WorldWideScience

Sample records for cable tray ampacity

  1. Cable tray fire tests

    International Nuclear Information System (INIS)

    Klamerus, L.J.

    1978-01-01

    Funds were authorized by the Nuclear Regulatory Commission to provide data needed for confirmation of the suitability of current design standards and regulatory guides for fire protection and control in water reactor power plants. The activities of this program through August 1978 are summarized. A survey of industry to determine current design practices and a screening test to select two cable constructions which were used in small scale and full scale testing are described. Both small and full scale tests to assess the adequacy of fire retardant coatings and full scale tests on fire shields to determine their effectiveness are outlined

  2. Analytical model for cable tray fires

    International Nuclear Information System (INIS)

    Clarke, R.K.

    1975-09-01

    A model for cable tray fires based on buoyant plume theory is presented. Using the model in conjunction with empirical data on size of natural fires and burning rate of cellulosic materials, estimates are made of the heat flux as a function of vertical and horizontal distance from a tray fire. Both local fires and fires extending along a significant length of tray are considered. For the particular set of fire parameters assumed in the calculations, the current tray separation criteria of five feet vertical and three feet horizontal are found to be marginal for local fires and too small to prevent fire spread for extended tray fires. 8 references. (auth)

  3. Vibration isolation of cable tray hangers

    International Nuclear Information System (INIS)

    Pearce, B.K.; Dixon, M.W.; Jackson, J.E.

    1984-01-01

    Analytical and experimental investigations have been performed to partially evaluate the feasibility of using much more flexible support systems than those presently used to support electrical and control cables in nuclear power plants. This approach, which entails introducing a flexible element between the support and the component being supported, could apply to many types of support systems, such as for piping, HVAC or even bridges. However, this paper addresses the specific case of cable tray hangers only. It was found that, for appropriate stiffness and damping characteristics, this concept could be used effectively to isolate cable trays from hanger motion caused by seismic excitation and to significantly reduce hanger loads while maintaining reasonable displacements. This was found to be true for all variations in system parameters investigated. Thus, the flexible hanger concept appears to offer much potential. However, additional study including full-scale testing and more detailed analysis must be completed before the concept can be validated for plant use

  4. SQUG cable tray and conduit evaluation procedure

    International Nuclear Information System (INIS)

    Smith, P.D.; Eder, S.J.; Conoscente, J.P.

    1990-01-01

    Cable tray and conduit systems for electrical cables are a common feature and industrial facilities. They have an excellent performance history in past strong earthquake, even though they are rarely designed for earthquakes. Considerable data have been gathered on their performance in earthquakes and in shake table testing. The data have been used to develop a procedure for the verification of the seismic adequacy of cable tray and conduit systems in operating nuclear plants. The procedure is discussed in this paper. It will result in substantial savings, such as reduced engineering effort, fewer modifications of existing hardware, and simpler documentation, relative to alternate procedures like dynamic analysis of shake table testing. The procedure ensures safety-function in a unique manner since the methodology used to develop it (1) is based on a large body of historical data and (2) uses a relative approach of ensuring that nuclear plant systems will perform at least as well as systems that performed well in past earthquakes. (orig.)

  5. AmpaCity. Superconducting cables and fault current limiters for the energy supply in conurbations

    International Nuclear Information System (INIS)

    Merschel, F.; Noe, M.; Stemmle, M.; Hobl, A.; Sauerbach, O.

    2013-01-01

    In 2013 RWE Germany is working jointly with cable manufacturer Nexans and with the scientific support of the Karlsruhe Institute of Technology (KIT) to install world's longest superconducting cable in the downtown area electricity grid of Essen. The AmpaCity project is partly funded by the German Federal Ministry of Economics and Technology and is playing an exemplary role in the further development of electricity grids in major cities worldwide. The project consortium presents AmpaCity as a convincing system solution especially with respect to economics and security of supply. Components of the system are a superconducting three-phase AC cable with two terminations and one connection joint in combination with a fault current limiter, which is also based on superconducting materials. The superconducting system is designed for 10 kV nominal voltage and 40 MW nominal power. It will replace a 110 kV cable system of equal capacity. At the same time, the project partners are paving the way for high failsafe performance, as the cable in conjunction with the fault current limiter cannot be overloaded by short circuit currents in the event of faults in the grid. Planning and follow up on the civil works in Essen posed a major challenge. Cable laying in the inner city, with various crossings of major highways, tramways, as well as already dense cable routes necessitated very thorough preparation and coordination. The civil works in Essen started in April 2013. At around the same time, after the cable had passed the type test, it went into production. Cable laying is scheduled for late summer. After commissioning, planned for the end of 2013, the field trial will run for at least two years under real grid conditions, to demonstrate this technology's suitability for wider deployment.

  6. Cable tray ultimate strength test employing a large shaker table

    Energy Technology Data Exchange (ETDEWEB)

    Komatsu, K.; Myojin, K.; Imai, K. [The Kansai Electric Power Co., Osaka (Japan); Fuyama, H. [Mitsubishi Heavy Industries Ltd, Takasago (Japan); Kokubo, E. [Mitsubishi Heavy Industdries Ltd, Kobe (Japan)

    2004-07-01

    Ultimate behaviors of cable trays, used in nuclear plants, have not been well studied since cable trays are designed based on conservative design criteria. In this study, by employing a large shaker table, an ultimate strength test was conducted for cable trays used in nuclear power plants. This report describes the results of shaker table test. The following results were obtained. First, in an S{sub 2} earthquake, the damping ratio was so large - more than 30% due to the rubbing of cables - that a large response was not present and the strains in the support were within the elastic limits. Secondly, the support was strong enough to sustain the cable trays even when the strain in the support was 20 times larger than the elastic limit. (authors)

  7. Calculation of harmonic losses and ampacity in low-voltage power cables when used for feeding large LED lighting loads

    Directory of Open Access Journals (Sweden)

    N. J. Milardovich

    2014-10-01

    Full Text Available A numerical investigation on the harmonic disturbances in low-voltage cables feeding large LED loads is reported. A frequency domain analysis on several commercially-available LEDs was performed to investigate the signature of the harmonic current injected into the power system. Four-core cables and four single-core cable arrangements (three phases and neutral of small, medium, and large conductor cross sections, with the neutral conductor cross section approximately equal to the half of the phase conductors, were examined. The cables were modelled by using electromagnetic finite-element analysis software. High harmonic power losses (up to 2.5 times the value corresponding to an undistorted current of the same rms value of the first harmonic of the LED current were found. A generalized ampacity model was employed for re-rating the cables. It was found that the cross section of the neutral conductor plays an important role in the derating of the cable ampacity due to the presence of a high-level of triplen harmonics in the distorted current. The ampacity of the cables should be derated by about 40 %, almost independent of the conductor cross sections. The calculation have shown that an incoming widespread use of LED lamps in lighting could create significant additional harmonic losses in the supplying low-voltage lines, and thus more severely harmonic emission limits should be defined for LED lamps.

  8. An enhanced fire hazard assessment model and validation experiments for vertical cable trays

    International Nuclear Information System (INIS)

    Li, Lu; Huang, Xianjia; Bi, Kun; Liu, Xiaoshuang

    2016-01-01

    Highlights: • An enhanced model was developed for vertical cable fire hazard assessment in NPP. • The validated experiments on vertical cable tray fires were conducted. • The capability of the model for cable tray with different cable spacing were tested. - Abstract: The model, referred to as FLASH-CAT (Flame Spread over Horizontal Cable Trays), was developed to estimate the heat release rate for vertical cable tray fire. The focus of this work is to investigate the application of an enhanced model to the single vertical cable tray fires with different cable spacing. The experiments on vertical cable tray fires with three typical cable spacing were conducted. The histories of mass loss rate and flame length were recorded during the cable fire. From the experimental results, it is found that the space between cable lines intensifies the cable combustion and accelerates the flame spread. The predictions by the enhanced model show good agreements with the experimental data. At the same time, it is shown that the enhanced model is capable of predicting the different behaviors of cable fires with different cable spacing by adjusting the flame spread speed only.

  9. An enhanced fire hazard assessment model and validation experiments for vertical cable trays

    Energy Technology Data Exchange (ETDEWEB)

    Li, Lu [Sate Key Laboratory of Fire Science, University of Science and Technology of China, Hefei 230027 (China); Huang, Xianjia, E-mail: huangxianjia@gziit.ac.cn [Joint Laboratory of Fire Safety in Nuclear Power Plants, Institute of Industry Technology Guangzhou & Chinese Academy of Sciences, Guangzhou 511458 (China); Bi, Kun; Liu, Xiaoshuang [China Nuclear Power Design Co., Ltd., Shenzhen 518045 (China)

    2016-05-15

    Highlights: • An enhanced model was developed for vertical cable fire hazard assessment in NPP. • The validated experiments on vertical cable tray fires were conducted. • The capability of the model for cable tray with different cable spacing were tested. - Abstract: The model, referred to as FLASH-CAT (Flame Spread over Horizontal Cable Trays), was developed to estimate the heat release rate for vertical cable tray fire. The focus of this work is to investigate the application of an enhanced model to the single vertical cable tray fires with different cable spacing. The experiments on vertical cable tray fires with three typical cable spacing were conducted. The histories of mass loss rate and flame length were recorded during the cable fire. From the experimental results, it is found that the space between cable lines intensifies the cable combustion and accelerates the flame spread. The predictions by the enhanced model show good agreements with the experimental data. At the same time, it is shown that the enhanced model is capable of predicting the different behaviors of cable fires with different cable spacing by adjusting the flame spread speed only.

  10. Full-scale horizontal cable-tray tests: Fire-propagation characteristics

    International Nuclear Information System (INIS)

    Anon.

    1991-01-01

    At the Fermi National Accelerator Center (Fermilab), as at any high-energy physics laboratory, the experimental program depends on complex arrays of equipment that require years to assemble and place in service. These equipment arrays are typically located in enclosed tunnels or experimental halls and could be destroyed by rapidly propagating, uncontrolled fire. Cable trays, both vertical and horizontal, are an integral and ubiquitous component of these installations. Concurrently, throughout industry and within the professional fire-fighting community, there has been concern over the flammability and fire propagation characteristics of electrical cables in open cable trays. While some information was available concerning fire propagation in vertical cable trays, little was known about fires in horizontal cable trays. In view of the potential for loss of equipment and facilities, not to mention the programmatic impact of a fire, Fermilab initiated a program of full-scale, horizontal cable-tray fire tests to determine the flammability and rate of horizontal fire propagation in cable-tray configurations and cable mixed typical of those existing in underground tunnel enclosures and support buildings as Fermilab. This series of tests addressed the effects of ventilation rates and cable-tray fill, fire-fighting techniques, and the effectiveness and value of automatic sprinklers, smoke detection, and cable-coating fire barriers in detecting, controlling, or extinguishing a cable-tray fire. Detailed descriptions of each fire test, including sketches of cable-tray configuration and contents, instrumentation, ventilation rates, Fermilab Fire Department personnel observations, photographs, and graphs of thermocouple readings are available in a report of these tests prepared by the Fermilab Safety Section

  11. Reduction of seismic loads in cable tray hangers

    International Nuclear Information System (INIS)

    Pearce, B.K.; Jackson, J.E.; Dixon, M.W.; Bourne, F.R.

    1984-01-01

    A study has been conducted to partially assess the feasibility of using flexible rather than rigid support systems for carrying electrical and control cables in nuclear power plants. Using analytical and experimental studies, it was found that a flexible hanger design with appropriate stiffness and damping characteristics could be used to isolate trays from hanger vibration and significantly reduce hanger loads during seismic events if the connectors could be adequately tuned to account for system variables. Finite element techniques were used to select a flexible connector for a specified base hanger system. Tests were conducted on one-third-scale models to establish values for some of the parameters and to partially verify the analytical methods. For the hanger systems considered, introduction of the flexible connector allowed support-hanger loads and hanger displacements to be reduced greatly while satisfying tray displacement constraints. It appears that a flexible-connector system can provide better dynamic response than the conventional type system using rigid connectors. This conclusion is valid for all variations in system parameters studied. Although the flexible-connector concept looks very promising based on this study, substantial work, including full-scale testing, must be completed before this concept can be validated for actual plant designs. (orig.)

  12. Report on full-scale horizontal cable tray fire tests, FY 1988

    International Nuclear Information System (INIS)

    Riches, W.M.

    1988-09-01

    In recent years, there has been much discussion throughout industry and various governmental and fire protection agencies relative to the flammability and fire propagation characteristics of electrical cables in open cable trays. It has been acknowledged that under actual fire conditions, in the presence of other combustibles, electrical cable insulation can contribute to combustible fire loading and toxicity of smoke generation. Considerable research has been conducted on vertical cable tray fire propagation, mostly under small scale laboratory conditions. In July 1987, the Fermi National Accelerator Laboratory initiated a program of full scale, horizontal cable tray fire tests, in the absence of other building combustible loading, to determine the flammability and rate of horizontal fire propagation in cable tray configurations and cable mixes typical of those existing in underground tunnel enclosures and support buildings at the Laboratory. The series of tests addressed the effects of ventilation rates and cable tray fill, fire fighting techniques, and effectiveness and value of automatic sprinklers, smoke detection and cable coating fire barriers in detecting, controlling or extinguishing a cable tray fire. This report includes a description of the series of fire tests completed in June 1988, as well as conclusions reached from the test results

  13. On seismic design of cable trays and their supports

    International Nuclear Information System (INIS)

    Hartmann, B.

    1978-01-01

    Codes presently in force for design of nuclear power plants require seismic qualification for all electric equipment. In the case of cable trays and their supports one usually attempts to meet the requirements of the code by stiffening a standardized design. This procedure leads to impracticall,imensions for the mountings and, above all, to the loss of the modular character. With strong earthquakes however, it may become irrational at all. This paper suggests an alternate strategy. It starts with a standardized system again, adding some units. These are on the one hand diagonal bracing elements, arbitrarily to arrange, thus gaining a more or less rigid supporting framework. And on the other hand as an essential modification, elastomer rubber pads are inserted as spring bearings. With these pads between the supporting and the adjoining structure, the assembly becomes tractable with respect to earthquake qualification. The question of material properties is also addressed. The elastomer pads have to be chosen so as to fulfil all expected functions under usual as well as extreme environmental conditions. (Author)

  14. Test-based approach to cable tray support system analysis and design: Behavior and test methods

    Energy Technology Data Exchange (ETDEWEB)

    Reigles, Damon G., E-mail: dreigles@engnovex.com [engNoveX, Inc., 19C Trolley Square, Wilmington, DE 19806 (United States); Brachmann, Ingo; Johnson, William H. [Bechtel Nuclear, Security & Environmental, 12011 Sunset Hills Rd, Suite 110, Reston, VA 20190 (United States); Gürbüz, Orhan [Tobolski Watkins Engineering, Inc., 4125 Sorrento Valley Blvd, Suite B, San Diego, CA 92121 (United States)

    2016-06-15

    Highlights: • Describes dynamic response behavior of unistrut type cable tray supports. • Summarizes observations from past full-scale shake table test programs. • Outlines testing methodologies necessary to identify key system parameters. - Abstract: Nuclear power plant safety-related cable tray support systems subjected to seismic loadings were originally understood and designed to behave as linear elastic systems. This behavioral paradigm persisted until the early 1980s when, due to evolution of regulatory criteria, some as-installed systems needed to be qualified to higher seismic motions than originally designed for. This requirement prompted a more in-depth consideration of the true seismic response behavior of support systems. Several utilities initiated extensive test programs, which demonstrated that trapeze strut-type cable tray support systems exhibited inelastic and nonlinear response behaviors with plastic hinging at the connections together with high damping due to bouncing of cables in the trays. These observations were used to demonstrate and justify the seismic adequacy of the aforementioned as-installed systems. However, no formalized design methodology or criteria were ever established to facilitate use of these test data for future evaluations. This paper assimilates and reviews the various test data and conclusions for the purpose of developing a design methodology for the seismic qualification of safety-related cable tray support systems.

  15. Full-scale fire experiments on vertical horizontal cable trays

    International Nuclear Information System (INIS)

    Mangs, J.; Keski-Rahkonen, O.

    1997-10-01

    Two full-scale fire experiments on PVC cables used in nuclear power plants were carried out, one with cables in vertical position and one with cables in horizontal position. The vertical cable bundle, 3 m high, 300 mm wide and 30 mm thick, was attached to a steel cable ladder. The vertical bundle experiment was carried out in nearly free space with three walls near the cable ladder guiding air flow in order to stabilise flames. The horizontal cable experiment was carried out in a small room with five cable bundles attached to steel cable ladders. Three of the 2 m long cable bundles were located in an array, equally spaced above each other near one long side of the room and two correspondingly near the opposite long side. The vertical cable bundle was ignited with a small propane gas burner beneath the lower edge of the bundle. The horizontal cable bundles were ignited with a small propane burner beneath the lowest bundle in an array of three bundles. Rate of heat release by means of oxygen consumption calorimetry, mass change, CO 2 , CO and smoke production rate and gas, wall and cable surface temperatures were measured as a function of time, as well as time to sprinkler operation and failure of test voltage in cables. Additionally, the minimum rate of heat release needed to ignite the bundle was determined. This paper concentrates on describing and recording the experimental set-up and the data obtained. (orig.)

  16. Ceramic fiber blanket wrap for fire protection of cable trays and conduits

    International Nuclear Information System (INIS)

    Chaille, C.E.; Reiman, R.J.

    1980-01-01

    In some areas of nuclear power plants, cables of redundant electrical systems, which are necessary for the safe shutdown of the reactor, are in close proximity. If a fire should occur in one of these areas, both electrical systems could be destroyed before the fire is extinguished and control of the reactor may be lost. A ceramic fiber blanket was evaluated as a fire protective wrap around cable trays and conduits. 2 refs

  17. Assessment of the burning behavior of protected and unprotected cables and cable trays in nuclear installations using small- and large-scale experiments

    Energy Technology Data Exchange (ETDEWEB)

    Siemon, Matthias; Riese, Olaf; Zehfuss, Jochen [Technische Univ. Braunschweig (Germany). Inst. fuer Baustoffe, Massivbau und Brandschutz (iBMB)

    2015-12-15

    Electric installations and cables are a main fire risk source in industrial buildings and power plants. In general, cables and cable systems are associated with flash-over phenomena due to pyrolysis of fuel gases induced by the heat of an adjacent fire, fire spread along cable trays affecting additional areas besides the fire origin, being an ignition source due to malfunction. If burning, cables can emit large amounts of smoke and toxic products affecting occupants as well as the long-term functionality of structure and installations. Paying attention to these risks has led to the development of fire retardant non-corrosive (non-halogenated) cables which are qualified to reduce the individual or all of the risks mentioned. For existing installations in industrial buildings and power plants with halogenated cables, different protection measures are available and widely applied retroactively. Important protective measures are intumescent or ablative coatings, cable casings and bindings. For qualification of the effects of the protection measures, small-scale tests investigating a single cable specimen as well as large-scale cable tray test setups have been developed and carried out in the last 20 years at iBMB. In this paper, these test results are analysed regarding their effects on the heat release, ignition time and fire spread over cable trays. Furthermore, national and international research projects have investigated the burning behaviour of different cable types, tray installations, tray loading and spacing and ventilation conditions. As a conclusion, the main outcomes of past researches are summarized. Influence factors (e.g. pre-heating due to high power utilization, influence of cable aging) which have not been accounted for in detail are emphasized. The modelling of unprotected cables has been internationally studied in recent years. For future applications, the question of applicability of recently developed sub-models on the fire behaviour of protected

  18. Fully predictive simulation of real-scale cable tray fire based on small-scale laboratory experiments

    Energy Technology Data Exchange (ETDEWEB)

    Beji, Tarek; Merci, Bart [Ghent Univ. (Belgium). Dept. of Flow, Heat and Combustion Mechanics; Bonte, Frederick [Bel V, Brussels (Belgium)

    2015-12-15

    This paper presents a computational fluid dynamics (CFD)-based modelling strategy for real-scale cable tray fires. The challenge was to perform fully predictive simulations (that could be called 'blind' simulations) using solely information from laboratory-scale experiments, in addition to the geometrical arrangement of the cables. The results of the latter experiments were used (1) to construct the fuel molecule and the chemical reaction for combustion, and (2) to estimate the overall pyrolysis and burning behaviour. More particularly, the strategy regarding the second point consists of adopting a surface-based pyrolysis model. Since the burning behaviour of each cable could not be tracked individually (due to computational constraints), 'groups' of cables were modelled with an overall cable surface area equal to the actual value. The results obtained for one large-scale test (a stack of five horizontal trays) are quite encouraging, especially for the peak Heat Release Rate (HRR) that was predicted with a relative deviation of 3 %. The time to reach the peak is however overestimated by 4.7 min (i.e. 94 %). Also, the fire duration is overestimated by 5 min (i.e. 24 %). These discrepancies are mainly attributed to differences in the HRRPUA (heat release rate per unit area) profiles between the small-scale and large-scale. The latter was calculated by estimating the burning area of cables using video fire analysis (VFA).

  19. An evaluation of methodology for seismic qualification of equipment, cable trays, and ducts in ALWR plants by use of experience data

    International Nuclear Information System (INIS)

    Bandyopadhyay, K.K.; Kana, D.D.; Kennedy, R.P.; Schiff, A.J.

    1997-07-01

    Advanced Reactor Corporation (ARC) has developed a methodology for seismic qualification of equipment, cable trays and ducts in Advanced Light Water Reactor plants. A Panel (members of which acted as individuals) supported by the Office of Nuclear Regulatory Research of the Nuclear Regulatory Commission has evaluated this methodology. The review approach and observations are included in this report. In general, the Panel supports the ARC methodology with some exceptions and provides recommendations for further improvements. 26 refs., 10 figs., 1 tab

  20. An evaluation of methodology for seismic qualification of equipment, cable trays, and ducts in ALWR plants by use of experience data

    Energy Technology Data Exchange (ETDEWEB)

    Bandyopadhyay, K.K.; Kana, D.D.; Kennedy, R.P.; Schiff, A.J.

    1997-07-01

    Advanced Reactor Corporation (ARC) has developed a methodology for seismic qualification of equipment, cable trays and ducts in Advanced Light Water Reactor plants. A Panel (members of which acted as individuals) supported by the Office of Nuclear Regulatory Research of the Nuclear Regulatory Commission has evaluated this methodology. The review approach and observations are included in this report. In general, the Panel supports the ARC methodology with some exceptions and provides recommendations for further improvements. 26 refs., 10 figs., 1 tab.

  1. Understanding losses in three core armoured submarine cables

    DEFF Research Database (Denmark)

    Silva, Filipe Miguel Faria da; Ebdrup, Thomas; Bak, Claus Leth

    2016-01-01

    . For practical an economical reasons the preferred choice of cable for both the array and the transmission cables are three-core armoured submarine cables. Therefore, it has becoming increasingly important to be able to calculate the ampacity of such cables accurately. At present time, the ampacity of three......-core armoured submarine cables is calculated according to IEC 60287-1-1 [1]. Various measurements conducted both by cable manufacturers and transmission system operators (TSO) have shown that using the cable rating method stated in IEC 60287-1-1 underestimates the cable ampacity [2]-[6]. Furthermore......, measurements conducted within the cable industry have shown that an armoured three core cable has higher losses than equal unarmoured three core cables. It is also suggested that the inaccuracy in the IEC armour’s loss factor (λ2) is the main responsible for the conservatism in the IEC cable rating method...

  2. Intelligent printing system with AMPAC: boot program for printing machine with AMPAC

    Science.gov (United States)

    Yuasa, Tomonori; Mishina, Hiromichi

    2000-12-01

    The database AMPAC proposes the simple and unified format to describe single parameter of whole field of design, production and management. The database described by the format can be used commonly in any field connected by the network production system, since the description accepts any parameter in any fields and is field independent definition.

  3. Thermometer by optical fiber for ampacity studies in overhead transmission lines; Termometro a fibra optica para estudo da ampacidade em linhas de transmissao aereas

    Energy Technology Data Exchange (ETDEWEB)

    Valente, L.C.G.; Kawase, L.R.; Silva Filho, J.I. da; Silva, J.M.M. da [Centro de Pesquisas de Energia Eletrica, Rio de Janeiro, RJ (Brazil); Igarashi, A.Y. [Universidade Federal, Rio de Janeiro, RJ (Brazil)

    1995-12-31

    This article suggests the utilization of thermometers constructed from optical fibers technology in overhead power transmission lines. This will help the studies in progress about the electric power systems ampacity. It also presents the advantages of using optical fibers instead of conventional thermometers. As an example, the fact that the optical fibers are dielectric and make possible the remote monitoring. It is also shown a possibility of introducing such measuring system in electric junctions where OPGW cables are used 4 refs., 4 figs.; e-mail: liliana at fis.puc-rio.br

  4. Carbon Nanotube Composite Ampacity and Metallic CNT Buckypaper Conductivity

    Science.gov (United States)

    De Groh, Henry C., III

    2016-01-01

    NASA is currently working on developing motors for hybrid electric propulsion applications in aviation. To make electric power more feasible in airplanes higher power to weight ratios are sought for electric motors. One facet to these efforts is to improve (increase) the conductivity and (lower) density of the magnet wire used in motors. Carbon nanotubes (CNT) and composites containing CNT are being explored as a possible way to increase wire conductivity and lower density. Presented here are measurements of the current carrying capacity (ampacity) of a composite made from CNT and copper. The ability of CNT to improve the conductivity of such composites is hindered by the presence of semiconductive CNT (s-CNT) that exist in CNT supplies naturally, and currently, unavoidably. To solve this problem, and avoid s-CNT, various preferential growth and sorting methods are being explored. A supply of sorted 95 metallic CNT (m-CNT) was acquired in the form of thick film Buckypaper (BP) as part of this work and characterized using Raman spectroscopy, resistivity, and density measurements. The ampacity (Acm2) of the Cu-5volCNT composite was 3.8 lower than the same gauge pure Cu wire similarly tested. The lower ampacity in the composite wire is believed to be due to the presence of s-CNT in the composite and the relatively low (proper) level of longitudinal cooling employed in the test method. Although Raman spectroscopy can be used to characterize CNT, a strong relation between the ratios of the primary peaks GGand the relative amounts of m-CNT and s-CNT was not observed. The average effective conductivity of the CNT in the sorted, 95 m-CNT BP was 2.5 times higher than the CNT in the similar but un-sorted BP. This is an indication that improvements in the conductivity of CNT composites can be made by the use of sorted, highly conductive m-CNT.

  5. Real Time Load Optimisation of Cable Based Transmission Grids

    DEFF Research Database (Denmark)

    Olsen, Rasmus Schmidt; Holbøll, Joachim; Guðmundsdottir, Unnur Stella

    2011-01-01

    Energinet.dk has launched an investigation of dynamic current ratings of cable based transmission grids, where both internal and external parameters are variables. The first topic was to investigate state of the art within calculating the current carrying capacity (ampacity or loadability......) of cables embedded in larger cable systems. Some recently published research has been concerned with dynamic loadability, but such researches are based on many assumptions. It is shown in the paper, that only limited research has been concerned with larger cable grids, and no remarkable work could been...

  6. Advanced superconducting power cable for MV urban power supply

    Energy Technology Data Exchange (ETDEWEB)

    Schmidt, Frank [Nexans Deutschland GmbH, Hannover (Germany); Merschel, Frank [RWE Deutschland AG, Essen (Germany); Noe, Mathias [Karlsruhe Institute of Technology, Karlsruhe (Germany)

    2015-07-01

    In recent years the technology of superconducting power cable systems has progressed such that the technical hurdles preparing for commercial applications have been mastered. Several field tests of large scale prototypes for the applications of superconducting cables as well as superconducting fault current limiters have been successfully accomplished and the technology of such systems is ready for commercialization. The presentation will give a detailed overview of the German AmpaCity project. An overview will be given on the development, manufacturing and installation of the 10 kV, 40 MVA HTS system consisting of a fault current limiter and of a 1 km cable in the city of Essen. Since it is the first time that a one kilometer HTS cable system is installed together with an HTS fault current limiter in a real grid application between two substations within a city center area, AmpaCity serves as a lighthouse project. In addition it is worldwide the longest installed HTS cable system so far. It is expected that relatively large technical advances will be made in the future of the comparatively new HTS technology, which in turn will bring associated cost reductions. For this reason, the AmpaCity pilot project in the downtown area of Essen in Germany will be an important step on the way to achieving more widespread application of HTS technology.

  7. Impacts of rising air temperatures on electric transmission ampacity and peak electricity load in the United States

    Science.gov (United States)

    Bartos, Matthew; Chester, Mikhail; Johnson, Nathan; Gorman, Brandon; Eisenberg, Daniel; Linkov, Igor; Bates, Matthew

    2016-11-01

    Climate change may constrain future electricity supply adequacy by reducing electric transmission capacity and increasing electricity demand. The carrying capacity of electric power cables decreases as ambient air temperatures rise; similarly, during the summer peak period, electricity loads typically increase with hotter air temperatures due to increased air conditioning usage. As atmospheric carbon concentrations increase, higher ambient air temperatures may strain power infrastructure by simultaneously reducing transmission capacity and increasing peak electricity load. We estimate the impacts of rising ambient air temperatures on electric transmission ampacity and peak per-capita electricity load for 121 planning areas in the United States using downscaled global climate model projections. Together, these planning areas account for roughly 80% of current peak summertime load. We estimate climate-attributable capacity reductions to transmission lines by constructing thermal models of representative conductors, then forcing these models with future temperature projections to determine the percent change in rated ampacity. Next, we assess the impact of climate change on electricity load by using historical relationships between ambient temperature and utility-scale summertime peak load to estimate the extent to which climate change will incur additional peak load increases. We find that by mid-century (2040-2060), increases in ambient air temperature may reduce average summertime transmission capacity by 1.9%-5.8% relative to the 1990-2010 reference period. At the same time, peak per-capita summertime loads may rise by 4.2%-15% on average due to increases in ambient air temperature. In the absence of energy efficiency gains, demand-side management programs and transmission infrastructure upgrades, these load increases have the potential to upset current assumptions about future electricity supply adequacy.

  8. TMI cable tracer operation and maintenance manual for assembly 417910

    International Nuclear Information System (INIS)

    Sumstine, R.L.

    1983-11-01

    This manual provides technical information and instructions to operate and maintain the cable tracer designed for the Three Mile Island (TMI) Unit 2 Reactor Building. The TMI cable tracer was developed to allow TMI personnel to trace cables in cable trays that may be tested or sectioned for destructive examination

  9. Analysis on the Ampacity-Testing Feasibility of Steel-Armour Three-Core Cable by Feeding One-phase Curren%以单相电流测试三芯钢带铠装电缆载流量的可行性分析

    Institute of Scientific and Technical Information of China (English)

    赵继光; 牛海清; 张群峰; 游勇; 张尧; 李光明

    2014-01-01

    配电电缆一般为三芯钢带铠装结构,加载于三相导体的交流电流在磁性材料的钢带铠装层将产生工频磁场,由此产生铠装损耗;若三相导体加载三相对称电流,铠装层的合成磁场较小(甚至为零),其铠装损耗较小;若三相导体加载单相电流,铠装层磁场较大,其损耗较大。在开展三芯电缆载流量试验时,由于电源容量限制,拟加载单相电流,可能会对载流量的试验结果产生影响。为研究三芯钢带铠装电缆通以三相和单相电流的铠装损耗,及其对载流量试验结果的影响,本文研究了三芯电缆钢带铠装损耗的计算方法;在试验场开展了加载单相电流的直埋单根三芯电缆载流量试验,定量计算了加载单相电流时的三芯电缆的铠装损耗;分析了加载单相电流时铠装损耗对载流量试验影响的程度。研究表明,三芯铠装电缆加载单相电流时的铠装损耗不可忽略,但对载流量的影响不大,且偏保守。%Distribution three-core cable is usually with steel armour.When AC current is applied to the cable, there is a magnetic field in its armour and then steel armour loss.If the current is three-phase symmetry, the magnetic field of armour is small and its loss is ig-norable; If cable is feed with a single phase current, its magnetic field is big and its armour loss cannot be ignored.For restrict of power capacity, the rating experiments of 10kV cable with cluster laying are intended to apply a single-phase current, which bring in the steel armour loss and may decrease the experiment result.To research the armour loss and its effect on the rating of three-core ca-ble with single-phase current applied, the calculation method of armour loss is research here;the current rating experiment is carried out, its steel armour loss is calculated; and the current ratings applied with single-phase current is compared with that applied with three

  10. Ifa Divination Trays from Isale-Oyo

    OpenAIRE

    Pogoson, O. I.; Akande, A. O.

    2016-01-01

    This paper is a study of the images and patterns on ifa divination trays from Isale-Oyo. The paper also explains some ifa paraphernalia. The paper establishes that ifa trays from Isale-Oyo bear distinctive features when compared with other ifa trays in Yorubaland such as those of Ijebu and Osogbo. Central to this study is the iconographic description and interpretations of Isale-Oyo divination trays. Data were collected through direct interviews with divination tray owners. Photographs of ...

  11. Performance testing of the new AMPAC fire debris bag against three other commercial fire debris bags.

    Science.gov (United States)

    Grutters, Michiel M P; Dogger, Judith; Hendrikse, Jeanet N

    2012-09-01

    Fire debris evidence is collected and stored in a wide range of containers, including various polymer bags. Four different polymer bags have been investigated, including the NYLON, DUO, ALU, and AMPAC bags. The latter is the successor of the Kapak Fire DebrisPAK™. Microscopy and infrared spectroscopy were used to elucidate the composition of the bags. Gas chromatography/mass spectrometry was used to investigate performance parameters such as background volatiles, leak rate, cross-contamination, recovery, and sorption. The NYLON bag was susceptible for leakage and cross-contamination and showed decreased recoveries. The DUO and ALU bags showed some background volatiles, sorption, and poor recoveries. The AMPAC bag performed excellent: low background, no leakage or cross-contamination, good recoveries, and only traces of sorption. Heat sealing proved to be the best method of closure. Preliminary studies on AMPAC bags showed that polyethylene clamps are easy to use on-site and preserve ignitable liquids adequately for a limited period of time. © 2012 American Academy of Forensic Sciences.

  12. Gamma scanning of large sieve tray towers

    International Nuclear Information System (INIS)

    McCaw, D.D.; Hulbert, V.G.; Smith, A.E.

    1976-01-01

    A special instrument based on the use of gamma rays, has been developed, which assists in the evaluation of the effects of changes in controlled variables on sieve tray performance. Internal structural damage, and local tray flooding are readily detectable from outside the vessel. The instrument is described, and examples of its use are given. (author)

  13. Startup and operation at the Browns Ferry Nuclear Plant (includes March 22, 1975, cabel tray fire)

    International Nuclear Information System (INIS)

    Metke, R.G.

    1977-01-01

    This paper addresses itself to significant events experienced during startup and operation of the three unit Browns Ferry Nuclear Plant located near Athens, Alabama. It consists of two major parts: (1) Resolution of significant equipment problems, and (2) Description of the March 22, 1975, cable tray fire. Identification of principal problems and their solutions should help prevent similar obstacles and related costly delays at other nuclear stations

  14. Comparing surgical trays with redundant instruments with trays with reduced instruments: a cost analysis.

    Science.gov (United States)

    John-Baptiste, A; Sowerby, L J; Chin, C J; Martin, J; Rotenberg, B W

    2016-01-01

    When prearranged standard surgical trays contain instruments that are repeatedly unused, the redundancy can result in unnecessary health care costs. Our objective was to estimate potential savings by performing an economic evaluation comparing the cost of surgical trays with redundant instruments with surgical trays with reduced instruments ("reduced trays"). We performed a cost-analysis from the hospital perspective over a 1-year period. Using a mathematical model, we compared the direct costs of trays containing redundant instruments to reduced trays for 5 otolaryngology procedures. We incorporated data from several sources including local hospital data on surgical volume, the number of instruments on redundant and reduced trays, wages of personnel and time required to pack instruments. From the literature, we incorporated instrument depreciation costs and the time required to decontaminate an instrument. We performed 1-way sensitivity analyses on all variables, including surgical volume. Costs were estimated in 2013 Canadian dollars. The cost of redundant trays was $21 806 and the cost of reduced trays was $8803, for a 1-year cost saving of $13 003. In sensitivity analyses, cost savings ranged from $3262 to $21 395, based on the surgical volume at the institution. Variation in surgical volume resulted in a wider range of estimates, with a minimum of $3253 for low-volume to a maximum of $52 012 for high-volume institutions. Our study suggests moderate savings may be achieved by reducing surgical tray redundancy and, if applied to other surgical specialties, may result in savings to Canadian health care systems.

  15. Develop and Manufacture an airlock sliding tray

    Energy Technology Data Exchange (ETDEWEB)

    Lawton, Cindy M. [Los Alamos National Lab. (LANL), Los Alamos, NM (United States)

    2014-02-26

    The goal of this project is to continue to develop an airlock sliding tray and then partner with an industrial manufacturing company for production. The sliding tray will be easily installed into and removed from most glovebox airlocks in a few minutes. Technical Approach: A prototype of a sliding tray has been developed and tested in the LANL cold lab and 35 trays are presently being built for the plutonium facility (PF-4). The current, recently approved design works for a 14-inch diameter round airlock and has a tray length of approximately 20 inches. The grant will take the already tested and approved round technology and design for the square airlock. These two designs will be suitable for the majority of the existing airlocks in the multitude of DOE facilities. Partnering with an external manufacturer will allow for production of the airlock trays at a much lower cost and increase the availability of the product for all DOE sites. Project duration is estimated to be 12-13 months. Benefits: The purpose of the airlock sliding trays is fourfold: 1) Mitigate risk of rotator cuff injuries, 2) Improve ALARA, 3) Reduce risk of glovebox glove breaches and glove punctures, and 4) Improve worker comfort. I have had the opportunity to visit many other DOE facilities including Savannah, Y-12, ORNL, Sandia, and Livermore for assistance with ergonomic problems and/or injuries. All of these sites would benefit from the airlock sliding tray and I can assume all other DOE facilities with gloveboxes built prior to 1985 could also use the sliding trays.

  16. Cable fire tests in France

    International Nuclear Information System (INIS)

    Kaercher, M.

    2000-01-01

    Modifications are being carried out in all French nuclear power plants to improve fire safety. These modifications are based on a three level defense in depth concept: fire preventing, fire containing and fire controlling. Fire containing requires many modifications such as protection of cable races and assessment of fire propagation which both need R and D development. On one hand, cable wraps made with mineral wool were tested in all configurations including effect of aging, overheating and fire and qualified for the use as protection from common failure modes. On the other hand, cables races in scale one were subject to gas burner or solvent pool fire to simulate ignition and fire propagation between trays and flash over situations. These tests have been performed under several typical lay out conditions. The results of the tests can be used as input data in computer modelling for validation of fire protection measures. (orig.) [de

  17. View of food tray to be used in Skylab program

    Science.gov (United States)

    1972-01-01

    A close-up view of a food tray which is scheduled to be used in the Skylab program. Several packages of space food lie beside the tray. The food in the tray is ready to eat. Out of tray, starting from bottom left: grape drink, beef pot roast, chicken and rice, beef sandwiches and sugar cookie cubes, In tray, from back left: orange drink, strawberries, asparagus, prime rib, dinner roll and butterscotch pudding in the center.

  18. Ifa Divination Trays from Isale-Oyo

    Directory of Open Access Journals (Sweden)

    O. I. Pogoson

    2011-10-01

    Full Text Available This paper is a study of the images and patterns on ifa divination trays from Isale-Oyo. The paper also explains some ifa paraphernalia. The paper establishes that ifa trays from Isale-Oyo bear distinctive features when compared with other ifa trays in Yorubaland such as those of Ijebu and Osogbo. Central to this study is the iconographic description and interpretations of Isale-Oyo divination trays. Data were collected through direct interviews with divination tray owners. Photographs of the trays were also taken. The investigation revealed that:Divination trays from Isale-Oyo combine features found on both Ijebu and Osogbo trays.The Esu figure continues to occupy the top central position on Oyo divination trays, even though with representational variations elsewhere in Yorubaland.Some divination trays in Oyo carry no decorations on their borders, and in some recent cases, ceramic plates are now used for divination.Este artigo trata dos padrões e imagens dos tabuleiros de adivinhação ifa usados em Isale-Oyo (Nigéria, bem como de outros objectos religiosos associados. Argumenta-se que os tabuleiros ifa de Isale-Oyo têm características que os distinguem de outros tabuleiros ifa da região yoruba, como os de Ijebu e Osogbo. A descrição e a interpretação da iconografia dos tabuleiros de adivinhação constituem o foco deste estudo. Os dados discutidos foram recolhidos através de entrevistas a proprietários de tabuleiros de adivinhação e fotografias de tabuleiros. Conclui-se que:Os tabuleiros de adivinhação de Isale-Oyo combinam traços dos tabuleiros de Ijebu e dos tabuleiros de Osogbo.A figura de Esu continua a ocupar a posição central superior nos tabuleiros de adivinhação de Oyo, embora se registem variações na sua representação noutras zonas do território yoruba.Alguns tabuleiros de adivinhação de Oyo não possuem qualquer decoração nos frisos, e nalguns casos recentes vêm sendo utilizados na adivinhação pratos

  19. Design guide for fire protection of grouped electrical cables

    International Nuclear Information System (INIS)

    Dungan, K.W.

    1991-05-01

    This paper develops design guidance for fire protection of grouped electrical cables using previous research and the concept of design objectives based on damage limits. A quantitative approach is taken to establishing performance-oriented design objectives and addressing fires exposing cables as well as cable fires. A one-page Design Calculation Checklist is developed and examples are shown. In addition, testing was done for placement of linear thermal detection on cable trays and recommendations are given. 32 refs., 10 figs., 8 tabs

  20. How do you like them cables?

    CERN Multimedia

    Sergei Malyukov

    Cabling work is not for clautrophobic people! Cables are like the blood vessels and nervous system of ATLAS. With the help of all these cables, we can power ATLAS, control the detector and read out the data. Like the human blood vessels, they penetrate inside the ATLAS volume, reaching each of its elements. The ATLAS developers started to think about design of services, cables and pipes at the very first stages of the project. The cabling project has been developing most intensively during the last five years, passing through the projection and CAD design phases, then the installation of cable trays and finally the cables. The cable installation itself took two and a half years and was done by teams of technicians from several institutes from Russia, the Czech Republic and Poland. Here are some numbers to illustrate the scale of the ATLAS cabling system. More than 25000 optical fiber channels are used for reading the information from the sub-detectors and delivering the timing signals. The total numbe...

  1. Steady State Modelling of Three-core Wire Armoured Submarine Cables

    DEFF Research Database (Denmark)

    Baù, Matteo; Viafora, Nicola; Hansen, Chris Skovgaard

    2016-01-01

    This paper introduces Finite Element Method mod-elling techniques applied to wire armoured submarine three-core cables, whose nominal voltages range from 36 to 245 kV. The analysis is focused on the implementation of the net voltage cancellation principle in a 2D environment. The model is utilised...... confirm that the wire armour stranding is not accounted for, but also suggest that the ampacity underrating might be due to other inaccuracies in the IEC modelling indications. Overall, the difference in terms of current rating between the FEM and the IEC approach is found to be voltage dependent and more...

  2. Ni Nanobuffer Layer Provides Light-Weight CNT/Cu Fibers with Superior Robustness, Conductivity, and Ampacity.

    Science.gov (United States)

    Zou, Jingyun; Liu, Dandan; Zhao, Jingna; Hou, Ligan; Liu, Tong; Zhang, Xiaohua; Zhao, Yonghao; Zhu, Yuntian T; Li, Qingwen

    2018-03-07

    Carbon nanotube (CNT) fiber has not shown its advantage as next-generation light-weight conductor due to the large contact resistance between CNTs, as reflected by its low conductivity and ampacity. Coating CNT fiber with a metal layer like Cu has become an effective solution to this problem. However, the weak CNT-Cu interfacial bonding significantly limits the mechanical and electrical performances. Here, we report that a strong CNT-Cu interface can be formed by introducing a Ni nanobuffer layer before depositing the Cu layer. The Ni nanobuffer layer remarkably promotes the load and heat transfer efficiencies between the CNT fiber and Cu layer and improves the quality of the deposited Cu layer. As a result, the new composite fiber with a 2 μm thick Cu layer can exhibit a superhigh effective strength >800 MPa, electrical conductivity >2 × 10 7 S/m, and ampacity >1 × 10 5 A/cm 2 . The composite fiber can also sustain 10 000 times of bending and continuously work for 100 h at 90% ampacity.

  3. Cooling unit for a superconducting power cable. Two years successful operation

    Energy Technology Data Exchange (ETDEWEB)

    Herzog, Friedhelm [Messer Group GmbH, Krefeld (Germany); Kutz, Thomas [Messer Industriegase GmbH, Bad Soden (Germany); Stemmle, Mark [Nexans Deutschland GmbH, Hannover (Germany); Kugel, Torsten [Westnetz GmbH, Essen (Germany)

    2016-07-01

    High temperature super conductors (HTS) can efficiently be cooled with liquid nitrogen down to a temperature of 64 K (-209 C). Lower temperatures are not practical, because nitrogen becomes solid at 63 K (-210 C). To achieve this temperature level the coolant has to be vaporized below atmospheric pressure. Messer has developed a cooling unit with an adequate vacuum subcooler, a liquid nitrogen circulation system, and a storage vessel for cooling an HTS power cable. The cooling unit was delivered in 2013 for the German AmpaCity project of RWE Deutschland AG, Nexans and Karlsruhe Institute of Technology. Within this project RWE and Nexans installed the worldwide longest superconducting power cable in the city of Essen, Germany. The cable is in operation since March 10th, 2014.

  4. TrayGen: Arranging objects for exhibition and packaging

    KAUST Repository

    Yang, Yongliang; Huang, Qixing

    2013-01-01

    We present a framework, called TrayGen, to generate tray designs for the exhibition and packaging of a collection of objects. Based on principles from shape perception and visual merchandising, we abstract a number of design guidelines on how

  5. The US market for high-temperature superconducting wire in transmission cable applications

    Energy Technology Data Exchange (ETDEWEB)

    Forbes, D

    1996-04-01

    Telephone interviews were conducted with 23 utility engineers concerning the future prospects for high-temperature superconducting (HTS) transmission cables. All have direct responsibility for transmission in their utility, most of them in a management capacity. The engineers represented their utilities as members of the Electric Power Research Institute`s Underground Transmission Task Force (which has since been disbanded). In that capacity, they followed the superconducting transmission cable program and are aware of the cryogenic implications. Nineteen of the 23 engineers stated the market for underground transmission would grow during the next decade. Twelve of those specified an annual growth rate; the average of these responses was 5.6%. Adjusting that figure downward to incorporate the remaining responses, this study assumes an average growth rate of 3.4%. Factors driving the growth rate include the difficulty in securing rights-of-way for overhead lines, new construction techniques that reduce the costs of underground transmission, deregulation, and the possibility that public utility commissions will allow utilities to include overhead costs in their rate base. Utilities have few plans to replace existing cable as preventive maintenance, even though much of the existing cable has exceeded its 40-year lifetime. Ten of the respondents said the availability of a superconducting cable with the same life-cycle costs as a conventional cable and twice the ampacity would induce them to consider retrofits. The respondents said a cable with those characteristics would capture 73% of their cable retrofits.

  6. 21 CFR 872.3670 - Resin impression tray material.

    Science.gov (United States)

    2010-04-01

    ... (CONTINUED) MEDICAL DEVICES DENTAL DEVICES Prosthetic Devices § 872.3670 Resin impression tray material. (a) Identification. Resin impression tray material is a device intended for use in a two-step dental mold fabricating... 21 Food and Drugs 8 2010-04-01 2010-04-01 false Resin impression tray material. 872.3670 Section...

  7. 21 CFR 872.6880 - Preformed impression tray.

    Science.gov (United States)

    2010-04-01

    ...) MEDICAL DEVICES DENTAL DEVICES Miscellaneous Devices § 872.6880 Preformed impression tray. (a) Identification. A preformed impression tray is a metal or plastic device intended to hold impression material... 21 Food and Drugs 8 2010-04-01 2010-04-01 false Preformed impression tray. 872.6880 Section 872...

  8. Fire spread simulation of a full scale cable tunnel

    International Nuclear Information System (INIS)

    Huhtanen, R.

    1999-11-01

    A fire simulation of a full scale tunnel was performed by using the commercial code EFFLUENT as the simulation platform. Estimation was made for fire spread on the stacked cable trays, possibility of fire spread to the cable trays on the opposite wall of the tunnel, detection time of smoke detectors in the smouldering phase and response of sprinkler heads in the flaming phase. According to the simulation, the rise of temperature in the smouldering phase is minimal, only of the order 1 deg C. The estimates of optical density of smoke show that normal smoke detectors should give an alarm within 2-4 minutes from the beginning of the smouldering phase, depending on the distance to the detector (in this case it was assumed that the thermal source connected to the smoke source was 50 W). The flow conditions at smoke detectors may be challenging, because the velocity magnitude is rather low at this phase. At 4 minutes the maximum velocity at the detectors is 0.12 m/s. During the flaming phase (beginning from 11 minutes) fire spreads on the stacked cable trays in an expected way, although the ignition criterion seems to perform poorly when ignition of new objects is considered. The Upper cable trays are forced to ignite by boundary condition definitions according to the experience found from ti full scale experiment and an earlier simulation. After 30 minutes the hot layer in the room becomes so hot that it speeds up the fire spread and the rate of heat release of burning objects. Further, the hot layer ignites the cable trays on the opposite wall of the tunnel after 45 minutes. It is estimated that the sprinkler heads would be activated at 20-22 minutes near the fire source and at 24-28 minutes little further from the fire source when fast sprinkler heads are used. The slow heads are activated between 26-32 minutes. (orig.)

  9. Improvement of flame resistance of non-flame retardant cables by applying fire protection measures

    International Nuclear Information System (INIS)

    Takemura, Yujiro; Segoshi, Yoshinori; Jinno, Susumu; Mii, Kazuki

    2017-01-01

    The new regulatory requirements, which were put in force after the Fukushima Daiichi accident, impose the use of flame retardant cables on the plant components having safety functions for the purpose of fire protection. However, some Japanese nuclear power plants built in the early days use non-flame retardant cables that do not pass the demonstration test to check for the flame resistance. To cope with the new regulatory requirements, a fire protection measure for non-flame retardant cables was introduced to assure flame resistance of non-flame retardant cables equivalent to or higher than that of flame retardant cables. To illustrate the fire protection measure, both non-flame retardant cables and its cable tray are covered with fire protection sheet fabricated from incombustible material to form an assembly. Considering the demonstration test results, it can be concluded that flame resistance performance of non-flame retardant cables equivalent to or higher than that of flame retardant cables can be assured by forming the assembly even if an external fire outside the assembly and internal cable fire inside the assembly are assumed. This paper introduces the design of the assembly consisting of a bundle of cables and a cable tray and summarizes the results of demonstration tests. (author)

  10. Calculation of temperature rise for cable conductor of DCS cabinet power based on theory of numerical thermal transfer

    International Nuclear Information System (INIS)

    Tian Yong; Zhang Longqiang; Yang Zhen; Yu Bin

    2014-01-01

    In order to ensure a long-term reliable operation of the DCS cabinet's 220 V AC power cable, it was needed to confirm whether the conductor temperature rise of power cable meet the requirement of the cable specification. Based on the actual data in site and the theory of numerical heat transfer, conservative model was established, and the conductor temperature was calculated. The calculation results show that the cable arrangement on the cable tray will not lead to the conductor temperature rise of power cable over than the required temperature in technical specification. (authors)

  11. CoFlo tray Design and Technology Report

    Energy Technology Data Exchange (ETDEWEB)

    William R. Trutna

    2005-04-04

    This report consists of two major segments. CoFlo Tray Design is the first section. The objectives of this section are: (1) Determine the design requirements for increased capacity by the substitution of CoFlo trays for sieve trays in a 15-tray 46-inch diameter column. The Design Basis was obtained from the Separations Research Program, which was solicited by an industrial customer on the use of CoFlo trays for their application. (2) Illustrate the design procedures so that they can be computerized to rapidly provide design and cost information for future customers. A summary of the research studies on which each design procedure is based is included. (3) Compare the costs of new sieve tray and CoFlo tray columns for this application to illustrate the savings inherent in the CoFlo process. Exhibits are the second section of this report and its objectives are to: (a) Report the extensive research studies on the CoFlo tray and related items; (b) Analyze present and potential future performance of the CoFlo tray; (c) Present comparative costs for sieve and CoFlo tray columns; and (d) List the applications for the CoFlo deentrainer.

  12. Cable handling

    International Nuclear Information System (INIS)

    1980-01-01

    In computerized axial tomography scanning, problems arise in exchanging electrical signals between fixed and rotating assemblies. A novel method of overcoming this problem is described in detail for both signal and high voltage cables. Apparatus using a sequence of drums and pulleys is used to maintain the interconnecting cables in a neat arrangement and free from mechanical strain. The apparatus is simple and relatively easy and inexpensive to assemble and maintain. (UK)

  13. Drying time of tray adhesive for adequate tensile bond strength between polyvinylsiloxane impression and tray resin material.

    Science.gov (United States)

    Yi, Myong-Hee; Shim, Joon-Sung; Lee, Keun-Woo; Chung, Moon-Kyu

    2009-07-01

    Use of custom tray and tray adhesive is clinically recommended for elastomeric impression material. However there is not clear mention of drying time of tray adhesive in achieving appropriate bonding strength of tray material and impression material. This study is to investigate an appropriate drying time of tray adhesives by evaluating tensile bonding strength between two types of polyvinylsiloxane impression materials and resin tray, according to various drying time intervals of tray adhesives, and with different manufacturing company combination of impression material and tray adhesive. Adhesives used in this study were Silfix (Dentsply Caulk, Milford, Del, USA) and VPS Tray Adhesive (3M ESPE, Seefeld, Germany) and impression materials were Aquasil Ultra (monophase regular set, Dentsply Caulk, Milford, Del, USA) and Imprint II Garant (regular body, 3M ESPE, Seefeld, Germany). They were used combinations from the same manufacture and exchanged combinations of the two. The drying time was designed to air dry, 5 minutes, 10 minutes, 15 minutes, 20 minutes, and 25 minutes. Total 240 of test specimens were prepared by auto-polymerizing tray material (Instant Tray Mix, Lang, Wheeling, Il, USA) with 10 specimens in each group. The specimens were placed in the Universal Testing machine (Instron, model 3366, Instron Corp, University avenue, Nowood, MA, USA) to perform the tensile test (cross head speed 5 mm/min). The statistically efficient drying time was evaluated through ANOVA and Scheffe test. All the tests were performed at 95% confidence level. The results revealed that at least 10 minutes is needed for Silfix-Aquasil, and 15 minutes for VPS Tray Adhesive-Imprint II, to attain an appropriate tensile bonding strength. VPS Tray Adhesive-Imprint II had a superior tensile bonding strength when compared to Silfix-Aquasil over 15 minutes. Silfix-Aquasil had a superior bonding strength to VPS Tray Adhesive-Aquasil, and VPS Tray Adhesive-Imprint II had a superior tensile

  14. Minimally Clinically Important Change in the Activity Measure for Post-Acute Care (AM-PAC), a Generic Patient-Reported Outcome Tool, in People With Low Back Pain.

    Science.gov (United States)

    Lee, Natalie; Thompson, Nicolas R; Passek, Sandra; Stilphen, Mary; Katzan, Irene L

    2017-11-01

    The Activity Measure for Post-Acute Care (AM-PAC) is a generic metric of patient-reported functional status. The minimal clinically important difference (MCID) in the AM-PAC score has not been determined. The study objective was to determine the MCID for AM-PAC in people with low back pain. This was a retrospective cohort study. Anchor-based and distribution-based methods were used to estimate the MCID. The Modified Low Back Pain Disability Questionnaire was used as the anchor. Adults who had a primary ICD-9 code for low back pain in at least 1 outpatient physical therapist visit during an episode of care and who completed both the AM-PAC and the Modified Low Back Pain Disability Questionnaire in at least 2 visits during the care episode were included. The MCID was calculated for the AM-PAC basic mobility version as well its adapted version, which the Cleveland Clinic uses for patients 65 years old or older. A total of 1,271 participants were eligible for study. For the AM-PAC basic mobility version, anchor-based methods yielded MCID estimates of between 3.4 and 5.1, whereas distribution-based methods yielded estimates of 1.7 to 4.2. The minimal detectable change (MDC) for the AM-PAC basic mobility version was 3.3. For the adapted AM-PAC basic mobility version, the MCID was estimated to be between 2.9 and 4.0 via anchor-based methods and between 1.2 to 3.5 via distribution-based methods. The MDC for the adapted AM-PAC basic mobility version was 3.5. The estimated MCID was designed for people with low back pain only. The MCID ranged from 3.3 to 5.1 for the AM-PAC basic mobility version and 3.5 to 4 for the adapted version, with the MDC as the lower limit. Changes in the AM-PAC for people with low back pain may be interpreted using the estimated MCID. Future studies are needed to determine the AM-PAC MCID for populations other than those with low back pain. © 2017 American Physical Therapy Association

  15. Adaptation of the Activity Measure Post-Acute Care (AM-PAC) from English to Mandarin using the dual-panel translation approach

    DEFF Research Database (Denmark)

    Chang, Feng-Hang; Liou, Tsan-Hon; Brodersen, John

    2017-01-01

    translated using the dual-panel method. The translated AM-PAC was tested in 550 Chinese-speaking rehabilitation outpatients. Floor and ceiling effects were evaluated and internal consistency was assessed using Cronbach's alpha. Spearman correlation was used to assess the concurrent validity of the AM...

  16. TrayGen: Arranging objects for exhibition and packaging

    KAUST Repository

    Yang, Yongliang

    2013-10-01

    We present a framework, called TrayGen, to generate tray designs for the exhibition and packaging of a collection of objects. Based on principles from shape perception and visual merchandising, we abstract a number of design guidelines on how to organize the objects on the tray for the exhibition of their individual features and mutual relationships. Our framework realizes these guidelines by analyzing geometric shapes of the objects and optimizing their arrangement. We demonstrate that the resultant tray designs not only save space, but also highlight the characteristic of each object and the inter-relations between objects. © 2013 The Eurographics Association and John Wiley & Sons Ltd.

  17. Cable Stability

    Energy Technology Data Exchange (ETDEWEB)

    Bottura, L [European Organization for Nuclear Research, Geneva (Switzerland)

    2014-07-01

    Superconductor stability is at the core of the design of any successful cable and magnet application. This chapter reviews the initial understanding of the stability mechanism, and reviews matters of importance for stability such as the nature and magnitude of the perturbation spectrum and the cooling mechanisms. Various stability strategies are studied, providing criteria that depend on the desired design and operating conditions.

  18. Experimental study of thermal field deriving from an underground electrical power cable buried in non-homogeneous soils

    International Nuclear Information System (INIS)

    Lieto Vollaro, Roberto de; Fontana, Lucia; Vallati, Andrea

    2014-01-01

    The electrical cables ampacity mainly depends on the cable system operation temperature. To achieve a better cable utilization and reduce the conservativeness typically employed in buried cable design, an accurate evaluation of the heat dissipation through the cables and the surrounding soil is important. In the traditional method adopted by the International Electrotechnical Commission (IEC) and the Institute of Electrical and Electronics Engineers (IEEE) for the computation of the thermal resistance between an existing underground cable system and the external environment, it is still assumed that the soil is homogeneous and has uniform thermal conductivity. Numerical studies have been conducted to predict the temperature distribution around the cable for various configurations and thermal properties of the soil. The paper presents an experimental study conducted on a scale model to investigate the heat transfer of a buried cable, with different geometrical configurations and thermal properties of the soil, and to validate a simplified model proposed by the authors in 2012 for the calculation of the thermal resistance between the underground pipe or electrical cable and the ground surface, in cases where the filling of the trench is filled with layers of materials with different thermal properties. Results show that experimental data are in good agreement with the numerical ones. -- Highlights: • Heat transfer of a buried cable has been experimentally studied on a scale model. • Different configurations and thermal properties of the soil have been tested. • Authors previously proposed a simplified model and obtained numerical results. • Experimental results and numerical ones previously obtained were in accordance

  19. Image Processing Techniques for Assessment of Dental Trays

    National Research Council Canada - National Science Library

    Yergin, E

    2001-01-01

    .... This technique was used for the alignment of six brands of perforated metal trays with 170 lower arch cast models collected from patients having Angle Class 1 type occlusion with minor malocclusions...

  20. Image Processing Techniques for Assessment of Dental Trays

    Science.gov (United States)

    2001-10-25

    170 patients having Angle Class I molar relationships with minor malocclusions and teeth including second molars fully erupted without loss of tooth...Abstract-A tray selected for the dental patient must adapt to the curvature of the teeth and allow the impression material to be in appropriate...brands of perforated metal trays with 170 lower arch cast models collected from patients having Angle Class 1 type occlusion with minor malocclusions

  1. Influence of Custom Trays, Dual-Arch Passive, Flexed Trays and Viscosities of Elastomeric Impression Materials on Working Dies

    Science.gov (United States)

    Kohli, Shivani; Kalsi, Rupali

    2016-01-01

    Introduction Dual arch impression technique signifies an essential improvement in fixed prosthodontics and has numerous benefits over conventional impression techniques. The accuracy of working dies fabricated from dual arch impression technique remains in question because there is little information available in the literature. Aim This study was conducted to compare the accuracy of working dies fabricated from impressions made from two different viscosities of impression materials using metal, plastic dual arch trays and custom made acrylic trays. Materials and Methods The study samples were grouped into two groups based on the viscosity of impression material used i.e. Group I (monophase), whereas Group II consisted of Dual Mix technique using a combination of light and heavy body material. These were further divided into three subgroups A, B and C depending on the type of impression tray used (metal dual arch tray, plastic dual arch tray and custom made tray). Measurements of the master cast were made using profile projector. Descriptive statistics like mean, Standard Deviation (SD) were calculated for all the groups. One way analysis of variance (ANOVA) was used for multiple group comparisons. A p-value of 0.05 or less was considered statistically significant. Results The gypsum dies obtained with the three types of impression trays using two groups of impression materials were smaller than the master models in dimensions. Conclusion The plastic dual arch trays produced dies which were the least accurate of the three groups. There was no significant difference in the die dimensions obtained using the two viscosities of impression materials. PMID:27437342

  2. CABLES MUSCULARES

    Directory of Open Access Journals (Sweden)

    Alejandro Gómez

    Full Text Available Los cables musculares o fibras de nitinol presentan una excelente alternativa a los actuadores convencionales, con una fuerza de actuación muy alta, equivalente a la de los actuadores hidráulicos, proporcionalmente a su peso, además de su acción silenciosa. Este material, inventado en 1963, aún no es muy conocido y de ahí que se haya realizado una recopilación de sus propiedades. Entre ellas, la temperatura de transición es la más importante, por ser la que activa la aleación. Muchos sistemas se han creado para alcanzar adecuadamente la temperatura de transición, y también se continúa en la investigación de métodos que ayuden a lograr un control preciso del movimiento de la aleación con memoria de forma (SMA.

  3. Applications of T-ray spectroscopy in the petroleum field

    Science.gov (United States)

    Al-Douseri, Fatemah M.

    2005-11-01

    Because of heavy usage of petroleum products, which are the main source of energy in daily life and industry, a fast, reliable, and portable analysis system is needed to complement traditional techniques. Terahertz (THz) radiation, or T-rays, is electromagnetic radiation in the 0.1 to 10 THz frequency range. One unique attribute of T-rays is their ability to sensitively measure the induced molecular dipole moments in non-polar liquids such as aromatics, which make up the majority of the contents of many petroleum products. This information can lead to several applications in petroleum analysis. The application of T-rays to petroleum product analysis has the potential to make a significant impact in the petroleum field. In this dissertation, I show the first use of T-ray time-domain spectroscopy and Fourier transform infrared (FTIR) spectroscopy techniques for petroleum product analysis. I report on the feasibility of analyzing selected petroleum products, including gasoline, diesel, lubricating oil, and selected compounds of toluene, ethylbenzene, and xylene (BTEX). With the use of a T-ray time-domain spectrometer. I demonstrate that gasolines with different octane numbers and diesel all show specific absorption coefficients and refractive indexes in the spectral range from 0.5 to 2.0 THz. Furthermore, I report the qualitative and quantitative analysis of selected BTEX components in gasoline and diesel using FTIR spectroscopy in the 50 to 650 cm-1 region. I distinguish gasolines with different octane numbers from diesel and lubricating oil according to their different spectral features. I also determine the concentration of (o, m, p) xylene isomers in gasoline according to their specific absorption bands. The experimental results in this thesis, imply that linking between the knowledge of petroleum products and the development of T-ray spectrometer with the cooperation of industry might translate the T-ray spectroscopic system into a real world application in

  4. Universal Cable Brackets

    Science.gov (United States)

    Vanvalkenburgh, C.

    1985-01-01

    Concept allows routing easily changed. No custom hardware required in concept. Instead, standard brackets cut to length and installed at selected locations along cable route. If cable route is changed, brackets simply moved to new locations. Concept for "universal" cable brackets make it easy to route electrical cable around and through virtually any structure.

  5. Cable line engineering

    International Nuclear Information System (INIS)

    Jang, Hak Sin; Kim, Sin Yeong

    1998-02-01

    This book is about cable line engineering. It is comprised of nine chapters, which deals with summary of cable communication such as way, process of cable communication and optical communication, Line constant of transmission on primary constant, reflection and crosstalk, communication cable line of types like flat cable, coaxial cable and loaded cable, Install of communication line with types and facility of aerial line, construction method of communication line facility, Measurement of communication line, Carrier communication of summary, PCM communication with Introduction, regeneration relay system sampling and quantization and Electric communication service and general information network with mobile communication technique and satellite communication system.

  6. Cultural and semantic equivalence of the activity measure post-acute care (AM-PAC) after its translation into Mandarin Chinese.

    Science.gov (United States)

    Chang, Feng-Hang; Ni, Pengsheng; Chiou, Hung-Yi; Hou, Wen-Hsuan; Jette, Alan M

    2018-03-21

    The purpose of this study was to investigate the cultural and semantic equivalence of the Activity Measure Post-Acute Care (AM-PAC) outpatient short forms after they were translated from American English to Mandarin Chinese. This study was conducted with a composite sample of a group of 483 American adults (mean age 63.1 years, 42.4% males) and 553 Taiwanese adults (mean age 60.6 years, 47.2% males) who were undergoing home care or outpatient rehabilitation services. A confirmatory factor analysis tested the cultural equivalence of the AM-PAC dimensions between the US and Taiwanese samples. Semantic equivalence was tested through an item response theory-based differential item functioning (DFI) analysis. Results of the confirmatory factor analysis demonstrated good model-data fit of the AM-PAC in both the US and Taiwanese samples. Significant DFI was found for six Basic Mobility items, two Daily Activity items, and four Applied Cognition items. A DFI-adjusted conversion table was generated to transform the raw scores of the measure for comparisons between the two countries. This study provides evidence to support the conceptual equivalence of the AM-PAC when used in rehabilitation patients between American and Taiwanese cultural contexts. Some DFI items between the two groups were found, suggesting that some differences in semantic understanding of these items between cultures require cross-cultural adjustments. Implications for Rehabilitation Cultural equivalence needs to be tested before applying a clinical measure to another context. The findings of this study supported the three activity domains that the Activity Measure Post-Acute Care measures: Basic Mobility, Daily Activity, and Applied Cognition, which are all important rehabilitation outcomes that need to be assessed and monitored across rehabilitation settings. Differential item functioning was observed between the English and Chinese versions of the Activity Measure Post-Acute Care, indicating that

  7. Test results for cables used in nuclear power plants by a new environmental testing method

    Energy Technology Data Exchange (ETDEWEB)

    Handa, Katsue; Fujimura, Shun-ichi; Hayashi, Toshiyasu; Takano, Keiji; Oya, Shingo

    1982-12-01

    In the nuclear power plants using PWRs or BWRs in Japan, environmental tests are provided, in which simulated LOCA conditions are considered so as to conform with Japanese conditions, and many cables which passed these tests are presently employed. Lately, the new environmental testing, in which a credible accident called MSLB (main steam line breakage) is taken into account, is investigated in PWR nuclear power plants, besides LOCA. This paper reports on the results of evaluating some PWR cables for this new environmental testing conditions. The several cables tested were selected out of PH cables (fire-retardant, ethylene propylene rubber insulated, chlorosulfonated polyethylene sheathed cables) as the cables for safety protecting circuits and to be used in containment vessels where the cables are to be exposed to severe environmental test conditions of 2 x 10/sup 8/ Rad ..gamma..-irradiation and simulated LOCA. All these cables have been accepted after the vertical tray burning test provided in the IEEE Standard 383. The new testing was carried out by sequentially applying thermal deterioration, ..gamma..-irradiation, and the exposure to steam (twice 300 s exposures to 190 deg C superheated steam). After completing each step, tensile strength, elongation, insulation resistance and breakdown voltage were measured, respectively. Every cable tested showed satisfactory breakdown voltage after the exposure to steam, thus it was decided to be acceptable. In future, it is required to investigate the influence of the rate of temperature rise on the cable to be tested in MSLB simulation.

  8. Test results for cables used in nuclear power plants by a new environmental testing method

    International Nuclear Information System (INIS)

    Handa, Katsue; Fujimura, Shun-ichi; Hayashi, Toshiyasu; Takano, Keiji; Oya, Shingo

    1982-01-01

    In the nuclear power plants using PWRs or BWRs in Japan, environmental tests are provided, in which simulated LOCA conditions are considered so as to conform with Japanese conditions, and many cables which passed these tests are presently employed. Lately, the new environmental testing, in which a credible accident called MSLB (main steam line breakage) is taken into account, is investigated in PWR nuclear power plants, besides LOCA. This paper reports on the results of evaluating some PWR cables for this new environmental testing conditions. The several cables tested were selected out of PH cables (fire-retardant, ethylene propylene rubber insulated, chlorosulfonated polyethylene sheathed cables) as the cables for safety protecting circuits and to be used in containment vessels where the cables are to be exposed to severe environmental test conditions of 2 x 10 8 Rad γ-irradiation and simulated LOCA. All these cables have been accepted after the vertical tray burning test provided in the IEEE Standard 383. The new testing was carried out by sequentially applying thermal deterioration, γ-irradiation, and the exposure to steam (twice 300 s exposures to 190 deg C superheated steam). After completing each step, tensile strength, elongation, insulation resistance and breakdown voltage were measured, respectively. Every cable tested showed satisfactory breakdown voltage after the exposure to steam, thus it was decided to be acceptable. In future, it is required to investigate the influence of the rate of temperature rise on the cable to be tested in MSLB simulation. (Wakatsuki, Y.)

  9. Continuous operation of NPP Kori Unit 1 - Fireproof paint for cables

    International Nuclear Information System (INIS)

    Wendt, Dipl-Ing. Ruediger; Kim, Duill; Sik, Cho Hong

    2008-01-01

    Fireproof cable coating materials have been used in European NPP, especially in Germany, Russia, Ukraine, Czech Republic, Lithuania, Switzerland. Wide experiences were made during operation while applying these systems. In NPP Kori, Unit 1, a fire proof cable coating project was realised for the first time in a NPP of KHNP. The scope of services of the cable trays to coat amounts to 15,587m 2 . In different fire compartments and rooms the cables should be coated partially respectively completely with the fire proof cable coating system. The extent of cable surfaces to coat was stipulated by KHNP on the basis of an analysis made by KHNP. The project was tendered on the basis of a technical specification of KHNP. The specification is mainly predicted on Korean and US standards. The most important criteria for the fire proof cable coating is resumed as follows: The fireproof cable coating has to assure the fire protection of the cables for a period defined and for operational conditions defined in such a manner that the general conditions for the operation of the cable installation will not be affected

  10. Development of non-halogen cables for nuclear power stations

    Energy Technology Data Exchange (ETDEWEB)

    Yagyu, Hideki; Yamamoto, Yasuaki; Onishi, Takao (Hitachi Cable, Ltd., Tokyo (Japan))

    1983-12-01

    The non-halogen fire-resistant cables for nuclear power stations which never generate halogen gas, have been developed. The cables comprise the insulator of EP rubber and the sheath of polyolefine containing non-halogen inorganic fire-retardant. The results of the environmental test and fire-resistance test are described. In the environmental test, the cables were subjected to the heating, gamma-irradiation and steam exposure successively, according to IEEE specification 323,383, and subsequently the change in the appearance, tensile strength and electrical performance of the cables was measured. In the fire-resistance test, the vertical tray fire test according to the IEEE specification 383 was adopted, and other tests including the vertical fire test on insulator cores, oxygen index, the generation of corrosive gas, copper mirror corrosion test, gas toxicity test and optical smoke density test were carried out. It became clear that the cables did not generate halogen gas on burning, and brought about reduced toxicity, corrosion and smoke, and that the safety against fire is greatly improved by using the cables.

  11. Development of non-halogen cables for nuclear power stations

    International Nuclear Information System (INIS)

    Yagyu, Hideki; Yamamoto, Yasuaki; Onishi, Takao

    1983-01-01

    The non-halogen fire-resistant cables for nuclear power stations which never generate halogen gas, have been developed. The cables comprise the insulator of EP rubber and the sheath of polyolefine containing non-halogen inorganic fire-retardant. The results of the environmental test and fire-resistance test are described. In the environmental test, the cables were subjected to the heating, gamma-irradiation and steam exposure successively, according to IEEE specification 323,383, and subsequently the change in the appearance, tensile strength and electrical performance of the cables was measured. In the fire-resistance test, the vertical tray fire test according to the IEEE specification 383 was adopted, and other tests including the vertical fire test on insulator cores, oxygen index, the generation of corrosive gas, copper mirror corrosion test, gas toxicity test and optical smoke density test were carried out. It became clear that the cables did not generate halogen gas on burning, and brought about reduced toxicity, corrosion and smoke, and that the safety against fire is greatly improved by using the cables. (Yoshitake, I.)

  12. Herbal dryer: drying of ginger (zingiber officinale) using tray dryer

    Science.gov (United States)

    Haryanto, B.; Hasibuan, R.; Alexander; Ashari, M.; Ridha, M.

    2018-02-01

    Drying is widely used as a method to preserve food because of its convenience and affordability. Drying of ginger using tray dryer were carried out at various drying conditions, such as air-drying flow, air-drying temperature, and sample dimensions, to achieve the highest drying rate. Samples with various dimensions were placed in the tray dryer and dried using various air-drying flow and temperatures. The weights of samples were observed every 3 minutes interval. Drying was stopped after three times of constant weighing. Data of drying was collected to make the drying curves. Drying curves show that the highest drying rate is achieved using highest air flow and temperature.

  13. Challenges to validation of a complex nonsterile medical device tray.

    Science.gov (United States)

    Prince, Daniel; Mastej, Jozef; Hoverman, Isabel; Chatterjee, Raja; Easton, Diana; Behzad, Daniela

    2014-01-01

    Validation by steam sterilization of reusable medical devices requires careful attention to many parameters that directly influence whether or not complete sterilization occurs. Complex implant/instrument tray systems have a variety of configurations and components. Geobacillus stearothermophilus biological indicators (BIs) are used in overkill cycles to to simulate worst case conditions and are intended to provide substantial sterilization assurance. Survival of G. stearothermophilus spores was linked to steam access and size of load in the chamber. By a small and reproducible margin, it was determined that placement of the trays in a rigid container into minimally loaded chambers were more difficult to completely sterilize than maximally loaded chambers.

  14. Superconducting ac cable

    Science.gov (United States)

    Schmidt, F.

    1980-11-01

    The components of a superconducting 110 kV ac cable for power ratings or = 2000 MVA were developed. The cable design is of the semiflexible type, with a rigid cryogenic envelope containing a flexible hollow coaxial cable core. The cable core consists of spirally wound Nb-A1 composite wires electrically insulated by high pressure polyethylene tape wrappings. A 35 m long single phase test cable with full load terminals rated at 110 kV and 10 kA was constructed and successfully tested. The results obtained prove the technical feasibility and capability of this cable design.

  15. Superconducting ac cable

    International Nuclear Information System (INIS)

    Schmidt, F.

    1980-01-01

    The components of a superconducting 110 kV ac cable for power ratings >= 2000 MVA have been developed. The cable design especially considered was of the semiflexible type, with a rigid cryogenic envelope and flexible hollow coaxial cable cores pulled into the former. The cable core consists of spirally wound Nb-Al composite wires and a HDPE-tape wrapped electrical insulation. A 35 m long single phase test cable with full load terminations for 110 kV and 10 kA was constructed and successfully tested. The results obtained prove the technical feasibility and capability of our cable design. (orig.) [de

  16. Simulators of tray distillation columns as tools for interpreting ...

    African Journals Online (AJOL)

    ... at 0.05 m intervals were determined from top to the bottom of simulators of tray distillation columns exposed to 20 mCi of 137 Cs. Signals generated from the simulators were identical with the experimental signals obtained from the Stabilizer Column of the crude oil distillation unit at the Tema Oil Refinery Ghana Limited.

  17. Journal of EEA, Vol. 30, 2013 SIEVE TRAY EFFICIENCY USING ...

    African Journals Online (AJOL)

    dell

    Journal of EEA, Vol. 30, 2013. SIEVE TRAY EFFICIENCY USING CFD MODELING AND SIMULATION ... ABSTRACT. In this work, computational fluid dynamics (CFD) .... per unit volume, MG is the molecular weight of the gas/vapor, kL and kG ...

  18. Bactericidal paper trays doped with silver nanoparticles for egg ...

    Indian Academy of Sciences (India)

    the AgNPs-deposited paper egg trays improved the shelf-life of the eggs by more than 14 days ... In this work, we developed a new method to prepare anti- ... on an electronic balance (Sartorius). ..... significant changes with respect to physical quality param- ... Due to possible human health effects from silver exposure,.

  19. Transmission Line Ampacity Improvements of AltaLink Wind Plant Overhead Tie-Lines Using Weather-Based Dynamic Line Rating

    Energy Technology Data Exchange (ETDEWEB)

    Bhattarai, Bishnu P.; Gentle, Jake P.; Hill, Porter; McJunkin, Tim; Myers, Kurt S.; Abbound, Alex; Renwick, Rodger; Hengst, David

    2017-07-01

    Abstract—Overhead transmission lines (TLs) are conventionally given seasonal ratings based on conservative environmental assumptions. Such an approach often results in underutilization of the line ampacity as the worst conditions prevail only for a short period over a year/season. We presents dynamic line rating (DLR) as an enabling smart grid technology that adaptively computes ratings of TLs based on local weather conditions to utilize additional headroom of existing lines. In particular, general line ampacity state solver utilizes measured weather data for computing the real-time thermal rating of the TLs. The performance of the presented method is demonstrated from a field study of DLR technology implementation on four TL segments at AltaLink, Canada. The performance is evaluated and quantified by comparing the existing static and proposed dynamic line ratings, and the potential benefits of DLR for enhanced transmission assets utilization. For the given line segments, the proposed DLR results in real-time ratings above the seasonal static ratings for most of the time; up to 95.1% of the time, with a mean increase of 72% over static rating.

  20. Energy cable engineering. Energiekabeltechnik

    Energy Technology Data Exchange (ETDEWEB)

    Luecking, H W

    1981-01-01

    This textbook intends to explain cable elements and common cable constructions according to VDE, and in a second part, to review the theoretical fundamentals and their consequences with a view to the construction of cables for higher voltages and powers. It will give the student a picture of the variety of problems and solutions which make cable engineering so interesting and show the practising engineer how to derive a theoretical system from their extensive everyday experience.

  1. Cable Supported Bridges

    DEFF Research Database (Denmark)

    Gimsing, Niels Jørgen

    Cable supported bridges in the form of suspension bridges and cable-stayed bridges are distinguished by their ability to overcome large spans.The book concentrates on the synthesis of cable supported bridges, covering both design and construction aspects. The analytical part covers simple methods...... to quantify the different structural configurations and allows a preliminary optimization of the main structure.Included are the most recent advances in structural design, corrosion protection of cables, aerodynamic safety, and erection procedures....

  2. Cable Television: Franchising Considerations.

    Science.gov (United States)

    Baer, Walter S.; And Others

    This volume is a comprehensive reference guide to cable television technology and issues of planning, franchising, and regulating a cable system. It is intended for local government officials and citizens concerned with the development of cable television systems in their communities, as well as for college and university classes in…

  3. Colleges and Cable Franchising.

    Science.gov (United States)

    Glenn, Neal D.

    After noting issues of audience appeal and financial and philosophical support for educational broadcasting, this paper urges community colleges to play an active role in the process of cable franchising. The paper first describes a cable franchise as a contract between a government unit and the cable television (CATV) company which specifies what…

  4. Cable strengthened arches

    NARCIS (Netherlands)

    Kamerling, M.W.

    2013-01-01

    The structural efficiency of arches, subjected to several variable loads, can be increased by strengthening these arches with cables. For these structures it can be necessary, especially in case the permanent load is small, to post-tension the cables to avoid any compression acting on the cables. A

  5. DC Cable for Railway

    Science.gov (United States)

    Tomita, Masaru

    The development of a superconducting cable for railways has commenced, assuming that a DC transmission cable will be used for electric trains. The cable has been fabricated based on the results of current testing of a superconducting wire, and various evaluation tests have been performed to determine the characteristics of the cable. A superconducting transmission cable having zero electrical resistance and suitable for railway use is expected to enhance regeneration efficiency, reduce power losses, achieve load leveling and integration of sub-stations, and reduce rail potential.

  6. Development of Integrated Assessment System for Underground Power Cable Performance: A Case Study

    Science.gov (United States)

    Turan, Faiz Mohd; Johan, Kartina; Soliha Sahimi, Nur; Nor, Nik Hisyamudin Muhd

    2017-08-01

    The basic operation of any electrical machines that is catered to serve needs of civilization involves electrical power which is the main source to trigger the internal mechanism in the machines then transfer the power to other form of energy such as mechanical, light, sound and etc. The supplies of electrical does not happen just by providing the source itself, it has load carrying agent which in many cases, user would refer to it as cable. Specifically, it is the power cable which its ampacity depends significantly on the operation temperature and load stress on it. Apart from having to focus on providing improvement on improving efficiency on the source itself, power cable plays and important role because without it, current ranging from low to high could not be transmitted and hence a failure of the power system generally. Studies have conducted to discuss whether which factor contributes relatively more to the causes of power cable failure or breakdown. Such factors can be narrowed down to the three major causes which are over temperature, over voltage and stress caused by over current. Over current is one of the factor which is depends on the usage of the power system itself. The higher the usage of the power system, higher the chances of over current to take place. This will then produce load stress on the cable which eventually destroy the insulator of the cable and slowly reach the core of the cable. It is believed that an assessment method should be implemented in order to predict the performance and failure rate of the power cable and use this prediction as reference rather than just letting power failure to happen anytime unpredictable which cause huge inconvenience to users and industries. Not only do a method should be implemented, it should be as easy to be used and understood by large range of users and integrated by a graphical user interface to be used. Therefore, this research will further narrow down on the approaches to do so and the location

  7. Apparatus for feeding nuclear fuel pellets to a loading tray

    International Nuclear Information System (INIS)

    Huggins, T.B.

    1979-01-01

    Apparatus for feeding nuclear fuel pellets at a uniform predetermined rate between pellet centering and grinding apparatus and a tray for loading pellets into nuclear fuel rod. Pellets discharged from the grinding apparatus are conveyed by a belt to a drive wheel forcing the pellets in engagement with the belt. The pellets under the drive wheel are capable of pushing a line of about 36 pellets onto a pellet dumping mechanism. As the dumping mechanism is actuated to dump the pellets on to a loading tray, the pellets moving toward the mechanism are stopped and the drive wheel is simultaneously lifted off the pellets until the pellet dumping process is completed. (U.K.)

  8. T-ray relevant frequencies for osteosarcoma classification

    Science.gov (United States)

    Withayachumnankul, W.; Ferguson, B.; Rainsford, T.; Findlay, D.; Mickan, S. P.; Abbott, D.

    2006-01-01

    We investigate the classification of the T-ray response of normal human bone cells and human osteosarcoma cells, grown in culture. Given the magnitude and phase responses within a reliable spectral range as features for input vectors, a trained support vector machine can correctly classify the two cell types to some extent. Performance of the support vector machine is deteriorated by the curse of dimensionality, resulting from the comparatively large number of features in the input vectors. Feature subset selection methods are used to select only an optimal number of relevant features for inputs. As a result, an improvement in generalization performance is attainable, and the selected frequencies can be used for further describing different mechanisms of the cells, responding to T-rays. We demonstrate a consistent classification accuracy of 89.6%, while the only one fifth of the original features are retained in the data set.

  9. Design and Production of Damage-Resistant Tray Pack Containers

    Science.gov (United States)

    1985-07-01

    No COMMENT ,34.5 ýX .7.. . , . 35.0 x 36.0 x " 36.5 x • - . ,- 37.0 x 37.5 X 22 Ma after failure .4 J L,. Local Red stain...VACUUM-TRAY PACK SAMPLE 90#-BASELINE !4 TEST LEVEL PANEL VACUUM YES NO COMMENT 𔃾 I S2"X - 3" X 4ŕ x 4.5" X 27 Ma with Red spot @ S1 - wrinkle. * i...44 i 63 DATE 8-29-84 * SAMPLE # 3 TEST TYPE VACUUM-TRAY PACK SAMPLE 90#/0.050" REINFORCED TEST LEVEL PAN] VACUUM YES NO COMMENT i ", 2" X 2 1 V - I

  10. Training to Increase Safe Tray Carrying Among Cocktail Servers

    OpenAIRE

    Scherrer, Megan D; Wilder, David A

    2008-01-01

    We evaluated the effects of training on proper carrying techniques among 3 cocktail servers to increase safe tray carrying on the job and reduce participants' risk of developing musculoskeletal disorders. As participants delivered drinks to their tables, their finger, arm, and neck positions were observed and recorded. Each participant received individual safety training that focused on proper carrying positions and techniques after baseline data were collected. A multiple baseline design acr...

  11. Cable aging tests

    International Nuclear Information System (INIS)

    Hubbard, G.

    1993-01-01

    This paper describes the results from aging, condition monitoring, and loss-of-coolant accident (LOCA) testing of class 1E electrical cables, per NUREG/CR-5772. This test was designed to test the performance of cables which had been aged with simultaneous radiation and thermal exposure. The tested cables included crosslinked polyolefin cables, ethylene propylene rubber cables, and miscellaneous cable types. Cables were exposed to 20, 40, and 60 years equivalent aging, and then exposed to LOCA tests at the end of their qualified life to determine the minimum insulation thickness needed for survival of the test. Failures were found in a large number of the tested cables. As a result the NRC has sent information notices to the industry regarding potential insulation problems. The results have raised the question of whether the artificial aging methods provide adequate testing methods. As a result of this testing the NRC is reviewing the artificial aging procedures, the adequacy of environmental qualification requirements for cable safety, and reexamining data from condition monitoring of installed cables

  12. Tropical field performance of dual-pass PV tray dryer

    Science.gov (United States)

    Iskandar, A. Noor; Ya'acob, M. E.; Anuar, M. S.

    2017-09-01

    Solar Photovoltaic technology has become the preferable solution in many countries around the globe to solve the ever increasing energy demand of the consumers. In line with the consumer need, food processing technology has huge potentials of integration with the renewable energy resources especially in drying process which consumes the highest electricity loads. Traditionally, the solar dryer technology was applied in agriculture and food industries utilizing the sun's energy for drying process, but this is highly dependable on the weather condition and surrounding factors. This work shares some field performance of the new design of portable dual-pass PV tray dryer for drying crops in an enclosed system. The dual-pass PV tray dryer encompass a lightweight aluminium box structure with dimensions of 1.1m (L) x 0.6m (W) x 0.2m (H) and can hold a load capacity of 300g - 3kg of crop depending on the types of the crops. Experiments of field performance monitoring were conducted in October -November 2016 which justifies a considerable reduction in time and crops quality improvement when using the dual-pass PV tray dryer as compared to direct-sun drying.

  13. Effects of surface tension on tray point efficiencies

    Energy Technology Data Exchange (ETDEWEB)

    Chen, G.X.; Afacan, A.; Chuang, K.T. (Alberta Univ., Edmonton, AB (Canada))

    1994-08-01

    Sieve tray efficiencies for the distillation of methanol/water, acetic acid/water, and cyclohexane/n-heptane mixtures were measured as a function of composition under fixed vapor and liquid rates in a 0.15 m diameter distillation column. The three binary distillation systems used in the study had a wide range of surface tensions measured as a function of composition. From the efficiencies measured, the number of vapor- and liquid-phase transfer units (Ng and Nl) was determined and the effects of surface tension on Ng and Nl were identified. To further verify the results obtained from the distillation column, bubble sizes in froths for air/water, air/methanol, and air/(water + surfactant) systems with different surface tensions were measured. The results show that surface tension has a significant effect on tray efficiency and the number of transfer units. Bubble sizes in the tray froths were mainly determined by surface tension, and bubble breakup and coalescence occur in the froths. 45 refs., 15 figs., 1 tab.

  14. Sizewell 'B' cable installation

    International Nuclear Information System (INIS)

    Gemmell, D.R.

    1992-01-01

    N G Bailey and Co. Ltd., UK were awarded the contract for the procurement, manufacture, works testing, works finishing, supply, delivery, off-loading, storage, installation, site finishing, preservation, setting to work and site testing of the following; the main cable installation throughout the Station including the addition of the Radioactive Waste Building, earthing and lightning protection installation, cable supporting steelwork and carriers and glanding and termination of cables. The cabling installation comprises power distribution, control and instrumentation cabling including all the associated cabling accessories, terminal boxes and similar components. The way that the contract was set-up, awarded and is now being carried out is described. Planning and industrial relations have been key features of the contract. (Author)

  15. Accuracy of implant transfer with open-tray and closed-tray impression techniques and surface detail reproduction of the tooth during impression

    Directory of Open Access Journals (Sweden)

    Hakimeh Siadat

    2012-01-01

    Full Text Available Background and Aims: Accurate recording of implant location is required to achieve passive fit and have the implants without stress concentration. The aim of this in-vitro study was to evaluate the dimensional and angular accuracy of open-tray and closed-tray impression techniques using polyether impression material and also to assess the surface detail reproduction of the tooth while impression making.Materials and Methods: One reference metal model with 2 implants (Implantium on the position of the maxillary second premolar and first molar and one molar tooth for evaluation of surface details was prepared. 27 polyether impressions of these models were made (9 using open-tray, 9 using closed-tray techniques and 9 were made just of the surface of the teeth without any implants. Impressions were poured with ADA type IV stone. Coordinate Measuring Machine was used for measuring the dimensional accuracy and video measuring machine for surface detail reproduction. All of these measurements were compared with the measurements on the reference model. Data were analyzed by and compared by T-test and One-way ANOVA.Results: There was a significant statistical difference between open-tray and closed-tray techniques (P0.05.Conclusion: The accuracy of open-tray impression technique was more than closed-tray technique. The surface detail reproduction of the tooth was not affected by impression technique.

  16. Cable support arrangements

    International Nuclear Information System (INIS)

    Pendleton, E.; Murray, A.

    1983-01-01

    A cable support arrangement extending from a refuelling level floor of a nuclear reactor to the inner shield of a double rotatable shield comprises a linearly extensible cable support and disciplining boom, reaching from the floor to the main shield, and a circumferentially extensible cable support and disciplining means running from the end of the boom to a fixed end on the inner shield. (author)

  17. High voltage dc cables

    Energy Technology Data Exchange (ETDEWEB)

    Bjustrom, B

    1965-12-01

    How stress distribution in dc cables varies with temperature and stress level, influence of polarity reversals and space charges, and different types of overvoltage to which dc cable may be subjected are discussed. Design problems, especially as related to corrosion protection and to mechanical stress caused by wire armoring during manufacturing and laying, accessories and work done on test methods, and the possibility of designing 400 to 600 kV dc cables for transmitting 2000 to 4000 MW are described.

  18. Electrical power cable engineering

    CERN Document Server

    Thue, William A

    2011-01-01

    Fully updated, Electrical Power Cable Engineering, Third Edition again concentrates on the remarkably complex design, application, and preparation methods required to terminate and splice cables. This latest addition to the CRC Press Power Engineering series covers cutting-edge methods for design, manufacture, installation, operation, and maintenance of reliable power cable systems. It is based largely on feedback from experienced university lecturers who have taught courses on these very concepts.The book emphasizes methods to optimize vital design and installation of power cables used in the

  19. COPPER CABLE RECYCLING TECHNOLOGY

    International Nuclear Information System (INIS)

    Chelsea Hubbard

    2001-01-01

    The United States Department of Energy (DOE) continually seeks safer and more cost-effective technologies for use in deactivation and decommissioning (D and D) of nuclear facilities. The Deactivation and Decommissioning Focus Area (DDFA) of the DOE's Office of Science and Technology (OST) sponsors large-scale demonstration and deployment projects (LSDDPs). At these LSDDPs, developers and vendors of improved or innovative technologies showcase products that are potentially beneficial to the DOE's projects and to others in the D and D community. Benefits sought include decreased health and safety risks to personnel and the environment, increased productivity, and decreased costs of operation. The Idaho National Engineering and Environmental Laboratory (INEEL) generated a list of statements defining specific needs and problems where improved technology could be incorporated into ongoing D and D tasks. One such need is to reduce the volume of waste copper wire and cable generated by D and D. Deactivation and decommissioning activities of nuclear facilities generates hundreds of tons of contaminated copper cable, which are sent to radioactive waste disposal sites. The Copper Cable Recycling Technology separates the clean copper from contaminated insulation and dust materials in these cables. The recovered copper can then be reclaimed and, more importantly, landfill disposal volumes can be reduced. The existing baseline technology for disposing radioactively contaminated cables is to package the cables in wooden storage boxes and dispose of the cables in radioactive waste disposal sites. The Copper Cable Recycling Technology is applicable to facility decommissioning projects at many Department of Energy (DOE) nuclear facilities and commercial nuclear power plants undergoing decommissioning activities. The INEEL Copper Cable Recycling Technology Demonstration investigated the effectiveness and efficiency to recycle 13.5 tons of copper cable. To determine the effectiveness

  20. Cable Diagnostic Focused Initiative

    Energy Technology Data Exchange (ETDEWEB)

    Hartlein, R.A.; Hampton, R.N.

    2010-12-30

    This report summarizes an extensive effort made to understand how to effectively use the various diagnostic technologies to establish the condition of medium voltage underground cable circuits. These circuits make up an extensive portion of the electric delivery infrastructure in the United States. Much of this infrastructure is old and experiencing unacceptable failure rates. By deploying efficient diagnostic testing programs, electric utilities can replace or repair circuits that are about to fail, providing an optimal approach to improving electric system reliability. This is an intrinsically complex topic. Underground cable systems are not homogeneous. Cable circuits often contain multiple branches with different cable designs and a range of insulation materials. In addition, each insulation material ages differently as a function of time, temperature and operating environment. To complicate matters further, there are a wide variety of diagnostic technologies available for assessing the condition of cable circuits with a diversity of claims about the effectiveness of each approach. As a result, the benefits of deploying cable diagnostic testing programs have been difficult to establish, leading many utilities to avoid the their use altogether. This project was designed to help address these issues. The information provided is the result of a collaborative effort between Georgia Tech NEETRAC staff, Georgia Tech academic faculty, electric utility industry participants, as well as cable system diagnostic testing service providers and test equipment providers. Report topics include: •How cable systems age and fail, •The various technologies available for detecting potential failure sites, •The advantages and disadvantages of different diagnostic technologies, •Different approaches for utilities to employ cable system diagnostics. The primary deliverables of this project are this report, a Cable Diagnostic Handbook (a subset of this report) and an online

  1. Automated Cable Preparation for Robotized Stator Cable Winding

    Directory of Open Access Journals (Sweden)

    Erik Hultman

    2017-04-01

    Full Text Available A method for robotized cable winding of the Uppsala University Wave Energy Converter generator stator has previously been presented and validated. The purpose of this study is to present and validate further developments to the method: automated stand-alone equipment for the preparation of the winding cables. The cable preparation consists of three parts: feeding the cable from a drum, forming the cable end and cutting the cable. Forming and cutting the cable was previously done manually and only small cable drums could be handled. Therefore the robot cell needed to be stopped frequently. The new equipment was tested in an experimental robot stator cable winding setup. Through the experiments, the equipment was validated to be able to perform fully automated and robust cable preparation. Suggestions are also given on how to further develop the equipment with regards to performance, robustness and quality. Hence, this work represents another important step towards demonstrating completely automated robotized stator cable winding.

  2. Idealized flow patterns and transit times in gas/liquid contacting trays with multiple box downcomers

    International Nuclear Information System (INIS)

    D'Arcy, D.

    1977-08-01

    Trays with multiple box downcomers are often used in chemical process plants nowadays. In order to make a theoretical assessment of the mass transfer efficiency of such trays, knowledge is needed of the time spent by the liquid at various parts of the tray. An idealized but reasonable flow pattern has been assumed and the local velocities and transit times along ten equally-spaced stream lines have been computed. Numerical and graphical results are presented. (author)

  3. Cable aging management

    International Nuclear Information System (INIS)

    Anandkumaran, A.; Sedding, H.

    2012-01-01

    Worldwide, due to the age of the majority of nuclear generating stations significant attention is being paid to the condition of the major components, e.g., reactor, steam generator, turbine generator, transformer, etc., with respect to relicensing and life extension. However, there is recognition that cable systems are critical to the safe, reliable and economic operation of nuclear power plants. Consequently, there is great interest in ageing management of low and medium voltage cables in the nuclear environment. Successful implementation of such programs requires an understanding of how the materials associated with cables and their accessories behave under normal operating and accident conditions. However, there is also a great need to determine the actual condition of the materials and systems in order to make rational decisions on whether or not to replace cables to ensure long term assurance of reliable operation. This proposed contribution describes an approach to cable ageing management of low and medium voltage cables based on measurements of material and electrical properties obtained in the laboratory and in the field. The effectiveness of various chemical, mechanical and electrical test methods are discussed in the context of, • Cable configuration, i.e., low or medium voltage, shielded or unshielded • Material type, i.e., PVC, XLPE, EPR, etc., • Ageing stress, i.e., electrical, thermal, radiation, thermal plus radiation, etc. These factors are key to identifying the most appropriate test method (or methods) to enable understanding of the current condition of the cable. While electrical test methods, e.g., ac withstand testing, partial discharge and various dielectric loss measurement techniques have been found effective for medium voltage cables, they are of very limited use on low voltage cables that constitute the majority of cables in nuclear power plants. This limited effectiveness is due to the lack of a well defined ground plane that is a

  4. Normative data for distal line bisection and baking tray task.

    Science.gov (United States)

    Facchin, Alessio; Beschin, Nicoletta; Pisano, Alessia; Reverberi, Cristina

    2016-09-01

    Line bisection is one of the tests used to diagnose unilateral spatial neglect (USN). Despite its wide application, no procedure or norms were available for the distal variant when the task was performed at distance with a laser pointer. Furthermore, the baking tray task was an ecological test aimed at diagnosing USN in a more natural context. The aim of this study was to collect normative values for these two tests in an Italian population. We recruited a sample of 191 healthy subjects with ages ranging from 20 to 89 years. They performed line bisection with a laser pointer on three different line lengths (1, 1.5, and 2 m) at a distance of 3 m. After this task, the subjects performed the baking tray task and a second repetition of line bisection to test the reliability of measurement. Multiple regression analysis revealed no significant effects of demographic variables on the performance of both tests. Normative cut-off values for the two tests were developed using non-parametric tolerance intervals. The results formed the basis for clinical use of these two tools for assessing lateralized performance of patients with brain injury and for diagnosing USN.

  5. Proposed superscreened cables and connectors

    International Nuclear Information System (INIS)

    Fowler, E.P.

    1975-11-01

    The paper summarises the present availability of superscreened cables and proposes the specification of a family of cables to meet the foreseeable needs of the nuclear power industry. The cable numbering system is described, special tests outlined and important details given for the chosen cables. Appropriate connectors are also discussed and listed with an outline of their required screening performance. (author)

  6. Costly cables; Lange Leitung

    Energy Technology Data Exchange (ETDEWEB)

    Hautmann, Daniel

    2012-08-15

    Connection of offshore wind turbines to the onshore power supply grid requires costly cables for HV DC power transmission. The technology is mature enough to enable low-loss power transmission, but construction times may last several years.

  7. Cable Aerodynamic Control

    DEFF Research Database (Denmark)

    Kleissl, Kenneth

    to a categorization of the different control technics together with an identification of two key mechanisms for reduction of the design drag force. During this project extensive experimental work examining the aerodynamics of the currently used cable surface modifications together with new innovative proposals have...... been conducted. The two current prevailing systems consisting of helically filleted cables and cables with a pattern-indented surface were directly compared under the same conditions and both applications were found with attractive properties. The pattern-indented surface maintained a low supercritical...... of reducing the intensity of the axial flow and disrupting the near wake flow structures. Similar studies during wet conditions with artificial simulation of light rain in the wind tunnel showed that the plain cable suffered from severe rain-wind induced vibrations. But despite the presence of both upper...

  8. In Vitro Comparative Evaluation of Different Types of Impression Trays and Impression Materials on the Accuracy of Open Tray Implant Impressions: A Pilot Study

    Directory of Open Access Journals (Sweden)

    Sonam Gupta

    2017-01-01

    Full Text Available Purpose. For a precise fit of multiple implant framework, having an accurate definitive cast is imperative. The present study evaluated dimensional accuracy of master casts obtained using different impression trays and materials with open tray impression technique. Materials and Methods. A machined aluminum reference model with four parallel implant analogues was fabricated. Forty implant level impressions were made. Eight groups (n=5 were tested using impression materials (polyether and vinylsiloxanether and four types of impression trays, two being custom (self-cure acrylic and light cure acrylic and two being stock (plastic and metal. The interimplant distances were measured on master casts using a coordinate measuring machine. The collected data was compared with a standard reference model and was statistically analyzed using two-way ANOVA. Results. Statistically significant difference (p0.05 was observed between varied stock and custom trays. Conclusions. The polyether impression material proved to be more accurate than vinylsiloxanether impression material. The rigid nonperforated stock trays, both plastic and metal, could be an alternative for custom trays for multi-implant impressions when used with medium viscosity impression materials.

  9. Integrated CFD investigation of heat transfer enhancement using multi-tray core catcher in SFR

    International Nuclear Information System (INIS)

    Rakhi; Sharma, Anil Kumar; Velusamy, K.

    2017-01-01

    Highlights: • Heat transfer enhancement using multi-tray core catcher for SFR is investigated. • The capability of a single core collector tray is estimated. • Double and triple collector trays with innovative designs is discussed. • Provision of openings in the trays contributed to enhanced natural circulation. - Abstract: To render future SFR more robust and safe, certain BDBE have been considered in the recent years. A Core Disruptive Accident leading to a whole core meltdown scenario has gained the interest of researchers. Various design concepts and safety measures have been suggested and incorporated in design to address such a low probability scenario. A core catcher concept, in particular, has proved to be inevitable as an in-vessel core retention device in SFR for safe retention of core debris arising out after the severe accident. This study aims to analyse the cooling capability of the innovative design concept of core catcher to remove decay heat of degraded core after the accident. First, the capability of single collection tray is established and then the study is extended to two and three collection trays with different design concepts. Transient forms of governing equations of mass, momentum and energy conservations along with k-ε turbulence model are solved by finite volume based CFD solver. Boussinesq approximation is invoked to model buoyancy in sodium. The study shows that a single collection tray is capable of removing up to 20 MW decay heat load in a typical 500 MWe pool type SFR. Further, studies are carried out to improve the natural circulation of sodium around the source, in the lower plenum and to distribute core debris of the whole core to multiple collection trays. It is found that the double and triple collection trays can accommodate decay loads up to 29 MW. Provision of openings in the collection trays has proved to be effective in improving the heat transfer and sodium flow as well as in distributing the core debris to the

  10. Magnet cable manufacturing

    International Nuclear Information System (INIS)

    Royet, J.

    1985-07-01

    The superconducting magnets used in the construction of particle accelerators are mostly built from flat, multistrand cables with rectangular or keystoned cross sections. The superconducting strands are mostly circular but a design of a cable made of preflattened wires was proposed a few years ago under the name of Berkeley flat; such cable shows some interesting characteristics. Another design consists of a few smaller precabled wires (e.g. 6 around 1). This configuration allows smaller filaments and a better transposition of the current elements. The Superconducting Super Collider project involves the largest amount of superconducting cable ever envisaged for a single machine. Furthermore, the design calls for exceptional accuracy and improved characteristics of the cable. A part of the SSC research and development program is focused on these important questions. In this paper we emphasize the difference between the conventional cabling and wires with superconducting. A new concept for the tooling will be introduced as well as the necessary characteristics of a specialized cabler. 5 figs

  11. Biodegradable foam trays obtained from mixtures of non-irradiated and irradiated cassava starches

    International Nuclear Information System (INIS)

    Brant, A.J.C.; Naime, N.; Lugao, A.B.; Ponce, P.

    2015-01-01

    Biodegradable polymers, such as starch, cellulose, PHB, PLA, and derivatives thereof, are being studied to produce innovative packaging in the most diverse shapes (films, bags, trays, bottles, etc.) to attend this current market trend. The aim of this work was to produce foam trays from cassava starch for food packaging by extrusion-thermopressing process. Their formulations were based on non-irradiated and γ-irradiated starches at diverse radiation absorbed doses (kGy) in order to evaluate the influence of the irradiated starches on the physical properties of the trays. Water absorption results showed an irregular increase with the increase of the absorbed dose: 26.32% and 39.84% for the trays based on starch 0 kGy and 1:1 (w/w) mixture of starches 0 kGy and 100.0 kGy, respectively. Other physicochemical properties were evaluated from the starches utilized and the trays obtained. (author)

  12. Biodegradable foam trays obtained from mixtures of non-irradiated and irradiated cassava starches

    Energy Technology Data Exchange (ETDEWEB)

    Brant, A.J.C.; Naime, N.; Lugao, A.B.; Ponce, P., E-mail: thonybrant@gmail.com, E-mail: patiponce@gmail.com [Instituto de Pesquisas Energeticas e Nucleares (IPEN/CNEN-SP), Sao Paulo, SP (Brazil)

    2015-07-01

    Biodegradable polymers, such as starch, cellulose, PHB, PLA, and derivatives thereof, are being studied to produce innovative packaging in the most diverse shapes (films, bags, trays, bottles, etc.) to attend this current market trend. The aim of this work was to produce foam trays from cassava starch for food packaging by extrusion-thermopressing process. Their formulations were based on non-irradiated and γ-irradiated starches at diverse radiation absorbed doses (kGy) in order to evaluate the influence of the irradiated starches on the physical properties of the trays. Water absorption results showed an irregular increase with the increase of the absorbed dose: 26.32% and 39.84% for the trays based on starch 0 kGy and 1:1 (w/w) mixture of starches 0 kGy and 100.0 kGy, respectively. Other physicochemical properties were evaluated from the starches utilized and the trays obtained. (author)

  13. Towards functional 3D T-ray imaging

    International Nuclear Information System (INIS)

    Ferguson, Bradley; Wang, Shaohong; Gray, Doug; Abbott, Derek; Zhang, X-C

    2002-01-01

    We review the recent development of T-ray computed tomography, a terahertz imaging technique that allows the reconstruction of the three-dimensional refractive index profile of weakly scattering objects. Terahertz pulse imaging is used to obtain images of the target at multiple projection angles and the filtered backprojection algorithm enables the reconstruction of the object's frequency-dependent refractive index. The application of this technique to a biological bone sample and a plastic test structure is demonstrated. The structure of each target is accurately resolved and the frequency-dependent refractive index is determined. The frequency-dependent information may potentially be used to extract functional information from the target, to uniquely identify different materials or to diagnose medical conditions

  14. Cabling design of booster and storage ring construction progress of TPS

    International Nuclear Information System (INIS)

    Wong, Y.-S.; Liu, K.-B.; Liu, C.-Y.; Wang, B.-S.

    2017-01-01

    The 2012 Taiwan Photon Source (TPS) cable construction project started after 10 months to complete the cable laying and installation of power supply. The circumference of the booster ring (BR) is 496.8 m, whereas that of the storage ring (SR) is 518.4 m. Beam current is set to 500 mA at 3.3 GeV. The paper on grounding systems discusses the design of the ground wire (< 0.2 Ω) with low impedance, power supply of the accelerator and cabling tray. The flow and size of the ground current are carefully evaluated to avoid grounded current from flowing everywhere, which causes interference problems. In the design of the TPS, special shielding will be established to isolate the effects of electromagnetic interference on the magnet and ground current. Booster ring dipoles are connected by a series of 54-magnet bending dipole; the cable size of its stranded wire measures 250 mm"2, with a total length of 5000 m. Booster ring and storage ring quadrupoles have 150 magnets; the cable size of their stranded wire is 250 mm"2, with a total length of 17000 m. Storage ring dipole consists of 48 magnets; the cable size of its stranded wire is 325 mm"2, with a total length of 6000 m. This study discusses the power supply cabling design of the storage ring and booster ring construction progress of TPS. The sections of this paper are divided into discussions of the construction of the control and instrument area, cabling layout of booster ring and storage ring, as well as the installation and commission machine. This study also discusses the use of a high-impedance meter to determine the effect of cabling insulation and TPS power supply machine on energy transfer to ensure the use of safe and correct magnet.

  15. Instrumentation Cables Test Plan

    Energy Technology Data Exchange (ETDEWEB)

    Muna, Alice Baca [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States); LaFleur, Chris Bensdotter [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States)

    2016-10-01

    A fire at a nuclear power plant (NPP) has the potential to damage structures, systems, and components important to safety, if not promptly detected and suppressed. At Browns Ferry Nuclear Power Plant on March 22, 1975, a fire in the reactor building damaged electrical power and control systems. Damage to instrumentation cables impeded the function of both normal and standby reactor coolant systems, and degraded the operators’ plant monitoring capability. This event resulted in additional NRC involvement with utilities to ensure that NPPs are properly protected from fire as intended by the NRC principle design criteria (i.e., general design criteria 3, Fire Protection). Current guidance and methods for both deterministic and performance based approaches typically make conservative (bounding) assumptions regarding the fire-induced failure modes of instrumentation cables and those failure modes effects on component and system response. Numerous fire testing programs have been conducted in the past to evaluate the failure modes and effects of electrical cables exposed to severe thermal conditions. However, that testing has primarily focused on control circuits with only a limited number of tests performed on instrumentation circuits. In 2001, the Nuclear Energy Institute (NEI) and the Electric Power Research Institute (EPRI) conducted a series of cable fire tests designed to address specific aspects of the cable failure and circuit fault issues of concern1. The NRC was invited to observe and participate in that program. The NRC sponsored Sandia National Laboratories to support this participation, whom among other things, added a 4-20 mA instrumentation circuit and instrumentation cabling to six of the tests. Although limited, one insight drawn from those instrumentation circuits tests was that the failure characteristics appeared to depend on the cable insulation material. The results showed that for thermoset insulated cables, the instrument reading tended to drift

  16. Cable laying methods in a multi-cable elevator system

    Energy Technology Data Exchange (ETDEWEB)

    Dvornikov, V.I.; Makhinyan, V.V.

    1984-01-01

    Based on the solution of differential equations describing the stress and deformation state of cables during rolling on the drum, a conclusion is made concerning a rational method for hanging cables with a free-spinning end.

  17. [Application of individual light-curing resin tray as edge plastic material in complete denture modulo].

    Science.gov (United States)

    Chai, Mei; Tang, Xuyan; Liang, Guangku

    2015-12-01

    To investigate clinical effect of individual light-curing resin tray as edge plastic material in complete denture modulo.
 A total of 30 patients with poor condition for alveolar ridge of mandible were chosen individual tray with individual light-curing resin tray for material edge shaping or traditional individual impression tray for edge shaping cream to produce complete denture. The operability, questionnaire about denture retention, comfort, mucosal cases and chewing function in the process of shaping the edge were investigated three months later after wearing dentures.
 There was no significant difference in retention, comfort, mucosa and the chewing function between the two mandibular denture impression methods. However, the patients with individual light-curing resin tray as edge shaping material felt better in the process than that in the patients with die-cream as the edge shaping material (P<0.05). Furthermore, the manipulation with individual light-curing resin tray as edge shaping material is easy for doctor.
 Although the clinical effect of Individual light-curing resin tray material as the edge shaping material is equal to that of impression cream, it saves time and human resource. Moreover, it is more acceptable for the patients and thus it can be spread in clinics.

  18. A distillation tray with high efficiency and excellent operating flexibility for viscous mixture separation

    Directory of Open Access Journals (Sweden)

    Li Qunsheng

    2014-01-01

    Full Text Available The flow-guided sieve-valve tray(FGS-VTwith high efficiency was designed to overcome the shortcoming of low operating flexibility of the flow-guided sieve tray. Its dimensions and geometry, as well as structure characteristics, were presented. The hydrodynamics and mass transfer performance, including dry-plate pressure drop, wet plate-pressure drop, weeping, entrainment and tray efficiency, of two types of FGS-VTs (FGS-VTs with 14 and 8 valves, respectively and one flow-guided sieve tray were tested in an air-water-oxygen cold model experiment with a 0.6 m diameter plexiglass column. The results demonstrate that FGS-VT with 14 valves works better than FGS-VT with 8 valves, and in comparison with the flow-guided sieve tray, the flow-guided sieve-valve tray with 14 valves has higher tray efficiency, bigger operating flexibility, and lower wet-plate pressure drop (when all the valves are opened fully.Additionally, two typical applications to separate the mixture with high viscosity, solid, powder, easy-to-foam or easy self-polymerization components proved the unique advantages of FGS-VT.

  19. Application of FDM three-dimensional printing technology in the digital manufacture of custom edentulous mandible trays

    Science.gov (United States)

    Chen, Hu; Yang, Xu; Chen, Litong; Wang, Yong; Sun, Yuchun

    2016-01-01

    The objective was to establish and evaluate a method for manufacture of custom trays for edentulous jaws using computer aided design and fused deposition modeling (FDM) technologies. A digital method for design the custom trays for edentulous jaws was established. The tissue surface data of ten standard mandibular edentulous plaster models, which was used to design the digital custom tray in a reverse engineering software, were obtained using a 3D scanner. The designed tray was printed by a 3D FDM printing device. Another ten hand-made custom trays were produced as control. The 3-dimentional surface data of models and custom trays was scanned to evaluate the accuracy of reserved impression space, while the difference between digitally made trays and hand-made trays were analyzed. The digitally made custom trays achieved a good matching with the mandibular model, showing higher accuracy than the hand-made ones. There was no significant difference of the reserved space between different models and its matched digitally made trays. With 3D scanning, CAD and FDM technology, an efficient method of custom tray production was established, which achieved a high reproducibility and accuracy. PMID:26763620

  20. High Temperature Superconducting Underground Cable

    International Nuclear Information System (INIS)

    Farrell, Roger A.

    2010-01-01

    The purpose of this Project was to design, build, install and demonstrate the technical feasibility of an underground high temperature superconducting (HTS) power cable installed between two utility substations. In the first phase two HTS cables, 320 m and 30 m in length, were constructed using 1st generation BSCCO wire. The two 34.5 kV, 800 Arms, 48 MVA sections were connected together using a superconducting joint in an underground vault. In the second phase the 30 m BSCCO cable was replaced by one constructed with 2nd generation YBCO wire. 2nd generation wire is needed for commercialization because of inherent cost and performance benefits. Primary objectives of the Project were to build and operate an HTS cable system which demonstrates significant progress towards commercial progress and addresses real world utility concerns such as installation, maintenance, reliability and compatibility with the existing grid. Four key technical areas addressed were the HTS cable and terminations (where the cable connects to the grid), cryogenic refrigeration system, underground cable-to-cable joint (needed for replacement of cable sections) and cost-effective 2nd generation HTS wire. This was the worlds first installation and operation of an HTS cable underground, between two utility substations as well as the first to demonstrate a cable-to-cable joint, remote monitoring system and 2nd generation HTS.

  1. The Danish Superconducting Cable Project

    DEFF Research Database (Denmark)

    Tønnesen, Ole

    1997-01-01

    The design and construction of a superconducting cable is described. The cable has a room temperature dielectric design with the cryostat placed inside the electrical insulation.BSCCO 2223 superconducting tapes wound in helix form around a former are used as the cable conductor. Results from...

  2. Heat-shrinkable splicing materials for Class 1E wire and cable systems in nuclear power generating stations

    International Nuclear Information System (INIS)

    Handa, Katsue; Maruyama, Masahiro; Kanno, Mikio; Ohya, Shingo; Nagakawa, Seiji; Sugimori, Mikihiro

    1987-01-01

    This report describes the shapes of heat-shrinkable splicing materials (cable sleeve and breakout, and round end cap) made of polyolefine resin, their application to cable splicing, and the properties of the materials as well as of the splice using them. Particularly, the report features introduction of their properties as determined by tests under the same conditions as used in Japan in qualifying tests on wires and cables for nuclear power generating stations. The heat-shrinkable splicing materials proved to be equal in properties to flame-retardant cables for nuclear power plants when tested for oxygen index and subjected to a vertical flame test on ''insulated wire'' and a vertical tray flame test on the cable splice. It was also confirmed that Class 1E cable using these splicing materials could stand the most rigorous environmental test in Japan. Therefore they can be used for splicing Class 1E wires and cables and the splice formed with them can be regarded as Class 1E specified in IEEE Std. 383. (author)

  3. Cable indenter aging monitor

    International Nuclear Information System (INIS)

    Shook, T.A.; Gardner, J.B.

    1988-07-01

    This project was undertaken to develop a hand-held, nondestructive test device to assess the aged condition of electrical cable by in situ measurement of mechanical properties of polymeric jackets and insulations. The device is an indenter similar to those used to make hardness measurements. Comparison of measurements made on installed cables with previous measurements serving as baseline aging/mechanical property data will determine the state of aging of the field cables. Such a device will be valuable in nuclear and fossil plant life extension programs. Preliminary laboratory tests on cables covered with ethylene propylene rubber (EPR) and chlorosulfated polyethylene (CSPE) point to the measurement of the rate of force increase resulting from constant rate deformation as having the best correlation with progressive thermal aging. This first phase of the work has demonstrated the technical feasibility of the method. A second phase will include the generation of additional groundwork data and the design of the portable indenter for in situ plant measurements

  4. Accuracy of a separating foil impression using a novel polyolefin foil compared to a custom tray and a stock tray technique

    Science.gov (United States)

    Pastoret, Marie-Hélène; Bühler, Julia; Weiger, Roland

    2017-01-01

    PURPOSE To compare the dimensional accuracy of three impression techniques- a separating foil impression, a custom tray impression, and a stock tray impression. MATERIALS AND METHODS A machined mandibular complete-arch metal model with special modifications served as a master cast. Three different impression techniques (n = 6 in each group) were performed with addition-cured silicon materials: i) putty-wash technique with a prefabricated metal tray (MET) using putty and regular body, ii) single-phase impression with custom tray (CUS) using regular body material, and iii) two-stage technique with stock metal tray (SEP) using putty with a separating foil and regular body material. All impressions were poured with epoxy resin. Six different distances (four intra-abutment and two inter-abutment distances) were gauged on the metal master model and on the casts with a microscope in combination with calibrated measuring software. The differences of the evaluated distances between the reference and the three test groups were calculated and expressed as mean (± SD). Additionally, the 95% confidence intervals were calculated and significant differences between the experimental groups were assumed when confidence intervals did not overlap. RESULTS Dimensional changes compared to reference values varied between -74.01 and 32.57 µm (MET), -78.86 and 30.84 (CUS), and between -92.20 and 30.98 (SEP). For the intra-abutment distances, no significant differences among the experimental groups were detected. CUS showed a significantly higher dimensional accuracy for the inter-abutment distances with -0.02 and -0.08 percentage deviation compared to MET and SEP. CONCLUSION The separation foil technique is a simple alternative to the custom tray technique for single tooth restorations, while limitations may exist for extended restorations with multiple abutment teeth. PMID:28874996

  5. Design, Development and Evaluation of a Pneumatic Seeder for Automatic Planting of Seeds in Cellular Trays

    Directory of Open Access Journals (Sweden)

    E Movahedi

    2014-04-01

    Full Text Available For planting fine seeds in cellular trays, an automatic pneumatic seeder was designed, constructed and evaluated. CATIA software was used to design and analysis the system parts of the seeder. Different parts of the seeder, including vibrating seed hopper, vacuum boom, seed picking nozzles, seed tube, pneumatic system and electronic control unit for automation of the seeder, were designed and constructed. The area of nozzle orifice was used to calculate the required pressure of nozzle tip. The seeder was evaluated using two sizes of trays. Experiments were performed with five replications and the error of planting the seeds in the 105 and 390-cellular trays were 1.9 and 0.46 percent, respectively. The time of planting for 105 and 390 cellular trays reduced from 20 min (for manual seeding to 35 s and from 90 min to 160 s, respectively.

  6. Development and characteristics of halogen-free flame-retardant cables for nuclear power plants

    Energy Technology Data Exchange (ETDEWEB)

    Kanemitsuya, K.; Furukawa, K.; Tachibana, T.; Ohara, H.; Ebiike, Y.; Hamachi, K.; Makino, M. (Mitsubishi Cable Industries Ltd., Tokyo (Japan))

    1992-10-01

    Halogen-free flame-retardant (HF-FR) cables for use in nuclear power plants, especially in pressurized water type (PWR) plants, have been developed to advancing the safety and reliability of nuclear power plants. HF-FR cables generate no corrosive gases and minimal amount of toxic gases and smoke during fires, and are accordingly quite safe in comparison with the conventional cables which can cause the secondary calamity by eliminating a large amount of hydrogen halide gas and smoke. HF-FR ethylene-propylene rubber (EPR) and crosslinked polyolefin (XLPO) are used as insulating materials, and HF-FR ethylene-vinyl acetate (EVA) elastomer and polyolefin (PO) are used as jacketing materials. The results of a series of experiments on several types of HF-FR cables have revealed that these cables fully satisfy every requirement, including reliability under LOCA (Loss of Coolant Accidents) simulated conditions, long-term (40y) reliability under thermal and [gamma]-ray exposure, and flame resistivity under vertical tray test (IEEE Std. 383). (author).

  7. Heat and Mass Transfer Measurements for Tray-Fermented Fungal Products

    Science.gov (United States)

    Jou, R.-Y.; Lo, C.-T.

    2011-01-01

    In this study, heat and mass transfer in static tray fermentation, which is widely used in solid-state fermentation (SSF) to produce fungal products, such as enzymes or koji, is investigated. Specifically, kinetic models of transport phenomena in the whole-tray chamber are emphasized. The effects of temperature, moisture, and humidity on microbial growth in large-scale static tray fermentation are essential to scale-up SSF and achieve uniform fermentation. In addition, heat and mass transfer of static tray fermentation of Trichoderma fungi with two tray setups—traditional linen coverings and stacks in a temperature-humidity chamber is examined. In both these setups, the following factors of fermentation were measured: air velocity, air temperature, illumination, pH, carbon dioxide (CO2) concentration, and substrate temperature, and the effects of bed height, moisture of substrate, and relative humidity of air are studied. A thin (1 cm) bed at 28 °C and 95 % relative humidity is found to be optimum. Furthermore, mixing was essential for achieving uniform fermentation of Trichoderma fungi. This study has important applications in large-scale static tray fermentation of fungi.

  8. Accuracy of a self-perforating impression tray for dental implants.

    Science.gov (United States)

    Marotti, Juliana; Tortamano, Pedro; Castilho, Tatiana R R N; Steagall, Washington; Wolfart, Stefan; Haselhuhn, Klaus

    2014-10-01

    Difficulties are involved in impression making with conventional open impression trays. The purpose of this study was to evaluate the accuracy of transferring implant impressions with a self-perforating impression tray. A reference model of a mandible was fabricated, and 4 implants were placed in the regions of the first premolars and lateral incisors (implants 1, 2, 3, 4). Ten impressions of the reference model with polyvinyl siloxane were made for each group; control (conventional open impression tray) and test (self-perforating impression tray; Miratray Implant). A metal bar was screw-retained on implant 1, and the gaps generated at the vestibular face of implants 3 and 4 were measured by optical microcopy. The 2-way ANOVA and least square difference post hoc test were used (α=.05). Higher mean (±SD) values were obtained for the test group than for the control group for both implants: implant 3: 150 ±84 μm for the test group, 73 ±63 μm for the control group (P=.019); implant 4: 129 ±65 μm for the test group, 62 ±61 μm for the control group (P=.04). The self-perforating impression tray provided less accuracy than the conventional open tray. Copyright © 2014 Editorial Council for the Journal of Prosthetic Dentistry. Published by Elsevier Inc. All rights reserved.

  9. Development of Inspection Robots for Bridge Cables

    Directory of Open Access Journals (Sweden)

    Hae-Bum Yun

    2013-01-01

    Full Text Available This paper presents the bridge cable inspection robot developed in Korea. Two types of the cable inspection robots were developed for cable-suspension bridges and cable-stayed bridge. The design of the robot system and performance of the NDT techniques associated with the cable inspection robot are discussed. A review on recent advances in emerging robot-based inspection technologies for bridge cables and current bridge cable inspection methods is also presented.

  10. Development of inspection robots for bridge cables.

    Science.gov (United States)

    Yun, Hae-Bum; Kim, Se-Hoon; Wu, Liuliu; Lee, Jong-Jae

    2013-01-01

    This paper presents the bridge cable inspection robot developed in Korea. Two types of the cable inspection robots were developed for cable-suspension bridges and cable-stayed bridge. The design of the robot system and performance of the NDT techniques associated with the cable inspection robot are discussed. A review on recent advances in emerging robot-based inspection technologies for bridge cables and current bridge cable inspection methods is also presented.

  11. Effects of impression levels and trays on the accuracy of impressions taken from angulated implants.

    Science.gov (United States)

    Geramipanah, Farideh; Sahebi, Majid; Davari, Maryam; Hajimahmoudi, Mohammadreza; Rakhshan, Vahid

    2015-09-01

    It is crucial to keep the misfit of the abutment-fixture unit at the lowest possible rate. There are a few controversial studies on the accuracy of impression making of angulated implants, and much fewer (and controversial) studies on the abutment-level impression technique, which is a convenient and clinically favorable method. Besides, there are no studies on comparison of sectional vs. full-arch trays. We aimed to assess these. A trapezoidal model with four angulated implants installed at 20° and 30° buccal tilts was fabricated. Forty impressions were taken from this model, with two groups of full-arch and sectional custom trays (n = 2 × 20), each divided into two subgroups of implant-level and abutment-level techniques (n = 2 × 2 × 10 in four subgroups). Absolute and non-absolute linear and angular impression errors were estimated by comparing the fabricated casts with the model, using a coordinate measuring machine. The effects of sectional/full-arch trays and abutment-level and fixture-level techniques on impression accuracies were analyzed using one- and two-way analyses of variance (ANOVA), Tukey, Mann-Whitney, and one-sample t-tests (α = 0.05, Mann-Whitney's α using the Bonferroni Bonferroni method). No significant differences between the absolute linear errors of the two trays (P = 0.100 [ANOVA]) and the two levels (P = 0.400 [ANOVA]) were observed. The assessment of absolute angular errors showed no significant differences (all P values ≥ 0.4 [ANOVA]). The difference between the linear errors in the full-arch vs. sectional trays was not significant in the fixture-level group (P = 0.290). However, in the abutment-level group, the linear error was significantly greater in the sectional tray compared to full-arch tray (P = 0.013, α = 0.025 [Mann-Whitney]). Using sectional trays might not be advantageous over full-arch trays. Sectional trays are not recommended for taking abutment-level impressions. The abutment

  12. The effect of impression volume and double-arch trays on the registration of maximum intercuspation.

    Science.gov (United States)

    Hahn, Sara M; Millstein, Philip L; Kinnunen, Taru H; Wright, Robert F

    2009-12-01

    The type of double-arch trays used may affect occlusion. The purpose of this study was to determine what effect, if any, double-arch tray design and impression material volume had on the registration of maximum intercuspation (MI). Quadrant impressions were made on articulated fracture-resistant dental casts mounted in maximum intercuspation occlusion. Three types of sideless double-arch impression trays were used: First Bite with nylon webbing, Sultan's 3-Way with double crosshatch webbing, and Premium's 3-in-1 Tray with single crosshatch webbing. Vinyl polysiloxane impression material (Aquasil Ultra Rigid Fast Set) was distributed at 2 different volumes (5.4 ml and 8.3 ml), and 60 impressions were made (n=10). A weight of 1.2 kg was placed on the upper arm of an Artex articulator, ensuring complete closure. The impressions were allowed to polymerize for 5 minutes. After polymerization, specimens were placed on a light box, and a camera set at a fixed distance was used to capture the light transmission that was projected through the impression material. The camera transferred the information to an image analysis program (ImageJ). This system allowed the different amounts of light projected through the impression to be translated into a gray scale value (GSV), which was assigned a thickness value, in millimeters, of a specified occlusal contact area. To assess reliability of the experimental design, 10 control impressions were made by directly applying impression material onto the typodont. These were analyzed in the same manner as the impressions made with trays. A 2-way ANOVA comparing volume by tray type was used (alpha=.05). This was followed by a Tukey HSD test. There was no main effect for volume of impression material (P=.71). Tray type was significantly different (Precord making.

  13. Cable networks, services, and management

    CERN Document Server

    2015-01-01

    Cable Networks, Services, and Management is the first book to cover cable networks, services, and their management, in-depth, for network operators, engineers, researchers, and students. Thirteen experts in various fields have contributed their knowledge of network architectures and services, Operations, Administration, Maintenance, Provisioning, Troubleshooting (OAMPT) for residential and business services, cloud, Software Defined Networks (SDN), as well as virtualization concepts and their applications as part of the future directions of cable networks. The book begins by introducing architecture and services for Data Over Cable Service Interface Specification (DOCSIS) 3.0/ 3.1, Converged Cable Access Platform (CCAP), Content Distribution Networks (CDN, IP TV, and Packet Cable and Wi-Fi for Residential Services. Topics that are discussed in proceeding chapters include: operational systems and management architectures, service orders, provisioning, fault manageme t, performance management, billing systems a...

  14. 14 CFR 23.689 - Cable systems.

    Science.gov (United States)

    2010-01-01

    ... in cable tension throughout the range of travel under operating conditions and temperature variations... 14 Aeronautics and Space 1 2010-01-01 2010-01-01 false Cable systems. 23.689 Section 23.689... Systems § 23.689 Cable systems. (a) Each cable, cable fitting, turnbuckle, splice, and pulley used must...

  15. Dynamic testing of cable structures

    Directory of Open Access Journals (Sweden)

    Caetano Elsa

    2015-01-01

    Full Text Available The paper discusses the role of dynamic testing in the study of cable structures. In this context, the identification of cable force based on vibration measurements is discussed. Vibration and damping assessment are then introduced as the focus of dynamic monitoring systems, and particular aspects of the structural behaviour under environmental loads are analysed. Diverse application results are presented to support the discussion centred on cable-stayed bridges, roof structures, a guyed mast and a transmission line.

  16. Performing of recent real scale cable fire experiments and presentation of the results in the frame of the international collaborative fire modeling project ICFMP. Final report

    International Nuclear Information System (INIS)

    Hosser, Dietmar; Riese, Olaf; Klingenberg, Mark

    2005-01-01

    As a part of the Fire Risk Research Program, the German iBMB (Institut fuer Baustoffe, Massivbau und Brandschutz) of Braunschweig University of Technology and GRS (Gesellschaft fuer Anlagenund Reaktorsicherheit mbH) are participating in an International Collaborative Fire Modeling Project (ICFMP) to assess and validate fire computer codes for nuclear power plant applications. This assessment is being conducted through benchmarking and validation exercises. The tests are simulating cable fires scenarios in a single compartment. The goal of the actual cable fire series is to investigate the effects of a natural fire to vertically routed cables (worst case) with different cable insulation material (PVC and FRNC). Another important aspect of cable fire is the risk of function failure. Therefore in the test series the short circuit and the conduction loss of cables are measured. This report includes a first description of the experimental results for test 1 - test 4 of the International Collaborative Fire Model Project conducted in December 2003 at the iBMB in Germany. The experimental data are reported on the International Collaborative Fire Model Project - Platform. The measured data shall be the basis for fire simulations. The tests show that the FRNC cables have significantly better characteristics in case of fire. No substantial flame spread takes place even in case of preheating. PVC cables could be ignited with a burner output of 50 kW, in contrary, the FRNC cables could be ignited at burner output of 150 kW. The preheating has a complex effect on the fire behavior of the cables. It may occur that gases are pyrolysed which are not ignited during the phase of preheating. These gases are transported from the cable surrounding and may leave the fire room. Short circuits occur first in case ''conductor to conductor'' and later in case ''conductor to tray''. The time periods until short circuits occur are strongly dependent on the preheating of the cables. In case of

  17. Electromagnetic transients in power cables

    CERN Document Server

    da Silva, Filipe Faria

    2013-01-01

    From the more basic concepts to the most advanced ones where long and laborious simulation models are required, Electromagnetic Transients in Power Cables provides a thorough insight into the study of electromagnetic transients and underground power cables. Explanations and demonstrations of different electromagnetic transient phenomena are provided, from simple lumped-parameter circuits to complex cable-based high voltage networks, as well as instructions on how to model the cables.Supported throughout by illustrations, circuit diagrams and simulation results, each chapter contains exercises,

  18. Superconducting flat tape cable magnet

    Science.gov (United States)

    Takayasu, Makoto

    2015-08-11

    A method for winding a coil magnet with the stacked tape cables, and a coil so wound. The winding process is controlled and various shape coils can be wound by twisting about the longitudinal axis of the cable and bending following the easy bend direction during winding, so that sharp local bending can be obtained by adjusting the twist pitch. Stack-tape cable is twisted while being wound, instead of being twisted in a straight configuration and then wound. In certain embodiments, the straight length should be half of the cable twist-pitch or a multiple of it.

  19. Calculation of electron contamination doses produced using blocking trays for 6 MV X-rays

    Energy Technology Data Exchange (ETDEWEB)

    Butson, M.J. E-mail: mbutson@guessmail.com; Cheung Tsang; Yu, P.K.N

    2002-04-01

    Calculation of electron contamination doses whilst using blocking trays in radiotherapy is achieved by comparison of measured absorbed dose within the first few centimeters of a water phantom. Electron contamination of up to 28% of maximum dose is produced at the central axis of the beam whilst using a 6 mm Perspex blocking tray for a 30 cmx30 cm field. The electron contamination is spread over the entire field reducing slightly towards the edge of the beam. Electron contamination from block trays is also present outside the primary collimated X-ray beam with more than 20% of the maximum dose deposited at the surface, 5 cm outside the primary collimated beam at a field size of 40 cmx40 cm. The electron contamination spectrum has been calculated from measured results.

  20. Dimensional changes in plaster cast models due to the position of the impression tray during setting

    Directory of Open Access Journals (Sweden)

    Betina Grehs Porto

    2014-01-01

    Full Text Available Introduction: The objective of this study was to assess whether the positioning of the impression tray could cause distortion to plaster casts during gypsum setting time.Materials and Methods: Fifteen pairs of master models were cast with alginate impression material and immediately filled with gypsum. Impressions were allowed to set with the tray in the noninverted position (Group A or in the inverted position (Group B. The plaster models were digitized using a laser scanner (3Shape R-700, 3Shape A/S, Copenhagen, Denmark. Measurements of tooth size and distance were obtained using O3d software (Widialabs, Brazil measurement tools. Data were analyzed by paired t-test and linear regression with 5% significance.Results and Conclusion: Most of the measurements from both groups were similar, except forthe lower intermolar distance. It was not possible to corroborate the presence of distortions due to the position of the impression tray during gypsum setting time.

  1. Polylactic acid trays for fresh-food packaging: A Carbon Footprint assessment.

    Science.gov (United States)

    Ingrao, Carlo; Tricase, Caterina; Cholewa-Wójcik, Agnieszka; Kawecka, Agnieszka; Rana, Roberto; Siracusa, Valentina

    2015-12-15

    This paper discusses application of Carbon Footprint (CF) for quantification of the 100-year Global Warming Potential (GWP100) associated with the life cycle of polylactic acid (PLA) trays for packaging of fresh foods. A comparison with polystyrene (PS)-based trays was done considering two different transport system scenarios for PLA-granule supply to the tray production firm: a transoceanic freight vessel and an intercontinental freight aircraft. Doing so enabled estimation of the influence of the transportation phase on the GHG-emission rate associated with the PLA-trays' life cycle. From the assessment, the GWP100 resulted to be mainly due to PLA-granulate production and to its transportation to the tray manufacturing facility. Also, the study documented that, depending upon the transport system considered, the CF associated with the life cycle of the PLA trays can worsen so much that the latter are no longer GHG-emission saving as they are expected to be compared to the PS ones. Therefore, based upon the findings of the study, it was possible for the authors to understand the importance and the need of accounting for the transport-related issues in the design of PLA-based products, thus preserving their environmental soundness compared to traditional petroleum-based products. In this context, the study could be used as the base to reconsider the merits of PLA usage for product manufacturing, especially when high distances are implied, as in this analysed case. So, the authors believe that new research and policy frameworks should be designed and implemented for both development and promotion of more globally sustainable options. Copyright © 2015 Elsevier B.V. All rights reserved.

  2. Cable deterioration analysis method

    International Nuclear Information System (INIS)

    Sugiyama, Masahiko; Nitta, Makoto.

    1997-01-01

    At first, a hardness of a minute region and an elongation at break are measured relative to a plurality of reference samples having deterioration which is different stepwise, to obtain a relation between the hardness of the minute region and the elongation at break. They are obtained as information of correlation showing the degree of deterioration of cables. Then, samples are collected. The samples are collected from a PVC sheath. In this case, the samples to be used for the measurement are extremely small piece having the size of one side of about several hundred μm. Then, the hardness of the minute region of the samples is measured. The measured hardness of the minute region is corresponded to the previously obtained information of the correlation for deteriorations to judge the state of deterioration for the collected samples. With such procedures, the state of deterioration for electric wires and cables to be used in nuclear facilities such as power plants can easily be diagnosed substantially non destructively. (I.N.)

  3. Cable Television in Sedalia, Missouri.

    Science.gov (United States)

    Lamkin, Kathryn Janel

    A field study was conducted of the status of cable television in Sedalia, Missouri. Based on interviews of city council members and staff members of Cablevision, the Sedalia cable franchise holder, the following issues were investigated: (1) subscription rates; (2) franchise negotiations; (3) quality of existing services; and (4) possible…

  4. The optimum spanning catenary cable

    Science.gov (United States)

    Wang, C. Y.

    2015-03-01

    A heavy cable spans two points in space. There exists an optimum cable length such that the maximum tension is minimized. If the two end points are at the same level, the optimum length is 1.258 times the distance between the ends. The optimum lengths for end points of different heights are also found.

  5. Production of diosgenin from Dioscorea zingiberensis with mixed culture in a new tray bioreactor

    Directory of Open Access Journals (Sweden)

    Yutong Cheng

    2016-01-01

    Full Text Available A new tray bioreactor was developed for the production of diosgenin from Dioscorea zingiberensis with Trichoderma reesei and Aspergillus fumigatus. The influence of initial moisture content, temperature, tray bed depth and mixing times was investigated. The best fermentation condition is initial moisture content of 75%, bioreactor temperature of 35°C, solid bed depth of 1.5 cm and three mixings carrying out on the first, third and fifth day. Under the optimized fermentation conditions, after 144 h incubation, maximum diogenin concentration of 68.2 μmol/g was detected.

  6. Photonic-powered cable assembly

    Science.gov (United States)

    Sanderson, Stephen N.; Appel, Titus James; Wrye, IV, Walter C.

    2013-01-22

    A photonic-cable assembly includes a power source cable connector ("PSCC") coupled to a power receive cable connector ("PRCC") via a fiber cable. The PSCC electrically connects to a first electronic device and houses a photonic power source and an optical data transmitter. The fiber cable includes an optical transmit data path coupled to the optical data transmitter, an optical power path coupled to the photonic power source, and an optical feedback path coupled to provide feedback control to the photonic power source. The PRCC electrically connects to a second electronic device and houses an optical data receiver coupled to the optical transmit data path, a feedback controller coupled to the optical feedback path to control the photonic power source, and a photonic power converter coupled to the optical power path to convert photonic energy received over the optical power path to electrical energy to power components of the PRCC.

  7. Cable Bacteria in Freshwater Sediments

    DEFF Research Database (Denmark)

    Risgaard-Petersen, Nils; Kristiansen, Michael; Frederiksen, Rasmus

    2015-01-01

    In marine sediments cathodic oxygen reduction at the sediment surface can be coupled to anodic sulfide oxidation in deeper anoxic layers through electrical currents mediated by filamentous, multicellular bacteria of the Desulfobulbaceae family, the so-called cable bacteria. Until now, cable...... bacteria have only been reported from marine environments. In this study, we demonstrate that cable bacteria also occur in freshwater sediments. In a first step, homogenized sediment collected from the freshwater stream Giber Å, Denmark, was incubated in the laboratory. After 2 weeks, pH signatures...... marine cable bacteria, with the genus Desulfobulbus as the closest cultured lineage. The results of the present study indicate that electric currents mediated by cable bacteria could be important for the biogeochemistry in many more environments than anticipated thus far and suggest a common evolutionary...

  8. Length of a Hanging Cable

    Directory of Open Access Journals (Sweden)

    Eric Costello

    2011-01-01

    Full Text Available The shape of a cable hanging under its own weight and uniform horizontal tension between two power poles is a catenary. The catenary is a curve which has an equation defined by a hyperbolic cosine function and a scaling factor. The scaling factor for power cables hanging under their own weight is equal to the horizontal tension on the cable divided by the weight of the cable. Both of these values are unknown for this problem. Newton's method was used to approximate the scaling factor and the arc length function to determine the length of the cable. A script was written using the Python programming language in order to quickly perform several iterations of Newton's method to get a good approximation for the scaling factor.

  9. Modeling of Electrical Cable Failure in a Dynamic Assessment of Fire Risk

    Science.gov (United States)

    Bucknor, Matthew D.

    Fires at a nuclear power plant are a safety concern because of their potential to defeat the redundant safety features that provide a high level of assurance of the ability to safely shutdown the plant. One of the added complexities of providing protection against fires is the need to determine the likelihood of electrical cable failure which can lead to the loss of the ability to control or spurious actuation of equipment that is required for safe shutdown. A number of plants are now transitioning from their deterministic fire protection programs to a risk-informed, performance based fire protection program according to the requirements of National Fire Protection Association (NFPA) 805. Within a risk-informed framework, credit can be taken for the analysis of fire progression within a fire zone that was not permissible within the deterministic framework of a 10 CFR 50.48 Appendix R safe shutdown analysis. To perform the analyses required for the transition, plants need to be able to demonstrate with some level of assurance that cables related to safe shutdown equipment will not be compromised during postulated fire scenarios. This research contains the development of new cable failure models that have the potential to more accurately predict electrical cable failure in common cable bundle configurations. Methods to determine the thermal properties of the new models from empirical data are presented along with comparisons between the new models and existing techniques used in the nuclear industry today. A Dynamic Event Tree (DET) methodology is also presented which allows for the proper treatment of uncertainties associated with fire brigade intervention and its effects on cable failure analysis. Finally a shielding analysis is performed to determine the effects on the temperature response of a cable bundle that is shielded from a fire source by an intervening object such as another cable tray. The results from the analyses demonstrate that models of similar

  10. [The geometry of the keel determines the behaviour of the tibial tray against torsional forces in total knee replacement].

    Science.gov (United States)

    García David, S; Cortijo Martínez, J A; Navarro Bermúdez, I; Maculé, F; Hinarejos, P; Puig-Verdié, L; Monllau, J C; Hernández Hermoso, J A

    2014-01-01

    The keel design of the tibial tray is essential for the transmission of the majority of the forces to the peripheral bone structures, which have better mechanical proprieties, thus reducing the risk of loosening. The aim of the present study was to compare the behaviour of different tibial tray designs submitted to torsional forces. Four different tibial components were modelled. The 3-D reconstruction was made using the Mimics software. The solid elements were generated by SolidWorks. The finite elements study was done by Unigraphics. A torsional force of 6 Nm. applied to the lateral aspects of each tibial tray was simulated. The GENUTECH® tibial tray, with peripheral trabecular bone support, showed a lower displacement and less transmitted tensions under torsional forces. The results suggest that a tibial tray with more peripheral support behaves mechanically better than the other studied designs. Copyright © 2013 SECOT. Published by Elsevier Espana. All rights reserved.

  11. Novel method of fabricating individual trays for maxillectomy patients by computer-aided design and rapid prototyping.

    Science.gov (United States)

    Huang, Zhi; Wang, Xin-zhi; Hou, Yue-Zhong

    2015-02-01

    Making impressions for maxillectomy patients is an essential but difficult task. This study developed a novel method to fabricate individual trays by computer-aided design (CAD) and rapid prototyping (RP) to simplify the process and enhance patient safety. Five unilateral maxillectomy patients were recruited for this study. For each patient, a computed tomography (CT) scan was taken. Based on the 3D surface reconstruction of the target area, an individual tray was manufactured by CAD/RP. With a conventional custom tray as control, two final impressions were made using the different types of tray for each patient. The trays were sectioned, and in each section the thickness of the material was measured at six evenly distributed points. Descriptive statistics and paired t-test were used to examine the difference of the impression thickness. SAS 9.3 was applied in the statistical analysis. Afterwards, all casts were then optically 3D scanned and compared digitally to evaluate the feasibility of this method. Impressions of all five maxillectomy patients were successfully made with individual trays fabricated by CAD/RP and traditional trays. The descriptive statistics of impression thickness measurement showed slightly more uneven results in the traditional trays, but no statistical significance was shown. A 3D digital comparison showed acceptable discrepancies within 1 mm in the majority of cast areas. The largest difference of 3 mm was observed in the buccal wall of the defective areas. Moderate deviations of 1 to 2 mm were detected in the buccal and labial vestibular groove areas. This study confirmed the feasibility of a novel method of fabricating individual trays by CAD/RP. Impressions made by individual trays manufactured using CAD/RP had a uniform thickness, with an acceptable level of accuracy compared to those made through conventional processes. © 2014 by the American College of Prosthodontists.

  12. Custom sectional impression trays with interlocking type handle for microstomia patients

    Directory of Open Access Journals (Sweden)

    Fernandes Aquaviva

    2009-01-01

    Full Text Available Making impressions in microstomia patients is often cumbersome. A modification of standard impression procedure is often necessary while treating such patients. This article describes the fabrication of a custom sectional impression tray with interlocking type of a handle for definitive impression procedures in a microstomia patient.

  13. Implementing Adlerian Sand Tray Therapy with Adult Male Substance Abuse Offenders: A Phenomenological Inquiry

    Science.gov (United States)

    Monakes, Sarah; Garza, Yvonne; Wiesner, Van, III; Watts, Richard E.

    2011-01-01

    The purpose of this phenomenological study was to understand the perceptions of adult male substance offenders who experienced sand tray therapy as an adjunct to their cognitive behavioral rehabilitative treatment. Results indicate a positive experience for participants. Implications for counselors are discussed. (Contains 1 table.)

  14. [Evaluation of production and clinical working time of computer-aided design/computer-aided manufacturing (CAD/CAM) custom trays for complete denture].

    Science.gov (United States)

    Wei, L; Chen, H; Zhou, Y S; Sun, Y C; Pan, S X

    2017-02-18

    To compare the technician fabrication time and clinical working time of custom trays fabricated using two different methods, the three-dimensional printing custom trays and the conventional custom trays, and to prove the feasibility of the computer-aided design/computer-aided manufacturing (CAD/CAM) custom trays in clinical use from the perspective of clinical time cost. Twenty edentulous patients were recruited into this study, which was prospective, single blind, randomized self-control clinical trials. Two custom trays were fabricated for each participant. One of the custom trays was fabricated using functional suitable denture (FSD) system through CAD/CAM process, and the other was manually fabricated using conventional methods. Then the final impressions were taken using both the custom trays, followed by utilizing the final impression to fabricate complete dentures respectively. The technician production time of the custom trays and the clinical working time of taking the final impression was recorded. The average time spent on fabricating the three-dimensional printing custom trays using FSD system and fabricating the conventional custom trays manually were (28.6±2.9) min and (31.1±5.7) min, respectively. The average time spent on making the final impression with the three-dimensional printing custom trays using FSD system and the conventional custom trays fabricated manually were (23.4±11.5) min and (25.4±13.0) min, respectively. There was significant difference in the technician fabrication time and the clinical working time between the three-dimensional printing custom trays using FSD system and the conventional custom trays fabricated manually (Pmanufacture custom trays by three-dimensional printing method, there is no need to pour preliminary cast after taking the primary impression, therefore, it can save the impression material and model material. As to completing denture restoration, manufacturing custom trays using FSD system is worth being

  15. 10BASE5 Ethernet Cable & Vampire Tap

    CERN Document Server

    1983-01-01

    10BASE5 Thick Ethernet Cable, 10Mbit/sec. In the 1980s and early 1990's, Ethernet became more popular and provided a much faster data transmission rate. This cable is one of the first ethernet cables from 1983, a thick, bulky affair. Computers were attached via "Vampire Taps" which were connectors screwed straight through the shielding of the cable.

  16. 14 CFR 27.1365 - Electric cables.

    Science.gov (United States)

    2010-01-01

    ... 14 Aeronautics and Space 1 2010-01-01 2010-01-01 false Electric cables. 27.1365 Section 27.1365... STANDARDS: NORMAL CATEGORY ROTORCRAFT Equipment Electrical Systems and Equipment § 27.1365 Electric cables. (a) Each electric connecting cable must be of adequate capacity. (b) Each cable that would overheat...

  17. 30 CFR 18.45 - Cable reels.

    Science.gov (United States)

    2010-07-01

    ... and locomotives shall maintain positive tension on the portable cable during reeling and unreeling. Such tension shall only be high enough to prevent a machine from running over its own cable(s). (e... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Cable reels. 18.45 Section 18.45 Mineral...

  18. 14 CFR 25.689 - Cable systems.

    Science.gov (United States)

    2010-01-01

    ... cable system must be designed so that there will be no hazardous change in cable tension throughout the... 14 Aeronautics and Space 1 2010-01-01 2010-01-01 false Cable systems. 25.689 Section 25.689... STANDARDS: TRANSPORT CATEGORY AIRPLANES Design and Construction Control Systems § 25.689 Cable systems. (a...

  19. Accuracy of Different Implant Impression Techniques: Evaluation of New Tray Design Concept.

    Science.gov (United States)

    Liu, David Yu; Cader, Fathima Nashmie; Abduo, Jaafar; Palamara, Joseph

    2017-12-29

    To evaluate implant impression accuracy with a new tray design concept in comparison to nonsplinted and splinted impression techniques for a 2-implant situation. A reference bar titanium framework was fabricated to fit on 2 parallel implants. The framework was used to generate a resin master model with 2 implants that fit precisely against the framework. Three impression techniques were evaluated: (1) nonsplinted, (2) splinted, and (3) nonsplinted with modified tray impressions. All the trays were fabricated from light-cured acrylic resin material with openings that corresponded to the implant impression copings. Ten impressions were taken for each technique using poly(vinyl siloxane) impression material. The impressions were poured with type IV dental stone to generate the test casts. A rosette strain gauge was bonded to the middle of the framework. As the framework retaining screws were tightened on each test cast, the developed strains were recorded until the completion of the tightening to 35 Ncm. The generated strains of the rosette strain gauge were used to calculate the maximum principal strain. A statistically significant difference was observed among the different impression techniques. The modified tray design impression technique was associated with the least framework strains, which indicates greater accuracy compared with the other techniques. There was no significant difference between the splinted and the nonsplinted impression techniques. The new tray design concept appeared to produce more accurate implant impressions than the other techniques. Despite the statistical difference among the impression techniques, the clinical significance of this difference is yet to be determined. © 2017 by the American College of Prosthodontists.

  20. Dimensional changes of alginate impression by using perforated and non-perforated ring trays

    Directory of Open Access Journals (Sweden)

    Sumadhi Sastrodihardjo

    2010-03-01

    Full Text Available Dimensional changes are a common occurrence in impressions, either during or after impression taking. It produces a difference in the dimensions of the object and the model, which leads to the restoration being ill-fitted. Several causal factors have been proposed such as friction between the impression material and the teeth, the bulk of the impression material, the type of impression materials used, the impression technique, the pouring time and many others. The exact causal factor is still unknown and the dimensional change mechanism is still poorly understood. The objective of this research was to investigate the role of the perforation on the ring trays in producing dimensional changes in the impression by using perforated and non-perforated ring trays. Alginate impressions were made on the frustum of cone metal master die with a 7.08 mm base diameter, 7.03 mm top diameter and 9.23 mm height using perforated and non-perforated ring trays with 9.40 mm in diameter and 14.17 mm in height. The dimensional change was determined by comparing the dimension of the dental stone die and its metal master die. The results showed that the percentage of dimensional changes that occurred by using perforated ring tray were (+ 0.56±0.40 on the top area, (- 3.54±2.92 on base area and (+ 1.54±0.83 in height, respectively. As compared to using non-perforated ring trays, the percentage of dimensional changes that occurred were (- 0.49±0.49 on top area, (- 8.76±3.95 on base area and (+ 1.19±0.71 in height, respectively. There was a significant difference in the direction of the dimensional changes on both the top areas, but not in the base areas and height.

  1. Numerical prediction of fire extinguishment characteristics of sodium leak collection tray in a fast breeder reactor

    International Nuclear Information System (INIS)

    Diwakar, S.V.; Mangarjuna Rao, P.; Kasinathan, N.; Das, Sarit K.; Sundararajan, T.

    2011-01-01

    Highlights: ► Sodium fire extinguishment in a leak collection tray is modeled by lumped approach. ► Hydrodynamics of liquid sodium on tray is emulated through a draining/sloshing model. ► Pool burning rates in the tray and holdup vessel are numerically estimated. ► The model directly yields the mass of sodium recovered after extinction of fire. ► Model predictions are in reasonable agreement with the available experimental data. - Abstract: Sodium leak collection tray (LCT) is an efficient passive device used for the extinguishment of liquid sodium fire in case of an accidental leakage from the secondary circuit of a fast breeder reactor. The LCT essentially isolates the leaking sodium into closed containers where the resulting fire is extinguished due to limited availability of oxygen. The current work aims to highlight the combustion extinguishment characteristics of LCT through a lumped formulation by conserving the mass and energy of liquid sodium and constituent gases in various parts of the LCT. Here, the complex hydrodynamics of liquid sodium is emulated through a semi-analytical draining/sloshing model and its burning rates are predicted through a three-dimensional open pool combustion model for the tray region and a closed pool combustion model for the holdup vessel. These simulations evaluate the burning rates at discrete levels of liquid sodium which are subsequently interpolated to establish correlations involving instantaneous liquid levels and oxygen concentration. Using the correlations obtained from the draining and combustion models, the overall lumped formulation directly predicts the un-burnt sodium recoverable after the extinguishment of fire in the LCT. The predicted results of this model compare well with the available experimental data.

  2. Cables - a question of custom-design

    International Nuclear Information System (INIS)

    Doig, Tom

    1994-01-01

    Electrical equipment such as cabling can often be the limiting factor as far as machine operations in radioactive environments are concerned. Electronic and electrical equipment will degrade if exposed to ionising radiation, affecting equipment reliability, or causing complete failure. However, several companies provide custom-designed products directed specifically at the nuclear industry. One such company is Habia Cable which has built up its business in submarine cables, internal engine cables, and cables for high fire risk situations. It began supplying custom-designed cables to the nuclear industry in 1986, and has since then supplied cables throughout Europe from its plant in Sweden. (Author)

  3. Motility of electric cable bacteria

    DEFF Research Database (Denmark)

    Bjerg, Jesper Tataru; Damgaard, Lars Riis; Holm, Simon Agner

    2016-01-01

    Cable bacteria are filamentous bacteria that electrically couple sulfide oxidation and oxygen reduction at centimeter distances, and observations in sediment environments have suggested that they are motile. By time-lapse microscopy, we found that cable bacteria used gliding motility on surfaces...... with a highly variable speed of 0.50.3 ms1 (meanstandard deviation) and time between reversals of 155108 s. They frequently moved forward in loops, and formation of twisted loops revealed helical rotation of the filaments. Cable bacteria responded to chemical gradients in their environment, and around the oxic......-anoxic interface, they curled and piled up, with straight parts connecting back to the source of sulfide. Thus, it appears that motility serves the cable bacteria in establishing and keeping optimal connections between their distant electron donor and acceptors in a dynamic sediment environment....

  4. Cable SGEMP Code Validation Study

    Energy Technology Data Exchange (ETDEWEB)

    Ballard, William Parker [Sandia National Lab. (SNL-CA), Livermore, CA (United States). Center for CA Weapons Systems Engineering

    2013-05-01

    This report compared data taken on the Modular Bremsstrahlung Simulator using copper jacketed (cujac) cables with calculations using the RHSD-RA Cable SGEMP analysis tool. The tool relies on CEPXS/ONBFP to perform radiation transport in a series of 1D slices through the cable, and then uses a Green function technique to evaluate the expected current drive on the center conductor. The data were obtained in 2003 as part of a Cabana verification and validation experiment using 1-D geometries, but were not evaluated until now. The agreement between data and model is not adequate unless gaps between the dielectric and outer conductor (ground) are assumed, and these gaps are large compared with what is believed to be in the actual cable.

  5. Air flow around suspended cables

    Directory of Open Access Journals (Sweden)

    Gołębiowska Irena

    2017-01-01

    Full Text Available The impact of wind on construction structures is essential issue in design and operation. In particular, the wind can cause the dengerous vibrations of slender structures with low rigidity, eg. vibrations of cables of suspension and cable-stayed bridges or high voltage transmision lines, thus understanding of wind flow around such constructions is significant. In the paper the results of the analysis of wind flow around the cables for different Reynolds number is presented. The analysed flow meets the Navier-Stokes and continuity equations. The circle and elipse section of the cable is analysed. The discusion of vorticity, drag and lift coefficients and cases due to different angle of wind flow action is presented. The boundary layer and its infuence on total flow is analysed.

  6. Nuclear instrumentation cable end seal

    International Nuclear Information System (INIS)

    Cannon, C.P.; Brown, D.P.

    1979-01-01

    An improved coaxial end seal for hermetically sealed nuclear instrumentation cable exhibiting an improved breakdown pulse noise characteristic under high voltage, high temperature conditions is described. A tubular insulator body has metallized interior and exterior surface portions which are braze sealed to a center conductor and an outer conductive sheath. The end surface of the insulator body which is directed toward the coaxial cable to which it is sealed has a recessed surface portion within which the braze seal material terminates

  7. Static and Dynamic Characteristics of a Long-Span Cable-Stayed Bridge with CFRP Cables

    Directory of Open Access Journals (Sweden)

    Xu Xie

    2014-06-01

    Full Text Available In this study, the scope of CFRP cables in cable-stayed bridges is studied by establishing a numerical model of a 1400-m span of the same. The mechanical properties and characteristics of CFRP stay cables and of a cable-stayed bridge with CFRP cables are here subjected to comprehensive analysis. The anomalies in the damping properties of free vibration, nonlinear parametric vibration and wind fluctuating vibration between steel cables and CFRP cables are determined. The structural stiffness, wind resistance and traffic vibration of the cable-stayed bridge with CFRP cables are also analyzed. It was found that the static performances of a cable-stayed bridge with CFRP cables and steel cables are basically the same. The natural frequencies of CFRP cables do not coincide with the major natural frequencies of the cable-stayed bridge, so the likelihood of CFRP cable-bridge coupling vibration is minuscule. For CFRP cables, the response amplitudes of both parametric vibration and wind fluctuating vibration are smaller than those of steel cables. It can be concluded from the research that the use of CFRP cables does not change the dynamic characteristics of the vehicle-bridge coupling vibration. Therefore, they can be used in long-span cable-stayed bridges with an excellent mechanical performance.

  8. Static and Dynamic Characteristics of a Long-Span Cable-Stayed Bridge with CFRP Cables.

    Science.gov (United States)

    Xie, Xu; Li, Xiaozhang; Shen, Yonggang

    2014-06-23

    In this study, the scope of CFRP cables in cable-stayed bridges is studied by establishing a numerical model of a 1400-m span of the same. The mechanical properties and characteristics of CFRP stay cables and of a cable-stayed bridge with CFRP cables are here subjected to comprehensive analysis. The anomalies in the damping properties of free vibration, nonlinear parametric vibration and wind fluctuating vibration between steel cables and CFRP cables are determined. The structural stiffness, wind resistance and traffic vibration of the cable-stayed bridge with CFRP cables are also analyzed. It was found that the static performances of a cable-stayed bridge with CFRP cables and steel cables are basically the same. The natural frequencies of CFRP cables do not coincide with the major natural frequencies of the cable-stayed bridge, so the likelihood of CFRP cable-bridge coupling vibration is minuscule. For CFRP cables, the response amplitudes of both parametric vibration and wind fluctuating vibration are smaller than those of steel cables. It can be concluded from the research that the use of CFRP cables does not change the dynamic characteristics of the vehicle-bridge coupling vibration. Therefore, they can be used in long-span cable-stayed bridges with an excellent mechanical performance.

  9. Recolonization of macrofauna in unpolluted sands placed in a polluted yachting harbour: A field approach using experimental trays

    Science.gov (United States)

    Guerra-García, J. M.; García-Gómez, J. C.

    2009-01-01

    A field experiment using trays was conducted at Ceuta's yachting harbour, North Africa, to study the effect in recolonization of placing trays with unpolluted defaunate sediments (fine and gross sands with low contents of organic matter) inside an enclosed yachting harbour characterized by high percentages of silt and clay and high concentrations of organic matter. Sediment recolonization in the trays was mainly undertaken by the species living naturally at the yachting harbour, which recolonized both uncontaminated gross and fine sand trays (such as the crustaceans Corophium runcicorne, Corophium sextonae and Nebalia bipes, the mollusc Parvicardium exiguum and the polychaete Pseudomalacoceros tridentata). However, other species like the polychaetes Cirriformia tentaculata and Platynereis dumerilii, although also abundant in the yachting harbour, were unable to colonize the trays through transport of larvae and/or adults in the water column. The recolonization was very quick, and after the first month, the values of abundance, species richness, diversity and evenness were similar in the experimental trays and in the reference area (yachting harbour). Although the multivariate analysis showed that the species composition differed between the trays and the reference area, there were no significant differences in recolonization of gross and fine sands, indicating that other factors different from the granulometry are modulating the recolonization patterns.

  10. Use of slow-release fertilizer on the production of sweet potatoes plantlets in tray

    Directory of Open Access Journals (Sweden)

    Amarílis Beraldo Rós

    2013-12-01

    Full Text Available The production of plantlets in containers generally requires the use of fertilizers. The aim of this study was to evaluate the production of sweet potato in styrofoam trays using slow-release fertilizer. The experiment was carried out, under a screen-protected nursery, in a factorial scheme 5x5, with five doses of slow-release fertilizer NPK 19-06-10 (0, 50, 100, 150 e 200 g per 25 kg de substrate and five times of plantlets permanence in tray (14, 28, 42, 56 and 70 days after planting the cuttings. The number and dry matter of roots and leaves were evaluated. The number of roots was not influenced by fertilizer addition. In general, there is not damage to plantlets growth until the highest dose used. Therefore, the fertilizer addition increases the sweet potato plants growth and the dose of 200 g per 25 kg of substrate is responsible for the best results.

  11. Simulators of tray distillation columns as tools for interpreting gamma-ray scan profile signal

    International Nuclear Information System (INIS)

    Offei-Mensah, P.S.; Gbadago, J.K.; Dagadu, C.P.K.; Danso, K.A.

    2008-01-01

    Simulators of tray distillation columns were used to provide technical guidelines for interpreting signals from gamma ray scans used for analysing malfunctions in distillation columns. The transmitted radiation intensities at 0.05 m intervals were determined from top to bottom of simulators of tray distillation columns exposed to 20 mCi of '1'3'7 Cs. Signals generated from the simulators were identical with the experimental signals obtained from the stabilizer column of the crude oil distillation unit at the Tema Oil Refinery Ghana Limited. Changes in the signal level were observed with changes in diameter, type of material (gasoline, air, debris, steel) and orientation of scan line. The analysis provided accurate interpretation of gamma scan profiles. (au)

  12. The RHIC transfer line cable database

    International Nuclear Information System (INIS)

    Scholl, E.H.; Satogata, T.

    1995-01-01

    A cable database was created to facilitate and document installation of cables and wiring in the RHIC project, as well as to provide a data source to track possible wiring and signal problems. The eight tables of this relational database, currently implemented in Sybase, contain information ranging from cable routing to attenuation of individual wires. This database was created in a hierarchical scheme under the assumption that cables contain wires -- each instance of a cable has one to many wires associated with it. This scheme allows entry of information pertinent to individual wires while only requiring single entries for each cable. Relationships to other RHIC databases are also discussed

  13. Optical Measurement of Cable and String Vibration

    Directory of Open Access Journals (Sweden)

    Y. Achkire

    1998-01-01

    Full Text Available This paper describes a non contacting measurement technique for the transverse vibration of small cables and strings using an analog position sensing detector. On the one hand, the sensor is used to monitor the cable vibrations of a small scale mock-up of a cable structure in order to validate the nonlinear cable dynamics model. On the other hand, the optical sensor is used to evaluate the performance of an active tendon control algorithm with guaranteed stability properties. It is demonstrated experimentally, that a force feedback control law based on a collocated force sensor measuring the tension in the cable is feasible and provides active damping in the cable.

  14. Study on The Effectiveness of Egg Tray and Coir Fibre as A Sound Absorber

    Science.gov (United States)

    Kaamin, Masiri; Farah Atiqah Ahmad, Nor; Ngadiman, Norhayati; Kadir, Aslila Abdul; Razali, Siti Nooraiin Mohd; Mokhtar, Mardiha; Sahat, Suhaila

    2018-03-01

    Sound or noise pollution has become one major issues to the community especially those who lived in the urban areas. It does affect the activity of human life. This excessive noise is mainly caused by machines, traffic, motor vehicles and also any unwanted sounds that coming from outside and even from the inside of the building. Such as a loud music. Therefore, the installation of sound absorption panel is one way to reduce the noise pollution inside a building. The selected material must be a porous and hollow in order to absorb high frequency sound. This study was conducted to evaluate the potential of egg tray and coir fibre as a sound absorption panel. The coir fibre has a good coefficient value which make it suitable as a sound absorption material and can replace the traditional material; syntactic and wooden material. The combination of pyramid shape of egg tray can provide a large surface for uniform sound reflection. This study was conducted by using a panel with size 1 m x 1 m with a thickness of 6 mm. This panel consist of egg tray layer, coir fibre layer and a fabric as a wrapping for the aesthetic value. Room reverberation test has been carried to find the loss of reverberation time (RT). Result shows that, a reverberation time reading is on low frequency, which is 125 Hz to 1600 Hz. Within these frequencies, this panel can shorten the reverberation time of 5.63s to 3.60s. Hence, from this study, it can be concluded that the selected materials have the potential as a good sound absorption panel. The comparison is made with the previous research that used egg tray and kapok as a sound absorption panel.

  15. Scanning electron microscope/energy dispersive x ray analysis of impact residues in LDEF tray clamps

    Science.gov (United States)

    Bernhard, Ronald P.; Durin, Christian; Zolensky, Michael E.

    1993-01-01

    Detailed optical scanning of tray clamps is being conducted in the Facility for the Optical Inspection of Large Surfaces at JSC to locate and document impacts as small as 40 microns in diameter. Residues from selected impacts are then being characterized by Scanning Electron Microscopy/Energy Dispersive X-ray Analysis at CNES. Results from this analysis will be the initial step to classifying projectile residues into specific sources.

  16. Neutron coincidence counter for MOX fuel pins in storage trays: users' manual

    International Nuclear Information System (INIS)

    Cowder, L.; Menlove, H.

    1982-08-01

    The neutron coincidence counter for measurement of mixed-oxide fuel pins in storage trays is described. The special detector head has been designed so that the detectors, high-voltage junction boxes, and electronics are interchangeable with those of the high-level neutron coincidence counter system. This manual describes the system components and the operation and maintenance of the counter. The counter was developed at Los Alamos National Laboratory for in-plant inspection applications by the International Atomic Energy Agency

  17. Study on The Effectiveness of Egg Tray and Coir Fibre as A Sound Absorber

    Directory of Open Access Journals (Sweden)

    Kaamin Masiri

    2018-01-01

    Full Text Available Sound or noise pollution has become one major issues to the community especially those who lived in the urban areas. It does affect the activity of human life. This excessive noise is mainly caused by machines, traffic, motor vehicles and also any unwanted sounds that coming from outside and even from the inside of the building. Such as a loud music. Therefore, the installation of sound absorption panel is one way to reduce the noise pollution inside a building. The selected material must be a porous and hollow in order to absorb high frequency sound. This study was conducted to evaluate the potential of egg tray and coir fibre as a sound absorption panel. The coir fibre has a good coefficient value which make it suitable as a sound absorption material and can replace the traditional material; syntactic and wooden material. The combination of pyramid shape of egg tray can provide a large surface for uniform sound reflection. This study was conducted by using a panel with size 1 m x 1 m with a thickness of 6 mm. This panel consist of egg tray layer, coir fibre layer and a fabric as a wrapping for the aesthetic value. Room reverberation test has been carried to find the loss of reverberation time (RT. Result shows that, a reverberation time reading is on low frequency, which is 125 Hz to 1600 Hz. Within these frequencies, this panel can shorten the reverberation time of 5.63s to 3.60s. Hence, from this study, it can be concluded that the selected materials have the potential as a good sound absorption panel. The comparison is made with the previous research that used egg tray and kapok as a sound absorption panel.

  18. Fabrication of customized sectional impression trays in management of patients with limited mouth opening: a simple and unique approach.

    Science.gov (United States)

    Krishna Ch, Vamsi; Mahendranadh Reddy, K; Gupta, Nidhi; Mahadev Shastry, Y; Chandra Sekhar, N; Aditya, Venkat; Reddy, G V K Mohan

    2013-01-01

    Impression making is not only important but is also the most significant step in the fabrication of any fixed or removable prosthesis. Proper impression making may be hindered by certain pathologic conditions. Reduced mouth opening is one of the common mechanical obstructions for proper orientation of the impression tray in the patient's mouth. In patients with trismus induced by submucous fibrosis, the procedure may be even more difficult to carry out because of reduced tissue resiliency and obliteration of vestibular spaces. Use of sectional trays offers one of the alternatives to overcome the problem of restricted mouth opening. Fabrication of customized impression trays according to the patient dentition improves the accuracy of impression making. The present case reports describe the fabrication of sectional custom trays designed for dentulous patients with chronic tobacco-induced submucous fibrosis.

  19. Combat Ration Network for Technology Implementation. Polymeric Tray Manufacturability, Part 2 (Short Term Project - STP1002B)

    National Research Council Canada - National Science Library

    Bruins, Henderikus

    1999-01-01

    .... Therefore, a second Polymeric Tray Manufacturability at the CORANET Demonstration Site at Rutgers University Food Manufacturing Technology Facility was conducted on June 9-10, 1998 to specifically address these issues...

  20. Static and Dynamic Mechanical Properties of Long-Span Cable-Stayed Bridges Using CFRP Cables

    Directory of Open Access Journals (Sweden)

    Mei Kuihua

    2017-01-01

    Full Text Available The elastic modulus and deadweight of carbon fiber-reinforced polymer (CFRP cables are different from those of steel cables. Thus, the static and dynamic behaviors of cable-stayed bridges using CFRP cables are different from those of cable-stayed bridges using steel cables. The static and dynamic performances of the two kinds of bridges with a span of 1000 m were studied using the numerical method. The effects of geometric nonlinear factors on static performance of the two kinds of cable-stayed bridges were analyzed. The live load effects and temperature effects of the two cable-stayed bridges were also analyzed. The influences of design parameters, including different structural systems, the numbers of auxiliary piers, and the space arrangement types of cable, on the dynamic performance of the cable-stayed bridge using CFRP cables were also studied. Results demonstrate that sag effect of the CFRP cable is much smaller than that of steel cable. The temperature effects of CFRP cable-stayed bridge are less than those of steel cable-stayed bridge. The vertical bending natural vibration frequency of the CFRP cable-stayed bridge is generally lower than that of steel cable-stayed bridge, whereas the torsional natural vibration frequency of the former is higher than that of the latter.

  1. Treatability test of a stacked-tray air stripper for VOC in water

    Energy Technology Data Exchange (ETDEWEB)

    Pico, T., LLNL

    1998-04-01

    A common strategy for hydraulic containment and mass removal at VOC contaminated sites is `pump and treat (P&T)`. In P&T operations, contaminated ground water is pumped from wells, treated above ground, and discharged. Many P&T remediation systems at VOC sites rely on air stripping technology because VOCs are easily transferred to the vapor phase. In stacked-tray air strippers, contaminated water is aerated while it flows down through a series of trays. System operations at LLNL are strictly regulated by the California and federal Environmental Protection Agencies (Cal/EPA and EPA), the Bay Area Air Quality Management District (BAAQMD), the California Regional Water Quality Control Board (RWQCB) and the Department of Toxic Substances Control (DTSC). These agencies set discharge limits, require performance monitoring, and assess penalties for non-compliance. National laboratories are also subject to scrutiny by the public and other government agencies. This extensive oversight makes it necessary to accurately predict field treatment performance at new extraction locations to ensure compliance with all requirements prior to facility activation. This paper presents treatability test results for a stacked- tray air stripper conducted at LLNL and compares them to the vendor`s modeling software results.

  2. Umbilical Cable Recovery Load Analysis

    Institute of Scientific and Technical Information of China (English)

    YAN Shu-wang; JIA Zhao-lin; FENG Xiao-wei; LI Shi-tao

    2013-01-01

    Umbilical cable is a kind of integrated subsea cable widely used in the exploration and exploitation of oil and gas field.The severe ocean environment makes great challenges to umbilical maintenance and repair work.Damaged umbilical is usually recovered for the regular operation of the offshore production system.Analysis on cables in essence is a two-point boundary problem.The tension load at the mudline must be known first,and then the recovery load and recovery angle on the vessel can be solved by use of catenary equation.The recovery analysis also involves umbilicalsoil interaction and becomes more complicated.Calculation methods for recovery load of the exposed and buried umbilical are established and the relationship between the position of touch down point and the recovery load as well as the recovery angle and recovery load are analyzed.The analysis results provide a theoretical reference for offshore on-deck operation.

  3. Online Cable Tester and Rerouter

    Science.gov (United States)

    Lewis, Mark; Medelius, Pedro

    2012-01-01

    Hardware and algorithms have been developed to transfer electrical power and data connectivity safely, efficiently, and automatically from an identified damaged/defective wire in a cable to an alternate wire path. The combination of online cable testing capabilities, along with intelligent signal rerouting algorithms, allows the user to overcome the inherent difficulty of maintaining system integrity and configuration control, while autonomously rerouting signals and functions without introducing new failure modes. The incorporation of this capability will increase the reliability of systems by ensuring system availability during operations.

  4. Data Base On Cables And Connectors

    Science.gov (United States)

    Bowen, Arlen R.; Oliver, John D.

    1995-01-01

    Report describes Connector Adapter Cable Information Data Base (CONNAID) computer program, managing data base containing necessary information concerning electrical connectors, breakout boxes, adapter cables, backshells, and pertinent torque specifications for engineering project.

  5. OTEC riser cable model and prototype testing

    Science.gov (United States)

    Kurt, J. P.; Schultz, J. A.; Roblee, L. H. S.

    1981-12-01

    Two different OTEC riser cables have been developed to span the distance between a floating OTEC power plant and the ocean floor. The major design concerns for a riser cable in the dynamic OTEC environment are fatigue, corrosion, and electrical/mechanical aging of the cable components. The basic properties of the cable materials were studied through tests on model cables and on samples of cable materials. Full-scale prototype cables were manufactured and were tested to measure their electrical and mechanical properties and performance. The full-scale testing was culminated by the electrical/mechanical fatigue test, which exposes full-scale cables to simultaneous tension, bending and electrical loads, all in a natural seawater environment.

  6. 30 CFR 7.407 - Test for flame resistance of electric cables and cable splices.

    Science.gov (United States)

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Test for flame resistance of electric cables... Electric Cables, Signaling Cables, and Cable Splice Kits § 7.407 Test for flame resistance of electric... material and 21/2 inches of conductor insulation. The type, amperage, voltage rating, and construction of...

  7. Preliminary design, construction and evaluation of robot of tomato seed planting for the trays of greenhouse

    Directory of Open Access Journals (Sweden)

    J Ghezavati

    2015-09-01

    Full Text Available Introduction: From an economic viewpoint, tomato is considered as the second most valuable crop after potato. It is also preceded by the potato in terms of per capita consumption in the world. In 2008, the cultivation area used for the tomato as equal to 163,539 hectares in Iran and the production of it was equal to 5,887,715 tons with an average production of 117,887 tons in 4352 hectares in the provinces, respectively. Having high production volume and quality, costly hybrid seeds are currently used for the major planting areas of vegetable in Iran. Most of the used transplanted seedlings are 83%. Since the seeds are expensive, the percentage of seedlings and healthy and disease-free seeds should be used for maximized germination and be transferred to the fields of open space. Preparing seedlings in transplanting trays is a technology to respond to this need. Trays are covered with a layer of Peat and Miculite fertilizers. Then, one seed is manually placed in each cell after gauging and preparing a suitable field. However, manually placing seeds is time-consuming and requires hard labor. Sixteen working labors per hour are required for 15 × 7 cell in order to have 10200 seedlings grown in 100 trays. Due to lack of adequate labor, production capacity of greenhouses is reduced, especially in the farming season when finding labor for planting vegetable sprouts is laborious. Therefore, mechanizing tray seeding operations is essential to increase the capacity of the growing industry of greenhouses in Iran. Materials and Methods: Initially, the tomato seeds were examined in the laboratory. The most important parameters of the study included size, shape, weight, the speed of getting out of the tank and the minimum carrying speed. Then, a vacuum-based single seed picking unit was prepared to investigate the factors influencing the design, so that a single tomato seed can be harvested from the masses. The most important factors considered in the

  8. Trenchless Replacement of Buried Cable Lines

    Directory of Open Access Journals (Sweden)

    Hans-Joachim Bayer

    2007-01-01

    Full Text Available An enormous amount of underground electricity and telecommunication cables have been worn over the time with technical defects or need capacity increases. Thus, new lines need to be installed. In urban areas, even in smaller communities and in natural reserves, open trenching is difficult and often not permitted.In response, new patented methods of trenchless cable replacement using the HDD equipment have been developed by the TT Group. The new technology is called “Wash-over-cable-replacement” and applies specially designed drill heads, cutting around the old cable string in various configurations (completely closed, U-shape or S-shape embracing, depending to the coating type of the old cable. This special cable replacement drill head separates the cable from the surrounding adhesive soil or the sand bedding by creating a very small annular space around the cable thus enabling the pulling or dragging out of the old cable section between the start and the exit pit. After the old cable has been loosened from the surrounding soil by means of the wash over process and pulled out, the new cable can be smoothly pulled into the void using the drill rods and embedding the new cable in a rich bed of Bentonite.The wash-over drill heads are slim and have inner and outer nozzles for Bentonite and bits to handle roots, pebbles, gravel and the like. These drill heads perform very quickly (up to 3 meters per minute to effectively wash over existing cables without damaging the cable coating and prepare the ground for a fast new laying of a new cable in the existing line. Network owners also benefit from the fact that new geodetic or topographic surveys and documentations of the new cable are not necessary. Only the documents, remarks, technical codes and existing geodetic data need to be updated.The paper will outline the technological background and include several practical job examples.

  9. Active optical cable for intrasatellite communications

    Science.gov (United States)

    Blasco, J.; Cano, D.; Navasquillo, O.; Esteban, M. A.

    2017-11-01

    DAS Photonics and Airbus Defence and Space (Spain) have been working for more than six years in the concept of an Active Optical Cable (AOC) for copper cable substitution. The main advantages that AOC offers are significant mass and size saving, better flexibility and routing of the cable and immunity to EMI.

  10. Cable Television Report and Suggested Ordinance.

    Science.gov (United States)

    League of California Cities, Sacramento.

    Guidelines and suggested ordinances for cable television regulation by local governments are comprehensively discussed in this report. The emphasis is placed on franchising the cable operator. Seventeen legal aspects of franchising are reviewed, and an exemplary ordinance is presented. In addition, current statistics about cable franchising in…

  11. Remote Acquisition Amplifier For 50-Ohm Cable

    Science.gov (United States)

    Amador, Jose J.

    1995-01-01

    Buffer-amplifier unit designed to drive 50-Ohm cables up to 100 ft. (30 m) long, compensating for attenuation in cables and enabling remote operation of oscilloscopes. Variable resistor provides for adjustment of gain of amplifier, such that overall gain from input terminals of amplifier to output end of cable set to unity.

  12. 300 Area signal cable study

    International Nuclear Information System (INIS)

    Whattam, J.W.

    1994-01-01

    This report was prepared to discuss the alternatives available for removing the 300 Area overhead signal cable system. This system, installed in 1969, has been used for various monitoring and communication signaling needs throughout the 300 Area. Over the years this cabling system has deteriorated, has been continually reconfigured, and has been poorly documented to the point of nonreliability. The first step was to look at the systems utilizing the overhead signal cable that are still required for operation. Of the ten systems that once operated via the signal cable, only five are still required; the civil defense evacuation alarms, the public address (PA) system, the criticality alarms, the Pacific Northwest Laboratory Facilities Management Control System (FMCS), and the 384 annunciator panel. Of these five, the criticality alarms and the FMCS have been dealt with under other proposals. Therefore, this study focused on the alternatives available for the remaining three systems (evacuation alarms, PA system, and 384 panel) plus the accountability aid phones. Once the systems to be discussed were determined, then three alternatives for providing the signaling pathway were examined for each system: (1) re-wire using underground communication ducts, (2) use the Integrated Voice/Data Telecommunications System (IVDTS) already installed and operated by US West, and (3) use radio control. Each alternative was developed with an estimated cost, advantages, and disadvantages. Finally, a recommendation was provided for the best alternative for each system

  13. Arrangement for guiding transport cables

    International Nuclear Information System (INIS)

    1981-01-01

    This patent relates especially to x-ray equipment such as that used for computerized tomography, and in particular to an arrangement for guiding and supporting a plurality of power transmission cables and cooling hoses in a flexible manner. (U.K.)

  14. Selecting a Cable System Operator.

    Science.gov (United States)

    Cable Television Information Center, Washington, DC.

    Intended to assist franchising authorities with the process of selecting a cable television system operator from franchise applicants, this document provides a framework for analysis of individual applications. Section 1 deals with various methods which can be used to select an operator. The next section covers the application form, the vehicle a…

  15. Offshore Cable Installation - Lillgrund. Lillgrund Pilot Project

    Energy Technology Data Exchange (ETDEWEB)

    Unosson, Oscar [Vattenfall Vindkraft AB, Stockholm (Sweden)

    2009-01-15

    This report describes the installation method and the experiences gained during the installation of the submarine cables for the offshore wind farm at Lillgrund. The wind farm consists of 48 wind turbines and is expected to produce 0.33 TWh annually. Different aspects of the installation, such as techniques, co-operation between the installation teams, weather conditions and regulatory and environmental issues are described in this report. In addition, recommendations and guidelines are provided, which hopefully can be utilised in future offshore wind projects. The trenches, in which the submarine cables were laid, were excavated weeks before the cable laying. This installation technique proved to be successful for the laying of the inter array cables. The export cable, however, was laid into position with difficulty. The main reason why the laying of the export cable proved more challenging was due to practical difficulties connected with the barge entrusted with the cable laying, Nautilus Maxi. The barge ran aground a number of times and it had difficulties with the thrusters, which made it impossible to manoeuvre. When laying the inter array cables, the method specification was closely followed, and the laying of the cables was executed successfully. The knowledge and experience gained from the offshore cable installation in Lillgrund is essential when writing technical specifications for new wind plant projects. It is recommended to avoid offshore cable installation work in winter seasons. That will lower the chances of dealing with bad weather and, in turn, will reduce the risks

  16. Computational study of the heat transfer of an avian egg in a tray.

    Science.gov (United States)

    Eren Ozcan, S; Andriessens, S; Berckmans, D

    2010-04-01

    The development of an embryo in an avian egg depends largely on its temperature. The embryo temperature is affected by its environment and the heat produced by the egg. In this paper, eggshell temperature and the heat transfer characteristics from one egg in a tray toward its environment are studied by means of computational fluid dynamics (CFD). Computational fluid dynamics simulations have the advantage of providing extensive 3-dimensional information on velocity and eggshell temperature distribution around an egg that otherwise is not possible to obtain by experiments. However, CFD results need to be validated against experimental data. The objectives were (1) to find out whether CFD can successfully simulate eggshell temperature from one egg in a tray by comparing to previously conducted experiments, (2) to visualize air flow and air temperature distribution around the egg in a detailed way, and (3) to perform sensitivity analysis on several variables affecting heat transfer. To this end, a CFD model was validated using 2 sets of temperature measurements yielding an effective model. From these simulations, it can be concluded that CFD can effectively be used to analyze heat transfer characteristics and eggshell temperature distribution around an egg. In addition, air flow and temperature distribution around the egg are visualized. It has been observed that temperature differences up to 2.6 degrees C are possible at high heat production (285 mW) and horizontal low flow rates (0.5 m/s). Sensitivity analysis indicates that average eggshell temperature is mainly affected by the inlet air velocity and temperature, flow direction, and the metabolic heat of the embryo and less by the thermal conductivity and emissivity of the egg and thermal emissivity of the tray.

  17. Development of an integrated, unattended assay system for LWR-MOX fuel pellet trays

    International Nuclear Information System (INIS)

    Stewart, J.E.; Hatcher, C.R.; Pollat, L.L.

    1994-01-01

    Four identical unattended plutonium assay systems have been developed for use at the new light-water-reactor mixed oxide (LWR-MOX) fuel fabrication facility at Hanau, Germany. The systems provide quantitative plutonium verification for all MOX pellet trays entering or leaving a large, intermediate store. Pellet-tray transport and storage systems are highly automated. Data from the ''I-Point'' (information point) assay systems will be shared by the Euratom and International Atomic Energy Agency (IAEA) Inspectorates. The I-Point system integrates, for the first time, passive neutron coincidence counting (NCC) with electro-mechanical sensing (EMS) in unattended mode. Also, provisions have been made for adding high-resolution gamma spectroscopy. The system accumulates data for every tray entering or leaving the store between inspector visits. During an inspection, data are analyzed and compared with operator declarations for the previous inspection period, nominally one month. Specification of the I-point system resulted from a collaboration between the IAEA, Euratom, Siemens, and Los Alamos. Hardware was developed by Siemens and Los Alamos through a bilateral agreement between the German Federal Ministry of Research and Technology (BMFT) and the US DOE. Siemens also provided the EMS subsystem, including software. Through the USSupport Program to the IAEA, Los Alamos developed the NCC software (NCC COLLECT) and also the software for merging and reviewing the EMS and NCC data (MERGE/REVIEW). This paper describes the overall I-Point system, but emphasizes the NCC subsystem, along with the NCC COLLECT and MERGE/REVIEW codes. We also summarize comprehensive testing results that define the quality of assay performance

  18. Scanning electron microscope/energy dispersive x ray analysis of impact residues on LDEF tray clamps

    Science.gov (United States)

    Bernhard, Ronald P.; Durin, Christian; Zolensky, Michael E.

    1992-01-01

    To better understand the nature of particulates in low-Earth orbit (LEO), and their effects on spacecraft hardware, we are analyzing residues found in impacts on the Long Duration Exposure Facility (LDEF) tray clamps. LDEF experiment trays were held in place by 6 to 8 chromic-anodized aluminum (6061-T6) clamps that were fastened to the spacecraft frame using three stainless steel hex bolts. Each clamp exposed an area of approximately 58 sq cm (4.8 cm x 12.7 cm x .45 cm, minus the bolt coverage). Some 337 out of 774 LDEF tray clamps were archived at JSC and are available through the Meteoroid & Debris Special Investigation Group (M&D SIG). Optical scanning of clamps, starting with Bay/Row A01 and working toward H25, is being conducted at JSC to locate and document impacts as small as 40 microns. These impacts are then inspected by Scanning Electron Microscopy/Energy Dispersive X-ray Analysis (SEM/EDXA) to select those features which contain appreciable impact residue material. Based upon the composition of projectile remnants, and using criteria developed at JSC, we have made a preliminary discrimination between micrometeoroid and space debris residue-containing impact features. Presently, 13 impacts containing significant amounts of unmelted and semi-melted micrometeoritic residues were forwarded to Centre National d'Etudes Spatiales (CNES) in France. At the CNES facilities, the upgraded impacts were analyzed using a JEOL T330A SEM equipped with a NORAN Instruments, Voyager X-ray Analyzer. All residues were quantitatively characterized by composition (including oxygen and carbon) to help understand interplanetary dust as possibly being derived from comets and asteroids.

  19. Experimental Evaluation of Pool Fire Suppression Performance of Sodium Leak Collection Tray in Open Air

    International Nuclear Information System (INIS)

    Parida, F.C.; Rao, P.M.; Ramesh, S.S.; Malarvizhi, B.; Gopalakrishnan, V.; Rao, E.H.V.M.; Kasinathan, N.; Kannan, S.E.

    2006-01-01

    In the event of sodium leakage from heat transfer circuits of fast breeder reactors (FBR), liquid sodium catches fire in ambient air leading to production of flame, smoke and heat. One of the passive fire protection methods involves immediate collection of the leaking sodium to a sodium hold-up vessel (SHV) covered with a sloping cover tray (SCT) having a few drain pipes and one vent pipe (as in Fig. 1). As soon as the liquid sodium falls on the sloping cover tray, gravity guides the sodium through drain pipes into the bottom tray in which self-extinction occurs due to oxygen starvation. This sodium fire protection equipment called leak collection tray (LCT) works without the intervention of an operator and external power source. A large number of LCTs are strategically arranged under the sodium circulating pipe lines in the FBR plants to serve as passive suppression devices. In order to test the efficacy of the LCT, four tests were conducted. Two tests were with LCT having three drain pipes and rest with one. In each experiment, nearly 40 kg of hot liquid sodium at 550 deg. C was discharged on the LCT in the open air. Continuous on-line monitoring of temperature at strategic locations (∼ 28 points) were carried out. Colour video-graphy was employed for taking motion pictures of various time-dependent events like sodium dumping, appearance of flame and release of smoke through vent pipes. After self-extinction of sodium fire, the LCT was allowed to cool overnight in an argon atmosphere. Solid samples of sodium debris in the SCT and SHV were collected by manual core drilling machine. The samples were subjected to chemical analysis for determination of unburnt and burnt sodium. The results of the four tests revealed an interesting feature: LCT with three drain pipes showed far lower sodium collection efficiency and much higher sodium combustion than that with just one drain pipe. Thermal fluctuations in temperature sensor located near the tip of the drain pipe have

  20. Modeling Separation Dynamics in a Multi-Tray Bio-Ethanol Distillation Column

    DEFF Research Database (Denmark)

    Løhndorf, Petar Durdevic; Pedersen, Simon; Yang, Zhenyu

    2015-01-01

    the product quality and energy consumption in a typical bio-ethanol distillation column is proposed in this paper. The proposed model is derived based on mass and energy balance principles, with an empirical model of the evaporation dynamics of liquids on column trays. The model parameters are identified......The high energy consumption of popularly used distillation columns has motivated development of energytracking dynamic models with the ultimate objective for potential better energy and quality control of these separation facilities. A dynamic model being able to explicitly describe both...

  1. Evaluation of the bone microstructures after the mandibular reconstruction, using bioresorbable hydroxyapatite/poly-L-lactide mesh tray and the particulate cancellous bone

    International Nuclear Information System (INIS)

    Takahashi, Hidetoshi; Matsuo, Akira; Chiba, Hiroshige

    2010-01-01

    The combination of particulate cancellous bone and marrow (PCBM) and a titanium tray is frequently used for mandibular reconstruction. However, there are difficulties in bending the tray and forming a suitable contour. In addition, the metallic ions elute into the living body and the hinders the implant insertion; therefore, a removable operation is required after reconstruction. Hydroxyapatite/poly-L-lactide (HA/PLLA) is a bone-bonding material that has both bio-activity and bio-resorbability. It may overcome the weakness of a titanium tray, but the bone microstructures have not been evaluated after the use of this tray for PCBM reconstruction. We created defects on the mandible of a beagle and reconstructed it by filling it with a mixture of PCBM and PRP using the HA/PLLA tray. We examined the bone-formation mechanism using a confocal laser microscope and bone microstructural analysis using microCT. As a result, compared to the titanium tray, the bone-formation is delayed during the first 3 to 6 months with an HA/PLLA tray. However, a formation of new bone with equal quality is observed after 12 months. According to the bone microstructural measurement, both of them had higher bone volume fraction than the native bone but other parameters were the same. From the above, the quantity of the new bone in the HA/PLLA tray is the same as the bone in the titanium tray, and has equal bone microstructures with the surrounding native bone. (author)

  2. Tubing and cable cutting tool

    Science.gov (United States)

    Mcsmith, D. D.; Richardson, J. I. (Inventor)

    1984-01-01

    A hand held hydraulic cutting tool was developed which is particularly useful in deactivating ejection seats in military aircraft rescue operations. The tool consists primarily of a hydraulic system composed of a fluid reservoir, a pumping piston, and an actuator piston. Mechanical cutting jaws are attached to the actuator piston rod. The hydraulic system is controlled by a pump handle. As the pump handle is operated the actuator piston rod is forced outward and thus the cutting jaws are forced together. The frame of the device is a flexible metal tubing which permits easy positioning of the tool cutting jaws in remote and normally inaccessible locations. Bifurcated cutting edges ensure removal of a section of the tubing or cable to thereby reduce the possibility of accidental reactivation of the tubing or cable being severed.

  3. Electromagnetic Transients in Power Cables

    DEFF Research Database (Denmark)

    Silva, Filipe Faria Da; Bak, Claus Leth

    . The chapter ends by proposing a systematic method that can be used when doing the insulation co-ordination study for a line, as well as the modelling requirements, both modelling depth and modelling detail of the equipment, for the study of the different types of transients followed by a step-by-step generic...... typically used for the screens of cables (both-ends bonding and cross-boding) and also presents methods that can be used to estimate the maximum current of a cable for different types of soils, i.e. thermal calculations. The end of the chapter introduces the shunt reactor, which is an important element...... detail of the equipment, for the study of the different types of transients followed by a step-by-step generic example....

  4. Exposure to antimony from polyethylene terephthalate (PET) trays used in ready-to-eat meals.

    Science.gov (United States)

    Haldimann, M; Blanc, A; Dudler, V

    2007-08-01

    Antimony residues, a result of the use of a polycondensation catalyst in the production of polyethylene terephthalate (PET) oven-proof trays, were analysed in ready-to-eat meals. The toxicity of antimony has raised concerns about consumer safety; therefore, the migration of small fractions of these residues into ready meals and foods as a result of cooking directly in the PET trays was studied. A straightforward approach of measuring real samples was selected to obtain accurate exposure data. Background antimony concentration was determined separately from a series of lunch meals, which ranged from not detectable to 3.4 microg kg(-1). Microwave and conventional oven-cooking caused a distinct increase in the concentration of antimony in food and ready meals of 0-17 and 8-38 microg kg(-1), respectively, depending, to a certain extent, on the industrial preparations. The migrated quantities of antimony corresponded to 3-13 microg. For comparison, PET roasting bags and ready-made dough products in PET baking dishes were also evaluated. About half of the products prepared at a temperature of 180 degrees C exceeded the specific migration limit set for food contact material by the European Commission. However, the migrated amounts of antimony relative to the accepted tolerable daily intake (TDI) show that exposure from this type of food is currently not of toxicological concern.

  5. Sintesis Bahan Dasar Tibial Tray Berbasis HDPE Yang Diperkuat Dengan Iradiasi Gamma

    Directory of Open Access Journals (Sweden)

    Sulistioso Giat S.

    2014-04-01

    Full Text Available Tibial tray yang sudah komersil dibuat dari Polimer Ultra High Molecular Weight Polyethylene (UHMWPE tetapi harganya sangat mahal. Oleh karena itu pada penelitian ini digunakan polimer High Density Polyethylene (HDPE untuk pembuatan tibial tray karena harganya yang lebih murah dan memiliki kemiripan sifat dengan UHMWPE. HDPE dibuat dengan dua metode, yaitu metode hot press dan pemanasan tanpa tekanan (PTT. UHMWPE dengan metode hot press digunakan sebagai pembanding. Metode hot press dilakukan pada suhu 180 °C dan diberi tekanan sebesar 200 kg/cm2. Sedangkan metode pemanasan tanpa tekanan (PTT dilakukan di dalam oven pada suhu 180°C. Film tipis UHMWPE dan sampel HDPE yang dihasilkan dari kedua metode tersebut, kemudian diiradiasi sinar gamma dengan variasi dosis 0, 100, 200, 300 dan 500 kGy. Karakterisasi mencakup analisis morfologi dengan Scanning Electron Microscope (SEM, uji kekerasan, kekuatan tarik, dan derajat kristalinitas. Semakin tinggi dosis radiasi, maka kekerasan dan derajat kristalinitas semakin meningkat, tetapi kekuatan tarik semakin menurun. Dosis radiasi untuk sampel HDPE yang optimum , adalah 100 kGy untuk HDPE yang dibuat dengan metoda hot press, pada kondisi ini HDPE mempunyai kekuatan mekanik mendekati nilai kekuatan mekanik UHMWPE, sedangkan HDPE yang dibuat dengan metode PTT kekuatan mekaniknya masih dibawah kekuatan mekanik HDPE yang dibuat dengan metoda hot press 

  6. Comparison study of cable geometries and superconducting tape layouts for high-temperature superconductor cables

    Science.gov (United States)

    Ta, Wurui; Shao, Tianchong; Gao, Yuanwen

    2018-04-01

    High-temperature superconductor (HTS) rare-earth-barium-copper-oxide (REBCO) tapes are very promising for use in high-current cables. The cable geometry and the layout of the superconducting tapes are directly related to the performance of the HTS cable. In this paper, we use numerical methods to perform a comparison study of multiple-stage twisted stacked-tape cable (TSTC) conductors to find better cable structures that can both improve the critical current and minimize the alternating current (AC) losses of the cable. The sub-cable geometry is designed to have a stair-step shape. Three superconducting tape layouts are chosen and their transport performance and AC losses are evaluated. The magnetic field and current density profiles of the cables are obtained. The results show that arrangement of the superconducting tapes from the interior towards the exterior of the cable based on their critical current values in descending order can enhance the cable's transport capacity while significantly reducing the AC losses. These results imply that cable transport capacity improvements can be achieved by arranging the superconducting tapes in a manner consistent with the electromagnetic field distribution. Through comparison of the critical currents and AC losses of four types of HTS cables, we determine the best structural choice among these cables.

  7. An industrial cabling machine for the SSC

    International Nuclear Information System (INIS)

    Royet, J.; Armer, R.; Hannaford, R.; Scanlan, R.

    1989-02-01

    The SSC project will need the manufacturing of some 25,000 kilometers of keystoned flat cable. The technical specifications of the various cables to be produced are the result of five years of research and development work at LBL. An experimental cable machine was built and run in the laboratory; many improvements were implemented and tested. Semi-industrial production of the various cables was performed, and the resulting cables were used and tested in the one-meter model magnets and 17.5 meter dipole prototypes. From these experiments an industrial cabler specification was generated and used for an international RFQ. The winner of the contract is Dour Metal, a Belgium company that built the first industrial prototype which is now in a production line at New England Electric Wire Company. In this paper we describe the main characteristics of the machine and give the first industrial production results of superconducting keystoned cable for the SSC project. 4 refs

  8. Initial tension loss in cerclage cables.

    Science.gov (United States)

    Ménard, Jérémie; Émard, Maxime; Canet, Fanny; Brailovski, Vladimir; Petit, Yvan; Laflamme, George Y

    2013-10-01

    Cerclage cables, frequently used in the management of fractures and osteotomies, are associated with a high failure rate and significant loosening during surgery. This study compared the capacity to maintain tension of different types of orthopaedic cable systems. Multifilament Cobalt-Chrome (CoCr) cables with four different crimp/clamp devices (DePuy, Stryker, Zimmer and Smith&Nephew) and one non-metallic Nylon (Ny) cable from Kinamed were instrumented with a load cell to measure tension during insertion. Significant tension loss was observed with crimping for all cables (Ptensioner led to an additional unexpected tension loss (CoCr-DePuy: 18%, CoCr-Stryker: 29%, CoCr-Smith&Nephew: 33%, Ny: 46%, and CoCr-Zimmer: 52%). The simple CoCr (DePuy) cable system outperformed the more sophisticated locking devices due to its significantly better ability to prevent tension loss. Copyright © 2013 Elsevier Inc. All rights reserved.

  9. Fatigue of cable anchorage of large cable stayed bridge; Daikibo shachokyo cable teichaku kozo no hiro

    Energy Technology Data Exchange (ETDEWEB)

    Endo, T.; Matsumoto, T. [Honshu-Shikoku Bridge Authority, Tokyo (Japan); Tsukahara, H. [Yokogawa Bridge Corp., Tokyo (Japan); Miki, C. [Tokyo Institute of Technology, Tokyo (Japan)

    1995-10-21

    Design considerations such as design schemes, the assemblage and welding of steel plates, and safety for fatigue of welded connections have to be taken for the cable anchorages of the steel cable stayed bridges. In this study, two full scale models, which have different shape of box anchorages welded to the web of the main girder, were made to investigate fatigue characteristics as well as assemblage of plate and gelding details. Finite element analyses for both test models and actual bridges here carried out to compare stress distribution. It was confirmed that the assemblage and welding of both types of box anchorage were attainable kith required quality and accuracy. According to the fatigue test, fatigue cracks originated from the weldings of the bearing plate to which the load from cable socket applied directly were caused by out-of-plane bending of the bearing plate. It was proved that the slight modifications of the details around the bearing plate resulted in sufficient fatigue strength in both types of anchorage. 1 ref., 23 figs., 2 tabs.

  10. 47 CFR 76.802 - Disposition of cable home wiring.

    Science.gov (United States)

    2010-10-01

    ... 47 Telecommunication 4 2010-10-01 2010-10-01 false Disposition of cable home wiring. 76.802... MULTICHANNEL VIDEO AND CABLE TELEVISION SERVICE Cable Inside Wiring § 76.802 Disposition of cable home wiring. (a)(1) Upon voluntary termination of cable service by a subscriber in a single unit installation, a...

  11. Low Friction Cryostat for HTS Power Cable of Dutch Project

    NARCIS (Netherlands)

    Chevtchenko, O.; Zuijderduin, R.; Smit, J.; Willen, D.; Lentge, H.; Thidemann, C.; Traeholt, C.

    2012-01-01

    Particulars of 6 km long HTS AC power cable for Amsterdam project are: a cable has to fit in an annulus of 160 mm, with only two cooling stations at the cable ends [1]. Application of existing solutions for HTS cables would result in excessively high coolant pressure drop in the cable, possibly

  12. Field application of a cable NDT system for cable-stayed bridge using MFL sensors integrated

    Energy Technology Data Exchange (ETDEWEB)

    Kim, Ju Won; Choi, Jun Sung; Park, Seung Hee [Sungkyunkwan University, Seoul (Korea, Republic of); Lee, Eun Chan [Korea Maintance Co., Ltd., Seoul (Korea, Republic of)

    2014-02-15

    In this study, an automated cable non-destructive testing(NDT) system was developed to monitor the steel cables that are a core component of cable-stayed bridges. The magnetic flux leakage(MFL) method, which is suitable for ferromagnetic continuum structures and has been verified in previous studies, was applied to the cable inspection. A multi-channel MFL sensor head was fabricated using hall sensors and permanent magnets. A wheel-based cable climbing robot was fabricated to improve the accessibility to the cables, and operating software was developed to monitor the MFL-based NDT research and control the climbing robot. Remote data transmission and robot control were realized by applying wireless LAN communication. Finally, the developed element techniques were integrated into an MFL-based cable NDT system, and the field applicability of this system was verified through a field test at Seohae Bridge, which is a typical cable-stayed bridge currently in operation.

  13. Field application of a cable NDT system for cable-stayed bridge using MFL sensors integrated

    International Nuclear Information System (INIS)

    Kim, Ju Won; Choi, Jun Sung; Park, Seung Hee; Lee, Eun Chan

    2014-01-01

    In this study, an automated cable non-destructive testing(NDT) system was developed to monitor the steel cables that are a core component of cable-stayed bridges. The magnetic flux leakage(MFL) method, which is suitable for ferromagnetic continuum structures and has been verified in previous studies, was applied to the cable inspection. A multi-channel MFL sensor head was fabricated using hall sensors and permanent magnets. A wheel-based cable climbing robot was fabricated to improve the accessibility to the cables, and operating software was developed to monitor the MFL-based NDT research and control the climbing robot. Remote data transmission and robot control were realized by applying wireless LAN communication. Finally, the developed element techniques were integrated into an MFL-based cable NDT system, and the field applicability of this system was verified through a field test at Seohae Bridge, which is a typical cable-stayed bridge currently in operation.

  14. Power cables now and in the future

    Energy Technology Data Exchange (ETDEWEB)

    Wanser, G

    1976-01-01

    A survey is presented of the problems to be faced with the underground supply of electric power to large, urban areas and of the contributions that improvements in power cable technology will make to solving these problems. It is concluded that the increase in population densities and the rising demand for energy on the part of individual consumers bring up problems for electricity supply and thus have a direct influence on development trends in cable engineering. During the last few years the increasing capacities required in power transmission have led to the use of higher voltages and to the application of special methods of cooling for the oil-filled cable. When the technical and economic possibilities with present-day cable techniques have been exhausted, we must anticipate the introduction of new types of cable, i.e., gas-insulated cables and superconducting cables. The problems involved in power distribution are being solved successfully by resorting to larger conductor cross-sectional areas and by raising the voltage levels. The advantages of plastic cables are also being utilized on a wide scale. The requirement that there be freedom from partial discharges in plastic cables operating at medium and higher voltages is becoming increasingly more widely adopted as a new quality criterion in cable engineering. New materials from the polymer range are permitting the introduction of fittings which are easier to install and which reduce costs. Cable engineering has already, to a considerable extent, adapted itself to face future problems. Even so, there are still a large number of problems in cable engineering requiring research, development and operation.

  15. High-voltage polymeric insulated cables

    Energy Technology Data Exchange (ETDEWEB)

    Ross, A

    1987-01-01

    Reviews developments in high-voltage (here defined as 25 kV, 66 kV and 132 kV) polymeric insulated cables in the UK over the period 1979-1986, with particular reference to the experience of the Eastern Electricity Board. Outlines the background to the adoption of XPLE-insulated solid cable, and the design, testing, terminations, jointing and costs of 25 kV, 66 kV and 132 kV cables.

  16. Device for guiding various diameter size cable

    Energy Technology Data Exchange (ETDEWEB)

    Litvinov, I.M.; Klauzer, L.P.; Yeganov, L.I.; Zaripov, A.M.

    1982-01-30

    A design is submitted for a device to guide cable of various diameters. This device consists of a profiled multiple-pass roller, and clamps for uniting cut cable. This design is simplified by allowing both the rollers and their supports to rotate on the roller axis thus facilitating interaction with the clamps. The working surface of the supports is evolute while the outside surfaces have screw-channels for transfering the cable from one roller pass to the other.

  17. Vincennes University: Pioneer in Cable TV

    Science.gov (United States)

    Beckes, Isaac K.

    1972-01-01

    The development of cable educational television at Vincennes University (Indiana) is discussed in terms of the financing, securing of franchises, educational goals and plans for future expansion. (RN)

  18. Capacitor discharge process for welding braided cable

    Science.gov (United States)

    Wilson, Rick D.

    1995-01-01

    A capacitor discharge process for welding a braided cable formed from a plurality of individual cable strands to a solid metallic electrically conductive member comprises the steps of: (a) preparing the electrically conductive member for welding by bevelling one of its end portions while leaving an ignition projection extending outwardly from the apex of the bevel; (b) clamping the electrically conductive member in a cathode fixture; (c) connecting the electrically conductive member clamped in the cathode fixture to a capacitor bank capable of being charged to a preselected voltage value; (d) preparing the braided cable for welding by wrapping one of its end portions with a metallic sheet to form a retaining ring operable to maintain the individual strands of the braided cable in fixed position within the retaining ring; (e) clamping the braided cable and the retaining ring as a unit in an anode fixture so that the wrapped end portion of the braided cable faces the ignition projection of the electrically conductive member; and (f) moving the cathode fixture towards the anode fixture until the ignition projection of the electrically conductive member contacts the end portion of the braided cable thereby allowing the capacitor bank to discharge through the electrically conductive member and through the braided cable and causing the electrically conductive member to be welded to the braided cable via capacitor discharge action.

  19. Analytical and numerical construction of equivalent cables.

    Science.gov (United States)

    Lindsay, K A; Rosenberg, J R; Tucker, G

    2003-08-01

    The mathematical complexity experienced when applying cable theory to arbitrarily branched dendrites has lead to the development of a simple representation of any branched dendrite called the equivalent cable. The equivalent cable is an unbranched model of a dendrite and a one-to-one mapping of potentials and currents on the branched model to those on the unbranched model, and vice versa. The piecewise uniform cable, with a symmetrised tri-diagonal system matrix, is shown to represent the canonical form for an equivalent cable. Through a novel application of the Laplace transform it is demonstrated that an arbitrary branched model of a dendrite can be transformed to the canonical form of an equivalent cable. The characteristic properties of the equivalent cable are extracted from the matrix for the transformed branched model. The one-to-one mapping follows automatically from the construction of the equivalent cable. The equivalent cable is used to provide a new procedure for characterising the location of synaptic contacts on spinal interneurons.

  20. 30 CFR 77.601 - Trailing cables or portable cables; temporary splices.

    Science.gov (United States)

    2010-07-01

    ... LABOR COAL MINE SAFETY AND HEALTH MANDATORY SAFETY STANDARDS, SURFACE COAL MINES AND SURFACE WORK AREAS OF UNDERGROUND COAL MINES Trailing Cables § 77.601 Trailing cables or portable cables; temporary... or splices that heat or spark under load shall not be used. ...

  1. Switching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines

    DEFF Research Database (Denmark)

    da Silva, Filipe Miguel Faria; Bak, Claus Leth; Balle Holst, Per

    2011-01-01

    The disconnection of HV underground cables may, if unsuccessful, originate a restrike in the circuit breaker, leading to high overvoltages, and potentially damaging the cable and near equipment. Due to the cable high capacitance and low resistance the voltage damping is slow, resulting, half a cy...

  2. ANALISIS KELAYAKAN TEKNIS DAN FINANSIAL DARI INVESTASI PENGADAAN TRAY DRYER BERBAHAN BAKAR BIOMASSA PADA USAHA ARANG TEMPURUNG KELAPA BERBASIS EKSPOR (Studi Kasus di Tropica Nucifera Industry – Yogyakarta

    Directory of Open Access Journals (Sweden)

    Fanny Widadie

    2013-11-01

    Full Text Available The purpose of the study is to assess the technical and financial feasibility of procurement investment Tray Dryer fueled biomass to operations of coconut shell charcoal briquette in PT. Tropica Nucifera Industry. The result showed that investment-Tray Dryer on cocnut shell charcoal briquette bussiness was highly feasibile both the technical and financial aspects. The technical aspect was seen that the quantity-production capabilities of coconut shell charcoal briquettes using a dryer-Tray Dryer could be increased 15 percent compared the previous consdition-used of solar energy. While the quality of the charcoal briquettes produced from Tray Dryer was a much butter quality, moisture content (6.39%; ash (2.65%; carbon-bound (85.83%, compared to using sunlight, water content (15.89; ash (2.57% and carbon-bound (77.32%.The financial aspects of procurement Tray Dryer investment that its value was more feasible than previous, nothing Tray Dryer. Coconut shell charcoal briquet enterprises without using Tray Dryer was feasible to be done with NPV 1,058,928.12, IRR 63%, Payback Period 1 year and 9 moths, Net B/C 2.25 and analysis of swicthcing value reached 20 percent. And after the business using Tray Drayer, the financial analysis was much more feasible with NPV 2,285,500,498.12, IRR 113%, Payback Period 11 months, Net B/C 3.5 and analysis of switching value reached 50 percent.

  3. Cellulase production through solid-state tray fermentation, and its use for bioethanol from sorghum stover.

    Science.gov (United States)

    Idris, Ayman Salih Omer; Pandey, Ashok; Rao, S S; Sukumaran, Rajeev K

    2017-10-01

    The production of cellulase by Trichoderma reesei RUT C-30 under solid-state fermentation (SSF) on wheat bran and cellulose was optimized employing a two stage statistical design of experiments. Optimization of process parameters resulted in a 3.2-fold increase in CMCase production to 959.53IU/gDS. The process was evaluated at pilot scale in tray fermenters and yielded 457IU/gDS using the lab conditions and indicating possibility for further improvement. The cellulase could effectively hydrolyze alkali pretreated sorghum stover and addition of Aspergillus niger β-glucosidase improved the hydrolytic efficiency 174%, indicating the potential to use this blend for effective saccharification of sorghum stover biomass. The enzymatic hydrolysate of sorghum stover was fermented to ethanol with ∼80% efficiency. Copyright © 2017 Elsevier Ltd. All rights reserved.

  4. Interim Status Closure Plan Open Burning Treatment Unit Technical Area 16-399 Burn Tray

    Energy Technology Data Exchange (ETDEWEB)

    Vigil-Holterman, Luciana R. [Los Alamos National Laboratory

    2012-05-07

    This closure plan describes the activities necessary to close one of the interim status hazardous waste open burning treatment units at Technical Area (TA) 16 at the Los Alamos National Laboratory (LANL or the Facility), hereinafter referred to as the 'TA-16-399 Burn Tray' or 'the unit'. The information provided in this closure plan addresses the closure requirements specified in the Code of Federal Regulations (CFR), Title 40, Part 265, Subparts G and P for the thermal treatment units operated at the Facility under the Resource Conservation and Recovery Act (RCRA) and the New Mexico Hazardous Waste Act. Closure of the open burning treatment unit will be completed in accordance with Section 4.1 of this closure plan.

  5. A simple method for fabricating custom sectional impression trays for making definitive impressions in patients with microstomia

    OpenAIRE

    Bachhav, Vinay Chila; Aras, Meena Ajay

    2012-01-01

    Objective: A maximum mouth opening that is smaller than the size of a complete denture can make prosthetic treatment challenging. This article describes a simple technique used to fabricate maxillary and mandibular custom sectional impression trays for making definitive impressions in patients with microstomia.

  6. Energy and exergy analyses of native cassava starch drying in a tray dryer

    International Nuclear Information System (INIS)

    Aviara, Ndubisi A.; Onuoha, Lovelyn N.; Falola, Oluwakemi E.; Igbeka, Joseph C.

    2014-01-01

    Energy and exergy analyses of native cassava starch drying in a tray dryer were carried out to assess the performance of the system in terms of energy utilization, energy utilization ratio, energy efficiency, exergy inflow and outflow, exergy loss and exegetic efficiency. The results indicated that for the starch with ash content of 0.76%, 0.85% crude protein, 0.16% crude fat, negligible amount of fiber, average granule size of 14.1 μm, pH of 5.88, amylose content of 23.45% and degree of crystallinity of 22.34%, energy utilization and energy utilization ratio increased from 1.93 to 5.51 J/s and 0.65 to 0.6 as the drying temperature increased from 40 to 60 °C. Energy efficiency increased from 16.036 to 30.645%, while exergy inflow, outflow and losses increased from 0.399 to 2.686, 0.055 to 0.555 and 0.344 to 2.131 J/s respectively in the above temperature range. Exergetic efficiency increased with increase in both drying air temperature and energy utilization and was lower than energy efficiency. Exergetic improvement potential also increased with increase in drying air temperature. Model equations that could be used to express the energy and exergy parameters as a function of drying temperature were established. - Highlights: • Energy and exergy analyses of cassava starch drying in a tray dryer were carried out. • Energy utilization increased with drying temperature. • Energy efficiency was higher than exergy efficiency. • Energy and exergy efficiencies increased with increase in temperature. • Improvement potential increased with increase in temperature

  7. The influence of gamma radiation on HDPE properties for tibial tray

    International Nuclear Information System (INIS)

    Sulistioso, G.S.; Dewi, R.K.; Maria, C.P.; Nada, M.

    2012-01-01

    A research on HDPE as tibial tray in total knee joint replacement surgery has been done. The aims of this research were to characterize the influence of gamma radiation on chemical, and mechanical properties on HDPE is made by using hot press method then irradiated with various doses of gamma rays of 0 kGy, 25 kGy, 50 kGy, 75 kGy, 100 kGy, 125 kGy, and 150 kGy at a dose rate 9 kGy/h. The irradiated HDPE were tested for their chemical, and mechanical properties. The chemical properties test, involve crosslinking and free radicals. The mechanical properties test, involve hardness, tensile strength, and elongation at break. The results showed that gamma radiation from IRKA IV th category can enhance the, chemical properties of HDPE in terms of percentage and number of radical crosslinking and mechanical properties of HDPE in terms of hardness, tensile strength and elongation at break with different changes from the initial state before radiation also the optimum dose to obtain better physical, chemical, and mechanical properties of HDPE, crosslinking percentage at 99.71%; height of radical peroxide curve at 13 cm; hardness (shore A) at 94.33; modulus of elasticity at 1113.03 N/mm 2 ; yield stress at 26.38 N/mm 2 ; tensile strength at 31.11 N/mm 2 ; and elongation at break at 440.37%, so that HDPE can be used as tibial tray. (author)

  8. Sound absorption study on acoustic panel from kapok fiber and egg tray

    Science.gov (United States)

    Kaamin, Masiri; Mahir, Nurul Syazwani Mohd; Kadir, Aslila Abd; Hamid, Nor Baizura; Mokhtar, Mardiha; Ngadiman, Norhayati

    2017-12-01

    Noise also known as a sound, especially one that is loud or unpleasant or that causes disruption. The level of noise can be reduced by using sound absorption panel. Currently, the market produces sound absorption panel, which use synthetic fibers that can cause harmful effects to the health of consumers. An awareness of using natural fibers from natural materials gets attention of some parties to use it as a sound absorbing material. Therefore, this study was conducted to investigate the potential of sound absorption panel using egg trays and kapok fibers. The test involved in this study was impedance tube test which aims to get sound absorption coefficient (SAC). The results showed that there was good sound absorption at low frequency from 0 Hz up to 900 Hz where the maximum absorption coefficient was 0.950 while the maximum absorption at high frequencies was 0.799. Through the noise reduction coefficient (NRC), the material produced NRC of 0.57 indicates that the materials are very absorbing. In addition, the reverberation room test was carried out to get the value of reverberation time (RT) in unit seconds. Overall this panel showed good results at low frequencies between 0 Hz up to 1500 Hz. In that range of frequency, the maximum reverberation time for the panel was 3.784 seconds compared to the maximum reverberation time for an empty room was 5.798 seconds. This study indicated that kapok fiber and egg tray as the material of absorption panel has a potential as environmental and cheap products in absorbing sound at low frequency.

  9. Assessment of sodium conductor distribution cable

    Energy Technology Data Exchange (ETDEWEB)

    None

    1979-06-01

    The study assesses the barriers and incentives for using sodium conductor distribution cable. The assessment considers environmental, safety, energy conservation, electrical performance and economic factors. Along with all of these factors considered in the assessment, the sodium distribution cable system is compared to the present day alternative - an aluminum conductor system. (TFD)

  10. Cable Television: Citizen Participation After the Franchise.

    Science.gov (United States)

    Price, Monroe E.; Botein, Michael

    The Federal Communications Commission (FCC) has incorporated several allowances in its regulations pertaining to cable television. Some of these enable citizen groups and communities to intervene in the cable franchise after the final issuance in order to correct deficiencies in the franchising process and the administration of the franchise.…

  11. Cable Technology: A Challenge for Adult Educators.

    Science.gov (United States)

    Palchinsky, Jo

    The penetration of cable television throughout American communities makes it a potentially significant tool for improving the quality and accessibility of adult education. As cities begin to include in the cable franchise allotment monies for access by community members, adult educators need to become actively involved during the development of a…

  12. The Selling of Cable Television 1972.

    Science.gov (United States)

    National Cable Television Association, Inc., Washington, DC.

    The 1972 Cable Television Marketing Workshop reviewed in depth a wide variety of marketing and public relations techniques as they pertain to cable television. The workshop was attended by representatives of commercial television systems throughout the United States; it was intended to disseminate the sales and marketing experience of those…

  13. An ACLU Guide to Cable Television.

    Science.gov (United States)

    Powledge, Fred

    Proceeding from the hypothesis that cable television (CATV) is one of the most significant developments in modern America, this booklet examines the medium itself and then devotes special attention to the capacity of CATV to serve the First Amendment interest in diversity of expression. The opening section deals with the size and growth of cable,…

  14. Cable Television: The Process of Franchising.

    Science.gov (United States)

    Johnson, Leland L.; Botein, Michael

    In an effort to insure that cable television franchising procedures at the local level are based on a competitive and well-conceived selection process, this report discusses some of the most important steps of the franchising process. Not only does it show how the community should assess its needs and appraise the merits of the cable operator, but…

  15. Cables for nuclear power generating stations, (6)

    International Nuclear Information System (INIS)

    Kakuta, Tsunemi; Asakawa, Naoki; Yamamoto, Tomotaka; Watanabe, Mikio; Shingo, Yoshioki.

    1981-01-01

    New inorganic material insulated flexible triaxial cables have been developed for the purpose of applying around the primary circuit of fast breeder reactor (FBR). These cables were tested at high temperature and high #betta#-ray radiation environment, and they showed good electrical properties. Other noted results were that they showed good fire proof and flame resistant properties. (author)

  16. Cable Television and Educational Access: A Reconsideration.

    Science.gov (United States)

    Thornton, Lee R.; Greene, James C.

    1986-01-01

    Considers the possible impact of recent federal legislation on educational utilization of cable television. Stresses the importance of educators understanding the law's provisions and acting to initiate relationships with cable companies. Reviews public educational or governmental access provisions. Presents strategies for promoting reciprocity…

  17. Intermodal resonance of vibrating suspended cables

    NARCIS (Netherlands)

    Rienstra, S.W.

    2010-01-01

    The weakly nonlinear free vibrations of a single suspended cable, or a coupled system of suspended cables, may be classified as gravity modes (no tension variations to leading order) and elasto-gravity modes (tension and vertical displacement equally important). It was found earlier [12] that the

  18. A new multiconstraint method for determining the optimal cable stresses in cable-stayed bridges.

    Science.gov (United States)

    Asgari, B; Osman, S A; Adnan, A

    2014-01-01

    Cable-stayed bridges are one of the most popular types of long-span bridges. The structural behaviour of cable-stayed bridges is sensitive to the load distribution between the girder, pylons, and cables. The determination of pretensioning cable stresses is critical in the cable-stayed bridge design procedure. By finding the optimum stresses in cables, the load and moment distribution of the bridge can be improved. In recent years, different research works have studied iterative and modern methods to find optimum stresses of cables. However, most of the proposed methods have limitations in optimising the structural performance of cable-stayed bridges. This paper presents a multiconstraint optimisation method to specify the optimum cable forces in cable-stayed bridges. The proposed optimisation method produces less bending moments and stresses in the bridge members and requires shorter simulation time than other proposed methods. The results of comparative study show that the proposed method is more successful in restricting the deck and pylon displacements and providing uniform deck moment distribution than unit load method (ULM). The final design of cable-stayed bridges can be optimised considerably through proposed multiconstraint optimisation method.

  19. Nonlinear Analysis of Cable Vibration of a Multispan Cable-Stayed Bridge under Transverse Excitation

    Directory of Open Access Journals (Sweden)

    Kun Lin

    2014-01-01

    Full Text Available The nonlinear vibrations of cable in a multispan cable-stayed bridge subjected to transverse excitation are investigated. The MECS (multielements cable system model, where multielements per cable stay are used, is built up and used to analyze the model properties of the multispan cable-stayed bridges. Then, a simplified two-degrees-of-freedom (2-DOFs model, where the tower or the deck is reduced to a beam, is proposed to analyze the nonlinear dynamic behaviors of the beam and cable. The results of MECS model analysis show that the main tower in the multispan cable-stayed bridge is prone to the transverse vibration, and the local vibration of cables only has a little impact on the frequency values of the global modes. The results of simplified model analysis show that the energy can be transformed between the modes of the beam and cable when the nature frequencies of them are very close. On the other hand, with the transverse excitation changing, the cable can exhibit richer quasi-periodic or chaotic motions due to the nonlinear terms caused by the coupled mode between the beam and cable.

  20. A New Multiconstraint Method for Determining the Optimal Cable Stresses in Cable-Stayed Bridges

    Directory of Open Access Journals (Sweden)

    B. Asgari

    2014-01-01

    Full Text Available Cable-stayed bridges are one of the most popular types of long-span bridges. The structural behaviour of cable-stayed bridges is sensitive to the load distribution between the girder, pylons, and cables. The determination of pretensioning cable stresses is critical in the cable-stayed bridge design procedure. By finding the optimum stresses in cables, the load and moment distribution of the bridge can be improved. In recent years, different research works have studied iterative and modern methods to find optimum stresses of cables. However, most of the proposed methods have limitations in optimising the structural performance of cable-stayed bridges. This paper presents a multiconstraint optimisation method to specify the optimum cable forces in cable-stayed bridges. The proposed optimisation method produces less bending moments and stresses in the bridge members and requires shorter simulation time than other proposed methods. The results of comparative study show that the proposed method is more successful in restricting the deck and pylon displacements and providing uniform deck moment distribution than unit load method (ULM. The final design of cable-stayed bridges can be optimised considerably through proposed multiconstraint optimisation method.

  1. Nuclear power plant cable materials :

    Energy Technology Data Exchange (ETDEWEB)

    Celina, Mathias C.; Gillen, Kenneth T; Lindgren, Eric Richard

    2013-05-01

    A selective literature review was conducted to assess whether currently available accelerated aging and original qualification data could be used to establish operational margins for the continued use of cable insulation and jacketing materials in nuclear power plant environments. The materials are subject to chemical and physical degradation under extended radiationthermal- oxidative conditions. Of particular interest were the circumstances under which existing aging data could be used to predict whether aged materials should pass loss of coolant accident (LOCA) performance requirements. Original LOCA qualification testing usually involved accelerated aging simulations of the 40-year expected ambient aging conditions followed by a LOCA simulation. The accelerated aging simulations were conducted under rapid accelerated aging conditions that did not account for many of the known limitations in accelerated polymer aging and therefore did not correctly simulate actual aging conditions. These highly accelerated aging conditions resulted in insulation materials with mostly inert aging processes as well as jacket materials where oxidative damage dropped quickly away from the air-exposed outside jacket surface. Therefore, for most LOCA performance predictions, testing appears to have relied upon heterogeneous aging behavior with oxidation often limited to the exterior of the cable cross-section a situation which is not comparable with the nearly homogenous oxidative aging that will occur over decades under low dose rate and low temperature plant conditions. The historical aging conditions are therefore insufficient to determine with reasonable confidence the remaining operational margins for these materials. This does not necessarily imply that the existing 40-year-old materials would fail if LOCA conditions occurred, but rather that unambiguous statements about the current aging state and anticipated LOCA performance cannot be provided based on

  2. Parallel monostrand stay cable bending fatigue

    DEFF Research Database (Denmark)

    Winkler, Jan Pawel

    This dissertation investigates the bending fatigue response of high-strength steel monostrands and multistrand stay cables to cyclic transverse deformations. Increasing bridge stock numbers and a push for longer cable-supported span lengths have led to an increased number of reported incidents...... of damage and replacement of bridge stay cables due to wind and traffic-induced fatigue. The understanding of fatigue mechanisms in most steel structures is well established. However, in the case of cables composed of steel strands, many important aspects related with bending fatigue remain to be clarified...... associated with variable loading, and different testing procedures. As most of the contemporary stay cables are comprised of a number of individual highstrength steel monostrands, the research study started with an extensive experimental work on the fatigue response of a single monostrand to cyclic flexural...

  3. Development of radiation resistant PEEK insulation cable

    International Nuclear Information System (INIS)

    Mio, Keigo; Ogiwara, Norio; Hikichi, Yusuke; Furukori, Hisayoshi; Arai, Hideyuki; Nishizawa, Daiji; Nishidono, Toshiro

    2009-04-01

    Material characterization and development has been carried out for cable insulation suitable for use in the J-PARC 3-GeV RCS radiation environment. In spite of its high cost, PEEK (polyether-ether-ketone) has emerged as the leading candidate satisfying requirements of being non-halogen based, highly incombustible and with radiation resistant at least 10 MGy, along with the usual mechanical characteristics such as good elongation at break, which are needed in a cable insulation. Gamma-ray irradiation tests have been done in order to study radiation resistance of PEEK cable. Further, mechanical, electrical and fire retardant characteristics of a complete cable such as would be used at the J-PARC RCS were investigated. As a result, PEEK cables were shown to be not degraded by radiation up to at least 10 MGy, and thus could be expected to operate stably under the 3-GeV RCS radiation environment. (author)

  4. Behaviour of electrical cables under fire conditions

    International Nuclear Information System (INIS)

    Bertrand, R.; Chaussard, M.; Gonzalez, R.; Lacoue, J.; Mattei, J.M.; Such, J.M.

    2002-01-01

    A Fire Probabilistic Safety Assessment - called the Fire PSA - is being carried out by the French Institute of Radiological Protection and Nuclear Safety (IPSN) to be used in the framework of the safety assessment of operating 900 MWe PWRs. The aim of this study is to evaluate the core damage conditional probability which could result from a fire. A fire can induce unavailability of safety equipment, notably damaging electrical cables introducing a significant risk contributor. The purpose of this paper is to present the electrical cable fire tests carried out by IPSN to identify the failure modes and to determine the cable damage criteria. The impact of each kind of cable failure mode and the methodology used to estimate the conditional probability of a failure mode when cable damage occurred is also discussed. (orig.) [de

  5. Physical degradation assessment of generator station cables

    International Nuclear Information System (INIS)

    Stonkus, D.J.

    1988-01-01

    Preliminary studies of fossil-fired and nuclear generator station cables indicate that the low voltage PVC insulated cables are in relatively good condition. The insulation is flexible and in the case of nuclear cables can withstand a design basis event after nearly 15 years of service. Cables insulated with styrene butadiene rubber have been found embrittled and cables insulated with SBR should be closely inspected in any plant assurance program. Thermal analysis using oxidative induction technique shows promise to indicate cable insulation degradation. Long term reliability assurance and plant life extension studies are being actively pursued at Ontario Hydro. A major study is currently underway to extend the life of the oldest operating fossil-fuel station, the 8-unit, 2400 MW Lakeview TGS in operation since the 1960s. Plant life assurance programs have been initiated at the 2000 MW Lambton TGS in operation since 1969, and for the oldest operating nuclear plant, Pickering NGS A in operation since the early 1970s. As cables are considered one of the critical components in a generator station due to the extreme difficulty and cost of cable replacement, test programs have been initiated to evaluate the physical degradation of the cables and relate the results to electrical diagnostic tests and to chemical changes. The decommissioning of two small nuclear stations, the 20 MW Nuclear Power Demonstration (NPD) and the 200 MW Douglas Point NGS, which were placed in service in 1962 and 1967 respectively, will provide an opportunity to perform destructive electrical and physical evaluation on field aged cables

  6. Wind-induced cable vibrations and countermeasures of cables of PC cable-stayed bridge. PC syachokyo keburu no kaze ni yoru shindo to sono taisaku

    Energy Technology Data Exchange (ETDEWEB)

    Yoneda, M. (Kawada Industries Inc., Tokyo (Japan))

    1994-05-01

    In recent years, long span of cable-stayed bridges is remarkable. The wind-induced cable vibration called as line vibration and wake galloping was given as an important problem not only in the steel cable-stayed bridges but also in the PC cable-stayed bridges. The technical engineers in design of the cable-stayed bridges have many times to confront the problems on the vibration control of cables, it is considered that sufficient understand of the wind-induced vibration and countermeasures for cables of the PC cable-stayed bridges is necessary. Many reports on the countermeasure examples and trend of vibration control centred on cables of the cable-stayed bridges have been published. In this paper, the wind-induced vibration of cables in the cable-stayed bridges was reviewed, the examples of countermeasures of vibration control on cables in the PC cable-stayed bridges was mainly introduced. The remaining tasks and future prospects on vibration control of the PC cable-stayed bridges were described. 14 refs., 13 figs., 4 tabs.

  7. Simulation of the cabling process for Rutherford cables: An advanced finite element model

    Science.gov (United States)

    Cabanes, J.; Garlasche, M.; Bordini, B.; Dallocchio, A.

    2016-12-01

    In all existing large particle accelerators (Tevatron, HERA, RHIC, LHC) the main superconducting magnets are based on Rutherford cables, which are characterized by having: strands fully transposed with respect to the magnetic field, a significant compaction that assures a large engineering critical current density and a geometry that allows efficient winding of the coils. The Nb3Sn magnets developed in the framework of the HL-LHC project for improving the luminosity of the Large Hadron Collider (LHC) are also based on Rutherford cables. Due to the characteristics of Nb3Sn wires, the cabling process has become a crucial step in the magnet manufacturing. During cabling the wires experience large plastic deformations that strongly modify the geometrical dimensions of the sub-elements constituting the superconducting strand. These deformations are particularly severe on the cable edges and can result in a significant reduction of the cable critical current as well as of the Residual Resistivity Ratio (RRR) of the stabilizing copper. In order to understand the main parameters that rule the cabling process and their impact on the cable performance, CERN has developed a 3D Finite Element (FE) model based on the LS-Dyna® software that simulates the whole cabling process. In the paper the model is presented together with a comparison between experimental and numerical results for a copper cable produced at CERN.

  8. Non-cable vehicle guidance

    Energy Technology Data Exchange (ETDEWEB)

    Daugela, G.C.; Willott, A.M.; Chopiuk, R.G.; Thornton, S.E.

    1988-06-01

    The purpose is to determine the most promising driverless mine vehicle guidance systems that are not dependent on buried cables, and to plan their development. The project is presented in two phases: a preliminary study and literature review to determine whether suitable technologies exist to justify further work; and an in-depth assessment and selection of technologies for vehicle guidance. A large number of guidance elements are involved in a completely automated vehicle. The technologies that hold the best potential for development of guidance systems for mine vehicles are ultrasonics, radar, lasers, dead reckoning, and guidance algorithms. The best approach to adaptation of these technologies is on a step by step basis. Guidance modules that are complete in themselves and are designed to be integrated with other modules can provide short term benefits. Two modules are selected for development: the dragline operations monitor and automated machine control for optimized mining (AMCOM). 99 refs., 20 figs., 40 tabs.

  9. Self-healing cable for extreme environments

    Science.gov (United States)

    Huston, Dryver R. (Inventor); Tolmie, Bernard R. (Inventor)

    2009-01-01

    Self-healing cable apparatus and methods disclosed. The self-healing cable has a central core surrounded by an adaptive cover that can extend over the entire length of the self-healing cable or just one or more portions of the self-healing cable. The adaptive cover includes an axially and/or radially compressible-expandable (C/E) foam layer that maintains its properties over a wide range of environmental conditions. A tape layer surrounds the C/E layer and is applied so that it surrounds and axially and/or radially compresses the C/E layer. When the self-healing cable is subjected to a damaging force that causes a breach in the outer jacket and the tape layer, the corresponding localized axially and/or radially compressed portion of the C/E foam layer expands into the breach to form a corresponding localized self-healed region. The self-healing cable is manufacturable with present-day commercial self-healing cable manufacturing tools.

  10. Neutron detector with gamma compensated cable

    International Nuclear Information System (INIS)

    Warren, H.D.

    1975-01-01

    An illustrative embodiment of the invention describes a technique for essentially eliminating the radiation induced background currents that are generated in the cable that connects an ''in-core'' neutron detector to an electrical terminal that is outside of the reactor's radiation field. This undesirable radiation-induced cable current is suppressed through an appropriate selection of conductor and cable sheath materials and sizes that generally satisfy the equation: Z/sub l/sup n/d/sub l/ = Z/sub s/sup m/d/sub s/ where Z is the atomic number of the material; d is a characteristic of the size of the cable component; m and/n have values between 1 and 5 to express the electron emissivity of the cable component from photoelectric and Compton effects; l represents the conductor; and s represents the sheath. Thus, the radiation-generated electrons emitted from the conductor and the oppositely-directed electrons emitted from the inner surface of the cable sheath are mutually cancelled if this equation is satisfied. A typical cable that does meet this criterion at low temperatures has a centrally disposed Zircaloy-2 inner conductor of 0.011 inch diameter, an annular insulation of magnesium oxide powder compacted to 100 percent density, and an Inconel sheath with an outside diameter of 0.062 inch and 0.011 inch wall thickness. (auth)

  11. Optimal space utilization of a greenhouse using multi-rack tray system: Thermal modeling and experimental validation

    International Nuclear Information System (INIS)

    Sethi, V.P.; Dubey, R.K.

    2008-01-01

    In this study, upper space inside an east-west oriented greenhouse (where the micro-climate is also under control) is optimised for producing maximum number of nursery plants by developing a multi-rack tray system (MRTS). The MRTS is designed in such a way that the vertical distance between the two consecutive trays (H) and width of the tray (W) is optimised for different months of the year at different latitudes so that the shadow of the upper tray does not fall on the lower one. The number of stacks in a greenhouse of fixed height (say 4 m) is a direct function of the maximum altitude angle of the sun at noon (α s ) at particular latitude. It is observed that at 10 deg. N and 20 deg. N latitudes α s remains greater than 45 deg. (H/W > 1) even during the winter months. It means not more than two stacks are possible inside a 4 m high greenhouse during December and January. The computations show that at 30 deg. N, 40 deg. N and 50 deg. N latitude, the number of stacks inside a greenhouse can be five, seven and twelve, respectively during the winter months of December and January. A transient thermal model coupled with MRTS is also developed to predict the soil, plant and air temperature inside the greenhouse. It is observed that the predicted and measured values are in close agreement. It is also observed that due to the increased mass of soil (in the trays) inside the greenhouse and due to reduced conduction losses to the ground beneath, MRTS also acted as a soil heat storage system before germination of the plants which stored heat during the sun-shine hours and released the same during the off-shine hours and resulted in 5-2deg. C higher inside air temperature till the early night hours as compared to ambient air temperature. Nursery of marigold (ornamental plant) is successfully raised using the MRTS inside a 3 m high greenhouse having three stacks at 30 deg. N latitude. Experiments showed that there was almost uniform growth of plants in all the three trays

  12. 46 CFR 111.60-5 - Cable installation.

    Science.gov (United States)

    2010-10-01

    ... REQUIREMENTS Wiring Materials and Methods § 111.60-5 Cable installation. (a) Each cable installation must meet... 46 Shipping 4 2010-10-01 2010-10-01 false Cable installation. 111.60-5 Section 111.60-5 Shipping... incorporated by reference; see 46 CFR 110.10-1), including clause 8. (b) Each cable installation made in...

  13. Electrical cabling system associated at a nuclear reactor

    International Nuclear Information System (INIS)

    Dejeux, P.; Desfontaines, G.

    1988-01-01

    This cabling system for an electrical device in a nuclear reactor comprises at least a first cable issued of the device, a second cable comprising a first portion, a second portion and a third portion joining the second by a multiple quick fitting connector capable to connect at least ten second portions at ten other third portions of the second cable [fr

  14. Choice Of Computer Networking Cables And Their Effect On Data ...

    African Journals Online (AJOL)

    Computer networking is the order of the day in this Information and Communication Technology (ICT) age. Although a network can be through a wireless device most local connections are done using cables. There are three main computer-networking cables namely coaxial cable, unshielded twisted pair cable and the optic ...

  15. Non-linear stochastic response of a shallow cable

    DEFF Research Database (Denmark)

    Larsen, Jesper Winther; Nielsen, Søren R.K.

    2004-01-01

    The paper considers the stochastic response of geometrical non-linear shallow cables. Large rain-wind induced cable oscillations with non-linear interactions have been observed in many large cable stayed bridges during the last decades. The response of the cable is investigated for a reduced two...

  16. Development of evaluation methodology to assess the sodium fire suppression performance of leak collection tray

    International Nuclear Information System (INIS)

    Parida, F.C.; Rao, P.M.; Ramesh, S.S.; Somayajulu, P.A.; Malarvizhi, B.; Kannan, S.E.

    2005-01-01

    Full text of publication follows: Leakage of hot liquid sodium and its subsequent combustion in the form of a pool cannot be completely ruled out in a Fast breeder Reactor (FBR) plant in spite of provision for adequate safety measures. To protect the plant system from the hazardous effects of flame, heat and smoke, one of the passive protection devices used in FBR plants is the Leak Collection Tray (LCT). The design of LCT is based on immediate channeling of burning liquid sodium on the funnel shaped sloping cover tray (SCT) to the bottom sodium hold-up vessel (SHV) in which self-extinction of the fire occurs due to oxygen starvation. The SCT has one or three drain pipes and air vent pipes depending on the type of design. In each experiment, a known amount ranging from 30 to 40 kg of hot liquid sodium at 550 deg. C was discharged on the LCT in the open air. Continuous on-line monitoring of temperature at strategic locations (∼ 28 points) was carried out. Colour video-graphy was employed for taking motion pictures of various time-dependent events like sodium dumping, appearance of flame and release of smoke through vent pipes. After self-extinction of sodium fire, the LCT was allowed to cool overnight in an argon atmosphere. Solid samples of sodium debris in the SCT and SHV were collected by manual core drilling machine. The samples were subjected to chemical analysis for determination of unburnt and burnt sodium. The sodium debris removed from SCT and SHV were separately weighed. To assess the performance of the LCT, two different geometrical configurations of SCT, one made up of stainless steel an the other of carbon steel, were used. Three broad phenomena are identified as the basis of evaluation methodology. These are (a) thermal transients, i.e. heating and cooling of the bulk sodium in SCT and SHV respectively, (b) post test sodium debris distribution between SCT and SHV as well as (c) sodium combustion and smoke release behaviour. Under each category

  17. Development of evaluation methodology to assess the sodium fire suppression performance of leak collection tray

    Energy Technology Data Exchange (ETDEWEB)

    Parida, F.C.; Rao, P.M.; Ramesh, S.S.; Somayajulu, P.A.; Malarvizhi, B.; Kannan, S.E. [Engineering Safety Division, Safety Group, Indira Gandhi Centre for Atomic Research, Kalpakkam - 603102, Tamilnadu (India)

    2005-07-01

    Full text of publication follows: Leakage of hot liquid sodium and its subsequent combustion in the form of a pool cannot be completely ruled out in a Fast breeder Reactor (FBR) plant in spite of provision for adequate safety measures. To protect the plant system from the hazardous effects of flame, heat and smoke, one of the passive protection devices used in FBR plants is the Leak Collection Tray (LCT). The design of LCT is based on immediate channeling of burning liquid sodium on the funnel shaped sloping cover tray (SCT) to the bottom sodium hold-up vessel (SHV) in which self-extinction of the fire occurs due to oxygen starvation. The SCT has one or three drain pipes and air vent pipes depending on the type of design. In each experiment, a known amount ranging from 30 to 40 kg of hot liquid sodium at 550 deg. C was discharged on the LCT in the open air. Continuous on-line monitoring of temperature at strategic locations ({approx} 28 points) was carried out. Colour video-graphy was employed for taking motion pictures of various time-dependent events like sodium dumping, appearance of flame and release of smoke through vent pipes. After self-extinction of sodium fire, the LCT was allowed to cool overnight in an argon atmosphere. Solid samples of sodium debris in the SCT and SHV were collected by manual core drilling machine. The samples were subjected to chemical analysis for determination of unburnt and burnt sodium. The sodium debris removed from SCT and SHV were separately weighed. To assess the performance of the LCT, two different geometrical configurations of SCT, one made up of stainless steel an the other of carbon steel, were used. Three broad phenomena are identified as the basis of evaluation methodology. These are (a) thermal transients, i.e. heating and cooling of the bulk sodium in SCT and SHV respectively, (b) post test sodium debris distribution between SCT and SHV as well as (c) sodium combustion and smoke release behaviour. Under each category

  18. Wire in the Cable-Driven System of Surgical Robot

    Science.gov (United States)

    Wang, X. F.; Lv, N.; Mu, H. Z.; Xue, L. J.

    2017-07-01

    During the evolution of the surgical robot, cable plays an important role. It translates motion and force precisely from surgeon’s hand to the tool’s tips. In the paper, the vertical wires, the composition of cable, are mathematically modeled from a geometric point of view. The cable structure and tension are analyzed according to the characteristics of wire screw twist. The structural equations of the wires in different positions are derived for both non-bent cable and bent cable, respectively. The bending moment formula of bent cable is also obtained. This will help researchers find suitable cable and design more matched pulley.

  19. Condition Monitoring of Cables Task 3 Report: Condition Monitoring Techniques for Electric Cables

    Energy Technology Data Exchange (ETDEWEB)

    Villaran, M.; Lofaro, R.; na

    2009-11-30

    For more than 20 years the NRC has sponsored research studying electric cable aging degradation, condition monitoring, and environmental qualification testing practices for electric cables used in nuclear power plants. This report summarizes several of the most effective and commonly used condition monitoring techniques available to detect damage and measure the extent of degradation in electric cable insulation. The technical basis for each technique is summarized, along with its application, trendability of test data, ease of performing the technique, advantages and limitations, and the usefulness of the test results to characterize and assess the condition of electric cables.

  20. On the Minimum Cable Tensions for the Cable-Based Parallel Robots

    Directory of Open Access Journals (Sweden)

    Peng Liu

    2014-01-01

    Full Text Available This paper investigates the minimum cable tension distributions in the workspace for cable-based parallel robots to find out more information on the stability. First, the kinematic model of a cable-based parallel robot is derived based on the wrench matrix. Then, a noniterative polynomial-based optimization algorithm with the proper optimal objective function is presented based on the convex optimization theory, in which the minimum cable tension at any pose is determined. Additionally, three performance indices are proposed to show the distributions of the minimum cable tensions in a specified region of the workspace. An important thing is that the three performance indices can be used to evaluate the stability of the cable-based parallel robots. Furthermore, a new workspace, the Specified Minimum Cable Tension Workspace (SMCTW, is introduced, within which all the minimum tensions exceed a specified value, therefore meeting the specified stability requirement. Finally, a camera robot parallel driven by four cables for aerial panoramic photographing is selected to illustrate the distributions of the minimum cable tensions in the workspace and the relationship between the three performance indices and the stability.

  1. Parametrically excited oscillation of stay cable and its control in cable-stayed bridges.

    Science.gov (United States)

    Sun, Bing-nan; Wang, Zhi-gang; Ko, J M; Ni, Y Q

    2003-01-01

    This paper presents a nonlinear dynamic model for simulation and analysis of a kind of parametrically excited vibration of stay cable caused by support motion in cable-stayed bridges. The sag, inclination angle of the stay cable are considered in the model, based on which, the oscillation mechanism and dynamic response characteristics of this kind of vibration are analyzed through numerical calculation. It is noted that parametrically excited oscillation of a stay cable with certain sag, inclination angle and initial static tension force may occur in cable-stayed bridges due to deck vibration under the condition that the natural frequency of a cable approaches to about half of the first model frequency of the bridge deck system. A new vibration control system installed on the cable anchorage is proposed as a possible damping system to suppress the cable parametric oscillation. The numerical calculation results showed that with the use of this damping system, the cable oscillation due to the vibration of the deck and/or towers will be considerably reduced.

  2. Influence of Icing on Bridge Cable Aerodynamics

    DEFF Research Database (Denmark)

    Koss, Holger; Frej Henningsen, Jesper; Olsen, Idar

    2013-01-01

    In recent years the relevance of ice accretion for wind-induced vibration of structural bridge cables has been recognised and became a subject of research in bridge engineering. Full-scale monitoring and observation indicate that light precipitation at moderate low temperatures between zero and -5......°C may lead to large amplitude vibrations of bridge cables under wind action. For the prediction of aerodynamic instability quasi-steady models have been developed estimating the cable response magnitude based on structural properties and aerodynamic force coefficients for drag, lift and torsion...... forces of different bridge cables types. The experiments were conducted in a wind tunnel facility capable amongst others to simulate incloud icing conditions....

  3. 47 CFR 32.2422 - Underground cable.

    Science.gov (United States)

    2010-10-01

    ... FOR TELECOMMUNICATIONS COMPANIES Instructions for Balance Sheet Accounts § 32.2422 Underground cable... manholes and ducts in connection with construction work and the cost of permits and privileges for the...

  4. 47 CFR 32.2423 - Buried cable.

    Science.gov (United States)

    2010-10-01

    ... FOR TELECOMMUNICATIONS COMPANIES Instructions for Balance Sheet Accounts § 32.2423 Buried cable. (a... of cleaning manholes and ducts in connection with construction work and the cost of permits and...

  5. Chinese Market for Fibres and Cables

    Institute of Scientific and Technical Information of China (English)

    2003-01-01

    This article presents a summary of Chinese market of optical fibres and cables based on the development of the optical communications industry. Analysis shows that the market will keep growing for sometime in the future.

  6. Exergetic performance analyses of drying of broccoli florets in a tray drier

    International Nuclear Information System (INIS)

    Zafer Erbay

    2009-01-01

    At present, the drying process is one of the major procedures of food preservation and an important unit operation in a wide variety of food industries. Recently, drying of vegetables is of a particular interest because it is added to various ready-to-eat meals in order to improve their nutritional quality due to health benefit compounds present in vegetables (vitamins, phytochemicals, dietary fibers). Broccoli has been described as a vegetable with a high nutritional value due to its important content of vitamins, antioxidants and anti-carcinogenic compounds. Broccoli dehydration has not been investigated to a great extent and a few data are available in the open literature. In this study, broccoli florets were dried in a tray drier at a temperature range of 50-70 deg C with an air velocity range of 0.5-1.5 m/s. The performance of the process and system was evaluated using the exergy analysis method. Based on the experimental data, effects of the drying air temperature and the velocity on the performance of the drying process were discussed. It was obtained that the exergy evaporation rate and the exergetic efficiency of the process were obtained to vary between 0.0006-0.0029 kW and 0.27-1.16%, respectively. They increased as the drying air temperature increased, while the exergetic efficiency decreased with the rise in the drying air velocity. (author)

  7. Cable system transients theory, modeling and simulation

    CERN Document Server

    Ametani, Akihiro; Nagaoka, Naoto

    2015-01-01

    A systematic and comprehensive introduction to electromagnetic transient in cable systems, written by the internationally renowned pioneer in this field Presents a systematic and comprehensive introduction to electromagnetic transient in cable systems Written by the internationally renowned pioneer in the field Thorough coverage of the state of the art on the topic, presented in a well-organized, logical style, from fundamentals and practical applications A companion website is available

  8. Torsion instability of Dynamic Cables during Installation

    OpenAIRE

    Opgård, Marie Finstad

    2017-01-01

    The oil and gas industry today is a heavily regulated segment, and current standard hasestablished restrictions which yields a very limited weather window for offshore cable installations. This is due to experience with cable failure in harsh weather. A limiting factor in current practice is the design criterion for the minimum allowable radius of curvature in the touchdown point. In addition, current practice does not allow for occurrence of compression in the touch down zone...

  9. Ecology: Electrical Cable Bacteria Save Marine Life

    DEFF Research Database (Denmark)

    Nielsen, Lars Peter

    2016-01-01

    Animals at the bottom of the sea survive oxygen depletion surprisingly often, and a new study identifies cable bacteria in the sediment as the saviors. The bacterial electrical activity creates an iron 'carpet', trapping toxic hydrogen sulfide.......Animals at the bottom of the sea survive oxygen depletion surprisingly often, and a new study identifies cable bacteria in the sediment as the saviors. The bacterial electrical activity creates an iron 'carpet', trapping toxic hydrogen sulfide....

  10. A Cable-Shaped Lithium Sulfur Battery.

    Science.gov (United States)

    Fang, Xin; Weng, Wei; Ren, Jing; Peng, Huisheng

    2016-01-20

    A carbon nanostructured hybrid fiber is developed by integrating mesoporous carbon and graphene oxide into aligned carbon nanotubes. This hybrid fiber is used as a 1D cathode to fabricate a new cable-shaped lithium-sulfur battery. The fiber cathode exhibits a decent specific capacity and lifespan, which makes the cable-shaped lithium-sulfur battery rank far ahead of other fiber-shaped batteries. © 2015 WILEY-VCH Verlag GmbH & Co. KGaA, Weinheim.

  11. MVAC Submarine cable, impedance measurements and analysis

    DEFF Research Database (Denmark)

    Arentsen, Martin Trolle; Expethit, Adrian; Pedersen, Morten Virklund

    2017-01-01

    influence the losses. Secondly, cable parameters such as component impedances, positive-, zero-sequence impedances and losses are measured for varying currents and frequencies. Zero sequence is measured for two setups, one with armour grounded, and with armour open to match CIGREs formula assumption......-sequence impedance is found between the measurements and the CIGRÉ formulas. It is concluded that the formulas are not accurate for the specific cable under test....

  12. Polyethylene as a possible hvdc cable insulant

    Energy Technology Data Exchange (ETDEWEB)

    Hawley, W.G.; Body, R.S.; Mason, J.H.

    1966-10-01

    Many cable authorities have expressed the view that polyethylene would be attractive for this application. The dc conductivity of polyethylene is lower than that of impregnated paper, and varies less with temperature and stress. Polyethylene also has higher thermal conductivity and is resistant to moisture and electrochemical deterioration. Furthermore, processing polyethylene cables should ultimately involve lower capital and manufacturing costs. However, polyethylene has a lower limiting short circuit temperature unless it is cross linked.

  13. Development of mechanical methods for cell-tray propagation and field transplanting of dwarf napiergrass (Pennisetum purpureum Schumach.

    Directory of Open Access Journals (Sweden)

    Renny Fatmyah Utamy

    2016-01-01

    Full Text Available Since dwarf napiergrass (Pennisetum purpureum Schumach. must be propagated vegetatively due to lack of viable seeds, root splitting and stem cuttings are generally used to obtain true-to-type plant populations. These ordinary methods are laborious and costly, and are the greatest barriers for expanding the cultivation area of this crop. The objectives of this research were to develop nursery production of dwarf napiergrass in cell trays and to compare the efficiency of mechanical versus manual methods for cell-tray propagation and field transplanting. After defoliation of herbage either by a sickle (manually or hand-mowing machine, every potential aerial tiller bud was cut to a single one for transplanting into cell trays as stem cuttings and placed in a glasshouse over winter. The following June, nursery plants were trimmed to a 25–cm length and transplanted in an experimental field (sandy soil with 20,000 plants ha^(−1 either by shovel (manually or Welsh onion planter. Labour time was recorded for each process. The manual defoliation of plants required 44% more labour time for preparing the stem cuttings (0.73 person-min. stemcutting^(−1 compared to using hand-mowing machinery (0.51 person-min. stem-cutting^(−1. In contrast, labour time for transplanting required an extra 0.30 person-min. m^(−2 (14% using the machinery compared to manual transplanting, possibly due to the limited plot size for machinery operation. The transplanting method had no significant effect on plant establishment or plant growth, except for herbage yield 110 days after planting. Defoliation of herbage by machinery, production using a cell-tray nursery and mechanical transplanting reduced the labour intensity of dwarf napiergrass propagation.

  14. The analysis of cable forces based on natural frequency

    Science.gov (United States)

    Suangga, Made; Hidayat, Irpan; Juliastuti; Bontan, Darwin Julius

    2017-12-01

    A cable is a flexible structural member that is effective at resisting tensile forces. Cables are used in a variety of structures that employ their unique characteristics to create efficient design tension members. The condition of the cable forces in the cable supported structure is an important indication of judging whether the structure is in good condition. Several methods have been developed to measure on site cable forces. Vibration technique using correlation between natural frequency and cable forces is a simple method to determine in situ cable forces, however the method need accurate information on the boundary condition, cable mass, and cable length. The natural frequency of the cable is determined using FFT (Fast Fourier Transform) Technique to the acceleration record of the cable. Based on the natural frequency obtained, the cable forces then can be determine by analytical or by finite element program. This research is focus on the vibration techniques to determine the cable forces, to understand the physical parameter effect of the cable and also modelling techniques to the natural frequency and cable forces.

  15. Proposal for the award of a contract for the supply of LHC dipole thermal shield bottom tray assemblies

    CERN Document Server

    2000-01-01

    This document concerns the award of a contract for the supply of 1 250 LHC dipole thermal shield bottom tray assemblies. Following a market survey carried out among 95 firms in sixteen Member States, a call for tenders (IT-2650/LHC/LHC) was sent on 8 November 1999 to eight firms in six Member States. By the closing date, CERN had received four tenders. The Finance Committee is invited to agree to the negotiation of a contract with the firm EISENWERKE KAISERSLAUTERN (DE), the lowest bidder, for the supply of 1 250 LHC dipole thermal shield bottom tray assemblies for a total amount of 6 150 808 euros (9 858 518 Swiss francs), subject to revision for contractual deliveries after 31 December 2001, with an option for the supply of up to 150 additional thermal shield bottom tray assemblies, for a total amount of 696 979 euros (1 117 118 Swiss francs), subject to revision for contractual deliveries after 31 December 2001, bringing the total amount to a maximum of 6 847 787 euros (10 975 636 Swiss francs), subject to...

  16. Structural behavior of cable superconductors

    International Nuclear Information System (INIS)

    Becker, H.; Marston, P.

    1983-01-01

    The structural properties of cable superconductor coils, for particle accelerators such as the Tevatron and the CBA (Colliding Beam Accelerator), depend upon direction of loading. For compression perpendicular to the ''flat faces'' of the conductor, the coils exhibit nonlinear, inelastic and time dependent behavior. The same is true for ''inplane'' compression loading perpendicular to the conductor edges. In the lengthwise direction, the coils display tension and compression stress-strain curves typical of structural metals. The loading of primary concern is compression perpendicular to the conductor faces since deformations in that direction can have a major influence on magnetic field quality. However, the coil behavior under that condition is uncertain because of the nonlinear stress strain curve complicated by creep and relaxation at the stress levels induced by preloading and Lorentz forces. Furthermore, the stiffness of the loading fixture appears to influence the data as shown by results from tests run under different conditions at Berkeley, Brookhaven and MIT. The paper displays test data on stress-strain curves for all three loading directions. Results are presented for RT, 77 K and 4 K behavior. Data of various investigators are compared. The applicability of a relatively simple power law between stress and strain is depicted

  17. Environmental assessment of submarine power cables

    Energy Technology Data Exchange (ETDEWEB)

    Isus, Daniel; Martinez, Juan D. [Grupo General Cable Sistemas, S.A., 08560-Manlleu, Barcelona (Spain); Arteche, Amaya; Del Rio, Carmen; Madina, Virginia [Tecnalia Research and Innovation, 20009 San Sebastian (Spain)

    2011-03-15

    Extensive analyses conducted by the European Community revealed that offshore wind energy have relatively benign effects on the marine environment by comparison to other forms of electric power generation [1]. However, the materials employed in offshore wind power farms suffer major changes to be confined to the marine environment at extreme conditions: saline medium, hydrostatic pressure... which can produce an important corrosion effect. This phenomenon can affect on the one hand, to the material from the structural viewpoint and on the other hand, to the marine environment. In this sense, to better understand the environmental impacts of generating electricity from offshore wind energy, this study evaluated the life cycle assessment for some new designs of submarine power cables developed by General Cable. To achieve this goal, three approaches have been carried out: leaching tests, eco-toxicity tests and Life Cycle Assessment (LCA) methodologies. All of them are aimed to obtaining quantitative data for environmental assessment of selected submarine cables. LCA is a method used to assess environmental aspects and potential impacts of a product or activity. LCA does not include financial and social factors, which means that the results of an LCA cannot exclusively form the basis for assessment of a product's sustainability. Leaching tests results allowed to conclude that pH of seawater did not significantly changed by the presence of submarine three-core cables. Although, it was slightly higher in case of broken cable, pH values were nearly equals. Concerning to the heavy metals which could migrate to the aquatic medium, there were significant differences in both scenarios. The leaching of zinc is the major environmental concern during undersea operation of undamaged cables whereas the fully sectioned three-core cable produced the migration of significant quantities of copper and iron apart from the zinc migrated from the galvanized steel. Thus, the tar

  18. Environmental assessment of submarine power cables

    International Nuclear Information System (INIS)

    Isus, Daniel; Martinez, Juan D.; Arteche, Amaya; Del Rio, Carmen; Madina, Virginia

    2011-03-01

    Extensive analyses conducted by the European Community revealed that offshore wind energy have relatively benign effects on the marine environment by comparison to other forms of electric power generation [1]. However, the materials employed in offshore wind power farms suffer major changes to be confined to the marine environment at extreme conditions: saline medium, hydrostatic pressure... which can produce an important corrosion effect. This phenomenon can affect on the one hand, to the material from the structural viewpoint and on the other hand, to the marine environment. In this sense, to better understand the environmental impacts of generating electricity from offshore wind energy, this study evaluated the life cycle assessment for some new designs of submarine power cables developed by General Cable. To achieve this goal, three approaches have been carried out: leaching tests, eco-toxicity tests and Life Cycle Assessment (LCA) methodologies. All of them are aimed to obtaining quantitative data for environmental assessment of selected submarine cables. LCA is a method used to assess environmental aspects and potential impacts of a product or activity. LCA does not include financial and social factors, which means that the results of an LCA cannot exclusively form the basis for assessment of a product's sustainability. Leaching tests results allowed to conclude that pH of seawater did not significantly changed by the presence of submarine three-core cables. Although, it was slightly higher in case of broken cable, pH values were nearly equals. Concerning to the heavy metals which could migrate to the aquatic medium, there were significant differences in both scenarios. The leaching of zinc is the major environmental concern during undersea operation of undamaged cables whereas the fully sectioned three-core cable produced the migration of significant quantities of copper and iron apart from the zinc migrated from the galvanized steel. Thus, the tar

  19. Application study on the first cable-stayed bridge with CFRP cables in China

    Directory of Open Access Journals (Sweden)

    Kuihua Mei

    2015-08-01

    Full Text Available In order to push forward the development of CFRP cable-stayed bridge and accumulate experiences, the study on the application of the first cable-stayed bridge with CFRP cables in China was carried out. The design essentials of main components of the bridge were introduced and its integral performances, including static properties, dynamic properties and seismic response were analyzed using finite element method. A new bond-type anchorage was developed and the processes of fabricating and installing CFRP cables were elaborated. Based on the results of construction simulation, a tension scheme for bridge was propound. During constructing, the stresses and displacement of girder and pylon, as well as the forces and stresses of cables, were tested. The results indicate that all sections of the bridge could meet the requirements of the ultimate bearing capacity and normal service; the performance of the anchorage is good and the stresses in each cable system are similar; the tested values accord well with the calculated values. Further, creep deformation of the resin in anchorages under service load is not obvious. All these results demonstrate that the first application of CFRP cables in the cable-stayed bridge in China is successful.

  20. Ship nuclear power device of cable aging management

    International Nuclear Information System (INIS)

    Wei Hua; Chen Miao; Chen Tao

    2012-01-01

    Cable for marine nuclear power plant continuous delivery of electrical energy. Cable is mostly in the high temperature and strong radiation and harsh working environment, and can not be replaced in the lifetime This should be the cable aging management methods through research, maintenance and repair program to provide a scientific basis. Cable aging management approach for a number of different levels of cable management at different levels, relying on computers and other modern tools, the use of information management database software maintenance of the cable through the science of aging control. Cable Aging Management including the scope of cable aging management, classification management basis and used for different levels of management supervision and implementation of means testing approach. Application of the ship that has the operational management science, both planned maintenance to improve the science, but also improves the efficiency of aging management. This management method can be extended to nuclear power plants of cable aging management. (authors)

  1. Cable condition monitoring in a pressurized water reactor environment

    International Nuclear Information System (INIS)

    Al-Hussaini, T.J.

    1988-01-01

    Oconee Nuclear Station is the first nuclear plant designed, engineered and constructed by Duke Power Company. Even though the accelerated aging method was available to determine the life expectancy of the cable used in the reactor building, no natural aging data was available at that time. In order to be able to verify the condition of the reactor building cable over the life of the plant, an on-going cable monitoring plan was instituted. Various types of cable were selected to be monitored, and they were installed in cable life evaluation circuits in the reactor building. At five year intervals over the life of the plant, cable samples would be removed from these cable life evaluation circuits and tested to determine the effects of the reactor building environment on the integrity of the cable. A review of the cable life evaluation circuits and the results of the evaluation program to date is presented

  2. Characterization of fiber optic cables under large tensile loads

    International Nuclear Information System (INIS)

    Ogle, J.W.; Looney, L.D.; Peterson, R.T.

    1984-01-01

    Fiber optic cables designed for the Nevada Test Site (NTS) have to withstand an unusually harsh environment. Cables have been manufactured under a 6 year old DOE specification that has been slightly modified as the cable requirements are better understood. In order to better understand the cable properties a unique capability has been established at the NTS. Instrumentation has been developed to characterize the transmission properties of 1 km of fiber optic cable placed under a controlled tensile load up to 1500 lbs. The properties measured are cable tension, cable elongation, induced attenuation, attenuation vs. location, fiber strain, bandwidth, and ambient temperature. Preforming these measurements on cables from the two qualified NTS fiber optic cable manufacturers, Siecor and Andrew Corp., led to a new set of specifications

  3. Applying Diagnostics to Enhance Cable System Reliability (Cable Diagnostic Focused Initiative, Phase II)

    Energy Technology Data Exchange (ETDEWEB)

    Hartlein, Rick [Georgia Tech Research Corporation (GTRC), Atlanta, GA (United States). National Electric Energy Testing, Research and Applications Center (NEETRAC); Hampton, Nigel [Georgia Tech Research Corporation (GTRC), Atlanta, GA (United States). National Electric Energy Testing, Research and Applications Center (NEETRAC); Perkel, Josh [Georgia Tech Research Corporation (GTRC), Atlanta, GA (United States). National Electric Energy Testing, Research and Applications Center (NEETRAC); Hernandez, JC [Univ. de Los Andes, Merida (Venezuela); Elledge, Stacy [Georgia Tech Research Corporation (GTRC), Atlanta, GA (United States). National Electric Energy Testing, Research and Applications Center (NEETRAC); del Valle, Yamille [Georgia Tech Research Corporation (GTRC), Atlanta, GA (United States). National Electric Energy Testing, Research and Applications Center (NEETRAC); Grimaldo, Jose [Georgia Inst. of Technology, Atlanta, GA (United States). School of Electrical and Computer Engineering; Deku, Kodzo [Georgia Inst. of Technology, Atlanta, GA (United States). George W. Woodruff School of Mechanical Engineering

    2016-02-01

    The Cable Diagnostic Focused Initiative (CDFI) played a significant and powerful role in clarifying the concerns and understanding the benefits of performing diagnostic tests on underground power cable systems. This project focused on the medium and high voltage cable systems used in utility transmission and distribution (T&D) systems. While many of the analysis techniques and interpretations are applicable to diagnostics and cable systems outside of T&D, areas such as generating stations (nuclear, coal, wind, etc.) and other industrial environments were not the focus. Many large utilities in North America now deploy diagnostics or have changed their diagnostic testing approach as a result of this project. Previous to the CDFI, different diagnostic technology providers individually promoted their approach as the “the best” or “the only” means of detecting cable system defects.

  4. Durability evaluation of photovoltaic blanket materials exposed on LDEF tray S1003

    International Nuclear Information System (INIS)

    Rutledge, S.K.; Olle, R.M.

    1992-01-01

    Several candidate protective coatings on Kapton and uncoated Kapton were exposed to the low Earth orbital (LEO) environment on the Long Duration Exposure Facility (LDEF) to determine if the coatings could be used to protect polymeric substrates from degradation in the LEO environment. The coatings that were evaluated were 700 A of aluminum oxide, 650 A of silicon dioxide, and 650 A of a 4 percent polytetrafluoroethylene-96 percent silicon dioxide mixed coating. All of the coatings evaluated were ion beam sputter deposited. These materials were exposed to a very low atomic oxygen fluence (4.8 x 10 exp 19 atoms/sq. cm) as a result of the experiment tray being located 98 degrees from the ram direction. As a result of the low atomic oxygen fluence, determination of a change in mass was not possible for any of the samples including the uncoated Kapton. There was no evidence of spalling of any of the coatings after the approximately 33,600 thermal cycles recorded for LDEF. The surface of the uncoated Kapton, however, did show evidence of grazing incidence texturing. There was a 7-8 percent increase in solar absorptance for the silicon dioxide and aluminum oxide coated Kapton and only a 4 percent increase for the mixed coating. It appears that the addition of a small amount of fluoropolymer may reduce the magnitude of absorptance increase due to environmental exposure. Thermal emittance did not change significantly for any of the exposed samples. Scanning electron microscopy revealed few micrometeoroid or debris impacts, but the impact sites found indicated that the extent of damage or cracking of the coating around the defect site did not extend beyond a factor of three of the impact crater diameter. This limiting of impact damage is of great significance for the durability of thin film coatings used for protection against the LEO environment

  5. Feasibility analysis of vacuum sieve tray for tritium extraction in the HCLL test blanket system

    Energy Technology Data Exchange (ETDEWEB)

    Okino, Fumito, E-mail: fumito.okino@iae.kyoto-u.ac.jp [Kyoto University Institute of Advanced Energy, 611-0011 Gokasho, Uji, Kyoto (Japan); Calderoni, Pattrick [Fusion For Energy, 08019 Barcelona (Spain); Kasada, Ryuta; Konishi, Satoshi [Kyoto University Institute of Advanced Energy, 611-0011 Gokasho, Uji, Kyoto (Japan)

    2016-11-01

    Highlights: • The authors discovered faster mass transport on a droplet falling in a vacuum. • Primary cause of the hydrogen release from droplet is by the oscillation of a droplet. • The spherical oscillation induces the internal advection and enhances mass transfer. • This assumption agreed with previous experimental results. - Abstract: This paper describes the quantitative analysis for the design of a tritium extraction system that uses liquid PbLi droplets in vacuum (Vacuum Sieve Tray, VST), for application to the ITER helium-cooled lithium lead (HCLL) test blanket system (TBS). The parametric dependences of tritium extraction efficiency from the main geometrical features such as initial droplet velocity, nozzle head height, nozzle diameter, and flow rate are discussed. With nozzle diameters between 0.4 and 0.6 mm, extraction efficiency is estimated from 0.77 to 0.96 at the falling height of 0.5 m, with flow rate between 0.2 and 1.0 kg/s. The device has a height of 1.6 m, within the external dimensions of the HCLL Test Blanket Module (TBM), and no additional pumping power is required. The attained results are considered attractive not only for ITER, but also in view of the application of the VST concept as a candidate tritium extraction system for the European Union's demonstration fusion reactor (DEMO). The extraction efficiency of a single droplet column, which is the basis of the design analysis presented, has been validated experimentally with hydrogen. However, further experiments are required on an integrated system with size relevant to the proposed HCLL-TBS design to validate system-level effects, particularly regarding the desorption process in an array of multiple droplets.

  6. Change during Psychotherapy through Sand Play Tray in Children That Have Been Sexually Abused

    Directory of Open Access Journals (Sweden)

    María D. L. Angeles Tornero

    2017-05-01

    Full Text Available This paper presents the results of a qualitative study on the use of sandplay, or sand tray therapy, in the psychotherapeutic process of children who have been sexually abused. A longitudinal study was carried out with seven participants between the ages of 7 and 10 years old. Data was produced during observation of the therapeutic activity over the course of three different phases of treatment, using a rubric created especially for this observation. Three sandplay sessions were recorded: one at the start of therapy, one at the 3-month mark, and the third and final session after 6 months of treatment. Sessions were then transcribed for later analysis. A rubric was developed in order to help researchers identify central themes, behaviors and content of creative play, as well as the therapeutic relationship. Transcribed sessions and observation rubrics were evaluated using qualitative content analysis, and information was categorized according to verbal and behavioral characteristics of the game. Results of the present study reveal common and transversal forms of playful expression among this group of children shown by their engagement with sandplay. During this activity, participants elaborate personal stories that feature violence as a central theme, often involving aggression between two or more individuals. They also express their need for care and protection and work to resolve conflicts using fantasy. The shifting dynamics of sandplay at each stage of therapeutic treatment is an important finding that reveals the progress made during psychotherapy. In the third phase of treatment, sandplay encouraged movement among children, allowing them to act out meaningful scenarios and create structured situations with positive outcomes. Finally, the value of sandplay as an important therapeutic tool is discussed, primarily its role in supporting processes of change and allowing participants to assign new meanings to traumatic experiences. Its

  7. Young's moduli of cables for high field superconductive dipole magnet

    International Nuclear Information System (INIS)

    Yamada, Shunji; Shintomi, Takakazu.

    1983-01-01

    Superconductive dipole magnets for big accelerators are subjected to enormous electro-magnetic force, when they are operated with high field such as 10 Tesla. They should be constructed by means of superconductive cables, which have high Young's modulus, to obtain good performance. To develop such cables we measured the Young's moduli of cables for practical use of accelerator magnets. They are monolithic and compacted strand cables. We measured also Young's moduli of monolithic copper and brass cables for comparison. The obtained data showed the Young's moduli of 35 and 15 GPa for the monolithic and compacted strand cables, respectively. (author)

  8. CSNS control cable information management system based on web

    International Nuclear Information System (INIS)

    Lu Huihui; Wang Chunhong; Li Luofeng; Liu Zhengtong; Lei Bifeng

    2014-01-01

    This paper presents an approach to data modeling a great number of control devices and cables with complicated relations of CSNS (China Spallation Neutron Source). The CSNS accelerator control cable database was created using MySQL, and the control cable information management system based on Web was further built. During the development of the database, the design idea of IRMIS database was studied. and the actual situation of CSNS accelerator control cables was investigated. The control cable database model fitting the requirements was designed. This system is of great convenience to manage and maintain CSNS control devices and cables in the future. (authors)

  9. High voltage pulsed cable design: a practical example

    Energy Technology Data Exchange (ETDEWEB)

    Kewish, R.W. Jr.; Boicourt, G.P.

    1979-01-01

    The design of optimum high voltage pulse cable is difficult because very little emperical data are available on performance in pulsed applications. This paper follows the design and testing of one high voltage pulse cable, 40/100 trigger cable. The design was based on an unproven theory and the impressive outcome lends support to the theory. The theory is outlined and it is shown that there exists an inductance which gives a cable of minimum size for a given maximum stress. Test results on cable manufactured according to the design are presented and compared with the test results on the cable that 40/100 replaces.

  10. High voltage pulsed cable design: a practical example

    International Nuclear Information System (INIS)

    Kewish, R.W. Jr.; Boicourt, G.P.

    1979-01-01

    The design of optimum high voltage pulse cable is difficult because very little emperical data are available on performance in pulsed applications. This paper follows the design and testing of one high voltage pulse cable, 40/100 trigger cable. The design was based on an unproven theory and the impressive outcome lends support to the theory. The theory is outlined and it is shown that there exists an inductance which gives a cable of minimum size for a given maximum stress. Test results on cable manufactured according to the design are presented and compared with the test results on the cable that 40/100 replaces

  11. NEPO cable system aging management programs

    International Nuclear Information System (INIS)

    Toman, G.

    2002-01-01

    Full text: Cable polymer aging and condition monitoring is being studied in detail under the Nuclear Energy Plant Optimization Program (NEPO) that is co-sponsored by the U.S. Department of Energy and EPRI. Significant advances in modeling of polymer aging and condition monitoring have occurred and continue to be developed. The activities include: Analysis of the linearity of the Arrhenius model to room temperature; Development of a wear-out technique for determining remaining life of cable polymers; Determination of the aging fragility point for composite EPR/CSPE insulation with respect to LOCA function; Development of visual/tactile training aids for cable assessment; Development of a totally new nuclear magnetic resonance condition monitoring technique; Assessment of existing techniques with regard to repeatability, accuracy and ease of use. Through use of highly precise oxygen consumption experiments, the linearity of the Arrhenius model is being evaluated. In these experiments, polymer is placed in vials with a known amount of oxygen and aged at much lower temperatures than is possible with standard accelerated aging techniques. aging results are possible at room temperature. The technique is being applied to commonly used insulation and jacket polymers. The wear-out technique allows highly non-linear aging behavior to be made linear. The wearout point of a polymer is determined through high-rate aging and use of a condition monitoring technique to establish the end point. Then, micro-samples of cable that have been naturally aged are subjected to high rate aging to the same end point. The ratio of the remaining high rate aging period to the total high rate aging time provides a linear indication of the remaining service time. Initial screening of nuclear plant cable systems can use visual/tactile techniques to identify cable that has aged significantly. Training aids have been developed by developing sets of specimens with accelerated aging ranging from none

  12. Configuration of an inelastic flexible anchored cable

    Directory of Open Access Journals (Sweden)

    T. P. Dreyer

    1992-07-01

    Full Text Available Consider an inelastic, perfectly flexible cable with given external forces acting on the total length of the cable. The one end-point is fixed in the origin and the other end-point is anchored at a given point (a;b;c in space. The resulting configuration of the cable in space can be modelled by a system of non-linear differential equations. In this article it is shown that this continuous model of the cable can always be solved in terms of an integral. In the special case of a constant (i.e. independent of the position on the cable external force per unit length the solution is given explicitly in terms of three constants that describe the tension at the origin. These three constants are determined by the boundary values a, b and c at the other end-point, and must be calculated in general by a numerical procedure from the three resulting simultaneous non-linear equations. A few applications of this method are shown.

  13. Development of innovative superconducting DC power cable

    Energy Technology Data Exchange (ETDEWEB)

    Matsushita, Teruo; Kiuchi, Masaru [Dept. of Computer Science and Electronics Kyushu Institute of Technology, Iizuka (Japan)

    2017-09-15

    It is required to reduce the cost of superconducting cable to realize a superconducting DC power network that covers a wide area in order to utilize renewable energy. In this paper a new concept of innovative cable is introduced that can enhance the current-carrying capacity even though the same superconducting tape is used. Such a cable can be realized by designing an optimal winding structure in such a way that the angle between the tape and magnetic field becomes small. This idea was confirmed by preliminary experiments for a single layer model cable made of Bi-2223 tapes and REBCO coated conductors. Experiments of three and four layer cables of practical sizes were also done and it was found that the current-carrying capacity increased as theoretically predicted. If the critical current properties of commercial superconducting tapes are further improved in a parallel magnetic field, the enhancement will become pronounced and this technology will surely contribute to realization of superconducting DC power network.

  14. External heating of electrical cables and auto-ignition investigation

    Energy Technology Data Exchange (ETDEWEB)

    Courty, L., E-mail: leo.courty@univ-orleans.fr [Univ. Orleans, PRISME EA 4229, 63 Avenue de Lattre de Tassigny, 18020 Bourges (France); Garo, J.P. [Institut P’, UPR 3346 CNRS, ENSMA, Univ. Poitiers, 1 Av. Clément Ader, Téléport 2, BP 40109, 86961 Futuroscope Chasseneuil (France)

    2017-01-05

    Highlights: • Electrical cables pyrolysis and flammability have been studied. • Two different experimental setups were used to study cables mass loss and flammability. • A 1-D thermal model for cables mass loss and temperature is proposed. • Spontaneous and piloted ignitions have been investigated. - Abstract: Electric cables are now extensively used for both residential and industrial applications. During more than twenty years, multi-scale approaches have been developed to study fire behavior of such cables that represents a serious challenge. Cables are rather complicated materials because they consist of an insulated part and jacket of polymeric materials. These polymeric materials can have various chemical structures, thicknesses and additives and generally have a char-forming tendency when exposed to heat source. In this work, two test methods are used for the characterization of cable pyrolysis and flammability. The first one permits the investigation of cable pyrolysis. A description of the cable mass loss is obtained, coupling an Arrhenius expression with a 1D thermal model of cables heating. Numerical results are successfully compared with experimental data obtained for two types of cable commonly used in French nuclear power plants. The second one is devoted to ignition investigations (spontaneous or piloted) of these cables. All these basic observations, measurements and modelling efforts are of major interest for a more comprehensive fire resistance evaluation of electric cables.

  15. External heating of electrical cables and auto-ignition investigation

    International Nuclear Information System (INIS)

    Courty, L.; Garo, J.P.

    2017-01-01

    Highlights: • Electrical cables pyrolysis and flammability have been studied. • Two different experimental setups were used to study cables mass loss and flammability. • A 1-D thermal model for cables mass loss and temperature is proposed. • Spontaneous and piloted ignitions have been investigated. - Abstract: Electric cables are now extensively used for both residential and industrial applications. During more than twenty years, multi-scale approaches have been developed to study fire behavior of such cables that represents a serious challenge. Cables are rather complicated materials because they consist of an insulated part and jacket of polymeric materials. These polymeric materials can have various chemical structures, thicknesses and additives and generally have a char-forming tendency when exposed to heat source. In this work, two test methods are used for the characterization of cable pyrolysis and flammability. The first one permits the investigation of cable pyrolysis. A description of the cable mass loss is obtained, coupling an Arrhenius expression with a 1D thermal model of cables heating. Numerical results are successfully compared with experimental data obtained for two types of cable commonly used in French nuclear power plants. The second one is devoted to ignition investigations (spontaneous or piloted) of these cables. All these basic observations, measurements and modelling efforts are of major interest for a more comprehensive fire resistance evaluation of electric cables.

  16. An evaluation of the fire barrier system thermo-lag 330-1

    International Nuclear Information System (INIS)

    Nowlen, S.P.

    1994-09-01

    This report presents the results of three fire endurance tests and one ampacity derating test set of the fire barrier system Thermo-Lag 330-1 Subliming Coating. Each test was performed using cable tray specimens protected by a nominal three-hour fire barrier envelope comprised of two layers of nominal 1/2 inch thick material. The fire barrier systems for two of the three fire endurance test articles and for the ampacity derating test article were installed in accordance with the manufacturer's installations procedures. The barrier system for the third fire endurance test article was a full reproduction of one of the original manufacturer's qualification test articles. This final test article included certain installation enhancements not considered typical of current nuclear power plant installations. The primary criteria for fire endurance performance evaluation was based on cable circuit integrity testing. Secondary consideration was also given to the temperature rise limits set forth in the ASTM E119 standard fire barrier test procedure. All three of the fire endurance specimens failed prematurely. Circuit integrity failures for the two fire endurance test articles with procedures-based installations were recorded at approximately 76 and 59 minutes into the exposures for a 6 inch wide and 12 inch wide cable tray respectively. Temperature excursion failures (single point) for these two test articles were noted at approximately 65 and 56 minutes respectively. The first circuit integrity failure for the full reproduction test article was recorded approximately 119 minutes into the exposure, and the first temperature excursion failure for this test article was recorded approximately 110 minutes into the exposure

  17. Frequency Dependent Losses in Transmission Cable Conductors

    DEFF Research Database (Denmark)

    Olsen, Rasmus Schmidt; Holbøll, Joachim; Guðmundsdóttir, Unnur Stella

    2011-01-01

    , such as thermal conditions in and around the cable, as well as the heat generated in conductors, screens, armours etc., taking into account proximity and skin effects. The work performed and presented in this paper is concerned with an improved determination of the losses generated in the conductor, by means...... of better calculation of the AC resistance of transmission cable conductors, in particular regarding higher frequencies. In this way, also losses under harmonics can be covered. Furthermore, the model is suitable for modelling of transient attenuation in high voltage cables. The AC resistance is calculated...... based on the current density distribution in different conductor designs by means of the Finite Element Method (FEM). The obtained results and methods are compared to available standards (IEC publication 60287-1-1)....

  18. Distance and Cable Length Measurement System

    Science.gov (United States)

    Hernández, Sergio Elias; Acosta, Leopoldo; Toledo, Jonay

    2009-01-01

    A simple, economic and successful design for distance and cable length detection is presented. The measurement system is based on the continuous repetition of a pulse that endlessly travels along the distance to be detected. There is a pulse repeater at both ends of the distance or cable to be measured. The endless repetition of the pulse generates a frequency that varies almost inversely with the distance to be measured. The resolution and distance or cable length range could be adjusted by varying the repetition time delay introduced at both ends and the measurement time. With this design a distance can be measured with centimeter resolution using electronic system with microsecond resolution, simplifying classical time of flight designs which require electronics with picosecond resolution. This design was also applied to position measurement. PMID:22303169

  19. Computer-Aided Engineering Of Cabling

    Science.gov (United States)

    Billitti, Joseph W.

    1989-01-01

    Program generates data sheets, drawings, and other information on electrical connections. DFACS program, centered around single data base, has built-in menus providing easy input of, and access to, data for all personnel involved in system, subsystem, and cabling. Enables parallel design of circuit-data sheets and drawings of harnesses. Also recombines raw information to generate automatically various project documents and drawings, including index of circuit-data sheets, list of electrical-interface circuits, lists of assemblies and equipment, cabling trees, and drawings of cabling electrical interfaces and harnesses. Purpose of program to provide engineering community with centralized data base for putting in, and gaining access to, functional definition of system as specified in terms of details of pin connections of end circuits of subsystems and instruments and data on harnessing. Primary objective to provide instantaneous single point of interchange of information, thus avoiding

  20. Radiation techology in cable making industry

    International Nuclear Information System (INIS)

    Kourim, P.; Vokal, A.

    1985-01-01

    Electron accelerators are used in radiation cross-linking of elastomer and thermoplastic layers of cable insulation and sheathing. Another application is cross-linking of insulation bands and moulded products to achieve thermal contractibility. Ionizing radiation is used for curing insulation lacquers on winding leads. In Czechoslovakia, problems of radiation curing of silicone rubber have been studied since 1973. Instrumentation has been installed including accelerators. The feasibility has also been studied of radiation cross-linking of insulation and semiconductor cable cores of hose-type trailing cables. Polyethylene mixes have been designed and prepared which are suitable for radiation cross-linking aimed at increasing thermal resistance above 100 degC. (M.D.)

  1. Power applications for superconducting cables in Denmark

    DEFF Research Database (Denmark)

    Tønnesen, Ole; Østergaard, Jacob; Olsen, S. Krüger

    1999-01-01

    In Denmark a growing concern for environmental protection has lead to wishes that the open country is kept free of overhead lines as far as possible. New lines under 100 kV and existing 60/50 kV lines should be established as underground cables. Superconducting cables represent an interesting...... in cases such as transmission of energy into cities and through areas of special interest. The planned large groups of windmills in Denmark generating up to 2000 MVA or more both on dry land and off-shore will be an obvious case for the application of superconducting AC or DC cables. These opportunities...... can be combined with other new technologies such as HVDC light transmission using isolated gate bipolar transistors (IGBTs). The network needed in a system with a substantial wind power generation has to be very strong in order to handle energy fluctuations. Such a network will be possible...

  2. Electrothermal Coordination in Cable Based Transmission Grids

    DEFF Research Database (Denmark)

    Olsen, Rasmus Schmidt; Holbøll, Joachim; Gudmundsdottir, Unnur Stella

    2013-01-01

    behavior of the components. The dynamic temperature calculations of power cables are suggested to be based on thermoelectric equivalents (TEEs). It is shown that the thermal behavior can be built into widely used load flow software, creating a strong ETC tool. ETC is, through two case scenarios, proven...... to be beneficial for both operator and system planner. It is shown how the thermal behavior can be monitored in real-time during normal dynamic load and during emergencies. In that way, ETC enables cables to be loaded above their normal rating, while maintaining high reliability of the system, which potentially...

  3. The Schmehausen cable net cooling tower

    International Nuclear Information System (INIS)

    Schlaich, J.; Mayr, G.; Weber, P.; Jasch, E.

    1976-01-01

    The prototype of a large cable net shell as a natural-draught cooling tower for the THTR-300 is presented. Results of wind tunnel tests and calculations are given, and the capacity is discussed. Design features of the main components are presented in illustrations and are described with regard to the construction process of the cooling tower. Finally, it is shown that the cable net cooling tower is a suitable construction for large dimensions and caving-in or seismic areas. (orig./HP) [de

  4. Relative stiffness of flat conductor cables

    Science.gov (United States)

    Hankins, J. D.

    1976-01-01

    The measurement of the bending moment required to obtain a given deflection in short lengths of flat conductor cable (FCC) is presented in this report. Experimental data were taken on 10 different samples of FCC and normalized to express all bending moments (relative stiffness factor) in terms of a cable 5.1 cm (2.0 in.) in width. Data are presented in tabular and graphical form for the covenience of designers who may be interested in finding torques exerted on critical components by short lengths of FCC.

  5. Modeling of Pressure Effects in HVDC Cables

    DEFF Research Database (Denmark)

    Szabo, Peter; Hassager, Ole; Strøbech, Esben

    1999-01-01

    A model is developed for the prediction of pressure effects in HVDC mass impregnatedcables as a result of temperature changes.To test the model assumptions, experiments were performed in cable like geometries.It is concluded that the model may predict the formation of gas cavities.......A model is developed for the prediction of pressure effects in HVDC mass impregnatedcables as a result of temperature changes.To test the model assumptions, experiments were performed in cable like geometries.It is concluded that the model may predict the formation of gas cavities....

  6. Analysis of Electrical Coupling Parameters in Superconducting Cables

    CERN Document Server

    Bottura, L; Rosso, C

    2003-01-01

    The analysis of current distribution and redistribution in superconducting cables requires the knowledge of the electric coupling among strands, and in particular the interstrand resistance and inductance values. In practice both parameters can have wide variations in cables commonly used such as Rutherford cables for accelerators or Cable-in-Conduits for fusion and SMES magnets. In this paper we describe a model of a multi-stage twisted cable with arbitrary geometry that can be used to study the range of interstrand resistances and inductances that is associated with variations of geometry. These variations can be due to cabling or compaction effects. To describe the variations from the nominal geometry we have adopted a cable model that resembles to the physical process of cabling and compaction. The inductance calculation part of the model is validated by comparison to semi-analytical results, showing excellent accuracy and execution speed.

  7. Manufacturing experience for the LHC inner triplet quadrupole cables

    CERN Document Server

    Scanlan, R M; Bossert, R; Kerby, J S; Ghosh, A K; Boivin, M; Roy, T

    2002-01-01

    The design for the U.S. LHC Inner Triplet Quadrupole magnet requires a 37 strand (inner layer) and a 46 strand (outer layer) cable. This represents the largest number of strands attempted to date for a production quantity of Rutherford-type cable. The cable parameters were optimized during the production of a series of short prototype magnets produced at FNAL. These optimization studies focused on critical current degradation, dimensional control, coil winding, and interstrand resistance. After the R&D phase was complete, the technology was transferred to NEEW and a new cabling machine was installed to produce these cables. At present, about 60 unit lengths, out of 90 required for the entire production series of magnets, have been completed for each type of cable. The manufacturing experience with these challenging cables will be reported. Finally, the implications for even larger cables, with more strands, will be discussed. (8 refs).

  8. Energy analysis of vehicle-to-cable barrier impacts.

    Science.gov (United States)

    2013-06-01

    An accident reconstruction technique was developed for estimating the energy absorbed during an impact with a cable barrier system as well as the initial impact velocity. The kinetic energy absorbed during a cable barrier system impact is comprised o...

  9. Device to take up slack in monorail cables

    Energy Technology Data Exchange (ETDEWEB)

    Szymanski, J

    1978-08-01

    This paper discusses the necessity to take up the slack of a monorail cable in an HBNPC mine in order to ensure good adhesion between the metal cable and the pulley. A new device has been tested with satisfactory results.

  10. Power plant cable condition monitoring and testing at Georgia Power

    International Nuclear Information System (INIS)

    Champion, T.C.

    1988-01-01

    Georgia Power's Research Center has been heavily involved in the evaluation of electrical insulating materials and cables since its inception more than 17 years ago. For the past ten years that expertise has been applied to cables used in generation plants. This paper discusses the results of two test programs. The first is a quality control inspection on 169 samples of new power generation cables. The second is a material degradation evaluation on four short cable samples removed from a coal fired plant during an equipment upgrade. The new material evaluation was performed to identify the cause of a high failure rate upon initial hi-pot testing of newly installed cables. The material degradation evaluation was performed to evaluate the need for replacement of existing cables during an equipment upgrade. Results of the evaluations have led to development of a detailed proposal for a program to evaluate cable degradation and remaining life for cables used in power generation facilities

  11. Configuration Synthesis for Fully Restrained 7-Cable-Driven Manipulators

    Directory of Open Access Journals (Sweden)

    Xiaoqiang Tang

    2012-10-01

    Full Text Available Cable distribution plays a vital role in Cable Driven Parallel Manipulators (CDPMs regarding tension and workspace quality, especially in fully restrained CDPMs. This paper focuses on three typical configurations of fully restrained CDPMs with 7 cables in order to introduce an approach for configuration synthesis. Firstly, the kinematic models of three types of CDPMs with 7 cables are set up. Then, in order to evaluate workspace quality, two new indices are proposed by using tensions along each cable, which are the All Cable Tension Distribution Index (ACTDI and Global Tension Distribution Index (GTDI. Next, the three types of CDPMs with 7 cables are analysed with the two indices. At the end, according to different performance requirements, the configurations of cable distribution are discussed and selected.

  12. Superscreened co-axial cables for the nuclear power industry

    International Nuclear Information System (INIS)

    1977-05-01

    This specification covers the requirements of superscreened cables. Part 1 covers general requirements and test methods. Part 2 covers data sheets setting out the electrical and mechanical requirements for each type of cable, together with engineering information. (U.K.)

  13. Fault Management of a Cold Dielectric HTS Power Transmission Cable

    International Nuclear Information System (INIS)

    Maguire, J; Allais, A; Yuan, J; Schmidt, F; Hamber, F; Welsh, Tom

    2006-01-01

    High temperature superconductor (HTS) power transmission cables offer significant advantages in power density over conventional copper-based cables. As with conventional cables, HTS cables must be safe and reliable when abnormal conditions, such as local and through faults, occur in the power grid. Due to the unique characteristics of HTS power cables, the fault management of an HTS cable is different from that of a conventional cable. Issues, such as nitrogen bubble formation within lapped dielectric material, need to be addressed. This paper reviews the efforts that have been performed to study the fault conditions of a cold dielectric HTS power cable. As a result of the efforts, a fault management scheme has been developed, which provides both local and through faults system protection. Details of the fault management scheme with examples are presented

  14. Composite carbon fiber cables; Des cables composites en fibres de carbone

    Energy Technology Data Exchange (ETDEWEB)

    Anon.

    2002-10-01

    In order to fulfill the requirements of offshore engineering, Freyssinet, a daughter company of the European Vinci group, has developed a series of high-performance carbon fiber cables. These composite materials have an excellent fatigue behaviour in a huge range of constraints. Moreover, their low weight allows the implementation of very long lengths of cables in marine environment with no loss in capacity. The specific weight of the current part of the cable is reduced by a factor of 4 with respect to an equivalent capacity armature made of steel. These materials were presented in June 2002 at the ultra deep engineering and technologies (UDET) exhibition of Brest (France). (J.S.)

  15. Solid phase radioimmunoassay for plasma testosterone using a plastic microtiter tray

    International Nuclear Information System (INIS)

    Hosogi, Hidemi

    1975-01-01

    In order to simplify radioimmunoassay for plasma testosterone and to measure many samples at the same time, a method of solid phase radioimmunoassay utilizing a plastic disposable microtiter tray (DMT) by which chromatography can be omitted was investigated. Other steroids except for 5α-dihydrotestosterone (5α-DHT) had a low degree of cross reactivity with the antiserum. Five α-DHT which could be measured together with testosterone in this assay was not a problem clinically because of its strong androgenic activity. The best standard curve was obtained when the antiserum was diluted to 1:1000. The sensitivity of this assay was 10 pg-tube. The maximal adsorption of antibody to plastic DMT was observed when the pH of the antiserum was within the range of 6.5-9.5 and the precoating time was 24 hr at room temperature. The best pH of the incubation buffer was 0.8, and the antigen-antibody reaction became a plateau when the incubation exceeded 6 hrs. The water blank in this assay was 4.6 +- 2.1 pg/tube. The recovery of testosterone (50, 100, 200 pg) when added to 0.1 ml female plasma was 99 +- 6.8%. Coefficients of variation within assay and between assays were below 11.2% and 20.0%, respectively. Correlation between this method and the dextran-coated charcoal method was fairly good (r=0.938). Plasma testosterone levels in 10 normal males and 12 normal females were 616 +- 202 (mean +- SD) ng/dl and 66 +- 29 (mean +- SD) ng/dl, respectively. The levels were low in patients with hypopituitarism, hypogonadism and acromegaly. They were normal in patients with Cushing's syndrome due to adrenal hyperplasia and adenoma, but they were high in a patient with adrenal carcinoma. In a patient with testicular feminization, the level was 632 ng/dl. This increased after the administration of HCG, and decreased to 127.5 ng/dl after castration. (auth.)

  16. Accuracy of a reformulated fast-set vinyl polysiloxane impression material using dual-arch trays.

    Science.gov (United States)

    Kang, Alex H; Johnson, Glen H; Lepe, Xavier; Wataha, John C

    2009-05-01

    A common technique used for making crown impressions involves use of a vinyl polysiloxane impression material in combination with a dual-arch tray. A leading dental manufacturer has reformulated its vinyl polysiloxane (VPS) impression line, but the accuracy of the new material has not been verified. The purpose of this study was to assess the accuracy of reformulated VPS impression materials using the single-step dual-arch impression technique. Dual-arch impressions were made on a typodont containing a master stainless steel standard crown preparation die, from which gypsum working dies were formed, recovered, and measured. The impression materials evaluated were Imprint 3 Penta Putty with Quick Step Regular Body (IP-0); Imprint 3 Penta Quick Step Heavy Body with Quick Step Light Body (IP-1); Aquasil Ultra Rigid Fast Set with LV Fast Set (AQ-1); and Aquasil Ultra Heavy Fast Set with XLV Fast Set (AQ-2) (n=10). All impressions were disinfected with CaviCide spray for 10 minutes prior to pouring with type IV gypsum. Buccolingual (BL), mesiodistal (MD), and occlusogingival (OG) dimensions were measured and compared to the master die using an optical measuring microscope. Linear dimensional change was also assessed for IP-0 and AQ-1 at 1 and 24 hours based on ANSI/ADA Specification No. 19. Single-factor ANOVA with Dunnett's T3 multiple comparisons was used to compare BL, MD, and OG changes, with hypothesis testing at alpha=.05. A repeated-measures ANOVA was used to compare linear dimensional changes. There were statistical differences among the 4 impression systems for 3 of 4 dimensions of the master die. IP-0 working dies were significantly larger in MD and OG-L dimensions but significantly smaller in the BL dimension. IP-1 working dies were significantly smaller in the BL dimension compared to the master die. With the exception of IP-0, differences detected were small and clinically insignificant. No significant differences were observed for linear dimensional change

  17. SSC 40 mm cable results and 50 mm design discussions

    International Nuclear Information System (INIS)

    Christopherson, D.; Capone, D.; Hannaford, R.; Remsbottom, R.; Delashmit, R.; Jayakumar, R.J.; Snitchler, G.; Scanlan, R.; Royet, J.

    1991-01-01

    This paper presents a summary of the cable produced for the 1990 40 mm Dipole Program. The cable design parameters for the 50 mm Dipole Program are discussed, as well as portions of the SSC specification draft. Considerations leading to the final cable configuration and the results of preliminary trials are included. The first iteration of a strand mapping program to automate cable strand maps is introduced

  18. SSC 40 mm cable results and 50 mm design discussions

    International Nuclear Information System (INIS)

    Christopherson, D.; Capone, D.; Hannaford, R.; Remsbottom, R.; Jayakumar, R.; Snitchler, G.; Scanlan, R.; Royet, J.

    1990-09-01

    A summary of the cable produced for the 1990 40 mm Dipole Program is presented. The cable design parameters for the 50 mm Dipole Program are discussed, as well as portions of the SSC specification draft. Considerations leading to the final cable configuration and the results of preliminary trials are included. The first iteration of a strand mapping program to automate cable strand maps is introduced. 7 refs., 2 figs., 1 tab

  19. 47 CFR 27.1202 - Cable/BRS cross-ownership.

    Science.gov (United States)

    2010-10-01

    ... portion of the franchise area actually served by the cable operator's cable system and the cable operator... franchise area actually served by the cable operator's cable system the cable operator will use the BRS... that no portion of the GSA of the BRS station is within the portion of the franchise area actually...

  20. Cable Television 1980: Status and Prospect for Higher Education.

    Science.gov (United States)

    Baus, F., Ed.

    Baseline information for the would-be cable television educational programer is provided by two papers, one an overview of the state of the cable television industry, and the other a report on a marketing study conducted to determine consumer attitudes toward cable TV as an educational medium. In "The Promise and Reality of Cable…

  1. 24 CFR 3285.704 - Telephone and cable TV.

    Science.gov (United States)

    2010-04-01

    ... 24 Housing and Urban Development 5 2010-04-01 2010-04-01 false Telephone and cable TV. 3285.704....704 Telephone and cable TV. Refer to § 3285.906 for considerations pertinent to installation of telephone and cable TV. ...

  2. 30 CFR 75.804 - Underground high-voltage cables.

    Science.gov (United States)

    2010-07-01

    ... AND HEALTH MANDATORY SAFETY STANDARDS-UNDERGROUND COAL MINES Underground High-Voltage Distribution § 75.804 Underground high-voltage cables. (a) Underground high-voltage cables used in resistance... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Underground high-voltage cables. 75.804 Section...

  3. 75 FR 61116 - Refunds Under the Cable Statutory License

    Science.gov (United States)

    2010-10-04

    ... Copyright Act, before it was amended to allow a cable system to calculate its royalty fees on a community-by... statutory license set forth in Section 111 are required to pay royalty fees to the Copyright Office... the methodology for a cable operator to calculate royalty fees. Cable operators now pay royalty fees...

  4. 47 CFR 76.111 - Cable sports blackout.

    Science.gov (United States)

    2010-10-01

    ... 47 Telecommunication 4 2010-10-01 2010-10-01 false Cable sports blackout. 76.111 Section 76.111... CABLE TELEVISION SERVICE Network Non-duplication Protection, Syndicated Exclusivity and Sports Blackout § 76.111 Cable sports blackout. (a) No community unit located in whole or in part within the specified...

  5. 46 CFR 111.60-6 - Fiber optic cable.

    Science.gov (United States)

    2010-10-01

    ... 46 Shipping 4 2010-10-01 2010-10-01 false Fiber optic cable. 111.60-6 Section 111.60-6 Shipping COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED) ELECTRICAL ENGINEERING ELECTRIC SYSTEMS-GENERAL REQUIREMENTS Wiring Materials and Methods § 111.60-6 Fiber optic cable. Each fiber optic cable must— (a) Be...

  6. 30 CFR 75.600 - Trailing cables; flame resistance.

    Science.gov (United States)

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Trailing cables; flame resistance. 75.600 Section 75.600 Mineral Resources MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR COAL MINE... cables; flame resistance. [Statutory Provisions] Trailing cables used in coal mines shall meet the...

  7. 30 CFR 75.600-1 - Approved cables; flame resistance.

    Science.gov (United States)

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Approved cables; flame resistance. 75.600-1 Section 75.600-1 Mineral Resources MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR COAL MINE... cables; flame resistance. Cables shall be accepted or approved by MSHA as flame resistant. [57 FR 61223...

  8. Working Paper for the Revision of San Francisco's Cable Franchise.

    Science.gov (United States)

    San Francisco Public Library, CA. Video Task Force.

    Ideas are presented for the revision of San Francisco's cable franchise. The recommendations in the report are based upon national research of library and urban use of cable communications and are designed to help the city's present and future cable franchises to comply with the regulations of the Federal Communications Commission by March 31,…

  9. A simulated-annealing-based approach for wind farm cabling

    NARCIS (Netherlands)

    Lehmann, S.; Rutter, I.; Wagner, D.; Wegner, F.

    2017-01-01

    We study the problem of computing a wind farm cabling with minimum costs allowing different cable types. Our model distinguishes different levels of granularity, where the highest level represents the cabling problem for the whole wind farm. Since even the most restricted of these problems is

  10. Cable Television: Technical Considerations in Franchising Major Market Systems.

    Science.gov (United States)

    Pilnick, Carl

    The 1972 Federal Communications Commission's (FCC) regulations on cable television were intended to assist the penetration of cable television into the large metropolitan regions of the United States. In these major market areas, the task for developing an appropriate franchise is complicated by the changing functional nature of the cable systems…

  11. 46 CFR 111.12-9 - Generator cables.

    Science.gov (United States)

    2010-10-01

    ... 46 Shipping 4 2010-10-01 2010-10-01 false Generator cables. 111.12-9 Section 111.12-9 Shipping... REQUIREMENTS Generator Construction and Circuits § 111.12-9 Generator cables. (a) The current-carrying capacity of generator cables must not be: (1) Less than 115 percent of the continuous generator rating; or (2...

  12. 7 CFR 1755.870 - RUS specification for terminating cables.

    Science.gov (United States)

    2010-01-01

    ... core wrap. (f) Shield. (1) An aluminum shield, plastic coated on one side, shall be applied... section establishes the requirements for terminating cables used to connect incoming outside plant cables... cylindrical core. (iii) The cable structure is completed by the application of a core wrap, a shield, and a...

  13. 30 CFR 75.817 - Cable handling and support systems.

    Science.gov (United States)

    2010-07-01

    ... High-Voltage Longwalls § 75.817 Cable handling and support systems. Longwall mining equipment must be provided with cable-handling and support systems that are constructed, installed and maintained to minimize... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Cable handling and support systems. 75.817...

  14. Environmental Impact of a Submarine Cable: Case Study of the Acoustic Thermometry of Ocean Climate (ATOC)/ Pioneer Seamount Cable

    Science.gov (United States)

    Kogan, I.; Paull, C. K.; Kuhnz, L.; von Thun, S.; Burton, E.; Greene, H. G.; Barry, J. P.

    2003-12-01

    To better understand the potential impacts of the presence of cables on the seabed, a topic of interest for which little data is published or publicly available, a study of the environmental impacts of the ATOC/Pioneer Seamount cable was conducted. The 95 km long, submarine, coaxial cable extends between Pioneer Seamount and the Pillar Point Air Force Station in Half Moon Bay, California. Approximately two thirds of the cable lies within the Monterey Bay National Marine Sanctuary. The cable is permitted to NOAA- Oceanic and Atmospheric Research for transmitting data from a hydrophone array on Pioneer Seamount to shore. The cable was installed unburied on the seafloor in 1995. The cable path crosses the continental shelf, descends to a maximum depth of 1,933 m, and climbs back upslope to 998 m depth near the crest of Pioneer Seamount. A total of 42 hours of video and 152 push cores were collected in 10 stations along cable and control transects using the ROVs Ventana and Tiburon equipped with cable-tracking tools. The condition of the cable, its effect on the seafloor, and distribution of benthic megafauna and infauna were determined. Video data indicated the nature of interaction between the cable and the seafloor. Rocky nearshore areas, where wave energies are greatest, showed the clearest evidence of impact. Here, evidence of abrasion included frayed and unraveling portions of the cable's armor and vertical grooves in the rock apparently cut by the cable. The greatest incision and armor damage occurred on ledges between spans in irregular rock outcrop areas. Unlike the nearshore rocky region, neither the rocks nor the cable appeared damaged along outcrops on Pioneer Seamount. Multiple loops of slack cable added during a 1997 cable repair operation were found lying flat on the seafloor. Several sharp kinks in the cable were seen at 240 m water depths in an area subjected to intense trawling activity. Most of the cable has become buried with time in sediment

  15. Broadband Wireline Provider Service: Cable Modem - DOCSIS 3.0; BBRI_cableDOCSIS12

    Data.gov (United States)

    University of Rhode Island Geospatial Extension Program — This dataset represents the availability of wireline broadband Internet access in Rhode Island via "Cable Modem - DOCSIS 3.0" technology. Broadband availability is...

  16. Broadband Wireline Provider Service: Cable Modem - Other; BBRI_cableOther12

    Data.gov (United States)

    University of Rhode Island Geospatial Extension Program — This dataset represents the availability of wireline broadband Internet access in Rhode Island via "Cable Modem - Other" technology. Broadband availability is...

  17. Aluminium cables in automotive applications : Prestudy of aluminium cable uses in Scania products&Failure analysis and evaluation

    OpenAIRE

    Man, Yu

    2016-01-01

    The increasing demand of light constructed vehicles as well as soaring price of copper metal owing to limited nature resources have been promoting the use of aluminium metal as an alternative conductor of automotive cables. This thesis work is to lay theoretical foundations for further research and development regarding the introduction of new automotive cables i.e. aluminium cables. Current application of automotive aluminium cables in automotive industry as well as failure analysis and eval...

  18. NRC Information Notice No. 92-01: Cable damage caused by inadequate cable installation procedures and controls

    International Nuclear Information System (INIS)

    Rossi, C.E.

    1993-01-01

    In June 1989, the Tennessee Valley Authority (TVA) removed the cables from a conduit in the reactor protection system of the Watts Bar Nuclear Plant, Unit 2, to inspect for damage. TVA selected this conduit in response to an employee's concern that a welding arc that struck the conduit in response to an employee's concern that a welding arc that struck the conduit during construction may have damaged cables in the conduit. When the cables were removed, TVA found significant damage in the insulation of some cables. This damage was not attributed to heat generated by the alleged welding arc. The damage was principally attributed to the pulling stresses exerted during the initial installation of the cables. Some of the cables had insulation removed down to the conductors. To assess the extent of cable damage and determine the scope of its investigation, TVA removed more cables from conduits that constituted the most difficult pulls (worst case) and found varying degrees of damage that it attributed to pulling stresses. To fill a conduit at Watts Bar, personnel used pull cords to pull more cables through the conduits over the top of existing cables. This practice is called ''pull-by.'' This practice can cause damage to the existing cables from the sawing action of the pull cords and the friction of cables as they are pulled over existing cables. TVA instituted programs to assess the adequacy of cable installation at all its nuclear facilities and take appropriate corrective actions. At Watts Bar, TVA replaced cables in conduits which exceeded a calculated threshold value of side wall bearing pressure (SWBP) and performed a high-potential (hi-pot) tests on a number of other cables in conduits with SWBP below the calculated threshold value

  19. Mineral insulated cables for post accident service

    International Nuclear Information System (INIS)

    McMillin, P.L.; Winkler, M.E.

    1986-01-01

    The regulatory requirement to measure the gamma radiation levels during accident conditions inside a reactor containment building is discussed. The development of a mineral-insulated cable and connector system to accurately transmit this measurement is described and a model of the response is developed

  20. AC loss in superconducting tapes and cables

    NARCIS (Netherlands)

    Oomen, M.P.

    2000-01-01

    The present study discusses the AC loss in high-temperature superconductors. Superconducting materials with a relatively high critical temperature were discovered in 1986. They are presently developed for use in large-scale power-engineering devices such as power-transmission cables, transformers

  1. History of cable-stayed bridges

    DEFF Research Database (Denmark)

    Gimsing, Niels Jørgen

    1999-01-01

    The principle of supporting a bridge deck by inclined tension members leading to towers on either side of the span has been known for centuries. However, the real development of cable-stayed bridges did not begin before the 1950s. Since then the free span has been increased from 183 m in the Strö...

  2. Improved cable insulation for superconducting magnets

    International Nuclear Information System (INIS)

    Anerella, M.; Ghosh, A.K.; Kelly, E.; Schmalzle, J.; Willen, E.; Fraivillig, J.; Ochsner, J.; Parish, D.J.

    1993-01-01

    Several years ago, Brookhaven joined with DuPont in a cooperative effort to develop improved cable insulation for SSC superconducting dipole magnets. The effort was supported by the SSC Central Design Group and later the SSC Laboratory. It was undertaken because turn-to-turn and midplane shorts were routinely being experienced during the assembly of magnets with coils made of the existing Kapton/fiberglass (K/FG) system of Kapton film overwrapped with epoxy-impregnated fiberglass tape. Dissection of failed magnets showed that insulation disruption and punch-through was occurring near the inner edges of turns close to the magnet midplane. Coil pressures of greater than 17 kpsi were sufficient to disrupt the insulation at local high spots where the cable had been strongly compacted in the keystoning operation during cable manufacture. In the joint development program, numerous combinations of polyimide films manufactured by DuPont with varying configurations and properties (including thickness) were subjected to tests at Brookhaven. Early tests were bench trials using wrapped cable samples. The most promising candidates were used in coils and many of these promising candidates were used in coils and many of these assembled and tested as magnets in both the SSC and RHIC magnet programs currently underway. The Kapton CI (CI) system that has been adopted represents a suitable compromise of numerous competing factors. It exhibits improved performance in the critical parameter of compressive punch-through resistance as well as other advantages over the K/FG system

  3. Cable Television for Librarians. Ordinances and Franchises

    Science.gov (United States)

    Drexel Library Quarterly, 1973

    1973-01-01

    A short lecture is presented on how librarians can incorporate their programing into that of existing and future cable television stations. The lecture was followed by a question/answer period. (Other conference materials are LI 503071-503076 and 503078 through 503084.) (SM)

  4. Improved cable insulation for superconducting magnets

    International Nuclear Information System (INIS)

    Anerella, M.; Ghosh, A.K.; Kelly, E.; Schmalzle, J.; Willen, E.; Fraivillig, J.; Ochsner, J.; Parish, D.J.

    1993-01-01

    Several years ago, Brookhaven joined with DuPont in a cooperative effort to develop improved cable insulation for SSC superconducting dipole magnets. The effort was supported by the SSC Central Design Group and later the SSC Laboratory. It was undertaken because turn-to-turn and midplane shorts were routinely being experienced during the assembly of magnets with coils made of the existing Kapton/Fiberglass (K/FG) system of Kapton film overwrapped with epoxy-impregnated fiberglass tape. Dissection of failed magnets showed that insulation disruption and punch-through was occurring near the inner edges of turns close to the magnet midplane. Coil pressures of greater than 17 kpsi were sufficient to disrupt the insulation at local high spots where wires in neighboring turns crossed one another and where the cable had been strongly compacted in the keystoning operation during cable manufacture. In the joint development program, numerous combinations of polyimide films manufactured by DuPont with varying configurations and properties (including thickness) were subjected to tests at Brookhaven. Early tests were bench trials using wrapped cable samples. The most promising candidates were used in coils and many of these assembled and tested as magnets in both the SSC and RHIC magnet programs currently underway. The Kapton CI (CI) system that has been adopted represents a suitable compromise of numerous competing factors. It exhibits improved performance in the critical parameter of compressive punch-through resistance as well as other advantages over the K/FG system

  5. Optimization of bridge cables with concave fillets

    DEFF Research Database (Denmark)

    Burlina, Celeste; Georgakis, Christos T.; Larsen, Søren V.

    In this paper the aerodynamic performance of new cable surfaces with concave fillet are examined and compared to plain, dimpled and helically filleted surfaces. To this end, an extensive wind-tunnel campaign was undertaken. Preliminary flow visualizations tests and static tests were performed to ...

  6. Cinema Futures: Cain, Abel or Cable?

    NARCIS (Netherlands)

    Elsaesser, Thomas; Hoffmann, Kay

    1998-01-01

    In the late 1960s, the cinema was pronounced dead. Television, like a Biblical Cain had slain his brother Abel. Some thirty years later, a remarkable reversal: rarely has the cinema been more popular. And yet, rarely has the cinema's future seemed more uncertain. Cinema Futures: Cain, Abel or Cable?

  7. Wide-band cable systems at SLAC

    International Nuclear Information System (INIS)

    Struven, W.

    1983-01-01

    SLAC's first cable TV system was installed in 1979 to remotely monitor a narrow pulse which was generated in the west end of the klystron gallery. When Stanford Linear Collider (SLC) experimental work started at the west end of the accelerator, the original 1979 cable was upgraded to a bidirectional system so that 2 MBaud point-to-point data and several video and 9600 baud channels could be transmitted. The implementation of the SLC requires a complete upgrading of the accelerator control system. The system is based on a distributed processing configuration using a PDP11/780 VAX in the Main Control Center (MCC) and Intel single-board computers in a multibus configuration along the accelerator. The high-speed data linking is supplied by a 1 MBaud Time Division Multiple Access (TDMA) Network. The same cable is used to provide video, low-speed data, voice and high-speed point-to-point data services. The transmission system will utilize a wideband midsplit cable facility to collect and distribute signals to all parts of the network

  8. Cable Design for FAIR SIS 300

    NARCIS (Netherlands)

    Kaugerts, J.; Moritz, G.; Wilson, M.N.; Ghosh, A.K.; den Ouden, A.

    GSI, Darmstadt is preparing to build FAIR (Facility for Antiproton and Ion Research) which include SIS 300, a 300T - m fast-ramping heavy ion synchrotron. Dipoles for this ring will be 2.9 m long, producing 6 T over a 100 mm coil aperture and ramped at 1 T/s. The cable for these dipoles must have

  9. Microminiature coaxial cable and methods manufacture

    Science.gov (United States)

    Bongianni, W.L.

    1986-04-08

    A coaxial cable is provided having a ribbon inner conductor surrounded by a dielectric and a circumferential conductor. The coaxial cable may be microminiature comprising a very thin ribbon strip conductor from between 5 to 15 [mu]m thick and from 150 to 200 [mu]m wide, having a surrounding foamed dielectric or parylene applied thereon by a vapor plasma process and an outer conductor of an adhering high conductivity metal vacuum deposited on the dielectric. Alternately the foam dielectric embodiment may have a contiguous parylene coating applied adjacent the inner conductor or the outer conductor or both. Also, the cable may be fabricated by forming a thin ribbon of strip conductive material into an inner conductor, applying thereabout a dielectric by spraying on a solution of polystyrene and polyethylene and then vacuum depositing and adhering high conductivity metal about the dielectric. The cable strength may be increased by adding glass microfilament fibers or glass microballoons to the solution of polystyrene and polyethylene. Further, the outer conductive layer may be applied by electroless deposition in an aqueous solution rather than by vacuum deposition. A thin coating of parylene is preferably applied to the outer conductor to prevent its oxidation and inhibit mechanical abrasion. 2 figs.

  10. Galloping instability to chaos of cables

    CERN Document Server

    Luo, Albert C J

    2017-01-01

    This book provides students and researchers with a systematic solution for fluid-induced structural vibrations, galloping instability and the chaos of cables. They will also gain a better understanding of stable and unstable periodic motions and chaos in fluid-induced structural vibrations. Further, the results presented here will help engineers effectively design and analyze fluid-induced vibrations.

  11. Bulk Electrical Cable Non-Destructive Examination Methods for Nuclear Power Plant Cable Aging Management Programs

    Energy Technology Data Exchange (ETDEWEB)

    Glass, Samuel W. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Jones, Anthony M. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Fifield, Leonard S. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States); Hartman, Trenton S. [Pacific Northwest National Lab. (PNNL), Richland, WA (United States)

    2016-09-01

    This Pacific Northwest National Laboratory milestone report describes progress to date on the investigation of nondestructive test methods focusing particularly on bulk electrical test methods that provide key indicators of cable aging and damage. The work includes a review of relevant literature as well as hands-on experimental verification of inspection capabilities. As nuclear power plants consider applying for second, or subsequent, license renewal to extend their operating period from 60 years to 80 years, it is important to understand how the materials installed in plant systems and components will age during that time and develop aging management programs to assure continued safe operation under normal and design basis events (DBE). Normal component and system tests typically confirm the cables can perform their normal operational function. The focus of the cable test program, however, is directed toward the more demanding challenge of assuring the cable function under accident or DBE. The industry has adopted 50% elongation at break (EAB) relative to the un-aged cable condition as the acceptability standard. All tests are benchmarked against the cable EAB test. EAB, however, is a destructive test so the test programs must apply an array of other nondestructive examination (NDE) tests to assure or infer the overall set of cable’s system integrity. Assessment of cable integrity is further complicated in many cases by vendor’s use of dissimilar material for jacket and insulation. Frequently the jacket will degrade more rapidly than the underlying insulation. Although this can serve as an early alert to cable damage, direct test of the cable insulation without violating the protective jacket becomes problematic. This report addresses the range of bulk electrical NDE cable tests that are or could be practically implemented in a field-test situation with a particular focus on frequency domain reflectometry (FDR). The FDR test method offers numerous advantages

  12. A unique cabling designed to produce Rutherford-type superconducting cable for the SSC project

    International Nuclear Information System (INIS)

    Grisel, J.; Royet, J.M.; Scanlan, R.M.; Armer, R.

    1988-08-01

    Up to 25,000 Km of keystoned flat cable must be produced for the SSC project. Starting from a specification developed by Lawrence Berkeley Laboratory (LBL), a special cabling machine has been designed by Dour Metal. It has been designed to be able to run at a speed corresponding to a maximum production rate of 10 m/min. This cabling machine is the key part of the production line which consists of a precision Turkshead equipped with a variable power drive, a caterpillar, a dimensional control bench, a data acquisition system, and a take-up unit. The main features of the cabling unit to be described are a design with nearly equal path length between spool and assembling point for all the wires, and the possibility to run the machine with several over- or under-twisting ratios between cable and wires. These requirements led Dour Metal to the choice of an unconventional mechanical concept for a cabling machine. 4 refs., 2 figs

  13. Shape accuracy optimization for cable-rib tension deployable antenna structure with tensioned cables

    Science.gov (United States)

    Liu, Ruiwei; Guo, Hongwei; Liu, Rongqiang; Wang, Hongxiang; Tang, Dewei; Song, Xiaoke

    2017-11-01

    Shape accuracy is of substantial importance in deployable structures as the demand for large-scale deployable structures in various fields, especially in aerospace engineering, increases. The main purpose of this paper is to present a shape accuracy optimization method to find the optimal pretensions for the desired shape of cable-rib tension deployable antenna structure with tensioned cables. First, an analysis model of the deployable structure is established by using finite element method. In this model, geometrical nonlinearity is considered for the cable element and beam element. Flexible deformations of the deployable structure under the action of cable network and tensioned cables are subsequently analyzed separately. Moreover, the influence of pretension of tensioned cables on natural frequencies is studied. Based on the results, a genetic algorithm is used to find a set of reasonable pretension and thus minimize structural deformation under the first natural frequency constraint. Finally, numerical simulations are presented to analyze the deployable structure under two kinds of constraints. Results show that the shape accuracy and natural frequencies of deployable structure can be effectively improved by pretension optimization.

  14. Clinical study of the safety and effectiveness of a novel over-the-counter bleaching tray system

    Science.gov (United States)

    Ghalili, K Michael; Khawaled, Kamal; Rozen, Doran; Afsahi, Veda

    2014-01-01

    We investigated color change, gingival irritation, and tooth sensitivity in patients undergoing at-home vital tooth bleaching with a novel over-the-counter bleaching tray system. Tooth color shade in anterior teeth, supragingival plaque and gingivitis in Ramfjord teeth, as well as visual assessment of teeth gingival tissues and mucosa were evaluated in-office prior to treatment, after two consecutive applications of the 9% hydrogen peroxide bleaching product, after eight applications (10 minutes/day for 3 days at home), and after ten applications (50 minutes exposure over 5 days). Color stability was evaluated at 3 months after completing the treatment regimen. Over-the-counter bleaching products can be used by the patient at home without dentist supervision, but are frequently associated with gingival irritation and tooth sensitivity despite low concentrations of peroxide agents. Our investigations showed that the treatment is tolerable and safe with a low incidence of adverse effects. Any adverse effects associated with use of the whitening gel and tray are temporary, easily controlled, and often disappear within minutes of treatment. Statistical analysis revealed significant improvement in teeth whitening following treatment (mean color change of seven shades) and at three months after treatment. PMID:24591847

  15. Effect of tray-based and trayless tooth whitening systems on microhardness of enamel surface and subsurface.

    Science.gov (United States)

    Teixeira, Erica C N; Ritter, André V; Thompson, Jeffrey Y; Leonard, Ralph H; Swift, Edward J

    2004-12-01

    To evaluate the effect of tray-based and trayless tooth whitening systems on surface and subsurface microhardness of human enamel. Enamel slabs were obtained from recently extracted human third molars. Specimens were randomly assigned to six groups according to tooth whitening treatment (n = 10): 6.0% hydrogen peroxide (HP) (Crest Whitestrips), 6.5% HP (Crest Professional Whitestrips), 7.5% HP (Day White Excel 3), 9.5% HP (Day White Excel 3), 10% carbamide peroxide (Opalescence), and a control group (untreated). Specimens were treated for 14 days following manufacturers' recommended protocols, and were immersed in artificial saliva between treatments. Enamel surface Knoop microhardness (KHN) was measured immediately before treatment, and at days 1, 7, and 14 of treatment. After treatment, subsurface microhardness was measured at depths of 50-500 microm. Data were analyzed for statistical significance using analysis of variance. Differences in microhardness for treated vs. untreated enamel surface were not statistically significant at any time interval. For 6.5% and 9.5% HP, there was a decrease in surface microhardness values during treatment, but at the end of treatment the microhardness values were not statistically different from the baseline values. For the enamel subsurface values, no differences were observed between treated vs. untreated specimens at each depth. Trayless and tray-based tooth whitening treatments do not significantly affect surface or subsurface enamel microhardness.

  16. 2nd International Conference on Cable-Driven Parallel Robots

    CERN Document Server

    Bruckmann, Tobias

    2015-01-01

    This volume presents the outcome of the second forum to cable-driven parallel robots, bringing the cable robot community together. It shows the new ideas of the active researchers developing cable-driven robots. The book presents the state of the art, including both summarizing contributions as well as latest research and future options. The book cover all topics which are essential for cable-driven robots: Classification Kinematics, Workspace and Singularity Analysis Statics and Dynamics Cable Modeling Control and Calibration Design Methodology Hardware Development Experimental Evaluation Prototypes, Application Reports and new Application concepts

  17. A preliminary bending fatigue spectrum for steel monostrand cables

    DEFF Research Database (Denmark)

    Winkler, Jan; Fischer, Gregor; Georgakis, Christos T.

    2011-01-01

    This paper presents the results of the experimental study on the bending fatigue resistance of high-strength steel monostrand cables. From the conducted fatigue tests in the high-stress, low-cycle region, a preliminary bending fatigue spectrum is derived for the estimation of monostrand cable...... service life expectancy. The presented preliminary bending fatigue spectrum of high-strength monostrands is currently unavailable in the published literature. The presented results provide relevant information on the bending mechanism and fatigue characteristics of monostrand steel cables in tension...... and flexure and show that localized cable bending has a pronounced influence on the fatigue resistance of cables under dynamic excitations....

  18. Energy losses of superconducting power transmission cables in the grid

    DEFF Research Database (Denmark)

    Østergaard, Jacob; Okholm, Jan; Lomholt, Karin

    2001-01-01

    One of the obvious motives for development of superconducting power transmission cables is reduction of transmission losses. Loss components in superconducting cables as well as in conventional cables have been examined. These losses are used for calculating the total energy losses of conventional...... as well as superconducting cables when they are placed in the electric power transmission network. It is concluded that high load connections are necessary to obtain energy saving by the use of HTSC cables. For selected high load connections, an energy saving of 40% is expected. It is shown...

  19. Superconducting power cables in Denmark - a case study

    DEFF Research Database (Denmark)

    Østergaard, Jacob

    1997-01-01

    A case study of a 450 MVA, 132 kV high temperature superconducting (HTS) power transmission cable has been carried out. In the study, a superconducting cable system is compared to a conventional cable system which is under construction for an actual transmission line in the Danish grid. The study...... that HTS cables will be less expensive for high power ratings, have lower losses for lines with a high load, and have a reduced reactive power production. The use of superconducting cables in Denmark accommodate plans by the Danish utility to make a substantial conversion of overhead lines to underground...

  20. Comparison of advanced high power underground cable designs

    International Nuclear Information System (INIS)

    Erb, J.; Heinz, W.; Hofmann, A.; Koefler, H.J.; Komarek, P.; Maurer, W.; Nahar, A.

    1975-09-01

    In this paper, advanced high power underground cable designs are compared in the light of available literature, of reports and information supplied by participating industries (AEG, BICC, CGE, Pirelli, Siemens), spontaneous contributions by EdF, France, BBC and Felten and Guilleaume Kabelwerke A.G., Germany, and Hitachi, Furukawa, Fujikura and Sumitomo, Japan, and earlier studies carried out at German public research centres. The study covers cables with forced cooling by oil or water, SF 6 -cables, polyethylene cables, cryoresistive and superconducting cables. (orig.) [de

  1. ASSESSMENT OF CABLE AGING USING CONDITION MONITORING TECHNIQUES

    International Nuclear Information System (INIS)

    GROVE, E.; LOFARO, R.; SOO, P.; VILLARAN, M.; HSU, F.

    2000-01-01

    Electric cables in nuclear power plants suffer degradation during service as a result of the thermal and radiation environments in which they are installed. Instrumentation and control cables are one type of cable that provide an important role in reactor safety. Should the polymeric cable insulation material become embrittled and cracked during service, or during a loss-of-coolant-accident (LOCA) and when steam and high radiation conditions are anticipated, failure could occur and prevent the cables from fulfilling their intended safety function(s). A research program is being conducted at Brookhaven National Laboratory to evaluate condition monitoring (CM) techniques for estimating the amount of cable degradation experienced during in-plant service. The objectives of this program are to assess the ability of the cables to perform under a simulated LOCA without losing their ability to function effectively, and to identify CM techniques which may be used to determine the effective lifetime of cables. The cable insulation materials tested include ethylene propylene rubber (EPR) and cross-linked polyethylene (XLPE). Accelerated aging (thermal and radiation) to the equivalent of 40 years of service was performed, followed by exposure to simulated LOCA conditions. The effectiveness of chemical, electrical, and mechanical condition monitoring techniques are being evaluated. Results indicate that several of these methods can detect changes in material parameters with increasing age. However, each has its limitations, and a combination of methods may provide an effective means for trending cable degradation in order to assess the remaining life of cables

  2. Behaviour at thermal ageing of power cable components through penetrations

    International Nuclear Information System (INIS)

    Puiu, D.; Gyongyosi, T.; Dinu, E.

    2009-01-01

    The materials for electric insulation and exterior jackets of the power cables are formulated organic compounds. The environmental service conditions will induce chemical and/or physical processes at molecular level of the material; these processes are the ageing mechanisms. The power cables passing through penetrations lead to an increase of the rate of thermal ageing mechanisms, resulting in irreversible degradation of mechanical and electric properties of the organic compounds and of the functional properties of the cable. The paper presents the results of the laboratory tests when the real environmental service conditions for penetration are simulated, the comparison with the results of the thermal computation of the power cables heating and the evaluation of the influence of temperature increase of the power cable components on the cable lifetime. For the particular case of a power cable with PVC insulation, we estimated a lifetime decrease about seven years as referred to lifetime of about 30 years for operation in air. (authors)

  3. submitter On Roebel Cable Geometry for Accelerator Magnet

    CERN Document Server

    Fleiter, J; Ballarino, A

    2016-01-01

    Roebel-type cables made of a ReBCO conductor are potential candidates for high-field accelerator magnets. The necessity to promote a large effective transverse section in a Roebel cable to avoid local overstress leading to degradation in electrical performance has been recently addressed. In this paper, a new geometry of meander tapes for a Roebel cable that enhances both the transverse effective section and the current margin at crossing segments is discussed. As Roebel cables are bent at the coil ends, the modulation of the bending radius of strands along the cable pitch leads to a shift of the strands with respect to each other. The shift magnitude is analytically investigated in this paper as a function of both cable features and coil geometry. Finally, the minimum transposition pitch of Roebel cables is determined on the basis of coil characteristics.

  4. Defying c-Abl signaling circuits through small allosteric compounds

    Directory of Open Access Journals (Sweden)

    Stefania eGonfloni

    2014-11-01

    Full Text Available Many extracellular and intracellular signals promote the c-Abl tyrosine kinase activity. c-Abl in turn triggers a multitude of changes either in protein phosphorylation or in gene expression in the cell. Yet, c-Abl takes part in diverse signaling routes because of several domains linked to its catalytic core. Complex conformational changes turn on and off its kinase activity. These changes affect surface features of the c-Abl kinase and likely its capability to bind actin and/or DNA. Two specific inhibitors (ATP-competitive or allosteric compounds regulate the c-Abl kinase through different mechanisms. NMR studies show that a c-Abl fragment (SH3-SH2-linker-SH1 adopts different conformational states upon binding to each inhibitor. This supports an unconventional use for allosteric compounds to unraveling physiological c-Abl signaling circuits.

  5. Optimal Cable Tension Distribution of the High-Speed Redundant Driven Camera Robots Considering Cable Sag and Inertia Effects

    Directory of Open Access Journals (Sweden)

    Yu Su

    2014-03-01

    Full Text Available Camera robots are high-speed redundantly cable-driven parallel manipulators that realize the aerial panoramic photographing. When long-span cables and high maneuverability are involved, the effects of cable sags and inertias on the dynamics must be carefully dealt with. This paper is devoted to the optimal cable tension distribution (OCTD for short of the camera robots. Firstly, each fast varying-length cable is discretized into some nodes for computing the cable inertias. Secondly, the dynamic equation integrated with the cable inertias is set up regarding the large-span cables as catenaries. Thirdly, an iterative optimization algorithm is introduced for the cable tension distribution by using the dynamic equation and sag-to-span ratios as constraint conditions. Finally, numerical examples are presented to demonstrate the effects of cable sags and inertias on determining tensions. The results justify the convergence and effectiveness of the algorithm. In addition, the results show that it is necessary to take the cable sags and inertias into consideration for the large-span manipulators.

  6. Long-term test of the 22.9kV HTS power cable system in LS Cable Ltd

    International Nuclear Information System (INIS)

    Jang, Hyun Man; Lee, Chang Young; Kim, Choon Dong; Kim, Do Hyung; Park, In Son; Ji, Bong Ki; Kim, Dong Wook; Cho, Jeonwook

    2006-01-01

    Since 2001, LS cable Ltd. has been developing the design, manufacturing and evaluation technologies for high temperature superconducting (HTS) power cable system as a member of DAPAS (Dream for Advanced Power system by Applied Superconductivity technology) program in Korea. The 30 m HTS cable system that is rated at 22.9 kV and 1.2 kA giving a rated capacity of 50 MVA had been developed and tested. The cable was designed as a cold dielectric type employing Bi-2223 HTS tapes and polypropylene (PP) laminated paper as the conductor and electrical insulation, respectively. The cable is cooled with sub-cooled liquid nitrogen at temperature from 75 to 77 K. The manufacturing and the installation of the cable system were completed in 2004. Long-term performance test of the cable system has been conducted for six months to verify its electric and mechanical properties in 2005

  7. Dynamical Analysis and Simulation Validation of Incompletely Restrained Cable-Suspended Swinging System Driven by Two Cables

    Directory of Open Access Journals (Sweden)

    Naige Wang

    2016-01-01

    Full Text Available The flexibility of the suspension multicables and driven length difference between two cables cause the translation and rotation of the platform in the incompletely restrained cable-suspended system driven by two cables (IRCSWs2, which are theoretically investigated in this paper. The suspension cables are spatially discretized using the assumed modes method (AMM and the equations of motion are derived from Lagrange equations of the first kind. Considering all the geometric matching conditions are approximately linear with external actuator, the differential algebraic equations (DAEs are transformed to a system of ordinary differential equations (ODEs. Using linear boundary conditions of the suspension cable, the current method can obtain not only the accurate longitudinal displacements of cable and posture of the platform, but also the tension between the platform and cables, and the current method is verified by ADAMS simulation.

  8. Development of polymer packaging for power cable

    Directory of Open Access Journals (Sweden)

    S. Sremac

    2014-10-01

    Full Text Available This paper discusses the issues of product design and the procedure of developing polymer packaging as one of the most important engineering tasks. For the purpose of packing power cables a polymer packaging has been designed in the form of drum. Packaging and many other consumer products are largely produced using polymeric materials due to many positive features. High Density Polyethylene is the type of polyethylene proposed for packaging purposes due to its low degree of branching and strong intermolecular forces. Transport and storage processes were automated based on the radio-frequency identification technology. The proposed system is flexible in terms of its possibility of accepting and processing different types of cables and other products.

  9. Loop Group Parakeet Virtual Cable Concept Demonstrator

    Science.gov (United States)

    Dowsett, T.; McNeill, T. C.; Reynolds, A. B.; Blair, W. D.

    2002-07-01

    The Parakeet Virtual Cable (PVC) concept demonstrator uses the Ethernet Local Area Network (LAN) laid for the Battle Command Support System (BCSS) to connect the Parakeet DVT(DA) (voice terminal) to the Parakeet multiplexer. This currently requires pairs of PVC interface units to be installed for each DVT(DA) . To reduce the cost of a PVC installation, the concept of a Loop Group Parakeet Virtual Cable (LGPVC) was proposed. This device was designed to replace the up to 30 PVC boxes and the multiplexer at the multiplexer side of a PVC installation. While the demonstrator is largely complete, testing has revealed an incomplete understanding of how to emulate the proprietary handshaking occurring between the circuit switch and the multiplexer. The LGPVC concept cannot yet be demonstrated.

  10. Optical fiber cable chemical stripping fixture

    Science.gov (United States)

    Kolasinski, John R. (Inventor); Coleman, Alexander M. (Inventor)

    1995-01-01

    An elongated fixture handle member is connected to a fixture body member with both members having interconnecting longitudinal central axial bores for the passage of an optical cable therethrough. The axial bore of the fixture body member, however, terminates in a shoulder stop for the outer end of a jacket of the optical cable covering both an optical fiber and a coating therefor, with an axial bore of reduced diameter continuing from the shoulder stop forward for a predetermined desired length to the outer end of the fixture body member. A subsequent insertion of the fixture body member including the above optical fiber elements into a chemical stripping solution results in a softening of the exposed external coating thereat which permits easy removal thereof from the optical fiber while leaving a desired length coated fiber intact within the fixture body member.

  11. Cabling in the Skyrme–Faddeev model

    International Nuclear Information System (INIS)

    Jennings, Paul

    2015-01-01

    The Skyrme–Faddeev model is a three-dimensional nonlinear field theory that has topological soliton solutions, called hopfions, which are novel string-like solutions taking the form of knots and links. Solutions found thus far take the form of torus knots and links of these, however torus knots form only a small family of known knots. It is an open question whether any non-torus knot hopfions exist. In this paper we present a construction of knotted fields with the form of cable knots to which an energy minimization scheme can be applied. We find the first known hopfions which do not have the form of torus knots, but instead take the form of cable and hyperbolic knots. (paper)

  12. Cryogenic cooling system for HTS cable

    Energy Technology Data Exchange (ETDEWEB)

    Yoshida, Shigeru [Taiyo Nippon Sanso, Tsukuba (Japan)

    2017-06-15

    Recently, Research and development activity of HTS (High Temperature Superconducting) power application is very progressive worldwide. Especially, HTS cable system and HTSFCL (HTS Fault current limiter) system are proceeding to practical stages. In such system and equipment, cryogenic cooling system, which makes HTS equipment cooled lower than critical temperature, is one of crucial components. In this article, cryogenic cooling system for HTS application, mainly cable, is reviewed. Cryogenic cooling system can be categorized into conduction cooling system and immersion cooling system. In practical HTS power application area, immersion cooling system with sub-cooled liquid nitrogen is preferred. The immersion cooling system is besides grouped into open cycle system and closed cycle system. Turbo-Brayton refrigerator is a key component for closed cycle system. Those two cooling systems are focused in this article. And, each design and component of the cooling system is explained.

  13. Organic dielectrics in high voltage cables

    Energy Technology Data Exchange (ETDEWEB)

    Vermeer, J

    1962-03-01

    It appears that the limit has been reached in the applicability of oil-impregnated paper as the dielectric for ehv cables, as with rising voltages the prevention of conductor losses becomes increasingly difficult, while the dielectric losses of the insulation, increasing as the square of the voltage, contribute to a greater extent to the temperature rise of the conductor. The power transmitting capacity of ehv cables reaches a maximum at 500 to 600 kV for these reasons. Apart from artificial cooling, a substantial improvement can be obtained only with the use of insulating materials with much lower dielectric losses; these can moreover be applied with a smaller wall thickness, but this means higher field strengths. Synthetic polymer materials meet these requirements but can be used successfully only in the form of lapped film tapes impregnated with suitable liquids. The electrical properties of these heterogeneous dielectrics, in particular, their impulse breakdown strengths are studied in detail.

  14. Southwire's High Temperature Superconducting Cable Development - Summary Report

    International Nuclear Information System (INIS)

    Sinha, Uday; Lindsay, David

    2005-01-01

    Final technical report on Southwire HTS cable development program. Southwire started an HTS cable development program beginning early 1995 with a Co-operative Research and Development Agreement (CRADA) with Oak Ridge National Laboratory. The development task was to study the properties of HTS tapes, and construct hand wound 1-m cables to study the winding characteristics of the tapes. Within a short time several 1-m long cables were constructed and tested. A goal was established to construct a 30-m long, three single-phase cables suitable to carry 1250-Aac at 12.4 kV and power Southwire's two main manufacturing plants, machinery division, and part of the corporate headquarters building. Southwire chose to construct a cold dielectric (CD) design cable that has the advantage of shielding magnetic fields and suitable for carrying larger amounts of current for future applications. The CD design however, required a dielectric material that would be suitable at liquid nitrogen temperature. After considerable testing, a polymer based tape called ''Cryoflex'' was developed by Southwire for use as a cold dielectric. Southwire developed a HTS cable making facility for the winding of HTS and dielectric tapes. At the same time Southwire and ORNL developed at Oak Ridge a dielectric testing laboratory and a 5-m cable test bed. The HTS cable requires special terminations that connect cables at 77 K and high pressures (design pressure of 150 psi) with outside power at ambient temperature and pressure. Two types of terminations called Vacuum (T-1) and Pressure termination (T-2) were developed. The vacuum termination needed very high vacuum (10 -5 bar) and cold ceramic bushings that were expensive and unreliable. The modified pressure termination eliminated vacuum, utilize industrial bushings, reduced cost, and increased reliability. Two 5-m cables were designed and constructed at Southwire with the same rating as needed for the 30-m cables. The 5-m cables were tested successfully

  15. Construction control of cable-stayed bridges

    OpenAIRE

    Lozano Galant, José Antonio

    2013-01-01

    Premi extraordinari doctorat curs 2012-2013, àmbit d’Enginyeria Civil This work presents a study of the simulation of cable-stayed bridges built on temporary supports focused on their response during construction and in service. To simulate the behavior during construction, a set of four different algorithms has been developed to deal with initial design (Backward Algorithm), updating the tensioning process when deviations on site are measured (Forward Algorithm), optimization processes (D...

  16. Electromagnetic compatibility design and cabling system rules

    International Nuclear Information System (INIS)

    Raimbourg, J.

    2009-01-01

    This report is devoted to establish EMC (Electromagnetic Compatibility) design and cabling system rules. It is intended for hardware designers in charge of designing electronic maps or integrating existing materials into a comprehensive system. It is a practical guide. The rules described in this document do not require enhanced knowledge of advanced mathematical or physical concepts. The key point is to understand phenomena with a pragmatic approach to highlight the design and protection rules. (author)

  17. Automated wireless monitoring system for cable tension using smart sensors

    Science.gov (United States)

    Sim, Sung-Han; Li, Jian; Jo, Hongki; Park, Jongwoong; Cho, Soojin; Spencer, Billie F.; Yun, Chung-Bang

    2013-04-01

    Cables are critical load carrying members of cable-stayed bridges; monitoring tension forces of the cables provides valuable information for SHM of the cable-stayed bridges. Monitoring systems for the cable tension can be efficiently realized using wireless smart sensors in conjunction with vibration-based cable tension estimation approaches. This study develops an automated cable tension monitoring system using MEMSIC's Imote2 smart sensors. An embedded data processing strategy is implemented on the Imote2-based wireless sensor network to calculate cable tensions using a vibration-based method, significantly reducing the wireless data transmission and associated power consumption. The autonomous operation of the monitoring system is achieved by AutoMonitor, a high-level coordinator application provided by the Illinois SHM Project Services Toolsuite. The monitoring system also features power harvesting enabled by solar panels attached to each sensor node and AutoMonitor for charging control. The proposed wireless system has been deployed on the Jindo Bridge, a cable-stayed bridge located in South Korea. Tension forces are autonomously monitored for 12 cables in the east, land side of the bridge, proving the validity and potential of the presented tension monitoring system for real-world applications.

  18. External heating of electrical cables and auto-ignition investigation.

    Science.gov (United States)

    Courty, L; Garo, J P

    2017-01-05

    Electric cables are now extensively used for both residential and industrial applications. During more than twenty years, multi-scale approaches have been developed to study fire behavior of such cables that represents a serious challenge. Cables are rather complicated materials because they consist of an insulated part and jacket of polymeric materials. These polymeric materials can have various chemical structures, thicknesses and additives and generally have a char-forming tendency when exposed to heat source. In this work, two test methods are used for the characterization of cable pyrolysis and flammability. The first one permits the investigation of cable pyrolysis. A description of the cable mass loss is obtained, coupling an Arrhenius expression with a 1D thermal model of cables heating. Numerical results are successfully compared with experimental data obtained for two types of cable commonly used in French nuclear power plants. The second one is devoted to ignition investigations (spontaneous or piloted) of these cables. All these basic observations, measurements and modelling efforts are of major interest for a more comprehensive fire resistance evaluation of electric cables. Copyright © 2016 Elsevier B.V. All rights reserved.

  19. Cabling for an SSC silicon tracking system

    International Nuclear Information System (INIS)

    Ziock, H.; Boissevain, J.; Cooke, B.; Miller, W.

    1990-01-01

    As part of the Superconducting Super Collider Laboratory (SSCL) funded silicon tracking subsystem R ampersand D program, we examine the problems associated with cabling such a system. Different options for the cabling plant are discussed. A silicon microstrip tracking detector for an SSC experiment is an extremely complex system. The system consists of approximately 10 7 detector channels, each of which requires a communication link with the outside world and connections to the detector bias voltage supply, to a DC power supply for the onboard electronics, and to an adjustable discrimination level. The large number of channels and the short time between beam interactions (16 nanoseconds) dictates the need for high speed and large bandwidth communication channels, and a power distribution system that can handle the high current draw of the electronics including the large AC component due to their switching. At the same time the constraints imposed by the physics measurements require that the cable plant have absolutely minimal mass and radiation length. 4 refs., 2 figs

  20. Commercialization of Medium Voltage HTS Triax TM Cable Systems

    Energy Technology Data Exchange (ETDEWEB)

    Knoll, David

    2012-12-31

    The original project scope that was established in 2007 aimed to install a 1,700 meter (1.1 mile) medium voltage HTS Triax{TM} cable system into the utility grid in New Orleans, LA. In 2010, however, the utility partner withdrew from the project, so the 1,700 meter cable installation was cancelled and the scope of work was reduced. The work then concentrated on the specific barriers to commercialization of HTS cable technology. The modified scope included long-length HTS cable design and testing, high voltage factory test development, optimized cooling system development, and HTS cable life-cycle analysis. In 2012, Southwire again analyzed the market for HTS cables and deemed the near term market acceptance to be low. The scope of work was further reduced to the completion of tasks already started and to testing of the existing HTS cable system in Columbus, OH. The work completed under the project included: • Long-length cable modeling and analysis • HTS wire evaluation and testing • Cable testing for AC losses • Optimized cooling system design • Life cycle testing of the HTS cable in Columbus, OH • Project management. The 200 meter long HTS Triax{TM} cable in Columbus, OH was incorporated into the project under the initial scope changes as a test bed for life cycle testing as well as the site for an optimized HTS cable cooling system. The Columbus cable utilizes the HTS TriaxTM design, so it provided an economical tool for these of the project tasks.

  1. A sectional-splinting technique for impressing multiple implant units by eliminating the use of an open tray

    Directory of Open Access Journals (Sweden)

    Suryakant C. Deogade

    2014-01-01

    Full Text Available Since the inception of root form implant dentistry by P-I Branemark in the early 1980′s, so many technical advances have been put forward by several authors. However, the open tray impression technique is still performed for impressing multiple implant fixtures as it was first described in the original Branemark procedure manual. The most critical aspect for a successful implant-supported restoration is the passive and an accurate fit of superstructures to avoid preload and loading stresses. Splinting impression technique in multiple implants has gained popularity. Auto-polymerizing acrylic resin is among the most routinely practiced splinting material for multiple implant units. However, unfortunately, it exhibits shrinkage, which makes an impression quite inaccurate. This case report presents the solution to minimize the shrinkage of resin by utilizing sectional-splinting technique as advocated in the previous implant literature.

  2. Modeling Cable and Guide Channel Interaction in a High-Strength Cable-Driven Continuum Manipulator.

    Science.gov (United States)

    Moses, Matthew S; Murphy, Ryan J; Kutzer, Michael D M; Armand, Mehran

    2015-12-01

    This paper presents several mechanical models of a high-strength cable-driven dexterous manipulator designed for surgical procedures. A stiffness model is presented that distinguishes between contributions from the cables and the backbone. A physics-based model incorporating cable friction is developed and its predictions are compared with experimental data. The data show that under high tension and high curvature, the shape of the manipulator deviates significantly from a circular arc. However, simple parametric models can fit the shape with good accuracy. The motivating application for this study is to develop a model so that shape can be predicted using easily measured quantities such as tension, so that real-time navigation may be performed, especially in minimally-invasive surgical procedures, while reducing the need for hazardous imaging methods such as fluoroscopy.

  3. Rapid optimization of tension distribution for cable-driven parallel manipulators with redundant cables

    Science.gov (United States)

    Ouyang, Bo; Shang, Weiwei

    2016-03-01

    The solution of tension distributions is infinite for cable-driven parallel manipulators(CDPMs) with redundant cables. A rapid optimization method for determining the optimal tension distribution is presented. The new optimization method is primarily based on the geometry properties of a polyhedron and convex analysis. The computational efficiency of the optimization method is improved by the designed projection algorithm, and a fast algorithm is proposed to determine which two of the lines are intersected at the optimal point. Moreover, a method for avoiding the operating point on the lower tension limit is developed. Simulation experiments are implemented on a six degree-of-freedom(6-DOF) CDPM with eight cables, and the results indicate that the new method is one order of magnitude faster than the standard simplex method. The optimal distribution of tension distribution is thus rapidly established on real-time by the proposed method.

  4. Evaluation of the Thickness and Oxygen Transmission Rate before and after Thermoforming Mono- and Multi-layer Sheets into Trays with Variable Depth

    Directory of Open Access Journals (Sweden)

    Mieke Buntinx

    2014-12-01

    Full Text Available During thermoforming, plastic sheets are heated and subsequently deformed through the application of mechanical stretching and/or pressure. This process directly impacts sheet properties such as material thickness in walls, corners, and bottom, crystallinity in the constituent layers, and particularly the oxygen gas permeability. The aim of this study was to quantify the impact of thermoforming on thickness and oxygen transmission rate (OTR of selected packaging materials (polypropylene (PP; PP/ethylene-vinyl alcohol co-polymer/PP (PP/EVOH/PP; polystyrene/EVOH/polyethylene (PS/EVOH/PE; amorphous polyethylene terephtalate/PE (APET/PE; APET/PE/EVOH/PE; polyamide/PE (PA/PE; and (PE/PA/EVOH/PA/PE. These materials were extruded in two different thicknesses and thermoformed into trays with the same top dimensions and variable depths of 25, 50, and/or 75 mm and a 50 mm tray with a variable radius of the corners. The distribution of the material thickness in the trays was visualized, showing the locations that were most affected by the deep drawn process. The OTR results indicate that the calculated OTR, based on a homogeneous material distribution, can be used as a rough approximation of the measured OTR. However, detailed analysis of crystallization and unequal thinning, which is also related to the tray design, remains necessary to explain the deviation of the measured OTR as compared to the predicted one.

  5. Sanitation Can Be A Foundation Disease Management Tool: Potential Of Spreading Binucleate Rhizoctonia from Nursery Propagation Floors To Trays Containing Azalea Stem Cuttings

    Science.gov (United States)

    Binucelate Rhizoctonia spp. (BNR), the cause of web blight, are present all year on container-grown azaleas in the southern U.S. BNR can be eliminated during vegetative propagation by submerging stem cuttings in 50°C water for 21 minutes. The objective was to evaluate risk of rooting trays being con...

  6. Accuracy of implant transfer and surface detail reproduction with polyether and polyvinyl siloxane using closed-tray impression technique

    Directory of Open Access Journals (Sweden)

    Marzieh Alikhasi

    2013-10-01

    Full Text Available   Background and Aims: Making accurate impressions of prepared teeth when they are adjacent to dental implants is of great importance. In these situations, disregarding the selection of appropriate impression material and technique, not only can affect accuracy of transferring of the 3-dimentional spatial status of implant, but also can jeopardize the accurate recording of tooth. In the present study, the accuracy of two impression materials with taper impression copings for recording implant position and surface details was evaluated.   Materials and Methods: One metal reference model with 2 implants (Implantium and a preparation of three grooves on a tooth according to ADA no. 19 standard was fabricated. 10 medium- consistency polyEther (PE impressions using custom trays and 10 polyVinyl Siloxane (PVS putty wash impressions using prefabricated trays with conical impression coping were made. Impressions were poured with ADA type IV stone. A Coordinate Measuring Machine (CMM evaluated x, y and angular displacement of the implant analog heads and also accuracy of groove reproduction were measured using a Video Measuring Machine (VMM. These measurements were compared to the ones from reference model. Data were analyzed using one-way ANOVA and T-test.   Results: Putty wash PVS had less linear discrepancy compared with reference model (P > 0.001. There was no significant difference in the surface detail reproduction (P = 0.15.   Conclusion: Putty wash PVS had better results for linear displacement compared with medium consistency PE. There was no significant difference in surface detail reproduction between the two impression materials.

  7. Design, processing, and properties of Bi 2212\\/Ag Rutherford cables

    CERN Document Server

    Collings, E W; Scanlan, R M; Dietderich, D R; Motowidlo, L R; Sokolowski, R S; Aoki, Y; Hasegawa, T

    1999-01-01

    In a program intended to explore the use of high temperature superconducting (HTSC) cables in high field synchrotron dipole magnets model Bi:2212/Ag Rutherford cables were designed bearing in mind the needs for mechanical integrity, relatively high tensile strength, and low coupling losses. To satisfy these needs a core-type cable design was selected and a readily available heat-resistant core material acquired. Cables were wound for critical current- and AC loss measurement. Both winding-induced (mechanical) and core-induced (chemical) critical current degradation was examined. Interstrand coupling loss was measured calorimetrically on model cable samples with bare- and oxide-coated cores. From the results it was predicted that the losses of full-scale Bi:2212/Ag-wound LHC-type Rutherford cables would fall close to the acceptability range for the windings of high-field accelerator dipoles. (10 refs).

  8. Loss and Inductance Investigation in Superconducting Cable Conductors

    DEFF Research Database (Denmark)

    Olsen, Søren Krüger; Tønnesen, Ole; Træholt, Chresten

    1999-01-01

    An important parameter in the design and optimization of a superconducting cable conductor is the control of the current distribution among single tapes and layers. This distribution is to a large degree determined by inductances, since the resistances are low. The self and mutual inductances...... of transport current and current distribution.This presentation is based on a number of experiments performed on prototype superconducting cable conductors. The critical current (1uV/cm) of the conductor at 77K was 1590 A (cable #1) and 3240 A (cable #2) respectively.At an rms current of 2 kA (50 Hz) the AC......-loss was measured on cable #2 to 0.6W/mxphase. This is, to our knowledge, the lowest AC-loss (at 2kA and 77K) of a high temperature superconducting cable conductor reported so far....

  9. Dynamic characteristics of stay cables with inerter dampers

    Science.gov (United States)

    Shi, Xiang; Zhu, Songye

    2018-06-01

    This study systematically investigates the dynamic characteristics of a stay cable with an inerter damper installed close to one end of a cable. The interest in applying inerter dampers to stay cables is partially inspired by the superior damping performance of negative stiffness dampers in the same application. A comprehensive parametric study on two major parameters, namely, inertance and damping coefficients, are conducted using analytical and numerical approaches. An inerter damper can be optimized for one vibration mode of a stay cable by generating identical wave numbers in two adjacent modes. An optimal design approach is proposed for inerter dampers installed on stay cables. The corresponding optimal inertance and damping coefficients are summarized for different damper locations and interested modes. Inerter dampers can offer better damping performance than conventional viscous dampers for the target mode of a stay cable that requires optimization. However, additional damping ratios in other vibration modes through inerter damper are relatively limited.

  10. Guy cable design and damping for vertical axis wind turbines

    Science.gov (United States)

    Carne, T. G.

    1981-01-01

    Guy cables are frequently used to support vertical axis wind turbines since guying the turbine reduces some of the structural requirements on the tower. The guys must be designed to provide both the required strength and the required stiffness at the top of the turbine. The axial load which the guys apply to the tower, bearings, and foundations is an undesirable consequence of using guys to support the turbine. Limiting the axial load so that it does not significantly affect the cost of the turbine is an important objective of the cable design. The lateral vibrations of the cables is another feature of the cable design which needs to be considered. These aspects of the cable design are discussed, and a technique for damping cable vibrations was mathematically analyzed and demonstrated with experimental data.

  11. Frequency analysis of a tower-cable coupled system

    Energy Technology Data Exchange (ETDEWEB)

    Park, Moo Yeol [Young Sin Precision Engineering Ltd., Gyungju (Korea, Republic of); Kim, Seock Hyun; Park, In Su [Kangwon National University, Chuncheon (Korea, Republic of); Cui, Chengxun [Yanbian University, Yangji (China)

    2013-06-15

    This study considers the prediction of natural frequency to avoid resonance in a wind turbine tower- cable coupled system. An analytical model based on the Rayleigh-Ritz method is proposed to predict the resonance frequency of a wind turbine tower structure supported by four guy cables. To verify the validity of the analytical model, a small tower-cable model is manufactured and tested. The frequency and mode data of the tower model are obtained by modal testing and finite element analysis. The validity of the proposed method is verified through the comparison of the frequency analysis results. Finally, using a parametric study with the analytical model, we identified how the cable tension and cable angle affect the resonance frequency of the wind turbine tower structure. From the analysis results, the tension limit and optimal angle of the cable are identified.

  12. State of the art in power cable design, failure mechanisms and testing

    International Nuclear Information System (INIS)

    Orton, H.

    2005-01-01

    This presentation describes state of the art in power cable design, failure mechanisms and testing. It gives a history of cable usage and design of cables, describes different cable types, assessment of the condition of cables, aging and failures, testing and diagnostics

  13. 47 CFR 1.1155 - Schedule of regulatory fees and filing locations for cable television services.

    Science.gov (United States)

    2010-10-01

    ... locations for cable television services. 1.1155 Section 1.1155 Telecommunication FEDERAL COMMUNICATIONS... Schedule of regulatory fees and filing locations for cable television services. Fee amount Address 1. Cable Television Relay Service $315 FCC, Cable, P.O. Box 979084, St. Louis, MO 63197-9000 2. Cable TV System (per...

  14. An Acoustic Source Reactive to Tow Cable Strum

    Science.gov (United States)

    2012-09-21

    sound wave radiates from the head mass. Dkt . No. 101720 Application No. ?? REPLACEMENT SHEET? /3 DRAFT 1 CABLE CURVATURE INDUCING LONGITUDINAL...MOTION IDEALIZED TOW CABLE (NO TRANSVERSE VIBRATION) REALISTIC TOW CABLE (INCLUDES TRANSVERSE VIBRATION) DIRECTION OF TOW FIG. 1 (PRIOR ART) Dkt . No...DISPLACEMENT DISPLACEMENT LONGITUDINAL (PRIOR ART) DISPLACEMENT LONGITUDINAL Dkt . No. 101720 Application No. ?? REPLACEMENT SHEET? /3 DRAFT 10 A B B A

  15. Similarity Analysis of Cable Insulations by Chemical Test

    Energy Technology Data Exchange (ETDEWEB)

    Kim, Jong Seog [Central Research Institute of Korea Hydro and Nuclear Power Co., Daejeon (Korea, Republic of)

    2013-10-15

    As result of this experiment, it was found that FT-IR test for material composition, TGA test for aging trend are applicable for similarity analysis of cable materials. OIT is recommended as option if TGA doesn't show good trend. Qualification of new insulation by EQ report of old insulation should be based on higher activation energy of new insulation than that of old one in the consideration of conservatism. In old nuclear power plant, it is easy to find black cable which has no marking of cable information such as manufacturer, material name and voltage. If a type test is required for qualification of these cables, how could I select representative cable? How could I determine the similarity of these cables? If manufacturer has qualified a cable for nuclear power plant more than a decade ago and composition of cable material is changed with similar one, is it acceptable to use the old EQ report for recently manufactured cable? It is well known to use FT-IR method to determine the similarity of cable materials. Infrared ray is easy tool to compare compositions of each material. But, it is not proper to compare aging trend of these materials. Study for similarity analysis of cable insulation by chemical test is described herein. To study a similarity evaluation method for polymer materials, FT-IR, TGA and OIT tests were performed for two cable insulation(old and new) which were supplied from same manufacturer. FT-IR shows good result to compare material compositions while TGA and OIT show good result to compare aging character of materials.

  16. Method discussion of the performance evaluation on nuclear plant cable

    International Nuclear Information System (INIS)

    Lu Yongfang; Zhong Weixia; Sun Jiansheng; Liu Jingping

    2014-01-01

    A stock cable, which is same as the nuclear plant cable in service, was treated by thermal aging. After that, the mechanical property, the flame retardant property, the anti-oxidation were measured, and relationships between them due to the thermal aging were established. By those analysis, evaluating the in-service cable performance in nuclear plant and calculating its remaining life. Furthermore, the feasibility of this method was disscussed. (authors)

  17. Total Magnetic Field Signatures over Submarine HVDC Power Cables

    Science.gov (United States)

    Johnson, R. M.; Tchernychev, M.; Johnston, J. M.; Tryggestad, J.

    2013-12-01

    Mikhail Tchernychev, Geometrics, Inc. Ross Johnson, Geometrics, Inc. Jeff Johnston, Geometrics, Inc. High Voltage Direct Current (HVDC) technology is widely used to transmit electrical power over considerable distances using submarine cables. The most commonly known examples are the HVDC cable between Italy and Greece (160 km), Victoria-Tasmania (300 km), New Jersey - Long Island (82 km) and the Transbay cable (Pittsburg, California - San-Francisco). These cables are inspected periodically and their location and burial depth verified. This inspection applies to live and idle cables; in particular a survey company could be required to locate pieces of a dead cable for subsequent removal from the sea floor. Most HVDC cables produce a constant magnetic field; therefore one of the possible survey tools would be Marine Total Field Magnetometer. We present mathematical expressions of the expected magnetic fields and compare them with fields observed during actual surveys. We also compare these anomalies fields with magnetic fields produced by other long objects, such as submarine pipelines The data processing techniques are discussed. There include the use of Analytic Signal and direct modeling of Total Magnetic Field. The Analytic Signal analysis can be adapted using ground truth where available, but the total field allows better discrimination of the cable parameters, in particular to distinguish between live and idle cable. Use of a Transverse Gradiometer (TVG) allows for easy discrimination between cable and pipe line objects. Considerable magnetic gradient is present in the case of a pipeline whereas there is less gradient for the DC power cable. Thus the TVG is used to validate assumptions made during the data interpretation process. Data obtained during the TVG surveys suggest that the magnetic field of a live HVDC cable is described by an expression for two infinite long wires carrying current in opposite directions.

  18. Problems with conductors and dielectrics for cryogenic cables

    Energy Technology Data Exchange (ETDEWEB)

    Bogner, G; Penczynski, P [Siemens A.G., Erlangen (F.R. Germany). Abt. Reaktortechnik

    1976-06-01

    The most important problems which need to be solved if superconducting power cables are to be used on a large scale are connected with the superconducting cable materials and the dielectrics used for insulation. Research work on superconducting materials for ac and dc cables is briefly reviewed together with stabilization problems for these materials. Three types of insulation are considered - vacuum, subcooled or supercritical helium, and foil wound insulation. The merits and problems encountered in each case are discussed.

  19. Similarity Analysis of Cable Insulations by Chemical Test

    International Nuclear Information System (INIS)

    Kim, Jong Seog

    2013-01-01

    As result of this experiment, it was found that FT-IR test for material composition, TGA test for aging trend are applicable for similarity analysis of cable materials. OIT is recommended as option if TGA doesn't show good trend. Qualification of new insulation by EQ report of old insulation should be based on higher activation energy of new insulation than that of old one in the consideration of conservatism. In old nuclear power plant, it is easy to find black cable which has no marking of cable information such as manufacturer, material name and voltage. If a type test is required for qualification of these cables, how could I select representative cable? How could I determine the similarity of these cables? If manufacturer has qualified a cable for nuclear power plant more than a decade ago and composition of cable material is changed with similar one, is it acceptable to use the old EQ report for recently manufactured cable? It is well known to use FT-IR method to determine the similarity of cable materials. Infrared ray is easy tool to compare compositions of each material. But, it is not proper to compare aging trend of these materials. Study for similarity analysis of cable insulation by chemical test is described herein. To study a similarity evaluation method for polymer materials, FT-IR, TGA and OIT tests were performed for two cable insulation(old and new) which were supplied from same manufacturer. FT-IR shows good result to compare material compositions while TGA and OIT show good result to compare aging character of materials

  20. Development of halogen-free cables for nuclear power plants

    International Nuclear Information System (INIS)

    Yamamoto, Mitsuo; Ito, Kazumi; Yaji, Takeo; Yoshida, Shin; Sakurai, Takako; Matsushita, Shigetoshi.

    1990-01-01

    On the occasion where serious fire accidents were experienced in the past, the need for making flame-retardant wire and cable incombustible took place and has since been generalizing. Various sorts of flame-retardant cables have already been developed and been actually used. From the viewpoint of avoiding the interference with the evacuation and fire-fighting activity in case of fire or the secondary accidents such as corrosion of the distributing panel, etc., the demand for non-halogen flame-retardant cable has rapidly been increasing in recent years in some fields of general industries, because this specific cable would generate the least amount of toxic smoke or corrosive gas even when it should burn. Similar demand has been increasing also for the cable used for nuclear power plants. In this field, earnest desire has been made for the development of non-halogen flame-retardant cable having specific environmental resistance specially required at nuclear power plants in addition to the properties and capacities required in general industries. The authors have continued examinations on the anti-environmental properties of the materials for cable such as long heat resistance, radiation resistance, steam resistance and succeeded in completing various sorts of non-halogen flame-retardant cable for nuclear power plants. In this report, we will introduce various features of the cable we have developed this time as well as the long-term reliability of non-halogen flame-retardant materials. (author)

  1. Debris from cobalt-chrome cable may cause acetabular loosening.

    Science.gov (United States)

    Kelley, S S; Johnston, R C

    1992-12-01

    To address the issue of nonunion with trochanteric osteotomy, surgeons have experimented with various modes of fixation, wire and cable being the two most popular. From a group of 643 primary cemented total hip arthroplasties performed by a single surgeon via the trans-trochanteric approach, minimum four-year roentgenographic follow-up evaluations were performed on 322 hips (50%). The method of fixation was stainless steel monofilament wire in 162 cases and Co-Cr cable in 160. Trochanteric union rates were 75% (122 patients) for the wire group and 79% (126 patients) for the cable. Breakage rates of the entire trochanteric fixation construction (all three wires or cables) were 43% (68 patients) for the wire and 12% (20 patients) for the cable. Unraveled cable was seen in 56% of the hips (90 patients), and in 47% of these hips, there were no broken cables. Blinded roentgenographic analysis of the acetabulum, preformed independently, revealed that loosening of the acetabulum in the cable group was greater than in the wire group. Cables offer no significant benefit over wires and may have potential adverse effects. Generation of significant particulate debris was noted roentgenographically, and marked reaction/destruction was found at the time of revision surgery.

  2. Stationary operational behavior unsymmetrical superconducting three-phase cable

    Energy Technology Data Exchange (ETDEWEB)

    Iser, R.

    1974-01-01

    A superconducting cable with a coaxial conductor arrangement is electrically unsymmetrical. Voltage and current relationships are analyzed for such a cable where, as a result of reactance and capacitance matrices being unsymmetric, large voltage unsymmetry appears. This limits the practical length of this type of cable. It is shown that a significant gain in symmetry is attained by the use of two cables connected in parallel. The compensating current which then occurs involves no disadvantage. The circuit described permits overloads of up to 100 percent.

  3. Strand critical current degradation in $Nb_{3}$ Sn Rutherford cables

    CERN Document Server

    Barzi, E; Higley, H C; Scanlan, R M; Yamada, R; Zlobin, A V

    2001-01-01

    Fermilab is developing 11 Tesla superconducting accelerator magnets based on Nb/sub 3/Sn superconductor. Multifilamentary Nb/sub 3/Sn strands produced using the modified jelly roll, internal tin, and powder-in-tube technologies were used for the development and test of the prototype cable. To optimize the cable geometry with respect to the critical current, short samples of Rutherford cable with packing factors in the 85 to 95% range were fabricated and studied. In this paper, the results of measurements of critical current, n-value and RRR made on the round virgin strands and on the strands extracted from the cable samples are presented. (5 refs).

  4. Development mineral insulated cables for nuclear instrumentation of reactors

    International Nuclear Information System (INIS)

    Calvo, W.A.P.; Hess Junior, A.; Brito Maciel, R. de

    1990-01-01

    In-core and out-of-core neutron detectors for reactor and safety control systems are usually connected by means of mineral insulated cables. The electrical signal, either a pulse or a current, is transmitted along the cable at high temperature, pressure and radiation and should not be influenced by electromagnetic interfereces from the environment. In this paper it is presented the result of the analysis of the mechanical and electrical properties of several types of mineral insulated cables and also the design, manufacture, sealing, cable ends and their applications to nuclear detectors of various types. (author) [pt

  5. Interstrand contact resistances of Bi-2212 Rutherford cables for SMES

    International Nuclear Information System (INIS)

    Kawagoe, A.; Kawabata, Y.; Sumiyoshi, F.; Nagaya, S.; Hirano, N.

    2006-01-01

    Interstrand contact resistances of Bi-2212 Rutherford cables for SMES coils were evaluated from a comparison between measured data and 2D-FEM analyses on interstrand coupling losses in these cables. The cables were composed of 30 non-twisted Bi-2212 strands with a diameter of 0.81 mm and a cable twist pitch of 90 mm. Three samples were measured; one of them had NiCr cores and the others had no cores. One of the latter two samples repeatedly experienced bending. The interstrand coupling losses were measured in liquid helium for the straight samples under transverse ac ripple magnetic fields superposed on dc bias magnetic fields. The transverse magnetic field was applied to the samples in directions both perpendicular and parallel to the flat face of the cable. The effect of the bending on the interstrand coupling losses could be neglected for the non-cored samples. The interstrand coupling losses of NiCr cored sample decreased by about 30% compared with the non-cored samples, in case the direction of the transverse magnetic fields applied to the cable is perpendicular to the flat face of the cable. Using these results and 2D-FEM analyses, taking into account that interstrand contact conditions vary from the center to the edge in the cross-section of cables, gave us the conclusion that the between side-by-side strands contact with metallurgical bond only in both edges of the cables

  6. Interstrand contact resistances of Bi-2212 Rutherford cables for SMES

    Science.gov (United States)

    Kawagoe, A.; Kawabata, Y.; Sumiyoshi, F.; Nagaya, S.; Hirano, N.

    2006-10-01

    Interstrand contact resistances of Bi-2212 Rutherford cables for SMES coils were evaluated from a comparison between measured data and 2D-FEM analyses on interstrand coupling losses in these cables. The cables were composed of 30 non-twisted Bi-2212 strands with a diameter of 0.81 mm and a cable twist pitch of 90 mm. Three samples were measured; one of them had NiCr cores and the others had no cores. One of the latter two samples repeatedly experienced bending. The interstrand coupling losses were measured in liquid helium for the straight samples under transverse ac ripple magnetic fields superposed on dc bias magnetic fields. The transverse magnetic field was applied to the samples in directions both perpendicular and parallel to the flat face of the cable. The effect of the bending on the interstrand coupling losses could be neglected for the non-cored samples. The interstrand coupling losses of NiCr cored sample decreased by about 30% compared with the non-cored samples, in case the direction of the transverse magnetic fields applied to the cable is perpendicular to the flat face of the cable. Using these results and 2D-FEM analyses, taking into account that interstrand contact conditions vary from the center to the edge in the cross-section of cables, gave us the conclusion that the between side-by-side strands contact with metallurgical bond only in both edges of the cables.

  7. Estimation of Medium Voltage Cable Parameters for PD Detection

    DEFF Research Database (Denmark)

    Villefrance, Rasmus; Holbøll, Joachim T.; Henriksen, Mogens

    1998-01-01

    Medium voltage cable characteristics have been determined with respect to the parameters having influence on the evaluation of results from PD-measurements on paper/oil and XLPE-cables. In particular, parameters essential for discharge quantification and location were measured. In order to relate...... and phase constants. A method to estimate this propagation constant, based on high frequency measurements, will be presented and will be applied to different cable types under different conditions. The influence of temperature and test voltage was investigated. The relevance of the results for cable...

  8. Development of scaling rules for Rutherford type superconducting cables

    International Nuclear Information System (INIS)

    Royet, J.M.; Scanlan, R.M.

    1991-01-01

    During the R and D phase of the Superconducting Supercollider (SSC) program, LBL was responsible for establishing the parameters for cables used in SSC dipole and quadrupole magnets. In addition, LBL has collaborated with Fermi National Accelerator Laboratory on the design and fabrication of a new cable for use in the Low Beta Quadrupoles. As a result of the development work on these and other cables, we have arrived a set of scaling rules which provide guidelines for choosing the parameters for a wide range of superconducting cables. These parameters include strand size, strand number, keystone angle, percent compaction, cable pitch and compacted cable dimensions. In addition, we have defined the tolerance ranges for the key cable manufacturing parameters such as mandrel size and shape, strand tension, and Turkshead temperature control. In this paper, the authors present the results on cables ranging from 8 strands to 36 strands of 0.65mm wire and from 8 strands to 30 strands of 0.8mm wire. The authors use these results to demonstrate the application of the scaling rules for Rutherford-type cable

  9. Development of scaling rules for Rutherford type superconducting cables

    International Nuclear Information System (INIS)

    Royet, J.M.; Scanlan, R.M.

    1990-09-01

    During the R ampersand D phase of the Superconducting Supercollider (SSC) program, LBL was responsible for establishing the parameters for cables used in SSC dipole and quadrupole magnets. In addition, the design and fabrication of a new cable for use in the Low Beta Quadrupoles. As a result of the development work on these and other cables, we have arrived a set of scaling rules which provide guidelines for choosing the parameters for a wide range of superconducting cables. These parameters include strand size, strand number, keystone angle, percent compaction, cable pitch and compacted cable dimensions. In addition, we have defined the tolerance ranges for the key cable manufacturing parameters such as mandrel size and shape, stand tension, and Turkshead temperature control. In this paper, we present the results on cables ranging from 8 strands to 36 strands of 0.65mm wire and from 8 strands to 30 strands of 0.8mm wire. We use these results to demonstrate the application of the scaling rules for Rutherford-type cable

  10. Recent development of the Cu/Nb-Ti superconducting cables for SSC in Hitachi Cable, Ltd

    International Nuclear Information System (INIS)

    Sakai, S.; Iwaki, G.; Sawada, Y.; Moriai, H.; Ishigami, Y.

    1989-01-01

    In these few years, Cu/Nb-Ti superconducting cables for the dipole magnets of SSC projects have been developed in the industrial scale in Hitachi Cable, Ltd. The features of these developed conductors are as follows. (1) The diameter of Nb-Ti filaments is very small, 4-6 μm. (2) The critical current density (J c ) is very high, 2,850-3,050 A/mm 2 at 5 T on wires, 2750-2950 A/mm 2 at 5 T on cables in industrial scale. The champion J c of wires is 3,460 A/mm 2 at 5 T in the laboratory scale. (3) The RRR Residual Resistivity Ratio values of developed cables is very high, approximately 200, due to the newly developed high purity Oxygen Free Copper (OFC). (4) The conductors have been wound to the 1 m length dipole magnet in Hitachi Ltd., and it has generated 6.7 T in the central magnetic field at 6,595 A. The Cu/Cu-Mn/Nb-Ti composite wires which avoid the possibility of electrical coupling of the filaments have been produced in laboratory scale. The RRR of the copper stabilizer and J c properties have not degraded because of no metallurgical reactions between Cu and Mn, Nb-Ti and Mn. 7 refs., 9 figs., 4 tabs

  11. Method of exchanging cables of neutron monitoring instrumentation tube and folding device of the cable

    International Nuclear Information System (INIS)

    Sakamaki, Kazuo.

    1990-01-01

    In a BWR type reactor, a wide range monitor (WRNM) is used instead of a conventional neutron source range monitor (SRM) or an intermediate range monitor (IRM). The WRNM is always fixed to a predetermined position in a reactor core while containing a detection section in a dry tube, different from a conventional monitor. Accordingly, driving devices for the conventional detection section such as in SRM and IRM are not necessary but, when the reactor is operated for a long period of time, it is sometimes necessary to be replaced with new WRNM. According to the present invention, the cable of the detector placed in a neutron instrumentation tube is connected to a cable take-up drum in a take-up device passing through a cask. Then, the cable is taken-up by driving the take-up drum by a driving motor and the WRNM detection section attached to the top end of the cable is contained in the cask. With this constitution, replacing and processing operation for the detection section can be facilitated and operator's exposure dose can be reduced. (I.S.)

  12. Power laws from linear neuronal cable theory

    DEFF Research Database (Denmark)

    Pettersen, Klas H; Lindén, Henrik Anders; Tetzlaff, Tom

    2014-01-01

    suggested to be at the root of this phenomenon, we here demonstrate a possible origin of such power laws in the biophysical properties of single neurons described by the standard cable equation. Taking advantage of the analytical tractability of the so called ball and stick neuron model, we derive general...... are homogeneously distributed across the neural membranes and themselves exhibit pink ([Formula: see text]) noise distributions. While the PSD noise spectra at low frequencies may be dominated by synaptic noise, our findings suggest that the high-frequency power laws may originate in noise from intrinsic ion...

  13. Modelling and simulation of railway cable systems

    Energy Technology Data Exchange (ETDEWEB)

    Teichelmann, G.; Schaub, M.; Simeon, B. [Technische Univ. Muenchen, Garching (Germany). Zentrum Mathematik M2

    2005-12-15

    Mathematical models and numerical methods for the computation of both static equilibria and dynamic oscillations of railroad catenaries are derived and analyzed. These cable systems form a complex network of string and beam elements and lead to coupled partial differential equations in space and time where constraints and corresponding Lagrange multipliers express the interaction between carrier, contact wire, and pantograph head. For computing static equilibria, three different algorithms are presented and compared, while the dynamic case is treated by a finite element method in space, combined with stabilized time integration of the resulting differential algebraic system. Simulation examples based on reference data from industry illustrate the potential of such computational tools. (orig.)

  14. Two-way cable television project

    Science.gov (United States)

    Wilkens, H.; Guenther, P.; Kiel, F.; Kraus, F.; Mahnkopf, P.; Schnee, R.

    1982-02-01

    The market demand for a multiuser computer system with interactive services was studied. Mean system work load at peak use hours was estimated and the complexity of dialog with a central computer was determined. Man machine communication by broadband cable television transmission, using digital techniques, was assumed. The end to end system is described. It is user friendly, able to handle 10,000 subscribers, and provides color television display. The central computer system architecture with remote audiovisual terminals is depicted and software is explained. Signal transmission requirements are dealt with. International availability of the test system, including sample programs, is indicated.

  15. Fibre optic cable in the nuclear industry

    International Nuclear Information System (INIS)

    Roberts, Berwyn

    1987-01-01

    The uses of optical fibre cables to transmit light signals include medical applications and telecommunications. In the nuclear industry the applications include process control and monitoring, conventional datacoms, security fencing and sensors. Time division multiplexing is described and currently available fibre optic multipexers are listed and explained. Single and multimode fibres are mentioned. Fibre optics are also used in cryogenics, to monitor the integrity of the storage vessels for cryogenic liquids. The uses of fibre optics at Hartlepool, Heysham I and Torness are mentioned in particular. (UK)

  16. 77 FR 67290 - Basic Service Tier Encryption Compatibility Between Cable Systems and Consumer Electronics Equipment

    Science.gov (United States)

    2012-11-09

    ...-126] Basic Service Tier Encryption Compatibility Between Cable Systems and Consumer Electronics... between consumer electronics equipment (such as digital television sets) and newly encrypted cable service... Act''), Congress sought to make sure that consumer electronics equipment could receive cable...

  17. Continued development of a non-proprietary, high-tension, cable end terminal system.

    Science.gov (United States)

    2016-04-29

    A non-proprietary, cable guardrail system is currently under development for the Midwest States Pooled Fund Program. : A cable guardrail end terminal was necessary to accompany the cable guardrail system. The objective of this research : project was ...

  18. A PSO Driven Intelligent Model Updating and Parameter Identification Scheme for Cable-Damper System

    Directory of Open Access Journals (Sweden)

    Danhui Dan

    2015-01-01

    Full Text Available The precise measurement of the cable force is very important for monitoring and evaluating the operation status of cable structures such as cable-stayed bridges. The cable system should be installed with lateral dampers to reduce the vibration, which affects the precise measurement of the cable force and other cable parameters. This paper suggests a cable model updating calculation scheme driven by the particle swarm optimization (PSO algorithm. By establishing a finite element model considering the static geometric nonlinearity and stress-stiffening effect firstly, an automatically finite element method model updating powered by PSO algorithm is proposed, with the aims to identify the cable force and relevant parameters of cable-damper system precisely. Both numerical case studies and full-scale cable tests indicated that, after two rounds of updating process, the algorithm can accurately identify the cable force, moment of inertia, and damping coefficient of the cable-damper system.

  19. Copper Cable Recycling Technology. Innovative Technology Summary Report

    International Nuclear Information System (INIS)

    2001-01-01

    The United States Department of Energy (DOE) continually seeks safer and more cost-effective technologies for use in deactivation and decommissioning (D and D) of nuclear facilities. The Deactivation and Decommissioning Focus Area (DDFA) of the DOE's Office of Science and Technology (OST) sponsors large-scale demonstration and deployment projects (LSDDPs). At these LSDDPs, developers and vendors of improved or innovative technologies showcase products that are potentially beneficial to the DOE's projects and to others in the D and D community. Benefits sought include decreased health and safety risks to personnel and the environment, increased productivity, and decreased costs of operation. The Idaho National Engineering and Environmental Laboratory (INEEL) generated a list of statements defining specific needs and problems where improved technology could be incorporated into ongoing D and D tasks. One such need is to reduce the volume of waste copper wire and cable generated by D and D. Deactivation and decommissioning activities of nuclear facilities generates hundreds of tons of contaminated copper cable, which are sent to radioactive waste disposal sites. The Copper Cable Recycling Technology separates the clean copper from contaminated insulation and dust materials in these cables. The recovered copper can then be reclaimed and, more importantly, landfill disposal volumes can be reduced. The existing baseline technology for disposing radioactively contaminated cables is to package the cables in wooden storage boxes and dispose of the cables in radioactive waste disposal sites. The Copper Cable Recycling Technology is applicable to facility decommissioning projects at many Department of Energy (DOE) nuclear facilities and commercial nuclear power plants undergoing decommissioning activities. The INEEL Copper Cable Recycling Technology Demonstration investigated the effectiveness and efficiency to recycle 13.5 tons of copper cable. To determine the effectiveness

  20. Cook Strait cable leak investigation, March-June 1985

    International Nuclear Information System (INIS)

    Barry, B.J.; Fitzgerald, G.J.

    1985-09-01

    An investigation was made to locate a gas leak in an under-sea electric power cable. Krypton-85 was used as the tracer. Despite problems with the investigation there was strong evidence to suggest that the leak was in the joint between the land and sea portions of the cable. (auths)

  1. A Critical Look At South Dakota Cable TV Franchising.

    Science.gov (United States)

    Williamson, Rick P.

    An examination of the present status and future potential of cable television (CATV) in South Dakota is conducted. Chapter 1 offers a brief introduction to cable in the State and Chapter 2 discusses the value of CATV to South Dakota. The next Chapter presents a State plan for communications and the fourth deals with the subject of franchising. The…

  2. Lightning-resistant, low-inductance detonator cables

    Energy Technology Data Exchange (ETDEWEB)

    Druce, R.L.; Lee, R.S.; Moua, K.

    1994-04-01

    A lightning strike on a flat detonator cable in close proximity to a high explosive (HE) main charge poses a possible detonation hazard if the electrical explosion of the cable launches the dielectric cover coat of the cable at a high enough velocity to shock-initiate the HE. The detonator cable for the W87 system has been demonstrated to be incapable of initiating LX-17 main-charge explosive even for a 99 percentile negative lightning strike (1). The W87 cable is a relatively high inductance cable, unsuitable for use with low-inductance firesets. We have performed tests on a low-inductance cable designed for the W89 program, which show it to be marginal in its ability to withstand a lightning strike without the possibility of initiating a heated LX-17 main charge HE. A new cable design, proposed by R.E. Lee of LLNL has been tested and shown to be capable of withstanding a 99 percentile negative lightning strike without initiating LX-17 heated to 250{degree}C.

  3. Uses of Cable Television in Eight Midwestern Communities.

    Science.gov (United States)

    Gotsch, Constance M.

    This study of midwestern cable television systems was designed to accomplish three purposes: (1) compare recommended administration and franchise provisions with actual administration and franchise provisions to see how these policies relate to the future development of educational channels; (2) determine how educators and cable managers work…

  4. Measurements and modeling of EMC, applied to cabling and wiring

    NARCIS (Netherlands)

    Bargboer, G.

    2011-01-01

    A myriad of cables transport power and communication signals in larger buildings and installations. Cross talk between cables and connected equipment is a major concern. Regulations do exist, but often show to be insufficient to avoid undesirable coupling. The current thesis research addresses this

  5. 24 CFR 3285.906 - Telephone and cable TV.

    Science.gov (United States)

    2010-04-01

    ... URBAN DEVELOPMENT MODEL MANUFACTURED HOME INSTALLATION STANDARDS Optional Information for Manufacturer's Installation Instructions § 3285.906 Telephone and cable TV. It is recommended that the installation instructions explain that telephone and cable TV wiring should be installed in accordance with requirements of...

  6. Comparison of several innovative bridge cable surface modifications

    DEFF Research Database (Denmark)

    Kleissl, Kenneth; Georgakis, Christos T.

    Over the last two decades, several bridge cable manufacturers have introduced surface modifications on the high-density polyethylene (HDPE) sheathing that is installed for the protection of inner cable strands or wires. The modifications are based on research undertaken predominantly in Europe...

  7. Aerodynamic force coefficients of plain bridge cables in wet conditions

    DEFF Research Database (Denmark)

    Matteoni, Giulia; Georgakis, Christos T.

    In this paper, the aerodynamic forces and force coefficients from preliminary static wind tunnel tests on a plain cable in wet conditions are presented. The presented results are for several different relative cable wind-angles. A comparison is made with tests in dry conditions. In dry conditions...

  8. Chemical oxidation of cable insulating oil contaminated soil

    NARCIS (Netherlands)

    Jinlan Xu,; Pancras, T.; Grotenhuis, J.T.C.

    2011-01-01

    Leaking cable insulating oil is a common source of soil contamination of high-voltage underground electricity cables in many European countries. In situ remediation of these contaminations is very difficult, due to the nature of the contamination and the high concentrations present. Chemical

  9. Prevention of cable fires in nuclear power plants

    International Nuclear Information System (INIS)

    Murota, George; Yajima, Kazuo

    1979-01-01

    Nuclear power generation is indispensable to secure required electric power, therefore double or triple safety measures are necessary to prevent serious accidents absolutely. As for the countermeasures to cable fires, interest grew rapidly with the fire in Browns Ferry Power Station in USA in 1975 as the turning point, because multi-strand grouped cables caused to promote the spread of fire. In Japan, also the fire prevention measures for wires and cables were more strengthened, and the measures for preventing the spread of cable fires with the agent preventing the spread of fires have occupied the important position. When multi-strand cables are ignited by some cause, the fire spreads with very large combustion force along wirings to other rooms and installations, and electric systems are broken down. The harmful corrosive gas generated from the burning coating materials of cables diffuses very quickly. In nuclear power stations, the cables which are very hard to burn are adopted, fire prevention sections are established positively, the fire-resisting capability of fire prevention barriers is reviewed, and fire-resisting and smoke-preventing treatments are applied to the parts where cables penetrate walls, floors or ceilings. The paint and the sealing material which prevent the spread of fires are introduced. (Kako, I.)

  10. Optimized and practical electrical joints for CORC type HTS cables

    CERN Document Server

    Mulder, T; van der Laan, D C; Mentink, M G T; Dhallé, M; ten Kate, H H J

    2015-01-01

    Within CERN the development of REBCO-CORC (Conductor On Round Core) type cables is pursued in view of possible application in future detector and accelerator magnets. An important issue is the design and qualification of terminations for connecting CORC cables mutually or to bus-bars. A termination design is envisaged that combines a simple manufacturing process with a lowest possible joint terminal resistance in the few nΩ range at 4.2 K, first for a single CORC cable and subsequently for CORC based Cable-in-Conduit Conductors. The investigation concerns the effect of tapering the CORC cable within the joint to form a staircase like geometry, which allows current to pass more directly from the copper joint casing to the inner REBCO layers of the CORC cable. Simulations have shown a substantial decrease in joint resistance at operating current in the case both CORC cable and joint casing are tapered. The CORC cable and new joint were tested at CERN. In this paper, some details of the new joint design, fabric...

  11. Optimized and practical electrical joints for CORC type HTS cables

    International Nuclear Information System (INIS)

    Mulder, T; Dudarev, A; Mentink, M G T; Ten Kate, H H J; Van der Laan, D C; Dhallé, M

    2015-01-01

    Within CERN the development of REBCO-CORC (Conductor On Round Core) type cables is pursued in view of possible application in future detector and accelerator magnets. An important issue is the design and qualification of terminations for connecting CORC cables mutually or to bus-bars. A termination design is envisaged that combines a simple manufacturing process with a lowest possible joint terminal resistance in the few nΩ range at 4.2 K, first for a single CORC cable and subsequently for CORC based Cable-in-Conduit Conductors. The investigation concerns the effect of tapering the CORC cable within the joint to form a staircase like geometry, which allows current to pass more directly from the copper joint casing to the inner REBCO layers of the CORC cable. Simulations have shown a substantial decrease in joint resistance at operating current in the case both CORC cable and joint casing are tapered. The CORC cable and new joint were tested at CERN. In this paper, some details of the new joint design, fabrication process, and model are presented and the results are summarized. (paper)

  12. New, clean handling process introduced to improve cable quality

    Energy Technology Data Exchange (ETDEWEB)

    Hunt, C G

    1990-05-01

    The clean room system introduced by Canada Wire and Cable Limited in its Toronto plant for its cable manufacturing operation is described. While clean room technology is common in the food processing industry, optical and aerospace manufacturing processes, this is the first time it has been applied to wire and cable extrusion in North America. The purpose of the clean compound handling system is to prevent particle contamination in the shielding and cable insulation materials, as part of an effort to prevent premature underground electric cable failures. Two rooms are dedicated to handling different types of insulation compound, two are dedicated to receiving semi-conducting shielding material, and the fifth room functions as an air lock for the two insulation rooms. The atmosphere is highly regulated with programmable logic control. The air supply filters capture 99.97% of all particles 0.3 microns or larger. The system also maintains air temperature, relative humidity and static pressure. The life variability of cross-linked polyethylene primary distribution cable is dependant on five factors: material purity, extra clean compound handling, cable design, manufacturing process, and installation and operation practices. The clean room system is expected to result in cable that is more resistant to water treeing failures. 2 figs.

  13. Heat resistant wire and cable and heat shrinkable tubes

    Energy Technology Data Exchange (ETDEWEB)

    Ueno, Keiji [Sumitomo Electric Industries Ltd. (Japan)

    1994-12-31

    Radiation processes have been used in industrial fields (e.g. wire and cable, heat shrinkable tubes) for about 30 years. In Japan, 60 electron beam accelerators were used in R and D, 54 in wire and cable, 24 in tire rubber, 16 in paint curing, 14 in PE foam and 9 accelerators were used in heat shrinkable tubes in 1993. Many properties (e.g. solder resistance, thermal deformation, and solven resistance) of wire and cable are improved by using radiation processes, and many kinds of radiation crosslinked wire and cable are used in the consumer market (TV sets, VTR`s, audio disc players, etc.), automobiles (automobile wire harnesses, fusible link wires, sensor cables etc.), and the industrial market (computer cables, cables for keyboards, coaxial cables, etc.). Another important industrial application of E{beta} radiation process is heat shrinkable tubes. Heat shinkable tubes, heated by a hot gun, shrink 1/2 {approx} 1/3 of their inner diameters. Heat shrinkable tubes are used for covers of distributing line terminals, joint covers of telecommunication lines, protection of fuel pipe lines and so on. In this seminar, actual applications and characteristic properties of radiation crosslinked materials are presented.

  14. 47 CFR 15.118 - Cable ready consumer electronics equipment.

    Science.gov (United States)

    2010-10-01

    ... 47 Telecommunication 1 2010-10-01 2010-10-01 false Cable ready consumer electronics equipment. 15... Unintentional Radiators § 15.118 Cable ready consumer electronics equipment. (a) All consumer electronics TV... provisions of this section. Consumer electronics TV receiving equipment that includes features intended for...

  15. Cable systems for experimental facilities in JAERI TANDEM ACCELERATOR BUILDING

    International Nuclear Information System (INIS)

    Tukihashi, Yoshihiro; Yoshida, Tadashi; Takekoshi, Eiko

    1979-03-01

    Measuring cable systems for experimental facilities in JAERI TANDEM ACCELERATOR BUILDING were completed recently. Measures are taken to prevent penetration of noises into the measuring systems. The cable systems are described in detail, including power supplies and grounding for the measuring systems. (author)

  16. Proposed Ordinance for the Regulation of Cable Television. Working Draft.

    Science.gov (United States)

    Chicago City Council, IL.

    A model ordinance is proposed for the regulation of cable television in the city of Chicago. It defines the language of the ordinance, sets forth the method of granting franchises, and describes the terms of the franchises. The duties of a commission to regulate cable television are listed and the method of selecting commission members is…

  17. Evaluation of cable aging degradation based on plant operating condition

    International Nuclear Information System (INIS)

    Kim, Jong-Seog

    2005-01-01

    Extending the lifetime of nuclear power plant [(hereafter referred simply as ''NPP'')] is one of the most important concerns in the world nuclear industry. Cables are one of the long live items which have not been considered to be replaced during the design life of NPP. To extend the cable life beyond the design life, we need to prove that the design life is too conservative compared with the actual aging. Condition monitoring is one of the useful ways for evaluating the aging condition of cable. In order to simulate the natural aging in nuclear power plant, a study on accelerated aging needs to be conducted first. In this paper, evaluations of mechanical aging degradation for cable jacket were performed after accelerated aging under the continuous heating and intermittent heating. Contrary to general expectation, the intermittent heating to cable jacket showed low aging degradation, 50% break-elongation and 60% indenter modulus, compared with continuous heating. With the plant maintenance period of 1 month after every 12 or 18 months operation, we can easily deduce that the life time of cable jacket can be extended much longer than estimated through the general EQ (Environmental Qualification) test, which adopts continuous accelerated aging for determining cable life. Therefore, a systematic approach which considers the actual environment condition of nuclear power plant is required for determining the life of cables. (author)

  18. 7 CFR 1755.507 - Aerial cable services.

    Science.gov (United States)

    2010-01-01

    ... requirements: (1) Strand supported lashed construction shall be used. (2) Where practicable a 5/16 in. (8 mm...) Construction on poles shall comply with applicable construction drawings for regular line construction. Aerial... copper and fiber optic cables. (4) Where practicable, aerial cable shall pass under electrical guys...

  19. Education and Cable TV: A Guide to Franchising and Utilization.

    Science.gov (United States)

    Shafer, Jon

    Designed to provide the educator with some answers about cable television (CATV), this monograph and resource catalog provides a basic description of CATV, its educational uses, and the franchising provisions which relate to its educational uses. The transition of CATV from an association with broadcast television toward cable information systems…

  20. Distance Protection of Cross-Bonded Transmission Cable-Systems

    DEFF Research Database (Denmark)

    Bak, Claus Leth; F. Jensen, Christian

    2014-01-01

    In this paper the problems of protecting a cross-bonded cable system using distance protection are analysed. The combination of the desire to expand the high voltage transmission grid and the public's opinion towards new installations of overhead lines (OHL), more and more transmission cable syst...

  1. Long-term monitoring FBG-based cable load sensor

    Science.gov (United States)

    Zhang, Zhichun; Zhou, Zhi; Wang, Chuan; Ou, Jinping

    2006-03-01

    Stay cables are the main load-bearing components of stayed-cable bridges. The cables stress status is an important factor to the stayed-cable bridge structure safety evaluation. So it's very important not only to the bridge construction, but also to the long-term safety evaluation for the bridge structure in-service. The accurate measurement for cable load depends on an effective sensor, especially to meet the long time durability and measurement demand. FBG, for its great advantage of corrosion resistance, absolute measurement, high accuracy, electro-magnetic resistance, quasi-distribution sensing, absolute measurement and so on, is the most promising sensor, which can cater for the cable force monitoring. In this paper, a load sensor has been developed, which is made up of a bushing elastic supporting body, 4 FBGs uniformly-spaced attached outside of the bushing supporting body, and a temperature compensation FBG for other four FBGs, moreover a cover for protection of FBGs. Firstly, the sensor measuring principle is analyzed, and relationship equation of FBG wavelength shifts and extrinsic load has also been gotten. And then the sensor calibration experiments of a steel cable stretching test with the FBG load sensor and a reference electric pressure sensor is finished, and the results shows excellent linearity of extrinsic load and FBG wavelength shifts, and good repeatability, which indicates that such kind of FBG-based load sensor is suitable for load measurement, especially for long-term, real time monitoring of stay-cables.

  2. Double Layered Sheath in Accurate HV XLPE Cable Modeling

    DEFF Research Database (Denmark)

    Gudmundsdottir, Unnur Stella; Silva, J. De; Bak, Claus Leth

    2010-01-01

    This paper discusses modelling of high voltage AC underground cables. For long cables, when crossbonding points are present, not only the coaxial mode of propagation is excited during transient phenomena, but also the intersheath mode. This causes inaccurate simulation results for high frequency...

  3. Shape modification of bridge cables for aerodynamic vibration control

    DEFF Research Database (Denmark)

    Kleissl, Kenneth; Georgakis, Christos

    2010-01-01

    In this paper, the viability of modifying cable shape and surface for the purpose of controlling wind-induced vibrations is examined. To this end, an extensive wind-tunnel test campaign was carried out on various cable sections in the critical Reynolds number region under both smooth and turbulen...

  4. On stiffening cables of a long reach manipulator

    International Nuclear Information System (INIS)

    Wang, S.L.; Santiago, P.

    1996-01-01

    A long reach manipulator will be used for waste remediation in large underground storage tanks. The manipulator's slenderness makes it flexible and difficult to control. A low-cost and effective method to enhance the manipulator's stiffness is proposed in this research by using suspension cables. These cables can also be used to accurately measure the position of the manipulator's wrist

  5. Advanced nuclear power plant design with minimized use of cables

    International Nuclear Information System (INIS)

    Anon.

    1984-01-01

    The objective of this report is to present a nuclear power plant design with a minimum utilization of cables. The report describes the types of software and hardware that will be needed to minimize hard-wired control and instrumentation circuits and to reduce the quantity of low voltage power cables while maintaining a high availability and reliability of the plant control systems

  6. Reducing Actuator Requirements in Continuum Robots Through Optimized Cable Routing.

    Science.gov (United States)

    Case, Jennifer C; White, Edward L; SunSpiral, Vytas; Kramer-Bottiglio, Rebecca

    2018-02-01

    Continuum manipulators offer many advantages compared to their rigid-linked counterparts, such as increased degrees of freedom and workspace volume. Inspired by biological systems, such as elephant trunks and octopus tentacles, many continuum manipulators are made of multiple segments that allow large-scale deformations to be distributed throughout the body. Most continuum manipulators currently control each segment individually. For example, a planar cable-driven system is typically controlled by a pair of cables for each segment, which implies two actuators per segment. In this article, we demonstrate how highly coupled crossing cable configurations can reduce both actuator count and actuator torque requirements in a planar continuum manipulator, while maintaining workspace reachability and manipulability. We achieve highly coupled actuation by allowing cables to cross through the manipulator to create new cable configurations. We further derive an analytical model to predict the underactuated manipulator workspace and experimentally verify the model accuracy with a physical system. We use this model to compare crossing cable configurations to the traditional cable configuration using workspace performance metrics. Our work here focuses on a simplified planar robot, both in simulation and in hardware, with the goal of extending this to spiraling-cable configurations on full 3D continuum robots in future work.

  7. Elasticity and mechanical advantage in cables and ropes

    International Nuclear Information System (INIS)

    O'Shea, M J

    2007-01-01

    The conditions under which one can gain mechanical advantage by pulling with a force F perpendicular to a cable (or rope) that is fixed at both ends are examined. While this is a commonly discussed example in introductory physics classes, its solution in terms of fundamental properties of the cable requires one to model the elasticity of the cable. This solution has several complex and interesting features, e.g. a large increase in the tension in the cable may occur upon application of F if (i) F lies in a certain range and (ii) the initial tension T 1 in the cable (before F is applied) satisfies T 1 < 0.0340 κ. Here, κ is the spring constant of a unit length of the cable. For steel cables and cables composed of other materials such as carbon nanorods where the elasticity is low, significant increases in tension are possible. Examples involving walking a tightrope and attempting to increase the tension in a rope hauling a load are considered. Two programs to solve the equations of this work are available in the electronic version of this journal

  8. Automation of Underground Cable Laying Equipment Using PLC and Hmi

    Science.gov (United States)

    Mal Kothari, Kesar; Samba, Vishweshwar; Tania, Kinza; Udayakumar, R., Dr; Karthikeyan, Ram, Dr

    2018-04-01

    Underground cable laying is an alternative for overhead cable laying of telecommunication and power transmission lines. It is becoming very popular in recent times because of some of its advantages over overhead cable laying. This type of cable laying is mostly practiced in developed countries because it is more expensive than overhead cable laying. Underground cable laying is more suitable when land is not available, and it also increases the aesthetics. This paper implements the automation on a manually operated cable pulling winch machine using programmable logic controller (PLC). Winch machines are useful in underground cable laying. The main aim of the project is to replace all the mechanical functions with electrical controls which are operated through a touch screen (HMI). The idea is that the machine should shift between parallel and series circuit automatically based on the pressure sensed instead of manually operating the solenoid valve. Traditional means of throttling the engine using lever and wire is replaced with a linear actuator. Sensors such as proximity, pressure and load sensor are used to provide the input to the system. The HMI used will display the speed, length and tension of the rope being winded. Ladder logic is used to program the PLC.

  9. Medium and high voltage power cables market in Europe

    International Nuclear Information System (INIS)

    Kupiec, M.

    1992-06-01

    This note gives an overview of the European market for medium and high voltage power cables. In this text, emphasis is placed on suppliers and important European clients; there is also a brief review of the different techniques for cable laying and utilization in Europe. This not has mainly been drafted from informations supplied by EUROPACABLE

  10. Heat resistant wire and cable and heat shrinkable tubes

    International Nuclear Information System (INIS)

    Keiji Ueno

    1994-01-01

    Radiation processes have been used in industrial fields (e.g. wire and cable, heat shrinkable tubes) for about 30 years. In Japan, 60 electron beam accelerators were used in R and D, 54 in wire and cable, 24 in tire rubber, 16 in paint curing, 14 in PE foam and 9 accelerators were used in heat shrinkable tubes in 1993. Many properties (e.g. solder resistance, thermal deformation, and solven resistance) of wire and cable are improved by using radiation processes, and many kinds of radiation crosslinked wire and cable are used in the consumer market (TV sets, VTR's, audio disc players, etc.), automobiles (automobile wire harnesses, fusible link wires, sensor cables etc.), and the industrial market (computer cables, cables for keyboards, coaxial cables, etc.). Another important industrial application of Eβ radiation process is heat shrinkable tubes. Heat shinkable tubes, heated by a hot gun, shrink 1/2 ∼ 1/3 of their inner diameters. Heat shrinkable tubes are used for covers of distributing line terminals, joint covers of telecommunication lines, protection of fuel pipe lines and so on. In this seminar, actual applications and characteristic properties of radiation crosslinked materials are presented

  11. Ground Loop Impedance of Long EHV Cable Lines

    DEFF Research Database (Denmark)

    Ohno, Teruo; Bak, Claus Leth; Sørensen, Thomas K.

    2012-01-01

    The distance protection scheme without communication is often applied to the backup protection of EHV cable lines. For a reliable operation of a ground distance relay, the ground loop impedance of EHV cable lines needs to have a linear relationship to the distance from the relay location...... to the fault location. The discontinuity of the ground loop impedance at cross-bonding points may have an ill effect on the reliable operation of the ground distance relay. However, the cause and parameters of the discontinuity and its effects on the ground distance relay protection have not been discussed...... in literature. Through the calculation of the ground loop impedance for cable lines, it has been found that, for long EHV cable lines, the reliable operation of the ground distance relay is possible with a typical relay setting. Effects of parameters, such as substation grounding, cable layouts...

  12. Development of low-smoke, flame-retarding cables

    International Nuclear Information System (INIS)

    Kato, H.; Kanemitsuya, K.; Furukawa, K.; Mio, K.

    1983-01-01

    A great deal of attention has been given to the potential fire hazard of combustion gases from organic materials. Although cable industries have developed flame-retarding organic materials for the insulation and jacketing of wires and cables, there was insufficient prevention of toxic gas formation during combustion. To cope with these problems associated with conventional PVC cables, the authors have directed to develop low-smoke, flame-retarding plasticized PVC formulations retaining the original mechanical, electrical and aging properties. A series of basic investigations on smoke suppression followed by an evaluation on practical cables could indicate some effective means to end these problems. This paper describes the results and discussion on smoke suppressing study of plasticized PVC as well as behavior and characteristics of the low-smoke, flame-retarding PVC wires and cables using these materials. (author)

  13. Overcurrent experiments on HTS tape and cable conductor

    DEFF Research Database (Denmark)

    Tønnesen, Ole; Jensen, Kim Høj; Træholt, Chresten

    2001-01-01

    their critical current. In this light, it is important to investigate the response of HTS tapes and cable conductors to overcurrents several times the critical current. A number of experiments have been performed on HTS tapes and cable conductors, with currents up to 20 times the critical current. During...... overcurrent experiments, the voltage, and the temperature were measured as functions of time in order to investigate the dynamic behavior of the HTS tape and cable conductor. After each experiment, damage to the superconductors was assessed by measuring the critical current. Preliminary results show...... that within seconds an HTS tape (critical current=17 A) heats above room temperature with an overcurrent larger than 140 A. Similar overcurrent experiments showed that a HTS cable conductor could sustain damage with overcurrents exceeding 10 times the critical current of the cable conductor....

  14. Life-assessment technique for nuclear power plant cables

    International Nuclear Information System (INIS)

    Bartonicek, B.; Hnat, V.; Placek, V.

    1998-01-01

    The condition of polymer-based cable material can be best characterized by measuring elongation at break of its insulating materials. However, it is not often possible to take sufficiently large samples for measurement with the tensile testing machine. The problem has been conveniently solved by utilizing differential scanning calorimetry technique. From the tested cable, several microsamples are taken and the oxidation induction time (OIT) is determined. For each cable which is subject to the assessment of the lifetime, the correlation of OIT with elongation at break and the correlation of elongation at break with the cable service time has to be performed. A reliable assessment of the cable lifetime depends on accuracy of these correlations. Consequently, synergistic effects well known at this time - dose rate effects and effects resulting from the different sequence of applying radiation and elevated temperature must be taken into account

  15. Behaviour of French electrical cables under fire conditions

    Energy Technology Data Exchange (ETDEWEB)

    Bertrand, R.; Chaussard, M.; Gonzalez, R.; Lacoue, J.; Mattei, J.M.; Such, J.M

    2001-12-01

    A fire Probabilistic Safety Assessment - called fire PSA - is being carried out by the French Institute of Nuclear Safety and Protection (IPSN) to be used in the framework of the safety assessment of operating 900 MWe PWRs. The aim of this study is to evaluate the core damage conditional probability which could result from a fire. A fire can induce unavailability of safety equipment notably damaging electrical cables that are a significant risk contributor. The purpose of this communication is to present the electrical cable fire tests carried out by IPSN to identify the failure modes and to determine the cable damage criteria. Moreover, are indicated the impact of each kind of cable failure mode and the methodology used to estimate the conditional probability of a failure mode when cable damage occurred. (authors)

  16. MVAC Submarine cable, magnetic fields measurements and analysis

    DEFF Research Database (Denmark)

    Arentsen, Martin Trolle; Expethit, Adrian; Pedersen, Morten Virklund

    2017-01-01

    Standard 60287. Researchers believe that the wire armour of three phased submarine cables is the reason for the inaccurate calculations by the standard. Studies show that the magnetic behaviour of these cables are changed due to the wire armour. In order to investigate this hypothesis, this paper intends...... to supply the theoretical research with data from magnetic field measurements on a wire armoured 3-phase submarine cable, together with an investigation of the induced currents in the different cable components. The influence of the physical arrangement of the armour wires on the electric behaviour is also...... investigated, since several researchers believe that the twisting of the armour wires result in zero net induced voltage over one helix length. This is shown to be valid for the tested cable. Finally a replica of the armour has been built with just a single conductor in the centre. This setup was used...

  17. Development of environmental-friendly wire and cable

    International Nuclear Information System (INIS)

    Ueno, Keiji

    1996-01-01

    The electron beam technology has been used in many industrial fields as a method of conventional polymer modification or optimum processability. The main industrial fields of radiation crosslinking are wire and cable, heat shrinkable tubings, plastic foams, precuring of tires, floppy disk curing, foods packaging films, and so on. The radiation crosslinking of wire and cable was started in 1961 in Japan and 15 wire and cable companies are now using electron beam accelerators for production or R and D. The dominant characteristics of crosslinking of insulation materials are application at high temperature, good oil and chemical resistibility and high mechanical properties. These radiation crosslinking wire and cable are applied widely in electronics equipments and automobiles. Recently, electronics manufacturers have indicated deep concern over the effects on the environment. Wire and cable also are required to be applicable for environmental preservation. (J.P.N.)

  18. Sound cable crossing brings inexpensive electric power to Long Island

    International Nuclear Information System (INIS)

    Grzan, J.; Goyette, R.

    1992-01-01

    This paper reports that while many electric-utility customers in New York State benefit from inexpensive hydroelectric power from Canada and upstate New York, lack of sufficient transmission connections have prevented this electricity from reaching Long Island. However, a newly constructed underground/underwater link capable of carrying 700-MW now transmits low-cost electricity to the island, saving money for customers. The self-contained fluid-filled cable used for the underwater portion of the project is the largest underwater cable in the world. The use of high-pressure, fluid-filled pipe-type cable on the land portion represents the largest application of paper-polypropylene-paper (PPP) insulated cable in the United States. State-of-the-art technologies were implemented in the use of temperature monitoring and leak detection systems, SF 6 gas-insulated substation, and underwater cable laying and embedment techniques

  19. Losses in armoured three-phase submarine cables

    DEFF Research Database (Denmark)

    Ebdrup, Thomas; Silva, Filipe Miguel Faria da; Bak, Claus Leth

    2014-01-01

    The number of offshore wind farms will keep increasing in the future as a part of the shift towards a CO2 free energy production. The energy harvested from the wind farm must be brought to shore, which is often done by using a three-phase armoured submarine power cable. The use of an armour...... increases the losses in armoured cables compared to unarmoured cables. In this paper a thorough state of the art analysis is conducted on armour losses in three-phase armoured submarine power cables. The analysis shows that the IEC 60287-1-1 standard overestimates the armour losses which lead...... to the installation of cables with excessive phase conductor cross section. This paper also presents an example of the potential economic benefits of having a better knowledge of the losses introduced by the armour....

  20. Potential Impact of Submarine Power Cables on Crab Harvest

    Science.gov (United States)

    Bull, A. S.; Nishimoto, M.

    2016-02-01

    Offshore renewable energy installations convert wave or wind energy to electricity and transfer the power to shore through transmission cables laid on or buried beneath the seafloor. West coast commercial fishermen, who harvest the highly prized Dungeness crab (Metacarcinus magister) and the rock crab (Cancer spp.), are concerned that the interface of crabs and electromagnetic fields (EMF) from these cables will present an electrified fence on the seafloor that their target resource will not cross. Combined with the assistance of professional fishermen, submarine transmission cables that electrify island communities and offshore oil platforms in the eastern Pacific provide an opportunity to test the harvest of crab species across power transmission cables. In situ field techniques give commercial crab species a choice to decide if they will cross fully energized, EMF emitting, power transmission cables, in response to baited traps. Each independent trial is either one of two possible responses: the crab crosses the cable to enter a trap (1) or the crab does not cross the cable to enter a trap (0). Conditions vary among sample units by the following categorical, fixed factors (i.e., covariates) of cable structure (buried or unburied); direction of cable from crab position (west or east, north or south); time and season. A generalized linear model is fit to the data to determine whether any of these factors affect the probability of crabs crossing an energized cable to enter baited traps. Additionally, the experimental design, aside from the number of runs (set of sample trials) and the dates of the runs, is the same in the Santa Barbara Channel for rock crab and Puget Sound for Dungeness crab, and allows us to compare the capture rates of the two species in the two areas. We present preliminary results from field testing in 2015.

  1. Cable-to-post attachments for use in non-proprietary high-tension cable median barrier - phase II.

    Science.gov (United States)

    2016-03-24

    The objective of this study was to reevaluate and improve the existing cable-to-post attachment hardware that is utilized : in the non-proprietary cable barrier being developed at MwRSF. The study focused on redesigning the bolted, tabbed : bracket (...

  2. Aerodynamics of the cable of cable-stayed bridges; Shachokyo cable no kuriki shindo tokusei no rikai to soreni motozuku kuriki seishinho no teian

    Energy Technology Data Exchange (ETDEWEB)

    Matsumoto, M. [Kyoto University, Kyoto (Japan). Faculty of Engineering; Aoki, J.; Fuji, D. [West Japan Railway Company, Osaka (Japan); Kitayama, N. [Ishikawajima-Harima Heavy Industries Co. Ltd., Tokyo (Japan); Daito, Y. [Kyoto University, Kyoto (Japan)

    1996-07-21

    Wind tunnel tests were conducted assuming the aerodynamics of the cable of cable-stayed bridges especially in the case of strong wind with rain. Based on the results, an aerodynamic damping method was proposed. Factors of the rain vibration generation include the three-dimensional axial flow behind the cable, which is formed by the wind direction deviation angle, the upper side water flow on the cable surface formed by the rain, and the Karman vortex shedding, which are not uniform in the span direction. Newly proposed cable with elliptical plates showed an effective dumping performance. It restrains the formation of water flow due to its profile, and is effective for unstableness due to water flow formation. Distribution of the axial flow in the cable span direction was made clear. Three-dimensionality of the vortex shedding was greatly affected by this axial flow. Frequency of the Karman vortex shedding changed in the wide band by the axial flow. It was suggested that three-dimensionality of the flow field is enhanced by the rolling vibration, resulting in the unstableness of heaving vibration. 5 refs., 15 figs.

  3. Design of anti-theft/cable cut real time alert system for copper cable using microcontroller and GSM technology

    Science.gov (United States)

    Lim, E. K.; Norizan, M. N.; Mohamad, I. S.; Yasin, M. N. M.; Murad, S. A. Z.; Baharum, N. A.; Jamalullail, N.

    2017-09-01

    This paper presents the design of anti-theft/cable cut real time alert system using microcontroller and GSM technology. The detection part is using the electrical circuit wire connection in detecting the voltage drop of the cable inside the microcontroller digital input port. The GSM wireless modem is used to send the location of cable cut directly to the authority mobile phone. Microcontroller SK40C with Microchip PIC16F887 is used as a controller to control the wireless modem and also the detection device. The device is able to detect and display the location of the cable cut on the LCD display besides of and sending out the location of the cable break to the authority mobile phone wirelessly via SMS.

  4. Effect of Concrete Creep on the displacement of single tower single cable plane Extradosed Cable-stayed Bridge

    Science.gov (United States)

    Shi, Jing-xian; Ran, Zhi-hong

    2018-03-01

    Extradossed Cable-stayed Bridge is both cable-stayed Bridge and Continuous rigid frame bridge mechanics feature, Beam is the main force components, cable is supplement.This article combined with a single tower and single cable plane Extradossed cable-stayed bridge in Yunnan, use different creep calculation models and analysis deflection caused by creep effects. The results showing that deflection caused by creep effect is smaller than the same span continuous rigid frame bridge, the value is about 2cm. On the other hand the deflection is increasing with ambient humidity decreases, therefore in the dry environment the calculation model is relatively large in the pre-camber. In the choice of RC creep model is significant in the dry areas.

  5. Improved practical formulas for estimation of cable tension by vibration method; Shindoho ni yoru cable choryoku jitsuyo santeishiki no hosei

    Energy Technology Data Exchange (ETDEWEB)

    Zui, H. [Setsunan University, Osaka (Japan). Faculty of Engineering; Shinke, T. [Kobe Technical College, Kobe, Kobe (Japan); Hamazaki, Y. [Kobe Steel, Ltd., Kobe (Japan)

    1995-10-21

    The vibration method is usually utilized on the measurement of cable tension during construction of cable bridge such as Nielsen bridges or cable stayed bridges. Practical formula for the vibration method previously proposed by authors is often used where bending rigidity is taken into account. These formula, however, have a certain limit of application and do not yield good results when the cable is not slender or not enough mentioned. The practical formula is modified to improve the accuracy and new formulas are made. The new practical formulas are applicable to any cables, regardless of its length and tension in it. The accuracy is confirmed through comparison of the value obtained by practical formulas with measured values and calculated value by F.E.M. 2 refs., 4 figs., 1 tab.

  6. PCACE- PERSONAL COMPUTER AIDED CABLING ENGINEERING

    Science.gov (United States)

    Billitti, J. W.

    1994-01-01

    A computerized interactive harness engineering program has been developed to provide an inexpensive, interactive system which is designed for learning and using an engineering approach to interconnection systems. PCACE is basically a database system that stores information as files of individual connectors and handles wiring information in circuit groups stored as records. This directly emulates the typical manual engineering methods of data handling, thus making the user interface to the program very natural. Data files can be created, viewed, manipulated, or printed in real time. The printed ouput is in a form ready for use by fabrication and engineering personnel. PCACE also contains a wide variety of error-checking routines including connector contact checks during hardcopy generation. The user may edit existing harness data files or create new files. In creating a new file, the user is given the opportunity to insert all the connector and harness boiler plate data which would be part of a normal connector wiring diagram. This data includes the following: 1) connector reference designator, 2) connector part number, 3) backshell part number, 4) cable reference designator, 5) cable part number, 6) drawing revision, 7) relevant notes, 8) standard wire gauge, and 9) maximum circuit count. Any item except the maximum circuit count may be left blank, and any item may be changed at a later time. Once a file is created and organized, the user is directed to the main menu and has access to the file boiler plate, the circuit wiring records, and the wiring records index list. The organization of a file is such that record zero contains the connector/cable boiler plate, and all other records contain circuit wiring data. Each wiring record will handle a circuit with as many as nine wires in the interface. The record stores the circuit name and wire count and the following data for each wire: 1) wire identifier, 2) contact, 3) splice, 4) wire gauge if different from standard

  7. Vertical Cable Seismic Survey for Hydrothermal Deposit

    Science.gov (United States)

    Asakawa, E.; Murakami, F.; Sekino, Y.; Okamoto, T.; Ishikawa, K.; Tsukahara, H.; Shimura, T.

    2012-04-01

    The vertical cable seismic is one of the reflection seismic methods. It uses hydrophone arrays vertically moored from the seafloor to record acoustic waves generated by surface, deep-towed or ocean bottom sources. Analyzing the reflections from the sub-seabed, we could look into the subsurface structure. This type of survey is generally called VCS (Vertical Cable Seismic). Because VCS is an efficient high-resolution 3D seismic survey method for a spatially-bounded area, we proposed the method for the hydrothermal deposit survey tool development program that the Ministry of Education, Culture, Sports, Science and Technology (MEXT) started in 2009. We are now developing a VCS system, including not only data acquisition hardware but data processing and analysis technique. Our first experiment of VCS surveys has been carried out in Lake Biwa, JAPAN in November 2009 for a feasibility study. Prestack depth migration is applied to the 3D VCS data to obtain a high quality 3D depth volume. Based on the results from the feasibility study, we have developed two autonomous recording VCS systems. After we carried out a trial experiment in the actual ocean at a water depth of about 400m and we carried out the second VCS survey at Iheya Knoll with a deep-towed source. In this survey, we could establish the procedures for the deployment/recovery of the system and could examine the locations and the fluctuations of the vertical cables at a water depth of around 1000m. The acquired VCS data clearly shows the reflections from the sub-seafloor. Through the experiment, we could confirm that our VCS system works well even in the severe circumstances around the locations of seafloor hydrothermal deposits. We have, however, also confirmed that the uncertainty in the locations of the source and of the hydrophones could lower the quality of subsurface image. It is, therefore, strongly necessary to develop a total survey system that assures a accurate positioning and a deployment techniques

  8. Characterization and drying of caja bagasse (Spondias mombin L. in a tray dryer using a factorial planning

    Directory of Open Access Journals (Sweden)

    Andréia Souto da Silva

    2012-03-01

    Full Text Available The caja (Spondias mombin L. is used in the manufacture of ice-cream, jams, pulps, beverages being also consumed in natura. One of the most important procedures in food conservation is drying, considering that most fresh fruits contain approximately 80% of water. Food drying is used to obtain two basic aspects: (1 the economic factor; in the shipping and handling of the product; (2 at the manipulation; once dried and grinded, the material is rehydrated, at desirable levels, to formulate a new product as in ice cream, jams, yoghurts and drinks and may also be added to pasta, biscuits and other industrialized products. The aim of this study was to investigate the kinetics of caja bagasse drying in a fixed-bed tray dryer, using central composite factorial planning. The following factors were evaluated: temperature (55, 65 and 75 ºC, dryer inlet air velocity (3.2, 4.6 and 6.0 m.s-1 and cake thickness (0.8, 1.2 and 1.6 cm where the response of the considered variable was caja bagasse moisture content (b.s. and the results showed that the main effects and their interactions were significant at a 95% confidence level being the best condition obtained at temperature of 75 ºC, velocity of 6.0 m.s-1 and cake thickness of 0.8 cm.

  9. [What is hidden behind the Baking Tray Task? Study of sensibility and specificity in right-hemispheric stroke patients].

    Science.gov (United States)

    Garcia-Fernandez, Juan; Garcia-Molina, Alberto; Aparicio-Lopez, Celeste; Sanchez-Carrion, Rocío; Ensenat, Antònia; Pena-Casanova, Jordi; Roig-Rovira, Teresa

    2015-12-16

    Tham and Tegner proposed the Baking Tray Task (BTT) as a fast simple assessment test for detecting spatial negligence. However, very few studies have examined its validity as a diagnostic test. To analyse the diagnostic validity of the BTT by measuring its specificity and sensitivity in a sample of subjects with right hemisphere strokes. Forty-eight patients with right hemisphere vascular lesions were distributed in two groups (negligence group, n = 35; non-negligence group, n = 13) according to the scores obtained in a battery of visuospatial examination tests. The participants' performance on the BTT was compared with that of a healthy control group (n = 12). The results showed a high level of sensitivity of the BTT, but low specificity. The performance on the BTT of eight of the 13 members of the non-negligence group was suggestive of negligence. The BTT has proved to be a sensitive test for the detection of spatial negligence. Yet, based on its low specificity, its use alone as a single diagnostic test is not recommended.

  10. Model and simulation of a vacuum sieve tray for T extraction from liquid PbLi breeding blankets

    International Nuclear Information System (INIS)

    Mertens, M.A.J.; Demange, D.; Frances, L.

    2016-01-01

    Highlights: • A simulation tool was developed to analyse, optimise and scale up VST set-ups. • This tool predicts that efficiencies higher than 90% can be reached. • Upscaling to DEMO breeding blanket flow rates results in feasibly sized designs. - Abstract: Tritium self-sufficiency within a nuclear fusion reactor is necessary to demonstrate nuclear fusion as a viable source of energy. Tritium can be produced within liquid eutectic PbLi but then has to be extracted to be refuelled to the plasma. The vacuum sieve tray (VST) method is based on the extraction of tritium from millimetre-scaled oscillating PbLi droplets falling inside a vacuum chamber. A simulation tool was developed describing the fluid dynamics occurring along the PbLi flow and was used to study the influence of the different geometrical and operational parameters on the VST performance. The simulation predicts that extraction efficiencies over 90% can be easily reached according to theory and previous experimental results. The size of the VST extraction unit for a fusion reactor is estimated based on the findings from our single-nozzle model and assuming no T reabsorption. It is found to be in the feasible range. Nevertheless, two approaches are discussed which may further reduce this size by up to 90%. The simulation tool proved to be an easy and powerful way to analyse and optimise VST set-ups at any scale.

  11. Impact of measurement approach on the quality of gamma scanning density profile in a tray type lab-scale column

    International Nuclear Information System (INIS)

    Shahabinejad, H.; Feghhi, S.A.H.; Khorsandi, M.

    2014-01-01

    This article presents a study for investigating impact of the measurement approach on the quality of gamma scanning density profile in tray type columns using experimental and computational evaluations. Experimental density profiles from the total and the photopeak count measurements, as two approaches in gamma ray column scanning technique, has been compared with the computational density profile from Monte Carlo simulation results. We used a laboratory distillation column of 51 cm diameter as an illustrative example for this investigation. 137 Cs was used as a gamma ray source with the activity of 296 MBq (8 mCi), with a NaI(Tl) detector. MCNP4C Monte Carlo code has been used for simulations. The quality of the density profile in the photopeak count approach is relatively within 155–204% better than that of the total count approach for experimental results. The same comparison for simulation results leads to a relative difference within 100–135% for the density profile. - Highlights: • The quality of density profile in gamma scanning technique has been studied. • Quality of density profile depends on the measurement approach. • A laboratory distillation column has been used as an illustrative example. • MCNP4C Monte Carlo code has been used for simulations

  12. Comparison of efficacy of tray-delivered carbamide and hydrogen peroxide for at-home bleaching: a systematic review and meta-analysis.

    Science.gov (United States)

    Luque-Martinez, Issis; Reis, Alessandra; Schroeder, Marcos; Muñoz, Miguel Angel; Loguercio, Alessandro D; Masterson, Danielle; Maia, Lucianne C

    2016-09-01

    The aim of the study was to compare the color change produced by tray-delivered carbamide peroxide [CP] versus hydrogen peroxide products [HP] for at-home bleaching through a systematic review and meta-analysis. MEDLINE via PubMeb, Scopus, Web of Science, Latin American and Caribbean Health Sciences Literature database (LILACS), Brazilian Library in Dentistry (BBO), and Cochrane Library and Grey literature were searched without restrictions. The abstracts of the International Association for Dental Research (IADR) and unpublished and ongoing trial registries were also searched. Dissertations and theses were explored using the ProQuest Dissertations and Periodicos Capes Theses databases. We included randomized clinical trials that compared tray-delivered CP versus HP for at-home dental bleaching. The color change in shade guide units (SGU) and ΔE were the primary outcomes, and tooth sensitivity and gingival irritation were the secondary outcomes. The risk of bias tool of the Cochrane Collaboration was used for quality assessment. After duplicate removal, 1379 articles were identified. However, only eight studies were considered to be at "low" risk of bias in the key domains of the risk bias tool and they were included in the analysis. For ΔE, the standardized mean difference was -0.45 (95 % CI -0.69 to -0.21), which favored tray-delivered CP products (p whitening efficacy than HP-based products in terms of ΔE, but they were similar in terms of ΔSGU. Both whitening systems demonstrated equal level of gingival irritation and tooth sensitivity. Tray-delivered CP gels have a slightly better whitening efficacy than HP-based products in terms of ΔE. This should be interpreted with caution as the data of ΔSGU did not show statistical difference between the products.

  13. Pressure dynamics in the trays caused by differences of the various impression materials and thickness of the relief in the maxillary edentulous model.

    Science.gov (United States)

    Iwasaki, Masatoshi; Kawara, Misao; Inoue, Sayumi; Komiyama, Osamu; Iida, Takashi; Asano, Takashi

    2016-04-01

    The purpose of this study is to compare the pressure dynamics in the trays caused by differences in the various impression materials and in the thickness of the relief provided for the trays. In this study, two types of polyvinylsiloxane elastomers, one type of polyether elastomer and one type of alginate impression material were used. Pressure sensors were embedded at eight locations in a model of an edentulous maxilla, and used a simulation model covered with a pseudomucosa. For each impression material, the measurement was performed five times for each of the three types of trays, and the mean values were determined. Statistical analysis was carried out using one-way analysis of variance and the Tukey's HDS method, and the various pressure sensor values for each of the impression materials were compared 10s and 20s after the start of the measurement. Additionally, we compared differences among the three types of trays after 20s. The pressure values for sensors placed in the relief region tended to become uniform. Furthermore, we saw a tendency for the pressure to increase at the alveolar crests of the first molars on the left and right and at the posterior border of the palate, all of which support the denture, when relief was provided. The above results suggest that making the final impression for the denture using the selective pressure technique, with consideration given to the pressure dynamic, may lead to a good outcome in terms of preservation of the alveolar ridge. Copyright © 2015 Japan Prosthodontic Society. Published by Elsevier Ltd. All rights reserved.

  14. Status of the segment interconnect, cable segment ancillary logic, and the cable segment hybrid driver projects

    International Nuclear Information System (INIS)

    Swoboda, C.; Barsotti, E.; Chappa, S.; Downing, R.; Goeransson, G.; Lensy, D.; Moore, G.; Rotolo, C.; Urish, J.

    1985-01-01

    The FASTBUS Segment Interconnect (SI) provides a communication path between two otherwise independent, asynchronous bus segments. In particular, the Segment Interconnect links a backplane crate segment to a cable segment. All standard FASTBUS address and data transactions can be passed through the SI or any number of SIs and segments in a path. Thus systems of arbitrary connection complexity can be formed, allowing simultaneous independent processing, yet still permitting devices associated with one segment to be accessed from others. The model S1 Segment Interconnect and the Cable Segment Ancillary Logic covered in this report comply with all the mandatory features stated in the FASTBUS specification document DOE/ER-0189. A block diagram of the SI is shown

  15. An applicable method for efficiency estimation of operating tray distillation columns and its comparison with the methods utilized in HYSYS and Aspen Plus

    Science.gov (United States)

    Sadeghifar, Hamidreza

    2015-10-01

    Developing general methods that rely on column data for the efficiency estimation of operating (existing) distillation columns has been overlooked in the literature. Most of the available methods are based on empirical mass transfer and hydraulic relations correlated to laboratory data. Therefore, these methods may not be sufficiently accurate when applied to industrial columns. In this paper, an applicable and accurate method was developed for the efficiency estimation of distillation columns filled with trays. This method can calculate efficiency as well as mass and heat transfer coefficients without using any empirical mass transfer or hydraulic correlations and without the need to estimate operational or hydraulic parameters of the column. E.g., the method does not need to estimate tray interfacial area, which can be its most important advantage over all the available methods. The method can be used for the efficiency prediction of any trays in distillation columns. For the efficiency calculation, the method employs the column data and uses the true rates of the mass and heat transfers occurring inside the operating column. It is highly emphasized that estimating efficiency of an operating column has to be distinguished from that of a column being designed.

  16. An Assembly Line Balancing Problem Automotive Cables

    Directory of Open Access Journals (Sweden)

    Triki Hager

    2015-02-01

    Full Text Available In this paper, an Assembly Line Balancing Problem (ALBP is presented in a real-world automotive cables manufacturer company. This company found it necessary to balance its line, since it needs to increase the production rate. In this ALBP, the number of stations is known and the objective is to minimize cycle time where both precedence and zoning constrains must be satisfied. This problem is formulated as a binary linear program (BLP. Since this problem is NP-hard, an innovative Genetic Algorithm (GA is implemented. The full factorial design is used to obtain the better combination GA parameters and a simple convergence experimental study is performed on the stopping criteria to reduce computational time. Comparison of the proposed GA results with CPLEX software shows that, in a reasonable time, the GA generates consistent solutions that are very close to their optimal ones. Therefore, the proposed GA approach is very effective and competitive.

  17. Hall probe magnetometer for SSC magnet cables

    International Nuclear Information System (INIS)

    Cross, R.W.; Goldfarb, R.B.

    1991-01-01

    The authors of this paper constructed a Hall probe magnetometer to measure the magnetization hysteresis loops of Superconducting Super Collider magnet cables. The instrument uses two Hall-effect field sensors to measure the applied field H and the magnetic induction B. Magnetization M is calculated from the difference of the two quantities. The Hall probes are centered coaxially in the bore of a superconducting solenoid with the B probe against the sample's broad surface. An alternative probe arrangement, in which M is measured directly, aligns the sample probe parallel to the field. The authors measured M as a function of H and field cycle rate both with and without a dc transport current. Flux creep as a function of current was measured from the dependence of ac loss on the cycling rate and from the decay of magnetization with time. Transport currents up to 20% of the critical current have minimal effect on magnetization and flux creep

  18. Temperature rise of cyclicly loaded power cables

    Energy Technology Data Exchange (ETDEWEB)

    Brakelmann, H

    1984-09-01

    A calculation method for the current ratings of cyclicly loaded power cables is introduced, taking into account optional shapes of the load cycle as well as the drying-out of the soil. The method is based on the Fourier-analysis of the loss cycle, representing an extension of the calculation method of VDE 0298. It is shown, that the ''VDE-method'' gives good results for the thermal resistances, if an ''utility load cycle'' in accordance with VDE 0298 is supposed. Only for cycles deviating essentially from the utility load cycle, the thermal resistances calculated by the ''VDE-method'' may be too great. In these cases the represented method is advantageous and can be processed by the aid of microcomputers.

  19. Local Distribution Fiber Optic Cable Communication System.

    Science.gov (United States)

    1981-03-20

    T 1 0 1 72 2304 T 1 0 0 36 1152 T 0 1 1 18 576 T 0 1 0 9 288 T 0 0 1 128 4096 S 1 1 0 64 2048 S 1 0 1 48 1536 S 1 0 0 32 1024 S 0 1 1 16 512 S 0 1 0a...channels. For 32 kb/s channels, the trunk transmission rates are 256, 288, 512, 576, 1024, 1152, 1536, 2048 , and 2304 kb/s. The DGM functions as...connectors will remain mated, even under transport conditions. In the MP shelter, power cables are drawn from the VDI /CAP nest. Extra flexible hook-up

  20. Design and Trajectory Analysis of Incompletely Restrained Cable-Suspension Swing System Driven by Two Cables

    Directory of Open Access Journals (Sweden)

    Naige Wang

    2015-12-01

    Full Text Available In order to simulate the swing conditions of a suspended platform of a construction shaft, marine ships, cars, etc., an incompletely restrained cable-suspension swing system driven by two cables (IRCSWs2 was designed and parameter trajectories of displacements, angles and tensions were systematically investigated. Firstly, the motion mechanism of the IRCSWs2 is described and the corresponding kinematic model is established. For further evaluating the analytical expressions, the ADAMS simulation model and the physical prototype experimental model were developed. The basic consistency and slight difference among the three models are illustrated by a comparison of different parameters. The approximately linear relationship between the driving displacements of two cables and the swing angles of the platform was obtained. Finally, the effects of various parameters on displacements, angles and tensions were analysed, and the results indicate that the translation of a suspended platform is slight during its swing and that the novel IRCSWs2 can be used to drive heavy loads using a relatively small driving force, which is useful for simulating swing environmental conditions long-term, in addition to being cost-effective.

  1. Solid-cryogen-stabilized, cable-in-conduit (CIC) superconducting cables

    Science.gov (United States)

    Voccio, J. P.; Michael, P. C.; Bromberg, L.; Hahn, S.

    2015-12-01

    This paper considers the use of a solid cryogen as a means to stabilize, both mechanically and thermally, magnesium diboride (MgB2) superconducting strands within a dual-channel cable-in-conduit (CIC) cable for use in AC applications, such as a generator stator winding. The cable consists of two separate channels; the outer channel contains the superconducting strands and is filled with a fluid (liquid or gas) that becomes solid at the device operating temperature. Several options for fluid will be presented, such as liquid nitrogen, hydrocarbons and other chlorofluorocarbons (CFCs) that have a range of melting temperatures and volumetric expansions (from solid at operating temperature to fixed volume at room temperature). Implications for quench protection and conductor stability, enhanced through direct contact with the solid cryogen, which has high heat capacity and thermal conductivity (compared with helium gas), will be presented. Depending on the cryogen, the conductor will be filled initially either with liquid at atmospheric conditions or a gas at high pressure (∼100 atm). After cooldown, the cryogen in the stranded-channel will be solid, essentially locking the strands in place, preventing strand motion and degradation due to mechanical deformation while providing enhanced thermal capacity for stability and protection. The effect of cryogen porosity is also considered. The relatively high heat capacity of solid cryogens at these lower temperatures (compared to gaseous helium) enhances the thermal stability of the winding. During operation, coolant flow through the open inner channel will minimize pressure drop.

  2. MR damping system on Dongting Lake cable-stayed bridge

    Science.gov (United States)

    Chen, Z. Q.; Wang, X. Y.; Ko, J. M.; Ni, Y. Q.; Spencer, Billie F., Jr.; Yang, G.

    2003-08-01

    The Dongting Lake Bridge is a cable-stayed bridge crossing the Dongting Lake where it meets the Yangtze River in southern central China. After this bridge was completed in 1999, its cables were observed to be sensitive to rain-wind-induced vibration, especially under adverse weather conditions of both rain and wind. To investigate the possibility of using MR damping systems to reduce cable vibration, a joint project between the Central South University of China and the Hong Kong Polytechnic University was conducted. Based on the promising research results, the bridge authority decided to install MR damping systems on the longest 156 stay cables. The installation started in July 2001 and finished in June 2002, making it the world's first application of MR dampers on cable-stayed bridge to suppress the rain-wind-induced cable vibration. As a visible and permanent aspect of bridge, the MR damping system must be aesthetically pleasing, reliable, durable, easy to maintain, as well as effective in vibration mitigation. Substantial work was done to meet these requirements. This paper describes the implementation of MR damping systems for cable vibration reduction.

  3. Thin film conductors for self-equalizing cables

    Science.gov (United States)

    Owen, G.; Trutna, W. R.; Orsley, T. J.; Lucia, F.; Daly, C. B.

    2017-10-01

    Self-equalizing cables using hollow conductors with wall thickness less than the skin depth were proposed in 1929. However, they do not appear ever to have been widely used, although the idea has resurfaced and been refined from time to time. In the early 2000's, self-equalizing conductors consisting of solid magnetic steel cores coated with silver were developed by W.L. Gore, and used in their 2.5 Gb/s "Eye-Opener" cables, although higher speed versions never appeared. We have revived the original 1929 idea, proposing to use glass as a solid insulating core. This technology can potentially work at frequencies of many 10's of GHz. Possible uses include short range GHz links such as USB and Thunderbolt, and intra-rack interconnections in data centers. Our feasibility experiments have validated the principle. Copper coated glass fibers can, in principle, be manufactured, but in these tests, the conductors were capillaries internally coated with silver as these are easily obtainable, relatively inexpensive and serve to test the concept. The performance of these experimental twin lead cables corresponds to calculations, confirming the general principle. By calculation, we have compared the performance of cables made from copper-on-insulator conductors to that of similar cables made with solid copper conductors, and verified that copper-on-insulator cables have significantly less frequency dependent loss. We have also made and tested cables with copper on PEEK conductors as surrogates for copper on glass fiber.

  4. Versatile cable handling mechanisms for remote operator control

    Energy Technology Data Exchange (ETDEWEB)

    Collie, A.A.; White, T.S.; Christopher, M.D.; Hewer, N.D. [Portech Ltd., Portsmouth (United Kingdom)

    1996-12-31

    This paper describes a system of cable management for keeping the umbilical cables of remote operating vehicles and manipulators tidy and contained without direct intervention by operators. Two distinct types of winding mechanism have been designed. One mechanism is a fixed reel type where the cable is wound onto the reel by a rotating bail arm. The other mechanism consists of a pair of curved belts held against each other between which cable is passed. The complete system includes tension measuring and slack loop take-up devices. The whole system is controlled by a servo system in conjunction with a PC based visual graphic environment which allows a variety of mechanisms to be built up into a system able to handle up to four umbilical cables simultaneously. The control system provides additional tension sensors and cable odometers connected to the control system so that the operator has immediate perception of all the cable parameters, and by defining rules, can set up a variety of alarm situations. (Author).

  5. Versatile cable handling mechanisms for remote operator control

    International Nuclear Information System (INIS)

    Collie, A.A.; White, T.S.; Christopher, M.D.; Hewer, N.D.

    1996-01-01

    This paper describes a system of cable management for keeping the umbilical cables of remote operating vehicles and manipulators tidy and contained without direct intervention by operators. Two distinct types of winding mechanism have been designed. One mechanism is a fixed reel type where the cable is wound onto the reel by a rotating bail arm. The other mechanism consists of a pair of curved belts held against each other between which cable is passed. The complete system includes tension measuring and slack loop take-up devices. The whole system is controlled by a servo system in conjunction with a PC based visual graphic environment which allows a variety of mechanisms to be built up into a system able to handle up to four umbilical cables simultaneously. The control system provides additional tension sensors and cable odometers connected to the control system so that the operator has immediate perception of all the cable parameters, and by defining rules, can set up a variety of alarm situations. (Author)

  6. Versatile cable handling mechanisms for remote operator control

    International Nuclear Information System (INIS)

    Collie, A.A.; White, T.S.; Christopher, M.D.; Hewer, N.D.

    1996-01-01

    This paper describes a system of cable management for keeping the umbilical cables of remote operating vehicles and manipulators tidy and contained without direct intervention by operators. Two distinct types of winding mechanism have been designed. One mechanism is a fixed reel type where the cable is wound onto the reel by a rotating bail arm. The other mechanism consists of a pair of curved belts held against each other, between which cable is passed. The complete system includes tension measuring and slack loop take-up devices. The whole system is controlled by a servo system in conjunction with a PC based visual graphic environment which allows a variety of mechanisms to be built up into a system able to handle up to four umbilical cables simultaneously. The control system provides additional tension sensors and cable odometers connected to the control system so that the operator has immediate perception of all the cable parameters, and by defining rules, can set up a variety of alarm situations. (UK)

  7. Longest cable-stayed bridge TATARA; Longest shachokyo Tatara Ohashi

    Energy Technology Data Exchange (ETDEWEB)

    Fujii, K. [Hiroshima University, Hiroshima (Japan). Faculty of Engineering

    1998-06-15

    The world`s longest cable-stayed bridge Tatara having a central span of 890 m had the both ends closed in August 1997, linking Namakuchi Island and Omishima Island. Final finishing work is continuing for opening of the West Seto Expressway in the spring of 1999. A cable-stayed bridge supports the bridge girders by perpendicular components of tensile force of cables stayed obliquely. On the other hand, there is a concern that the girders may have axial compression force generated due to horizontal components of the force from the cable tensile force, which can cause buckling of the girders. Therefore, in order to suspend the girders efficiently by increasing the perpendicular components of the cable force, and moreover to suppress the axial compression force on the girders, it is more advantageous to make bridge towers high, hence the towers of this bridge are highest among the bridges on the Shimanami Ocean Road. This bridge whose long girders are stayed with 21-stage multi cables presented a problem in designing the buckling in steel girders near the towers due to the horizontal components of the force generated by the bridge. Discussions were given, therefore, by using load withstanding force experiments using a whole bridge model of 1/50 scale, buckling experiments on full-size reinforcing plate models, and load withstanding force analysis using a tower model. A number of other technical discussions were repeated, by which the world`s longest cable-stayed bridge was completed. 9 figs., 1 tab.

  8. Improving greater trochanteric reattachment with a novel cable plate system.

    Science.gov (United States)

    Baril, Yannick; Bourgeois, Yan; Brailovski, Vladimir; Duke, Kajsa; Laflamme, G Yves; Petit, Yvan

    2013-03-01

    Cable-grip systems are commonly used for greater trochanteric reattachment because they have provided the best fixation performance to date, even though they have a rather high complication rate. A novel reattachment system is proposed with the aim of improving fixation stability. It consists of a Y-shaped fixation plate combined with locking screws and superelastic cables to reduce cable loosening and limit greater trochanter movement. The novel system is compared with a commercially available reattachment system in terms of greater trochanter movement and cable tensions under different greater trochanteric abductor application angles. A factorial design of experiments was used including four independent variables: plate system, cable type, abductor application angle, and femur model. The test procedure included 50 cycles of simultaneous application of an abductor force on the greater trochanter and a hip force on the femoral head. The novel plate reduces the movements of a greater trochanter fragment within a single loading cycle up to 26%. Permanent degradation of the fixation (accumulated movement based on 50-cycle testing) is reduced up to 46%. The use of superelastic cables reduces tension loosening up to 24%. However this last improvement did not result in a significant reduction of the grater trochanter movement. The novel plate and cables present advantages over the commercially available greater trochanter reattachment system. The plate reduces movements generated by the hip abductor. The superelastic cables reduce cable loosening during cycling. Both of these positive effects could decrease the risks related to grater trochanter non-union. Copyright © 2012 IPEM. Published by Elsevier Ltd. All rights reserved.

  9. Current distribution in Cable-In-Conduit Conductors

    International Nuclear Information System (INIS)

    Ferri, M.A.

    1994-05-01

    A numerical study of the current distribution in Cable-In-Conduit Conductors (CICC's) experiencing linearly ramping transport currents and transverse magnetic fields was conducted for both infinitely long, periodic cables and finite length cables terminated in low resistance joints. The goal of the study was to gain insight into the phenomenon known as Ramp Rate Limitation, an as yet unexplained correspondence between maximum attainable current and the ramp time taken to reach that current in CICC superconducting magnets. A discrete geometric model of a 27 strand multiply twisted CICC was developed to effectively represent the flux linkages, mutual inductances, and resistive contact points between the strands of an experimentally tested cable. The results of the numerical study showed that for fully periodic cables, the current imbalances due to ramping magnetic fields and ramping transport currents are negligible in the range of experimentally explored operating conditions. For finite length, joint terminated cables, however, significant imbalances can exist. Unfortunately, quantitative results are limited by a lack of knowledge of the transverse resistance between strands in the joints. Nonetheless, general results are presented showing the dependency of the imbalance on cable length, ramp time, and joint resistance for both ramping transverse magnet fields and ramping transport currents. At the conclusion of the study, it is suggested that calculated current imbalances in a finite length cable could cause certain strands to prematurely ''quench'' -- become non-superconducting --thus leading to an instability for the entire cable. This numerically predicted ''current imbalance instability'' is compared to the experimentally observed Ramp Rate Limitation for the 27 strand CICC sample

  10. Rotator cuff tendon connections with the rotator cable.

    Science.gov (United States)

    Rahu, Madis; Kolts, Ivo; Põldoja, Elle; Kask, Kristo

    2017-07-01

    The literature currently contains no descriptions of the rotator cuff tendons, which also describes in relation to the presence and characteristics of the rotator cable (anatomically known as the ligamentum semicirculare humeri). The aim of the current study was to elucidate the detailed anatomy of the rotator cuff tendons in association with the rotator cable. Anatomic dissection was performed on 21 fresh-frozen shoulder specimens with an average age of 68 years. The rotator cuff tendons were dissected from each other and from the glenohumeral joint capsule, and the superior glenohumeral, coracohumeral, coracoglenoidal and semicircular (rotator cable) ligaments were dissected. Dissection was performed layer by layer and from the bursal side to the joint. All ligaments and tendons were dissected in fine detail. The rotator cable was found in all specimens. It was tightly connected to the supraspinatus (SSP) tendon, which was partly covered by the infraspinatus (ISP) tendon. The posterior insertion area of the rotator cable was located in the region between the middle and inferior facets of the greater tubercle of the humerus insertion areas for the teres minor (TM), and ISP tendons were also present and fibres from the SSP extended through the rotator cable to those areas. The connection between the rotator cable and rotator cuff tendons is tight and confirms the suspension bridge theory for rotator cuff tears in most areas between the SSP tendons and rotator cable. In its posterior insertion area, the rotator cable is a connecting structure between the TM, ISP and SSP tendons. These findings might explain why some patients with relatively large rotator cuff tears can maintain seamless shoulder function.

  11. Aerodynamic instability of cables in transmission power lines; Inestabilidad aerodinamica en cables de lineas de transmision

    Energy Technology Data Exchange (ETDEWEB)

    Lopez Lopez, Alberto; Vilar Rojas, Jorge Ivan; Munoz Black, Celso J. [Instituto de Investigaciones Electricas, Cuernavaca (Mexico)

    1995-12-31

    One of the aerodynamic instabilities of transmission power lines cables is galloping, which consists in the appearance of important cable vibrations, mainly when the wind hits orthogonally the power line. In some cases the maximum amplitude that occurs reaches several meters, even when the wind velocities in a region are well below the value used for the mechanical design of the power lines. In general terms, galloping is associated with particular climatic conditions such as low temperatures and high humidities. In these conditions a coating of ice that adheres to the cable is formed, changing its transverse cross section, propitiating the galloping, although some authors have reported galloping without ice. These climatic conditions are presented mainly in the Northern part of our country and in the high regions of the mountain zones; nevertheless, the galloping phenomenon has been reported in few cases by Comision Federal de Electricidad (CFE). The possible expansion of the power lines in these regions of the country leads to prevent the measures needed to diminish the appearance of this phenomenon. In this paper mention is made in particular of the solution adopted to the galloping problem that has appeared in the transmission power line of Salamayuca to Reforma, Ciudad Juarez, Chihuahua (CFE,1991). [Espanol] Una de las inestabilidades aerodinamicas que se presentan en los cables de lineas de transmision es el galopeo, el cual consiste en la aparicion de vibraciones importantes de los cables, sobre todo cuando el flujo del viento incide ortogonalmente a la linea. En algunos casos las amplitudes maximas que se presentan llegan a ser de varios metros, aun cuando las velocidades del viento en una region esten muy por debajo del valor empleado para el diseno mecanico de las lineas. Generalmente, el galopeo se asocia con condiciones climaticas particulares como son las bajas temperaturas y altas humedades. En estas condiciones se forma una cubierta de hielo que se

  12. Aerodynamic instability of cables in transmission power lines; Inestabilidad aerodinamica en cables de lineas de transmision

    Energy Technology Data Exchange (ETDEWEB)

    Lopez Lopez, Alberto; Vilar Rojas, Jorge Ivan; Munoz Black, Celso J [Instituto de Investigaciones Electricas, Cuernavaca (Mexico)

    1996-12-31

    One of the aerodynamic instabilities of transmission power lines cables is galloping, which consists in the appearance of important cable vibrations, mainly when the wind hits orthogonally the power line. In some cases the maximum amplitude that occurs reaches several meters, even when the wind velocities in a region are well below the value used for the mechanical design of the power lines. In general terms, galloping is associated with particular climatic conditions such as low temperatures and high humidities. In these conditions a coating of ice that adheres to the cable is formed, changing its transverse cross section, propitiating the galloping, although some authors have reported galloping without ice. These climatic conditions are presented mainly in the Northern part of our country and in the high regions of the mountain zones; nevertheless, the galloping phenomenon has been reported in few cases by Comision Federal de Electricidad (CFE). The possible expansion of the power lines in these regions of the country leads to prevent the measures needed to diminish the appearance of this phenomenon. In this paper mention is made in particular of the solution adopted to the galloping problem that has appeared in the transmission power line of Salamayuca to Reforma, Ciudad Juarez, Chihuahua (CFE,1991). [Espanol] Una de las inestabilidades aerodinamicas que se presentan en los cables de lineas de transmision es el galopeo, el cual consiste en la aparicion de vibraciones importantes de los cables, sobre todo cuando el flujo del viento incide ortogonalmente a la linea. En algunos casos las amplitudes maximas que se presentan llegan a ser de varios metros, aun cuando las velocidades del viento en una region esten muy por debajo del valor empleado para el diseno mecanico de las lineas. Generalmente, el galopeo se asocia con condiciones climaticas particulares como son las bajas temperaturas y altas humedades. En estas condiciones se forma una cubierta de hielo que se

  13. Effects of Various Factors on the Viv-Induced Fatigue Damage In The Cable Of Submerged Floating Tunnel

    Directory of Open Access Journals (Sweden)

    Luoa Gang

    2015-12-01

    Full Text Available According to the modal superposition method, the vortex vibration procedure of submerged floating tunnel cable was compiled using Matlab, based on the calculated results, the fatigue damage was predicted. The effects of various factors, such as cable density, cable length, and pretension and velocity distribution on vortex induced fatigue damage in the cable were studied. The results show that velocity distribution has more effect on the cable fatigue damage than cable length, cable density and pre-tension. Secondly, cable length has also relatively effect on the cable damage fatigue, cable density and pretension has limited in a certain range.

  14. Experimental Investigation of Aerodynamic Instability of Iced Bridge Cable Sections

    DEFF Research Database (Denmark)

    Koss, Holger; Lund, Mia Schou Møller

    2013-01-01

    The accretion of ice on structural bridge cables changes the aerodynamic conditions of the surface and influences hence the acting wind load process. Full-scale monitoring indicates that light precipitation at moderate low temperatures between zero and -5°C may lead to large amplitude vibrations...... of bridge cables under wind action. This paper describes the experimental simulation of ice accretion on a real bridge cable sheet HDPE tube segment (diameter 160mm) and its effect on the aerodynamic load. Furthermore, aerodynamic instability will be estimated with quasi-steady theory using the determined...

  15. Cable fire risk of a nuclear power plant

    International Nuclear Information System (INIS)

    Aulamo, H.

    1998-02-01

    The aim of the study is to carry out a comprehensive review of cable fire risk issues of nuclear power plants (NPP) taking into account latest fire and risk assessment research results. A special emphasis is put on considering the fire risk analysis of cable rooms in the framework of TVO Olkiluoto NPP probabilistic safety assessment. The assumptions made in the analysis are assessed. The literature study section considers significant fire events at nuclear power plants, the most severe of which have nearly led to a reactor core damage (Browns Ferry, Greifswald, Armenia, Belojarsk, Narora). Cable fire research results are also examined

  16. Arc tracking energy balance for copper and aluminum aeronautic cables

    International Nuclear Information System (INIS)

    André, T; Valensi, F; Teulet, P; Cressault, Y; Zink, T; Caussé, R

    2017-01-01

    Arc tracking tests have been carried out between two voluntarily damaged aeronautic cables. Copper or aluminum conductors have been exposed to short circuits under alternating current. Various data have been recorded (arc voltage and current, radiated power and ablated mass), enabling to determine a power balance, in which every contribution is estimated. The total power is mainly transferred to the cables (between 50 and 65%, depending on the current and the cable type), and causes the melting and partial vaporization of the metallic core and insulating material, or is conducted or radiated. The other part is deposited into the arc column, being either radiated, convected or conducted. (paper)

  17. Effects of ice accretion on the aerodynamics of bridge cables

    DEFF Research Database (Denmark)

    Demartino, C.; Koss, Holger; Georgakis, Christos T.

    2015-01-01

    and stay cables. The aim of this paper is twofold; first, it was investigated the ice accretion process and the final shape of the ice accreted; then the aerodynamics of the ice accreted bridge cables was characterized, and related to the ice shape. Different climatic conditions, i.e. combinations...... of temperature, wind speed and yaw angle of accretion, were reproduced in a climatic wind tunnel, giving rise to different types of accretion. These were chosen such to generate the most common natural ice formations expected to produce bridge cable vibrations. A description of the geometric characteristics...

  18. Cable handling system for use in a nuclear reactor

    International Nuclear Information System (INIS)

    Crosgrove, R.O.; Larson, E.M.; Moody, E.

    1982-01-01

    A cable handling system for use in an installation such as a nuclear reactor is disclosed herein along with relevant portions of the reactor which, in a preferred embodiment, is a liquid metal fast breeder reactor. The cable handling system provides a specific way of interconnecting certain internal reactor components with certain external components, through an assembly of rotatable plugs. Moreover, this is done without having to disconnect these components from one another during rotation of the plugs and yet without interfering with other reactor components in the vicinity of the rotating plugs and cable handling system

  19. Superconducting Cable Development for Future High Energy Physics Detector Magnets

    Science.gov (United States)

    Horvath, I. L.

    1995-11-01

    Under the leadership of the Swiss Federal Institute of Technology (ETHZ) an international ad hoc collaboration for superconducting cables developed an aluminium stabilised superconducting cable for future detector magnets. With the financial support of the Swiss government, this R&D work was carried out for the European Organisation for Nuclear Research (CERN). In this report the manufacturing process is described and results of the quality control measurements are summarised. These tests showed that the industrial manufacturing of an aluminium stabilised superconducting cable is feasible.

  20. Conventional cable testing methods: strengths, weaknesses and possibilities

    International Nuclear Information System (INIS)

    Reynolds, P.H.

    1988-01-01

    The paper reviews the major conventional methods that can be used to test power plant cables. It assesses their usefulness in diagnosing the condition of the insulation of the cable and then proposes some possible directions for innovation. The methods examined are dc insulation resistance measurement, ac signal injection for continuous monitoring and fault location, and the ac measurement of capacitance and loss angle. Specific subjects considered are the effects of temperature, cable construction and installation, and the validity of insulation resistance or loss angle measurement. The innovative proposals refer to the use of automation in the measurement and of computer-based Expert Systems for the evaluation of the results