WorldWideScience

Sample records for efficient air cleaning

  1. The high efficiency steel filters for nuclear air cleaning

    International Nuclear Information System (INIS)

    Bergman, W.; Larsen, G.; Lopez, R.; Williams, K.; Violet, C.

    1990-08-01

    We have, in cooperation with industry, developed high-efficiency filters made from sintered stainless-steel fibers for use in several air-cleaning applications in the nuclear industry. These filters were developed to overcome the failure modes in present high-efficiency particulate air (HEPA) filters. HEPA filters are made from glass paper and glue, and they may fail when they get hot or wet and when they are overpressured. In developing our steel filters, we first evaluated the commercially available stainless-steel filter media made from sintered powder and sintered fiber. The sintered-fiber media performed much better than sintered-powder media, and the best media had the smallest fiber diameter. Using the best media, we then built prototype filters for venting compressed gases and evaluated them in our automated filter tester. 12 refs., 20 figs

  2. High efficiency steel filters for nuclear air cleaning

    International Nuclear Information System (INIS)

    Bergman, W.; Conner, J.; Larsen, G.; Lopez, R.; Turner, C.; Vahla, G.; Violet, C.; Williams, K.

    1991-01-01

    The authors have, in cooperation with industry, developed high-efficiency filters made from sintered stainless-steel fibers for use in several air-cleaning applications in the nuclear industry. These filters were developed to overcome the failure modes in present high-efficiently particulate air (HEPA) filters. HEPA filters are made from glass paper and glue, and they may fail when they get hot or wet and when they are overpressured. In developing steel filters, they first evaluated the commercially available stainless-steel filter media made from sintered powder and sintered fiber. The sintered-fiber media performed much better than sintered-powder media, and the best media had the smallest fiber diameter. Using the best media, prototype filters were then built for venting compressed gases and evaluated in their automated filter tester

  3. Nuclear air cleaning

    International Nuclear Information System (INIS)

    Bellamy, R.R.

    1994-01-01

    This report briefly describes the history of the use of high- efficiency particulate air filters for air cleaning at nuclear installations in the United States and discusses future uses of such filters

  4. Air cleaning efficiency of deodorant materials under dynamic conditions: effect of air flow rate

    DEFF Research Database (Denmark)

    Mizutani, Chiyomi; Bivolarova, Mariya Petrova; Melikov, Arsen Krikor

    2014-01-01

    Unpleasant odor is a serious problem in hospitals and elderly facilities. One of the unpleasant odors is ammonia originating from human urine and sweat. The air cleaning efficiency of porous activated carbon fiber fabric which has been treated with acid, and porous activated carbon fiber fabric...... mixed with ammonia gas at a concentration of 20 ppm and velocities of 0.05, 0.15, 0.3 and 1.2 m/s. The activated carbon fibers treated with acid had a high deodorizing effect for ammonia (0.8) at a velocity of 0.05 m/s. The deodorizing effect of this material decreased with the increase in the velocity....... The porous activated carbon fiber fabric did not have a deodorant effect....

  5. Investigation of efficiency of air cleaning from acetone using a segmental construction biofilter

    Directory of Open Access Journals (Sweden)

    Denas Bacevičius

    2015-10-01

    Full Text Available Volatile organic compounds, e. g. acetone, have a direct impact on climate change, decrease of ozone in the air, and on the growth of greenhouse effect. One of the most popular air purifying methods from VOC is a biological air cleaning. Experimental investigations were conducted to determine the efficiency of the new structure of biofilter with polypropylene plates segments. During the investigations the efficiency of segmental construction biofilter of air purification at different initial concentrations of pollutants was determined. Different concentrations of pollutants were estimated during the acetone dilution with water. During the tests the efficiency of biofilter air purification from acetone vapor and its change under different concentrations of vapors was set. Based on test results, the maximum efficiency of biofilter air purification was up to 93%. Studies have shown that increasing the allowable pollutant concentration, the efficiency of air purification unit decreases. Increasing the concentration of supplied acetone vapor into the biofilter from 232 to 701 mg/m3, cleaning efficiency decreased from 92.8 to 82.3%. Since microorganisms fail to oxidize organic compounds, the filter works better at lower initial concentrations of pollutants.

  6. Feasibility for the medium efficiency filter as a postfilter in the air cleaning unit

    International Nuclear Information System (INIS)

    Lim, H. S.; Jung, D. Y.; Byun, S. C.; Kim, S. H.

    2002-01-01

    The Air Cleaning Unit (ACU) is provided in a nuclear facility to filter the radioactive materials in gaseous effluents released from the facility during normal operation and during a postulated accident. The Air Cleaning Unit (ACU) consists of pre-HEPA filters, charcoal adsorber, post HEPA filters, fans, etc. The charcoal filters keep on-site dose and off-site effluents ALARA, consistent with regulatory requirements. The function of HEPA filter downstream of charcoal(carbon) adsorber in ACU is to catch potential radioactive carbon dust and to be a backup in the event of failure of upstream HEPA. Previous Regulatory Guide use only post HEPA filter of charcoal adsorber downstream but the Regulatory Guide of current revisions allows use of 95% dust spot efficiency filters in lieu of HEPA at the downstream of the carbon adsorber. In this paper is described that the background information of filters, Current Regulatory Guide of revised by the United States Nuclear Regulatory Commission and the feasibility for the medium efficiency filter as a carbon adsorber post filter in the Air Cleaning Unit

  7. Energy efficient biological air cleaning for farm stable ventilation; Energieffektiv biologisk luftrensning til staldventilation

    Energy Technology Data Exchange (ETDEWEB)

    Groenborg Nicolaisen, C.; Hansen, Mads P.R. [Teknologisk Institut, Aarhus (Denmark); Stroem, J.; Soerensen, Keld [DXT. Danish Exergy Technology A/S, Skoerping (Denmark); Goetke, C. [Lokalenergi Aarhus, Viby J. (Denmark); Morsing, S.; Soerensen, Lars C. [SKOV A/S, Roslev (Denmark); Ladegaerd Jensen, T.; Pedersen, Poul [Videncenter for svineproduktion, Copenhagen (Denmark)

    2013-05-01

    The project has been designed to reduce energy consumption for air purification by 30% while having a payback period of maximum 3 years. The project has achieved very significant results which are far above the target. Particularly satisfying is the wide range of new components that are launched in late 2012. By implementing the newly developed system at 100% cleaning (LPC 13 ventilators and Dynamic multistep control) in relation to Best Practice (SKOV's original system with DA600 fans) in a concrete pigsty, a saving of 61% and a simple payback of 1.7 years is achieved. Similarly, it is found that the energy used for pump operation can be reduced by 37% with the new Dynamic sprinkling control. At 20% cleaning a potential saving of 15% per year and a payback period of between 0 and 5 years was found, which is dependent on the desired performance as the capacities in the bio-filter's upper capacity range between 26 thousand to 30 thousand m3 / h entails costs for an additional extraction unit in the new solution. Furthermore, the newly developed components proved highly suitable for standard installations without air cleaning where a savings potential is 53% and the payback period 1.5 years. Product-wise, the project formed the basis for the development of: 1. New energy-efficient ventilation units (LPC11, 12,13) that are suitable for air purification; 2. A new energy-saving control principle (Dynamic Multi-Step) which is particularly suitable for low-energy ventilators; 3. A new energy-saving flow measurement system for ventilating ducts (Dynamic air to the central exhaust); 4. An energy-saving pressure control in common ducts (pressure control as a function of outside temperature); 5. Proposal for a new energy-saving pump operation for sprinkling of biological filters (Dynamic sprinkling). (LN)

  8. Canada's Clean Air Act

    International Nuclear Information System (INIS)

    2006-01-01

    This paper provided an outline of Canada's Clean Air Act and examined some of the regulatory changes that will occur as a result of its implementation. The Act is being introduced to strengthen the legislative basis for taking action on reducing air pollution and GHGs, and will allow the government to regulate both indoor and outdoor air pollutants and GHGs. The Act will require the Ministers of the Environment and Health to establish national air quality objectives, as well as to monitor and report on their attainment. The Canadian Environmental Protection Act will be amended to enable the government to regulate the blending of fuels and their components. The Motor Vehicle Fuel Consumption Standards Act will also be amended to enhance the government's authority to regulate vehicle fuel efficiency. The Energy Efficiency Act will also be expanded to allow the government to set energy efficiency standards and labelling requirements for a wider range of consumer and commercial products. The Act will commit to short, medium and long-term industrial air pollution targets. Regulations will be proposed for emissions from industry; on-road and off-road vehicles and engines; and consumer and commercial products. It was concluded that the Government of Canada will continue to consult with provinces, territories, industries and Canadians to set and reach targets for the reduction of both indoor and outdoor air pollutants and GHG emissions. 6 figs

  9. Interactions between energy efficiency and emission trading under the 1990 Clean Air Act Amendments

    International Nuclear Information System (INIS)

    Hillsman, E.L.; Alvic, D.R.

    1994-08-01

    The 1990 Clean Air Act Amendments affect electric utilities in numerous ways. The feature that probably has received the greatest attention is the provision to let utilities trade emissions of sulfur dioxide (SO 2 ), while at the same time requiring them to reduce S0 2 emissions in 2000 by an aggregate 43%. The emission trading system was welcomed by many as a way of reducing the cost of reducing emissions, by providing greater flexibility than past approaches. This report examines some of the potential interactions between trading emissions and increasing end-use energy efficiency. The analysis focuses on emission trading in the second phase of the trading program, which begins in 2000. The aggregate effects, calculated by an emission compliance and trading model, turn out to be rather small. Aggressive improvement of end-use efficiency by all utilities might reduce allowance prices by $22/ton (1990 dollars), which is small compared to the reduction that has occurred in the estimates of future allowance prices and when compared to the roughly $400/ton price we estimate as a base case. However, the changes in the allowance market that result are large enough to affect some compliance decisions. If utilities in only a few states improve end-use efficiency aggressively, their actions may not have a large effect on the price of an allowance, but they could alter the demand for allowances and thereby the compliance decisions of utilities in other states. The analysis shows how improving electricity end-use efficiency in some states can cause smaller emission reductions in other states, relative to what would have happened without the improvements. Such a result, while not surprising given the theory behind the emission trading system, is upsetting to people who view emissions, environmental protection, and energy efficiency in moral rather than strictly economic terms

  10. Efficiency enhancement in IGCC power plants with air-blown gasification and hot gas clean-up

    International Nuclear Information System (INIS)

    Giuffrida, Antonio; Romano, Matteo C.; Lozza, Giovanni

    2013-01-01

    Air-blown IGCC systems with hot fuel gas clean-up are investigated. In detail, the gas clean-up station consists of two reactors: in the first, the raw syngas exiting the gasifier and passed through high-temperature syngas coolers is desulfurized by means of a zinc oxide-based sorbent, whereas in the second the sulfided sorbent is duly regenerated. The hot fuel gas clean-up station releases H 2 S-free syngas, which is ready to fuel the combustion turbine after hot gas filtration, and a SO 2 -laden stream, which is successively treated in a wet scrubber. A thermodynamic analysis of two air-blown IGCC systems, the first with cold fuel gas clean-up and the second with hot fuel gas clean-up, both with a state-of-the-art combustion turbine as topping cycle, shows that it is possible to obtain a really attractive net efficiency (more than 51%) for the second system, with significant improvements in comparison with the first system. Nevertheless, higher efficiency is accomplished with a small reduction in the power output and no sensible efficiency improvements seem to be appreciated when the desulfurization temperature increases. Other IGCC systems, with an advanced 1500 °C-class combustion turbine as the result of technology improvements, are investigated as well, with efficiency as high as 53%. - Highlights: ► Hot fuel gas clean-up is a highly favorable technology for IGCC concepts. ► Significant IGCC efficiency improvements are possible with hot fuel gas clean-up. ► Size reductions of several IGCC components are possible. ► Higher desulfurization temperatures do not sensibly affect IGCC efficiency. ► IGCC efficiency as high as 53% is possible with a 1500°C-class combustion turbine

  11. The Clean Air Act

    International Nuclear Information System (INIS)

    Coburn, L.L.

    1990-01-01

    The Clean Air Act amendments alter the complex laws affecting atmospheric pollution and at the same time have broad implications for energy. Specifically, the Clean Air Act amendments for the first time deal with the environmental problem of acid deposition in a way that minimizes energy and economic impacts. By relying upon a market-based system of emission trading, a least cost solution will be used to reduce sulfur dioxide (SO 2 ) emissions by almost 40 percent. The emission trading system is the centerpiece of the Clean Air Act (CAA) amendments effort to resolve energy and environmental interactions in a manner that will maximize environmental solutions while minimizing energy impacts. This paper will explore how the present CAA amendments deal with the emission trading system and the likely impact of the emission trading system and the CAA amendments upon the electric power industry

  12. Self Cleaning High Efficiency Particulate Air (HEPA) Filtration without Interrupting Process Flow - 59347

    International Nuclear Information System (INIS)

    Chadwick, Chris

    2012-01-01

    The strategy of protecting the traditional glass fibre HEPA filtration train from it's blinding contamination and the recovery of dust by the means of self cleaning, pre-filtration is a proven means in the reduction of ultimate disposal volumes and has been used within the Fuel Production Industry. However, there is an increasing demand in nuclear applications requiring elevated operating temperatures, fire resistance, moisture resistance and chemical composition that the existing glass fibre HEPA filtration cannot accommodate, which can be remedied by the use of a metallic HEPA filter media. Previous research suggests that the then costs to the Department of Energy (DOE), based on a five year life cycle, was $29.5 million for the installation, testing, removal and disposal of glass fibre HEPA filtration trains. Within these costs, $300 was the value given to the filter and $4, 450 was given to the peripheral activity. Development of a low cost, cleanable, metallic, direct replacement of the traditional filter train will the clear solution. The Bergman et al work has suggested that a 1000 ft 3 /min, cleanable, stainless HEPA could be commercially available for $5, 000 each, whereas the industry has determined that the truer cost of such an item in isolation would be closer to $15, 000. This results in a conflict within the requirement between 'low cost' and 'stainless HEPA'. By proposing a system that combines metallic HEPA filtration with the ability to self clean without interrupting the process flow, the need for a tradition HEPA filtration train will be eliminated and this dramatically reduces the resources required for cleaning or disposal, thus presenting a route to reducing ultimate costs. The paper will examine the performance characteristics, filtration efficiency, flow verses differential pressure and cleanability of a self cleaning HEPA grade sintered metal filter element, together with data to prove the contention. (authors)

  13. Air-cleaning apparatus

    International Nuclear Information System (INIS)

    Howard, A.G.

    1981-01-01

    An air-cleaning, heat-exchange apparatus includes a main housing portion connected by means of an air inlet fan to the kitchen exhaust stack of a restaurant. The apparatus includes a plurality of heat exchangers through which a heat-absorptive fluid is circulated, simultaneously, by means of a suitable fluid pump. These heat exchangers absorb heat from the hot exhaust gas, out of the exhaust stack of the restaurant, which flows over and through these heat exchangers and transfers this heat to the circulating fluid which communicates with remote heat exchangers. These remote heat exchangers further transfer this heat to a stream of air, such as that from a cold-air return duct for supplementing the conventional heating system of the restaurant. Due to the fact that such hot exhaust gas is heavily grease laden , grease will be deposited on virtually all internal surfaces of the apparatus which this exhaust gas contacts. Consequently, means are provided for spraying these contacted internal surfaces , as well as the hot exhaust gas itself, with a detergent solution in which the grease is soluble, thereby removing grease buildup from these internal surfaces

  14. Clean air in the Anthropocene.

    Science.gov (United States)

    Lelieveld, Jos

    2017-08-24

    In atmospheric chemistry, interactions between air pollution, the biosphere and human health, often through reaction mixtures from both natural and anthropogenic sources, are of growing interest. Massive pollution emissions in the Anthropocene have transformed atmospheric composition to the extent that biogeochemical cycles, air quality and climate have changed globally and partly profoundly. It is estimated that mortality attributable to outdoor air pollution amounts to 4.33 million individuals per year, associated with 123 million years of life lost. Worldwide, air pollution is the major environmental risk factor to human health, and strict air quality standards have the potential to strongly reduce morbidity and mortality. Preserving clean air should be considered a human right, and is fundamental to many sustainable development goals of the United Nations, such as good health, climate action, sustainable cities, clean energy, and protecting life on land and in the water. It would be appropriate to adopt "clean air" as a sustainable development goal.

  15. Containment air cleaning for LMFBRs

    International Nuclear Information System (INIS)

    Hilliard, R.K.; McCormack, J.D.; Owen, R.K.; Postma, A.K.

    1979-01-01

    A variety of air cleaning concepts was evaluated for potential use in future sodium-cooled breeder reactors. A 3-stage aqueous scrubber system was selected for large-scale demonstration testing under conditions similar to those postulated for containment venting and purging during reactor melt-through accidents. Two tests were performed in the Containment Systems Test Facility using a quench tank, a jet venturi scrubber and a high efficiency fibrous scrubber in series. The results of two tests with Na/sub 2/O/sub 2/ and NaOH aerosol and NaI vapor are presented showing >99.9% removal of Na/sub 2/O/sub 2/ and NaOH and >99.7% for NaI. 7 refs

  16. Clean Air and Water

    Centers for Disease Control (CDC) Podcasts

    The air we breathe and the water we drink are both vital components of our health. Nevertheless, bacteria, pollutants, and other contaminates can alter life-giving air and water into health-threatening hazards. Learn about how scientists at the Centers for Disease Control and Prevention work to protect the public from air and water-related health risks.

  17. Air cleaning using regenerative silica gel wheel

    DEFF Research Database (Denmark)

    Fang, Lei

    2011-01-01

    This paper discussed the necessity of indoor air cleaning and the state of the art information on gas-phase air cleaning technology. The performance and problems of oxidation and sorption air cleaning technology were summarized and analysed based on the literature studies. Eventually, based...... on an experimental study, a technology called clean air heat pump is proposed as a practical approach for indoor air cleaning....

  18. Clean Air and Water

    Centers for Disease Control (CDC) Podcasts

    2007-04-10

    The air we breathe and the water we drink are both vital components of our health. Nevertheless, bacteria, pollutants, and other contaminates can alter life-giving air and water into health-threatening hazards. Learn about how scientists at the Centers for Disease Control and Prevention work to protect the public from air and water-related health risks.  Created: 4/10/2007 by CDC National Center for Environmental Health.   Date Released: 4/13/2007.

  19. Air conditioning systems to clean radioactive air

    International Nuclear Information System (INIS)

    Ganz, G.

    1987-01-01

    The author reports a study by the Institutes fuer Klimatechnik and Umweltschutz Giessen that shows that air conditioning systems not only make the atmosphere more comfortable, they also extract dust particles. This cleaning action is also valid for radioactively contaminated air. (G.T.H./Auth.)

  20. Meeting the clean air demand

    International Nuclear Information System (INIS)

    Hocker, C.

    1991-01-01

    This article addresses the impacts to the emissions control industry and the future of small independent projects of the Clean Air Act. Topics discussed include technological and market niche of pollution control companies, risk reduction by owning and operating the emission control portion of the plant as a separate entity, the diversity of technologies, and legislative effects

  1. Electric utilities and clean air

    International Nuclear Information System (INIS)

    Evans, J.E.

    1991-01-01

    This paper reports that electricity has become essential to American life. Approximately 70 percent of the nation's electricity is produced by burning fossil fuels, with coal, the most abundant, domestically-available, extracted natural resource, providing over 55 percent of the total electricity consumed. Emissions resulting from the burning of fossil fuels are regulated by both the federal and state governments. In 1970, Congress passed the comprehensive Clean Air Act which established a national program to protect the nation's air quality. In 1977, additional strict regulations were passed, which mandated even more stringent emission controls for factories, power plants and auto emissions. Prior to passage of the Clean Air Act of 1990, utilities were required to adhere to three major types of clean air regulations: National Ambient Air Quality Standards (NAAQS), New Source Performance Standards (NSPS), and Prevention of Significant Deterioration (PSD) review. NAAQS established limits for the maximum concentration levels of specific air pollutants in the ambient atmosphere. For example, for an area to be in compliance with the NAAQS for sulfur dioxide (SO 2 ), its annual average SO 2 concentration must not exceed 0.03 ppm of SO 2 and a peak 24 hour level of 0.14 ppm of SO 2 must not be exceeded more than once per year

  2. Efficient methods of piping cleaning

    Directory of Open Access Journals (Sweden)

    Orlov Vladimir Aleksandrovich

    2014-01-01

    Full Text Available The article contains the analysis of the efficient methods of piping cleaning of water supply and sanitation systems. Special attention is paid to the ice cleaning method, in course of which biological foil and various mineral and organic deposits are removed due to the ice crust buildup on the inner surface of water supply and drainage pipes. These impurities are responsible for the deterioration of the organoleptic properties of the transported drinking water or narrowing cross-section of drainage pipes. The co-authors emphasize that the use of ice compared to other methods of pipe cleaning has a number of advantages due to the relative simplicity and cheapness of the process, economical efficiency and lack of environmental risk. The equipment for performing ice cleaning is presented, its technological options, terms of cleansing operations, as well as the volumes of disposed pollution per unit length of the water supply and drainage pipelines. It is noted that ice cleaning requires careful planning in the process of cooking ice and in the process of its supply in the pipe. There are specific requirements to its quality. In particular, when you clean drinking water system the ice applied should be hygienically clean and meet sanitary requirements.In pilot projects, in particular, quantitative and qualitative analysis of sediments adsorbed by ice is conducted, as well as temperature and the duration of the process. The degree of pollution of the pipeline was estimated by the volume of the remote sediment on 1 km of pipeline. Cleaning pipelines using ice can be considered one of the methods of trenchless technologies, being a significant alternative to traditional methods of cleaning the pipes. The method can be applied in urban pipeline systems of drinking water supply for the diameters of 100—600 mm, and also to diversion collectors. In the world today 450 km of pipelines are subject to ice cleaning method.Ice cleaning method is simple

  3. US-China Clean Energy Research Center on Building Energy Efficiency: Materials that Improve the Cost-Effectiveness of Air Barrier Systems

    Energy Technology Data Exchange (ETDEWEB)

    Hun, Diana E. [Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States)

    2016-12-01

    The US–China Clean Energy Research Center (CERC) was launched in 2009 by US Energy Secretary Steven Chu, Chinese Minister of Science and Technology Wan Gang, and Chinese National Energy Agency Administrator Zhang Guobao. This 5-year collaboration emerged from the fact that the United States and China are the world’s largest energy producers, energy consumers, and greenhouse gas emitters, and that their joint effort could have significant positive repercussions worldwide. CERC’s main goal is to develop and deploy clean energy technologies that will help both countries meet energy and climate challenges. Three consortia were established to address the most pressing energy-related research areas: Advanced Coal Technology, Clean Vehicles, and Building Energy Efficiency (BEE). The project discussed in this report was part of the CERC-BEE consortia; its objective was to lower energy use in buildings by developing and evaluating technologies that improve the cost-effectiveness of air barrier systems for building envelopes.

  4. Experimental study on air cleaning effect of clean air heat pump and its impact on ventilation requirement

    DEFF Research Database (Denmark)

    Fang, Lei; Sheng, Ying; Nie, Jinzhe

    2017-01-01

    This study investigated air purification effect of a Clean-Air Heat Pump (CAHP) which combined a desiccant wheel with a heat pump for both air cleaning and HVAC of buildings. The experiment was conducted in a field lab at four different outdoor air supply rates with and without air cleaning by CAHP....... Both sensory assessments of perceived air quality and chemical measurements of TVOC concentrations were conducted for evaluating the air cleaning performance of the CAHP. The results of experiment showed that running the CAHP improved significantly perceived air quality. At 2 L/s per person of outdoor...... air supply rate with operating the CAHP, the air quality was equivalent to the value at the higher outdoor air supply rate of 10 L/s per person without running CAHP. The TVOC measurements observed over 92% of efficiency on removal of indoor air VOCs and no VOCs accumulation on the desiccant wheel...

  5. Clean Air Act. Revision 5

    Energy Technology Data Exchange (ETDEWEB)

    1994-02-15

    This Reference Book contains a current copy of the Clean Air Act, as amended, and those regulations that implement the statute and appear to be most relevant to DOE activities. The document is provided to DOE and contractor staff for informational purposes only and should not be interpreted as legal guidance. This Reference Book has been completely revised and is current through February 15, 1994.

  6. Clean air strategy for Alberta: Background project reports

    International Nuclear Information System (INIS)

    1991-06-01

    As a background to the development of a clean air strategy for Alberta, reports are presented which cover the definition of what clean air is, the applicability of full cost accounting to this strategy, market-based approaches to managing Alberta air emissions, gas and electric utility incentives programs for energy efficiency, energy efficiency legislation in Alberta and other jurisdictions, initiatives which address emissions reduction in the transportation sector, coordination of science and technology relevant to clean air issues, and initiatives in energy and environmental education

  7. Pollution Law - Clean Air Act

    International Nuclear Information System (INIS)

    Schmitt Glaeser, W.; Meins, J.W.

    1982-01-01

    This volume deals with how the living space air is kept clean by means of the pollution law, focussing on the documentation of central problems of pollution law by means of selected articles and court decisions. The literature and jurisdiction available on this sector of which we can hardly keep track makes such a documentation look useful and necessary. It will make working easier for those who do not have direct access to large libraries. The only intention of the guide for the pollution law which preceeds the documentation is to outline basic problems. It is intended to provide basic information in this complex field of law. At the same time, it also constitutes a 'guide' for the documentation: By naming the documentation number in the margin of the respective passage reference is made to the documented publications which deal with the legal issues considered. Using this guide, the documentation can be easily tapped. (orig.) [de

  8. An experimental evaluation on air purification performance of Clean-Air Heat Pump (CAHP) air cleaner

    DEFF Research Database (Denmark)

    Sheng, Ying; Fang, Lei; Sun, Yuexia

    2018-01-01

    was 96.8%, which indicated that the most of gaseous pollutants were not accumulated in the CAHP. The regeneration temperature for the wheel could affect the air purification performance of CAHP. At 70 °C of regeneration temperature, the air-cleaning efficiency reached 96.7%. Up to 70% of the outdoor air......The escalation of energy consumption in buildings and heightened concerns about acceptable indoor air quality stimulate interest in the usage of air cleaner as an adjunct for indoor environmental conditioning. A regenerative desiccant wheel integrated into a ventilation system termed Clean-Air Heat...... Pump (CAHP) can improve the air quality during the process of dehumidification without using additional energy. An experimental study in a field lab was performed to investigate the air cleaning performance of CAHP. Photoacoustic gas analyzer-INNOVA was used to characterize chemical removal of indoor...

  9. Allegheny County Clean Indoor Air Act Exemptions

    Data.gov (United States)

    Allegheny County / City of Pittsburgh / Western PA Regional Data Center — List and location of all the businesses and social clubs who have received an exemption from the Pennsylvania Clean Indoor Air Act. “The Clean Indoor Air Act, Act...

  10. Nuclear air cleaning activities in Germany

    International Nuclear Information System (INIS)

    Wilhelm, J.

    1991-01-01

    The discussion is limited to nuclear air cleaning activities in the Federal Republic of Germany. Work is underway on containment venting with regard to filtration based on a combination of stainless steel roughing and fine filters with a decontamination factor similar to or better than that achieved with high-efficiency particulate air filters. The main point of interest is the development of relatively small filter units that can be located inside the containment. The concept of a new design for double containment having annular rooms between the steel containment and the concrete containment is discussed. Work related to the dismantling of decommissioned reactors and limited research for fuel reprocessing facilities are also noted

  11. Can a Clean-Air Heat Pump (CAHP) maintain air purification capability when using polluted air for regeneration?

    DEFF Research Database (Denmark)

    Sheng, Ying; Fang, Lei

    2018-01-01

    Clean Air Heat Pump (CAHP) was one type of rotary desiccant cooling system which combined a silica gel rotor with a heat pump to achieve air cleaning, dehumidifying and cooling in buildings. Using exhaust air from the conditioned room for regeneration of the silica gel rotor might have an advantage...... on reducing the regeneration air temperature and further improving the energy performance of the CAHP. However, the exhaust air carried a lot of indoor air pollutants. Whether using exhaust air for the regeneration of the silica gel rotor had an impact on the air cleaning performance of the CAHP...... was experimentally studied. The results showed that using the air contained acetone or toluene for regeneration reduced the pollutants removal capability of CAHP with a reduction of approx. 10% in air cleaning efficiency. The energy performance of the CAHP when using exhaust air for regeneration was also evaluated...

  12. Clean Air Markets - Monitoring Surface Water Chemistry

    Science.gov (United States)

    Learn about how EPA uses Long Term Monitoring (LTM) and Temporily Integrated Monitoring of Ecosystems (TIME) to track the effect of the Clean Air Act Amendments on acidity of surface waters in the eastern U.S.

  13. Clean Air Markets - Allowances Query Wizard

    Data.gov (United States)

    U.S. Environmental Protection Agency — The Allowances Query Wizard is part of a suite of Clean Air Markets-related tools that are accessible at http://camddataandmaps.epa.gov/gdm/index.cfm. The Allowances...

  14. Clean Air Markets - Compliance Query Wizard

    Data.gov (United States)

    U.S. Environmental Protection Agency — The Compliance Query Wizard is part of a suite of Clean Air Markets-related tools that are accessible at http://ampd.epa.gov/ampd/. The Compliance module provides...

  15. Clean Air Markets - Quick Facts and Trends

    Data.gov (United States)

    U.S. Environmental Protection Agency — The Quick Facts and Trends module is part of a suite of Clean Air Markets-related tools that are accessible at http://camddataandmaps.epa.gov/gdm/index.cfm. The...

  16. Odor and the Clean Air Act

    International Nuclear Information System (INIS)

    Morse, H.N.

    1993-01-01

    The case described in this paper involves the interpretation of language contained in the Texas Clean Air Act Texas Health and Safety Code Ann. Sections 382.001-382.141. The State of Texas, on behalf of the Texas Air Control Board, brought suit in the District Court of Erath County, Texas against the F/R Cattle Company, Inc., alleging that, because of odors emanating from the company's cattle feeding facility, the company was violating the Clean Air Act. The Board is granted the power and duty to administer the Clean Air Act and is directed to accomplish the purposes of the Act through the control of air contaminants by all practical and economically feasible methods. Described here is the evidence presented at and proceedings of the trial

  17. Canadian government motivators for clean air vehicles

    Energy Technology Data Exchange (ETDEWEB)

    Forster, J. [Transport Canada, Ottawa, ON (Canada)

    1999-07-01

    A slide presentation is included which covers: why support clean air vehicles, key areas of action including climate change and cleaner air and conclusions. Reasons for supporting clean air vehicles include: the environment is not a top of mind issue for Canadians but is a core issue, transportation contributes significantly to environmental problems, e.g., 40-50% of smog emissions, and 27% of greenhouse gas emissions, and clean air vehicles are part of the solution. The first area of action is that of climate change, and includes as elements: the Kyoto Protocol, First Ministers, and 15 Issue Tables. The second area of action is clean air. Action on climate change can have ancillary benefits, e.g., reduction in smog-related emissions. Government is taking action to address smog in concert with the provinces in the Federal Smog Management Plan. A key element in the Plan is that of ensuring that appropriate emissions standards are in place. Transport Canada supports clean air vehicles through research conducted at the Transporation Research and Development Centre. Further Transport Canada involvement includes: partnership in Montreal 2000, demonstration/conversion testing, development of advanced EV systems, and membership in the CEVEQ. In the longer term, new technologies hold the key to addressing many environmental challenges. This is particularly true with respect to climate change and air quality, and new vehicle technologies will play an important role.

  18. New Air Cleaning Strategies for Reduced Commercial Building Ventilation Energy

    Energy Technology Data Exchange (ETDEWEB)

    Sidheswaran, Meera; Destaillats, Hugo; Sullivan, Douglas P.; Fisk, William J.

    2010-10-27

    Approximately ten percent of the energy consumed in U.S. commercial buildings is used by HVAC systems to condition outdoor ventilation air. Reducing ventilation rates would be a simple and broadly-applicable energy retrofit option, if practical counter measures were available that maintained acceptable concentrations of indoor-generated air pollutants. The two general categories of countermeasures are: 1) indoor pollutant source control, and 2) air cleaning. Although pollutant source control should be used to the degree possible, source control is complicated by the large number and changing nature of indoor pollutant sources. Particle air cleaning is already routinely applied in commercial buildings. Previous calculations indicate that particle filtration consumes only 10percent to 25percent of the energy that would otherwise be required to achieve an equivalent amount of particle removal with ventilation. If cost-effective air cleaning technologies for volatile organic compounds (VOCs) were also available, outdoor air ventilation rates could be reduced substantially and broadly in the commercial building stock to save energy. The research carried out in this project focuses on developing novel VOC air cleaning technologies needed to enable energy-saving reductions in ventilation rates. The minimum required VOC removal efficiency to counteract a 50percent reduction in ventilation rate for air cleaning systems installed in the HVAC supply airstream is modest (generally 20percent or less).

  19. Ductless personalized ventilation with local air cleaning

    DEFF Research Database (Denmark)

    Dalewski, Mariusz; Vesely, Michal; Melikov, Arsen Krikor

    2012-01-01

    An experiment with 28 human subjects was performed to examine effects of using a local air cleaning device combined with ductless personalized ventilation (DPV) on perceived air quality. Experiments were performed in a test room with displacement ventilation. The DPV at one of two desks was equip......An experiment with 28 human subjects was performed to examine effects of using a local air cleaning device combined with ductless personalized ventilation (DPV) on perceived air quality. Experiments were performed in a test room with displacement ventilation. The DPV at one of two desks...... was equipped with an activated carbon filter installed at the air intake, while the DPV at the second desk was without such a filter. The air temperature in the occupied zone (1.1 m above the floor) was 29 °C. The pollution load in the room was simulated by PVC floor covering. The subjects assessed...

  20. Source terms in relation to air cleaning

    International Nuclear Information System (INIS)

    Bernero, R.M.

    1985-01-01

    There are two sets of source terms for consideration in air cleaning, those for routine releases and those for accident releases. With about 1000 reactor years of commercial operating experience in the US done, there is an excellent data base for routine and expected transient releases. Specifications for air cleaning can be based on this body of experience with confidence. Specifications for air cleaning in accident situations is another matter. Recent investigations of severe accident behavior are offering a new basis for source terms and air cleaning specifications. Reports by many experts in the field describe an accident environment notably different from previous models. It is an atmosphere heavy with aerosols, both radioactive and inert. Temperatures are sometimes very high; radioiodine is typically in the form of cesium iodide aerosol particles; other nuclides, such as tellurium, are also important aerosols. Some of the present air cleaning requirements may be very important in light of these new accident behavior models. Others may be wasteful or even counterproductive. The use of the new data on accident behavior models to reevaluate requirements promptly is discussed

  1. Continuing challenges in nuclear air cleaning

    International Nuclear Information System (INIS)

    Moeller, D.W.

    1976-01-01

    The safe operation of nuclear facilities is heavily dependent upon the adequate performance of air cleaning systems. Although many problems have been solved, new questions and new challenges continue to arise. These are well illustrated by weaknesses in air cleaning and ventilating systems revealed by the Browns Ferry fire, and the need to develop additional data on the reliability of such systems, particularly under emergency conditions, as revealed by the Reactor Safety Study. Assessments of the degree to which engineered safety features can compensate for deficiencies in nuclear power plant sites continue to challenge those involved in risk/benefit evaluations. Additional challenges are being generated by the air cleaning requirements associated with the commercial development of the liquid metal fast breeder reactor

  2. New air cleaning technology in Japan

    International Nuclear Information System (INIS)

    Yoshida, Y.; Kitani, S.; Matsui, H.; Ikezawa, Y.

    1981-01-01

    Application of the new techniques and improvements in air cleaning systems have been made to reduce release of radioactive materials from nuclear facilities based on the ALARA concept. For example, the reduction of release of radioactive gaseous effluents has been made by installation of a charcoal gas hold-up system and a clean steam supply system for a turbine gland seal in a BWR and of a gas decay tank system in a PWR. In connection with the effort for reduction of releases in plants, research and development on air cleaning technology have also been made. Some activities mentioned in the present paper are: removal of particulates, airborne radioiodine, noble gases and tritium; penetration characteristics of submicron DOP aerosol for HEPA filters; radioiodine removal from air exhausts; and operational performance of the incineration plants using ceramic filters

  3. Sonochemical cleaning efficiencies in dental instruments

    Science.gov (United States)

    Tiong, T. Joyce; Walmsley, A. Damien; Price, Gareth J.

    2012-05-01

    Ultrasound has been widely used for cleaning purposes in a variety of situations, including in dental practice. Cleaning is achieved through a combination of acoustically driven streaming effects and sonochemical effects arising from the production of inertial cavitation in a liquid. In our work, various dental instruments used for endodontic (root canal) treatment have been evaluated for their efficiency in producing sonochemical effects in an in-vitro cleaning environment. The areas where cavitation was produced were mapped by monitoring chemiluminescence from luminol solutions and this was correlated with their cleaning efficiencies - assessed by the ability to bleach a dye, to form an emulsion by mixing immiscible components and also to remove ink from a glass surface. The results showed good correlation (Pearson's coefficient > 0.9) between the cavitation and cleaning efficiencies, suggesting that the former plays an important role in cleaning. The methods developed and the results will be beneficial in endodontics research in order to optimise future root canal instruments and treatments.

  4. Electricity competition and clean air

    International Nuclear Information System (INIS)

    Gibbons, J.; Bjorkquist, S.

    1998-04-01

    The government of Ontario plans to establish a competitive market for the generation and sale of electricity by the year 2000, at which time Ontario Hydro will lose its monopoly. The government's rationale for moving to a competitive electricity market and the details of why this move could lead to a significant increase in air pollution was discussed. An overview of the health and environmental effects of electricity related air pollution was presented and the current national and provincial air quality objectives were outlined. The government of Ontario has promised that in implementing a competitive electricity market it will ensure that the province's environmental protection record is maintained and improved. It was suggested that in order to fulfill this commitment, new environmental regulations should be established to ensure that Ontario's total electricity-related emissions will decline when competition begins. Currently, air pollution from coal-fired power generating stations causes some of Ontario's most challenging health and environmental problems. Coal-fired generation stations are also major contributors to the build-up of greenhouse gases in the atmosphere. 74 refs., 2 tabs., 2 figs

  5. Household air pollution, health, and climate change: cleaning the air

    Science.gov (United States)

    Goldemberg, Jose; Martinez-Gomez, Javier; Sagar, Ambuj; Smith, Kirk R.

    2018-03-01

    Air pollution from the use of solid household fuels is now recognized to be a major health risk in developing countries. Accordingly, there has been some shift in development thinking and investment from previous efforts, which has focused only on improving the efficiency of household fuel use, to those that focus on reducing exposure to the air pollution that leads to health impact. Unfortunately, however, this is occurring just as the climate agenda has come to dominate much of the discourse and action on international sustainable development. Thus, instead of optimizing approaches that centrally focus on the large health impact, the household energy agenda has been hampered by the constraints imposed by a narrow definition of sustainability—one primarily driven by the desire to mitigate greenhouse emissions by relying on renewable biomass fueling so-called improved cookstoves. In reality, however, solid biomass is extremely difficult to burn sufficiently cleanly in household stoves to reach health goals. In comparison to the international development community, however, some large countries, notably Brazil historically and more recently, India have substantially expanded the use of liquefied petroleum gas (LPG) in their household energy mix, using their own resources, having a major impact on their national energy picture. The net climate impact of such approaches compared to current biomass stoves is minimal or non-existent, and the social and health benefits are, in contrast, potentially great. LPG can be seen as a transition fuel for clean household energy, with induction stoves powered by renewables as the holy grail (an approach already being adopted by Ecuador as also discussed here). The enormous human and social benefits of clean energy, rather than climate concerns, should dominate the household energy access agenda today.

  6. Testing of nuclear air-cleaning systems

    International Nuclear Information System (INIS)

    Anon.

    1975-01-01

    A standard is presented which describes methods for field-testing nuclear power plant air cleaning systems. Included are specifications for visual inspection; duct and housing leak test; mounting frame pressure leak test; airflow capacity, distribution, and residence time tests; air-aerosol mixing uniformity test; in place leak test of HEPA filter banks; multiple sampling technique; in-place leak test of adsorber stage; laboratory testing of adsorbent; and duct heater performance test

  7. Senate begins clean air legislation debate

    International Nuclear Information System (INIS)

    Yates, M.

    1990-01-01

    This article reports on Senate debate on the Clean Air Act Amendments of 1989. Topics include acid rain provisions, administration objections, costs of the bill including disparity of costs in different regions and cost-sharing proposals, and the effects the current energy policy will have on the bill. Presidential, Senate, and subcommittee views on the bill are presented

  8. CARBON ADSORPTION FOR INDOOR AIR CLEANING

    Science.gov (United States)

    The paper discusses the use of carbon adsorption for indoor air cleaning, focusing on the removal of volatile organic compounds (VOCs) using granular activated carbon (GAC). It addresses GAC performance in two directions. Initially, it presents performance measurements for GAC at...

  9. Clean air: time for responsible reform

    International Nuclear Information System (INIS)

    Hart, G.

    1982-01-01

    An opinion concerning the renewal of the Clean Air Act by Gary Hart, the U.S. Senator from Colorado, is presented. Hart discusses how effective programs covered by the act can be preserved, how burdensome requirements can be streamlined, and how coverage can be expanded to unforeseen problems

  10. Ensuring clean air: Developing a clean air strategy for British Columbia

    International Nuclear Information System (INIS)

    1992-04-01

    In 1992, a clean air strategy will be developed to incorporate views of British Columbians on ways to meet goals related to air quality. A discussion paper is presented to provide information to those interested in participation in developing this strategy. The paper gives information on air quality issues important to the province, including local air quality, urban smog, ozone layer depletion, and global climate change. The views and concerns expressed by stakeholders who attended the Clean Air Conference in 1991 are summarized. The process used to develop the clean air strategy is outlined and some outcomes to be anticipated from the strategy are suggested, including policies and priorities for action to ensure clean air. Air pollutants of concern are total reduced sulfur, mainly from pulp mills and gas processing plants; smoke from wood burning; sulfur dioxide from pulp mills and gas plants; hydrogen fluoride from aluminum smelting; ground-level ozone in urban areas; and acid rain. Elements of a clean air strategy include a smoke management policy, management strategies for greenhouse gases and ozone smog, ozone layer protection measures, regional air quality management plans, and long-term planning efforts in energy use, transportation modes, community design, and land use. 12 refs., 14 figs., 2 tabs

  11. Controlling the cost of clean air - A new clean coal technology

    International Nuclear Information System (INIS)

    Kindig, J.K.; Godfrey, R.L.

    1991-01-01

    This article presents the authors' alternative to expensive coal combustion products clean-up by cleaning the coal, removing the sulfur, before combustion. Topics discussed include sulfur in coal and the coal cleaning process, the nature of a new coal cleaning technology, the impact on Clean Air Act compliance, and the economics of the new technology

  12. Benefits and Costs of the Clean Air Act

    Science.gov (United States)

    Congress added to the 1990 Clean Air Act Amendments a requirement under section 812 that EPA conduct periodic, scientifically reviewed studies to assess the benefits and the costs of the entire Clean Air Act.

  13. Significant OH production under surface cleaning and air cleaning conditions: Impact on indoor air quality.

    Science.gov (United States)

    Carslaw, N; Fletcher, L; Heard, D; Ingham, T; Walker, H

    2017-11-01

    We report measurements of hydroxyl (OH) and hydroperoxy (HO 2 ) radicals made by laser-induced fluorescence spectroscopy in a computer classroom (i) in the absence of indoor activities (ii) during desk cleaning with a limonene-containing cleaner (iii) during operation of a commercially available "air cleaning" device. In the unmanipulated environment, the one-minute averaged OH concentration remained close to or below the limit of detection (6.5×10 5  molecule cm -3 ), whilst that of HO 2 was 1.3×10 7  molecule cm -3 . These concentrations increased to ~4×10 6 and 4×10 8  molecule cm -3 , respectively during desk cleaning. During operation of the air cleaning device, OH and HO 2 concentrations reached ~2×10 7 and ~6×10 8  molecule cm -3 respectively. The potential of these OH concentrations to initiate chemical processing is explored using a detailed chemical model for indoor air (the INDCM). The model can reproduce the measured OH and HO 2 concentrations to within 50% and often within a few % and demonstrates that the resulting secondary chemistry varies with the cleaning activity. Whilst terpene reaction products dominate the product composition following surface cleaning, those from aromatics and other VOCs are much more important during the use of the air cleaning device. © 2017 John Wiley & Sons A/S. Published by John Wiley & Sons Ltd.

  14. 14 CFR 1260.34 - Clean air and water.

    Science.gov (United States)

    2010-01-01

    ... 14 Aeronautics and Space 5 2010-01-01 2010-01-01 false Clean air and water. 1260.34 Section 1260... AGREEMENTS General Provisions § 1260.34 Clean air and water. Clean Air and Water October 2000 (Applicable... the Clean Air Act (42 U.S.C. 1857c-8(c)(1) or the Federal Water Pollution Control Act (33 U.S.C. 1319...

  15. The 1990 Clean Air Act amendments

    International Nuclear Information System (INIS)

    Torrens, I.M.; Cichanowicz, J.E.; Platt, J.B.

    1992-01-01

    The impacts of the 1990 Clean Air Act Amendments on utilities are substantial, presenting a host of new technical challenges, introducing new business risks, changing costs of electric generation, creating new winners and losers, and calling for new organizational responses capable of dealing with the complexity and short time for decisions. The magnitude of costs and unknowns puts clean air compliance into a new league of energy issues, in which the decisions utilities must make are not simply technological or engineering economic choices, but rather are very complex business decisions with numerous stakeholders, pitfalls, and opportunities. This paper summarizes the key regulatory requirements of the CAAA, outlines compliance options and questions facing the utility industry, and addresses how utility strategic business decisions could be affected

  16. The Clean Air Act Amendments of 1990

    International Nuclear Information System (INIS)

    Mosby, R.C.

    1991-01-01

    The natural gas liquids industry and specifically the gas processing business has not been rosy the last several years. processors have been faced with low NGL prices, high inventories and more regulations which have forced product margins to all time lows and have resulted in plant closings, mergers and a determined search for those processors that are left for ways to make ends meet until times get better. Whether a barometer for the future or merely a fluke in the economy, things got better in 1990. Last year represented a change for the positive in all the indicators characterizing the gas processing business. An early winter in 1989, propane distribution problems, overall increases in petrochemical demand for NGLs and the fear brought on by events in Kuwait all contributed to changes in the marketplace. For the gas processor, these events combined with relatively low natural gas prices to produce wider processing margins and a degree of prosperity. The biggest regulatory event in 1990 however was without a doubt the Clean Air Act Amendments. These sweeping changes to the 1970 Clean Air Act promise to affect the economy and public health well into the next century. The purpose of this paper is to examine first the major provisions of the Clean Air Act Amendments of 1990 and then relate those anticipated changes to the gas processing industry. As will be examined later, the Amendments will create both threats and opportunities for gas processors

  17. Sizing of air cleaning systems for access to nuclear plant spaces

    International Nuclear Information System (INIS)

    Estreich, P.J.

    A mathematical basis is developed to provide the practicing engineer with a method for sizing air-cleaning systems for nuclear facilities. In particular, general formulas are provided to relate cleaning and contamination dynamics of an enclosure such that safe conditions are obtained when working crews enter. Included in these considerations is the sizing of an air-cleaning system to provide rapid decontamination of airborne radioactivity. Multiple-nuclide contamination sources, leak rate, direct radiation, contaminant mixing efficiency, filter efficiencies, air-cleaning-system operational modes, and criteria for maximum permissible concentrations are integrated into the procedure. (author)

  18. Air and gas cleaning technology for nuclear applications

    International Nuclear Information System (INIS)

    First, M.W.

    1986-01-01

    All large-scale uses of radioactive materials require rigid control of off-gases and generated aerosols. Nuclear air and gas cleaning technology has answered the need from the days of the Manhattan Project to the present with a variety of devices. The one with the longest and most noteworthy service is the HEPA (high efficiency particulate air) filter that originally was referred to as an absolute filter in recognition of its extraordinary particle retention characteristics. Activated-charcoal adsorbers have been employed worldwide for retention of volatile radioiodine in molecular and combined forms and, less frequently, for retention of radioactive noble gases. HEPA filters and activated -charcoal adsorbers are often used with auxiliary devices that serve to extend their effective service life or significantly improve collection efficiency under unfavorable operating conditions. Use of both air cleaning devices and their auxiliaries figure prominently in atomic energy, disposal of high- and low-level nuclear wastes, and in the production of fissile materials. The peaceful uses of nuclear energy would be impossible without these, or equivalent, air- and gas-cleaning devices

  19. Clean Air Act amendments of 1991: Detailed summary of titles

    International Nuclear Information System (INIS)

    1990-01-01

    ;Contents: Provisions for Attainment and Maintenance of National Ambient Air Quality Standards; Provisions Relating to Mobile Sources; Hazardous Air Pollutants; Acid Deposition Control; Permits; Stratospheric Ozone Protection; Provisions Relating to Enforcement; Miscellaneous Provisions; Clean Air Research; Disadvantaged Business Concerns; Clean Air Employment Transition Assistance

  20. Clean air strategy for Alberta: Report to the ministers

    International Nuclear Information System (INIS)

    1991-11-01

    As a response to continuing discussions on the impact of fossil fuels on global warming, acid deposition, and smog, a clean air strategy consultation program was announced by Alberta's Ministers of Energy and Environment to encourage public discussion on air emissions resulting from the production and use of energy. The consultation program had three objectives: to help identify and clarify the most important issues associated with energy production and use which need to be addressed in developing a clean air strategy; to outline practical and achievable actions which can be taken to reduce emissions; and to develop program and policy recommendations to the provincial government. The consultation program included workshops and regional sessions, as well as background research. The discussions, findings, and conclusions from the program are summarized. Several air quality management challenges were identified, including the need for a more comprehensive system for managing air quality; the priority of local air quality issues and problems; the need to address cumulative regional emissions and impacts; and scientific and economic uncertainties. A number of goals have been developed to address these challenges, such as implementation of a comprehensive air quality management system, identification of cost-effective energy conservation and efficiency opportunities, development of innovative and targeted solutions to manage cumulative emissions, and improvement of the gathering and application of scientific and technical knowledge regarding atmospheric processes and effects. A glossary of terms is included. 12 figs., 17 tabs

  1. Experimental study on energy performance of clean air heat pump

    DEFF Research Database (Denmark)

    Fang, Lei; Nie, Jinzhe; Olesen, Bjarne W.

    2014-01-01

    An innovative clean air heat pump (CAHP) was designed and developed based on the air purification capacity of regenerative silica gel rotor. The clean air heat pump integrated air purification, dehumidification and cooling in one unit. A prototype of the clean air heat pump was developed...... to investigate its energy performance. Energy consumption of the prototype of CAHP was measured in laboratory at different climate conditions including mild-cold, mildhot and extremely hot and humid climates. The energy saving potential of the clean air heat pump compared to a conventional ventilation and air......-conditioning system was calculated. The experimental results showed that the clean air heat pump saved substantial amount of energy compared to the conventional system. For example, the CAHP can save up to 59% of electricity in Copenhagen, up to 40% of electricity in Milan and up to 30% of electricity in Colombo...

  2. Ceramic membrane defouling (cleaning) by air Nano Bubbles.

    Science.gov (United States)

    Ghadimkhani, Aliasghar; Zhang, Wen; Marhaba, Taha

    2016-03-01

    Ceramic membranes are among the most promising technologies for membrane applications, owing to their excellent resistance to mechanical, chemical, and thermal stresses. However, membrane fouling is still an issue that hampers the applications at large scales. Air Nano Bubbles (NBs), due to high mass transfer efficiency, could potentially prevent fouling of ceramic membrane filtration processes. In this study, bench and pilot scale ceramic membrane filtration was performed with air NBs to resist fouling. To simulate fouling, humic acid, as an organic foulant, was applied to the membrane flat sheet surface. Complete membrane clogging was achieved in less than 6 h. Membrane defouling (cleaning) was performed by directly feeding of air NBs to the membrane cells. The surface of the ceramic membrane was superbly cleaned by air NBs, as revealed by atomic force microscope (AFM) images before and after the treatment. The permeate flux recovered to its initial level (e.g., 26.7 × 10(-9) m(3)/m(2)/s at applied pressure of 275.8 kPa), which indicated that NBs successfully unclogged the pores of the membrane. The integrated ceramic membrane and air NBs system holds potential as an innovative sustainable technology. Copyright © 2015 Elsevier Ltd. All rights reserved.

  3. Clean Air Act compliance issues/panel

    International Nuclear Information System (INIS)

    Anon.

    1992-01-01

    This morning, four panelists will discuss the birth of the free market allowance trading system, how it was formed, when it was formed, how it was sold, how allowance trading has worked, how it is expected to work, and how utilities are planning based on allowance trading. We will also hear from a utility commissioner who will make some of the final decisions on cost recovery. So we will have various perspectives today on allowance trading. Many of you are here to learn more about how to comply with the Clean Air Act Amendments of 1990. Allowance trading is the cornerstone of the entire Title 4, the acid deposition title of the amendments, in which SO 2 emission allowances are a tradeable right. Following the four presentations, we will entertain questions to the four participants from the audience

  4. Revised Clean Air Act - Consequent enforcement necessary

    International Nuclear Information System (INIS)

    Keel, A.

    2008-01-01

    This article discusses the stipulations of the Swiss Clean Air Act regarding wood-fired combustion systems. In particular, the regulations on fine-dust emissions from wood-fired systems are discussed and its influence on the market for wood-fired heating systems is examined. Conformity statements can be issued for heating systems with a power of less than 70 kW that are tested to meet EN standards by accredited testing facilities. The history of the Swiss Association for Wood Energy and its efforts to introduce quality labels in this area of business are discussed. The situation regarding equipment with a power of less than 70 kW is addressed, as are large-scale wood-fired furnaces with ratings up to over 1,000 kW.

  5. New Jersey: Clean Air Communities (A Former EPA CARE Project)

    Science.gov (United States)

    Clean Air Communities (CAC) is the recipient of a Level II CARE cooperative agreement to implement recommendations by the state’s Environmental Justice Task Force and the Air Toxics Pilot Project to reduce environmental risks.

  6. New Clean Air Act complicates power plant operation, design

    International Nuclear Information System (INIS)

    Smock, R.W.

    1991-01-01

    In November the president signed into law the new Clean Air Act, ushering in a new era in the power generation industry. This paper reviews the six important sections of the Clean Air Act and their impact on power plant operation and design

  7. 17th DOE nuclear air cleaning conference: proceedings. Volume 2

    International Nuclear Information System (INIS)

    First, M.W.

    1983-02-01

    Volume 2 contains papers presented at the following sessions: adsorption; noble gas treatment; personnel education and training; filtration and filter testing; measurement and instrumentation; air cleaning equipment response to accident related stress; containment venting air cleaning; and an open end session. Twenty-eight papers were indexed separately for inclusion in the Energy Data Base. Ten papers had been entered earlier

  8. Air-cleaning systems for sodium-fire-aerosol control

    International Nuclear Information System (INIS)

    Hilliard, R.K.; Muhlestein, L.D.

    1982-05-01

    A development program has been carried out at the Hanford Engineering Development Laboratory (HEDL) with the purpose of developing and proof testing air cleaning components and systems for use under severe sodium fire conditions, including those involving high levels of radioactivity. The air cleaning components tested can be classified as either dry filters or aqueous scrubbers. Test results are presented

  9. A brief history of the air cleaning conferences

    International Nuclear Information System (INIS)

    First, M.W.

    1995-01-01

    I have been asked to prepare a history of the air cleaning conferences. Undertaking such a task is, of course, a wonderful opportunity for reminiscences and a chance to retell old war stories. I must admit that it has taken much longer than I anticipated because I found myself so completely engrossed rereading the old records that time seemed to stop, although the hours passed. But a history of the nuclear air cleaning conferences means more than a stroll down memory lane. The 23 recorded air cleaning conference proceedings reflect an important aspect of the history of major nuclear developments, both military and civilian, because engineered safety features designed to prevent dispersion of radioactive products to the environment have always been a necessity for progress in this field. For this reason, I hope the history of the nuclear air cleaning conferences will not only be enjoyable, but also have meaning for young people entering this field. The air cleaning conferences were an outgrowth of the operations of the U.S. Atomic Energy Commission's (AEC) Stack Gas Working Group established in 1948 to review air cleaning operations at AEC installations. AEC's Division of Engineering sponsored and funded air cleaning research and development at Harvard University's School of Public Health, beginning about the same time. In addition to research and development, the Harvard contract called for consulting and educational services. The latter provided the opportunity for meetings devoted to information on air cleaning that could be applied to ongoing and anticipated nuclear operations

  10. 17th DOE nuclear air cleaning conference: proceedings. Volume 2

    Energy Technology Data Exchange (ETDEWEB)

    First, M.W. (ed.)

    1983-02-01

    Volume 2 contains papers presented at the following sessions: adsorption; noble gas treatment; personnel education and training; filtration and filter testing; measurement and instrumentation; air cleaning equipment response to accident related stress; containment venting air cleaning; and an open end session. Twenty-eight papers were indexed separately for inclusion in the Energy Data Base. Ten papers had been entered earlier.

  11. New Air Cleaning Strategies for Reduced Commercial Building Ventilation Energy ? FY11 Final Report

    Energy Technology Data Exchange (ETDEWEB)

    Sidheswaran, Meera; Destaillats, Hugo; Cohn, Sebastian; Sullivan, Douglas P.; Fisk, William J.

    2011-10-31

    The research carried out in this project focuses on developing novel volatile organic compounds (VOCs) air cleaning technologies needed to enable energy-saving reductions in ventilation rates. we targeted a VOC air cleaning system that could enable a 50% reduction in ventilation rates. In a typical commercial HVAC system that provides a mixture of recirculated and outdoor air, a VOC air cleaner in the supply airstream must have a 15% to 20% VOC removal efficiency to counteract a 50% reduction in outdoor air supply.

  12. Comparison between polluted and clean air masses over Lake Michigan

    International Nuclear Information System (INIS)

    Alkezweeny, A.J.; Laulainen, N.S.

    1981-01-01

    Clean and polluted air masses, advected over Lake Michigan, were studied using instrumental aircraft during the summers of 1976 and 1978. The results show that regardless of the degree of pollution, the particle size distribution is bimodal. The concentrations of sulfate, nitrate and trace metals in a clean air mass are more than an order of magnitude lower than those in polluted air masses. Furthermore, these concentrations are comparable with those measured in remote areas of the world. In clean air the ratio of the total light scattering to Rayleigh scattering is very close to one, indicating very low concentrations of particulates in the optically active size classes

  13. Air cleaning issues with contaminated sites

    Energy Technology Data Exchange (ETDEWEB)

    Bellamy, R.R. [Nuclear Regulatory Commission, King of Prussia, PA (United States)

    1997-08-01

    The US Nuclear Regulatory Commission has developed a list of contaminated sites that warrant special USNRC attention because they pose unique or complex decommissioning issues. This list of radiologically contaminated sites is termed the Site Decommissioning Management Plan (SDMP), and was first issued in 1990. A site is placed on the SDMP list if it has; (1) Problems with the viability of the responsible organization (e.g., the licensee for the site is unable or unwilling to pay for the decommissioning); (2) Large amounts of soil contamination or unused settling ponds or burial grounds that may make the waste difficult to dispose of; (3) The long-term presence of contaminated, unused buildings; (4) A previously terminated license; or (5) Contaminated or potential contamination of the ground water from on-site wastes. In deciding whether to add a site to the SDMP list, the NRC also considers the projected length of time for decommissioning and the willingness of the responsible organization to complete the decommissioning in a timely manner. Since the list was established, 9 sites have been removed from the list, and the current SDMP list contains 47 sites in 11 states. The USNRC annually publishes NUREG-1444, {open_quotes}Site Decommissioning Management Plan{close_quotes}, which updates the status of each site. This paper will discuss the philosophical goals of the SDMP, then will concentrate on the regulatory requirements associated with air cleaning issues at the SDMP sites during characterization and remediation. Both effluent and worker protection issues will be discussed. For effluents, the source terms at sites will be characterized, and measurement techniques will be presented. Off-site dose impacts will be included. For worker protection issues, air sampling analyses will be presented in order to show how the workers are adequately protected and their doses measured to satisfy regulatory criteria during decontamination operations. 1 tab.

  14. Efficient methods of nanoimprint stamp cleaning based on imprint self-cleaning effect

    Energy Technology Data Exchange (ETDEWEB)

    Meng Fantao; Chu Jinkui [Key Laboratory for Micro/Nano Technology and System of Liaoning Province, Dalian University of Technology, 116024 Dalian (China); Luo Gang; Zhou Ye; Carlberg, Patrick; Heidari, Babak [Obducat AB, SE-20125 Malmoe (Sweden); Maximov, Ivan; Montelius, Lars; Xu, H Q [Division of Solid State Physics, Lund University, Box 118, S-22100 Lund (Sweden); Nilsson, Lars, E-mail: ivan.maximov@ftf.lth.se [Department of Food Technology, Engineering and Nutrition, Lund University, Box 117, S-22100 Lund (Sweden)

    2011-05-06

    Nanoimprint lithography (NIL) is a nonconventional lithographic technique that promises low-cost, high-throughput patterning of structures with sub-10 nm resolution. Contamination of nanoimprint stamps is one of the key obstacles to industrialize the NIL technology. Here, we report two efficient approaches for removal of typical contamination of particles and residual resist from stamps: thermal and ultraviolet (UV) imprinting cleaning-both based on the self-cleaning effect of imprinting process. The contaminated stamps were imprinted onto polymer substrates and after demolding, they were treated with an organic solvent. The images of the stamp before and after the cleaning processes show that the two cleaning approaches can effectively remove contamination from stamps without destroying the stamp structures. The contact angles of the stamp before and after the cleaning processes indicate that the cleaning methods do not significantly degrade the anti-sticking layer. The cleaning processes reported in this work could also be used for substrate cleaning.

  15. 16th DOE nuclear air cleaning conference: proceedings

    International Nuclear Information System (INIS)

    First, M.W.

    1981-02-01

    Major topics discussed during the Sixteenth DOE Nuclear Air Cleaning Conference were: waste treatment, including volume reduction and storage; system and component response to stress and accident conditions; Three Mile Island accident; iodine adsorption; treatment and storage of noble gas: treatment of offgases from chemical processing; aerosol; behavior; containment venting; laboratory and in-place filter-testing methods; and particulate filtration. Volume I of the Proceedings has 49 papers from the following sessions; HEPA filter test methods; noble gas separation; air cleaning system design; containment venting; iodine adsorption; reprocessing offgas cleaning; critical review; filtration; filter testing; and aerosols. Volume II contains 44 papers from the sessions on: nuclear waste treatment; critical review; noble gas treatment; carbon-14 and tritium; air cleaning system response to stress; nuclear standards and safety; round table; open end; and air cleaning technology at Three Mile Island. Abstracts are provided for all of these papers

  16. 16th DOE nuclear air cleaning conference: proceedings

    International Nuclear Information System (INIS)

    First, M.W.

    1981-02-01

    Major topics discussed during the Sixteenth DOE Nuclear Air Cleaning Conference were: waste treatment, including volume reduction and storage; system and component response to stress and accident conditions; Three Mile Island accident; iodine adsorption; treatment and storage of noble gas; treatment of offgases from chemical processing; aerosol behavior; containment venting; laboratory and in-place filter-testing methods; and particulate filtration. Volume I of the Proceedings has 49 papers from the following sessions: HEPA filter test methods; noble gas separation; air cleaning system design; containment venting; iodine adsorption; reprocessing offgas cleaning; critical review; filtration, filter testing, and aerosols. Volume II contains 44 papers from the sessions on: nuclear waste treatment; critical review; noble gas treatment; carbon-14 and tritium; air cleaning system response to stress; nuclear standards and safety; round table; open end; and air cleaning technology at Three Mile Island. Abstracts are provided for all of these papers

  17. 60 years of Health Protection under the Clean Air Acts

    OpenAIRE

    Longhurst, J.

    2016-01-01

    2016 marks 60 years of UK Clean Air Acts. This presentation explores the challenges, opportunities and progress since the Clean Air Act, 1956. It reflects upon historical attempts to manage air pollution noting success factors and barriers to progress. Particular attention is given to the impact of the 1952 Great Smog and the role of National Smoke Abatement Society, the forerunner of Environmental Protection UK, in creating the momentum for the 1956 Act. The presentation concludes with a rev...

  18. Nuclear air cleaning: the need for a change in emphasis

    International Nuclear Information System (INIS)

    Carbaugh, E.H.

    1982-11-01

    The nuclear industry now has over 35 years of experience in nuclear air cleaning. This experience covers technology development, system design, operations, and maintenance. Much of the past experience has been directed towards technology development with particular emphasis on high efficiency particulate air (HEPA) filters. Implementation of this technology has lagged its development by a number of years. A recent study examines the cause and frequencies of HEPA filter changeouts and failures. These data lead to a conclusion that a shift in emphasis from technology development to the training of personnel and the designing and maintaining of such systems is needed. Some highlights of the data and a discussion of topics which should be addressed in training will be presented

  19. Nuclear air cleaning: the need for a change in emphasis

    International Nuclear Information System (INIS)

    Carbaugh, E.H.

    1983-01-01

    The nuclear industry now has over 35 years of experience in nuclear air cleaning. This experience covers technology development, system design, operations, and maintenance. Much of the past experience has been directed towards technology development with particular emphasis on high efficiency particulate air (HEPA) filters. Implementation of this technology has lagged its development by a number of years. A recent study examines the causes and frequencies of HEPA filter changeouts and failures. These data lead to a conclusion that a shift in emphasis from technology development to the training of personnel and the designing and maintaining of such systems is needed. Some highlights of the data and a discussion of topics which should be addressed in training will be presented. 7 references, 5 tables

  20. Evaluating impacts of Clean Air Act compliance strategies

    International Nuclear Information System (INIS)

    Shirer, D.A.; Evans, R.J.; Harrison, C.D.; Kehoe, D.B.

    1993-01-01

    The Clean Air Act Amendments of 1990 requires that by the year 2000, US SO 2 emissions must be reduced by 10 million tons. This requirement will have significant impact on coal-fired electric utilities. As a result, most utilities are currently evaluating numerous compliance options, including buying allowances, coal cleaning/blending/switching, and flue gas scrubbing. Moreover, each utility must address its own unique circumstances with regard to competition, efficiency, capital expenditures, reliability, etc. and many utilities may choose a combination of compliance options to simultaneously satisfy their environmental, performance, and financial objectives. The Coal Quality Expert, which is being developed under a clean coal technology project funded by US DOE and EPRI, will predict the economic, operational, and environmental benefits of using higher-quality coals and provides an assessment of the merits of various post-combustion control technologies for specific utility applications. This paper presents background on how utilities evaluate their compliance options, and it describes how the Coal Quality Expert could be used for such evaluations in the future to assure that each utility can select the best combination of coal specifications and emission control technologies to meet its compliance objectives

  1. Evaluation of air cleaning technologies existing in the Danish market

    DEFF Research Database (Denmark)

    Ardkapan, Siamak Rahimi; Afshari, Alireza; Bergsøe, Niels Christian

    2014-01-01

    Five portable air cleaning technologies including one new technology were evaluated to find their effectiveness in removing ultrafine particles. Measurements were carried out both in a duct and in a test room. The results showed that the technologies that use/create ozone to clean air can increase...... the ozone level significantly in the room. Moreover, they can cause generation of ultrafine particles and consequently increase ultrafine particle concentration in the room. The study suggests using a mechanical filter with low pressure drop as a recommended air cleaning technology in order to remove...

  2. Combining active chilled beams and air cleaning technologies to improve indoor climate in offices

    DEFF Research Database (Denmark)

    Ardkapan, Siamak Rahimi; Afshari, Alireza; Bergsøe, Niels Christian

    2012-01-01

    This project is part of a long-term research programme studying the possibilities of using efficient air cleaning technologies to improve the indoor air quality in buildings. The purpose of this part of the project is to study energy-saving potential by combining cooling and cleaning of air in of....... Furthermore, the measurement results of the combined system showed that adding the filter accelerated the removal rate of the particles by 2 (h-1). However, the efficiency of the chilled beam in exchanging the heat reduced by 38%....

  3. CLEAN-AIR heat pump. Reduced energy consumption for ventilation in buildings by integrating air cleaning and heat pump. Final Report; CLEAN-AIR heat pump - Reduceret energiforbrug til ventilation af bygninger ved luftrensning integreret med luft varmepumpe. Slut rapport

    Energy Technology Data Exchange (ETDEWEB)

    Fang, L.; Olesen, Bjarne W.; Molinaro, G.; Simmonsen, P.; Skocajic, S. [Danmarks Tekniske Univ. Institut for Byggeri og Anlaeg, Lyngby (Denmark); Hummelshoej, R.M.; Carlassara, L. [COWI A/S, Lyngby, (Denmark); Groenbaek, H.; Hansen, Ole R. [Exhausto A/S, Langeskov (Denmark)

    2011-07-01

    much lower than the domestic price. For the extremely hot and humid climate, the clean air heat pump has the maximum ability of the energy saving for ventilation. The calculations showed that annual energy saving of using the clean air heat pump for ventilation in Sri Lanka is 62%. In general, the clean air heat pump system is suitable for ventilation in all kind of climates around the world except for the hot and dry climate. The annual energy saving is expected in the range between 30% and 60% depending on the climate. It is worth noting that the calculated energy reduction of a ventilation system using the clean air heat pump technology was an extra saving compared to a ventilation system that equipped with the high efficiency counter flow heat recovery equipment with a temperature efficiency of 80%. Based on this simulation, it can be concluded that the energy saving of the clean air heat pump for ventilation is remarkable. Therefore, the technology is highly recommended provided that this simulation results are further validated by experiments. (Author)

  4. Some impacts of the 1990 Clean Air Act and state clean-air regulations on the fertilizer industry

    International Nuclear Information System (INIS)

    Breed, C.E.; Kerns, O.S.

    1992-01-01

    The Clean Air Act amendments of 1990 will intensify national efforts to reduce air pollution. They will have major impacts on governmental agencies and on industrial and commercial facilities throughout the country. As with other industries, it is essential for fertilizer dealers and producers to understand how these changes to the Clean Air Act can significantly change the way they do business. This paper is proffered as an overview of ways in which the 1990 amendments to the Clean Air Act may impact the fertilizer industry. The nonattainment, toxics, and permit provisions of the amended act will be three areas of particular concern to the fertilizer industry. Implementation of the new regulatory requirements of this legislation promises to be a long and onerous process for all concerned. However, it appears that state and local regulations may have a much more profound impact on the fertilizer industry than the new Clean Air Act

  5. Utility view of the source term and air cleaning

    International Nuclear Information System (INIS)

    Littlefield, P.S.

    1985-01-01

    The utility view of the source term and air cleaning is discussed. The source term is made up of: (1) noble gases, which there has been a tendency to ignore in the past because it was thought there was nothing that could be done with them anyway, (2) the halogens, which have been dealt with in Air Cleaning Conferences in the past in terms of charcoal and other systems for removing them, and (3) the solid components of the source term which particulate filters are designed to handle. Air cleaning systems consist of filters, adsorbers, containment sprays, suppression pools in boiling water reactors and ice beds in ice condenser-equipped plants. The feasibility and cost of air cleaning systems are discussed

  6. Proceedings of the fifteenth DOE nuclear air cleaning conference

    Energy Technology Data Exchange (ETDEWEB)

    First, M.W. (ed.)

    1979-02-01

    Papers presented are grouped under the following topics: noble gas separation, damage control, aerosols, test methods, new air cleaning technology from Europe, open-end, and filtration. A separate abstract was prepared for each paper.

  7. Agenda and Presentations from Circumpolar Workshop: Transport and Clean Air

    Science.gov (United States)

    EPA and its partners convened Transport and Clean Air, a Circumpolar Workshop held in December 2013. This seminar allowed leading experts to share best practices on reducing emissions of particulates and black carbon from diesel sources in the Arctic.

  8. A brief history of the air cleaning conferences

    Energy Technology Data Exchange (ETDEWEB)

    First, M.W.

    1995-02-01

    I have been asked to prepare a history of the air cleaning conferences. Undertaking such a task is, of course, a wonderful opportunity for reminiscences and a chance to retell old war stories. I must admit that it has taken much longer than I anticipated because I found myself so completely engrossed rereading the old records that time seemed to stop, although the hours passed. But a history of the nuclear air cleaning conferences means more than a stroll down memory lane. The 23 recorded air cleaning conference proceedings reflect an important aspect of the history of major nuclear developments, both military and civilian, because engineered safety features designed to prevent dispersion of radioactive products to the environment have always been a necessity for progress in this field. For this reason, I hope the history of the nuclear air cleaning conferences will not only be enjoyable, but also have meaning for young people entering this field. The air cleaning conferences were an outgrowth of the operations of the U.S. Atomic Energy Commission`s (AEC) Stack Gas Working Group established in 1948 to review air cleaning operations at AEC installations. AEC`s Division of Engineering sponsored and funded air cleaning research and development at Harvard University`s School of Public Health, beginning about the same time. In addition to research and development, the Harvard contract called for consulting and educational services. The latter provided the opportunity for meetings devoted to information on air cleaning that could be applied to ongoing and anticipated nuclear operations.

  9. Can commonly-used fan-driven air cleaning technologies improve indoor air quality? A literature review

    DEFF Research Database (Denmark)

    Zhang, Yinping; Mo, Jinhan; Li, Yuguo

    2011-01-01

    America, and Asia with expertise in air cleaning, aerosol science, medicine, chemistry and ventilation. The effects on health were not examined. Over 26,000 articles were identified in major literature databases; 400 were selected as being relevant based on their titles and abstracts by the first two......Air cleaning techniques have been applied worldwide with the goal of improving indoor air quality. The effectiveness of applying these techniques varies widely, and pollutant removal efficiency is usually determined in controlled laboratory environments which may not be realized in practice. Some...... air cleaners are largely ineffective, and some produce harmful by-products. To summarize what is known regarding the effectiveness of fan-driven air cleaning technologies, a state-of-the-art review of the scientific literature was undertaken by a multidisciplinary panel of experts from Europe, North...

  10. Food-Growing, Air- And Water-Cleaning Module

    Science.gov (United States)

    Sauer, R. L.; Scheld, H. W.; Mafnuson, J. W.

    1988-01-01

    Apparatus produces fresh vegetables and removes pollutants from air. Hydroponic apparatus performs dual function of growing fresh vegetables and purifying air and water. Leafy vegetables rooted in granular growth medium grow in light of fluorescent lamps. Air flowing over leaves supplies carbon dioxide and receives fresh oxygen from them. Adaptable to production of food and cleaning of air and water in closed environments as in underwater research stations and submarines.

  11. Clean Air Slots Amid Atmospheric Pollution

    Science.gov (United States)

    Hobbs, Peter V.

    2002-01-01

    This article investigates the mechanism for those layers in the atmosphere that are free of air borne pollution even though the air above and below them carry pollutants. Atmospheric subsidence is posed as a mechanism for this phenomenon.

  12. Combining active chilled beams and air-cleaning technologies to improve the indoor climate in offices

    DEFF Research Database (Denmark)

    Ardkapan, Siamak Rahimi; Afshari, Alireza; Bergsøe, Niels Christian

    2013-01-01

    This project is part of a long-term research programme to study the possibilities of using efficient air-cleaning technologies to improve the indoor air quality in buildings. The purpose of this part of the project was to study the energy-saving potential of combining the cooling and cleaning of ...... than 5 Pa (0.104 Ibf /ft2). Furthermore, the measurement results of the combined system showed that adding the filter accelerated the removal rate of the particles by 2 h-1. However, the efficiency of the chilled beam in exchanging heat was reduced by 38%....

  13. Clean indoor air increases physical independence : a pilot study

    NARCIS (Netherlands)

    Snijders, M.C.L.; Koren, L.G.H.; Kort, H.S.M.; Bronswijk, van J.E.M.H.

    2001-01-01

    Clean indoor air enhances health. In a pilot study, we examined whether a good indoor air quality increases the activity potential of older persons with chronic lung disease. Five older persons were studied while performing kitchen activities. Body movement and heart rate were monitored.

  14. Clean Air Slots Amid Dense Atmospheric Pollution in Southern Africa

    Science.gov (United States)

    Hobbs, Peter V.

    2003-01-01

    During the flights of the University of Washington's Convair-580 in the Southern African Regional Science Initiative (SAFARI 2000) in southern Africa, a phenomenon was observed that has not been reported previously. This was the occurrence of thin layers of remarkably clean air, sandwiched between heavily polluted air, which persisted for many hours during the day. Photographs are shown of these clean air slots (CAS), and particle concentrations and light scattering coefficients in and around such slot are presented. An explanation is proposed for the propensity of CAS to form in southern Africa during the dry season.

  15. Fundamentals of air cleaning technology and its application in cleanrooms

    CERN Document Server

    Xu, Zhonglin

    2014-01-01

    Fundamentals of Air Cleaning Technology and Its Application in Cleanrooms sets up the theoretical framework for cleanrooms. New ideas and methods are presented, which include the characteristic index of cleanrooms, uniform and non-uniform distribution characteristics, the minimum sampling volume, a new concept of outdoor air conditioning and the fundamentals of leakage-preventing layers. Written by an author who can look back on major scientific achievements and 50 years of experience in this field, this book offers a concise and accessible introduction to the fundamentals of air cleaning technology and its application. The work is intended for researchers, college teachers, graduates, designers, technicians and corporate R&D personnel in the field of HVAC and air cleaning technology. Zhonglin Xu is a senior research fellow at China Academy of Building Research.

  16. The Clean Coal Program's contributions to addressing the requirements of the Clean Air Act Amendments of 1990

    International Nuclear Information System (INIS)

    Miller, R.L.

    1992-01-01

    The purpose of this paper is to examine the potential contributions of the US Department of Energy's Clean Coal Program (CCP) to addressing the requirements of the Clean Air Act (CAA) Amendments of 1990 (CAA90). Initially funded by Congress in 1985, the CCP is a government and industry co-funded effort to demonstrate a new generation of more efficient, economically feasible, and environmentally acceptable coal technologies in a series of full- scale ''showcase'' facilities built across the country. The CCP is expected to provide funding for more than $5 billion of projects during five rounds of competition, with at least half of the funding coming from the private sector. To date, 42 projects have been selected in the first 4 rounds of the CCP. The CAA and amendments form the basis for regulating emissions of air pollutants to protect health and the environment throughout the United States. Although the origin of the CAA can be traced back to 1955, many amendments passed since that time are testimony to the iterative process involved in the regulation of air pollution. Three key components of CAA90, the first major amendments to the CAA since 1977, include mitigation measures to reduce levels of (1) acid deposition, (2) toxic air pollutants, and (3) ambient concentrations of air pollutants. This paper focuses on the timeliness of clean coal technologies in contributing to these provisions of CAA90

  17. The Clean Air Act and the Economy

    Science.gov (United States)

    Since 1970, cleaner air and a growing economy have gone hand in hand. The Act has created market opportunities that have helped to inspire innovation in cleaner technologies for which the United States has become a global market leader.

  18. Enlisting municipal governments in a national approach to clean air and climate change

    International Nuclear Information System (INIS)

    2006-01-01

    The Federation of Canadian Municipalities (FCM) and the Government of Canada have a shared commitment to improve environmental performance and protect the health of Canadians. Air pollution and climate change are also a shared responsibility among federal, municipal and provincial/territorial governments. Although they operate independently, their policies and programs tend to overlap. This is both costly and inefficient. In order to create synergies and leverage the role and potential of each level of government, the FCM proposed a national approach to clean air and climate change. The approach involves all levels of government in a nationally coordinated effort, with roles appropriate to their capacities. The municipal role in clean air and climate change action, roles and responsibilities of municipal governments, and guiding principles of a new Canadian approach were discussed in this document. Recommendations and next steps were also identified. They centred on the following themes: enhancing public transit, clean transportation and related infrastructure; improving commercial and residential building efficiency; stimulating ongoing productivity and pollution prevention within municipal operations through incentives and policies; enhancing clean energy; strengthened and enforceable air quality standards; emissions trading; climate change adaptation; public education and awareness; and demonstrating success and ensuring accountability. The document concluded that only a long-term intergovernmental partnership can meet the challenges posed by climate change and air pollution. FCM urged the Government of Canada to adopt an integrative and strategic approach to clean air and climate change by enlisting municipal governments as partners in both its development and implementation

  19. Emergency air cleaning system development for LMFBR containments

    International Nuclear Information System (INIS)

    McCormack, J.D.; Hilliard, R.K.; Postma, A.K.; Muhlestein, L.D.

    1975-01-01

    Criteria for evaluating the various types of Emergency Air Cleaning Systems which may be used in LMFBR plants have been established for both single containment and containment-confinement arrangements. These two plant arrangements have quite different air cleaning requirements for postulated design base accident conditions. Work is currently in progress to select from a list of candidate air cleaning systems those which best meet the criteria requirements. By means of a weighted rating system, areas of strength or weakness can be found and the conceptual system design then optimized. The final system arrangements will be ranked and several of the most promising systems selected for large-scale tests in the former CSE vessel at Hanford. 8 references. (U.S.)

  20. Cleaning products and air fresheners: exposure to primary and secondary air pollutants

    DEFF Research Database (Denmark)

    Nazaroff, W.; Weschler, Charles J.

    2004-01-01

    Building occupants, including cleaning personnel, are exposed to a wide variety of airborne chemicals when cleaning agents and air fresheners are used in buildings. Certain of these chemicals are listed by the state of California as toxic air contaminants (TACs) and a subset of these are regulated...... by the US federal government as hazardous air pollutants (HAPs). California's Proposition 65 list of species recognized as carcinogens or reproductive toxicants also includes constituents of certain cleaning products and air fresheners. In addition, many cleaning agents and air fresheners contain chemicals...... that can react with other air contaminants to yield potentially harmful secondary products. For example, terpenes can react rapidly with ozone in indoor air generating many secondary pollutants, including TACs such as formaldehyde. Furthermore, ozone-terpene reactions produce the hydroxyl radical, which...

  1. New challenges to air/gas cleaning systems

    Energy Technology Data Exchange (ETDEWEB)

    Kovach, J.L. [NUCON International, Inc., Columbus, OH (United States)

    1997-08-01

    This paper discusses the need for changes in the design and manufacturing of air and gas cleaning systems to meet waste management and site remediation requirements. Current design and manufacturing practices are primarily directed toward evaluating operational problems with existing systems in nuclear reactor facilities. However, nuclear waste management needs have developed which are much broader in scope and have different processing conditions. Numerous examples of air cleaning needs for waste management activities are provided; the major differences from operating facility needs are the requirement for continuous effluent treatment under widely different processing conditions. Related regulatory issues are also discussed briefly. 1 ref.

  2. 77 FR 3386 - Approval and Promulgation of Air Quality Implementation Plans; Pennsylvania; Clean Vehicles Program

    Science.gov (United States)

    2012-01-24

    ... Promulgation of Air Quality Implementation Plans; Pennsylvania; Clean Vehicles Program AGENCY: Environmental... vehicles (LEV II). The Clean Air Act (CAA) contains specific authority allowing any state to adopt new... CFR Part 52 Environmental protection, Air pollution control, Incorporation by reference...

  3. Experimental researches and comparison on aerodynamic parameters and cleaning efficiency of multi-level multi-channel cyclone

    Directory of Open Access Journals (Sweden)

    Aleksandras Chlebnikovas

    2015-10-01

    Full Text Available Multi-level multi-channel cyclone – the lately designed air cleaning device that can remove ultra-fine 20 μm particulatematter (PM from dusted air and reach over 95% of the overall cleaning efficiency. Multi-channel cyclone technology is based on centrifugal forces and has the resulting additional filtering process operation. Multi-level structure of cyclone allows to achieve higher air flow cleaning capacity at the same dimensions of the device, thus saving installation space required for the job, production and operating costs. Studies have examined the air flow parameters change in one–, two– and three–levels multichannel cyclone. These constructions differ according to the productivity of cleaned air under the constant peripheral and transitional (50/50 case air flow relations. Accordance with the results of air flow dynamics – velocity distribution of multi-channel cyclone, aerodynamic resistance and efficiency can be judged on the flow turbulence, the flow channel cross-section and select the most appropriate application. Cleaning efficiency studies were carried out using fine granite and wood ashes PM. The maximum cleaning efficiency was 93.3%, at an average of 4.5 g/m3, the aerodynamic resistance was equal to 1525 Pa.

  4. Nanomaterials for benign indoor environments: Electrochromics for 'smart windows', sensors for air quality, and photo-catalysts for air cleaning

    International Nuclear Information System (INIS)

    Granqvist, C.G.; Azens, A.; Heszler, P.; Kish, L.B.; OEsterlund, L.

    2007-01-01

    Nanomaterials can be used in a number of technologies in order to accomplish benign indoor environments. This paper takes a unified view on this problem from a solar-energy-based perspective and specifically considers electrochromics for achieving good day-lighting jointly with energy efficiency, sensors aimed at air quality assessment, and photocatalysis for air cleaning. Recent results, mainly from the authors' laboratories, are reported for all of these areas. (author)

  5. Clean burn: Incinerators get more efficient

    International Nuclear Information System (INIS)

    Budd, G.

    2003-01-01

    Combustion efficiency and accuracy of today's new breed of incinerators is discussed. The latest of these units are capable of delivering 99.99 per cent combustion efficiency with no visible flame, black smoke or detectable odour. Near-complete combustion is achieved with incineration because of the very high temperatures reached in the enclosed combustion chamber as a combination of temperature, time for burning, and a good mix of gases and oxygen. Controlling these inputs is the key to efficient incineration, as is high quality fibre refractory lining; control means control of the stack top temperature, which will affect what comes out of the top water and how well the combustion byproducts are dispersed. Until recently, incinerators have not been highly regarded by the oil industry. However, with the growing concerns about greenhouse gases, carcinogens and in response to increasing regulations aimed at reducing venting and flaring, incinerators are coming into their own. Today they are seen more and more frequently in well testing, coalbed methane testing, at battery sites and at gas plants

  6. Clean air litigation; Klagen fuer Saubere Luft

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2016-11-11

    The pollution of air by nitrogen dioxide (NO{sub 2}) in cities is one of the central challenges of air pollution in Germany, in addition to the pollution of particulate matter (PM10). In cooperation with the British non-governmental organization ClientEarth, the German Environmental Aid (DUH) filed a lawsuit in November 2015 for exceeding air quality limits for NO{sub 2}. The cities of Stuttgart, Frankfurt, Duesseldorf, Essen, Gelsenkirchen, Aachen, Cologne and Bonn are affected. Here, citizens are constantly exposed to high air pollution. Because of the excess of the NO{sub 2} limits at all traffic-related measuring stations in Berlin, the DUH initiated legal steps and filed a lawsuit too in June 2016. With the lawsuits, DUH wants to promote the implementation of measures to reduce NO{sub 2} in Germany. [German] Die Belastung der Luft durch Stickstoffdioxid (NO{sub 2}) in Staedten ist neben der Belastung durch Feinstaub (PM10) eine der zentralen Herausforderungen der Luftreinhaltung in Deutschland. In Zusammenarbeit mit der britischen Nichtregierungsorganisation ClientEarth legte die Deutsche Umwelthilfe (DUH) im November 2015 Klage wegen Ueberschreitung der Luftqualitaetsgrenzwerte fuer NO{sub 2}ein. Betroffen sind die Staedte Stuttgart, Frankfurt, Duesseldorf, Essen, Gelsenkirchen, Aachen, Koeln und Bonn. Hier sind Buergerinnen und Buerger anhaltend zu hoher Luftverschmutzung ausgesetzt. Wegen Ueberschreitung der NO{sub 2}-Grenzwerte an allen verkehrsnahen Messstationen in Berlin hat die DUH im Juni 2016 auch hier rechtliche Schritte eingeleitet und Klage eingereicht. Mit den Klagen will die DUH die Umsetzung von Massnahmen zur NO{sub 2}-Reduktion in Deutschland voranbringen.

  7. VOCs and formaldehyde emissions from cleaning products and air fresheners

    OpenAIRE

    Solal , Cécilia; Rousselle , Christophe; Mandin , Corinne; Manel , Jacques; Maupetit , François

    2008-01-01

    International audience; Human indoor exposure to Volatile Organic Compounds (VOCs) may be associated with the use of household products. However little is known about their emissions and to what extent they contribute to indoor air pollution. The French Agency for Environmental and Occupational Health Safety (Afsset) conducted tests in order to characterize VOCs emissions from 32 consumer products: air fresheners, glass cleaners, furniture polishes, toilet products, carpet and floor cleaning ...

  8. Air toxics and the 1990 Clean Air Act: Managing trace element emissions

    International Nuclear Information System (INIS)

    Chow, W.; Levin, L.; Miller, M.J.

    1992-01-01

    The US Environmental Protection Agency (EPA) has historically regulated air toxics (hazardous air pollutants) under Section 112 of the Clean Air Act. To date, EPA has established emission standards for 8 hazardous air pollutants (arsenic, asbestos, benzene, beryllium, mercury, radionuclides, coke oven emissions and vinyl chloride). The US electric utility industry was not determined to be a source category requiring regulation for any of the eight chemicals. Of the eight, radionuclides were the last species for which EPA established hazardous emissions standards. In this instance, EPA determined that the risks associated with electric utility fossil fuel power plant emissions were sufficiently low that they should not be regulated. However, the 1990 Clean Air Act Amendments require a new evaluation of the electric utility industry emissions of hazardous air pollutants. This paper summarizes the key features of the air toxics provisions of the Clean Air Act Amendments, describes EPRI's activities on the subject, and provides some preliminary insights from EPRI's research to date

  9. Prototype firing range air cleaning system

    International Nuclear Information System (INIS)

    Glissmeyer, J.A.; Mishima, J.; Bamberger, J.A.

    1984-07-01

    PNL's study proceeded by examining the characteristics of the aerosol challenge to the filtration system and the operating experience at similar firing ranges. Candidate filtration systems were proposed; including baghouses, cartridge houses, electrostatic precipitators, cleanable high efficiency filters, rolling filters and cyclones--each followed by one or more of the existing filter banks. Methodology was developed to estimate the operating costs of the candidate systems. Costs addressed included the frequency (based on fractional efficiency and loading data) and cost of media replacement, capital investment, maintenance, waste disposal and electrical power consumption. The recommended system will be installed during calendar year 1984

  10. Index to the AEC/ERDA/DOE Air Cleaning Conferences

    International Nuclear Information System (INIS)

    Burchsted, C.A.

    1980-01-01

    A comprehensive index to the papers in the second through sixteenth AEC/ERDA/DOE Nuclear Air Cleaning Conference is discussed. The index will be published in early 1981 and will be designated as Volume 3 of the proceeding of the sixteenth conference. The index has three parts, a straight numeric tabulation, an author index, and a key word in context (KWIC) index

  11. Proceedings of the fifteenth DOE nuclear air cleaning conference

    Energy Technology Data Exchange (ETDEWEB)

    First, M.W. (ed.)

    1979-02-01

    Papers presented are grouped under the following topics: air cleaning; waste volume reduction and preparation for storage; tritium, carbon-14, ozone; containment of accidental releases; adsorbents and absorbents; and off-gas treatment. A separate abstract was prepared for each paper.

  12. Plants Clean Air and Water for Indoor Environments

    Science.gov (United States)

    2007-01-01

    Wolverton Environmental Services Inc., founded by longtime government environmental scientist B.C. "Bill" Wolverton, is an environmental consulting firm that gives customers access to the results of his decades of cutting-edge bioremediation research. Findings about how to use plants to improve indoor air quality have been published in dozens of NASA technical papers and in the book, "How to Grow Fresh Air: 50 Houseplants That Purify Your Home or Office." The book has now been translated into 12 languages and has been on the shelves of bookstores for nearly 10 years. A companion book, "Growing Clean Water: Nature's Solution to Water Pollution," explains how plants can clean waste water. Other discoveries include that the more air that is allowed to circulate through the roots of the plants, the more effective they are at cleaning polluted air; and that plants play a psychological role in welfare in that people recover from illness faster in the presence of plants. Wolverton Environmental is also working in partnership with Syracuse University, to engineer systems consisting of modular wicking filters tied into duct work and water supplies, essentially tying plant-based filters into heating, ventilation, and air conditioning (HVAC) systems. Also, the company has recently begun to assess the ability of the EcoPlanter to remove formaldehyde from interior environments. Wolverton Environmental is also in talks with designers of the new Stennis Visitor's Center, who are interested in using its designs for indoor air-quality filters

  13. Effect of Air Cleaning Technologies in Conjunction With the Use of Rotary Heat Exchangers in Residential Buildings

    DEFF Research Database (Denmark)

    Afshari, Alireza; Bergsøe, Niels Christian; Ekberg, Lars

    2013-01-01

    This study is part of a research project concerning the possibilities of applying efficient air cleaning technologies using rotary heat exchanger in residential buildings. The purpose of this project was to identify and adapt new air-cleaning technologies for implementation in HVAC systems...... with rotary air-to-air heat exchangers. For this purpose, a mechanical filter with low pressure drop and a 4 cm thick activated carbon filter were selected for testing in a laboratory environment. The measurements included testing of the filters, separately and combined, in a ductwork to study the efficiency...

  14. Energy from Waste--clean, efficient, renewable: transitions in combustion efficiency and NOx control.

    Science.gov (United States)

    Waldner, M H; Halter, R; Sigg, A; Brosch, B; Gehrmann, H J; Keunecke, M

    2013-02-01

    Traditionally EfW (Energy from Waste) plants apply a reciprocating grate to combust waste fuel. An integrated steam generator recovers the heat of combustion and converts it to steam for use in a steam turbine/generator set. This is followed by an array of flue gas cleaning technologies to meet regulatory limitations. Modern combustion applies a two-step method using primary air to fuel the combustion process on the grate. This generates a complex mixture of pyrolysis gases, combustion gases and unused combustion air. The post-combustion step in the first pass of the boiler above the grate is intended to "clean up" this mixture by oxidizing unburned gases with secondary air. This paper describes modifications to the combustion process to minimize exhaust gas volumes and the generation of noxious gases and thus improving the overall thermal efficiency of the EfW plant. The resulting process can be coupled with an innovative SNCR (Selective Non-Catalytic Reduction) technology to form a clean and efficient solid waste combustion system. Measurements immediately above the grate show that gas compositions along the grate vary from 10% CO, 5% H(2) and 0% O(2) to essentially unused "pure" air, in good agreement with results from a mathematical model. Introducing these diverse gas compositions to the post combustion process will overwhelm its ability to process all these gas fractions in an optimal manner. Inserting an intermediate step aimed at homogenizing the mixture above the grate has shown to significantly improve the quality of combustion, allowing for optimized process parameters. These measures also resulted in reduced formation of NO(x) (nitrogenous oxides) due to a lower oxygen level at which the combustion process was run (2.6 vol% O(2,)(wet) instead of 6.0 vol% O(2,)(wet)). This reduction establishes optimal conditions for the DyNOR™ (Dynamic NO(x) Reduction) NO(x) reduction process. This innovative SNCR technology is adapted to situations typically

  15. Chapter 4: Assessing the Air Pollution, Greenhouse Gas, Air Quality, and Health Benefits of Clean Energy Initiatives

    Science.gov (United States)

    Chapter 4 of Assessing the Multiple Benefits of Clean Energy helps state states understand the methods, models, opportunities, and issues associated with assessing the GHG, air pollution, air quality, and human health benefits of clean energy options.

  16. Performance evaluation of air cleaning devices of an operating low level radioactive solid waste incinerator

    International Nuclear Information System (INIS)

    Subramanian, V.; Surya Narayana, D.S.; Sundararajan, A.R.; Satyasai, P.M.; Ahmed, Jaleel

    1997-01-01

    Particle removal efficiencies of a cyclone separator, baghouse filters and a high efficiency particulate activity (HEPA) filter bank of an incinerator have been determined during the incineration of combustible low level solid radioactive wastes with surface dose of 20 - 50 gy/h. Experimental runs have been carried out to collect the particulates in various aerodynamic size ranges using an eight stage Andersen sampler and a low pressure impactor (LPI) while the incinerator is in operation. The collection efficiencies of the cyclone, baghouse and HEPA filters have been found to be 100 per cent for particles of size greater than 4.7, 2.1 and 1.1 μm respectively. The results of our investigations indicate that the air cleaning devices of the incinerator are working according to their design criteria. The data will be useful in the design and operation of air cleaning devices for toxic gaseous effluents. (author). 3 refs., 2 figs., 1 tab

  17. The diffusion and impact of clean indoor air laws.

    Science.gov (United States)

    Eriksen, Michael P; Cerak, Rebecca L

    2008-01-01

    Over the past quarter century, primarily as a result of scientific discovery, citizen advocacy, and legislative action, comprehensive clean indoor air laws have spread rapidly throughout the world. Laws that establish completely smoke-free indoor environments have many relative advantages including being low cost, safe, effective, and easy to implement. The diffusion of these laws has been associated with a dramatic and rapid reduction in population levels of serum cotinine among nonsmokers and has also contributed to a reduction in overall cigarette consumption among smokers, with no adverse economic impact, except to the tobacco industry. Currently, nearly half of the U.S. population lives in jurisdictions with some combination of completely smoke-free workplaces, restaurants, or bars. The diffusion of clean indoor air laws is spreading rapidly throughout the world, stimulated by the first global health treaty, the Framework Convention on Tobacco Control.

  18. Market Initiatives for Clean Air Schools; Marktinitiatieven frisse scholen

    Energy Technology Data Exchange (ETDEWEB)

    Teeuwen, D. [Communication Concert, Weesp (Netherlands)

    2012-07-15

    Seven years ago, the Clean Air Schools Program was launched to encourage people to use less energy and improve the indoor environment. In 2012, the program Energy and Built Environment will no longer pay specific attention focused on school buildings. Therefore, the market needs to jump in. 'Market initiatives' refers to projects, products and services that contribute to the realization of Clean Air Schools and which are not initiated by the Dutch government [Dutch] Zeven jaar geleden is het Frisse Scholen Programma gestart om gemeenten en scholen te stimuleren om minder energie te gebruiken en het binnenmilieu te verbeteren. In 2012 biedt het programma Energie en Gebouwde Omgeving geen ruimte meer voor specifieke aandacht gericht op scholen. Daarom zal het stokje overgedragen moeten worden aan marktpartijen. Met 'marktinitiatieven' wordt gedoeld op projecten, producten en diensten die bijdragen aan de realisatie van Frisse Scholen en niet door de Rijksoverheid worden geinitieerd.

  19. Nuclear air cleaning programs in progress in France

    International Nuclear Information System (INIS)

    Mulcey, P.

    1991-01-01

    A short presentation is given of the nuclear air cleaning programs in progress in France with respect to pressurized water reactors, fuel reprocessing plants, radioactive waste management facilities, and the dismantling of nuclear facilities. The effects of fires in rooms and ventilation ducts in all nuclear facilities is being studied and computer simulation codes are being developed. A brief review of filter development and filter testing is also presented

  20. Methods for air cleaning system design and accident analysis

    International Nuclear Information System (INIS)

    Gregory, W.S.; Nichols, B.D.

    1987-01-01

    This paper describes methods, in the form of a handbook and five computer codes, that can be used for nuclear facility air cleaning system design and accident analysis. Four of the codes were developed primarily at the Los Alamos National Laboratory, and one was developed in France. Tools such as these are used to design ventilation systems in the mining industry but do not seem to be commonly used in the nuclear industry. For example, the Nuclear Air Cleaning Handbook is an excellent design reference, but it fails to include information on computer codes that can be used to aid in the design process. These computer codes allow the analyst to use the handbook information to form all the elements of a complete system design. Because these analysis methods are in the form of computer codes they allow the analyst to investigate many alternative designs. In addition, the effects of many accident scenarios on the operation of the air cleaning system can be evaluated. These tools originally were intended for accident analysis, but they have been used mostly as design tools by several architect-engineering firms. The Cray, VAX, and personal computer versions of the codes, an accident analysis handbook, and the codes availability will be discussed. The application of these codes to several design operations of nuclear facilities will be illustrated, and their use to analyze the effect of several accident scenarios also will be described

  1. Motivations for self-regulation: The clean air action plan

    International Nuclear Information System (INIS)

    Giuliano, Genevieve; Linder, Alison

    2013-01-01

    In the fall of 2006 the Ports of Long Beach and Los Angeles announced the Clean Air Action Plan (CAAP). Its intent was to greatly accelerate emissions reductions from port activities. The CAAP was unprecedented in several ways: it was a voluntary agreement between two competing ports; it was achieved with the cooperation of local, state and federal agencies; it promised large particulate emissions reductions along with continued port growth, and it had a price tag of $2.1 billion. What explains the Ports’ decision to implement the CAAP? We conduct a case study to explore alternative explanations for the CAAP. Using data from interviews, media, and the history of events leading up to the CAAP, we find that the CAAP was a strategic response to social and political pressures that had built up over the previous decade. Its intent was to respond to local concerns and reduce opposition to port growth. The CAAP represents an example of the potential of voluntary efforts to solve environmental problems. - Highlights: • We conduct a case study of self-regulation for emissions reduction at seaports in Southern California. • We examine motivations for implementing the Clean Air Action Plan. • We find that social and political pressures were the main motivators, with regulatory threats a contributing factor. • The Clean Air Action Plan is a powerful example of the potential of voluntary strategies

  2. Air Cleaning Devices for HVAC Supply Systems in Schools. Technical Bulletin.

    Science.gov (United States)

    Wheeler, Arthur E.

    Guidelines for maintaining indoor air quality in schools with HVAC air cleaning systems are provided in this document. Information is offered on the importance of air cleaning, sources of air contaminants and indoor pollutants, types of air cleaners and particulate filters used in central HVAC systems, vapor and gas removal, and performance…

  3. Clean air and energy: from conflict to reconciliation

    International Nuclear Information System (INIS)

    Kolstad, C.D.; Schulze, W.D.; Williams, M.D.

    1982-01-01

    Unconstrained energy resource development in the Rocky Mountain west is likely to threaten the environment and the health and well-being of the people. Impacts may be associated with visibility degradation, toxic concentrations of gases, and deposition of acidic or toxic substances. Because the possible benefits of energy development in the region are very large, there is great concern that constraints imposed by air quality regulation may preclude the use of important resources or make unduly expensive energy produced from the region. The conflict between energy and clean air in the region is exacerbated by non-energy sources, such as copper smelters and urban areas, that already pose significant environmental threats. The hard policy question is not how to preserve clean air resources or how to develop energy but how to achieve and balance both goals. The effects and regulatory costs and benefits of air pollution control are discussed, and policy directions to protect air quality while pursuing energy development are presented

  4. The Clean Air Act Amendments of 1990 - Implementation

    International Nuclear Information System (INIS)

    Radford, N.D. Jr.

    1991-01-01

    On November 15, 1991 the Clean Air Act Amendments of 1990 were signed into law. The Amendments include eleven titles. They are: Title I specifies the requirements for attainment and maintenance of the national ambient air quality standards; Title II provides for more stringent motor vehicle emission limits and cleaner vehicle fuels; Title III addresses the release of air toxics; Title IV creates an acid deposition control program; Title V imposes a new comprehensive operating permit system for stationary sources; Title VI provides for stratospheric ozone protection; Title VII imposes increased civil and criminal penalties and liability; Title VIII contains miscellaneous provisions. Title IX provides for air quality research projects; Title X directs the EPA to make ten percent of research funds available to disadvantaged businesses; and Title XI amends the Job Training Partnership Act

  5. Tools for Predicting Cleaning Efficiency in the LHC

    CERN Document Server

    Assmann, R W; Brugger, M; Hayes, M; Jeanneret, J B; Kain, V; Kaltchev, D I; Schmidt, F

    2003-01-01

    The computer codes SIXTRACK and DIMAD have been upgraded to include realistic models of proton scattering in collimator jaws, mechanical aperture restrictions, and time-dependent fields. These new tools complement long-existing simplified linear tracking programs used up to now for tracking with collimators. Scattering routines from STRUCT and K2 have been compared with one another and the results have been cross-checked to the FLUKA Monte Carlo package. A systematic error is assigned to the predictions of cleaning efficiency. Now, predictions of the cleaning efficiency are possible with a full LHC model, including chromatic effects, linear and nonlinear errors, beam-beam kicks and associated diffusion, and time-dependent fields. The beam loss can be predicted around the ring, both for regular and irregular beam losses. Examples are presented.

  6. Performance evaluation of control room HVAC and air cleaning systems under accident conditions

    International Nuclear Information System (INIS)

    Almerico, F.; Machiels, A.J.; Ornberg, S.C.; Lahti, G.P.

    1985-01-01

    In light water reactors, control rooms and technical support centers must be designed to provide habitable environments in accordance with the requirements specified in General Design Criterion 19 of Appendix A, 10 CFR Part 50. Therefore, the effectiveness of HVAC and air cleaning system designs with respect to plant operator protection has to be evaluated by the system designer. Guidance for performing the analysis has been previously given in ANSI/ASME N509-1980 as well as in presentations at past Air Cleaning Conferences. The previous work is extended and the methodology used in a generic, interactive computer program that performs Main Control Room and Technical Support Center (TSC) habitability analyses for LWR nuclear power plants is presented. For given accident concentrations of radionuclides or hazardous gases in the outdoor air intakes and plant spaces surrounding the Main Control Room (or TSC), the program models the performance of the HVAC and air cleaning system designs, and determines control room (or TSC) contaminant concentrations and plant operator protection factors. Calculated or actual duct leakage, air cleaning efficiency, and airborne contamination are taken into account. Flexibility of the model allows for the representation of most control rooms (or TSC) and associated HVAC and air cleaning system conceptual designs that have been used by the US architect/engineers. The program replaced tedious calculations to determine the effects of HVAC ductwork and equipment leakage and permits (1) parametric analyses of various HVAC system design options early in the conceptual phase of a project, and (2) analysis of the effects of leakage test results on contaminant room concentrations, and therefore operator doses

  7. Monitor Clean and Efficient. Current state of affairs 2010

    International Nuclear Information System (INIS)

    Gerdes, J.

    2010-04-01

    This is the second report of the annual Monitor of the Dutch Clean and Efficient programme. The monitoring focuses on the development of target variables, effects, results and progress of the process. Most of the data regarding the results and effects concern the period until the end of 2009. Some data are not yet available for 2009 and can therefore only be provided for the preceding years. [nl

  8. Proceedings of the clean air and climate change summit

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2010-07-01

    The Clean Air Partnership was established in the Greater Toronto Area (GTA) over 10 years ago to work on issues related to air pollution and climate change. This summit presented details of the partnership's municipal activities and provided an outline of various projects conducted to reduce air pollution, increase the use of green energy, and encourage residents to reduce their ecological footprint. Climate change was discussed in relation to the recent economic crisis and recently discovered problems related to ocean acidification. The International Energy Agency (IEA) annual report was discussed in relation to peak oil and future economic crises. Advancements in green energy policy in Ontario were outlined. Sustainable housing and renewable energy projects in Germany were presented along with successful urban designs in Melbourne, New York City, and Denver. The GTA-CAC inter-governmental declaration on clean air was discussed, and an interim progress report was presented. The summit concluded with a video presentation of a collaborative artistic piece about climate change and the Arctic. 11 figs.

  9. Proceedings of the clean air and climate change summit

    International Nuclear Information System (INIS)

    2010-01-01

    The Clean Air Partnership was established in the Greater Toronto Area (GTA) over 10 years ago to work on issues related to air pollution and climate change. This summit presented details of the partnership's municipal activities and provided an outline of various projects conducted to reduce air pollution, increase the use of green energy, and encourage residents to reduce their ecological footprint. Climate change was discussed in relation to the recent economic crisis and recently discovered problems related to ocean acidification. The International Energy Agency (IEA) annual report was discussed in relation to peak oil and future economic crises. Advancements in green energy policy in Ontario were outlined. Sustainable housing and renewable energy projects in Germany were presented along with successful urban designs in Melbourne, New York City, and Denver. The GTA-CAC inter-governmental declaration on clean air was discussed, and an interim progress report was presented. The summit concluded with a video presentation of a collaborative artistic piece about climate change and the Arctic. 11 figs.

  10. Eastern States Harness Clean Energy to Promote Air Quality

    Energy Technology Data Exchange (ETDEWEB)

    2007-10-01

    States on the East Coast are including renewable energy and energy efficiency projects into their air quality plans that they submit to the EPA to address nonattainment for nitrogen oxides and other pollutants.

  11. Phase I Recommendations by the Air Quality Management Work Group to the Clean Air Act Advisory Committee

    Science.gov (United States)

    Recommendations to the Clean Air Act Advisory Committee by Air Quality Management Work Group addressing the recommendations made by the National Research Council to improve the U.S. air quality management system.

  12. Will the US Clean Air Act come to Australia?

    International Nuclear Information System (INIS)

    Saxby, Bill

    1992-01-01

    This article examines the Clean Air Act and whether the emerging situation in Sydney and Melbourne is likely to require similar radical action to prevent a decline in public health of city dwellers. It is concluded that both Sydney and Melbourne are in the league of the world's polluted cities. The pollutants of concern are mainly carbon monoxide and ozone. Emissions reduction in these two cities during the 1980s has reduced photochemical smog formation to near the guidelines, but both these cities retain the potential to form high levels of photochemical smog under the right weather conditions, as shown by Sydney in 1990. 2 tabs., ills

  13. Air-cleaning devices for vented filtered LMFBR containment

    International Nuclear Information System (INIS)

    Muhlestein, L.D.; Hilliard, R.K.

    1982-07-01

    An effort lasting several years is summarized which evaluated, developed and tested air cleaning devices for potential use in breeder reactor containment venting applications. State-of-technology evaluations were completed for both a hypothetical head release accident and a primary vessel melt-through accident. Commercially available systems or components were tested which included HEPA filters, sand and gravel beds, and aqueous scrubbers. Large-scale demonstration tests were completed and results are presented for two- and three-stage conventional aqueous scrubber systems; and for a newly developed passive, submerged gravel scrubber

  14. Investigation of air cleaning system response to accident conditions

    International Nuclear Information System (INIS)

    Andrae, R.W.; Bolstad, J.W.; Foster, R.D.; Gregory, W.S.; Horak, H.L.; Idar, E.S.; Martin, R.A.; Ricketts, C.I.; Smith, P.R.; Tang, P.K.

    1980-01-01

    Air cleaning system response to the stress of accident conditions are being investigated. A program overview and hghlight recent results of our investigation are presented. The program includes both analytical and experimental investigations. Computer codes for predicting effects of tornados, explosions, fires, and material transport are described. The test facilities used to obtain supportive experimental data to define structural integrity and confinement effectiveness of ventilation system components are described. Examples of experimental results for code verification, blower response to tornado transients, and filter response to tornado and explosion transients are reported

  15. The actual practice of air cleaning in Belgian nuclear facilities

    Energy Technology Data Exchange (ETDEWEB)

    Goossens, W.R. [PEGO, Mol (Belgium)

    1995-02-01

    With 60% of its power generation from nuclear stations Belgium has 7 nuclear power stations in operation with a total capacity of 5.4 MWe. Enriched uranium is imported and converted to fuel assemblies. The actinides of reprocessed fuel are recycled as MOX fuel. A main waste conditioning operation has been performed in the PAMELA vitrifier. The actual practice of nuclear air cleaning in the Belgian PWR station DOEL-4 and in the PAMELA -vitrification plant for high level liquid waste is reviewed.

  16. Experimental Study on Indoor Air Cleaning Technique of Nano-Titania Catalysis Under Plasma Discharge

    International Nuclear Information System (INIS)

    Gao Deli; Yang Xuechang; Zhou Fei; Wu Yuhuang

    2008-01-01

    In this study, a new technique of air cleaning by plasma combined with catalyst was proposed, which consisted of electrostatic precipitation, volatile organic compounds (VOCs) decomposition and sterilization. A novel indoor air purifier based on this technique was adopted. The experimental results showed that formaldehyde decomposition by the plasma-catalyst hybrid system was more efficient than that by plasma only. Positive discharge was better than negative discharge in formaldehyde removal. Meanwhile, the outlet concentration of ozone byproduct was effectively reduced by the nano-titania catalyst.

  17. Air-cleaning philosophy in a nuclear-materials fabrication plant

    International Nuclear Information System (INIS)

    Ward, F.Y.; Yoder, R.E.

    1982-01-01

    At the Department of Energy's Rocky Flats Plant there is a major ventilation improvement project underway. To achieve the desired goals of ALARA regarding radioactivity and toxic material releases and natural phenomena insults, a comprehensive air-cleaning philosophy and policy statement was developed. Design of the upgraded systems were evaluated against these statements and we believe that upon completion of the projects that an efficient system will be demonstrated. the design permits reuse and heat recovery of ventilation air, the optimization of sampling points to reduce analytical laboratory services. This paper discusses the basis of the philosophy and the engineering features incorporated to meet this stated objective. Points of compromise are noted

  18. Emission allowance trading under the Clean Air Act Amendments: An incentive mechanism for the adoption of Clean Coal Technologies

    International Nuclear Information System (INIS)

    South, D.W.; McDermott, K.A.

    1993-01-01

    Title IV of the Clean Air Act Amendments of 1990 (P.L. 101-549) uses tradeable SO 2 allowances as a means of reducing acidic emissions from the electricity generating industry. The use of emission allowances generates two important results; first, utilities are given the flexibility to choose their optimal (least cost) compliance strategies and second, the use of emission allowances creates greater incentives for the development and commercialization of innovative emissions control technology. Clean Coal Technologies (CCTs) are able to generate electricity more efficiently, use a wide variety of coal grades and types, and dramatically reduce emissions of SO 2 , NO x , CO 2 , and PM per kWh. However, development and adoption of the technology is limited by a variety of regulatory and technological risks. The use of SO 2 emission allowances may be able to provide incentives for utility (and nonutility) adoption of this innovative technology. Emission allowances permit the utility to minimize costs on a systemwide basis and provides rewards for addition emission reductions. As CCTs are a more efficient and low emitting source of electricity, the development and implementation of this technology is desirable. This paper will explore the relationship between the incentives created by the SO 2 allowance market and CCT development. Regulatory hindrances and boons for the allowance market shall also be identified to analyze how market development, state mandates, and incentive regulation will effect the ability of allowances to prompt CCT adoption

  19. Toronto 2001 Inter-governmental Declaration on Clean Air

    International Nuclear Information System (INIS)

    2001-01-01

    This formal declaration commits the municipalities in the Greater Toronto Area, the provincial government of Ontario, and the federal government in Ottawa to undertake certain specific actions to improve air quality in their respective areas of jurisdiction, recognizing the validity of claims made by experts in numerous studies, linking air pollution to premature deaths, illnesses and hospitalization in major Canadian cities. The declaration also recognizes the validity of scientific claims as to the relationship between solar radiation, ambient heat, ground level ozone and global climate change, and the role played in air pollution by fossil fuel combustion. The Declaration calls for cooperation of all governments operating in the Greater Toronto Area to take inter-governmental actions to improve air quality by following up on key issues identified at annual Summits and by supporting the planning of future Summits, by working together with the Toronto Organizing Committee for the Olympic Games to ensure that the 2008 Olympic Games will contribute to a legacy of clean air for the Toronto region, and by implementing a social marketing campaign to help householders reduce both home energy use and vehicle kilometres travelled by 20 per cent. Beyond these inter-governmental commitments, special commitments of individual municipalities, and the provincial and federal governments also form part of the Declaration

  20. USNRC regulatory guidance for engineered safety feature air cleaning systems

    International Nuclear Information System (INIS)

    Bellamy, R.R.

    1991-01-01

    The need for clear, technically appropriate, and easily implementable guidance for the design, testing, and maintenance of nuclear air cleaning systems has long been recognized. Numerous industry consensus standards have been issued and revised over the last 30 years. Guidance has also been published by the US Nuclear Regulatory Commission in the form of regulations, regulatory guides, standard review plans, NUREG documents, and information notices. This paper will summarize the latest revisions to these documents and emphasize Regulatory Guide 1.52, Design, Testing, and Maintenance Criteria for Post-Accident Engineered-Safety-Feature Atmosphere Cleanup System Air Filtration and Adsorption Units of Light-Water-Cooled Nuclear Power Plants, which was last revised in 1978. The USNRC has undertaken a project to revise this regulatory guide, and the status of that revision is highlighted

  1. 76 FR 68381 - Approval and Promulgation of Air Quality Implementation Plans; Pennsylvania; Pennsylvania Clean...

    Science.gov (United States)

    2011-11-04

    ... Promulgation of Air Quality Implementation Plans; Pennsylvania; Pennsylvania Clean Vehicles Program AGENCY... Implementation Plan (SIP) revision submitted by the Commonwealth of Pennsylvania. This SIP revision contains Pennsylvania's Clean Vehicle Program, which adopts California's second generation low emission vehicle program...

  2. A comparative study on laser induced shock cleaning of radioactive contaminants in air and water

    Science.gov (United States)

    Kumar, Aniruddha; Prasad, Manisha; Bhatt, R. B.; Behere, P. G.; Biswas, D. J.

    2018-03-01

    Efficient removal of Uranium-di-oxide (UO2) particulates from stainless steel surface was effected by Nd-YAG laser induced plasma shock waves in air as well as in water environment. The propagation velocity of the generated shock wave was measured by employing the photo-acoustic probe deflection method. Monitoring of the alpha activity of the sample with a ZnS (Ag) scintillation detector before and after the laser exposure allowed the estimation of decontamination efficiency defined as the percentage removal of the initial activity. Experiments were carried out to study the effect of laser pulse energy, number of laser exposures, orientation of the sample, the separation between the substrate surface and the onset point of the shock wave on the de-contamination efficiency. The most optimised cleaning was found to occur when the laser beam impinged normally on the sample that was immersed in water and placed at a distance of ∼0.7 mm from the laser focal spot. Analysis of the cleaned surface by optical microscopes established that laser induced shock cleaning in no way altered the surface property. The shock force generated in both air and water has been estimated theoretically and has been found to exceed the Van der Waal's binding force for spherical contaminant particulate.

  3. Krakow clean fossil fuels and energy efficiency project

    Energy Technology Data Exchange (ETDEWEB)

    Butcher, T.A.; Pierce, B.L. [Brookhaven National Lab., Upton, NY (United States)

    1995-11-01

    The Support for Eastern European Democracy (SEED) Act of 1989 directed the U.S. Department of Energy (DOE) to undertake an equipment assessment project aimed at developing the capability within Poland to manufacture or modify industrial-scale combustion equipment to utilize fossil fuels cleanly. This project is being implemented in the city of Krakow as the `Krakow Clean Fossil Fuels and Energy Efficiency Project.` Funding is provided through the U.S. Agency for International Development (AID). The project is being conducted in a manner that can be generalized to all of Poland and to the rest of Eastern Europe. The historic city of Krakow has a population of 750,000. Almost half of the heating energy used in Krakow is supplied by low-efficiency boilerhouses and home coal stoves. Within the town, there are more than 1,300 local boilerhouses and 100,000 home stoves. These are collectively referred to as the `low emission sources` and they are the primary sources of particulates and hydrocarbon emissions in the city and major contributors of sulfur dioxide and carbon monoxide.

  4. 77 FR 41930 - Bleed Air Cleaning and Monitoring Equipment and Technology

    Science.gov (United States)

    2012-07-17

    .... Bill 658, requires the FAA to identify bleed air purification technology. Specifically, the FAA seeks... Administration 14 CFR Part 25 [Docket No. FAA-2012-0714] Bleed Air Cleaning and Monitoring Equipment and... developers, manufacturers, and the public related to effective air cleaning technology and sensor technology...

  5. 76 FR 76762 - Notice of Lodging of Consent Decree Under the Clean Air Act

    Science.gov (United States)

    2011-12-08

    ... recovery at no additional cost; (2) no longer accept small appliances, motor vehicle air conditioners... DEPARTMENT OF JUSTICE Notice of Lodging of Consent Decree Under the Clean Air Act Notice is hereby.... Environmental Protection Agency (``U.S. EPA''), sought penalties and injunctive relief under the Clean Air Act...

  6. 76 FR 57764 - Notice of Lodging of Consent Decree Under the Clean Air Act

    Science.gov (United States)

    2011-09-16

    ... recovery at no additional cost; (2) no longer accept small appliances, motor vehicle air conditioners... DEPARTMENT OF JUSTICE Notice of Lodging of Consent Decree Under the Clean Air Act Notice is hereby... Agency (``U.S. EPA''), sought penalties and injunctive relief under the Clean Air Act (``CAA'') against...

  7. 77 FR 23278 - Notice of Lodging of Consent Decree Under the Clean Air Act

    Science.gov (United States)

    2012-04-18

    ... accept small appliances, motor vehicle air conditioners (``MVACs''), or MVAC- like appliances with cut... DEPARTMENT OF JUSTICE Notice of Lodging of Consent Decree Under the Clean Air Act Notice is hereby... Agency (``U.S. EPA''), sought penalties and injunctive relief under the Clean Air Act (``CAA'') against...

  8. Chicago Clean Air, Clean Water Project: Environmental Monitoring for a Healthy, Sustainable Urban Future

    Energy Technology Data Exchange (ETDEWEB)

    none, none; Tuchman, Nancy [Institute of Environmental Sustainability (IES), Chicago, IL (United States)

    2015-11-11

    The U.S. Department of Energy awarded Loyola University Chicago and the Institute of Environmental Sustainability (IES) $486,000.00 for the proposal entitled “Chicago clean air, clean water project: Environmental monitoring for a healthy, sustainable urban future.” The project supported the purchase of analytical instruments for the development of an environmental analytical laboratory. The analytical laboratory is designed to support the testing of field water and soil samples for nutrients, industrial pollutants, heavy metals, and agricultural toxins, with special emphasis on testing Chicago regional soils and water affected by coal-based industry. Since the award was made in 2010, the IES has been launched (fall 2013), and the IES acquired a new state-of-the-art research and education facility on Loyola University Chicago’s Lakeshore campus. Two labs were included in the research and education facility. The second floor lab is the Ecology Laboratory where lab experiments and analyses are conducted on soil, plant, and water samples. The third floor lab is the Environmental Toxicology Lab where lab experiments on environmental toxins are conducted, as well as analytical tests conducted on water, soil, and plants. On the south end of the Environmental Toxicology Lab is the analytical instrumentation collection purchased from the present DOE grant, which is overseen by a full time Analytical Chemist (hired January 2016), who maintains the instruments, conducts analyses on samples, and helps to train faculty and undergraduate and graduate student researchers.

  9. Socio-economic considerations of cleaning Greater Vancouver's air

    International Nuclear Information System (INIS)

    2005-08-01

    Socio-economic considerations of better air quality on the Greater Vancouver population and economy were discussed. The purpose of the study was to provide socio-economic information to staff and stakeholders of the Greater Vancouver Regional District (GVRD) who are participating in an Air Quality Management Plan (AQMP) development process and the Sustainable Region Initiative (SRI) process. The study incorporated the following methodologies: identification and review of Canadian, American, and European quantitative socio-economic, cost-benefit, cost effectiveness, competitiveness and health analyses of changes in air quality and measures to improve air quality; interviews with industry representatives in Greater Vancouver on competitiveness impacts of air quality changes and ways to improve air quality; and a qualitative analysis and discussion of secondary quantitative information that identifies and evaluates socio-economic impacts arising from changes in Greater Vancouver air quality. The study concluded that for the Greater Vancouver area, the qualitative analysis of an improvement in Greater Vancouver air quality shows positive socio-economic outcomes, as high positive economic efficiency impacts are expected along with good social quality of life impacts. 149 refs., 30 tabs., 6 appendices

  10. Design of off-gas and air cleaning systems at nuclear power plants

    International Nuclear Information System (INIS)

    1987-01-01

    The primary purpose of this report is to describe the current design of air and process off-gas cleaning technologies used in nuclear power plants (NPPs). Because of the large inventory of fission products that are produced in the fuel (i.e. in the range of 5x10 19 Bq per GW(e)·a) and the highly restrictive airborne radionuclide release limits being established by Member States, air and process off-gas cleaning technologies are constantly being improved to provide higher airborne radionuclide recovery efficiencies and a smaller probability of malfunction. For various technologies considered an attempt has been made to provide the following information: (a) Process description in terms of principles of off-gas and air cleaning, operating parameters and system performance; (b) Design for normal and accident situations; (c) Design of components with regard to construction materials, size, shape and geometry of the system, resistance to chemical and physical degradation from the operational environment, safety and quality assurance requirements

  11. Complying with Clean Air Act acid rain provisions: A case history of required air quality analyses

    International Nuclear Information System (INIS)

    McComb, G.G. Jr.; Naperkoski, G.J.; Rogers, F.A.

    1990-01-01

    Clean Air Act Amendments being considered by Congress require SO 2 emissions reductions from numerous large power generation sources nationwide. As currently written, these amendments also require that the affected sources must continue to comply with all provisions of the existing Clean Air Act while achieving the required reductions. United Engineers and Constructors is presently assisting utilities in the evaluation of compliance options for units totaling over 18,000 MW. The methods of achieving compliance with the probable requirements of the Act most often include the retrofit installation of SO 2 scrubbers. A study designed to determine permitting issues and the scope of air quality analyses required to demonstrate the regulatory acceptability of installation of wet scrubbing systems has been completed for units totaling a portion of the above-referenced 18,000 MW. The study results show that, under certain commonly occurring circumstances, there is a risk of creating National Ambient Air Quality Standards contraventions for SO 2 and NO 2 when scrubbers are installed at an existing facility. Any such contraventions subject the plant to state and/or federal enforcement actions. In addition, installation of materials handling equipment for lime stone can trigger Prevention of Significant Deterioration requirements as a major modification. This paper is divided into two major areas. The first deals with the air quality regulatory requirements imposed upon installation of pollution control equipment. The first section is further sub-divided into two sections: one covering requirements emanating from the 1977 Clean Air Act Amendments and its implementing regulations and the other the regulatory requirements of the new Clean Air Act Amendments. This section on regulatory requirements provides background information for the understanding of the second major section of the paper which gives the results of the hypothetical case study

  12. Proceedings of the 21st DOE/NRC Nuclear Air Cleaning Conference

    International Nuclear Information System (INIS)

    First, M.W.; Harvard Univ., Boston, MA

    1991-02-01

    Separate abstracts have been prepared for the papers presented at the meeting on nuclear facility air cleaning technology in the following specific areas of interest: air cleaning technologies for the management and disposal of radioactive wastes; Canadian waste management program; radiological health effects models for nuclear power plant accident consequence analysis; filter testing; US standard codes on nuclear air and gas treatment; European community nuclear codes and standards; chemical processing off-gas cleaning; incineration and vitrification; adsorbents; nuclear codes and standards; mathematical modeling techniques; filter technology; safety; containment system venting; and nuclear air cleaning programs around the world. (MB)

  13. Proceedings of the 21st DOE/NRC Nuclear Air Cleaning Conference; Sessions 1--8

    Energy Technology Data Exchange (ETDEWEB)

    First, M.W. [ed.] [Harvard Univ., Boston, MA (United States). Harvard Air Cleaning Lab.

    1991-02-01

    Separate abstracts have been prepared for the papers presented at the meeting on nuclear facility air cleaning technology in the following specific areas of interest: air cleaning technologies for the management and disposal of radioactive wastes; Canadian waste management program; radiological health effects models for nuclear power plant accident consequence analysis; filter testing; US standard codes on nuclear air and gas treatment; European community nuclear codes and standards; chemical processing off-gas cleaning; incineration and vitrification; adsorbents; nuclear codes and standards; mathematical modeling techniques; filter technology; safety; containment system venting; and nuclear air cleaning programs around the world. (MB)

  14. The importance of damper drive performance for clean air

    International Nuclear Information System (INIS)

    Wistrom, K.

    2002-01-01

    Amendments to the U.S. Federal Clean Air Act require petroleum refineries and other industries to examine every aspects of their process heating operations in order to reduce cumulative nitrogen oxide emissions from their plants. It has been found that changing the final damper control elements to more reliable and accurate damper drives greatly improves the combustion of air and flue gases and reduces tramp air from entering furnaces. This paper discusses the increasing importance of precise damper drives in nitrogen oxides reduction efforts, and the challenges involved in effecting good damper control. It also provides some technical details about final control drives, manufactured by TYPE K Damper Drives, a division of Controls International Inc., that thrive in environments of extreme temperatures, heavy vibration and fly ash, while providing continuous duty service with smooth, accurate and repeatable damper positioning. Case history of an Ontario oil refinery installing several damper drives designed by TYPE K, indicating high level of nitrogen oxides reduction is described to illustrate the importance and the advantages of damper control drives designed by this firm. In addition to meeting regulatory requirements, additional benefits include improved product quality and safety levels, combined with lower maintenance expenses. photos

  15. Impact of clean air legislation on the petroleum industry

    International Nuclear Information System (INIS)

    Driscoll, J.G.

    1991-01-01

    As the 1990s begin, the petroleum refining and marketing industry faces an unprecedented number of environmental issues that, combined, will bring major changes in the fundamentals of the business by the turn of the century. The following background on the history of environmentally driven change in the oil business provides a broad view of current environmental laws and regulations, while addressing timing and general impacts on the downstream segment. It will then focus on the Clean Air Act of 1990, providing information on the range of areas this comprehensive legislative initiative will regulate. Finally, the discussion narrows to the mobile source provisions of the act. It is through this section that the most foundational changes in our business will occur. In this paper the nature of those changes are discussed, and a short list of issues with potential for significant impact on a global basis are covered

  16. Air and gas cleaning methods for reactor containment vessels

    Energy Technology Data Exchange (ETDEWEB)

    Silverman, L.

    1963-11-15

    In this paper, a survey is made of the existing and some proposed new methods for the control and purification of air and gases which might be released from a reactor contained or confined for protection of the health and safety of the public from potential accidents. The difference between confinement and containment concepts must be considered. The problems involved and the need for decontamination, site selection, exclusion area, population density, distance, etc., have been discussed elsewhere. We propose to discuss here the safety measures necessary to control the release of radioactive materials to the environment. This requires special systems which must function effectively to minimize loss of fission products such as halogens and particulates. These can penetrate the confinement filters or the containment vessel to a limited extent even after cleaning.

  17. Clean Air for London (CLEARFLO) Final Campaign Summary

    Energy Technology Data Exchange (ETDEWEB)

    Worsnop, D. R. [Aerodyne Research, Inc., Billerica, MA (United States); Williams, L. R. [Aerodyne Research, Inc., Billerica, MA (United States); Herndon, S. C. [Aerodyne Research, Inc., Billerica, MA (United States); Dubey, M. [Los Alamos National Lab. (LANL), Los Alamos, NM (United States); Ng, N. L. [Georgia Inst. of Technology, Atlanta, GA (United States); Thornton, J. [Univ. of Washington, Seattle, WA (United States); Knighton, B. [Montana State Univ., Bozeman, MT (United States); Coulter, R. [Argonne National Lab. (ANL), Argonne, IL (United States); Prévôt, Ash [Paul Scherrer Inst. (PSI), Villigen (Switzerland)

    2016-03-01

    This field campaign funded the participation of scientists from seven different research groups and operated over thirty instruments during the Winter Intensive Operating Period (January-February 2012) of the Clean Air for London (ClearfLo) campaign. The campaign took place at a rural site in Detling, UK, 45 kilometers southeast of central London. The primary science questions for the ClearfLo winter IOP (intensive operational periods) were: 1) “what is the urban increment of particulate matter (PM) and other pollutants in the greater London area?” and 2) “what is the contribution of solid fuel use for home heating to wintertime PM?” An additional motivation for the Detling measurements was the question of whether coatings on black carbon particles enhance absorption.

  18. Consistent approach to air-cleaning system duct design

    International Nuclear Information System (INIS)

    Miller, W.H.; Ornberg, S.C.; Rooney, K.L.

    1981-01-01

    Nuclear power plant air-cleaning system effectiveness is dependent on the capability of a duct system to safely convey contaminated gas to a filtration unit and subsequently to a point of discharge. This paper presents a logical and consistent design approach for selecting sheet metal ductwork construction to meet applicable criteria. The differences in design engineers' duct construction specifications are acknowledged. Typical duct construction details and suggestions for their effective use are presented. Improvements in duct design sections of ANSI/ASME N509-80 are highlighted. A detailed leakage analysis of a control room HVAC system is undertaken to illustrate the effects of conceptual design variations on duct construction requirements. Shortcomings of previously published analyses and interpretations of a current standard are included

  19. Citizen Science Air Sensor Project with Clean Air Carolina and the Eastern Band of Cherokee Indians Fact Sheet

    Science.gov (United States)

    EPA scientists are partnering with Clean Air Carolina (CAC) in Charlotte, N.C., and the Eastern Band of Cherokee Indians (EBCI) in Cherokee, N.C., to conduct a citizen science air quality project in these regions.

  20. Notification: Background Investigation Services EPA’s Efforts to Incorporate Environmental Justice Into Clean Air Act Inspections for Air Toxics

    Science.gov (United States)

    Project #OPE-FY14-0017, March 7, 2014. The OIG plans to begin the preliminary research phase of an evaluation of the EPA's efforts to incorporate environmental justice into Clean Air Act (CAA) inspections for air toxics.

  1. Experimental analysis of indoor air quality improvement achieved by using a Clean-Air Heat Pump (CAHP) air-cleaner in a ventilation system

    DEFF Research Database (Denmark)

    Sheng, Ying; Fang, Lei; Nie, Jinzhe

    2017-01-01

    This study investigated the air purification effect of a Clean-Air Heat Pump (CAHP) air-cleaner which combined a silica gel rotor with a heat pump to achieve air cleaning, heating and ventilation in buildings. The experiments were conducted in a field laboratory and compared a low outdoor air...... supply rate with CAHP air purification of recirculated air with three different outdoor air supply rates without recirculation or air cleaning. Sensory assessments of perceived air quality and chemical measurements of TVOC concentration were used to evaluate the air-cleaning performance of the CAHP....... The results of the experiment showed that the operation of the CAHP significantly improved the perceived air quality in a room polluted by both human bio-effluents and building materials. At the outdoor airflow rate of 2 L/s per person, the indoor air quality with CAHP was equivalent to what was achieved...

  2. Removal of mercury vapor from ambient air of dental clinics using an air cleaning system based on silver nanoparticles

    Directory of Open Access Journals (Sweden)

    Chiman Saeidi

    2015-06-01

    Full Text Available Background & objective: Mercury is a toxic and bio-accumulative pollutant that has adverse effects on environmental and human health. There have been a number of attempts to regulate mercury emissions tothe atmosphere. Silver nanoparticles are a number of materials that have highly potential to absorb mercury and formation of mercury amalgam.The aim of this study is removal of mercury vapors in the dental clinic using a n a ir cleaning system based on silver nanoparticles. Methods: In this study, silver nanoparticles coated on the bed of foam and chemical and structural properties were determined using a number of methods such as UV-VIS-NIR spectroscopy and Scanning Electron Microscope (SEM connected the X-ray Emission Spectroscopy Energy (EDS. The a ir cleaning system efficiency to remove of the mercury vapor in simulated conditions in the laboratory and real conditions in the dental clinicwere measured by Cold Vapor Atomic Absorption Spectroscopy (CVAAS. Results: The images of SEM, showed that average sizeof silver nanoparticles in colloidal solution was ∼ 30nm and distribution of silver nanoparticles coated on foam was good. EDS spectrum confirmed associated the presence of silver nanoparticles coated on foam. The significantly difference observed between the concentration of mercury vapor in the off state (9.43 ± 0.342 μg.m-3 and on state (0.51 ± 0.031μg.m-3 of the a ir cleaning system. The mercury vapor removal efficiencyof the a ir cleaning system was calculated 95%. Conclusion : The air cleaning system based on foam coated by silver nanoparticles, undertaken to provide the advantages such as use facilitating, highly efficient operational capacity and cost effective, have highly sufficiency to remove mercury vapor from dental clinics.

  3. High Efficiency Room Air Conditioner

    Energy Technology Data Exchange (ETDEWEB)

    Bansal, Pradeep [Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States)

    2015-01-01

    This project was undertaken as a CRADA project between UT-Battelle and Geberal Electric Company and was funded by Department of Energy to design and develop of a high efficiency room air conditioner. A number of novel elements were investigated to improve the energy efficiency of a state-of-the-art WAC with base capacity of 10,000 BTU/h. One of the major modifications was made by downgrading its capacity from 10,000 BTU/hr to 8,000 BTU/hr by replacing the original compressor with a lower capacity (8,000 BTU/hr) but high efficiency compressor having an EER of 9.7 as compared with 9.3 of the original compressor. However, all heat exchangers from the original unit were retained to provide higher EER. The other subsequent major modifications included- (i) the AC fan motor was replaced by a brushless high efficiency ECM motor along with its fan housing, (ii) the capillary tube was replaced with a needle valve to better control the refrigerant flow and refrigerant set points, and (iii) the unit was tested with a drop-in environmentally friendly binary mixture of R32 (90% molar concentration)/R125 (10% molar concentration). The WAC was tested in the environmental chambers at ORNL as per the design rating conditions of AHAM/ASHRAE (Outdoor- 95F and 40%RH, Indoor- 80F, 51.5%RH). All these modifications resulted in enhancing the EER of the WAC by up to 25%.

  4. Testing on air cleaning systems: Testing of the components in-place tests

    International Nuclear Information System (INIS)

    Billard, F.; Brion, J.

    1967-01-01

    The reliability of air cleaning systems is dependent on testing they are submitted to. Although in-place tests are the most important as they act as final tests upon achieved plants, component tests are necessary too. They allow detection of defective units before they are installed, partition of unit defects from mounting defects and they are more sensitive. For similar reasons, material teats are most useful. The various tests are described, about aerosol filters for one part, iodine trap for the other. The checked features are: materials nature, units sizes, efficiency, air resistance, flammability, humidity resistance, temperature resistance, adsorbent friability, etc... On iodine trapping systems, small check traps, working by-pass with the main trap are periodically subjected to efficiency test. This control allow to cut down the in-place tests frequency, particularly when poisoning from organic vapours is to be feared. (authors) [fr

  5. Proceedings of the 24. DOE/NRC nuclear air cleaning and treatment conference

    International Nuclear Information System (INIS)

    First, M.W.

    1997-08-01

    This report contains the papers presented at the 24th DOE/NRC Nuclear Air Cleaning and Treatment Conference and the associated discussions. Major topics are: (1) nuclear air cleaning issues, (2) waste management, (3) instrumentation and measurement, (4) testing air and gas cleaning systems, (5) progress and challenges in cleaning up Hanford, (6) international nuclear programs, (7) standardized test methods, (8) HVAC, (9) decommissioning, (10) computer modeling applications, (11) adsorption, (12) iodine treatment, (13) filters, and (14) codes and standards for filters and adsorbers. Selected papers have been indexed separately for inclusion in the Energy Science and Technology Database

  6. Proceedings of the 24. DOE/NRC nuclear air cleaning and treatment conference

    Energy Technology Data Exchange (ETDEWEB)

    First, M.W. [ed.] [Harvard Univ., Boston, MA (United States). Harvard Air Cleaning Lab.

    1997-08-01

    This report contains the papers presented at the 24th DOE/NRC Nuclear Air Cleaning and Treatment Conference and the associated discussions. Major topics are: (1) nuclear air cleaning issues, (2) waste management, (3) instrumentation and measurement, (4) testing air and gas cleaning systems, (5) progress and challenges in cleaning up Hanford, (6) international nuclear programs, (7) standardized test methods, (8) HVAC, (9) decommissioning, (10) computer modeling applications, (11) adsorption, (12) iodine treatment, (13) filters, and (14) codes and standards for filters and adsorbers. Selected papers have been indexed separately for inclusion in the Energy Science and Technology Database.

  7. Establishing reliable good initial quantum efficiency and in-situ laser cleaning for the copper cathodes in the RF gun

    Energy Technology Data Exchange (ETDEWEB)

    Zhou, F., E-mail: zhoufeng@slac.stanford.edu; Sheppard, J.C.; Vecchione, T.; Jongewaard, E.; Brachmann, A.; Corbett, J.; Gilevich, S.; Weathersby, S.

    2015-05-21

    Establishing good initial quantum efficiency (QE) and reliable in-situ cleaning for copper cathode in the RF gun is of critical importance for the RF gun operations. Recent studies on the SLAC RF gun test bed indicated that the pre-cleaning (plasma cleaning) in the test chamber followed by copper cathode exposure to air for cathode change leads to a very low initial QE in the RF gun, and also demonstrated that without the pre-cleaning good initial QE >4×10{sup −5} can be routinely achieved in the RF gun with the cathodes of QE <1×10{sup −7} measured in the test chamber. QE can decay over the time in the RF gun. The in-situ laser cleaning technique for copper cathodes in the RF gun is established and refined in comparison to previous cleaning at the linac coherent light source, resulting in an improved QE and emittance evolutions. The physics of the laser cleaning process is discussed. It is believed that the reflectivity change is one of the major factors for the QE boost with the laser cleaning.

  8. 14 CFR 1274.926 - Clean Air-Water Pollution Control Acts.

    Science.gov (United States)

    2010-01-01

    ... 14 Aeronautics and Space 5 2010-01-01 2010-01-01 false Clean Air-Water Pollution Control Acts...-Water Pollution Control Acts. Clean Air-Water Pollution Control Acts July 2002 If this cooperative... 91-604) and section 308 of the Federal Water Pollution Control Act, as amended (33 U.S.C. 1251 et seq...

  9. 45 CFR 2543.86 - Clean Air Act and the Federal Water Pollution Control Act.

    Science.gov (United States)

    2010-10-01

    ... 45 Public Welfare 4 2010-10-01 2010-10-01 false Clean Air Act and the Federal Water Pollution... Water Pollution Control Act. Contracts and subgrants of amounts in excess of $100,000 shall contain a... regulations issued pursuant to the Clean Air Act (42 U.S.C. 7401 et seq.) and the Federal Water Pollution...

  10. Implementation of the clean air strategy for Alberta

    Energy Technology Data Exchange (ETDEWEB)

    Sandhu, H.S.; Angle, R.P. [Alberta Dept. of Environmental Protection, Alberta (Canada); Kelly, M. [Clean Air Strategic Alliance, Alberta (Canada)

    1995-12-31

    Air quality and its effects on the environment and human health have received considerable attention during the last three decades in Alberta, Canada. Among the issues receiving a high priority are acid deposition, smog and global warming. There are various sources of emissions to Alberta`s atmosphere, many of which relate to the extraction, processing, and burning of fossil fuels; pulp and paper manufacture; and transportation. There are also natural sources of contaminants, such as particulates from forest fires and methane from bogs. The extraction, processing and combustion of fossil fuels play an important role in Alberta`s economy. The province produces over 80 % of the oil and natural gas in Canada, and nearly half the coal. Low sulphur coal is used in power plants to supply more than 90 % of the electricity used in this province by nearly three million people. As a result, Alberta is responsible for about 27 % of the CO{sub 2}, 23 % of the nitrogen oxides, and 16 % of the SO{sub 2} emissions generated in Canada. Alberta`s air quality is monitored by the Government of Alberta at nine continuous, eight intermittent, over 250 static, and 12 precipitation monitoring stations. Parameters such as carbon monoxide, oxides of nitrogen, sulphur dioxide, particulates, and ion-content of precipitation are measured. Industry operates a large number of ambient and static SO{sub 2} and H{sub 2}S monitoring stations across Alberta, with monitoring costs estimated at 56-80 million USD annually. The unique features of the Clean Air Strategy for Alberta (CASA) have already been published elsewhere. This presentation discusses the mechanism and progress on its implementation. (author)

  11. Implementation of the clean air strategy for Alberta

    Energy Technology Data Exchange (ETDEWEB)

    Sandhu, H S; Angle, R P [Alberta Dept. of Environmental Protection, Alberta (Canada); Kelly, M [Clean Air Strategic Alliance, Alberta (Canada)

    1996-12-31

    Air quality and its effects on the environment and human health have received considerable attention during the last three decades in Alberta, Canada. Among the issues receiving a high priority are acid deposition, smog and global warming. There are various sources of emissions to Alberta`s atmosphere, many of which relate to the extraction, processing, and burning of fossil fuels; pulp and paper manufacture; and transportation. There are also natural sources of contaminants, such as particulates from forest fires and methane from bogs. The extraction, processing and combustion of fossil fuels play an important role in Alberta`s economy. The province produces over 80 % of the oil and natural gas in Canada, and nearly half the coal. Low sulphur coal is used in power plants to supply more than 90 % of the electricity used in this province by nearly three million people. As a result, Alberta is responsible for about 27 % of the CO{sub 2}, 23 % of the nitrogen oxides, and 16 % of the SO{sub 2} emissions generated in Canada. Alberta`s air quality is monitored by the Government of Alberta at nine continuous, eight intermittent, over 250 static, and 12 precipitation monitoring stations. Parameters such as carbon monoxide, oxides of nitrogen, sulphur dioxide, particulates, and ion-content of precipitation are measured. Industry operates a large number of ambient and static SO{sub 2} and H{sub 2}S monitoring stations across Alberta, with monitoring costs estimated at 56-80 million USD annually. The unique features of the Clean Air Strategy for Alberta (CASA) have already been published elsewhere. This presentation discusses the mechanism and progress on its implementation. (author)

  12. Evaluating The Operation Of Three Air Cleaners Working Individually In A Clean Room

    DEFF Research Database (Denmark)

    Ardkapan, Siamak Rahimi; Afshari, Alireza; Bergsøe, Niels Christian

    2011-01-01

    The use of portable air cleaners is becoming increasingly popular in many countries including Denmark. Portable air cleaners are known for not only removing but also generating particles and gases. To clarify this, three air cleaning technologies were evaluated. They were nonthermal plasma......, photochemical air purifier and corona discharge ionizer. The concentrations of ultrafine particles, ozone and total volatile organic compounds were measured both in a duct and in a clean room. It was found that the studied air cleaning technologies increased the ozone level in the clean room and the duct....... The increase of ozone level in the clean room was more than that was measured in the duct. Additionally, it was found that the number of ultrafine particles in the room increased due to the generated ozone. The number of generated particles changed with the season. The study leads to the recommendation...

  13. Fossil fuels and air pollution in USA after the Clean Air Act

    International Nuclear Information System (INIS)

    Chuveliov, A.V.

    1990-01-01

    This paper addresses environmental issues in the USA after the Clean Air Act. Economic damage assessment to population and environment due to air pollution from stationary and mobile sources producing and utilizing fossil fuels in the USA for the period of 1970--1986 is determined and discussed. A comparison of environmental damage assessments for the USA and USSR is provided. The paper also addresses ecologo-economical aspects of hydrogen energy and technology. The effectiveness of hydrogen use in ferrous metallurgy and motor vehicles in the USA is determined and discussed

  14. Development of filters for exhaust air or off-gas cleaning

    International Nuclear Information System (INIS)

    Wilhelm, J.

    1988-01-01

    The activities of the 'Laboratorium fuer Aerosolphysik und Filtertechnik II' of the 'Kernforschungszentrum Karlsruhe' concentrate on the development of filters to be used for cleaning nuclear and conventional exhaust air and off-gas. Originally, these techniques were intended to be applied in nuclear facilities only. Their application for conventional gas purification, however, has led to a reorientation of research and development projects. By way of example, it is reported about the use of the multi-way sorption filter for radioiodine removal in nuclear power plants and following flue-gas purification in heating power plants as well as for off-gas cleaning in chemical industry. The improvement of HEPA filters and the development of metal fibre filters has led to components which can be used in the range of high humidity and moisture as well as at high temperatures and an increased differential pressure. The experience obtained in the field of high-efficiency filtering of nuclear airborne particles is made use of during the investigations concerning the removal of particles of conventional pollutants in the submicron range. A technique of radioiodine removal and an improved removal of airborne particles has been developed for use in the future reprocessing plant. Thus, a maximum removal efficiency can be achieved and an optimum waste management is made possible. It is reported about the components obtained as a result of these activities and their use for off-gas cleaning in the Wackersdorf reprocessing plant (WAW). (orig.) [de

  15. Whole house particle removal and clean air delivery rates for in-duct and portable ventilation systems.

    Science.gov (United States)

    Macintosh, David L; Myatt, Theodore A; Ludwig, Jerry F; Baker, Brian J; Suh, Helen H; Spengler, John D

    2008-11-01

    A novel method for determining whole house particle removal and clean air delivery rates attributable to central and portable ventilation/air cleaning systems is described. The method is used to characterize total and air-cleaner-specific particle removal rates during operation of four in-duct air cleaners and two portable air-cleaning devices in a fully instrumented test home. Operation of in-duct and portable air cleaners typically increased particle removal rates over the baseline rates determined in the absence of operating a central fan or an indoor air cleaner. Removal rates of 0.3- to 0.5-microm particles ranged from 1.5 hr(-1) during operation of an in-duct, 5-in. pleated media filter to 7.2 hr(-1) for an in-duct electrostatic air cleaner in comparison to a baseline rate of 0 hr(-1) when the air handler was operating without a filter. Removal rates for total particulate matter less than 2.5 microm in aerodynamic diameter (PM2.5) mass concentrations were 0.5 hr(-1) under baseline conditions, 0.5 hr(-1) during operation of three portable ionic air cleaners, 1 hr(-1) for an in-duct 1-in. media filter, 2.4 hr(-1) for a single high-efficiency particle arrestance (HEPA) portable air cleaner, 4.6 hr(-1) for an in-duct 5-in. media filter, 4.7 hr(-1) during operation of five portable HEPA filters, 6.1 hr(-1) for a conventional in-duct electronic air cleaner, and 7.5 hr(-1) for a high efficiency in-duct electrostatic air cleaner. Corresponding whole house clean air delivery rates for PM2.5 attributable to the air cleaner independent of losses within the central ventilation system ranged from 2 m3/min for the conventional media filter to 32 m3/min for the high efficiency in-duct electrostatic device. Except for the portable ionic air cleaner, the devices considered here increased particle removal indoors over baseline deposition rates.

  16. Aerosol challenges to air cleaning systems during severe accidents in nuclear plants

    International Nuclear Information System (INIS)

    Gieseke, J.A.

    1985-01-01

    A variety of air cleaning systems may be operating in nuclear power plants and under severe accident conditions, these systems may be treating airborne concentrations of aerosols which are very high. Predictions of airborne aerosol concentrations in nuclear power plant containments under severe accident conditions are reviewed to provide a basis for evaluating the potential effects on the air cleaning systems. The air cleaning systems include filters, absorber beds, sprays, water pools, ice beds, and condensers. Not all of these were intended to operate as air cleaners but will in fact be good aerosol collectors. Knowledge of expected airborne concentrations will allow better evaluation of system performances

  17. Development of an air cleaning system for dissolving high explosives from nuclear warheads

    Energy Technology Data Exchange (ETDEWEB)

    Bergman, W.; Wilson, K.; Staggs, K.; Wapman, D. [Lawrence Livermore National Lab., CA (United States)

    1997-08-01

    The Department of Energy (DOE) has a major effort underway in dismantling nuclear weapons. In support of this effort we have been developing a workstation for removing the high explosive (HE) from nuclear warheads using hot sprays of dimethyl sulfoxide (DMSO) solvent to dissolve the HE. An important component of the workstation is the air cleaning system that is used to contain DMSO aerosols and vapor and radioactive aerosols. The air cleaning system consists of a condenser to liquefy the hot DMSO vapor, a demister pad to remove most of the DMSO aerosols, a high efficiency particulate air (HEPA) filter to remove the remaining aerosols, an activated carbon filter to remove the DMSO vapor, and a final HEPA filter to meet the redundancy requirement for HEPA filters in radioactive applications. The demister pad is a 4{double_prime} thick mat of glass and steel fibers and was selected after conducting screening tests on promising candidates. We also conducted screening tests on various activated carbons and found that all had a similar performance. The carbon breakthrough curves were fitted to a modified Wheeler`s equation and gave excellent predictions for the effect of different flow rates. After all of the components were assembled, we ran a series of performance tests on the components and system to determine the particle capture efficiency as a function of size for dioctyl sebacate (DOS) and DMSO aerosols using laser particle counters and filter samples. The pad had an efficiency greater than 990% for 0.1 {mu}m DMSO particles. Test results on the prototype carbon filter showed only 70% efficiency, instead of the 99.9% in small scale laboratory tests. Thus further work will be required to develop the prototype carbon filter. 7 refs., 18 figs., 10 tabs.

  18. Cleaning the air with renewable energy : briefing note

    International Nuclear Information System (INIS)

    2002-09-01

    The Clean Air Renewable Energy Coalition promotes the development of the renewable energy industry in Canada. It acknowledges the effort that the Canadian government has taken to advance investment in renewable energy, but the Coalition is concerned that these investments alone will not achieve the desired objectives without additional policy development by federal, provincial and territorial governments. This report presents an overview of 7 proposals designed to promote and advance renewable energy in Canada. The benefits of these proposals include cleaner air, improved health, engaging public and industry participation in climate change initiatives, and fostering innovation and entrepreneurship in the sector. Brief details were presented for the following 7 proposals: (1) establish a national low-impact renewable energy target for Canada, (2) increase the Wind Power Production Incentive (WPPI) to 2.7 cent per kilowatt hour to ensure appropriate investment in wind energy and harmonization with the United States, (3) extend incentive programs similar to the WPPI to other renewable energy technologies, (4) work with other levels of government to implement policy mechanisms to meet the recommended national renewable energy target, (5) expand the Market Incentive Program (MIP) funding to 30 million dollars per year to 2012 and consult with the provinces and territories to develop a broad-based consumer green energy rebate and education program, (6) identify mechanisms to ensure a meaningful role for renewable energy to contribute to the country's climate change strategy, and (7) develop a Wind Energy Mapping and Wind Measurement Initiative. In a recent update, the Coalition states that low environmental impact renewable energy needs market recognition for its environmental and social benefits. In general, these benefits are not financially valued in energy market pricing. In addition, energy sources that impact significantly on the environment are not financially

  19. Clean air renewable energy (CARE) coalition : a case study

    Energy Technology Data Exchange (ETDEWEB)

    Lambert, G. [Suncor Energy, Fort McMurray, AB (Canada); Pollock, D. [Pembina Institute for Appropriate Development, Drayton Valley, AB (Canada)

    2002-07-01

    This paper highlights the opportunity for new partnerships between business and non-governmental organizations in the field of sustainable development through the growing convergence of interests. The authors also briefly describe both Suncor Energy and the Pembina Institute for Appropriate Development stances on sustainable development. Since 1990, both organizations have collaborated on the future of the emerging renewable energy industry. Renewable energy represents an energy source diversification through the regional creation of jobs and improved air quality and associated benefits resulting from the reductions in greenhouse gas emissions. The Clean Air Renewable Energy Coalition (Coalition) was established in December 2000 in order to assess the barriers to capital investment in the renewable energy industry. It was revealed that the international community as a whole was further ahead than Canada in terms of renewable support, production and export of technology and services. Some of the challenges facing the industry are: low demand for renewables and low supply. The coalition allowed for the joint identification of desired policy changes, such as new tax incentives for renewable energy supply and demand. Efforts were made in inviting the support of industry, municipalities and environmental non governmental organizations. The list of members that have joined the coalition to date was shown. The coalition is asking for consumer green energy credit, designed for the creation of demand and the education of the general public, and producer incentives to increase supply. The proposals were explained, as well as the strategic principles underlying them. A new tax incentive was announced in the December 2001 Canadian federal budget. The authors concluded by mentioning some future opportunities and the lessons learned on the importance of the right partners, of broad-based advocacy, of targeted and focuses messages, and of evolutionary change.

  20. Clean air renewable energy (CARE) coalition : a case study

    International Nuclear Information System (INIS)

    Lambert, G.; Pollock, D.

    2002-01-01

    This paper highlights the opportunity for new partnerships between business and non-governmental organizations in the field of sustainable development through the growing convergence of interests. The authors also briefly describe both Suncor Energy and the Pembina Institute for Appropriate Development stances on sustainable development. Since 1990, both organizations have collaborated on the future of the emerging renewable energy industry. Renewable energy represents an energy source diversification through the regional creation of jobs and improved air quality and associated benefits resulting from the reductions in greenhouse gas emissions. The Clean Air Renewable Energy Coalition (Coalition) was established in December 2000 in order to assess the barriers to capital investment in the renewable energy industry. It was revealed that the international community as a whole was further ahead than Canada in terms of renewable support, production and export of technology and services. Some of the challenges facing the industry are: low demand for renewables and low supply. The coalition allowed for the joint identification of desired policy changes, such as new tax incentives for renewable energy supply and demand. Efforts were made in inviting the support of industry, municipalities and environmental non governmental organizations. The list of members that have joined the coalition to date was shown. The coalition is asking for consumer green energy credit, designed for the creation of demand and the education of the general public, and producer incentives to increase supply. The proposals were explained, as well as the strategic principles underlying them. A new tax incentive was announced in the December 2001 Canadian federal budget. The authors concluded by mentioning some future opportunities and the lessons learned on the importance of the right partners, of broad-based advocacy, of targeted and focuses messages, and of evolutionary change

  1. Cleaning the air with renewable energy : briefing note

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2002-09-01

    The Clean Air Renewable Energy Coalition promotes the development of the renewable energy industry in Canada. It acknowledges the effort that the Canadian government has taken to advance investment in renewable energy, but the Coalition is concerned that these investments alone will not achieve the desired objectives without additional policy development by federal, provincial and territorial governments. This report presents an overview of 7 proposals designed to promote and advance renewable energy in Canada. The benefits of these proposals include cleaner air, improved health, engaging public and industry participation in climate change initiatives, and fostering innovation and entrepreneurship in the sector. Brief details were presented for the following 7 proposals: (1) establish a national low-impact renewable energy target for Canada, (2) increase the Wind Power Production Incentive (WPPI) to 2.7 cent per kilowatt hour to ensure appropriate investment in wind energy and harmonization with the United States, (3) extend incentive programs similar to the WPPI to other renewable energy technologies, (4) work with other levels of government to implement policy mechanisms to meet the recommended national renewable energy target, (5) expand the Market Incentive Program (MIP) funding to 30 million dollars per year to 2012 and consult with the provinces and territories to develop a broad-based consumer green energy rebate and education program, (6) identify mechanisms to ensure a meaningful role for renewable energy to contribute to the country's climate change strategy, and (7) develop a Wind Energy Mapping and Wind Measurement Initiative. In a recent update, the Coalition states that low environmental impact renewable energy needs market recognition for its environmental and social benefits. In general, these benefits are not financially valued in energy market pricing. In addition, energy sources that impact significantly on the environment are not

  2. Methods for air cleaning and protection of building occupants from airborne pathogens

    Energy Technology Data Exchange (ETDEWEB)

    Bolashikov, Z.D.; Melikov, A.K. [International Centre for Indoor Environment and Energy, Department of Civil Engineering, Technical University of Denmark, Nils Koppels Alle, building 402, 2800 Lyngby (Denmark)

    2009-07-15

    This article aims to draw the attention of the scientific community towards the elevated risks of airborne transmission of diseases and the associated risks of epidemics or pandemics. The complexity of the problem and the need for multidisciplinary research is highlighted. The airborne route of transmission, i.e. the generation of pathogen laden droplets originating in the respiratory tract of an infected individual, the survivability of the pathogens, their dispersal indoors and their transfer to a healthy person are reviewed. The advantages and the drawbacks of air dilution, filtration, ultraviolet germicidal irradiation (UVGI), photocatalytic oxidation (PCO), plasmacluster ions and other technologies for air disinfection and purification from pathogens are analyzed with respect to currently used air distribution principles. The importance of indoor air characteristics, such as temperature, relative humidity and velocity for the efficiency of each method is analyzed, taking into consideration the nature of the pathogens themselves. The applicability of the cleaning methods to the different types of total volume air distribution used at present indoors, i.e. mixing, displacement and underfloor ventilation, as well as advanced air distribution techniques (such as personalized ventilation) is discussed. (author)

  3. Promoting energy efficient building in China through clean development mechanism

    International Nuclear Information System (INIS)

    Zhou, Lu; Li, Jing; Chiang, Yat Hung

    2013-01-01

    This study aims to investigate the barriers which impede the promotion of Energy Efficient Building (EEB), and to propose solutions to alleviate these barriers by capturing the benefits from Clean Development Mechanism (CDM), in the context of China. Through comprehensive literature review, eight types of significant barriers are identified, including weak enforcement of government policies, market inefficiency, information barrier, small and scattering buildings, fragmentation of the construction industry, perceived high risk, higher initial cost, and difficulty in energy management. To overcome the barriers, the potential of CDM to facilitate EEB promotion is then discussed. These barriers are verified and potential solutions are tested with a questionnaire survey conducted among five professional groups in China, i.e. designers, project managers, quantity surveyors, marketing managers and property managers. The results suggest that they generally identified with the barriers. However, their limited awareness of CDM implies that corresponding policies should be formulated and implemented to improve their capability of providing more EEBs with CDM. - Highlights: ► Eight types of significant barriers to the implement of EEB are identified. ► The sources and roots of barriers are verified with the industry professionals. ► Benefits of CDM to EEB are discussed. ► There is limited awareness of CDM in building sector. ► Overcoming or alleviating these barriers through CDM and other sources are proposed

  4. Proceedings of the 23rd DOE/NRC nuclear air cleaning conference

    Energy Technology Data Exchange (ETDEWEB)

    First, M.W. [ed.] [Harvard Univ., Boston, MA (United States). Harvard Air Cleaning Lab.

    1995-02-01

    The report contains the papers presented at the 23rd DOE/NRC Nuclear Air Cleaning Conference and the associated discussions. Major topics are: (1) nuclear air cleaning codes, (2) nuclear waste, (3) filters and filtration, (4) effluent stack monitoring, (5) gas processing, (6) adsorption, (7) air treatment systems, (8) source terms and accident analysis, and (9) fuel reprocessing. Selected papers are indexed separately for inclusion in the Energy Science and Technology Database.

  5. Learning from 25 years of experience with the United States clean air act

    Energy Technology Data Exchange (ETDEWEB)

    Schulze, R.H. [Trinity Consultants Incorporated, Dallas, TX (United States)

    1995-12-31

    Twenty-five years ago, the United States embarked on a quest to attain clean air. President Nixon, in signing the Clean Air Act of 1970, defined clean air as the objective for the `70s. Although enormous progress has been made, much remains to be done. Newly constructed industry is quite clean, but many older facilities continue to operate with antiquated controls. Significant advances have been made in cleaning up the emissions from new automobiles, but two factors have impaired progress. First, cars last longer than they did in 1970, so the average age of the fleet has increased. Second, travel has increased as people have moved to the suburbs. Thus, the emission decreases from clean cars have not been as great as expected. This presentation will address some of the lessons learned from the efforts in the United States to implement clean air programs. In a large number of countries, excessively elaborate studies have been substituted for action programs. Since much is now known about air quality, fairly brief studies can define programs that should be undertaken. What may take longer is developing public support and enthusiasm for improved air quality. In most cases, it is desirable to reduce spending on studies and increase spending on devising and implementing plans, as well as effectively communicating the necessary changes to the public. Balanced spending on studies- and action programs is essential to a sound air quality control program. (author)

  6. Learning from 25 years of experience with the United States clean air act

    Energy Technology Data Exchange (ETDEWEB)

    Schulze, R H [Trinity Consultants Incorporated, Dallas, TX (United States)

    1996-12-31

    Twenty-five years ago, the United States embarked on a quest to attain clean air. President Nixon, in signing the Clean Air Act of 1970, defined clean air as the objective for the `70s. Although enormous progress has been made, much remains to be done. Newly constructed industry is quite clean, but many older facilities continue to operate with antiquated controls. Significant advances have been made in cleaning up the emissions from new automobiles, but two factors have impaired progress. First, cars last longer than they did in 1970, so the average age of the fleet has increased. Second, travel has increased as people have moved to the suburbs. Thus, the emission decreases from clean cars have not been as great as expected. This presentation will address some of the lessons learned from the efforts in the United States to implement clean air programs. In a large number of countries, excessively elaborate studies have been substituted for action programs. Since much is now known about air quality, fairly brief studies can define programs that should be undertaken. What may take longer is developing public support and enthusiasm for improved air quality. In most cases, it is desirable to reduce spending on studies and increase spending on devising and implementing plans, as well as effectively communicating the necessary changes to the public. Balanced spending on studies- and action programs is essential to a sound air quality control program. (author)

  7. AEC Regulatory view of the reliability of air cleaning systems in nuclear facilities

    International Nuclear Information System (INIS)

    Bellamy, R.R.; Zavadoski, R.W.

    1975-01-01

    Air cleaning systems in nuclear facilities can be divided into three categories: ventilation exhaust systems, containment atmosphere cleanup systems, and process offgas systems. These systems have been the subject of numerous reports, regulatory guides, discussions, and meetings. Some of the analyses have been critical of the operation and design of these air cleaning systems--in particular, the engineered safety features containment atmosphere cleanup systems. Although for the most part the criticism is applicable, and recognizing that there are a number of unresolved issues pertaining to gaseous waste management systems, there are data to show that air cleaning systems in use in nuclear facilities are performing their intended function. (U.S.)

  8. Federal-state partnership: An overview of the Clean Air Act through the 1980s

    International Nuclear Information System (INIS)

    Anon.

    1991-01-01

    This chapter examines the experience with Clean Air Act regulation over the past two decades as a means of understanding the multiple layers of regulatory requirements that now exist since the enactment of the 1990 Amendments to the Act. The efforts of Congress and the EPA to deal with the complexities of clean air regulation suggest several themes for the 1990s: more federal oversight, more complex regulatory issues, an emphasis on alternatives to traditional rulemaking proceedings, and a search for innovative ways to control the escalating costs of clean air regulation

  9. 78 FR 2333 - Approval of the Clean Air Act, Section 112(l), Authority for Hazardous Air Pollutants: Asbestos...

    Science.gov (United States)

    2013-01-11

    ...] Approval of the Clean Air Act, Section 112(l), Authority for Hazardous Air Pollutants: Asbestos Management... protection, Administrative practice and procedure, Air pollution control, Hazardous substances, Incorporation...-Sw 2100: Management and Control of Asbestos Disposal Sites Not Operated after July 9, 1981,'' and the...

  10. Cleaning and air conditioning device for atmosphere in thermonuclear reactor chamber

    International Nuclear Information System (INIS)

    Ishida, Seiji.

    1993-01-01

    The device of the present invention removes tritium efficiently and attains ventilation and conditioning of a great amount of air flow. That is, there are disposed a humidity separator, a filter, a heater, a catalyst filled layer, a water jetting type humidifying heat insulation cooler and a cooler in this order from an inlet side (upstream) of contaminated room atmospheric gases. The catalyst filled layer, etc. are incorporated integrally into the ventilation air conditioning facility for ventilating air in the chamber of the thermonuclear reactor, to clean a tritium atmosphere at the same time. Accordingly, the device is made compact as a whole. A limit for the air flow rate owing to the use of the conventional catalyst tower and adsorbing tower is eliminated. Then a ventilating air conditioning for a great flow rate can be attained. Tritium is removed by cooling and dehumidification without using any adsorbent. Accordingly, an adsorbing tower is no more necessary and conventional regeneration operation is not required. As a result, space for installation is reduced, the system is simplified and the cost for construction and facility can be reduced. (I.S.)

  11. An efficient, environmentally acceptable, clean up system for well completions

    International Nuclear Information System (INIS)

    Berg, Oe.; Saasen, A.

    1996-01-01

    Evaluation of different casing cleaning fluid systems has been a difficult task due to the lack of a standardised laboratory measurement technique for technical performance. In order to meet the need for a reliable evaluation of different chemicals and fluid systems used in casing cleaning, a laboratory procedure for the evaluation of casing cleaning chemicals has been developed. This procedure has been successfully applied in the development of a new environmentally acceptable casing cleaning fluid system. Two different procedures are presented. An old method where the drilling fluid was displaced down the annulus and up the drill string was found to be ineffective compared to a method where the drilling fluid was displaced up in the annulus. The application of this procedure together with the use of the new chemical additive has reduced the cost of casing cleanup operations in the range of 30-40%. 10 refs., 1 fig., 4 tabs

  12. Self-cleaning efficiency of artificial superhydrophobic surfaces.

    Science.gov (United States)

    Bhushan, Bharat; Jung, Yong Chae; Koch, Kerstin

    2009-03-03

    The hierarchical structured surface of the lotus (Nelumbo nucifera, Gaertn.) leaf provides a model for the development of biomimetic self-cleaning surfaces. On these water-repellent surfaces, water droplets move easily at a low inclination of the leaf and collect dirt particles adhering to the leaf surface. Flat hydrophilic and hydrophobic, nanostructured, microstructured, and hierarchical structured superhydrophobic surfaces were fabricated, and a systematic study of wettability and adhesion properties was carried out. The influence of contact angle hysteresis on self-cleaning by water droplets was studied at different tilt angles (TA) of the specimen surfaces (3 degrees for Lotus wax, 10 degrees for n-hexatriacontane, as well as 45 degrees for both types of surfaces). At 3 degrees and 10 degrees TA, no surfaces were cleaned by moving water applied onto the surfaces with nearly zero kinetic energy, but most particles were removed from hierarchical structured surfaces, and a certain amount of particles were captured between the asperities of the micro- and hierarchical structured surfaces. After an increase of the TA to 45 degrees (larger than the tilt angles of all structured surfaces), as usually used for industrial self-cleaning tests, all nanostructured surfaces were cleaned by water droplets moving over the surfaces followed by hierarchical and microstructures. Droplets applied onto the surfaces with some pressure removed particles residues and led to self-cleaning by a combination of sliding and rolling droplets. Geometrical scale effects were responsible for superior performance of nanostructured surfaces.

  13. Partial pit exhaust improves indoor air quality and effectiveness of air cleaning in livestock housing

    DEFF Research Database (Denmark)

    Zhang, Guoqiang; Bjerg, B.; Zong, C.

    2017-01-01

    Ammonia and odor emissions from livestock production systems cause negative impact on atmospheric environment and local society. It is, therefore, important to develop cost-effective methods to reduce these emissions. Air cleaning technologies, including chemical and biological filters, have been...... and experimental investigations, to identify important factors that may affect the system performances for removal of ammonia and other pollutants from the animal housing and to address the extension work that may be needed to apply the method in actual production scales. It is shown that PPAE is an effective...

  14. Air compressor efficiency in a Vietnamese enterprise

    Energy Technology Data Exchange (ETDEWEB)

    Yang, Ming [3E and T International, Suite 1506, Building No. 10, Luo Ma Shi Street, Xuan Wu District, Beijing 100052 (China)

    2009-06-15

    Compressed air systems in a Vietnamese footwear manufacturing enterprise consume about 10% of enterprise's total electric power supply. Energy efficiency of these air compressor systems, either equipped with new and efficient compressors or old and inefficient ones, can only reach between 5% and 10%. In other words, regardless whatever air compressors were installed, energy loss from the compressor systems was over 80%. This study discovered that energy loss was due to non-optimized operations of the air compressor systems and air leakages. The objectives of the paper are to uncover energy saving potential in Vietnamese air compressor systems, demonstrate methodologies used in the auditing and assessment, share auditing and assessment results, and serve a guide on how to analyze energy efficiency in a compressed air system. This paper concludes that energy efficiency investment in air compressor systems in the Vietnamese enterprise could be extremely cost-effective. If the enterprise invests USD 84,000 in the air compressors to improve efficiency performance, the investment capital will be recovered in about six months. The net present value of the investment will be about USD 864,000 at a discount rate of 12%. (author)

  15. Air compressor efficiency in a Vietnamese enterprise

    Energy Technology Data Exchange (ETDEWEB)

    Yang Ming [3E and T International, Suite 1506, Building No. 10, Luo Ma Shi Street, Xuan Wu District, Beijing 100052 (China)], E-mail: ming.yang7@gmail.com

    2009-06-15

    Compressed air systems in a Vietnamese footwear manufacturing enterprise consume about 10% of enterprise's total electric power supply. Energy efficiency of these air compressor systems, either equipped with new and efficient compressors or old and inefficient ones, can only reach between 5% and 10%. In other words, regardless whatever air compressors were installed, energy loss from the compressor systems was over 80%. This study discovered that energy loss was due to non-optimized operations of the air compressor systems and air leakages. The objectives of the paper are to uncover energy saving potential in Vietnamese air compressor systems, demonstrate methodologies used in the auditing and assessment, share auditing and assessment results, and serve a guide on how to analyze energy efficiency in a compressed air system. This paper concludes that energy efficiency investment in air compressor systems in the Vietnamese enterprise could be extremely cost-effective. If the enterprise invests USD 84,000 in the air compressors to improve efficiency performance, the investment capital will be recovered in about six months. The net present value of the investment will be about USD 864,000 at a discount rate of 12%.

  16. Air compressor efficiency in a Vietnamese enterprise

    International Nuclear Information System (INIS)

    Yang Ming

    2009-01-01

    Compressed air systems in a Vietnamese footwear manufacturing enterprise consume about 10% of enterprise's total electric power supply. Energy efficiency of these air compressor systems, either equipped with new and efficient compressors or old and inefficient ones, can only reach between 5% and 10%. In other words, regardless whatever air compressors were installed, energy loss from the compressor systems was over 80%. This study discovered that energy loss was due to non-optimized operations of the air compressor systems and air leakages. The objectives of the paper are to uncover energy saving potential in Vietnamese air compressor systems, demonstrate methodologies used in the auditing and assessment, share auditing and assessment results, and serve a guide on how to analyze energy efficiency in a compressed air system. This paper concludes that energy efficiency investment in air compressor systems in the Vietnamese enterprise could be extremely cost-effective. If the enterprise invests USD 84,000 in the air compressors to improve efficiency performance, the investment capital will be recovered in about six months. The net present value of the investment will be about USD 864,000 at a discount rate of 12%.

  17. An analysis of candidates for addition to the Clean Air Act list of hazardous air pollutants

    Energy Technology Data Exchange (ETDEWEB)

    Sonya Lunder; Tracey J. Woodruff; Daniel A. Axelrad [University of California, Berkeley, CA (United States). School of Public Health

    2004-02-01

    There are 188 air toxics listed as hazardous air pollutants (HAPs) in the Clean Air Act (CAA), based on their potential to adversely impact public health. This paper presents several analyses performed to screen potential candidates for addition to the HAPs list. We analyzed 1086 HAPs and potential HAPs, including chemicals regulated by the state of California or with emissions reported to the Toxics Release Inventory (TRI). HAPs and potential HAPs were ranked by their emissions to air, and by toxicity-weighted (tox-wtd) emissions for cancer and noncancer, using emissions information from the TRI and toxicity information from state and federal agencies. Separate consideration was given for persistent, bioaccumulative toxins (PBTs), reproductive or developmental toxins, and chemicals under evaluation for regulation as toxic air contaminants in California. Forty-four pollutants were identified as candidate HAPs based on three ranking analyses and whether they were a PBT or a reproductive or developmental toxin. Of these, nine qualified in two or three different rankings (ammonia (NH{sub 3}), copper (Cu), Cu compounds, nitric acid (HNO{sub 3}), N-methyl-2-pyrrolidone, sulfuric acid (H{sub 2}SO{sub 4}), vanadium (V) compounds, zinc (Zn), and Zn compounds). This analysis suggests further evaluation of several pollutants for possible addition to the CAA list of HAPs. 28 refs., 2 figs., 11 tabs.

  18. Evaluation of air cleaning system concepts for emergency use in LMFBR plants

    International Nuclear Information System (INIS)

    Hilliard, R.K.; McCormack, J.D.; Postma, A.K.

    1976-12-01

    Nineteen different air cleaning concepts are arranged into twenty-four systems and evaluated for use as accident mitigating systems in LMFBR plants. Both single, low-leakage containment plants and once-through operation applicable to containment/confinement plants are considered. Plant characteristics affecting air cleaning requirements are defined for 1000 MW(e) plants and a sodium and radiological release term is postulated. The accident conditions under which the emergency air cleaning system (EACS) must function is established by use of SOFIRE-II and HAA-3B computer codes. Criteria are developed for evaluating the various systems and for assigning comparative ratings. The numerical ratings are combined with information on cost and development potential to arrive at recommendations for the most promising systems. The conclusion is made that reliable and effective systems are feasible for use as engineered safety features for LMFBR plants, but that development effort is required for all the air cleaning concepts evaluated

  19. 75 FR 24946 - Proposed Consent Decree, Clean Air Act Citizen Suit

    Science.gov (United States)

    2010-05-06

    ..., South Carolina, Wisconsin, Indiana, Michigan, Ohio, Louisiana, Kansas, Nebraska, Missouri, Colorado..., Wisconsin, Indiana, Michigan, Ohio, Louisiana, Kansas, Nebraska, Missouri, Colorado, Montana, South Dakota... ENVIRONMENTAL PROTECTION AGENCY [FRL-9146-3] Proposed Consent Decree, Clean Air Act Citizen Suit...

  20. 75 FR 10794 - Clean Air Act Advisory Committee (CAAAC) Request for Nominations to the CAAAC

    Science.gov (United States)

    2010-03-09

    ... Clean Air Act Advisory Committee (CAAAC) on November 19, 1990, to provide independent advice and counsel... Nominations: The U.S. Environmental Protection Agency (EPA) invites nominations of qualified candidates to be...

  1. Developing self-cleaning and air purifying transportation infrastructure components to minimize environmental impact of transportation.

    Science.gov (United States)

    2013-10-01

    Creating transportation infrastructure, which can clean up itself and contaminated air surrounding it, can be a : groundbreaking approach in addressing environmental challenges of our time. This project has explored a possibility of : depositing coat...

  2. Risk Management Programs under Clean Air Act Section 112(r): Guidance for Implementing Agencies

    Science.gov (United States)

    Accidental release prevention programs under section 112(r) of the Clean Air Act (CAA) are related to and build on activities under the Emergency Planning and Community Right-to-Know Act, and Occupational Safety and Health Administration standards.

  3. OH and HO2 chemistry in clean marine air during SOAPEX-2

    Directory of Open Access Journals (Sweden)

    R. Sommariva

    2004-01-01

    Full Text Available Model-measurement comparisons of HOx in extremely clean air ([NO] The free-radical chemistry was studied using a zero-dimensional box-model based upon the Master Chemical Mechanism (MCM. Two versions of the model were used, with different levels of chemical complexity, to explore the role of hydrocarbons upon free-radical budgets under very clean conditions. The "detailed" model was constrained to measurements of CO, CH4 and 17 NMHCs, while the "simple" model contained only the CO and CH4 oxidation mechanisms, together with inorganic chemistry. The OH and HO2 (HOx concentrations predicted by the two models agreed to within 5–10%. The model results were compared with the HOx concentrations measured by the FAGE (Fluorescence Assay by Gas Expansion technique during four days of clean Southern Ocean marine boundary layer (MBL air. The models overestimated OH concentrations by about 10% on two days and about 20% on the other two days. HO2 concentrations were measured during two of these days and the models overestimated the measured concentrations by about 40%. Better agreement with measured HO2 was observed by using data from several MBL aerosol measurements to estimate the aerosol surface area and by increasing the HO2 uptake coefficient to unity. This reduced the modelled HO2 overestimate by ~40%, with little effect on OH, because of the poor HO2 to OH conversion at the low ambient NOx concentrations. Local sensitivity analysis and Morris One-At-A-Time analysis were performed on the "simple" model, and showed the importance of reliable measurements of j(O1D and [HCHO] and of the kinetic parameters that determine the efficiency of O(1D to OH and HCHO to HO2 conversion. A 2σ standard deviation of 30–40% for OH and 25–30% for HO2 was estimated for the model calculations using a Monte Carlo technique coupled with Latin Hypercube Sampling (LHS.

  4. Proceedings of the 21st DOE/NRC nuclear air cleaning conference

    International Nuclear Information System (INIS)

    First, M.W.

    1991-02-01

    The 21st meeting of the Department of Energy/Nuclear Regulatory Commission (DOE/NRC) Nuclear Air Cleaning Conference was held in San Diego, CA on August 13--16, 1990. The proceedings have been published as a two volume set. Volume 2 contains sessions covering adsorbents, nuclear codes and standards, modelling, filters, safety, containment venting and a review of nuclear air cleaning programs around the world. Also included is the list of attendees and an index of authors and speakers

  5. Research and development on air cleaning system of reprocessing plant in Japan

    International Nuclear Information System (INIS)

    Naruki, K.

    1985-01-01

    Present status in Japan of R and D on air cleaning systems, especially of the fuel reprocessing plant is summarized. The description is centered on the R and D and experience of Tokai-reprocessing plant, which covers the plant air cleaning system, effort carried out for decreasing I 2 effluence in the actual vented off-gas, and R and D for recovery of Kr and 3 H. Some experimental results for the evaluation of HEPA filter are also described

  6. Effectiveness of HVAC duct cleaning procedures in improving indoor air quality.

    Science.gov (United States)

    Ahmad, I; Tansel, B; Mitrani, J D

    2001-12-01

    Indoor air quality has become one of the most serious environmental concerns as an average person spends about 22 hr indoors on a daily basis. The study reported in this article, was conducted to determine the effectiveness of three commercial HVAC (Heating Ventilation Air Conditioning) duct cleaning processes in reducing the level of airborne particulate matter and viable bioaerosols. The three HVAC sanitation processes were: (1) Contact method (use of conventional vacuum cleaning of interior duct surfaces); (2) Air sweep method (use of compressed air to dislodging dirt and debris); (3) Rotary brush method (insertion of a rotary brush into the ductwork to agitate and dislodge the debris). Effectiveness of these sanitation processes was evaluated in terms of airborne particulate and viable bioaerosol concentrations in residential homes. Eight identical homes were selected in the same neighborhood. Two homes were cleaned using each procedure and two were used as controls. It was found that both particle count readings and bioaerosol concentrations were higher when cleaning was being performed than before or after cleaning, which suggests that dirt, debris and other pollutants may become airborne as a result of disturbances caused by the cleaning processes. Particle count readings at 0.3 micron size were found to have increased due to cigarette smoking. Particle counts at 1.0 micron size were reduced due to HVAC duct cleaning. Post-level bioaerosol concentrations, taken two days after cleaning, were found to be lower than the pre-level concentrations suggesting that the cleaning procedures were effective to some extent. Homes cleaned with the Air Sweep procedure showed the highest degree of reduction in bioaerosol concentration among the three procedures investigated.

  7. Efficiency of Compressed Air Energy Storage

    DEFF Research Database (Denmark)

    Elmegaard, Brian; Brix, Wiebke

    2011-01-01

    The simplest type of a Compressed Air Energy Storage (CAES) facility would be an adiabatic process consisting only of a compressor, a storage and a turbine, compressing air into a container when storing and expanding when producing. This type of CAES would be adiabatic and would if the machines...... were reversible have a storage efficiency of 100%. However, due to the specific capacity of the storage and the construction materials the air is cooled during and after compression in practice, making the CAES process diabatic. The cooling involves exergy losses and thus lowers the efficiency...... of the storage significantly. The efficiency of CAES as an electricity storage may be defined in several ways, we discuss these and find that the exergetic efficiency of compression, storage and production together determine the efficiency of CAES. In the paper we find that the efficiency of the practical CAES...

  8. Proceedings of the 19th DOE/NRC nuclear air cleaning conference

    International Nuclear Information System (INIS)

    First, M.W.

    1987-05-01

    This document contains the papers and the associated discussions of the 19 DOE/NRC Nuclear Air Cleaning Conference. Sessions were devoted to (1) fire, explosion and accident analysis, (2) adsorption and iodine retention, (3) filters and filter testing, (4) standards and regulation, (5) treatment of radon, krypton, tritium and carbon-14, (6) ventilation and air cleaning in reactor operations, (7) dissolver off-gas cleaning, (8) adsorber fires, (9) nuclear grade carbon testing, (10) sampling and monitoring, and (11) field test experience. Individual papers were processed separately for the data base

  9. Efficiency enhancement of InP nanowire solar cells by surface cleaning

    NARCIS (Netherlands)

    Cui, Y.; Wang, J.; Plissard, S.R.; Cavalli, A.; Vu, T.T.T.; Veldhoven, van P.J.; Gao, L.; Trainor, M.J.; Verheijen, M.A.; Haverkort, J.E.M.; Bakkers, E.P.A.M.

    2013-01-01

    We demonstrate an efficiency enhancement of an InP nanowire (NW) axial p–n junction solar cell by cleaning the NW surface. NW arrays were grown with in situ HCl etching on an InP substrate patterned by nanoimprint lithography, and the NWs surfaces were cleaned after growth by piranha etching. We

  10. Self-Scrubbing Coal -- an integrated approach to clean air

    Energy Technology Data Exchange (ETDEWEB)

    Harrison, K.E. [Custom Coals Corp., Pittsburgh, PA (United States)

    1997-12-31

    Carefree Coal is coal cleaned in a proprietary dense-media cyclone circuit, using ultrafine magnetite slurries, to remove noncombustible material, including up to 90% of the pyritic sulfur. Deep cleaning alone, however, cannot produce a compliance fuel from coals with high organic sulfur contents. In these cases, Self-Scrubbing Coal will be produced. Self-Scrubbing Coal is produced in the same manner as Carefree Coal except that the finest fraction of product from the cleaning circuit is mixed with limestone-based additives and briquetted. The reduced ash content of the deeply-cleaned coal will permit the addition of relatively large amounts of sorbent without exceeding boiler ash specifications or overloading electrostatic precipitators. This additive reacts with sulfur dioxide (SO{sub 2}) during combustion of the coal to remove most of the remaining sulfur. Overall, sulfur reductions in the range of 80--90% are achieved. After nearly 5 years of research and development of a proprietary coal cleaning technology coupled with pilot-scale validation studies of this technology and pilot-scale combustion testing of Self-Scrubbing Coal, Custom Coals Corporation organized a team of experts to prepare a proposal in response to DOE`s Round IV Program Opportunity Notice for its Clean Coal Technology Program under Public Law 101-121 and Public Law 101-512. The main objective of the demonstration project is the production of a coal fuel that will result in up to 90% reduction in sulfur emissions from coal-fired boilers at a cost competitive advantage over other technologies designed to accomplish the same sulfur emissions and over naturally occurring low sulfur coals.

  11. Development of an emergency air-cleaning system for liquid-metal reactors

    International Nuclear Information System (INIS)

    Owen, R.K.

    1980-11-01

    A novel air cleaning concept has been developed for potential use in venting future commercial liquid metal fast breeder reactor containment buildings in the unlikely event of postulated core disruptive accidents. The passive concept consists of a submerged gravel bed to collect the bulk of particulate contaminates carried by the vented gas. A fibrous scrubber could be combined with the submerged gravel scrubber to enhance collection efficiencies for the smaller sized particles. The submerged gravel scrubber is unique in that water flow through the packed bed is induced by the gas flow, eliminating the need for an active liquid pump. In addition, design gas velocities through the packed bed are 10 to 20 times higher than for a conventional sand bed filter

  12. Testing and operation of nuclear air-cleaning systems in Qinshan NPP

    International Nuclear Information System (INIS)

    Yang Lin

    1993-01-01

    The components of nuclear air-cleaning system, system function, operational mode and the performance of cleaning components in Qinshan Nuclear Power Plant are described. The items, purpose, methods and results of in-place testing after the installation are also described in detail. The in-place testing verifies that nuclear air-cleaning systems in Qinshan Nuclear Power Plant are reliable and high effective. It also describes the points of the operational management. It is shown that the good operational management is the key which developed prescription function of nuclear air-cleaning systems. At present, Qinshan Nuclear Power Plant will be in full power, the normal operation of the system is satisfied with the demand of safe operation in Qinshan Nuclear Power Company

  13. 40 CFR 60.2971 - What are the emission limitations for air curtain incinerators that burn only wood waste, clean...

    Science.gov (United States)

    2010-07-01

    ... air curtain incinerators that burn only wood waste, clean lumber, and yard waste? 60.2971 Section 60... Incinerators That Burn Only Wood Waste, Clean Lumber, and Yard Waste § 60.2971 What are the emission limitations for air curtain incinerators that burn only wood waste, clean lumber, and yard waste? (a) Within...

  14. Low Temperature Combustion Demonstrator for High Efficiency Clean Combustion

    Energy Technology Data Exchange (ETDEWEB)

    Ojeda, William de

    2010-07-31

    The project which extended from November 2005 to May of 2010 demonstrated the application of Low Temperature Combustion (LTC) with engine out NOx levels of 0.2 g/bhp-hr throughout the program target load of 12.6bar BMEP. The project showed that the range of loads could be extended to 16.5bar BMEP, therefore matching the reference lug line of the base 2007 MY Navistar 6.4L V8 engine. Results showed that the application of LTC provided a dramatic improvement over engine out emissions when compared to the base engine. Furthermore LTC improved thermal efficiency by over 5% from the base production engine when using the steady state 13 mode composite test as a benchmark. The key enablers included improvements in the air, fuel injection, and cooling systems made in Phases I and II. The outcome was the product of a careful integration of each component under an intelligent control system. The engine hardware provided the conditions to support LTC and the controller provided the necessary robustness for a stable combustion. Phase III provided a detailed account on the injection strategy used to meet the high load requirements. During this phase, the control strategy was implemented in a production automotive grade ECU to perform cycle-by-cycle combustion feedback on each of the engine cylinders. The control interacted on a cycle base with the injection system and with the Turbo-EGR systems according to their respective time constants. The result was a unique system that could, first, help optimize the combustion system and maintain high efficiency, and secondly, extend the steady state results to the transient mode of operation. The engine was upgraded in Phase IV with a Variable Valve Actuation system and a hybrid EGR loop. The impact of the more versatile EGR loop did not provide significant advantages, however the application of VVA proved to be an enabler to further extend the operation of LTC and gain considerable benefits in fuel economy and soot reduction. Finally

  15. Clean Air Act Guidelines and Standards for Waste Management

    Science.gov (United States)

    This page contains the stationary sources of air pollution for the waste management industries, and their corresponding air pollution regulations. To learn more about the regulations for each industry, just click on the links below.

  16. Clean Air Act Standards and Guidelines for Electric Utilities

    Science.gov (United States)

    This page contains the stationary sources of air pollution for theelectric utilitiesr industries, and their corresponding air pollution regulations. To learn more about the regulations for each industry, just click on the links below.

  17. Clean Air Act Standards and Guidelines for Sterilizers

    Science.gov (United States)

    This page contains the stationary sources of air pollution for the sterilizer industries, and their corresponding air pollution regulations. To learn more about the regulations for each industry, just click on the links below.

  18. Clean Air Act Standards and Guidelines for Mineral Processing

    Science.gov (United States)

    This page contains the stationary sources of air pollution for the mineral processing industries, and their corresponding air pollution regulations. To learn more about the regulations for each industry, just click on the links below.

  19. Scenarios for a Clean Energy Future: Interlaboratory Working Group on Energy-Efficient and Clean-Energy Technologies

    Energy Technology Data Exchange (ETDEWEB)

    None, None

    2000-12-18

    This study estimates the potential for public policies and R and D programs to foster clean energy technology solutions to the energy and environmental challenges facing the nation. These challenges include global climate change, air pollution, oil dependence, and inefficiencies in the production and use of energy. The study uses a scenario-based approach to examine alternative portfolios of public policies and technologies. Although the report makes no policy recommendations, it does present policies that could lead to impressive advances in the development and deployment of clean energy technologies without significant net economic impacts. Appendices are available electronically at: www.nrel.gov/docs/fy01osti/29379appendices.pdf (6.4 MB).

  20. Bioinspired Bifunctional Membrane for Efficient Clean Water Generation.

    Science.gov (United States)

    Liu, Yang; Lou, Jinwei; Ni, Mengtian; Song, Chengyi; Wu, Jianbo; Dasgupta, Neil P; Tao, Peng; Shang, Wen; Deng, Tao

    2016-01-13

    Solving the problems of water pollution and water shortage is an urgent need for the sustainable development of modern society. Different approaches, including distillation, filtration, and photocatalytic degradation, have been developed for the purification of contaminated water and the generation of clean water. In this study, we explored a new approach that uses solar light for both water purification and clean water generation. A bifunctional membrane consisting of a top layer of TiO2 nanoparticles (NPs), a middle layer of Au NPs, and a bottom layer of anodized aluminum oxide (AAO) was designed and fabricated through multiple filtration processes. Such a design enables both TiO2 NP-based photocatalytic function and Au NP-based solar-driven plasmonic evaporation. With the integration of these two functions into a single membrane, both the purification of contaminated water through photocatalytic degradation and the generation of clean water through evaporation were demonstrated using simulated solar illumination. Such a demonstration should also help open up a new strategy for maximizing solar energy conversion and utilization.

  1. No Need to Wait for the Clean Air Dividend

    Science.gov (United States)

    Shindell, Drew

    2012-01-01

    upfront costs of some measures can be prohibitive even when they eventually pay for themselves. But this can be overcome by mechanisms such as international financing of capital costs. For other measures, the costs are typically borne by a few while the benefits accrue to everybody. In such cases civil society and governments must get involved. Governments are starting to act. In February, the US, Canada, Sweden, Bangladesh, Ghana and Mexico launched the Climate and Clean Air Coalition to support implementation of measures like these. This coalition will hopefully expand and achieve rapid, widespread adoption of measures to cut black carbon and ozone. While the climate benefits will be substantial, it is important to note that these measures cannot substitute for cuts in carbon dioxide. Black carbon, ozone, carbon monoxide and methane stay in the atmosphere for a fairly short time - a few days for black carbon and about a decade for methane. They thus respond quickly to emissions changes and give us substantial leverage over near-term climate change. In contrast, carbon dioxide is very long-lived and so responds slowly to emissions changes. This means that cuts have little immediate impact, but it also means they must be made now to avoid disastrous changes later on. Controlling short-lived climate pollutants is thus an issue of fairness. Much as failure to reduce carbon dioxide emissions soon would condemn future generations to disastrous change, failure to reduce near-term climate change condemns those alive today to suffer worsening effects of the sort already seen. Some wonder if we really can do both. We can, and we must.

  2. Effect of design and technology on the efficiency of ultrasonic facilities for sheet cleaning

    International Nuclear Information System (INIS)

    Lubyanitskij, G.D.

    1977-01-01

    Various techniques are reviewed for enhancing the efficiency of ultrasonic cleaning of various items, such as sheets, and for lowering the energy consumption of the process. It is important to maintain a specified spacing between the item to be cleaned and the supersound projector, to remove the contaminants accumulating in the surface layer of the solution and to provide an adequate combination between the ultrasonic and the mechanical cleaning means. It is noted that the injection of the surfactants directly into the cleaning zone lowers the intensity of foaming without affecting the quality of cleaning. In some cases the cleaning is even speeded up due to an improvement in conditions for the transmission of acoustic waves in areas at some distance from the converter

  3. Netherlands export country for electricity? New developments in power plants and the impact on the Clean and Efficient programme

    International Nuclear Information System (INIS)

    Seebregts, A.J.; Daniels, B.W.

    2008-07-01

    This report explores part of the effects of the Dutch Climate Programme 'Clean and Efficient - Opportunities for Tomorrow' on the emissions of air pollutants, as included in the National Emissions Ceilings. The starting point for the analysis is the ex ante evaluation of Clean and Efficient as published in September 2007. Specifically for the Netherlands, the role of the power generation sector is important. For the near future (up to 2015), about 11 to 15 GW of new fossil generation capacity is being planned. In combination with the Clean and Efficient Programme, this will have a large impact on the resulting national emissions of air pollutants. Strong climate policies and high CO2 prices are likely to result in a lower electricity demand than the original reference projection (the Global Economy High Oil Price scenario). In addition, more renewable electricity generation and more cogeneration are expected. These changes are likely to improve the international competitiveness of the Dutch electricity generation. As a result, electricity exports rise and part of the emission reductions materialize outside the Netherlands, rather than within its borders [nl

  4. The community takes charge : story and success of Clean Air Hamilton

    International Nuclear Information System (INIS)

    McCarry, B.

    2004-01-01

    Clean Air Hamilton was established in 2001 to identify priority air quality issues, pollution sources, and evaluate impacts and solutions for air quality issues. Clean Air Hamilton also assesses the human health effects of ambient air exposures in Hamilton. A 1997 survey of Hamilton residents showed that most citizens were extremely concerned about health effects, black fallout, smog visibility, and odours. Clean Air Hamilton has established an air monitoring network which includes 19 member companies and 22 industrial sites. The objective is to determine recent contaminant trends in upwind/downwind air quality. The timeline for establishing the Hamilton air monitoring network was presented. The network, which serves as a model for Ontario and Canada, monitors the impact of vehicular and industrial emissions and establishes ten-year air quality trends for benzo(a)pyrene, sulphur, nitrogen dioxide, and ozone at industrial sites and the downtown core. Analysis of air quality trends shows that there has been improvement in levels of some locally-generated contaminants. The data has also been used for epidemiological studies to determine the health effects of industry on Hamiltonians. figs

  5. L’Aquila Smart Clean Air City: The Italian Pilot Project for Healthy Urban Air

    Directory of Open Access Journals (Sweden)

    Alessandro Avveduto

    2017-11-01

    Full Text Available Exposure to atmospheric pollution is a major concern for urban populations. Currently, no effective strategy has been adopted to tackle the problem. The paper presents the Smart Clean Air City project, a pilot experiment concerning the improvement in urban air quality. Small wet scrubber systems will be operating in a network configuration in suitable urban areas of L’Aquila city (Italy. The purpose of this work is to describe the project and show the preliminary results obtained in the characterization of two urban sites before the remediation test; the main operating principles of the wet scrubber system will be discussed, as well as the design of the mobile treatment plant for the processing of wastewater resulting from scrubber operation. Measurements of particle size distributions in the range of 0.30–25 µm took place in the two sites of interest, an urban background and a traffic area in the city of L’Aquila. The mean number concentration detected was 2.4 × 107 and 4.5 × 107 particles/m3, respectively. Finally, theoretical assessments, performed by Computational Fluid Dynamics (CFD codes, will show the effects of the wet scrubber operation on air pollutants under different environmental conditions and in several urban usage patterns.

  6. Air toxics provisions of the Clean Air Act: Potential impacts on energy

    International Nuclear Information System (INIS)

    Hootman, H.A.; Vernet, J.E.

    1991-11-01

    This report provides an overview of the provisions of the Clean Air Act and its Amendments of 1990 that identify hazardous air pollutant (HAP) emissions and addresses their regulation by the US Environmental Protection Agency (EPA). It defines the major energy sector sources of these HAPs that would be affected by the regulations. Attention is focused on regulations that would cover coke oven emissions; chromium emission from industrial cooling towers and the electroplating process; HAP emissions from tank vessels, asbestos-related activities, organic solvent use, and ethylene oxide sterilization; and emissions of air toxics from municipal waste combustors. The possible implications of Title III regulations for the coal, natural gas, petroleum, uranium, and electric utility industries are examined. The report discusses five major databases of HAP emissions: (1) TRI (EPA's Toxic Release Inventory); (2) PISCES (Power Plant Integrated Systems: Chemical Emissions Studies developed by the Electric Power Research Institute); (3) 1985 Emissions Inventory on volatile organic compounds (used for the National Acid Precipitation Assessment Program); (4) Particulate Matter Species Manual (EPA); and (5) Toxics Emission Inventory (National Aeronautics and Space Administration). It also offers information on emission control technologies for municipal waste combustors

  7. 76 FR 9609 - Notice of Proposed Consent Decree Under the Clean Air Act

    Science.gov (United States)

    2011-02-18

    ... the Environmental Protection Agency and the San Joaquin Valley Unified Air Pollution Control District... related to emissions of pollutants; install and operate required pollution control technology; undertake... Clean Air Act, 42 U.S.C. 7413(b), for alleged environmental violations at defendant's biomass electric...

  8. 77 FR 39262 - Notice of Lodging of Consent Decree Under the Clean Air Act

    Science.gov (United States)

    2012-07-02

    ... Frozen Bakery Products, Inc. (collectively ``Cottage'') for violations of the federal Clean Air Act, 42 U... Joaquin Valley Unified Air Pollution Control District v. Cottage Bakery, Inc. and Ralcorp Frozen Bakery Products, Inc., case number 2:12-at-00895, was lodged with the United States District Court for the Eastern...

  9. Smogbusters: Grassroots Action for Clean Air and Sustainable Transport in Australia

    Science.gov (United States)

    Manners, Eric; Wake, David; Carlisle, Rachel

    2009-01-01

    Smogbusters was a national, community-based, government-funded community education program promoting clean air and sustainable transport in Australia from 1994 to 2002. Smogbusters aimed to improve air quality primarily by raising awareness about motor vehicle transport and its negative impacts on health, the environment and communities, and by…

  10. Human Response to Ductless Personalised Ventilation: Impact of Air Movement, Temperature and Cleanness on Eye Symptoms

    DEFF Research Database (Denmark)

    Dalewski, Mariusz; Fillon, Maelys; Bivolarova, Maria

    2013-01-01

    environment facially applied individually controlled air movement of room air, with or without local filtering, did not have significant impact on eye blink frequency and tear film quality. The local air movement and air cleaning resulted in increased eye blinking frequency and improvement of tear film......The performance of ductless personalized ventilation (DPV) in conjunction with displacement ventilation (DV) was studied in relation to peoples’ health, comfort and performance. This paper presents results on the impact of room air temperature, using of DPV and local air filtration on eye blink...

  11. Sample and injection manifolds used to in-place test of nuclear air-cleaning system

    International Nuclear Information System (INIS)

    Qiu Dangui; Li Xinzhi; Hou Jianrong; Qiao Taifei; Wu Tao; Zhang Jirong; Han Lihong

    2012-01-01

    Objective: According to the regulations of nuclear safety rules and related standards, in-place test of the nuclear air-cleaning systems should be carried out before and during operation of the nuclear facilities, which ensure them to be in good condition. In some special conditions, the use of sample and injection manifolds is required to make the test tracer and ventilating duct air fully mixed, so as to get the on-spot typical sample. Methods: This paper introduces the technology and application of the sample and injection manifolds in nuclear air-cleaning system. Results: Multi point injection and multi point sampling technology as an effective experimental method, has been used in a of domestic and international nuclear facilities. Conclusion: The technology solved the problem of uniformly of on-spot injection and sampling,which plays an important role in objectively evaluating the function of nuclear air-cleaning system. (authors)

  12. The Political Economy of Clean Air Legislation. An Analysis of Voting in the U.S. Senate on Amendments to the 1990 Clean Air Act

    International Nuclear Information System (INIS)

    Burkey, M.L.; Durden, G.C.

    1998-01-01

    Much research in political science and economics has attempted to explain voting patterns among members of legislative bodies. In this paper we extend the existing analysis in three ways. First, we address the subject of voting on air quality regulation by the U.S. Senate. A subject of great importance and significance, such votes have not previously been the focus of much empirical investigation. Second, we develop an arguably more correct and effective methodology for measuring and understanding the ideological preferences of individual Senators, as revealed by their voting patterns on 1990 amendments to the Clean Air Act. Third, we apply the minimum chi-square methodology for estimating the determinants of Senator voting patterns on the issue. In Section 2, the economic theory of regulation is elaborated as it is specifically related to 1990 senate voting on amendments to the Clean Air Act. In Section 3, we provide a brief literature review, focusing on the principal-agent model and how voting patterns are influenced by campaign contributions, constituent socio-economic characteristics, and individual legislator ideology. In Section 4 we present a very simple model of the principal-agent relationship which underlies legislative voting behavior. In this section (supplemented by information in an appendix) we introduce a new methodology for creating a proxy variable to represent legislator ideology, comparing the new method with those previously used. Section 5 provides a chronological background on clean air legislation, and Section 6 discusses the data and proxy variables used for the empirical estimations. Section 7 contains a presentation and evaluation of three empirical techniques, including one not previously used, the minimum chi-square method which, we argue, is both appropriate and easily interpretable. This claim is based upon the fact that the dependent variable, SCORE, is neither continuous nor dichotomous, but ordered and categorical, constructed

  13. Wet-air oxidation cleans up black wastewater

    Energy Technology Data Exchange (ETDEWEB)

    1993-09-01

    Sterling Organics produces the analgesic paracetamol (acetaminophen) at its Dudley, England, plant. The wastewater from the batch process contains intermediates such as para-aminophenol (PAP) and byproducts such as thiosulfates, sulfites and sulfides. To stay ahead of increasingly strict environmental legislation, Sterling Organics installed a wet-air oxidation system at the Dudley facility in August 1992. The system is made by Zimpro Environmental Inc. (Rothschild, Wis.). Zimpro's wet-air oxidation system finds a way around the limitations of purely chemical or physical processes. In the process, compressed air at elevated temperature and pressure oxidizes the process intermediates and byproducts and removes the color from the wastewater.

  14. 75 FR 34647 - Approval of the Clean Air Act, Section 112(l), Authority for Hazardous Air Pollutants: Air...

    Science.gov (United States)

    2010-06-18

    ... Solvent NESHAP for cleaning or drying parts, except any cold cleaning machine that uses a solvent which... cleaning machines in which parts such as film, coils, wire, and metal strips are cleaned at speeds... requires each cleaning machine to have [[Page 34650

  15. Users view of the reliability of air cleaning systems in nuclear facilities

    International Nuclear Information System (INIS)

    Kovach, J.L.

    1975-01-01

    The state of the art of air cleaning systems has advanced, but a wealth of knowledge did not result in a commensurate increase in the improvement of the design, manufacture, and operation of air cleaning systems. Often the developed data is not available or known to the designer, equipment supplier or operator. There are still systems installed where the equipment will operate under the specified criteria only when it is new and little thought is given to the subsequent maintainance and operating problems. The dissemination of available information to all of those concerned with the design, construction, installation, and operation of air cleaning systems through relevant standards, guides, etc. is unsatisfactory at the present time. (U.S.)

  16. G20 Clean Energy, and Energy Efficiency Deployment and Policy Progress

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2011-07-01

    G-20 Clean Energy, and Energy Efficiency Deployment and Policy Progress, a report prepared by the International Energy Agency (IEA) in collaboration with the G-20 Clean Energy and Energy Efficiency Working Group, provides an overview of clean energy and energy efficiency technology deployment and summarises support policies in place across G-20 countries. The report highlights that while clean energy technology deployment has made steady progress and energy efficiency improvements have been made, continued reliance on fossil fuels to meet growth in global energy demand presents a significant challenge. Scaling-up the deployment of renewable energy, in addition to improving end-use efficiency, enhancing the efficiency of fossil fuel based power generation, and supporting the widespread deployment of CCS will, therefore, also be crucial aspects of the transition to a cleaner energy future. Because the G-20 group of countries represent close to 80% of energy-related CO2 emissions, by developing and deploying energy efficiency and clean energy technologies, they are presented with a unique opportunity to make collective progress in transitioning the global energy system. IEA Deputy Executive Director Richard Jones emphasised the importance of G-20 efforts, saying, 'The IEA welcomes this important collaboration with the G-20. Enhanced deployment of clean energy technologies and of energy efficiency improvements offers energy security and environmental benefits. It will also enable cost savings over the medium and long term -- an aspect that is particularly relevant at a time of economic uncertainty. We believe that enhanced policy assessment and analysis, building on this initial report, will enable governments to take more cost effective and efficient policy decisions.' This report was issued on the authority of the IEA Executive Director, it does not necessarily represent the views of IEA Member countries or the G20.

  17. G20 Clean Energy, and Energy Efficiency Deployment and Policy Progress

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2011-07-01

    G-20 Clean Energy, and Energy Efficiency Deployment and Policy Progress, a report prepared by the International Energy Agency (IEA) in collaboration with the G-20 Clean Energy and Energy Efficiency Working Group, provides an overview of clean energy and energy efficiency technology deployment and summarises support policies in place across G-20 countries. The report highlights that while clean energy technology deployment has made steady progress and energy efficiency improvements have been made, continued reliance on fossil fuels to meet growth in global energy demand presents a significant challenge. Scaling-up the deployment of renewable energy, in addition to improving end-use efficiency, enhancing the efficiency of fossil fuel based power generation, and supporting the widespread deployment of CCS will, therefore, also be crucial aspects of the transition to a cleaner energy future. Because the G-20 group of countries represent close to 80% of energy-related CO2 emissions, by developing and deploying energy efficiency and clean energy technologies, they are presented with a unique opportunity to make collective progress in transitioning the global energy system. IEA Deputy Executive Director Richard Jones emphasised the importance of G-20 efforts, saying, 'The IEA welcomes this important collaboration with the G-20. Enhanced deployment of clean energy technologies and of energy efficiency improvements offers energy security and environmental benefits. It will also enable cost savings over the medium and long term -- an aspect that is particularly relevant at a time of economic uncertainty. We believe that enhanced policy assessment and analysis, building on this initial report, will enable governments to take more cost effective and efficient policy decisions.' This report was issued on the authority of the IEA Executive Director, it does not necessarily represent the views of IEA Member countries or the G20.

  18. Cleaning products and air fresheners: emissions and resulting concentrations of glycol ethers and terpenoids.

    Science.gov (United States)

    Singer, B C; Destaillats, H; Hodgson, A T; Nazaroff, W W

    2006-06-01

    Experiments were conducted to quantify emissions and concentrations of glycol ethers and terpenoids from cleaning product and air freshener use in a 50-m3 room ventilated at approximately 0.5/h. Five cleaning products were applied full-strength (FS); three were additionally used in dilute solution. FS application of pine-oil cleaner (POC) yielded 1-h concentrations of 10-1300 microg/m3 for individual terpenoids, including alpha-terpinene (90-120), d-limonene (1000-1100), terpinolene (900-1300), and alpha-terpineol (260-700). One-hour concentrations of 2-butoxyethanol and/or d-limonene were 300-6000 microg/m3 after FS use of other products. During FS application including rinsing with sponge and wiping with towels, fractional emissions (mass volatilized/dispensed) of 2-butoxyethanol and d-limonene were 50-100% with towels retained, and approximately 25-50% when towels were removed after cleaning. Lower fractions (2-11%) resulted from dilute use. Fractional emissions of terpenes from FS use of POC were approximately 35-70% with towels retained, and 20-50% with towels removed. During floor cleaning with dilute solution of POC, 7-12% of dispensed terpenes were emitted. Terpene alcohols were emitted at lower fractions: 7-30% (FS, towels retained), 2-9% (FS, towels removed), and 2-5% (dilute). During air-freshener use, d-limonene, dihydromyrcenol, linalool, linalyl acetate, and beta-citronellol) were emitted at 35-180 mg/day over 3 days while air concentrations averaged 30-160 microg/m3. While effective cleaning can improve the healthfulness of indoor environments, this work shows that use of some consumer cleaning agents can yield high levels of volatile organic compounds, including glycol ethers--which are regulated toxic air contaminants--and terpenes that can react with ozone to form a variety of secondary pollutants including formaldehyde and ultrafine particles. Persons involved in cleaning, especially those who clean occupationally or often, might encounter

  19. The regulation of hazardous air pollutants under the Clean Air Act Amendments of 1990: Effects on the Portland cement industry

    International Nuclear Information System (INIS)

    Mikols, E.H.; Gill, A.S.; Dougherty, A.

    1996-01-01

    Title III of the 1990 Clean Air Act Amendments (CAAA) addresses the control of hazardous air pollutants (HAPs) from major sources of air pollution in the US. In the CAAA, Congress defined 189 compounds as hazardous air pollutants in need of additional control by the Environmental Protection Agency (EPA). Congress directed EPA to identify the major source categories which emit HAPs and to prepare regulations that would reduce and control future HAP emissions. This paper outlines the activities undertaken by EPA to regulate HAP emissions from Portland cement plants and the program developed by the Portland cement manufacturing industry to cope with Title III

  20. Efficiancy of hydrogen peroxide for cleaning production areas and equipments in the radiopharmaceutical production

    Energy Technology Data Exchange (ETDEWEB)

    Baptista, Tatyana S.; Batista, Vanessa; Gomes, Antonio; Matsuda, Margareth; Fukumori, Neuza; Araujo, Elaine B. de, E-mail: tsbaptista@ipen.br [Instituto de Pesquisas Energeticas e Nucleares (IPEN/CNEN-SP), Sao Paulo, SP (Brazil)

    2013-07-01

    A great challenge in the radiopharmaceuticals production is to fulfill the Good Manufacturing Practices (GMPs), involving the validation of process and of all supporting activities such as cleaning and sanitization. The increasingly strict requirements for quality assurance system, with several norms and normative resolutions has led to a constant concern with programs and cleaning validation in pharmaceutical production. The main goal of GMP is to reduce risks inherent to pharmaceutical production, that is to reduce product contamination with microorganisms and cross-contamination. The basic requirements to prevent contamination is the development and implementation of efficient cleaning programs. In the case of clean rooms for the production of injectable radiopharmaceuticals, the requirement for cleaning programs is evidently higher due to the characteristics of these areas with hot cells for radioactive materials, where sterile radiopharmaceuticals are manipulated and distributed before administration to patients just after minutes or hours of its preparation. In the Radiopharmacy Department at IPEN it was established a cleaning program for clean rooms and hot cells using a hydrogen peroxide solution (20% proxitane alfa). The objective of this work was to assess effectiveness of this cleaning agent in reducing and/or eliminating microbial load in the clean rooms and equipment to acceptable levels in accordance with the current legislation. The analysis was conducted using results of the environmental monitoring program with and settling contact plates in clean rooms after the cleaning procedures. Furthermore, it was possible to evaluate the action of the sanitizing agent on the microbial population on the surface of equipment and clean rooms. It was also evaluated the best way to accomplish the cleaning program considering the dosimetric factor in each production process, as the main concern of pharmaceutical companies is the microbiological contamination, in

  1. Efficiancy of hydrogen peroxide for cleaning production areas and equipments in the radiopharmaceutical production

    International Nuclear Information System (INIS)

    Baptista, Tatyana S.; Batista, Vanessa; Gomes, Antonio; Matsuda, Margareth; Fukumori, Neuza; Araujo, Elaine B. de

    2013-01-01

    A great challenge in the radiopharmaceuticals production is to fulfill the Good Manufacturing Practices (GMPs), involving the validation of process and of all supporting activities such as cleaning and sanitization. The increasingly strict requirements for quality assurance system, with several norms and normative resolutions has led to a constant concern with programs and cleaning validation in pharmaceutical production. The main goal of GMP is to reduce risks inherent to pharmaceutical production, that is to reduce product contamination with microorganisms and cross-contamination. The basic requirements to prevent contamination is the development and implementation of efficient cleaning programs. In the case of clean rooms for the production of injectable radiopharmaceuticals, the requirement for cleaning programs is evidently higher due to the characteristics of these areas with hot cells for radioactive materials, where sterile radiopharmaceuticals are manipulated and distributed before administration to patients just after minutes or hours of its preparation. In the Radiopharmacy Department at IPEN it was established a cleaning program for clean rooms and hot cells using a hydrogen peroxide solution (20% proxitane alfa). The objective of this work was to assess effectiveness of this cleaning agent in reducing and/or eliminating microbial load in the clean rooms and equipment to acceptable levels in accordance with the current legislation. The analysis was conducted using results of the environmental monitoring program with and settling contact plates in clean rooms after the cleaning procedures. Furthermore, it was possible to evaluate the action of the sanitizing agent on the microbial population on the surface of equipment and clean rooms. It was also evaluated the best way to accomplish the cleaning program considering the dosimetric factor in each production process, as the main concern of pharmaceutical companies is the microbiological contamination, in

  2. Hydrogen energy - Abundant, efficient, clean: A debate over the energy-system-of-change

    Energy Technology Data Exchange (ETDEWEB)

    Winter, Carl-Jochen [International Association for Hydrogen Energy (IAHE), c/o ENERGON Carl-Jochen Winter e.K., Obere St.-Leonhardstr. 9, 88662 Ueberlingen (Germany)

    2009-07-15

    Both secondary energies, electricity and hydrogen, have much in common: they are technology driven; both are produced from any available primary energy; once produced both are environmentally and climatically clean over the entire length of their respective conversion chains, from production to utilization; they are electrochemically interchangeable via electrolyses and fuel cells; both rely on each other, e.g., when electrolyzers and liquefiers need electricity or when electricity-providing low temperature fuel cells need hydrogen; in cases of secondary energy transport over longer distances they compete with each other; in combined fossil fuel cycles both hydrogen and electricity are produced in parallel exergetically highly efficiently; hydrogen in addition to electricity helps exergizing the energy system and, thus, maximizing the available technical work. There are dissimilarities, too: electricity transports information, hydrogen does not; hydrogen stores and transports energy, electricity does not (in macroeconomic terms). The most obvious dissimilarity is their market presence, both in capacities and in availability: Electricity is globally ubiquitous (almost), whilst hydrogen energy is still used in only selected industrial areas and in much smaller capacities. The article describes in 15 chapters, 33 figures, 3 tables, and 2 Annexes the up-and-coming hydrogen energy economy, its environmental and climatic relevance, its exergizing influence on the energy system, its effect on decarbonizing fossil fueled power plants, the introduction of the novel non-heat-engine-related electrochemical energy converter fuel cell in portable electronics, in stationary and mobile applications. Hydrogen guarantees environmentally and climatically clean transportation on land, in air and space, and at sea. Hydrogen facilitates the electrification of vehicles with practically no range limits. (author)

  3. 77 FR 16548 - Clean Air Act Advisory Committee

    Science.gov (United States)

    2012-03-21

    ..., and consensus-building skills. --Ability to volunteer time to attend meetings 2-3 times a year... third term. The CAAAC usually meets 2-3 times annually with workgroups meeting more frequently. The... governments issues. --Experience working with air quality policy issues. --Executive management level...

  4. The Krakow clean fossil fuels and energy efficiency program

    Energy Technology Data Exchange (ETDEWEB)

    Feibus, H.

    1995-12-31

    The joint effort by Polish and American organizations in Krakow has accomplished a great deal in just a few years. In particular, the low emission sources program has had major successes. Poland and America have a lot to learn from each other in the clean and economical use of coal. Both our countries are major producers and users of coal. Both have had to deal with the emissions of particulate and organics from coal combustion. We were fortunate, since our free market economy and democratic government helped us deal with a lot of these problems in the 1950s. In Poland, the freedom to solve these problems has evolved only in the last few years. In the first phase of the program, Polish and American engineers ran combustion tests on boilers and stoves in Krakow. They also performed analyses on the cost and feasibility of various equipment changes. The results of the first phase were used in refining the spreadsheet model to give better estimates of costs emissions. The first phase also included analyses of incentives for proceeding with needed changes. These analyses identified actions needed to create a market for the goods and services which control pollution. Such actions could include privatization, regulation, or financial incentives. The second phase of the program consisted of public meetings in Chicago, Washington, and Krakow. The purpose of the meetings was to inform U.S. and Polish firms about the results of phase 1 and to encourage them to compete to take part in phase 3. The third phase currently underway consists of the commercial ventures that were competitively selected. These ventures were consistent with recommendations unanimously made by the BSC. The three phases of the Polish-American program are discussed.

  5. Human Response to Ductless Personalized Ventilation with Local Air Cleaning: Air Quality and Prevalence of SBS Symptoms

    DEFF Research Database (Denmark)

    Dalewski, Mariusz; Bivolarova, Maria; Fillon, Maelys

    2013-01-01

    The impact of local air cleaning and cooling of the head region by ductless personalized ventilation (DPV) on perceived air quality (PAQ) and Sick Building Syndrome (SBS) symptoms was studied. Thirty subjects participated in experiments performed in a test room with displacement ventilation (DV...... with air filter and 29 °C with DPV without filter. During the experiments the subjects simulated office work and answered on computerized questionnaires. At warm environment PAQ and air freshness significantly improved when DPV was used. Eye dryness increased significantly with time but was not influenced...... by air temperature and filtering. At 29 °C the facially applied air movement from DPV increased the eye dryness. The SBS symptoms increased with time and were higher (not significantly) at the warm conditions. Air movement did not have profound impact on the SBS symptoms, while filtering had only at 23...

  6. Is the perception of clean, humid air indeed affected by cooling the respiratory tract?

    Science.gov (United States)

    Burek, Rudolf; Polednik, Bernard; Guz, Łukasz

    2017-07-01

    The study aims at determining exposure-response relationships after short exposure to clean air and long exposure to air polluted by people. The impact of water vapor content in the indoor air on its acceptability (ACC) was assessed by the occupants after a short exposure to clean air and an hour-long exposure to increasingly polluted air. The study presents a critical analysis pertaining to the stimulation of olfactory sensations by the air enthalpy suggested in previous models and proposes a new model based on the Weber-Fechner law. Our assumption was that water vapor is the stimulus of olfactory sensations. The model was calibrated and verified in field conditions, in a mechanically ventilated and air conditioned auditorium. Measurements of the air temperature, relative humidity, velocity and CO2 content were carried out; the acceptability of air quality was assessed by 162 untrained students. The subjective assessments and the measurements of the environmental qualities allowed for determining the Weber coefficients and the threshold concentrations of water vapor, as well as for establishing the limitations of the model at short and long exposure to polluted indoor air. The results are in agreement with previous studies. The standard error equals 0.07 for immediate assessments and 0.17 for assessments after adaptation. Based on the model one can predict the ACC assessments of trained and untrained participants.

  7. Proceedings of the 10th world clean air congress. Emissions and control

    International Nuclear Information System (INIS)

    Tolvanen, M.; Anttila, P.; Kaemaeri, J.

    1995-01-01

    Rapid economical growth and expansion of human population have produced a number of environmental problems with varying geographic dimensions. While local problems remain near the pollution sources, the focus of the scientific community is more and more shifted towards regional, continental and global consequences of air pollutants. The theme of the 10th Clean Air Congress 'Growing Challenges from Local to Global' reflects the growing demand from the scientific and professional community working in air pollution prevention and environmental protection - more and more complex mechanisms should be understood on a growing spatial scale. The 10th World Clean Air Congress addresses in its more than 400 presentations, documented in three Volumes of Proceedings, the history, the present and the potential futures of the air pollution problems. Air has during different times always represented something valuable to people: the logo of the Congress, the octahedron sign, sympolizes the element of air in acient Greek philosophy. Today air quality is not only valued as important, it is a death serious matter. This Volume includes the presentations of the path A 'Emissions and Control' of the Congress. This path deals with issues related to measurement, monitoring and inventories of air pollutants from mobile and stationary sources, and the various ways to control the emissions of acidifying pollutants, air toxics and aerosols, volatile organic compounds, and odours. Integrated approaches to pollution prevention and non-waste technologies in various industrial sectors, have recently obtained special attention

  8. Evaluation of the Ventilation and Air Cleaning System Design Concepts for Safety Requirements during Fire Conditions in Nuclear Applications

    International Nuclear Information System (INIS)

    Rashad, S.; El-Fawal, M.; Kandil, M.

    2013-01-01

    The ventilation and air cleaning system in the nuclear or radiological installations is one of the essential nuclear safety concerns. It is responsible for confining the radioactive materials involved behind suitable barriers during normal and abnormal conditions. It must be designed to prevent the release of harmful products (radioactive gases, or airborne radioactive materials) from the system or facility, impacting the public or workers, and doing environmental damage. There are two important safety functions common to all ventilation and air cleaning system in nuclear facilities. They are: a) the requirements to maintain the pressure of the ventilated volume below that of surrounding, relatively non-active areas, in order to inhibit the spread of contamination during normal and abnormal conditions, and b) the need to treat the ventilated gas so as to minimize the release of any radioactive or toxic materials. Keeping the two important safety functions is achieved by applying the fire protection for the ventilation system to achieve safety and adequate protection in nuclear applications facilities during fire and accidental criticality conditions.The main purpose of this research is to assist ventilation engineers and experts in nuclear installations for safe operation and maintaining ventilation and air cleaning system during fire accident in nuclear facilities. The research focuses on fire prevention and protection of the ventilation systems in nuclear facilities. High-Efficiency particulate air (HEPA) filters are extremely susceptible to damage when exposed to the effects of fire, smoke, and water; it is the intent of this research to provide the designer with the experience gained over the years from hard lessons learned in protecting HEPA filters from fire. It describes briefly and evaluates the design safety features, constituents and working conditions of ventilation and air cleaning system in nuclear and radioactive industry.This paper provides and

  9. A baseline evaluation of casino air quality after enactment of Nevada's Clean Indoor Air Act.

    Science.gov (United States)

    York, Nancy L; Lee, Kiyoung

    2010-01-01

    The U.S. Surgeon General reports that there is no safe level of exposure to secondhand smoke (SHS). The purpose of this study was to measure levels of fine particulate matter in nonsmoking casino restaurants after enactment of Nevada's Clean Indoor Air Act (NCIAA). Fine particulate mattercasino hotel restaurants and gaming areas for a total of 32 venues. A battery-operated SidePak aerosol monitor was discreetly used for at least 30 min in each venue. Nonsmoking restaurant PM2.5 levels ranged from 5 to 101 microg/m3 (M=31; SD=22.9) while gaming areas ranged from 20 to 73 microg/m3 (M=48; SD=15.9). There was a significant difference in PM2.5 between restaurants and gaming areas, t30=-2.54, p=.017. There was also a strong correlation between the levels of restaurant PM2.5 and gaming area PM2.5 (r=.71; p=.005). Fine PM2.5 in all casino areas was above what the Environmental Protection Agency recommends as healthy. This information can be used to educate policy decision makers when discussing potential strengthening of the law.

  10. Clean Air Act : historical information on EPA's process for reviewing California waiver requests and making waiver determinations

    Science.gov (United States)

    2009-01-01

    Emissions from mobile sources, such as automobiles and trucks, contribute to air quality degradation and can threaten public health and the environment. Under the Clean Air Act, the Environmental Protection Agency (EPA) regulates these emissions. The...

  11. Effects of welding fumes on nuclear air cleaning system carbon adsorber banks

    Energy Technology Data Exchange (ETDEWEB)

    Roberson, P.W. [Duke Power Company, Huntersville, NC (United States)

    1997-08-01

    Standard Technical Specifications for nuclear air cleaning systems include requirements for surveillance tests following fire, painting, or chemical release in areas communicating with the affected system. To conservatively implement this requirement, many plants categorize welding as a chemical release process, and institute controls to ensure that welding fumes do not interact with carbon adsorbers in a filter system. After reviewing research data that indicated welding had a minimal impact on adsorber iodine removal efficiency, further testing was performed with the goal of establishing a welding threshold. It was anticipated that some quantity of weld electrodes could be determined that had a corresponding detrimental impact on iodine removal efficiency for the exposed adsorber. This value could be used to determine a conservative sampling schedule that would allow the station to perform laboratory testing to ensure system degradation did not occur without a full battery of surveillance tests. A series of tests was designed to demonstrate carbon efficiency versus cumulative welding fume exposure. Three series of tests were performed, one for each of three different types of commonly used weld electrodes. Carbon sampling was performed at baseline conditions, and every five pounds of electrode thereafter. Two different laboratory tests were performed for each sample; one in accordance with ASTM 3803/1989 at 95% relative humidity and 30 degrees C, and another using the less rigorous conditions of 70% relative humidity and 80 degrees C. Review of the test data for all three types of electrodes failed to show a significant correlation between carbon efficiency degradation and welding fume exposure. Accordingly, welding is no longer categorized as a `chemical release process` at McGuire Nuclear Station, and limits on welding fume interaction with ventilation systems have been eliminated. 4 refs., 3 figs., 1 tab.

  12. Dynamics Analysis of Castor Hulling in the Process of Air-and-Screen Cleaning

    Directory of Open Access Journals (Sweden)

    Gao Ruitao

    2016-01-01

    Full Text Available The air-and-screen cleaning mechanism of castor hulling is analyzed in this paper. And the numeric expression equations of the castor dynamics analysis are established. The correlation of floating speeds vp, air speeds w, the direction angle of airflow velocity β, the direction angle of vibration δ, the friction angle ϕ, the slip coefficient, the fell coefficient and the jumping coefficient are analyzed.

  13. Dynamics Analysis of Castor Hulling in the Process of Air-and-Screen Cleaning

    OpenAIRE

    Gao Ruitao; Cao Yuhua; Yao Liangliang; Jin Hong

    2016-01-01

    The air-and-screen cleaning mechanism of castor hulling is analyzed in this paper. And the numeric expression equations of the castor dynamics analysis are established. The correlation of floating speeds vp, air speeds w, the direction angle of airflow velocity β, the direction angle of vibration δ, the friction angle ϕ, the slip coefficient, the fell coefficient and the jumping coefficient are analyzed.

  14. Off-gas and air cleaning systems for accident conditions in nuclear power plants

    International Nuclear Information System (INIS)

    1993-01-01

    This report surveys the design principles and strategies for mitigating the consequences of abnormal events in nuclear power plants by the use of air cleaning systems. Equipment intended for use in design basis accident and severe accident conditions is reviewed, with reference to designs used in IAEA Member States. 93 refs, 48 figs, 23 tabs

  15. 75 FR 62421 - Notice of Lodging of Consent Decree Under the Clean Air Act

    Science.gov (United States)

    2010-10-08

    ... States of America v. James Valley Ethanol, LLC, Northern Lights Ethanol, LLC, and Poet Plant Management... Ethanol, LLC (``James Valley''), Northern Lights Ethanol, LLC (``Northern Lights''), and POET Plant Management (``POET'') pursuant to Sections 111 and 502(a) of the Clean Air Act (the ``Act''), 42 U.S.C. 7411...

  16. 77 FR 44544 - Approval and Promulgation of Air Quality Implementation Plans; Utah; Determination of Clean Data...

    Science.gov (United States)

    2012-07-30

    ... further progress plans, reasonably available control measures, and contingency measures, no longer apply... Promulgation of Air Quality Implementation Plans; Utah; Determination of Clean Data for the 1987 PM 10 Standard... VI. Statutory and Executive Order Reviews Definitions For the purpose of this document, we are giving...

  17. 78 FR 38074 - Notice of Lodging of Proposed Consent Decree Under the Clean Air Act

    Science.gov (United States)

    2013-06-25

    ... manufacturing plants operating in as many states. The states of Arkansas, Idaho, Kansas, Montana, Nebraska... DEPARTMENT OF JUSTICE Notice of Lodging of Proposed Consent Decree Under the Clean Air Act On June... Court for the District of Kansas in the lawsuit entitled United States et al. v. Ash Grove Cement...

  18. 78 FR 43200 - Proposed Settlement Agreement, Clean Air Act Citizen Suit

    Science.gov (United States)

    2013-07-19

    ... Social Responsibility--Los Angeles v. EPA, No. 12-56175, upon receipt of written notice from EPA that the... ENVIRONMENTAL PROTECTION AGENCY [EPA-HQ-OGC-2013-0484; FRL-9835-6] Proposed Settlement Agreement, Clean Air Act Citizen Suit AGENCY: Environmental Protection Agency (EPA). ACTION: Notice of proposed...

  19. Dependence of adsorption quality of carbon in NPP air cleaning systems

    International Nuclear Information System (INIS)

    Vujisic, Lj.

    1994-01-01

    A relationship which describes the influence of aging, relative humidity and organic poisons on the adsorption quality of coconut charcoal has been established. The relationship is rearranged for easy calculation of the reliable operation time of the adsorbent media in charcoal filters of any single nuclear air-cleaning system during accidental and incidental situation of NPP (author)

  20. Proceedings of the 10th world clean air congress. Impacts and management

    Energy Technology Data Exchange (ETDEWEB)

    Kaemaeri, J.; Tolvanen, M.; Anttila, P.; Salonen, R.O. [eds.

    1995-12-31

    Rapid economical growth and expansion of human population have produced a number of environmental problems with varying geographic dimensions. While local problems remain near the pollution sources, the focus of the scientific community is more and more shifted towards regional, continental and global consequences of air pollutants. The theme of the 10th Clean Air Congress `Growing Challenges from Local to Global` reflects the growing demand from the scientific and professional community working in air pollution prevention and environmental protection - more and more complex mechanisms should be understood on a growing spatial scale. The 10th World Clean Air Congress addresses in its more than 400 presentations, documented in three Volumes of Proceedings, the history, the present and the potential futures of the air pollution problems. This volume includes all papers of paths C `Pollutant Impacts`, D `Pollution Management`, and E `Health Effects`. Path C includes numerous highly relevant papers dealing with climate change and greenhouse gases, as well as with environmental effects of air pollutants mostly on materials and vegetation. The most critical issues on air pollutant management throw light on national and regional abatement strategies and on the applicability of various tools for pollution management. The path on effects on human health includes a session on `Air pollution epidemiology` sponsored by the Economic Commission for Europe and a session on `Health effect control strategies` sponsored by the UN World Health Organization. In these sessions invited speakers describe the current understanding of human responses to air pollution exposure

  1. Proceedings of the 10th world clean air congress. Impacts and management

    Energy Technology Data Exchange (ETDEWEB)

    Kaemaeri, J; Tolvanen, M; Anttila, P; Salonen, R O [eds.

    1996-12-31

    Rapid economical growth and expansion of human population have produced a number of environmental problems with varying geographic dimensions. While local problems remain near the pollution sources, the focus of the scientific community is more and more shifted towards regional, continental and global consequences of air pollutants. The theme of the 10th Clean Air Congress `Growing Challenges from Local to Global` reflects the growing demand from the scientific and professional community working in air pollution prevention and environmental protection - more and more complex mechanisms should be understood on a growing spatial scale. The 10th World Clean Air Congress addresses in its more than 400 presentations, documented in three Volumes of Proceedings, the history, the present and the potential futures of the air pollution problems. This volume includes all papers of paths C `Pollutant Impacts`, D `Pollution Management`, and E `Health Effects`. Path C includes numerous highly relevant papers dealing with climate change and greenhouse gases, as well as with environmental effects of air pollutants mostly on materials and vegetation. The most critical issues on air pollutant management throw light on national and regional abatement strategies and on the applicability of various tools for pollution management. The path on effects on human health includes a session on `Air pollution epidemiology` sponsored by the Economic Commission for Europe and a session on `Health effect control strategies` sponsored by the UN World Health Organization. In these sessions invited speakers describe the current understanding of human responses to air pollution exposure

  2. Application of nuclear air cleaning and treatment codes

    International Nuclear Information System (INIS)

    Kriskovich, J.R.

    1995-01-01

    All modifications to existing ventilation systems, as well as any new ventilation systems used on the Hanford Site are required to meet both American Society of Mechanical Engineers (ASME) codes N509 and N510. Difficulties encountered when applying code N509 at the Hanford Site include the composition of the ventilation air stream and requirements related to ventilation equipment procurement. Also, the existing ventilation systems for the waste tanks at the Hanford Site cannot be tested in accordance with code N510 because of the current configuration of these systems

  3. Application of nuclear air cleaning and treatment codes

    Energy Technology Data Exchange (ETDEWEB)

    Kriskovich, J.R. [Westinghouse Hanford Company, Richland, WA (United States)

    1995-02-01

    All modifications to existing ventilation systems, as well as any new ventilation systems used on the Hanford Site are required to meet both American Society of Mechanical Engineers (ASME) codes N509 and N510. Difficulties encountered when applying code N509 at the Hanford Site include the composition of the ventilation air stream and requirements related to ventilation equipment procurement. Also, the existing ventilation systems for the waste tanks at the Hanford Site cannot be tested in accordance with code N510 because of the current configuration of these systems.

  4. 23 CFR 633.211 - Implementation of the Clean Air Act and the Federal Water Pollution Control Act.

    Science.gov (United States)

    2010-04-01

    ... Water Pollution Control Act. 633.211 Section 633.211 Highways FEDERAL HIGHWAY ADMINISTRATION, DEPARTMENT...) implementing requirements with respect to the Clean Air Act and the Federal Water Pollution Control Act are... Contracts (Appalachian Contracts) § 633.211 Implementation of the Clean Air Act and the Federal Water...

  5. 78 FR 69709 - Notice of Extension to Public Comment Period for Consent Decree Under the Clean Air Act and the...

    Science.gov (United States)

    2013-11-20

    ... Clean Air Act and the Emergency Planning and Community Right- To Know Act'' On September 30, 2013, the... lawsuit filed under the Clean Air Act and the Emergency Planning & Community Right to Know Act, the United... would receive comments concerning the settlement for a period of thirty (30) days from the date of...

  6. 40 CFR 60.3066 - What are the emission limitations for air curtain incinerators that burn only wood waste, clean...

    Science.gov (United States)

    2010-07-01

    ... air curtain incinerators that burn only wood waste, clean lumber, and yard waste? 60.3066 Section 60... Waste Incineration Units That Commenced Construction On or Before December 9, 2004 Model Rule-Air Curtain Incinerators That Burn Only Wood Waste, Clean Lumber, and Yard Waste § 60.3066 What are the...

  7. 75 FR 75463 - Clean Air Act Operating Permit Program; Petition To Object to Title V Permit for Luke Paper...

    Science.gov (United States)

    2010-12-03

    ... ENVIROMENTAL PROTECTION AGENCY [FRL-9234-9] Clean Air Act Operating Permit Program; Petition To Object to Title V Permit for Luke Paper Company, Luke, MD AGENCY: Environmental Protection Agency (EPA). ACTION: Notice of final action. SUMMARY: Pursuant to section 505(b)(2) of the Clean Air Act (CAA), the...

  8. Air emission points for facilities in Iowa with operating permits for Title V of the Federal Clean Air Act_considered MAJOR permits

    Data.gov (United States)

    Iowa State University GIS Support and Research Facility — Air emission points for facilities in Iowa with operating permits for Title V of the Federal Clean Air Act, considered "major" permits. Also includes emission points...

  9. Demand for Clean Energies Efficient Development in Buildings Technologies

    International Nuclear Information System (INIS)

    Mustafa Omer, Abdeen

    2017-01-01

    Aims/Purpose: The increased availability of reliable and efficient energy services stimulates new development alternatives. This article discusses the potential for such integrated systems in the stationary and portable power market in response to the critical need for a cleaner energy technology. Throughout the theme several issues relating to renewable energies, environment, and sustainable development are examined from both current and future perspectives. It is concluded that green energies like wind, solar, ground source heat pumps, and biomass must be promoted, implemented, and demonstrated from the economic and/or environmental point view. Biogas from biomass appears to have potential as an alternative energy source, which is potentially rich in biomass resources. This is an overview of some salient points and perspectives of biogas technology. The current literature is reviewed regarding the ecological, social, cultural and economic impacts of biogas technology. This article gives an overview of present and future use of biomass as an industrial feedstock for production of fuels, chemicals and other materials. However, to be truly competitive in an open market situation, higher value products are required. Results suggest that biogas technology must be encouraged, promoted, invested, implemented, and demonstrated, but especially in remote rural areas. Study design: Anticipated patterns of future energy use and consequent environmental impacts (acid precipitation, ozone depletion and the greenhouse effect or global warming) are comprehensively discussed in this article. Place and Duration of Study: National Centre for Research, Energy Research Institute (ERI), between January 2014 and July 2015. (author)

  10. Needs, resources and climate change: Clean and efficient conversion technologies

    KAUST Repository

    Ghoniem, Ahmed F.

    2011-02-01

    Energy "powers" our life, and energy consumption correlates strongly with our standards of living. The developed world has become accustomed to cheap and plentiful supplies. Recently, more of the developing world populations are striving for the same, and taking steps towards securing their future energy needs. Competition over limited supplies of conventional fossil fuel resources is intensifying, and more challenging environmental problems are springing up, especially related to carbon dioxide (CO 2) emissions. There is strong evidence that atmospheric CO 2 concentration is well correlated with the average global temperature. Moreover, model predictions indicate that the century-old observed trend of rising temperatures could accelerate as carbon dioxide concentration continues to rise. Given the potential danger of such a scenario, it is suggested that steps be taken to curb energy-related CO 2 emissions through a number of technological solutions, which are to be implemented in a timely fashion. These solutions include a substantial improvement in energy conversion and utilization efficiencies, carbon capture and sequestration, and expanding the use of nuclear energy and renewable sources. Some of these technologies already exist, but are not deployed at sufficiently large scale. Others are under development, and some are at or near the conceptual state. © 2010 Elsevier Ltd. All rights reserved.

  11. [Assessment of the air quality improment of cleaning and disinfection on central air-conditioning ventilation system].

    Science.gov (United States)

    Liu, Hongliang; Zhang, Lei; Feng, Lihong; Wang, Fei; Xue, Zhiming

    2009-09-01

    To assess the effect of air quality of cleaning and disinfection on central air-conditioning ventilation systems. 102 air-conditioning ventilation systems in 46 public facilities were sampled and investigated based on Hygienic assessment criterion of cleaning and disinfection of public central air-conditioning systems. Median dust volume decreased from 41.8 g/m2 to 0.4 g/m2, and the percentage of pipes meeting the national standard for dust decreased from 17.3% (13/60) to 100% (62/62). In the dust, median aerobic bacterial count decreased from 14 cfu/cm2 to 1 cfu/cm2. Median aerobic fungus count decreased from 10 cfu/cm2 to 0 cfu/cm2. The percentage of pipes with bacterial and fungus counts meeting the national standard increased from 92.4% (171/185) and 82.2% (152/185) to 99.4% (165/166) and 100% (166/166), respectively. In the ventilation air, median aerobic bacterial count decreased from 756 cfu/m3 to 229 cfu/m3. Median aerobic fungus count decreased from 382 cfu/m3 to 120 cfu/m3. The percentage of pipes meeting the national standard for ventilation air increased from 33.3% (81/243) and 62.1% (151/243) to 79.8% (292/366) and 87.7% (242/276), respectively. But PM10 rose from 0.060 mg/m3 to 0.068 mg/m3, and the percentage of pipes meeting the national standard for PM10 increased from 74.2% (13/60) to 90.2% (46/51). The cleaning and disinfection of central air-conditioning ventilation systems could have a beneficial effect of air quality.

  12. Clean air, clear market. Making emissions trading work: The role of a computer-assisted auction

    International Nuclear Information System (INIS)

    Bartels, C.W.; Marron, D.B.; Lipsky, M.I.

    1993-01-01

    Creating a new commodity presents the chance to develop new markets in which to trade it. In many cases, existing markets can be adapted easily; in other cases it proves worthwhile to develop new forms that reflect special characteristics of the commodity and those who trade it. In the case of the sulfur dioxide (SO 2 ) emission allowances created by the Clean Air Act Amendments of 1990, a number of standard market forms already have been adopted. While these will prove useful for handling some transactions, a new Market Clearing Auction (MCA) offers buyers and sellers a centralized marketplace for trading SO 2 emission allowances. The MCA, which was developed by the brokerage firm Cantor Fitzgerald, is a computer-assisted open-quotes smartclose quotes auction designed to replicate the outcome of an efficient market in emission allowances, and accepts bids and offers for any possible combination of allowances. Orders can be submitted for streams of allowances. Orders can be submitted for streams of allowances covering more than one year. The auction then determines the combination of bids and offers that maximizes the gains from trades in the market, and establishes uniform market clearing prices for each allowance issue (1995, 1996, and so on). Once executed, trades are settled on a cash-forward basis; that is, allowances are delivered and payments are made at future dates

  13. Evidence of recovery of Juniperus virginiana trees from sulfur pollution after the Clean Air Act.

    Science.gov (United States)

    Thomas, Richard B; Spal, Scott E; Smith, Kenneth R; Nippert, Jesse B

    2013-09-17

    Using dendroisotopic techniques, we show the recovery of Juniperus virginiana L. (eastern red cedar) trees in the Central Appalachian Mountains from decades of acidic pollution. Acid deposition over much of the 20th century reduced stomatal conductance of leaves, thereby increasing intrinsic water-use efficiency of the Juniperus trees. These data indicate that the stomata of Juniperus may be more sensitive to acid deposition than to increasing atmospheric CO2. A breakpoint in the 100-y δ(13)C tree ring chronology occurred around 1980, as the legacy of sulfur dioxide emissions declined following the enactment of the Clean Air Act in 1970, indicating a gradual increase in stomatal conductance (despite rising levels of atmospheric CO2) and a concurrent increase in photosynthesis related to decreasing acid deposition and increasing atmospheric CO2. Tree ring δ(34)S shows a synchronous change in the sources of sulfur used at the whole-tree level that indicates a reduced anthropogenic influence. The increase in growth and the δ(13)C and δ(34)S trends in the tree ring chronology of these Juniperus trees provide evidence for a distinct physiological response to changes in atmospheric SO2 emissions since ∼1980 and signify the positive impacts of landmark environmental legislation to facilitate recovery of forest ecosystems from acid deposition.

  14. Give clean air the economic value it deserves

    International Nuclear Information System (INIS)

    Verhagen, H.

    2000-01-01

    India contributes more to the management of the atmosphere than a country like the Netherlands. This is not to the credit of the Indian government; rather, it is merely a consequence of poverty. Poor people use almost no fossil fuels and emit almost no CO2. Paying developing countries for this environmental service to the world community would create a financial incentive to continue to provide this service in the future, while at the same time generating additional funds to improve the living standards of the poorest people. The attractiveness of this approach depends on one important assumption: the conventional development path - economic growth implies emissions - must be replaced by a sustainable development path delinks economic growth from increasing emissions. Rich industrialised countries also have an interest in such decoupling. The compensation they pay the developing countries would fall proportionately to the reduction of their CO2 emissions. So an incentive is created on both sides to switch over to a low-carbon energy strategy. After the completion of this transition, every country can use as much energy as it wants, because energy consumption would then no longer cause CO2 emissions. This is the picture of the future to which the United Air Fund aspires

  15. Hanford Waste Vitrification Plant Clean Air Act permit application

    International Nuclear Information System (INIS)

    1990-04-01

    This document briefly describes the Hanford Site and provides a general overview of the Hanford Waste Vitrification Plant (HWVP). Other topics include sources of emissions, facility operating parameters, facility emissions, pollutant and radionuclide control technology and air quality. The HWVP will convert mixed wastes (high-activity radioactive and hazardous liquid wastes) to a solid vitrified form (borosilicate glass) for disposal. Mixed wastes pretreated in the Hanford Site B Plant will be pumped into double- shell tanks in the 200 East Area for interim storage. This pretreated mixed waste will be batch transferred from interim storage to the HWVP facility, where the waste will be concentrated by evaporation, treated with chemicals, and mixed with glass-forming materials. The mixture will then be continuously fed into an electrically heated glass melter. The molten glass will be poured into canisters that will be cooled, sealed, decontaminated, and stored until the vitrified product can be transferred to a geologic repository. 25 refs., 18 figs., 32 tabs

  16. Cleaning efficiency enhancement by ultrasounds for membranes used in dairy industries.

    Science.gov (United States)

    Luján-Facundo, M J; Mendoza-Roca, J A; Cuartas-Uribe, B; Álvarez-Blanco, S

    2016-11-01

    Membrane cleaning is a key point for the implementation of membrane technologies in the dairy industry for proteins concentration. In this study, four ultrafiltration (UF) membranes with different molecular weight cut-offs (MWCOs) (5, 15, 30 and 50kDa) and materials (polyethersulfone and ceramics) were fouled with three different whey model solutions: bovine serum albumin (BSA), BSA plus CaCl2 and whey protein concentrate solution (Renylat 45). The purpose of the study was to evaluate the effect of ultrasounds (US) on the membrane cleaning efficiency. The influence of ultrasonic frequency and the US application modes (submerging the membrane module inside the US bath or applying US to the cleaning solution) were also evaluated. The experiments were performed in a laboratory plant which included the US equipment and the possibility of using two membrane modules (flat sheet and tubular). The fouling solution that caused the highest fouling degree for all the membranes was Renylat 45. Results demonstrated that membrane cleaning with US was effective and this effectiveness increased at lower frequencies. Although no significant differences were observed between the two different US applications modes tested, slightly higher cleaning efficiencies values placing the membrane module at the bottom of the tank were achieved. Copyright © 2016 Elsevier B.V. All rights reserved.

  17. Clean/alternative fueled fleet programs - 1990 Amendments to the Clean Air Act, the Colorado Air Pollution Prevention and Control Act, and Denver City and County regulations

    International Nuclear Information System (INIS)

    Bowles, S.L.; Manderino, L.A.

    1993-01-01

    Despite substantial regulations for nearly two decades, attainment of this ambient standards for ozone and carbon monoxide (CO) remain difficult goals to achieve, Even with of ozone precursors and CO. The 1990 Amendments to the Clean Air Act (CAA90) prescribe further reductions of mobile source emissions. One such reduction strategy is using clean fuels, such as methanol, ethanol, or other alcohols (in blends of 85 percent or more alcohol with gasoline or other fuel), reformulated gasoline or diesel, natural gas, liquified petroleum gas, hydrogen, or electricity. There are regulatory measures involving special fuels which will be required in areas heavily polluted with ozone and CO. The state of Colorado recently passed the 1992 Air Pollution Prevention and Control Act which included provisions for the use of alternative fuels which will be implemented in 1994. In addition to adhering to the Colorado state regulations, the city and county of Denver also have regulations pertaining to the use of alternative fuels in fleets of 10 or more vehicles. Denver's program began in 1992. This paper will address the issue of fleet conversion and its impact on industry in Colorado, and Denver in particular

  18. The impact of cost recovery on electric utilities' Clean Air Act compliance strategies

    International Nuclear Information System (INIS)

    Bensinger, D.L.

    1993-01-01

    By 1995, over 200 electric power plant units in twenty one states must comply with Phase I of the acid rain requirements in Title IV of the 1990 Clean Air Act Amendments (CAAA). By the year 2000, an additional 2200 units must comply with the Title IV. Compliance costs are expected to necessitate significant electricity rate increases. In order to recover their compliance costs, utilities must file rate increase requests with state public utility commissions (PUC's), and undergo a rate proceeding involving public heatings. Because of the magnitude of cost and the complexity of compliance options, including interaction with Titles I and III of the CAAA, extensive PUC reviews of compliance strategies are likely. These reviews could become as adversarial as the nuclear prudence reviews of the 1980's. A lack of understanding of air pollution and the CAA by much of the general public and the flexibility of compliance options creates an environment conducive to adverse public reaction to the cost of complying with the Clean Air Act. Public attitudes toward pollution control technologies will be greatly affected by these hearings, and the early plant hearings will shape the utility rate making process under the Clean Air Act. Inadequate cost recovery due to constrained compliance strategies or adverse hearings could significantly inhibit industry willingness to invest in certain control technologies or advanced combustion technologies. There are already signs that Clean Air Act compliance will be the prudence issue of the 1990's for utilities, even where state statutes mandate particular compliance approaches. Specific actions should be undertaken now by the utility industry to improve the probability of sound cost recovery decisions, preserve compliance options, including multimedia strategies, and avoid the social- and cost-acceptance problems of nuclear power

  19. High efficiency novel window air conditioner

    International Nuclear Information System (INIS)

    Bansal, Pradeep

    2015-01-01

    Highlights: • Use of novel refrigerant mixture of R32/R125 (85/15% molar conc.) to reduce global warming and improve energy efficiency. • Use of novel features such as electronically commuted motor (ECM) fan motor, slinger and sub-merged sub-cooler. • Energy savings of up to 0.1 Quads per year in USA and much more in Asia/Middle East where WACs are used in large numbers. • Payback period of only 1.4 years of the novel efficient WAC. - Abstract: This paper presents the results of an experimental and analytical evaluation of measures to raise the efficiency of window air conditioners (WAC). In order to achieve a higher energy efficiency ratio (EER), the original capacity of a baseline R410A unit was reduced by replacing the original compressor with a lower capacity but higher EER compressor, while all heat exchangers and the chassis from the original unit were retained. Subsequent major modifications included – replacing the alternating current fan motor with a brushless high efficiency electronically commutated motor (ECM) motor, replacing the capillary tube with a needle valve to better control the refrigerant flow and refrigerant set points, and replacing R410A with a ‘drop-in’ lower global warming potential (GWP) binary mixture of R32/R125 (85/15% molar concentration). All these modifications resulted in significant enhancement in the EER of the baseline WAC. Further, an economic analysis of the new WAC revealed an encouraging payback period

  20. 77 FR 20625 - Air Pollution Control: Proposed Action on Clean Air Act Grants to the Idaho Department of...

    Science.gov (United States)

    2012-04-05

    ...The U.S. EPA has made a proposed determination that reduction in expenditures of non-Federal funds for the Idaho Department of Environmental Quality (IDEQ) in support of its continuing air program under Clean Air Act (CAA) Section 105 for the period of calendar year 2010 was not selective relative to the expenditures of all other executive branch agencies in the State for the same period. This determination, when final, will reset IDEQ's required recipient maintenance of effort level for 2010 and 2011, retain its federal award for the 2010 and 2011 grant years, and allow IDEQ to remain eligible for a Sec. 105 grant for 2012 and beyond.

  1. 78 FR 51184 - Air Pollution Control: Proposed Actions on Clean Air Act Section 105 Grant to the Lane Regional...

    Science.gov (United States)

    2013-08-20

    ...The EPA has made a proposed determination that a reduction in recurring expenditures of non-Federal funds for the Lane Regional Air Protection Agency (LRAPA) in Eugene, Oregon is a result of agency wide non-selective reductions in expenditures. This determination, when final, will permit the LRAPA to continue to receive grant funding under Section 105 of the Clean Air Act for the state fiscal year (SFY) 2014. This determination will also reset the LRAPA required maintenance of effort level for SFY 2012 and 2013 to reflect the non-selective reductions made to address reductions in revenue due to adverse economic conditions in Lane County, Oregon.

  2. Influence of wet chemical cleaning on quantum efficiency of GaN photocathode

    International Nuclear Information System (INIS)

    Wang Xiao-Hui; Gao Pin; Wang Hong-Gang; Li Biao; Chang Ben-Kang

    2013-01-01

    GaN samples 1–3 are cleaned by a 2:2:1 solution of sulfuric acid (98%) to hydrogen peroxide (30%) to de-ionized water; hydrochloric acid (37%); or a 4:1 solution of sulfuric acid (98%) to hydrogen peroxide (30%). The samples are activated by Cs/O after the same annealing process. X-ray photoelectron spectroscopy after the different ways of wet chemical cleaning shows: sample 1 has the largest proportion of Ga, N, and O among the three samples, while its C content is the lowest. After activation the quantum efficiency curves show sample 1 has the best photocathode performance. We think the wet chemical cleaning method is a process which will mainly remove C contamination. (condensed matter: electronic structure, electrical, magnetic, and optical properties)

  3. Technical development of nuclear air cleaning in the People's Republic of China

    International Nuclear Information System (INIS)

    Li Xue Qun; Liu Hui; Wang Tie Shen; Xin Song Niam; Guo Liang Tian.

    1985-01-01

    In the past 20 years, with the utilization of nuclear technology in China, air cleaning techniques were developed to prevent the environment from pollution caused by radioactive materials and to ensure the safety of occupational personnel. The technical developments involve many fields including the manufacture of filter media and adsorbents; the application of filters and iodine adsorbers and the testing of them; the improvement of instruments and methods for aerosol concentration measurement; the retention of radioactive noble gases; and others. As nuclear power stations are to be built in China, nuclear air cleaning will be advancing more rapidly. Many programs have been scheduled, such as producing other types of adsorbers, moisture separators, nuclear grade HEPA filters that have excellent performance to resist adverse circumstances, and in-place testing for units of ventilation systems in nuclear facilities. These programs are discussed

  4. The ageing and poisoning of charcoal used in nuclear plant air cleaning systems

    International Nuclear Information System (INIS)

    Broadbent, D.

    1986-01-01

    Ageing and Poisoning are terms which are used to describe the in-service deterioration or weathering of activated charcoals used to remove radioiodine from air cleaning systems. This paper describes an investigation aimed at identifying the relative importance of the two effects and at comparing the resistance to weathering of potassium iodide (KI) impregnated charcoal with triethylene diamine (TEDA) impregnated charcoal. Some preliminary results are given on the rates of oxidative ageing of charcoals as a function of temperature and relative humidity. The effect on charcoal performance of organic poisons has been examined by measuring the index of performance (k-factor) of charcoals preloaded with a range of organic solvents. Finally the combined effect of oxidative ageing and organic poisoning has been measured using realistic operating conditions of temperature and relative humidity. The in-service deterioration of charcoal in air cleaning systems can be accounted for by a combination of oxidative ageing and poisoning by airborne organic solvents. (author)

  5. Study of loading/air back-pulse cleaning cycles on the performance of ceramic membrane filters

    International Nuclear Information System (INIS)

    Waggoner, Charles; Alderman, Steven; Parsons, Michael; Hogoncamp, Kristina; Alderman, Steven

    2007-01-01

    Available in abstract form only. Full text of publication follows: The most commonly identified threats to conventional glass fiber HEPA filter performance are moisture and rapid blinding of filters by smoke. Regenerable filter media composed of ceramics or sintered metal can be utilized as pre-filters to protect the more vulnerable glass fiber HEPA filters in the event of upset conditions. Additionally, used in a pre-filtering application, the use of these regenerable filters can potentially extend the lifetime of conventional units. A series of tests have been conducted using CeraMem ceramic membrane filters in an effort to evaluate their performance after repeated loading and air back pulse cleaning. This was done in an effort to access filter performance after repeated loading/cleaning cycles. The filters were loaded using a solid potassium chloride aerosol challenge. The filters were evaluated for pressure drop and filtering efficiency changes from one cleaning cycle to the next. Additionally, the particle size distribution of the aerosol penetrating the filters was measured. (authors)

  6. XPS response in the corrosion products analysis for copper exposed at clean air environment

    International Nuclear Information System (INIS)

    Mariaca, L.; Morcillo, M.; Feliu Jr, S.; Gonzalez, J.A.

    1998-01-01

    In this work is presented the obtained response for superficial analysis technique by X-ray photoelectron spectroscopy (XPS or ESCA), to determine the corrosion products formed during the copper exposure at environment without pollutants (clean air) at 50, 70 and 90 % of relative humidity at 35 Centigrade. One of the copper corrosion products most knew is Cu 2 O. This oxide is formed instantly to be exposed the copper at air. However in function of the exposure time and the relative humidity at it is exposed, the Cu 2 O oxide is transformed at Cu O and Cu(OH) 2 (Author)

  7. CLEAN-ROADS project: air quality considerations after the application of a novel MDSS on winter road maintenance activities

    Science.gov (United States)

    Pretto, Ilaria; Malloci, Elisa; Tonidandel, Gabriele; Benedetti, Guido; Di Napoli, Claudia; Piazza, Andrea; Apolloni, Roberto; Cavaliere, Roberto

    2016-04-01

    With this poster we present the environmental benefit on air quality derived by the application of the CLEAN-ROADS pilot project. The CLEAN-ROADS project addresses the problem of the environmental pollution caused by de-icing salts during winter road maintenance activities in the Province of Trento (Italy). A demonstrative Maintenance Decision Support System (MDSS) has been developed in order to improve the intervention procedures of the road management service. Specifically it aims to optimize the efficiency of how available resources (e.g., salt consumption) are currently used while guaranteeing the current level of road safety. The CLEAN-ROADS project has been tested and validated on a test area located in a valley bottom (Adige Valley), where the highest optimization margins are to be expected. The project supports current road maintenance practices, which has proved to be reliable and accurate, with a new scalable and energy-efficient road monitoring system. This system is based on a network of road weather stations (road weather information system, RWIS) installed on the test route. It is capable to collect real-time data about the road conditions and to perform short-term and now-cast road weather forecasts, which actively integrate weather data and bulletins covering the target area [1]. This poster presents the results obtained from a three-year monitoring activity with the aim to (1) determine the impact of de-icing salts on air quality and (2) quantify the improvements obtained by the application of the CLEAN-ROADS project on air quality. The Ambient Air Quality and Cleaner Air for Europe Directive (2008/50/EC) states that contributions to exceedances of particulate matter PM10 limit values that are attributable to road winter salting may be subtracted when assessing compliance with air quality limit values, once provided that reasonable measures have been taken to lower concentrations [2]. As the de-icing salts used in road maintenance are mainly based

  8. Vertically Aligned Graphene Sheets Membrane for Highly Efficient Solar Thermal Generation of Clean Water.

    Science.gov (United States)

    Zhang, Panpan; Li, Jing; Lv, Lingxiao; Zhao, Yang; Qu, Liangti

    2017-05-23

    Efficient utilization of solar energy for clean water is an attractive, renewable, and environment friendly way to solve the long-standing water crisis. For this task, we prepared the long-range vertically aligned graphene sheets membrane (VA-GSM) as the highly efficient solar thermal converter for generation of clean water. The VA-GSM was prepared by the antifreeze-assisted freezing technique we developed, which possessed the run-through channels facilitating the water transport, high light absorption capacity for excellent photothermal transduction, and the extraordinary stability in rigorous conditions. As a result, VA-GSM has achieved average water evaporation rates of 1.62 and 6.25 kg m -2 h -1 under 1 and 4 sun illumination with a superb solar thermal conversion efficiency of up to 86.5% and 94.2%, respectively, better than that of most carbon materials reported previously, which can efficiently produce the clean water from seawater, common wastewater, and even concentrated acid and/or alkali solutions.

  9. Phase II Recommendations by the Air Quality Management Subcommittee to the Clean Air Act Advisory Committee

    Science.gov (United States)

    The primary charge of the AQM Subcommittee was to develop recommendations to improve the air quality management system and address the air quality challenges in this country expected over the next 10 to 20 years. This report addresses those challenges.

  10. Regulatory policy issues and the Clean Air Act: Issues and papers from the state implementation workshops

    Energy Technology Data Exchange (ETDEWEB)

    Rose, K. [ed.; Burns, R.E.

    1993-07-01

    The National Regulatory Research Institute (NRRI), with funding from the US Environmental Protection Agency (EPA) and the US Department of Energy (DOE), conducted four regional workshops` on state public utility commission implementation of the Clean Air Act Amendments of 1990 (CAAA). The workshops had four objectives: (1) to discuss key issues and concerns on CAAA implementation, (2) to encourage a discussion among states on issues of common interests, (3) to attempt to reach consensus, where possible, on key issues, and (4) to provide the workshop participants with information and materials to assist in developing state rules, orders, and procedures. From the federal perspective, a primary goal was to ensure that workshop participants return to their states with a comprehensive background and understanding of how state commission actions may affect implementation of the CAAA and to be able to provide guidance to their jurisdictional utilities. It was hoped that this would reduce some of the uncertainty utilities face and assist in the development of an efficient allowance market. This report is divided into two main sections. In Section II, eleven principal issues are identified and discussed. These issues were chosen because they were either the most frequently discussed or they were related to the questions asked in response to the speakers` presentations. This section does not cover all the issues relevant to state implementation nor all the issues discussed at the workshops; rather, Section II is intended to provide an overview of the,planning, ratemaking, and multistate issues. Part III is a series of workshop papers presented by some of the speakers. Individual papers have been cataloged separately.

  11. 75 FR 22400 - Clean Air Act Operating Permit Program; Petition To Object to Title V Permit for Wheelabrator...

    Science.gov (United States)

    2010-04-28

    ... ENVIROMENTAL PROTECTION AGENCY [FRL-9142-6] Clean Air Act Operating Permit Program; Petition To Object to Title V Permit for Wheelabrator Baltimore, L.P., Baltimore City, MD AGENCY: Environmental Protection Agency (EPA). ACTION: Notice of final action. SUMMARY: Pursuant to section 505(b)(2) of the Clean...

  12. Cleaning Products and Air Fresheners: Emissions and ResultingConcentrations of Glycol Ethers and Terpenoids

    Energy Technology Data Exchange (ETDEWEB)

    Singer, Brett C.; Destaillat, Hugo; Hodgson, Alfred T.; Nazaroff,William W.

    2005-08-01

    Experiments were conducted to quantify emissions and concentrations of glycol ethers and terpenoids from cleaning product and air freshener use in a 50-m{sup 3} room ventilated at {approx}0.5 h{sup -1}. Five cleaning products were applied full-strength (FS); three were additionally used in dilute solution. FS application of pine-oil cleaner (POC) yielded 1-h concentrations of 10-1300 {micro}g m{sup -3} for individual terpenoids, including {alpha}-terpinene (90-120), d-limonene (1000-1100), terpinolene (900-1300), and {alpha}-terpineol (260-700). One-hour concentrations of 2-butoxyethanol and/or dlimonene were 300-6000 {micro}g m{sup -3} after FS use of other products. During FS application including rinsing with sponge and wiping with towels, fractional emissions (mass volatilized/dispensed) of 2-butoxyethanol and d-limonene were 50-100% with towels retained, {approx}25-50% when towels were removed after cleaning. Lower fractions (2-11%) resulted from dilute use. Fractional emissions of terpenes from FS use of POC were {approx}35-70% with towels retained, 20-50% with towels removed. During floor cleaning with dilute solution of POC, 7-12% of dispensed terpenes were emitted. Terpene alcohols were emitted at lower fractions: 7-30% (FS, towels retained), 2-9% (FS, towels removed), and 2-5% (dilute). During air-freshener use, d-limonene, dihydromyrcenol, linalool, linalyl acetate, and {beta}-citronellol were emitted at 35-180 mg d{sup -1} over three days while air concentrations averaged 30-160 {micro}g m{sup -3}.

  13. Movable air solar collector and its efficiency

    International Nuclear Information System (INIS)

    Lauva, A.; Aboltinš, A.; Palabinskis, J.; Karpova Sadigova, N.

    2008-01-01

    Implementing the guidelines of the Latvian National Programme for Energy in the field of alternative energy, intensive research shall be carried on regarding the use of solar energy, as it can be successfully used not only for the purposes of water heating and production of electrical energy, but also for air warming. The amount of heat necessary for the drying of rough forage and grain drying by active aeration in June, July and August can be obtained using solar radiation. The Latvian Guidelines for the Energy Development 2006-2016 state that the solar radiance in Latvia is of quite low intensity. The total amount of solar energy is 1109 kWh m -2 per year. The period of usage of the solar thermal energy is beginning from the last decade of April, when the intensity of radiation is 120 kWh m -2 , until the first decade of September. Within this period (approximately 1800 hours), it is possible to use the solar thermal energy by placing solar collectors. The usage of solar collectors for in drying of agricultural production is topical from the viewpoint of decreasing the consumption of energy used for the drying, as electrical energy and fossil energy resources become more expensive and tend to run out. In the processes that concern drying of agricultural production, efficiently enough solar radiation energy can be used. Due to this reason researching continues and expands in the field of usage of solar energy for the processes of drying and heating. The efficiency factor of the existing solar collectors is not high, but they are of simple design and cheep for production and exploitation. By improving the design of the solar collectors and choosing modern materials that absorb the solar radiation energy, it is possible the decrease the efficiency factor of solar collectors and decrease the production costs. In the scientific laboratory of grain drying and storage of Latvia University of Agriculture, a pilot device movable folding solar collector pilot device

  14. Energy Efficient in-Sensor Data Cleaning for Mining Frequent Itemsets

    Directory of Open Access Journals (Sweden)

    Jacques M. BAHI

    2012-03-01

    Full Text Available Limited energy, storage, computational power represent the main constraint of sensor networks. Development of algorithms that take into consideration this extremely demanding and constrained environment of sensor networks became a major challenge. Communicating messages over a sensor network consume far more energy than processing it and mining sensors data should respect the characteristics of sensor networks in terms of energy and computation constraints, network dynamics, and faults. This lead us to think of a data cleaning pre processing phase to reduce the packet size transmitted and prepare the data for an efficient and scalable data mining. This paper introduces a tree-based bi-level periodic data cleaning approach implemented on both the source node and the aggregator levels. Our contribution in this paper is two folds. First we look on a periodic basis at each data measured and periodically clean it while taking into consideration the number of occurrences of the measures captured which we shall call weight. Then, a data cleaning is performed between groups of nodes on the level of the aggregator, which contains lists of measures along with their weights. The quality of the information should be preserved during the in-network transmission through the weight of each measure captured by the sensors. This weight will constitute the key optimization of the frequent pattern tree. The result set will constitute a perfect training set to mine without higher CPU consumption allowing us to send only the useful information to the sink. The experimental results show the effectiveness of this technique in terms of energy efficiency and quality of the information by focusing on a periodical data cleaning while taking into consideration the weight of the data captured.

  15. Efficiency of different protocols for enamel clean-up after bracket debonding: an in vitro study

    Directory of Open Access Journals (Sweden)

    Lara Carvalho Freitas Sigilião

    2015-10-01

    Full Text Available Objective: This study aimed to assess the efficiency of six protocols for cleaning-up tooth enamel after bracket debonding.Methods:A total of 60 premolars were divided into six groups, according to the tools used for clean-up: 12-blade bur at low speed (G12L, 12-blade bur at high speed (G12H, 30-blade bur at low speed (G30L, DU10CO ORTHO polisher (GDU, Renew System (GR and Diagloss polisher (GD. Mean roughness (Ra and mean roughness depth (Rz of enamel surface were analyzed with a profilometer. Paired t-test was used to assess Ra and Rz before and after enamel clean-up. ANOVA/Tukey tests were used for intergroup comparison. The duration of removal procedures was recorded. The association between time and variation in enamel roughness (∆Ra, ∆Rz were evaluated by Pearson's correlation test. Enamel topography was assessed by scanning electron microscopy (SEM.Results:In Groups G12L and G12H, original enamel roughness did not change significantly. In Groups G30L, GDU, GR and GD, a smoother surface (p < 0.05 was found after clean-up. In Groups G30L and GD, the protocols used were more time-consuming than those used in the other groups. Negative and moderate correlation was observed between time and (∆Ra, ∆Rz; Ra and (∆Ra, ∆Rz; Rz (r = - 0.445, r = - 0.475, p < 0.01.Conclusion:All enamel clean-up protocols were efficient because they did not result in increased surface roughness. The longer the time spent performing the protocol, the lower the surface roughness.

  16. Proceedings of the 21st DOE/NRC nuclear air cleaning conference; Volume 2, Sessions 9--16

    Energy Technology Data Exchange (ETDEWEB)

    First, M.W. [ed.] [Harvard Univ., Boston, MA (United States). Harvard Air Cleaning Lab.

    1991-02-01

    The 21st meeting of the Department of Energy/Nuclear Regulatory Commission (DOE/NRC) Nuclear Air Cleaning Conference was held in San Diego, CA on August 13--16, 1990. The proceedings have been published as a two volume set. Volume 2 contains sessions covering adsorbents, nuclear codes and standards, modelling, filters, safety, containment venting and a review of nuclear air cleaning programs around the world. Also included is the list of attendees and an index of authors and speakers. (MHB)

  17. Twenty-second DOE/NRC nuclear air cleaning and treatment conference

    International Nuclear Information System (INIS)

    Bellamy, R.R.; Moeller, D.W.; First, M.W.

    1992-01-01

    The Twenty-Second Department of Energy/Nuclear Regulatory Commission Nuclear Air Cleaning and Treatment Conference was held Aug. 24-27, 1992, in Denver, Colo. A total of 224 air-cleaning specialists attended the conference. The United States and 12 foreign countries were represented, and the specialists were affiliated with government agencies, educational institutions, and all aspects of the nuclear industry, including utilities, architect engineers, equipment suppliers, and consultants. Several major topics were discussed, similar to areas covered at previous conferences: chemical processing off-gas cleaning; particulate filler developments, including filter testing, performance, and response to physical stress,adsorber testing and performance, including laboratory and in-place testing; waste management; system operation; codes and standards; and advanced nuclear power plants. The conference continued to provide an effective forum for direct interchange of information of both a practical and theoretical nature. International participation and interest continues, as evidenced by over 40% of the papers being sponsored by foreign interests and almost 20% of the attendees being from outside the United States. The potential for new, safer nuclear plants of an advanced design was an optimistic note during the conference. Regulatory authorities are playing a major role in providing guidance in the development of safety goals and other technical criteria for these new installations

  18. The impact of chemical cleaning on separation efficiency and properties of reverse osmosis membrane

    KAUST Repository

    Baatiyyah, Hani

    2018-04-01

    One of most major concerns from both cost-effective and technical point of view in membrane process industry is membrane cleaning. The aim of the project was to investigate the variations in membrane surface properties and separation efficiency of reverse osmosis membrane. Compativtive analysis have to be performed on four RO membrane before and after exposing the virgin membrane into chemical cleaning to identify and analysis the impact of the chemical cleaning on the performance of RO membrane. Commerical chemical cleaning used in this project were caustic and acidic cleaning agent. The project’s aim is the investigation of simulation software’s precision for the four membranes performance projection at different conditions of the feed water. The assessment of the membranes performance was done in the Innovation Cluster at pilot plant that was industrial in size. The main commercial elements used were the thin-film composite membranes with a spiral-wound of 8-inch polyamide. Ultrafiltration (UF) and seawater RO membrane pretreatment process was done for the red sea sourced feed water. A pressure vessel dimensioned at 8-inch was operated in conjunction with an individual element at 8 -20 m3/hr feed flow rate, with an 8 to 12 % recovery and an average 35,000-42,000 mg/L of total dissolved solids (TDS) composition for the feed water. To achieve the project’s aim in assessing the membranes, three phase experimental stages were completed. The membranes performance was assessed in terms of their water flux, salt rejection, boron rejection, bicarbonate rejection and permeate quality. In addition, the membrane surfaces were characterized after exposing the fresh membranes with a chemical cleaning reagent. The experimental results showed an increase in both permeate flow and salt passage for all studied elements. The changes in the membranes performance were systematically explained based on the changes in the charge density and chemical structure of the membranes

  19. Effects of filter housing and ductwork configuration on air flow uniformity inside air cleaning filter housings

    International Nuclear Information System (INIS)

    Paul, J.D.

    1993-01-01

    Each new HEPA filter installation presents a different physical configuration based on the system requirements, the available space and designer preference. Each different configuration can result in variations of air flow uniformity inside the filter housing across the filter banks. This paper presents the results of air flow uniformity testing for six different filter housing/ductwork configurations and discusses if any of those variations in air flow uniformity is attributable to the difference in the physical arrangements for the six cases

  20. 76 FR 52275 - Approval and Promulgation of Air Quality Implementation Plans; Virginia; Revisions to Clean Air...

    Science.gov (United States)

    2011-08-22

    ... evaluation and voluntarily discloses such violations to the Commonwealth and takes prompt and appropriate... CFR Part 52 Environmental protection, Air pollution control, Incorporation by reference, Nitrogen...

  1. 76 FR 30600 - Approval and Promulgation of Air Quality Implementation Plans; Virginia; Revisions to Clean Air...

    Science.gov (United States)

    2011-05-26

    ... and takes prompt and appropriate measures to remedy the violations. Virginia's Voluntary Environmental... Environmental protection, Air pollution control, Nitrogen dioxide, Ozone, Particulate matter, Reporting and...

  2. An introduction to the design, commissioning and operation of nuclear air cleaning systems for Qinshan Nuclear Power Plant

    Energy Technology Data Exchange (ETDEWEB)

    Xinliang Chen; Jiangang Qu; Minqi Shi [Shanghai Nuclear Engineering Research and Design Institute (China)] [and others

    1995-02-01

    This paper introduces the design evolution, system schemes and design and construction of main nuclear air cleaning components such as HEPA filter, charcoal adsorber and concrete housing etc. for Qinshan 300MW PWR Nuclear Power Plant (QNPP), the first indigenously designed and constructed nuclear power plant in China. The field test results and in-service test results, since the air cleaning systems were put into operation 18 months ago, are presented and evaluated. These results demonstrate that the design and construction of the air cleaning systems and equipment manufacturing for QNPP are successful and the American codes and standards invoked in design, construction and testing of nuclear air cleaning systems for QNPP are applicable in China. The paper explains that the leakage rate of concrete air cleaning housings can also be assured if sealing measures are taken properly and embedded parts are designed carefully in the penetration areas of the housing and that the uniformity of the airflow distribution upstream the HEPA filters can be achieved generally no matter how inlet and outlet ducts of air cleaning unit are arranged.

  3. Design Principles for Covalent Organic Frameworks as Efficient Electrocatalysts in Clean Energy Conversion and Green Oxidizer Production.

    Science.gov (United States)

    Lin, Chun-Yu; Zhang, Lipeng; Zhao, Zhenghang; Xia, Zhenhai

    2017-05-01

    Covalent organic frameworks (COFs), an emerging class of framework materials linked by covalent bonds, hold potential for various applications such as efficient electrocatalysts, photovoltaics, and sensors. To rationally design COF-based electrocatalysts for oxygen reduction and evolution reactions in fuel cells and metal-air batteries, activity descriptors, derived from orbital energy and bonding structures, are identified with the first-principle calculations for the COFs, which correlate COF structures with their catalytic activities. The calculations also predict that alkaline-earth metal-porphyrin COFs could catalyze the direct production of H 2 O 2 , a green oxidizer and an energy carrier. These predictions are supported by experimental data, and the design principles derived from the descriptors provide an approach for rational design of new electrocatalysts for both clean energy conversion and green oxidizer production. © 2017 WILEY-VCH Verlag GmbH & Co. KGaA, Weinheim.

  4. Interaction between Titles 2 and 3 of the Clean Air Act as amended, 1990

    Energy Technology Data Exchange (ETDEWEB)

    Szpunar, C.B.

    1996-02-01

    This report examines Some issues that would I affect the refining industry if the requirements for hazardous air pollutants set out in Title III of the Clean Air Act Amendments were to impede the market entrance of oxygenated fuels, as me; required by Title II. It describes the mandate for reformulated gasoline; considers gasoline characteristics in light of component shifts in refining; examines the supply of, demand for, and cost of various feedstocks and blendstocks; and identifies the emissions and atmospheric impacts that might result from the production and use of reformulated gasoline. Attention is focused on methanol and MTBE, two potential blendstocks that are also hazardous air pollutants, and on maximum achievable control technology standards, which might be applied to the stationary sources that produce them.

  5. Interaction between Titles 2 and 3 of the Clean Air Act as amended, 1990

    International Nuclear Information System (INIS)

    Szpunar, C.B.

    1996-02-01

    This report examines Some issues that would I affect the refining industry if the requirements for hazardous air pollutants set out in Title III of the Clean Air Act Amendments were to impede the market entrance of oxygenated fuels, as me; required by Title II. It describes the mandate for reformulated gasoline; considers gasoline characteristics in light of component shifts in refining; examines the supply of, demand for, and cost of various feedstocks and blendstocks; and identifies the emissions and atmospheric impacts that might result from the production and use of reformulated gasoline. Attention is focused on methanol and MTBE, two potential blendstocks that are also hazardous air pollutants, and on maximum achievable control technology standards, which might be applied to the stationary sources that produce them

  6. DESIGNING AND EFFICIENCY EFFECT OF AUTOMATIC BALL-CLEANING SYSTEM FOR CONDENSER 180-KTsS-1 OF TURBINE Т-180/210-130-1 LMZ. Part 1

    Directory of Open Access Journals (Sweden)

    Yu. A. Zenovich-Leshkevich-Ol’pinskiy

    2015-01-01

    Full Text Available In order to reduce losses in the cooling source (condenser and to increase effectiveness of fuel-and-power resources utilization, the authors present a modern automatic ball-cleaning system for the pipes of condenser 180-KTsS-1 of turbine unit Т-180/210-130-1 LMZ of Gomel CHP-2. The article examines exploitation challenges of the steam turbine condensers and methods of clearing them from sedimentations. Depending on the sedimentation character and composition, and the quality of cooling water at the power plant, they apply various methods of the condenser tubes clearing: heat drying, vacuum dehydration, acid-washing, pipes-shooting with water and water-air pistols, ablution with high-pressure water jet etc. All the applied cleaning methods are the periodical means to fight the sedimentations and require the turbine halting or unloading, predetermine the equipment operating between clearings with constantly smearing cooling surfaces of the condensers, i.e. with reduced efficiency of equipment operation.The installation of the ball-cleaning system practically excludes defects of the chemical and mechanical cleaning methods, which leads to the condenser pipes life-in-service increase, the full-flow condensate quality improvement, reliability and efficient performance enhancement of the steam turbines equipment. The authors consider developed algorithms of data processing and designed system control of the condenser cleaning that allowed realizing its operation in automatic mode.

  7. Review of failures in nuclear air cleaning systems (1975--1978)

    International Nuclear Information System (INIS)

    Moeller, D.W.

    1979-01-01

    During the period from January 1, 1975 through June 30, 1978, over 9,000 Licensee Event Reports (LERs) pertaining to the operation of commercial light water nuclear power plants in the US were reported to the Nuclear Regulatory Commission. Of these reports, over 1,200 (approximately 13%) pertained to failures in air monitoring, ventilating and cleaning systems. For BWR installations, over half of the reported events related to failures in equipment for monitoring the performance of air cleaning systems as contrasted to failures in the systems themselves. In PWR installations, failures in monitoring equipment amounted to about 32% of the total. Reported problem areas in BWR installations included the primary containment and standby gas treatment and off-gas systems, as well as the High Pressure Coolant Injection and Reactor Core Isolation Systems. For PWR installations, reported problem areas included primary containment and associated spray systems and waste processing equipment. Although data on reported failures in power reactor installations can be interpreted in a variety of ways, one message is clear. There is a need for research on the development of more reliable equipment for sampling and monitoring air systems. Equipment that provides inaccurate data on the performance of such systems can lead to as many problems as inadequacies in the systems themselves

  8. Amine-based post-combustion CO2 capture in air-blown IGCC systems with cold and hot gas clean-up

    International Nuclear Information System (INIS)

    Giuffrida, A.; Bonalumi, D.; Lozza, G.

    2013-01-01

    Highlights: • Hot fuel gas clean-up is a very favorable technology for IGCC concepts. • IGCC net efficiency reduces to 41.5% when realizing post-combustion CO 2 capture. • Complex IGCC layouts are necessary if exhaust gas recirculation is realized. • IGCC performance does not significantly vary with exhaust gas recirculation. - Abstract: This paper focuses on the thermodynamic performance of air-blown IGCC systems with post-combustion CO 2 capture by chemical absorption. Two IGCC technologies are investigated in order to evaluate two different strategies of coal-derived gas clean-up. After outlining the layouts of two power plants, the first with conventional cold gas clean-up and the second with hot gas clean-up, attention is paid to the CO 2 capture station and to issues related to exhaust gas recirculation in combined cycles. The results highlight that significant improvements in IGCC performance are possible if hot coal-derived gas clean-up is realized before the syngas fuels the combustion turbine, so the energy cost of CO 2 removal in an amine-based post-combustion mode is less strong. In particular, IGCC net efficiency as high as 41.5% is calculated, showing an interesting potential if compared to the one of IGCC systems with pre-combustion CO 2 capture. Thermodynamic effects of exhaust gas recirculation are investigated as well, even though IGCC performance does not significantly vary against a more complicated plant layout

  9. Determination of the Clean Air Delivery Rate (CADR of Photocatalytic Oxidation (PCO Purifiers for Indoor Air Pollutants Using a Closed-Loop Reactor. Part I: Theoretical Considerations

    Directory of Open Access Journals (Sweden)

    Éric Dumont

    2017-03-01

    Full Text Available This study demonstrated that a laboratory-scale recirculation closed-loop reactor can be an efficient technique for the determination of the Clean Air Delivery Rate (CADR of PhotoCatalytic Oxidation (PCO air purification devices. The recirculation closed-loop reactor was modeled by associating equations related to two ideal reactors: one is a perfectly mixed reservoir and the other is a plug flow system corresponding to the PCO device itself. Based on the assumption that the ratio between the residence time in the PCO device and the residence time in the reservoir τP/τR tends to 0, the model highlights that a lab closed-loop reactor can be a suitable technique for the determination of the efficiency of PCO devices. Moreover, if the single-pass removal efficiency is lower than 5% of the treated flow rate, the decrease in the pollutant concentration over time can be characterized by a first-order decay model in which the time constant is proportional to the CADR. The limits of the model are examined and reported in terms of operating conditions (experiment duration, ratio of residence times, and flow rate ranges.

  10. The impact of the US Clean Air Act - seven years after enactment

    Energy Technology Data Exchange (ETDEWEB)

    Aloe, A.; Ailor, D.

    2000-07-01

    The United States Clean Air Act Amendments of 1990 (CAAA) have added operating expenses, renewed interest in coke battery repair techniques, played a role in new battery technology choices and spurred investigation into non-traditional coke making technologies. United States coke producers have demonstrated compliance with the new standards. The ultimate impact of the CAAA requirements will be known as aging coke batteries in the United States are shut down. At that point the demand for coke coupled with the CAAA requirements will determine if new batteries are built, and if so, what technology will be used. 7 refs., 4 figs., 2 tabs.

  11. Response of air cleaning system dampers and blowers to simulated tornado transients

    International Nuclear Information System (INIS)

    Gregory, W.; Idar, E.; Smith, P.; Hensel, E.; Smith, E.

    1985-01-01

    The effects of tornado-like pressure transients upon dampers and blowers in nuclear air cleaning systems were studied. For the dampers pressure drop as a function of flow rate was obtained and an empirical relationship developed. Transient response was examined for several types of dampers, as was structural integrity. Both centrifugal and axi-vane blowers were tested and transient characteristic curves were generated in outrunning and backflow situations. The transient characteristic curves do not necessarily match the quasi-steady characteristic curves

  12. Testing Open-Air Storage of Stumps to Provide Clean Biomass for Energy Production

    Directory of Open Access Journals (Sweden)

    Luigi Pari

    2017-10-01

    Full Text Available When orchards reach the end of the productive cycle, the stumps removal becomes a mandatory operation to allow new soil preparation and to establish new cultivations. The exploitation of the removed stump biomass seems a valuable option, especially in the growing energy market of the biofuels; however, the scarce quality of the material obtained after the extraction compromises its marketability, making this product a costly waste to be disposed. In this regard, the identification of affordable strategies for the extraction and the cleaning of the material will be crucial in order to provide to plantation owners the chance to sell the biomass and offset the extraction costs. Mechanical extraction and cleaning technologies have been already tested on forest stumps, but these systems work on the singular piece and would be inefficient in the conditions of an intensive orchard, where stumps are small and numerous. The objective of this study was to test the possibility to exploit a natural stumps cleaning system through open-air storage. The tested stumps were obtained from two different vineyards, extracted with an innovative stump puller specifically designed for continuous stump removal in intensively-planted orchards. The effects of weathering were evaluated to determine the fuel quality immediately after the extraction and after a storage period of six months with respect to moisture content, ash content, and heating value. Results indicated interesting storage performance, showing also different dynamics depending on the stumps utilized.

  13. The successful of finite element to invent particle cleaning system by air jet in hard disk drive

    Science.gov (United States)

    Jai-Ngam, Nualpun; Tangchaichit, Kaitfa

    2018-02-01

    Hard Disk Drive manufacturing has faced very challenging with the increasing demand of high capacity drives for Cloud-based storage. Particle adhesion has also become increasingly important in HDD to gain more reliability of storage capacity. The ability to clean on surfaces is more complicated in removing such particles without damaging the surface. This research is aim to improve the particle cleaning in HSA by using finite element to develop the air flow model then invent the prototype of air cleaning system to remove particle from surface. Surface cleaning by air pressure can be applied as alternative for the removal of solid particulate contaminants that is adhering on a solid surface. These technical and economic challenges have driven the process development from traditional way that chemical solvent cleaning. The focus of this study is to develop alternative way from scrub, ultrasonic, mega sonic on surface cleaning principles to serve as a foundation for the development of new processes to meet current state-of-the-art process requirements and minimize the waste from chemical cleaning for environment safety.

  14. Are there SO2 externality costs beyond the Clean Air Act Amendments of 1990?

    International Nuclear Information System (INIS)

    Sanghi, A.; Joseph, A.L.

    1992-01-01

    Inclusion of environmental externality costs in the selection of utility resources has become a reality in New York, Massachusetts, Nevada and California. Soon several other jurisdictions are likely to join these states in using environmental externality costs in decision-making. The consideration of environmental externalities are bound to profoundly affect utility decision-making in the future. So far attention has focused largely on air emission externalities of SO 2 , NO x and CO 2 . However, the recent Clean Air Act Amendments (CAAA) will reduce SO 2 emissions from utilities by about 50 percent. With such a large reduction in SO 2 loading, the question has been raised as to the need to further consider SO 2 externality costs in decision-making. This paper comments on this issue. By using generation and emission data from New York utilities, the paper shows that SO 2 emission externalities exist even after complying with requirements of the CAAA

  15. Self-cleaning threaded rod spinneret for high-efficiency needleless electrospinning

    Science.gov (United States)

    Zheng, Gaofeng; Jiang, Jiaxin; Wang, Xiang; Li, Wenwang; Zhong, Weizheng; Guo, Shumin

    2018-07-01

    High-efficiency production of nanofibers is the key to the application of electrospinning technology. This work focuses on multi-jet electrospinning, in which a threaded rod electrode is utilized as the needless spinneret to achieve high-efficiency production of nanofibers. A slipper block, which fits into and moves through the threaded rod, is designed to transfer polymer solution evenly to the surface of the rod spinneret. The relative motion between the slipper block and the threaded rod electrode promotes the instable fluctuation of the solution surface, thus the rotation of threaded rod electrode decreases the critical voltage for the initial multi-jet ejection and the diameter of nanofibers. The residual solution on the surface of threaded rod is cleaned up by the moving slipper block, showing a great self-cleaning ability, which ensures the stable multi-jet ejection and increases the productivity of nanofibers. Each thread of the threaded rod electrode serves as an independent spinneret, which enhances the electric field strength and constrains the position of the Taylor cone, resulting in high productivity of uniform nanofibers. The diameter of nanofibers decreases with the increase of threaded rod rotation speed, and the productivity increases with the solution flow rate. The rotation of electrode provides an excess force for the ejection of charged jets, which also contributes to the high-efficiency production of nanofibers. The maximum productivity of nanofibers from the threaded rod spinneret is 5-6 g/h, about 250-300 times as high as that from the single-needle spinneret. The self-cleaning threaded rod spinneret is an effective way to realize continuous multi-jet electrospinning, which promotes industrial applications of uniform nanofibrous membrane.

  16. The National Coordinated Research Programme for Air Quality. Another choice for clean air

    International Nuclear Information System (INIS)

    Van Giezen, M.; Havinga, A.; De Boer, H.

    2009-01-01

    On August 1st 2009 the National Coordinated Research Programme for Air quality (NSL in Dutch) entered into operation. This programme must help improve air quality such that it meets the European standards. At the same time the deadlock between environment and space is also solved. A special approach has been chosen for this purpose, which is based on a common interest of the State, provinces and local authorities. It was an intensive and interesting process. The annual monitoring will have to show whether or not the NSL will meet its objectives. [nl

  17. Radioisotope tracer technology for a hydraulic efficiency diagnosis of sludge digester after cleaning up

    International Nuclear Information System (INIS)

    Jung, Sung Hee; Kim Jong Bum; Choi, Byung Jong

    2004-03-01

    Radiotracer experiments were carried out on a cylindrical 2-stage anaerobic sludge digester in order to investigate the improvement of its efficiency by means of RTD (Residence Time Distribution) measurements before and after cleaning up the inside of the digester. The tracer was Sc-46 in an EDTA solution which forms such a stable complex compound to keep the isotope from being absorbed onto the surface of the pipelines or the wall. It was injected into the digester by pressurized nitrogen gas and its movement was monitored by NaI(Tl) scintillation detectors installed around the digester and recorded for a month by a 24-channel data acquisition system specially developed for radiotracer experiments by the Korea Tracer Group of KAERI. The experimental data was analyzed for the MRT (Mean Residence Time) and other parameters characterizing the flow behavior. After the cleaning of the digesters the variance has been decreased and the sludge dynamics was activated as a result of the increase of the effective volume from 20% to 80% after cleaning up in the secondary digester. Particularly the MRT of the secondary digester which has no mixing mechanism has been increased by 3 times

  18. Assessment of cleaning efficiency of the polydisperse gas flow in double-flow dedusting system

    Directory of Open Access Journals (Sweden)

    O.G. Butenko

    2016-05-01

    Full Text Available One of priority problems of nature protection activity at the industrial enterprises is upgrading the gas emissions cleaning of polydispersed dust. To solve the problem of catching of small fraction dust the double-flow dedusting system has been offered. Aim: The aim of the work is to determine the dependency type of the cleaning efficiency of polydisperse gas flow on gas separation factor double-flow dedusting system. Materials and methods: The analysis of influence of gas separation factor in the dividing device of double-flow dedusting system on its efficiency is carried out. By drawing up the mass balance of system on gas and on the mass of dust the general dependence for breakthrough of the main catcher, characterizing overall effectiveness of system, is received. Results: It is shown that value of breakthrough factor of the main catcher depends on dimensionless efficiency factors of the equipment. The received general dependence of breakthrough factor on separation factor allows to define the optimum value of separation factor for any combined dedusting system.

  19. Characterization of biogenic volatile organic compounds (BVOCs) in cleaning reagents and air fresheners in Hong Kong

    Science.gov (United States)

    Huang, Yu; Ho, Steven Sai Hang; Ho, Kin Fai; Lee, Shun Cheng; Gao, Yuan; Cheng, Yan; Chan, C. S.

    2011-11-01

    Biogenic volatile organic compounds (BVOCs) emitted from cleaning products and air fresheners indoors are prone to oxidation resulting in the formation of secondary pollutants that can pose health risks on residents. In this study, a solid phase microextraction (SPME) coupled with gas chromatography/mass spectrometry (SPME-GC/MS) method was applied for the determination of BVOCs compositions in three categories of cleaning products including floor cleaners (FC), kitchen cleaners (KC) and dishwashing detergents (DD), and also air fresheners (AF). The analysis results demonstrated that chemical composition and concentration of individual BVOC varied broadly with household products in the view of their different functions and scents as indicated on the labels. The concentration of total BVOCs for sample FC1 was the highest up to 4146.0 μg g -1, followed by FC2 of 264.6 μg g -1, FC4 of 249.3 μg g -1 and FC3 of 139.2 μg g -1. D-limonene was the most abundant detected BVOCs in KC samples with the chemical composition varying from 19.6 ± 1.0 to 1513.0 ± 37.1 μg g -1. For dishwashing detergents, only D-limonene was detected and quantified. The BVOCs compositions of air freshener samples are much more complicated. It was estimated that the consumption of floor cleaners contributed 51% of the total BVOCs amount indoors in Hong Kong, followed by air fresheners 42%, kitchen cleaners 5% and dishwashing detergents 2%.

  20. Solid oxide fuel cells for transportation: A clean, efficient alternative for propulsion

    International Nuclear Information System (INIS)

    Kumar, R.; Krumpelt, M.; Myles, K.M.

    1993-01-01

    Fuel cells show great promise for providing clean and efficient transportation power. Of the fuel cell propulsion systems under investigation, the solid oxide fuel cell (SOFC) is particularly attractive for heavy duty transportation applications that have a relatively long duty cycle, such as locomotives, trucks, and barges. Advantages of the SOFC include a simple, compact system configuration; inherent fuel flexibility for hydrocarbon and alternative fuels; and minimal water management. The specific advantages of the SOFC for powering a railroad locomotive are examined. Feasibility, practicality, and safety concerns regarding SOFCs in transportation applications are discussed, as am the major R ampersand D issues

  1. Efficiency of cleaning and disinfection of surfaces: correlation between assessment methods

    OpenAIRE

    Frota, Oleci Pereira; Ferreira, Adriano Menis; Guerra, Odanir Garcia; Rigotti, Marcelo Alessandro; Andrade, Denise de; Borges, Najla Moreira Amaral; Almeida, Margarete Teresa Gottardo de

    2017-01-01

    ABSTRACT Objective: to assess the correlation among the ATP-bioluminescence assay, visual inspection and microbiological culture in monitoring the efficiency of cleaning and disinfection (C&D) of high-touch clinical surfaces (HTCS) in a walk-in emergency care unit. Method: a prospective and comparative study was carried out from March to June 2015, in which five HTCS were sampled before and after C&D by means of the three methods. The HTCS were considered dirty when dust, waste, humidity an...

  2. Modern efficient methods of steel vertical oil tanks clean-up

    Directory of Open Access Journals (Sweden)

    Nekrasov Vladimir

    2016-01-01

    Full Text Available The legislative base of the Russian Federation operating in the field of operation of tanks and tank parks is considered, and consecutive stages of technological process of cleaning of vertical steel tanks from oil ground deposits are presented. In work shortcomings of existing most widespread electromechanical mixers are described when using a hydraulic method of removal and prevention of formation of ground deposits in tanks with oil and oil products. For the purpose of increase of efficiency, reliability and decrease in power consumption of washout of oil ground deposits in tanks the new design of system of funneled washout and prevention of formation of deposits is offered.

  3. Basic environmental principles for the promotion of clean and efficient energy

    International Nuclear Information System (INIS)

    Hanmer, R.; Connor-Lajambe, H.

    1994-01-01

    The purpose of this paper is to reiterate what might be considered basic principles for promoting clean and efficient energy. These principles have very important implications for the design of energy supply and transportation facilities, but they go far beyond that to unify such design with the design, use and maintenance of many other types of facilities and goods. These principles also affect the way we consider energy security in the context of sustainable development. In annex, this paper presents the recommendation of the Council, with a list of environmentally favourable energy options. (TEC). 2 refs., Annex

  4. EER, COP, and the Second Law Efficiency for Air Conditioners

    Science.gov (United States)

    Leff, Harvey S.; Teeters, William D.

    1978-01-01

    Describes the relationship existing between coefficient of performance (COP) and energy efficiency ratio (EER) in air conditioning units and introduces new efficiency parameters measured relative to the energy extracted from the primary energy source. (SL)

  5. Postulated accident conditions for air cleaning systems and radiological dose assessments for containment options

    International Nuclear Information System (INIS)

    Hilliard, R.K.; Postma, A.K.

    1975-01-01

    Ambient conditions and performance requirements for emergency air cleaning systems applicable to commercial LMFBR plants were studied. The focus of this study centered on aerosol removal under hypothetical core disruptive accident conditions. Effort completed includes a review of air cleaning systems related to LMFBR plants, selection of three reference containment system designs, postulation of the EACS design basis accident (EACS-DBA), analysis of thermal conditions resulting from the DBA, analysis of aerosol transport behavior following the DBA, and an estimate of bone dose at the site boundary for each of the reference plant designs. Reference plant concepts were a single containment system (e.g., FFTF), a double containment system (e.g., CRBRP with closed head compartment), and a containment-confinement design in which an inerted, sealed primary volume was located within a ventilated building whose exhaust was filtered. The reference design basis accident selected here involved release to the inner containment system of 1 percent of non-volatile solids and plutonium, 25 percent of core halogens, 25 percent of core volatile solids, 100 percent of core noble gases, 68 lbs of sodium vapor and 5000 lbs of liquid sodium. 13 references. (U.S.)

  6. Association between clean indoor air laws and voluntary smokefree rules in homes and cars.

    Science.gov (United States)

    Cheng, Kai-Wen; Okechukwu, Cassandra A; McMillen, Robert; Glantz, Stanton A

    2015-03-01

    This study examines the influence that smokefree workplaces, restaurants and bars have on the adoption of smokefree rules in homes and cars, and whether there is an association with adopting smokefree rules in homes and cars. Bivariate probit models were used to jointly estimate the likelihood of living in a smokefree home and having a smokefree car as a function of law coverage and other variables. Household data were obtained from the nationally representative Social Climate Survey of Tobacco Control 2001, 2002 and 2004-2009; clean indoor air law data were from the American Nonsmokers' Rights Foundation Tobacco Control Laws Database. 'Full coverage' and 'partial coverage' smokefree legislation is associated with an increased likelihood of having voluntary home and car smokefree rules compared with 'no coverage'. The association between 'full coverage' and smokefree rule in homes and cars is 5% and 4%, respectively, and the association between 'partial coverage' and smokefree rules in homes and cars is 3% and 4%, respectively. There is a positive association between the adoption of smokefree rules in homes and cars. Clean indoor air laws provide the additional benefit of encouraging voluntary adoption of smokefree rules in homes and cars. Published by the BMJ Publishing Group Limited. For permission to use (where not already granted under a licence) please go to http://group.bmj.com/group/rights-licensing/permissions.

  7. 76 FR 54462 - Notification of a Public Teleconference; Clean Air Scientific Advisory Committee; Air Monitoring...

    Science.gov (United States)

    2011-09-01

    ... found at the EPA CASAC Web site at http://www.epa.gov/casac . Any inquiry regarding EPA's draft Near.... State and local air agencies are required to consider traffic volumes, fleet mix, roadway design, traffic congestion patterns, local terrain or topography, meteorology, population exposure and other...

  8. Air quality improvements and health benefits from China’s clean air action since 2013

    Science.gov (United States)

    Zheng, Yixuan; Xue, Tao; Zhang, Qiang; Geng, Guannan; Tong, Dan; Li, Xin; He, Kebin

    2017-11-01

    Aggressive emission control measures were taken by the Chinese government after the promulgation of the ‘Air Pollution Prevention and Control Action Plan’ in 2013. Here we evaluated the air quality and health benefits associated with this stringent policy during 2013-2015 by using surface PM2.5 concentrations estimated from a three-stage data fusion model and cause-specific integrated exposure-response functions. The population-weighted annual mean PM2.5 concentrations decreased by 21.5% over China during 2013-2015, reducing from 60.5 in 2013 to 47.5 μg m-3 in 2015. Subsequently, the national PM2.5-attributable mortality decreased from 1.22 million (95% CI: 1.05, 1.37) in 2013 to 1.10 million (95% CI: 0.95, 1.25) in 2015, which is a 9.1% reduction. The limited health benefits compared to air quality improvements are mainly due to the supralinear responses of mortality to PM2.5 over the high concentration end of the concentration-response functions. Our study affirms the effectiveness of China’s recent air quality policy; however, due to the nonlinear responses of mortality to PM2.5 variations, current policies should remain in place and more stringent measures should be implemented to protect public health.

  9. Section 112 hazardous air pollutants Clean Air Act Amendments of 1990; potential impact of fossil/NUC

    International Nuclear Information System (INIS)

    Cronmiller, R.E.

    1990-01-01

    Control of hazardous air pollutants under the Clean Air Act (CAA) goes back several decades. Section 112 of the 1970 CAA as amended in 1977 served as the national statutory basis for controlling hazardous air pollutants until the most recent 1990 Amendments. Following severe criticism of the effectiveness of the Act to address hazardous air pollutant issues and a pile of seemingly never ending lawsuits challenging the regulatory process, the U.S. Congress has substantially rewritten Section 112 in the 1990 CAA Amendments. Many provisions heretofore requiring findings or regulatory decisions by the Environmental Protection Agency (EPA) Administrator are now automatic in the sense that the decisions have already been made by the US Congress legislatively. Thus, the new Section 112 has eliminated many of the existing regulatory obstacles, or safeguards; this will likely result in sweeping new regulatory programs mandating extensive controls on many industrial activities. A much needed study program to address fossil fuel fired steam electric generating units' hazardous air emissions and to identify control alternatives to regulate these emissions, if regulation is required, was incorporated into new Section 112. Because of this study, the regulatory fate of these units under the new Section 112 remains highly uncertain. An extensive regulatory program addressing hazardous air pollutants of these utility units under Section 112 would dwarf electric utility costs associated with the new acid rain control program. First, this paper identifies major provisions of the old law and the resulting regulatory status for both coal and nuclear power facilities before addressing the new Section 112 under the 1990 CAA Amendments and potential implications for electric utilities specifically

  10. Evaluation of the combined betatron and momentum cleaning in point 3 in terms of cleaning efficiency and energy deposition for the LHC Collimation upgrade

    CERN Document Server

    Lari, L; Boccone, V; Brugger, M; Cerutti, F; Ferrari, A; Rossi, A; Versaci, R; Vlachoudis, V; Wollmann, D; Mereghetti, A; Faus-Golfe, A

    2011-01-01

    The Phase I LHC Collimation System Upgrade could include moving part of the Betatron Cleaning from LHC Point 7 to Point 3 to improve both operation flexibility and intensity reach. In addition, the partial relocation of beam losses from the current Betatron cleaning region at Point 7 will mitigate the risks of Single Event Upsets to equipment installed in adjacent and partly not sufficient shielded areas. The combined Betatron and Momentum Cleaning at Point 3 implies that new collimators have to be added as well as to implement a new collimator aperture layout. This paper shows the whole LHC Collimator Efficiency variation with the new layout at different beam energies. As part of the evaluation, energy deposition distribution in the IR3 region give indications about the effect of this new implementations not only on the collimators themselves but also on the other beam line elements as well as in the IR3 surrounding areas.

  11. Ethanol-fueled low temperature combustion: A pathway to clean and efficient diesel engine cycles

    International Nuclear Information System (INIS)

    Asad, Usman; Kumar, Raj; Zheng, Ming; Tjong, Jimi

    2015-01-01

    Highlights: • Concept of ethanol–diesel fueled Premixed Pilot Assisted Combustion (PPAC). • Ultra-low NOx and soot with diesel-like thermal efficiency across the load range. • Close to TDC pilot injection timing for direct combustion phasing control. • Minimum pilot quantity (15% of total energy input) for clean, stable operation. • Defined heat release profile distribution (HRPD) to optimize pilot-ethanol ratio. - Abstract: Low temperature combustion (LTC) in diesel engines offers the benefits of ultra-low NOx and smoke emissions but suffers from lowered energy efficiency due to the high reactivity and low volatility of diesel fuel. Ethanol from renewable biomass provides a viable alternate to the petroleum based transportation fuels. The high resistance to auto-ignition (low reactivity) and its high volatility make ethanol a suitable fuel for low temperature combustion (LTC) in compression-ignition engines. In this work, a Premixed Pilot Assisted Combustion (PPAC) strategy comprising of the port fuel injection of ethanol, ignited with a single diesel pilot injection near the top dead centre has been investigated on a single-cylinder high compression ratio diesel engine. The impact of the diesel pilot injection timing, ethanol to diesel quantity ratio and exhaust gas recirculation on the emissions and efficiency are studied at 10 bar IMEP. With the lessons learnt, successful ethanol–diesel PPAC has been demonstrated up to a load of 18 bar IMEP with ultra-low NOx and soot emissions across the full load range. The main challenge of PPAC is the reduced combustion efficiency especially at low loads; therefore, the authors have presented a combustion control strategy to allow high efficiency, clean combustion across the load range. This work entails to provide a detailed framework for the ethanol-fueled PPAC to be successfully implemented.

  12. Notification: Background Investigation Services New Assignment Notification: EPA’s Efforts to Incorporate Environmental Justice Into Clean Air Act Inspections for Air Toxics

    Science.gov (United States)

    The purpose of this memorandum is to notify you that the EPA OIG plans to begin the preliminary research phase of an evaluation of the U.S. EPA's efforts to incorporate environmental justice into Clean Air Act inspections for air toxics.

  13. Methods for air cleaning and protection of building occupants from airborne pathogens

    DEFF Research Database (Denmark)

    Bolashikov, Zhecho Dimitrov; Melikov, Arsen Krikor

    2009-01-01

    germicidal irradiation (UVGI), photocatalytic oxidation (PCO), plasmacluster ions and other technologies for air disinfection and purification from pathogens are analyzed with respect to currently used air distribution principles. The importance of indoor air characteristics, such as temperature, relative...... of transmission, i.e. the generation of pathogen laden droplets originating in the respiratory tract of an infected individual, the survivability of the pathogens, their dispersal indoors and their transfer to a healthy person are reviewed. The advantages and the drawbacks of air dilution, filtration, ultraviolet...... humidity and velocity for the efficiency of each method is analyzed, taking into consideration the nature of the pathogens themselves. The applicability of the methods to the different types of total volume air distribution used at present indoors, i.e. mixing, displacement and underfloor ventilation...

  14. Determinants of efficiency in the provision of municipal street-cleaning and refuse collection services.

    Science.gov (United States)

    Benito-López, Bernardino; Moreno-Enguix, María del Rocio; Solana-Ibañez, José

    2011-06-01

    Effective waste management systems can make critical contributions to public health, environmental sustainability and economic development. The challenge affects every person and institution in society, and measures cannot be undertaken without data collection and a quantitative analysis approach. In this paper, the two-stage double bootstrap procedure of Simar and Wilson (2007) is used to estimate the efficiency determinants of Spanish local entities in the provision of public street-cleaning and refuse collection services. The purpose is to identify factors that influence efficiency. The final sample comprised 1072 municipalities. In the first stage, robust efficiency estimates are obtained with Data Envelopment Analysis (DEA). We apply the second stage, based on a truncated-regression, to estimate the effect of a group of environmental factors on DEA estimates. The results show the existence of a significant relation between efficiency and all the variables analysed (per capita income, urban population density, the comparative index of the importance of tourism and that of the whole economic activity). We have also considered the influence of a dummy categorical variable - the political sign of the governing party - on the efficient provision of the services under study. The results from the methodology proposed show that municipalities governed by progressive parties are more efficient. Copyright © 2011 Elsevier Ltd. All rights reserved.

  15. Determinants of efficiency in the provision of municipal street-cleaning and refuse collection services

    International Nuclear Information System (INIS)

    Benito-Lopez, Bernardino; Rocio Moreno-Enguix, Maria del; Solana-Ibanez, Jose

    2011-01-01

    Effective waste management systems can make critical contributions to public health, environmental sustainability and economic development. The challenge affects every person and institution in society, and measures cannot be undertaken without data collection and a quantitative analysis approach. In this paper, the two-stage double bootstrap procedure of is used to estimate the efficiency determinants of Spanish local entities in the provision of public street-cleaning and refuse collection services. The purpose is to identify factors that influence efficiency. The final sample comprised 1072 municipalities. In the first stage, robust efficiency estimates are obtained with Data Envelopment Analysis (DEA). We apply the second stage, based on a truncated-regression, to estimate the effect of a group of environmental factors on DEA estimates. The results show the existence of a significant relation between efficiency and all the variables analysed (per capita income, urban population density, the comparative index of the importance of tourism and that of the whole economic activity). We have also considered the influence of a dummy categorical variable - the political sign of the governing party - on the efficient provision of the services under study. The results from the methodology proposed show that municipalities governed by progressive parties are more efficient.

  16. Evaluating the Impact of Air Pollution on Human Health in China: the Price of Clean Air

    Science.gov (United States)

    Wang, X.; Mauzerall, D. L.; Hu, Y.; Russell, A. G.; Woo, J.; Streets, D. G.

    2003-12-01

    Population growth, rapid urbanization and economic development are contributing to increased energy consumption in China. One of the unintended consequences is poor air quality due to a lack of environmental controls. The coal dependent energy structure in China only worsens the situation. Quantification of the environmental costs resulting from air pollution is needed in order to provide a mechanism for making strategic energy policy that accounts for the life-cycle cost of energy use. However, few such studies have been conducted for China that examine the entire energy system. Here we examine the extent to which public health has been compromised due to elevated air pollution and how China could incorporate environmental costs into future energy and environmental policies. Taking the Shandong region in eastern China as a case study, we develop a high-resolution regional inventory for anthropogenic emissions of NOx, CO, PM2.5, PM10, VOCs, NH3 and SO2. SMOKE (Sparse Matrix Operator Kernel Emissions Modeling System) is used to process spatial and temporal distributions and chemical speciation of the regional emissions, MM5 (the Fifth-Generation NCAR/Penn State Meso-scale Model, Version 3) is used to generate meteorology and Models3/CMAQ (Community Multi-scale Air Quality Modeling System) is used to simulate ambient concentrations of particulates and other gaseous species in this region. We then estimate the mortality and morbidity in this region resulting from exposure to these air pollutants. We also estimate the monetary values associated with the resulting mortality and morbidity and quantify the contributions from various economic sectors (i.e. power generation, transportation, industry, residential and others). Finally, we examine the potential health benefits that adoption of best available or advanced energy (coal-based, in particular) and environmental technologies in different sectors could bring about. The results of these analyses are intended to provide

  17. Hawaii Clean Energy Initiative Existing Building Energy Efficiency Analysis: November 17, 2009 - June 30, 2010

    Energy Technology Data Exchange (ETDEWEB)

    Finch, P.; Potes, A.

    2010-06-01

    In June 2009, the State of Hawaii enacted an Energy Efficiency Portfolio Standard (EEPS) with a target of 4,300 gigawatt hours (GWh) by 2030 (Hawaii 2009). Upon setting this goal, the Hawaii Clean Energy Initiative, Booz Allen Hamilton (BAH), and the National Renewable Energy Laboratory (NREL), working with select local stakeholders, partnered to execute the first key step toward attaining the EEPS goal: the creation of a high-resolution roadmap outlining key areas of potential electricity savings. This roadmap was divided into two core elements: savings from new construction and savings from existing buildings. BAH focused primarily on the existing building analysis, while NREL focused on new construction forecasting. This report presents the results of the Booz Allen Hamilton study on the existing building stock of Hawaii, along with conclusions on the key drivers of potential energy efficiency savings and on the steps necessary to attain them.

  18. Development of a software and hardware system for monitoring the air cleaning process using a cyclone-separator

    Science.gov (United States)

    Nicolaeva, B. K.; Borisov, A. P.; Zlochevskiy, V. L.

    2017-08-01

    The article is devoted to the development of a hardware-software complex for monitoring and controlling the process of air purification by means of a cyclone-separator. The hardware of this complex is the Arduino platform, to which are connected pressure sensors, air velocities, dustmeters, which allow monitoring of the main parameters of the cyclone-separator. Also, a frequency converter was developed to regulate the rotation speed of an asynchronous motor necessary to correct the flow rate, the control signals of which come with Arduino. The program part of the complex is written in the form of a web application in the programming language JavaScript and inserts into CSS and HTML for the user interface. This program allows you to receive data from sensors, build dependencies in real time and control the speed of rotation of an asynchronous electric drive. The conducted experiment shows that the cleaning efficiency is 95-99.9%, while the airflow at the cyclone inlet is 16-18 m/s, and at the exit 50-70 m/s.

  19. Ontario's Clean Air Action Plan : protecting environmental and human health in Ontario

    International Nuclear Information System (INIS)

    2004-01-01

    Ontario's Clean Air Action Plan was launched in June 2000 in an effort to improve air quality and comply with the Canada-Wide Standards for Particulate Matter and Ozone. This paper describes Ontario's approach to reducing smog. Smog-related air pollution is linked to health problems such as premature death, respiratory and heart problems. Smog also contributes to environmental problems such as damage to forests, agricultural crops and natural vegetation. The two main ingredients of smog are ground level ozone and particulate matter. In order to reduce the incidence of smog, the following four key smog-causing pollutants must be reduced: nitrogen oxides, volatile organic compounds, sulphur dioxide and particular matter. This paper includes the 2001 estimates for Ontario's emissions inventory along with Ontario's smog reduction targets. It was noted that approximately half of all smog in Ontario comes from sources in the midwestern United States. The province of Ontario is committed to replacing coal-fired power plants with cleaner sources of energy. It is also considering emission caps for key industrial sectors. The key players in reducing smog include municipalities, industry, individuals, the federal government and programs that reduce emissions in the United States. 3 figs., 8 tabs., 1 appendix

  20. Competing initiatives: a new tobacco industry strategy to oppose statewide clean indoor air ballot measures.

    Science.gov (United States)

    Tung, Gregory J; Hendlin, Yogi H; Glantz, Stanton A

    2009-03-01

    To describe how the tobacco and gaming industries opposed clean indoor air voter initiatives in 2006, we analyzed media records and government and other publicly available documents and conducted interviews with knowledgeable individuals. In an attempt to avoid strict "smoke free" regulations pursued by health groups via voter initiatives in Arizona, Ohio, and Nevada, in 2006, the tobacco and gaming industries sponsored competing voter initiatives for alternative laws. Health groups succeeded in defeating the pro-tobacco competing initiatives because they were able to dispel confusion and create a head-to-head competition by associating each campaign with its respective backer and instructing voters to vote "no" on the pro-tobacco initiative in addition to voting "yes" on the health group initiative.

  1. Summary and overview of the allowance program in the Clean Air Act Amendments of 1990

    International Nuclear Information System (INIS)

    Anon.

    1992-01-01

    Title IV of the Clean Air Act Amendments of 1990 (CAAA) created a new regulatory instrument, an emission allowance, that electric power producers will be required to possess and expend to emit sulfur dioxide into the atmosphere. The emission allowance system will be integrated into an already complex system of state and federal electric utility regulation. The way state public utility commissions and the Federal Energy Regulatory Commission respond to utility compliance actions will greatly affect the decisions that electric utilities under their jurisdiction make to comply with the CAAA and the cost of compliance to ratepayers. This chapter summarizes the CAAA, presenting dates for the implementation of the allowance system rule, and discusses conservation and renewable energy bonus allowances, EPA allowance sales and auctions, allowance pooling, exempt power facilities, election by additional resources, nitrogen oxides control, compliance planning third-party ownership, allowance property rights, and an example of utility compliance options with allowances. 11 refs., 6 tabs

  2. Preliminary assessment of future refining impacts of the Clean Air Act Amendments of 1990

    International Nuclear Information System (INIS)

    Hadder, G.R.

    1991-09-01

    A preliminary assessment of the future refining impacts of the Clean Air Act Amendments of 1990 has been performed with the Navy Mobility Fuels Forecasting Systems. The assessment suggests that gasoline reformulation costs in domestic coastal and near-coastal refining regions in the year 2000 could be 3.5 to 5.6 cents per gallon (in terms of 1989 currency). For heating value equivalent to one gallon of conventional gasoline, the regional total added costs (including reformulation costs) for reformulated gasoline could be 5.9 to 8.0 cents. In blending reformulated gasolines, the reduction of butane for lower Reid vapor pressure and the reduction of reformate for lower aromatics are generally compensated by increased percentages of alkylate and/or straight run naphthas. Relatively larger refinery process capacity additions are required for butane isomerization, alkylation, aromatics recovery, and distillate hydrotreating. 21 refs., 3 figs., 18 tabs

  3. Extended-life nuclear air cleaning filters via dynamic exclusion prefilters

    Energy Technology Data Exchange (ETDEWEB)

    Wright, S.R.; Crouch, H.S.; Bond, J.H. [Micro Composite Materials Corp., Durham, NC (United States)

    1997-08-01

    The primary objective of this investigation was to ascertain if a dynamic, self-cleaning particulate exclusion precleaner, designed for relatively large dust removal (2 to 100+ {mu}m diameter particles) from helicopter turbine inlets, could be extended to submicron filtration. The improved device could be used as a prefilter for HEPA filtration systems, significantly increasing service life. In nuclear air cleaning, its use would reduce the amount of nuclear particulate matter that would otherwise be entrapped in the HEPA filter cartridge/panel, causing fouling and increased back pressure, as well as requiring subsequent disposal of the contaminated media at considerable expense. A unique (patent-pending) mechanical separation device has recently been developed to extract particulate matter from fluid process streams based on a proprietary concept called Boundary Layer Momentum Transfer (BLMT). The device creates multiple boundary layers that actively exclude particles from entering the perimeter of the device, while allowing air to traverse the boundaries relatively unimpeded. A modified two-dimensional (2-D) computerized flow simulation model was used to assist in the prototype design. Empirical results are presented from particle breakthrough and AP experiments obtained from a reduced-scale prototype filter. Particles larger than 0.23 {mu}m were actively excluded by the prototype, but at a higher pressure drop than anticipated. Experimental data collected indicates that the filter housing and the inlet flow configuration may contribute significantly to improvements in device particle separation capabilities. Furthermore, preliminary experiments have shown that other downstream pressure drop considerations (besides those just across the spinning filtration disks) must be included to accurately portray the AP across the device. Further detailed quantitative investigations on a larger scale (1,000 CFM) prototype are warranted. 3 refs., 5 figs., 2 tabs.

  4. Efficiency of cleaning and disinfection of surfaces: correlation between assessment methods

    Directory of Open Access Journals (Sweden)

    Oleci Pereira Frota

    Full Text Available ABSTRACT Objective: to assess the correlation among the ATP-bioluminescence assay, visual inspection and microbiological culture in monitoring the efficiency of cleaning and disinfection (C&D of high-touch clinical surfaces (HTCS in a walk-in emergency care unit. Method: a prospective and comparative study was carried out from March to June 2015, in which five HTCS were sampled before and after C&D by means of the three methods. The HTCS were considered dirty when dust, waste, humidity and stains were detected in visual inspection; when ≥2.5 colony forming units per cm2 were found in culture; when ≥5 relative light units per cm2 were found at the ATP-bioluminescence assay. Results: 720 analyses were performed, 240 per method. The overall rates of clean surfaces per visual inspection, culture and ATP-bioluminescence assay were 8.3%, 20.8% and 44.2% before C&D, and 92.5%, 50% and 84.2% after C&D, respectively (p<0.001. There were only occasional statistically significant relationships between methods. Conclusion: the methods did not present a good correlation, neither quantitative nor qualitatively.

  5. New Source Review and coal plant efficiency gains: How new and forthcoming air regulations affect outcomes

    International Nuclear Information System (INIS)

    Adair, Sarah K.; Hoppock, David C.; Monast, Jonas J.

    2014-01-01

    Forthcoming carbon dioxide (CO 2 ) regulations for existing power plants in the United States have heightened interest in thermal efficiency gains for coal-fired power plants. Plant modifications to improve thermal efficiency can trigger New Source Review (NSR), a Clean Air Act requirement to adopt of state-of-the-art pollution controls. This article explores whether existing coal plants would likely face additional pollution control requirements if they undertake modifications that trigger NSR. Despite emissions controls that are or will be installed under the Mercury and Air Toxics Standards (MATS) and Clean Air Interstate Rule (CAIR) or its replacement, 80% of coal units (76% of capacity) that are expected to remain in operation are not projected to meet the minimum NSR requirements for at least one pollutant: nitrogen oxides or sulfur dioxide. This is an important consideration for the U.S. Environmental Protection Agency and state policymakers as they determine the extent to which CO 2 regulation will rely on unit-by-unit thermal efficiency gains versus potential flexible compliance strategies such as averaging, trading, energy efficiency, and renewable energy. NSR would likely delay and add cost to thermal efficiency projects at a majority of coal units, including projects undertaken to comply with forthcoming CO 2 regulation. - Highlights: • We explore the status of the U.S. coal-fired fleet relative to New Source Review (NSR) requirements. • Modifications to improve thermal efficiency can trigger NSR. • Thermal efficiency gains may also be an important strategy for forthcoming CO 2 regulation. • 80% Of non-retiring coal-fired units are projected not to meet minimum NSR requirements. • NSR is an important consideration for the design of CO 2 regulations for existing plants

  6. Fuelling clean air : municipal fuel purchasing policies that reduce emissions contributing to poor air quality and climate change

    International Nuclear Information System (INIS)

    Perrotta, K.

    2003-03-01

    Air quality can be improved by low sulphur fuels in two ways: through the direct reduction of sulphates, sulphur dioxide and PM; and by improving the effectiveness of existing emission control devices. This report examined three case studies involving the fuel purchasing policies in three Ontario municipalities: Toronto, Waterloo, and Brampton. Toronto favors purchasing conventional fuels with lower sulphur levels. Waterloo will purchase on-road diesel for its off-road diesel fleet; ultra low sulphur diesel (ULSD) for buses; and 10 per cent ethanol blended with 90 per cent gasoline (E10) for its gasoline-fuelled fleet. Brampton purchased 20 per cent biodiesel blended with 80 per cent on-road diesel (B20). Two approaches were examined for lowering emissions from gasoline fuelled vehicles: favouring gasoline with the lowest sulphur levels, and purchasing E10. It was recommended that the Greater Toronto Area (GTA) Clean Air Council look into: ownership of emissions trading credits created as a result of fuel purchasing policies; the benefits of, and mechanisms available for, pooling fuel purchases; and, establishing a subcommittee to monitor developments related to fuels, vehicles and emission control technologies. 48 refs., 18 tabs

  7. Nuclear air cleaning handbook. Design, construction, and testing of high-efficiency air cleaning systems for nuclear application

    International Nuclear Information System (INIS)

    Burchsted, C.A.; Kahn, J.E.; Fuller, A.B.

    1976-01-01

    The handbook is a revision of ORNL/NSIC-65. The purposes of the handbook are to summarize available information in a manner that is useful to the designer, to point out shortcomings in design and construction practice, and to provide guides and recommendations for the design of future systems

  8. Nuclear air cleaning handbook. Design, construction, and testing of high-efficiency air cleaning systems for nuclear application

    Energy Technology Data Exchange (ETDEWEB)

    Burchsted, C.A.; Kahn, J.E.; Fuller, A.B.

    1976-01-01

    The handbook is a revision of ORNL/NSIC-65. The purposes of the handbook are to summarize available information in a manner that is useful to the designer, to point out shortcomings in design and construction practice, and to provide guides and recommendations for the design of future systems. (TFD)

  9. Efficiency at Sorting Cards in Compressed Air

    Science.gov (United States)

    Poulton, E. C.; Catton, M. J.; Carpenter, A.

    1964-01-01

    At a site where compressed air was being used in the construction of a tunnel, 34 men sorted cards twice, once at normal atmospheric pressure and once at 3½, 2½, or 2 atmospheres absolute pressure. An additional six men sorted cards twice at normal atmospheric pressure. When the task was carried out for the first time, all the groups of men performing at raised pressure were found to yield a reliably greater proportion of very slow responses than the group of men performing at normal pressure. There was reliably more variability in timing at 3½ and 2½ atmospheres absolute than at normal pressure. At 3½ atmospheres absolute the average performance was also reliably slower. When the task was carried out for the second time, exposure to 3½ atmospheres absolute pressure had no reliable effect. Thus compressed air affected performance only while the task was being learnt; it had little effect after practice. No reliable differences were found related to age, to length of experience in compressed air, or to the duration of the exposure to compressed air, which was never less than 10 minutes at 3½ atmospheres absolute pressure. PMID:14180485

  10. A survey of the extent of compliance with Title V of the Clean Air Act Amendments of 1990

    Energy Technology Data Exchange (ETDEWEB)

    Goss, Carol; Sandhu, Ravinder [Department of Environmental Analysis and Management, Troy State University, Troy (United States)

    1999-04-01

    As public awareness of environmental issues increases, the federal government is faced with continually renewing and redesigning the air quality regulations for the betterment of air quality. This study was designed to survey the compliance of Title V of the 1990 Clean Air Act by industries in Alabama, California, Pennsylvania, and South Carolina. Forty survey forms per state were sent out to facilities selected at random. The maximum number of responses were obtained from South Carolina followed by Alabama, California, and Pennsylvania. The study showed that large industries, with an average annual revenue in excess of ?10 million and more than 300 employees, responded with higher frequency and these companies were more in compliance with Title V of the 1990 Clean Air Act

  11. Assessment of clean development mechanism potential of large-scale energy efficiency measures in heavy industries

    International Nuclear Information System (INIS)

    Hayashi, Daisuke; Krey, Matthias

    2007-01-01

    This paper assesses clean development mechanism (CDM) potential of large-scale energy efficiency measures in selected heavy industries (iron and steel, cement, aluminium, pulp and paper, and ammonia) taking India and Brazil as examples of CDM project host countries. We have chosen two criteria for identification of the CDM potential of each energy efficiency measure: (i) emission reductions volume (in CO 2 e) that can be expected from the measure and (ii) likelihood of the measure passing the additionality test of the CDM Executive Board (EB) when submitted as a proposed CDM project activity. The paper shows that the CDM potential of large-scale energy efficiency measures strongly depends on the project-specific and country-specific context. In particular, technologies for the iron and steel industry (coke dry quenching (CDQ), top pressure recovery turbine (TRT), and basic oxygen furnace (BOF) gas recovery), the aluminium industry (point feeder prebake (PFPB) smelter), and the pulp and paper industry (continuous digester technology) offer promising CDM potential

  12. Preservation of atomically clean silicon surfaces in air by contact bonding

    DEFF Research Database (Denmark)

    Grey, Francois; Ljungberg, Karin

    1997-01-01

    When two hydrogen-passivated silicon surfaces are placed in contact under cleanroom conditions, a weak bond is formed. Cleaving this bond under ultrahigh vacuum (UHV) conditions, and observing the surfaces with low energy electron diffraction and scanning tunneling microscopy, we find that the or...... reconstruction from oxidation in air, Contact bonding opens the way to novel applications of reconstructed semiconductor surfaces, by preserving their atomic structure intact outside of a UHV chamber. (C) 1997 American Institute of Physics.......When two hydrogen-passivated silicon surfaces are placed in contact under cleanroom conditions, a weak bond is formed. Cleaving this bond under ultrahigh vacuum (UHV) conditions, and observing the surfaces with low energy electron diffraction and scanning tunneling microscopy, we find...... that the ordered atomic structure of the surfaces is protected from oxidation, even after the bonded samples have been in air for weeks. Further, we show that silicon surfaces that have been cleaned and hydrogen-passivated in UHV can be contacted in UHV in a similarly hermetic fashion, protecting the surface...

  13. High Mercury Wet Deposition at a "Clean Air" Site in Puerto Rico.

    Science.gov (United States)

    Shanley, James B; Engle, Mark A; Scholl, Martha; Krabbenhoft, David P; Brunette, Robert; Olson, Mark L; Conroy, Mary E

    2015-10-20

    Atmospheric mercury deposition measurements are rare in tropical latitudes. Here we report on seven years (April 2005 to April 2012, with gaps) of wet Hg deposition measurements at a tropical wet forest in the Luquillo Mountains, northeastern Puerto Rico, U.S. Despite receiving unpolluted air off the Atlantic Ocean from northeasterly trade winds, during two complete years the site averaged 27.9 μg m(-2) yr(-1) wet Hg deposition, or about 30% more than Florida and the Gulf Coast, the highest deposition areas within the U.S. These high Hg deposition rates are driven in part by high rainfall, which averaged 2855 mm yr(-1). The volume-weighted mean Hg concentration was 9.8 ng L(-1), and was highest during summer and lowest during the winter dry season. Rainout of Hg (decreasing concentration with increasing rainfall depth) was minimal. The high Hg deposition was not supported by gaseous oxidized mercury (GOM) at ground level, which remained near global background concentrations (<10 pg m(-3)). Rather, a strong positive correlation between Hg concentrations and the maximum height of rain detected within clouds (echo tops) suggests that droplets in high convective cloud tops scavenge GOM from above the mixing layer. The high wet Hg deposition at this "clean air" site suggests that other tropical areas may be hotspots for Hg deposition as well.

  14. Pollution prevention incentives and disincentives created by the Clean Air Act

    International Nuclear Information System (INIS)

    Webb, C.F.; Wolffe, G.S.

    1998-01-01

    Environmental laws and regulations have not always been implemented in a manner that allows for the consideration of pollution prevention (P2) alternatives as a means of achieving progress toward air quality goals. Recently, the US Environmental Protection Agency (EPA) has been making strides to reinterpret laws and regulations to be more flexible and encourage P2 projects that do not involve end-of-the-pipe controls. For instance, when conducting control technology evaluations such as best available control technology (BACT) and lowest achievable emission rate (LAER), facilities can and should take into consideration P2 options that accomplish the same emission reduction goals as traditional end-of-the-pipe controls. There are also new emissions trading provisions building on those allowed in the acid rain and offset trading programs that promise to make P2 projects much more cost-effective. Several traditional 'command-and-control' programs of the Clean Air Act (CAA) also promote P2 projects. For instance, emission reductions realized through P2 projects show managers a direct cost savings due to reductions in Title V facility annual emissions fees and possibly a direct cost benefit through sale of emission credits. Furthermore, the CAA encourages P2 indirectly through the detail understanding of processes gained from emissions inventories and risk management plans (RMPs). However, many CAA prescriptive programs create disincentives for industry to select P2 alternatives. 30 refs

  15. Experimental evaluation on energy performance of innovative clean air heat pump for indoor environment control in summer and winter seasons

    DEFF Research Database (Denmark)

    Nie, Jinzhe; Fang, Lei; Olesen, Bjarne W.

    2014-01-01

    Based on the air purification capacity of regenerative silica gel rotor, an innovative clean air heat pump (CAHP) was designed, developed and investigated through experimental studies. The CAHP integrated air purification, dehumidification and heating/cooling in one unit. A prototype of the CAHP...... was developed. Laboratory experimental studies were conducted to investigate its energy performance under different outdoor climates including cold, mild-cold, mild-hot and extremely hot and humid climates. The energy performance of the CAHP was then evaluated by comparing with a conventional air source heat...... pump. The results showed that to keep same indoor air quality, the CAHP could save substantial amount of energy. For example, compared to the conventional air source heat pump, the CAHP could save up to 59%, 40%, 30% of electricity for ventilation and air conditioning in a test room in summer...

  16. 77 FR 73459 - California State Motor Vehicle Pollution Control Standards; Notice of Waiver of Clean Air Act...

    Science.gov (United States)

    2012-12-10

    ... ENVIRONMENTAL PROTECTION AGENCY [FRL-9759-4] California State Motor Vehicle Pollution Control Standards; Notice of Waiver of Clean Air Act Preemption; California's 2010 Model Year Heavy-Duty Vehicle and... for CARB's own motor vehicle pollution control program based on lack of compelling and extraordinary...

  17. 77 FR 32135 - Notice of Lodging of Consent Decree Under the Clean Air Act and the Emergency Planning and...

    Science.gov (United States)

    2012-05-31

    ... Emergency Planning and Community Right to Know Act. Notice is hereby given that on May 23, 2012, a proposed..., was lodged with the United States District Court for the Northern District of Indiana. The settlement... the Clean Air Act and under the Emergency Planning and Community Right to Know Act related to the...

  18. 78 FR 1759 - Notice of Approval of Clean Air Act Outer Continental Shelf Minor Source/Title V Minor Permit...

    Science.gov (United States)

    2013-01-09

    ... documents relevant to the above-referenced permits are available for public inspection during normal... permit decisions, to the extent it is available, may be sought by filing a petition for review in the... ENVIRONMENTAL PROTECTION AGENCY 40 CFR PART 52 [FRL-9767-5] Notice of Approval of Clean Air Act...

  19. 78 FR 6817 - Clean Air Act Operating Permit Program; Petition for Objection to State Operating Permit for...

    Science.gov (United States)

    2013-01-31

    ... Wisconsin Public Service Corporation--JP Pulliam Plant. Pursuant to section 505(b)(2) of the Act, a... ENVIRONMENTAL PROTECTION AGENCY [FRL 9774-6] Clean Air Act Operating Permit Program; Petition for Objection to State Operating Permit for Wisconsin Public Service Corporation--JP Pulliam Plant AGENCY...

  20. 76 FR 53452 - Clean Air Act Operating Permit Program; Response to Petition To Reopen the 2001 Title V Permit...

    Science.gov (United States)

    2011-08-26

    ... ENVIROMENTAL PROTECTION AGENCY [FRL-9457-3 ] Clean Air Act Operating Permit Program; Response to Petition To Reopen the 2001 Title V Permit for Reliant Portland Generating Station, Upper Mount Bethel Township, Northampton County, PA AGENCY: Environmental Protection Agency (EPA). ACTION: Notice of action...

  1. A resource allocation model to support efficient air quality ...

    African Journals Online (AJOL)

    Efficient implementation of policies and strategies require that ... †Graduate School of Business Leadership, University of South Africa, P.O. Box 392, Pretoria, 0003, .... and source, emissions, air quality and meteorological data reporting.

  2. Aerodynamic Efficiency Enhancements for Air Vehicles, Phase I

    Data.gov (United States)

    National Aeronautics and Space Administration — The need for aerodynamics-based efficiency enhancements for air vehicles is presented. Concepts are presented for morphing aircraft, to enable the aircraft to...

  3. Aerodynamic Efficiency Enhancements for Air Vehicles, Phase II

    Data.gov (United States)

    National Aeronautics and Space Administration — The need for aerodynamics-based efficiency enhancements for air vehicles is presented. The results of the Phase I investigation of concepts for morphing aircraft are...

  4. Efficient Conversation: The Talk between Pilots and Air Traffic Controllers.

    Science.gov (United States)

    Simmons, James L.

    Two-way radio communications between air traffic controllers using radar on the ground to give airplane pilots instructions are of interest within the developing framework of the sociology of language. The main purpose of air traffic control language is efficient communication to promote flight safety. This study describes the standardized format…

  5. Monitor Clean and Efficient. Background information. Methods and references as applied in the Monitor in April 2009

    International Nuclear Information System (INIS)

    Gerdes, J.; De Ligt, T.

    2010-01-01

    This report contains background information about the Monitor Clean and Efficient that was published in April 2009. The goal and approach of the Monitor are clarified, as well as the methods and data that are used. The structure of this report resembles the structure of the Monitor. Sources and dates of availability are mentioned along with the data, as are the parties collecting and processing the information. The results that were found using this methodology have been published in the Monitor Clean and Efficient. [nl

  6. Evaluation of seasonal exergy efficiency of air handing unit

    Directory of Open Access Journals (Sweden)

    Kęstutis Genys

    2015-10-01

    Full Text Available The article deals with the air handling unit seasonal exergy efficiency. TRNSYS simulation tool is used to evaluate it. The object of research is air treatment device used to treat an air for the ventilation of laboratory. The mathematical model of air handling unit using TRNSYS simulation tool was developed when the technical parameters of air handling unit and energy exchange in it were analysed. The developed model according to the made observations during the warm and cold periods was tested and validation of elements was performed. The simulation of air handling unit operation after the verification of reliability and permitted tolerances was performed. The control mechanisim which allows simulating the operation of air handling unit during cold and warm periods of the year was made. The mathematical algorithm for calculation of air handling unit exergy efficiency coefficient applying the principles of exergy analysis was developed. The seasonal exergy efficiency of air handling unit equal to 3.94 percent during the simulation was obtained.

  7. 40 CFR 60.3063 - When must I comply if my air curtain incinerator burns only wood waste, clean lumber, and yard...

    Science.gov (United States)

    2010-07-01

    ... incinerator burns only wood waste, clean lumber, and yard waste? 60.3063 Section 60.3063 Protection of... Units That Commenced Construction On or Before December 9, 2004 Model Rule-Air Curtain Incinerators That Burn Only Wood Waste, Clean Lumber, and Yard Waste § 60.3063 When must I comply if my air curtain...

  8. Safety by design: effects of operating room floor marking on the position of surgical devices to promote clean air flow compliance and minimise infection risks

    NARCIS (Netherlands)

    de Korne, Dirk F.; van Wijngaarden, Jeroen D. H.; van Rooij, Jeroen; Wauben, Linda S. G. L.; Hiddema, U. Frans; Klazinga, Niek S.

    2012-01-01

    To evaluate the use of floor marking on the positioning of surgical devices within the clean air flow in an operating room (OR) to minimise infection risk. Laminar flow clean air systems are important in preventing infection in ORs but, for optimal results, surgical devices must be correctly

  9. The temporal evolution process from fluorescence bleaching to clean Raman spectra of single solid particles optically trapped in air

    Science.gov (United States)

    Gong, Zhiyong; Pan, Yong-Le; Videen, Gorden; Wang, Chuji

    2017-12-01

    We observe the entire temporal evolution process of fluorescence and Raman spectra of single solid particles optically trapped in air. The spectra initially contain strong fluorescence with weak Raman peaks, then the fluorescence was bleached within seconds, and finally only the clean Raman peaks remain. We construct an optical trap using two counter-propagating hollow beams, which is able to stably trap both absorbing and non-absorbing particles in air, for observing such temporal processes. This technique offers a new method to study dynamic changes in the fluorescence and Raman spectra from a single optically trapped particle in air.

  10. High efficiency particulate air filter experience survey

    International Nuclear Information System (INIS)

    Carbaugh, E.H.

    1983-01-01

    Causes and magnitude of HEPA filter changeouts and failures at DOE sites for the years 1977 to 1979 were evaluated. Conclusions inferred from the data follow: HEPA filters have been generally performing the task they were designed for; most changeouts have been made because of filter plugging, preventive maintenance, or precautionary reasons rather than evidence of filter failure; where failures have been experienced, records generally have not been adequate to determine the cause of failure; where cause of failure has been determined, damage attributed to personnel handling and installation has been substantially more prevalent than that from filter environmental exposure. The need for improved personnel training in handling and installation was stressed. Some reduction in filter failure frequency can be achieved by improving the acid and moisture resistance of filters, and providing adequate pretreatment of air prior to HEPA filtration

  11. Modeling and optimization of processes for clean and efficient pulverized coal combustion in utility boilers

    Directory of Open Access Journals (Sweden)

    Belošević Srđan V.

    2016-01-01

    Full Text Available Pulverized coal-fired power plants should provide higher efficiency of energy conversion, flexibility in terms of boiler loads and fuel characteristics and emission reduction of pollutants like nitrogen oxides. Modification of combustion process is a cost-effective technology for NOx control. For optimization of complex processes, such as turbulent reactive flow in coal-fired furnaces, mathematical modeling is regularly used. The NOx emission reduction by combustion modifications in the 350 MWe Kostolac B boiler furnace, tangentially fired by pulverized Serbian lignite, is investigated in the paper. Numerical experiments were done by an in-house developed three-dimensional differential comprehensive combustion code, with fuel- and thermal-NO formation/destruction reactions model. The code was developed to be easily used by engineering staff for process analysis in boiler units. A broad range of operating conditions was examined, such as fuel and preheated air distribution over the burners and tiers, operation mode of the burners, grinding fineness and quality of coal, boiler loads, cold air ingress, recirculation of flue gases, water-walls ash deposition and combined effect of different parameters. The predictions show that the NOx emission reduction of up to 30% can be achieved by a proper combustion organization in the case-study furnace, with the flame position control. Impact of combustion modifications on the boiler operation was evaluated by the boiler thermal calculations suggesting that the facility was to be controlled within narrow limits of operation parameters. Such a complex approach to pollutants control enables evaluating alternative solutions to achieve efficient and low emission operation of utility boiler units. [Projekat Ministarstva nauke Republike Srbije, br. TR-33018: Increase in energy and ecology efficiency of processes in pulverized coal-fired furnace and optimization of utility steam boiler air preheater by using in

  12. The Clean Air Act Amendments of 1990: Opportunities for Promoting Renewable Energy; Final Report: December 11, 2000

    Energy Technology Data Exchange (ETDEWEB)

    Wooley, D.R.; Morss, E.M. (Young, Sommer, Ward, Ritzenberg, Wooley, Baker and Moore, LLC, Albany, New York)

    2001-01-08

    This report explores key aspects of the intersection between the nation's clean air and energy goals and proposes alternatives for encouraging renewable energy in the context of the federal Clean Air Act (CAA). As with most environmental statutes enacted in the early 1970s, the 1970 CAA embraced a somewhat rigid ''command-and-control'' approach to achieving its clean air goals. Although effective, this approach has been criticized for discouraging creative and cost-effective solutions to reducing air emissions. In response to this concern, Congress included the first significant market-based program to address an environmental problem-in this case, acid rain caused by sulfur dioxide (SO2) emissions from power plants-in the 1990 CAA Amendments. This program prompted the federal government and various state governments to pursue other market-based programs to address air pollution problems. Ten years have elapsed since the passage of the 1990 CAA Amendments, so the time is ripe to consider expanding opportunities for renewable energy development in the reform of clean air policies. A significant potential for renewables exists in conjunction with international efforts to reduce emissions of greenhouse gases (GHG), including CO2. Unfortunately, Congressional opposition to international GHG reduction agreements makes it difficult to develop GHG emission-reduction programs, including a cap-and-trade alternative, that would enable the renewables industry to harness this potential. The renewable industry can, however, track developments both nationally and internationally to ensure that the programs developed adequately address renewables.

  13. Lab-scale investigation of Middle-Bosnia coals to achieve high-efficient and clean combustion technology

    Directory of Open Access Journals (Sweden)

    Smajevic Izet

    2014-01-01

    Full Text Available This paper describes full lab-scale investigation of Middle-Bosnia coals launched to support selection an appropriate combustion technology and to support optimization of the boiler design. Tested mix of Middle-Bosnia brown coals is projected coal for new co-generation power plant Kakanj Unit 8 (300-450 MWe, EP B&H electricity utility. The basic coal blend consisting of the coals Kakanj: Breza: Zenica at approximate mass ratio of 70:20:10 is low grade brown coal with very high percentage of ash - over 40%. Testing that coal in circulated fluidized bed combustion technique, performed at Ruhr-University Bohum and Doosan Lentjes GmbH, has shown its inconveniency for fluidized bed combustion technology, primarily due to the agglomeration problems. Tests of these coals in PFC (pulverized fuel combustion technology have been performed in referent laboratory at Faculty of Mechanical Engineering of Sarajevo University, on a lab-scale PFC furnace, to provide reliable data for further analysis. The PFC tests results are fitted well with previously obtained results of the burning similar Bosnian coal blends in the PFC dry bottom furnace technique. Combination of the coals shares, the process temperature and the air combustion distribution for the lowest NOx and SO2 emissions was found in this work, provided that combustion efficiency and CO emissions are within very strict criteria, considering specific settlement of lab-scale furnace. Sustainability assessment based on calculation economic and environmental indicators, in combination with Low Cost Planning method, is used for optimization the power plant design. The results of the full lab-scale investigation will help in selection optimal Boiler design, to achieve sustainable energy system with high-efficient and clean combustion technology applied for given coals.

  14. Emissions in 2001 conform the reference scenario (GE WLO with high oil price) and including Clean and Efficient

    International Nuclear Information System (INIS)

    Kroon, P.; Menkveld, M.

    2008-08-01

    This memo shows the calculation of an estimate for the total greenhouse gas emissions in 2011 in the reference scenario (GE WLO is the Dutch abbreviation for Global Economy and Welfare and Environment), including the impact of the Clean and Efficient programme from the assessment of ECN (Energy research Centre of the Netherlands) and MNP (Netherlands Environmental Assessment Agency) [nl

  15. Ship emissions and the use of current air cleaning technology: contributions to air pollution and acidification in the Baltic Sea

    Science.gov (United States)

    Claremar, Björn; Haglund, Karin; Rutgersson, Anna

    2017-10-01

    The shipping sector is a significant contributor to emissions of air pollutants in marine and coastal regions. In order to achieve sustainable shipping, primarily through new regulations and techniques, greater knowledge of dispersion and deposition of air pollutants is required. Regional model calculations of the dispersion and concentration of sulfur, nitrogen, and particulate matter, as well as deposition of oxidized sulfur and nitrogen from the international maritime sector in the Baltic Sea and the North Sea, have been made for the years 2011 to 2013. The contribution from shipping is highest along shipping lanes and near large ports for concentration and dry deposition. Sulfur is the most important pollutant coupled to shipping. The contribution of both SO2 concentration and dry deposition of sulfur represented up to 80 % of the total in some regions. WHO guidelines for annual concentrations were not trespassed for any analysed pollutant, other than PM2.5 in the Netherlands, Belgium, and central Poland. However, due to the resolution of the numerical model, 50 km × 50 km, there may be higher concentrations locally close to intense shipping lanes. Wet deposition is more spread and less sensitive to model resolution. The contribution of wet deposition of sulfur and nitrogen from shipping was up to 30 % of the total wet deposition. Comparison of simulated to measured concentration at two coastal stations close to shipping lanes showed some underestimations and missed maximums, probably due to resolution of the model and underestimated ship emissions. A change in regulation for maximum sulfur content in maritime fuel, in 2015 from 1 to 0.1 %, decreases the atmospheric sulfur concentration and deposition significantly. However, due to costs related to refining, the cleaning of exhausts through scrubbers has become a possible economic solution. Open-loop scrubbers meet the air quality criteria but their consequences for the marine environment are largely unknown

  16. Index to the 1st through 16th AEC/ERDA/DOE nuclear air cleaning conferences

    International Nuclear Information System (INIS)

    Burchsted, C.A.

    1981-02-01

    The Proceedings of the sixteen conferences comprise a vertible encyclopedia on the technology of nuclear air and gas treatment and the control of airborne nuclear waste. These Proceedings cover the history of the technology; describe most of the research and developments in the field, worldwide, since the early 1950's; describe the problems that have been encountered and the solutions found to those problems; and summarize experience with equipment and systems developed for the control of airborne radioactive wastes in laboratory, radiochemical, and reactor operations, both government and commercial. The problem with this encyclopedia is that there has been no index to it; there has been no easy way for searching it to find what was available. This index fills the gap. The first conference was an informal meeting of a number of interested parties from among the then AEC contractors. Consequently, there were no proceedings for that meeting. The subsequent conferences, with their years, locations, and Proceedings numbers, are listed. This index consists of three parts: a tabulation of papers and their authors by paper number (Part I); a tabulation of papers and their paper numbers by author (Part II); and a key-word-in context (KWIC) index of papers. The paper number is a two-part designation consisting of the number of the conference (2, 3...16) followed by the page number of the paper in the corresponding Proceedings. The author index lists each author who has participated in the air cleaning conferences over the years, and the paper index lists all authors of the respective papers. The KWIC index is, in effect, a comprehensive subject cross index; each paper is listed as many times, by keyword, as there are major terms (i.e., keywords) in its title. Although this multiple listing results in a lengthy list, it provides a very deep cross-indexing of the papers

  17. BACT analysis under the Clean Air Act's PCD program

    Energy Technology Data Exchange (ETDEWEB)

    Simms, P.; Walke, J. [National Resources Development Council, Washington, DC (United States)

    2006-11-15

    Before a company may build a new major industrial source of air pollution, or make modifications to an existing major source in the USA it must apply for and receive a Clean Air Act (CAA) Prevention of Significant Deterioration (PSD) permit. State environmental agencies typically issue such permits, either under state law or by exercising delegated authority to implement the federal PSD program. To fully comply with the CAA, the emissions limits identified as BACT must incorporate consideration of more than just add-on emissions control technology, they must also reflect appropriate considerations of fuel quality (e.g. low-sulfur coal) and process changes (e.g. advanced combustion techniques) as a means of controlling emissions, and must consider the other environmental and public welfare benefits of the identified emissions control options. Several states including New Mexico and Illinois have already determined that innovated technologies, such as Integrated Gasification Combined Cycle (IGCC), must be considered in connection with the BACT analysis for new coal-fired power plants. Even the notion that BACT is categorically limited in scope to the general type of facility proposed is contrary to EPA precedent. For example, the Environmental Appeals Board (EAB) has explained that permitting authorities retain the discretion under the definition of BACT to require dramatically different facility designs (e.g. a natural gas plant instead of a coal-fired power plant). The best advice for any permit applicant is to include in the BACT analysis a careful and honest examination of better performing alternative processes and/or innovative combustion techniques and to aggressively pursue such options wherever feasible. 17 refs.

  18. The 1990 Clean Air Act Amendments and the Great Lakes economy: Challenges and opportunities

    International Nuclear Information System (INIS)

    Hanson, D.; Molburg, J.; Pandola, G.; Taxon, T.; Lurie, G.; Fisher, R.; Boyd, G.; Fox, J.

    1991-01-01

    This paper deals with the market for SO 2 emission allowances over time and electric utility compliance choices. For currently high emitting plants ( > 2.5 lb SO 2 /MMBtu), the 1990 Clean Air Act Amendments (CAAA) provide for about twice as many SO 2 allowances to be issued per year in Phase 1 (1995--1999) than in Phase 2. Also, considering the scrubber incentives in Phase 1, there is likely to be substantial emission banking for use in Phase 2. Allowance prices are expected to increase over time at a rate less than the return on alternative investments, so utilities which are risk neutral or other potential speculators in the allowance market are not expected to bank allowances. The allowances will be banked by risk averse utilities or the utilities may buy forward contracts for SO 2 allowances. However, speculators may play an important role by selling forward contracts for SO 2 allowances to the risk averse utilities. The Argonne Utility Simulation Model (ARGUS) is being revised to incorporate the provisions of the CAAA acid rain title and to simulate SO 2 allowance prices, compliance choices, capacity expansion, system dispatch, fuel use, and emissions. The revised model (ARGUS2) incorporates unit-level performance data and can incorporate unit-specific compliance decisions when these are known. The model has been designed for convenience in analyzing alternatives scenarios (demand growth rates, technology mix, economic parameters, etc). 1 ref., 5 figs

  19. Future refining impacts of the Clean Air Act amendments of 1990

    International Nuclear Information System (INIS)

    Hadder, G.R.

    1992-01-01

    An assessment of the future refining impacts of the U.S. Clean Air Act Amendments of 1990 has been performed with the Navy Mobility Fuels Forecasting System. In 1992, the Environmental Protection Agency (EPA) should finalize precise requirements for Phase I reformulated gasoline, to be produced in 1995-1999. EPA requirements for Phase II reformulated gasoline, to be produced after 1999, will not be established until 1993. The assessment of refining impacts assumes that reformulated gasoline with likely Phase I specifications will be produced for markets projected for the year 2000. The assessment suggests that gasoline reformulation costs in U.S. coastal and near-coastal refining regions could be 3.5 to 5.6 cents per gallon (1989 U.S. currency). The relative value of MTBE is the most important determinant of the reformulation cost. For mileage equivalent to one gallon of conventional gasoline, the regional total added costs (including reformulation costs) for reformulated gasoline could be 5.2 to 7.6 cents. In blending reformulated gasolines, the reduction of butane for lower Reid vapor pressure and the reduction of reformate for lower aromatics are generally compensated by increased percentages of alkylate and/or straight run naphthas. Relatively larger refinery process capacity additions are required for butane isomerization alkylation aromatics recovery, and distillate hydrotreating. (Author)

  20. Sulfur dioxide emissions and market effects under the Clean Air Act Acid Rain Program

    International Nuclear Information System (INIS)

    Zipper, C.E.; Gilroy, L.

    1998-01-01

    The Clean Air Act Amendments of 1990 (CAAA90) established a national program to control sulfur dioxide (SO 2 ) emissions from electricity generation. CAAA90's market-based approach includes trading and banking of SO 2 -emissions allowances. The paper presents an analysis of data describing electric utility SO 2 emissions in 1995, the first year of the program's Phase I, and market effects over the 1990-95 period. Fuel switching and flue-gas desulfurization were the dominant means used in 1995 by targeted generators to reduce emissions to 51% of 1990 levels. Flue-gas desulfurization costs, emissions allowance prices, low-sulfur coal prices, and average sulfur contents of coals shipped to electric utilities declined over the 1990-95 period. Projections indicate that 13-15 million allowances will have been banked during the programs' Phase I, which ends in 1999, a quantity expected to last through the first decade of the program's stricter Phase II controls. In 1995, both allowance prices and SO 2 emissions were below pre-CAAA90 expectations. The reduction of SO 2 emissions beyond pre-CAAA90 expectations, combined with lower-than-expected allowance prices and declining compliance costs, can be viewed as a success for market-based environmental controls. 21 refs., 6 figs., 3 tabs

  1. Decision-making for complying with SO2 provisions of the Clean Air Act

    International Nuclear Information System (INIS)

    Metzler, A.R.; Gallardy, P.B.; Sebesta, J.J.; Mc Laughlin, B.R.; Ireland, P.A.

    1992-01-01

    Prior to the Clean Air Act of 1990 (CAA), SO 2 removal options were based on a command and control approach for each plant. This approach usually resulted in the addition of an FGD system. However, the CAA offers a market based emission allowance program which offers considerable flexibility for compliance with the new regulations. The flexibility for compliance introduces more available options into the evaluation and increases the complexity of the decision-making process. This paper discusses the methodology of a recent analysis which evaluated various strategies for meeting SO 2 compliance. The importance of evaluating options based on certain goals is discussed. An overall goal was established to develop a flexible and least cost compliance plan. However, these goals need to be balanced against constraints for the utility which may include: minimizing SO 2 allowance market risk; optimizing the availability, cost and timing of capital expenditures into the analysis; minimizing site impacts and construction lead time; and coordinating strategies from various units and stations into a cohesive plan

  2. Human breath measurements in a clean-air chamber to determine half-lives for volatile organic compounds

    Science.gov (United States)

    Gordon, Sydney M.; Wallace, Lance A.; Pelllzzari, Edo D.; O'Neill, Hugh J.

    The expired breath of four non-occupationally exposed subjects was monitored following exposure at near-normal environmental concentrations using a specially developed pulmonary clearance technique. The four were exposed to polluted air on a heavily trafficked freeway or at a local dry-cleaning establishment, then spent the next 10 h in a clean-air environmental chamber. Breath and chamber-air samples were collected at regular intervals throughout the 10-h period and analyzed for the presence of selected target compounds. The breath levels of two of the compounds were elevated and decreased slowly with time once the subjects began to breathe clean air. Nonlinear least-squares fitting of the decay-uptake curves permitted the calculation of biological half-lives. Several of the target compounds occurred, however, at very low levels, and the resultant experimental scatter limited the value of these measurements. Higher initial exposures to most of the target compounds would have improved the reliability of the estimates.

  3. Improving the Solar Panel Efficiency by Using Cooling and Cleaning Techniques

    Directory of Open Access Journals (Sweden)

    Anmar Khalil Ibrahim

    2017-11-01

    Full Text Available This paper is a contribution to research work which aims at ending the electricity crisis in Iraq. The electric power stations, which use conventional fuel, are unable to provide the growing population with electricity all day-long. Moreover, electric distribution lines are sometimes exposed to attacks by terrorists. This paper recommends solar energy as the optimum solution to the electricity problem in Iraq, since it is both renewable and friendly to the environment. The paper also concentrated on reliability techniques to improve the efficiency of the solar energy system. This was achieved by means of designing and constructing a cooling system that consists of fans, sprinklers and wipers to eliminate excessive heat from solar panels when temperature rises to maximum levels. Sprinklers and wipers are also useful for cleaning the panels because dust is a negative factor which undermines the generation capacity of solar panels.   The cooling system is operated by means of a microcontroller that is programmed through Proteus 8, Arduino, and Matlab2016. Statistics reveal that a cooling system has significantly improved the productive capacity of the solar system and it can achieve an energy gain of (34.55%.

  4. New, Efficient and Clean Strategies to Explore CP Violation Through Neutral B Decays

    CERN Document Server

    Fleischer, Robert

    2003-01-01

    We point out that decays of the kind $B_d\\to D_\\pm K_{S(L)}$ and $B_s\\to D_\\pm\\eta^{(')},D_\\pm\\phi, ...$, where $D_+$ and $D_-$ denote the CP-even and CP-odd eigenstates of the neutral D-meson system, respectively, provide very efficient, theoretically clean determinations of the angle $\\gamma$ of the unitarity triangle. In this new strategy, we use the $B^0_q$--$\\bar{B^0_q}$ ($q\\in\\{d,s\\}$) mixing phase $\\phi_q$ as an input, and employ only ``untagged'' and mixing-induced CP-violating observables, which satisfy a very simple relation, allowing us to determine $\\tan\\gamma$. Using a plausible dynamical assumption, $\\gamma$ can be fixed in an essentially unambiguous manner. The corresponding formalism can also be applied to $B_d\\to D_\\pm\\pi^0,D_\\pm\\rho^0, >...$ and $B_s\\to D_\\pm K_{S(L)}$ decays. Although these modes appear less attractive for the extraction of $\\gamma$, they provide interesting determinations of $\\sin\\phi_q$. In comparison with the conventional $B_d\\to J/\\psi K_{S(L)}$ and $B_s\\to J/\\psi\\phi$ ...

  5. Efficient production and economics of the clean fuel hydrogen. Paper no. IGEC-1-Keynote-Elnashaie

    International Nuclear Information System (INIS)

    Elnashaie, S.

    2005-01-01

    This paper/plenary lecture to this green energy conference briefly discusses six main issues: 1) The future of hydrogen economy; 2) Thermo-chemistry of hydrogen production for different techniques of autothermic operation using different feedstocks; 3) Improvement of the hydrogen yield and minimization of reformer size through combining fast fluidization with hydrogen and oxygen membranes together with CO 2 sequestration; 4) Efficient production of hydrogen using novel Autothermal Circulating Fluidized Bed Membrane Reformer (ACFBMR); 5) Economics of hydrogen production; and, 6) Novel gasification process for hydrogen production from biomass. It is shown that hydrogen economy is not a Myth as some people advocate, and that with well-directed research it will represent a bright future for humanity utilizing such a clean, everlasting fuel, which is also free of deadly conflicts for the control of energy sources. It is shown that autothermic production of hydrogen using novel reformers configurations and wide range of feedstocks is a very promising route towards achieving a successful hydrogen economy. A novel process for the production of hydrogen from different renewable biomass sources is presented and discussed. The process combines the principles of pyrolysis with the simultaneous use of catalyst, membranes and CO 2 sequestration to produce pure hydrogen directly from the unit. Some of the novel processes presented are essential components of modern bio-refineries. (author)

  6. Optimal sampling plan for clean development mechanism energy efficiency lighting projects

    International Nuclear Information System (INIS)

    Ye, Xianming; Xia, Xiaohua; Zhang, Jiangfeng

    2013-01-01

    Highlights: • A metering cost minimisation model is built to assist the sampling plan for CDM projects. • The model minimises the total metering cost by the determination of optimal sample size. • The required 90/10 criterion sampling accuracy is maintained. • The proposed metering cost minimisation model is applicable to other CDM projects as well. - Abstract: Clean development mechanism (CDM) project developers are always interested in achieving required measurement accuracies with the least metering cost. In this paper, a metering cost minimisation model is proposed for the sampling plan of a specific CDM energy efficiency lighting project. The problem arises from the particular CDM sampling requirement of 90% confidence and 10% precision for the small-scale CDM energy efficiency projects, which is known as the 90/10 criterion. The 90/10 criterion can be met through solving the metering cost minimisation problem. All the lights in the project are classified into different groups according to uncertainties of the lighting energy consumption, which are characterised by their statistical coefficient of variance (CV). Samples from each group are randomly selected to install power meters. These meters include less expensive ones with less functionality and more expensive ones with greater functionality. The metering cost minimisation model will minimise the total metering cost through the determination of the optimal sample size at each group. The 90/10 criterion is formulated as constraints to the metering cost objective. The optimal solution to the minimisation problem will therefore minimise the metering cost whilst meeting the 90/10 criterion, and this is verified by a case study. Relationships between the optimal metering cost and the population sizes of the groups, CV values and the meter equipment cost are further explored in three simulations. The metering cost minimisation model proposed for lighting systems is applicable to other CDM projects as

  7. Development of ultra low dew-point clean air generator; Cho tei roten seijo kuki hassei sochi no kaihatsu

    Energy Technology Data Exchange (ETDEWEB)

    Nishimura, H.; Okamura, N. [Takasago thermal Engineering Co., Ltd., Kanagawa (Japan)

    2000-05-10

    To reduce the manufacturing cost of semiconductors, some systems have been proposed that use a cheap and high purity Clean Dry Air (CDA). CDA can reduce process step such as wafer cleaning, because CDA flow in stocker prevents the wafer surface from adsorbing of moisture and organic impurities. We have already optimized a two-stage rotary dehumidifier and have conducted a study of methods for cheaply manufacturing air that has a low dew-point of -70 degree C to -50 degree C. We have further developed the method in which a dry dehumidifier is used, and developed an ultra low dew-point air generator. The air generator is a three-stage rotary dehumidifier in which a further stage is added to the two-stage rotary dehumidifier. The main component of the rotors is metal silicate. The air generator can supply dry air with a dew-point of -110 degree C. or less, in which the concentration in all gaseous contaminants is far below 1 ppb. We made a trial calculation of the manufacturing cost, and an average cost of 0.25 yen/m{sup 3} was obtained. (author)

  8. A 14-year longitudinal study of the impact of clean indoor air legislation on state smoking prevalence, USA, 1997-2010.

    Science.gov (United States)

    Becker, Craig M; Lee, Joseph G L; Hudson, Suzanne; Hoover, Jeanne; Civils, Donald

    2017-06-01

    While clean indoor air legislation at the state level is an evidence-based recommendation, only limited evidence exists regarding the impact of clean indoor air policies on state smoking prevalence. Using state smoking prevalence data from 1997 to 2010, a repeated measures observational analysis assessed the association between clean indoor air policies (i.e., workplace, restaurant, and bar) and state smoking prevalence while controlling for state cigarette taxes and year. The impacts from the number of previous years with any clean indoor air policy, the number of policies in effect during the current year, and the number of policies in effect the previous year were analyzed. Findings indicate a smoking prevalence predicted decrease of 0.13 percentage points (p=0.03) for each additional year one or more clean indoor air policies were in effect, a predicted decrease of 0.12 percentage points (p=0.09) for each policy in effect in the current year, and a predicted decrease of 0.22 percentage points (p=0.01) for each policy in effect in the previous year on the subsequent year. Clean indoor air policies show measurable associations with reductions in smoking prevalence within a year of implementation above and beyond taxes and time trends. Further efforts are needed to diffuse clean indoor air policies across states and provinces that have not yet adopted such policies. Copyright © 2017 The Authors. Published by Elsevier Inc. All rights reserved.

  9. Clean and efficient energy conversion processes (Cecon-project). Final report

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1998-12-31

    The objectives of the work programme reported are the development and testing of two optimised energy conversion processes, both consisting of a radiant surface gas burner and a ceramic heat exchanger. The first sub-objective of the programme is related to industrial heating, drying and curing processes requireing low and medium heat fluxes. It is estimated that around one tenth of the total EC industrial energy use is associated with such processes. The majority of these processes currently use convection and conduction as the main heat transfer mechanisms and overall energy efficiencies are typically below 25%. For many drying and finishing processes (such as curing powder coatings and drying paints, varnishes, inks, and for the fabrication of paper and textiles), radiant heating can achieve much faster dyring rates and higher energy efficiency than convective heating. In the project new concepts of natural gas fired radiant heating have been investigated which would be much more efficient than the existing processes. One element of the programme was the evelopment of gas burners having enhanced radiant efficiencies. A second concerned the investigation of the safety of gas burners containing significant volumes of mixed gas and air. Finally the new gas burners were tested in combination with the high temperature heat exchanger to create highly efficient radiant heating systems. The second sub-objective concerned the development of a compact low cost heat exchanger capable of achieving high levels of heat recovery (up to 60%) which could be easily installed on industrial processes. This would make heat recovery a practical proposition on processes where existing heat recovery technology is currently not cost effective. The project will have an impact on industrial processes consuming around 80 MTOE of energy per year within EU countries (1 MTOE equals 41.8 PJ). The overall energy saving potential of the project is estimated to be around 22 MTOE which is around 10

  10. Efficiency of deodorant materials for ammonia reduction in indoor air

    DEFF Research Database (Denmark)

    Bivolarova, Mariya Petrova; Mizutani, Chiyomi; Melikov, Arsen Krikor

    2014-01-01

    A comparative study about the removability of ammonia gas in the air by activated carbon fiber (ACF) felt chemically treated with acid and a cotton fabric processed with iron phthalocyanine with copper (Cu) was performed in small-scale experiments. The test rig consisted of a heated plate and its...... proved activated carbon fiber felt with acid to be highly efficient in removing ammonia gas. Air temperature did not have profound effect on ACF performance. However, efficiency of the carbon fiber felt decreased when relative humidity was raised from 20 to 80%....

  11. Health and efficiency in trimix versus air breathing in compressed air workers

    NARCIS (Netherlands)

    van Rees Vellinga, T. P.; Verhoeven, A. C.; van Dijk, F. J. H.; Sterk, W.

    2006-01-01

    The Western Scheldt Tunneling Project in the Netherlands provided a unique opportunity to evaluate the effects of trimix usage on the health of compressed air workers and the efficiency of the project. Data analysis addressed 318 exposures to compressed air at 3.9-4.4 bar gauge and 52 exposures to

  12. WRF modeling of PM2.5 remediation by SALSCS and its clean air flow over Beijing terrain.

    Science.gov (United States)

    Cao, Qingfeng; Shen, Lian; Chen, Sheng-Chieh; Pui, David Y H

    2018-06-01

    Atmospheric simulations were carried out over the terrain of entire Beijing, China, to investigate the effectiveness of an air-pollution cleaning system named Solar-Assisted Large-Scale Cleaning System (SALSCS) for PM 2.5 mitigation by using the Weather Research and Forecasting (WRF) model. SALSCS was proposed to utilize solar energy to generate airflow therefrom the airborne particulate pollution of atmosphere was separated by filtration elements. Our model used a derived tendency term in the potential temperature equation to simulate the buoyancy effect of SALSCS created with solar radiation on its nearby atmosphere. PM 2.5 pollutant and SALSCS clean air were simulated in the model domain by passive tracer scalars. Simulation conditions with two system flow rates of 2.64 × 10 5  m 3 /s and 3.80 × 10 5  m 3 /s were tested for seven air pollution episodes of Beijing during the winters of 2015-2017. The numerical results showed that with eight SALSCSs installed along the 6 th Ring Road of the city, 11.2% and 14.6% of PM 2.5 concentrations were reduced under the two flow-rate simulation conditions, respectively. Copyright © 2018 Elsevier B.V. All rights reserved.

  13. An analysis of SO2 emission compliance under the 1990 Clean Air Act Amendments

    International Nuclear Information System (INIS)

    Hanson, D.A.; Cilek, C.M.; Pandola, G.; Taxon, T.

    1992-01-01

    The effectiveness of SO 2 emission allowance trading under Title 4 of the 1990 Amendments to the Clean Air Act (CAA) is of great interest due to the innovative nature of this market incentive approach. However, it may be a mistake to frame the compliance problem for a utility as a decision to trade or not. Trading of allowances should be the consequence, not the decision. The two meaningful decision variables for a utility are the control approaches chosen for its units and the amount of allowances to hold in its portfolio of assets for the future. The number allowances to be bought or sold (i.e. traded) is determined by the emission reduction and banking decisions. Our preferred approach is to think of the problem in terms of ABC's of the 1990 CAA Amendments: abatement strategy, banking, and cost competitiveness. The implications of the general principles presented in this paper on least cost emission reductions and emissions banking to hedge against risk are being simulated with version 2 of the ARGUS model representing the electric utility sector and regional coal supplies and transportation rates. A rational expectations forecast for allowances prices is being computed. The computed allowance price path has the property that demand for allowances by electric utilities for current use or for banking must equal the supply of allowances issued by the federal government or provided as forward market contracts in private market transactions involving non-utility speculators. From this rational expectations equilibrium forecast, uncertainties are being explored using sensitivity tests. Some of the key issues are the amount of scrubbing and when it is economical to install it, the amount of coal switching and how much low sulfur coal premiums will be bid up; and the amount of emission trading within utilities and among different utilities

  14. Residential air-conditioner usage in China and efficiency standardization

    International Nuclear Information System (INIS)

    Wu, Jianghong; Liu, Chaopeng; Li, Hongqi; Ouyang, Dong; Cheng, Jianhong; Wang, Yuanxia; You, Shaofang

    2017-01-01

    Determining the real energy consumption and usage pattern of a room air-conditioner (RAC) are important issues from the point of view of both RAC design and evaluation of its energy efficiency. An air-conditioner's running time is fundamental data for the calculation of SEER and APF values. Therefore, in 2010, a nationwide investigation of RAC usage was conducted and 400 selected air-conditioning-units were monitored for a full year to obtain data on their cooling and heating usage. Two running time curves (cooling and heating) were obtained for the air-conditioners as a function of outdoor air temperatures using statistical analysis. The results show that the 27–30 °C temperature range accounts for more than 52% of the cooling time. Conversely, the 0–8 °C temperature range is associated with more than 75% of the heating time. The research presented in this paper has significantly contributed to China's new variable-speed RAC efficiency standard (GB21455-2013). It also has far-reaching implications for both the air-conditioner industry and energy policy in China due to its different method of calculating energy efficiency. - Highlights: • A nationwide survey to realize China's residential air-conditions usage behaviors. • Air-conditioner running time-environment temperature curves are obtained. • The peak heating demand and peak cooling demand happen at 28 °C and 4 °C, respectively. • The temperature of 27 °C–30 °C accounts for over 52% refrigeration time. • The temperature of 0 °C–8 °C occupies more than 75% heating time.

  15. The construction of a process line for high efficiency silicon solar cells under clean-room conditions

    International Nuclear Information System (INIS)

    Aberle, A.; Faller, C.; Grille, T.; Glunz, S.; Kamerewerd, F.J.; Kopp, J.; Knobloch, J.; Klussmann, S.; Lauby, E.; Noel, A.; Paul, O.; Schaeffer, E.; Schubert, U.; Seitz, S.; Sterk, S.; Voss, B.; Warta, W.; Wettling, W.

    1992-08-01

    The aim of this research project was to plan, construct and test a clean-room technology laboratory for the manufacturing of silicon solar cells with 20% efficiency (1.5AM). In addition to the establishment of the laboratory, there existed the case of establishing the material and technological fundamentals of high-efficiency solar cells, testing and optimizing all stages of production as well as constructing test stands for accompanying characterisation work. The following final report describes the construction of the laboratory and characterisation systems, the material elements of high-efficiency solar cells as well as the most important results of solar cell production and optimisation. (orig./BWI) [de

  16. Ship emissions and the use of current air cleaning technology: contributions to air pollution and acidification in the Baltic Sea

    Directory of Open Access Journals (Sweden)

    B. Claremar

    2017-10-01

    Full Text Available The shipping sector is a significant contributor to emissions of air pollutants in marine and coastal regions. In order to achieve sustainable shipping, primarily through new regulations and techniques, greater knowledge of dispersion and deposition of air pollutants is required. Regional model calculations of the dispersion and concentration of sulfur, nitrogen, and particulate matter, as well as deposition of oxidized sulfur and nitrogen from the international maritime sector in the Baltic Sea and the North Sea, have been made for the years 2011 to 2013. The contribution from shipping is highest along shipping lanes and near large ports for concentration and dry deposition. Sulfur is the most important pollutant coupled to shipping. The contribution of both SO2 concentration and dry deposition of sulfur represented up to 80 % of the total in some regions. WHO guidelines for annual concentrations were not trespassed for any analysed pollutant, other than PM2.5 in the Netherlands, Belgium, and central Poland. However, due to the resolution of the numerical model, 50 km  ×  50 km, there may be higher concentrations locally close to intense shipping lanes. Wet deposition is more spread and less sensitive to model resolution. The contribution of wet deposition of sulfur and nitrogen from shipping was up to 30 % of the total wet deposition. Comparison of simulated to measured concentration at two coastal stations close to shipping lanes showed some underestimations and missed maximums, probably due to resolution of the model and underestimated ship emissions. A change in regulation for maximum sulfur content in maritime fuel, in 2015 from 1 to 0.1 %, decreases the atmospheric sulfur concentration and deposition significantly. However, due to costs related to refining, the cleaning of exhausts through scrubbers has become a possible economic solution. Open-loop scrubbers meet the air quality criteria but their consequences for

  17. Simulation of the influence of flue gas cleaning system on the energetic efficiency of a waste-to-energy plant

    Energy Technology Data Exchange (ETDEWEB)

    Grieco, E.; Poggio, A. [Politecnico di Torino, Corso Duca degli Abruzzi 24, Torino 10121 (Italy)

    2009-09-15

    Municipal solid waste incinerators are designed to enhance the electrical efficiency obtained by the plant as much as possible. For this reason strong integration between the flue gas cleaning system and the heat recovery system is required. To provide higher electrical efficiencies acid gas neutralization process has the major importance in flue gas cleaning system. At least four technologies are usually applied for acid gas removal: dry neutralization with Ca(OH){sub 2} or with NaHCO{sub 3}, semi-dry neutralization with milk of lime and wet scrubbing. Nowadays, wet scrubbers are rarely used as a result of the large amount of liquid effluents produced; wet scrubbing technology is often applied as a final treatment after a dry neutralization. Operating conditions of the plant were simulated by using Aspen Plus in order to investigate the influences of four different technologies on the electrical efficiency of the plant. The results of the simulations did not show a great influence of the gas cleaning system on the net electrical efficiency, as the difference between the most advantageous technology (neutralization with NaHCO{sub 3}) and the worst one, is about 1%. (author)

  18. Gasoline compression ignition approach to efficient, clean and affordable future engines

    KAUST Repository

    Kalghatgi, Gautam

    2017-04-03

    The worldwide demand for transport fuels will increase significantly but will still be met substantially (a share of around 90%) from petroleum-based fuels. This increase in demand will be significantly skewed towards commercial vehicles and hence towards diesel and jet fuels, leading to a probable surplus of lighter low-octane fuels. Current diesel engines are efficient but expensive and complicated because they try to reduce the nitrogen oxide and soot emissions simultaneously while using conventional diesel fuels which ignite very easily. Gasoline compression ignition engines can be run on gasoline-like fuels with a long ignition delay to make low-nitrogen-oxide low-soot combustion very much easier. Moreover, the research octane number of the optimum fuel for gasoline compression ignition engines is likely to be around 70 and hence the surplus low-octane components could be used without much further processing. Also, the final boiling point can be higher than those of current gasolines. The potential advantages of gasoline compression ignition engines are as follows. First, the engine is at least as efficient and clean as current diesel engines but is less complicated and hence could be cheaper (lower injection pressure and after-treatment focus on control of carbon monoxide and hydrocarbon emissions rather than on soot and nitrogen oxide emissions). Second, the optimum fuel requires less processing and hence would be easier to make in comparison with current gasoline or diesel fuel and will have a lower greenhouse-gas footprint. Third, it provides a path to mitigate the global demand imbalance between heavier fuels and lighter fuels that is otherwise projected and improve the sustainability of refineries. The concept has been well demonstrated in research engines but development work is needed to make it feasible on practical vehicles, e.g. on cold start, adequate control of exhaust carbon monoxide and hydrocarbons and control of noise at medium to high loads

  19. A resource allocation model to support efficient air quality ...

    African Journals Online (AJOL)

    Research into management interventions that create the required enabling environment for growth and development in South Africa are both timely and appropriate. In the research reported in this paper, the authors investigated the level of efficiency of the Air Quality Units within the three spheres of government viz.

  20. California Clean Air Act: A compliance strategy for the City of San Diego`s non-emergency fleet

    Energy Technology Data Exchange (ETDEWEB)

    1992-12-31

    Historically, parts of California have had the worst air quality in the nation. The California Energy Commission began experimenting with alternate fuels in the 1970`s in an effort to reduce harmful automobile emissions and hence, improve air quality. It is recognized that the costs to California which result from our air quality problems are immense. Ten to twenty billion dollars each year is the estimated damage in terms of health impacts, materials damages, lost agricultural crop output and forest damages. As the California population increases and health care costs escalate, the total monetary damages from air pollution will increase. The California Energy Commission goal to improve air quality became a mandate in 1988 with the passage of the California Clean Air Act (CCAA). The CCAA requires a revised air quality strategy for the San Diego district since we do not meet State air quality standards for smog, carbon monoxide and nitrogen dioxide. Smog remains San Diego`s major air quality problem, even though the annual number of days each year over the Federal standard has been reduced by 55 percent in the past ten years. Ten years ago about two-thirds of San Diego`s smog was transported from Los Angeles. Today more than 60 per cent of the days San Diego exceeds the State standard are from locally generated smog. It is estimated that 57% of the reactive hydrocarbon emissions (which react with nitrogen dioxide in the presence of sunlight to form smog) is from cars, trucks and buses. The Air Pollution Control District (part of the County of San Diego) is the office that the Air Resources Board has put in charge of creating regulations and designing strategy to reduce polluting emissions. The purpose of this project is to determine the full cost of acquiring and operating a municipal fleet which meets the mandates of the California Clean Air Act. With that information, a plan to meet the Clear Air Act (CCAA) requirements can be formulated by local government.

  1. 40 CFR 60.3064 - What must I do if I close my air curtain incinerator that burns only wood waste, clean lumber...

    Science.gov (United States)

    2010-07-01

    ... curtain incinerator that burns only wood waste, clean lumber, and yard waste and then restart it? 60.3064... Other Solid Waste Incineration Units That Commenced Construction On or Before December 9, 2004 Model Rule-Air Curtain Incinerators That Burn Only Wood Waste, Clean Lumber, and Yard Waste § 60.3064 What...

  2. 40 CFR 60.3067 - How must I monitor opacity for air curtain incinerators that burn only wood waste, clean lumber...

    Science.gov (United States)

    2010-07-01

    ... curtain incinerators that burn only wood waste, clean lumber, and yard waste? 60.3067 Section 60.3067... Incineration Units That Commenced Construction On or Before December 9, 2004 Model Rule-Air Curtain Incinerators That Burn Only Wood Waste, Clean Lumber, and Yard Waste § 60.3067 How must I monitor opacity for...

  3. 40 CFR 62.14820 - How must I monitor opacity for air curtain incinerators that burn 100 percent wood wastes, clean...

    Science.gov (United States)

    2010-07-01

    ... curtain incinerators that burn 100 percent wood wastes, clean lumber, and/or yard waste? 62.14820 Section... Requirements for Commercial and Industrial Solid Waste Incineration Units That Commenced Construction On or Before November 30, 1999 Air Curtain Incinerators That Burn 100 Percent Wood Wastes, Clean Lumber And/or...

  4. Air purification in industrial plants producing automotive rubber components in terms of energy efficiency

    Directory of Open Access Journals (Sweden)

    Grzebielec Andrzej

    2017-04-01

    Full Text Available In automotive industry plants, which use injection molding machines for rubber processing, tar contaminates air to such an extent that air fails to enter standard heat recovery systems. Accumulated tar clogs ventilation heat recovery exchangers in just a few days. In the plant in which the research was conducted, tar contamination causes blockage of ventilation ducts. The effect of this phenomenon was that every half year channels had to be replaced with new ones, since the economic analysis has shown that cleaning them is not cost-efficient. Air temperature inside such plants is often, even in winter, higher than 30°C. The air, without any means of heat recovery, is discharged outside the buildings. The analyzed plant uses three types of media for production: hot water, cold water at 14°C (produced in a water chiller, and compressed air, generated in a unit with a rated power consumption of 180 kW. The aim of the study is to determine the energy efficiency improvement of this type of manufacturing plant. The main problem to solve is to provide an air purification process so that air can be used in heat recovery devices. The next problem to solve is to recover heat at such a temperature level that it would be possible to produce cold for technological purposes without air purification. Experimental studies have shown that air purification is feasible. By using one microjet head, a total of 75% of tar particles was removed from the air; by using 4 heads, a purification efficiency of 93% was obtained. This method of air purification causes air temperature to decrease from 35°C to 20°C, which significantly reduces the potential for heat recovery. The next step of the research was designing a cassette-plate heat exchanger to exchange heat without air purification. The economic analysis of such a solution revealed that replacing the heat exchanger with a new one even once a year was not cost-efficient. Another issue examined in the context of

  5. Clean air. Measures against fine dust and nitrogen oxide; Luftreinhalteplanung. Massnahmen gegen Feinstaub und Stickstoffoxide

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2011-10-15

    Within the meeting of the Bavarian Environmental Protection Agency (Augsburg, Federal Republic of Germany) at 13th October, 2011, in Augsburg (Federal Republic of Germany), the following lectures were held: (1) Air pollution burden in Bavaria - Results from actual investigations (Juergen Diemer); (2) Winter spreading services: Reduction of particulate matter by means of CMA (Wolfgang Hafner); (3) Scenarios for the development of immission loads by NO{sub 2} at traffic-orientated air quality measuring stations in Bavaria (Frank Duennebeil); (4) Photocatalytic efficiency of titanium dioxide coatings in the reduction of the loading by nitrous oxides (Anja Baum); (5) Environmental zone Berlin (Martin Lutz); (6) Environmental zones in the Ruhr district (Cornelia Wappenschmidt); (7) Environmental zone Augsburg (Manfred Ertl); (8) Reduction of NO{sub x} by Euro 6 diesel passenger cars (Thomas Fortner); (9) (e)-Mobility leads to a new era. The next step in the evolution of the automobility (BMW Group); (10) Experience report on the FE project: 'Testing of diesel particle filters for the utilization in the inland navigation' (Torsen Mundt); (11) Reduction of the pollution burden by means of an ecological traffic control: Analysis and control of the pollution control by means of 'smart' IT solutions (Stefen Schaefer); (12) Emissions reductions at busses by means of SCRT upgrading (Detlef Plachta).

  6. Seeing Through Smoke: Sorting through the Science and Politics in the Making of the 1956 British Clean Air Act (Invited)

    Science.gov (United States)

    Kenny, D. A.

    2010-12-01

    The 1952 “Killer Smog” left over 4000 citizens of Greater London dead in a single week. It was a highly visible environmental disaster, which pinned the British government with responsibility over factory and domestic coal smoke pollution. Within four years of the Smog, the British parliament passed the 1956 Clean Air Act, which was designed primarily to prevent the release of dark smoke from the chimneys of private dwellings and factories. This act is considered a significant turning point in the history of environmental regulation. Through the analysis of confidential documents from government ministries and Members of Parliament, my research has focused on how decisions were made following this man-made environmental catastrophe. The primary focus of this presentation will be to explore why the British government appeared lethargic in the face of its long-standing coal pollution problem and why it finally passed the first clean air act in the world. In this case, establishing responsibility and organizing research were the major time constraints on policy action. In the months following the 1952 Smog, government departments passed off responsibility and quarreled over jurisdiction in the smog matter. Ministries held responsible for air pollution jointly established the Committee on Air Pollution to find a solution to urban smog. In the years following, the Committee on Air Pollution compiled research on the health effects and economic impact of air pollution, deriving its information from a variety of sources. In its 1954 final report, the committee named smoke and sulfur dioxide the most likely culprits of the 1952 deaths, and it recommended the elimination of smoke-producing coal from the British market, a major change to how the British fueled their homes and factories. The resulting 1956 Clean Air Act was the product of numerous compromises over the economic, political, and social issues present in Great Britain at the time. The British government

  7. Effect of air flow on tubular solar still efficiency.

    Science.gov (United States)

    Thirugnanasambantham, Arunkumar; Rajan, Jayaprakash; Ahsan, Amimul; Kandasamy, Vinothkumar

    2013-01-01

    An experimental work was reported to estimate the increase in distillate yield for a compound parabolic concentrator-concentric tubular solar still (CPC-CTSS). The CPC dramatically increases the heating of the saline water. A novel idea was proposed to study the characteristic features of CPC for desalination to produce a large quantity of distillate yield. A rectangular basin of dimension 2 m × 0.025 m × 0.02 m was fabricated of copper and was placed at the focus of the CPC. This basin is covered by two cylindrical glass tubes of length 2 m with two different diameters of 0.02 m and 0.03 m. The experimental study was operated with two modes: without and with air flow between inner and outer tubes. The rate of air flow was fixed throughout the experiment at 4.5 m/s. On the basis of performance results, the water collection rate was 1445 ml/day without air flow and 2020 ml/day with air flow and the efficiencies were 16.2% and 18.9%, respectively. THE EXPERIMENTAL STUDY WAS OPERATED WITH TWO MODES: without and with air flow between inner and outer tubes. The rate of air flow was fixed throughout the experiment at 4.5 m/s. On the basis of performance results, the water collection rate was 1445 ml/day without air flow and 2020 ml/day with air flow and the efficiencies were 16.2% and 18.9%, respectively.

  8. Early Warning Report: Use of Contractors to Conduct Clean Air Act Risk Management Program Inspections in Certain States Goes Against Court Decisions

    Science.gov (United States)

    Report #12-P-0376, March 28, 2012. The OIG is currently evaluating whether the EPA has adequate management controls for ensuring the effectiveness of its Clean Air Act (CAA) Section 112(r) risk management program inspections.

  9. Potential Impact of Clean Air Act Regulations on Nitrogen Fate and Transport in the Neuse River Basin: a Modeling Investigation Using CMAQ and SWAT

    Science.gov (United States)

    There has been extensive analysis of Clean Air Act Amendment (CAAA) regulation impacts to changes in atmospheric nitrogen deposition; however, few studies have focused on watershed nitrogen transfer particularly regarding long-term predictions. In this study, we investigated impa...

  10. Fluid drag reduction and efficient self-cleaning with rice leaf and butterfly wing bioinspired surfaces

    Science.gov (United States)

    Bixler, Gregory D.; Bhushan, Bharat

    2013-08-01

    Researchers are continually inspired by living nature to solve complex challenges. For example, unique surface characteristics of rice leaves and butterfly wings combine the shark skin (anisotropic flow leading to low drag) and lotus leaf (superhydrophobic and self-cleaning) effects, producing the so-called rice and butterfly wing effect. In this paper, we present an overview of rice leaf and butterfly wing fluid drag and self-cleaning studies. In addition, we examine two other promising aquatic surfaces in nature known for such properties, including fish scales and shark skin. Morphology, drag, self-cleaning, contact angle, and contact angle hysteresis data are presented to understand the role of wettability, viscosity, and velocity. Liquid repellent coatings are utilized to recreate or combine various effects. Discussion is provided along with conceptual models describing the role of surface structures related to low drag, self-cleaning, and antifouling properties. Modeling provides design guidance when developing novel low drag and self-cleaning surfaces for applications in the medical, marine, and industrial fields.

  11. Negative pressure of the environmental air in the cleaning area of the materials and sterilization center: a systematic review

    Directory of Open Access Journals (Sweden)

    Caroline Lopes Ciofi-Silva

    Full Text Available ABSTRACT Objective: to analyze the scientific evidence on aerosols generated during cleaning activities of health products in the Central Service Department (CSD and the impact of the negative pressure of the ambient air in the cleaning area to control the dispersion of aerosols to adjacent areas. Method: for this literature systematic review the following searches were done: search guidelines, manuals or national and international technical standards given by experts; search in the portal and databases PubMed, Scopus, CINAHL and Web of Science; and a manual search of scientific articles. Results: the five technical documents reviewed recommend that the CSD cleaning area should have a negative differential ambient air pressure, but scientific articles on the impact of this intervention were not found. The four articles included talked about aerosols formed after the use of a ultrasonic cleaner (an increased in the contamination especially during use and pressurized water jet (formation of smaller aerosols 5μm. In a study, the aerosols formed from contaminated the hot tap water with Legionella pneumophila were evaluated. Conclusions: there is evidence of aerosol formation during cleanup activities in CSD. Studies on occupational diseases of respiratory origin of workers who work in CSD should be performed.

  12. Summary of efficiency testing of standard and high-capacity high-efficiency particulate air filters subjected to simulated tornado depressurization and explosive shock waves

    International Nuclear Information System (INIS)

    Smith, P.R.; Gregory, W.S.

    1985-04-01

    Pressure transients in nuclear facility air cleaning systems can originate from natural phenomena such as tornadoes or from accident-induced explosive blast waves. This study was concerned with the effective efficiency of high-efficiency particulate air (HEPA) filters during pressure surges resulting from simulated tornado and explosion transients. The primary objective of the study was to examine filter efficiencies at pressure levels below the point of structural failure. Both standard and high-capacity 0.61-m by 0.61-m HEPA filters were evaluated, as were several 0.2-m by 0.2-m HEPA filters. For a particular manufacturer, the material release when subjected to tornado transients is the same (per unit area) for both the 0.2-m by 0.2-m and the 0.61-m by 0.61-m filters. For tornado transients, the material release was on the order of micrograms per square meter. When subjecting clean HEPA filters to simulated tornado transients with aerosol entrained in the pressure pulse, all filters tested showed a degradation of filter efficiency. For explosive transients, the material release from preloaded high-capacity filters was as much as 340 g. When preloaded high-capacity filters were subjected to shock waves approximately 50% of the structural limit level, 1 to 2 mg of particulate was released

  13. Efficient air pollution abatement for regions in China

    Energy Technology Data Exchange (ETDEWEB)

    Hu, J.L. [National Chiao Tung University, Taipei (Taiwan). Inst. for Business & Management

    2006-08-15

    This paper computes the efficient air pollution abatement ratios of 30 regions in China during the period 1996-2002. Three air emissions (SO{sub 2}, soot and dust) are considered. Data envelopment analysis (DEA) with a single output (real GDP) and five inputs (labour, real capital stock, SO{sub 2}, dust and soot emissions) is used to compute the target emissions of each region for each year. The efficient abatement ratios of each region in each year are then obtained by dividing the target emission by the actual emission of an air pollutant. Our major findings are: 1. The eastern area is the most efficient region with respect to SO{sub 2}, soot and dust emissions in every year during the research period. 2. The eastern, central and western areas have the lowest, medium and highest 1996-2002 average target abatement ratios of SO, (22.09%, 42.23% and 57.58%), soot (26.19%, 56.34% and 66.37%) and dust (15.20%, 29.09% and 40.59%), respectively. 3. These results are consistent with the Environmental Kuznets Curve (EKC) theory, whereby a more developed area will use environmental goods more efficiently than a less developed area. 4. Compared to dust emission, the average target abatement ratios for SO{sub 2} and soot emissions (as direct outcomes of burning coal) are relatively much higher for all three areas.

  14. DESIGNING AND EFFICIENCY EFFECT OF AUTOMATIC BALL-CLEANING SYSTEM FOR CONDENSER 180-KTsS-1 OF TURBINE Т-180/210-130-1 LMZ. Part 2

    Directory of Open Access Journals (Sweden)

    Yu. A. Zenovich-Leshkevich-Ol’pinskiy

    2015-01-01

    Full Text Available The authors elaborate the economical efficiency evaluation technique that could be universal and applied for technical-and-economic feasibility study of the ball-cleaning system installation on the steam turbines of the electric power plants. Besides the effect from reducing the exhaust steam pressure in the condenser by means of the ball-cleaning system implementation, this technique also accounts for the effect of lowering the condenser hydraulic pressure.The article refers to the practical results of the ball-cleaning system introduction on the steam turbines of Gomel CHP-2. As a result of regular application of the ball-cleaning system the temperature difference of the condensers of all blocks Т-180/210-130-1 confined into the regulatory values and the cleanness coefficient of all three turbine units reached 0,85. The authors consider the working results, implementation experience of the ball-cleaning system at Gomel CHP-2 and its efficiency evaluation technique to be worth disseminating when introducing the analogous systems at the plants of Belarusian power network.The authors suggest measures on the condenser automatic-cleaning system improvement with the turbine mathematical-simulation model employment that will make it possible to optimize the condenser cleaning regimes and to increase the ball-cleaning system effectiveness with the condenser cleanness coefficient growing up to 0,90–0,92.

  15. An efficient marker-free vector for clean gene transfer into plants ...

    African Journals Online (AJOL)

    A marker-free vector, pBINMF, for clean gene transfer was constructed based on the binary vector pBINPLUS. Vector pBINMF, carrying only a multiple cloning site (MCS) between the left and the right T-DNA border, was suitable to directly generate marker-free transgenic plants (MFTPs) without any vector sequences ...

  16. Fighting ambient air pollution and its impact on health: from human rights to the right to a clean environment.

    Science.gov (United States)

    Guillerm, N; Cesari, G

    2015-08-01

    Clean air is one of the basic requirements of human health and well-being. However, almost nine out of 10 individuals living in urban areas are affected by air pollution. Populations living in Africa, South-East Asia, and in low- and middle-income countries across all regions are the most exposed. Exposure to outdoor air pollution ranks as the ninth leading risk factor for mortality, killing 3.2 million people each year, especially young children, the elderly, persons with lung or cardiovascular disease, those who work or exercise outdoors and low-income populations. In October 2013, the International Agency for Research on Cancer (IARC) classified outdoor air pollution as carcinogenic to humans, calling air pollution 'a major environmental health problem'. Human rights and environmental norms are powerful tools to combat air pollution and its impact on health. The dependence of human rights on environmental quality has been recognised in international texts and by human rights treaty bodies. The growing awareness of the environment has already yielded considerable legislative and regulatory output. However, the implementation of standards remains a pervasive problem. In the fight against violations of norms, citizens have a crucial role to play. We discuss the relevance of a yet to be proclaimed standalone right to a healthy environment.

  17. Indoor secondary pollutants from cleaning product and air freshener use in the presence of ozone

    DEFF Research Database (Denmark)

    Singer, B.C.; Coleman, B.K.; Destaillats, H.

    2006-01-01

    introduction. In the absence of reactive chemicals, the chamber ozone level was approximately 60 ppb. Ozone was substantially consumed following cleaning product use, mainly by homogeneous reaction. For the AFR, ozone consumption was weaker and heterogeneous reaction with sorbed AFR-constituent VOCs...... than 100 mu g m(-3)) in some experiments. Ozone consumption and elevated hydroxyl radical concentrations persisted for 10-12 h following brief cleaning events, indicating that secondary pollutant production can persist for extended periods. (c) 2006 Elsevier Ltd. All rights reserved....

  18. Tobacco control policies are egalitarian: a vulnerabilities perspective on clean indoor air laws, cigarette prices, and tobacco use disparities.

    Science.gov (United States)

    Dinno, Alexis; Glantz, Stanton

    2009-04-01

    This study models independent associations of state or local strong clean indoor air laws and cigarette prices with current smoker status and consumption in a multilevel framework, including interactions with educational attainment, household income and race/ethnicity and the relationships of these policies to vulnerabilities in smoking behavior. Cross sectional survey data are employed from the February 2002 panel of the Tobacco Use Supplement of the Current Population Survey (54,024 individuals representing the US population aged 15-80). Non-linear relationships between both outcome variables and the predictors were modeled. Independent associations of strong clean indoor air laws were found for current smoker status (OR 0.66), and consumption among current smokers (-2.36 cigarettes/day). Cigarette price was found to have independent associations with both outcomes, an effect that saturated at higher prices. The odds ratio for smoking for the highest versus lowest price over the range where there was a price effect was 0.83. Average consumption declined (-1.16 cigarettes/day) over the range of effect of price on consumption. Neither policy varied in its effect by educational attainment, or household income. The association of cigarette price with reduced smoking participation and consumption was not found to vary with race/ethnicity. Population vulnerability in consumption appears to be structured by non-white race categories, but not at the state and county levels at which the policies we studied were enacted. Clean indoor air laws and price increases appear to benefit all socio-economic and race/ethnic groups in our study equally in terms of reducing smoking participation and consumption.

  19. Clean Air Act Standards and Guidelines for Energy, Engines, and Combustion

    Science.gov (United States)

    This page contains the stationary sources of air pollution for the energy, engines, and combustion industries, and their corresponding air pollution regulations. To learn more about the regulations for each industry, just click on the links below.

  20. Clean Air Act Standards and Guidelines for Chemical Production and Distribution

    Science.gov (United States)

    This page contains the stationary sources of air pollution for the chemical production & distribution industries, and their corresponding air pollution regulations. To learn more about the regulations for each industry, click on the links below.

  1. Clean Air Act Guidelines and Standards for Solvent Use and Surface Coating Industry

    Science.gov (United States)

    This page contains the stationary sources of air pollution for the solvent use and surface coating industries, and their corresponding air pollution regulations. To learn more about the regulations for each industry, just click on the links below.

  2. Clean Air Act Standards and Guidelines for Agriculture, Food and Forestry

    Science.gov (United States)

    This page contains the stationary sources of air pollution for the agriculture, food, and forestry industries, and their corresponding air pollution regulations. To learn more about the regulations for each industry, just click on the links below.

  3. Preliminary calculations for the CAFE project (Clean Air For Europe); Calculs preparatoires pour la strategie thematique CAFE (Clean Air For Europe)

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2005-09-15

    The European Commission decided in 2001 an analysis program to reduce the atmospheric emissions. This report presents different limit scenari for France in 2020 (the reference scenari and the MTFR scenari, Maximum Technically Feasible Reduction), optimized scenari calculated by the RAINS model (Regional Air Pollution Information and Simulation), the costs of the scenari calculated with RAINS and the cost-benefit analysis of the strategy CAFE. From the study results, the benefits are higher than the costs, even with the most ambitious scenari. At an european level the emission reduction strategies have no effect on the employment but an impact on the Gross Domestic Product (decrease between 0,04 % and 0,12 % in function of the scenari). (A.L.B.)

  4. Engineered-safety-feature air-cleaning systems for commercial light-water-cooled nuclear power plants

    International Nuclear Information System (INIS)

    Burchsted, C.A.

    1975-01-01

    Substantial improvement has been observed in the design and construction of ESF air cleaning systems in some of the newer power plants, as compared to earlier practice, but there is still much to be done. Adequate space must be provided for these facilities in the earliest containment and building layout, and system designers, equipment designers, and building layout engineers must give adequate consideration to easy access to facilitate maintenance and testing. Finally, constructors and utilities must provide for proper storage of critical components such as HEPA filters and adsorber cells during construction and during the period awaiting startup of the plant. (U.S.)

  5. Development of High Efficiency Clean Combustion Engine Designs for Spark-Ignition and Compression-Ignition Internal Combustion Engines

    Energy Technology Data Exchange (ETDEWEB)

    Marriott, Craig; Gonzalez, Manual; Russell, Durrett

    2011-06-30

    This report summarizes activities related to the revised STATEMENT OF PROJECT OBJECTIVES (SOPO) dated June 2010 for the Development of High-Efficiency Clean Combustion engine Designs for Spark-Ignition and Compression-Ignition Internal Combustion Engines (COOPERATIVE AGREEMENT NUMBER DE-FC26-05NT42415) project. In both the spark- (SI) and compression-ignition (CI) development activities covered in this program, the goal was to develop potential production-viable internal combustion engine system technologies that both reduce fuel consumption and simultaneously met exhaust emission targets. To be production-viable, engine technologies were also evaluated to determine if they would meet customer expectations of refinement in terms of noise, vibration, performance, driveability, etc. in addition to having an attractive business case and value. Prior to this activity, only proprietary theoretical / laboratory knowledge existed on the combustion technologies explored The research reported here expands and develops this knowledge to determine series-production viability. Significant SI and CI engine development occurred during this program within General Motors, LLC over more than five years. In the SI program, several engines were designed and developed that used both a relatively simple multi-lift valve train system and a Fully Flexible Valve Actuation (FFVA) system to enable a Homogeneous Charge Compression Ignition (HCCI) combustion process. Many technical challenges, which were unknown at the start of this program, were identified and systematically resolved through analysis, test and development. This report documents the challenges and solutions for each SOPO deliverable. As a result of the project activities, the production viability of the developed clean combustion technologies has been determined. At this time, HCCI combustion for SI engines is not considered production-viable for several reasons. HCCI combustion is excessively sensitive to control variables

  6. Fuel flexible distributed combustion for efficient and clean gas turbine engines

    International Nuclear Information System (INIS)

    Khalil, Ahmed E.E.; Gupta, Ashwani K.

    2013-01-01

    Highlights: • Examined distributed combustion for gas turbines applications using HiTAC. • Gaseous, liquid, conventional and bio-fuels are examined with ultra-low emissions. • Novel design of fuel flexibility without any atomizer for liquid fuel sprays. • Demonstrated fuel flexibility with emissions x and CO, low noise, enhanced stability, higher efficiency and alleviation of combustion instability. Distributed reaction conditions were achieved using swirl for desirable controlled mixing between the injected air, fuel and hot reactive gases from within the combustor prior to mixture ignition. In this paper, distributed combustion is further investigated using a variety of fuels. Gaseous (methane, diluted methane, hydrogen enriched methane and propane) and liquid fuels, including both traditional (kerosene) and alternate fuels (ethanol) that cover a wide range of calorific values are investigated with emphasis on pollutants emission and combustor performance with each fuel. For liquid fuels, no atomization or spray device was used. Performance evaluation with the different fuels was established to outline the flexibility of the combustor using a wide range of fuels of different composition, phase and calorific value with specific focus on ultra-low pollutants emission. Results obtained on pollutants emission and OH * chemiluminescence for the specific fuels at various equivalence ratios are presented. Near distributed combustion conditions with less than 8 PPM of NO emission were demonstrated under novel premixed conditions for the various fuels tested at heat (energy) release intensity (HRI) of 27 MW/m 3 -atm. and a rather high equivalence ratio of 0.6. Higher equivalence ratios lacked favorable distributed combustion conditions. For the same conditions, CO emission varied for each fuel; less than 10 ppm were demonstrated for methane based fuels, while heavier liquid fuels provided less than 40 ppm CO emissions. Lower emissions of NO ( x can be possible by

  7. An Investigation on the Efficiency of Air Purification Using a Biofilter with Activated Bed of Different Origin

    Directory of Open Access Journals (Sweden)

    Zagorskis Alvydas

    2014-12-01

    Full Text Available Recent studies in the area of biological air treatment in filters have addressed fundamental key issues, such as a biofilter bed of different origin composed of natural zeolite granules, foam cubes and wood chips. When foam and zeolite are mixed with wood chips to remove volatile organic compounds from the air, not only biological but also adsorption air purification methods are accomplished. The use of complex purification technologies helps to improve the efficiency of a filter as well as the bed service life of the filter bed. Investigations revealed that microorganisms prevailing in biological purification, can also reproduce themselves in biofilter beds of inorganic and synthetic origin composed of natural zeolite and foam. By cultivating associations of spontaneous microorganisms in the filter bed the dependencies of the purification efficiency of filter on the origin, concentration and filtration time of injected pollutants were determined. The highest purification efficiency was obtained when air polluted with acetone vapour was supplied to the equipment at 0.1 m/s of superficial gas velocity. When cleaning air from volatile organic compounds (acetone, toluene and butanol, under the initial pollutant concentration of ~100 mg/m3, the filter efficiency reached 95 %.

  8. Substrate Effect on Plasma Clean Efficiency in Plasma Enhanced Chemical Vapor Deposition System

    Directory of Open Access Journals (Sweden)

    Shiu-Ko JangJian

    2007-01-01

    Full Text Available The plasma clean in a plasma-enhanced chemical vapor deposition (PECVD system plays an important role to ensure the same chamber condition after numerous film depositions. The periodic and applicable plasma clean in deposition chamber also increases wafer yield due to less defect produced during the deposition process. In this study, the plasma clean rate (PCR of silicon oxide is investigated after the silicon nitride deposited on Cu and silicon oxide substrates by remote plasma system (RPS, respectively. The experimental results show that the PCR drastically decreases with Cu substrate compared to that with silicon oxide substrate after numerous silicon nitride depositions. To understand the substrate effect on PCR, the surface element analysis and bonding configuration are executed by X-ray photoelectron spectroscopy (XPS. The high resolution inductively coupled plasma mass spectrometer (HR-ICP-MS is used to analyze microelement of metal ions on the surface of shower head in the PECVD chamber. According to Cu substrate, the results show that micro Cu ion and the CuOx bonding can be detected on the surface of shower head. The Cu ion contamination might grab the fluorine radicals produced by NF3 ddissociation in the RPS and that induces the drastic decrease on PCR.

  9. "Clean, green and ethical" animal production. Case study: reproductive efficiency in small ruminants.

    Science.gov (United States)

    Martin, Graeme B; Kadokawa, Hiroya

    2006-02-01

    In response to changes in society and thus the marketplace, we need a vision for the future of our animal industries, including both on-farm and off-farm activities, that is "clean, green and ethical". Using small ruminants as a case study, we describe three "clean, green and ethical" strategies that farmers could use to improve reproductive performance. The first allows control of the timing of reproductive events by using socio-sexual signals (the "male effect") to induce synchronised ovulation in females. The second strategy, "focus feeding", is based on using short periods of nutritional supplements that are precisely timed and specifically designed for each event in the reproductive process (eg, gamete production, embryo survival, fetal programming, colostrum production). The third strategy aims to maximize offspring survival by a combination of management, nutrition and genetic selection for behaviour (temperament). All of these approaches involve non-pharmacological manipulation of the endogenous control systems of the animals and complement the detailed information from ultrasound that is now becoming available. Importantly, these approaches all have a solid foundation in reproductive biology. In several cases, they are currently used in commercial practice, but there is still room for improvement through both basic and applied research. Ultimately, these "clean, green and ethical" tools can be cost-effective, increase productivity and, at the same time, greatly improve the image of meat and milk industries in society and the marketplace.

  10. The Solubility of Ozone in Deionized Water and its Cleaning Efficiency

    Energy Technology Data Exchange (ETDEWEB)

    Han, J.H.; Park, J.G. [Hanyang University, Seoul (Korea, Republic of); Kwak, Y.S. [Hanyang Technology Co., Ltd., Ansan (Korea, Republic of)

    1998-06-01

    The purpose of this study was to investigate the behavior of ozone in DI water and the reaction with wafers during the semiconductor wet cleaning process. The solubility of ozone in DI water was not only dependent on the temperature but also directly proportional to the input concentration of ozone. The lower the initial ozone concentration and the temperature, the longer the half-life time of ozone. The reaction order of ozone in DI water was calculated to be around 1.5. The redox potential reached a saturation value in 5min and slightly increased as the input ozone concentrations increased. The completely hydrophilic surface was created in 1min when HF etched silicon wafer was cleaned in ozonized DI water containing higher ozone concentrations than 2ppm. Spectroscopic ellipsometry measurements showed that the chemical oxide formed by ozonized DI water was measured to be thicker than that by piranha solution. The wafers contaminated with a non-ionic surfactant were more effectively cleaned in ozonized DI water than in piranha and ozonized piranha solutions. (author). 19 refs., 11 figs., 1 tab.

  11. Magnetic Refrigeration Technology for High Efficiency Air Conditioning

    Energy Technology Data Exchange (ETDEWEB)

    Boeder, A; Zimm, C

    2006-09-30

    Magnetic refrigeration was investigated as an efficient, environmentally friendly, flexible alternative to conventional residential vapor compression central air conditioning systems. Finite element analysis (FEA) models of advanced geometry active magnetic regenerator (AMR) beds were developed to minimize bed size and thus magnet mass by optimizing geometry for fluid flow and heat transfer and other losses. Conventional and magnetocaloric material (MCM) regenerator fabrication and assembly techniques were developed and advanced geometry passive regenerators were built and tested. A subscale engineering prototype (SEP) magnetic air conditioner was designed, constructed and tested. A model of the AMR cycle, combined with knowledge from passive regenerator experiments and FEA results, was used to design the regenerator beds. A 1.5 Tesla permanent magnet assembly was designed using FEA and the bed structure and plenum design was extensively optimized using FEA. The SEP is a flexible magnetic refrigeration platform, with individually instrumented beds and high flow rate and high frequency capability, although the current advanced regenerator geometry beds do not meet performance expectations, probably due to manufacturing and assembly tolerances. A model of the AMR cycle was used to optimize the design of a 3 ton capacity magnetic air conditioner, and the system design was iterated to minimize external parasitic losses such as heat exchanger pressure drop and fan power. The manufacturing cost for the entire air conditioning system was estimated, and while the estimated SEER efficiency is high, the magnetic air conditioning system is not cost competitive as currently configured. The 3 ton study results indicate that there are other applications where magnetic refrigeration is anticipated to have cost advantages over conventional systems, especially applications where magnetic refrigeration, through the use of its aqueous heat transfer fluid, could eliminate intermediate

  12. Electrical efficiency losses occurred by the air compressor for PEMFC

    International Nuclear Information System (INIS)

    Haubrock, J.; Heideck, G.; Styczynski, Z.

    2006-01-01

    Fuel Cells are characterised by a high efficiency and comparatively small emissions. Depending on their partial load behaviour and their high efficiency, Fuel Cells are well suited for net connected or isolated autonomous energy generators for thermal and electricity power production. Proton Exchange Membrane (PEM) Fuel Cell systems need several external components to produce electricity and thermal power. However, the high theoretical degree of efficiency of 83% is decreased by these components. To reach higher fuel utilisation it is necessary to reduce the energy consumption of these components. In this study, the influence of the air supply compressor on the fuel utilisation is investigated and an optimization strategy was developed. The results were reviewed by a real test set up using an autonomous PEM Fuel Cell system. (authors)

  13. The Sequential Probability Ratio Test: An efficient alternative to exact binomial testing for Clean Water Act 303(d) evaluation.

    Science.gov (United States)

    Chen, Connie; Gribble, Matthew O; Bartroff, Jay; Bay, Steven M; Goldstein, Larry

    2017-05-01

    The United States's Clean Water Act stipulates in section 303(d) that states must identify impaired water bodies for which total maximum daily loads (TMDLs) of pollution inputs into water bodies are developed. Decision-making procedures about how to list, or delist, water bodies as impaired, or not, per Clean Water Act 303(d) differ across states. In states such as California, whether or not a particular monitoring sample suggests that water quality is impaired can be regarded as a binary outcome variable, and California's current regulatory framework invokes a version of the exact binomial test to consolidate evidence across samples and assess whether the overall water body complies with the Clean Water Act. Here, we contrast the performance of California's exact binomial test with one potential alternative, the Sequential Probability Ratio Test (SPRT). The SPRT uses a sequential testing framework, testing samples as they become available and evaluating evidence as it emerges, rather than measuring all the samples and calculating a test statistic at the end of the data collection process. Through simulations and theoretical derivations, we demonstrate that the SPRT on average requires fewer samples to be measured to have comparable Type I and Type II error rates as the current fixed-sample binomial test. Policymakers might consider efficient alternatives such as SPRT to current procedure. Copyright © 2017 Elsevier Ltd. All rights reserved.

  14. Seismic simulation and functional performance evaluation of a safety related, seismic category I control room emergency air cleaning system

    International Nuclear Information System (INIS)

    Manley, D.K.; Porco, R.D.; Choi, S.H.

    1985-01-01

    Under a nuclear contract MSA was required to design, manufacture, seismically test and functionally test a complete Safety Related, Seismic Category I, Control Room Emergency Air Cleaning System before shipment to the Yankee Atomic Electric Company, Yankee Nuclear Station in Rowe, Massachusetts. The installation of this system was required to satisfy the NRC requirements of NUREG-0737, Section III, D.3.4, ''Control Room Habitability''. The filter system tested was approximately 3 ft. wide by 8 ft. high by 18 ft. long and weighed an estimated 8300 pounds. It had a design flow rate of 3000 SCFM and contained four stages of filtration - prefilters, upstream and downstream HEPA filters and Type II sideload charcoal adsorber cells. The filter train design followed the guidelines set forth by ANSI/ASME N509-1980. Seismic Category I Qualification Testing consisted of resonance search testing and triaxial random multifrequency testing. In addition to ANSI/ASME N510-1980 testing, triaxial response accelerometers were placed at specific locations on designated prefilters, HEPA filters, charcoal adsorbers and test canisters along with accelerometers at the corresponding filter seal face locations. The purpose of this test was to demonstrate the integrity of the filters, filter seals, and monitor seismic response levels which is directly related to the system's ability to function during a seismic occurrence. The Control Room Emergency Air Cleaning System demonstrated the ability to withstand the maximum postulated earthquake for the plant site by remaining structurally sound and functional

  15. Mobile ultra-clean unidirectional airflow screen reduces air contamination in a simulated setting for intra-vitreal injection.

    Science.gov (United States)

    Lapid-Gortzak, Ruth; Traversari, Roberto; van der Linden, Jan Willem; Lesnik Oberstein, Sarit Y; Lapid, Oren; Schlingemann, Reinier O

    2017-02-01

    The aim of this study is to determine whether the use of a mobile ultra-clean laminar airflow screen reduces the air-borne particle counts in the setting of a simulated procedure of an intra-vitreal injection. A mobile ultra-clean unidirectional airflow (UDF) screen was tested in a simulated procedure for intra-vitreal injections in a treatment room without mechanical ventilation. One UDF was passed over the instrument tray and the surgical area. The concentration of particles was measured in the background, over the instrument table, and next to the ocular area. The degree of protection was calculated at the instrument table and at the surgical site. Use of the UDF mobile screen reduced the mean particle concentration (particles > 0.3 microns) on the instrument table by a factor of at least 100.000 (p air contamination. Mobile UDF screen reduces the mean particle concentration substantially. The mobile UDF screen may therefore allow for a safer procedural environment for ambulatory care procedures such as intra-vitreal injections in treatment rooms.

  16. Researches in increase of efficiency of electrokinetic process of ground cleaning from radionuclides

    International Nuclear Information System (INIS)

    Prozorov, L.B.; Shcheglov, M.Y.; Nikolaevsky, V.B.; Tkachenko, A.V.

    2003-01-01

    Potentially perspective method of decontamination of ground is electrokinetic method, which basic advantage consists in an opportunity of its application for clearing ground with low filtering by ability directly on a place of local contaminated (in situ). Thus moving the large volumes of the contaminated ground is excluded. Base of this method is the processes of electromigration and electro-osmotic, proceeding in a contaminated ground lay at imposing an electrical field of a constant current. Electrokinetic method of cleaning of ground from radionuclides provides their transfer in water-soluble, mobile form, carry as positive or negative ions under influence of an electrical field into electrode chambers with their subsequent recycling.Electrokinetic method in practice can be realized as follows: in the contaminated ground establish special electrode devices, fill their electrolyte and connect to a source of a constant current. Formed in the anode device as a result of electrochemical decomposition of water the ions of hydrogen under action of an electrical field move to the cathode, thus cooperate with a ground and superside cations of radioactive elements. Desorbed cations of contaminate act in catholyte, which periodically or continuously is exposed to clearing, for example, on sorption column. Last years the experts MosNPO Radon carry out complex researches directed on development of electrokinetic technology of cleaning ground from radionuclides and heavy metals. To the present time laboratory and bench tests of electrokinetic method are carried out. The basic attention at study of process of cleaning was given to objects contaminated Cs-137, most difficult recovery an element, which is strongly fixed by clay minerals and can enter into crystal structure. (authors)

  17. Device for filling up air cleaning cells with adsorbent coal and its loading process

    International Nuclear Information System (INIS)

    Parish, H.C.; Allard, M.D.; Petit, J.L.; Sfulgis, I.S.

    1976-01-01

    This invention concerns improved appliances enabling granules to be compressed, evenly on the whole, in a hopper, filter or any other component to be filled with such granules. This criterion is particularly important in the case of air filters using granulated adsorbing coal for separating the radioactive substances in the air should an ccident occur in a nuclear power station [fr

  18. Development of an air knife to remove seed coat fragments during lint cleaning

    Science.gov (United States)

    An air knife is a tool commonly used to blow off debris in a manufacturing line. The knife may also be used to break the attachment force between a lint cleaner saw and a seed coat fragment (SCF) with attached fiber, and remove them. Work continued on evaluating an auxiliary air knife mounted on t...

  19. 75 FR 80809 - Proposed Consent Decree, Clean Air Act Citizen Suit

    Science.gov (United States)

    2010-12-23

    ... Department of Air Quality to the Tennessee Valley Authority's Paradise Fossil Plant in Drakesboro, Kentucky... permit issued by the Kentucky Department of Air Quality to the Tennessee Valley Authority's Paradise...'s policy is that public comments, whether submitted electronically or in paper, will be made...

  20. 78 FR 16630 - Clean Air Act Grant: South Coast Air Quality Management District; Opportunity for Pubic Hearing

    Science.gov (United States)

    2013-03-18

    ... disproportionately impacted or singled out for a reduction. A section 105 recipient must submit a final financial.... The recipient must provide evidence that the air program is not being singled out for a reduction or...

  1. Highly concentrated EDTA gel improves cleaning efficiency of root canal preparation in vitro.

    Science.gov (United States)

    Putzer, P; Hoy, L; Günay, H

    2008-12-01

    Debris and smear layer, as a product of mechanical root canal instrumentation, reduce the effectiveness of pharmacological substances to prevent post-treatment diseases and impair direct contact of filling materials with a clean dentinal surface. The aim of this in vitro study was to investigate the presence and localization of debris and smear layer via scanning electron microscope analysis after standardized root canal preparation with different chelating agents. Dentin surfaces received treatment with: (1) 15% ethylenediaminetetraacetic acid (EDTA), (2) 18.6% EDTA (3) and 24% EDTA or without any demineralizing chemicals as control. Forty vertically split human premolars were sputtered and divided into coronal, middle, and apical sections, followed by a randomized, blinded score evaluation using five scores. Pairwise comparisons of all treatment groups against a control group have been performed by Mann-Whitney U test and the Kruskal-Wallis test. Debris grades showed no significant difference between the three regions of the root canals, except for 18.6% EDTA in the central third. Smear layer and smear plug removal was concentration-dependent. Removal of the smear layer in the three areas showed that there was a statistically significant difference between all parts when using 18.6% and 24% EDTA concentrations compared with the control. The best smear layer removal in the apical region was observed using a 24% EDTA gel as chelating agent and lubricant. The usage of EDTA gel >/=18.6% presented a better cleaning regime when compared to the control group.

  2. Design of ventilation and air cleaning systems for the new Los Alamos Plutonium Facility

    International Nuclear Information System (INIS)

    Mitchell, R.; DeField, J.; Stafford, R.; McNeese, W.; Eberhardt, W.; Laushkin, N.

    1975-01-01

    The Los Alamos Scientific Laboratory's new plutonium facility will conform to AECM Appendix 6301-Part II, Section H-Minimum Design Criteria for New Plutonium Facilities. The glove box process exhaust air is filtered through three or four stages of HEPA filters. The design of this multi-stage filter installation is shown with a method of in-place testing of each stage individually. A glove box filter holder and the in-place test procedure is described. General room air from plutonium work areas is recirculated at the rate of eight air changes per hour with a 10 percent fresh air make-up. The filter plenums for the recirculated air are designed to permit in-place testing of each of the two filter stages. (U.S.)

  3. Indoor air quality in energy efficient buildings. A literature review

    Energy Technology Data Exchange (ETDEWEB)

    Thomsen, Judith; Berge, Magnar

    2012-07-01

    There is currently a major focus on measures to reduce global warming. Several international studies show that the energy efficiency of buildings is the easiest and most cost-effective climate action. Passive houses are characterized of that the buildings are more airtight, have more insulation and has balanced mechanical ventilation with heat recovery. This report discusses about this one-sided focus on energy conservation, and if {sup c}hange{sup }in building methods can have a negative impact on indoor air quality and people's health. (Author)

  4. Comparison of three distinct clean air suits to decrease the bacterial load in the operating room: an observational study.

    Science.gov (United States)

    Kasina, Piotr; Tammelin, Ann; Blomfeldt, Anne-Marie; Ljungqvist, Bengt; Reinmüller, Berit; Ottosson, Carin

    2016-01-01

    Lowering air-borne bacteria counts in the operating room is essential in prevention of surgical site infections in orthopaedic joint replacement surgery. This is mainly achieved by decreasing bacteria counts through dilution, with appropriate ventilation and by limiting the bacteria carrying skin particles, predominantly shed by the personnel. The aim of this study was to investigate if a single use polypropylene clothing system or a reusable polyester clothing system could offer similar air quality in the operating room as a mobile laminar airflow device-assisted reusable cotton/polyester clothing system. Prospective observational study design, comparing the performance of three Clean Air Suits by measuring Colony Forming Units (CFU)/m(3) of air during elective hip and knee arthroplasties, performed at a large university-affiliated hospital. The amount of CFU/m(3) of air was measured during 37 operations of which 13 were performed with staff dressed in scrub suits made of a reusable mixed material (69 % cotton, 30 % polyester, 1 % carbon fibre) accompanied by two mobile laminar airflow units. During 24 procedures no mobile laminar airflow units were used, 13 with staff using a reusable olefin fabric clothing (woven polypropylene) and 11 with staff dressed in single-use suits (non-woven spunbonded polypropylene). Air from the operating field was sampled through a filter, by a Sartorius MD8, and bacterial colonies were counted after incubation. There were 6-8 measurements from each procedure, in total 244 measurements. Statistical analysis was performed by Mann-Whitney U-test. The single-use polypropylene suit reduced the amount of CFU/m(3) to a significantly lower level than both other clothing systems. Single-use polypropylene clothing systems can replace mobile laminar airflow unit-assisted reusable mixed material-clothing systems. Measurements in standardized laboratory settings can only serve as guidelines as environments in real operation settings present a

  5. Testing of adsorbents used in nuclear power plant air cleaning systems using the open-quotes Newclose quotes standards

    International Nuclear Information System (INIS)

    Freeman, W.P.

    1993-01-01

    Ever since the publication of the NRC Information Notice No. 87-32: Deficiencies in the Testing of Nuclear-Grade Activated Charcoal, nuclear power facilities in the US have struggled in their efforts to open-quotes...review the information for applicability to their facilities and consider action, if appropriate ...close quotes as stated in the notice. The encouragement of resident NRC inspectors at some nuclear power facilities has prompted a variety of responses ranging from no change at all in testing requirements to contemplated changes in plant technical specifications. This confusion is the result of a couple factors. The first factor is the lack of a current revision to NRC Regulatory Guide 1.52, the basic document used in nuclear power plant technical specifications for the testing of engineered-safety feature (ESF) post accident air cleaning systems. The second factor is the standards that have been written since the last revision of Reg. Guide 1.52 which include two revision of ANSI N509 and N510, two revisions of RDT M16-1T, two version of ASTM D3803, two versions of ASTM D4069, and three versions of an SME code AG-1. Few of the standards and codes listed above are commensurate with each other and, thus, present a nearly insolvable maze to the HVAC engineer asked to upgrade adsorbent testing requirements following the standards. This paper describes the authors experience with a number of nuclear power facilities in their efforts to meet the requirements of the new standards of testing adsorbents from nuclear power plant air cleaning systems. The existing standards are discussed in light of the current state of the art for adsorbent testing of adsorbent media from nuclear air treatment systems. Test results are presented showing the impact of new test requirements on acceptance criteria when compared to the old test requirements and recommendations are offered for solution of this testing problem in the future. 12 refs., 5 tabs

  6. Potential impacts of energy efficiency policies in the U.S. industry: Results from the clean energy futures study

    International Nuclear Information System (INIS)

    Worrell, Ernst; Price, Lynn

    2001-01-01

    Scenarios for a Clean Energy Future (CEF) studied the role that efficient clean energy technologies can play in meeting the economic and environmental challenges for our future energy supply. The study describes a portfolio of policies that would motivate energy users and businesses to invest in innovative energy efficient technologies. On the basis of the portfolios, two policy scenarios have been developed, i.e. a moderate scenario and an advanced scenario. We focus on the industrial part of the CEF-study. The studied policies include a wide scope of activities, which are organized under the umbrella of voluntary industrial sector agreements. The policies for the policy scenarios have been modeled using the National Energy Modeling System (CEF-NEMS). Under the reference scenario industrial energy use would grow to 41 Quads in 2020, compared to 34.8 Quads in 1997, with an average improvement of the energy intensity by 1.1% per year. In the Moderate scenario the annual improvement is a bout 1.5%/year, leading to primary energy use of 37.8 Quads in 2020, resulting in 10% lower CO2 emissions by 2020 compared to the reference scenario. In the Advanced scenario the annual improvement increases to 1.8% per year, leading to primary energy use of 34.3 Quads in 2020, and 29% lower CO2 emissions. We report on the policies, assumptions and results for industry

  7. Air pollution-related health and climate benefits of clean cookstove programs in Mozambique

    Science.gov (United States)

    Anenberg, Susan C.; Henze, Daven K.; Lacey, Forrest; Irfan, Ans; Kinney, Patrick; Kleiman, Gary; Pillarisetti, Ajay

    2017-02-01

    Approximately 95% of households in Mozambique burn solid fuels for cooking, contributing to elevated indoor and outdoor fine particulate matter (PM2.5) concentrations and subsequent health and climate impacts. Little is known about the potential health and climate benefits of various approaches for expanding the use of cleaner stoves and fuels in Mozambique. We use state-of-the-science methods to provide a first-order estimation of potential air pollution-related health and climate benefits of four illustrative scenarios in which traditional cooking fires and stoves are displaced by cleaner and more efficient technologies. For rural areas, we find that a 10% increase in the number of households using forced draft wood-burning stoves could achieve >2.5 times more health benefits from reduced PM2.5 exposure (200 avoided premature deaths and 14 000 avoided disability adjusted life years, DALYs, over a three-year project lifetime) compared to natural draft stoves in the same households, assuming 70% of households use the new technology for both cases. Expanding use of LPG stoves to 10% of households in five major cities is estimated to avoid 160 premature deaths and 11 000 DALYs from reduced PM2.5 exposure for a three-year intervention, assuming 60% of households use the new stove. Advanced charcoal stoves would achieve ∽80% of the PM2.5-related health benefits of LPG stoves. Approximately 2%-5% additional health benefits would result from reduced ambient PM2.5, depending on the scenario. Although climate impacts are uncertain, we estimate that all scenarios would reduce expected climate change-related temperature increases from continued solid fuel use by 4%-6% over the next century. All results are based on an assumed adjustment factor of 0.8 to convert from laboratory-based emission reduction measurements to exposure reductions, which could be optimistic in reality given potential for continued use of the traditional stove. We conclude that cleaner cooking stoves

  8. Market effects of environmental regulation: coal, railroads, and the 1990 Clean Air Act

    Energy Technology Data Exchange (ETDEWEB)

    Busse, M.R.; Keohane, N.O. [University of California Berkeley, Berkeley, CA (United States)

    2007-01-01

    Many environmental regulations encourage the use of 'clean' inputs. When the suppliers of such an input have market power, environmental regulation will affect not only the quantity of the input used but also its price. We investigate the effect of the Title IV emissions trading program for sulfur dioxide on the market for low-sulfur coal. We find that the two railroads transporting coal were able to price discriminate on the basis of environmental regulation and geographic location. Delivered prices rose for plants in the trading program relative to other plants, and by more at plants near a low-sulfur coal source.

  9. Performances in Tank Cleaning

    Directory of Open Access Journals (Sweden)

    Fanel-Viorel Panaitescu

    2018-03-01

    Full Text Available There are several operations which must do to maximize the performance of tank cleaning. The new advanced technologies in tank cleaning have raised the standards in marine areas. There are many ways to realise optimal cleaning efficiency for different tanks. The evaluation of tank cleaning options means to start with audit of operations: how many tanks require cleaning, are there obstructions in tanks (e.g. agitators, mixers, what residue needs to be removed, are cleaning agents required or is water sufficient, what methods can used for tank cleaning. After these steps, must be verify the results and ensure that the best cleaning values can be achieved in terms of accuracy and reliability. Technology advancements have made it easier to remove stubborn residues, shorten cleaning cycle times and achieve higher levels of automation. In this paper are presented the performances in tank cleaning in accordance with legislation in force. If tank cleaning technologies are effective, then operating costs are minimal.

  10. Removal of NO2 and O3 generated from corona discharge in indoor air cleaning with MnO2 catalyst

    International Nuclear Information System (INIS)

    Ge, H; Yu, R; Zhu, Y M; Mi, D

    2013-01-01

    The production rules and removal efficiency of harmful byproducts such as NO 2 and O 3 generated from DC corona discharge in indoor air cleaning were investigated. The production behaviours of NO 2 and O 3 and the relationship between the amount of catalyst (MnO 2 ) and the removal rate of harmful byproducts were experimentally studied. Further, indoor application tests were carried out in a closed room with 90 m 3 . The results showed that the concentrations of NO 2 and O 3 produced by corona discharge linearly increased with discharge time. The NO 2 yield is larger than O 3 by almost one order of magnitude under the same discharge power. To satisfy the demand of Standard of Indoor Air Quality (GB/T18883-2002), the power consumption of unit volume should be less than 1 W m −3 and the catalyst MnO 2 consumptions in positive-negative corona discharge were 200 cm 3 W −1 and 100 cm 3 W −1 , respectively.

  11. Brushless Cleaning of Solar Panels and Windows

    Science.gov (United States)

    Schneider, H. W.

    1982-01-01

    Machine proposed for cleaning solar panels and reflectors uses multiple vortexes of air, solvent, and water to remove dust and dirt. Uses no brushes that might abrade solar surfaces and thereby reduce efficiency. Machine can be readily automated and can be used on curved surfaces such as aparbolic reflectors as well as on flat ones. Cleaning fluids are recycled, so that large quantities of water and solvent are not needed.

  12. Radioactivity in the furnace air-cleaning filter from a house with an unusually high level of airborne radon

    International Nuclear Information System (INIS)

    Rundo, J.; Essling, M.A.; Urnezis, P.W.

    1979-01-01

    The amounts of the three short-lived daughters of radon on the furnace air-cleaning filter from a house with a high level of radon were estimated to be 8.2, 33, and 38 kBq (0.22, 0.89, and 1.03 μCi) for 218 Po, 214 Pb, and 214 Bi, respectively, at the time of removal from the furnace. These data were used to calculate the airborne concentrations of the three, and the results indicated that about 70% of the daughters were lost to surfaces in the house and by impaction in the air ducts. The filter's content of 210 Pb was found to be 4.4 kBg (0.12 μCi); from this the average concentration of radon-producing filterable daughters during the time the furnace blower operated, was estimated to be 860 Bq m -3 . This indicated that there was no significant loss to surfaces or in air ducts. Possible reasons for the difference are given. The filter was also found to contain 1 kBq (27 nCi) of 212 Bi from the thorium series

  13. Gasoline compression ignition approach to efficient, clean and affordable future engines

    KAUST Repository

    Kalghatgi, Gautam; Johansson, Bengt

    2017-01-01

    towards diesel and jet fuels, leading to a probable surplus of lighter low-octane fuels. Current diesel engines are efficient but expensive and complicated because they try to reduce the nitrogen oxide and soot emissions simultaneously while using

  14. Basic Research Needs for Clean and Efficient Combustion of 21st Century Transportation Fuels

    Energy Technology Data Exchange (ETDEWEB)

    McIlroy, A.; McRae, G.; Sick, V.; Siebers, D. L.; Westbrook, C. K.; Smith, P. J.; Taatjes, C.; Trouve, A.; Wagner, A. F.; Rohlfing, E.; Manley, D.; Tully, F.; Hilderbrandt, R.; Green, W.; Marceau, D.; O' Neal, J.; Lyday, M.; Cebulski, F.; Garcia, T. R.; Strong, D.

    2006-11-01

    To identify basic research needs and opportunities underlying utilization of evolving transportation fuels, with a focus on new or emerging science challenges that have the potential for significant long-term impact on fuel efficiency and emissions.

  15. Cleaning of porous filters in fossilized bed reactors

    International Nuclear Information System (INIS)

    Rodrigo Otero, A.; Sancho Rod, J.

    1965-01-01

    In this report are established the optimum working conditions of a filter cleaning system by blow back. For this purpose it was determined in the first place the blow back air rate necessary to have a good cleaning. The reasons for which it was not possible until now to control the pressure in a fluidized bed calcination reactor are analyzed and a criteria is established to calculate the optimum floe necessary to clean efficiently a porous by this procedures. (Author)

  16. Air contamination for predicting wound contamination in clean surgery: A large multicenter study.

    Science.gov (United States)

    Birgand, Gabriel; Toupet, Gaëlle; Rukly, Stephane; Antoniotti, Gilles; Deschamps, Marie-Noelle; Lepelletier, Didier; Pornet, Carole; Stern, Jean Baptiste; Vandamme, Yves-Marie; van der Mee-Marquet, Nathalie; Timsit, Jean-François; Lucet, Jean-Christophe

    2015-05-01

    The best method to quantify air contamination in the operating room (OR) is debated, and studies in the field are controversial. We assessed the correlation between 2 types of air sampling and wound contaminations before closing and the factors affecting air contamination. This multicenter observational study included 13 ORs of cardiac and orthopedic surgery in 10 health care facilities. For each surgical procedure, 3 microbiologic air counts, 3 particles counts of 0.3, 0.5, and 5 μm particles, and 1 bacteriologic sample of the wound before skin closure were performed. We collected data on surgical procedures and environmental characteristics. Of 180 particle counts during 60 procedures, the median log10 of 0.3, 0.5, and 5 μm particles was 7 (interquartile range [IQR], 6.2-7.9), 6.1 (IQR, 5.4-7), and 4.6 (IQR, 0-5.2), respectively. Of 180 air samples, 50 (28%) were sterile, 90 (50%) had 1-10 colony forming units (CFU)/m(3) and 40 (22%) >10 CFU/m(3). In orthopedic and cardiac surgery, wound cultures at closure were sterile for 24 and 9 patients, 10 and 11 had 1-10 CFU/100 cm(2), and 0 and 6 had >10 CFU/100 cm(2), respectively (P air microbial counts (P contamination (P = .22). This study suggests that particle counting is a good surrogate of airborne microbiologic contamination in the OR. Copyright © 2015 Association for Professionals in Infection Control and Epidemiology, Inc. Published by Elsevier Inc. All rights reserved.

  17. HVAC--the importance of clean intake section and dry air filter in cold climate.

    Science.gov (United States)

    Hanssen, S O

    2004-01-01

    HVAC systems, if properly designed, installed, operated and maintained, will improve thermal conditions and air quality indoors. However, the success strongly depends on the design of the system and the quality of the components we use in our HVAC installations. Regrettably, several investigations have revealed that many HVAC installations have a lot of operational and maintenance problems, especially related to moisture, rain and snow entrainment. In short, it seems that too little attention is placed on the design of the intake section, despite the fact that there exists a large number of national and international guidelines and recommendations. This is a serious problem because the air intake is the initial component of the ventilation plant and as such the first line of defense against debris and other outdoor air pollutants. Unfortunately, the design is often an argued compromise between the architect, the civil engineer and the HVAC engineer. In the future, the technical, hygienic and microbiological feature of air intakes must be better ensured in order to avoid the air intake becoming a risk component as regards contamination and indoor air quality. Further, it seems that the magnitude of the problem is not well known, or recognized, by the building designers, engineers and professionals involved in the construction and operation of buildings. This fact needs to be addressed more seriously, because obviously there is a big difference between the idealistic architectonic design, engineering intentions and the real life situation. Several practical recommendations for design and operation of HVAC systems are presented. Following the recommendations will result in less pollution from the HVAC-system and increased indoor environmental quality.

  18. Krakow clean fossil fuels and energy efficiency program. Phase 1 report

    Energy Technology Data Exchange (ETDEWEB)

    Butcher, T.; Pierce, B. [eds.

    1995-06-01

    Krakow is one of the largest and oldest cities in Poland. It is situated in the south of the country on the banks of the Vistula River. From the 11th until the 17th centuries, it was the capital of Poland. Today, Krakow is a city of 750,000 residents, one of the largest centers of higher education, an important industrial center, and is of particular importance because of the number and kinds of historic buildings and sites. For this reason, Krakow was included by the UNESCO in the list of the world`s cultural heritages. For about three decades, significant air pollution has been one of Krakow`s most serious problems. Because the city is situated in the Vistula River valley, it is poorly ventilated and experiences a high concentration of air pollutants. The quality of air in Krakow is affected mainly by industry (Sendzimir Steelworks, energy industry, chemical plants), influx from the Silesian industrial region (power plants, metallurgy), transboundary pollution (Ostrava - Czech Republic), and local sources of low pollution, i.e. more than 1,000 boiler houses using solid fuels and more than 100,000 coal-fired home stoves. These local sources, with low stacks and almost no pollution-control equipment, are responsible for about 35-40% of the air pollution. This report presents phase I results of a program to reduce pollution in krakow. Phase I was to gather information on emissions and costs, and to verify assumptions on existing heating methods and alternatives.

  19. The effects of Title IV of the Clean Air Act amendments of 1990 on electric utilities: An update

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1997-03-01

    This report presents data and analyses related to Phase I implementation of the Clean Air Act Amendment by electric utilities. It describes the strategies used to comply with the Acid Rain Program in 1995, the effect of compliance on sulfur dioxide emissions levels, the cost of compliance, and the effects of the program on coal supply and demand. The first year of Phase I demonstrated that the market-based sulfur dioxide emissions control system could achieve significant reductions in emissions at lower than expected costs. Some utilities reduced aggregate emissions below legal requirements due to economic incentives; other utilities purchased additional allowances to avoid noncompliance. More than half of the utilities switched to or blended with lower sulfur coal, due to price reductions in the coal market which were partially due to the allowance trading program. 21 figs., 20 tabs.

  20. Energy Efficiency and Air Quality Repairs at Lyonsdale Biomass

    Energy Technology Data Exchange (ETDEWEB)

    Brower, Michael R; Morrison, James A; Spomer, Eric; Thimot, Carol A

    2012-07-31

    This project enabled Lyonsdale Biomass, LLC to effect analyses, repairs and upgrades for its biomass cogeneration facility located in Lewis County, New York and close by the Adirondack Park to reduce air emissions by improving combustion technique and through the overall reduction of biomass throughput by increasing the system's thermodynamic efficiency for its steam-electrical generating cycle. Project outcomes result in significant local, New York State, Northeast U.S. and national benefits including improved renewable energy operational surety, enhanced renewable energy efficiency and more freedom from foreign fossil fuel source dependence. Specifically, the reliability of the Lyonsdale Biomass 20MWe woody biomass combined-heat and power (CHP) was and is now directly enhanced. The New York State and Lewis County benefits are equally substantial since the facility sustains 26 full-time equivalency (FTE) jobs at the facility and as many as 125 FTE jobs in the biomass logistics supply chain. Additionally, the project sustains essential local and state payment in lieu of taxes revenues. This project helps meet several USDOE milestones and contributes directly to the following sustainability goals:  Climate: Reduces greenhouse gas emissions associated with bio-power production, conversion and use, in comparison to fossil fuels. Efficiency and Productivity: Enhances efficient use of renewable resources and maximizes conversion efficiency and productivity. Profitability: Lowers production costs. Rural Development: Enhances economic welfare and rural development through job creation and income generation. Standards: Develop standards and corresponding metrics for ensuring sustainable biopower production. Energy Diversification and Security: Reduces dependence on foreign oil and increases energy supply diversity. Net Energy Balance: Ensures positive net energy balance for all alternatives to fossil fuels.

  1. RESULTS OF A PILOT FIELD STUDY TO EVALUATE THE EFFECTIVENESS OF CLEANING RESIDENTIAL HEATING AND AIR-CONDITIONING SYSTEMS AND THE IMPACT ON INDOOR AIR QUALITY AND SYSTEM PERFORMANCE

    Science.gov (United States)

    The report discusses and gives results of a pilot field study to evaluate the effectiveness of air duct cleaning (ADC) as a source removal technique in residential heating and air-conditioning (HAC) systems and its impact on airborne particle, fiber, and bioaerosol concentrations...

  2. Tuning 3D topography on biomimetic surface for efficient self-cleaning and microfluidic manipulation

    International Nuclear Information System (INIS)

    Guan, Wei-Sheng; Huang, Han-Xiong; Chen, An-Fu

    2015-01-01

    Currently, micro-/nanotopography on polymeric replica is generally limited to 2D when a mechanical demolding approach is applied. In this work, one-step replication of bio-inspired 3D topography is achieved using microinjection compression molding with novel dual-layer molds. Using a proposed flexible template, the replica topography and wettability are highly tunable during molding. Moreover, dual-scale topography on the mold is developed by coating the micropatterned insert with submicron silica particles. Contact angle and roll-off angle measurements indicate the lotus leaf, rose petal and rice leaf effects on biomimetic surfaces. Among the three kinds of surfaces, the petal-inspired surface possesses the superior performance in self-cleaning submicron contaminants and mechanical robustness, which is highly correlated to the low roughness-induced adhesive superhydrophobicity and the absence of fragile submicron-/nanostructure, respectively. Furthermore, a multi-layer mold structure is proposed for fabricating the open microfluidic devices. The embedment of the hydrophilic and hydrophobic silica particles in the microstructured open channel and the hydrophobic silica particles in the background area during replication renders the wettability contrast sharp, realizing the self-driven flow of microfluid confined within the open microchannel. (paper)

  3. Tuning 3D topography on biomimetic surface for efficient self-cleaning and microfluidic manipulation

    Science.gov (United States)

    Guan, Wei-Sheng; Huang, Han-Xiong; Chen, An-Fu

    2015-03-01

    Currently, micro-/nanotopography on polymeric replica is generally limited to 2D when a mechanical demolding approach is applied. In this work, one-step replication of bio-inspired 3D topography is achieved using microinjection compression molding with novel dual-layer molds. Using a proposed flexible template, the replica topography and wettability are highly tunable during molding. Moreover, dual-scale topography on the mold is developed by coating the micropatterned insert with submicron silica particles. Contact angle and roll-off angle measurements indicate the lotus leaf, rose petal and rice leaf effects on biomimetic surfaces. Among the three kinds of surfaces, the petal-inspired surface possesses the superior performance in self-cleaning submicron contaminants and mechanical robustness, which is highly correlated to the low roughness-induced adhesive superhydrophobicity and the absence of fragile submicron-/nanostructure, respectively. Furthermore, a multi-layer mold structure is proposed for fabricating the open microfluidic devices. The embedment of the hydrophilic and hydrophobic silica particles in the microstructured open channel and the hydrophobic silica particles in the background area during replication renders the wettability contrast sharp, realizing the self-driven flow of microfluid confined within the open microchannel.

  4. Direct in-vessel applications experiments at Harvard Air Cleaning Laboratory. Annual report, October 1, 1975--January 31, 1977

    International Nuclear Information System (INIS)

    Mallove, E.; Hinds, W.; First, M.W.

    1977-02-01

    Prototypes of direct in-vessel emergency air cleaning systems were evaluated for possible application in an LMFBR containment vessel after a hypothetical core disruptive accident. These were turbulence enhanced sedimentation, powder dispersal scavenging, acoustic agglomeration enhanced sedimentation, and combinations of turbulence with powder dispersal. The effect of turbulent agglomeration in enhancing the sedimentation of a sodum pool fire aerosol was experimentally demonstrated in a 90 m 3 test chamber, 4 meters high. Two hour dose reduction factors (DRF(2 hr)) from 7 to 56 were achieved in the 4 meter high chamber using fan-induced turbulent agglomeration on aerosols that varied in initial mass concentration from 1 to 12 gm/m 3 . In the same chamber, a prototype limestone powder dispersal scavenging system was tested and achieved DRF(2 hr)'s up to 10. The beneficial effect of combining turbulence with powder dispersal in a single system was demonstrated in a test which yielded a DRF(2 hr) of 20. This was greater than for either mechanism separately applied when initial aerosol mass concentration was 2 gm/m3. Acoustic agglomeration of sodium pool fire aerosols was tested in a smaller 0.65 m 3 , 75 cm high settling chamber, using an electronic siren which produced a sound pressure level of 145 dB in the reverberant chamber. The DRF(2 hr) in the small chamber with the siren operating was found to be from 17 to 31, 2 to 3 times greater than the DRF(2 hr) for unperturbed settling. Pulse-jet engines were found to be unsuitable for generating high sound levels for this application. Scaling each of the systems tested to a 30 m high containment vessel indicated no reason why one or more of the systems investigated could not be applied successfully as an emergency air cleaning system

  5. 76 FR 9610 - Notice of Proposed Consent Decree Under the Clean Air Act

    Science.gov (United States)

    2011-02-18

    ... pollution control technology; undertake periodic equipment testing; and to submit required reports. The... resolves allegations by the Environmental Protection Agency and the San Joaquin Valley Unified Air Pollution Control District (``District''), asserted in a complaint filed together with the Consent Decree...

  6. 78 FR 49511 - Clean Air Act Advisory Committee (CAAAC): Notice of Meeting

    Science.gov (United States)

    2013-08-14

    [email protected] , preferably at least 10 days prior to the meeting to give EPA as much time as possible to... Committee agenda and any documents prepared for the meeting will be publicly available on the CAAAC Web site... CAAAC meeting minutes, will also be available on the CAAAC Web site or by contacting the Office of Air...

  7. 75 FR 51483 - Notice of Lodging of Consent Decree Under the Clean Air Act

    Science.gov (United States)

    2010-08-20

    ... given that on August 9, 2010, a proposed Consent Decree in United States v. Middlesex County Utilities... Air Pollution Control Act, N.J.S.A. 26:2C-1 et seq., at the Middlesex County landfill in East... to the United States and New Jersey, and shall upgrade the Middlesex County Landfill Gas Collection...

  8. 75 FR 25855 - Clean Air Act Advisory Committee (CAAAC): Notice of Meeting

    Science.gov (United States)

    2010-05-10

    ...) Permits/NSR/Toxics Integration--Liz Naess, (919) 541-1892; (2) Economic Incentives and Regulatory... Air Act of 1990. The Committee advises on economic, environmental, technical scientific, and...., Washington, DC. Seating will be available on a first come, first served basis. The Economic Incentives and...

  9. 75 FR 22787 - Proposed Settlement Agreement, Clean Air Act Citizen Suit

    Science.gov (United States)

    2010-04-30

    ... INFORMATION CONTACT: Rick Vetter, Air and Radiation Law Office (2344A), Office of General Counsel, U.S... Parish, a non-profit corporation, (hereinafter collectively ``LEAN'') filed a complaint in the United..., LEAN alleges that EPA has failed to fulfill a mandatory duty to respond to an administrative petition...

  10. 75 FR 75672 - Proposed Settlement Agreement, Clean Air Act Citizen Suit

    Science.gov (United States)

    2010-12-06

    ...: Jan Tierney, Air and Radiation Law Office (2344A), Office of General Counsel, U.S. Environmental... with the Court in LEAN v. Jackson (civil action no. 1:09-01333) a motion pursuant to Fed. R. Civ. P. 41... available for public viewing at the Office of Environmental Information (OEI) Docket in the EPA Docket...

  11. 78 FR 18979 - Proposed Settlement Agreement, Clean Air Act Citizen Suit

    Science.gov (United States)

    2013-03-28

    .... Jackson, Case No. 12- 1096 (D.D.C.) (``LEAN v. Jackson''). Plaintiffs filed this suit to compel the... INFORMATION CONTACT: Melina Williams, Air and Radiation Law Office (2344A), Office of General Counsel, U.S... Amended Complaint with prejudice in LEAN v. Jackson. In addition, the proposed settlement agreement...

  12. 75 FR 1770 - Proposed Consent Decree, Clean Air Act Citizen Suit

    Science.gov (United States)

    2010-01-13

    ... Division, to the Public Service of Colorado to operate the Hayden Station power plant near Hayden, Colorado... Environment, Air Pollution Division, to the Public Service of Colorado to operate the Hayden Station power plant near Hayden, Colorado. Under the terms of the proposed consent decree, EPA has agreed to respond...

  13. Efficiency and durability of a self-cleaning coating on concrete and stones under both natural and artificial ageing trials

    Science.gov (United States)

    Carmona-Quiroga, P. M.; Martínez-Ramírez, S.; Viles, H. A.

    2018-03-01

    This study aimed to test the performance under long-term working conditions of a commercial self-cleaning coating, a water-based TiO2 sol, on three building materials important in recent and older European heritage; Portland limestone, Woodkirk sandstone and concrete. First, the compatibility of the coating (effect on petrophysical properties) with the substrates was demonstrated by examining aesthetic properties and water vapour permeability of the building materials and secondly, the self-cleaning ability of the TiO2 nanoparticles in degrading artificial stain (rhodamine B) under UV light was evaluated. Finally, the durability (lasting performance) of photocatalytic activity was assessed during one year of outdoor exposure trial and 2000 h of accelerated ageing in a chamber with UV radiation and condensation cycles. Results showed that photocatalytic activity was unaltered on concrete, whereas on sandstone, particularly after artificial ageing, it was reduced due to the removal of nanoparticles from the surface. On limestone, a decrease of TiO2 content was observed but photodegradation efficiency (ability to perform as self-cleaner) seemed not to be affected.

  14. Energy efficiency impact of EGR on organizing clean combustion in diesel engines

    International Nuclear Information System (INIS)

    Divekar, Prasad S.; Chen, Xiang; Tjong, Jimi; Zheng, Ming

    2016-01-01

    Highlights: • Studied EGR impact on efficiency and emissions of diesel and dual-fuel combustion. • Quantified effectiveness of intake dilution for NOx reduction using EGR. • Identified suitable EGR ranges for mitigating emissions–efficiency trade-off. • Developed careful control of intake dilution and in-cylinder excess ratio. • Enabled ultra-low NOx in both diesel and dual-fuel combustion via EGR control. - Abstract: Exhaust gas recirculation (EGR) is a commonly recognized primary technique for reducing NOx emissions in IC engines. However, depending on the extent of its use, the application of EGR in diesel engines is associated with an increase in smoke emissions and a reduction in thermal efficiency. In this work, empirical investigations and parametric analyses are carried out to assess the impact of EGR in attaining ultra-low NOx emissions while minimizing the smoke and efficiency penalties. Two fuelling strategies are studied, namely diesel-only injection and dual-fuel injection. In the dual-fuel strategy, a high volatility liquid fuel is injected into the intake ports, and a diesel fuel is injected directly into the cylinder. The results suggest that the reduction in NOx can be directly correlated with the intake dilution caused by EGR and the correlation is largely independent of the fuelling strategy, the intake boost, and the engine load level. Simultaneously ultra-low NOx and smoke emissions can be achieved at high intake boost and intake dilution levels in the diesel-only combustion strategy and at high ethanol fractions in the dual-fuel strategy. The efficiency penalty associated with EGR is attributed to two primary factors; the combustion off-phasing and the reduction in combustion efficiency. The combustion off-phasing can be minimized by the closed loop control of the diesel injection timing in both the fuelling strategies, whereas the combustion efficiency can be improved by limiting the intake dilution to moderate levels. The

  15. Controlling particulate matter under the Clean Air Act: a menu of options

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    1996-07-01

    This document was prepared by STAPPA and ALAPCO to help US state and local air pollution control officials understand the effects of particulate matter (PM) on human health and air quality, the relative contribution of various sources to particulate emissions, and the effectiveness and costs of various approaches - including innovative ones - to minimizing these emissions. The document covers particulate matter with a nominal diameter of 10 microns ({mu}m) or less (PM{sub 10}), including `fine` PM of 2.5 microns or less in diameter (PM{sub 2.5}). Sections cover: the effects of particulate matter on human health; regulatory issues; characterization of particulate matter; emission control strategies for mobile sources (diesel engines, small nonroad engines, alternative fuels etc.), particulates from stationary sources (electric utilities, industry and commercial fuel combustion; mineral products industry, metallurgical industry etc.); particulates from area sources; and market-based strategies for controlling particulate matter. 2 apps.

  16. Air Emission Projections During Acid Cleaning of F-Canyon Waste Header No.2

    International Nuclear Information System (INIS)

    CHOI, ALEXANDER

    2004-01-01

    The purpose of this study was to develop the air emission projections for the maintenance operation to dissolve and flush out the scale material inside the F-Canyon Waste Header No.2. The chemical agent used for the dissolution is a concentrated nitric acid solution, so the pollutant of concern is the nitric acid vapor. Under the very conservative operating scenarios considered in this study, it was determined that the highest possible rate of nitric acid emission during the acid flush would be 0.048 lb. per hr. It turns out that this worst-case air emission projection is just below the current exemption limit of 0.05 lb. per hr. for permit applications

  17. Health and efficiency in trimix versus air breathing in compressed air workers.

    Science.gov (United States)

    Van Rees Vellinga, T P; Verhoeven, A C; Van Dijk, F J H; Sterk, W

    2006-01-01

    The Western Scheldt Tunneling Project in the Netherlands provided a unique opportunity to evaluate the effects of trimix usage on the health of compressed air workers and the efficiency of the project. Data analysis addressed 318 exposures to compressed air at 3.9-4.4 bar gauge and 52 exposures to trimix (25% oxygen, 25% helium, and 50% nitrogen) at 4.6-4.8 bar gauge. Results revealed three incidents of decompression sickness all of which involved the use of compressed air. During exposure to compressed air, the effects of nitrogen narcosis were manifested in operational errors and increased fatigue among the workers. When using trimix, less effort was required for breathing, and mandatory decompression times for stays of a specific duration and maximum depth were considerably shorter. We conclude that it might be rational--for both medical and operational reasons--to use breathing gases with lower nitrogen fractions (e.g., trimix) for deep-caisson work at pressures exceeding 3 bar gauge, although definitive studies are needed.

  18. Hybrid and Plug-In Electric Vehicles (Spanish Version); Clean Cities, Energy Efficiency & Renewable Energy (EERE)

    Energy Technology Data Exchange (ETDEWEB)

    None

    2015-08-01

    This is a Spanish-language brochure about hybrid and plug-in electric vehicles, which use electricity as their primary fuel or to improve the efficiency of conventional vehicle designs. These vehicles can be divided into three categories: hybrid electric vehicles (HEVs), plug-in hybrid electric vehicles (PHEVs), all-electric vehicles (EVs). Together, they have great potential to cut U.S. petroleum use and vehicle emissions.

  19. Investigation of the biofuel flue and producer gases cleaning efficiency using ESP

    Science.gov (United States)

    Poškas, Robertas; Sirvydas, Arūnas; Poškas, Povilas; Striūgas, Nerijus; Pedišius, Nerijus; Valinčius, Vitas

    2017-11-01

    The use of biofuel has been increasing in Europe over the last years, and the reason for that is acceptable cost and the least negative impact on the environment. However, NOx and emissions of fine particulates are important, and biofuel is still a disadvantage compared to oil and natural gas fired systems. Usually, flue gas is filtered in multicyclones or fibre filters before discharge into the atmosphere. Yet, in the case of fine particulates, the filters of such type do not show high effectiveness, thus electrostatic precipitators are used. In this comparative study on biofuel (wood pellets), the collection efficiency of solid particles from a class 3 boiler (50 kW) and from a gasification unit (100 kW) was investigated. Although releases of solid particles from modern boilers are low, a combination of such a boiler with an electrostatic precipitator may reduce the releases of particles to the minimum, and the collection efficiency of the electrostatic precipitator obtained during the investigation was 98-99%. There is a big difference in particle concentrations comparing the systems with flue gas and producer gas. As the working conditions in the test section with producer gas were harder, it led to lower efficiency of the electrostatic precipitator ( 75%).

  20. Investigation of the biofuel flue and producer gases cleaning efficiency using ESP

    Directory of Open Access Journals (Sweden)

    Poškas Robertas

    2017-01-01

    Full Text Available The use of biofuel has been increasing in Europe over the last years, and the reason for that is acceptable cost and the least negative impact on the environment. However, NOx and emissions of fine particulates are important, and biofuel is still a disadvantage compared to oil and natural gas fired systems. Usually, flue gas is filtered in multicyclones or fibre filters before discharge into the atmosphere. Yet, in the case of fine particulates, the filters of such type do not show high effectiveness, thus electrostatic precipitators are used. In this comparative study on biofuel (wood pellets, the collection efficiency of solid particles from a class 3 boiler (50 kW and from a gasification unit (100 kW was investigated. Although releases of solid particles from modern boilers are low, a combination of such a boiler with an electrostatic precipitator may reduce the releases of particles to the minimum, and the collection efficiency of the electrostatic precipitator obtained during the investigation was ~98-99%. There is a big difference in particle concentrations comparing the systems with flue gas and producer gas. As the working conditions in the test section with producer gas were harder, it led to lower efficiency of the electrostatic precipitator (~75%.

  1. FISSION 2120: a program for assessing the need for engineered safety feature grade air cleaning systems in post accident environments

    International Nuclear Information System (INIS)

    Martin, G. Jr.; Michlewicz, D.; Thomas, J.

    1979-01-01

    A computer program FISSION 2120, has been developed to evaluate the need for various engineered Safety Feature grade air cleaning systems to mitigate radiation exposures resulting from accidential releases of radioactivity. Those systems which are generally investigated include containment sprays with chemical additives, containment fan coolers with charcoal filters, and negative pressure maintenance systems for double barrier containments with either one-pass filtration or recirculation with filtration. The program can also be used to calculate the radiation doses to control room personnel. This type of analysis is directed towards the various protection aspects of the emergency ventilation system and involves the modeling of the radiological source terms and the atmospheric transport of the radioactive releases. The modeling is enhanced by the inherent capability of the program to accommodate simultaneous release of activity from several sources and to perform a dose evaluation for a wide range of the design characteristics of control room emergency air filtration systems. Use of the program has resulted in considerable savings in the time required to perform such analyses and in the selection of the most cost-effective Engineered Safety Features

  2. Reactive inspection response of NRC Region III to potential technical deficiencies identified in recent Nuclear Air Cleaning Conference papers

    International Nuclear Information System (INIS)

    Gill, C.F.

    1987-01-01

    In order to effectively meet its responsibility to protect the public health and safety, the Nuclear Regulatory Commission (NRC) nuclear power plant licensing and inspection programs respond to potential technical deficiencies identified by conference and professional society meeting papers when deemed appropriate. The NRC staff's response mechanisms for such technical deficiencies include: generic letters, Bulletins, Information Notices, Standard Review Plan (NUREG-0800) revisions, docketed Final Safety Analysis Report (FSAR) questions, special studies, special (reactive) inspection, and inspection program revisions. This paper describes reactive inspection efforts by Region III in response to potential technical deficiencies identified in recent air cleaning conference papers, including: post-accident effluent sample line deposition losses; failure to implement good engineering practices in the design, construction, and testing of Nuclear Air Treatment Systems (NATS); filter bypass via filter housing drain lines; spinster carbon degradation; use of silicone sealants and other temporary patching material in NATS; filter housing fire protection deluge system problems; lack of charcoal batch traceability; Quality Assurance records problems involving equipment, vendor, filter, and personnel qualifications; inadequate ANSI/ASME N510 acceptance criteria and tests; and failure to adequately demonstrate control room habitability per 10 CFR 50, Appendix A, General Design Criterion-19. Region III inspections indicate that many of these deficiencies appear to be prevalent. Inspection findings and utility responses to the findings are discussed. NRC Region III and Headquarters programmatic reactions to the identified generic problem areas are also discussed

  3. Validation of the criteria for initiating the cleaning of heating, ventilation, and air-conditioning (HVAC) ductwork under real conditions.

    Science.gov (United States)

    Lavoie, Jacques; Marchand, Geneviève; Cloutier, Yves; Lavoué, Jérôme

    2011-08-01

    Dust accumulation in the components of heating, ventilation, and air-conditioning (HVAC) systems is a potential source of contaminants. To date, very little information is available on recognized methods for assessing dust buildup in these systems. The few existing methods are either objective in nature, involving numerical values, or subjective in nature, based on experts' judgments. An earlier project aimed at assessing different methods of sampling dust in ducts was carried out in the laboratories of the Institut de recherche Robert-Sauvé en santé et en sécurité du travail (IRSST). This laboratory study showed that all the sampling methods were practicable, provided that a specific surface-dust cleaning initiation criterion was used for each method. However, these conclusions were reached on the basis of ideal conditions in a laboratory using a reference dust. The objective of this present study was to validate these laboratory results in the field. To this end, the laboratory sampling templates were replicated in real ducts and the three sampling methods (the IRSST method, the method of the U.S. organization National Air Duct Cleaner Association [NADCA] and that of the French organization Association pour la Prévention et l'Étude de la Contamination [ASPEC]) were used simultaneously in a statistically representative number of systems. The air return and supply ducts were also compared. Cleaning initiation criteria under real conditions were found to be 6.0 mg/100 cm(2) using the IRSST method, 2.0 mg/100 cm(2) using the NADCA method, and 23 mg/100 cm(2) using the ASPEC method. In the laboratory study, the criteria using the same methods were 6.0 for the IRSST method, 2.0 for the NADCA method, and 3.0 for the ASPEC method. The laboratory criteria for the IRSST and NADCA methods were therefore validated in the field. The ASPEC criterion was the only one to change. The ASPEC method therefore allows for the most accurate evaluation of dust accumulation in HVAC

  4. Air-handling energy efficiency and design practices

    Energy Technology Data Exchange (ETDEWEB)

    Nilsson, Lars J.

    1993-12-31

    With good design practices and life-cycle cost optimization, specific fan power for individual fans will be between 0.5 and 1kW/m{sup 3}/s. Data from nearly 1000 audited fans in Sweden show that the average measured SFPI weighted by drawn motor power is 1.5 kW/m{sup 3}/s and the situation appears to be similar in other countries. Contract forms used by Swedish builders, and consultants` design practices are analyzed here to search for an explanation to the low performance of installed systems. Identified as two major barriers to efficient system design are the lack of performance specifications when procuring systems and the incentive structure in the building sector. As a consequence, duct design methods, rules of thumb, and vendor recommendations are not leading to system optimization. The broad minima in life cycle costs over a range of air-handling unit sizes show that potential economic welfare losses from efficiency standards are likely to be smaller than the losses that result from today`s design practices. 73 refs, 4 figs, 3 tabs

  5. Air-handling energy efficiency and design practices

    Energy Technology Data Exchange (ETDEWEB)

    Nilsson, Lars J

    1994-12-31

    With good design practices and life-cycle cost optimization, specific fan power for individual fans will be between 0.5 and 1kW/m{sup 3}/s. Data from nearly 1000 audited fans in Sweden show that the average measured SFPI weighted by drawn motor power is 1.5 kW/m{sup 3}/s and the situation appears to be similar in other countries. Contract forms used by Swedish builders, and consultants` design practices are analyzed here to search for an explanation to the low performance of installed systems. Identified as two major barriers to efficient system design are the lack of performance specifications when procuring systems and the incentive structure in the building sector. As a consequence, duct design methods, rules of thumb, and vendor recommendations are not leading to system optimization. The broad minima in life cycle costs over a range of air-handling unit sizes show that potential economic welfare losses from efficiency standards are likely to be smaller than the losses that result from today`s design practices. 73 refs, 4 figs, 3 tabs

  6. Controlling the clean room atmosphere

    International Nuclear Information System (INIS)

    Meeks, R.F.

    1979-01-01

    Several types of clean rooms are commonly in use. They include the conventional clean room, the horizontal laminar flow clean room, the vertical laminar flow clean room and a fourth type that incorporates ideas from the previous types and is known as a clean air bench or hood. These clean rooms are briefly described. The origin of contamination and methods for controlling the contamination are discussed

  7. 40 CFR Appendix H to Subpart A of... - Clean Air Act Amendments of 1990 Phaseout Schedule for Production of Ozone-Depleting Substances

    Science.gov (United States)

    2010-07-01

    ... 40 Protection of Environment 17 2010-07-01 2010-07-01 false Clean Air Act Amendments of 1990 Phaseout Schedule for Production of Ozone-Depleting Substances H Appendix H to Subpart A of Part 82... STRATOSPHERIC OZONE Production and Consumption Controls Pt. 82, Subpt. A, App. H Appendix H to Subpart A of Part...

  8. Modulated diesel fuel injection strategy for efficient-clean utilization of low-grade biogas

    International Nuclear Information System (INIS)

    Wang, Xiaole; Qian, Yong; Zhou, Qiyan; Lu, Xingcai

    2016-01-01

    Highlights: • Influences of direct injection strategy on biogas RCCI mode are researched. • Excessive early pilot injection timing leads to the retard of combustion. • Overall indicated thermal efficiency of low-grade biogas can be higher than 40%. • Pilot injection timing has strong influence on particle size distribution. • Composition of biogas has a great influence on the gas emissions. - Abstract: Recently, as a kind of renewable fuel, low-grade biogas has been researched to apply in internal combustion engine. In this paper, an experimental study was conducted to study the influence of injection strategies on the efficient utilization of low-grade biogas in Reactivity Controlled Compression Ignition (RCCI) mode with port fuel injection of biogas and in-cylinder direct injection of diesel based on a modified electronic controlled high-pressure directly injected compression ignition engine. Considered the high proportion of inert gas in biogas, a four-components simulated gas (H_2:CO:CH_4:N_2 = 5:40:5:50 vol%) has been selected as test fuels to simulate biogas. The effects of several injection control parameters such as pilot injection timing, main injection timing, common rail pressure and pilot injection ratio on the combustion and emissions are analyzed in detail. The research demonstrates that the main injection timing can effectively control the combustion phase and excessive early pilot injection timing leads to retard of combustion. CO emissions are relatively high due to homogenous charge of biogas. NOx and smoke emissions can be effectively controlled. In RCCI mode, the indicated thermal efficiency of biogas/diesel can reach 40%.

  9. LDDX: A High Efficiency Air Conditioner for DOD Buildings

    Science.gov (United States)

    2017-02-01

    Additional Benefits ........................................................................................................ 3 1.2.6 Deliverables...inadequate latent cooling can lead building managers to restrict ventilation to minimal levels that further compromise both the comfort and health of...bulb temperatures for outdoor air and return air respectively per ANSI/AHRI Standard 210/240 “Performance Rating of Unitary Air-Conditioning and Air

  10. Economic and environmental aspects on energy alternatives for a clean air -- wind farms

    Energy Technology Data Exchange (ETDEWEB)

    Calanter, P.; Serban, O. [Bucharest Academy of Economic Studies (Romania). Doctoral School; Dragomir, A. [SC CEPSTRA GRUP SRL, Bucharest (Romania)

    2011-07-01

    Fossil fuels combustion in the energy sector is a major contribution to the generation of greenhouse gases emission (GHG) -- mainly carbon dioxide. Emissions reduction represents an important means to protect the environment and to improve the health status of the population -- the major requirement in the context of a sustainble development strategy -- knowing the association of the greenhouse effect with climate change. Fossil fuels are limited and expensive resources. According to the Romanian National Agency for Mineral Resources (2009), under the current extraction level the national oil and gas resources are industrial exploitable for 15 years, while coal would be available for about 30 years. At present, the alternative of renewable energy -- solar, wind, geothermal, hydro, and biomass -- is becoming more and more attractive at the global scale. The use of renewable energy offers a clean alternative for energy production, which allows considerable reduction in emissions of greenhouse gases, contributing to climate change mitigation efforts, and also savings of fossil fuels limited resources. Wind energy represents an increasingly more attractive alternative in Romania. Regulations concern not only investment and operation of installations, but also energy recovery and environmental protection. Even though the use of the entire national wind energy potential could determine a significant GHG emissions reduction, the technology, infrastructure and environmental restrictions limits wind energy valorization. Wind farms development, sustained by landscape, wind speed distribution and investors financial promotion, competes with the prudence imposed by the potential environmental impact (biodiversity, microclimate, etc), and the lack of historical data and information structuring. Adequate organization and dissemination of relevant information might be valuable for investors and sustainable development strategies. To estimate the GHG emissions reduction in Romania

  11. Challenges of efficient and clean use of fossil fuels for power production

    Energy Technology Data Exchange (ETDEWEB)

    Vortmeyer, Nicolas; Zimmermann, Gerhard

    2010-09-15

    Constantly increasing resource efficiency together with the broad introduction of CCS technologies is fundamental for a continuous use of fossil fuels in power generation against the background of up-coming requirements for CO2 emission reduction. In principle, CCS means up-grading conventional power plant technology with proven CO2 removal processes. However, this leads to additional losses, auxiliary power demand and cost. System integration, development or at least adaption of components and processes are the main requirements in this context. Different technology solutions and recent developments will be addressed as well as challenges when implementing in demonstration projects.

  12. Ultra Clean 1.1MW High Efficiency Natural Gas Engine Powered System

    Energy Technology Data Exchange (ETDEWEB)

    Zurlo, James; Lueck, Steve

    2011-08-31

    Dresser, Inc. (GE Energy, Waukesha gas engines) will develop, test, demonstrate, and commercialize a 1.1 Megawatt (MW) natural gas fueled combined heat and power reciprocating engine powered package. This package will feature a total efficiency > 75% and ultra low CARB permitting emissions. Our modular design will cover the 1 – 6 MW size range, and this scalable technology can be used in both smaller and larger engine powered CHP packages. To further advance one of the key advantages of reciprocating engines, the engine, generator and CHP package will be optimized for low initial and operating costs. Dresser, Inc. will leverage the knowledge gained in the DOE - ARES program. Dresser, Inc. will work with commercial, regulatory, and government entities to help break down barriers to wider deployment of CHP. The outcome of this project will be a commercially successful 1.1 MW CHP package with high electrical and total efficiency that will significantly reduce emissions compared to the current central power plant paradigm. Principal objectives by phases for Budget Period 1 include: • Phase 1 – market study to determine optimum system performance, target first cost, lifecycle cost, and creation of a detailed product specification. • Phase 2 – Refinement of the Waukesha CHP system design concepts, identification of critical characteristics, initial evaluation of technical solutions, and risk mitigation plans. Background

  13. Dual-Fuel Combustion for Future Clean and Efficient Compression Ignition Engines

    Directory of Open Access Journals (Sweden)

    Jesús Benajes

    2016-12-01

    Full Text Available Stringent emissions limits introduced for internal combustion engines impose a major challenge for the research community. The technological solution adopted by the manufactures of diesel engines to meet the NOx and particle matter values imposed in the EURO VI regulation relies on using selective catalytic reduction and particulate filter systems, which increases the complexity and cost of the engine. Alternatively, several new combustion modes aimed at avoiding the formation of these two pollutants by promoting low temperature combustion reactions, are the focus of study nowadays. Among these new concepts, the dual-fuel combustion mode known as reactivity controlled compression ignition (RCCI seems more promising because it allows better control of the combustion process by means of modulating the fuel reactivity depending on the engine operating conditions. The present experimental work explores the potential of different strategies for reducing the energy losses with RCCI in a single-cylinder research engine, with the final goal of providing the guidelines to define an efficient dual-fuel combustion system. The results demonstrate that the engine settings combination, piston geometry modification, and fuel properties variation are good methods to increase the RCCI efficiency while maintaining ultra-low NOx and soot emissions for a wide range of operating conditions.

  14. Compliance with the Clean Air Act Amendments: Challenge of the 90's

    International Nuclear Information System (INIS)

    Odegard, G.J.; Van, H.

    1993-01-01

    With its 17,593 miles of pipeline, El Paso Natural Gas Company is one of the country's largest interstate natural gas transmission companies. To keep the gas continually moving through the pipeline, it is compressed back to high pressures at 73 stations comprising 1,210,120 horsepower located along the pipeline route. These compressor stations, which operate 24 hours a day every day, house 316 reciprocating engines and 92 gas turbines. As fuel, these engines and turbines burn natural gas. Natural gas combustion releases emissions of nitrogen oxides and carbon monoxide with small amounts of particulates, sulfur dioxide and volatile organic compounds. This presentation will describe how one large energy company plans to comply with these new requirements over the next several years. El Paso has developed an extensive Air Program designed to obtain all needed operating permits by the November 1995 deadline. Work is underway to quantify and document emissions at every operating facility. Emissions tests will measure NOx, CO, oxygen, CO 2 , water, stack temperature, stack velocity and fuel flow rate. Data generated by the Emissions Inventory System will be used not only for permit applications, but to develop alternative emission reduction strategies at facilities located in nonattainment areas. Dispersion modeling will be performed to analyze compliance with PSD increments and National Ambient Air Quality Standards

  15. Clean air benefits and costs in the GVRD [Greater Vancouver Regional District

    International Nuclear Information System (INIS)

    Gislason, G.; Martin, J.; Williams, D.; Caton, B.; Rich, J.; Rojak, S.; Robinson, J.; Stuermer, A. von

    1994-01-01

    Air pollution is a major concern in the Greater Vancouver Regional District in British Columbia. An analysis was conducted to assess the costs and benefits of an innovative plan to reduce the emissions of five primary pollutants in the GVRD: nitrogen oxides (NOx), sulfur oxides (SOx), volatile organic compounds (VOCs), particulates, and CO. The study adopts a damage function approach in which the benefits of reduced emissions are given by the averted damages to human health, crops, and so on. Under a base case scenario, motor vehicle emission controls and additional measures proposed in the region's air quality management plan (AQMP) are projected to lead to emission reductions of 873,000 tonnes in the GVRD by the year 2020, compared to the emission level projected without intervention. The AQMP is projected to avert over its life some 2,800 premature deaths, 33,000 emergency room visits, 13 million restricted activity days, and 5 million symptoms. Crop losses due to ozone are projected to decrease by 1-4%/y over the next several decades due to the AQMP. Damage averted to materials and property per tonne of pollutant reduced ranges from $30 for VOC to $180 for particulates. Under base-case conservative assumptions, the AQMP generates $5.4 billion in benefits and $3.8 billion in costs, nearly 2/3 of which are paid by the industrial and commercial sectors. 1 tab

  16. Autothermal upgrading of biomass and wastes for clean and efficient production of power

    Energy Technology Data Exchange (ETDEWEB)

    Rafal Kobylecki; Zbigniew Bis; Wojciech Nowak [Czestochowa University of Technology (Poland)

    2005-07-01

    In this paper it is demonstrated that the main barrier of large scale heat and electricity production from biomass may be significantly reduced or eliminated by fuel upgrading and thermal treatment in a specially-designed pilot plant autothermal reactor. The process does not require significant amount of additional energy, since the whole process is run autothermal. The process final products are hot flue gases and a solid residue called a 'biocarbon' of LHV of roughly 28 MJ/kg. The properties of the biocarbon were similar, regardless of the input raw fuel type (biomass, waste, sewage sludge, energy crops, etc.). The use of the biocarbon for direct co-combustion with coal does not require installation of any additional feeding or fuel treatment systems at the power plants. Apart from its possible direct combustion, the biocarbon can be also efficiently used as a promising solid energy carrier for other processes (e.g. fuel cells). 6 refs., 6 figs.

  17. Measurements of free radicals in a megacity during the Clean Air for London Project

    Science.gov (United States)

    Heard, Dwayne; Whalley, Lisa; Stone, Daniel; Clancy, Noel; Lee, James; Kleffman, Jorg; Laufs, Sebastian; Bandy, Brian

    2013-04-01

    Free radicals control the photo-oxidative chemistry of the atmosphere, being responsible for the transformation of primary emissions into secondary pollutants such as NO2, O3, multifunctional species and particulates. Here we present measurements of OH, HO2 and RO2 radicals and OH reactivity recorded at North Kensington, Central London, during two Intensive Operational Periods (IOPs) of the Clear Air for London (Clearflo) project in the summer and winter of 2012. OH and HO2 were measured using laser-induced fluorescence (LIF) spectroscopy at low pressure (the FAGE technique), and RO2 was measured using the recently developed ROXLIF technique, which utilises an external flow-reactor interfaced to FAGE, and which is able to discriminate between HO2 and organic peroxy radicals. Through control of reagent gases we are further able to provide a separate measurement of those RO2 species which are known to give an interference for HO2 measurements (namely alkene, aromatic and large-chain alkane derived RO2). OH reactivity was measured using laser-flash photolysis combined with FAGE. Low concentrations of radicals were observed during the winter IOP, with mixing ratios of [OH] ~ 0.04 pptv, [HO2] ~ 0.4 pptv, and [RO2] ~ 1.6 pptv at noon, all displaying a negative correlation with NO. The photolysis of O3 and subsequent reaction of O(1D) with H2O vapour was only a minor contribution to radical production in winter, with photolysis of HONO a major radical source. The summer IOP coincided with the London Olympic Games, with a number of pollution events, with ozone peaking at 100 ppbv (exceeding EU air quality directives) and elevated radical concentrations (peak [OH] ~ 0.14 pptv, [HO2] ~ 4 pptv, [RO2] ~ 6.4 pptv) being observed. The net rate of ozone production was calculated from radical observations and agreed well with measured ozone production, suggesting that advection/dilution by continental air-masses was not playing a significant role in determining ozone

  18. More than clean air and tranquillity: Residential green is independently associated with decreasing mortality.

    Science.gov (United States)

    Vienneau, Danielle; de Hoogh, Kees; Faeh, David; Kaufmann, Marco; Wunderli, Jean Marc; Röösli, Martin

    2017-11-01

    Green space may improve health by enabling physical activity and recovery from stress or by decreased pollution levels. We investigated the association between residential green (greenness or green space) and mortality in adults using the Swiss National Cohort (SNC) by mutually considering air pollution and transportation noise exposure. To reflect residential green at the address level, two different metrics were derived: normalised difference vegetation index (NDVI) for greenness, and high resolution land use classification data to identify green spaces (LU-green). We used stratified Cox proportional hazard models (stratified by sex) to study the association between exposure and all natural cause mortality, respiratory and cardiovascular disease (CVD), including ischemic heart disease, stroke and hypertension related mortality. Models were adjusted for civil status, job position, education, neighbourhood socio-economic position (SEP), geographic region, area type, altitude, air pollution (PM 10 ), and transportation noise. From the nation-wide SNC, 4.2 million adults were included providing 7.8years of follow-up and respectively 363,553, 85,314 and 232,322 natural cause, respiratory and CVD deaths. Hazard ratios (and 95%-confidence intervals) for NDVI [and LU-green] per interquartile range within 500m of residence were highly comparable: 0.94 (0.93-0.95) [0.94 (0.93-0.95)] for natural causes; 0.92 (0.91-0.94) [0.92 (0.90-0.95)] for respiratory; and 0.95 (0.94-0.96) [0.96 (0.95-0.98)] for CVD mortality. Protective effects were stronger in younger individuals and in women and, for most outcomes, in urban (vs. rural) and in the highest (vs. lowest) SEP quartile. Estimates remained virtually unchanged after incremental adjustment for air pollution and transportation noise, and mediation by these environmental factors was found to be small. We found consistent evidence that residential green reduced the risk of mortality independently from other environmental

  19. Cleaning the Air and Improving Health with Hydrogen Fuel-Cell Vehicles

    Science.gov (United States)

    Jacobson, M. Z.; Colella, W. G.; Golden, D. M.

    2005-06-01

    Converting all U.S. onroad vehicles to hydrogen fuel-cell vehicles (HFCVs) may improve air quality, health, and climate significantly, whether the hydrogen is produced by steam reforming of natural gas, wind electrolysis, or coal gasification. Most benefits would result from eliminating current vehicle exhaust. Wind and natural gas HFCVs offer the greatest potential health benefits and could save 3700 to 6400 U.S. lives annually. Wind HFCVs should benefit climate most. An all-HFCV fleet would hardly affect tropospheric water vapor concentrations. Conversion to coal HFCVs may improve health but would damage climate more than fossil/electric hybrids. The real cost of hydrogen from wind electrolysis may be below that of U.S. gasoline.

  20. Photocatalytic equipment with nitrogen-doped titanium dioxide for air cleaning and disinfecting

    International Nuclear Information System (INIS)

    Le, Thanh Son; Ngo, Quoc Buu; Nguyen, Viet Dung; Nguyen, Hoai Chau; Dao, Trong Hien; Tran, Xuan Tin; Kabachkov, E N; Balikhin, I L

    2014-01-01

    Nitrogen-doped TiO 2 nanoparticle photocatalysts were synthesized by a sol–gel procedure using tetra-n-butyl orthotitanate as a titanium precursor and urea as a nitrogen source. Systematic studies for the preparation parameters and their impact on the material's structure were carried out by multiple techniques: thermogravimetric and differential scanning calorimetric analysis, x-ray diffraction, scanning electron microscope, transmission electron microscopy, energy dispersive x-ray spectroscopy and UV–Vis diffuse reflectance spectrophotometry showed that the nitrogen-doped TiO 2 calcined at 500 °C for 3 h exhibited a spherical form with a particle size about 15–20 nm and crystal phase presented a mixture of 89.12% anatase. The obtained product was deposited on a porous quartz tube (D = 74 mm; l = 418 mm) to manufacture an air photocatalytic cleaner as a prototype of the TIOKRAFT company's equipment. The created air cleaner was able to remove 60% of 10 ppm acetone within 390 min and degrade 98.5% of bacteria (total aerobic bacteria and fungi, 300 cfu m −3 ) within 120 min in a 10 m 3 box. These photodegradation activities of N-TiO 2 are higher than that of the commercial nano-TiO 2 (Skyspring Inc., USA, particle size of 5–10 nm). (paper)