In recent years, there has been increasing demand for resource-recycling of waste plastic, especially due to the introduction of legislation on recycling of materials used for packages of household goods. Methods of recycling waste plastic from household goods are currently still under development, and appropriate techniques to deal with such waste are required. Toshiba has developed a technique to dehydrochlorinate plastic containing polyvinyl chloride (PVC). This paper introduces our petrolization and dehydrochlorination system for waste plastic containing PVC. (author)
Activated charcoal which is the desulfurizing agent for the fuel cell plant can be used only at the normal temperature, and it must be placed upstream of the fuel gas, increasing the displacement flow of the fuel gas processed in the desulfurizer. In addition, a large quantity of activated charcoal must be filled or the frequency of its exchange must be increased because activated charcoal used at the normal temperature has little sulfur absorbing capacity. This invention is concerned with provision of a desulfurizer in the downstream of the fuel gas compressor of the fuel cell plant to remove sulfur content in the fuel gas by this desulfurizer. As a result, the displacement flow of the processing gas is decreased to increase the processing capacity of the desulfurizing agent. In addition, hydrogen recycling can be eliminated to realize compact arrangement of the equipment and economization of energy consumption. Metal oxide based desulfurizers of copper, iron, zinc, manganese, etc. ...
The demonstration test of a power system stabilizer, employing a fuzzy theory, in the two hydroelectric power stations of Kyusyu Electric Power Co., Inc. is described. The PSS inputs auxiliary signals to the automatic voltage regulator (AVR) of a generator and generates an electric torque in the direction opposite to the operating direction of a generator to enhance the damping effect and improve the system stability. Usually, the change in the slide information of a generator is detected, and the phase adjustment is performed so that the damping is the optimum value. However, since the damping is optimized in the specific system state, no complete damping may be obtained when the system state is changed. A fuzzy theory was thus applied for the control operation part. In a secondary fuzzy PSS, the velocity and acceleration were calculated from the slide information of a generator to produce a control signal. In the third dimension, moreover, the position (integral information of ...
Four HVDC (high voltage DC) {+-} 250kV submarine OF (oil-filled) cables are to be installed each capable of 1.4-million kW for one dipole channel and two returns for forwarding to Yura Switchyard a part of the power to be generated by a Tachibanawan coal-fired power plant to open in 2000. The first cable is now being laid. They are to cover a distance of 48km on the sea bottom, and their 190mm diameter is the largest in the world and this decreases the required number of cables for a reduction in the construction cost. The installation is executed by use of a dedicated cable laying ship loaded with cables. The ship is equipped with five thruster screws by adjusting which a cable is fed into the sea and laid on the bottom with high positional accuracy in all directions, and with a 10m-accurate DPS (Dynamic Positioning System) besides GPS (Global Positioning System). Operating on the sea bottom is a simultaneous laying/burying machine which buries the cable 2-3m deep in the sea bottom. ...