WorldWideScience
1

Dynamics of HVDC system under unbalanced AC transmission line faults and its stabilization. Koryukei fuheiko kosho ni taisuru chokuryu keito no odo tokusei to anteika seigyo  

Energy Technology Data Exchange (ETDEWEB)

The application of HVDC system to the trunk power supply system requires the transmission of DC power as much as possible to improve the stability of the whole AC/DC system. To meet this requirement, continued pulse system, which keeps sending a DC current even when an AC voltage lowers remarkably, has been used. The stability is much more improved by adding damping control which modulates converter active and/or reactive power. In order to make full use of such control effects, it is important that the HVDC system maintains stable operation during faults and reclosing of the AC system. In particular, it is necessary to prevent a repetitive commutation failure following the unbalanced AC transmission line faults. In this paper, the cause of the repetitive commutation failure is discussed by using the ...

1992-01-20

2

Peculiarities of operation modes of 1200 kV AC long-distance transmission lines and some results of field tests thereon  

Energy Technology Data Exchange (ETDEWEB)

Since 1985 the operating sections of the 1200 kV AC Ekibastuz-Urals transmission system were used for a variety of field studies on a wide range of technological problems associated to high voltage transmission lines. The tests performed confirmed correctness of the main engineering and design decision made at development stage and demonstrated that such transmission lines are reliable and efficient. 3 figs.

1989-12-31

3

Conawapa to Winnipeg Power Transmission Complex. Southern Receiver System: Environmental impact assessment status report  

International Nuclear Information System (INIS)

Development of the Conawapa-Winnipeg power transmission complex in Manitoba includes five interrelated transmission and conversion facilities. Environmental and socio-economic assessment work done to date on one component of this system (the upgrading of the Southern Receiver System) is described. This system is composed of a network of high voltage transmission lines and station facilities serving power demand in Winnipeg and southern Manitoba. The upgrading involves three main elements: energizing a second 230 kV ac circuit on an existing tower line running from the proposed Riel Station site to the existing St. Vital Station; constructing a new double-circuit 230 kV tower line on the same existing right-of-way between St. Vital and the Riel site area; and installing an additional transformer and other necessary equipment at St. Vital and other stations ...

1992-01-01

4

Analysis of algorithms for ultra high speed relays for the protection of high voltage transmission lines  

Energy Technology Data Exchange (ETDEWEB)

The object of this research is the evaluation of the performance of ultra high speed relays (UHSR's) used for protection of a-c transmission lines. For purposes of this report, these are relays whose response time is less than a quarter of a cycle of the 60 Hz wave (i.e. 4.167 ms.). To identify relaying schemes that may comply with this definition, a literature survey was undertaken. The selected relays were studied in detail and modeled on a digital computer. A theoretical description of these relays is presented. Records of real transient data as well as of simulated data were used as input to the digital models of relays. The real data were recorded by means of monitoring stations connected to the Florida Power and Light Company transmission lines. The simulated data were obtained by modeling the relevant parts of the utility's transmission system using a ...

1984-01-01

5

De-icing technologies: Introduction to Manitoba Hydro's use of ice melting and ice rolling technologies to remove ice from subtransmission and 115 kV transmission lines  

International Nuclear Information System (INIS)

Manitoba Hydro's Ice Storm Management Program to reduce ice damage to overhead power lines in the voltage range of 8 kV to 115 kV is described. Overhead power lines are de-iced either by AC ice melting, which involves placing a three-phase short at a calculated point, or ice rolling, which is a process of mechanically stripping ice from conductors. Direct current heating and underground distribution systems are also accepted prevention measures. Advantages and disadvantages of each of these methods of de-icing are reviewed. Material for this paper has been extracted from a workshop manual prepared for the 1993 and 1998 Ice Storm Management workshops organized by Manitoba Hydro through the Canadian Electrical Association. 1 ref.

1999-03-29

7

US Air Force Aircraft in Southeast Asia Tested by the Air Force ...  

Science.gov (United States)

... feet in length, and 26 feet 2 inches high. The AC-119G and AC-119K, are powered with two General Electric J85-17 jet engines pod-mounted ...

1970-03-01

8

Photovoltaic Technologies Beyond the Horizon: Optical Rectenna Solar Cell, Final Report, 1 August 2001-30 September 2002  

Energy Technology Data Exchange (ETDEWEB)

ITN Energy Systems is developing next-generation solar cells based on the concepts of an optical rectenna. ITN's optical rectenna consists of two key elements: (1) an optical antenna to efficiently absorb the incident solar radiation, and (2) a high-frequency metal-insulator-metal (MIM) tunneling diode that rectifies the AC field across the antenna, providing DC power to an external load. The combination of a rectifying diode at the feedpoints of a receiving antenna is often referred to as a rectenna. Rectennas were originally proposed in the 1960s for power transmission by radio waves for remote powering of aircraft for surveillance or communications platforms. Conversion efficiencies greater than 85% have been demonstrated at radio frequencies (efficiency defined as DC power generated divided by RF power incident on the device). ...

2003-02-01

9

Power control for wind turbines in weak grids: Concepts development  

Energy Technology Data Exchange (ETDEWEB)

Presently, high wind potentials in remote areas may not be utilized for electricity production due to limited grid transmission capacity and/or difficulties in matching the electricity production with the demand. The overall project objective is to help overcome these bottlenecks, i.e. to identify and analyze methods and technologies for making it viable to utilize more of the wind potential in remote areas. The suggestion is to develop a power control concept for wind turbines which will even out the power fluctuations and make it possible to increase the wind energy penetration. The main options are to combine wind power with a pumped hydro power storage or with an AC/DC converter and battery storage. The AC/DC converter can either be an `add-on` type or it can be designed as an integrated part of a variable speed wind turbine. The idea is ...

1999-03-01

10

HVDC submarine power cables systems state of the art and future developments  

Energy Technology Data Exchange (ETDEWEB)

The paper begins with an introduction on the reasons that lead to the use of HVDC submarine cable links. The main aspects for the choice of direct current are presented as well as the advantages deriving from the utilization of submarine cables. The second part is dedicated to a discussion on the various type of insulation that could be used in power cables and their possible application to HVDC submarine cables. In the following there is a description of the main characteristics and technical details of some particular project that at present time (1995) are in progress. Two projects are briefly presented: Spain-Morocco, a 26 km long interconnection for the transmission, in a first phase, of 700 MW from Spain to Morocco at 400 kV a.c. by means of three cables, plus one spare, of the fluid filled type. The cables are designed for a future change to d.c. 450 kV, allowing a transmission of 500 MW each ...

1995-12-31

11

Transient overvoltages and overcurrents during line fault tests on the Hokkaido-Honshu HVDC line  

Energy Technology Data Exchange (ETDEWEB)

A series of line fault tests have been conducted at completion of Stage I of the Hokkaido-Honshu HVDC Link of Electric Power Development Co., Ltd., prior to its commercial operation, in order to study transient overvoltages and overcurrents and to confirm safety operation of system protecting devices in case of DC transmission line faults. The Hokkaido-Honshu HVDC Link is a metallic return HVDC overhead line and cable transmission system, currently being a monopolar system. For this, measurements were conducted this time on reverse polarity overvoltages occurring on main line cable, return line overvoltages, fault arc dynamic characteristics, and DC bypass current through the AC system. The results obtained were then compared with the analysis results by the HVDC surge similator or digital simulation conducted for system design prior to the field tests. As a result, a close accordance was found between ...

1982-08-01

12

The combined SOx/NOx/air toxics reduction process using activated coke and flue gas clean up  

Energy Technology Data Exchange (ETDEWEB)

The dry desulfurization, denitrification and air toxics removal process using activated coke (AC) has been commercially adapted for flue gas clean up of a power plant, an oil refinery plant, an iron ore sintering plant, and a refuse incinerator. This process can achieve 100% removal of SO{sub x}, over 80% removal of NO{sub x} and effective removal of air toxics such as Hg, HCL, dioxines, etc., by contacting flue gas with AC and injecting NH{sub 3} for DeNO{sub x} at temperature range of about 100-200{degrees}C. For flue gas treatment, AC has several functions, which basically depends on the chemical surface group on AC inner surface. As adsorbent, AC can adsorb SO{sub x} at the relatively basic oxygen group site, where the adsorbed SO{sub x} is stored as sulfuric acid into micropore structure of AC. As catalyst, AC can ...

1996-10-01

13

Direct energy conversion for IEC fusion for space applications  

Energy Technology Data Exchange (ETDEWEB)

The paper describes a concept of extracting fusion power from D-{sup 3}He fueled IEC (Inertia Electrostatic Configuration) devices. The fusion system consists of a series of fusion modules and direct energy converters at an end or at both ends. This system of multiple units is linear and is connected by a magnetic field. A pair of coils anti-parallel to the magnetic field yields a field-null domain at the center of each unit as required for IEC operation. A stabilizing coil installed between the coil pairs eliminates the strong attractive force between the anti-parallel coils. Accessible regions for charged particle trajectories are essentially isolated from the coil structure. Thus, charged particles are directed along magnetic field lines to the direct energy converter without appreciable losses. A direct energy converter unit designed to be compatible to this unique system is also described. It basically consists of a separator and a traveling wave converter. A ...

2000-08-01

14

Towards quantitative PET/MRI: a review of MR-based attenuation correction techniques  

International Nuclear Information System (INIS)

Positron emission tomography (PET) is a fully quantitative technology for imaging metabolic pathways and dynamic processes in vivo. Attenuation correction of raw PET data is a prerequisite for quantification and is typically based on separate transmission measurements. In PET/CT attenuation correction, however, is performed routinely based on the available CT transmission data. Recently, combined PET/magnetic resonance (MR) has been proposed as a viable alternative to PET/CT. Current concepts of PET/MRI do not include CT-like transmission sources and, therefore, alternative methods of PET attenuation correction must be found. This article reviews existing approaches to MR-based attenuation correction (MR-AC). Most groups have proposed MR-AC algorithms for brain PET studies and more recently also for torso PET/MR imaging. Most MR-AC strategies require the use of ...

2009-03-01

15

PWM applications for the electric railway traction system fed by the AC/DC dual power line  

Energy Technology Data Exchange (ETDEWEB)

The latest electronic circuit technology that can be used for the electric railway traction system fed by an AC/DC dual power line was developed. This system consists of reverse conducting GTO thyristors, microprocessors, and DSP`s. In the AC power supply line section, the line converter is controlled by PWM technology to secure a high power factor and reduce the higher harmonic generation of an input current as far as possible. The line converter and motor converter use reverse conducting GTO thyristors. Since these converters are cooled using a heat pipe cooler, they are reduced in size and weight. The electric grounding point of the main power circuit is set to the negative side of the DC line for AC and DC line sections. Therefore, the AC/DC selector switch was simplified in structure. Moreover, the DC input for the ...

1996-01-01

16

A comparison of methods for calculating audible noise of high voltage transmission lines  

Energy Technology Data Exchange (ETDEWEB)

During the last several years, audible noise produced by high voltage transmission lines in corona has emerged as an important design consideration. In this same time frame a number of different methods for calculating audible noise levels have been proposed. The methods currently available, for both ac and dc lines, are described in this paper and are compared through application to practical line geometries for which data from long-term measurements are available.

1982-10-01

17

Electricity on the rig. Part 3 - New electric rig technology  

Energy Technology Data Exchange (ETDEWEB)

The use of an SCR-controlled power system on an offshore drilling rig has lead to an increased acceptance of high technology equipment. Such equipment increases drilling productivity, reduces maintenance, and improves reliability. Most new rigs now have AC squirrel cage motors, brushless AC generators, silicon controlled rectifiers, DC motors, and swtichgear and motor starters. Several opportunities for cost reductions in SCR systems, such as improving the power factor, are studied in this paper.

1983-07-01

19

Predicting formula development of audible noise on a 765 kV AC transmission line 1  

Energy Technology Data Exchange (ETDEWEB)

Audible noise from corona discharge had been identified as one of the most important factors in the design of conductor configurations for high-voltage transmission lines. 500 kV and above. Therefore this paper describes audible noise characteristics of 6 X 480 mm{sup 2} conductor bundle in KEPRI 765 kV Test Line and Corona Cage. Prediction formula for audible(corona) noise on a 765 kV Transmission Line was developed using this results. (author). 4 refs., 4 figs., 4 tabs.

1996-04-01

20

Development of a New Class of Low Cost, High Frequency Link Direct DC to AC Converters for Solid Oxide Fuel Cells (SOFC)  

Science.gov (United States)

This project proposes to design and develop a new class of power converters (direct DC to AC) to drastically improve performance and optimize the cost, size, weight and volume of the DC to AC converter in SOFC systems. The proposed topologies employ a high frequency link; direct DC to AC conversion approach. The direct DC to AC conversion approach is more efficient and operates without an intermediate dc-link stage. The absence of the dc-link, results in the elimination of bulky, aluminum electrolytic capacitors, which in turn leads to a reduction in the cost, volume, size and weight of the power electronic converter. The feasibility of two direct DC to AC converter topologies and their suitability to meet SECA objectives will be investigated. Laboratory proto-type converters (3-5kW) will be designed and tested in Phase-1. A detailed design ...

2003-12-01

21

When loss is more (for transmission towers) | SmartPlanet  

Wastenet

... ice, hurricanes, and trees (less likely on high voltage transmission lines ) can bring down above ground power lines. Flooding, Leeching ground ...

22

Project considerations and design of systems for wheeling cogenerated power  

Energy Technology Data Exchange (ETDEWEB)

Wheeling electric power, the transmission of electricity not owned by an electric utility over its transmission lines, is a term not generally recognized outside the electric utility industry. Investigation of the term`s origin is intriguing. For centuries, wheel has been used to describe an entire machine, not just individual wheels within a machine. Thus we have waterwheel, spinning wheel, potter`s wheel and, for an automobile, wheels. Wheel as a verb connotes transmission or modification of forces and motion in machinery. With the advent of an understanding of electricity, use of the word wheel was extended to be transmission of electric power as well as mechanical power. Today, use of the term wheeling electric power is restricted to utility transmission of power that it ...

1994-08-01

23

Basic Research Leading to Compact, Portable Pulsed Power  

Science.gov (United States)

... 1 ..... 14 High Dielectric Constant Ceramics for Use in Blumlein Transmission Lines ..... 14 ...

2007-03-31

24

Probability of backflashover in transmission lines due to lightning strokes using Monte-Carlo simulation  

Energy Technology Data Exchange (ETDEWEB)

A method, which estimates the lightning performance of high voltage transmission lines based on the Monte-Carlo simulation technique, is described in this paper. The average number of faults which occur in a transmission line, dividing them in single-phase and three-phase faults, as well as the average grounding resistances of the transmission lines are calculated. The method is applied, on several operating Greek transmission lines, showing good correlation between predicted and field observation results. The proposed method can be used as a useful tool in the design of electric power systems, aiding in the right insulation dimensioning of a transmission line.(author)

2003-02-01

25

Calculation of the transmission capacity of long-distance EHV single-core submarine cable systems  

Energy Technology Data Exchange (ETDEWEB)

A general calculation method for the analysis of transmission capability of a long-distance single-core ac submarine cable system is presented. The method is based on modal transformation of voltages and currents in multiconductor cable systems. Using this method, numerical calculations on 500 kV submarine cable systems have been performed with particular reference to the effect of the distance between bonds connecting metallic sheath, outer conductor and armor on the transmission capacity of the system. It was clarified that the transmission capacity of the system increased with decreasing bond intervals. Examination of the current distributions between various conductors along the length showed that this increase of transmission capacity was mainly due to the dispersion of the charging current into the metallic sheath, outer conductor and armoring at the bonding points. Analytical ...

1981-11-01

26

Computer Controlled MHD Power Consolidation and Pulse ...  

Science.gov (United States)

... is a standard in the utility industry which is used to study switching transients on power distribution networks and high-voltage transmission lines. ...

1990-08-01

27

The effect of patient positioning aids on PET quantification in PET/MR imaging  

British Library Electronic Table of Contents (United Kingdom)

Objectives Clinical PET/MR requires the use of patient positioning aids to immobilize and support patients for the duration of the combined examination. Ancillary immobilization devices contribute to overall attenuation of the PET signal, but are not detected with conventional MR sequences and, hence, are ignored in standard MR-based attenuation correction (MR-AC). We report on the quantitative effect of not accounting for the attenuation of patient positioning aids in combined PET/MR imaging. Methods We used phantom and patient data acquired with positioning aids on a PET/CT scanner (Biograph 16, HI-REZ) to mimic PET/MR imaging conditions. Reference CT-based attenuation maps were generated from measured (original) CT transmission images (origCT-AC). We also created MR-like attenuation map...

2011-01-01

28

2000 MW HVDC link between England and France  

Energy Technology Data Exchange (ETDEWEB)

The HVDC link across the English Channel, which was brought into service in 1986, has several innovative features. Techniques used in its construction together with recent developments have consolidated the viability of HVDC links for a variety of applications. Outlines the main features of the scheme, including the benefits of interconnecting the British and French 400 kV AC power systems; integration of the UK converter system to the 400 kV AC grid; the DC submarine cables; convertor equipment (particularly the UK installation); and future HVDC developments. 6 refs.

1987-03-01

29

Isolated PWM DC-AC SICAM with an active capacitive voltage clamp[Pulse Density Modulated; Pulse Width Modulation  

Energy Technology Data Exchange (ETDEWEB)

In this report an isolated PWM DC-AC SICAM with an active capacitive voltage clamp is presented. AC-DC power supply is implemented in its simplest form: diode rectifier followed by a medium-size charge-storage capacitors and possibly with an EMC filter on the mains entrance. Isolation from the AC mains is achieved using a high frequency (HF) transformer, whose voltages are not audio-modulated. The latter simplifies the design and is expected to have many advantages over the approach where the transformer voltages are modulated in regards to the audio signal reference. Input stage is built as a DC-AC inverter (push-pull, half-bridge or a full-bridge) and operated with 50% duty cycle, with all the challenges to avoid transformer saturation and obtain symmetrical operation. On the secondary side the output section is implemented as rectifier+inverter AC-AC stage, ...

2004-03-15

30

Now try to explain network security  

Science.gov (United States)

Overloaded transmission lines are only part of the problem. The ability of the network to carry power is also limited by the supply of reactive power and by frequency stability. Reactive power problems must be corrected in minutes, frequency stability problems in seconds. There is no way that market forces can handle these problems. Reactive power must be supplied to all long transmission and distribution lines to compensate for the loss of reactive volt-amperes - and resulting voltage drop - in the reactance along the line`s length. 7 figs.

1996-10-01

31

Needs for Constructing and Possibilities of Nuclear Power Plants Interconnection to the Croatian Electricity Grid  

International Nuclear Information System (INIS)

Due to development of electric power system and considering an increase of electrical energy consumption, needs for larger units in new power plants are obvious. Connection of large nuclear power plants to the grid, depending on their power and location, usually requires significant investments in transmission network development and construction. Considering the capacity of the 400 kV transmission network in Croatia, this problem is evident. This paper deals with the possibilities of nuclear power plants construction, as one possible option in electric power system development, and their interconnection to the electricity grid. (author).

1998-06-15

32

Southern receiver system: Environmental impact assessment status report: Conawapa to Winnipeg Power Transmission Complex  

Energy Technology Data Exchange (ETDEWEB)

The Conawapa-Winnipeg Power Transmission Complex includes five interrelated transmission and conversion facilities. This booklet describes work done on the upgrade of the southern receiver system, one component of the complex. The southern receiver system is composed of a network of high voltage transmission lines and station facilities. The booklet includes a description of the upgrade, the project setting, short and long-term effects and impact management, and the next steps to be taken in the process, including the regulatory process and public consultation.

1992-01-01

33

A MAC protocol for cognitive wireless sensor body area networking  

British Library Electronic Table of Contents (United Kingdom)

Abstract In this paper, a Cognitive Radio Based Medium Access Control (CR-MAC) protocol for Wireless Sensor Body Area Networks (WSBAN) that utilizes cognitive radio transmission is proposed. In this proposal, the sensor nodes are classified into nodes of life-critical health information and nodes of non-critical health information. The CR-MAC protocol prioritizes the critical packets access to the transmission medium by transmitting them with higher power while transmitting lower priority packets using lower transmission power. At the receiver, a higher priority packet experiences collision only when there are more than one critical packet transmission at the same transmission slot while non critical packets experience collision when there are more than one transmission at the same transmi...

2010-01-01

34

AC motor drive system for electric cars  

Energy Technology Data Exchange (ETDEWEB)

Various main circuit equipment with large capacity GTO thyristors are outlined for AC and DC electric cars. The configuration of a PWM converter system is presented for the AC main motor drive system of the Shinkansen trains, and its following features are described: the high power factor control capable of keeping a power factor 100% constantly, energy saving by power regenerative braking, the small triple structure with large capacity reverse-conducting GTO thyristors of 4,500V/3,000A, and the reduction of equivalent interfering current and harmonic current by three phase-triple phase difference operation. Furthermore, a control logic equipment with 16 bit MPU and a main transformer are outlined, and the verification test results of the control logic equipment by an analog model simulation and the combinational test results of the commercial equipment are reported. Prototype VVVF ...

1989-08-10

35

Results from field experiments on AC polluted insulators in Mexico  

Energy Technology Data Exchange (ETDEWEB)

As contamination flashover is in Mexico the second cause of transmission line faults, the Mexican Electrical Research Institute carried out a project to determine pollution patterns for the Republic of Mexico to be used for the design of external insulation. Results from the project are presented: the modelling, based on the field data of 23 experimental sites, of long term variations of pollution patterns as a function of environmental variables, insulator shape and position, as well as other important field results. 32 refs, 2 figs, 4 tabs

1995-12-01

36

Etching characteristics of high-purity aluminum in hydrochloric acid solutions  

Energy Technology Data Exchange (ETDEWEB)

We investigated the effects of additives to the etching solution of 1 M hydrochloric acid on the electrochemical etching behavior for aluminum electrolytic capacitors, using scanning and transmission electron microscopy, and AC impedance spectroscopy. For the addition of 1 M sulfuric acid or 5% ethylene glycol to the hydrochloric acid solution, the distribution of etch tunnels was more uniform with high density of etch pits compared with that without addition. The highest specific surface area was obtained from the electrolyte with 5% ethylene glycol additive. The correlation of internal morphologies of etched foils with impedance parameters was interpreted by impedance techniques.

2007-03-25

37

Assessing the profitability of reactive power compensation devices  

Energy Technology Data Exchange (ETDEWEB)

A probabilistic method for assessing the profitability of reactive power compensation devices such as capacitors, static VAR compensators and generators, which improve network security, was described. Since network development is limited by environmental constraints, power networks are operated close to their limits. Because of this fact transmission network planning increasingly relies on techno-economic models to improve network security and profitability. The proposed method consists of analyzing large numbers of constrained power system states, extracted from power system simulation exercises. The paper describes details of the method and provides an example of a numerical application on a part of the French power transmission system. 10 refs., 8 figs.

1997-12-31

38

Research and development of photovoltaic power system; Taiyoko hatsuden system no jissho kenkyu  

Energy Technology Data Exchange (ETDEWEB)

This paper reports the result obtained during fiscal 1994 on a demonstration research on photovoltaic power generating systems. Solar cells with an output of 750 kW, storage battery facilities with an output of 3,058 kWh, three DC-AC converters with a rating of 250 kW, and a diesel generator with an output of 300 kW having been installed up to the previous fiscal year were combined to perform comprehensive adjustments and tests such as battery charge/discharge tests and AC parallel operation tests. The battery charge/discharge tests revealed that the 10 hour rate discharge capacity meets the specifications, and the batteries are free of deterioration after a demonstration operation of about 4.5 months. Difference between the power generation record and the planned value is thought due to the following reasons: the array output data in a power line connected system come about 90% of ...

1994-12-01

39

Integral air-conditioning system for electric cars. Integrales Klimasystem fuer Elektroautomobile  

Energy Technology Data Exchange (ETDEWEB)

Increasing environmental awareness and new legislation in Europe and, in particular, America have accelerated the development of marketable electric cars which satisfy customer demands in terms of performance, range capability, safety and comfort. Tomorrow's electric cars will therefore require powerful heating and cooling systems for the passenger compartment which meet the conditions specific to this particular mode of transport and which do not overly affect the range capability of such vehicles. At Behr GmbH suitable system concepts were developed at a very early stage which were based on a high proportion of recirculated air, the use of the A/C unit as a heat pump, and heat recovery. This paper will examine two typical A/C systems which combine good heating and cooling characteristics with the low electric power requirement of only 1,5-2 kW. (orig.).

1992-11-01

40

Direct energy recovery with ac electric power output  

Energy Technology Data Exchange (ETDEWEB)

A concept of direct energy recovery system applying an alternating or rotating magnetic field is proposed for a negative-ion-based neutral beam injection system (NNB) to heat a plasma and/or drive a plasma current in a fusion reactor. Nearly same amounts of residual positive and negative hydrogen-isotope ion beams with beam energy of {approx}1 MeV are produced in an NNB using a gas neutralizing cell. Consequently, a recovered energy is obtained directly in the form of ac electric power, if these positive- and negative-ion beams are alternated or rotated and introduced to two or more recovery electrodes in turn by an alternating or rotating magnetic field. This concept will greatly reduce a technological difficulty in regeneration of a recovered electric energy with such a very high voltage. (author).

1994-12-31

41

Trade curtailment schemes for the security control of the transmission network in a deregulated environment  

Energy Technology Data Exchange (ETDEWEB)

Due to deregulation, the electrical power industry is undergoing deep changes, moving towards an open market. Two kinds of parties are active in the new environment: the economical agents (producers, consumers, brokers) and the power system operator, the former interested in power exchanges and their economic value, the latter in bus injections and their threat to the security of the transmission network. The variables used to model the transmission network operation have to be meaningful to the power system operator as well as to the economical parties; the action rules followed by the power system operator to enforce network security have to be carefully designed to be equitable and non-discriminatory. In this paper, a modeling of the power exchanges is proposed in the form of multilateral trades, and some rules for ...

2002-01-01

43

Maximum entropy probability method applied to assess voltage sag frequency due to transmission line fault in the electric power system  

British Library Electronic Table of Contents (United Kingdom)

Abstract Voltage sag caused by faults on an electric power transmission line is one of the most intractable power quality issues for both utility companies and customers. The fault in power system randomly exists along transmission lines due to the combination of many uncertain factors. To predict and assess the annual expected sag frequency (ESF) deriving from the faults along lines, a stochastic based method that employs maximum entropy principle, namely the maximum entropy probability method (MEPM), has been introduced in this paper. Moreover, various types of faults have been considered systematically. With the fault line intervals and the sample moments taken into account, the discrete values of distribution probability of fault locations along the transmission lines have been estimat...

2010-01-01

45

Evidence from 12 geographically disparate power grids - NASA  

Science.gov (United States)

miles of high-voltage transmission lines with 12 intercon- nections to electricity systems in New York and Canada. As of 1 March 2003, ISO New England has ...

46

Capturing energy in the air to power electronics | SmartPlanet  

Wastenet

...smart grid applications where you could place them very close to the high-voltage transmission lines , very close to transformers and so on. Photo:...

47

Particle Swarm Optimization Based Reactive Power Optimization  

CERN Document Server

Reactive power plays an important role in supporting the real power transfer by maintaining voltage stability and system reliability. It is a critical element for a transmission operator to ensure the reliability of an electric system while minimizing the cost associated with it. The traditional objectives of reactive power dispatch are focused on the technical side of reactive support such as minimization of transmission losses. Reactive power cost compensation to a generator is based on the incurred cost of its reactive power contribution less the cost of its obligation to support the active power delivery. In this paper an efficient Particle Swarm Optimization (PSO) based reactive power optimization approach is presented. The optimal reactive power dispatch problem is a ...

2010-01-01

48

The effect of high voltage transmission lines on agricultural land values in minnesota  

Energy Technology Data Exchange (ETDEWEB)

Overhead, high power transmission lines have secured rights of way on agricultural lands in Minnesota. The economic impact of such utility crossings, including effects on land price, was investigated. Sale records and survey data were analyzed. Buyers, sellers, and brokers were interviewed concerning inconvenience, radio interference, appearance, and loss of irrigation possibilities due to the transmission lines. In nine affected sales, there was only one case in which less money was indicated for the farm because of the presence of a transmission line.

1981-04-01

49

The effect of high voltage transmission lines on agricultural land values in Minnesota  

Energy Technology Data Exchange (ETDEWEB)

Overhead, high power transmission lines have secured rights of way on agricultural lands in Minnesota. The economic impact of such utility crossings, including effects on land price, was investigated. Sale records and survey data were analyzed. Buyers, sellers, and brokers were interviewed concerning inconvenience, radio interference, appearance, and loss of irrigation possibilities due to the transmission lines. In nine affected sales, there was only one case in which less money was indicated for the farm because of the presence of a transmission line.

1981-04-01

50

High voltage transmission lines - what are the hazards  

International Nuclear Information System (INIS)

With the increasing use of high voltage alternating current (HVAC) transmission lines there is a growing concern among the public about possible human health effects resulting from exposure to the electric fields associated with these lines. While there is no definitive evidence of such effects, mounting public fear and activism over hypothesized health risks is already causing delays in the licensing and constuction of major power transmission facilities, and is encouraging the formation of regulatory policy. This paper briefly reviews the concerns, biological effects data and standards for HVAC transmission lines.

1984-07-01

51

Calculating ac/dc resistance ratios for high-pressure oil-filled cable designs. Volume 2. Details of mathematical derivations. Final report  

Energy Technology Data Exchange (ETDEWEB)

Conventional methods for calculating electricity losses in pipe-type cable systems rely heavily on data measured in lower-voltage systems in the 1950s. With the new technique developed in this study, engineers can compute power losses more precisely for cables of various configurations and voltage ratings.

1985-04-01

52

Database for thermal and mechanical properties of REBaCuO bulks  

International Nuclear Information System (INIS)

The thermal properties (thermal conductivity, thermal diffusivity, thermoelectric power, thermal dilatation, etc.) and the mechanical properties (Young's modulus, strength, hardness, fracture toughness, etc.) have been measured at low temperatures (4-300K) and under a high magnetic field (0-10T) for about 50 REBaCuO bulks (RE=Y, Gd, Nd, Sm, Dy, etc.). We have constructed the database of these properties and opened it on the Web site (thermal properties: http://ikebehp.mat.iwate-u.ac.jp/database.html and mechanical properties: http://paris.mech.iwate-u.ac.jp/sc-bulk/database.html). The influence of the species of RE ions, the content, size and dispersion of the RE211 (or Nd422) phase and Ag particles and the defects distribution on these properties is characterized.

2005-10-01

53

New approach to compensation of extra high voltage transmission lines  

Energy Technology Data Exchange (ETDEWEB)

A computer-aided design procedure has been developed for the series compensation of an extra high voltage line with a compensating network connected at one or the other end or both ends. Higher degree polynomial equations are derived in terms of compensating elements to compute the network parameters for optimum received power with constrained capacitor terminal voltage, safe line current, Ferranti voltage and transient stability. It is shown that series capacitors located at both ends provide the most effective means from the viewpoint of power transmission capability in either direction, transmission efficiency and series capacitor rating in comparison with a capacitor located at one or the other end.

1985-09-01

54

Negative ion formation in magnetically insulated transmission lines  

Energy Technology Data Exchange (ETDEWEB)

Negative ion intensities of over 3 x 10/sup 5/ A/m/sup 2/ at energies of 2 MeV have been measured in a magnetically insulated transmission line. This negative ion production can affect the power flow in multiterawatt pulsed power devices, and may also have applications in the generation of high-intensity neutral or negative ion beams.

1982-05-01

55

Electric loading of power transmission lines - statistical methodology and real time management; Carregamento eletrico de linhas de transmissao - metodologia estatistica e gerenciamento em tempo real  

Energy Technology Data Exchange (ETDEWEB)

This paper shows a computerized system, that adopt a statistical methodology and simultaneous measurements of wind velocity and environment temperature, as an experiences at the power transmission lines with environmental monitoring systems. 9 figs., 16 refs.

1991-12-31

56

The integration of renewable energy sources into electric power transmission systems  

Energy Technology Data Exchange (ETDEWEB)

Renewable energy technologies such as photovoltaics, solar thermal power plants, and wind turbines are nonconventional, environmentally attractive sources of energy that can be considered for electric power generation. Many of the areas with abundant renewable energy resources (very sunny or windy areas) are far removed from major load centers. Although electrical power can be transmitted over long distances of many hundreds of miles through high-voltage transmission lines, power transmission systems often operate near their limits with little excess capacity for new generation sources. This study assesses the available capacity of transmission systems in designated abundant renewable energy resource regions and identifies the requirements for high-capacity plant integration in selected cases. In general, about 50 MW of ...

1995-07-01

57

Radio and television interference caused by corona discharges from high-voltage transmission lines  

Energy Technology Data Exchange (ETDEWEB)

Increase in power utility loads in industrialized countries, as well as developing countries, demands a higher level of transmission line voltage. Radio interference (RI) problems have been determined to be a limiting factor in selecting the size of transmission line conductors. Transmission line noise is primarily caused by corona discharges in the immediate vicinity of the conductor. It has been observed that discharges occur during both half-cycles of the applied voltage, but positive corona is usually predominant at AM radio frequencies range with practical high-voltage and extra high-voltage transmission lines. The corona radio noise effect is highly dependent upon the presence of particles on the surface of the conductor and the increase of the electrical gradient beyond the breakdown value of the air. Therefore, corona radio noise varies significantly with the weather and ...

1996-11-01

58

Radio and television interference caused by corona discharges from high-voltage transmission lines  

Energy Technology Data Exchange (ETDEWEB)

Increase in power utility loads in industrialized countries, as well as developing countries, demands a higher level of transmission line voltage. Radio interference (RI) problems have been determined to be a limiting factor in selecting the size of transmission line conductors. Transmission line noise is primarily caused by corona discharges in the immediate vicinity of the conductor. It has been observed that discharges occur during both half-cycles of the applied voltage, but positive corona is usually predominant at AM radio frequencies range with practical high-voltage and extra high-voltage transmission lines. The corona radio noise effect is highly dependent upon the presence of particles on the surface of the conductor and the increase of the electrical gradient beyond the breakdown value of the air. Therefore, corona radio noise varies significantly with the weather and ...

1995-10-01

59

Radio and television interference caused by corona discharges from high-voltage transmission lines  

International Nuclear Information System (INIS)

Increase in power utility loads in industrialized countries, as well as developing countries, demands a higher level of transmission line voltage. Radio interference (RI) problems have been determined to be a limiting factor in selecting the size of transmission line conductors. Transmission line noise is primarily caused by corona discharges in the immediate vicinity of the conductor. It has been observed that discharges occur during both half-cycles of the applied voltage, but positive corona is usually predominant at AM radio frequencies range with practical high-voltage and extra high-voltage transmission lines. The corona radio noise effect is highly dependent upon the presence of particles on the surface of the conductor and the increase of the electrical gradient beyond the breakdown value of the air. Therefore, corona radio noise varies significantly with the weather and ...

1996-04-09

60

Curecanti-Blue Mesa-Salida 115-kV transmission lines access roads rehabilitation, maintenance, and construction project. Environmental Assessment  

Science.gov (United States)

Western Area Power Administration (Western) is a power marketing agency of the US Department of Energy, with jurisdiction in 15 western states. The Salt Lake City Area (SLCA) of Western performs the agency`s mission in parts of Colorado, New Mexico, Texas, Utah, Arizona, Wyoming, and Nevada. As part of its mission, Western owns, operates, and maintains a system of transmission lines for transmitting bulk electrical energy from points of generation to and between delivery points. Part of that system in southwestern Colorado includes the Blue Mesa-Curecanti and Blue Mesa-Salida 115-kV transmission lines. Western proposes to conduct maintenance and improve its access roads for these two transmission lines. This paper discusses the impacts to the existing environment as well as the environmental consequences resulting from the maintenance and construction that is proposed.

1993-07-01

61

A novel wavelet transform aided neural network based transmission line fault analysis method  

Energy Technology Data Exchange (ETDEWEB)

In the present scenario of market driven business, power supply has become more like a commodity. Reliable and quality power need to be ensured to meet customer requirements. In such a situation, it is extremely important that transmission line faults be identified accurately, reliably and in quick time. Advanced signal processing tools such as discrete wavelet transform (DWT) can be used very effectively for parameterisation and characterization of the fault signals. On the other hand, properly configured neural network (NN) can be utilized for classification of the faults based on the DWT signal. The present contribution uses electromagnetic transient program (EMTP) for modeling of a real transmission system and MATLAB for DWT and NN. Various types of faults have been simulated at different locations along the transmission line and an attempt has been made to correctly identify ...

2009-06-15

62

Intersociety energy conversion engineering conference, 20th, Miami Beach, FL, August 18-23, 1985, Proceedings. Volumes 1, 2, and 3  

International Nuclear Information System (INIS)

Topics related to aerospace power are discussed, taking into account trends and issues of military space power systems technology, space station power system advanced development, the application and use of nuclear power for future spacecraft, the current status of advanced solar array technology development, the application of a parabolic trough concentrator to space station power needs, life test results of the Intelsat-V nickel-cadmium battery, and metal hydride hydrogen storage in nickel hydrogen batteries. Other subjects explored are concerned with alternative fuels, biomass energy, biomedical power, coal gasification, electric power cycles, and electric propulsion. Attention is given to an advanced terrestrial vehicle electric propulsion systems assessment, fuel cells as electric propulsion power plants, a sinewave ...

1985-08-18

63

Integrated evolutionary neural network approach with distributed computing for congestion management  

British Library Electronic Table of Contents (United Kingdom)

Electric supply industry is facing deregulation all over the world. Under deregulated power supply scenario, power transmission congestion has become more intensified and recurrent, as compared to conventional regulated power system. Congestion may lead to violation of voltage or transmission capacity limits, thus threatens the power system security and reliability. Also the growing congestion may lead to unanticipated divergent electricity pricing. Owing to these facts congestion management has become a crucial issue in the deregulated power system scenario. Fast and precise prediction of nodal congestion prices in real time deregulated/spot power market may enable market participants and system operators to keep pace with the congestion by taking preventive measures like transaction resc...

2010-01-01

64

Optimization of Hellenic overhead high-voltage transmission lines lightning protection  

Energy Technology Data Exchange (ETDEWEB)

It is well known that the lightning protection of transmission lines is exclusively relying on their correct initial design. Although detailed engineering studies are usually performed by electric power utilities for the design of new transmission lines, there are reported cases where the design is based simply on tradition or on utilities' standardization policy. In this paper, the lightning protection of high-voltage transmission lines is faced as an optimization problem where optimum design parameters are calculated for the lines, relating their cost with the lightning failures' cost, aiming to reduce or even eliminate lightning failures. The optimization method considers all the available protection means, i.e. ground wires and surge arresters. In order to validate the effectiveness of the proposed method, it is applied on several operating Hellenic ...

2009-04-15

65

Electrical human-power transmission. The bicycle technology of the 21st century; Elektrische Muskelkrafttransmission. Fahrradtechnologie des 21. Jahrhunderts. Schlussbericht  

Energy Technology Data Exchange (ETDEWEB)

Since 1994-95 the University of Applied Sciences Berne is working on weather-proof electric bicycles. The main drawbacks of bicycles, no weather-protection, little comfort of the saddle, the difficulty of climbing hills, are to be eliminated. The electro-mechanical drive-train of 'Ultraleichtmobil ULM BE 2000', developed in 1995-96, was mechanically complicated. This resulted in reduced energy-efficiency and intense maintenance. Too, the drive-train was expensive in production. A fully electrical human-power transmission seemed to be the solution to the problems mentioned above. It is appealing not only to the user of the vehicle, but also to the producer and to the persons doing the maintenance. Following an internal study showing the technical feasibility of such an electrical transmission, a controllable DC/DC-converter which allows to operate a pedal-driven generator at maximum efficiency has been ...

1999-12-01

66

Improvement of power system stability by high speed power control of adjustable speed machine; Kahensokuki no koshutsuryoku seigyo ni yoru denryoku keito no anteido kojo  

Energy Technology Data Exchange (ETDEWEB)

Large capacity adjustable speed machines (ASMs) at pumped storage power station have been put into full operation and the operating characteristics of ASM have been highly evaluated from the view point of power system operation. The output power (input power) of ASM can be controlled very quickly by applying a vector control scheme to the excitation control. This quick responsive feature of ASM can make it possible to improve the stability of the neighbor sub-power system. For improvement of transient stability, the output power of ASM is reduced very quickly in order to control the acceleration of neighbor generators during and after transmission line faults. For improvement of dynamic stability, the output power of ASM is modulated in accordance with the stabilizing signals detected from the swing of generator rotor or ...

1997-01-20

67

Proceedings of the Areva Technical Days. Session 5  

Energy Technology Data Exchange (ETDEWEB)

This document presents the proceedings of the Areva technical days, presented during the session 5 the 9 and 10 december 2004, at Istanbul. It deals with the operations of the transmission and distribution division. With manufacturing facilities in over 40 countries and a sales network in over 100, Areva offers customers technological solutions for nuclear power generation and electricity transmission and distribution (the Group also provides interconnect systems to the telecommunications, computer and automotive markets). It provides five topics: a general presentation of Areva, the strategic stakes for transmission and distribution by world-zone, economic and strategic stakes of business unit products, business unit systems and business unit automation. (A.L.B.)

2004-07-01

68

Multiple stress aging of solid-dielectric extruded dry-cured insulation systems for power transmission cables  

Energy Technology Data Exchange (ETDEWEB)

A detailed examination of the aging processes that may take place in solid-dielectric extruded-type high voltage transmission cables under dry conditions is presented. Particular emphasis is placed on the aging process as affected by the separate and simultaneous action of four main aging factors, namely the electrical, mechanical and thermal stresses, and the physical and chemical environment. A number of pertinent aging models are considered and their validity and applicability to accelerated aging tests on solid-type transmission cables are discussed.

1994-01-01

69

A Reduced Wind Power Grid Model for Research and Education  

Energy Technology Data Exchange (ETDEWEB)

A reduced grid model of a transmission system with a number of central power plants, consumption centers, local wind turbines and a large offshore wind farm is developed and implemented in the simulation tool PowerFactory (DIgSILENT). The reduced grid model is given by Energinet.dk, Transmission System Operator of Denmark (TSO) for Natural Gas and Electricity, to the Danish Universities and the Risoe National Laboratory. Its intended usage is education and studying of interaction between electricity-producing wind turbines and a realistic transmission system. Focus in these studies is on voltage stability issues and on the ride-through capability of different wind turbine concepts, equipped with advanced controllers, developed by the Risoe National Laboratory.

2006-07-01

70

An improved soft switched PWM interleaved boost AC-DC converter  

International Nuclear Information System (INIS)

In this paper, an improved soft switched two cell interleaved boost AC/DC converter with high power factor is proposed and investigated. A new auxiliary circuit is designed and added to two cell interleaved boost converter to reduce the switching losses. The proposed auxiliary circuit is implemented using only one auxiliary switch and a minimum number of passive components without an important increase in the cost and complexity of the converter. The main advantage of this auxiliary circuit is that it not only provides zero-voltage-transition (ZVT) for the main switches but also provides soft switching for the auxiliary switch and diodes. Though all semiconductor devices operate under soft switching, they do not have any additional voltage and current stresses. The proposed converter operates successfully in soft switching operation mode for a wide range of input voltage level and the load. In addition, it has advantages such as fewer structure ...

2011-01-01

71

The effects of high voltage transmission lines on the health of adjacent resident populations  

Energy Technology Data Exchange (ETDEWEB)

A community health survey of 438 individuals was taken to detect health problems related to high voltage electrical transmission among an adjacent residential population. Results revealed no significant or consistent relationships between exposure to a high voltage DC power line and the perceived health problems that were measured. The sample was not, however, large enough to draw statistically significant conclusions regarding possible health effects with a very low incidence.

1984-01-01

72

Modeling dependent failures for the availability of extra high voltage transmission lines  

Energy Technology Data Exchange (ETDEWEB)

This paper investigates the calculation of availability for parallel transmission lines (two or more) in the same tower or on the same right of way. As in many studies, the development of mathematical models is an important step. The models are justified using historical data and known characteristics of power system elements. A statistical method was used to generalize the failure rate and repair rate from real operating data. Application of the new model (which combines common-mode, simultaneous independent, and dependent outages) is discussed.

1989-06-01

73

Highlights of technical support to the Department of Energy, Division of Electric Energy Systems, Electric Power and Transmission Programs. Final technical report, 1980-1981  

Energy Technology Data Exchange (ETDEWEB)

A broad-based, multidisciplinary research program is being conducted to study biological effects of electric and magnetic fields from high-voltage transmission lines. Assistance and technical support for this program are reported. (DLC)

1982-02-01

74

Combined heuristic with fuzzy system to transmission system expansion planning  

Energy Technology Data Exchange (ETDEWEB)

A heuristic algorithm that employs fuzzy logic is proposed to the power system transmission expansion planning problem. The algorithm is based on the divide to conquer strategy, which is controlled by the fuzzy system. The algorithm provides high quality solutions with the use of fuzzy decision making, which is based on nondeterministic criteria to guide the search. The fuzzy system provides a self-adjusting mechanism that eliminates the manual adjustment of parameters to each system being solved. (author)

2011-01-15

75

Calculation of 3-D electrical field distribution around technical devices in the vicinity of high voltage transmission lines  

Energy Technology Data Exchange (ETDEWEB)

The influence that electromagnetic fields have on mechanical and electronic equipment was discussed. A three dimensional numerical simulation model of electric fields around high voltage power transmission lines was described. 4 refs., 1 tab., 5 figs.

1997-12-31

76

Calculation of 3-D electrical field distribution around technical devices in the vicinity of high voltage transmission lines  

International Nuclear Information System (INIS)

The influence that electromagnetic fields have on mechanical and electronic equipment was discussed. A three dimensional numerical simulation model of electric fields around high voltage power transmission lines was described. 4 refs., 1 tab., 5 figs.

1997-08-24

77

Power system stabilizer application in a two unit plant analytical studies and field tests  

Energy Technology Data Exchange (ETDEWEB)

The use of excitation system controls, specifically the Power System Stabilizer (PSS), to improve damping of power system oscillations and thus extend steady-state stability limits has been a subject of great interest in recent years. The desire to more fully utilize transmission capacity led to the installation of PSS controls on greater numbers of generating units to maintain stability margins. This paper addresses the tuning and adjustment of PSS controls in a two unit power plant. Both analytical studies and field test confirmations are presented. The practical difficulties of verifying the PSS control loop gain margin by testing are explored. A simplified procedure is outlined. The Lower Colorado River Authority (LCRA), Fayette Power Project (FPP) consists of two 683.7 MVA tandem compound steam turbine driven generators. The excitation systems are of the alternator rectifier ...

1983-02-01

78

A study on the anodic protection of titanium evaporators in Al[sub 2](SO[sub 4])[sub 3] solution  

Energy Technology Data Exchange (ETDEWEB)

The feasibility of the anodic protection of titanium evaporators in Al[sub 2](SO[sub 4])[sub 3] solution was studied by the measurement of polarization curves, weight loss, solubility of passive film and AC impedance. The protection parameters and efficiency were determined. In addition, the practical technology of anodic protection was studied by screening reference electrodes and auxiliary cathodes. Throwing power was also measured. Four rows of tube-type evaporators of titanium have been anodically protected in situ. Field tests lasting more than one year shows satisfactory results. (orig.)

1993-07-01

79

Implications of high temperature superconductors for power generation  

International Nuclear Information System (INIS)

Superconducting generators for high power applications have been of interest for a number of years. Superconducting generators using low temperature superconductors (LTS) have been manufactured to produce up to 20 MW of electrical power and have been configured in either synchronous alternators which have an AC output that may be subsequently rectified to produce DC and homopolar generators which produce low voltage DC. Typically these generators require scrupulous attention to vacuum integrity for cryogenic insulation at 4.2K and tend to be somewhat fragile because of extensive thermal and magnetic shields that are not required in conventional power generators. Recently, high purity aluminum composites have been developed for a high power AC generator that is cooled by cryogenic hydrogen at 21K. This aluminum generator is very compact and lightweight and is ...

1991-08-03

80

Radiographic experience with power transmission equipment  

Energy Technology Data Exchange (ETDEWEB)

This paper describes radiography as one of the most efficient and cost effective methods for inspecting electric cabls. Details of one project in particular, i.e., the inspection of high-pressure, oil-filled, pipe-type cables (HPOF) are given. 2 refs.

1980-01-01

81

Living and Working Around High-Voltage Power Lines.  

Energy Technology Data Exchange (ETDEWEB)

This booklet presents safe practices that you should follow if your activities take you near high-voltage transmission lines. It documents information that has generally been available to the public.

1981-08-01

82

Helical piles for power transmission lines : case study in northern Manitoba  

Energy Technology Data Exchange (ETDEWEB)

This document presented the results of a full-scale pile load tests conducted on helix pile foundations supporting power transmission towers in northern Manitoba. The site conditions were described along with pile installation and the performance of the foundations. The pile load tests were carried out in 2 different soil conditions, notably soft to firm clays and stiff high plastic clays with silt varves. The performance of the helix pile foundations were examined under axial compressive and axial tension (uplift) loading conditions. The results of the compressive load tests were presented in the form of load settlement curves while the results of the uplift load tests were presented in the form of load displacement curves. Both types of load tests in soft or stiff clays showed the suitability of helical pile foundations for power transmission lines in northern Manitoba. The cylindrical shear failure ...

2008-07-15

83

Electric and magnetic field exposures for people living near a 735-kilovolt power line.  

UK PubMed Central (United Kingdom)

The purpose of this study was to assess the effect of a 735-kV transmission line on the electric and magnetic field exposures of people living at the edge of the line's right of way. Exposure of 18...Full Text Available

1995-09-01

84

A multi-objective framework for dynamic transmission expansion planning in competitive electricity market  

Energy Technology Data Exchange (ETDEWEB)

Restructuring of power system has changed the traditional planning objectives and introduced challenges in the field of Transmission Expansion Planning (TEP). Due to these changes, new approaches and criteria are needed for transmission planning in deregulated environment. Therefore, in this paper, a dynamic expansion methodology is presented using a multi-objective optimization framework. Investment cost, congestion cost and reliability are considered in the optimization as three objectives. To overcome the difficulties in solving the non-convex and mixed integer nature of the optimization problems, a Non-Dominated Sorting Genetic Algorithm (NSGA II) approach is used followed by a fuzzy decision making analysis to obtain the final optimal solution. The planning methodology has been demonstrated on the IEEE 24-bus test system and north-east of Iran national 400 kV transmission grid to show the ...

2010-10-15

85

Optimal security-constrained power scheduling by Benders decomposition  

Energy Technology Data Exchange (ETDEWEB)

This paper presents a Benders decomposition approach to determine the optimal day-ahead power scheduling in a pool-organized power system, taking into account dispatch, network and security constraints. The study model considers the daily market and the technical constraints resolution as two different and consecutive processes. The daily market is solved in a first stage subject to economical criteria exclusively and then, the constraints solution algorithm is applied to this initial dispatch through the redispatching method. The Benders partitioning algorithm is applied to this constraints solution process to obtain an optimal secure power scheduling. The constraints solution includes a full AC network and security model to incorporate voltages magnitudes as they are a critical factor in some real power systems. The algorithm determines the active power ...

2007-05-15

86

A New Green Power Inverter for Fuel Cells  

DEFF Research Database (Denmark)

This paper presents a new grid connected inverter for fuel cells. It consists of a two stage power conversion topology. Since the fuel cell operates with a low voltage in a wide voltage range (25 V-45 V) this volt- age must be transformed to around 350-400 V in order to invert this dc power into ac power to the grid. The proposed converter consists of an isolated dc-dc converter cascaded with a single phase H-bridge inverter. The dc-dc converter is a current-fed push-pull converter. A new dedicated voltage mode startup procedure has been developed in order to limit the inrush current during startup. The inverter is controlled as a power factor controller with resistor emulation.Experimental results of converter efficiency, grid performance and fuel cell response are shown for a 1 kW prototype. The proposed converter exhibits a high efficiency in a wide power ...

2002-01-01

87

Satellite power systems (SPS) concept definition study (Exhibit D). Solid-state amplifier investigation. Final report  

Energy Technology Data Exchange (ETDEWEB)

Data resulting from a continuing effort to provide system/subsystem definition data to aid in the evaluation of the SPS program concept is presented. The specific data described relate to the proposed use of solid state devices as microwave power amplifiers in the satellite microwave power transmission subsystem.

1981-04-01

88

High-temperature superconductivity (HTS): summary of case study results; Vorteile der Hochtemperatursupraleitung. Resultate von Fallstudie  

Energy Technology Data Exchange (ETDEWEB)

The system study 'High Temperature Superconductivity (HTS) in power systems' lists the technical and economical advantages for power generation, transmission and distribution systems using components made of HTS material as seen in the light of current knowledge in the superconductivity area. This report lists the advantages of using high-temperature superconductivity in the power industry area and summarises the results obtained in various case studies on the subject.

2000-07-01

89

Electrical equipment of the Marchtrenk power station on the river Traun  

Energy Technology Data Exchange (ETDEWEB)

By way of introduction, the author describes the electrical equipment of the power station on the River Traun and then lists the main features of the electrical systems such as generators, transformers, the power transmission systems as, e.g., the generator leads, the 8 kV switch plant, the 110 kV oil-filled cable as well as the station-service, control, protection and monitoring systems. The control of the headwater level and of the mechanical systems of the barrage is described in detail.

1982-03-01

90

Underground electric-power transmission-system environmental impact assessment  

Energy Technology Data Exchange (ETDEWEB)

The US Department of Energy, Division of Electric Energy Systems, has undertaken to identify the environmental issues and potential impacts associated with the installation of underground electric power transmission systems. This study reports the results of investigations into the advanced cable technologies being considered for future underground applications, as part of the development oriented research program of the Division of Electric Energy Systems. While the technology involves a high level of sophistication, there are relatively few impacts to the environment that are potentially significant, and of these none are inherently non-mitigable. Route planning, system design, and methods of construction and accident response can be pursued in order to minimize impacts where strict constraints are appropriate.

1982-03-01

91

Electricity supply in Germany  

Energy Technology Data Exchange (ETDEWEB)

Data on various aspects of the electric power industry in Germany is presented in this article. A map of high voltage transmission lines used by the public utilities is included, which indicates the fuel used at each power station. Data on power generated by fuel used from 1991 to 1996 is given, and additional or new capacity for 1995 to 1999 is also noted. Other tables detail capital investment in public utilities energy input by fuel source, power capacity by utility or private power stations by energy source, utility ownership and electricity demand by consumer. (UK)

1997-09-01

92

A gridded D-"3He IEC power plant  

International Nuclear Information System (INIS)

Inertial Electrostatic Confinement (IEC) fusion was recently described by an Electric Power Research Institute (EPRI) review panel as potentially leading to a most attractive fusion reactor from a utility point of view, if the physics issues can be resolved. Consequently, a design for a small 25-MW electric D-"3He fueled power plant has been explored. Key power plant components consist of the IEC, direct energy conversion and a step-down converter for electrical power transmission. (author).

93

A novel wavelet transform aided neural network based transmission line fault analysis method  

British Library Electronic Table of Contents (United Kingdom)

In the present scenario of market driven business, power supply has become more like a commodity. Reliable and quality power need to be ensured to meet customer requirements. In such a situation, it is extremely important that transmission line faults be identified accurately, reliably and in quick time. Advanced signal processing tools such as discrete wavelet transform (DWT) can be used very effectively for parameterisation and characterization of the fault signals. On the other hand, properly configured neural network (NN) can be utilized for classification of the faults based on the DWT signal. The present contribution uses electromagnetic transient program (EMTP) for modeling of a real transmission system and MATLAB for DWT and NN. Various types of faults have been simulated at differ...

2009-01-01

94

Living and Working Safely Around High-Voltage Power Lines.  

Energy Technology Data Exchange (ETDEWEB)

High-voltage transmission lines can be just as safe as the electrical wiring in the homes--or just as dangerous. The crucial factor is ourselves: they must learn to behave safely around them. This booklet is a basic safety guide for those who live and work around power lines. It deals primarily with nuisance shocks due to induced voltages, and with potential electric shock hazards from contact with high-voltage lines. References on possible long-term biological effects of transmission lines are shown. In preparing this booklet, the Bonneville Power Administration has drawn on more than 50 years of experience with high-voltage transmission. BPA operates one of the world`s largest networks of long-distance, high-voltage lines. This system has more than 400 substations and about 15,000 miles of transmission lines, almost 4,400 miles of which are operated at 500,000 ...

2001-06-01

95

Analysis of lightning fault detection, location and protection on short and long transmission lines using Real Time Digital Simulation  

Energy Technology Data Exchange (ETDEWEB)

The purpose of this paper is to present an analysis of lightning fault detection, location and protection using numeric distance relays applied in high voltage transmission lines, more specifically in the 500 kV transmission lines of CEMIG (Brazilian Energy Utility) between the Vespasiano 2 - Neves 1 (short line - 23.9 km) and Vespasiano 2 - Mesquita (long line - 148.6 km) substations. The analysis was based on the simulations results of numeric distance protective relays on power transmission lines, realized in September 02 to 06, 2002, at Siemens AG's facilities (Erlangen - Germany), using Real Time Digital Simulator (RTDS{sup TM}). Several lightning faults simulations were accomplished, in several conditions of the electrical power system where the protective relays would be installed. The results are presented not only with the times of lightning faults elimination, but ...

2007-07-01

96

Calculating ac/dc resistance ratios for high-pressure oil-filled cable Designs. Volume 1. Designer's guide. Final report  

Energy Technology Data Exchange (ETDEWEB)

Using electromatic field theory, a new method is developed for calculating alternating current in power cables installed in pipes of carbon steel (magnetic pipes). The technique for evaluating these losses is based on the method of images which replaces complicated distribution of currents in the system with a sequence of thin conductors. The method not only gives a mathematical framework for the solution of alternating current losses, but it also gives the underlying physical picture of effects contributing to these losses. Skin effect, proximity effect and losses due to the pipe are calculated separately. For the first time, the increase of losses in the conductors, when the cables are placed in a magetic pipe, are analyzed mathematically. Good agreement is obtained between the result of calculations and the experimentally determined ac-dc resistance ratios for pipe-type cables with concentric stranded copper conductors and also for cables ...

1985-04-01

97

Numerical simulations of nucleate boiling in impinging jets: Applications in power electronics cooling  

Energy Technology Data Exchange (ETDEWEB)

Boiling jet impingement cooling is currently being explored to cool power electronics components. In hybrid vehicles, inverters are used for DC-AC conversion. These inverters involve a number of insulated-gate bipolar transistors (IGBTs), which are used as on/off switches. The heat dissipated in these transistors can result in heat fluxes of up to 200 W/cm{sup 2}, which makes the thermal management problem quite important. In this paper, turbulent jet impingement involving nucleate boiling is explored numerically. The framework for these computations is the CFD code FLUENT. For nucleate boiling, the Eulerian multiphase model is used. The numerical results for boiling water and R113 jets (submerged) are validated against existing experimental data in the literature. Some representative IGBT package simulations that use R134a as the cooling fluid are also presented. (author)

2008-01-15

98

Delta connected resonant snubber circuit  

Energy Technology Data Exchange (ETDEWEB)

A delta connected, resonant snubber-based, soft switching, inverter circuit achieves lossless switching during dc-to-ac power conversion and power conditioning with minimum component count and size. Current is supplied to the resonant snubber branches solely by the dc supply voltage through the main inverter switches and the auxiliary switches. Component count and size are reduced by use of a single semiconductor switch in the resonant snubber branches. Component count is also reduced by maximizing the use of stray capacitances of the main switches as parallel resonant capacitors. Resonance charging and discharging of the parallel capacitances allows lossless, zero voltage switching. In one embodiment, circuit component size and count are minimized while achieving lossless, zero voltage switching within a three-phase inverter.

1998-01-01

99

Honshu-Shikoku linking transmission cable building plan. ; Development of power sources. Honshi renkei sodensen kensetsu keikaku. ; Dengen kaihatsu  

Energy Technology Data Exchange (ETDEWEB)

This paper describes a Honshu-Shikoku linking transmission cable building plan and its technical features. The Chugoku District and the Shikoku District are supplied with power currently by the Chugoku-Shikoku trunk line of 220,000 volts. To cope with the anticipated power shortage, a plan was established to install power cables for 500,000 volts on the Honshu-Shikoku connecting bridge. The plan calls far an installation length of 127.4 km and a transmission capacity of 1.2 million kW per line. The cable installation on the Seto Bridge was completed already, the construction is now in the peak period for building steel towers on the land sections, and laying overhead cables and underground cables. Commencement of the operation is scheduled 1994 on one liner, and 2000 on two lines. The technical features include the Japan's first large-capacity, long-distance underground ...

1992-03-01

100

BOOKMARKS:  

Wastenet

on practical projects such as woodland management, limestone grassland management, cattle management, conflict management and education. ...Cathy Heaton Telephone 01772 892400 Email cenquiries@uclan.ac.uk www.uclan.ac.uk/schoolbne

101

Impact of independent power producers in a deregulated system  

Energy Technology Data Exchange (ETDEWEB)

Independent power producers (IPPs) have had open access to existing power systems ever since the electric power industry was restructured and deregulated. IPPs are small-scale, distributed, and independently operated. Introducing an IPP to the power system can be beneficial to the existing power system because it can increase the security margin or reduce production cost and environmental pollution. The disadvantage is that some IPPs are not subject to dispatch control, consequently, they may reduce the network security. Often IPPs use co-generation, small-scale hydro, even fuel cells or other types of renewable energy sources. An evaluation of IPPs impact on an existing utility power system was determined in a modified IEEE 14 bus system. The total generating cost, environmental impact, transmission line margin, voltage profile, network ...

1997-04-01

102

The European energy market and environmental considerations: Options for Norwegian industry  

Energy Technology Data Exchange (ETDEWEB)

The power industry is undergoing major changes. Deregulation and a competitive climate demand effective solutions. Costs and losses must be reduced, and overall efficiency must be raised. Industrial options connected to energy market and environmental considerations are discussed. Themes discussed in this paper are environmental challenges, the fuel factor, power plants in use today, the Norwegian power system, the European system, power exchange across borders, the transmission system, the future European system, and options for Norwegian industry. 27 figs.

1995-12-31

103

Some reflections on the network power plant interaction  

International Nuclear Information System (INIS)

The layout of the network with its frequency and transmission power control shows how the time behaviour of power plants and consumers determines the frequency curve during sudden power disturbances. As for switching processes in the network for the turbine, network operation entails loads due to shock-like disturbance functions to which one should not normally respond by switching off. The interception controllers are therefore adjusted via a simulation model by which the vibrations of the turbine rotor can be modelled in real time under different network loads. (GL).

1978-11-24

104

Environmental pollution abatement - data acqusition and evaluation by the accounting department. Umweltschutz - Erfassung und Auswertung im Rechnungswesen  

Energy Technology Data Exchange (ETDEWEB)

The booklet presents general information and practical hints for the task of acquiring and evaluating the data describing investments and other expenditure and activities for pollution abatement measures taken by electric utilities. The information is intended as an aid for establishing standard criteria for assignment and evaluation, and for comparison and classification of pollution abatement measures. As a line of orientation, a catalogue of pollution control measures is given, arranged into the following sections: Fossil-fueled power plants; nuclear power plants (BWR and PWR); hydroelectric power plants; power transmission and distribution. (HSCH)

1986-01-01

105

12th Symposium on Space Nuclear Power and Propulsion. Conference on Alternative Power from Space (APFS),Conference on Accelerator-Driven Transmutation Technologies and Applications (A-DTTA)  

International Nuclear Information System (INIS)

These proceedings represent papers presented at the 12th symposium on Space Nuclear Power and Propulsion held in Albuquerque, New Mexico. The symposium theme was ''commercialization and technology transfer''. The topics discussed include: wireless power transmission, solar power from space next generation spacecraft, space power electronics and power management, flight testing of components, manufacturing and processing of materials, nuclear propulsion, reactors and shielding and many others of interest to the scientific community representing industry, government and academic institutions. There were 163 papers presented at the conference and 60 have been abstracted for the Energy Science and Technology database.

1995-01-08

106

Beam direct converter with varying magnetic field  

Energy Technology Data Exchange (ETDEWEB)

The concept of a direct energy recovery system that applies a varying magnetic field is proposed for a negative-ion-based neutral beam injection system (NNB) to heat a plasma and/or drive a plasma current in a fusion reactor. The output beam energy and power of such an NNB will be {approximately}1 MeV and {approximately}1- MW/beam-line, respectively, and nearly the same amounts of positive- and negative-ion beams remain unneutralized in an NNB by using a gas-neutralizing cell. Therefore, the output of a beam direct convertor in an NNB is a bipolar direct current (dc) electric power with close to {plus_minus} 1 MV and several amperes if a conventional electrostatic or magnetostatic field is applied for ion beam separation. However, such high-voltage dc power is difficult to handle at the point of the regeneration of the power back to a commercial electric line because a very high voltage inverter tough ...

1994-12-01

107

Development of a through-the-earth monitor system. Open file report (final) Oct 77-Dec 80  

Energy Technology Data Exchange (ETDEWEB)

The object of this program was to design and build a self-contained system for remote monitoring of the atmosphere in mines. The system developed uses the mine pager phone line as the primary communication channel and also has the capability of using 208 Hz in the ELF band for wireless transmission through the earth. The depth for through-the-earth transmission is expected to be about 80 to 90 meters in high conductivity soil and is limited by the noise level in the ELF band-pass filters. The underground components of the TEM System are energized by mine power through a battery charger-storage battery power supply. In the event of mine power failure the battery capacity is more than sufficient for 1 week's operation with interrogations every 4 hours.

1980-12-01

108

Lightning performance assessment of Hellenic high voltage transmission lines  

Energy Technology Data Exchange (ETDEWEB)

A methodology for assessing the lightning performance of Hellenic high voltage transmission lines has been developed. Its main advantage is that the analysed transmission line is divided into regions and the analysis is conducted separately for each one region, taking into account the individual characteristics, which exist in each one of them. The developed approach intends to offer more accuracy in the assessment of lightning performance of Hellenic high voltage transmission lines and of similar lines, where they run at the same time through a plain region, a coastline and/or a mountainous region. The aims of the paper are to describe in detail the proposed methodology and to present results obtained by its application on operating Hellenic transmission lines of 150 and 400 kV. The computed results are compared with the results produced by another software tool published in the technical literature ...

2008-04-15

109

An optimal design method for improving the lightning performance of overhead high voltage transmission lines  

Energy Technology Data Exchange (ETDEWEB)

This paper presents a method for the optimal design of high voltage transmission lines taking into consideration shielding and backflashover failure rates. The minimization of suitably defined performance indices, which relate the failures caused by lightning in a transmission line to both line insulation level and tower footing resistance, is aimed. Optimum values for both line insulation level and tower footing resistance are calculated. The method is applied on several operating Hellenic transmission lines of 150 and 400kV, respectively, carefully selected among others, due to their high failure rates during lightning thunderstorms. Special attention has been paid on open loop lines, where a possible failure could bring the system out of service causing significant problems. The obtained design parameters, which reduce the failure rates caused by lightning, are compared with the existing design parameters of the ...

2006-04-15

110

Testing modern protective relays  

Energy Technology Data Exchange (ETDEWEB)

Modern microprocessor-based relays for the protection of the various power system components such as generators, transformers, feeders, and high voltage transmission lines are becoming more sophisticated as increasingly more complex functions and capabilities can be included in the microprocessor. With this increasing complexity, and the increasing complexity of the power system itself, there is even more value in testing the suitability of relaying equipment for the intended applications. This paper reviews the testing philosophy, experience, and capabilities developed at Ontario Hydro over more than 25 years of testing protective relays.

1994-01-01

111

Power transmitting fluids containing esters of hydrocarbyl succinic acid or anhydride with thio-bis-alkanols  

Energy Technology Data Exchange (ETDEWEB)

Mineral oil based power transmitting fluids, such as automatic transmission fluids, are disclosed which contain 0.05 to 2.0 weight percent of an ester of a thio-bis alkanol and a C/sub 12/-C/sub 50/ hydrocarbon succinic acid or anhydride, the ester being a multifunctional additive providing the properties of friction modification, corrosion inhibition, anti-wear, oxidation inhibition and extreme pressure properties to the fluids.

1987-10-27

113

Application of artificial neural network methods for the lightning performance evaluation of Hellenic high voltage transmission lines  

Energy Technology Data Exchange (ETDEWEB)

Feed-forward (FF) artificial neural networks (ANN) and radial basis function (RBF) ANN methods were addressed for evaluating the lightning performance of high voltage transmission lines. Several structures, learning algorithms and transfer functions were tested in order to produce a model with the best generalizing ability. Actual input and output data, collected from operating Hellenic high voltage transmission lines, as well as simulated output data were used in the training, validation and testing process. The aims of the paper are to describe in detail and compare the proposed FF and RBF ANN models, to state their advantages and disadvantages and to present results obtained by their application on operating Hellenic transmission lines of 150kV and 400kV. The ANN results are also compared with results obtained using conventional methods and real records of outage rate showing a quite satisfactory agreement. The proposed ...

2007-01-15

114

Secondary stresses on transmission tower structures  

Energy Technology Data Exchange (ETDEWEB)

The power industry is moving toward the use of high-voltage transmission lines on tall, flexible towers. These towers are designed for heavier loadings than were previous towers, but the secondary effects of tower displacement tend to be ignored in the present day tower analysis. This paper examines the secondary effects from the large displacement of flexible towers, reviews the secondary stresses arising from joint rigidity and member continuity, and examines the reliability of tower strength predicted by the ASCE design guidelines. More realistic tower test acceptance criteria and a more reliable tower design methodology are suggested.

1984-06-01

115

MITL - A 2-D code to investigate electron flow through non-uniform field region of magnetically insulated transmission lines  

Science.gov (United States)

Self-magnetically insulated, high-voltage transmission lines are used in inertial confinement fusion particle accelerators in order to transmit power from the vacuum insulator to the diode. This paper describes a time-dependent 2-D code (MITL) for calculating (for planar or triplate geometries) the motion of test electrons through the tapered input or output convolutes of such lines. MITL results show that the electron canonical momentum in the direction of the flow changes as the electron passes through the convoluted geometry; it is suggested that these electrons lead to losses observed in long self-magnetically insulated lines.

1979-01-01

116

Controlled serial compensator for load control and excess-current release. Geregelter Serienkompensator fuer Lastflussregelung und Ueberstrombegrenzung  

Energy Technology Data Exchange (ETDEWEB)

With the compensator-series equipment put into operation in 1992 - giving a performance of 330 Mvar - it was made possible for high-performance electronics to use a continuously variable, fully loaded power transmission line and to regulate the energy flow and minimise overcurrent losses. As well as these technical qualities, this system could offer environmental advantages for European implementation. This would avoid the need to plan and construct new high voltage transmission lines in order to meet increased demand. (orig.)

1994-06-01

117

An assessment of health impacts of electrical power transmission lines  

International Nuclear Information System (INIS)

The types of investigations undertaken to test for possible biological effects of extremely low frequency electric fields have been numerous. However, neither animal and plant experimentation nor clinical studies nor experience with operating extremely high voltage transmission lines have to date provided convincing evidence of a harmful effect from exposure to electric fields associated with transmission lines in spite of numerous attempts to find such effects. Analysis of internal fields and currents supports these observations as the levels appear to be too low to affect mammalian cells. Thus, while one can never prove the negative (i.e. that there is no effect), the overwhelming body of evidence indicates that the electric fields associated with high-voltage lines have no deleterious biological effects. (author).

1981-06-26

118

Status of electric power in the Missouri River Basin  

Energy Technology Data Exchange (ETDEWEB)

This third Missouri River Basin Commission report on Status of Electric Power in the Missouri River Basin provides information on the status of electric power generation, future needs, and potentials for meeting these needs. Information for this 1980 update is based upon available published information up to and including December 31, 1979. State and federal members of the Missouri River Basin Commission provided information for sections of the report and on legislative activities. Information is included on the planning and projected costs of hydro, nuclear and fossil-fuel power plants, pumped-storage plants, transmission systems, projected power demands, the environmental, socio-economic-cultural impacts of electric power generation, and regulations affecting energy development. (LCL)

1980-01-01

119

Industrial experience with an intelligent AC/DC standard  

Energy Technology Data Exchange (ETDEWEB)

AC/DC voltage standards based entirely on solid-state references used as secondary, working, or transfer standards is widespread, although metrological performance is typically defined only via comparison with a higher level standard. The present report shows the improvements of the output metrological characteristics of an ac/dc calibrator by establishing three internal hierarchical levels of dc voltage references and by constant calibration of ac measuring circuits.

1989-04-01

122

Electric field measurement on time domain generated by corona on insulators on distribution systems  

Energy Technology Data Exchange (ETDEWEB)

Radio interference and TV interference are being a problem in urban and rural areas. This interference is generated by high voltage transmission lines as well as distribution lines. The radio noise can be produced by polluted or damaged insulators, and by metal parts of the distribution lines. The corona effect on the surface of the dielectric material produces high frequency electromagnetic fields during the ionization and during the recombination period. Fields of different intensity are produced by positive voltage and negative voltage. The insulator flashover (leaking current) also produces electromagnetic fields. A new technique to measure these fields was developed. This technique measures the radiated fields on time domain and on frequency domain. This permits us to characterize the radiated field and thus identify the type of the source. Several measurements were done varying the type of the RF generator, i.e., new insulator and broken insulator. A ...

1996-12-31

123

Accelerated aging tests of chromium containing amorphous hydrogenated carbon coatings for solar collectors  

Energy Technology Data Exchange (ETDEWEB)

Chromium containing amorphous hydrogenated carbon films (a-C : H/Cr) have been prepared by simultaneous rf plasma activated chemical vapour deposition of methane and magnetron sputtering of a chromium target. During deposition the substrates were heated (up to 300C) and DC biased (-200 and -600 V) in order to obtain films with high chemical stability. Constant temperature tests were performed at 250C in air with coatings deposited on silicon substrates. The degradation of the coatings was monitored by Raman spectroscopy and reflectance and transmission measurements. The main degradation mechanisms are discussed and the relevant parameters which improve the durability of the coatings are presented. Furthermore, the durability of solar selective, multilayered coatings which were deposited on copper sheets was investigated. Based on accelerated aging tests at different temperature loads in air (at 220C, 250C and 300C) and in a humid environment ...

1998-07-13

124

Environmental Assessment of the Gering-Stegall 115-kV Transmission Line Consolidation Project, Scotts Bluff County, Nebraska  

International Nuclear Information System (INIS)

The Department of Energy (DOE), Western Area Power Administration (Western) proposes to consolidate segments of two transmission lines near the Gering Substation in Gering, Nebraska. The transmission lines are both located in Scotts Bluff County, Nebraska. The transmission lines are both located in Scotts Bluff County, Nebraska, within the city of Gering. Presently, there are three parallel 115-kilovolt (kV) transmission lines on separate rights-of-way (ROW) that terminate at the Gering Substation. The project would include dismantling the Archer-Gering wood-pole transmission line and rebuilding the remaining two lines on single-pole steel double circuit structures. The project would consolidate the Gering-Stegall North and Gering-Stegall South 115-kV transmission lines on to one ROW for a 1.33-mile segment between the Gering Substation and ...

1999-05-01

125

Environmental Assessment of the Gering-Stegall 115-kV Transmission Line Consolidation Project, Scotts Bluff County, Nebraska  

Energy Technology Data Exchange (ETDEWEB)

The Department of Energy (DOE), Western Area Power Administration (Western) proposes to consolidate segments of two transmission lines near the Gering Substation in Gering, Nebraska. The transmission lines are both located in Scotts Bluff County, Nebraska. The transmission lines are both located in Scotts Bluff County, Nebraska, within the city of Gering. Presently, there are three parallel 115-kilovolt (kV) transmission lines on separate rights-of-way (ROW) that terminate at the Gering Substation. The project would include dismantling the Archer-Gering wood-pole transmission line and rebuilding the remaining two lines on single-pole steel double circuit structures. The project would consolidate the Gering-Stegall North and Gering-Stegall South 115-kV transmission lines on to one ROW for a 1.33-mile segment between the Gering Substation and ...

1995-05-01

126

Conference on reformation of regulation in OECD/IEA power sector - Conference on reformation of regulation in USA, Netherlands, Japan  

Energy Technology Data Exchange (ETDEWEB)

Since 1995, OECD started to examine the current situation of government regulation in each member country and discussed to recommend quality improvement of regulation to member countries. The conference on reformation of regulation in power industry was held in October and December 1998. In USA, enhancing competition in supplying electricity was recommended by eliminating differentiation in use of power network, transmission network and incidental facilities. The retail competition is also an important reformation. The reformation in Netherlands can be seen as following EU guide for revealing problems of the existing regulation in the power industry and for opening up a power market. The Dutch government passed the power act for opening up a market to the public between 1999 and 2007. In Japan, the entry of independent power provider (IPP) ...

1999-01-01

127

500-kV cable lines  

Energy Technology Data Exchange (ETDEWEB)

A detailed description is given of the design, fabrication, and installation of oil-filled 500-kV cable lines used for the first time in the USSR for transmitting electric power from step-up transformers installed several meters from the hydroelectric generators to an outdoor distribution system or a junction point at which they are connected to overhead power transmission lines. These lines are 950 to 1050 m long and they are placed at levels differing by 45 m along the route. These lines can transmit power as great as 630 MV.A.

1980-01-01

128

Fundamental limits on beam stability at the advanced photon source  

International Nuclear Information System (INIS)

Orbit correction is now routinely performed at the few-micron level in the Advanced Photon Source (APS) storage ring. Three diagnostics are presently in use to measure and control both AC and DC orbit motions: broad-band turn-by-turn rf beam position monitors (BPMs), narrow-band switched heterodyne receivers, and photoemission-style x-ray beam position monitors. Each type of diagnostic has its own set of systematic error effects that place limits on the ultimate pointing stability of x-ray beams supplied to users at the APS. Limiting sources of beam motion at present are magnet power supply noise, girder vibration, and thermal timescale vacuum chamber and girder motion. This paper will investigate the present limitations on orbit correction, and will delve into the upgrades necessary to achieve true sub-micron beam stability.

1998-12-10

129

Development of ambient sampling chemi/chemical ion source with dielectric barrier discharge  

British Library Electronic Table of Contents (United Kingdom)

The development of a new configuration of chemical ionization (CI)-based ion source is presented. The ambient air containing the gaseous sample is sniffed into an enclosed ionization chamber which is of sub-ambient pressure, and is subsequently mixed with metastable species in front of the ion inlet of the mass spectrometer. Metastable helium atoms (He*) are used in this study as the primary ionizing agents and are generated from a dielectric barrier discharge (DBD) source. The DBD is powered by an AC high-voltage supply and the configuration of the electrodes is in such a way that the generated plasma is confined within the discharge tube and is not extended into the ionization chamber. The construction of the ion source is simple, and volatile compounds released from the bulky sample can...

2010-01-01

130

Breathers in Josephson junction ladders: Resonances and electromagnetic wave spectroscopy  

DEFF Research Database (Denmark)

We present a theoretical study of the resonant interaction between dynamical localized states (discrete breathers) and linear electromagnetic excitations (EE's) in Josephson junction ladders. By making use of direct numerical simulations we find that such an interaction manifests itself by resonant steps and various sharp switchings (voltage jumps) in the current-voltage characteristics. Moreover, the power of ac oscillations away from the breather center (the breather tail) displays singularities as the externally applied dc bias decreases. All these features may be mapped to the spectrum of EE's that has been derived analytically and numerically. Using an improved analysis of the breather tail, a spectroscopy of the EE's is developed, The nature of breather instability driven by localized EE's is established.

2001-01-01

131

Population exposure to power-frequency fields: concepts, components, and control  

Energy Technology Data Exchange (ETDEWEB)

There are many sources of population exposures to power-frequency (50/60 Hz) electric and magnetic fields including household appliances and wiring, neighborhood distribution circuits, and high-voltage transmission lines. Bioeffects studies were unable to demonstrate that exposures to power-frequency fields can affect public health. Researcher have likewise been unable to show that the health effects of such exposures are negligible. State and federal regulatory agencies are, therefore, grappling with questions of whether and how to regulate the sitting or design of new extra high-voltage transmission lines so as to control the ground-level fields to which people are exposed. The purpose of this dissertation is to illuminate some of the exposure-related aspects of these question. A taxonomy of the relationship between field encounter and effect is developed to clarify the meaning of terms such as ...

1986-01-01

132

System control and data acquisition of the two new FWCD RF systems at DIII-D  

Energy Technology Data Exchange (ETDEWEB)

The Fast Wave Current Drive (FWCD) system at DIII-D has increased its available radio frequency (RF) power capabilities with the addition of two new high power transmitters along with their associated transmission line systems. A Sun Sparc-10 workstation, functioning as the FWCD operator console, is being used to control transmitter operating parameters and transmission line tuning parameters, along with acquiring data and making data available for integration into the DIII-D data acquisition system. Labview, a graphical user interface application, is used to manage and control the above processes. This paper will discuss the three primary branches of the FWCD computer control system: transmitter control, transmission line tuning control, and FWCD data acquisition. The main control program developed uses VXI, GPIB, CAMAC, Serial, and Ethernet protocols to blend the three branches ...

1995-10-01

133

An artificial neural network for directional comparison relaying of transmission lines  

Energy Technology Data Exchange (ETDEWEB)

Distance protection, differential protection and directional comparison schemes are presently used for protecting transmission lines. Directional comparison relays are set to respond to faults in the protection zone without intentional time delay and are, therefore, used where high-speed fault clearing is needed. Artificial Neural Networks (ANNs) can handle most situations which cannot be defined sufficiently for finding a deterministic solution. The design and testing of an ANN for directional comparison protection of transmission lines are presented in this paper. Training patterns were generated using voltage and current samples for faults at various locations along a transmission line. The faults were simulated using an electromagnetic transient program and a sample three-phase power system. The performance of the proposed discriminator was checked using data simulated for testing and the fault data ...

1997-12-31

134

Utility activities that create power quality problems  

Energy Technology Data Exchange (ETDEWEB)

Power quality problems are caused by activities normal to utility operations such as maintenance outages and capacitor switching or events that are abnormal such as lightning strikes and equipment failures. Disconnection and reconnection of transmission lines and transformers can cause switching surges, and are more severe on extra high voltage transmission lines than high voltage lines. Capacitor switching can cause transients and harmonics that may affect sensitive equipment, and are the source of 3rd, 5th, 7th and 9th harmonics in the hundreds of hertz ranges. Overload, sudden loss of generating capacity and transmission line faults are typical problems affecting system stability. Fault interruptions and reclosings can cause surges in the distribution system, and lightning strikes may cause voltage surges or dips due to arrester sparkover. Blackouts, brownouts, voltage fluctuations, travelling wave ...

1992-02-01

135

Outlook for using wind energy for electrification of agriculture in Estonian SSR  

Energy Technology Data Exchange (ETDEWEB)

The developed electrical networks in the agricultural regions of the Estonian SSR make it possible to construct relatively powerful wind power plants at the sites of the most favorable wind conditions with small outlays for the power transmission lines. The wind power plant electricity can be used to electrify the production processes in agriculture, while the surplus can be supplied to the energy system. The inclusion of the wind power plants in the energy system makes it possible to improve the total generation of energy or reduce the consumption of fuel. With the efficient arrangement of the wind power plants, one can also reduce the energy losses during its transfer. Calculations indicated that in the coastal zones of the Estonian SSR, one can obtain specific power of 420-480 kW/km/sup 2/. For comparison it is ...

1982-01-01

136

Design of power system stabilizer through state variable feedback  

Energy Technology Data Exchange (ETDEWEB)

When the transmission line is very long or the generator is operated at a power factor nearly equal to 1.0, the machine regulated by an automatic voltage regulator (AVR) cannot be operated stably due to poor dynamic stability. To overcome this difficulty, the so called power system stabilizer (PSS) is very useful, in that output power or rotor speed of the generator is used as a feedback signal. The primary obective of the PSS is to damp the swing of the generator as quickly as possible. A method is proposed for designing PSS which yields a given eigenvalue. In the second method, the use of a Heffron-Phillips model is discussed. Next, a detailed procedure for the proposed design method is presented. A generalized method of a PSS design based on Park's equation and matrix operation is proposed.

1980-05-01

137

Upgrading the ampacity of HPFF pipe-type cable circuits  

Energy Technology Data Exchange (ETDEWEB)

The upgrading of several 69 kV pipe-type cable feeders on the Potomac Electric Power Company (PEPCo) transmission cable system is discussed. The methods used for the ampacity calculation are described. The fluid circulation approach required to meet the feeder emergency load requirements are discussed. For the feeders that were in service for approximately 40 years, a system life evaluation was performed.

1994-12-31

138

Report of the Committee on Electric Utility Regulation  

Energy Technology Data Exchange (ETDEWEB)

In 1991 the Federal Energy Regulatory Commission (FERC) continued it efforts to restructure the electric utility industry, emphasizing market-based pricing of wholesale power transactions and transmission access and pricing. Other issues covered in this report include pricing and policy initiatives, filing procedures, the generic rate of return on common equity, the price squeeze, contract interpretation, and legislative developments.

1992-01-01

139

Pumping manual/7th edition  

Energy Technology Data Exchange (ETDEWEB)

This book includes the latest developments and covers pump performance, selection and operations, materials, seals and packings, effective fluid characteristics, filtration, piping systems, economics, valves, instrumentation, automatic controls, power transmission equipment, pump and pipeline heating, and more. An extensive data section contains formulas, charts, symbols, nomographs, and standard specification documents.

1984-01-01

140

Nuclear power plants and the ''dying forests''  

International Nuclear Information System (INIS)

Possible causes of forest damage are discussed. Mapping of affected areas by various workers resulted in dissimilar pictures. Release of radioactive rare gases, aerosols, tritium and carbon-14 seems unlikely to have a significant influence on forest damage. Influence of radioactive fallout, ozone formation by high-voltage transmission lines and synergistic effects is also found to be negligible.

1985-01-01

141

HVDC submarine cables for the Hokkaido Honshu linkage  

Energy Technology Data Exchange (ETDEWEB)

The direct-current submarine cable interconnecting Hokkaido and Honshu (hereafter called HH linkage) is an example of installation of an undersea cable for long-distance power transmission crossing a sea strait. In particular, the feature of this interconnection is that an oil-filled (OF) cable is used for the high-voltage side with crosslinked polyethylene (XPLE) cable adopted for the return to comprise a conductor return system. The details of the facilities, especially the design of the OF submarine cable are described. 3 refs.

1981-04-01

142

Environmentally inoffensive electric drive for the VW Golf  

Energy Technology Data Exchange (ETDEWEB)

Electric cars run silently and produce no exhaust fumes. In cooperation with other companies BBC has developed a compact drive system for the VW Golf comprising a battery-powered separately excited DC motor, transmission, control system and setpoint devices. With a range of 57 km and a top speed of 90 km/h, the electric Golf lends itself well to city driving.

1981-01-01

143

DOE supports market-based pricing in case before FERC  

Energy Technology Data Exchange (ETDEWEB)

The Department of Energy has used its seldom-used statutory authority and filed comments with the Federal Energy Regulatory Commission urging support for Public Service Company of Indiana's request that the FERC allow it to sell up to 450 megawatts of firm power to eligible wholesale purchasers at negotiated or market-based rates in exchange for open transmission access for other generators.

1990-04-12

144

Corona effect in high voltage transmission lines; O efeito corona em linhas eletricas aereas de alta-tensao  

Energy Technology Data Exchange (ETDEWEB)

Corona from bare conductors of electrical overhead power lines is studied in this article. Its origin, as well as, its bad influences over communication systems are both studied, yet. Line`s models are defined, in order to be able the examination of Corona on line`s cables. Formulas for the surface electrical gradient calculations are shown. (author) 2 refs.

1993-12-01

145

Biological effects of extremely low frequency (ELF) electromagnetic fields: a perspective on the issues  

Energy Technology Data Exchange (ETDEWEB)

This apper discusses whether health risks are associated with exposure to electromagnetic fields that exist beneath high-voltage transmission lines. This is a question receiving increasing attention as the electric utility industry prepares to supply its customers with increased amounts of electric power. 26 refs.

1980-01-01

146

Biological effects from electric fields associated with high voltage transmission lines  

Energy Technology Data Exchange (ETDEWEB)

Efforts during the past year by the US Department of Energy and the Electric Power Research Institute-funded laboratories to investigate the biological effects from electric fields are described in resume form. Investigations generally have been summarized with objectives, accomplishments of the past year, and some indication of projected studies.

1983-11-01

147

Optimal pole shifting controller for interconnected power system  

Energy Technology Data Exchange (ETDEWEB)

Research highlights: {yields} Mathematical model represents a power system which consists of synchronous machine connected to infinite bus through transmission line. {yields} Power system stabilizer was designed based on optimal pole shifting controller. {yields} The system performances was tested through load disturbances at different operating conditions. {yields} The system performance with the proposed optimal pole shifting controller is compared with the conventional pole placement controller. {yields} The digital simulation results indicated that the proposed controller has a superior performance. -- Abstract: Power system stabilizer based on optimal pole shifting is proposed. An approach for shifting the real parts of the open-loop poles to any desired positions while preserving the imaginary parts is presented. In each step of this approach, it is required to solve a first-order or a ...

2011-05-15

148

Optimal pole shifting controller for interconnected power system  

International Nuclear Information System (INIS)

Research highlights: ? Mathematical model represents a power system which consists of synchronous machine connected to infinite bus through transmission line. ? Power system stabilizer was designed based on optimal pole shifting controller. ? The system performances was tested through load disturbances at different operating conditions. ? The system performance with the proposed optimal pole shifting controller is compared with the conventional pole placement controller. ? The digital simulation results indicated that the proposed controller has a superior performance. -- Abstract: Power system stabilizer based on optimal pole shifting is proposed. An approach for shifting the real parts of the open-loop poles to any desired positions while preserving the imaginary parts is presented. In each step of this approach, it is required to solve a first-order or a second-order linear matrix Lyapunov equation ...

2011-05-01

149

Submarine 525 kV power transmission line for Vancouver island  

Energy Technology Data Exchange (ETDEWEB)

The studies undertaken by the B.C. Hydro company at the Canada showed that the existing system of hydroelectric power plants and transport cables will not be able to satisfy the increasing energy demand on the Vancouver island after 1985, and that the best solution will be the installation of a 525 kV transfer system from the continent. THe STK participated to the development and the immersion of this new system, the first in the world comprising submarine 525 kV transport parts. This paper presents the planning, the development, the submerging and the installation of two sections of submarine cable.

1985-01-01

150

News from the world; Echos du monde  

Energy Technology Data Exchange (ETDEWEB)

This document gathers a series of very short articles concerning nuclear industry around the world. Areva company is investing 30 million euros in its Chalon-Saint-Marcel plant, it is the consequence of the extension of service life of nuclear power plants in the Usa. Areva holds 40% of the American market concerning the replacement of steam generators and 50% of that concerning the replacement of closure heads. The Obrigheim nuclear power plant was definitely closed down on may 2004, this decommissioning is a step forward in the German policy of progressively stepping out of nuclear energy. Chinese authorities are willing to construct 40 nuclear reactors in 15 years, despite that, the contribution of nuclear energy to the generation of electricity will reach only 4% in 2020. In 2007 Cea will begin the construction works of a new research reactor (Jules Horowitz reactor) in the Cadarache site. Prices of the yellow cake have been going up during ...

2005-04-01

151

High-efficiency RF suppression circuit for fluorescent lamp inverters using charge pump and partial smoothinf capacitors; Chagi ponpu shiki korikiritsu bubun heikatsu hoshiki wo mochiita keikoto inbatayo kochoha teigen kairo  

Energy Technology Data Exchange (ETDEWEB)

A highly efficiency partial smoothing method is proposed to be used for inverters for 40W class household fluorescent inverters. In this system, the input current from the commercial AC power source is accumulated in a capacitor with comparatively small capacity as the electric charge, and then the lamp circuit is driven by the inverter utilizing the charging voltage of the capacitor and the charging voltage of the separately prepared partial smoothing capacitor. By this method, the RF harmonic components in the supply current can be decreased to improve the power factor with no complicated feedback controlling device. In addition, comparatively small capacity coils and capacitors can be used. The structure of the circuit and the operation of this proposed method are described, and the operational characteristic of the prototype circuit and the result of analysis are shown. Furthermore, problems and improving method of the ...

1997-06-20

152

SBNE-Cover1  

Wastenet

on practical projects such as woodland management, limestone grassland management, cattle management, conflict management and education. ...Cathy Heaton Telephone 01772 892400 Email cenquiries@uclan.ac.uk www.uclan.ac.uk/schoolbne

153

Chromosomal damage in human lymphocytes from radio-isotope therapy  

International Nuclear Information System (INIS)

(Dec 1973). United Kingdom Stevenson, AC Medical Research Council, Oxford

154

AC.MDM3 - NAIF  

Science.gov (United States)

... }wtv{tv|l^\\h xuwxsqs |qhlnnusnvsqvwzvsrsstrpokfb`ba`]chc][TSWg nkjsrkjkdcenz |{|{{{w khghfbddkmhkljnkeexhgrnimppqsovr|umnmgloplqqqv ~soljowwvvt{|rsuqtp ...

155

Evaluation of a Superconducting Fault Current Limiter Model for Electric Power System  

Science.gov (United States)

Fault current limiters (FCLs) are devices for to suppress current in electric power system. The FCL is extensively expected to suppress fault current, particularly required for trunk power systems heavily connected high-voltage transmission lines, such as 500 kV class power system. For this reason, FCLs based on various principles of operation have been developed. Most of the FCLs under development which employ superconductors are based on the quenching phenomenon peculiar to the superconducting state, that is, making use of a rapid transition to normal conducting state, an electrical resistance appears, and this resistance is used to suppress fault currents. However, this elevation of resistance, although increasing the fault current suppression effect, also tend to raise the overvoltage occurring FCL, the ascertainment of the overvoltage is important as regards the protection of the FCL as well as ...

2003-01-01

156

Environmental impacts of nuclear and coal-fired power plants  

International Nuclear Information System (INIS)

The current situation in the development of nuclear power in the world and in Czechoslovakia is briefly outlined and the possibilities are discussed of alternative energy resources. The environmental impact is described of conventional power plants firing coal; sulphur and nitrogen oxides are mentioned and their environmental impacts shown. Their quantities and the quantities of other gaseous, liquid and soid wastes produced by coal power plants are given. Annual estimates are presented of radioactive material emissions; trace amount emissions of toxic metals and their ecological risks are shown. Concern over the increasing concentration of CO_2 in the atmosphere is voiced. For nuclear power plants, the amount of radionuclides in stack emission and of those released into water flows is tabulated. Their effect on the aqueous ecosystem is characterized as is thermal pollution of water flows and the ...

1984-01-01

157

Evaluation of improvements in the installation of rural underground transmission lines: Final report  

Energy Technology Data Exchange (ETDEWEB)

This report presents the results of an investigation into currently used methods for installation of underground high voltage power transmission cable, and offers recommendations for potentially improving these methods. Suggested enhancements cover the emplacement of both high pressure oil filled (HPOPT) pipe type and self contained oil filled (SCOF) cable systems. Cost comparisons of conventionally installed cable systems versus systems using proposed techniques and equipment are developed for a specific site selected for study. The report also documents the test results of laboratory experiments conducted to demonstrate the feasibility of using interference fit pipe couplings in place of welded pipe joints. 10 refs., 31 figs., 15 tabs.

1987-10-01

158

Electrotransmission of high traffic capability. Elektroperedachi povyshennoi propusknoi sposobnosti  

Energy Technology Data Exchange (ETDEWEB)

Comparative indices are given for the efficiency of phase control of remote-controlled self-compensating high-voltage transmission lines, including a consideration of the power transfer effect between high-voltage line circuits. A description is given of certain circuit variations for performing the technical means of regulating phase shift, and their characteristics which make it possible to evaluate the effect of the phase regulators on the electrical transmission system are also given. An examination is made of problems concerned with the design of lines, relay protection, computation of transfer processes and dynamic stability as well as the computation of over-voltage when shutting off short circuits during amplified electromagnetic ties between line circuits.

1981-01-01

159

Detect and classify faults using neural nets  

Energy Technology Data Exchange (ETDEWEB)

The analysis of transmission line faults is essential to the proper performance of the power system. It is required if protective relays are to take the appropriate action and in monitoring the performance of relays, circuit breakers, and other protective and control elements. The detection and classification of transmission line faults is a fundamental component of such fault analysis. Another application of fault analysis is in software packages for automated analysis of digital fault recorder (DFR) files. Recently, such a package, called DFR Assistant, was developed for substation applications. This program can be installed locally in a substation, in which case it is connected directly to the DFR via a high speed parallel link, or it can be installed at a central station, in which case it can be configured to automatically analyze events coming from all DFRs.

1996-10-01

160

Adaptation of an air-dielectric RF cable for use as an oil-filled high voltage pulse transmission line  

Energy Technology Data Exchange (ETDEWEB)

This paper describes the specifications, conceptual design, prototype testing and operating experience of an oil-filled high voltage pulse transmission cable adapted from commercially available air-dielectric RF components. Lawrence Livermore National Laboratory's Advanced Test Accelerator (ATA) requires a method of transmitting 250kV, 70 nanosecond pulses from the power conditioning equipment to the accelerator. The oil-filled cable approach was chosen over alternative concepts because of its high voltage holding capacity, long life and flexibility. The criteria for cable and connector design are discussed. The results of prototype testing and performance of the final design are presented.

1984-11-01

161

Development of a HVDC prototype breaker. Final report  

Energy Technology Data Exchange (ETDEWEB)

The significant design features of a high-voltage dc (HVDC) circuit breaker based on the commutation concept were developed. Tests of components indicate the breaker is capable of interrupting a fault current of 10 kA on a 400 kV system and absorbing up to 10 MJ of system energy without generating more than 1.6 per unit (P.U.) voltage of the system. Interactions of the breaker with a three-terminal network were studied, using a system simulator. An ultrafast hydraulic actuator system was developed for this program which enables the breaker to initiate the current limiting process within 5 ms after receipt of a trip signal. A new hydraulic valve, operated by a repulsion coil, minimizes the delay before motion begins. Interruption will occur in series-connected vacuum interrupters. A 400 kV circuit breaker is estimated to require eight breaks in series. Only a single break was tested as part of this program because of the scale and cost required for multibreak tests. System energy will ...

1980-06-01

162

Wind power data transmission challenges; Les defis de la transmission de donnees en eolien  

Energy Technology Data Exchange (ETDEWEB)

This presentation outlined the corporate history of the Ohmega Group, a small company from Gaspe, Quebec which offers consulting services to the automation and telecommunication sector. It was created in 1982 and has been involved with the wind power industry since 1996. The main services provided by Ohmega Group include electrical and mechanical construction and maintenance services. This paper also reviewed the benefits of using Supervisory Control and Data Acquisition (SCADA) systems in the wind power industry to monitor, control and collect data from wind turbines. The Ohmega Group has provided consulting services to Cartier Wind Energy Inc., a company that was awarded several wind turbine projects by Hydro-Quebec Distribution. The Ohmega Group applied the SCADA system at the Baie des Sables, Anse a Valleau and Carleton wind turbine arrays. The typical architecture of SCADA systems on a wind farm was presented along with ...

2008-07-01

163

Power line fault current coupling to nearby natural gas pipelines: Volume 1, Analytic methods and graphical techniques: Final report. [Electromagnetic and Conductive Coupling Analysis of Powerlines and Pipelines (ECCAPP)  

Energy Technology Data Exchange (ETDEWEB)

A generalized approach to the analysis of the effects of transmission line faults on natural gas transmission pipelines has been developed and is presented in this report. A state of the art user-friendly computational tool has been developed and verified for the analysis of interference between electrical power lines and nearby buried or above-ground pipelines. This computer program, ECCAPP, is distinguished by its ability to model and analyze accurately complex, realistic interactions between pipelines and power lines, using easily obtained input data. The final report consists of three volumes. An independent fourth volume was also developed to simplify the installation of the ECCAPP software. This report, volume 1, contains the theory upon which the ECCAPP computer program is based. A parametric analysis and graphical charts have been formulated using ECCAPP to permit estimates to be made in the ...

1987-11-01

164

Point and transfer mobility of point-connected ribbed plates  

Science.gov (United States)

The work reported in this paper addresses the problem of structure-borne sound transmission between vibrating sources and ribbed-plate receiver structures. Vibrating sources, such as pumps, motors, fans, etc., transmit vibro-acoustic power, causing noise complaints by occupants in cars, trains, aircraft, buildings and/or material fatigue and damage. The transmission process is complicated in that sources transmit power through several contacts and by up to six components of excitation at each contact. The structure-borne sound power is a function of source activity, source mobility and receiver mobility, and all three quantities must be known to some degree. For non-homogeneous receiver structures, such as thin-plate cavity constructions or lightweight framed constructions, the sheathing plates are typically fastened to the framing members using bolts, screws or spot-welded joints. ...

2011-09-01

165

Performance of distance relays in a 150 kV grid in case of cross-country faults. Gedrag van distantiebeveiligingen in een 150 kV-net bij cross-country fouten  

Energy Technology Data Exchange (ETDEWEB)

In the 150 kV power system of the Dutch energy utility MEGA Limburg cross-country faults have caused problems in the protection of high voltage transmission lines. A cross-country fault is the simultaneous presence of two single-phase earth connections in different phases and places within the grid. These cross-country faults can lead to the incorrect operation of a number of distance relays, which could result in the faulty disconnection of high voltage transmission lines. To gain an insight into these problems, the transient phenomenon in the power system during cross-country faults were studied. For this purpose, the simulation program EMTP (ElectroMagnetic Transients Program) has been used. Simulation models of the 150 kV power system and the measuring system of a distance relay were developed within EMTP. 7 figs., 1 ill.

1994-11-01

166

Bonneville Power Administration, Office of Engineering 10-Year Plan, 1992-2001 : Draft.  

Energy Technology Data Exchange (ETDEWEB)

For over 50 years, the Bonneville Power Administration (BPA) has evolved to supply electric power to more than 170 customer utilities and direct service industries across 14,800 miles of high voltage transmission lines. BPA's Office of Engineering provides the planning, development, and engineering for the required expansion, upgrade, and replacement of the transmission system. The purpose of this 10-Year Plan is to present strategies to maintain a reliable energy delivery system within changing public, business, technological, and environmental climates. The issues and trends discussed in this document and our strategies for addressing them provide the background for the Office of Engineering programs and projects. With a budget in the hundreds of millions annually and increasing public concern, we welcome the opportunity to communicate with our customers. In addition to the factors, trends ...

1992-05-01

167

Bonneville Power Administration, Office of Engineering 10-Year Plan, 1992-2001 : Draft.  

Energy Technology Data Exchange (ETDEWEB)

For over 50 years, the Bonneville Power Administration (BPA) has evolved to supply electric power to more than 170 customer utilities and direct service industries across 14,800 miles of high voltage transmission lines. BPA`s Office of Engineering provides the planning, development, and engineering for the required expansion, upgrade, and replacement of the transmission system. The purpose of this 10-Year Plan is to present strategies to maintain a reliable energy delivery system within changing public, business, technological, and environmental climates. The issues and trends discussed in this document and our strategies for addressing them provide the background for the Office of Engineering programs and projects. With a budget in the hundreds of millions annually and increasing public concern, we welcome the opportunity to communicate with our customers. In addition to the factors, trends and issues ...

1992-05-01

168

Telephone Flat Geothermal Development Project Environmental Impact Statement Environmental Impact Report. Final  

Energy Technology Data Exchange (ETDEWEB)

This Final Environmental Impact Statement and Environmental Impact Report (Final EIS/EIR) has been prepared to meet the requirements of the National Environmental Policy Act (NEPA) and the California Environmental Quality Act (CEQA). The Proposed Action includes the construction, operation, and decommissioning of a 48 megawatt (gross) geothermal power plant with ancillary facilities (10-12 production well pads and 3-5 injection well pads, production and injection pipelines), access roads, and a 230-kilovolt (kV) transmission line in the Modoc National Forest in Siskiyou County, California. Alternative locations for the power plant site within a reasonable distance of the middle of the wellfield were determined to be technically feasible. Three power plant site alternatives are evaluated in the Final EIS/EIR.

1999-02-01

169

Surface changes on LiNi{sub 0.8}Co{sub 0.2}O{sub 2} particles during testing of high-power lithium-ion cells.  

Energy Technology Data Exchange (ETDEWEB)

LiNi{sub 0.8}Co{sub 0.2}O{sub 2} particles from high-power lithium-ion cells were examined to determine material changes that result from accelerated aging tests. X-ray absorption spectroscopy (XAS) and transmission electron microscope (TEM) data indicated a Li{sub x}Ni{sub 1-x}O-type layer on the particle surfaces. The greater thickness on particles from high-power fade cells indicate that these surface layers are a significant contributor to cathode impedance rise observed during cell tests.

2002-08-01

170

Satellite power system (SPS) concept definition study (Exhibit D). Volume 2: systems/subsystems analyses. Final report  

Energy Technology Data Exchange (ETDEWEB)

Modifications to the reference concept were studied and the best approaches defined. The impact of the high efficiency multibandgap solar array on the reference concept design is considered. System trade studies for several solid state concepts, including the sandwich concept and a separate antenna/solar concept, are described. Two solid state concepts were selected and a design definition is presented for each. Magnetrons as an alternative to the reference klystrons for dc/rf conversion are evaluated. System definitions are presented for the preferred klystron and solid state concepts. Supporting systems are analyzed, with major analysis in the microwave, structures, and power distribution areas. Results of studies for thermal control, attitude control, stationkeeping, and details of a multibandgap solar cell study are included. Advanced laser concepts and the meteorological effects of a laser beam power transmission ...

1981-01-01

171

Assessment of information impacts in power system security against malicious attacks in a general framework  

International Nuclear Information System (INIS)

In the analysis of power systems security, recently a new concern related to possible malicious attacks caught much attention. Coordination among different transmission system operators (TSO) in an interconnected power system to counteract such attacks has become an important problem. This paper presents a general framework for describing the physical, cyber and decision-making aspects of the problem and their interrelations; within this framework, an analytic tool for the assessment of information impacts in handling on-line security after a malicious attack is proposed and discussed. The model is based on the socially rational multi-agent systems and the equilibrium of a fictitious play is considered to analyze the impacts of various levels of information available to the interconnected system operators on the outcomes of the decision-making process under attack. A 34-buses test system, with 3 systems interconnected by ...

2009-06-01

172

Analysis of even harmonics generation in an isolated electric power system  

British Library Electronic Table of Contents (United Kingdom)

Harmonics bred from loads are mainly odd order because the current waveforms have half-wave symmetry. Since the even harmonics are negligibly small, they generally are not measured in electric power systems. However, even harmonics were measured at a 500/275/154 kV substation in Hokuriku Electric Power Company after a transmission line fault was corrected. The even harmonics caused malfunctions of protective digital relays because the relays used 4th harmonics at the input filter as the automatic supervisory signal. This paper describes mechanisms of generation of the even harmonics by comparing the measured waveforms with the ATP-EMTP simulation results. Analysis of these results has clearly shown that there are three different mechanisms of generation of even harmonics. The first mechani...

2009-01-01

173

An Energy-Efficient Resource Allocation Scheme for Mobile Ad Hoc Computational Grids  

British Library Electronic Table of Contents (United Kingdom)

Due to recent advancements in mobile computing and communication technologies, mobile ad hoc computational Grids are emerging as a new computing paradigm, enabling innovative applications through sharing of computing resources among mobile devices without any pre-existing network infrastructure. Energy-efficient resource allocation is one of the key issues in mobile ad hoc computational Grids due to limited battery life of mobile nodes. To reduce energy consumption, we propose a hybrid power-based resource allocation scheme for allocation of interdependent tasks to nodes within mobile ad hoc computational Grid. The basic idea is to exploit dependencies and task type, and allocate interdependent tasks to nodes accessible at minimum transmission power. We also propose a power-based algorithm...

2011-01-01

174

Abstracts of recent reports: Maryland power plant research program 1992 through 1997  

Energy Technology Data Exchange (ETDEWEB)

The goals of the program include predicting the impact of proposed new generating facilities, evaluating proposed high voltage transmission lines, assessing the impact of existing generating facilities, forecasting future demand for electric power, and investigating numerous information gaps through a long-range research program. The Power Plant Assessment Division (PPAD) is responsible for all PSC licensing support, site specific research, and radiological monitoring. The list of reports summarizes information of over 190 technical publications that represent the Program`s formalized research and monitoring efforts over the last five years. Reports are listed in chronological order by topical heading.

1997-12-01

175

Energy saving dc-dc converter circuit  

Energy Technology Data Exchange (ETDEWEB)

An energy saving dc-dc converter circuit is disclosed having two energy efficient means which operate in tandem, an energy conserving means and a voltage doubling means. These energy efficient means are applied in combination with elements commonly found in dc-dc converter circuits, namely an ac voltage generator, a transformer for stepping up the generated ac voltage, and means for storing the converted dc voltage. The energy conserving means is connected to the dc voltage storage means. It comprises a resettable inhibit circuit which cuts off the provision of dc voltage for conversion for a predetermined interval when the output of the converter exceeds a predetermined level. The voltage doubling means is reponsive to outputs of the inhibit circuit of the energy conserving means and the ac voltage generator. It provides a phase inverted waveform of the generated ac voltage on one of two leads to the ...

1982-06-22

176

The market potential for SMES in electric utility applications. Final report  

Energy Technology Data Exchange (ETDEWEB)

Superconducting magnetic energy storage (SMES) is an emerging technology with features that are potentially attractive in electric utility applications. This study evaluates the potential for SMES technology in the generation, transmission, distribution, and use of electric energy; the time frame of the assessment is through the year 2030. Comparisons are made with other technology options, including both commercially available and advanced systems such as various peaking generation technologies, transmission stability improvement technologies, and power quality enhancement devices. The methodology used for this study focused on the needs of the market place, the capabilities of S and the characteristics of the competing technologies. There is widespread interest within utilities for the development of SMES technology, but there is no general consensus regarding the most attractive size. Considerable uncertainty exists ...

1994-06-01

177

Characterization of carbon-based electrochemical capacitor technology from Maxwell Energy Products, Inc.  

Energy Technology Data Exchange (ETDEWEB)

The electrochemical capacitor devices described in this report were deliverables from the US Department of Energy--Idaho Operations Office (DOE-ID) Contract No. DE-AC07-92ID13404 as part of the US Department of Energy`s (DOE) High Power Energy Storage Program. The Idaho national Engineering and Environmental Laboratory (INEEL) has responsibility for technical management, testing, and evaluation of high-power batteries and electrochemical capacitors under this Program. The DOE has developed various electrochemical capacitors as candidate power assist devices for the Partnership for a New Generation of Vehicles (PNGV) fast response engine requirement. This contract with Maxwell Energy Products, Inc. (Maxwell) was intended to develop a high-energy-density, high-power-density ultracapacitor that is capable of load leveling batteries in electric vehicles. The performance criteria for ...

1998-04-01

178

50 Hz - electromagnetic fields. Regulations concerning non-ionizing radiation; 50 Hz-Magnetfelder. Gesetzgeberische Moeglichkeiten auf dem Gebiet der nichtionisierenden Strahlung und Handlungsprogramme in Schweden  

Energy Technology Data Exchange (ETDEWEB)

As a central supervision authority the National Electrical Safety Board (Elsaekerhetsverket) has the main responsibility for the safety of high voltage power lines and other power electric equipment. It is therefore also responsible for questions concerning the effects of power frequency magnetic fields on the environment. According to the rules it is not allowed to draw overhead power lines with a voltage exceeding 1000 V above buildings. Their minimum distance to buildings must not be below 5 m. For regions comprised by rural development plans the directions prescribe a minimum distance of 10 m between buildings and high voltage transmission lines with a voltage of 55 kV or more. The publication of two large epidemiological studies about exposure to magnetic fields and cancer in Sweden in autumn 1992 has brought magnetic fields problems to general notice again. A statement on ...

1993-06-01

179

Synchronized sampling improves fault location  

Energy Technology Data Exchange (ETDEWEB)

Transmission line faults must be located accurately to allow maintenance crews to arrive at the scene and repair the faulted section as soon as possible. Rugged terrain and geographical layout cause some sections of power transmission lines to be difficult to reach. In the past, a variety of fault location algorithms were introduced as either an add-on feature in protective relays or stand-alone implementation in fault locators. In both cases, the measurements of current and voltages were taken at one terminal of a transmission line only. Under such conditions, it may become difficult to determine the fault location accurately, since data from other transmission line ends are required for more precise computations. In the absence of data from the other end, existing algorithms have accuracy problems under several circumstances, such as varying switching and loading conditions, fault ...

1995-04-01

180

Identification and characterization of populations living near high-voltage transmission lines: A pilot study  

Energy Technology Data Exchange (ETDEWEB)

Populations living close to high-voltage transmission lines often have residential magnetic field exposures in excess of 1 [mu]T, and sometimes over 2 [mu]T. Yet, populations studied in most epidemiologic investigations of the association between residential magnetic field exposure and cancer typically have exposures below 1 [mu]T and frequently below 0.5 [mu]T. To improve statistical power and precision, it would be useful to compare high exposure populations with low exposure population. Toward this end, we have developed an automated method for identifying populations living near high-voltage transmissions lines. These populations likely have more highly exposed individuals that the population at large. The method uses a geographic information system (GIS) to superimpose digitized transmission line locations on U.S. Census block location data and then extract relevant demographic data. Analysis of ...

1993-12-01

181

Serviceability of steam generators at NPPs with reactors of the WWER-440 and WWER-1000 types  

Energy Technology Data Exchange (ETDEWEB)

Steam generators (SG) are the weak link of nuclear power plants, their service life is shorter than the service life of other NPP components. This paper is dedicated to a statistical analysis of SG damages and failures. Heat exchanging tubes (HET) are the most damaged elements in SG, there are on average 286 plugged or repaired tubes in each operating SG. The usually mechanisms of tube failure are the following: denting, corrosion at tube outside, pitting, fretting, and circular crack propagation. Most of damages are located in the transition zone above a tube plate. This study shows that the factors that are involved in the SG HET fault probability are: - design features of SG and secondary equipment elements (high pressure feed heaters (HPFH), low pressure feed heater (LPFH)), - water chemistry at different points of condensate feed pipe, composition and density of deposits on HET surface, efficiency of mechanical and chemical washing, - the physical and chemical ...

2002-07-01

182

Design of an onboard battery charger for an electric vehicle  

Energy Technology Data Exchange (ETDEWEB)

This report describes the design of an on-board battery charger for an electric car. There are already various battery charger units on the market. However, these are not specifically designed for this application, and consequently do not provide an ideal solution. Because these products are not specific to one application, and instead opt to cover a variety of briefs, they are not ideal. They also tend to be heavier and more expensive than if the charger was built specifically for one purpose. The main design considerations were that the charger should be compact and lightweight. It was also specified that the design should be able to operate using either the single-phase or three-phase AC supply. Before the design process for the battery charger could commence, it was necessary for the author to get an appreciation of power electronics, since he had no previous experience in the subject. The author focused his attention on areas of the ...

2001-07-01

183

Solutions to defect-related problems in implanted silicon by controlled injection of vacancies by high-energy ion irradiation  

Energy Technology Data Exchange (ETDEWEB)

Amorphization and a dual implant technique have been used to manipulate residual defects that persist following implantation and post-implant thermal treatments. Residual defects can often be attributed to ion-induced defect excesses. A defect is considered to be excess when it occurs in a localized region at a concentration greater than its complement. Sources of excess defects include spatially separated Frenkel pairs, excess interstitials resulting from the implanted atoms, and sputtering. Preamorphizing prior to dopant implantation has been proposed to eliminate dopant broadening due to ion channeling as well as dopant diffusion during subsequent annealing. However, transient-enhanced diffusion (TED) of implanted boron has been observed in pre-amorphized Si. The defects driving this enhanced boron diffusion are thought to be the extended interstitial-type defects that form below the amorphous-crystalline interface during implantation. A dual implantation process was applied in an ...

1999-06-01

184

Solutions to defect-related problems in implanted silicon by controlled injection of vacancies by high-energy ion irradiation  

International Nuclear Information System (INIS)

Amorphization and a dual implant technique have been used to manipulate residual defects that persist following implantation and post-implant thermal treatments. Residual defects can often be attributed to ion-induced defect excesses. A defect is considered to be excess when it occurs in a localized region at a concentration greater than its complement. Sources of excess defects include spatially separated Frenkel pairs, excess interstitials resulting from the implanted atoms, and sputtering. Preamorphizing prior to dopant implantation has been proposed to eliminate dopant broadening due to ion channeling as well as dopant diffusion during subsequent annealing. However, transient-enhanced diffusion (TED) of implanted boron has been observed in pre-amorphized Si. The defects driving this enhanced boron diffusion are thought to be the extended interstitial-type defects that form below the amorphous-crystalline interface during implantation. A dual implantation process was applied in an ...

1999-06-01

185

Boron depth profiles and residual damage following rapid thermal annealing of low-temperature BSi molecular ion implantation in silicon  

Energy Technology Data Exchange (ETDEWEB)

The influence of substrate temperature on both the implantation and post-annealing characteristics of molecular-ion-implanted 5 x 10{sup 14} cm{sup -2} 77 keV BSi in silicon was investigated in terms of boron depth profiles and damage microstructures. The substrate temperatures under investigation consisted of room temperature (RT) and liquid nitrogen temperature (LT). Post-annealing treatments were performed using rapid thermal annealing (RTA) at 1050 deg, C for 25 s. Boron depth profiles and damage microstructures in both the as-implanted and as-annealed specimens were determined using secondary ion mass spectrometry (SIMS) and transmission electron microscopy (TEM), respectively. The as-implanted results revealed that, compared to the RT specimen, the LT specimen yields a shallower boron depth profile with a reduced tail into the bulk. An amorphous layer containing a smooth amorphous-to-crystalline (a/c) interface is evident in the LT ...

2007-08-15

186

Multi-objective optimal generation scheduling considering operators' adaptability concept. Un prime yosha no manzokudo wo koryoshita hatsudenki shutsuryoku no tamokuteki saiteki haibun  

Energy Technology Data Exchange (ETDEWEB)

Demands for electric power system, which include not only minimization of generation cost but also protection of environmental condition and maintenance of transmission security, have been diversified The priority of these objectives may change according to load change, weather, and other conditions. Since these objectives are usually in a trade-off relationship and generally non-commensurable, it is difficult to handle by conventional optimization of a single objective function. This report describes multi-objective scheduling of thermal power system. The adaptability of three performance indicies, such as economic efficiency, NO{sub x} emission, and transmission security, to operators are defined by membership functions in fuzzy set theory. coordinated solution in which the adaptability of operators is maximized can be obtained by maximizing the fuzzy decision-making function composed of the ...

1992-01-20

187

Magnetic field-induced currents in the human body in proximity of power lines  

Energy Technology Data Exchange (ETDEWEB)

Electric currents induced due to 60 Hz magnetic fields in a human body placed in a close proximity of various high voltage transmission lines are computed. A realistic model of the human body from the anatomical and electrical point of view with resolution of 1.3 cm for the body and 0.665 cm for the head is used. The computations are performed using the impedance method. Three representative configurations of high voltage transmission lines, namely 500 kV, 138 kV and 25 kV are analyzed. The results indicate that the maximum current densities of the order of 0.2 {micro}A/cm{sup 2} can be induced in a lineman working on a 500 kV line (0.5 m away from closest conductors). A good correlation can be seen between the computed magnetic field in the location of the human body and the induced current densities. The induced currents computed here and estimated from measured magnetic fields in various power line environments are ...

1996-01-01

188

MIMO (multi-input multi-output) adaptive power system stabilizer  

Energy Technology Data Exchange (ETDEWEB)

A multivariate adaptive power system stabilizer is proposed. The advantages of using coordinated governor and excitation control are discussed, and the problems associated with constant parameter power system stabilizers (CPSS) are highlighted. The proposed multi-input multi-output (MIMO) power system stabilizer can coordinate the governor and excitation control and can overcome the problems associated with CPSS in power system stabilization. Selective multivariable state modelling, identification and control methods are investigated and the MIMO least squares technique with variable forgetting factor is used for system identification, guaranteeing good parameter tracking after a disturbance. Two multivariable self-tuning algorithms are investigated, the generalized minimum variance control and pole-shifting control algorithms. The multivariable self-searching pole-shifting algorithm is developed. ...

1988-01-01

189

Development of a survey-design support sytem using soil data base; Doshitsu data base wo mochiita chosa sekkei shien system no kaihatsu ni tsuite  

Energy Technology Data Exchange (ETDEWEB)

It is desired that the data on past ground information are easily picked out and used effectively when construction of power facilities such as power plants is planned. For this purpose, a data base system that is available for survey planning and design business has been developed. This system is divided into subsystems for input, registration, and output, which all can be processed by the personal computers. It also has a retrieval function for maps such as area maps and power facility maps in addition to a retrieval function for characters. As output functions, the system has a function to extract ground information through maps of facilities and their peripheries, an output function for geological profiles and soil test results, and liquefaction analysis and design constant setting support functions. As instances, applications of this system to the thermal power plant location program and to the ...

1994-09-05

190

Smart Acquisition EELS  

Energy Technology Data Exchange (ETDEWEB)

Electron energy loss (EEL) spectroscopy and high angle annular dark field (HAADF) imaging in aberration-corrected electron microscopes are powerful techniques to determine the chemical composition and structure of materials at atomic resolution. We have implemented Smart Acquisition, a flexible system of scanning transmission electron microsocpy (STEM) beam position control and EELS collection, on two aberration-corrected dedicated cold field emission gun (FEG) STEMs located at SuperSTEM, Daresbury Laboratory. This allows the collection of EEL spectra from spatially defined areas with a much lower electron dose possible than existing techniques such as spectrum imaging.

2010-07-01

191

Simplified RF power system for Wideroe-type linacs  

Energy Technology Data Exchange (ETDEWEB)

The RF system for the SuperHILAC injector linac was designed and constructed for minimum system complexity, wide dynamic range, and ease of maintenance. The final amplifier is close coupled to the linac and operates in an efficient semilinear mode, eliminating troublesome transmission lines, modulators, and high level regulators. The system has been operated at over 250 kW, 23 MHz with good regulation. The low level RF electronics are contained in a single chassis adjacent to the RF control computer, which monitors all important operating parameters. A unique 360/sup 0/ phase and amplitude modular is used for precise control and regulation of the accelerating voltage.

1981-03-01

192

Gaseous dielectrics V  

Energy Technology Data Exchange (ETDEWEB)

This book discusses the progress and problems of current interest in gaseous dielectrics and their use, with special emphasis on insulation in high-voltage transmission lines and substations. Topics covered include: basic physics of gaseous dielectrics; basic mechanisms; gas decomposition, reactions and toxicity; diagnostics and field probes; gases and mixtures for GIS transformers and circuit breakers; gaseous media for discharge chemistry and etching/corona; gas engineering for pulsed power and switching; gas breakdown under steep-fronted voltages; new developments in gas-insulated equipment and gas handling; gas/insulator interface/flashover; and quality control in testing gas-insulated equipment. Contains approximately 85 papers.

1987-01-01

193

Electricity exchanges across international borders - 1983  

Energy Technology Data Exchange (ETDEWEB)

This report summarizes the electricity exchanges between the US and Mexico and Canada during calendar year 1983. The construction, operation and maintenance of any electric transmission facility which crosses an international border of the United States requires a Presidential Permit. These permits have been granted by the Department of Energy (DOE) since its formation in 1977. Between 1953 and 1977, these permits were issued by the former Federal Power Commission. Prior to 1953, they were issued by the President of the United States. Presidential Permits require that an annual report be filed by the permit holder detailing all transactions with the foreign country.

1984-09-01

194

Electrical impact of Mt. St. Helens  

Energy Technology Data Exchange (ETDEWEB)

Ash fallout from the Mount Saint Helens eruptions affected high-voltage transmission in a four-state area as volatile gases caused conductivity changes and corrosion. The Bonneville Power Authority (BPA) found that it was possible to maintain electric service except for a few short, localized outages. Cleaning ash from transformers and substations was the first priority. Tests were underway within 48 hours to determine ash characteristics and cleaning procedures. A summary to what happened and what was learned is presented in two lists. (DCK)

1981-08-01

195

Airport expansion requires major wetlands mitigation project  

Energy Technology Data Exchange (ETDEWEB)

This article describes the steps taken to mitigate the impact to existing wetlands by creating new wetlands in an airport expansion project. The project addressed maintaining suitable amounts of wetlands to accommodate peak waterfowl populations, moving of high voltage power transmission towers, and maintaining agricultural and hunting interests. This project involved recreating of open water areas, marsh habitat, mud flat habitat, saline meadow habitat, maintaining two existing wetlands in the area of the new wetlands without disturbing them, and improving upland habitat surrounding the new wetlands.

1994-01-01

196

The Australian Geographic Team Marsupial solar-powered car  

Energy Technology Data Exchange (ETDEWEB)

As in all vehicles of this type, low weight and aerodynamic drag must be achieved without compromising safety, and in an extremely rugged structure. This has been done by using a chrome-molybdenum steel space-frame, surrounded by a Kevlar/foam sandwich body shell. The solar panel wing, which uses a laminar flow section to obtain low drag, does not tilt except when the vehicle is stationary. A high degree of redundancy is built into the vehicle; for example there are two motors and transmissions, the solar array is divided into seven parallel sub-arrays, and the power electronics is multiply redundant. Built entirely in the garage of a suburban house, the Australian Geographic Team Marsupial car cost less than US$50,000 to construct.

1988-01-01

197

PSPs at Bhira and Bhivpuri  

International Nuclear Information System (INIS)

Tata Electric Companies (TEC) are engaged in the generation of hydro and thermal energy. TEC, to minimise backing down of its thermal units in off peak hours and also to at least partially meet the growing deficit in the supply during peak hours is moving to install pumped storage plants (PSPs) utilising off-peak surplus energy for pumping the water from lower pond to the upper pond for subsequent utilisation for power generation during peak hours. In view of some of the infra structural facilities such as storage ponds, water conductor system, transmission lines, etc. being already available, at the existing hydro power stations owned by TEC, the pumped storage units are being proposed within the environs of existing hydro stations, i.e. a 150 MW pumped storage unit at Bhira and a 90 MW pumped storage unit at Bhivpuri. The projects are described and cost estimates is given. (author). 2 figs.

1992-01-01

198

Incorporating externalities into a full cost approach to electric power generation life-cycle costing  

Energy Technology Data Exchange (ETDEWEB)

This study presents a full cost approach to determine the levelized cost of energy (LCOE) of 14 electricity generation technologies. It encompasses costs incurred at all stages of the fuel cycle, including those that are traditionally omitted from economic evaluations of generation technologies. Incorporating these 'externalities' increases the likelihood of developing the most economical and sustainable power resource from a societal perspective. The following externalities are included in this analysis: damage from air pollution, energy security, transmission and distribution costs, and other environmental impacts. Incorporating externalities has a large impact on the LCOE and the relative attractiveness of electricity generation options. Results indicate that clean and efficient generation technologies are the most attractive when all options are examined using a full cost, levelized approach. (author)

2002-12-01

199

Dynamic voltage control by remote voltage regulation for pumped storage plants  

Energy Technology Data Exchange (ETDEWEB)

This paper presents a new application in dynamic voltage control based on an older method of voltage regulation. The resulting method is suitable for adoption inn multi-unit pumped storage plants. Inherent operation characteristics of pumped storage plants in the pumping mode can created visible load rejection overvoltages on the transmission and the nearby distribution networks and cause customer complaints. This paper proposes a method in which the on-line units' excitation system impedance compensators are utilized to reduce the magnitude of these overvoltages. This paper presents the theoretical background, computer simulation results, and the field test results at the Pacific Gas and Electric Company's Helms Pumped Storage Plant. This paper should be of interest in the areas of power system planning as well as power system operation.

1988-08-01

200

Double plasma mirror for ultrahigh temporal contrast ultra-intense laser pulses  

International Nuclear Information System (INIS)

We present and characterize a very efficient optical device that employs the plasma mirror technique to increase the contrast of high-power laser systems. Contrast improvements higher than 104 with 50% transmission are shown to be routinely achieved on a typical 10 TW laser system when the pulse is reflected on two consecutive plasma mirrors. Used at the end of the laser system, this double plasma mirror preserves the spatial profile of the initial beam, is unaffected by shot-to-shot fluctuations, and is suitable for most high peak power laser systems. We use the generation of high-order harmonics as an effective test for the contrast improvement produced by the double plasma mirrors. (authors)

201

Application of GIS for the evaluation of human exposure to magnetic field in the vicinity of power lines  

Energy Technology Data Exchange (ETDEWEB)

Application of the Geographic Information System (GIS) with a statistical model to evaluate the magnetic field exposure of a population from high-voltage transmission lines near residential areas is discussed, focusing on the interaction of the GIS with the statistical model. In an effort to validate the model measurements of the magnetic field, profiles were taken at two sites and these profiles have been compared with calculated values. Two conclusions have been drawn from the results: (1) the statistical model linked with the GIS is a very powerful tool for the evaluation of exposure of a population to magnetic fields, and (2) success depends on the presence of other sources of magnetic fields and on the exactness of the data used in the model. 4 refs., 5 figs.

1998-10-01

202

An innovative method of providing total breaker failure protection  

Energy Technology Data Exchange (ETDEWEB)

Breaker failure relaying has been generally achieved through the use of a current monitoring relay to determine whether current continues to flow into a fault after a breaker has been instructed to interrupt the circuit. If current continues to flow after a predefined period of time, the circuit breaker is considered to have failed. Steps must then be taken to trip the next set of upstream breakers in the power system to remove the faulted circuit and prevent system damage. However, with industrial power systems, this may be the utility`s breakers on the feeding transmission line. Regardless, breaker failure schemes must be designed to isolate both the faulted circuit and the failed circuit breaker. This paper discusses a new and innovative method of protecting a circuit breaker from the failure described above, plus other failures that go unprotected with conventional schemes, this providing total breaker failure ...

1996-09-01

203

A free topology safeguards network  

Energy Technology Data Exchange (ETDEWEB)

Free Topology Network technology provides cost reduction benefits as well as flexibility in safeguards applications. Power line communications technologies have proven viability for transmission and reception of safeguards data, including surveillance photographs, the source of the largest data files. In the future, enhancements will be made to the technology that should boost both performance and flexibility. Work is already underway to achieve higher data rates over power line communications eventually, it should be possible to reach data rates of one million bits per second or higher. Also, the use of technologies such as Novell Embedded Systems Technology (NEST) and Echelon LON technology will allow a greater number of safeguards technologies to become resident on the Free Topology Safeguards Network.

1995-12-31

204

A free topology safeguards network  

International Nuclear Information System (INIS)

Free Topology Network technology provides cost reduction benefits as well as flexibility in safeguards applications. Power line communications technologies have proven viability for transmission and reception of safeguards data, including surveillance photographs, the source of the largest data files. In the future, enhancements will be made to the technology that should boost both performance and flexibility. Work is already underway to achieve higher data rates over power line communications eventually, it should be possible to reach data rates of one million bits per second or higher. Also, the use of technologies such as Novell Embedded Systems Technology (NEST) and Echelon LON technology will allow a greater number of safeguards technologies to become resident on the Free Topology Safeguards Network.

1995-07-09

205

Effect of Infrared Pulsated Laser on the Dielectric Properties of Makrofol Polycarbonate  

International Nuclear Information System (INIS)

Makrofol-De 1-1 CC Polycarbonate is a class of polymeric solid state nuclear track detectors which has many applications in various industrial fields. A study of the modification possibility of the dielectric properties of Makrofol polymer using laser irradiation has been carried out. In tbe present work, Makrofol samples were irradiated using different fluences between 0.47 and 10.4 J/cm"2 of 5 watt infrared pulsated laser. The mollifications in the laser irradiated Makrofol samples have been studied as a function of fluence using dielectric constant #epsilon#', dielectric loss #epsilon#"and AC conductivity #sigma#_AC measurements. Tbe frequency dependencies (100 Hz-5 MHz) of #epsilon#', #epsilon#"and #sigma#_AC at 35 degree c were investigated. The dielectric constant #epsilon#', dielectric loss #epsilon#"and AC conductivity #sigma#_AC were found to increase at heating up to 100 ...

206

Single parameter analysis of hysteretic magnetic flux trapping in high T{sub c} superconductor ribbon  

Energy Technology Data Exchange (ETDEWEB)

This paper described the application of an AC surface probe, similar to presently used eddy current probes, to the measurement of DC transport critical currents and critical state dissipation in high {Tc} superconductors. It has been shown that the probe can provide quantitative measurement of the full field penetration in superconducting samples by measuring the response of AC induced screening currents for superconducting materials in the form of tapes with overlayers of silver. In this manner, the AC probe can be used to replace the contact DC probe for determining critical currents in a noncontacting and local manner suitable for scanning over or along the sample.

1992-10-01

207

Single parameter analysis of hysteretic magnetic flux trapping in high T_c superconductor ribbon  

International Nuclear Information System (INIS)

This paper described the application of an AC surface probe, similar to presently used eddy current probes, to the measurement of DC transport critical currents and critical state dissipation in high T_c superconductors. It has been shown that the probe can provide quantitative measurement of the full field penetration in superconducting samples by measuring the response of AC induced screening currents for superconducting materials in the form of tapes with overlayers of silver. In this manner, the AC probe can be used to replace the contact DC probe for determining critical currents in a noncontacting and local manner suitable for scanning over or along the sample.

1992-07-19

208

Single parameter analysis of hysteretic magnetic flux trapping in high T[sub c] superconductor ribbon  

Energy Technology Data Exchange (ETDEWEB)

This paper described the application of an AC surface probe, similar to presently used eddy current probes, to the measurement of DC transport critical currents and critical state dissipation in high [Tc] superconductors. It has been shown that the probe can provide quantitative measurement of the full field penetration in superconducting samples by measuring the response of AC induced screening currents for superconducting materials in the form of tapes with overlayers of silver. In this manner, the AC probe can be used to replace the contact DC probe for determining critical currents in a noncontacting and local manner suitable for scanning over or along the sample.

1992-01-01

209

On load flow control in electric power systems  

Energy Technology Data Exchange (ETDEWEB)

This dissertation deals with the control of active power flow, or load flow in electric power systems. During the last few years, interest in the possibilities to control the active power flows in transmission systems has increased significantly. There is a number of reasons for this, coming both from the application side - that is, from power system operations - and from the technological side. where advances in power electronics and related technologies have made new system components available. Load flow control is by nature a multi-input multi-output problem, since any change of load flow in one line will be complemented by changes in other lines. Strong cross-coupling between controllable components is to be expected, and the possibility of adverse interactions between these components cannot be rejected straightaway. Interactions with dynamic phenomena in ...

2000-01-01

210

UARS PEM Level 2 VMAG AC - Mirador - NASA  

Science.gov (United States)

May 11, 2011 ... The Particle Environment Monitor (PEM) on NASA's Upper Atmosphere Research Satellite (UARS) measures the type, amount, energy, and ...

212

The Morphological Basis of the Armor-Like Folded Skin of the Greater Indian Rhinoceros as a Thermoregulator  

Science.gov (United States)

... 041.034.0403 The Morphological Basis of the Armor-Like Folded Skin of the Greater Indian Rhinoceros ... hendo@um.u-tokyo.ac.jp ...

214

Structure and Characterization of Nicotinic Acetylcholine ...  

Science.gov (United States)

... the ct-neurotoxin from Dendroaspis viridis venom (a-DTX) , which binds to four sites on the AcChR molecule (Conti-Tronconi & Raftery 1986). ...

1991-11-07

215

State II Dissociation Element Formation Following Activator Excision in Maize  

UK PubMed Central (United Kingdom)

Active Activator (Ac) elements undergo mutations to become nonautonomous Dissociation (Ds) elements at a low frequency. To understand...Full Text Available

2007-10-01

216

Journals at IDEAS  

Wastenet

... Advances in Complex Systems ( ACS) 413 (413) 2001-2011 Springer Advances in Data Analysis and Classification 59 (59) 2008-2011 Advances in Management Advances In Management ...

217

Fish intake and acute coronary syndrome  

British Library Electronic Table of Contents (United Kingdom)

Aims To study the effect of fish consumption on the risk of acute coronary syndrome (ACS) in healthy subjects. Methods and results This Danish follow-up study included 57 053 men and women between 50 and 64 years. Intake of lean and fatty fish was estimated from a detailed and validated food frequency questionnaire. Potential cases of ACS were identified through nationwide medical databases. A total of 1122 cases of ACS were verified during a mean follow-up period of 7.6 years. Among men, intake of fatty fish was associated with a lower risk of ACS. For men in the highest quintile of fish intake compared with the lowest quintile, the hazard ratio was 0.67 (95% confidence interval: 0.53-0.85). The inverse association was observed for intakes >6 g of fatty fish per day with no obvious additi...

2010-01-01

220

Correlated accumulation of anthocyanins and rosmarinic acid in mechanically stressed red cell suspensions of basil (Ocimum basilicum)  

British Library Electronic Table of Contents (United Kingdom)

A red basil cell line (T2b) rich in rosmarinic acid (RA) was selected for the stable production of anthocyanins (ACs) in the dark. Cell suspension cultures were subjected to mechanical stress through increased agitation (switch from 90 to 150rpm) to determine the relationship between AC and RA accumulation. Cell extracts were analyzed by HPLC and LC-MS, and the resulting data were processed with multivariate statistical analysis. MS and MS/MS spectra facilitated the putative annotation of several complex cyanidin-based ACs, which were esterified with coumaric acid and, in some cases, also with malonic acid. It was also possible to identify various RA-related molecules, some caffeic and coumaric acid derivatives and some flavanones. Mechanical stress increased the total AC and RA contents, ...

2011-01-01

221

Characteristics of diethylenetriamine-crosslinked cotton stalk/wheat stalk and their biosorption capacities for phosphate  

British Library Electronic Table of Contents (United Kingdom)

Two polymeric biosorbents were prepared from cotton stalk (CS) and wheat straw (WS) by the epichlorohydrin-diethylenetriamine-trimethylamine method. Amine-crosslinked cotton stalk (AC-CS) and wheat stalk (AC-WS) were used for the adsorption of phosphate, and their physicochemical properties as well as biosorption properties for phosphate were discussed intensively. Results indicated that the contents of holocellulose in CS and WS corresponded to the distinct phosphate adsorption capacities between AC-CS and AC-WS. Zeta potential and Raman spectra analysis illustrated the electrostatic attraction between phosphate ions and biosorbents. The adsorption of phosphate was not strongly pH dependent when the pH was about 4.0-9.0. The Langmuir isotherm provided the better fit and the maximum adsorp...

2011-01-01

222

Advisory Committee for GPRA Performance Assessment (AC/GPA) Report FY2003  

Science.gov (United States)

... impact. The Committee reviewed voluminous materials from NSF?s retrospective and prospective award ...

223

Report on the Swedish National Energy Administration's program for energy efficiency 1998-2001; Redovisning av Energimyndighetens insatser foer energieffektivisering aaren 1998-2001  

Energy Technology Data Exchange (ETDEWEB)

Support for raising energy efficiency is reported for the following five areas during 1998-2001: 1. Fuel-based energy systems with the sub-areas: Sustainable production of biofuels, including ash recycling; Cogeneration; and Large scale heat production. 2. Transport with two sub-areas: Internal combustion engines; and Electric drive-lines. 3. Power production/Power technology with the sub-areas: Hydropower; Wind power; Power transmission and distribution; and Photovoltaic solar cells. 4. Industry with the sub-areas: Processes; and Support systems in industry. 5. Buildings with the sub-areas: Heating, cooling and climatic shields; and Components and support systems. In total, 1,800 M SEK (about 180 M USD) was contributed by the Energy Administration during this period. An overview of the projects is presented in this report.

2002-01-01

224

Playing the money game  

Energy Technology Data Exchange (ETDEWEB)

Conventional methods of financing power generation, transmission and distribution in India cannot keep pace with the ever-growing demand. Alternative methods are discussed. Given the vast growth potential, funding can be by equity or debt capital or a hybrid of these. There is an urgent necessity to develop local capital markets as a source of funds since there are limits to how much can be derived from foreign investors, multilaterals and export credit agencies. The domestic financial institutions have raised large amounts for private investment in other sectors. With the creation of a proper climate and power companies set up with an attractive rate of return, sufficient capital could be forthcoming from both domestic and external markets for the power sector. In other sectors, Indian companies have been able to attract investment through Global Depository Receipts and Euroconvertible Bonds, for ...

1997-01-01

225

OPC Server and BridgeView Application for High Voltage Power Supply Lecroy 1458  

CERN Document Server

Abstract The aim of this project was to develop an OPC server to communicate over an RS232 serial line. This communication media is commonly used with commercial instruments. The development was made for a High Voltage power supply in the context of the Alice [1] experiment. In addition, the structured modular concept will allow changing the transmission media or power supply type with little effort. The high voltage power supply should be accessible remotely through a network. OPC[2] is an acronym for OLE[3] for Process Control. OPC is based on the DCOM [3] communication protocol, which allows communication with any computer running a Windows based OS. This standard is widely used in industry to access device data through Windows applications. The concept is based on the client-server architecture. The hardware and the software architecture are described. Subsequently details of the implemented ...

2000-01-01

226

EdF competing in the European electricity market. Interview with Francois Ailleret, Electricite de France, Paris  

International Nuclear Information System (INIS)

The French nuclear power program was pushed through in order to reduce the country's dependence on imported fossil sources of energy. Nuclear power and hydro power have achieved a level of self-sufficiency in the energy sector of more than 50%. It should be emphasized that the French nuclear power program was largely self-financed. Electricite de France (EdF) considers itself well prepared for the European market, provided the creation of the single market implies that electricity rates are taken as a yardstick of competitiveness. Negotiations about a European directive on deregulating the electricity market were for the government to hold. EdF pleaded in favor of preserving for each country a certain leeway for shaping its own policy. The road to deregulation was to be opened, but the specific situation of each country was to be taken electricity to be passed through imposes narrow constraints upon an ...

1996-01-01

227

Difference Antenna Selection and Power Allocation for Wireless Cognitive Systems  

CERN Document Server

In this paper, we propose an antenna selection method in a wireless cognitive radio (CR) system, namely difference selection, whereby a single transmit antenna is selected at the secondary transmitter out of $M$ possible antennas such that the weighted difference between the channel gains of the data link and the interference link is maximized. We analyze mutual information and outage probability of the secondary transmission in a CR system with difference antenna selection, and propose a method of optimizing these performance metrics of the secondary data link subject to practical constraints on the peak secondary transmit power and the average interference power as seen by the primary receiver. The optimization is performed over two parameters: the peak secondary transmit power and the difference selection weight $\\delta\\in [0, 1]$. We show that, difference selection using the optimized parameters ...

2010-01-01

228

Applications of cathodic protection for the protection of aqueous and soil corrosion of power plant components  

International Nuclear Information System (INIS)

Power plant components exposed to environments such as water and soil are susceptible to severe corrosion. Many times the effect of corrosion in power plant components can be catastrophic. The problem is aggravated for underground pipelines due to additional factors such as large network of pipelines, proximity to earth mat, high voltage transmission lines, corrosive chemicals, inadequate approach etc. Other components such as condenser water boxes, internals of pipelines, clarifier bridge structures, cooling water inlet gates and pipes etc. which are in continuous contact with water, are subjected to severe corrosion. The nature and locations of all such components are at places which are not accessible for routine maintenance and hence they require long term reliable protection against corrosion. Experience has shown that anti-corrosive coatings are inadequate in preventing corrosion and due to their location regular ...

1999-11-22

229

Request for an Analytical Transmission Electron Microscope.  

Science.gov (United States)

... Accession Number : ADA189111. Title : Request for an Analytical Transmission Electron Microscope. Descriptive Note : Final rept. ...

1987-10-16

230

A bright field scanning transmission electron microscope (STEM ...  

Science.gov (United States)

A bright field scanning transmission electron microscope (STEM) micrograph showing a Wassonite grain in dark contrast. ...

231

Power line fault current coupling to nearby natural gas pipelines: Volume 2, User's guide for ECCAPP computer program  

Energy Technology Data Exchange (ETDEWEB)

A generalized approach to the analysis of the effects of transmission line faults on natural gas transmission pipelines has been developed and is presented in this report. A state of the art user-friendly computational tool has been developed and verified for the analysis of interference between electrical power lines and nearby buried or above-ground pipelines. This computer program, ECCAPP, is distinguished by its ability to model and analyze accurately complex, realistic interactions between pipelines and power lines, using easily obtained input data. The final report consists of three volumes. An independent fourth volume was also developed to simplify the installation of the ECCAPP software. Volume 1 contains the theory upon which the ECCAPP computer program is based. A parametric analysis and graphical charts have been formulated using ECCAPP to permit estimates to be made in the field or during ...

1987-10-01

232

Improving T D reliability. How pumped storage can boost network security  

Energy Technology Data Exchange (ETDEWEB)

The key to improving transmission-network security is faster response to contingencies. Now a new breed of pumped-storage plant - designed for ultra-fast response - may soon provide a tool dispatchers can use to improve network security. This type of plant can also substantially increase the effective capacity of existing transmission lines and improve the performance of thermal generating units. The Mt. Hope Waterpower Project, planned for Rockaway Township, NJ, 35 miles west of New York City, lies strategically adjacent to major load centers at the eastern end of the PJM control area and near the interconnection point with the New York Power Pool (NYPP). This location also is in an area deficient in significant generating facilities. Maximum design capacity of the project is 2000 MW, provided by six reversible pump/turbines, each with a nominal 340-MW rating. The upper reservoir, with a surface area of only 60 acres, ...

1994-03-01

233

Electrical wind generation, feasibility study and analysis in Lebanon  

International Nuclear Information System (INIS)

Full text.This paper is to investigate the potentials and possibilities of electrical generation via wind turbine. Special attention is directed to the interpretation of wind generation characteristics and parameters found in Lebanon and linking the electrical energy to the Lebanese slectric grid. Although much of the wind energy research is very well established and boomed globally (USA, Europe, India and China), in Lebanon is never used. At a time when climate scientists are increasingly concerned about carbon dioxide emissions from coal and diesel plants, and the nuclear industry is drying, the significance of a major new source os electricity is clear. there are many motives and feasibility criteria for qind power generation in Lebanon. They include the need for increasing the Lebanese electrical capacity, reducing air pollution, alternative energy sources and prices and availability of oil. The work will include literature survey on current wind energy ...

1999-11-02

234

Bounds on the Achievable Rate for the Fading Relay Channel with Finite Input Constellations  

CERN Document Server

We consider the wireless Rayleigh fading relay channel with finite complex input constellations. Assuming global knowledge of the channel state information and perfect synchronization, upper and lower bounds on the achievable rate, for the full-duplex relay, as well as the more practical half-duplex relay (in which the relay cannot transmit and receive simultaneously), are studied. Assuming the power constraint at the source node and the relay node to be equal, the gain in rate offered by the use of relay over the direct transmission (without the relay) is investigated. It is shown that for the case of finite complex input constellations, the relay gain attains the maximum at a particular SNR and at higher SNRs the relay gain tends to become zero. Since practical schemes always use finite complex input constellation, the above result means that the relay offers maximum advantage over the direct transmission when we operate ...

2011-01-01

235

Ballard fuel cells and the changing energy landscape  

Energy Technology Data Exchange (ETDEWEB)

The numerous challenges facing the North American electric utility industry were discussed. In addition to competition, electric utilities are faced with low demand growth, public pressure to avoid adding transmission and distribution capacity, and strict environmental requirements. In view of these developments, large central generation additions that have been industry norm until recently, do not always make economic sense in the current environment. Instead, smaller, distributed additions to generating capacity is becoming the new norm. Small-scale on-site generating capacity has the added advantage of reducing the need for expensive high-voltage transmission lines. The Ballard generation system described here is a modular, efficient fuel cell-based solution to implementing distributed power concepts. The system is natural gas fueled, with low noise, vibration and emissions. Apart from its other advantages, it provides ...

1997-02-01

236

A surface acoustic wave electric field strength meter for environmental studies of HV transmission lines  

International Nuclear Information System (INIS)

In recent years, there has been a significant increase in concern over the health and safety aspects of high voltage transmission lines (HVTL). The majority of research has focused on effects directly or indirectly involved with the central nervous system, including physiological, ultrastructural, and biochemical alterations, changes in blood composition, behaviour, reproduction, and development. Several recent epidemiological reports have presented preliminary data suggesting an increase in the incidence of cancer among children and adults exposed to magnetic fields through living close to various types of electrical power lines or devices. With the increase in environmental concerns there has been a concomitant consideration of biological effects and health implications related to presently existing HVTL and those planned in the future. It was concluded that the electric and magnetic field strengths and the electrical discharges are the most ...

1988-04-01

237

A model for calculation of RCS pressure during reflux boiling under reduced inventory conditions and its assessment against PKL data  

International Nuclear Information System (INIS)

Based on the occurrence of a number of plant incidents during low power and shutdown operating conditions, the Nuclear Regulatory Commission (NRC) has initiated several programs to better quantify risk during these periods. One specific issue of interest is the loss of residual heat removal (RHR) under reduced coolant inventory conditions. This issue is also of interest in the Federal Republic of Germany and an experiment was performed in the integral PKL-3 experimental facility at Siemens-KWU to supply applicable data. Recently, an effort has been undertaken at the Idaho National Engineering Laboratory (INEL) to identify and analyze the important thermal-hydraulic phenomena in pressurized water reactors following loss of vital AC power and consequent loss of the RHR system during reduced inventory operation. The thermal-hydraulic response of a nuclear steam supply system (NSSS) with a closed reactor coolant system (RCS) to ...

1991-10-01

238

Long- but not short-term heat acclimation produces an apoptosis-resistant cardiac phenotype: a lesson from heat stress and ischemic/reperfusion insults  

UK PubMed Central (United Kingdom)

Long-term heat acclimation (AC, 30d/34°C) is a phenotypic adaptation leading to increased thermotolerance during heat stress (HS, 2 h 41°C). AC also renders protection against...Full Text Available

2010-09-01

239

A single amino acid substitution modulates low-pH-triggered membrane fusion of GP64 protein in Autographa californica and Bombyx mori nucleopolyhedroviruses  

International Nuclear Information System (INIS)

We have previously shown that budded viruses of Bombyx mori nucleopolyhedrovirus (BmNPV) enter the cell cytoplasm but do not migrate into the nuclei of non-permissive Sf9 cells that support a high titer of Autographa californica multicapsid nucleopolyhedrovirus (AcMNPV) multiplication. Here we show, using the syncytium formation assay, that low-pH-triggered membrane fusion of BmNPV GP64 protein (Bm-GP64) is significantly lower than that of AcMNPV GP64 protein (Ac-GP64). Mutational analyses of GP64 proteins revealed that a single amino acid substitution between Ac-GP64 H155 and Bm-GP64 Y153 can have significant positive or negative effects on membrane fusion activity. Studies using bacmid-based GP64 recombinant AcMNPV harboring point-mutated ac-gp64 and bm-gp64 genes showed that Ac-GP64 H155Y and Bm-GP64 Y153H substitutions decreased and ...

2010-09-01

240

Influences of particle sizes and contents of chemical blowing agents on foaming wood plastic composites prepared from poly(vinyl chloride) and rice hull  

British Library Electronic Table of Contents (United Kingdom)

This research aims to investigate the effects of chemical blowing agent (CBA) contents and particle sizes on the properties of foamed poly(vinyl chloride) (PVC)/rice hull (RH) composites. Fine particles of azodicarbonamide (AC) at 5, 8, 11 and 22mm were modified with 20% by weight of ZnO and used at 0-3.0% by weight. The average cell size and density of the PVC/RH foamed profiles were reduced as the content of modified azodicarbonamide (mAC) increased. Larger mAC particles lowered the density more effectively. Maximum reduction of density by 46% was achieved when mAC 22mm was applied at 2.0% by weight. Larger blowing particles led to PVC/RH foam with greater flexural modulus and strength. Greater impact strength, observed when 5mm mAC was applied, resulted from the rather thick cell wall c...

2011-01-01

241

Energy analysis of a solar pre-water heating system; Analise energetica de um sistema de pre-aquecimento solar de agua  

Energy Technology Data Exchange (ETDEWEB)

Several technological alternatives have been studied taking into consideration that one of the biggest problems of the electric power companies is to provide electric power during the peak consumption periods, which largest contribution to the increase of the demand comes from the residential sector, especially by the use of electric showers. One of the most promising alternatives is the pre-water heating system for reduced power showers, developed by Universidade de Campinas and Companhia Paulista de Forca e Luz. The goal of this system is basically to reduce demand during the peak periods, in order to avoid heavy investments by the electric power companies in generation, transmission and distribution of electric power directed to low acquisitive power customers, a sector in which the electric power price is not enough ...

1996-12-31

242

Voltage and reactive power control by means of static compensators of vars in electric power systems; Control de voltaje y potencia reactiva mediante compensadores estaticos de Vars en sistemas electricos de potencia  

Energy Technology Data Exchange (ETDEWEB)

In this thesis a study is made of the of voltage characteristics and reactive power control in the transmission network of the Electric Power Systems (EPS) with static compensators of VARs (SCVs). The necessity of voltage and reactive power control and the application of SCVs as a solution means for three representative operation stages of the EPS, considering balanced operation conditions and fundamental frequency is analyzed: Operation in the presence of incremental voltage changes, quasi-stationary operation or steady state and behavior at the occurrence of big disturbances. The application of SCVs to systems of integral transmission is in general a closed loop control system, reason why the analysis of the interaction of the system EPS-SCV is considered as an essential part of the voltage and reactive power control study. Firstly, the response analysis of ...

1987-07-01

243

Two-gigawatt burst-mode operation of the intense microwave prototype (IMP) free-electron laser (FEL) for the microwave tokamak experiment (MTX)  

Energy Technology Data Exchange (ETDEWEB)

The MTX explored the plasma heating effects of 140 GHz microwaves from both Gyrotrons and from the IMP FEL wiggler. The Gyrotron was long pulse length (0.5 seconds maximum) and the FEL produced short-pulse length, high-peak power, single and burst modes of 140 GHZ microwaves. Full-power operations of the IMP FEL wiggler were commenced in April of 1992 and continued into October of 1992. The Experimental Test Accelerator H (ETA-II) provided a 50-nanosecond, 6-MeV, 2--3 kAmp electron beam that was introduced co-linear into the IMP FEL with a 140 GHz Gyrotron master oscillator (MO). The FEL was able to amplify the MO signal from approximately 7 kW to peaks consistently in the range of 1--2 GW. This microwave pulse was transmitted into the MTX and allowed the exploration of the linear and non-linear effects of short pulse, intense power in the MTX plasma. Single pulses were used to explore and gain operating experience in the ...

1993-10-06

244

Fuzzy coordination of multi-objectives reflecting the operator's intention for dynamic generation rescheduling [of power systems  

Energy Technology Data Exchange (ETDEWEB)

This paper proposes a novel and efficient algorithm to obtain optimal generation dispatch reflecting the operator's intention in power system rescheduling. In optimal system operation, various objectives, such as economy, quality and transmission security, need to be achieved simultaneously. However, these objectives are often contradictory and in a trade-off relationship with respect to each other thus making it difficult to handle this class of problem by conventional approaches. In the proposed algorithm, optimal generation dispatch is formulated as a multi-objective optimization problem. A fuzzy coordination technique based on fuzzy set theory is used to obtain an optimal solution. Evaluation indices composed of fuel cost, transmission line overload and AFC regulation capacity margin are measured by the membership functions, and multi-objective optimization is solved by maximizing the composite performance ...

1992-10-01

245

Working hot  

International Nuclear Information System (INIS)

The author says ''barehand'' methods, where specially trained utility workers are called in conductive suits to equalize voltage over their bodies, to maintain high-voltage transmission lines are on the rise. Utilities are building lines at higher voltages and selling more power to other utilities, making it highly inconvenient to take the lines out of service. However, some unions view the barehand work with less than enthusiasm. Touching lines energized at hundreds of thousands of volts demands flawless equipment and rigid work procedures followed to the letter. Some local unions contend that adequate safety procedures and training, and appropriate penalties for workplace negligence, should be in place before utilities may do barehand work. The author discusses some of the methods of barehand work and the equipment used, i.e. steel-mesh lineman's suit, bucket truck's boom, helicopters, and robots.

1988-01-01

246

Very high voltage cables with synthesis insulation; Les cables tres haute tension a isolation synthetique  

Energy Technology Data Exchange (ETDEWEB)

A historical review on insulated cables for power transmission, is presented, beginning with impregnated paper insulation, oil filled cables and natural rubber cables. High density and chemically reticulated polyethylene were then used for high voltage and very high voltage cables; the advantages of polyethylene compared to impregnated paper cables are discussed, which led to research programs at EDF on various themes concerning the optimization of polyethylene cables: dielectric properties and reliability, thermomechanical behaviour, thermal ageing of materials, testing methods (acceptance dielectric test and long duration temperature test); utilization of low- and high-density and chemically reticulated polyethylene for 225 kV cables is discussed

1997-06-01

247

TUNABLE FIBER FABRY-PEROT FILTER FOR OPTICAL CARRIER-SUPPRESSION AND SINGLE-SIDEBAND MODULATION IN RADIO OVER FIBER LINKS  

British Library Electronic Table of Contents (United Kingdom)

A novel method of simultaneous realization of optical carrier-suppression and single-sideband modulation using fiber Fabry-Perot tunable filter is presented. In order to enhance transmission performance of radio over fiber links, we use a fiber Fabry-Perot tunable filter to filter out one sideband as well as suppress the optical carrier power. The results demonstrate 20.5dB and 14.2dB improvement in the signal noise ratios when 18GHz and 10GHz microwave signals carrying 5Mbit/s quadrature-phase-shift-keyed (QPSK) format data is transmitted over 35 km single mode fiber, respectively.

2006-01-01

248

Progress on significant R and D projects  

Science.gov (United States)

This report updates the status of 32 large projects having EPRI authorizations of $5 million or more. It also describes 86 smaller projects that have EPRI authorizations of less than $5 million and that have a high likelihood of producing a utility-useful new near-term accomplishment within the next two years. Finally, there are 45 examples of analytical, experimental and bench-scale projects that were influential in confirming or redirecting EPRI's research program. These examples cover the entire spectrum of electric R and D: (1) fuel processing, (2) electric power generation, (3) transmission and distribution, (4) energy storage and management, (5) energy analysis, and (6) environmental assessment and control.

1982-08-01

249

Polymer Fuel Cells Challenge  

Wastenet

...Polymer Fuel Cells Challenge Publications News Events Login Register Search Content type All Web pages Case studies Publications News Video Home ...Buildings Carbon capture & storage Combined heat & power Electricity transmission & distribution Energy storage Fuel cells Geothermal Hydroelectric Hydrogen Industry Lighting Marine Metering Nuclear Solar Transport Wind ...Home Emerging technologies Current focus areas Polymer Fuel Cell Challenge Polymer Fuel Cells Challenge The objective of the Polymer Fuel Cells Challenge is to develop,...prove and commercialise novel polymer fuel cell technologies that have the potential to deliver a step-change in overall system cost. What are ...

250

One-step synthesis of Pt-supported carbon nanohorns for fuel cell electrode by arc plasma in liquid nitrogen  

International Nuclear Information System (INIS)

One-step synthesis of Pt-loaded carbon nanoparticles including single-wall carbon nanohorns (SWNHs) by arc plasma in liquid nitrogen was demonstrated using Pt-contained graphite anode. The size distribution of Pt particles can be controlled by adjusting the concentration of Pt in the graphite anode. In the observation by transmission electron microscope, the diameter of less than 5 nm of Pt particles were observed as approximately 90% among the Pt particles when Pt was contained in the anode at 1.3 at.%. When Pt concentration in the anode was decreased to 0.4 at.%, the percentage of Pt particles whose diameter is less than 5 nm decreased to approximately 60%. It was verified that the as-grown Pt-loaded products produced by this method can be useful for the power generation by polymer electrolyte fuel cell.

2006-10-10

251

Magnetically applied pressure-shear : a new technique for direct strength measurement at high pressure (final report for LDRD project 117856).  

Energy Technology Data Exchange (ETDEWEB)

A new experimental technique to measure material shear strength at high pressures has been developed for use on magneto-hydrodynamic (MHD) drive pulsed power platforms. By applying an external static magnetic field to the sample region, the MHD drive directly induces a shear stress wave in addition to the usual longitudinal stress wave. Strength is probed by passing this shear wave through a sample material where the transmissible shear stress is limited to the sample strength. The magnitude of the transmitted shear wave is measured via a transverse VISAR system from which the sample strength is determined.

2010-09-01

252

Hybrid insulator - the excellent post insulator for HVAC and HVDC power station  

Energy Technology Data Exchange (ETDEWEB)

A solid layer artificial pollution test was carried out to study the pollution performance of a new type of hybrid station post insulator used in suspension and tensile high voltage transmission lines. The structure of the separated silicone rubber shed and porcelain core hybrid insulator was shown. The new insulator showed excellent pollution performance under both HVAC and HVDC conditions. It also exhibited excellent aging performance in artificial aging tests. The mechanical strength of the hybrid insulator was also better than normal composite insulators. Another advantage revealed was the fact that separated silicone rubber sheds and porcelain core hybrid post insulators are easier to manufacture than normal porcelain post insulators and other hybrid insulators. 5 refs., 6 tabs., 1 fig.

1997-12-31

253

Fault location observability analysis and optimal meter placement based on voltage measurements  

British Library Electronic Table of Contents (United Kingdom)

Various transmission line fault location algorithms have been proposed in the past depending on measurements available. These methods evince that if a sufficient number of meters are placed in a power network to record the fault measurements, then the fault location can be reliably estimated. A relevant question to ask may be: how many meters are sufficient in order to derive a reliable and unique fault location estimate for a given network? This paper addresses this question by defining and performing the fault location observability analysis. An optimal meter placement scheme is proposed for determining the optimal locations to place meters so as to make the system observable while minimizing the required number of meters to reduce costs. The proposed method is especially useful for powe...

2009-01-01

254

Evaluation of HVDC cables for the St. Lawrence crossing of Hydro-Quebec 500 kV DC Line. Part 1; Dielectric and accelerated aging tests on prototypes  

Energy Technology Data Exchange (ETDEWEB)

This paper describes the dielectric and accelerated aging tests on prototype {plus minus}500 kV dc oil-filled self-contained cables. The extensive test program was required to evaluate the High-Voltage cables for the St. Lawrence river crossing of the {plus minus}500 kV Quebec-New England HVDC power transmission system. The paper relates the main elements of the test program. It describes the required insulation levels, the characteristics of the cables supplied by three different manufacturers, as well as the cables' installation for the type tests and accelerated aging tests. Details of the test program and procedures followed to carry out the tests are given. Findings of the tests are also reported.

1992-04-01

255

Dynamic construction of outage lists for safety analysis of power transmission lines. Dynamische Erstellung von Ausfallisten fuer die Sicherheitsanalyse elektrischer Energieuebertragungssysteme  

Energy Technology Data Exchange (ETDEWEB)

An adaptive contingency selection process is set up which produces outage lists in order to guarantee on-line network security control. The quality index system used so far did not detect and reveal all critical variables due to observation problems in the mapping of two functions. The new process uses the results of the outage simulation computing of the system status just past for the drawing up of an up-to-date outage list. A linear correcting function transform the G{sub 2}-values of the standard quality index method - which still incorporate the observation problem effect - into improved values G. Studies which use data from realstic high-voltage networks prove that the detection of critical variables is far superior to ordinary methods. (orig.).

1990-04-23

256

Danger: high voltage  

Science.gov (United States)

Electric utilities have been surprised by recent opposition to the construction of very-high-voltage transmission lines, which met with little resistance in the past. Concerns over health and safety factors are associated with the increase in the number of such lines, although their presence has always been an inconvenience and a hazard for those living and working in the immediate vicinity. The new lines present additional hazards due to the continuous flow of small electric currents and the charges that build up in the area of the towers and lines. The lines are also a threat to persons wearing cardiac pacemakers. There is experimental evidence from the Soviet Union and the U.S. that electric and magnetic fields at the frequencies of such power lines can have serious biological effects on growth rates and the functioning of the central nervous system. Full disclosure that possible risks are involved and the opportunity to avoid these risks is ...

1978-05-01

257

Complexity Adjusted Soft-Output Sphere Decoding by Adaptive LLR Clipping  

CERN Document Server

A-posteriori probability (APP) receivers operating over multiple-input, multiple-output channels provide enhanced performance at the cost of increased complexity. However, employing full APP processing over favorable transmission environments, where less efficient approaches may already provide the required performance at a reduced complexity, results in waste of resources (e.g, processing energy/power). Therefore, for slowly varying channel statistics, substantial complexity savings can be achieved by simple adaptive schemes which perform performance tracking and adjust the complexity of the soft output sphere decoder by adaptively setting the related log-likelihood ratio (LLR) clipping value.

2010-01-01

258

Anderson introduces a new biomass baler  

Energy Technology Data Exchange (ETDEWEB)

Canadian-based Anderson Group Company has developed an innovative round baler for harvesting a large variety of woody biomass. The baler was initially developed in 2005 in collaboration with the University Laval and Agriculture and Agri-Food Canada. The third generation BIOBALER{sup TM} is currently built, engineered and commercialized by Anderson. It can produce up to 40 bales/hr in short rotations woody crops such as willow and hybrid poplar. The unit can harvest brushes up to 125 mm in diameter. A standard tractor can pull the BIOBALER in fallow or abandoned land, under power transmission lines, and between planted trees. The patented BIOBALER includes a mulcher head attachment, a choice of long or short swivel tongue, a fixed chamber and an undercarriage frame.

2010-07-01

259

Radiofrequency electromagnetic fields in the Cookridge area of Leeds  

Energy Technology Data Exchange (ETDEWEB)

On the 8 and 9 May 2002 representatives of the National Radiological Protection Board (NRPB) performed a radiofrequency electromagnetic field survey in the Cookridge area of Leeds in order to assess exposure to radio signals from transmitters mounted on a water tower/a lattice tower and a radio station tower. Guidelines on limiting exposure to radio signals have been published by NRPB and the International Commission on Non-Ionizing Radiation Protection (ICNIRP). These guidelines are designed to prevent established adverse effects on human health. During this survey, the total exposures due to all radio signals from 30 MHz to 18000 MHz (18 GHz) were measured. This frequency range was chosen as it includes mobile phone base station transmissions, which are at around 900 and 1800 MHz and super high frequency (SHF) transmissions from most of the large microwave dish antennas mounted on the towers. In addition, other major sources of radiofrequency ...

2002-07-01

260

Screening for von Willebrand disease: contribution of an automated assay for von Willebrand factor activity.  

Science.gov (United States)

Summary.? Measuring von Willebrand factor (VWF) activity is essential to the diagnosis of von Willebrand disease (VWD). The VWF activity is usually assessed based on measurement of the ristocetin cofactor (VWF:RCo). However, that test is technically challenging and has high intra- and inter-assay variabilities. The HemosIL VWF activity (VWF:AC) is a fully automated assay, recently proposed as a good alternative to VWF:RCo for VWD diagnosis. This study was undertaken to assess this new method. First, the analytical performance of VWF:AC on an automated coagulo-meter (ACLTop) was determined, and then this new method was compared with VWF:RCo and the platelet function analyzer (PFA100) for 160 patients referred for VWD screening. The VWF:AC achieved acceptable precision with within-run and between-run coefficients of variation ranging from 2.3% to 14.1%, and linearity from 10% to 100%. Despite some marked differences between ...

2011-09-28

261

Modification of adenylate cyclase by photoaffinity analogs of forskolin  

Energy Technology Data Exchange (ETDEWEB)

Photoaffinity labeling analogs of the adenylate cyclase activator forskolin (PF) have been synthesized, purified and tested for their effect on preparations of membrane-bound, Lubrol solubilized and forskolin affinity-purified adenylate cyclase (AC). All analogs of forskolin significantly activated AC. However, in the presence of 0.1 to 0.3 microM forskolin, the less active forskolin photoaffinity probes at 100 microM caused inhibition. This inhibition was dose-dependent for PF, suggesting that PF may complete with F for the same binding site(s). After cross-linking (125I)PF-M to either membrane or Lubrol-solubilized AC preparations by photolysis, a radiolabeled 100-110 kDa protein band was observed after autoradiography following SDS-PAGE. F at 100 microM blocked the photoradiolabeling of this protein. Radioiodination of forskolin-affinity purified AC showed several protein bands on autoradiogram, ...

1989-01-01

262

Horizontal vibration suppression method suitable for super-high-speed elevators; Chokosoku elevator ni tekishita kago yokoshindo yokusei hoshiki  

Energy Technology Data Exchange (ETDEWEB)

Horizontal vibrations of elevator cars mainly occur because a car swings as roller guides installed at corners of a car frame move on a winding guide rail at high speeds. Rider comfort in high speed elevators is worsened by these vibrations. Conventional active dampers suppressing horizontal vibrations using ac servo motors make cars heavier so driving power becomes larger, and they are not easily applied to existing elevators. An active damping control method suited to super-high-speed elevators is which can solve these problems. The method suppresses vibrations by generating only enough magnetic force needed to suppress them only when vibrations of the car franc are produced. The vibrations are detected using acceleration detectors and magnets installed on left and right sides of the car frame. A computer simulator was made to analyze phenomena of car vibrations and to verify effects of the proposed magnetic damping controller. It was found ...

1998-03-01

263

Electrochemical noise measurements of sustained microbially influenced pitting corrosion in a laboratory flow loop system.  

Energy Technology Data Exchange (ETDEWEB)

Because of the chaotic nature of the corrosion process and the complexity of the electrochemical noise signals that are generated, there is no generally accepted method of measuring and interpreting these signals that allows the consistent detection and identification of sustained localized pitting (SLP) as compared to general corrosion. We have reexamined electrochemical noise analysis (ENA) of localized corrosion using different hardware, signal collection, and signal processing designs than those used in conventional ENA techniques. The new data acquisition system was designed to identify and monitor the progress of SLP by analyzing the power spectral density (PSD) of the trend of the corrosion current noise level (CNL) and potential noise level (PNL). Each CNL and PNL data point was calculated from the root-mean- square value of the ac components of current and potential fluctuation signals, which were measured simultaneously during a short ...

1999-01-13

264

Influence of mechanical bending and temperature on the threshold voltage instability of a-Si:H thin-film transistors under electrical stress  

British Library Electronic Table of Contents (United Kingdom)

This paper studies the electrical characteristics of hydrogenated amorphous silicon thin-film transistors (a-Si:H TFTs) under flat and bending situations after AC/DC stress at different temperatures. Stress temperature was varied from 77K to 400K, and threshold voltage shifts were extracted to analyze degradation mechanisms. It was found that high temperature and mechanical bending played important roles under AC stress, with an enhanced stress effect resulting in a more serious degradation. This study also discusses the dependence between the accumulated sum of bias rising and falling time and the threshold voltage shifts under AC stress.

2011-01-01

265

Improving acetic acid production of Acetobacter pasteurianus AC2005 in hawthorn vinegar fermentation by using beer for seed culture  

British Library Electronic Table of Contents (United Kingdom)

Summary Fruit vinegar can be obtained biologically from the fermentation of fruit wine using species of the genera Acetobacter. However, the productivity of vinegar is generally low because of the inhibition by substrate ethanol and product acetic acid. In this research, the yield of acetic acid, as well as the cell growth, in hawthorn vinegar fermentation was enhanced using beer for seed preparation. The higher yield of acetic acid of AC2005 was because of the higher alcohol dehydrogenase and aldehyde dehydrogenase activities caused by using beer for seed preparation. Furthermore, Acetobacter pasteurianus AC2005 showed acid stability during the fed batch fermentation of hawthorn vinegar.

2010-01-01

266

Evaluation of CO2 adsorption capacity of solid sorbents  

British Library Electronic Table of Contents (United Kingdom)

The CO2 adsorption capacity of the low-cost solid sorbents of waste tire char (TC) and chicken waste char (CW) was compared with commercial active carbon (AC) and 5?? zeolite (ZA) using thermogravimetric analysis (TG), pressurized TG, and differential scanning calorimetry (DSC). The sorbents were degassed in a TG up to 150??C to release all gases on the surface of the sample, then cooled down to the designed temperature for adsorption. TG results indicated that the CO2 adsorption capacity of TC was higher than that of CW, but lower than those of AC and ZA. The maximum adsorption rate of TC at 50??C was 0.61% min?1, lower than that of AC, but higher than that of CW, 0.44% min?1. The maximum adsorption rate of ZA at 50??C was 3.1% min?1. When the pressure was over 4?bar, the adsorption rate ...

2011-01-01

267

Comparison between two different designs in the AC voltage measurement  

British Library Electronic Table of Contents (United Kingdom)

In this paper, a comparison is done between two different techniques in measuring the AC voltage. The first technique is the single junction thermal voltage converters (SJTVC) which consist of one thermal element (TE) which its output e.m.f. in the range of 7-12mV and the other is the new designed thermal voltage converters which consist of a number of TEs connected in parallel, series and series/parallel to increase their output e.m.f. (becomes in the range of 35-51mV). The effect of increasing the output e.m.f. is studied in this paper through evaluating the uncertainty budget and proved that its increase has a great effect on the accuracy and the uncertainty of the AC voltage measurement.

2011-01-01

268

Communication Apprehension and Resting Alpha Range Asymmetry in the Anterior Cortex  

British Library Electronic Table of Contents (United Kingdom)

In this study, we examined the relationship between trait-like communication apprehension (CA) and resting alpha range asymmetry in the anterior cortex (AC). Although theory and research in cognitive neuroscience suggest that asymmetry in the AC constitutes a relatively stable, inborn, substrate of emotion, some studies indicate that asymmetry can be increased by experimentally induced transitory anxiety. Transitory anxiety produced by interaction with strangers covaries with trait-like CA, raising questions regarding whether asymmetrical electrical activity in the AC during data collection represents resting levels as assumed in the literature or transitory reactions to dyadic interaction with the experimenter. Because the question if unanswered poses issues for theory and approaches to r...

2011-01-01

269

11. Preparation of natural radioactive materials  

International Nuclear Information System (INIS)

Uranium and thorium ores are the source of natural radionuclides. Briefly described are the original and current methods of long-lived nuclide separation ("2"3"8U, "2"3"5U, "2"2"6Ra, "2"3"0Th, "2"3"1Pa, "2"2"7Ac, "2"3"2Th, "2"2"8Ra+"2"2"8Ac, "2"2"8Th), some short-lived nuclides ("2"3"4Th and "2"2"8Ac), radon, short-lived radon daughter products and long-lived radon daughter products ("2"1"0Pb, "2"1"0Bi, "2"1"0Po). Some nuclides, such as "2"1"0Po or "2"3"1Pa can more easily be producedin reactors. (Ha).

270

Scaling up prevention programmes to reduce the sexual transmission of HIV in China  

UK PubMed Central (United Kingdom)

Background Since 2007, sex has been the major mode of HIV transmission in China, accounting for 75% of new infections in 2009. Reducing sexual transmission is a major challenge for China...Full Text Available

2010-12-01

271

Relationship Between Exposure, Clinical Malaria, and Age in an Area of Changing Transmission Intensity  

UK PubMed Central (United Kingdom)

The relationship between malaria transmission intensity and clinical disease is important for predicting the outcome of control measures that reduce transmission. Comparisons of hospital data...Full Text Available

2008-08-01

272

Knowledge and behaviour of nurse/midwives in the prevention of vertical transmission of HIV in Owerri, Imo State, Nigeria: a cross-sectional study  

UK PubMed Central (United Kingdom)

BackgroundMother-to-Child Transmission (MTCT) of HIV remains the main mode of acquisition of HIV in children. Transmission of HIV may occur during pregnancy, delivery or breastfeeding....Full Text Available

273

Loaded Transducer Fpr Downhole Drilling Component  

Energy Technology Data Exchange (ETDEWEB)

A robust transmission element for transmitting information between downhole tools, such as sections of drill pipe, in the presence of hostile environmental conditions, such as heat, dirt, rocks, mud, fluids, lubricants, and the like. The transmission element maintains reliable connectivity between transmission elements, thereby providing an uninterrupted flow of information between drill string components. A transmission element is mounted within a recess proximate a mating surface of a downhole drilling component, such as a section of drill pipe. To close gaps present between transmission elements, transmission elements may be biased with a "spring force," urging them closer together.

2005-07-05

274

Underground high-power transmission: first results of testing a 110 kV lowpressure oil-filled cable with a water cooled conductor in Berlin (West), Germany  

Energy Technology Data Exchange (ETDEWEB)

The Berliner Kraft- u. Licht (BEWAG)AG have been conducting investigations during the last several years on a 110 kV low-pressure oil-filled high-power cable with a water cooled conductor and a load capacity of 950 MVA at 110 kV. After successful transport of the cable drums (weight: 16 metric tons; diameter: 4.9 m) from the manufacturing in Cologne, West Germany, to Berlin (West), and after laying of the cable over a 300 m stretch, the commissioning tests in accordance with IEC and VDE* standards have been concluded, and several loadings with a current of 5000 A have been performed. Now, after completion of various improvements in the test system, preparations are underway for initiation of long-term testing over a period of approx. 18 months.

1982-07-01

275

Report on system operation - A background report prepared by the Nordel Operation Committee/OPG in the Nordel project on enhancing efficient functioning of the Nordic electricity market  

Energy Technology Data Exchange (ETDEWEB)

This report contains the operation procedures in extreme situations and lessons learned from blackouts, based on a mandate given by the Operations Committee. Nordic TSOs have had common rules and principles for system operation i.e. System Operation Agreement since the late 1990s. The rules have been revised according to the system security and market changes and needs. The collaboration between system operators is regular and fruitful. The knowledge and capability to manage extreme situations of the Nordic power system has continuously increased and the recent blackouts did not show major deficiencies in operation practices. Regardless of the existing good collaboration it is important to continue development in the future in order to ensure high system security. Important development areas are security of reserve supervision and coordination of calculation procedures for transmission limits, enhancement of data exchange routines between ...

2004-12-01

276

Measurements of radio propagation in rock salt for the detection of high-energy neutrinos  

CERN Document Server

We present measurements of the transmission of radio/microwave pulses through salt in the Cote Blanche salt mine operated by the North American Salt Company in St. Mary Parish, Louisiana. These results are from data taken in the southwestern region of the 1500 ft. (457 m) deep level of the mine on our third and most recent visit to the mine. We transmitted and received a fast, high-power, broadband pulse from within three vertical boreholes that were drilled to depths of 100 ft. (30 m) and 200 ft. below the 1500 ft. level using three different pairs of dipole antennas whose bandwidths span 125 to 900 MHz. By measuring the relative strength of the received pulses between boreholes with separations of 50 m and 169 m, we deduce the attenuation of the signal attributed to the salt medium. We fit the frequency dependence of the attenuation to a power law and find the best fit field attenuation lengths to be 93 \\pm 7 m at 150 ...

2008-01-01

277

Electron flow in the SABRE linear induction adder in positive polarity  

International Nuclear Information System (INIS)

In a positive polarity induction adder each of the induction cavities is a cathode, which emits electrons at a unique potential. These broad spectrum electrons strongly affect Magnetically Insulated Transmission Line (MITL) behavior. Electron flow decreases the cavity-to-MITL coupling efficiency, and reduces the power transport efficiency along the system. Also, the operating impedance of the MITL is lowered, reducing the diode impedance required for good coupling and good total system power efficiency. It is therefore imperative to understand the details of MITL electron flow. In previous work, measurement of MITL electron flow for a twenty-stage linear induction adder (Hermes III), operated in positive polarity, was compared with simulations. There was qualitative agreement, but some differences were noted. For example, measured electron flow in the first cavities was greater than in the simulations. The authors have ...

1993-05-17

278

Electromagnetic radiation unmasked  

International Nuclear Information System (INIS)

This article describes the nature of the electromagnetic waves, what they are and how do they affect us. Current concern is focused on exposure to low level power-frequency magnetic fields like microwave radiation from mobile phones and leaking microwave ovens; high power radiation from defence and airport radars; fields close to high voltage transmission lines; radio frequency fields from industrial welders and heaters and DC magnetic fields in aluminium smelters. These fields with frequency less than 300 GHz do not carry sufficient energy to break chemical bonds and it is assumed that they cannot damage cell DNA. The amount of radiation absorbed by a human exposed to far field electromagnetic radiation (EMR) depends on the orientation and size of the person. In the 30-300 MHz range it is possible to excite resonance in the whole or partial body such as the head. It is emphasised that since there are some evidence that ...

1996-01-01

279

EMFs run aground  

International Nuclear Information System (INIS)

Presently no one knows whether electromagnetic fields (EMFs) play a role in human cancer or other ailments, though epidemiological studies over the years have suggested that possibility. A study by the Electric Power Research Institute attempted to quantify everything it could about the magnetic environment of a home, identifying not only major sources of magnetic fields, but also their frequencies, strengths, and how they fall off with distance. Sources of a homes magnetic environment include appliances, overhead powerlines, and grounding connections to metallic water pipes. Fields will vary over time, depending on how much current is passing through the electrically conductive sources. Additional contributors to a home's magnetic background may include unusual wiring in the walls, underground power lines, and near-by high voltage transmission lines. This paper summarizes the study results, indicating weak, persistant EMFs ...

1993-08-01

280

Design of multifunction anti-terrorism robotic system based on police dog  

Science.gov (United States)

Aimed at some typical constraints of police dogs and robots used in the areas of reconnaissance and counterterrorism currently, the multifunction anti-terrorism robotic system based on police dog has been introduced. The system is made up of two parts: portable commanding device and police dog robotic system. The portable commanding device consists of power supply module, microprocessor module, LCD display module, wireless data receiving and dispatching module and commanding module, which implements the remote control to the police dogs and takes real time monitor to the video and images. The police dog robotic system consists of microprocessor module, micro video module, wireless data transmission module, power supply module and offence weapon module, which real time collects and transmits video and image data of the counter-terrorism sites, and gives military attack based on commands. The system combines police dogs" ...

2007-11-01

281

Design of electron beam accelerators for microwave application  

Energy Technology Data Exchange (ETDEWEB)

Relativistic electron beams are used for generating high power microwaves. These microwave sources require electron beam generators spanning significant ranges in voltage and impedance. The pulsed power technology used to generate these electron beams is presented. Electron beam generators that produce beams with pulse durations in the 10-ns to 100-ns regime consist of an energy-storage section, pulse-shaping section, and an electron beam diode. The energy-storage section is either a Marx generator or capacitor bank-pulsed transformer. The pulse shaping is done with high-voltage transmission lines. The electron beam diode is usually a cold-cathode, space-charge-limited flow device. For longer pulses (/approximately/1 ..mu..s) the energy storage and pulse chaping can be combined. Lumped-element pulse-forming networks (PFN) can be designed to produce the desired pulse shape. The Marx generator becomes one of the elements of ...

1988-07-01

282

Design of electron beam accelerator for microwave application  

Energy Technology Data Exchange (ETDEWEB)

Relativistic electron beams are used for generating high power microwaves. These microwave sources require electron beam generators spanning significant ranges in voltage and impedance. The pulsed power technology used to generate these electron beams is presented. Electron beam generators that produce beams with pulse durations in the 10 ns to 100 ns regime consist of an energy storage section, pulse shaping section, and an electron beam diode. The energy storage section is either a Marx generator or capacitor bank-pulsed transformer. The pulse shaping is done with high-voltage transmission lines. The electron beam diode is usually a cold-cathode, space-charge-limited flow device. For longer pulses (approx.1 ..mu..s) the energy storage and pulse shaping can be combined. Lumped-element pulsed-forming networks (PFN) can be designed to produce the desired pulse shape. The Marx generator becomes one of the elements of the PFN. ...

1988-01-01

283

Design and experimental results on a terawatt magnetically controlled plasma opening switch  

Energy Technology Data Exchange (ETDEWEB)

The magnetically controlled plasma opening switch (MCPOS) is an advanced plasma opening switch that utilizes magnetic fields to improve operation. Magnetic fields always dominate terawatt, pulsed power plasma opening switches. For that reason, the MCPOS uses controlled applied magnetic fields with magnitude comparable to the self-magnetic field of the storage inductor. One applied field holds the plasma in place while energy accumulates in the storage inductor, then another applied field pushes the plasma away from the cathode to allow energy to flow downstream. Over a ten month period, an MCPOS was designed, built, and tested on DECADE Module 2 at Physics International. The peak drive current was 1.8 MA in 250 ns. The output parameters were up to 1 MA into an electron beam load. The radiation temporal pulse width averaged 60 nanoseconds full-width at half-maximum. The peak load voltage ranged from one to two megavolts. The experiments demonstrated efficient ...

1998-05-01

284

Development of an unmanned construction method in a caisson type pile foundation pit for power transmission; Soden`yo shinso kiso konai mujinka koho no kaihatsu  

Energy Technology Data Exchange (ETDEWEB)

For large transmission steel towers to be built in a mountainous area, caisson type pile foundations are often applied. The works for construction of this kind of foundation are manned operations such as drilling, arranging reinforcements, concrete laying, etc. in a narrow vertical pit which is 3m in diameter and about 20m in depth, but securing labour force of good quality for such works becomes increasingly difficult. In order to cope with the above situation and achieve reduction of costs, shortening of construction period, improvement of safety, saving of manpower, etc. a power supply company and construction companies have developed jointly a method of unmanned construction in a caisson type pile foundation pit. This method consists of the use of a caisson type pile full size excavator (this consists of an excavator proper, a vacuum soil discharging device, a monitor/controller, a load crane and a reaction pad, and performs continuously ...

1996-06-25

285

Proposal concerning calculation method of bearing power of cast-in-place piles in gravel layer; Rekiso ni okeru basho uchi kui no shijiryoku santeiho ni kansuru ichiteian  

Energy Technology Data Exchange (ETDEWEB)

The Minami-Iwaki trunk line now under construction by Tokyo Electric Power Company is an UHV transmission line which covers 130km from the central region of the Abukuma highlands, Fukushima Prefecture, through the northern ridge of the Kanto Plain to Imaichi City, Tochigi Prefecture and has 235 steel towers. About 30% of the ground along the above route is mainly layers of sand and gravel. Accordingly it has become urgent to design rationally the pile foundations in the sand and gravel layers. Hence the company has studied an estimation method of the ultimate bearing power of cast-in-place piles penetrating the sand and gravel layers and the displacement of pile heads. In this report, the result of the above study is described. The company has so far used the equations in accordance to the Meyerhof equations for the estimations of the ultimate bearing power and this time, this equations have been ...

1995-11-05

286

Early failure detection of damages of roller bearing in frequency variable wind power gears. Internal analysis methods in CM systems; Fehlerfrueherkennung von Waelzlagerschaeden in drehzahlvariablen Windgetrieben. Interne Analysemethoden in CM-Systemen  

Energy Technology Data Exchange (ETDEWEB)

In the past, Condition Monitoring Systems (CMS) still showed weaknesses during the employment in the damage diagnosis and/or early failure detection of damages of roller bearings in transmissions of wind power plants. This is not only due to the insufficient consideration of the variable frequency of the wind power plants during the internal processing. The presently used methods of analysis result from the communication technology and are used successfully for years at frequency solid systems. Usually, only too few information are at the disposal to the supplier of CMS in order to parametrize their systems on the respective application particularly. An exact knowledge of the internal structure of the object to be diagnosed is compellingly necessary for a successful diagnosis so that a loadable statement based on the acquired measuring data base becomes possible. Furthermore, one must clarify the borders of the presently ...

2010-07-01

287

Development of a tool to collect insulation oil in a cable connection box without interrupting power supply; Muteiden ni yoru cable setsuzokubakonai zetsuen`yu saishu kogu no kaihatsu  

Energy Technology Data Exchange (ETDEWEB)

While underground power transmission lines have become to use CV cables as the mainstream, existing facilities still use OF cables. Factors of OF cable deterioration include heat cycles during operation and surge intrusion. As a method to diagnose this deterioration in insulation, characteristics tests are performed by collecting insulation oil in a cable connection box. The insulation oil collection work has been done conventionally with the power line stopped to prevent danger from induction voltage. A power uninterruptible oil collection tool was developed recently. The tool consists mainly of an insulator made of epoxy resin, wherein a connection box connector is rotated and loosened by operating an insulating operation rod, with the structure not contacted directly with metallic sheath, so that insulation oil can go through the oil collecting tool and gets collected. Discussions were given on the ...

1999-02-10

288

Allocation of risks in a competitive electric market  

Energy Technology Data Exchange (ETDEWEB)

To many, recent developments in electric markets are perplexing. Competition has appeared, often in the form of new players who do not own and operate generation or transmission facilities. Yet, these players happily enter into contracts obliging them to make or take delivery of power at set prices for months or even years into the future. They seem unconcerned about predicted capacity shortages, fuel price uncertainty or unpredictable plant outages. For the most part, these new players understand these risks quite well. They simply believe in the efficacy of markets. Until recently, price ensured recovery of cost. They foresee a true market where price makes supply equal demand and cost is not a factor in the short term at least. The appearance of such players is an augury of the new industry structure, one in which specialists in taking and managing distinct business risks evolve from within or enter from outside. They take and manage price ...

1996-03-01

289

Transtelephonic Electrocardiographic Transmission in the Preparticipation Screening of Athletes  

UK PubMed Central (United Kingdom)

Transtelephonic electrocardiographic transmission (TET) is the most widespread form of telecardiology since it enables clinicians to assess patients at a distance. The purpose of this study was to assess...Full Text Available

2008-01-01

290

Defective Glycinergic Synaptic Transmission in Zebrafish Motility Mutants  

UK PubMed Central (United Kingdom)

Glycine is a major inhibitory neurotransmitter in the spinal cord and brainstem. Recently, in vivo analysis of glycinergic synaptic transmission has been pursued in zebrafish using...Full Text Available

291

UK CDHF for STP UK  

Science.gov (United States)

Original holdings are now kept by the World Data Centre C1 at RAL: http://wdcc1. bnsc.rl.ac.uk MODS DOY = 246 ADID_REF Not applicable LOGICAL_FILE_ID ...

292

Print sec333photoindex (256 pages)  

Science.gov (United States)

Electro-Magnet. Antenna Panels Types Simulated Hail Stone Damage A.Panel ...... X-Band Klystron Electro Magnet. 11. I I. 333-6104 AcBc. 333-6105 Color ...

293

Explicit risk in acute coronary syndrome management  

UK PubMed Central (United Kingdom)

At least implicitly, most clinical decisions represent an integration of disease and treatment-based risk assessments. Often, as is the case with acute coronary syndrome (ACS), these decisions need...Full Text Available

2009-06-01

294

Computational Analysis of Dynamic SPK(S8)-JP-8 Fueled ...  

Science.gov (United States)

the Advanced Distillation Curve, Energy & Fuels, Vol. 22, No. 2, pp. 11041114. http://pubs.acs.org/doi/full/10.1021/ef700562c. Lemmon, E. W., Huber, M. L., ...

295

Comparison of prasugrel and clopidogrel in patients with acute coronary syndrome undergoing percutaneous coronary intervention  

UK PubMed Central (United Kingdom)

Antiplatelet agents are the cornerstone of treatment for patients with acute coronary syndrome (ACS) undergoing percutaneous coronary intervention (PCI). Clopidogrel, when added to aspirin, has demonstrated...Full Text Available

2009-01-01

296

Characterization of genes in the cellulose-synthesizing operon (acs operon) of Acetobacter xylinum: implications for cellulose crystallization.  

UK PubMed Central (United Kingdom)

The synthesis of an extracellular ribbon of cellulose in the bacterium Acetobacter xylinum takes place from linearly arranged, membrane-localized, cellulose-synthesizing and extrusion complexes that...Full Text Available

1994-09-01

297

Antianxiety and antidepressant-like effects of AC-5216, a novel mitochondrial benzodiazepine receptor ligand  

UK PubMed Central (United Kingdom)

We investigated the ability of N-benzyl-N-ethyl-2-(7,8-dihydro-7-methyl-8-oxo-2-phenyl-9H-purin-9-yl)acetamide...Full Text Available

2004-08-01

298

Adhesive capsulitis and dynamic splinting: a controlled, cohort study  

UK PubMed Central (United Kingdom)

BackgroundAdhesive Capsulitis (AC) affects patient of all ages, and stretching protocols are commonly prescribed for this condition. Dynamic splinting has been shown effective in...Full Text Available

299

Abciximab: a reappraisal of its use in coronary care  

UK PubMed Central (United Kingdom)

Platelet reactivity plays a pivotal role in the pathogenesis of ischemic adverse events during and after acute coronary syndromes (ACS), and percutaneous coronary intervention (PCI). Glycoprotein (GP)...Full Text Available

2008-03-01

300

AC-130H Gunship Armor Upgrade Project  

Energy Technology Data Exchange (ETDEWEB)

This report covers the test methods and equipment for testing aircraft armor both hard and soft. The hard armor are the typical ceramic type while the soft armor are various types of layered composite materials. 10 figs. (JEF)

1990-09-19

301

Radioiodinated phenoxyacetic acid derivatives as potential brain imaging agents, 1; Efficient synthesis via trimethylsilyl intermediates  

Energy Technology Data Exchange (ETDEWEB)

The usefulness of radioiodination via demetallation of aryltrimethylsilanes was demonstrated. The radioiodination reaction was found to be very rapid and the regiospecific incorporation of radioiodine could be carried out with high radiochemical yields and high radiospecific activity. {sup 125}I-Labeled dimethylaminoethyl iodophenoxyacetate derivatives (5a-e), dimethylaminoethyl iodophenoxyacetamide derivatives (7a-c), iodophenoxyethyl ethylenediamine derivatives (9,14) and an iodophenoxyethylpiperazine derivative (18) were efficiently synthesized from the corresponding aryltrimethylsilyl intermediates (4a-e, 6a-c, 8, 13, 17) by this method. (author).

1989-09-01

302

Radioiodinated phenoxyacetic acid derivatives as potential brain imaging agents, 1  

International Nuclear Information System (INIS)

The usefulness of radioiodination via demetallation of aryltrimethylsilanes was demonstrated. The radioiodination reaction was found to be very rapid and the regiospecific incorporation of radioiodine could be carried out with high radiochemical yields and high radiospecific activity. "1"2"5I-Labeled dimethylaminoethyl iodophenoxyacetate derivatives (5a-e), dimethylaminoethyl iodophenoxyacetamide derivatives (7a-c), iodophenoxyethyl ethylenediamine derivatives (9,14) and an iodophenoxyethylpiperazine derivative (18) were efficiently synthesized from the corresponding aryltrimethylsilyl intermediates (4a-e, 6a-c, 8, 13, 17) by this method. (author).

303

NewProductsAndServices  

Wastenet

... John Cannaday and Ken Weddle present the framework for a Product Design Engineering project (http://engineering.dartmouth.edu/~teps/images/ProductDesign.pdf) for high school students which may have relevance at a more advanced level. David Price has created a Mechanical Engineering Design (http://www.soton.ac.uk/~cds/) site containing engineering design notes. The Virtual Reality Engineering Library Home Page at the University of Bristol (http://www.dig.bris.ac.uk/virtual_lib/) is a library ...

304

Influence of tempering on microstructure and hardness of high-temperature 9%Cr-steels; Einfluss des Anlassens auf Gefuege und Haerte warmfester 9%Cr-Staehle  

Energy Technology Data Exchange (ETDEWEB)

The influences of temperature and duration of tempering on hardness and microstructure were investigated at high-temperature martensitic and low-carbon steels with 9% chrome and the further alloying elements molybdenium, vanadium, niobium and partially tungsten. After austenitizing and subsequent air cooling the steels were tempered at temperatures below, at and above Ac{sub 1b} for different times and finally a hardness test was performed. Making use of the temperature dependence of the hardness tempering diagrams were constructed and the Hollomon-Jaffe-Parameter on the three steels was determined within its application limits. Micrographs of the structure shows the formation of the carbides and the martensite. At tempering temperatures below Ac{sub 1b} a decrease of hardness occurs, above Ac{sub 1b}, a hardness rise due to the partial austenitizing was obtained. While hardening below Ac{sub 1b}, the ...

1999-06-01

305

A. C. losses in the SSC high energy booster dipole magnets  

Energy Technology Data Exchange (ETDEWEB)

The baseline design for the SSC High Energy Booster (HEB) has dipole bending magnets with a 50 mm aperture. An analysis of the cryogenic heat load due to A.C. losses generated in the HEB ramp cycle are reported for this magnet. Included in this analysis are losses from superconductor hysteresis, yoke hysteresis, strand eddy currents, and cable eddy currents. The A.C. loss impact of 2.5 {mu}m vs. 6 {mu}m filament conductor is presented. A 60 mm aperture design is also investigated. 8 refs., 3 tabs.

1991-06-01

306

The hepatic-arterial/portal-venous scintiangiogram in alcoholic hepatitis  

Energy Technology Data Exchange (ETDEWEB)

This study was designed to identify abnormalities in the hepatic-arterial/portal-venous scintiangiogram (SA) in alcoholic hepatitis (AH). SA's were performed in 35 patients with acute alcoholic hepatitis (AAH), 8; acute alcoholic hepatitis superimposed on cirrhosis (A/C), 14; and cirrhosis (C), 13. Posterior flows were done with a bolus of 10 mCi Tc-99m sulfur colloid with computer time-activity curves over the liver and left kidney. Curves were analyzed for per cent of hepatic arterial (HA) and portal venous contribution using the slope ratio method. Hepatic arterialization was estimated from the angle of the HA component of the curve. Reversal of the relative contribution of the hepatic and portal components of total flow were seen in all groups. Although quite severe in AH, the degree of reversal could not be used to differentiate among the groups. The average HA angle in AAH was 48.3 +- 8.1, in A/C 41.5 +- 10.6, and in C 30.4 +- ...

1984-01-01

307

The hepatic-arterial/portal-venous scintiangiogram in alcoholic hepatitis  

International Nuclear Information System (INIS)

This study was designed to identify abnormalities in the hepatic-arterial/portal-venous scintiangiogram (SA) in alcoholic hepatitis (AH). SA's were performed in 35 patients with acute alcoholic hepatitis (AAH), 8; acute alcoholic hepatitis superimposed on cirrhosis (A/C), 14; and cirrhosis (C), 13. Posterior flows were done with a bolus of 10 mCi Tc-99m sulfur colloid with computer time-activity curves over the liver and left kidney. Curves were analyzed for per cent of hepatic arterial (HA) and portal venous contribution using the slope ratio method. Hepatic arterialization was estimated from the angle of the HA component of the curve. Reversal of the relative contribution of the hepatic and portal components of total flow were seen in all groups. Although quite severe in AH, the degree of reversal could not be used to differentiate among the groups. The average HA angle in AAH was 48.3 +- 8.1, in A/C 41.5 +- 10.6, and in C 30.4 +- 12.1. In ...

1984-06-05

308

7. Kassel symposium on energy systems technology: Renewable energy sources and efficient utilization of energy; 7. Kasseler Symposium Energie-Systemtechnik: Erneuerbare Energien und rationelle Energieverwendung  

Energy Technology Data Exchange (ETDEWEB)

This proceedings volume comprises 17 papers on the following subjects: Methane hydrates, compounds of gas and water; Compressed air stroage gas turbine power plants / Scheduled application for load levelling between varying wind power production and power demand; Modern pumped storage power stations in the GW range - the PSW Goldisthal example; Lead batteries - new developments and future applications; Alkaline battery systems for hybrid electric road vehicles; Lighium systems and their applications; Zinc/air cells; Hydrogen storage - metal hydride storage, compressed gas storage, LNG storage; Carbon nanofibres for hydrogen storage; Double-layer condensers - technology, cost, perslpectives; Supercondensers in motor vehicles; Superconducting magnetic energy stores; Flywheel storage - status report; Decentralized energy storage in the European integrated supply grid - the EU project DISPOWER; ...

2002-07-01

309

Enterprise energy management : Part 1  

Energy Technology Data Exchange (ETDEWEB)

The needs of large industrial, commercial, and institutional energy consumers are more closely connected with the needs of power utilities and energy services companies, a result of the evolving global energy environment. Consumer choice, competition amongst energy suppliers, and increased demand are brought about in some regions by deregulation. Increasingly, large energy consumers expect high levels of quality and reliability from the energy delivered. As a result, management of the cost and the quality of the energy product and the energy assets that produce, deliver, control and consume it requires different strategies. Three major challenges must be overcome: (1) requirement to support economic and efficient delivery, purchasing and use of energy, (2) requirement to guarantee higher levels of power quality and reliability, and (3) requirement to supply the growing demand for energy while establishing a market-based pricing system. The ...

2001-09-01

310

Development of quality assurance requirements as part of the regulatory framework in the United Kingdom  

International Nuclear Information System (INIS)

Within the United Kingdom, the regulatory body having responsibility for the licensing of nuclear installations is the Health and Safety Executive (HSE). The Nuclear Installations Inspectorate (NII) is that part of HSE which administers this function. Discussions on the applicability of quality assurance (QA) to licensed sites began in 1974, and an internal report was published in 1975. In parallel with work going on at the International Atomic Energy Agency (IAEA) to prepare Quality Assurance for Safety in Nuclear Power Plants: A Code of Practice, Safety Series No. 50-C-QA, NII published a second report in 1978 entitled A Guide to the Quality Assurance Programme for Nuclear Power Plants. In 1980, the construction of advanced gas cooled reactors at Heysham 2 and at Torness was licensed, and a condition was attached to the licences requiring the licensees to submit their QA arrangements to the NII for approval. The licensees' response was to ...

1988-11-07

311

Therapeutic Approaches to the Treatment of Botulism  

Science.gov (United States)

... above. In the initial round of experiments, the venom of Dendroaspis augustepsis was tested for its actions on neuromuscular transmission. ...

1989-10-01

313

Numerical calculation of the transient response of transmission systems using the natural spline functions, with applications on high-voltage transmission lines  

Energy Technology Data Exchange (ETDEWEB)

To determine the transient response of linear and time-invariant transmission systems which are only described for discret frequencies, it is possible to find a good functional approximation by means of the generalized impulse method, combined with the most important natural spline-interpolation functions of the first and the third degree. This procedure has been applied to calculate the step response of the transient behaviour of the zero-sequence impedance system of the high voltage transmission line.

1981-10-01

314

Methods of reducing magnetic field near the transmission lines  

International Nuclear Information System (INIS)

Due to biological effects of magnetic fields of high voltage transmission lines and induced effects on has pipe line, telecommunication system and interference with sensitive electronic equipment, many effort have been done to reduce transmission lines magnetic fields and several ideas have been introduced. In this paper we review three methods: phase split, shielded and compacted line methods. With aid of a developed software programme these methods are then applied to transmission lines and the results are analyzed.

2003-01-01

320

Study on vibration of transmission lines when gust is blowing (an interim report); Kyofuji no haiden senro no yodo ni kansuru kenkyu  

Energy Technology Data Exchange (ETDEWEB)

As an interim report on the study on vibration of transmission lines when gust is blowing, this paper introduces events of confused and other contacts between transmission lines, photographing of transmission line vibration, physical measurement on transmission line response, and development of simulation software. Events of confused contacts of high-voltage transmission lines with overhead ground wires have the following common conditions: gust blows nearly perpendicularly to the line direction; no obstacles exist in upwind directions; the wind blows upward or downward against high-voltage transmission lines; and size of the high-voltage transmission lines is 25 mm{sup 2}. According to photographs of transmission line vibration, it appears that gust caused a high-voltage transmission line on the ...

1996-03-25

321

What will keep the lights on in Ontario: Responses to a policy short-circuit  

Energy Technology Data Exchange (ETDEWEB)

Ontario's electricity industry restructuring program is reviewed, with a view to identify the reasons behind the failure of deregulation which was expected to create competition, to stabilize, or even reduce, prices to consumers, and attract serious private sector investment for the construction of new generating capacity. The report painstakingly reviews the series of events which resulted in a steep rise in electricity rates during the summer of 2002, immediately after deregulation came into effect, which led to freezing retail electricity rates and related charges by the then Conservative provincial government, and the reversal of that decision by the newly-elected Liberal government in the fall of 2003, and plans to bring back retail hydro rates that reflect the cost of production. The authors provide a discussion of policy options and a series of recommendations that are expected to create incentives to reduce and shift demand, encourage the use of more energy-efficient ...

2003-12-01

322

New trends in electricity pricing in Sweden from a utility perspective  

Energy Technology Data Exchange (ETDEWEB)

Sweden is facing a re-structured electricity market beginning January 1, 1996, implying full competition in the purchasing and selling of electricity. The transmission and distribution of electricity will remain as a franchised monopoly and this business has to be strictly separated from the electricity trading. In the monopolistic environment, pricing of electricity has been based on more or less relevant costs and a resonable rate of return. The energy charges have reflected the system short range marginal costs while the demand and fixed charges have been adapted to give a total cost level corresponding to the system average cost. Tariffs of this type, known as time-of-use tariffs, have stimulated peak shaving during peak load (high cost hours) and valley filling during low load (low cost hours), increasing the load factor. Restructuring will influence the pricing in several ways. Pricing of transmission and distribution services will be ...

1996-03-01

323

A New Approach to Studying Biological and Soft Materials Using Focused Ion Beam Scanning Electron Microscopy (FIB SEM)  

International Nuclear Information System (INIS)

Over the last decade techniques such as confocal light microscopy, in combination with fluorescent labelling, have helped biologists and life scientists to study biological architectures at tissue and cell level in great detail. Meanwhile, obtaining information at very small length scales is possible with the combination of sample preparation techniques and transmission electron microscopy (TEM) or scanning transmission electron microscopy (STEM). Scanning electron microscopy (SEM) is well known for the determination of surface characteristics and morphology. However, the desire to understand the three dimensional relationships of meso-scale hierarchies has led to the development of advanced microscopy techniques, to give a further complementary approach. A focused ion beam (FIB) can be used as a nano-scalpel and hence allows us to reveal internal microstructure in a site-specific manner. Whilst FIB instruments have been used to study and ...

2006-02-22

324

The condition monitoring of fluid-filled taped cables employed in underground transmission through dissolved gas analysis  

Energy Technology Data Exchange (ETDEWEB)

There is an urgent need to monitor the condition of fluid-filled taped (FFT) cables. The Dissolved-Gas Analysis (DGA) technique that has been successfully applied to power transformers holds great potential for the preventive maintenance of FFT cables. However, before this emerging technique can be properly applied to cables, a suitable fluid sampling and subsequent gas analysis method had to be developed, including the generation of both laboratory and field data to aid in data interpretation. Data on gas saturation levels in various cable fluids have been presented. This paper describes a novel method developed specifically for FFT cables and discusses field results so obtained. The type, distribution and concentration of gases from fluid alone and paper alone under electrical stress has been presented, including the differences between normal and not-so-normal cable systems as demonstrated by DGA. The concept of wet tensile strength has been introduced to the ...

1994-12-31

325

Study of porous silicon morphologies for electron transport  

International Nuclear Information System (INIS)

Field emitter devices are being developed for the gigatron, a high-efficiency, high frequency and high power microwave source. One approach being investigated is porous silicon, where a dense matrix of nanoscopic pores are galvanically etched into a silicon surface. In the present paper pore morphologies were used to characterize these materials. Using of Scanning Electron Microscope (SEM) and Transmission Electron Microscope (TEM) images of both N-type and P-type porous layers, it is found that pores propagate along the <100> crystallographic direction, perpendicular to the surface of (100) silicon. Distinct morphologies were observed systematically near the surface, in the main bulk and near the bottom of N-type (100) silicon lift-off samples. It is seen that the pores are not cylindrical but exhibit more or less approximately square cross sections. X-ray diffraction spectra and electron diffraction patterns verified that bulk porous ...

1993-05-17

326

Repair of failed 138kV pipe type cable line  

Energy Technology Data Exchange (ETDEWEB)

On February 9, 1995 ComEd experienced a pipe type cable failure on 138kV line 13717. Line 1737 is a bulk power transmission cable circuit connecting The Fisk and Crawford generating stations located within city limits. The line is approximately 4.5 miles long and was originally installed in 1975. This line is forced cooled, has 2,500 KCMIL copper conductors with 505 mils of paper insulation in an 8 inch pritec coated steel pipe. The splices are constructed with Voltalit castings. The failure occurred approximately 3,500 feet from Crawford Station. It was easy to locate the failure since the cable joint casing was breached resulting in the loss of approximately 2,600--2,700 gallons of dielectric fluid. Upon field examination B Phase was determined to have failed. The failure occurred 12 inches inside the casing in an area where it was impossible to install a long connector or add an additional short length of cable to create a piece out. The ...

1996-11-01

327

Photoconducting properties of ultraviolet detectors based on GaN and Al{sub 1{minus}x}Ga{sub x}N films grown by ECR-MBE  

Energy Technology Data Exchange (ETDEWEB)

GaN and Al{sub 1{minus}x}Ga{sub x}N films were grown by the method of ECR-MBE. Absorption constants as a function of wavelength were determined from transmission measurements. Photoconducting detectors were fabricated from these films and characterized in terms of their spectral response and photoconductive gain. Mobility-lifetime products were determined from the measurement of photoconductive gain. The resistivity and mobility-lifetime products of the films were varied from 10--10{sup 9} ohm-cm and 10{sup {minus}3}--10{sup {minus}8} cm{sup 2}/V respectively by changing the microwave power in the ECR discharge from 20--60 watts. The change in the mobility-lifetime product is attributed to change in the lifetimes of the photogenerated carriers. This assumption is supported by direct measurement of detector response times. Finally, the authors report for the first time, the detection of alpha particles using GaN detectors.

1997-12-31

328

Photoconducting properties of ultraviolet detectors based on GaN and Al_1_-_xGa_xN films grown by ECR-MBE  

International Nuclear Information System (INIS)

GaN and Al_1_-_xGa_xN films were grown by the method of ECR-MBE. Absorption constants as a function of wavelength were determined from transmission measurements. Photoconducting detectors were fabricated from these films and characterized in terms of their spectral response and photoconductive gain. Mobility-lifetime products were determined from the measurement of photoconductive gain. The resistivity and mobility-lifetime products of the films were varied from 10--10"9 ohm-cm and 10"-"3--10"-"8 cm"2/V respectively by changing the microwave power in the ECR discharge from 20--60 watts. The change in the mobility-lifetime product is attributed to change in the lifetimes of the photogenerated carriers. This assumption is supported by direct measurement of detector response times. Finally, the authors report for the first time, the detection of alpha particles using GaN detectors.

1996-12-02

329

PILC cable technology and accessories  

Energy Technology Data Exchange (ETDEWEB)

Studies were conducted to examine the pressure on fluid-filled cables of electric power transmission networks in the event of an oil leak. Transition splices between paper-insulated oil-impregnated cable systems (PILC) and solid dielectric cable is difficult to perform. A proper PILC is composed of a means to contain oil within the cable structure and to keep moisture out. A failure of the cable joint could occur if an oil leak dries out the paper. Since oil pressure in most PILC cables is high, strong mechanical means must be devised to contain the oil within the cable. Resin systems, heat shrink systems and wiped lead sleeves to reseal the PILC cable over the splice, are among the methods used to stop an oil leak. A system has been designed using an EPDM tube contained under mechanical pressure; it has proven to be effective over a wide range of pressure conditions. Test results utilizing this system were presented. 1 ref., 1 tab., 4 figs.

1996-08-01

330

Optical and structural properties of Ge films from ion-assisted deposition  

International Nuclear Information System (INIS)

The optical properties and microstructure of germanium (Ge) films, prepared by ion-assisted deposition (IAD) process, were investigated. The Ge films were deposited on sapphire and silicon substrates, with and without simultaneous Ar+ bombardment. Higher index films, with a refractive index 7.7% larger than that of the single crystalline Ge wafer, were obtained with the IAD process. The density of the IAD film could be 1.5% greater than that of the e-beam film. The results of the heat treatment indicated that the optical and structural properties of the IAD films were more stable. Ge nano-crystallites could be observed under high ion power density, which induced a crystalline structure in the Ge thin films. The average size of the nano-crystallites, as determined from both the X-ray diffraction data and the transmission electron microscopy images, showed that no systematic change had occurred. The results presented in this work suggest that the ...

2008-11-28

331

Oil-filled, multi-core cable with at least one conductor differing from others  

Energy Technology Data Exchange (ETDEWEB)

This patent discloses an oil-filled, multi-core, electric cable having three cores within a metal sheath suitable for underwater applications. Each core has a conductor surrounded by insulation and has substantially the same outer dimensions as the other cores. One conductor is made of copper and has a central oil duct. The other conductors are made of stranded aluminum wires in side-by-side and contacting relation and the ratio of the cross-sectional area of the metal of the copper conductor to the cross-sectional area of the metal of each aluminum conductor is the reciprocal of the ratio of the electrical conductivities thereof. One object of this invention is that of overcoming the drawbacks existing in the known oil-filled, multi-core cables, i.e. to provide cable which, in case of a rupture of the cable sheath, has fairly small leakages of insulating, fluid oil from the cable and at the same time permits a reduction in the weight of the cable for equal power ...

1987-02-03

332

Non-Destructive Testing of Bus-Bar Joints Powering LHC Superconducting Magnets, by Using Gamma Sources  

CERN Document Server

The main LHC superconducting magnets (dipoles and quadrupoles) use Rutherford type cables, stabilized electrically and thermally with copper profiles. The portions of cables are connected to each other by a soft soldering technique (Sn96Ag4) with an overlapping length corresponding to one pitch of the superconducting strands. The splice constitutes a "composite" structure with the interchanging layers of Sn96Ag4 and NbTi superconductor, located inside a Cu cage. In order to ensure a high level of reliability (failure probability not exceeding 10-8) for some 10000 connections in the LHC, a non-destructive technique to check the quantity of solder in the joint is foreseen. The technique is based on a gamma ray source (241Am) and the detection is position-sensitive in the transmission mode. Scintillating detectors of gamma rays are used and their accumulated length corresponds to the length of the radioactive source (120 mm). The method can be used in-situ, the ...

2004-01-01

333

MTX diagnostic and timing system for free-electron laser heating experiments  

International Nuclear Information System (INIS)

In the microwave tokamak experiment (MTX) program, we are concentrating on experiments using intense, free-electron laser (FEL) generated microwave pulses. In initial FEL experiments, several diagnostic instruments were operated during injection of microwave pulses with peak powers to 0.2 GW at durations of 10 ns. Fixed and spatially scanning microwave detectors and receivers and a 48-element calorimeter on the inside wall of MTX diagnosed the GW-level FEL microwave pulses. With these diagnostics, linear-wave absorption and efficiencies of transmission through the quasi-optical transport system were studied. In addition, several radially resolved measurements of plasma density, temperature, and emission were made during FEL injection and were used in the analysis of microwave absorption data. A timing system, slaved to the FEL pulse arrival time, is capable of accuracy to a few nanoseconds in order to allow measurement of heating effects on the ...

334

Leveraging the power of mesh  

Energy Technology Data Exchange (ETDEWEB)

Mesh network applications are used by utilities for metering, demand response, and mobile workforce management. This presentation provided an overview of a multi-dimensional mesh application designed to offer improved scalability and higher throughput in advanced metering infrastructure (AMI) systems. Mesh applications can be used in AMI for load balancing and forecasting, as well as for distribution and transmission planning. New revenue opportunities can be realized through the application's ability to improve notification and monitoring services, and customer service communications. Mesh network security features include data encryption, data fragmentation and the automatic re-routing of data. In order to use mesh network applications, networks must have sufficient bandwidth and provide flexibility at the endpoint layer to support multiple devices from multiple vendors, as well as support multiple protocols. It was concluded that smart meters will not ...

2006-07-01

335

High Voltage Measurements on Nine PFNs for the LHC Injection Kicker Systems  

CERN Document Server

Each of the two LHC injection kicker magnet systems must produce a kick of 1.3 T.m with a flattop duration variable up to 7.86 microseconds, and rise and fall times of less than 900 ns and 3 microseconds, respectively. A kicker magnet system consists of four 5 Ohm transmission line magnets with matching terminating resistors, four 5 Ohm Pulse Forming Networks (PFN) and two Resonant Charging Power Supplies (RCPS). Nine PFNs, together with associated switch tanks, and dump switch terminating resistors have been built at TRIUMF and all have been tested at high voltage (54 kV) to ensure that the performance is within specification. This paper describes the HV measurements, compares these results with low voltage measurements and analyses the pulse performance of the PFNs. The measurements are compared with results from PSpice simulations and small discrepancies between the predictions and measurements are explained.

2005-01-01

336

Formation of Si-nanoparticles in a microwave reactor: Comparison between experiments and modelling  

International Nuclear Information System (INIS)

The formation and growth of silicon-nanoparticles from silane in a microwave reactor was investigated. Experiments were performed for the following conditions: precursor concentration 380-2530 ppm, pressures of 20-30 mbar, microwave powers 120-300 W. The formed particles were examined in-situ with a particle mass spectrometer. Additionally, particles were collected on grids and analyzed by transmission electron microscopy, X-ray diffraction, and by determining the specific surface area by BET. The particle size was found to be in the range of 5-8 nm in diameter. A simple model was used to simulate the particle formation processes taking place inside the reactor. The microwave energy coupled into the reactor flow was treated as a spatially distributed energy source resulting in a local temperature increase. The particles were assumed to have a monodisperse size distribution. To allow an approximation of their shape they were characterized by ...

2005-02-01

337

Electromagnetic fields and cancer: how ICNIRP has dealt with the issue  

International Nuclear Information System (INIS)

Whether exposure to electromagnetic fields (EMFs) cause cancer has been vigorously debated for many years and has been the most vexing issue with which ICNIRP has had to deal during its short existence. There have been three parts of the electromagnetic spectrum that the issue of cancer has raised: static (0 Hz) magnetic fields, extremely low frequency (ELF) fields (defined as > 0-300 Hz, but concerns have been raised almost exclusively at the power frequencies of 50/60 Hz), and radiofrequency (RF) fields (300 Hz -300 GHz). By far the major problems have arisen during the construction of new high voltage transmission lines and mobile telephone systems. Actions by protest groups concerned with possible health effects, especially with cancer in children, has now reached such a scale that it is costing electrical utilities and communications companies billions of dollars annually world-wide. With such high stakes, ICNIRP has had to be extremely ...

1996-04-01

338

Dynamic Rating and Underground Monitoring System (DRUMS)  

Energy Technology Data Exchange (ETDEWEB)

Drums is an acronym for Dynamic Rating and Underground Monitoring System, with specific application to high-pressure pipe-type cable systems which are the predominant means of underground electric power transmission in the United States. The primary objective of this EPRI-sponsored feasibility study was to establish the technical feasibility of seven DRUMS functions and two novel DRUMS communication schemes. The seven DRUMS functions which monitor the system's vital and measurable parameters in real time and perform system diagnostics in the event of component deterioration, malfunction or failure are: Real Time Current Monitoring and Rating; Leak Detection and Location; Fault Location; Pothead Monitoring; Oil Monitoring; Pipe Protection; and Splice Monitoring. The two DRUMS communication schemes are internal to the pipe cable system. Mechanical Communication will use pressure pulses to transmit data along the system, while the ...

1991-07-01

339

Development of a leak location system for use on underground electric power transmission cable. Final report  

Energy Technology Data Exchange (ETDEWEB)

This report describes a study to evaluate methods for locating leaks of dielectric fluid from buried high-voltage cable systems. Two primary types of leak location systems were investigated: (1) systems that will rapidly isolate the leak within a manhole section, typically 1000-m long on a feeder that might be 30-km long; and (2) systems that will then pinpoint the location of the leak. Rapid leak isolation was accomplished by developing an enhanced conductivity oil probe which allows the injection of a small quantity of conductive oil and which indicates the path of the oil as it drifts downstream in the direction of the leak. Two methods for pinpointing the leak were proven. The more successful method was the use of trained leak location dogs which were found to have far better sensitivity than instruments and which could detect cable oil alone without the need for additives. A tracer gas injection and detection scheme was developed for use in areas where the dogs may be unsuitable. ...

1982-10-01

340

Characterization of spent fuel approved testing material--ATM-104  

Energy Technology Data Exchange (ETDEWEB)

The characterization data obtained to date are described for Approved Testing Material 104 (ATM-104), which is spent fuel from Assembly DO47 of the Calvert Cliffs Nuclear Power Plant (Unit 1), a pressurized-water reactor. This report is one in a series being prepared by the Materials Characterization Center at Pacific Northwest Laboratory (PNL) on spent fuel ATMs. The ATMs are receiving extensive examinations to provide a source of well-characterized spent fuel for testing in the US Department of Energy Office of Civilian Radioactive Waste Management (OCRWM) Program. ATM-104 consists of 128 full-length irradiated fuel rods with rod-average burnups of about 42 MWd/kgM and expected fission gas release of about 1%. A variety of analyses were performed to investigate cladding characteristics, radionuclide inventory, and redistribution of fission products. Characterization data include (1) fabricated fuel design, irradiation history, and subsequent storage and handling ...

1991-12-01

341

Characterization of spent fuel approved testing material---ATM-105  

Energy Technology Data Exchange (ETDEWEB)

The characterization data obtained to data are described for Approved Testing Material 105 (ATM-105), which is spent fuel from Bundles CZ346 and CZ348 of the Cooper Nuclear Power Plant, a boiling-water reactor. This report is one in a series being prepared by the Materials Characterization Center at Pacific Northwest Laboratory (PNL) on spent fuel ATMs. The ATMs are receiving extensive examinations to provide a source of well-characterized spent fuel for testing in the US Department of Energy Office of Civilian Radioactive Waste Management (OCRWM) Program. ATM-105 consists of 88 full-length irradiated fuel rods with rod-average burnups of about 2400 GJ/kgM (28 MWd/kgM) and expected fission gas release of about 1%. Characterization data include (1) descriptions of as-fabricated fuel design, irradiation history, and subsequent storage and handling; (2) isotopic gamma scans; (3) fission gas analyses; (4) ceramography of the fuel and metallography of the cladding; (5) ...

1991-12-01

342

Calibration of the modulation transfer function of surface profilometers with binary pseudo-random test standards: expanding the application range  

Energy Technology Data Exchange (ETDEWEB)

A modulation transfer function (MTF) calibration method based on binary pseudo-random (BPR) gratings and arrays [Proc. SPIE 7077-7 (2007), Opt. Eng. 47, 073602 (2008)] has been proven to be an effective MTF calibration method for a number of interferometric microscopes and a scatterometer [Nucl. Instr. and Meth. A616, 172 (2010)]. Here we report on a further expansion of the application range of the method. We describe the MTF calibration of a 6 inch phase shifting Fizeau interferometer. Beyond providing a direct measurement of the interferometer's MTF, tests with a BPR array surface have revealed an asymmetry in the instrument's data processing algorithm that fundamentally limits its bandwidth. Moreover, the tests have illustrated the effects of the instrument's detrending and filtering procedures on power spectral density measurements. The details of the development of a BPR test sample suitable for calibration of scanning and ...

2011-03-14

343

Calibration of the modulation transfer function of surface profilometers with binary pseudo-random test standards: Expanding the application range  

Energy Technology Data Exchange (ETDEWEB)

A modulation transfer function (MTF) calibration method based on binary pseudo-random (BPR) gratings and arrays [Proc. SPIE 7077-7 (2007), Opt. Eng. 47(7), 073602-1-5 (2008)] has been proven to be an effective MTF calibration method for a number of interferometric microscopes and a scatterometer [Nucl. Instr. and Meth. A 616, 172-82 (2010]. Here we report on a significant expansion of the application range of the method. We describe the MTF calibration of a 6 inch phase shifting Fizeau interferometer. Beyond providing a direct measurement of the interferometer's MTF, tests with a BPR array surface have revealed an asymmetry in the instrument's data processing algorithm that fundamentally limits its bandwidth. Moreover, the tests have illustrated the effects of the instrument's detrending and filtering procedures on power spectral density measurements. The details of the development of a BPR test sample suitable for calibration of scanning ...

2010-07-26

344

Adsorption based processes as alternative to common gas conditioning at underground storage facilities using Sorbead; Procedes bases sur l'adsorption comme solution de rechange dans le conditionnement du gaz dans des lieux de stockage souterrains a l'aide de Sorbead  

Energy Technology Data Exchange (ETDEWEB)

The European gas market is continuing to expand due to increased industrial, domestic and power generation demand. As a result of this demand, and the trend toward liberalization of the market, the need for storage of gas is also increasing. One key segment of the large scale storage of gas is underground storage, either in partially depleted gas or oil fields, naturally occurring caverns, aquifers and salt cavities. In most cases the gas produced after storage requires conditioning to meet the water of hydrocarbon dew point specification of the gas transmission system. For that reason export gas from storage will require gas conditioning in order to meet pipeline specifications. Adsorption as a feasible and reliable process will be presented in detail and especially in regards to hydrocarbon dew-pointing compared with other process options. (author)

2000-07-01

345

An integrated Tomographic Gamma Scanning system for non-destructive assay of radioactive waste  

Energy Technology Data Exchange (ETDEWEB)

The Tomographic Gamma Scanning (TGS) technique is a relatively new method in the field of non-destructive assay (NDA) of radioactive waste. The TGS technique combines High Resolution Gamma Spectrometry (HRGS) with Three-Dimensional (3-D) low spatial resolution transmission and emission image reconstruction techniques to achieve assay goals. When compared to the traditional methods such as Segmented Gamma Scanning (SGS), the TGS technique can yield better accuracies for cases where the radionuclide is distributed non-uniformly in a heterogeneous matrix. The TGS technique is ideally suited for low-to-moderate density waste matrices, say 1.0 g cm{sup -3} or below for 55 US gal. drums, although it can be extended to higher densities by using alternative approaches to the design or analyses. Recently Canberra Industries designed, built and characterized four such TGS systems for nuclear power plant applications. Many of the design features and the ...

2007-08-21

346

An integrated Tomographic Gamma Scanning system for non-destructive assay of radioactive waste  

International Nuclear Information System (INIS)

The Tomographic Gamma Scanning (TGS) technique is a relatively new method in the field of non-destructive assay (NDA) of radioactive waste. The TGS technique combines High Resolution Gamma Spectrometry (HRGS) with Three-Dimensional (3-D) low spatial resolution transmission and emission image reconstruction techniques to achieve assay goals. When compared to the traditional methods such as Segmented Gamma Scanning (SGS), the TGS technique can yield better accuracies for cases where the radionuclide is distributed non-uniformly in a heterogeneous matrix. The TGS technique is ideally suited for low-to-moderate density waste matrices, say 1.0 g cm"-"3 or below for 55 US gal. drums, although it can be extended to higher densities by using alternative approaches to the design or analyses. Recently Canberra Industries designed, built and characterized four such TGS systems for nuclear power plant applications. Many of the design features and the end ...

2007-08-21

347

HST/ACS observations of shell galaxies: inner shells, shell colours and dust  

CERN Document Server

AIM:Learn more about the origin of shells and dust in early type galaxies. METHOD: V-I colours of shells and underlying galaxies are derived, using HST Advanced Camera for Surveys (ACS) data. A galaxy model is made locally in wedges and subtracted to determine shell profiles and colours. We applied Voronoi binning to our data to get smoothed colour maps of the galaxies. Comparison with N-body simulations from the literature gives more insight to the origin of the shell features. Shell positions and dust characteristics are inferred from model galaxy subtracted images. RESULT: The ACS images reveal shells well within the effective radius in some galaxies (at 1.7 kpc in the case of NGC 5982). In some cases, strong nuclear dust patches prevent detection of inner shells. Most shells have colours which are similar to the underlying galaxy. Some inner shells are redder than the galaxy. All six shell galaxies show out of dynamical equilibrium dust ...

2007-01-01

348

Genetic analysis of the psychostimulant effects of nicotine in chromosome substitution strains and F2 crosses derived from A/J and C57BL/6J progenitors  

British Library Electronic Table of Contents (United Kingdom)

Previous research utilizing the AcB/BcA recombinant congenic strains (RCS) of mice mapped provisional quantitative trait loci (QTLs) for the psychostimulant effects of nicotine to multiple regions on chromosomes 7, 11, 12, 14, 16, and 17. The current study was designed to confirm these QTLs in an A/J (A)??C57Bl/6J (B6) F2 cross and a panel of B6.A chromosome substitution strains (CSS). The panel of B6.A CSS consists of 21 strains, each carrying a different A/J chromosome on a B6 background. The A??B6 F2, CSS, A, and B6 mice were tested for sensitivity to the effects of nicotine on locomotor activity using a computerized open-field apparatus. In A??B6 F2 mice two QTLs were identified which confirm those previously observed in the AcB/BcA RCS. Significant differences in the expression of ...

2009-01-01

349

FY 1999 project on the development of new industry support type international standards. Standardization of evaluation testing method of thermal properties of polymer materials; 1999 nendo shinki sangyo shiengata kokusai hyojun kaihatsu jigyo seika hokokusho. Kobunshi zairyo no netsutokusei hyoka shiken hoho no hyojunka  

Energy Technology Data Exchange (ETDEWEB)

For the purpose of proposing it to ISO, the R and D were conducted of a new evaluation method of thermal properties of polymer materials. The FY 1999 results were summarized. In this fiscal year, the development of the ac Joule heating equipment was proceeded with based on the study at the technical committee, and the measuring device was installed. In the comparative measurement with conventional methods, study was proceeded with of the laser flash method, AC calorimetry method and specific heat measurement. In the technical survey, the developmental state of the ac method, especially, was examined as a testing method of thermal properties of polymer materials. It is in the stage of the basic research by keyword selection, and the search for literature is to be made in full scale. As to the needs in the industrial circle, as a result of the questionnaire survey made, it was found out that there were a wide variety of the ...

2000-03-01

350

High-power pseudospark and BLT switches  

CERN Document Server

High-power pseudospark and BLT switches

1988-01-01

351

The VOISE Algorithm: a Versatile Tool for Automatic Segmentation of Astronomical Images  

CERN Document Server

The auroras on Jupiter and Saturn can be studied with a high sensitivity and resolution by the Hubble Space Telescope (HST) ultraviolet (UV) and far-ultraviolet (FUV) Space Telescope spectrograph (STIS) and Advanced Camera for Surveys (ACS) instruments. We present results of automatic detection and segmentation of Jupiter's auroral emissions as observed by HST ACS instrument with VOronoi Image SEgmentation (VOISE). VOISE is a dynamic algorithm for partitioning the underlying pixel grid of an image into regions according to a prescribed homogeneity criterion. The algorithm consists of an iterative procedure that dynamically constructs a tessellation of the image plane based on a Voronoi Diagram, until the intensity of the underlying image within each region is classified as homogeneous. The computed tessellations allow the extraction of quantitative information about the auroral features such as mean intensity, latitudinal and longitudinal ...

2009-01-01

352

The relationship between the Plasmodium falciparum parasite ratio in childhood and climate estimates of malaria transmission in Kenya  

UK PubMed Central (United Kingdom)

BackgroundPlasmodium falciparum morbid and fatal risks are considerably higher in areas supporting parasite prevalence ≥25%, when compared with low transmission...Full Text Available

353

The effects of high voltage transmission lines on the health of adjacent resident populations.  

UK PubMed Central (United Kingdom)

A community health survey of 438 individuals was taken to detect health problems related to high voltage electrical transmission among an adjacent residential population. Results revealed no significant...Full Text Available

1984-01-01

354

Risks of leukaemia among residents close to high voltage transmission electric lines.  

UK PubMed Central (United Kingdom)

OBJECTIVES: To reassess the risk of leukaemia associated with residential exposure near high voltage transmission electric lines of 49 kV and above in view of the recent publications. METHODS: Through...Full Text Available

1997-09-01

355

Preliminary parasitological results of a pilot mollusciciding campaign to control transmission of Schistosoma mansoni in St Lucia*  

UK PubMed Central (United Kingdom)

A mollusciciding campaign was begun in Cul-de-Sac Valley, St Lucia, at the end of 1970, following several years of epidemiological studies in which transmission of Schistosoma mansoni...Full Text Available

1976-01-01

356

Nonlinear transmission of two successive ultrashort laser pulses by a thin semiconductor film under two-photon generation of biexcitons. Giant oscillator strength model  

International Nuclear Information System (INIS)

The possibility to compress and to split laser pulses at their nonlinear optical transmission through semiconductor films was investigated

2011-07-07

357

Mitochondrial transmission during mating in Saccharomyces cerevisiae is determined by mitochondrial fusion and fission and the intramitochondrial segregation of mitochondrial DNA.  

UK PubMed Central (United Kingdom)

To gain insight into the process of mitochondrial transmission in yeast, we directly labeled mitochondrial proteins and mitochondrial DNA (mtDNA) and observed their fate after the fusion of two cells....Full Text Available

1997-07-01

358

In situ nanoindentation in a transmission electron microscope  

Science.gov (United States)

This dissertation presents the development of the novel mechanical testing technique of in situ nanoindentation in a transmission electron microscope (TEM). This technique makes it possible to simultaneously observe and quantify the mechanical behavior of nano-scale volumes of solids.

2002-12-02

359

Entry and release of transmissible gastroenteritis coronavirus are restricted to apical surfaces of polarized epithelial cells.  

UK PubMed Central (United Kingdom)

The transmissible gastroenteritis coronavirus (TGEV) infects the epithelial cells of the intestinal tract of pigs, resulting in a high mortality rate in piglets. This study shows the interaction of...Full Text Available

1994-12-01

360

A nested case-control study of maternal-neonatal transmission of hepatitis B virus in a Chinese population  

UK PubMed Central (United Kingdom)

AIM: To examine the determinants of maternal-neonatal transmission of hepatitis B virus (HBV).METHODS: A nested case-control study was conducted in Changsha, Hunan, People’s Republic...Full Text Available

2011-08-21

361

Vibration Transmissibility Characteristics of Occupied ...  

Science.gov (United States)

... The relatively large, low frequency multi-axis motions observed at the chest may be a contributor to discomfort in locomotive engineers. ...

2006-09-01

362

NEUROPLASTICITY and INNOVATION  

Science.gov (United States)

OF VOCALIZED SPEECH THROUGH. ANALYSIS OF NEURAL SIGNALS. " SYNTHETIC TELEPATHY- WIRELESS. TRANSMISSION OF DECODED. THOUGHTS. " IMPLANTABLE MEMORY-ELIMINATES ...

363

Microsoft Word - June 11 Profile.doc  

Wastenet

These pipeline networks transport gas from WA's major onshore transmission pipelines to commercial and residential customers in

364

Effects of gamma irradiation on the sperm transmission and oviposition response in Helicoverpa armigera (L. NOCTUIDAE)  

International Nuclear Information System (INIS)

Transmissions of sperm by unirradiated and irradiated cotton bollworm, Helicoverpa armigera, were studied by live dissection of females immediately after the initiation of mating. In cotton bollworm the sperm transfer was rather a complex process. In fact unirradiated males failed to transfer sperm in about 19% of their matings. When irradiated with 250 Gy and 400 Gy, aberrations of sperm transmission were about 21% and 50% respectively. The failure of spermatophore 'cap' location was an important reason of sperm transmission aberrations. When females mated to high-dose-irradiated males, their oviposition response appeared abnormal

2002-02-01

365

Contribution to the compensation of extra high voltage transmission lines  

Energy Technology Data Exchange (ETDEWEB)

An improved method to design suitable compensating schemes for extra high voltage transmission lines is presented. The technique is general and effective and will greatly facilitate the design of the optimal compensation scheme for extra high voltage transmission lines. The technique is illustrated for a typical 500 kV system. The equations developed here for voltage maxima and minima along the transmission line eliminate the need for point-to-point computation of the voltage profile. The controversy existing in the literature over the problem of making a choice between pi and tee configurations has been removed and it is established with a mathematical proof that the tee configuration requires compensating elements of lower ratings.

1987-04-01

366

An accurate fault location on mutually coupled transmission lines using synchronized sampling  

Energy Technology Data Exchange (ETDEWEB)

The mutual inductance between parallel transmission lines influences the locating of the transmission line faults. A fault location algorithm for parallel lines developed in this paper takes into account the magnetic coupling between parallel lines. The paper presents a detailed description of the developed algorithm and test results performed on a simplified real transmission line. The obtained error is less than 0.5 percent in most cases. Also, the developed algorithm is not sensitive to typical fault parameters, such as: resistance, type, location, and incidence angle. 7 refs, 4 figs, 12 tabs

1995-12-31

367

An Evaluation of the Severity of the January 1998 Ice Storm in ...  

Science.gov (United States)

... storm. There was little damage to high-voltage transmission lines and communication towers in northern New England. ...

1998-04-01

368

Silicone-rubber washers soothe vibrating transmission lines  

Science.gov (United States)

Silicone-rubber washers function as damping and articulating elements in cast-aluminum spacers that separate bundle subconductors in each phase of extra-high-voltage transmission lines. Spacer/dampers are located every 3 ft. along transmission lines on Canada's first operational 500 and 735 kV system.

1965-01-01

369

Peculiarities of Swift Proton Transmission through Tapered Glass Capillaries  

International Nuclear Information System (INIS)

A study of the 150-300 keV proton beam transmission through glass (borosilicate) tapered capillaries with different diameters of the input and output of the capillary was performed. The focusing effect was observed. The areal density of the transmitted beam is enhanced by approximately 20 times. It was shown that changing a taper angle from 0.5 deg to 1.7 deg evidences the increase of the transmission coefficient more than by 300 times keeping the initial energy spectrum of ions. (author)

2011-07-01

370

Measurement of audible noise from transmission lines  

Energy Technology Data Exchange (ETDEWEB)

The audible noise produced by corona on high-voltage transmission lines has several characteristics that differentiate it from other community noises. Transmission line noise is quite broadband and has a significant high frequency content. Special instrumentation designed to measure this type of noise pollution is described. All measuring systems have the same three basic elements: a transducer, a processing device, and an output device. Recorders, microphone devices, frequency analyzers, and meteorological instrumentation are discussed.

1981-03-01

371

Fault prediction on high voltage transmission lines  

Energy Technology Data Exchange (ETDEWEB)

The prediction of faults on high voltage transmission lines requires the detection of incipient faults, which is implemented by detection of the radio noise due to contaminated insulators, insulation deterioration, and improver connections. It is shown that the radio noise due to incipient faults is separable and identifiable from normal transmission line radio noise, hence faults can be predicted.

1982-12-01

372

Evaluation of lightning-induced overvoltages for high voltage transmission lines  

Energy Technology Data Exchange (ETDEWEB)

This paper presents some results of lightning induced over voltages for a typical high voltage transmission line configuration. The authors developed an elaborated electromagnetic coupling between the lightning channel and characteristics and the resulting induced overvoltage. The lightning current parameters, for local data, in order to determine the occurrence severity for high voltage transmission lines. (author)

2001-07-01

373

Fiscal 1996 report on the results of the subsidy operation under the Sunshine Project on the development of a geothermal water use power plant, etc. Development of the binary cycle power plant (development of the measurement while drilling system for geothermal wells); 1996 nendo New Sunshine keikaku hojo jigyo seika hokokusho. Nessui riyo hatsuden plant nado kaihatsu (binary cycle hatsuden plant no kaihatsu (chinetsusei kussakuji kotei joho kenchi system no kaihatsu))  

Energy Technology Data Exchange (ETDEWEB)

The R and D were carried out of a detecting system for measurement of data on the bottom of geothermal well, data transmission and signal processing, and an analysis system for well drilling trajectory control and well assessment while geothermal well drilling based on the data obtained by the detecting system. The paper reported the results of the technology development in fiscal 1996. In the development of the detecting system, improvement/design were conducted on a mud pulse generator constituting sonde, well bottom signal processing equipment, mode switch and inclined information sensor, and the system equivalent to the actual one was manufactured to conduct a running test at high temperature/pressure. Moreover, a test to confirm heat resistance of electronic parts was made for further improvement in heat resistance of the sonde, in order to obtain the data. In the development of an analysis system, conducted were enhancement of operability of the ...

1997-03-01

374

China: output grows with modernization  

Science.gov (United States)

In 1978, China's coal mining industry achieved an output of 618,000,000 metric tons of raw hard coal, an increase of 128,000,000 tons compared with 1977. This has been achieved primarily by increased new mine development and the modernizaion and expansion of existing mines. While 96% of China's coal is currently produced from underground mines, only 33% of this output is from full mechanized operations, i.e., mechanized longwall retreat faces. Over 1% is produced by hydraulic mining. The current Ten-Year Plan (1975-1985) established that the major thrust of new development and activity should be made particularly in the Shandong, Anhui, Henan, Guizhou, and Yunnan provinces. China is presently concentrating on the construction/enlargement of eight major coal mining centers, mainly in the north and northeast of the country, each with a designed capacity in excess of 10,000,000 tons a year. China has elected to import large quantities of mining machinery and equipment, ...

1979-11-01

375

Optimum arrangements of the phase conductors of overhead transmission lines for the electric field minimization  

Energy Technology Data Exchange (ETDEWEB)

The magnitude of electric and magnetic fields around a high voltage three-phase transmission line was studied. A three-phase transmission circuit with parallel conductors produces rotating elliptic electric and magnetic fields. This study investigated the optimum arrangement of the phase conductors to minimize the maximum value of the magnetic flux density and to minimize the intensity of the resultant electric field. Two different types of high voltage double circuit transmission lines of 400 kV were considered. The optimum arrangement of the phase conductors was determined. It was concluded that the optimum arrangement can be easily applied to already constructed high voltage transmission lines by properly interchanging the phase conductors at the substations. 10 refs., 1 tab., 4 figs.

1997-12-31

376

Optimum arrangements of the phase conductors of overhead transmission lines for the electric field minimization  

International Nuclear Information System (INIS)

The magnitude of electric and magnetic fields around a high voltage three-phase transmission line was studied. A three-phase transmission circuit with parallel conductors produces rotating elliptic electric and magnetic fields. This study investigated the optimum arrangement of the phase conductors to minimize the maximum value of the magnetic flux density and to minimize the intensity of the resultant electric field. Two different types of high voltage double circuit transmission lines of 400 kV were considered. The optimum arrangement of the phase conductors was determined. It was concluded that the optimum arrangement can be easily applied to already constructed high voltage transmission lines by properly interchanging the phase conductors at the substations. 10 refs., 1 tab., 4 figs.

1997-08-24

377

High-Voltage Transmission Lines: The Ongoing Search for Biological Effects.  

Energy Technology Data Exchange (ETDEWEB)

During the early 1970s, controversy developed over the possible biological effects of electric fields from new 500-kilovolt and 765-kilovolt transmission lines. This, along with growing interest in advancing transmission voltage into the ultrahigh-voltage range (1000 kilovolts and above), led to the initiation of numerous research projects. Several reviews of this research by scientists in the US and other countries indicate that transmission lines have not been proven to be a health hazard to people or animals. The issue remains controversial, however, because research has confirmed some subtle effects of electric fields, and because it is an inseparable part of the public opposition that often accompanies the siting of high-voltage transmission lines. In addition, there is renewed interest in magnetic fields, including a possible association between such fields and human cancers. 2 figures, 2 tables.

1984-12-20

378

Electrical Transmission Line Diametrical Retention Mechanism  

Science.gov (United States)

The invention is a mechanism for retaining an electrical transmission line. In one embodiment of the invention it is a system for retaining an electrical transmission line within downhole components. The invention allows a transmission line to be attached to the internal diameter of drilling components that have a substantially uniform drilling diameter. In accordance with one aspect of the invention, the system includes a plurality of downhole components, such as sections of pipe in a drill string, drill collars, heavy weight drill pipe, and jars. The system also includes a coaxial cable running between the first and second end of a drill pipe, the coaxial cable having a conductive tube and a conductive core within it. The invention allows the electrical transmission line to withstand the tension and compression of drill pipe during routine drilling cycles.

2006-01-03

379

Accounting-related transmission issues  

Energy Technology Data Exchange (ETDEWEB)

Various initiatives have been undertaken by the Federal Energy Regulatory Commission (FERC) to deregulate wholesale electric energy markets. These initiatives have focused on restructuring the transmission systems in the US and recently have culminated in a proposal requiring formation of and participation in regional transmission organizations. The overall form of regulation selected to determine rates for transmission entities as well as underlying regulatory decisions reached on key issues will have profound implications for transmission entities. For example, traditional cost-based regulation would require one set of accounting and reporting rules, while incentive-based regulation may not be subject to those same rules. An overview of some of the major accounting and financial reporting issues that will need to be considered is presented.

1999-12-01

380

tgz Document (18304k)  

Science.gov (United States)

N F Q k q V N h l b hs x j p bN t gX Y I r bN X U Y Fff c o t dA A p A DA2 AC7LAR A Ak VAwt A jA A A A t A bNA A A dZA A A A A A X A A M A LA A E A A wA V A A A A oA V A A oA M A...

2011-02-17

381

lue0725b.020  

Science.gov (United States)

uJ Ccna =+!F Vl,) (On# P*9p .FGww z,r` dcb= >uD/ rN3W $ gp0w# rW8- A$c= b8aU Pkfs pmRh }>Tua }zz~ EwHc D;t' =kF9 hk6d /_sU }+>IK j'$ 0=:b "OR? ,2pz{V# U}}6 ...

382

The electrical measurement of AC losses in a three-phase tri-axial superconducting cable  

International Nuclear Information System (INIS)

In a three-phase tri-axial cable, the magnetic interaction between the phases makes the loss measurement by an electromagnetic method very complex. We developed the theoretical background showing that three-phase AC loss measurements by the electromagnetic method are, in principle, possible. We then implemented this theory in practical measurements on a 3 m long, tri-axial cable fabricated from RABiTS (rolling-assisted biaxially textured substrate) coated conductor. Initially, the proposed measurement technique was implemented in the simpler cases when the three cable phases are 180"0 out of phase, i.e. (0"0, 180"0, 360"0) or (0"0, 360"0, 180"0) rather than (0"0, 120"0, 240"0) as in a traditional three-phase system. For these cases, the currents in the phases are either in phase (360"0 phase difference) or anti-phase (180"0 phase difference). These are essentially single-phase measurements with only one transport current used as the supply for all three phases. ...

2010-09-01

383

Improved understanding of atmospheric organic aerosols via innovations in soft ionization aerosol mass spectrometry.  

Science.gov (United States)

Organic molecules are a significant and highly varied component of atmospheric aerosols. Measurement of aerosol composition and improvements in our understanding of the complex chemistry involved in their formation and aging are being aided by innovations in soft ionization aerosol MS. (To listen to a podcast about this feature, please go to the Analytical Chemistry multimedia page at pubs.acs.org/page/ancham/audio/index.html.). PMID:21275431

2011-01-24

384

Early Dynamic Risk Stratification with Baseline Troponin Levels and 90-minute ST Segment Resolution to Predict 30 Day Cardiovascular Mortality in STEMI: Analysis from CLARITY TIMI-28  

UK PubMed Central (United Kingdom)

BackgroundTroponin is the preferred biomarker for risk stratification in non-ST-elevation ACS. The incremental prognostic utility of the initial magnitude of troponin...Full Text Available

2010-06-01

385

Development of a retrofit coal combustor for industrial applications  

Energy Technology Data Exchange (ETDEWEB)

In this first quarterly technical report for DOE Contract No. DE-AC22-87PC79654, a description of the background, technology, and application is provided. The design and fabrication of advanced combustion chambers were completed during this period. Initial testing on both the bare metal and refractory lined advanced chambers were initiated. The units were tested initially with gas but primarily with coal. A Pittsburgh No. 8 pulverized coal was used for these test activities. Both advanced chambers pulsed well.

1987-01-01

386

Critical current measurements of high Tc superconductors in a scanning low temperature cryostat  

Energy Technology Data Exchange (ETDEWEB)

Maintaining uniformity of properties over long distances is one of the fabrication problems encountered with the new high {Tc} superconductors. Uniform properties are crucial in long tapes or wires with high critical current since local nonuniformities can limit the current carrying capacity of the whole piece. Transport critical currents in high {Tc} superconductors are conventionally measured with the contact 4-point probe DC current-voltage technique. This technique requires contact with the sample and and spatially averages over the region between the two voltage contacts. Two techniques have been used to infer the critical state model. The first uses the net magnetization of a suitably shaped sample in an external magnetic field. The second combines a DC magnetic field with AC induced currents to infer spatial flux profiles. The AC magnetization technique offers an advantage in that it is noncontacting; however, it also averages the ...

1991-01-01

387

Clinical Characteristics and Outcomes of Patients with Acute Coronary Syndrome and Prior Coronary Artery Bypass Grafting in a Large Middle Eastern Cohort  

UK PubMed Central (United Kingdom)

Background:Acute Coronary Syndrome (ACS) can occur in patients with prior coronary artery bypass grafting (CABG). In the Gulf Registry of acute coronary events (Gulf RACE), we identified...Full Text Available

388

CCMAP Contract  

Environmental Research Database

DescriptionCEH - Quest CCMAP see http://quest.bris.ac.uk/research/themes/CCMAP.html CCMAP (Climate-carbon modelling, assimilation and prediction) Leader: Dr. Eleanor Blyth (CEH, Wallingford) Overview and Goals CCMAP is one of QUEST's Theme 1 projects and is about to be commissioned to the Centre for Ecology and Hydrology at Wallingford. The Principal Investigator will be Dr. Eleanor Blyth, with subcontracts to the Universities of Bristol (Dr. Wolfgang Knorr, Earth Sciences and QUEST; Andy Ridgw [continued...

389

Accommodation : Accommodation, campus and Brighton : ... : University of Sussex  

Wastenet

... Further information For more detailed information on available accommodation, refer to our housing guide At home with us, visit Residential Services, or contact : T +44 (0)1273 678220 E housing@sussex.ac.uk Davidrsquo;s perspective lsquo;When my wife and I decided to study at Sussex, we applied for University accommodation. We were delighted with the lovely self-contained flat on Clifton Road in Brighton that we got via the Housing Office. ...

390

Application of a power system stabilizer in the nuclear power plant Borssele  

Energy Technology Data Exchange (ETDEWEB)

After that power fluctuations had occurred at Borssele nuclear power station it was decided to install a power system stabilizer. This stabilizer shall reduce the unwanted power fluctuations. The preliminary research and the results of measurements carried out during commissioning are described. (J.C.R.)

1985-03-01

391

Environmental concerns for high-voltage transmission lines in UNIPEDE countries  

Energy Technology Data Exchange (ETDEWEB)

High-voltage transmission lines can pose an environmental problem, especially in countries where the electricity production is at a distance from the demand location. Planning, construction, and operation of high voltage transmission lines should be conducted within a comprehensive environmental policy, which may include assessment of visual impact, landscape and wildlife protection, and reduction of health risks. This paper reviews the environmental policies and action in planning, construction, and operation as developed by the utilities members of the Union Internationale des Producteurs et Distributeurs d`Energie Electrique (UNIPEDE). The paper also presents a brief outline of the health issues associated with the effects of electromagnetic fields to humans.

1996-11-01

392

Environmental concerns for high-voltage transmission lines in UNIPEDE countries  

International Nuclear Information System (INIS)

High-voltage transmission lines can pose an environmental problem, especially in countries where the electricity production is at a distance from the demand location. Planning, construction, and operation of high voltage transmission lines should be conducted within a comprehensive environmental policy, which may include assessment of visual impact, landscape and wildlife protection, and reduction of health risks. This paper reviews the environmental policies and action in planning, construction, and operation as developed by the utilities members of the Union Internationale des Producteurs et Distributeurs d'Energie Electrique (UNIPEDE). The paper also presents a brief outline of the health issues associated with the effects of electromagnetic fields to humans.

1996-01-01

393

Electric field exposure from electric blankets  

Energy Technology Data Exchange (ETDEWEB)

Comparisons of the 60 Hz electric field exposures associated with high voltage transmission lines to those associated with common household sources can provide an important input to regulatory decisions that involve transmission line fields. Electric blankets are of interest in this context because the exposures they produce are among the most intense and prolonged of any of the household sources of 60 Hz electric field exposure. This paper presents a theoretical analysis of the body surface fields induced by electric blankets. Electric blanket exposure intensities are compared to those associated with transmission lines.

1987-04-01

394

Application of activity on node network technique to monitor progress of transmission works in Himachal Pradesh  

Energy Technology Data Exchange (ETDEWEB)

Construction of high voltage transmission lines in a difficult hilly terrain within the limited time frame calls for the adoption of modern management tools for controlling the progress. The activity on node network system for such works, in which parallel and overlapping activities are involved is highly useful and is being used in Himachal Pradesh State Electricity Board. This network system has helped the Board to provide an effective and efficient mode of progress reporting at all levels of functioning. A remarkable example is the control of construction of 190 km - 200 kV dc transmission line within four years and six months.

1987-02-01

395

Triple ion-beam studies of radiation damage effects in a 316LN austenitic alloy for a high power spallation neutron source  

Energy Technology Data Exchange (ETDEWEB)

Austenitic 316LN alloy was ion-irradiated using the unique Triple Ion Beam Facility (TIF) at ORNL to investigate radiation damage effects relevant to spallation neutron sources. The TIF was used to simulate significant features of GeV proton irradiation effects in spallation neutron source target materials by producing displacement damage while simultaneously injecting helium and hydrogen at appropriately high gas/dpa ratios. Irradiations were carried out at 80, 200, and 350 C using 3.5 MeV Fe{sup ++}, 360 keV He{sup +}, and 180 keV H{sup +} to accumulate 50 dpa by Fe, 10,000 appm of He, and 50,000 appm of H. Irradiations were also carried out at 200 C in single and dual ion beam modes. The specific ion energies were chosen to maximize the damage and the gas accumulation at a depth of {approximately} 1 {micro}m. Variations in microstructure and hardness of irradiated specimens were studied using transmission electron microscopy (TEM) and a nanoindentation ...

1997-09-01

396

The intelligent communications platform, or putting the smart into the smart grid  

Energy Technology Data Exchange (ETDEWEB)

North American technologies designed to improve electricity transmission and distribution systems were discussed. Legislation in the United States and Canada is now being implemented to ensure the widespread adoption of advanced metering technologies. Grid technologies will also be expected to address carbon dioxide (CO{sub 2}) emissions, as governments are now encouraging investment in distributed generation technologies such as solar, wind, and biodiesel energy. It is expected that smart grid systems will provide increased reliability, interoperability, 2-way communications, risk management services, and have the capacity to support new power resources. Devices will be added to the overall system in order to support smart metering applications. Advanced metering infrastructure (AMI) will use automated measurements of time-of-use energy consumption. Improved outage management detection and restoration monitoring programs will be used, as well ...

2008-11-15

397

The enhanced genomic instability was induced by alpha particle and low-energy ion irradiation in somatic cells of Arabidopsis thaliana  

International Nuclear Information System (INIS)

Although low-energy ion radiation has been proven to have a wide range of biological effects and led to fruitful achievements as a new mutagenic source for genetic modification, there still exist some disputes about its mutagenic mechanisms because of its short-penetrating property. In present research, Arabidopsis thaliana transgenic for GUS recombination substrate was used to evaluate the genomic instability induced by irradiations of alpha particle (3.3MeV) and Low-energy-Argon ion (30 KeV). A pronounced effects of alpha particle irradiation to Arabidopsis thaliana seedlings and Argon ion irradiation to seeds on the somatic homologous recombination frequency (sHRF) were reported. The sHRFs increased 1.88-fold and 2.42-fold, respectively, which indicated that the short-penetrating radiation could effectively induce the plant genomic instability in either dry seeds or seedlings with active metabolism. The local alpha particle irradiation of root was performed. Result exhibited ...

2008-08-12

398

Recent progress of the JAERI free electron laser driven by a compact superconducting RF linac  

International Nuclear Information System (INIS)

A prototype for a quasi-cw, and high-average power free electron laser (FEL) driven by a 15 MeV superconducting rf linac has been developed, and constructed at Tokai, JAERI since 1989. Cryogenic and accelerating fields' performances of four JAERI superconducting accelerator modules have been realized without any serious problem in the FEL accelerator vault and experimental hall. Since modification and related maintenance of the cryogenic refrigerator system for the driver were completed in the middle of October 1995, the system has run with no trouble, and the driver has been continuously run very successfully up to now. The optical resonator system and related electron beam transport system have been modified to realize larger acceptance than the old for both of the undulator radiation and energetic electron beam in 1995 Japanese fiscal year. In the modification, an alignment and distance measurement system has been newly developed, and successfully applied to ...

1997-02-28

399

Radwaste Drum Assay Technology by Segmented Gamma Scanning System  

Energy Technology Data Exchange (ETDEWEB)

Nuclear Act of Korea requires the manifest of low and intermediate level radioactive waste generated from nuclear power plants and other nuclear facilities prior to deliver to a disposal sites. Individual history records of the radioactive waste should be described the information about the activity of nuclides in the drum, total activity, weight, the type of waste. So a fully automated nuclide analysis assay system(non-destructive) of a radwaste drum was developed. For the nuclides that could not be analysed directly by MCA, the activities of the representative {gamma}-emitters(Cs-137, Co-60) contained in the drum were measured by using that system. Then the scaling factors were used to calculate the activities of {alpha} - and {beta}-emitters. This assay system divided a drum into 8 segments, a segment into 8 sectors to minimize analysis error, and used several methods(transmission ratio, differential peak absorption, mean density ...

2009-01-15

400

Microstructural features of dissimilar welds between 316LN austenitic stainless steel and alloy 800  

Energy Technology Data Exchange (ETDEWEB)

For joining type 316LN austenitic stainless steel to modified 9Cr-1Mo steel for power plant application, a trimetallic configuration using an insert piece (such as alloy 800) of intermediate thermal coefficient of expansion (CTE) has been sometimes suggested for bridging the wide gap in CTE between the two steels. Two joints are thus involved and this paper is concerned with the weld between 316LN and alloy 800. These welds were produced using three types of filler materials: austenitic stainless steels corresponding to 316,16Cr-8Ni-2Mo, and the nickel-base Inconel 182{sup 1}. The weld fusion zones and the interfaces with the base materials were characterised in detail using light and transmission electron microscopy. The 316 and Inconel 182 weld metals solidified dendritically, while the 16-8-2(16%Cr-8%Ni-2%Mo) weld metal showed a predominantly cellular substructure. The Inconel weld metal contained a large number of inclusions when deposited ...

2000-11-15

401

Environmental-impact assessment of dams and reservoir projects (review and a case study)  

International Nuclear Information System (INIS)

Dams and reservoirs are among one of the most sensitive of all development Project, in terms of pervasiveness of their influence in altering the environmental conditions and resources. In the present study, major dams and reservoir projects are reviewed, from the environmental point of view. Dams and Reservoir projects bring about major changes in the immediate environment, thus affecting public health, settlements, farmlands, roads and historical sites. Impacts on human population and wildlife may be profound. Tropical diseases, involving fresh-water hosts or vectors in their transmission, are often common around new reservoirs. Large lakes create limnological changes, excessive evaporation, seepage, disturbance in water-table and increased tendencies of landslides and earthquakes. Micro climatic changes are possible, such as fog formation, increased cloudiness and modified rainfall-patterns. Retention of sediment results in silting up of reservoirs. Water ...

402

Energy Conversion and Storage Program: 1992 Annual report  

Energy Technology Data Exchange (ETDEWEB)

This report is the 1992 annual progress report for the Energy Conversion and Storage Program, a part of the Energy and Environment Division of the Lawrence Berkeley Laboratory. Work described falls into three broad areas: electrochemistry; chemical applications; and materials applications. The Energy Conversion and Storage Program applies principles of chemistry and materials science to solve problems in several areas: (1) production of new synthetic fuels, (2) development of high-performance rechargeable batteries and fuel cells, (3) development of advanced thermochemical processes for energy conversion, (4) characterization of complex chemical processes and chemical species, and (5) study and application of novel materials for energy conversion and transmission. Projects focus on transport-process principles, chemical kinetics, thermodynamics, separation processes, organic and physical chemistry, novel materials, and advanced methods of analysis. Electrochemistry ...

1993-06-01

403

Energy Conversion and Storage Program. 1990 annual report  

Energy Technology Data Exchange (ETDEWEB)

The Energy Conversion and Storage Program applies chemistry and materials science principles to solve problems in (1) production of new synthetic fuels, (2) development of high-performance rechargeable batteries and fuel cells, (3) development of advanced thermochemical processes for energy conversion, (4) characterization of complex chemical processes, and (5) application of novel materials for energy conversion and transmission. Projects focus on transport-process principles, chemical kinetics, thermodynamics, separation processes, organic and physical chemistry, novel materials, and advanced methods of analysis. Electrochemistry research aims to develop advanced power systems for electric vehicle and stationary energy storage applications. Topics include identification of new electrochemical couples for advanced rechargeable batteries, improvements in battery and fuel-cell materials, and the establishment of engineering principles applicable ...

1992-03-01

404

Energy Conversion and Storage Program  

Energy Technology Data Exchange (ETDEWEB)

The Energy Conversion and Storage Program applies chemistry and materials science principles to solve problems in (1) production of new synthetic fuels, (2) development of high-performance rechargeable batteries and fuel cells, (3) development of advanced thermochemical processes for energy conversion, (4) characterization of complex chemical processes, and (5) application of novel materials for energy conversion and transmission. Projects focus on transport-process principles, chemical kinetics, thermodynamics, separation processes, organic and physical chemistry, novel materials, and advanced methods of analysis. Electrochemistry research aims to develop advanced power systems for electric vehicle and stationary energy storage applications. Topics include identification of new electrochemical couples for advanced rechargeable batteries, improvements in battery and fuel-cell materials, and the establishment of engineering principles applicable ...

1992-03-01

405

Analysis of degradation in nickel-based alloys using focused ion beam imaging and specimen preparation combined with analytical electron microscopy  

International Nuclear Information System (INIS)

Focused ion beam (FIB) microscopes have become well-established in the semiconductor industry during the past decade, and are rapidly gaining attention in the field of materials science, both as a tool for producing site specific, parallel sided transmission electron microscope (TEM) specimens and as stand alone specimen preparation and imaging systems. FIB secondary electron imaging (SEI) of nickel-based alloys, such as commercially produced Alloy 600 (approximately Ni 15Cr 10Fe 0.5C), has been demonstrated to show a high degree of sensitivity to the presence of deformation in the alloy, and FIB secondary ion imaging (SII) is particularly useful for identifying the presence of grain boundary corrosion, as secondary ion yields from metallic specimens can increase by three orders of magnitude in the presence of oxygen. This 'oxygen enhanced yield', makes FIB SII ideal for detection of corrosion at grain boundaries down to thicknesses of only a few tens of ...

2002-09-23

406

A decision support technique for the analysis of autonomous and grid-connected renewable energy systems  

International Nuclear Information System (INIS)

There is an increasing interest in using novel methods to generate electrical energy using wind and solar energy sources. Unfortunately, such energy sources are intermittent, and, therefore, conventional sources must still be available to meet demand during critical periods. In addition, renewable energy technologies are still expensive in general, although extensive research programs are being conducted to overcome this disadvantage. Hence, reliability, economic assessment and environmental impacts are three objectives to be satisfied simultaneously when designing either an autonomous or a grid-connected hybrid power generation system. The installation of any of these two systems should, undoubtedly, be preceded by an assessment of the available resources at the candidate site. In addition, many other factors are to be studied, including economics of transmission lines, site constraints, distances etc. In this thesis, the subjective judgments ...

407

Terms Beginning With \\  

Wastenet

... Microwaves, radio waves, and low-frequency electromagnetic fields from high-voltage transmission lines . Non-Methane Hydrocarbon (NMHC): The sum of all hydrocarbon air ...

408

Residential proximity to high voltage transmission lines and depressive symptomatology  

Energy Technology Data Exchange (ETDEWEB)

A number of epidemiological studies indicate an association between depression and proximity to high voltage transmission lines. These studies have been criticized, however, for using surrogate measures of electromagnetic fields (EMFs) and unstandardized measures of depression. In an effort to overcome these limitations, the Center for Epidemiological Studies Depression (CES-D) scale was administered to 152 women living either adjacent to a transmission line or one block away. Results indicate that homes adjacent to the transmission lines have an average EMF level of 4.86 milligauss at their front door and those one block away have an average of 0.68 milligauss. There was no significant difference in CES-D scores between the groups, controlling for demographic variables. There appeared to be an increase in other health effects, including cancer and miscarriages, but these findings were preliminary and need further ...

1992-01-01

409

Powertrain and apparatus using a continuously variable ratio transmission to improve fuel economy  

Energy Technology Data Exchange (ETDEWEB)

An automotive powertrain includes a conventional piston engine, a continuously variable ratio transmission, an engine speed sensor and a feedback control system. The control system adjusts both the transmission ratio and the throttle valve in the engine carburetor or fuel metering system in response to the position of the accelerator pedal and in response to the crankshaft speed as measured by the engine sensor. The transmission provides extreme overdrive gear ratios which allow the engine to be operated at wide open throttle even during moderate cruising, and, in addition, the engine carburetor or fuel metering system is calibrated to deliver to the engine a stoichiometric air-fuel mixture which is combined, before combustion, with a special proportion of recirculated exhaust gas. As a result of extensive wide open throttle engine operation with the above mentioned intake charge composition, combustion variables are ...

1981-07-28

410

Opportunistic Cooperation in Cognitive Femtocell Networks  

CERN Document Server

We investigate opportunistic cooperation between unlicensed secondary users and legacy primary users in a cognitive radio network. Specifically, we consider a model of a cognitive network where a secondary user can cooperatively transmit with the primary user in order to improve the latter's effective transmission rate. In return, the secondary user gets more opportunities for transmitting its own data when the primary user is idle. This kind of interaction between the primary and secondary users is different from the traditional dynamic spectrum access model in which the secondary users try to avoid interfering with the primary users while seeking transmission opportunities on vacant primary channels. In our model, the secondary users need to balance the desire to cooperate more (to create more transmission opportunities) with the need for maintaining sufficient energy levels for their own ...

2011-01-01

411

Nutating Mechanical Transmission (Maroth Drive Principle)  

Science.gov (United States)

... d Diameter of ro.'ling element of a cylindrical roller bearing ... L Life (B-10) of a cyl.ndrical roller bearing LACA Contact ratio ...

1974-01-01

412

Newer molecules in the treatment of schizophrenia: A clinical update  

UK PubMed Central (United Kingdom)

Schizophrenia is a heterogeneous psychiatric disorder in which multiple neurotransmitter systems have been implicated. Increased and decreased dopamine transmission in the subcortical meso-limbic and...Full Text Available

2011-04-01

413

NASA - Hurricane Season 2008: Hurricane Ike (Atlantic Ocean)  

Science.gov (United States)

The company reports that with the help of outside companies, they completed all major fixes including high-voltage transmission lines to neighborhood ...

414

NAME=\\  

Wastenet

...Systems, UWA investigating rate uplift effects of shallow foundation systems associated with high voltage transmission line support towers. This work was funded by National Grid, ...

415

Microscopic-Observation Drug-Susceptibility Assay for the Diagnosis of TB  

UK PubMed Central (United Kingdom)

BACKGROUNDNew diagnostic tools are urgently needed to interrupt the transmission of tuberculosis and multidrug-resistant tuberculosis. Rapid,...Full Text Available

2006-10-12

416

Malaria transmission in two localities in north-western Argentina  

UK PubMed Central (United Kingdom)

BackgroundMalaria is one of the most important tropical diseases that affects people globally. The influence of environmental conditions in the patterns of temporal distribution...Full Text Available

417

Interaction of legionella pneumophila and helicobacter pylori with bacterial species isolated from drinking water biofilms  

UK PubMed Central (United Kingdom)

BackgroundIt is well established that Legionella pneumophila is a waterborne pathogen; by contrast, the mode of Helicobacter pylori transmission...Full Text Available

418

High voltage transmission lines studies with the use of artificial intelligence  

Energy Technology Data Exchange (ETDEWEB)

The paper presents an alternative approach for the studies of high voltage transmission lines based on artificial intelligence and more specifically artificial neural networks (ANNs). In contrast to the existing conventional-analytical techniques and simulations which are using in the calculations empirical and/or approximating equations, this approach is based only on actual field data and actual measurements. The proposed approach is applied on high voltage transmission lines in order to calculate the lightning outages, on grounding systems in order to assess the grounding resistance and on high voltage transmission lines' polluted insulators in order to estimate the critical flashover voltage. The obtained results are very close to the actual ones for all three case studies, something which clearly implies that the ANN approach is well working and has an acceptable accuracy, constituting an additional tool of ...

2009-12-15

419

Elk distribution and spatial overlap with livestock during the brucellosis transmission risk period  

British Library Electronic Table of Contents (United Kingdom)

Summary 1.-The presence of Brucella abortus within free-ranging wildlife populations is an important conservation and management issue because of the risk of brucellosis transmission between wildlife and livestock. Predicting wildlife distributions is necessary to forecast wildlife and livestock spatial overlap and the potential for brucellosis transmission. 2.-We used Global Positioning System data collected from telemetry-collared female elk Cervus elaphus to develop resource selection function (RSF) models during the brucellosis transmission risk period (the abortion and calving periods). We validated extrapolation of predictive models at two nearby elk ranges within the Greater Yellowstone Ecosystem. Additionally, we integrated extrapolated RSF maps and domestic livestock distributions...

2011-01-01

420

Electronics in mining symposium  

Energy Technology Data Exchange (ETDEWEB)

The symposium reviewed the use of electronics in mining today. Subjects covered include control systems; remote sensing; telemetry; data transmission; microprocessors and transportation systems. 15 papers have been abstracted separately.

1984-01-01

421

Electricity transmission congestion costs: A review of recent reports  

Energy Technology Data Exchange (ETDEWEB)

Recently, independent system operators (ISOs) and others have published reports on the costs of transmission congestion. The magnitude of congestion costs cited in these reports has contributed to the national discussion on the current state of U.S. electricity transmission system and whether it provides an adequate platform for competition in wholesale electricity markets. This report reviews reports of congestion costs and begins to assess their implications for the current national discussion on the importance of the U.S. electricity transmission system for enabling competitive wholesale electricity markets. As a guiding principle, we posit that a more robust electricity system could reduce congestion costs; and thereby, (1) facilitate more vibrant and fair competition in wholesale electricity markets, and (2) enable consumers to seek out the lowest prices for electricity. Yet, examining the details suggests that, ...

2003-10-01

422

Documentation of Contact Precautions in an Electronic Health Record  

UK PubMed Central (United Kingdom)

Contact precautions are implemented to reduce transmission of multidrug-resistant organisms but may also increase hospital costs and patient complications. The goal of this study was to determine...Full Text Available

2011-07-01

423

Do pediatric emergency departments pose a risk of infection?  

UK PubMed Central (United Kingdom)

BackgroundThere is no data documenting the existence of a risk of infection transmission in ambulatory healthcare settings but concern remains. Our objective was to determine the...Full Text Available

424

Cholinergic modulation of multivesicular release regulates striatal synaptic potency and integration  

UK PubMed Central (United Kingdom)

The pleiotropic actions of neuromodulators on pre- and postsynaptic targets present challenges to disentangling the mechanisms underlying regulation of synaptic transmission. Within the striatum,...Full Text Available

2009-09-01

425

Airborne minerals and related aerosol particles: Effects on climate and the environment  

UK PubMed Central (United Kingdom)

Aerosol particles are ubiquitous in the troposphere and exert an important influence on global climate and the environment. They affect climate through scattering, transmission, and absorption of...Full Text Available

1999-03-30

426

[Pilot-plant testing for flue gas desulfurization and dust removal by activated coke].  

Science.gov (United States)

A developed flue gas desulfurization and dust removal process with a cross-flow moving bed filled with activated coke (AC) was tested on a pilot scale with the gas treatment capacity of 1000 mg x h(-t). The results show that a easy-operating and stable-running pilot-scale testing equipment can be reached, and under the conditions of testing space velocity, the feed gas temperature of 120 degrees C, SO2 concentrations of 3232-6006 mg x m(-3) and dust concentration of 89.3-1599.7 mg x m(-3), the high efficiency of flue gas desulfurization and dust removal is reached with the purity of dust less than 50 mg x m(-3). In the technology, the spent AC was regenerated by heating, and the SO2 concentration in the desorption gas is about 40.1%, which can be efficiently recovered as a sulfur resource. Favorable economy benefit can be reached by using the process. PMID:16850821

2006-05-01

427

Nuclear factor of activated T cell (NFAT) transcription proteins regulate genes involved in adipocyte metabolism and lipolysis  

Science.gov (United States)

NFAT involvement in adipocyte physiological processes was examined by treatment with CsA and/or GSK3{beta} inhibitors (Li{sup +} or TZDZ-8), which prevent or increase NFAT nuclear translocation, respectively. CsA treatment reduced basal and TNF{alpha}-induced rates of lipolysis by 50%. Adipocytes preincubated with Li{sup +} or TZDZ-8 prior to CsA and/or TNF{alpha}, exhibited enhanced basal rates of lipolysis and complete inhibition of CsA-mediated decreased rates of lipolysis. CsA treatment dramatically reduced the mRNA levels of adipocyte-specific genes (aP2, HSL, PPAR{gamma}, ACS and Adn), compared with control or TNF{alpha}-treatment, whereas Li{sup +} pretreatment blocked the inhibitory effects of CsA, and mRNA levels of aP2, HSL, PPAR{gamma}, and ACS were found at or above control levels. NFAT nuclear localization, assessed by EMSA, confirmed that CsA or Li{sup +} treatments inhibited or increased NFAT nuclear translocation, respectively. ...

2007-09-21

428

Level structure of "2"1"6At  

International Nuclear Information System (INIS)

The level structure and configurations of "2"1"6At have been studied by observing the alpha decay of "2"2"0Fr, which is in secular equilibrium with "2"2"4Ac. Six of the 16 observed states are tentatively assigned to the configuration #pi#(h_9_/_2)"3#upsilon#(g_9_/_2)"5, and four to the mixed configuration #pi#(h_9_/_2)"3#upsilon#(g_9_/_2)"4(i_1_1_/_2)+#pi#(h_9_/_2)"2(f _7_/_2)#upsilon#(g_9_/_2)"5. These two configurations in "2"1"6At are compared with the corresponding configurations in "2"1"2Bi and "2"1"0Bi. The shape transitions are traced from the quadrupole-octupole deformed "2"2"4Ac through "2"2"0Fr and "2"1"6At, to "2"1"2Bi, described by the spherical shell model, using the alpha decay sequence beginning with "2"2"8Pa. copyright 1996 The American Physical Society.

429

Impedance analysis of hydrogen adsorption on palladium in 0. 1 M NaOH solution  

Energy Technology Data Exchange (ETDEWEB)

The behaviour of hydrogen adsorption on palladium has been investigated by a.c. impedance measurements in 0.1 M NaOH solution of pH 13 at 298 K. The electrode impedance has been measured by superimposing an a.c. voltage of 5 mV amplitude ranging between 10{sup -1} and 10{sup 4} Hz on a d.c. potential range from -0.76 to 0.44 V (standard hydrogen electrode (SHE)). The equivalent circuit representing the hydrogen adsorption reaction is proposed from the analysis of the frequency dependence of electrode admittance. The capacitance, arising from the adsorbed hydrogen, has been determined as a function of applied potential by complex non-linear least-squares curve fitting method based on the proposed equivalent circuit. As the cathodic applied potential increased from -0.36 to -0.76 V (SHE), the adsorption capacitance considerably increased owing to the enhanced coverage of hydrogen adsorbed on the palladium surface. In the applied potential range ...

1991-10-21

430

Hybridization and Modification of the Ni/C{sub 60} Composites  

Science.gov (United States)

Hybridization and thermal evolution of the Ni+C{sub 60} composites, deposited on Si(001) at room temperature, were studied using Scanning Electron Microscopy, {mu}-Raman spectroscopy and Rutherford Backscattering. As-deposited, the hybrid films exhibited a granular nano-structure with Ni nano-particles encapsulated in C{sub 60} polymerized rinds. The Ni and C (C{sub 60}) distributions in a top layer were found homogeneous with a stable Ni/C (C{sub 60}) ratio; in the larger depth the distributions were inhomogeneous and their ratio dramatically varied. At elevated temperatures, all structural parameters were changed. In the subsurface layer Ni- and C (C{sub 60})-rich zones were formed (due to the induced phase separation), C{sub 60}-molecules decayed and their fragments were transformed into amorphous carbon (a-C). The free volume distribution of the stressed hybrid matter was analyzed by the Hg marker that (in a form of vapors) in-diffused in to the samples. The ...

2009-03-10

431

Gas electrode reactions in molten carbonate media. Pt. 2. Oxygen reduction kinetics on conductive oxide electrodes in (Li+K)CO/sub 3/ eutectic at 650/sup 0/C  

Energy Technology Data Exchange (ETDEWEB)

The electrode kinetics for oxygen reduction on conducting metal oxides, including lithiated NiO (formed in situ) and Sb-doped SnO/sub 2/, have been investigated. Kinetic measurements were carried out by using ac impedance and coulostatic relaxation methods. The ac behavior on the oxide electrodes was analyzed on the basis of a modified Randles-Ershler type equivalent circuit which takes into account the effect of non-faradaic components due to the semiconducting oxide films. The kinetic parameters (the charge transfer resistance and Warburg coefficient) and the interfacial parameters (the double layer capacity, film capacity and film resistance) were obtained by a least squares curve fitting method under P/sub O2//P/sub CO2/=0.9/0.1 atmosphere. The exchange current density was found to be 10 to 20 mA cm/sup -2/ at the oxide electrodes, assuming n=2. The coulostatic relaxation experiments supported the magnitude of the i/sub o/ values.

1986-01-01

432

Enhanced corrosion resistance of mild steel in hydrochloric acid solution by new thiadiazole derivatives: Electrochemical, theoretical and XPS studies  

Energy Technology Data Exchange (ETDEWEB)

In this work, a new class of thiadiazole derivatives, namely 3,5-bis(2-thienyl)-1,3,4-thiadiazole (2-TTH) and 3,5-bis(3-thienyl)-1,3,4-thiadiazole (3-TTH), have been studied as possible corrosion inhibitors for mild steel in molar hydrochloric acid (1M HCl). Polarisation curves and AC impedance methods have been used. These studies have shown that the thiadiazole derivatives were very good inhibitors for mild steel in 1M HCl. Comparison of results showed that 3-TTH was the best inhibitor. The potential of zero charge (PZC) of mild steel was studied by ac impedance method, and the mechanism of adsorption has been predicted. X-ray photoelectron spectroscopy surface analysis with thiadiazole derivatives shows that it chemisorbed at the mild steel/HCl interface. The adsorption of these inhibitors followed Langmuir's adsorption isotherm. The electronic properties of 2-TTH and 3-TTH, obtained using the AM1 semi-empirical quantum chemical ...

2004-07-01

433

Electrochemical properties of passive films on 440C stainless steel. Ph. D. Thesis  

Energy Technology Data Exchange (ETDEWEB)

Type 440C stainless steel is a high-C, high-Cr martensitic steel used in applications requiring high hardness and wear resistance in combination with moderate corrosion resistance. Typical applications include precision aerospace bearings and critical components in computer disk drives. The properties of passive films formed on 440C steel were investigated using advanced electrochemical techniques with a view to establishing a method to measure film stability directly in the passivation baths. Electrochemical measurements were sensitive to the passive film properties and were able to quantify the effect of cooling rate on passive film stability. The techniques used included linear polarization, AC impedance, small amplitude cyclic voltammetry, and coulostatic transient measurements. These provided results that exhibited excellent agreement with the AC impedance technique providing the most information about the interfacial reactions. It was ...

1990-10-01

434

Effects of Intensity and Position Modulation On Switched Electrode Electronics Beam Position Monitor Systems at Jefferson Lab  

Energy Technology Data Exchange (ETDEWEB)

Two types of switched electrode electronics beam position monitors are in use at Jefferson Lab. Together they provide accurate beam position to the control system for beam intensities between 50 nA and 2 mA. One version, called the linac style, has a switching frequency of 125 kHz. The other, called the transport type, has a switching frequency of 7 kHz. The basic system provides information to the control system at a 1 Hz update rate. The systems are regularly used to measure the AC component of beam position and energy as well as suppress this motion as part of a fast feedback system. Position data produced by the system are also acquired on an event by event basis as part of the nuclear physics program in two of the experimental halls. This paper will focus on the AC characteristics of the system. These characteristics are affected by analog filter frequencies and a time delay between the measurement of the positive electrode signal and the ...

2000-05-01

435

Development of an efficient, low-NOx domestic gas-range cooktop. Phase 3. Annual technical report, January 1986-December 1986  

Science.gov (United States)

The objective of the program is to develop a domestic cooktop with low-NOx emissions and high efficiency. During the first two phases of the program, three design concepts were developed, and two versions of developmental prototypes using the IR-Jet approach were fabricated and tested. The third phase was initiated to address the design issues of burner turndown and modulation and to conduct the field test of a prototype with one IR-Jet and three conventional burners. Two prototypes containing one IR-Jet and three conventional burners and utilizing blower speed control for air/gas modulation were fabricated. One unit employed a brushless dc motor and the other a 2-pole ac motor. The ac motor prototype was field tested. Field testing showed the need for a mechanical air/gas valve for modulation and for a 1500 Btu/hr simmer setting. A 4-inch-diameter stepped-tile configuration provided input rates from 1500 to 8000 Btu/hr. A manufacturer, Copreci ...

1987-06-01

436

Development and testing of commercial-scale, coal-fired combustion systems, Phase 3. Technical progress report, October 1990--December 1990  

Energy Technology Data Exchange (ETDEWEB)

The US Department of Energy`s Pittsburgh Energy Technology Center (PETC) is actively pursuing the development and testing of coal-fired combustion systems for residential, commercial, and industrial market sectors. In response, MTCI initiated the development of a new combustor technology based on the principle of pulse combustion under the sponsorship of PETC (Contract No. AC22-83PC60419). The initial pulse combustor development program was conducted in three phases (MTCI, Development of a Pulsed Coal Combustor Fired with CWM, Phase III Final Report, DOE Contract No. AC22-83PC60419, November 1986). Phase I included a review of the prior art in the area of pulse combustion and the development of pulse combustor design concepts. It led to the conclusion that pulse combustors offer technical and base-of-operation advantages over conventional burners and also indicated favorable economics for replacement of oil- and gas-fired equipment.

1990-12-31

437

Development and testing of commercial-scale, coal-fired combustion systems, Phase 3  

Energy Technology Data Exchange (ETDEWEB)

The US Department of Energy's Pittsburgh Energy Technology Center (PETC) is actively pursuing the development and testing of coal-fired combustion systems for residential, commercial, and industrial market sectors. In response, MTCI initiated the development of a new combustor technology based on the principle of pulse combustion under the sponsorship of PETC (Contract No. AC22-83PC60419). The initial pulse combustor development program was conducted in three phases (MTCI, Development of a Pulsed Coal Combustor Fired with CWM, Phase III Final Report, DOE Contract No. AC22-83PC60419, November 1986). Phase I included a review of the prior art in the area of pulse combustion and the development of pulse combustor design concepts. It led to the conclusion that pulse combustors offer technical and base-of-operation advantages over conventional burners and also indicated favorable economics for replacement of oil- and gas-fired equipment.

1990-01-01

438

CuBr blue light emitting electroluminescent thin film devices  

British Library Electronic Table of Contents (United Kingdom)

Abstract Visible blue cathodoluminescence (CL), photoluminescence (PL), x-ray excited optical luminescence (XEOL) and electroluminescence (EL) via Zf free excitonic emission have been obtained from CuBr thin films deposited on glass, Cr coated glass, GaAs and Si substrates. In addition to the Zf emission several peaks corresponding to Cu+ emissions via 3d94s - d10 transitions were observed on the AC EL spectrum at 2.10, 2.7, 3.03, 3.07 and 3.80 eV. X-ray diffraction (XRD) measurements confirmed that the vacuum evaporated CuBr thin films grow preferentially with a (111) orientation irrespective of the substrate. While the AC voltage source was found to have no detrimental effects on CuBr thin films, cathodic deposition of Cu metal via electrolytic decomposition was observed under steady sta...

2011-01-01

439

AC loss measurements of model and full size 50mm SSC collider dipole magnets at Fermilab  

Energy Technology Data Exchange (ETDEWEB)

Tests have recently been performed at Fermilab in order to measure the energy losses due to eddy currents and iron and superconductor magnetization. These measurements were performed on six 1.5m long model magnets and eight 15m long full scale collider dipole magnets. AC losses were measured as a function of ramp rate using sawtooth ramps from 500, to 5000 Amps for both types of magnets, while bipolar studies were additionally performed on some of the short magnets. The measured magnet voltage and current for a complete cycle are digitally integrated to yield the energy loss per cycle. Measurement reproducibility is typically 5%, with good agreement between long magnet measurements and extrapolations from short magnet measurement results. Magnetization loss measurements among similar magnet types agree to within experimental error, while eddy current losses correlate strongly with the observed dependence of quench current on ramp rate.

1992-09-01

440

The nucleotide sequence of a major species of leucine tRNA from bovine liver.  

UK PubMed Central (United Kingdom)

Through the use of a variety of post-labeling techniques, the nucleotide sequence of a major species of leucine tRNA from bovine liver was determined to be pG-G-U-A-G-C-G-U-G-m-G-C-ac-C-G-A-G-C-G-G-D-C-psi-A-A-G-G-C-m-G-C-U-G-G-A-psim-...Full Text Available

1980-02-25

441

Structural origin of optical bowing in semiconductor alloys p  

Energy Technology Data Exchange (ETDEWEB)

The principle of conservation and transferability of chemical bonds explains the recent discovery by extended x-ray absorption fine-structure measurements of two unequal anion-cation bond lengths R/sub A/C and R/sub B/C in A/sub x/B/sub 1-x/C zinc-blende semiconductor alloys despite the close adherence of the lattice constant to the average value (Vegard rule). This bond alternation, manifested as a structural distortion to a local chalcopyrite coordination around the anions, explains also most of the observed optical bowing in semiconductor alloys.

1983-08-22

442

Structural origin of optical bowing in semiconductor alloys p  

International Nuclear Information System (INIS)

The principle of conservation and transferability of chemical bonds explains the recent discovery by extended x-ray absorption fine-structure measurements of two unequal anion-cation bond lengths R/sub A/C and R/sub B/C in A/sub x/B/sub 1-x/C zinc-blende semiconductor alloys despite the close adherence of the lattice constant to the average value (Vegard rule). This bond alternation, manifested as a structural distortion to a local chalcopyrite coordination around the anions, explains also most of the observed optical bowing in semiconductor alloys.

443

Stability of coherently strained semiconductor superlattices  

International Nuclear Information System (INIS)

The excess energy of several III-V and II-VI strained-layer semiconductor superlattices (AC)_p(BC)_p is studied as a function of the repeat period p and orientation G=[001], [110], [111], and [201], using first-principles calculations. We discover a number of universal features, including the predicted instability for nearly all p's and G's with respect to bulk disproportionation, the identification of chalcopyrite as a metastable ordered structure, and the stability of all thin epitaxial [110] and [201] and most common-anion [001] superlattices relative to coherent phase separation.

444

Reliable dates for the last 50.000 years; Des dates fiables pour les 50 000 dernieres annees  

Energy Technology Data Exchange (ETDEWEB)

The accuracy of the carbon 14 dating method is dependent on the fluctuations of carbon 14 in the atmosphere over long periods of time. Fossil corals that are dated by both carbon 14 and uranium-thorium methods allows the setting of calibration curves for the carbon 14 method for the last 50.000 years. The uranium-thorium method is based on the measurement of the ratio of 2 isotopes: thorium 230 and uranium 234 that are both present in the decay chain of uranium 238. (A.C.)

2004-03-01

445

Phase separation, transport and magnetic properties of La2/3A1/3Mn1-xCoxO3, A=Ca, Sr (0.5x1)  

British Library Electronic Table of Contents (United Kingdom)

We present the low-temperature physical properties of the polycrystalline perovskite systems La2/3A1/3Mn1-xCoxO3, A=Ca, Sr (0.5x1) including electrical resistance, magnetization, ac and dc susceptibilities. The experimental data suggest the presence of correlated ferromagnetic clusters embedded in some non-ferromagnetic matrix. The systems show semiconducting behavior and negative magnetoresistance.

2008-01-01

446

PD and BD probability distribution and equiprobabilistic V-T characteristic of oil-filled transformer insulation  

Energy Technology Data Exchange (ETDEWEB)

Probability distributions of partial discharge (PD) and dielectric breakdown voltage were investigated for the typical components of oil-filled transformer insulation. The equi-probabilistic PD and BD V-t characteristics were obtained from experimental results in the time range from several ..mu..sec to 10 hours. The authors point out that there is a close relationship between the scattering of PD voltage and the inclination of V-t characteristics in a long term region for ac voltage.

1982-08-01

447

Nonlinear vibrations and chaos in electrostatic torsional actuators  

British Library Electronic Table of Contents (United Kingdom)

Electrostatic torsional micro-mirrors have wide spread use in different industries for diverse purposes. This paper investigates the development of superharmonics and chaotic responses in electrostatic torsional micro-mirrors near the pull-in condition. Appearance of nonlinear phenomena is investigated in models accounting for and disregarding the coupling of torsional and flexural deflections. Analysis of the system response to step and harmonic excitation reveals the appearance of DC and AC symmetry breaking. Increasing the amplitude of harmonic excitation, the response in the form of distinct superharmonics changes to a broad band response, where there is loss of periodicity and the response becomes chaotic. Accounting for flexural deflections in coupled model reduces the voltage thresh...

2011-01-01

448

Magnetic phase diagrams of the TbRh{sub 2-x}Pd{sub x}Si{sub 2} and TbRu{sub 2-x}Pd{sub x}Si{sub 2} systems  

Energy Technology Data Exchange (ETDEWEB)

The a.c. susceptibility and high field magnetization of TbRh{sub 2-x}Pd{sub x}Si{sub 2} and TbRu{sub 2-x}Pd{sub x}Si{sub 2} compounds were investigated up to 140 kOe. The (T, x) magnetic phase diagrams were determined. For both systems, an increase in the Pd content causes a decrease in the Neel temperature and changes the magnetization curves. (orig.)

1995-12-01

449

Lithium ionic conductivity in LiI?Li2S?La2O2Sm (m=1, 2) composite electrolyte by solid state reaction  

British Library Electronic Table of Contents (United Kingdom)

New lithium ion composite electrolyte, LiI?Li2S?La2O2Sm (m=1, 2) was synthesized from the binary Li2S?LaOI system through solid state reaction. The lithium ion conductive property was investigated by AC impedance spectroscopy. And the highest conductivity of the obtained electrolyte at room temperature was found to be 3.0?10?6?S cm?1. The notable ionic conduction was attributed to the in situ formed amorphous LiI.

2008-01-01

450

Infinite-parametric extension of the conformal algebra in D>2 space-time dimensions  

International Nuclear Information System (INIS)

On the basis of the analytic continuations of semisimple Lie algebras discovered recently by us we construct manifestly quasiconformal infinite-dimensional algebras AC(so(4, 1)) and PAC(so(3, 2)) extending the conformal algebras in three-dimensional euclidean and Minkowski space-time like the Virasoro algebra extends so(2, 1). Their higher spin generalizations are also constructed. A counterpart of the central extension for D > 2 and possible appplications in exactly solvable conformal quantum field models in D > 2 are discussed. (orig.).

1991-01-01

451

Identification of the #pi#g_9_/_2 band new levels in "1"2"1Cs  

International Nuclear Information System (INIS)

The #pi#g_9_/_2 band structure in "1"2"1Cs is obtained. The experiment was performed at the HI-13 MV tandem accelerator of China Institute of Atomic Energy. The excited states of "1"2"1Cs were populated via the reaction "1"1"2Sn("1"2C, p2n). The #gamma#-#gamma# coincidence data were taken with five BGO-AC HpGe detectors at beam energy of 60 Mev. The energy-level schemes of "1"2"1Cs is presented.

1992-01-01

452

Einstein and relativity soon out of date? Neutrinos: faster than light; Einstein et la relativite bientot depasses? Neutrinos: plus vite que la lumiere  

Energy Technology Data Exchange (ETDEWEB)

Two thirds of the neutrinos produced in the sun are not detected. In the last decade several experiments have allowed to give a limit to the neutrino mass and in some cases a negative value of the square of the mass was proposed. A negative value is inconsistent theoretically except in the case of tachyons which are particles allowed to travel faster than light. Consider neutrinos as tachyons could be a solution to find the answers to some of the riddles set by neutrinos. (A.C.)

1997-10-01

453

Development of a retrofit coal combustor for industrial applications. Technical progress report, January--March 1987  

Energy Technology Data Exchange (ETDEWEB)

In this first quarterly technical report for DOE Contract No. DE-AC22-87PC79654, a description of the background, technology, and application is provided. The design and fabrication of advanced combustion chambers were completed during this period. Initial testing on both the bare metal and refractory lined advanced chambers were initiated. The units were tested initially with gas but primarily with coal. A Pittsburgh No. 8 pulverized coal was used for these test activities. Both advanced chambers pulsed well.

1987-12-31

454

BUBL LINK: Skin cancer  

Wastenet

...CanCom Dermatology Image Bank Dermatology Online Atlas Introduction to Skin Cancer Malignant Melanoma Skin Cancer (Not Melanoma) Comments: bubl@bubl.ac.... Covers anatomy, melanoma, infections, and dermatological disorders in AIDS. Author: University of Utah ...994 Resource type: document Malignant Melanoma This leaflet on malignant melanoma covers early detection, causes, clinical signs and symptoms, and provides ...9 Resource type: document Skin Cancer (Not Melanoma) Information on basal cell and squamous cell skin cancers. Author: ...

455

BUBL LINK: Biblical studies  

Wastenet

...com: Christianity: General All-in-One Biblical Resources Search Anno Domini: Jesus Through the Centuries Bible and Homosexuality Bible Reading Fellowship Bible Society Bible ...of the New Testament Vine's Expository Dictionary of New Testament Words Virtual Christianity: Bibles Whole Bible Comments: bubl@bubl.ac.uk About....com: Christianity: General Offers original articles and features about Christianity in general plus annotated links to selected relevant Internet resources, compiled by ... Also includes a gallery of Christian images such as The Last Supper by Leonardo Da Vinci. Author: About....

456

Association analysis of the INHA gene with litter size in Boer goats  

British Library Electronic Table of Contents (United Kingdom)

This study investigated the association between differences in litter size in Boer does, with genetic polymorphisms in the inhibin alpha gene. Our preliminary (n=209) results found 12 SNPs, including the non-synonymous polymorphisms 911T/C and 946A/C, resulting in corresponding 299V/A and 311T/P amino acid polymorphisms. Of the SNPs, 651A/G was preliminarily suggested as a useful marker for litter size of the second parity in the population studied, showing an overdominance effect. Polymorphisms, sequence, and genotype distributions were also characterized.

2009-01-01

457

Active dissolution of nickel based alloys in thiosulphate solution  

International Nuclear Information System (INIS)

Repassivation resulting from the bared metal surface is a critical process for judging whether or not material suffers from corroding or immunizing. Nickel based alloys with high chromium content were developed to increase the corrosion resistant to sulphur compounds. Active humps resulting from active dissolution of nickel were obtained by creating the bared metal surfaces in thiosulphate solutions. The lower the Cr content the higher is the dissolution rate. The passive films formed on the bared metal surface were examined by ac impedance. Results suggest the formation of multi-layers oxide which were affected by active dissolution reactions during repassivation. (author).

1989-10-01

458

A journey inside infinity; Voyage au coeur de l'infini  

Energy Technology Data Exchange (ETDEWEB)

The authors draw the story of the concept of infinity in sciences from the ancient Greek civilization to modern times, from the Greek idea of atom to quantum physics and cosmology. It is shown how what was considered as limits in ancient times, have been progressively seen as unknown worlds, and are now being investigated with the use of big machines like particle accelerators. This book is composed of 3 main chapters: 1) the quest for the infinitely big, 2) the quest for the infinitely small, and 3) the big-bang theory that appears as the meeting point of the 2 infinites. (A.C.)

2010-07-01

459

A correlation between electrochemical parameters and stress corrosion cracking of alloy 600 in high temperature caustic solution  

International Nuclear Information System (INIS)

The properties of the passive films formed on Alloy 600 at different applied potentials in 10% NaOH solution at 315 .deg. C was studied using in situ AC impedance and polarization measurements. The results were correlated with the stress corrosion cracking (SCC) behavior obtained from the C-ring tests in the same conditions. The change of the semiconductive property and the peak of relaxation time were observed at 0.2 V where the SCC rate showed a maximum. These results were also consistent with the prediction parameter for SCC obtained from fast and slow polarization scans.

2001-10-01

460

Low k thin films based on rf plasma-polymerized aniline  

International Nuclear Information System (INIS)

Thermally stable materials with low dielectric constant (k<3.9) are being hotly pursued. They are essential as interlayer dielectrics/intermetal dielectrics in integrated circuit technology, which reduces parasitic capacitance and decreases the RC time constant. Most of the currently employed materials are based on silicon. Low k films based on organic polymers are supposed to be a viable alternative as they are easily processable and can be synthesized with simpler techniques. It is known that the employment of ac/rf plasma polymerization yields good quality organic thin films, which are homogenous, pinhole free and thermally stable. These polymer thin films are potential candidates for fabricating Schottky devices, storage batteries, LEDs, sensors, super capacitors and for EMI shielding. Recently, great efforts have been made in finding alternative methods to prepare low dielectric constant thin films in place of silicon-based materials. Polyaniline thin films ...

2004-06-01

461

Evaluation of cathodic dis-bonding of three types of coatings by DC and AC methods  

Energy Technology Data Exchange (ETDEWEB)

For the protection of buried steel pipeline, it is common practice to coat the pipelines with highly insulating coating and apply a cathodic current to insulate the pipe from the aggressive environment. Cathodic current protects holidays or damaged area of coating which required less current than would be needed for an uncoated pipe, but because of the cathodic reactions evolution will be taken H{sub 2} and OH{sup -} on holidays which exposed metal to the environment place. This effect is to cause loss bond of coating around the holidays called cathodic dis-bonding. In this paper we measured cathodic dis-bonding of three types of coatings at - 1.5 V(Cu/CuSO{sub 4}) according to ASTM G8. We studied on cathodic dis-bonding resistance of petroleum-base, coal tar-base and polyethylene plastic tape coatings. After 30 days immersion in electrolyte it was found that the cathodic disbanding resistance of polyethylene plastic tape coating is lower than others and high cathodic dis-bonding ...

2004-07-01

462

Characterization of activated carbon prepared from chicken waste and coal  

Energy Technology Data Exchange (ETDEWEB)

Activated carbons (ACs) were prepared from chicken waste (CW) and coal (E-coal) blended at the ratios of 100:0, 80:20, 50:50, 20:80, and 0:100. The process included carbonization in flowing gaseous nitrogen (300 mL min{sup -1}) at ca. 430{sup o}C for 60 min and successive steam activation (0.1 mL min{sup -1} water injection with a flow of N{sub 2} at 100 mL min{sup -1}) at 650{sup o}C for 30 min. Chicken waste is low in sulfur content but is high in volatile matter (about 55 wt %), and ACs with higher specific surface area were more successfully obtained by mixing with coal. The specific surface area of the CW/Coal blend AC can be estimated by SSA{sub BET} = -65.8x{sup 2} + 158x + 168, where SSA{sub BET} is the specific surface area in m{sup 2} g{sup -1} as determined by the BET method using CO{sub 2} as the adsorbent, where x is the coal fraction by weight in the CW/coal blend ranging from 0.0 to 1.0 (e.g., x = 0.0 ...

2007-12-15

463

RF Cavities and Power Amplifier for the Compact Proton Synchrotron  

CERN Document Server

RF Cavities and Power Amplifier for the Compact Proton Synchrotron

2003-01-01

464

Power in the system  

International Nuclear Information System (INIS)

May 1972. United States Warren, FH Federal Power Commission,

1972-05-01

465

Low Energy Part of the CONCERT High-Power Proton Linac  

CERN Document Server

Low Energy Part of the CONCERT High-Power Proton Linac

2001-01-01

466

Electric power generation. Thermal power generating systems. 2. rev. and enl. ed.  

International Nuclear Information System (INIS)

This is a manuscript for a lecture contents: 1. Steam power and fundamentals of the steam power process, 2. conventional, nuclear and other steam generation processes, 3. cooling systems for steam power plants, 4. gas turbine power plants and combined-cycle power plants, 5. cogeneration, 6. development of thermal power plants and environmental effects. (orig.).

467

Electric power generation. Thermal power generating systems  

International Nuclear Information System (INIS)

This is a manuscript for a lecture contents: 1) Steam power and fundamentals of the steam power process, 3) conventional, nuclear and other steam generation processes, 4) cooling systems for steam power plants, 5) gas turbine power plants and combined-cycle power plants, 6) cogeneration, 7) development of thermal power plants and environmental effects. (GL).

468

Downed Power Lines  

Medline Plus

English - Downed Power Lines Click to Stop Video Click to Start Video To Listen to the Audio ...

469

Coated Superalloys for Power Installations  

International Science & Technology Center (ISTC)

Characterization and Testing of Coated Nickel- and Iron-Based Superalloys for Application in High-Temperature Power Installations

470

Principles of ground relaying for high voltage and extra high voltage transmission lines  

Energy Technology Data Exchange (ETDEWEB)

This paper is a tutorial discussion of the basic principles of ground relaying for high voltage and extra high voltage transmission lines. Three different HV configurations are considered: Long lines, lines with a weak mid-point station, and mutually-coupled lines. Application criteria for EHV circuits are also discussed, and specific setting calculations are included where appropriate.

1983-02-01

471

PRO2000 vaginal gel for prevention of HIV-1 infection (Microbicides Development Programme 301): a phase 3, randomised, double-blind, parallel-group trial  

UK PubMed Central (United Kingdom)

SummaryBackgroundInnovative prevention strategies for HIV-1 transmission are urgently needed. PRO2000 vaginal gel was efficacious against HIV-1 transmission in studies...Full Text Available

2010-10-16

472

New concept in transmission line reclosure using high-frequency fault transients  

Energy Technology Data Exchange (ETDEWEB)

The authors present a new concept: 'adaptive optimal reclosure' under transmission line faults by integrating the adaptive and optimal reclosure techniques. Simulation studies prove that the proposed technique is able to first detect the persistence time of fault path arc and then capture the optimal reclosure time, thereby enhancing system stability. (author)

1997-07-01

473

Need and specifications for a data transmission system for the mining industry  

Energy Technology Data Exchange (ETDEWEB)

The demands made on data transmission systems by modern mining companies are used to show why the currently used multiplexers cannot satisfy future requirement. The telecommunications department of Bergbau-Forschung GmbH is now developing a telecommunication system for underground work. The requirements made on this system are reported.

1980-02-01

474

MCNPX analysis of 68 MeV neutron transmission on iron  

Energy Technology Data Exchange (ETDEWEB)

A 68 MeV neutron transmission experiment on iron has been analyzed with MCNPX using the Los Alamos LA150 neutron data library, the ECN/BRC 150 MeV neutron data library and with the intranuclear cascade code LAHET. The clear improvement of using the data libraries is confirmed. Also, other materials present in LA150 have been checked using the same MCNPX set-up. 10 refs.

1999-02-01

475

Induction effects of a 765 kV transmission line on a center pivot irrigator  

Energy Technology Data Exchange (ETDEWEB)

The use of irrigation systems in the proximity of high voltage transmission lines is increasing. This study examines the induced voltages and currents on a pivotal irrigation system operating under a 765 kV line. With a few simple precautions such as a system can be operated in complete safety. 1 ref.

1981-01-01

476

Identification and characterization of populations living near high-voltage transmission lines: a pilot study.  

UK PubMed Central (United Kingdom)

Populations living close to high-voltage transmission lines often have residential magnetic field exposures in excess of 1 microT, and sometimes over 2 microT. Yet, populations studied in most epidemiologic...Full Text Available

1993-12-01

477

Gamma ray detecting device using dislocation-free crystal  

Energy Technology Data Exchange (ETDEWEB)

This patent describes a {gamma}-ray detector. It comprises: a dislocation-free single crystal having an input surface and a transmission surface at opposite ends thereof; an active shield surrounding the crystal and functioning as an anticoincidence counter; and {gamma}-ray detector means disposed adjacent the transmission surface of the crystal for receiving and detecting {gamma}-rays of a predetermined wavelength incident on the input surface of the crystal at a specific Bragg angle and transmitted through the crystal.

1991-04-30

478

Fuel ignition by high voltage capacitive discharges  

Energy Technology Data Exchange (ETDEWEB)

The study examined the possibility for fuel ignition by spark discharge caused by induction effects under high voltage transmission lines. Theoretical background information on capacitive spark discharges and fuel ignition processes is given. Laboratory experiments were conducted to test the dependence of fuel ignition on three parameters: impedance in discharge path, multiple discharges, and larger electrode shapes. The results of these tests are discussed in terms of fuel ignition possibilities under high voltage transmission lines.

1983-03-01

479

Fractal dimension determination of sol-gel powders using transmission electron microscopy images  

Energy Technology Data Exchange (ETDEWEB)

SiO{sub 2}, TiO{sub 2} and AlO(OH) powders obtained by the sol-gel method were investigated by transmission electron microscopy. The mass-radius relation was used to determine the fractal dimensions from the images. These fractal dimensions were corrected in order to obtain the powder fractal dimensions. The results indicate a good fractal behavior and high fractal dimensions.

2004-09-15

480

Electricity supply in the United Kingdom. Brief details and statistics  

Energy Technology Data Exchange (ETDEWEB)

Statistical detail is given of the electricity generation and transmission systems in the UK. Breakdown by type of station, by fuel and the proportion generated by others apart from the generating or area boards is presented. Figures are provided for the various high voltage transmission lines in terms of route and circuit length as well as the number of towers and the capacity of mains transformers.

1987-06-01

481

Aspects of landscaping in case of constructing new HV transmission line. Landschaftsschutzaspekte beim Bau einer neuen Hochspannungsleitung  

Energy Technology Data Exchange (ETDEWEB)

When constructing new high-voltage transmission lines landscape aspects play a more and more important role. The project described is particularly interesting as it demonstrates that it is possible to find acceptable solutions for everyone if all partners are prepared to make concessions. The article also describes a new concept for the connection of concrete tower elements. (orig.).

1991-01-23

482

Analysis of microstructure of materials using a combination of a focused ion beam and transmission electron microscopy  

Energy Technology Data Exchange (ETDEWEB)

Recent development in application of a focused ion beam (FIB) technique to preparation of thin foil specimens for transmission electron microscopy (TEM) observation has been reviewed. Combined technique of FIB/TEM enables one to analyze those microstructures which have been almost impossible or very difficult to analyze so far. (author)

2002-03-01

483

Altered GABAA receptor-mediated synaptic transmission disrupts the firing of gonadotropin-releasing hormone neurons in male mice under conditions that mimic steroid abuse  

UK PubMed Central (United Kingdom)

Gonadotropin–releasing hormone (GnRH) neurons are the central regulators of reproduction. GABAergic transmission plays a critical role in pubertal activation of pulsatile GnRH secretion....Full Text Available

2010-05-12

484

Active RF filter for high voltage transmission lines  

Energy Technology Data Exchange (ETDEWEB)

A new technique is described in this paper for a general active radio frequency (RF) filter trap that can be used for suppressing noise or interference on high voltage (HV) transmission lines. The technique exploits the Miller effect of an RF amplifier in conjunction with a special sensing circuit, and is potentially far more economical to implement than conventional techniques that use passive HV filter components.

1993-07-01

485

A fuzzy logic based fault classification approach using current samples only  

Energy Technology Data Exchange (ETDEWEB)

An approach for classification of transmission line faults is presented. The approach is based on fuzzy logic and requires the consideration of the samples of three phase currents at one end of transmission line. To illustrate the effectiveness of the proposed approach extensive simulation studies, using EMTP and MATLAB, have been carried out for different types of fault considering wide variations in the operating conditions. (author)

2007-04-15

486

The concept of power correction techniques and its use in the reactor regulation and protection systems in Indian PHWRs  

International Nuclear Information System (INIS)

Reactor Power Measurement is an essential part of the Reactor Power Control Loop in PHWRs. None of the available power measuring sensor offers characteristics which allow their direct use in the Reactor Power Control Loop. Thermal power, which is considered as relatively accurate, suffers from measurement delays and is used only as reference. Neutronic power sensors like Ion Chambers and Self Powered Neutron Detectors (SPNDs) which sense instantaneous power suffer from inaccuracies. A technique is required which makes use of both types-reference power and instantaneous power to extract real power information from the signals. This paper describes techniques to calibrate (correct) neutronic power that with the thermal reference ...

2010-02-01

487

Pricing of constraints - the England & Wales experience  

Energy Technology Data Exchange (ETDEWEB)

The existence, in real-time, of transmission constraints, demand forecasting errors, generator failures, and other factors impose additional costs through the need to run more expensive generation. These costs can appear as a significant component of the wholesale price to demand served by electricity markets operated over transmission networks. In the England & Wales Pool these costs are passed through directly to supply companies. The Transmission System Operator ({open_quotes}TSO{close_quotes}) can exert significant influence on these costs through improved availability of transmission circuits and through appropriate investment, but has no incentive to do so. Since the inception of the Pool, these costs have increased in level and volatility, and have proved difficult to hedge. In response, St Clements Services were instrumental in assisting Pool members to develop an {open_quotes}Uplift ...

1996-03-01

488

Groundwater travel time uncertainty analysis. Sensitivity of results to model geometry, and correlations and cross correlations among input parameters  

Energy Technology Data Exchange (ETDEWEB)

This study examines the sensitivity of the travel time distribution predicted by a reference case model to (1) scale of representation of the model parameters, (2) size of the model domain, (3) correlation range of log-transmissivity, and (4) cross correlations between transmissivity and effective thickness. The basis for the reference model is the preliminary stochastic travel time model previously documented by the Basalt Waste Isolation Project. Results of this study show the following. The variability of the predicted travel times can be adequately represented when the ratio between the size of the zones used to represent the model parameters and the log-transmissivity correlation range is less than about one-fifth. The size of the model domain and the types of boundary conditions can have a strong impact on the distribution of travel times. Longer log-transmissivity correlation ranges cause larger ...

1985-03-01

489

Accuracy of LLP system and lightning frequency map evaluated from transmission line faults; Rakurai ichi hyotei system no seido to rakurai hindo map no sodensen torippu jiko ni motozuku hyoka  

Energy Technology Data Exchange (ETDEWEB)

Accuracy of an LLP system and a lightning frequency map is evaluated by using transmission line faults in Hokuriku area from November in 1993 to October in 1996. The accuracy and efficiency of the system were calculated by statistical methods. From the above results, the lightning frequency map with 10 minutes meshes was proved capable of replacing the Isokeraunic Level Map with 15 minutes meshes used now for lightning protection design. However, the correlation between the number of detected lightning flashes and transmission line faults in each mesh was found to be week. This result suggests that more detailed analysis taking account of the length of transmission lines in each mesh is necessary. The correlation is stronger in winter than in summer, despite the fact that there is difference in the lightning current distribution in each mesh in winter. This characteristic can be explained if upward flashes from ...

1997-10-20

490

The electric power industry in Czechoslovakia - development and present state. Entwicklung und gegenwaertiger Stand der tschechoslowakischen Elektrizitaetswirtschaft  

Energy Technology Data Exchange (ETDEWEB)

Some general topical information (generating capacity and electric power generation, development and structure of electric power consumption, frequency and peak load, exchange of electricity) is followed by an account of the situation of coal-fired power plants, hydroelectric power plants and nuclear power plants, and a brief discussion of the environmental situation (emissions and wastes, immissions, and air pollution abatement measures for power plants). (orig./UA).

1992-11-02

491

Sound transmission loss of composite sandwich panels  

Science.gov (United States)

Light composite sandwich panels are increasingly used in automobiles, ships and aircraft, because of the advantages they offer of high strength-to-weight ratios. However, the acoustical properties of these light and stiff structures can be less desirable than those of equivalent metal panels. These undesirable properties can lead to high interior noise levels. A number of researchers have studied the acoustical properties of honeycomb and foam sandwich panels. Not much work, however, has been carried out on foam-filled honeycomb sandwich panels. In this dissertation, governing equations for the forced vibration of asymmetric sandwich panels are developed. An analytical expression for modal densities of symmetric sandwich panels is derived from a sixth-order governing equation. A boundary element analysis model for the sound transmission loss of symmetric sandwich panels is proposed. Measurements of the modal density, total loss factor, radiation loss factor, and ...

2009-01-01

492

Commission for Energy regulation (CRE) - Activity report june 2008; Commission de regulation de l'energie (CRE) - Rapport d'activite juin 2008  

Energy Technology Data Exchange (ETDEWEB)

CRE is the French commission for energy regulation. CRE's remit is to assist in ensuring the proper operation of the electricity and natural gas markets for the benefit of the end-user. In particular, CRE ensures that the conditions of access to electricity and natural gas transmission and distribution systems do not hinder the development of competition. It monitors, for the electricity and natural gas sectors, all transactions made between suppliers, traders and producers, all transactions made on the organised markets and cross-border trading. It ensures that suppliers, traders and producers propose offers that are consistent with their financial and technical constraints. It monitors the implementation of and compliance with regulations giving consumers the right to choose their supplier in a competitive market, and allowing new suppliers to enter the market. This document is the 2008 activity report of CRE. Content: A - How CRE works: CRE regulatory ...

2008-07-01

493

Wind power in Poland; Gerangel an der Ostsee-Kueste  

Energy Technology Data Exchange (ETDEWEB)

Poland intends to construct 2,000 MW of wind power systems during the next four years. This is the start of the Polish wind power industry. (orig.)

2006-08-15

494

Power Management for Real-Time Systems  

Science.gov (United States)

... CycleSim models an IBM PowerPC 405GP system-on-a-chip and includes a cycle-accurate, event-based power model of the processor core and ...

2004-07-01

495

Power Analyzer for Pocket Computing (PAPC)  

Science.gov (United States)

... Those functions are fundamental routines to build a power model for more complex circuits or functional blocks. ... 21 of 54 6. Memory Power Model ...

2004-01-01

496

Global Vigilance, Reach, and Power? Made Possible only ...  

Science.gov (United States)

... 4. TITLE AND SUBTITLE Global Vigilance, Reach, and Power? Made Possible only with a Robust 5a. ... Global Vigilance, Reach, and Power? ...

2005-05-17

497

The electron cyclotron absorption diagnostic for the JET pumped divertor plasma  

International Nuclear Information System (INIS)

We present the design of a diagnostic system to measure electron cyclotron absorption at the second harmonic E-mode resonance in the JET pumped divertor plasma. The diagnostic will measure transmission as a function of frequency along one or more sightlines from which the spatial profile of the n_eT_e product will be deduced. The divertor is briefly described, and the electron cyclotron resonance physics relevant to this measurement is reviewed. The problems of measuring transmission using an oversized transmission system are discussed and the chosen measurement technique, a swept frequency interferometer using a coherent radiation source, is described. A prototype of the instrument has been assembled to test the measurement technique. Some data demonstrating the instrument's characteristics are presented. The nonresonant losses, which may affect the interpretation of the measurement, are also discussed. (orig.).

1993-03-01

498

Final report: technical contributions to the development of incipient fault detection/location instrumentation  

Energy Technology Data Exchange (ETDEWEB)

The transmission of electrical energy by use of underground cables is increasing. Fault location techniques have certain limitations; incipient fault detection and location would help reduce the maintenance cost of these lines as well as improve the reliability of service. The report discusses some test results related to RF-probing techniques applied to high-voltage transmission lines. The high-frequency losses and attenuation in high-voltage cables places certain ultimate limitations on RF-probing techniques for incipient fault detection. Time-domain reflectrometry methods were employed to assess the RF-transmission properties of high-voltage cables at frequencies as high as 6 GHz. Fast-Fourier-transform deconvolution was used to obtain loss measurements as a function of frequency. The loss mechanisms were identified. The measurement hardware and methods are discussed as well as analysis approach leading to the ...

1986-04-01

499

Evaluation of Reports on Environmental Measurements of Electromagnetic Fields Generated by High Voltage Transmission Lines and Substations  

International Nuclear Information System (INIS)

This paper presents some situations, in which measurements of electromagnetic fields generated by transmission lines and substations should be performed. The range of measurements may differ, but maximum values of electric and magnetic fields and flux density must be identified in all situations. The area with electric field exceeding 1 kV/m should be identified as well. The author also presents basic requirements to be met by the measurement technique. These requirements are specified according to the national standard. Special attention should be paid to the identification of the spatial distribution of electric field and flux density generated in the vicinity of high voltage transmission lines. To verify the measurement results, it is necessary to calculate the distribution of both aforesaid field components. For environmental protection purposes, it is also proposed that the report should include measurements of electromagnetic fields of 50 ...

2007-01-01