WorldWideScience

Sample records for condenser tube alloys

  1. Investigation of impingement attack mechanism of copper alloy condenser tubes

    Energy Technology Data Exchange (ETDEWEB)

    Fukumura, Takuya; Nakajima, Nobuo; Arioka, Koji; Totsuka, Nobuo; Nakagawa, Tomokazu [Institute of Nuclear Safety System Inc., Mihama, Fukui (Japan)

    2001-09-01

    In order to investigate generation and growth mechanisms of impingement attacks of sea water against copper alloy condenser tubes used in condensers of nuclear power plants, we took out condenser tubes from actual condensers, cut them into several pieces and carried out several material tests mainly for impinged spots. In addition water flow inside of a pit was analyzed. From the results of the investigation, it was found that all of impingement attacks were found in the marks left by sessile organisms and none were found in downstream of the marks as frequently proposed so far. At the pits generated inside the marks, iron coating was striped and zinc content was deficient in some cases. Combining these data and the result of flow analysis, we considered the following mechanism of the impingement attacks: sessile organisms clinging to the surface of the condenser tube and growth, occlusion of the tube, extinction and decomposition of sessile organisms, pollution corrosion under the organisms and cavity formation, occlusion removal by the cleaning, generation of impingement attacks by flow collision inside the cavity, growth of the impingement attacks. (author)

  2. Study on corrosion of thermal power plant condenser tubes

    Energy Technology Data Exchange (ETDEWEB)

    Mohammadi, Abdolreza Rashidi; Zhaam, Ali Akbar [Niroo Research Institute, end of Poonak Bakhtari blvd., Shahrak Ghods, Tehran (Iran)

    2004-07-01

    The aim of this investigation is to study kinds of corrosion mechanisms in thermal power plant condenser tubes. Condenser is a shell and tube heat exchanger in which cooling water flows through its tubes. While the steam from low pressure turbine passes within condenser tubes, it is condensed by cooling water. The exhausted steam from low pressure turbine is condensed on external surface of condenser tubes and heat is transferred to cooling water which flow into tubes. Tubes composition is usually copper-based alloys, stainless steel or titanium. Annual damages due to corrosion cause much cost for replacement and repairing metallic equipment and installations in electric power industry. Because of existence of different contaminants in water and steam cycle, condenser tubes surfaces are exposed to corrosion. Contaminants like oxygen, carbon dioxide, chloride ion and ammonia in water and steam cycle originate several damages such as pitting and crevice corrosion, erosion, galvanic attack, SCC, condensed corrosion, de-alloying in thermal power plant condenser. The paper first states how corrosion damage takes place in condensers and then introduces types of usual alloys used in condensers and also their corrosion behavior. In continuation, a brief explanation is presented about kinds of condenser failures due to corrosion. Then, causes and locations of different mechanisms of corrosion events on condenser tubes and effects of different parameters such as composition, temperature, chloride and sulfide ion concentration, pH, water velocity and biological precipitation are examined and finally protection methods are indicated. Also some photos of tubes specimens related to power plants are studied and described in each case of mentioned mechanisms. (authors)

  3. Titanium condenser tubes. Problems and their solution for wider application to large surface condensers. [PWR

    Energy Technology Data Exchange (ETDEWEB)

    Sato, S; Sugiyama, S; Nagata, K; Nanba, K; Shimono, M [Sumitomo Light Metal Industries Ltd., Tokyo (Japan)

    1977-06-01

    The corrosion resistance of titanium in sea water is extremely excellent, but titanium tubes are expensive, and the copper alloy tubes resistant in polluted sea water were developed, therefore they were not used practically. In 1970, ammonia attack was found on the copper alloy tubes in the air-cooled portion of condensers, and titanium tubes have been used as the countermeasure. As the result of the use, the galvanic attack on copper alloy tube plates with titanium tubes as cathode and the hydrogen absorption at titanium tube ends owing to excess electrolytic protection was observed, but the corrosion resistance of titanium tubes was perfect. These problems can be controlled by the application of proper electrolytic protection. The condensers with all titanium tubes adopted recently in USA are intended to realize perfectly no-leak condensers as the countermeasure to the corrosion in steam generators of PWR plants. Regarding large condensers of nowadays, three problems are pointed out, namely the vibration of condenser tubes, the method of joining tubes and tube plates, and the tubes of no coolant leak. These three problems in case of titanium tubes were studied, and the problem of the fouling of tubes was also examined. The intervals of supporting plates for titanium tubes should be narrowed. The joining of titanium tubes and titanium tube plates by welding is feasible and promising. The cleaning with sponge balls is effective to control fouling.

  4. Titanium condenser tubes--problems and their solutions for wider application to large surface condensers

    Energy Technology Data Exchange (ETDEWEB)

    Sato, S; Sugiyama, Y; Nagata, K; Namba, K; Shimono, M

    1978-01-01

    To meet the demand for high reliability condensers for thermal and nuclear power plants, especially for PWR plants, the condensers installed entirely with titanium tubes have been investigated and used. Some difficulties from conventional copper alloy tubes exist. Further investigations are necessary on three items: (1) tube vibration; (2) joining tubes to tube plate; (3) fouling (bio-fouling) control. Literature survey on the tube vibration suggests that the probability of tube vibration due to decreased stiffness of titanium tubes in comparison with conventional copper alloy tubes can be decreased by designing the proper span length between supports. Experiments on seal welding of tubes to a tube plate have successfully proved that pulsed TIG arc welding is applicable to get reliable and strong joints, even on site, by suitable countermeasures. Experiments on the fouling (bio-fouling) of titanium tubes in marine application reveal that the increased fouling of titanium tubes could be controlled by proper application of sponge ball cleaning.

  5. Condensate subcooling near tube exit during horizontal in-tube condensation

    International Nuclear Information System (INIS)

    Hashizume, K.; Abe, N.; Ozeki, T.

    1992-01-01

    In-tube condensation is encountered in various applications for heat exchangers, such as domestic air-conditioning equipment, industrial air-cooled condensers, and moisture separator reheaters (MSRs) for nuclear power pants. Numerous research work has been conducted to predict the condensation heat transfer coefficient, and we have now enough information for thermal design of heat exchangers with horizontal in-tube condensation. Most of the research is analytical and/or experimental work in the annular or stratified flow regime, or experimental work on bulk condensation, i.e., from saturated vapor to complete condensation. On the other hand, there exist few data about the heat transfer phenomena in the very lower-quality region near the tube exit. The purpose of this paper is to clarify the condensation heat transfer phenomena near the tube exit experimentally and analytically, and to predict the degree of condensate subcooling

  6. The use of titanium for condenser tube bundles

    International Nuclear Information System (INIS)

    Dobrovitch, N.

    2002-01-01

    In a power plant, the condenser is a strategic heat exchanger with regards to the efficiency of the steam turbine and its reliability guarantees the performance and continuous operation of the plant. Until the early 1980's, copper alloys were routinely used in condenser tubes, thanks to their high heat transfer rates. Yet numerous problems arose from the use of this material, such as stress cracking corrosion, ammoniacal corrosion, fouling, erosion, dezincification, abrasion, erosion-corrosion,... and lately the problem of inadequateness of copper with nuclear steam generators (in nuclear power plant the abrasion problem of the copper alloy tubes created a deposit problem in the steam generator conducting to the replacement of all the condensers). The trend was then to consider new tube materials, such stainless steel and titanium, firstly for particular operating conditions and now for most of the projects, with several objectives, such as: 1) improve the reliability (titanium in particular can bring major improvements such as higher water velocities promoting better heat coefficients, excellent resistance to abrasion, erosion and corrosion thereby improving resistance to fouling; 2) find more cost-effective solutions. The first investment is higher but money is saved on maintenance costs and on time reliability of the material. Titanium tube manufacturing has greatly evolved for the last 20 years. Tubes are mostly welded tubes from ASTM SB 338 grade 1 made on a continuous manufacturing line. All manufacturing operations (welding, annealing, non-destructive testing) are fully automated to produce high quality tubes in large quantities. The most common way to attach tubes to a tubesheet is to roller expand them. (A.C.)

  7. Analysis of Ruptured Heater Tube of Degasser Condenser in Wolsong Unit 4

    International Nuclear Information System (INIS)

    Kim, Hong Pyo; Kim, J. S.; Lim, Y. S.; Kim, S. S.; Hwang, S. S.; Kim, D. J.; Kim, S. W.; Jeong, M. K.; Hong, J. H.

    2007-08-01

    In a degasser condenser in Wolsong unit 4, the cracks were found in the heater tube no. 6 and no. 7. To avoid additional damages in the specimen during a decontamination process for the previous analysis, the cracks were analyzed without any decontamination process in this work. We performed the investigation of the ruptured surface morphology, the EDS analysis of the ruptured surface, the microstructural analysis of Alloy 800H sheath tube and literature survey to find the failure mechanism. From the results, it was expected that the sheath tube has been exposed in a steam condition as the coolant level was decreased in the degasser condenser, leading to the rupture of the sheath tube

  8. CONDENSATION OF WATER VAPOR IN A VERTICAL TUBE CONDENSER

    Directory of Open Access Journals (Sweden)

    Jan Havlík

    2015-10-01

    Full Text Available This paper presents an analysis of heat transfer in the process of condensation of water vapor in a vertical shell-and-tube condenser. We analyze the use of the Nusselt model for calculating the condensation heat transfer coefficient (HTC inside a vertical tube and the Kern, Bell-Delaware and Stream-flow analysis methods for calculating the shell-side HTC from tubes to cooling water. These methods are experimentally verified for a specific condenser of waste process vapor containing air. The operating conditions of the condenser may be different from the assumptions adopted in the basic Nusselt theory. Modifications to the Nusselt condensation model are theoretically analyzed.

  9. Preventing freezing of condensate inside tubes of air cooled condenser

    International Nuclear Information System (INIS)

    Joo, Jeong A; Hwang, In Hwan; Lee, Dong Hwan; Cho, Young Il

    2012-01-01

    An air cooled condenser is a device that is used for converting steam into condensate by using ambient air. The air cooled condenser is prone to suffer from a serious explosion when the condensate inside the tubes of a heat exchanger is frozen; in particular, tubes can break during winter. This is primarily due to the structural problem of the tube outlet of an existing conventional air cooled condenser system, which causes the backflow of residual steam and noncondensable gases. To solve the backflow problem in such condensers, such a system was simulated and a new system was designed and evaluated in this study. The experimental results using the simulated condenser showed the occurrence of freezing because of the backflow inside the tube. On the other hand, no backflow and freezing occurred in the advanced new condenser, and efficient heat exchange occurred

  10. Operative behaviour of a condenser tube under ETA chemistry

    International Nuclear Information System (INIS)

    Chocron, Mauricio; Burkart, Arturo; Rodriguez, Ivanna; Raul, Manera; Diego, Quinteros

    2012-09-01

    Among the various recommendations for the surveillance of the integrity of the materials of the Secondary Cycle (Balance of Plant) it is the periodic removal of a steam generator tube and a condenser tube and their analysis. It considers assessment of the water chemistry, corrosion and the reciprocal effect on or from other components of the cycle. Embalse N.P.P. is a CANDU 6 type, Pressurized Heavy Water Reactor, located in Cordoba Province, Argentina. Previous papers have shown results on tubes removed from the steam generators (Bordoni et al., NPC'08, September 15-18, 2008, Berlin, Germany; 6 th Canadian Nuclear Society - Steam Generators Conference, November 8-11, 2009, Toronto, Canada). Considering that the Embalse BOP has mixed metallurgy, i.e., steam generator tubes made of A800, piping made of ferrous alloys and condenser tubes made of Admiralty Brass and also taking into account that the chemistry has been modified from Morpholine control to ETA control (Fernandez et. al, NPC'2010, October 3-7, Quebec City, Canada), it has been decided to remove and analyze a condenser tube that has been placed in operation coincidently with the establishment of the ETA chemical control. The extraction is dated along with the November 2011 Plant Programmed Outage. Objectives are assessing the operative behavior of the tube performing visual and optical microscope inspection, SEM analysis of the oxides and deposits in exposed surfaces and occluded locations like tube sheet and other tests as well. Results are compared to the same analysis performed on a new tube in storage and integrated with the chemical operative figures of the cycle during the period: chemical data and corrosion products transport. (authors)

  11. Enhanced Evaporation and Condensation in Tubes

    Science.gov (United States)

    Honda, Hiroshi

    A state-of-the-art review of enhanced evaporation and condensation in horizontal microfin tubes and micro-channels that are used for air-conditioning and refrigeration applications is presented. The review covers the effects of flow pattern and geometrical parameters of the tubes on the heat transfer performance. Attention is paid to the effect of surface tension which leads to enhanced evaporation and condensation in the microfin tubes and micro-channels. A review of prior efforts to develop empirical correlations of the heat transfer coefficient and theoretical models for evaporation and condensation in the horizontal microfin tubes and micro-channels is also presented.

  12. Ferromagnetic material inspection for feedwater heater and condenser tubes

    International Nuclear Information System (INIS)

    Anon.

    1987-01-01

    In recent years, special ferritic stainless steels, such as AL29-4C/sup TM/, Sea-Cure/sup TM/, E-Brite/sup TM/, 439, and similar alloys have been introduced as tube material in condensers, feedwater heaters, moisture separator/reheaters, and other heat exchangers. In addition, carbon steel tubes are widely used in feedwater heaters and heat exchangers in chemical plants. The main problem with the in-service inspection of these ferritic alloys and carbon steel tubes lies in their highly ferromagnetic properties. These properties severely limit the application of the standard eddy current techniques. The effort was undertaken under EPRI sponsorship to develop a reliable technique for in-service inspection of ferromagnetic tubes. The new method combines the measurement of magnetic flux leakage generated around the defects with measurement of total flux in the tube wall. The heart of the inspection system is a special ID probe that magnetizes the tube and generates signals for any tube defect. A permanent record of inspection is provided with a strip-chart or magnetic tape recorder. The laboratory and field evaluation of this new system demonstrated its very good sensitivity to small defects, its reliability, and its ruggedness. Defects as small as 10% external wall loss in heavy wall carbon steel tube were detected. Tubes in the power plant were inspected at a rate of 300-500 tubes per eight-hour shift. The other advantages of this newly developed technique are its simplicity, low cost of instrumentation, easy data interpretation, and full portability

  13. The use of titanium for condenser tube bundles

    International Nuclear Information System (INIS)

    Dobrowitch, Nicolas

    2003-01-01

    In a power plant, the condenser is a strategic heat exchanger with regards to the efficiency of the steam turbine and its reliability guarantees the performance and continuous operation of the plant. Until the early 1980s, copper alloys were routinely used in condenser tubes, thanks to their high heat transfer rates. Yet, numerous problems arose from the use of this material, such as stress corrosion cracking, ammoniacal corrosion, fouling, erosion, dezincification, abrasion, erosion-corrosion, etc. and lately the problem of the inadequacy of copper with nuclear steam generators. The trend was then to consider new tube materials, such as stainless steel and titanium, at first for particular operating conditions and now for most of the projects, with several objectives, such as: improving reliability (titanium in particular can bring major improvements including higher water velocities promoting better heat transfer coefficients, and excellent resistance to abrasion, erosion and corrosion thereby improving resistance to fouling); finding more cost-effective solutions. The first investment is higher but money is saved on maintenance costs and on time reliability of the material. (orig.)

  14. Condenser tube buckling within tube-tubesheet joints

    International Nuclear Information System (INIS)

    Willertz, L.E.; Kalnins, A.; Updike, D.P.

    1991-01-01

    The problem of the appearance of protrusions, or bumps, in the interior of roller-expanded tubes within a tubesheet is addressed. Such bumps have been observed in condensers of power plants. A brief history of the reported occurrences of the bumps is given. The hypothesis is advanced that the mechanics of the formation of the bumps is similar to a buckling problem that has 'bifurcation at infinity'. Following this hypothesis, a two-dimensional physical model is developed, and the application of this model to study a three-dimensional bump is proposed. It is proposed in this paper that an initial deviation from the circular shape of the tube required to produce a bump. It is shown that without such a deviation the tubes cannot buckle. An experiment with short tube segments has been performed that verifies some of the features of the observed condenser tube bumps. Exactly what force produced the initial deviation for the observed bumps is still unknown. Available evidence implicates the hydro-laser jet that is used in the cleaning of tubes and tubesheets. A scenario of how a bump could have been produced by the hydro-laser jet is proposed. (author)

  15. Condensation Analysis of Steam/Air Mixtures in Horizontal Tubes

    International Nuclear Information System (INIS)

    Lee, Kwon Yeong; Bae, Sung Won; Kim, Moo Hwan

    2008-01-01

    Perhaps the most common flow configuration in which a convective condensation occurs is a flow in a horizontal circular tube. This configuration is encountered in air-conditioning and refrigeration condensers as well as condensers in Rankine power cycles. Although a convective condensation is also sometimes contrived to occur in a co-current vertical downward flow, a horizontal flow is often preferred because the flow can be repeatedly passed through the heat exchanger core in a serpentine fashion without trapping liquid or vapor in the return bends. Many researchers have investigated a in-tube condensation for horizontal heat exchangers. However, almost all of them obtained tube section-averaged data without a noncondensable gas. Recently, Wu and Vierow have experimentally studied the condensation of steam in a horizontal heat exchanger with air present. In order to measure the condenser tube inner surface temperatures and to calculate the local heat fluxes, they developed an innovative thermocouple design that allowed for nonintrusive measurements. Here we developed a theoretical model using the heat and mass analogy to analyze a steam condensation with a noncondensable gas in horizontal tubes

  16. Biofouling and its prevention in condenser tubes

    Energy Technology Data Exchange (ETDEWEB)

    Mimura, K; Minamoto, K; Kyohara, S [Kobe Steel Ltd. (Japan). Central Research and Development Lab.

    1979-04-01

    In this paper, biofouling in condenser tubes and methods of prevention are described. Biofouling has a tendency to occur in tubes under lower velocity of sea water, and fouling organisms, if allowed to build up, cannot be removed by ordinary nylon brush cleaning. As the results of our investigation, it was concluded that sponge ball cleaning should be employed when the condenser is operated under lower velocity of sea water in the bacteria breeding season.

  17. Externally fired gas turbine cycles with high temperature heat exchangers utilising Fe-based ODS alloy tubing

    International Nuclear Information System (INIS)

    Olsson, F.; Svensson, S.-A.; Duncan, R.

    2001-01-01

    This work is part of the BRITE / EuRAM Project 'Development of Torsional Grain Structures to Improve Biaxial Creep Performance of Fe-based ODS Alloy Tubing for Biomass Power Plant'. The main goal of this project is to heat exchanger tubes working at 1100 o C and above. The paper deals with design implications of a biomass power plant, using an indirectly fired gas turbine with a high temperature heat exchanger containing Fe-based ODS alloy tubing. In the current heat exchanger design, ODS alloy tubing is used in a radiant section, using a bayonet type tube arrangement. This enables the use of straight sections of ODS tubing and reduces the amount of material required. In order to assess the potential of the power plant system, thermodynamic calculations have been conducted. Both co-generation and condensing applications are studied and results so far indicate that the electrical efficiency is high, compared to values reached by conventional steam cycle power plants of the same size (approx. 5 MW e ). (author)

  18. Analytical study of condensation heat transfer on titanium tube with super-hydrophobic surface

    Energy Technology Data Exchange (ETDEWEB)

    Ji, Dae Yun; Park, Hyun Gyu; Lee, Kwon Yeong [Handong Global University, Pohang (Korea, Republic of)

    2016-05-15

    There are many nuclear or fossil power plants which occupy more than 85% among entire power plants in the world. These plants release heat through condenser into nature. The condenser is an important component for cooling the working fluid after the turbine. Its performance is related with material and size of its tubes. To have good performance or to reduce condenser size, it is important to increase condensation heat transfer coefficient on condenser tubes. Ma et al. executed heat transfer experiment in dropwise condensation with non-condensable gas, and studied how the amount of air and pressure difference affect condensation heat transfer coefficient. The more non-condensable gas existed, the condensation heat transfer coefficient was decreased. Shen et al. studied condensation heat transfer at horizontal bundle tubes. Several variables such as coolant velocity, saturated pressure, and surface conditions were studied. As a result, surface modified brass tube and stainless tube showed higher condensation heat transfer coefficient as much as 1.3 and 1.4 times comparing with their bare tubes, in 70 kPa vacuum condition respectively. Rausch et al. studied dropwise condensation on ion-implanted titanium surface. Experimental study is performed to evaluate the performance of surface modified titanium tube in vacuum state. SAM coating is used to make super-hydrophobic surface of titanium tube. Preliminary analysis were performed considering filmwise and dropwise condensations, respectively. Experiment facility is almost prepared and the test result will be shown soon.

  19. Signal characteristics of guided wave for condenser tube of NPP

    International Nuclear Information System (INIS)

    Min, Lee Dong; Hoon, Choi Sang; Yeong, Yang Tae

    2012-01-01

    A Condenser is a large heat exchanger of the shell and tube type. Cooling water enters through the water box, through the tubesheet and into the tubes(about 80,000 tubes/unit). The shell side of the condenser receives steam from the low pressure turbines exhaust. The steam is cooled to a liquid by passing over the tubes where the cooling water is circulated. Because seawater is used as a coolant, condenser tubes are easily damaged. For such a reason, nondestructive testing conducted periodically. But nondestructive testing takes a lot of manpower and time. Guided wave technique can overcome these shortcomings. In this study, we made an effort evaluating a guided wave defect signal

  20. A Study on Condensation Heat Transfer at the Exterior Surface of S.A.M. Coated Titanium Tube Using in Steam Condensers

    Energy Technology Data Exchange (ETDEWEB)

    Im, Sung-Gu; Lee, Sang-Hyup; Ji, Dae-Yun; Park, Hyun-Gyu; Lee, Kwon-Yeong [Handong Global University, Pohang (Korea, Republic of)

    2016-10-15

    Condensation occurs when the temperature of a steam is reduced below its saturation temperature. There exist two forms of condensation on cooling surface: dropwise, and film condensations. Usually, dropwise condensation has a better heat transfer performance than film condensation, but it has limit of short period. Ma et al. executed heat transfer experiment in dropwise condensation with non-condensable gas, and studied how the amount of air and pressure difference affect condensation heat transfer coefficient. The more non-condensable gas exist, the condensation heat transfer coefficient is decreased. As a result, surface modified brass tube and stainless tube showed higher condensation heat transfer coefficient as much as 1.3 and 1.4 times comparing with their bare tubes in 70 kPa vacuum condition respectively. Most of power plants use sea water as coolant, so the surface of metal tubes could be corroded by the coolant. We had researched an experimental study related to condensation heat transfer on surface modified titanium tube. Our experimental facility was designed to show how two kinds of tube's heat transfer performances are different in a same condition. We changed the range of saturation pressure and coolant flow rate to observe tube's performance change. When saturation pressure and coolant flow rate increase, overall heat transfer coefficients were increased. When residue of non-condensable gases was decreased, the overall heat transfer coefficients were increased. S.A.M. coated tube's overall heat transfer coefficients were lower than those of bare tube, because the droplets didn't have a tendency of frequently falling down.

  1. Specification of steam generator, condenser and regenerative heat exchanger materials for nuclear applications

    International Nuclear Information System (INIS)

    Jovasevic, J.V.; Stefanovic, V.M.; Spasic, Z.LJ.

    1977-01-01

    The basic standards specifications of materials for nuclear applications are selected. Seamless Ni-Cr-Fe alloy Tubes (Inconel-600) for steam generators, condensers and other heat exchangers can be employed instead of austenitic stainless steal or copper alloys tubes; supplementary requirements for these materials are given. Specifications of Ni-Cr-Fe alloy plate, sheet and strip for steam generator lower sub-assembly, U-bend seamless copper-alloy tubes for heat exchanger and condensers are also presented. At the end, steam generator channel head material is proposed in the specification for carbon-steel castings suitable for welding

  2. Heat transfer performance of condenser tubes in an MSF desalination system

    International Nuclear Information System (INIS)

    Galal, T.; Kalendar, A.; Al Saftawi, A.; Zedan, M.

    2010-01-01

    The present research examines the amount of condensed fresh water off the outer-side surface of heat exchangers in an MSF system. The quantitative modeling of condensed water on the outer surface of comparable tubes, enhanced and plain, in a simulated MSF technique is investigated. An adapted simulation design on a test-rig facility, accounting for the condenser tubing in actual industrial desalination plate-form, is used with corrugated and smooth aluminum-brass material tubes 1100mm long and 23mm bore. A single phase flow of authentic brine water that typifies real fouling is utilized to simulate the actual environmental life of a multi-stage flashing desalination system, with coolant flow velocity 0.1 m/s in the two delineated types of condenser tubing. It is demonstrated that the condensate water amount from the specified enhanced tube is about 1.22 times the condensate water amount from the smooth tube, adaptive for 140 running hours under deliberated constrains. The topic covers a comparative analysis of thermal performance. Comparing results with fresh water confirm the effect of fouling on significantly lowering the value of the overall heat transfer coefficient versus time. Fouling resistance R f is reported with the critical coolant flow speed of 0.1 m/s. Comparison between the fouling resistance for both smooth and corrugated tubes versus time is performed. The fouling thermal resistance of the corrugated tube is 0.56 of the fouling thermal resistance of the smooth tube after140 running hours of the experiment are concluded. Overall, in the case of real brine, results prove that heat performance for the corrugated tube is superior to the plain tube over the studied time period (140 hrs) for the chosen range of flow speeds

  3. Assessment of RELAP5/MOD3.3 condensation models for the tube bundle condensation in the PCCS of ESBWR

    International Nuclear Information System (INIS)

    Zhou, W.; Wolf, B.; Revankar, S.T.

    2011-01-01

    The passive containment condenser system (PCCS) in an ESBWR reactor consists of vertical tube bundle submerged in a large pool of water. The condensation model for the PCCS in a thermalhydraulics code RELAP5/MOD3.3 consists of the default Nusselt model and an alternate condensation model from UCB condensation correlation. An assessment of the PCCS condensation model in RELAP5/MOD3.3 was carried out using experiments conducted on a single tube and tube bundle PCCS tests at Purdue University. The experimental conditions were simulated with the default and the alternate condensation models in the REALP5/MOD3.3 beta version of the code. The default model and the UCB model (alternate model) give quite different results on condensation heat transfer for the PCCS. The default model predicts complete condensation well whereas the UCB model predicts the through flow condensation well. Based on this study it was found that none of the models in REALP5 can predict complete condensation as well as the through flow condensation well. (author)

  4. Assessment of RELAP5/MOD3.3 condensation models for the tube bundle condensation in the PCCS of ESBWR

    Energy Technology Data Exchange (ETDEWEB)

    Zhou, W., E-mail: wenzzhou@cityu.edu.hk [Department of Mechanical and Biomedical Engineering, City University of Hong Kong, Hong Kong (China); Wolf, B. [Purdue University, West Lafayette, IN 47907 (United States); Revankar, S. [Purdue University, West Lafayette, IN 47907 (United States); POSTECH, Pohang (Korea, Republic of)

    2013-11-15

    The passive containment condenser system (PCCS) in an ESBWR reactor consists of vertical tube bundle submerged in a large pool of water. The condensation model for the PCCS in a thermalhydraulics code RELAP5/MOD3.3 consists of the default Nusselt model and an alternate condensation model from UCB condensation correlation. An assessment of the PCCS condensation model in RELAP5/MOD3.3 was carried out using experiments conducted on a single tube and tube bundle PCCS tests at Purdue University. The experimental conditions were simulated with the default and the alternate condensation models in the REALP5/MOD3.3 beta version of the code. The default model and the UCB model (alternate model) give quite different results on condensation heat transfer for the PCCS. The default model predicts complete condensation well whereas the UCB model predicts the through flow condensation well. Based on this study it was found that none of the models in REALP5 can predict complete condensation as well as the through flow condensation well.

  5. Relaxation and corrosion resistance of alloy 800 used for steam generator tubes of ship borne boilers

    International Nuclear Information System (INIS)

    Corrieu, J.M.; Cortial, F.; Maillard, J.L.; Vernot-Loier, C.; Lebeau, M.

    1994-01-01

    The INCO ''INCOLOY 800'' trademark groups the Fe-Cr-Ni alloys containing 30 to 35% nickel, 19 to 23% chromium, 0,15 to 0,60% aluminium, 0,15 to 0,60% titanium and less than 0,10% carbon contents, used as construction materials for condenser and heat exchanger tubes. In parallel with water chemistry control and studies aimed at reducing the residual stresses resulting from tube expansion, studies have been conducted to a better understanding of this alloy, its metallurgy and its corrosion behaviour under accurately defined fabrication and heat treatment conditions. The purpose of this paper is to present the results of a behaviour study of INDRET alloy 800 concerning isothermal relaxation and effects of the said relaxation heat treatments on alloy microstructure studied with a transmission electron-chemical method to determine the sensitiveness to intergranular corrosion, and by electrochemistry in pressurized hot water. (authors). 4 figs., 5 tabs., 7 refs

  6. Improving the thermodynamic efficiency of steam turbine condensers with partial tube replacement and an advanced tube bundle design

    International Nuclear Information System (INIS)

    Drosdziok, A.; Zorner, W.

    1989-01-01

    Many different problems have been experienced with power plant condensers all over the world. It has become apparent that plant availability and cost-effectiveness are significantly influenced by the thermodynamic design of the condensers and the materials selected. This paper reports that by refitting older condensers in operating plants it has proven possible to improve thermodynamic efficiency by changing the tube bundle design. In conjunction with the replacement of the cooper-bearing tubing in these condensers, which became necessary because of the introduction of high AVT (All Volatile Treatment) conditioning in the secondary circuit, it has generally been possible to fulfil the requirements imposed on the condensers without a deterioration of plant efficiency. By experience, best results have been obtained by replacing the condenser bundle with an advanced tube bundle design. Apart from solving all problems, this further improves the thermodynamic efficiency of the condensers. In nuclear power plants constructed by the Siemens KWU Group the condensers are tailored to present-day requirements

  7. A Preliminary Study of Transverse Curvature Effects on Condensation Heat Transfer on Vertical Tube in the Presence of Non-condensable Gas

    Energy Technology Data Exchange (ETDEWEB)

    Lee, Yeon Gun; Kim, Sin [Jeju National Univ., Jeju (Korea, Republic of); Jerng, Dong Wook [Chung Ang Univ., Seoul (Korea, Republic of)

    2013-10-15

    In this study, the effect of the transverse curvature on the condensation HTC on a vertical tube in the presence of air is preliminarily investigated by using the analysis of boundary layer for free convective heat transfer. The results indicate that the heat transfer performance can be enhanced as the outer diameter of condenser tubes is small. To confirm this curvature effect, an experimental program to obtain the condensation heat transfer data for various values of tube diameter is indispensable. Currently, by a joint research project of Jeju National University and Chung-Ang University, a condensation test facility is being designed and constructed to acquire the condensation HTC data as shown in Fig. 3. From a series of experiment on a single vertical tube, the effects of not only the tube diameter but the inclination, the existence of fins and the local velocity of a bulk mixture by natural circulation will be evaluated precisely. An empirical correlation for the condensation heat transfer of a steam-air mixture will also be developed for design optimization and performance evaluation of the PCCS. The Passive Containment Cooling System (PCCS) provides passive means to remove the decay heat and protect the integrity of the containment during severe accidents. Korea, in which all the NPPs employ the concrete containment, may adopt a PCCS using internal condensers. In the event of the loss-of-coolant accident (LOCA), steam released from the reactor coolant system is mixed with air inside the containment and condensed on the outer surface of inclined condenser tubes. It is noted that, among previous theoretical and empirical models for condensation on outer wall in the presence of non-condensable gas, no one took into account the effect of a tube diameter. Though the condensation heat transfer coefficient may vary with transverse curvature of condenser tubes, such a curvature effect has not been reported so far. In this study, a preliminary analysis is conducted

  8. A Preliminary Study of Transverse Curvature Effects on Condensation Heat Transfer on Vertical Tube in the Presence of Non-condensable Gas

    International Nuclear Information System (INIS)

    Lee, Yeon Gun; Kim, Sin; Jerng, Dong Wook

    2013-01-01

    In this study, the effect of the transverse curvature on the condensation HTC on a vertical tube in the presence of air is preliminarily investigated by using the analysis of boundary layer for free convective heat transfer. The results indicate that the heat transfer performance can be enhanced as the outer diameter of condenser tubes is small. To confirm this curvature effect, an experimental program to obtain the condensation heat transfer data for various values of tube diameter is indispensable. Currently, by a joint research project of Jeju National University and Chung-Ang University, a condensation test facility is being designed and constructed to acquire the condensation HTC data as shown in Fig. 3. From a series of experiment on a single vertical tube, the effects of not only the tube diameter but the inclination, the existence of fins and the local velocity of a bulk mixture by natural circulation will be evaluated precisely. An empirical correlation for the condensation heat transfer of a steam-air mixture will also be developed for design optimization and performance evaluation of the PCCS. The Passive Containment Cooling System (PCCS) provides passive means to remove the decay heat and protect the integrity of the containment during severe accidents. Korea, in which all the NPPs employ the concrete containment, may adopt a PCCS using internal condensers. In the event of the loss-of-coolant accident (LOCA), steam released from the reactor coolant system is mixed with air inside the containment and condensed on the outer surface of inclined condenser tubes. It is noted that, among previous theoretical and empirical models for condensation on outer wall in the presence of non-condensable gas, no one took into account the effect of a tube diameter. Though the condensation heat transfer coefficient may vary with transverse curvature of condenser tubes, such a curvature effect has not been reported so far. In this study, a preliminary analysis is conducted

  9. Effect of flow velocity on the process of air-steam condensation in a vertical tube condenser

    Science.gov (United States)

    Havlík, Jan; Dlouhý, Tomáš

    2018-06-01

    This article describes the influence of flow velocity on the condensation process in a vertical tube. For the case of condensation in a vertical tube condenser, both the pure steam condensation process and the air-steam mixture condensation process were theoretically and experimentally analyzed. The influence of steam flow velocity on the value of the heat transfer coefficient during the condensation process was evaluated. For the condensation of pure steam, the influence of flow velocity on the value of the heat transfer coefficient begins to be seen at higher speeds, conversely, this effect is negligible at low values of steam velocity. On the other hand, for the air-steam mixture condensation, the influence of flow velocity must always be taken into account. The flow velocity affects the water vapor diffusion process through non-condensing air. The presence of air significantly reduces the value of the heat transfer coefficient. This drop in the heat transfer coefficient is significant at low velocities; on the contrary, the decrease is relatively small at high values of the velocity.

  10. In-service inspection of condenser tubes by means of electrochemical methods

    International Nuclear Information System (INIS)

    Taelemans, G.

    The commissioning of an increasing number of large nuclear power plants involves an increased significance of such condenser tube problems as: - erosion on tube ends, - generalized corrosion and pitting corrosion, - deposits in the tubes. In order to solve such problems, investigations were performed especially focused on a measurement technique that enables in-service behaviour of condenser tubes to be monitored. For such a purpose, measurement of the polarization resistance has been adopted. The existing corrosion products and scaled-off iron oxides were eliminated by means of a carborundum balls processing, as clearly appears from polarization resistance reduction. Then iron sulphate was injected in order to build a new and better protective layer. In addition, the tube was kept clean by means of foam rubber balls. There is a second implementation area: fouled condenser tubes. A significant polarization resistance reduction is noted during the acid cleaning. (orig.) [de

  11. Assessment of horizontal in-tube condensation models using MARS code. Part I: Stratified flow condensation

    Energy Technology Data Exchange (ETDEWEB)

    Jeon, Seong-Su [Department of Engineering Project, FNC Technology Co., Ltd., Bldg. 135-308, Seoul National University, Gwanak-gu, Seoul 151-744 (Korea, Republic of); Department of Nuclear Engineering, Seoul National University, Gwanak-gu, Seoul 151-744 (Korea, Republic of); Hong, Soon-Joon, E-mail: sjhong90@fnctech.com [Department of Engineering Project, FNC Technology Co., Ltd., Bldg. 135-308, Seoul National University, Gwanak-gu, Seoul 151-744 (Korea, Republic of); Park, Ju-Yeop; Seul, Kwang-Won [Korea Institute of Nuclear Safety, 19 Kuseong-dong, Yuseong-gu, Daejon (Korea, Republic of); Park, Goon-Cherl [Department of Nuclear Engineering, Seoul National University, Gwanak-gu, Seoul 151-744 (Korea, Republic of)

    2013-01-15

    Highlights: Black-Right-Pointing-Pointer This study collected 11 horizontal in-tube condensation models for stratified flow. Black-Right-Pointing-Pointer This study assessed the predictive capability of the models for steam condensation. Black-Right-Pointing-Pointer Purdue-PCCS experiments were simulated using MARS code incorporated with models. Black-Right-Pointing-Pointer Cavallini et al. (2006) model predicts well the data for stratified flow condition. Black-Right-Pointing-Pointer Results of this study can be used to improve condensation model in RELAP5 or MARS. - Abstract: The accurate prediction of the horizontal in-tube condensation heat transfer is a primary concern in the optimum design and safety analysis of horizontal heat exchangers of passive safety systems such as the passive containment cooling system (PCCS), the emergency condenser system (ECS) and the passive auxiliary feed-water system (PAFS). It is essential to analyze and assess the predictive capability of the previous horizontal in-tube condensation models for each flow regime using various experimental data. This study assessed totally 11 condensation models for the stratified flow, one of the main flow regime encountered in the horizontal condenser, with the heat transfer data from the Purdue-PCCS experiment using the multi-dimensional analysis of reactor safety (MARS) code. From the assessments, it was found that the models by Akers and Rosson, Chato, Tandon et al., Sweeney and Chato, and Cavallini et al. (2002) under-predicted the data in the main condensation heat transfer region, on the contrary to this, the models by Rosson and Meyers, Jaster and Kosky, Fujii, Dobson and Chato, and Thome et al. similarly- or over-predicted the data, and especially, Cavallini et al. (2006) model shows good predictive capability for all test conditions. The results of this study can be used importantly to improve the condensation models in thermal hydraulic code, such as RELAP5 or MARS code.

  12. Investigation of enhanced condensation heat transfer outside vertical titanium circularly-grooved tube

    International Nuclear Information System (INIS)

    Zhaorigetu; Huang Weitang; Lv Xiangbo; Liu Feng

    2005-01-01

    The investigation of enhanced condensation heat transfer had been conducted on the outside vertical Titanium circularly-grooved tube. The experimental result indicates that the Titanium circularly-grooved tube is fairly efficient in enhancing the heat transfer. Within the experimental scope, the total heat transfer coefficient of the optimum circularly-grooved tube is 1.12 to 1.36 times of that of the Titanium smooth tube. Through regression analysis on the experimental data, the experimental correlations for the inside heat transfer coefficient, the condensation heat transfer coefficient on film condensation and the friction coefficient were achieved. (authors)

  13. Studies on the causes of failures in titanium tube condensers of nuclear power plants

    International Nuclear Information System (INIS)

    Kim, Uh Chul; Kim, Joung Soo; Jang, Soon Sik; Park, Su Hoon; Chung, Han Sub; Hwang, Seong Sik

    1990-03-01

    All condenser tubes in domestic nuclear power plants using sea water as condenser coolant are Ti material, while water boxes and tubesheets are, respectively, made of carbon steel and Cu-alloys. In this case, to prevent galvanic corrosion occuring between these materials, cathodic protection by an impressed direct current method is being used. Under inappropriate conditions, however, over-protection can generate hydrogen gas on Ti-tube surfaces, which may cause hydrogen embrittlement to the Ti tubes. Therefore, proper conditions for appropriate cathodic protection must be obtained through experiments. Galvanic corrosion between these three different materials was investigated, first. When SA 285 is coupled with Cu or Ti in sea water, under the same surface area, galvanic corrosion rate of SA 285 significantly increases (For example, corrosion rate increment, 2 x 10 -1 → 8 ma for SA 285 coupled with Cu). It was also affected by Cu more than by Ti. In addition, as the surface area ratio of SA 285 to Ti decreases, the corrosion rate of SA 285 increases. This is similar to SA 285-Cu couple. In this case, corrosion rate of SA 285 is higher than that of SA 285-Ti system. For Cu-Ti coulpe, as the surface area ratio of Cu to Ti increases, current density increases slightly up to 1.5 μA/cm 2 , which is very low. (author)

  14. A Local Condensation Analysis Representing Two-phase Annular Flow in Condenser/radiator Capillary Tubes

    Science.gov (United States)

    Karimi, Amir

    1991-01-01

    NASA's effort for the thermal environmental control of the Space Station Freedom is directed towards the design, analysis, and development of an Active Thermal Control System (ATCS). A two phase, flow through condenser/radiator concept was baselined, as a part of the ATCS, for the radiation of space station thermal load into space. The proposed condenser rejects heat through direct condensation of ATCS working fluid (ammonia) in the small diameter radiator tubes. Analysis of the condensation process and design of condenser tubes are based on the available two phase flow models for the prediction of flow regimes, heat transfer, and pressure drops. The prediction formulas use the existing empirical relationships of friction factor at gas-liquid interface. An attempt is made to study the stability of interfacial waves in two phase annular flow. The formulation is presented of a stability problem in cylindrical coordinates. The contribution of fluid viscosity, surface tension, and transverse radius of curvature to the interfacial surface is included. A solution is obtained for Kelvin-Helmholtz instability problem which can be used to determine the critical and most dangerous wavelengths for interfacial waves.

  15. Effect of sponge ball cleaning on removing vernacles in condenser tubes

    International Nuclear Information System (INIS)

    Mimura, Keisuke; Minamoto, Kenju; Kyohara, Shigeru

    1977-01-01

    Usually aluminum brass material is adopted for the condenser tubes in thermal and nuclear power stations today, and sea water is treated with chlorine for the purpose of smooth operation and maintenance, but recently, this treatment tends to be avoided in view of environment preservation. When the chlorine treatment is not carried out, vernacles and other marine living things adhere to the internal surfaces of condenser tubes, and the corrosion of the tubes and the lowering of heat transfer rate occur. In this study, sponge ball cleaning was selected as the method of mechanically removing the adhering living things in tubes. When the balls are used too frequently, the formation of protective film is hindered, and the corrosion of tubes is accelerated, therefore it is important to determine the optimal frequency. The model condenser test and the immersion test of aluminum brass and titanium tubes were carried out. The testing method, the operation record and the test results are reported. Vernacles are apt to adhere to titanium tubes rather than aluminum brass tubes, and in case of aluminum brass tubes, they adhere to those with iron hydroxide film rather than those as manufactured. Vernacles adhere more as the flow speed in tubes is lower and the number of larvae in water is more. It was confirmed that the sponge ball cleaning was extremely effective for removing vernacles. (Kako, I.)

  16. Effect of sponge ball cleaning on removing vernacles in condenser tubes

    Energy Technology Data Exchange (ETDEWEB)

    Mimura, K; Minamoto, K; Kyohara, S [Kobe Steel Ltd. (Japan)

    1977-01-01

    Usually aluminum brass material is adopted for the condenser tubes in thermal and nuclear power stations today, and sea water is treated with chlorine for the purpose of smooth operation and maintenance, but recently, this treatment tends to be avoided in view of environment preservation. When the chlorine treatment is not carried out, vernacles and other marine living things adhere to the internal surfaces of condenser tubes, and the corrosion of the tubes and the lowering of heat transfer rate occur. In this study, sponge ball cleaning was selected as the method of mechanically removing the adhering living things in tubes. When the balls are used too frequently, the formation of protective film is hindered, and the corrosion of tubes is accelerated, therefore it is important to determine the optimal frequency. The model condenser test and the immersion test of aluminum brass and titanium tubes were carried out. The testing method, the operation record and the test results are reported. Vernacles are apt to adhere to titanium tubes rather than aluminum brass tubes, and in case of aluminum brass tubes, they adhere to those with iron hydroxide film rather than those as manufactured. Vernacles adhere more as the flow speed in tubes is lower and the number of larvae in water is more. It was confirmed that the sponge ball cleaning was extremely effective for removing vernacles.

  17. Comparative study during condensation of R152 a and R134 a with presence of non-condensable gas inside a vertical tube

    Science.gov (United States)

    Charef, Adil; Feddaoui, M'barek; Najim, Monssif; Meftah, Hicham

    2018-04-01

    A computational study of the liquid film condensation from vapour-gas mixtures of HFC refrigerants inside a vertical tube is performed. The external wall of the tube is subjected to constant temperature. The model uses an implicit finite difference method to solve the governing equations for the liquid film and gas flow together including the boundary and interfacial matching conditions. Parametric computations were realised to examine the effects of inlet Reynolds number, tube length, and inlet temperature of the gas mixtures on the condensation mechanism. A comparative study between the results obtained for studied R152 a and R134 a with presence of non-condensable gas is made. The predicted results indicate that the condensation of R152 a-air corresponds to a higher accumulated condensation m c d and local heat transfer coefficient h T when compared to R134 a-air in the same conditions. Increasing the inlet Reynolds number or the tube length improve the condensation. Additionally, lower non-condensable gas in R152 a - a i r substantially enhances the heat and mass exchanges.

  18. Theory and design of heat exchanger : shell and tube condenser and reboiler

    International Nuclear Information System (INIS)

    Min, Ui Dong

    1996-02-01

    This book gives descriptions of shell and tube heat exchanger including from, sorts, structure like shell and shell side, channel, and sliding bar, basic design of heat exchanger, flow-induced vibration, shell side condenser, tube side condenser and design of basic structure of condenser by types, selection of reboiler type, kettle type reboiler, internal reboiler, pump through reboiler, design of reboiler like kettle and internal reboiler, and horizontal and vertical thermosyphon reboiler.

  19. Condensation heat transfer coefficients of flammable refrigerants on various enhanced tubes

    International Nuclear Information System (INIS)

    Park, Ki Jung; Jung, Dong Soo

    2005-01-01

    In this study, external condensation Heat Transfer Coefficients (HTCs) of six flammable refrigerants of propylene (R1270), propane (R290), isobutane (R600a), butane (R600), dimethylether (RE170), and HFC32 were measured at the vapor temperature of 39 .deg. C on a 1023 fpm low fin and turbo-C tubes. All data were taken under the heat flux of 32∼116 and 42∼142 kW/m 2 for the low fin and turbo-C tubes respectively. Flammable refrigerants' data obtained on enhanced tubes showed a typical trend that external condensation HTCs decrease with increasing wall subcooling. HFC32 and DME showed up to 30% higher HTCs than those of HCFC22 due to their excellent thermophysical properties. Propylene, propane, isobutane, and butane showed similar or lower HTCs than those of HCFC22. Beatty and Katz' correlation predicted the HTCs of the flammable refrigerants obtained on a low fin tube within a mean deviation of 7.3%. Turbo-C tube showed the best performance due to its 3 dimensional surface geometry for fast removal of condensate

  20. Modelling of Condensation in Vertical Tubes for Passive Safety System

    International Nuclear Information System (INIS)

    Papini, D.; Ricotti, M.; Santini, L.; Grgic, D.

    2008-01-01

    Condensation in vertical tubes plays an important role in the performance of heat exchangers in passive safety systems, widely adopted in next generation reactors. Vertical pipe condensers are implemented in the GE-SBWR1000 Isolation Condenser as well as in the Emergency Heat Removal System (EHRS) of the IRIS reactor. The transient and safety analysis is usually carried out by means of best-estimate, thermalhydraulic codes, as RELAP. Suitable heat transfer correlations are required to duly model the two-phase processes. As far as the condensation process is concerned, RELAP5/MOD3.3 adopts the Nusselt correlation to calculate the heat transfer coefficient in laminar conditions and the Shah correlation for turbulent conditions; the maximum of the predictions from laminar and turbulent regimes is used to calculate the condensation heat transfer coefficient. Shah correlation is generally considered as the best empirical correlation for turbulent annular film condensation, but suitable in proper ranges of the various parameters. Nevertheless, recent investigations have pointed out that its validity is highly questionable for high pressure and large diameter tube applications with water, as should be for the utilization for vertical tube condensers in passive safety systems. Thus, a best-estimate model, based on the theory of film condensation on a plain wall, is proposed. Condensate velocity, expressed in terms of Reynolds number, governs the development of three different regime zones: laminar, laminar wavy and turbulent. The best correlation for each regime (Nusselt's for laminar, Kutateladze's for laminar wavy and Chen's for turbulent) is considered and then implemented in RELAP code. Comparison between the Nusselt-Shah and the proposed model shows substantial differences in heat transfer coefficient prediction. Especially, a trend of increasing value of the heat transfer coefficient with tube abscissa (and quality decreasing) is predicted, when turbulence

  1. Development of zirconium alloy tube manufacturing technology

    International Nuclear Information System (INIS)

    Kim, In Kyu; Park, Chan Hyun; Lee, Seung Hwan; Chung, Sun Kyo

    2009-01-01

    In late 2004, Korea Nuclear Fuel Company (KNF) launched a government funded joint development program with Westinghouse Electric Co. (WEC) to establish zirconium alloy tube manufacturing technology in Korea. Through this program, KNF and WEC have developed a state of the art facility to manufacture high quality nuclear tubes. KNF performed equipment qualification tests for each manufacturing machine with the support of WEC, and independently carried out product qualification tests for each tube product to be commercially produced. Apart from those tests, characterization test program consisting of specification test and characterization test was developed by KNF and WEC to demonstrate to customers of KNF the quality equivalency of products manufactured by KNF and WEC plants respectively. As part of establishment of performance evaluation technology for zirconium alloy tube in Korea, KNF carried out analyses of materials produced for the characterization test program using the most advanced techniques. Thanks to the accomplishment of the development of zirconium alloy tube manufacturing technology, KNF is expected to acquire positive spin off benefits in terms of technology and economy in the near future

  2. Heat transfer performance during in-tube condensation in horizontal smooth, micro-fin and herringbone tubes

    OpenAIRE

    2008-01-01

    M.Ing. An experimental investigation was conducted into the heat transfer characteristics of horizontal smooth, micro-fin and herringbone tubes during in-tube condensation. The study focused on the heat transfer coefficients of refrigerants R-22, R-134a and R-407C inside the three tubes. The herringbone tube results were compared to the smooth and micro-fin tube results. The average increase in the heat transfer coefficient when compared to the smooth tube was found to be as high as 322% w...

  3. The Effect of Condensate Inundation on Steam Condensation Heat Transfer to Wire-Wrapped Tubing.

    Science.gov (United States)

    1983-06-01

    my Thesis Advisor, for his support and patient guidance throughout the project. My sincere appreciation to Dr. A.S. Wanniarachchi, my Second Reader...and perforated tube installation. The tubes were positioned using nylon tube sheets that were attached to the exterior of the condenser end plates. To...Co Tco #5 014 Tt 015 Tsat 016 Tcond 017 T 018 vap 53 IV. PROCEDURES A. INSTALLATION AND OPERATING PROCEDURES 1. 2-r-eparat inDfCndes ubu Prior to

  4. Development of Zirconium alloys (for pressure tubes)

    Energy Technology Data Exchange (ETDEWEB)

    Kim, Young Suk; Kwon, Sang Chul; Choo, Ki Nam; Jung, Chung Hwan; Yim, Kyong Soo; Kim, Sung Soo; Baek, Jong Hyuk; Jeong, Yong Hwan; Kim, Kyong Ho; Cho, Hae Dong [Korea Atomic Energy Research Inst., Daeduk (Korea, Republic of); Hwang, S. K.; Kim, M. H. [Inha Univ., Incheon (Korea, Republic of); Kwon, S. I [Korea Univ., Seoul (Korea, Republic of); Kim, I. S. [Korea Advanced Inst. of Science and Technology, Taejon (Korea, Republic of)

    1997-09-01

    The objective of this research is to set up the basic technologies for the evaluation of pressure tube integrity and to develop improved zirconium alloys to prevent pressure tube failures due to DHC and hydride blister caused by excessive creep-down of pressure tubes. The experimental procedure and facilities for characterization of pressure tubes were developed. The basic research related to a better understanding of the in-reactor performances of pressure tubes leads to noticeable findings for the first time : the microstructural effect on corrosion and hydrogen pick-up behavior of Zr-2.5Nb pressure tubes, texture effect on strength and DHC resistance and enhanced recrystallization by Fe in zirconium alloys and etc. Analytical methodology for the assessment of pressure tubes with surface flaws was set up. A joint research is being under way with AECL to determine the fracture toughness of O-8 at the EOL (End of Life) that had been quadruple melted and was taken out of the Wolsung Unit-1 after 10 year operation. In addition, pressure tube with texture controlled is being made along with VNINM in Russia as a joint project between KAERI and Russia. Finally, we succeeded in developing 4 different kinds of zirconium alloys with better corrosion resistance, low hydrogen pickup fraction and higher creep strength. (author). 121 refs., 65 tabs., 260 figs

  5. Heat exchanger tubing materials for CANDU nuclear generating stations

    International Nuclear Information System (INIS)

    Taylor, G.F.

    1977-07-01

    The performance of steam generator tubing (nickel-chromium-iron alloy in NPD and nickel-copper alloy in Douglas Point and Pickering generating stations) has been outstanding and no corrosion-induced failures have occurred. The primary coolant will be allowed to boil in the 600 MW (electrical) CANDU-PHW reactors. An iron-nickel-chromium alloy has been selected for the steam generator tubing because it will result in lower radiation fields than the alloys used before. It is also more resistant than nickel-chromium-iron alloy to stress corrosion cracking in the high purity water of the primary circuit, an unlikely but conceivable hazard associated with higher operating temperatures. Austenitic alloy and ferritic-austenitic stainless steel tubing have been selected for the moderator coolers in CANDU reactors being designed and under construction. These materials will reduce the radiation fields around the moderator circuit while retaining the good resistance to corrosion in service water that has characterized the copper-nickel alloys now in use. Brass and bronze tubes in feedwater heaters and condensers have given satisfactory service but do, however, complicate corrosion control in the steam cycle and, to reduce the transport of corrosion products from the feedtrain to the steam generator, stainless steel is preferred for feedwater heaters and stainlss steel or titanium for condensers. (author)

  6. MARS-KS Code Assessment for Condensation Heat Transfer in Horizontal Tube with the Presence of Non-Condensable Gas using Purdue Experiment

    International Nuclear Information System (INIS)

    Jeon, Seong Su; Lee, Byung Chul; Park, Ju Yeop; Seul, Kwang Won

    2011-01-01

    In South Korea, advanced power reactor plus (APR+), as a Korean specific reactor, is currently under development for the export strategy. In order to raise competitiveness of the APR+ in the world market, it is necessary to develop the original technology for the improved technology, economics, and safety features. For this purpose, a passive auxiliary feedwater system (PAFS) was adopted as an improved safety design concept of APR+: and then there have been many efforts to develop the PAFS. According to PAFS design concept, PAFS can completely replace the auxiliary feedwater system. When the design basis accident, in which feedwater is unavailable, occurs, the PAFS can remove the residual heat in the core and then prevent the core damage. In the PAFS with the horizontal type heat exchanger, two-phase natural circulation, condensation heat transfer in tube, boiling heat transfer in pool, natural convection in pool, etc. are considered as very important thermalhydraulic phenomena (see Fig. 1). Compared with the vertical heat exchanger from these phenomena, the major difference of the horizontal heat exchanger is the condensation heat transfer phenomena in the tube side. There have been many efforts to understand the condensation heat transfer with in the presence of NC gas in tube but most researches focused on the condensation heat transfer in vertical tube. Therefore the details of the condensation heat transfer in the presence of NC gas in horizontal condenser tubes are not well understood. In order to develop the safety evaluation system for APR+ PAFS, it is required to evaluate the capability and applicability of the MARS-KS code for modeling the condensation heat transfer in the horizontal tube with NC gas because many heat transfer correlations in MARS-KS are known to have much uncertainty. In particular, there is no reliable model for the condensation phenomena in horizontal tube with NC gas. In order to assess the MARS-KS code results and identify the

  7. Heat transfer with geometric shape of micro-fin tubes (I) - Condensing heat transfer

    Energy Technology Data Exchange (ETDEWEB)

    Kwak, K M; Chang, J S; Bai, C H; Chung, M [Yeungnam University, Kyungsan (Korea)

    1999-11-01

    To examine the enhancement mechanism of condensing heat transfer through microfin tube, the condensation experiments with refrigerant HCFC 22 are performed using 4 and 6 kinds of microfin tubes with outer diameter of 9.52 mm and 7.0 mm, respectively. Used microfin tubes have different shape and number of fins with each other. The main heat transfer enhancement mechanism is known to be the enlargement of heat transfer area and turbulence promotion. Together with these main factors, we can find other enhancement factors by the experimental data, which are the overflow of the refrigerant over the microfin and microfin arrangement. The overflow of the refrigerant over the microfin can be analyzed by the geometric shape of the microfin. microfin tubes having a shape which can give much overflow over the microfin show large condensing heat transfer coefficients. The effect of microfin arrangement is related to the heat transfer resistance of liquid film of refrigerant. The condensing heat transfer coefficients are high for the microfin tube with even distribution of liquid film. 17 refs., 14 figs., 3 tabs.

  8. Mixed convection heat transfer between a steam / non-condensable gas mixture and an inclined finned tube bundle

    Energy Technology Data Exchange (ETDEWEB)

    Cachard, F. de; Lomperski, S.; Monauni, G.R. [Paul Scherrer Inst. (PSI), Villigen (Switzerland). Lab. for Thermal-Hydraulics

    1999-07-01

    An experimental and analytical program was performed at PSI to study the performance of a finned-tube condenser in the presence of non-condensable gases at low gas mass fluxes. The model developed for this application includes mixed convection heat transfer between the vapour/non-condensable mixture and the finned-tubes, heat conduction through the fins and tubes, and evaporative heat transfer inside the tubes. The finned-tubes condenser model has been assessed against data obtained at the PSI LINX facility with two test condensers. For the 62 LINX experiments performed, the model predictions are very good, i.e., less than 10 % standard deviation between experimental and predicted results. (authors)

  9. Low in reactor creep Zr-base alloy tubes

    International Nuclear Information System (INIS)

    Cheadle, B.A.; Holt, R.A.

    1984-01-01

    This invention relates to zirconium alloy tubes especially for use in nuclear power reactors. More particularly it relates to quaternary 3.5 percent Sn, 1 percent Mo, 1 percent Nb, balance Zr alloy tubes which have been extruded, cold worked and heat treated to lower their dislocation density. In one embodiment the alloys are cold worked less than 5 percent and stress relieved to produce a low dislocation density and in another embodiment the alloys are cold worked up to about 50 percent and annealed to produce a very low dislocation density and also small equiaxed β grains

  10. Non destructive methods applied on condenser tubes of copper alloys, stainless steel and titanium in the various standards and specifications

    International Nuclear Information System (INIS)

    Richter, H.; Heckhaeuser, H.

    1982-01-01

    For condenser tubes the Eddy current method is mostly applied and is found to be a suitable instrument to fulfil the demand to segregate tubes with harmful, injurious defects. Depending on individual special requirements ultrasonic testing may be performed as a additional test to increase the defect detection probability. Most standards applicable for condenser tubes do give preference the exclusive requirements ''test standard'' and ''sensitivity level'' which practically cannot maintain identical or strictly comparable test results relating to different equipment and test data. For a mutual understanding between the various partners involved additional test data should be taken into consideration as to allow clear interpretations of results anticipated. The type of artificial defects specified should take into account, that the exclusive mean of this defect is to establish the sensitivity and not to simulate any natural defect occuring in the tube to be tested. Regarding the physical interactions of EC and UT is recommended to specify bore holes drilled through the wall for EC and longitudinal notches on outside and/or inside surface for UT. For setting purpose the size of bore hole and notch should be selected such as to maintain easy reproducable preparation and sufficient clear and reliable responses

  11. Effects of roll waves on annular flow heat transfer at horizontal condenser tube

    International Nuclear Information System (INIS)

    Kondo, Masaya; Nakamura, Hideo; Anoda, Yoshinari; Sakashita, Akihiro

    2002-01-01

    Heat removal characteristic of a horizontal in-tube condensation heat exchanger is under investigation to be used for a passive containment cooling system (PCCS) of a next generation-type BWR. Flow regime observed at the inlet of the condenser tube was annular flow, and the local heat transfer rate was ∼20% larger than the prediction by the Dobson-Chato correlation. Roll waves were found to appear on the liquid film in the annular flow. The measured local condensation heat transfer rate was being closely related to the roll waves frequency. Based on these observations, a model is proposed which predicts the condensation heat transfer coefficient for annular flows around the tube inlet. The proposed model predicts well the influences of pressure, local gas-phase velocity and film thickness. (author)

  12. Failure of Titanium Condenser Tubes after 24 Years Power Plant Service

    DEFF Research Database (Denmark)

    Montgomery, Melanie; Enemark, Allan; Hangaard, Anders

    2014-01-01

    The titanium condenser has been in operation for 24 years at Amager unit 3 power plant. In February 2012, the plant was contaminated by seawater due to a failed condenser tube and some tubes were plugged. A month later, the plant tripped again. Small leaks were found again and finally approx. 200...... a plant trip. In addition, small amounts of titanium hydride were revealed to be present in the tubes within the tubesheet indicating that the carbon steel tubesheet was corroding due to ingress of salt water. Although this was not the reason for the failure, it indicated the need for repair of the epoxy...

  13. Mixed convection heat transfer between a steam/non-condensable gas mixture and an inclined finned tube bundle

    Energy Technology Data Exchange (ETDEWEB)

    De Cachard, F.; Lompersky, S.; Monauni, G.R. [Paul Scherrer Institute, Villigen (Switzerland). Thermal Hydraulic Lab.

    1999-07-01

    An experimental and analytical program was performed at PSI (Paul Scherrer Institute) to study the performance of a finned-tube condenser in the presence of non-condensable gases at low gas mass fluxes. The model developed for this application includes mixed convection heat transfer between the vapour/non-condensable mixture and the finned tubes, heat conduction through the fins and tubes, and evaporative heat transfer inside the tubes. On the gas, heat transfer correlations are used, and the condensation rate is calculated using the heat/mass transfer analogy. A combination of various available correlations for forced convection in staggered finned tube bundles is used, together with a correction accounting for superimposed natural convection. For the condensate heat transfer resistance, the beatty and Katz model for gravity driven liquid films on the tubes is used. The fine efficiency is accounted for using classical iterative calculations. Evaporative heat transfer inside the tubes is predicted using the Chen correlation. The finned tube condenser model has been assessed against data obtained at the PSI LINX facility with two test condensers. For the 62 LINX experiments performed, the model predictions are very good, i.e., less then 10% standard deviation between experimental and predicted results.

  14. Theoretical modeling of steam condensation in the presence of a noncondensable gas in horizontal tubes

    International Nuclear Information System (INIS)

    Lee, Kwon-Yeong; Kim, Moo Hwan; Kim, Moo Hwan

    2008-01-01

    A theoretical model was developed to investigate a steam condensation with a noncondensable gas in a horizontal tube. The heat transfer through the vapor/noncondensable gas mixture boundary layer consists of the sensible heat transfer and the latent heat transfer given up by the condensing vapor, and it must equal that from the condensate film to the tube wall. Therefore, the total heat transfer coefficient is given by the film, condensation and sensible heat transfer coefficients. The film heat transfer coefficients of the upper and lower portions of the tube were calculated separately from Rosson and Meyers (1965) correlation. The heat and mass transfer analogy was used to analyze the steam/noncondensable gas mixture boundary layer. Here, the Nusselt and Sherwood numbers in the gas phase were modified to incorporate the effects of condensate film roughness, suction, and developing flow. The predictions of the theoretical model for the experimental heat transfer coefficients at the top and bottom of the tube were reasonable. The calculated heat transfer coefficients at the top of the tube were higher than those at the bottom of it, as experimental results. As the temperature potential at the top of tube was lower than that at the bottom of it, the heat fluxes at the upper and lower portions of the tube were similar to each other. Generally speaking, however, the model predictions showed a good agreement with experimental data. The new empirical correlation proposed by Lee and Kim (2008) for the vertical tube was applied to the condensation of steam/noncondensable mixture in a horizontal tube. Nusselt theory and Chato correlation were used to calculate the heat transfer coefficients at top and bottom of the horizontal tube, respectively. The predictions of the new empirical correlation were good and very similar with the theoretical model. (author)

  15. Numerical investigation of convective condensation with the presence of non-condensable gases in a vertical tube

    Energy Technology Data Exchange (ETDEWEB)

    Fu, Wen [Key Laboratory of Advanced Reactor Engineering and Safety of Ministry of Education, Collaborative Innovation Center of Advanced Nuclear Energy Technology, Institute of Nuclear and New Energy Technology, Tsinghua University, Beijing 100084 (China); Li, Xiaowei, E-mail: lixiaowei@tsinghua.edu.cn [Key Laboratory of Advanced Reactor Engineering and Safety of Ministry of Education, Collaborative Innovation Center of Advanced Nuclear Energy Technology, Institute of Nuclear and New Energy Technology, Tsinghua University, Beijing 100084 (China); Wu, Xinxin [Key Laboratory of Advanced Reactor Engineering and Safety of Ministry of Education, Collaborative Innovation Center of Advanced Nuclear Energy Technology, Institute of Nuclear and New Energy Technology, Tsinghua University, Beijing 100084 (China); Corradini, Michael L. [Department of Engineering Physics, University of Wisconsin-Madison, 1500 Engineering Drive, Madison, WI 53706 (United States)

    2016-02-15

    Highlights: • Gas mixture convective condensation in vertical tubes were simulated using FLUENT code. • The simulation results matched well with experimental data. • The detailed velocity field and species distribution were investigated. • The suction factors predicted by CFD models were compared with the classical correlations. • The effects of air and helium on steam condensation were compared. - Abstract: Steam condensation is degraded when non-condensable gases are present. Convective condensation of steam–air mixture and steam–helium mixture in vertical tubes were simulated using the CFD code FLUENT. The condensation process was modeled by defining source terms for the mass, momentum, species and energy conservation equations. Several cases with various steam mass fractions were simulated, the results matched well with the experimental data. Detailed velocity field and species distribution were investigated. The radial velocity was clearly represented, and the suction effect was modeled, which needs to be accounted for when using the heat and mass transfer analogy theory. The Nusselt and Sherwood numbers predicted by CFD models were compared with the classical correlations, and the suction effects were analyzed. The suction effect is proportional to steam mass fraction, while the suction factor is little affected by the Reynolds number. For forced convection flow in this work, the buoyant force can be neglected, so the larger diffusion coefficient of steam–helium mixture would improve the steam condensation compared to steam–air mixture. The condensation mass fluxes of steam–helium mixture and steam–air mixture are almost the same at relatively high steam inlet molar fraction (≥90%).

  16. New Czechoslovak detector of leaking condenser tubes usable in both shutdown and reduced output operation of power unit

    International Nuclear Information System (INIS)

    Matal, O.; Klinga, J.; Varvarovsky, F.; Zachar, J.; Fratric, D.

    1986-01-01

    The main reason for penetration of undesirable admixtures from cooling water in the condensate is the inleakage of steam turbine condensers. Briefly assessed are the means and methods of detecting and locating condenser leaks used in the world and in power facilities in Czechoslovakia. Equipment was developed based on measuring the difference between the pressure in a temporarily closed condenser tube and ambient pressure, for leak testing of condenser tubes during operation and during shutdown of WWER-440 units. Two types of the equipment were tested in practice. Type VUEZ-PHN 85P meets the requirements of objective leak tests and those of leak location in condenser tubes and of leak detection in tube expansion in the tube plates of WWER-440 unit condensers, this as concerns sensitivity, the objectivity of results, the cost of tests, and minimal losses of power during the test. Type VUEZ-PHN 85P can be used for leak location in all tube type heat exchangers with access to tube outlets in which under- or overpressure can be achieved in the space between the tubes relative to ambient pressure during the test. (Z.M.) 5 figs., 4 tabs., 11 refs

  17. Determining the Optimum Inner Diameter of Condenser Tubes Based on Thermodynamic Objective Functions and an Economic Analysis

    Directory of Open Access Journals (Sweden)

    Rafał Laskowski

    2016-12-01

    Full Text Available The diameter and configuration of tubes are important design parameters of power condensers. If a proper tube diameter is applied during the design of a power unit, a high energy efficiency of the condenser itself can be achieved and the performance of the whole power generation unit can be improved. If a tube assembly is to be replaced, one should verify whether the chosen condenser tube diameter is correct. Using a diameter that is too large increases the heat transfer area, leading to over-dimensioning and higher costs of building the condenser. On the other hand, if the diameter is too small, water flows faster through the tubes, which results in larger flow resistance and larger pumping power of the cooling-water pump. Both simple and complex methods can be applied to determine the condenser tube diameter. The paper proposes a method of technical and economic optimisation taking into account the performance of a condenser, the low-pressure (LP part of a turbine, and a cooling-water pump as well as the profit from electric power generation and costs of building the condenser and pumping cooling water. The results obtained by this method were compared with those provided by the following simpler methods: minimization of the entropy generation rate per unit length of a condenser tube (considering entropy generation due to heat transfer and resistance of cooling-water flow, minimization of the total entropy generation rate (considering entropy generation for the system comprising the LP part of the turbine, the condenser, and the cooling-water pump, and maximization of the power unit’s output. The proposed methods were used to verify diameters of tubes in power condensers in a200-MW and a 500-MW power units.

  18. A condensation experiment in the accumulated conditions of noncondensable gas in a vertical tube

    International Nuclear Information System (INIS)

    Lee, Kwon Yeong; Kim, Moo Hwan

    2005-01-01

    Full text of publication follows: It has been well known that the presence of noncondensable gases in vapors can greatly inhibit the condensation process. Many analytical and experimental studies were conducted to investigate the effect of noncondensable gases on steam condensation for both stagnant and forced-convective situations either over a plate or outside a horizontal tube. Recently, several researches have been performed for the condensation in the presence of noncondensable gases taken place inside the vertical tube in order to give the information to design the passive containment cooling system (PCCS) in Simplified Boiling Water Reactor (SBWR). Generally, the experimental results showed that the heat transfer coefficient depends on inlet noncondensable gas mass fraction, inlet saturated steam temperature related with system pressure and inlet mixture Reynolds number. This research was performed for the System-integrated Modular Advanced ReacTor-Pilot (SMART-P), in which the remaining heat is removed from the core passively by Passive Residual Heat Removal System (PRHRS) condenser in a period of serious accident. The PRHRS is separated from working fluid loop, and pressurized by a nitrogen gas during the normal operation of SMART-P. But when the PRHRS starts operating, the nitrogen gas acts as a noncondensable gas and affects the heat transfer characteristics of the PRHRS. The experimental conditions of this study were almost similar with those of previous researches except the noncondensable gas was accumulated and remained inside the vertical tube. In the previous researches, the noncondensable gas was flowing with constant flow rate. Because of the condensate inside condenser tube, the accumulation of noncondensable gas could be developed inside the vertical tube. At steady-state condition the local temperatures and system pressure were measured to obtain heat transfer characteristics. This study also gave the information about the distribution of the

  19. Operational experiences with on line BWR condenser tube leak verification

    International Nuclear Information System (INIS)

    Bryant, R.A.; Duvall, W.E.; Kirkley, W.B.; Zavadoski, R.W.

    1988-01-01

    Verifying condenser tube leaks at a boiling water reactor is, at best, a difficult task carried out in hot steamy water boxes with concurrent radiation exposure. For small apparent leaks with slight chemical changes there is always uncertainty of whether the problem is a condenser tube leak or a feedback from radwaste. Most conventional methods (e.g soap tests, Saran wrap suction, and helium tests) usually involve a load reduction to isolate the water boxes one at a time and hours of drain down on each box. The sensitivity of the most sensitive test (helium) is of the order of 7500 l per day per box. Sulfur hexafluoride has been successfully used at a BWR to identify one leaking water box out of four while the unit was at 100 % power. The actual tubes leakig in the water box were identified by injecting helium during drain down of the box and subsequent manifold testing. Additional tests with sulfur hexafluoride on the second BWR unit indicated tight water boxes to within the sensitivity of the measurement, i.e. less than 19 l per day for all four boxes. Problems encountered in both tests included sulfur hexafluoride carry over from the plume of the cooling towers and off gas considerations. In brief sulfur hexafluoride can be used to quickly identify which particular water box has a condenser tube leak or, just as quickly, establish the integrity of all the water boxes to a level not previously attainable. (author)

  20. TRACE assessment on local condensation heat transfer in presence of non-condensable gas inside a vertical tube

    Energy Technology Data Exchange (ETDEWEB)

    Cho, Yong Jin; Ahn, Seung Hoon; Kim, Kap; Kim, Hho Jung [Korea Institute of Nuclear Safety, Daejeon (Korea, Republic of)

    2009-07-01

    TRACE assessment was performed to investigate local condensation heat transfer coefficients in the presence of a noncondensable gas inside a vertical tube. The data obtained from pure steam and steam/nitrogen mixture condensation experiments were compared to study the effects of noncondensable nitrogen gas on the annular film condensation phenomena. The condenser tube had a small inner diameter of 13mm (about 1/2-in.) and this experiment had been performed to prove the effectiveness of the a Passive Residual Heat Removal System (PRHRS) of SMART (System-integrated Modular Advanced ReacTor), which is a small modular integral-type pressurized water reactor that is developed for the dual purposes of seawater desalination and small-scaled power generation. In the case of nitrogen presence, TRACE results show the converged results but the prediction is different from experimental data. The candidate reasons can be focused on several models, such as the film thickness calculation, surface area, and condensation heat transfer correlations, etc. In the case of pure steam condensation case, TRACE results shows large oscillations and do not converge. This should be investigated in detail to identify the reason. Until now, the oscillation in thermal hydraulic parameters results from the film thickness calculation and surface area calculation. For future works, the whole sets of the experiment will be assessed and the improvement of TRACE will be performed.

  1. TRACE assessment on local condensation heat transfer in presence of non-condensable gas inside a vertical tube

    International Nuclear Information System (INIS)

    Cho, Yong Jin; Ahn, Seung Hoon; Kim, Kap; Kim, Hho Jung

    2009-01-01

    TRACE assessment was performed to investigate local condensation heat transfer coefficients in the presence of a noncondensable gas inside a vertical tube. The data obtained from pure steam and steam/nitrogen mixture condensation experiments were compared to study the effects of noncondensable nitrogen gas on the annular film condensation phenomena. The condenser tube had a small inner diameter of 13mm (about 1/2-in.) and this experiment had been performed to prove the effectiveness of the a Passive Residual Heat Removal System (PRHRS) of SMART (System-integrated Modular Advanced ReacTor), which is a small modular integral-type pressurized water reactor that is developed for the dual purposes of seawater desalination and small-scaled power generation. In the case of nitrogen presence, TRACE results show the converged results but the prediction is different from experimental data. The candidate reasons can be focused on several models, such as the film thickness calculation, surface area, and condensation heat transfer correlations, etc. In the case of pure steam condensation case, TRACE results shows large oscillations and do not converge. This should be investigated in detail to identify the reason. Until now, the oscillation in thermal hydraulic parameters results from the film thickness calculation and surface area calculation. For future works, the whole sets of the experiment will be assessed and the improvement of TRACE will be performed

  2. Area effect on galvanic corrosion of condenser materials with titanium tubes in nuclear power plants

    International Nuclear Information System (INIS)

    Hwang, Seong Sik; Kim, Joung Soo; Kim, Uh Chul

    1993-01-01

    Titanium tubes have recently been used in condensers of nuclear power plants since titanium has very good corrosion resistance to seawater. However, when it is connected to Cu alloys as tube sheet materials and these Cu alloys are connected to carbon steels as water box materials, it makes significant galvanic corrosion on connected materials. It is expected from electrochemical tests that the corrosion rate of carbon steel will increase when it is galvanically coupled with Ti or Cu in sea water and the corrosion rate of Cu will increase when it is coupled with Ti, of this couple is exposed to sea water for a long time. It is also expected that the surface area ratios, R 1 (surface area of carbon steel/surface area of Ti) and R 2 (surface area of carbon steel/surface area of Cu) are very improtant for the galvanic corrosion of carbon steel and that these should not be kept to low values in order to minimize the galvanic corrosion on the carbon steel of the water box. Immersed galvanic corrosion tests show that the corrosion rate of carbon steel is 4.4 mpy when this ratio is 10 -2 . The galvanic corrosion rate of this carbon steel is increased from 4.4 mpy to 13 mpy at this area ratio, 1, when this connected galvanic specimen is galvanically coupled with a Ti tube. This can be rationalized by the combined effects of R 1 and R 2 on the polarization curve. (Author)

  3. Condensation of pure and near-azeotropic refrigerants in microfin tubes: A new computational procedure

    Energy Technology Data Exchange (ETDEWEB)

    Cavallini, A; Del Col, D; Mancin, S; Rossetto, L [Dipartimento di Fisica Tecnica, University of Padova, Via Venezia 1, Padova 35131 (Italy)

    2009-01-15

    Microfin tubes are widely used in air cooled and water cooled heat exchangers for heat pump and refrigeration applications during condensation or evaporation of refrigerants. In order to design heat exchangers and to optimize heat transfer surfaces, accurate procedures for computing pressure drops and heat transfer coefficients are necessary. This paper presents a new simple model for the prediction of the heat transfer coefficient to be applied to condensation in horizontal microfin tubes of halogenated and natural refrigerants, pure fluids or nearly azeotropic mixtures. The updated model accounts for refrigerant physical properties, two-phase flow patterns in microfin tubes and geometrical characteristics of the tubes. It is validated against a data bank of 3115 experimental heat transfer coefficients measured in different independent laboratories all over the world including diverse inside tube geometries and different condensing refrigerants among which R22, R134a, R123, R410A and CO{sub 2}. (author)

  4. Field tests of 2- and 40-tube condensers at the East Mesa Geothermal Test Site

    Energy Technology Data Exchange (ETDEWEB)

    Murphy, R.W.; Domingo, N.

    1982-05-01

    Two water-cooled isobutane condensers, one with 2 tubes and one with 40 tubes, were subjected to field tests at the East Mesa Geothermal Test Site to assess relative heat transfer performance in both surface evaporator and direct-contact evaporator modes. The five groups of tests established that field performance was below earlier laboratory-determined levels and that direct-contact evaporator mode performance was poorer than that for the surface evaporator mode. In all test situations, fluted condenser tubes performed better than smooth condenser tubes. Cooling water quality had no significant effect on performance, but brine preflash in the direct-contact mode did promote some relative performance improvement. Important implications of these results for binary geothermal power plants are that (1) working-fluid-side impurities can significantly degrade heat transfer performance of the power plant condensers and (2) provisions for minimizing such impurities may be required.

  5. Feasibility study on the guided wave technique for condenser tube in NPP

    International Nuclear Information System (INIS)

    Choi, Sung Nam; Kim, Young Ho; Kim, Hyung Nam; Yoo, Hyun Joo; Hwang, W. G.

    2004-01-01

    The condenser tube is examined by the eddy current test (ECT) method to identify the integrity of the nuclear power plant. Because ECT probe is moved through the tube inside to identify flaws, the ECT probe should be exchanged periodically due to the wear of probe surface in order to remove the noise form the ECT signal. Moreover, it is impossible to examine the tube by ECT method because the ECT probe can not move through the inside due to the deformation such as dent. Recently, the theory of guided wave was established and the equipment applying the theory has been actively developed so as to overcome the limitation of ECT method for the tube inspection of heater exchanger in nuclear power plant. The object of this study is to know the feasibility of applying the guided wave technique to condenser tube in NPP

  6. Properties and application study of Inconel alloy tube made in China

    International Nuclear Information System (INIS)

    Yang Xiang; Su Xingwan; Wen Yan

    1997-01-01

    The mech-physical properties and the corrosion resistance properties of the SG tube of Inconel alloy made in China under any conditions are briefly presented, and the test and research for bending and expending the tubes have been performed. In the process of corrosion experiments the Inconel alloy tubes were compared with that of the same kind of materials made in foreign countries. The Inconel alloy tubes have better stress corrosion resistance cracking prosperities than Inconel 600 and Incoloy 800 when they were in the solutions which contained high concentrated chlorine ion and alkali at high temperature

  7. Heat transfer performance during condensation of R-134a inside helicoidal tubes

    International Nuclear Information System (INIS)

    Al-Hajeri, M.H.; Koluib, A.M.; Mosaad, M.; Al-Kulaib, S.

    2007-01-01

    This paper reports an experimental investigation of condensation heat transfer and pressure drop of an ozone friendly refrigerant, R-134a, inside a helical tube for climatic conditioning of hot regions. This study concerns the condensation of R-134a flowing through annular helical tubes with different operating refrigerant saturated temperatures. The average pressure drop is measured and compared with data from relevant literature. The measurements of R-134a were performed on mass flow flux ranges from 50 to 680 kg/m 2 s. The study provides experimental data that could be used for the design and development of more efficient condensers for refrigeration and air conditioning (A/C) systems working with the same refrigerant

  8. Effect of tubing condensate on non-invasive positive pressure ventilators tested under simulated clinical conditions.

    Science.gov (United States)

    Hart, Diana Elizabeth; Forman, Mark; Veale, Andrew G

    2011-09-01

    Water condensate in the humidifier tubing can affect bi-level ventilation by narrowing tube diameter and increasing airflow resistance. We investigated room temperature and tubing type as ways to reduce condensate and its effect on bi-level triggering and pressure delivery. In this bench study, the aim was to test the hypothesis that a relationship exists between room temperature and tubing condensate. Using a patient simulator, a Res-med bi-level device was set to 18/8 cm H(2)O and run for 6 h at room temperatures of 16°C, 18°C and 20°C. The built-in humidifier was set to a low, medium or high setting while using unheated or insulated tubing or replaced with a humidifier using heated tubing. Humidifier output, condensate, mask pressure and triggering delay of the bi-level were measured at 1 and 6 h using an infrared hygrometer, metric weights, Honeywell pressure transducer and TSI pneumotach. When humidity output exceeded 17.5 mg H(2)O/L, inspiratory pressure fell by 2-15 cm H(2)O and triggering was delayed by 0.2-0.9 s. Heating the tubing avoided any such ventilatory effect whereas warmer room temperatures or insulating the tubing were of marginal benefit. Users of bi-level ventilators need to be aware of this problem and its solution. Bi-level humidifier tubing may need to be heated to ensure correct humidification, pressure delivery and triggering.

  9. Study on manufacturing technology of fuel guide tube using HANA alloys

    International Nuclear Information System (INIS)

    Kim, Hyungil; Jung, Yangil; Park, Dongjun; Park, Jeongyong; Kim, Ilhyun; Choi, Byungkwon; Jeong, Yonghwan; Park, Sangyoon

    2013-04-01

    This research was focused on the study for the manufacturing technology of HANA alloys to crease the corrosion resistance of 30% as well as the to improve the strength of 10% when compared to the commercial zirconium alloys. The new manufacturing concept having higher corrosion resistance and strength than commercial alloy performance can be obtained in this research. This result was transferred to the KNF and, that will be commercialized. This research result can be summarized like this; Ο Parameter study to increase formability of HANA alloy tube - Study on alloy element and heat-treatment effect - Study on texture development mechanism - Study on final annealing effect Ο Out-of-pile performance evaluation of HANA alloy tube - Corrosion performance evaluation of HANA alloy manufactured at KNF - Mechanical performance evaluation of HANA alloy manufactured at KNF - Recrystallization behavior evaluation of HANA alloy manufactured at KNF - Texture characterization of HANA alloy manufactured at KNF - Microstructure characterization of HANA alloy manufactured at KNF Ο Manufacturing guideline setup to increase formability of HANA alloy tube - Manufacturing guideline setup to decrease surface defect - Manufacturing guideline setup to increase strength and corrosion resistance - Manufacturing guideline setup to control texture

  10. Tube in zirconium base alloy for nuclear fuel assembly and manufacturing process of such a tube

    International Nuclear Information System (INIS)

    Mardon, J.P.; Senevat, J.; Charquet, D.

    1996-01-01

    This patent concerns the description and manufacturing guidelines of a zirconium alloy tube for fuel cladding or fuel assembly guiding. The alloy contains (in weight) 0.4 to 0.6% of tin, 0.5 to 0.8% of iron, 0.35 to 0.50% of vanadium and 0.1 to 0.18% of oxygen. The carbon and silicon tenors range from 100 to 180 ppm and from 80 to 120 ppm, respectively. The alloy contains only zirconium, plus inevitable impurities, and is completely recrystallized. Corrosion resistance tests were performed on tubes made of this alloy and compared to corrosion tests performed on zircaloy 4 tubes. These tests show a better corrosion resistance and a lower corrosion kinetics for the new alloy, even in presence of lithium and iodine, and a lower hydridation rate. The mechanical resistance of this alloy is slightly lower than the one of zircaloy 4 but becomes equivalent or slightly better after two irradiation cycles. The ductility remains always equal or better than for zircaloy 4. (J.S.)

  11. Material reliability of Ni alloy electrodeposition for steam generator tube repair

    International Nuclear Information System (INIS)

    Kim, Dong Jin; Kim, Myong Jin; Kim, Joung Soo; Kim, Hong Pyo

    2007-01-01

    Due to the occasional occurrences of Stress Corrosion Cracking (SCC) in steam generator tubing (Alloy 600), degraded tubes are removed from service by plugging or are repaired for re-use. Since electrodeposition inside a tube dose not entail parent tube deformation, residual stress in the tube can be minimized. In this work, tube restoration via electrodeposition inside a steam generator tubing was performed after developing the following: an anode probe to be installed inside a tube, a degreasing condition to remove dirt and grease, an activation condition for surface oxide elimination, a tightly adhered strike layer forming condition between the electroforming layer and the Alloy 600 tube, and the condition for an electroforming layer. The reliability of the electrodeposited material, with a variation of material properties, was evaluated as a function of the electrodeposit position in the vertical direction of a tube using the developed anode. It has been noted that the variation of the material properties along the electrodeposit length was acceptable in a process margin. To improve the reliability of a material property, the causes of the variation occurrence were presumed, and an attempt to minimize the variation has been made. A Ni alloy electrodeposition process is suggested as a Primary Water Stress Corrosion Cracking (PWSCC) mitigation method for various components, including steam generator tubes. The Ni alloy electrodeposit formed inside a tube by using the installed assembly shows proper material properties as well as an excellent SCC resistance

  12. Development of heat treated Zr-2.5% Nb alloy tubes for pressure tubes

    International Nuclear Information System (INIS)

    Saibaba, N.; Jha, S.K.; Tonpe, S.

    2011-01-01

    Zr-2.5% Nb alloy is the candidate material for pressure tubes of Pressurized Heavy Water Reactors (PHWR), and are manufactured in cold working condition while heat treated pressure tubes are used in RBMK and FUGEN type of reactors. The diametral creep of these tubes is the life limiting factor. This paper presents the extensive work carried out for the optimization of process parameters to manufacture heat treated Zr-2.5% Nb pressure tubes. Extensive dilactometry study was carried out to establish the transus temperature for the alloy and the effect of soaking temperature and cooling rate on the microstructure was characterized. On the basis of the study, water quenching (at 883 deg C) in the a b region with 20-25% primary a phase was selected, further cold worked, aged and finally autoclaved. Mechanical properties of the finished tubes were found to be comparable to the cold worked route. Large number of full sized tubes of about 700 - 800 mm long was produced to establish the repeatability. (author)

  13. Condensation heat transfer of R22 and R410A in horizontal smooth and microfin tubes

    Energy Technology Data Exchange (ETDEWEB)

    Kim, Man-Hoe; Shin, Joeng-Seob [Korea Advanced Institute of Science and Technology, Daejeon (Korea). Department of Mechanical Engineering

    2005-09-01

    An experimental investigation of condensation heat transfer in 9.52 mm O.D. horizontal copper tubes was conducted using R22 and R410A. The test rig had a straight, horizontal test section with an active length of 0.92 m and was cooled by the heat transfer fluid (cold water) circulated in a surrounding annulus. Constant heat flux of 11.0 kW/m{sup 2} was maintained throughout the experiment and refrigerant quality varied from 0.9 to 0.1. The condensation test results at 45 {sup o}C were reported for 40-80 kg/h mass flow rate. The local and average condensation coefficients for seven microfin tubes were presented compared to those for a smooth tube. The average condensation coefficients of R22 and R410A for the microfin tubes were 1.7-3.19 and 1.7-2.94 times larger than those in smooth tube, respectively. (author)

  14. Comparative assessment of condensation models for horizontal tubes

    International Nuclear Information System (INIS)

    Schaffrath, A.; Kruessenberg, A.K.; Lischke, W.; Gocht, U.; Fjodorow, A.

    1999-01-01

    The condensation in horizontal tubes plays an important role e.g. for the determination of the operation mode of horizontal steam generators of VVER reactors or passive safety systems for the next generation of nuclear power plants. Two different approaches (HOTKON and KONWAR) for modeling this process have been undertaken by Forschungszentrum Juelich (FZJ) and University for Applied Sciences Zittau/Goerlitz (HTWS) and implemented into the 1D-thermohydraulic code ATHLET, which is developed by the Gesellschaft fuer Anlagen- und Reaktorsicherheit (GRS) mbH for the analysis of anticipated and abnormal transients in light water reactors. Although the improvements of the condensation models are developed for different applications (VVER steam generators - emergency condenser of the SWR1000) with strongly different operation conditions (e.g. the temperature difference over the tube wall in HORUS is up to 30 K and in NOKO up to 250 K, the heat flux density in HORUS is up to 40 kW/m 2 and in NOKO up to 1 GW/m 2 ) both models are now compared and assessed by Forschungszentrum Rossendorf FZR e.V. Therefore, post test calculations of selected HORUS experiments were performed with ATHLET/KONWAR and compared to existing ATHLET and ATHLET/HOTKON calculations of HTWS. It can be seen that the calculations with the extension KONWAR as well as HOTKON improve significantly the agreement between computational and experimental data. (orig.) [de

  15. Analysis of experiments for vertical out-tube steam condensation in presence of non-condensable gases

    International Nuclear Information System (INIS)

    Su Jiqiang; Sun Zhongning; Fan Guangming; Guo Zixuan

    2014-01-01

    In order to investigate the influence of various parameters in the steam condensation heat transfer process with non-condensable gas, and to get a more suitable empirical correlation, the wall under-cooling, pressure and the content of non-condensable gas were studied outside a vertical tube by experiments. The results showed that: at the same pressure, the relationship between wall sub-cooling and HTC is exponential, and helium stratification does not happen within the experimental range. Based on the analysis of various experimental variables, combined with a large number of experimental data, a wider scope of application of the empirical correlation associated is obtained with the experimental value of the error within ±20%. (authors)

  16. Estimation of a tube diameter in a ‘church window’ condenser based on entropy generation minimization

    Directory of Open Access Journals (Sweden)

    Laskowski Rafał

    2015-09-01

    Full Text Available The internal diameter of a tube in a ‘church window’ condenser was estimated using an entropy generation minimization approach. The adopted model took into account the entropy generation due to heat transfer and flow resistance from the cooling-water side. Calculations were performed considering two equations for the flow resistance coefficient for four different roughness values of a condenser tube. Following the analysis, the internal diameter of the tube was obtained in the range of 17.5 mm to 20 mm (the current internal diameter of the condenser tube is 22 mm. The calculated diameter depends on and is positively related to the roughness assumed in the model.

  17. Amorphous bimetallic alloys prepared by steam condensation

    International Nuclear Information System (INIS)

    Drago, V.

    1988-01-01

    Amorphous alloys of MnSn are prepared by steam condensation, in a substratum with a temperature near of the liquid helium. The magnetic and paramagnetic hyperfine spectrum and the ordination temperature by Moessbauer effect 119Sn are measured. A diagram of magnetic phase is proposed, basing on the measures of Moessbauer effect. (C.G.C.) [pt

  18. Film flow analysis for a vertical evaporating tube with inner evaporation and outer condensation

    International Nuclear Information System (INIS)

    Park, Il Seouk

    2008-01-01

    A numerical study for the flow, heat and mass transfer characteristics of the evaporating tube with the films flowing down on both the inside and outside tube walls has been carried out. The condensation occurs along the outside wall while the evaporation occurs at the free surface of the inside film. The transport equations for momentum and energy are parabolized by the boundary-layer approximation and solved by using the marching technique. The calculation domain of 2 film flow regions (evaporating and condensation films at the inside and outside tube wall respectively) and tube wall is solved simultaneously. The coupling technique for the problem with the 3 different regions and the 2 interfaces of them has been developed to calculated the temperature field. The velocity and temperature fields and the amount of the condensed and evaporated mass as well as the position where the evaporating film is completely dried out are successfully predicted for various inside pressures and inside film inlet flow rates

  19. Simulation of steam condensation in the presence of noncondensable gases in horizontal condenser tubes using RELAP5 for advanced nuclear reactors

    International Nuclear Information System (INIS)

    Macedo, Luiz Alberto; Torres, Walmir Maximo

    2009-01-01

    Horizontal heat exchangers are used in advanced light water nuclear reactors in their passive cooling systems, such as residual heat removal (RHRS) and passive containment cooling system (PCCS). Condensation studies of steam and noncondensable gases mixtures in these heat exchangers are very important due to the phenomena multidimensional nature and the condensate stratification effects. This work presents a comparison between simulation results and experimental data in steady state conditions for some inlet pressure, steam and noncondensable gases (air) inlet mass fractions. The test section is three meters long and consists of two concentric tubes containing pressure, temperature and flow rate sensors. The internal tube, called condenser, contains steam-air mixture flow and external tube is a counter current cooler with water flow rate at low temperature. This test section was modeled and simulations were performed with RELAP5 code. Experimental tests were carried out for 200 to 400 kPa inlet pressure and 5, 10, 15 and 20% of inlet air mass fractions. Comparisons between experimental data and simulation results are presented for 200 and 400 kPa pressure conditions and showed good agreement. However, for 400 kPa inlet steam pressure and inlet air mass fractions above 5%, the simulated temperatures are lower than the experimental data at the final third from the inlet condenser tube, indicating a code overestimation of heat transfer coefficient. New correlations for heat transfer coefficient in these steam-air conditions must be theoretical and experimentally studied and implemented in RELAP5 code for better representing the condensation phenomena. (author)

  20. Single-tube condensation experiment in Passive Auxiliary Feedwater System of APR1400+

    Energy Technology Data Exchange (ETDEWEB)

    Shin, Chang Wook; No, Hee Cheon; Yun, Bong Yo; Jeon, Byong Guk [Korea Advanced Institute of Science and Technology, Daejeon (Korea, Republic of)

    2012-05-15

    Conventional Korean nuclear power plants, Advanced Power Reactors (APR), are characterized by an active cooling system. However, Active cooling system may not prevent significant damage without any AC power source available for its operation as vividly illustrated through the recent Fukushima incident. In the APR1400+ to be designed, an independent passive cooling system was added in order to overcome the aforementioned shortcomings. In the Passive Auxiliary Feedwater System (PAFS), gravity force and density difference between steam and water are used. The system comprises of 240 condensation tubes to efficiently remove decay heat. Before applying the PAFS to APR1400+, the system's safety and heat removal performance must be verified. The present study experimentally evaluates the heat removal performance of a single tube in the PAFS. The objectives of SCOP (Single-tube Condensation experiment facility of PAFS) are the evaluation of the heat removal performance in the tube of the PAFS and database construction under various tube designs and test conditions. Reaching these objectives, we developed advanced measurement techniques for the amount of moisture, heat flux, and water film thickness.

  1. Heat transfer during forced convection condensation inside horizontal tube

    Energy Technology Data Exchange (ETDEWEB)

    Tandon, T.N. [M.M.M. Engineering College, Gorakhpur, Uttar Pradesh (India). Dept. of Mechanical Engineering; Varma, H.K.; Gupta, C.P. [Roorkee Univ., Uttar Pradesh (India). Dept. of Mechanical and Industrial Engineering

    1995-03-01

    This paper presents the results of an experimental investigation on heat transfer behaviour during forced convection condensation inside a horizontal tube for wavy, semi-annular and annular flows. A qualitative study was made of the effect of various parameters - refrigerant mass flux, vapour quality, condensate film temperature drop and average vapour mass velocity - on average condensing-heat transfer coefficient. Akers-Rosson correlations have been found to predict the heat transfer coefficients within {+-} 25% for the entire range of data. A closer examination of the data revealed that the nature of the relation for the heat transfer coefficient changes from annular and semi-annular flow to wavy flow. Akers-Rosson correlations with changed constant and power have been recommended for the two flow regimes. (author)

  2. A survey on the corrosion susceptibility of Alloy 800 CANDU steam generator tubing materials

    International Nuclear Information System (INIS)

    Lu, Y.C.; Dupuis, M.; Burns, D.

    2008-01-01

    To provide support for a proactive steam generator (SG) aging management strategy, a survey on the corrosion susceptibility of the archived Alloy 800 tubing from CANDU SGs under plausible crevice chemistry conditions was conducted to assess the potential material degradation issues in CANDU SGs. Archived Alloy 800 samples were collected from four CANDU utilities. High-temperature electrochemical analysis was carried out to assess the corrosion susceptibility of the archived SG tubing under simulated CANDU crevice chemistry conditions at both 150 o C and 300 o C. The potentiodynamic polarization results obtained from the archived CANDU SG tubes were compared to the data from ex-service tubes removed from Darlington Nuclear Generating Station (DNGS) SGs and a reference nuclear grade Alloy 800 tubing. It was found that the removed Darlington SG tubes, with signs of in-service degradation, were more susceptible to pitting corrosion than the reference nuclear grade Alloy 800 tubing. At 150 o C, under the same neutral crevice chemistry conditions, the potentiodynamic polarization curve of the ex-service Darlington SG tubing has an active peak, which is a sign of propensity to crevice/underdeposit corrosion. This active peak was not observed in any of the potentiodynamic polarization curves of all archived Alloy 800 CANDU SG tubing indicating that archived CANDU SG tubes are less susceptible to the underdeposit corrosion under SG startup conditions. The corrosion behaviour of the archived Alloy 800 tubes from CANDU SG was similar to that of the reference nuclear grade Alloy 800 tubing. The results of this survey suggest that the Alloy 800 tubing materials used in the existing CANDU utilities (other than ex-service DNGS tubing) will continue to have reliable performance under specified CANDU operating conditions. Ex-service SG tubing from DNGS, although showing lower than average corrosion resistance, still has a wide acceptable operating margin and the in

  3. In-operation testing of condensers tubes in EDF thermal power plants

    International Nuclear Information System (INIS)

    Sermadiras, P.; Cormier, J.

    1982-01-01

    Electricite de France requires manufacturers to perform a number of tests on condenser tubes, as it does itself, including eddy current tests. This article describes the worksite inspection procedures, which use internal single-frequency probes to detect the following irregularities: - in differential mode: external corrosion, impacts, foreign matter, vibrations, internal behaviour of tubes; - in absolute mode: corrosion by ammonia [fr

  4. Condensation of nano-refrigerant inside a horizontal tube

    Science.gov (United States)

    Darzi, Milad; Sadoughi, M. K.; Sheikholeslami, M.

    2018-05-01

    In this paper, condensing pressure drop of refrigerant-based nanofluid inside a tube is studied. Isobutene was selected as the base fluid while CuO nanoparticles were utilized to prepare nano-refrigerant. However, for the feasibility of nanoparticle dispersion into the refrigerant, Polyester oil (POE) was utilized as lubricant oil and added to the pure refrigerant by 1% mass fraction. Various values of mass flux, vapor quality, concentration of nanoparticle are investigated. Results indicate that adding nanoparticles leads to enhance frictional pressure drop. Nanoparticles caused larger pressure drop penalty at relatively lower vapor qualities which may be attributed to the existing condensation flow pattern such that annular flow is less influenced by nanoparticles compared to intermittent flow regime.

  5. Steam condensation on finned tubes, in the presence of non-condensable gases and aerosols: Influence of impaction, diffusiophoresis and settling on aerosol deposition

    International Nuclear Information System (INIS)

    Munoz-Cobo, J.L.; Pena, J.; Herranz, L.E.; Perez-Navarro, A.

    2005-01-01

    This paper presents a mechanistic model to predict the steam condensation on containment finned tube heat exchangers in the presence of non-condensable gases (NC) and aerosols. The total thermal resistance from the bulk gas to the coolant is formulated as a parallel combination of the convective and condensation gas resistances coupled in series to those of condensate layer, the aerosol fouling layer, the wall, and the coolant. The condensate layer thermal resistance is calculated by means of an Adamek-based condensation model. The aerosol fouling layer is computed based on diffusiophoresis, settling and impaction mechanisms. The gas mixture (steam plus NC) thermal resistance is formulated based on a diffusion layer modeling. Finally, this paper presents a Montecarlo method implemented in the FORTRAN code TAEROSOL that is able to compute the amount of aerosol mass that is deposited by impaction on the top of the finned tubes. The model results are compared with the available experimental data of the CONGA European project

  6. An experimental study of high pressure steam condensation in a vertical tube of passive secondary condensation system

    Energy Technology Data Exchange (ETDEWEB)

    Kim, Sang Jae; No, Hee Cheon [KAIST, Taejon (Korea, Republic of)

    1998-07-01

    To investigate the physical parameters of PSCS (Passive Secondary Condensation System) which is a passive residual heat removal system of CP-1300, the high pressure condensation experiments are performed in a small scale experimental facility. The experimental parameters are the local heat flux and the transfer coefficient and the pressure drop in a condensation heat trasnfer. The film condensation heat transfer coefficients in a vertical tube are calculated from the measured wall temperature difference and compared with the analytical models. A new analytical condensation model is developed based on the annular film flow model. The present model gives marginally better results than those from the Shah model in comparison with the experimental data in the database. Also, experimental data are compared with the results of the RELAP5/MOD3.2 thermal hydraulic code. The RELAP5/MOD3.2 underpredicts the condensation heat transfer coefficients of the present experiment by 50 %.

  7. Condensers

    International Nuclear Information System (INIS)

    Andrieux, M.B.

    1984-01-01

    Characteristics of the condenser cooling waters of various French 900 MW nuclear power plants. Design and description of various types of condensers: condensers feeded directly with river water, condensers feeded by cooling towers, condensers feeded with sea water of brackish water. Presentation of the main problems encountered with the brass bundles (ammoniacal corrosion, erosion of the peripheral tubes, vibrations of the tubes), with the titanium bundles, with the tubular plates, the tubes-tubular plates assemblies, the coatings of the condenser water chamber (sea water), the vapor by-pass and with the air inlet. Analysis of the in service performances such as condensation pressure, oxygen content and availability [fr

  8. Non azeotrope mixing refrigerating fluids condensation outside of an horizontal tubes stack; Condensation de melanges non azeotropes de fluides frigorigenes a l'exterieur d'un faisceau de tubes horizontaux

    Energy Technology Data Exchange (ETDEWEB)

    Signe, J.Ch.

    1999-04-16

    The development of non-azeotrope mixing, as regular refrigerating fluids substitute, calls in question the experience for the design of refrigerating and cooling machinery. Studies to better understand these fluids behaviour are necessary. The aim of this thesis is the knowledge enlargement on the pure fluids and non azeotrope mixing condensation, outside of a tubes stack, and to simulate the heat transfers. The tubes stack is a condenser, type TEMA X often used in refrigerating machinery. The binary mixing HFC 134a-HFC23, allows a large sliding scale. (A.L.B.)

  9. Multifrequency Eddy current testing of heat exchange tubes with a rotating probe

    International Nuclear Information System (INIS)

    Levy, R.

    1982-01-01

    Multi-frequency eddy current analyses have been used in France industrially since 1975. In light of the experienced gained during many steam generator inspections, this technique was applied to the examination of sheet and tube heat exchangers featuring tubes in very different materials such as copper, stainless steel and titanium. The principle of multi-frequency Eddy current inspection is first reviewed, using the example of a condenser with nickel alloy tubes (Inconel, Incoloy). This is followed by the description of a specific application of this technique to a condenser with titanium tubes, analyzed with a rotating local probe [fr

  10. Condensation of refrigerants in horizontal microfin tubes: comparison of prediction methods for heat transfer

    Energy Technology Data Exchange (ETDEWEB)

    Wang, H S; Honda, H [Kyushu University, Fukuoka (Japan). Institute of Advanced Material Study

    2003-06-01

    A comparison was made between the predictions of previously proposed empirical correlations and theoretical model and available experimental data for the heat transfer coefficient during condensation of refrigerants in horizontal microfin tubes. The refrigerants tested were R11, R123, R134a, R22 and R410A. Experimental data for six tubes with the tube inside diameter at fin root of 6.49-8.8 8 mm, the fin height of 0.16-0.24 mm, fin pitch of 0.34-0.53 mm and helix angle of groove of 12-20{sup o} were adopted. The r.m.s. error of the predictions for all tubes and all refrigerants decreased in the order of the correlations proposed by Luu and Bergies [ASHRAE Trans. 86 (1980) 293], Cavallini et al. Condensation of new refrigerants inside smooth and enhanced tubes. In: Proc. 19th Int. Cong. Refrigeration, vol. IV, Hague, The Netherlands, 1995. p. 105-114, Shikazono et al. [Trans. Jap. Sco. Mech. Engrs. 64 (1995) 196], Kedzierski and Goncalves [J. Enhanced Heat Transfer 6 (1999) 16], Yu and Koyama [Yu J, Koyama S. Condensation heat transfer of pure refrigerants in microfin tubes. In: Proc. Int. Refrigeration Conference at Purdue Univ., West Lafayette, USA, 1998. p. 325-330], and the theoretical model proposed by Wang et al. [Int. J. Heat Mass Transfer 45 (2002) 1513]. (author)

  11. Thermal hydraulics-I. 5. Local Heat Transfer and Flow Transition in U-Tubes During a Reflux Condensation Mode

    International Nuclear Information System (INIS)

    Chun, Moon-Hyun; Lee, Kyung-Won; Chu, In-Cheol

    2001-01-01

    For the safety analysis of nuclear power plant (NPP) mid-loop operation, it is very important to determine the mechanisms governing heat transfer and to investigate the factors affecting the onset of flooding in steam generator U-tubes during a reflux condensation mode. The main purpose of this work is to evaluate the local condensation heat transfer with and without non-condensable gases (air) and to investigate the effect of multiple U-tubes on the onset of flooding during a reflux condensation. A schematic diagram of the experimental apparatus is shown in Fig. 1. In the present study, five U-tubes with the same inner diameter of 0.0162 m are installed in a rectangular pool to simulate the geometry of the pressurized water reactor steam generator U-tubes of the Korea standard NPP (KSNPP) (Ulchin Units 3 and 4, inner diameter≅0.01692 m). One central U-tube (2.8 m high) is fully equipped with 32 thermocouples to evaluate the heat transfer coefficients (HTCs), whereas the others (i.e., two short tubes 2.5 m high and two long tubes 3.3 m high) are used to investigate the effect of multiple U-tubes on the flooding phenomena. The local heat flux through a U-tube wall was evaluated from the temperature gradient of the U-tube wall. The onset of flooding, on the other hand, was determined by measuring the change in pressure difference between the bottom and the top of the U-tubes. A total of 512 data for local condensation HTCs (108 for pure steam flow and 404 for steam-air flow conditions, respectively) have been obtained for various flow rates of steam and air under atmospheric conditions. The experimental results for a pure steam flow, in general, agree with the classical Nusselt theory, as shown in Fig. 2. At a relatively high-steam Reynolds number (i.e., >3500), however, the present data are slightly higher than the values predicted by Nusselt theory because of the influence of interfacial shear. In the case of pure steam condensation, the condensate film acts as

  12. Corrosion behaviour of hyper duplex stainless steel in various metallurgical conditions for sea water cooled condensers

    International Nuclear Information System (INIS)

    Singh, Umesh Pratap; Kain, Vivekanand; Chandra, Kamlesh

    2011-01-01

    The sea water cooled condensers have to resist severe corrosion as marine environment is the most corrosive natural environment. Copper alloys are being phased out due to difficulties in water chemistry control and Titanium base alloys are extremely expensive. Austenitic stainless steels (SS) remain prone to localized corrosion in marine environments hence not suitable. These heat exchangers operate at temperatures not exceeding 50 deg C and at very low pressures. The tubes of these heat exchangers are joined to the carbon steel tube sheets by roll expansion or by roll expansion followed by seam welding. These conditions are expected to affect the localized corrosion resistance of the tube in roll joined region due to cold working and in the tube-tube sheet welded joint due to thermal effects of welding. In this study, the localized corrosion behaviour of a Hyper Duplex Stainless Steel (HDSS) has been evaluated, and compared with other materials e.g. types 304L SS, 316L SS, Duplex SS 2205, Titanium grade - 2, and Al Brass. The evaluation is done in three metallurgical conditions (a) as received, (b) cold rolled and (c) welded condition in synthetic sea water at room temperature and at 50 deg C to assess the resistance to crevice, pitting and stress corrosion cracking using standard ASTM exposure and electrochemical techniques. The results provide comparative assessment of these alloys and show their susceptibility in the three metallurgical conditions as encountered in condensers. Hyper-duplex SS has been shown to be highly resistant in sea water for the condenser tubing application. (author)

  13. Comparison of tubeside condensation and evaporation characteristics of smooth and enhanced heat transfer 1EHT tubes

    International Nuclear Information System (INIS)

    Kukulka, David J.; Smith, Rick; Li, Wei

    2015-01-01

    Results are presented here from an experimental investigation that was performed to evaluate the inside condensation and evaporation heat transfer of R410A, R22 and R32 that took place in a 12.7 mm (0.5 in) O.D. horizontal copper tube at low mass fluxes. Tubes considered in this evaluation consisted of a smooth tube (inner diameter 11.43 mm) and a newly developed enhanced surface Vipertex™ 1EHT tube. Heat transfer enhancement is an important factor in obtaining energy efficiency improvements in a variety of heat transfer applications. Utilization of enhanced heat transfer tubes is often utilized in the development of high performance air conditioning and refrigeration systems. Vipertex™ has designed and produced these surfaces through three dimensional material surface modifications which produces flow optimized, enhanced heat transfer tubes that increase heat transfer. Heat transfer enhancement plays an important role in improving energy efficiencies and developing high performance thermal systems. This study details the evaluation of the in-tube evaporation and condensation that takes place in these tubes over a wide range of conditions. The test apparatus utilized included a straight horizontal test section with an active length heated by water circulated in the surrounding annulus. Constant heat flux was maintained and refrigerant quality varied. In-tube evaporation measurements of R22, R32 and R410A are reported for evaporation at 10 °C with mass flow rates in the range of 15–40 kg h"−"1. Single phase measurements are reported for mass flow rates from 15 kg h"−"1 to 80 kg h"−"1. Condensation tests were conducted at a saturation temperature of 47 °C, with an inlet quality of 0.8 and an outlet quality of 0.1. In a comparison to smooth tubes, the average heat transfer coefficients for the Vipertex 1EHT tube exceeded those of a smooth tube. Average evaporation and condensation heat transfer coefficients for R22, R32 and R410A in the 1EHT

  14. KTA 625 alloy tube with excellent corrosion resistance and heat resistance

    International Nuclear Information System (INIS)

    Fujiwara, Kazuo; Kadonaga, Toshiki; Kikuma, Seiji.

    1982-01-01

    The problems when seamless tubes are produced by using nickel base 625 alloy (61Ni-22Cr-9Mo-Cb) which is known as a corrosion resistant and heat resistant alloyF were examined, and the confirmation experiment was carried out on its corrosion resistance and heat resistance. Various difficulties have been experienced in the tube making owing to the characteristics due to the chemical composition, but they were able to be solved by the repeated experiments. As for the characteristics of the product, the corrosion resistance was excellent particularly in the environment containing high temperature, high concentration chloride, and also the heat resistance was excellent in the wide temperature range from normal temperature to 1000 deg C. From these facts, the wide fields of application are expected for these alloy tubes, including the evaporation and concentration equipment for radioactive wastes in atomic energy field. Expecting the increase of demand hereafter, Kobe Steel Ltd. examined the problems when seamless tubes are produced from the 625 alloy by Ugine Sejournet process. The aptitude for tube production such as the chemical composition, production process and the product characteristics, the corrosion resistance against chloride, hydrogen sulfide, polythionic and other acids,F the high temperature strength and oxidation resistance are reported. (Kako, I.)

  15. Corrosion performance of Al-Si-Cu hypereutectic alloys in a synthetic condensed automotive solution

    Directory of Open Access Journals (Sweden)

    Hamilta de Oliveira Santos

    2005-06-01

    Full Text Available In this investigation the corrosion resistance of four Al-Si hypereutectic alloys in a solution typical of condensate from automotive fuel combustion products, and referred to here as synthetic condensed automotive solution, has been studied. Three commercial alloys that are used for cylinder liners, and a laboratory made alloy, were studied by electrochemical impedance spectroscopy and measurements were taken after increasing times of immersion in this solution. Comparison of the electrochemical response of the four alloys in the corrosive solution was carried out. Although the mechanisms by which the four alloys corroded were similar, the results indicated differences in corrosion resistances of these alloys, and these differences could be related to their microstructures. The laboratory prepared alloy showed increased susceptibility to pitting corrosion compared to the commercial alloys. The surfaces of the alloys were examined, before and after the corrosion test, by scanning electron microscopy and analyzed by energy dispersive spectroscopy. The results indicated preferential attack of the aluminium matrix phase in all the alloys. The alloy with higher copper content and prepared by spray forming was more susceptible to pitting compared to the other alloys. The EIS response at low frequencies indicated a diffusion-controlled process, probably that of oxygen to the alloy interface.

  16. Wear behavior of 2-1/4 Cr-1Mo tubing against alloy 718 tube-support material in sodium-cooled steam generators

    International Nuclear Information System (INIS)

    Wilson, W.L.

    1983-05-01

    A series of prototypic steam generator 2-1/4 Cr-1 Mo tube/alloy 718 tube support plate wear tests were conducted in direct support of the Westinghouse Nuclear Components Division -- Breeder Reactor Components Project Large Scale steam Generator design. The initial objective was to verify the acceptable wear behavior of softer, ''over-aged'' alloy 718 support plate material. For all interfaces under all test conditions, resultant wear damage was adhesive in nature with varying amounts of 2-1/4 Cr-1 Mo tube material being adhesively transferred to the alloy 718 tube supports. Maximum tube wear depths exceeded the initially established design allowable limit of 127 μm (.005 in.) at 17 of the 18 interfaces tested. A decrease in contact stresses produced acceptable tube wear depths below a readjusted maximum design allowable value of 381 μm (.015 in.). Additional conservatisms associated with the simulation of a 40-year lifetime of rubbing in a one-week laboratory test provided further confidence that the 381 μm maximum tube wear allowance would not be exceeded in service. Softer, ''over-aged'' alloy 718 material was found to produce slightly less wear damage on 2-1/4 Cr-1 Mo tubing than fully age hardened material. Also, air formed oxide films on the alloy 718 reduced initial tube wear and delayed the onset of adhesive surface damage. However, at high surface stress levels, these films were not sufficiently stable to provide adequate long term protection from adhesive wear. The results of the present work and those of previous test programs suggest that the successful in-sodium tribological performance of 2-1/4 Cr-1 Mo/alloy 718 rubbing couples is dependent upon the presence of lubricative surface films, such as oxides and/or surface reaction or deposition products. 11 refs., 13 figs., 4 tabs

  17. Assessment of RELAP5/MOD3 with condensation experiment for pure steam condensation in a vercal tube

    Energy Technology Data Exchange (ETDEWEB)

    Kim, Sang Jae; No, Hee Cheon [Korea Advanced Institute of Science and Technology, Taejon (Korea, Republic of)

    1999-12-31

    The film condensation models in RELAP5/MOD3.1 and RELAP5/MOD3.2 are assessed with the data of experiment performed in the scaled down condensation experimental facility with a single vertical tube of inner diameter of 46 mm in the range of pressure 0.1 {approx} 7.5 MPa for the PSCS(Passive Secondary Condenser System). Both MOD3.1 and MOD3.2 don`t shows any reliable predictions of the experimental data. The RELAP5/MOD3.1 overpredicts the heat transfer coefficients of experiment, whereas the RELAP5/MOD3.2 underpredicts those data. It is recommended that the film condensation model in RELAP5/MOD3.2 should be modified to have a larger heat transfer coefficient than those of the present model to give the reliable predictions. 7 refs., 6 figs., 1 tab. (Author)

  18. Assessment of RELAP5/MOD3 with condensation experiment for pure steam condensation in a vercal tube

    Energy Technology Data Exchange (ETDEWEB)

    Kim, Sang Jae; No, Hee Cheon [Korea Advanced Institute of Science and Technology, Taejon (Korea, Republic of)

    1998-12-31

    The film condensation models in RELAP5/MOD3.1 and RELAP5/MOD3.2 are assessed with the data of experiment performed in the scaled down condensation experimental facility with a single vertical tube of inner diameter of 46 mm in the range of pressure 0.1 {approx} 7.5 MPa for the PSCS(Passive Secondary Condenser System). Both MOD3.1 and MOD3.2 don`t shows any reliable predictions of the experimental data. The RELAP5/MOD3.1 overpredicts the heat transfer coefficients of experiment, whereas the RELAP5/MOD3.2 underpredicts those data. It is recommended that the film condensation model in RELAP5/MOD3.2 should be modified to have a larger heat transfer coefficient than those of the present model to give the reliable predictions. 7 refs., 6 figs., 1 tab. (Author)

  19. Fundamental basis and implementation of shell and tube heat exchanger project design: condenser and evaporator study

    Science.gov (United States)

    Dalkilic, A. S.; Acikgoz, O.; Tapan, S.; Wongwises, S.

    2016-12-01

    A shell and tube heat exchanger is used as a condenser and an evaporator in this theoretical study. Parametric performance analyses for various actual refrigerants were performed using well-known correlations in open sources. Condensation and evaporation were occurred in the shell side while the water was flowing in the tube side of heat exchanger. Heat transfer rate from tube side was kept constant for condenser and evaporator design. Condensing temperatures were varied from 35 to 60 °C whereas evaporating temperatures were ranging from -15 to 10 °C for the refrigerants of R12, R22, R134a, R32, R507A, R404A, R502, R407C, R152A, R410A and R1234ZE. Variation of convective heat transfer coefficients of refrigerants, total heat transfer coefficients with Reynolds numbers and saturation temperatures were given as validation process considering not only fouling resistance and omission of it but also staggered (triangular) and line (square) arrangements. The minimum tube lengths and necessary pumping powers were calculated and given as case studies for the investigated refrigerants considering validation criteria. It was understood that refrigerant type, fouling resistance and arrangement type are one of the crucial issues regarding the determination of heat exchanger's size and energy consumption. Consequently, R32 and R152a were found to require the shortest tube length and lowest pumping power in the condenser, whereas R507 and R407C have the same advantages in the evaporator. Their heat transfer coefficients were also determined larger than others as expectedly.

  20. Condensation heat transfer and pressure drop of R-410A in flat aluminum multi-port tubes

    Science.gov (United States)

    Kim, Nae-Hyun

    2018-02-01

    Brazed heat exchangers with aluminum flat multi-port tubes are being used as condensers of residential air-conditioners. In this study, R-410A condensation tests were conducted in four multi-port tubes having a range of hydraulic diameter (0.78 ≤ Dh ≤ 0.95 mm). The test range covered the mass flux from 100 to 400 kg/m2 s and the heat flux at 3 kW/m2, which are typical operating conditions of residential air conditioners. Results showed that both the heat transfer coefficient and the pressure drop increased as the hydraulic diameter decreased. The effect of hydraulic diameter on condensation heat transfer was much larger than the predictions of existing correlations for the range of investigation. Comparison of the data with the correlations showed that some macro-channel tube correlations and mini-channel tube correlations reasonably predicted the heat transfer coefficient. However, macro-channel correlations highly overpredicted the pressure drop data.

  1. Stratified flow model for convective condensation in an inclined tube

    International Nuclear Information System (INIS)

    Lips, Stéphane; Meyer, Josua P.

    2012-01-01

    Highlights: ► Convective condensation in an inclined tube is modelled. ► The heat transfer coefficient is the highest for about 20° below the horizontal. ► Capillary forces have a strong effect on the liquid–vapour interface shape. ► A good agreement between the model and the experimental results was observed. - Abstract: Experimental data are reported for condensation of R134a in an 8.38 mm inner diameter smooth tube in inclined orientations with a mass flux of 200 kg/m 2 s. Under these conditions, the flow is stratified and there is an optimum inclination angle, which leads to the highest heat transfer coefficient. There is a need for a model to better understand and predict the flow behaviour. In this paper, the state of the art of existing models of stratified two-phase flows in inclined tubes is presented, whereafter a new mechanistic model is proposed. The liquid–vapour distribution in the tube is determined by taking into account the gravitational and the capillary forces. The comparison between the experimental data and the model prediction showed a good agreement in terms of heat transfer coefficients and pressure drops. The effect of the interface curvature on the heat transfer coefficient has been quantified and has been found to be significant. The optimum inclination angle is due to a balance between an increase of the void fraction and an increase in the falling liquid film thickness when the tube is inclined downwards. The effect of the mass flux and the vapour quality on the optimum inclination angle has also been studied.

  2. Experimental study on condensation heat transfer enhancement and pressure drop penalty factors in four microfin tubes

    Energy Technology Data Exchange (ETDEWEB)

    Han, D [Korea University, Seoul (Korea). Institute of Advanced Machinery Design; Lee, Kyu-Jung [Korea University, Seoul (Korea). Dept. of Mechanical Engineering

    2005-08-01

    Heat transfer and pressure drop characteristics of four microfin tubes were experimentally investigated for condensation of refrigerants R134a, R22, and R410A in four different test sections. The microfin tubes examined during this study consisted of 8.92, 6.46, 5.1, and 4 mm maximum inside diameter. The effect of mass flux, vapor quality, and refrigerants on condensation was investigated in terms of the heat transfer enhancement factor and the pressure drop penalty factor. The pressure drop penalty factor and the heat transfer enhancement factor showed a similar tendency for each tube at given vapor quality and mass flux. Based on the experimental data and the heat-momentum analogy, correlations for the condensation heat transfer coefficients in an annular flow regime and the frictional pressure drops are proposed. (author)

  3. Effects of fin shape on condensation in herringbone microfin tubes

    Energy Technology Data Exchange (ETDEWEB)

    Miyara, Akio [Saga University (Japan). Dept. of Mechanical Engineering; Otsubo, Yusuke; Ohtsuka, Satoshi; Mizuta, Yoshihiko [Saga University (Japan). Graduate School of Science and Engineering

    2003-06-01

    Effects of fin height and helix angle on condensation inside a herringbone microfin tube have been experimentally investigated with five types of herringbone microfin tubes. Heat transfer coefficients are about 2-4 times higher than that of the helical microfin tube under high mass velocity conditions. In the low mass velocity, they are equal to that of the helical microfin tube. The heat transfer enhancement increases with fin height up to 0.18 mm; higher fin heights show enhancement values similar to the 0.18 mm results. Pressure drop increases with the fin height. Larger helix angle yields higher heat transfer and higher pressure drop. For the lowest fin and/or smallest helix angle, the pressure drop is comparable with that of the helical microfin tube, while the heat transfer enhancement is higher. The enhancement mechanism is discussed from flow pattern observations. Effect of mass transfer resistance for R410A is estimated and negligible effects have been proved. (author)

  4. Analysis study of the condensation heat transfer coefficient in the presence of noncondensable on PCCS vertical condenser tube using MARS-KS

    Energy Technology Data Exchange (ETDEWEB)

    Choi, Dong jae; Jang, Yeong jun; Lee, Yeon-Gun [Jeju National University, Jeju (Korea, Republic of); Kim, Sin [Chung-Ang University, Seoul (Korea, Republic of)

    2015-10-15

    The Passive Containment Cooling System (PCCS) to be introduced in advanced LWRs removes released energy to an external heat sink by a naturally driven flow. Containment through the condensation heat transfer phenomenon in the event of the loss of coolant accident (LOCA) or main steam line break (MSLB). As the released steam pressurizes the containment, the PCCS will activate to transport the decay heat In this study, a numerical analysis of the condensation heat transfer coefficients on the PCCS condenser tube is conducted using the MARS-KS code. The condensation heat transfer coefficients are obtained from JNU condensation tests performed on a 1000 long and 40 mm O.D. tube. The analysis condition covers 2 and 4 bar for the air mass fraction ranging from 0.1 to 0.8. The JNU single vertical condensation experimental results, Uchida's and Dehbi's correlation compared with the MARS-KS code's results at 2 and 4 bar. Experimental results and MARS-KS predicted heat transfer coefficient is different from the thermal resistances and Wall subcooling. An average relative error is 18.8% and 15% at 2 and 4 bar, respectively. Uchida's correlation is considered the noncondensable gas mass fraction only. Therefore, that is lower than MARS-KS results at 4 bar. Dehbi's correlation affected by ratio of the height-to-diameter, so its results are higher condensation heat transfer coefficient than MARS-KS predicted results.

  5. Effect of sponge ball cleaning on removing barnacles in condenser tubes

    Energy Technology Data Exchange (ETDEWEB)

    Mimura, K; Minamoto, K; Kyohara, S [Kobe Steel Ltd. (Japan)

    1977-07-01

    Considering environmental protection, the recent tendency has been to give up chlorination of cooling water for power stations. The experimental results show that cooling sea-water without chlorination cannot get rid of barnacles which grow inside condenser tubes when the speed of the cooling water is less than 1 m/s. Cleaning by sponge balls 2 -- 3 times a week is found to be effective for both barnacle prevention and inactive film formation on the tube surface.

  6. Refrigerant charge, pressure drop, and condensation heat transfer in flattened tubes

    Energy Technology Data Exchange (ETDEWEB)

    Wilson, M J; Newell, T A; Chato, J C [University of Illinois, Urbana, IL (United States). Dept. of Mechanical and Industrial Engineering; Infante Ferreira, C A [Delft University of Technology (Netherlands). Laboratory for Refrigeration and Indoor Climate Control

    2003-06-01

    Horizontal smooth and microfinned copper tubes with an approximate diameter of 9 mm were successively flattened in order to determine changes in flow field characteristics as a round tube is altered into a flattened tube profile. Refrigerants R134a and R410A were investigated over a mass flux range from 75 to 400 kg m{sup -2} s{sup -}2{sup 1} and a quality range from approximately 10-80%. For a given refrigerant mass flow rate, the results show that a significant reduction in refrigerant charge is possible. Pressure drop results show increases of pressure drop at a given mass flux and quality as a tube profile is flattened. Heat transfer results indicate enhancement of the condensation heat transfer coefficient as a tube is flattened. Flattened tubes with an 18{sup o} helix angle displayed the highest heat transfer coefficients. Smooth tubes and axial microfin tubes displayed similar levels of heat transfer enhancement. Heat transfer enhancement is dependent on the mass flux, quality and tube profile. (author)

  7. Salvaging of service exposed cast alloy 625 cracker tubes of ammonia based Heavy Water Plants

    International Nuclear Information System (INIS)

    Kumar, Niraj; Misra, B.; Mahajan, M.P.; Mittra, J.; Sundararaman, M.; Chakravartty, J.K.

    2006-01-01

    In ammonia based heavy water plants, cracking of ammonia vapour, enriched in deuterium is carried out inside a cracker tube, packed with catalyst. These cracker tubes are made of alloy 625 (either wrought or cast) having dimensions of about 12.5 metres long, 88 mm outer diameter and 7.9 mm wall thickness. Seventy such tubes are housed in a typical ammonia cracker unit. The anticipated design life of such tube is 1,00,000 hrs. when operated at 720 degC based on creep as main degradation mechanism. Presently, these tubes are being operated at 680 degC skin temperature. Alloy 625 tubes are costly and normally not manufactured in India and are being imported. The cast alloy 625 cracker tubes have outlived their design life of 100,000 hrs. Therefore it has been decided to salvage the cast cracker tubes and extend the life further as it had already been done for wrought tubes. Similar to the earlier attempt of resolutionising of wrought alloy 625 tubes, efforts are in progress to salvage these cast tubes. In this study, cast tubes samples were subjected to solution-annealing treatment at two different temperatures, 1100degC and 1160degC respectively for two hrs. Mechanical properties along with the microstructure of the samples, which were resolutionized at 1160degC were comparable with that of virgin material. The 12.5 metres long cast alloy 625 cracker tubes will also be shortly solution-annealed in a specially designed resistance heating furnace after completing some more tests. (author)

  8. Characteristics of Pilger Die Materials for Nuclear Zirconium Alloy Tubes

    International Nuclear Information System (INIS)

    Park, Ki Bum; Kim, In Kyu; Park, Min Young; Kahng, Jong Yeol; Kim, Sun Doo

    2011-01-01

    KEPCO Nuclear Fuel Company's (KEPCO NF) tube manufacturing facility, Techno Special Alloy (TSA) Plant, has started cold pilgering operation since 2008. It is obvious that the cold pilgering process is one of the key processes controlling the quality and the characteristics of the tubes manufactured, i.e. nuclear zirconium alloy tube in KEPCO NF. Cold pilgering is a rolling process for forming metal tubes in which diameter and wall thickness are reduced in a number of forming steps, using ring dies at outside of the tube and a curved mandrel at inside to reduce tube cross sections by up to 90 percent. The OD size of tube is reduced by a pair of dies, and ID size and wall thickness is controlled simultaneously by mandrel. During the cold pilgering process, both tools are the critical components for providing qualified tube. Development of pilger die and mandrel has been a significant importance in the zirconium tube manufacturing and a major goal of KEPCO NF. The objective of this study is to evaluate the life time of pilger die during pilgering. Therefore, a comparison of the heat treatment and mechanical properties of between AISI 52100 and AISI H13 materials was made in this study

  9. Numerical modeling of condensation from vapor-gas mixtures for forced down flow inside a tube

    International Nuclear Information System (INIS)

    Yuann, R.Y.; Schrock, V.E.; Chen, Xiang, M.

    1995-01-01

    Laminar film condensation is the dominant heat transfer mode inside tubes. In the present paper direct numerical simulation of the detailed transport process within the steam-gas core flow and in the condensate film is carried out. The problem was posed as an axisymmetric two dimensional (r, z) gas phase inside an annular condensate film flow with an assumed smooth interface. The fundamental conservation equations were written for mass, momentum, species concentration and energy in the gaseous phase with effective diffusion parameters characterizing the turbulent region. The low Reynolds number two equation κ-ε model was employed to determine the eddy diffusion coefficients. The liquid film was described by similar formulation without the gas species equation. An empirical correlation was employed to correct for the effect of film waviness on the interfacial shear. A computer code named COAPIT (Condensation Analysis Program Inside Tube) was developed to implement numerical solution of the fundamental equations. The equations were solved by a marching technique working downstream from the entrance of the condensing section. COAPIT was benchmarked against experimental data and overall reasonable agreement was found for the key parameters such as heat transfer coefficient and tube inner wall temperature. The predicted axial development of radial profiles of velocity, composition and temperature and occurrence of metastable vapor add insight to the physical phenomena

  10. Numerical modeling of condensation from vapor-gas mixtures for forced down flow inside a tube

    Energy Technology Data Exchange (ETDEWEB)

    Yuann, R Y [Taiwan Power Company, Taipei (Taiwan, Province of China); Schrock, V E [Univ. of California, Berkeley, CA (United States); Chen, Xiang

    1995-09-01

    Laminar film condensation is the dominant heat transfer mode inside tubes. In the present paper direct numerical simulation of the detailed transport process within the steam-gas core flow and in the condensate film is carried out. The problem was posed as an axisymmetric two dimensional (r, z) gas phase inside an annular condensate film flow with an assumed smooth interface. The fundamental conservation equations were written for mass, momentum, species concentration and energy in the gaseous phase with effective diffusion parameters characterizing the turbulent region. The low Reynolds number two equation {kappa}-{epsilon} model was employed to determine the eddy diffusion coefficients. The liquid film was described by similar formulation without the gas species equation. An empirical correlation was employed to correct for the effect of film waviness on the interfacial shear. A computer code named COAPIT (Condensation Analysis Program Inside Tube) was developed to implement numerical solution of the fundamental equations. The equations were solved by a marching technique working downstream from the entrance of the condensing section. COAPIT was benchmarked against experimental data and overall reasonable agreement was found for the key parameters such as heat transfer coefficient and tube inner wall temperature. The predicted axial development of radial profiles of velocity, composition and temperature and occurrence of metastable vapor add insight to the physical phenomena.

  11. A thermodynamic approach on vapor-condensation of corrosive salts from flue gas on boiler tubes in waste incinerators

    International Nuclear Information System (INIS)

    Otsuka, Nobuo

    2008-01-01

    Thermodynamic equilibrium calculation was conducted to understand the effects of tube wall temperature, flue gas temperature, and waste chemistry on the type and amount of vapor-condensed 'corrosive' salts from flue gas on superheater and waterwall tubes in waste incinerators. The amount of vapor-condensed compounds from flue gases at 650-950 deg. C on tube walls at 350-850 deg. C was calculated, upon combustion of 100 g waste with 1.6 stoichiometry (in terms of the air-fuel ratio). Flue gas temperature, rather than tube wall temperature, influenced the deposit chemistry of boiler tubes significantly. Chlorine, sulfur, sodium, potassium, and calcium contents in waste affected it as well

  12. Enhanced Condensation Heat Transfer

    Science.gov (United States)

    Rose, John Winston

    The paper gives some personal observations on various aspects of enhanced condensation heat transfer. The topics discussed are external condensation (horizontal low-finned tubes and wire-wrapped tubes), internal condensation (microfin tubes and microchannels) and Marangoni condensation of binary mixtures.

  13. Heat transfer during condensation of HFC-134a and R-404A inside of a horizontal smooth and micro-fin tube

    Energy Technology Data Exchange (ETDEWEB)

    Sapali, S N [Govt. College of Engineering, Department of Mechanical Engineering, Shivaji Nagar, Pune, Maharashtra 411 005 (India); Patil, Pradeep A [AISSMS College of Engineering, Pune University, Mechanical Engineering Department, Kennedy Road, Near R.T.O., Pune, Maharashtra 411 001 (India)

    2010-11-15

    In recent small and medium capacity refrigeration systems, the condenser tubes are provided with micro-fins from inside. The vapour refrigerant at the compressor outlet and the condenser inlet is in superheat state. As it advances in the condenser it is in two phases and at the outlet it is in sub cooled liquid. The heat transfer coefficient (HTC) during condensation of HFC-134a and R-404A in a smooth (8.56 mm ID) and micro-fin tubes (8.96 mm ID) are experimentally investigated. Different from previous studies, the present experiments are performed for various condensing temperatures, with superheating and sub cooling and using hermetically sealed compressor. The test runs are done at average saturated condensing temperatures ranging from 35 C to 60 C. The mass fluxes are between 90 and 800 kg m{sup -2} s{sup -1}. The experimental results indicate that the average HTC increases with mass flux but decreases with increasing condensing temperature for both smooth and micro-fin tubes. The average condensation HTCs of HFC-134a and R-404A for the micro-fin tubes were 1.5-2.5 and 1.3-2 times larger than that in smooth tube respectively. The HTCs for R-404A are less than that of HFC-134a. New correlations based on the data gathered during the experimentation for predicting condensation HTCs are proposed for wide range of operating conditions. (author)

  14. Possible first occurrence of external corrosion on alloy 600TT tubes in France

    International Nuclear Information System (INIS)

    Boccanfuso, M.; Thebault, Y.; Massini, B.; Bigne, L.

    2015-01-01

    During the last decade, in different countries, several occurrences of external corrosion have been identified on steam generator (SG) tube bundles equipped with thermally treated 600 alloy. In France, this feedback leads EDF to enhance the SG inspection program. Nevertheless, until now, no damage of this type was reported. Recently, during in-service inspection at the Cattenom plant on a SG equipped with alloy 600TT tubes, Eddy current tests have highlighted a signal that could be related to external corrosion. The tube was removed and sent to the EDF hot laboratory for destructive examinations. Various exams were performed at different scales to characterize the causes of this NDT signal, the material properties and the residual stresses. The assessments carried out on the tube conclude that the source of the damage is external intergranular stress corrosion cracking, also called ODSCC (Outside Diameter Stress Corrosion Cracking) making it the first occurrence on the tube bundles made of alloy 600TT in the French fleet. This first case of 600 TT ODSCC in France is an unexpected and particular one, because of its altitude in the full mechanical rolling area. This is reinforced by the low number of occurrences noted to date (only one after nearly 30 years of operation of alloy 600TT tube bundles). International (Biblis) OPEX had identified recent IGSCC with cracks initiated and propagated in the tubesheet. For this case, the scenario considered requires highly restrictive conditions (tube in the sludge zone and on the periphery of the tube bundle, including the tube lane) and may explain the singular nature of the Cattenom tube

  15. Experimental study of air-cooled water condensation in slightly inclined circular tube using infrared temperature measurement technique

    Energy Technology Data Exchange (ETDEWEB)

    Kim, Hyungdae [Nuclear Engineering Department, Kyung Hee University, Yongin (Korea, Republic of); Kwon, Tae-Soon [Korea Atomic Energy Research Institute, Daedeok-daero 989-111, Yuseong-gu, Daejeon 305-353 (Korea, Republic of); Kim, Dong Eok, E-mail: dekim@knu.ac.kr [Department of Precision Mechanical Engineering, Kyungpook National University, Sangju (Korea, Republic of)

    2016-11-15

    Highlights: • Air-cooled condensation experiments in an inclined Pyrex glass tube were performed. • High-resolution wall temperature data and flow regime formations could be obtained. • The local heat flux was strongly dependent on the air-side heat transfer. • A CFD analysis was conducted for calculating the local heat flux distribution. - Abstract: This study presents the results of an investigation of the air-cooled water condensation heat transfer characteristics inside a slightly inclined circular tube made of transparent Pyrex glass. The high-resolution wall temperature data and stratified film formations could be obtained with the assistance of an infrared (IR) thermometry technique and side-view visualization using a CCD camera. In all experimental cases, the condensation flow patterns were in the fully-stratified flow region. In addition, the experimentally measured void fraction corresponded well with the logarithmic mean void fraction model. The local temperature differences in the cooling air flow across the condenser tube and high-resolution temperature profiles on the tube’s outer wall were obtained in the experimental measurements. Under the experimental conditions of this study, the local heat flux distributions in the longitudinal direction of the test tube were strongly dependent on the cooling air velocity. And, with the help of IR thermometry, the tube outer wall temperature data at 45 local points could be measured. From the data, the asymmetry distribution of the local wall temperatures and the accurate location of the transition from two-phase mixture to single phase liquid inside the tube could be obtained. Also, the analysis of the thermal resistances by condensation, wall conduction and air convection showed that the air convective heat transfer behavior can play a dominant role to the local heat transfer characteristics. Finally, in order to obtain the local heat flux distribution along the tube’s outer wall, a two

  16. Field synergy characteristics in condensation heat transfer with non-condensable gas over a horizontal tube

    Directory of Open Access Journals (Sweden)

    Junxia Zhang

    2017-05-01

    Full Text Available Field synergy characteristics in condensation heat transfer with non-condensable gas (NCG over a horizontal tube were numerically simulated. Consequently, synergy angles between velocity and pressure or temperature gradient fields, gas film layer thickness, and induced velocity and shear stress on gas–liquid interface were obtained. Results show that synergy angles between velocity and temperature gradient fields are within 73.2°–88.7° and ascend slightly with the increment in mainstream velocity and that the synergy is poor. However, the synergy angle between velocity and pressure gradient fields decreases intensively with the increase in mainstream velocity at θ ≤ 30°, thereby improving the pressure loss. As NCG mass fraction increases, the gas film layer thickness enlarges and the induced velocity and shear stress on gas–liquid interface decreases. The synergy angles between velocity and temperature gradient fields increase, and the synergy angles between velocity and pressure gradient fields change at θ = 70°, decrease at θ 70°. When the horizontal tube circumference angle increases, the synergy angles between velocity and temperature or pressure gradient fields decrease, the synergy between velocity and pressure fields enhances, and the synergy between velocity and temperature fields degrades.

  17. Determination of heat transfer coefficient with vapor condensation inside the tubes diesel’s radiator sections

    Directory of Open Access Journals (Sweden)

    Y.K.Sklifus

    2012-12-01

    Full Text Available The article presents the calculation of heat transfer coefficient during condensation of steam, the mathematical model of temperature distribution in the gas and liquid phases of the coolant and the model of the formation of the condensate film on the walls of the tubes.

  18. Stress relief treatment of Alloy 600 steam generator tubing

    International Nuclear Information System (INIS)

    Rooyen, D. van; Cragnolino, C.

    1994-01-01

    The intergranular stress corrosion cracking (IGSCC) of Alloy 600 tubing in the primary side of operating steam generators is the subject of this investigation. The objective of the program was to examine the feasibility of heat treatment to alleviate the IGSCC problem. In addition to this, tests were also performed to examine the IGSCC susceptibility of nuclear grade Alloy 600 tubing obtained from various sources. Examination of temperature-time combinations that may hold potential for improved IGSCC resistance of the transition regions of tubes expanded into tube sheet holes was done. The combinations fall in two categories. One is of short duration and relatively high temperature, where induction is the best method of heating because the treatment only lasts from some tens of seconds to a few minutes. The other is carried out in a lower temperature range and lasts for several hours. This latter combination of temperatures and times is considered for the so-called global heat treatment of entire tube sheet. To assess the effect of these treatments, reverse U-bend testing in high purity deaerated water containing an overpressure of hydrogen was employed and several heats of Alloy 600 were compared in tests at 365 degrees C, which is well above actual operating temperatures of steam generators, but provides an accelerated test procedure. Results of furnace heating in the range of 550-610 degrees C indicated improvement in IGSCC resistance, with best performance after a heat treatment at 610 degrees C for nine hours. In addition to stress relief, carbide precipitation can also occur, and their relative contributions to the improvement is discussed

  19. Theoretical analysis of film condensation in horizontal microfin tubes; Microfin tsuki suihei kannai gyoshuku no riron kaiseki

    Energy Technology Data Exchange (ETDEWEB)

    Honda, H; Wang, H [Kyushu University, Fukuoka (Japan). Institute of Advanced Material Study; Nozu, S [Okamaya Prefectural University, Okayama (Japan). Faculty of Computer Science and System Engineering

    2000-10-25

    A theoretical study has been made of film condensation in helically-grooved, horizontal microfin tubes. The annular flow regime and the stratified flow regime were considered. For the annular flow regime, a previously developed theoretical model was applied. For the stratified flow regime, the height of stratified condensate was estimated by a modified Taitel and Dukler model. For the upper part of the tube exposed to the vapor flow, numerical calculation of Laminar film condensation considering the combined effects of gravity and surface tension forces was conducted. The heat transfer coefficient at the lower part of the tube was estimated by an empirical equation for the internally finned tubes developed by Carnavos. The theoretical predictions of the circumferential average heat transfer coefficient by the two theoretical models were compared with available experimental data for four refrigerants and four tubes. Generally, the annular flow model gave a higher heat transfer coefficient than the stratified flow model in the high quality region, whereas the stratified flow model gave a higher heat transfer coefficient in the low quality region. For tubes with fin heights of 0.16 {approx} 0.24 mm, most of the experimental data agreed within {+-} 20% with the higher of the two theoretical predictions. (author)

  20. Visualization of cross-sectional flow structure during condensation of steam in a slightly inclined horizontal tube

    Energy Technology Data Exchange (ETDEWEB)

    Puseya, Andree; Kim, H. [Kyung Hee University, Yongin (Korea, Republic of); Kwon, T. S. [Korea Atomic Energy Research Institute, Daejeon (Korea, Republic of)

    2015-10-15

    These flow characteristics called flow patterns still depend on a proper visualization technique in order to identify such local distribution. These proper distributions will have a dependence on the inclination of the tube as well, as it was demonstrated by Lips and Mayer. This work is focused on presenting an experimental investigation to visualize the cross sectional two-phase flow structure for condensation of steam in a horizontal tube and identify the liquid-gas interface using the axial-viewing technique. This innovative technique developed by Hewitt and more recently used in visualization works by Badie, permits the achievement to identify those systems in the area of interest by looking directly into the two-phase flow system during condensation of steam inside a pipe with technology such a high speed camera. An experimental work to visualize and locate the liquid-gas interface for steam condensation in horizontal tubes with slightly inclination was developed on this research The experimental results shows that the axial viewing technique works well with condensation phenomena and can be used for further developments in the field such as determination of liquid film geometry and calculation of void fraction.

  1. The temperature dependence of the tensile properties of thermally treated Alloy 690 tubing

    International Nuclear Information System (INIS)

    Harrod, D.L.; Gold, R.E.; Larsson, B.; Bjoerkman, G.

    1992-01-01

    Tensile tests were run in air on full tube cross-sections of 22.23 mm OD by 1.27 mm wall thickness Alloy 690 steam generator production tubes from ten (10) heats of material at eight (8) temperatures between room temperature and 760 degrees C. The tubing was manufactured to specification requirements consistent with the EPRI guidelines for Alloy 690 tubing. The room temperature stress-strain curves are described quite well by the Voce equation. Ductile fracture by dimpled rupture was observed at all test temperatures. The elevated temperature tensile properties are compared with design data given in the ASME Code

  2. Numerical analysis of the influence of circuit arrangement on a fin-and-tube condenser performance

    Directory of Open Access Journals (Sweden)

    Cesare Maria Joppolo

    2015-09-01

    Full Text Available In the present paper a model for the steady-state simulation of fin-and-tube condenser is developed. The model is based on a finite volume approach that divides each tube into small elemental volumes where mass, momentum and energy conservation equations are solved using the effectiveness-NTU method and with appropriate correlations for void fraction, friction factor and heat transfer coefficient calculation. The model is validated against experimental data on two small condensers finding that the calculated heat transfer rate and refrigerant-side pressure drop agree within ±5% and ±21% respectively to the experimental values. The model is then used to numerically analyse the impact of different circuit arrangements on the condenser heat transfer rate, refrigerant-side pressure drop and refrigerant charge.

  3. Condensation heat transfer of steam on a single horizontal tube

    Science.gov (United States)

    Graber, K. A.

    1983-06-01

    An experimental apparatus was designed, constructed and instrumented in an effort to systematically and carefully study the condensation heat-transfer coefficient on a single, horizontal tube. A smooth, thick-walled copper tube of length 133.5 mm, with an outside diameter of 15.9 mm and an inside diameter of 12.7 mm was instrumented with six wall thermocouples. The temperature rise across the test section was measured accurately using quartz crystal thermometers. The inside heat-transfer coefficient was determined using the Sieder-Tate correlation with leading coefficient of 0.029. Initial steam side data were taken at atmospheric pressure to test the data acquisition/reduction computer programs.

  4. Condensing heat transfer characteristics of R22 and R410A in 9.52 mm O.D. smooth and microfin tubes

    Energy Technology Data Exchange (ETDEWEB)

    Kim, M H; Shin, J S; Lim, B H [Sam Sung Electronics Corporation Limited (Korea, Republic of)

    1998-10-01

    An experimental investigation of condensation heat transfer in 9.52 mm horizontal copper tubes was conducted using R22 and R410A. The test rig had a straight, horizontal test section with an active length of 0.92 m and was cooled by the heat transfer fluid(cold water) circulated in a surrounding annulus. Constant heat flux of 11.0 kW/m{sup 2} was maintained throughout the experiment and refrigerant quality varied from 0.9 to 0.1. The condensation test results at 45 deg. C were reported for 40{approx}80 kg/h mass flow rate. The local and average condensation coefficients for seven microfin tubes were presented compared to those for a smooth tube. The average condensation coefficients of R22 and R410A for the microfin tubes were 1.7{approx}3.19 and 1.7{approx}2.94 times larger than those in smooth tube, respectively. (author). 19 refs., 9 figs., 4 tabs.

  5. Experiments on condensation heat transfer characteristics inside a microfin tube with R410A

    Energy Technology Data Exchange (ETDEWEB)

    Han, D H; Cho, Y J [Korea University Graduate School, Seoul (Korea); Lee, K J; Park, S S [Korea University, Seoul (Korea)

    2000-11-01

    Due to the ozone depletion and global warming potentials, some refrigerants (CFCs and HCFCs) have been rapidly substituted. R410A is considered as the alternative refrigerant of R22 for the air-conditioners used at home and in industry. Experiments on the condensation heat transfer characteristics inside a smooth or a micro-fin tube with R410A are performed in this study. The test tubes 7/9.52 mm in outer diameters and 3 m in length are used. Varying the mass flux of the refrigerant and the condensation temperatures, the average heat transfer coefficients and pressure drop are investigated. It is shown that the heat transfer is enhanced and the amount of pressure drops are larger in the microfin tube than the smooth tube. From the heat transfer enhancement coefficient and the pressure penalty factor, it is found that the high heat transfer enhancement coefficients are obtained in the range of small mass flux while the penalty factors are almost equal. (author). 13 refs., 12 figs., 1 tab.

  6. The development of octagon Zr-4 alloy tube for heating reactors

    International Nuclear Information System (INIS)

    Yang Fanglin; Yang Yingli; Wang Guangshen

    1989-10-01

    The asymmetrical octagon Zr-4 alloy tubes which are used for fuel assembly in the heating reactor have been developed. The thickness of tube wall is 1.5 mm and the length is 1725 mm. The long side of the octagon is 138.7 0.3 +0.2 mm, the short side is 93.1 ± 0.1 mm. To manufacture these tubes a stretch draw forming processing method is adopted. The process is divided into two phases. In the first phase, a short draw mould is used to stretch the Zr-4 alloy tube. In the second phase, a long draw mould, its length is equal to the end-produt length, is used to complete the final processing. The size accuracy and repeatability of this method are excellent and can fully meet the design requirements

  7. Process for forming seamless tubing of zirconium or titanium alloys from welded precursors

    International Nuclear Information System (INIS)

    Sabol, G.P.; Barry, R.F.

    1987-01-01

    A process is described for forming seamless tubing of a material selected from zirconium, zirconium alloys, titanium, and titanium alloys, from welded precursor tubing of the material, having a heterogeneous structure resulting from the welding thereof. The process consists of: heating successive axial segments of the welded tubing, completely through the wall thereof, including the weld, to uniformly transform the heterogeneous, as welded, material into the beta phase; quenching the beta phase tubing segments, the heating and quenching effected sufficiently rapid enough to produce a fine sized beta grain structure completely throughout the precursor tubing, including the weld, and to prevent growth of beta grains within the material larger than 200 micrometers in diameter; and subsequently uniformly deforming the quenched precursor tubing by cold reduction steps to produce a seamless tubing of final size and shape

  8. Degradation of Alloy 800 steam generator tubing and its long-term behaviour predictions for plant life management

    International Nuclear Information System (INIS)

    Lu, Y.C.; Tapping, R.L.; Pandey, M.D.

    2009-01-01

    Alloy 800 tubing has a good service record in steam generators (SGs) in both German pressurized water reactors and CANDU 6 reactors, however, a recent comprehensive examination of several ex-service SG tubes removed from Darlington Nuclear Generating Station (DNGS) found that these SG tubes (which had experienced shallow pitting in service) were more susceptible to pitting corrosion in laboratory tests than a reference nuclear grade Alloy 800 tubing under SG crevice chemistry conditions. This was an unexpected finding and has raised questions about possible effects of in-service 'aging' on SG tubing. In addition, there has also been recent evidence that a few Alloy 800 tubes have experienced stress corrosion cracking (SCC) in some German pressurized water reactors (PWRs), possibly after many years of degradation-free service, although the inspection history of these tubes is not available to confirm that the reported degradation initiated recently. These findings suggest that Alloy 800 tubing may have some aging degradation susceptibility after many years of service. To provide support for a proactive SG aging management, a survey on the corrosion susceptibility of the archived Alloy 800 tubing from CANDU SGs under plausible crevice chemistry conditions was conducted to assess the potential material degradation issues in CANDU SGs. Experimental work was also performed to investigate the root cause leading to Alloy 800 SG tubing degradation. The results from this study suggested that a combination of negative factors; aggressive chemistry resulting from impurity ingress into the secondary side of the SGs, elevated electrochemical corrosion potential (ECP) during SG transients and surface strain/plastic deformation, might have led to the degradation of the ex-service SG tubing. The studies have shown that each of these conditions in isolation does not cause degradation of Alloy 800 SG tubing; a synergistic combination of factors is required. The OPEX and experimental

  9. Condition monitoring and life assessment of lake water cooled admiralty brass condenser tubes of a nuclear power plant

    International Nuclear Information System (INIS)

    De, P.K.; Ghosal, S.K.; Kutty, K.K.; Bhat, H.R.

    2000-01-01

    The present paper deals with the failure of condenser tubes in a nuclear power plant. The tubes were made of arsenical admiralty brass and were cooled using lake water. They were in service for over 25 years. So far about 1000 tubes have been plugged as they failed due to several reasons. In order to assess the remaining life of the existing tubes as well as to investigate the cause of recent tube failures, some of the tubes from the condenser were removed and examined in detail following several procedure. It was observed that in general, wall thickness of the tubes was reduced by 10- 15%. Maximum reduction in wall thickness took place near the water inlet ends. No denting type phenomenon was observed at the tube to tube-support plate crevice locations. At certain locations on ID surfaces of some tubes, small steps, 0.2 mm high, were noticed along the longitudinal direction of the tubes. ID surfaces of the tubes were covered with light gray coloured thin and adherent corrosion products decorated with red spots at places. EDAX analysis showed that these red spots were enriched with copper. While some pits were present on the ID surfaces, the OD surfaces were covered with shining black oxide film. Fracture surfaces of the tubes, which had lost much strength and broke while taking them out of the condenser, showed presence of cleavages with fatigue striations near the OD edges. Mechanical properties of the tubes as such had deteriorated significantly. The tubes were observed to have been degraded to a large extent due to localised corrosion on the ID surfaces and corrosion fatigue damage caused by flow induced vibration. Under the present operational conditions, the tubes are expected to perform satisfactorily for a limited period. (author)

  10. Creep-Rupture Behavior of Ni-Based Alloy Tube Bends for A-USC Boilers

    Science.gov (United States)

    Shingledecker, John

    Advanced ultrasupercritical (A-USC) boiler designs will require the use of nickel-based alloys for superheaters and reheaters and thus tube bending will be required. The American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code Section II PG-19 limits the amount of cold-strain for boiler tube bends for austenitic materials. In this summary and analysis of research conducted to date, a number of candidate nickel-based A-USC alloys were evaluated. These alloys include alloy 230, alloy 617, and Inconel 740/740H. Uniaxial creep and novel structural tests and corresponding post-test analysis, which included physical measurements, simplified analytical analysis, and detailed microscopy, showed that different damage mechanisms may operate based on test conditions, alloy, and cold-strain levels. Overall, creep strength and ductility were reduced in all the alloys, but the degree of degradation varied substantially. The results support the current cold-strain limits now incorporated in ASME for these alloys for long-term A-USC boiler service.

  11. Characterization of Tubing from Advanced ODS alloy (FCRD-NFA1)

    International Nuclear Information System (INIS)

    Maloy, Stuart Andrew; Aydogan, Eda; Anderoglu, Osman; Lavender, Curt; Anderson, Iver; Rieken, Joel; Lewandowski, John; Hoelzer, Dave; Odette, George R.

    2016-01-01

    Fabrication methods are being developed and tested for producing fuel clad tubing of the advanced ODS 14YWT and FCRD-NFA1 ferritic alloys. Three fabrication methods were based on plastically deforming a machined thick-wall tube sample of the ODS alloys by pilgering, hydrostatic extrusion or drawing to decrease the outer diameter and wall thickness and increase the length of the final tube. The fourth fabrication method consisted of the additive manufacturing approach involving solid-state spray deposition (SSSD) of ball milled and annealed powder of 14YWT for producing thin-wall tubes. Of the four fabrication methods, two methods were successful at producing tubing for further characterization: production of tubing by high-velocity oxy-fuel spray forming and production of tubing using high-temperature hydrostatic extrusion. The characterization described shows through neutron diffraction the texture produced during extrusion while maintaining the beneficial oxide dispersion. In this research, the parameters for innovative thermal spray deposition and hot extrusion processing methods have been developed to produce the final nanostructured ferritic alloy (NFA) tubes having approximately 0.5 mm wall thickness. Effect of different processing routes on texture and grain boundary characteristics has been investigated. It was found that hydrostatic extrusion results in combination of plane strain and shear deformations which generate rolling textures of ?- and ?-fibers on and together with a shear texture of ?-fiber on and . On the other hand, multi-step plane strain deformation in cross directions leads to a strong rolling textures of ?- and ?-fiber on together with weak ?-fiber on . Even though the amount of the equivalent strain is similar, shear deformation leads to much lower texture indexes compared to the plane strain deformations. Moreover, while 50% of hot rolling brings about a large number of high-angle grain boundaries (HAB), 44% of shear deformation results

  12. Characterization of Tubing from Advanced ODS alloy (FCRD-NFA1)

    Energy Technology Data Exchange (ETDEWEB)

    Maloy, Stuart Andrew [Los Alamos National Lab. (LANL), Los Alamos, NM (United States); Aydogan, Eda [Los Alamos National Lab. (LANL), Los Alamos, NM (United States); Anderoglu, Osman [Los Alamos National Lab. (LANL), Los Alamos, NM (United States); Lavender, Curt [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Anderson, Iver [Ames Lab., Ames, IA (United States); Rieken, Joel [Ames Lab., Ames, IA (United States); Lewandowski, John [Case Western Reserve Univ., Cleveland, OH (United States); Hoelzer, Dave [Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States); Odette, George R. [Univ. of California, Santa Barbara, CA (United States)

    2016-09-20

    Fabrication methods are being developed and tested for producing fuel clad tubing of the advanced ODS 14YWT and FCRD-NFA1 ferritic alloys. Three fabrication methods were based on plastically deforming a machined thick-wall tube sample of the ODS alloys by pilgering, hydrostatic extrusion or drawing to decrease the outer diameter and wall thickness and increase the length of the final tube. The fourth fabrication method consisted of the additive manufacturing approach involving solid-state spray deposition (SSSD) of ball milled and annealed powder of 14YWT for producing thin-wall tubes. Of the four fabrication methods, two methods were successful at producing tubing for further characterization: production of tubing by high-velocity oxy-fuel spray forming and production of tubing using high-temperature hydrostatic extrusion. The characterization described shows through neutron diffraction the texture produced during extrusion while maintaining the beneficial oxide dispersion. In this research, the parameters for innovative thermal spray deposition and hot extrusion processing methods have been developed to produce the final nanostructured ferritic alloy (NFA) tubes having approximately 0.5 mm wall thickness. Effect of different processing routes on texture and grain boundary characteristics has been investigated. It was found that hydrostatic extrusion results in combination of plane strain and shear deformations which generate rolling textures of α- and γ-fibers on {001}<110> and {111}<110> together with a shear texture of ζ-fiber on {011}<211> and {011}<011>. On the other hand, multi-step plane strain deformation in cross directions leads to a strong rolling textures of θ- and ε-fiber on {001}<110> together with weak γ-fiber on {111}<112>. Even though the amount of the equivalent strain is similar, shear deformation leads to much lower texture indexes compared to the plane strain deformations. Moreover, while 50% of hot rolling brings about a large number of

  13. Condensation heat transfer and pressure drop of R-410A in a 7.0 mm O.D. microfin tube at low mass fluxes

    Science.gov (United States)

    Kim, Nae-Hyun

    2016-12-01

    R-410A condensation heat transfer and pressure drop data are provided for a 7.0 mm O.D. microfin tube at low mass fluxes (50-250 kg/m2 s). The heat transfer coefficient of the microfin tube shows a minimum behavior with the mass flux. At a low mass flux, where flow pattern is stratified, condensation induced by surface tension by microfins overwhelms condensation induced by shear, and the heat transfer coefficient decreases as mass flux increases. At a high mass flux, where flow pattern is annular, condensation induced by shear governs the heat transfer, and the heat transfer coefficient increases as mass flux increases. The pressure drop of the microfin tube is larger than that of the smooth tube at the annular flow regime. On the contrary, the pressure drop of the smooth tube is larger than that of the microfin tube at the stratified flow regime.

  14. Analytical TEM of service-induced SCC in alloy 600TT steam generator tubing

    International Nuclear Information System (INIS)

    Wolfe, R.; Legras, L.; Boccanfuso; Martin, A.

    2015-01-01

    In 2008, Vogtle Electric Generating Plant Unit 1 performed tube pulls to confirm outside diameter stress corrosion cracking (ODSCC) in a steam generator with thermally treated Alloy 600TT tubing. Subsequent metallographic and other laboratory work attributed the cracking to the non-optimal microstructure of the tubing and the elevated residual stresses at the expansion transition. In the current work, analytical transmission electron microscopy was performed to gain a better understanding of this in-service cracking through a detailed characterization of the oxides and crack tips. These examinations, which are the first of this kind for U.S. Alloy 600TT tubing service cracks, detected lead (Pb) in the region of the top-of-tube sheet crevice, in oxides at the crack tips, and at degraded grain boundaries. In addition, sulfur was observed in oxides on the outside surface of the tube in the free span area. The presence of Pb at the crack tip and the lack of plasticity on the observed failure surfaces suggest that the environment played a predominant role in the cracking of this tubing with a non-optimal microstructure. The significance of the degradation will be discussed in the context of overall corrosion indications in Alloy 600TT steam generators in the United States. (authors)

  15. The resistance to PWSCC of explosively expanded Alloy 600 tube-to-tubesheet joints

    International Nuclear Information System (INIS)

    Gold, R.E.; Pement, F.W.; Tarabek, S.A.; Economy, G.

    1992-01-01

    Experimental evaluations were performed to determine the approximate magnitude of the residual stresses associated with explosively expanded steam generator tubing, and to assess the resistance to primary water stress corrosion cracking (PWSCC) of these expansions. Indexing of residual stresses was performed by means of magnesium chloride exposures of surrogate stainless steel mockups. The PWSCC resistance was evaluated by the testing of pressurized mockups of explosively expanded mill annealed Alloy 600 tubing in a highly accelerated Alloy 600 tubing in a highly accelerated steam test environment. Shot peening of the inside tube surfaces was demonstrated to be effective in modifying the residual stresses, providing additional resistance to PWSCC

  16. Experimental investigation of reflux condensation heat transfer in PWR steam generator tubes in the presence of noncondensible gases

    Energy Technology Data Exchange (ETDEWEB)

    Vierow, Karen; Wu, Tiejun [Purdue Univ., West Lafayette (United States); Nagae, Takashi [Institute of Nuclear Safety System, Tokyo (Japan)

    2003-07-01

    Under certain circumstances in a Pressurized Water Reactor (PWR), the coolant system may be in a partially drained state and reflux condensation in the steam generator U-tubes can be the major heat removal mechanism. Noncondensable gases may be present and would degrade the heat transfer rate. If heat removal rates are insufficient, this situation could lead to core boil-off, fuel rod heatup, and eventually core damage. The Institute of Nuclear Safety System, Inc. (INSS) and the Nuclear Heat Transfer Systems Laboratory at Purdue University have begun a cooperative research program to investigate the effectiveness of reflux condensation in PWR steam generator U-tubes in the presence of noncondensable gases. The final objectives are to provide local heat transfer data for development of methods to analyze reflux condensation in PWR steam generator U-tubes and to investigate the potential for flooding. Key features of the experimental data reported herein are that they are local data under laminar steam/gas mixture and condensate film flow and they are taken from a test section with dimensions similar to an actual steam generator tube. Steady state data were obtained under various steam and air inlet flow rates and pressures. The data show the significant degrading effect of noncondensable gas on heat transfer coefficients. From the data, correlations for the reflux condensation local heat transfer coefficient and the local Nusselt number under laminar conditions were derived. These experiments are providing essential and unique fundamental data for development of methods to analyze reflux condensation.

  17. A model for the performance of a vertical tube condenser in the presence of noncondensable gases

    Energy Technology Data Exchange (ETDEWEB)

    Guentay, A.D.S.

    1995-09-01

    Some proposed vertical tube condensers are designed to operate at high noncondensable fractions, which warrants a simple model to predict their performance. Models developed thus far are usually non self-contained as they require the specification of the wall temperature to predict the local condensation rate. The present model attempts to fill this gap by addressing the secondary side heat transfer as well. Starting with momentum balance which includes the effect of interfacial shear stress, a Nusselt-type algebraic equation is derived for the film thickness as a function of flow and geometry parameters. The heat and mass transfer analogy relations are then invoked to deduce the condensation rate of steam onto the tube wall. Lastly, the heat transfer to the secondary side is modelled to include cooling by forced, free or mixed convection flows. The model is used for parametric simulations to determine the impact on the condenser performance of important factors such as the inlet gas fraction, the mixture inlet flowrate, the total pressure, and the molecular weight of the noncondensable gas. The model performed simulations of some experiments with pure steam and air-steam mixtures flowing down a vertical tube. The model predicts the data quite well.

  18. RELAP5 analysis of reflux condensation behavior in heat transfer tube bundle of a steam generator

    International Nuclear Information System (INIS)

    Minami, Noritoshi; Chikusa, Toshiaki; Nagae, Takashi; Murase, Michio

    2007-01-01

    In case of loss of the residual heat removal system and other alternative cooling methods under mid-loop operation during shutdown of the pressurized water reactor plant, reflux condensation in the steam generator (SG) may be an effective heat removal mechanism. In reflux condensation experiments 7.2c with injection of nitrogen gas using the BETHSY facility in France, which is a scale model of a pressurized water reactor plant, 34 heat transfer tubes were divided into two kinds of flow patterns, which were steam forward flow and nitrogen reverse flow. In this study, we simulated the BETHSY experiments using the transient analysis code RELAP5. Modifying calculation equations for interfacial friction force and wall friction force between the inlet plenum and heat transfer tubes, nitrogen reverse flow was successfully simulated. In calculations with alteration of the flow area ratio to two flow channels for the heat transfer tube bundle, the number of active tubes with the maximum nitrogen recirculation flow rate agreed rather well with the observed number of active tubes. In calculations with three flow channels for the heat transfer tube bundle, the average number of active tubes in several calculations with different flow area ratios of the three flow channels predicted the number of active tubes well. (author)

  19. Electrohydrodynamic enhancement of in-tube convective condensation heat transfer

    Energy Technology Data Exchange (ETDEWEB)

    Sadek, H.; Robinson, A.J.; Ching, C.Y.; Shoukri, M. [McMaster University, Department of Mechanical Engineering, Hamilton, Ont. (Canada); Cotton, J.S. [Dana Corporation, Long Manufacturing Division, Oakville, Ont. (Canada)

    2006-05-15

    An experimental investigation of electrohydrodynamic (EHD) augmentation of heat transfer for in-tube condensation of flowing refrigerant HFC-134a has been performed in a horizontal, single-pass, counter-current heat exchanger with a rod electrode placed in the centre of the tube. The effects of varying the mass flux (55kg/m{sup 2}s=tube. (author)

  20. Condensing heat transfer characteristics of hydrocarbon refrigerants in 9.52 and 12.7 mm smooth tube

    Science.gov (United States)

    Yoon, Jung-In; Lee, Ho-Saeng; Lee, Kwang-Bae; Kim, Jae-Dol; Bansal, Pradeep

    2005-12-01

    Experimental results for heat transfer characteristic and pressure gradients of hydrocarbon (HC) refrigerants and R-22 during condensing inside horizontal double pipe heat exchangers are presented. The test sections which have one tube diameter of 12.70 mm with 0.86 mm wall thickness, another tube diameter of 9.52 mm with 0.76 mm wall thickness are used for this investigation. The local condensing heat transfer coefficients of HC refrigerants were higher than that of R-22. The average condensing heat transfer coefficient increased with the increase of the mass flux. It showed the higher values in HC refrigerants than R-22. Comparing the heat transfer coefficient of experimental results with that of other correlations, the presented results had a good agreement with most of the Cavallini’s correlations.

  1. Structural specifics of the condensate prepared by thermal evaporation of alloys of As2S3-Yb systems

    International Nuclear Information System (INIS)

    Ehfendiev, Eh.G.; Mamedov, A.I.; Il'yasov, T.M.; Rustamov, P.G.

    1987-01-01

    The problem aimed at preparation of the films of As 2 S 3 -Yb system, at studying their substructure depending on condensation conditions and defining noncrystallinity region of this system in the film state, is formulated. It is shown that in representative samples of As 2 S 3 -Yb system the vitrification region is extended up to 7 at.% Yb, in the films noncrystallinity region is extended up to 30 at.% Yb. With up to 30 at.% increase of ytterbium amount in initial alloys a tendency to crystallization in amorphous condensate structure is noticed. In evaporation of As 2 S 3 + 40 at.% Yb and As 2 S 3 + 50 at.% Yb, unknown in the film state YbAs 2 S 4 , Yb 3 As 4 S 9 and YbAs 4 S 7 phases are prepared, and the latter is formed in case of As 2 S 3 + 50 at.% Yb alloy at small evaporation rates (∼10 A/s). Substructure of As 2 S 3 + 50 at.% Yb alloy prepared condensate is more dependent on evaporation rate than in evaporation of As 2 S 3 + 40 at.% Yb alloy. In this case, evaporation rates being ∼ 100 A/s, the condensate has a polycrystal structure, and at small rates of ∼ 10 A/c, condensate structure is primarily blocked

  2. Numerical simulation of condensation phase change flow in an inclined tube with bend

    Energy Technology Data Exchange (ETDEWEB)

    Jo, Jong Chull; Shin, Byung Soo; Do, Kyu Sik [Korea Institute of Nuclear Safety, Daejeon (Korea, Republic of); Lee, Yong Kap [Anflux Co., Seoul (Korea, Republic of)

    2012-10-15

    The new PWR design named APR+ incorporates a passive auxiliary feedwater system (PAFS) as shown in Fig.1. The PAFS consists of two separate divisions. Each division is equipped with one passive condensation heat exchanger (PCHX), isolation or drain or vent valves, check valves, instrumentation and control, and pipes. It is aligned to feed condensed water to its corresponding steam generator (SG). During the PAFS normal operation, steam being produced in the SG secondary side by the residual heat moves up due to buoyancy force and then flows into the PCHX where steam is condensed on the inner surface of the tubes of which the outer surfaces are cooled by the water stored in the passive condensation cooling tank (PCCT). The condensate is passively fed into the SG economizer by gravity. Because the thermal hydraulic characteristics in the PCHT determine the condensation mass rate and the possibility of system instability and water hammer, it is important to understand the condensation phase change flow in the PCHT. This paper presents a numerical simulation of the condensation phase change flow in the PCHX adopted for the APR+ PAFS.

  3. R404A condensing under forced flow conditions inside smooth, microfin and cross-hatched horizontal tubes

    Energy Technology Data Exchange (ETDEWEB)

    Infante Ferreira, C A; Nan, X [Delft University of Technology (Netherlands). Laboratory for Refrigeration and Indoor Climate Control; Newell, T A; Chato, J C [University of Illinois, Urbana, IL (United States). Dept. of Mechanical and Industrial Engineering

    2003-06-01

    Two-phase heat transfer coefficient characteristics of R404A condensing under forced flow conditions inside smooth, microfin and cross-hatched horizontal tubes are experimentally investigated. Experimental parameters include a lubricating polyol ester oil concentration varied from 0 to 4%. The test runs were done at average inlet saturated condensing temperatures of 40{sup o}C. The inlet vapor was kept at saturation (quality = 1.0). The mass fluxes were between 200 and 600 kg/m{sup 2}s, and the heat fluxes were selected to obtain a quality of 0.0 at the outlet of the test section, varying from 5 to 45 kW/m{sup 2}. The heat transfer enhancement factor varied between 1.8 and 2.4 for both microfin and cross-hatched tubes. The larger values applied for larger mass fluxes for the cross-hatched tube and smaller mass fluxes for the microfin tube. Enhancement factors increased as oil concentration increased up to oil concentrations of 2%. For higher oil concentrations the enhancement decreased especially at high mass fluxes, the cross-hatched tube being less sensitive to oil contamination. Pressure drop in the test section increased by approximately 25% as the oil concentration increased from 0 to 4%. The results from the experiments are compared with those calculated from correlations reported in the literature. Moreover, modified correlations for the condensation heat transfer coefficient are proposed for practical applications. (author)

  4. A Study on Corrosion and Fretting Wear Resistance of Alloy 690 Tubes

    Energy Technology Data Exchange (ETDEWEB)

    Won, Ju Jin; Min, Su Jung; Kim, Myeong Su; Kim, Kyu Tae [Dongguk Univ., Gyeongju (Korea, Republic of)

    2013-10-15

    In this article, the effects of such failures have on the materials of alloy 690 are assessed. The corroded volume variation and mass decreased continuously with time. However, the oxide volume changes in an irregular pattern since the oxide formed on the alloy 690 metal may be detached due to the flake formation. The amount of the fretting wear increased with time. It can be seen that the wear rate increased with time and reduced at the later time. The test results show that the ductility decreased as corrosion increases. Alloy 690 is broadly used as a material of nuclear power plant's steam generator tubes because of its excellent mechanical strength, corrosion properties, wear properties and stability at a high temperature. However, the tubes for nuclear power plant's steam generators become a major threat for lifetime management and efficient operation of nuclear power plant due to various corrosion and fretting wear failures caused by flow-induced vibration (FIV) that occurs between tubes.

  5. Experiment of flow regime map and local condensing heat transfer coefficients inside three dimensional inner microfin tubes

    Science.gov (United States)

    Du, Yang; Xin, Ming Dao

    1999-03-01

    This paper developed a new type of three dimensional inner microfin tube. The experimental results of the flow patterns for the horizontal condensation inside these tubes are reported in the paper. The flow patterns for the horizontal condensation inside the new made tubes are divided into annular flow, stratified flow and intermittent flow within the test conditions. The experiments of the local heat transfer coefficients for the different flow patterns have been systematically carried out. The experiments of the local heat transfer coefficients changing with the vapor dryness fraction have also been carried out. As compared with the heat transfer coefficients of the two dimensional inner microfin tubes, those of the three dimensional inner microfin tubes increase 47-127% for the annular flow region, 38-183% for the stratified flow and 15-75% for the intermittent flow, respectively. The enhancement factor of the local heat transfer coefficients is from 1.8-6.9 for the vapor dryness fraction from 0.05 to 1.

  6. Simulation studies on Tube End Expansion of AA2014 Alloy Tubes

    Science.gov (United States)

    Venugopal, L.; Prasad, N. E. C.; Geeta Krishna, P.; Praveen, L.

    2018-03-01

    End forming is defined as forming the end of tubular forms either by inverting the tube or by expanding it. It finds application in many fields such as in automotive and aerospace sectors as power transmission elements, fuel lines, exhaust pipes etc. The main aim of the present work is to expand the AA2014 alloy tubes with different die sets without any fracture. Deform 2D software was used for performing simulations on expanding the tubes with different die set (punch) values having differed forming angles (α = 15°, 30° and 45°) and expansion ratios (rp/r0 = 1.39, 1.53 and 1.67). Experiments were also conducted and the results correlate with the simulation results. The results shows that for the punch having less cone angle (α) values the linear displacement is more rather than higher cone angles. But in the case of higher cone angles the radial displacement is more than the linear displacement.

  7. A Study On Critical Thinning In Thin-walled Tube Bending Of Al-Alloy 5052O Via Coupled Ductile Fracture Criteria

    International Nuclear Information System (INIS)

    Li Heng; Yang He; Zhan Mei

    2010-01-01

    Thin-walled tube bending(TWTB) method of Al-alloy tube has attracted wide applications in aerospace, aviation and automobile,etc. While, under in-plane double tensile stress states at the extrados of bending tube, the over-thinning induced ductile fracture is one dominant defect in Al-alloy tube bending. The main objective of this study is to predict the critical wall-thinning of Al-alloy tube bending by coupling two ductile fracture criteria(DFCs) into FE simulation. The DFCs include Continuum Damage Mechanics(CDM)-based model and GTN porous model. Through the uniaxial tensile test of the curved specimen, the basic material properties of the Al-alloy 5052O tube is obtained; via the inverse problem solution, the damage parameters of both the two fracture criteria are interatively determined. Thus the application study of the above DFCs in the TWTB is performed, and the more reasonable one is selected to obtain the critical thinning of Al-alloy tube in bending. The virtual damage initiation and evolution (when and where the ductile fracture occurs) in TWTB are investigated, and the fracture mechanisms of the voided Al-alloy tube in tube bending are consequently discussed.

  8. State of the Art Report On Condensation Phenomena Within Tubes in the Presence of Noncondensable Gas

    International Nuclear Information System (INIS)

    Polo, J.

    1998-01-01

    Condensation phenomena play an important role in many industrial applications; in particular; the nuclear industry uses such processes in different systems for both operation and safety aspects. Thus most of the engineering safety features in the current Light Water Reactor (LWR) plants as well as in the new advanced/passive type design are based on the condensation phenomena inside tubes to reduce the system pressure and to remove the decay heat released under accidental conditions. Regarding the new advanced/passive plant designs such a systems must ensure their capabilities under severe accident conditions, that means, under the presence of non-condensable gas an even aerosol particles. The presence of even a small quantity of non condensable gas in liquid-vapour has profound influence on the resistance to heat transfer at the liquid-vapour interface leading to reduce in the heat transfer rate. In consequence, the safety analysis of the Simplified Boiling Water Reactor (SBWR) promoted in increase in the modelling, model development and experimental research on the gas mixtures condensing inside vertical tubes. This report summarises the last models developed as well as the experimental findings on such processes. (Author) 51 refs

  9. Proceedings: Condenser technology conference

    International Nuclear Information System (INIS)

    Tsou, J.L.; Mussalli, Y.G.

    1991-08-01

    Seam surface condenser and associated systems performance strongly affects availability and heat rate in nuclear and fossil power plants. Thirty-six papers presented at a 1990 conference discuss research results, industry experience, and case histories of condenser problems and solutions. This report contains papers on life extension, performance improvement, corrosion and failure analysis, fouling prevention, and recommendation for future R ampersand D. The information represents recent work on condenser problems and solutions to improve the procurement, operation, and maintenance functions of power plant personnel. Several key points follow: A nuclear and a fossil power plant report show that replacing titanium tube bundles improves condenser availability and performance. One paper reports 10 years of experience with enhanced heat transfer tubes in utility condensers. The newly developed enhanced condenser tubes could further improve condensing heat transfer. A new resistance summation method improves the accuracy of condenser performance prediction, especially for stainless steel and titanium tubed condensers. Several papers describe improved condenser fouling monitoring techniques, including a review of zebra mussel issues

  10. Experimental study of the condensation heat transfer characteristics of CO2 in a horizontal microfin tube with a diameter of 4.95 mm

    Science.gov (United States)

    Son, Chang-Hyo; Oh, Hoo-Kyu

    2012-11-01

    The condensation heat transfer characteristics for CO2 flowing in a horizontal microfin tube were investigated by experiment with respect to condensation temperature and mass flux. The test section consists of a 2,400 mm long horizontal copper tube of 4.6 mm inner diameter. The experiments were conducted at refrigerant mass flux of 400-800 kg/m2s, and saturation temperature of 20-30 °C. The main experimental results showed that annular flow was highly dominated the majority of condensation flow in the horizontal microfin tube. The condensation heat transfer coefficient increases with decreasing saturation temperature and increasing mass flux. The experimental data were compared against previous heat transfer correlations. Most correlations failed to predict the experimental data. However, the correlation by Cavallini et al. showed relatively good agreement with experimental data in the microfin tube. Therefore, a new condensation heat transfer correlation is proposed with mean and average deviations of 3.14 and -7.6 %, respectively.

  11. Condensation heat transfer for refrigerant-oil mixtures in microfin tube condenser

    Energy Technology Data Exchange (ETDEWEB)

    Cho, K N [Sungkyunkwan University, Seoul (Korea); Tae, S J [Sungkyunkwan University Graduate School, Seoul (Korea)

    2000-04-01

    Condensation heat transfer experiments for R-22 and R-407 C refrigerants mixed with mineral oil and POE oil respectively were performed in straight and U-bend sections of a microfin tube. Experimental parameters were an oil concentration from 0 to 5 %, a mass flux from 100 to 400 kg/m{sup 2}s and an inlet quality from 0.5 to 0.9. The enhancement factors for R-22 and R-407 C refrigerants at the first straight section decreased continuously as the oil concentration increased. They decreased rapidly as the mass maximum at the 90 deg. position. The heat transfer coefficients at the second straight section within the dimensionless length of 48 were larger by a maximum of 33 % than the average heat transfer coefficients at the first straight section. (author). 10 refs., 6 figs., 1 tab.

  12. Condensation of refrigerants in horizontal, spirally grooved microfin tubes: Numerical analysis of heat transfer in the annular flow regime

    Energy Technology Data Exchange (ETDEWEB)

    Nozu, S; Honda, H

    2000-02-01

    A method is presented for estimating the condensation heat transfer coefficient in a horizontal, spirally grooved microfin tube. Based on the flow observation study performed by the authors, a laminar film condensation model in the annular flow regime is proposed. The model assumes that all the condensate flow occurs through the grooves. The condensate film is segmented into thin and thick film regions. In the thin film region formed on the fin surface, the condensate is assumed to be drained by the combined surface tension and vapor shear forces. In the thick film region formed in the groove, on the other hand, the condensate is assumed to be driven by the vapor shear force. The present and previous local heat transfer data including four fluids (CFC11, HCFC22, HCFC123, and HFCl34a) and three microfin tubes are found to agree with the present predictions to a mean absolute deviation of 15.1%.

  13. On the characteristics and application of thin wall welded titanium tubes for heat transfer

    International Nuclear Information System (INIS)

    Nishimura, Takashi; Miyamoto, Yoshiyuki

    1985-01-01

    Because of the excellent corrosion resistance, thin wall welded titanium tubes have become to be used in large number as the heat transfer tubes of condensers and seawater desalting plants using seawater in place of conventional copper alloy tubes. Especially in nuclear power plants, the all titanium condensers using thin wall welded titanium tubes and titanium tube plates were adopted in the almost all plants under construction or expected to be constructed. In this report, the various characteristics of thin wall welded titanium tubes required for using them as heat transfer tubes, such as corrosion resistance, heat transfer characteristics, fatigue strength and expanding characteristics, are outlined, and the state of use is described. At first, relatively thick seamless titanium tubes were used for chemical industry, but thereafter, due to the advance of the mass production techniques, the welded titanium tubes of less than 0.7 mm thickness and high quality have become to be supplied at low cost. In 1969, titanium tubes were used for the first time in Japan for the air cooler in the condenser of Akita Power Station, Tohoku Electric Power Co., Inc. The features of titanium are small specific gravity, small linear expansion coefficient and small Young's modulus. (Kako, I.)

  14. Steam condensation heat transfer in the presence of noncondensables in a vertical tube of passive containment cooling system

    International Nuclear Information System (INIS)

    Park, Hyun Sik

    1999-02-01

    A database for laminar condensation heat transfer is constructed from the previous experimental data at various condensation conditions. Based on the database, the condensation models in the standard RELAP5/MOD3.2 code are assessed and improved. Two wall film condensation models, the default and the alternative, are used in RELAP5/MOD3.2. The default model of the laminar film condensation in RELAP5/MOD3.2 does not give any reliable predictions, and its alternative model always predicts higher values than the experimental data. Therefore, it is needed to develop a new correlation based on the experimental data of various operating ranges. A set of condensation experiments in the presence of noncondensable gas in a vertical tube of the passive containment cooling system of the CP-1300 are performed. The experimental results show that the heat transfer coefficients (HTCs) increase as the inlet air mass fraction decreases and the inlet saturated steam temperature decreases. However, the dependence of the inlet mixture Reynolds number on the HTC is small for the operating range. An empirical correlation is developed, and its predictions are compared with experimental data to show good agreement with the standard deviation of 22.3%. The experimental HTCs are also compared with the predictions from the default and the alternative models used in RELAP5/MOD3.2. The experimental apparatus is modeled with two wall-film condensation models in RELAP5/MOD3.2 and the empirical correlation, and simulations are performed for several subtests to be compared with the experimental results. Overall, the simulation results show that the default model of RELAP5/MOD3.2 underpredicts the HTCs, and the alternative model overpredicts them, while the empirical correlation predicts them well throughout the condensing tube. Both the nodalization study and the sensitivity study are also performed. The nodalization study shows that the variation of the node number does not change both modeling

  15. Evaluation of candidate Stirling engine heater tube alloys after 3500 hours exposure to high pressure doped hydrogen or helium

    Science.gov (United States)

    Misencik, J. A.; Titran, R. H.

    1984-01-01

    The heater head tubes of current prototype automotive Stirling engines are fabricated from alloy N-155, an alloy which contains 20 percent cobalt. Because the United States imports over 90 percent of the cobalt used in this country and resource supplies could not meet the demand imposed by automotive applications of cobalt in the heater head (tubes plus cylinders and regenerator housings), it is imperative that substitute alloys free of cobalt be identified. The research described herein focused on the heater head tubes. Sixteen alloys (15 potential substitutes plus the 20 percent Co N-155 alloy) were evaluated in the form of thin wall tubing in the NASA Lewis Research Center Stirling simulator materials diesel fuel fired test rigs. Tubes filled with either hydrogen doped with 1 percent CO2 or with helium at a gas pressure of 15 MPa and a temperature of 820 C were cyclic endurance tested for times up to 3500 hr. Results showed that two iron-nickel base superalloys, CG-27 and Pyromet 901 survived the 3500 hr endurance test. The remaining alloys failed by creep-rupture at times less than 3000 hr, however, several other alloys had superior lives to N-155. Results further showed that doping the hydrogen working fluid with 1 vol % CO2 is an effective means of reducing hydrogen permeability through all the alloy tubes investigated.

  16. Forming of Zr-4 alloy guide tube with varied diameters

    International Nuclear Information System (INIS)

    Wei Songyan; Tian Zhenye

    1989-10-01

    A new built-up mould method to manufacture Zr-4 alloy guide tubes with varied diameters at the middle of tube is introduced. The guide tube is used in nuclear power plants for guiding the control rods. This method has many advantages such as simple in forming, low cost of manufacturing, no need of special devices and favour of batch processing. The test results show that the accuracy of size, mechanical properties, resistance to corrosion, grain size and hydrogenate orientation of the end-products can meet the technical needs for nuclear reactor operation

  17. Polycrystalline models for the calculation of residual stresses in zirconium alloys tubes

    International Nuclear Information System (INIS)

    Signorelli, J.W.; Turner, P.A.; Lebensohn, R.A.; Pochettino, A.A.

    1995-01-01

    Tubes made of different Zirconium alloys are used in various types of reactors. The final texture of tubes as well as the distribution of residual stresses depend on the mechanical treatments done during their manufacturing process. The knowledge and prediction of both the final texture and the distribution of residual stresses in a tube for nuclear applications are of outstanding importance in relation with in-reactor performance of the tube, especially in what concerns to its irradiation creep and growth behaviour. The viscoplastic and the elastoplastic self consistent polycrystal models are used to investigate the influence of different mechanical treatments, performed during rolling processes on the final distribution of intergranular residual stresses of zirconium alloys tubes. The residual strains predictions with both formulations show a non linear dependence with the orientation, but they are qualitatively different. This discrepancy could be explain in terms of the relative plastic activity between the -type and -type deformation modes predicted with the viscoplastic and elastoplastic models. (author). 10 refs., 4 figs., 1 tab

  18. Rejuvenation of service exposed ammonia cracker tubes of cast Alloy 625 and their re-use

    Energy Technology Data Exchange (ETDEWEB)

    Singh, J.B., E-mail: jbsingh@barc.gov.in [Mechanical Metallurgy Division, Bhabha Atomic Research Centre, Mumbai 400085 (India); Verma, A. [Mechanical Metallurgy Division, Bhabha Atomic Research Centre, Mumbai 400085 (India); Jaiswal, D.M.; Kumar, N.; Patel, R.D. [Heavy Water Board, Department of Atomic Energy, Anushakti Nagar, Mumbai 400094 (India); Chakravartty, J.K. [Mechanical Metallurgy Division, Bhabha Atomic Research Centre, Mumbai 400085 (India)

    2015-09-17

    This study is an extension of a previous study undertaken to rejuvenate ammonia cracker tubes of Alloy 625 alloy that have been service exposed in heavy water plants for their full service life of 100,000 h. The service exposure caused significant microstructural modifications and deterioration in mechanical properties, and a solution annealing treatment of 2 h at 1160 °C rejuvenated all properties similar to those of the virgin alloy. The present study reports the evolution of microstructure and mechanical properties of a full service exposed centrifugally cast Alloy 625 tube that was put into service again for 55,000 h after receiving a rejuvenation treatment. During the second service, microstructural modifications, increase in strength and loss of ductility were on the lines of the work reported earlier. However, it was encouraging to observe that degraded properties after the second service life remained within the bounds of those of virgin and full service exposed tubes. The good performance of the rejuvenated tube during the second service life has been attributed to good control of operation parameters that limited the precipitation of grain boundary carbides during the first service life, which otherwise would have had a direct bearing on premature failure of tubes during their second service life.

  19. Effects of Tube Diameter and Tubeside Fin Geometry on the Heat Transfer Performance of Air-Cooled Condensers

    Science.gov (United States)

    Wang, H. S.; Honda, Hiroshi

    A theoretical study has been made on the effects of tube diameter and tubeside fin geometry on the heat transfer performance of air-cooled condensers. Extensive numerical calculations of overall heat transfer from refrigerant R410A flowing inside a horizontal microfin tube to ambient air were conducted for a typical operating condition of the air-cooled condenser. The tubeside heat transfer coefficient was calculated by applying a modified stratified flow model developed by Wang et al.8). The numerical results show that the effects of tube diameter, fin height, fin number and helix angle of groove are significant, whereas those of the width of flat portion at the fin tip, the radius of round corner at the fin tip and the fin half tip angle are small.

  20. Simulation of shell-and-tube condensers of the refrigerating machines with superheated and subcooled refrigerant

    International Nuclear Information System (INIS)

    Ciconkov, Risto

    1994-01-01

    Opposite to many authors who found the simulation of the shell-and-tube condensers on the condensing process only, in this work all thermodynamic processes which appear such as: the process of cooling the superheated refrigerant to the saturated vapor, the process of condensation and option with subcooling are considered. A selection of heat transfer equations is made corresponding to the processes, a mathematical model and adequate computer programme are composed. The functioning of this programme is presented on a concrete example. A computer programing knowledge for the using programme is not necessary. Neither is a programme support. (author)

  1. Analysis of heat flow in a tube bank of a condenser considering the influence of air

    Directory of Open Access Journals (Sweden)

    Joachimiak Magda

    2017-09-01

    Full Text Available The pressure of wet water vapor inside a condenser has a great impact on the efficiency of thermal cycle. The value of this pressure depends on the mass share of inert gases (air. The knowledge of the spots where the air accumulates allows its effective extraction from the condenser, thus improving the conditions of condensation. The condensation of water vapor with the share of inert gas in a model tube bank of a condenser has been analyzed in this paper. The models include a static pressure loss of the water vapor/air mixture and the resultant changes in the water vapor parameters. The mass share of air in water vapor was calculated using the Dalton’s law. The model includes changes of flow and thermodynamic parameters based on the partial pressure of water vapor utilizing programmed water vapor tables. In the description of the conditions of condensation the Nusselts theory was applied. The model allows for a deterioration of the heat flow conditions resulting from the presence of air. The paper contains calculations of the water vapor flow with the initial mass share of air in the range 0.2 to 1%. The results of calculations clearly show a great impact of the share of air on the flow conditions and the deterioration of the conditions of condensation. The data obtained through the model for a given air/water vapor mixture velocity upstream of the tube bank allow for identification of the spots where the air accumulates.

  2. Improved heat transfer on condensers with Ti tubes by means of granulate spheres

    International Nuclear Information System (INIS)

    Multer, I.

    1985-01-01

    Swedish power plants are located on the Baltic Sea coast and on the West coast. The cooling water is of high quality with low to medium impurity concentrations. In spite of this, pipe leakages occurred after a short period of operation, and the SoMs tubes had to be replaced by Ti tubes. Contrary to expectations, the heat transfer coefficient was higher by 10 to 20% with Ti tubes. This improvement is assumed to be due to the fact that Ti tube condensers are easier to clean by means of foamed rubber balls. As it was impossible to obtain a heat transfer coefficient of 100% with foamed rubber balls, experiments were carried out with granulate balls developed by Taprogge. In 6 series of experiments the overall heat transfer coefficient could be raised by 8%. Further experiments will follow. (orig.) [de

  3. Recommended method to prevent leakage of titanium tube in condenser

    International Nuclear Information System (INIS)

    Wang Jun

    2010-01-01

    Qinshan Phase III is located at the estuary area of Qiantang River, where contains much slit and sand in the seawater. Since the units were put into operation, tube bundles in the condenser have been scratched, damaged or blocked by hard foreign materials, and outside wall thickness reduced and broken due to various reasons. Many tube bundles are discarded. In order to effectively prevent the re-occurrence of such problem and eliminate the existing defects, equipment management personnels of Qinshan Phase III work together with experts both from home and abroad, and perfom root-analysis for various cause of defects. After the problem root is identified, a serious of specific and effective measures are taken to prevent and eliminate the problem and reached a good effect. This paper herein is written for comments and reference. (authors)

  4. Assessment of RELAP5/MOD3.2 with condensation experiment in the presence of noncondensables in a vertical tube

    Energy Technology Data Exchange (ETDEWEB)

    Park, Hyun Sik; No, Hee Cheon [Korea Advanced Institute of Science and Technology, Taejon (Korea, Republic of)

    1999-12-31

    The standard RELAP5/MOD3.2 code were assessed with the condensation experiment in the presence of noncondensable gas in a vertical tube of PCCS of CP-1300. There are two wall film condensation models, the default model and the alternative model, in RELAP5/MOD3.2. The experimental apparatus was modeled with the two models, and simulations were performed for several sub-tests to be compared with the experimental results. In overall sense the simulation results showed that the default model of RELAP5/MOD3.2 under-predicts the heat transfer coefficients, while the alternative model over-predicts them throughout the condensing tube. 10 refs., 6 figs. (Author)

  5. Assessment of RELAP5/MOD3.2 with condensation experiment in the presence of noncondensables in a vertical tube

    Energy Technology Data Exchange (ETDEWEB)

    Park, Hyun Sik; No, Hee Cheon [Korea Advanced Institute of Science and Technology, Taejon (Korea, Republic of)

    1998-12-31

    The standard RELAP5/MOD3.2 code were assessed with the condensation experiment in the presence of noncondensable gas in a vertical tube of PCCS of CP-1300. There are two wall film condensation models, the default model and the alternative model, in RELAP5/MOD3.2. The experimental apparatus was modeled with the two models, and simulations were performed for several sub-tests to be compared with the experimental results. In overall sense the simulation results showed that the default model of RELAP5/MOD3.2 under-predicts the heat transfer coefficients, while the alternative model over-predicts them throughout the condensing tube. 10 refs., 6 figs. (Author)

  6. Heat transfer, erosion and acid condensation characteristics for novel H-type finned oval tube

    International Nuclear Information System (INIS)

    Wang, Y; Zhao, X; Tang, G

    2015-01-01

    Low efficiency of heat transfer, acid corrosion and erosion of economizers affect the economy and security in coal-fired power plants significantly. The H-type finned oval tube is proposed to alleviate these problems. Based on the H-type finned oval tube, we investigated three novel types of fins, including bleeding dimples, longitudinal vortex generators (LVGs), and compound dimple-LVG. We considered the three aspects together, and obtained the heat transfer, acid condensation rate and erosion loss. The results show that the tube bank with the new structured fins can improve the performance on the three aspects, and the compound dimple-LVG performs the highest comprehensive effect. (paper)

  7. Titanium application to power plant condensers

    International Nuclear Information System (INIS)

    Itoh, H.

    1987-01-01

    Recently, the growth of operating performance and construction plan of titanium-tubed condensers in thermal and unclear power plants has been very impressive. High-quality, thinner welded titanium tubes used for cooling tubes, matching design specifications of condensers, have been stably supplied through mass production. It now can be said that various technical problems for titanium-tubed condensers have been solved, but data on operating performance in large-scale commercial plants are still scarce, and site-by-site information needs be exchanged more frequently and on a larger scale. Projects to replace existing condenser cooling tubes with those of corrosion-resistant titanium have been actively furthered, with the only remaining barrier to full employment being cost effectiveness. It is hoped that condenser and tube manufacturers will conduct more joint value analyses

  8. Simulating Porous Magnetite Layer Deposited on Alloy 690TT Steam Generator Tubes.

    Science.gov (United States)

    Jeon, Soon-Hyeok; Son, Yeong-Ho; Choi, Won-Ik; Song, Geun Dong; Hur, Do Haeng

    2018-01-02

    In nuclear power plants, the main corrosion product that is deposited on the outside of steam generator tubes is porous magnetite. The objective of this study was to simulate porous magnetite that is deposited on thermally treated (TT) Alloy 690 steam generator tubes. A magnetite layer was electrodeposited on an Alloy 690TT substrate in an Fe(III)-triethanolamine solution. After electrodeposition, the dense magnetite layer was immersed to simulate porous magnetite deposits in alkaline solution for 50 days at room temperature. The dense morphology of the magnetite layer was changed to a porous structure by reductive dissolution reaction. The simulated porous magnetite layer was compared with flakes of steam generator tubes, which were collected from the secondary water system of a real nuclear power plant during sludge lancing. Possible nuclear research applications using simulated porous magnetite specimens are also proposed.

  9. Electrochemical behavior of tube-fin assembly for an aluminum automotive condenser with improved corrosion resistance

    Science.gov (United States)

    Pech-Canul, M. A.; Guía-Tello, J. C.; Pech-Canul, M. I.; Aguilar, J. C.; Gorocica-Díaz, J. A.; Arana-Guillén, R.; Puch-Bleis, J.

    An aluminum automotive condenser was designed to exhibit high corrosion resistance in the seawater acetic acid test (SWAAT) combining zinc coated microchannel tubes and fins made with AA4343/AA3003(Zn)/AA4343 brazing sheet. Electrochemical measurements in SWAAT solution were carried out under laboratory conditions using tube-fin assembly and individual fin and tube samples withdrawn from the condenser core. The aim was to gain information on the protective role of the zinc sacrificial layer and about changes in corrosion behavior as a function of immersion time. External corrosion of the tube-fin system was simulated by immersion of mini-core samples under open circuit conditions. The corrosion rate increased rapidly during the first 6 h and slowly afterwards. The short time behavior was related to the dissolution of the oxide film and fast dissolution of the outermost part of the zinc diffusion layer. With the aid of cross-sectional depth corrosion potential profiles, it was shown that as the sacrificial layer gets dissolved, the surface concentration of zinc decreases and the potential shifts to less negative values. The results of galvanic coupling of tube and fins in a mini-cell showed that the tube became the anode while the fins exhibited cathodic behavior. An evolution in the galvanic interaction was observed, due to the progressive dissolution of the sacrificial zinc layer. The difference of uncoupled potentials between tube and fins decreased from 71 mV to 32 mV after 84 h of galvanic coupling. At the end of such period there was still a part of the zinc sacrificial layer remaining which would serve for protection of the tube material for even longer periods and there were indications of slight corrosion in the fins.

  10. Electrochemical behavior of tube-fin assembly for an aluminum automotive condenser with improved corrosion resistance

    Directory of Open Access Journals (Sweden)

    M.A. Pech-Canul

    Full Text Available An aluminum automotive condenser was designed to exhibit high corrosion resistance in the seawater acetic acid test (SWAAT combining zinc coated microchannel tubes and fins made with AA4343/AA3003(Zn/AA4343 brazing sheet. Electrochemical measurements in SWAAT solution were carried out under laboratory conditions using tube-fin assembly and individual fin and tube samples withdrawn from the condenser core. The aim was to gain information on the protective role of the zinc sacrificial layer and about changes in corrosion behavior as a function of immersion time. External corrosion of the tube-fin system was simulated by immersion of mini-core samples under open circuit conditions. The corrosion rate increased rapidly during the first 6 h and slowly afterwards. The short time behavior was related to the dissolution of the oxide film and fast dissolution of the outermost part of the zinc diffusion layer. With the aid of cross-sectional depth corrosion potential profiles, it was shown that as the sacrificial layer gets dissolved, the surface concentration of zinc decreases and the potential shifts to less negative values. The results of galvanic coupling of tube and fins in a mini-cell showed that the tube became the anode while the fins exhibited cathodic behavior. An evolution in the galvanic interaction was observed, due to the progressive dissolution of the sacrificial zinc layer. The difference of uncoupled potentials between tube and fins decreased from 71 mV to 32 mV after 84 h of galvanic coupling. At the end of such period there was still a part of the zinc sacrificial layer remaining which would serve for protection of the tube material for even longer periods and there were indications of slight corrosion in the fins. Keywords: Aluminum, Automotive, Corrosion, Galvanic, Zn coating

  11. Effect of non-condensable gas on heat transfer in steam turbine condenser and modelling of ejector pump system by controlling the gas extraction rate through extraction tubes

    International Nuclear Information System (INIS)

    Strušnik, Dušan; Golob, Marjan; Avsec, Jurij

    2016-01-01

    Graphical abstract: Control of the amount of the pumped gases through extraction tubes. The connecting locations interconnect the extraction tubes for STC gas pumping. The extraction tubes are fitted with 3 control valves to control the amount of the pumped gas depending on the temperature of the pumped gas. The amount of the pumped gas increases through the extraction tubes, where the pumped gases are cooler and decreases, at the same time, through the extraction tubes, where the pumped gases are warmer. As a result, pumping of a larger amount of NCG is ensured and of a smaller amount of CG, given that the NCG concentration is the highest on the colder places. This way, the total amount of the pumped gases from the STC can be reduced, the SEPS operates more efficiently and consumes less energy for its operation. - Highlights: • Impact of non-condensable gas on heat transfer in a steam turbine condenser. • The ejector system is optimised by selecting a Laval nozzle diameter. • Simulation model of the control of the amount of pumped gases through extraction tubes. • Neural network and fuzzy logic systems used to control gas extraction rate. • Simulation model was designed by using real process data from the thermal power plant. - Abstract: The paper describes the impact of non-condensable gas (NCG) on heat transfer in a steam turbine condenser (STC) and modelling of the steam ejector pump system (SEPS) by controlling the gas extraction rate through extraction tubes. The ideal connection points for the NCG extraction from the STC are identified by analysing the impact of the NCG on the heat transfer and measuring the existing system at a thermal power plant in Slovenia. A simulation model is designed using the Matlab software and Simulink, Neural Net Work, Fuzzy Logic and Curve Fitting Toolboxes, to control gas extraction rate through extraction tubes of the gas pumped from the STC, thus optimising the operation of the steam ejector pump system (SEPS). The

  12. Experimental determination of the heat transfer coefficient in shell-and-tube condensers using the Wilson plot method

    Directory of Open Access Journals (Sweden)

    Havlik Jan

    2017-01-01

    Full Text Available This article deals with the experimental determination of heat transfer coefficients. The calculation of heat transfer coefficients constitutes a crucial issue in design and sizing of heat exchangers. The Wilson plot method and its modifications based on measured experimental data utilization provide an appropriate tool for the analysis of convection heat transfer processes and the determination of convection coefficients in complex cases. A modification of the Wilson plot method for shell-and-tube condensers is proposed. The original Wilson plot method considers a constant value of thermal resistance on the condensation side. The heat transfer coefficient on the cooling side is determined based on the change in thermal resistance for different conditions (fluid velocity and temperature. The modification is based on the validation of the Nusselt theory for calculating the heat transfer coefficient on the condensation side. A change of thermal resistance on the condensation side is expected and the value is part of the calculation. It is possible to improve the determination accuracy of the criterion equation for calculation of the heat transfer coefficient using the proposed modification. The criterion equation proposed by this modification for the tested shell-and-tube condenser achieves good agreement with the experimental results and also with commonly used theoretical methods.

  13. Thermal creep behavior of N36 zirconium alloy cladding tube

    International Nuclear Information System (INIS)

    Wang, P.; Zhao, W.; Dai, X.

    2015-01-01

    N36 is an alloy containing Zr, Sn, Nb and Fe that is developed by China as a superior cladding material to meet the performance of PWR fuel assembly at the maximum fuel rod burn-up. The creep characteristics of N36 zirconium alloy cladding tube were investigated at temperature from 593 K to 723 K with stress ranging from 20 MPa to 160 MPa. Transitions in creep mechanisms were noted, showing the distinct three rate-controlled creep mechanisms for the alloy at test conditions. In the region of low stresses with stress exponent n ∼ 1 and activation energy Q ∼ (104±4) kJ.mol -1 , Coble creep, based on diffusion of materials through grain boundaries, is the dominant rate-controlling mechanism, which contributes to the creep deformation. The formation of slip bands acts as an accommodation mechanism. In the region of middle stress with stress exponent n ∼ 3 and activation energy Q ∼ (195±7) kJ.mol -1 , micro-creep, caused by viscous gliding of dislocations due to the interaction of O atoms with dislocations, controls the deformation. In the high stress region with stress exponent n ∼ 5-6 and activation energy Q ∼ (210±10) kJ.mol -1 , two mechanisms of the climb of edge dislocations (EDC) and the motion of jogged screw dislocation (MJS) contribute to rate controlling process. In test conditions N36 alloy cladding tube behaves a type of creep similar to that noted in class-I (A) alloys

  14. Condensation in complex geometries

    International Nuclear Information System (INIS)

    Lauro, F.

    1975-01-01

    A mathematical evaluation of the condensation exchange coefficient can only succeds for well specified cases: small upright or inclined plates, horizontal tubes, small height vertical tubes. Among the main hypotheses accounted for this mathematical development in the case of the condensate, a laminar flow and uniform surface temperature are always considered. In practice certain shapes of surfaces significantly increase the heat transfer during the vapor condensation on a surface wet by the condensate. Such surfaces are rough surfaces such as the condensate is submitted to surface tension effects, negligeable for plane or large curvature surfaces, and the nature of the material may play an important role (temperature gradients). Results from tests on tubes with special shapes, performed in France or out of France, are given [fr

  15. Qualification of stainless steel for OTEC heat exchanger tubes

    Energy Technology Data Exchange (ETDEWEB)

    LaQue, F.L.

    1979-01-01

    The history of the AL-6X alloy is reviewed and its credentials as a candidate for use as tubing in Ocean Thermal Energy Conversion Heat Exchangers are examined. Qualification is based on results of accelerated tests using ferric chloride for resistance to crevice corrosion and pitting, long-time crevice corrosion and pitting tests in natural sea water and anticipated resistance to attack by ammonia and mixtures of ammonia and sea water. Since the alloy has no natural resistance to fouling by marine organisms, it must be able to accomodate action to prevent fouling by chlorination or to remove it by mechanical cleaning techniques or appropriate chemical cleaning methods. The satisfactory behavior indicated by the various accelerated and long-time corrosion tests has been confirmed by excellent performance of several million feet of tubing in condensers in coastal power plants. Early evaluation tests demonstrated the need for proper heat treatment to avoid the presence of a sigma phase, which promoted severe pitting of some, but not all, specimens in tests in natural sea water. The available data qualify the AL-6X alloy as being a satisfactory alternate to titanium for tubes in OTEC heat exchangers.

  16. THE DETECTION OF THE NECESSARY CONDITIONS OF EFFECTIVE FUNCTIONING OF THE BALL CLEANING SYSTEM OF THE TUBES OF STEAM TURBINE CONDENSERS. Part 1

    Directory of Open Access Journals (Sweden)

    A. G. Gerasimova

    2017-01-01

    Full Text Available A problem of an increase of the power of turbine by improving heat transfer in condensers of steam turbines is considered in the article as a topical one. The analysis of contamination of the internal surfaces of cooling tubes and of the influence of pollution on the process of heat transfer in turbine condensers has been fulfilled. The existing method of cleaning of condenser tubes with the use of porous elastic balls of sponge rubber that is implemented on a number of large thermal power plants and state region power plants of the Republic of Belarus is examined. In the operation of the ball cleaning system a significant drawback has been revealed, viz. a low efficiency of this method due to the failure to comply with preparation the system of circulating water for operation. Also, a certain imperfection of ball cleaning system technology has been determined. One of the prerequisites for the effective functioning of the ball cleaning system is a certain degree of purity of the pipe system of the condenser, characterized by the coefficient of purity. To determine the effectiveness of ball cleaning system a series of experiments on the launching of porous rubber balls in the pipe system of the main and the embedded bunches of the T-250/300-240 UTMZ turbine has been produced. Immediately before the experiments hydraulic cleaning of the tubes of the condenser by a high-pressure installation were carried out. During the experiments, records of the number of downloaded porous rubber balls, of the number of rubber balls captured in a loading chamber, and of the number of rubber balls that remained in a calibration device were kept. A large proportion of default of the balls caused by the presence of residues of the carbonate sediments, that obstruct the movement of porous rubber balls in the tubes of the condenser, was determined. The presence of carbonate deposits in the tubes of the condenser indicates a lack of effectiveness of antiscale treatment

  17. A calculation and measurement of the flow field in a steam condenser external to the tube nest

    International Nuclear Information System (INIS)

    Stastny, M.; Feistauer, M.

    1989-01-01

    The suggested physical and mathematical model is used to solve the flow of steam normal to the cooling tubes of condenser cross-sections in the region external to the nests. Numerical calculations are carried out by means of a multipurpose system of programmes for the finite element method and a programme for the boundary layer calculation. The results of the calculations are compared with measurements on the condenser of a 500MW steam turbine. The calculations of the flow field in a double pass condenser for the 1000MW saturated steam turbine are described. (author)

  18. PLUSS-A weldless leaktight sleeve for alloy 600/690 steam generator tubes

    International Nuclear Information System (INIS)

    Potz, F.; Bohmann, W.

    1998-01-01

    The ABB PLUSS sleeving represents a new SG tube repair technique qualified and approved to replace in the future most of the plugging as well as welded sleeving. Basically the advantages of an innovative combination of both alloys 600/690 and 800 are taken into consideration. The upper sleeve/SG tube-joint is hydraulically expanded stressing the SG tube only within the elastic range. The lower joint is hard rolled. The installation processes are simple and reproducible, fast, computerized and individually recorded. The operating temperature range of the sleeved SG-tube is effectively reduced so that any further corrosion is impeded. Both, sleeve and SG tube are fully inspectable by ECT. (author)

  19. Evaporation and condensation of steam-water in a vertical tube

    International Nuclear Information System (INIS)

    Sun, G.; Hewitt, G.F.

    2001-01-01

    Heat Transfer data have been obtained for water from single-phase flow to two-phase annular flow at 0.07-0.09 MPa in a 9.5 mm vertical bore tube under conditions of evaporation and condensation in the same test section. The main aim of the experiments was to elucidate the mechanism of heat transfer in annular flow by distinguishing between the conventional explanation of a purely convective mechanism at high quality region and the alternative hypothesis in which heat transfer is enhanced by secondary nucleation in the region. To avoid ambiguities in local hydrodynamic conditions the experiments were carried out under the same conditions (namely equilibrium annular flow) for both evaporation and condensation in the same test section. The results indicated a forced convective mechanism of the conventional type rather than the alternative thin film boiling mechanism (secondary nucleation) as suggested by Mesler (AIChE, 23 (1977) 448). The heat transfer coefficients in single-phase flow and annular flow regimes are compared with literature correlations. The results show that the present data are in reasonable agreement with existing correlations

  20. All welded titanium condenser adopted in atomic power plants

    International Nuclear Information System (INIS)

    Iwai, Nagao; Itabashi, Yukihiko

    1980-01-01

    Condensers in power plants are shell-and-tube type heat exchangers. Most condensers use seawater as a coolant. Their tube and tube Sheets have usually been made of brass, which resists corrosion but cannot completely prevent it; as a result, tubes sometimes corrode or erode, allowing seawater to leak into the turbine cycle. As is well known, titanium has almost complete corrosion resistance against seawater; for this reason titanium tubes have replaced brass ones in some condensers operating in Europe and the USA. Even in such condensers, though, the tube plates have still been made of brass, tightly fitted to the titanium tubes, and it has proved impossible to eliminate seawater leakage at the junctions between tubes and tube Sheets. In order to eliminate such leakage completely, the tube Sheets must be made of titanium too, and the tubes and plates must be welded together. However, the welding of titanium requires an extremely celan atmosphere, a condition very difficult to fulfill at power plant construction sites, and the use of whole welded titanium tube condensers has long been considered a practical impossibility. Such all-titanium welded condensers have now been successfully constructed and installed in two 600 MW fossil power plants and one 1100 MW nuclear power plant. This paper describes the techniques used, add in addition reviews the various materials that have been used in condenser tubes. (author)

  1. Computations for a condenser. Experimental results

    International Nuclear Information System (INIS)

    Walden, Jean.

    1975-01-01

    Computations for condensers are presented with experimental results. The computations are concerned with the steam flux at the condenser input, and inside the tube bundle. Experimental results are given for the flux inside the condenser sleeve and the flow passing through the tube bundle [fr

  2. Numerical study of the thermo-flow performances of novel finned tubes for air-cooled condensers in power plant

    Science.gov (United States)

    Guo, Yonghong; Du, Xiaoze; Yang, Lijun

    2018-02-01

    Air-cooled condenser is the main equipment of the direct dry cooling system in a power plant, which rejects heat of the exhaust steam with the finned tube bundles. Therefore, the thermo-flow performances of the finned tubes have an important effect on the optimal operation of the direct dry cooling system. In this paper, the flow and heat transfer characteristics of the single row finned tubes with the conventional flat fins and novel jagged fins are investigated by numerical method. The flow and temperature fields of cooling air for the finned tubes are obtained. Moreover, the variations of the flow resistance and average convection heat transfer coefficient under different frontal velocity of air and jag number are presented. Finally, the correlating equations of the friction factor and Nusselt number versus the Reynolds number are fitted. The results show that with increasing the frontal velocity of air, the heat transfer performances of the finned tubes are enhanced but the pressure drop will increase accordingly, resulting in the average convection heat transfer coefficient and friction factor increasing. Meanwhile, with increasing the number of fin jag, the heat transfer performance is intensified. The present studies provide a reference in optimal designing for the air-cooled condenser of direct air cooling system.

  3. Evolution of the feedback from experience on degradations of French nuclear power plants condensers and foreseen solutions

    Energy Technology Data Exchange (ETDEWEB)

    Mayos, M.; Chanel, F.; Copin, E.; Carlier, L. [EDF/DIN/CEIDRE, Saint-Denis (France); Coquio, N.; Garbay, E. [EDF/DIN/CEIDRE, Avoine (France); Bastian, C. [EDF/DPN/UNIE, Saint-Denis (France)

    2011-07-01

    The materials constituting the condenser tubes of French nuclear power plants display a great diversity and are subject to different degradations, known from the operational feedback from experience. Copper alloys (mainly brass), which were bound to disappear in renovated condensers, are still significantly present, due to their unique bacteriostatic ability. Brass tubes lifetime is still governed in general by steady abrasion, as evaluated by eddy current nondestructive testing. However, an atypical NDE (non-destructive evaluation) behavior has led to spot a new damage: localized under-deposit pitting corrosion on the raw water side, caused by the particular quality of water chemistry and heavy scaling of the tube surface. This damage is likely to overcome steady abrasion for tube life prediction. Prevention includes a tighter look at NDE indications and improved descaling solutions (chemical or mechanical). Other specific damages have been reported from operation feedback: the main one was accidental stress corrosion cracking, which has occurred on some recently renovated brass condenser tube bundles. Thanks to a metallurgical and mechanical study, its cause was found in the manufacturing process. This experience has resulted in tightened specifications for brass tubes manufacturing. Stainless steel and titanium still appear more damage-resistant and represent a safe solution when no microorganism issue is present. The degradation feedback, confirmed by NDE inspections, is very low in French power plants. However, titanium hydriding still represents an issue when cathodic protection is present. Furthermore, some other damages have been reported on titanium, like isolated steam erosion. Vibration fatigue damage has been observed on stainless steel tubes, but it is more in relationship with the condenser design than with the material itself. (authors)

  4. Influence of tube spinning on formability of friction stir welded aluminum alloy tubes for hydroforming application

    Energy Technology Data Exchange (ETDEWEB)

    Wang, X.S. [State Key Laboratory of Advanced Welding and Joining, Harbin Institute of Technology, Harbin 150001 (China); Hu, Z.L., E-mail: zhilihuhit@163.com [State Key Laboratory of Advanced Welding and Joining, Harbin Institute of Technology, Harbin 150001 (China); Hubei Key Laboratory of Advanced Technology of Automobile Parts, Wuhan University of Technology, Wuhan 430070 (China); State Key Laboratory of Materials Processing and Die and Mould Technology, Huazhong University of Science and Technology (China); Yuan, S.J. [State Key Laboratory of Advanced Welding and Joining, Harbin Institute of Technology, Harbin 150001 (China); Hua, L. [Hubei Key Laboratory of Advanced Technology of Automobile Parts, Wuhan University of Technology, Wuhan 430070 (China)

    2014-06-01

    Due to economic and ecological reasons, the application of tailor-welded blanks of aluminum alloy has gained more and more attention in manufacturing lightweight structures for automotives and aircrafts. In the study, the research was aimed to highlight the influence of spinning on the formability of FSW tubes. The microstructural characteristics of the FSW tubes during spinning were studied by electron backscattered diffraction (EBSD) and transmission electron microscopy (TEM). The formability of the FSW tubes with different spinning reduction was assessed by hydraulic bulge test. It is found that the spinning process shows a grain refinement of the tube. The grains of the FSW tube decrease with increasing thickness reduction, and the effect of grain refinement is more obvious for the BM compared to that of the weld. The difference of grain size and precipitates between the weld and BM leads to an asymmetric W-type microhardness distribution after spinning. The higher thickness reduction of the tube, the more uniform distribution of grains and precipitates it shows, and consequently results in more significant increase of strength. As compared with the result of tensile test, the tube after spinning shows better formability when the stress state changes from uniaxial to biaxial stress state.

  5. Development of balanced downflow type surface condensers, (2)

    International Nuclear Information System (INIS)

    Tomida, Akira; Oshima, Yoshikuni; Okochi, Isao; Izumi, Kenkichi.

    1976-01-01

    As the size of the condensers for power generation plants grew large, the new balanced downflow type condenser was developed and completed on the basis of the experiment on steam flow according to the two-dimensional flow model, the analysis of the performance in a tube nest with a computer, and the studies on the effect of outside liquid film and the reheating deaeration of condensate. When the balanced downflow type condensers were adopted for actual plants, the construction, strength and production method were examined, and the reliability of the new condenser was confirmed by the thermal characteristic experiment with the model similar to the actual machine. The condenser comprises a condenser body, supporting plates, cooling tubes, tube plates, water chambers, and reinforcements, and the cooling tubes are arranged so as to exchange heat effectively. The arrangement of tubes is divided into three regions, namely radiation portion, densely arranged portion, and air cooling portion. In the balanced downflow type condensers, the dilution by utilizing condensate is provided against ammonia attack. The apparatuses for the thermal characteristic experiment and the experimental results, and the results of the performance test on the actual balanced downflow type condenser are reported. (Kako, I.)

  6. Impact Fretting Wear Behavior of Alloy 690 Tubes in Dry and Deionized Water Conditions

    Institute of Scientific and Technical Information of China (English)

    Zhen-Bing Cai; Jin-Fang Peng; Hao Qian; Li-Chen Tang; Min-Hao Zhu

    2017-01-01

    The impact fretting wear has largely occurred at nuclear power device induced by the flow-induced vibration,and it will take potential hazards to the service of the equipment.However,the present study focuses on the tangential fretting wear of alloy 690 tubes.Research on impact fretting wear of alloy 690 tubes is limited and the related research is imminent.Therefore,impact fretting wear behavior of alloy 690 tubes against 304 stainless steels is investigated.Deionized water is used to simulate the flow environment of the equipment,and the dry environment is used for comparison.Varied analytical techniques are employed to characterize the wear and tribochemical behavior during impact fretting wear.Characterization results indicate that cracks occur at high impact load in both water and dry equipment;however,the water as a medium can significantly delay the cracking time.The crack propagation behavior shows a jagged shape in the water,but crack extended disorderly in dry equipment because the water changed the stress distribution and retarded the friction heat during the wear process.The SEM and XPS analysis shows that the main failure mechanisms of the tube under impact fretting are fatigue wear and friction oxidation.The effect of medium(water) on fretting wear is revealed,which plays a potential and promising role in the service of nuclear power device and other flow equipments.

  7. Observations and insights into Pb-assisted stress corrosion cracking of alloy 600 steam generator tubes

    International Nuclear Information System (INIS)

    Thomas, L.; Bruemmer, Stephen M.

    2005-01-01

    Pb-assisted stress-corrosion cracking (PbSCC) of Alloy 600 steam-generator tubing in high-temperature-water service and laboratory tests were studied by analytical transmission electron microscopy of cross-sectioned samples. Examinations of pulled tubes from many pressurized water reactors revealed lead in cracks from 11 of 17 samples. Comparisons of the degraded intergranular structures with ones produced in simple laboratory tests with PbO in near-neutral AVT water showed that the PbSCC characteristics in service tubing could be reproduced without complex chemistries and heat-flow conditions that can occur during plant operation. Observations of intergranular and transgranular cracks promoted by Pb in the test samples also provided new insights into the mechanisms of PbSCC in mill-annealed and thermally treated Alloy 600

  8. SCC analysis of Alloy 600 tubes from a retired steam generator

    Science.gov (United States)

    Hwang, Seong Sik; Kim, Hong Pyo

    2013-09-01

    Steam generators (SG) equipped with Alloy 600 tubes of a Korean nuclear power plants were replaced with a new one having Alloy 690 tubes in 1998 after 20 years of operation. To set up a guide line for an examination of the other SG tubes, a metallographic examination of the defected tubes was carried out. A destructive analysis on 71 tubes was addressed, and a relation among the stress corrosion crack (SCC) defect location, defect depth, and location of the sludge pile was obtained. Tubes extracted from the retired SG were transferred to a hot laboratory. Detailed nondestructive analysis examinations were taken again at the laboratory, and the tubes were then destructively examined. The types and sizes of the cracks were characterized. The location and depth of the SCC were evaluated in terms of the location and height of the sludge. Most axial cracks were in the sludge pile, whereas the circumferential ones were around the top of the tube sheet (TTS) or below the TTS. Average defect depth of the axial cracks was deeper than that of the circumferential ones. Axial cracks at tube support plate (TSP) seem to be related with corrosion/sludge in crevice like at the TTS region. Circumferential cracks at TSP seem to be caused by tube denting at the upper part of the TSP. Tubes not having clear ECT signals for quantifying an ECT data-base. Tubes having no ECT signal. Tubes with a large ECT signal. Tubes with various types and sizes of flaws (primary water stress corrosion cracking (PWSCC), outside diameter stress corrosion cracking (ODSCC), Pit). Tubes with distinct PWSCC or ODSCC. Tubes were extracted from the RSG based on the field ECT with the criteria, and transferred to a hot laboratory at the Korea Atomic Energy Research Institute (KAERI) for destructive examination. A comprehensive ECT inspection was performed again at the hot laboratory to confirm the location of the cracks obtained from a field inspection. These exact locations of the defects were marked on the

  9. Effects of Oxidation and fractal surface roughness on the wettability and critical heat flux of glass-peened zirconium alloy tubes

    International Nuclear Information System (INIS)

    Fong, R.W.L.; Nitheanandan, T.; Bullock, C.D.; Slater, L.F.; McRae, G.A.

    2003-05-01

    Glass-bead peening the outside surfaces of zirconium alloy tubes has been shown to increase the Critical Heat Flux (CHF) in pool boiling of water. The CHF is found to correlate with the fractal roughness of the metal tube surfaces. In this study on the effect of oxidation on glass-peened surfaces, test measurements for CHF, surface wettability and roughness have been evaluated using various glass-peened and oxidized zirconium alloy tubes. The results show that oxidation changes the solid-liquid contact angle (i.e., decreases wettability of the metal-oxide surface), but does not change the fractal surface roughness, appreciably. Thus, oxidation of the glass-peened surfaces of zirconium alloy tubes is not expected to degrade the CHF enhancement obtained by glass-bead peening. (author)

  10. Flow condensation pressure drop characteristics of R410A-oil mixture inside small diameter horizontal microfin tubes

    Energy Technology Data Exchange (ETDEWEB)

    Huang, Xiangchao; Ding, Guoliang; Hu, Haitao; Zhu, Yu [Institute of Refrigeration and Cryogenics, Shanghai Jiaotong University, Shanghai 200240 (China); Gao, Yifeng [International Copper Association Shanghai Office, Shanghai 200020 (China); Deng, Bin [Institute of Heat Transfer Technology, Golden Dragon Precise Copper Tube Group Inc., Shanghai 200135 (China)

    2010-11-15

    Flow condensation pressure drop characteristics of R410A-oil mixture inside small diameter (5.0 mm and 4.0 mm O.D.) horizontal microfin tubes were investigated experimentally covering nominal oil concentrations from 0% to 5%. The research results indicate that, comparing with the frictional pressure drop of pure R410A, the frictional pressure drop of R410A-oil mixture may decrease by maximum of 18% when the vapor quality is lower than 0.6, and increase by maximum of 13% when the vapor quality is higher than 0.6. A new frictional pressure drop correlation for R410A-oil mixture flow condensation inside microfin tubes is developed based on the refrigerant-oil mixture properties, and can agree with 94% of the experimental data within a deviation of -30% to +30%. (author)

  11. Thermal design, rating and second law analysis of shell and tube condensers based on Taguchi optimization for waste heat recovery based thermal desalination plants

    Science.gov (United States)

    Chandrakanth, Balaji; Venkatesan, G; Prakash Kumar, L. S. S; Jalihal, Purnima; Iniyan, S

    2018-03-01

    The present work discusses the design and selection of a shell and tube condenser used in Low Temperature Thermal Desalination (LTTD). To optimize the key geometrical and process parameters of the condenser with multiple parameters and levels, a design of an experiment approach using Taguchi method was chosen. An orthogonal array (OA) of 25 designs was selected for this study. The condenser was designed, analysed using HTRI software and the heat transfer area with respective tube side pressure drop were computed using the same, as these two objective functions determine the capital and running cost of the condenser. There was a complex trade off between the heat transfer area and pressure drop in the analysis, however second law analysis was worked out for determining the optimal heat transfer area vs pressure drop for condensing the required heat load.

  12. Delayed hydride cracking behavior of Zr-2.5Nb alloy pressure tubes for PHWR700

    Energy Technology Data Exchange (ETDEWEB)

    Sunil, S.; Bind, A.K.; Khandelwal, H.K.; Singh, R.N., E-mail: rnsingh@barc.gov.in; Chakravartty, J.K.

    2015-11-15

    In order to attain improved in-reactor performance few prototypes pressure tubes of Zr-2.5Nb alloy were manufactured by employing forging to break the cast structure and to obtain more homogeneous microstructure. Both double forging and single forging were employed. The forged material was further processed by employing hot extrusion, cold pilgering and autoclaving. A detailed characterization in terms of mechanical properties and microstructure of the prototype tubes were carried for qualifying it for intended use as pressure tubes in PHWR700 reactors. In this work, Delayed Hydride Cracking (DHC) behavior of the forged Zr-2.5Nb pressure tube material characterized in terms of DHC velocity and threshold stress intensity factor associated with DHC (K{sub IH}) was compared with that of conventionally manufactured material in the temperature range of 200–283 °C. Activation energy associated with the DHC in this alloy was found to be ∼60 kJ/mol for the forged materials.

  13. Integrity evaluation of Alloy 600 RV head penetration tubes in Korean PWR plants

    International Nuclear Information System (INIS)

    Kang, Young Hwan; Park, Sung Ho; Hong, Sung Yull; Choi, Kwang Hee

    1995-01-01

    The structural integrity assessment of Alloy 600 RV head penetration tubes has been an important issue for the economical and reliable operation of power plants. In this paper, an overview of the integrity evaluation program for the RV head penetration tubes in Korean nuclear power plants is presented. Since the crack growth mechanism of the penetration tube is due to the primary water stress corrosion cracking (PWSCC) which is mainly related to the stress at the tube, the present paper consists of three primary activities: the stress evaluation, the flaw evaluation, and data generation through material and mechanical tests. (author). 5 refs, 2 figs, 1 tab

  14. Long-term creep rupture strength of weldment of Fe-Ni based alloy as candidate tube and pipe for advanced USC boilers

    Energy Technology Data Exchange (ETDEWEB)

    Bao, Gang; Sato, Takashi [Babcok-Hitachi K.K., Hiroshima (Japan). Kure Research Laboratory; Marumoto, Yoshihide [Babcok-Hitachi K.K., Hiroshima (Japan). Kure Div.

    2010-07-01

    A lot of works have been going to develop 700C USC power plant in Europe and Japan. High strength Ni based alloys such as Alloy 617, Alloy 740 and Alloy 263 were the candidates for boiler tube and pipe in Europe, and Fe-Ni based alloy HR6W (45Ni-24Fe-23Cr-7W-Ti) is also a candidate for tube and pipe in Japan. One of the Key issues to achieve 700 C boilers is the welding process of these alloys. Authors investigated the weldability and the long-term creep rupture strength of HR6W tube. The weldments were investigated metallurgically to find proper welding procedure and creep rupture tests are ongoing exceed 38,000 hours. The long-term creep rupture strengths of the HST weld joints are similar to those of parent metals and integrity of the weldments was confirmed based on with other mechanical testing results. (orig.)

  15. Influence of oil on flow condensation heat transfer of R410A inside 4.18 mm and 1.6 mm inner diameter horizontal smooth tubes

    Energy Technology Data Exchange (ETDEWEB)

    Huang, Xiangchao; Ding, Guoliang; Hu, Haitao; Zhu, Yu.; Peng, Hao [Institute of Refrigeration and Cryogenics, Shanghai Jiaotong University, Shanghai 200240 (China); Gao, Yifeng [International Copper Association Shanghai Office, Shanghai 200020 (China); Deng, Bin [Institute of Heat Transfer Technology, Golden Dragon Precise Copper Tube Group Inc., Shanghai 200135 (China)

    2010-01-15

    The influence of oil on condensation heat transfer of R410A inside 4.18 mm and 1.6 mm inner diameter horizontal smooth tubes is investigated experimentally. The experimental condensing temperature is 40 C, and nominal oil concentration range is from 0% to 5%. The test results indicate that the presence of oil deteriorates the heat transfer, and the deterioration effect becomes obvious with the increase of oil concentration. At oil concentration of 5%, the heat transfer coefficient decreases by maximum 24.9% and 28.5% for 4.18 mm and 1.6 mm tubes, respectively. A new correlation for heat transfer coefficients of R410A-oil mixture flow condensation inside smooth tubes is proposed, which agrees with all the experimental data within a deviation of -30% {proportional_to} +20%. (author)

  16. Tensile properties of Zr-2.5 Nb pressure tube alloy between 25 and 800 degC

    International Nuclear Information System (INIS)

    Singh, R.N.; Kishore, R.; Sinha, T.K.; Banerjee, S.

    2000-10-01

    Tensile properties of zirconium-2.5 wt. % niobium pressure tube material were evaluated by uniaxial tension tests at temperatures between 25 and 800 degC and under strain-rates varying from 3.3 x 10 -5 to 3.3 x 10 -3 /s. Tests were carried out on specimens fabricated from the sections of finished (autoclaved) tubes as well as on those machined from the sections of cold worked (2 nd pilgered) tubes. Moreover, specimens fabricated from finished tubes belonging to twenty different heats were tested at 300 degC to study the heat to heat variation in tensile properties of this alloy. In order to study the effect of the crystallographic texture on the tensile properties, specimens oriented in longitudinal as well as, in transverse directions of the tubes were also tested. Results showed that both yield and ultimate tensile strengths of this alloy decreased monotonically with increasing test temperatures, with a rapid fall in strengths above a temperature of 350 degC (623 K). The tensile ductility did not change appreciably up to 400 degC (673K) but increased rapidly above this temperature. The observed results on the temperature dependence of the strength and ductility indicated the possible occurrence of dynamic strain-ageing in this alloy in the temperature range of 200-300 degC (473 to 573 K). The transverse specimens showed higher strengths and lower ductility as compared to those of the longitudinal specimens up to a temperature of 350 degC (623 K). Above 350 degC, the difference in the strengths and the ductility of the two types of the specimens, became negligibly small indicating that the texture did not appreciably influence the tensile properties of this alloy at temperatures exceeding 350 degC. The alloy developed extensive superplasticity (ductility exceeding 100 %), when tested in the temperature range of 650-800 degC. Maximum ductility values of 650 % for longitudinal and 900 % for the transverse orientation with strain-rate sensitivity (m) exceeding 0

  17. Heat and mass transfer prediction of binary refrigerant mixtures condensing in a horizontal microfin tube

    Energy Technology Data Exchange (ETDEWEB)

    Koyama, Shigeru; Yu, Jian; Ishibashi, Akira

    1999-07-01

    In the face of the phase-out of HCFC22 for its effect on globe environment, the alternative refrigerant has been paid attention in the refrigeration and heat pump industry. In the present stage, it is found that any pure refrigerant is not a good substitute of HCFC22 for the system in use. The authors have to use binary or ternary refrigerant mixtures as the substitute to meet industrial requirement. But until now, although the heat transfer characteristics of the refrigerant mixtures can be measured in experiments and predicted in some degree, the mass transfer characteristics in condensation process, which is a main part in most systems, can not be clarified by both experimental and theoretical methods. In the present study a non-equilibrium model for condensation of binary refrigerant mixtures inside a horizontal microfin tube is proposed. In this model it is assumed that the phase equilibrium is only established at the vapor-liquid interface, while the bulk vapor and the bulk liquid are in non-equilibrium in the same cross section. The mass transfer characteristic in vapor core is obtained from the analogy between mass and momentum transfer. In the liquid layer, the mass fraction distribution is neglected, but the mass transfer coefficient is treated as infinite that can keep a finite value for the mass transfer rate in liquid phase. From the calculation results compared with the experimental ones for the condensation of HFC134a/HCFC123 and HCFC22/CFC114 mixtures, it is found that the calculated heat flux distribution along the tube axis is in good agreement with that of experiment, and the calculated values of condensing length agree well with the experimental ones. Using the present model, the local mass faction distribution, the diffusion mass transfer rate and the mass transfer characteristics in both vapor and liquid phase are demonstrated. From these results, the effect of mass transfer resistance on condensation heat transfer characteristics for binary

  18. Condensation heat transfer characteristics of R410A-oil mixture in 5 mm and 4 mm outside diameter horizontal microfin tubes

    Energy Technology Data Exchange (ETDEWEB)

    Huang, Xiangchao; Ding, Guoliang; Hu, Haitao; Zhu, Yu [Institute of Refrigeration and Cryogenics, Shanghai Jiaotong University, Shanghai 200240 (China); Gao, Yifeng [International Copper Association Shanghai Office, Shanghai 200020 (China); Deng, Bin [Institute of Heat Transfer Technology, Golden Dragon Precise Copper Tube Group Inc., Shanghai 200135 (China)

    2010-10-15

    Condensation heat transfer characteristics of R410A-oil mixture in 5 mm and 4 mm outside diameter horizontal microfin tubes were investigated experimentally. The experimental condensing temperature is 40 C, and nominal oil concentration range is from 0% to 5%. The test results indicate that the presence of oil deteriorates the heat transfer. The deterioration effect is negligible at nominal oil concentration of 1%, and becomes obvious with the increase of nominal oil concentration. At 5% nominal oil concentration, the heat transfer coefficient of R410A-oil mixture is found to have a maximum reduction of 25.1% and 23.8% for 5 mm and 4 mm tubes, respectively. The predictabilities of the existing condensation heat transfer correlations were verified with the experimental data, and Yu and Koyama correlation shows the best predictability. By replacing the pure refrigerant properties with the mixture's properties, Yu and Koyama correlation has a deviation of -15% to + 20% in predicting the local condensation heat transfer coefficient of R410A-oil mixture. (author)

  19. Enhancement of Condensation Heat Transfer Rate of the Air-Steam Mixture on a Passive Condenser System Using Annular Fins

    Directory of Open Access Journals (Sweden)

    Yeong-Jun Jang

    2017-11-01

    Full Text Available This paper presents an experimental investigation on the enhancement of the heat transfer rate of steam condensation on the external surfaces of a vertical tube with annular fins. A cylindrical condenser tube, which is 40 mm in outer diameter and 1000 mm in length, with annular disks of uniform cross-sectional area is fabricated in the manner of ensuring perfect contact between the base surface and fins. A total of 13 annular fins of 80 mm diameter were installed along the tube height in order to increase the effective heat transfer area by 85%. Through a series of condensation tests for the air-steam mixture under natural convection conditions, the heat transfer data was measured in the pressure range of between 2 and 5 bar, and the air mass fraction from 0.3 to 0.7. The rates of heat transfer of the finned tube are compared to those that are measured on a bare tube to demonstrate the enhanced performance by extended surfaces. In addition, based on the experimental results and the characteristics of steam condensation, the applicability of finned tubes to a large condenser system with a bundle layout is evaluated.

  20. Boiling and condensation in microfin tubes

    Science.gov (United States)

    Schlager, Lynn M.

    A general overview of microfin tubes and their applications is presented. Manufacturing processes, commercial availability, experimental heat transfer, and pressure drop data for various refrigerants (including alternative refrigerants and refrigerant-oil mixtures), physical mechanisms of enhancement, and the incorporation of microfin tubes in common heat exchanger configurations are discussed. Microfin tubes, also known by various trade names, are characterized by numerous small fins which typically spiral down the inside wall of tubes at angles ranging from 10 to 30 degrees. The number of fins ranges from 48 to 70 with typical fin heights of 0.12 to 0.30 mm (fin height generally less than 3 percent of the inside diameter of the tube). Fin shapes may vary and the inside surface area of microfin tubes is 10 to 70 percent greater than the area of equivalent smooth tubes. Heat transfer can be enhanced by up to a factor of three with microfin tubes.

  1. Examination of steam generator alloy 800 NG tube from the Almaraz unit 2 NPP

    International Nuclear Information System (INIS)

    Diego, G. de; Gomez Briceno, D.; Maffiotte, C.; Baladia, M.; Arias, C.J.

    2015-01-01

    The steam generators of Almaraz Unit 2 were replaced in 1997 by the model 61W/D3 (Siemens) with Alloy 800NG steam generator tubes. Denting indications were firstly detected in 2006 in the SG-3. Crack indications were identified in 2009. At the end of 2011, three tubes were recovered from this steam generator to carry out destructive examination in order to identify the root cause of the tubes degradation. Analysis of deposits point out the existence of multiples elements in the removed OD (Outer Diameter) deposits as well as in the deposits at the free tube under sludge and at the transition zone. Deposits are more abundant at the transition zone than at free tube. About 10% Na concentration has been detected, whereas S and Cl appear in small concentrations. Si appears regularly and Cr, Ni concentrations in the deposits are similar. Multiple intergranular cracks have been detected at 3 mm above the last contact point between the tube and the TS (tube support), in a band of around 5 mm, practically in the whole perimeter of the tube. Fracture surface of crack-B was partially covered by a Si rich layer, whereas fracture surface of crack-A seems to be cleaner. However, no significant differences in composition, except higher amount of S in crack-B, were found in the deposits of both cracks. EDX mapping and Auger profiles point out Ni enrichment with slight Cr enrichment or depletion and Fe depletion. The comparison of Auger profiles with available results for Alloy 800 tested in caustic and acid sulfate environments seems to indicate that the environment inside the cracks detected in the tube R67C48 is neutral or moderately caustic

  2. An evaluation of the statistical variability in thermal expansion properties of steam generator tubesheet (SA-508) and tubing (Alloy-600TT)

    International Nuclear Information System (INIS)

    Riccardella, P.C.; Staples, J.F.; Kandra, J.T.

    2009-01-01

    Inspections of steam generator tubing are performed in U.S. PWRs as part of the Steam Generator Management Program. Westinghouse has recently completed a technical justification demonstrating that in steam generators with thermally treated Ni-Cr Alloy (Alloy 600TT) tubes that are hydraulically expanded into low alloy steel (SA-508) tubesheets, flaws in the region of the tubes below a certain distance from the top of the tubesheet, denoted H * , will not result in reactor coolant pressure boundary breach nor unacceptable primary-to-secondary leakage. This is because, even if a flaw in this region were to result in complete tube sever, if the length of undegraded tube in the tubesheet exceeds H*, neither operating nor accident loadings create sufficient pull-out forces to overcome the frictional forces between the tube and tubesheet. One key component of this technical justification is the differential thermal expansion between the tube and tubesheet, since a significant portion of the pullout strength of the hydraulically expanded tube-to-tubesheet joint is due to mechanical interference resulting from the larger expansion of the tubing relative to the tubesheet at a given temperature. To address this phenomenon, a detailed statistical evaluation of coefficient of thermal expansion (CTE) data for the tubesheet material (SA-508) and the tube material (thermally treated Alloy-600) was performed. Data used in the evaluation included existing test results obtained from a number of sources as well as extensive new laboratory data developed specifically for this purpose. The evaluation resulted in recommended statistical distributions of this property for the two materials including their means and probabilistic variability. In addition, it was determined that the CTE values reported in the ASME Code (Section II) represent reasonably conservative mean values for both the tubesheet and tubing material. (author)

  3. Condensation coefficient of water in a weak condensation state

    International Nuclear Information System (INIS)

    Kobayashi, Kazumichi; Watanabe, Shunsuke; Yamano, Daigo; Yano, Takeru; Fujikawa, Shigeo

    2008-01-01

    The condensation coefficient of water at a vapor-liquid interface is determined by combining shock tube experiments and numerical simulations of the Gaussian-BGK Boltzmann equation. The time evolution in thickness of a liquid film, which is formed on the shock tube endwall behind the shock wave reflected at the endwall, is measured with an optical interferometer consisting of the physical beam and the reference one. The reference beam is utilized to eliminate systematic noises from the physical beam. The growth rate of the film is evaluated from the measured time evolution and it is incorporated into the kinetic boundary condition for the Boltzmann equation. From a numerical simulation using the boundary condition, the condensation coefficient of water is uniquely deduced. The results show that, in a condition of weak condensation near a vapor-liquid equilibrium state, the condensation coefficient of water is almost equal to the evaporation coefficient estimated by molecular dynamics simulations near a vapor-liquid equilibrium state and it decreases as the system becomes a nonequilibrium state. The condensation coefficient of water is nearly identical with that of methanol [Mikami, S., Kobayashi, K., Ota, T., Fujikawa, S., Yano, T., Ichijo, M., 2006. Molecular gas dynamics approaches to interfacial phenomena accompanied with condensation. Exp. Therm. Fluid Sci. 30, 795-800].

  4. Condensation coefficient of water in a weak condensation state

    Science.gov (United States)

    Kobayashi, Kazumichi; Watanabe, Shunsuke; Yamano, Daigo; Yano, Takeru; Fujikawa, Shigeo

    2008-07-01

    The condensation coefficient of water at a vapor-liquid interface is determined by combining shock tube experiments and numerical simulations of the Gaussian-BGK Boltzmann equation. The time evolution in thickness of a liquid film, which is formed on the shock tube endwall behind the shock wave reflected at the endwall, is measured with an optical interferometer consisting of the physical beam and the reference one. The reference beam is utilized to eliminate systematic noises from the physical beam. The growth rate of the film is evaluated from the measured time evolution and it is incorporated into the kinetic boundary condition for the Boltzmann equation. From a numerical simulation using the boundary condition, the condensation coefficient of water is uniquely deduced. The results show that, in a condition of weak condensation near a vapor-liquid equilibrium state, the condensation coefficient of water is almost equal to the evaporation coefficient estimated by molecular dynamics simulations near a vapor-liquid equilibrium state and it decreases as the system becomes a nonequilibrium state. The condensation coefficient of water is nearly identical with that of methanol [Mikami, S., Kobayashi, K., Ota, T., Fujikawa, S., Yano, T., Ichijo, M., 2006. Molecular gas dynamics approaches to interfacial phenomena accompanied with condensation. Exp. Therm. Fluid Sci. 30, 795-800].

  5. Multiaxial ratcheting behavior of zirconium alloy tubes under combined cyclic axial load and internal pressure

    Energy Technology Data Exchange (ETDEWEB)

    Chen, G.; Zhang, X. [School of Chemical Engineering and Technology, Tianjin University, Tianjin 300072 (China); Xu, D.K. [Environmental Corrosion Center, Institute of Metal Research, Chinese Academy of Sciences, Shenyang 110016 (China); Li, D.H. [Hunan Taohuajiang Nuclear Power Co., Ltd, Yiyang, 413000 (China); Chen, X. [School of Chemical Engineering and Technology, Tianjin University, Tianjin 300072 (China); Zhang, Z., E-mail: zhe.zhang@tju.edu.cn [School of Chemical Engineering and Technology, Tianjin University, Tianjin 300072 (China)

    2017-06-15

    In this study, a series of uniaxial and multiaxial ratcheting tests were conducted at room temperature on zirconium alloy tubes. The experimental results showed that for uniaxial symmetrical cyclic test, the axial ratcheting strain ɛ{sub x} did not accumulate obviously in initial stage, but gradually increased up to 1% with increasing stress amplitude σ{sub xa}. For multiaxial ratcheting tests, the zirconium alloy tube was highly sensitive to both the axial stress amplitude σ{sub xa} and the internal pressure p{sub i}. The hoop ratcheting strain ɛ{sub θ} increased continuously with the increase of axial stress amplitude, whereas the evolution of axial ratcheting strain ɛ{sub x} was related to the axial stress amplitude. The internal pressure restricted the ratcheting accumulation in the axial direction, but promoted the hoop ratcheting strain on the contrary. The prior loading history greatly restrained the ratcheting behavior of subsequent cycling with a small internal pressure. - Highlights: •Uniaxial and multiaxial ratcheting behavior of the zirconium alloy tubes are investigated at room temperature. •The ratcheting depends greatly on the stress amplitude or internal pressure. •The interaction between the axial and hoop ratcheting mechanisms is greatly dependent on the internal pressure level. •The ratcheting is influenced significantly by the loading history of internal pressure.

  6. Multiaxial ratcheting behavior of zirconium alloy tubes under combined cyclic axial load and internal pressure

    International Nuclear Information System (INIS)

    Chen, G.; Zhang, X.; Xu, D.K.; Li, D.H.; Chen, X.; Zhang, Z.

    2017-01-01

    In this study, a series of uniaxial and multiaxial ratcheting tests were conducted at room temperature on zirconium alloy tubes. The experimental results showed that for uniaxial symmetrical cyclic test, the axial ratcheting strain ɛ x did not accumulate obviously in initial stage, but gradually increased up to 1% with increasing stress amplitude σ xa . For multiaxial ratcheting tests, the zirconium alloy tube was highly sensitive to both the axial stress amplitude σ xa and the internal pressure p i . The hoop ratcheting strain ɛ θ increased continuously with the increase of axial stress amplitude, whereas the evolution of axial ratcheting strain ɛ x was related to the axial stress amplitude. The internal pressure restricted the ratcheting accumulation in the axial direction, but promoted the hoop ratcheting strain on the contrary. The prior loading history greatly restrained the ratcheting behavior of subsequent cycling with a small internal pressure. - Highlights: •Uniaxial and multiaxial ratcheting behavior of the zirconium alloy tubes are investigated at room temperature. •The ratcheting depends greatly on the stress amplitude or internal pressure. •The interaction between the axial and hoop ratcheting mechanisms is greatly dependent on the internal pressure level. •The ratcheting is influenced significantly by the loading history of internal pressure.

  7. Fabrication of Aluminum Tubes Filled with Aluminum Alloy Foam by Friction Welding

    Directory of Open Access Journals (Sweden)

    Yoshihiko Hangai

    2015-10-01

    Full Text Available Aluminum foam is usually used as the core of composite materials by combining it with dense materials, such as in Al foam core sandwich panels and Al-foam-filled tubes, owing to its low tensile and bending strengths. In this study, all-Al foam-filled tubes consisting of ADC12 Al-Si-Cu die-cast aluminum alloy foam and a dense A1050 commercially pure Al tube with metal bonding were fabricated by friction welding. First, it was found that the ADC12 precursor was firmly bonded throughout the inner wall of the A1050 tube without a gap between the precursor and the tube by friction welding. No deformation of the tube or foaming of the precursor was observed during the friction welding. Next, it was shown that by heat treatment of an ADC12-precursor-bonded A1050 tube, gases generated by the decomposition of the blowing agent expand the softened ADC12 to produce the ADC12 foam interior of the dense A1050 tube. A holding time during the foaming process of approximately tH = 8.5 min with a holding temperature of 948 K was found to be suitable for obtaining a sound ADC12-foam-filled A1050 tube with sufficient foaming, almost uniform pore structures over the entire specimen, and no deformation or reduction in the thickness of the tube.

  8. Hydride-induced degradation of hoop ductility in textured zirconium-alloy tubes: A theoretical analysis

    International Nuclear Information System (INIS)

    Qin, W.; Szpunar, J.A.; Kozinski, J.

    2012-01-01

    Hydride-induced degradation of hoop ductility in Zr-alloy tubular components has been studied for many years because of its importance in the nuclear industry. In this paper the role of intergranular and intragranular δ-hydrides in the degradation of ductility of the textured Zr-alloy tubes is investigated. The correlation among hydride distribution, orientation and morphology in the tubes is formulated based on thermodynamic modeling, and then analyzed. The results show that the applied stress, the crystallographic texture of α-Zr matrix, the grain-boundary structure, and the morphology and size of Zr grains simultaneously govern the site preference and the orientation of hydrides. A criterion is proposed to determine the threshold stress of hydride reorientation. The hoop ductility of the hydrided Zr tubes is discussed using the concept of macroscopic fracture strain. It is shown that the intergranular hydrides may be more deleterious to ductility than the intragranular ones. This work defines a general framework for understanding the relation of the microstructure of hydride-forming materials to embrittlement.

  9. Brazing open cell reticulated copper foam to stainless steel tubing with vacuum furnace brazed gold/indium alloy plating

    Science.gov (United States)

    Howard, Stanley R [Windsor, SC; Korinko, Paul S [Aiken, SC

    2008-05-27

    A method of fabricating a heat exchanger includes brush electroplating plated layers for a brazing alloy onto a stainless steel tube in thin layers, over a nickel strike having a 1.3 .mu.m thickness. The resultant Au-18 In composition may be applied as a first layer of indium, 1.47 .mu.m thick, and a second layer of gold, 2.54 .mu.m thick. The order of plating helps control brazing erosion. Excessive amounts of brazing material are avoided by controlling the electroplating process. The reticulated copper foam rings are interference fit to the stainless steel tube, and in contact with the plated layers. The copper foam rings, the plated layers for brazing alloy, and the stainless steel tube are heated and cooled in a vacuum furnace at controlled rates, forming a bond of the copper foam rings to the stainless steel tube that improves heat transfer between the tube and the copper foam.

  10. Thermal creep properties of alloy D9 stainless steel and 316 stainless steel fuel clad tubes

    International Nuclear Information System (INIS)

    Latha, S.; Mathew, M.D.; Parameswaran, P.; Bhanu Sankara Rao, K.; Mannan, S.L.

    2008-01-01

    Uniaxial thermal creep rupture properties of 20% cold worked alloy D9 stainless steel (alloy D9 SS) fuel clad tubes for fast breeder reactors have been evaluated at 973 K in the stress range 125-250 MPa. The rupture lives were in the range 90-8100 h. The results are compared with the properties of 20% cold worked type 316 stainless steel (316 SS) clad tubes. Alloy D9 SS were found to have higher creep rupture strengths, lower creep rates and lower rupture ductility than 316 SS. The deformation and damage processes were related through Monkman Grant relationship and modified Monkman Grant relationship. The creep damage tolerance parameter indicates that creep fracture takes place by intergranular cavitation. Precipitation of titanium carbides in the matrix and chromium carbides on the grain boundaries, dislocation substructure and twins were observed in transmission electron microscopic investigations of alloy D9 SS. The improvement in strength is attributed to the precipitation of fine titanium carbides in the matrix which prevents the recovery and recrystallisation of the cold worked microstructure

  11. Average Natural Convective Heat Transfer of Air-cooled Condensing Heat Exchanger of Emergency Cooldown Tank - Effect of Tube Banks

    International Nuclear Information System (INIS)

    Huh, Seon Jeong; Lee, Hee Joon; Kim, Myoung Jun; Moon, Joo Hyung; Bae, Youngmin; Kim, Young-In

    2016-01-01

    Recently emergency cooldown tank(ECT) is a great concern of passive cooling system for the safety of nuclear reactor. After the operation of a conventional passive cooling system for an extended period, however, the water level falls as a result of the evaporation from the ECT, as steam is emitted from the open top of the tank. In this study, the effect of heat transfer area at the air cooled condensing heat exchanger was investigated by changing 5×5 tube banks into 4×4 and 3×3. Moreover, each of air-side natural convective heat transfer coefficient of tube banks was compared to existing correlations. This study presents the effect of heat transfer area at air-cooled condensing heat exchanger. As heat transfer area decreased, the temperature of outlet increased. In other words, the cooling performance got lower with the decrease of heat transfer area. In addition, the average natural convective heat transfer coefficient was 15.3 W/m"2/K from the 4×4 tube banks, and 4.92 W/m"2/K from the 3×3 tube banks, which had quite a large error more than 46% especially with the value of 4×4 tube banks compared to the value from correlation equation. Therefore, according to this result, it is needed to measure the local heat transfer coefficient of vertical cylinder more elaborately in further study

  12. Average Natural Convective Heat Transfer of Air-cooled Condensing Heat Exchanger of Emergency Cooldown Tank - Effect of Tube Banks

    Energy Technology Data Exchange (ETDEWEB)

    Huh, Seon Jeong; Lee, Hee Joon [Kookmin University, Seoul (Korea, Republic of); Kim, Myoung Jun; Moon, Joo Hyung; Bae, Youngmin; Kim, Young-In [Korea Atomic Energy Research Institute, Daejeon (Korea, Republic of)

    2016-10-15

    Recently emergency cooldown tank(ECT) is a great concern of passive cooling system for the safety of nuclear reactor. After the operation of a conventional passive cooling system for an extended period, however, the water level falls as a result of the evaporation from the ECT, as steam is emitted from the open top of the tank. In this study, the effect of heat transfer area at the air cooled condensing heat exchanger was investigated by changing 5×5 tube banks into 4×4 and 3×3. Moreover, each of air-side natural convective heat transfer coefficient of tube banks was compared to existing correlations. This study presents the effect of heat transfer area at air-cooled condensing heat exchanger. As heat transfer area decreased, the temperature of outlet increased. In other words, the cooling performance got lower with the decrease of heat transfer area. In addition, the average natural convective heat transfer coefficient was 15.3 W/m{sup 2}/K from the 4×4 tube banks, and 4.92 W/m{sup 2}/K from the 3×3 tube banks, which had quite a large error more than 46% especially with the value of 4×4 tube banks compared to the value from correlation equation. Therefore, according to this result, it is needed to measure the local heat transfer coefficient of vertical cylinder more elaborately in further study.

  13. Development of high performance condensers for thermal and nuclear power plants

    International Nuclear Information System (INIS)

    Okouchi, Isao; Takahashi, Sankichi; Tomita, Akira.

    1980-01-01

    As the trend toward the large capacity of thermal and nuclear power plants advances, condensers also become large, and from the viewpoint of energy saving in whole plants, the maintenance of high performance and reliability is strongly desired. Hitachi Ltd. responded to this demand, and repeated the basic investigation with a model condenser on the selection of condenser cooling tubes and their arrangement. As the result, balanced downflow type tube arrangement was developed, which enables smooth steam flow and the improvement of condenser performance by forming the intense flow of turbine exhaust from the upper part of tube nest downward and making the steam flow in the lower part of tube nest into radial form toward air ejecting port. This tube arrangement has been applied to actual machines, and the excellent results have been obtained. In particular, the improvement of the degree of vacuum due to the reduction of steam flow loss is advantageous for increasing the power output of turbines. Thereupon, based on the basic experiment with various models of tube arrangement and the consideration on the operational results of actual machines using this tube arrangement, the features of this technique are reported. The basic construction of tube arrangement, the steam flow in tube nest, the vacuum in condensers, the supercooling of condensate, and actual balanced downflow type condensers are described. (Kako, I.)

  14. Study on Hydroforming of Magnesium Alloy Tube under Temperature Condition

    Science.gov (United States)

    Wang, Xinsong; Wang, Shouren; Zhang, Yongliang; Wang, Gaoqi; Guo, Peiquan; Qiao, Yang

    2018-01-01

    First of all, under 100 °C, 150 °C, 200 °C, 250 °C, 300 °C and 350 °C, respectively do the test of magnesium alloy AZ31B temperature tensile and the fracture of SEM electron microscopic scanning, studying the plastic forming ability under six different temperature. Secondly, observe and study the real stress-strain curves and fracture topography. Through observation and research can concluded that with the increase of temperature, the yield strength and tensile strength of AZ31B was increased, and the elongation rate and the plastic deformation capacity are increased obviously. Taking into account the actual production, energy consumption, and mold temperature resistance, 250 °Cwas the best molding temperature. Finally, under the temperature condition of 250 °C, the finite element simulation and simulation of magnesium alloy profiled tube were carried out by Dynaform, and the special wall and forming limit diagram of magnesium alloy were obtained. According to the forming wall thickness and forming limit diagram, the molding experiment can be optimized continuously.

  15. Modeling of Kerena Emergency Condenser

    Science.gov (United States)

    Bryk, Rafał; Schmidt, Holger; Mull, Thomas; Wagner, Thomas; Ganzmann, Ingo; Herbst, Oliver

    2017-12-01

    KERENA is an innovative boiling water reactor concept equipped with several passive safety systems. For the experimental verification of performance of the systems and for codes validation, the Integral Test Stand Karlstein (INKA) was built in Karlstein, Germany. The emergency condenser (EC) system transfers heat from the reactor pressure vessel (RPV) to the core flooding pool in case of water level decrease in the RPV. EC is composed of a large number of slightly inclined tubes. During accident conditions, steam enters into the tubes and condenses due to the contact of the tubes with cold water at the secondary side. The condensed water flows then back to the RPV due to gravity. In this paper two approaches for modeling of condensation in slightly inclined tubes are compared and verified against experiments. The first approach is based on the flow regime map. Depending on the regime, heat transfer coefficient is calculated according to specific semi-empirical correlation. The second approach uses a general, fully-empirical correlation. The models are developed with utilization of the object-oriented Modelica language and the open-source OpenModelica environment. The results are compared with data obtained during a large scale integral test, simulating loss of coolant accident performed at Integral Test Stand Karlstein (INKA). The comparison shows a good agreement.Due to the modularity of models, both of them may be used in the future in systems incorporating condensation in horizontal or slightly inclined tubes. Depending on his preferences, the modeller may choose one-equation based approach or more sophisticated model composed of several exchangeable semi-empirical correlations.

  16. Condensation of refrigerant CFC 11 in horizontal microfin tubes. Proposal of a correlation equation for frictional pressure gradient; Reibai CFC11 no microfin tsuki suihei kannai gyoshuku. Atsuryoku koka no jikkenshiki no teian

    Energy Technology Data Exchange (ETDEWEB)

    Nozu, S [Univ. of Okayama Prefecture, Okayama (Japan); Katayama, H [Mitsubishi Chemical Co., Inc., Tokyo (Japan); Nakata, H [Daikin Industries, Ltd., Osaka (Japan); Honda, H [Kyushu University, Fukuoka (Japan). Institute of Advanced Material Study

    1996-09-25

    Local heat transfer and pressure drop measurements were made during condensation of CFC 11 in microfin tubes. A smooth tube and two microfin tubes with different fin dimensions were used. Flow observation study with use of an industrial bore-scope revealed that the condensate swirled along the grooves, and a thick condensate film covered fins in the lower part of the tube in the low quality region. Static pressure gradients in the microfin tubes were up to 70 percent larger than that in a smooth tube. A correlation equation for the local frictional pressure gradient was derived, in which the effect of refrigerant mass velocity was introduced on the basis of the flow regime consideration. The measured frictional pressure gradient data were found by the present method to have a mean absolute deviation of 8.3 percent. 24 refs., 11 figs., 3 tabs.

  17. Evaluation of High Temperature Corrosion Resistance of Finned Tubes Made of Austenitic Steel And Nickel Alloys

    Directory of Open Access Journals (Sweden)

    Turowska A.

    2016-06-01

    Full Text Available The purpose of the paper was to evaluate the resistance to high temperature corrosion of laser welded joints of finned tubes made of austenitic steel (304,304H and nickel alloys (Inconel 600, Inconel 625. The scope of the paper covered the performance of corrosion resistance tests in the atmosphere of simulated exhaust gases of the following chemical composition: 0.2% HCl, 0.08% SO2, 9.0% O2 and N2 in the temperature of 800°C for 1000 hours. One found out that both tubes made of austenitic steel and those made of nickel alloy displayed good resistance to corrosion and could be applied in the energy industry.

  18. Time-dependent leak behavior of flawed Alloy 600 tube specimens at constant pressure

    Energy Technology Data Exchange (ETDEWEB)

    Bahn, Chi Bum, E-mail: bahn@anl.gov [Argonne National Laboratory, Argonne, IL 60439 (United States); Majumdar, Saurin [Argonne National Laboratory, Argonne, IL 60439 (United States); Harris, Charles [United States Nuclear Regulatory Commission, Rockville, MD 20852 (United States)

    2011-10-15

    Leak rate testing has been performed using Alloy 600 tube specimens with throughwall flaws. Some specimens have shown time-dependent leak behavior at constant pressure conditions. Fractographic characterization was performed to identify the time-dependent crack growth mechanism. The fracture surface of the specimens showed the typical features of ductile fracture, as well as the distinct crystallographic facets, typical of fatigue crack growth at low {Delta}K level. Structural vibration appears to have been caused by the oscillation of pressure, induced by a high-pressure pump used in a test facility, and by the water jet/tube structure interaction. Analyses of the leak behaviors and crack growth indicated that both the high-pressure pump and the water jet could significantly contribute to fatigue crack growth. To determine whether the fatigue crack growth during the leak testing can occur solely by the water jet effect, leak rate tests at constant pressure without the high-pressure pump need to be performed. - Highlights: > Leak rate of flawed Alloy 600 tubing increased at constant pressure condition. > Fractography revealed two cases: ductile tearing and crystallographic facets. > Crystallographic facets are typical features of fatigue crack growth at low {Delta}K. > Fatigue source could be water jet-induced vibration and/or high-pressure pump pulsation.

  19. Proving the viability of manufacturing of multi-layer steel/vanadium alloy/steel composite tubes by numerical simulations and experiment

    Science.gov (United States)

    Nechaykina, T.; Nikulin, S.; Rozhnov, A.; Molotnikov, A.; Zavodchikov, S.; Estrin, Y.

    2018-05-01

    Vanadium alloys are promising structural materials for fuel cladding tubes for fast-neutron reactors. However, high solubility of oxygen and nitrogen in vanadium alloys at operating temperatures of 700 °C limits their application. In this work, we present a novel composite structure consisting of vanadium alloy V-4Ti-4Cr (provides high long-term strength of the material) and stainless steel Fe-0.2C-13Cr (as a corrosion resistant protective layer). It is produced by co-extrusion of these materials forming a three-layered tube. Finite element simulations were utilised to explore the influence of the various co-extrusion parameters on manufacturability of multi-layered tubes. Experimental verification of the numerical modelling was performed using co-extrusion with the process parameters suggested by the numerical simulations. Scanning electron microscopy and microhardness measurements revealed a defect-free diffusion layer at the interfaces between both materials indicating a good quality bonding for these co-extrusion conditions.

  20. Flow condensation heat transfer coefficients of R22, R134a, R407C, and R410A inside plain and microfin tubes

    Energy Technology Data Exchange (ETDEWEB)

    Jung, Dongsoo; Cho, Youngmok; Park, Kiho [Inha Univ., Incheon (Korea). Dept. of Mechanical Engineering

    2004-01-01

    Flow condensation heat transfer coefficients (HTCs) of R22, R134a, R407C, and R410A inside horizontal plain and microfin tubes of 9.52 mm outside diameter and 1 m length were measured at the condensation temperature of 40{sup o}C with mass fluxes of 100, 200, and 300 kg m{sup -2} s{sup -1} and a heat flux of 7.7-7.9 kW m{sup -2}. For a plain tube, HTCs of R134a and R410A were similar to those of R22 while HTCs of R407C are 11-15% lower than those of R22. For a microfin tube, HTCs of R134a were similar to those of R22 while HTCs of R407C and R410A were 23-53% and 10-21% lower than those of R22. For a plain tube, our correlation agreed well with the present data for all refrigerants exhibiting a mean deviation of 11.6%. Finally, HTCs of a microfin tube were 2-3 times higher than those of a plain tube and the heat transfer enhancement factor decreased as the mass flux increased for all refrigerants tested. (Author)

  1. Performance of casting aluminum-silicon alloy condensing heating exchanger for gas-fired boiler

    Science.gov (United States)

    Cao, Weixue; Liu, Fengguo; You, Xue-yi

    2018-01-01

    Condensing gas boilers are widely used due to their high heat efficiency, which comes from their ability to use the recoverable sensible heat and latent heat in flue gas. The condensed water of the boiler exhaust has strong corrosion effect on the heat exchanger, which restricts the further application of the condensing gas boiler. In recent years, a casting aluminum-silicon alloy (CASA), which boasts good anti-corrosion properties, has been introduced to condensing hot water boilers. In this paper, the heat transfer performance, CO and NOx emission concentrations and CASA corrosion resistance of a heat exchanger are studied by an efficiency bench test of the gas-fired boiler. The experimental results are compared with heat exchangers produced by Honeywell and Beka. The results show that the excess air coefficient has a significant effect on the heat efficiency and CO and NOx emission of the CASA water heater. When the excess air coefficient of the CASA gas boiler is 1.3, the CO and NOx emission concentration of the flue gas satisfies the design requirements, and the heat efficiency of water heater is 90.8%. In addition, with the increase of heat load rate, the heat transfer coefficient of the heat exchanger and the heat efficiency of the water heater are increased. However, when the heat load rate is at 90%, the NOx emission in the exhaust gas is the highest. Furthermore, when the temperature of flue gas is below 57 °C, the condensation of water vapor occurs, and the pH of condensed water is in the 2.5 5.5 range. The study shows that CASA water heater has good corrosion resistance and a high heat efficiency of 88%. Compared with the heat exchangers produced by Honeywell and Beka, there is still much work to do in optimizing and improving the water heater.

  2. Modeling of Kerena Emergency Condenser

    Directory of Open Access Journals (Sweden)

    Bryk Rafał

    2017-12-01

    Full Text Available KERENA is an innovative boiling water reactor concept equipped with several passive safety systems. For the experimental verification of performance of the systems and for codes validation, the Integral Test Stand Karlstein (INKA was built in Karlstein, Germany. The emergency condenser (EC system transfers heat from the reactor pressure vessel (RPV to the core flooding pool in case of water level decrease in the RPV. EC is composed of a large number of slightly inclined tubes. During accident conditions, steam enters into the tubes and condenses due to the contact of the tubes with cold water at the secondary side. The condensed water flows then back to the RPV due to gravity. In this paper two approaches for modeling of condensation in slightly inclined tubes are compared and verified against experiments. The first approach is based on the flow regime map. Depending on the regime, heat transfer coefficient is calculated according to specific semi-empirical correlation. The second approach uses a general, fully-empirical correlation. The models are developed with utilization of the object-oriented Modelica language and the open-source OpenModelica environment. The results are compared with data obtained during a large scale integral test, simulating loss of coolant accident performed at Integral Test Stand Karlstein (INKA. The comparison shows a good agreement.Due to the modularity of models, both of them may be used in the future in systems incorporating condensation in horizontal or slightly inclined tubes. Depending on his preferences, the modeller may choose one-equation based approach or more sophisticated model composed of several exchangeable semi-empirical correlations.

  3. Improvement of reliability of heater and condenser

    International Nuclear Information System (INIS)

    Yamagishi, Hiroki

    1988-01-01

    Recently, the diversification of the operation modes of power plants has advanced as well as daily start and stop and weekly start and stop operations, as the result, the needs for the reliability improvement of various heat exchangers around steam turbines heighten. In newly constructed plants, the design to meet this demand is carried out, but also in existing platns, the application of the latest technology is investigated. As for the reliability of condensers, aluminum brass cooling tubes have been used by doing the optimal maintenance and taking the measures against deposit attack. In the case of requiring high reliability, the examples of adopting titanium cooling tubes increased. The technology of titanium tube condensers, completely assembled condensers, the replacement of existing brass tubes with titanium tubes and so on are discussed. In the case of feed heaters, the deterioration phenomena due to the lapse of long years, such as the attack of steel tube inlet, the drain attack on the external surfaces of steel tubes, the ammonia attack of aluminum brass tubes and the adhesion of scale to heaters, are explained, and the countermeasures are shown. (Kako, I.)

  4. Prevention of condenser tubes corroson from polluted sea wtaer at Saijo thermal power station. Saijo hatsudensho ni okeru fukusuiki kan no boshoku taisaku

    Energy Technology Data Exchange (ETDEWEB)

    Okada, T.; Sato, N.; Ito, M. (Shikoku Electric Power Co. Inc., Kagawa (Japan))

    1991-03-15

    After the oil shock, Saijou thermal power station converted its energy source into coal to diversify the power source. With rising operation rate at the plant after fuel conversion, leaky condenser tubes have increased. Such leakage concentrated especially in new 70/30 cupro-nickel tubes equipped in air cooling zones of the condenser. This report investigates the cause of this leakage and describes the study results on the corrosion prevention. Consequently, following two measures were taken: a measure to prevent local erosion of aluminum brass pipes by means of preventing inflow of foreign materials such as seashells; a measure to prevent corrosion of 70/30 cupro-nickel sulfide by strengthening the injection of ferrous sulfate and by test loading of coated tubes. As a result, no sea water was leaked. Moreover, it was found through the eddy current examination that sulfide corrosion of the new 70/30 cupro-nickel tubes was reduced by iron coat and the rate of losing its thickness decreased remarkably. 1 ref., 15 figs., 5 tabs.

  5. A comparison of R-22, R-134a, R-410a, and R-407c condensation performance in smooth and enhanced tubes: Part 1, Heat transfer

    Energy Technology Data Exchange (ETDEWEB)

    Eckels, S J; Tesene, B A

    1999-07-01

    Local and average heat transfer coefficients during condensation are reported for R-22, R-134a, R-410a, and R-407c in one smooth tube and three enhanced surface tubes. The test tubes included a 3/8 inch outer diameter smooth tube, a 3/8 inch outer diameter microfin tube, a 5/16 inch outer diameter microfin tube, and a 5/8 inch outer diameter microfin tube. The local and average heat transfer coefficients were measured over a mass flux range of 92,100 lb/ft{sup 2}{center_dot}h to 442,200 lb/ft{sup 2}{center_dot}h and at saturation temperatures of 104 F and 122 F. A comparison of the performance of the different refrigerants reveals that R-134a has the highest heat transfer performance followed by R-22 and R-410a, which have similar performances. In general, R-407c had the lowest performance of the refrigerants tested. The microfin tube more than doubles the heat transfer coefficient compared to the smooth tube for all refrigerants at the low mass fluxes, but only increases the heat transfer coefficients by 50% at the highest mass flux tested. The measured heat transfer coefficients are also compared with a number of correlations for condensation.

  6. Experimental studies on condensation of steam mixed with noncondensable gas inside the vertical tube in a pool filled with subcooled water

    International Nuclear Information System (INIS)

    Maheshwari, N.K.; Saha, D.; Sinha, R.K.; Aritomi, M.

    2003-01-01

    A passive containment cooling system with immersed condensers has been proposed as one of the alternatives for the advanced heavy water reactor (AHWR) being designed in India. The system removes residual/decay heat released into the containment through the immersed condensers kept in a pool of water following loss of coolant accident. An important aspect of the immersed condensers is the potential degradation of its performance due to the presence of noncondensable gases. Experiments are performed to obtain reliable data on condensation phenomena in presence of air. These experiments are conducted on full-scale tubes of condensers immersed in a pool of water maintaining similar conditions as in the prototype of AHWR. A method has been proposed for the determination of the local heat transfer rate using correlations given in literature. The parametric effects of air mass fraction, pressure, steam flow, etc. on condensation heat transfer in presence of noncondensable gas have been studied. The experimental results are compared with the correlations given in literature. (orig.)

  7. Crack growth of throughwall flaw in Alloy 600 tube during leak testing

    International Nuclear Information System (INIS)

    Bahn, Chi Bum; Majumdar, Saurin

    2015-01-01

    Graphical abstract: - Highlights: • A series of leak testing was conducted at a constant pressure and room temperature. • The time-dependent increase in the leak rate was observed. • The fractography revealed slip offsets and crystallographic facets. • Time-dependent plasticity at the crack tip caused the slip offsets. • Fatigue by jet/structure interaction caused the crystallographic facets. - Abstract: We examined the issue of whether crack growth in a full thickness material can occur in a leaking crack. A series of leak tests was conducted at a room temperature and constant pressure (17.3 MPa) with Alloy 600 tube specimens containing a tight rectangular throughwall axial fatigue crack. To exclude a potential pulsation effect by a high pressure pump, the test water was pressurized by using high pressure nitrogen gas. Fractography showed that crack growth in the full thickness material can occur in the leaking crack by two mechanisms: time-dependent plasticity at the crack tip and fatigue induced by jet/structure interaction. The threshold leak rate at which the jet/structure interaction was triggered was between 1.3 and 3.3 L/min for the specific heat of the Alloy 600 tube tested

  8. Fuel assembly and fuel cladding tube

    International Nuclear Information System (INIS)

    Tsutsumi, Shinro; Ito, Ken-ichi; Inagaki, Masatoshi; Nakajima, Junjiro.

    1996-01-01

    A fuel cladding tube is a zirconium liner tube formed by lining a pure zirconium layer on the inner side of a zirconium alloy tube. The fuel cladding tube is formed by extrusion molding of a composite billet formed by inserting a pure zirconium billet into a zirconium alloy billet. Accordingly, the pure zirconium layer and the zirconium alloy tube are strongly joined by metal bond. The fuel cladding tube has an external oxide film on the outer surface of the zirconium alloy tube and an internal oxide film on the inner side of the pure zirconium layer. The external oxide film has a thickness preferably of about 1μm. The internal oxide film has a thickness of not more than 10μm, preferably, from 1 to 5μm. With such a constitution, flaws to be formed on both inner and outer surfaces of the cladding tube upon assembling a fuel assembly can be reduced thereby enabling to reduce the amount of hydrogen absorbed to the cladding tube. (I.N.)

  9. The Study of Heat Treatment Effects on Chromium Carbide Precipitation of 35Cr-45Ni-Nb Alloy for Repairing Furnace Tubes

    Directory of Open Access Journals (Sweden)

    Nakarin Srisuwan

    2016-01-01

    Full Text Available This paper presents a specific kind of failure in ethylene pyrolysis furnace tubes. It considers the case in which the tubes made of 35Cr-45Ni-Nb high temperature alloy failed to carburization, causing creep damage. The investigation found that used tubes became difficult to weld repair due to internal carburized layers of the tube. The microstructure and geochemical component of crystallized carbide at grain boundary of tube specimens were characterized by X-ray diffractometer (XRD, scanning electron microscopy (SEM with back-scattered electrons mode (BSE, and energy dispersive X-ray spectroscopy (EDS. Micro-hardness tests was performed to determine the hardness of the matrix and the compounds of new and used tube material. The testing result indicated that used tubes exhibited a higher hardness and higher degree of carburization compared to those of new tubes. The microstructure of used tubes also revealed coarse chromium carbide precipitation and a continuous carbide lattice at austenite grain boundaries. However, thermal heat treatment applied for developing tube weld repair could result in dissolving or breaking up chromium carbide with a decrease in hardness value. This procedure is recommended to improve the weldability of the 35Cr-45Ni-Nb used tubes alloy.

  10. The research activities on in-tube condensation in the presence of noncondensables for passive cooling applications

    Energy Technology Data Exchange (ETDEWEB)

    Tanrikut, A [Turkish Atomic Energy Authority, Ankara (Turkey)

    1996-12-01

    The introduction of nuclear power becomes an attractive solution to the problem of increasing demand for electricity power capacity in Turkey. Thus, Turkey is willing to follow the technological development trends in advanced reactor systems and to participate in joint research studies. The primary objectives of the passive design features are to simplify the design, which assures the minimized demand on operator, and to improve plant safety. To accomplish these features the operating principles of passive safety systems should be well understood by an experimental validation program. Such a validation program is also important for the assessment of advanced computer codes which are currently used for design and licensing procedures. The condensation mode of heat transfer plays an important role for the passive heat removal applications in the current nuclear power plants (e.g. decay heat removal via steam generators in case of loss of heat removal system) and advanced water-cooled reactor systems. But is well established that the presence of noncondensable gases can greatly inhibit the condensation process due to the build-up of noncondensable gas concentration at the liquid/gas interface. The isolation condenser of passive containment cooling system of the simplified boiling water reactors is a typical application area of in-tube condensation in the presence of noncondensable. This paper describes the research activities at the Turkish Atomic Energy Authority concerning condensation in the presence of air, as a noncondensable gas. (author). 9 refs, 6 figs.

  11. The research activities on in-tube condensation in the presence of noncondensables for passive cooling applications

    International Nuclear Information System (INIS)

    Tanrikut, A.

    1996-01-01

    The introduction of nuclear power becomes an attractive solution to the problem of increasing demand for electricity power capacity in Turkey. Thus, Turkey is willing to follow the technological development trends in advanced reactor systems and to participate in joint research studies. The primary objectives of the passive design features are to simplify the design, which assures the minimized demand on operator, and to improve plant safety. To accomplish these features the operating principles of passive safety systems should be well understood by an experimental validation program. Such a validation program is also important for the assessment of advanced computer codes which are currently used for design and licensing procedures. The condensation mode of heat transfer plays an important role for the passive heat removal applications in the current nuclear power plants (e.g. decay heat removal via steam generators in case of loss of heat removal system) and advanced water-cooled reactor systems. But is well established that the presence of noncondensable gases can greatly inhibit the condensation process due to the build-up of noncondensable gas concentration at the liquid/gas interface. The isolation condenser of passive containment cooling system of the simplified boiling water reactors is a typical application area of in-tube condensation in the presence of noncondensable. This paper describes the research activities at the Turkish Atomic Energy Authority concerning condensation in the presence of air, as a noncondensable gas. (author). 9 refs, 6 figs

  12. The elastic properties of zirconium alloy fuel cladding and pressure tubing materials

    International Nuclear Information System (INIS)

    Rosinger, H.E.; Northwood, D.O.

    1979-01-01

    A knowledge of the elastic properties of zirconium alloys is required in the mathematical modelling of cladding and pressure tubing performance. Until recently, little of this type of data was available, particularly at elevated temperatures. The dynamic elastic moduli of zircaloy-2, zircaloy-4, the alloys Zr-1.0 wt%Nb, Zr-2.5 wt%Nb and Marz grade zirconium have therefore been determined over the temperature range 275 to 1000 K. Young's modulus and shear modulus for all the zirconium alloys decrease with temperature and are expressed by empirical relations fitted to the data. The elastic properties are texture dependent and a detailed study has been conducted on the effect of texture on the elastic properties of Zr-1.0 wt% Nb over the temperature range 275 to 775 K. The results are compared with polycrystalline elastic constants computed from single crystal elastic constants, and the effect of texture on the dynamic elastic moduli is discussed in detail. (Auth.)

  13. Analysis of aldehydes in human exhaled breath condensates by in-tube SPME-HPLC.

    Science.gov (United States)

    Wang, ShuLing; Hu, Sheng; Xu, Hui

    2015-11-05

    In this paper, polypyrrole/graphene (PPy/G) composite coating was prepared by a facile electrochemical polymerization strategy on the inner surface of a stainless steel (SS) tube. Based on the coating tube, a novel online in-tube solid-phase microextraction -high performance liquid chromatography (IT-SPME-HPLC) was developed and applied for the extraction of aldehydes in the human exhaled breath condensates (EBC). The hybrid PPy/G nanocomposite exhibits remarkable chemical and mechanical stability, high selectivity, and satisfactory extraction performance toward aldehyde compounds. Moreover, the proposed online IT-SPME-HPLC method possesses numerous superiorities, such as time and cost saving, process simplicity, high precision and sensitivity. Some parameters related to extraction efficiency were optimized systematically. Under the optimal conditions, the recoveries of the aldehyde compounds at three spiked concentration levels varied in the range of 85%-117%. Good linearity was obtained with excellent correlation coefficients (R(2)) being larger than 0.994. The relative standard deviations (n = 5) of the method ranged from 1.8% to 11.3% and the limits of detection were between 2.3 and 3.3 nmol L(-1). The successful application of the proposed method in human EBC indicated that it is a promising approach for the determination of trace aldehyde metabolites in complex EBC samples. Copyright © 2015 Elsevier B.V. All rights reserved.

  14. Analysis of the characteristics of heat transfer enhancement in steam condensers

    International Nuclear Information System (INIS)

    Yan Changqi; Sun Zhongning

    2001-01-01

    The influence of main factors on overall heat transfer was analyzed, and the effects of fouling factors on heat transfer characteristics in steam condenser were clarified. It was proposed that the tube outside enhancement is the most important attribute, when outside heat transfer coefficient increased there will be a big increase in condenser efficiency. The characteristics of heat transfer enhancement by spirally indented tube were investigated. It was proposed that condenser heat transfer efficiency will be raised when the low fin tube or the spirally indented tube with special treated surface were used

  15. Influence of the S/N ratio on the corrosion release of Alloy 690 tubes in a primary coolant

    International Nuclear Information System (INIS)

    Shim, Hee-Sang; Choi, Myung Sik; Kim, Kyung Mo; Seo, Myung Ji; Hur, Do Haeng; Choi, Tack-Sang; Yoo, One

    2014-01-01

    Alloy 690TT is a promising steam generator (SG) tube material of a pressurized water reactor due to its excellent resistance to stress corrosion cracking (SCC) that has caused problems in Alloy 600 as an old SG tube material. The qualities of this material have been managed thoroughly from manufacturing step under various specification regulations as well as in in-service step. For examples, the surface roughness are prescribed as the values less than 1.6 μm for the tube outside and 0.5 μm for the inside, respectively. In addition, the surface state and defect must be qualified through the eddy current test (ECT) and the ultrasonic test (UT) according to the ASME Section III, NB2550. Then, the signal-to-noise (S/N) ratio, which is measured using ECT bobbin probe, is the important criteria to determine the material and it shall be 15 to 1 or higher at the standard frequency for any fixed 0.5 m length of any tube. The corrosion behaviours of the Alloy 690TT under high-temperature pressurized primary water have been studied widely in a point of the SCC but discussed narrowly in a point of the corrosion release. In particular, the effect of the S/N ratio on the corrosion release of this material surface has been rarely investigated. In this work, we evaluate the influence of the S/N ratio on the corrosion release of Alloy 690 SG tubes. The specimens with different S/N ratio were selected through ECT bobbin inspection and a corrosion release test was conducted using a simulated primary circulation loop. The material properties and oxidation behaviours were investigated by surface profiler, scanning electron microscopy, transmission electron microscopy, grazing incidence X-ray diffraction and etc. As a result, the corrosion rate was matched preferably with the MRPC characteristics showing macroscopic surface state rather than with the bobbin S/N ratio results. (author)

  16. Air source heat pump water heater: Dynamic modeling, optimal energy management and mini-tubes condensers

    International Nuclear Information System (INIS)

    Ibrahim, Oussama; Fardoun, Farouk; Younes, Rafic; Louahlia-Gualous, Hasna

    2014-01-01

    This paper presents a dynamic simulation model to predict the performance of an ASHPWH (air source heat pump water heater). The developed model is used to assess its performance in the Lebanese context. It is shown that for the four Lebanese climatic zones, the expected monthly values of the average COP (coefficient of performance) varies from 2.9 to 5, leading to high efficiencies compared with conventional electric water heaters. The energy savings and GHG (greenhouse gas) emissions reduction are investigated for each zone. Furthermore, it is recommended to use the ASHPWH during the period of highest daily ambient temperatures (noon or afternoon), assuming that the electricity tariff and hot water loads are constant. In addition, an optimal management model for the ASHPWH is developed and applied for a typical winter day of Beirut. Moreover, the developed dynamic model of ASHPWH is used to compare the performance of three similar systems that differ only with the condenser geometry, where results show that using mini-condenser geometries increase the COP (coefficient of performance) and consequently, more energy is saved as well as more GHG emissions are reduced. In addition, the condenser “surface compactness” is increased giving rise to an efficient compact heat exchanger. - Highlights: • Numerical modeling and experimental validation for ASHPWH (air source heat pump water heater). • Optimization of the ASHPWH-condenser length. • Comparison of the ASHPWH with conventional electric water heater according to energy efficiency and green gas house emissions. • Development of an energetic-economic optimal management model for ASHPWH. • Energetic and environmental assessment of ASHPWH with mini-tubes condensers

  17. Ion-induced swelling of ODS ferritic alloy MA957 tubing to 500 dpa

    Energy Technology Data Exchange (ETDEWEB)

    Toloczko, M.B., E-mail: mychailo.toloczko@pnnl.gov [Pacific Northwest National Laboratory, Richland, WA 99354 (United States); Garner, F.A. [Radiation Effects Consulting, Richland, WA 99354 (United States); Voyevodin, V.N.; Bryk, V.V.; Borodin, O.V.; Mel’nychenko, V.V.; Kalchenko, A.S. [Kharkov Institute of Physics and Technology, Kharkov (Ukraine)

    2014-10-15

    In order to study the potential swelling behavior of the ODS ferritic alloy MA957 at very high dpa levels, specimens were prepared from pressurized tubes that were unirradiated archives of tubes previously irradiated in FFTF to doses as high as 110 dpa. These unirradiated specimens were irradiated with 1.8 MeV Cr{sup +} ions to doses ranging from 100 to 500 dpa and examined by transmission electron microscopy. No co-injection of helium or hydrogen was employed. It was shown that compared to several tempered ferritic/martensitic steels irradiated in the same facility, these tubes were rather resistant to void swelling, reaching a maximum value of only 4.5% at 500 dpa and 450 °C. In this fine-grained material, the distribution of swelling was strongly influenced by the presence of void denuded zones along the grain boundaries.

  18. Superelastic NiTi memory alloy micro-tube under tension - nucleation and propagation of martensite band

    International Nuclear Information System (INIS)

    Li, Z.Q.; Sun, Q.P.

    2000-01-01

    The superelastic behavior of polycrystalline NiTi shape memory alloy micro-tube under tension is studied experimentally. The nominal stress-strain curve of the micro-tube is recorded. By using a special surface coating it is found that the deformation of the tube is via the nucleation and propagation of stress-induced martensite band. The experiments show that the martensite nucleates in the form of a spiral lens-shaped narrow band that is inclined at 61 to the axis of loading when the stress reaches the peak of stress-strain curve. The width and the length of the band grew gradually with increase of loading and finally joined and merged into a single band. The subsequent deformation of the tube is realized by the propagation of this cylindrical martensite band. (orig.)

  19. Microstructure control of Zr-Nb-Sn alloy with Mo addition for HWR pressure tube application

    International Nuclear Information System (INIS)

    Hwang, S. K.; Kim, M. H.; Kim, J. H.; Kwon, S. I.; Kim, Y. S.

    1997-01-01

    As a basic research to develop the material for heavy water reactor pressure tube application the effect of Mo addition to Zr-Nb-Sn alloy was studied for the purpose of minimizing the amount of cold working while maintaining a high strength. To select the target alloy system we first designed various alloy compositions and chose Zr-Nb-Sn and Zr-Nb-Mo through multi-regression analysis of the relationship between the basic properties and the compositions. Plasma arc melting was used to produce the alloys and the microstructure change introduced by the processing steps including hot forging, beta-heat treatment, hot rolling, cold rolling and recrystallization heat treatment was investigated. Recrystallization of Zr-Nb-Sn was retarded by adding Mo and this resulted in a fine grain structure in Zr-Nb-Sn-Mo alloy. Beside the retarding effect recrystallization, Mo increased the amount of residual beta phase and showed an indication of precipitation hardening, which added up to the possibility of applying the alloy for the desired usage. (author)

  20. Reflux condensation behavior in SBLOCA tests of ATLAS facility

    International Nuclear Information System (INIS)

    Kim, Yeon-Sik; Park, Hyun-Sik; Cho, Seok; Choi, Ki-Yong; Kang, Kyoung-Ho

    2017-01-01

    Highlights: • Behavior of a reflux condensation heat transfer was investigated for SBLOCA tests. • Behavior of the reflux condensate in HL, SG inlet plenum, and U-tubes were evaluated. • Concept of a steam moisturizing phenomenon was introduced and discussed. • Test data and MARS calculations were compared and discussed on the reflux condensate. - Abstract: The behavior of the reflux condensation heat transfer in a hot side steam generator (SG) U-tubes during a cold leg (CL) pipe and a direct vessel injection (DVI) line break in small break loss-of-coolant accident (SBLOCA) tests of the ATLAS facility was investigated including MARS code calculations. Among the SBLOCA tests, a 6″-CL pipe and 50%-DVI line break SBLOCA test were selected to investigate the behavior of the reflux condensation. A reflux condensation heat transfer seemed to occur from the time the SG U-tubes were half-empty to near the loop seal clearing (LSC). It was found that a transition regime existed between the reflux condensation heat transfer and reverse heat transfer. The remaining reflux condensate in SG U-tubes owing to the counter-current flow limit (CCFL) phenomenon and a separating effect of liquid carry-over and/or entrainment with steam moisturizing seemed to affect the thermal-hydraulic behavior of the transition regime. It was also found that the steam flowrate of the loop pipings and SG U-tubes seemed to have a strong effect on the duration time of the transition regime, e.g., a larger steam flowrate results in a longer duration. From a comparison of the reflux condensation behavior between the ATLAS tests and MARS code calculations, overall qualitative agreements were found between the two cases. The largest discrepancies were found in the SG inlet plenum water level between the two cases, and the authors suggest that the combination effects of the remaining reflux condensate in SG U-tubes and a separating effect of liquid carry-over and/or entrainment with steam

  1. Viability of thin wall tube forming of ATF FeCrAl

    Energy Technology Data Exchange (ETDEWEB)

    Maloy, Stuart Andrew [Los Alamos National Lab. (LANL), Los Alamos, NM (United States); Aydogan, Eda [Los Alamos National Lab. (LANL), Los Alamos, NM (United States); Anderoglu, Osman [Los Alamos National Lab. (LANL), Los Alamos, NM (United States); Lavender, Curt [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Yamamoto, Yukinori [Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States)

    2016-09-16

    Fabrication of thin walled tubing of FeCrAl alloys is critical to its success as a candidate enhanced accident-tolerant fuel cladding material. Alloys that are being investigated are Generation I and Generation II FeCrAl alloys produced at ORNL and an ODS FeCrAl alloy, MA-956 produced by Special Metals. Gen I and Gen II FeCrAl alloys were provided by ORNL and MA-956 was provided by LANL (initially produced by Special Metals). Three tube development efforts were undertaken. ORNL led the FeCrAl Gen I and Gen II alloy development and tube processing studies through drawing tubes at Rhenium Corporation. LANL received alloys from ORNL and led tube processing studies through drawing tubes at Century Tubing. PNNL led the development of tube processing studies on MA-956 through pilger processing working with Sandvik Corporation. A summary of the recent progress on tube development is provided in the following report and a separate ORNL report: ORNL/TM-2015/478, “Development and Quality Assessments of Commercial Heat Production of ATF FeCrAl Tubes”.

  2. SeZnSb alloy and its nano tubes, graphene composites properties

    Directory of Open Access Journals (Sweden)

    Abhay Kumar Singh

    2013-04-01

    Full Text Available Composite can alter the individual element physical property, could be useful to define the specific use of the material. Therefore, work demonstrates the synthesis of a new composition Se96-Zn2-Sb2 and its composites with 0.05% multi-walled carbon nano tubes and 0.05% bilayer graphene, in the glassy form. The diffused amorphous structure of the multi walled carbon nano tubes and bilayer gaphene in the Se96-Zn2-Sb2 alloy have been analyzed by using the Raman, X-ray photoluminescence spectroscopy, Furrier transmission infrared spectra, photoluminescence, UV/visible absorption spectroscopic measurements. The diffused prime Raman bands (G and D have been appeared for the multi walled carbon nano tubes and graphene composites, while the X-ray photoluminescence core energy levels peak shifts have been observed for the composite materials. Subsequently the photoluminescence property at room temperature and a drastic enhancement (upto 80% in infrared transmission percentage has been obtained for the bilayer graphene composite, along with optical energy band gaps for these materials have been evaluated 1.37, 1.39 and 1.41 eV.

  3. Scandinavian experience of titanium condensers

    International Nuclear Information System (INIS)

    Multer, I.; Hedstroem, M.

    1985-01-01

    The Albrass condenser tubing in Sweden and Finnish nuclear power plants has caused much concern. After the appearance of the first tube leak, the deterioration has been very rapid. A typical development is represented by the Ringhals unit 2 eddy current (EC) measurements. They are, despite the difference in salinity, almost identical with Forsmark units 1 and 2 and units 1 and 2 of the TVO power company at Olkiluoto, Finland. For instance, in summer 1984, 3000 tubes were plugged in TVO 2 after four years of operation. The cause was pitting and/or erosion-corrosion. The failure rate, although the plugging criteria have been different from the EPRI concept, has exceeded that reported in the US and UK; and it has been necessary, especially with the strict feed water chemistry requirements in the PWR's, to arrange for retubing after a very short time, approximately 3 years after the first leak. The history of the nuclear plant condensers is shown; the average condenser life span has been approximately 6.5 years

  4. Steam generators, turbines, and condensers. Volume six

    International Nuclear Information System (INIS)

    Anon.

    1986-01-01

    Volume six covers steam generators (How steam is generated, steam generation in a PWR, vertical U-tube steam generators, once-through steam generators, how much steam do steam generators make?), turbines (basic turbine principles, impulse turbines, reaction turbines, turbine stages, turbine arrangements, turbine steam flow, steam admission to turbines, turbine seals and supports, turbine oil system, generators), and condensers (need for condensers, basic condenser principles, condenser arrangements, heat transfer in condensers, air removal from condensers, circulating water system, heat loss to the circulating water system, factors affecting condenser performance, condenser auxiliaries)

  5. Demonstration of a shape memory alloy torque tube-based morphing radiator

    Science.gov (United States)

    Chong, Jorge B.; Walgren, Patrick; Hartl, Darren J.

    2018-03-01

    Long-distance crewed space exploration will require advanced thermal control systems (TCS) with the ability to handle a wide range of thermal loads. The ability of a TCS to adapt to the thermal environment is described by the turndown ratio. Developing radiators with high turndown ratios is critical for improving TCS technology. This paper describes a novel morphing radiator designed to achieve a high turndown ratio by varying its own radiative view factor and effective emissivity through the use of shape memory alloys (SMAs). This radiator features two SMA torque tubes cantilevered to a rigid fixture. The working fluid is transported within the SMA tubes through an annular flow system. In a cold environment, radiator panels fixed to the free ends of the tubes are oriented vertically in a parallel-plate fashion, where the high-emissivity interior faces have restricted views to the environment and heat rejection is minimized. When the system heats up, the tubes actuate by twisting in opposing directions, bringing the panels to a horizontal position with the interior faces exposed to maximize heat rejection. When the system cools down, the tubes twist in reverse, restoring the panels to the vertical orientation where heat rejection is again minimized. This variable heat rejection system has the potential for achieving higher turndown ratios than those of current state-of-the-art systems. A benchtop prototype has been designed and tested to demonstrate actuation and to explore internal heat transfer effects. Prototype design, testing, and results are herein described.

  6. Environmentally assisted fatigue evaluation model of alloy 690 steam generator tube in high temperature water

    International Nuclear Information System (INIS)

    Tan Jibo; Wu Xinqiang; Han Enhou; Wang Xiang; Liu Xiaoqiang; Xu Xuelian

    2015-01-01

    Nickel-based alloy 690 has been widely used as steam generator tube in light water reactor (LWR) nuclear power plants, which may suffer from corrosion fatigue during long-term service. Many researches and operating experience indicated that the effect of LWR environment could significantly reduce the fatigue life of structural materials. However. such an environmental degradation effect was not fully addressed in the current ASME code design fatigue curves. Therefore, the Regulatory Guide 1.207 issued by US NRC required a new NPP have to incorporate the environment effects into fatigue analyses. In the last few decades, researchers in USA and Japan systematically investigated the corrosion fatigue behavior of nuclear-grade structural materials in LWR environment. Then, ANL model and JSME model were proposed, which incorporated environmental effects, including temperature, dissolved oxygen (DO) and strain rate for the nickel-based alloys. Due to lack of experiment data on domestic materials, there is no related environmental fatigue design model in China. In the present work, based on the corrosion fatigue tests of a kind of boat-shaped specimen in borated and lithiated high temperature water, the corrosion fatigue behavior and environmentally assisted cracking mechanism of domestic Alloy 690 steam generator tube have been investigate. An IMR model for the nickel-based alloy was proposed. The environmental fatigue life correction factor (F en ) was established, which addressed the environmental factors, including temperature, strain rate and dissolved oxygen. The method to evaluate environmental fatigue damage of structural materials in NPPs was proposed. (authors)

  7. Failure evaluation on a high-strength alloy SA213-T91 super heater tube of a power generation

    Energy Technology Data Exchange (ETDEWEB)

    Ahmad, J.; Purbolaksono, J.; Beng, L.C.; Ahmad, A. [University of Tenaga Nas, Kajang (Malaysia). Dept. of Mechanical Engineering

    2010-07-01

    This article presents failure investigation on a high-strength alloy SA213-T91 superheater tube. This failure is the first occurrence involving the material in Kapar Power Station Malaysia. The investigation includes visual inspections, hardness measurements, and microscopic examinations. The failed super-heater tube shows a wide open rupture with thin and blunt edges. Hardness readings on all the as-received tubes are used for estimating the operating metal temperature of the super-heater tubes. Microstructures of the failed tube show numerous creep cavities consisting of individual pores and chain of pores which form micro-and macro-cracks. The findings confirmed that the super-heater tube is failed by short-term overheating. Higher temperatures of the flue gas due to the inconsistent feeding of pulverized fuels into the burner is identified to cause overheating of the failed tube.

  8. Condensing boiler applications in the process industry

    International Nuclear Information System (INIS)

    Chen, Qun; Finney, Karen; Li, Hanning; Zhang, Xiaohui; Zhou, Jue; Sharifi, Vida; Swithenbank, Jim

    2012-01-01

    Major challenging issues such as climate change, energy prices and fuel security have focussed the attention of process industries on their energy efficiency and opportunities for improvement. The main objective of this research study was to investigate technologies needed to exploit the large amount of low grade heat available from a flue gas condensing system through industrial condensing boilers. The technology and application of industrial condensing boilers in various heating systems were extensively reviewed. As the condensers require site-specific engineering design, a case study was carried out to investigate the feasibility (technically and economically) of applying condensing boilers in a large scale district heating system (40 MW). The study showed that by recovering the latent heat of water vapour in the flue gas through condensing boilers, the whole heating system could achieve significantly higher efficiency levels than conventional boilers. In addition to waste heat recovery, condensing boilers can also be optimised for emission abatement, especially for particle removal. Two technical barriers for the condensing boiler application are corrosion and return water temperatures. Highly corrosion-resistant material is required for condensing boiler manufacture. The thermal design of a 'case study' single pass shell-and-tube condensing heat exchanger/condenser showed that a considerable amount of thermal resistance was on the shell-side. Based on the case study calculations, approximately 4900 m 2 of total heat transfer area was required, if stainless steel was used as a construction material. If the heat transfer area was made of carbon steel, then polypropylene could be used as the corrosion-resistant coating material outside the tubes. The addition of polypropylene coating increased the tube wall thermal resistance, hence the required heat transfer area was approximately 5800 m 2 . Net Present Value (NPV) calculations showed that the choice of a carbon

  9. Welding qualification procedure for fuel rods tubes of Zr-Sn alloys by the TIG automatic process

    International Nuclear Information System (INIS)

    1984-11-01

    It is presented the requirements to be used in the Welding qualification procedure for tubes of Zr-Sn alloys, specified in the ASTM B353 regulatory guide, used in the fabrication of fuel rods PWR reactors by the automatic TIG process. (E.G.) [pt

  10. Incorporation of Condensation Heat Transfer in a Flow Network Code

    Science.gov (United States)

    Anthony, Miranda; Majumdar, Alok

    2002-01-01

    Pure water is distilled from waste water in the International Space Station. The distillation assembly consists of an evaporator, a compressor and a condenser. Vapor is periodically purged from the condenser to avoid vapor accumulation. Purged vapor is condensed in a tube by coolant water prior to entering the purge pump. The paper presents a condensation model of purged vapor in a tube. This model is based on the Finite Volume Method. In the Finite Volume Method, the flow domain is discretized into multiple control volumes and a simultaneous analysis is performed.

  11. Numerical analysis on the condensation heat transfer and pressure drop characteristics of the horizontal tubes of modular shell and tube-bundle heat exchanger

    International Nuclear Information System (INIS)

    Ko, Seung Hwan; Park, Hyung Gyu; Kim, Charn Jung; Park, Byung Kyu

    2001-01-01

    A numerical analysis of the heat and mass transfer and pressure drop characteristics in modular shell and tube bundle heat exchanger was carried out. Finite concept method based on FVM and κ-ε turbulent model were used for this analysis. Condensation heat transfer enhanced total heat transfer rate 4∼8% higher than that of dry heat exchanger. With increasing humid air inlet velocity, temperature and relative humidity, and with decreasing heat exchanger aspect ratio and cooling water velocity, total heat and mass transfer rate could be increased. Cooling water inlet velocity had little effect on total heat transfer

  12. Standard specification for Nickel-Chromium-Iron alloys (UNS N06600, N06601, N06603, N06690, N06693, N06025, N06045, and N06696), Nikel-Chromium-Cobalt-Molybdenum alloy (UNS N06617), and Nickel-Iron-Chromium-Tungsten alloy (UNS N06674) seamless pipe and tube

    CERN Document Server

    American Society for Testing and Materials. Philadelphia

    2011-01-01

    Standard specification for Nickel-Chromium-Iron alloys (UNS N06600, N06601, N06603, N06690, N06693, N06025, N06045, and N06696), Nikel-Chromium-Cobalt-Molybdenum alloy (UNS N06617), and Nickel-Iron-Chromium-Tungsten alloy (UNS N06674) seamless pipe and tube

  13. Comparative study of water chemistry and surface oxide composition on alloy 600 steam generator tubing

    International Nuclear Information System (INIS)

    Bjoernkvist, L.; Norring, K.; Nyborg, L.

    1993-01-01

    The Ringhals 3 steam generators experience secondary IGSCC on the tubes at support plate locations. Its sister unit Ringhals 4 is so far without IGSCC. Extensive work has been carried out in order to determine the local chemistry in crevices and the composition of deposits and oxide films on the tubes. Hot soaks of the SG:s at zero power has been performed and the water chemistry in occluded crevices of the SGs was predicted to be alkaline, pH 300degreesC = 10. In addition to eddy current testing, a large number of tubes have been pulled and destructively examined. These analysis include SEM/EDS characterization of TSP crevice deposits and Auger electron spectroscopy (AES) with depth profiling to reveal the composition of the tube OD oxide film. The AES analysis show an outer oxide rich in Fe 3 O 4 , mostly deposited. The actual Alloy 600 oxide is found below the magnetite and is 1-2 μm thick. The composition profile of the oxide exhibits a Cr-depletion relative to Ni in the outer part of the oxide, whereas an enrichment is found in depth. In order to correlate the water chemistry to the oxide composition profiles and deposits on pulled tubes, reference samples were prepared in an autoclave. The environments were chosen similar to the predicted Ringhals 3 and 4 crevice chemistry. Exposure both in an alkaline (pH 320degreesC∼ 9.9) and an acidic (pH 320degreesC ∼4.3) environment, containing sodium, chloride and sulphate, was studied. Some samples were also found on the Alloy 600 samples exposed to alkaline environment. Thus the prediction of alkaline chemistry was verified. The enrichment of chromium relative to nickel was shown to be potential and time dependent resulting in an increased Cr/Ni ratio at Cr-max with increasing potential and time

  14. Prediction of Heat Removal Capacity of Horizontal Condensation Heat Exchanger submerged in Pool

    Energy Technology Data Exchange (ETDEWEB)

    Jeon, Seong-Su; Hong, Soon-Joon [FNC Tech., Yongin (Korea, Republic of); Cho, Hyoung-Kyu [Seoul National University, Seoul (Korea, Republic of); Park, Goon-Cherl [KEPCO International Nuclear Graduate School, Ulsan (Korea, Republic of)

    2014-10-15

    As representative passive safety systems, there are the passive containment cooling system (PCCS) of ESBWR, the emergency condenser system (ECS) of the SWR-1000, the passive auxiliary feed-water system (PAFS) of the APR+ and etc. During the nuclear power plant accidents, these passive safety systems can cool the nuclear system effectively via the heat transfer through the steam condensation, and then mitigate the accidents. For the optimum design and the safety analysis of the passive safety system, it is essential to predict the heat removal capacity of the heat exchanger well. The heat removal capacity of the horizontal condensation heat exchanger submerged in a pool is determined by a combination of a horizontal in-tube condensation heat transfer and a boiling heat transfer on the horizontal tube. Since most correlations proposed in the previous nuclear engineering field were developed for the vertical tube, there is a certain limit to apply these correlations to the horizontal tube. Therefore, this study developed the heat transfer model for the horizontal Ushaped condensation heat exchanger submerged in a pool to predict well the horizontal in-tube condensation heat transfer, the boiling heat transfer on the horizontal tube and the overall heat removal capacity of the heat exchanger using the best-estimate system analysis code, MARS.

  15. Condenser Design for the Proposed AM600 NPP

    Energy Technology Data Exchange (ETDEWEB)

    Rahman, Md. Mizanur; Abdallah, Khaled Atya Ahmed; Field, Robert M. [KEPCO International Nuclear Graduate School, Ulsan (Korea, Republic of)

    2015-10-15

    The design goals are to make the condenser more robust and compact with a reduced component count. The AM600 condenser design also has new features as described below. Considering that the minimum heat sink temperature for potentially emergent nuclear countries is on the order of 21.deg. C or higher, a turbine design with a single low pressure rotor can be considered without sacrificing thermal efficiency. The condenser back pressure range for the considered markets is on the order of 2 to 3 in-HgA. With these boundary conditions, the AM600 condenser duty can be met with a single pressure zone design with a total of eight (8) titanium tube bundles (four (4) per pass) divided into four isolable sections. Due to the compact design (i.e., accepting exhaust from only one low pressure cylinder), both axial ends of the condenser are unobstructed and available for attachment of extended flash chambers, diverting inflows away from the tube bundles. The single shell design of this condenser then allows for an innovative design feature, namely the extended flash chambers. This permits the routing of dump, drain, vent, and bypass flows directly to these chambers, bypassing the condenser shell. Within the condenser shell, this design eliminates impingement plates, impingement boxes, and spargers. Failure of these components represents an ongoing source of condenser tube damage in operating nuclear units, requiring significant resources for outage inspections. The extended flash chamber approach also has a number of other advantages as delineated above.

  16. Fluid mechanics and heat transfer spirally fluted tubing

    Science.gov (United States)

    Larue, J. C.; Libby, P. A.; Yampolsky, J. S.

    1981-08-01

    The objective of this program is to develop both a qualitative and a quantitative understanding of the fluid mechanics and heat transfer mechanisms that underlie the measured performance of the spirally fluted tubes under development at General Atomic. The reason for the interest in the spirally fluted tubes is that results to date have indicated three advantages to this tubing concept: The fabrication technique of rolling flutes on strip and subsequently spiralling and simultaneously welding the strip to form tubing results in low fabrication costs, approximately equal to those of commercially welded tubing. The heat transfer coefficient is increased without a concomitant increase of the friction coefficient on the inside of the tube. In single-phase axial flow of water, the helical flutes continuously induce rotation of the flow both within and without the tube as a result of the effect of curvature. An increase in condensation heat transfer on the outside of the tube is achieved. In a vertical orientation with fluid condensing on the outside of the helically fluted tube, the flutes provide a channel for draining the condensed fluid.

  17. SCC of Alloy 600 in PWR steam generator tubes

    International Nuclear Information System (INIS)

    Pascali, R.; Buzzanca, G.; Quaglia, G.M.; Ronchetti, C.

    1986-01-01

    The studies reported in this paper concern the evaluation of Alloy 600 and 690 behaviour in chemical agressive conditions simulating the concentration film on heat exchanging tube. The corrosion tests have been performed to evidence the influence of metallurgical conditions and different heats. Various devices for reproducing dead areas and steam blanketing have been designed and tested, such as, umbrellas, rings, thin deposits, etc. A system to reproduce the S.G. areas with thick deposits has been designed successively and set up in a previous series of tests, in boiling water at 56 kg/cm/sup 2/, 270 0 C and heat flux 45 W/cm/sup 2/. Caustic SCC tests have been carried out in adiabatic conditions also using small autoclaves

  18. Plugging of feed inlet tube upstands with Ni/Ti shape memory alloy plugs - Heysham 1 power station

    International Nuclear Information System (INIS)

    Mathews, A.J.

    1988-01-01

    The paper contains a description of a new approach for Plugging feed inlet tubes of Gas-Cooled Reactors. Instead of utilizing the original explosive method plugging by fitting a shape memory alloy plug into the upstand is being described. (author)

  19. Comparison of Heat Transfer Coefficients of Silver Coated and Chromium Coated Copper Tubes of Condenser in Dropwise Condensation

    OpenAIRE

    Er. Shivesh Kumar; Dr. Amit Kumar

    2016-01-01

    Since centuries steam is being used in power generating system. The steam leaving the power unit is reconverted into water in a condenser designed to transfer heat from the steam to the cooling water as rapidly and as efficiently as possible. The efficiency of condenser depends on rate of condensation and mode of condensation of steam in the condenser. The increase in efficiency of the condenser enhances the heat transfer co-efficient which in turn results in economic design of condenser and ...

  20. Lifespan estimation of seal welded super stainless steels for water condenser of nuclear power plants

    Science.gov (United States)

    Kim, Young Sik; Park, Sujin; Chang, Hyun Young

    2014-01-01

    When sea water was used as cooling water for water condenser of nuclear power plants, commercial stainless steels can not be applied because chloride concentration exceeds 20,000 ppm. There are many opinions for the materials selection of tube and tube sheets of a condenser. This work reviewed the application guide line of stainless steels for sea-water facilities and the estimation equations of lifespan were proposed from the analyses of both field data for sea water condenser and experimental results of corrosion. Empirical equations for lifespan estimation were derived from the pit initiation time and re-tubing time of stainless steel tubing in sea water condenser of nuclear power plants. The lifespan of seal-welded super austenitic stainless steel tube/tube sheet was calculated from these equations. Critical pitting temperature of seal-welded PRE 50 grade super stainless steel was evaluated as 60 °C. Using the proposed equation in engineering aspect, tube pitting corrosion time of seal-welded tube/tube sheet was calculated as 69.8 years and re-tubing time was estimated as 82.0 years.

  1. Minimum Leakage Condenser Test Program

    International Nuclear Information System (INIS)

    1978-05-01

    This report presents the results and analysis of tests performed on four critical areas of large surface condensers: the tubes, tubesheets, tube/tubesheet joints and the water chambers. Significant changes in operation, service duty and the reliability considerations require that certain existing design criteria be verified and that improved design features be developed. The four critical areas were treated analytically and experimentally. The ANSYS finite element computer program was the basic analytical method and strain gages were used for obtaining experimental data. The results of test and analytical data are compared and recommendations made regarding potential improvement in condenser design features and analytical techniques

  2. A comparison of R-22, R-134a, R-410a, and R-407c condensation performance in smooth and enhanced tubes: Part 2, Pressure drop

    Energy Technology Data Exchange (ETDEWEB)

    Eckels, S J; Tesene, B A

    1999-07-01

    This paper reports pressure drops during condensation for R-22, R-134a, R-410a, and R-407c in three enhanced tubes and one smooth tube. The test tubes were a 3/8 inch outer diameter smooth tube, a 3/8 inch outer diameter microfin tube, a 5/16 inch outer diameter microfin tube, and a 5/8 inch outer diameter microfin tube. Pressure drops are reported at four mass fluxes, at two saturation temperatures, and over a range of average qualities in the test tubes. The pressure drops for R-410a were approximately 40% lower than those of R-22 in both tubes. R-407c had 10% to 20% lower pressure drops than R-22, while 134-a had slightly larger pressure drops than R-22. The microfin tube pressure drops were, on average, 40% to 80% higher than those for the smooth tube for all refrigerants. The pressure drop penalty of the microfin tube was shown to decrease with increased quality.

  3. Analytical model for power plant condenser for transients and off-normal operating conditions

    International Nuclear Information System (INIS)

    Thangamani, I.; Dutta, Anu; Chakraborty, G.; Ghosh, A.K.

    2006-11-01

    A computer code for power plant condenser dynamic analysis has been developed based on a lumped parameter approach considering time dependent mass and energy conservation equations over the control volumes for the shell side as well as tube side fluids. Effects of heat transfer on condenser structure and hot well level transients were considered in the analysis. Suitable heat transfer coefficient recommended by various standards and codes were employed. The code was used to analyze the condenser performance during steady state as well as transient (load rejection or turbine trip) conditions. The condenser performance is predicted in terms of condenser back pressure, shell side steam temperature and tube side coolant exit temperature with respect to time. As a part of parametric studies, the effect of change in tube side coolant flow rate and inlet temperature was also studied. The analysis predicted that up to 47% of rated coolant flow rate on the tube side (for design conditions), the steam dumping can be continued without condenser isolation. The paper describes the detailed methodology adopted for the condenser modeling and presents the results obtained from the different parametric studies and code validation. (author)

  4. Heat exchanger with intermediate evaporating and condensing fluid

    International Nuclear Information System (INIS)

    Fraas, A.P.

    1978-01-01

    A shell and tube-type heat exchanger, such as a liquid sodium-operated steam generator for use in nuclear reactors, comprises a shell containing a primary fluid tube bundle, a secondary fluid tube bundle at higher elevation, and an intermediate fluid vaporizing at the surface of the primary fluid tubes and condensing at the surface of the secondary fluid tubes

  5. Stress Corrosion Cracking of Ni-base Alloys in Sulfur Containing Solutions at 340 .deg. C

    Energy Technology Data Exchange (ETDEWEB)

    Lee, Eun Hee; Hwang, Seong Sik; Kim, Dong Jin; Kim, Sung Woo [KAERI, Daejeon (Korea, Republic of)

    2016-05-15

    Sulfur has been identified as one of the major impurities introduced into the secondary water of pressurized water-reactors (PWRs). Sulfur can originate from various sources, such as resin sources, feed water, cooling water in-leakage, and condenser leaks. Many authors have investigated effects of reduced sulfur in a wide pH range with or without additives. The presence of reduced sulfur species on the surfaces of pulled tubes having stress corrosion cracking (SCC) was also identified. In present work, SCC tests were conducted to investigate effects of reduced sulfur species on the SCC behavior of Ni-base Alloys. The Alloy 690 TT showed the most SCC resistant, regardless of the sulfur species. The Cr content and heat treatments of alloys appeared the increase in the SCC resistance.

  6. Design of spiral fin type condenser for hydrogen cryogenic distillation column

    International Nuclear Information System (INIS)

    Iwai, Yasunori; Nishi, Masataka; Yamanishi, Toshihiko

    2005-08-01

    The purpose of this paper is the proposal of new concept condenser for hydrogen cryogenic distillation column of Hydrogen Isotope Separation System (ISS) in a fusion reactor, and the establishment of numerical evaluation method of the hydrogen isotope inventory in the condenser. A large amount of hydrogen isotopes including high concentration of tritium, radioactive hydrogen isotope, has been handled in the cryogenic distillation column. Therefore, from the safety point of view, cryogenic coolant tube was commonly arranged to surround the condensed area to prevent the mixing of tritium into the coolant. This inevitable arrangement leads the difficulty in the minimization of the condenser. The scale of condenser has influence on the scale of the ISS and its earthquake-resistance. The spiral fin type condenser, which introduces fins inside it and in coolant tube to enhance heat exchange, is proposed as a new concept condenser for hydrogen cryogenic distillation column to miniaturize the condenser. The volume of spiral fin type condenser is estimated to become less than half of that of coil tube type condenser currently in use. Accordingly, it is found that the adoption of spiral fin type condenser realizes the significant miniaturization of the ISS. Moreover, the numerical evaluation method of the hydrogen isotope inventory in the condenser is proposed. The validity of this method was confirmed by the experimental data. The synthetic design of the condenser for the hydrogen cryogenic distillation column is achieved by the combination of the proposed new concept condenser with the numerical evaluation method of the hydrogen isotope inventory. (author)

  7. X-ray study of texture in zirconium alloy tubes and in graphite

    International Nuclear Information System (INIS)

    Skvortsov, V.V.; Alekseev, S.I.

    1987-01-01

    X-ray study of texture in zirconium alloy tubes and in graphite has been developed. The method is based on constructing coordinate grid of stereographic projection determining quantity and coordinates of points where measurements should be performed depending on a specimen slope pitch. Complete stereographic projection obtained so is a base both for constructing pole figures showing distribution normales of plane system being studied and for calculating texture coefficients determining property anisotropy in materials under investigation. This method can be applied to study texture in items of any materials independent of the item shape

  8. Protected air-cooled condenser for the Clinch River Breeder Reactor Plant

    International Nuclear Information System (INIS)

    Louison, R.; Boardman, C.E.

    1981-01-01

    The long term residual heat removal for the Clinch River Breeder Reactor Plant (CRBRP) is accomplished through the use of three protected air-cooled condensers (PACC's) each rated at 15M/sub t/ following a normal or emergency shutdown of the reactor. Steam is condensed by forcing air over the finned and coiled condenser tubes located above the steam drums. The steam flow is by natural convection. It is drawn to the PACC tube bundle for the steam drum by the lower pressure region in the tube bundle created from the condensing action. The concept of the tube bundle employs a unique patented configuration which has been commercially available through CONSECO Inc. of Medfore, Wisconsin. The concept provides semi-parallel flow that minimizes subcooling and reduces steam/condensate flow instabilities that have been observed on other similar heat transfer equipment such as moisture separator reheaters (MSRS). The improved flow stability will reduce temperature cycling and associated mechanical fatigue. The PACC is being designed to operate during and following the design basis earthquake, depressurization from the design basis tornado and is housed in protective building enclosure which is also designed to withstand the above mentioned events

  9. Effect of Mixed Working Fluid Composition on Binary Cycle Condenser Heat Transfer Coefficients

    Energy Technology Data Exchange (ETDEWEB)

    Dan Wendt; Greg Mines

    2011-10-01

    Effect of Mixed Working Fluid Composition on Binary Cycle Condenser Heat Transfer Coefficients Dan Wendt, Greg Mines Idaho National Laboratory The use of mixed working fluids in binary power plants can provide significant increases in plant performance, provided the heat exchangers are designed to take advantage of these fluids non-isothermal phase changes. In the 1980's testing was conducted at DOE's Heat Cycle Research Facility (HCRF) where mixtures of different compositions were vaporized at supercritical pressures and then condensed. This testing had focused on using the data collected to verify that Heat Transfer Research Incorporated (HTRI) codes were suitable for the design of heat exchangers that could be used with mixtures. The HCRF data includes mixture compositions varying from 0% to 40% isopentane and condenser tube orientations of 15{sup o}, 60{sup o}, and 90{sup o} from horizontal. Testing was performed over a range of working fluid and cooling fluid conditions. Though the condenser used in this testing was water cooled, the working fluid condensation occurred on the tube-side of the heat exchanger. This tube-side condensation is analogous to that in an air-cooled condenser. Tube-side condensing heat transfer coefficient information gleaned from the HCRF testing is used in this study to assess the suitability of air-cooled condenser designs for use with mixtures. Results of an air-cooled binary plant process model performed with Aspen Plus indicate that that the optimal mixture composition (producing the maximum net power for the scenario considered) is within the range of compositions for which data exist. The HCRF data is used to assess the impact of composition, tube orientation, and process parameters on the condensing heat transfer coefficients. The sensitivity of the condensing coefficients to these factors is evaluated and the suitability of air-cooled condenser designs with mixtures is assessed. This paper summarizes the evaluation

  10. Microstructure, elastic deformation behavior and mechanical properties of biomedical β-type titanium alloy thin-tube used for stents.

    Science.gov (United States)

    Tian, Yuxing; Yu, Zhentao; Ong, Chun Yee Aaron; Kent, Damon; Wang, Gui

    2015-05-01

    Cold-deformability and mechanical compatibility of the biomedical β-type titanium alloy are the foremost considerations for their application in stents, because the lower ductility restricts the cold-forming of thin-tube and unsatisfactory mechanical performance causes a failed tissue repair. In this paper, β-type titanium alloy (Ti-25Nb-3Zr-3Mo-2Sn, wt%) thin-tube fabricated by routine cold rolling is reported for the first time, and its elastic behavior and mechanical properties are discussed for the various microstructures. The as cold-rolled tube exhibits nonlinear elastic behavior with large recoverable strain of 2.3%. After annealing and aging, a nonlinear elasticity, considered as the intermediate stage between "double yielding" and normal linear elasticity, is attributable to a moderate precipitation of α phase. Quantitive relationships are established between volume fraction of α phase (Vα) and elastic modulus, strength as well as maximal recoverable strain (εmax-R), where the εmax-R of above 2.0% corresponds to the Vα range of 3-10%. It is considered that the "mechanical" stabilization of the (α+β) microstructure is a possible elastic mechanism for explaining the nonlinear elastic behavior. Copyright © 2015 Elsevier Ltd. All rights reserved.

  11. Pre-oxidation and its effect on reducing high-temperature corrosion of superheater tubes during biomass firing

    DEFF Research Database (Denmark)

    Okoro, Sunday Chukwudi; Kvisgaard, M.; Montgomery, Melanie

    2017-01-01

    Superheater tubes in biomass-fired power plants experience high corrosion rates due to condensation of corrosive alkali chloride-rich deposits. To explore the possibility of reducing the corrosion attack by the formation of an initial protective oxide layer, the corrosion resistance of pre......-oxidised Al and Ti-containing alloys (Kanthal APM and Nimonic 80A, respectively) was investigated under laboratory conditions mimicking biomass firing. The alloys were pre-oxidised at 900°C for 1 week. Afterwards, pre-oxidised samples, and virgin non-pre-oxidised samples as reference, were coated...... with a synthetic deposit of KCl and exposed at 560°C for 1 week to a gas mixture typical of biomass firing. Results show that pre-oxidation could hinder the corrosion attack; however, the relative success was different for the two alloys. While corrosion attack was observed on the pre-oxidised Kanthal APM, the pre...

  12. Numerical modeling of counter-current condensation in a Black Liquor Gasification plant

    International Nuclear Information System (INIS)

    Risberg, Mikael; Gebart, Rikard

    2013-01-01

    Pressurized Entrained flow High Temperature Black Liquor Gasification is a novel technique to recover the inorganic chemicals and available energy in black liquor originating from kraft pulping. The gasifier has a direct quench that quickly cools the raw syngas when it leaves the hot reactor by spraying the gas with a water solution. As a result, the raw syngas becomes saturated with steam. Typically the gasifier operates at 30 bar which corresponds to a dew point of about 235 °C and a steam concentration in the saturated syngas that is about 3 times higher than the total concentration of the other species in the syngas. After the quench cooler the syngas is passed through a counter-current condenser where the raw syngas is cooled and most of the steam is condensed. The condenser consists of several vertical tubes where reflux condensation occurs inside the tubes due to water cooling of the tubes on the shell-side. A large part of the condensation takes place inside the tubes on the wall and results in a counterflow of water driven by gravity through the counter current condenser. In this study a computational fluid dynamics model is developed for the two-phase fluid flow on the tube-side of the condenser and for the single phase flow of the shell-side. The two-phase flow was treated using an Euler–Euler formulation with closure correlations for heat flux, condensation rate and pressure drop inside the tubes. The single-phase model for the shell side uses closure correlations for the heat flux and pressure drop. Predictions of the model are compared with results from experimental measurements in a condenser used in a 3 MW Black Liquor Gasification development plant. The results are in good agreement with the limited experimental data that has been collected in the experimental gasifier. However, more validation data is necessary before a definite conclusion can be drawn about the predictive capability of the code. -- Highlights: • A multi-phase model for a

  13. Cladding tube manufacturing technology

    Energy Technology Data Exchange (ETDEWEB)

    Hahn, R. [Kraftwerk Union AG, Mulheim (Germany); Jeong, Y.H.; Baek, B.J.; Kim, K.H.; Kim, S.J.; Choi, B.K.; Kim, J.M. [Korea Atomic Energy Research Institute, Taejon (Korea, Republic of)

    1999-04-01

    This report gives an overview of the manufacturing routine of PWR cladding tubes. The routine essentially consists of a series of deformation and annealing processes which are necessary to transform the ingot geometry to tube dimensions. By changing shape, microstructure and structure-related properties are altered simultaneously. First, a short overview of the basics of that part of deformation geometry is given which is related to tube reducing operations. Then those processes of the manufacturing routine which change the microstructure are depicted, and the influence of certain process parameters on microstructure and material properties are shown. The influence of the resulting microstructure on material properties is not discussed in detail, since it is described in my previous report 'Alloy Development for High Burnup Cladding.' Because of their paramount importance still up to now, and because manufacturing data and their influence on properties for other alloys are not so well established or published, the descriptions are mostly related to Zry4 tube manufacturing, and are only in short for other alloys. (author). 9 refs., 46 figs.

  14. Experience in quality assurance of alloy D9 clad tubes for Prototype Fast Breeder Reactor

    International Nuclear Information System (INIS)

    Kapoor, K.; Prahlad, B.

    2012-01-01

    Stainless Steel Alloy D9 is the material for cladding in various sub-assemblies of Prototype Fast Breeder Reactor (PFBR). The fabrication, inspection, testing and supply of the clad tubes for the first core of PFBR is nearly completed. The paper also compares the specification requirements and the achieved results for some of the critical aspects which is arrived after completing supply against the first core requirement

  15. Steam generator tube integrity program

    International Nuclear Information System (INIS)

    Dierks, D.R.; Shack, W.J.; Muscara, J.

    1996-01-01

    A new research program on steam generator tubing degradation is being sponsored by the U.S. Nuclear Regulatory Commission (NRC) at Argonne National Laboratory. This program is intended to support a performance-based steam generator tube integrity rule. Critical areas addressed by the program include evaluation of the processes used for the in-service inspection of steam generator tubes and recommendations for improving the reliability and accuracy of inspections; validation and improvement of correlations for evaluating integrity and leakage of degraded steam generator tubes, and validation and improvement of correlations and models for predicting degradation in steam generator tubes as aging occurs. The studies will focus on mill-annealed Alloy 600 tubing, however, tests will also be performed on replacement materials such as thermally-treated Alloy 600 or 690. An overview of the technical work planned for the program is given

  16. Effect of chloride and sulphate ions on the electrochemical corrosion behavior of alloy 800NG in PWR secondary water environment at 250 deg C

    International Nuclear Information System (INIS)

    Mansur, Fabio A.; Schvartzman, Monica Maria de A.M.; Quinan, Marco A.D.; Soares, Antonio E.G.; Nogueira, Pedro Henrique B.O.

    2013-01-01

    Alloy 800NG (nuclear grade) is used in nuclear steam generators (SG) as the tubing material for pressurized water reactors (PWRs) because of its high corrosion resistance. The corrosion resistance is due to the protective character of the oxide film formed on the tube surface by contact with the high temperature pressurized water. Nevertheless, corrosion has been the major cause of tube failures in nuclear SGs. The existing experience of different nuclear power plants shows that the water chemistry has an important role in maintaining the integrity of the protective oxide films. Many of such problems have been attributed to secondary side water chemistry conditions and excursions, many of which have been resulted from condenser cooling water ingress. Alloy 800 is known to undergo passivity breakdown and pitting in the presence of chloride ions under oxidative water conditions. In this work the effect of chloride and sulphate ions at various concentrations on the corrosion behavior of Alloy 800 tube at 250 deg C was investigated using the potentiodynamic anodic polarization technique. An active-passive transition occurred at 250 deg C in all studied conditions and the oxide film grown on surface showed greater porosity and lower resistance to localised corrosion in all studied conditions. (author)

  17. Performance of evaporative condensers

    Energy Technology Data Exchange (ETDEWEB)

    Ettouney, Hisham M.; El-Dessouky, Hisham T.; Bouhamra, Walid; Al-Azmi, Bader

    2001-07-01

    Experimental investigation is conducted to study the performance of evaporative condensers/coolers. The analysis includes development of correlations for the external heat transfer coefficient and the system efficiency. The evaporative condenser includes two finned-tube heat exchangers. The system is designed to allow for operation of a single condenser, two condensers in parallel, and two condensers in series. The analysis is performed as a function of the water-to-air mass flow rate ratio (L/G) and the steam temperature. Also, comparison is made between the performance of the evaporative condenser and same device as an air-cooled condenser. Analysis of the collected data shows that the system efficiency increases at lower L/G ratios and higher steam temperatures. The system efficiency for various configurations for the evaporative condenser varies between 97% and 99%. Lower efficiencies are obtained for the air-cooled condenser, with values between 88% and 92%. The highest efficiency is found for the two condensers in series, followed by two condensers in parallel and then the single condenser. The parallel condenser configuration can handle a larger amount of inlet steam and can provide the required system efficiency and degree of subcooling. The correlation for the system efficiency gives a simple tool for preliminary system design. The correlation developed for the external heat transfer coefficient is found to be consistent with the available literature data. (Author)

  18. Development of the advanced nuclear materials -Development of Inconel alloys-

    International Nuclear Information System (INIS)

    Kuk, Il Hyun; Chang, Jin Sung; Lee, Chang Kyu; Park, Soon Dong; Kim, Woo Kon; Jeong, Man Kyo; Woo, Yoon Myung; Han, Chang Hee

    1995-07-01

    The performance and the integrity of the steam generator U-tubes directly affects the efficiency and economics of nuclear power plant because they are closely interrelated with the maintenance and repair. Also the steam generator U-tubes have been one of world-wide hot issues in nuclear power plants for long time because of their continuing corrosion-related degradation. Right after stress corrosion cracking of Alloy 600 tubes are reported at primary side, in which the environment is believed to be tightly controlled all the time, in mid 80's, alloy 690 has started to replace alloy 600. Alloy 690 is basically same with alloy 600 except more Cr content. Firstly minor elements in alloy 690 (C, B, N, Y, Mo) were added or controlled to improve hot workability and corrosion resistance. It would be much more desirable if the mechanism or basic understanding of the degradation phenomena of steam generator U-tubes in operation conditions can be illuminated through the alloy modification research. Alloy 600 tubes which were preproduced in cooperation with Sammi Special Steel were evaluated, being compared with imported one. Also alloy 600 and alloy 690 tubes were produced from Inconel 600 and 690 INCO- forged bar. These will be closely evaluated with purely Korean-made alloy 600 and 690 tubes. 22 tabs., 93 figs., 14 refs. (Author)

  19. A pulsed eddy current probe for inspection of support plates from within Alloy-800 steam generator tubes

    International Nuclear Information System (INIS)

    Krause, T. W.; Babbar, V. K.; Underhill, P. R.

    2014-01-01

    Support plate degradation and fouling in nuclear steam generators (SGs) can lead to SG tube corrosion and loss of efficiency. Inspection and monitoring of these conditions can be integrated with preventive maintenance programs, thereby advancing station-life management processes. A prototype pulsed eddy current (PEC) probe, targeting inspection issues associated with SG tubes in SS410 tube support plate structures, has been developed using commercial finite element (FE) software. FE modeling was used to identify appropriate driver and pickup coil configurations for optimum sensitivity to changes in gap and offset for Alloy-800 SG tubes passing through 25 mm thick SS410 support plates. Experimental measurements using a probe that was manufactured based on the modeled configuration, were used to confirm the sensitivity of differential PEC signals to changes in relative position of the tube within the tube support plate holes. Models investigated the effect of shift and tilt of tube with respect to hole centers. Near hole centers and for small shifts, modeled signal amplitudes from the differentially connected coil pairs were observed to change linearly with tube shift. This was in agreement with experimentally measured TEC coil response. The work paves the way for development of a system targeting the inspection and evaluation of support plate structures in steam generators

  20. A pulsed eddy current probe for inspection of support plates from within Alloy-800 steam generator tubes

    Science.gov (United States)

    Krause, T. W.; Babbar, V. K.; Underhill, P. R.

    2014-02-01

    Support plate degradation and fouling in nuclear steam generators (SGs) can lead to SG tube corrosion and loss of efficiency. Inspection and monitoring of these conditions can be integrated with preventive maintenance programs, thereby advancing station-life management processes. A prototype pulsed eddy current (PEC) probe, targeting inspection issues associated with SG tubes in SS410 tube support plate structures, has been developed using commercial finite element (FE) software. FE modeling was used to identify appropriate driver and pickup coil configurations for optimum sensitivity to changes in gap and offset for Alloy-800 SG tubes passing through 25 mm thick SS410 support plates. Experimental measurements using a probe that was manufactured based on the modeled configuration, were used to confirm the sensitivity of differential PEC signals to changes in relative position of the tube within the tube support plate holes. Models investigated the effect of shift and tilt of tube with respect to hole centers. Near hole centers and for small shifts, modeled signal amplitudes from the differentially connected coil pairs were observed to change linearly with tube shift. This was in agreement with experimentally measured TEC coil response. The work paves the way for development of a system targeting the inspection and evaluation of support plate structures in steam generators.

  1. The role of flooding in the design of vent and reflux condensers

    International Nuclear Information System (INIS)

    Sacramento, Julio C.; Heggs, Peter J.

    2009-01-01

    Reflux and vent condensers are vertical separators where film condensation occurs. A vapour mixture is supplied at the bottom of the tubes and encounters vertical cold surfaces. A falling film forms and exits from the bottom of the tubes, flowing counter-current to the vapour, but co-current to the coolant on the shell side. Flooding occurs when the condensate flow moves from a gravity regime to a shear regime. Vapour velocities at or above the flooding velocity will cause the liquid to exit from the top of the tubes rather than from the bottom. The main disadvantage of these condensers is the limited flooding velocity allowed. Several investigators propose correlations to predict the flooding velocity. In most cases these correlations come from isothermal experiments data, thus the general recommendation of using safety factors of at least 30%. This work compares these correlations to new experimental values of flooding in steam/air vent condensation. The experimental apparatus is a 3 m long, double-pipe condenser with an internal diameter of 0.028 m. The conclusions presented here will aid the design engineer to understand better the applicability of the discussed correlations in the design of steam/air vent condensers

  2. New method for the simultaneous condensation of complete ternary alloy systems under ultrahigh vacuum conditions

    International Nuclear Information System (INIS)

    Mehrtens, A.; Moske, M.; Samwer, K.

    1988-01-01

    An ultrahigh vacuum apparatus is described for the simultaneous condensation of complete ternary alloy systems. Three singly controlled electron beam evaporation sources provide a constant evaporation rate of the different elements. A specially designed rotating mask guarantees a concentration gradient on the substrate according to a ternary phase diagram. The conversion of the actual concentration profile into a standard ternary phase diagram is done by simple computer calculations. They involve corrections for the beam characteristics of the evaporation sources and for the rotating mask. As an example, measurements for the Zr--Cu--Co system are given. The concentration range for the amorphous phase is compared with thermodynamic predictions using Miedema's parameter

  3. Mock-up tests on the combustion of hydrogen-air mixture in the vertical tube simulating the CNS channel of the CARR

    International Nuclear Information System (INIS)

    Yu Qingfeng; Feng Quanke; Kawai, Takeshi; Xu Jian

    2007-01-01

    A two-phase thermo-siphon loop for removing nuclear heating and maintaining the stable liquid level in the moderator cell was adopted for the cold neutron source (CNS) of the China advanced research reactor (CARR). The moderator is liquid hydrogen. The two-phase thermo-siphon loop consists of the crescent-shape moderator cell, the moderator transfer tube, and the condenser. The hydrogen is supplied from the buffer tank to the condenser. The main feature of the loop is that the moderator cell is covered by the helium sub-cooling system. The cold helium gas from the helium refrigerator is firstly introduced into the helium sub-cooling system and then flows up through the tube covering the moderator transfer tube into the condenser. The main part of this system is installed in the CNS vertical channel made of aluminum alloy 6061 T6 (Al-6061-T6) of 6 mm in thickness, 270 mm in outer diameter and about 6 m in height. For confirming the safety of the CNS channel, the combustion tests using a tube compatible with the CNS channel were carried out using the hydrogen-air mixture under which air is introduced into the tube at 1 atmosphere, and then hydrogen gas is supplied from the gas cylinder up to the test pressures. And maximum test pressure is 0.14 MPa G. This condition is involved with the maximum design basis accident of the CARR-CNS. The peak pressure due to combustion was 1.09 MPa, and the design pressure of the CNS channel is 3 MPa. The safety of the CNS was thus verified even if the maximum design basis accident occurs. The pressure and stress distributions along the axial direction and the displacement of the tube were also measured

  4. Synthesis and characterization of Ni-Mo filler brazing alloy for Mo-W joining for microwave tube technology

    Directory of Open Access Journals (Sweden)

    Frank Ferrer Sene

    2013-04-01

    Full Text Available A brazing process based on Ni-Mo alloy was developed to join porous tungsten cathode bottom and dense molybdenum cathode body for microwave tubes manufacture. The Ni-Mo alloy was obtained by mixing and milling powders in the eutectic composition, and applied on the surface of the components. The brazing was made at 1400 °C by using induction heating in hydrogen for 5 minutes. Alumina surfaces were coated with the binder and analyzed by Energy Dispersive X-rays Fluorescence. The brazed samples were analyzed by Scanning Electron Microscopy coupled to Energy Dispersive Spectroscopy. Stress-strain tests were performed to determine the mechanical behavior of the joining. The quality of the brazing was evaluated by assuring the presence of a "meniscus" formed by the Ni-Mo alloy on the border of the tungsten and molybdenum joint, the absence of microstructural defects in the interface between the tungsten and molybdenum alloys, and the adhesion of the brazed components.

  5. Oxide Dispersion Strengthened Fe(sub 3)Al-Based Alloy Tubes: Application Specific Development for the Power Generation Industry

    Energy Technology Data Exchange (ETDEWEB)

    Kad, B.K.

    1999-07-01

    A detailed and comprehensive research and development methodology is being prescribed to produce Oxide Dispersion Strengthened (ODS)-Fe3Al thin walled tubes, using powder extrusion methodologies, for eventual use at operating temperatures of up to 1100C in the power generation industry. A particular 'in service application' anomaly of Fe3Al-based alloys is that the environmental resistance is maintained up to 1200C, well beyond where such alloys retain sufficient mechanical strength. Grain boundary creep processes at such high temperatures are anticipated to be the dominant failure mechanism.

  6. Theoretical Analysis of Effects of Wall Suction on Entropy Generation Rate in Laminar Condensate Layer on Horizontal Tube

    Directory of Open Access Journals (Sweden)

    Tong-Bou Chang

    2014-01-01

    Full Text Available The effects of wall suction on the entropy generation rate in a two-dimensional steady film condensation flow on a horizontal tube are investigated theoretically. In analyzing the liquid flow, the effects of both the gravitational force and the viscous force are taken into account. In addition, a film thickness reduction ratio, Sf, is introduced to evaluate the effect of wall suction on the thickness of the condensate layer. The analytical results show that, the entropy generation rate depends on the Jakob number Ja, the Rayleigh number Ra, the Brinkman number Br, the dimensionless temperature difference ψ, and the wall suction parameter Sw. In addition, it is shown that in the absence of wall suction, a closed-form correlation for the Nusselt number can be derived. Finally, it is shown that the dimensionless entropy generation due to heat transfer, NT, increases with an increasing suction parameter Sw, whereas the dimensionless entropy generation due to liquid film flow friction, NF, decreases.

  7. Air condensation plants

    International Nuclear Information System (INIS)

    Kelp, F.; Pohl, H.H.

    1978-01-01

    In this plant the steam is distributed by a ventilator from the bottom to symmetrically fixed, inclined cooling elements with tubes. The upper part of the current side of the cooling elements as well as the bottom part of the outflow side can be covered by cover plates via a control circuit. This way, part of the air amount is deviated and in case of unfavourable atmospheric conditions (cold) the air is heated. This heating is enough to prevent freezing of the condensate on the cooling tubes. (DG) [de

  8. Evaluation of Advanced Models for PAFS Condensation Heat Transfer in SPACE Code

    Energy Technology Data Exchange (ETDEWEB)

    Bae, Byoung-Uhn; Kim, Seok; Park, Yu-Sun; Kang, Kyung Ho [Korea Atomic Energy Research Institute, Daejeon (Korea, Republic of); Ahn, Tae-Hwan; Yun, Byong-Jo [Pusan National University, Busan (Korea, Republic of)

    2015-10-15

    The PAFS (Passive Auxiliary Feedwater System) is operated by the natural circulation to remove the core decay heat through the PCHX (Passive Condensation Heat Exchanger) which is composed of the nearly horizontal tubes. For validation of the cooling and operational performance of the PAFS, PASCAL (PAFS Condensing Heat Removal Assessment Loop) facility was constructed and the condensation heat transfer and natural convection phenomena in the PAFS was experimentally investigated at KAERI (Korea Atomic Energy Research Institute). From the PASCAL experimental result, it was found that conventional system analysis code underestimated the condensation heat transfer. In this study, advanced condensation heat transfer models which can treat the heat transfer mechanisms with the different flow regimes in the nearly horizontal heat exchanger tube were analyzed. The models were implemented in a thermal hydraulic safety analysis code, SPACE (Safety and Performance Analysis Code for Nuclear Power Plant), and it was evaluated with the PASCAL experimental data. With an aim of enhancing the prediction capability for the condensation phenomenon inside the PCHX tube of the PAFS, advanced models for the condensation heat transfer were implemented into the wall condensation model of the SPACE code, so that the PASCAL experimental result was utilized to validate the condensation models. Calculation results showed that the improved model for the condensation heat transfer coefficient enhanced the prediction capability of the SPACE code. This result confirms that the mechanistic modeling for the film condensation in the steam phase and the convection in the condensate liquid contributed to enhance the prediction capability of the wall condensation model of the SPACE code and reduce conservatism in prediction of condensation heat transfer.

  9. Heat transfer characteristics of an EHD condenser. 2nd Report. ; Development of an EHD condenser. EHD gyoshukuki no netsudentatsu seino. 2. ; EHD gyoshukuki no jitsuyoka kenkyu

    Energy Technology Data Exchange (ETDEWEB)

    Yamashita, K; Kumagai, M; Sekita, S [Toshiba Corp., Tokyo (Japan); Yabe, A; Taketani, T; Kikuchi, K [Mechanical Engineering Laboratory, Tsukuba (Japan)

    1991-05-25

    As a series of high performance heat pump R and D as requested by the NEDO, the electrohydrodynamical (EHD) effect being applied to a shell-tube type heat exchanger, experiment to put it to practical use was made under a high temperature and high pressure condition to assume the heat pump. Design and manufacture being made of a 50kW class shell-tube type EHD condenser, the use of C {sub 6} F {sub 14} at 150 centigrade in temperature had the condensation heat transfer attain in enhancement ratio, at the highest, to six times as high as conventional. At that time, the consumed power at the helical wire with-lattice electrode was 0.0001% of the converted quantity of heat so that it could be limited to a negligibly very small value. For the EHD condenser, the condensation heat transfer enhancement method with use of the helical wire with-lattice electrode had its enhancement performance known to be effective in case that the heat transfer tube was long or that the medium was small in condensation latent heat. As a heat pump use condenser, there was known not to occur degradation in condensation heat transfer performance nor large enlargement in consumed power by lubrication oil, contained in the compressor. 9 refs., 14 figs., 1 tab.

  10. Strong, corrosion-resistant aluminum tubing

    Science.gov (United States)

    Reed, M. W.; Adams, F. F.

    1980-01-01

    When aluminum tubing having good corrosion resistance and postweld strength is needed, type 5083 alloy should be considered. Chemical composition is carefully controlled and can be drawn into thin-wall tubing with excellent mechanical properties. Uses of tubing are in aircraft, boats, docks, and process equipment.

  11. Sloshing motion dynamics of a free surface in the draft tube cone of a Francis turbine operating in synchronous condenser mode

    Science.gov (United States)

    Vagnoni, Elena; Andolfatto, Loïc; Favrel, Arthur; Avellan, François

    2016-11-01

    The penetration of the electrical grid by intermittent renewable energy sources induces grid fluctuations which must be compensated in order to guarantee the stability of the grid. Hydropower plants can supply reactive power to ensure the grid stabilization by operating in condenser mode. In this operating mode, the turbine operates with the tail water depressed to let the runner spin in air to reduce the power consumption. Pressurized air is injected in the draft tube cone to maintain the water level below the runner and this induces air-water interaction phenomena which cause important power losses. Flow visualization and pressure fluctuation measurements are performed in a reduced scale physical model of a Francis turbine operating in condenser mode to investigate the dynamics of the air-water interaction in the draft tube cone which causes the sloshing motion of the free surface. An image post-processing method is developed, enabling a quantitative description of the sloshing motion. The latter depends on the Froude number. By increasing the value of the Froude number, the amplitude of the sloshing motion decreases, as well as the amplitude of the pressure fluctuations. The frequency of the sloshing motion corresponds to the first natural frequency of the water volume.

  12. Experimental study on heat transfer with condensation of vapors of pure nitrogen tetroxide with nitrogen oxide additions on a bundle of horizontal tubes

    International Nuclear Information System (INIS)

    Batishcheva, T.M.; Derov, B.T.; Kolykhan, L.I.; Pulyaev, V.F.

    1977-01-01

    The results of an experimental investigation of heat transfer during condensation of pure N 2 O 4 vapours and with NO admixtures on the outside surface of a bundle of horizontal tubes are considered. The tests with pure N 2 O 4 have been performed at pressures between 0.3-1.0 MPa in the range of thermal loads 22-121 kW/m 2 , temperature heads of 5-33 grades with complete condensation and evaporation. The content of admixtures boiling at high temperatures do not exceed 0.8%. A concentration of noncondensing nitrogen oxide in a gas phase have changed in the range of 3-27%. It is shown, that a concentration of noncondensible NO doesn't result in a considerable decrease of the heat transfer intensity as well as in the case of condensation of vapour-liquid mixtures. The generalized criterion relations are presented

  13. Creep and stress rupture behaviour of zircaloy-2 and Zr-2.5% Nb alloy tubes at 573 K

    International Nuclear Information System (INIS)

    Laha, K.; Bhanu Sankara Rao, K.; Chandravathi, K.S.; Mannan, S.L.

    1992-01-01

    Zirconium alloys are extensively used for coolant tubes of pressurised heavy water reactors. The choice of these materials is based on their good corrosion resistance in water, low capture cross section for thermal neutrons and good mechanical properties. In this paper the results of an investigation performed on the creep and rupture behaviour of indigenously produced zircaloy-2 and Zr-2.5% Nb alloy are presented. Samples for creep testing were cut longitudinally from finished pressure tubes. Creep rupture tests were carried out in air under constant load conditions at 300 C employing five stress levels in the range 300-360 MPa. Zr-2.5% Nb alloy displayed higher rupture lives at all stress levels compared to zircaloy-2. Steady state creep rate of Zr-2.5%Nb was lower than that zircaloy-2 at identical stress levels. In the stress range of the experiments, the dependence of the steady state creep rate (ε s ) on applied stress (σ) for both the alloys could be represented by a power law, ε s =A σ n The stress sensitivity (n) for Zr-2.5% Nb was lower than that of zircaloy-2. For both the alloys the time to creep rupture t r was found related to the steady state creep rate through the modified Monkman-Grant relation (ε s ) α . t r = constant. Similar value of α was obtained for both the materials. Zr-2.5%Nb exhibited higher ductility (% elongation to rupture) compared to zircaloy-2 at stress levels ≥ 320 MPa. At lower stresses significant difference in ductility was not noticed. Percentage reduction in area was lower in Zr-2.5%Nb at all stress levels indicating better resistance for necking. The time for onset of tertiary was longer for Zr-2.5% Nb alloy. The proportion of life spent by Zr-2.5% Nb in steady state creep regime was higher compared to that of zircaloy-2. Metallographic investigations on longitudinal sections in both the alloys showed large number of intragranular pores close to the fracture surface. A few number of cracks which are characteristic of

  14. Condensation heat transfer coefficient of air-cooled condensing heat exchanger of emergency cooldown tank in long-term passive cooling system

    International Nuclear Information System (INIS)

    Huh, Seon Jeong; Lee, Hee Joon; Moon, Joo Hyung; Bae, Youngmin; Kim, Young In

    2017-01-01

    For the design purpose of air-cooled condensing heat exchanger of emergency cooldown tank, average condensation heat transfer coefficient inside a circular tube was reduced by a thermal sizing program using the experimental data of Kim et al. It was compared to the existing condensation heat transfer correlations. Moreover, a sensitivity analysis of both inside condensation and outside air natural convection correlations was performed. Although condensation heat transfer did not play a great role to design over 10 3 W/m 2 /K, the improved Shah's correlation gives the best prediction for the design. Consequently, air natural convection coefficient significantly affects the design of air-cooled condensing heat exchanger. (author)

  15. Characterization of tube support alloys

    International Nuclear Information System (INIS)

    Vaia, A.R.

    1985-01-01

    The involvement and relationship of carbon steel corrosion products in the tube denting phenomenon promoted an intensive research effort to: 1) understand, reproduce, and arrest the denting process, and 2) evaluate alternative tube support materials to provide additional corrosion resistance. The paper summarizes a corrosion testing program for the verification of type 405 stainless steel under acid or all volatile treatment conditions

  16. Scalable shape- and size-controlled synthesis of metal nano-alloys

    KAUST Repository

    Bakr, Osman M.

    2016-01-21

    Embodiments of the present disclosure provide for a continuous-flow reactor, methods of making metal nano-alloys, and metal nano-alloys. An embodiment of the continuous-flow reactor includes a first tubular component having a tubular inlet and a tubular outlet, and a heated tube-in-tube gas reactor fluidly connected to the first tubular component, wherein the heated tube-in-tube gas reactor comprises an inner tube having a gas permeable surface and an outer tube. An embodiment of the method of producing metal nano-alloys, includes contacting a reducible metal precursor and a reducing fluid in a continuous-flow reactor to form a mixed solution; and flowing the mixed solution through the continuous-flow reactor for a residence time to form the metal nano-alloys. An embodiment of the composition includes a plurality of metal nano-alloys having a monodisperse size distribution and a uniform shape distribution.

  17. Spring/dimple instrument tube restraint

    International Nuclear Information System (INIS)

    DeMario, E.E.; Lawson, C.N.

    1993-01-01

    A nuclear fuel assembly for a pressurized water nuclear reactor has a spring and dimple structure formed in a non-radioactive insert tube placed in the top of a sensor receiving instrumentation tube thimble disposed in the fuel assembly and attached at a top nozzle, a bottom nozzle, and intermediate grids. The instrumentation tube thimble is open at the top, where the sensor or its connection extends through the cooling water for coupling to a sensor signal processor. The spring and dimple insert tube is mounted within the instrumentation tube thimble and extends downwardly adjacent the top. The springs and dimples restrain the sensor and its connections against lateral displacement causing impact with the instrumentation tube thimble due to the strong axial flow of cooling water. The instrumentation tube has a stainless steel outer sleeve and a zirconium alloy inner sleeve below the insert tube adjacent the top. The insert tube is relatively non-radioactivated inconel alloy. The opposed springs and dimples are formed on diametrically opposite inner walls of the insert tube, the springs being formed as spaced axial cuts in the insert tube, with a web of the insert tube between the cuts bowed radially inwardly for forming the spring, and the dimples being formed as radially inward protrusions opposed to the springs. 7 figures

  18. Keeping condensers clean

    Energy Technology Data Exchange (ETDEWEB)

    Wicker, K.

    2006-04-15

    The humble condenser is among the biggest contributors to a steam power plant's efficiency. But although a clean condenser can provide great economic benefit, a dirty one can raise plant heat rate, resulting in large losses of generation revenue and/or unnecessarily high fuel bills. Conventional methods for cleaning fouled tubes range form chemicals to scrapers to brushes and hydro-blasters. This article compares the available options and describes how one power station, Omaha Public Power District's 600 MW North Omaha coal-fired power station, cleaned up its act. The makeup and cooling water of all its five units comes from the Missouri River. 6 figs.

  19. Experimental investigation of thermal-hydraulic performance of PCCS with horizontal tube heat exchangers: single U-tube test

    International Nuclear Information System (INIS)

    Nakamura, Hideo; Anoda, Yoshinari; Arai, Kenji; Kurita, Tomohisa

    2000-01-01

    JAERI and JAPC started a cooperative study to verify performance of a PCCS (Passive Containment Cooling System) using horizontal heat exchanger for next-generation BWR in 1998. A test facility with a horizontal single U-tube was constructed in JAERI in 1999 to investigate fundamental condensation behavior under influences of non-condensable gas. Preliminary pre-test analyses were performed using RELAP5/ MOD3.2.1.2 code to expect the experimental outcomes by incorporating a correlation for condensation degradation because of non-condensable gas by Ueno et al. for better prediction. Preliminary results from both experiments (shakedown) and pre-test analyses indicated that the PCCS using horizontal U-tube heat exchanger is promising. Steam generated under assumed severe accident conditions; steam generation rate approx. = 1% core power, non-condensable gas concentration of 1% and simulated containment vessel pressure of 0.7 MPa, was totally condensed with a small differential pressure across inlet and outlet plenum. Experimental data will be accumulated to develop models and correlations for a better prediction of responses of the PCCS using horizontal heat exchanger during postulated severe accidents. (author)

  20. Experimental research on in-tube condensation in the presence of air

    International Nuclear Information System (INIS)

    Tanrikut, A.; Yesin, O.

    2000-01-01

    In this research work, in-tube condensation in the presence of air is investigated experimentally for different operating conditions, and inhibiting effect of air is analyzed by comparing the experimental data of air/steam mixture with the data of corresponding pure steam cases, with respect to temperature, heat flux, and heat transfer coefficient. The test matrix covers the range of; P=2-6 bar, Re v =45000-94000, and X i =0%-52%. The inhibiting effect of air manifests itself as a remarkable decrease in centerline temperature (10 deg. C - 50 deg. C), depending on inlet air mass fraction. However, the measured centerline temperature is suppressed compared to the predicted one, from the Gibbs-Dalton Law, which indicates that the centerline temperature measurements are highly affected by inner wall thermal conditions, possibly due to narrow channel and high vapor Reynolds number. Even at the lowest air quality (10%) the reduction of the heat flux is 20% while it reaches up to 50% for the quality of 40%. Maximum percent decrease of the heat transfer coefficient was observed in runs with the system pressure of 2 bar; 45% and 65%, for the air mass fraction of 10% and 28%, respectively. (author)

  1. Evolution of grain boundary character distributions in alloy 825 tubes during high temperature annealing: Is grain boundary engineering achieved through recrystallization or grain growth?

    International Nuclear Information System (INIS)

    Bai, Qin; Zhao, Qing; Xia, Shuang; Wang, Baoshun; Zhou, Bangxin; Su, Cheng

    2017-01-01

    Grain boundary engineering (GBE) of nickel-based alloy 825 tubes was carried out with different cold drawing deformations by using a draw-bench on a factory production line and subsequent annealing at various temperatures. The microstructure evolution of alloy 825 during thermal-mechanical processing (TMP) was characterized by means of the electron backscatter diffraction (EBSD) technique to study the TMP effects on the grain boundary network and the evolution of grain boundary character distributions during high temperature annealing. The results showed that the proportion of ∑ 3 n coincidence site lattice (CSL) boundaries of alloy 825 tubes could be increased to > 75% by the TMP of 5% cold drawing and subsequent annealing at 1050 °C for 10 min. The microstructures of the partially recrystallized samples and the fully recrystallized samples suggested that the proportion of low ∑ CSL grain boundaries depended on the annealing time. The frequency of low ∑ CSL grain boundaries increases rapidly with increasing annealing time associating with the formation of large-size highly-twinned grains-cluster microstructure during recrystallization. However, upon further increasing annealing time, the frequency of low ∑ CSL grain boundaries decreased markedly during grain growth. So it is concluded that grain boundary engineering is achieved through recrystallization rather than grain growth. - Highlights: •The grain boundary engineering (GBE) is applicable to 825 tubes. •GBE is achieved through recrystallization rather than grain growth. •The low ∑ CSL grain boundaries in 825 tubes can be increased to > 75%.

  2. The effect of the number of condensed phases modeled on aerosol behavior during an induced steam generator tube rupture sequence

    International Nuclear Information System (INIS)

    Bixler, N.E.; Schaperow, J.H.

    1998-06-01

    VICTORIA is a mechanistic computer code designed to analyze fission product behavior within a nuclear reactor coolant system (RCS) during a severe accident. It provides detailed predictions of the release of radioactive and nonradioactive materials from the reactor core and transport and deposition of these materials within the RCS. A recently completed independent peer review of VICTORIA, while confirming the overall adequacy of the code, recommended a number of modeling improvements. One of these recommendations, to model three rather than a single condensed phase, is the focus of the work reported here. The recommendation has been implemented as an option so that either a single or three condensed phases can be treated. Both options have been employed in the study of fission product behavior during an induced steam generator tube rupture sequence. Differences in deposition patterns and mechanisms predicted using these two options are discussed

  3. Minimize corrosion degradation of steam generator tube materials

    International Nuclear Information System (INIS)

    Lu, Y.

    2006-01-01

    As part of a coordinated program, AECL is developing a set of tools to aid with the prediction and management of steam generator performance. Although stress corrosion cracking (of Alloy 800) has not been detected in any operating steam generator, for life management it is necessary to develop mechanistic models to predict the conditions under which stress corrosion cracking is plausible. Experimental data suggest that all steam generator tube materials are susceptible to corrosion degradation under some specific off-specification conditions. The tolerance to the chemistry upset for each steam generator tube alloy is different. Electrochemical corrosion behaviors of major steam generator tube alloys were studied under the plausible aggressive crevice chemistry conditions. The potential hazardous conditions leading to steam generator tube degradation and the conditions, which can minimize steam generator tube degradation have been determined. Recommended electrochemical corrosion potential/pH zones were defined for all major steam generator tube materials, including Alloys 600, 800, 690 and 400, under CANDU steam generator operating and startup conditions. Stress corrosion cracking tests and accelerated corrosion tests were carried out to verify and revise the recommended electrochemical corrosion potential/pH zones. Based on this information, utilities can prevent steam generator material degradation surprises by appropriate steam generator water chemistry management and increase the reliability of nuclear power generating stations. (author)

  4. Experimental investigation of the sloshing motion of the water free surface in the draft tube of a Francis turbine operating in synchronous condenser mode

    Science.gov (United States)

    Vagnoni, Elena; Favrel, Arthur; Andolfatto, Loïc; Avellan, François

    2018-06-01

    Hydropower units may be required to operate in condenser mode to supply reactive power. In this operating mode, the water level in the turbine or pump-turbine is decreased below the runner by closing the guide vanes and injecting pressurized air. While operating in condenser mode the machine experiences power losses due to several air-water interaction phenomena which cause air losses. One of such phenomena is the sloshing motion of the water free surface below the runner in the draft tube cone of a Francis turbine. The objective of the present work is to experimentally investigate the sloshing motion of the water free surface in the draft tube cone of a reduced scale physical model of a Francis turbine operating in condenser mode. Images acquisition and simultaneous pressure fluctuation measurements are performed and an image processing method is developed to investigate amplitude and frequency of the sloshing motion of the free surface. It is found that this motion is excited at the natural frequency of the water volume and corresponds to the azimuthal wavenumber m = 1 of a rotating gravity wave. The amplitude of the motion is perturbed by wave breaking and it decreases by increasing the densimetric Froude number. The sloshing frequency slightly increases with respect to the natural frequency of the water volume by increasing the densimetric Froude number. Moreover, it results that this resonant phenomenon is not related to the torque perturbation.

  5. A porous media calculation for the isolation condenser heat transfer and circulation

    International Nuclear Information System (INIS)

    Jaakko, Miettinen; Ismo, Karppinen

    2003-01-01

    In the development of advanced light water reactors, thermohydraulic phenomena are versatile in comparison with the present concepts. The new features include, for example, passive safety systems, where energy transport takes place by natural circulation instead of forced flow. In the isolation condenser, the steam generated in the reactor vessel is conduced into the heat transfer tubes. The tube bundle has been submerged into a large water pool, where the heat flux through the tube wall initially is heating the subcooled water, but rather soon boiling take place. The temperature differences and void fraction in the pool create large two-phase circulation. For modeling of the entire condenser a combined application of two types of simulation models has been selected. For the whole geometry, a porous media solution has been developed, where the existence of the heat transfer tubes in the water pool and their heat generation is described by the porous media approach. The 3-dimensional solution of two-phase equations is based on the drift-flux formalism. The condensation and liquid film generation inside the heat transfer tube is modelled using a 1-dimensional model considering the steam core, liquid film and heat transfer tube. The heat flux through the tube wall defines the boundary conditions for the water pool. Parallel to the porous media development for the entire process facility, the phase change models have been improved for Fluent 6 mixture model, and the code is used for analysing in detail the heat transfer around the tubing. The purpose in the analyses is to obtain more detailed information of the flow field and vapour distribution around the tube bundle. By combining the porous media model for the entire facility, with the CFD models for the two-phase flow details around the heat transfer tubes and experimental studies the most important mechanisms around the condensation pool can be gathered. In this context the porous media model is considered. (author)

  6. Bottom nozzle to guide tube connection

    International Nuclear Information System (INIS)

    Bryan, W.J.

    1991-01-01

    This patent describes a nuclear fuel assembly which includes an upper end fitting and a lower end fitting spaced therefrom and connected thereto by elongated guide tubes of one alloy having an open upper end and a closed lower end with spaced fuel element retaining grids mounted on the guide tubes therebetween, the closed lower ends of the guide tubes including a threaded central passageway and the attachment of the guide tubes to the lower end fitting of another alloy. It comprises: an externally threaded bolt with a first end threadably received in the threaded central passageway of the lower end of the guide tube and a head at the other end of the side of the lower end fitting opposite the guide tube; an interruption in the external threads of the bolt which forms a groove which communicates the interior of the guide tube with the side of the lower end fitting opposite the guide tube and enhances its frictional engagement with the threaded central passageway, thereby to hold and attach the guide tube and lower end fitting firmly together, even through a series of temperature cycles

  7. Corrosion in PWR steam generator tubes made of alloy 600TT: overview of operating experience, NDE and safety issues

    International Nuclear Information System (INIS)

    Curieres, I. de; Sollier, T.; Delaval, C.

    2015-01-01

    About 60 PWR plants worldwide are operating with steam generator tubes made of alloy 600TT, among which 27 are located in France. This alloy is susceptible to corrosion, both on the primary and secondary side in every fleet, though with different kinetics or extent. It is noteworthy that many of the primary side corrosion issues can be clearly explained by design or operating conditions. However, studies show that all the secondary side issues are much hardly explained by simple considerations. This paper will give an overview of the international operating experience of this alloy and indicate the associated controllability and safety-related issues. An emphasis will be put on the manufacturing, chemistry and specificities of the different fleets. The French situation will be reviewed in this frame. (authors)

  8. One dimensional analysis model for condensation heat transfer in feed water heater

    International Nuclear Information System (INIS)

    Murase, Michio; Takamori, Kazuhide; Aihara, Tsuyoshi

    1998-01-01

    In order to simplify condensation heat transfer calculations for feed water heaters, one dimensional (1D) analyses were compared with three dimensional (3D) analyses. The results showed that average condensation heat transfer coefficients by 1D analyses with 1/2 rows of heat transfer tubes agreed with those by 3D analyses within 7%. Using the 1D analysis model, effects of the pitch of heat transfer tubes were evaluated. The results showed that the pitch did not affect much on heat transfer rates and that the size of heat transfer tube bundle could be decreased by a small pitch. (author)

  9. Furnace Brazing Parameters Optimized by Taguchi Method and Corrosion Behavior of Tube-Fin System of Automotive Condensers

    Science.gov (United States)

    Guía-Tello, J. C.; Pech-Canul, M. A.; Trujillo-Vázquez, E.; Pech-Canul, M. I.

    2017-08-01

    Controlled atmosphere brazing has a widespread industrial use in the production of aluminum automotive heat exchangers. Good-quality joints between the components depend on the initial condition of materials as well as on the brazing process parameters. In this work, the Taguchi method was used to optimize the brazing parameters with respect to corrosion performance for tube-fin mini-assemblies of an automotive condenser. The experimental design consisted of five factors (micro-channel tube type, flux type, peak temperature, heating rate and dwell time), with two levels each. The corrosion behavior in acidified seawater solution pH 2.8 was evaluated through potentiodynamic polarization and electrochemical impedance spectroscopy (EIS) measurements. Scanning electron microscope (SEM) and energy-dispersive x-ray spectroscopy (EDS) were used to analyze the microstructural features in the joint zone. The results showed that the parameters that most significantly affect the corrosion rate are the type of flux and the peak temperature. The optimal conditions were: micro-channel tube with 4.2 g/m2 of zinc coating, standard flux, 610 °C peak temperature, 5 °C/min heating rate and 4 min dwell time. The corrosion current density value of the confirmation experiment is in excellent agreement with the predicted value. The electrochemical characterization for selected samples gave indication that the brazing conditions had a more significant effect on the kinetics of the hydrogen evolution reaction than on the kinetics of the metal dissolution reaction.

  10. Fireside corrosion testing of candidate superheater tube alloys, coatings, and claddings -- Phase 2 field testing

    Energy Technology Data Exchange (ETDEWEB)

    Blough, J.L. [Foster Wheeler Development Corp., Livingston, NJ (United States)

    1996-08-01

    In Phase 1 of this project, a variety of developmental and commercial tubing alloys and claddings was exposed to laboratory fireside corrosion testing simulating a superheater or reheater in a coal-fired boiler. Phase 2 (in situ testing) has exposed samples of 347, RA85H, HR3C, 253MA, Fe{sub 3}Al + 5Cr, 310 modified, NF 709, 690 clad, and 671 clad for over 10,000 hours to the actual operating conditions of a 250-MW coal-fired boiler. The samples were installed on air-cooled, retractable corrosion probes, installed in the reheater cavity, controlled to the operating metal temperatures of an existing and advanced-cycle, coal-fired boiler. Samples of each alloy are being exposed for 4,000, 12,000, and 16,000 hours of operation. The present results are for the metallurgical examination of the corrosion probe samples after approximately 4,400 hours of exposure.

  11. Development and quality assessments of commercial heat production of ATF FeCrAl tubes

    Energy Technology Data Exchange (ETDEWEB)

    Yamamoto, Yukinori [Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States)

    2015-09-01

    Development and quality assessment of the 2nd generation ATF FeCrAl tube production with commercial manufacturers were conducted. The manufacturing partners include Sophisticated Alloys, Inc. (SAI), Butler, PA for FeCrAl alloy casting via vacuum induction melting, Oak Ridge National Laboratory (ORNL) for extrusion process to prepare the master bars/tubes to be tube-drawn, and Rhenium Alloys, Inc. (RAI), North Ridgeville, OH, for tube-drawing process. The masters bars have also been provided to Los Alamos National Laboratory (LANL) who works with Century Tubes, Inc., (CTI), San Diego, CA, as parallel tube production effort under the current program.

  12. Method of forming magnetostrictive rods from rare earth-iron alloys

    Science.gov (United States)

    McMasters, O. Dale

    1986-09-02

    Rods of magnetrostructive alloys of iron with rare earth elements are formed by flowing a body of rare earth-iron alloy in a crucible enclosed in a chamber maintained under an inert gas atmosphere, forcing such molten rare-earth-iron alloy into a hollow mold tube of refractory material positioned with its lower end portion within the molten body by means of a pressure differential between the chamber and mold tube and maintaining a portion of the molten alloy in the crucible extending to a level above the lower end of the mold tube so that solid particles of higher melting impurities present in the alloy collect at the surface of the molten body and remain within the crucible as the rod is formed in the mold tube.

  13. Importance of crevices formed between tubes and tube plate for the operational behaviour of heat exchangers

    International Nuclear Information System (INIS)

    Achten, N.; Herbsleb, G.; Wieling, N.

    1986-01-01

    It must be guaranteed by construction and manufacture of heat exchangers that primary and secondary medium are completely separated from each other. When this requirement is fullfilled, the operational use of heat exchangers can be impaired by corrosion reactions within the crevice formed between tube and tube plate which may result in corrosion damage. The various techniques which are in use to connect tubes and tube plate and which are described in the present report, must be valued with respect to the tightness of the connection as well as to the formation of crevices between tubes and tube plate. Corrosion resistant copperbase alloys and stainless steels are the most important materials which are in use for the construction of heat exchangers. The mechanisms of crevice corrosion with unalloyed and low alloy carbon steels, stainless steels, and mixed connections between tube and tube plate with these materials are described in detail. Crevice corrosion may be caused also by the formation of galvanic cells between materials of differing electrochemical response. Furthermore, the concentration of aggressive media in crevices between tubes and tube plate can lead to corrosion damage of heat exchanger tubes. For the service operation of heat exchangers without any hazard of corrosion damage in crevices between tubes and tube plate, such crevices must be avoided by proper construction and manufacture. As a model for suitable measures to avoid crevices, the manufacture of steam generators for PWR's is described. (orig.) [de

  14. Simulation of the condensation experiment for the SG primary of SMART with MIDAS/SMR

    Energy Technology Data Exchange (ETDEWEB)

    Park, Jong Hwa; Kim, Dong Ha; Chung, Young Jong; Park, Sun Hee [Korea Atomic Energy Research Institute, Daejeon (Korea, Republic of); Cho, Seong Won [Korea Radiation Technology Institute Co., Daejeon (Korea, Republic of)

    2012-05-15

    SMART is new concept of reactor that all the main components such as the steam generator, the coolant pumps and the pressurizer are located inside the reactor vessel. MIDAS/SMR V1.0.3 code has been used for estimating the severe accident from SMART. SMART has the SG tube with helical shape that is different from that of PWR. MIDAS code has the condensation model for the both sides of surfaces from the various kinds of geometry. But it does not have the condensation model for the helical type of tube. In this study, the condensation experiment for the outer surface of the SG tube in SMART that was performed by Po-Hang university was simulated with MIDAS/SMR under the assumption of straight pipe. The simulation results showed well predictions of the amount of heat removal from the SG tube primary side and thermal hydraulic parameters

  15. Simulation of the condensation experiment for the SG primary of SMART with MIDAS/SMR

    International Nuclear Information System (INIS)

    Park, Jong Hwa; Kim, Dong Ha; Chung, Young Jong; Park, Sun Hee; Cho, Seong Won

    2012-01-01

    SMART is new concept of reactor that all the main components such as the steam generator, the coolant pumps and the pressurizer are located inside the reactor vessel. MIDAS/SMR V1.0.3 code has been used for estimating the severe accident from SMART. SMART has the SG tube with helical shape that is different from that of PWR. MIDAS code has the condensation model for the both sides of surfaces from the various kinds of geometry. But it does not have the condensation model for the helical type of tube. In this study, the condensation experiment for the outer surface of the SG tube in SMART that was performed by Po-Hang university was simulated with MIDAS/SMR under the assumption of straight pipe. The simulation results showed well predictions of the amount of heat removal from the SG tube primary side and thermal hydraulic parameters

  16. Heat transfer enhancement with condensation by surface rotation

    Energy Technology Data Exchange (ETDEWEB)

    Vasiliev, L L; Khrolenok, V V [A.V. Luikov Heat and Mass Transfer Inst., Minsk (Belarus)

    1993-11-01

    Process intensification relies on many unit operations on enhanced heat transfer. One technique for the enhancement of condensation heat transfer is the use of surface rotation. This is particularly effective in reducing the condensate film thickness. The formulae and relationships given in this paper are concerned with rotating discs and tubes, and can be used for developing advanced heat exchanger concepts. (Author)

  17. Repair technology for steam generator tubes

    Energy Technology Data Exchange (ETDEWEB)

    Kim, Seung Ho; Jung, Hyun Kyu; Jung, Seung Ho; Kim, Chang Hoi; Jung, Young Moo; Seo, Yong Chil; Kim, Jung Su; Seo, Moo Hong

    2001-02-01

    The most commonly used sleeving materials are thermally treated Alloy 600 and thermally treated Alloy 690 Alloy. Currently, thermally treated Alloy 690 and Alloy 800 are being offered although Alloy 800 has not been licensed in the US. To install sleeve, joint strength, leak tightness, PWSCC resistance, evaluation on process parameter range and the effect of equipments and procedures on repair plan and radiation damage have to be investigated before sleeving. ABB CE provides three type of leak tight Alloy 690 TIG welded and PLUSS sleeve. Currently, Direct Tube Repair technique using Nd:YAG laser has been developed by ABB CE and Westinghouse. FTI has brazed and kinetic sleeve designs for recirculating steam generator and hydraulic and rolled sleeve designs for one-through steam generators. Westinghouse provides HEJ, brazed and laser welded sleeve design. When sleeve is installed in order to repair the damaged S/G tubes, it is certain that defects can be occurred due to the plastic induced stress and thermal stress. Therefore it is important to minimize the residual stress. FTI provides the electrosleeve technique as a future repair candidate using electroplating.

  18. Repair technology for steam generator tubes

    International Nuclear Information System (INIS)

    Kim, Seung Ho; Jung, Hyun Kyu; Jung, Seung Ho; Kim, Chang Hoi; Jung, Young Moo; Seo, Yong Chil; Kim, Jung Su; Seo, Moo Hong

    2001-02-01

    The most commonly used sleeving materials are thermally treated Alloy 600 and thermally treated Alloy 690 Alloy. Currently, thermally treated Alloy 690 and Alloy 800 are being offered although Alloy 800 has not been licensed in the US. To install sleeve, joint strength, leak tightness, PWSCC resistance, evaluation on process parameter range and the effect of equipments and procedures on repair plan and radiation damage have to be investigated before sleeving. ABB CE provides three type of leak tight Alloy 690 TIG welded and PLUSS sleeve. Currently, Direct Tube Repair technique using Nd:YAG laser has been developed by ABB CE and Westinghouse. FTI has brazed and kinetic sleeve designs for recirculating steam generator and hydraulic and rolled sleeve designs for one-through steam generators. Westinghouse provides HEJ, brazed and laser welded sleeve design. When sleeve is installed in order to repair the damaged S/G tubes, it is certain that defects can be occurred due to the plastic induced stress and thermal stress. Therefore it is important to minimize the residual stress. FTI provides the electrosleeve technique as a future repair candidate using electroplating

  19. Enhancement of heat transfer. The performance of micro-fin tubes

    International Nuclear Information System (INIS)

    Muzzio, A.

    2001-01-01

    Micro-fin tubes are characterised by numerous, very small integral fins that spiral down the inner surface. A very interesting feature of their performance in flow boiling and condensation is a large heat transfer enhancement accompanied by a low pressure drop penalty. This paper presents a general overview of micro-fin tubes and of their performance in evaporation, condensation and single-phase flow [it

  20. Cladding tube manufacturing technology

    International Nuclear Information System (INIS)

    Hahn, R.; Jeong, Y. H.; Baek, B. J.; Kim, K. H.; Kim, S. J.; Choi, B. K.; Kim, J. M.

    1999-04-01

    This report gives an overview of the manufacturing routine of PWR cladding tubes. The routine essentially consists of a series of deformation and annealing processes which are necessary to transform the ingot geometry to tube dimensions. By changing shape, microstructure and structure-related properties are altered simultaneously. First, a short overview of the basics of that part of deformation geometry is given which is related to tube reducing operations. Then those processes of the manufacturing routine which change the microstructure are depicted, and the influence of certain process parameters on microstructure and material properties are shown. The influence of the resulting microstructure on material properties is not discussed in detail, since it is described in my previous report A lloy Development for High Burnup Cladding . Because of their paramount importance still up to now, and because manufacturing data and their influence on properties for other alloys are not so well established or published, the descriptions are mostly related to Zry4 tube manufacturing, and are only in short for other alloys. (author). 9 refs., 46 figs

  1. Open Loop Heat Pipe Radiator Having a Free-Piston for Wiping Condensed Working Fluid

    Science.gov (United States)

    Weinstein, Leonard M. (Inventor)

    2015-01-01

    An open loop heat pipe radiator comprises a radiator tube and a free-piston. The radiator tube has a first end, a second end, and a tube wall, and the tube wall has an inner surface and an outer surface. The free-piston is enclosed within the radiator tube and is capable of movement within the radiator tube between the first and second ends. The free-piston defines a first space between the free-piston, the first end, and the tube wall, and further defines a second space between the free-piston, the second end, and the tube wall. A gaseous-state working fluid, which was evaporated to remove waste heat, alternately enters the first and second spaces, and the free-piston wipes condensed working fluid from the inner surface of the tube wall as the free-piston alternately moves between the first and second ends. The condensed working fluid is then pumped back to the heat source.

  2. Leakproof Swaged Joints in Thin-Wall Tubing

    Science.gov (United States)

    Stuckenberg, F. H.; Crockett, L. K.; Snyder, W. E.

    1986-01-01

    Tubular inserts reinforce joints, reducing incidence of leaks. In new swaging technique, tubular inserts placed inside ends of both tubes to be joined. Made from thicker-wall tubing with outside diameter that matches inside diameter of thin tubing swaged, inserts support tube ends at joint. They ensure more uniform contact between swage fitting and tubing. New swaging technique developed for Al/Ti/V-alloy hydraulic supply lines.

  3. Steam generator tube performance

    International Nuclear Information System (INIS)

    Tatone, O.S.; Pathania, R.S.

    1984-10-01

    A review of the performance of steam generator tubes in 116 water-cooled nuclear power reactors showed that tubes were plugged at 54 (46 percent) of the reactors. The number of tubes removed from service decreased from 4 692 (0.30 percent) in 1981 to 3 222 (0.20 percent) in 1982. The leading causes of tube failures were stress corrosion cracking from the primary side, stress corrosion cracking (or intergranular attack) from the secondary side and pitting corrosion. The lowest incidence of corrosion-induced defects from the secondary side occurred in reactors that have used only volatile treatment, with or without condensate demineralization

  4. Characterization of cylinder liners produced with hypereutectic Al-Si alloys and investigation of corrosion behaviour in synthetic automotive condensed solution

    International Nuclear Information System (INIS)

    Santos, Hamilta de Oliveira

    2006-01-01

    In the present study four hypereutectic Al-Si alloys, three produced by spray forming and one by casting, were characterized for microhardness, roughness, microstructure, texture and corrosion resistance in a synthetic automotive condensed solution (SACS). Two of the spray formed alloys tested were obtained from cylinder liners and the other was laboratory made. Spray forming involves alloy atomization and droplets deposition on a substrate, previous to the solidification of all of the droplets. This process favours the production of materials with a fine microstructure free of macrosegregation that is related to improved hot workability. The microstructure characterization of the four alloys revealed the presence of porosities in the laboratory made alloy. All the three alloys produced by spray forming showed a homogeneous distribution of primary precipitates. The microstructure of one of the alloys showed eutectic microstructure, indicating that this alloy was fabricated by casting. In the cylinder liners, the surface roughness was measured and the microhardness of all the alloys was also evaluated. Furthermore, the laboratory made alloy was hot and cold rolled. Texture determinations were carried out to investigate the correlation between the alloy type and their fabrication process. The texture investigation indicated that the fine distribution of primary silicon phase in the alloy hindered the development of texture typical of aluminium alloys deformation, even after severe mechanical work, such as those used in the conversion of pre-formed in cylinder liners. The surface roughness results indicated typical characteristics of the surface finishing used, honing or chemical etching. The microhardness results were dependent on the fabrication process used, with higher microhardness associated to the eutectic alloy comparatively to the spray formed ones. All hypereutectic alloys were tested for corrosion resistance using electrochemical impedance spectroscopy in

  5. Oxide Dispersion Strengthened Fe3Al-Based Alloy Tubes: Application Specific Development for the Power Generation Industry

    Energy Technology Data Exchange (ETDEWEB)

    Kad, B.K.

    2002-02-08

    A detailed and comprehensive research and development methodology is being prescribed to produce Oxide Dispersion Strengthened (ODS)-Fe{sub 3}Al thin walled tubes, using powder extrusion methodologies, for eventual use at operating temperatures of up to 1100% in the power generation industry. A particular ''in service application'' anomaly of Fe{sub 3}Al-based alloys is that the environmental resistance is maintained up to 1200 C, well beyond where such alloys retain sufficient mechanical strength. Grain boundary creep processes at such high temperatures are anticipated to be the dominant failure mechanism. Thus, the challenges of this program are manifold: (1) to produce thin walled ODS-Fe{sub 3}Al tubes, employing powder extrusion methodologies, with (2) adequate increased strength for service at operating temperatures, and (3) to mitigate creep failures by enhancing the as-processed grain size in ODS-Fe{sub 3}Al tubes. Our research progress till date has resulted in the successful batch production of typically 8 Ft. lengths of 1-3/8 inch diameter, 1/8 inch wall thickness, ODS-Fe{sub 3}Al tubes via a proprietary single step extrusion consolidation process. The process parameters for such consolidation methodologies have been prescribed and evaluated as being routinely reproducible. Such processing parameters (i.e., extrusion ratios, temperature, can design etc.) were particularly guided by the need to effect post-extrusion recrystallization and grain growth at a sufficiently low temperature, while still meeting the creep requirement at service temperatures. Static recrystallization studies show that elongated grains (with their long axis parallel to the extrusion axis), typically 200-2000 {micro}m in diameter, and several millimeters long can be obtained routinely, at 1200 C. The growth kinetics are affected by the interstitial impurity content in the powder batches. For example complete recrystallization, across the tube wall thickness, is

  6. Control of biofouling on titanium condenser tubes with the use of electroless copper plating

    International Nuclear Information System (INIS)

    Anandkumar, B.; George, R.P.; Kamachi Mudali, U.; Ramachandran, D.

    2015-01-01

    In sea water environments titanium condenser tubes face serious issues of biofouling and biomineralization. Electroless plating of nanocopper film is attempted inside the tubes for the control of biofilm formation. Using advanced techniques like AFM, SEM, and XPS, electroless copper plated flat Ti specimens were characterized. Examination of Cu coated Ti surfaces using AFM and SEM showed more reduction in the microroughness compared to anodized Ti surface. Cu 2p 3/2 peak in XPS spectral analysis showed the shift in binding energy inferring the reduction of the hydroxide to metallic copper. Tubular specimens were exposed to sea water up to three months and withdrawn at monthly intervals to evaluate antibacterial activity and long term stability of the coating. Total viable counts and epifluorescence microscopy analyses showed two orders decrease in bacterial counts on copper coated Ti specimens when compared to as polished control Ti specimens. Molecular biology techniques like DGGE and protein expression analysis system were done to get insight into the community diversity and copper tolerance of microorganisms. DGGE gel bands clearly showed the difference in the bacterial diversity inferring from the 16S rRNA gene fragments (V3 regions). Protein analysis showed distinct protein spots appearing in electroless copper coated Ti biofilm protein samples in addition to protein spots common to both the biofilms of Cu coated and as polished Ti. The results indicated copper accumulating proteins in copper resistant bacterial species of biofilm. Reduced microroughness of the surface and toxic copper ions resulted in good biofouling control even after three months exposure to sea water. (author)

  7. IGA resistance of TT Alloy 690 and concentration behavior of Broached Egg Crate tube support configuration

    International Nuclear Information System (INIS)

    Suzuki, S.; Kusakabe, T.; Yamamoto, H.; Arioka, K.; Ochi, T.

    1992-01-01

    In order to improve the reliability of the Steam Generator (SG), TT Alloy 690 and BEC (Broached Egg Crate) type tube support plate has been developed. Some tests are carried out to heighten the reliability for these improvements all the more and the following results are obtained. (1) SERT test (Slow Extension Rate Test) made clear that TT690 has less IGA susceptibility in comparison with MA600. (2) The alkaline susceptibility on the occurrence of IGA/SCC on TT690 and MA600 obtained by SERT corresponds to that obtained by Model Boiler test. (3) By model boiler test, superior concentration behaviors for BEC type tube support plate configuration have been recognized in comparison with Drill type. This result is obtained by the joint research of the five utilities (Kansai Epco, Hokkaido Epco, Shikoku Epco, Kyushu Epco, JAPCO) and MHI

  8. Investigations on the Steam Condensation in a Vertical Tube Geometry

    Energy Technology Data Exchange (ETDEWEB)

    Hwang, Ji-Hwan; Jerng, Dong-wook [Chung-Ang University, Seoul (Korea, Republic of)

    2016-10-15

    In case of accidents that threats containment integrity, such as Station Black Out (SBO), it is able to depressurize containment using exterior-surface condensation in presence of non-condensable gases, which is named as Passive Containment Cooling System (PCCS). It is very important to precisely predict heat removal capability PCCS, as it affects safety and economics. The effect of curvature is not yet experimentally and numerically studied. It is reported that the effect of curvature exists at single-phase condition, yet it is not studied that if it can applicable to two-phase condensation in presence of non-condensables. In this paper, various experimental data are collected to analyze if it is able to observe curvature effect. However, it is hard to analyze experimental data, as the geometry, experimental conditions and means of measurement differs. To check if the differences between experiments are curvature effect, each experiment is compared with CFD simulation result using a commercial CFD code, STAR-CCM+. In this paper, with correlations derived from prior studies, we found the existence of curvature effect under PCCS operating condition. However, it is unable to find out a clear curvature effect at experiment data as they scatter much. As a means of comparison reference between experiment, CFD code is used. From comparison between CFD and experiment, we could confirm the existence of curvature effect. However, measured heat transfer coefficients of Kawakubo’s experiment are relatively low, whereas Dehbi’s measurement data are relatively high. Also, considering that usage of eq. overly supplies steam to condensing shell region, heat transfer coefficients of Pan Tong’s measured relatively high, but not as much that of Dehbi’s. A further experimental identification is needed for evaluation. Currently, CFD code calculates the curvature effect. Overall trend versus air mass fraction is similar with average of experiment.

  9. Eddy current testing device for metallic tubes at least locally curved

    International Nuclear Information System (INIS)

    Pigeon, Marcel; Vienot, Claude.

    1975-01-01

    Steam generators, condensers and heat exchangers generally consist of metallic tube bundles, the tubes having a complex geometry. The invention concerns an Eddy current testing device for metallic tubes at least locally curved, operating by translation of a probe inside the tubes [fr

  10. Air-cooled steam condensers non-freeze warranties

    Energy Technology Data Exchange (ETDEWEB)

    Larinoff, M.W.

    1995-09-01

    What this paper is suggesting is the seller quote a condenser package with a LIMITED NON-FREEZE WARRANTY. Relieve the inexperienced buyer of the responsibility for selecting freeze protection design options. The seller cannot afford to over-design because of the added costs and the need for a competitive price. Yet he cannot under-design and allow the condenser tubes to freeze periodically and then pay the repair bills in accordance with the warranty.

  11. Corrosion and Rupture of Steam Generator Tubings in PWRs

    Energy Technology Data Exchange (ETDEWEB)

    Hwang, Seong Sik; Kim, Hong Pyo

    2007-08-15

    This report is intended to provide corrosion engineers in the filed of nuclear energy with information on the corrosion and rupture behavior of steam generator tubing in PWRs. Various types of corrosion in PWR steam generator tubing have been reported all around the world, and countermeasures such as the addition of corrosion inhibitors, a water chemistry control, a tube plugging and sleeving have been applied. Steam generators equipped with alloy 600 tubing, which are not so resistant to a stress corrosion cracking (SCC), have generally been replaced with new steam generators made of alloy 690 TT (Thermally treated). Pull tube examination results which were performed of KAERI are summarized. The tubes were affected by a pitting, SCC, and a denting. Nondestructive examination method for the tubes and repair techniques are also reviewed. In addition, the regulatory guidance of some countries are reviewed. As a part of a tube integrity project in Korea, some results on a tube rupture and leak behaviors for axial cracks are also mentioned.

  12. Corrosion and Rupture of Steam Generator Tubings in PWRs

    International Nuclear Information System (INIS)

    Hwang, Seong Sik; Kim, Hong Pyo

    2007-08-01

    This report is intended to provide corrosion engineers in the filed of nuclear energy with information on the corrosion and rupture behavior of steam generator tubing in PWRs. Various types of corrosion in PWR steam generator tubing have been reported all around the world, and countermeasures such as the addition of corrosion inhibitors, a water chemistry control, a tube plugging and sleeving have been applied. Steam generators equipped with alloy 600 tubing, which are not so resistant to a stress corrosion cracking (SCC), have generally been replaced with new steam generators made of alloy 690 TT (Thermally treated). Pull tube examination results which were performed of KAERI are summarized. The tubes were affected by a pitting, SCC, and a denting. Nondestructive examination method for the tubes and repair techniques are also reviewed. In addition, the regulatory guidance of some countries are reviewed. As a part of a tube integrity project in Korea, some results on a tube rupture and leak behaviors for axial cracks are also mentioned

  13. Experimental investigation on enhanced heat transfer of vertical condensers with trisection helical baffles

    International Nuclear Information System (INIS)

    Wu, Jiafeng; Zhou, Jiahao; Chen, Yaping; Wang, Mingchao; Dong, Cong; Guo, Ya

    2016-01-01

    Highlights: • Trisection helical baffles are introduced for vertical condenser enhancement. • Condensation in short-section and intermediate drainage is applied in new schemes. • Helical baffles with liquid dam and drainage gaps can promote condenser performance. • Dual-thread baffle scheme is superior to that of single-thread one by about 19%. • Condensation enhancement ratio of helical schemes is 1.5–2.5 over segment one. - Abstract: The vertical condensers have advantages of small occupation area, convenient in assemble or dismantle tube bundle and simple structure etc. However, the low heat transfer performance limits their applications. To enhance the heat transfer, a novel type of vertical condensers was designed by introducing trisection helical baffles with liquid dams and gaps for facilitating condensate drainage. Four configurations of vertical condensers with trisection helical baffle are experimentally studied and compared to a traditional segment baffle condenser. The enhancement ratio of trisection helical baffle schemes is about 1.5–2.5 and the heat transfer coefficient of the dual-thread trisection helical baffle scheme is superior to that of the single-thread one by about 19%. Assistant by the theoretical study, the experimental data is simulated and the condensation enhancement mechanisms by applying trisection helical baffle in vertical condenser are summarized as condensate drainage, short tube construct and reduce steam dead zone functions of the helical baffles.

  14. Deposition of magnetite particles onto alloy-800 steam generator tubes

    Energy Technology Data Exchange (ETDEWEB)

    Basset, M.; Arbeau, N.; McInerney, J.; Lister, D.H. [Univ. of New Brunswick, Dept. of Chemical Engineering, Fredericton, NB (Canada)

    1998-07-01

    Fouling is a particularly serious problem in the power generating industry. Deposits modify the thermalhydraulic characteristics of heat transfer surfaces by changing the resistance to heat transfer and the resistance to fluid flow, and, if thick enough, can harbour aggressive chemicals. Deposits are also implicated in the increase of radiation fields around working areas in the primary heat transfer systems of nuclear power plants. In order to understand the preliminary steps of the formation of corrosion product deposits on the outsides of steam generator tubes, a laboratory program has investigated the deposition of magnetite particles from suspension in water onto Alloy-800 surfaces under various conditions of flow, chemistry and boiling heat transfer. A recirculating loop made of stainless steel operating at less than 400kPa pressure, with a nominal coolant temperature of 90 degrees C, was equipped with a vertical glass column which housed a 2.5E-01m-long Alloy-800 boiler tube capable of generating a heat flux of 240kW/m{sup 2} . A concentration of suspended magnetite of 5.0E-03kg/m{sup 3} was maintained in the recirculating coolant, which was maintained at a pH of 7.5. The magnetite was synthesized with a sol-gel process, which was developed to produce reproducibly monodispersed, colloidal (<1{mu}m) and nearly spherical particles. A radiotracing method was used to characterize the deposit evolution with time and to quantify the removal of magnetite particles. The results from a series of deposition experiments are presented here. The deposition process is described in terms of a two-step mechanism: the transport step, involving the transport from the bulk of the liquid to the vicinity of the surface, followed by the attachment step, involving the attachment of the particle onto the surface. Under non-boiling heat transfer conditions, diffusion seems to be the dominant factor ruling deposition with a small contribution from thermophoresis; removal was

  15. Deposition of magnetite particles onto alloy-800 steam generator tubes

    International Nuclear Information System (INIS)

    Basset, M.; Arbeau, N.; McInerney, J.; Lister, D.H.

    1998-01-01

    Fouling is a particularly serious problem in the power generating industry. Deposits modify the thermalhydraulic characteristics of heat transfer surfaces by changing the resistance to heat transfer and the resistance to fluid flow, and, if thick enough, can harbour aggressive chemicals. Deposits are also implicated in the increase of radiation fields around working areas in the primary heat transfer systems of nuclear power plants. In order to understand the preliminary steps of the formation of corrosion product deposits on the outsides of steam generator tubes, a laboratory program has investigated the deposition of magnetite particles from suspension in water onto Alloy-800 surfaces under various conditions of flow, chemistry and boiling heat transfer. A recirculating loop made of stainless steel operating at less than 400kPa pressure, with a nominal coolant temperature of 90 degrees C, was equipped with a vertical glass column which housed a 2.5E-01m-long Alloy-800 boiler tube capable of generating a heat flux of 240kW/m 2 . A concentration of suspended magnetite of 5.0E-03kg/m 3 was maintained in the recirculating coolant, which was maintained at a pH of 7.5. The magnetite was synthesized with a sol-gel process, which was developed to produce reproducibly monodispersed, colloidal (<1μm) and nearly spherical particles. A radiotracing method was used to characterize the deposit evolution with time and to quantify the removal of magnetite particles. The results from a series of deposition experiments are presented here. The deposition process is described in terms of a two-step mechanism: the transport step, involving the transport from the bulk of the liquid to the vicinity of the surface, followed by the attachment step, involving the attachment of the particle onto the surface. Under non-boiling heat transfer conditions, diffusion seems to be the dominant factor ruling deposition with a small contribution from thermophoresis; removal was considered

  16. Influences of Alloying Element and Annealing on the Microstructure and Corrosion Resistance of Steam Generator Tubing Materials of Nuclear Power Plant (I)

    International Nuclear Information System (INIS)

    Kim, Young Sik; Pari, Yong Soo; Kuk, Il Hiun

    1996-01-01

    Influences of alloying elements and annealing heat treatments on Alloy 690 and Alloy 600 for steam generator tubing materials of nuclear power plants were studied. OM, SEM, TEM, and XRD analyses were used to study the microstructural changes of the alloys. Mechanical properties were investigated by means of tension tests and Rockwell hardness tests, and corrosion resistance was evaluated using the anodic polarization tests and the 65% boiling nitric acid immersion tests. Increasing the carbon content of Alloy 690, the hardness and tensile strength were increased, but the elongation and grain size were decreased. However, increasing the annealing temperature, the tensile strength and hardness were decreased, but the elongation and grain size were increased. Increasing the carbon content of Alloy 690, the results of the anodic polarization tests and the nitric acid immersion tests showed that the annealing temperature to reveal a minimum corrosion rate was increased. This behavior seemed to be due to the combination of the solid solution of carbon in the matrix and grain growth with annealing. In this work, the corrosion properties of Alloy 690 were better than that of Alloy 600, and the range of the optimum annealing temperature of Alloy 690 was from 1100 .deg. C to 1150 .deg. C

  17. Methods for batch fabrication of cold cathode vacuum switch tubes

    Science.gov (United States)

    Walker, Charles A [Albuquerque, NM; Trowbridge, Frank R [Albuquerque, NM

    2011-05-10

    Methods are disclosed for batch fabrication of vacuum switch tubes that reduce manufacturing costs and improve tube to tube uniformity. The disclosed methods comprise creating a stacked assembly of layers containing a plurality of adjacently spaced switch tube sub-assemblies aligned and registered through common layers. The layers include trigger electrode layer, cathode layer including a metallic support/contact with graphite cathode inserts, trigger probe sub-assembly layer, ceramic (e.g. tube body) insulator layer, and metallic anode sub-assembly layer. Braze alloy layers are incorporated into the stacked assembly of layers, and can include active metal braze alloys or direct braze alloys, to eliminate costs associated with traditional metallization of the ceramic insulator layers. The entire stacked assembly is then heated to braze/join/bond the stack-up into a cohesive body, after which individual switch tubes are singulated by methods such as sawing. The inventive methods provide for simultaneously fabricating a plurality of devices as opposed to traditional methods that rely on skilled craftsman to essentially hand build individual devices.

  18. Influence of surface condition on the corrosion resistance of copper alloy condenser tubes in sea water

    Energy Technology Data Exchange (ETDEWEB)

    Sato, S; Nagata, K; Yamauchi, S

    1979-07-01

    Investigation was made on the influence of various surface conditions of aluminum brass tube. The corrosion behavior of aluminum brass tube, with nine kinds of surface conditions, was studied in stagnant 0.1N NaHCo/sub 3/ solution and flowing sea water (natural, Fe/sup + +/ containing and S/sup - -/ containing water). Surface treatments investigated contained bright annealing, special annealing to form carbon film, hot oxidizing and pickling. Anodic polarization measurements in 0.1N NaHCO/sub 3/ solution showed that the oxidized surface was superior and that the pickled surface was inferior. However, relation between these characteristics and corrosion resistance in sea water has not been established. Electrochemical characteristics in flowing sea water were dependent on the surface conditions in the very beginning of immersion time; nobler corrosion potential for the surface with carbon film, higher polarization resistance for the bright annealed and the oxidized surface, and faster decrease of polarization resistance in S/sup - -/ containing sea water for the pickled surface. However, these differences disappeared in the immersion time of only 2 to 7 days. It was revealed, by the statistical analysis on the corrosion depth in corrosion test in flowing sea water and in jet impingement test, that the corrosion behavior was not influenced by surface conditions, but was significantly influenced by quality of sea water and sponge ball cleaning. Sulfide ion of 0.05 ppm caused severe pitting corrosion, and sponge ball cleaning of 5 chances a week caused erosion corrosion. From above results, it was concluded that surface conditions of aluminum brass were not important to sea water corrosion, and that quality of sea water and operating condition such as sponge ball cleaning were more significant.

  19. Steam generator tube performance

    International Nuclear Information System (INIS)

    Tatone, O.S.; Pathania, R.S.

    1982-04-01

    The performance of steam generator tubes in water-cooled nuclear power reactors has been reviewed for 1980. Tube defects occurred at 38% of the 97 reactors surveyed. This is a marginal improvement over 1979 when defects occurred at 41% of the reactors. The number of failed tubes was also lower, 0.14% of the tubes in service in 1980 compared with 0.20% of those in service in 1979. Analysis of the causes of these failures indicates that stress corrosion cracking was the leading failure mechanism. Reactors that used all-volatile treatment of secondary water, with or without full-flow condensate demineralization since start-up showed the lowest incidence of corrosion-related defects

  20. Stress relief to prevent stress corrosion in the transition region of expanded Alloy 600 steam-generator tubing. Final report

    International Nuclear Information System (INIS)

    Woodward, J.; van Rooyen, D.

    1983-05-01

    The feasibility of preventing primary side roll transition cracking has been investigated, using induction heating to attain stress relief of expanded Ni-Cr-Fe Alloy 600 steam generator tubing. Work on rolled tubing and U-bends has shown that temperatures with which stress relief can be obtained range from 700 to 850 0 C, with lower temperatures in this range requiring longer times at temperature to provide the requisite reduction in residual stresses. No work has yet been done outside this range. Preliminary tests, using induction heating, have been carried out on a mock tube sheet assembly, designed to the dimensions of a typical steam generator, and have identified the type of heating/cooling cycle that would occur in the tube sheet during a stress relief operation. Preliminary results show that the times to reach the higher temperatures in the range observed to give stress relief, of the order of 850 0 C, can be as short as 8 seconds, and less with optimum coil design and power control

  1. Heat removal capability of divertor coaxial tube assembly

    International Nuclear Information System (INIS)

    Shibui, Masanao; Nakahira, Masataka; Tada, Eisuke; Takatsu, Hideyuki

    1994-05-01

    To deal with high power flowing in the divertor region, an advanced divertor concept with gas target has been proposed for use in ITER/EDA. The concept uses a divertor channel to remove the radiated power while allowing neutrals to recirculate. Candidate channel wall designs include a tube array design where many coaxial tubes are arranged in the toroidal direction to make louver. The coaxial tube consists of a Be protection tube encases many supply tubes wound helically around a return tube. V-alloy and hardened Cu-alloy have been proposed for use in the supply and return tubes. Some coolants have also been proposed for the design including pressurized He and liquid metals, because these coolants are consistent with the selection of coolants for the blanket and also meet the requirement of high temperature operation. In the coaxial tube design, the coolant area is restricted and brittle Be material is used under severe thermal cyclings. Thus, to obtain the coaxial tube with sufficient safety margin for the expected fusion power excursion, it is essential to understand its applicability limit. The paper discusses heat removal capability of the coaxial tube and recommends some design modifications. (author)

  2. The effect lead impurities on the corrosion resistance of alloy 600 and alloy 690 in high temperature water

    International Nuclear Information System (INIS)

    Sakai, T.; Nakagomi, N.; Kikuchi, T.; Aoki, K.; Nakayasu, F.; Yamakawa, K.

    1998-01-01

    Degradation of nickel-based alloy steam generator (SG) tubing caused by lead-induced corrosion has been reported recently in some PWR plants. Several laboratory studies also have shown that lead causes intergranular or transgranular stress corrosion cracking (IGSCC or TGSCC) of the tubing materials. Information from previous studies suggests two possible explanations for the mechanism of lead-induced corrosion. One is selective dissolution of tube metal elements, resulting in formation of a lead-containing nickel-depleted oxide film as observed in mildly acidic environments. The other explanation is an increase in potential, as has been observed in lead-contaminated caustic environments, although not in all volatile treatment (AVT) water such as the ammonium-hydrazine water chemistry. These observation suggest that an electrochemical reaction between metal elements and dissolved lead might be the cause of lead-induced corrosion. The present work was undertaken to clarify the lead-induced corrosion mechanism of nickel-based alloys from an electrochemical viewpoint, focusing on mildly acidic and basic environments. These are the probable pH conditions in the crevice region between the tube and tube support plate of the SG where corrosion damage could occur. Measurements of corrosion potential and electrochemical polarization of nickel-based alloys were performed to investigate the effect of lead on electrochemical behavior of the alloys. Then, constant extension rate tests (CERT) were carried out to determine the corrosion susceptibility of the alloys in a lead-contaminated environment. (J.P.N.)

  3. Characteristics of hydrostatically extruded Zr-2.5Nb alloy

    International Nuclear Information System (INIS)

    Jie, Z.; Jiaqi, D.; Tieqi, Y.; Wenxian, H.; Yan, L.; Yunxia, Z.; Zhenhe, L.

    1984-01-01

    Hydrostatic extrusion is a new production technology. Zr-2.5Nb alloy tubes cold hydrostatically extruded possess excellent mechanical properties similar to heat-treated tubes and better than cold-worked tubes. Examination by transmission electron microscope shows that the alloy is of a uniform cell substructure containing the (α + β) phases, which is one of important factors improving properties of the alloy. The study of texture, stress, and reorientation of the hydride shows that hydrostatically extruded tubes with basal plane normals in the radial direction have obviously higher hydride reorientation threshold stress than tubes with basal plane normals in the circumferential direction. Moreover, investigation of fracture toughness reveals that hydride distributed perpendicular to the crack propagation direction restrains further propagation of the crack. It is favorable for preserving the fracture resistance of the material

  4. Recovery of Water from Boiler Flue Gas Using Condensing Heat Exchangers

    Energy Technology Data Exchange (ETDEWEB)

    Edward Levy; Harun Bilirgen; John DuPoint

    2011-03-31

    Most of the water used in a thermoelectric power plant is used for cooling, and DOE has been focusing on possible techniques to reduce the amount of fresh water needed for cooling. DOE has also been placing emphasis on recovery of usable water from sources not generally considered, such as mine water, water produced from oil and gas extraction, and water contained in boiler flue gas. This report deals with development of condensing heat exchanger technology for recovering moisture from flue gas from coal-fired power plants. The report describes: (1) An expanded data base on water and acid condensation characteristics of condensing heat exchangers in coal-fired units. This data base was generated by performing slip stream tests at a power plant with high sulfur bituminous coal and a wet FGD scrubber and at a power plant firing high-moisture, low rank coals. (2) Data on typical concentrations of HCl, HNO{sub 3} and H{sub 2}SO{sub 4} in low temperature condensed flue gas moisture, and mercury capture efficiencies as functions of process conditions in power plant field tests. (3) Theoretical predictions for sulfuric acid concentrations on tube surfaces at temperatures above the water vapor dewpoint temperature and below the sulfuric acid dew point temperature. (4) Data on corrosion rates of candidate heat exchanger tube materials for the different regions of the heat exchanger system as functions of acid concentration and temperature. (5) Data on effectiveness of acid traps in reducing sulfuric acid concentrations in a heat exchanger tube bundle. (6) Condensed flue gas water treatment needs and costs. (7) Condensing heat exchanger designs and installed capital costs for full-scale applications, both for installation immediately downstream of an ESP or baghouse and for installation downstream of a wet SO{sub 2} scrubber. (8) Results of cost-benefit studies of condensing heat exchangers.

  5. Recovery of Water from Boiler Flue Gas Using Condensing Heat Exchangers

    Energy Technology Data Exchange (ETDEWEB)

    Levy, Edward; Bilirgen, Harun; DuPont, John

    2011-03-31

    Most of the water used in a thermoelectric power plant is used for cooling, and DOE has been focusing on possible techniques to reduce the amount of fresh water needed for cooling. DOE has also been placing emphasis on recovery of usable water from sources not generally considered, such as mine water, water produced from oil and gas extraction, and water contained in boiler flue gas. This report deals with development of condensing heat exchanger technology for recovering moisture from flue gas from coal-fired power plants. The report describes: • An expanded data base on water and acid condensation characteristics of condensing heat exchangers in coal-fired units. This data base was generated by performing slip stream tests at a power plant with high sulfur bituminous coal and a wet FGD scrubber and at a power plant firing highmoisture, low rank coals. • Data on typical concentrations of HCl, HNO{sub 3} and H{sub 2}SO{sub 4} in low temperature condensed flue gas moisture, and mercury capture efficiencies as functions of process conditions in power plant field tests. • Theoretical predictions for sulfuric acid concentrations on tube surfaces at temperatures above the water vapor dewpoint temperature and below the sulfuric acid dew point temperature. • Data on corrosion rates of candidate heat exchanger tube materials for the different regions of the heat exchanger system as functions of acid concentration and temperature. • Data on effectiveness of acid traps in reducing sulfuric acid concentrations in a heat exchanger tube bundle. • Condensed flue gas water treatment needs and costs. • Condensing heat exchanger designs and installed capital costs for full-scale applications, both for installation immediately downstream of an ESP or baghouse and for installation downstream of a wet SO{sub 2} scrubber. • Results of cost-benefit studies of condensing heat exchangers.

  6. Influence of hydrogen content on fracture toughness of CWSR Zr-2.5Nb pressure tube alloy

    Science.gov (United States)

    Singh, R. N.; Bind, A. K.; Srinivasan, N. S.; Ståhle, P.

    2013-01-01

    In this work, influence of hydrogen and temperature on the fracture toughness parameters of unirradiated, cold worked and stress relieved (CWSR) Zr-2.5Nb pressure tube alloys used in Indian Pressurized Heavy Water Reactor is reported. The fracture toughness tests were carried out using 17 mm width curved compact tension specimens machined from gaseously hydrogen charged tube-sections. Metallography of the samples revealed that hydrides were predominantly oriented along axial-circumferential plane of the tube. Fracture toughness tests were carried out in the temperature range of 30-300 °C as per ASTM standard E-1820-06, with the crack length measured using direct current potential drop (DCPD) technique. The fracture toughness parameters (JQ, JMax and dJ/da), were determined. The critical crack length (CCL) for catastrophic failure was determined using a numerical method. It was observed that for a given test temperature, the fracture toughness parameters representing crack initiation (JQ) and crack propagation (JMax, and dJ/da) is practically unaffected by hydrogen content. Also, for given hydrogen content, all the aforementioned fracture toughness parameters increased with temperature to a saturation value.

  7. Determination of condensation nuclei using a modified Aitken method

    International Nuclear Information System (INIS)

    Kubie, G.; Schless, D.

    1981-01-01

    A test set-up for ultra-microscopic detection of condensation nuclei according to the Aitken-method is described, and it is shown that due to the delay of a video camera tube the video-technique allows to store flashlight shots of condensation particles such as they occur in an expansion cloud chamber. The possibilities resulting from that technique are stated. (orig.) [de

  8. The stress-rupture behavior of tubes made from austenitic stainless steels and Ni-based alloys subjected to internal pressure

    International Nuclear Information System (INIS)

    Schaefer, L.; Kempe, H.

    1983-12-01

    The report outlines the stress-rupture results obtained on tubes tested as possible fuel rod cladding tubes for fast breeder reactors cooled with sodium, steam or gas. For the rupture elongations of some specimens showing a pronounced burst, higher values than in earlier reports are now indicated because of better evaluation techniques. The choice and comparisons of materials are explained, the calculations of stresses and strains are described, and reference is made to the own studies carried out to date of the parameters influencing creep-rupture behaviour. Minor modifications of the composition of an alloy and of the mechanical-thermal treatment of materials, respectively, are seen to produce clearcut changes in the stress-rupture properties. (orig.) [de

  9. Assessment and improvement of condensation model in RELAP5/MOD3

    Energy Technology Data Exchange (ETDEWEB)

    Rho, Hui Cheon; Choi, Kee Yong; Park, Hyeon Sik; Kim, Sang Jae [Korea Advanced Institute of Science and Technology, Taejon (Korea, Republic of); Lee, Sang Il [Korea Power Engineering Co., Inc., Seoul (Korea, Republic of)

    1997-07-15

    The objective of this research is to remove the uncertainty of the condensation model through the assessment and improvement of the various heat transfer correlations used in the RELAP5/MOD3 code. The condensation model of the standard RELAP5/MOD3 code is systematically arranged and analyzed. A condensation heat transfer database is constructed from the previous experimental data on various condensation phenomena. Based on the constructed database, the condensation models in the code are assessed and improved. An experiment on the reflux condensation in a tube of steam generator in the presence of noncondensable gases is planned to acquire the experimental data.

  10. Experimental Investigation of Flow Condensation in Microgravity

    Science.gov (United States)

    Lee, Hyoungsoon; Park, Ilchung; Konishi, Christopher; Mudawar, Issam; May, Rochelle I.; Juergens, Jeffery R.; Wagner, James D.; Hall, Nancy R.; Nahra, Henry K.; Hasan, Mohammed M.; hide

    2013-01-01

    Future manned missions to Mars are expected to greatly increase the space vehicle's size, weight, and heat dissipation requirements. An effective means to reducing both size and weight is to replace single-phase thermal management systems with two-phase counterparts that capitalize upon both latent and sensible heat of the coolant rather than sensible heat alone. This shift is expected to yield orders of magnitude enhancements in flow boiling and condensation heat transfer coefficients. A major challenge to this shift is a lack of reliable tools for accurate prediction of two-phase pressure drop and heat transfer coefficient in reduced gravity. Developing such tools will require a sophisticated experimental facility to enable investigators to perform both flow boiling and condensation experiments in microgravity in pursuit of reliable databases. This study will discuss the development of the Flow Boiling and Condensation Experiment (FBCE) for the International Space Station (ISS), which was initiated in 2012 in collaboration between Purdue University and NASA Glenn Research Center. This facility was recently tested in parabolic flight to acquire condensation data for FC-72 in microgravity, aided by high-speed video analysis of interfacial structure of the condensation film. The condensation is achieved by rejecting heat to a counter flow of water, and experiments were performed at different mass velocities of FC-72 and water and different FC-72 inlet qualities. It is shown that the film flow varies from smooth-laminar to wavy-laminar and ultimately turbulent with increasing FC-72 mass velocity. The heat transfer coefficient is highest near the inlet of the condensation tube, where the film is thinnest, and decreases monotonically along the tube, except for high FC-72 mass velocities, where the heat transfer coefficient is enhanced downstream. This enhancement is attributed to both turbulence and increased interfacial waviness. One-ge correlations are shown to

  11. Water nucleation : wave tube experiments and theoretical considerations

    NARCIS (Netherlands)

    Holten, V.

    2009-01-01

    This work is an experimental and theoretical study of the condensation of water. Condensation consists of nucleation – the formation of droplets – and the subsequent growth of those droplets. In our expansion tube setup, these processes are separated in time with the nucleation pulse principle, in

  12. The influence of lead on stress corrosion cracking of steam generator tubing

    International Nuclear Information System (INIS)

    Ryan Curtis Wolfe

    2015-01-01

    Lead (Pb) is present at low concentrations on the secondary side of steam generators, but is known to accumulate in steam generator sludge and become concentrated in crevices and cracks. Pb is known to have played a role in the degradation of Alloy 600MA tubing, necessitating the replacement of those steam generators. There is new evidence which indicates that Pb has also played a role in the stress corrosion cracking (SCC) of Alloy 600TT. Furthermore. laboratory testing indicates that advanced tubing alloys such as Alloy 690TT and Alloy 800NG area also susceptible to this attack. In response to these vulnerabilities, utilities are attempting to manufacture tubing using processes which will impart optimal corrosion resistance, fabricate and operate SG's to minimize stress in the tubing, undertake efforts to identify and remove the sources of Pb, reduce the existing inventory of Pb using chemical or mechanical cleaning processes, and maintain rigorous chemistry controls. Research is warranted to qualify chemical methods to mitigate PbSCC that may be observed in service. This presentation will review work performed through the Electric Power Research Institute (EPRI) to address the issue of Pb-assisted stress corrosion cracking of steam generator tubing. (author)

  13. Flow Analysis of Isobutane (R-600A) Inside AN Adiabatic Capillary Tube

    Science.gov (United States)

    Alok, Praveen; Sahu, Debjyoti

    2018-02-01

    Capillary tubes are simple narrow tubes but the phase change which occurs inside the capillary tubes is complex to analyze. In the present investigation, an attempt is made to analyze the flow of Isobutane (R-600a) inside the coiled capillary tubes for different load conditions by Homogeneous Equilibrium Model. The Length and diameter of the capillary tube not only depend on the pressure and temperature of the condenser and evaporator but also on the cooling load. The present paper investigates the change in dimensions of the coil capillary tube with respect to the change in cooling load on the system for the constant condenser and evaporator conditions. ANSYS CFX (Central Florida Expressway) software is used to study the flow characteristics of the refrigerant. Appropriate helical coil is selected for this analysis.

  14. Microstructure and textural characterization of hot extruded Zr-2.5Nb alloy PHWR pressure tube fabricated by various ingot processing route

    International Nuclear Information System (INIS)

    Vaibhaw, Kumar; Jha, S.K.; Saibaba, N.; Neogy, S.; Mani Krishna, K.V.; Srivastava, D.; Dey, G.K.

    2011-01-01

    Zr-2.5 Nb alloys finds its applications as a pressure tube component in pressure tube type thermal reactors such as PHWRs and RBMK due to properties attributed such as low neutron absorption cross section, high temperature strength and corrosion resistance etc. Manufacturing of this life time components involves series of thermo-mechanical processes of hot working and cold working with intermediate annealing. The life time of Pressure tube are limited due to their diametral creep properties which is governed by metallurgical characteristics such as texture, microstructure dislocation density etc. The primary breakdown of cast structure in Vacuum Arc Melted ingot can be effected by either hot extrusion or forging in single or multiple stages before final hot extrusion step into the blank for manufacturing of seamless pressure tube. Elevated temperature deformation carried out in hot working above the recrystallization temperature would enable impositions of large strains in single step. This deformation causes a significant change in the microstructure of the material and depends on process parameters such as extrusion ratio, temperature and strain rate. Basic microstructure developed at this deformation stage has significant bearing on the final properties of the material fabricated with subsequent cold working steps. The major texture in α+β Zr-2.5 Nb alloy is established during final extrusion to blank which does not change significantly during subsequent cold pilgering. However, microstructure is modified significantly in subsequent cold working which can be effected by cold pilgering or cold drawing in single or multiple steps. Present paper brings out the various ingot processing routes using forging and or extrusion followed for fabrication of pressure tubes. The development of texture and microstructures has been discussed at the blank stage from these processing routes and also with respect to varying extrusion variable such as extrusion ratio

  15. Continuous condensation device for vapors in the atmosphere

    International Nuclear Information System (INIS)

    Tricot, M.

    1983-01-01

    The continuous condensation device for vapors from the atmosphere is such those in which this atmosphere circulates in contact with a cold source involving the condensation of these vapors. It includes a thermoelectric module using the Peltier effect; the hot side is bonded to a heat sink and the cold side is in contact with an insulated condensation chamber in which flows the atmosphere charged with vapors to be condensated. The condensation chamber has a metallic structure through which a low voltage direct current is passed; this structure has small blades with holes, through which the condensate flows under gravity in the lower part of the chamber which have a hole to evacuate this liquid. The thermoelectric module comprises an assembly of thermocouples made of an array of alloy plates. The temperature inside the condensation chamber is maintained at just above 0 0 C. This device is used for the sampling of atmosphere water especially in the determination of tritium content of the atmosphere around nuclear installations [fr

  16. Comparison of evaluation method for planar flaw in pressure tube

    International Nuclear Information System (INIS)

    Choi, Sung Nam; Kim, Hyung Nam; Yoo, Hyun Joo; Hwang, Won Gul

    2009-01-01

    CSA N285.4-94 requires the periodic inservice inspection and surveillance of pressure tubes in operating CANDU nuclear power reactors. If the inspection results reveal a flaw exceeding the acceptance criteria of the Code, the flaw must be evaluated to determine if the pressure is acceptable for continued service. Currently, the flaw evaluation methodology and acceptance criteria specified in CSA N285.8-05, 'Technical requirements for in-service evaluation of zirconium alloy pressure tubes in CANDU reactors'. The Code is applicable to zirconium alloy pressure tubes. The evaluation methodology for a crack-like flaw is similar to that of FFSG(Fitness For Service Guideline for Zirconium alloy pressure in operation CANDU) used now. The object of this paper is to address the fracture initiation and plastic collapse evaluation for the planar flaw as it applies to the pressure tube on Wolsong NPP.

  17. Inelastic analysis of finite length and depth cracked tubes

    International Nuclear Information System (INIS)

    Reich, M.; Prachuktam, S.; Gardner, D.

    1977-01-01

    Steam generator tube failure can at times result in reactor safety problems and subsequent premature reactor shutdowns. Typical PWR steam generator units contain thousands of long straight tubes with U-bend sections. These tubes are primarily made from alloy 600 and their sizes vary between 3 / 4 '' and 7 / 8 '' (1.905 cm and 2.223 cm) in diameter with nominal thicknesses of 0.043'' to 0.053'' (0.109 cm to 0.135 cm). Since alloy 600 (and the previously used 304-SS tubes) are ductile, high toughness materials LEFM (linear elastic fracture mechanics) criteria do not apply. This paper concerns itself with the prediction of the failure pressures for typical PWR steam generator tubes with longitudinal finite length and finite depth cracks. Only local plastic overload failure is considered

  18. Effect of design and operation parameters on heat transfer coefficient in condensers

    International Nuclear Information System (INIS)

    Eskin, N.; Arslan, G.; Balci, T.

    2009-01-01

    Accurate and optimum usage of energy sources is gaining importance all over the world due to the increase of energy need and limited energy sources. Increasing condenser efficiency, reduce both the dimensions and the material usage and also the investment cost of the devices. This can be maintained by increasing the heat transfer coefficient in condensers. Generally, tubes having plain inner surfaces are mounted horizontally in serpentine type condenser applications and due to the performance loss results from the congestion in serpentine connections, vertical tube mounting is not preferred. Due to the complexity of the two-phase flow, a single set of correlation for heat transfer cannot be used. Average and local heat transfer coefficient for condensers are determined. Moreover, for each experiments flow pattern is determined and the validity of the correlations are compared according to that flow pattern. In Table 2, some of the experiments for R134a are listed. Local heat transfer coefficient is also important for condenser design. As a result, to design effective condensers the accuracy of the correlations is very important. When all the experiments are taken into account, it is seen that deviation of the correlations differs according to the refrigerant type, tube dimensions, mass flux, saturation temperature and flow pattern. For high mass flux (>400 kg/m 2 s) Traviss (1973) correlation failed. For small diameters (<3.14 mm) Tandon (1985) correlation estimate the heat transfer coefficient with a high deviation. Most accurate results are obtained for Akers et al. (1959), M.M. Shah (1978), Cavallini and Zecchlin (1974), J.R. Thome - J. El Hajal - A. Cavallini (2003) correlations. For high mass flux and annular flow, M.M. Shah (1978) correlation estimates the heat transfer coefficient with high precision. However, as the tube diameter decrease, this deviation increases. For small tube diameter such as 0.691 mm Cavallini and Zecchlin (1974) gives the most

  19. The study of marine corrosion of copper alloys in chlorinated condenser cooling circuits: the role of microbiological components.

    Science.gov (United States)

    Carvalho, Maria L; Doma, Jemimah; Sztyler, Magdalena; Beech, Iwona; Cristiani, Pierangela

    2014-06-01

    The present paper reports the on-line monitoring of corrosion behavior of the CuNi 70:30 and Al brass alloys exposed to seawater and complementary offline microbiological analyses. An electrochemical equipment with sensors specifically set for industrial application and suitable to estimate the corrosion (by linear polarization resistance technique), the biofilm growth (by the BIOX electrochemical probe), the chlorination treatment and other physical-chemical parameters of the water has been used for the on-line monitoring. In order to identify and better characterize the bacteria community present on copper alloys, tube samples were collected after a long period (1year) and short period (2days) of exposition to treated natural seawater (TNSW) and natural seawater (NSW). From the collected samples, molecular techniques such as DNA extraction, polymerase chain reaction (PCR), denaturing gradient gel electrophoresis (DGGE) and identification by sequencing were performed to better characterize and identify the microbial biodiversity present in the samples. The monitoring data confirmed the significant role played by biofouling deposition against the passivity of these Cu alloys in seawater and the positive influence of antifouling treatments based on low level dosages. Molecular analysis indicated biodiversity with the presence of Marinobacter, Alteromonas and Pseudomonas species. Copyright © 2013 Elsevier B.V. All rights reserved.

  20. Feasibility Test with a STS304 tube of the Eddy Current Test using a Bobbin Probe for the SMART SG Tube Inspection

    International Nuclear Information System (INIS)

    Lee, Yoon Sang; Jung, Hyun Kyu; Choung, Yun Hang

    2010-01-01

    The SMART SG tubes will be made of Alloy 690. The outside diameter will be 17 mm and the thickness will be 2.5 mm. They will be assembled helically around, and their innermost diameter will be about 600 mm and the total length will be about 32 meters. For the sake of safety, SMART SG tubes are designed for use with thick tubes such as 2.5 mm thickness compared to about 1 mm thickness of normal Korean standard pressurized water reactor tubes. Due to using thick tubes such as the 2.5 mm varieties, it was doubted that the Eddy Current Testing Method (ECT) would be a feasible method. Therefore we are trying to check the feasibility of the ECT using the substitute material STS304 tube instead of Alloy 690 tubes with the bobbin type ECT probe. The previous paper reported the feasibility of the ECT using modeling, but this paper will report the preliminary experimental results and comparison with the previous results of the modeling for the STS304 tube

  1. A condenser for very high power steam turbines

    International Nuclear Information System (INIS)

    Gardey, Robert.

    1973-01-01

    The invention relates to a condenser for very high power steam turbines under the masonry-block supporting the low-pressure stages of the turbine, that condenser comprises two horizontal aligned water-tube bundles passing through the steam-exhaust sleeves of the low-pressure stages, on both sides of a common inlet water box. The invention can be applied in particular to the 1000-2000 MW turbines of light water nuclear power stations [fr

  2. Experimental and theoretical investigations on condensation heat transfer at very low pressure to improve power plant efficiency

    International Nuclear Information System (INIS)

    Berrichon, J.D.; Louahlia-Gualous, H.; Bandelier, Ph.; Bariteau, N.

    2014-01-01

    Highlights: • Theoretical model for condensation heat transfer at very low pressure is developed using only one iterative loop. • Experimental results on steam and air steam condensation heat transfer at very low pressure are presented. • The developed model gives the good predictions for local condensation heat transfer at low pressure. • A maximal deterioration of 50% in condensation heat transfer is obtained at low pressure for air fraction of 4%. • A new correlation including effect of a wavy film surface for steam condensation at low pressure is suggested. - Abstract: This paper presents experimental investigation on the influence of very low pressure on local and average condensation heat transfer in a vertical tube. Furthermore, this paper develops an analytical study for film condensation heat transfer coefficient in the presence of non-condensable gas inside a vertical tube. The condensate film thickness is calculated for each location in a tube using mass and heat transfer analogy. The effects of interfacial shear stress and waves on condensate film surface are included in the model. The comparative studies show that the present model well predicts the experimental data of Khun et al. [1]for local condensation of steam air mixture at high pressure. Different correlations defined for condensation heat transfer are evaluated. It is found that the correlations of Cavallini and Zecchin [2] and Shah [3] are the closest to the calculated steam condensation local heat transfer coefficient. The model gives a satisfactory accuracy with the experimental results for condensation heat transfer at very low pressure. The mean deviation between the predictions of the theoretical model with the measurements for pure saturated vapor is 12%. Experimental data show that the increase of air fraction to 4% deteriorates condensation heat transfer at low pressure up to 50%

  3. Fouling research and cleaning effect by sponge ball on condencer tubes

    Energy Technology Data Exchange (ETDEWEB)

    Matsumoto, S; Sano, A [Kansai Electric Power Co., Inc., Osaka (Japan); Minamoto, K; Mimura, K; Kyohara, S

    1978-07-01

    Systematic research has been performed to investigate the cleaning effect on condensers cooled by sea water. The test has been done for a year using the test condenser at the Kainan Power Station, Kansai Electric Power Company. The main purpose of this research was to see the effect of cleaning inner walls of condenser tubes with sponge balls on the prevention of adhesion of marine creatures such as barnacles and other shellfishes. As the test tubes, the aluminum-brass and titanium tubes with 25.4 mm diameter, 1.245 mm thickness and 170 mm length were used. Frequency of cleaning and flow rate were chosen as the variable parameters. The effect of seasons was also investigated. Major conclusions drawn from this research were as follows. (1) More adhesion of barnacles was observed at slower flow speed and in titanium tubes rather than aluminum brass tubes. (2) At the flow speed of 1 m/sec. cleaning frequency of more than twice a week was necessary to perfectly avoid the adhesion. (3) In summer, the adhesion was most intensive, whereas in winter, it was the least. (4) Barnacles were the most predominant organism. (5) Cleaning with sponge balls was effective.

  4. Comparison of characteristics parameters in the evaluation of wall thickness diminishing in admiralty brass tubes of the steam condenser, tested by eddy currents

    International Nuclear Information System (INIS)

    Obrutsky, Alba E.; Mendez, Jorge A.; Acosta, Cesar D.; Scopelliti, Jose D.

    1999-01-01

    This work is aimed to appraise the measure of the wall thickness diminishing in the signals evaluation obtained in the inspection of steam condenser by eddy currents. In the analysis of the obtained signals were observed in the brass tubes a great quantity of internal defects whose signal indicates that there were diminishing of the wall thickness between 80% and 100%. With all this information and analyzing the data acquired, the tubes with more important indications were selected to make a more exhaustive study of the found defectology. As first test, it was measured the thickness of the worn tubes, comparing them with the original ones that are in stock. It was verified that the tubes separated for this study presented a 30% less thickness in comparison with the new tubes. A semiquantitative chemical test (EDAX) was made to verify if it was the same material. One of the extracted tubes (066 Y1) was reinspected in order to isolate the area with indications. Once this was performed, it was decided to cut the tube to make a visual inspection and to evaluate to what type of defect corresponds to the signals obtained. In the metallography it was confirm that it was a horseshoe type defect. When performing a dimensional control test of the found real defect, it was checked that the information obtained by eddy currents regarding the diminishing of the wall thickness diminishing was valid. At a last stage of the test, it was proceed to make an study and verification of the used parameters, probes, standards and finally determine which shall be the convenient modifications to minimize errors. (author)

  5. A State of the Art Report on Wear Damage of Steam Generator Tubes

    International Nuclear Information System (INIS)

    Lim, Yun Soo; Kim, Joung Soo; Kim, Hong Pyo; Hwang, Seong Sik; Jung, Man Kyo

    2004-10-01

    The recent status on wear damage of steam generator tubes caused by flow-induced vibration was investigated, and the criteria for structural integrity evaluation of the wear-damaged tubes were reviewed. It was surveyed how the wear damage of tubes could be affected by main parameters, such as, materials properties and their combination, impact load and vibration amplitude/frequency, contact areas and diametral clearance between the tube and tube support plate, wear test duration, and test temperature. Finally, corrosive wear, which means the combined action of corrosion and wear simultaneously, was also surveyed in this report. There has been only a few works concerned on the wear damage of steam generator tubes in Korea, compared with the leading foreign research institutes. Especially, the experience related to the wear characteristics of Alloy 690, which has become a replacement material for Alloy 600 as steam generator tubes, is far from satisfactory. Systematic studies, therefore, concerned with structural integrity of tubes as well as improvement of were resistance of Alloy 690 in the PWR environment are needed

  6. Fireside corrosion testing of candidate superheater tube alloys, coatings, and claddings -- Phase 2 field testing

    Energy Technology Data Exchange (ETDEWEB)

    Blough, J.L.; Seitz, W.W.; Girshik, A. [Foster Wheeler Development Corp., Livingston, NJ (United States)

    1998-06-01

    In Phase 1 of this project, laboratory experiments were performed on a variety of developmental and commercial tubing alloys and claddings by exposing them to fireside corrosion tests which simulated a superheater or reheater in a coal-fired boiler. Phase 2 (in situ testing) has exposed samples of 347, RA85H, HR3C, RA253MA, Fe{sub 3}Al + 5Cr, Ta-modified 310, NF 709, 690 clad, 671 clad, and 800HT for up to approximately 16,000 hours to the actual operating conditions of a 250-MW, coal-fired boiler. The samples were installed on air-cooled, retractable corrosion probes, installed in the reheater cavity, and controlled to the operating metal temperatures of an existing and advanced-cycle, coal-fired boiler. Samples of each alloy were exposed for 4,483, 11,348, and 15,883 hours of operation. The present results are for the metallurgical examination of the corrosion probe samples after the full 15,883 hours of exposure. A previous topical report has been issued for the 4,483 hours of exposure.

  7. Evaluation of sea water chlorine demand in condenser cooling water at TAPS 1 and 2

    International Nuclear Information System (INIS)

    Papachan, Deepa; Gupta, P.K.; Patil, D.P.; Save, C.B.; Anilkumar, K.R.

    2008-01-01

    To prevent microbiological growth in the condenser tubes, condenser cooling water chlorination is very important. For effective chlorination, chlorine dose rate and frequency of dosing has to be determined on the basis of sea water chlorine demand. TAPS 1 and 2 is located near Arabian sea and draws water from this sea for its condenser cooling. The present practice of chlorine dosing at TAPS 1 and 2, based on the analysis carried out by GE in 1969, is 2500 kg/day/CWpump and 90 kg/day/SSWpump for a contact period of 25 minutes. Normal frequency of dosing is once per 8 hour and booster dose is once in a week at the same rate for 1 hour. The criteria of effective chlorination is to get residual chlorine of 2-3 ppm at the condenser water box outlet during chlorination at water box inlet/CW pump suction header in the recommended dose rate. The other option of chlorination was continuous dosing to get 0.5 ppm residual chlorine. This option has its own limitations as it is more expensive and also that micro organisms get immune to chlorine eventually due to continuous dosing. Nevertheless higher chlorine dosing is detrimental to AI-brass condenser tubes. Therefore the second option was not adopted at TAPS 1 and 2. Tarapur Atomic Power Station-1 is in the process of replacement of condenser tubes due to frequent condenser tube failures in the recent years. It was essential to analyse the present sea water chlorine demand and re-determine the chlorine dose rate because of development of industries under Maharashtra Industrial Development Corporation (MIDC) and simultaneous population growth around this area over a period of three decades. This paper discusses the experimental observations regarding significant change in sea water chlorine demand over this period and the effect of seasonal changes on sea water chlorine demand. (author)

  8. Effect of Ti3+ ion on the Corrosion Behavior of Alloy 600

    International Nuclear Information System (INIS)

    Lee, Chang Bong; Lim, Han Gwi; Kim, Bok Hee; Kim, Ki Ju

    1999-01-01

    Alloy 600 has been widely used as a steam generator tubing material in pressurized water reactors(PWRs) nuclear power plants. Corrosion of steam generator tubing mainly occurs on the secondary water side. The purpose of this work is primarily concerned with examining the effect of Ti 3+ ion concentrations on the corrosion behavior of the Alloy 600 steam generator tubing material. Corrosion behavior of the Alloy 600 steam generator tubing material was studied in aqueous solutions with varying Ti 3+ ion concentration at room temperature. Potentiodynamic and potentiostatic polarization techniques were used to determine the corrosion and pitting potentials for the Alloy 600 test material. The addition of Ti 3+ ion to 1000ppm, showed inhibition effect on the corrosion of Alloy 600. But the corrosion of Alloy 600 was accelerated when the concentration of Ti 3+ ion exceeded 1000ppm, it is assumed that the effect of general corrosion of Alloy 600 is more sensitive than pitting corrosion. It is considered that the passive film which was formed on the Alloy 600 surface in the 100ppm Ti 3+ ion containing solution is mainly consisted of TiO 2

  9. Acoustic emission analysis on tensile failure of steam-side oxide scales formed on T22 alloy superheater tubes

    Energy Technology Data Exchange (ETDEWEB)

    Huang, Jun-Lin; Zhou, Ke-Yi, E-mail: boiler@seu.edu.cn; Xu, Jian-Qun [Key Laboratory of Energy Thermal Conversion and Control of Ministry of Education, School of Energy and Environment, Southeast University, Nanjing 210096, Jiangsu Province (China); Wang, Xin-Meng; Tu, Yi-You [School of Materials Science and Engineering, Southeast University, Nanjing 210096, Jiangsu Province (China)

    2014-07-28

    Failure of steam-side oxide scales on boiler tubes can seriously influence the safety of coal-fired power plants. Uniaxial tensile tests employing acoustic emission (AE) monitoring were performed, in this work, to investigate the failure behavior of steam-side oxide scales on T22 alloy boiler superheater tubes. The characteristic frequency spectra of the captured AE signals were obtained by performing fast Fourier transform. Three distinct peak frequency bands, 100-170, 175-250, and 280-390 kHz, encountered in different testing stages were identified in the frequency spectra, which were confirmed to, respectively, correspond to substrate plastic deformation, oxide vertical cracking, and oxide spalling with the aid of scanning electronic microscopy observations, and can thus be used for distinguishing different oxide failure mechanisms. Finally, the critical cracking strain of the oxide scale and the interfacial shear strength of the oxide/substrate interface were estimated, which are the critical parameters urgently desired for modeling the failure behavior of steam-side oxide scales on boiler tubes of coal-fired power plants.

  10. Acoustic emission analysis on tensile failure of steam-side oxide scales formed on T22 alloy superheater tubes

    Science.gov (United States)

    Huang, Jun-Lin; Zhou, Ke-Yi; Wang, Xin-Meng; Tu, Yi-You; Xu, Jian-Qun

    2014-07-01

    Failure of steam-side oxide scales on boiler tubes can seriously influence the safety of coal-fired power plants. Uniaxial tensile tests employing acoustic emission (AE) monitoring were performed, in this work, to investigate the failure behavior of steam-side oxide scales on T22 alloy boiler superheater tubes. The characteristic frequency spectra of the captured AE signals were obtained by performing fast Fourier transform. Three distinct peak frequency bands, 100-170, 175-250, and 280-390 kHz, encountered in different testing stages were identified in the frequency spectra, which were confirmed to, respectively, correspond to substrate plastic deformation, oxide vertical cracking, and oxide spalling with the aid of scanning electronic microscopy observations, and can thus be used for distinguishing different oxide failure mechanisms. Finally, the critical cracking strain of the oxide scale and the interfacial shear strength of the oxide/substrate interface were estimated, which are the critical parameters urgently desired for modeling the failure behavior of steam-side oxide scales on boiler tubes of coal-fired power plants.

  11. Acoustic emission analysis on tensile failure of steam-side oxide scales formed on T22 alloy superheater tubes

    International Nuclear Information System (INIS)

    Huang, Jun-Lin; Zhou, Ke-Yi; Xu, Jian-Qun; Wang, Xin-Meng; Tu, Yi-You

    2014-01-01

    Failure of steam-side oxide scales on boiler tubes can seriously influence the safety of coal-fired power plants. Uniaxial tensile tests employing acoustic emission (AE) monitoring were performed, in this work, to investigate the failure behavior of steam-side oxide scales on T22 alloy boiler superheater tubes. The characteristic frequency spectra of the captured AE signals were obtained by performing fast Fourier transform. Three distinct peak frequency bands, 100-170, 175-250, and 280-390 kHz, encountered in different testing stages were identified in the frequency spectra, which were confirmed to, respectively, correspond to substrate plastic deformation, oxide vertical cracking, and oxide spalling with the aid of scanning electronic microscopy observations, and can thus be used for distinguishing different oxide failure mechanisms. Finally, the critical cracking strain of the oxide scale and the interfacial shear strength of the oxide/substrate interface were estimated, which are the critical parameters urgently desired for modeling the failure behavior of steam-side oxide scales on boiler tubes of coal-fired power plants.

  12. The modelling of condensation in horizontal tubes and the comparison with experimental data

    Directory of Open Access Journals (Sweden)

    Bryk Rafał

    2017-01-01

    Full Text Available The condensation in horizontal tubes plays an important role in determining the operation mode of passive safety systems of modern nuclear power plants. In this paper, two different approaches for modelling of this phenomenon are compared and verified against experimental data. The first approach is based on the flow regime map developed by Tandon. Depending on the regime, the heat transfer coefficient is calculated according to corresponding semi-empirical correlation. The second approach uses a general, fully empirical correlation proposed by Shah. Both models are developed with utilization of the object-oriented, equation-based Modelica language and the open-source Open-Modelica environment. The results are compared with data obtained during a large scale integral test, simulating a Loss of Coolant Accident scenario performed at the dedicated Integral Test Facility Karlstein (INKA which was built at the Components Testing Department of AREVA in Karlstein, Germany. The INKA facility was designed to test the performance of the passive safety systems of KERENA, the new AREVA boiling water reactor design. INKA represents the KERENA containment with a volume scaling of 1:24. Components heights and levels over the ground are in the full scale. The comparison of simulations results shows a good agreement.

  13. Modelling of film condensation in presence of non condensable gases

    International Nuclear Information System (INIS)

    Genevieve Geffraye; Dominique Bestion; Vladimir Kalitvianski

    2005-01-01

    Full text of publication follows: This paper presents recent developments in the modelling of the condensation due to heat removal from a wall with a possible presence of hydrogen, nitrogen, or air. This work is mainly concerned with nuclear reactor safety with particular reference to situations related to new reactor design, cold shutdown state and severe accident analysis. Film condensation of steam in presence of nitrogen and helium in a tube has been investigated in the COTURNE experiment in a rather large range of parameters, pressure (from 0.1 to 7 Mpa), heat flux (0.1 to 6 W/cm 2 ), mass fraction of noncondensable gas (0 to 1) and also in presence of superheated steam. The experiment represents a Steam Generator tube of a Pressurised Water Reactor and can simulate both co-current or countercurrent flow of steam and water.The models are implemented in the CATHARE code used for nuclear reactor thermal-hydraulics. The code uses two mass balance equations for liquid and gas, two momentum balance equations for liquid and gas and two energy balance equations for liquid and gas. Additional mass transport equations can be added for each non condensable gas. Heat transfers from wall to liquid film, from liquid to interface and gas to interface are modelled. The liquid film heat transfer coefficient is first investigated in pure saturated steam conditions in the pressure range from 0.1 to 7 Mpa. The CATHARE film condensation model in pure steam conditions is derived from Chen's correlation. Chen proposes a general correlation for the film condensation, covering the wavy-laminar and the turbulent film regimes and taking into account the interfacial friction effect. A large data base of laminar film regime was used including COTURNE data other available data found in the literature. The analysis of these data base suggests an influence of the liquid Reynolds number, according to the Nusselt theory, and also of the Eoetvoes number, with surface tension effects. A

  14. Millstone 3 condensate dissolved gas monitoring

    International Nuclear Information System (INIS)

    Burns, T.F.; Grondahl, E.E.; Snyder, D.T.

    1988-01-01

    Condensate dissolved oxygen problems at Millstone Point Unit 3 (MP3) were investigated using the Dissolved Gas Monitoring System developed by Radiological and Chemical Technology, Inc. under EPRI sponsorship. Argon was injected into the turbine exhaust basket tips to perform a dissolved gas transport analysis and determine steam jet air ejector gas removal efficiency. The operating configuration of the steam jet air ejector system was varied to determine the effect on gas removal efficiency. Following circulating water chlorination, the gas removal efficiency was determined to evaluate the effect of condenser tube fouling on steam jet air ejector performance

  15. Neutronographic Texture Analysis of Zirconium Based Alloys

    International Nuclear Information System (INIS)

    Kruz'elová, M; Vratislav, S; Kalvoda, L; Dlouhá, M

    2012-01-01

    Neutron diffraction is a very powerful tool in texture analysis of zirconium based alloys used in nuclear technique. Textures of five samples (two rolled sheets and three tubes) were investigated by using basal pole figures, inversion pole figures, and ODF distribution function. The texture measurement was performed at diffractometer KSN2 on the Laboratory of Neutron Diffraction, Department of Solid State Engineering, Faculty of Nuclear Sciences and Physical Engineering, CTU in Prague. Procedures for studying textures with thermal neutrons and procedures for obtaining texture parameters (direct and inverse pole figures, three dimensional orientation distribution function) are also described. Observed data were processed by software packages HEXAL and GSAS. Our results can be summarized as follows: i) All samples of zirconium alloys show the distribution of middle area into two maxima in basal pole figures. This is caused by alloying elements. A characteristic split of the basal pole maxima tilted from the normal direction toward the transverse direction can be observed for all samples, ii) Sheet samples prefer orientation of planes (100) and (110) perpendicular to rolling direction and orientation of planes (002) perpendicular to normal direction, iii) Basal planes of tubes are oriented parallel to tube axis, meanwhile (100) planes are oriented perpendicular to tube axis. Level of resulting texture and maxima position is different for tubes and for sheets. The obtained results are characteristic for zirconium based alloys.

  16. Experimental study on external condensation heat transfer characteristics of bellows

    International Nuclear Information System (INIS)

    Feng Dianyi; Hu Jiansheng

    2008-01-01

    Flow model and heat transfer of condensation flow outside of bellows have been theoretically and experimentally studied. The formula for calculation of condensation heat transfer coefficient was deduced, and corrected through experiment. The calculation results are accordant with the experimental ones, and the errors is less than 10%. The effect of bellows structure parameters and pipe diameter on the enhancement heat transfer has been investigated. It is found that in the steady flow region, the average condensation heat transfer coefficient in a bellows is 3 ∼ 5 times than that in a straight tube under the same conditions, and when considering the increasing in heat transfer area, the effectiveness of enhancement heat transfer is 5 ∼ 7 times than that in a straight tube. To facilitate the engineering design and application of bellows, the formula for the calculation of the average heat transfer coefficient of a fluid in a bellows was also given. (authors)

  17. Final Technical Report - High-Performance, Oxide-Dispersion-Strengthened Tubes for Production of Ethylene adn Other Industrial Chemicals

    Energy Technology Data Exchange (ETDEWEB)

    McKimpson, Marvin G.

    2006-04-06

    This project was undertaken by Michigan Technological University and Special Metals Corporation to develop creep-resistant, coking-resistant oxide-dispersion-strengthened (ODS) tubes for use in industrial-scale ethylene pyrolysis and steam methane reforming operations. Ethylene pyrolysis tubes are exposed to some of the most severe service conditions for metallic materials found anywhere in the chemical process industries, including elevated temperatures, oxidizing atmospheres and high carbon potentials. During service, hard deposits of carbon (coke) build up on the inner wall of the tube, reducing heat transfer and restricting the flow of the hydrocarbon feedstocks. About every 20 to 60 days, the reactor must be taken off-line and decoked by burning out the accumulated carbon. This decoking costs on the order of $9 million per year per ethylene plant, accelerates tube degradation, and requires that tubes be replaced about every 5 years. The technology developed under this program seeks to reduce the energy and economic cost of coking by creating novel bimetallic tubes offering a combination of improved coking resistance, creep resistance and fabricability not available in current single-alloy tubes. The inner core of this tube consists of Incoloy(R) MA956, a commercial ferritic Fe-Cr-Al alloy offering a 50% reduction in coke buildup combined with improved carburization resistance. The outer sheath consists of a new material - oxide dispersion strengthened (ODS) Alloy 803(R) developed under the program. This new alloy retains the good fireside environmental resistance of Alloy 803, a commercial wrought alloy currently used for ethylene production, and provides an austenitic casing to alleviate the inherently-limited fabricability of the ferritic Incoloy(R) MA956 core. To provide mechanical compatibility between the two alloys and maximize creep resistance of the bimetallic tube, both the inner Incoloy(R) MA956 and the outer ODS Alloy 803 are oxide dispersion

  18. Coupling of standard condensing nuclear power stations to horizontal aluminium tubes multieffect distillation plants

    International Nuclear Information System (INIS)

    Adar, J.

    1977-01-01

    No large nuclear back-pressure turbines are available to-day. Standard condensing nuclear turbines could operate continuously with a back-pressure of up to 7'' Hg, exhausting huge amounts of steam at 56degC-64degC with a loss of electricity production of only 6%-10%. The horizontal aluminium tube multieffect distillation process developed by 'Israel Desalination Engineering Ltd' is very suitable for the use of such low-grade heat. A special flash-chamber loop constitutes a positive barrier against any possible contamination being carried over by the steam exhausted from the turbine to the desalination plant. The operation is designed to be flexible so that the power plant can be operated either in conjunction with the desalination plant or as a single purpose plant. Flow sheets, heat and mass balances have been prepared for eight different combinations of plants. Only standard equipment is being used in the power plant. The desalination plant consists of 6 to 12 parallel double lines, each of them similar to a large prototype now being designed. Water production varies between 50 and 123 MGD and water cost between 90 and 137 c/1000 gallons. Costs are based on actual bids

  19. Development of process route for the production of Fe-0.12C-9CR-2W-0.35Y2O3 ODS alloy tubing for Indian FBR application

    International Nuclear Information System (INIS)

    Lakshminarayana, B.; Tonpe, S.; Jha, S.K.; Kapoor, Komal; Dubey, A.K.; Gurunadh, J.; Surender, A.; Deshpande, K.V.K.; Maity, P.K.

    2011-01-01

    In the wake of Nuclear Renaissance, India is playing key role in generation of clean and green Nuclear Energy. It has entered into its second stage Nuclear Power Program on commercial scale with the commencement of construction of 500 MWe Prototype Fast Breeder Reactor (PFBR) at Kalpakkam. Nuclear Fuel Complex (NFC), Hyderabad is playing a crucial role in the manufacture of all the critical sub-assemblies in SS (D9) grade materials for this reactor. The SS(D9) material with controlled cold work is having very good void swelling resistance and high temperature properties, which can sustain fluence of 100 dpa. The paper covers the manufacturing process and characterization of the ODS tubes for fuel clad application. Manufacturing of 9 Cr 2W Y 2 O 3 - ODS martensitic steel fuel cladding tube has been taken up in Nuclear Fuel Complex, Hyderabad with mechanical alloying followed by MS canning of mechanically alloyed powder, upsetting and hot extrusion and subsequently thermo mechanical process. Manufacturing technology of ODS steel tube is critical with respect its chemical composition, dimensional tolerances, Y 2 O 3 particle size and its distribution and achievement of mechanical properties with proper combination of cold working and heat treatment. The paper covers the manufacturing process and characterization of the ODS tubes for fuel clad application. Manufacturing process for the production of ODS alloy (9 Cr 2W Y 2 O 3 - ODS) has been optimized for mass scale production at NFC

  20. Steam generator tube performance: world experience with water-cooled nuclear power reactors during 1979

    International Nuclear Information System (INIS)

    Tatone, O.S.; Pathania, R.S.

    1981-01-01

    The performance of steam generator tubes in water-cooled nuclear power reactors is reviewed for 1979. Tube failures occurred at 38 of the 93 reactors surveyed. The causes of these failures and the procedures designed to deal with them are described. The defect rate, although higher than that in 1978, was still lower than the rates of the two previous years. Methods being employed to detect defects include the increased use of multifrequency eddy-current testing and a trend to full-length inspection of all tubes. To reduce the incidence of tube failure by corrosion, plant operators are turning to full-flow condensate demineralization and more leak-resistant condenser tubes. 10 tables

  1. Delayed hydride cracking in Zr-2.5Nb pressure tubes

    International Nuclear Information System (INIS)

    Mieza, Juan I.; Domizzi, Gladys; Vigna, Gustavo L.

    2007-01-01

    Zr-2.5 Nb alloy from CANDU pressure tubes are prone to failure by hydrogen intake. One of the degradation mechanisms is delayed hydride cracking, which is characterized by the velocity of cracking. In this work, we study the effect of beta zirconium phase transformation over delayed hydride cracking velocity in Zr-2.5 Nb alloy from pressure tubes. Acoustic emission technique was used for cracking detection. (author) [es

  2. Prospects for zirconium structural alloys at high temperatures

    International Nuclear Information System (INIS)

    Thomas, W.R.

    1969-05-01

    Improved station efficiencies and lower capital costs provide incentives for the development of zirconium alloys for pressure tubes which can operate at temperatures above 450 o C. The experience of the Ti industry indicates that a complex alloy containing solution hardeners of Sn or Al and precipitation hardeners of Mo and Nb and perhaps Si will be required. The thermal neutron cross-section of the alloy will be about 10% higher than Zircaloy-2 and because of its poor corrosion resistance will require cladding with a corrosion resistant alloy such as Zr-Cr. Results to date indicate that such a pressure tube is feasible. (author)

  3. Fouling research and cleaning effect by sponge ball on condencer tubes

    International Nuclear Information System (INIS)

    Matsumoto, Seizo; Sano, Akira; Minamoto, Kenju; Mimura, Keisuke; Kyohara, Shigeru.

    1978-01-01

    Systematic research has been performed to investigate the cleaning effect on condensers cooled by sea water. The test has been done for a year using the test condenser at the Kainan Power Station, Kansai Electric Power Company. The main purpose of this research was to see the effect of cleaning inner walls of condenser tubes with sponge balls on the prevention of adhesion of marine creatures such as barnacles and other shellfishes. As the test tubes, the aluminum-brass and titanium tubes with 25.4 mm diameter, 1.245 mm thickness and 170 mm length were used. Frequency of cleaning and flow rate were chosen as the variable parameters. The effect of seasons was also investigated. Major conclusions drawn from this research were as follows. (1) More adhesion of barnacles was observed at slower flow speed and in titanium tubes rather than aluminum brass tubes. (2) At the flow speed of 1 m/sec. cleaning frequency of more than twice a week was necessary to perfectly avoid the adhesion. (3) In summer, the adhesion was most intensive, whereas in winter, it was the least. (4) Barnacles were the most predominant organism. (5) Cleaning with sponge balls was effective. (Aoki, K.)

  4. Development of microstructure in thermomechanical processing of zirconium alloys

    International Nuclear Information System (INIS)

    Jha, S.K.; Saibaba, N.; Jayaraj, R.N.

    2009-01-01

    Zirconium based alloys are used for the manufacture of fuel tubes pressure tubes calandria tubes and other components of Pressurized Heavy Water Reactors (PHWRS). In single or two phase zirconium alloy system a variety of microstructure can be generated by suitable heat treatments by the process of equilibrium and non equilibrium phase transformations Microstructure can also be modified by alloying with α and β stabilizers. The microstructure in Zr alloys could be single hexagonal phase (α alloys) two phase bcc and hexagonal (α + β alloys) phase, single metastable martensitic microstructure and β with ω phase. The microstructural and micro textural evolution during thermo mechanical treatments depends strongly on such initial microstructure. Hot extrusion is a significant bulk deformation step which decides the initial microstructure of the alloy. It is carried out at elevated temperature i e above the recrystallization temperature, which enable imposition of large strains in single step. This deformation causes a significant change in the microstructure of the material and depends on extrusion process parameters such as temperature, strain rate (Ram speed), reduction ratio etc. In the present paper development of microstructures, microtexture and texture have been examined. An attempt is also made to optimise the hot working parameters for different Zirconium alloys with help of these studies. (author)

  5. Patchouli Oil Production for Fixative Aromatheraphy: A Case Study Design of Condenser for Steam Distillation

    Directory of Open Access Journals (Sweden)

    Egi Agustian

    2015-06-01

    Full Text Available Patchouli oil is an important material for aromatherapy industries and made from patchouli leaves by steam distillation. The important parts of steam distillation is condenser. The problem is process of farmer's patchouli based on experience not used chemical process of steam distillation cause not effective and efficient. The study was designed of condensers on steam distillation for patchouli leaves. Specification of condenser type is shell and tube, stainless steel material and water as coolant. Tubing sized is ¼ inch with 500 mm of length and 24 pieces. Shell measuring 2.5 inch and 600 mm of length. The performance of condenser gave the efficiency at 94.51%. The process condition of ratio stems to leaves is 5:6 and 4.5 hours was considered ideal for steam distillation. The used of energy is lowest cause the efficiency condenser and yield will be higher. Patchouli oil yield of 2.39% and patchouli alcohol content is 35.65%.

  6. Heat treated tube for cladding nuclear fuel element

    International Nuclear Information System (INIS)

    Eddens, F.C.; White, D.W.; Harmon, J.L.

    1983-01-01

    The zirconium alloy tube comprises a metallurgical gradient across the width of the tube wall wherein the tube has a more corrosion-resistant metallurgical condition at the outer circumference and a less corrosion-resistant metallurgical condition at the inner circumference. The metallurgical gradient can be generated by heating an outer circumferential portion of the tube to the high alpha or mixed alpha plus beta range while maintaining the inner surface at a lower temperature, followed by cooling of the tube. Preferably the tube is made of Zircaloy. (author)

  7. Influence of microstructure modification on the circumferential creep of Zr–Nb–Sn–Fe cladding tubes

    International Nuclear Information System (INIS)

    Jeong, Gu Beom; Kim, In Won; Hong, Sun Ig

    2016-01-01

    Out-of-reactor, non-irradiated thermal creep performances and lives of annealed and stress-relieved Zr-1.02Nb-0.69Sn-0.12Fe cladding tubes were studied and compared. The creep rates of annealed Zr-1.02Nb-0.69Sn-0.12Fe cladding tubes were appreciably slower than those of stress-relieved annealed counterpart. The stress exponent increased slightly from 5.1 to 6.1 in the stress-relieved cladding to 5.3–6.3 in the annealed cladding. The creep activation energy of the annealed Zr-1.02Nb-0.69Sn-0.12Fe alloy (300–330 kJ/mol) was larger compared to that of the stress-relieved alloy (210–260 kJ/mol). The creep activation energy of annealed alloy is close to that of self-diffusion in α-Zr (336 kJ/mol). The smaller activation energy in the stress-relieved alloy is attributed to the increasing contribution of faster diffusion path such as grain boundaries and dislocations. The presence of dislocation arrays with higher dislocation density and smaller grain size in the stress-relived alloy was confirmed by TEM analysis. The creep rupture time increased dramatically in the annealed Zr–1Nb- 0.7Sn-0.1Fe alloy compared to that of stress-relieved alloy, supporting the decrease of creep rate by annealing. The creep life of Zr-1.02Nb-0.69Sn-0.12Fe claddings can be extended through microstructure modification by annealing at intermediate temperatures in which dislocation creep dominates. - Highlights: • Effect of microstructure modification on creep in Zr–Nb–Sn–Fe tubes was studied. • Creep activation energy in annealed tubes was larger than in stress-relieved tubes. • Lower dislocation density in lager grains was observed after creep in annealed tubes. • Larson–Miller parameter of annealed tube was larger than that of stress-relieved one. • Creep life of tubes was extended through microstructure modification by annealing.

  8. Theory of laminar film condensation

    CERN Document Server

    Fujii, Tetsu

    1991-01-01

    Since the petroleum crisis in the 1970s, a lot of effort to save energy was made in industry, and remarkable achievements have been made. In the research and development concerning thermal energy, however, it was clar­ ified that one of the most important problems was manufacturing con­ densing systems with smaller size and higher performance. To solve this problem we need a method which synthesizes selections_ of the type of con­ denser, cooling tube and its arrangement, assessment of fouling on the cooling surfaces, consideration of transient characteristics of a condenser, etc. The majority of effort, however, has been to devise a surface element which enhances the heat transfer coefficient in condensation of a single or multicomponent vapor. Condensation phenomena are complexly affected by a lot of physical property values, and accordingly the results of theo­ retical research are expressed with several dimensionless parameters. On the other hand, the experimental research is limited to those with som...

  9. Experimental and Thermalhydraulic Code Assessment of the Transient Behavior of the Passive Condenser System in an Advanced Boiling Water Reactor

    Energy Technology Data Exchange (ETDEWEB)

    S.T. Revankar; W. Zhou; Gavin Henderson

    2008-07-08

    The main goal of the project was to study analytically and experimentally the condensation heat transfer for the passive condenser system such as GE Economic Simplified Boiling Water Reactor (ESBWR). The effect of noncondensable gas in condenser tube and the reduction of secondary pool water level to the condensation heat transfer coefficient was the main focus in this research. The objectives of this research were to : 1) obtain experimental data on the local and tube averaged condensation heat transfer rates for the PCCS with non-condensable and with change in the secondary pool water, 2) assess the RELAP5 and TRACE computer code against the experimental data, and 3) develop mathematical model and ehat transfer correlation for the condensation phenomena for system code application. The project involves experimentation, theoretical model development and verification, and thermal- hydraulic codes assessment.

  10. Experimental and Thermalhydraulic Code Assessment of the Transient Behavior of the Passive Condenser System in an Advanced Boiling Water Reactor

    International Nuclear Information System (INIS)

    S.T. Revankar; W. Zhou; Gavin Henderson

    2008-01-01

    The main goal of the project was to study analytically and experimentally the condensation heat transfer for the passive condenser system such as GE Economic Simplified Boiling Water Reactor (ESBWR). The effect of noncondensable gas in condenser tube and the reduction of secondary pool water level to the condensation heat transfer coefficient was the main focus in this research. The objectives of this research were to: (1) obtain experimental data on the local and tube averaged condensation heat transfer rates for the PCCS with non-condensable and with change in the secondary pool water, (2) assess the RELAP5 and TRACE computer code against the experimental data, and (3) develop mathematical model and heat transfer correlation for the condensation phenomena for system code application. The project involves experimentation, theoretical model development and verification, and thermal-hydraulic codes assessment

  11. Droplet behaviour in a Ranque-Hilsch vortex tube

    Energy Technology Data Exchange (ETDEWEB)

    Liew, R; Zeegers, J C H [Department of Applied Physics, Eindhoven University of Technology, PO Box 513, 5600 MB Eindhoven (Netherlands); Michalek, W R; Kuerten, J G M, E-mail: r.liew@tue.nl [Department of Mechanical Engineering, Eindhoven University of Technology, PO Box 513, 5600 MB Eindhoven (Netherlands)

    2011-12-22

    The vortex tube is an apparatus by which compressed gas is separated into cold and warm streams. Although the apparatus is mostly used for cooling, the possibility to use the vortex tube as a device for removing non-desired condensable components from gas mixtures is investigated. To give first insight on how droplets behave in the vortex tube, a MATLAB model is written. The model tracks Lagrangian droplets in time and space according to the forces acting on the droplets. Phase interactions, i.e. evaporation or condensation, are modeled according to the kinetic approach for phase interactions. Liquid (water) concentrations are shown for two cases where the humidity at the inlet of the vortex tube is varied from 0% to 50%. It is clearly observed from the results that the concentration of liquid increases with increasing humidity. The higher this concentration is, the higher the probability that droplets collide with each other and form larger droplets which are swirled towards the wall to form an easy-to-separate liquid film.

  12. Evaluation of crack propagation of alloy 600 tube in high temperature water, (1)

    International Nuclear Information System (INIS)

    Hirano, Hideo; Kawamura, H.; Kawamura, Kohji; Matsubara, Masaaki

    1990-01-01

    This report describes the analysis of stress intensity factors at cracks in alloy 600 steam generator tubes. Based on the results of the analysis, IGA/SCC tests were carried out to examine the effect of stress intensity and water quality on the crack propagation rate. The main test result are as follows: (1) Hoop stress was caused by the pressure difference between the internal and external surface of the steam generator tube. The calculated hoop stress was about 7 kg/mm 2 . In addition, the temperature difference between the internal and external surface caused thermal stress. The thermal stress was about 10 kg/mm 2 at the external surface and the one at the internal surface was about -10 kg/mm 2 . Total stress at the external and internal surface was 17 kg/mm 2 and -3 kg/mm 2 , respectively. (2) The stress intensity factor at the crack tip increased with increasing crack length. For a long crack, the stress intensity factor decreased with increasing crack number. However, for a short crack, the stress intensity factor decreased little with increasing crack number. (3) Under high stress-intensity conditions, i.e. 40∼50 kg·mm -3/2 , the IGA/SCC test showed that IGA/SCC propagated in AVT and AVT/boric-acid solution at 320degC and 350degC. However, the propagation rate was low. (author)

  13. Experimental study and modeling of high-temperature oxidation and phase transformation of cladding-tubes made in zirconium alloy

    International Nuclear Information System (INIS)

    Mazeres, Benoit

    2013-01-01

    One of the hypothetical accident studied in the field of the safety studies of Pressurized light Water Reactor (PWR) is the Loss-Of-Coolant-Accident (LOCA). In this scenario, zirconium alloy fuel claddings could undergo an important oxidation at high temperature (T≅ 1200 C) in a steam environment. Cladding tubes constitute the first confinement barrier of radioelements and then it is essential that they keep a certain level of ductility after quenching to ensure their integrity. These properties are directly related to the growth kinetics of both the oxide and the αZr(O) phase and also to the oxygen diffusion profile in the cladding tube after the transient. In this context, this work was dedicated to the understanding and the modeling of the both oxidation phenomenon and oxygen diffusion in zirconium based alloys at high temperature. The numerical tool (EKINOX-Zr) used in this thesis is based on a numerical resolution of a diffusion/reaction problem with equilibrium-conditions on three moving boundaries: gas/oxide, oxide/αZr(O), αZr(O)/βZr. EKINOX-Zr kinetics model is coupled with ThermoCalc software and the Zircobase database to take into account the influence of the alloying elements (Sn, Fe, Cr, Nb) but also the influence of hydrogen on the solubility of oxygen. This study focused on two parts of the LOCA scenario: the influence of a pre-oxide layer (formed in-service) and the effects of hydrogen. Thanks to the link between EKINOX-Zr and the thermodynamic database Zircobase, the hydrogen effects on oxygen solubility limit could be considered in the numerical simulations. Thus, simulations could reproduce the oxygen diffusion profiles measured in pre-hydrided samples. The existence of a thick pre-oxide layer on cladding tubes can induce a reduction of this pre-oxide layer before the growth of a high-temperature one during the high temperature dwell under steam. The first simulations performed using the numerical tool EKINOX-Zr showed that this particular

  14. A Eutectic Melting Study of Double Wall Cladding Tubes of FeCrAl and Zircaloy-4

    Energy Technology Data Exchange (ETDEWEB)

    Lim, Woojin; Son, Seongmin; Lee, You Ho; Lee, Jeong Ik; Ryu, Ho Jin [Korea Advanced Institute of Science and Technology, Daejeon (Korea, Republic of); Jeong, Eun [Kyunghee University, Yongin (Korea, Republic of)

    2015-10-15

    The eutectic melting behavior of FeCrAl/Zircaloy-4 double wall cladding tubes was investigated by annealing at various temperatures ranging from 900 .deg. C to 1300 .deg. C. It was found that significant eutectic melting occurred after annealing at temperatures equal to or higher than 1150 .deg. C. It means that an additional diffusion barrier layer is necessary to limit the eutectic melting between FeCrAl and Zircaloy-4 alloy cladding tubes. Coating of FeCrAl layers on the Zr alloy cladding tube is being investigated for the development of accident tolerant fuel by exploiting of both the oxidation resistance of FeCrAl alloys and the neutronic advantages of Zr alloys. Coating of FeCrAl alloys on Zr alloy cladding tubes can be performed by various techniques including thermal spray, laser cladding, and co-extrusion. Son et al. also reported the fabrication of FeCrAl/Zr ally double wall cladding by the shrink fit method. For the double layered cladding tubes, the thermal expansion mismatch between the dissimilar materials, severe deformation or mechanical failure due to the evolution of thermal stresses can occur when there is a thermal cycling. In addition to the thermal stress problems, chemical compatibilities between the two different alloys should be investigated in order to check the stability and thermal margin of the double wall cladding at a high temperature. Generally, it is considered that Zr alloy cladding will maintain its mechanical integrity up to 1204 .deg. C (2200 .deg. F) to satisfy the acceptance criteria for emergency core cooling systems.

  15. Complete Status Report Documenting Development of Friction Stir Welding for Joining Thin Wall Tubing of ODS Alloys

    Energy Technology Data Exchange (ETDEWEB)

    Hoelzer, David T. [Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States); Bunn, Jeffrey R. [Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States); Gussev, Maxim N. [Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States)

    2017-08-01

    The development of friction stir welding (FSW) for joining thin sections of the advanced oxide dispersion strengthened (ODS) 14YWT ferritic alloy was initiated in Fuel Cycle Research and Development (FCRD), now the Nuclear Technology Research and Development (NTRD), in 2015. The first FSW experiment was conducted in late FY15 and successfully produced a bead-on-plate stir zone (SZ) on a 1 mm thick plate of 14YWT (SM13 heat). The goal of this research task is to ultimately demonstrate that FSW is a feasible method for joining thin wall (0.5 mm thick) tubing of 14YWT.

  16. 3D CFD simulations to study the effect of inclination of condenser tube on natural convection and thermal stratification in a passive decay heat removal system

    Energy Technology Data Exchange (ETDEWEB)

    Minocha, Nitin [Homi Bhabha National Institute, Anushaktinagar, Mumbai 400 094 (India); Joshi, Jyeshtharaj B., E-mail: jbjoshi@gmail.com [Homi Bhabha National Institute, Anushaktinagar, Mumbai 400 094 (India); Department of Chemical Engineering, Institute of Chemical Technology, Matunga, Mumbai 400 019 (India); Nayak, Arun K. [Reactor Engineering Division, Bhabha Atomic Research Center, Trombay, Mumbai 400 085 (India); Vijayan, Pallippattu K., E-mail: vijayanp@barc.gov.in [Reactor Engineering Division, Bhabha Atomic Research Center, Trombay, Mumbai 400 085 (India)

    2016-08-15

    Highlights: • Investigation of three-dimensional natural convection and thermal stratification inside large water pool. • Effect of inclination (α) of condenser tube on fluid flow and heat transfer. • The heat transfer was found to be maximum for α = 90° and minimum for α = 15°. • Laminar-turbulent natural convection and heat transfer in the presence of longitudinal vortices. - Abstract: Many advanced nuclear reactors adopt methodologies of passive safety systems based on natural forces such as gravity. In one of such system, the decay heat generated from a reactor is removed by isolation condenser (ICs) submerged in a large water pool called the Gravity Driven Water Pool (GDWP). The objective of the present study was to design an IC for the passive decay heat removal system (PDHRS) for advanced nuclear reactor. First, the effect of inclination of IC tube on three dimensional temperature and flow fields was investigated inside a pilot scale (10 L) GDWP. Further, the knowledge of these fields has been used for the quantification of heat transfer and thermal stratification phenomenon. In a next step, the knowledge gained from the pilot scale GDWP has been extended to design an IC for real size GDWP (∼10,000 m{sup 3}). Single phase CFD simulation using open source CFD code [OpenFOAM-2.2] was performed for different tube inclination angles (α) (w.r.t. to vertical direction) in the range 0° ⩽ α ⩽ 90°. The results indicate that the heat transfer coefficient increases with increase in tube inclination angle. The heat transfer was found to be maximum for α = 90° and minimum for α = 15°. This behavior is due to the interaction between the primary flow (due to pressure gradient) and secondary flow (due to buoyancy force). The primary flow enhanced the fluid sliding motion at the tube top whereas the secondary flow resulted in enhancement in fluid motion along the circumference of tube. As the angle of inclination (α) of the tube was increased, the

  17. Device and method for shortening reactor process tubes

    Science.gov (United States)

    Frantz, Charles E.; Alexander, William K.; Lander, Walter E. B.

    1980-01-01

    This disclosure describes a device and method for in situ shortening of nuclear reactor zirconium alloy process tubes which have grown as a result of radiation exposure. An upsetting technique is utilized which involves inductively heating a short band of a process tube with simultaneous application of an axial load sufficient to cause upsetting with an attendant decrease in length of the process tube.

  18. A Method to Establishing Tube Plugging Criterion for Heat Exchangers with Straight Tubes

    Energy Technology Data Exchange (ETDEWEB)

    Kim, Hyungnam [KHNP CRI, Daejeon (Korea, Republic of)

    2016-10-15

    The difference of thermal expansion coefficients between the shell and tube materials causes the stress in axial direction of tube. Because of the axial stress due to thermal load, the straight tubes are used for heat exchangers operated in low temperature such as CCW (Component Cooling Water) heat exchangers and condensers. It is inevitable for the materials of the components to be degraded as the power plants become older. The degradation accompanies increasing maintenance cost as well as creating safety issues. The materials and wall thickness of heat exchanger tubes in nuclear power plants are selected to withstand system temperature, pressure, and corrosion. There are many codes and standards to be referred for calculating the minimum thickness of the heat exchanger tube in the designing stage. However, the codes and standards related to show the tube plugging criteria may not exist currently. In this paper, a method to establish the tube plugging criteria of BOP heat exchangers, which is based on the USNRC Regulatory Guide 1.121, is introduced and the tube plugging criteria for the TPCCW heat exchanger of Yonggwang NPP No. 1 and 2. A method to establish the tube plugging criteria of heat exchangers with straight tubes are introduced based on the USNRC Regulatory Guide 1.121. As an example, the tube plugging criterion for the CCW heat exchanger of a nuclear power plant is provided.

  19. Experimental observations on uniaxial whole-life transformation ratchetting and low-cycle stress fatigue of super-elastic NiTi shape memory alloy micro-tubes

    Science.gov (United States)

    Song, Di; Kang, Guozheng; Kan, Qianhua; Yu, Chao; Zhang, Chuanzeng

    2015-07-01

    In this work, the low-cycle fatigue failure of super-elastic NiTi shape memory alloy micro-tubes with a wall thickness of 150 μm is investigated by uniaxial stress-controlled cyclic tests at human body temperature 310 K. The effects of mean stress, peak stress, and stress amplitude on the uniaxial whole-life transformation ratchetting and fatigue failure of the NiTi alloy are observed. It is concluded that the fatigue life depends significantly on the stress levels, and the extent of martensite transformation and its reverse play an important role in determining the fatigue life. High peak stress or complete martensite transformation shortens the fatigue life.

  20. Experimental observations on uniaxial whole-life transformation ratchetting and low-cycle stress fatigue of super-elastic NiTi shape memory alloy micro-tubes

    International Nuclear Information System (INIS)

    Song, Di; Kang, Guozheng; Kan, Qianhua; Yu, Chao; Zhang, Chuanzeng

    2015-01-01

    In this work, the low-cycle fatigue failure of super-elastic NiTi shape memory alloy micro-tubes with a wall thickness of 150 μm is investigated by uniaxial stress-controlled cyclic tests at human body temperature 310 K. The effects of mean stress, peak stress, and stress amplitude on the uniaxial whole-life transformation ratchetting and fatigue failure of the NiTi alloy are observed. It is concluded that the fatigue life depends significantly on the stress levels, and the extent of martensite transformation and its reverse play an important role in determining the fatigue life. High peak stress or complete martensite transformation shortens the fatigue life. (paper)

  1. Flow forming of Al-Zn alloys 7075

    International Nuclear Information System (INIS)

    Abbas, G.

    1997-01-01

    Feasibility of flow forming aluminium alloy 7075 for manufacturing the tubes of about 70 mm diameter and different lengths has been studied. The elongation of the material was increased by increasing the working temperature of the process. Effect of various process parameters like roller rpm, roller offset, roller feed, spindle speed etc. on the flow ability of ally 7075 and the hardness and surface furnish of the tube has been determined. It was found that the roller bite and roller speed, of the flow forming machine, were two most important process parameters, which affected the hardness and the surface finish of the tube. By establishing the optimum process parameters, it was possible to produce aluminium alloy 7075 tubes of lengths ranging from 500 cm to 1 m with 70 mm outer diameter. The maximum hardness achieved on the surface of the tube was 146 Hv with good surface finish. (author)

  2. Condensation of refrigerants in horizontal microfin tubes. Numerical analysis of heat transfer for annular flow regime; Reibai no microfin tsuki suihei kannai gyoshuku. Kanjoryu ryoiki ni okeru netsudentatsu no suchi kaiseki

    Energy Technology Data Exchange (ETDEWEB)

    Nozu, S [Okayama Prefectural University, Okayama (Japan); Honda, H [Kyushu University, Fukuoka (Japan). Institute of Advanced Material Study

    1998-07-25

    A method for predicting the local heat transfer coefficient is presented for film condensation of vapor in a spirally grooved horizontal microfin-tube. Based on the flow observation study performed by the present authors, film flow model between fins in the annular flow regime is proposed. For the fin surface, laminar condensate film controlled by the combined effects of vapor shear and surface tension forces is analyzed. While, in the groove, thick condensate film driven by the vapor shear force is taken into consideration. A parameter which accounts for the transition from annular- to stratified flow regimes is also derived. The present and previous local heat transfer data for fluorocarbon refrigerants in the annular flow regime are found by the present numerical analysis to have a mean absolute deviation of 15.1 percent. 12 refs., 10 figs., 2 tabs.

  3. Flow patterns during refrigerant condensation in smooth and enhanced tubes

    OpenAIRE

    2009-01-01

    M.Ing. The Montreal Protocol led to the phasing-out of ozone layer depleting refrigerants and replacing them with more environmentally friendly refrigerants, which in many cases caused heat transfer degradation in heat exchanger equipment. To make up for the heat transfer degradation, there was a need for the application of heat transfer enhancement techniques. One such technique is the use of micro-fin tubes as opposed to traditional smooth tubes. The purpose of this study is to develop a...

  4. Effect of Elemental Sulfur and Sulfide on the Corrosion Behavior of Cr-Mo Low Alloy Steel for Tubing and Tubular Components in Oil and Gas Industry.

    Science.gov (United States)

    Khaksar, Ladan; Shirokoff, John

    2017-04-20

    The chemical degradation of alloy components in sulfur-containing environments is a major concern in oil and gas production. This paper discusses the effect of elemental sulfur and its simplest anion, sulfide, on the corrosion of Cr-Mo alloy steel at pH 2 and 5 during 10, 20 and 30 h immersion in two different solutions. 4130 Cr-Mo alloy steel is widely used as tubing and tubular components in sour services. According to the previous research in aqueous conditions, contact of solid sulfur with alloy steel can initiate catastrophic corrosion problems. The corrosion behavior was monitored by the potentiodynamic polarization technique during the experiments. Energy dispersive X-ray spectroscopy (EDS) and scanning electron microscopy (SEM) have been applied to characterize the corrosion product layers after each experiment. The results show that under the same experimental conditions, the corrosion resistance of Cr-Mo alloy in the presence of elemental sulfur is significantly lower than its resistance in the presence of sulfide ions.

  5. A simple modelling of mass diffusion effects on condensation with noncondensable gases for the CATHARE Code

    Energy Technology Data Exchange (ETDEWEB)

    Coste, P.; Bestion, D. [Commissariat a l Energie Atomique, Grenoble (France)

    1995-09-01

    This paper presents a simple modelling of mass diffusion effects on condensation. In presence of noncondensable gases, the mass diffusion near the interface is modelled using the heat and mass transfer analogy and requires normally an iterative procedure to calculate the interface temperature. Simplifications of the model and of the solution procedure are used without important degradation of the predictions. The model is assessed on experimental data for both film condensation in vertical tubes and direct contact condensation in horizontal tubes, including air-steam, Nitrogen-steam and Helium-steam data. It is implemented in the Cathare code, a french system code for nuclear reactor thermal hydraulics developed by CEA, EDF, and FRAMATOME.

  6. Define optimal conditions for steam generator tube integrity and an extended steam generator service life

    International Nuclear Information System (INIS)

    Lu, Y.C.

    2007-01-01

    Steam generator (SG) tubing materials are susceptible to corrosion degradation in certain electrochemical corrosion potential regions in the presence of some aggressive ions. Because of the hideout of impurities, the local chemistry conditions in areas under sludge and inside SG crevices may be very aggressive with high concentrations of chlorides and other impurities. These areas are the locations where SG tubing materials are susceptible to degradation such as pitting, crevice corrosion, intergranular attack (IGA) and stress corrosion cracking (SCC). The corrosion susceptibility of each SG alloy is different and is a function of the electrochemical corrosion potential (ECP) and chemical environment. Electrochemical corrosion behaviors of major SG tube alloys were studied under some plausible aggressive crevice chemistry conditions. The possible hazardous conditions leading to SG tube degradation and the conditions, which can minimize SG tube degradation have been determined. Optimal operating conditions in the form of a 'Recommended ECP/pH zone' for minimizing corrosion degradation have been defined for all major SG tube materials, including Alloys 600, 800, 690 and 400, under CANDU SG operating and startup conditions. SCC tests and accelerated corrosion tests were carried out to verify and revise the recommended ECP/pH zones. This information is being incorporated into ChemAND, a system health monitor for plant chemistry management developed by AECL, which alloys utilities to evaluate the status of the SG alloys and to minimize SG material degradation by appropriate SG water chemistry management. (author)

  7. Dry coolers and air-condensing units (Review)

    Science.gov (United States)

    Milman, O. O.; Anan'ev, P. A.

    2016-03-01

    The analysis of factors affecting the growth of shortage of freshwater is performed. The state and dynamics of the global market of dry coolers used at electric power plants are investigated. Substantial increase in number and maximum capacity of air-cooled condensers, which have been put into operation in the world in recent years, are noted. The key reasons facilitating the choice of developers of the dry coolers, in particular the independence of the location of thermal power plant from water sources, are enumerated. The main steam turbine heat removal schemes using air cooling are considered, their comparison of thermal efficiency is assessed, and the change of three important parameters, such as surface area of heat transfer, condensate pump flow, and pressure losses in the steam exhaust system, are estimated. It is shown that the most effective is the scheme of direct steam condensation in the heat-exchange tubes, but other schemes also have certain advantages. The air-cooling efficiency may be enhanced much more by using an air-cooling hybrid system: a combination of dry and wet cooling. The basic applied constructive solutions are shown: the arrangement of heat-exchange modules and the types of fans. The optimal mounting design of a fully shopassembled cooling system for heat-exchange modules is represented. Different types of heat-exchange tubes ribbing that take into account the operational features of cooling systems are shown. Heat transfer coefficients of the plants from different manufacturers are compared, and the main reasons for its decline are named. When using evaporative air cooling, it is possible to improve the efficiency of air-cooling units. The factors affecting the faultless performance of dry coolers (DC) and air-condensing units (ACU) and the ways of their elimination are described. A high velocity wind forcing reduces the efficiency of cooling systems and creates preconditions for the development of wind-driven devices. It is noted that

  8. Staking solutions to tube vibration problems (developed by Technos et Compagnie - FRANCE)

    International Nuclear Information System (INIS)

    Hewitt, E.W.; Bizard, A.; Horn, M.J.

    1989-01-01

    Electric generating plant steam surface condensers have been prone to vibration induced tube failures. One common and effective method for stopping this vibration has been to insert stakes into the bundle to provide additional support. Stakes have been fabricated of a variety of rigid and semi-rigid materials of fixed dimensions. Installation difficulties and problems of incomplete tube support have been associated with this approach. New developments in the application of plastic technology has offered another approach. Stakes made of plastic tubes which are flattened, by evacuation, at the time of manufacture may now be easily inserted into the tube bundle. After insertion, the vacuum is released and the memory of the plastic causes the stakes to expand and assume their original form. The spring force of the plastic cradles the adjacent condenser tubes and stops the vibration. Developed for Electricite de France (EDF), the stakes are currently installed in 19 units of the French utility system, and two units in the United States

  9. Condensing heat transfer following a loss-of-coolant accident

    International Nuclear Information System (INIS)

    Krotiuk, W.J.; Rubin, M.B.

    1978-01-01

    A new method for calculating the steam mass condensation energy removal rates on cold surfaces in contact with an air-steam mixture has been developed. This method is based on the principles of mass diffusion of steam from an area of high concentration to the condensing surface, which is an area of low steam concentration. This new method of calculating mass condensation has been programmed into the CONTEMPT-LT Mod 26 computer code, which calculates the pressure and temperature transients inside a light water reactor containment following a loss-of-coolant accident. The condensing heat transfer coefficient predicted by the mass diffusion method is compared to existing semi-empirical correlations and to the experimental results of the Carolinas Virginia Tube Reactor Containment natural decay test. Closer agreement with test results is shown in the calculation of containment pressure, temperature, and heat sink surface temperature using the mass diffusion condensation method than when using any existing semi-empirical correlation

  10. A color magnetic vortex condensate in QCD

    International Nuclear Information System (INIS)

    Ambjoern, J.; Olesen, P.

    1980-03-01

    It is shown that there exists a very close analogy between a lattice of vorticies in a superconductor near the critical field and a condensate of color magnetic flux tubes due to the unstable mode in QCD. This analogy makes it possible to identify a dynamical Higgs field in QCD. It is shown that the color magnetic flux tubes are quantized in terms of the center group Z(2) in the SU(2) case. In the case of SU(N) it is possible to select a color direction of the field such that one has Z(N) quantization. (Auth.)

  11. Delayed hydrogen cracking of zirconium alloy pressure tubes

    International Nuclear Information System (INIS)

    Jackman, A.H.; Dunn, J.T.

    1976-10-01

    After several years of almost continuous service, Pickering Units 3 and 4 have both experienced long outages to replace cracked pressure tubes. This report summarizes the status of the investigation into the cause of the cracks as of May 1976. The basic cause of the cracking was the presence of very high residual tensile stresses in the pressure tubes due to improper rolling procedures. These residual stresses are being reduced to acceptable levels by local stress relieving techniques at Bruce G.S. and in future reactors improvements in rolling procedures and changes in pressure tube specifications will prevent a recurrence of this problem. (author)

  12. Design and performance evaluation of a cryogenic condenser for an in-pile experiment

    Science.gov (United States)

    Graham, R. W.; Crum, R. J.; Hsu, Y.

    1972-01-01

    An apparatus was designed to enable in-pile irradiation of materials in liquid hydrogen at cryogenic temperatures. One of the principal components of this apparatus was a horizontal tube condenser. The performance of the condenser was evaluated by running a liquid-nitrogen prototype of the apparatus at heat loads comparable to or greater than those expected during the irradiation. The test showed that the condenser was capable of handling the design heat load and that the design procedure was sound.

  13. Advanced Ultrasupercritical (AUSC) Tube Membrane Panel Development

    Energy Technology Data Exchange (ETDEWEB)

    Pschirer, James [Alstom Power Inc., Windsor, CT (United States); Burgess, Joshua [Alstom Power Inc., Windsor, CT (United States); Schrecengost, Robert [Alstom Power Inc., Windsor, CT (United States)

    2017-08-16

    Alstom Power Inc., a wholly owned subsidiary of the General Electric Company (GE), has completed the project “Advanced Ultrasupercritical (AUSC) Tube Membrane Panel Development” under U.S. Department of Energy (DOE) Award Number DE-FE0024076. This project was part of DOE’s Novel Crosscutting Research and Development to Support Advanced Energy Systems program. AUSC Tube Membrane Panel Development was a two and one half year project to develop and verify the manufacturability and serviceability of welded tube membrane panels made from high performance materials suitable for the AUSC steam cycles, defined as high pressure steam turbine inlet conditions of 700-760°C (1292-1400°F) and 24.5-35MPa (3500-5000psi). The difficulty of this challenge lies in the fact that the membrane-welded construction imposes demands on the materials that are unlike any that exist in other parts of the boiler. Tube membrane panels have been designed, fabricated, and installed in boilers for over 50 years with relatively favorable experience when fabricated from carbon and Cr-Mo low alloy steels. The AUSC steam cycle requires membrane tube panels fabricated from materials that have not been used in a weldment with metal temperatures in the range of 582-610°C (1080-1130°F). Fabrication materials chosen for the tubing were Grade 92 and HR6W. Grade 92 is a creep strength enhanced ferritic Cr-Mo alloy and HR6W is a high nickel alloy. Once the materials were chosen, GE performed the engineering design of the panels, prepared shop manufacturing drawings, and developed manufacturing and inspection plans. After the materials were purchased, GE manufactured and inspected the tube membrane panels, determined if post fabrication heat treatment of the tube membrane panels was needed, performed pre- and post-weld heat treatment on the Grade 92 panels, conducted final nondestructive inspection of any heat treated tube membrane panels, conducted destructive inspection of the completed tube

  14. Probabilistic analysis of degradation incubation time of steam generator tubing materials

    International Nuclear Information System (INIS)

    Pandey, M.D.; Jyrkama, M.I.; Lu, Y.; Chi, L.

    2012-01-01

    The prediction of degradation free lifetime of steam generator (SG) tubing material is an important step in the life cycle management and decision for replacement of steam generators during the refurbishment of a nuclear station. Therefore, an extensive experimental research program has been undertaken by the Canadian Nuclear Industry to investigate the degradation of widely-used SG tubing alloys, namely, Alloy 600 TT, Alloy 690 TT, and Alloy 800. The corrosion related degradations of passive metals, such as pitting, crevice corrosion and stress corrosion cracking (SCC) etc. are assumed to start with the break down of the passive film at the tube-environment interface, which is characterized by the incubation time for passivity breakdown and then the degradation growth rate, and both are influenced by the chemical environment and coolant temperature. Since the incubation time and growth rate exhibit significant variability in the laboratory tests used to simulate these degradation processes, the use of probabilistic modeling is warranted. A pit is initiated with the breakdown of the passive film on the SG tubing surface. Upon exposure to aggressive environments, pitting corrosion may not initiate immediately, or may initiate and then re-passivate. The time required to initiate pitting corrosion is called the pitting incubation time, and that can be used to characterize the corrosion resistance of a material under specific test conditions. Pitting may be the precursor to other corrosion degradation mechanisms, such as environmentally-assisted cracking. This paper will provide an overview of the results of the first stage of experimental program in which samples of Alloy 600 TT, Alloy 690 TT, and Alloy 800 were tested under various temperatures and potentials and simulated crevice environments. The testing environment was chosen to represent layup, startup, and full operating conditions of the steam generators. Degradation incubation times for over 80 samples were

  15. Inconel alloys development -Development of the advanced nuclear materials-

    International Nuclear Information System (INIS)

    Kuk, Il Hiun; Jang, Jin Sung; Rhee, Chang Kyu; Chung, Man Kyo; Woo, Yun Myeoung; Han, Chang Hee

    1994-07-01

    We surveyed the current status and problems in S/G U-tubes in Korea and worldwide. Also we gathered manufacturing specifications of S/G U-tubes and compared/analyzed the differences in them company by company. We produced alloy 600 tubes (in cooperation with Sammi Special Steels) through V.I.M. (Vacuum Induction Melting; 2 ton capacity), 4 steps of hot press forging, hot extrusion (10:1 of reduction ratio), 3 steps of cold pilgerings and so on. We will continue to characterize the tubes and 2nd time preproduce the tubes using the feed-back data. With regard to alloy 690, which is getting popular for S/G U-tubes worldwide, we cast four 60 Kg ingots and two 6 Kg ingots by V.I.M.. We analyzed the chemical composition, macrostructures, hot workability, and so on ; all ingots were good except on 60 Kg ingot. Finally we produced high quality alloy 690 ingot (about 1 Kg) by E.S.R. (Electroslag Remelting) method (in cooperation with Yeoungnam University). We used CaF/CaO/Al2O3/MgO quartenary slag system. We have made directionally grown good ingots by E.S.R. and especially the hot workability at 1100 deg C - the temperature at which V.I.M. ingots showed very poor hot workability - was very much improved (from 30 to 90 % of reduction of area). We continue to analyze the effects of E.S.R. to the structure and properties of alloy 690 (grain size, morphology, and directionality; any changes of inclusions and so on). (Author)

  16. Delayed Hydride Cracking Mechanism in Zirconium Alloys and Technical Requirements for In-Service Evaluation of Zr-2.5Nb Tubes with Flaws

    International Nuclear Information System (INIS)

    Kim, Young Suk

    2007-01-01

    In association with periodic inspection of CANDU nuclear power plant components, Canadian Standards Association issued CSA N285.8 in 2005 as technical requirements for in-service evaluation of zirconium alloy pressure tubes in CANDU reactors. This first version, CSA N285.8 involves procedures for, firstly, the evaluation of pressure tube flaws, secondly, the evaluation of pressure tube to calandria tube contact and, thirdly, the assessment of a reactor core, and material properties and derived quantities. The evaluation of pressure tube flaws includes delayed hydride cracking evaluation the procedures of which are stipulated based on the existing delayed hydride cracking models. For example, the evaluation of flaw-tip hydride precipitation during reactor cooldown involves a procedure to calculate the equilibrium hydrogen equivalent concentration in solution at the flaw tip, Htipas follows: Htip=Hfexp[- (VH delta no.)/RT], where Hf is the total bulk hydrogen equivalent concentration, VH partial molar volume of hydrogen in zirconium, δ a difference in hydrostatic stress between the bulk and the crack tip. When Htip ≥TSSP at temperature, then flaw-tip hydride is predicted to precipitate. Eq. (1) suggests that hydrogen concentration at the crack tip would increase due to an work energy given by the difference in the hydrostatic stress

  17. State-of-the-art review of OPG steam generator tubing degradation mechanisms

    International Nuclear Information System (INIS)

    Brennenstuhl, A.M.; Ramamurthy, S.; Good, G.M.

    2009-01-01

    Steam generator (SG) degradation has been a major cause of pressurized water reactor (PWR) incapability world-wide and has limited the useful life of SGs at some utilities. The vast majority of the degradation has been the result of SCC of the thin walled nickel alloy SG tubes and has been most prevalent in mill annealed (MA) Alloy 600. Fortunately, Ontario Power Generation (OPG) SG tubes are manufactured from alloys that have much better resistance to this form of localized corrosion than Alloy 600MA and as a consequence have not encountered SCC to date. Other forms of degradation nevertheless have been experienced; some units at Pickering - B in particular have had many Alloy 400 SG tubes removed from service due to severe underdeposit corrosion (UDC) and costly modifications have been made to Darlington SGs to prevent leaks as a result of SG tube fretting-wear at tube supports. Degradation other than UDC and fretting-wear which could pose a threat to the future reliable operation of OPG's nuclear fleet has also been observed. Important activities in effectively managing SG degradation include determining the mode of degradation and arriving at an understanding of the contributing factors. This is done by a combination of non-destructive examination (NDE) of SG tubing in-situ, SG tube removals for metallurgical examination and research and development. SG tube metallurgical examinations provide information that can be used in the timely development of a strategy dealing with the degradation in the short to intermediate timeframe. Determining the main causative factors at a mechanistic level helps to improve the predictive capability and increases the probability of dealing with the problem in the most cost-effective way. OPG has used this approach together with in-situ NDE inspections during planned outages of its nuclear reactors to minimize the possibility of unscheduled outages and provide the best possible fitness-for-service assessments. Many metallurgical

  18. Evaluation on mechanical and corrosion properties of steam generator tubing materials

    International Nuclear Information System (INIS)

    Kim, In Sup; Lee, Byong Whi; Lee, Sang Kyu; Lee, Young Ho; Kim, Jun Whan; Lee, Ju Seok; Kwon, Hyuk Sang; Kim, Su Jung

    1998-06-01

    Steam generator is one of the major components of nuclear reactor pressure boundary. It's main function os transferring heat which generated in the reactor to turbine generator through steam generator tube. In these days, steam generator tubing materials of operating plant are used Inconel 600 alloys. But according to the operation time, there are many degradation phenomena which included mechanical damage due to flow induced vibration and corrosion damage due to PWSCC, IGA/SCC and pitting etc. Recently Inconel 690 alloys are selected as new and replacement steam generator tubes for domestic nuclear power plant. But there are few study about mechanical and corrosion properties of Inconel 600 and 690. The objectives of this study is to evaluate and compare mechanical and corrosion propertied of steam generator tube materials

  19. Evaluation on mechanical and corrosion properties of steam generator tubing materials

    Energy Technology Data Exchange (ETDEWEB)

    Kim, In Sup; Lee, Byong Whi; Lee, Sang Kyu; Lee, Young Ho; Kim, Jun Whan; Lee, Ju Seok; Kwon, Hyuk Sang; Kim, Su Jung [Korea Advanced Institute of Science and Technology, Taejon (Korea, Republic of)

    1998-06-15

    Steam generator is one of the major components of nuclear reactor pressure boundary. It's main function os transferring heat which generated in the reactor to turbine generator through steam generator tube. In these days, steam generator tubing materials of operating plant are used Inconel 600 alloys. But according to the operation time, there are many degradation phenomena which included mechanical damage due to flow induced vibration and corrosion damage due to PWSCC, IGA/SCC and pitting etc. Recently Inconel 690 alloys are selected as new and replacement steam generator tubes for domestic nuclear power plant. But there are few study about mechanical and corrosion properties of Inconel 600 and 690. The objectives of this study is to evaluate and compare mechanical and corrosion propertied of steam generator tube materials.

  20. Wear behavior of steam generator tubes in nuclear power plant operating condition

    International Nuclear Information System (INIS)

    Kim, In-Sup; Hong, Jin-Ki; Kim, Hyung-Nam; Jang, Ki-Sang

    2003-01-01

    Reciprocating sliding wear tests were performed on steam generator tubes materials at steam generator operating temperature. The material surfaces react with oxygen to form oxides. The oxide properties such as formation rate and mechanical properties are varied with the test temperature and alloy composition. So, it is important to investigate the wear properties of each steam generator tube materials in steam generator operating condition. The tests results indicated that the wear coefficient in work rate model of alloy 690 was faster than that of alloy 800. From the scanning electron microscopy observation, the wear scars were similar each other and worn surfaces were covered with oxide layers. It seemed that the oxide layers were formed by wear debris sintering or cold welding and these layer properties affected the wear rate of steam generator tube materials. (author)

  1. Expanded heat treatment to form residual compressive hoop stress on inner surface of zirconium alloy tubing

    International Nuclear Information System (INIS)

    Megata, Masao

    1997-01-01

    A specific heat treatment process that introduces hoop stress has been developed. This technique can produce zirconium alloy tubing with a residual compressive hoop stress near the inner surface by taking advantage of the mechanical anisotropy in hexagonal close-packed zirconium crystal. Since a crystal having its basal pole parallel to the tangential direction of the tubing is easier to exhibit plastic elongation under the hoop stress than that having its basal pole parallel to the radial direction, the plastic and elastic elongation can coexist under a certain set of temperature and hoop stress conditions. The mechanical anisotropy plays a role to extend the coexistent stress range. Thus, residual compressive hoop stress is formed at the inner surface where more plastic elongation occurs during the heat treatment. This process is referred to as expanded heat treatment. Since this is a fundamental crystallographic principle, it has various applications. The application to improve PCI/SCC (pellet cladding interaction/stress corrosion cracking) properties of water reactor fuel cladding is promising. Excellent results were obtained with laboratory-scale heat treatment and an out-reactor iodine SCC test. These results included an extension of the time to SCC failure. (author)

  2. Changes in the design, fabrication and setting of guide tube support pins in alloy X750

    International Nuclear Information System (INIS)

    Benhamou, C.; Chambrin, J.L.; Todeschini, P.; Champredonde, J.; Lemaire, E.

    2004-01-01

    As a consequence of a problem of stress corrosion cracking (SCC) encountered on guide tube support pins (GTSP) of first generation (1982) and of second generation (1987), EDF and Framatome decided in mars 1988 to launch an important program involving a complete overhaul of the design, the material used, the fabrication and the setting in reactor of GTSP. This program has led to the implementation in 900 MWe and 1300 MWe PWR of a new tube guide support pin called NG89. This implementation began in 1989, now 15 years later, 40% of the operating GTSP in 900 MWe and 1300 MWe PWR are of NG89 type, the oldest ones cumulate 105000 hours in service without negative feedback experience. The main features of the NG89 is: - to be made from an alloy X-750 containing boron (from 25 to 45 ppm) - to have a SCC threshold set at 720 MPa - to be machined from metal bars completely treated, - to have a rolling of the fillets, and - to undergo a shot blasting on the zones of the surface the most acted upon. (A.C.)

  3. Effect of heat treatment and composition on stress corrosion cracking of steam generation tubing materials

    International Nuclear Information System (INIS)

    Kim, H. P.; Hwang, S. S.; Kuk, I. H.; Kim, J. S.; Oh, C. Y.

    1998-01-01

    Effects of heat treatment and alloy composition on stress corrosion cracking (SCC) of steam generator tubing materials have been studied in 40% NaOH at 315.deg.C at potential of +200mV above corrosion potential using C-ring specimen and reverse U bend specimen. The tubing materials used were commercial Alloy 600, Alloy 690 and laboratory alloys, Ni-χCr-10Fe. Commercial Alloy 600, Alloy 690 were mill annealed or thermally treated.Laboratory alloy Ni-χCr-10Fe, and some of Alloy 600 and Alloy 690 were solution annealed. Polarization curves were measured to find out any relationship between SCC susceptibility and electrochemical behaviour. The variation in thermal treatment of Alloy 600 and Alloy 690 had no effect on polarization behaviour probably due to small area fraction of carbide and Cr depletion zone near grain boundary. In anodic polarization curves, the first and second anodic peaks at about 170mV and about at 260mV, respectively, above corrosion potential were independent of Cr content, whereas the third peak at 750mV above corrosion potential and passive current density in-creased with Cr content. SCC susceptibility decreased with Cr content and thermal treatment producing semicontinuous grain boundary decoration. Examination of cross sectional area of C-ring specimen showed deep SCC cracks for the alloys with less than 17%Cr and many shallow attacks for alloy 690. The role of Cr content in steam generator tubing materials and grain boundary carbide on SCC were discussed

  4. Fireside corrosion testing of candidate superheater tube alloys, coatings, and claddings -- Phase 2

    Energy Technology Data Exchange (ETDEWEB)

    Blough, J.L.; Seitz, W.W. [Foster Wheeler Development Corp., Livingston, NJ (United States)

    1997-12-01

    In Phase 1 a variety of developmental and commercial tubing alloys and claddings were exposed to laboratory fireside corrosion testing simulating a superheater or reheater in a coal-fired boiler. Phase 2 (in situ testing) has exposed samples of 347 RA-85H, HR3C, 253MA, Fe{sub 3}Al + 5Cr, 310 Ta modified, NF 709, 690 clad, and 671 clad for approximately 4,000, 12,000, and 16,000 hours to the actual operating conditions of a 250-MW coal-fired boiler. The samples were assembled on an air-cooled, retractable corrosion probe, the probe was installed in the reheater activity of the boiler and controlled to the operating metal temperatures of an existing and advanced-cycle coal-fired boiler. The results will be presented for the preliminary metallurgical examination of the corrosion probe samples after 16,000 hours of exposure. Continued metallurgical and interpretive analysis is still on going.

  5. Re-Condensation and Liquefaction of Helium and Hydrogen Using Coolers

    International Nuclear Information System (INIS)

    Green, Michael A.

    2009-01-01

    Coolers are used to cool cryogen free devices at temperatures from 5 to 30 K. Cryogen free cooling involves a temperature drop within the device being cooled and between the device and the cooler cold heads. Liquid cooling with a liquid cryogen distributed over the surface of a device combined with re-condensation can result in a much lower temperature drop between the cooler and the device being cooled. The next logical step beyond simple re-condensation is using a cooler to liquefy the liquid cryogen in the device. A number of tests of helium liquefaction and re-condensation of helium have been run using a pulse tube cooler in the drop-in mode. This report discusses the parameter space over which re-condensation and liquefaction for helium and hydrogen can occur.

  6. Preparation of metallic uranium tubes; Elaboration des tubes d'uranium metallique

    Energy Technology Data Exchange (ETDEWEB)

    Lerouge, G; Decours, J [Commissariat a l' Energie Atomique, Saclay (France). Centre d' Etudes Nucleaires

    1964-07-01

    The production furnace is an induction heated vacuum furnace having a capacity at the moment of 250 kg. Previously the crucible was heated by the inductor, the mould being outside the inductor. The tubes thus produced contained cavities, the alloy structure was fine; this was cold-mould casting, At the moment the top of the moulds are pre-heated, this is the so called hot-mould casting. This method has the advantage of eliminating the cavities but leads to a less fine microstructure. The alloy used for the 18 x 40 mm and 23 x 43 mm tubes is U-Mo (1.1 per cent). Since the moulds are now heated at the top, the solidification of the metal is very slow in this zone leading to a pronounced {gamma} grain, whereas towards the base the faster cooling leads to a smaller {gamma} grain. The {gamma} structure depends essentially on the solidification rate and on the time spent in this zone. In order to obtain a fine and homogeneous grain along the whole length of the tube, a controlled cooling treatment is effected. It consists in heating the uranium tubes in the {gamma} place and then in cooling them at a rate of between 20 and 50 deg C/mm down to 400 deg C. The 77 x 95 mm and 54 x 70 mm annular elements are at the moment being produced for research purposes. Their preparation is similar to that of 18 x 40 mm and 23 x 43 mm elements. The 77 x 95 mm tubes are at the moment made from U-Cr alloy (0.1 per cent); because of their size, their preparation is carried out in 600 mm diameter furnaces. (authors) [French] Le four d'elaboration est un four sous vide chaufffe par induction, dont la capacite actuelle est de 250 kg. Anterieurement le creuset seul etait chauffe par l'inducteur, les moules etaient hors de l'inducteur. Les tubes obtenus presentaient des cavites, la structure de l'alliage etait fine, c'etait la coulee en moules froids. Actuellement on prechauffe le haut des moules, c'est la coulee dite en moules chauds. Cette facon de faire a l'avantage de supprimer les cavites

  7. Stationary flow in magnetic tubes of force

    International Nuclear Information System (INIS)

    Engvold, O.; Jensen, E.

    1976-01-01

    For one particular set of boundary conditions Pikel'ner obtained a stationary solution displaying a condensation, which he applied to quiescent prominences. Calculations in the stationary case for a range of parameters have been carried out, after some modifications of the basic equations. These modifications involved a complete non-LTE formulation of the ionization equilibrium, an improved radiative loss-function and more accurate values of the thermodynamic parameters. The calculations were carried out for a hydrogen helium mixture with B = 10 and for a pure hydrogen gas. The solutions were terminated where the optical thickness in lyα along the tube exceeded unity, corresponding to T approx.equal to 20 000K. The solutions are strongly dependent upon the geometry of the tube of force. Condensations may be made to appear on the ascending as well as on the descending branch of the magnetic arch by varying the parameters. Solutions also depend strongly upon the energy input into the tube at the footpoint, mainly determined by the injection velocity and the starting value of the temperature gradient. The radiative loss is of less importance for the values of the gas pressure close to the Pikel'ner case. Recent observational data indicate gas pressure in the chromosphere corona transition region as much as 4 times the boundary pressure assumed by Pikel'ner. Such a high initial pressure, however, produce no condensation. In the temperature range 1.2x10 5 K > T > 5x10 4 K the temperature gradients in the condensations are in fair agreement with observations of the CIII lines in the EUV-region. For higher temperatures 5x10 5 K > T > 2x10 5 K our temperature gradients are much smaller than those indicated by observations. (Auth.)

  8. Condensate polisher application for PWR steam generator corrosion control

    International Nuclear Information System (INIS)

    Sawochka, S.G.; Leibovitz, J.; Siegwarth, D.P.; Pearl, W.L.

    1981-01-01

    The evolution of corrosion attack modes particularly in recirculating U-tube PWR steam generators has dictated a thorough review of the advantages and disadvantages of condensate polishing. Analytical modeling techniques to qualitatively predict crevice chemistry variations resulting from steam generator bulk water variations have allowed valuable insights to be developed. Modeling results complemented by steam generator and laboratory corrosion data will be employed to set condensate demineralizer effluent specifications consistent with control of steam generator corrosion. Laboratory and plant studies are being performed to demonstrate achievability of necessary effluent specifications. (author)

  9. Effects of homogeneous condensation in compressible flows: Ludwieg-tube experiments and simulations

    NARCIS (Netherlands)

    Luo, X.; Lamanna, G.; Holten, A.P.C.; Dongen, van M.E.H.

    2007-01-01

    Effects of homogeneous nucleation and subsequent droplet growth in compressible flows in humid nitrogen are investigated numerically and exptl. A Ludwieg tube is employed to produce expansion flows. Corresponding to different configurations, three types of expt. are carried out in such a tube.

  10. SCC testing of steam generator tubes repaired by welded sleeves

    International Nuclear Information System (INIS)

    Pierson, E.; Stubbe, J.

    1993-01-01

    One way to repair steam generator tubing is to introduce a sleeve inside the tube so that it spans the corroded area and to seal it at both ends. This technique has been studied at Laborelec with a particular attention paid to the occurrence of new SCC cracks at the upper joint. Tube segments coming from the same lot of mill annealed alloy 600 were sent to six manufacturers to be sleeved by their own procedure (including TIG, laser or kinetic welding, followed or not by a stress relief heat treatment), and then tested at Laborelecin 10% NaOH at 350 degrees C. The tests were performed with and without differential pressure i.e. in capsules (Δ = 9 and 19 MPa) and in autoclave (Δp = 0). Nearly all the not stress relieved mock-ups developed through cracks in several hundred hours in auto-clave. The cracks were circumferential and situated near the weld. At 9 and 19 MPa, the time to failure decreased and longitudinal cracks appeared near the weld and at the transition zone of expanded areas. Cracks were never observed in the alloy 690 sleeve, except in the weld bead. Reference capsules (roll expaned tubes) made of the same lot of alloy 600 were tested in the same environment

  11. X-ray tube targets

    International Nuclear Information System (INIS)

    Hirsch, H.H.

    1980-01-01

    In rotary targets for X-ray tubes warping is a problem which causes X-ray deficiency. A rotary target is described in which warping is reduced by using alloys of molybdenum with 0.05 to 10% iron, silicon, cobalt, tantalum, niobium, hafnium, stable metal oxide or mixture thereof. Suitable mixtures are 0.5 to 10% of tantalum, niobium or hafnium with from 0.5 to 5% yttrium oxide, or 0.05 to 0.3% of cobalt or silicon. Optionally 0.1 to 5% by weight of additional material may be alloyed with the molybdenum, such as tantalum or hafnium carbides. (author)

  12. Improving the antimicrobial properties of titanium condenser material by surface modification using nanotechnology

    International Nuclear Information System (INIS)

    George, Rani P.; Dash, S.; Krishnan, R.; Kamruddin, M.; Kalavathi, S.; Tyagi, A.K.; Manoharan, N.; Dayal, R.K.; Vishwakarma, Vinita; Theresa, Josephine

    2008-01-01

    Biofouling is one of the major problems faced by condenser materials of power plants using seawater for cooling. Fouling control strategies in condensers include a combination of mechanical and chemical treatments like sponge ball cleaning, back washing and chlorination. In general, numerous studies have shown that no routine treatment regime can successfully keep the condenser tube clean over a period extending to years. Surface properties of the substratum influence initial adhesion and growth of bacterial cells on materials, modification of the surface for mitigating microbial attachment is the need of the hour. Metal nanoparticles are known to exhibit enhanced physical and chemical properties when compared to their bulk counter parts because of their high surface to volume ratios. Metals like copper are very toxic to microorganisms and effectively kill most of the microbes by blocking the respiratory enzyme. Copper alloys with their excellent resistance to biofouling are used extensively for marine applications. However, they are prone to localized corrosion initiation and consequently are getting replaced by extremely corrosion resistant titanium. Still, the inertness and biocompatibility of titanium makes it very susceptible to biofouling. Hence, this study attempts to use nano technology methods of surface modification of titanium using thin film of copper and also multilayers and bilayers of copper and nickel. This is aimed at improving the antimicrobial properties of this condenser pipe material. These nano structured thin films have been grown on titanium substrate using pulsed DC magnetron-sputtering and pulsed laser deposition. The thin films were characterized using Atomic Force Microscopy (AFM), Glancing Incidence X-ray Diffraction (GIXRD) and scanning electron microscopy (SEM with EDAX analysis). Antimicrobial properties were evaluated by exposure studies in seawater and bacterial cultures and by post exposure analysis using culture and

  13. Proceedings of the 9. National Meeting on Condensed Matter Physics

    International Nuclear Information System (INIS)

    1986-01-01

    The 9. National Meeting on Condensed Matter Physics presents works developed in the following fields: amorphous materials, atomic and molecular physics, biophysics, crystallography, defects, growth and critical phenomena, instrumentation, liquid crystals, magnetism, matter science/mechanical properties, metals and alloys, optic, magnetic resonance and semiconductors. (M.C.K.) [pt

  14. Proceedings of the 12. National Meeting on Condensed Matter Physics

    International Nuclear Information System (INIS)

    1989-01-01

    The XII National Meeting on Condensed Matter Physics presented works in the areas: atomic and molecular physics; biophysics; crystallography; defects growth and characterization of crystals; instrumentation; liquid crystals; magnetism; science of materials, metals and alloys; magnetic resonance; semiconductors; superconductivity and; surfaces and thin films. (M.C.K.) [pt

  15. Analysis of hafnium in zirconium alloys

    International Nuclear Information System (INIS)

    Kondo, Isao; Sakai, Fumiaki; Ohuchi, Yoshifusa; Nakamura, Hisashi

    1977-01-01

    It is required to analyse alloying components and impurity elements in the acceptance analysis of zirconium alloys as the material for fuel cladding tubes and pressure tubes for advanced thermal reactors. Because of extreme similarity in chemical properties between zirconium and hafnium, about 100 ppm of hafnium is usually contained in zirconium alloys. Zircaloy-2 alloy and 2.5% Nb-zirconium with the addition of hafnium had been prepared as in-house standard samples for rapid analysis. Study was made on fluorescent X-ray analysis and emission spectral analysis to establish the analytical method. By using these in-house standard samples, acceptance analysis was successfully carried out for the fuel cladding tubes for advanced thermal reactors. Sulfuric acid solution was prepared from JAERI-Z 1, 2 and 3, the standard sample for zircaloy-2 prepared by the Analytical Committee on Nuclear Fuel and Reactor Materials, JAERI, and zirconium oxide (Hf 1 ppm/Zr). Standard Hf solution was added to the sulfuric acid solution step by step, to make up a series of the standard oxide samples by the precipitation process. By the use of these standard samples, the development of the analytical method and joint analysis were made by the three-member analytical technique research group including PNC. The analytical precision for the fluorescent X-ray analysis was improved by attaching a metallic yttrium filter to the window of an X-ray tube so as to suppress the effect due to zirconium matrix. The variation factor of the joint analysis was about 10% to show good agreement, and the indication value was determined. (Kobatake, H.)

  16. Condensation heat transfer of a feed-water heater and improvement of its performance

    International Nuclear Information System (INIS)

    Takamori, Kazuhide; Murase, Michio; Baba, Yoshikazu; Aihara, Tsuyoshi

    1995-01-01

    In this study, a condensation heat transfer model, coupled with a three-dimensional two-phase flow analysis, was developed. In the heat transfer model, the liquid film flow rate on the heat transfer tubes was calculated by a mass balance equation and the liquid film thickness was calculated from the liquid film flow rate using Nusselt's laminar flow model and Fujii's equation for the steam velocity effect. The model was verified by condensation heat transfer experiments. In the experiments, 112 horizontal, staggered tubes with an outer diameter of 16mm and length of 0.55m were used. The calculated over-all heat transfer coefficients agreed with the data within ±5% under the inlet quality conditions of 13-100%. Based on a three-dimensional two-phase flow analysis, an improved feed-water heater with support plates, which have flow holes between the upper and lower tube bundles, was designed. The total heat exchange capacity of the improved feed-water heater increased about 6%. (author)

  17. Preparation of metallic uranium tubes; Elaboration des tubes d'uranium metallique

    Energy Technology Data Exchange (ETDEWEB)

    Lerouge, G.; Decours, J. [Commissariat a l' Energie Atomique, Saclay (France). Centre d' Etudes Nucleaires

    1964-07-01

    The production furnace is an induction heated vacuum furnace having a capacity at the moment of 250 kg. Previously the crucible was heated by the inductor, the mould being outside the inductor. The tubes thus produced contained cavities, the alloy structure was fine; this was cold-mould casting, At the moment the top of the moulds are pre-heated, this is the so called hot-mould casting. This method has the advantage of eliminating the cavities but leads to a less fine microstructure. The alloy used for the 18 x 40 mm and 23 x 43 mm tubes is U-Mo (1.1 per cent). Since the moulds are now heated at the top, the solidification of the metal is very slow in this zone leading to a pronounced {gamma} grain, whereas towards the base the faster cooling leads to a smaller {gamma} grain. The {gamma} structure depends essentially on the solidification rate and on the time spent in this zone. In order to obtain a fine and homogeneous grain along the whole length of the tube, a controlled cooling treatment is effected. It consists in heating the uranium tubes in the {gamma} place and then in cooling them at a rate of between 20 and 50 deg C/mm down to 400 deg C. The 77 x 95 mm and 54 x 70 mm annular elements are at the moment being produced for research purposes. Their preparation is similar to that of 18 x 40 mm and 23 x 43 mm elements. The 77 x 95 mm tubes are at the moment made from U-Cr alloy (0.1 per cent); because of their size, their preparation is carried out in 600 mm diameter furnaces. (authors) [French] Le four d'elaboration est un four sous vide chaufffe par induction, dont la capacite actuelle est de 250 kg. Anterieurement le creuset seul etait chauffe par l'inducteur, les moules etaient hors de l'inducteur. Les tubes obtenus presentaient des cavites, la structure de l'alliage etait fine, c'etait la coulee en moules froids. Actuellement on prechauffe le haut des moules, c'est la coulee dite en moules chauds. Cette facon de faire a l

  18. Impact of the surface roughness of AISI 316L stainless steel on biofilm adhesion in a seawater-cooled tubular heat exchanger-condenser.

    Science.gov (United States)

    García, Sergio; Trueba, Alfredo; Vega, Luis M; Madariaga, Ernesto

    2016-11-01

    The present study evaluated biofilm growth in AISI 316L stainless steel tubes for seawater-cooled exchanger-condensers that had four different arithmetic mean surface roughness values ranging from 0.14 μm to 1.2 μm. The results of fluid frictional resistance and heat transfer resistance regarding biofilm formation in the roughest surface showed increases of 28.2% and 19.1% respectively, compared with the smoothest surface. The biofilm thickness taken at the end of the experiment showed variations of up to 74% between the smoothest and roughest surfaces. The thermal efficiency of the heat transfer process in the tube with the roughest surface was 17.4% greater than that in the tube with the smoothest surface. The results suggest that the finish of the inner surfaces of the tubes in heat exchanger-condensers is critical for improving energy efficiency and avoiding biofilm adhesion. This may be utilised to reduce biofilm adhesion and growth in the design of heat exchanger-condensers.

  19. Dynamic Modeling of Steam Condenser and Design of PI Controller Based on Grey Wolf Optimizer

    OpenAIRE

    Shu-Xia Li; Jie-Sheng Wang

    2015-01-01

    Shell-and-tube condenser is a heat exchanger for cooling steam with high temperature and pressure, which is one of the main kinds of heat exchange equipment in thermal, nuclear, and marine power plant. Based on the lumped parameter modeling method, the dynamic mathematical model of the simplified steam condenser is established. Then, the pressure PI control system of steam condenser based on the Matlab/Simulink simulation platform is designed. In order to obtain better performance, a new meta...

  20. Numerical and Experimental Analysis on the Cavity Formation and Shrinkage for Investment Cast Alloy 738 4 mm-Thick Rectangular Tube

    International Nuclear Information System (INIS)

    Park, Myeong-Il; Choi, Yoon Suk; Yoo, Jae-Hyun; Park, Sang-Hu; Kim, Kyeong-Min; Lee, Yeong-Chul; Lee, Jung-Seok; Lee, Jae-Hyun

    2017-01-01

    Investment casting for the thin (4 mm thick) rectangular tube (40 mm wide, 80 mm high and 200 mm long) was carried out numerically and experimentally for Alloy 738, which is a precipitation-hardened Ni-base superalloy. Two types of rectangular tubes, one with a regular array (10 mm by 10 mm square array) of protruded rods (3 mm in diameter and 3mm in height) embedded on the outer surface and the other with just smooth surface, were investment-cast at the same time through the side feeding mold design. The investment casting simulation predicted the presence of cavities, particularly in the area away from the gate for both types of rectangular tubes. In particular, for the rectangular tube with embedded protruded rods cavities were found mainly in the areas between the protruded rods. This simulation result was qualitatively consistent with the experimental observation from the X-ray analysis. Also, both prediction and experiment showed that the dimensional shrinkage (particularly in the longitudinal direction) of the investment-cast rectangular tube is reduced by having protruded rods embedded on the outer surface. Additional numerical attempts were made to check how the amount of cavities and dimensional shrinkage change by varying the preheating temperature and the thickness of the mold. The results predicted that the amount of cavities and the dimensional shrinkage are significantly reduced by increasing the preheating temperature of the mold by 200 ℃. However, an increase in mold thickness from 10 mm to 12 mm showed almost no difference in cavity population and a slight decrease in dimensional shrinkage.

  1. Numerical and Experimental Analysis on the Cavity Formation and Shrinkage for Investment Cast Alloy 738 4 mm-Thick Rectangular Tube

    Energy Technology Data Exchange (ETDEWEB)

    Park, Myeong-Il; Choi, Yoon Suk; Yoo, Jae-Hyun; Park, Sang-Hu [Pusan National University, Busan (Korea, Republic of); Kim, Kyeong-Min; Lee, Yeong-Chul [Sung Il Turbine Co., Ltd., Busan (Korea, Republic of); Lee, Jung-Seok; Lee, Jae-Hyun [Changwon National University, Changwon (Korea, Republic of)

    2017-02-15

    Investment casting for the thin (4 mm thick) rectangular tube (40 mm wide, 80 mm high and 200 mm long) was carried out numerically and experimentally for Alloy 738, which is a precipitation-hardened Ni-base superalloy. Two types of rectangular tubes, one with a regular array (10 mm by 10 mm square array) of protruded rods (3 mm in diameter and 3mm in height) embedded on the outer surface and the other with just smooth surface, were investment-cast at the same time through the side feeding mold design. The investment casting simulation predicted the presence of cavities, particularly in the area away from the gate for both types of rectangular tubes. In particular, for the rectangular tube with embedded protruded rods cavities were found mainly in the areas between the protruded rods. This simulation result was qualitatively consistent with the experimental observation from the X-ray analysis. Also, both prediction and experiment showed that the dimensional shrinkage (particularly in the longitudinal direction) of the investment-cast rectangular tube is reduced by having protruded rods embedded on the outer surface. Additional numerical attempts were made to check how the amount of cavities and dimensional shrinkage change by varying the preheating temperature and the thickness of the mold. The results predicted that the amount of cavities and the dimensional shrinkage are significantly reduced by increasing the preheating temperature of the mold by 200 ℃. However, an increase in mold thickness from 10 mm to 12 mm showed almost no difference in cavity population and a slight decrease in dimensional shrinkage.

  2. Mitigation of caustic stress corrosion cracking of steam generator tube materials by blowdown -a case study

    International Nuclear Information System (INIS)

    Dutta, Anu; Patwegar, I.A.; Chaki, S.K.; Venkat Raj, V.

    2000-01-01

    The vertical U-tube steam generators are among the most important equipment in nuclear power plants as they form the vital link between the reactor and the turbogenerator. Over ∼ 35 years of operating experience of water cooled reactor has demonstrated that steam generator tubes are susceptible to various forms of degradation. This degradation leads to failure and outages of the power plant. A majority of these failures have been attributed to concentrated alkali attacks in the low flow areas such as crevices in the tube to tube sheet joints, baffle plate location and the areas of sludge deposits. Free hydroxides can be produced by improper maintenance of phosphate chemical control in the secondary side of the steam generators and also by the thermal decomposition of impurities present in the condenser cooling water which may leak into the feed water through the condenser tubes. The free hydroxides concentrate in the low flow areas. This buildup of free hydroxide in combination with residual stress leads to caustic stress corrosion cracking. In order to mitigate caustic stress corrosion cracking of Inconel 600 tubes, the trend is to avoid phosphate dosing. Instead All Volatile Treatment (AVT) for secondary water is used backed by full flow condensate polishing. Sodium hydroxide concentration is now being considered as the basis for steam generator blowdown. A methodology has been established for determining the blowdown requirement in order to mitigate caustic stress corrosion cracking in the secondary side of the vertical U-tube natural circulation steam generator. A case study has been carried out for zero solid treatment (AVT coupled with full flow condensate polishing plant) water chemistry. Only continuous blowdown schemes have been studied based on maximum caustic concentration permissible in the secondary side of the steam generator. The methodology established can also be used for deciding concentration of any other impurities

  3. Environmental sustainability by adoption of alternate cooling media for condenser cooling

    International Nuclear Information System (INIS)

    Gandhi, Jaymin; Patel, Nilesh

    2015-01-01

    Water having ability to dissolve most substances and to support biological life, every cooling water system in power plant is subjected to potential operational problems which are mainly corrosion, scaling and biological fouling. Control of cooling water chemistry is very critical in preventing above said problems. In view of scarcity of water and looking into the future trends in the environment protection, water media can be replaced with air. Having such concept in thermal and combined cycle power plants, use of Air-cooled condenser (ACC) for Nuclear power plant may be explored. During last decade number of installations with ACC also increased, largely in response to the growing attention being paid to environmental concerns as well of water scarcity. The rising importance of 'Save Water and Environment', calls for a broader understanding of the design and application principles involved for ACC. This paper identifies the basic configurations of air cooled condensers used in the power industry together with their merits and demerits when compared to those exhibited by traditional steam surface condensers including environmental and corrosion issues. Several factors that affect the performance of air-cooled condensers are described in detail, especially the consequences that result from the fouling of the finned-tubes. To rectify the degradations in performance that result from external tube fouling, a number of cleaning procedures are described. Due to relatively high cost of sweet water and large requirement of sea water, Air cooled condenser may become viable option in future. (author)

  4. Aeronautical requirements for Inconel 718 alloy

    Science.gov (United States)

    Elefterie, C. F.; Guragata, C.; Bran, D.; Ghiban, B.

    2017-06-01

    The project goal is to present the requirements imposed by aviation components made from super alloys based on Nickel. A significant portion of fasteners, locking lugs, blade retainers and inserts are manufactured from Alloy 718. The thesis describes environmental factors (corrosion), conditions of external aggression (salt air, intense heat, heavy industrial pollution, high condensation, high pressure), mechanical characteristics (tensile strength, yield strength and fatigue resistance) and loadings (tensions, compression loads) that must be satisfied simultaneously by Ni-based super alloy, compared to other classes of aviation alloys (as egg. Titanium alloys, Aluminum alloys). For this alloy the requirements are strength durability, damage tolerance, fail safety and so on. The corrosion can be an issue, but the fatigue under high-magnitude cyclic tensile loading it’s what limits the lifetime of the airframe. Also, the excellent malleability and weldability characteristics of the 718 system make the material physical properties tolerant of manufacturing processes. These characteristics additionally continue to provide new opportunities for advanced manufacturing methods.

  5. Study of condensate removal from wells

    Energy Technology Data Exchange (ETDEWEB)

    Gusein-Zade, Z I

    1967-01-01

    A pressure profile of well No. 218 in the Karadag condensate field showed that pressure did not vary linearly with depth. Calculations indicated that at depths of 3,000-3,640 m, produced fluid had a density of 0.29g/ cmU3D, whereas pure condensate gas should have a density of 0.11g/cmU3D. Apparently liquid was accumulating in the well. Other data showed that gas velocity in the well at various depths varied from 6 to 11 m/sec. It was also found that this same range of gas velocities was sufficient to prevent liquid accumulation in other wells. In an effort to solve this problem, the upward flow of gas-water and of gas-condensate mixtures in tubes was studied. Each had a different flow regime. Gas-condsensate formed foam, whereas the gas-water mixture did not. This resolved the problem, since foam is known to aid the removal of liquid by gas. Additional research showed that water was present in, and promoted accumulation of, liquid in well No. 218.

  6. Horizontal beam tubes in FRM-II

    International Nuclear Information System (INIS)

    Coors, D.; Vanvor, D.

    2001-01-01

    The new research reactor in Garching FRM-II is equipped with 10 leak tight horizontal beam tubes (BT1 - BT10), each of them consisting of a beam tube structure taking an insert with neutron channels. The design of all beam tube structures is similar whereas the inserts are adapted to the special requirements of the using of each beam tube. Inside the reflector tank the beam tube structures are shaped by the inner cones which are made of Al-alloy with circular and rectangular cross sections. They are located in the region of maximum neutron flux (exception BT10), they are directly connected to the flanges of the reflector tank, their lengths are about 1.5 m (exception BT10) and their axes are directed tagentially to the core centre thus contributing to a low γ-noise at the experiments. (orig.)

  7. Flow behaviour of autoclaved, 20% cold worked, Zr-2.5Nb alloy pressure tube material in the temperature range of room temperature to 800 deg. C

    International Nuclear Information System (INIS)

    Dureja, A.K.; Sinha, S.K.; Srivastava, Ankit; Sinha, R.K.; Chakravartty, J.K.; Seshu, P.; Pawaskar, D.N.

    2011-01-01

    Pressure tube material of Indian Heavy Water Reactors is 20% cold-worked and stress relieved Zr-2.5Nb alloy. Inherent variability in the process parameters during the fabrication stages of pressure tube and also along the length of component have their effect on micro-structural and texture properties of the material, which in turn affect its strength parameters (yield strength and ultimate tensile strength) and flow characteristics. Data of tensile tests carried out in the temperature range from room temperature to 800 deg. C using the samples taken out from a single pressure tube have been used to develop correlations for characterizing the strength parameters' variation as a function of axial location along length of the tube and the test temperature. Applicability of Ramberg-Osgood, Holloman and Voce's correlations for defining the post yield behaviour of the material has been investigated. Effect of strain rate change on the deformation behaviour has also been studied.

  8. Numerical simulation of gas-liquid two-phase flow behavior with condensation heat transfer

    International Nuclear Information System (INIS)

    Takamori, Kazuhide; Murase, Michio; Baba, Yoshikazu; Aihara, Tsuyoshi.

    1995-01-01

    In this study, condensation heat transfer experiments were performed in order to verify a condensation heat transfer model coupled with a three-dimensional two-phase flow analysis. In the heat transfer model, the liquid film flow rate on the heat transfer tubes was calculated by a mass balance equation and the liquid film thickness was calculated from the liquid film flow rate using Nusselt's laminar flow model and Fujii's equation for steam velocity effect. In the experiments, 112 horizontal staggered tubes with an outer diameter of 16 mm and length of 0.55 m were used. Steam and spray water were supplied to the test section, and inlet quality was controlled by the spray water flow rate. The temperature was 100degC and the pressure was 0.1 MPa. The overall heat transfer coefficients were measured for inlet quality of 13-100%. From parameter calculations for the falling liquid film ratio from the upper tubes to the lower tubes, the calculated overall heat transfer coefficients agreed with the data to within ±5% at the falling liquid film ratio of 0.7. (author)

  9. Dissimilar Joining of ODS and F/M Steel Tube by Friction Stir Welding

    Energy Technology Data Exchange (ETDEWEB)

    Kang, Suk Hoon; Noh, Sanghoon; Kim, Jun Hwan; Kim, Tae Kyu [Korea Atomic Energy Research Institute, Daejeon (Korea, Republic of)

    2014-05-15

    Oxide Dispersion strengthened (ODS) steels, it is well known that uniform nano-oxide dispersoids act as pinning points to obstruct dislocation and grain boundary motion, however, those advantages will be disappeared while the material is subjected to the high temperature of conventional fusion welding. Rotary friction welding, also referred to as friction stir welding (FSW), has shown great promise as a method for welding traditionally difficult to weld materials such as aluminum alloys. This relatively new technology has more recently been applied to higher melting temperature alloys such as steels, nickel-based and titanium alloys. Friction stir processing (FSP) is a method of changing the properties of a metal through intense, localized plastic deformation. FSW is the precursor of the FSP technique. When ideally implemented, this process mixes the material without changing the phase and creates a microstructure with fine, equiaxed grains. This homogeneous grain structure, separated by high-angle boundaries, allows some alloys to take on superplastic properties. In this study, FSW is used as a substitutive welding process between FMS tube and ODS parts. The dimension of tube is 7.0 OD, 0.5 T. During the FSW, dynamic-recrystallized grains are developed; the uniform oxides Dispersion is preserved in the metal matrix. The microstructure and microtexture of the material near the stir zone is found to be influenced by the rotational behavior of the tool. The additive effect from FSP on sample surface is considered. Since the mechanical alloying (MA) and FSP commonly apply extreme shear deformation on materials, the Dispersion of oxide particle in ODS steels is very active during both processes. Friction stir welding appears to be a very promising technique for the welding of FMS and ODS steels in the form of sheet and tube. FSW could successfully produce defect-free welds on FMS tubes and ODS ring assembly. FSW produces a fine grain structure consisting of ferrite and

  10. Dissimilar Joining of ODS and F/M Steel Tube by Friction Stir Welding

    International Nuclear Information System (INIS)

    Kang, Suk Hoon; Noh, Sanghoon; Kim, Jun Hwan; Kim, Tae Kyu

    2014-01-01

    Oxide Dispersion strengthened (ODS) steels, it is well known that uniform nano-oxide dispersoids act as pinning points to obstruct dislocation and grain boundary motion, however, those advantages will be disappeared while the material is subjected to the high temperature of conventional fusion welding. Rotary friction welding, also referred to as friction stir welding (FSW), has shown great promise as a method for welding traditionally difficult to weld materials such as aluminum alloys. This relatively new technology has more recently been applied to higher melting temperature alloys such as steels, nickel-based and titanium alloys. Friction stir processing (FSP) is a method of changing the properties of a metal through intense, localized plastic deformation. FSW is the precursor of the FSP technique. When ideally implemented, this process mixes the material without changing the phase and creates a microstructure with fine, equiaxed grains. This homogeneous grain structure, separated by high-angle boundaries, allows some alloys to take on superplastic properties. In this study, FSW is used as a substitutive welding process between FMS tube and ODS parts. The dimension of tube is 7.0 OD, 0.5 T. During the FSW, dynamic-recrystallized grains are developed; the uniform oxides Dispersion is preserved in the metal matrix. The microstructure and microtexture of the material near the stir zone is found to be influenced by the rotational behavior of the tool. The additive effect from FSP on sample surface is considered. Since the mechanical alloying (MA) and FSP commonly apply extreme shear deformation on materials, the Dispersion of oxide particle in ODS steels is very active during both processes. Friction stir welding appears to be a very promising technique for the welding of FMS and ODS steels in the form of sheet and tube. FSW could successfully produce defect-free welds on FMS tubes and ODS ring assembly. FSW produces a fine grain structure consisting of ferrite and

  11. Numerical simulation of tubes-in-tube heat exchanger in a mixed refrigerant Joule-Thomson cryocooler

    Science.gov (United States)

    Damle, R. M.; Ardhapurkar, P. M.; Atrey, M. D.

    2017-02-01

    Mixed refrigerant Joule-Thomson (MRJT) cryocoolers can produce cryogenic temperatures with high efficiency and low operating pressures. As compared to the high system pressures of around 150-200 bar with nitrogen, the operational pressures with non-azeotropic mixtures (e.g., nitrogen-hydrocarbons) come down to 10-25 bar. With mixtures, the heat transfer in the recuperative heat exchanger takes place in the two-phase region. The simultaneous boiling and condensation of the cold and hot gas streams lead to higher heat transfer coefficients as compared to single phase heat exchange. The two-phase heat transfer in the recuperative heat exchanger drastically affects the performance of a MRJT cryocooler. In this work, a previously reported numerical model for a simple tube-in-tube heat exchanger is extended to a multi tubes-in-tube heat exchanger with a transient formulation. Additionally, the J-T expansion process is also considered to simulate the cooling process of the heat exchanger from ambient temperature conditions. A tubes-in-tube heat exchanger offers more heat transfer area per unit volume resulting in a compact design. Also, the division of flow in multiple tubes reduces the pressure drop in the heat exchanger. Simulations with different mixtures of nitrogen-hydrocarbons are carried out and the numerical results are compared with the experimental data.

  12. Manufacturing of FeCrAl/Zr Dual Layer tube for its application to LWR Fuel cladding

    Energy Technology Data Exchange (ETDEWEB)

    Park, Dong Jun; Lim, Do Wan; Jung, Yang Il; Kim, Hyun Gil; Park, Jeong Yong [Korea Atomic Energy Research Institute, Daejeon (Korea, Republic of)

    2013-10-15

    Many advanced materials such as MAX phases, Mo, SiC, and Fe-based alloys are being considered a possible candidate to substitute the Zr-based alloy cladding has been used in light water reactors. Among the proposed candidate materials, Fe-based alloy is one of the most promising candidates owing to its excellent formability, very good high strength, and corrosion resistance at high temperature. However, neutron cross section of FeCrAl alloy is much higher than that of existing Zr-based alloys. In this study, FeCrAl/Zr dual layer tube was manufactured by using a hot isostatic pressing (HIP) method. The thickness of outer FeCrAl layer was varied from 50 to 250 μm but all the FeCrAl/Zr dual layer tube samples maintained its total thickness of 570 μm. For a detailed microstructural characterization of FeCrAl/Zr dual layer, polarized optical microscopy and scanning electron microscopy (SEM) study carried out and its mechanical property was measured by ring compression test. FeCrAl/Zr dual layer tube sample was successfully manufactured with good adhesion between both layers. Inter layer showing gradual element variation was observed at interface. Result obtained from simulated LOCA test indicates that FeCrAl/Zr dual layer tube may maintain its integrity during LOCA and its accident tolerance had greatly improved compared to that of Zr-based alloy.

  13. Hydrogen charging, hydrogen content analysis and metallographic examination of hydride in zirconium alloys

    International Nuclear Information System (INIS)

    Singh, R.N.; Kishore, R.; Mukherjee, S.; Roychowdhury, S.; Srivastava, D.; Sinha, T.K.; De, P.K.; Banerjee, S.; Gopalan, B.; Kameswaran, R.; Sheelvantra, Smita S.

    2003-12-01

    Gaseous and electrolytic hydrogen charging techniques for introducing controlled amount of hydrogen in zirconium alloy is described. Zr-1wt%Nb fuel tube, zircaloy-2 pressure tube and Zr-2.5Nb pressure tube samples were charged with up to 1000 ppm of hydrogen by weight using one of the aforementioned methods. These hydrogen charged Zr-alloy samples were analyzed for estimating the total hydrogen content using inert gas fusion technique. Influence of sample surface preparation on the estimated hydrogen content is also discussed. In zirconium alloys, hydrogen in excess of the terminal solid solubility precipitates out as brittle hydride phase, which acquire platelet shaped morphology due to its accommodation in the matrix and can make the host matrix brittle. The F N number, which represents susceptibility of Zr-alloy tubes to hydride embrittlement was measured from the metallographs. The volume fraction of the hydride phase, platelet size, distribution, interplatelet spacing and orientation were examined metallographically using samples sliced along the radial-axial and radial-circumferential plane of the tubes. It was observed that hydride platelet length increases with increase in hydrogen content. Considering the metallographs generated by Materials Science Division as standard, metallographs prepared by the IAEA round robin participants for different hydrogen concentration was compared. It is felt that hydride micrographs can be used to estimate not only that approximate hydrogen concentration of the sample but also its size, distribution and orientation which significantly affect the susceptibility to hydride embrittlement of these alloys. (author)

  14. Analysis of Polycyclic Aromatic Hydrocarbons (PAHs in soils using ultrasonic agitation, heater/mini condenser tube and gaseous chromatography

    Directory of Open Access Journals (Sweden)

    Jurandir Pereira Pinto

    2006-02-01

    Full Text Available The increase in the number of gas stations in Brazil made it also possible the increase in the risk of underground waters contamination due to fuel spill. The polycyclic aromatic hydrocarbons (PAHs are petroleum-derived components and constitute a group of organic pollutants which are persistent in the environment and have highly carcinogenic capacity. In this work it was developed a PAHs analysis methodology in soils for quantifying these components, using the gaseous chromatography technique, through the optimization and validation of the chromatographic as well as the extraction, concentration and purification conditions of the PAHs. A good resolution for the sixteen PAHs was obtained, with retention times ranging from 6.1 to 43.7 minutes. The tube-heater/mini condenser system used for the solvent evaporation also showed satisfactory recovery for the naphthalene (83% as well as the extraction method by ultrasonic agitation with dichloromethane, obtaining recoveries that ranged from 74 to 104%. The analysis method proved to be appropriate for the quantification of the 16 PAHs in the evaluation of the environmental contamination in gas stations.

  15. Method for automatic filling of nuclear fuel rod cladding tubes

    International Nuclear Information System (INIS)

    Bezold, H.

    1979-01-01

    Prior to welding the zirconium alloy cladding tubes with end caps, they are automatically filled with nuclear fuel tablets and ceramic insulating tablets. The tablets are introduced into magazine drums and led through a drying oven to a discharging station. The empty cladding tubes are removed from this discharging station and filled with tablets. A filling stamp pushes out the columns of tablets in the magazine tubes of the magazine drum into the cladding tube. Weight and measurement of length determine the filled state of the cladding tube. The cladding tubes are then led to the welding station via a conveyor belt. (DG) [de

  16. The numerical and experimental study of two passes power plant condenser

    Directory of Open Access Journals (Sweden)

    Rusowicz Artur

    2017-01-01

    Full Text Available The steam condenser is one of the most important element in whole power plant installation. Their proper design and operation makes a significant contribution to the efficiency of electricity production. The purpose of this article is to propose a two-dimensional mathematical model that allows modeling condenser work. In the model, the tube bundle is treated as a porous bed. The analysis has been subjected to a two passes power condenser with a capacity of 50 MW. The mathematical analysis was compared with the results of experimental studies. The average error between the model and the experiment for difference of cooling water temperatures was 5.15% and 11.60% for the first and second pass respectively. This allows to conclude that the proposed model is good enough to optimize future work of the condenser.

  17. Studies on the permeation of hydrogen through steam generator tubes at high temperatures using an electrochemical method

    International Nuclear Information System (INIS)

    Giraudeau, F.; Yang, L.; Steward, F.R.; DeBouvier, O.

    1998-01-01

    The permeation of hydrogen through steam generator tubes at high temperatures (∼ 300 degrees C) has been studied using an electrochemical technique. With this technique, hydrogen is generated on one side of the tube and monitored on the other side. The time for the hydrogen to reach the other side is used to determine the diffusion coefficient of hydrogen in the tube. Boundary conditions at the entry and exit sides have been investigated separately. Preliminary studies were performed on Stainless Steel 316 and Nickel Alloy 800 to better understand the influence of the solution chemistry on the electrochemical evolution of hydrogen. The surface phenomena effect and the trapping effect are discussed to account for differences observed in the permeation response. The hydrogen permeation through oxides at the exit side has been studied. Two nickel alloys (Alloy 800 and Alloy 600), materials widely used for steam generator tubes, have been investigated. The tubes were prefilmed using two different treatments. The oxides were formed in dry air at high temperatures (300 degrees C to 600 degrees C), or in humid gas at 300 degrees C. The diffusion coefficients at 300 degrees C in Stainless Steel 316 and Alloy 800 were determined to be of the order of 10 -6 - 10 -7 cm 2 /s for the bare metal. This is in agreement with results obtained by gas phase permeation techniques in the literature. (author)

  18. Leak behavior of steam generator tube-to-tubesheet joints under creep condition: Experimental study

    International Nuclear Information System (INIS)

    Bahn, Chi Bum; Majumdar, Saurin; Kasza, Ken E.; Shack, William J.

    2013-01-01

    To address concerns regarding excessive leakage from throughwall cracks in steam generator tube-to-tubesheet joints under severe accident conditions, leak rate testing was conducted using tube-to-collar joint specimens. The tube interior and the interface between tube and collar (crevice) were pressurized independently using nitrogen gas. The leak rate through the crevice was almost zero when the specimens were pressurized at ∼500 °C; this low leak rate is attributed to thermal mismatch effects preventing much leakage. The near zero leak rate was maintained until the onset of large leakage at higher temperatures. The leak rate behavior after the onset of the large leakage was not much affected by the crevice length or heat-to-heat variation of Alloy 600 tubes. This suggests that once the crevice gap opens, the creep rate of the low alloy steel collar becomes dominant. Specimens with different tube diameters behaved essentially the same way. To simulate a flawed steam generator tube in the tubesheet, the crevice region was pressurized through a hole in the tube. This simulation resulted in essentially the same behavior as those specimens whose tubes and crevices were pressurized independently. Oxidation of low alloy steel collars in air tests can increase the flow resistance, and thus tests using nitrogen gas would provide more conservative leak rate data. Highlights: ► Leak rates were measured by using tube-to-collar joint specimens under creep condition. ► Leak rate through the joint interface was almost zero at ∼500 °C due to thermal mismatch. ► The near zero leak rate was maintained until the onset of large leakage at ∼680 °C. ► The leak behavior after the onset of the large leakage was not affected by hydraulic expansion length or tube heats.

  19. Evaluation of Fatigue Crack Initiation for Volumetric Flaw in Pressure Tube

    International Nuclear Information System (INIS)

    Choi, Sung Nam; Yoo, Hyun Joo

    2005-01-01

    CAN/CSA.N285.4-94 requires the periodic inservice inspection and surveillance of pressure tubes in operating CANDU nuclear power reactors. If the inspection results reveal a flaw exceeding the acceptance criteria of the Code, the flaw must be evaluated to determine if the pressure is acceptable for continued service. Currently, the flaw evaluation methodology and acceptance criteria specified in CSA-N285.05-2005, 'Technical requirements for in-service evaluation of zirconium alloy pressure tubes in CANDU reactors'. The Code is applicable to zirconium alloy pressure tubes. The evaluation methodology for a crack-like flaw is similar to that of ASME B and PV Sec. XI, 'Inservice Inspection of Nuclear Power Plant Components'. However, the evaluation methodology for a blunt volumetric flaw is described in CSA-N285.05-2005 code. The object of this paper is to address the fatigue crack initiation evaluation for the blunt volumetric flaw as it applies to the pressure tube at Wolsong NPP

  20. Characterization of BOR-60 Irradiated 14YWT-NFA1 Tubes

    Energy Technology Data Exchange (ETDEWEB)

    Saleh, Tarik A. [Los Alamos National Lab. (LANL), Los Alamos, NM (United States); Maloy, Stuart Andrew [Los Alamos National Lab. (LANL), Los Alamos, NM (United States); Aydogan, Eda [Los Alamos National Lab. (LANL), Los Alamos, NM (United States); Quintana, Matthew Estevan [Los Alamos National Lab. (LANL), Los Alamos, NM (United States); Romero, Tobias J. [Los Alamos National Lab. (LANL), Los Alamos, NM (United States)

    2017-02-15

    Tubes of FCRD 14YWT-NFA1 Alloy were placed in the BOR-60 reactor and irradiated under a fast flux neutron environment to two conditions: 7 dpa at 360-370 °C and 6 dpa at 385-430 °C. Small sections of the tube were cut and sent to UC Berkeley for nanohardness testing and focused ion beam (FIB) milling of TEM specimens. FIB specimens were sent back to LANL for final FIB milling and TEM imaging. Hardness data and TEM images are presented in this report. This is the first fast reactor neutron irradiated information on the 14YWT-NFA1 alloy.

  1. Irradiation creep of dispersion strengthened copper alloy

    Energy Technology Data Exchange (ETDEWEB)

    Pokrovsky, A.S.; Barabash, V.R.; Fabritsiev, S.A. [and others

    1997-04-01

    Dispersion strengthened copper alloys are under consideration as reference materials for the ITER plasma facing components. Irradiation creep is one of the parameters which must be assessed because of its importance for the lifetime prediction of these components. In this study the irradiation creep of a dispersion strengthened copper (DS) alloy has been investigated. The alloy selected for evaluation, MAGT-0.2, which contains 0.2 wt.% Al{sub 2}O{sub 3}, is very similar to the GlidCop{trademark} alloy referred to as Al20. Irradiation creep was investigated using HE pressurized tubes. The tubes were machined from rod stock, then stainless steel caps were brazed onto the end of each tube. The creep specimens were pressurized by use of ultra-pure He and the stainless steel caps subsequently sealed by laser welding. These specimens were irradiated in reactor water in the core position of the SM-2 reactors to a fluence level of 4.5-7.1 x 10{sup 21} n/cm{sup 2} (E>0.1 MeV), which corresponds to {approx}3-5 dpa. The irradiation temperature ranged from 60-90{degrees}C, which yielded calculated hoop stresses from 39-117 MPa. A mechanical micrometer system was used to measure the outer diameter of the specimens before and after irradiation, with an accuracy of {+-}0.001 mm. The irradiation creep was calculated based on the change in the diameter. Comparison of pre- and post-irradiation diameter measurements indicates that irradiation induced creep is indeed observed in this alloy at low temperatures, with a creep rate as high as {approx}2 x 10{sup {minus}9}s{sup {minus}1}. These results are compared with available data for irradiation creep for stainless steels, pure copper, and for thermal creep of copper alloys.

  2. Irradiation creep of dispersion strengthened copper alloy

    International Nuclear Information System (INIS)

    Pokrovsky, A.S.; Barabash, V.R.; Fabritsiev, S.A.

    1997-01-01

    Dispersion strengthened copper alloys are under consideration as reference materials for the ITER plasma facing components. Irradiation creep is one of the parameters which must be assessed because of its importance for the lifetime prediction of these components. In this study the irradiation creep of a dispersion strengthened copper (DS) alloy has been investigated. The alloy selected for evaluation, MAGT-0.2, which contains 0.2 wt.% Al 2 O 3 , is very similar to the GlidCop trademark alloy referred to as Al20. Irradiation creep was investigated using HE pressurized tubes. The tubes were machined from rod stock, then stainless steel caps were brazed onto the end of each tube. The creep specimens were pressurized by use of ultra-pure He and the stainless steel caps subsequently sealed by laser welding. These specimens were irradiated in reactor water in the core position of the SM-2 reactors to a fluence level of 4.5-7.1 x 10 21 n/cm 2 (E>0.1 MeV), which corresponds to ∼3-5 dpa. The irradiation temperature ranged from 60-90 degrees C, which yielded calculated hoop stresses from 39-117 MPa. A mechanical micrometer system was used to measure the outer diameter of the specimens before and after irradiation, with an accuracy of ±0.001 mm. The irradiation creep was calculated based on the change in the diameter. Comparison of pre- and post-irradiation diameter measurements indicates that irradiation induced creep is indeed observed in this alloy at low temperatures, with a creep rate as high as ∼2 x 10 -9 s -1 . These results are compared with available data for irradiation creep for stainless steels, pure copper, and for thermal creep of copper alloys

  3. First application of hollow fiber filter for PWR condensate polishing

    International Nuclear Information System (INIS)

    Tsuda, S.; Otoha, K.; Takiguchi, H.

    2002-01-01

    In Tsuruga Unit-2 (PWR 1160 MWe commenced commercial operation in 1987), current procedure for secondary system clean-up before start-up had prolonged outage time and had consumed a huge amount of de-ionized (DI) water. In addition, iron oxide in condensate had accelerated the degradation of condensate demineralizer (CD) resin. The corrosion product of iron could also influence the secondary side corrosion of steam generator (SG) tubing if it intruded into SG through CD. To solve these problems, Japan Atomic Power Company (JAPC) decided to introduce hollow fiber filter (HFF) type condensate filter into Tsuruga-2, as the first application to PWR in the world. Because of retro-fitted HFF in Tsuruga Unit-2, limitations for installation space and flow resistance in condensate system and cost reduction required new design for compact and low differential pressure system and for long life filter module. JAPC and ORGANO assessed methodologies to achieve these goals. An advanced HFF system, including a newly developed compact HFF module design, was installed at Tsuruga Unit-2 in 1997 based on the assessment. During the 5 years since the installation, the HFF system has provided excellent crud removal that enables to shorten the outage period and to reduce DI water consumption drastically. Stable differential pressure (dP) trend of the HFF system indicates an expected module life of more than 7 years, with backwash cleaning required only 2 or 3 times per year. In addition to providing the expected operating cost reduction and improved SG tube integrity, numerous additional benefits have resulted from the retrofit. (authors)

  4. Effects of microstructure and mechanical properties of alloys 600 an 690 on secondary side SCC

    International Nuclear Information System (INIS)

    Vaillant, F.; Buisine, D.; Prieux, B.; Fournel, J.C.; Gelpi, A.

    1996-03-01

    Modeling for secondary side cracking is needed to understand the behaviour of alloy 600 in plants. They require a comprehensive understanding of the various influences of the material properties on Stress Corrosion Cracking (SCC), based on field experience and laboratory data. In an attempt to predict the materials effects on SCC behaviour of new steam generators, laboratory corrosion data of alloy 690 were overviewed. French field experience with steam generators equipped with drilled tube support plates (TSPs) has demonstrated that the lower the yield stress (YS) and the carbon content, the higher the susceptibility t secondary side cracking of mill-annealed (MA) alloy 600. Also heat treated (700 deg. C x 16 h) tubing has been shown to have a much better resistance, but this excellent resistance could not be attributed only to the material properties. In laboratory environments, particularly in caustics, results have confirmed several of the above mentioned key findings on alloy 600: in caustic environments and under constant loading, tubes fabricated from MA alloy 600 with low YS have exhibited the worst resistance to initiation; YS was found to be the most accurate parameter to account for the behaviour of MA alloy 600. A heat treatment at 700 deg. C appeared to reduce the propagation rates of cracks in alloy 600. The best IGSCC resistance of alloy 690 was obtained for tubes with intergranular precipitation of carbides. TT (700 deg. C) significantly improved the propagation resistance of alloy 690; in acidic and neutral sulfate environments, IGSCC of alloy 600 was not strongly dependent on the microstructure in the MA condition, but sensitization was detrimental. When alloy 600 and particularly alloy 690 were thermally treated at 700 deg. C x 16 h, the resistance to IGSCC was significantly improved. Tests performed on alloy 690 have shown a better resistance to IGSCC initiation and propagation than alloy 600, in NaOH and acidic sulfate environments. (authors

  5. Effect of the environment on a SG tube fatigue cracking at Fessenheim unit 2

    International Nuclear Information System (INIS)

    Duisabeau, L.; Fargeas, E.; Miloudi, S.; Leduc, A.; Hollner, S.; Thebault, Y.; Legras, L.; Mansour, C.

    2015-01-01

    In 2008, a primary-to-secondary leak was detected at TSP n8 level, on the tube R12C62 of Fessenheim unit 2 SG3. The leak was associated to a high cycle fatigue crack that was confirmed two years after, when the tube was pulled out for destructive examination. It revealed on the one hand a highly oxidized fracture surface and on the other hand, that the fatigue crack was initiated on small IGA (Intergranular Attack) piles located at the OD (Outside Diameter) surface of the alloy 600MA tube. In order to take into account a potential environmental effect on the fatigue limit of alloy 600MA in mechanical calculations implemented to establish the root cause failure analysis, several investigations were conducted to evaluate the environment at the tube/tubesheet interstice. To achieve this goal, a multi-scale analysis has been performed. It includes a global analysis of the corrosion damage of the SG, the SG chemistry monitoring, an evaluation of the pH in confined areas with MulteQ calculations based on hide out returns, as well as oxides characterization on the tube by Transmission Electronic Microscopy. All methods converge to a slightly neutral pH with pollutants such as copper, lead and sulfates leading to the conclusion that the fatigue limit of alloy 600MA has not been reduced by the chemical environment. All these chemical elements are known to affect in a certain extent the corrosion resistance of the alloy 600 in the secondary water. If all these pollutants can be detected during the global monitoring of the plant during operation or outage (blow down, hideout returns, feed water and sludge chemical analysis), transmission electronic microscopy offers a unique technique for better understanding how these pollutants may react in confined area, corroded area or free span oxides in the alloy 600 and thus for a better understanding of the corrosion mechanism of nickel based alloys in the secondary side

  6. Modelling the thermodynamic performance of a concentrated solar power plant with a novel modular air-cooled condenser

    International Nuclear Information System (INIS)

    Moore, J.; Grimes, R.; Walsh, E.; O'Donovan, A.

    2014-01-01

    This paper aims at developing a novel air-cooled condenser for concentrated solar power plants. The condenser offers two significant advantages over the existing state-of-the-art. Firstly, it can be installed in a modular format where pre-assembled condenser modules reduce installation costs. Secondly, instead of using large fixed speed fans, smaller speed controlled fans are incorporated into the individual modules. This facility allows the operating point of the condenser to change and continuously maximise plant efficiency. A thorough experimental analysis was performed on a number of prototype condenser designs. This analysis investigated the validly and accuracy of correlations from literature in predicting the thermal and aerodynamic characteristics of different designs. These measurements were used to develop a thermodynamic model to predict the performance of a 50 MW CSP (Concentrated Solar Power) plant with various condenser designs installed. In order to compare different designs with respect to the specific plant capital cost, a techno-economic analysis was performed which identified the optimum size of each condenser. The results show that a single row plate finned tube design, a four row, and a two row circular finned tube design are all similar in terms of their techno-economic performance and offer significant savings over other designs. - Highlights: • A novel air cooled condenser for CSP (Concentrated Solar Power) applications is proposed. • A thorough experimental analysis of various condenser designs was performed. • Heat transfer and flow friction correlations validated for fan generated air flow. • A thermodynamic model to calculate CSP plant output is presented. • Results show the proposed condenser design can continually optimise plant output

  7. Denting of Inconel 600 steam generator tubes in pressurized water reactors

    International Nuclear Information System (INIS)

    Van Rooyen, D.; Weeks, J.R.

    1976-10-01

    Rapid, localized corrosion of carbon steel tube support plates (TSP) has led to cases of denting of steam generator tubes, due to the pressure of corrosion products formed in crevices between the tubes and TSP holes. The corrosion product is mainly magnetite (Fe 3 O 4 ), formed in ''run-away'' fashion as a result of local chemistry changes when an extended operation with phosphate (PO 4 ) treatment of the secondary coolant is followed by an all volatile treatment (AVT). The rate of the ''run-away'' magnetite formation, and therefore, the extent of damage will probably vary with the amounts of the harmful chemicals present and with temperature. Leaky condensers are felt to be responsible for the presence of Cl - ions, and for the observation that denting is more extensive in plants with salt water cooled condensers. It is possible that thermal cycles assist the denting process, both by mechanical and chemical ratchetting mechanisms. Recommendations are presented concerning the continued operation of plants with observed denting

  8. The impact of fouling on performance evaluation of evaporative coolers and condensers

    Energy Technology Data Exchange (ETDEWEB)

    Qureshi, B.A.; Zubair, S.M. [King Fahd University of Petroleum and Minerals, Dhahran (Saudi Arabia). Mechanical Engineering Dept.

    2005-11-15

    Fouling of evaporative cooler and condenser tubes is one of the most important factors affecting their thermal performance, which reduces effectiveness and heat transfer capability with time. In this paper, the experimental data on fouling reported in the literature are used to develop a fouling model for this class of heat exchangers. The model predicts the decrease in heat transfer rate with the growth of fouling. A detailed model of evaporative coolers and condensers, in conjunction with the fouling model, is used to study the effect of fouling on the thermal performance of these heat exchangers at different air inlet wet bulb temperatures. The results demonstrate that fouling of tubes reduces gains in performance resulting from decreasing values of air inlet wet bulb temperature. It is found that the maximum decrease in effectiveness due to fouling is about 55 and 78% for the evaporative coolers and condensers, respectively, investigated in this study. For the evaporative cooler, the value of process fluid outlet temperature T{sub p,out} varies by 0.66% only at the clean condition for the ambient wet bulb temperatures considered. (author)

  9. High-temperature air oxidation of E110 and Zr-1%Nb alloys claddings with coatings

    International Nuclear Information System (INIS)

    Kuprin, A.S.; Belous, V.A.; Voyevodin, V.N.; Bryk, V.V.; Vasilenko, R.L.; Ovcharenko, V.D.; Tolmachova, G.N.; V'yugov, P.N.

    2014-01-01

    Results of experimental study of the influence of protective vacuum-arc claddings on the base of compounds zirconium-chromium and of its nitrides on air oxidation resistance at temperatures 660, 770, 900, 1020, 1100 deg C during 3600 s. of tubes produced of zirconium alloys E110 and Zr-1%Nb (calcium-thermal alloy of Ukrainian production) are presented. Change of hardness, the width of oxide layer and depth of oxygen penetration into alloys from the side of coating and without coating are investigated by the methods of nanoindentation and by scanning electron microscopy. It is shown that the thickness of oxide layer in zirconium alloys at temperatures 1020 and 1100 deg C from the side of the coating doesn't exceed 5 μm, and from the unprotected side reaches the value of ≥ 120 μm with porous and rough structure. Tubes with coatings save their shape completely independently of the type of alloy; tubes without coatings deform with the production of through cracks

  10. Deuterium absorption in CANDU Zr-2.5Nb pressure tubes

    International Nuclear Information System (INIS)

    Ploc, R.A.; McRae, G.A.

    1999-12-01

    Corrosion of CANDU Zr-2.5%Nb pressure tubes in heavy water results in the formation of an oxide film and the absorption of deuterium by the alloy. If deuterium concentrations are allowed to exceed the terminal solid solubility of the alloy, brittle deuterides can form, thereby limiting the service life of a component. In CANDU pressure tubes, ingress rates are largely determined by the metastable β-Zr that is present as a thin layer encasing the predominant α-Zr grains (approximately 90% by volume). The distribution and continuity of the corroded β-phase in the oxide provides a pervasive web for the development of interconnected porosity from the free surface to the oxide/metal interface. Changing the distribution of the β-phase in the alloy changes the nature of the oxide porosity, a technique that can be used to reduce deuterium ingress rates. (author)

  11. Deuterium absorption in CANDU Zr-2.5Nb pressure tubes

    Energy Technology Data Exchange (ETDEWEB)

    Ploc, R.A.; McRae, G.A

    1999-12-01

    Corrosion of CANDU Zr-2.5%Nb pressure tubes in heavy water results in the formation of an oxide film and the absorption of deuterium by the alloy. If deuterium concentrations are allowed to exceed the terminal solid solubility of the alloy, brittle deuterides can form, thereby limiting the service life of a component. In CANDU pressure tubes, ingress rates are largely determined by the metastable {beta}-Zr that is present as a thin layer encasing the predominant {alpha}-Zr grains (approximately 90% by volume). The distribution and continuity of the corroded {beta}-phase in the oxide provides a pervasive web for the development of interconnected porosity from the free surface to the oxide/metal interface. Changing the distribution of the {beta}-phase in the alloy changes the nature of the oxide porosity, a technique that can be used to reduce deuterium ingress rates. (author)

  12. Experience of Electricite de France in the use of sea water for cooling thermal power stations

    International Nuclear Information System (INIS)

    Boyer, R.M.E.; Malherbe, C.

    1979-01-01

    The sea is a practically unlimited reserve of water for cooling conventional or nuclear thermal power stations. On the other hand, its use gives rise to numerous problems relating to the design and operation of the equipment. The main problems encountered at EDF are associated with filter screens (clogging, corrosion), the distribution ducts (encrusted organisms), the water boxes, the tube plates, and above all, the condenser tubes (corrosion, corrosion-erosion). The site-construction of several PWR nuclear sets has caused EDF to dispense with the use of cuprous alloys for the tubes of condensers using sea water; these are now of thin-walled seam-welded titanium. In order to reduce further the risks of leakage, these tubes are expanded into double tube plates between which fresh water is trapped under pressure. (author)

  13. Burner rig alkali salt corrosion of several high temperature alloys

    Science.gov (United States)

    Deadmore, D. L.; Lowell, C. E.

    1977-01-01

    The hot corrosion of five alloys was studied in cyclic tests in a Mach 0.3 burner rig into whose combustion chamber various aqueous salt solutions were injected. Three nickel-based alloys, a cobalt-base alloy, and an iron-base alloy were studied at temperatures of 700, 800, 900, and 1000 C with various salt concentrations and compositions. The relative resistance of the alloys to hot corrosion attack was found to vary with temperature and both concentration and composition of the injected salt solution. Results indicate that the corrosion of these alloys is a function of both the presence of salt condensed as a liquid on the surface and of the composition of the gas phases present.

  14. Experimental investigation of the reverse heat transfer of R134a flow through non-adiabatic coiled capillary tubes

    Energy Technology Data Exchange (ETDEWEB)

    Zareh, Masoud; Heidari, Mohammad Ghorbani [Islamic Azad University, Tehran (Iran, Islamic Republic of)

    2016-07-15

    This research represents an experimental investigation of the metastable flow and re-condensation phenomenon through non-adiabatic lateral helical capillary tubes and suction tube heat exchanger. The results show that mass flux ratio has a vital role: It affects metastable flow and also reverse heat transfer phenomenon through non-adiabatic helical capillary tube. Therefore, by increasing of the mass flux ratio, the rate of heat transfer between them decreases. In contrast to the strong rate condition of heat transfer between them, reverse heat transfer or re-condensation maybe happen. Moreover, experimental results show that for R134 flow with mass flux ratio more than 57.84, metastable flow exists in non-adiabatic capillary tube with 0.9144 mm inner diameter, 30 mm coil diameter, 6.18 m length, 4 mm inner diameter of compressor suction tube.

  15. Influence of hydrogen content on impact toughness of Zr-2.5Nb pressure tube alloy

    Energy Technology Data Exchange (ETDEWEB)

    Singh, R.N., E-mail: rnsingh@barc.gov.in [Mechanical Metallurgy Division, Bhabha Atomic Research Centre, Mumbai 400085 (India); Viswanathan, U.K.; Kumar, Sunil; Satheesh, P.M.; Anantharaman, S. [Post Irradiation Examination Division, Bhabha Atomic Research Centre, Mumbai 400085 (India); Chakravartty, J.K. [Mechanical Metallurgy Division, Bhabha Atomic Research Centre, Mumbai 400085 (India); Stahle, P. [Division of Solid Mechanics, Lund University/LTH, SE22100 Lund (Sweden)

    2011-07-15

    Highlights: > For the first time impact behaviour of Zr-2.5Nb pressure tube material used in Indian Pressurized Heavy Water Reactor (IPHWR) as a function of hydrogen content and temperature is being reported. > The critical hydrogen concentration to cause low energy fracture at 25 and 200 deg. C is suggested. > The impact behaviour is rationalized in terms of hydrogen content, test temperature, microstructural features and state of stress ahead of a crack. - Abstract: Influence of hydrogen content on the impact toughness of Zr-2.5% Nb alloy was examined by carrying out instrumented drop weight tests in the temperature range of 25-250 deg. C using curved Charpy specimens fabricated from unirradiated pressure tubes of Indian Pressurized Heavy Water Reactor (IPHWR). Hydrogen content of the samples was between 10 and 170 ppm by weight (wppm). Sharp ductile-to-brittle-transition behaviour was demonstrated by hydrided materials. The temperature for the onset of transition increased with the increase in the hydrogen content of the specimens. The fracture surfaces of unhydrided specimen exhibited ductile fracture caused by micro void coalescence and tear ridges at lower temperatures and by fibrous fracture at intermediate and at higher temperatures. Except for the samples tested at the upper shelf energy levels, the fracture surfaces of all hydrided samples were suggestive of hydride assisted failure. In most cases the transverse cracks observed in the fracture path matched well with the hydride precipitate distribution and orientation.

  16. Melting and casting of FeAl-based cast alloy

    Energy Technology Data Exchange (ETDEWEB)

    Sikka, V.K. [Oak Ridge National Lab., TN (United States); Wilkening, D. [Columbia Falls Aluminum Co., Columbia Falls, MT (United States); Liebetrau, J.; Mackey, B. [AFFCO, L.L.C., Anaconda, MT (United States)

    1998-11-01

    The FeAl-based intermetallic alloys are of great interest because of their low density, low raw material cost, and excellent resistance to high-temperature oxidation, sulfidation, carburization, and molten salts. The applications based on these unique properties of FeAl require methods to melt and cast these alloys into complex-shaped castings and centrifugal cast tubes. This paper addresses the melting-related issues and the effect of chemistry on the microstructure and hardness of castings. It is concluded that the use of the Exo-Melt{trademark} process for melting and the proper selection of the aluminum melt stock can result in porosity-free castings. The FeAl alloys can be melted and cast from the virgin and revert stock. A large variation in carbon content of the alloys is possible before the precipitation of graphite flakes occurs. Titanium is a very potent addition to refine the grain size of castings. A range of complex sand castings and two different sizes of centrifugal cast tubes of the alloy have already been cast.

  17. Studies on the causes of failures in titanium tube condensers of nuclear power plants

    International Nuclear Information System (INIS)

    Kim, Uh Chul; Kim, Joung Soo; Chung, Han Sub; Hwang, Seong Sik; Hur, Do Haeng

    1991-02-01

    The amount of hydrogen absorbed in Ti tubes varies as the surface condition of Ti tubes changes. It was observed that the amount of hydrogen absorbed in Ti tubes was highest in as-received and welded specimens, while that could be reduced by oxidizing them to make stable oxide surface film or by pickling them. The results of the experiments done by varing the applied cathodic potentials show that hydrogen content absorbed in Ti tubes increases very sharply at or below the potential of -0.9 V versus SCE, which suggests that critical potential for cathodic protection should be above -0.9 V versus SCE. (Author)

  18. Properties of the chalcogenide–carbon nano tubes and graphene composite materials

    International Nuclear Information System (INIS)

    Singh, Abhay Kumar; Kim, JunHo; Park, Jong Tae; Sangunni, K.S.

    2015-01-01

    Highlights: • Chalcogenides. • Melt quenched. • Composite materials. • Multi walled carbon nano tubes. • Bilayer graphene. - Abstract: Composite can deliver more than the individual elemental property of the material. Specifically chalcogenide- multi walled carbon nano tubes and chalcogenide- bilayer graphene composite materials could be interesting for the investigation, which have been less covered by the investigators. We describe micro structural properties of Se 55 Te 25 Ge 20, Se 55 Te 25 Ge 20 + 0.025% multi walled carbon nano tubes and Se 55 Te 25 Ge 20 + 0.025% bilayer graphene materials. This gives realization of the alloying constituents inclusion/or diffusion inside the multi walled carbon nano tubes and bilayer graphene under the homogeneous parent alloy configuration. Raman spectroscopy, X-ray photoelectron spectroscopy, UV/Visible spectroscopy and Fourier transmission infrared spectroscopy have also been carried out under the discussion. A considerable core energy levels peak shifts have been noticed for the composite materials by the X-ray photoelectron spectroscopy. The optical energy band gaps are measured to be varied in between 1.2 and 1.3 eV. In comparison to parent (Se 55 Te 25 Ge 20 ) alloy a higher infrared transmission has been observed for the composite materials. Subsequently, variation in physical properties has been explained on the basis of bond formation in solids

  19. W-007H B Plant Process Condensate Treatment Facility. Revision 3

    International Nuclear Information System (INIS)

    Rippy, G.L.

    1995-01-01

    B Plant Process Condensate (BCP) liquid effluent stream is the condensed vapors originating from the operation of the B Plant low-level liquid waste concentration system. In the past, the BCP stream was discharged into the soil column under a compliance plan which expired January 1, 1987. Currently, the BCP stream is inactive, awaiting restart of the E-23-3 Concentrator. B Plant Steam Condensate (BCS) liquid effluent stream is the spent steam condensate used to supply heat to the E-23-3 Concentrator. The tube bundles in the E-23-3 Concentrator discharge to the BCS. In the past, the BCS stream was discharged into the soil column. Currently, the BCS stream is inactive. This project shall provide liquid effluent systems (BCP/BCS/BCE) capable of operating for a minimum of 20 years, which does not include the anticipated decontamination and decommissioning (D and D) period

  20. W-007H B Plant Process Condensate Treatment Facility. Revision 3

    Energy Technology Data Exchange (ETDEWEB)

    Rippy, G.L.

    1995-01-20

    B Plant Process Condensate (BCP) liquid effluent stream is the condensed vapors originating from the operation of the B Plant low-level liquid waste concentration system. In the past, the BCP stream was discharged into the soil column under a compliance plan which expired January 1, 1987. Currently, the BCP stream is inactive, awaiting restart of the E-23-3 Concentrator. B Plant Steam Condensate (BCS) liquid effluent stream is the spent steam condensate used to supply heat to the E-23-3 Concentrator. The tube bundles in the E-23-3 Concentrator discharge to the BCS. In the past, the BCS stream was discharged into the soil column. Currently, the BCS stream is inactive. This project shall provide liquid effluent systems (BCP/BCS/BCE) capable of operating for a minimum of 20 years, which does not include the anticipated decontamination and decommissioning (D and D) period.

  1. Development of low temperature solid state joining technology of dissimilar for nuclear heat exchanger tube components

    Energy Technology Data Exchange (ETDEWEB)

    NONE

    2010-08-15

    By conventional fusion welding process (TIG), a realization of reliable and sound joints for the nuclear heat exchanger components is very difficult, especially for the parts comprising of the dissimilar metal couples (Ti-STS, Ti-Cu alloy etc.). This is mainly attributed to the formation of brittle intermetallics (Ti{sub x}Cu{sub y}, Ti{sub x}Fe{sub y}, Ti{sub x}Ni{sub y} etc.) and wide difference in physical properties. Moreover, it usually employs very high thermal input, so making it difficult to obtain sound joints due to generations of high residual stresses and degradation of the adjacent base metals, even for similar metal combinations. In this project, the low temperature solid-state joining technology was established by developing new alloy fillers, e.g. the multi-component eutectic based alloys or amorphous alloys, and thereby lowering the joining temperature down to {approx}800 .deg. C without affecting the structural properties of base metals. Based on a low temperature joining, the interlayer engineering technology was then developed to be able to eliminate the brittleness of the joints for strong Ti-STS dissimilar joints, and the diffusion brazing technology of Ti-Ti with a superior joining strength and corrosion-resistance comparable to those of base metal were developed. By using those developed technologies, the joining procedures feasible for the heat exchanger components were finally established for the dissimilar metal joints including Ti tube sheet to super STS tube, Ti tube sheet to super STS tube sheet, and the joints of the Ti tube to Ti tube sheet

  2. A novel Fe–Cr–Nb matrix composite containing the TiB_2 neutron absorber synthesized by mechanical alloying and final hot isostatic pressing (HIP) in the Ti-tubing

    International Nuclear Information System (INIS)

    Litwa, Przemysław; Perkowski, Krzysztof; Zasada, Dariusz; Kobus, Izabela; Konopka, Gustaw; Czujko, Tomasz; Varin, Robert A.

    2016-01-01

    The Fe–Cr–Ti-Nb elemental powders were mechanically alloyed/ball milled with TiB_2 and a small quantity of Y_2O_3 ceramic to synthesize a novel Fe-based alloy-ceramic powder composite that could be processed by hot isostatic pressing (HIP) for a perceived potential application as a neutron absorber in nuclear reactors. After ball milling for the 30–80 h duration relatively uniform powders with micrometric sizes were produced. With increasing milling time a fraction of TiB_2 particles became covered with the much softer Fe-based alloy which resulted in the formation of a characteristic “core-mantel” structure. For the final HIP-ing process the mechanically alloyed powders were initially uniaxially pressed into rod-shaped compacts and then cold isostatically pressed (CIP-ed). Subsequently, the rod-shaped compacts were placed in the Ti-tubing and subjected to hot isostatic pressing (HIP) at 1150 °C/200 MPa pressure. The HIP-ing process resulted in the formation of the near-Ti and intermediate diffusional layers in the microstructure of HIP-ed samples which formed in accord with the Fe-Ti binary phase diagram. Those layers contain the phases such as α-Ti (HCP), the FeTi intermetallic and their hypo-eutectoid mixtures. In addition, needle-like particles were formed in both layers in accord with the Ti-B binary phase diagram. Nanohardness testing, using a Berkovich type diamond tip, shows that the nanohardness in the intermediate layer areas, corresponding to the composition of the hypo-eutectoid mixture of Ti-FeTi, equals 980.0 (±27.1) HV and correspondingly 1176.9 (±47.6) HV for the FeTi phase. The nanohardness in the sample's center in the areas with the fine mixture of Fe-based alloy and small TiB_2 particles equals 1048.3 (±201.8) HV. The average microhardness of samples HIP-ed from powders milled for 30 and 80 h is 588 HV and 733 HV, respectively. - Highlights: • A Fe–Cr–Nb-based composite with TiB_2 neutron absorbing ceramic was mechanically

  3. Predicting tube repair at French nuclear steam generators using statistical modeling

    Energy Technology Data Exchange (ETDEWEB)

    Mathon, C., E-mail: cedric.mathon@edf.fr [EDF Generation, Basic Design Department (SEPTEN), 69628 Villeurbanne (France); Chaudhary, A. [EDF Generation, Basic Design Department (SEPTEN), 69628 Villeurbanne (France); Gay, N.; Pitner, P. [EDF Generation, Nuclear Operation Division (UNIE), Saint-Denis (France)

    2014-04-01

    Electricité de France (EDF) currently operates a total of 58 Nuclear Pressurized Water Reactors (PWR) which are composed of 34 units of 900 MWe, 20 units of 1300 MWe and 4 units of 1450 MWe. This report provides an overall status of SG tube bundles on the 1300 MWe units. These units are 4 loop reactors using the AREVA 68/19 type SG model which are equipped either with Alloy 600 thermally treated (TT) tubes or Alloy 690 TT tubes. As of 2011, the effective full power years of operation (EFPY) ranges from 13 to 20 and during this time, the main degradation mechanisms observed on SG tubes are primary water stress corrosion cracking (PWSCC) and wear at anti-vibration bars (AVB) level. Statistical models have been developed for each type of degradation in order to predict the growth rate and number of affected tubes. Additional plugging is also performed to prevent other degradations such as tube wear due to foreign objects or high-cycle flow-induced fatigue. The contribution of these degradation mechanisms on the rate of tube plugging is described. The results from the statistical models are then used in predicting the long-term life of the steam generators and therefore providing a useful tool toward their effective life management and possible replacement.

  4. Effect of texture on creep deformation behavior of Zr-2.5Nb alloy

    International Nuclear Information System (INIS)

    Guguloth, Krishna; Swaminathan, J.; Mitra, Rahul; Ghosh, R.N.; Singh, R.N.; Chakravartty, J.K.

    2016-01-01

    Zr-2.5%Nb alloys are extensively used as high temperature pressure tubes in nuclear reactor. Therefore creep behavior of this alloy is of considerable importance. The paper presents creep strain-time plots on two sets of specimens made from two as received pressure tubes having different diameters. These tubes were reported to have undergone different processing routes; both tubes were autoclaved at the same temperature in the steam atmosphere. A comparison of the creep strain-time plots of the two sets of specimen under identical test conditions showed a marked difference. The chemical composition and the microstructure of the two sets of samples were also found to be similar. Therefore X-ray diffraction patterns were taken from the two tubes. The ratio of intensity of two prominent reflections from 0002 and 1120 planes of alpha Zr in the case of 90mm tube was found to be 1.79; whereas that from the 110mm tube was 0.25. This suggests that in the case of 110mm tube most of the basal planes were less favorably oriented with respect to the loading axis. This is the reason why creep strength of 110mm tube was found to be higher. The paper also describes how the effect of texture can be incorporated in evaluating the creep behavior of Zr-Nb alloy. This suggests that a relatively larger volume of creep test data on Zr-2.5Nb pressure tube is necessary to account for the effect texture so that a reliable estimate of its creep life could be obtained. (author)

  5. Excessively High Vapor Pressure of Al-based Amorphous Alloys

    Directory of Open Access Journals (Sweden)

    Jae Im Jeong

    2015-10-01

    Full Text Available Aluminum-based amorphous alloys exhibited an abnormally high vapor pressure at their approximate glass transition temperatures. The vapor pressure was confirmed by the formation of Al nanocrystallites from condensation, which was attributed to weight loss of the amorphous alloys. The amount of weight loss varied with the amorphous alloy compositions and was inversely proportional to their glass-forming ability. The vapor pressure of the amorphous alloys around 573 K was close to the vapor pressure of crystalline Al near its melting temperature, 873 K. Our results strongly suggest the possibility of fabricating nanocrystallites or thin films by evaporation at low temperatures.

  6. Heat transfer and pressure drop of condensation of hydrocarbons in tubes

    Science.gov (United States)

    Fries, Simon; Skusa, Severin; Luke, Andrea

    2018-03-01

    The heat transfer coefficient and pressure drop are investigated for propane. Two different mild steel plain tubes and saturation pressures are considered for varying mass flux and vapour quality. The pressure drop is compared to the Friedel-Correlation with two different approaches to determine the friction factor. The first is calculation as proposed by Friedel and the second is through single phase pressure drop investigations. For lower vapour qualities the experimental results are in better agreement with the approach of the calculated friction factor. For higher vapour qualities the experimental friction factor is more precise. The pressure drop increases for a decreasing tube diameter and saturation pressure. The circumferential temperature profile and heat transfer coefficients are shown for a constant vapour quality at varying mass fluxes. The subcooling is highest for the bottom of the tube and lowest for the top. The average subcooling as well as the circumferential deviation decreases for rising mass fluxes. The averaged heat transfer coefficients are compared to the model proposed by Thome and Cavallini. The experimental results are in good agreement with both correlations, however the trend is better described with the correlation from Thome. The experimental heat transfer coefficients are under predicted by Thome and over predicted by Cavallini.

  7. A REVIEW ON THE ODSCC OF STEAM GENERATOR TUBES IN KOREAN NPPS

    Directory of Open Access Journals (Sweden)

    HANSUB CHUNG

    2013-08-01

    Full Text Available The ODSCC detected in the TSP position of Ulchin 3&4 SGs are typical ODSCC of Alloy 600MA tubes. The causative chemical environment is formed by concentration of impurities inside the occluded region formed by the tube surface, egg crate strips, and sludge deposit there. Most cracks are detected at or near the line contacts between the tube surface and the egg crate strips. The region of dense crack population, as defined as between 4th and 9th TSPs, and near the center of hot leg hemisphere plane, coincided well with the region of preferential sludge deposition as defined by thermal hydraulics calculation using SGAP computer code. The cracks developed homogeneously in a wide range of SGs, so that the number of cracks detected each outage increased very rapidly since the first detection in the 8th refueling outage. The root cause assessment focused on investigation of the difference in microstructure and manufacturing residual stress in order to reveal the cause of different susceptibilities to ODSCC among identical six units. The manufacturing residual stress as measured by XRD on OD surface and by split tube method indicated that the high residual stress of Alloy 600MA tube played a critical role in developing ODSCC. The level of residual stress showed substantial variations among the six units depending on details of straightening and OD grinding processes. Youngwang 3&4 tubes are less susceptible to ODSCC than U3 and U4 tubes because semi-continuous coarse chromium carbides are formed along the grain boundary of Y3&4 tubes, while there are finer less continuous chromium carbides in U3 and U4. The different carbide morphology is caused by the difference in cooling rate after mill anneal. There is a possibility that high chromium content in the Y3&4 tubes, still within the allowable range of Alloy 600, has made some contribution to the improved resistance to ODSCC. It is anticipated that ODSCC in Y5&6 SGs will be retarded more considerably

  8. Bromine-quenched high temperature G-M tube with passivated cathode

    International Nuclear Information System (INIS)

    Mitrofanov, N.

    1975-01-01

    A bromine doped self-quenching Geiger-Mueller tube having an operational life expectancy in excess of 1,200 hours at a temperature of 315 0 C is described. The tube comprises a passivated metal coated cathode which is conditioned or aged for operation at room temperature, thus obviating the necessity of thermally cycling the tube at progressively elevated temperatures. Useful metal coatings for the cathode include chromium, platinum, and nickel-copper alloys deposited in a layer less than about 1 mil thick. A method for passivating the metal coated cathode and subsequently conditioning the tube and its contents is disclosed. (auth)

  9. Control rod guide tube of nuclear reactor

    International Nuclear Information System (INIS)

    Suda, Yoshitaka; Ito, Kenji; Matsumoto, Kunio.

    1994-01-01

    Zr having a residual tensile stress of 3 to 10kg/mm 2 in a circumferential direction is used for the main ingredient of a control guide tube of a nuclear reactor. For this purpose, an appropriate correction method such as a roll-correction, tension-correction and press-correction method is applied to an existent Zr-base alloy tube with no substantial residual stress. If the residual tensile stress in the circumferential direction is smaller than 3kg/mm 2 , an effect sufficient to suppress irradiation growth is not obtainable, if it exceeds 10kg/mm 2 , dimensional changes, cracks or the like occurs locally since the wall thickness of the control rod guide tube is small and, accordingly, this often results in failed products as the control guide tube. (N.H.)

  10. Reactor fuel cladding tube with excellent corrosion resistance and method of manufacturing the same

    International Nuclear Information System (INIS)

    Okuda, Takanari; Kanehara, Mitsuo; Abe, Katsuhiro; Nishimura, Takashi.

    1995-01-01

    The present invention provides a fuel cladding tube having an excellent corrosion resistance and thus a long life, and a suitable manufacturing method therefor. Namely, in the fuel cladding tube, the outer circumference of an inner layer made of a zirconium base alloy is coated with an outer layer made of a metal more corrosion resistant than the zirconium base alloy. Ti or a titanium alloy is suitable for the corrosion resistant metal. In addition, the outer layer can be coated by a method such as vapor deposition or plating, not limited to joining of the inner layer material and the outer layer material. Specifically, a composite material having an inner layer made of a zirconium alloy coated by the outer material made of a titanium alloy is applied with hot fabrication at a temperature within a range of from 500 to 850degC and at a fabrication rate of not less than 5%. The fabrication method includes any of extrusion, rolling, drawing, and casting. As the titanium-base alloy, a Ti-Al alloy or a Ti-Nb alloy containing Al of not more than 20wt%, or Nb of not more than 20wt% is preferred. (I.S.)

  11. Optimization of Peripheral Finned-Tube Evaporators Using Entropy Generation Minimization

    OpenAIRE

    Pussoli, Bruno; Barbosa Jr., Jader; da Silva, Luciana; Kaviany, Massoud

    2012-01-01

    The peripheral finned-tube (PFT) is a new geometry for enhanced air-side heat transfer under moisture condensate blockage (evaporators). It consists of individual hexagonal (peripheral) fin arrangements with radial fins whose bases are attached to the tubes and tips are interconnected with the peripheral fins. In this paper, experimentally validated semi-empirical models for the air-side heat transfer and pressure drop are combined with the entropy generation minimization theory to determine ...

  12. Diphasic flow downstream of circulation-water condenser during priming

    International Nuclear Information System (INIS)

    Ibler, B.; Sabaton, M.; Canavelis, R.

    1982-01-01

    The experimental study presented here describes the experiments for visualizing diphasic flow carried out on a 1/10 model of a circulation-water condenser for a 1,300-MW nuclear power unit. The essential object of the experiments was to validate the layout for the tubing proposed by the Design Office, from the point of view of its incidence on the stability of the flows and the mechanical solidity of the structures during the relatively anarchical phase of automatic priming of the condenser. The observations made have rendered it possible firstly to analyse the pattern of flows in greater detail and secondly to conclude that a simplified and cheaper layout of pipes is acceptable without great risk [fr

  13. Method of and apparatus for use in joining tubular components and tube assemblies made thereby

    International Nuclear Information System (INIS)

    Percival, S.R.

    1979-01-01

    A method of joining difficult to weld materials involves the forming of a rolled joint. A particular application is the joining of zirconium alloy calandria tubes to stainless steel tube-plates in a SGHWR. (UK)

  14. Workshop proceedings: U-bend tube cracking in steam generators

    Science.gov (United States)

    Shoemaker, C. E.

    1981-06-01

    A design to reduce the rate of tube failure in high pressure feedwater heaters, a number of failed drawn and stress relieved Monel 400 U-bend tubes removed from three high pressure feedwater heaters was examined. Steam extracted from the turbine is used to preheat the boiler feedwater in fossil fuel fired steam plants to improve thermal efficiency. This is accomplished in a series of heaters between the condenser hot well and the boiler. The heaters closest to the boiler handle water at high pressure and temperature. Because of the severe service conditions, high pressure feedwater heaters are frequently tubed with drawn and stress relieved Monel 400.

  15. Requirements of Inconel 718 alloy for aeronautical applications

    Science.gov (United States)

    Ghiban, Brandusa; Elefterie, Cornelia Florina; Guragata, Constantin; Bran, Dragos

    2018-02-01

    The main requirements imposed by aviation components made from super alloys based on Nickel are presented in present paper. A significant portion of fasteners, locking lugs, blade retainers and inserts are manufactured from Inconel 718 alloy. The thesis describes environmental factors (corrosion), conditions of external aggression (salt air, intense heat, heavy industrial pollution, high condensation, high pressure), mechanical characteristics (tensile strength, creep, density, yield strength, fracture toughness, fatigue resistance) and loadings (tensions, compression loads) that must be satisfied simultaneously by Ni-based super alloy, compared to other classes of aviation alloys (as egg. Titanium alloys, Aluminum alloys). For this alloy the requirements are strength, durability, damage tolerance, fail safety and so on. The corrosion can be an issue, but the fatigue under high-magnitude cyclic tensile loading it what limits the lifetime of the airframe. The excellent malleability and weldability characteristics of the 718 system make the material physical properties tolerant of manufacturing processes. These characteristics additionally continue to provide new opportunities for advanced manufacturing methods.

  16. Dimensioning of emergency condensers in accordance with safety requirements

    Energy Technology Data Exchange (ETDEWEB)

    Palavecino, C [SIEMENS, Energieerzeugung, Offenbach (Germany)

    1996-12-01

    The emergency condensers are heat exchangers consisting of a parallel arrangement of horizontal U-tubes between two common heads. The tope header is connected via piping to the reactor vessel steam space, while the lower header is connected to the reactor vessel below the reactor vessel water level. The heat exchangers are located in a pool filled with cold water. The emergency condensers and the reactor vessel thus form a system of communicating pipes. At normal reactor water level, the emergency condensers are flooded with cold, non-flowing water. No heat transfer takes place in this condition. If there is a drop in the reactor water level, the heat exchanging surfaces are gradually uncovered and the incoming steam condenses on the cold surfaces. The cold condensate in returned to the reactor vessel. In this way, heat is removed from the reactor vessel and water simultaneously supplied to the reactor vessel. This means that the emergency condensers function as a heat removal system while at the same time serving as HP and LP coolant injection systems. The emergency condensers operate with the highest possible degree of passivity imaginable, namely through a drop in the reactor vessel water level alone, requiring neither control systems nor power supply. The design of the emergency condensers must meet the requirements dictated by the thermal and the hydraulic conditions. Taking into consideration a redundancy degree of N + 2, a specific thermal rating of 63 MW per emergency condenser results for a reactor with an output of 2778 MW. The total performance of the emergency condenser system in thus 252 MW, or 9.1% of reactor output. The probability of failure of the emergency condenser of Siemens SWR 1000 is approximately 10{sup -4} per demand, while that of the older emergency condenser designs is approximately 2 to 3 x 10{sup -3} per demand. (author). 7 figs, 2 tabs.

  17. Feasibility of Shape-Memory Ni/Ti Alloy Wire Containing Tube Elevators for Transcrestal Detaching Maxillary Sinus Mucosa: Ex Vivo Study

    Directory of Open Access Journals (Sweden)

    Yanfeng Li

    2016-12-01

    Full Text Available Background: Osteotome sinus floor elevation is a less invasive approach to augment an insufficient alveolar bone at the posterior maxilla for dental implantation. However, this approach has some limitations due to the lack of sinus lift tools available for clinical use and the small transcrestal access to the maxillary sinus floor. We recently invented shape-memory Ni/Ti alloy wire containing tube elevators for transcrestal detaching maxillary sinus mucosa, and developed goat ex vivo models for direct visualizing the effectiveness of detaching sinus mucosa in real time during transcrestal maxillary sinus floor elevation. Methods: We evaluated our invented elevators, namely elevator 012 and elevator 014, for their effectiveness for transcrestal detaching maxillary sinus mucosa using the goat ex vivo models. We measured the length of sinus mucosa detached in mesial and distal directions or buccal and palatal directions, and the space volume created by detaching maxillary sinus mucosa in mesial, distal, buccal and palatal directions using the invented elevators. Results: Elevator 012 had a shape-memory Ni/Ti alloy wire with a diameter of 0.012 inch, while elevator 014 had its shape-memory Ni/Ti alloy wire with a diameter of 0.014 inch. Elevator 012 could detach the goat maxillary sinus mucosa in the mesial or distal direction for 12.1±4.3 mm, while in the buccal or palatal direction for 12.5±6.7 mm. The elevator 014 could detach the goat maxillary sinus mucosa for 23.0±4.9 mm in the mesial or distal direction, and for 19.0±8.1 mm in the buccal or palatal direction. An average space volume of 1.7936±0.2079 ml was created after detaching the goat maxillay sinus mucosa in both mesial/distal direction and buccal/palatal direction using elevator 012; while the average space volume created using elevator 014 was 1.8764±0.2366 ml. Conclusion: Both two newly invented tube elevators could effectively detach the maxillary sinus mucosa on the goat ex

  18. Feasibility of Shape-Memory Ni/Ti Alloy Wire Containing Tube Elevators for Transcrestal Detaching Maxillary Sinus Mucosa: Ex Vivo Study.

    Science.gov (United States)

    Li, Yanfeng; Wang, Fuli; Hu, Pin; Fan, Jiadong; Han, Yishi; Liu, Bin; Liu, Tao; Yang, Chunhao; Gu, Xiangmin

    2016-01-01

    Osteotome sinus floor elevation is a less invasive approach to augment an insufficient alveolar bone at the posterior maxilla for dental implantation. However, this approach has some limitations due to the lack of sinus lift tools available for clinical use and the small transcrestal access to the maxillary sinus floor. We recently invented shape-memory Ni/Ti alloy wire containing tube elevators for transcrestal detaching maxillary sinus mucosa, and developed goat ex vivo models for direct visualizing the effectiveness of detaching sinus mucosa in real time during transcrestal maxillary sinus floor elevation. We evaluated our invented elevators, namely elevator 012 and elevator 014, for their effectiveness for transcrestal detaching maxillary sinus mucosa using the goat ex vivo models. We measured the length of sinus mucosa detached in mesial and distal directions or buccal and palatal directions, and the space volume created by detaching maxillary sinus mucosa in mesial, distal, buccal and palatal directions using the invented elevators. Elevator 012 had a shape-memory Ni/Ti alloy wire with a diameter of 0.012 inch, while elevator 014 had its shape-memory Ni/Ti alloy wire with a diameter of 0.014 inch. Elevator 012 could detach the goat maxillary sinus mucosa in the mesial or distal direction for 12.1±4.3 mm, while in the buccal or palatal direction for 12.5±6.7 mm. The elevator 014 could detach the goat maxillary sinus mucosa for 23.0±4.9 mm in the mesial or distal direction, and for 19.0±8.1 mm in the buccal or palatal direction. An average space volume of 1.7936±0.2079 ml was created after detaching the goat maxillay sinus mucosa in both mesial/distal direction and buccal/palatal direction using elevator 012; while the average space volume created using elevator 014 was 1.8764±0.2366 ml. Both two newly invented tube elevators could effectively detach the maxillary sinus mucosa on the goat ex vivo sinus models. Moreover, elevator 014 has advantages over

  19. Thin-walled large-diameter zirconium alloy tubes in CANDU reactors

    International Nuclear Information System (INIS)

    Price, E.G.; Richinson, P.J.

    1978-08-01

    The requirements of the thin-walled large-diameter Zircaloy-2 tubing used in CANDU reactors are reviewed. Strength, residual stress patterns, texture and prior deformation contribute to the stability of these tubes. The extent to which the present manufacturing route meets these requirements is discussed. (author)

  20. Progressive degradation of alloy 690 and the development of a significant improvement in alloy 800CR

    International Nuclear Information System (INIS)

    Staehle, Roger W.; Arioka, Koji; Tapping, Robert

    2015-01-01

    The present most widely used alloys for tubing in steam generators and structural materials in water cooled reactors are Alloy 690 and Alloy 800. However, both alloys, while improved over Alloy 600 may not meet the needs of longer range applications in the range of 80-100 years. Alloy 690 sustains damage resulting from the formation of cavities at grain boundaries which eventually cover about 50% of the area of the grain boundaries with the remainder covering being covered with carbides. The cavities seem to nucleate on the carbides leaving the grain boundaries a structure of cavities and carbides. Such a structure will lead the Alloy 690 to fail completely. Normal Alloy 800 does not produce such cavities and probably retains a large amount of its corrosion resistance but does sustain progressive SCC at low rate. A new alloy, 800CR, has been developed in a collaboration among Arioka, Tapping, and Staehle. This alloy is based on a Cr composition of 23.5-27% with the remainder retaining the previous Alloy 800 composition. 800CR sustains a crack velocity about 100 times less than Alloy 690 and a negligible rate of initiation. The 800CR, alloy is now seeking a patent. (authors)