panels play a low part in the progressing of a fire. There is an electrocution hazard for firemen intervening on a roof bearing solar panels. A device cutting the continuous current generating by the panels is being studied. (A.C.)

  16. Perspective pulse devices and automatic systems fire explosive protection of the radioactive infected objects

    International Nuclear Information System (INIS)

    Zakhmatov, V.D.; Kozhemyakin, A.S.; Pyatova, A.V.

    1999-01-01

    The suppression of fires in Chernobyl zone has shown complete unprofitable of traditional fire engineering to work on is radioactive of the infected district. In this connection as effective ways extinguishive in object 'Shelter' alongside with known traditional means and the systems offer to apply more perspective pulse systems, based on use energy small practically safe charges of gunpowder or explosive substances, in particular. Pulse explosive cone extinguishive of the device various sizes

  17. Flexural behaviour of partially bonded carbon fibre reinforced polymers strengthened concrete beams: Application to fire protection systems design

    International Nuclear Information System (INIS)

    Firmo, J.P.; Arruda, M.R.T.; Correia, J.R.; Tiago, C.

    2015-01-01

    Highlights: • The mechanical behaviour of partially bonded CFRP strengthened beams was modelled. • Two dimensional non-linear finite element models were developed. • Partially bonded beams can present similar flexural strength to fully bonded ones. • Relations between the bonded length and the strength reduction were proposed. • The proposed relations were used for the design of fire protection systems. - Abstract: Recent fire resistance tests on reinforced concrete (RC) beams strengthened with carbon fibre reinforced polymers (CFRP) laminates showed that it is possible to attain considerable fire endurance provided that thermal insulation is applied at the anchorage zones of the strengthening system. With such protection, although the CFRP laminate prematurely debonds in the central part of the beam, it transforms into a cable fixed at the extremities until one of the anchorage zones loses its bond strength. The main objective of this paper is to propose a simplified methodology for the design of fire protection systems for CFRP strengthened-RC beams, which is based on applying thicker insulation at the anchorage zones (promoting the above mentioned “cable behaviour”) and a thinner one at the current zone (avoiding tensile rupture of the carbon fibres). As a first step towards the validation of this methodology, finite element (FE) models were developed to simulate the flexural behaviour at ambient temperature of full-scale RC beams strengthened with CFRP laminates according to the externally bonded reinforcement (EBR) and near surface mounted (NSM) techniques, in both cases fully or partially bonded (the latter simulating the cable). The FE models were calibrated with results of 4-point bending tests on small-scale beams and then extended for different beam geometries, with spans (L) varying from 2 m to 5 m, in which the influence of the CFRP bonded length (l b ) and the loading type (point or uniformly distributed) on the strength reduction was

  18. High temperature corrosion during biomass firing: improved understanding by depth resolved characterisation of corrosion products

    DEFF Research Database (Denmark)

    Okoro, Sunday Chukwudi; Montgomery, Melanie; Jappe Frandsen, Flemming

    2015-01-01

    changes within the near surface region (covering both the deposit and the steel surface). Such cross-section analysis was further complemented by plan view investigations (additionally involving X-ray diffraction) combined with removal of the corrosion products. Improved insights into the nature......The high temperature corrosion of an austenitic stainless steel (TP 347H FG), widely utilised as a superheater tube material in Danish power stations, was investigated to verify the corrosion mechanisms related to biomass firing. KCl coated samples were exposed isothermally to 560 degrees C...... of the corrosion products as a function of distance from the deposit surface were revealed through this comprehensive characterisation. Corrosion attack during simulated straw-firing conditions was observed to occur through both active oxidation and sulphidation mechanisms....

  19. Fire Event Data from Licensee Event Reports

    Data.gov (United States)

    Nuclear Regulatory Commission — The purpose of this study data is to provide a metric with which to assess the effectiveness of improvements to the U.S. NRC's fire protection regulations in support...

  20. A New Method of Improving Transformer Restricted Earth Fault Protection

    Directory of Open Access Journals (Sweden)

    KRSTIVOJEVIC, J. P.

    2014-08-01

    Full Text Available A new method of avoiding malfunctioning of the transformer restricted earth fault (REF protection is presented. Application of the proposed method would eliminate unnecessary operation of REF protection in the cases of faults outside protected zone of a transformer or a magnetizing inrush accompanied by current transformer (CT saturation. On the basis of laboratory measurements and simulations the paper presents a detailed performance assessment of the proposed method which is based on digital phase comparator. The obtained results show that the new method was stable and precise for all tested faults and that its application would allow making a clear and precise difference between an internal fault and: (i external fault or (ii magnetizing inrush. The proposed method would improve performance of REF protection and reduce probability of maloperation due to CT saturation. The new method is robust and characterized by high speed of operation and high reliability and security.

  1. Can fire safety in hotels be improved? Results from the survey of a panel of experts in Spain.

    Science.gov (United States)

    Rubio-Romero, Juan Carlos; Márquez-Sierra, Francisco; Suárez-Cebador, Manuel

    2016-06-08

    The hotel industry is an important driver of the European labour market with over 250,000 hotels employing some 2 million people. In Spain, 240 workers were injured by fires in hotels from 2004 to 2008. Fire is considered to be the most important risk in the hotel industry, but the lack of an EU-wide data recording system for hotels makes it difficult to give exact figures for fire events. We analysed the state of fire prevention systems in hotels in Spain with the aim of proposing strategies to improve fire safety. A 10-item questionnaire was administered from 2007 to 2009 to 15 Spanish experts in fire safety. The questions were measured using a Likert scale and classified into 4 sections: current state of installations, influence of establishment characteristics, application of regulations and priority ranking of actions. Descriptive statistics summarized the data and t-tests evaluated the agreement foreach statement in the questionnaire. The statistical analysis showed homogeneity in the responses by the experts in all four categories: current state of fire safety installations, influence of establishment characteristics, application of regulations, and priority of actions. There was consensus among the experts over the necessity to improve the enforcement of regulations and also regarding the existence of an association between the hotel category (in Spain they are ranked using a 1 to 5 "star" rating system) and the level of fire safety; hotels with a higher category had higher levels of safety. There is a need to identify ways to apply fire safety standards to older hotels so that they comply with new regulations, to standardize regulations for different regions and countries, to improve the maintenance of installations and equipment, to increase the effectiveness of inspections conducted by government bodies, and to raise the general awareness of stakeholders involved in hotel fire prevention.

  2. Applying principles from safety science to improve child protection.

    Science.gov (United States)

    Cull, Michael J; Rzepnicki, Tina L; O'Day, Kathryn; Epstein, Richard A

    2013-01-01

    Child Protective Services Agencies (CPSAs) share many characteristics with other organizations operating in high-risk, high-profile industries. Over the past 50 years, industries as diverse as aviation, nuclear power, and healthcare have applied principles from safety science to improve practice. The current paper describes the rationale, characteristics, and challenges of applying concepts from the safety culture literature to CPSAs. Preliminary efforts to apply key principles aimed at improving child safety and well-being in two states are also presented.

  3. Fire protection considerations in the design of plutonium handling and storage facility

    International Nuclear Information System (INIS)

    Blanchard, A.

    2000-01-01

    Unwanted fire in a facility that handles plutonium must be addressed early in the facility design. Such fires have the potential for transporting radioactive contamination throughout the building and widespread downwind dispersal. Features that mitigate such events can be severely challenged during the fire. High temperatures can cause storage containers to burst; a very efficient dispersal mechanism for radioactive contamination. The fire will also establish ventilation patterns that cause the migration of smoke and radioactive contamination throughout the facility. The smoke and soot generated by the fire will enter the exhaust system and travel to the filtration system where it will deposit on the filters. The quantity of smoke generated during a typical multi-room fire is expected to blind most High Efficiency Particulate Airfilter (HEPA) media. The blinding can have two possible outcomes. (1) The air movement though the facility is reduced, compromising the negative pressure containment and allowing contamination to leave the building though doors and other openings; or (2) the filters collapse allowing the contamination to bypass the filtration media and exit the building through the filter plenum. HEPA filter blinding during severe fires can be prevented or mitigated. Increasing the face surface area of HEPA filters will increase the smoke filtration capacity of the system, thus preventing blinding. As an alternative sandfilters can be provided to mitigate the effects of the HEPA filter bypass. Both concepts have distinct advantages. This paper will explore these two design concepts and two others; it will describe the design requirements necessary for each concept to prevent unacceptable contamination spread. The intent is to allow the filter media selection to be based on a comprehensive understanding of the four different design concepts

  4. Forest fires

    International Nuclear Information System (INIS)

    Fuller, M.

    1991-01-01

    This book examines the many complex and sensitive issues relating to wildland fires. Beginning with an overview of the fires of 1980s, the book discusses the implications of continued drought and considers the behavior of wildland fires, from ignition and spread to spotting and firestorms. Topics include the effects of weather, forest fuels, fire ecology, and the effects of fire on plants and animals. In addition, the book examines firefighting methods and equipment, including new minimum impact techniques and compressed air foam; prescribed burning; and steps that can be taken to protect individuals and human structures. A history of forest fire policies in the U.S. and a discussion of solutions to fire problems around the world completes the coverage. With one percent of the earth's surface burning every year in the last decade, this is a penetrating book on a subject of undeniable importance

  5. Improving 200 MW NDHR reactor protection system with GAL devices

    International Nuclear Information System (INIS)

    Shi Mingde; Li Duo; Xie Zhengguo

    1999-01-01

    The emergence of General Array Logic (GAL), a fairly new type of logic devices with the characteristics of user-definable logic functions, have led to a revolutionary change in the design of logical circuits. The improvements of the reactor protection system for the 200 MW nuclear district heating reactor (NDHR) using GAL are covered

  6. Compositions comprising lignosulfonates for crop protection and crop improvement

    NARCIS (Netherlands)

    Stevens, L.H.; Kok, C.J.; Krieken, van der W.M.

    2009-01-01

    International patent application number: WO2004067699http://www.wipo.int/patentscope/search/en/WO2004067699 (EN)The invention relates to a composition for protecting an agricultural crop against external threats, such as weeds, pathogens, abiotic and biotic stresses and/or for improving the quality

  7. Improving privacy protection in the area of behavioural targeting

    NARCIS (Netherlands)

    Zuiderveen Borgesius, F.J.

    2014-01-01

    This PhD thesis discusses how European law could improve privacy protection in the area of behavioural targeting. Behavioural targeting, also referred to as online profiling, involves monitoring people’s online behaviour, and using the collected information to show people individually targeted

  8. An evaluation of The Great Escape: can an interactive computer game improve young children's fire safety knowledge and behaviors?

    Science.gov (United States)

    Morrongiello, Barbara A; Schwebel, David C; Bell, Melissa; Stewart, Julia; Davis, Aaron L

    2012-07-01

    Fire is a leading cause of unintentional injury and, although young children are at particularly increased risk, there are very few evidence-based resources available to teach them fire safety knowledge and behaviors. Using a pre-post randomized design, the current study evaluated the effectiveness of a computer game (The Great Escape) for teaching fire safety information to young children (3.5-6 years). Using behavioral enactment procedures, children's knowledge and behaviors related to fire safety were compared to a control group of children before and after receiving the intervention. The results indicated significant improvements in knowledge and fire safety behaviors in the intervention group but not the control. Using computer games can be an effective way to promote young children's understanding of safety and how to react in different hazardous situations.

  9. Wildland Fire Management Plan for Brookhaven National Laboratory

    International Nuclear Information System (INIS)

    Schwager, K.; Green, T. M.

    2014-01-01

    The DOE policy for managing wildland fires requires that all areas managed by DOE and/or Its various contractors which can sustain fire must have a FMP that details fire management guidelines for operational procedures associated with wildland fire, operational, and prescribed fires. FMPs provide guidance on fire preparedness, fire prevention, wildfire suppression, and the use of controlled ''prescribed'' fires and mechanical means to control the amount of available combustible material. Values reflected in the BNL Wildland FMP include protecting life and public safety; Lab properties, structures and improvements; cultural and historical sites; neighboring private and public properties; and endangered, threatened, and species of concern. Other values supported by the plan include the enhancement of fire-dependent ecosystems at BNL. The plan will be reviewed periodically to ensure fire program advances and will evolve with the missions of DOE and BNL.

  10. Wildland Fire Management Plan for Brookhaven National Laboratory

    Energy Technology Data Exchange (ETDEWEB)

    Schwager, K.; Green, T. M.

    2014-10-01

    The DOE policy for managing wildland fires requires that all areas managed by DOE and/or Its various contractors which can sustain fire must have a FMP that details fire management guidelines for operational procedures associated with wildland fire, operational, and prescribed fires. FMPs provide guidance on fire preparedness, fire prevention, wildfire suppression, and the use of controlled ''prescribed'' fires and mechanical means to control the amount of available combustible material. Values reflected in the BNL Wildland FMP include protecting life and public safety; Lab properties, structures and improvements; cultural and historical sites; neighboring private and public properties; and endangered, threatened, and species of concern. Other values supported by the plan include the enhancement of fire-dependent ecosystems at BNL. The plan will be reviewed periodically to ensure fire program advances and will evolve with the missions of DOE and BNL.

  11. Improving satellite-based post-fire evapotranspiration estimates in semi-arid regions

    Science.gov (United States)

    Poon, P.; Kinoshita, A. M.

    2017-12-01

    Climate change and anthropogenic factors contribute to the increased frequency, duration, and size of wildfires, which can alter ecosystem and hydrological processes. The loss of vegetation canopy and ground cover reduces interception and alters evapotranspiration (ET) dynamics in riparian areas, which can impact rainfall-runoff partitioning. Previous research evaluated the spatial and temporal trends of ET based on burn severity and observed an annual decrease of 120 mm on average for three years after fire. Building upon these results, this research focuses on the Coyote Fire in San Diego, California (USA), which burned a total of 76 km2 in 2003 to calibrate and improve satellite-based ET estimates in semi-arid regions affected by wildfire. The current work utilizes satellite-based products and techniques such as the Google Earth Engine Application programming interface (API). Various ET models (ie. Operational Simplified Surface Energy Balance Model (SSEBop)) are compared to the latent heat flux from two AmeriFlux eddy covariance towers, Sky Oaks Young (US-SO3), and Old Stand (US-SO2), from 2000 - 2015. The Old Stand tower has a low burn severity and the Young Stand tower has a moderate to high burn severity. Both towers are used to validate spatial ET estimates. Furthermore, variables and indices, such as Enhanced Vegetation Index (EVI), Normalized Difference Moisture Index (NDMI), and the Normalized Burn Ratio (NBR) are utilized to evaluate satellite-based ET through a multivariate statistical analysis at both sites. This point-scale study will able to improve ET estimates in spatially diverse regions. Results from this research will contribute to the development of a post-wildfire ET model for semi-arid regions. Accurate estimates of post-fire ET will provide a better representation of vegetation and hydrologic recovery, which can be used to improve hydrologic models and predictions.

  12. Drought, Fire and Insects in Western US Forests: Observations to Improve Regional Land System Modeling

    Science.gov (United States)

    Law, B. E.; Yang, Z.; Berner, L. T.; Hicke, J. A.; Buotte, P.; Hudiburg, T. W.

    2015-12-01

    Drought, fire and insects are major disturbances in the western US, and conditions are expected to get warmer and drier in the future. We combine multi-scale observations and modeling with CLM4.5 to examine the effects of these disturbances on forests in the western US. We modified the Community Land Model, CLM4.5, to improve simulated drought-related mortality in forests, and prediction of insect outbreaks under future climate conditions. We examined differences in plant traits that represent species variation in sensitivity to drought, and redefined plant groupings in PFTs. Plant traits, including sapwood area: leaf area ratio and stemwood density were strongly correlated with water availability during the ecohydrologic year. Our database of co-located observations of traits for 30 tree species was used to produce parameterization of the model by species groupings according to similar traits. Burn area predicted by the new fire model in CLM4.5 compares well with recent years of GFED data, but has a positive bias compared with Landsat-based MTBS. Biomass mortality over recent decades increased, and was captured well by the model in general, but missed mortality trends of some species. Comparisons with AmeriFlux data showed that the model with dynamic tree mortality only (no species trait improvements) overestimated GPP in dry years compared with flux data at semi-arid sites, and underestimated GPP at more mesic sites that experience dry summers. Simulations with both dynamic tree mortality and species trait parameters improved estimates of GPP by 17-22%; differences between predicted and observed NEE were larger. Future projections show higher productivity from increased atmospheric CO2 and warming that somewhat offsets drought and fire effects over the next few decades. Challenges include representation of hydraulic failure in models, and availability of species trait and carbon/water process data in disturbance- and drought-impacted regions.

  13. IMPROVING THE INTEROPERABILITY OF DISASTER MODELS: A CASE STUDY OF PROPOSING FIREML FOR FOREST FIRE MODEL

    Directory of Open Access Journals (Sweden)

    W. Jiang

    2018-04-01

    Full Text Available This paper presents a new standardized data format named Fire Markup Language (FireML, extended by the Geography Markup Language (GML of OGC, to elaborate upon the fire hazard model. The proposed FireML is able to standardize the input and output documents of a fire model for effectively communicating with different disaster management systems to ensure a good interoperability. To demonstrate the usage of FireML and testify its feasibility, an adopted forest fire spread model being compatible with FireML is described. And a 3DGIS disaster management system is developed to simulate the dynamic procedure of forest fire spread with the defined FireML documents. The proposed approach will enlighten ones who work on other disaster models' standardization work.

  14. Improving the Interoperability of Disaster Models: a Case Study of Proposing Fireml for Forest Fire Model

    Science.gov (United States)

    Jiang, W.; Wang, F.; Meng, Q.; Li, Z.; Liu, B.; Zheng, X.

    2018-04-01

    This paper presents a new standardized data format named Fire Markup Language (FireML), extended by the Geography Markup Language (GML) of OGC, to elaborate upon the fire hazard model. The proposed FireML is able to standardize the input and output documents of a fire model for effectively communicating with different disaster management systems to ensure a good interoperability. To demonstrate the usage of FireML and testify its feasibility, an adopted forest fire spread model being compatible with FireML is described. And a 3DGIS disaster management system is developed to simulate the dynamic procedure of forest fire spread with the defined FireML documents. The proposed approach will enlighten ones who work on other disaster models' standardization work.

  15. Consumer Protection Strategies: A Literature Review and Synthesis. Improving the Consumer Protection Function in Postsecondary Education.

    Science.gov (United States)

    Helliwell, Carolyn B.; Jung, Steven M.

    Summarized are the findings of an American Institutes for Research (AIR) project to field test a data capture and dissemination system that would provide information for improving consumer protection in postsecondary education. Presented is a discussion of the methodology used, examples of consumer abuses cited in the literature, an analysis of…

  16. Improving freight fire safety : experiment testing and computer modeling to further development of mist-controlling additives for fire mitigation.

    Science.gov (United States)

    2012-08-01

    With the purpose to minimize or prevent crash-induced fires in road and rail transportation, the : current interest in bio-derived and blended transportation fuels is increasing. Based on two years : of preliminary testing and analysis, it appears to...

  17. 75 FR 66735 - National Fire Protection Association (NFPA): Request for Comments on NFPA's Codes and Standards

    Science.gov (United States)

    2010-10-29

    ... 59A Standard for the P Production, Storage, and Handling of Liquefied Natural Gas (LNG). NFPA 75... Horizontally in Fire Resistance-Rated Floor Systems. NFPA 385 Standard for Tank P Vehicles for Flammable and Combustible Liquids. NFPA 497 Recommended Practice P for the Classification of Flammable Liquids, Gases, or...

  18. Social protection: potential for improving HIV outcomes among adolescents.

    Science.gov (United States)

    Cluver, Lucie D; Hodes, Rebecca J; Sherr, Lorraine; Orkin, F Mark; Meinck, Franziska; Lim Ah Ken, Patricia; Winder-Rossi, Natalia E; Wolfe, Jason; Vicari, Marissa

    2015-01-01

    Advances in biomedical technologies provide potential for adolescent HIV prevention and HIV-positive survival. The UNAIDS 90-90-90 treatment targets provide a new roadmap for ending the HIV epidemic, principally through antiretroviral treatment, HIV testing and viral suppression among people with HIV. However, while imperative, HIV treatment and testing will not be sufficient to address the epidemic among adolescents in Southern and Eastern Africa. In particular, use of condoms and adherence to antiretroviral therapy (ART) remain haphazard, with evidence that social and structural deprivation is negatively impacting adolescents' capacity to protect themselves and others. This paper examines the evidence for and potential of interventions addressing these structural deprivations. New evidence is emerging around social protection interventions, including cash transfers, parenting support and educational support ("cash, care and classroom"). These interventions have the potential to reduce the social and economic drivers of HIV risk, improve utilization of prevention technologies and improve adherence to ART for adolescent populations in the hyper-endemic settings of Southern and Eastern Africa. Studies show that the integration of social and economic interventions has high acceptability and reach and that it holds powerful potential for improved HIV, health and development outcomes. Social protection is a largely untapped means of reducing HIV-risk behaviours and increasing uptake of and adherence to biomedical prevention and treatment technologies. There is now sufficient evidence to include social protection programming as a key strategy not only to mitigate the negative impacts of the HIV epidemic among families, but also to contribute to HIV prevention among adolescents and potentially to remove social and economic barriers to accessing treatment. We urge a further research and programming agenda: to actively combine programmes that increase availability of

  19. CONCEPTS OF IMPROVING CURRENT PROTECTION OF POWER-GRID LINES

    Directory of Open Access Journals (Sweden)

    F. A. Romaniuk

    2015-01-01

    Full Text Available The  6–35  kV  power-grid  current  protection  serves  to  protect  the  transmission  lines against phase-to-phase short-circuits. The major disadvantage of it lies in the relatively large time delays of the last stages especially in the main sections of the grid owing to the stepped relay characteristics as well as a large number of the steps. A full-fledged protection of the 6–35 kV lines against inter-phase short circuits can be provided by the two-stage current protection: the first stage being the current cutoff without any time delay and the second stage – the maximum current protection where the time delay is linear contingent on the distance between the protection placement and the fault-point location. The article introduces the rating formulae for the time delays of the second-stage and their exemplary graphic presentation. The authors offer a variant for solving the problem with computation of the second-stage time delays in those instances where several feeders diverge from the bus bars of the substation located in the end of the protected line.Improving current protections for the 6–35 kV transmission lines with one-end power supply against interphase short-circuits can be based on the collective application of the following principles: accounting for the type and location of the short-circuit which provides for the high-performance cutoff zone instantaneous expansion and its independence on the mode of failure and the grid operation mode. It also allows increase of the last stage sensitiveness towards asymmetrical short-circuits; detection of the short-circuit location only on the results of fault currents measurement which simplifies the protection implementation; realization of the last (second protection stage with linear-dependent time delay which ensures potentiality of its operation speed increase.

  20. Operational and layup cycle protection of high-pressure fossil-fired utility boilers using an organic filming amine

    Energy Technology Data Exchange (ETDEWEB)

    Verib, George J. [FirstEnergy Corp., Akron, OH (United States)

    2012-06-15

    Economic conditions have caused many fossil-fired units to either drastically cycle load or shut down during low demand periods, where previously the units had been under a constant-load operation. The most current cycle chemistry guidelines employed are excellent in protecting the steam-water cycle during constant-load operation, but they have not minimized corrosion and provided protection of unit equipment during economic reserve off periods. Alternate methods of off-line protection and transient-load operation have been explored to minimize corrosion during these periods. The FirstEnergy Corp. has been using an alternate proprietary, organic filming amine to protect units during operation and short-term non-operational periods. Explored are the initial issues of high steam cation conductivity, use of the filming amine to protect the cycle during idle production periods, and the chemical amounts needed. The proprietary chemistry has shown the ability to successfully and significantly reduce corrosion throughout the steam-water cycle during transient-load situations and during non-operational periods while maintaining the chemistry guidelines of the industry and OEMs. (orig.)

  1. Informing the network: Improving communication with interface communities during wildland fire

    Science.gov (United States)

    Taylor, J.G.; Gillette, S.C.; Hodgson, R.W.; Downing, J.L.; Burns, M.R.; Chavez, D.J.; Hogan, J.T.

    2007-01-01

    An interagency research team studied fire communications that took place during different stages of two wildfires in southern California: one small fire of short duration and one large fire of long duration. This "quick- response" research showed that pre-fire communication planning was particularly effective for smaller fire events and parts of that planning proved invaluable for the large fire event as well. Information seeking by the affected public relied on locally convenient sources during the small fire. During the large fire, widespread evacuations disrupted many of the local informal communication networks. Residents' needs were for "real-time, " place-specific information: precise location, severity, size, and direction of spread of the fires. Fire management agencies must contribute real-time, place-specific fire information when it is most needed by the affected public, as they try to make sense out of the chaos of a wildland fire. Disseminating fire information as broadly as possible through multiple pathways will maximize the probability of the public finding the information they need. ?? Society for Human Ecology.

  2. Fires, ecological effects of

    Science.gov (United States)

    W. J. Bond; Robert Keane

    2017-01-01

    Fire is both a natural and anthropogenic disturbance influencing the distribution, structure, and functioning of terrestrial ecosystems around the world. Many plants and animals depend on fire for their continued existence. Others species, such as rainforest plants species, are extremely intolerant of burning and need protection from fire. The properties of a fire...

  3. Force Protection for Fire Fighters: Warm Zone Operations at Paramilitary Style Active Shooter Incidents in a Multi-Hazard Environment as a Fire Service Core Competency

    Science.gov (United States)

    2012-03-01

    Attacks,” Der Speigel, July 25, 2011, http://www.spiegel.de/international/europe/0,1518,776437,00.html 114 “Profile: Anders Behring Breivik ,” BBC...144 Patrick Donovan, “Puyallup Fire & Rescue’s Response to Active School Shooting Incident,” National Fire Academy (July 2008): 24, 26, 49...Learn Them.” Homeland Security Affairs Journal II, no. 2 (July 2006): 11. Donovan, Patrick . “Puyallup Fire & Rescue’s Response to Active School

  4. Using social science to understand and improve wildland fire organizations: an annotated reading list

    Science.gov (United States)

    Gregory Larson; Vita Wright; Cade Spaulding; Kelly Rossetto; Georgi Rausch; Andrea Richards; Stephanie Durnford

    2007-01-01

    The wildland fire community has spent the past decade trying to understand and account for the role of human factors in wildland fire organizations. Social research that is relevant to managing fire organizations can be found in disciplines such as social psychology, management, and communication. However, such research has been published primarily for scientific and...

  5. Improved NOx emissions and combustion characteristics for a retrofitted down-fired 300-MWe utility boiler.

    Science.gov (United States)

    Li, Zhengqi; Ren, Feng; Chen, Zhichao; Liu, Guangkui; Xu, Zhenxing

    2010-05-15

    A new technique combining high boiler efficiency and low-NO(x) emissions was employed in a 300MWe down-fired boiler as an economical means to reduce NO(x) emissions in down-fired boilers burning low-volatile coals. Experiments were conducted on this boiler after the retrofit with measurements taken of gas temperature distributions along the primary air and coal mixture flows and in the furnace, furnace temperatures along the main axis and gas concentrations such as O(2), CO and NO(x) in the near-wall region. Data were compared with those obtained before the retrofit and verified that by applying the combined technique, gas temperature distributions in the furnace become more reasonable. Peak temperatures were lowered from the upper furnace to the lower furnace and flame stability was improved. Despite burning low-volatile coals, NO(x) emissions can be lowered by as much as 50% without increasing the levels of unburnt carbon in fly ash and reducing boiler thermal efficiency.

  6. 77 FR 58081 - Protection of Stratospheric Ozone: Listing of Substitutes for Ozone-Depleting Substances-Fire...

    Science.gov (United States)

    2012-09-19

    ... 332919 Nozzles, fire fighting, manufacturing. Manufacturing 334290 Fire detection and alarm systems... substitutes for halon 1301 for use in total flooding fire suppression systems in normally unoccupied spaces... regulated Category NAICS Code entities Construction 238210 Alarm system (e.g., fire, burglar), electric...

  7. Environment protection by coupling of a municipal waste incinerator to an existing coal fire steam boiler

    Energy Technology Data Exchange (ETDEWEB)

    Ionel, I.; Stanescu, P.D.O.; Gruescu, C.; Savu, A.; Ungureanu, C. [University of Politehnic Timisoara, Timisoara (Romania)

    2006-12-15

    The paper offers an analysis of the potential coupling of a municipal waste incinerator in Romania, to an existing coal fired steam boiler. Considering the retention of heavy metals as well as HCl from the waste flue gases before entering the boiler, the simulation analysis of the boiler, under the situation that the gases from the scrubber are introduced, are presented As general conclusion one notes that it is possible to apply the concept even if the analysed case is of less importance, but more potential application are viewed for larger industrial application, for new concepts of modern power plants, to meet EU environmental regulations, especially for CO{sub 2} reduction.

  8. Extension and update of the reliability data for fire protection equipment in German light water reactors; Ergaenzung und Aktualisierung von Zuverlaessigkeitskenngroessen fuer Brandschutzeinrichtungen in deutschen Leichtwasserreaktoren

    Energy Technology Data Exchange (ETDEWEB)

    Forell, Burkhard; Einarsson, Svante

    2016-12-15

    Within the BMUB project 3610R01370 ''Extension and update of reliability data for fire protection equipment in German light water reactors'' plant-specific as well as generic failure rates for the technical reliability of active fire protection features in German nuclear power plants have been calculated. Based on results of previous projects, in this project observation times of components were updated and extended and additional components and functions were assessed. Now, the data evaluated results from a total of six German reference plants with seven reactor units.

  9. Heliox Improves Carbon Dioxide Removal during Lung Protective Mechanical Ventilation.

    Science.gov (United States)

    Beurskens, Charlotte J; Brevoord, Daniel; Lagrand, Wim K; van den Bergh, Walter M; Vroom, Margreeth B; Preckel, Benedikt; Horn, Janneke; Juffermans, Nicole P

    2014-01-01

    Introduction. Helium is a noble gas with low density and increased carbon dioxide (CO2) diffusion capacity. This allows lower driving pressures in mechanical ventilation and increased CO2 diffusion. We hypothesized that heliox facilitates ventilation in patients during lung-protective mechanical ventilation using low tidal volumes. Methods. This is an observational cohort substudy of a single arm intervention study. Twenty-four ICU patients were included, who were admitted after a cardiac arrest and mechanically ventilated for 3 hours with heliox (50% helium; 50% oxygen). A fixed protective ventilation protocol (6 mL/kg) was used, with prospective observation for changes in lung mechanics and gas exchange. Statistics was by Bonferroni post-hoc correction with statistical significance set at P ventilation, respiratory rate decreased (25 ± 4 versus 23 ± 5 breaths min(-1), P = 0.010). Minute volume ventilation showed a trend to decrease compared to baseline (11.1 ± 1.9 versus 9.9 ± 2.1 L min(-1), P = 0.026), while reducing PaCO2 levels (5.0 ± 0.6 versus 4.5 ± 0.6 kPa, P = 0.011) and peak pressures (21.1 ± 3.3 versus 19.8 ± 3.2 cm H2O, P = 0.024). Conclusions. Heliox improved CO2 elimination while allowing reduced minute volume ventilation in adult patients during protective mechanical ventilation.

  10. Smoking and Home Fire Safety

    Science.gov (United States)

    ... Materials Working with the Media Fire Protection Technology Smoking fire safety outreach materials As a member of ... Not reported 7% In transport 1% 195 incidents Smoking fire safety messages to share It is important ...

  11. Can radiation protection be further improved in underground mines

    International Nuclear Information System (INIS)

    Bernhard, S.

    1992-01-01

    The efforts of optimization made by mine operators to improve radiation protection are illustrated by results and comments. Routinely, uranium miners are the most exposed workers in the fuel cycle (average: 20-30 mSv.y -1 for underground mines). In uranium mines, especially for ten years, operators have been striving to lower collective doses and comply with the regulation in force based on ICRP recommendations. Since 1988, french uranium miners have registered no effective cumulated doses exceeding the basic limit of 50 mSv.y -1 , which does not occur in every country. In 1990, ICRP issued new recommendations lowering the basic limit so that the average should not exceed 20 mSv.y -1 . To comply with the limit, the operators should make a number of more or less restricting arrangements. Additional financial means would become important in present mines. New operating concepts should be sought for new mines. Independently of the financial aspects, should not the expenses made towards lowering a risk already very low (hypothetic and long-term risk) be better used to improve conventional safety. Furthermore, there appears a number of noxious effects running against the aim pursued. As a conclusion, more efficient radiation protection could be achieved by implementation of the principle of optimization of the collective dose instead of more severe limits of individual doses

  12. ECONOMICS AND FEASIBILITY OF RANKINE CYCLE IMPROVEMENTS FOR COAL FIRED POWER PLANTS

    Energy Technology Data Exchange (ETDEWEB)

    Richard E. Waryasz; Gregory N. Liljedahl

    2004-09-08

    ALSTOM Power Inc.'s Power Plant Laboratories (ALSTOM) has teamed with the U.S. Department of Energy National Energy Technology Laboratory (DOE NETL), American Electric Company (AEP) and Parsons Energy and Chemical Group to conduct a comprehensive study evaluating coal fired steam power plants, known as Rankine Cycles, equipped with three different combustion systems: Pulverized Coal (PC), Circulating Fluidized Bed (CFB), and Circulating Moving Bed (CMB{trademark}). Five steam cycles utilizing a wide range of steam conditions were used with these combustion systems. The motivation for this study was to establish through engineering analysis, the most cost-effective performance potential available through improvement in the Rankine Cycle steam conditions and combustion systems while at the same time ensuring that the most stringent emission performance based on CURC (Coal Utilization Research Council) 2010 targets are met: > 98% sulfur removal; < 0.05 lbm/MM-Btu NO{sub x}; < 0.01 lbm/MM-Btu Particulate Matter; and > 90% Hg removal. The final report discusses the results of a coal fired steam power plant project, which is comprised of two parts. The main part of the study is the analysis of ten (10) Greenfield steam power plants employing three different coal combustion technologies: Pulverized Coal (PC), Circulating Fluidized Bed (CFB), and Circulating Moving Bed (CMB{trademark}) integrated with five different steam cycles. The study explores the technical feasibility, thermal performance, environmental performance, and economic viability of ten power plants that could be deployed currently, in the near, intermediate, and long-term time frame. For the five steam cycles, main steam temperatures vary from 1,000 F to 1,292 F and pressures from 2,400 psi to 5,075 psi. Reheat steam temperatures vary from 1,000 F to 1,328 F. The number of feedwater heaters varies from 7 to 9 and the associated feedwater temperature varies from 500 F to 626 F. The main part of the

  13. Improvement of Forest Fire Detection Algorithm Using Brightness Temperature Lapse Rate Correction in HIMAWARI-8 IR Channels: Application to the 6 may 2017 Samcheok City, Korea

    Science.gov (United States)

    Park, S. H.; Park, W.; Jung, H. S.

    2018-04-01

    Forest fires are a major natural disaster that destroys a forest area and a natural environment. In order to minimize the damage caused by the forest fire, it is necessary to know the location and the time of day and continuous monitoring is required until fire is fully put out. We have tried to improve the forest fire detection algorithm by using a method to reduce the variability of surrounding pixels. We focused that forest areas of East Asia, part of the Himawari-8 AHI coverage, are mostly located in mountainous areas. The proposed method was applied to the forest fire detection in Samcheok city, Korea on May 6 to 10, 2017.

  14. Spatial-temporal distribution of fire-protected savanna physiognomies in Southeastern Brazil

    Directory of Open Access Journals (Sweden)

    Marcelo H.O. Pinheiro

    2010-06-01

    Full Text Available The analysis of the influence of edaphic finer textures, as a facilitating factor for the expansion of forest formations in the absence of fire, was possible thanks to rare characteristics found in a savanna fragment located in the State of São Paulo, Brazil. The total suppression of fire for over four decades, and the occurrence of two savanna physiognomies, cerrado sensu stricto and cerradão, allowed the conduction of this study based on the hypothesis that cerradão, a physiognomy of forest aspect consisting of fire-sensitive tree and shrubs species, is favored by fire absence and higher soil hydric retention capacity. Edaphic samples were collected from a regular grid of 200 m² for the production of isopletic maps of the distribution of clay, fine sand, coarse sand and silt edaphic textures by the geostatistic method of ordinary kriging. Changes in the areas occupied by both savanna physiognomies, defined on the basis of aerial photographs taken over a period of 43 years, were assessed through mean variation rates. Besides corroborating the hypothesis of edaphic hydric retention as a facilitating factor for the expansion of forest physiognomies in savanna areas, we were able to infer the positive influence of higher precipitation on the increase in cerradão expansion rates.A influência de texturas edáficas finas, como fator de facilitação para a expansão de formações florestais sobre áreas savânicas, através da maior retenção hídrica edáfica, na ausência de incêndios, foi possível ser estudada graças às características encontradas em um fragmento savânico com 38,8 ha, situado em Corumbataí (SP. A supressão total do fogo por quatro décadas, e a ocorrência de duas fisionomias, cerrado sensu stricto e cerradão, permitiram a condução deste estudo. Amostras de solo foram coletadas em uma grade regular de 200 m², abrangendo toda a área do fragmento. Foram produzidos mapas iso-pléticos, com a distribuição das

  15. Industry participation in the development of a risk-informed, performance-based regulation for fire protection at US nuclear power plants

    International Nuclear Information System (INIS)

    Emerson, F.A.

    1998-01-01

    The USNRC staff have recently been directed by the NRC Commissioners to evaluate quickly the development of a risk-informed, performance-based fire protection regulation to replace the current regulations. The US nuclear industry does not believe a new rule is necessary to increase fire safety, and believes that there are significant risks and potentially significant benefits depending on the construction of the rule. However, the industry will actively work with NRC staff if rulemaking proceeds such that the risks are minimized and the benefits maximized. A Nuclear Energy Institute (NEI) Issue Task Force (ITF) has been established to guide the participation of industry in any rulemaking activity. If rulemaking proceeds, a framework should be established for the evolution of a fire protection rule from the current prescriptive basis to a risk-informed, performance-based rule. (author)

  16. Utilizing Remote Sensing Information to Improve Post-fire Rainfall-runoff Predictions after the 2010 Bull Fire in the Sequoia National Forest, CA

    Science.gov (United States)

    Kinoshita, A. M.; Hale, B.; Hogue, T. S.

    2012-12-01

    Post-fire management decisions are guided by rainfall-runoff predictions, which ultimately influence downstream treatment and mitigation costs. The current study investigates evolving rainfall-runoff partitioning at the watershed scale over a two-year period after the 2010 Bull Fire which occurred in the southern Sequoia National Forest in California. Stage height was measured at five-minute intervals using pressure transducers, tipping buckets were installed for rainfall duration and intensity, and channel cross-sections were measured approximately every two months to detail sediment deposition or scour. We also utilize remotely sensed vegetation data to evaluate vegetation recovery in the studied watersheds and the corresponding relationship to storm runoff. Normalized Difference Vegetation Index (NDVI), a measure of vegetation greenness, is evaluated for its potential use as a key recovery indicator. Preliminary results focus on alterations in annual and seasonal precipitation and discharge relationships using in-situ data and Landsat NDVI values for the period of study. NDVI values are consistent with a comprehensive burn, with an acute decrease observed in the initial post-fire period. However, vegetation recovery is highly variable in the studied systems and influenced by shorter-term biomass pulses (grasses) while longer-term recovery of other species (chaparral and pine) is ongoing. Runoff ratios are elevated during early storms and show some recovery in the later part of the study period. The ability to accurately and confidently predict post-fire runoff and longer-term recovery is critical for monitoring values-at-risk, reducing mitigation costs, and improving warnings to downstream public communities.

  17. Building 431 fire tests

    International Nuclear Information System (INIS)

    Alvares, N.J.; Beason, D.G.; Ford, H.W.; Magee, M.W.

    1977-01-01

    An extensive discussion of considerations for fire protection in the LLL mirror fusion test facility (MFTF) is presented. Because of the large volume and high bays of the building, sufficient data on fire detection is unavailable. Results of fire detection tests using controlled fire sources in the building are presented. Extensive data concerning the behavior of the building atmosphere are included. Candidate fire detection instrumentation and extinguishing systems for use in the building are briefly reviewed

  18. Study Improving Performance of Centrifugal Compressor In Paiton Coal Fired Power Plant Unit 1 And 2

    Science.gov (United States)

    Kusuma, Yuriadi; Permana, Dadang S.

    2018-03-01

    The compressed air system becomes part of a very important utility system in a Plant, including the Steam Power Plant. In PLN’S coal fired power plant, Paiton units 1 and 2, there are four Centrifugal air compressor types, which produce compressed air as much as 5.652 cfm and with electric power capacity of 1200 kW. Electricity consumption to operate centrifugal compressor is 7.104.117 kWh per year. This study aims to measure the performance of Centrifugal Compressors operating in Paiton’s coal fired power plant units 1 and 2. Performance Compressor is expressed by Specific Power Consumption (SPC) in kW/100 cfm. For this purpose, we measure the compressed air flow rate generated by each compressor and the power consumed by each compressor. The result is as follows Air Compressor SAC 2B : 15.1 kW/100 cfm, Air Compressor SAC 1B : 15.31 kW/100 cfm,Air Compressor SAC 1A : 16.3 kW/100 cfm and air Compressor SAC 2C : 18.19 kW/100 cfm. From the measurement result, air compressor SAC 2B has the best performance that is 15.1 kW / 100 cfm. In this study we analyze efforts to improve the performance of other compressors to at least match the performance of the SAC 2B air compressor. By increasing the Specific Power Consumption from others Compressor, it will get energy saving up to 284,165 kWh per year.

  19. The burning behaviour of sodium and consequences to be drawn for fire protection measures, by the example of the Kalkar nuclear power plant

    International Nuclear Information System (INIS)

    Hoppe, E.

    1977-01-01

    The burning behaviour of sodium leakages is described. The specific protective measures to be derived from the burning behaviour is discussed using the example of the Kalkar nuclear power station, where sodium is used as a coolant. A basic boundary condition to be considered in the system of protective measures against Na fires is the activity confinement in case of a release of radioactive sodium. (orig.) [de

  20. Heliox Improves Carbon Dioxide Removal during Lung Protective Mechanical Ventilation

    Directory of Open Access Journals (Sweden)

    Charlotte J. Beurskens

    2014-01-01

    Full Text Available Introduction. Helium is a noble gas with low density and increased carbon dioxide (CO2 diffusion capacity. This allows lower driving pressures in mechanical ventilation and increased CO2 diffusion. We hypothesized that heliox facilitates ventilation in patients during lung-protective mechanical ventilation using low tidal volumes. Methods. This is an observational cohort substudy of a single arm intervention study. Twenty-four ICU patients were included, who were admitted after a cardiac arrest and mechanically ventilated for 3 hours with heliox (50% helium; 50% oxygen. A fixed protective ventilation protocol (6 mL/kg was used, with prospective observation for changes in lung mechanics and gas exchange. Statistics was by Bonferroni post-hoc correction with statistical significance set at P<0.017. Results. During heliox ventilation, respiratory rate decreased (25±4 versus 23±5 breaths min−1, P=0.010. Minute volume ventilation showed a trend to decrease compared to baseline (11.1±1.9 versus 9.9±2.1 L min−1, P=0.026, while reducing PaCO2 levels (5.0±0.6 versus 4.5±0.6 kPa, P=0.011 and peak pressures (21.1±3.3 versus 19.8±3.2 cm H2O, P=0.024. Conclusions. Heliox improved CO2 elimination while allowing reduced minute volume ventilation in adult patients during protective mechanical ventilation.

  1. Improved Design of Unequal Error Protection LDPC Codes

    Directory of Open Access Journals (Sweden)

    Sandberg Sara

    2010-01-01

    Full Text Available We propose an improved method for designing unequal error protection (UEP low-density parity-check (LDPC codes. The method is based on density evolution. The degree distribution with the best UEP properties is found, under the constraint that the threshold should not exceed the threshold of a non-UEP code plus some threshold offset. For different codeword lengths and different construction algorithms, we search for good threshold offsets for the UEP code design. The choice of the threshold offset is based on the average a posteriori variable node mutual information. Simulations reveal the counter intuitive result that the short-to-medium length codes designed with a suitable threshold offset all outperform the corresponding non-UEP codes in terms of average bit-error rate. The proposed codes are also compared to other UEP-LDPC codes found in the literature.

  2. 75 FR 66725 - National Fire Protection Association (NFPA) Proposes To Revise Codes and Standards

    Science.gov (United States)

    2010-10-29

    ... for Solvent 5/23/2011 Extraction Plants. NFPA 51--2007 Standard for the Design and 11/23/2010... Practice for a 5/23/2011 Field Flame Test for Textiles and Films. NFPA 909--2010 Code for the Protection of...

  3. Spatial optimization of operationally relevant large fire confine and point protection strategies: Model development and test cases

    Science.gov (United States)

    Yu Wei; Matthew P. Thompson; Jessica R. Haas; Gregory K. Dillon; Christopher D. O’Connor

    2018-01-01

    This study introduces a large fire containment strategy that builds upon recent advances in spatial fire planning, notably the concept of potential wildland fire operation delineations (PODs). Multiple PODs can be clustered together to form a “box” that is referred as the “response POD” (or rPOD). Fire lines would be built along the boundary of an rPOD to contain a...

  4. Exploiting heat treatment effects on SMAs macro and microscopic properties in developing fire protection devices

    Science.gov (United States)

    Burlacu, L.; Cimpoeşu, N.; Bujoreanu, L. G.; Lohan, N. M.

    2017-08-01

    Ni-Ti shape memory alloys (SMAs) are intelligent alloys which demonstrate unique properties, such as shape memory effect, two-way shape memory effect, super-elasticity and vibration damping which, accompanied by good processability, excellent corrosion resistance and biocompatibility as well as fair wear resistance and cyclic stability, enabled the development of important industrial applications (such as sensors, actuators, fasteners, couplings and valves), medical applications (such as stents, bone implants, orthodontic archwires, minimal invasive surgical equipment) as well as environmental health and safety devices (anti-seismic dampers, fire safety devices). The phase transitions in Ni-Ti SMAs are strongly influenced by processing methods, chemical compositions and thermomechanical history. This paper presents a study of the effects of heat treatment on the mechanical and thermal properties of commercial Ni-Ti shape memory alloy (SMA). The experimental work involved subjecting a SMA rod to heat-treatment consisting in heating up to 500°C, 10 minutes-maintaining and water quenching. Mechanical properties were highlighted by microhardness tests while thermal characteristics were emphasized by differential scanning calorimetry (DSC). The presence of chemical composition fluctuations was checked by X-ray energy dispersive spectroscopy performed with an EDAX Bruker analyzer.

  5. Mitigation of fire damage and escalation by fireproofing: A risk-based strategy

    International Nuclear Information System (INIS)

    Tugnoli, Alessandro; Cozzani, Valerio; Di Padova, Annamaria; Barbaresi, Tiziana; Tallone, Fabrizio

    2012-01-01

    Passive fire protection by the application of fireproofing materials is a crucial safety barrier in the prevention of the escalation of fire scenarios. Fireproofing improves the capacity of process items and of support structures to maintain their structural integrity during a fire, preventing or at least delaying the collapse of structural elements. Maintenance and cost issues require, however, to apply such protection only where an actual risk of severe fire scenarios is present. Available methodologies for fireproofing application in on-shore installation do not consider the effect of jet-fires. In the present study, a risk-based methodology aimed at the protection from both pool fire and jet fire escalation was developed. The procedure addresses both the prevention of domino effect and the mitigation of asset damage due to the primary fire scenario. The method is mainly oriented to early design application, allowing the identification of fireproofing zones in the initial phases of lay-out definition.

  6. Afforestation, Subsequent Forest Fires and Provision of Hydrological Services

    NARCIS (Netherlands)

    Nunes, João Pedro; Naranjo Quintanilla, Paula; Santos, Juliana Marisa; Serpa, Dalila; Carvalho-Santos, Cláudia; Rocha, João; Keizer, Jan Jacob; Keesstra, Saskia Deborah

    2018-01-01

    Mediterranean landscapes have experienced extensive abandonment and reforestation in recent decades, which should have improved the provision of hydrological services such as flood mitigation, soil erosion protection and water quality regulation. However, these forests are fire-prone, and the

  7. Towards improved quantification of post-fire conifer mortality and recovery: Impacts of fire radiative flux on seedling and mature tree mortality, physiology, and growth

    Science.gov (United States)

    Sparks, A. M.; Kolden, C.; Smith, A. M.

    2016-12-01

    Fire activity, in terms of intensity, frequency, and total area burned, is expected to increase with changing climate. A challenge for landscape level assessment of fire effects, termed burn severity, is that current assessments provide very little information regarding vegetation physiological performance and recovery, limiting our understanding of fire effects on ecosystem services such as carbon storage/cycling. To address these limitations, we evaluated an alternative dose-response methodology for quantifying fire effects that attempts to bridge fire combustion dynamics and ecophysiology. Specifically, we conducted a highly controlled, laboratory assessment of seedling response to increasing doses of fire radiative energy applied through surface fires, for two western U.S. conifer species. Seedling physiology and spectral reflectance were acquired pre- and up to 1 year post-fire. Post-fire mortality, physiological performance, and spectral reflectance were strongly related with fire radiative energy density (FRED: J m-2) dose. To examine how these relationships change with tree size and age, we conducted small prescribed fires at the tree scale (35 m2) in a mature conifer stand. Radial growth and resin duct defenses were assessed on the mature conifer trees following the prescribed fires. Differences in dose-response relationships between seedlings and mature trees indicate the importance of fire behavior (e.g., flaming-dominated versus smoldering-dominated combustion) in characterizing these relationships. Ultimately, these results suggest that post-fire impacts on growth of surviving seedlings and mature trees require modes of heat transfer to impact tree canopies.

  8. Fire preparedness measures in buildings with hot laboratories

    International Nuclear Information System (INIS)

    Oberlaender, B.C.

    2003-01-01

    Important hot laboratory safety issues are the general design/construction of the building with respect to fire, fire prevention, fire protection, administrative controls, and risk assessment. Within the network of the European Working Group Hot Laboratories and Remote Handling items concerning 'fire preparedness measures in hot laboratories' were screened and studied. Two questionnaires were sent to European hot laboratories; the first in November 2002 on 'fire preparedness measures, fire detection and fire suppression/extinguishing in lead shielded cells, concrete shielded cells' and the second in June 2003 on 'Fire preparedness measures in buildings with hot laboratories'. The questionnaires were filled in by a total of ten hot laboratories in seven European countries. On request of participants the answers were evaluated and 'anonymised' for presentation and discussion at the plenary meeting. The answers showed that many European hot laboratories are implementing improvements to their fire protection programmes to comply with more stringent requirements of the national authorities. The recommendations ('International guidelines for the fire protection of Nuclear Power Plants') given by the insurance pools are followed up with national variations. An ISO standard (ISO 17873) is in progress giving criteria for the design and the operation of ventilation systems as well as fire hazard management in nuclear installations others than reactors

  9. Review of the IAEA fire symposium

    International Nuclear Information System (INIS)

    Fischer, J.

    1991-01-01

    The IAEA Symposium on Fire Protection and Fire Fighting in Nuclear Installations covered a large scope in the field in order to provide the opportunity for screening all aspects of present technology, research and development, standardization, licensing and fire fighting practices. Although application to any nuclear facility was within its scope, the majority of presentations concerned nuclear power plants. The approach to fire protection is the classical one in all plant designs: reduction of fire loads, appropriate zoning, manual and automatic extinguishment. However, methods of analysis and consequence prediction are changing. Computerized fire modelling is becoming a powerful tool in this area; probabilistic analytical methods are being improved, though they are not yet used widely for fire hazards. Differences in opinion were revealed in the definition of barrier resistance, the prediction of cable insulation behaviour and the optimal design of extinguishing systems. Greater international co-operation, especially in these areas, may be a good way of optimizing results with limited resources. Discussion contributions showed interest in exchange of experience in more specialized topics and encouraged the IAEA to increase its activity in the area of fire protection. (orig.)

  10. Subsurface Fire Hazards Technical Report

    International Nuclear Information System (INIS)

    Logan, R.C.

    1999-01-01

    The results from this report are preliminary and cannot be used as input into documents supporting procurement, fabrication, or construction. This technical report identifies fire hazards and proposes their mitigation for the subsurface repository fire protection system. The proposed mitigation establishes the minimum level of fire protection to meet NRC regulations, DOE fire protection orders, that ensure fire containment, adequate life safety provisions, and minimize property loss. Equipment requiring automatic fire suppression systems is identified. The subsurface fire hazards that are identified can be adequately mitigated

  11. Recycled blocks with improved sound and fire insulation containing construction and demolition waste.

    Science.gov (United States)

    Leiva, Carlos; Solís-Guzmán, Jaime; Marrero, Madelyn; García Arenas, Celia

    2013-03-01

    The environmental problem posed by construction and demolition waste (C&D waste) is derived not only from the high volume produced, but also from its treatment and disposal. Treatment plants receive C&D waste which is then transformed into a recycled mixed aggregate. The byproduct is mainly used for low-value-added applications such as land escape restoration, despite the high quality of the aggregate. In the present work, the chemical composition properties and grading curve properties of these aggregates are defined. Furthermore, the resulting recycled concrete with a high proportion of recycled composition, from 20% to 100% replacement of fine and coarse aggregate, is characterized physically and mechanically. An environmental study of the new construction material when all aggregates are substituted by C&D waste shows a low toxicity level, similar to that of other construction materials. The new material also has improved properties with respect to standard concrete such as high fire resistance, good heat insulation, and acoustic insulation. Copyright © 2012 Elsevier Ltd. All rights reserved.

  12. Probabilistic risk assessment for back-end facilities: Improving the treatment of fire and explosion scenarios

    International Nuclear Information System (INIS)

    Sunman, C.R.J.; Campbell, R.J.; Wakem, M.J.

    1996-01-01

    The nuclear reprocessing facilities at Sellafield are a key component of the International business of BNFL. The operations carried out at the site extend from the receipt and storage of irradiated fuel, chemical reprocessing, plutonium and uranium finishing, through mixed oxide fuel production. Additionally there are a wide range of supporting processes including solid waste encapsulation, vitrification, liquid waste evaporation and treatment. Decommissioning of the site's older facilities is also proceeding. The comprehensive range of these activities requires that the safety assessment team keeps up to date with developments in the field, as well as conducting and sponsoring appropriate research into methodologies and modelling in order to deliver a cost effective, timely service. This paper will review the role of Probabilistic Risk Assessment (PRA) in safety cases for operations at Sellafield and go on to describe some areas of PRA methodology development in the UK and in which BNFL is a contributor. Finally the paper will summarise some specific areas of methodology development associated with improving the modelling of fire and explosion hazards which are specific to BNFL. (author)

  13. Behavioral interventions for improving condom use for dual protection.

    Science.gov (United States)

    Lopez, Laureen M; Otterness, Conrad; Chen, Mario; Steiner, Markus; Gallo, Maria F

    2013-10-26

    Unprotected sex is a major risk factor for disease, disability, and mortality in many areas of the world due to the prevalence and incidence of sexually transmitted infections (STI) including HIV. The male condom is one of the oldest contraceptive methods and the earliest method for preventing the spread of HIV. When used correctly and consistently, condoms can provide dual protection, i.e., against both pregnancy and HIV/STI. We examined comparative studies of behavioral interventions for improving condom use. We were interested in identifying interventions associated with effective condom use as measured with biological assessments, which can provide objective evidence of protection. Through September 2013, we searched computerized databases for comparative studies of behavioral interventions for improving condom use: MEDLINE, POPLINE, CENTRAL, EMBASE, LILACS, OpenGrey, COPAC, ClinicalTrials.gov, and ICTRP. We wrote to investigators for missing data. Studies could be either randomized or nonrandomized. They examined a behavioral intervention for improving condom use. The comparison could be another behavioral intervention, usual care, or no intervention. The experimental intervention had an educational or counseling component to encourage or improve condom use. It addressed preventing pregnancy as well as the transmission of HIV/STI. The focus could be on male or female condoms and targeted to individuals, couples, or communities. Potential participants included heterosexual women and heterosexual men.Studies had to provide data from test results or records on a biological outcome: pregnancy, HIV/STI, or presence of semen as assessed with a biological marker, e.g., prostate-specific antigen. We did not include self-reported data on protected or unprotected sex, due to the limitations of recall and social desirability bias. Outcomes were measured at least three months after the behavioral intervention started. Two authors evaluated abstracts for eligibility and

  14. Quantifying the role of fire in the Earth system – Part 1: Improved global fire modeling in the Community Earth System Model (CESM1)

    OpenAIRE

    F. Li; S. Levis; D. S. Ward

    2013-01-01

    Modeling fire as an integral part of an Earth system model (ESM) is vital for quantifying and understanding fire–climate–vegetation interactions on a global scale and from an Earth system perspective. In this study, we introduce to the Community Earth System Model (CESM) the new global fire parameterization proposed by Li et al. (2012a, b), now with a more realistic representation of the anthropogenic impacts on fires, with a parameterization of peat fires, and with other minor modifications....

  15. WebFIRE

    Data.gov (United States)

    U.S. Environmental Protection Agency — The Factor Information Retrieval (FIRE) Data System is a database management system containing EPA's recommended emission estimation factors for criteria and...

  16. Study of the fire resistant behavior of unfilled and carbon nanofibers reinforced polybenzimidazole coating for structural applications

    OpenAIRE

    Iqbal, H.M.S.; Stec, A.A.; Patel, P.; Bhowmik, S.; Benedictus, R.

    2013-01-01

    With increasing interest in epoxy-based carbon fiber composites for structural applications, it is important to improve the fire resistant properties of these materials. The fire resistant performance of these materials can be improved either by using high performance epoxy resin for manufacturing carbon fiber composite or by protecting the previously used epoxy-based composite with some fire resistant coating. In this context, work is carried out to evaluate the fire resistance performance o...

  17. Design options for improving protective gloves for industrial assembly work.

    Science.gov (United States)

    Dianat, Iman; Haslegrave, Christine M; Stedmon, Alex W

    2014-07-01

    The study investigated the effects of wearing two new designs of cotton glove on several hand performance capabilities and compared them against the effects of barehanded, single-layered and double cotton glove conditions when working with hand tools (screwdriver and pliers). The new glove designs were based on the findings of subjective hand discomfort assessments for this type of work and aimed to match the glove thickness to the localised pressure and sensitivity in different areas of the hand as well as to provide adequate dexterity for fine manipulative tasks. The results showed that the first prototype glove and the barehanded condition were comparable and provided better dexterity and higher handgrip strength than double thickness gloves. The results support the hypothesis that selective thickness in different areas of the hand could be applied by glove manufacturers to improve the glove design, so that it can protect the hands from the environment and at the same time allow optimal hand performance capabilities. Copyright © 2014 Elsevier Ltd and The Ergonomics Society. All rights reserved.

  18. Project-oriented management of industrial production of fire and rescue equipment by means of geometric modelling

    OpenAIRE

    Rak, Iu; Bondarenko, V.

    2013-01-01

    Objective: The objective of the research is to develop a method based on the geometric modelling for the purpose of improving the effectiveness of fire protection project management in industrial production of fire protection technology systems. Methods: The theoretical inheritance mode of effective management in project-organizational structure of fire protection and specialized technical equipment production using geometric modelling. Results: Mathematical and geometric models of project ma...

  19. Cost of two fire

    International Nuclear Information System (INIS)

    Vasil'ev, Yu.

    2001-01-01

    The problem of the protection of nuclear sites in connection with the fires in summer of 2000 near two greatest nuclear sites: the Pacific Northwest National Laboratory located on the site of Hanford Nuclear Center, and Los Alamos National Laboratory is considered. Both fires occur beyond the Laboratories. Undertaken urgent procedures for fire fighting and recovery of the objects are characterized [ru

  20. LANDFIRE 2010—Updates to the national dataset to support improved fire and natural resource management

    Science.gov (United States)

    Nelson, Kurtis J.; Long, Donald G.; Connot, Joel A.

    2016-02-29

    The Landscape Fire and Resource Management Planning Tools (LANDFIRE) 2010 data release provides updated and enhanced vegetation, fuel, and fire regime layers consistently across the United States. The data represent landscape conditions from approximately 2010 and are the latest release in a series of planned updates to maintain currency of LANDFIRE data products. Enhancements to the data products included refinement of urban areas by incorporating the National Land Cover Database 2006 land cover product, refinement of agricultural lands by integrating the National Agriculture Statistics Service 2011 cropland data layer, and improved wetlands delineations using the National Land Cover Database 2006 land cover and the U.S. Fish and Wildlife Service National Wetlands Inventory data. Disturbance layers were generated for years 2008 through 2010 using remotely sensed imagery, polygons representing disturbance events submitted by local organizations, and fire mapping program data such as the Monitoring Trends in Burn Severity perimeters produced by the U.S. Geological Survey and the U.S. Forest Service. Existing vegetation data were updated to account for transitions in disturbed areas and to account for vegetation growth and succession in undisturbed areas. Surface and canopy fuel data were computed from the updated vegetation type, cover, and height and occasionally from potential vegetation. Historical fire frequency and succession classes were also updated. Revised topographic layers were created based on updated elevation data from the National Elevation Dataset. The LANDFIRE program also released a new Web site offering updated content, enhanced usability, and more efficient navigation.

  1. Managing wildland fires: integrating weather models into fire projections

    Science.gov (United States)

    Anne M. Rosenthal; Francis Fujioka

    2004-01-01

    Flames from the Old Fire sweep through lands north of San Bernardino during late fall of 2003. Like many Southern California fires, the Old Fire consumed susceptible forests at the urban-wildland interface and spread to nearby city neighborhoods. By incorporating weather models into fire perimeter projections, scientist Francis Fujioka is improving fire modeling as a...

  2. The comparison of the actual fire protection and control measures according to the data derived from Istanbul Forest Directorate

    Directory of Open Access Journals (Sweden)

    Mehmet Altuğ Küçükosmanoğlu

    2015-01-01

    Full Text Available The aim of this study is to examine Istanbul Regional Forest Directorate precautions and control measures against the forest fires. With the study it is obvious to see the Regional Directorate of Forestry’s success by means of controlling the fires.

  3. Root cause analysis for fire events at nuclear power plants

    International Nuclear Information System (INIS)

    1999-09-01

    Fire hazard has been identified as a major contributor to a plant' operational safety risk. The International nuclear power community (regulators, operators, designers) has been studying and developing tools for defending against this hazed. Considerable advances have been achieved during past two decades in design and regulatory requirements for fire safety, fire protection technology and related analytical techniques. The IAEA endeavours to provide assistance to Member States in improving fire safety in nuclear power plants. A task was launched by IAEA in 1993 with the purpose to develop guidelines and good practices, to promote advanced fire safety assessment techniques, to exchange state of the art information, and to provide engineering safety advisory services and training in the implementation of internationally accepted practices. This TECDOC addresses a systematic assessment of fire events using the root cause analysis methodology, which is recognized as an important element of fire safety assessment

  4. Improved Short-Circuit Protection for Power Cells in Series

    Science.gov (United States)

    Davies, Francis

    2008-01-01

    A scheme for protection against short circuits has been devised for series strings of lithium electrochemical cells that contain built-in short-circuit protection devices, which go into a high-resistance, current-limiting state when heated by excessive current. If cells are simply connected in a long series string to obtain a high voltage and a short circuit occurs, whichever short-circuit protection device trips first is exposed to nearly the full string voltage, which, typically, is large enough to damage the device. Depending on the specific cell design, the damage can defeat the protective function, cause a dangerous internal short circuit in the affected cell, and/or cascade to other cells. In the present scheme, reverse diodes rated at a suitably high current are connected across short series sub-strings, the lengths of which are chosen so that when a short-circuit protection device is tripped, the voltage across it does not exceed its rated voltage. This scheme preserves the resetting properties of the protective devices. It provides for bypassing of cells that fail open and limits cell reversal, though not as well as does the more-expensive scheme of connecting a diode across every cell.

  5. Immersive virtual reality-based training improves response in a simulated operating room fire scenario.

    Science.gov (United States)

    Sankaranarayanan, Ganesh; Wooley, Lizzy; Hogg, Deborah; Dorozhkin, Denis; Olasky, Jaisa; Chauhan, Sanket; Fleshman, James W; De, Suvranu; Scott, Daniel; Jones, Daniel B

    2018-01-25

    SAGES FUSE curriculum provides didactic knowledge on OR fire prevention. The objective of this study is to evaluate the impact of an immersive virtual reality (VR)-based OR fire training simulation system in combination with FUSE didactics. The study compared a control with a simulation group. After a pre-test questionnaire that assessed the baseline knowledge, both groups were given didactic material that consists of a 10-min presentation and reading materials about precautions and stopping an OR fire from the FUSE manual. The simulation group practiced on the OR fire simulation for one session that consisted of five trials within a week from the pre-test. One week later, both groups were reassessed using a questionnaire. A week after the post-test both groups also participated in a simulated OR fire scenario while their performance was videotaped for assessment. A total of 20 subjects (ten per group) participated in this IRB approved study. Median test scores for the control group increased from 5.5 to 9.00 (p = 0.011) and for the simulation group it increased from 5.0 to 8.5 (p = 0.005). Both groups started at the same baseline (pre-test, p = 0.529) and reached similar level in cognitive knowledge (post-test, p = 0.853). However, when tested in the mock OR fire scenario, 70% of the simulation group subjects were able to perform the correct sequence of steps in extinguishing the simulated fire whereas only 20% subjects in the control group were able to do so (p = 0.003). The simulation group was better than control group in correctly identifying the oxidizer (p = 0.03) and ignition source (p = 0.014). Interactive VR-based hands-on training was found to be a relatively inexpensive and effective mode for teaching OR fire prevention and management scenarios.

  6. Improving Reliability of a fire-fighting pump set with Axiomatic Design

    Directory of Open Access Journals (Sweden)

    Arcidiacono Gabriele

    2017-01-01

    Full Text Available This paper introduces a case study featuring Axiomatic Design and Multi-Level Hierarchical model (MLH applied to redesign a fire-fighting pump set. In particular, two different design concepts are presented to be applied to the supporting frame of the system to limit a vibration problem that can arise during potential malfunctioning of the fire-fighting pump. The selection of the best design has been carried out through reliability evaluation process and through the cost of failure based on the MLH model.

  7. Advanced fire prevention techniques for ITER-INDIA laboratory building, IPR

    International Nuclear Information System (INIS)

    Modi, D.V.; Channa Reddy, D.

    2016-01-01

    Just as air and water, survival of human life without fire is unimaginable. However, fire can be a boon as well as a bane. The ability to control the use of fire is an art towards improved industrial development. The same phenomenon is also applicable for research and development sector. Fire Safety is a key issue for any kind of research laboratories. Fire hazards in laboratories arise from the storage and use of flammable materials and electrical installations and from hazardous operations carried out there. The risk of damage due to fire depends on the combustible available, their physical arrangement, the geometry of the building, likelihood of the ignition, etc. The risk is also controlled by the fire protection measures in place, which relate to both fire prevention and fire control. (author)

  8. Can Social Protection Improve Sustainable Development Goals for Adolescent Health?

    Science.gov (United States)

    Cluver, Lucie D; Orkin, F Mark; Meinck, Franziska; Boyes, Mark E; Yakubovich, Alexa R; Sherr, Lorraine

    2016-01-01

    The first policy action outlined in the Sustainable Development Goals (SDGs) is the implementation of national social protection systems. This study assesses whether social protection provision can impact 17 indicators of five key health-related SDG goals amongst adolescents in South Africa. We conducted a longitudinal survey of adolescents (10-18 years) between 2009 and 2012. Census areas were randomly selected in two urban and two rural health districts in two South African provinces, including all homes with a resident adolescent. Household receipt of social protection in the form of 'cash' (economic provision) and 'care' (psychosocial support) social protection, and health-related indicators within five SDG goals were assessed. Gender-disaggregated analyses included multivariate logistic regression, testing for interactions between social protection and socio-demographic covariates, and marginal effects models. Social protection was associated with significant adolescent risk reductions in 12 of 17 gender-disaggregated SDG indicators, spanning SDG 2 (hunger); SDG 3 (AIDS, tuberculosis, mental health and substance abuse); SDG 4 (educational access); SDG 5 (sexual exploitation, sexual and reproductive health); and SDG 16 (violence perpetration). For six of 17 indicators, combined cash plus care showed enhanced risk reduction effects. Two interactions showed that effects of care varied by poverty level for boys' hunger and girls' school dropout. For tuberculosis, and for boys' sexual exploitation and girls' mental health and violence perpetration, no effects were found and more targeted or creative means will be needed to reach adolescents on these challenging burdens. National social protection systems are not a panacea, but findings suggest that they have multiple and synergistic positive associations with adolescent health outcomes. Such systems may help us rise to the challenges of health and sustainable development.

  9. Can Social Protection Improve Sustainable Development Goals for Adolescent Health?

    Directory of Open Access Journals (Sweden)

    Lucie D Cluver

    Full Text Available The first policy action outlined in the Sustainable Development Goals (SDGs is the implementation of national social protection systems. This study assesses whether social protection provision can impact 17 indicators of five key health-related SDG goals amongst adolescents in South Africa.We conducted a longitudinal survey of adolescents (10-18 years between 2009 and 2012. Census areas were randomly selected in two urban and two rural health districts in two South African provinces, including all homes with a resident adolescent. Household receipt of social protection in the form of 'cash' (economic provision and 'care' (psychosocial support social protection, and health-related indicators within five SDG goals were assessed. Gender-disaggregated analyses included multivariate logistic regression, testing for interactions between social protection and socio-demographic covariates, and marginal effects models.Social protection was associated with significant adolescent risk reductions in 12 of 17 gender-disaggregated SDG indicators, spanning SDG 2 (hunger; SDG 3 (AIDS, tuberculosis, mental health and substance abuse; SDG 4 (educational access; SDG 5 (sexual exploitation, sexual and reproductive health; and SDG 16 (violence perpetration. For six of 17 indicators, combined cash plus care showed enhanced risk reduction effects. Two interactions showed that effects of care varied by poverty level for boys' hunger and girls' school dropout. For tuberculosis, and for boys' sexual exploitation and girls' mental health and violence perpetration, no effects were found and more targeted or creative means will be needed to reach adolescents on these challenging burdens.National social protection systems are not a panacea, but findings suggest that they have multiple and synergistic positive associations with adolescent health outcomes. Such systems may help us rise to the challenges of health and sustainable development.

  10. CONSUMER PROTECTION: Federal Actions Are Needed to Improve Oversight of the Household Goods Moving Industry

    National Research Council Canada - National Science Library

    2001-01-01

    .... The Motor Carrier Safety Improvement Act of 1999 directed that we assess the effectiveness of the Department of Transportation s consumer protection activities for the interstate household goods...

  11. Applying State-of-the-Art Technologies to Reduce Escape Times from Fires Using Environmental Sensing, Improved Occupant Egress Guidance, and Multiple Communication Protocols

    National Research Council Canada - National Science Library

    Street, Thomas T; Hammond, Mark H; Williams, Frederick W

    2009-01-01

    ...) was tasked with investigating various technology and concepts--such as visual signals and unique audible sounds--that have the potential to improve residential occupant escape in the event of fire...

  12. Fire safety study of Dodewaard and Borssele nuclear power plants

    International Nuclear Information System (INIS)

    1988-03-01

    From the nuclear and conventional fire safety audits of both Dutch nuclear power plants performed under supervision of the Nuclear Safety Inspectorate and the Inspectorate for the Fire Services it turns out that the fire safety is sufficient however amenable for improvement. Besides a detailed description of the method of examination, the study 'Fire Safety' contains the results of the audit and 14 respectively 15 recommendations for improvement of the fire safety in Dodewaard and Borssele. The suggested recommendations which are applicable to both power plants are the following: fire fighting training for operators and guards, a complete emergency ventilation system of the control room, increase in the number of detectors and alarms, an increase in the quantity of water available for high-pressure fire fighting, improvement of fire barriers between several redundancies of nuclear safety systems, an investigation and possible improvement of the heat and radiation protection offered by presently used fire fighting suits. For Dodewaard a closed emergency staircase in the reactor building (secondary containment) is deemed necessary for personnel emergency escape routes and continued fire fighting if required

  13. Fire safety

    International Nuclear Information System (INIS)

    Keski-Rahkonen, O.; Bjoerkman, J.; Hostikka, S.; Mangs, J.; Huhtanen, R.; Palmen, H.; Salminen, A.; Turtola, A.

    1998-01-01

    According to experience and probabilistic risk assessments, fires present a significant hazard in a nuclear power plant. Fires may be initial events for accidents or affect safety systems planned to prevent accidents and to mitigate their consequences. The project consists of theoretical work, experiments and simulations aiming to increase the fire safety at nuclear power plants. The project has four target areas: (1) to produce validated models for numerical simulation programmes, (2) to produce new information on the behavior of equipment in case of fire, (3) to study applicability of new active fire protecting systems in nuclear power plants, and (4) to obtain quantitative knowledge of ignitions induced by important electric devices in nuclear power plants. These topics have been solved mainly experimentally, but modelling at different level is used to interpret experimental data, and to allow easy generalisation and engineering use of the obtained data. Numerical fire simulation has concentrated in comparison of CFD modelling of room fires, and fire spreading on cables on experimental data. So far the success has been good to fair. A simple analytical and numerical model has been developed for fire effluents spreading beyond the room of origin in mechanically strongly ventilated compartments. For behaviour of equipment in fire several full scale and scaled down calorimetric experiments were carried out on electronic cabinets, as well as on horizontal and vertical cable trays. These were carried out to supply material for CFD numerical simulation code validation. Several analytical models were developed and validated against obtained experimental results to allow quick calculations for PSA estimates as well as inter- and extrapolations to slightly different objects. Response times of different commercial fire detectors were determined for different types of smoke, especially emanating from smoldering and flaming cables to facilitate selection of proper detector

  14. Improving the thermal efficiency of a jaggery production module using a fire-tube heat exchanger.

    Science.gov (United States)

    La Madrid, Raul; Orbegoso, Elder Mendoza; Saavedra, Rafael; Marcelo, Daniel

    2017-12-15

    Jaggery is a product obtained after heating and evaporation processes have been applied to sugar cane juice via the addition of thermal energy, followed by the crystallisation process through mechanical agitation. At present, jaggery production uses furnaces and pans that are designed empirically based on trial and error procedures, which results in low ranges of thermal efficiency operation. To rectify these deficiencies, this study proposes the use of fire-tube pans to increase heat transfer from the flue gases to the sugar cane juice. With the aim of increasing the thermal efficiency of a jaggery installation, a computational fluid dynamic (CFD)-based model was used as a numerical tool to design a fire-tube pan that would replace the existing finned flat pan. For this purpose, the original configuration of the jaggery furnace was simulated via a pre-validated CFD model in order to calculate its current thermal performance. Then, the newly-designed fire-tube pan was virtually replaced in the jaggery furnace with the aim of numerically estimating the thermal performance at the same operating conditions. A comparison of both simulations highlighted the growth of the heat transfer rate at around 105% in the heating/evaporation processes when the fire-tube pan replaced the original finned flat pan. This enhancement impacted the jaggery production installation, whereby the thermal efficiency of the installation increased from 31.4% to 42.8%. Copyright © 2017 Elsevier Ltd. All rights reserved.

  15. Improving Fire Emission Estimates in the eastern United States Using Satellite-Based Fuel Loading Factors

    Science.gov (United States)

    Yongqiang Liu; John J. Qu; Xianjun Hao; Wanting Wang

    2005-01-01

    Wildfires can lead to severe environmental consequences by releasing large amounts of particulate matter (PM) and precursors of ozone (Sandberg et al., 1999; Riebau and Fox, 2001). The Southeast has the most burned area among various U.S. regions (Stanturf et al., 2002) and has regionally some of the highest levels of PM and ozone in the nation. Fires have been found...

  16. Improved modelling of sodium-spray fires and sodium-combustion aerosol chemical evolution - 15488

    International Nuclear Information System (INIS)

    Mathe, E.; Kissane, M.; Petitprez, D.

    2015-01-01

    In the context of the Generation IV Initiative, the consequences of a severe-accident in sodium-cooled fast reactor (SFR) must be studied. Being pyrophoric, sodium will burn upon contact with air in a containment creating toxic aerosols and we must take into account these fire aerosols when assessing the source term. We have developed a numerical simulation named NATRAC to calculate the mass of aerosols produced during a spray fire in a SFR severe accident. The results show that the mass of oxide aerosols can involve more than 60% of the ejected sodium. In a second part we have developed a numerical simulation named STARK based on the Cooper model that models the physico-chemical transformations of the aerosols. However, this model has never been validated and the literature does not permit to do so. In these conditions, we have designed and performed our own experiment ESSTIA to obtain the missing values of the parameters that govern Cooper model. The modified Cooper model we propose with the new parameters reproduces correctly the ESSTIA experimental data. The only parameter that has not yet been measured is the tortuosity of the sodium-fire aerosols surface layers. A dedicated experiment using real sodium-fire aerosols could eliminate any doubts about the uncertainty of the proposed Cooper model

  17. Manufacturing of Fire Resistance Geopolymer: A Review

    Directory of Open Access Journals (Sweden)

    Aziz Ikmal Hakem

    2016-01-01

    Full Text Available Protection against fire using inorganic polymer is a new application of engineering technology. Even though, there are varieties of fire-protection materials, there is always a need for the development of new materials with improved thermophysical properties and low cost. Geopolymer composites materials are promising from this point of view. Granulated blast furnace slag, boiler ash and fly ash have been used as the prime materials for forming geopolymers composites. Geopolymers have been studied due to its unique properties such as a good fire resistance. Geopolymer offers an innovative for application associated with the high thermal application. This paper summarizes on the potential of alkaliactivated materials over the past decades along with outlines of the manufacturing of geopolymer composites for fire resistance application.

  18. Protecting smallholders' food security by improving soils | CRDI ...

    International Development Research Centre (IDRC) Digital Library (Canada)

    The resilience of farming systems to climate change and variability depends upon healthy soil. ... communities I know already struggle with perennial food deficits and limited .... Protection de la sécurité alimentaire des petits exploitants grâce à ...

  19. Heliox Improves Carbon Dioxide Removal during Lung Protective Mechanical Ventilation

    NARCIS (Netherlands)

    Beurskens, Charlotte J.; Brevoord, Daniel; Lagrand, Wim K.; van den Bergh, Walter M.; Vroom, Margreeth B.; Preckel, Benedikt; Horn, Janneke; Juffermans, Nicole P.

    2014-01-01

    Introduction. Helium is a noble gas with low density and increased carbon dioxide (CO2) diffusion capacity. This allows lower driving pressures in mechanical ventilation and increased CO2 diffusion. We hypothesized that heliox facilitates ventilation in patients during lung-protective mechanical

  20. Fire protection electrical engineering

    International Nuclear Information System (INIS)

    Oh, Jung Min

    2000-03-01

    This book concentrates of electricity with current, voltage, power, ohms law, access of resistance, electrolytic analysis and battery, static on frictional electricity and electrostatic induction, coulomb's law, Gauss's law, condenser and capacity, magmatism on magnetic field and magnetic line of force, magnetic circuit, electromagnetic force, electromotive current, basic alternating current circuit, circuit network analysis, three-phase current, non-sinusoidal alternating current, transient phenomena, semiconductor, electric measurement on measurement over resistance, power, power rate and circuit tester, automatic control on introduction, term, classification, foundation of sequence control, logic circuit and basic logic circuit and electric equipment.

  1. IMPROVEMENT OF FOREST FIRE DETECTION ALGORITHM USING BRIGHTNESS TEMPERATURE LAPSE RATE CORRECTION IN HIMAWARI-8 IR CHANNELS: APPLICATION TO THE 6 MAY 2017 SAMCHEOK CITY, KOREA

    Directory of Open Access Journals (Sweden)

    S. H. Park

    2018-04-01

    Full Text Available Forest fires are a major natural disaster that destroys a forest area and a natural environment. In order to minimize the damage caused by the forest fire, it is necessary to know the location and the time of day and continuous monitoring is required until fire is fully put out. We have tried to improve the forest fire detection algorithm by using a method to reduce the variability of surrounding pixels. We focused that forest areas of East Asia, part of the Himawari-8 AHI coverage, are mostly located in mountainous areas. The proposed method was applied to the forest fire detection in Samcheok city, Korea on May 6 to 10, 2017.

  2. Fighting fires in nuclear plants

    International Nuclear Information System (INIS)

    Fantom, L.F.; Weldon, G.E.

    1978-01-01

    Since the Browns Ferry incident, the specter of fires at nuclear plants has been the focus of attention by NRC, the utilities, and the public. There are sophisticated hardware and software available - in the form of fire-protection systems and equipment and training and fire-protection programs. Potential fire losses at nuclear faclities can be staggering. Thus, it behooves all those involved to maximize fire-protection security while simultaneously minimizing the chance of human error, which cancels out the effectiveness of the most up-to-date protective systems and devices

  3. German data for risk based fire safety assessment

    International Nuclear Information System (INIS)

    Roewekamp, M.; Berg, H.P.

    1998-01-01

    Different types of data are necessary to perform risk based fire safety assessments and, in particular, to quantify the fire event tree considering the plant specific conditions. Data on fire barriers, fire detection and extinguishing, including also data on secondary effects of a fire, have to be used for quantifying the potential hazard and damage states. The existing German database on fires in nuclear power plants (NPPs) is very small. Therefore, in general generic data, mainly from US databases, are used for risk based safety assessments. Due to several differences in the plant design and conditions generic data can only be used as conservative assumptions. World-wide existing generic data on personnel failures in case of fire fighting have only to be adapted to the plant specific conditions inside the NPP to be investigated. In contrary, unavailabilities of fire barrier elements may differ strongly depending on different standards, testing requirements, etc. In addition, the operational behaviour of active fire protection equipment may vary depending on type and manufacturer. The necessity for more detailed and for additional plant specific data was the main reason for generating updated German data on the operational behaviour of active fire protection equipment/features in NPPs to support risk based fire safety analyses being recommended to be carried out as an additional tool to deterministic fire hazard analyses in the frame of safety reviews. The results of these investigations revealed a broader and more realistic database for technical reliability of active fire protection means, but improvements as well as collection of further data are still necessary. (author)

  4. Ballistic characteristics improving and maintenance of protective ballistic vests

    OpenAIRE

    RADONJIC VOJKAN M.; JOVANOVIC DANKO M.; ZIVANOVIC GORAN Z.; RESIMIC BRANKO V.

    2014-01-01

    The work presents research of the materials necessary for the maintenance of protective ballistic vests. In this paper is proposed a new construction design with modern materials for ballistic inserts producing. This paper also presents the results of laboratory tests of ballistic cartridges with new materials. Based on the test results, it can be concluded, the proposed technical solution for making ballistic inserts adequately meets current standards.

  5. Heliox Improves Carbon Dioxide Removal during Lung Protective Mechanical Ventilation

    OpenAIRE

    Beurskens, Charlotte J; Brevoord, Daniel; Lagrand, Wim K; van den Bergh, Walter M; Vroom, Margreeth B; Preckel, Benedikt; Horn, Janneke; Juffermans, Nicole P

    2014-01-01

    Introduction. Helium is a noble gas with low density and increased carbon dioxide (CO2) diffusion capacity. This allows lower driving pressures in mechanical ventilation and increased CO2 diffusion. We hypothesized that heliox facilitates ventilation in patients during lung-protective mechanical ventilation using low tidal volumes. Methods. This is an observational cohort substudy of a single arm intervention study. Twenty-four ICU patients were included, who were admitted after a cardiac arr...

  6. Application of Mensuration Technology to Improve the Accuracy of Field Artillery Firing Unit Location

    Science.gov (United States)

    2013-12-13

    8 U.S. Army Field Artillery Operations ............................................................................ 8 Geodesy ...Experts in this field of study have a full working knowledge of geodesy and the theory that allows mensuration to surpass the level of accuracy achieved...desired. (2) Fire that is intended to achieve the desired result on target.”6 Geodesy : “that branch of applied mathematics which determines by observation

  7. Evaluating a smartphone application to improve child passenger safety and fire safety knowledge and behaviour.

    Science.gov (United States)

    Omaki, Elise; Shields, Wendy C; McDonald, Eileen; Aitken, Mary E; Bishai, David; Case, James; Gielen, Andrea

    2017-02-01

    Although proven measures for reducing injury due to motor vehicle collision and residential fires exist, the number of families properly and consistently using child passenger restraints and smoke alarms remains low. This paper describes the design of the Safety In Seconds (SIS) 2.0 study, which aims to evaluate the impact of a smartphone app on parents' use of child restraints and smoke alarms. SIS is a multisite randomised controlled trial. Participants are parents of children aged 4-7 years who are visiting the Pediatric Emergency Department or Pediatric Trauma Service. Parents are randomised to receive tailored education about child passenger safety or about fire safety via the SIS smartphone app. A baseline and two follow-up surveys at 3 months and 6 months are conducted. Primary outcomes are: (1) having the correct child restraint for the child's age and size; (2) restraining the child in the back seat of the car; (3) buckling the child up for every ride; (4) having the restraint inspected by a child passenger safety technician; (5) having a working smoke alarm on every level of the home; (6) having hard-wired or lithium battery smoke alarms; (7) having and (8) practising a fire escape plan. Finding ways to communicate with parents about child passenger and fire safety continues to be a research priority. This study will contribute to the evidence about how to promote benefits of proper and consistent child restraint and smoke alarm use. NCT02345941; Pre-results. Published by the BMJ Publishing Group Limited. For permission to use (where not already granted under a licence) please go to http://www.bmj.com/company/products-services/rights-and-licensing/.

  8. Alkali chloride induced corrosion of superheaters under biomass firing conditions: Improved insights from laboratory scale studies

    DEFF Research Database (Denmark)

    Okoro, Sunday Chukwudi; Montgomery, Melanie; Jappe Frandsen, Flemming

    2015-01-01

    One of the major operational challenges experienced by power plants firing biomass is the high corrosion rate of superheaters. This limits the outlet steam temperature of the superheaters and consequently, the efficiency of the power plants. The high corrosion rates have been attributed to the fo......One of the major operational challenges experienced by power plants firing biomass is the high corrosion rate of superheaters. This limits the outlet steam temperature of the superheaters and consequently, the efficiency of the power plants. The high corrosion rates have been attributed......, [1–3]). However, complete understanding of the corrosion mechanism under biomass-firing conditions has not yet been achieved. This is attributed partly to the complex nature of the corrosion process since there are many species produced from fuel combustion which can interact with one another...... and the steel surface. Many studies have focused on specific parameters such as, deposit composition (KCl, K2SO4, K2CO3, etc.) or gas species such as HCl, SO2, H2O [4–6], however, more research is necessary to understand the interaction of deposits and gas mixtures with each other and metallic superheater...

  9. Radiation protection-culture. Culture improvement in radiation protection and ALARA behaviour

    International Nuclear Information System (INIS)

    Boehler, M.C.

    1994-12-01

    In order to that the optimization principle become an actual professional liable dynamical critter in the radiological protection topics, the hierarchic impulse and the personnel sensitiveness are determining. The ALARA (As Low As Reasonably Achievable) in the firm cultivation modify the behaviour and act philosophy. 7 refs., 2 figs

  10. Impact of fires on nuclear safety

    International Nuclear Information System (INIS)

    Skvarka, P.; Zmajkovic, I.

    1990-01-01

    Factors which are relevant with respect to fire hazard are summarized based on Revision 1 of IAEA Safety Guide No. 50-SG-D2, ''Fire Protection in Nuclear Power Plants'', of 1990. They include data acquisition, quantification of fire risks, assessment of adequacy of fire protection measures, modification of the fire protection system proposed. According to the above document, fire hazard analysis should define and document those parts of the fire protection system that must be present in order to secure safe operation of the nuclear power plant. (Z.M.). 2 appendices, 4 refs

  11. Protecting unauthorized immigrant mothers improves their children's mental health.

    Science.gov (United States)

    Hainmueller, Jens; Lawrence, Duncan; Martén, Linna; Black, Bernard; Figueroa, Lucila; Hotard, Michael; Jiménez, Tomás R; Mendoza, Fernando; Rodriguez, Maria I; Swartz, Jonas J; Laitin, David D

    2017-09-08

    The United States is embroiled in a debate about whether to protect or deport its estimated 11 million unauthorized immigrants, but the fact that these immigrants are also parents to more than 4 million U.S.-born children is often overlooked. We provide causal evidence of the impact of parents' unauthorized immigration status on the health of their U.S. citizen children. The Deferred Action for Childhood Arrivals (DACA) program granted temporary protection from deportation to more than 780,000 unauthorized immigrants. We used Medicaid claims data from Oregon and exploited the quasi-random assignment of DACA eligibility among mothers with birthdates close to the DACA age qualification cutoff. Mothers' DACA eligibility significantly decreased adjustment and anxiety disorder diagnoses among their children. Parents' unauthorized status is thus a substantial barrier to normal child development and perpetuates health inequalities through the intergenerational transmission of disadvantage. Copyright © 2017 The Authors, some rights reserved; exclusive licensee American Association for the Advancement of Science. No claim to original U.S. Government Works.

  12. History of Fire Events in the U.S. Commercial Nuclear Industry

    International Nuclear Information System (INIS)

    Bijan Najafi; Joglar-Biloch, Francisco; Kassawara, Robert P.; Khalil, Yehia

    2002-01-01

    Over the past decade, interest in performance-based fire protection has increased within the nuclear industry. In support of this growing interest, in 1997 the Electric Power Research Institute (EPRI) developed a long-range plan to develop/improve data and tools needed to support Risk-Informed/Performance-Based fire protection. This plan calls for continued improvement in collection and use of information obtained from fire events at nuclear plants. The data collection process has the objectives of improving the insights gained from such data and reducing the uncertainty in fire risk and fire modeling methods in order to make them a more reliable basis for performance based fire protection programs. In keeping with these objectives, EPRI continues to collect, review and analyze fire events in support of the nuclear industry. EPRI collects these records in cooperation with the Nuclear Electric Insurance Limited (NEIL), by compiling public fire event reports and by direct solicitation of U.S. nuclear facilities. EPRI fire data collection project is based on the principle that the understanding of history is one of the cornerstones of improving fire protection technology and practice. Therefore, the goal has been to develop and maintain a comprehensive database of fire events with flexibility to support various aspects of fire protection engineering. With more than 1850 fire records over a period of three decades and 2400 reactor years, this is the most comprehensive database of nuclear power industry fire events in existence today. In general, the frequency of fires in the U.S. commercial nuclear industry remains constant. In few cases, e.g., transient fires and fires in BWR offgas/recombiner systems, where either increasing or decreasing trends are observed, these trends tend to slow after 1980. The key issues in improving quality of the data remain to be consistency of the recording and reporting of fire events and difficulties in collection of records. EPRI has

  13. Workshop on explosions, BLEVEs, fires, etc.

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1995-12-31

    The purpose of this workshop will be to provide a bridge between engineering practices, modeling, and measurement of fires and explosions, and use this information in a practical manner to improve the fire safety of the process facility. New techniques and information are available on the means to prevent, predict and mitigate fires and explosions. A review of BLEVEs and methods for preventing and protecting against the effects of BLEVES in large petrochemical facilities. Observations and the use of models that have been successful in predicting the effects of vapor explosions for the prevention of collapse of structures and mitigation of the effects of vapor explosions in process facilities are presented. Recent work involving the measurement of radiation from large jet fires at the Kuwaiti oil fields and fire tests of crude oil spills on the sea is discussed. Fire radiation measurement can be used to predict effects on structures, facilities, and the complexity of fire fighting operations required for control of spill and pool fires. Practical applications of techniques for prevention and control of explosions within building, resulting from failures of autoclaves or release of flammable gas to the atmosphere of the building are discussed.

  14. Specialists' meeting on sodium fires

    Energy Technology Data Exchange (ETDEWEB)

    Kozlov, F A; Kuznetsova, R I [eds.

    1989-07-01

    The four sessions of the meeting covered the following topics: 1. general approach to fast reactor safety, standards of fire safety, maximum design basis accidents for sodium leaks and fires, status of sodium fires in different countries; 2. physical and chemical processes during combustion of sodium and its interaction with structural and technological materials and methods for structural protection; 3. methods of sodium fires extinguishing and measures for localizing aerosol combustion products, organization of fire fighting procedures, instruction and training of fire personnel; 4. elimination of the consequences of sodium fires.

  15. Specialists' meeting on sodium fires

    International Nuclear Information System (INIS)

    Kozlov, F.A.; Kuznetsova, R.I.

    1989-01-01

    The four sessions of the meeting covered the following topics: 1. general approach to fast reactor safety, standards of fire safety, maximum design basis accidents for sodium leaks and fires, status of sodium fires in different countries; 2. physical and chemical processes during combustion of sodium and its interaction with structural and technological materials and methods for structural protection; 3. methods of sodium fires extinguishing and measures for localizing aerosol combustion products, organization of fire fighting procedures, instruction and training of fire personnel; 4. elimination of the consequences of sodium fires

  16. Pre-fire planning for nuclear power plants

    International Nuclear Information System (INIS)

    Talbert, J.H.

    1980-01-01

    Regardless of the fire prevention measures which are taken, plant experience indicates that fires will occur in a nuclear power plant. When a fire occurs, the plant staff must handle the fire emergency. Pre-fire planning is a method of developing detailed fire attack plans and salvage operations to protect equipment from damage due to fire and fire fighting operations. This paper describes the purpose and use of a pre-fire plan to achieve these goals in nuclear power plants

  17. Improvement of radiation protection conditions during radiodiagnostic investigations

    International Nuclear Information System (INIS)

    Ivanov, E.V.; Livshits, R.E.; Lev, M.Ya.; Zakharenko, Yu.S.; Kal'nitskij, S.A.; Nechiporuk, V.I.

    1978-01-01

    Thermoluminescence dosimeters were used to estimate individual doses of radiation received by personnel of radiodiagnostic laboratories. The experiment, which lasted 3 months, showed that although the average levels of radiation did not exceed the permissible values, in some cases the personnel could receive an annual dose close to the maximum permissible one. A number of arrangements to improve radiation safety were proposed

  18. Advanced surface protection for improved reliability PCB systems (ASPIS)

    NARCIS (Netherlands)

    Ballantyne, A.; Forrest, G.; Goosey, M.; Griguceviciene, A.; Juodkazyte, J.; Kellner, R.; Kosenko, A.; Ramanauskas, R.; Ryder, K.; Selskis, A.; Tarozaite, R.; Veninga, E.

    2012-01-01

    Purpose - The purpose of this paper is to detail progress on the European Commission supported FP7 ASPIS project that is undertaking a multi-faceted approach to develop novel and improved nickel-gold (ENIG) solderable finish chemistries and processes in order to overcome issues such as "black pad"

  19. Development of aircraft lavatory compartments with improved fire resistance characteristics. Phase 4: Sandwich panel decorative ink development

    Science.gov (United States)

    Jayarajan, A.; Johnson, G. A.; Korver, G. L.; Anderson, R. A.

    1983-01-01

    Five chemically different resin systems with improved fire resistance properties were studied for a possible screenprinting ink application. Fire resistance is hereby defined as the cured ink possessing improvements in flammability, smoke emission, and thermal stability. The developed ink is for application to polyvinyl fluoride film. Only clear inks without pigments were considered. Five formulations were evaluated compared with KC4900 clear acrylic ink, which was used as a baseline. The tests used in the screening evaluation included viscosity, smoke and toxic gas emission, limiting oxygen index (LOI), and polyvinyl fluoride film (PVF) printability. A chlorofluorocarbon resin (FPC461) was selected for optimization studies. The parameters for optimization included screenprinting process performance, quality of coating, and flammability of screenprinted 0.051-mm (0.002-in.) white Tedlar. The quality of the screenprinted coating on Tedlar is dependent on viscosity, curing time, adhesion to polyvinyl fluoride film, drying time (both inscreen and as an applied film), and silk screen mesh material and porosity.

  20. Emergency watershed protection measures in highly unstable terrain on the Blake Fire, Six Rivers National Forest, 1987

    Science.gov (United States)

    Mark E. Smith; Kenneth A. Wright

    1989-01-01

    The Blake Fire burned about 730 ha of mature timber on the west slope of South Fork Mountain in northwestern California. Many steep innergorge and landslide headwall areas burned very hot, killing most large trees and consuming much of the large organic debris in unstable drainages. This created a potential for adverse effects on downstream fisheries from landsliding...

  1. Improving Mitochondrial Function Protects Bumblebees from Neonicotinoid Pesticides.

    Directory of Open Access Journals (Sweden)

    Michael B Powner

    Full Text Available Global pollination is threatened by declining insect pollinator populations that may be linked to neonicotinoid pesticide use. Neonicotinoids over stimulate neurons and depolarize their mitochondria, producing immobility and death. However, mitochondrial function can be improved by near infrared light absorbed by cytochrome c oxidase in mitochondrial respiration. In flies, daily exposure to 670nm light throughout life increases average lifespan and aged mobility, and reduces systemic inflammation. Here we treat bumble bees with Imidacloprid a common neonicotinoid. This undermined ATP and rapidly induced immobility and reduced visual function and survival. Bees exposed to insecticide and daily to 670nm light showed corrected ATP levels and significantly improved mobility allowing them to feed. Physiological recordings from eyes revealed that light exposure corrected deficits induced by the pesticide. Overall, death rates in bees exposed to insecticide but also given 670nm light were indistinguishable from controls. When Imidacloprid and light exposure were withdrawn, survival was maintained. Bees and insects generally cannot see deep red light so it does not disturb their behaviour. Hence, we show that deep red light exposure that improves mitochondrial function, reverses the sensory and motor deficits induced by Imidacloprid. These results may have important implications as light delivery is economic and can be placed in hives/colonies.

  2. Developing new serious games tools to improve radiation protection

    International Nuclear Information System (INIS)

    Majersky, T.; Rapant, T.; Bayer, M.; Majersky, D.

    2008-01-01

    In this paper, novel software technologies for simulation and training of workers in radiologically dangerous conditions are presented. Such new software tools enable the radiation protection managers and workers to better evaluate, visualize and intuitively understand the radiation situation. In the first part of the paper, virtual reality planning tool ALPLANNER is introduced. ALPLANNER enables computation of worker's doses and 3D simulation of planned activities in the environment. In the second part of the paper , a software technology SP ACEVISION for real-time interactive 3D visualization of radioactivity is presented. Radiation fields can be spatially and dynamically visualized in the environment using computer games technologies. Such real-time visualization can be used by RP staff to compute and visualize direct responses of the radiation field to the effects of shielding. Another presented application is determination and visualization of activity sources in inhomogeneous radiation fields. Practical example of how the mentioned software technologies are used during the decommissioning of NPP A-1 Jaslovske Bohunice is provided. Practical example of how the mentioned software technologies are used during the decommissioning of NPP A-1 Jaslovske Bohunice is provided. (authors)

  3. Developing new serious games tools to improve radiation protection

    International Nuclear Information System (INIS)

    Majersky, T.; Rapant, T.; Bayer, M.; Majersky, D.

    2009-01-01

    In this paper, novel software technologies for simulation and training of workers in radiologically dangerous conditions are presented. Such new software tools enable the radiation protection managers and workers to better evaluate, visualize and intuitively understand the radiation situation. In the first part of the paper, virtual reality planning tool ALPLANNER is introduced. ALPLANNER enables computation of worker's doses and 3D simulation of planned activities in the environment. In the second part of the paper , a software technology SP ACEVISION for real-time interactive 3D visualization of radioactivity is presented. Radiation fields can be spatially and dynamically visualized in the environment using computer games technologies. Such real-time visualization can be used by RP staff to compute and visualize direct responses of the radiation field to the effects of shielding. Another presented application is determination and visualization of activity sources in inhomogeneous radiation fields. Practical example of how the mentioned software technologies are used during the decommissioning of NPP A-1 Jaslovske Bohunice is provided. Practical example of how the mentioned software technologies are used during the decommissioning of NPP A-1 Jaslovske Bohunice is provided. (authors)

  4. Improved radiation protection for physicians performing cardiac catheterization

    International Nuclear Information System (INIS)

    Gertz, E.W.; Wisneski, J.A.; Gould, R.G.; Akin, J.R.

    1982-01-01

    Physicians and their assistants performing diagnostic angiography must be concerned with the radiation exposure they receive. The introduction of hemiaxial projections for imaging has increased diagnostic accuracy but has also greatly increased the physicians' exposure to scattered radiation. This increase is especially critical for the eyes and thyroid of the physician who routinely performs these procedures. To reduce such exposure a ceiling-suspended shield (60 x 45 cm), made of 6.4 mm glass with a 19.5 kg/m2 (4 lb/ft2) lead equivalency, was developed. During procedures the shield is interposed between the physician and the region of the patient acting as the source of scattered radiation. The degree of radiation protection to the operator was assessed by measuring the distribution of scattered radiation in the vicinity of the operator with and without the shield. The effectiveness of the shield was determined in the 30 degrees right anterior oblique (RAO), 5 degrees left anterior oblique (LAO), 35 degrees LAO, and 50 degrees LAO-15 degrees cranial angulations. At critical heights such as the level of the eyes and thyroid, scattered radiation levels were reduced by 85% or greater in all angulations. Without interfering with the physician's ability to observe the patient or manipulate the catheter, this shield can significantly reduce the physician's exposure to radiation

  5. Therapeutic games to improve attachment capabilities and protect sexual health.

    Science.gov (United States)

    Beier, Klaus M; Rebensburg, Klaus; Behrmann, Malte

    2010-01-01

    From the very beginning of life, man's fundamental needs for acceptance, security, trust, warmth and closeness can only be satisfied in relationships [1]. During infancy this is accomplished by body contact and the emotional experience of being taken care of, for instance by the sheltering manner in which an infant is held during breast-feeding. Through this parental loving care the modus of satisfying psychosocial fundamental needs by skin contact is learned by the infant and reinforced on a neuronal level, the way all processes of learning elementary skills generally are. According to present knowledge, chronic lack of security transmitted by frustration of psychosocial fundamental needs increases the probability of developing psychological and physical disorders. Furthermore it hinders overcoming prevailing diseases [2]. In developing therapeutic computer games this phylogenetically established programming for attachment in order to fulfill fundamental psychosocial needs will be the focus of interaction, cognitive triggers and strategic as well as emotional rules to be applied in the games which are designed in a modular way for difficult developmental phases (e.g. adolescence) or various chronic diseases. This is a new approach transferring sexological clinical experience into therapeutic computer games for prevention purposes and protection of sexual health.

  6. Characterization and improvement of coatings protecting concrete against contamination

    International Nuclear Information System (INIS)

    Bernard, A.; Gerland, H.

    1985-01-01

    A new type of coatings has been developped for the protection of concrete structures which simplifies the dismantling of nuclear power reactors and decreases the risks of getting a huge volume of wastes. These coatings are decontaminable, resistant, adherent and, if necessary, strippable. They usually consist of composite systems, in order to perfectly fulfill the often contradicting functions. This made difficult the development of such a material. Different tests have been performed on many systems using such a type of painting: decontamination test (standard NF T 30 901), artificial aging (standard NF T 30 049), peeling tests, chemical corrosion tests. Some of these coatings have been selected. Each of them is an example of a given configuration - one layer strippable coating, composite system, etc... Many other coatings although not reported, gave encouraging results. Although in apparent contradiction with the present subject, an other property of these removable coatings has been studied, namely the fixing of contamination. This could also give interesting results. A prototype of such a coating has been qualified. We also present here a device developed by the STMI company. This device would allow taking off the contaminated coatings in case of a problem with the normal removal. Using peeling coatings in the Nuclear Power Reactors in the CEE seems to be an interesting possibility for the future

  7. Safety protection and technical improvement of 60Co irradiation facilities

    International Nuclear Information System (INIS)

    Zhou Yongxing; Liang Cannan

    1993-01-01

    To ensure personal safety, some improvements has been made in the design of 60 Co irradiation compartment. The shielding door was interlocked while the 60 Co source to be lifted to the irradiation position or lowered to the shielded position. A universal change-over switch was used to cut the power supply when the source moved beyond the limits. Both γ-ray alarm and a closed-TV system were adopted. The electromagnetic attraction method was employed to shift the 60 Co source from the Pb container to the source pipe

  8. Wildland Fire Management Plan for Brookhaven National Laboratory

    Energy Technology Data Exchange (ETDEWEB)

    Green,T.

    2009-10-23

    This Wildland Fire Management Plan (FMP) for Brookhaven National Lab (BNL) updates the 2003 plan incorporating changes necessary to comply with DOE Order 450.1 and DOE P 450.4, Federal Wildland Fire Management Policy and Program Review; Wildland and Prescribed Fire Management Policy and implementation Procedures Reference Guide. This current plan incorporates changes since the original draft of the FMP that result from new policies on the national level. This update also removes references and dependence on the U.S. Fish & Wildlife Service and Department of the Interior, fully transitioning Wildland Fire Management responsibilities to BNL. The Department of Energy policy for managing wildland fires requires that all areas, managed by the DOE and/or its various contractors, that can sustain fire must have a FMP that details fire management guidelines for operational procedures associated with wild fire, operational, and prescribed fires. Fire management plans provide guidance on fire preparedness, fire prevention, wildfire suppression, and the use of controlled, 'prescribed' fires and mechanical means to control the amount of available combustible material. Values reflected in the BNL Wildland FMP include protecting life and public safety; Lab properties, structures and improvements; cultural and historical sites; neighboring private and public properties; and endangered, threatened, and species of concern. Other values supported by the plan include the enhancement of fire-dependent ecosystems at BNL. This FMP will be reviewed periodically to ensure the fire program advances and evolves with the missions of the DOE and BNL. This Fire Management Plan is presented in a format that coverers all aspects specified by DOE guidance documents which are based on the national template for fire management plans adopted under the National Fire Plan. The DOE is one of the signatory agencies on the National Fire Plan. This FMP is to be used and implemented for the

  9. A quantitative performance assessment of improved cooking stoves and traditional three-stone-fire stoves using a two-pot test design in Chamwino, Dodoma, Tanzania

    Science.gov (United States)

    Hafner, J.; Uckert, G.; Graef, F.; Hoffmann, H.; Kimaro, A. A.; Sererya, O.; Sieber, S.

    2018-02-01

    In Tanzania, a majority of rural residents cook using firewood-based three-stone-fire stoves. In this study, quantitative performance differences between technologically advanced improved cooking stoves and three-stone-fire stoves are analysed. We test the performance of improved cooking stoves and three-stone-fire stoves using local cooks, foods, and fuels, in the semi-arid region of Dodoma in Tanzania. We used the cooking protocol of the Controlled Cooking Test following a two-pot test design. The findings of the study suggest that improved cooking stoves use less firewood and less time than three-stone-fire stoves to conduct a predefined cooking task. In total, 40 households were assessed and ask to complete two different cooking tasks: (1) a fast cooking meal (rice and vegetables) and (2) a slow cooking meal (beans and rice). For cooking task 1, the results show a significant reduction in firewood consumption of 37.1% by improved cooking stoves compared to traditional three-stone-fire stoves; for cooking task 2 a reduction of 15.6% is found. In addition, it was found that the time needed to conduct cooking tasks 1 and 2 was significantly reduced by 26.8% and 22.8% respectively, when improved cooking stoves were used instead of three-stone-fire-stoves. We observed that the villagers altered the initial improved cooking stove design, resulting in the so-called modified improved cooking stove. In an additional Controlled Cooking Test, we conducted cooking task 3: a very fast cooking meal (maize flour and vegetables) within 32 households. Significant changes between the initial and modified improved cooking stoves regarding firewood and time consumption were not detected. However, analyses show that both firewood and time consumption during cooking was reduced when large amounts (for 6-7 household members) of food were prepared instead of small amounts (for 2-3 household members).

  10. Fire Perimeters

    Data.gov (United States)

    California Natural Resource Agency — The Fire Perimeters data consists of CDF fires 300 acres and greater in size and USFS fires 10 acres and greater throughout California from 1950 to 2003. Some fires...

  11. Fire History

    Data.gov (United States)

    California Natural Resource Agency — The Fire Perimeters data consists of CDF fires 300 acres and greater in size and USFS fires 10 acres and greater throughout California from 1950 to 2002. Some fires...

  12. Manual fire fighting tactics at Nuclear Power Plant

    International Nuclear Information System (INIS)

    Jee, Moon Hak; Moon, Chan Kook

    2012-01-01

    The general requirements of fire protection at nuclear power plant (NPP) are fire protection program, fire hazard analysis, and fire prevention features. In addition, specific fire protection requirements such as water supplies, fire detection, fire protection of safe related equipment, and safe shutdown capabilities must be provided. Particularly, manual fire fighting is required as specific requirements with the provisions to secure manual fire suppression, fire brigade and its training, and administrative controls for manual fire fighting. If a fire is alarmed and confirmed to be a real fire, the fire brigade must take manual fire fighting activities as requested at fire protection program. According to the present requirements in itself, there is not any specific manual fire fighting ways or practical strategies. In general, fire zones or compartments at NPPs are built in a confined condition. In theory, the fire condition will change from a combustible-controlled fire to a ventilation-governing fire with the time duration. In case of pool fire with the abundant oxygen and flammable liquid, it can take just a few minutes for the flash-over to occur. For the well-confined fire zone, it will change from a flame fire to a smoldering state before the entrance door is opened by the fire brigade. In this context, the manual fire fighting activities must be based on a quantitative analysis and a fire risk evaluation. At this paper, it was suggested that the fire zones at NPPs should be grouped on the inherent functions and fire characteristics. Based on the fire risk characteristics and the fire zone grouping, the manual fire fighting tactics are suggested as an advanced fire fighting solution

  13. Effectiveness of ventilation improvements as a protective measure against radon

    International Nuclear Information System (INIS)

    Hoving, P.; Arvela, H.

    1993-01-01

    Radon reduction rates for ventilation improvement measures vary considerably. In 70% of the cases studied, further mitigation is needed to reach a level of 400 Bq/m 3 . Ventilation measures in crawl spaces and basements have resulted in reduction rates of up to 90%, though more typically 30-70%. Installing new mechanical systems in dwellings has resulted in 20-80% reduction rates. If fan use or fan efficiency is increased, radon levels can be reduced as much as when new systems are installed. Increasing fresh-air supply through vents or window gaps reduces radon concentrations 10-40%. Low ventilation rates, measured after mitigation using the passive per fluorocarbon tracer gas method, seem to be accompanied by also low radon reduction rates. Multiple zone tracer gas measurements were conducted in order to reveal radon entry from the soil and radon transport between zones. (orig.). (3 refs., 3 figs., 2 tabs.)

  14. Possibilities for improving corrosion protection of reinforced concrete by modified hydrotalcites: a literature review

    NARCIS (Netherlands)

    Yang, Z.; Fischer, H.R.; Polder, R.B.

    2012-01-01

    Modified Hydrotalcites (MHTs) represent a group of technologically promising materials for improving corrosion protection in concrete owing to their low cost, relative simplicity of preparation, and plenty of composition variables. Numerous academic and commercial studies on MHTs have been carried

  15. Novel enabling technologies of gene isolation and plant transformation for improved crop protection

    Energy Technology Data Exchange (ETDEWEB)

    Torok, Tamas

    2013-02-04

    Meeting the needs of agricultural producers requires the continued development of improved transgenic crop protection products. The completed project focused on developing novel enabling technologies of gene discovery and plant transformation to facilitate the generation of such products.

  16. FIRE HAZARDS ANALYSIS - BUSTED BUTTE

    International Nuclear Information System (INIS)

    Longwell, R.; Keifer, J.; Goodin, S.

    2001-01-01

    The purpose of this fire hazards analysis (FHA) is to assess the risk from fire within individual fire areas at the Busted Butte Test Facility and to ascertain whether the DOE fire safety objectives are met. The objective, identified in DOE Order 420.1, Section 4.2, is to establish requirements for a comprehensive fire and related hazards protection program for facilities sufficient to minimize the potential for: (1) The occurrence of a fire related event. (2) A fire that causes an unacceptable on-site or off-site release of hazardous or radiological material that will threaten the health and safety of employees. (3) Vital DOE programs suffering unacceptable interruptions as a result of fire and related hazards. (4) Property losses from a fire and related events exceeding limits established by DOE. Critical process controls and safety class systems being damaged as a result of a fire and related events

  17. 30 CFR 75.1103-6 - Automatic fire sensors; actuation of fire suppression systems.

    Science.gov (United States)

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Automatic fire sensors; actuation of fire... Protection § 75.1103-6 Automatic fire sensors; actuation of fire suppression systems. Point-type heat sensors or automatic fire sensor and warning device systems may be used to actuate deluge-type water systems...

  18. Radiation protection education and training in Switzerland: What can be improved?

    International Nuclear Information System (INIS)

    Jahn, Swen-Gunnar

    2013-01-01

    In the frame of the amendment of the Swiss radiation protection regulations (StSV) the radiation protection education and training system is checked whether there is a need for improvement measures or the regulations have to be revised. Experiences, the comparison with other education and training systems and international developments were compiled and evaluated The responsible expert group with participants from authorities and instructors decided that no fundamental changes are necessary. In the contribution two items are discussed: The mandatory external consulting of licensees by acknowledged radiation protection experts - as required by the EU BSS (basic safety standards) with the definition of a radiation protection expert (RPE) - bears more disadvantages than advantages. On the other hand the improvement potential with respect to clearness and courtesy of requirements for radiation protection education and training in Switzerland were considered in the frame of WU-BSS revision.

  19. Improving Freight Fire Safety: Analysis and Testing of Real Engine Conditions to Progress Development of Mist-controlling Additives for Fire Mitigation

    Science.gov (United States)

    2009-12-01

    The formation of a fuel mist resulting from high shear stresses acting on the fuel during violent sloshing and tank rupture under the energy of a crash severely increases the occurrence and intensity of fires in transportation related accidents. In o...

  20. Does the Establishment of Sustainable Use Reserves Affect Fire Management in the Humid Tropics?

    Science.gov (United States)

    Carmenta, Rachel; Blackburn, George Alan; Davies, Gemma; de Sassi, Claudio; Lima, André; Parry, Luke; Tych, Wlodek; Barlow, Jos

    2016-01-01

    Tropical forests are experiencing a growing fire problem driven by climatic change, agricultural expansion and forest degradation. Protected areas are an important feature of forest protection strategies, and sustainable use reserves (SURs) may be reducing fire prevalence since they promote sustainable livelihoods and resource management. However, the use of fire in swidden agriculture, and other forms of land management, may be undermining the effectiveness of SURs in meeting their conservation and sustainable development goals. We analyse MODIS derived hot pixels, TRMM rainfall data, Terra-Class land cover data, socio-ecological data from the Brazilian agro-census and the spatial extent of rivers and roads to evaluate whether the designation of SURs reduces fire occurrence in the Brazilian Amazon. Specifically, we ask (1) a. Is SUR location (i.e., de facto) or (1) b. designation (i.e. de jure) the driving factor affecting performance in terms of the spatial density of fires?, and (2), Does SUR creation affect fire management (i.e., the timing of fires in relation to previous rainfall)? We demonstrate that pre-protection baselines are crucial for understanding reserve performance. We show that reserve creation had no discernible impact on fire density, and that fires were less prevalent in SURs due to their characteristics of sparser human settlement and remoteness, rather than their status de jure. In addition, the timing of fires in relation to rainfall, indicative of local fire management and adherence to environmental law, did not improve following SUR creation. These results challenge the notion that SURs promote environmentally sensitive fire-management, and suggest that SURs in Amazonia will require special attention if they are to curtail future accidental wildfires, particularly as plans to expand the road infrastructure throughout the region are realised. Greater investment to support improved fire management by farmers living in reserves, in addition to

  1. Does the Establishment of Sustainable Use Reserves Affect Fire Management in the Humid Tropics?

    Directory of Open Access Journals (Sweden)

    Rachel Carmenta

    Full Text Available Tropical forests are experiencing a growing fire problem driven by climatic change, agricultural expansion and forest degradation. Protected areas are an important feature of forest protection strategies, and sustainable use reserves (SURs may be reducing fire prevalence since they promote sustainable livelihoods and resource management. However, the use of fire in swidden agriculture, and other forms of land management, may be undermining the effectiveness of SURs in meeting their conservation and sustainable development goals. We analyse MODIS derived hot pixels, TRMM rainfall data, Terra-Class land cover data, socio-ecological data from the Brazilian agro-census and the spatial extent of rivers and roads to evaluate whether the designation of SURs reduces fire occurrence in the Brazilian Amazon. Specifically, we ask (1 a. Is SUR location (i.e., de facto or (1 b. designation (i.e. de jure the driving factor affecting performance in terms of the spatial density of fires?, and (2, Does SUR creation affect fire management (i.e., the timing of fires in relation to previous rainfall? We demonstrate that pre-protection baselines are crucial for understanding reserve performance. We show that reserve creation had no discernible impact on fire density, and that fires were less prevalent in SURs due to their characteristics of sparser human settlement and remoteness, rather than their status de jure. In addition, the timing of fires in relation to rainfall, indicative of local fire management and adherence to environmental law, did not improve following SUR creation. These results challenge the notion that SURs promote environmentally sensitive fire-management, and suggest that SURs in Amazonia will require special attention if they are to curtail future accidental wildfires, particularly as plans to expand the road infrastructure throughout the region are realised. Greater investment to support improved fire management by farmers living in reserves

  2. Fire Hazard Analysis for the Cold Vacuum Drying (CVD) Facility

    Energy Technology Data Exchange (ETDEWEB)

    JOHNSON, B.H.

    1999-08-19

    This Fire Hazard Analysis assesses the risk from fire within individual fire areas in the Cold Vacuum Drying Facility at the Hanford Site in relation to existing or proposed fire protection features to ascertain whether the objectives of DOE Order 5480.7A Fire Protection are met.

  3. Fire Hazard Analysis for the Cold Vacuum Drying (CVD) Facility

    International Nuclear Information System (INIS)

    JOHNSON, B.H.

    1999-01-01

    This Fire Hazard Analysis assesses the risk from fire within individual fire areas in the Cold Vacuum Drying Facility at the Hanford Site in relation to existing or proposed fire protection features to ascertain whether the objectives of DOE Order 5480.7A Fire Protection are met

  4. ASSESSMENT OF THE UTILITY OF THE ADVANCED HIMAWARI IMAGER TO DETECT ACTIVE FIRE OVER AUSTRALIA

    Directory of Open Access Journals (Sweden)

    B. Hally

    2016-06-01

    Full Text Available Wildfire detection and attribution is an issue of importance due to the socio-economic impact of fires in Australia. Early detection of fires allows emergency response agencies to make informed decisions in order to minimise loss of life and protect strategic resources in threatened areas. Until recently, the ability of land management authorities to accurately assess fire through satellite observations of Australia was limited to those made by polar orbiting satellites. The launch of the Japan Meteorological Agency (JMA Himawari-8 satellite, with the 16-band Advanced Himawari Imager (AHI-8 onboard, in October 2014 presents a significant opportunity to improve the timeliness of satellite fire detection across Australia. The near real-time availability of images, at a ten minute frequency, may also provide contextual information (background temperature leading to improvements in the assessment of fire characteristics. This paper investigates the application of the high frequency observation data supplied by this sensor for fire detection and attribution. As AHI-8 is a new sensor we have performed an analysis of the noise characteristics of the two spectral bands used for fire attribution across various land use types which occur in Australia. Using this information we have adapted existing algorithms, based upon least squares error minimisation and Kalman filtering, which utilise high frequency observations of surface temperature to detect and attribute fire. The fire detection and attribution information provided by these algorithms is then compared to existing satellite based fire products as well as in-situ information provided by land management agencies. These comparisons were made Australia-wide for an entire fire season - including many significant fire events (wildfires and prescribed burns. Preliminary detection results suggest that these methods for fire detection perform comparably to existing fire products and fire incident reporting

  5. New tendencies in wildland fire simulation for understanding fire phenomena: An overview of the WFDS system capabilities in Mediterranean ecosystems

    Science.gov (United States)

    Pastor, E.; Tarragó, D.; Planas, E.

    2012-04-01

    Wildfire theoretical modeling endeavors predicting fire behavior characteristics, such as the rate of spread, the flames geometry and the energy released by the fire front by applying the physics and the chemistry laws that govern fire phenomena. Its ultimate aim is to help fire managers to improve fire prevention and suppression and hence reducing damage to population and protecting ecosystems. WFDS is a 3D computational fluid dynamics (CFD) model of a fire-driven flow. It is particularly appropriate for predicting the fire behaviour burning through the wildland-urban interface, since it is able to predict the fire behaviour in the intermix of vegetative and structural fuels that comprise the wildland urban interface. This model is not suitable for operational fire management yet due to computational costs constrains, but given the fact that it is open-source and that it has a detailed description of the fuels and of the combustion and heat transfer mechanisms it is currently a suitable system for research purposes. In this paper we present the most important characteristics of the WFDS simulation tool in terms of the models implemented, the input information required and the outputs that the simulator gives useful for understanding fire phenomena. We briefly discuss its advantages and opportunities through some simulation exercises of Mediterranean ecosystems.

  6. WILDLAND FIRE MANAGEMENT PLAN FOR BROOKHAVEN NATIONAL LABORATORY.

    Energy Technology Data Exchange (ETDEWEB)

    ENVIRONMENTAL AND WASTE MANAGEMENT SERVICES DIVISION

    2003-09-01

    This Wildland Fire Management Plan (FMP) for Brookhaven National Lab (BNL) and the Upton Ecological and Research Reserve (Upton Reserve) is based on the U.S. Fish & Wildlife Service (FWS) fire management planning procedures and was developed in cooperation with the Department of Energy (DOE) by Brookhaven Science Associates. As the Upton Reserve is contained within the BNL 5,265-acre site, it is logical that the plan applies to both the Upton Reserve and BNL. The Department of the Interior policy for managing wildland fires requires that all areas managed by FWS that can sustain fire must have an FMP that details fire management guidelines for operational procedures and specifies values to be protected or enhanced. Fire management plans provide guidance on fire preparedness, fire prevention, wildfire suppression, and the use of controlled, ''prescribed'' fires and mechanical means to control the amount of available combustible material. Values reflected in the BNL/Upton Reserve Wildland FMP include protecting life and public safety; Lab properties, structures and improvements; cultural and historical sites; neighboring private and public properties; and endangered and threatened species and species of concern. Other values supported by the plan include the enhancement of fire-dependent ecosystems at BNL and the Upton Reserve. This FMP will be reviewed periodically to ensure the fire program advances and evolves with the missions of FWS, BNL, and the Upton Reserve. This Fire Management Plan is a modified version of the Long Island National Wildlife Refuge Complex Fire plan (updated in 2000), which contains all FWS fire plan requirements and is presented in the format specified by the national template for fire management plans adopted under the National Fire Plan. The DOE is one of the signatory agencies on the National Fire Plan. FWS shall be, through an Interagency Agreement dated November 2000 (Appendix C), responsible for coordinating and

  7. Fire hazard analysis for the fuel supply shutdown storage buildings

    International Nuclear Information System (INIS)

    REMAIZE, J.A.

    2000-01-01

    The purpose of a fire hazards analysis (FHA) is to comprehensively assess the risk from fire and other perils within individual fire areas in a DOE facility in relation to proposed fire protection so as to ascertain whether the objectives of DOE 5480.7A, Fire Protection, are met. This Fire Hazards Analysis was prepared as required by HNF-PRO-350, Fire Hazards Analysis Requirements, (Reference 7) for a portion of the 300 Area N Reactor Fuel Fabrication and Storage Facility

  8. Fire safety engineering

    International Nuclear Information System (INIS)

    Smith, D.N.

    1989-01-01

    The periodic occurrence of large-scale, potentially disastrous industrial accidents involving fire in hazardous environments such as oilwell blowouts, petrochemical explosions and nuclear installations highlights the need for an integrated approach to fire safety engineering. Risk reduction 'by design' and rapid response are of equal importance in the saving of life and property in such situations. This volume of papers covers the subject thoroughly, touching on such topics as hazard analysis, safety design and testing, fire detection and control, and includes studies of fire hazard in the context of environment protection. (author)

  9. Overview of fire curtains in construction

    Directory of Open Access Journals (Sweden)

    Nedryshkin Oleg

    2016-01-01

    Full Text Available A fire curtain is use where, if there is a fire, it is necessary to create a temporary barrier within an opening, which seals off the area on fire. The curtain descends and prevents any fire and smoke from spreading from one area to another. It also allows people access to protected escape routes without any loss of fire resistance. The paper aims to presents the results of analysis of the scientific literature on the subject of fire curtains.

  10. FIRE PERMIT NOW ON EDH!

    CERN Multimedia

    TIS General Safety Group or

    2001-01-01

    The electronic version of the Fire Permit form is now active. The aim of the Fire Permit procedure is to reduce the risk of fire or explosion. It is mandatory when performing 'hot work' (mainly activities which involve the use of naked flames or other heat sources - e.g. welding, brazing, cutting, grinding, etc.). Its use is explained in the CERN Fire Protection Code E. (Fire Protection) The new electronic form, which is substantially unchanged from the previous authorizing procedure, will be available on the Electronic Document Handling system (https://edh.cern.ch/) as of 1st September 2001. From this date use of the paper version should be discontinued.

  11. Fire detection in warehouse facilities

    CERN Document Server

    Dinaburg, Joshua

    2013-01-01

    Automatic sprinklers systems are the primary fire protection system in warehouse and storage facilities. The effectiveness of this strategy has come into question due to the challenges presented by modern warehouse facilities, including increased storage heights and areas, automated storage retrieval systems (ASRS), limitations on water supplies, and changes in firefighting strategies. The application of fire detection devices used to provide early warning and notification of incipient warehouse fire events is being considered as a component of modern warehouse fire protection.Fire Detection i

  12. Process to realize a tight and fire-proof cable penetration, ensuring a biological protection and associated cable penetration

    International Nuclear Information System (INIS)

    Beckers, G.

    1986-01-01

    According to the present invention, the cables pass through a wall by means of an opening. A casting panel is realized for plugging each opening face, and a viscous, rapid-setting and fire-proof cement is injected to form continuous external caps. One spare tube allows the inside part to communicate with the outside of the opening; a liquid resin mixture containing at least a material of high atomic weight is injected through this tube between the two casting panels. The resin harden by polymerization in-situ. The invention applies, more particularly, to cable penetrations in nuclear reactors [fr

  13. Nuclear hazard/fire hazard: an elusive and important linkage

    International Nuclear Information System (INIS)

    Mariani, L.P.

    1977-01-01

    The Brown's Ferry Fire signaled a yellow alert for nuclear safety related fire protection and showed that fire protection engineering must be regarded as a bona fide nuclear discipline. A single-failure design criteria violation resulted in fire damage to plant systems and plant instrumentation. Localized damage lead to significant consequences. Although the linkage between fire and nuclear hazard is termed subtle, effective standards and criteria development must be aimed to future plants. Combined fire protection and nuclear engineering inspections are planned

  14. The Calculation and Design of Fire suppression system in the proton accelerator research center

    International Nuclear Information System (INIS)

    Jeon, G. P.; Kim, J. Y.; Cho, J. H.; Min, Y. S.; Mun, K. J.; Cho, J. S.; Nam, J. M.; Park, S. S.; Joo, H. G.

    2010-01-01

    The fire protection system is composed of various fire suppression systems and fire detection and alarm systems. The primary function of the fire protection system is to protect life and property from a fire through detecting fires quickly and suppressing those fires that occur. In this paper, we described the fire suppression system only. The fire suppression system capacity for fire hydrant, the water mist system, sprinkler system and clean agent system is calculated and designed in compliance with the applicable Korean Acts that are applicable to fire protection and the NFSC code

  15. Location Privacy Protection Based on Improved K-Value Method in Augmented Reality on Mobile Devices

    Directory of Open Access Journals (Sweden)

    Chunyong Yin

    2017-01-01

    Full Text Available With the development of Augmented Reality technology, the application of location based service (LBS is more and more popular, which provides enormous convenience to people’s life. User location information could be obtained at anytime and anywhere. So user location privacy security suffers huge threats. Therefore, it is crucial to pay attention to location privacy protection in LBS. Based on the architecture of the trusted third party (TTP, we analyzed the advantages and shortages of existing location privacy protection methods in LBS on mobile terminal. Then we proposed the improved K-value location privacy protection method according to privacy level, which combines k-anonymity method with pseudonym method. Through the simulation experiment, the results show that this improved method can anonymize all service requests effectively. In addition to the experiment of execution time, it demonstrated that our proposed method can realize the location privacy protection more efficiently.

  16. Forest Fire Occurrence in Southern Counties, 1966-1975

    Science.gov (United States)

    M.L. Doolittle

    1977-01-01

    Forest fire occurrence data for individual protection units generally are unavailable outside particular state organization. Number of fires, area protected and fire occurrence rate (fires per 1,000,000 acres) from 1966 to 1975, are presented in tables for the 993 counties under protection in 13 southern states. These data are compared with data for the preceeding...

  17. Instrumentation for mine safety: fire and smoke problems and solutions

    International Nuclear Information System (INIS)

    Stevens, R.B.

    1982-01-01

    Underground fires continue to be one of the most serious hazards to life and property in the mining industry. Although underground mines are analogous to high-rise buildings where persons are isolated from immediate escape or rescue, application of technology to locate and control fire hazards while still in their controllable state is slow to be implemented in underground mines. This paper describes several USBM (Bureau of Mines) safety programs which included in-mine testing with mine fire and smoke sensors, telemetry and instrumentation to develop recommendations for improving mine fire safety. It is hoped that the technology developed during these programs can be added to other programs to provide the mining industry with the necessary fire safety facts. By recognizing fire potentials and being provided with cost-effective, proven components that will perform reliably under the poor environmental conditions of mining, mine operators can provide protection for their working life and property equal to that which they provide for themselves and their families at home. The basis of this report is two USBM programs for fire protection in metal and nonmetal mines and one coal program. The data was collected beginning in May 1974 and continuing through the present with underground tests of a South African fire system installed at Magma Mine in Superior, Arizona, and a computer-assisted, experimental system at Peabody Coal Mine in Pawnee, Illinois

  18. INVESTIGATION OF MICROPROCESSOR CURRENT PROTECTION LINES WITH IMPROVED INDICES OF TECHNICAL PERFECTION

    Directory of Open Access Journals (Sweden)

    E. V. Buloichyk

    2014-01-01

    Full Text Available Technical perfection improvement of microprocessor current protection of distribution networks lines is provided by introduction of asymmetrical fault mode determination and fault location functions in the algorithm of its functioning. As a result of computing experiment the basic indices of the technical perfection of current protection have been obtained in the paper. The paper proves high efficiency of the proposed methods that ensure selective and proper operation in the different modes of the controlled line.

  19. Fire performance, microstructure and thermal degradation of an epoxy based nano intumescent fire retardant coating for structural applications

    Energy Technology Data Exchange (ETDEWEB)

    Aziz, Hammad, E-mail: engr.hammad.aziz03@gmail.com; Ahmad, Faiz, E-mail: faizahmad@petronas.com.my; Yusoff, P. S. M. Megat; Zia-ul-Mustafa, M. [Department of Mechanical Engineering, Universiti Teknologi PETRONAS, Bandar Seri Iskandar, Tronoh 31750, Perak (Malaysia)

    2015-07-22

    Intumescent fire retardant coating (IFRC) is a passive fire protection system which swells upon heating to form expanded multi-cellular char layer that protects the substrate from fire. In this research work, IFRC’s were developed using different flame retardants such as ammonium polyphosphate, expandable graphite, melamine and boric acid. These flame retardants were bound together with the help of epoxy binder and cured together using curing agent. IFRC was then reinforced with nano magnesium oxide and nano alumina as inorganic fillers to study their effect towards fire performance, microstructure and thermal degradation. Small scale fire test was conducted to investigate the thermal insulation of coating whereas fire performance was calculated using thermal margin value. Field emission scanning electron microscopy was used to examine the microstructure of char obtained after fire test. Thermogravimetric analysis was conducted to investigate the residual weight of coating. Results showed that the performance of the coating was enhanced by reinforcement with nano size fillers as compared to non-filler based coating. Comparing both nano size magnesium oxide and nano size alumina; nano size alumina gave better fire performance with improved microstructure of char and high residual weight.

  20. 46 CFR 118.600 - Fire axe.

    Science.gov (United States)

    2010-10-01

    ... 46 Shipping 4 2010-10-01 2010-10-01 false Fire axe. 118.600 Section 118.600 Shipping COAST GUARD... OVERNIGHT ACCOMMODATIONS FOR MORE THAN 49 PASSENGERS FIRE PROTECTION EQUIPMENT Additional Equipment § 118.600 Fire axe. A vessel of more than 19.8 meters (65 feet) in length must have at least one fire axe...